Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2023-10-16 08:32:06
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2179.80 | 437.52 | 437.52 |
Net Site Energy | 2179.80 | 437.52 | 437.52 |
Total Source Energy | 5733.11 | 1150.72 | 1150.72 |
Net Source Energy | 5733.11 | 1150.72 | 1150.72 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 374.69 | 422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 150.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 232.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 51.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 91.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 138.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1617.96 | 561.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 374.69 | 422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 150.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 232.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 51.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 91.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 138.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 374.69 | 422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 150.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 232.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 51.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 91.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 138.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 123.83 | 112.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 324.75 | 112.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 123.83 | 112.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 324.75 | 112.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1617.961 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1617.961 | 100.00 |
Total On-Site and Utility Electric Sources | 1617.961 | 100.00 |
Total Electricity End Uses | 1617.961 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 548.33 |
Time Setpoint Not Met During Occupied Cooling | 111.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3158.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.6636 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.6636 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.6636 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 6.6636 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.6636 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-JAN-07:10 | 02-FEB-12:20 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 212408.91 | 148130.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8334.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 243.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7525.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 10500.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 255304.87 | 158631.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 212408.91 | 148130.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 8334.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 243.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7525.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 10500.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 1186.64 | 458.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 476.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 736.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 37.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 290.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 150.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5124.08 | 609.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 238.18 | 92.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 95.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 58.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 30.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1028.48 | 122.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 238.18 | 92.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 95.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 58.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 30.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1028.48 | 122.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.94 | 0.255285 | 0.217000 | 0.637060 | 0.680759 | 0.500000 | 0.001492 |
CORE_MID VAV BOX COMPONENT | 2.15 | 0.348686 | 0.296000 | 0.636212 | 0.929831 | 0.500000 | 0.001093 |
CORE_TOP VAV BOX COMPONENT | 2.23 | 0.335741 | 0.285000 | 0.636188 | 0.895310 | 0.500000 | 0.001135 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.780497 | 0.202424 | 0.191000 | 0.149075 | 0.539798 | 0.500000 | 0.001882 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.846364 | 0.118178 | 0.100000 | 0.084636 | 0.315142 | 0.500000 | 0.003224 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.03 | 0.152680 | 0.130000 | 0.134523 | 0.407145 | 0.500000 | 0.002495 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.931398 | 0.107382 | 0.091000 | 0.084757 | 0.300000 | 0.500000 | 0.003548 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.577049 | 0.273793 | 0.245000 | 0.141377 | 0.730114 | 0.500000 | 0.001392 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.689108 | 0.145147 | 0.123000 | 0.084760 | 0.387058 | 0.500000 | 0.002625 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.821376 | 0.192350 | 0.163000 | 0.133884 | 0.512933 | 0.500000 | 0.001981 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.734530 | 0.136162 | 0.116000 | 0.085205 | 0.363099 | 0.500000 | 0.002798 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.614211 | 0.257227 | 0.219000 | 0.134512 | 0.685939 | 0.500000 | 0.001481 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.833593 | 0.319970 | 0.500000 | 0.003175 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.943571 | 0.167440 | 0.142000 | 0.133987 | 0.446507 | 0.500000 | 0.002275 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.863901 | 0.115772 | 0.098000 | 0.084662 | 0.308724 | 0.500000 | 0.003291 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 20294.53 |
CORE_MID VAV BOX REHEAT COIL | 28520.54 |
CORE_TOP VAV BOX REHEAT COIL | 49039.24 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 24863.92 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 16140.09 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 24629.74 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 16285.44 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 18382.76 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12007.29 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 18190.79 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 12134.39 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 19540.02 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 12738.51 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 19325.54 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 12868.63 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.88 | 1.08 | 5.76 | 2.39 | 5.03 | 5.03 | 0.300000 | 0.474917 | 5.03 |
PACU_VAV_MID | 2.70 | 1.07 | 5.40 | 2.92 | 4.49 | 4.49 | 0.300000 | 0.650202 | 4.49 |
PACU_VAV_TOP | 2.91 | 1.09 | 5.83 | 4.11 | 5.16 | 5.16 | 0.300000 | 0.795953 | 5.16 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.03 |
PACU_VAV_MID_OA_CONTROLLER | 4.49 |
PACU_VAV_TOP_OA_CONTROLLER | 5.16 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.03 | 105026.34 | 0.759643 | 1.68 | 35005.28 | 0.759643 |
PACU_VAV_MID COOLING COIL | 4.49 | 97046.02 | 0.746552 | 1.50 | 32345.44 | 0.746552 |
PACU_VAV_TOP COOLING COIL | 5.16 | 108092.28 | 0.758794 | 1.72 | 36027.16 | 0.758794 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 38238.80 |
PACU_VAV_MID HEATING COIL | 40693.17 |
PACU_VAV_TOP HEATING COIL | 39572.31 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.03 |
PACU_VAV_MID FAN | 4.49 |
PACU_VAV_TOP FAN | 5.16 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 31.498 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7597 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7464 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.9868 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2198 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2318 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2198 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2318 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.082 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.106 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7793 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.474 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.237 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.474 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.236 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.31468885E-12 | 0.58742715E-14 | -0.96802560E-13 | 0.16792992E-15 |
43 | 6 | 0.28872123E-07 | 0.21416477E-09 | 0.66123209E-08 | -0.13627602E-12 |
44 | 5 | -0.19112651E-03 | 0.18301600E-05 | -0.98293898E-04 | 0.65360363E-08 |
45 | 4 | 0.29333920 | 0.88954174E-03 | 0.10011225 | -0.33739231E-04 |
46 | 3 | -7.2899446 | 0.27524297E-01 | -2.3459205 | 0.29124746E-01 |
47 | 2 | 40.949034 | 0.97737712E-01 | 15.293846 | -0.33420785 |
48 | 1 | -80.605481 | 0.44056480E-01 | -29.167461 | 1.0798913 |
49 | 0 | 46.824338 | 0.88531397E-03 | 16.290617 | |
50 | 7 | -0.30618227E-12 | 0.12614254E-14 | -0.97456297E-13 | 0.16278992E-15 |
51 | 6 | 0.29029541E-07 | 0.21075172E-09 | 0.66470638E-08 | -0.13712239E-12 |
52 | 5 | -0.19192439E-03 | 0.17992386E-05 | -0.98693455E-04 | 0.65698920E-08 |
53 | 4 | 0.29427084 | 0.87374093E-03 | 0.10044741 | -0.33870887E-04 |
54 | 3 | -7.3083902 | 0.27014250E-01 | -2.3513943 | 0.29215155E-01 |
55 | 2 | 41.009863 | 0.95860246E-01 | 15.316286 | -0.33488536 |
56 | 1 | -80.652088 | 0.43184114E-01 | -29.187576 | 1.0808846 |
57 | 0 | 46.824338 | 0.86726935E-03 | 16.290137 | |
58 | 7 | -0.27636417E-12 | 0.12990813E-14 | -0.82271001E-13 | 0.80162457E-16 |
59 | 6 | 0.26158967E-07 | 0.26982527E-09 | 0.60134738E-08 | -0.12176112E-12 |
60 | 5 | -0.17726759E-03 | 0.23481051E-05 | -0.91336903E-04 | 0.59516496E-08 |
61 | 4 | 0.27699908 | 0.11597994E-02 | 0.94241662E-01 | -0.31446529E-04 |
62 | 3 | -6.9660490 | 0.36401088E-01 | -2.2498311 | 0.27538282E-01 |
63 | 2 | 39.880486 | 0.13088809 | 14.898993 | -0.32230875 |
64 | 1 | -79.786295 | 0.59645051E-01 | -28.813249 | 1.0624348 |
65 | 0 | 46.824344 | 0.12114519E-02 | 16.299244 | |
66 | 7 | -0.19168505E-08 | -0.51383041E-15 | 0.68469349E-14 | -0.93730203E-16 |
67 | 6 | 0.61617009E-05 | 0.42103975E-08 | 0.31882761E-02 | -0.26745931E-04 |
68 | 5 | -0.44250412E-03 | 0.24935927E-05 | -0.22363399 | 0.19553507E-02 |
69 | 4 | 0.10175003E-01 | 0.11350545E-03 | 4.8280370 | -0.45250478E-01 |
70 | 3 | -0.89340535E-01 | 0.90260008E-03 | -38.012894 | 0.39855955 |
71 | 2 | 0.31721614 | 0.15015396E-02 | 116.46736 | -1.4177174 |
72 | 1 | -0.45784565 | 0.45746588E-03 | -143.89754 | 2.0488794 |
73 | 0 | 0.22322007 | 0.11078117E-04 | 60.838472 | |
74 | 7 | -0.18147523E-08 | -0.43765969E-15 | 0.59880535E-14 | -0.82299290E-16 |
75 | 6 | 0.64914511E-05 | 0.44428550E-08 | 0.31873263E-02 | -0.26737964E-04 |
76 | 5 | -0.46689866E-03 | 0.26323880E-05 | -0.22358000 | 0.19548742E-02 |
77 | 4 | 0.10740407E-01 | 0.11982633E-03 | 4.8271378 | -0.45241835E-01 |
78 | 3 | -0.94318369E-01 | 0.95296379E-03 | -38.007814 | 0.39850340 |
79 | 2 | 0.33490849 | 0.15853305E-02 | 116.45748 | -1.4175852 |
80 | 1 | -0.48339250 | 0.48313585E-03 | -143.89172 | 2.0487838 |
81 | 0 | 0.23567793 | 0.11657420E-04 | 60.838472 | |
82 | 7 | -0.19168505E-08 | -0.51383063E-15 | 0.68469351E-14 | -0.93730206E-16 |
83 | 6 | 0.61617009E-05 | 0.42103975E-08 | 0.31882761E-02 | -0.26745931E-04 |
84 | 5 | -0.44250412E-03 | 0.24935927E-05 | -0.22363399 | 0.19553507E-02 |
85 | 4 | 0.10175003E-01 | 0.11350545E-03 | 4.8280370 | -0.45250478E-01 |
86 | 3 | -0.89340535E-01 | 0.90260008E-03 | -38.012894 | 0.39855955 |
87 | 2 | 0.31721614 | 0.15015396E-02 | 116.46736 | -1.4177174 |
88 | 1 | -0.45784565 | 0.45746588E-03 | -143.89754 | 2.0488794 |
89 | 0 | 0.22322007 | 0.11078117E-04 | 60.838472 | |
90 | 7 | -0.18146260E-08 | -0.43662845E-15 | 0.62700332E-14 | -0.82012168E-16 |
91 | 6 | 0.64918823E-05 | 0.44431590E-08 | 0.31873251E-02 | -0.26737954E-04 |
92 | 5 | -0.46693053E-03 | 0.26325692E-05 | -0.22357993 | 0.19548736E-02 |
93 | 4 | 0.10741146E-01 | 0.11983458E-03 | 4.8271366 | -0.45241823E-01 |
94 | 3 | -0.94324870E-01 | 0.95302955E-03 | -38.007807 | 0.39850333 |
95 | 2 | 0.33493160 | 0.15854399E-02 | 116.45746 | -1.4175850 |
96 | 1 | -0.48342587 | 0.48316934E-03 | -143.89172 | 2.0487836 |
97 | 0 | 0.23569420 | 0.11658190E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.342_SHGC_EAST_0.379 | 35 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
2 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 36 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
3 | WINDOW_U_0.342_SHGC_WEST_0.379 | 37 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
4 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 38 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2394E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2460E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3767E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3823E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2411E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2870E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3624E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3867E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1708 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.2019E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1948 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1049 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1170 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0052E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8200E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8082E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2396E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2471E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3768E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3836E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2426E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2948E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3621E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3864E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.7422E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4954E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.3751E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2027E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.4302E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7446E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6593E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6671E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9282E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.9549E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.6202E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.6395E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2150E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.2217E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0914E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0997E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6891E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7473E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9172E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9641E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3994E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4341E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3621E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3864E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.4956E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5757E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4661E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9646E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1861E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3440E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8200E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8082E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6889E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7478E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9165E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9629E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3980E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4286E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3624E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3867E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.6951E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9834E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0577E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5557E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5985E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3517E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6593E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6671E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2657E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.3430E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7826E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.8682E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7100E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7406E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0916E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0999E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1701 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1107 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1908 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1254 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1254 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.3337E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.4952E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.5650E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.4859E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.3484E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.1427E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.0692E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.2537E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.6396E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.5541E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.6039E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.1179E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.3521E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0190E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6319E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.7391E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9541E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.4952E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.5650E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.4730E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.8600E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.8687E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4523E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.4470E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.2637E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.5542E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6040E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1701 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1106 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1908 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1254 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1254 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.3329E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.4947E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.5647E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.4858E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.3481E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.1425E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.0689E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.2533E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.6392E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.5536E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.6036E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.1181E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.3520E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0191E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6317E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.7389E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9540E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.4947E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.5647E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.4730E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.8598E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.8687E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4521E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.4466E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.2634E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.5536E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.6037E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 38861.23274 | 38861.23274 | 2.93576 | 2.93576 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 10951.06253 | 10951.06253 | 0.48431 | 0.48431 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 28485.61769 | 28485.61769 | 2.14937 | 2.14937 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 20117.78754 | 20117.78754 | 0.89528 | 0.89528 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 29304.47441 | 29304.47441 | 2.23224 | 2.23224 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 31.09400 | 1.53649E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 34491.34680 | 34491.34680 | 1.53938 | 1.53938 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9233.81583 | 9233.81583 | 0.70347 | 0.70347 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 17447.80516 | 17447.80516 | 0.78050 | 0.78050 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11109.45094 | 11109.45094 | 0.84636 | 0.84636 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 25.67033 | 1.53549E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 11325.62735 | 11325.62735 | 0.50665 | 0.50665 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13582.78843 | 13582.78843 | 1.03479 | 1.03479 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53646E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 17283.74911 | 17283.74911 | 0.77315 | 0.77315 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12225.65705 | 12225.65705 | 0.93140 | 0.93140 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 11427.44773 | 11427.44773 | 0.51121 | 0.51121 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7198.52825 | 7198.52825 | 0.54838 | 0.54838 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 12905.74918 | 12905.74918 | 0.57705 | 0.57705 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9045.89855 | 9045.89855 | 0.68911 | 0.68911 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 26.27100 | 1.53560E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 8429.25240 | 8429.25240 | 0.37692 | 0.37692 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10782.14108 | 10782.14108 | 0.82138 | 0.82138 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53648E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 12771.28442 | 12771.28442 | 0.57102 | 0.57102 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9642.17143 | 9642.17143 | 0.73453 | 0.73453 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 28.39100 | 1.53599E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 8518.28343 | 8518.28343 | 0.38091 | 0.38091 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8062.30977 | 8062.30977 | 0.61421 | 0.61421 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 13717.56918 | 13717.56918 | 0.61338 | 0.61338 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10942.09231 | 10942.09231 | 0.83359 | 0.83359 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 25.03433 | 1.53537E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 8942.24274 | 8942.24274 | 0.39987 | 0.39987 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 12385.67621 | 12385.67621 | 0.94357 | 0.94357 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53644E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 13567.32602 | 13567.32602 | 0.60664 | 0.60664 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11339.93037 | 11339.93037 | 0.86390 | 0.86390 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 9033.38644 | 9033.38644 | 0.40396 | 0.40396 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 72980.48 | 5.03290 | 5.03290 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 42945.85 | 2.39021 | 2.39021 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:40:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 65880.37 | 4.48957 | 4.48957 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 43028.07 | 2.91913 | 2.91913 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:30:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 74517.56 | 5.16473 | 5.16473 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 42681.37 | 4.11088 | 4.11088 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.93576 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25528 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21700 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63706 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68076 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.49245E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20294.52698 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.14937 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34869 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29600 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63621 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.92983 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09267E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 28520.54385 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.23224 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33574 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28500 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63619 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89531 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.13480E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 49039.24312 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78050 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20242 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19100 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14907 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53980 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.88218E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24863.92358 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84636 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11818 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.46364E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31514 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.22394E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16140.09333 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.03479 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15268 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13452 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40715 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.49542E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24629.73822 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93140 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10738 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.10000E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47572E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.54809E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16285.43948 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.57705 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27379 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24500 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14138 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73011 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.39156E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18382.76235 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68911 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14515 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12300 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47603E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38706 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.62493E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12007.28522 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82138 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19235 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16300 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13388 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51293 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.98076E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18190.78810 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73453 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13616 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11600 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52055E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36310 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.79813E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12134.39409 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61421 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25723 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21900 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13451 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68594 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.48118E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19540.02039 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83359 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31997 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.17530E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12738.50909 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.94357 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16744 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14200 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13399 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44651 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.27544E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19325.53585 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86390 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11577 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.80000E-002 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.46623E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30872 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.29096E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12868.62504 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.87891 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08229 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.75782 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.39021 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.03290 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.03290 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.47492 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.70232 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07440 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.40464 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.91913 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.48957 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.48957 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.65020 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.91265 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08918 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.82529 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 4.11088 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.16473 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.16473 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.79595 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.03290 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.48957 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.16473 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.03290 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.03290 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 105026.34149 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.75964 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.67746 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35005.27962 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.75964 |
152 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 38238.79782 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.03290 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.48957 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.48957 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 97046.01768 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74655 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.49637 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32345.43769 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74655 |
161 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 40693.17041 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.48957 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.16473 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.16473 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 108092.28432 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.75879 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.72141 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 36027.15836 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.75879 |
170 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 39572.30595 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.16473 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 104233.47 | 355659.37 | 11.39 | 2.90 | 3.26 | 3.44 | 3.60 | 9.91 | 11.13 | 11.73 | 12.27 | 5.5523 | 4.4290 | 2.9818 | 1.2180 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 96437.82 | 329059.51 | 11.46 | 2.92 | 3.28 | 3.46 | 3.61 | 9.96 | 11.21 | 11.81 | 12.32 | 4.9529 | 3.9453 | 2.6553 | 1.0988 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 107287.93 | 366081.63 | 11.40 | 2.90 | 3.26 | 3.44 | 3.60 | 9.91 | 11.14 | 11.73 | 12.27 | 5.6977 | 4.5465 | 3.0613 | 1.2504 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.220 | 0.209 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.232 | 0.219 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.220 | 0.209 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.232 | 0.219 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.2566823521E-002 | 2.1232777475E-002 | Pass | Pass | 0.4822470615 | 0.4918715019 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1328246362 | 8.7615843826E-002 | Pass | Pass | 0.4991243384 | 0.4841051451 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.5554572237E-002 | 4.0234799881E-002 | Pass | Pass | 0.4894210328 | 0.4738307986 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.8629579781E-002 | 3.8962576457E-002 | Pass | Pass | 0.4913073705 | 0.4706672554 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 8.5385649519E-003 | 1.0721106202E-002 | Pass | Pass | 1.2067207052 | 3.0877061961 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1260655853 | 0.1178675901 | Pass | Pass | 20.1035864552 | 114.0674305703 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4739967244 | 0.4296725239 | Pass | Pass | 24.1258739321 | 89.5952113205 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5252859924 | 0.4976923694 | Pass | Pass | 29.9991705547 | 106.9052369025 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4503103036 | 0.4560424366 | Pass | Pass | 44.1160044887 | 189.0647768137 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5318233768 | 0.4975164926 | Pass | Pass | 51.8570260205 | 275.2341898803 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3304447883 | 0.2997133304 | Pass | Pass | 12.9035847706 | 40.3780439111 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3841566866 | 0.3520339211 | Pass | Pass | 16.8675576687 | 57.2902630511 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3329122749 | 0.3199440194 | Pass | Pass | 19.8537097005 | 77.5149793651 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3921959756 | 0.3546261929 | Pass | Pass | 29.2051341530 | 147.1761631787 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3434294783 | 0.3147596040 | Pass | Pass | 17.3736997200 | 70.7177576021 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3871310359 | 0.3672511917 | Pass | Pass | 24.0340056427 | 91.9038314274 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3445280897 | 0.3448260674 | Pass | Pass | 17.0830354142 | 65.8601378549 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3946938454 | 0.3660904264 | Pass | Pass | 17.6003777369 | 61.7724623405 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3601.31 | 232.91 | 0.00 | 1717.92 | 845.71 | 6397.84 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.212 | 0.220 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.223 | 0.232 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.212 | 0.220 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.223 | 0.232 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.342_SHGC_NORTH_0.379 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.342_SHGC_EAST_0.379 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.342_SHGC_WEST_0.379 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.342_SHGC_EAST_0.379 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.342_SHGC_EAST_0.379 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.342_SHGC_WEST_0.379 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.342_SHGC_WEST_0.379 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.342_SHGC_NORTH_0.379 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.342_SHGC_EAST_0.379 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.342_SHGC_WEST_0.379 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 1.943 | 0.380 | 0.418 | |||||||||||||||||
North Total or Average | 195.79 | 1.943 | 0.380 | 0.418 | |||||||||||||||||
Non-North Total or Average | 456.84 | 1.943 | 0.380 | 0.418 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.12 | 0.0000 | Y | 6.77 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.96 | 0.0000 | Y | 4.26 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.72 | 0.0000 | Y | 6.67 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.86 | 0.0000 | Y | 4.25 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.05 | 0.0000 | Y | 6.76 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.92 | 0.0000 | Y | 4.26 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.69 | 0.0000 | Y | 6.66 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.82 | 0.0000 | Y | 4.24 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.12 | 0.0000 | Y | 6.77 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.96 | 0.0000 | Y | 4.26 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.72 | 0.0000 | Y | 6.67 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.86 | 0.0000 | Y | 4.25 |
Interior Lighting Total | 6.6636 | 4982.19 | 33199.39 | 232.62 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 42.24 | 42.24 | 4.47 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.63 | 62.93 | 4.82 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.63 | 47.43 | 41.98 | |
Exterior Lighting Total | 5686.19 | 51.26 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 105026.34 | 79782.53 | 25243.81 | 0.76 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 97046.02 | 72449.92 | 24596.10 | 0.75 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 108092.28 | 82019.75 | 26072.53 | 0.76 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 104233.5 | 2.90 | 9.91 | N/A | N/A | 11.39 | |
PACU_VAV_MID COOLING COIL | 96437.8 | 2.92 | 9.96 | N/A | N/A | 11.46 | |
PACU_VAV_TOP COOLING COIL | 107287.9 | 2.90 | 9.91 | N/A | N/A | 11.40 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 20294.53 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 28520.54 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 49039.24 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 24863.92 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16140.09 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 24629.74 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16285.44 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18382.76 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12007.29 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18190.79 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12134.39 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 19540.02 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12738.51 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 19325.54 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12868.63 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 38238.80 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 40693.17 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 39572.31 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.03 | 11567.92 | 2298.46 | 1.00 | 1.13 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.49 | 10386.11 | 2313.39 | 1.00 | 1.13 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.16 | 11870.94 | 2298.46 | 1.00 | 1.13 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 104233.47 | 2.90 | 9.91 | 11.39 | 5.5523 | 3.26 | 11.13 | 4.4290 | 3.44 | 11.73 | 2.9818 | 3.60 | 12.27 | 1.2180 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 96437.82 | 2.92 | 9.96 | 11.46 | 4.9529 | 3.28 | 11.21 | 3.9453 | 3.46 | 11.81 | 2.6553 | 3.61 | 12.32 | 1.0988 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 107287.93 | 2.90 | 9.91 | 11.40 | 5.6977 | 3.26 | 11.14 | 4.5465 | 3.44 | 11.73 | 3.0613 | 3.60 | 12.27 | 1.2504 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 38861.23 | 38861.23 | 39.51 | 2.936 | 2.936 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00881 | 23.36 | 0.01535 | 0.425 | 0.00 |
CORE_MID | 28485.62 | 28485.62 | 28.96 | 2.149 | 2.149 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 23.36 | 0.01535 | 0.425 | 0.00 |
CORE_TOP | 29304.47 | 29304.47 | 29.80 | 2.232 | 2.232 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00891 | 31.09 | 0.01536 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9233.82 | 9233.82 | 44.54 | 0.703 | 0.703 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00920 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11109.45 | 11109.45 | 84.64 | 0.846 | 0.846 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00889 | 25.67 | 0.01535 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13582.79 | 13582.79 | 65.51 | 1.035 | 1.035 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00898 | 30.93 | 0.01536 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12225.66 | 12225.66 | 93.15 | 0.931 | 0.931 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00885 | 29.54 | 0.01536 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7198.53 | 7198.53 | 34.72 | 0.548 | 0.548 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00914 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9045.90 | 9045.90 | 68.91 | 0.689 | 0.689 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00884 | 26.27 | 0.01536 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10782.14 | 10782.14 | 52.00 | 0.821 | 0.821 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00893 | 31.02 | 0.01536 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9642.17 | 9642.17 | 73.46 | 0.735 | 0.735 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00882 | 28.39 | 0.01536 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8062.31 | 8062.31 | 38.88 | 0.614 | 0.614 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00921 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10942.09 | 10942.09 | 83.36 | 0.834 | 0.834 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00886 | 25.03 | 0.01535 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12385.68 | 12385.68 | 59.74 | 0.944 | 0.944 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00898 | 30.85 | 0.01536 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11339.93 | 11339.93 | 86.40 | 0.864 | 0.864 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00884 | 29.54 | 0.01536 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 10951.06 | 10951.06 | 11.13 | 0.484 | 0.484 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
CORE_MID | 20117.79 | 20117.79 | 20.45 | 0.895 | 0.895 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
CORE_TOP | 34491.35 | 34491.35 | 35.07 | 1.539 | 1.539 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 17447.81 | 17447.81 | 84.15 | 0.780 | 0.780 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00752 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11325.63 | 11325.63 | 86.28 | 0.507 | 0.507 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 17283.75 | 17283.75 | 83.36 | 0.773 | 0.773 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00752 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11427.45 | 11427.45 | 87.06 | 0.511 | 0.511 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 12905.75 | 12905.75 | 62.24 | 0.577 | 0.577 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8429.25 | 8429.25 | 64.22 | 0.377 | 0.377 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12771.28 | 12771.28 | 61.60 | 0.571 | 0.571 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8518.28 | 8518.28 | 64.90 | 0.381 | 0.381 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 13717.57 | 13717.57 | 66.16 | 0.613 | 0.613 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00749 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8942.24 | 8942.24 | 68.13 | 0.400 | 0.400 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00748 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 13567.33 | 13567.33 | 65.44 | 0.607 | 0.607 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00749 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9033.39 | 9033.39 | 68.82 | 0.404 | 0.404 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00749 | -26.20 | 0.00036 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.03 | 5.03 | 2.39 | 2.39 | 5.0329 | 2.3902 | 5.0329 | 0.4749 | 0.3000 |
PACU_VAV_MID | 4.49 | 4.49 | 2.92 | 2.92 | 4.4896 | 2.9191 | 4.4896 | 0.6502 | 0.3000 |
PACU_VAV_TOP | 5.16 | 5.16 | 4.11 | 4.11 | 5.1647 | 4.1109 | 5.1647 | 0.7960 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 20294.527 | 20294.527 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20294.53 | 15428.56 | 0.484314 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3289 | 10951.06 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 28520.544 | 28520.544 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 28520.54 | 28520.54 | 0.895281 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3289 | 20117.79 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 49039.243 | 49039.243 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 49039.24 | 49039.24 | 1.539378 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3290 | 34491.35 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 24863.924 | 24863.924 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24863.92 | 24863.92 | 0.780497 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00751964 | 46.4116 | 17447.81 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 16140.093 | 16140.093 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16140.09 | 16140.09 | 0.506650 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00750735 | 46.3370 | 11325.63 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 24629.738 | 24629.738 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24629.74 | 24629.74 | 0.773146 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00751538 | 46.3856 | 17283.75 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 16285.439 | 16285.439 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16285.44 | 16285.44 | 0.511212 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00751145 | 46.3620 | 11427.45 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 18382.762 | 18382.762 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18382.76 | 18382.76 | 0.577049 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00764732 | 47.1861 | 12905.75 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 12007.285 | 12007.285 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12007.29 | 12007.29 | 0.376918 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00764098 | 47.1477 | 8429.25 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 18190.788 | 18190.788 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18190.79 | 18190.79 | 0.571022 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00764354 | 47.1631 | 12771.28 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 12134.394 | 12134.394 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12134.39 | 12134.39 | 0.380908 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00764474 | 47.1706 | 8518.28 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 19540.020 | 19540.020 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19540.02 | 19540.02 | 0.613376 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00749307 | 46.2483 | 13717.57 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 12738.509 | 12738.509 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12738.51 | 12738.51 | 0.399871 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00748261 | 46.1849 | 8942.24 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 19325.536 | 19325.536 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19325.54 | 19325.54 | 0.606643 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00748770 | 46.2156 | 13567.33 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 12868.625 | 12868.625 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12868.63 | 12868.63 | 0.403956 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00748757 | 46.2151 | 9033.39 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 105026.341 | 79782.534 | 5.032896 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 106548.48 | 83066.04 | 5.032896 | 25.37 | 17.71 | 0.01013974 | 10.85 | 10.85 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 18.9970 | 24.00 | 0.00891397 | 45.7431 | 66055.09 | 0.00 | 108296.26 | 79211.02 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 38238.798 | 38238.798 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:40:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38238.80 | 38238.80 | 1.509869 | -9.14 | -9.14 | 0.00300728 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 63.3234 | 16.50 | 0.00736378 | 60.2397 | 14553.36 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 97046.018 | 72449.922 | 4.489570 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 98953.43 | 74924.10 | 4.489570 | 25.53 | 17.96 | 0.01038154 | 10.83 | 10.83 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 21.2960 | 24.00 | 0.00903041 | 46.3332 | 58843.02 | 0.00 | 100067.47 | 71999.09 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 40693.170 | 40693.170 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:30:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40693.17 | 40693.17 | 1.346871 | -13.38 | -13.38 | 0.00231019 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 70.9868 | 16.64 | 0.00720981 | 58.4474 | 15223.42 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 108092.284 | 82019.752 | 5.164733 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 109701.32 | 85055.23 | 5.164733 | 25.33 | 17.73 | 0.01017707 | 10.85 | 10.85 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 18.5121 | 24.00 | 0.00899461 | 46.1524 | 67615.75 | 0.00 | 111457.65 | 81455.01 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 39572.306 | 39572.306 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:20:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39572.31 | 39572.31 | 1.549420 | -9.33 | -9.33 | 0.00298026 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 61.7070 | 16.29 | 0.00742520 | 61.5497 | 16916.73 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 20294.527 | 20294.527 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20294.53 | 15428.56 | 1.0000 | 0.55626170 | 0.484314 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20294.53 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.81 | 0.00800000 | 21.00 | 0.00800000 | 49.3289 | 10951.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 28520.544 | 28520.544 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 28520.54 | 28520.54 | 1.0000 | 1.02828036 | 0.895281 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28520.54 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 49.3289 | 20117.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 49039.243 | 49039.243 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 49039.24 | 49039.24 | 1.0000 | 1.76806202 | 1.539378 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 49039.24 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 49.3290 | 34491.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 24863.924 | 24863.924 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24863.92 | 24863.92 | 1.0000 | 0.89644448 | 0.780497 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24863.92 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00751964 | 21.00 | 0.00751964 | 46.4116 | 17447.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 16140.093 | 16140.093 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16140.09 | 16140.09 | 1.0000 | 0.58191530 | 0.506650 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16140.09 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00750735 | 21.00 | 0.00750735 | 46.3370 | 11325.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 24629.738 | 24629.738 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24629.74 | 24629.74 | 1.0000 | 0.88800116 | 0.773146 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24629.74 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00751538 | 21.00 | 0.00751538 | 46.3856 | 17283.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 16285.439 | 16285.439 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16285.44 | 16285.44 | 1.0000 | 0.58715562 | 0.511212 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16285.44 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00751145 | 21.00 | 0.00751145 | 46.3620 | 11427.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 18382.762 | 18382.762 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18382.76 | 18382.76 | 1.0000 | 0.66277254 | 0.577049 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18382.76 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00764732 | 21.00 | 0.00764732 | 47.1861 | 12905.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 12007.285 | 12007.285 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12007.29 | 12007.29 | 1.0000 | 0.43291094 | 0.376918 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12007.29 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00764098 | 21.00 | 0.00764098 | 47.1477 | 8429.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 18190.788 | 18190.788 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18190.79 | 18190.79 | 1.0000 | 0.65585110 | 0.571022 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18190.79 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00764354 | 21.00 | 0.00764354 | 47.1631 | 12771.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 12134.394 | 12134.394 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12134.39 | 12134.39 | 1.0000 | 0.43749373 | 0.380908 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12134.39 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00764474 | 21.00 | 0.00764474 | 47.1706 | 8518.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 19540.020 | 19540.020 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19540.02 | 19540.02 | 1.0000 | 0.70449635 | 0.613376 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19540.02 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00749307 | 21.00 | 0.00749307 | 46.2483 | 13717.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 12738.509 | 12738.509 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12738.51 | 12738.51 | 1.0000 | 0.45927450 | 0.399871 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12738.51 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00748261 | 21.00 | 0.00748261 | 46.1849 | 8942.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 19325.536 | 19325.536 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19325.54 | 19325.54 | 1.0000 | 0.69676332 | 0.606643 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19325.54 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00748770 | 21.00 | 0.00748770 | 46.2156 | 13567.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 12868.625 | 12868.625 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12868.63 | 12868.63 | 1.0000 | 0.46396571 | 0.403956 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12868.63 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00748757 | 21.00 | 0.00748757 | 46.2151 | 9033.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 105026.341 | 79782.534 | 5.032896 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6893 | 1004.8586 | 1.1486 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.032896 | 5.78056228 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 106548.48 | 83066.04 | 1.0145 | 5.78056228 | 5.032896 | 25.37 | 17.71 | 0.01013974 | 51326.5 | 10.85 | 10.85 | 0.00850000 | 32327.0 | -999.0 | -999.00 | -999.00 | -999.00 | 11567.918 | 94980.57 | 31.20 | 0.01536508 | 23.13 | 0.95610000 | 18.9970 | 24.00 | 0.00891397 | 24.00 | 0.00891397 | 45.7431 | 66055.09 | 0.00 | 108296.26 | 79211.02 | 5.55227377 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.70 | 12.69 | 0.00913079 | 35817.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 38238.798 | 38238.798 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.032896 | 5.78056228 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:40:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 38238.80 | 38238.80 | 1.0000 | 1.73416868 | 1.509869 | -9.14 | -9.14 | 0.00300728 | -1717.9 | 12.80 | 11.18 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38238.80 | -26.20 | 0.00036134 | -26.20 | 0.95610000 | 63.3234 | 20.30 | 0.00757558 | 16.50 | 0.00736378 | 60.2397 | 14553.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 97046.018 | 72449.922 | 4.489570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1388 | 1004.8586 | 1.1486 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.489570 | 5.15652194 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 98953.43 | 74924.10 | 1.0197 | 5.15652194 | 4.489570 | 25.53 | 17.96 | 0.01038154 | 52114.0 | 10.83 | 10.83 | 0.00850000 | 32314.9 | -999.0 | -999.00 | -999.00 | -999.00 | 10386.111 | 88567.32 | 31.20 | 0.01536508 | 23.13 | 0.95610000 | 21.2960 | 24.00 | 0.00903041 | 24.00 | 0.00903041 | 46.3332 | 58843.02 | 0.00 | 100067.47 | 71999.09 | 4.95287830 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.44 | 12.41 | 0.00896272 | 35118.5 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 40693.170 | 40693.170 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.489570 | 5.15652194 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:30:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 40693.17 | 40693.17 | 1.0000 | 1.54695658 | 1.346871 | -13.38 | -13.38 | 0.00231019 | -7722.7 | 12.80 | 11.18 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40693.17 | -26.20 | 0.00036134 | -26.20 | 0.95610000 | 70.9868 | 17.99 | 0.00707845 | 16.64 | 0.00720981 | 58.4474 | 15223.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 108092.284 | 82019.752 | 5.164733 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7587 | 1004.8586 | 1.1486 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.164733 | 5.93198374 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 109701.32 | 85055.23 | 1.0149 | 5.93198374 | 5.164733 | 25.33 | 17.73 | 0.01017707 | 51388.8 | 10.85 | 10.85 | 0.00850000 | 32327.1 | -999.0 | -999.00 | -999.00 | -999.00 | 11870.939 | 97830.38 | 31.20 | 0.01536508 | 23.13 | 0.95610000 | 18.5121 | 24.00 | 0.00899461 | 24.00 | 0.00899461 | 46.1524 | 67615.75 | 0.00 | 111457.65 | 81455.01 | 5.69771522 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.68 | 12.66 | 0.00912008 | 35760.6 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 39572.306 | 39572.306 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.164733 | 5.93198374 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:20:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39572.31 | 39572.31 | 1.0000 | 1.77959512 | 1.549420 | -9.33 | -9.33 | 0.00298026 | -1972.6 | 12.80 | 11.18 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39572.31 | -26.20 | 0.00036134 | -26.20 | 0.95610000 | 61.7070 | 17.86 | 0.00720048 | 16.29 | 0.00742520 | 61.5497 | 16916.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.03 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.49 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.16 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2517.67 | 3032.50 | 427.67 |
