Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:31
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2023-10-16 08:32:04
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1880.15 | 377.37 | 377.37 |
Net Site Energy | 1880.15 | 377.37 | 377.37 |
Total Source Energy | 5048.59 | 1013.33 | 1013.33 |
Net Source Energy | 5048.59 | 1013.33 | 1013.33 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 236.97 | 296.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 112.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 232.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 51.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 94.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 137.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1445.28 | 434.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 236.97 | 296.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 112.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 232.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 51.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 94.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 137.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 236.97 | 296.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 112.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 232.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 51.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 94.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 137.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 57.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 89.02 | 87.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 290.09 | 87.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 57.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 89.02 | 87.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 290.09 | 87.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1445.278 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1445.278 | 100.00 |
Total On-Site and Utility Electric Sources | 1445.278 | 100.00 |
Total Electricity End Uses | 1445.278 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 370.33 |
Time Setpoint Not Met During Occupied Cooling | 104.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2797.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:31 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.6636 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.6636 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.6636 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 6.6636 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.6636 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 09-JAN-08:09 | 09-JAN-09:00 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 170517.87 | 139081.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25003.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 45864.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 818.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5340.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 9578.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 253237.92 | 148660.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 170517.87 | 139081.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 25003.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 818.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 5340.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 9578.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 750.49 | 321.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 354.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 737.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 164.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 37.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 298.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 149.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4577.20 | 471.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 150.64 | 64.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 71.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 148.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 59.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 30.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 918.71 | 94.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 150.64 | 64.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 71.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 148.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 59.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 30.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 918.71 | 94.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.20 | 0.234295 | 0.199000 | 0.636553 | 0.624788 | 0.500000 | 0.001626 |
CORE_MID VAV BOX COMPONENT | 2.34 | 0.320713 | 0.273000 | 0.637957 | 0.855235 | 0.500000 | 0.001188 |
CORE_TOP VAV BOX COMPONENT | 2.46 | 0.305052 | 0.259000 | 0.636313 | 0.813473 | 0.500000 | 0.001249 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.779295 | 0.202737 | 0.172000 | 0.134039 | 0.540631 | 0.500000 | 0.001879 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.918671 | 0.108877 | 0.093000 | 0.085436 | 0.300000 | 0.500000 | 0.003499 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.23 | 0.128352 | 0.109000 | 0.134170 | 0.342273 | 0.500000 | 0.002968 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.04 | 0.095821 | 0.081000 | 0.084546 | 0.300000 | 0.500000 | 0.003976 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.602762 | 0.262113 | 0.223000 | 0.134416 | 0.698968 | 0.500000 | 0.001454 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.753787 | 0.132692 | 0.113000 | 0.085178 | 0.353846 | 0.500000 | 0.002871 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.976497 | 0.161794 | 0.138000 | 0.134757 | 0.431451 | 0.500000 | 0.002355 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.820129 | 0.121951 | 0.104000 | 0.085293 | 0.325202 | 0.500000 | 0.003124 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.677422 | 0.233225 | 0.198000 | 0.134130 | 0.621933 | 0.500000 | 0.001634 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.910350 | 0.300000 | 0.500000 | 0.003468 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.13 | 0.140354 | 0.119000 | 0.133954 | 0.374278 | 0.500000 | 0.002715 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.966155 | 0.103519 | 0.088000 | 0.085022 | 0.300000 | 0.500000 | 0.003680 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 18593.75 |
CORE_MID VAV BOX REHEAT COIL | 26831.59 |
CORE_TOP VAV BOX REHEAT COIL | 47453.27 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 22221.96 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14535.17 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 22386.78 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 14656.19 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 16906.74 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11158.03 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 17061.68 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11261.06 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 17283.52 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 11376.02 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 17423.77 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 11483.01 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.18 | 1.08 | 6.35 | 2.42 | 5.60 | 5.60 | 0.300000 | 0.432470 | 5.60 |
PACU_VAV_MID | 3.01 | 1.08 | 6.02 | 2.89 | 5.02 | 5.02 | 0.300000 | 0.575112 | 5.02 |
PACU_VAV_TOP | 3.21 | 1.07 | 6.43 | 4.15 | 5.79 | 5.79 | 0.300000 | 0.716334 | 5.79 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.60 |
PACU_VAV_MID_OA_CONTROLLER | 5.02 |
PACU_VAV_TOP_OA_CONTROLLER | 5.79 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.60 | 92771.06 | 0.800655 | 1.87 | 30920.59 | 0.800655 |
PACU_VAV_MID COOLING COIL | 5.02 | 83164.46 | 0.800655 | 1.67 | 27718.71 | 0.800655 |
PACU_VAV_TOP COOLING COIL | 5.79 | 95926.14 | 0.800655 | 1.93 | 31972.18 | 0.800655 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 36660.94 |
PACU_VAV_MID HEATING COIL | 38016.92 |
PACU_VAV_TOP HEATING COIL | 36587.00 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.60 |
PACU_VAV_MID FAN | 5.02 |
PACU_VAV_TOP FAN | 5.79 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 31.498 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7597 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7464 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.9868 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2198 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2318 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2198 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2318 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.082 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.106 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7793 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.474 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.237 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.474 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.236 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.31468885E-12 | 0.58742715E-14 | -0.96802560E-13 | 0.16792992E-15 |
43 | 6 | 0.28872123E-07 | 0.21416477E-09 | 0.66123209E-08 | -0.13627602E-12 |
44 | 5 | -0.19112651E-03 | 0.18301600E-05 | -0.98293898E-04 | 0.65360363E-08 |
45 | 4 | 0.29333920 | 0.88954174E-03 | 0.10011225 | -0.33739231E-04 |
46 | 3 | -7.2899446 | 0.27524297E-01 | -2.3459205 | 0.29124746E-01 |
47 | 2 | 40.949034 | 0.97737712E-01 | 15.293846 | -0.33420785 |
48 | 1 | -80.605481 | 0.44056480E-01 | -29.167461 | 1.0798913 |
49 | 0 | 46.824338 | 0.88531397E-03 | 16.290617 | |
50 | 7 | -0.30618227E-12 | 0.12614254E-14 | -0.97456297E-13 | 0.16278992E-15 |
51 | 6 | 0.29029541E-07 | 0.21075172E-09 | 0.66470638E-08 | -0.13712239E-12 |
52 | 5 | -0.19192439E-03 | 0.17992386E-05 | -0.98693455E-04 | 0.65698920E-08 |
53 | 4 | 0.29427084 | 0.87374093E-03 | 0.10044741 | -0.33870887E-04 |
54 | 3 | -7.3083902 | 0.27014250E-01 | -2.3513943 | 0.29215155E-01 |
55 | 2 | 41.009863 | 0.95860246E-01 | 15.316286 | -0.33488536 |
56 | 1 | -80.652088 | 0.43184114E-01 | -29.187576 | 1.0808846 |
57 | 0 | 46.824338 | 0.86726935E-03 | 16.290137 | |
58 | 7 | -0.27636417E-12 | 0.12990813E-14 | -0.82271001E-13 | 0.80162457E-16 |
59 | 6 | 0.26158967E-07 | 0.26982527E-09 | 0.60134738E-08 | -0.12176112E-12 |
60 | 5 | -0.17726759E-03 | 0.23481051E-05 | -0.91336903E-04 | 0.59516496E-08 |
61 | 4 | 0.27699908 | 0.11597994E-02 | 0.94241662E-01 | -0.31446529E-04 |
62 | 3 | -6.9660490 | 0.36401088E-01 | -2.2498311 | 0.27538282E-01 |
63 | 2 | 39.880486 | 0.13088809 | 14.898993 | -0.32230875 |
64 | 1 | -79.786295 | 0.59645051E-01 | -28.813249 | 1.0624348 |
65 | 0 | 46.824344 | 0.12114519E-02 | 16.299244 | |
66 | 7 | -0.19168505E-08 | -0.51383041E-15 | 0.68469349E-14 | -0.93730203E-16 |
67 | 6 | 0.61617009E-05 | 0.42103975E-08 | 0.31882761E-02 | -0.26745931E-04 |
68 | 5 | -0.44250412E-03 | 0.24935927E-05 | -0.22363399 | 0.19553507E-02 |
69 | 4 | 0.10175003E-01 | 0.11350545E-03 | 4.8280370 | -0.45250478E-01 |
70 | 3 | -0.89340535E-01 | 0.90260008E-03 | -38.012894 | 0.39855955 |
71 | 2 | 0.31721614 | 0.15015396E-02 | 116.46736 | -1.4177174 |
72 | 1 | -0.45784565 | 0.45746588E-03 | -143.89754 | 2.0488794 |
73 | 0 | 0.22322007 | 0.11078117E-04 | 60.838472 | |
74 | 7 | -0.18147523E-08 | -0.43765969E-15 | 0.59880535E-14 | -0.82299290E-16 |
75 | 6 | 0.64914511E-05 | 0.44428550E-08 | 0.31873263E-02 | -0.26737964E-04 |
76 | 5 | -0.46689866E-03 | 0.26323880E-05 | -0.22358000 | 0.19548742E-02 |
77 | 4 | 0.10740407E-01 | 0.11982633E-03 | 4.8271378 | -0.45241835E-01 |
78 | 3 | -0.94318369E-01 | 0.95296379E-03 | -38.007814 | 0.39850340 |
79 | 2 | 0.33490849 | 0.15853305E-02 | 116.45748 | -1.4175852 |
80 | 1 | -0.48339250 | 0.48313585E-03 | -143.89172 | 2.0487838 |
81 | 0 | 0.23567793 | 0.11657420E-04 | 60.838472 | |
82 | 7 | -0.19168505E-08 | -0.51383063E-15 | 0.68469351E-14 | -0.93730206E-16 |
83 | 6 | 0.61617009E-05 | 0.42103975E-08 | 0.31882761E-02 | -0.26745931E-04 |
84 | 5 | -0.44250412E-03 | 0.24935927E-05 | -0.22363399 | 0.19553507E-02 |
85 | 4 | 0.10175003E-01 | 0.11350545E-03 | 4.8280370 | -0.45250478E-01 |
86 | 3 | -0.89340535E-01 | 0.90260008E-03 | -38.012894 | 0.39855955 |
87 | 2 | 0.31721614 | 0.15015396E-02 | 116.46736 | -1.4177174 |
88 | 1 | -0.45784565 | 0.45746588E-03 | -143.89754 | 2.0488794 |
89 | 0 | 0.22322007 | 0.11078117E-04 | 60.838472 | |
90 | 7 | -0.18146260E-08 | -0.43662845E-15 | 0.62700332E-14 | -0.82012168E-16 |
91 | 6 | 0.64918823E-05 | 0.44431590E-08 | 0.31873251E-02 | -0.26737954E-04 |
92 | 5 | -0.46693053E-03 | 0.26325692E-05 | -0.22357993 | 0.19548736E-02 |
93 | 4 | 0.10741146E-01 | 0.11983458E-03 | 4.8271366 | -0.45241823E-01 |
94 | 3 | -0.94324870E-01 | 0.95302955E-03 | -38.007807 | 0.39850333 |
95 | 2 | 0.33493160 | 0.15854399E-02 | 116.45746 | -1.4175850 |
96 | 1 | -0.48342587 | 0.48316934E-03 | -143.89172 | 2.0487836 |
97 | 0 | 0.23569420 | 0.11658190E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.342_SHGC_EAST_0.379 | 35 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
2 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 36 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
3 | WINDOW_U_0.342_SHGC_WEST_0.379 | 37 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
4 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 38 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2826E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2891E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4398E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4454E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1269E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.1721E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3624E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3867E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1720 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.9229E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1976 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1150 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1139 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9799E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8200E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8082E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2829E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2912E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4401E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4478E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1298E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.1855E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3621E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3864E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.4873E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.9222E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.3153E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7343E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.8300E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9514E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6593E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6671E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.4257E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.4535E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.2433E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.2635E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4630E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.4702E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0914E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0997E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8454E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.9058E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0466E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.0962E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4906E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.5282E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3621E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3864E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7185E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7016E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6490E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0678E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3365E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4030E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8200E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8082E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8449E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.9067E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0453E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.0939E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4881E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.5186E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3624E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3867E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.6238E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9876E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9297E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5321E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.4708E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3008E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6593E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6671E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2370E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.3171E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7148E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.8045E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6324E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.6628E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0916E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0999E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1765 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1213 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2003 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1401 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1232 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.3186E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.4952E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.5650E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.2011E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.7573E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.0460E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.5784E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.6403E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.8382E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.5541E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.6039E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.3552E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.5005E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.2139E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7538E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.9008E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0271E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.4952E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.5650E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.4002E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.8640E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.7412E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4299E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.3224E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.2150E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.5542E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6040E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1765 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1213 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2003 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1401 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1232 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.3178E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.4947E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.5647E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.2011E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.7570E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.0459E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.5781E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.6399E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.8377E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.5536E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.6036E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.3554E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.5004E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.2140E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7536E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.9005E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0269E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.4947E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.5647E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.4002E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.8638E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.7412E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4297E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3220E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.2147E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.5536E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.6037E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 38815.74098 | 38815.74098 | 3.19876 | 3.19876 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 10224.08869 | 10224.08869 | 0.49328 | 0.49328 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 28387.87878 | 28387.87878 | 2.33684 | 2.33684 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 18922.31145 | 18922.31145 | 0.91857 | 0.91857 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 29573.01598 | 29573.01598 | 2.45681 | 2.45681 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 32.76000 | 6.30583E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 33368.53576 | 33368.53576 | 1.62455 | 1.62455 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9381.05875 | 9381.05875 | 0.77930 | 0.77930 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 33.08000 | 6.30633E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 15593.48011 | 15593.48011 | 0.76076 | 0.76076 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11058.93285 | 11058.93285 | 0.91867 | 0.91867 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.96000 | 6.29539E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 10199.01864 | 10199.01864 | 0.49761 | 0.49761 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 14817.71128 | 14817.71128 | 1.23092 | 1.23092 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.26667 | 6.30663E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 15708.93256 | 15708.93256 | 0.76641 | 0.76641 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12564.93146 | 12564.93146 | 1.04378 | 1.04378 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 10283.79562 | 10283.79562 | 0.50175 | 0.50175 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7255.81098 | 7255.81098 | 0.60276 | 0.60276 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.40000 | 6.30683E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 11868.87748 | 11868.87748 | 0.57880 | 0.57880 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9073.87865 | 9073.87865 | 0.75379 | 0.75379 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 26.86667 | 6.29676E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 7832.47134 | 7832.47134 | 0.38199 | 0.38199 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 11754.74385 | 11754.74385 | 0.97650 | 0.97650 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.40000 | 6.30683E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 11977.40345 | 11977.40345 | 0.58410 | 0.58410 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9872.48793 | 9872.48793 | 0.82013 | 0.82013 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 28.76000 | 6.29966E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 7904.63530 | 7904.63530 | 0.38552 | 0.38552 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8154.65793 | 8154.65793 | 0.67742 | 0.67742 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.40000 | 6.30683E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 12133.68840 | 12133.68840 | 0.59170 | 0.59170 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10958.69557 | 10958.69557 | 0.91035 | 0.91035 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.50667 | 6.29470E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 7985.74292 | 7985.74292 | 0.38946 | 0.38946 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 13550.53217 | 13550.53217 | 1.12566 | 1.12566 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.13333 | 6.30642E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 12231.92087 | 12231.92087 | 0.59650 | 0.59650 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11630.45872 | 11630.45872 | 0.96616 | 0.96616 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 8060.68214 | 8060.68214 | 0.39312 | 0.39312 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 75865.83 | 5.60430 | 5.60430 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 40828.09 | 2.42369 | 2.42369 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 68889.81 | 5.02396 | 5.02396 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 40483.31 | 2.88934 | 2.88934 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 77806.35 | 5.79490 | 5.79490 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 40839.70 | 4.15108 | 4.15108 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.19876 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23430 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19900 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63655 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62479 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.62615E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18593.75038 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.33684 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32071 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27300 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63796 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85524 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18798E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26831.58839 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.45681 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30505 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25900 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63631 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.81347 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.24897E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 47453.26594 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77930 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20274 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17200 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13404 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54063 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.87929E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22221.96024 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.91867 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10888 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.30000E-002 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.54364E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.49937E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14535.16529 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23092 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12835 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10900 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13417 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34227 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.96839E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22386.78000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.04378 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.58207E-002 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.10000E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.45458E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.97618E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14656.19193 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.60276 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26211 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22300 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13442 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69897 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.45357E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16906.73775 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75379 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13269 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11300 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51779E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35385 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.87130E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11158.03094 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.97650 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16179 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13800 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13476 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43145 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.35484E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17061.68451 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82013 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12195 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10400 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52934E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32520 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.12422E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11261.06358 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67742 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23322 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19800 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13413 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62193 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.63362E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17283.52083 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.91035 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.46768E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11376.01602 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.12566 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14035 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11900 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13395 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37428 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.71456E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17423.76720 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.96616 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10352 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.80000E-002 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50217E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.68049E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11483.00608 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.17597 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07620 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.35193 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.42369 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.60430 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.60430 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.43247 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.00821 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07572 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.01643 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.88934 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.02396 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.02396 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.57511 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.21473 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07450 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.42947 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 4.15108 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.79490 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.79490 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.71633 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.60430 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 5.02396 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.79490 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.60430 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.60430 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 92771.05970 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.86791 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 30920.59420 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
152 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 36660.94386 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.60430 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.02396 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.02396 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 83164.45798 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.67449 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 27718.71384 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
161 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 38016.92173 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 5.02396 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.79490 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.79490 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 95926.13694 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.93144 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31972.18144 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
170 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 36587.00363 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.79490 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 91174.70 | 311100.99 | 11.07 | 2.80 | 3.17 | 3.34 | 3.50 | 9.54 | 10.82 | 11.40 | 11.93 | 5.6690 | 4.4825 | 3.0045 | 1.2650 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 81733.40 | 278885.95 | 11.07 | 2.80 | 3.17 | 3.34 | 3.50 | 9.54 | 10.82 | 11.40 | 11.93 | 5.0820 | 4.0183 | 2.6933 | 1.1340 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 94275.49 | 321681.31 | 11.07 | 2.80 | 3.17 | 3.34 | 3.50 | 9.54 | 10.82 | 11.40 | 11.93 | 5.8618 | 4.6349 | 3.1066 | 1.3081 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.220 | 0.209 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.232 | 0.219 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.220 | 0.209 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.232 | 0.219 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.5675885830E-002 | 6.7157620469E-002 | Pass | Pass | 8.4774335240E-002 | 0.2722231291 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1067866327 | 7.4948978348E-002 | Pass | Pass | 0.3661859774 | 0.4705856132 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.6879711553E-002 | 2.2818112759E-002 | Pass | Pass | 0.1099030282 | 0.3006860066 | Fail | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.6184156957E-002 | 2.4743590072E-002 | Pass | Pass | 9.2938231587E-002 | 0.2853649820 | Fail | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 2.7938093126E-002 | 2.9990174334E-002 | Pass | Pass | 0.1141342378 | 0.3176462981 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.2173451262E-002 | 2.2697709262E-002 | Pass | Pass | 0.5212870910 | 1.3098253398 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2390773644 | 0.2904635805 | Pass | Pass | 14.5173568995 | 68.9942397503 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1942975232 | 0.2641445806 | Pass | Pass | 35.6170213711 | 283.3919536118 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2030246420 | 0.1968071972 | Pass | Pass | 7.0966908184 | 51.9421247431 | Pass | Fail |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2389050940 | 0.2725207243 | Pass | Pass | 33.9939940286 | 199.6569035839 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.0210290210E-002 | 0.1035536969 | Pass | Pass | 16.5957209149 | 184.3746793933 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.2931072459E-002 | 6.2821024925E-002 | Pass | Pass | 1.1182597088 | 7.3503079791 | Pass | Fail |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1029112118 | 9.9731329547E-002 | Pass | Pass | 8.4488265172E-002 | 0.2662926282 | Pass | Fail |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 5.4926553731E-002 | 5.2252190968E-002 | Pass | Pass | 12.1230072099 | 107.9981601970 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.3825222310E-002 | 0.1043148457 | Pass | Pass | 1.3395182391 | 7.0408636690 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 7.8159016498E-002 | 0.1060656521 | Pass | Pass | 1.2165655779 | 6.6567152520 | Fail | Fail |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1264565024 | 0.1286433150 | Pass | Pass | 0.4511206311 | 2.9292541433 | Pass | Fail |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.3003913433E-002 | 0.1017045792 | Pass | Pass | 1.2973592939 | 6.9157212051 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3574.57 | 192.82 | 0.00 | 2098.44 | 607.44 | 6473.28 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.212 | 0.220 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.223 | 0.232 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.212 | 0.220 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.223 | 0.232 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.342_SHGC_NORTH_0.379 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.342_SHGC_EAST_0.379 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.342_SHGC_WEST_0.379 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.342_SHGC_EAST_0.379 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.342_SHGC_EAST_0.379 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.342_SHGC_WEST_0.379 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.342_SHGC_WEST_0.379 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.342_SHGC_NORTH_0.379 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.342_SHGC_EAST_0.379 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.342_SHGC_WEST_0.379 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 1.943 | 0.380 | 0.418 | |||||||||||||||||
North Total or Average | 195.79 | 1.943 | 0.380 | 0.418 | |||||||||||||||||
Non-North Total or Average | 456.84 | 1.943 | 0.380 | 0.418 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.24 | 0.0000 | Y | 6.81 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.96 | 0.0000 | Y | 4.26 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.77 | 0.0000 | Y | 6.68 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.02 | 0.0000 | Y | 4.27 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.19 | 0.0000 | Y | 6.79 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.92 | 0.0000 | Y | 4.26 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.73 | 0.0000 | Y | 6.67 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.97 | 0.0000 | Y | 4.26 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.24 | 0.0000 | Y | 6.81 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.96 | 0.0000 | Y | 4.26 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.77 | 0.0000 | Y | 6.68 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.02 | 0.0000 | Y | 4.27 |
Interior Lighting Total | 6.6636 | 4982.19 | 33199.39 | 232.83 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 42.11 | 42.11 | 4.46 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.57 | 62.84 | 4.81 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.57 | 48.07 | 42.54 | |
Exterior Lighting Total | 5686.19 | 51.81 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 92771.06 | 74277.64 | 18493.42 | 0.80 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 83164.46 | 66586.06 | 16578.40 | 0.80 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 95926.14 | 76803.77 | 19122.37 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 91174.7 | 2.80 | 9.54 | N/A | N/A | 11.07 | |
PACU_VAV_MID COOLING COIL | 81733.4 | 2.80 | 9.54 | N/A | N/A | 11.07 | |
PACU_VAV_TOP COOLING COIL | 94275.5 | 2.80 | 9.54 | N/A | N/A | 11.07 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 18593.75 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 26831.59 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 47453.27 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 22221.96 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14535.17 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 22386.78 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14656.19 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16906.74 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11158.03 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17061.68 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11261.06 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17283.52 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11376.02 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17423.77 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11483.01 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 36660.94 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 38016.92 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 36587.00 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.60 | 12881.27 | 2298.46 | 1.00 | 1.13 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.02 | 11547.39 | 2298.46 | 1.00 | 1.13 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.79 | 12603.26 | 2174.89 | 1.00 | 1.13 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 91174.70 | 2.80 | 9.54 | 11.07 | 5.6690 | 3.17 | 10.82 | 4.4825 | 3.34 | 11.40 | 3.0045 | 3.50 | 11.93 | 1.2650 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 81733.40 | 2.80 | 9.54 | 11.07 | 5.0820 | 3.17 | 10.82 | 4.0183 | 3.34 | 11.40 | 2.6933 | 3.50 | 11.93 | 1.1340 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 94275.49 | 2.80 | 9.54 | 11.07 | 5.8618 | 3.17 | 10.82 | 4.6349 | 3.34 | 11.40 | 3.1066 | 3.50 | 11.93 | 1.3081 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 38815.74 | 38815.74 | 39.47 | 3.199 | 3.199 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00881 | 21.56 | 0.00629 | 0.425 | 0.00 |
CORE_MID | 28387.88 | 28387.88 | 28.86 | 2.337 | 2.337 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 21.56 | 0.00629 | 0.425 | 0.00 |
CORE_TOP | 29573.02 | 29573.02 | 30.07 | 2.457 | 2.457 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00891 | 32.76 | 0.00631 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9381.06 | 9381.06 | 45.25 | 0.779 | 0.779 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00866 | 33.08 | 0.00631 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11058.93 | 11058.93 | 84.25 | 0.919 | 0.919 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00858 | 25.96 | 0.00630 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 14817.71 | 14817.71 | 71.47 | 1.231 | 1.231 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00860 | 33.27 | 0.00631 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12564.93 | 12564.93 | 95.73 | 1.044 | 1.044 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00858 | 30.36 | 0.00630 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7255.81 | 7255.81 | 35.00 | 0.603 | 0.603 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00877 | 33.40 | 0.00631 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9073.88 | 9073.88 | 69.13 | 0.754 | 0.754 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00864 | 26.87 | 0.00630 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11754.74 | 11754.74 | 56.69 | 0.976 | 0.976 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00867 | 33.40 | 0.00631 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9872.49 | 9872.49 | 75.22 | 0.820 | 0.820 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.00 | 24.00 | 0.00863 | 28.76 | 0.00630 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8154.66 | 8154.66 | 39.33 | 0.677 | 0.677 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00871 | 33.40 | 0.00631 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10958.70 | 10958.70 | 83.49 | 0.910 | 0.910 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00859 | 25.51 | 0.00629 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 13550.53 | 13550.53 | 65.35 | 1.126 | 1.126 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00863 | 33.13 | 0.00631 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11630.46 | 11630.46 | 88.61 | 0.966 | 0.966 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00859 | 30.36 | 0.00630 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 10224.09 | 10224.09 | 10.40 | 0.493 | 0.493 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 0.425 | 0.00 |
CORE_MID | 18922.31 | 18922.31 | 19.24 | 0.919 | 0.919 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 0.425 | 0.00 |
CORE_TOP | 33368.54 | 33368.54 | 33.93 | 1.625 | 1.625 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 15593.48 | 15593.48 | 75.21 | 0.761 | 0.761 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10199.02 | 10199.02 | 77.70 | 0.498 | 0.498 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15708.93 | 15708.93 | 75.76 | 0.766 | 0.766 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10283.80 | 10283.80 | 78.35 | 0.502 | 0.502 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 11868.88 | 11868.88 | 57.24 | 0.579 | 0.579 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7832.47 | 7832.47 | 59.67 | 0.382 | 0.382 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11977.40 | 11977.40 | 57.77 | 0.584 | 0.584 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 7904.64 | 7904.64 | 60.22 | 0.386 | 0.386 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 12133.69 | 12133.69 | 58.52 | 0.592 | 0.592 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 7985.74 | 7985.74 | 60.84 | 0.389 | 0.389 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12231.92 | 12231.92 | 59.00 | 0.596 | 0.596 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 8060.68 | 8060.68 | 61.41 | 0.393 | 0.393 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -27.60 | 0.00034 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.60 | 5.60 | 2.42 | 2.42 | 5.6043 | 2.4237 | 5.6043 | 0.4325 | 0.3000 |
PACU_VAV_MID | 5.02 | 5.02 | 2.89 | 2.89 | 5.0240 | 2.8893 | 5.0240 | 0.5751 | 0.3000 |
PACU_VAV_TOP | 5.79 | 5.79 | 4.15 | 4.15 | 5.7949 | 4.1511 | 5.7949 | 0.7163 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 18593.750 | 18593.750 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18593.75 | 14408.67 | 0.493278 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 10224.09 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 26831.588 | 26831.588 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26831.59 | 26831.59 | 0.918574 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 18922.31 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 47453.266 | 47453.266 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 47453.27 | 47453.27 | 1.624553 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 33368.54 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 22221.960 | 22221.960 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22221.96 | 22221.96 | 0.760764 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00775674 | 43.8767 | 15593.48 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 14535.165 | 14535.165 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14535.17 | 14535.17 | 0.497608 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00775215 | 43.8512 | 10199.02 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 22386.780 | 22386.780 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22386.78 | 22386.78 | 0.766407 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00775847 | 43.8863 | 15708.93 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 14656.192 | 14656.192 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14656.19 | 14656.19 | 0.501752 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00775412 | 43.8622 | 10283.80 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 16906.738 | 16906.738 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16906.74 | 16906.74 | 0.578799 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00782727 | 44.2689 | 11868.88 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 11158.031 | 11158.031 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11158.03 | 11158.03 | 0.381993 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00782612 | 44.2626 | 7832.47 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 17061.685 | 17061.685 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17061.68 | 17061.68 | 0.584103 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00782894 | 44.2783 | 11977.40 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 11261.064 | 11261.064 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11261.06 | 11261.06 | 0.385520 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00782778 | 44.2718 | 7904.64 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 17283.521 | 17283.521 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17283.52 | 17283.52 | 0.591698 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00773952 | 43.7799 | 12133.69 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 11376.016 | 11376.016 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11376.02 | 11376.02 | 0.389456 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00773665 | 43.7640 | 7985.74 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 17423.767 | 17423.767 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17423.77 | 17423.77 | 0.596499 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00774163 | 43.7917 | 12231.92 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 11483.006 | 11483.006 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11483.01 | 11483.01 | 0.393118 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00773909 | 43.7777 | 8060.68 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 92771.060 | 74277.637 | 5.604300 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 90680.50 | 90680.50 | 5.604300 | 25.60 | 15.44 | 0.00835219 | 10.66 | 9.88 | 0.00835219 | 33.40 | 0.00630683 | 16.37 | 17.0601 | 24.00 | 0.00877339 | 41.2895 | 67395.93 | 0.00 | 95659.42 | 70482.02 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 36660.944 | 36660.944 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 36660.94 | 36660.94 | 1.681290 | -7.80 | -7.80 | 0.00348412 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 56.8671 | 18.32 | 0.00764895 | 51.1228 | 13507.17 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 83164.458 | 66586.061 | 5.023965 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 81290.38 | 81290.38 | 5.023965 | 25.79 | 15.47 | 0.00831556 | 10.66 | 9.85 | 0.00831556 | 33.40 | 0.00630683 | 16.37 | 19.0308 | 24.00 | 0.00878929 | 41.3630 | 60310.47 | 0.00 | 85753.72 | 63183.49 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 38016.922 | 38016.922 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38016.92 | 38016.92 | 1.507189 | -11.04 | -11.04 | 0.00295798 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 63.4360 | 17.36 | 0.00716695 | 50.9120 | 16091.62 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 95926.137 | 76803.766 | 5.794898 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 93879.23 | 93879.23 | 5.794898 | 25.53 | 15.41 | 0.00834023 | 10.78 | 9.92 | 0.00834023 | 33.24 | 0.00630658 | 16.31 | 16.4990 | 24.00 | 0.00874362 | 41.1509 | 69531.53 | 0.00 | 98912.72 | 72879.07 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 36587.004 | 36587.004 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 36587.00 | 36587.00 | 1.738469 | -7.09 | -7.09 | 0.00357523 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 54.9967 | 16.24 | 0.00766686 | 58.4139 | 14102.10 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 18593.750 | 18593.750 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18593.75 | 14408.67 | 1.0000 | 0.51949057 | 0.493278 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18593.75 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.81 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 10224.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 26831.588 | 26831.588 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26831.59 | 26831.59 | 1.0000 | 0.96738672 | 0.918574 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26831.59 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 18922.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 47453.266 | 47453.266 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 47453.27 | 47453.27 | 1.0000 | 1.71088116 | 1.624553 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 47453.27 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 33368.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 22221.960 | 22221.960 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22221.96 | 22221.96 | 1.0000 | 0.80119107 | 0.760764 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22221.96 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00775674 | 21.00 | 0.00775674 | 43.8767 | 15593.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 14535.165 | 14535.165 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14535.17 | 14535.17 | 1.0000 | 0.52405119 | 0.497608 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14535.17 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00775215 | 21.00 | 0.00775215 | 43.8512 | 10199.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 22386.780 | 22386.780 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22386.78 | 22386.78 | 1.0000 | 0.80713349 | 0.766407 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22386.78 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00775847 | 21.00 | 0.00775847 | 43.8863 | 15708.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 14656.192 | 14656.192 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14656.19 | 14656.19 | 1.0000 | 0.52841469 | 0.501752 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14656.19 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00775412 | 21.00 | 0.00775412 | 43.8622 | 10283.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 16906.738 | 16906.738 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16906.74 | 16906.74 | 1.0000 | 0.60955592 | 0.578799 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16906.74 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00782727 | 21.00 | 0.00782727 | 44.2689 | 11868.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 11158.031 | 11158.031 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11158.03 | 11158.03 | 1.0000 | 0.40229191 | 0.381993 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11158.03 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00782612 | 21.00 | 0.00782612 | 44.2626 | 7832.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 17061.685 | 17061.685 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17061.68 | 17061.68 | 1.0000 | 0.61514237 | 0.584103 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17061.68 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00782894 | 21.00 | 0.00782894 | 44.2783 | 11977.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 11261.064 | 11261.064 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11261.06 | 11261.06 | 1.0000 | 0.40600665 | 0.385520 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11261.06 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00782778 | 21.00 | 0.00782778 | 44.2718 | 7904.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 17283.521 | 17283.521 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17283.52 | 17283.52 | 1.0000 | 0.62314046 | 0.591698 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17283.52 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00773952 | 21.00 | 0.00773952 | 43.7799 | 12133.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 11376.016 | 11376.016 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11376.02 | 11376.02 | 1.0000 | 0.41015115 | 0.389456 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11376.02 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00773665 | 21.00 | 0.00773665 | 43.7640 | 7985.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 17423.767 | 17423.767 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17423.77 | 17423.77 | 1.0000 | 0.62819691 | 0.596499 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17423.77 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00774163 | 21.00 | 0.00774163 | 43.7917 | 12231.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 11483.006 | 11483.006 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11483.01 | 11483.01 | 1.0000 | 0.41400857 | 0.393118 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11483.01 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00773909 | 21.00 | 0.00773909 | 43.7777 | 8060.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 92771.060 | 74277.637 | 5.604300 | -999.0 | -999.000 | -999.0000 | 1.03582 | 1.00000 | 1020.3663 | 1004.8586 | 1.0531 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.604300 | 5.90211153 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 90680.50 | 90680.50 | 0.9775 | 5.90211153 | 5.604300 | 25.60 | 15.44 | 0.00835219 | 47014.0 | 10.66 | 9.88 | 0.00835219 | 31766.5 | -999.0 | -999.00 | -999.00 | -999.00 | 12881.267 | 77799.23 | 33.40 | 0.00630683 | 16.37 | 0.95610000 | 17.0601 | 24.00 | 0.00877339 | 24.00 | 0.00877339 | 41.2895 | 67395.93 | 0.00 | 95659.42 | 70482.02 | 5.66902274 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.51 | 13.70 | 0.00944336 | 38448.3 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36660.944 | 36660.944 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.604300 | 5.90211153 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 36660.94 | 36660.94 | 1.0000 | 1.77063346 | 1.681290 | -7.80 | -7.80 | 0.00348412 | 820.4 | 12.80 | 10.41 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36660.94 | -27.60 | 0.00034190 | -27.60 | 0.95610000 | 56.8671 | 18.29 | 0.00762687 | 18.32 | 0.00764895 | 51.1228 | 13507.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 83164.458 | 66586.061 | 5.023965 | -999.0 | -999.000 | -999.0000 | 1.02352 | 1.00000 | 1020.2982 | 1004.8586 | 1.0531 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.023965 | 5.29093780 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 81290.38 | 81290.38 | 0.9775 | 5.29093780 | 5.023965 | 25.79 | 15.47 | 0.00831556 | 47113.3 | 10.66 | 9.85 | 0.00831556 | 31674.0 | -999.0 | -999.00 | -999.00 | -999.00 | 11547.390 | 69742.99 | 33.40 | 0.00630683 | 16.37 | 0.95610000 | 19.0308 | 24.00 | 0.00878929 | 24.00 | 0.00878929 | 41.3630 | 60310.47 | 0.00 | 85753.72 | 63183.49 | 5.08198575 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.51 | 13.70 | 0.00944336 | 38448.3 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 38016.922 | 38016.922 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.023965 | 5.29093780 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 38016.92 | 38016.92 | 1.0000 | 1.58728134 | 1.507189 | -11.04 | -11.04 | 0.00295798 | -3751.5 | 12.80 | 10.41 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38016.92 | -27.60 | 0.00034190 | -27.60 | 0.95610000 | 63.4360 | 17.70 | 0.00749670 | 17.36 | 0.00716695 | 50.9120 | 16091.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 95926.137 | 76803.766 | 5.794898 | -999.0 | -999.000 | -999.0000 | 1.05047 | 1.00000 | 1020.3441 | 1004.8586 | 1.0531 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.794898 | 6.10283811 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 93879.23 | 93879.23 | 0.9787 | 6.10283811 | 5.794898 | 25.53 | 15.41 | 0.00834023 | 46906.4 | 10.78 | 9.92 | 0.00834023 | 31853.7 | -999.0 | -999.00 | -999.00 | -999.00 | 12603.256 | 81275.97 | 33.24 | 0.00630658 | 16.31 | 0.95610000 | 16.4990 | 24.00 | 0.00874362 | 24.00 | 0.00874362 | 41.1509 | 69531.53 | 0.00 | 98912.72 | 72879.07 | 5.86182214 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.51 | 13.70 | 0.00944336 | 38448.3 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36587.004 | 36587.004 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.794898 | 6.10283811 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 36587.00 | 36587.00 | 1.0000 | 1.83085143 | 1.738469 | -7.09 | -7.09 | 0.00357523 | 1773.1 | 12.80 | 10.41 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36587.00 | -27.60 | 0.00034190 | -27.60 | 0.95610000 | 54.9967 | 17.98 | 0.00752655 | 16.24 | 0.00766686 | 58.4139 | 14102.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.60 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.02 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.79 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1236.67 | 3179.00 | 148.50 |
CORE_MID | 1594.17 | 4017.67 | 855.33 |
CORE_TOP | 2316.00 | 4292.50 | 1663.50 |
PERIMETER_TOP_ZN_3 | 3258.50 | 4490.50 | 2539.00 |
PERIMETER_TOP_ZN_2 | 3363.83 | 4060.83 | 2238.50 |
PERIMETER_TOP_ZN_1 | 3044.17 | 3859.83 | 1863.17 |
PERIMETER_TOP_ZN_4 | 3362.50 | 4175.83 | 2322.00 |
PERIMETER_BOT_ZN_3 | 2846.50 | 4601.50 | 2317.67 |
PERIMETER_BOT_ZN_2 | 3018.00 | 3956.83 | 1842.17 |
PERIMETER_BOT_ZN_1 | 2681.00 | 3938.50 | 1556.00 |
PERIMETER_BOT_ZN_4 | 2968.83 | 4060.17 | 1916.33 |
PERIMETER_MID_ZN_3 | 2831.33 | 4300.67 | 2056.67 |
PERIMETER_MID_ZN_2 | 2591.17 | 3367.00 | 1631.83 |
PERIMETER_MID_ZN_1 | 2725.17 | 3582.00 | 1403.33 |
PERIMETER_MID_ZN_4 | 2984.83 | 3952.33 | 1850.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4666.33 | 4838.50 | 2797.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.83 | 0.00 | 0.83 | 0.00 |
CORE_TOP | 8.67 | 0.00 | 6.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 174.83 | 8.50 | 84.67 | 6.00 |
PERIMETER_TOP_ZN_2 | 105.50 | 32.00 | 22.33 | 28.00 |
PERIMETER_TOP_ZN_1 | 84.50 | 33.17 | 16.17 | 28.17 |
PERIMETER_TOP_ZN_4 | 105.83 | 34.00 | 24.83 | 18.00 |
PERIMETER_BOT_ZN_3 | 73.33 | 0.00 | 51.50 | 0.00 |
PERIMETER_BOT_ZN_2 | 23.17 | 22.83 | 5.00 | 21.50 |
PERIMETER_BOT_ZN_1 | 315.67 | 27.17 | 305.00 | 24.50 |
PERIMETER_BOT_ZN_4 | 23.83 | 23.50 | 5.33 | 11.67 |
PERIMETER_MID_ZN_3 | 68.67 | 5.00 | 34.17 | 3.83 |
PERIMETER_MID_ZN_2 | 39.50 | 29.67 | 6.67 | 27.67 |
PERIMETER_MID_ZN_1 | 27.00 | 33.33 | 4.83 | 30.67 |
PERIMETER_MID_ZN_4 | 39.83 | 32.83 | 8.17 | 17.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 495.17 | 134.50 | 370.33 | 104.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.909 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.649 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.624 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.720 | 0.114 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 1.160 | 0.120 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 1.181 | 0.114 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 1.039 | 0.120 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.584 | 0.061 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.976 | 0.064 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.925 | 0.883 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.841 | 0.064 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.704 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 1.046 | 0.106 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 1.187 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 1.013 | 0.100 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.51 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 108.48 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 14437071.09 | 0.00 | 14437071.09 | 0.00 | 14437071.09 | 13393058.27 | 5077.38 | 545.20 | 3137.42 | 145.57 |
CORE_MID | 10377753.46 | 0.00 | 10377753.46 | 0.00 | 10377753.46 | 13393058.27 | 5318.37 | 824.59 | 2617.05 | 208.85 |
CORE_TOP | 9986846.61 | 0.00 | 9986846.61 | 0.00 | 9986846.61 | 13393058.27 | 5539.29 | 839.70 | 2381.01 | 99.07 |
PERIMETER_TOP_ZN_3 | 2428661.90 | 0.00 | 2428661.90 | 759318.16 | 3187980.06 | 2823374.22 | 4657.13 | 862.34 | 3240.52 | 99.05 |
PERIMETER_TOP_ZN_2 | 2460601.77 | 0.00 | 2460601.77 | 506209.06 | 2966810.84 | 1787429.43 | 4522.78 | 411.62 | 3825.60 | 99.05 |
PERIMETER_TOP_ZN_1 | 3957377.91 | 0.00 | 3957377.91 | 759318.16 | 4716696.08 | 2823374.22 | 4535.35 | 804.81 | 3419.84 | 99.05 |
PERIMETER_TOP_ZN_4 | 2230256.06 | 0.00 | 2230256.06 | 506209.06 | 2736465.12 | 1787312.18 | 4626.21 | 1070.88 | 3062.91 | 99.05 |
PERIMETER_BOT_ZN_3 | 1973758.71 | 0.00 | 1973758.71 | 403724.27 | 2377482.98 | 2823374.22 | 6072.14 | 488.24 | 2199.62 | 145.57 |
PERIMETER_BOT_ZN_2 | 2072338.46 | 0.00 | 2072338.46 | 269147.90 | 2341486.36 | 1787429.43 | 5566.33 | 487.85 | 2705.82 | 145.57 |
PERIMETER_BOT_ZN_1 | 3112008.66 | 0.00 | 3112008.66 | 3161469.32 | 6273477.98 | 2823374.22 | 5175.72 | 402.67 | 3181.62 | 145.57 |
PERIMETER_BOT_ZN_4 | 1796352.00 | 0.00 | 1796352.00 | 269147.90 | 2065499.90 | 1787312.18 | 5621.72 | 427.91 | 2710.37 | 145.57 |
PERIMETER_MID_ZN_3 | 2374817.34 | 0.00 | 2374817.34 | 632073.14 | 3006890.49 | 2823374.22 | 4866.51 | 987.71 | 2905.78 | 208.85 |
PERIMETER_MID_ZN_2 | 2284168.16 | 0.00 | 2284168.16 | 421379.56 | 2705547.72 | 1601953.02 | 4525.00 | 974.03 | 3260.97 | 1117.85 |
PERIMETER_MID_ZN_1 | 3974470.65 | 0.00 | 3974470.65 | 632073.14 | 4606543.79 | 2823374.22 | 4554.24 | 1063.73 | 3142.03 | 208.85 |
PERIMETER_MID_ZN_4 | 2169373.33 | 0.00 | 2169373.33 | 421379.56 | 2590752.89 | 1787312.18 | 4705.37 | 877.28 | 3177.35 | 208.85 |
Total Facility | 65635856.12 | 0.00 | 65635856.12 | 8741449.25 | 74377305.37 | 67658168.57 | 6847.48 | 1730.30 | 4532.52 | 1205.59 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6687 | 0.0000 | 0.6687 | 0.0000 | 0.6687 | 0.4247 | 2308.83 | 545.20 | 3088.98 |
CORE_MID | 0.4782 | 0.0000 | 0.4782 | 0.0000 | 0.4782 | 0.4247 | 2555.53 | 824.59 | 2562.88 |
CORE_TOP | 0.4600 | 0.0000 | 0.4600 | 0.0000 | 0.4600 | 0.4247 | 2784.43 | 839.62 | 2318.96 |
PERIMETER_TOP_ZN_3 | 0.1121 | 0.0000 | 0.1121 | 0.0178 | 0.1299 | 0.0895 | 1902.26 | 862.26 | 3178.47 |
PERIMETER_TOP_ZN_2 | 0.1141 | 0.0000 | 0.1141 | 0.0119 | 0.1259 | 0.0567 | 1767.94 | 411.56 | 3763.49 |
PERIMETER_TOP_ZN_1 | 0.1835 | 0.0000 | 0.1835 | 0.0178 | 0.2013 | 0.0895 | 1780.51 | 804.75 | 3357.74 |
PERIMETER_TOP_ZN_4 | 0.1023 | 0.0000 | 0.1023 | 0.0119 | 0.1141 | 0.0567 | 1871.41 | 1070.88 | 3000.71 |
PERIMETER_BOT_ZN_3 | 0.0909 | 0.0000 | 0.0909 | 0.0095 | 0.1004 | 0.0895 | 3303.59 | 488.24 | 2151.18 |
PERIMETER_BOT_ZN_2 | 0.0960 | 0.0000 | 0.0960 | 0.0063 | 0.1023 | 0.0567 | 2797.97 | 487.81 | 2657.22 |
PERIMETER_BOT_ZN_1 | 0.1441 | 0.0000 | 0.1441 | 0.1384 | 0.2825 | 0.0895 | 2407.16 | 402.67 | 3133.17 |
PERIMETER_BOT_ZN_4 | 0.0827 | 0.0000 | 0.0827 | 0.0063 | 0.0890 | 0.0567 | 2853.41 | 427.88 | 2661.71 |
PERIMETER_MID_ZN_3 | 0.1095 | 0.0000 | 0.1095 | 0.0148 | 0.1244 | 0.0895 | 2103.67 | 987.71 | 2851.62 |
PERIMETER_MID_ZN_2 | 0.1029 | 0.0000 | 0.1029 | 0.0105 | 0.1133 | 0.0567 | 1762.36 | 973.92 | 2297.72 |
PERIMETER_MID_ZN_1 | 0.1843 | 0.0000 | 0.1843 | 0.0148 | 0.1991 | 0.0895 | 1791.44 | 1063.73 | 3087.82 |
PERIMETER_MID_ZN_4 | 0.0997 | 0.0000 | 0.0997 | 0.0099 | 0.1095 | 0.0567 | 1942.73 | 877.28 | 3122.99 |
Total Facility | 3.0289 | 0.0000 | 3.0289 | 0.2698 | 3.2987 | 2.1513 | 4057.76 | 1730.04 | 4449.10 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 25943566.00 | 0.00 | 25943566.00 | 22614548.33 | 4174.57 | 2.07 | 4583.36 | 145.57 |
PACU_VAV_MID | 23491392.29 | 0.00 | 23491392.29 | 22429071.92 | 4148.47 | 3.48 | 4608.05 | 208.41 |
PACU_VAV_TOP | 23361751.05 | 0.00 | 23361751.05 | 22614548.33 | 4165.02 | 2.12 | 4592.86 | 98.07 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.2006 | 0.0000 | 1.2006 | 0.7171 | 1406.01 | 2.07 | 4534.92 |
PACU_VAV_MID | 1.0842 | 0.0000 | 1.0842 | 0.7084 | 1385.64 | 3.48 | 4553.88 |
PACU_VAV_TOP | 1.0779 | 0.0000 | 1.0779 | 0.7171 | 1410.22 | 2.12 | 4530.66 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 841.39 | 2174.35 | 0.00 | 0.00 | 0.00 | 1919.46 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 164.42 | 2355.28 | 0.00 | 0.00 | 0.00 | 2513.14 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 148.98 | 2170.84 | 0.00 | 0.00 | 0.00 | 2545.51 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.0486 | 2.2483 | 0.0000 | 0.0000 | 0.0000 | 0.8819 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.0303 | 1.9417 | 0.0000 | 0.0000 | 0.0000 | 0.8383 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.0208 | 1.9757 | 0.0000 | 0.0000 | 0.0000 | 0.8488 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 943 |
Defaulted Fields | 546 |
Fields with Defaults | 2233 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1445.28 | 12315.29 | 26-MAR-17:30 | 253237.92 | 09-JAN-08:10 |
Electricity:Building | 938.26 | 12146.72 | 26-MAR-17:20 | 70868.50 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 291.77 | 4006.86 | 01-JAN-00:10 | 23121.21 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 938.26 | 12146.72 | 26-MAR-17:20 | 70868.50 | 02-JAN-08:10 |
InteriorLights:Electricity | 232.83 | 905.38 | 26-MAR-17:20 | 25003.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 232.83 | 905.38 | 26-MAR-17:20 | 25003.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 232.83 | 905.38 | 26-MAR-17:20 | 25003.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 232.83 | 905.38 | 26-MAR-17:20 | 25003.79 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 31.14 | 413.68 | 12-MAR-17:10 | 2475.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.81 | 27.57 | 01-JAN-10:10 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.81 | 27.57 | 01-JAN-10:10 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.67 | 261.88 | 26-MAR-17:10 | 1567.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.26 | 17.46 | 01-JAN-08:50 | 658.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.26 | 17.46 | 01-JAN-08:50 | 658.76 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 31.01 | 413.67 | 12-MAR-17:10 | 2475.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.68 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.68 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.68 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.27 | 17.46 | 01-JAN-10:10 | 658.71 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.27 | 17.46 | 01-JAN-10:10 | 658.71 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 31.12 | 413.68 | 12-MAR-17:10 | 2475.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.79 | 27.57 | 01-JAN-10:10 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.79 | 27.57 | 01-JAN-10:10 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.66 | 261.88 | 26-MAR-17:10 | 1567.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.26 | 17.46 | 01-JAN-08:40 | 658.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.26 | 17.46 | 01-JAN-08:40 | 658.76 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 31.01 | 413.67 | 12-MAR-17:10 | 2475.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.67 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.67 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.67 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.26 | 17.46 | 01-JAN-10:00 | 658.71 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.26 | 17.46 | 01-JAN-10:00 | 658.71 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 31.14 | 413.68 | 12-MAR-17:10 | 2475.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.81 | 27.57 | 01-JAN-10:10 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.81 | 27.57 | 01-JAN-10:10 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.67 | 261.88 | 26-MAR-17:10 | 1567.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.26 | 17.46 | 01-JAN-08:50 | 658.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.26 | 17.46 | 01-JAN-08:50 | 658.76 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 31.01 | 413.67 | 12-MAR-17:10 | 2475.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.68 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.68 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.68 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.27 | 17.46 | 01-JAN-10:10 | 658.71 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.27 | 17.46 | 01-JAN-10:10 | 658.71 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 455.06 | 168.34 | 01-JAN-00:10 | 216675.97 | 09-JAN-07:10 |