CORE_MID | 3209.33 | 3594.17 | 1454.17 |
CORE_TOP | 3618.67 | 3820.33 | 2000.83 |
PERIMETER_TOP_ZN_3 | 4163.50 | 4188.33 | 2741.17 |
PERIMETER_TOP_ZN_2 | 4146.83 | 3988.83 | 2564.83 |
PERIMETER_TOP_ZN_1 | 3822.83 | 3844.17 | 2218.50 |
PERIMETER_TOP_ZN_4 | 4162.50 | 4029.83 | 2610.67 |
PERIMETER_BOT_ZN_3 | 3854.00 | 4217.83 | 2500.50 |
PERIMETER_BOT_ZN_2 | 3977.67 | 3888.83 | 2295.67 |
PERIMETER_BOT_ZN_1 | 3701.33 | 4144.67 | 2285.67 |
PERIMETER_BOT_ZN_4 | 3939.33 | 3910.67 | 2280.33 |
PERIMETER_MID_ZN_3 | 3961.67 | 3968.83 | 2375.17 |
PERIMETER_MID_ZN_2 | 3404.00 | 3311.00 | 2007.83 |
PERIMETER_MID_ZN_1 | 3652.00 | 3591.17 | 1866.17 |
PERIMETER_MID_ZN_4 | 3981.17 | 3820.50 | 2270.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5095.33 | 4739.00 | 3158.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 1.67 | 0.83 | 1.67 | 0.83 |
CORE_MID | 2.83 | 0.33 | 2.00 | 0.33 |
CORE_TOP | 18.83 | 0.00 | 13.67 | 0.00 |
PERIMETER_TOP_ZN_3 | 292.17 | 6.17 | 131.83 | 4.00 |
PERIMETER_TOP_ZN_2 | 187.33 | 32.00 | 43.17 | 29.50 |
PERIMETER_TOP_ZN_1 | 162.50 | 28.00 | 38.67 | 25.17 |
PERIMETER_TOP_ZN_4 | 181.50 | 34.67 | 43.50 | 20.67 |
PERIMETER_BOT_ZN_3 | 165.67 | 0.33 | 114.00 | 0.33 |
PERIMETER_BOT_ZN_2 | 51.33 | 18.00 | 7.67 | 18.00 |
PERIMETER_BOT_ZN_1 | 467.00 | 22.67 | 441.17 | 22.50 |
PERIMETER_BOT_ZN_4 | 50.67 | 25.17 | 9.67 | 14.50 |
PERIMETER_MID_ZN_3 | 171.50 | 3.00 | 88.50 | 1.67 |
PERIMETER_MID_ZN_2 | 92.50 | 28.67 | 14.83 | 27.33 |
PERIMETER_MID_ZN_1 | 68.50 | 26.33 | 11.50 | 25.33 |
PERIMETER_MID_ZN_4 | 92.17 | 31.83 | 17.83 | 19.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 775.17 | 136.50 | 548.33 | 111.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.74 | 52.94 | 2698.04 | 0.868 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.74 | 52.94 | 2698.04 | 0.640 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.74 | 52.94 | 2698.04 | 0.629 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.58 | 11.16 | 568.77 | 0.798 | 0.123 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.90 | 7.07 | 360.08 | 1.080 | 0.129 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.58 | 11.16 | 568.77 | 1.017 | 0.123 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.90 | 7.06 | 360.05 | 1.044 | 0.129 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.58 | 11.16 | 568.77 | 0.651 | 0.065 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.90 | 7.07 | 360.08 | 0.914 | 0.069 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.58 | 11.16 | 568.77 | 0.857 | 0.888 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.90 | 7.06 | 360.05 | 0.869 | 0.069 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.58 | 11.16 | 568.77 | 0.742 | 0.102 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.54 | 7.07 | 360.08 | 0.981 | 0.114 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.58 | 11.16 | 568.77 | 0.999 | 0.103 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.90 | 7.06 | 360.05 | 0.998 | 0.108 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.74 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.74 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.74 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.90 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.90 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.54 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.74 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.74 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.74 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.90 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.90 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.54 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.75 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 13750012.55 | 0.00 | 13750012.55 | 0.00 | 13750012.55 | 13393058.27 | 5400.05 | 618.04 | 2741.91 | 285.62 |
CORE_MID | 10213382.90 | 0.00 | 10213382.90 | 0.00 | 10213382.90 | 13393058.27 | 5422.83 | 1073.83 | 2263.34 | 322.60 |
CORE_TOP | 10027349.39 | 0.00 | 10027349.39 | 0.00 | 10027349.39 | 13393058.27 | 5714.52 | 1038.59 | 2006.89 | 105.00 |
PERIMETER_TOP_ZN_3 | 2680840.61 | 0.00 | 2680840.61 | 834711.09 | 3515551.70 | 2823374.22 | 4160.23 | 26.64 | 4573.13 | 105.00 |
PERIMETER_TOP_ZN_2 | 2283826.19 | 0.00 | 2283826.19 | 556470.72 | 2840296.91 | 1787429.43 | 4622.68 | 968.49 | 3168.82 | 104.98 |
PERIMETER_TOP_ZN_1 | 3398070.56 | 0.00 | 3398070.56 | 834711.09 | 4232781.66 | 2823374.22 | 4531.96 | 996.09 | 3231.95 | 105.00 |
PERIMETER_TOP_ZN_4 | 2227513.73 | 0.00 | 2227513.73 | 556470.72 | 2783984.45 | 1787312.18 | 4541.21 | 975.51 | 3243.27 | 104.98 |
PERIMETER_BOT_ZN_3 | 2194957.44 | 0.00 | 2194957.44 | 443809.51 | 2638766.95 | 2823374.22 | 5331.59 | 81.45 | 3346.96 | 285.62 |
PERIMETER_BOT_ZN_2 | 1936168.99 | 0.00 | 1936168.99 | 295871.23 | 2232040.22 | 1787429.43 | 5297.84 | 632.68 | 2829.49 | 285.62 |
PERIMETER_BOT_ZN_1 | 2882113.03 | 0.00 | 2882113.03 | 3202062.74 | 6084175.77 | 2823374.22 | 4894.38 | 593.39 | 3272.22 | 285.62 |
PERIMETER_BOT_ZN_4 | 1849531.97 | 0.00 | 1849531.97 | 295871.23 | 2145403.20 | 1787312.18 | 5245.13 | 579.99 | 2934.88 | 285.62 |
PERIMETER_MID_ZN_3 | 2492929.48 | 0.00 | 2492929.48 | 694831.36 | 3187760.84 | 2823374.22 | 4556.84 | 895.03 | 3308.13 | 322.60 |
PERIMETER_MID_ZN_2 | 2083857.94 | 0.00 | 2083857.94 | 463218.12 | 2547076.06 | 1601953.02 | 4367.30 | 782.07 | 3610.63 | 1231.60 |
PERIMETER_MID_ZN_1 | 3340104.15 | 0.00 | 3340104.15 | 694831.36 | 4034935.51 | 2823374.22 | 4525.21 | 1101.71 | 3133.08 | 322.60 |
PERIMETER_MID_ZN_4 | 2127477.47 | 0.00 | 2127477.47 | 463218.12 | 2590695.59 | 1787312.18 | 4597.50 | 1107.64 | 3054.87 | 322.60 |
Total Facility | 63488136.41 | 0.00 | 63488136.41 | 9336077.29 | 72824213.71 | 67658168.57 | 6721.35 | 1764.66 | 4733.47 | 1370.33 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6359 | 0.0000 | 0.6359 | 0.0000 | 0.6359 | 0.4247 | 2625.05 | 618.04 | 2699.91 |
CORE_MID | 0.4701 | 0.0000 | 0.4701 | 0.0000 | 0.4701 | 0.4247 | 2657.80 | 1073.83 | 2211.37 |
CORE_TOP | 0.4620 | 0.0000 | 0.4620 | 0.0000 | 0.4620 | 0.4247 | 2958.06 | 1038.59 | 1946.35 |
PERIMETER_TOP_ZN_3 | 0.1237 | 0.0000 | 0.1237 | 0.0192 | 0.1429 | 0.0895 | 1403.79 | 26.62 | 4512.59 |
PERIMETER_TOP_ZN_2 | 0.1058 | 0.0000 | 0.1058 | 0.0128 | 0.1186 | 0.0567 | 1866.22 | 968.49 | 3108.28 |
PERIMETER_TOP_ZN_1 | 0.1574 | 0.0000 | 0.1574 | 0.0192 | 0.1765 | 0.0895 | 1775.57 | 996.09 | 3171.34 |
PERIMETER_TOP_ZN_4 | 0.1023 | 0.0000 | 0.1023 | 0.0128 | 0.1151 | 0.0567 | 1784.83 | 975.51 | 3182.66 |
PERIMETER_BOT_ZN_3 | 0.1010 | 0.0000 | 0.1010 | 0.0102 | 0.1112 | 0.0895 | 2556.59 | 81.45 | 3304.96 |
PERIMETER_BOT_ZN_2 | 0.0896 | 0.0000 | 0.0896 | 0.0068 | 0.0964 | 0.0567 | 2523.05 | 632.68 | 2787.28 |
PERIMETER_BOT_ZN_1 | 0.1332 | 0.0000 | 0.1332 | 0.1391 | 0.2724 | 0.0895 | 2119.38 | 593.39 | 3230.22 |
PERIMETER_BOT_ZN_4 | 0.0851 | 0.0000 | 0.0851 | 0.0068 | 0.0919 | 0.0567 | 2470.37 | 579.96 | 2892.67 |
PERIMETER_MID_ZN_3 | 0.1149 | 0.0000 | 0.1149 | 0.0160 | 0.1309 | 0.0895 | 1791.81 | 895.03 | 3256.16 |
PERIMETER_MID_ZN_2 | 0.0961 | 0.0000 | 0.0961 | 0.0113 | 0.1073 | 0.0567 | 1602.58 | 782.00 | 2649.41 |
PERIMETER_MID_ZN_1 | 0.1545 | 0.0000 | 0.1545 | 0.0160 | 0.1705 | 0.0895 | 1760.18 | 1101.71 | 3081.11 |
PERIMETER_MID_ZN_4 | 0.0978 | 0.0000 | 0.0978 | 0.0106 | 0.1084 | 0.0567 | 1832.85 | 1107.56 | 3002.59 |
Total Facility | 2.9296 | 0.0000 | 2.9296 | 0.2807 | 3.2103 | 2.1513 | 3931.41 | 1764.46 | 4657.10 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 29830234.54 | 0.00 | 29830234.54 | 22614548.33 | 4144.26 | 1.84 | 4613.90 | 285.33 |
PACU_VAV_MID | 26723598.79 | 0.00 | 26723598.79 | 22429071.92 | 4108.67 | 1.62 | 4649.72 | 322.17 |
PACU_VAV_TOP | 27198171.63 | 0.00 | 27198171.63 | 22614548.33 | 4093.93 | 1.39 | 4664.68 | 104.48 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.3785 | 0.0000 | 1.3785 | 0.7171 | 1369.26 | 1.84 | 4571.90 |
PACU_VAV_MID | 1.2318 | 0.0000 | 1.2318 | 0.7084 | 1343.64 | 1.62 | 4597.74 |
PACU_VAV_TOP | 1.2549 | 0.0000 | 1.2549 | 0.7171 | 1337.55 | 1.39 | 4604.07 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 493.78 | 2390.23 | 0.00 | 0.00 | 0.00 | 2205.80 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 107.58 | 2491.29 | 0.00 | 0.00 | 0.00 | 2591.75 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 112.09 | 2206.21 | 0.00 | 0.00 | 0.00 | 2571.65 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.2532 | 2.5046 | 0.0000 | 0.0000 | 0.0000 | 1.0446 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.2219 | 2.1277 | 0.0000 | 0.0000 | 0.0000 | 0.9933 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.2091 | 2.2397 | 0.0000 | 0.0000 | 0.0000 | 1.0174 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 943 |
Defaulted Fields | 546 |
Fields with Defaults | 2233 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1617.96 | 12315.29 | 09-APR-17:30 | 255304.87 | 30-JAN-07:10 |
Electricity:Building | 938.05 | 12146.72 | 09-APR-17:20 | 70537.40 | 03-NOV-07:10 |
Electricity:Zone:CORE_BOTTOM | 291.77 | 4006.86 | 01-JAN-00:10 | 23121.21 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 938.05 | 12146.72 | 09-APR-17:20 | 70537.40 | 03-NOV-07:10 |
InteriorLights:Electricity | 232.62 | 905.38 | 09-APR-17:20 | 25003.79 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 232.62 | 905.38 | 09-APR-17:20 | 25003.79 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 232.62 | 905.38 | 09-APR-17:20 | 25003.79 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 232.62 | 905.38 | 09-APR-17:20 | 25003.79 | 02-JAN-16:40 |
Electricity:Zone:CORE_MID | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 31.11 | 413.68 | 26-MAR-17:10 | 2475.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.77 | 27.57 | 01-JAN-10:00 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.77 | 27.57 | 01-JAN-10:00 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.67 | 261.88 | 09-APR-17:10 | 1567.33 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.26 | 17.46 | 01-JAN-09:40 | 658.76 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.26 | 17.46 | 01-JAN-09:40 | 658.76 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 31.00 | 413.67 | 26-MAR-17:10 | 2475.79 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.67 | 27.57 | 01-JAN-09:40 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.67 | 27.57 | 01-JAN-09:40 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.65 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.25 | 17.46 | 01-JAN-09:50 | 658.71 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.25 | 17.46 | 01-JAN-09:50 | 658.71 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 31.09 | 413.68 | 26-MAR-17:10 | 2475.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.76 | 27.57 | 01-JAN-10:00 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.76 | 27.57 | 01-JAN-10:00 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.66 | 261.88 | 09-APR-17:10 | 1567.33 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.26 | 17.46 | 01-JAN-09:40 | 658.76 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.26 | 17.46 | 01-JAN-09:40 | 658.76 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 31.00 | 413.67 | 26-MAR-17:10 | 2475.79 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.66 | 27.57 | 01-JAN-09:40 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.66 | 27.57 | 01-JAN-09:40 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.64 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.24 | 17.46 | 01-JAN-09:50 | 658.71 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.24 | 17.46 | 01-JAN-09:50 | 658.71 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 31.11 | 413.68 | 26-MAR-17:10 | 2475.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.77 | 27.57 | 01-JAN-10:00 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.77 | 27.57 | 01-JAN-10:00 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.67 | 261.88 | 09-APR-17:10 | 1567.33 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.26 | 17.46 | 01-JAN-09:40 | 658.76 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.26 | 17.46 | 01-JAN-09:40 | 658.76 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 31.00 | 413.67 | 26-MAR-17:10 | 2475.79 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.67 | 27.57 | 01-JAN-09:40 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.67 | 27.57 | 01-JAN-09:40 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.65 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.25 | 17.46 | 01-JAN-09:50 | 658.71 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.25 | 17.46 | 01-JAN-09:50 | 658.71 | 02-JAN-16:40 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 628.50 | 168.57 | 09-APR-17:30 | 220178.32 | 30-JAN-07:10 |
ExteriorEquipment:Electricity | 11.69 | 168.34 | 01-JAN-00:10 | 839.72 | 03-NOV-07:20 |
Transformer:ExteriorEquipment:Electricity | 11.69 | 168.34 | 01-JAN-00:10 | 839.72 | 03-NOV-07:20 |
ElectricityPurchased:Facility | 1617.96 | 12315.29 | 09-APR-17:30 | 255304.87 | 30-JAN-07:10 |
ElectricityPurchased:Plant | 1617.96 | 12315.29 | 09-APR-17:30 | 255304.87 | 30-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1617.96 | 12315.29 | 09-APR-17:30 | 255304.87 | 30-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1617.96 | 12315.29 | 09-APR-17:30 | 255304.87 | 30-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1617.96 | 12315.29 | 09-APR-17:30 | 255304.87 | 30-JAN-07:10 |
ElectricityNet:Plant | 1617.96 | 12315.29 | 09-APR-17:30 | 255304.87 | 30-JAN-07:10 |
Cogeneration:ElectricityNet | 1617.96 | 12315.29 | 09-APR-17:30 | 255304.87 | 30-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1617.96 | 12315.29 | 09-APR-17:30 | 255304.87 | 30-JAN-07:10 |
Heating:Electricity | 374.69 | 0.00 | 01-JAN-00:40 | 212408.91 | 30-JAN-07:10 |
General:Heating:Electricity | 374.69 | 0.00 | 01-JAN-00:40 | 212408.91 | 30-JAN-07:10 |
Fans:Electricity | 91.73 | 0.00 | 01-JAN-00:40 | 32052.63 | 04-AUG-07:10 |
General:Fans:Electricity | 91.73 | 0.00 | 01-JAN-00:40 | 32052.63 | 04-AUG-07:10 |
ExteriorLights:Electricity | 51.26 | 0.00 | 01-JAN-08:00 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 51.26 | 0.00 | 01-JAN-08:00 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 150.39 | 0.00 | 01-JAN-00:10 | 82003.88 | 04-AUG-15:30 |
General:Cooling:Electricity | 150.39 | 0.00 | 01-JAN-00:10 | 82003.88 | 04-AUG-15:30 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-17:20 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-17:20 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-17:20 |
WIRED_LTG_ELECTRICITY | 6.54 | 0.00 | 01-JAN-00:10 | 702.61 | 02-JAN-16:50 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 561.84 | 1886.44 | 19-JAN-04:20 | 158631.09 | 02-FEB-12:20 |
NaturalGas:HVAC | 422.85 | 0.00 | 01-JAN-00:40 | 148130.34 | 06-JAN-07:20 |
Heating:NaturalGas | 422.85 | 0.00 | 01-JAN-00:40 | 148130.34 | 06-JAN-07:20 |
General:Heating:NaturalGas | 422.85 | 0.00 | 01-JAN-00:40 | 148130.34 | 06-JAN-07:20 |
NaturalGas:Plant | 138.99 | 1886.44 | 02-JAN-07:20 | 12758.92 | 15-FEB-12:30 |
WaterSystems:NaturalGas | 138.99 | 1886.44 | 02-JAN-07:20 | 12758.92 | 15-FEB-12:30 |
Water Heater:WaterSystems:NaturalGas | 138.99 | 1886.44 | 02-JAN-07:20 | 12758.92 | 15-FEB-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2524.77 | 0.00 | 01-JAN-00:40 | 528595.05 | 30-JAN-07:10 |
EnergyTransfer:Building | 1145.24 | 0.00 | 01-JAN-00:40 | 209609.67 | 30-JAN-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 192.79 | 0.00 | 01-JAN-00:40 | 27708.48 | 04-AUG-08:00 |
Heating:EnergyTransfer | 353.34 | 0.00 | 01-JAN-00:40 | 209047.63 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.53 | 0.00 | 01-JAN-00:10 | 16298.23 | 02-JAN-07:00 |
General:Heating:EnergyTransfer | 353.34 | 0.00 | 01-JAN-00:40 | 209047.63 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.53 | 0.00 | 01-JAN-00:10 | 16298.23 | 02-JAN-07:00 |
Cooling:EnergyTransfer | 791.91 | 0.00 | 01-JAN-00:40 | 165465.11 | 26-JUN-15:30 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 192.25 | 0.00 | 01-JAN-00:40 | 27708.48 | 04-AUG-08:00 |
General:Cooling:EnergyTransfer | 791.91 | 0.00 | 01-JAN-00:40 | 165465.11 | 26-JUN-15:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 192.25 | 0.00 | 01-JAN-00:40 | 27708.48 | 04-AUG-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 63.89 | 0.00 | 01-JAN-00:40 | 19403.07 | 02-FEB-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 40.71 | 0.00 | 01-JAN-00:40 | 19403.07 | 02-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 40.71 | 0.00 | 01-JAN-00:40 | 19403.07 | 02-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 23.18 | 0.00 | 01-JAN-00:10 | 11033.94 | 26-JUN-13:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 23.18 | 0.00 | 01-JAN-00:10 | 11033.94 | 26-JUN-13:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 30.67 | 0.00 | 01-JAN-00:40 | 10549.82 | 30-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 18.26 | 0.00 | 01-JAN-00:40 | 10549.82 | 30-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 18.26 | 0.00 | 01-JAN-00:40 | 10549.82 | 30-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 12.41 | 0.00 | 01-JAN-00:10 | 5401.96 | 26-JUN-10:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 12.41 | 0.00 | 01-JAN-00:10 | 5401.96 | 26-JUN-10:30 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 29.20 | 0.00 | 01-JAN-00:40 | 8329.73 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 13.34 | 0.00 | 01-JAN-00:40 | 8329.73 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 13.34 | 0.00 | 01-JAN-00:40 | 8329.73 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 15.86 | 0.00 | 01-JAN-00:10 | 5576.78 | 26-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 15.86 | 0.00 | 01-JAN-00:10 | 5576.78 | 26-JUN-15:10 |
EnergyTransfer:Zone:CORE_MID | 127.12 | 0.00 | 01-JAN-00:40 | 24735.22 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 5.80 | 0.00 | 01-JAN-00:40 | 24735.22 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 5.80 | 0.00 | 01-JAN-00:40 | 24735.22 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 121.32 | 0.00 | 01-JAN-00:20 | 19508.63 | 26-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 121.32 | 0.00 | 01-JAN-00:20 | 19508.63 | 26-JUN-08:10 |
EnergyTransfer:Zone:CORE_TOP | 130.31 | 0.00 | 01-JAN-00:40 | 28663.18 | 11-DEC-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 21.98 | 0.00 | 01-JAN-00:40 | 28663.18 | 11-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 21.98 | 0.00 | 01-JAN-00:40 | 28663.18 | 11-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 108.33 | 0.00 | 01-JAN-00:10 | 20544.78 | 26-JUN-13:40 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 108.33 | 0.00 | 01-JAN-00:10 | 20544.78 | 26-JUN-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 60.58 | 0.00 | 01-JAN-00:40 | 11470.43 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 36.49 | 0.00 | 01-JAN-00:40 | 11470.43 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 36.49 | 0.00 | 01-JAN-00:40 | 11470.43 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 24.09 | 0.00 | 01-JAN-00:10 | 7389.16 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 24.09 | 0.00 | 01-JAN-00:10 | 7389.16 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 45.44 | 0.00 | 01-JAN-00:40 | 11135.38 | 19-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 21.42 | 0.00 | 01-JAN-00:40 | 11135.38 | 19-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 21.42 | 0.00 | 01-JAN-00:40 | 11135.38 | 19-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 24.02 | 0.00 | 01-JAN-00:20 | 9364.02 | 26-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 24.02 | 0.00 | 01-JAN-00:20 | 9364.02 | 26-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 65.26 | 0.00 | 01-JAN-00:40 | 14476.03 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 26.05 | 0.00 | 01-JAN-00:40 | 14476.03 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 26.05 | 0.00 | 01-JAN-00:40 | 14476.03 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 39.21 | 0.00 | 01-JAN-00:20 | 13780.19 | 07-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 39.21 | 0.00 | 01-JAN-00:20 | 13780.19 | 07-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 46.64 | 0.00 | 01-JAN-00:40 | 11544.71 | 19-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 22.26 | 0.00 | 01-JAN-00:40 | 11544.71 | 19-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 22.26 | 0.00 | 01-JAN-00:40 | 11544.71 | 19-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 24.37 | 0.00 | 01-JAN-00:20 | 9719.64 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 24.37 | 0.00 | 01-JAN-00:20 | 9719.64 | 05-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 42.63 | 0.00 | 01-JAN-00:40 | 8123.89 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 22.39 | 0.00 | 01-JAN-00:40 | 8123.89 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 22.39 | 0.00 | 01-JAN-00:40 | 8123.89 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.24 | 0.00 | 01-JAN-00:10 | 5552.81 | 04-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.24 | 0.00 | 01-JAN-00:10 | 5552.81 | 04-AUG-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 33.92 | 0.00 | 01-JAN-00:40 | 8254.78 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 12.40 | 0.00 | 01-JAN-00:40 | 8254.78 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 12.40 | 0.00 | 01-JAN-00:40 | 8254.78 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 21.52 | 0.00 | 01-JAN-00:20 | 7540.42 | 26-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 21.52 | 0.00 | 01-JAN-00:20 | 7540.42 | 26-JUN-08:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 65.87 | 0.00 | 01-JAN-00:40 | 17115.03 | 02-FEB-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 36.83 | 0.00 | 01-JAN-00:40 | 17115.03 | 02-FEB-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 36.83 | 0.00 | 01-JAN-00:40 | 17115.03 | 02-FEB-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 29.04 | 0.00 | 01-JAN-00:20 | 12100.66 | 07-SEP-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 29.04 | 0.00 | 01-JAN-00:20 | 12100.66 | 07-SEP-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 34.09 | 0.00 | 01-JAN-00:40 | 8347.59 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 12.82 | 0.00 | 01-JAN-00:40 | 8347.59 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 12.82 | 0.00 | 01-JAN-00:40 | 8347.59 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 21.28 | 0.00 | 01-JAN-00:20 | 7611.37 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 21.28 | 0.00 | 01-JAN-00:20 | 7611.37 | 05-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 46.76 | 0.00 | 01-JAN-00:40 | 8839.11 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 21.93 | 0.00 | 01-JAN-00:40 | 8839.11 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 21.93 | 0.00 | 01-JAN-00:40 | 8839.11 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 24.83 | 0.00 | 01-JAN-00:10 | 6801.50 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 24.83 | 0.00 | 01-JAN-00:10 | 6801.50 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 36.29 | 0.00 | 01-JAN-00:40 | 9551.74 | 26-JUN-08:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 12.64 | 0.00 | 01-JAN-00:40 | 9354.36 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 12.64 | 0.00 | 01-JAN-00:40 | 9354.36 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 23.65 | 0.00 | 01-JAN-00:20 | 9551.74 | 26-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 23.65 | 0.00 | 01-JAN-00:20 | 9551.74 | 26-JUN-08:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 55.49 | 0.00 | 01-JAN-00:40 | 12805.03 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 14.28 | 0.00 | 01-JAN-00:40 | 12805.03 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 14.28 | 0.00 | 01-JAN-00:40 | 12805.03 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 41.21 | 0.00 | 01-JAN-00:20 | 12764.88 | 07-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 41.21 | 0.00 | 01-JAN-00:20 | 12764.88 | 07-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 38.28 | 0.00 | 01-JAN-00:40 | 9458.96 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 13.20 | 0.00 | 01-JAN-00:40 | 9458.96 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 13.20 | 0.00 | 01-JAN-00:40 | 9458.96 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 25.09 | 0.00 | 01-JAN-00:20 | 9259.88 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 25.09 | 0.00 | 01-JAN-00:20 | 9259.88 | 05-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 55.82 | 0.00 | 01-JAN-00:10 | 7149.73 | 22-FEB-12:30 |
PlantLoopHeatingDemand:Plant | 55.82 | 0.00 | 01-JAN-00:10 | 7149.73 | 22-FEB-12:30 |
WaterSystems:PlantLoopHeatingDemand | 55.82 | 0.00 | 01-JAN-00:10 | 7149.73 | 22-FEB-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 55.82 | 0.00 | 01-JAN-00:10 | 7149.73 | 22-FEB-12:30 |
EnergyTransfer:HVAC | 1323.71 | 0.00 | 01-JAN-00:40 | 364215.90 | 04-AUG-07:10 |
HeatingCoils:EnergyTransfer | 712.97 | 0.00 | 01-JAN-00:40 | 327925.32 | 02-FEB-07:10 |
CoolingCoils:EnergyTransfer | 610.75 | 0.00 | 01-JAN-00:10 | 364215.90 | 04-AUG-07:10 |
EnergyTransfer:Plant | 55.82 | 0.00 | 01-JAN-00:10 | 7149.73 | 22-FEB-12:30 |
WaterSystems:EnergyTransfer | 55.82 | 0.00 | 01-JAN-00:10 | 7149.73 | 22-FEB-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 55.82 | 0.00 | 01-JAN-00:10 | 7149.73 | 22-FEB-12:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.531 | -192.255 | 0.000 | 0.000 | 33.519 | 55.599 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -133.562 |
CORE_MID | 0.000 | 0.000 | 5.802 | -121.318 | 0.000 | 0.000 | 34.935 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -90.443 |
CORE_TOP | 0.000 | 0.000 | 21.983 | -108.327 | 0.000 | 0.000 | 35.560 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -120.240 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 36.492 | -24.091 | 0.000 | 0.000 | 7.668 | 6.774 | 24.333 | 17.352 | 0.000 | 0.105 | 0.001 | 0.000 | -40.456 | 0.000 | -15.217 | -12.959 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 21.415 | -24.021 | 0.000 | 0.000 | 4.777 | 4.263 | 15.404 | 32.612 | 0.000 | 0.065 | 0.001 | 0.000 | -25.188 | 0.000 | -10.296 | -19.031 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 26.052 | -39.211 | 0.000 | 0.000 | 7.457 | 6.671 | 24.332 | 67.277 | 0.000 | 0.097 | 0.001 | 0.000 | -36.788 | 0.000 | -15.718 | -40.169 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 22.264 | -24.374 | 0.000 | 0.000 | 4.809 | 4.246 | 15.403 | 34.036 | 0.000 | 0.064 | 0.001 | 0.000 | -26.078 | 0.000 | -10.337 | -20.034 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 22.391 | -20.244 | 0.000 | 0.000 | 7.645 | 6.757 | 24.333 | 17.700 | 0.000 | 0.070 | 0.000 | 0.000 | -41.280 | 0.000 | -8.362 | -9.010 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 12.404 | -21.520 | 0.000 | 0.000 | 4.751 | 4.256 | 15.404 | 32.810 | 0.000 | 0.038 | 0.001 | 0.000 | -26.036 | 0.000 | -5.710 | -16.397 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 36.827 | -29.042 | 0.000 | 0.000 | 7.699 | 6.663 | 24.332 | 68.195 | 0.000 | 1.104 | 0.000 | 0.000 | -37.862 | 0.000 | -53.547 | -24.369 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 12.817 | -21.275 | 0.000 | 0.000 | 4.774 | 4.239 | 15.403 | 34.305 | 0.000 | 0.036 | 0.000 | 0.000 | -26.989 | 0.000 | -5.739 | -17.571 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 21.926 | -24.833 | 0.000 | 0.000 | 7.583 | 6.774 | 24.333 | 17.110 | 0.000 | 0.090 | 2.208 | 0.000 | -42.057 | 0.000 | -13.133 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 12.641 | -23.652 | 0.000 | 0.000 | 3.497 | 4.263 | 15.404 | 32.366 | 0.000 | 0.054 | 0.000 | 0.000 | -26.155 | 0.000 | -8.877 | -9.541 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 14.277 | -41.211 | 0.000 | 0.000 | 7.368 | 6.671 | 24.332 | 66.984 | 0.000 | 0.083 | 0.000 | 0.000 | -38.347 | 0.000 | -13.590 | -26.568 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 13.195 | -25.088 | 0.000 | 0.000 | 4.759 | 4.246 | 15.403 | 33.900 | 0.000 | 0.054 | 0.000 | 0.000 | -27.118 | 0.000 | -8.909 | -10.443 |
TOPFLOOR_PLENUM | 40.714 | -23.176 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.082 | 5.274 | 0.000 | 0.000 | 0.000 | -22.894 | -0.005 |
MIDFLOOR_PLENUM | 18.262 | -12.407 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.131 | 16.374 | 0.000 | 0.000 | 0.000 | -22.360 | -0.000 |
FIRSTFLOOR_PLENUM | 13.343 | -15.859 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.103 | 20.465 | 0.000 | 0.000 | 0.000 | -18.052 | -0.000 |
Total Facility | 72.319 | -51.442 | 281.016 | -740.460 | 0.000 | 0.000 | 176.801 | 232.618 | 705.434 | 454.649 | 0.000 | 2.177 | 44.326 | 0.000 | -394.354 | 0.000 | -232.740 | -550.343 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 17-JUL-05:12 | 0.00 | 0.00 | 0.00 | -41664.81 | 0.00 | 0.00 | 318.01 | 548.43 | 4989.51 | 0.00 | 0.00 | 0.00 | 35808.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 31-JUL-05:12 | 0.00 | 0.00 | 0.00 | -31069.88 | 0.00 | 0.00 | 324.38 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 27171.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 11-SEP-05:12 | 0.00 | 0.00 | 0.00 | -31930.75 | 0.00 | 0.00 | 333.58 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 28022.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 25-JUN-17:21 | 0.00 | 0.00 | 0.00 | -12373.39 | 0.00 | 0.00 | 0.00 | 27.57 | 386.10 | 3207.32 | 0.00 | 391.68 | 8360.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JUL-09:32 | 0.00 | 0.00 | 0.00 | -14471.81 | 0.00 | 0.00 | 12.98 | 17.46 | 302.86 | 9459.19 | 0.00 | 0.00 | 4715.50 | 0.00 | -0.00 | 0.00 | -36.18 | 0.00 |
PERIMETER_TOP_ZN_1 | 04-SEP-12:52 | 0.00 | 0.00 | 0.00 | -18731.91 | 0.00 | 0.00 | 22.47 | 27.57 | 478.41 | 15324.24 | 0.00 | 0.00 | 3047.84 | 0.00 | -0.00 | 0.00 | -168.63 | 0.00 |
PERIMETER_TOP_ZN_4 | 14-MAY-16:31 | 0.00 | 0.00 | 0.00 | -17029.28 | 0.00 | 0.00 | 13.23 | 17.46 | 302.86 | 12148.51 | 0.00 | 0.00 | 4643.69 | 0.00 | -0.00 | 0.00 | -96.47 | 0.00 |
PERIMETER_BOT_ZN_3 | 05-JUL-06:03 | 0.00 | 0.00 | 0.00 | -7445.78 | 0.00 | 0.00 | 144.56 | 165.45 | 637.89 | 2880.61 | 0.00 | 0.00 | 3636.73 | 0.00 | -0.00 | 0.00 | -19.46 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-JUL-08:41 | 0.00 | 0.00 | 0.00 | -12106.67 | 0.00 | 0.00 | 15.56 | 17.46 | 302.86 | 9657.54 | 0.00 | 0.00 | 2220.54 | 0.00 | -0.00 | 0.00 | -107.28 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-12:52 | 0.00 | 0.00 | 0.00 | -14477.08 | 0.00 | 0.00 | 24.63 | 27.57 | 478.41 | 15432.28 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -83.97 | -1401.84 |
PERIMETER_BOT_ZN_4 | 04-SEP-16:51 | 0.00 | 0.00 | 0.00 | -12984.58 | 0.00 | 0.00 | 14.80 | 17.46 | 302.86 | 10341.19 | 0.00 | 0.00 | 2347.00 | 0.00 | -0.00 | 0.00 | -38.71 | 0.00 |
PERIMETER_MID_ZN_3 | 25-JUN-18:31 | 0.00 | 0.00 | 0.00 | -9955.84 | 0.00 | 0.00 | 0.00 | 27.57 | 386.10 | 3892.68 | 0.00 | 151.46 | 5498.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 25-JUN-08:31 | 0.00 | 0.00 | 0.00 | -15440.43 | 0.00 | 0.00 | 13.32 | 17.46 | 302.86 | 11322.27 | 0.00 | 0.00 | 3919.46 | 0.00 | -0.00 | 0.00 | -134.94 | 0.00 |
PERIMETER_MID_ZN_1 | 30-JUL-13:42 | 0.00 | 0.00 | 0.00 | -16340.65 | 0.00 | 0.00 | 23.62 | 27.57 | 478.41 | 10391.63 | 0.00 | 0.00 | 5439.43 | 0.00 | -0.00 | 0.00 | -20.02 | 0.00 |
PERIMETER_MID_ZN_4 | 25-JUN-17:51 | 0.00 | 0.00 | 0.00 | -15984.30 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 9758.77 | 0.00 | 72.88 | 5890.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 26-JUN-13:50 | 0.00 | -11034.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.34 | 10933.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 05-JUL-06:15 | 0.00 | -6223.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6284.47 | 0.00 | -0.00 | 0.00 | -60.75 | 0.00 |
FIRSTFLOOR_PLENUM | 05-JUL-06:15 | 0.00 | -6314.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6361.36 | 0.00 | -0.00 | 0.00 | -46.49 | 0.00 |
Total Facility | 05-JUL-06:03 | 0.00 | -6904.51 | 0.00 | -175861.69 | 0.00 | 0.00 | 3482.55 | 6557.23 | 21098.80 | 33866.00 | 0.00 | 0.00 | 121702.55 | 0.00 | 0.00 | 0.00 | -3940.92 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 18363.69 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 4405.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22981.07 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 28230.59 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -30884.37 |
CORE_TOP | 30-JAN-05:01 | 0.00 | 0.00 | 31656.99 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -34310.78 |
PERIMETER_TOP_ZN_3 | 06-MAR-05:11 | 0.00 | 0.00 | 12166.31 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3237.55 | 0.00 | -2252.63 | -7235.56 |
PERIMETER_TOP_ZN_2 | 06-MAR-05:11 | 0.00 | 0.00 | 13034.82 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2159.55 | 0.00 | -1518.90 | -9710.52 |
PERIMETER_TOP_ZN_1 | 06-MAR-05:11 | 0.00 | 0.00 | 15922.21 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3357.22 | 0.00 | -2280.28 | -10844.15 |
PERIMETER_TOP_ZN_4 | 06-MAR-05:11 | 0.00 | 0.00 | 14265.29 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2226.58 | 0.00 | -1526.69 | -10866.17 |
PERIMETER_BOT_ZN_3 | 30-JAN-05:01 | 0.00 | 0.00 | 8533.76 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4654.89 | 0.00 | -1469.94 | -2968.37 |
PERIMETER_BOT_ZN_2 | 30-JAN-05:01 | 0.00 | 0.00 | 10059.33 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3027.64 | 0.00 | -987.61 | -6398.22 |
PERIMETER_BOT_ZN_1 | 02-FEB-07:10 | 0.00 | 0.00 | 17700.06 | 0.00 | 0.00 | 0.00 | 216.04 | 346.86 | 637.88 | 0.00 | 0.00 | 0.00 | 25891.60 | 0.00 | -5669.12 | 0.00 | -39123.32 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-JAN-05:01 | 0.00 | 0.00 | 10691.82 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3117.85 | 0.00 | -989.28 | -6938.84 |
PERIMETER_MID_ZN_3 | 19-JAN-04:42 | 0.00 | 0.00 | 9484.23 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4762.80 | 0.00 | -3452.07 | -1828.80 |
PERIMETER_MID_ZN_2 | 19-JAN-04:42 | 0.00 | 0.00 | 12564.63 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3068.18 | 0.00 | -2337.81 | -7512.79 |
PERIMETER_MID_ZN_1 | 19-JAN-04:42 | 0.00 | 0.00 | 14301.87 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4621.78 | 0.00 | -3494.22 | -6745.31 |
PERIMETER_MID_ZN_4 | 19-JAN-04:42 | 0.00 | 0.00 | 13022.57 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3168.24 | 0.00 | -2337.69 | -7870.79 |
TOPFLOOR_PLENUM | 02-FEB-06:13 | 20406.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -676.28 | -19730.28 |
MIDFLOOR_PLENUM | 30-JAN-07:04 | 10827.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -720.04 | -10107.20 |
FIRSTFLOOR_PLENUM | 02-JAN-07:01 | 9359.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -426.84 | -8932.97 |
Total Facility | 11-DEC-06:01 | 25950.80 | 0.00 | 208261.04 | 0.00 | 0.00 | 0.00 | 2634.09 | 1072.56 | 17291.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -40642.10 | 0.00 | -9645.17 | -204922.72 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.7578 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0329 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.4046 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.4896 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.8253 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.1647 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.8789 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0823 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.7023 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0744 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.9126 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0892 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9358 | 2.9358 | 0.6371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1494 | 2.1494 | 0.6362 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2322 | 2.2322 | 0.6362 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7805 | 0.7805 | 0.1491 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8464 | 0.8464 | 0.0846 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0348 | 1.0348 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9314 | 0.9314 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5770 | 0.5770 | 0.1414 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6891 | 0.6891 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8214 | 0.8214 | 0.1339 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7345 | 0.7345 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6142 | 0.6142 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8336 | 0.8336 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9436 | 0.9436 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8639 | 0.8639 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.7578 | 5.0329 | 5.7578 | 1.0823 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.4046 | 4.4896 | 5.4046 | 1.0744 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.8253 | 5.1647 | 5.8253 | 1.0892 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4679 | 1.4679 | 0.6371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0747 | 1.0747 | 0.6362 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1161 | 1.1161 | 0.6362 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3902 | 0.3902 | 0.1491 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4232 | 0.4232 | 0.0846 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5174 | 0.5174 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4657 | 0.4657 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2885 | 0.2885 | 0.1414 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3446 | 0.3446 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4107 | 0.4107 | 0.1339 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3673 | 0.3673 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3071 | 0.3071 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4168 | 0.4168 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4718 | 0.4718 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4320 | 0.4320 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.8789 | 1.0823 | 1.0823 | 1.0823 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.7023 | 1.0744 | 1.0744 | 1.0744 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.9126 | 1.0892 | 1.0892 | 1.0892 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 548.33 |
Number of hours cooling loads not met | 111.00 |
Number of hours not met | 659.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 374.69 | 212408.91 | 422.85 | 148130.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 150.39 | 82003.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 232.62 | 25003.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 51.26 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.69 | 839.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 91.73 | 32052.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 138.99 | 12758.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1617.96 |
Natural Gas | 0.00 | 561.84 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 2179.80 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.69 |
Space Heating | 75.21 |
Space Cooling | 30.19 |
Fans (All) | 18.41 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 324.75 |
Subtotal | 324.75 |
Natural Gas [MJ/m2] | |
Space Heating | 84.87 |
Service Water Heating | 27.90 |
Miscellaneous (All) | 112.77 |
Subtotal | 112.77 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.67 |
Space Heating | 36.59 |
Space Cooling | 6.90 |
Fans (All) | 4.21 |
Service Water Heating | 6.38 |
Receptacle Equipment | 32.36 |
Miscellaneous | 2.89 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 807. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8719.17 | 40.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8750.33 | 9.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8752.00 | 8.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8736.83 | 23.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8645.50 | 114.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8676.83 | 83.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8624.17 | 135.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8692.67 | 67.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8717.83 | 42.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8666.33 | 93.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8744.67 | 15.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8647.67 | 112.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8685.83 | 74.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8632.00 | 128.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8618.50 | 141.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8618.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 141.50 | 0.00 | 0.00 | 0.00 |
Average | 8699.38 | 60.62 | 0.00 | 0.00 | 0.00 |
Sum | 156588.83 | 1091.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128302.00 | 2.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 2.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.22 | 0.11 | 0.00 | 0.00 | 0.00 |
Sum | 614578.00 | 2.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8226.67 | 533.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8384.17 | 375.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8478.00 | 282.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8291.17 | 468.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8208.33 | 551.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8233.67 | 526.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8168.67 | 591.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8422.67 | 337.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8225.17 | 534.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8194.67 | 565.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8174.83 | 585.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8239.33 | 520.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8158.50 | 601.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8196.00 | 564.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8125.33 | 634.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7881.83 | 878.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8235.17 | 524.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8304.50 | 455.50 | 0.00 | 0.00 | 0.00 |
Min | 7881.83 | 282.00 | 0.00 | 0.00 | 0.00 |
Max | 8478.00 | 878.17 | 0.00 | 0.00 | 0.00 |
Average | 8230.48 | 529.52 | 0.00 | 0.00 | 0.00 |
Sum | 148148.67 | 9531.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127956.50 | 347.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128110.50 | 193.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128195.67 | 108.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24848.17 | 60.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 13980.00 | 36.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24847.50 | 61.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 13978.17 | 37.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24876.17 | 32.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14006.00 | 10.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24367.17 | 541.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14006.67 | 9.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24872.17 | 36.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10125.17 | 8.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24871.33 | 37.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14007.17 | 8.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128195.67 | 541.83 | 0.00 | 0.00 | 0.00 |
Average | 34058.24 | 85.09 | 0.00 | 0.00 | 0.00 |
Sum | 613048.33 | 1531.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:06
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.743827E+10 | 9361.53 | 13-JAN-17:00 | 2.20 | 0.77 | 0.168329E+10 | 2606.56 | 13-JAN-14:20 | 2.20 | 0.77 |
February | 0.756253E+10 | 10193.67 | 24-FEB-17:00 | 7.20 | 5.13 | 0.163043E+10 | 2606.64 | 24-FEB-14:20 | 7.20 | 5.13 |
March | 0.109811E+11 | 16065.95 | 30-MAR-07:03 | 1.10 | 0.61 | 0.208645E+10 | 2606.65 | 17-MAR-09:09 | 1.10 | 0.61 |
April | 0.136377E+11 | 37381.55 | 17-APR-06:02 | 10.00 | 8.65 | 0.189422E+10 | 2606.68 | 11-APR-13:09 | 10.00 | 8.65 |
May | 0.202737E+11 | 41179.37 | 30-MAY-05:12 | 14.60 | 14.60 | 0.207539E+10 | 2606.71 | 09-MAY-13:09 | 14.60 | 14.60 |
June | 0.242466E+11 | 41306.90 | 19-JUN-05:12 | 11.87 | 10.77 | 0.207084E+10 | 2606.69 | 01-JUN-09:00 | 11.87 | 10.77 |
July | 0.249693E+11 | 41673.69 | 17-JUL-05:12 | 16.33 | 16.20 | 0.192592E+10 | 2606.66 | 19-JUL-09:20 | 21.47 | 17.08 |
August | 0.264282E+11 | 41507.27 | 14-AUG-05:12 | 15.77 | 15.05 | 0.216213E+10 | 2891.33 | 04-AUG-07:49 | 15.77 | 15.05 |
September | 0.219307E+11 | 41473.26 | 12-SEP-05:12 | 15.93 | 15.59 | 0.191804E+10 | 2606.65 | 21-SEP-13:09 | 12.80 | 11.83 |
October | 0.154441E+11 | 18087.84 | 04-OCT-08:00 | 8.10 | 6.47 | 0.198665E+10 | 2606.66 | 20-OCT-09:20 | 13.20 | 9.25 |
November | 0.112797E+11 | 17792.46 | 03-NOV-16:00 | 15.00 | 9.33 | 0.189602E+10 | 2606.66 | 14-NOV-10:20 | 3.70 | 2.00 |
December | 0.806295E+10 | 9960.62 | 07-DEC-16:20 | -5.7 | -8.8 | 0.174560E+10 | 2606.64 | 08-DEC-10:20 | -5.0 | -5.5 |
Annual Sum or Average | 0.192255E+12 | 0.230750E+11 | ||||||||
Minimum of Months | 0.743827E+10 | 9361.53 | -5.7 | -8.8 | 0.163043E+10 | 2606.56 | -5.0 | -5.5 | ||
Maximum of Months | 0.264282E+11 | 41673.69 | 16.33 | 16.20 | 0.216213E+10 | 2891.33 | 21.47 | 17.08 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -2.8 | -3.2 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 3508959.68 | 309.92 | 24-FEB-15:10 | 8.30 | 5.66 | 0.00 | 0.00 | 01-FEB-00:10 | 8.30 | 5.66 |
March | 0.125374E+09 | 1863.92 | 24-MAR-14:30 | 13.05 | 6.50 | 0.00 | 0.00 | 01-MAR-00:10 | 13.05 | 6.50 |
April | 0.113399E+10 | 8486.12 | 18-APR-14:20 | 28.30 | 20.65 | 0.00 | 0.00 | 01-APR-00:10 | 28.30 | 20.65 |
May | 0.269541E+10 | 9511.87 | 31-MAY-14:00 | 29.40 | 19.44 | 0.00 | 0.00 | 01-MAY-00:10 | 29.40 | 19.44 |
June | 0.517257E+10 | 11033.94 | 26-JUN-13:50 | 31.60 | 21.99 | 0.00 | 0.00 | 01-JUN-00:10 | 31.60 | 21.99 |
July | 0.570105E+10 | 10375.46 | 05-JUL-14:00 | 27.20 | 19.77 | 0.00 | 0.00 | 01-JUL-00:10 | 27.20 | 19.77 |
August | 0.524296E+10 | 10771.77 | 04-AUG-15:10 | 33.90 | 25.49 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 25.49 |
September | 0.274855E+10 | 9666.81 | 07-SEP-15:00 | 31.70 | 18.53 | 0.00 | 0.00 | 01-SEP-00:10 | 31.70 | 18.53 |
October | 0.307630E+09 | 3901.03 | 20-OCT-14:50 | 23.18 | 13.31 | 0.00 | 0.00 | 01-OCT-00:10 | 23.18 | 13.31 |
November | 45473194.32 | 1903.58 | 03-NOV-14:30 | 16.10 | 10.04 | 0.00 | 0.00 | 01-NOV-00:10 | 16.10 | 10.04 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 |
Annual Sum or Average | 0.231765E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.8 | -3.2 | 0.00 | 0.00 | -2.8 | -3.2 | ||
Maximum of Months | 0.570105E+10 | 11033.94 | 33.90 | 25.49 | 0.00 | 0.00 | 33.90 | 25.49 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11200637.59 | 3283.29 | 05-JAN-05:01 | -21.2 | -21.5 | 0.00 | 0.00 | 01-JAN-00:10 | -21.2 | -21.5 |
February | 10338543.41 | 2900.06 | 16-FEB-05:01 | -17.3 | -17.7 | 0.00 | 0.00 | 01-FEB-00:10 | -17.3 | -17.7 |
March | 25784878.90 | 2217.70 | 11-MAR-06:01 | -7.5 | -8.2 | 0.00 | 0.00 | 01-MAR-00:10 | -7.5 | -8.2 |
April | 0.414636E+09 | 3617.13 | 17-APR-16:00 | 19.40 | 11.31 | 0.00 | 0.00 | 01-APR-00:10 | 19.40 | 11.31 |
May | 0.109019E+10 | 4106.72 | 30-MAY-16:00 | 27.80 | 19.90 | 0.00 | 0.00 | 01-MAY-00:10 | 27.80 | 19.90 |
June | 0.284254E+10 | 5582.99 | 26-JUN-10:10 | 28.58 | 22.40 | 0.00 | 0.00 | 01-JUN-00:10 | 28.58 | 22.40 |
July | 0.329859E+10 | 6224.73 | 05-JUL-06:15 | 19.80 | 18.77 | 0.00 | 0.00 | 01-JUL-00:10 | 19.80 | 18.77 |
August | 0.302296E+10 | 4708.22 | 04-AUG-15:40 | 33.90 | 26.00 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 26.00 |
September | 0.157122E+10 | 4431.55 | 11-SEP-14:20 | 28.70 | 20.20 | 0.00 | 0.00 | 01-SEP-00:10 | 28.70 | 20.20 |
October | 80505925.70 | 1457.90 | 14-OCT-06:03 | -1.4 | -2.3 | 0.00 | 0.00 | 01-OCT-00:10 | -1.4 | -2.3 |
November | 31277359.80 | 2080.99 | 26-NOV-01:11 | -24.4 | -24.7 | 0.00 | 0.00 | 01-NOV-00:10 | -24.4 | -24.7 |
December | 7642858.86 | 2874.73 | 28-DEC-05:01 | -17.2 | -17.5 | 0.00 | 0.00 | 01-DEC-00:10 | -17.2 | -17.5 |
Annual Sum or Average | 0.124069E+11 | 0.00 | ||||||||
Minimum of Months | 7642858.86 | 1457.90 | -24.4 | -24.7 | 0.00 | 0.00 | -24.4 | -24.7 | ||
Maximum of Months | 0.329859E+10 | 6224.73 | 33.90 | 26.00 | 0.00 | 0.00 | 33.90 | 26.00 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 39544872.19 | 2708.34 | 05-JAN-05:01 | -21.2 | -21.5 | 0.00 | 0.00 | 01-JAN-00:10 | -21.2 | -21.5 |
February | 46055244.05 | 2820.48 | 04-FEB-05:11 | -30.6 | -30.8 | 0.00 | 0.00 | 01-FEB-00:10 | -30.6 | -30.8 |
March | 88538466.38 | 2977.25 | 17-MAR-05:01 | -7.4 | -8.1 | 0.00 | 0.00 | 01-MAR-00:10 | -7.4 | -8.1 |
April | 0.563623E+09 | 3562.61 | 18-APR-15:10 | 27.75 | 20.46 | 0.00 | 0.00 | 01-APR-00:10 | 27.75 | 20.46 |
May | 0.153419E+10 | 4077.94 | 30-MAY-16:00 | 27.80 | 19.90 | 0.00 | 0.00 | 01-MAY-00:10 | 27.80 | 19.90 |
June | 0.325604E+10 | 6128.85 | 26-JUN-12:10 | 30.68 | 21.60 | 0.00 | 0.00 | 01-JUN-00:10 | 30.68 | 21.60 |
July | 0.384354E+10 | 6315.76 | 05-JUL-06:15 | 19.80 | 18.77 | 0.00 | 0.00 | 01-JUL-00:10 | 19.80 | 18.77 |
August | 0.383427E+10 | 5000.56 | 04-AUG-12:10 | 31.20 | 26.19 | 0.00 | 0.00 | 01-AUG-00:10 | 31.20 | 26.19 |
September | 0.229771E+10 | 5057.26 | 11-SEP-12:05 | 27.88 | 20.86 | 0.00 | 0.00 | 01-SEP-00:10 | 27.88 | 20.86 |
October | 0.240030E+09 | 1970.29 | 27-OCT-06:02 | 0.25 | -1.1 | 0.00 | 0.00 | 01-OCT-00:10 | 0.25 | -1.1 |
November | 86243122.04 | 2330.26 | 10-NOV-07:02 | -2.2 | -2.8 | 0.00 | 0.00 | 01-NOV-00:10 | -2.2 | -2.8 |
December | 29419823.26 | 2116.34 | 28-DEC-05:01 | -17.2 | -17.5 | 0.00 | 0.00 | 01-DEC-00:10 | -17.2 | -17.5 |
Annual Sum or Average | 0.158592E+11 | 0.00 | ||||||||
Minimum of Months | 29419823.26 | 1970.29 | -30.6 | -30.8 | 0.00 | 0.00 | -30.6 | -30.8 | ||
Maximum of Months | 0.384354E+10 | 6315.76 | 31.20 | 26.19 | 0.00 | 0.00 | 31.20 | 26.19 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.356134E+10 | 5455.48 | 13-JAN-17:00 | 2.20 | 0.77 | 0.148950E+10 | 2316.45 | 13-JAN-14:00 | 2.20 | 0.77 |
February | 0.417429E+10 | 5636.68 | 24-FEB-17:00 | 7.20 | 5.13 | 0.140131E+10 | 2342.38 | 24-FEB-16:00 | 7.20 | 5.13 |
March | 0.670578E+10 | 7861.95 | 24-MAR-16:00 | 10.60 | 5.50 | 0.183320E+10 | 2606.56 | 24-MAR-13:20 | 10.60 | 5.50 |
April | 0.883156E+10 | 24271.24 | 17-APR-06:02 | 10.00 | 8.65 | 0.177574E+10 | 2606.65 | 14-APR-09:30 | 10.00 | 8.65 |
May | 0.133933E+11 | 29491.54 | 30-MAY-05:12 | 14.60 | 14.60 | 0.205840E+10 | 2606.68 | 09-MAY-13:09 | 14.60 | 14.60 |
June | 0.167766E+11 | 30579.23 | 19-JUN-05:12 | 11.87 | 10.77 | 0.206457E+10 | 2606.66 | 26-JUN-09:20 | 27.57 | 22.45 |
July | 0.177479E+11 | 31072.43 | 31-JUL-05:12 | 17.07 | 15.19 | 0.192210E+10 | 2607.04 | 03-JUL-09:09 | 17.07 | 15.19 |
August | 0.179004E+11 | 30443.68 | 14-AUG-05:12 | 15.77 | 15.05 | 0.215735E+10 | 2728.97 | 04-AUG-07:40 | 15.77 | 15.05 |
September | 0.137665E+11 | 30656.83 | 11-SEP-05:12 | 19.80 | 17.33 | 0.190209E+10 | 2607.74 | 25-SEP-09:30 | 8.60 | 5.24 |
October | 0.829149E+10 | 9838.91 | 20-OCT-16:00 | 21.30 | 12.72 | 0.189531E+10 | 2606.62 | 19-OCT-13:20 | 21.30 | 12.72 |
November | 0.596113E+10 | 9696.84 | 03-NOV-16:00 | 15.00 | 9.33 | 0.168134E+10 | 2606.58 | 02-NOV-13:20 | 15.00 | 9.33 |
December | 0.420738E+10 | 5274.52 | 07-DEC-16:30 | -6.1 | -9.1 | 0.147860E+10 | 2271.65 | 07-DEC-14:00 | -6.1 | -9.1 |
Annual Sum or Average | 0.121318E+12 | 0.216595E+11 | ||||||||
Minimum of Months | 0.356134E+10 | 5274.52 | -6.1 | -9.1 | 0.140131E+10 | 2271.65 | -6.1 | -9.1 | ||
Maximum of Months | 0.179004E+11 | 31072.43 | 21.30 | 17.33 | 0.215735E+10 | 2728.97 | 27.57 | 22.45 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.175341E+10 | 5101.30 | 13-JAN-16:50 | 2.48 | 0.97 | 0.146102E+10 | 2220.59 | 13-JAN-14:00 | 2.48 | 0.97 |
February | 0.260263E+10 | 5559.11 | 24-FEB-17:00 | 7.20 | 5.13 | 0.135241E+10 | 2320.72 | 24-FEB-16:00 | 7.20 | 5.13 |
March | 0.508746E+10 | 7584.63 | 24-MAR-16:00 | 10.60 | 5.50 | 0.173489E+10 | 2606.44 | 24-MAR-13:00 | 10.60 | 5.50 |
April | 0.785060E+10 | 17080.77 | 17-APR-15:20 | 19.40 | 11.61 | 0.170015E+10 | 2606.67 | 18-APR-09:09 | 23.27 | 18.95 |
May | 0.129103E+11 | 21184.00 | 30-MAY-06:02 | 15.18 | 15.13 | 0.203677E+10 | 2606.69 | 09-MAY-13:09 | 15.18 | 15.13 |
June | 0.168297E+11 | 31686.23 | 12-JUN-05:12 | 17.80 | 17.26 | 0.205543E+10 | 2606.66 | 09-JUN-09:20 | 17.80 | 17.26 |
July | 0.178496E+11 | 31646.69 | 03-JUL-05:12 | 18.50 | 17.39 | 0.191952E+10 | 2606.67 | 25-JUL-09:09 | 23.68 | 19.04 |
August | 0.175450E+11 | 25246.34 | 14-AUG-06:02 | 16.10 | 15.45 | 0.215212E+10 | 2606.72 | 08-AUG-09:09 | 16.10 | 15.45 |
September | 0.124281E+11 | 31927.99 | 11-SEP-05:12 | 19.80 | 17.33 | 0.186306E+10 | 2606.74 | 06-SEP-09:39 | 19.80 | 17.33 |
October | 0.692833E+10 | 9336.71 | 20-OCT-16:00 | 21.30 | 12.72 | 0.175842E+10 | 2606.59 | 03-OCT-13:20 | 21.30 | 12.72 |
November | 0.434685E+10 | 8595.72 | 03-NOV-16:00 | 15.00 | 9.33 | 0.158137E+10 | 2606.56 | 03-NOV-13:20 | 15.00 | 9.33 |
December | 0.219498E+10 | 4945.90 | 01-DEC-16:25 | -2.8 | -4.8 | 0.141901E+10 | 2168.28 | 01-DEC-14:00 | -2.8 | -4.8 |
Annual Sum or Average | 0.108327E+12 | 0.210342E+11 | ||||||||
Minimum of Months | 0.175341E+10 | 4945.90 | -2.8 | -4.8 | 0.135241E+10 | 2168.28 | -2.8 | -4.8 | ||
Maximum of Months | 0.178496E+11 | 31927.99 | 21.30 | 17.39 | 0.215212E+10 | 2606.74 | 23.68 | 19.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11323525.75 | 861.93 | 14-JAN-17:02 | -7.4 | -8.6 | 0.301874E+09 | 406.71 | 18-JAN-14:00 | -17.2 | -17.5 |
February | 34991823.90 | 1032.64 | 24-FEB-15:50 | 8.30 | 5.84 | 0.275096E+09 | 422.41 | 24-FEB-14:00 | 8.30 | 5.84 |
March | 0.412389E+09 | 1361.53 | 28-MAR-15:30 | 16.40 | 10.50 | 0.340964E+09 | 506.41 | 28-MAR-15:39 | 16.13 | 10.43 |
April | 0.131532E+10 | 5653.98 | 18-APR-15:00 | 28.30 | 20.65 | 0.329153E+09 | 549.50 | 18-APR-09:20 | 28.30 | 20.65 |
May | 0.308599E+10 | 6124.04 | 31-MAY-14:50 | 29.90 | 19.65 | 0.416980E+09 | 549.50 | 09-MAY-13:09 | 29.90 | 19.65 |
June | 0.493292E+10 | 12375.06 | 25-JUN-17:21 | 31.40 | 21.75 | 0.428981E+09 | 549.50 | 09-JUN-09:20 | 31.40 | 21.75 |
July | 0.519665E+10 | 10347.77 | 02-JUL-16:51 | 28.90 | 21.17 | 0.404211E+09 | 549.50 | 19-JUL-09:20 | 21.47 | 17.08 |
August | 0.485321E+10 | 6776.16 | 04-AUG-15:20 | 33.90 | 25.66 | 0.450782E+09 | 549.51 | 30-AUG-13:00 | 23.90 | 18.14 |
September | 0.285010E+10 | 6124.83 | 11-SEP-14:00 | 28.90 | 20.23 | 0.374821E+09 | 549.51 | 06-SEP-09:39 | 28.90 | 20.23 |
October | 0.973980E+09 | 1633.13 | 20-OCT-15:30 | 22.30 | 13.06 | 0.334127E+09 | 535.00 | 20-OCT-15:00 | 21.30 | 12.72 |
November | 0.416443E+09 | 1379.68 | 03-NOV-15:30 | 15.55 | 9.47 | 0.312771E+09 | 516.27 | 03-NOV-13:00 | 15.55 | 9.47 |
December | 8043592.88 | 863.30 | 02-DEC-17:03 | 1.70 | 0.90 | 0.292782E+09 | 406.76 | 08-DEC-14:00 | -15.6 | -15.9 |
Annual Sum or Average | 0.240914E+11 | 0.426254E+10 | ||||||||
Minimum of Months | 8043592.88 | 861.93 | -7.4 | -8.6 | 0.275096E+09 | 406.71 | -17.2 | -17.5 | ||
Maximum of Months | 0.519665E+10 | 12375.06 | 33.90 | 25.66 | 0.450782E+09 | 549.51 | 31.40 | 21.75 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 29433319.98 | 576.90 | 12-JAN-10:30 | -1.4 | -2.2 | 0.192842E+09 | 270.44 | 12-JAN-10:39 | -0.9 | -1.9 |
February | 93325341.82 | 818.67 | 24-FEB-10:30 | 5.00 | 1.88 | 0.177869E+09 | 343.70 | 24-FEB-10:30 | 5.00 | 1.88 |
March | 0.474138E+09 | 2542.19 | 28-MAR-09:35 | 9.07 | 5.68 | 0.229770E+09 | 347.88 | 28-MAR-09:00 | 10.00 | 6.30 |
April | 0.138160E+10 | 7836.46 | 18-APR-09:30 | 24.20 | 19.59 | 0.221611E+09 | 347.88 | 18-APR-09:09 | 24.20 | 19.59 |
May | 0.313195E+10 | 11136.90 | 28-MAY-09:02 | 19.68 | 17.00 | 0.273259E+09 | 348.38 | 31-MAY-09:50 | 27.02 | 19.46 |
June | 0.488315E+10 | 14198.90 | 25-JUN-08:42 | 25.73 | 21.05 | 0.273041E+09 | 348.45 | 26-JUN-09:00 | 28.30 | 22.44 |
July | 0.524018E+10 | 14476.48 | 02-JUL-09:32 | 26.33 | 21.34 | 0.256832E+09 | 348.56 | 05-JUL-09:30 | 23.60 | 20.34 |
August | 0.473195E+10 | 11874.81 | 27-AUG-08:53 | 22.80 | 19.47 | 0.287170E+09 | 348.48 | 02-AUG-09:50 | 22.80 | 19.47 |
September | 0.297671E+10 | 14044.93 | 04-SEP-09:32 | 17.57 | 12.97 | 0.246597E+09 | 347.90 | 06-SEP-09:39 | 24.67 | 18.11 |
October | 0.779327E+09 | 3028.61 | 20-OCT-09:30 | 13.70 | 9.50 | 0.229461E+09 | 347.88 | 20-OCT-09:20 | 13.70 | 9.50 |
November | 0.284313E+09 | 1025.34 | 04-NOV-09:30 | 7.50 | 4.04 | 0.201068E+09 | 347.86 | 03-NOV-13:20 | 7.50 | 4.04 |
December | 14625724.05 | 544.04 | 01-DEC-10:20 | -2.9 | -4.5 | 0.186005E+09 | 261.06 | 01-DEC-10:30 | -2.8 | -4.4 |
Annual Sum or Average | 0.240207E+11 | 0.277552E+10 | ||||||||
Minimum of Months | 14625724.05 | 544.04 | -2.9 | -4.5 | 0.177869E+09 | 261.06 | -2.8 | -4.4 | ||
Maximum of Months | 0.524018E+10 | 14476.48 | 26.33 | 21.34 | 0.287170E+09 | 348.56 | 28.30 | 22.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.471889E+09 | 4577.78 | 12-JAN-12:30 | 1.95 | 0.38 | 0.326495E+09 | 549.50 | 03-JAN-14:20 | 1.95 | 0.38 |
February | 0.736261E+09 | 7896.09 | 24-FEB-13:45 | 7.62 | 4.99 | 0.302115E+09 | 549.50 | 24-FEB-14:20 | 7.97 | 5.32 |
March | 0.143429E+10 | 8368.78 | 24-MAR-13:30 | 12.75 | 6.50 | 0.375658E+09 | 549.50 | 22-MAR-13:00 | 12.75 | 6.50 |
April | 0.272821E+10 | 17169.65 | 16-APR-13:32 | 27.43 | 20.35 | 0.349312E+09 | 549.88 | 18-APR-13:50 | 28.12 | 20.65 |
May | 0.420875E+10 | 10703.19 | 29-MAY-13:23 | 24.15 | 19.85 | 0.422892E+09 | 549.77 | 30-MAY-13:39 | 26.70 | 19.86 |
June | 0.596097E+10 | 16502.88 | 11-JUN-15:22 | 33.05 | 24.40 | 0.429295E+09 | 550.19 | 26-JUN-13:50 | 31.60 | 21.99 |
July | 0.663146E+10 | 17122.09 | 30-JUL-13:12 | 26.87 | 20.18 | 0.404341E+09 | 549.98 | 31-JUL-13:00 | 26.10 | 21.45 |
August | 0.713007E+10 | 12817.73 | 29-AUG-13:30 | 23.60 | 16.39 | 0.451989E+09 | 550.26 | 21-AUG-13:50 | 23.60 | 16.39 |
September | 0.564134E+10 | 18731.31 | 04-SEP-12:52 | 21.10 | 14.00 | 0.386768E+09 | 557.05 | 07-SEP-13:20 | 31.87 | 18.17 |
October | 0.270458E+10 | 11456.05 | 20-OCT-13:05 | 21.93 | 12.68 | 0.374644E+09 | 549.64 | 20-OCT-13:00 | 22.60 | 13.03 |
November | 0.995442E+09 | 10383.62 | 03-NOV-13:30 | 15.85 | 10.76 | 0.333213E+09 | 549.59 | 03-NOV-13:00 | 16.10 | 10.47 |
December | 0.568746E+09 | 5676.79 | 01-DEC-13:25 | -0.9 | -3.3 | 0.316409E+09 | 549.49 | 15-DEC-14:20 | -7.6 | -9.3 |
Annual Sum or Average | 0.392120E+11 | 0.447313E+10 | ||||||||
Minimum of Months | 0.471889E+09 | 4577.78 | -0.9 | -3.3 | 0.302115E+09 | 549.49 | -7.6 | -9.3 | ||
Maximum of Months | 0.713007E+10 | 18731.31 | 33.05 | 24.40 | 0.451989E+09 | 557.05 | 31.87 | 21.99 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 43087390.11 | 768.08 | 12-JAN-16:00 | 2.80 | 1.13 | 0.193868E+09 | 319.69 | 12-JAN-16:10 | 2.62 | 1.03 |
February | 0.129623E+09 | 2737.76 | 24-FEB-16:30 | 7.75 | 5.51 | 0.179236E+09 | 347.82 | 24-FEB-14:00 | 7.75 | 5.51 |
March | 0.484680E+09 | 3166.67 | 23-MAR-16:00 | 17.20 | 10.15 | 0.223439E+09 | 347.82 | 28-MAR-13:00 | 16.70 | 10.30 |
April | 0.166115E+10 | 15614.21 | 16-APR-16:12 | 28.70 | 20.49 | 0.215821E+09 | 347.85 | 18-APR-09:20 | 23.73 | 19.27 |
May | 0.298209E+10 | 17031.65 | 14-MAY-16:31 | 21.70 | 15.60 | 0.266136E+09 | 347.86 | 09-MAY-13:20 | 21.70 | 15.60 |
June | 0.473118E+10 | 16300.50 | 25-JUN-16:41 | 31.78 | 21.74 | 0.271916E+09 | 347.86 | 09-JUN-09:20 | 31.78 | 21.74 |
July | 0.519124E+10 | 16282.22 | 02-JUL-16:51 | 28.90 | 21.17 | 0.256213E+09 | 347.85 | 19-JUL-09:20 | 21.47 | 17.08 |
August | 0.486312E+10 | 14819.55 | 05-AUG-17:04 | 25.32 | 17.94 | 0.286171E+09 | 347.86 | 30-AUG-13:00 | 23.90 | 18.14 |
September | 0.293037E+10 | 16686.60 | 04-SEP-16:51 | 22.20 | 14.41 | 0.239851E+09 | 347.86 | 06-SEP-09:39 | 24.67 | 18.11 |
October | 0.965685E+09 | 5611.76 | 20-OCT-15:30 | 22.30 | 13.06 | 0.221864E+09 | 347.84 | 11-OCT-13:20 | 22.30 | 13.06 |
November | 0.328703E+09 | 3698.27 | 03-NOV-15:30 | 15.55 | 9.47 | 0.201478E+09 | 347.83 | 03-NOV-13:20 | 15.55 | 9.47 |
December | 63308240.72 | 762.40 | 01-DEC-15:50 | -1.6 | -4.0 | 0.187706E+09 | 318.57 | 01-DEC-15:00 | -1.7 | -4.1 |
Annual Sum or Average | 0.243742E+11 | 0.274370E+10 | ||||||||
Minimum of Months | 43087390.11 | 762.40 | -1.6 | -4.0 | 0.179236E+09 | 318.57 | -1.7 | -4.1 | ||
Maximum of Months | 0.519124E+10 | 17031.65 | 31.78 | 21.74 | 0.286171E+09 | 347.86 | 31.78 | 21.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11136732.47 | 832.11 | 14-JAN-17:02 | -7.4 | -8.6 | 0.300379E+09 | 406.72 | 18-JAN-14:00 | -17.2 | -17.5 |
February | 19421402.08 | 831.58 | 11-FEB-17:02 | -3.4 | -4.7 | 0.274297E+09 | 406.71 | 03-FEB-14:09 | -3.4 | -4.7 |
March | 0.308460E+09 | 1109.63 | 28-MAR-15:30 | 16.40 | 10.50 | 0.337224E+09 | 459.39 | 28-MAR-13:00 | 16.40 | 10.50 |
April | 0.865061E+09 | 3121.21 | 18-APR-15:00 | 28.30 | 20.65 | 0.318609E+09 | 549.49 | 17-APR-13:20 | 28.30 | 20.65 |
May | 0.202754E+10 | 3934.84 | 31-MAY-15:00 | 30.00 | 19.70 | 0.406934E+09 | 549.50 | 05-MAY-13:20 | 30.00 | 19.70 |
June | 0.364913E+10 | 5482.30 | 26-JUN-14:30 | 31.40 | 21.97 | 0.429229E+09 | 549.50 | 01-JUN-13:20 | 31.40 | 21.97 |
July | 0.418807E+10 | 7449.31 | 05-JUL-06:03 | 19.60 | 18.69 | 0.404267E+09 | 549.50 | 19-JUL-09:20 | 21.47 | 17.08 |
August | 0.427750E+10 | 5552.81 | 04-AUG-15:30 | 33.90 | 25.83 | 0.453251E+09 | 571.04 | 04-AUG-07:49 | 33.90 | 25.83 |
September | 0.286153E+10 | 5776.51 | 11-SEP-06:03 | 19.50 | 17.29 | 0.388803E+09 | 549.50 | 06-SEP-09:20 | 19.50 | 17.29 |
October | 0.140404E+10 | 1503.47 | 20-OCT-13:50 | 22.47 | 12.96 | 0.356184E+09 | 540.23 | 02-OCT-13:00 | 22.47 | 12.96 |
November | 0.621829E+09 | 1308.96 | 03-NOV-15:20 | 15.73 | 9.52 | 0.323310E+09 | 522.65 | 03-NOV-13:00 | 15.73 | 9.52 |
December | 10333517.50 | 831.40 | 02-DEC-17:03 | 1.70 | 0.90 | 0.293519E+09 | 406.72 | 08-DEC-14:00 | -15.6 | -15.9 |
Annual Sum or Average | 0.202440E+11 | 0.428601E+10 | ||||||||
Minimum of Months | 10333517.50 | 831.40 | -7.4 | -8.6 | 0.274297E+09 | 406.71 | -17.2 | -17.5 | ||
Maximum of Months | 0.427750E+10 | 7449.31 | 33.90 | 25.83 | 0.453251E+09 | 571.04 | 33.90 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30954459.19 | 583.42 | 13-JAN-11:20 | 2.77 | 0.85 | 0.193149E+09 | 271.23 | 13-JAN-10:00 | 2.77 | 0.85 |
February | 76031223.14 | 723.18 | 24-FEB-10:10 | 4.60 | 1.53 | 0.177064E+09 | 314.00 | 24-FEB-10:20 | 4.80 | 1.70 |
March | 0.408795E+09 | 1199.65 | 28-MAR-09:35 | 9.07 | 5.68 | 0.226400E+09 | 347.88 | 28-MAR-09:20 | 9.07 | 5.68 |
April | 0.971807E+09 | 5327.04 | 18-APR-09:30 | 24.20 | 19.59 | 0.217948E+09 | 347.88 | 13-APR-09:09 | 24.20 | 19.59 |
May | 0.223006E+10 | 6199.93 | 31-MAY-09:20 | 26.47 | 19.61 | 0.272711E+09 | 347.88 | 09-MAY-09:20 | 26.47 | 19.61 |
June | 0.401503E+10 | 11249.60 | 11-JUN-09:41 | 27.62 | 21.00 | 0.274035E+09 | 362.70 | 26-JUN-07:00 | 25.00 | 21.93 |
July | 0.461247E+10 | 12108.92 | 04-JUL-08:41 | 22.70 | 19.71 | 0.257023E+09 | 348.24 | 05-JUL-09:09 | 23.07 | 20.39 |
August | 0.450101E+10 | 8175.25 | 20-AUG-10:13 | 22.80 | 18.82 | 0.287965E+09 | 374.05 | 04-AUG-07:49 | 22.80 | 18.82 |
September | 0.313426E+10 | 11440.58 | 04-SEP-09:32 | 17.57 | 12.97 | 0.252539E+09 | 347.88 | 06-SEP-09:20 | 23.73 | 17.58 |
October | 0.107232E+10 | 2662.00 | 20-OCT-09:40 | 14.20 | 9.74 | 0.247069E+09 | 347.88 | 20-OCT-09:20 | 14.20 | 9.74 |
November | 0.430423E+09 | 1245.86 | 04-NOV-08:55 | 5.60 | 2.83 | 0.209328E+09 | 347.87 | 03-NOV-13:20 | 5.60 | 2.83 |
December | 36515632.16 | 587.87 | 05-DEC-09:30 | -6.4 | -8.4 | 0.186847E+09 | 271.44 | 05-DEC-10:09 | -5.9 | -8.1 |
Annual Sum or Average | 0.215197E+11 | 0.280208E+10 | ||||||||
Minimum of Months | 30954459.19 | 583.42 | -6.4 | -8.4 | 0.177064E+09 | 271.23 | -5.9 | -8.1 | ||
Maximum of Months | 0.461247E+10 | 12108.92 | 27.62 | 21.00 | 0.287965E+09 | 374.05 | 26.47 | 21.93 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 75538183.07 | 1143.91 | 13-JAN-14:30 | 3.90 | 1.72 | 0.275992E+09 | 496.40 | 13-JAN-14:39 | 3.90 | 1.72 |
February | 0.174303E+09 | 1752.52 | 24-FEB-14:25 | 8.05 | 5.40 | 0.263935E+09 | 549.51 | 24-FEB-14:20 | 8.05 | 5.40 |
March | 0.521610E+09 | 3841.77 | 24-MAR-14:00 | 13.30 | 6.51 | 0.338091E+09 | 549.50 | 28-MAR-13:09 | 15.78 | 9.88 |
April | 0.124124E+10 | 9494.25 | 18-APR-12:00 | 27.80 | 20.94 | 0.325134E+09 | 549.56 | 18-APR-13:39 | 27.93 | 20.65 |
May | 0.233362E+10 | 9986.43 | 31-MAY-12:00 | 29.40 | 19.85 | 0.398942E+09 | 549.51 | 03-MAY-13:20 | 29.40 | 19.85 |
June | 0.434142E+10 | 11577.14 | 26-JUN-16:10 | 31.60 | 21.99 | 0.419800E+09 | 559.06 | 26-JUN-12:09 | 31.60 | 21.99 |
July | 0.548405E+10 | 13198.52 | 02-JUL-15:21 | 29.40 | 21.49 | 0.402180E+09 | 549.62 | 05-JUL-13:00 | 27.20 | 19.77 |
August | 0.653812E+10 | 11595.88 | 04-AUG-12:00 | 31.10 | 26.10 | 0.450921E+09 | 571.46 | 04-AUG-12:09 | 31.20 | 26.19 |
September | 0.520008E+10 | 14476.37 | 04-SEP-12:52 | 21.10 | 14.00 | 0.385785E+09 | 604.33 | 07-SEP-12:09 | 30.78 | 18.58 |
October | 0.212464E+10 | 10009.93 | 01-OCT-13:33 | 18.90 | 12.26 | 0.372772E+09 | 549.56 | 20-OCT-13:00 | 22.60 | 13.03 |
November | 0.801016E+09 | 8266.85 | 03-NOV-12:07 | 15.60 | 11.02 | 0.317503E+09 | 549.49 | 03-NOV-13:20 | 15.77 | 10.85 |
December | 0.207050E+09 | 1260.35 | 02-DEC-12:40 | 5.40 | 2.84 | 0.280356E+09 | 516.78 | 01-DEC-14:39 | 5.40 | 2.84 |
Annual Sum or Average | 0.290427E+11 | 0.423141E+10 | ||||||||
Minimum of Months | 75538183.07 | 1143.91 | 3.90 | 1.72 | 0.263935E+09 | 496.40 | 3.90 | 1.72 | ||
Maximum of Months | 0.653812E+10 | 14476.37 | 31.60 | 26.10 | 0.450921E+09 | 604.33 | 31.60 | 26.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30739786.33 | 707.23 | 12-JAN-16:10 | 2.62 | 1.03 | 0.193614E+09 | 298.47 | 12-JAN-16:10 | 2.62 | 1.03 |
February | 89993386.82 | 1513.12 | 24-FEB-16:40 | 7.57 | 5.38 | 0.178030E+09 | 338.67 | 24-FEB-16:00 | 7.20 | 5.13 |
March | 0.374803E+09 | 1530.68 | 23-MAR-16:00 | 17.20 | 10.15 | 0.220793E+09 | 338.68 | 24-MAR-15:30 | 11.70 | 6.01 |
April | 0.111269E+10 | 8598.30 | 15-APR-17:04 | 29.72 | 18.80 | 0.215707E+09 | 347.85 | 18-APR-09:20 | 23.73 | 19.27 |
May | 0.199712E+10 | 12143.13 | 14-MAY-16:31 | 21.70 | 15.60 | 0.265584E+09 | 347.85 | 09-MAY-09:39 | 21.70 | 15.60 |
June | 0.380488E+10 | 12508.40 | 25-JUN-17:21 | 31.40 | 21.75 | 0.272883E+09 | 347.86 | 20-JUN-13:00 | 31.40 | 21.75 |
July | 0.453276E+10 | 12727.12 | 02-JUL-18:01 | 28.12 | 21.02 | 0.256931E+09 | 347.86 | 19-JUL-09:20 | 21.47 | 17.08 |
August | 0.458375E+10 | 10371.43 | 05-AUG-17:04 | 25.32 | 17.94 | 0.287942E+09 | 347.87 | 08-AUG-09:09 | 20.28 | 15.58 |
September | 0.298982E+10 | 12983.77 | 04-SEP-16:51 | 22.20 | 14.41 | 0.249656E+09 | 347.85 | 06-SEP-09:20 | 23.73 | 17.58 |
October | 0.121812E+10 | 4681.92 | 11-OCT-16:00 | 17.80 | 11.96 | 0.239036E+09 | 347.85 | 19-OCT-13:20 | 17.33 | 9.97 |
November | 0.471147E+09 | 3089.96 | 03-NOV-15:40 | 15.37 | 9.43 | 0.210161E+09 | 347.84 | 03-NOV-13:20 | 15.37 | 9.43 |
December | 69900491.85 | 738.85 | 01-DEC-15:50 | -1.6 | -4.0 | 0.188182E+09 | 309.39 | 01-DEC-15:00 | -1.7 | -4.1 |
Annual Sum or Average | 0.212757E+11 | 0.277852E+10 | ||||||||
Minimum of Months | 30739786.33 | 707.23 | -1.6 | -4.0 | 0.178030E+09 | 298.47 | -1.7 | -4.1 | ||
Maximum of Months | 0.458375E+10 | 12983.77 | 31.40 | 21.75 | 0.287942E+09 | 347.87 | 31.40 | 21.75 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 24477531.74 | 852.01 | 13-JAN-14:40 | 3.90 | 1.72 | 0.302425E+09 | 408.15 | 13-JAN-14:50 | 3.90 | 1.72 |
February | 61041169.55 | 960.08 | 24-FEB-16:30 | 7.75 | 5.51 | 0.276241E+09 | 431.94 | 24-FEB-14:00 | 7.75 | 5.51 |
March | 0.564798E+09 | 1258.34 | 28-MAR-15:30 | 16.40 | 10.50 | 0.348098E+09 | 520.44 | 24-MAR-13:00 | 16.40 | 10.50 |
April | 0.146955E+10 | 5233.66 | 18-APR-15:00 | 28.30 | 20.65 | 0.341791E+09 | 549.49 | 18-APR-09:20 | 28.30 | 20.65 |
May | 0.309539E+10 | 5665.71 | 31-MAY-06:03 | 18.27 | 16.32 | 0.426206E+09 | 549.51 | 09-MAY-09:20 | 18.27 | 16.32 |
June | 0.481843E+10 | 9955.20 | 25-JUN-18:31 | 29.97 | 21.56 | 0.433226E+09 | 551.68 | 26-JUN-08:09 | 25.37 | 22.03 |
July | 0.510120E+10 | 8775.86 | 04-JUL-18:42 | 25.28 | 21.09 | 0.405153E+09 | 550.47 | 03-JUL-13:20 | 25.28 | 21.09 |
August | 0.484174E+10 | 6497.46 | 04-AUG-07:33 | 25.03 | 24.26 | 0.453563E+09 | 565.99 | 04-AUG-07:40 | 25.03 | 24.26 |
September | 0.299180E+10 | 7286.82 | 11-SEP-06:03 | 19.50 | 17.29 | 0.388315E+09 | 549.50 | 06-SEP-09:20 | 19.50 | 17.29 |
October | 0.129628E+10 | 1824.38 | 02-OCT-15:00 | 18.30 | 14.84 | 0.355861E+09 | 549.49 | 03-OCT-13:20 | 12.97 | 9.14 |
November | 0.559449E+09 | 1453.87 | 03-NOV-13:10 | 15.68 | 10.94 | 0.323447E+09 | 531.95 | 07-NOV-14:30 | 13.05 | 11.26 |
December | 9318259.24 | 795.43 | 02-DEC-17:03 | 1.70 | 0.90 | 0.293460E+09 | 406.73 | 08-DEC-14:00 | -15.6 | -15.9 |
Annual Sum or Average | 0.248335E+11 | 0.434778E+10 | ||||||||
Minimum of Months | 9318259.24 | 795.43 | 1.70 | 0.90 | 0.276241E+09 | 406.73 | -15.6 | -15.9 | ||
Maximum of Months | 0.510120E+10 | 9955.20 | 29.97 | 24.26 | 0.453563E+09 | 565.99 | 28.30 | 24.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34524008.18 | 661.21 | 13-JAN-11:05 | 2.48 | 0.68 | 0.141706E+09 | 288.51 | 13-JAN-11:09 | 2.48 | 0.68 |
February | 0.105615E+09 | 2038.99 | 24-FEB-11:05 | 5.68 | 2.52 | 0.131586E+09 | 356.46 | 24-FEB-11:09 | 5.68 | 2.52 |
March | 0.508348E+09 | 4863.30 | 24-MAR-12:02 | 11.78 | 6.31 | 0.173253E+09 | 356.78 | 28-MAR-10:09 | 10.47 | 6.54 |
April | 0.142825E+10 | 8301.72 | 18-APR-10:05 | 25.78 | 20.58 | 0.168512E+09 | 356.46 | 14-APR-10:09 | 25.78 | 20.58 |
May | 0.309392E+10 | 14009.64 | 29-MAY-09:12 | 22.77 | 18.33 | 0.203524E+09 | 356.47 | 04-MAY-10:09 | 22.77 | 18.33 |
June | 0.464892E+10 | 15445.55 | 25-JUN-08:31 | 25.37 | 20.95 | 0.203691E+09 | 375.17 | 26-JUN-08:09 | 25.37 | 22.03 |
July | 0.502259E+10 | 15392.31 | 04-JUL-08:61 | 22.30 | 19.61 | 0.191236E+09 | 356.46 | 18-JUL-10:09 | 22.30 | 15.22 |
August | 0.455721E+10 | 14210.63 | 27-AUG-09:22 | 23.60 | 19.50 | 0.213146E+09 | 360.49 | 04-AUG-07:40 | 23.60 | 19.50 |
September | 0.301637E+10 | 11594.51 | 17-SEP-08:53 | 21.70 | 16.10 | 0.185668E+09 | 356.45 | 05-SEP-14:09 | 21.70 | 16.10 |
October | 0.874120E+09 | 4832.24 | 03-OCT-12:02 | 12.30 | 9.04 | 0.178107E+09 | 356.45 | 30-OCT-12:09 | 16.13 | 9.73 |
November | 0.324919E+09 | 2971.17 | 03-NOV-12:03 | 15.60 | 11.02 | 0.152653E+09 | 356.44 | 03-NOV-12:09 | 15.60 | 11.02 |
December | 37116514.72 | 625.64 | 05-DEC-09:50 | -6.2 | -8.3 | 0.136867E+09 | 276.85 | 05-DEC-09:00 | -6.1 | -8.3 |
Annual Sum or Average | 0.236519E+11 | 0.207995E+10 | ||||||||
Minimum of Months | 34524008.18 | 625.64 | -6.2 | -8.3 | 0.131586E+09 | 276.85 | -6.1 | -8.3 | ||
Maximum of Months | 0.502259E+10 | 15445.55 | 25.78 | 20.95 | 0.213146E+09 | 375.17 | 25.78 | 22.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.602908E+09 | 5347.06 | 12-JAN-12:30 | 1.95 | 0.38 | 0.332057E+09 | 549.50 | 03-JAN-14:20 | 1.95 | 0.38 |
February | 0.882983E+09 | 8097.59 | 24-FEB-13:35 | 7.43 | 4.81 | 0.309343E+09 | 549.50 | 24-FEB-14:20 | 7.97 | 5.32 |
March | 0.175110E+10 | 8534.87 | 24-MAR-13:10 | 12.38 | 6.48 | 0.385230E+09 | 549.50 | 28-MAR-13:09 | 15.78 | 9.88 |
April | 0.295884E+10 | 15736.39 | 16-APR-13:22 | 27.25 | 20.22 | 0.360532E+09 | 550.39 | 18-APR-13:20 | 27.57 | 20.63 |
May | 0.429690E+10 | 13990.78 | 29-MAY-12:32 | 24.63 | 19.18 | 0.429378E+09 | 550.73 | 30-MAY-13:20 | 26.70 | 19.86 |
June | 0.585392E+10 | 15778.78 | 25-JUN-12:32 | 31.33 | 22.61 | 0.433154E+09 | 550.80 | 30-JUN-13:20 | 29.40 | 21.96 |
July | 0.652779E+10 | 16342.85 | 30-JUL-13:42 | 27.12 | 19.61 | 0.405362E+09 | 550.86 | 05-JUL-13:20 | 27.12 | 19.61 |
August | 0.710534E+10 | 15321.88 | 13-AUG-16:11 | 25.40 | 20.51 | 0.454143E+09 | 551.12 | 04-AUG-07:40 | 25.40 | 20.51 |
September | 0.588920E+10 | 15964.10 | 04-SEP-13:02 | 21.20 | 14.03 | 0.395830E+09 | 566.67 | 07-SEP-13:20 | 31.87 | 18.17 |
October | 0.331727E+10 | 15690.67 | 01-OCT-13:13 | 18.80 | 12.23 | 0.390473E+09 | 549.66 | 20-OCT-13:20 | 22.07 | 12.75 |
November | 0.128121E+10 | 10663.77 | 03-NOV-13:05 | 15.68 | 10.94 | 0.346264E+09 | 549.61 | 03-NOV-13:00 | 16.10 | 10.47 |
December | 0.743493E+09 | 6275.97 | 01-DEC-13:25 | -0.9 | -3.3 | 0.321137E+09 | 549.50 | 28-DEC-14:20 | -4.8 | -6.0 |
Annual Sum or Average | 0.412110E+11 | 0.456290E+10 | ||||||||
Minimum of Months | 0.602908E+09 | 5347.06 | -0.9 | -3.3 | 0.309343E+09 | 549.50 | -4.8 | -6.0 | ||
Maximum of Months | 0.710534E+10 | 16342.85 | 31.33 | 22.61 | 0.454143E+09 | 566.67 | 31.87 | 21.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 65167420.86 | 795.83 | 12-JAN-16:00 | 2.80 | 1.13 | 0.194523E+09 | 328.11 | 12-JAN-16:10 | 2.62 | 1.03 |
February | 0.174446E+09 | 2779.15 | 24-FEB-16:30 | 7.75 | 5.51 | 0.180493E+09 | 347.84 | 24-FEB-14:00 | 7.75 | 5.51 |
March | 0.623291E+09 | 3282.81 | 23-MAR-16:00 | 17.20 | 10.15 | 0.227969E+09 | 347.83 | 28-MAR-13:50 | 16.52 | 10.22 |
April | 0.179035E+10 | 15342.60 | 16-APR-17:21 | 27.50 | 20.07 | 0.223196E+09 | 347.85 | 18-APR-09:20 | 23.73 | 19.27 |
May | 0.301099E+10 | 13599.32 | 14-MAY-16:42 | 21.70 | 15.70 | 0.270775E+09 | 347.86 | 09-MAY-09:20 | 21.70 | 15.70 |
June | 0.464468E+10 | 15986.69 | 25-JUN-17:51 | 31.10 | 21.81 | 0.274308E+09 | 347.86 | 20-JUN-13:00 | 31.10 | 21.81 |
July | 0.511132E+10 | 15079.99 | 30-JUL-17:01 | 25.92 | 18.82 | 0.256823E+09 | 347.94 | 03-JUL-09:09 | 25.92 | 18.82 |
August | 0.484264E+10 | 15483.34 | 13-AUG-16:11 | 25.40 | 20.51 | 0.287512E+09 | 348.99 | 04-AUG-07:40 | 25.40 | 20.51 |
September | 0.305180E+10 | 13382.72 | 04-SEP-16:22 | 22.20 | 14.41 | 0.247040E+09 | 347.86 | 06-SEP-09:20 | 23.73 | 17.58 |
October | 0.124525E+10 | 5628.93 | 20-OCT-15:30 | 22.30 | 13.06 | 0.233045E+09 | 347.85 | 19-OCT-13:20 | 22.30 | 13.06 |
November | 0.443338E+09 | 3892.50 | 03-NOV-15:30 | 15.55 | 9.47 | 0.208548E+09 | 347.83 | 03-NOV-13:20 | 15.55 | 9.47 |
December | 84844444.21 | 798.00 | 01-DEC-15:50 | -1.6 | -4.0 | 0.189255E+09 | 329.36 | 01-DEC-15:00 | -1.7 | -4.1 |
Annual Sum or Average | 0.250881E+11 | 0.279349E+10 | ||||||||
Minimum of Months | 65167420.86 | 795.83 | -1.6 | -4.0 | 0.180493E+09 | 328.11 | -1.7 | -4.1 | ||
Maximum of Months | 0.511132E+10 | 15986.69 | 31.10 | 21.81 | 0.287512E+09 | 348.99 | 31.10 | 21.81 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.424691E+09 | 18363.74 | 02-JAN-05:01 | -4.5 |
February | 48630350.37 | 15400.16 | 06-FEB-06:11 | -15.0 |
March | 2573430.11 | 12500.28 | 06-MAR-07:01 | -12.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 13791011.30 | 15707.45 | 29-NOV-07:01 | -5.6 |
December | 41620425.86 | 16193.36 | 11-DEC-06:03 | -22.1 |
Annual Sum or Average | 0.531306E+09 | |||
Minimum of Months | 0.00 | 0.00 | -22.1 | |
Maximum of Months | 0.424691E+09 | 18363.74 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113191E+11 | 19233.91 | 19-JAN-06:12 | -27.8 |
February | 0.721886E+10 | 20406.54 | 02-FEB-06:13 | -36.7 |
March | 0.381727E+10 | 17550.43 | 06-MAR-06:05 | -14.1 |
April | 0.162483E+10 | 14176.64 | 03-APR-05:12 | -7.2 |
May | 0.409044E+09 | 4001.42 | 21-MAY-07:30 | 9.20 |
June | 0.211207E+09 | 3453.02 | 19-JUN-05:12 | 11.87 |
July | 0.117810E+09 | 3551.99 | 31-JUL-05:12 | 17.07 |
August | 0.185224E+09 | 2784.66 | 27-AUG-07:40 | 17.97 |
September | 0.631994E+09 | 6760.99 | 30-SEP-06:03 | 0.60 |
October | 0.140691E+10 | 8922.46 | 23-OCT-06:02 | -3.0 |
November | 0.491057E+10 | 17218.19 | 28-NOV-06:12 | -18.1 |
December | 0.886071E+10 | 19074.10 | 09-DEC-06:12 | -22.8 |
Annual Sum or Average | 0.407135E+11 | |||
Minimum of Months | 0.117810E+09 | 2784.66 | -36.7 | |
Maximum of Months | 0.113191E+11 | 20406.54 | 17.97 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.483727E+10 | 10827.21 | 30-JAN-07:04 | -29.0 |
February | 0.300420E+10 | 10208.71 | 06-FEB-07:05 | -15.0 |
March | 0.205228E+10 | 8985.95 | 06-MAR-07:11 | -12.6 |
April | 0.912676E+09 | 6979.59 | 03-APR-06:11 | -7.0 |
May | 0.139547E+09 | 3991.44 | 21-MAY-08:13 | 11.50 |
June | 53006516.20 | 4230.63 | 25-JUN-15:11 | 32.20 |
July | 36647408.51 | 3800.60 | 30-JUL-13:42 | 27.12 |
August | 24745181.07 | 3843.86 | 13-AUG-15:31 | 25.77 |
September | 0.214639E+09 | 4450.11 | 03-SEP-10:23 | 18.60 |
October | 0.104683E+10 | 6002.91 | 01-OCT-13:13 | 18.80 |
November | 0.220936E+10 | 10597.26 | 27-NOV-07:11 | -9.4 |
December | 0.373083E+10 | 10798.08 | 11-DEC-07:03 | -21.7 |
Annual Sum or Average | 0.182620E+11 | |||
Minimum of Months | 24745181.07 | 3800.60 | -29.0 | |
Maximum of Months | 0.483727E+10 | 10827.21 | 32.20 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.370756E+10 | 9359.81 | 02-JAN-07:01 | -5.9 |
February | 0.231200E+10 | 7292.83 | 06-FEB-07:01 | -15.0 |
March | 0.159257E+10 | 5491.28 | 06-MAR-07:01 | -12.7 |
April | 0.620568E+09 | 3665.89 | 03-APR-07:40 | -6.3 |
May | 50370519.00 | 2071.81 | 01-MAY-07:07 | 6.88 |
June | 18002516.51 | 2299.79 | 11-JUN-14:22 | 32.50 |
July | 27494946.13 | 2409.46 | 02-JUL-15:21 | 29.40 |
August | 22263467.12 | 2303.07 | 07-AUG-05:12 | 8.70 |
September | 67339325.72 | 2877.17 | 04-SEP-15:32 | 22.20 |
October | 0.466298E+09 | 4010.89 | 16-OCT-07:04 | 0.92 |
November | 0.162617E+10 | 7001.23 | 27-NOV-07:01 | -9.4 |
December | 0.283216E+10 | 7289.83 | 11-DEC-07:01 | -21.7 |
Annual Sum or Average | 0.133428E+11 | |||
Minimum of Months | 18002516.51 | 2071.81 | -21.7 | |
Maximum of Months | 0.370756E+10 | 9359.81 | 32.50 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258460E+10 | 28230.64 | 02-JAN-05:01 | -4.5 |
February | 0.100929E+10 | 27019.84 | 06-FEB-05:01 | -14.5 |
March | 0.256092E+09 | 25526.13 | 06-MAR-06:01 | -14.1 |
April | 54607719.39 | 24603.52 | 03-APR-05:01 | -7.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.600606E+09 | 27053.21 | 27-NOV-05:11 | -9.4 |
December | 0.129681E+10 | 27242.13 | 11-DEC-05:01 | -22.2 |
Annual Sum or Average | 0.580201E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.2 | |
Maximum of Months | 0.258460E+10 | 28230.64 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.768984E+10 | 31657.05 | 30-JAN-05:01 | -27.9 |
February | 0.423266E+10 | 31133.01 | 06-FEB-05:01 | -14.5 |
March | 0.164388E+10 | 31260.68 | 06-MAR-05:11 | -15.2 |
April | 0.370277E+09 | 29991.26 | 03-APR-04:01 | -6.8 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 4377866.53 | 22956.51 | 30-SEP-06:03 | 0.60 |
October | 0.112218E+09 | 26853.79 | 16-OCT-05:01 | 0.48 |
November | 0.259191E+10 | 30985.73 | 27-NOV-05:01 | -9.4 |
December | 0.533737E+10 | 31032.46 | 11-DEC-05:01 | -22.2 |
Annual Sum or Average | 0.219825E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.9 | |
Maximum of Months | 0.768984E+10 | 31657.05 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114370E+11 | 12118.78 | 23-JAN-05:11 | -18.0 |
February | 0.706057E+10 | 12035.16 | 05-FEB-22:02 | -21.6 |
March | 0.338774E+10 | 12166.48 | 06-MAR-05:11 | -15.2 |
April | 0.908456E+09 | 11411.93 | 03-APR-01:53 | -6.1 |
May | 17981473.94 | 9347.44 | 02-MAY-05:12 | 2.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 80237194.69 | 9853.14 | 30-SEP-05:01 | 0.10 |
October | 0.583543E+09 | 10270.36 | 16-OCT-04:22 | 1.35 |
November | 0.434563E+10 | 11992.57 | 26-NOV-00:42 | -24.4 |
December | 0.867045E+10 | 12049.84 | 11-DEC-06:01 | -22.1 |
Annual Sum or Average | 0.364916E+11 | |||
Minimum of Months | 0.00 | 0.00 | -24.4 | |
Maximum of Months | 0.114370E+11 | 12166.48 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.691710E+10 | 12996.18 | 23-JAN-05:11 | -18.0 |
February | 0.399034E+10 | 12787.56 | 05-FEB-22:02 | -21.6 |
March | 0.177707E+10 | 13035.19 | 06-MAR-05:11 | -15.2 |
April | 0.483132E+09 | 12032.03 | 03-APR-01:53 | -6.1 |
May | 3767009.92 | 9272.76 | 02-MAY-05:12 | 2.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 35535914.94 | 10470.76 | 30-SEP-05:01 | 0.10 |
October | 0.278883E+09 | 10736.08 | 24-OCT-05:11 | 2.07 |
November | 0.262174E+10 | 12762.20 | 27-NOV-02:62 | -11.0 |
December | 0.530750E+10 | 12766.32 | 09-DEC-02:11 | -22.6 |
Annual Sum or Average | 0.214151E+11 | |||
Minimum of Months | 0.00 | 0.00 | -22.6 | |
Maximum of Months | 0.691710E+10 | 13035.19 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.812272E+10 | 15866.84 | 23-JAN-05:11 | -18.0 |
February | 0.459272E+10 | 15638.52 | 03-FEB-04:42 | -33.9 |
March | 0.244417E+10 | 15922.58 | 06-MAR-05:11 | -15.2 |
April | 0.742062E+09 | 14885.58 | 03-APR-01:53 | -6.1 |
May | 17519308.85 | 12128.20 | 02-MAY-05:12 | 2.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 55888042.48 | 12841.09 | 30-SEP-05:01 | 0.10 |
October | 0.361475E+09 | 13148.27 | 16-OCT-05:01 | 0.48 |
November | 0.313315E+10 | 15716.82 | 27-NOV-02:62 | -11.0 |
December | 0.658212E+10 | 15659.91 | 09-DEC-02:11 | -22.6 |
Annual Sum or Average | 0.260518E+11 | |||
Minimum of Months | 0.00 | 0.00 | -33.9 | |
Maximum of Months | 0.812272E+10 | 15922.58 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.709311E+10 | 14228.78 | 23-JAN-05:11 | -18.0 |
February | 0.416607E+10 | 13991.88 | 03-FEB-04:42 | -33.9 |
March | 0.197983E+10 | 14265.72 | 06-MAR-05:11 | -15.2 |
April | 0.515872E+09 | 12681.06 | 03-APR-04:01 | -6.8 |
May | 12854812.02 | 9751.86 | 02-MAY-05:12 | 2.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 52526010.51 | 11578.18 | 30-SEP-05:01 | 0.10 |
October | 0.334982E+09 | 11742.46 | 16-OCT-05:01 | 0.48 |
November | 0.268432E+10 | 13957.56 | 26-NOV-22:02 | -13.3 |
December | 0.542470E+10 | 14016.27 | 09-DEC-02:11 | -22.6 |
Annual Sum or Average | 0.222643E+11 | |||
Minimum of Months | 0.00 | 0.00 | -33.9 | |
Maximum of Months | 0.709311E+10 | 14265.72 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.769765E+10 | 8533.76 | 30-JAN-05:01 | -27.9 |
February | 0.488998E+10 | 8435.70 | 01-FEB-04:52 | -30.0 |
March | 0.238439E+10 | 8085.00 | 13-MAR-04:01 | -9.4 |
April | 0.652258E+09 | 8074.46 | 03-APR-04:01 | -6.8 |
May | 9158428.38 | 6463.14 | 01-MAY-06:03 | 6.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 2136314.71 | 5672.44 | 30-SEP-06:03 | 0.60 |
October | 31785868.97 | 6515.01 | 16-OCT-06:02 | -0.4 |
November | 0.187042E+10 | 8367.56 | 27-NOV-02:62 | -11.0 |
December | 0.485277E+10 | 8387.94 | 11-DEC-05:11 | -22.2 |
Annual Sum or Average | 0.223906E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.0 | |
Maximum of Months | 0.769765E+10 | 8533.76 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.454448E+10 | 10059.30 | 30-JAN-05:01 | -27.9 |
February | 0.257606E+10 | 9856.86 | 02-FEB-04:11 | -35.4 |
March | 0.108962E+10 | 9512.15 | 13-MAR-04:01 | -9.4 |
April | 0.273578E+09 | 9517.49 | 03-APR-04:01 | -6.8 |
May | 303512.37 | 2023.42 | 02-MAY-06:03 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 124292.07 | 828.61 | 30-SEP-06:03 | 0.60 |
October | 8102287.88 | 6475.31 | 27-OCT-06:02 | 0.25 |
November | 0.104912E+10 | 9799.94 | 27-NOV-02:62 | -11.0 |
December | 0.286248E+10 | 9889.91 | 11-DEC-05:11 | -22.2 |
Annual Sum or Average | 0.124039E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.4 | |
Maximum of Months | 0.454448E+10 | 10059.30 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100136E+11 | 16260.58 | 31-JAN-07:10 | -30.5 |
February | 0.644199E+10 | 17700.40 | 02-FEB-07:10 | -36.7 |
March | 0.475942E+10 | 13396.11 | 06-MAR-08:00 | -12.2 |
April | 0.224965E+10 | 12564.30 | 03-APR-07:00 | -6.7 |
May | 0.545735E+09 | 10268.63 | 02-MAY-06:10 | 2.30 |
June | 0.171109E+09 | 8802.82 | 02-JUN-06:10 | 7.30 |
July | 1518352.30 | 3071.24 | 24-JUL-06:07 | 12.35 |
August | 20284249.83 | 7771.78 | 16-AUG-06:06 | 9.97 |
September | 0.377111E+09 | 10331.89 | 29-SEP-06:10 | 0.10 |
October | 0.104906E+10 | 10768.53 | 23-OCT-06:10 | -3.0 |
November | 0.377108E+10 | 14025.49 | 28-NOV-08:00 | -16.7 |
December | 0.742742E+10 | 15008.83 | 11-DEC-08:00 | -21.7 |
Annual Sum or Average | 0.368280E+11 | |||
Minimum of Months | 1518352.30 | 3071.24 | -36.7 | |
Maximum of Months | 0.100136E+11 | 17700.40 | 12.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.467853E+10 | 10691.80 | 30-JAN-05:01 | -27.9 |
February | 0.263767E+10 | 10486.19 | 02-FEB-04:11 | -35.4 |
March | 0.122180E+10 | 10104.86 | 06-MAR-05:01 | -15.4 |
April | 0.244101E+09 | 10175.84 | 03-APR-04:01 | -6.8 |
May | 3127289.54 | 5395.17 | 02-MAY-06:03 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 1494289.90 | 3828.65 | 30-SEP-06:03 | 0.60 |
October | 9185170.13 | 6723.66 | 16-OCT-06:02 | -0.4 |
November | 0.108946E+10 | 10418.52 | 27-NOV-04:02 | -10.4 |
December | 0.293193E+10 | 10536.66 | 11-DEC-05:11 | -22.2 |
Annual Sum or Average | 0.128173E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.4 | |
Maximum of Months | 0.467853E+10 | 10691.80 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.774272E+10 | 9484.40 | 19-JAN-04:42 | -27.0 |
February | 0.433338E+10 | 9099.31 | 03-FEB-04:42 | -33.9 |
March | 0.170397E+10 | 8937.85 | 06-MAR-05:01 | -15.4 |
April | 0.326781E+09 | 8536.86 | 03-APR-04:01 | -6.8 |
May | 1413229.85 | 6355.30 | 02-MAY-06:03 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 7537942.20 | 6867.22 | 30-SEP-06:03 | 0.60 |
October | 87290426.68 | 7450.33 | 16-OCT-05:01 | 0.48 |
November | 0.237961E+10 | 8930.27 | 27-NOV-05:11 | -9.4 |
December | 0.534301E+10 | 9126.41 | 10-DEC-10:42 | -16.4 |
Annual Sum or Average | 0.219257E+11 | |||
Minimum of Months | 0.00 | 0.00 | -33.9 | |
Maximum of Months | 0.774272E+10 | 9484.40 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.456460E+10 | 12564.86 | 19-JAN-04:42 | -27.0 |
February | 0.234761E+10 | 12068.81 | 02-FEB-04:11 | -35.4 |
March | 0.869929E+09 | 11928.31 | 06-MAR-05:01 | -15.4 |
April | 0.171919E+09 | 11336.16 | 03-APR-04:01 | -6.8 |
May | 216426.26 | 1442.84 | 02-MAY-06:03 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 3497882.88 | 5562.82 | 30-SEP-06:03 | 0.60 |
October | 47696124.53 | 9841.47 | 16-OCT-05:01 | 0.48 |
November | 0.141178E+10 | 11938.95 | 27-NOV-05:11 | -9.4 |
December | 0.322336E+10 | 12062.05 | 09-DEC-02:11 | -22.6 |
Annual Sum or Average | 0.126406E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.4 | |
Maximum of Months | 0.456460E+10 | 12564.86 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.498238E+10 | 14302.15 | 19-JAN-04:42 | -27.0 |
February | 0.245362E+10 | 13649.34 | 02-FEB-04:11 | -35.4 |
March | 0.111927E+10 | 13535.28 | 06-MAR-05:01 | -15.4 |
April | 0.245006E+09 | 12975.52 | 03-APR-04:01 | -6.8 |
May | 1283584.98 | 5864.84 | 02-MAY-06:03 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 5293090.24 | 8647.36 | 30-SEP-06:03 | 0.60 |
October | 53053885.67 | 11168.31 | 16-OCT-05:01 | 0.48 |
November | 0.156540E+10 | 13599.55 | 27-NOV-05:11 | -9.4 |
December | 0.385173E+10 | 13709.37 | 09-DEC-02:11 | -22.6 |
Annual Sum or Average | 0.142770E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.4 | |
Maximum of Months | 0.498238E+10 | 14302.15 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.472690E+10 | 13022.81 | 19-JAN-04:42 | -27.0 |
February | 0.248184E+10 | 12500.98 | 02-FEB-04:11 | -35.4 |
March | 0.966621E+09 | 12321.40 | 06-MAR-05:01 | -15.4 |
April | 0.170328E+09 | 11732.39 | 03-APR-04:01 | -6.8 |
May | 1195021.83 | 4530.30 | 02-MAY-06:03 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 6160023.10 | 5652.79 | 30-SEP-06:03 | 0.60 |
October | 54524070.64 | 10271.78 | 16-OCT-05:01 | 0.48 |
November | 0.145993E+10 | 12350.69 | 27-NOV-05:11 | -9.4 |
December | 0.332769E+10 | 12502.63 | 09-DEC-02:11 | -22.6 |
Annual Sum or Average | 0.131952E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.4 | |
Maximum of Months | 0.472690E+10 | 13022.81 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.642017E+09 | 1040.56 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.539419E+09 | 861.30 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.592169E+09 | 713.39 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.512743E+09 | 582.71 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.533475E+09 | 496.34 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.527908E+09 | 558.23 | 13-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.496726E+09 | 558.93 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.557382E+09 | 534.75 | 31-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.521304E+09 | 582.95 | 21-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.570537E+09 | 999.89 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.623687E+09 | 1040.56 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.656333E+09 | 1040.56 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.677370E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.496726E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.656333E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.398674E+09 | 658.76 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.337524E+09 | 553.80 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.373966E+09 | 466.11 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324567E+09 | 359.10 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.340086E+09 | 341.17 | 24-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.336131E+09 | 342.18 | 13-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.315866E+09 | 342.63 | 31-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.354445E+09 | 314.23 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330215E+09 | 359.51 | 29-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.356917E+09 | 579.16 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.389859E+09 | 658.76 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.404503E+09 | 658.76 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.426275E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.315866E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.404503E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.616006E+09 | 1040.56 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.523399E+09 | 831.79 | 14-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.588084E+09 | 584.36 | 01-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.512537E+09 | 581.52 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.536636E+09 | 496.34 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.530959E+09 | 561.32 | 13-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.498829E+09 | 562.21 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.559943E+09 | 525.40 | 31-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.519788E+09 | 579.33 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.558641E+09 | 938.40 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.605018E+09 | 1040.56 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.621366E+09 | 1040.56 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.667121E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.498829E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.621366E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.396450E+09 | 658.71 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335403E+09 | 512.03 | 14-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.373339E+09 | 446.22 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324148E+09 | 433.72 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.337859E+09 | 333.72 | 25-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.334102E+09 | 359.34 | 13-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314619E+09 | 360.66 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.353064E+09 | 350.85 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.328486E+09 | 441.39 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.358849E+09 | 634.82 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.387129E+09 | 658.71 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.402382E+09 | 658.71 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.424583E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.314619E+09 | 333.72 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.402382E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.639234E+09 | 1040.56 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.537659E+09 | 852.01 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.590993E+09 | 700.68 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.511725E+09 | 579.93 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.533017E+09 | 496.34 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.527600E+09 | 554.27 | 13-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.496470E+09 | 555.00 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.557037E+09 | 529.71 | 31-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.520565E+09 | 580.19 | 21-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.569030E+09 | 998.04 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.621405E+09 | 1040.56 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.652612E+09 | 1040.56 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.675735E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.496470E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.652612E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.397625E+09 | 658.76 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.336523E+09 | 549.03 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.373400E+09 | 460.16 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324219E+09 | 356.93 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.339828E+09 | 338.98 | 24-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.335934E+09 | 339.30 | 13-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.315643E+09 | 339.93 | 31-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.354181E+09 | 314.23 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.329875E+09 | 357.52 | 29-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.356370E+09 | 575.10 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.389128E+09 | 658.76 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.402963E+09 | 658.76 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.425569E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.315643E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.402963E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.614957E+09 | 1040.56 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.522849E+09 | 823.41 | 14-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.587526E+09 | 581.59 | 01-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.511867E+09 | 578.67 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.536077E+09 | 496.34 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.530488E+09 | 557.54 | 13-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.498444E+09 | 558.48 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.559349E+09 | 496.34 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.519211E+09 | 576.36 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.558152E+09 | 933.42 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.604107E+09 | 1040.56 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.619735E+09 | 1040.56 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.666276E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.498444E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.619735E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.395478E+09 | 658.71 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.334708E+09 | 506.99 | 14-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.372963E+09 | 437.07 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.323606E+09 | 426.88 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.337598E+09 | 314.21 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.333782E+09 | 357.34 | 13-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314450E+09 | 358.72 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.352792E+09 | 348.56 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.328042E+09 | 434.76 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.358085E+09 | 633.91 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.386254E+09 | 658.71 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.400977E+09 | 658.71 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.423874E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.314450E+09 | 314.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.400977E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.642015E+09 | 1040.56 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.539417E+09 | 861.30 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.592168E+09 | 713.37 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.512742E+09 | 582.70 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.533474E+09 | 496.34 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.527908E+09 | 558.22 | 13-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.496726E+09 | 558.92 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.557381E+09 | 534.74 | 31-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.521303E+09 | 582.95 | 21-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.570535E+09 | 999.89 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.623685E+09 | 1040.56 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.656328E+09 | 1040.56 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.677368E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.496726E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.656328E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.398673E+09 | 658.76 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.337523E+09 | 553.80 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.373966E+09 | 466.10 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324567E+09 | 359.09 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.340085E+09 | 341.17 | 24-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.336131E+09 | 342.18 | 13-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.315866E+09 | 342.63 | 31-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.354445E+09 | 314.23 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330214E+09 | 359.51 | 29-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.356916E+09 | 579.16 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.389858E+09 | 658.76 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.404490E+09 | 658.76 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.426273E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.315866E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.404490E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.616005E+09 | 1040.56 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.523399E+09 | 831.77 | 14-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.588084E+09 | 584.35 | 01-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.512536E+09 | 581.52 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.536635E+09 | 496.34 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.530958E+09 | 561.31 | 13-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.498826E+09 | 562.20 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.559943E+09 | 525.39 | 31-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.519788E+09 | 579.33 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.558640E+09 | 938.40 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.605017E+09 | 1040.56 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.621412E+09 | 1040.56 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.667124E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.498826E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.621412E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.396449E+09 | 658.71 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335402E+09 | 512.02 | 14-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.373338E+09 | 446.23 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324147E+09 | 433.70 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.337859E+09 | 333.71 | 25-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.334102E+09 | 359.34 | 13-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314619E+09 | 360.65 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.353064E+09 | 350.85 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.328486E+09 | 441.37 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.358848E+09 | 634.82 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.387128E+09 | 658.71 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.402380E+09 | 658.71 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.424582E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.314619E+09 | 333.71 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.402380E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.642017E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285382E+10 |
February | 0.901968E+09 | 0.539419E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208097E+10 |
March | 0.107774E+10 | 0.592169E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177085E+10 |
April | 0.956342E+09 | 0.512743E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9675371.84 | 0.110614E+10 |
May | 0.103597E+10 | 0.533475E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3524664.82 | 0.637941E+09 |
June | 0.103308E+10 | 0.527908E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45137300.62 | 0.373876E+09 |
July | 0.959235E+09 | 0.496726E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15487857.65 | 0.274861E+09 |
August | 0.107774E+10 | 0.557382E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17477131.89 | 0.368330E+09 |
September | 0.956342E+09 | 0.521304E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13544706.71 | 0.566950E+09 |
October | 0.994195E+09 | 0.570537E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104064E+10 |
November | 0.984487E+09 | 0.623687E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176141E+10 |
December | 0.959235E+09 | 0.656333E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238085E+10 |
Annual Sum or Average | 0.119305E+11 | 0.677370E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104847E+09 | 0.152166E+11 |
Minimum of Months | 0.901968E+09 | 0.496726E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274861E+09 |
Maximum of Months | 0.107774E+10 | 0.656333E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45137300.62 | 0.285382E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.398674E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190777E+10 |
February | 0.571020E+09 | 0.337524E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139246E+10 |
March | 0.682301E+09 | 0.373966E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119663E+10 |
April | 0.605444E+09 | 0.324567E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5798340.69 | 0.764728E+09 |
May | 0.655854E+09 | 0.340086E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2349493.54 | 0.442468E+09 |
June | 0.654023E+09 | 0.336131E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28526762.92 | 0.255626E+09 |
July | 0.607275E+09 | 0.315866E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9658727.23 | 0.190169E+09 |
August | 0.682301E+09 | 0.354445E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11342473.78 | 0.252680E+09 |
September | 0.605444E+09 | 0.330215E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7612889.85 | 0.396775E+09 |
October | 0.629407E+09 | 0.356917E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722287E+09 |
November | 0.623262E+09 | 0.389859E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118175E+10 |
December | 0.607275E+09 | 0.404503E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159252E+10 |
Annual Sum or Average | 0.755301E+10 | 0.426275E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65288688.02 | 0.102959E+11 |
Minimum of Months | 0.571020E+09 | 0.315866E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190169E+09 |
Maximum of Months | 0.682301E+09 | 0.404503E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28526762.92 | 0.190777E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.616006E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288431E+10 |
February | 0.901968E+09 | 0.523399E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212999E+10 |
March | 0.107774E+10 | 0.588084E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183879E+10 |
April | 0.956342E+09 | 0.512537E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7954618.97 | 0.116330E+10 |
May | 0.103597E+10 | 0.536636E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3524564.69 | 0.658220E+09 |
June | 0.103308E+10 | 0.530959E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43217937.19 | 0.376623E+09 |
July | 0.959235E+09 | 0.498829E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14441706.43 | 0.280429E+09 |
August | 0.107774E+10 | 0.559943E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16955531.15 | 0.384816E+09 |
September | 0.956342E+09 | 0.519788E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10923706.36 | 0.611283E+09 |
October | 0.994195E+09 | 0.558641E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114258E+10 |
November | 0.984487E+09 | 0.605018E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181521E+10 |
December | 0.959235E+09 | 0.621366E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243267E+10 |
Annual Sum or Average | 0.119305E+11 | 0.667121E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97018064.79 | 0.157182E+11 |
Minimum of Months | 0.901968E+09 | 0.498829E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280429E+09 |
Maximum of Months | 0.107774E+10 | 0.621366E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43217937.19 | 0.288431E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.396450E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190892E+10 |
February | 0.570983E+09 | 0.335403E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139946E+10 |
March | 0.682256E+09 | 0.373339E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119941E+10 |
April | 0.605404E+09 | 0.324148E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4951521.21 | 0.774422E+09 |
May | 0.655811E+09 | 0.337859E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2349892.10 | 0.444427E+09 |
June | 0.653980E+09 | 0.334102E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27940466.70 | 0.257343E+09 |
July | 0.607235E+09 | 0.314619E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9558967.01 | 0.196221E+09 |
August | 0.682256E+09 | 0.353064E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11392872.35 | 0.260831E+09 |
September | 0.605404E+09 | 0.328486E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7379542.95 | 0.400098E+09 |
October | 0.629366E+09 | 0.358849E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718525E+09 |
November | 0.623221E+09 | 0.387129E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118343E+10 |
December | 0.607235E+09 | 0.402382E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159353E+10 |
Annual Sum or Average | 0.755252E+10 | 0.424583E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63573262.32 | 0.103366E+11 |
Minimum of Months | 0.570983E+09 | 0.314619E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196221E+09 |
Maximum of Months | 0.682256E+09 | 0.402382E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27940466.70 | 0.190892E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.639234E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153586E+10 |
February | 0.901968E+09 | 0.537659E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113516E+10 |
March | 0.107774E+10 | 0.590993E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.964132E+09 |
April | 0.956342E+09 | 0.511725E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9606994.01 | 0.589367E+09 |
May | 0.103597E+10 | 0.533017E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1987852.56 | 0.327028E+09 |
June | 0.103308E+10 | 0.527600E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29642741.72 | 0.196619E+09 |
July | 0.959235E+09 | 0.496470E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10325560.72 | 0.143518E+09 |
August | 0.107774E+10 | 0.557037E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9910081.57 | 0.201980E+09 |
September | 0.956342E+09 | 0.520565E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8563088.13 | 0.325681E+09 |
October | 0.994195E+09 | 0.569030E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626149E+09 |