ExteriorEquipment:Electricity | 11.69 | 168.34 | 01-JAN-00:10 | 840.16 | 04-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 11.69 | 168.34 | 01-JAN-00:10 | 840.16 | 04-JAN-08:20 |
ElectricityPurchased:Facility | 1445.28 | 12315.29 | 26-MAR-17:30 | 253237.92 | 09-JAN-08:10 |
ElectricityPurchased:Plant | 1445.28 | 12315.29 | 26-MAR-17:30 | 253237.92 | 09-JAN-08:10 |
Cogeneration:ElectricityPurchased | 1445.28 | 12315.29 | 26-MAR-17:30 | 253237.92 | 09-JAN-08:10 |
General:Cogeneration:ElectricityPurchased | 1445.28 | 12315.29 | 26-MAR-17:30 | 253237.92 | 09-JAN-08:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1445.28 | 12315.29 | 26-MAR-17:30 | 253237.92 | 09-JAN-08:10 |
ElectricityNet:Plant | 1445.28 | 12315.29 | 26-MAR-17:30 | 253237.92 | 09-JAN-08:10 |
Cogeneration:ElectricityNet | 1445.28 | 12315.29 | 26-MAR-17:30 | 253237.92 | 09-JAN-08:10 |
General:Cogeneration:ElectricityNet | 1445.28 | 12315.29 | 26-MAR-17:30 | 253237.92 | 09-JAN-08:10 |
Heating:Electricity | 236.97 | 0.00 | 01-JAN-00:10 | 208488.79 | 09-JAN-07:10 |
General:Heating:Electricity | 236.97 | 0.00 | 01-JAN-00:10 | 208488.79 | 09-JAN-07:10 |
Fans:Electricity | 94.35 | 0.00 | 01-JAN-00:10 | 33603.97 | 17-JUL-15:30 |
General:Fans:Electricity | 94.35 | 0.00 | 01-JAN-00:10 | 33603.97 | 17-JUL-15:30 |
ExteriorLights:Electricity | 51.81 | 0.00 | 01-JAN-08:20 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 51.81 | 0.00 | 01-JAN-08:20 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 112.05 | 0.00 | 01-JAN-00:10 | 80132.97 | 17-JUL-16:00 |
General:Cooling:Electricity | 112.05 | 0.00 | 01-JAN-00:10 | 80132.97 | 17-JUL-16:00 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 04-JAN-18:10 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 04-JAN-18:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 04-JAN-18:10 |
WIRED_LTG_ELECTRICITY | 6.54 | 0.00 | 01-JAN-00:10 | 702.61 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 434.87 | 1886.44 | 05-JAN-06:10 | 148660.08 | 09-JAN-10:00 |
NaturalGas:HVAC | 296.90 | 0.00 | 01-JAN-00:10 | 139081.09 | 29-DEC-08:20 |
Heating:NaturalGas | 296.90 | 0.00 | 01-JAN-00:10 | 139081.09 | 29-DEC-08:20 |
General:Heating:NaturalGas | 296.90 | 0.00 | 01-JAN-00:10 | 139081.09 | 29-DEC-08:20 |
NaturalGas:Plant | 137.96 | 1886.44 | 04-JAN-05:10 | 12174.28 | 16-FEB-12:20 |
WaterSystems:NaturalGas | 137.96 | 1886.44 | 04-JAN-05:10 | 12174.28 | 16-FEB-12:20 |
Water Heater:WaterSystems:NaturalGas | 137.96 | 1886.44 | 04-JAN-05:10 | 12174.28 | 16-FEB-12:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2008.40 | 0.00 | 01-JAN-00:10 | 508360.34 | 09-JAN-07:10 |
EnergyTransfer:Building | 1042.82 | 0.00 | 01-JAN-00:10 | 203735.99 | 09-JAN-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 197.09 | 0.00 | 01-JAN-00:10 | 29189.86 | 05-SEP-07:20 |
Heating:EnergyTransfer | 229.00 | 0.00 | 01-JAN-00:10 | 203137.47 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.07 | 0.00 | 01-JAN-00:10 | 6955.62 | 09-JAN-07:10 |
General:Heating:EnergyTransfer | 229.00 | 0.00 | 01-JAN-00:10 | 203137.47 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.07 | 0.00 | 01-JAN-00:10 | 6955.62 | 09-JAN-07:10 |
Cooling:EnergyTransfer | 813.82 | 0.00 | 01-JAN-00:10 | 182295.59 | 17-JUL-15:40 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 197.02 | 0.00 | 01-JAN-00:10 | 29189.86 | 05-SEP-07:20 |
General:Cooling:EnergyTransfer | 813.82 | 0.00 | 01-JAN-00:10 | 182295.59 | 17-JUL-15:40 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 197.02 | 0.00 | 01-JAN-00:10 | 29189.86 | 05-SEP-07:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 54.17 | 0.00 | 01-JAN-00:10 | 18124.54 | 11-JAN-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 30.80 | 0.00 | 01-JAN-00:10 | 18124.54 | 11-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 30.80 | 0.00 | 01-JAN-00:10 | 18124.54 | 11-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 23.37 | 0.00 | 01-JAN-00:10 | 12623.18 | 17-JUL-14:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 23.37 | 0.00 | 01-JAN-00:10 | 12623.18 | 17-JUL-14:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 25.48 | 0.00 | 01-JAN-00:10 | 10775.51 | 09-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.02 | 0.00 | 01-JAN-00:10 | 10775.51 | 09-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.02 | 0.00 | 01-JAN-00:10 | 10775.51 | 09-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 11.46 | 0.00 | 01-JAN-00:10 | 6033.64 | 17-JUL-15:40 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 11.46 | 0.00 | 01-JAN-00:10 | 6033.64 | 17-JUL-15:40 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 25.26 | 0.00 | 01-JAN-00:10 | 6176.41 | 17-JUL-16:00 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 9.86 | 0.00 | 01-JAN-00:10 | 5212.42 | 09-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 9.86 | 0.00 | 01-JAN-00:10 | 5212.42 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 15.39 | 0.00 | 01-JAN-00:10 | 6176.41 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 15.39 | 0.00 | 01-JAN-00:10 | 6176.41 | 17-JUL-16:00 |
EnergyTransfer:Zone:CORE_MID | 123.81 | 0.00 | 01-JAN-00:10 | 22451.17 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 2.51 | 0.00 | 01-JAN-00:10 | 22451.17 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 2.51 | 0.00 | 01-JAN-00:10 | 22451.17 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 121.31 | 0.00 | 01-JAN-00:10 | 20299.53 | 05-SEP-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 121.31 | 0.00 | 01-JAN-00:10 | 20299.53 | 05-SEP-07:20 |
EnergyTransfer:Zone:CORE_TOP | 119.99 | 0.00 | 01-JAN-00:10 | 27954.17 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 13.55 | 0.00 | 01-JAN-00:10 | 27954.17 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 13.55 | 0.00 | 01-JAN-00:10 | 27954.17 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 106.44 | 0.00 | 01-JAN-00:10 | 21362.85 | 17-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 106.44 | 0.00 | 01-JAN-00:10 | 21362.85 | 17-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 46.11 | 0.00 | 01-JAN-00:10 | 10362.71 | 30-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 24.16 | 0.00 | 01-JAN-00:10 | 10362.71 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 24.16 | 0.00 | 01-JAN-00:10 | 10362.71 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 21.94 | 0.00 | 01-JAN-00:10 | 7386.57 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 21.94 | 0.00 | 01-JAN-00:10 | 7386.57 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 39.56 | 0.00 | 01-JAN-00:10 | 10329.48 | 07-AUG-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 13.86 | 0.00 | 01-JAN-00:10 | 10161.24 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 13.86 | 0.00 | 01-JAN-00:10 | 10161.24 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 25.70 | 0.00 | 01-JAN-00:10 | 10329.48 | 07-AUG-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 25.70 | 0.00 | 01-JAN-00:10 | 10329.48 | 07-AUG-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 62.15 | 0.00 | 01-JAN-00:10 | 14533.88 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 16.91 | 0.00 | 01-JAN-00:10 | 14533.88 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 16.91 | 0.00 | 01-JAN-00:10 | 14533.88 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 45.24 | 0.00 | 01-JAN-00:10 | 14373.82 | 01-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 45.24 | 0.00 | 01-JAN-00:10 | 14373.82 | 01-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 39.34 | 0.00 | 01-JAN-00:10 | 10931.42 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 0.00 | 01-JAN-00:10 | 10931.42 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 0.00 | 01-JAN-00:10 | 10931.42 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 24.42 | 0.00 | 01-JAN-00:10 | 10730.93 | 17-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 24.42 | 0.00 | 01-JAN-00:10 | 10730.93 | 17-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 31.78 | 0.00 | 01-JAN-00:10 | 7502.72 | 09-JAN-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 12.93 | 0.00 | 01-JAN-00:10 | 7502.72 | 09-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 12.93 | 0.00 | 01-JAN-00:10 | 7502.72 | 09-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 18.85 | 0.00 | 01-JAN-00:10 | 5771.77 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 18.85 | 0.00 | 01-JAN-00:10 | 5771.77 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 30.51 | 0.00 | 01-JAN-00:10 | 8491.15 | 17-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 6.89 | 0.00 | 01-JAN-00:10 | 8223.18 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 6.89 | 0.00 | 01-JAN-00:10 | 8223.18 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 23.62 | 0.00 | 01-JAN-00:10 | 8491.15 | 17-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 23.62 | 0.00 | 01-JAN-00:10 | 8491.15 | 17-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 60.14 | 0.00 | 01-JAN-00:10 | 16844.95 | 09-JAN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 26.15 | 0.00 | 01-JAN-00:10 | 16844.95 | 09-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 26.15 | 0.00 | 01-JAN-00:10 | 16844.95 | 09-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 33.99 | 0.00 | 01-JAN-00:10 | 13148.51 | 17-JUL-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 33.99 | 0.00 | 01-JAN-00:10 | 13148.51 | 17-JUL-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 28.81 | 0.00 | 01-JAN-00:10 | 8645.41 | 09-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 7.37 | 0.00 | 01-JAN-00:10 | 8645.41 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 7.37 | 0.00 | 01-JAN-00:10 | 8645.41 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 21.45 | 0.00 | 01-JAN-00:10 | 8448.62 | 17-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 21.45 | 0.00 | 01-JAN-00:10 | 8448.62 | 17-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 36.26 | 0.00 | 01-JAN-00:10 | 8566.39 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 12.43 | 0.00 | 01-JAN-00:10 | 8566.39 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 12.43 | 0.00 | 01-JAN-00:10 | 8566.39 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 23.83 | 0.00 | 01-JAN-00:10 | 6685.28 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 23.83 | 0.00 | 01-JAN-00:10 | 6685.28 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 32.88 | 0.00 | 01-JAN-00:10 | 10286.56 | 07-AUG-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 7.08 | 0.00 | 01-JAN-00:10 | 8902.78 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 7.08 | 0.00 | 01-JAN-00:10 | 8902.78 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 25.79 | 0.00 | 01-JAN-00:10 | 10286.56 | 07-AUG-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 25.79 | 0.00 | 01-JAN-00:10 | 10286.56 | 07-AUG-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 56.30 | 0.00 | 01-JAN-00:10 | 13663.93 | 01-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 7.88 | 0.00 | 01-JAN-00:10 | 12391.75 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 7.88 | 0.00 | 01-JAN-00:10 | 12391.75 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 48.42 | 0.00 | 01-JAN-00:10 | 13663.93 | 01-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 48.42 | 0.00 | 01-JAN-00:10 | 13663.93 | 01-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 33.15 | 0.00 | 01-JAN-00:10 | 10126.83 | 17-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 7.59 | 0.00 | 01-JAN-00:10 | 8830.19 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 7.59 | 0.00 | 01-JAN-00:10 | 8830.19 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 25.56 | 0.00 | 01-JAN-00:10 | 10126.83 | 17-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 25.56 | 0.00 | 01-JAN-00:10 | 10126.83 | 17-JUL-17:00 |
PlantLoopHeatingDemand:Facility | 55.07 | 0.00 | 01-JAN-00:10 | 6985.87 | 21-FEB-12:20 |
PlantLoopHeatingDemand:Plant | 55.07 | 0.00 | 01-JAN-00:10 | 6985.87 | 21-FEB-12:20 |
WaterSystems:PlantLoopHeatingDemand | 55.07 | 0.00 | 01-JAN-00:10 | 6985.87 | 21-FEB-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 55.07 | 0.00 | 01-JAN-00:10 | 6985.87 | 21-FEB-12:20 |
EnergyTransfer:HVAC | 910.51 | 0.00 | 01-JAN-00:10 | 305027.33 | 09-JAN-07:10 |
HeatingCoils:EnergyTransfer | 474.50 | 0.00 | 01-JAN-00:10 | 305027.33 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 436.01 | 0.00 | 01-JAN-00:10 | 285989.78 | 07-SEP-15:00 |
EnergyTransfer:Plant | 55.07 | 0.00 | 01-JAN-00:10 | 6985.87 | 21-FEB-12:20 |
WaterSystems:EnergyTransfer | 55.07 | 0.00 | 01-JAN-00:10 | 6985.87 | 21-FEB-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 55.07 | 0.00 | 01-JAN-00:10 | 6985.87 | 21-FEB-12:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.067 | -197.024 | 0.000 | 0.000 | 33.082 | 55.599 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -127.891 |
CORE_MID | 0.000 | 0.000 | 2.508 | -121.305 | 0.000 | 0.000 | 34.418 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -86.645 |
CORE_TOP | 0.000 | 0.000 | 13.554 | -106.436 | 0.000 | 0.000 | 35.269 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -113.411 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 24.162 | -21.944 | 0.000 | 0.000 | 7.654 | 6.807 | 24.333 | 17.044 | 0.000 | 0.108 | 0.001 | 0.000 | -38.652 | 0.000 | -11.291 | -8.220 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 13.864 | -25.696 | 0.000 | 0.000 | 4.744 | 4.263 | 15.404 | 37.797 | 0.000 | 0.069 | 0.000 | 0.000 | -24.390 | 0.000 | -7.684 | -18.371 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 16.915 | -45.237 | 0.000 | 0.000 | 7.401 | 6.683 | 24.332 | 81.603 | 0.000 | 0.102 | 0.001 | 0.000 | -36.533 | 0.000 | -11.880 | -43.387 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 14.919 | -24.423 | 0.000 | 0.000 | 4.798 | 4.272 | 15.403 | 36.104 | 0.000 | 0.069 | 0.000 | 0.000 | -25.574 | 0.000 | -7.710 | -17.858 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 12.930 | -18.852 | 0.000 | 0.000 | 7.627 | 6.791 | 24.333 | 17.358 | 0.000 | 0.063 | 0.000 | 0.000 | -39.833 | 0.000 | -6.296 | -4.121 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 6.890 | -23.617 | 0.000 | 0.000 | 4.703 | 4.256 | 15.404 | 37.898 | 0.000 | 0.038 | 0.001 | 0.000 | -25.532 | 0.000 | -4.351 | -15.687 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 26.150 | -33.990 | 0.000 | 0.000 | 7.568 | 6.673 | 24.332 | 82.293 | 0.000 | 1.237 | 0.004 | 0.000 | -38.340 | 0.000 | -46.679 | -29.245 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 7.366 | -21.446 | 0.000 | 0.000 | 4.748 | 4.264 | 15.403 | 36.310 | 0.000 | 0.038 | 0.001 | 0.000 | -26.769 | 0.000 | -4.364 | -15.551 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 12.432 | -23.833 | 0.000 | 0.000 | 7.550 | 6.807 | 24.333 | 16.727 | 0.000 | 0.091 | 6.340 | 0.000 | -40.540 | 0.000 | -9.907 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 7.082 | -25.795 | 0.000 | 0.000 | 3.464 | 4.263 | 15.404 | 37.473 | 0.000 | 0.057 | 0.000 | 0.000 | -25.541 | 0.000 | -6.742 | -9.663 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 7.881 | -48.422 | 0.000 | 0.000 | 7.296 | 6.683 | 24.332 | 81.228 | 0.000 | 0.086 | 0.002 | 0.000 | -38.342 | 0.000 | -10.426 | -30.317 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 7.593 | -25.560 | 0.000 | 0.000 | 4.731 | 4.272 | 15.403 | 35.903 | 0.000 | 0.058 | 0.001 | 0.000 | -26.817 | 0.000 | -6.757 | -8.826 |
TOPFLOOR_PLENUM | 30.801 | -23.373 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.108 | 9.675 | 0.000 | 0.000 | 0.000 | -17.210 | -0.000 |
MIDFLOOR_PLENUM | 14.021 | -11.462 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.132 | 14.375 | 0.000 | 0.000 | 0.000 | -17.067 | -0.000 |
FIRSTFLOOR_PLENUM | 9.864 | -15.395 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.102 | 19.285 | 0.000 | 0.000 | 0.000 | -13.857 | -0.000 |
Total Facility | 54.687 | -50.230 | 174.314 | -763.579 | 0.000 | 0.000 | 175.053 | 232.828 | 705.434 | 517.737 | 0.000 | 2.357 | 49.686 | 0.000 | -386.864 | 0.000 | -182.220 | -529.192 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 14-AUG-05:12 | 0.00 | 0.00 | 0.00 | -42355.13 | 0.00 | 0.00 | 313.25 | 548.43 | 4989.51 | 0.00 | 0.00 | 0.00 | 36503.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 31-JUL-05:12 | 0.00 | 0.00 | 0.00 | -30593.28 | 0.00 | 0.00 | 324.92 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 26694.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 05-SEP-05:12 | 0.00 | 0.00 | 0.00 | -32341.46 | 0.00 | 0.00 | 314.71 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 28452.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-18:31 | 0.00 | 0.00 | 0.00 | -11527.91 | 0.00 | 0.00 | 0.00 | 27.57 | 386.10 | 4135.31 | 0.00 | 115.93 | 6862.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JUL-08:51 | 0.00 | 0.00 | 0.00 | -15955.52 | 0.00 | 0.00 | 12.51 | 17.46 | 302.86 | 11827.95 | 0.00 | 0.00 | 3945.92 | 0.00 | -0.00 | 0.00 | -151.18 | 0.00 |
PERIMETER_TOP_ZN_1 | 15-OCT-14:32 | 0.00 | 0.00 | 0.00 | -19898.46 | 0.00 | 0.00 | 22.87 | 27.57 | 478.41 | 15499.71 | 0.00 | 0.00 | 4250.69 | 0.00 | -0.00 | 0.00 | -380.80 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-16:51 | 0.00 | 0.00 | 0.00 | -17874.33 | 0.00 | 0.00 | 11.24 | 17.46 | 302.86 | 12978.39 | 0.00 | 0.00 | 4675.11 | 0.00 | -0.00 | 0.00 | -110.72 | 0.00 |
PERIMETER_BOT_ZN_3 | 04-SEP-16:11 | 0.00 | 0.00 | 0.00 | -8771.81 | 0.00 | 0.00 | 29.57 | 27.57 | 478.42 | 1861.72 | 0.00 | 72.01 | 6302.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 16-JUL-09:41 | 0.00 | 0.00 | 0.00 | -12461.31 | 0.00 | 0.00 | 14.76 | 17.46 | 302.86 | 9811.27 | 0.00 | 0.00 | 2375.67 | 0.00 | -0.00 | 0.00 | -60.70 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-14:51 | 0.00 | 0.00 | 0.00 | -16214.69 | 0.00 | 0.00 | 22.02 | 27.57 | 478.41 | 12268.18 | 0.00 | 58.14 | 3360.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 16-JUL-18:21 | 0.00 | 0.00 | 0.00 | -14321.16 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 11786.01 | 0.00 | 21.17 | 2252.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-18:22 | 0.00 | 0.00 | 0.00 | -10764.57 | 0.00 | 0.00 | 0.00 | 27.57 | 386.10 | 4417.74 | 0.00 | 97.67 | 5835.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 06-AUG-08:41 | 0.00 | 0.00 | 0.00 | -16292.28 | 0.00 | 0.00 | 11.59 | 17.46 | 302.86 | 13002.84 | 0.00 | 0.00 | 3007.70 | 0.00 | -0.00 | 0.00 | -50.16 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-14:51 | 0.00 | 0.00 | 0.00 | -18716.53 | 0.00 | 0.00 | 20.47 | 27.57 | 478.41 | 12193.22 | 0.00 | 81.25 | 5915.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 16-JUL-17:01 | 0.00 | 0.00 | 0.00 | -17216.78 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 13310.02 | 0.00 | 31.97 | 3612.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 17-JUL-14:50 | 0.00 | -12622.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.73 | 12615.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 05-SEP-06:10 | 0.00 | -6637.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6690.72 | 0.00 | -0.00 | 0.00 | -53.05 | 0.00 |
FIRSTFLOOR_PLENUM | 17-JUL-12:08 | 0.00 | -6450.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.28 | 6396.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-SEP-06:03 | 0.00 | -10351.44 | 0.00 | -184086.54 | 0.00 | 0.00 | 3473.02 | 8197.57 | 21098.80 | 724.09 | 0.00 | 0.00 | 169259.61 | 0.00 | -4190.19 | 0.00 | -4124.94 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-07:12 | 0.00 | 0.00 | 14406.85 | 0.00 | 0.00 | 0.00 | 875.16 | 1645.36 | 8796.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25724.16 |
CORE_MID | 09-JAN-05:01 | 0.00 | 0.00 | 25694.58 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -28348.37 |
CORE_TOP | 30-JAN-05:11 | 0.00 | 0.00 | 32070.91 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -34724.70 |
PERIMETER_TOP_ZN_3 | 30-JAN-05:11 | 0.00 | 0.00 | 11270.72 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3336.68 | 0.00 | -1707.32 | -6786.16 |
PERIMETER_TOP_ZN_2 | 30-JAN-05:11 | 0.00 | 0.00 | 13093.73 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2224.08 | 0.00 | -1153.45 | -10070.36 |
PERIMETER_TOP_ZN_1 | 30-JAN-05:11 | 0.00 | 0.00 | 17421.17 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3466.19 | 0.00 | -1741.06 | -12773.36 |
PERIMETER_TOP_ZN_4 | 30-JAN-05:11 | 0.00 | 0.00 | 14789.59 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2287.12 | 0.00 | -1159.52 | -11697.10 |
PERIMETER_BOT_ZN_3 | 29-JAN-20:12 | 0.00 | 0.00 | 8076.13 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4407.35 | 0.00 | -648.22 | -3451.30 |
PERIMETER_BOT_ZN_2 | 09-JAN-02:41 | 0.00 | 0.00 | 9939.18 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2980.28 | 0.00 | -519.72 | -6793.32 |
PERIMETER_BOT_ZN_1 | 09-JAN-08:00 | 0.00 | 0.00 | 16844.71 | 0.00 | 0.00 | 0.00 | 262.94 | 346.86 | 637.88 | 0.00 | 0.00 | 0.00 | 15398.50 | 0.00 | -4027.74 | 0.00 | -29463.14 | 0.00 |
PERIMETER_BOT_ZN_4 | 09-JAN-02:41 | 0.00 | 0.00 | 10769.19 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2909.99 | 0.00 | -520.99 | -7692.36 |
PERIMETER_MID_ZN_3 | 08-JAN-17:32 | 0.00 | 0.00 | 9215.37 | 0.00 | 0.00 | 0.00 | 59.37 | 57.81 | 478.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4386.41 | 0.00 | -702.14 | -4722.42 |
PERIMETER_MID_ZN_2 | 30-JAN-05:01 | 0.00 | 0.00 | 11778.53 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2315.93 | 0.00 | -1027.00 | -8789.76 |
PERIMETER_MID_ZN_1 | 09-JAN-02:51 | 0.00 | 0.00 | 14930.14 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4364.41 | 0.00 | -1216.76 | -9908.41 |
PERIMETER_MID_ZN_4 | 30-JAN-05:01 | 0.00 | 0.00 | 11894.71 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2381.45 | 0.00 | -1027.97 | -8839.44 |
TOPFLOOR_PLENUM | 11-JAN-06:12 | 19569.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -121.77 | -19447.79 |
MIDFLOOR_PLENUM | 09-JAN-07:04 | 11123.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -408.19 | -10714.90 |
FIRSTFLOOR_PLENUM | 22-MAY-05:01 | 8338.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -928.13 | -7410.80 |
Total Facility | 09-JAN-06:01 | 29301.57 | 0.00 | 193319.86 | 0.00 | 0.00 | 0.00 | 2546.67 | 1072.56 | 17291.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -45531.53 | 0.00 | -8161.04 | -189839.60 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 6.3519 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.6043 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 6.0164 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0240 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.4295 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.7949 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.1760 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0762 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 3.0082 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0757 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.2147 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0745 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1988 | 3.1988 | 0.6366 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3368 | 2.3368 | 0.6380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4568 | 2.4568 | 0.6363 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7793 | 0.7793 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9187 | 0.9187 | 0.0854 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2309 | 1.2309 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0438 | 1.0438 | 0.0845 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6028 | 0.6028 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7538 | 0.7538 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9765 | 0.9765 | 0.1348 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8201 | 0.8201 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6774 | 0.6774 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9103 | 0.9103 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1257 | 1.1257 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9662 | 0.9662 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 6.3519 | 5.6043 | 6.3519 | 1.0762 | 0.0000 | 1.0000 |
PACU_VAV_MID | 6.0164 | 5.0240 | 6.0164 | 1.0757 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.4295 | 5.7949 | 6.4295 | 1.0745 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5994 | 1.5994 | 0.6366 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1684 | 1.1684 | 0.6380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2284 | 1.2284 | 0.6363 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3896 | 0.3896 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4593 | 0.4593 | 0.0854 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6155 | 0.6155 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5219 | 0.5219 | 0.0845 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3014 | 0.3014 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3769 | 0.3769 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4882 | 0.4882 | 0.1348 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4101 | 0.4101 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3387 | 0.3387 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4552 | 0.4552 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5628 | 0.5628 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4831 | 0.4831 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.1760 | 1.0762 | 1.0762 | 1.0762 | 0.0000 | 1.0000 |
PACU_VAV_MID | 3.0082 | 1.0757 | 1.0757 | 1.0757 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.2147 | 1.0745 | 1.0745 | 1.0745 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 370.33 |
Number of hours cooling loads not met | 104.83 |
Number of hours not met | 475.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 236.97 | 208488.79 | 296.90 | 139081.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 112.05 | 80132.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 232.83 | 25003.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 51.81 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.69 | 840.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 94.35 | 33603.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 137.96 | 12174.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1445.28 |
Natural Gas | 0.00 | 434.87 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1880.15 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.73 |
Space Heating | 47.56 |
Space Cooling | 22.49 |
Fans (All) | 18.94 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 290.09 |
Subtotal | 290.09 |
Natural Gas [MJ/m2] | |
Space Heating | 59.59 |
Service Water Heating | 27.69 |
Miscellaneous (All) | 87.28 |
Subtotal | 87.28 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.38 |
Space Heating | 28.40 |
Space Cooling | 5.96 |
Fans (All) | 5.02 |
Service Water Heating | 7.34 |
Receptacle Equipment | 37.52 |
Miscellaneous | 3.38 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 737. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8758.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8740.50 | 19.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8743.67 | 16.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8738.00 | 22.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8749.67 | 10.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8752.33 | 7.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8745.67 | 14.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8742.00 | 18.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8744.33 | 15.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8738.67 | 21.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8689.50 | 70.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8689.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 70.50 | 0.00 | 0.00 | 0.00 |
Average | 8747.66 | 12.34 | 0.00 | 0.00 | 0.00 |
Sum | 157457.83 | 222.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128297.67 | 6.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 6.33 | 0.00 | 0.00 | 0.00 |
Average | 34142.98 | 0.35 | 0.00 | 0.00 | 0.00 |
Sum | 614573.67 | 6.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8726.67 | 33.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8751.67 | 8.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8756.67 | 3.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8754.33 | 5.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8748.50 | 11.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8752.33 | 7.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8751.00 | 9.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8756.67 | 3.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8747.50 | 12.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8750.17 | 9.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8749.33 | 10.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8747.00 | 13.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8726.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 33.33 | 0.00 | 0.00 | 0.00 |
Average | 8752.46 | 7.54 | 0.00 | 0.00 | 0.00 |
Sum | 157544.33 | 135.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128272.83 | 31.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128287.33 | 16.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128297.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128297.33 | 31.17 | 0.00 | 0.00 | 0.00 |
Average | 34140.31 | 3.03 | 0.00 | 0.00 | 0.00 |
Sum | 614525.50 | 54.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.746132E+10 | 8939.10 | 19-JAN-16:50 | -6.4 | -8.0 | 0.181254E+10 | 2606.63 | 20-JAN-10:20 | -2.9 | -5.7 |
February | 0.840697E+10 | 16291.39 | 28-FEB-08:02 | -4.5 | -4.7 | 0.173397E+10 | 2606.63 | 28-FEB-10:20 | 2.03 | 0.11 |
March | 0.126273E+11 | 16294.52 | 01-MAR-17:00 | 7.80 | 3.22 | 0.212316E+10 | 2606.64 | 01-MAR-10:00 | 7.80 | 3.22 |
April | 0.145168E+11 | 18833.45 | 26-APR-08:00 | 10.00 | 4.73 | 0.190863E+10 | 2606.64 | 04-APR-09:09 | 10.00 | 4.73 |
May | 0.178987E+11 | 41168.15 | 22-MAY-05:01 | -0.6 | -0.6 | 0.207344E+10 | 2606.84 | 02-MAY-13:09 | -0.6 | -0.6 |
June | 0.238307E+11 | 40895.32 | 26-JUN-05:12 | 10.33 | 9.12 | 0.207067E+10 | 2606.68 | 29-JUN-09:20 | 25.17 | 12.64 |
July | 0.251131E+11 | 41105.60 | 31-JUL-05:12 | 14.60 | 10.97 | 0.192620E+10 | 2606.71 | 13-JUL-09:00 | 14.60 | 10.97 |
August | 0.262815E+11 | 42351.49 | 14-AUG-05:12 | 12.03 | 9.76 | 0.216180E+10 | 2606.66 | 24-AUG-09:00 | 20.00 | 12.25 |
September | 0.216904E+11 | 41291.52 | 06-SEP-05:12 | 15.00 | 12.76 | 0.191852E+10 | 2606.73 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.176628E+11 | 37309.20 | 19-OCT-06:02 | 12.02 | 5.45 | 0.199008E+10 | 2606.65 | 13-OCT-09:20 | 12.02 | 5.45 |
November | 0.125525E+11 | 17913.56 | 03-NOV-16:00 | 14.30 | 7.69 | 0.195059E+10 | 2606.64 | 03-NOV-09:09 | 14.30 | 7.69 |
December | 0.898278E+10 | 14045.76 | 07-DEC-08:20 | -1.5 | -2.6 | 0.184210E+10 | 2606.64 | 07-DEC-10:09 | 3.35 | 1.22 |
Annual Sum or Average | 0.197025E+12 | 0.235117E+11 | ||||||||
Minimum of Months | 0.746132E+10 | 8939.10 | -6.4 | -8.0 | 0.173397E+10 | 2606.63 | -2.9 | -5.7 | ||
Maximum of Months | 0.262815E+11 | 42351.49 | 15.00 | 12.76 | 0.216180E+10 | 2606.84 | 25.17 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 391851.68 | 130.56 | 14-JAN-13:25 | 10.00 | 4.73 | 0.00 | 0.00 | 01-JAN-00:10 | 10.00 | 4.73 |
February | 54739920.63 | 1507.94 | 26-FEB-14:35 | 16.33 | 6.24 | 0.00 | 0.00 | 01-FEB-00:10 | 16.33 | 6.24 |
March | 0.235879E+09 | 1936.88 | 22-MAR-15:20 | 11.10 | 4.12 | 0.00 | 0.00 | 01-MAR-00:10 | 11.10 | 4.12 |
April | 0.925071E+09 | 5747.04 | 25-APR-15:00 | 17.00 | 7.46 | 0.00 | 0.00 | 01-APR-00:10 | 17.00 | 7.46 |
May | 0.216352E+10 | 8894.95 | 19-MAY-15:00 | 28.30 | 14.88 | 0.00 | 0.00 | 01-MAY-00:10 | 28.30 | 14.88 |
June | 0.479136E+10 | 10101.46 | 23-JUN-13:30 | 31.40 | 15.21 | 0.00 | 0.00 | 01-JUN-00:10 | 31.40 | 15.21 |
July | 0.648999E+10 | 12623.18 | 17-JUL-14:50 | 36.20 | 17.00 | 0.00 | 0.00 | 01-JUL-00:10 | 36.20 | 17.00 |
August | 0.555525E+10 | 11442.93 | 07-AUG-15:30 | 32.50 | 16.07 | 0.00 | 0.00 | 01-AUG-00:10 | 32.50 | 16.07 |
September | 0.253000E+10 | 8526.88 | 05-SEP-14:20 | 24.40 | 15.02 | 0.00 | 0.00 | 01-SEP-00:10 | 24.40 | 15.02 |
October | 0.602604E+09 | 5311.77 | 18-OCT-15:20 | 24.80 | 11.42 | 0.00 | 0.00 | 01-OCT-00:10 | 24.80 | 11.42 |
November | 25088172.40 | 1107.53 | 03-NOV-14:50 | 14.67 | 7.71 | 0.00 | 0.00 | 01-NOV-00:10 | 14.67 | 7.71 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 |
Annual Sum or Average | 0.233739E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.1 | -4.2 | 0.00 | 0.00 | -2.1 | -4.2 | ||
Maximum of Months | 0.648999E+10 | 12623.18 | 36.20 | 17.00 | 0.00 | 0.00 | 36.20 | 17.00 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12101324.77 | 3123.28 | 26-JAN-05:01 | -22.2 | -22.7 | 0.00 | 0.00 | 01-JAN-00:10 | -22.2 | -22.7 |
February | 11254973.70 | 3779.78 | 01-FEB-05:01 | -25.0 | -25.2 | 0.00 | 0.00 | 01-FEB-00:10 | -25.0 | -25.2 |
March | 29765374.41 | 3654.87 | 04-MAR-05:02 | -19.1 | -19.6 | 0.00 | 0.00 | 01-MAR-00:10 | -19.1 | -19.6 |
April | 0.177096E+09 | 2469.47 | 29-APR-05:01 | -7.7 | -8.6 | 0.00 | 0.00 | 01-APR-00:10 | -7.7 | -8.6 |
May | 0.634390E+09 | 3080.90 | 19-MAY-16:00 | 27.80 | 14.54 | 0.00 | 0.00 | 01-MAY-00:10 | 27.80 | 14.54 |
June | 0.235498E+10 | 4088.28 | 23-JUN-15:30 | 27.50 | 14.33 | 0.00 | 0.00 | 01-JUN-00:10 | 27.50 | 14.33 |
July | 0.351790E+10 | 6033.64 | 17-JUL-15:40 | 36.83 | 17.19 | 0.00 | 0.00 | 01-JUL-00:10 | 36.83 | 17.19 |
August | 0.312324E+10 | 6101.21 | 07-AUG-06:10 | 19.45 | 10.91 | 0.00 | 0.00 | 01-AUG-00:10 | 19.45 | 10.91 |
September | 0.137902E+10 | 6637.08 | 05-SEP-06:10 | 18.90 | 13.05 | 0.00 | 0.00 | 01-SEP-00:10 | 18.90 | 13.05 |
October | 0.195790E+09 | 1792.70 | 18-OCT-15:50 | 24.50 | 11.12 | 0.00 | 0.00 | 01-OCT-00:10 | 24.50 | 11.12 |
November | 20629015.00 | 1744.60 | 21-NOV-06:01 | -9.3 | -10.6 | 0.00 | 0.00 | 01-NOV-00:10 | -9.3 | -10.6 |
December | 5595605.20 | 3187.58 | 29-DEC-05:01 | -25.0 | -25.3 | 0.00 | 0.00 | 01-DEC-00:10 | -25.0 | -25.3 |
Annual Sum or Average | 0.114618E+11 | 0.00 | ||||||||
Minimum of Months | 5595605.20 | 1744.60 | -25.0 | -25.3 | 0.00 | 0.00 | -25.0 | -25.3 | ||
Maximum of Months | 0.351790E+10 | 6637.08 | 36.83 | 17.19 | 0.00 | 0.00 | 36.83 | 17.19 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58870937.03 | 3330.21 | 06-JAN-05:01 | -24.5 | -24.9 | 0.00 | 0.00 | 01-JAN-00:10 | -24.5 | -24.9 |
February | 67043973.49 | 3448.30 | 04-FEB-05:01 | -20.4 | -20.8 | 0.00 | 0.00 | 01-FEB-00:10 | -20.4 | -20.8 |
March | 0.135402E+09 | 3094.91 | 01-MAR-07:01 | -9.6 | -10.3 | 0.00 | 0.00 | 01-MAR-00:10 | -9.6 | -10.3 |
April | 0.422970E+09 | 3388.14 | 29-APR-05:01 | -7.7 | -8.6 | 0.00 | 0.00 | 01-APR-00:10 | -7.7 | -8.6 |
May | 0.985245E+09 | 3256.65 | 19-MAY-16:00 | 27.80 | 14.54 | 0.00 | 0.00 | 01-MAY-00:10 | 27.80 | 14.54 |
June | 0.291279E+10 | 4304.68 | 29-JUN-15:10 | 32.02 | 14.63 | 0.00 | 0.00 | 01-JUN-00:10 | 32.02 | 14.63 |
July | 0.406315E+10 | 6450.21 | 17-JUL-12:08 | 35.18 | 16.48 | 0.00 | 0.00 | 01-JUL-00:10 | 35.18 | 16.48 |
August | 0.387718E+10 | 5900.96 | 07-AUG-16:00 | 32.20 | 16.16 | 0.00 | 0.00 | 01-AUG-00:10 | 32.20 | 16.16 |
September | 0.208147E+10 | 5903.13 | 05-SEP-07:10 | 18.98 | 12.62 | 0.00 | 0.00 | 01-SEP-00:10 | 18.98 | 12.62 |
October | 0.650943E+09 | 2674.88 | 18-OCT-16:00 | 24.40 | 11.02 | 0.00 | 0.00 | 01-OCT-00:10 | 24.40 | 11.02 |
November | 91520730.50 | 2114.51 | 10-NOV-07:02 | -4.5 | -5.4 | 0.00 | 0.00 | 01-NOV-00:10 | -4.5 | -5.4 |
December | 48304703.36 | 3207.40 | 29-DEC-05:01 | -25.0 | -25.3 | 0.00 | 0.00 | 01-DEC-00:10 | -25.0 | -25.3 |
Annual Sum or Average | 0.153949E+11 | 0.00 | ||||||||
Minimum of Months | 48304703.36 | 2114.51 | -25.0 | -25.3 | 0.00 | 0.00 | -25.0 | -25.3 | ||
Maximum of Months | 0.406315E+10 | 6450.21 | 35.18 | 16.48 | 0.00 | 0.00 | 35.18 | 16.48 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.399466E+10 | 4920.31 | 13-JAN-17:00 | 7.80 | 3.93 | 0.153257E+10 | 2263.74 | 13-JAN-16:00 | 7.80 | 3.93 |
February | 0.499314E+10 | 8262.52 | 28-FEB-17:00 | 10.00 | 4.31 | 0.150168E+10 | 2606.60 | 28-FEB-14:09 | 10.00 | 4.31 |
March | 0.714329E+10 | 8540.24 | 01-MAR-17:00 | 7.80 | 3.22 | 0.194792E+10 | 2606.60 | 01-MAR-14:20 | 7.80 | 3.22 |
April | 0.844112E+10 | 12040.74 | 25-APR-16:00 | 17.80 | 7.70 | 0.185270E+10 | 2606.64 | 17-APR-09:20 | 17.80 | 7.70 |