November | 0.984487E+09 | 0.621405E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100575E+10 |
December | 0.959235E+09 | 0.652612E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131053E+10 |
Annual Sum or Average | 0.119305E+11 | 0.675735E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70036318.70 | 0.836177E+10 |
Minimum of Months | 0.901968E+09 | 0.496470E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143518E+09 |
Maximum of Months | 0.107774E+10 | 0.652612E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29642741.72 | 0.153586E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.397625E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102706E+10 |
February | 0.571020E+09 | 0.336523E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762414E+09 |
March | 0.682301E+09 | 0.373400E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.656154E+09 |
April | 0.605444E+09 | 0.324219E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4702422.68 | 0.414002E+09 |
May | 0.655854E+09 | 0.339828E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1275547.35 | 0.237778E+09 |
June | 0.654023E+09 | 0.335934E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16439884.21 | 0.139247E+09 |
July | 0.607275E+09 | 0.315643E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5463296.90 | 0.103713E+09 |
August | 0.682301E+09 | 0.354181E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6198529.56 | 0.142356E+09 |
September | 0.605444E+09 | 0.329875E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4271076.91 | 0.232496E+09 |
October | 0.629407E+09 | 0.356370E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441270E+09 |
November | 0.623262E+09 | 0.389128E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676594E+09 |
December | 0.607275E+09 | 0.402963E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876809E+09 |
Annual Sum or Average | 0.755301E+10 | 0.425569E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38350757.60 | 0.570989E+10 |
Minimum of Months | 0.571020E+09 | 0.315643E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103713E+09 |
Maximum of Months | 0.682301E+09 | 0.402963E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16439884.21 | 0.102706E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.614957E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100394E+11 |
February | 0.901968E+09 | 0.522849E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762008E+10 |
March | 0.107774E+10 | 0.587526E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659508E+10 |
April | 0.956342E+09 | 0.511867E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24217146.61 | 0.410787E+10 |
May | 0.103597E+10 | 0.536077E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68344542.84 | 0.227284E+10 |
June | 0.103308E+10 | 0.530488E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274650E+09 | 0.125048E+10 |
July | 0.959235E+09 | 0.498444E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233545E+09 | 0.634031E+09 |
August | 0.107774E+10 | 0.559349E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329301E+09 | 0.942762E+09 |
September | 0.956342E+09 | 0.519211E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173839E+09 | 0.209442E+10 |
October | 0.994195E+09 | 0.558152E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412462E+10 |
November | 0.984487E+09 | 0.604107E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582154E+10 |
December | 0.959235E+09 | 0.619735E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.804382E+10 |
Annual Sum or Average | 0.119305E+11 | 0.666276E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110390E+10 | 0.535470E+11 |
Minimum of Months | 0.901968E+09 | 0.498444E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634031E+09 |
Maximum of Months | 0.107774E+10 | 0.619735E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329301E+09 | 0.100394E+11 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.395478E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102750E+10 |
February | 0.570983E+09 | 0.334708E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765705E+09 |
March | 0.682256E+09 | 0.372963E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657206E+09 |
April | 0.605404E+09 | 0.323606E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3097704.88 | 0.423131E+09 |
May | 0.655811E+09 | 0.337598E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1280879.17 | 0.237881E+09 |
June | 0.653980E+09 | 0.333782E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16223672.98 | 0.140275E+09 |
July | 0.607235E+09 | 0.314450E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5422553.14 | 0.109417E+09 |
August | 0.682256E+09 | 0.352792E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6215192.17 | 0.148687E+09 |
September | 0.605404E+09 | 0.328042E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3996444.84 | 0.235035E+09 |
October | 0.629366E+09 | 0.358085E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438309E+09 |
November | 0.623221E+09 | 0.386254E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678176E+09 |
December | 0.607235E+09 | 0.400977E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877525E+09 |
Annual Sum or Average | 0.755252E+10 | 0.423874E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36236447.17 | 0.573885E+10 |
Minimum of Months | 0.570983E+09 | 0.314450E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109417E+09 |
Maximum of Months | 0.682256E+09 | 0.400977E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16223672.98 | 0.102750E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.642015E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239718E+10 |
February | 0.901968E+09 | 0.539417E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177236E+10 |
March | 0.107774E+10 | 0.592168E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153514E+10 |
April | 0.956342E+09 | 0.512742E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9141585.81 | 0.974318E+09 |
May | 0.103597E+10 | 0.533474E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2964532.71 | 0.555600E+09 |
June | 0.103308E+10 | 0.527908E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38400066.38 | 0.325766E+09 |
July | 0.959235E+09 | 0.496726E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13379495.47 | 0.237684E+09 |
August | 0.107774E+10 | 0.557381E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14803858.46 | 0.321061E+09 |
September | 0.956342E+09 | 0.521303E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11575565.09 | 0.505784E+09 |
October | 0.994195E+09 | 0.570535E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951277E+09 |
November | 0.984487E+09 | 0.623685E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153184E+10 |
December | 0.959235E+09 | 0.656328E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202534E+10 |
Annual Sum or Average | 0.119305E+11 | 0.677368E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90265103.92 | 0.131334E+11 |
Minimum of Months | 0.901968E+09 | 0.496726E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237684E+09 |
Maximum of Months | 0.107774E+10 | 0.656328E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38400066.38 | 0.239718E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.398673E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159953E+10 |
February | 0.421807E+09 | 0.337523E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118661E+10 |
March | 0.502994E+09 | 0.373966E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104009E+10 |
April | 0.447140E+09 | 0.324567E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5110716.96 | 0.672058E+09 |
May | 0.484071E+09 | 0.340085E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1896095.09 | 0.383434E+09 |
June | 0.482240E+09 | 0.336131E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24170599.03 | 0.222590E+09 |
July | 0.448971E+09 | 0.315866E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7918973.26 | 0.163953E+09 |
August | 0.502994E+09 | 0.354445E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9096359.40 | 0.219568E+09 |
September | 0.447140E+09 | 0.330214E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6297792.26 | 0.350894E+09 |
October | 0.465148E+09 | 0.356916E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658994E+09 |
November | 0.460569E+09 | 0.389858E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102684E+10 |
December | 0.448971E+09 | 0.404490E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135248E+10 |
Annual Sum or Average | 0.557719E+10 | 0.426273E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54490535.99 | 0.887704E+10 |
Minimum of Months | 0.421807E+09 | 0.315866E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163953E+09 |
Maximum of Months | 0.502994E+09 | 0.404490E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24170599.03 | 0.159953E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.616005E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243515E+10 |
February | 0.901968E+09 | 0.523399E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182637E+10 |
March | 0.107774E+10 | 0.588084E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159837E+10 |
April | 0.956342E+09 | 0.512536E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6990838.77 | 0.102085E+10 |
May | 0.103597E+10 | 0.536635E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2964188.43 | 0.570337E+09 |
June | 0.103308E+10 | 0.530958E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37024731.99 | 0.327366E+09 |
July | 0.959235E+09 | 0.498826E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12344830.06 | 0.241761E+09 |
August | 0.107774E+10 | 0.559943E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14263460.23 | 0.333634E+09 |
September | 0.956342E+09 | 0.519788E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9188781.57 | 0.538911E+09 |
October | 0.994195E+09 | 0.558640E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103151E+10 |
November | 0.984487E+09 | 0.605017E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158474E+10 |
December | 0.959235E+09 | 0.621412E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208142E+10 |
Annual Sum or Average | 0.119305E+11 | 0.667124E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82776831.04 | 0.135904E+11 |
Minimum of Months | 0.901968E+09 | 0.498826E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241761E+09 |
Maximum of Months | 0.107774E+10 | 0.621412E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37024731.99 | 0.243515E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.396449E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160222E+10 |
February | 0.570983E+09 | 0.335402E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119284E+10 |
March | 0.682256E+09 | 0.373338E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103980E+10 |
April | 0.605404E+09 | 0.324147E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4234138.57 | 0.678956E+09 |
May | 0.655811E+09 | 0.337859E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1976433.68 | 0.385352E+09 |
June | 0.653980E+09 | 0.334102E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23747098.21 | 0.223528E+09 |
July | 0.607235E+09 | 0.314619E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8167654.82 | 0.169174E+09 |
August | 0.682256E+09 | 0.353064E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9590566.11 | 0.226183E+09 |
September | 0.605404E+09 | 0.328486E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6191338.37 | 0.353986E+09 |
October | 0.629366E+09 | 0.358848E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653208E+09 |
November | 0.623221E+09 | 0.387128E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102874E+10 |
December | 0.607235E+09 | 0.402380E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135516E+10 |
Annual Sum or Average | 0.755252E+10 | 0.424582E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53907229.75 | 0.890915E+10 |
Minimum of Months | 0.570983E+09 | 0.314619E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169174E+09 |
Maximum of Months | 0.682256E+09 | 0.402380E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23747098.21 | 0.160222E+10 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319109E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241322E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212627E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11950100.74 | 0.136566E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2795578.56 | 0.758566E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49651336.77 | 0.438610E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13937807.35 | 0.320508E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14039825.13 | 0.442845E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11031077.96 | 0.715070E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137983E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214353E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275672E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103406E+09 | 0.180519E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320508E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49651336.77 | 0.319109E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398882E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299638E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262901E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14352639.42 | 0.169455E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3566517.77 | 0.967249E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61998895.66 | 0.558993E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17281529.88 | 0.409537E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18264868.86 | 0.559892E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15329964.20 | 0.885993E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165521E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260706E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340714E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130794E+09 | 0.223598E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409537E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61998895.66 | 0.398882E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415441E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308719E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269086E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6179189.65 | 0.172839E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2621323.15 | 0.101233E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40714718.57 | 0.573565E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8388950.75 | 0.430012E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14267849.31 | 0.578935E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9893623.66 | 0.891340E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162684E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262633E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349342E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82065655.09 | 0.228936E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430012E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40714718.57 | 0.415441E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5546.04 | 29-JAN-10:51 |
February | 1306.65 | 01-FEB-10:09 | 861.30 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3922.91 | 10-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 713.39 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2974.39 | 20-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 582.71 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 487.63 | 15-APR-17:01 | 2238.37 | 02-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.65 | 31-MAY-13:00 | 1466.93 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 558.23 | 13-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 571.39 | 11-JUN-15:25 | 1222.62 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 558.93 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.11 | 02-JUL-15:35 | 567.86 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 534.75 | 31-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.60 | 04-AUG-16:40 | 742.72 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 582.95 | 21-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.97 | 17-SEP-14:42 | 1115.46 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 999.89 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1494.54 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4295.44 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6589.85 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567.86 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 571.39 | 6589.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3713.60 | 29-JAN-10:51 |
February | 827.22 | 01-FEB-10:09 | 553.80 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2613.58 | 10-FEB-22:01 |
March | 827.22 | 01-MAR-10:09 | 466.11 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2007.63 | 06-MAR-06:00 |
April | 827.22 | 03-APR-09:09 | 359.10 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 294.76 | 15-APR-17:01 | 1524.29 | 02-APR-23:55 |
May | 827.22 | 01-MAY-09:09 | 341.17 | 24-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.43 | 31-MAY-13:00 | 988.98 | 01-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 342.18 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 387.99 | 11-JUN-15:23 | 817.10 | 02-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 342.63 | 31-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.81 | 02-JUL-15:35 | 387.98 | 09-JUL-10:00 |
August | 827.22 | 01-AUG-09:09 | 314.23 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.07 | 04-AUG-16:40 | 507.18 | 06-AUG-09:00 |
September | 827.22 | 01-SEP-09:09 | 359.51 | 29-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.41 | 06-SEP-16:00 | 744.51 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 579.16 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 999.80 | 24-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2861.88 | 20-NOV-22:01 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4393.22 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.98 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 387.99 | 4393.22 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5601.68 | 29-JAN-10:51 |
February | 1306.65 | 01-FEB-10:09 | 831.79 | 14-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3924.88 | 10-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 584.36 | 01-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3168.57 | 05-MAR-13:53 |
April | 1306.65 | 03-APR-09:09 | 581.52 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.83 | 15-APR-17:01 | 2244.23 | 02-APR-23:55 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.65 | 31-MAY-13:00 | 1493.49 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 561.32 | 13-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 569.92 | 11-JUN-15:23 | 1228.81 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 562.21 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.74 | 02-JUL-15:35 | 574.35 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 525.40 | 31-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.60 | 04-AUG-16:40 | 807.17 | 06-AUG-14:00 |
September | 1306.65 | 01-SEP-09:09 | 579.33 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.54 | 06-SEP-16:00 | 1126.71 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 938.40 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1548.88 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4298.34 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6589.87 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.35 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 569.92 | 6589.87 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3697.50 | 29-JAN-10:51 |
February | 827.17 | 01-FEB-10:09 | 512.03 | 14-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2613.01 | 10-FEB-22:01 |
March | 827.17 | 01-MAR-10:09 | 446.22 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2007.63 | 06-MAR-06:00 |
April | 827.17 | 03-APR-09:09 | 433.72 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.12 | 15-APR-17:10 | 1524.94 | 02-APR-23:55 |
May | 827.17 | 01-MAY-09:09 | 333.72 | 25-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.43 | 31-MAY-13:00 | 985.99 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 359.34 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.41 | 11-JUN-15:00 | 809.68 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 360.66 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.56 | 02-JUL-14:54 | 396.92 | 09-JUL-21:00 |
August | 827.17 | 01-AUG-09:09 | 350.85 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.07 | 04-AUG-16:40 | 508.81 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 441.39 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.41 | 06-SEP-16:00 | 790.77 | 24-SEP-16:20 |
October | 827.17 | 02-OCT-09:09 | 634.82 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1004.57 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2861.63 | 20-NOV-22:01 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4393.22 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 333.72 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.92 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 378.41 | 4393.22 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2967.45 | 29-JAN-10:51 |
February | 1306.65 | 01-FEB-10:09 | 852.01 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2095.47 | 10-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 700.68 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1585.56 | 20-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 579.93 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.72 | 15-APR-17:01 | 1194.23 | 02-APR-23:53 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.18 | 31-MAY-13:00 | 799.26 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 554.27 | 13-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.13 | 18-JUN-16:00 | 710.99 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 555.00 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.42 | 02-JUL-15:30 | 296.98 | 09-JUL-10:00 |
August | 1306.65 | 01-AUG-09:09 | 529.71 | 31-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.15 | 04-AUG-16:40 | 417.62 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 580.19 | 21-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.11 | 17-SEP-15:00 | 653.51 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 998.04 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 955.79 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2296.66 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3499.04 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.98 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 367.72 | 3499.04 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1985.45 | 29-JAN-10:51 |
February | 827.22 | 01-FEB-10:09 | 549.03 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1396.92 | 10-FEB-22:01 |
March | 827.22 | 01-MAR-10:09 | 460.16 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1077.62 | 05-MAR-09:53 |
April | 827.22 | 03-APR-09:09 | 356.93 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.18 | 15-APR-17:01 | 794.52 | 02-APR-23:53 |
May | 827.22 | 01-MAY-09:09 | 338.98 | 24-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.12 | 31-MAY-13:00 | 562.30 | 01-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 339.30 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.55 | 11-JUN-15:04 | 490.24 | 02-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 339.93 | 31-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.66 | 02-JUL-15:23 | 207.57 | 09-JUL-10:00 |
August | 827.22 | 01-AUG-09:09 | 314.23 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.43 | 04-AUG-16:40 | 288.20 | 06-AUG-09:00 |
September | 827.22 | 01-SEP-09:09 | 357.52 | 29-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.32 | 10-SEP-15:00 | 447.11 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 575.10 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 655.59 | 24-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1530.64 | 20-NOV-22:01 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2332.68 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.57 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 212.55 | 2332.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 44677.57 | 31-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 823.41 | 14-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 51524.14 | 02-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 581.59 | 01-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 28141.36 | 06-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 578.67 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2940.99 | 18-APR-12:00 | 23243.47 | 03-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4129.67 | 31-MAY-12:00 | 14781.40 | 02-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 557.54 | 13-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5849.03 | 26-JUN-16:10 | 11239.22 | 02-JUN-06:05 |
July | 1306.65 | 03-JUL-09:09 | 558.48 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4480.29 | 26-JUL-16:10 | 8179.60 | 24-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 496.34 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6605.14 | 04-AUG-16:05 | 11142.11 | 07-AUG-06:01 |
September | 1306.65 | 01-SEP-09:09 | 576.36 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5291.58 | 07-SEP-16:05 | 16556.60 | 29-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 933.42 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 19523.96 | 23-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 32439.36 | 28-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 36547.60 | 11-DEC-17:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8179.60 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 6605.14 | 51524.14 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1978.60 | 29-JAN-10:51 |
February | 827.17 | 01-FEB-10:09 | 506.99 | 14-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1396.65 | 10-FEB-22:01 |
March | 827.17 | 01-MAR-10:09 | 437.07 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1062.67 | 12-MAR-16:00 |
April | 827.17 | 03-APR-09:09 | 426.88 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.30 | 15-APR-17:06 | 789.47 | 02-APR-23:53 |
May | 827.17 | 01-MAY-09:09 | 314.21 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.12 | 31-MAY-13:00 | 548.78 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 357.34 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.90 | 11-JUN-15:03 | 477.97 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 358.72 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.05 | 02-JUL-14:43 | 217.97 | 09-JUL-10:00 |
August | 827.17 | 01-AUG-09:09 | 348.56 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.43 | 04-AUG-16:40 | 298.64 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 434.76 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.00 | 10-SEP-14:58 | 446.83 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 633.91 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 655.49 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1530.66 | 20-NOV-22:01 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2332.68 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.97 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 209.90 | 2332.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4634.91 | 29-JAN-10:51 |
February | 1306.65 | 01-FEB-10:09 | 861.30 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3278.65 | 10-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 713.37 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2498.60 | 06-MAR-06:00 |
April | 1306.65 | 03-APR-09:09 | 582.70 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 433.04 | 15-APR-17:01 | 1861.02 | 02-APR-23:53 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.75 | 31-MAY-13:00 | 1306.60 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 558.22 | 13-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 474.37 | 11-JUN-14:52 | 1109.07 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 558.92 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.66 | 02-JUL-15:20 | 484.56 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 534.74 | 31-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.60 | 04-AUG-16:40 | 653.21 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 582.95 | 21-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.71 | 17-SEP-15:00 | 989.63 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 999.89 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1411.80 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3586.86 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5481.83 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.56 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 474.37 | 5481.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 658.76 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3102.63 | 29-JAN-10:51 |
February | 805.43 | 01-FEB-08:09 | 553.80 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2184.52 | 10-FEB-22:01 |
March | 805.43 | 01-MAR-08:09 | 466.10 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1726.20 | 05-MAR-09:53 |
April | 805.43 | 03-APR-07:10 | 359.09 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.82 | 15-APR-17:01 | 1240.67 | 02-APR-23:53 |
May | 805.43 | 01-MAY-07:10 | 341.17 | 24-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.84 | 31-MAY-13:00 | 879.13 | 01-MAY-24:00 |
June | 805.43 | 01-JUN-07:10 | 342.18 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.58 | 11-JUN-15:14 | 740.93 | 02-JUN-05:00 |
July | 805.43 | 03-JUL-07:10 | 342.63 | 31-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.35 | 02-JUL-15:55 | 345.65 | 09-JUL-10:00 |
August | 805.43 | 01-AUG-07:10 | 314.23 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.74 | 04-AUG-16:40 | 445.69 | 06-AUG-09:00 |
September | 805.43 | 01-SEP-07:10 | 359.51 | 29-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.34 | 10-SEP-15:00 | 660.37 | 18-SEP-23:00 |
October | 805.43 | 02-OCT-07:10 | 579.16 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 944.74 | 24-OCT-05:00 |
November | 805.43 | 01-NOV-07:10 | 658.76 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2389.93 | 20-NOV-22:01 |
December | 805.43 | 01-DEC-08:09 | 658.76 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3654.53 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.65 | |||||
Maximum of Months | 805.43 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 329.58 | 3654.53 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4810.20 | 29-JAN-13:00 |
February | 1306.65 | 01-FEB-10:09 | 831.77 | 14-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3280.20 | 10-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 584.35 | 01-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2777.78 | 05-MAR-13:53 |
April | 1306.65 | 03-APR-09:09 | 581.52 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 325.00 | 15-APR-17:01 | 1861.02 | 02-APR-23:53 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.75 | 31-MAY-13:00 | 1326.67 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 561.31 | 13-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 474.36 | 11-JUN-14:52 | 1113.72 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 562.20 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.64 | 02-JUL-15:55 | 496.43 | 09-JUL-10:00 |
August | 1306.65 | 01-AUG-09:09 | 525.39 | 31-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.60 | 04-AUG-16:40 | 664.90 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 579.33 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.18 | 10-SEP-14:58 | 999.73 | 24-SEP-13:40 |
October | 1306.65 | 02-OCT-09:09 | 938.40 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1457.10 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3589.59 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5481.83 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496.43 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 474.36 | 5481.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3089.35 | 29-JAN-10:51 |
February | 827.17 | 01-FEB-10:09 | 512.02 | 14-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2184.19 | 10-FEB-22:01 |
March | 827.17 | 01-MAR-10:09 | 446.23 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1669.85 | 06-MAR-06:00 |
April | 827.17 | 03-APR-09:09 | 433.70 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.43 | 15-APR-17:10 | 1240.67 | 02-APR-23:53 |
May | 827.17 | 01-MAY-09:09 | 333.71 | 25-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.84 | 31-MAY-13:00 | 877.00 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 359.34 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 316.25 | 11-JUN-14:52 | 734.58 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 360.65 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.33 | 02-JUL-15:14 | 337.94 | 09-JUL-21:00 |
August | 827.17 | 01-AUG-09:09 | 350.85 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.74 | 04-AUG-16:40 | 447.03 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 441.37 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.19 | 10-SEP-14:55 | 671.60 | 24-SEP-16:20 |
October | 827.17 | 02-OCT-09:09 | 634.82 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 947.53 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2389.90 | 20-NOV-22:01 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3654.53 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 333.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.94 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 316.25 | 3654.53 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 6119.70 | 29-JAN-10:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4289.41 | 04-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3474.56 | 21-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.51 | 15-APR-17:01 | 2716.59 | 02-APR-23:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.69 | 31-MAY-13:00 | 1844.41 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 648.36 | 11-JUN-14:52 | 1580.24 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.96 | 02-JUL-15:10 | 638.41 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.67 | 04-AUG-16:40 | 874.52 | 06-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.46 | 17-SEP-14:42 | 1389.08 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2121.44 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4550.92 | 20-NOV-22:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7451.48 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 638.41 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 648.36 | 7451.48 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 7595.52 | 29-JAN-10:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5401.41 | 04-FEB-22:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4368.88 | 21-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 688.56 | 15-APR-17:01 | 3258.15 | 02-APR-23:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.50 | 31-MAY-13:00 | 2329.88 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 816.55 | 11-JUN-14:52 | 1982.07 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.81 | 02-JUL-15:00 | 807.93 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.75 | 04-AUG-16:40 | 1103.76 | 06-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.43 | 17-SEP-14:42 | 1755.33 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2547.78 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5636.19 | 20-NOV-22:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9251.27 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 807.93 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 816.55 | 9251.27 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 7912.87 | 29-JAN-10:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5621.90 | 10-FEB-22:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4458.01 | 20-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.34 | 15-APR-17:01 | 3196.77 | 02-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.52 | 31-MAY-13:00 | 2239.77 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 606.08 | 11-JUN-15:00 | 1869.77 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.26 | 25-JUL-16:00 | 867.29 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.70 | 03-AUG-16:00 | 1134.68 | 06-AUG-09:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.80 | 06-SEP-16:00 | 1689.00 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2258.73 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6136.70 | 20-NOV-22:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9349.77 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 867.29 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 606.08 | 9349.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9361.53 | 13-JAN-17:00 | 12070.02 | 9872.03 | 28785.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10193.67 | 24-FEB-17:00 | 6035.01 | 4936.01 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16065.95 | 30-MAR-07:03 | 54315.07 | 44424.13 | 163666.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 37381.55 | 17-APR-06:02 | 6352.64 | 8226.80 | 43983.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41179.37 | 30-MAY-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41306.90 | 19-JUN-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41673.69 | 17-JUL-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 41507.27 | 14-AUG-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41473.26 | 12-SEP-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18087.84 | 04-OCT-08:00 | 6035.01 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17792.46 | 03-NOV-16:00 | 6035.01 | 4936.01 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9960.62 | 07-DEC-16:20 | 12070.02 | 9872.03 | 28785.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 9361.53 | 2541.06 | 2193.73 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41673.69 | 54315.07 | 44424.13 | 163666.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1315.82 |
February | 309.92 | 24-FEB-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.12 |
March | 1863.92 | 24-MAR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556.22 |
April | 8486.12 | 18-APR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.79 | 0.00 |
May | 9511.87 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.66 | 0.00 |
June | 11033.94 | 26-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.34 | 0.00 |
July | 10375.46 | 05-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.55 | 0.00 |
August | 10771.77 | 04-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.75 | 0.00 |
September | 9666.81 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.55 | 0.00 |
October | 3901.03 | 20-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.62 |
November | 1903.58 | 03-NOV-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.53 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1760.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11033.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.75 | 1760.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3283.29 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1778.20 |
February | 2900.06 | 16-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1990.50 |
March | 2217.70 | 11-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.70 |
April | 3617.13 | 17-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4106.72 | 30-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.92 | 0.00 |
June | 5582.99 | 26-JUN-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.85 | 0.00 |
July | 6224.73 | 05-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.75 |
August | 4708.22 | 04-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.32 | 0.00 |
September | 4431.55 | 11-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.01 | 0.00 |
October | 1457.90 | 14-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.38 |
November | 2080.99 | 26-NOV-01:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3356.17 |
December | 2874.73 | 28-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1566.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1457.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6224.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.32 | 3356.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2708.34 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1400.67 |
February | 2820.48 | 04-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1168.33 |
March | 2977.25 | 17-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.84 |
April | 3562.61 | 18-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.78 | 0.00 |
May | 4077.94 | 30-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.26 | 0.00 |
June | 6128.85 | 26-JUN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.75 | 0.00 |
July | 6315.76 | 05-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.49 |
August | 5000.56 | 04-AUG-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.92 | 0.00 |
September | 5057.26 | 11-SEP-12:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.54 | 0.00 |
October | 1970.29 | 27-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.60 |
November | 2330.26 | 10-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 728.37 |
December | 2116.34 | 28-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1242.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1970.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6315.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.92 | 1400.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5455.48 | 13-JAN-17:00 | 12070.02 | 9872.03 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5636.68 | 24-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7861.95 | 24-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24271.24 | 17-APR-06:02 | 6352.64 | 8226.80 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29491.54 | 30-MAY-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30579.23 | 19-JUN-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31072.43 | 31-JUL-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30443.68 | 14-AUG-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30656.83 | 11-SEP-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9838.91 | 20-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9696.84 | 03-NOV-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5274.52 | 07-DEC-16:30 | 12070.02 | 9872.03 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5274.52 | 2541.06 | 2193.73 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31072.43 | 12070.02 | 9872.03 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5101.30 | 13-JAN-16:50 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5559.11 | 24-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7584.63 | 24-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17080.77 | 17-APR-15:20 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21184.00 | 30-MAY-06:02 | 6352.64 | 8226.80 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31686.23 | 12-JUN-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31646.69 | 03-JUL-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 25246.34 | 14-AUG-06:02 | 6352.64 | 8226.80 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31927.99 | 11-SEP-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9336.71 | 20-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8595.72 | 03-NOV-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4945.90 | 01-DEC-16:25 | 12070.02 | 9872.03 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 4945.90 | 2541.06 | 2193.73 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31927.99 | 12070.02 | 9872.03 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 861.93 | 14-JAN-17:02 | 334.80 | 289.04 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.78 |
February | 1032.64 | 24-FEB-15:50 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.62 |
March | 1361.53 | 28-MAR-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.09 |
April | 5653.98 | 18-APR-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 116.87 | 0.00 |
May | 6124.04 | 31-MAY-14:50 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 71.05 | 0.00 |
June | 12375.06 | 25-JUN-17:21 | 0.00 | 193.02 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 391.68 | 0.00 |
July | 10347.77 | 02-JUL-16:51 | 468.72 | 193.02 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 112.49 | 0.00 |
August | 6776.16 | 04-AUG-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 95.02 | 0.00 |
September | 6124.83 | 11-SEP-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 96.84 | 0.00 |
October | 1633.13 | 20-OCT-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.56 |
November | 1379.68 | 03-NOV-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.17 |
December | 863.30 | 02-DEC-17:03 | 200.88 | 173.42 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 861.93 | 0.00 | 173.42 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12375.06 | 1306.65 | 496.34 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 391.68 | 442.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 576.90 | 12-JAN-10:30 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.87 |
February | 818.67 | 24-FEB-10:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.75 |
March | 2542.19 | 28-MAR-09:35 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.39 |
April | 7836.46 | 18-APR-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.95 | 0.00 |
May | 11136.90 | 28-MAY-09:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.19 |
June | 14198.90 | 25-JUN-08:42 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.30 |
July | 14476.48 | 02-JUL-09:32 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.18 |
August | 11874.81 | 27-AUG-08:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.30 |
September | 14044.93 | 04-SEP-09:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.31 |
October | 3028.61 | 20-OCT-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.70 |
November | 1025.34 | 04-NOV-09:30 | 261.23 | 104.74 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.94 |
December | 544.04 | 01-DEC-10:20 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 544.04 | 169.56 | 69.83 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14476.48 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.95 | 375.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4577.78 | 12-JAN-12:30 | 1375.43 | 992.69 | 2551.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.72 |
February | 7896.09 | 24-FEB-13:45 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.43 |
March | 8368.78 | 24-MAR-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.14 |
April | 17169.65 | 16-APR-13:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 40.67 | 0.00 |
May | 10703.19 | 29-MAY-13:23 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.63 |
June | 16502.88 | 11-JUN-15:22 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 525.69 | 0.00 |
July | 17122.09 | 30-JUL-13:12 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.07 |
August | 12817.73 | 29-AUG-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.12 |
September | 18731.31 | 04-SEP-12:52 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.63 |
October | 11456.05 | 20-OCT-13:05 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.37 |
November | 10383.62 | 03-NOV-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.39 |
December | 5676.79 | 01-DEC-13:25 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4577.78 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18731.31 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 525.69 | 322.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 768.08 | 12-JAN-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.96 |
February | 2737.76 | 24-FEB-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.66 |
March | 3166.67 | 23-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.36 |
April | 15614.21 | 16-APR-16:12 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 103.17 | 0.00 |
May | 17031.65 | 14-MAY-16:31 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.47 |
June | 16300.50 | 25-JUN-16:41 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 211.74 | 0.00 |
July | 16282.22 | 02-JUL-16:51 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 25.47 | 0.00 |
August | 14819.55 | 05-AUG-17:04 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.26 |
September | 16686.60 | 04-SEP-16:51 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.83 |
October | 5611.76 | 20-OCT-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.71 |
November | 3698.27 | 03-NOV-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.32 |
December | 762.40 | 01-DEC-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 762.40 | 254.33 | 104.73 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17031.65 | 805.38 | 314.21 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 211.74 | 246.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 832.11 | 14-JAN-17:02 | 334.80 | 289.04 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.73 |
February | 831.58 | 11-FEB-17:02 | 334.80 | 262.25 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.55 |
March | 1109.63 | 28-MAR-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.54 |
April | 3121.21 | 18-APR-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 62.90 | 0.00 |
May | 3934.84 | 31-MAY-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 38.74 | 0.00 |
June | 5482.30 | 26-JUN-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 44.04 | 0.00 |
July | 7449.31 | 05-JUL-06:03 | 803.52 | 496.35 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.46 |
August | 5552.81 | 04-AUG-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 50.78 | 0.00 |
September | 5776.51 | 11-SEP-06:03 | 1071.35 | 754.64 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.71 |
October | 1503.47 | 20-OCT-13:50 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.05 |
November | 1308.96 | 03-NOV-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.43 |
December | 831.40 | 02-DEC-17:03 | 200.88 | 173.42 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 831.40 | 200.88 | 173.42 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7449.31 | 1306.65 | 754.64 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 62.90 | 253.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 583.42 | 13-JAN-11:20 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.45 |
February | 723.18 | 24-FEB-10:10 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.25 |
March | 1199.65 | 28-MAR-09:35 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.03 |
April | 5327.04 | 18-APR-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.11 | 0.00 |
May | 6199.93 | 31-MAY-09:20 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 8.38 | 0.00 |
June | 11249.60 | 11-JUN-09:41 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.85 | 0.00 |
July | 12108.92 | 04-JUL-08:41 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.28 |
August | 8175.25 | 20-AUG-10:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.72 |
September | 11440.58 | 04-SEP-09:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.27 |
October | 2662.00 | 20-OCT-09:40 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.33 |
November | 1245.86 | 04-NOV-08:55 | 508.69 | 209.49 | 1009.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.47 |
December | 587.87 | 05-DEC-09:30 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 583.42 | 169.56 | 69.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12108.92 | 1654.44 | 628.45 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.85 | 357.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1143.91 | 13-JAN-14:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2199.50 |
February | 1752.52 | 24-FEB-14:25 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1808.15 |
March | 3841.77 | 24-MAR-14:00 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1271.41 |
April | 9494.25 | 18-APR-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 2940.99 | 0.00 |
May | 9986.43 | 31-MAY-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4129.67 | 0.00 |
June | 11577.14 | 26-JUN-16:10 | 401.76 | 275.75 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 5849.03 | 0.00 |
July | 13198.52 | 02-JUL-15:21 | 602.64 | 248.17 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 81.12 | 0.00 |
August | 11595.88 | 04-AUG-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4845.38 | 0.00 |
September | 14476.37 | 04-SEP-12:52 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.97 |
October | 10009.93 | 01-OCT-13:33 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.13 |
November | 8266.85 | 03-NOV-12:07 | 3816.70 | 1489.03 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 938.04 |
December | 1260.35 | 02-DEC-12:40 | 137.54 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1143.91 | 137.54 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14476.37 | 3816.70 | 1489.03 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 5849.03 | 2199.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 707.23 | 12-JAN-16:10 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.52 |
February | 1513.12 | 24-FEB-16:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.56 |
March | 1530.68 | 23-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.15 |
April | 8598.30 | 15-APR-17:04 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 111.89 | 0.00 |
May | 12143.13 | 14-MAY-16:31 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.27 |
June | 12508.40 | 25-JUN-17:21 | 0.00 | 122.19 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 123.51 | 0.00 |
July | 12727.12 | 02-JUL-18:01 | 0.00 | 157.10 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 9.77 | 0.00 |
August | 10371.43 | 05-AUG-17:04 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.08 |
September | 12983.77 | 04-SEP-16:51 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.71 |
October | 4681.92 | 11-OCT-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.20 |
November | 3089.96 | 03-NOV-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.71 |
December | 738.85 | 01-DEC-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 707.23 | 0.00 | 122.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12983.77 | 805.38 | 314.21 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 123.51 | 123.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 852.01 | 13-JAN-14:40 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.97 |
February | 960.08 | 24-FEB-16:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.80 |
March | 1258.34 | 28-MAR-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.69 |
April | 5233.66 | 18-APR-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 97.88 | 0.00 |
May | 5665.71 | 31-MAY-06:03 | 803.52 | 496.35 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.20 |
June | 9955.20 | 25-JUN-18:31 | 0.00 | 220.59 | 3088.82 | 0.00 | 0.00 | 0.00 | 0.00 | 151.46 | 0.00 |
July | 8775.86 | 04-JUL-18:42 | 0.00 | 165.44 | 2316.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.97 |
August | 6497.46 | 04-AUG-07:33 | 3816.70 | 1489.03 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 3.21 | 0.00 |
September | 7286.82 | 11-SEP-06:03 | 1071.35 | 759.27 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.37 |
October | 1824.38 | 02-OCT-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.07 |
November | 1453.87 | 03-NOV-13:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.31 |
December | 795.43 | 02-DEC-17:03 | 200.88 | 173.42 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 795.43 | 0.00 | 165.44 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9955.20 | 3816.70 | 1489.03 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 151.46 | 204.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 661.21 | 13-JAN-11:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.23 |
February | 2038.99 | 24-FEB-11:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.63 |
March | 4863.30 | 24-MAR-12:02 | 4832.57 | 1885.36 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.94 |
April | 8301.72 | 18-APR-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 28.04 | 0.00 |
May | 14009.64 | 29-MAY-09:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.56 |
June | 15445.55 | 25-JUN-08:31 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.94 |
July | 15392.31 | 04-JUL-08:61 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.03 |
August | 14210.63 | 27-AUG-09:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.32 |
September | 11594.51 | 17-SEP-08:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.05 |
October | 4832.24 | 03-OCT-12:02 | 4832.57 | 1885.36 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.18 |
November | 2971.17 | 03-NOV-12:03 | 2416.29 | 942.68 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.58 |
December | 625.64 | 05-DEC-09:50 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 564.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 625.64 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15445.55 | 4832.57 | 1885.36 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 28.04 | 564.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5347.06 | 12-JAN-12:30 | 1375.43 | 992.69 | 2551.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.95 |
February | 8097.59 | 24-FEB-13:35 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.48 |
March | 8534.87 | 24-MAR-13:10 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.05 |
April | 15736.39 | 16-APR-13:22 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 12.72 | 0.00 |
May | 13990.78 | 29-MAY-12:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.10 |
June | 15778.78 | 25-JUN-12:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 232.69 | 0.00 |
July | 16342.85 | 30-JUL-13:42 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.02 |
August | 15321.88 | 13-AUG-16:11 | 468.72 | 193.02 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.24 |
September | 15964.10 | 04-SEP-13:02 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.41 |
October | 15690.67 | 01-OCT-13:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.52 |
November | 10663.77 | 03-NOV-13:05 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.38 |
December | 6275.97 | 01-DEC-13:25 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5347.06 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16342.85 | 2613.31 | 992.69 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 232.69 | 491.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 795.83 | 12-JAN-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.03 |
February | 2779.15 | 24-FEB-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.93 |
March | 3282.81 | 23-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.96 |
April | 15342.60 | 16-APR-17:21 | 0.00 | 122.19 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.57 |
May | 13599.32 | 14-MAY-16:42 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.55 |
June | 15986.69 | 25-JUN-17:51 | 0.00 | 157.10 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 72.88 | 0.00 |
July | 15079.99 | 30-JUL-17:01 | 0.00 | 122.19 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.54 |
August | 15483.34 | 13-AUG-16:11 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.50 |
September | 13382.72 | 04-SEP-16:22 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.49 |
October | 5628.93 | 20-OCT-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.53 |
November | 3892.50 | 03-NOV-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.83 |
December | 798.00 | 01-DEC-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 795.83 | 0.00 | 87.28 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15986.69 | 805.38 | 314.21 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 72.88 | 208.03 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.210895E+12 | 255304.87 | 30-JAN-07:10 | 0.132982E+12 | 157779.45 | 30-JAN-09:30 |
February | 0.153858E+12 | 252361.73 | 02-FEB-07:10 | 0.913347E+11 | 158631.09 | 02-FEB-12:20 |
March | 0.128985E+12 | 215714.80 | 06-MAR-07:10 | 0.629527E+11 | 108513.41 | 06-MAR-08:09 |
April | 0.101205E+12 | 184762.82 | 03-APR-06:10 | 0.331736E+11 | 82781.36 | 03-APR-06:00 |
May | 0.103500E+12 | 136300.31 | 31-MAY-15:09 | 0.133322E+11 | 39497.07 | 02-MAY-06:10 |
June | 0.128151E+12 | 173855.98 | 26-JUN-07:49 | 0.115718E+11 | 21894.99 | 03-JUN-06:19 |
July | 0.138131E+12 | 167080.57 | 05-JUL-10:50 | 0.109001E+11 | 9972.85 | 03-JUL-11:20 |
August | 0.142236E+12 | 179918.82 | 04-AUG-07:10 | 0.112891E+11 | 11025.82 | 07-AUG-06:19 |
September | 0.108239E+12 | 144505.74 | 11-SEP-09:50 | 0.129946E+11 | 46406.81 | 29-SEP-06:10 |
October | 0.954828E+11 | 113479.90 | 16-OCT-06:10 | 0.244647E+11 | 57921.56 | 23-OCT-06:40 |
November | 0.130406E+12 | 236691.70 | 27-NOV-07:10 | 0.560123E+11 | 126616.79 | 28-NOV-07:00 |
December | 0.176872E+12 | 247810.23 | 11-DEC-07:10 | 0.100828E+12 | 153603.95 | 09-DEC-07:30 |
Annual Sum or Average | 0.161796E+13 | 0.561836E+12 | ||||
Minimum of Months | 0.954828E+11 | 113479.90 | 0.109001E+11 | 9972.85 | ||
Maximum of Months | 0.210895E+12 | 255304.87 | 0.132982E+12 | 158631.09 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.200662E+11 | 0.602207E+10 | 0.593559E+11 | 0.983053E+09 | 0.574081E+10 | 12379742.02 | 0.118714E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178241E+11 | 0.477907E+10 | 0.537310E+11 | 0.889306E+09 | 0.434813E+10 | 11196021.66 | 0.722746E+11 | 367256.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207957E+11 | 0.441157E+10 | 0.617796E+11 | 0.102904E+10 | 0.428415E+10 | 12675672.10 | 0.365563E+11 | 0.116234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.184126E+11 | 0.348415E+10 | 0.572952E+11 | 0.946219E+09 | 0.503432E+10 | 11960507.72 | 0.117191E+11 | 0.430154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197068E+11 | 0.302042E+10 | 0.605677E+11 | 0.100554E+10 | 0.734396E+10 | 12527707.06 | 0.864054E+09 | 0.109792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.195872E+11 | 0.270375E+10 | 0.594895E+11 | 0.989881E+09 | 0.131242E+11 | 12231776.97 | 0.238261E+09 | 0.320060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.183333E+11 | 0.287876E+10 | 0.583622E+11 | 0.961669E+09 | 0.146079E+11 | 12256437.81 | 3951228.32 | 0.429707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.204886E+11 | 0.333052E+10 | 0.617796E+11 | 0.102889E+10 | 0.146664E+11 | 12675672.10 | 33685592.18 | 0.408960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.184905E+11 | 0.388110E+10 | 0.572729E+11 | 0.946020E+09 | 0.918327E+10 | 11960507.72 | 0.993590E+09 | 0.174596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194442E+11 | 0.491326E+10 | 0.593671E+11 | 0.982584E+09 | 0.428997E+10 | 12379742.02 | 0.499262E+10 | 0.148074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197669E+11 | 0.558954E+10 | 0.580818E+11 | 0.964780E+09 | 0.426695E+10 | 12059151.09 | 0.415440E+11 | 0.179700E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197018E+11 | 0.625066E+10 | 0.583511E+11 | 0.962730E+09 | 0.484072E+10 | 12256437.81 | 0.867531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232618E+12 | 0.512649E+11 | 0.705434E+12 | 0.116897E+11 | 0.917308E+11 | 0.146559E+09 | 0.374688E+12 | 0.150390E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.178241E+11 | 0.270375E+10 | 0.537310E+11 | 0.889306E+09 | 0.426695E+10 | 11196021.66 | 3951228.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.207957E+11 | 0.625066E+10 | 0.617796E+11 | 0.102904E+10 | 0.146664E+11 | 12675672.10 | 0.118714E+12 | 0.429707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.120591E+12 | 0.00 | 0.123907E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.800085E+11 | 0.00 | 0.113262E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.500576E+11 | 0.00 | 0.128951E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.214255E+11 | 0.00 | 0.117481E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.135309E+10 | 0.00 | 0.119791E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.230480E+09 | 0.00 | 0.113413E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.109001E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 5991391.79 | 0.00 | 0.112831E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.236519E+10 | 0.00 | 0.106294E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.132209E+11 | 0.00 | 0.112439E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.446548E+11 | 0.00 | 0.113576E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.889348E+11 | 0.00 | 0.118934E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.422848E+12 | 0.00 | 0.138988E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.106294E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.120591E+12 | 0.00 | 0.128951E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 25003.79 | 02-JAN-16:40 | 5686.19 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 838.79 | 02-JAN-16:49 | 7676.21 | 02-JAN-06:19 | 6.85 | 02-JAN-17:19 | 212408.91 | 30-JAN-07:10 |
February | 23035.24 | 14-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 836.41 | 22-FEB-08:20 | 7223.46 | 06-FEB-07:10 | 6.85 | 02-FEB-22:19 | 210582.89 | 02-FEB-07:10 |
March | 21170.50 | 01-MAR-16:00 | 5686.19 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 834.30 | 14-MAR-07:19 | 6059.66 | 06-MAR-07:10 | 6.85 | 01-MAR-18:19 | 181014.00 | 06-MAR-07:10 |
April | 20664.51 | 10-APR-07:10 | 5686.19 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 834.39 | 10-APR-07:19 | 21929.50 | 18-APR-15:09 | 6.85 | 01-APR-05:10 | 151351.92 | 03-APR-06:10 |
May | 19750.06 | 24-MAY-15:00 | 3328.83 | 01-MAY-19:10 | 45864.70 | 01-MAY-07:10 | 833.12 | 25-MAY-07:19 | 23553.72 | 30-MAY-15:30 | 6.85 | 02-MAY-07:10 | 37210.86 | 02-MAY-06:10 |
June | 20258.61 | 13-JUN-07:10 | 3328.83 | 01-JUN-19:40 | 45864.70 | 01-JUN-07:10 | 833.85 | 13-JUN-07:19 | 31205.30 | 26-JUN-15:30 | 6.85 | 10-JUN-17:10 | 12303.54 | 05-JUN-06:10 |
July | 20264.44 | 20-JUL-07:10 | 3328.83 | 01-JUL-19:00 | 45864.70 | 03-JUL-07:10 | 833.86 | 20-JUL-07:19 | 30920.55 | 03-JUL-15:20 | 6.85 | 01-JUL-16:10 | 1375.36 | 24-JUL-06:10 |
August | 19947.32 | 31-AUG-07:10 | 5686.19 | 08-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 833.44 | 31-AUG-07:19 | 32052.63 | 04-AUG-07:10 | 6.85 | 01-AUG-05:10 | 3990.07 | 16-AUG-06:10 |
September | 20673.01 | 21-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 834.40 | 21-SEP-07:19 | 24308.64 | 07-SEP-15:00 | 6.85 | 02-SEP-16:10 | 44154.67 | 30-SEP-06:10 |
October | 24253.07 | 31-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 839.16 | 31-OCT-07:19 | 9388.97 | 20-OCT-15:30 | 6.85 | 03-OCT-11:09 | 74874.18 | 16-OCT-06:10 |
November | 25003.79 | 06-NOV-16:00 | 5686.19 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 839.72 | 03-NOV-07:19 | 6763.16 | 03-NOV-14:39 | 6.85 | 01-NOV-16:10 | 194602.20 | 27-NOV-07:10 |
December | 25003.79 | 01-DEC-16:30 | 5686.19 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 839.04 | 22-DEC-08:20 | 7367.81 | 11-DEC-07:10 | 6.85 | 01-DEC-06:10 | 205072.17 | 11-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 19750.06 | 3328.83 | 45864.70 | 833.12 | 6059.66 | 6.85 | 1375.36 | |||||||
Maximum of Months | 25003.79 | 5686.19 | 45864.70 | 839.72 | 32052.63 | 6.85 | 212408.91 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 148.22 | 24-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5872.19 | 25-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 49973.16 | 18-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 51078.78 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 79667.37 | 26-JUN-07:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 76804.37 | 05-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 82003.88 | 04-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 62947.56 | 06-SEP-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21419.56 | 20-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3892.17 | 03-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82003.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 255304.87 | 30-JAN-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 7525.71 | 6.85 | 212408.91 | 0.00 | 0.00 |
February | 252361.73 | 02-FEB-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 6408.59 | 6.85 | 210582.89 | 0.00 | 0.00 |
March | 215714.80 | 06-MAR-07:10 | 7291.91 | 21098.80 | 0.00 | 243.58 | 6059.66 | 6.85 | 181014.00 | 0.00 | 0.00 |
April | 184762.82 | 03-APR-06:10 | 7241.08 | 21098.80 | 0.00 | 243.58 | 4820.59 | 6.85 | 151351.92 | 0.00 | 0.00 |
May | 136300.31 | 31-MAY-15:09 | 19671.42 | 42072.41 | 0.00 | 831.72 | 23016.64 | 6.85 | 0.00 | 50701.28 | 0.00 |
June | 173855.98 | 26-JUN-07:49 | 19671.42 | 45864.70 | 0.00 | 833.07 | 27812.57 | 6.85 | 0.00 | 79667.37 | 0.00 |
July | 167080.57 | 05-JUL-10:50 | 19671.42 | 41577.77 | 0.00 | 831.54 | 28188.63 | 6.85 | 0.00 | 76804.37 | 0.00 |
August | 179918.82 | 04-AUG-07:10 | 19671.42 | 45864.70 | 0.00 | 815.84 | 32052.63 | 6.85 | 0.00 | 81507.38 | 0.00 |
September | 144505.74 | 11-SEP-09:50 | 19671.42 | 40588.47 | 0.00 | 831.19 | 22432.38 | 6.85 | 0.00 | 60975.44 | 0.00 |
October | 113479.90 | 16-OCT-06:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 3235.47 | 6.85 | 74874.18 | 0.00 | 0.00 |
November | 236691.70 | 27-NOV-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 6719.25 | 6.85 | 194602.20 | 0.00 | 0.00 |
December | 247810.23 | 11-DEC-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 7367.81 | 6.85 | 205072.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 113479.90 | 7241.08 | 21098.80 | 0.00 | 243.58 | 3235.47 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 255304.87 | 19671.42 | 45864.70 | 5686.19 | 833.07 | 32052.63 | 6.85 | 212408.91 | 81507.38 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 148130.34 | 06-JAN-07:19 | 0.00 | 12660.79 | 31-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 148130.34 | 01-FEB-07:19 | 0.00 | 12758.92 | 15-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 98960.09 | 06-MAR-08:09 | 0.00 | 12671.74 | 01-MAR-12:20 | 0.00 |
April | 0.00 | 0.00 | 73832.86 | 03-APR-06:00 | 0.00 | 11895.14 | 06-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 31312.05 | 02-MAY-06:19 | 0.00 | 10687.37 | 02-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 13251.05 | 03-JUN-06:19 | 0.00 | 10123.74 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9972.85 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 3519.15 | 07-AUG-06:10 | 0.00 | 9893.13 | 02-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 38925.63 | 29-SEP-06:19 | 0.00 | 9950.13 | 28-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 51376.52 | 23-OCT-06:19 | 0.00 | 10078.34 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 122163.36 | 25-NOV-07:30 | 0.00 | 10236.14 | 30-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 144938.16 | 09-DEC-07:30 | 0.00 | 11466.11 | 26-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9893.13 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 148130.34 | 0.00 | 12758.92 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 19.60 | 1.67 | 19.60 | 0.00 | 19.60 | 0.00 | 19.60 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.07 | 0.83 | 25.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.67 | 19.60 | 1.67 | 19.60 | 0.83 | 20.69 | 0.83 | 21.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.60 | 1.67 | 19.60 | 0.83 | 25.07 | 0.83 | 25.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 18.71 | 1.33 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
February | 0.17 | 19.25 | 0.17 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.74 | 0.33 | 24.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 17.99 | 0.17 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
December | 0.50 | 18.46 | 0.33 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 |
Annual Sum or Average | 2.83 | 18.61 | 2.00 | 18.91 | 0.33 | 19.29 | 0.33 | 19.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 19.25 | 1.33 | 19.25 | 0.33 | 24.74 | 0.33 | 24.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.17 | 18.77 | 6.17 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
February | 3.33 | 18.62 | 2.33 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
March | 1.00 | 17.74 | 0.50 | 18.21 | 0.00 | 18.21 | 0.00 | 18.21 |
April | 0.17 | 19.31 | 0.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.00 | 18.71 | 1.50 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
December | 4.17 | 18.69 | 3.00 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
Annual Sum or Average | 18.83 | 18.67 | 13.67 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.17 | 19.31 | 6.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 118.33 | 16.08 | 58.50 | 16.55 | 0.00 | 16.55 | 0.00 | 16.55 |
February | 59.17 | 16.31 | 28.33 | 16.84 | 0.00 | 16.84 | 0.00 | 16.84 |
March | 19.67 | 15.90 | 7.00 | 16.25 | 0.00 | 16.25 | 0.00 | 16.25 |
April | 3.33 | 15.68 | 0.50 | 16.18 | 0.00 | 16.18 | 0.00 | 16.18 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.52 | 3.00 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.43 | 1.00 | 27.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 30.33 | 15.78 | 10.50 | 16.24 | 0.00 | 16.24 | 0.00 | 16.24 |
December | 61.33 | 15.87 | 27.00 | 16.31 | 0.00 | 16.31 | 0.00 | 16.31 |
Annual Sum or Average | 292.17 | 16.04 | 131.83 | 16.51 | 6.17 | 16.67 | 4.00 | 16.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.33 | 16.31 | 58.50 | 16.84 | 4.67 | 27.52 | 3.00 | 27.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 71.83 | 14.60 | 20.17 | 14.67 | 0.00 | 14.67 | 0.00 | 14.67 |
February | 32.83 | 14.71 | 6.33 | 14.80 | 0.00 | 14.80 | 0.00 | 14.80 |
March | 13.17 | 15.08 | 1.00 | 15.11 | 0.00 | 15.11 | 0.00 | 15.11 |
April | 2.67 | 14.83 | 0.00 | 14.83 | 1.83 | 19.95 | 1.83 | 22.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.64 | 4.67 | 27.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.00 | 6.67 | 28.05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.96 | 8.67 | 27.99 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.62 | 4.00 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.64 | 3.67 | 27.64 |
October | 0.17 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
November | 22.50 | 14.66 | 4.33 | 14.67 | 0.00 | 14.67 | 0.00 | 14.67 |
December | 44.17 | 14.73 | 11.33 | 14.78 | 0.00 | 14.78 | 0.00 | 14.78 |
Annual Sum or Average | 187.33 | 14.70 | 43.17 | 14.75 | 32.00 | 16.34 | 29.50 | 17.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 0.00 | 14.67 |
Maximum of Months | 71.83 | 17.20 | 20.17 | 17.20 | 9.67 | 28.00 | 8.67 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 64.33 | 15.03 | 16.00 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 |
February | 30.17 | 15.45 | 7.67 | 15.87 | 0.00 | 15.87 | 0.00 | 15.87 |
March | 11.50 | 15.39 | 1.17 | 15.56 | 0.00 | 15.56 | 0.00 | 15.56 |
April | 2.67 | 14.90 | 0.00 | 14.90 | 2.00 | 20.49 | 1.83 | 22.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.45 | 1.83 | 27.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.86 | 4.50 | 27.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.81 | 5.83 | 27.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.62 | 5.50 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.02 | 5.00 | 28.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.57 | 0.67 | 27.57 |
November | 16.67 | 14.85 | 3.83 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
December | 37.17 | 15.17 | 10.00 | 15.40 | 0.00 | 15.40 | 0.00 | 15.40 |
Annual Sum or Average | 162.50 | 15.15 | 38.67 | 15.40 | 28.00 | 16.91 | 25.17 | 18.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.98 | 0.00 | 14.98 |
Maximum of Months | 64.33 | 15.45 | 16.00 | 15.87 | 6.83 | 28.02 | 5.83 | 28.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 69.67 | 14.51 | 19.67 | 14.55 | 0.00 | 14.55 | 0.00 | 14.55 |
February | 32.67 | 14.66 | 7.00 | 14.71 | 0.00 | 14.71 | 0.00 | 14.71 |
March | 13.00 | 15.03 | 1.67 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
April | 2.67 | 14.82 | 0.00 | 14.82 | 2.33 | 21.08 | 1.50 | 22.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.89 | 3.00 | 27.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 28.41 | 4.00 | 28.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 28.34 | 5.67 | 28.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.94 | 3.50 | 27.96 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.06 | 3.00 | 28.08 |
October | 0.17 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 |
November | 21.17 | 14.62 | 4.50 | 14.62 | 0.00 | 14.62 | 0.00 | 14.62 |
December | 42.17 | 14.63 | 10.67 | 14.64 | 0.00 | 14.64 | 0.00 | 14.64 |
Annual Sum or Average | 181.50 | 14.62 | 43.50 | 14.64 | 34.67 | 16.45 | 20.67 | 17.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 | 0.00 | 14.55 |
Maximum of Months | 69.67 | 17.24 | 19.67 | 17.24 | 11.17 | 28.41 | 5.67 | 28.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 74.50 | 18.06 | 53.83 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 |
February | 51.83 | 18.24 | 37.33 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
March | 7.33 | 17.65 | 4.00 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 |
April | 0.50 | 18.80 | 0.33 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.66 | 0.33 | 24.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9.00 | 17.22 | 4.33 | 17.87 | 0.00 | 17.87 | 0.00 | 17.87 |
December | 22.50 | 17.38 | 14.17 | 17.82 | 0.00 | 17.82 | 0.00 | 17.82 |
Annual Sum or Average | 165.67 | 17.96 | 114.00 | 18.45 | 0.33 | 18.45 | 0.33 | 18.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.50 | 18.80 | 53.83 | 19.19 | 0.33 | 24.66 | 0.33 | 24.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.17 | 15.19 | 4.50 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 |
February | 11.83 | 15.14 | 0.83 | 15.18 | 0.00 | 15.18 | 0.00 | 15.18 |
March | 2.83 | 16.07 | 0.17 | 16.24 | 0.00 | 16.24 | 0.00 | 16.24 |
April | 0.17 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.36 | 0.67 | 27.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.44 | 5.67 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.70 | 6.33 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 26.92 | 2.17 | 26.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.55 | 3.17 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4.50 | 15.53 | 0.17 | 15.67 | 0.00 | 15.67 | 0.00 | 15.67 |
December | 9.83 | 15.43 | 2.00 | 15.53 | 0.00 | 15.53 | 0.00 | 15.53 |
Annual Sum or Average | 51.33 | 15.31 | 7.67 | 15.39 | 18.00 | 18.22 | 18.00 | 19.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.17 | 16.77 | 4.50 | 16.77 | 6.33 | 27.70 | 6.33 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 131.83 | 15.85 | 118.83 | 15.88 | 0.00 | 15.88 | 0.00 | 15.88 |
February | 85.83 | 16.36 | 80.50 | 16.38 | 0.00 | 16.38 | 0.00 | 16.38 |
March | 60.67 | 17.54 | 60.00 | 17.54 | 0.00 | 17.54 | 0.00 | 17.54 |
April | 28.50 | 18.36 | 28.33 | 18.36 | 0.83 | 18.50 | 0.83 | 18.62 |
May | 3.17 | 19.47 | 3.17 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.42 | 2.00 | 27.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.53 | 2.83 | 27.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 26.78 | 3.00 | 26.78 |
September | 2.67 | 19.65 | 2.67 | 19.65 | 13.33 | 24.17 | 13.17 | 24.92 |
October | 11.17 | 19.09 | 11.17 | 19.09 | 0.67 | 19.34 | 0.67 | 19.57 |
November | 47.83 | 17.44 | 47.00 | 17.45 | 0.00 | 17.45 | 0.00 | 17.45 |
December | 95.33 | 16.70 | 89.50 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
Annual Sum or Average | 467.00 | 16.78 | 441.17 | 16.81 | 22.67 | 17.05 | 22.50 | 17.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.88 | 0.00 | 15.88 |
Maximum of Months | 131.83 | 19.65 | 118.83 | 19.65 | 13.33 | 27.53 | 13.17 | 27.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.50 | 15.12 | 4.83 | 15.14 | 0.00 | 15.14 | 0.00 | 15.14 |
February | 10.67 | 15.24 | 1.50 | 15.25 | 0.00 | 15.25 | 0.00 | 15.25 |
March | 1.50 | 16.35 | 0.17 | 16.64 | 0.00 | 16.64 | 0.00 | 16.64 |
April | 0.17 | 16.72 | 0.00 | 16.72 | 1.33 | 26.50 | 0.83 | 26.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.46 | 1.17 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.92 | 3.00 | 27.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.89 | 4.50 | 27.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.63 | 2.17 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.72 | 2.83 | 27.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4.83 | 15.49 | 0.50 | 15.58 | 0.00 | 15.58 | 0.00 | 15.58 |
December | 11.00 | 15.23 | 2.67 | 15.21 | 0.00 | 15.21 | 0.00 | 15.21 |
Annual Sum or Average | 50.67 | 15.25 | 9.67 | 15.26 | 25.17 | 18.95 | 14.50 | 20.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.50 | 16.72 | 4.83 | 16.72 | 9.33 | 27.92 | 4.50 | 27.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 72.83 | 16.84 | 38.17 | 17.40 | 0.00 | 17.40 | 0.00 | 17.40 |
February | 37.50 | 17.07 | 20.17 | 17.61 | 0.00 | 17.61 | 0.00 | 17.61 |
March | 7.17 | 16.95 | 3.00 | 17.55 | 0.00 | 17.55 | 0.00 | 17.55 |
April | 0.67 | 17.76 | 0.33 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.34 | 1.50 | 27.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.00 | 27.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.61 | 0.17 | 24.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15.50 | 16.41 | 7.83 | 16.84 | 0.00 | 16.84 | 0.00 | 16.84 |
December | 37.83 | 16.48 | 19.00 | 16.92 | 0.00 | 16.92 | 0.00 | 16.92 |
Annual Sum or Average | 171.50 | 16.78 | 88.50 | 17.30 | 3.00 | 17.41 | 1.67 | 17.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 72.83 | 17.76 | 38.17 | 18.20 | 2.67 | 27.34 | 1.50 | 27.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 38.67 | 14.85 | 7.17 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
February | 17.17 | 15.05 | 1.67 | 15.14 | 0.00 | 15.14 | 0.00 | 15.14 |
March | 3.50 | 15.51 | 0.00 | 15.51 | 0.00 | 15.51 | 0.00 | 15.51 |
April | 0.50 | 15.99 | 0.00 | 15.99 | 1.00 | 23.57 | 1.00 | 25.09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.74 | 4.50 | 27.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.63 | 7.17 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.91 | 8.67 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.46 | 2.83 | 27.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.86 | 3.17 | 27.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10.17 | 14.91 | 2.33 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
December | 22.50 | 15.01 | 3.67 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 |
Annual Sum or Average | 92.50 | 14.96 | 14.83 | 14.98 | 28.67 | 17.67 | 27.33 | 19.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.67 | 15.99 | 7.17 | 15.99 | 9.00 | 27.91 | 8.67 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.67 | 15.28 | 5.17 | 15.46 | 0.00 | 15.46 | 0.00 | 15.46 |
February | 12.50 | 15.44 | 1.50 | 15.68 | 0.00 | 15.68 | 0.00 | 15.68 |
March | 2.00 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 |
April | 0.50 | 17.47 | 0.17 | 17.94 | 1.67 | 25.02 | 1.67 | 26.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.39 | 1.50 | 27.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.69 | 4.33 | 27.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.68 | 5.83 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.57 | 4.67 | 27.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.95 | 5.33 | 27.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.56 | 1.67 | 27.56 |
November | 8.17 | 15.19 | 2.00 | 15.27 | 0.33 | 15.65 | 0.33 | 16.01 |
December | 15.67 | 15.23 | 2.67 | 15.35 | 0.00 | 15.35 | 0.00 | 15.35 |
Annual Sum or Average | 68.50 | 15.32 | 11.50 | 15.48 | 26.33 | 18.51 | 25.33 | 20.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.35 | 0.00 | 15.35 |
Maximum of Months | 29.67 | 17.47 | 5.17 | 17.94 | 6.17 | 27.95 | 5.83 | 27.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 38.33 | 14.83 | 7.33 | 14.82 | 0.00 | 14.82 | 0.00 | 14.82 |
February | 17.33 | 15.07 | 2.33 | 15.14 | 0.00 | 15.14 | 0.00 | 15.14 |
March | 2.50 | 15.53 | 0.00 | 15.53 | 0.00 | 15.53 | 0.00 | 15.53 |
April | 0.50 | 15.96 | 0.00 | 15.96 | 2.17 | 25.83 | 1.33 | 26.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.88 | 2.50 | 27.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.30 | 3.50 | 28.34 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 28.23 | 5.33 | 28.25 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.92 | 3.17 | 27.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.88 | 3.50 | 27.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.00 | 14.90 | 3.00 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
December | 22.50 | 14.96 | 5.17 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
Annual Sum or Average | 92.17 | 14.94 | 17.83 | 14.94 | 31.83 | 17.89 | 19.33 | 19.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.33 | 15.96 | 7.33 | 15.96 | 10.33 | 28.30 | 5.33 | 28.34 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.66 | 234.83 | 21.37 | 234.83 | 21.21 |
February | 454.00 | 22.42 | 83.83 | 22.18 | 83.83 | 22.00 |
March | 493.67 | 23.31 | 3.33 | 23.30 | 3.33 | 23.28 |
April | 347.33 | 23.71 | 52.33 | 23.83 | 0.00 | 23.83 |
May | 50.50 | 23.96 | 290.67 | 24.45 | 0.00 | 24.45 |
June | 0.00 | 0.00 | 438.33 | 24.40 | 0.00 | 24.40 |
July | 0.00 | 0.00 | 492.00 | 24.45 | 0.00 | 24.45 |
August | 1.50 | 24.69 | 504.00 | 24.40 | 1.50 | 24.40 |
September | 38.67 | 23.98 | 270.50 | 24.57 | 0.00 | 24.57 |
October | 277.33 | 24.06 | 27.83 | 24.15 | 0.00 | 24.15 |
November | 370.50 | 23.11 | 45.17 | 23.01 | 29.33 | 22.87 |
December | 497.00 | 22.42 | 74.83 | 22.21 | 74.83 | 22.05 |
Annual Sum or Average | 3032.50 | 22.87 | 2517.67 | 23.31 | 427.67 | 23.13 |
Minimum of Months | 0.00 | 0.00 | 3.33 | 21.37 | 0.00 | 21.21 |
Maximum of Months | 502.00 | 24.69 | 504.00 | 24.57 | 234.83 | 24.57 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.54 | 450.67 | 20.47 | 450.67 | 20.45 |
February | 454.00 | 21.01 | 286.33 | 20.84 | 286.33 | 20.77 |
March | 513.17 | 21.96 | 137.67 | 21.70 | 137.67 | 21.54 |
April | 393.83 | 22.62 | 68.17 | 22.62 | 33.67 | 22.50 |
May | 136.50 | 23.61 | 201.00 | 23.98 | 0.00 | 23.98 |
June | 27.33 | 23.47 | 368.00 | 24.23 | 0.00 | 24.23 |
July | 0.00 | 0.00 | 475.33 | 24.33 | 0.00 | 24.33 |
August | 1.00 | 24.27 | 481.00 | 24.27 | 1.00 | 24.27 |
September | 135.67 | 23.55 | 196.33 | 24.07 | 0.00 | 24.07 |
October | 469.83 | 23.12 | 0.00 | 23.12 | 0.00 | 23.12 |
November | 463.83 | 21.81 | 176.67 | 21.49 | 176.67 | 21.30 |
December | 497.00 | 20.85 | 368.17 | 20.71 | 368.17 | 20.65 |
Annual Sum or Average | 3594.17 | 21.83 | 3209.33 | 22.19 | 1454.17 | 21.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 20.47 | 0.00 | 20.45 |
Maximum of Months | 513.17 | 24.27 | 481.00 | 24.33 | 450.67 | 24.33 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.13 | 479.33 | 20.09 | 479.33 | 20.08 |
February | 454.00 | 20.47 | 367.67 | 20.36 | 367.67 | 20.31 |
March | 514.00 | 21.37 | 253.33 | 21.11 | 253.33 | 20.97 |
April | 408.33 | 22.01 | 124.50 | 21.89 | 88.17 | 21.67 |
May | 182.33 | 23.28 | 171.67 | 23.71 | 0.00 | 23.71 |
June | 61.00 | 23.20 | 347.50 | 24.12 | 0.00 | 24.12 |
July | 6.50 | 23.53 | 458.67 | 24.29 | 0.00 | 24.29 |
August | 20.00 | 23.52 | 445.67 | 24.20 | 3.00 | 24.20 |
September | 197.50 | 23.02 | 164.00 | 23.58 | 3.00 | 23.56 |
October | 492.17 | 22.19 | 64.67 | 22.01 | 64.67 | 21.86 |
November | 485.50 | 21.07 | 273.67 | 20.75 | 273.67 | 20.59 |
December | 497.00 | 20.29 | 468.00 | 20.24 | 468.00 | 20.23 |
Annual Sum or Average | 3820.33 | 21.32 | 3618.67 | 21.67 | 2000.83 | 21.36 |
Minimum of Months | 6.50 | 20.13 | 64.67 | 20.09 | 0.00 | 20.08 |
Maximum of Months | 514.00 | 23.53 | 479.33 | 24.29 | 479.33 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.57 | 501.00 | 19.57 | 501.00 | 19.57 |
February | 454.00 | 19.76 | 441.17 | 19.74 | 441.17 | 19.74 |
March | 514.00 | 20.54 | 383.00 | 20.40 | 383.00 | 20.35 |
April | 427.00 | 21.09 | 224.83 | 20.95 | 193.00 | 20.76 |
May | 252.00 | 22.65 | 176.17 | 23.20 | 10.33 | 23.14 |
June | 125.33 | 23.49 | 349.67 | 24.10 | 37.67 | 24.20 |
July | 68.50 | 24.51 | 448.83 | 24.36 | 46.33 | 24.42 |
August | 90.17 | 23.54 | 397.83 | 24.05 | 38.67 | 24.06 |
September | 269.67 | 22.24 | 178.83 | 22.84 | 27.83 | 22.71 |
October | 499.67 | 21.06 | 213.00 | 20.77 | 213.00 | 20.62 |
November | 489.00 | 20.16 | 352.17 | 19.92 | 352.17 | 19.83 |
December | 497.00 | 19.68 | 497.00 | 19.68 | 497.00 | 19.68 |
Annual Sum or Average | 4188.33 | 20.77 | 4163.50 | 21.12 | 2741.17 | 20.85 |
Minimum of Months | 68.50 | 19.57 | 176.17 | 19.57 | 10.33 | 19.57 |
Maximum of Months | 514.00 | 24.51 | 501.00 | 24.36 | 501.00 | 24.42 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.69 | 488.67 | 19.67 | 488.67 | 19.66 |
February | 454.00 | 19.93 | 408.67 | 19.84 | 408.67 | 19.81 |
March | 504.00 | 20.86 | 304.33 | 20.58 | 304.33 | 20.45 |
April | 393.00 | 21.58 | 201.50 | 21.54 | 146.83 | 21.31 |
May | 174.83 | 23.33 | 252.00 | 23.99 | 24.33 | 24.09 |
June | 104.50 | 24.20 | 384.50 | 24.36 | 47.83 | 24.52 |
July | 87.50 | 25.73 | 470.50 | 24.69 | 77.50 | 24.86 |
August | 83.67 | 24.69 | 444.83 | 24.33 | 61.50 | 24.44 |
September | 219.83 | 22.81 | 223.50 | 23.55 | 37.33 | 23.58 |
October | 482.33 | 21.61 | 137.50 | 21.28 | 137.00 | 21.07 |
November | 486.17 | 20.33 | 334.83 | 20.07 | 334.83 | 19.95 |
December | 497.00 | 19.77 | 496.00 | 19.77 | 496.00 | 19.77 |
Annual Sum or Average | 3988.83 | 21.06 | 4146.83 | 21.46 | 2564.83 | 21.20 |
Minimum of Months | 83.67 | 19.69 | 137.50 | 19.67 | 24.33 | 19.66 |
Maximum of Months | 504.00 | 25.73 | 496.00 | 24.69 | 496.00 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 495.00 | 20.01 | 421.50 | 19.79 | 421.50 | 19.71 |
February | 438.67 | 20.38 | 341.00 | 20.12 | 335.83 | 20.01 |
March | 461.67 | 20.99 | 289.00 | 20.76 | 276.00 | 20.60 |
April | 358.33 | 21.36 | 217.17 | 21.43 | 149.67 | 21.19 |
May | 200.83 | 22.78 | 225.50 | 23.56 | 19.17 | 23.55 |
June | 128.17 | 23.63 | 348.00 | 24.15 | 42.50 | 24.27 |
July | 90.83 | 24.91 | 443.33 | 24.51 | 64.67 | 24.63 |
August | 102.17 | 24.30 | 423.33 | 24.28 | 60.00 | 24.38 |
September | 224.83 | 22.88 | 237.00 | 23.60 | 40.50 | 23.65 |
October | 389.67 | 21.63 | 172.33 | 21.64 | 117.17 | 21.41 |
November | 467.17 | 20.71 | 293.83 | 20.40 | 280.67 | 20.21 |
December | 486.83 | 20.23 | 410.83 | 20.01 | 410.83 | 19.93 |
Annual Sum or Average | 3844.17 | 21.24 | 3822.83 | 21.61 | 2218.50 | 21.33 |
Minimum of Months | 90.83 | 20.01 | 172.33 | 19.79 | 19.17 | 19.71 |
Maximum of Months | 495.00 | 24.91 | 443.33 | 24.51 | 421.50 | 24.63 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.72 | 488.17 | 19.69 | 488.17 | 19.68 |
February | 450.33 | 20.02 | 406.00 | 19.92 | 406.00 | 19.88 |
March | 491.17 | 20.75 | 331.00 | 20.53 | 329.67 | 20.43 |
April | 371.50 | 21.28 | 223.67 | 21.32 | 160.67 | 21.09 |
May | 213.67 | 22.93 | 227.00 | 23.60 | 27.33 | 23.66 |
June | 129.50 | 23.74 | 372.33 | 24.21 | 47.17 | 24.35 |
July | 94.50 | 25.17 | 455.67 | 24.58 | 72.83 | 24.72 |
August | 101.83 | 24.23 | 443.83 | 24.26 | 61.33 | 24.34 |
September | 248.00 | 22.61 | 219.00 | 23.30 | 41.50 | 23.30 |
October | 449.83 | 21.26 | 187.83 | 21.02 | 170.50 | 20.82 |
November | 480.50 | 20.30 | 332.67 | 20.04 | 330.17 | 19.92 |
December | 497.00 | 19.81 | 475.33 | 19.76 | 475.33 | 19.75 |
Annual Sum or Average | 4029.83 | 20.99 | 4162.50 | 21.39 | 2610.67 | 21.13 |
Minimum of Months | 94.50 | 19.72 | 187.83 | 19.69 | 27.33 | 19.68 |
Maximum of Months | 502.00 | 25.17 | 488.17 | 24.58 | 488.17 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.65 | 502.00 | 19.65 | 502.00 | 19.65 |
February | 454.00 | 19.94 | 449.83 | 19.93 | 449.83 | 19.93 |
March | 514.00 | 20.57 | 397.00 | 20.48 | 397.00 | 20.45 |
April | 465.33 | 21.11 | 235.83 | 20.94 | 222.67 | 20.81 |
May | 379.00 | 22.67 | 88.00 | 22.87 | 11.00 | 22.83 |
June | 121.50 | 23.19 | 299.33 | 23.93 | 19.50 | 23.95 |
July | 29.83 | 24.47 | 443.50 | 24.27 | 22.83 | 24.30 |
August | 45.50 | 23.96 | 425.00 | 24.14 | 23.00 | 24.16 |
September | 221.33 | 22.83 | 164.00 | 23.43 | 3.17 | 23.40 |
October | 499.33 | 21.87 | 57.83 | 21.74 | 57.83 | 21.63 |
November | 489.00 | 20.81 | 294.67 | 20.54 | 294.67 | 20.41 |
December | 497.00 | 19.98 | 497.00 | 19.98 | 497.00 | 19.98 |
Annual Sum or Average | 4217.83 | 21.01 | 3854.00 | 21.28 | 2500.50 | 21.01 |
Minimum of Months | 29.83 | 19.65 | 57.83 | 19.65 | 3.17 | 19.65 |
Maximum of Months | 514.00 | 24.47 | 502.00 | 24.27 | 502.00 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.82 | 492.50 | 19.81 | 492.50 | 19.80 |
February | 454.00 | 20.16 | 418.50 | 20.11 | 418.50 | 20.09 |
March | 514.00 | 20.96 | 311.83 | 20.73 | 311.83 | 20.63 |
April | 410.50 | 21.55 | 181.00 | 21.47 | 139.33 | 21.24 |
May | 205.17 | 23.12 | 189.17 | 23.82 | 6.33 | 23.84 |
June | 104.50 | 24.14 | 383.00 | 24.35 | 40.33 | 24.46 |
July | 54.17 | 26.29 | 484.50 | 24.68 | 54.17 | 24.83 |
August | 37.33 | 25.26 | 491.17 | 24.38 | 32.50 | 24.44 |
September | 162.33 | 23.44 | 233.83 | 24.13 | 13.33 | 24.21 |
October | 462.83 | 22.61 | 22.00 | 22.56 | 16.67 | 22.49 |
November | 485.00 | 21.05 | 277.17 | 20.73 | 277.17 | 20.58 |
December | 497.00 | 20.07 | 493.00 | 20.07 | 493.00 | 20.07 |
Annual Sum or Average | 3888.83 | 21.29 | 3977.67 | 21.70 | 2295.67 | 21.41 |
Minimum of Months | 37.33 | 19.82 | 22.00 | 19.81 | 6.33 | 19.80 |
Maximum of Months | 514.00 | 26.29 | 493.00 | 24.68 | 493.00 | 24.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 18.85 | 481.33 | 18.79 | 481.33 | 18.77 |
February | 451.67 | 19.67 | 375.67 | 19.49 | 375.67 | 19.43 |
March | 497.33 | 20.53 | 310.00 | 20.27 | 308.33 | 20.14 |
April | 417.83 | 21.18 | 207.33 | 21.10 | 168.00 | 20.90 |
May | 333.33 | 22.37 | 116.83 | 22.87 | 11.00 | 22.83 |
June | 186.17 | 23.03 | 301.00 | 23.80 | 60.50 | 23.86 |
July | 117.50 | 24.12 | 449.67 | 24.32 | 95.33 | 24.34 |
August | 110.50 | 23.84 | 468.00 | 24.22 | 82.00 | 24.24 |
September | 194.00 | 22.92 | 243.00 | 23.89 | 25.17 | 24.00 |
October | 383.50 | 22.23 | 73.33 | 22.42 | 21.67 | 22.31 |
November | 457.17 | 20.68 | 252.50 | 20.41 | 235.67 | 20.19 |
December | 493.67 | 19.66 | 422.67 | 19.51 | 421.00 | 19.44 |
Annual Sum or Average | 4144.67 | 20.93 | 3701.33 | 21.27 | 2285.67 | 20.97 |
Minimum of Months | 110.50 | 18.85 | 73.33 | 18.79 | 11.00 | 18.77 |
Maximum of Months | 502.00 | 24.12 | 481.33 | 24.32 | 481.33 | 24.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.83 | 492.50 | 19.81 | 492.50 | 19.81 |
February | 454.00 | 20.23 | 415.00 | 20.16 | 415.00 | 20.14 |
March | 512.67 | 20.92 | 333.67 | 20.71 | 333.67 | 20.61 |
April | 407.83 | 21.59 | 172.17 | 21.49 | 136.67 | 21.29 |
May | 253.83 | 22.89 | 163.00 | 23.45 | 11.17 | 23.43 |
June | 109.67 | 23.75 | 368.83 | 24.23 | 32.33 | 24.32 |
July | 48.00 | 26.09 | 481.33 | 24.64 | 44.67 | 24.77 |
August | 30.00 | 25.52 | 486.33 | 24.40 | 28.67 | 24.47 |
September | 173.17 | 23.29 | 239.00 | 24.00 | 17.17 | 24.07 |
October | 443.00 | 22.37 | 44.33 | 22.34 | 27.00 | 22.25 |
November | 479.50 | 21.03 | 267.33 | 20.71 | 265.67 | 20.55 |
December | 497.00 | 20.10 | 475.83 | 20.06 | 475.83 | 20.05 |
Annual Sum or Average | 3910.67 | 21.25 | 3939.33 | 21.65 | 2280.33 | 21.37 |
Minimum of Months | 30.00 | 19.83 | 44.33 | 19.81 | 11.17 | 19.81 |
Maximum of Months | 512.67 | 26.09 | 492.50 | 24.64 | 492.50 | 24.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.67 | 496.83 | 19.67 | 496.83 | 19.67 |
February | 454.00 | 19.97 | 423.17 | 19.93 | 423.17 | 19.92 |
March | 514.00 | 20.83 | 326.50 | 20.63 | 326.50 | 20.55 |
April | 417.17 | 21.49 | 164.17 | 21.39 | 127.17 | 21.18 |
May | 209.83 | 23.05 | 183.17 | 23.57 | 1.67 | 23.55 |
June | 88.00 | 23.94 | 376.67 | 24.26 | 31.00 | 24.34 |
July | 32.67 | 25.14 | 474.17 | 24.42 | 30.50 | 24.46 |
August | 51.83 | 24.07 | 440.50 | 24.19 | 32.17 | 24.21 |
September | 221.50 | 22.74 | 175.83 | 23.39 | 6.00 | 23.36 |
October | 491.83 | 21.72 | 99.50 | 21.50 | 99.00 | 21.34 |
November | 489.00 | 20.66 | 304.17 | 20.35 | 304.17 | 20.21 |
December | 497.00 | 19.88 | 497.00 | 19.88 | 497.00 | 19.88 |
Annual Sum or Average | 3968.83 | 21.00 | 3961.67 | 21.39 | 2375.17 | 21.10 |
Minimum of Months | 32.67 | 19.67 | 99.50 | 19.67 | 1.67 | 19.67 |
Maximum of Months | 514.00 | 25.14 | 497.00 | 24.42 | 497.00 | 24.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.57 | 415.17 | 19.54 | 415.17 | 19.53 |
February | 385.00 | 19.99 | 338.50 | 19.89 | 338.50 | 19.85 |
March | 424.50 | 21.07 | 229.83 | 20.75 | 229.83 | 20.60 |
April | 322.50 | 21.84 | 138.50 | 21.88 | 91.33 | 21.68 |
May | 139.17 | 23.73 | 213.33 | 24.25 | 22.50 | 24.40 |
June | 86.00 | 24.73 | 337.67 | 24.56 | 46.00 | 24.73 |
July | 67.50 | 26.33 | 413.33 | 24.85 | 67.33 | 25.04 |
August | 55.33 | 25.13 | 394.67 | 24.46 | 46.50 | 24.55 |
September | 171.67 | 23.23 | 187.50 | 23.97 | 20.67 | 24.07 |
October | 398.33 | 22.10 | 57.33 | 21.94 | 51.83 | 21.78 |
November | 412.00 | 20.66 | 260.17 | 20.34 | 260.17 | 20.20 |
December | 422.00 | 19.78 | 418.00 | 19.77 | 418.00 | 19.77 |
Annual Sum or Average | 3311.00 | 21.23 | 3404.00 | 21.64 | 2007.83 | 21.37 |
Minimum of Months | 55.33 | 19.57 | 57.33 | 19.54 | 20.67 | 19.53 |
Maximum of Months | 427.00 | 26.33 | 418.00 | 24.85 | 418.00 | 25.04 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.50 | 20.25 | 402.67 | 19.99 | 402.67 | 19.90 |
February | 436.00 | 20.74 | 302.83 | 20.45 | 297.50 | 20.30 |
March | 454.67 | 21.35 | 240.83 | 21.10 | 226.33 | 20.91 |
April | 345.50 | 21.78 | 173.00 | 21.95 | 98.00 | 21.73 |
May | 160.83 | 23.12 | 230.50 | 23.86 | 8.17 | 23.90 |
June | 97.67 | 24.16 | 367.33 | 24.32 | 39.67 | 24.44 |
July | 62.67 | 25.62 | 471.00 | 24.58 | 53.67 | 24.71 |
August | 70.33 | 24.91 | 464.33 | 24.39 | 51.00 | 24.49 |
September | 182.33 | 23.39 | 246.67 | 24.05 | 27.33 | 24.16 |
October | 363.67 | 22.29 | 111.00 | 22.49 | 43.83 | 22.36 |
November | 447.00 | 21.13 | 247.00 | 20.85 | 225.67 | 20.62 |
December | 477.00 | 20.48 | 394.83 | 20.27 | 392.33 | 20.18 |
Annual Sum or Average | 3591.17 | 21.52 | 3652.00 | 21.95 | 1866.17 | 21.67 |
Minimum of Months | 62.67 | 20.25 | 111.00 | 19.99 | 8.17 | 19.90 |
Maximum of Months | 493.50 | 25.62 | 471.00 | 24.58 | 402.67 | 24.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.81 | 483.83 | 19.78 | 483.83 | 19.76 |
February | 450.50 | 20.24 | 380.50 | 20.11 | 380.50 | 20.06 |
March | 488.67 | 21.05 | 281.00 | 20.79 | 279.50 | 20.67 |
April | 358.17 | 21.69 | 172.67 | 21.80 | 106.17 | 21.58 |
May | 174.50 | 23.29 | 240.17 | 23.90 | 15.33 | 23.98 |
June | 97.67 | 24.23 | 394.50 | 24.36 | 41.17 | 24.48 |
July | 65.17 | 25.90 | 478.67 | 24.65 | 60.33 | 24.80 |
August | 68.50 | 24.81 | 472.17 | 24.37 | 50.83 | 24.45 |
September | 201.83 | 23.08 | 223.17 | 23.79 | 22.17 | 23.87 |
October | 439.17 | 21.92 | 98.83 | 21.79 | 78.50 | 21.61 |
November | 477.33 | 20.78 | 288.33 | 20.47 | 284.33 | 20.31 |
December | 497.00 | 20.01 | 467.33 | 19.95 | 467.33 | 19.93 |
Annual Sum or Average | 3820.50 | 21.22 | 3981.17 | 21.66 | 2270.00 | 21.39 |
Minimum of Months | 65.17 | 19.81 | 98.83 | 19.78 | 15.33 | 19.76 |
Maximum of Months | 502.00 | 25.90 | 483.83 | 24.65 | 483.83 | 24.80 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.66360 | 13.80120 | -0.5022 | 11.89054 |
February | 454.00000 | 22.41860 | 17.38523 | -0.2877 | 8.17154 |
March | 514.00000 | 23.35493 | 21.82738 | -0.0131 | 5.98335 |
April | 485.00000 | 23.88591 | 28.21745 | 0.19562 | 6.53557 |
May | 508.00000 | 24.33810 | 40.84427 | -0.4314 | 9.49224 |
June | 496.00000 | 24.35385 | 47.64351 | -0.3311 | 7.71801 |
July | 497.00000 | 24.44965 | 51.81200 | -0.2594 | 6.89864 |
August | 514.00000 | 24.38828 | 50.93285 | -0.2836 | 7.12014 |
September | 485.00000 | 24.39284 | 37.48535 | -0.4064 | 9.18979 |
October | 502.00000 | 24.17914 | 27.32073 | 0.27358 | 6.73613 |
November | 489.00000 | 23.38720 | 23.60508 | 0.01901 | 7.01705 |
December | 497.00000 | 22.41736 | 15.75511 | -0.2994 | 8.04930 |
Annual Sum or Average | 5943.00000 | 23.61077 | 31.51683 | -0.1938 | 7.89721 |
Minimum of Months | 454.00000 | 21.66360 | 13.80120 | -0.5022 | 5.98335 |
Maximum of Months | 514.00000 | 24.44965 | 51.81200 | 0.27358 | 11.89054 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.54163 | 14.31028 | -0.7699 | 19.07277 |
February | 454.00000 | 21.00975 | 18.57238 | -0.6121 | 14.19385 |
March | 514.00000 | 21.95984 | 23.75772 | -0.3287 | 8.98252 |
April | 485.00000 | 22.90439 | 30.58576 | -0.0267 | 7.08078 |
May | 508.00000 | 23.98721 | 42.39347 | -0.5568 | 12.19459 |
June | 496.00000 | 24.19363 | 48.90604 | -0.4036 | 8.87748 |
July | 497.00000 | 24.31462 | 52.78972 | -0.3231 | 7.50582 |
August | 514.00000 | 24.25313 | 51.96952 | -0.3550 | 7.89831 |
September | 485.00000 | 24.06285 | 38.93186 | -0.5445 | 12.38431 |
October | 502.00000 | 23.17688 | 29.98716 | 0.02836 | 5.76264 |
November | 489.00000 | 21.91851 | 26.00279 | -0.3263 | 10.45179 |
December | 497.00000 | 20.85032 | 16.86681 | -0.6635 | 15.51102 |
Annual Sum or Average | 5943.00000 | 22.77778 | 33.05350 | -0.4058 | 10.79877 |
Minimum of Months | 454.00000 | 20.54163 | 14.31028 | -0.7699 | 5.76264 |
Maximum of Months | 514.00000 | 24.31462 | 52.78972 | 0.02836 | 19.07277 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.12943 | 14.59324 | -0.9045 | 24.48347 |
February | 454.00000 | 20.47181 | 19.10702 | -0.7721 | 19.60779 |
March | 514.00000 | 21.36975 | 24.34586 | -0.4906 | 12.07069 |
April | 485.00000 | 22.34607 | 31.39690 | -0.1663 | 8.97483 |
May | 508.00000 | 23.79836 | 42.81726 | -0.6237 | 14.50991 |
June | 496.00000 | 24.09361 | 49.31611 | -0.4332 | 9.87507 |
July | 497.00000 | 24.27100 | 53.09766 | -0.3326 | 7.69234 |
August | 514.00000 | 24.17146 | 52.29959 | -0.3828 | 8.37549 |
September | 485.00000 | 23.71950 | 39.75500 | -0.6719 | 16.84149 |
October | 502.00000 | 22.22885 | 31.34896 | -0.2058 | 7.49179 |
November | 489.00000 | 21.09104 | 26.55449 | -0.5495 | 15.23219 |
December | 497.00000 | 20.28844 | 17.12026 | -0.8367 | 21.68297 |
Annual Sum or Average | 5943.00000 | 22.34690 | 33.60885 | -0.5292 | 13.84838 |
Minimum of Months | 454.00000 | 20.12943 | 14.59324 | -0.9045 | 7.49179 |
Maximum of Months | 514.00000 | 24.27100 | 53.09766 | -0.1663 | 24.48347 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.57493 | 14.23426 | -1.1415 | 34.40498 |
February | 454.00000 | 19.76372 | 19.37742 | -1.0156 | 29.31847 |
March | 514.00000 | 20.54480 | 25.51104 | -0.7178 | 18.29621 |
April | 485.00000 | 21.45823 | 32.87065 | -0.3781 | 13.30117 |
May | 508.00000 | 23.37927 | 43.97958 | -0.7426 | 19.88567 |
June | 496.00000 | 23.97866 | 50.51329 | -0.4267 | 11.53970 |
July | 497.00000 | 24.26076 | 54.57218 | -0.2901 | 7.83653 |
August | 514.00000 | 24.01174 | 53.83212 | -0.3998 | 9.40523 |
September | 485.00000 | 23.11610 | 41.72402 | -0.8565 | 25.24039 |
October | 502.00000 | 21.07618 | 33.55352 | -0.4759 | 12.07106 |
November | 489.00000 | 20.15666 | 28.13048 | -0.8056 | 23.08311 |
December | 497.00000 | 19.68391 | 17.44160 | -1.0697 | 31.24834 |
Annual Sum or Average | 5943.00000 | 21.76803 | 34.77881 | -0.6907 | 19.53747 |
Minimum of Months | 454.00000 | 19.57493 | 14.23426 | -1.1415 | 7.83653 |
Maximum of Months | 514.00000 | 24.26076 | 54.57218 | -0.2901 | 34.40498 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.68807 | 15.18622 | -1.0893 | 32.28004 |
February | 454.00000 | 19.92922 | 20.33815 | -0.9418 | 26.78563 |
March | 514.00000 | 20.92242 | 26.05608 | -0.5958 | 16.19209 |
April | 485.00000 | 22.08200 | 32.46889 | -0.2042 | 12.37768 |
May | 508.00000 | 23.89894 | 42.69029 | -0.5128 | 14.29035 |
June | 496.00000 | 24.14494 | 49.82820 | -0.2905 | 10.26651 |
July | 497.00000 | 24.45665 | 53.64455 | -0.1351 | 7.51453 |
August | 514.00000 | 24.18430 | 52.97352 | -0.2679 | 8.05280 |
September | 485.00000 | 23.59548 | 40.64985 | -0.6369 | 19.74324 |
October | 502.00000 | 21.69809 | 33.57365 | -0.3143 | 9.84100 |
November | 489.00000 | 20.35449 | 28.95194 | -0.7453 | 21.35959 |
December | 497.00000 | 19.77110 | 18.24493 | -1.0307 | 29.65019 |
Annual Sum or Average | 5943.00000 | 22.07862 | 34.67656 | -0.5607 | 17.26625 |
Minimum of Months | 454.00000 | 19.68807 | 15.18622 | -1.0893 | 7.51453 |
Maximum of Months | 514.00000 | 24.45665 | 53.64455 | -0.1351 | 32.28004 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.06177 | 14.55136 | -0.9374 | 28.36634 |
February | 454.00000 | 20.49759 | 18.95199 | -0.7611 | 22.50735 |
March | 514.00000 | 21.31984 | 24.33496 | -0.4877 | 15.01274 |
April | 485.00000 | 22.12503 | 31.34455 | -0.1864 | 12.95677 |
May | 508.00000 | 23.64183 | 43.05213 | -0.6220 | 17.42486 |
June | 496.00000 | 24.00096 | 50.28847 | -0.3890 | 11.45887 |
July | 497.00000 | 24.32175 | 54.18608 | -0.2265 | 8.01828 |
August | 514.00000 | 24.13785 | 53.00793 | -0.2929 | 8.76312 |
September | 485.00000 | 23.60852 | 40.08393 | -0.6066 | 19.66110 |
October | 502.00000 | 22.23255 | 30.85100 | -0.1616 | 10.12272 |
November | 489.00000 | 20.87577 | 27.37264 | -0.5959 | 18.66489 |
December | 497.00000 | 20.31181 | 17.00823 | -0.8596 | 25.36112 |
Annual Sum or Average | 5943.00000 | 22.27652 | 33.88450 | -0.5087 | 16.46179 |
Minimum of Months | 454.00000 | 20.06177 | 14.55136 | -0.9374 | 8.01828 |
Maximum of Months | 514.00000 | 24.32175 | 54.18608 | -0.1616 | 28.36634 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.71725 | 14.98513 | -1.0874 | 32.34729 |
February | 454.00000 | 20.04727 | 20.00621 | -0.9213 | 26.35283 |
March | 514.00000 | 20.89606 | 25.87583 | -0.6124 | 16.71119 |
April | 485.00000 | 21.97031 | 32.37666 | -0.2235 | 13.30351 |
May | 508.00000 | 23.61254 | 43.62677 | -0.6186 | 17.79031 |
June | 496.00000 | 24.05019 | 50.36919 | -0.3343 | 11.29375 |
July | 497.00000 | 24.37694 | 54.19846 | -0.1717 | 8.05922 |
August | 514.00000 | 24.14231 | 53.38086 | -0.2794 | 8.59853 |
September | 485.00000 | 23.39951 | 41.41435 | -0.7087 | 22.34230 |
October | 502.00000 | 21.55857 | 33.22146 | -0.3445 | 11.29713 |
November | 489.00000 | 20.37145 | 28.80391 | -0.7423 | 21.61935 |
December | 497.00000 | 19.80617 | 18.14307 | -1.0240 | 29.62254 |
Annual Sum or Average | 5943.00000 | 22.01257 | 34.82979 | -0.5864 | 18.19115 |
Minimum of Months | 454.00000 | 19.71725 | 14.98513 | -1.0874 | 8.05922 |
Maximum of Months | 514.00000 | 24.37694 | 54.19846 | -0.1717 | 32.34729 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.65014 | 14.58261 | -1.0983 | 32.27613 |
February | 454.00000 | 19.93829 | 19.70010 | -0.9650 | 26.58094 |
March | 514.00000 | 20.56615 | 26.10915 | -0.7199 | 17.39448 |
April | 485.00000 | 21.23180 | 34.11285 | -0.4544 | 12.24362 |
May | 508.00000 | 23.01947 | 46.05971 | -0.9125 | 24.93618 |
June | 496.00000 | 23.91652 | 50.86163 | -0.4995 | 11.73669 |
July | 497.00000 | 24.21842 | 54.43963 | -0.3457 | 7.92450 |
August | 514.00000 | 24.10651 | 53.36384 | -0.3925 | 8.57672 |
September | 485.00000 | 23.55986 | 40.99647 | -0.7091 | 18.31461 |
October | 502.00000 | 21.88284 | 32.75020 | -0.2615 | 7.65575 |
November | 489.00000 | 20.81241 | 27.64220 | -0.6134 | 16.41487 |
December | 497.00000 | 19.97953 | 17.79378 | -0.9566 | 25.97148 |
Annual Sum or Average | 5943.00000 | 21.92283 | 35.00333 | -0.6588 | 17.43995 |
Minimum of Months | 454.00000 | 19.65014 | 14.58261 | -1.0983 | 7.65575 |
Maximum of Months | 514.00000 | 24.21842 | 54.43963 | -0.2615 | 32.27613 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.82060 | 15.54769 | -1.0373 | 29.69678 |
February | 454.00000 | 20.15774 | 20.65342 | -0.8813 | 23.34880 |
March | 514.00000 | 20.96381 | 26.66672 | -0.5916 | 14.69370 |
April | 485.00000 | 21.97619 | 33.47546 | -0.2508 | 10.64814 |
May | 508.00000 | 23.85095 | 43.83949 | -0.5835 | 14.86758 |
June | 496.00000 | 24.18359 | 49.62591 | -0.3261 | 9.47603 |
July | 497.00000 | 24.48442 | 53.10109 | -0.1633 | 6.95040 |
August | 514.00000 | 24.29206 | 52.29868 | -0.2479 | 7.08072 |
September | 485.00000 | 24.03492 | 39.70545 | -0.4838 | 13.42029 |
October | 502.00000 | 22.72534 | 32.18968 | -0.0536 | 6.51322 |
November | 489.00000 | 21.07308 | 28.33609 | -0.5393 | 15.06234 |
December | 497.00000 | 20.07460 | 18.70347 | -0.9165 | 24.43034 |
Annual Sum or Average | 5943.00000 | 22.32012 | 34.63737 | -0.5038 | 14.61511 |
Minimum of Months | 454.00000 | 19.82060 | 15.54769 | -1.0373 | 6.51322 |
Maximum of Months | 514.00000 | 24.48442 | 53.10109 | -0.0536 | 29.69678 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 18.85208 | 13.15324 | -1.1467 | 34.92042 |
February | 454.00000 | 19.69378 | 17.57034 | -0.8926 | 24.94802 |
March | 514.00000 | 20.64874 | 23.30433 | -0.6148 | 16.47776 |
April | 485.00000 | 21.61356 | 31.06483 | -0.3077 | 12.14110 |
May | 508.00000 | 23.04650 | 44.85752 | -0.8426 | 23.49156 |
June | 496.00000 | 23.75166 | 51.52059 | -0.5029 | 13.34409 |
July | 497.00000 | 24.25496 | 55.53245 | -0.2735 | 7.87330 |
August | 514.00000 | 24.17046 | 53.82734 | -0.2821 | 8.03075 |
September | 485.00000 | 23.79519 | 39.03263 | -0.5162 | 16.20101 |
October | 502.00000 | 22.74271 | 28.88346 | 0.00616 | 7.48581 |
November | 489.00000 | 20.95502 | 25.17743 | -0.5072 | 15.95582 |
December | 497.00000 | 19.70115 | 15.66799 | -0.9196 | 26.23394 |
Annual Sum or Average | 5943.00000 | 21.95247 | 33.44481 | -0.5649 | 17.20742 |
Minimum of Months | 454.00000 | 18.85208 | 13.15324 | -1.1467 | 7.48581 |
Maximum of Months | 514.00000 | 24.25496 | 55.53245 | 0.00616 | 34.92042 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83084 | 15.38351 | -1.0396 | 29.86914 |
February | 454.00000 | 20.23480 | 20.47266 | -0.8663 | 23.07865 |
March | 514.00000 | 20.92391 | 26.60378 | -0.6091 | 15.20152 |
April | 485.00000 | 22.00829 | 33.11913 | -0.2360 | 10.79905 |
May | 508.00000 | 23.57050 | 44.78701 | -0.6902 | 18.07764 |
June | 496.00000 | 24.10723 | 50.07723 | -0.3642 | 10.18100 |
July | 497.00000 | 24.47678 | 53.32276 | -0.1739 | 6.99347 |
August | 514.00000 | 24.31168 | 52.38877 | -0.2394 | 7.01073 |
September | 485.00000 | 23.94405 | 40.13387 | -0.5239 | 14.57720 |
October | 502.00000 | 22.57458 | 31.90293 | -0.0847 | 6.96533 |
November | 489.00000 | 21.09292 | 28.17143 | -0.5344 | 15.23947 |
December | 497.00000 | 20.09887 | 18.65088 | -0.9117 | 24.41783 |
Annual Sum or Average | 5943.00000 | 22.28027 | 34.71296 | -0.5207 | 15.14217 |
Minimum of Months | 454.00000 | 19.83084 | 15.38351 | -1.0396 | 6.96533 |
Maximum of Months | 514.00000 | 24.47678 | 53.32276 | -0.0847 | 29.86914 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.67485 | 14.71594 | -1.0668 | 31.16851 |
February | 454.00000 | 19.96962 | 19.64724 | -0.9207 | 25.17174 |
March | 514.00000 | 20.83164 | 25.53413 | -0.6133 | 15.17521 |
April | 485.00000 | 21.86782 | 32.53358 | -0.2629 | 10.48657 |
May | 508.00000 | 23.66687 | 43.40705 | -0.6479 | 15.87133 |
June | 496.00000 | 24.14726 | 49.93994 | -0.3783 | 9.60158 |
July | 497.00000 | 24.34584 | 53.98615 | -0.2698 | 7.24990 |
August | 514.00000 | 24.14791 | 53.22547 | -0.3579 | 8.17223 |
September | 485.00000 | 23.53803 | 40.88771 | -0.7085 | 18.87938 |
October | 502.00000 | 21.76664 | 32.73045 | -0.2889 | 8.50348 |
November | 489.00000 | 20.65681 | 27.75853 | -0.6498 | 18.24089 |
December | 497.00000 | 19.87724 | 17.79272 | -0.9715 | 26.94511 |
Annual Sum or Average | 5943.00000 | 22.05806 | 34.47732 | -0.5924 | 16.20833 |
Minimum of Months | 454.00000 | 19.67485 | 14.71594 | -1.0668 | 7.24990 |
Maximum of Months | 514.00000 | 24.34584 | 53.98615 | -0.2629 | 31.16851 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.56711 | 15.12005 | -1.0696 | 31.56051 |
February | 385.00000 | 19.99324 | 20.06380 | -0.8870 | 24.34015 |
March | 433.00000 | 21.12505 | 25.58977 | -0.5220 | 14.04669 |
April | 410.00000 | 22.38548 | 31.54007 | -0.1202 | 10.75329 |
May | 430.00000 | 24.06678 | 41.97348 | -0.4653 | 12.71720 |
June | 418.00000 | 24.32347 | 49.01454 | -0.2572 | 9.21668 |
July | 422.00000 | 24.59837 | 52.77251 | -0.1167 | 7.36444 |
August | 433.00000 | 24.31747 | 52.28581 | -0.2466 | 7.55487 |
September | 410.00000 | 23.87654 | 39.68540 | -0.5457 | 16.25467 |
October | 427.00000 | 22.23857 | 31.99777 | -0.1695 | 7.70781 |
November | 417.00000 | 20.69799 | 27.76599 | -0.6320 | 17.97067 |
December | 422.00000 | 19.77910 | 18.13318 | -0.9780 | 27.35063 |
Annual Sum or Average | 5034.00000 | 22.26197 | 33.93002 | -0.4985 | 15.50055 |
Minimum of Months | 385.00000 | 19.56711 | 15.12005 | -1.0696 | 7.36444 |
Maximum of Months | 433.00000 | 24.59837 | 52.77251 | -0.1167 | 31.56051 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.30923 | 14.68044 | -0.8377 | 24.52594 |
February | 454.00000 | 20.87000 | 18.76643 | -0.6376 | 18.24620 |
March | 514.00000 | 21.67743 | 23.92878 | -0.3740 | 12.21345 |
April | 485.00000 | 22.51005 | 30.76505 | -0.0789 | 10.61756 |
May | 508.00000 | 23.86498 | 42.48800 | -0.5459 | 14.08786 |
June | 496.00000 | 24.15142 | 49.65160 | -0.3464 | 9.56489 |
July | 497.00000 | 24.40252 | 53.51446 | -0.2090 | 7.29591 |
August | 514.00000 | 24.24986 | 52.42403 | -0.2592 | 7.66437 |
September | 485.00000 | 23.92757 | 39.26050 | -0.4894 | 14.86273 |
October | 502.00000 | 22.84979 | 29.73954 | 0.00626 | 8.19320 |
November | 489.00000 | 21.42894 | 26.63476 | -0.4320 | 14.92794 |
December | 497.00000 | 20.62843 | 16.92666 | -0.7407 | 21.13702 |
Annual Sum or Average | 5943.00000 | 22.58646 | 33.36215 | -0.4106 | 13.56481 |