May | 0.106887E+11 | 27563.13 | 30-MAY-06:03 | 15.50 | 11.35 | 0.201575E+10 | 2606.67 | 04-MAY-13:09 | 15.50 | 11.35 |
June | 0.161094E+11 | 30332.71 | 26-JUN-05:12 | 10.33 | 9.12 | 0.206435E+10 | 2606.66 | 29-JUN-09:20 | 25.17 | 12.64 |
July | 0.178069E+11 | 30587.68 | 31-JUL-05:12 | 14.60 | 10.97 | 0.192225E+10 | 2606.67 | 13-JUL-09:00 | 14.60 | 10.97 |
August | 0.178485E+11 | 30489.15 | 14-AUG-05:12 | 12.03 | 9.76 | 0.215713E+10 | 2610.68 | 07-AUG-09:00 | 12.03 | 9.76 |
September | 0.132906E+11 | 29448.69 | 05-SEP-05:12 | 18.50 | 11.75 | 0.190587E+10 | 2606.70 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.938538E+10 | 12824.76 | 19-OCT-16:00 | 21.10 | 10.04 | 0.193958E+10 | 2608.00 | 31-OCT-13:30 | 8.05 | 1.63 |
November | 0.652565E+10 | 9304.57 | 03-NOV-16:00 | 14.30 | 7.69 | 0.177031E+10 | 2606.64 | 03-NOV-09:20 | 14.30 | 7.69 |
December | 0.507833E+10 | 5561.80 | 07-DEC-16:30 | 5.55 | 1.71 | 0.156602E+10 | 2508.15 | 07-DEC-14:00 | 5.55 | 1.71 |
Annual Sum or Average | 0.121306E+12 | 0.221761E+11 | ||||||||
Minimum of Months | 0.399466E+10 | 4920.31 | 5.55 | 1.71 | 0.150168E+10 | 2263.74 | 5.55 | 1.63 | ||
Maximum of Months | 0.178485E+11 | 30587.68 | 21.10 | 11.75 | 0.215713E+10 | 2610.68 | 25.17 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.212197E+10 | 4693.25 | 13-JAN-16:50 | 7.98 | 4.06 | 0.147081E+10 | 2194.42 | 13-JAN-16:00 | 7.80 | 3.93 |
February | 0.330483E+10 | 6964.56 | 28-FEB-17:00 | 10.00 | 4.31 | 0.140732E+10 | 2575.43 | 28-FEB-14:00 | 10.00 | 4.31 |
March | 0.569859E+10 | 7127.61 | 29-MAR-16:00 | 12.20 | 4.07 | 0.180838E+10 | 2606.53 | 23-MAR-13:50 | 12.20 | 4.07 |
April | 0.732863E+10 | 13053.62 | 25-APR-16:00 | 17.80 | 7.70 | 0.175881E+10 | 2606.62 | 25-APR-09:20 | 17.80 | 7.70 |
May | 0.985083E+10 | 16293.30 | 30-MAY-15:30 | 19.40 | 10.94 | 0.195681E+10 | 2606.69 | 02-MAY-13:20 | 19.40 | 10.94 |
June | 0.157766E+11 | 28607.72 | 26-JUN-06:02 | 13.03 | 10.64 | 0.205499E+10 | 2606.66 | 01-JUN-09:20 | 13.03 | 10.64 |
July | 0.179684E+11 | 31935.64 | 17-JUL-05:12 | 16.83 | 12.38 | 0.191867E+10 | 2606.66 | 13-JUL-09:00 | 16.83 | 12.38 |
August | 0.172597E+11 | 32304.72 | 07-AUG-05:12 | 17.77 | 10.09 | 0.214991E+10 | 2606.65 | 07-AUG-09:20 | 28.73 | 14.88 |
September | 0.118212E+11 | 32339.87 | 05-SEP-05:12 | 18.50 | 11.75 | 0.186580E+10 | 2606.69 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.759379E+10 | 12683.28 | 18-OCT-16:00 | 24.40 | 11.02 | 0.183787E+10 | 2606.61 | 19-OCT-13:20 | 21.10 | 10.10 |
November | 0.478591E+10 | 7444.62 | 03-NOV-16:00 | 14.30 | 7.69 | 0.163160E+10 | 2606.18 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.292605E+10 | 5151.38 | 07-DEC-16:25 | 5.55 | 1.71 | 0.146395E+10 | 2366.12 | 07-DEC-14:00 | 5.55 | 1.71 |
Annual Sum or Average | 0.106437E+12 | 0.213249E+11 | ||||||||
Minimum of Months | 0.212197E+10 | 4693.25 | 5.55 | 1.71 | 0.140732E+10 | 2194.42 | 5.55 | 1.71 | ||
Maximum of Months | 0.179684E+11 | 32339.87 | 24.40 | 12.38 | 0.214991E+10 | 2606.69 | 28.73 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11200178.34 | 721.23 | 14-JAN-17:05 | 8.90 | 4.06 | 0.302089E+09 | 406.72 | 05-JAN-14:39 | 8.90 | 4.06 |
February | 0.150537E+09 | 1101.64 | 27-FEB-16:10 | 17.78 | 6.92 | 0.280012E+09 | 500.81 | 27-FEB-16:30 | 15.55 | 6.44 |
March | 0.532451E+09 | 1155.14 | 29-MAR-16:00 | 12.20 | 4.07 | 0.347630E+09 | 518.92 | 29-MAR-15:00 | 12.20 | 4.07 |
April | 0.112173E+10 | 3372.24 | 07-APR-14:30 | 22.50 | 9.29 | 0.339808E+09 | 549.49 | 13-APR-13:20 | 12.97 | 7.01 |
May | 0.209876E+10 | 5279.57 | 19-MAY-16:00 | 27.80 | 14.54 | 0.392040E+09 | 549.50 | 04-MAY-13:20 | 27.80 | 14.54 |
June | 0.428773E+10 | 8062.18 | 21-JUN-06:03 | 17.38 | 13.20 | 0.428461E+09 | 549.50 | 01-JUN-09:20 | 17.38 | 13.20 |
July | 0.526075E+10 | 11527.86 | 16-JUL-18:31 | 32.40 | 17.11 | 0.403730E+09 | 549.51 | 21-JUL-13:20 | 25.97 | 12.49 |
August | 0.448154E+10 | 11331.61 | 06-AUG-16:11 | 35.40 | 16.13 | 0.447898E+09 | 549.50 | 07-AUG-09:20 | 28.73 | 14.88 |
September | 0.243941E+10 | 11250.42 | 04-SEP-15:41 | 32.70 | 16.52 | 0.374357E+09 | 549.50 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.110209E+10 | 2691.42 | 19-OCT-14:40 | 21.50 | 10.24 | 0.353393E+09 | 549.49 | 19-OCT-13:20 | 21.50 | 10.24 |
November | 0.400721E+09 | 1068.02 | 03-NOV-16:00 | 14.30 | 7.69 | 0.313346E+09 | 498.14 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 56995450.66 | 831.20 | 06-DEC-16:25 | 8.05 | 3.45 | 0.293807E+09 | 420.04 | 06-DEC-14:00 | 8.05 | 3.45 |
Annual Sum or Average | 0.219439E+11 | 0.427657E+10 | ||||||||
Minimum of Months | 11200178.34 | 721.23 | 8.05 | 3.45 | 0.280012E+09 | 406.72 | 8.05 | 3.45 | ||
Maximum of Months | 0.526075E+10 | 11527.86 | 35.40 | 17.11 | 0.447898E+09 | 549.51 | 28.73 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 37451991.10 | 540.73 | 20-JAN-10:30 | -2.8 | -5.5 | 0.193239E+09 | 272.89 | 20-JAN-10:39 | -2.6 | -5.4 |
February | 0.250152E+09 | 1670.65 | 27-FEB-10:30 | 13.05 | 4.83 | 0.185243E+09 | 347.87 | 28-FEB-10:39 | 2.97 | 0.62 |
March | 0.656164E+09 | 3660.42 | 23-MAR-10:10 | 8.40 | 1.62 | 0.239355E+09 | 347.88 | 01-MAR-10:00 | 8.40 | 1.62 |
April | 0.153008E+10 | 6331.55 | 25-APR-09:20 | 10.33 | 5.07 | 0.229512E+09 | 347.88 | 25-APR-09:20 | 10.33 | 5.07 |
May | 0.251286E+10 | 7818.53 | 19-MAY-08:50 | 17.52 | 11.29 | 0.261424E+09 | 347.89 | 02-MAY-13:09 | 17.52 | 11.29 |
June | 0.488139E+10 | 11823.50 | 25-JUN-08:22 | 16.15 | 11.58 | 0.273853E+09 | 348.54 | 23-JUN-09:00 | 16.15 | 11.58 |
July | 0.611203E+10 | 15957.88 | 02-JUL-08:51 | 22.20 | 15.44 | 0.256684E+09 | 348.45 | 03-JUL-09:00 | 23.30 | 14.49 |
August | 0.536409E+10 | 14722.64 | 06-AUG-08:52 | 27.20 | 14.17 | 0.286148E+09 | 348.60 | 11-AUG-09:00 | 27.80 | 12.62 |
September | 0.275090E+10 | 11734.64 | 04-SEP-08:22 | 26.15 | 14.59 | 0.245413E+09 | 347.88 | 14-SEP-13:00 | 21.70 | 13.42 |
October | 0.112799E+10 | 4642.45 | 18-OCT-09:40 | 19.07 | 8.41 | 0.241642E+09 | 347.88 | 16-OCT-09:20 | 19.07 | 8.41 |
November | 0.382864E+09 | 1692.23 | 03-NOV-09:50 | 8.30 | 5.09 | 0.208834E+09 | 347.87 | 03-NOV-09:30 | 8.30 | 5.09 |
December | 90119989.27 | 589.04 | 06-DEC-10:50 | 9.53 | 5.40 | 0.187582E+09 | 287.24 | 06-DEC-10:00 | 10.00 | 5.61 |
Annual Sum or Average | 0.256961E+11 | 0.280893E+10 | ||||||||
Minimum of Months | 37451991.10 | 540.73 | -2.8 | -5.5 | 0.185243E+09 | 272.89 | -2.6 | -5.4 | ||
Maximum of Months | 0.611203E+10 | 15957.88 | 27.20 | 15.44 | 0.286148E+09 | 348.60 | 27.80 | 14.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.545727E+09 | 4997.75 | 19-JAN-13:40 | -6.0 | -7.8 | 0.327390E+09 | 549.49 | 31-JAN-14:00 | -1.1 | -4.4 |
February | 0.148791E+10 | 11511.91 | 26-FEB-14:32 | 16.33 | 6.24 | 0.319739E+09 | 549.50 | 28-FEB-14:09 | 10.10 | 4.57 |
March | 0.234745E+10 | 11080.27 | 01-MAR-14:00 | 6.70 | 2.77 | 0.386492E+09 | 549.50 | 01-MAR-14:09 | 6.97 | 2.89 |
April | 0.277336E+10 | 10931.02 | 25-APR-13:30 | 16.40 | 7.12 | 0.357025E+09 | 549.50 | 13-APR-13:50 | 16.40 | 7.12 |
May | 0.366205E+10 | 10580.54 | 19-MAY-13:30 | 26.65 | 14.96 | 0.401942E+09 | 549.53 | 02-MAY-13:09 | 26.65 | 14.96 |
June | 0.586257E+10 | 14979.54 | 25-JUN-13:43 | 24.13 | 13.53 | 0.427573E+09 | 549.50 | 01-JUN-09:20 | 24.13 | 13.53 |
July | 0.759640E+10 | 18722.18 | 02-JUL-12:52 | 26.10 | 14.07 | 0.403551E+09 | 549.99 | 14-JUL-13:00 | 32.80 | 16.83 |
August | 0.817987E+10 | 19068.43 | 06-AUG-13:32 | 34.23 | 15.17 | 0.449267E+09 | 550.05 | 31-AUG-13:39 | 25.37 | 13.99 |
September | 0.605365E+10 | 19884.56 | 03-SEP-13:02 | 33.40 | 15.99 | 0.385280E+09 | 550.14 | 05-SEP-13:00 | 24.40 | 15.14 |
October | 0.397318E+10 | 19898.48 | 15-OCT-14:32 | 22.97 | 11.08 | 0.387465E+09 | 549.71 | 18-OCT-13:00 | 25.00 | 11.40 |
November | 0.193068E+10 | 11338.48 | 03-NOV-13:30 | 14.35 | 7.74 | 0.358033E+09 | 549.52 | 03-NOV-13:50 | 14.78 | 7.82 |
December | 0.824470E+09 | 5339.42 | 07-DEC-13:50 | 8.48 | 2.88 | 0.325299E+09 | 549.49 | 12-DEC-14:00 | -2.8 | -5.6 |
Annual Sum or Average | 0.452373E+11 | 0.452906E+10 | ||||||||
Minimum of Months | 0.545727E+09 | 4997.75 | -6.0 | -7.8 | 0.319739E+09 | 549.49 | -2.8 | -5.6 | ||
Maximum of Months | 0.817987E+10 | 19898.48 | 34.23 | 15.99 | 0.449267E+09 | 550.14 | 32.80 | 16.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 63754243.70 | 726.32 | 13-JAN-15:50 | 9.08 | 4.76 | 0.194544E+09 | 327.67 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.292716E+09 | 4176.41 | 28-FEB-16:40 | 10.37 | 4.49 | 0.184168E+09 | 347.84 | 27-FEB-14:20 | 10.37 | 4.49 |
March | 0.696086E+09 | 5307.24 | 28-MAR-16:00 | 10.60 | 3.09 | 0.228468E+09 | 347.82 | 02-MAR-14:00 | 10.60 | 3.09 |
April | 0.148074E+10 | 15729.84 | 16-APR-16:52 | 20.00 | 8.97 | 0.218934E+09 | 347.85 | 26-APR-13:20 | 11.10 | 4.81 |
May | 0.267472E+10 | 15872.38 | 28-MAY-17:12 | 20.73 | 10.39 | 0.250902E+09 | 347.87 | 02-MAY-13:09 | 20.73 | 10.39 |
June | 0.444241E+10 | 16058.79 | 18-JUN-17:32 | 25.20 | 14.48 | 0.270718E+09 | 347.86 | 01-JUN-09:20 | 25.20 | 14.48 |
July | 0.543512E+10 | 17873.34 | 02-JUL-16:51 | 25.60 | 14.12 | 0.255581E+09 | 347.86 | 21-JUL-13:20 | 25.97 | 12.49 |
August | 0.477953E+10 | 16509.88 | 06-AUG-16:11 | 35.40 | 16.13 | 0.283791E+09 | 347.86 | 07-AUG-09:20 | 28.73 | 14.88 |
September | 0.276344E+10 | 16626.62 | 04-SEP-16:21 | 32.80 | 16.63 | 0.238771E+09 | 347.86 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.124051E+10 | 10102.09 | 15-OCT-16:33 | 21.47 | 10.56 | 0.229898E+09 | 347.85 | 19-OCT-13:20 | 21.10 | 10.10 |
November | 0.440660E+09 | 3267.30 | 03-NOV-15:40 | 14.40 | 7.69 | 0.208611E+09 | 347.83 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.114128E+09 | 1119.75 | 06-DEC-15:30 | 10.25 | 4.94 | 0.190235E+09 | 338.68 | 06-DEC-16:19 | 8.50 | 3.80 |
Annual Sum or Average | 0.244238E+11 | 0.275462E+10 | ||||||||
Minimum of Months | 63754243.70 | 726.32 | 9.08 | 3.09 | 0.184168E+09 | 327.67 | 8.50 | 3.09 | ||
Maximum of Months | 0.543512E+10 | 17873.34 | 35.40 | 16.63 | 0.283791E+09 | 347.87 | 28.73 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11490939.57 | 725.73 | 21-JAN-17:03 | -0.6 | -3.8 | 0.302382E+09 | 406.72 | 05-JAN-14:50 | -0.6 | -3.8 |
February | 0.150557E+09 | 964.25 | 27-FEB-16:20 | 16.67 | 6.71 | 0.279611E+09 | 458.01 | 27-FEB-14:00 | 16.67 | 6.71 |
March | 0.465635E+09 | 1005.70 | 29-MAR-16:00 | 12.20 | 4.07 | 0.341585E+09 | 473.19 | 02-MAR-14:00 | 12.20 | 4.07 |
April | 0.926400E+09 | 1199.38 | 07-APR-14:40 | 22.23 | 9.16 | 0.325596E+09 | 543.42 | 07-APR-13:00 | 22.23 | 9.16 |
May | 0.156879E+10 | 3192.31 | 19-MAY-16:00 | 27.80 | 14.54 | 0.385873E+09 | 549.49 | 19-MAY-13:20 | 27.80 | 14.54 |
June | 0.313909E+10 | 4526.21 | 29-JUN-15:20 | 31.83 | 14.57 | 0.429949E+09 | 549.50 | 01-JUN-09:20 | 31.83 | 14.57 |
July | 0.419269E+10 | 8693.68 | 16-JUL-18:21 | 32.50 | 17.04 | 0.404062E+09 | 549.50 | 03-JUL-13:20 | 32.50 | 17.04 |
August | 0.370671E+10 | 6787.42 | 07-AUG-06:03 | 19.45 | 10.91 | 0.451378E+09 | 549.50 | 07-AUG-09:20 | 28.73 | 14.88 |
September | 0.242166E+10 | 8771.80 | 04-SEP-16:11 | 32.80 | 16.58 | 0.386719E+09 | 549.50 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.143327E+10 | 2388.94 | 19-OCT-14:30 | 21.40 | 10.24 | 0.374908E+09 | 549.49 | 19-OCT-13:20 | 21.40 | 10.24 |
November | 0.713534E+09 | 1109.04 | 08-NOV-14:10 | 13.78 | 7.92 | 0.325966E+09 | 513.82 | 08-NOV-14:20 | 13.67 | 7.87 |
December | 0.122677E+09 | 852.31 | 06-DEC-16:00 | 9.40 | 4.51 | 0.295769E+09 | 429.40 | 06-DEC-14:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.188525E+11 | 0.430380E+10 | ||||||||
Minimum of Months | 11490939.57 | 725.73 | -0.6 | -3.8 | 0.279611E+09 | 406.72 | -0.6 | -3.8 | ||
Maximum of Months | 0.419269E+10 | 8771.80 | 32.80 | 17.04 | 0.451378E+09 | 549.50 | 32.50 | 17.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44079839.43 | 556.61 | 20-JAN-10:10 | -3.1 | -5.8 | 0.193882E+09 | 278.62 | 20-JAN-10:20 | -2.9 | -5.7 |
February | 0.270362E+09 | 1377.15 | 28-FEB-09:25 | -0.3 | -1.4 | 0.186574E+09 | 347.88 | 28-FEB-10:39 | 2.97 | 0.62 |
March | 0.608027E+09 | 2209.76 | 23-MAR-10:30 | 8.60 | 1.66 | 0.238594E+09 | 347.88 | 01-MAR-10:39 | 8.60 | 1.66 |
April | 0.116472E+10 | 4030.44 | 25-APR-09:30 | 10.80 | 5.26 | 0.229995E+09 | 347.88 | 25-APR-09:20 | 10.80 | 5.26 |
May | 0.191740E+10 | 5192.92 | 19-MAY-09:20 | 18.53 | 11.74 | 0.262558E+09 | 347.89 | 02-MAY-13:09 | 18.53 | 11.74 |
June | 0.409902E+10 | 8800.26 | 30-JUN-06:02 | 12.67 | 9.41 | 0.274881E+09 | 348.29 | 23-JUN-09:00 | 12.67 | 9.41 |
July | 0.545354E+10 | 12462.32 | 16-JUL-09:41 | 23.12 | 16.45 | 0.257197E+09 | 348.13 | 13-JUL-09:39 | 23.12 | 16.45 |
August | 0.497965E+10 | 11556.42 | 06-AUG-09:32 | 29.07 | 14.77 | 0.287814E+09 | 348.26 | 11-AUG-09:00 | 27.80 | 12.62 |
September | 0.283201E+10 | 11974.07 | 04-SEP-08:51 | 26.70 | 14.88 | 0.252404E+09 | 347.88 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.146302E+10 | 3981.52 | 18-OCT-09:40 | 19.07 | 8.41 | 0.253849E+09 | 347.88 | 16-OCT-09:20 | 19.07 | 8.41 |
November | 0.608531E+09 | 1965.65 | 03-NOV-09:15 | 7.10 | 4.34 | 0.221897E+09 | 347.87 | 06-NOV-10:20 | 2.80 | 0.07 |
December | 0.176592E+09 | 625.76 | 07-DEC-10:50 | 5.55 | 2.29 | 0.190266E+09 | 300.15 | 07-DEC-10:00 | 6.10 | 2.52 |
Annual Sum or Average | 0.236170E+11 | 0.284991E+10 | ||||||||
Minimum of Months | 44079839.43 | 556.61 | -3.1 | -5.8 | 0.186574E+09 | 278.62 | -2.9 | -5.7 | ||
Maximum of Months | 0.545354E+10 | 12462.32 | 29.07 | 16.45 | 0.287814E+09 | 348.29 | 27.80 | 16.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.221589E+09 | 2304.68 | 14-JAN-12:30 | 10.30 | 4.97 | 0.292177E+09 | 510.19 | 02-JAN-14:09 | 10.30 | 4.97 |
February | 0.819613E+09 | 8650.98 | 27-FEB-13:25 | 17.75 | 6.76 | 0.291288E+09 | 549.50 | 28-FEB-14:09 | 10.10 | 4.57 |
March | 0.104280E+10 | 7607.11 | 01-MAR-13:20 | 5.97 | 2.26 | 0.361705E+09 | 549.51 | 13-MAR-13:09 | 8.80 | 2.43 |
April | 0.128987E+10 | 6608.13 | 25-APR-12:07 | 15.28 | 6.55 | 0.338280E+09 | 549.51 | 13-APR-13:09 | 15.28 | 6.55 |
May | 0.199056E+10 | 7499.86 | 19-MAY-14:00 | 27.20 | 15.02 | 0.380655E+09 | 549.51 | 02-MAY-13:09 | 27.20 | 15.02 |
June | 0.413614E+10 | 10861.26 | 29-JUN-12:00 | 30.60 | 14.31 | 0.418511E+09 | 549.52 | 19-JUN-13:39 | 30.60 | 14.31 |
July | 0.658307E+10 | 14980.45 | 16-JUL-16:21 | 33.05 | 17.81 | 0.401979E+09 | 604.44 | 17-JUL-12:09 | 35.18 | 16.48 |
August | 0.718835E+10 | 14866.57 | 06-AUG-13:32 | 34.23 | 15.17 | 0.447398E+09 | 602.68 | 07-AUG-12:09 | 32.80 | 15.88 |
September | 0.530206E+10 | 16214.50 | 04-SEP-14:51 | 32.20 | 16.66 | 0.385859E+09 | 557.61 | 07-SEP-15:09 | 24.78 | 20.11 |
October | 0.346929E+10 | 14564.41 | 15-OCT-16:12 | 21.83 | 10.69 | 0.388234E+09 | 551.08 | 18-OCT-13:00 | 25.00 | 11.40 |
November | 0.150413E+10 | 9628.49 | 03-NOV-12:07 | 12.62 | 7.22 | 0.352001E+09 | 549.50 | 13-NOV-14:09 | 4.88 | -1.5 |
December | 0.442652E+09 | 3125.45 | 02-DEC-13:30 | 9.40 | 4.37 | 0.304724E+09 | 549.50 | 21-DEC-14:09 | 1.60 | -3.1 |
Annual Sum or Average | 0.339901E+11 | 0.436281E+10 | ||||||||
Minimum of Months | 0.221589E+09 | 2304.68 | 5.97 | 2.26 | 0.291288E+09 | 510.19 | 1.60 | -3.1 | ||
Maximum of Months | 0.718835E+10 | 16214.50 | 34.23 | 17.81 | 0.447398E+09 | 604.44 | 35.18 | 20.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50788281.35 | 675.16 | 13-JAN-16:10 | 8.72 | 4.55 | 0.194374E+09 | 307.22 | 13-JAN-16:10 | 8.72 | 4.55 |
February | 0.274083E+09 | 3160.58 | 28-FEB-16:50 | 10.18 | 4.40 | 0.183783E+09 | 347.83 | 27-FEB-14:00 | 10.18 | 4.40 |
March | 0.581908E+09 | 3329.27 | 28-MAR-17:30 | 9.75 | 2.59 | 0.227333E+09 | 347.83 | 02-MAR-14:00 | 9.75 | 2.59 |
April | 0.105306E+10 | 5677.22 | 16-APR-17:22 | 19.70 | 8.86 | 0.219409E+09 | 347.85 | 26-APR-13:20 | 11.10 | 4.81 |
May | 0.195571E+10 | 8545.62 | 28-MAY-18:12 | 19.63 | 10.28 | 0.255382E+09 | 347.85 | 04-MAY-13:20 | 19.63 | 10.28 |
June | 0.356062E+10 | 10767.91 | 24-JUN-17:42 | 26.38 | 11.78 | 0.273658E+09 | 347.86 | 29-JUN-09:20 | 25.17 | 12.64 |
July | 0.469538E+10 | 14322.34 | 16-JUL-18:21 | 32.50 | 17.04 | 0.256718E+09 | 347.86 | 13-JUL-09:00 | 32.50 | 17.04 |
August | 0.429307E+10 | 12635.37 | 06-AUG-16:11 | 35.40 | 16.13 | 0.286921E+09 | 347.86 | 07-AUG-09:20 | 28.73 | 14.88 |
September | 0.271344E+10 | 14076.57 | 04-SEP-16:51 | 32.80 | 16.77 | 0.249423E+09 | 347.86 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.144863E+10 | 8486.75 | 15-OCT-16:12 | 21.83 | 10.69 | 0.246979E+09 | 347.85 | 16-OCT-09:20 | 17.60 | 9.11 |
November | 0.650587E+09 | 2964.95 | 03-NOV-15:50 | 14.35 | 7.69 | 0.218567E+09 | 347.84 | 03-NOV-13:50 | 14.35 | 7.69 |
December | 0.168926E+09 | 822.66 | 06-DEC-15:40 | 9.97 | 4.80 | 0.192016E+09 | 338.67 | 06-DEC-15:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.214462E+11 | 0.280456E+10 | ||||||||
Minimum of Months | 50788281.35 | 675.16 | 8.72 | 2.59 | 0.183783E+09 | 307.22 | 8.72 | 2.59 | ||
Maximum of Months | 0.469538E+10 | 14322.34 | 35.40 | 17.04 | 0.286921E+09 | 347.86 | 32.50 | 17.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 23183529.24 | 796.55 | 13-JAN-16:50 | 7.98 | 4.06 | 0.304226E+09 | 407.16 | 13-JAN-14:00 | 7.98 | 4.06 |
February | 0.284130E+09 | 1208.81 | 27-FEB-13:30 | 17.75 | 6.76 | 0.283488E+09 | 511.34 | 27-FEB-16:19 | 16.67 | 6.71 |
March | 0.827178E+09 | 1188.80 | 01-MAR-14:10 | 6.97 | 2.89 | 0.359238E+09 | 533.63 | 02-MAR-14:00 | 11.10 | 4.79 |
April | 0.139901E+10 | 3335.61 | 07-APR-14:30 | 22.50 | 9.29 | 0.355944E+09 | 549.49 | 13-APR-13:20 | 12.97 | 7.01 |
May | 0.226815E+10 | 4771.05 | 19-MAY-16:00 | 27.80 | 14.54 | 0.404306E+09 | 549.50 | 04-MAY-13:20 | 27.80 | 14.54 |
June | 0.432915E+10 | 7878.89 | 30-JUN-06:02 | 12.67 | 9.41 | 0.432843E+09 | 549.51 | 29-JUN-09:20 | 12.67 | 9.41 |
July | 0.517300E+10 | 10764.96 | 16-JUL-18:22 | 32.50 | 17.04 | 0.404935E+09 | 550.61 | 18-JUL-13:20 | 33.17 | 17.33 |
August | 0.453980E+10 | 9801.83 | 06-AUG-14:41 | 34.40 | 15.36 | 0.452363E+09 | 550.51 | 07-AUG-09:00 | 30.60 | 15.43 |
September | 0.268382E+10 | 9957.88 | 04-SEP-16:11 | 32.80 | 16.58 | 0.387277E+09 | 549.51 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.146521E+10 | 2972.03 | 19-OCT-14:30 | 21.40 | 10.24 | 0.373750E+09 | 549.49 | 19-OCT-13:20 | 21.40 | 10.24 |
November | 0.694998E+09 | 1261.03 | 03-NOV-13:25 | 14.35 | 7.74 | 0.326219E+09 | 525.08 | 08-NOV-14:20 | 13.67 | 7.87 |
December | 0.145200E+09 | 886.35 | 06-DEC-16:00 | 9.40 | 4.51 | 0.295978E+09 | 438.37 | 06-DEC-14:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.238328E+11 | 0.438057E+10 | ||||||||
Minimum of Months | 23183529.24 | 796.55 | 6.97 | 2.89 | 0.283488E+09 | 407.16 | 7.98 | 4.06 | ||
Maximum of Months | 0.517300E+10 | 10764.96 | 34.40 | 17.04 | 0.452363E+09 | 550.61 | 33.17 | 17.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 62302409.34 | 622.29 | 14-JAN-11:10 | 8.58 | 4.13 | 0.142502E+09 | 290.80 | 20-JAN-11:09 | -1.9 | -4.9 |
February | 0.282826E+09 | 4775.36 | 28-FEB-13:01 | 9.08 | 4.04 | 0.139684E+09 | 356.46 | 24-FEB-11:09 | 9.08 | 4.04 |
March | 0.746528E+09 | 5905.40 | 23-MAR-12:01 | 8.98 | 1.57 | 0.181143E+09 | 356.46 | 22-MAR-10:09 | 8.98 | 1.57 |
April | 0.164750E+10 | 7243.51 | 25-APR-10:05 | 12.57 | 5.85 | 0.174637E+09 | 356.46 | 13-APR-14:09 | 12.57 | 5.85 |
May | 0.252829E+10 | 8026.43 | 19-MAY-10:05 | 20.37 | 12.65 | 0.196401E+09 | 356.48 | 02-MAY-12:09 | 20.37 | 12.65 |
June | 0.473660E+10 | 14001.24 | 11-JUN-09:22 | 20.30 | 11.53 | 0.203899E+09 | 356.47 | 20-JUN-10:09 | 21.57 | 13.11 |
July | 0.582312E+10 | 15828.33 | 16-JUL-09:01 | 22.38 | 16.15 | 0.191271E+09 | 356.48 | 13-JUL-10:09 | 22.38 | 16.15 |
August | 0.521534E+10 | 16289.26 | 06-AUG-08:41 | 26.55 | 14.17 | 0.212942E+09 | 358.57 | 07-AUG-10:09 | 30.60 | 15.34 |
September | 0.283853E+10 | 14823.86 | 04-SEP-08:51 | 26.70 | 14.88 | 0.185445E+09 | 356.46 | 14-SEP-14:09 | 21.70 | 13.36 |
October | 0.131105E+10 | 6094.69 | 18-OCT-10:05 | 20.28 | 8.90 | 0.184218E+09 | 356.45 | 18-OCT-14:09 | 25.00 | 11.44 |
November | 0.472946E+09 | 4983.22 | 02-NOV-12:01 | 6.88 | 2.55 | 0.161383E+09 | 356.45 | 10-NOV-11:09 | 2.98 | -0.7 |
December | 0.129658E+09 | 672.32 | 07-DEC-11:10 | 6.38 | 2.62 | 0.140061E+09 | 312.70 | 07-DEC-11:09 | 6.38 | 2.62 |
Annual Sum or Average | 0.257947E+11 | 0.211359E+10 | ||||||||
Minimum of Months | 62302409.34 | 622.29 | 6.38 | 1.57 | 0.139684E+09 | 290.80 | -1.9 | -4.9 | ||
Maximum of Months | 0.582312E+10 | 16289.26 | 26.70 | 16.15 | 0.212942E+09 | 358.57 | 30.60 | 16.15 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.733745E+09 | 5956.13 | 19-JAN-13:30 | -6.2 | -7.9 | 0.332653E+09 | 549.50 | 06-JAN-14:20 | -6.2 | -7.9 |
February | 0.182833E+10 | 13524.13 | 26-FEB-13:53 | 15.60 | 5.76 | 0.328519E+09 | 549.65 | 28-FEB-14:00 | 10.60 | 4.78 |
March | 0.278489E+10 | 11851.95 | 01-MAR-13:35 | 6.33 | 2.52 | 0.399449E+09 | 549.76 | 23-MAR-13:50 | 9.90 | 2.40 |
April | 0.313098E+10 | 10632.84 | 25-APR-13:20 | 16.50 | 7.26 | 0.370543E+09 | 550.25 | 25-APR-13:20 | 16.50 | 7.26 |
May | 0.384821E+10 | 10042.98 | 19-MAY-13:30 | 26.65 | 14.96 | 0.412344E+09 | 549.53 | 02-MAY-13:09 | 26.65 | 14.96 |
June | 0.584097E+10 | 10578.48 | 25-JUN-11:23 | 21.15 | 13.24 | 0.432402E+09 | 549.53 | 19-JUN-13:39 | 21.15 | 13.24 |
July | 0.739031E+10 | 17256.91 | 16-JUL-13:01 | 29.78 | 18.22 | 0.405170E+09 | 550.92 | 19-JUL-13:20 | 30.53 | 17.76 |
August | 0.816186E+10 | 17899.76 | 06-AUG-14:41 | 34.40 | 15.36 | 0.453229E+09 | 550.93 | 07-AUG-09:00 | 30.60 | 15.43 |
September | 0.637972E+10 | 18716.33 | 04-SEP-14:51 | 32.20 | 16.66 | 0.394950E+09 | 563.55 | 07-SEP-15:09 | 24.78 | 20.11 |
October | 0.468328E+10 | 17450.64 | 15-OCT-15:22 | 22.50 | 10.93 | 0.400200E+09 | 558.41 | 18-OCT-13:20 | 24.60 | 11.01 |
November | 0.252226E+10 | 11982.67 | 03-NOV-13:05 | 13.92 | 7.65 | 0.370766E+09 | 549.67 | 06-NOV-14:09 | 8.22 | 3.23 |
December | 0.111808E+10 | 6360.17 | 12-DEC-12:30 | -2.8 | -5.7 | 0.334524E+09 | 549.49 | 19-DEC-14:39 | 12.07 | 7.31 |
Annual Sum or Average | 0.484226E+11 | 0.463475E+10 | ||||||||
Minimum of Months | 0.733745E+09 | 5956.13 | -6.2 | -7.9 | 0.328519E+09 | 549.49 | -6.2 | -7.9 | ||
Maximum of Months | 0.816186E+10 | 18716.33 | 34.40 | 18.22 | 0.453229E+09 | 563.55 | 30.60 | 20.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 83430398.05 | 759.03 | 13-JAN-15:50 | 9.08 | 4.76 | 0.195614E+09 | 336.91 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.390094E+09 | 4435.06 | 28-FEB-16:40 | 10.37 | 4.49 | 0.187413E+09 | 347.84 | 24-FEB-14:00 | 10.37 | 4.49 |
March | 0.897132E+09 | 5356.54 | 28-MAR-16:00 | 10.60 | 3.09 | 0.235566E+09 | 347.83 | 01-MAR-14:20 | 10.60 | 3.09 |
April | 0.165811E+10 | 9965.67 | 22-APR-17:06 | 16.10 | 8.62 | 0.228886E+09 | 347.85 | 07-APR-09:20 | 16.10 | 8.62 |
May | 0.277189E+10 | 14753.51 | 28-MAY-17:12 | 20.73 | 10.39 | 0.258283E+09 | 347.86 | 02-MAY-13:09 | 20.73 | 10.39 |
June | 0.440910E+10 | 14722.86 | 24-JUN-17:42 | 26.38 | 11.78 | 0.273838E+09 | 347.86 | 29-JUN-09:20 | 25.17 | 12.64 |
July | 0.529060E+10 | 17216.96 | 16-JUL-17:01 | 33.22 | 17.33 | 0.256561E+09 | 347.86 | 13-JUL-09:00 | 33.22 | 17.33 |
August | 0.477318E+10 | 15557.49 | 06-AUG-16:42 | 35.10 | 15.80 | 0.286582E+09 | 348.50 | 07-AUG-09:00 | 30.60 | 15.43 |
September | 0.292964E+10 | 16848.02 | 04-SEP-16:11 | 32.80 | 16.58 | 0.246603E+09 | 347.86 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.152073E+10 | 10690.16 | 15-OCT-15:22 | 22.50 | 10.93 | 0.241829E+09 | 347.85 | 19-OCT-09:20 | 17.43 | 8.38 |
November | 0.654314E+09 | 3624.59 | 03-NOV-15:40 | 14.40 | 7.69 | 0.216823E+09 | 347.83 | 03-NOV-13:50 | 14.40 | 7.69 |
December | 0.182790E+09 | 1415.47 | 06-DEC-15:40 | 9.97 | 4.80 | 0.193410E+09 | 345.88 | 06-DEC-14:00 | 9.97 | 4.80 |
Annual Sum or Average | 0.255610E+11 | 0.282141E+10 | ||||||||
Minimum of Months | 83430398.05 | 759.03 | 9.08 | 3.09 | 0.187413E+09 | 336.91 | 8.90 | 3.09 | ||
Maximum of Months | 0.529060E+10 | 17216.96 | 35.10 | 17.33 | 0.286582E+09 | 348.50 | 33.22 | 17.33 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57722303.38 | 14406.91 | 02-JAN-07:12 | -2.2 |
February | 6829152.08 | 11495.11 | 06-FEB-07:04 | 0.50 |
March | 709542.95 | 11408.55 | 06-MAR-07:01 | -19.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 1862479.66 | 10746.03 | 26-DEC-07:01 | -8.5 |
Annual Sum or Average | 67123478.09 | |||
Minimum of Months | 0.00 | 0.00 | -19.7 | |
Maximum of Months | 57722303.38 | 14406.91 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.879619E+10 | 19569.55 | 11-JAN-06:12 | -31.5 |
February | 0.438750E+10 | 16911.59 | 04-FEB-06:13 | -19.6 |
March | 0.305981E+10 | 17562.99 | 06-MAR-06:13 | -17.1 |
April | 0.125806E+10 | 9444.24 | 28-APR-06:01 | -5.2 |
May | 0.930256E+09 | 10121.53 | 08-MAY-06:01 | -2.7 |
June | 0.357195E+09 | 3427.14 | 25-JUN-08:22 | 16.15 |
July | 0.204376E+09 | 4891.75 | 09-JUL-07:52 | 16.10 |
August | 0.331298E+09 | 4103.74 | 06-AUG-07:32 | 22.57 |
September | 0.659707E+09 | 3734.44 | 20-SEP-06:03 | 3.48 |
October | 0.129194E+10 | 11299.09 | 10-OCT-06:01 | -6.1 |
November | 0.311970E+10 | 17098.94 | 27-NOV-06:13 | -14.4 |
December | 0.640467E+10 | 18766.80 | 29-DEC-06:12 | -25.2 |
Annual Sum or Average | 0.308007E+11 | |||
Minimum of Months | 0.204376E+09 | 3427.14 | -31.5 | |
Maximum of Months | 0.879619E+10 | 19569.55 | 22.57 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.358199E+10 | 11123.07 | 09-JAN-07:04 | -27.2 |
February | 0.210223E+10 | 8833.29 | 06-FEB-07:12 | 0.40 |
March | 0.168585E+10 | 8848.45 | 06-MAR-07:02 | -19.7 |
April | 0.706237E+09 | 4645.10 | 16-APR-13:03 | 18.48 |
May | 0.617146E+09 | 3410.78 | 14-MAY-15:32 | 16.30 |
June | 44231138.17 | 3882.95 | 18-JUN-15:52 | 25.00 |
July | 43149231.78 | 4563.22 | 09-JUL-15:22 | 28.30 |
August | 33481192.33 | 4948.95 | 06-AUG-15:21 | 35.00 |
September | 0.250913E+09 | 5297.71 | 17-SEP-12:23 | 10.85 |
October | 0.752249E+09 | 7742.38 | 15-OCT-15:22 | 22.50 |
November | 0.166076E+10 | 8719.84 | 27-NOV-07:11 | -13.4 |
December | 0.254301E+10 | 9423.39 | 26-DEC-07:11 | -8.7 |
Annual Sum or Average | 0.140212E+11 | |||
Minimum of Months | 33481192.33 | 3410.78 | -27.2 | |
Maximum of Months | 0.358199E+10 | 11123.07 | 35.00 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.277943E+10 | 7495.74 | 09-JAN-07:01 | -27.2 |
February | 0.163637E+10 | 5887.65 | 06-FEB-07:03 | 0.50 |
March | 0.119603E+10 | 5068.84 | 06-MAR-07:01 | -19.7 |
April | 0.352348E+09 | 2911.58 | 04-APR-07:04 | 0.47 |
May | 0.335577E+09 | 8336.71 | 22-MAY-05:01 | -0.6 |
June | 21129742.44 | 2089.57 | 27-JUN-05:13 | 12.07 |
July | 29563000.65 | 2844.66 | 16-JUL-15:41 | 32.88 |
August | 22751432.80 | 2788.29 | 06-AUG-15:32 | 35.20 |
September | 69098218.61 | 3214.32 | 17-SEP-13:43 | 12.02 |
October | 0.281510E+09 | 4563.39 | 15-OCT-16:12 | 21.83 |
November | 0.110430E+10 | 4622.68 | 14-NOV-08:06 | -2.8 |
December | 0.203594E+10 | 5864.39 | 26-DEC-07:01 | -8.5 |
Annual Sum or Average | 0.986405E+10 | |||
Minimum of Months | 21129742.44 | 2089.57 | -27.2 | |
Maximum of Months | 0.277943E+10 | 8336.71 | 35.20 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138011E+10 | 25694.52 | 09-JAN-05:01 | -27.2 |
February | 0.337609E+09 | 24803.33 | 06-FEB-05:11 | -0.2 |
March | 0.143820E+09 | 23820.20 | 06-MAR-06:01 | -16.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 4375716.74 | 20741.44 | 08-MAY-06:01 | -2.7 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 1665760.14 | 20769.94 | 10-OCT-06:01 | -6.1 |
November | 0.134299E+09 | 23458.09 | 27-NOV-06:01 | -14.5 |
December | 0.506500E+09 | 24664.85 | 26-DEC-05:11 | -7.4 |
Annual Sum or Average | 0.250838E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.138011E+10 | 25694.52 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.569867E+10 | 32070.63 | 30-JAN-05:11 | -16.8 |
February | 0.215509E+10 | 31462.69 | 06-FEB-05:11 | -0.2 |
March | 0.100171E+10 | 31751.87 | 06-MAR-05:11 | -17.8 |
April | 47802220.27 | 25306.39 | 28-APR-06:01 | -5.2 |
May | 0.152362E+09 | 28094.80 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 171112.29 | 1140.75 | 19-SEP-06:03 | 2.20 |
October | 98333164.60 | 28344.03 | 10-OCT-05:01 | -6.1 |
November | 0.109908E+10 | 31448.41 | 27-NOV-05:11 | -15.3 |
December | 0.330098E+10 | 31265.68 | 26-DEC-05:01 | -7.3 |
Annual Sum or Average | 0.135542E+11 | |||
Minimum of Months | 0.00 | 0.00 | -17.8 | |
Maximum of Months | 0.569867E+10 | 32070.63 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.841094E+10 | 11270.77 | 30-JAN-05:11 | -16.8 |
February | 0.408400E+10 | 10711.27 | 05-FEB-05:52 | -20.0 |
March | 0.224065E+10 | 11056.51 | 06-MAR-05:11 | -17.8 |
April | 0.389401E+09 | 9379.64 | 29-APR-04:02 | -7.8 |
May | 0.289827E+09 | 9880.68 | 08-MAY-04:01 | -2.3 |
June | 453744.61 | 2726.17 | 17-JUN-06:03 | 6.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 436872.08 | 2184.36 | 18-AUG-06:03 | 8.17 |
September | 47977413.66 | 8548.02 | 19-SEP-05:12 | 2.20 |
October | 0.393339E+09 | 10086.96 | 10-OCT-04:01 | -5.2 |
November | 0.237897E+10 | 10924.38 | 27-NOV-04:32 | -15.7 |
December | 0.592607E+10 | 10944.32 | 31-DEC-18:22 | -22.2 |
Annual Sum or Average | 0.241621E+11 | |||
Minimum of Months | 0.00 | 0.00 | -22.2 | |
Maximum of Months | 0.841094E+10 | 11270.77 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.505441E+10 | 13093.84 | 30-JAN-05:11 | -16.8 |
February | 0.225102E+10 | 12313.05 | 05-FEB-05:52 | -20.0 |
March | 0.120026E+10 | 12847.23 | 06-MAR-05:11 | -17.8 |
April | 0.172666E+09 | 10623.11 | 15-APR-05:01 | -0.6 |
May | 0.149452E+09 | 11382.26 | 08-MAY-04:01 | -2.3 |
June | 91330.56 | 304.44 | 16-JUN-06:05 | 2.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 22295039.18 | 8818.22 | 19-SEP-05:12 | 2.20 |
October | 0.188372E+09 | 11713.55 | 10-OCT-04:01 | -5.2 |
November | 0.134718E+10 | 12582.98 | 27-NOV-04:32 | -15.7 |
December | 0.347819E+10 | 12585.35 | 31-DEC-03:42 | -24.9 |
Annual Sum or Average | 0.138639E+11 | |||
Minimum of Months | 0.00 | 0.00 | -24.9 | |
Maximum of Months | 0.505441E+10 | 13093.84 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.613013E+10 | 17421.31 | 30-JAN-05:11 | -16.8 |
February | 0.262217E+10 | 16565.70 | 05-FEB-05:52 | -20.0 |
March | 0.163314E+10 | 17208.16 | 06-MAR-05:11 | -17.8 |
April | 0.336661E+09 | 14142.83 | 15-APR-05:01 | -0.6 |
May | 0.307747E+09 | 15352.57 | 08-MAY-04:01 | -2.3 |
June | 2129775.41 | 7659.85 | 17-JUN-06:03 | 6.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 1032992.43 | 4384.21 | 18-AUG-06:03 | 8.17 |
September | 35357493.64 | 12354.06 | 19-SEP-05:12 | 2.20 |
October | 0.238200E+09 | 15638.56 | 10-OCT-04:01 | -5.2 |
November | 0.156711E+10 | 16884.21 | 27-NOV-04:32 | -15.7 |
December | 0.404103E+10 | 16888.76 | 31-DEC-05:42 | -25.8 |
Annual Sum or Average | 0.169147E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.8 | |
Maximum of Months | 0.613013E+10 | 17421.31 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.533690E+10 | 14789.72 | 30-JAN-05:11 | -16.8 |
February | 0.241287E+10 | 13840.52 | 05-FEB-05:52 | -20.0 |
March | 0.137873E+10 | 14536.39 | 06-MAR-05:11 | -17.8 |
April | 0.239369E+09 | 11838.87 | 01-APR-05:11 | 5.60 |
May | 0.195096E+09 | 12845.26 | 08-MAY-04:01 | -2.3 |
June | 1553087.22 | 4904.58 | 17-JUN-06:03 | 6.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 844493.67 | 3168.43 | 18-AUG-06:03 | 8.17 |
September | 29218528.16 | 9020.22 | 19-SEP-05:12 | 2.20 |
October | 0.232844E+09 | 13247.41 | 10-OCT-04:01 | -5.2 |
November | 0.142805E+10 | 14201.11 | 27-NOV-04:32 | -15.7 |
December | 0.366356E+10 | 14189.80 | 31-DEC-03:42 | -24.9 |
Annual Sum or Average | 0.149190E+11 | |||
Minimum of Months | 0.00 | 0.00 | -24.9 | |
Maximum of Months | 0.533690E+10 | 14789.72 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.536687E+10 | 8076.15 | 29-JAN-20:12 | -26.1 |
February | 0.261379E+10 | 7933.48 | 05-FEB-21:12 | -17.0 |
March | 0.126497E+10 | 7934.49 | 06-MAR-05:01 | -18.4 |
April | 0.158058E+09 | 6821.33 | 29-APR-05:01 | -7.7 |
May | 82630057.83 | 6929.05 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 464866.61 | 1741.59 | 20-SEP-06:03 | 3.48 |
October | 26288021.83 | 6580.97 | 10-OCT-05:01 | -6.1 |
November | 0.699639E+09 | 7781.38 | 27-NOV-05:01 | -15.4 |
December | 0.271771E+10 | 8031.63 | 31-DEC-18:22 | -22.2 |
Annual Sum or Average | 0.129304E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.1 | |
Maximum of Months | 0.536687E+10 | 8076.15 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.308149E+10 | 9939.17 | 09-JAN-02:41 | -27.2 |
February | 0.131295E+10 | 9603.22 | 06-FEB-05:11 | -0.2 |
March | 0.524017E+09 | 9785.16 | 06-MAR-05:01 | -18.4 |
April | 45749343.99 | 8332.47 | 29-APR-05:01 | -7.7 |
May | 30935864.20 | 8436.00 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 8909536.90 | 7746.52 | 10-OCT-06:01 | -6.1 |
November | 0.376913E+09 | 9542.80 | 27-NOV-05:01 | -15.4 |
December | 0.150895E+10 | 9815.28 | 31-DEC-18:22 | -22.2 |
Annual Sum or Average | 0.688991E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.308149E+10 | 9939.17 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.766260E+10 | 16844.95 | 09-JAN-08:00 | -27.2 |
February | 0.405492E+10 | 15537.10 | 01-FEB-07:10 | -24.9 |
March | 0.297791E+10 | 15005.30 | 06-MAR-08:00 | -18.3 |
April | 0.157166E+10 | 12427.07 | 28-APR-06:10 | -5.2 |
May | 0.134577E+10 | 11984.95 | 08-MAY-06:10 | -2.7 |
June | 0.235106E+09 | 10382.66 | 16-JUN-07:00 | 2.20 |
July | 18142434.18 | 7117.09 | 05-JUL-06:06 | 9.40 |
August | 0.133089E+09 | 9287.64 | 17-AUG-06:05 | 8.30 |
September | 0.451954E+09 | 10449.75 | 19-SEP-07:00 | 2.20 |
October | 0.798173E+09 | 12276.99 | 10-OCT-06:10 | -6.1 |
November | 0.218383E+10 | 13914.17 | 27-NOV-07:50 | -13.0 |
December | 0.471777E+10 | 16385.09 | 29-DEC-08:00 | -27.8 |
Annual Sum or Average | 0.261509E+11 | |||
Minimum of Months | 18142434.18 | 7117.09 | -27.8 | |
Maximum of Months | 0.766260E+10 | 16844.95 | 9.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.330616E+10 | 10769.17 | 09-JAN-02:41 | -27.2 |
February | 0.136699E+10 | 10434.31 | 06-FEB-05:11 | -0.2 |
March | 0.618365E+09 | 10626.37 | 06-MAR-05:01 | -18.4 |
April | 60831658.73 | 8882.42 | 29-APR-05:01 | -7.7 |
May | 36342249.19 | 9189.71 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 11617357.52 | 8595.06 | 10-OCT-05:01 | -6.1 |
November | 0.371487E+09 | 10369.04 | 27-NOV-05:01 | -15.4 |
December | 0.159415E+10 | 10632.31 | 31-DEC-18:22 | -22.2 |
Annual Sum or Average | 0.736594E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.330616E+10 | 10769.17 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.521347E+10 | 9215.34 | 08-JAN-17:32 | -27.0 |
February | 0.220257E+10 | 8963.08 | 05-FEB-23:12 | -9.1 |
March | 0.876211E+09 | 8980.12 | 06-MAR-05:01 | -18.4 |
April | 57047458.63 | 7599.53 | 29-APR-05:01 | -7.7 |
May | 66027874.69 | 7980.99 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 1969237.58 | 5209.22 | 19-SEP-06:03 | 2.20 |
October | 69029217.75 | 7910.16 | 10-OCT-05:01 | -6.1 |
November | 0.946185E+09 | 8925.80 | 27-NOV-05:01 | -15.4 |
December | 0.299942E+10 | 9206.94 | 31-DEC-17:02 | -21.8 |
Annual Sum or Average | 0.124319E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.0 | |
Maximum of Months | 0.521347E+10 | 9215.34 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304742E+10 | 11778.51 | 30-JAN-05:01 | -17.0 |
February | 0.118113E+10 | 11382.41 | 06-FEB-05:11 | -0.2 |
March | 0.462622E+09 | 11519.76 | 06-MAR-05:01 | -18.4 |
April | 23384029.19 | 9670.83 | 29-APR-05:01 | -7.7 |
May | 36645161.04 | 10181.22 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 1125350.42 | 3347.84 | 19-SEP-06:03 | 2.20 |
October | 32107800.40 | 10075.18 | 10-OCT-05:01 | -6.1 |
November | 0.562033E+09 | 11425.70 | 27-NOV-05:01 | -15.4 |
December | 0.173580E+10 | 11712.20 | 31-DEC-18:22 | -22.2 |
Annual Sum or Average | 0.708227E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.2 | |
Maximum of Months | 0.304742E+10 | 11778.51 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.347212E+10 | 14930.11 | 09-JAN-02:51 | -27.2 |
February | 0.121954E+10 | 14401.06 | 06-FEB-05:11 | -0.2 |
March | 0.563225E+09 | 14688.41 | 06-MAR-05:01 | -18.4 |
April | 50185544.61 | 12387.72 | 29-APR-05:01 | -7.7 |
May | 74816453.87 | 13038.63 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 1167261.89 | 3960.42 | 19-SEP-06:03 | 2.20 |
October | 40394547.29 | 12893.19 | 10-OCT-05:01 | -6.1 |
November | 0.603390E+09 | 14599.76 | 27-NOV-05:01 | -15.4 |
December | 0.185638E+10 | 14850.51 | 31-DEC-03:42 | -24.9 |
Annual Sum or Average | 0.788122E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.347212E+10 | 14930.11 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.325172E+10 | 11894.69 | 30-JAN-05:01 | -17.0 |
February | 0.125546E+10 | 11488.86 | 06-FEB-05:11 | -0.2 |
March | 0.539865E+09 | 11638.48 | 06-MAR-05:01 | -18.4 |
April | 38398051.23 | 9540.44 | 29-APR-05:01 | -7.7 |