Minimum of Months | 454.00000 | 20.30923 | 14.68044 | -0.8377 | 7.29591 |
Maximum of Months | 514.00000 | 24.40252 | 53.51446 | 0.00626 | 24.52594 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.81487 | 15.44940 | -1.0138 | 29.26804 |
February | 454.00000 | 20.26714 | 20.12629 | -0.8251 | 22.46699 |
March | 514.00000 | 21.19791 | 25.60882 | -0.5078 | 13.76505 |
April | 485.00000 | 22.35682 | 31.78396 | -0.1152 | 10.76837 |
May | 508.00000 | 23.84905 | 43.01474 | -0.5387 | 14.26832 |
June | 496.00000 | 24.19890 | 49.73429 | -0.2922 | 9.37982 |
July | 497.00000 | 24.45675 | 53.55235 | -0.1541 | 7.33635 |
August | 514.00000 | 24.25299 | 52.78550 | -0.2458 | 7.53441 |
September | 485.00000 | 23.75860 | 40.51236 | -0.5793 | 16.85465 |
October | 502.00000 | 22.20245 | 32.05931 | -0.1701 | 8.25827 |
November | 489.00000 | 20.86454 | 28.24950 | -0.5892 | 17.15194 |
December | 497.00000 | 20.01420 | 18.47856 | -0.9238 | 25.44096 |
Annual Sum or Average | 5943.00000 | 22.28580 | 34.40656 | -0.4939 | 15.13741 |
Minimum of Months | 454.00000 | 19.81487 | 15.44940 | -1.0138 | 7.33635 |
Maximum of Months | 514.00000 | 24.45675 | 53.55235 | -0.1152 | 29.26804 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.141979E+09 | 40706544.42 | 13.06 | 0.118834E+09 | 23144930.11 | 0.00 | 0.22 | 25-MAR-15:00 | 0.00 | 01-MAR-00:10 | 6448.73 | 25-MAR-15:00 | 5362.40 | 25-MAR-15:00 | 1119.73 | 25-MAR-15:20 | 1813.96 | 25-MAR-15:00 | 0.00 |
April | 0.554554E+10 | 0.143576E+10 | 96.94 | 0.430183E+10 | 0.124370E+10 | 0.00 | 1.00 | 18-APR-08:40 | 0.00 | 01-APR-00:10 | 67503.89 | 18-APR-12:00 | 52818.34 | 18-APR-15:10 | 21851.94 | 18-APR-09:30 | 16761.34 | 18-APR-12:00 | 0.00 |
May | 0.141229E+11 | 0.359724E+10 | 235.51 | 0.107292E+11 | 0.339371E+10 | 0.00 | 1.00 | 05-MAY-12:40 | 0.00 | 01-MAY-00:10 | 65922.52 | 30-MAY-11:30 | 57077.08 | 31-MAY-15:10 | 26951.96 | 30-MAY-10:05 | 17031.61 | 31-MAY-12:00 | 0.00 |
June | 0.435658E+11 | 0.107911E+11 | 345.32 | 0.323165E+11 | 0.112493E+11 | 0.00 | 1.00 | 08-JUN-15:50 | 0.00 | 01-JUN-00:10 | 122233.27 | 26-JUN-07:50 | 70230.25 | 26-JUN-15:30 | 70692.86 | 26-JUN-05:12 | 27650.10 | 26-JUN-07:50 | 0.00 |
July | 0.621357E+11 | 0.149640E+11 | 432.55 | 0.419866E+11 | 0.201492E+11 | 0.00 | 1.00 | 02-JUL-08:61 | 0.00 | 01-JUL-00:10 | 114537.02 | 03-JUL-08:50 | 68388.72 | 03-JUL-15:10 | 68408.44 | 07-JUL-06:03 | 26419.63 | 05-JUL-10:50 | 0.00 |
August | 0.612117E+11 | 0.148280E+11 | 423.37 | 0.424231E+11 | 0.187886E+11 | 0.00 | 1.00 | 01-AUG-05:12 | 0.00 | 01-AUG-00:10 | 123436.53 | 03-AUG-05:12 | 69718.62 | 04-AUG-15:50 | 89081.21 | 04-AUG-07:00 | 27821.29 | 04-AUG-07:33 | 0.00 |
September | 0.257782E+11 | 0.652671E+10 | 279.20 | 0.228684E+11 | 0.290975E+10 | 0.00 | 1.00 | 01-SEP-11:00 | 0.00 | 01-SEP-00:10 | 98890.19 | 11-SEP-09:50 | 65833.42 | 07-SEP-15:50 | 46093.16 | 11-SEP-06:03 | 22971.11 | 11-SEP-09:50 | 0.00 |
October | 0.312270E+10 | 0.840661E+09 | 129.68 | 0.289549E+10 | 0.227211E+09 | 0.00 | 0.99 | 20-OCT-15:10 | 0.00 | 01-OCT-00:10 | 35857.49 | 20-OCT-15:10 | 35857.49 | 20-OCT-15:10 | 4943.99 | 02-OCT-15:00 | 8203.67 | 20-OCT-15:10 | 0.00 |
November | 0.537030E+09 | 0.149687E+09 | 27.89 | 0.459424E+09 | 77606149.29 | 0.00 | 0.37 | 02-NOV-16:00 | 0.00 | 01-NOV-00:10 | 11389.69 | 02-NOV-16:00 | 9202.06 | 02-NOV-13:00 | 2438.72 | 02-NOV-16:01 | 3084.86 | 02-NOV-16:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.216162E+12 | 0.531738E+11 | 1983.51 | 0.158099E+12 | 0.580622E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.621357E+11 | 0.149640E+11 | 432.55 | 0.424231E+11 | 0.201492E+11 | 0.00 | 1.00 | 0.00 | 123436.53 | 70230.25 | 89081.21 | 27821.29 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.130662E+09 | 37325334.48 | 11.00 | 0.111197E+09 | 19464448.67 | 0.00 | 0.26 | 25-MAR-15:00 | 0.00 | 01-MAR-00:10 | 7236.76 | 25-MAR-15:00 | 6685.79 | 25-MAR-15:00 | 955.18 | 25-MAR-15:50 | 2013.89 | 25-MAR-15:00 | 0.00 |
April | 0.537236E+10 | 0.136760E+10 | 80.62 | 0.420460E+10 | 0.116777E+10 | 0.00 | 1.00 | 15-APR-13:10 | 0.00 | 01-APR-00:10 | 67233.36 | 18-APR-12:30 | 55312.67 | 18-APR-15:00 | 23200.00 | 18-APR-09:30 | 16691.90 | 18-APR-14:05 | 0.00 |
May | 0.141140E+11 | 0.357588E+10 | 241.21 | 0.105411E+11 | 0.357290E+10 | 0.00 | 1.00 | 04-MAY-14:05 | 0.00 | 01-MAY-00:10 | 69018.97 | 30-MAY-11:00 | 57595.99 | 31-MAY-14:05 | 30833.18 | 30-MAY-10:05 | 16764.52 | 31-MAY-14:05 | 0.00 |
June | 0.415214E+11 | 0.102671E+11 | 349.75 | 0.308199E+11 | 0.107014E+11 | 0.00 | 1.00 | 08-JUN-14:05 | 0.00 | 01-JUN-00:10 | 113123.68 | 26-JUN-07:55 | 67418.77 | 26-JUN-14:05 | 65681.11 | 26-JUN-07:10 | 25645.98 | 26-JUN-07:55 | 0.00 |
July | 0.565295E+11 | 0.136260E+11 | 436.68 | 0.381368E+11 | 0.183926E+11 | 0.00 | 1.00 | 01-JUL-08:40 | 0.00 | 01-JUL-00:10 | 111042.27 | 03-JUL-08:50 | 64452.96 | 03-JUL-15:00 | 63032.76 | 05-JUL-06:03 | 25297.64 | 03-JUL-08:50 | 0.00 |
August | 0.527267E+11 | 0.128184E+11 | 424.05 | 0.365314E+11 | 0.161954E+11 | 0.00 | 1.00 | 01-AUG-06:03 | 0.00 | 01-AUG-00:10 | 114057.33 | 03-AUG-05:12 | 68232.07 | 04-AUG-15:20 | 81259.73 | 04-AUG-07:05 | 26205.78 | 04-AUG-14:05 | 0.00 |
September | 0.211845E+11 | 0.536706E+10 | 238.13 | 0.186731E+11 | 0.251138E+10 | 0.00 | 1.00 | 01-SEP-11:00 | 0.00 | 01-SEP-00:10 | 83330.58 | 11-SEP-09:50 | 63477.62 | 07-SEP-16:00 | 40325.76 | 11-SEP-06:03 | 20725.59 | 06-SEP-14:05 | 0.00 |
October | 0.120719E+10 | 0.324543E+09 | 49.83 | 0.101446E+10 | 0.192731E+09 | 0.00 | 0.88 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 28277.38 | 20-OCT-15:00 | 28277.38 | 20-OCT-15:00 | 4292.12 | 02-OCT-15:00 | 6692.66 | 20-OCT-15:00 | 0.00 |
November | 67165409.18 | 19099710.49 | 5.67 | 57193255.32 | 9972153.86 | 0.00 | 0.23 | 03-NOV-13:30 | 0.00 | 01-NOV-00:10 | 6232.12 | 03-NOV-13:30 | 5272.45 | 03-NOV-14:05 | 1272.94 | 03-NOV-13:00 | 1748.99 | 03-NOV-13:30 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.192853E+12 | 0.474030E+11 | 1836.94 | 0.140090E+12 | 0.527636E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.565295E+11 | 0.136260E+11 | 436.68 | 0.381368E+11 | 0.183926E+11 | 0.00 | 1.00 | 0.00 | 114057.33 | 68232.07 | 81259.73 | 26205.78 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 1244192.58 | 367256.30 | 0.83 | 1031086.39 | 213106.20 | 0.00 | 0.02 | 24-FEB-15:00 | 0.00 | 01-FEB-00:03 | 502.44 | 24-FEB-15:00 | 421.07 | 24-FEB-15:00 | 81.36 | 24-FEB-15:00 | 148.22 | 24-FEB-15:00 | 0.00 |
March | 0.133319E+09 | 38201918.94 | 11.00 | 0.109127E+09 | 24192035.66 | 0.00 | 0.24 | 25-MAR-15:00 | 0.00 | 01-MAR-00:10 | 7304.54 | 25-MAR-15:00 | 6383.46 | 25-MAR-15:00 | 1124.43 | 25-MAR-15:40 | 2044.34 | 25-MAR-15:00 | 0.00 |
April | 0.588042E+10 | 0.149818E+10 | 82.97 | 0.459291E+10 | 0.128751E+10 | 0.00 | 1.00 | 15-APR-13:20 | 0.00 | 01-APR-00:10 | 78769.02 | 16-APR-14:12 | 61961.42 | 18-APR-15:00 | 28382.93 | 16-APR-14:12 | 19252.82 | 16-APR-14:12 | 0.00 |
May | 0.149736E+11 | 0.380604E+10 | 242.52 | 0.112824E+11 | 0.369115E+10 | 0.00 | 1.00 | 04-MAY-14:00 | 0.00 | 01-MAY-00:10 | 71367.65 | 30-MAY-14:00 | 65366.86 | 31-MAY-15:00 | 27537.45 | 30-MAY-10:00 | 18550.50 | 31-MAY-15:00 | 0.00 |
June | 0.441077E+11 | 0.109479E+11 | 349.11 | 0.332096E+11 | 0.108981E+11 | 0.00 | 1.00 | 08-JUN-15:20 | 0.00 | 01-JUN-00:10 | 122240.96 | 26-JUN-06:03 | 81654.29 | 11-JUN-15:22 | 72728.26 | 26-JUN-05:12 | 28345.75 | 11-JUN-15:22 | 0.00 |
July | 0.594596E+11 | 0.143807E+11 | 436.36 | 0.402734E+11 | 0.191862E+11 | 0.00 | 1.00 | 01-JUL-12:40 | 0.00 | 01-JUL-00:10 | 111089.26 | 05-JUL-11:00 | 72890.57 | 02-JUL-15:32 | 64693.05 | 05-JUL-06:03 | 25653.46 | 05-JUL-11:00 | 0.00 |
August | 0.541658E+11 | 0.132496E+11 | 423.98 | 0.381069E+11 | 0.160589E+11 | 0.00 | 1.00 | 01-AUG-07:30 | 0.00 | 01-AUG-00:10 | 127039.91 | 04-AUG-06:03 | 78406.60 | 04-AUG-15:20 | 90430.33 | 04-AUG-07:10 | 28791.38 | 04-AUG-15:30 | 0.00 |
September | 0.218106E+11 | 0.556588E+10 | 234.93 | 0.191698E+11 | 0.264085E+10 | 0.00 | 1.00 | 01-SEP-12:05 | 0.00 | 01-SEP-00:10 | 83202.05 | 11-SEP-10:00 | 71427.04 | 07-SEP-15:50 | 31723.62 | 11-SEP-10:00 | 21779.11 | 06-SEP-14:00 | 0.00 |
October | 0.116042E+10 | 0.315533E+09 | 48.19 | 0.951269E+09 | 0.209152E+09 | 0.00 | 0.78 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 27366.14 | 20-OCT-15:00 | 27366.14 | 20-OCT-15:00 | 4179.08 | 02-OCT-15:00 | 6652.26 | 20-OCT-15:00 | 0.00 |
November | 37655492.14 | 10913316.35 | 4.50 | 31975010.38 | 5680481.77 | 0.00 | 0.12 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 3503.77 | 03-NOV-14:00 | 3120.22 | 03-NOV-14:30 | 622.95 | 03-NOV-13:30 | 1009.56 | 03-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.201730E+12 | 0.498134E+11 | 1834.39 | 0.147728E+12 | 0.540019E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.594596E+11 | 0.143807E+11 | 436.36 | 0.402734E+11 | 0.191862E+11 | 0.00 | 1.00 | 0.00 | 127039.91 | 81654.29 | 90430.33 | 28791.38 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 363.15 | 0.00 | 363.15 | 1.99 | 2877.13 | 0.00 | 0.00 | 0.00 |
February | 460.40 | 0.00 | 460.40 | 32.12 | 2297.59 | 0.00 | 0.00 | 0.00 |
March | 690.00 | 0.00 | 690.00 | 232.10 | 1451.97 | 0.00 | 0.00 | 0.00 |
April | 796.55 | 3.92 | 792.63 | 459.03 | 997.99 | 0.00 | 0.00 | 0.00 |
May | 1038.72 | 39.04 | 999.68 | 922.89 | 596.55 | 0.00 | 0.00 | 0.00 |
June | 1214.03 | 110.19 | 1103.84 | 1389.41 | 413.07 | 0.00 | 0.00 | 0.00 |
July | 1138.57 | 76.16 | 1062.41 | 1359.37 | 362.78 | 0.00 | 0.00 | 0.00 |
August | 953.32 | 16.90 | 936.42 | 1133.56 | 423.73 | 0.00 | 0.00 | 0.00 |
September | 730.92 | 0.18 | 730.74 | 689.50 | 728.50 | 0.00 | 0.00 | 0.00 |
October | 543.45 | 0.00 | 543.45 | 275.26 | 1084.53 | 0.00 | 0.00 | 0.00 |
November | 380.15 | 0.00 | 380.15 | 69.86 | 1696.28 | 0.00 | 0.00 | 0.00 |
December | 246.59 | 0.00 | 246.59 | 0.73 | 2520.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 714.32 | 20.61 | 693.71 | 550.24 | 1282.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.59 | 0.00 | 246.59 | 0.73 | 362.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1214.03 | 110.19 | 1103.84 | 1389.41 | 2877.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.77 | 213.48 | 305.30 | 230.62 | 1731.75 | 0.00 | 0.00 | 0.00 |
February | 687.63 | 302.36 | 385.27 | 405.52 | 1361.32 | 0.00 | 0.00 | 0.00 |
March | 934.28 | 370.84 | 563.44 | 731.55 | 892.82 | 0.00 | 0.00 | 0.00 |
April | 1147.21 | 502.40 | 644.81 | 1108.45 | 645.33 | 0.00 | 0.00 | 0.00 |
May | 1440.80 | 629.56 | 811.23 | 1614.20 | 406.59 | 0.00 | 0.00 | 0.00 |
June | 1585.56 | 690.49 | 895.07 | 1975.75 | 280.13 | 0.00 | 0.00 | 0.00 |
July | 1602.59 | 739.47 | 863.12 | 2044.30 | 245.69 | 0.00 | 0.00 | 0.00 |
August | 1350.96 | 582.43 | 768.53 | 1727.00 | 284.60 | 0.00 | 0.00 | 0.00 |
September | 1204.93 | 569.39 | 635.54 | 1424.82 | 473.72 | 0.00 | 0.00 | 0.00 |
October | 767.87 | 320.73 | 447.13 | 695.35 | 685.23 | 0.00 | 0.00 | 0.00 |
November | 453.05 | 147.16 | 305.89 | 249.07 | 1053.39 | 0.00 | 0.00 | 0.00 |
December | 350.93 | 150.70 | 200.23 | 161.89 | 1554.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1005.28 | 435.54 | 569.74 | 1034.11 | 798.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 350.93 | 147.16 | 200.23 | 161.89 | 245.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1602.59 | 739.47 | 895.07 | 2044.30 | 1731.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2258.40 | 1545.48 | 712.93 | 2021.00 | 2348.54 | 0.00 | 0.00 | 0.00 |
February | 2419.84 | 1634.86 | 784.98 | 2259.08 | 1882.21 | 0.00 | 0.00 | 0.00 |
March | 2105.80 | 1108.85 | 996.96 | 2064.43 | 1359.74 | 0.00 | 0.00 | 0.00 |
April | 1897.19 | 886.97 | 1010.22 | 2066.39 | 1024.08 | 0.00 | 0.00 | 0.00 |
May | 1571.76 | 426.12 | 1145.63 | 1807.65 | 654.64 | 0.00 | 0.00 | 0.00 |
June | 1525.94 | 310.69 | 1215.25 | 1952.47 | 444.72 | 0.00 | 0.00 | 0.00 |
July | 1615.31 | 407.02 | 1208.30 | 2158.04 | 388.67 | 0.00 | 0.00 | 0.00 |
August | 1819.92 | 652.67 | 1167.25 | 2471.75 | 455.82 | 0.00 | 0.00 | 0.00 |
September | 2205.36 | 1162.04 | 1043.32 | 2798.51 | 743.95 | 0.00 | 0.00 | 0.00 |
October | 2302.86 | 1444.72 | 858.14 | 2572.77 | 1053.88 | 0.00 | 0.00 | 0.00 |
November | 1737.50 | 1087.71 | 649.79 | 1656.94 | 1512.17 | 0.00 | 0.00 | 0.00 |
December | 1852.79 | 1403.47 | 449.32 | 1781.27 | 2168.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1939.91 | 1002.29 | 937.62 | 2133.34 | 1166.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1525.94 | 310.69 | 449.32 | 1656.94 | 388.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2419.84 | 1634.86 | 1215.25 | 2798.51 | 2348.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 514.49 | 208.17 | 306.32 | 238.59 | 1773.48 | 0.00 | 0.00 | 0.00 |
February | 754.42 | 371.75 | 382.66 | 499.56 | 1411.32 | 0.00 | 0.00 | 0.00 |
March | 900.62 | 335.08 | 565.54 | 692.63 | 922.06 | 0.00 | 0.00 | 0.00 |
April | 1313.73 | 649.62 | 664.11 | 1351.77 | 671.56 | 0.00 | 0.00 | 0.00 |
May | 1317.53 | 526.32 | 791.21 | 1480.89 | 428.03 | 0.00 | 0.00 | 0.00 |
June | 1545.97 | 669.98 | 875.98 | 1937.52 | 299.97 | 0.00 | 0.00 | 0.00 |
July | 1659.90 | 788.48 | 871.42 | 2140.15 | 267.93 | 0.00 | 0.00 | 0.00 |
August | 1451.17 | 665.99 | 785.18 | 1882.10 | 305.90 | 0.00 | 0.00 | 0.00 |
September | 1174.68 | 557.56 | 617.12 | 1395.54 | 494.31 | 0.00 | 0.00 | 0.00 |
October | 818.57 | 363.93 | 454.64 | 777.52 | 714.47 | 0.00 | 0.00 | 0.00 |
November | 489.97 | 181.19 | 308.78 | 312.02 | 1078.19 | 0.00 | 0.00 | 0.00 |
December | 376.81 | 177.63 | 199.18 | 208.99 | 1587.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1027.58 | 458.06 | 569.51 | 1079.29 | 826.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 376.81 | 177.63 | 199.18 | 208.99 | 267.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1659.90 | 788.48 | 875.98 | 2140.15 | 1773.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.04 | 0.00 | 121.04 | 0.71 | 961.78 | 0.00 | 0.00 | 0.00 |
February | 153.46 | 0.00 | 153.46 | 10.79 | 771.54 | 0.00 | 0.00 | 0.00 |
March | 229.99 | 0.00 | 229.99 | 82.65 | 486.74 | 0.00 | 0.00 | 0.00 |
April | 265.51 | 1.31 | 264.20 | 164.53 | 327.48 | 0.00 | 0.00 | 0.00 |
May | 346.22 | 13.01 | 333.21 | 325.04 | 189.69 | 0.00 | 0.00 | 0.00 |
June | 404.66 | 36.73 | 367.93 | 473.87 | 134.92 | 0.00 | 0.00 | 0.00 |
July | 379.50 | 25.38 | 354.12 | 461.39 | 119.61 | 0.00 | 0.00 | 0.00 |
August | 317.76 | 5.63 | 312.13 | 381.12 | 144.65 | 0.00 | 0.00 | 0.00 |
September | 243.63 | 0.06 | 243.57 | 227.73 | 259.25 | 0.00 | 0.00 | 0.00 |
October | 181.14 | 0.00 | 181.14 | 84.27 | 396.13 | 0.00 | 0.00 | 0.00 |
November | 126.71 | 0.00 | 126.71 | 20.23 | 600.63 | 0.00 | 0.00 | 0.00 |
December | 82.19 | 0.00 | 82.19 | 0.09 | 862.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 238.10 | 6.87 | 231.23 | 187.09 | 436.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.19 | 0.00 | 82.19 | 0.09 | 119.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 404.66 | 36.73 | 367.93 | 473.87 | 961.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.05 | 0.00 | 121.05 | 0.71 | 961.84 | 0.00 | 0.00 | 0.00 |
February | 153.47 | 0.00 | 153.47 | 10.79 | 771.60 | 0.00 | 0.00 | 0.00 |
March | 230.00 | 0.00 | 230.00 | 82.65 | 486.77 | 0.00 | 0.00 | 0.00 |
April | 265.52 | 1.31 | 264.21 | 164.54 | 327.50 | 0.00 | 0.00 | 0.00 |
May | 346.24 | 13.01 | 333.22 | 325.05 | 189.70 | 0.00 | 0.00 | 0.00 |
June | 404.67 | 36.73 | 367.94 | 473.89 | 134.93 | 0.00 | 0.00 | 0.00 |
July | 379.52 | 25.39 | 354.13 | 461.41 | 119.62 | 0.00 | 0.00 | 0.00 |
August | 317.77 | 5.63 | 312.14 | 381.13 | 144.66 | 0.00 | 0.00 | 0.00 |
September | 243.64 | 0.06 | 243.58 | 227.74 | 259.26 | 0.00 | 0.00 | 0.00 |
October | 181.15 | 0.00 | 181.15 | 84.27 | 396.16 | 0.00 | 0.00 | 0.00 |
November | 126.72 | 0.00 | 126.72 | 20.23 | 600.67 | 0.00 | 0.00 | 0.00 |
December | 82.20 | 0.00 | 82.20 | 0.09 | 862.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 238.11 | 6.87 | 231.24 | 187.09 | 436.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.20 | 0.00 | 82.20 | 0.09 | 119.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 404.67 | 36.73 | 367.94 | 473.89 | 961.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.05 | 0.00 | 121.05 | 0.71 | 961.84 | 0.00 | 0.00 | 0.00 |
February | 153.47 | 0.00 | 153.47 | 10.79 | 771.60 | 0.00 | 0.00 | 0.00 |
March | 230.00 | 0.00 | 230.00 | 82.65 | 486.77 | 0.00 | 0.00 | 0.00 |
April | 265.52 | 1.31 | 264.21 | 164.54 | 327.50 | 0.00 | 0.00 | 0.00 |
May | 346.24 | 13.01 | 333.22 | 325.05 | 189.70 | 0.00 | 0.00 | 0.00 |
June | 404.67 | 36.73 | 367.94 | 473.89 | 134.93 | 0.00 | 0.00 | 0.00 |
July | 379.52 | 25.39 | 354.13 | 461.41 | 119.62 | 0.00 | 0.00 | 0.00 |
August | 317.77 | 5.63 | 312.14 | 381.13 | 144.66 | 0.00 | 0.00 | 0.00 |
September | 243.64 | 0.06 | 243.58 | 227.74 | 259.26 | 0.00 | 0.00 | 0.00 |
October | 181.15 | 0.00 | 181.15 | 84.27 | 396.16 | 0.00 | 0.00 | 0.00 |
November | 126.72 | 0.00 | 126.72 | 20.23 | 600.67 | 0.00 | 0.00 | 0.00 |
December | 82.20 | 0.00 | 82.20 | 0.09 | 862.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 238.11 | 6.87 | 231.24 | 187.09 | 436.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.20 | 0.00 | 82.20 | 0.09 | 119.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 404.67 | 36.73 | 367.94 | 473.89 | 961.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 499.03 | 205.35 | 293.68 | 224.89 | 1679.02 | 0.00 | 0.00 | 0.00 |
February | 661.47 | 290.86 | 370.61 | 394.18 | 1332.35 | 0.00 | 0.00 | 0.00 |
March | 898.73 | 356.73 | 542.00 | 717.73 | 873.58 | 0.00 | 0.00 | 0.00 |
April | 1103.55 | 483.28 | 620.27 | 1089.53 | 624.57 | 0.00 | 0.00 | 0.00 |
May | 1385.98 | 605.61 | 780.37 | 1578.24 | 389.23 | 0.00 | 0.00 | 0.00 |
June | 1525.23 | 664.21 | 861.02 | 1918.28 | 273.73 | 0.00 | 0.00 | 0.00 |
July | 1541.62 | 711.33 | 830.28 | 1980.28 | 242.99 | 0.00 | 0.00 | 0.00 |
August | 1299.55 | 560.26 | 739.29 | 1668.83 | 287.96 | 0.00 | 0.00 | 0.00 |
September | 1159.08 | 547.73 | 611.36 | 1367.43 | 496.82 | 0.00 | 0.00 | 0.00 |
October | 738.65 | 308.53 | 430.12 | 647.74 | 736.98 | 0.00 | 0.00 | 0.00 |
November | 435.81 | 141.56 | 294.25 | 229.13 | 1083.14 | 0.00 | 0.00 | 0.00 |
December | 337.58 | 144.97 | 192.62 | 154.40 | 1539.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 967.03 | 418.97 | 548.06 | 1000.83 | 794.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 337.58 | 141.56 | 192.62 | 154.40 | 242.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1541.62 | 711.33 | 861.02 | 1980.28 | 1679.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.73 | 8.12 | 11.61 | 8.89 | 66.39 | 0.00 | 0.00 | 0.00 |
February | 26.15 | 11.50 | 14.65 | 15.59 | 52.68 | 0.00 | 0.00 | 0.00 |
March | 35.53 | 14.10 | 21.43 | 28.38 | 34.54 | 0.00 | 0.00 | 0.00 |
April | 43.63 | 19.11 | 24.53 | 43.08 | 24.69 | 0.00 | 0.00 | 0.00 |
May | 54.80 | 23.95 | 30.86 | 62.40 | 15.39 | 0.00 | 0.00 | 0.00 |
June | 60.31 | 26.26 | 34.04 | 75.85 | 10.82 | 0.00 | 0.00 | 0.00 |
July | 60.95 | 28.13 | 32.83 | 78.30 | 9.61 | 0.00 | 0.00 | 0.00 |
August | 51.38 | 22.15 | 29.23 | 65.98 | 11.39 | 0.00 | 0.00 | 0.00 |
September | 45.83 | 21.66 | 24.17 | 54.07 | 19.64 | 0.00 | 0.00 | 0.00 |
October | 29.21 | 12.20 | 17.01 | 25.61 | 29.14 | 0.00 | 0.00 | 0.00 |
November | 17.23 | 5.60 | 11.63 | 9.06 | 42.83 | 0.00 | 0.00 | 0.00 |
December | 13.35 | 5.73 | 7.62 | 6.10 | 60.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.24 | 16.57 | 21.67 | 39.57 | 31.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.35 | 5.60 | 7.62 | 6.10 | 9.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.95 | 28.13 | 34.04 | 78.30 | 66.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 752.79 | 515.15 | 237.64 | 689.98 | 779.77 | 0.00 | 0.00 | 0.00 |
February | 806.60 | 544.94 | 261.66 | 768.84 | 639.02 | 0.00 | 0.00 | 0.00 |
March | 701.92 | 369.61 | 332.31 | 704.31 | 460.43 | 0.00 | 0.00 | 0.00 |
April | 632.39 | 295.65 | 336.74 | 704.82 | 342.61 | 0.00 | 0.00 | 0.00 |
May | 523.91 | 142.04 | 381.87 | 621.81 | 211.44 | 0.00 | 0.00 | 0.00 |
June | 508.64 | 103.56 | 405.08 | 663.87 | 146.11 | 0.00 | 0.00 | 0.00 |
July | 538.43 | 135.67 | 402.76 | 728.37 | 130.84 | 0.00 | 0.00 | 0.00 |
August | 606.63 | 217.55 | 389.08 | 829.78 | 160.01 | 0.00 | 0.00 | 0.00 |
September | 735.11 | 387.34 | 347.77 | 934.98 | 270.11 | 0.00 | 0.00 | 0.00 |
October | 767.61 | 481.56 | 286.04 | 854.94 | 395.03 | 0.00 | 0.00 | 0.00 |
November | 579.16 | 362.56 | 216.59 | 552.09 | 540.14 | 0.00 | 0.00 | 0.00 |
December | 617.59 | 467.81 | 149.77 | 599.99 | 740.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 646.63 | 334.09 | 312.54 | 720.84 | 400.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 508.64 | 103.56 | 149.77 | 552.09 | 130.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 806.60 | 544.94 | 405.08 | 934.98 | 779.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 752.79 | 515.15 | 237.64 | 689.98 | 779.77 | 0.00 | 0.00 | 0.00 |
February | 806.60 | 544.94 | 261.66 | 768.84 | 639.02 | 0.00 | 0.00 | 0.00 |
March | 701.92 | 369.61 | 332.31 | 704.31 | 460.43 | 0.00 | 0.00 | 0.00 |
April | 632.39 | 295.65 | 336.74 | 704.82 | 342.61 | 0.00 | 0.00 | 0.00 |
May | 523.91 | 142.04 | 381.87 | 621.81 | 211.44 | 0.00 | 0.00 | 0.00 |
June | 508.64 | 103.56 | 405.08 | 663.87 | 146.11 | 0.00 | 0.00 | 0.00 |
July | 538.43 | 135.67 | 402.76 | 728.37 | 130.84 | 0.00 | 0.00 | 0.00 |
August | 606.63 | 217.55 | 389.08 | 829.78 | 160.01 | 0.00 | 0.00 | 0.00 |
September | 735.11 | 387.34 | 347.77 | 934.98 | 270.11 | 0.00 | 0.00 | 0.00 |
October | 767.61 | 481.56 | 286.04 | 854.94 | 395.03 | 0.00 | 0.00 | 0.00 |
November | 579.16 | 362.56 | 216.59 | 552.09 | 540.14 | 0.00 | 0.00 | 0.00 |
December | 617.59 | 467.81 | 149.77 | 599.99 | 740.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 646.63 | 334.09 | 312.54 | 720.84 | 400.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 508.64 | 103.56 | 149.77 | 552.09 | 130.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 806.60 | 544.94 | 405.08 | 934.98 | 779.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 752.74 | 515.12 | 237.62 | 689.93 | 779.72 | 0.00 | 0.00 | 0.00 |
February | 806.55 | 544.91 | 261.64 | 768.79 | 638.98 | 0.00 | 0.00 | 0.00 |
March | 701.88 | 369.58 | 332.29 | 704.26 | 460.40 | 0.00 | 0.00 | 0.00 |
April | 632.35 | 295.63 | 336.71 | 704.77 | 342.58 | 0.00 | 0.00 | 0.00 |
May | 523.88 | 142.03 | 381.85 | 621.77 | 211.43 | 0.00 | 0.00 | 0.00 |
June | 508.61 | 103.55 | 405.05 | 663.83 | 146.10 | 0.00 | 0.00 | 0.00 |
July | 538.40 | 135.66 | 402.74 | 728.33 | 130.83 | 0.00 | 0.00 | 0.00 |
August | 606.59 | 217.54 | 389.06 | 829.73 | 160.00 | 0.00 | 0.00 | 0.00 |
September | 735.06 | 387.32 | 347.75 | 934.92 | 270.09 | 0.00 | 0.00 | 0.00 |
October | 767.56 | 481.53 | 286.02 | 854.89 | 395.01 | 0.00 | 0.00 | 0.00 |
November | 579.12 | 362.54 | 216.58 | 552.06 | 540.10 | 0.00 | 0.00 | 0.00 |
December | 617.55 | 467.78 | 149.76 | 599.95 | 740.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 646.59 | 334.07 | 312.52 | 720.79 | 400.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 508.61 | 103.55 | 149.76 | 552.06 | 130.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 806.55 | 544.91 | 405.05 | 934.92 | 779.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 494.92 | 200.25 | 294.67 | 235.17 | 1717.88 | 0.00 | 0.00 | 0.00 |
February | 725.71 | 357.61 | 368.10 | 489.74 | 1379.53 | 0.00 | 0.00 | 0.00 |
March | 866.35 | 322.33 | 544.02 | 683.92 | 902.01 | 0.00 | 0.00 | 0.00 |
April | 1263.75 | 624.90 | 638.85 | 1324.05 | 656.96 | 0.00 | 0.00 | 0.00 |
May | 1267.40 | 506.30 | 761.11 | 1451.46 | 409.55 | 0.00 | 0.00 | 0.00 |
June | 1487.15 | 644.49 | 842.66 | 1881.98 | 293.91 | 0.00 | 0.00 | 0.00 |
July | 1596.74 | 758.48 | 838.27 | 2071.95 | 268.77 | 0.00 | 0.00 | 0.00 |
August | 1395.96 | 640.65 | 755.31 | 1818.91 | 313.14 | 0.00 | 0.00 | 0.00 |
September | 1129.99 | 536.35 | 593.64 | 1339.24 | 519.36 | 0.00 | 0.00 | 0.00 |
October | 787.42 | 350.08 | 437.34 | 733.09 | 768.15 | 0.00 | 0.00 | 0.00 |
November | 471.32 | 174.29 | 297.03 | 292.52 | 1109.03 | 0.00 | 0.00 | 0.00 |
December | 362.47 | 170.87 | 191.60 | 202.39 | 1571.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 988.48 | 440.63 | 547.85 | 1046.44 | 823.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 362.47 | 170.87 | 191.60 | 202.39 | 268.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1596.74 | 758.48 | 842.66 | 2071.95 | 1717.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.57 | 7.92 | 11.65 | 9.30 | 67.92 | 0.00 | 0.00 | 0.00 |
February | 28.69 | 14.14 | 14.55 | 19.36 | 54.55 | 0.00 | 0.00 | 0.00 |
March | 34.25 | 12.74 | 21.51 | 27.04 | 35.66 | 0.00 | 0.00 | 0.00 |
April | 49.97 | 24.71 | 25.26 | 52.35 | 25.98 | 0.00 | 0.00 | 0.00 |
May | 50.11 | 20.02 | 30.09 | 57.39 | 16.19 | 0.00 | 0.00 | 0.00 |
June | 58.80 | 25.48 | 33.32 | 74.41 | 11.62 | 0.00 | 0.00 | 0.00 |
July | 63.13 | 29.99 | 33.14 | 81.92 | 10.63 | 0.00 | 0.00 | 0.00 |
August | 55.19 | 25.33 | 29.86 | 71.92 | 12.38 | 0.00 | 0.00 | 0.00 |
September | 44.68 | 21.21 | 23.47 | 52.95 | 20.53 | 0.00 | 0.00 | 0.00 |
October | 31.13 | 13.84 | 17.29 | 28.99 | 30.37 | 0.00 | 0.00 | 0.00 |
November | 18.64 | 6.89 | 11.74 | 11.57 | 43.85 | 0.00 | 0.00 | 0.00 |
December | 14.33 | 6.76 | 7.58 | 8.00 | 62.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.08 | 17.42 | 21.66 | 41.38 | 32.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.33 | 6.76 | 7.58 | 8.00 | 10.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.13 | 29.99 | 33.32 | 81.92 | 67.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 363.15 | 0.00 | 363.15 | 1.67 | 2927.15 | 0.00 | 0.00 | 0.00 |
February | 460.40 | 0.00 | 460.40 | 28.97 | 2362.63 | 0.00 | 0.00 | 0.00 |
March | 690.00 | 0.00 | 690.00 | 221.73 | 1517.02 | 0.00 | 0.00 | 0.00 |
April | 796.55 | 3.92 | 792.63 | 448.07 | 1058.96 | 0.00 | 0.00 | 0.00 |
May | 1038.72 | 39.04 | 999.68 | 912.26 | 624.33 | 0.00 | 0.00 | 0.00 |
June | 1214.03 | 110.19 | 1103.84 | 1385.30 | 429.95 | 0.00 | 0.00 | 0.00 |
July | 1138.57 | 76.16 | 1062.41 | 1359.14 | 374.48 | 0.00 | 0.00 | 0.00 |
August | 953.32 | 16.90 | 936.42 | 1130.36 | 441.15 | 0.00 | 0.00 | 0.00 |
September | 730.92 | 0.18 | 730.74 | 676.30 | 775.46 | 0.00 | 0.00 | 0.00 |
October | 543.45 | 0.00 | 543.45 | 250.43 | 1173.55 | 0.00 | 0.00 | 0.00 |
November | 380.15 | 0.00 | 380.15 | 59.44 | 1784.59 | 0.00 | 0.00 | 0.00 |
December | 246.59 | 0.00 | 246.59 | 0.21 | 2592.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 714.32 | 20.61 | 693.71 | 542.56 | 1333.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.59 | 0.00 | 246.59 | 0.21 | 374.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1214.03 | 110.19 | 1103.84 | 1385.30 | 2927.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.77 | 213.48 | 305.30 | 228.36 | 1760.19 | 0.00 | 0.00 | 0.00 |
February | 687.63 | 302.36 | 385.27 | 399.36 | 1400.75 | 0.00 | 0.00 | 0.00 |
March | 934.28 | 370.84 | 563.44 | 719.03 | 933.80 | 0.00 | 0.00 | 0.00 |
April | 1147.21 | 502.40 | 644.81 | 1098.25 | 682.68 | 0.00 | 0.00 | 0.00 |
May | 1440.80 | 629.56 | 811.23 | 1608.34 | 422.97 | 0.00 | 0.00 | 0.00 |
June | 1585.56 | 690.49 | 895.07 | 1972.17 | 291.09 | 0.00 | 0.00 | 0.00 |
July | 1602.59 | 739.47 | 863.12 | 2043.20 | 253.10 | 0.00 | 0.00 | 0.00 |
August | 1350.96 | 582.43 | 768.53 | 1723.90 | 295.24 | 0.00 | 0.00 | 0.00 |
September | 1204.93 | 569.39 | 635.54 | 1415.49 | 500.92 | 0.00 | 0.00 | 0.00 |
October | 767.87 | 320.73 | 447.13 | 671.60 | 739.67 | 0.00 | 0.00 | 0.00 |
November | 453.05 | 147.16 | 305.89 | 236.91 | 1106.99 | 0.00 | 0.00 | 0.00 |
December | 350.93 | 150.70 | 200.23 | 158.51 | 1596.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1005.28 | 435.54 | 569.74 | 1026.32 | 829.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 350.93 | 147.16 | 200.23 | 158.51 | 253.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1602.59 | 739.47 | 895.07 | 2043.20 | 1760.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2258.40 | 1545.48 | 712.93 | 2011.90 | 2399.35 | 0.00 | 0.00 | 0.00 |
February | 2419.84 | 1634.86 | 784.98 | 2244.98 | 1947.89 | 0.00 | 0.00 | 0.00 |
March | 2105.80 | 1108.85 | 996.96 | 2050.76 | 1423.37 | 0.00 | 0.00 | 0.00 |
April | 1897.19 | 886.97 | 1010.22 | 2057.87 | 1083.61 | 0.00 | 0.00 | 0.00 |
May | 1571.76 | 426.12 | 1145.63 | 1804.03 | 683.98 | 0.00 | 0.00 | 0.00 |
June | 1525.94 | 310.69 | 1215.25 | 1952.40 | 463.77 | 0.00 | 0.00 | 0.00 |
July | 1615.31 | 407.02 | 1208.30 | 2160.89 | 401.75 | 0.00 | 0.00 | 0.00 |
August | 1819.92 | 652.67 | 1167.25 | 2473.30 | 474.23 | 0.00 | 0.00 | 0.00 |
September | 2205.36 | 1162.04 | 1043.32 | 2790.50 | 786.70 | 0.00 | 0.00 | 0.00 |
October | 2302.86 | 1444.72 | 858.14 | 2547.74 | 1134.39 | 0.00 | 0.00 | 0.00 |
November | 1737.50 | 1087.71 | 649.79 | 1634.62 | 1593.64 | 0.00 | 0.00 | 0.00 |
December | 1852.79 | 1403.47 | 449.32 | 1769.48 | 2239.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1939.91 | 1002.29 | 937.62 | 2124.06 | 1215.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1525.94 | 310.69 | 449.32 | 1634.62 | 401.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2419.84 | 1634.86 | 1215.25 | 2790.50 | 2399.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 514.49 | 208.17 | 306.32 | 237.53 | 1805.18 | 0.00 | 0.00 | 0.00 |
February | 754.42 | 371.75 | 382.66 | 495.95 | 1453.03 | 0.00 | 0.00 | 0.00 |
March | 900.62 | 335.08 | 565.54 | 685.39 | 964.46 | 0.00 | 0.00 | 0.00 |
April | 1313.73 | 649.62 | 664.11 | 1346.47 | 711.50 | 0.00 | 0.00 | 0.00 |
May | 1317.53 | 526.32 | 791.21 | 1477.87 | 447.65 | 0.00 | 0.00 | 0.00 |
June | 1545.97 | 669.98 | 875.98 | 1937.78 | 312.56 | 0.00 | 0.00 | 0.00 |
July | 1659.90 | 788.48 | 871.42 | 2142.54 | 276.84 | 0.00 | 0.00 | 0.00 |
August | 1451.17 | 665.99 | 785.18 | 1883.06 | 318.08 | 0.00 | 0.00 | 0.00 |
September | 1174.68 | 557.56 | 617.12 | 1388.72 | 523.91 | 0.00 | 0.00 | 0.00 |
October | 818.57 | 363.93 | 454.64 | 761.35 | 771.48 | 0.00 | 0.00 | 0.00 |
November | 489.97 | 181.19 | 308.78 | 302.45 | 1133.79 | 0.00 | 0.00 | 0.00 |
December | 376.81 | 177.63 | 199.18 | 206.38 | 1633.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1027.58 | 458.06 | 569.51 | 1074.98 | 859.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 376.81 | 177.63 | 199.18 | 206.38 | 276.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1659.90 | 788.48 | 875.98 | 2142.54 | 1805.18 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.972653E+09 | 0.00 | 0.972653E+09 | 5335717.01 | 0.770610E+10 |
February | 0.111380E+10 | 0.00 | 0.111380E+10 | 77713618.58 | 0.555833E+10 |
March | 0.184809E+10 | 0.00 | 0.184809E+10 | 0.621668E+09 | 0.388897E+10 |
April | 0.206467E+10 | 10172528.45 | 0.205450E+10 | 0.118980E+10 | 0.258680E+10 |
May | 0.278211E+10 | 0.104573E+09 | 0.267754E+10 | 0.247188E+10 | 0.159779E+10 |
June | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.360135E+10 | 0.107066E+10 |
July | 0.304954E+10 | 0.203981E+09 | 0.284556E+10 | 0.364093E+10 | 0.971665E+09 |
August | 0.255336E+10 | 45252673.04 | 0.250811E+10 | 0.303613E+10 | 0.113492E+10 |
September | 0.189454E+10 | 469762.04 | 0.189407E+10 | 0.178720E+10 | 0.188827E+10 |
October | 0.145558E+10 | 0.00 | 0.145558E+10 | 0.737256E+09 | 0.290479E+10 |
November | 0.985350E+09 | 0.00 | 0.985350E+09 | 0.181066E+09 | 0.439675E+10 |
December | 0.660462E+09 | 0.00 | 0.660462E+09 | 1944454.54 | 0.675121E+10 |
Annual Sum or Average | 0.225269E+11 | 0.650058E+09 | 0.218769E+11 | 0.173523E+11 | 0.404563E+11 |
Minimum of Months | 0.660462E+09 | 0.00 | 0.660462E+09 | 1944454.54 | 0.971665E+09 |
Maximum of Months | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.364093E+10 | 0.770610E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138948E+10 | 0.571775E+09 | 0.817705E+09 | 0.617701E+09 | 0.463832E+10 |
February | 0.166351E+10 | 0.731481E+09 | 0.932034E+09 | 0.981029E+09 | 0.329330E+10 |
March | 0.250237E+10 | 0.993267E+09 | 0.150911E+10 | 0.195937E+10 | 0.239133E+10 |
April | 0.297356E+10 | 0.130222E+10 | 0.167134E+10 | 0.287311E+10 | 0.167270E+10 |
May | 0.385903E+10 | 0.168622E+10 | 0.217281E+10 | 0.432346E+10 | 0.108901E+10 |
June | 0.410977E+10 | 0.178974E+10 | 0.232003E+10 | 0.512114E+10 | 0.726090E+09 |
July | 0.429239E+10 | 0.198061E+10 | 0.231178E+10 | 0.547545E+10 | 0.658056E+09 |
August | 0.361840E+10 | 0.155997E+10 | 0.205843E+10 | 0.462560E+10 | 0.762265E+09 |
September | 0.312318E+10 | 0.147587E+10 | 0.164732E+10 | 0.369314E+10 | 0.122788E+10 |
October | 0.205665E+10 | 0.859048E+09 | 0.119760E+10 | 0.186243E+10 | 0.183533E+10 |
November | 0.117430E+10 | 0.381434E+09 | 0.792865E+09 | 0.645582E+09 | 0.273039E+10 |
December | 0.939944E+09 | 0.403635E+09 | 0.536309E+09 | 0.433602E+09 | 0.416327E+10 |
Annual Sum or Average | 0.317026E+11 | 0.137353E+11 | 0.179673E+11 | 0.326116E+11 | 0.251879E+11 |
Minimum of Months | 0.939944E+09 | 0.381434E+09 | 0.536309E+09 | 0.433602E+09 | 0.658056E+09 |
Maximum of Months | 0.429239E+10 | 0.198061E+10 | 0.232003E+10 | 0.547545E+10 | 0.463832E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.604891E+10 | 0.413940E+10 | 0.190951E+10 | 0.541305E+10 | 0.629033E+10 |
February | 0.585407E+10 | 0.395506E+10 | 0.189902E+10 | 0.546518E+10 | 0.455345E+10 |
March | 0.564018E+10 | 0.296993E+10 | 0.267025E+10 | 0.552937E+10 | 0.364192E+10 |
April | 0.491751E+10 | 0.229903E+10 | 0.261848E+10 | 0.535608E+10 | 0.265442E+10 |
May | 0.420979E+10 | 0.114133E+10 | 0.306846E+10 | 0.484160E+10 | 0.175338E+10 |
June | 0.395523E+10 | 0.805306E+09 | 0.314992E+10 | 0.506079E+10 | 0.115272E+10 |
July | 0.432645E+10 | 0.109015E+10 | 0.323630E+10 | 0.578008E+10 | 0.104100E+10 |
August | 0.487447E+10 | 0.174810E+10 | 0.312637E+10 | 0.662033E+10 | 0.122086E+10 |
September | 0.571629E+10 | 0.301201E+10 | 0.270427E+10 | 0.725373E+10 | 0.192833E+10 |
October | 0.616797E+10 | 0.386954E+10 | 0.229844E+10 | 0.689090E+10 | 0.282271E+10 |
November | 0.450361E+10 | 0.281934E+10 | 0.168426E+10 | 0.429480E+10 | 0.391954E+10 |
December | 0.496252E+10 | 0.375905E+10 | 0.120347E+10 | 0.477095E+10 | 0.580906E+10 |
Annual Sum or Average | 0.611770E+11 | 0.316083E+11 | 0.295687E+11 | 0.672769E+11 | 0.367877E+11 |
Minimum of Months | 0.395523E+10 | 0.805306E+09 | 0.120347E+10 | 0.429480E+10 | 0.104100E+10 |
Maximum of Months | 0.616797E+10 | 0.413940E+10 | 0.323630E+10 | 0.725373E+10 | 0.629033E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137802E+10 | 0.557565E+09 | 0.820458E+09 | 0.639031E+09 | 0.475010E+10 |
February | 0.182508E+10 | 0.899346E+09 | 0.925736E+09 | 0.120855E+10 | 0.341427E+10 |
March | 0.241221E+10 | 0.897475E+09 | 0.151474E+10 | 0.185514E+10 | 0.246964E+10 |
April | 0.340519E+10 | 0.168381E+10 | 0.172138E+10 | 0.350379E+10 | 0.174067E+10 |
May | 0.352888E+10 | 0.140970E+10 | 0.211917E+10 | 0.396642E+10 | 0.114643E+10 |
June | 0.400715E+10 | 0.173660E+10 | 0.227055E+10 | 0.502204E+10 | 0.777535E+09 |
July | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.573217E+10 | 0.717626E+09 |
August | 0.388681E+10 | 0.178379E+10 | 0.210302E+10 | 0.504101E+10 | 0.819330E+09 |
September | 0.304477E+10 | 0.144521E+10 | 0.159957E+10 | 0.361724E+10 | 0.128124E+10 |
October | 0.219245E+10 | 0.974738E+09 | 0.121771E+10 | 0.208250E+10 | 0.191365E+10 |
November | 0.126999E+10 | 0.469642E+09 | 0.800349E+09 | 0.808746E+09 | 0.279466E+10 |
December | 0.100925E+10 | 0.475773E+09 | 0.533472E+09 | 0.559770E+09 | 0.425272E+10 |
Annual Sum or Average | 0.324057E+11 | 0.144455E+11 | 0.179602E+11 | 0.340364E+11 | 0.260779E+11 |
Minimum of Months | 0.100925E+10 | 0.469642E+09 | 0.533472E+09 | 0.559770E+09 | 0.717626E+09 |
Maximum of Months | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.573217E+10 | 0.475010E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.324202E+09 | 0.00 | 0.324202E+09 | 1891925.52 | 0.257603E+10 |
February | 0.371248E+09 | 0.00 | 0.371248E+09 | 26103457.18 | 0.186652E+10 |
March | 0.616000E+09 | 0.00 | 0.616000E+09 | 0.221370E+09 | 0.130368E+10 |
April | 0.688190E+09 | 3390682.39 | 0.684800E+09 | 0.426467E+09 | 0.848827E+09 |
May | 0.927327E+09 | 34856080.88 | 0.892471E+09 | 0.870588E+09 | 0.508074E+09 |
June | 0.104887E+10 | 95198633.35 | 0.953672E+09 | 0.122827E+10 | 0.349713E+09 |
July | 0.101647E+10 | 67990399.01 | 0.948475E+09 | 0.123579E+10 | 0.320367E+09 |
August | 0.851080E+09 | 15083510.68 | 0.835996E+09 | 0.102079E+10 | 0.387439E+09 |
September | 0.631484E+09 | 156579.94 | 0.631328E+09 | 0.590287E+09 | 0.671974E+09 |
October | 0.485171E+09 | 0.00 | 0.485171E+09 | 0.225715E+09 | 0.106100E+10 |
November | 0.328434E+09 | 0.00 | 0.328434E+09 | 52435883.03 | 0.155684E+10 |
December | 0.220144E+09 | 0.00 | 0.220144E+09 | 231752.24 | 0.230885E+10 |
Annual Sum or Average | 0.750862E+10 | 0.216676E+09 | 0.729194E+10 | 0.589994E+10 | 0.137593E+11 |
Minimum of Months | 0.220144E+09 | 0.00 | 0.220144E+09 | 231752.24 | 0.320367E+09 |
Maximum of Months | 0.104887E+10 | 95198633.35 | 0.953672E+09 | 0.123579E+10 | 0.257603E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.324215E+09 | 0.00 | 0.324215E+09 | 1891520.22 | 0.257620E+10 |
February | 0.371263E+09 | 0.00 | 0.371263E+09 | 26102486.22 | 0.186664E+10 |
March | 0.616024E+09 | 0.00 | 0.616024E+09 | 0.221371E+09 | 0.130376E+10 |
April | 0.688218E+09 | 3390773.53 | 0.684827E+09 | 0.426480E+09 | 0.848883E+09 |
May | 0.927363E+09 | 34857017.82 | 0.892506E+09 | 0.870615E+09 | 0.508104E+09 |
June | 0.104891E+10 | 95201192.32 | 0.953710E+09 | 0.122832E+10 | 0.349733E+09 |
July | 0.101651E+10 | 67992226.61 | 0.948514E+09 | 0.123584E+10 | 0.320385E+09 |
August | 0.851113E+09 | 15083916.13 | 0.836030E+09 | 0.102083E+10 | 0.387462E+09 |
September | 0.631510E+09 | 156584.15 | 0.631353E+09 | 0.590309E+09 | 0.672014E+09 |
October | 0.485190E+09 | 0.00 | 0.485190E+09 | 0.225717E+09 | 0.106106E+10 |
November | 0.328447E+09 | 0.00 | 0.328447E+09 | 52435054.83 | 0.155694E+10 |
December | 0.220152E+09 | 0.00 | 0.220152E+09 | 231703.80 | 0.230900E+10 |
Annual Sum or Average | 0.750891E+10 | 0.216682E+09 | 0.729223E+10 | 0.590013E+10 | 0.137602E+11 |
Minimum of Months | 0.220152E+09 | 0.00 | 0.220152E+09 | 231703.80 | 0.320385E+09 |
Maximum of Months | 0.104891E+10 | 95201192.32 | 0.953710E+09 | 0.123584E+10 | 0.257620E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.324215E+09 | 0.00 | 0.324215E+09 | 1891520.22 | 0.257620E+10 |
February | 0.371263E+09 | 0.00 | 0.371263E+09 | 26102486.22 | 0.186664E+10 |
March | 0.616024E+09 | 0.00 | 0.616024E+09 | 0.221371E+09 | 0.130376E+10 |
April | 0.688218E+09 | 3390773.53 | 0.684827E+09 | 0.426480E+09 | 0.848883E+09 |
May | 0.927363E+09 | 34857017.82 | 0.892506E+09 | 0.870615E+09 | 0.508104E+09 |
June | 0.104891E+10 | 95201192.32 | 0.953710E+09 | 0.122832E+10 | 0.349733E+09 |
July | 0.101651E+10 | 67992226.61 | 0.948514E+09 | 0.123584E+10 | 0.320385E+09 |
August | 0.851113E+09 | 15083916.13 | 0.836030E+09 | 0.102083E+10 | 0.387462E+09 |
September | 0.631510E+09 | 156584.15 | 0.631353E+09 | 0.590309E+09 | 0.672014E+09 |
October | 0.485190E+09 | 0.00 | 0.485190E+09 | 0.225717E+09 | 0.106106E+10 |
November | 0.328447E+09 | 0.00 | 0.328447E+09 | 52435054.83 | 0.155694E+10 |
December | 0.220152E+09 | 0.00 | 0.220152E+09 | 231703.80 | 0.230900E+10 |
Annual Sum or Average | 0.750891E+10 | 0.216682E+09 | 0.729223E+10 | 0.590013E+10 | 0.137602E+11 |
Minimum of Months | 0.220152E+09 | 0.00 | 0.220152E+09 | 231703.80 | 0.320385E+09 |
Maximum of Months | 0.104891E+10 | 95201192.32 | 0.953710E+09 | 0.123584E+10 | 0.257620E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133661E+10 | 0.550017E+09 | 0.786592E+09 | 0.602345E+09 | 0.449710E+10 |
February | 0.160022E+10 | 0.703645E+09 | 0.896572E+09 | 0.953610E+09 | 0.322323E+10 |
March | 0.240716E+10 | 0.955469E+09 | 0.145169E+10 | 0.192236E+10 | 0.233980E+10 |
April | 0.286041E+10 | 0.125266E+10 | 0.160775E+10 | 0.282406E+10 | 0.161887E+10 |
May | 0.371220E+10 | 0.162206E+10 | 0.209014E+10 | 0.422717E+10 | 0.104250E+10 |
June | 0.395339E+10 | 0.172163E+10 | 0.223176E+10 | 0.497217E+10 | 0.709517E+09 |
July | 0.412906E+10 | 0.190524E+10 | 0.222383E+10 | 0.530399E+10 | 0.650817E+09 |
August | 0.348072E+10 | 0.150061E+10 | 0.198011E+10 | 0.446980E+10 | 0.771270E+09 |
September | 0.300435E+10 | 0.141970E+10 | 0.158464E+10 | 0.354437E+10 | 0.128776E+10 |
October | 0.197840E+10 | 0.826358E+09 | 0.115204E+10 | 0.173492E+10 | 0.197393E+10 |
November | 0.112962E+10 | 0.366919E+09 | 0.762698E+09 | 0.593910E+09 | 0.280751E+10 |
December | 0.904179E+09 | 0.388275E+09 | 0.515904E+09 | 0.413552E+09 | 0.412324E+10 |
Annual Sum or Average | 0.304963E+11 | 0.132126E+11 | 0.172837E+11 | 0.315622E+11 | 0.250455E+11 |
Minimum of Months | 0.904179E+09 | 0.366919E+09 | 0.515904E+09 | 0.413552E+09 | 0.650817E+09 |
Maximum of Months | 0.412906E+10 | 0.190524E+10 | 0.223176E+10 | 0.530399E+10 | 0.449710E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52848333.44 | 21747177.24 | 31101156.20 | 23816197.61 | 0.177811E+09 |
February | 63271121.83 | 27821483.10 | 35449638.73 | 37704890.63 | 0.127444E+09 |
March | 95176819.75 | 37778372.49 | 57398447.26 | 76008468.51 | 92513441.17 |
April | 0.113098E+09 | 49529090.55 | 63569016.08 | 0.111661E+09 | 64008836.88 |
May | 0.146777E+09 | 64134625.01 | 82642305.37 | 0.167139E+09 | 41219574.43 |
June | 0.156314E+09 | 68071882.56 | 88241725.46 | 0.196595E+09 | 28053672.97 |
July | 0.163259E+09 | 75331340.01 | 87928116.42 | 0.209715E+09 | 25732725.38 |
August | 0.137625E+09 | 59332787.70 | 78291826.23 | 0.176732E+09 | 30495302.75 |
September | 0.118789E+09 | 56133846.95 | 62655254.45 | 0.140141E+09 | 50916737.01 |
October | 78223966.07 | 32673432.69 | 45550533.38 | 68597176.76 | 78047339.81 |
November | 44664048.95 | 14507661.16 | 30156387.79 | 23482664.79 | 0.111006E+09 |
December | 35750404.86 | 15352039.08 | 20398365.78 | 16351459.97 | 0.163029E+09 |
Annual Sum or Average | 0.120580E+10 | 0.522414E+09 | 0.683383E+09 | 0.124794E+10 | 0.990278E+09 |
Minimum of Months | 35750404.86 | 14507661.16 | 20398365.78 | 16351459.97 | 25732725.38 |
Maximum of Months | 0.163259E+09 | 75331340.01 | 88241725.46 | 0.209715E+09 | 0.177811E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201627E+10 | 0.137977E+10 | 0.636494E+09 | 0.184803E+10 | 0.208853E+10 |
February | 0.195132E+10 | 0.131833E+10 | 0.632997E+09 | 0.185998E+10 | 0.154592E+10 |
March | 0.188003E+10 | 0.989958E+09 | 0.890072E+09 | 0.188641E+10 | 0.123322E+10 |
April | 0.163915E+10 | 0.766329E+09 | 0.872818E+09 | 0.182689E+10 | 0.888033E+09 |
May | 0.140325E+10 | 0.380436E+09 | 0.102281E+10 | 0.166546E+10 | 0.566323E+09 |
June | 0.131839E+10 | 0.268430E+09 | 0.104996E+10 | 0.172075E+10 | 0.378710E+09 |
July | 0.144213E+10 | 0.363376E+09 | 0.107876E+10 | 0.195087E+10 | 0.350442E+09 |
August | 0.162480E+10 | 0.582689E+09 | 0.104211E+10 | 0.222248E+10 | 0.428582E+09 |
September | 0.190540E+10 | 0.100398E+10 | 0.901415E+09 | 0.242347E+10 | 0.700122E+09 |
October | 0.205596E+10 | 0.128982E+10 | 0.766136E+09 | 0.228988E+10 | 0.105805E+10 |
November | 0.150117E+10 | 0.939761E+09 | 0.561413E+09 | 0.143102E+10 | 0.140003E+10 |
December | 0.165414E+10 | 0.125299E+10 | 0.401152E+09 | 0.160700E+10 | 0.198305E+10 |
Annual Sum or Average | 0.203920E+11 | 0.105359E+11 | 0.985614E+10 | 0.227323E+11 | 0.126210E+11 |
Minimum of Months | 0.131839E+10 | 0.268430E+09 | 0.401152E+09 | 0.143102E+10 | 0.350442E+09 |
Maximum of Months | 0.205596E+10 | 0.137977E+10 | 0.107876E+10 | 0.242347E+10 | 0.208853E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201627E+10 | 0.137977E+10 | 0.636494E+09 | 0.184803E+10 | 0.208853E+10 |
February | 0.195132E+10 | 0.131833E+10 | 0.632997E+09 | 0.185998E+10 | 0.154592E+10 |
March | 0.188003E+10 | 0.989958E+09 | 0.890072E+09 | 0.188641E+10 | 0.123322E+10 |
April | 0.163915E+10 | 0.766329E+09 | 0.872818E+09 | 0.182689E+10 | 0.888033E+09 |
May | 0.140325E+10 | 0.380436E+09 | 0.102281E+10 | 0.166546E+10 | 0.566323E+09 |
June | 0.131839E+10 | 0.268430E+09 | 0.104996E+10 | 0.172075E+10 | 0.378710E+09 |
July | 0.144213E+10 | 0.363376E+09 | 0.107876E+10 | 0.195087E+10 | 0.350442E+09 |
August | 0.162480E+10 | 0.582689E+09 | 0.104211E+10 | 0.222248E+10 | 0.428582E+09 |
September | 0.190540E+10 | 0.100398E+10 | 0.901415E+09 | 0.242347E+10 | 0.700122E+09 |
October | 0.205596E+10 | 0.128982E+10 | 0.766136E+09 | 0.228988E+10 | 0.105805E+10 |
November | 0.150117E+10 | 0.939761E+09 | 0.561413E+09 | 0.143102E+10 | 0.140003E+10 |
December | 0.165414E+10 | 0.125299E+10 | 0.401152E+09 | 0.160700E+10 | 0.198305E+10 |
Annual Sum or Average | 0.203920E+11 | 0.105359E+11 | 0.985614E+10 | 0.227323E+11 | 0.126210E+11 |
Minimum of Months | 0.131839E+10 | 0.268430E+09 | 0.401152E+09 | 0.143102E+10 | 0.350442E+09 |
Maximum of Months | 0.205596E+10 | 0.137977E+10 | 0.107876E+10 | 0.242347E+10 | 0.208853E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201614E+10 | 0.137968E+10 | 0.636454E+09 | 0.184791E+10 | 0.208839E+10 |
February | 0.195120E+10 | 0.131824E+10 | 0.632957E+09 | 0.185986E+10 | 0.154582E+10 |
March | 0.187991E+10 | 0.989895E+09 | 0.890015E+09 | 0.188629E+10 | 0.123314E+10 |
April | 0.163904E+10 | 0.766281E+09 | 0.872762E+09 | 0.182678E+10 | 0.887977E+09 |
May | 0.140316E+10 | 0.380412E+09 | 0.102275E+10 | 0.166535E+10 | 0.566288E+09 |
June | 0.131831E+10 | 0.268413E+09 | 0.104990E+10 | 0.172064E+10 | 0.378686E+09 |
July | 0.144204E+10 | 0.363353E+09 | 0.107869E+10 | 0.195075E+10 | 0.350419E+09 |
August | 0.162470E+10 | 0.582652E+09 | 0.104205E+10 | 0.222234E+10 | 0.428555E+09 |
September | 0.190528E+10 | 0.100392E+10 | 0.901358E+09 | 0.242331E+10 | 0.700078E+09 |
October | 0.205583E+10 | 0.128974E+10 | 0.766088E+09 | 0.228974E+10 | 0.105798E+10 |
November | 0.150108E+10 | 0.939702E+09 | 0.561378E+09 | 0.143093E+10 | 0.139994E+10 |
December | 0.165404E+10 | 0.125291E+10 | 0.401126E+09 | 0.160690E+10 | 0.198292E+10 |
Annual Sum or Average | 0.203907E+11 | 0.105352E+11 | 0.985552E+10 | 0.227308E+11 | 0.126202E+11 |
Minimum of Months | 0.131831E+10 | 0.268413E+09 | 0.401126E+09 | 0.143093E+10 | 0.350419E+09 |
Maximum of Months | 0.205583E+10 | 0.137968E+10 | 0.107869E+10 | 0.242331E+10 | 0.208839E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132559E+10 | 0.536349E+09 | 0.789243E+09 | 0.629887E+09 | 0.460116E+10 |
February | 0.175564E+10 | 0.865125E+09 | 0.890516E+09 | 0.118477E+10 | 0.333735E+10 |
March | 0.232043E+10 | 0.863325E+09 | 0.145711E+10 | 0.183182E+10 | 0.241594E+10 |
April | 0.327563E+10 | 0.161974E+10 | 0.165589E+10 | 0.343193E+10 | 0.170283E+10 |
May | 0.339461E+10 | 0.135606E+10 | 0.203855E+10 | 0.388759E+10 | 0.109694E+10 |
June | 0.385469E+10 | 0.167052E+10 | 0.218416E+10 | 0.487809E+10 | 0.761817E+09 |
July | 0.427672E+10 | 0.203150E+10 | 0.224522E+10 | 0.554950E+10 | 0.719883E+09 |
August | 0.373893E+10 | 0.171592E+10 | 0.202301E+10 | 0.487178E+10 | 0.838713E+09 |
September | 0.292893E+10 | 0.139021E+10 | 0.153871E+10 | 0.347130E+10 | 0.134618E+10 |
October | 0.210903E+10 | 0.937648E+09 | 0.117138E+10 | 0.196352E+10 | 0.205742E+10 |
November | 0.122167E+10 | 0.451772E+09 | 0.769899E+09 | 0.758205E+09 | 0.287461E+10 |
December | 0.970846E+09 | 0.457669E+09 | 0.513176E+09 | 0.542084E+09 | 0.421008E+10 |
Annual Sum or Average | 0.311727E+11 | 0.138958E+11 | 0.172769E+11 | 0.330005E+11 | 0.259629E+11 |
Minimum of Months | 0.970846E+09 | 0.451772E+09 | 0.513176E+09 | 0.542084E+09 | 0.719883E+09 |
Maximum of Months | 0.427672E+10 | 0.203150E+10 | 0.224522E+10 | 0.554950E+10 | 0.460116E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52412564.45 | 21206694.15 | 31205870.30 | 24905025.35 | 0.181926E+09 |
February | 69416280.03 | 34206148.70 | 35210131.33 | 46844593.42 | 0.131956E+09 |
March | 91747546.41 | 34134985.47 | 57612560.94 | 72428292.16 | 95524016.49 |
April | 0.129515E+09 | 64042755.41 | 65472401.82 | 0.135695E+09 | 67328313.69 |
May | 0.134220E+09 | 53617326.43 | 80602273.03 | 0.153711E+09 | 43371961.57 |
June | 0.152410E+09 | 66050663.64 | 86359703.28 | 0.192875E+09 | 30121532.87 |
July | 0.169097E+09 | 80323503.52 | 88773639.56 | 0.219422E+09 | 28463504.90 |
August | 0.147833E+09 | 67845650.47 | 79987783.28 | 0.192625E+09 | 33161941.70 |
September | 0.115807E+09 | 54967644.38 | 60839120.57 | 0.137252E+09 | 53226674.09 |
October | 83388869.09 | 37073632.29 | 46315236.80 | 77635411.78 | 81348631.03 |
November | 48303623.31 | 17862585.56 | 30441037.76 | 29978589.87 | 0.113660E+09 |
December | 38386251.97 | 18095774.92 | 20290477.05 | 21433416.43 | 0.166463E+09 |
Annual Sum or Average | 0.123254E+10 | 0.549427E+09 | 0.683110E+09 | 0.130480E+10 | 0.102655E+10 |
Minimum of Months | 38386251.97 | 17862585.56 | 20290477.05 | 21433416.43 | 28463504.90 |
Maximum of Months | 0.169097E+09 | 80323503.52 | 88773639.56 | 0.219422E+09 | 0.181926E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.972653E+09 | 0.00 | 0.972653E+09 | 4460390.26 | 0.784007E+10 |
February | 0.111380E+10 | 0.00 | 0.111380E+10 | 70090001.40 | 0.571568E+10 |
March | 0.184809E+10 | 0.00 | 0.184809E+10 | 0.593878E+09 | 0.406319E+10 |
April | 0.206467E+10 | 10172528.45 | 0.205450E+10 | 0.116139E+10 | 0.274483E+10 |
May | 0.278211E+10 | 0.104573E+09 | 0.267754E+10 | 0.244338E+10 | 0.167220E+10 |
June | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.359071E+10 | 0.111442E+10 |
July | 0.304954E+10 | 0.203981E+09 | 0.284556E+10 | 0.364031E+10 | 0.100300E+10 |
August | 0.255336E+10 | 45252673.04 | 0.250811E+10 | 0.302755E+10 | 0.118158E+10 |
September | 0.189454E+10 | 469762.04 | 0.189407E+10 | 0.175296E+10 | 0.201000E+10 |
October | 0.145558E+10 | 0.00 | 0.145558E+10 | 0.670763E+09 | 0.314323E+10 |
November | 0.985350E+09 | 0.00 | 0.985350E+09 | 0.154062E+09 | 0.462565E+10 |
December | 0.660462E+09 | 0.00 | 0.660462E+09 | 560240.97 | 0.694315E+10 |
Annual Sum or Average | 0.225269E+11 | 0.650058E+09 | 0.218769E+11 | 0.171101E+11 | 0.420570E+11 |
Minimum of Months | 0.660462E+09 | 0.00 | 0.660462E+09 | 560240.97 | 0.100300E+10 |
Maximum of Months | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.364031E+10 | 0.784007E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138948E+10 | 0.571775E+09 | 0.817705E+09 | 0.611627E+09 | 0.471449E+10 |
February | 0.166351E+10 | 0.731481E+09 | 0.932034E+09 | 0.966129E+09 | 0.338869E+10 |
March | 0.250237E+10 | 0.993267E+09 | 0.150911E+10 | 0.192586E+10 | 0.250109E+10 |
April | 0.297356E+10 | 0.130222E+10 | 0.167134E+10 | 0.284666E+10 | 0.176952E+10 |
May | 0.385903E+10 | 0.168622E+10 | 0.217281E+10 | 0.430779E+10 | 0.113288E+10 |
June | 0.410977E+10 | 0.178974E+10 | 0.232003E+10 | 0.511186E+10 | 0.754508E+09 |
July | 0.429239E+10 | 0.198061E+10 | 0.231178E+10 | 0.547252E+10 | 0.677899E+09 |
August | 0.361840E+10 | 0.155997E+10 | 0.205843E+10 | 0.461730E+10 | 0.790765E+09 |
September | 0.312318E+10 | 0.147587E+10 | 0.164732E+10 | 0.366896E+10 | 0.129839E+10 |
October | 0.205665E+10 | 0.859048E+09 | 0.119760E+10 | 0.179881E+10 | 0.198114E+10 |
November | 0.117430E+10 | 0.381434E+09 | 0.792865E+09 | 0.614078E+09 | 0.286932E+10 |
December | 0.939944E+09 | 0.403635E+09 | 0.536309E+09 | 0.424545E+09 | 0.427617E+10 |
Annual Sum or Average | 0.317026E+11 | 0.137353E+11 | 0.179673E+11 | 0.323661E+11 | 0.261548E+11 |
Minimum of Months | 0.939944E+09 | 0.381434E+09 | 0.536309E+09 | 0.424545E+09 | 0.677899E+09 |
Maximum of Months | 0.429239E+10 | 0.198061E+10 | 0.232003E+10 | 0.547252E+10 | 0.471449E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.604891E+10 | 0.413940E+10 | 0.190951E+10 | 0.538869E+10 | 0.642641E+10 |
February | 0.585407E+10 | 0.395506E+10 | 0.189902E+10 | 0.543105E+10 | 0.471233E+10 |
March | 0.564018E+10 | 0.296993E+10 | 0.267025E+10 | 0.549276E+10 | 0.381236E+10 |
April | 0.491751E+10 | 0.229903E+10 | 0.261848E+10 | 0.533401E+10 | 0.280873E+10 |
May | 0.420979E+10 | 0.114133E+10 | 0.306846E+10 | 0.483193E+10 | 0.183197E+10 |
June | 0.395523E+10 | 0.805306E+09 | 0.314992E+10 | 0.506062E+10 | 0.120210E+10 |
July | 0.432645E+10 | 0.109015E+10 | 0.323630E+10 | 0.578772E+10 | 0.107604E+10 |
August | 0.487447E+10 | 0.174810E+10 | 0.312637E+10 | 0.662450E+10 | 0.127017E+10 |
September | 0.571629E+10 | 0.301201E+10 | 0.270427E+10 | 0.723299E+10 | 0.203912E+10 |
October | 0.616797E+10 | 0.386954E+10 | 0.229844E+10 | 0.682386E+10 | 0.303835E+10 |
November | 0.450361E+10 | 0.281934E+10 | 0.168426E+10 | 0.423693E+10 | 0.413073E+10 |
December | 0.496252E+10 | 0.375905E+10 | 0.120347E+10 | 0.473936E+10 | 0.599864E+10 |
Annual Sum or Average | 0.611770E+11 | 0.316083E+11 | 0.295687E+11 | 0.669844E+11 | 0.383469E+11 |
Minimum of Months | 0.395523E+10 | 0.805306E+09 | 0.120347E+10 | 0.423693E+10 | 0.107604E+10 |
Maximum of Months | 0.616797E+10 | 0.413940E+10 | 0.323630E+10 | 0.723299E+10 | 0.642641E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137802E+10 | 0.557565E+09 | 0.820458E+09 | 0.636192E+09 | 0.483498E+10 |
February | 0.182508E+10 | 0.899346E+09 | 0.925736E+09 | 0.119981E+10 | 0.351517E+10 |
March | 0.241221E+10 | 0.897475E+09 | 0.151474E+10 | 0.183575E+10 | 0.258321E+10 |
April | 0.340519E+10 | 0.168381E+10 | 0.172138E+10 | 0.349004E+10 | 0.184420E+10 |
May | 0.352888E+10 | 0.140970E+10 | 0.211917E+10 | 0.395833E+10 | 0.119898E+10 |
June | 0.400715E+10 | 0.173660E+10 | 0.227055E+10 | 0.502273E+10 | 0.810154E+09 |
July | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.573857E+10 | 0.741497E+09 |
August | 0.388681E+10 | 0.178379E+10 | 0.210302E+10 | 0.504360E+10 | 0.851950E+09 |
September | 0.304477E+10 | 0.144521E+10 | 0.159957E+10 | 0.359955E+10 | 0.135797E+10 |
October | 0.219245E+10 | 0.974738E+09 | 0.121771E+10 | 0.203919E+10 | 0.206634E+10 |
November | 0.126999E+10 | 0.469642E+09 | 0.800349E+09 | 0.783957E+09 | 0.293878E+10 |
December | 0.100925E+10 | 0.475773E+09 | 0.533472E+09 | 0.552775E+09 | 0.437472E+10 |
Annual Sum or Average | 0.324057E+11 | 0.144455E+11 | 0.179602E+11 | 0.339005E+11 | 0.271179E+11 |
Minimum of Months | 0.100925E+10 | 0.469642E+09 | 0.533472E+09 | 0.552775E+09 | 0.741497E+09 |
Maximum of Months | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.573857E+10 | 0.483498E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.99 | 2877.13 | 363.15 | 0.00 | 363.15 | 0.00 | 0.00 |
February | 32.12 | 2297.59 | 460.40 | 0.00 | 460.40 | 0.00 | 0.00 |
March | 232.10 | 1451.97 | 690.00 | 0.00 | 690.00 | 0.00 | 0.00 |
April | 459.03 | 997.99 | 796.55 | 3.92 | 792.63 | 0.00 | 0.00 |
May | 922.89 | 596.55 | 1038.72 | 39.04 | 999.68 | 0.00 | 0.00 |
June | 1389.41 | 413.07 | 1214.03 | 110.19 | 1103.84 | 0.00 | 0.00 |
July | 1359.37 | 362.78 | 1138.57 | 76.16 | 1062.41 | 0.00 | 0.00 |
August | 1133.56 | 423.73 | 953.32 | 16.90 | 936.42 | 0.00 | 0.00 |
September | 689.50 | 728.50 | 730.92 | 0.18 | 730.74 | 0.00 | 0.00 |
October | 275.26 | 1084.53 | 543.45 | 0.00 | 543.45 | 0.00 | 0.00 |
November | 69.86 | 1696.28 | 380.15 | 0.00 | 380.15 | 0.00 | 0.00 |
December | 0.73 | 2520.61 | 246.59 | 0.00 | 246.59 | 0.00 | 0.00 |
Annual Sum or Average | 550.24 | 1282.86 | 714.32 | 20.61 | 693.71 | 0.00 | 0.00 |
Minimum of Months | 0.73 | 362.78 | 246.59 | 0.00 | 246.59 | 0.00 | 0.00 |
Maximum of Months | 1389.41 | 2877.13 | 1214.03 | 110.19 | 1103.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 230.62 | 1731.75 | 518.77 | 213.48 | 305.30 | 0.00 | 0.00 |
February | 405.52 | 1361.32 | 687.63 | 302.36 | 385.27 | 0.00 | 0.00 |
March | 731.55 | 892.82 | 934.28 | 370.84 | 563.44 | 0.00 | 0.00 |
April | 1108.45 | 645.33 | 1147.21 | 502.40 | 644.81 | 0.00 | 0.00 |
May | 1614.20 | 406.59 | 1440.80 | 629.56 | 811.23 | 0.00 | 0.00 |
June | 1975.75 | 280.13 | 1585.56 | 690.49 | 895.07 | 0.00 | 0.00 |
July | 2044.30 | 245.69 | 1602.59 | 739.47 | 863.12 | 0.00 | 0.00 |
August | 1727.00 | 284.60 | 1350.96 | 582.43 | 768.53 | 0.00 | 0.00 |
September | 1424.82 | 473.72 | 1204.93 | 569.39 | 635.54 | 0.00 | 0.00 |
October | 695.35 | 685.23 | 767.87 | 320.73 | 447.13 | 0.00 | 0.00 |
November | 249.07 | 1053.39 | 453.05 | 147.16 | 305.89 | 0.00 | 0.00 |
December | 161.89 | 1554.39 | 350.93 | 150.70 | 200.23 | 0.00 | 0.00 |
Annual Sum or Average | 1034.11 | 798.70 | 1005.28 | 435.54 | 569.74 | 0.00 | 0.00 |
Minimum of Months | 161.89 | 245.69 | 350.93 | 147.16 | 200.23 | 0.00 | 0.00 |
Maximum of Months | 2044.30 | 1731.75 | 1602.59 | 739.47 | 895.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2021.00 | 2348.54 | 2258.40 | 1545.48 | 712.93 | 0.00 | 0.00 |
February | 2259.08 | 1882.21 | 2419.84 | 1634.86 | 784.98 | 0.00 | 0.00 |
March | 2064.43 | 1359.74 | 2105.80 | 1108.85 | 996.96 | 0.00 | 0.00 |
April | 2066.39 | 1024.08 | 1897.19 | 886.97 | 1010.22 | 0.00 | 0.00 |
May | 1807.65 | 654.64 | 1571.76 | 426.12 | 1145.63 | 0.00 | 0.00 |
June | 1952.47 | 444.72 | 1525.94 | 310.69 | 1215.25 | 0.00 | 0.00 |
July | 2158.04 | 388.67 | 1615.31 | 407.02 | 1208.30 | 0.00 | 0.00 |
August | 2471.75 | 455.82 | 1819.92 | 652.67 | 1167.25 | 0.00 | 0.00 |
September | 2798.51 | 743.95 | 2205.36 | 1162.04 | 1043.32 | 0.00 | 0.00 |
October | 2572.77 | 1053.88 | 2302.86 | 1444.72 | 858.14 | 0.00 | 0.00 |
November | 1656.94 | 1512.17 | 1737.50 | 1087.71 | 649.79 | 0.00 | 0.00 |