May | 46451558.51 | 10222.12 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 1312186.69 | 3565.88 | 19-SEP-06:03 | 2.20 |
October | 41904982.07 | 10114.37 | 10-OCT-05:01 | -6.1 |
November | 0.573926E+09 | 11538.71 | 27-NOV-05:01 | -15.4 |
December | 0.184391E+10 | 11817.63 | 31-DEC-17:02 | -21.8 |
Annual Sum or Average | 0.759295E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.8 | |
Maximum of Months | 0.325172E+10 | 11894.69 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.670341E+09 | 1040.56 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.538726E+09 | 888.78 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.599316E+09 | 988.92 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.510378E+09 | 755.21 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.532392E+09 | 582.38 | 03-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.519101E+09 | 532.07 | 26-JUN-11:30 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.495023E+09 | 560.07 | 07-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.555001E+09 | 572.32 | 17-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.523596E+09 | 769.87 | 11-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.579262E+09 | 1040.56 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.630401E+09 | 1040.56 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.653089E+09 | 1040.56 | 01-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.680663E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.495023E+09 | 532.07 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.670341E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.411749E+09 | 658.76 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335833E+09 | 529.58 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.376164E+09 | 625.70 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.321979E+09 | 454.18 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.337827E+09 | 362.16 | 03-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.331228E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314208E+09 | 344.75 | 07-JUL-07:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.352720E+09 | 349.08 | 17-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.329684E+09 | 421.02 | 13-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.359738E+09 | 658.76 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.390393E+09 | 658.76 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.401383E+09 | 658.76 | 01-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.426291E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.314208E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.411749E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.638238E+09 | 1040.56 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.521519E+09 | 776.21 | 02-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.593158E+09 | 988.92 | 17-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.510986E+09 | 753.56 | 14-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.534979E+09 | 583.36 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.522916E+09 | 496.34 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.497600E+09 | 561.62 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.558297E+09 | 573.39 | 17-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.521470E+09 | 748.12 | 11-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.563598E+09 | 1040.56 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.601442E+09 | 1040.56 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.618412E+09 | 1040.56 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.668261E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.497600E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.638238E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.415567E+09 | 658.71 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335618E+09 | 571.57 | 02-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.378183E+09 | 625.66 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324178E+09 | 488.24 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.337737E+09 | 425.07 | 03-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.328780E+09 | 341.47 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314214E+09 | 359.10 | 07-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.352231E+09 | 367.83 | 17-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.331179E+09 | 527.33 | 11-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.363550E+09 | 658.71 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.388606E+09 | 658.71 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.401803E+09 | 658.71 | 01-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.427165E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.314214E+09 | 341.47 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.415567E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.667665E+09 | 1040.56 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.537015E+09 | 880.64 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.598150E+09 | 986.98 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.509688E+09 | 744.29 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.532146E+09 | 579.58 | 03-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.518835E+09 | 528.45 | 26-JUN-11:30 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.494802E+09 | 556.22 | 07-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.554703E+09 | 569.04 | 17-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.522801E+09 | 759.06 | 11-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.577284E+09 | 1040.56 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.628186E+09 | 1040.56 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.650196E+09 | 1040.56 | 01-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.679147E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.494802E+09 | 528.45 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.667665E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.410252E+09 | 658.76 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335102E+09 | 523.58 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.375690E+09 | 624.69 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.321660E+09 | 447.35 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.337549E+09 | 360.19 | 03-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.331025E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314062E+09 | 341.96 | 07-JUL-07:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.352409E+09 | 346.52 | 17-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.329242E+09 | 368.55 | 13-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.359082E+09 | 658.76 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.389538E+09 | 658.76 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.400033E+09 | 658.76 | 01-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.425564E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.314062E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.410252E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.637064E+09 | 1040.56 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.520801E+09 | 756.17 | 02-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.592338E+09 | 986.98 | 17-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.510378E+09 | 742.56 | 14-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.534475E+09 | 580.62 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.522431E+09 | 496.34 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.497142E+09 | 557.86 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.557740E+09 | 570.17 | 17-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.520775E+09 | 736.21 | 11-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.562804E+09 | 1040.56 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.600433E+09 | 1040.56 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.616747E+09 | 1040.56 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.667313E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.497142E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.637064E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.414563E+09 | 658.71 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.334924E+09 | 568.53 | 02-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.377526E+09 | 624.65 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.323754E+09 | 483.04 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.337407E+09 | 370.18 | 03-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.328562E+09 | 338.77 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314029E+09 | 357.08 | 07-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.351938E+09 | 366.20 | 17-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330677E+09 | 523.36 | 11-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.362684E+09 | 658.71 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.387270E+09 | 658.71 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.400865E+09 | 658.71 | 01-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.426420E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.314029E+09 | 338.77 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.414563E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.670338E+09 | 1040.56 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.538724E+09 | 888.78 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.599315E+09 | 988.92 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.510377E+09 | 755.18 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.532391E+09 | 582.38 | 03-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.519101E+09 | 532.07 | 26-JUN-11:30 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.495023E+09 | 560.06 | 07-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.555001E+09 | 572.31 | 17-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.523595E+09 | 769.85 | 11-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.579261E+09 | 1040.56 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.630399E+09 | 1040.56 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.653087E+09 | 1040.56 | 01-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.680661E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.495023E+09 | 532.07 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.670338E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.411748E+09 | 658.76 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335832E+09 | 529.58 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.376164E+09 | 625.69 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.321979E+09 | 454.17 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.337827E+09 | 362.16 | 03-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.331227E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314208E+09 | 344.74 | 07-JUL-07:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.352720E+09 | 349.07 | 17-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.329684E+09 | 421.00 | 13-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.359737E+09 | 658.76 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.390392E+09 | 658.76 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.401382E+09 | 658.76 | 01-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.426290E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.314208E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.411748E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.638237E+09 | 1040.56 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.521519E+09 | 776.20 | 02-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.593157E+09 | 988.92 | 17-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.510985E+09 | 753.53 | 14-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.534978E+09 | 583.36 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.522916E+09 | 496.34 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.497599E+09 | 561.61 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.558296E+09 | 573.38 | 17-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.521470E+09 | 748.10 | 11-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.563597E+09 | 1040.56 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.601442E+09 | 1040.56 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.618412E+09 | 1040.56 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.668261E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.497599E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.638237E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.415566E+09 | 658.71 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335618E+09 | 571.56 | 02-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.378182E+09 | 625.65 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324177E+09 | 488.22 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.337737E+09 | 425.05 | 03-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.328780E+09 | 341.46 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314214E+09 | 359.10 | 07-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.352231E+09 | 367.82 | 17-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.331179E+09 | 527.32 | 11-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.363549E+09 | 658.71 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.388605E+09 | 658.71 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.401803E+09 | 658.71 | 01-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.427164E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.314214E+09 | 341.46 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.415566E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.670341E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173296E+10 |
February | 0.901968E+09 | 0.538726E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130411E+10 |
March | 0.107774E+10 | 0.599316E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122204E+10 |
April | 0.956342E+09 | 0.510378E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877536E+09 |
May | 0.103597E+10 | 0.532392E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2235233.00 | 0.902416E+09 |
June | 0.103308E+10 | 0.519101E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11579441.51 | 0.476211E+09 |
July | 0.959235E+09 | 0.495023E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38934239.20 | 0.322594E+09 |
August | 0.107774E+10 | 0.555001E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33880980.43 | 0.346712E+09 |
September | 0.956342E+09 | 0.523596E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20511819.25 | 0.600901E+09 |
October | 0.994195E+09 | 0.579262E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 505730.60 | 0.828758E+09 |
November | 0.984487E+09 | 0.630401E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116829E+10 |
December | 0.959235E+09 | 0.653089E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150830E+10 |
Annual Sum or Average | 0.119305E+11 | 0.680663E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107647E+09 | 0.112908E+11 |
Minimum of Months | 0.901968E+09 | 0.495023E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322594E+09 |
Maximum of Months | 0.107774E+10 | 0.670341E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38934239.20 | 0.173296E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.411749E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116240E+10 |
February | 0.571020E+09 | 0.335833E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.889493E+09 |
March | 0.682301E+09 | 0.376164E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834540E+09 |
April | 0.605444E+09 | 0.321979E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607337E+09 |
May | 0.655854E+09 | 0.337827E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1470600.97 | 0.609821E+09 |
June | 0.654023E+09 | 0.331228E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7660155.85 | 0.325446E+09 |
July | 0.607275E+09 | 0.314208E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24667396.72 | 0.223526E+09 |
August | 0.682301E+09 | 0.352720E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22051417.96 | 0.238060E+09 |
September | 0.605444E+09 | 0.329684E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12840731.55 | 0.415898E+09 |
October | 0.629407E+09 | 0.359738E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86183.03 | 0.577229E+09 |
November | 0.623262E+09 | 0.390393E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789348E+09 |
December | 0.607275E+09 | 0.401383E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101082E+10 |
Annual Sum or Average | 0.755301E+10 | 0.426291E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68776486.09 | 0.768392E+10 |
Minimum of Months | 0.571020E+09 | 0.314208E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223526E+09 |
Maximum of Months | 0.682301E+09 | 0.411749E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24667396.72 | 0.116240E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.638238E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178991E+10 |
February | 0.901968E+09 | 0.521519E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140994E+10 |
March | 0.107774E+10 | 0.593158E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129139E+10 |
April | 0.956342E+09 | 0.510986E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.927755E+09 |
May | 0.103597E+10 | 0.534979E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2175246.32 | 0.923666E+09 |
June | 0.103308E+10 | 0.522916E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11456940.51 | 0.481693E+09 |
July | 0.959235E+09 | 0.497600E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36915901.29 | 0.329895E+09 |
August | 0.107774E+10 | 0.558297E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32934503.60 | 0.358657E+09 |
September | 0.956342E+09 | 0.521470E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18414829.12 | 0.633757E+09 |
October | 0.994195E+09 | 0.563598E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 128330.51 | 0.914289E+09 |
November | 0.984487E+09 | 0.601442E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124253E+10 |
December | 0.959235E+09 | 0.618412E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157675E+10 |
Annual Sum or Average | 0.119305E+11 | 0.668261E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102026E+09 | 0.118802E+11 |
Minimum of Months | 0.901968E+09 | 0.497600E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329895E+09 |
Maximum of Months | 0.107774E+10 | 0.638238E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36915901.29 | 0.178991E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.415567E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116103E+10 |
February | 0.570983E+09 | 0.335618E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890014E+09 |
March | 0.682256E+09 | 0.378183E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834673E+09 |
April | 0.605404E+09 | 0.324178E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611257E+09 |
May | 0.655811E+09 | 0.337737E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1424862.79 | 0.624761E+09 |
June | 0.653980E+09 | 0.328780E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7595838.12 | 0.328003E+09 |
July | 0.607235E+09 | 0.314214E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24553604.52 | 0.227238E+09 |
August | 0.682256E+09 | 0.352231E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22008114.80 | 0.239517E+09 |
September | 0.605404E+09 | 0.331179E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12844803.12 | 0.414474E+09 |
October | 0.629366E+09 | 0.363550E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86213.66 | 0.573500E+09 |
November | 0.623221E+09 | 0.388606E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792361E+09 |
December | 0.607235E+09 | 0.401803E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101281E+10 |
Annual Sum or Average | 0.755252E+10 | 0.427165E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68513437.01 | 0.770963E+10 |
Minimum of Months | 0.570983E+09 | 0.314214E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227238E+09 |
Maximum of Months | 0.682256E+09 | 0.415567E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24553604.52 | 0.116103E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.667665E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.954630E+09 |
February | 0.901968E+09 | 0.537015E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732942E+09 |
March | 0.107774E+10 | 0.598150E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670495E+09 |
April | 0.956342E+09 | 0.509688E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469988E+09 |
May | 0.103597E+10 | 0.532146E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1353228.57 | 0.486548E+09 |
June | 0.103308E+10 | 0.518835E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6659076.80 | 0.252110E+09 |
July | 0.959235E+09 | 0.494802E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23475873.81 | 0.169999E+09 |
August | 0.107774E+10 | 0.554703E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19120048.51 | 0.188381E+09 |
September | 0.956342E+09 | 0.522801E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12231835.26 | 0.341443E+09 |
October | 0.994195E+09 | 0.577284E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 155568.06 | 0.492636E+09 |
November | 0.984487E+09 | 0.628186E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681924E+09 |
December | 0.959235E+09 | 0.650196E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.854771E+09 |
Annual Sum or Average | 0.119305E+11 | 0.679147E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62995631.01 | 0.629587E+10 |
Minimum of Months | 0.901968E+09 | 0.494802E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169999E+09 |
Maximum of Months | 0.107774E+10 | 0.667665E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23475873.81 | 0.954630E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.410252E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642353E+09 |
February | 0.571020E+09 | 0.335102E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503548E+09 |
March | 0.682301E+09 | 0.375690E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462634E+09 |
April | 0.605444E+09 | 0.321660E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334584E+09 |
May | 0.655854E+09 | 0.337549E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 827622.14 | 0.338946E+09 |
June | 0.654023E+09 | 0.331025E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4184017.52 | 0.178834E+09 |
July | 0.607275E+09 | 0.314062E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13572594.17 | 0.124262E+09 |
August | 0.682301E+09 | 0.352409E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12005723.12 | 0.133948E+09 |
September | 0.605444E+09 | 0.329242E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7062556.31 | 0.241295E+09 |
October | 0.629407E+09 | 0.359082E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49311.81 | 0.348343E+09 |
November | 0.623262E+09 | 0.389538E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466472E+09 |
December | 0.607275E+09 | 0.400033E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576128E+09 |
Annual Sum or Average | 0.755301E+10 | 0.425564E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37701825.06 | 0.435135E+10 |
Minimum of Months | 0.571020E+09 | 0.314062E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124262E+09 |
Maximum of Months | 0.682301E+09 | 0.410252E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13572594.17 | 0.642353E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.637064E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.775015E+10 |
February | 0.901968E+09 | 0.520801E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581209E+10 |
March | 0.107774E+10 | 0.592338E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558733E+10 |
April | 0.956342E+09 | 0.510378E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361183E+10 |
May | 0.103597E+10 | 0.534475E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15661780.58 | 0.338202E+10 |
June | 0.103308E+10 | 0.522431E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223428E+09 | 0.163851E+10 |
July | 0.959235E+09 | 0.497142E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540217E+09 | 0.746755E+09 |
August | 0.107774E+10 | 0.557740E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388237E+09 | 0.129490E+10 |
September | 0.956342E+09 | 0.520775E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68992154.28 | 0.227448E+10 |
October | 0.994195E+09 | 0.562804E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 901117.61 | 0.348106E+10 |
November | 0.984487E+09 | 0.600433E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483646E+10 |
December | 0.959235E+09 | 0.616747E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626329E+10 |
Annual Sum or Average | 0.119305E+11 | 0.667313E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123744E+10 | 0.466789E+11 |
Minimum of Months | 0.901968E+09 | 0.497142E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.746755E+09 |
Maximum of Months | 0.107774E+10 | 0.637064E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540217E+09 | 0.775015E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.414563E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640892E+09 |
February | 0.570983E+09 | 0.334924E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502449E+09 |
March | 0.682256E+09 | 0.377526E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461702E+09 |
April | 0.605404E+09 | 0.323754E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335439E+09 |
May | 0.655811E+09 | 0.337407E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 793864.03 | 0.349614E+09 |
June | 0.653980E+09 | 0.328562E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4107881.43 | 0.179969E+09 |
July | 0.607235E+09 | 0.314029E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13635940.74 | 0.126557E+09 |
August | 0.682256E+09 | 0.351938E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11941095.36 | 0.134526E+09 |
September | 0.605404E+09 | 0.330677E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7026872.88 | 0.242084E+09 |
October | 0.629366E+09 | 0.362684E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49326.83 | 0.347015E+09 |
November | 0.623221E+09 | 0.387270E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467373E+09 |
December | 0.607235E+09 | 0.400865E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576183E+09 |
Annual Sum or Average | 0.755252E+10 | 0.426420E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37554981.27 | 0.436380E+10 |
Minimum of Months | 0.570983E+09 | 0.314029E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126557E+09 |
Maximum of Months | 0.682256E+09 | 0.414563E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13635940.74 | 0.640892E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.670338E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148398E+10 |
February | 0.901968E+09 | 0.538724E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115051E+10 |
March | 0.107774E+10 | 0.599315E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107103E+10 |
April | 0.956342E+09 | 0.510377E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777757E+09 |
May | 0.103597E+10 | 0.532391E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1909957.32 | 0.792955E+09 |
June | 0.103308E+10 | 0.519101E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9833707.56 | 0.410016E+09 |
July | 0.959235E+09 | 0.495023E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33578027.50 | 0.277865E+09 |
August | 0.107774E+10 | 0.555001E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28503328.42 | 0.301587E+09 |
September | 0.956342E+09 | 0.523595E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17371790.41 | 0.534228E+09 |
October | 0.994195E+09 | 0.579261E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 218284.25 | 0.755387E+09 |
November | 0.984487E+09 | 0.630399E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104384E+10 |
December | 0.959235E+09 | 0.653087E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130755E+10 |
Annual Sum or Average | 0.119305E+11 | 0.680661E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91415095.45 | 0.990670E+10 |
Minimum of Months | 0.901968E+09 | 0.495023E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277865E+09 |
Maximum of Months | 0.107774E+10 | 0.670338E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33578027.50 | 0.148398E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.411748E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.994465E+09 |
February | 0.421807E+09 | 0.335832E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.785554E+09 |
March | 0.502994E+09 | 0.376164E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732335E+09 |
April | 0.447140E+09 | 0.321979E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537129E+09 |
May | 0.484071E+09 | 0.337827E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1208618.69 | 0.535618E+09 |
June | 0.482240E+09 | 0.331227E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6261267.27 | 0.280313E+09 |
July | 0.448971E+09 | 0.314208E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20433684.13 | 0.192533E+09 |
August | 0.502994E+09 | 0.352720E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18240906.85 | 0.206965E+09 |
September | 0.447140E+09 | 0.329684E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10771517.18 | 0.367885E+09 |
October | 0.465148E+09 | 0.359737E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57604.05 | 0.523845E+09 |
November | 0.460569E+09 | 0.390392E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706899E+09 |
December | 0.448971E+09 | 0.401382E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878845E+09 |
Annual Sum or Average | 0.557719E+10 | 0.426290E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56973598.17 | 0.674239E+10 |
Minimum of Months | 0.421807E+09 | 0.314208E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192533E+09 |
Maximum of Months | 0.502994E+09 | 0.411748E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20433684.13 | 0.994465E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.638237E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154173E+10 |
February | 0.901968E+09 | 0.521519E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124260E+10 |
March | 0.107774E+10 | 0.593157E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113047E+10 |
April | 0.956342E+09 | 0.510985E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817803E+09 |
May | 0.103597E+10 | 0.534978E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1860025.68 | 0.809798E+09 |
June | 0.103308E+10 | 0.522916E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9668660.86 | 0.415294E+09 |
July | 0.959235E+09 | 0.497599E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31148453.02 | 0.284632E+09 |
August | 0.107774E+10 | 0.558296E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27665267.04 | 0.311285E+09 |
September | 0.956342E+09 | 0.521470E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15586424.24 | 0.558755E+09 |
October | 0.994195E+09 | 0.563597E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 101560.73 | 0.820714E+09 |
November | 0.984487E+09 | 0.601442E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110939E+10 |
December | 0.959235E+09 | 0.618412E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138309E+10 |
Annual Sum or Average | 0.119305E+11 | 0.668261E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86030391.56 | 0.104256E+11 |
Minimum of Months | 0.901968E+09 | 0.497599E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284632E+09 |
Maximum of Months | 0.107774E+10 | 0.638237E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31148453.02 | 0.154173E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.415566E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.993532E+09 |
February | 0.570983E+09 | 0.335618E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784605E+09 |
March | 0.682256E+09 | 0.378182E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730818E+09 |
April | 0.605404E+09 | 0.324177E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539947E+09 |
May | 0.655811E+09 | 0.337737E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1204637.08 | 0.547737E+09 |
June | 0.653980E+09 | 0.328780E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6374291.67 | 0.282673E+09 |
July | 0.607235E+09 | 0.314214E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20734482.34 | 0.196021E+09 |
August | 0.682256E+09 | 0.352231E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18426665.76 | 0.207999E+09 |
September | 0.605404E+09 | 0.331179E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10781905.68 | 0.367036E+09 |
October | 0.629366E+09 | 0.363549E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74432.70 | 0.520000E+09 |
November | 0.623221E+09 | 0.388605E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.707312E+09 |
December | 0.607235E+09 | 0.401803E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.879167E+09 |
Annual Sum or Average | 0.755252E+10 | 0.427164E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57596415.23 | 0.675685E+10 |
Minimum of Months | 0.570983E+09 | 0.314214E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196021E+09 |
Maximum of Months | 0.682256E+09 | 0.415566E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20734482.34 | 0.993532E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202483E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162068E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149441E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108536E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1833536.11 | 0.109070E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9981223.80 | 0.555206E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38018373.30 | 0.376688E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32440814.19 | 0.414099E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20167154.33 | 0.752650E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36029.23 | 0.109159E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149690E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185413E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102477E+09 | 0.138572E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376688E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38018373.30 | 0.202483E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250012E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197793E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184898E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135271E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2398512.41 | 0.136864E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12826450.31 | 0.709253E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49057832.98 | 0.480720E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41723075.92 | 0.525192E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26158511.45 | 0.938014E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82814.08 | 0.132050E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180108E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224398E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132247E+09 | 0.170671E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480720E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49057832.98 | 0.250012E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255590E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198010E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187543E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137442E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1427365.81 | 0.140371E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10644873.07 | 0.744129E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38435151.02 | 0.500644E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37041596.94 | 0.536681E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20064170.60 | 0.938533E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129775E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176490E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223791E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107613E+09 | 0.172101E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500644E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38435151.02 | 0.255590E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3203.60 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 888.78 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1762.48 | 08-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 988.92 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2200.49 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 755.21 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1533.23 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 582.38 | 03-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.69 | 20-MAY-17:03 | 2772.32 | 22-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 532.07 | 26-JUN-11:30 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.87 | 29-JUN-15:00 | 1225.20 | 14-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 560.07 | 07-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 313.23 | 30-JUL-12:08 | 735.71 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 572.32 | 17-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 403.21 | 06-AUG-17:36 | 911.85 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 769.87 | 11-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 441.92 | 03-SEP-13:05 | 1591.42 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.30 | 15-OCT-14:00 | 1386.35 | 30-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1782.80 | 29-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2430.50 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 532.07 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 735.71 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 441.92 | 3203.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2134.99 | 05-JAN-22:01 |
February | 827.22 | 01-FEB-10:09 | 529.58 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1174.29 | 08-FEB-22:02 |
March | 827.22 | 01-MAR-10:09 | 625.70 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1468.76 | 02-MAR-23:00 |
April | 827.22 | 03-APR-09:09 | 454.18 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1023.63 | 27-APR-02:00 |
May | 827.22 | 01-MAY-09:09 | 362.16 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.45 | 20-MAY-17:03 | 1833.78 | 22-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.58 | 29-JUN-15:00 | 841.71 | 04-JUN-13:55 |
July | 827.22 | 03-JUL-09:09 | 344.75 | 07-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.03 | 30-JUL-12:08 | 490.03 | 05-JUL-01:00 |
August | 827.22 | 01-AUG-09:09 | 349.08 | 17-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.56 | 06-AUG-17:34 | 611.61 | 22-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 421.02 | 13-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 297.42 | 03-SEP-13:03 | 1055.65 | 12-SEP-03:00 |
October | 827.22 | 02-OCT-09:09 | 658.76 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.73 | 18-OCT-14:00 | 926.44 | 30-OCT-21:05 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1187.43 | 29-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1645.84 | 01-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.03 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 297.42 | 2134.99 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3204.51 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 776.21 | 02-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1766.65 | 08-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 988.92 | 17-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2267.78 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 753.56 | 14-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1546.67 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 583.36 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.40 | 19-MAY-16:00 | 2780.82 | 22-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.87 | 29-JUN-15:00 | 1234.11 | 04-JUN-13:55 |
July | 1306.65 | 03-JUL-09:09 | 561.62 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 320.05 | 30-JUL-12:05 | 743.05 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 573.39 | 17-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 407.91 | 06-AUG-17:34 | 931.34 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 748.12 | 11-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 423.04 | 03-SEP-13:10 | 1598.22 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.59 | 18-OCT-14:10 | 1428.38 | 30-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1783.31 | 29-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2447.00 | 01-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 743.05 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 423.04 | 3204.51 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2134.57 | 05-JAN-22:01 |
February | 827.17 | 01-FEB-10:09 | 571.57 | 02-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1175.43 | 08-FEB-22:02 |
March | 827.17 | 01-MAR-10:09 | 625.66 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1490.05 | 02-MAR-23:00 |
April | 827.17 | 03-APR-09:09 | 488.24 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1027.28 | 27-APR-02:00 |
May | 827.17 | 01-MAY-09:09 | 425.07 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.27 | 19-MAY-16:00 | 1830.94 | 22-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 341.47 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.58 | 29-JUN-15:00 | 818.94 | 14-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 359.10 | 07-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.86 | 30-JUL-14:45 | 507.24 | 05-JUL-01:00 |
August | 827.17 | 01-AUG-09:09 | 367.83 | 17-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.27 | 06-AUG-17:34 | 624.92 | 22-AUG-21:10 |
September | 827.17 | 01-SEP-09:09 | 527.33 | 11-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.95 | 03-SEP-13:03 | 1051.75 | 12-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 658.71 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.74 | 18-OCT-14:00 | 929.23 | 30-OCT-21:05 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1187.25 | 29-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1637.51 | 01-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 341.47 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507.24 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 293.95 | 2134.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1708.07 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 880.64 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 939.31 | 17-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 986.98 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1206.99 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 744.29 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 838.97 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 579.58 | 03-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.34 | 20-MAY-17:03 | 1676.88 | 22-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 528.45 | 26-JUN-11:30 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.15 | 29-JUN-15:00 | 695.85 | 14-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 556.22 | 07-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.10 | 30-JUL-12:00 | 413.54 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 569.04 | 17-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.65 | 06-AUG-18:00 | 522.71 | 23-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 759.06 | 11-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.12 | 03-SEP-13:00 | 970.26 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.79 | 15-OCT-14:00 | 797.25 | 30-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 953.91 | 29-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1383.32 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 528.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.54 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 273.12 | 1708.07 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1138.40 | 05-JAN-22:01 |
February | 827.22 | 01-FEB-10:09 | 523.58 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 630.38 | 17-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 624.69 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 817.52 | 02-MAR-23:00 |
April | 827.22 | 03-APR-09:09 | 447.35 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 583.08 | 27-APR-02:00 |
May | 827.22 | 01-MAY-09:09 | 360.19 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.56 | 20-MAY-17:03 | 1120.76 | 22-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.10 | 29-JUN-15:00 | 469.12 | 14-JUN-02:00 |
July | 827.22 | 03-JUL-09:09 | 341.96 | 07-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.34 | 30-JUL-11:58 | 284.09 | 05-JUL-01:00 |
August | 827.22 | 01-AUG-09:09 | 346.52 | 17-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.06 | 06-AUG-17:36 | 360.15 | 23-AUG-03:00 |
September | 827.22 | 01-SEP-09:09 | 368.55 | 13-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.04 | 03-SEP-12:51 | 648.83 | 12-SEP-03:00 |
October | 827.22 | 02-OCT-09:09 | 658.76 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 18-OCT-14:00 | 547.62 | 30-OCT-22:00 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 635.49 | 29-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 915.27 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.09 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 161.04 | 1138.40 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 38757.15 | 10-JAN-17:01 |
February | 1306.65 | 01-FEB-10:09 | 756.17 | 02-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 37117.37 | 01-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 986.98 | 17-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 31469.22 | 06-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 742.56 | 14-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 19484.05 | 28-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 580.62 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2521.95 | 19-MAY-16:10 | 17541.58 | 08-MAY-06:01 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4923.03 | 28-JUN-16:10 | 13864.72 | 16-JUN-07:00 |
July | 1306.65 | 03-JUL-09:09 | 557.86 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8602.16 | 17-JUL-16:03 | 9390.55 | 05-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 570.17 | 17-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5537.23 | 10-AUG-17:00 | 11523.62 | 28-AUG-06:01 |
September | 1306.65 | 01-SEP-09:09 | 736.21 | 11-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2978.21 | 01-SEP-16:10 | 14135.23 | 19-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.71 | 18-OCT-14:30 | 20496.00 | 10-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 26929.44 | 27-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 37333.50 | 29-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9390.55 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8602.16 | 38757.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1138.24 | 05-JAN-22:01 |
February | 827.17 | 01-FEB-10:09 | 568.53 | 02-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 636.54 | 17-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 624.65 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 836.95 | 02-MAR-23:00 |
April | 827.17 | 03-APR-09:09 | 483.04 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 581.37 | 27-APR-02:00 |
May | 827.17 | 01-MAY-09:09 | 370.18 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.74 | 20-MAY-17:03 | 1123.43 | 22-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 338.77 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.10 | 29-JUN-15:00 | 474.22 | 14-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 357.08 | 07-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.91 | 30-JUL-12:00 | 290.75 | 05-JUL-01:00 |
August | 827.17 | 01-AUG-09:09 | 366.20 | 17-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.24 | 06-AUG-17:34 | 361.03 | 23-AUG-03:00 |
September | 827.17 | 01-SEP-09:09 | 523.36 | 11-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.73 | 03-SEP-12:51 | 649.91 | 12-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 658.71 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.46 | 18-OCT-14:00 | 552.04 | 30-OCT-22:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 635.42 | 29-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 923.01 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 338.77 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.75 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 161.73 | 1138.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2673.06 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 888.78 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1471.74 | 08-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 988.92 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1918.70 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 755.18 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1358.74 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 582.38 | 03-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.69 | 20-MAY-17:03 | 2545.77 | 22-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 532.07 | 26-JUN-11:30 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.01 | 29-JUN-15:00 | 1089.72 | 14-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 560.06 | 07-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 277.37 | 30-JUL-11:53 | 651.49 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 572.31 | 17-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 328.24 | 06-AUG-17:24 | 808.82 | 23-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 769.85 | 11-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 387.56 | 03-SEP-13:00 | 1448.16 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.82 | 15-OCT-13:51 | 1216.10 | 30-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1491.41 | 29-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2026.18 | 01-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 532.07 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 651.49 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 387.56 | 2673.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 658.76 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1781.41 | 05-JAN-22:01 |
February | 805.43 | 01-FEB-08:09 | 529.58 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 980.61 | 08-FEB-22:02 |
March | 805.43 | 01-MAR-08:09 | 625.69 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1281.67 | 02-MAR-23:00 |
April | 805.43 | 03-APR-07:10 | 454.17 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 906.50 | 27-APR-02:00 |
May | 805.43 | 01-MAY-07:10 | 362.16 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.62 | 20-MAY-17:03 | 1685.38 | 22-MAY-04:00 |
June | 805.43 | 01-JUN-07:10 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.67 | 29-JUN-15:00 | 720.58 | 14-JUN-02:00 |
July | 805.43 | 03-JUL-07:10 | 344.74 | 07-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.48 | 30-JUL-14:58 | 433.95 | 05-JUL-01:00 |
August | 805.43 | 01-AUG-07:10 | 349.07 | 17-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 236.06 | 06-AUG-17:24 | 539.02 | 23-AUG-03:00 |
September | 805.43 | 01-SEP-07:10 | 421.00 | 13-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.26 | 03-SEP-12:51 | 961.43 | 12-SEP-03:00 |
October | 805.43 | 02-OCT-07:10 | 658.76 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.31 | 18-OCT-14:30 | 818.06 | 30-OCT-22:00 |
November | 805.43 | 01-NOV-07:10 | 658.76 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 993.34 | 29-NOV-22:02 |
December | 805.43 | 01-DEC-08:09 | 658.76 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1373.50 | 01-DEC-05:02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.95 | |||||
Maximum of Months | 805.43 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 249.26 | 1781.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2673.78 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 776.20 | 02-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1502.64 | 19-FEB-13:00 |
March | 1306.65 | 01-MAR-10:09 | 988.92 | 17-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1977.62 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 753.53 | 14-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1368.38 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 583.36 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.44 | 20-MAY-17:03 | 2553.19 | 22-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.00 | 29-JUN-15:00 | 1088.22 | 14-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 561.61 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.75 | 30-JUL-14:17 | 657.31 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 573.38 | 17-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 327.50 | 06-AUG-17:50 | 820.11 | 23-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 748.10 | 11-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 373.82 | 03-SEP-12:56 | 1453.57 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.36 | 18-OCT-14:40 | 1275.54 | 30-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1491.91 | 29-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2060.01 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 657.31 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 373.82 | 2673.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1781.18 | 05-JAN-22:01 |
February | 827.17 | 01-FEB-10:09 | 571.56 | 02-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 981.59 | 08-FEB-22:02 |
March | 827.17 | 01-MAR-10:09 | 625.65 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1299.45 | 02-MAR-23:00 |
April | 827.17 | 03-APR-09:09 | 488.22 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 909.30 | 27-APR-02:00 |
May | 827.17 | 01-MAY-09:09 | 425.05 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.54 | 19-MAY-16:00 | 1682.80 | 22-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 341.46 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.67 | 29-JUN-15:00 | 728.14 | 14-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 359.10 | 07-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.09 | 30-JUL-11:53 | 447.93 | 05-JUL-01:00 |
August | 827.17 | 01-AUG-09:09 | 367.82 | 17-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.02 | 06-AUG-17:24 | 542.86 | 23-AUG-03:00 |
September | 827.17 | 01-SEP-09:09 | 527.32 | 11-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.64 | 03-SEP-12:51 | 957.88 | 12-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 658.71 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.32 | 18-OCT-14:00 | 824.38 | 30-OCT-22:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 993.34 | 29-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1377.60 | 01-DEC-05:02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 341.46 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 447.93 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 250.64 | 1781.18 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3376.44 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2141.77 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2690.68 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1900.58 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.49 | 20-MAY-17:03 | 3745.07 | 22-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.89 | 29-JUN-15:00 | 1525.56 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.88 | 30-JUL-11:53 | 901.08 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.93 | 06-AUG-18:00 | 1152.88 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.69 | 03-SEP-13:00 | 2088.98 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.29 | 18-OCT-14:00 | 1746.22 | 30-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2014.86 | 26-NOV-19:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3074.84 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 901.08 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.69 | 3745.07 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4290.36 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2621.18 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3389.83 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2413.76 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.77 | 20-MAY-17:03 | 4654.14 | 22-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.35 | 29-JUN-15:00 | 1935.92 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.55 | 30-JUL-11:53 | 1132.93 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 526.90 | 06-AUG-17:50 | 1449.16 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 640.12 | 03-SEP-13:00 | 2596.61 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.77 | 18-OCT-14:00 | 2146.92 | 30-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2442.21 | 26-NOV-19:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3688.74 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1132.93 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 640.12 | 4654.14 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4639.58 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2554.68 | 08-FEB-22:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3436.63 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2354.80 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.07 | 20-MAY-17:03 | 4303.30 | 22-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.18 | 29-JUN-15:00 | 2019.38 | 04-JUN-13:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.27 | 30-JUL-14:20 | 1112.06 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.96 | 06-AUG-18:00 | 1452.49 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.73 | 03-SEP-12:51 | 2439.23 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2141.38 | 30-OCT-21:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2512.83 | 29-NOV-22:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3413.93 | 31-DEC-02:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1112.06 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.73 | 4639.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8939.10 | 19-JAN-16:50 | 6035.01 | 4936.01 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16291.39 | 28-FEB-08:02 | 54315.07 | 44424.13 | 163666.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16294.52 | 01-MAR-17:00 | 6035.01 | 4936.01 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18833.45 | 26-APR-08:00 | 18105.02 | 14808.04 | 54555.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41168.15 | 22-MAY-05:01 | 5717.38 | 1905.61 | 44905.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 40895.32 | 26-JUN-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41105.60 | 31-JUL-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 42351.49 | 14-AUG-05:12 | 3176.32 | 2742.16 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41291.52 | 06-SEP-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 37309.20 | 19-OCT-06:02 | 7623.17 | 9872.16 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17913.56 | 03-NOV-16:00 | 6035.01 | 4936.01 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14045.76 | 07-DEC-08:20 | 12070.02 | 9872.03 | 36370.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 8939.10 | 2541.06 | 1905.61 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42351.49 | 54315.07 | 44424.13 | 163666.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 130.56 | 14-JAN-13:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.83 |
February | 1507.94 | 26-FEB-14:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.69 |
March | 1936.88 | 22-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.75 |
April | 5747.04 | 25-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.92 |
May | 8894.95 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.56 | 0.00 |
June | 10101.46 | 23-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.62 | 0.00 |
July | 12623.18 | 17-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.73 | 0.00 |
August | 11442.93 | 07-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.90 | 0.00 |
September | 8526.88 | 05-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.11 |
October | 5311.77 | 18-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.14 |
November | 1107.53 | 03-NOV-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.97 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2198.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12623.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.56 | 2198.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3123.28 | 26-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1877.75 |
February | 3779.78 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 712.43 |
March | 3654.87 | 04-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1316.18 |
April | 2469.47 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.42 |
May | 3080.90 | 19-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.29 | 0.00 |
June | 4088.28 | 23-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.50 | 0.00 |
July | 6033.64 | 17-JUL-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.72 | 0.00 |
August | 6101.21 | 07-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.99 |
September | 6637.08 | 05-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.05 |
October | 1792.70 | 18-OCT-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 | 0.00 |
November | 1744.60 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.86 |
December | 3187.58 | 29-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1744.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6637.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.29 | 1877.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3330.21 | 06-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1659.41 |
February | 3448.30 | 04-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1106.33 |
March | 3094.91 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3388.14 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.37 |
May | 3256.65 | 19-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.68 | 0.00 |
June | 4304.68 | 29-JUN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.94 | 0.00 |
July | 6450.21 | 17-JUL-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.28 | 0.00 |
August | 5900.96 | 07-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.35 | 0.00 |
September | 5903.13 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.67 |
October | 2674.88 | 18-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 |
November | 2114.51 | 10-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.64 |
December | 3207.40 | 29-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2114.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6450.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.94 | 1659.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 4920.31 | 13-JAN-17:00 | 12070.02 | 9872.03 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8262.52 | 28-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8540.24 | 01-MAR-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12040.74 | 25-APR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 27563.13 | 30-MAY-06:03 | 5082.11 | 6581.44 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30332.71 | 26-JUN-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30587.68 | 31-JUL-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30489.15 | 14-AUG-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29448.69 | 05-SEP-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12824.76 | 19-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9304.57 | 03-NOV-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5561.80 | 07-DEC-16:30 | 12070.02 | 9872.03 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 4920.31 | 2541.06 | 2193.73 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30587.68 | 12070.02 | 9872.03 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 4693.25 | 13-JAN-16:50 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6964.56 | 28-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7127.61 | 29-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13053.62 | 25-APR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16293.30 | 30-MAY-15:30 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28607.72 | 26-JUN-06:02 | 7623.17 | 9872.16 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31935.64 | 17-JUL-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32304.72 | 07-AUG-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32339.87 | 05-SEP-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12683.28 | 18-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7444.62 | 03-NOV-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5151.38 | 07-DEC-16:25 | 12070.02 | 9872.03 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 4693.25 | 3176.32 | 2742.16 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32339.87 | 12070.02 | 9872.16 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 721.23 | 14-JAN-17:05 | 133.92 | 115.61 | 956.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.51 |
February | 1101.64 | 27-FEB-16:10 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.91 |
March | 1155.14 | 29-MAR-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.28 |
April | 3372.24 | 07-APR-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.82 |
May | 5279.57 | 19-MAY-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 99.40 | 0.00 |
June | 8062.18 | 21-JUN-06:03 | 1071.35 | 661.80 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.78 |
July | 11527.86 | 16-JUL-18:31 | 0.00 | 193.02 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 115.93 | 0.00 |
August | 11331.61 | 06-AUG-16:11 | 468.72 | 193.02 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 348.21 | 0.00 |
September | 11250.42 | 04-SEP-15:41 | 468.72 | 193.02 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 148.28 | 0.00 |
October | 2691.42 | 19-OCT-14:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.91 |
November | 1068.02 | 03-NOV-16:00 | 1272.23 | 561.38 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.53 |
December | 831.20 | 06-DEC-16:25 | 2544.47 | 2081.11 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 721.23 | 0.00 | 115.61 | 956.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11527.86 | 2544.47 | 2081.11 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 348.21 | 308.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 540.73 | 20-JAN-10:30 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.79 |
February | 1670.65 | 27-FEB-10:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.17 |
March | 3660.42 | 23-MAR-10:10 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.12 |
April | 6331.55 | 25-APR-09:20 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.64 |
May | 7818.53 | 19-MAY-08:50 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.35 |
June | 11823.50 | 25-JUN-08:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.70 |
July | 15957.88 | 02-JUL-08:51 | 339.13 | 139.65 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.18 |
August | 14722.64 | 06-AUG-08:52 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.65 |
September | 11734.64 | 04-SEP-08:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.24 |
October | 4642.45 | 18-OCT-09:40 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.49 |
November | 1692.23 | 03-NOV-09:50 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.30 |
December | 589.04 | 06-DEC-10:50 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 540.73 | 211.95 | 87.28 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.65 | |
Maximum of Months | 15957.88 | 1654.44 | 628.45 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4997.75 | 19-JAN-13:40 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.34 |
February | 11511.91 | 26-FEB-14:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.25 |
March | 11080.27 | 01-MAR-14:00 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.75 |
April | 10931.02 | 25-APR-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.63 |
May | 10580.54 | 19-MAY-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 42.67 | 0.00 |
June | 14979.54 | 25-JUN-13:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.29 |
July | 18722.18 | 02-JUL-12:52 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.73 |
August | 19068.43 | 06-AUG-13:32 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 263.70 | 0.00 |
September | 19884.56 | 03-SEP-13:02 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 332.76 | 0.00 |
October | 19898.48 | 15-OCT-14:32 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.80 |
November | 11338.48 | 03-NOV-13:30 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.10 |
December | 5339.42 | 07-DEC-13:50 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4997.75 | 267.84 | 110.30 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19898.48 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 332.76 | 482.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 726.32 | 13-JAN-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.66 |
February | 4176.41 | 28-FEB-16:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.44 |
March | 5307.24 | 28-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.39 |
April | 15729.84 | 16-APR-16:52 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.25 |
May | 15872.38 | 28-MAY-17:12 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.43 |
June | 16058.79 | 18-JUN-17:32 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.73 |
July | 17873.34 | 02-JUL-16:51 | 381.49 | 157.10 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.72 |
August | 16509.88 | 06-AUG-16:11 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 199.12 | 0.00 |
September | 16626.62 | 04-SEP-16:21 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 66.87 | 0.00 |
October | 10102.09 | 15-OCT-16:33 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.18 |
November | 3267.30 | 03-NOV-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.92 |
December | 1119.75 | 06-DEC-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 726.32 | 0.00 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17873.34 | 805.38 | 314.21 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 199.12 | 331.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 725.73 | 21-JAN-17:03 | 267.84 | 231.23 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.83 |
February | 964.25 | 27-FEB-16:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.32 |
March | 1005.70 | 29-MAR-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.97 |
April | 1199.38 | 07-APR-14:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.38 |
May | 3192.31 | 19-MAY-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 53.58 | 0.00 |
June | 4526.21 | 29-JUN-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 82.00 | 0.00 |
July | 8693.68 | 16-JUL-18:21 | 0.00 | 275.74 | 3861.03 | 0.00 | 0.00 | 0.00 | 0.00 | 62.54 | 0.00 |
August | 6787.42 | 07-AUG-06:03 | 1071.35 | 661.80 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 |
September | 8771.80 | 04-SEP-16:11 | 669.60 | 275.74 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 72.01 | 0.00 |
October | 2388.94 | 19-OCT-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.01 |
November | 1109.04 | 08-NOV-14:10 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.61 |
December | 852.31 | 06-DEC-16:00 | 1272.23 | 741.04 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 725.73 | 0.00 | 231.23 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8771.80 | 1306.65 | 741.04 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 82.00 | 166.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 556.61 | 20-JAN-10:10 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.44 |
February | 1377.15 | 28-FEB-09:25 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.07 |
March | 2209.76 | 23-MAR-10:30 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.03 |
April | 4030.44 | 25-APR-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.58 |
May | 5192.92 | 19-MAY-09:20 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.31 |
June | 8800.26 | 30-JUN-06:02 | 1017.38 | 628.46 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.15 |
July | 12462.32 | 16-JUL-09:41 | 339.13 | 139.65 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.70 |
August | 11556.42 | 06-AUG-09:32 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 24.12 | 0.00 |
September | 11974.07 | 04-SEP-08:51 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.57 |
October | 3981.52 | 18-OCT-09:40 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.51 |