December | 1781.27 | 2168.86 | 1852.79 | 1403.47 | 449.32 | 0.00 | 0.00 |
Annual Sum or Average | 2133.34 | 1166.53 | 1939.91 | 1002.29 | 937.62 | 0.00 | 0.00 |
Minimum of Months | 1656.94 | 388.67 | 1525.94 | 310.69 | 449.32 | 0.00 | 0.00 |
Maximum of Months | 2798.51 | 2348.54 | 2419.84 | 1634.86 | 1215.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 238.59 | 1773.48 | 514.49 | 208.17 | 306.32 | 0.00 | 0.00 |
February | 499.56 | 1411.32 | 754.42 | 371.75 | 382.66 | 0.00 | 0.00 |
March | 692.63 | 922.06 | 900.62 | 335.08 | 565.54 | 0.00 | 0.00 |
April | 1351.77 | 671.56 | 1313.73 | 649.62 | 664.11 | 0.00 | 0.00 |
May | 1480.89 | 428.03 | 1317.53 | 526.32 | 791.21 | 0.00 | 0.00 |
June | 1937.52 | 299.97 | 1545.97 | 669.98 | 875.98 | 0.00 | 0.00 |
July | 2140.15 | 267.93 | 1659.90 | 788.48 | 871.42 | 0.00 | 0.00 |
August | 1882.10 | 305.90 | 1451.17 | 665.99 | 785.18 | 0.00 | 0.00 |
September | 1395.54 | 494.31 | 1174.68 | 557.56 | 617.12 | 0.00 | 0.00 |
October | 777.52 | 714.47 | 818.57 | 363.93 | 454.64 | 0.00 | 0.00 |
November | 312.02 | 1078.19 | 489.97 | 181.19 | 308.78 | 0.00 | 0.00 |
December | 208.99 | 1587.78 | 376.81 | 177.63 | 199.18 | 0.00 | 0.00 |
Annual Sum or Average | 1079.29 | 826.92 | 1027.58 | 458.06 | 569.51 | 0.00 | 0.00 |
Minimum of Months | 208.99 | 267.93 | 376.81 | 177.63 | 199.18 | 0.00 | 0.00 |
Maximum of Months | 2140.15 | 1773.48 | 1659.90 | 788.48 | 875.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.12 | 2885.46 | 363.14 | 0.00 | 363.14 | 0.00 | 0.00 |
February | 32.37 | 2314.73 | 460.39 | 0.00 | 460.39 | 0.00 | 0.00 |
March | 247.95 | 1460.28 | 689.98 | 0.00 | 689.98 | 0.00 | 0.00 |
April | 493.61 | 982.48 | 796.54 | 3.92 | 792.61 | 0.00 | 0.00 |
May | 975.14 | 569.10 | 1038.70 | 39.04 | 999.66 | 0.00 | 0.00 |
June | 1421.65 | 404.78 | 1214.00 | 110.19 | 1103.82 | 0.00 | 0.00 |
July | 1384.21 | 358.85 | 1138.54 | 76.16 | 1062.39 | 0.00 | 0.00 |
August | 1143.39 | 433.98 | 953.30 | 16.89 | 936.40 | 0.00 | 0.00 |
September | 683.22 | 777.78 | 730.90 | 0.18 | 730.72 | 0.00 | 0.00 |
October | 252.82 | 1188.44 | 543.44 | 0.00 | 543.44 | 0.00 | 0.00 |
November | 60.69 | 1801.98 | 380.14 | 0.00 | 380.14 | 0.00 | 0.00 |
December | 0.26 | 2586.19 | 246.58 | 0.00 | 246.58 | 0.00 | 0.00 |
Annual Sum or Average | 561.27 | 1308.97 | 714.31 | 20.61 | 693.70 | 0.00 | 0.00 |
Minimum of Months | 0.26 | 358.85 | 246.58 | 0.00 | 246.58 | 0.00 | 0.00 |
Maximum of Months | 1421.65 | 2885.46 | 1214.00 | 110.19 | 1103.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 233.78 | 1745.41 | 518.76 | 213.47 | 305.29 | 0.00 | 0.00 |
February | 409.77 | 1385.03 | 687.62 | 302.36 | 385.26 | 0.00 | 0.00 |
March | 746.11 | 908.12 | 934.26 | 370.84 | 563.43 | 0.00 | 0.00 |
April | 1132.61 | 649.26 | 1147.19 | 502.39 | 644.80 | 0.00 | 0.00 |
May | 1640.65 | 404.62 | 1440.78 | 629.55 | 811.22 | 0.00 | 0.00 |
June | 1994.12 | 284.56 | 1585.54 | 690.47 | 895.06 | 0.00 | 0.00 |
July | 2058.58 | 252.59 | 1602.57 | 739.46 | 863.11 | 0.00 | 0.00 |
August | 1734.82 | 299.34 | 1350.94 | 582.42 | 768.52 | 0.00 | 0.00 |
September | 1421.49 | 516.46 | 1204.91 | 569.38 | 635.53 | 0.00 | 0.00 |
October | 673.36 | 766.12 | 767.85 | 320.73 | 447.13 | 0.00 | 0.00 |
November | 238.19 | 1125.97 | 453.04 | 147.16 | 305.89 | 0.00 | 0.00 |
December | 160.51 | 1600.31 | 350.93 | 150.70 | 200.23 | 0.00 | 0.00 |
Annual Sum or Average | 1040.40 | 825.59 | 1005.27 | 435.53 | 569.73 | 0.00 | 0.00 |
Minimum of Months | 160.51 | 252.59 | 350.93 | 147.16 | 200.23 | 0.00 | 0.00 |
Maximum of Months | 2058.58 | 1745.41 | 1602.57 | 739.46 | 895.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2069.88 | 2339.25 | 2258.31 | 1545.41 | 712.90 | 0.00 | 0.00 |
February | 2306.47 | 1917.02 | 2419.74 | 1634.79 | 784.95 | 0.00 | 0.00 |
March | 2112.87 | 1381.27 | 2105.72 | 1108.80 | 996.92 | 0.00 | 0.00 |
April | 2114.41 | 1027.79 | 1897.12 | 886.94 | 1010.18 | 0.00 | 0.00 |
May | 1865.39 | 634.31 | 1571.70 | 426.11 | 1145.60 | 0.00 | 0.00 |
June | 1991.57 | 438.31 | 1525.89 | 310.68 | 1215.21 | 0.00 | 0.00 |
July | 2185.07 | 392.51 | 1615.26 | 407.00 | 1208.26 | 0.00 | 0.00 |
August | 2489.29 | 480.03 | 1819.86 | 652.64 | 1167.22 | 0.00 | 0.00 |
September | 2804.88 | 810.31 | 2205.28 | 1161.99 | 1043.28 | 0.00 | 0.00 |
October | 2564.78 | 1185.07 | 2302.77 | 1444.66 | 858.11 | 0.00 | 0.00 |
November | 1656.24 | 1620.37 | 1737.43 | 1087.66 | 649.77 | 0.00 | 0.00 |
December | 1799.92 | 2221.11 | 1852.72 | 1403.41 | 449.31 | 0.00 | 0.00 |
Annual Sum or Average | 2162.46 | 1200.60 | 1939.84 | 1002.25 | 937.59 | 0.00 | 0.00 |
Minimum of Months | 1656.24 | 392.51 | 1525.89 | 310.68 | 449.31 | 0.00 | 0.00 |
Maximum of Months | 2804.88 | 2339.25 | 2419.74 | 1634.79 | 1215.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 244.47 | 1785.80 | 514.49 | 208.17 | 306.32 | 0.00 | 0.00 |
February | 509.10 | 1434.07 | 754.41 | 371.75 | 382.66 | 0.00 | 0.00 |
March | 710.97 | 937.67 | 900.60 | 335.07 | 565.53 | 0.00 | 0.00 |
April | 1376.40 | 682.93 | 1313.71 | 649.61 | 664.11 | 0.00 | 0.00 |
May | 1508.85 | 425.74 | 1317.52 | 526.31 | 791.20 | 0.00 | 0.00 |
June | 1956.39 | 305.53 | 1545.95 | 669.97 | 875.97 | 0.00 | 0.00 |
July | 2153.87 | 279.40 | 1659.88 | 788.47 | 871.41 | 0.00 | 0.00 |
August | 1890.83 | 325.52 | 1451.15 | 665.98 | 785.17 | 0.00 | 0.00 |
September | 1392.19 | 539.89 | 1174.67 | 557.55 | 617.11 | 0.00 | 0.00 |
October | 762.08 | 798.53 | 818.55 | 363.92 | 454.64 | 0.00 | 0.00 |
November | 304.08 | 1152.88 | 489.96 | 181.19 | 308.77 | 0.00 | 0.00 |
December | 210.39 | 1634.01 | 376.80 | 177.63 | 199.17 | 0.00 | 0.00 |
Annual Sum or Average | 1087.81 | 855.83 | 1027.56 | 458.06 | 569.51 | 0.00 | 0.00 |
Minimum of Months | 210.39 | 279.40 | 376.80 | 177.63 | 199.17 | 0.00 | 0.00 |
Maximum of Months | 2153.87 | 1785.80 | 1659.88 | 788.47 | 875.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.67 | 2927.15 | 363.15 | 0.00 | 363.15 | 0.00 | 0.00 |
February | 28.97 | 2362.63 | 460.40 | 0.00 | 460.40 | 0.00 | 0.00 |
March | 221.73 | 1517.02 | 690.00 | 0.00 | 690.00 | 0.00 | 0.00 |
April | 448.07 | 1058.96 | 796.55 | 3.92 | 792.63 | 0.00 | 0.00 |
May | 912.26 | 624.33 | 1038.72 | 39.04 | 999.68 | 0.00 | 0.00 |
June | 1385.30 | 429.95 | 1214.03 | 110.19 | 1103.84 | 0.00 | 0.00 |
July | 1359.14 | 374.48 | 1138.57 | 76.16 | 1062.41 | 0.00 | 0.00 |
August | 1130.36 | 441.15 | 953.32 | 16.90 | 936.42 | 0.00 | 0.00 |
September | 676.30 | 775.46 | 730.92 | 0.18 | 730.74 | 0.00 | 0.00 |
October | 250.43 | 1173.55 | 543.45 | 0.00 | 543.45 | 0.00 | 0.00 |
November | 59.44 | 1784.59 | 380.15 | 0.00 | 380.15 | 0.00 | 0.00 |
December | 0.21 | 2592.28 | 246.59 | 0.00 | 246.59 | 0.00 | 0.00 |
Annual Sum or Average | 542.56 | 1333.62 | 714.32 | 20.61 | 693.71 | 0.00 | 0.00 |
Minimum of Months | 0.21 | 374.48 | 246.59 | 0.00 | 246.59 | 0.00 | 0.00 |
Maximum of Months | 1385.30 | 2927.15 | 1214.03 | 110.19 | 1103.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 228.36 | 1760.19 | 518.77 | 213.48 | 305.30 | 0.00 | 0.00 |
February | 399.36 | 1400.75 | 687.63 | 302.36 | 385.27 | 0.00 | 0.00 |
March | 719.03 | 933.80 | 934.28 | 370.84 | 563.44 | 0.00 | 0.00 |
April | 1098.25 | 682.68 | 1147.21 | 502.40 | 644.81 | 0.00 | 0.00 |
May | 1608.34 | 422.97 | 1440.80 | 629.56 | 811.23 | 0.00 | 0.00 |
June | 1972.17 | 291.09 | 1585.56 | 690.49 | 895.07 | 0.00 | 0.00 |
July | 2043.20 | 253.10 | 1602.59 | 739.47 | 863.12 | 0.00 | 0.00 |
August | 1723.90 | 295.24 | 1350.96 | 582.43 | 768.53 | 0.00 | 0.00 |
September | 1415.49 | 500.92 | 1204.93 | 569.39 | 635.54 | 0.00 | 0.00 |
October | 671.60 | 739.67 | 767.87 | 320.73 | 447.13 | 0.00 | 0.00 |
November | 236.91 | 1106.99 | 453.05 | 147.16 | 305.89 | 0.00 | 0.00 |
December | 158.51 | 1596.54 | 350.93 | 150.70 | 200.23 | 0.00 | 0.00 |
Annual Sum or Average | 1026.32 | 829.36 | 1005.28 | 435.54 | 569.74 | 0.00 | 0.00 |
Minimum of Months | 158.51 | 253.10 | 350.93 | 147.16 | 200.23 | 0.00 | 0.00 |
Maximum of Months | 2043.20 | 1760.19 | 1602.59 | 739.47 | 895.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2011.90 | 2399.35 | 2258.40 | 1545.48 | 712.93 | 0.00 | 0.00 |
February | 2244.98 | 1947.89 | 2419.84 | 1634.86 | 784.98 | 0.00 | 0.00 |
March | 2050.76 | 1423.37 | 2105.80 | 1108.85 | 996.96 | 0.00 | 0.00 |
April | 2057.87 | 1083.61 | 1897.19 | 886.97 | 1010.22 | 0.00 | 0.00 |
May | 1804.03 | 683.98 | 1571.76 | 426.12 | 1145.63 | 0.00 | 0.00 |
June | 1952.40 | 463.77 | 1525.94 | 310.69 | 1215.25 | 0.00 | 0.00 |
July | 2160.89 | 401.75 | 1615.31 | 407.02 | 1208.30 | 0.00 | 0.00 |
August | 2473.30 | 474.23 | 1819.92 | 652.67 | 1167.25 | 0.00 | 0.00 |
September | 2790.50 | 786.70 | 2205.36 | 1162.04 | 1043.32 | 0.00 | 0.00 |
October | 2547.74 | 1134.39 | 2302.86 | 1444.72 | 858.14 | 0.00 | 0.00 |
November | 1634.62 | 1593.64 | 1737.50 | 1087.71 | 649.79 | 0.00 | 0.00 |
December | 1769.48 | 2239.63 | 1852.79 | 1403.47 | 449.32 | 0.00 | 0.00 |
Annual Sum or Average | 2124.06 | 1215.97 | 1939.91 | 1002.29 | 937.62 | 0.00 | 0.00 |
Minimum of Months | 1634.62 | 401.75 | 1525.94 | 310.69 | 449.32 | 0.00 | 0.00 |
Maximum of Months | 2790.50 | 2399.35 | 2419.84 | 1634.86 | 1215.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 237.53 | 1805.18 | 514.49 | 208.17 | 306.32 | 0.00 | 0.00 |
February | 495.95 | 1453.03 | 754.42 | 371.75 | 382.66 | 0.00 | 0.00 |
March | 685.39 | 964.46 | 900.62 | 335.08 | 565.54 | 0.00 | 0.00 |
April | 1346.47 | 711.50 | 1313.73 | 649.62 | 664.11 | 0.00 | 0.00 |
May | 1477.87 | 447.65 | 1317.53 | 526.32 | 791.21 | 0.00 | 0.00 |
June | 1937.78 | 312.56 | 1545.97 | 669.98 | 875.98 | 0.00 | 0.00 |
July | 2142.54 | 276.84 | 1659.90 | 788.48 | 871.42 | 0.00 | 0.00 |
August | 1883.06 | 318.08 | 1451.17 | 665.99 | 785.18 | 0.00 | 0.00 |
September | 1388.72 | 523.91 | 1174.68 | 557.56 | 617.12 | 0.00 | 0.00 |
October | 761.35 | 771.48 | 818.57 | 363.93 | 454.64 | 0.00 | 0.00 |
November | 302.45 | 1133.79 | 489.97 | 181.19 | 308.78 | 0.00 | 0.00 |
December | 206.38 | 1633.33 | 376.81 | 177.63 | 199.18 | 0.00 | 0.00 |
Annual Sum or Average | 1074.98 | 859.90 | 1027.58 | 458.06 | 569.51 | 0.00 | 0.00 |
Minimum of Months | 206.38 | 276.84 | 376.81 | 177.63 | 199.18 | 0.00 | 0.00 |
Maximum of Months | 2142.54 | 1805.18 | 1659.90 | 788.48 | 875.98 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5335717.01 | 0.770610E+10 | 0.972653E+09 | 0.00 | 0.972653E+09 | 0.00 | 0.00 |
February | 77713618.58 | 0.555833E+10 | 0.111380E+10 | 0.00 | 0.111380E+10 | 0.00 | 0.00 |
March | 0.621668E+09 | 0.388897E+10 | 0.184809E+10 | 0.00 | 0.184809E+10 | 0.00 | 0.00 |
April | 0.118980E+10 | 0.258680E+10 | 0.206467E+10 | 10172528.45 | 0.205450E+10 | 0.00 | 0.00 |
May | 0.247188E+10 | 0.159779E+10 | 0.278211E+10 | 0.104573E+09 | 0.267754E+10 | 0.00 | 0.00 |
June | 0.360135E+10 | 0.107066E+10 | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.00 | 0.00 |
July | 0.364093E+10 | 0.971665E+09 | 0.304954E+10 | 0.203981E+09 | 0.284556E+10 | 0.00 | 0.00 |
August | 0.303613E+10 | 0.113492E+10 | 0.255336E+10 | 45252673.04 | 0.250811E+10 | 0.00 | 0.00 |
September | 0.178720E+10 | 0.188827E+10 | 0.189454E+10 | 469762.04 | 0.189407E+10 | 0.00 | 0.00 |
October | 0.737256E+09 | 0.290479E+10 | 0.145558E+10 | 0.00 | 0.145558E+10 | 0.00 | 0.00 |
November | 0.181066E+09 | 0.439675E+10 | 0.985350E+09 | 0.00 | 0.985350E+09 | 0.00 | 0.00 |
December | 1944454.54 | 0.675121E+10 | 0.660462E+09 | 0.00 | 0.660462E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.173523E+11 | 0.404563E+11 | 0.225269E+11 | 0.650058E+09 | 0.218769E+11 | 0.00 | 0.00 |
Minimum of Months | 1944454.54 | 0.971665E+09 | 0.660462E+09 | 0.00 | 0.660462E+09 | 0.00 | 0.00 |
Maximum of Months | 0.364093E+10 | 0.770610E+10 | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.617701E+09 | 0.463832E+10 | 0.138948E+10 | 0.571775E+09 | 0.817705E+09 | 0.00 | 0.00 |
February | 0.981029E+09 | 0.329330E+10 | 0.166351E+10 | 0.731481E+09 | 0.932034E+09 | 0.00 | 0.00 |
March | 0.195937E+10 | 0.239133E+10 | 0.250237E+10 | 0.993267E+09 | 0.150911E+10 | 0.00 | 0.00 |
April | 0.287311E+10 | 0.167270E+10 | 0.297356E+10 | 0.130222E+10 | 0.167134E+10 | 0.00 | 0.00 |
May | 0.432346E+10 | 0.108901E+10 | 0.385903E+10 | 0.168622E+10 | 0.217281E+10 | 0.00 | 0.00 |
June | 0.512114E+10 | 0.726090E+09 | 0.410977E+10 | 0.178974E+10 | 0.232003E+10 | 0.00 | 0.00 |
July | 0.547545E+10 | 0.658056E+09 | 0.429239E+10 | 0.198061E+10 | 0.231178E+10 | 0.00 | 0.00 |
August | 0.462560E+10 | 0.762265E+09 | 0.361840E+10 | 0.155997E+10 | 0.205843E+10 | 0.00 | 0.00 |
September | 0.369314E+10 | 0.122788E+10 | 0.312318E+10 | 0.147587E+10 | 0.164732E+10 | 0.00 | 0.00 |
October | 0.186243E+10 | 0.183533E+10 | 0.205665E+10 | 0.859048E+09 | 0.119760E+10 | 0.00 | 0.00 |
November | 0.645582E+09 | 0.273039E+10 | 0.117430E+10 | 0.381434E+09 | 0.792865E+09 | 0.00 | 0.00 |
December | 0.433602E+09 | 0.416327E+10 | 0.939944E+09 | 0.403635E+09 | 0.536309E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.326116E+11 | 0.251879E+11 | 0.317026E+11 | 0.137353E+11 | 0.179673E+11 | 0.00 | 0.00 |
Minimum of Months | 0.433602E+09 | 0.658056E+09 | 0.939944E+09 | 0.381434E+09 | 0.536309E+09 | 0.00 | 0.00 |
Maximum of Months | 0.547545E+10 | 0.463832E+10 | 0.429239E+10 | 0.198061E+10 | 0.232003E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.541305E+10 | 0.629033E+10 | 0.604891E+10 | 0.413940E+10 | 0.190951E+10 | 0.00 | 0.00 |
February | 0.546518E+10 | 0.455345E+10 | 0.585407E+10 | 0.395506E+10 | 0.189902E+10 | 0.00 | 0.00 |
March | 0.552937E+10 | 0.364192E+10 | 0.564018E+10 | 0.296993E+10 | 0.267025E+10 | 0.00 | 0.00 |
April | 0.535608E+10 | 0.265442E+10 | 0.491751E+10 | 0.229903E+10 | 0.261848E+10 | 0.00 | 0.00 |
May | 0.484160E+10 | 0.175338E+10 | 0.420979E+10 | 0.114133E+10 | 0.306846E+10 | 0.00 | 0.00 |
June | 0.506079E+10 | 0.115272E+10 | 0.395523E+10 | 0.805306E+09 | 0.314992E+10 | 0.00 | 0.00 |
July | 0.578008E+10 | 0.104100E+10 | 0.432645E+10 | 0.109015E+10 | 0.323630E+10 | 0.00 | 0.00 |
August | 0.662033E+10 | 0.122086E+10 | 0.487447E+10 | 0.174810E+10 | 0.312637E+10 | 0.00 | 0.00 |
September | 0.725373E+10 | 0.192833E+10 | 0.571629E+10 | 0.301201E+10 | 0.270427E+10 | 0.00 | 0.00 |
October | 0.689090E+10 | 0.282271E+10 | 0.616797E+10 | 0.386954E+10 | 0.229844E+10 | 0.00 | 0.00 |
November | 0.429480E+10 | 0.391954E+10 | 0.450361E+10 | 0.281934E+10 | 0.168426E+10 | 0.00 | 0.00 |
December | 0.477095E+10 | 0.580906E+10 | 0.496252E+10 | 0.375905E+10 | 0.120347E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.672769E+11 | 0.367877E+11 | 0.611770E+11 | 0.316083E+11 | 0.295687E+11 | 0.00 | 0.00 |
Minimum of Months | 0.429480E+10 | 0.104100E+10 | 0.395523E+10 | 0.805306E+09 | 0.120347E+10 | 0.00 | 0.00 |
Maximum of Months | 0.725373E+10 | 0.629033E+10 | 0.616797E+10 | 0.413940E+10 | 0.323630E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.639031E+09 | 0.475010E+10 | 0.137802E+10 | 0.557565E+09 | 0.820458E+09 | 0.00 | 0.00 |
February | 0.120855E+10 | 0.341427E+10 | 0.182508E+10 | 0.899346E+09 | 0.925736E+09 | 0.00 | 0.00 |
March | 0.185514E+10 | 0.246964E+10 | 0.241221E+10 | 0.897475E+09 | 0.151474E+10 | 0.00 | 0.00 |
April | 0.350379E+10 | 0.174067E+10 | 0.340519E+10 | 0.168381E+10 | 0.172138E+10 | 0.00 | 0.00 |
May | 0.396642E+10 | 0.114643E+10 | 0.352888E+10 | 0.140970E+10 | 0.211917E+10 | 0.00 | 0.00 |
June | 0.502204E+10 | 0.777535E+09 | 0.400715E+10 | 0.173660E+10 | 0.227055E+10 | 0.00 | 0.00 |
July | 0.573217E+10 | 0.717626E+09 | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.00 | 0.00 |
August | 0.504101E+10 | 0.819330E+09 | 0.388681E+10 | 0.178379E+10 | 0.210302E+10 | 0.00 | 0.00 |
September | 0.361724E+10 | 0.128124E+10 | 0.304477E+10 | 0.144521E+10 | 0.159957E+10 | 0.00 | 0.00 |
October | 0.208250E+10 | 0.191365E+10 | 0.219245E+10 | 0.974738E+09 | 0.121771E+10 | 0.00 | 0.00 |
November | 0.808746E+09 | 0.279466E+10 | 0.126999E+10 | 0.469642E+09 | 0.800349E+09 | 0.00 | 0.00 |
December | 0.559770E+09 | 0.425272E+10 | 0.100925E+10 | 0.475773E+09 | 0.533472E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.340364E+11 | 0.260779E+11 | 0.324057E+11 | 0.144455E+11 | 0.179602E+11 | 0.00 | 0.00 |
Minimum of Months | 0.559770E+09 | 0.717626E+09 | 0.100925E+10 | 0.469642E+09 | 0.533472E+09 | 0.00 | 0.00 |
Maximum of Months | 0.573217E+10 | 0.475010E+10 | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5674965.96 | 0.772842E+10 | 0.972632E+09 | 0.00 | 0.972632E+09 | 0.00 | 0.00 |
February | 78308429.62 | 0.559981E+10 | 0.111377E+10 | 0.00 | 0.111377E+10 | 0.00 | 0.00 |
March | 0.664112E+09 | 0.391121E+10 | 0.184805E+10 | 0.00 | 0.184805E+10 | 0.00 | 0.00 |
April | 0.127943E+10 | 0.254659E+10 | 0.206463E+10 | 10172229.45 | 0.205445E+10 | 0.00 | 0.00 |
May | 0.261182E+10 | 0.152428E+10 | 0.278205E+10 | 0.104570E+09 | 0.267748E+10 | 0.00 | 0.00 |
June | 0.368491E+10 | 0.104918E+10 | 0.314669E+10 | 0.285601E+09 | 0.286109E+10 | 0.00 | 0.00 |
July | 0.370746E+10 | 0.961137E+09 | 0.304948E+10 | 0.203975E+09 | 0.284550E+10 | 0.00 | 0.00 |
August | 0.306244E+10 | 0.116236E+10 | 0.255331E+10 | 45251342.94 | 0.250806E+10 | 0.00 | 0.00 |
September | 0.177090E+10 | 0.201600E+10 | 0.189450E+10 | 469748.23 | 0.189403E+10 | 0.00 | 0.00 |
October | 0.677150E+09 | 0.318312E+10 | 0.145555E+10 | 0.00 | 0.145555E+10 | 0.00 | 0.00 |
November | 0.157306E+09 | 0.467073E+10 | 0.985328E+09 | 0.00 | 0.985328E+09 | 0.00 | 0.00 |
December | 695159.84 | 0.692685E+10 | 0.660448E+09 | 0.00 | 0.660448E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.177002E+11 | 0.412797E+11 | 0.225264E+11 | 0.650039E+09 | 0.218764E+11 | 0.00 | 0.00 |
Minimum of Months | 695159.84 | 0.961137E+09 | 0.660448E+09 | 0.00 | 0.660448E+09 | 0.00 | 0.00 |
Maximum of Months | 0.370746E+10 | 0.772842E+10 | 0.314669E+10 | 0.285601E+09 | 0.286109E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.626162E+09 | 0.467491E+10 | 0.138946E+10 | 0.571764E+09 | 0.817694E+09 | 0.00 | 0.00 |
February | 0.991315E+09 | 0.335068E+10 | 0.166349E+10 | 0.731466E+09 | 0.932021E+09 | 0.00 | 0.00 |
March | 0.199837E+10 | 0.243231E+10 | 0.250233E+10 | 0.993247E+09 | 0.150909E+10 | 0.00 | 0.00 |
April | 0.293572E+10 | 0.168288E+10 | 0.297351E+10 | 0.130219E+10 | 0.167132E+10 | 0.00 | 0.00 |
May | 0.439431E+10 | 0.108372E+10 | 0.385897E+10 | 0.168619E+10 | 0.217278E+10 | 0.00 | 0.00 |
June | 0.516877E+10 | 0.737571E+09 | 0.410971E+10 | 0.178971E+10 | 0.232000E+10 | 0.00 | 0.00 |
July | 0.551370E+10 | 0.676550E+09 | 0.429232E+10 | 0.198057E+10 | 0.231176E+10 | 0.00 | 0.00 |
August | 0.464653E+10 | 0.801765E+09 | 0.361835E+10 | 0.155994E+10 | 0.205840E+10 | 0.00 | 0.00 |
September | 0.368451E+10 | 0.133867E+10 | 0.312313E+10 | 0.147584E+10 | 0.164730E+10 | 0.00 | 0.00 |
October | 0.180352E+10 | 0.205198E+10 | 0.205662E+10 | 0.859031E+09 | 0.119759E+10 | 0.00 | 0.00 |
November | 0.617393E+09 | 0.291852E+10 | 0.117428E+10 | 0.381427E+09 | 0.792854E+09 | 0.00 | 0.00 |
December | 0.429903E+09 | 0.428627E+10 | 0.939929E+09 | 0.403627E+09 | 0.536302E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.328102E+11 | 0.260358E+11 | 0.317021E+11 | 0.137350E+11 | 0.179671E+11 | 0.00 | 0.00 |
Minimum of Months | 0.429903E+09 | 0.676550E+09 | 0.939929E+09 | 0.381427E+09 | 0.536302E+09 | 0.00 | 0.00 |
Maximum of Months | 0.551370E+10 | 0.467491E+10 | 0.429232E+10 | 0.198057E+10 | 0.232000E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.554397E+10 | 0.626545E+10 | 0.604867E+10 | 0.413923E+10 | 0.190944E+10 | 0.00 | 0.00 |
February | 0.557982E+10 | 0.463765E+10 | 0.585385E+10 | 0.395490E+10 | 0.189895E+10 | 0.00 | 0.00 |
March | 0.565912E+10 | 0.369959E+10 | 0.563997E+10 | 0.296981E+10 | 0.267016E+10 | 0.00 | 0.00 |
April | 0.548056E+10 | 0.266404E+10 | 0.491734E+10 | 0.229894E+10 | 0.261840E+10 | 0.00 | 0.00 |
May | 0.499627E+10 | 0.169893E+10 | 0.420965E+10 | 0.114128E+10 | 0.306837E+10 | 0.00 | 0.00 |
June | 0.516215E+10 | 0.113610E+10 | 0.395510E+10 | 0.805273E+09 | 0.314983E+10 | 0.00 | 0.00 |
July | 0.585249E+10 | 0.105130E+10 | 0.432631E+10 | 0.109011E+10 | 0.323620E+10 | 0.00 | 0.00 |
August | 0.666731E+10 | 0.128572E+10 | 0.487430E+10 | 0.174803E+10 | 0.312627E+10 | 0.00 | 0.00 |
September | 0.727025E+10 | 0.210032E+10 | 0.571608E+10 | 0.301189E+10 | 0.270419E+10 | 0.00 | 0.00 |
October | 0.686951E+10 | 0.317409E+10 | 0.616774E+10 | 0.386938E+10 | 0.229836E+10 | 0.00 | 0.00 |
November | 0.429297E+10 | 0.420000E+10 | 0.450343E+10 | 0.281922E+10 | 0.168420E+10 | 0.00 | 0.00 |
December | 0.482090E+10 | 0.594902E+10 | 0.496233E+10 | 0.375890E+10 | 0.120343E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.681953E+11 | 0.378622E+11 | 0.611747E+11 | 0.316070E+11 | 0.295678E+11 | 0.00 | 0.00 |
Minimum of Months | 0.429297E+10 | 0.105130E+10 | 0.395510E+10 | 0.805273E+09 | 0.120343E+10 | 0.00 | 0.00 |
Maximum of Months | 0.727025E+10 | 0.626545E+10 | 0.616774E+10 | 0.413923E+10 | 0.323620E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.654792E+09 | 0.478308E+10 | 0.137800E+10 | 0.557556E+09 | 0.820449E+09 | 0.00 | 0.00 |
February | 0.123162E+10 | 0.346931E+10 | 0.182506E+10 | 0.899331E+09 | 0.925726E+09 | 0.00 | 0.00 |
March | 0.190425E+10 | 0.251146E+10 | 0.241218E+10 | 0.897460E+09 | 0.151472E+10 | 0.00 | 0.00 |
April | 0.356762E+10 | 0.177016E+10 | 0.340515E+10 | 0.168378E+10 | 0.172137E+10 | 0.00 | 0.00 |
May | 0.404130E+10 | 0.114031E+10 | 0.352883E+10 | 0.140968E+10 | 0.211915E+10 | 0.00 | 0.00 |
June | 0.507096E+10 | 0.791938E+09 | 0.400710E+10 | 0.173657E+10 | 0.227052E+10 | 0.00 | 0.00 |
July | 0.576892E+10 | 0.748346E+09 | 0.444582E+10 | 0.211183E+10 | 0.233399E+10 | 0.00 | 0.00 |
August | 0.506440E+10 | 0.871875E+09 | 0.388676E+10 | 0.178376E+10 | 0.210300E+10 | 0.00 | 0.00 |
September | 0.360855E+10 | 0.139941E+10 | 0.304473E+10 | 0.144518E+10 | 0.159955E+10 | 0.00 | 0.00 |
October | 0.204115E+10 | 0.213877E+10 | 0.219242E+10 | 0.974722E+09 | 0.121770E+10 | 0.00 | 0.00 |
November | 0.788183E+09 | 0.298827E+10 | 0.126997E+10 | 0.469634E+09 | 0.800340E+09 | 0.00 | 0.00 |
December | 0.563518E+09 | 0.437654E+10 | 0.100923E+10 | 0.475765E+09 | 0.533467E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.343053E+11 | 0.269895E+11 | 0.324052E+11 | 0.144453E+11 | 0.179600E+11 | 0.00 | 0.00 |
Minimum of Months | 0.563518E+09 | 0.748346E+09 | 0.100923E+10 | 0.469634E+09 | 0.533467E+09 | 0.00 | 0.00 |
Maximum of Months | 0.576892E+10 | 0.478308E+10 | 0.444582E+10 | 0.211183E+10 | 0.233399E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 4460390.26 | 0.784007E+10 | 0.972653E+09 | 0.00 | 0.972653E+09 | 0.00 | 0.00 |
February | 70090001.40 | 0.571568E+10 | 0.111380E+10 | 0.00 | 0.111380E+10 | 0.00 | 0.00 |
March | 0.593878E+09 | 0.406319E+10 | 0.184809E+10 | 0.00 | 0.184809E+10 | 0.00 | 0.00 |
April | 0.116139E+10 | 0.274483E+10 | 0.206467E+10 | 10172528.45 | 0.205450E+10 | 0.00 | 0.00 |
May | 0.244338E+10 | 0.167220E+10 | 0.278211E+10 | 0.104573E+09 | 0.267754E+10 | 0.00 | 0.00 |
June | 0.359071E+10 | 0.111442E+10 | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.00 | 0.00 |
July | 0.364031E+10 | 0.100300E+10 | 0.304954E+10 | 0.203981E+09 | 0.284556E+10 | 0.00 | 0.00 |
August | 0.302755E+10 | 0.118158E+10 | 0.255336E+10 | 45252673.04 | 0.250811E+10 | 0.00 | 0.00 |
September | 0.175296E+10 | 0.201000E+10 | 0.189454E+10 | 469762.04 | 0.189407E+10 | 0.00 | 0.00 |
October | 0.670763E+09 | 0.314323E+10 | 0.145558E+10 | 0.00 | 0.145558E+10 | 0.00 | 0.00 |
November | 0.154062E+09 | 0.462565E+10 | 0.985350E+09 | 0.00 | 0.985350E+09 | 0.00 | 0.00 |
December | 560240.97 | 0.694315E+10 | 0.660462E+09 | 0.00 | 0.660462E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.171101E+11 | 0.420570E+11 | 0.225269E+11 | 0.650058E+09 | 0.218769E+11 | 0.00 | 0.00 |
Minimum of Months | 560240.97 | 0.100300E+10 | 0.660462E+09 | 0.00 | 0.660462E+09 | 0.00 | 0.00 |
Maximum of Months | 0.364031E+10 | 0.784007E+10 | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.611627E+09 | 0.471449E+10 | 0.138948E+10 | 0.571775E+09 | 0.817705E+09 | 0.00 | 0.00 |
February | 0.966129E+09 | 0.338869E+10 | 0.166351E+10 | 0.731481E+09 | 0.932034E+09 | 0.00 | 0.00 |
March | 0.192586E+10 | 0.250109E+10 | 0.250237E+10 | 0.993267E+09 | 0.150911E+10 | 0.00 | 0.00 |
April | 0.284666E+10 | 0.176952E+10 | 0.297356E+10 | 0.130222E+10 | 0.167134E+10 | 0.00 | 0.00 |
May | 0.430779E+10 | 0.113288E+10 | 0.385903E+10 | 0.168622E+10 | 0.217281E+10 | 0.00 | 0.00 |
June | 0.511186E+10 | 0.754508E+09 | 0.410977E+10 | 0.178974E+10 | 0.232003E+10 | 0.00 | 0.00 |
July | 0.547252E+10 | 0.677899E+09 | 0.429239E+10 | 0.198061E+10 | 0.231178E+10 | 0.00 | 0.00 |
August | 0.461730E+10 | 0.790765E+09 | 0.361840E+10 | 0.155997E+10 | 0.205843E+10 | 0.00 | 0.00 |
September | 0.366896E+10 | 0.129839E+10 | 0.312318E+10 | 0.147587E+10 | 0.164732E+10 | 0.00 | 0.00 |
October | 0.179881E+10 | 0.198114E+10 | 0.205665E+10 | 0.859048E+09 | 0.119760E+10 | 0.00 | 0.00 |
November | 0.614078E+09 | 0.286932E+10 | 0.117430E+10 | 0.381434E+09 | 0.792865E+09 | 0.00 | 0.00 |
December | 0.424545E+09 | 0.427617E+10 | 0.939944E+09 | 0.403635E+09 | 0.536309E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.323661E+11 | 0.261548E+11 | 0.317026E+11 | 0.137353E+11 | 0.179673E+11 | 0.00 | 0.00 |
Minimum of Months | 0.424545E+09 | 0.677899E+09 | 0.939944E+09 | 0.381434E+09 | 0.536309E+09 | 0.00 | 0.00 |
Maximum of Months | 0.547252E+10 | 0.471449E+10 | 0.429239E+10 | 0.198061E+10 | 0.232003E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.538869E+10 | 0.642641E+10 | 0.604891E+10 | 0.413940E+10 | 0.190951E+10 | 0.00 | 0.00 |
February | 0.543105E+10 | 0.471233E+10 | 0.585407E+10 | 0.395506E+10 | 0.189902E+10 | 0.00 | 0.00 |
March | 0.549276E+10 | 0.381236E+10 | 0.564018E+10 | 0.296993E+10 | 0.267025E+10 | 0.00 | 0.00 |
April | 0.533401E+10 | 0.280873E+10 | 0.491751E+10 | 0.229903E+10 | 0.261848E+10 | 0.00 | 0.00 |
May | 0.483193E+10 | 0.183197E+10 | 0.420979E+10 | 0.114133E+10 | 0.306846E+10 | 0.00 | 0.00 |
June | 0.506062E+10 | 0.120210E+10 | 0.395523E+10 | 0.805306E+09 | 0.314992E+10 | 0.00 | 0.00 |
July | 0.578772E+10 | 0.107604E+10 | 0.432645E+10 | 0.109015E+10 | 0.323630E+10 | 0.00 | 0.00 |
August | 0.662450E+10 | 0.127017E+10 | 0.487447E+10 | 0.174810E+10 | 0.312637E+10 | 0.00 | 0.00 |
September | 0.723299E+10 | 0.203912E+10 | 0.571629E+10 | 0.301201E+10 | 0.270427E+10 | 0.00 | 0.00 |
October | 0.682386E+10 | 0.303835E+10 | 0.616797E+10 | 0.386954E+10 | 0.229844E+10 | 0.00 | 0.00 |
November | 0.423693E+10 | 0.413073E+10 | 0.450361E+10 | 0.281934E+10 | 0.168426E+10 | 0.00 | 0.00 |
December | 0.473936E+10 | 0.599864E+10 | 0.496252E+10 | 0.375905E+10 | 0.120347E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.669844E+11 | 0.383469E+11 | 0.611770E+11 | 0.316083E+11 | 0.295687E+11 | 0.00 | 0.00 |
Minimum of Months | 0.423693E+10 | 0.107604E+10 | 0.395523E+10 | 0.805306E+09 | 0.120347E+10 | 0.00 | 0.00 |
Maximum of Months | 0.723299E+10 | 0.642641E+10 | 0.616797E+10 | 0.413940E+10 | 0.323630E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.636192E+09 | 0.483498E+10 | 0.137802E+10 | 0.557565E+09 | 0.820458E+09 | 0.00 | 0.00 |
February | 0.119981E+10 | 0.351517E+10 | 0.182508E+10 | 0.899346E+09 | 0.925736E+09 | 0.00 | 0.00 |
March | 0.183575E+10 | 0.258321E+10 | 0.241221E+10 | 0.897475E+09 | 0.151474E+10 | 0.00 | 0.00 |
April | 0.349004E+10 | 0.184420E+10 | 0.340519E+10 | 0.168381E+10 | 0.172138E+10 | 0.00 | 0.00 |
May | 0.395833E+10 | 0.119898E+10 | 0.352888E+10 | 0.140970E+10 | 0.211917E+10 | 0.00 | 0.00 |
June | 0.502273E+10 | 0.810154E+09 | 0.400715E+10 | 0.173660E+10 | 0.227055E+10 | 0.00 | 0.00 |
July | 0.573857E+10 | 0.741497E+09 | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.00 | 0.00 |
August | 0.504360E+10 | 0.851950E+09 | 0.388681E+10 | 0.178379E+10 | 0.210302E+10 | 0.00 | 0.00 |
September | 0.359955E+10 | 0.135797E+10 | 0.304477E+10 | 0.144521E+10 | 0.159957E+10 | 0.00 | 0.00 |
October | 0.203919E+10 | 0.206634E+10 | 0.219245E+10 | 0.974738E+09 | 0.121771E+10 | 0.00 | 0.00 |
November | 0.783957E+09 | 0.293878E+10 | 0.126999E+10 | 0.469642E+09 | 0.800349E+09 | 0.00 | 0.00 |
December | 0.552775E+09 | 0.437472E+10 | 0.100925E+10 | 0.475773E+09 | 0.533472E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.339005E+11 | 0.271179E+11 | 0.324057E+11 | 0.144455E+11 | 0.179602E+11 | 0.00 | 0.00 |
Minimum of Months | 0.552775E+09 | 0.741497E+09 | 0.100925E+10 | 0.469642E+09 | 0.533472E+09 | 0.00 | 0.00 |
Maximum of Months | 0.573857E+10 | 0.483498E+10 | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.592962E+10 | -0.516670E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -762924171.6 | 58.99 | 0.00 | 0.00 |
February | 0.546303E+10 | -0.479037E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -672657044.5 | 58.98 | 0.00 | 0.00 |
March | 0.633659E+10 | -0.561420E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -722393635.7 | 58.98 | 0.00 | 0.00 |
April | 0.554200E+10 | -0.485750E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -684493258.9 | 58.98 | 0.00 | 0.00 |
May | 0.559698E+10 | -0.490394E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -693037754.7 | 58.98 | 0.00 | 0.00 |
June | 0.520980E+10 | -0.454142E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668378202.0 | 58.99 | 0.00 | 0.00 |
July | 0.472414E+10 | -0.403674E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687399274.5 | 58.98 | 0.00 | 0.00 |
August | 0.503582E+10 | -0.434695E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688866913.1 | 58.98 | 0.00 | 0.00 |
September | 0.463449E+10 | -0.396705E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667435522.1 | 58.98 | 0.00 | 0.00 |
October | 0.500375E+10 | -0.430400E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -699754528.6 | 58.98 | 0.00 | 0.00 |
November | 0.522397E+10 | -0.452654E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -697433406.2 | 58.98 | 0.00 | 0.00 |
December | 0.552686E+10 | -0.478201E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -744842430.3 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.642270E+11 | -0.558374E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.838962E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.463449E+10 | -0.561420E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -762924171.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.633659E+10 | -0.396705E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -667435522.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.50 | 0.48 | 01-JAN-09:39 | 7173.57 | 37.33 | 205.17 | 243.67 | 5918.12 | 38.14 | 202.83 | 221.00 |
February | 226.83 | 0.50 | 0.48 | 01-FEB-07:00 | 8488.30 | 37.55 | 222.33 | 255.33 | 2483.37 | 28.91 | 193.33 | 237.67 |
March | 334.33 | 0.49 | 0.48 | 01-MAR-07:00 | 7738.37 | 30.40 | 270.33 | 327.00 | 1484.78 | 21.70 | 208.00 | 293.67 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:10 | 2331.30 | 19.15 | 9.50 | 346.67 | 1394.56 | 21.38 | 166.67 | 301.33 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:40 | 1795.27 | 18.76 | 0.00 | 395.33 | 1005.10 | 20.96 | 210.17 | 351.33 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-05:40 | 1829.58 | 19.00 | 0.00 | 396.00 | 1039.59 | 21.22 | 234.00 | 354.50 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:49 | 1900.00 | 19.30 | 2.33 | 406.00 | 1090.27 | 21.51 | 251.83 | 366.50 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:10 | 2109.23 | 19.20 | 3.17 | 378.67 | 1187.54 | 21.40 | 252.00 | 345.50 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 3065.24 | 20.95 | 46.50 | 332.67 | 1510.84 | 21.92 | 215.00 | 303.17 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-06:49 | 7307.99 | 33.26 | 293.33 | 305.83 | 1966.05 | 23.12 | 204.17 | 283.00 |
November | 254.83 | 0.50 | 0.48 | 01-NOV-07:49 | 5114.54 | 32.64 | 233.50 | 247.83 | 2785.27 | 31.00 | 227.67 | 226.00 |
December | 186.17 | 0.50 | 0.48 | 01-DEC-07:00 | 6237.10 | 36.22 | 168.83 | 219.17 | 5730.91 | 39.69 | 184.33 | 185.50 |
Annual Sum or Average | 3807.33 | 0.50 | 4126.55 | 25.32 | 1455.00 | 3854.17 | 1949.07 | 24.49 | 2550.00 | 3469.17 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1795.27 | 18.76 | 0.00 | 219.17 | 1005.10 | 20.96 | 166.67 | 185.50 | |
Maximum of Months | 428.67 | 0.50 | 0.48 | 8488.30 | 37.55 | 293.33 | 406.00 | 5918.12 | 39.69 | 252.00 | 366.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.51 | 0.48 | 01-JAN-09:39 | 1884.87 | 22.26 | 66.17 | 229.00 | 964.71 | 22.74 | 94.33 | 185.67 |
February | 226.83 | 0.51 | 0.48 | 01-FEB-07:49 | 2331.30 | 23.30 | 78.50 | 241.50 | 1290.26 | 23.97 | 95.67 | 205.50 |
March | 334.33 | 0.49 | 0.48 | 01-MAR-07:49 | 2957.87 | 21.74 | 103.33 | 320.83 | 1269.19 | 22.76 | 110.83 | 281.67 |
April | 285.17 | 0.50 | 0.48 | 01-APR-06:40 | 3481.23 | 21.43 | 77.33 | 347.67 | 2086.32 | 23.66 | 78.50 | 311.67 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-05:19 | 3633.41 | 22.20 | 136.33 | 403.00 | 1567.50 | 22.21 | 81.50 | 361.83 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-04:00 | 3284.43 | 20.96 | 95.67 | 404.50 | 1808.27 | 22.98 | 79.00 | 374.00 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 4146.90 | 22.47 | 123.33 | 414.33 | 1811.64 | 22.64 | 73.17 | 380.50 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:40 | 3295.14 | 21.25 | 110.83 | 381.00 | 1501.79 | 22.59 | 84.50 | 356.00 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-05:00 | 3330.24 | 22.26 | 95.17 | 330.33 | 1883.19 | 23.52 | 101.67 | 298.00 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-06:30 | 2087.77 | 20.97 | 88.67 | 291.67 | 1148.28 | 23.05 | 111.50 | 261.33 |
November | 254.83 | 0.51 | 0.48 | 01-NOV-07:40 | 1643.47 | 21.35 | 82.00 | 234.17 | 876.79 | 22.41 | 85.00 | 191.67 |
December | 186.17 | 0.52 | 0.48 | 01-DEC-07:00 | 1477.51 | 21.82 | 64.17 | 197.67 | 793.86 | 23.28 | 74.50 | 129.17 |
Annual Sum or Average | 3807.33 | 0.50 | 2972.75 | 21.79 | 1121.50 | 3795.67 | 1481.74 | 22.92 | 1070.17 | 3337.00 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1477.51 | 20.96 | 64.17 | 197.67 | 793.86 | 22.21 | 73.17 | 129.17 | |
Maximum of Months | 428.67 | 0.52 | 0.48 | 4146.90 | 23.30 | 136.33 | 414.33 | 2086.32 | 23.97 | 111.50 | 380.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.53 | 0.48 | 01-JAN-09:00 | 659.94 | 15.79 | 0.00 | 211.67 | 404.37 | 18.30 | 0.50 | 134.00 |
February | 226.83 | 0.53 | 0.48 | 01-FEB-08:00 | 695.93 | 16.16 | 0.00 | 226.50 | 434.22 | 18.63 | 0.00 | 164.67 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:09 | 943.38 | 17.67 | 0.00 | 317.67 | 550.12 | 19.88 | 8.00 | 263.67 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:10 | 1111.14 | 18.63 | 0.00 | 349.00 | 686.60 | 20.80 | 89.00 | 292.33 |
May | 428.67 | 0.49 | 0.48 | 01-MAY-05:00 | 1259.71 | 19.97 | 31.33 | 413.83 | 716.86 | 22.06 | 179.33 | 378.67 |
June | 400.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1522.18 | 22.72 | 96.50 | 413.83 | 890.45 | 24.08 | 266.67 | 392.17 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 1430.34 | 20.80 | 55.50 | 424.17 | 846.33 | 22.95 | 247.83 | 396.67 |
August | 410.83 | 0.49 | 0.48 | 01-AUG-05:49 | 1184.09 | 18.94 | 0.17 | 390.50 | 694.25 | 21.08 | 154.83 | 359.33 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 982.80 | 18.33 | 0.00 | 330.33 | 605.89 | 20.53 | 30.17 | 284.83 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-07:19 | 773.47 | 16.69 | 0.00 | 281.83 | 459.50 | 19.00 | 0.00 | 226.00 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-08:20 | 656.02 | 15.68 | 0.00 | 221.67 | 374.26 | 17.95 | 0.00 | 142.83 |
December | 186.17 | 0.55 | 0.48 | 01-DEC-09:09 | 481.23 | 14.36 | 0.00 | 172.33 | 304.10 | 17.03 | 0.00 | 65.17 |
Annual Sum or Average | 3807.33 | 0.50 | 1047.75 | 18.49 | 183.50 | 3753.33 | 620.83 | 20.65 | 976.33 | 3100.33 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 481.23 | 14.36 | 0.00 | 172.33 | 304.10 | 17.03 | 0.00 | 65.17 | |
Maximum of Months | 428.67 | 0.55 | 0.48 | 1522.18 | 22.72 | 96.50 | 424.17 | 890.45 | 24.08 | 266.67 | 396.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.51 | 0.48 | 01-JAN-09:50 | 2047.84 | 23.86 | 84.17 | 228.17 | 1187.38 | 24.35 | 94.50 | 185.17 |
February | 226.83 | 0.51 | 0.48 | 01-FEB-08:00 | 2333.26 | 21.49 | 63.33 | 239.83 | 1320.39 | 23.60 | 84.00 | 208.00 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:20 | 2532.25 | 21.43 | 94.50 | 323.17 | 1370.47 | 22.60 | 110.83 | 286.17 |
April | 285.17 | 0.50 | 0.48 | 02-APR-14:39 | 4544.84 | 22.41 | 84.50 | 349.83 | 1894.47 | 21.81 | 51.83 | 301.67 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:00 | 2718.55 | 17.76 | 50.50 | 402.67 | 1479.66 | 18.88 | 2.00 | 367.17 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-05:40 | 3474.50 | 18.23 | 50.33 | 405.50 | 1593.50 | 19.32 | 0.67 | 369.67 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:00 | 3857.60 | 18.72 | 56.00 | 412.33 | 1712.69 | 19.54 | 5.83 | 380.17 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:19 | 3239.17 | 20.13 | 84.67 | 386.33 | 1827.65 | 21.57 | 62.00 | 353.67 |
September | 326.50 | 0.49 | 0.48 | 01-SEP-06:49 | 3369.61 | 22.48 | 97.00 | 334.00 | 1985.55 | 23.86 | 90.50 | 301.67 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-07:30 | 2143.47 | 21.00 | 86.67 | 292.83 | 1171.44 | 22.87 | 97.50 | 260.33 |
November | 254.83 | 0.51 | 0.48 | 01-NOV-08:20 | 1697.18 | 21.16 | 83.83 | 235.50 | 924.62 | 22.10 | 78.00 | 194.33 |
December | 186.17 | 0.52 | 0.48 | 01-DEC-08:00 | 1555.45 | 20.81 | 55.00 | 201.17 | 891.44 | 22.91 | 64.17 | 126.33 |
Annual Sum or Average | 3807.33 | 0.50 | 2919.37 | 20.46 | 890.50 | 3811.33 | 1501.23 | 21.60 | 741.83 | 3334.33 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1555.45 | 17.76 | 50.33 | 201.17 | 891.44 | 18.88 | 0.67 | 126.33 | |
Maximum of Months | 428.67 | 0.52 | 0.48 | 4544.84 | 23.86 | 97.00 | 412.33 | 1985.55 | 24.35 | 110.83 | 380.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.50 | 0.48 | 01-JAN-09:39 | 6969.50 | 36.98 | 205.17 | 243.00 | 5762.31 | 37.76 | 200.17 | 219.33 |
February | 226.83 | 0.50 | 0.48 | 01-FEB-07:00 | 8300.74 | 37.32 | 222.33 | 254.33 | 2338.74 | 26.89 | 105.67 | 235.83 |
March | 334.33 | 0.49 | 0.48 | 01-MAR-07:00 | 7595.58 | 29.51 | 251.50 | 325.50 | 1382.71 | 18.89 | 14.33 | 290.83 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:10 | 2208.95 | 15.48 | 0.00 | 345.00 | 1304.34 | 19.03 | 29.50 | 296.00 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:40 | 1717.95 | 15.00 | 0.00 | 393.17 | 953.34 | 18.48 | 2.83 | 348.50 |
June | 400.67 | 0.51 | 0.48 | 01-JUN-05:40 | 1753.34 | 15.45 | 0.00 | 393.17 | 990.42 | 18.94 | 2.17 | 352.33 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:49 | 1818.04 | 15.77 | 0.00 | 404.67 | 1036.50 | 19.27 | 10.67 | 362.00 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:10 | 2011.48 | 15.52 | 0.00 | 376.17 | 1120.05 | 19.01 | 18.67 | 342.33 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 2927.44 | 17.47 | 26.00 | 330.83 | 1408.27 | 19.46 | 44.50 | 300.33 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-06:49 | 7158.20 | 32.70 | 290.83 | 304.00 | 1851.41 | 20.35 | 37.00 | 280.67 |
November | 254.83 | 0.50 | 0.48 | 01-NOV-07:49 | 4975.82 | 32.23 | 228.83 | 246.50 | 2682.88 | 29.91 | 184.83 | 224.50 |
December | 186.17 | 0.50 | 0.48 | 01-DEC-07:00 | 6046.15 | 35.39 | 167.50 | 217.33 | 5581.35 | 39.49 | 184.17 | 181.50 |
Annual Sum or Average | 3807.33 | 0.50 | 4002.77 | 22.94 | 1392.17 | 3833.67 | 1859.09 | 22.37 | 834.50 | 3434.17 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1717.95 | 15.00 | 0.00 | 217.33 | 953.34 | 18.48 | 2.17 | 181.50 | |
Maximum of Months | 428.67 | 0.51 | 0.48 | 8300.74 | 37.32 | 290.83 | 404.67 | 5762.31 | 39.49 | 200.17 | 362.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:39 | 1828.03 | 21.71 | 65.67 | 226.83 | 922.12 | 22.50 | 86.67 | 179.67 |
February | 226.83 | 0.51 | 0.48 | 01-FEB-07:49 | 2188.93 | 20.83 | 62.83 | 239.00 | 1239.91 | 23.76 | 89.17 | 203.00 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:49 | 2885.22 | 21.26 | 101.17 | 318.83 | 1212.62 | 22.56 | 94.50 | 279.00 |
April | 285.17 | 0.50 | 0.48 | 01-APR-06:49 | 3384.60 | 20.96 | 77.33 | 346.17 | 1974.74 | 22.63 | 64.67 | 308.00 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-05:19 | 3546.58 | 21.76 | 135.83 | 401.17 | 1500.37 | 22.02 | 79.50 | 358.00 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-04:00 | 3183.21 | 20.50 | 95.67 | 402.33 | 1720.22 | 22.19 | 68.33 | 368.50 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 4044.51 | 22.02 | 123.33 | 412.50 | 1736.99 | 22.47 | 70.83 | 376.83 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:40 | 3207.51 | 20.79 | 110.67 | 379.67 | 1434.73 | 22.41 | 77.50 | 353.17 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-05:00 | 3238.12 | 21.80 | 95.17 | 327.67 | 1810.53 | 23.32 | 91.00 | 294.83 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-06:40 | 2026.16 | 20.48 | 88.17 | 289.67 | 1100.56 | 22.84 | 98.33 | 258.67 |
November | 254.83 | 0.51 | 0.48 | 01-NOV-07:49 | 1598.34 | 20.89 | 81.17 | 231.67 | 843.16 | 22.01 | 76.83 | 186.17 |
December | 186.17 | 0.52 | 0.48 | 01-DEC-07:00 | 1432.91 | 21.33 | 64.00 | 193.17 | 732.51 | 21.81 | 64.00 | 123.67 |
Annual Sum or Average | 3807.33 | 0.50 | 2888.07 | 21.20 | 1101.00 | 3768.67 | 1415.29 | 22.52 | 961.33 | 3289.50 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1432.91 | 20.48 | 62.83 | 193.17 | 732.51 | 21.81 | 64.00 | 123.67 | |
Maximum of Months | 428.67 | 0.52 | 0.48 | 4044.51 | 22.02 | 135.83 | 412.50 | 1974.74 | 23.76 | 98.33 | 376.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.53 | 0.48 | 01-JAN-09:00 | 634.11 | 12.16 | 0.00 | 208.83 | 390.41 | 15.89 | 0.00 | 127.67 |
February | 226.83 | 0.53 | 0.48 | 01-FEB-09:09 | 669.88 | 12.67 | 0.00 | 224.83 | 420.40 | 16.38 | 0.00 | 159.00 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:09 | 910.06 | 14.15 | 0.00 | 315.00 | 531.70 | 17.63 | 0.00 | 257.83 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:10 | 1072.15 | 15.46 | 0.00 | 347.33 | 666.05 | 18.97 | 13.00 | 285.00 |
May | 428.67 | 0.49 | 0.48 | 01-MAY-06:40 | 1209.69 | 15.43 | 3.17 | 411.83 | 692.06 | 19.98 | 45.50 | 375.33 |
June | 400.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1457.50 | 19.31 | 75.50 | 412.50 | 859.04 | 22.28 | 111.83 | 390.67 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 1379.26 | 17.69 | 30.67 | 422.67 | 817.66 | 21.06 | 91.50 | 394.00 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1141.95 | 15.59 | 0.00 | 388.83 | 671.05 | 19.10 | 12.67 | 356.50 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 947.06 | 15.19 | 0.00 | 327.67 | 586.90 | 18.67 | 0.00 | 276.33 |
October | 325.17 | 0.52 | 0.48 | 01-OCT-07:19 | 745.30 | 13.11 | 0.00 | 279.00 | 444.10 | 16.68 | 0.00 | 219.83 |
November | 254.83 | 0.53 | 0.48 | 01-NOV-08:20 | 631.98 | 11.82 | 0.00 | 219.17 | 360.75 | 15.37 | 0.00 | 134.33 |
December | 186.17 | 0.55 | 0.48 | 01-DEC-09:50 | 461.95 | 10.47 | 0.00 | 166.00 | 293.89 | 14.39 | 0.00 | 58.50 |
Annual Sum or Average | 3807.33 | 0.51 | 1008.33 | 14.94 | 109.33 | 3723.67 | 600.00 | 18.54 | 274.50 | 3035.00 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 461.95 | 10.47 | 0.00 | 166.00 | 293.89 | 14.39 | 0.00 | 58.50 | |
Maximum of Months | 428.67 | 0.55 | 0.48 | 1457.50 | 19.31 | 75.50 | 422.67 | 859.04 | 22.28 | 111.83 | 394.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:50 | 1992.72 | 23.50 | 84.17 | 226.33 | 1144.95 | 24.27 | 93.83 | 179.17 |
February | 226.83 | 0.51 | 0.48 | 01-FEB-09:09 | 2262.91 | 21.08 | 63.33 | 238.00 | 1264.79 | 23.51 | 82.00 | 205.33 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:20 | 2465.63 | 21.02 | 94.00 | 320.50 | 1318.44 | 22.47 | 105.67 | 282.33 |
April | 285.17 | 0.50 | 0.48 | 02-APR-14:39 | 4342.73 | 21.97 | 84.50 | 347.83 | 1810.44 | 21.67 | 49.33 | 296.33 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:00 | 2637.20 | 17.26 | 49.83 | 400.83 | 1419.11 | 18.70 | 0.50 | 364.17 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-05:49 | 3334.18 | 17.74 | 50.33 | 403.33 | 1519.64 | 19.14 | 0.00 | 367.17 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:00 | 3749.51 | 18.23 | 56.00 | 410.50 | 1630.93 | 19.37 | 3.67 | 378.17 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:19 | 3146.76 | 19.67 | 84.50 | 384.00 | 1747.67 | 21.42 | 59.83 | 351.00 |
September | 326.50 | 0.49 | 0.48 | 01-SEP-06:49 | 3281.62 | 22.06 | 97.00 | 332.67 | 1882.86 | 23.72 | 87.50 | 298.00 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-07:30 | 2059.45 | 20.28 | 83.00 | 290.50 | 1120.33 | 22.76 | 95.67 | 257.50 |
November | 254.83 | 0.51 | 0.48 | 01-NOV-08:30 | 1598.00 | 19.49 | 70.17 | 233.00 | 888.57 | 21.99 | 77.33 | 190.83 |
December | 186.17 | 0.52 | 0.48 | 01-DEC-09:09 | 1509.96 | 20.40 | 55.00 | 198.83 | 855.64 | 22.83 | 63.17 | 120.67 |
Annual Sum or Average | 3807.33 | 0.50 | 2821.85 | 19.91 | 871.83 | 3786.33 | 1435.22 | 21.47 | 718.50 | 3290.67 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1509.96 | 17.26 | 49.83 | 198.83 | 855.64 | 18.70 | 0.00 | 120.67 | |
Maximum of Months | 428.67 | 0.52 | 0.48 | 4342.73 | 23.50 | 97.00 | 410.50 | 1882.86 | 24.27 | 105.67 | 378.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.50 | 0.48 | 01-JAN-09:39 | 6969.51 | 36.98 | 205.17 | 243.00 | 5762.19 | 37.76 | 200.17 | 219.33 |
February | 226.83 | 0.50 | 0.48 | 01-FEB-07:00 | 8300.71 | 37.32 | 222.33 | 254.33 | 2338.62 | 26.89 | 105.67 | 235.83 |
March | 334.33 | 0.49 | 0.48 | 01-MAR-07:00 | 7595.45 | 29.51 | 251.50 | 325.50 | 1382.60 | 18.89 | 14.33 | 290.83 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:10 | 2208.84 | 15.48 | 0.00 | 345.00 | 1304.25 | 19.03 | 29.67 | 296.00 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:40 | 1717.85 | 15.00 | 0.00 | 393.17 | 953.26 | 18.48 | 2.83 | 348.50 |
June | 400.67 | 0.51 | 0.48 | 01-JUN-05:40 | 1753.25 | 15.46 | 0.00 | 393.17 | 990.35 | 18.94 | 2.17 | 352.33 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:49 | 1817.94 | 15.78 | 0.00 | 404.67 | 1036.42 | 19.27 | 10.67 | 362.00 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:10 | 2011.36 | 15.53 | 0.00 | 376.17 | 1119.96 | 19.01 | 18.67 | 342.33 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 2927.32 | 17.47 | 26.00 | 330.83 | 1408.17 | 19.46 | 44.50 | 300.33 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-06:49 | 7158.12 | 32.70 | 290.83 | 304.00 | 1851.31 | 20.35 | 37.17 | 280.67 |
November | 254.83 | 0.50 | 0.48 | 01-NOV-07:49 | 4975.78 | 32.24 | 228.83 | 246.50 | 2682.78 | 29.91 | 184.83 | 224.50 |
December | 186.17 | 0.50 | 0.48 | 01-DEC-07:00 | 6046.18 | 35.39 | 167.50 | 217.33 | 5581.28 | 39.49 | 184.17 | 181.50 |
Annual Sum or Average | 3807.33 | 0.50 | 4002.69 | 22.94 | 1392.17 | 3833.67 | 1858.99 | 22.37 | 834.83 | 3434.17 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1717.85 | 15.00 | 0.00 | 217.33 | 953.26 | 18.48 | 2.17 | 181.50 | |
Maximum of Months | 428.67 | 0.51 | 0.48 | 8300.71 | 37.32 | 290.83 | 404.67 | 5762.19 | 39.49 | 200.17 | 362.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:39 | 1828.01 | 21.71 | 65.67 | 226.83 | 922.08 | 22.50 | 86.83 | 179.67 |
February | 226.83 | 0.51 | 0.48 | 01-FEB-07:49 | 2188.91 | 20.83 | 62.83 | 239.00 | 1239.86 | 23.76 | 89.17 | 203.00 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:49 | 2885.16 | 21.26 | 101.17 | 318.83 | 1212.55 | 22.56 | 94.50 | 279.00 |
April | 285.17 | 0.50 | 0.48 | 01-APR-06:49 | 3384.56 | 20.96 | 77.33 | 346.17 | 1974.67 | 22.63 | 64.67 | 308.00 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-05:19 | 3546.50 | 21.76 | 135.83 | 401.17 | 1500.29 | 22.02 | 79.50 | 358.00 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-04:00 | 3183.14 | 20.50 | 95.67 | 402.33 | 1720.13 | 22.19 | 68.33 | 368.50 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 4044.45 | 22.02 | 123.33 | 412.50 | 1736.91 | 22.47 | 71.00 | 376.83 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:40 | 3207.45 | 20.79 | 110.67 | 379.67 | 1434.65 | 22.41 | 77.67 | 353.17 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-05:00 | 3238.09 | 21.80 | 95.17 | 327.67 | 1810.45 | 23.32 | 91.00 | 294.83 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-06:40 | 2026.12 | 20.48 | 88.17 | 289.67 | 1100.50 | 22.84 | 98.50 | 258.67 |
November | 254.83 | 0.51 | 0.48 | 01-NOV-07:49 | 1598.30 | 20.90 | 81.17 | 231.67 | 843.11 | 22.01 | 76.83 | 186.17 |
December | 186.17 | 0.52 | 0.48 | 01-DEC-07:00 | 1432.90 | 21.33 | 64.00 | 193.17 | 732.48 | 21.81 | 64.00 | 123.67 |
Annual Sum or Average | 3807.33 | 0.50 | 2888.03 | 21.20 | 1101.00 | 3768.67 | 1415.22 | 22.52 | 962.00 | 3289.50 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1432.90 | 20.48 | 62.83 | 193.17 | 732.48 | 21.81 | 64.00 | 123.67 | |
Maximum of Months | 428.67 | 0.52 | 0.48 | 4044.45 | 22.02 | 135.83 | 412.50 | 1974.67 | 23.76 | 98.50 | 376.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.53 | 0.48 | 01-JAN-09:00 | 634.10 | 12.17 | 0.00 | 208.83 | 390.39 | 15.89 | 0.00 | 127.67 |
February | 226.83 | 0.53 | 0.48 | 01-FEB-09:09 | 669.87 | 12.67 | 0.00 | 224.83 | 420.38 | 16.38 | 0.00 | 159.00 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:09 | 910.02 | 14.15 | 0.00 | 315.00 | 531.66 | 17.63 | 0.00 | 257.83 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:10 | 1072.12 | 15.46 | 0.00 | 347.33 | 666.01 | 18.97 | 13.00 | 285.00 |
May | 428.67 | 0.49 | 0.48 | 01-MAY-06:40 | 1209.64 | 15.43 | 3.17 | 411.83 | 692.01 | 19.98 | 45.50 | 375.33 |
June | 400.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1457.46 | 19.32 | 75.50 | 412.50 | 858.98 | 22.28 | 112.00 | 390.67 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 1379.22 | 17.69 | 30.67 | 422.67 | 817.61 | 21.06 | 91.50 | 394.00 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1141.91 | 15.59 | 0.00 | 388.83 | 671.00 | 19.10 | 12.67 | 356.50 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 947.04 | 15.19 | 0.00 | 327.67 | 586.87 | 18.67 | 0.00 | 276.33 |
October | 325.17 | 0.52 | 0.48 | 01-OCT-07:19 | 745.27 | 13.11 | 0.00 | 279.00 | 444.07 | 16.68 | 0.00 | 219.83 |
November | 254.83 | 0.53 | 0.48 | 01-NOV-08:20 | 631.95 | 11.82 | 0.00 | 219.17 | 360.72 | 15.37 | 0.00 | 134.33 |
December | 186.17 | 0.55 | 0.48 | 01-DEC-09:50 | 461.94 | 10.47 | 0.00 | 166.00 | 293.88 | 14.39 | 0.00 | 58.50 |
Annual Sum or Average | 3807.33 | 0.51 | 1008.30 | 14.94 | 109.33 | 3723.67 | 599.96 | 18.54 | 274.67 | 3035.00 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 461.94 | 10.47 | 0.00 | 166.00 | 293.88 | 14.39 | 0.00 | 58.50 | |
Maximum of Months | 428.67 | 0.55 | 0.48 | 1457.46 | 19.32 | 75.50 | 422.67 | 858.98 | 22.28 | 112.00 | 394.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:50 | 1992.70 | 23.50 | 84.17 | 226.33 | 1144.90 | 24.27 | 93.83 | 179.17 |
February | 226.83 | 0.51 | 0.48 | 01-FEB-09:09 | 2262.89 | 21.08 | 63.33 | 238.00 | 1264.74 | 23.51 | 82.00 | 205.33 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:20 | 2465.57 | 21.02 | 94.00 | 320.50 | 1318.37 | 22.48 | 105.67 | 282.33 |
April | 285.17 | 0.50 | 0.48 | 02-APR-14:39 | 4342.69 | 21.98 | 84.50 | 347.83 | 1810.36 | 21.67 | 49.33 | 296.33 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:00 | 2637.14 | 17.26 | 49.83 | 400.83 | 1419.04 | 18.70 | 0.50 | 364.17 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-05:49 | 3334.11 | 17.74 | 50.33 | 403.33 | 1519.56 | 19.14 | 0.00 | 367.17 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:00 | 3749.44 | 18.23 | 56.00 | 410.50 | 1630.84 | 19.37 | 3.67 | 378.17 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:19 | 3146.70 | 19.68 | 84.50 | 384.00 | 1747.59 | 21.42 | 59.83 | 351.00 |
September | 326.50 | 0.49 | 0.48 | 01-SEP-06:49 | 3281.59 | 22.06 | 97.00 | 332.67 | 1882.79 | 23.72 | 87.50 | 298.00 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-07:30 | 2059.41 | 20.28 | 83.00 | 290.50 | 1120.27 | 22.76 | 95.67 | 257.50 |
November | 254.83 | 0.51 | 0.48 | 01-NOV-08:30 | 1597.96 | 19.49 | 70.17 | 233.00 | 888.52 | 21.99 | 77.33 | 190.83 |
December | 186.17 | 0.52 | 0.48 | 01-DEC-09:09 | 1509.95 | 20.40 | 55.00 | 198.83 | 855.61 | 22.83 | 63.17 | 120.67 |
Annual Sum or Average | 3807.33 | 0.50 | 2821.80 | 19.91 | 871.83 | 3786.33 | 1435.15 | 21.47 | 718.50 | 3290.67 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1509.95 | 17.26 | 49.83 | 198.83 | 855.61 | 18.70 | 0.00 | 120.67 | |