November | 1965.65 | 03-NOV-09:15 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.48 |
December | 625.76 | 07-DEC-10:50 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 556.61 | 254.35 | 104.74 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12462.32 | 1654.44 | 628.46 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 24.12 | 180.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2304.68 | 14-JAN-12:30 | 137.54 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.83 |
February | 8650.98 | 27-FEB-13:25 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 647.87 |
March | 7607.11 | 01-MAR-13:20 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1883.93 |
April | 6608.13 | 25-APR-12:07 | 3816.70 | 1489.03 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 885.50 |
May | 7499.86 | 19-MAY-14:00 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 326.84 | 0.00 |
June | 10861.26 | 29-JUN-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4624.09 | 0.00 |
July | 14980.45 | 16-JUL-16:21 | 669.60 | 275.74 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 55.09 | 0.00 |
August | 14866.57 | 06-AUG-13:32 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 152.14 | 0.00 |
September | 16214.50 | 04-SEP-14:51 | 535.68 | 220.59 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 58.14 | 0.00 |
October | 14564.41 | 15-OCT-16:12 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.30 |
November | 9628.49 | 03-NOV-12:07 | 3816.70 | 1489.03 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.02 |
December | 3125.45 | 02-DEC-13:30 | 133.92 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2304.68 | 133.92 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16214.50 | 3816.70 | 1489.03 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 4624.09 | 1883.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 675.16 | 13-JAN-16:10 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.38 |
February | 3160.58 | 28-FEB-16:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.76 |
March | 3329.27 | 28-MAR-17:30 | 84.78 | 104.74 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.55 |
April | 5677.22 | 16-APR-17:22 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.39 |
May | 8545.62 | 28-MAY-18:12 | 0.00 | 69.82 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.14 |
June | 10767.91 | 24-JUN-17:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 |
July | 14322.34 | 16-JUL-18:21 | 0.00 | 174.55 | 2444.18 | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 0.00 |
August | 12635.37 | 06-AUG-16:11 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 117.24 | 0.00 |
September | 14076.57 | 04-SEP-16:51 | 423.88 | 174.55 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | 0.00 |
October | 8486.75 | 15-OCT-16:12 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.27 |
November | 2964.95 | 03-NOV-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.37 |
December | 822.66 | 06-DEC-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 675.16 | 0.00 | 69.82 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14322.34 | 805.38 | 314.21 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 117.24 | 173.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 796.55 | 13-JAN-16:50 | 1272.23 | 1023.77 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.78 |
February | 1208.81 | 27-FEB-13:30 | 2544.47 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.28 |
March | 1188.80 | 01-MAR-14:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.44 |
April | 3335.61 | 07-APR-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.04 |
May | 4771.05 | 19-MAY-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 83.32 | 0.00 |
June | 7878.89 | 30-JUN-06:02 | 1607.03 | 992.70 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.08 |
July | 10764.96 | 16-JUL-18:22 | 0.00 | 275.74 | 3861.03 | 0.00 | 0.00 | 0.00 | 0.00 | 97.67 | 0.00 |
August | 9801.83 | 06-AUG-14:41 | 468.72 | 193.02 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 199.19 | 0.00 |
September | 9957.88 | 04-SEP-16:11 | 669.60 | 275.74 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 102.90 | 0.00 |
October | 2972.03 | 19-OCT-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.63 |
November | 1261.03 | 03-NOV-13:25 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.99 |
December | 886.35 | 06-DEC-16:00 | 1272.23 | 756.40 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 796.55 | 0.00 | 193.02 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10764.96 | 2613.31 | 1023.77 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 199.19 | 266.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 622.29 | 14-JAN-11:10 | 254.35 | 104.74 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.35 |
February | 4775.36 | 28-FEB-13:01 | 5638.00 | 2199.59 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.43 |
March | 5905.40 | 23-MAR-12:01 | 5638.00 | 2199.59 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.26 |
April | 7243.51 | 25-APR-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.31 |
May | 8026.43 | 19-MAY-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 |
June | 14001.24 | 11-JUN-09:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.47 |
July | 15828.33 | 16-JUL-09:01 | 339.13 | 139.65 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.19 |
August | 16289.26 | 06-AUG-08:41 | 381.52 | 157.11 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.16 |
September | 14823.86 | 04-SEP-08:51 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.66 |
October | 6094.69 | 18-OCT-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.77 |
November | 4983.22 | 02-NOV-12:01 | 6443.43 | 2513.82 | 7268.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.68 |
December | 672.32 | 07-DEC-11:10 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 622.29 | 211.95 | 87.28 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 | |
Maximum of Months | 16289.26 | 6443.43 | 2513.82 | 7268.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5956.13 | 19-JAN-13:30 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.06 |
February | 13524.13 | 26-FEB-13:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.57 |
March | 11851.95 | 01-MAR-13:35 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.21 |
April | 10632.84 | 25-APR-13:20 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.63 |
May | 10042.98 | 19-MAY-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 35.87 | 0.00 |
June | 10578.48 | 25-JUN-11:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.50 |
July | 17256.91 | 16-JUL-13:01 | 468.72 | 193.02 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 36.07 | 0.00 |
August | 17899.76 | 06-AUG-14:41 | 468.72 | 193.02 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 162.19 | 0.00 |
September | 18716.33 | 04-SEP-14:51 | 535.68 | 220.59 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 81.25 | 0.00 |
October | 17450.64 | 15-OCT-15:22 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.75 |
November | 11982.67 | 03-NOV-13:05 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.59 |
December | 6360.17 | 12-DEC-12:30 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5956.13 | 267.84 | 110.30 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18716.33 | 2613.31 | 992.69 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 162.19 | 483.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 759.03 | 13-JAN-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.60 |
February | 4435.06 | 28-FEB-16:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.99 |
March | 5356.54 | 28-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.72 |
April | 9965.67 | 22-APR-17:06 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.93 |
May | 14753.51 | 28-MAY-17:12 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.49 |
June | 14722.86 | 24-JUN-17:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.19 |
July | 17216.96 | 16-JUL-17:01 | 0.00 | 174.55 | 2444.18 | 0.00 | 0.00 | 0.00 | 0.00 | 31.97 | 0.00 |
August | 15557.49 | 06-AUG-16:42 | 423.88 | 174.55 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 197.36 | 0.00 |
September | 16848.02 | 04-SEP-16:11 | 423.88 | 174.55 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 36.28 | 0.00 |
October | 10690.16 | 15-OCT-15:22 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.32 |
November | 3624.59 | 03-NOV-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.35 |
December | 1415.47 | 06-DEC-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 759.03 | 0.00 | 87.28 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17216.96 | 805.38 | 314.21 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 197.36 | 278.49 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.178507E+12 | 253237.92 | 09-JAN-08:09 | 0.995551E+11 | 148660.08 | 09-JAN-09:00 |
February | 0.121587E+12 | 217003.00 | 06-FEB-07:10 | 0.624592E+11 | 144148.27 | 01-FEB-07:49 |
March | 0.115395E+12 | 212124.37 | 06-MAR-07:10 | 0.487074E+11 | 124640.77 | 04-MAR-07:30 |
April | 0.921741E+11 | 93416.67 | 06-APR-15:00 | 0.250449E+11 | 63415.52 | 29-APR-06:40 |
May | 0.100843E+12 | 126985.19 | 08-MAY-06:10 | 0.203186E+11 | 58584.67 | 08-MAY-06:30 |
June | 0.115833E+12 | 144158.34 | 29-JUN-15:09 | 0.119629E+11 | 32558.99 | 16-JUN-06:19 |
July | 0.132883E+12 | 175580.61 | 17-JUL-15:30 | 0.108901E+11 | 11312.17 | 05-JUL-06:19 |
August | 0.132150E+12 | 159351.70 | 07-AUG-15:39 | 0.114548E+11 | 15129.09 | 18-AUG-06:10 |
September | 0.104654E+12 | 157006.61 | 07-SEP-14:00 | 0.133841E+11 | 36098.01 | 19-SEP-06:19 |
October | 0.971747E+11 | 137946.55 | 10-OCT-06:10 | 0.208899E+11 | 71517.00 | 10-OCT-06:40 |
November | 0.109961E+12 | 208928.38 | 27-NOV-07:10 | 0.373623E+11 | 101111.37 | 27-NOV-08:09 |
December | 0.144118E+12 | 218617.38 | 26-DEC-07:10 | 0.728386E+11 | 148554.53 | 29-DEC-08:20 |
Annual Sum or Average | 0.144528E+13 | 0.434868E+12 | ||||
Minimum of Months | 0.921741E+11 | 93416.67 | 0.108901E+11 | 11312.17 | ||
Maximum of Months | 0.178507E+12 | 253237.92 | 0.995551E+11 | 148660.08 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.203139E+11 | 0.626771E+10 | 0.593559E+11 | 0.983364E+09 | 0.519099E+10 | 12379742.02 | 0.863822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178121E+11 | 0.491554E+10 | 0.537310E+11 | 0.889297E+09 | 0.413262E+10 | 11196021.66 | 0.398479E+11 | 0.247169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208531E+11 | 0.447730E+10 | 0.617796E+11 | 0.102911E+10 | 0.473464E+10 | 12675672.10 | 0.221512E+11 | 0.357194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183937E+11 | 0.347008E+10 | 0.572952E+11 | 0.946221E+09 | 0.482616E+10 | 11960507.72 | 0.528414E+10 | 0.194667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196916E+11 | 0.289027E+10 | 0.605677E+11 | 0.100554E+10 | 0.658086E+10 | 12527707.06 | 0.411968E+10 | 0.597441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.195061E+11 | 0.253198E+10 | 0.594895E+11 | 0.989844E+09 | 0.126874E+11 | 12231776.97 | 0.326056E+09 | 0.202899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.183183E+11 | 0.272636E+10 | 0.583622E+11 | 0.961662E+09 | 0.168029E+11 | 12256437.81 | 27267688.39 | 0.356722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.204689E+11 | 0.326860E+10 | 0.617796E+11 | 0.102888E+10 | 0.156979E+11 | 12675672.10 | 0.189676E+09 | 0.297035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.185086E+11 | 0.391803E+10 | 0.572729E+11 | 0.946035E+09 | 0.918304E+10 | 11960507.72 | 0.884443E+09 | 0.139287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195068E+11 | 0.500538E+10 | 0.593671E+11 | 0.982662E+09 | 0.553724E+10 | 12379742.02 | 0.338380E+10 | 0.337930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197818E+11 | 0.579766E+10 | 0.580818E+11 | 0.964787E+09 | 0.435053E+10 | 12059151.09 | 0.204203E+11 | 0.552439E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.196735E+11 | 0.653724E+10 | 0.583511E+11 | 0.962690E+09 | 0.462335E+10 | 12256437.81 | 0.539568E+11 | 810028.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232828E+12 | 0.518061E+11 | 0.705434E+12 | 0.116901E+11 | 0.943475E+11 | 0.146559E+09 | 0.236973E+12 | 0.112052E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.178121E+11 | 0.253198E+10 | 0.537310E+11 | 0.889297E+09 | 0.413262E+10 | 11196021.66 | 27267688.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.208531E+11 | 0.653724E+10 | 0.617796E+11 | 0.102911E+10 | 0.168029E+11 | 12675672.10 | 0.863822E+11 | 0.356722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.873180E+11 | 0.00 | 0.122371E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.512884E+11 | 0.00 | 0.111708E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.359857E+11 | 0.00 | 0.127217E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.134277E+11 | 0.00 | 0.116173E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.843875E+10 | 0.00 | 0.118798E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.684622E+09 | 0.00 | 0.112783E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 13731948.54 | 0.00 | 0.108764E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.176058E+09 | 0.00 | 0.112788E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.276249E+10 | 0.00 | 0.106216E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.967149E+10 | 0.00 | 0.112184E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.260806E+11 | 0.00 | 0.112817E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.610569E+11 | 0.00 | 0.117816E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.296904E+12 | 0.00 | 0.137964E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 13731948.54 | 0.00 | 0.106216E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.873180E+11 | 0.00 | 0.127217E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 25003.79 | 02-JAN-08:09 | 5686.19 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 840.16 | 04-JAN-08:20 | 7943.48 | 09-JAN-07:10 | 6.85 | 04-JAN-18:10 | 208488.79 | 09-JAN-07:10 |
February | 22756.81 | 02-FEB-08:09 | 5686.19 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 837.16 | 02-FEB-08:20 | 5976.67 | 06-FEB-07:10 | 6.85 | 03-FEB-07:19 | 175656.09 | 06-FEB-07:10 |
March | 24489.72 | 17-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 839.47 | 17-MAR-07:19 | 6234.04 | 06-MAR-06:10 | 6.85 | 01-MAR-06:10 | 177125.66 | 06-MAR-07:10 |
April | 22127.58 | 14-APR-07:10 | 5686.19 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 836.33 | 14-APR-07:19 | 12856.03 | 25-APR-15:00 | 6.85 | 01-APR-05:19 | 59317.47 | 29-APR-06:10 |
May | 20604.53 | 03-MAY-07:10 | 5686.19 | 01-MAY-05:10 | 45864.70 | 01-MAY-07:10 | 834.31 | 03-MAY-07:19 | 21548.62 | 19-MAY-15:30 | 6.85 | 15-MAY-11:09 | 95151.51 | 08-MAY-06:10 |
June | 19774.97 | 26-JUN-11:30 | 3328.83 | 01-JUN-20:10 | 45864.70 | 01-JUN-07:10 | 833.17 | 16-JUN-07:19 | 26856.38 | 29-JUN-15:09 | 6.85 | 18-JUN-16:49 | 13996.87 | 16-JUN-06:10 |
July | 20272.22 | 07-JUL-07:30 | 3328.83 | 01-JUL-20:30 | 45864.70 | 03-JUL-07:10 | 833.87 | 07-JUL-07:40 | 33603.97 | 17-JUL-15:30 | 6.85 | 02-JUL-08:09 | 5918.32 | 05-JUL-06:19 |
August | 20385.19 | 17-AUG-07:10 | 5686.19 | 03-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 834.02 | 17-AUG-07:19 | 31529.20 | 07-AUG-15:39 | 6.85 | 06-AUG-08:09 | 14123.84 | 18-AUG-06:10 |
September | 21941.55 | 11-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 836.08 | 11-SEP-07:19 | 30022.11 | 07-SEP-14:00 | 6.85 | 03-SEP-11:39 | 35708.39 | 19-SEP-06:10 |
October | 25003.79 | 30-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 840.16 | 30-OCT-07:19 | 15012.67 | 18-OCT-15:50 | 6.85 | 06-OCT-07:10 | 98895.06 | 10-OCT-06:10 |
November | 25003.79 | 01-NOV-07:10 | 5686.19 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 840.16 | 01-NOV-07:19 | 7151.57 | 03-NOV-15:30 | 6.85 | 02-NOV-07:10 | 167806.99 | 27-NOV-07:10 |
December | 25003.79 | 01-DEC-16:40 | 5686.19 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 840.16 | 21-DEC-08:20 | 6129.64 | 26-DEC-07:10 | 6.85 | 04-DEC-08:09 | 177117.49 | 26-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 19774.97 | 3328.83 | 45864.70 | 833.17 | 5976.67 | 6.85 | 5918.32 | |||||||
Maximum of Months | 25003.79 | 5686.19 | 45864.70 | 840.16 | 33603.97 | 6.85 | 208488.79 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8595.18 | 28-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7576.50 | 01-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20165.41 | 06-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41980.98 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 54930.51 | 29-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 80132.97 | 17-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 65538.06 | 07-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 65886.58 | 07-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30721.78 | 18-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6217.02 | 09-NOV-14:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 246.48 | 07-DEC-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80132.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 253237.92 | 09-JAN-08:09 | 25003.79 | 45864.70 | 5686.19 | 818.16 | 5340.35 | 6.85 | 170517.87 | 0.00 | 0.00 |
February | 217003.00 | 06-FEB-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 5976.67 | 6.85 | 175656.09 | 0.00 | 0.00 |
March | 212124.37 | 06-MAR-07:10 | 7567.26 | 21098.80 | 0.00 | 243.70 | 6082.09 | 6.85 | 177125.66 | 0.00 | 0.00 |
April | 93416.67 | 06-APR-15:00 | 19671.42 | 42072.41 | 0.00 | 831.72 | 10668.86 | 6.85 | 0.00 | 20165.41 | 0.00 |
May | 126985.19 | 08-MAY-06:10 | 6881.00 | 21098.80 | 0.00 | 243.53 | 3603.51 | 6.85 | 95151.51 | 0.00 | 0.00 |
June | 144158.34 | 29-JUN-15:09 | 19671.42 | 42072.41 | 0.00 | 831.72 | 26856.38 | 6.85 | 0.00 | 54719.57 | 0.00 |
July | 175580.61 | 17-JUL-15:30 | 19671.42 | 42072.41 | 0.00 | 831.72 | 33603.97 | 6.85 | 0.00 | 79394.24 | 0.00 |
August | 159351.70 | 07-AUG-15:39 | 19671.42 | 42072.41 | 0.00 | 831.72 | 31529.20 | 6.85 | 0.00 | 65240.11 | 0.00 |
September | 157006.61 | 07-SEP-14:00 | 19671.42 | 40588.47 | 0.00 | 831.19 | 30022.11 | 6.85 | 0.00 | 65886.58 | 0.00 |
October | 137946.55 | 10-OCT-06:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 3681.24 | 6.85 | 98895.06 | 0.00 | 0.00 |
November | 208928.38 | 27-NOV-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 5751.13 | 6.85 | 167806.99 | 0.00 | 0.00 |
December | 218617.38 | 26-DEC-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 6129.64 | 6.85 | 177117.49 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 93416.67 | 6881.00 | 21098.80 | 0.00 | 243.53 | 3603.51 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 253237.92 | 25003.79 | 45864.70 | 5686.19 | 831.72 | 33603.97 | 6.85 | 177125.66 | 79394.24 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 139081.09 | 09-JAN-09:39 | 0.00 | 12080.38 | 31-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 136184.68 | 01-FEB-07:40 | 0.00 | 12174.28 | 16-FEB-12:20 | 0.00 |
March | 0.00 | 0.00 | 120431.35 | 04-MAR-07:30 | 0.00 | 12086.90 | 01-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 57628.65 | 29-APR-06:19 | 0.00 | 10837.30 | 18-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 49699.84 | 08-MAY-06:30 | 0.00 | 10234.66 | 04-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 23706.62 | 16-JUN-06:19 | 0.00 | 10099.07 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 2862.74 | 05-JUL-06:19 | 0.00 | 9957.59 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 7182.85 | 18-AUG-06:10 | 0.00 | 9889.01 | 03-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 28038.95 | 19-SEP-06:30 | 0.00 | 9939.21 | 29-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 63463.19 | 10-OCT-06:30 | 0.00 | 10057.08 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 92979.08 | 27-NOV-08:20 | 0.00 | 10199.73 | 28-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 139081.09 | 29-DEC-08:20 | 0.00 | 11166.07 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 2862.74 | 0.00 | 9889.01 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 139081.09 | 0.00 | 12174.28 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 19.31 | 0.50 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
February | 0.17 | 19.38 | 0.17 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.40 | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Annual Sum or Average | 0.83 | 19.34 | 0.83 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.40 | 0.50 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.00 | 18.83 | 3.83 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
February | 0.67 | 17.68 | 0.33 | 18.16 | 0.00 | 18.16 | 0.00 | 18.16 |
March | 1.00 | 17.97 | 0.50 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 17.69 | 0.33 | 18.16 | 0.00 | 18.16 | 0.00 | 18.16 |
December | 1.33 | 18.85 | 1.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
Annual Sum or Average | 8.67 | 18.56 | 6.00 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.00 | 18.85 | 3.83 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 77.17 | 16.44 | 40.50 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 |
February | 24.83 | 16.50 | 11.33 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 |
March | 14.00 | 15.96 | 5.50 | 16.42 | 0.00 | 16.42 | 0.00 | 16.42 |
April | 0.17 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
May | 0.50 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.46 | 2.00 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.58 | 1.33 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.53 | 2.67 | 27.54 |
October | 0.33 | 18.03 | 0.17 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 |
November | 13.33 | 15.94 | 6.17 | 16.27 | 0.00 | 16.27 | 0.00 | 16.27 |
December | 44.50 | 15.95 | 21.00 | 16.34 | 0.00 | 16.34 | 0.00 | 16.34 |
Annual Sum or Average | 174.83 | 16.25 | 84.67 | 16.73 | 8.50 | 17.08 | 6.00 | 17.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 18.03 | 40.50 | 18.49 | 3.50 | 27.58 | 2.67 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 40.67 | 14.58 | 9.50 | 14.69 | 0.00 | 14.69 | 0.00 | 14.69 |
February | 15.00 | 14.95 | 2.17 | 15.00 | 0.00 | 15.00 | 0.00 | 15.00 |
March | 8.83 | 14.77 | 1.00 | 14.74 | 0.00 | 14.74 | 0.00 | 14.74 |
April | 0.17 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 |
May | 0.50 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.78 | 6.67 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.91 | 12.67 | 27.95 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.33 | 3.17 | 28.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.92 | 5.50 | 27.96 |
October | 0.17 | 16.58 | 0.00 | 16.58 | 0.00 | 16.58 | 0.00 | 16.58 |
November | 8.83 | 14.94 | 2.33 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
December | 31.33 | 14.76 | 7.33 | 14.73 | 0.00 | 14.73 | 0.00 | 14.73 |
Annual Sum or Average | 105.50 | 14.75 | 22.33 | 14.78 | 32.00 | 17.42 | 28.00 | 18.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.69 | 0.00 | 14.69 |
Maximum of Months | 40.67 | 16.99 | 9.50 | 16.99 | 15.00 | 28.33 | 12.67 | 28.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 33.50 | 14.93 | 8.17 | 15.20 | 0.00 | 15.20 | 0.00 | 15.20 |
February | 12.00 | 15.16 | 1.17 | 15.28 | 1.00 | 16.16 | 1.00 | 16.93 |
March | 7.83 | 14.86 | 1.00 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 |
April | 0.17 | 17.06 | 0.00 | 17.06 | 0.83 | 25.73 | 0.83 | 26.52 |
May | 0.50 | 16.89 | 0.00 | 16.89 | 1.17 | 24.21 | 1.17 | 25.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.61 | 4.00 | 27.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.87 | 7.67 | 27.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.98 | 4.50 | 28.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.15 | 6.67 | 28.20 |
October | 0.17 | 16.68 | 0.00 | 16.68 | 2.33 | 27.18 | 2.33 | 27.55 |
November | 6.00 | 15.13 | 1.00 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
December | 24.33 | 14.90 | 4.83 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 |
Annual Sum or Average | 84.50 | 14.98 | 16.17 | 15.11 | 33.17 | 18.28 | 28.17 | 19.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.90 | 0.00 | 14.90 |
Maximum of Months | 33.50 | 17.06 | 8.17 | 17.06 | 10.17 | 28.15 | 7.67 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 39.67 | 14.47 | 9.50 | 14.54 | 0.00 | 14.54 | 0.00 | 14.54 |
February | 14.83 | 14.85 | 2.33 | 14.79 | 0.00 | 14.79 | 0.00 | 14.79 |
March | 9.00 | 14.67 | 1.50 | 14.65 | 0.00 | 14.65 | 0.00 | 14.65 |
April | 0.17 | 17.10 | 0.00 | 17.10 | 1.17 | 26.58 | 0.67 | 27.05 |
May | 0.50 | 16.93 | 0.00 | 16.93 | 4.00 | 26.77 | 1.67 | 27.06 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.14 | 2.67 | 28.15 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 28.46 | 5.83 | 28.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.12 | 3.33 | 28.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.31 | 3.50 | 28.37 |
October | 0.33 | 15.80 | 0.00 | 15.80 | 0.50 | 22.92 | 0.33 | 24.30 |
November | 8.33 | 14.78 | 2.17 | 14.76 | 0.00 | 14.76 | 0.00 | 14.76 |
December | 33.00 | 14.73 | 9.33 | 14.69 | 0.00 | 14.69 | 0.00 | 14.69 |
Annual Sum or Average | 105.83 | 14.67 | 24.83 | 14.66 | 34.00 | 17.47 | 18.00 | 18.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.54 | 0.00 | 14.54 |
Maximum of Months | 39.67 | 17.10 | 9.50 | 17.10 | 11.33 | 28.46 | 5.83 | 28.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 51.67 | 18.14 | 37.83 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
February | 7.17 | 18.08 | 4.00 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 |
March | 4.83 | 17.53 | 2.67 | 18.16 | 0.00 | 18.16 | 0.00 | 18.16 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 19.05 | 0.83 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
December | 8.50 | 17.54 | 6.17 | 17.88 | 0.00 | 17.88 | 0.00 | 17.88 |
Annual Sum or Average | 73.33 | 18.04 | 51.50 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 51.67 | 19.05 | 37.83 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.00 | 15.28 | 3.17 | 15.45 | 0.00 | 15.45 | 0.00 | 15.45 |
February | 1.67 | 16.37 | 0.17 | 16.25 | 0.00 | 16.25 | 0.00 | 16.25 |
March | 2.00 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.53 | 3.83 | 27.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.71 | 9.50 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.91 | 2.83 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.68 | 5.33 | 27.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 16.64 | 0.00 | 16.64 | 0.00 | 16.64 | 0.00 | 16.64 |
December | 4.33 | 15.16 | 1.67 | 15.08 | 0.00 | 15.08 | 0.00 | 15.08 |
Annual Sum or Average | 23.17 | 15.34 | 5.00 | 15.41 | 22.83 | 20.92 | 21.50 | 22.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.00 | 16.64 | 3.17 | 16.64 | 10.00 | 27.91 | 9.50 | 27.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 98.83 | 16.65 | 91.17 | 16.71 | 0.00 | 16.71 | 0.00 | 16.71 |
February | 43.83 | 17.12 | 43.17 | 17.12 | 1.17 | 17.26 | 1.17 | 17.39 |
March | 40.83 | 18.42 | 40.67 | 18.43 | 0.00 | 18.43 | 0.00 | 18.43 |
April | 21.83 | 19.26 | 21.83 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
May | 16.50 | 19.28 | 16.50 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
June | 1.00 | 20.22 | 1.00 | 20.22 | 0.00 | 20.22 | 0.00 | 20.22 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 26.81 | 8.00 | 26.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 26.43 | 5.83 | 26.38 |
September | 1.83 | 20.13 | 1.83 | 20.13 | 8.17 | 25.49 | 6.50 | 26.38 |
October | 7.17 | 18.88 | 7.17 | 18.88 | 2.67 | 20.28 | 2.67 | 21.31 |
November | 27.17 | 18.25 | 27.00 | 18.26 | 0.33 | 18.31 | 0.33 | 18.37 |
December | 56.67 | 17.24 | 54.67 | 17.27 | 0.00 | 17.27 | 0.00 | 17.27 |
Annual Sum or Average | 315.67 | 17.59 | 305.00 | 17.63 | 27.17 | 18.03 | 24.50 | 18.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 0.00 | 16.71 |
Maximum of Months | 98.83 | 20.22 | 91.17 | 20.22 | 8.50 | 26.81 | 8.00 | 26.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.00 | 15.21 | 3.33 | 15.30 | 0.00 | 15.30 | 0.00 | 15.30 |
February | 1.83 | 16.26 | 0.00 | 16.26 | 0.00 | 16.26 | 0.00 | 16.26 |
March | 1.83 | 15.00 | 0.00 | 15.00 | 0.00 | 15.00 | 0.00 | 15.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.43 | 0.00 | 27.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.66 | 0.83 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.71 | 1.50 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.03 | 4.33 | 28.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.91 | 1.83 | 27.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.93 | 2.83 | 27.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.67 | 0.33 | 27.67 |
November | 0.33 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
December | 4.83 | 15.21 | 2.00 | 15.11 | 0.00 | 15.11 | 0.00 | 15.11 |
Annual Sum or Average | 23.83 | 15.30 | 5.33 | 15.32 | 23.50 | 20.93 | 11.67 | 22.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 0.00 | 15.00 |
Maximum of Months | 15.00 | 16.93 | 3.33 | 16.93 | 8.33 | 28.03 | 4.33 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 40.50 | 16.87 | 22.33 | 17.40 | 0.00 | 17.40 | 0.00 | 17.40 |
February | 8.17 | 16.04 | 2.83 | 16.32 | 0.00 | 16.32 | 0.00 | 16.32 |
March | 4.83 | 16.89 | 2.00 | 17.64 | 0.00 | 17.64 | 0.00 | 17.64 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.36 | 0.67 | 27.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.37 | 1.17 | 27.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.40 | 2.00 | 27.40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4.17 | 16.56 | 1.17 | 17.27 | 0.00 | 17.27 | 0.00 | 17.27 |
December | 11.00 | 16.26 | 5.83 | 16.56 | 0.00 | 16.56 | 0.00 | 16.56 |
Annual Sum or Average | 68.67 | 16.66 | 34.17 | 17.16 | 5.00 | 17.63 | 3.83 | 17.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 40.50 | 16.89 | 22.33 | 17.64 | 2.17 | 27.40 | 2.00 | 27.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.33 | 14.84 | 3.83 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
February | 6.50 | 15.29 | 0.67 | 15.25 | 0.00 | 15.25 | 0.00 | 15.25 |
March | 2.67 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.39 | 0.50 | 27.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.94 | 5.50 | 27.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.96 | 11.50 | 27.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.02 | 4.17 | 28.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.84 | 6.00 | 27.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.67 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
December | 7.33 | 14.98 | 2.17 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
Annual Sum or Average | 39.50 | 14.97 | 6.67 | 14.96 | 29.67 | 20.03 | 27.67 | 22.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.33 | 15.29 | 3.83 | 15.25 | 12.17 | 28.02 | 11.50 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.17 | 15.10 | 2.67 | 15.16 | 0.17 | 15.27 | 0.17 | 15.37 |
February | 2.33 | 15.61 | 0.50 | 15.49 | 1.33 | 19.47 | 1.33 | 21.53 |
March | 1.83 | 15.14 | 0.00 | 15.14 | 0.33 | 17.01 | 0.33 | 18.39 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.54 | 0.83 | 27.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.36 | 1.33 | 27.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.52 | 3.50 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.74 | 8.00 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.93 | 4.00 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.06 | 7.00 | 28.10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.02 | 2.83 | 28.02 |
November | 1.17 | 15.35 | 0.00 | 15.35 | 1.33 | 21.75 | 1.33 | 23.70 |
December | 5.50 | 15.06 | 1.67 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
Annual Sum or Average | 27.00 | 15.15 | 4.83 | 15.15 | 33.33 | 21.63 | 30.67 | 23.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 | 0.00 | 14.97 |
Maximum of Months | 16.17 | 15.61 | 2.67 | 15.49 | 8.83 | 28.06 | 8.00 | 28.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.50 | 14.85 | 4.17 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
February | 6.17 | 15.32 | 1.00 | 15.25 | 0.00 | 15.25 | 0.00 | 15.25 |
March | 2.50 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.01 | 0.67 | 28.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.95 | 1.67 | 27.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.00 | 2.50 | 27.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 28.32 | 5.50 | 28.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.05 | 3.33 | 28.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.10 | 3.33 | 28.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.70 | 0.50 | 27.75 |
November | 2.50 | 15.05 | 0.00 | 15.05 | 0.00 | 15.05 | 0.00 | 15.05 |
December | 8.17 | 14.96 | 3.00 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
Annual Sum or Average | 39.83 | 14.97 | 8.17 | 14.94 | 32.83 | 20.29 | 17.50 | 21.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.86 | 0.00 | 14.86 |
Maximum of Months | 20.50 | 15.32 | 4.17 | 15.25 | 10.67 | 28.32 | 5.50 | 28.34 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.45 | 97.83 | 22.18 | 97.83 | 21.99 |
February | 451.33 | 23.17 | 18.83 | 23.07 | 18.83 | 22.98 |
March | 503.33 | 23.69 | 2.17 | 23.68 | 2.17 | 23.66 |
April | 370.33 | 23.97 | 0.00 | 23.97 | 0.00 | 23.97 |
May | 213.67 | 23.97 | 71.33 | 24.39 | 0.00 | 24.39 |
June | 4.83 | 24.03 | 216.83 | 24.68 | 0.00 | 24.68 |
July | 1.17 | 26.73 | 348.67 | 24.62 | 1.17 | 24.63 |
August | 0.00 | 0.00 | 239.67 | 24.83 | 0.00 | 24.83 |
September | 27.00 | 24.02 | 185.33 | 24.77 | 0.00 | 24.77 |
October | 199.50 | 24.03 | 27.50 | 24.25 | 0.00 | 24.25 |
November | 408.83 | 23.80 | 0.00 | 23.80 | 0.00 | 23.80 |
December | 497.00 | 23.10 | 28.50 | 22.97 | 28.50 | 22.86 |
Annual Sum or Average | 3179.00 | 23.42 | 1236.67 | 23.68 | 148.50 | 23.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.18 | 0.00 | 21.99 |
Maximum of Months | 503.33 | 26.73 | 348.67 | 24.83 | 97.83 | 24.83 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.92 | 343.00 | 20.78 | 343.00 | 20.71 |
February | 454.00 | 21.65 | 158.83 | 21.40 | 158.83 | 21.26 |
March | 514.00 | 22.48 | 60.33 | 22.28 | 60.33 | 22.12 |
April | 470.83 | 23.31 | 0.00 | 23.31 | 0.00 | 23.31 |
May | 340.00 | 23.44 | 46.67 | 23.62 | 4.17 | 23.59 |
June | 83.50 | 23.83 | 149.67 | 24.22 | 0.00 | 24.22 |
July | 20.67 | 23.97 | 266.50 | 24.50 | 0.00 | 24.50 |
August | 23.50 | 23.81 | 152.17 | 24.62 | 0.00 | 24.62 |
September | 179.00 | 23.73 | 130.00 | 24.14 | 2.00 | 24.14 |
October | 444.17 | 23.49 | 0.50 | 23.49 | 0.50 | 23.48 |
November | 489.00 | 22.55 | 60.00 | 22.36 | 60.00 | 22.20 |
December | 497.00 | 21.34 | 226.50 | 21.07 | 226.50 | 20.93 |
Annual Sum or Average | 4017.67 | 22.45 | 1594.17 | 22.45 | 855.33 | 22.21 |
Minimum of Months | 20.67 | 20.92 | 0.00 | 20.78 | 0.00 | 20.71 |
Maximum of Months | 514.00 | 23.97 | 343.00 | 24.62 | 343.00 | 24.62 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.35 | 452.83 | 20.29 | 452.83 | 20.27 |
February | 454.00 | 20.94 | 316.00 | 20.74 | 316.00 | 20.66 |
March | 514.00 | 21.63 | 179.33 | 21.31 | 179.33 | 21.12 |
April | 475.67 | 22.65 | 51.83 | 22.45 | 51.83 | 22.28 |
May | 368.17 | 23.02 | 55.67 | 22.93 | 34.67 | 22.76 |
June | 133.33 | 23.60 | 138.33 | 24.00 | 0.00 | 24.00 |
July | 41.33 | 23.71 | 252.67 | 24.36 | 0.00 | 24.36 |
August | 79.83 | 23.65 | 136.83 | 24.24 | 0.00 | 24.24 |
September | 248.50 | 23.25 | 107.33 | 23.67 | 3.67 | 23.67 |
October | 489.67 | 22.75 | 32.00 | 22.60 | 32.00 | 22.48 |
November | 489.00 | 21.52 | 210.17 | 21.20 | 210.17 | 21.03 |
December | 497.00 | 20.54 | 383.00 | 20.38 | 383.00 | 20.32 |
Annual Sum or Average | 4292.50 | 21.84 | 2316.00 | 21.73 | 1663.50 | 21.45 |
Minimum of Months | 41.33 | 20.35 | 32.00 | 20.29 | 0.00 | 20.27 |
Maximum of Months | 514.00 | 23.71 | 452.83 | 24.36 | 452.83 | 24.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.68 | 497.67 | 19.68 | 497.67 | 19.68 |
February | 454.00 | 20.14 | 423.67 | 20.08 | 423.67 | 20.07 |
March | 514.00 | 20.62 | 351.33 | 20.41 | 351.33 | 20.33 |
April | 477.17 | 21.63 | 158.50 | 21.27 | 158.50 | 21.05 |
May | 391.83 | 22.31 | 112.67 | 22.12 | 81.17 | 21.85 |
June | 155.33 | 23.13 | 169.33 | 23.76 | 0.67 | 23.75 |
July | 65.33 | 23.73 | 279.67 | 24.35 | 5.50 | 24.39 |
August | 140.33 | 23.26 | 159.00 | 23.89 | 3.50 | 23.91 |
September | 306.50 | 22.48 | 127.00 | 22.85 | 37.33 | 22.75 |
October | 498.00 | 21.63 | 146.33 | 21.29 | 146.33 | 21.09 |
November | 489.00 | 20.40 | 352.33 | 20.21 | 352.33 | 20.13 |
December | 497.00 | 19.83 | 481.00 | 19.81 | 481.00 | 19.80 |
Annual Sum or Average | 4490.50 | 21.06 | 3258.50 | 21.02 | 2539.00 | 20.77 |