Maximum of Months | 428.67 | 0.52 | 0.48 | 4342.69 | 23.50 | 97.00 | 410.50 | 1882.79 | 24.27 | 105.67 | 378.17 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105829E+10 | 20294.53 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.358170E+09 | 20294.53 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8275752.06 | 20294.53 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 69553606.87 | 20294.53 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.191745E+09 | 20294.53 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105829E+10 | 20294.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115140E+11 | 13551.54 | 31-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.778558E+10 | 15143.84 | 02-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.584685E+10 | 11714.62 | 20-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.297799E+10 | 11826.03 | 19-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.710764E+09 | 11721.89 | 18-MAY-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.234560E+09 | 11403.44 | 02-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3951228.32 | 3950.30 | 24-JUL-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33685592.18 | 10000.11 | 16-AUG-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.492952E+09 | 11918.45 | 19-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133204E+10 | 11713.48 | 25-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.460027E+10 | 11759.10 | 20-NOV-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.870839E+10 | 12327.36 | 09-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.442411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3951228.32 | 3950.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.115140E+11 | 15143.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.571131E+10 | 11257.05 | 31-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.348603E+10 | 12007.29 | 02-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158032E+10 | 9816.51 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.486194E+09 | 9809.47 | 29-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 398460.82 | 2596.16 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 655697.52 | 1368.72 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19962545.25 | 8281.78 | 27-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147493E+10 | 9809.91 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.374029E+10 | 10342.40 | 09-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.571131E+10 | 12007.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.956384E+10 | 9522.82 | 31-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.645314E+10 | 10641.98 | 02-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.348419E+10 | 8239.51 | 30-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119643E+10 | 8243.42 | 24-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31300320.02 | 8196.26 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8468795.85 | 7300.50 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115924E+09 | 8205.55 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.261951E+10 | 8224.24 | 20-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.627197E+10 | 8660.44 | 09-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.297448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.956384E+10 | 10641.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.591390E+10 | 11794.28 | 30-JAN-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.358495E+10 | 12134.39 | 02-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176032E+10 | 10463.55 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.438839E+09 | 10456.05 | 29-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8062378.30 | 6908.91 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5394708.32 | 4926.51 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26646899.66 | 8598.74 | 16-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151521E+10 | 10456.52 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379238E+10 | 11024.10 | 09-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.591390E+10 | 12134.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.573730E+10 | 28520.54 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285580E+10 | 28520.54 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.926697E+09 | 28520.54 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174626E+09 | 28520.54 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157803E+10 | 28520.54 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.344274E+10 | 28520.54 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.573730E+10 | 28520.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.615209E+10 | 14753.83 | 31-JAN-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.328421E+10 | 17385.66 | 02-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163587E+10 | 13480.34 | 02-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.430402E+09 | 13511.60 | 03-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3920311.56 | 7531.18 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12296677.98 | 11063.52 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112240E+09 | 13331.54 | 27-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210947E+10 | 13557.31 | 20-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.491431E+10 | 13515.57 | 04-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.615209E+10 | 17385.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.554736E+10 | 11979.71 | 30-JAN-13:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.302858E+10 | 12738.51 | 02-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122453E+10 | 11807.51 | 14-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.281663E+09 | 11789.57 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 296755.35 | 1978.37 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7611129.28 | 7116.57 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 98578987.36 | 11745.62 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183555E+10 | 11869.55 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.403092E+10 | 11898.54 | 30-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.554736E+10 | 12738.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.940354E+10 | 9649.39 | 30-JAN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.565814E+10 | 11317.12 | 02-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.251364E+10 | 8821.30 | 10-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.586217E+09 | 8809.86 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4459534.68 | 8159.38 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20565245.09 | 8711.94 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.225765E+09 | 8771.97 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.315925E+10 | 8825.03 | 20-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.673372E+10 | 8797.90 | 04-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.283053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.940354E+10 | 11317.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.579427E+10 | 12269.18 | 05-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.325402E+10 | 12868.63 | 02-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140305E+10 | 12236.81 | 14-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.298727E+09 | 12218.23 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3155072.42 | 5814.23 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15172997.07 | 7231.26 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118084E+09 | 12172.66 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193314E+10 | 12289.33 | 20-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.418725E+10 | 12287.37 | 29-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.579427E+10 | 12868.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123761E+11 | 32415.03 | 31-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.776522E+10 | 35171.61 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.350971E+10 | 31921.24 | 10-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.890997E+09 | 31867.32 | 03-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3375.62 | 22.50 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21174147.60 | 29231.39 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.313426E+09 | 31806.11 | 10-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.471837E+10 | 32019.39 | 20-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.934515E+10 | 31905.32 | 05-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.389401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123761E+11 | 35171.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.966090E+10 | 15837.20 | 19-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.573243E+10 | 18465.38 | 02-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.320237E+10 | 14767.45 | 13-MAR-04:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109079E+10 | 14785.91 | 03-APR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33232364.97 | 14650.70 | 02-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1059249.77 | 644.45 | 03-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 95779201.42 | 14681.06 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.568180E+09 | 14758.71 | 23-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.390765E+10 | 14804.88 | 16-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.796343E+10 | 14770.43 | 14-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.322558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.966090E+10 | 18465.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.823255E+10 | 12290.04 | 31-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.497832E+10 | 13682.83 | 02-FEB-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.231465E+10 | 12069.68 | 18-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.706474E+09 | 12009.54 | 22-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6571736.46 | 11263.51 | 02-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 181162.34 | 213.24 | 05-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 59052042.82 | 11952.16 | 29-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.451051E+09 | 12006.40 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.325174E+10 | 12035.24 | 24-NOV-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.644034E+10 | 12035.39 | 27-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.264409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.823255E+10 | 13682.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.135684E+11 | 12664.75 | 31-JAN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.882957E+10 | 14300.35 | 02-FEB-08:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.455323E+10 | 11161.81 | 14-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140932E+10 | 11152.22 | 03-APR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 37828564.06 | 11079.20 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1431670.90 | 836.10 | 05-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.160638E+09 | 11136.30 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106422E+10 | 11192.37 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.544642E+10 | 11202.23 | 20-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104476E+11 | 11160.04 | 30-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.455186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.135684E+11 | 14300.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.848058E+10 | 13524.82 | 31-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.522045E+10 | 14674.90 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.259260E+10 | 13282.32 | 18-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.750453E+09 | 13171.62 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24061598.66 | 11840.66 | 02-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1028934.59 | 464.64 | 05-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 93829432.38 | 13152.99 | 29-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.546501E+09 | 13212.68 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.332486E+10 | 13237.76 | 20-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.654290E+10 | 13244.59 | 27-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.275773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.848058E+10 | 14674.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.318561E+11 | 38238.80 | 05-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.208356E+11 | 38238.80 | 01-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130373E+11 | 28614.36 | 06-MAR-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.510077E+10 | 22567.23 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.234267E+09 | 8241.33 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17717756.49 | 2761.81 | 03-JUN-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17400.00 | 203.00 | 07-AUG-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.385902E+09 | 10217.35 | 29-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.255800E+10 | 14256.03 | 23-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112532E+11 | 35463.99 | 25-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231626E+11 | 38238.80 | 09-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108442E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.318561E+11 | 38238.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.300854E+11 | 40693.17 | 06-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.205507E+11 | 40693.17 | 01-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130275E+11 | 27553.70 | 06-MAR-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.580832E+10 | 21417.09 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.380565E+09 | 8536.91 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 58104496.03 | 3525.76 | 03-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 359776.40 | 1080.01 | 07-AUG-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.654004E+09 | 10807.52 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.376956E+10 | 16046.82 | 23-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114675E+11 | 33683.49 | 25-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.224268E+11 | 39825.58 | 09-DEC-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108229E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.300854E+11 | 40693.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.345316E+11 | 39572.31 | 05-JAN-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.226205E+11 | 39572.31 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139813E+11 | 27705.63 | 08-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.623134E+10 | 20168.41 | 03-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.467640E+09 | 11340.79 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108562E+09 | 4552.79 | 03-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4415937.03 | 2270.31 | 07-AUG-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.852249E+09 | 13856.20 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.424913E+10 | 16974.34 | 23-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130031E+11 | 33839.77 | 25-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.255584E+11 | 39572.31 | 08-DEC-20:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.345316E+11 | 39572.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.141979E+09 | 0.118834E+09 | 6448.73 | 25-MAR-15:00 | 5362.40 | 0.00 |
April | 0.00 | 0.00 | 0.554554E+10 | 0.430183E+10 | 67503.89 | 18-APR-12:00 | 47439.04 | 0.00 |
May | 0.00 | 0.00 | 0.141229E+11 | 0.107292E+11 | 65922.52 | 30-MAY-11:30 | 44625.02 | 0.00 |
June | 0.00 | 0.00 | 0.435658E+11 | 0.323165E+11 | 122233.27 | 26-JUN-07:50 | 54964.75 | 0.00 |
July | 0.00 | 0.00 | 0.621357E+11 | 0.419866E+11 | 114537.02 | 03-JUL-08:50 | 53373.50 | 0.00 |
August | 0.00 | 0.00 | 0.612117E+11 | 0.424231E+11 | 123436.53 | 03-AUG-05:12 | 41208.46 | 0.00 |
September | 0.00 | 0.00 | 0.257782E+11 | 0.228684E+11 | 98890.19 | 11-SEP-09:50 | 59070.32 | 0.00 |
October | 0.00 | 0.00 | 0.312270E+10 | 0.289549E+10 | 35857.49 | 20-OCT-15:10 | 35857.49 | 0.00 |
November | 0.00 | 0.00 | 0.537030E+09 | 0.459424E+09 | 11389.69 | 02-NOV-16:00 | 9140.77 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.216162E+12 | 0.158099E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.621357E+11 | 0.424231E+11 | 123436.53 | 59070.32 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.130662E+09 | 0.111197E+09 | 7236.76 | 25-MAR-15:00 | 6685.79 | 0.00 |
April | 0.00 | 0.00 | 0.537236E+10 | 0.420460E+10 | 67233.36 | 18-APR-12:30 | 48230.40 | 0.00 |
May | 0.00 | 0.00 | 0.141140E+11 | 0.105411E+11 | 69018.97 | 30-MAY-11:00 | 43176.67 | 0.00 |
June | 0.00 | 0.00 | 0.415214E+11 | 0.308199E+11 | 113123.68 | 26-JUN-07:55 | 51437.11 | 0.00 |
July | 0.00 | 0.00 | 0.565295E+11 | 0.381368E+11 | 111042.27 | 03-JUL-08:50 | 52484.45 | 0.00 |
August | 0.00 | 0.00 | 0.527267E+11 | 0.365314E+11 | 114057.33 | 03-AUG-05:12 | 38751.26 | 0.00 |
September | 0.00 | 0.00 | 0.211845E+11 | 0.186731E+11 | 83330.58 | 11-SEP-09:50 | 50019.61 | 0.00 |
October | 0.00 | 0.00 | 0.120719E+10 | 0.101446E+10 | 28277.38 | 20-OCT-15:00 | 28277.38 | 0.00 |
November | 0.00 | 0.00 | 67165409.18 | 57193255.32 | 6232.12 | 03-NOV-13:30 | 5137.06 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.192853E+12 | 0.140090E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.565295E+11 | 0.381368E+11 | 114057.33 | 52484.45 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1244192.58 | 1031086.39 | 502.44 | 24-FEB-15:00 | 421.07 | 0.00 |
March | 0.00 | 0.00 | 0.133319E+09 | 0.109127E+09 | 7304.54 | 25-MAR-15:00 | 6383.46 | 0.00 |
April | 0.00 | 0.00 | 0.588042E+10 | 0.459291E+10 | 78769.02 | 16-APR-14:12 | 50386.10 | 0.00 |
May | 0.00 | 0.00 | 0.149736E+11 | 0.112824E+11 | 71367.65 | 30-MAY-14:00 | 61762.50 | 0.00 |
June | 0.00 | 0.00 | 0.441077E+11 | 0.332096E+11 | 122240.96 | 26-JUN-06:03 | 49550.83 | 0.00 |
July | 0.00 | 0.00 | 0.594596E+11 | 0.402734E+11 | 111089.26 | 05-JUL-11:00 | 58895.41 | 0.00 |
August | 0.00 | 0.00 | 0.541658E+11 | 0.381069E+11 | 127039.91 | 04-AUG-06:03 | 37505.96 | 0.00 |
September | 0.00 | 0.00 | 0.218106E+11 | 0.191698E+11 | 83202.05 | 11-SEP-10:00 | 51478.43 | 0.00 |
October | 0.00 | 0.00 | 0.116042E+10 | 0.951269E+09 | 27366.14 | 20-OCT-15:00 | 27366.14 | 0.00 |
November | 0.00 | 0.00 | 37655492.14 | 31975010.38 | 3503.77 | 03-NOV-14:00 | 3053.67 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.201730E+12 | 0.147728E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.594596E+11 | 0.402734E+11 | 127039.91 | 61762.50 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 2081.29 | 7364.10 | 31-JAN-12:11 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 2132.47 | 7412.43 | 16-FEB-12:07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2251.76 | 7403.84 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2026.24 | 7194.41 | 03-APR-11:14 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1984.95 | 6836.76 | 02-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1908.48 | 6393.54 | 01-JUN-11:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1658.51 | 5962.02 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1779.55 | 5744.10 | 01-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1683.42 | 5903.01 | 28-SEP-11:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1760.05 | 6255.23 | 31-OCT-11:13 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1900.33 | 6701.19 | 30-NOV-12:14 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1936.45 | 7085.62 | 29-DEC-12:14 |
Annual Sum or Average | 0.00 | 1924.09 | ||||
Minimum of Months | 0.00 | 0.00 | 1658.51 | 5744.10 | ||
Maximum of Months | 0.00 | 0.00 | 2251.76 | 7412.43 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.176357E+10 | 0.42 | 2821.59 | 02-JAN-05:01 | 0.84 |
February | 0.135533E+10 | 0.38 | 2821.59 | 01-FEB-07:01 | 0.85 |
March | 0.145488E+10 | 0.36 | 2821.59 | 06-MAR-07:01 | 0.85 |
April | 0.172342E+10 | 0.35 | 6487.72 | 18-APR-15:10 | 1.36 |
May | 0.254942E+10 | 0.39 | 7180.12 | 31-MAY-15:10 | 1.45 |
June | 0.456982E+10 | 0.52 | 11563.29 | 26-JUN-06:03 | 1.95 |
July | 0.536196E+10 | 0.55 | 10761.96 | 03-JUL-15:10 | 1.87 |
August | 0.567431E+10 | 0.57 | 11563.29 | 03-AUG-06:03 | 1.95 |
September | 0.369835E+10 | 0.46 | 11563.29 | 11-SEP-06:03 | 1.96 |
October | 0.174042E+10 | 0.33 | 3994.98 | 20-OCT-15:30 | 1.02 |
November | 0.146597E+10 | 0.35 | 2883.95 | 03-NOV-15:10 | 0.85 |
December | 0.146745E+10 | 0.38 | 2821.59 | 11-DEC-06:01 | 0.85 |
Annual Sum or Average | 0.328249E+11 | 0.42 | |||
Minimum of Months | 0.135533E+10 | 0.33 | 2821.59 | 0.84 | |
Maximum of Months | 0.567431E+10 | 0.57 | 11563.29 | 1.96 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.174314E+10 | 0.45 | 2836.96 | 03-JAN-07:01 | 0.91 |
February | 0.126838E+10 | 0.38 | 2836.96 | 02-FEB-07:01 | 0.91 |
March | 0.128728E+10 | 0.36 | 2836.96 | 02-MAR-07:01 | 0.91 |
April | 0.161560E+10 | 0.36 | 8101.10 | 18-APR-15:00 | 1.68 |
May | 0.244286E+10 | 0.41 | 8387.60 | 30-MAY-14:05 | 1.72 |
June | 0.439993E+10 | 0.54 | 10381.96 | 12-JUN-06:03 | 1.97 |
July | 0.481136E+10 | 0.55 | 10381.96 | 05-JUL-06:03 | 1.97 |
August | 0.472475E+10 | 0.54 | 10381.96 | 03-AUG-06:03 | 1.96 |
September | 0.289331E+10 | 0.43 | 9611.86 | 07-SEP-16:00 | 1.87 |
October | 0.124774E+10 | 0.32 | 3123.44 | 20-OCT-15:10 | 0.95 |
November | 0.121977E+10 | 0.35 | 2836.96 | 21-NOV-07:01 | 0.91 |
December | 0.143240E+10 | 0.39 | 2836.96 | 06-DEC-07:01 | 0.91 |
Annual Sum or Average | 0.290865E+11 | 0.42 | |||
Minimum of Months | 0.121977E+10 | 0.32 | 2836.96 | 0.91 | |
Maximum of Months | 0.481136E+10 | 0.55 | 10381.96 | 1.97 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.223410E+10 | 0.52 | 2807.50 | 04-JAN-07:01 | 0.83 |
February | 0.172442E+10 | 0.48 | 2807.50 | 18-FEB-07:03 | 0.83 |
March | 0.154200E+10 | 0.41 | 2807.50 | 03-MAR-07:01 | 0.83 |
April | 0.169530E+10 | 0.39 | 7659.64 | 18-APR-15:00 | 1.48 |
May | 0.235167E+10 | 0.41 | 8278.27 | 30-MAY-15:20 | 1.55 |
June | 0.415450E+10 | 0.50 | 11866.19 | 26-JUN-06:03 | 1.95 |
July | 0.443459E+10 | 0.50 | 10229.14 | 03-JUL-15:20 | 1.78 |
August | 0.426733E+10 | 0.49 | 10833.14 | 04-AUG-15:20 | 1.84 |
September | 0.259160E+10 | 0.42 | 9276.14 | 07-SEP-16:00 | 1.67 |
October | 0.130180E+10 | 0.34 | 2807.50 | 16-OCT-05:01 | 0.83 |
November | 0.158121E+10 | 0.43 | 2807.50 | 16-NOV-07:02 | 0.83 |
December | 0.194088E+10 | 0.48 | 2807.50 | 02-DEC-06:02 | 0.83 |
Annual Sum or Average | 0.298194E+11 | 0.45 | |||
Minimum of Months | 0.130180E+10 | 0.34 | 2807.50 | 0.83 | |
Maximum of Months | 0.443459E+10 | 0.52 | 11866.19 | 1.95 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:03 | 2.06 | 2.06 | 57.15 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 56.27 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 56.38 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:01 | 2.06 | 2.06 | 55.39 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:05 | 2.06 | 2.06 | 56.06 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 55.85 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 55.63 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 55.81 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 56.34 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.02 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 56.48 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:01 | 2.06 | 2.06 | 56.72 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 55.39 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.15 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 56.95 | 56.95 | 2081.29 | 7364.10 | 31-JAN-12:11 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 56.71 | 56.71 | 2132.47 | 7412.43 | 16-FEB-12:07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.85 | 56.85 | 2251.76 | 7403.84 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 55.90 | 55.90 | 2026.24 | 7194.41 | 03-APR-11:14 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.94 | 56.94 | 1984.95 | 6836.76 | 02-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.35 | 56.35 | 1908.48 | 6393.54 | 01-JUN-11:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.14 | 56.14 | 1658.51 | 5962.02 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.23 | 56.23 | 1779.55 | 5744.10 | 01-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.78 | 56.78 | 1683.42 | 5903.01 | 28-SEP-11:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.47 | 56.47 | 1760.05 | 6255.23 | 31-OCT-11:13 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.05 | 57.05 | 1900.33 | 6701.19 | 30-NOV-12:14 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.11 | 57.11 | 1936.45 | 7085.62 | 29-DEC-12:14 |
Annual Sum or Average | 0.00 | 1924.09 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.90 | 55.90 | 1658.51 | 5744.10 | ||
Maximum of Months | 0.00 | 0.00 | 57.11 | 57.11 | 2251.76 | 7412.43 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.355249E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.230232E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.141755E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.825863E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.689718E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.155954E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.203299E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.205360E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.107325E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.407566E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.118951E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.241722E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.195216E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.407566E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.355249E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.343777E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.193491E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.902840E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.475483E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.603058E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.146670E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.184374E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.175431E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.831602E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.212695E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.118543E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.247413E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.171227E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.212695E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.343777E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.545526E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.342508E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.177528E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.804151E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.625941E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.151061E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.188153E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.175170E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.858796E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.456072E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.222412E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.426802E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.250366E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.456072E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.545526E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.176357E+10 | 0.00 | 0.656175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135533E+10 | 0.00 | 0.425035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145488E+10 | 0.141979E+09 | 0.257172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172342E+10 | 0.554554E+10 | 0.102002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.254942E+10 | 0.141229E+11 | 0.984792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.456982E+10 | 0.435658E+11 | 0.252278E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.536196E+10 | 0.621357E+11 | 3951228.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.567431E+10 | 0.612117E+11 | 33702992.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.369835E+10 | 0.257782E+11 | 0.893373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174042E+10 | 0.312270E+10 | 0.405257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146597E+10 | 0.537030E+09 | 0.215327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146745E+10 | 0.00 | 0.458674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.328249E+11 | 0.216162E+12 | 0.217659E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135533E+10 | 0.00 | 3951228.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.567431E+10 | 0.621357E+11 | 0.656175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.174314E+10 | 0.00 | 0.627200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126838E+10 | 0.00 | 0.386314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128728E+10 | 0.130662E+09 | 0.207313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161560E+10 | 0.537236E+10 | 0.757995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.244286E+10 | 0.141140E+11 | 0.392397E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.439993E+10 | 0.415214E+11 | 58104496.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.481136E+10 | 0.565295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.472475E+10 | 0.527267E+11 | 359776.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.289331E+10 | 0.211845E+11 | 0.709650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124774E+10 | 0.120719E+10 | 0.432423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121977E+10 | 67165409.18 | 0.220829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143240E+10 | 0.00 | 0.457358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.290865E+11 | 0.192853E+12 | 0.202966E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.481136E+10 | 0.565295E+11 | 0.627200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.223410E+10 | 0.00 | 0.868501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172442E+10 | 1244192.58 | 0.551465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154200E+10 | 0.133319E+09 | 0.301539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169530E+10 | 0.588042E+10 | 0.110794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.235167E+10 | 0.149736E+11 | 0.569337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.415450E+10 | 0.441077E+11 | 0.112263E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.443459E+10 | 0.594596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.426733E+10 | 0.541658E+11 | 4415937.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.259160E+10 | 0.218106E+11 | 0.128272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130180E+10 | 0.116042E+10 | 0.719250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158121E+10 | 37655492.14 | 0.336521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.194088E+10 | 0.00 | 0.662977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.298194E+11 | 0.201730E+12 | 0.292341E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.443459E+10 | 0.594596E+11 | 0.868501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.176357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145488E+10 | 0.00 | 0.00 | 0.00 | 40706544.42 | 0.126800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172342E+10 | 0.00 | 0.00 | 0.00 | 0.143576E+10 | 0.509945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.254942E+10 | 0.00 | 0.00 | 0.00 | 0.359724E+10 | 0.750525E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.456982E+10 | 0.00 | 0.00 | 0.00 | 0.107911E+11 | 0.234560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.536196E+10 | 0.00 | 0.00 | 0.00 | 0.149640E+11 | 3951228.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.567431E+10 | 0.00 | 0.00 | 0.00 | 0.148280E+11 | 33685592.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.369835E+10 | 0.00 | 0.00 | 0.00 | 0.652671E+10 | 0.507471E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174042E+10 | 0.00 | 0.00 | 0.00 | 0.840661E+09 | 0.149458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146597E+10 | 0.00 | 0.00 | 0.00 | 0.149687E+09 | 0.102795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.328249E+11 | 0.00 | 0.00 | 0.00 | 0.531738E+11 | 0.109218E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3951228.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.567431E+10 | 0.00 | 0.00 | 0.00 | 0.149640E+11 | 0.337614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.174314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128728E+10 | 0.00 | 0.00 | 0.00 | 37325334.48 | 0.770380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161560E+10 | 0.00 | 0.00 | 0.00 | 0.136760E+10 | 0.177164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.244286E+10 | 0.00 | 0.00 | 0.00 | 0.357588E+10 | 11831674.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.439993E+10 | 0.00 | 0.00 | 0.00 | 0.102671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.481136E+10 | 0.00 | 0.00 | 0.00 | 0.136260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.472475E+10 | 0.00 | 0.00 | 0.00 | 0.128184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.289331E+10 | 0.00 | 0.00 | 0.00 | 0.536706E+10 | 55646049.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124774E+10 | 0.00 | 0.00 | 0.00 | 0.324543E+09 | 0.554668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121977E+10 | 0.00 | 0.00 | 0.00 | 19099710.49 | 0.106154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.290865E+11 | 0.00 | 0.00 | 0.00 | 0.474030E+11 | 0.947373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.481136E+10 | 0.00 | 0.00 | 0.00 | 0.136260E+11 | 0.326346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.223410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172442E+10 | 0.00 | 0.00 | 0.00 | 367256.30 | 0.325260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154200E+10 | 0.00 | 0.00 | 0.00 | 38201918.94 | 0.161726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169530E+10 | 0.00 | 0.00 | 0.00 | 0.149818E+10 | 0.484803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.235167E+10 | 0.00 | 0.00 | 0.00 | 0.380604E+10 | 0.101698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.415450E+10 | 0.00 | 0.00 | 0.00 | 0.109479E+11 | 3701017.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.443459E+10 | 0.00 | 0.00 | 0.00 | 0.143807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.426733E+10 | 0.00 | 0.00 | 0.00 | 0.132496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.259160E+10 | 0.00 | 0.00 | 0.00 | 0.556588E+10 | 0.430473E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130180E+10 | 0.00 | 0.00 | 0.00 | 0.315533E+09 | 0.294338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158121E+10 | 0.00 | 0.00 | 0.00 | 10913316.35 | 0.206490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.194088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.298194E+11 | 0.00 | 0.00 | 0.00 | 0.498134E+11 | 0.170733E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.443459E+10 | 0.00 | 0.00 | 0.00 | 0.143807E+11 | 0.523185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.198507E+11 | 0.00 | 0.00 | 698503.13 | 0.00 | 0.893940E+09 | 0.664613E+09 | 0.00 | 0.27 |
February | 0.141281E+11 | 0.00 | 0.00 | 3120814.00 | 0.00 | 81400640.49 | 0.346677E+10 | 0.00 | 0.28 |
March | 0.798283E+10 | 0.00 | 0.00 | 15523428.27 | 0.00 | 3571640.46 | 0.108356E+11 | 0.00 | 0.38 |
April | 0.347276E+10 | 0.238714E+09 | 0.00 | 22325079.76 | 24976723.92 | 0.00 | 0.124107E+11 | 0.00 | 0.46 |
May | 0.909346E+09 | 0.265282E+09 | 0.00 | 36808655.60 | 42740679.94 | 0.00 | 0.157270E+11 | 0.00 | 0.86 |
June | 0.344658E+09 | 0.299419E+10 | 0.00 | 29741684.27 | 0.157403E+09 | 0.00 | 0.100514E+11 | 0.00 | 0.95 |
July | 0.335922E+09 | 0.526930E+10 | 0.00 | 19847107.55 | 0.474867E+09 | 0.00 | 0.397610E+10 | 0.00 | 0.93 |
August | 0.403503E+09 | 0.532103E+10 | 0.00 | 28360487.82 | 0.192584E+09 | 0.00 | 0.615096E+10 | 0.00 | 1.00 |
September | 0.756567E+09 | 0.539201E+09 | 0.00 | 37035712.93 | 64352363.26 | 0.00 | 0.142783E+11 | 0.00 | 0.82 |
October | 0.869575E+09 | 0.00 | 0.00 | 33924138.30 | 450113.75 | 0.00 | 0.167099E+11 | 0.00 | 0.49 |
November | 0.712798E+10 | 0.00 | 0.00 | 17059046.78 | 0.00 | 39008763.10 | 0.107928E+11 | 0.00 | 0.40 |
December | 0.144894E+11 | 0.00 | 0.00 | 4249414.80 | 0.00 | 0.108817E+09 | 0.469582E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.706713E+11 | 0.146277E+11 | 0.00 | 0.248694E+09 | 0.957374E+09 | 0.112674E+10 | 0.109760E+12 | 0.00 | 0.60 |
Minimum of Months | 0.335922E+09 | 0.00 | 0.00 | 698503.13 | 0.00 | 0.00 | 0.664613E+09 | 0.00 | 0.27 |
Maximum of Months | 0.198507E+11 | 0.532103E+10 | 0.00 | 37035712.93 | 0.474867E+09 | 0.893940E+09 | 0.167099E+11 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.135023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812626E+10 | 0.00 | 0.00 | 0.27 |
February | 0.139673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331802E+10 | 0.00 | 0.00 | 0.28 |
March | 0.143325E+11 | 0.00 | 0.00 | 716897.48 | 0.00 | 0.673883E+09 | 0.103694E+10 | 0.00 | 0.31 |
April | 0.804832E+10 | 0.119348E+09 | 0.00 | 6078723.78 | 88084849.51 | 97227544.16 | 0.435750E+10 | 0.00 | 0.36 |
May | 0.226484E+10 | 0.206944E+09 | 0.00 | 18208219.81 | 94820027.86 | 0.00 | 0.897916E+10 | 0.00 | 0.59 |
June | 0.978820E+09 | 0.229450E+10 | 0.00 | 17618415.75 | 0.186010E+09 | 0.00 | 0.592965E+10 | 0.00 | 0.65 |
July | 0.501119E+09 | 0.395199E+10 | 0.00 | 12536854.06 | 0.432961E+09 | 0.00 | 0.249945E+10 | 0.00 | 0.67 |
August | 0.677496E+09 | 0.379610E+10 | 0.00 | 17232900.03 | 0.203933E+09 | 0.00 | 0.368896E+10 | 0.00 | 0.68 |
September | 0.246367E+10 | 0.402951E+09 | 0.00 | 17478538.41 | 50331923.71 | 0.00 | 0.736178E+10 | 0.00 | 0.54 |
October | 0.758184E+10 | 0.00 | 0.00 | 5407166.08 | 1810263.16 | 0.00 | 0.421917E+10 | 0.00 | 0.34 |
November | 0.105041E+11 | 0.00 | 0.00 | 2071620.71 | 0.00 | 0.180525E+10 | 0.205788E+10 | 0.00 | 0.30 |
December | 0.142640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412458E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.890864E+11 | 0.107718E+11 | 0.00 | 97349336.11 | 0.105795E+10 | 0.181452E+11 | 0.401305E+11 | 0.00 | 0.44 |
Minimum of Months | 0.501119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.143325E+11 | 0.395199E+10 | 0.00 | 18208219.81 | 0.432961E+09 | 0.812626E+10 | 0.897916E+10 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.617850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131606E+11 | 0.00 | 0.00 | 0.25 |
February | 0.780925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792307E+10 | 0.00 | 0.00 | 0.27 |
March | 0.118370E+11 | 0.00 | 0.00 | 240326.09 | 0.00 | 0.284124E+10 | 0.357819E+09 | 0.00 | 0.31 |
April | 0.845987E+10 | 0.127389E+09 | 0.00 | 4160841.49 | 0.105513E+09 | 0.603543E+09 | 0.268265E+10 | 0.00 | 0.36 |
May | 0.309378E+10 | 0.157971E+09 | 0.00 | 15969592.80 | 51805300.56 | 0.00 | 0.770454E+10 | 0.00 | 0.58 |
June | 0.120115E+10 | 0.217652E+10 | 0.00 | 15377179.52 | 0.256318E+09 | 0.00 | 0.539767E+10 | 0.00 | 0.67 |
July | 0.595712E+09 | 0.401772E+10 | 0.00 | 10990833.08 | 0.535189E+09 | 0.00 | 0.230169E+10 | 0.00 | 0.71 |
August | 0.835842E+09 | 0.348392E+10 | 0.00 | 15288737.80 | 0.285515E+09 | 0.00 | 0.310825E+10 | 0.00 | 0.68 |
September | 0.340150E+10 | 0.334661E+09 | 0.00 | 11538222.39 | 67709366.40 | 2183766.46 | 0.496512E+10 | 0.00 | 0.51 |
October | 0.904616E+10 | 0.00 | 0.00 | 1417135.22 | 425400.06 | 0.194786E+09 | 0.148624E+10 | 0.00 | 0.32 |
November | 0.794846E+10 | 0.00 | 41013.56 | 441560.01 | 1074.01 | 0.432670E+10 | 0.718626E+09 | 76170.47 | 0.29 |
December | 0.715694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.927981E+10 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.675642E+11 | 0.102982E+11 | 41013.56 | 75424428.39 | 0.130248E+10 | 0.383320E+11 | 0.287226E+11 | 76170.47 | 0.43 |
Minimum of Months | 0.595712E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.118370E+11 | 0.401772E+10 | 41013.56 | 15969592.80 | 0.535189E+09 | 0.131606E+11 | 0.770454E+10 | 76170.47 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 83544880.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745860E+10 | 0.00 | 0.00 | 0.44 |
February | 0.166619E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523100E+10 | 0.00 | 0.00 | 0.39 |
March | 0.104843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272882E+10 | 0.00 | 0.00 | 0.36 |
April | 0.145668E+10 | 46010660.21 | 0.00 | 520768.11 | 19538111.41 | 0.949117E+09 | 0.312665E+09 | 0.00 | 0.40 |
May | 0.108190E+10 | 49688925.26 | 0.00 | 3259005.67 | 11592686.88 | 23222273.82 | 0.137749E+10 | 0.00 | 0.66 |
June | 0.439759E+09 | 0.719120E+09 | 0.00 | 3804415.09 | 58432554.84 | 0.00 | 0.118837E+10 | 0.00 | 0.88 |
July | 0.168656E+09 | 0.126023E+10 | 0.00 | 2842870.09 | 0.107170E+09 | 0.00 | 0.571314E+09 | 0.00 | 0.93 |
August | 0.260328E+09 | 0.106576E+10 | 0.00 | 3469851.04 | 70891370.69 | 0.00 | 0.667452E+09 | 0.00 | 0.85 |
September | 0.110150E+10 | 0.100127E+09 | 0.00 | 1888371.70 | 15650366.42 | 96161094.93 | 0.660753E+09 | 0.00 | 0.56 |
October | 0.174610E+10 | 0.00 | 0.00 | 54530.42 | 99681.94 | 0.720692E+09 | 53633269.94 | 0.00 | 0.35 |
November | 0.808431E+09 | 0.00 | 14950.31 | 0.00 | 0.00 | 0.279699E+10 | 0.00 | 29371.62 | 0.36 |
December | 47124590.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529607E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.840907E+10 | 0.324094E+10 | 14950.31 | 15839812.10 | 0.283374E+09 | 0.253007E+11 | 0.483168E+10 | 29371.62 | 0.55 |
Minimum of Months | 47124590.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.174610E+10 | 0.126023E+10 | 14950.31 | 3804415.09 | 0.107170E+09 | 0.745860E+10 | 0.137749E+10 | 29371.62 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416395E+10 | 0.00 | 0.00 | 0.40 |
February | 0.249982E+09 | 0.00 | 0.00 | 3219.28 | 0.00 | 0.269495E+10 | 5149092.91 | 0.00 | 0.34 |
March | 0.851106E+09 | 0.00 | 0.00 | 281688.99 | 0.00 | 0.117432E+10 | 0.165985E+09 | 0.00 | 0.33 |
April | 0.752063E+09 | 76414877.20 | 0.00 | 1394692.61 | 5471167.49 | 0.415244E+09 | 0.787164E+09 | 0.00 | 0.51 |
May | 0.353903E+09 | 62933010.64 | 0.00 | 4904930.83 | 1681608.88 | 2734088.95 | 0.201635E+10 | 0.00 | 1.03 |
June | 0.185478E+09 | 0.691332E+09 | 0.00 | 4825832.70 | 20734545.89 | 0.00 | 0.150657E+10 | 0.00 | 1.42 |
July | 62482677.29 | 0.117242E+10 | 0.00 | 4141389.80 | 36659359.48 | 0.00 | 0.790361E+09 | 0.00 | 1.56 |
August | 99646690.73 | 0.985565E+09 | 0.00 | 4668894.76 | 21903561.95 | 0.00 | 0.907638E+09 | 0.00 | 1.34 |
September | 0.455279E+09 | 0.109812E+09 | 0.00 | 3599736.34 | 4201332.78 | 28138976.39 | 0.108251E+10 | 0.00 | 0.88 |
October | 0.103101E+10 | 0.00 | 0.00 | 301996.05 | 56593.79 | 0.257287E+09 | 0.183398E+09 | 0.00 | 0.33 |
November | 0.465140E+09 | 0.00 | 9743.85 | 37903.86 | 0.00 | 0.156223E+10 | 30916957.72 | 22833.15 | 0.33 |
December | 83515991.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318398E+10 | 0.00 | 0.00 | 0.36 |
Annual Sum or Average | 0.469910E+10 | 0.309847E+10 | 9743.85 | 24160285.22 | 90708170.25 | 0.134828E+11 | 0.747604E+10 | 22833.15 | 0.74 |
Minimum of Months | 62482677.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.103101E+10 | 0.117242E+10 | 9743.85 | 4904930.83 | 36659359.48 | 0.416395E+10 | 0.201635E+10 | 22833.15 | 1.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.982668E+09 | 0.00 | 0.00 | 557871.97 | 0.00 | 0.441328E+10 | 0.468009E+09 | 0.00 | 0.36 |
February | 0.107333E+10 | 0.00 | 0.00 | 994513.43 | 0.00 | 0.272298E+10 | 0.624557E+09 | 0.00 | 0.35 |
March | 0.123683E+10 | 0.00 | 0.00 | 2377101.41 | 0.00 | 0.161047E+10 | 0.136659E+10 | 0.00 | 0.43 |
April | 0.113742E+10 | 0.134509E+09 | 0.00 | 3466178.55 | 8657115.47 | 0.641249E+09 | 0.185011E+10 | 0.00 | 0.59 |
May | 0.729214E+09 | 78553373.71 | 0.00 | 5975791.10 | 5326677.16 | 21306379.79 | 0.244756E+10 | 0.00 | 0.89 |
June | 0.370175E+09 | 0.855280E+09 | 0.00 | 4755280.57 | 49587750.98 | 0.00 | 0.151449E+10 | 0.00 | 1.04 |
July | 0.154706E+09 | 0.157382E+10 | 0.00 | 3869947.25 | 72822709.88 | 0.00 | 0.728146E+09 | 0.00 | 1.14 |
August | 0.204400E+09 | 0.142701E+10 | 0.00 | 6201279.31 | 34217886.80 | 0.00 | 0.114756E+10 | 0.00 | 1.20 |
September | 0.735246E+09 | 0.223460E+09 | 0.00 | 6553477.48 | 4240270.82 | 47880240.29 | 0.201647E+10 | 0.00 | 0.99 |
October | 0.125308E+10 | 0.00 | 0.00 | 4648896.40 | 89951.51 | 0.295959E+09 | 0.228511E+10 | 0.00 | 0.59 |
November | 0.102852E+10 | 0.00 | 14865.75 | 1038581.78 | 0.00 | 0.177486E+10 | 0.666699E+09 | 32503.52 | 0.38 |
December | 0.575311E+09 | 0.00 | 0.00 | 1007204.45 | 0.00 | 0.377228E+10 | 0.754850E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.948090E+10 | 0.429264E+10 | 14865.75 | 41446123.69 | 0.174942E+09 | 0.153003E+11 | 0.158702E+11 | 32503.52 | 0.70 |
Minimum of Months | 0.154706E+09 | 0.00 | 0.00 | 557871.97 | 0.00 | 0.00 | 0.468009E+09 | 0.00 | 0.35 |
Maximum of Months | 0.125308E+10 | 0.157382E+10 | 14865.75 | 6553477.48 | 72822709.88 | 0.441328E+10 | 0.244756E+10 | 32503.52 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.193879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436970E+10 | 0.00 | 0.00 | 0.42 |
February | 0.301334E+09 | 0.00 | 0.00 | 71639.18 | 0.00 | 0.280522E+10 | 57174254.16 | 0.00 | 0.37 |
March | 0.703707E+09 | 0.00 | 0.00 | 460272.16 | 0.00 | 0.135973E+10 | 0.302051E+09 | 0.00 | 0.36 |
April | 0.705019E+09 | 57942768.80 | 0.00 | 2037526.69 | 6181608.52 | 0.436912E+09 | 0.113954E+10 | 0.00 | 0.58 |
May | 0.445524E+09 | 53375733.88 | 0.00 | 4831987.80 | 4123035.27 | 14320745.29 | 0.170051E+10 | 0.00 | 0.96 |
June | 0.232285E+09 | 0.635002E+09 | 0.00 | 3929316.09 | 19792064.46 | 0.00 | 0.121101E+10 | 0.00 | 1.29 |
July | 88113337.28 | 0.129626E+10 | 0.00 | 3648197.62 | 25647711.25 | 0.00 | 0.567009E+09 | 0.00 | 1.38 |
August | 0.126004E+09 | 0.966435E+09 | 0.00 | 4457149.23 | 20201739.76 | 0.00 | 0.771882E+09 | 0.00 | 1.30 |
September | 0.540495E+09 | 0.119003E+09 | 0.00 | 2992396.70 | 4665390.26 | 51486060.46 | 0.852987E+09 | 0.00 | 0.82 |
October | 0.877268E+09 | 0.00 | 0.00 | 1008663.13 | 56674.59 | 0.310667E+09 | 0.568335E+09 | 0.00 | 0.41 |
November | 0.527626E+09 | 0.00 | 9672.68 | 114594.97 | 0.00 | 0.157167E+10 | 73898974.09 | 22880.40 | 0.35 |
December | 0.213195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313946E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.495445E+10 | 0.312802E+10 | 9672.68 | 23551743.57 | 80668224.13 | 0.140592E+11 | 0.724440E+10 | 22880.40 | 0.72 |
Minimum of Months | 88113337.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.877268E+09 | 0.129626E+10 | 9672.68 | 4831987.80 | 25647711.25 | 0.436970E+10 | 0.170051E+10 | 22880.40 | 1.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 95187264.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721353E+10 | 0.00 | 0.00 | 0.42 |
February | 0.107405E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512075E+10 | 0.00 | 0.00 | 0.37 |
March | 0.843350E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288259E+10 | 0.00 | 0.00 | 0.33 |
April | 0.125224E+10 | 15124016.19 | 0.00 | 68690.91 | 25136259.54 | 0.109239E+10 | 61949800.31 | 0.00 | 0.31 |
May | 0.141828E+10 | 35655923.06 | 0.00 | 797804.42 | 10743317.12 | 26493348.32 | 0.402400E+09 | 0.00 | 0.45 |
June | 0.481859E+09 | 0.536340E+09 | 0.00 | 2575286.05 | 36111229.89 | 0.00 | 0.763834E+09 | 0.00 | 0.62 |
July | 0.146416E+09 | 0.931586E+09 | 0.00 | 2261071.68 | 0.106259E+09 | 0.00 | 0.447557E+09 | 0.00 | 0.69 |
August | 0.232482E+09 | 0.953462E+09 | 0.00 | 3003957.78 | 51935981.93 | 0.00 | 0.627204E+09 | 0.00 | 0.72 |
September | 0.988618E+09 | 0.102299E+09 | 0.00 | 2168096.88 | 14408167.41 | 7898443.68 | 0.800197E+09 | 0.00 | 0.51 |
October | 0.212723E+10 | 0.00 | 0.00 | 71734.76 | 99889.58 | 0.106782E+09 | 87308720.17 | 0.00 | 0.30 |
November | 0.116304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223722E+10 | 0.00 | 0.00 | 0.32 |
December | 65253150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496455E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.892137E+10 | 0.257447E+10 | 0.00 | 10946642.48 | 0.244694E+09 | 0.236522E+11 | 0.319045E+10 | 0.00 | 0.45 |
Minimum of Months | 65253150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.212723E+10 | 0.953462E+09 | 0.00 | 3003957.78 | 0.106259E+09 | 0.721353E+10 | 0.800197E+09 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128458E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418738E+10 | 0.00 | 0.00 | 0.39 |
February | 0.287714E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275743E+10 | 0.00 | 0.00 | 0.34 |
March | 0.907618E+09 | 0.00 | 0.00 | 48913.68 | 0.00 | 0.127095E+10 | 39103687.06 | 0.00 | 0.31 |
April | 0.815699E+09 | 45110095.73 | 0.00 | 707448.66 | 3309387.32 | 0.445445E+09 | 0.349479E+09 | 0.00 | 0.37 |
May | 0.467684E+09 | 50103247.78 | 0.00 | 2968021.71 | 3788570.00 | 203529.62 | 0.121509E+10 | 0.00 | 0.71 |
June | 0.193788E+09 | 0.577767E+09 | 0.00 | 3899865.36 | 14910842.41 | 0.00 | 0.117005E+10 | 0.00 | 1.11 |
July | 56448689.62 | 0.966713E+09 | 0.00 | 3529985.30 | 50788493.05 | 0.00 | 0.664946E+09 | 0.00 | 1.26 |
August | 94182947.41 | 0.929355E+09 | 0.00 | 4343598.61 | 23298369.60 | 0.00 | 0.910135E+09 | 0.00 | 1.21 |
September | 0.356416E+09 | 0.114362E+09 | 0.00 | 4183969.60 | 6870840.36 | 229320.48 | 0.133331E+10 | 0.00 | 0.86 |
October | 0.105760E+10 | 0.00 | 0.00 | 718748.14 | 59887.21 | 19691255.96 | 0.381528E+09 | 0.00 | 0.30 |
November | 0.702319E+09 | 0.00 | 0.00 | 71762.68 | 0.00 | 0.126257E+10 | 61566688.43 | 0.00 | 0.30 |
December | 0.224958E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291160E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.529289E+10 | 0.268341E+10 | 0.00 | 20472313.73 | 0.103026E+09 | 0.128555E+11 | 0.612521E+10 | 0.00 | 0.63 |
Minimum of Months | 56448689.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.105760E+10 | 0.966713E+09 | 0.00 | 4343598.61 | 50788493.05 | 0.418738E+10 | 0.133331E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.274529E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.908899E+10 | 0.00 | 0.00 | 0.53 |
February | 0.472005E+09 | 0.00 | 0.00 | 33785.33 | 0.00 | 0.605388E+10 | 25699526.54 | 0.00 | 0.46 |
March | 0.876955E+09 | 0.00 | 0.00 | 259481.40 | 0.00 | 0.396168E+10 | 0.148988E+09 | 0.00 | 0.44 |
April | 0.835841E+09 | 0.104015E+09 | 0.00 | 687515.12 | 4896764.08 | 0.192488E+10 | 0.334130E+09 | 0.00 | 0.42 |
May | 0.125952E+10 | 65987237.34 | 0.00 | 1295444.35 | 8406152.85 | 0.305807E+09 | 0.438880E+09 | 0.00 | 0.52 |
June | 0.553121E+09 | 0.704162E+09 | 0.00 | 2291964.51 | 38863931.97 | 0.111714E+09 | 0.582440E+09 | 0.00 | 0.68 |
July | 0.194926E+09 | 0.123953E+10 | 0.00 | 2349428.42 | 0.105234E+09 | 1883274.02 | 0.411354E+09 | 0.00 | 0.82 |
August | 0.243105E+09 | 0.139656E+10 | 0.00 | 4546424.74 | 41538800.42 | 20776764.44 | 0.842381E+09 | 0.00 | 0.99 |
September | 0.782413E+09 | 0.242384E+09 | 0.00 | 5071656.03 | 7717384.36 | 0.218254E+09 | 0.139041E+10 | 0.00 | 0.84 |
October | 0.140969E+10 | 121265.94 | 0.00 | 2370481.96 | 11158.31 | 0.647978E+09 | 0.106858E+10 | 0.00 | 0.44 |
November | 0.102219E+10 | 0.00 | 0.00 | 556985.53 | 0.00 | 0.313362E+10 | 0.340294E+09 | 0.00 | 0.43 |
December | 0.612426E+09 | 0.00 | 0.00 | 626.87 | 0.00 | 0.649343E+10 | 1993054.59 | 0.00 | 0.47 |
Annual Sum or Average | 0.853672E+10 | 0.375277E+10 | 0.00 | 19463794.26 | 0.206669E+09 | 0.319629E+11 | 0.558515E+10 | 0.00 | 0.59 |
Minimum of Months | 0.194926E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1883274.02 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.140969E+10 | 0.139656E+10 | 0.00 | 5071656.03 | 0.105234E+09 | 0.908899E+10 | 0.139041E+10 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.144944E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441296E+10 | 0.00 | 0.00 | 0.41 |
February | 0.291386E+09 | 0.00 | 0.00 | 11950.82 | 0.00 | 0.285188E+10 | 12742002.06 | 0.00 | 0.35 |
March | 0.769732E+09 | 0.00 | 0.00 | 113178.80 | 0.00 | 0.141462E+10 | 81943476.28 | 0.00 | 0.32 |
April | 0.817044E+09 | 35979731.05 | 0.00 | 956677.98 | 8166666.04 | 0.410380E+09 | 0.479998E+09 | 0.00 | 0.39 |
May | 0.593926E+09 | 43732759.18 | 0.00 | 2359712.88 | 5715407.23 | 6140070.20 | 0.826572E+09 | 0.00 | 0.62 |
June | 0.243708E+09 | 0.525304E+09 | 0.00 | 3237083.17 | 15101717.35 | 0.00 | 0.883979E+09 | 0.00 | 1.00 |
July | 71905726.53 | 0.105266E+10 | 0.00 | 2981436.86 | 27967049.48 | 0.00 | 0.466765E+09 | 0.00 | 1.11 |
August | 92545731.33 | 0.939818E+09 | 0.00 | 4081852.83 | 15888807.19 | 0.00 | 0.783566E+09 | 0.00 | 1.18 |
September | 0.442134E+09 | 0.126701E+09 | 0.00 | 3280875.00 | 5177452.42 | 4810316.64 | 0.101947E+10 | 0.00 | 0.79 |
October | 0.107833E+10 | 0.00 | 0.00 | 1084199.42 | 60201.75 | 27876190.94 | 0.506520E+09 | 0.00 | 0.35 |
November | 0.764969E+09 | 0.00 | 0.00 | 105846.23 | 0.00 | 0.125914E+10 | 79683373.91 | 0.00 | 0.32 |
December | 0.268460E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290892E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.557908E+10 | 0.272419E+10 | 0.00 | 18212813.98 | 78077301.45 | 0.132967E+11 | 0.514124E+10 | 0.00 | 0.60 |
Minimum of Months | 71905726.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.107833E+10 | 0.105266E+10 | 0.00 | 4081852.83 | 27967049.48 | 0.441296E+10 | 0.101947E+10 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.135978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663098E+10 | 0.00 | 0.00 | 0.39 |
February | 0.291435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459462E+10 | 0.00 | 0.00 | 0.34 |
March | 0.138754E+10 | 0.00 | 0.00 | 1545.27 | 0.00 | 0.211369E+10 | 9658877.61 | 0.00 | 0.32 |
April | 0.170563E+10 | 49494512.16 | 0.00 | 647732.40 | 10252117.18 | 0.522850E+09 | 0.346942E+09 | 0.00 | 0.36 |
May | 0.838608E+09 | 65915119.52 | 0.00 | 3702520.55 | 19919445.35 | 2931340.08 | 0.157012E+10 | 0.00 | 0.65 |
June | 0.298391E+09 | 0.770278E+09 | 0.00 | 4304116.72 | 38194963.98 | 0.00 | 0.130096E+10 | 0.00 | 0.84 |
July | 0.122275E+09 | 0.123564E+10 | 0.00 | 3088336.45 | 86798151.22 | 0.00 | 0.593698E+09 | 0.00 | 0.86 |
August | 0.211733E+09 | 0.117259E+10 | 0.00 | 3556725.99 | 40556803.41 | 0.00 | 0.711474E+09 | 0.00 | 0.82 |
September | 0.992861E+09 | 0.123469E+09 | 0.00 | 2400442.82 | 10641805.02 | 20620766.41 | 0.884820E+09 | 0.00 | 0.55 |
October | 0.209271E+10 | 0.00 | 0.00 | 183754.52 | 382737.77 | 0.187798E+09 | 0.142499E+09 | 0.00 | 0.32 |
November | 0.105601E+10 | 0.00 | 0.00 | 12963.80 | 0.00 | 0.226719E+10 | 31006039.90 | 0.00 | 0.32 |
December | 57567531.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472880E+10 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.919074E+10 | 0.341739E+10 | 0.00 | 17898138.52 | 0.206746E+09 | 0.210695E+11 | 0.559117E+10 | 0.00 | 0.51 |
Minimum of Months | 57567531.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.209271E+10 | 0.123564E+10 | 0.00 | 4304116.72 | 86798151.22 | 0.663098E+10 | 0.157012E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.127974E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368960E+10 | 0.00 | 0.00 | 0.34 |
February | 0.332857E+09 | 0.00 | 0.00 | 18109.77 | 0.00 | 0.223392E+10 | 10669522.49 | 0.00 | 0.29 |
March | 0.827060E+09 | 0.00 | 0.00 | 402328.78 | 0.00 | 0.912011E+09 | 0.226031E+09 | 0.00 | 0.29 |
April | 0.792681E+09 | 63073126.42 | 0.00 | 1601593.69 | 3949041.19 | 0.222291E+09 | 0.837207E+09 | 0.00 | 0.47 |
May | 0.320811E+09 | 77852958.95 | 0.00 | 4954318.58 | 5126155.16 | 192093.58 | 0.200358E+10 | 0.00 | 0.98 |
June | 0.139051E+09 | 0.686549E+09 | 0.00 | 4940533.67 | 18049699.15 | 0.00 | 0.148136E+10 | 0.00 | 1.30 |
July | 51657403.90 | 0.107758E+10 | 0.00 | 4198435.52 | 41867252.65 | 0.00 | 0.779253E+09 | 0.00 | 1.40 |
August | 97977713.72 | 0.986649E+09 | 0.00 | 4525798.57 | 20927936.49 | 0.00 | 0.941167E+09 | 0.00 | 1.25 |
September | 0.407495E+09 | 0.115680E+09 | 0.00 | 4020376.99 | 4861766.21 | 5184612.08 | 0.127837E+10 | 0.00 | 0.86 |
October | 0.960708E+09 | 0.00 | 0.00 | 642774.97 | 241932.26 | 79864869.86 | 0.365669E+09 | 0.00 | 0.30 |
November | 0.520980E+09 | 0.00 | 0.00 | 92874.18 | 0.00 | 0.121863E+10 | 76733299.50 | 0.00 | 0.28 |
December | 0.182349E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264525E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.476160E+10 | 0.300738E+10 | 0.00 | 25397144.70 | 95023783.12 | 0.110069E+11 | 0.800004E+10 | 0.00 | 0.67 |
Minimum of Months | 51657403.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.960708E+09 | 0.107758E+10 | 0.00 | 4954318.58 | 41867252.65 | 0.368960E+10 | 0.200358E+10 | 0.00 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114820E+10 | 0.00 | 0.00 | 866702.15 | 0.00 | 0.400161E+10 | 0.679827E+09 | 0.00 | 0.35 |
February | 0.126501E+10 | 0.00 | 0.00 | 1261965.23 | 0.00 | 0.243666E+10 | 0.828170E+09 | 0.00 | 0.35 |
March | 0.156399E+10 | 0.00 | 0.00 | 2917807.00 | 0.00 | 0.130523E+10 | 0.156641E+10 | 0.00 | 0.45 |
April | 0.144415E+10 | 0.132654E+09 | 0.00 | 3758779.94 | 7192674.77 | 0.369652E+09 | 0.187208E+10 | 0.00 | 0.59 |
May | 0.683100E+09 | 0.109434E+09 | 0.00 | 6143033.51 | 11788132.58 | 2931127.80 | 0.247531E+10 | 0.00 | 0.88 |
June | 0.312235E+09 | 0.913261E+09 | 0.00 | 5045968.52 | 38166628.20 | 0.00 | 0.151686E+10 | 0.00 | 0.99 |
July | 0.135338E+09 | 0.151614E+10 | 0.00 | 3816069.15 | 75145217.41 | 0.00 | 0.669378E+09 | 0.00 | 1.04 |
August | 0.199486E+09 | 0.154045E+10 | 0.00 | 5714764.50 | 29883718.84 | 0.00 | 0.109068E+10 | 0.00 | 1.14 |
September | 0.693684E+09 | 0.259403E+09 | 0.00 | 7012340.67 | 6654589.43 | 12016895.57 | 0.228277E+10 | 0.00 | 0.99 |
October | 0.138123E+10 | 556035.41 | 0.00 | 6054502.94 | 0.00 | 97198290.80 | 0.278164E+10 | 0.00 | 0.66 |
November | 0.139876E+10 | 0.00 | 0.00 | 1517539.31 | 0.00 | 0.140505E+10 | 0.883885E+09 | 0.00 | 0.40 |
December | 0.713369E+09 | 0.00 | 0.00 | 1406574.09 | 0.00 | 0.341483E+10 | 0.104934E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.109386E+11 | 0.447190E+10 | 0.00 | 45516046.99 | 0.168831E+09 | 0.130452E+11 | 0.176964E+11 | 0.00 | 0.68 |
Minimum of Months | 0.135338E+09 | 0.00 | 0.00 | 866702.15 | 0.00 | 0.00 | 0.669378E+09 | 0.00 | 0.35 |
Maximum of Months | 0.156399E+10 | 0.154045E+10 | 0.00 | 7012340.67 | 75145217.41 | 0.400161E+10 | 0.278164E+10 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.285193E+09 | 0.00 | 0.00 | 242.67 | 0.00 | 0.394425E+10 | 2507727.31 | 0.00 | 0.38 |
February | 0.464224E+09 | 0.00 | 0.00 | 87808.27 | 0.00 | 0.248109E+10 | 72907694.70 | 0.00 | 0.34 |
March | 0.965413E+09 | 0.00 | 0.00 | 539874.52 | 0.00 | 0.110677E+10 | 0.333798E+09 | 0.00 | 0.36 |
April | 0.927382E+09 | 55607316.67 | 0.00 | 2178873.65 | 4517705.33 | 0.241126E+09 | 0.113897E+10 | 0.00 | 0.57 |
May | 0.412932E+09 | 73301567.96 | 0.00 | 4700399.34 | 9603231.81 | 3803813.10 | 0.168810E+10 | 0.00 | 0.94 |
June | 0.190953E+09 | 0.681697E+09 | 0.00 | 4131968.47 | 14239826.12 | 0.00 | 0.119537E+10 | 0.00 | 1.23 |
July | 75143622.62 | 0.123715E+10 | 0.00 | 3500045.00 | 23123864.26 | 0.00 | 0.513886E+09 | 0.00 | 1.24 |
August | 0.121827E+09 | 0.105970E+10 | 0.00 | 4121173.84 | 13893217.98 | 0.00 | 0.742493E+09 | 0.00 | 1.24 |
September | 0.534332E+09 | 0.144504E+09 | 0.00 | 3141533.65 | 3891252.02 | 14534703.16 | 0.976665E+09 | 0.00 | 0.83 |
October | 0.112231E+10 | 0.00 | 0.00 | 1280945.01 | 240895.98 | 97628066.06 | 0.668549E+09 | 0.00 | 0.44 |
November | 0.735093E+09 | 0.00 | 0.00 | 145776.11 | 0.00 | 0.131962E+10 | 0.106775E+09 | 0.00 | 0.34 |
December | 0.289759E+09 | 0.00 | 0.00 | 351.09 | 0.00 | 0.280253E+10 | 3102785.89 | 0.00 | 0.33 |
Annual Sum or Average | 0.612456E+10 | 0.325196E+10 | 0.00 | 23828991.63 | 69509993.51 | 0.120113E+11 | 0.744313E+10 | 0.00 | 0.69 |
Minimum of Months | 75143622.62 | 0.00 | 0.00 | 242.67 | 0.00 | 0.00 | 2507727.31 | 0.00 | 0.33 |
Maximum of Months | 0.112231E+10 | 0.123715E+10 | 0.00 | 4700399.34 | 23123864.26 | 0.394425E+10 | 0.168810E+10 | 0.00 | 1.24 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:06
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.208274E+12 | 0.440796E+11 | 0.00 | 0.153492E+12 | 0.241183E+11 |
February | 0.226372E+12 | 0.332234E+11 | 0.00 | 0.138150E+12 | 0.160033E+11 |
March | 0.325140E+12 | 0.295044E+11 | 0.00 | 0.160183E+12 | 0.105337E+11 |
April | 0.377915E+12 | 0.181130E+11 | 0.00 | 0.171937E+12 | 0.253850E+11 |
May | 0.428358E+12 | 0.103556E+11 | 0.00 | 0.205363E+12 | 0.544603E+11 |
June | 0.441656E+12 | 0.246854E+10 | 0.00 | 0.107054E+12 | 0.161247E+12 |
July | 0.443874E+12 | 0.284949E+09 | 0.00 | 0.437808E+11 | 0.221095E+12 |
August | 0.388597E+12 | 0.231502E+10 | 0.00 | 0.841484E+11 | 0.209001E+12 |
September | 0.278989E+12 | 0.892151E+10 | 0.00 | 0.169800E+12 | 0.867060E+11 |
October | 0.220516E+12 | 0.184517E+11 | 0.00 | 0.189469E+12 | 0.961522E+10 |
November | 0.141847E+12 | 0.280731E+11 | 0.00 | 0.150257E+12 | 0.975250E+10 |
December | 0.119767E+12 | 0.371172E+11 | 0.00 | 0.144287E+12 | 0.177870E+11 |
Annual Sum or Average | 0.360131E+13 | 0.232908E+12 | 0.00 | 0.171792E+13 | 0.845705E+12 |
Minimum of Months | 0.119767E+12 | 0.284949E+09 | 0.00 | 0.437808E+11 | 0.961522E+10 |
Maximum of Months | 0.443874E+12 | 0.440796E+11 | 0.00 | 0.205363E+12 | 0.221095E+12 |