Minimum of Months | 65.33 | 19.68 | 112.67 | 19.68 | 0.67 | 19.68 |
Maximum of Months | 514.00 | 23.73 | 497.67 | 24.35 | 497.67 | 24.39 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.87 | 481.17 | 19.85 | 481.17 | 19.84 |
February | 454.00 | 20.53 | 344.50 | 20.32 | 344.50 | 20.23 |
March | 504.67 | 21.14 | 269.33 | 20.77 | 269.33 | 20.58 |
April | 385.50 | 21.86 | 123.50 | 21.57 | 106.67 | 21.30 |
May | 286.17 | 22.30 | 133.33 | 22.38 | 59.17 | 22.08 |
June | 113.50 | 23.78 | 270.00 | 24.32 | 19.33 | 24.44 |
July | 66.00 | 25.45 | 384.67 | 24.72 | 36.00 | 24.90 |
August | 89.83 | 23.66 | 299.67 | 24.28 | 12.67 | 24.36 |
September | 229.17 | 22.88 | 188.50 | 23.52 | 42.17 | 23.54 |
October | 444.83 | 22.05 | 100.00 | 21.70 | 98.33 | 21.45 |
November | 488.17 | 20.78 | 303.83 | 20.49 | 303.83 | 20.35 |
December | 497.00 | 19.93 | 465.33 | 19.88 | 465.33 | 19.87 |
Annual Sum or Average | 4060.83 | 21.27 | 3363.83 | 21.43 | 2238.50 | 21.15 |
Minimum of Months | 66.00 | 19.87 | 100.00 | 19.85 | 12.67 | 19.84 |
Maximum of Months | 504.67 | 25.45 | 481.17 | 24.72 | 481.17 | 24.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 492.67 | 20.47 | 397.33 | 20.23 | 396.17 | 20.13 |
February | 412.33 | 21.05 | 274.33 | 20.76 | 261.17 | 20.57 |
March | 437.17 | 21.15 | 267.00 | 20.91 | 242.67 | 20.71 |
April | 370.17 | 21.75 | 165.50 | 21.62 | 124.17 | 21.35 |
May | 311.83 | 22.19 | 155.67 | 22.32 | 73.83 | 22.03 |
June | 162.17 | 23.24 | 206.83 | 23.93 | 13.33 | 24.02 |
July | 89.67 | 24.37 | 319.67 | 24.51 | 27.33 | 24.67 |
August | 126.17 | 23.54 | 272.50 | 24.16 | 14.00 | 24.25 |
September | 214.17 | 22.82 | 221.67 | 23.57 | 42.50 | 23.60 |
October | 349.67 | 22.03 | 164.00 | 22.11 | 90.33 | 21.87 |
November | 420.00 | 21.22 | 243.17 | 20.95 | 221.17 | 20.74 |
December | 473.83 | 20.47 | 356.50 | 20.19 | 356.50 | 20.08 |
Annual Sum or Average | 3859.83 | 21.53 | 3044.17 | 21.69 | 1863.17 | 21.40 |
Minimum of Months | 89.67 | 20.47 | 155.67 | 20.19 | 13.33 | 20.08 |
Maximum of Months | 492.67 | 24.37 | 397.33 | 24.51 | 396.17 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.89 | 475.17 | 19.84 | 475.17 | 19.82 |
February | 445.00 | 20.43 | 358.17 | 20.25 | 356.50 | 20.17 |
March | 487.33 | 20.86 | 303.33 | 20.58 | 300.33 | 20.45 |
April | 408.50 | 21.71 | 165.17 | 21.49 | 138.67 | 21.25 |
May | 310.17 | 22.28 | 157.17 | 22.41 | 74.83 | 22.18 |
June | 153.83 | 23.28 | 243.00 | 23.99 | 12.83 | 24.06 |
July | 85.50 | 24.40 | 332.50 | 24.52 | 26.17 | 24.67 |
August | 128.50 | 23.48 | 247.00 | 24.13 | 13.33 | 24.21 |
September | 252.17 | 22.56 | 180.83 | 23.20 | 43.17 | 23.16 |
October | 429.33 | 21.70 | 147.67 | 21.46 | 128.50 | 21.22 |
November | 476.50 | 20.72 | 307.33 | 20.44 | 307.33 | 20.31 |
December | 497.00 | 19.99 | 445.17 | 19.89 | 445.17 | 19.85 |
Annual Sum or Average | 4175.83 | 21.20 | 3362.50 | 21.32 | 2322.00 | 21.05 |
Minimum of Months | 85.50 | 19.89 | 147.67 | 19.84 | 12.83 | 19.82 |
Maximum of Months | 502.00 | 24.40 | 475.17 | 24.52 | 475.17 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.93 | 501.00 | 19.93 | 501.00 | 19.93 |
February | 454.00 | 20.37 | 433.00 | 20.34 | 433.00 | 20.33 |
March | 514.00 | 20.67 | 383.17 | 20.56 | 383.17 | 20.51 |
April | 485.00 | 21.38 | 169.50 | 21.15 | 169.50 | 21.02 |
May | 454.17 | 22.38 | 75.33 | 22.19 | 65.50 | 22.01 |
June | 224.33 | 23.49 | 98.00 | 23.71 | 0.00 | 23.71 |
July | 52.83 | 23.75 | 227.17 | 24.28 | 0.00 | 24.28 |
August | 134.50 | 23.58 | 107.17 | 23.96 | 0.00 | 23.96 |
September | 292.67 | 22.98 | 90.50 | 23.38 | 3.83 | 23.38 |
October | 502.00 | 22.42 | 30.00 | 22.33 | 30.00 | 22.24 |
November | 489.00 | 21.07 | 263.50 | 20.84 | 263.50 | 20.73 |
December | 497.00 | 20.18 | 468.17 | 20.15 | 468.17 | 20.14 |
Annual Sum or Average | 4601.50 | 21.39 | 2846.50 | 21.25 | 2317.67 | 21.01 |
Minimum of Months | 52.83 | 19.93 | 30.00 | 19.93 | 0.00 | 19.93 |
Maximum of Months | 514.00 | 23.75 | 501.00 | 24.28 | 501.00 | 24.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.15 | 482.17 | 20.13 | 482.17 | 20.12 |
February | 454.00 | 20.83 | 331.00 | 20.62 | 331.00 | 20.54 |
March | 513.33 | 21.34 | 251.83 | 21.02 | 251.83 | 20.86 |
April | 433.83 | 22.21 | 75.00 | 21.98 | 70.17 | 21.79 |
May | 326.00 | 22.71 | 85.17 | 22.77 | 34.83 | 22.59 |
June | 91.50 | 23.73 | 260.33 | 24.35 | 6.50 | 24.40 |
July | 34.50 | 26.04 | 405.33 | 24.74 | 23.83 | 24.86 |
August | 43.50 | 24.17 | 320.50 | 24.47 | 7.67 | 24.53 |
September | 174.50 | 23.52 | 184.33 | 24.16 | 17.33 | 24.26 |
October | 399.83 | 22.91 | 15.17 | 22.89 | 9.67 | 22.84 |
November | 486.83 | 21.64 | 183.00 | 21.32 | 183.00 | 21.14 |
December | 497.00 | 20.35 | 424.17 | 20.26 | 424.17 | 20.23 |
Annual Sum or Average | 3956.83 | 21.63 | 3018.00 | 21.81 | 1842.17 | 21.52 |
Minimum of Months | 34.50 | 20.15 | 15.17 | 20.13 | 6.50 | 20.12 |
Maximum of Months | 513.33 | 26.04 | 482.17 | 24.74 | 482.17 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.17 | 19.88 | 405.67 | 19.66 | 404.17 | 19.57 |
February | 417.50 | 20.67 | 266.83 | 20.43 | 255.17 | 20.26 |
March | 472.17 | 21.02 | 217.17 | 20.72 | 213.33 | 20.55 |
April | 432.67 | 21.74 | 115.00 | 21.55 | 102.83 | 21.34 |
May | 378.67 | 21.97 | 108.00 | 21.98 | 67.50 | 21.76 |
June | 199.33 | 22.75 | 161.00 | 23.53 | 0.00 | 23.53 |
July | 62.67 | 23.50 | 318.00 | 24.39 | 8.67 | 24.45 |
August | 91.67 | 22.96 | 282.83 | 24.17 | 6.17 | 24.22 |
September | 182.17 | 22.98 | 225.00 | 23.98 | 22.83 | 24.09 |
October | 306.50 | 22.55 | 102.00 | 22.94 | 19.00 | 22.88 |
November | 409.00 | 21.59 | 153.67 | 21.38 | 130.50 | 21.13 |
December | 488.00 | 20.46 | 325.83 | 20.15 | 325.83 | 20.01 |
Annual Sum or Average | 3938.50 | 21.38 | 2681.00 | 21.59 | 1556.00 | 21.27 |
Minimum of Months | 62.67 | 19.88 | 102.00 | 19.66 | 0.00 | 19.57 |
Maximum of Months | 498.17 | 23.50 | 405.67 | 24.39 | 404.17 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.13 | 483.83 | 20.10 | 483.83 | 20.09 |
February | 450.17 | 20.71 | 349.67 | 20.54 | 349.67 | 20.47 |
March | 504.50 | 21.10 | 280.67 | 20.84 | 280.67 | 20.72 |
April | 450.50 | 22.03 | 106.83 | 21.81 | 97.67 | 21.62 |
May | 327.17 | 22.68 | 95.33 | 22.78 | 40.17 | 22.60 |
June | 132.33 | 23.61 | 208.17 | 24.14 | 5.00 | 24.18 |
July | 36.00 | 25.06 | 367.83 | 24.60 | 13.83 | 24.68 |
August | 70.83 | 23.81 | 255.83 | 24.39 | 5.33 | 24.43 |
September | 202.50 | 23.36 | 178.17 | 24.02 | 12.67 | 24.10 |
October | 409.83 | 22.77 | 30.83 | 22.78 | 15.83 | 22.71 |
November | 477.33 | 21.55 | 194.17 | 21.23 | 194.17 | 21.05 |
December | 497.00 | 20.36 | 417.50 | 20.24 | 417.50 | 20.20 |
Annual Sum or Average | 4060.17 | 21.57 | 2968.83 | 21.69 | 1916.33 | 21.41 |
Minimum of Months | 36.00 | 20.13 | 30.83 | 20.10 | 5.00 | 20.09 |
Maximum of Months | 504.50 | 25.06 | 483.83 | 24.60 | 483.83 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.94 | 493.17 | 19.93 | 493.17 | 19.93 |
February | 454.00 | 20.46 | 385.33 | 20.36 | 385.33 | 20.33 |
March | 514.00 | 21.02 | 267.17 | 20.77 | 267.17 | 20.64 |
April | 479.83 | 22.17 | 74.50 | 21.93 | 74.50 | 21.75 |
May | 367.67 | 22.68 | 73.17 | 22.63 | 39.67 | 22.43 |
June | 117.17 | 23.53 | 177.67 | 24.01 | 0.00 | 24.01 |
July | 29.33 | 23.92 | 302.00 | 24.45 | 1.50 | 24.46 |
August | 92.33 | 23.55 | 163.67 | 24.17 | 0.67 | 24.18 |
September | 264.50 | 22.91 | 109.00 | 23.40 | 9.00 | 23.39 |
October | 493.83 | 22.31 | 56.50 | 22.11 | 56.50 | 21.96 |
November | 489.00 | 20.95 | 271.00 | 20.68 | 271.00 | 20.54 |
December | 497.00 | 20.06 | 458.17 | 20.02 | 458.17 | 20.00 |
Annual Sum or Average | 4300.67 | 21.39 | 2831.33 | 21.37 | 2056.67 | 21.09 |
Minimum of Months | 29.33 | 19.94 | 56.50 | 19.93 | 0.00 | 19.93 |
Maximum of Months | 514.00 | 23.92 | 493.17 | 24.45 | 493.17 | 24.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.94 | 402.17 | 19.90 | 402.17 | 19.89 |
February | 381.33 | 20.75 | 269.50 | 20.51 | 269.50 | 20.41 |
March | 424.17 | 21.40 | 184.50 | 21.03 | 184.50 | 20.84 |
April | 328.17 | 22.29 | 71.00 | 22.18 | 49.67 | 21.97 |
May | 236.17 | 22.62 | 98.67 | 22.85 | 29.83 | 22.62 |
June | 84.50 | 24.28 | 227.83 | 24.57 | 18.33 | 24.71 |
July | 48.00 | 26.16 | 329.50 | 24.94 | 34.50 | 25.12 |
August | 60.50 | 24.27 | 242.17 | 24.57 | 13.50 | 24.68 |
September | 178.67 | 23.34 | 152.50 | 24.02 | 22.50 | 24.15 |
October | 360.83 | 22.48 | 45.17 | 22.33 | 39.17 | 22.15 |
November | 415.67 | 21.27 | 203.00 | 20.92 | 203.00 | 20.75 |
December | 422.00 | 20.06 | 365.17 | 19.96 | 365.17 | 19.92 |
Annual Sum or Average | 3367.00 | 21.54 | 2591.17 | 21.71 | 1631.83 | 21.43 |
Minimum of Months | 48.00 | 19.94 | 45.17 | 19.90 | 13.50 | 19.89 |
Maximum of Months | 427.00 | 26.16 | 402.17 | 24.94 | 402.17 | 25.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 488.33 | 20.77 | 364.00 | 20.51 | 360.83 | 20.39 |
February | 396.17 | 21.39 | 237.00 | 21.13 | 218.67 | 20.93 |
March | 427.00 | 21.61 | 195.83 | 21.40 | 165.67 | 21.17 |
April | 358.17 | 22.30 | 96.00 | 22.33 | 53.83 | 22.14 |
May | 287.00 | 22.59 | 125.00 | 22.82 | 41.33 | 22.60 |
June | 126.17 | 23.62 | 215.83 | 24.17 | 8.17 | 24.24 |
July | 57.17 | 24.89 | 348.83 | 24.61 | 21.67 | 24.73 |
August | 83.50 | 23.95 | 289.50 | 24.38 | 10.83 | 24.46 |
September | 181.00 | 23.40 | 229.33 | 24.10 | 23.67 | 24.24 |
October | 313.67 | 22.66 | 121.33 | 22.95 | 33.00 | 22.87 |
November | 402.00 | 21.78 | 193.33 | 21.59 | 156.50 | 21.34 |
December | 461.83 | 20.84 | 309.17 | 20.51 | 309.17 | 20.37 |
Annual Sum or Average | 3582.00 | 21.90 | 2725.17 | 22.14 | 1403.33 | 21.85 |
Minimum of Months | 57.17 | 20.77 | 96.00 | 20.51 | 8.17 | 20.37 |
Maximum of Months | 488.33 | 24.89 | 364.00 | 24.61 | 360.83 | 24.73 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.11 | 465.83 | 20.05 | 465.83 | 20.03 |
February | 443.00 | 20.77 | 319.50 | 20.55 | 316.50 | 20.45 |
March | 484.00 | 21.28 | 222.67 | 20.97 | 219.33 | 20.80 |
April | 400.50 | 22.27 | 94.17 | 22.17 | 67.67 | 21.99 |
May | 275.33 | 22.65 | 130.83 | 22.90 | 42.67 | 22.74 |
June | 110.67 | 23.68 | 252.50 | 24.21 | 9.33 | 24.28 |
July | 54.83 | 25.12 | 364.17 | 24.64 | 24.00 | 24.77 |
August | 86.00 | 23.88 | 260.00 | 24.37 | 10.17 | 24.45 |
September | 218.00 | 23.10 | 176.33 | 23.81 | 18.33 | 23.90 |
October | 412.00 | 22.38 | 68.67 | 22.31 | 46.67 | 22.15 |
November | 469.00 | 21.27 | 223.17 | 20.92 | 223.17 | 20.74 |
December | 497.00 | 20.26 | 407.00 | 20.11 | 407.00 | 20.05 |
Annual Sum or Average | 3952.33 | 21.53 | 2984.83 | 21.69 | 1850.67 | 21.41 |
Minimum of Months | 54.83 | 20.11 | 68.67 | 20.05 | 9.33 | 20.03 |
Maximum of Months | 502.00 | 25.12 | 465.83 | 24.64 | 465.83 | 24.77 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.44833 | 14.48974 | -0.3074 | 8.35738 |
February | 454.00000 | 23.17790 | 15.99069 | -0.1049 | 6.19281 |
March | 514.00000 | 23.70875 | 17.08535 | 0.05640 | 5.61494 |
April | 485.00000 | 24.11386 | 20.36832 | 0.20573 | 6.05571 |
May | 508.00000 | 24.31308 | 23.14444 | -0.5949 | 13.29836 |
June | 496.00000 | 24.34985 | 30.68442 | -0.4568 | 9.78672 |
July | 497.00000 | 24.45563 | 34.38887 | -0.3790 | 8.60516 |
August | 514.00000 | 24.40569 | 30.51300 | -0.4243 | 9.25641 |
September | 485.00000 | 24.40854 | 30.19145 | -0.4576 | 10.04946 |
October | 502.00000 | 24.27978 | 22.55766 | 0.28257 | 6.82652 |
November | 489.00000 | 23.92412 | 18.39668 | 0.12440 | 5.82965 |
December | 497.00000 | 23.10044 | 15.53722 | -0.1243 | 6.41200 |
Annual Sum or Average | 5943.00000 | 23.89488 | 22.82192 | -0.1833 | 8.04522 |
Minimum of Months | 454.00000 | 22.44833 | 14.48974 | -0.5949 | 5.61494 |
Maximum of Months | 514.00000 | 24.45563 | 34.38887 | 0.28257 | 13.29836 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.91753 | 15.24084 | -0.6609 | 15.35339 |
February | 454.00000 | 21.65405 | 17.57949 | -0.4484 | 10.63415 |
March | 514.00000 | 22.48334 | 19.06367 | -0.2274 | 7.63362 |
April | 485.00000 | 23.35251 | 22.05511 | 0.02260 | 5.80910 |
May | 508.00000 | 23.79087 | 24.63350 | -0.7849 | 19.82987 |
June | 496.00000 | 24.16624 | 31.75211 | -0.5387 | 11.47411 |
July | 497.00000 | 24.31543 | 35.36032 | -0.4443 | 9.56623 |
August | 514.00000 | 24.26327 | 31.47800 | -0.4967 | 10.53480 |
September | 485.00000 | 24.12980 | 31.44856 | -0.5821 | 13.07530 |
October | 502.00000 | 23.58658 | 24.39019 | 0.10036 | 5.76455 |
November | 489.00000 | 22.55033 | 20.61737 | -0.2024 | 7.43595 |
December | 497.00000 | 21.33873 | 17.25674 | -0.5290 | 12.55053 |
Annual Sum or Average | 5943.00000 | 23.05538 | 24.28050 | -0.4000 | 10.82274 |
Minimum of Months | 454.00000 | 20.91753 | 15.24084 | -0.7849 | 5.76455 |
Maximum of Months | 514.00000 | 24.31543 | 35.36032 | 0.10036 | 19.82987 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.34959 | 15.31632 | -0.8338 | 21.47995 |
February | 454.00000 | 20.93574 | 18.01890 | -0.6457 | 15.61487 |
March | 514.00000 | 21.63117 | 19.72987 | -0.4431 | 11.33064 |
April | 485.00000 | 22.67177 | 22.88168 | -0.1445 | 7.16753 |
May | 508.00000 | 23.38933 | 25.03418 | -0.9273 | 25.85760 |
June | 496.00000 | 24.04134 | 31.77026 | -0.5829 | 12.88244 |
July | 497.00000 | 24.25580 | 35.14110 | -0.4632 | 10.03661 |
August | 514.00000 | 24.16407 | 31.41502 | -0.5361 | 11.58929 |
September | 485.00000 | 23.78322 | 32.06271 | -0.7123 | 17.81112 |
October | 502.00000 | 22.77608 | 25.69905 | -0.1030 | 6.67503 |
November | 489.00000 | 21.52342 | 21.43765 | -0.4651 | 11.82857 |
December | 497.00000 | 20.54443 | 17.49877 | -0.7523 | 19.24032 |
Annual Sum or Average | 5943.00000 | 22.51729 | 24.70591 | -0.5509 | 14.29894 |
Minimum of Months | 454.00000 | 20.34959 | 15.31632 | -0.9273 | 6.67503 |
Maximum of Months | 514.00000 | 24.25580 | 35.14110 | -0.1030 | 25.85760 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.68472 | 15.13833 | -1.0786 | 31.71756 |
February | 454.00000 | 20.13871 | 18.64340 | -0.8905 | 23.96440 |
March | 514.00000 | 20.62339 | 20.77584 | -0.7044 | 18.00235 |
April | 485.00000 | 21.67246 | 24.60726 | -0.3768 | 11.00114 |
May | 508.00000 | 22.75519 | 26.75723 | -1.1169 | 34.49704 |
June | 496.00000 | 23.87160 | 32.44791 | -0.6090 | 14.72563 |
July | 497.00000 | 24.23291 | 35.26863 | -0.4347 | 10.35148 |
August | 514.00000 | 23.96681 | 32.21359 | -0.5816 | 13.85618 |
September | 485.00000 | 23.16502 | 33.91099 | -0.9098 | 27.13730 |
October | 502.00000 | 21.64671 | 27.72565 | -0.3687 | 10.38466 |
November | 489.00000 | 20.40106 | 22.69581 | -0.7574 | 19.88063 |
December | 497.00000 | 19.83243 | 18.02312 | -0.9945 | 28.25971 |
Annual Sum or Average | 5943.00000 | 21.84645 | 25.72284 | -0.7347 | 20.29739 |
Minimum of Months | 454.00000 | 19.68472 | 15.13833 | -1.1169 | 10.35148 |
Maximum of Months | 514.00000 | 24.23291 | 35.26863 | -0.3687 | 34.49704 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.87132 | 15.85227 | -1.0131 | 28.91385 |
February | 454.00000 | 20.53435 | 19.08334 | -0.7676 | 20.61343 |
March | 514.00000 | 21.19496 | 20.79327 | -0.5435 | 15.32897 |
April | 485.00000 | 22.33492 | 23.57896 | -0.1862 | 9.94042 |
May | 508.00000 | 23.14897 | 25.80955 | -0.9232 | 27.41222 |
June | 496.00000 | 24.15333 | 31.53085 | -0.4129 | 11.73493 |
July | 497.00000 | 24.44667 | 34.50754 | -0.2351 | 8.71043 |
August | 514.00000 | 24.17641 | 31.34728 | -0.3962 | 10.90079 |
September | 485.00000 | 23.62087 | 32.85733 | -0.6941 | 20.72637 |
October | 502.00000 | 22.28292 | 27.02746 | -0.1980 | 9.09401 |
November | 489.00000 | 20.78895 | 23.06836 | -0.6492 | 17.15935 |
December | 497.00000 | 19.93388 | 18.73111 | -0.9487 | 26.56129 |
Annual Sum or Average | 5943.00000 | 22.22045 | 25.38312 | -0.5798 | 17.24059 |
Minimum of Months | 454.00000 | 19.87132 | 15.85227 | -1.0131 | 8.71043 |
Maximum of Months | 514.00000 | 24.44667 | 34.50754 | -0.1862 | 28.91385 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.54810 | 14.71451 | -0.8136 | 23.74987 |
February | 454.00000 | 21.36380 | 17.15400 | -0.5295 | 17.19431 |
March | 514.00000 | 21.59271 | 18.93296 | -0.4234 | 14.38369 |
April | 485.00000 | 22.36087 | 22.80352 | -0.1786 | 10.51177 |
May | 508.00000 | 23.01101 | 25.58954 | -0.9834 | 30.47800 |
June | 496.00000 | 23.90291 | 32.00554 | -0.5509 | 14.82567 |
July | 497.00000 | 24.27765 | 34.86746 | -0.3502 | 10.27316 |
August | 514.00000 | 24.08893 | 31.34382 | -0.4350 | 12.08427 |
September | 485.00000 | 23.65001 | 32.09977 | -0.6353 | 20.47124 |
October | 502.00000 | 22.70562 | 24.87895 | -0.0557 | 9.83315 |
November | 489.00000 | 21.64266 | 20.61139 | -0.4126 | 14.19382 |
December | 497.00000 | 20.63178 | 17.18357 | -0.7419 | 21.80761 |
Annual Sum or Average | 5943.00000 | 22.48980 | 24.39118 | -0.5099 | 16.66119 |
Minimum of Months | 454.00000 | 20.54810 | 14.71451 | -0.9834 | 9.83315 |
Maximum of Months | 514.00000 | 24.27765 | 34.86746 | -0.0557 | 30.47800 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.88563 | 15.72635 | -1.0190 | 29.38369 |
February | 454.00000 | 20.51246 | 18.87762 | -0.7791 | 21.64584 |
March | 514.00000 | 21.02560 | 20.80194 | -0.5896 | 16.50186 |
April | 485.00000 | 22.10393 | 24.24852 | -0.2456 | 10.76436 |
May | 508.00000 | 23.03923 | 26.31988 | -0.9590 | 29.94107 |
June | 496.00000 | 23.92864 | 32.39428 | -0.5141 | 14.18908 |
July | 497.00000 | 24.29782 | 35.18302 | -0.3272 | 10.21944 |
August | 514.00000 | 24.05969 | 31.99744 | -0.4671 | 12.57472 |
September | 485.00000 | 23.40629 | 33.49281 | -0.7698 | 23.99836 |
October | 502.00000 | 22.06906 | 27.23764 | -0.2472 | 10.09647 |
November | 489.00000 | 20.80812 | 22.80172 | -0.6462 | 17.75657 |
December | 497.00000 | 19.98843 | 18.62495 | -0.9416 | 26.65407 |
Annual Sum or Average | 5943.00000 | 22.10637 | 25.67936 | -0.6249 | 18.62838 |
Minimum of Months | 454.00000 | 19.88563 | 15.72635 | -1.0190 | 10.09647 |
Maximum of Months | 514.00000 | 24.29782 | 35.18302 | -0.2456 | 29.94107 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.93002 | 15.55016 | -0.9942 | 27.65425 |
February | 454.00000 | 20.36735 | 18.90725 | -0.8242 | 20.64629 |
March | 514.00000 | 20.67102 | 21.34730 | -0.6915 | 16.35417 |
April | 485.00000 | 21.38081 | 25.87995 | -0.4533 | 10.47181 |
May | 508.00000 | 22.57871 | 27.98109 | -1.2008 | 37.58709 |
June | 496.00000 | 23.84093 | 33.12479 | -0.6658 | 15.29588 |
July | 497.00000 | 24.19399 | 35.63423 | -0.4861 | 10.46577 |
August | 514.00000 | 24.04011 | 32.49496 | -0.5849 | 12.89534 |
September | 485.00000 | 23.52038 | 33.65302 | -0.7959 | 20.99649 |
October | 502.00000 | 22.42443 | 27.21535 | -0.1685 | 6.78377 |
November | 489.00000 | 21.07073 | 22.58575 | -0.5597 | 13.30615 |
December | 497.00000 | 20.18408 | 18.35509 | -0.8626 | 22.44049 |
Annual Sum or Average | 5943.00000 | 22.02959 | 26.10163 | -0.6905 | 17.92021 |
Minimum of Months | 454.00000 | 19.93002 | 15.55016 | -1.2008 | 6.78377 |
Maximum of Months | 514.00000 | 24.19399 | 35.63423 | -0.1685 | 37.58709 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.14628 | 16.34196 | -0.9227 | 24.70670 |
February | 454.00000 | 20.82625 | 19.39939 | -0.6863 | 17.24116 |
March | 514.00000 | 21.34398 | 21.51246 | -0.5010 | 12.92104 |
April | 485.00000 | 22.41832 | 24.63015 | -0.1797 | 8.23531 |
May | 508.00000 | 23.26939 | 26.56763 | -0.9155 | 26.17011 |
June | 496.00000 | 24.23046 | 31.66945 | -0.4284 | 10.78752 |
July | 497.00000 | 24.52647 | 34.43287 | -0.2407 | 7.82212 |
August | 514.00000 | 24.31687 | 31.23271 | -0.3672 | 9.16697 |
September | 485.00000 | 24.05625 | 32.23221 | -0.5480 | 14.19585 |
October | 502.00000 | 23.16223 | 26.03333 | 0.02691 | 6.43545 |
November | 489.00000 | 21.65512 | 22.78772 | -0.4096 | 10.95932 |
December | 497.00000 | 20.34620 | 19.10863 | -0.8050 | 20.50463 |
Annual Sum or Average | 5943.00000 | 22.53678 | 25.53032 | -0.4977 | 14.09654 |
Minimum of Months | 454.00000 | 20.14628 | 16.34196 | -0.9227 | 6.43545 |
Maximum of Months | 514.00000 | 24.52647 | 34.43287 | 0.02691 | 26.17011 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.92545 | 13.14424 | -0.8906 | 25.53251 |
February | 454.00000 | 21.00196 | 15.73615 | -0.5596 | 16.78822 |
March | 514.00000 | 21.27424 | 17.86442 | -0.4575 | 12.86584 |
April | 485.00000 | 22.03858 | 22.42155 | -0.2496 | 9.24627 |
May | 508.00000 | 22.59091 | 25.63160 | -1.1228 | 35.48564 |
June | 496.00000 | 23.67286 | 32.35278 | -0.6555 | 16.80370 |
July | 497.00000 | 24.26895 | 34.66058 | -0.3864 | 9.92306 |
August | 514.00000 | 24.10644 | 31.00879 | -0.4387 | 11.41223 |
September | 485.00000 | 23.88856 | 31.25449 | -0.5316 | 15.81857 |
October | 502.00000 | 23.25353 | 23.33974 | 0.11534 | 7.85243 |
November | 489.00000 | 22.07639 | 18.82023 | -0.2464 | 10.58835 |
December | 497.00000 | 20.52709 | 15.53968 | -0.6914 | 19.18135 |
Annual Sum or Average | 5943.00000 | 22.39407 | 23.52908 | -0.5106 | 15.98863 |
Minimum of Months | 454.00000 | 19.92545 | 13.14424 | -1.1228 | 7.85243 |
Maximum of Months | 514.00000 | 24.26895 | 34.66058 | 0.11534 | 35.48564 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.12933 | 16.24521 | -0.9352 | 25.27497 |
February | 454.00000 | 20.74258 | 19.30662 | -0.7082 | 18.02690 |
March | 514.00000 | 21.15068 | 21.54530 | -0.5515 | 13.88204 |
April | 485.00000 | 22.18489 | 25.18635 | -0.2403 | 8.59073 |
May | 508.00000 | 23.27741 | 26.81282 | -0.9148 | 26.79275 |
June | 496.00000 | 24.08370 | 32.35373 | -0.5062 | 12.09288 |
July | 497.00000 | 24.42338 | 34.95695 | -0.3172 | 8.47521 |
August | 514.00000 | 24.24645 | 31.74471 | -0.4256 | 10.20166 |
September | 485.00000 | 23.96296 | 32.62373 | -0.5888 | 15.50016 |
October | 502.00000 | 23.04060 | 26.28093 | -0.0029 | 6.63748 |
November | 489.00000 | 21.60556 | 22.57052 | -0.4193 | 11.26405 |
December | 497.00000 | 20.35775 | 19.03644 | -0.8053 | 20.84634 |
Annual Sum or Average | 5943.00000 | 22.44591 | 25.75843 | -0.5343 | 14.80011 |
Minimum of Months | 454.00000 | 20.12933 | 16.24521 | -0.9352 | 6.63748 |
Maximum of Months | 514.00000 | 24.42338 | 34.95695 | -0.0029 | 26.79275 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.94233 | 15.40090 | -0.9711 | 26.92608 |
February | 454.00000 | 20.45545 | 18.68152 | -0.7723 | 19.32972 |
March | 514.00000 | 21.02434 | 20.58413 | -0.5724 | 13.96718 |
April | 485.00000 | 22.18597 | 24.06623 | -0.2383 | 8.15082 |
May | 508.00000 | 23.12292 | 26.32823 | -0.9826 | 28.70734 |
June | 496.00000 | 24.03901 | 32.23752 | -0.5528 | 12.32659 |
July | 497.00000 | 24.32007 | 35.28456 | -0.4085 | 9.30526 |
August | 514.00000 | 24.12404 | 32.03627 | -0.5273 | 11.74418 |
September | 485.00000 | 23.57308 | 33.20261 | -0.7641 | 20.60367 |
October | 502.00000 | 22.33332 | 26.74893 | -0.1883 | 7.42858 |
November | 489.00000 | 20.95229 | 22.21252 | -0.5869 | 14.67082 |
December | 497.00000 | 20.06480 | 18.22701 | -0.8827 | 23.69273 |
Annual Sum or Average | 5943.00000 | 22.19137 | 25.45594 | -0.6202 | 16.39823 |
Minimum of Months | 454.00000 | 19.94233 | 15.40090 | -0.9826 | 7.42858 |
Maximum of Months | 514.00000 | 24.32007 | 35.28456 | -0.1883 | 28.70734 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.94324 | 15.61550 | -0.9534 | 26.32976 |
February | 385.00000 | 20.78397 | 18.71924 | -0.6749 | 17.56797 |
March | 433.00000 | 21.45650 | 20.16420 | -0.4547 | 12.68625 |
April | 410.00000 | 22.69521 | 22.85942 | -0.0912 | 8.09625 |
May | 430.00000 | 23.39992 | 25.30868 | -0.8401 | 24.19484 |
June | 418.00000 | 24.31998 | 31.16130 | -0.3777 | 10.56638 |
July | 422.00000 | 24.61029 | 34.17603 | -0.2132 | 8.39923 |
August | 433.00000 | 24.34533 | 30.91053 | -0.3669 | 9.92560 |
September | 410.00000 | 23.93279 | 32.05227 | -0.5933 | 16.92624 |
October | 427.00000 | 22.75285 | 25.73060 | -0.0738 | 7.31298 |
November | 417.00000 | 21.27393 | 22.04550 | -0.5027 | 13.34113 |
December | 422.00000 | 20.06102 | 18.44513 | -0.8693 | 23.42585 |
Annual Sum or Average | 5034.00000 | 22.47377 | 24.79104 | -0.5007 | 14.89734 |
Minimum of Months | 385.00000 | 19.94324 | 15.61550 | -0.9534 | 7.31298 |
Maximum of Months | 433.00000 | 24.61029 | 34.17603 | -0.0738 | 26.32976 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.88130 | 14.67522 | -0.6928 | 19.74698 |
February | 454.00000 | 21.78622 | 16.86243 | -0.3944 | 13.83375 |
March | 514.00000 | 22.05129 | 18.55598 | -0.2837 | 11.14674 |
April | 485.00000 | 22.83012 | 22.20833 | -0.0507 | 8.23553 |
May | 508.00000 | 23.34518 | 25.16375 | -0.8597 | 25.16635 |
June | 496.00000 | 24.08671 | 31.77261 | -0.4915 | 12.12682 |
July | 497.00000 | 24.38999 | 34.82582 | -0.3190 | 8.96426 |
August | 514.00000 | 24.23756 | 31.19366 | -0.3855 | 10.08746 |
September | 485.00000 | 23.97829 | 31.49785 | -0.5138 | 15.35652 |
October | 502.00000 | 23.25629 | 23.92174 | 0.09493 | 8.26755 |
November | 489.00000 | 22.24930 | 19.89377 | -0.2357 | 10.98638 |
December | 497.00000 | 21.06766 | 16.97260 | -0.5944 | 17.44780 |
Annual Sum or Average | 5943.00000 | 22.85399 | 24.00543 | -0.3949 | 13.46103 |
Minimum of Months | 454.00000 | 20.88130 | 14.67522 | -0.8597 | 8.23553 |
Maximum of Months | 514.00000 | 24.38999 | 34.82582 | 0.09493 | 25.16635 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.11246 | 16.04700 | -0.9177 | 25.08725 |
February | 454.00000 | 20.85678 | 18.88455 | -0.6570 | 17.42694 |
March | 514.00000 | 21.44070 | 20.52165 | -0.4566 | 12.77558 |
April | 485.00000 | 22.61366 | 23.61280 | -0.1096 | 8.23747 |
May | 508.00000 | 23.38930 | 25.83413 | -0.8312 | 24.47379 |
June | 496.00000 | 24.11029 | 32.11487 | -0.4552 | 11.54588 |
July | 497.00000 | 24.40692 | 35.11944 | -0.2965 | 8.91977 |
August | 514.00000 | 24.21374 | 31.78341 | -0.4153 | 10.50440 |
September | 485.00000 | 23.79133 | 32.76678 | -0.6318 | 17.95009 |
October | 502.00000 | 22.71774 | 26.20967 | -0.0759 | 7.60816 |
November | 489.00000 | 21.37736 | 22.18586 | -0.4744 | 13.14607 |
December | 497.00000 | 20.25903 | 18.82898 | -0.8234 | 22.17661 |
Annual Sum or Average | 5943.00000 | 22.45255 | 25.36249 | -0.5118 | 14.98142 |
Minimum of Months | 454.00000 | 20.11246 | 16.04700 | -0.9177 | 7.60816 |
Maximum of Months | 514.00000 | 24.40692 | 35.11944 | -0.0759 | 25.08725 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.342348E+09 | 93105349.85 | 15.82 | 0.340562E+09 | 1786071.26 | 0.00 | 0.51 | 28-FEB-16:30 | 0.00 | 01-FEB-00:10 | 14372.80 | 28-FEB-16:30 | 14372.80 | 28-FEB-16:30 | 171.89 | 28-FEB-12:02 | 3755.09 | 28-FEB-16:30 | 0.00 |
March | 0.802299E+09 | 0.222753E+09 | 45.06 | 0.800917E+09 | 1381394.60 | 0.00 | 0.46 | 01-MAR-16:20 | 0.00 | 01-MAR-00:10 | 12773.97 | 01-MAR-16:20 | 12773.97 | 01-MAR-16:20 | 354.26 | 22-MAR-17:03 | 3381.74 | 01-MAR-16:20 | 0.00 |
April | 0.345471E+10 | 0.915127E+09 | 126.45 | 0.341901E+10 | 35699041.10 | 0.00 | 0.99 | 06-APR-16:00 | 0.00 | 01-APR-00:10 | 31376.01 | 06-APR-16:00 | 31376.01 | 06-APR-16:00 | 880.91 | 13-APR-17:03 | 7193.74 | 06-APR-16:00 | 0.00 |
May | 0.863717E+10 | 0.223806E+10 | 204.89 | 0.836751E+10 | 0.269655E+09 | 0.00 | 1.00 | 19-MAY-11:40 | 0.00 | 01-MAY-00:10 | 51666.21 | 19-MAY-15:30 | 51666.21 | 19-MAY-15:30 | 5070.13 | 02-MAY-13:00 | 13110.39 | 19-MAY-15:30 | 0.00 |
June | 0.273280E+11 | 0.687609E+10 | 318.91 | 0.260477E+11 | 0.128039E+10 | 0.00 | 1.00 | 05-JUN-12:05 | 0.00 | 01-JUN-00:10 | 64312.12 | 20-JUN-16:00 | 63298.88 | 29-JUN-15:10 | 13180.29 | 22-JUN-06:03 | 17957.14 | 29-JUN-15:10 | 0.00 |
July | 0.472985E+11 | 0.122630E+11 | 403.96 | 0.455731E+11 | 0.172542E+10 | 0.00 | 1.00 | 01-JUL-12:00 | 0.00 | 01-JUL-00:10 | 80411.29 | 17-JUL-16:00 | 80411.29 | 17-JUL-16:00 | 22724.05 | 19-JUL-06:03 | 26685.70 | 17-JUL-16:00 | 0.00 |
August | 0.404883E+11 | 0.103572E+11 | 365.12 | 0.400165E+11 | 0.471740E+09 | 0.00 | 1.00 | 01-AUG-10:40 | 0.00 | 01-AUG-00:10 | 73437.29 | 07-AUG-16:00 | 73437.29 | 07-AUG-16:00 | 5217.83 | 08-AUG-16:10 | 20935.18 | 07-AUG-16:00 | 0.00 |
September | 0.208345E+11 | 0.528147E+10 | 293.92 | 0.190333E+11 | 0.180123E+10 | 0.00 | 1.00 | 01-SEP-09:20 | 0.00 | 01-SEP-00:10 | 103009.41 | 07-SEP-14:55 | 61048.58 | 04-SEP-16:51 | 48649.79 | 07-SEP-14:55 | 23726.03 | 07-SEP-14:55 | 0.00 |
October | 0.688767E+10 | 0.174928E+10 | 175.33 | 0.682540E+10 | 62272644.53 | 0.00 | 1.00 | 18-OCT-11:40 | 0.00 | 01-OCT-00:10 | 47463.08 | 18-OCT-15:50 | 47463.08 | 18-OCT-15:50 | 1143.55 | 15-OCT-11:37 | 11012.56 | 18-OCT-15:50 | 0.00 |
November | 0.155957E+10 | 0.422675E+09 | 69.65 | 0.153615E+10 | 23422047.36 | 0.00 | 0.78 | 03-NOV-15:30 | 0.00 | 01-NOV-00:10 | 23511.39 | 03-NOV-15:30 | 23511.39 | 03-NOV-15:30 | 1030.48 | 03-NOV-17:08 | 5714.18 | 03-NOV-15:30 | 0.00 |
December | 2754552.26 | 810028.89 | 1.00 | 2644562.71 | 109989.55 | 0.00 | 0.03 | 07-DEC-15:00 | 0.00 | 01-DEC-00:10 | 838.66 | 07-DEC-15:00 | 807.73 | 07-DEC-15:00 | 32.88 | 07-DEC-14:20 | 246.48 | 07-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.157636E+12 | 0.404196E+11 | 2020.09 | 0.151963E+12 | 0.567310E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.472985E+11 | 0.122630E+11 | 403.96 | 0.455731E+11 | 0.180123E+10 | 0.00 | 1.00 | 0.00 | 103009.41 | 80411.29 | 48649.79 | 26685.70 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.288782E+09 | 79783256.71 | 17.50 | 0.288196E+09 | 586130.56 | 0.00 | 0.42 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 10336.14 | 28-FEB-15:10 | 10336.14 | 28-FEB-15:10 | 160.80 | 28-FEB-17:02 | 2764.95 | 28-FEB-15:10 | 0.00 |
March | 0.193987E+09 | 54209183.80 | 13.52 | 0.193511E+09 | 476124.74 | 0.00 | 0.37 | 01-MAR-15:10 | 0.00 | 01-MAR-00:10 | 8929.00 | 01-MAR-15:10 | 8929.00 | 01-MAR-15:10 | 179.54 | 01-MAR-17:01 | 2420.45 | 01-MAR-15:10 | 0.00 |
April | 0.193474E+10 | 0.508952E+09 | 71.54 | 0.191390E+10 | 20845825.66 | 0.00 | 0.96 | 06-APR-16:00 | 0.00 | 01-APR-00:10 | 27225.37 | 06-APR-16:00 | 27225.37 | 06-APR-16:00 | 685.22 | 23-APR-13:45 | 6287.64 | 06-APR-16:00 | 0.00 |
May | 0.713833E+10 | 0.181294E+10 | 156.65 | 0.694132E+10 | 0.197008E+09 | 0.00 | 1.00 | 18-MAY-14:50 | 0.00 | 01-MAY-00:10 | 52594.25 | 19-MAY-15:30 | 52594.25 | 19-MAY-15:30 | 4475.82 | 02-MAY-13:00 | 13358.56 | 19-MAY-15:20 | 0.00 |
June | 0.256998E+11 | 0.644619E+10 | 316.36 | 0.245488E+11 | 0.115102E+10 | 0.00 | 1.00 | 05-JUN-12:05 | 0.00 | 01-JUN-00:10 | 62057.21 | 21-JUN-14:05 | 61256.94 | 29-JUN-14:40 | 12904.57 | 22-JUN-06:03 | 17414.17 | 29-JUN-15:00 | 0.00 |
July | 0.432731E+11 | 0.112299E+11 | 404.51 | 0.418694E+11 | 0.140376E+10 | 0.00 | 1.00 | 01-JUL-10:00 | 0.00 | 01-JUL-00:10 | 76846.15 | 17-JUL-15:40 | 76846.15 | 17-JUL-15:40 | 19310.41 | 19-JUL-06:03 | 25205.88 | 17-JUL-15:40 | 0.00 |
August | 0.365075E+11 | 0.937207E+10 | 368.92 | 0.360969E+11 | 0.410556E+09 | 0.00 | 1.00 | 01-AUG-10:30 | 0.00 | 01-AUG-00:10 | 72889.83 | 07-AUG-15:20 | 72889.83 | 07-AUG-15:20 | 3926.39 | 22-AUG-15:30 | 21670.50 | 06-AUG-16:01 | 0.00 |
September | 0.168267E+11 | 0.426224E+10 | 237.31 | 0.154014E+11 | 0.142531E+10 | 0.00 | 1.00 | 01-SEP-09:20 | 0.00 | 01-SEP-00:10 | 92342.61 | 07-SEP-15:00 | 70347.04 | 04-SEP-16:11 | 43953.14 | 07-SEP-14:50 | 21269.16 | 07-SEP-14:55 | 0.00 |
October | 0.332911E+10 | 0.845371E+09 | 96.72 | 0.329809E+10 | 31020199.45 | 0.00 | 1.00 | 15-OCT-15:22 | 0.00 | 01-OCT-00:10 | 41924.62 | 18-OCT-15:50 | 41924.62 | 18-OCT-15:50 | 911.77 | 15-OCT-11:25 | 9770.06 | 18-OCT-15:20 | 0.00 |
November | 0.276943E+09 | 79292070.51 | 32.43 | 0.264399E+09 | 12544299.88 | 0.00 | 0.28 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 6650.39 | 09-NOV-14:00 | 6650.39 | 09-NOV-14:00 | 527.81 | 17-NOV-17:08 | 1842.65 | 09-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.135469E+12 | 0.346909E+11 | 1715.46 | 0.130816E+12 | 0.465312E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.432731E+11 | 0.112299E+11 | 404.51 | 0.418694E+11 | 0.142531E+10 | 0.00 | 1.00 | 0.00 | 92342.61 | 76846.15 | 43953.14 | 25205.88 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.264634E+09 | 74280598.64 | 17.24 | 0.262962E+09 | 1671515.62 | 0.00 | 0.33 | 27-FEB-15:30 | 0.00 | 01-FEB-00:10 | 9163.99 | 27-FEB-15:30 | 9163.99 | 27-FEB-15:30 | 374.98 | 28-FEB-17:02 | 2507.59 | 27-FEB-15:30 | 0.00 |
March | 0.285920E+09 | 80231868.06 | 17.93 | 0.285462E+09 | 457469.18 | 0.00 | 0.39 | 28-MAR-15:50 | 0.00 | 01-MAR-00:10 | 10762.11 | 28-MAR-15:50 | 10762.11 | 28-MAR-15:50 | 272.43 | 01-MAR-17:01 | 2906.29 | 28-MAR-15:50 | 0.00 |
April | 0.195571E+10 | 0.522587E+09 | 73.12 | 0.192233E+10 | 33381116.18 | 0.00 | 0.89 | 06-APR-16:00 | 0.00 | 01-APR-00:10 | 28314.75 | 06-APR-16:00 | 28314.75 | 06-APR-16:00 | 857.51 | 07-APR-18:00 | 6684.03 | 06-APR-16:00 | 0.00 |
May | 0.752284E+10 | 0.192341E+10 | 150.98 | 0.725734E+10 | 0.265498E+09 | 0.00 | 1.00 | 19-MAY-11:50 | 0.00 | 01-MAY-00:10 | 61099.81 | 19-MAY-15:30 | 61099.81 | 19-MAY-15:30 | 4873.05 | 02-MAY-13:00 | 15526.24 | 19-MAY-15:20 | 0.00 |
June | 0.275800E+11 | 0.696758E+10 | 314.61 | 0.262681E+11 | 0.131181E+10 | 0.00 | 1.00 | 05-JUN-12:40 | 0.00 | 01-JUN-00:10 | 69804.56 | 20-JUN-15:10 | 69601.84 | 29-JUN-14:50 | 7750.14 | 20-JUN-15:10 | 19831.78 | 29-JUN-15:00 | 0.00 |
July | 0.465471E+11 | 0.121794E+11 | 405.56 | 0.449437E+11 | 0.160337E+10 | 0.00 | 1.00 | 01-JUL-11:40 | 0.00 | 01-JUL-00:10 | 88467.67 | 17-JUL-15:30 | 88467.67 | 17-JUL-15:30 | 12107.63 | 17-JUL-06:03 | 28853.22 | 17-JUL-15:30 | 0.00 |
August | 0.384518E+11 | 0.997416E+10 | 367.50 | 0.378865E+11 | 0.565279E+09 | 0.00 | 1.00 | 01-AUG-11:40 | 0.00 | 01-AUG-00:10 | 83742.27 | 06-AUG-16:11 | 83742.27 | 06-AUG-16:11 | 4243.80 | 22-AUG-15:30 | 26283.57 | 06-AUG-16:11 | 0.00 |
September | 0.170974E+11 | 0.438496E+10 | 233.93 | 0.155200E+11 | 0.157732E+10 | 0.00 | 1.00 | 01-SEP-09:50 | 0.00 | 01-SEP-00:10 | 93359.50 | 07-SEP-15:20 | 79833.62 | 04-SEP-15:41 | 44391.76 | 07-SEP-15:00 | 23093.92 | 04-SEP-15:41 | 0.00 |
October | 0.302517E+10 | 0.784653E+09 | 91.24 | 0.296285E+10 | 62314646.31 | 0.00 | 1.00 | 18-OCT-12:50 | 0.00 | 01-OCT-00:10 | 42971.39 | 18-OCT-15:00 | 42971.39 | 18-OCT-15:00 | 1294.92 | 15-OCT-11:53 | 10092.48 | 18-OCT-15:00 | 0.00 |
November | 0.174467E+09 | 50471081.35 | 24.17 | 0.154719E+09 | 19748268.41 | 0.00 | 0.16 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 4183.28 | 04-NOV-14:00 | 3987.91 | 04-NOV-14:00 | 662.05 | 17-NOV-17:00 | 1194.12 | 04-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.142905E+12 | 0.369417E+11 | 1696.27 | 0.137464E+12 | 0.544085E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.465471E+11 | 0.121794E+11 | 405.56 | 0.449437E+11 | 0.160337E+10 | 0.00 | 1.00 | 0.00 | 93359.50 | 88467.67 | 44391.76 | 28853.22 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 316.01 | 0.00 | 316.01 | 14.99 | 2540.92 | 0.00 | 0.00 | 0.00 |
February | 446.19 | 0.00 | 446.19 | 95.74 | 1857.56 | 0.00 | 0.00 | 0.00 |
March | 724.82 | 0.00 | 724.82 | 289.89 | 1487.17 | 0.00 | 0.00 | 0.00 |
April | 826.45 | 4.82 | 821.63 | 474.28 | 1053.89 | 0.00 | 0.00 | 0.00 |
May | 1085.32 | 64.31 | 1021.01 | 845.06 | 795.64 | 0.00 | 0.00 | 0.00 |
June | 1263.80 | 145.26 | 1118.54 | 1317.98 | 528.03 | 0.00 | 0.00 | 0.00 |
July | 1154.55 | 108.14 | 1046.41 | 1423.33 | 445.54 | 0.00 | 0.00 | 0.00 |
August | 925.15 | 24.80 | 900.35 | 1039.73 | 503.29 | 0.00 | 0.00 | 0.00 |
September | 692.87 | 0.25 | 692.62 | 614.86 | 755.21 | 0.00 | 0.00 | 0.00 |
October | 505.41 | 0.00 | 505.41 | 258.44 | 1086.11 | 0.00 | 0.00 | 0.00 |
November | 343.58 | 0.00 | 343.58 | 70.24 | 1534.23 | 0.00 | 0.00 | 0.00 |
December | 265.00 | 0.00 | 265.00 | 8.08 | 2148.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 713.86 | 29.11 | 684.75 | 540.46 | 1225.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 265.00 | 0.00 | 265.00 | 8.08 | 445.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1263.80 | 145.26 | 1118.54 | 1423.33 | 2540.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 483.77 | 221.79 | 261.98 | 274.20 | 1559.41 | 0.00 | 0.00 | 0.00 |
February | 756.66 | 375.66 | 381.00 | 597.50 | 1140.95 | 0.00 | 0.00 | 0.00 |
March | 1017.40 | 420.97 | 596.43 | 866.12 | 939.80 | 0.00 | 0.00 | 0.00 |
April | 1298.10 | 643.33 | 654.77 | 1291.37 | 680.56 | 0.00 | 0.00 | 0.00 |
May | 1433.92 | 638.00 | 795.92 | 1519.04 | 540.77 | 0.00 | 0.00 | 0.00 |
June | 1856.02 | 955.11 | 900.91 | 2246.49 | 365.09 | 0.00 | 0.00 | 0.00 |
July | 1947.95 | 1101.23 | 846.72 | 2540.00 | 300.48 | 0.00 | 0.00 | 0.00 |
August | 1692.85 | 943.21 | 749.65 | 2157.33 | 336.08 | 0.00 | 0.00 | 0.00 |
September | 1197.53 | 618.16 | 579.37 | 1388.47 | 483.30 | 0.00 | 0.00 | 0.00 |
October | 859.16 | 436.27 | 422.89 | 841.69 | 690.11 | 0.00 | 0.00 | 0.00 |
November | 544.52 | 254.22 | 290.30 | 402.01 | 942.73 | 0.00 | 0.00 | 0.00 |
December | 401.62 | 172.49 | 229.12 | 217.32 | 1317.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1126.05 | 566.02 | 560.03 | 1198.54 | 773.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 401.62 | 172.49 | 229.12 | 217.32 | 300.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1947.95 | 1101.23 | 900.91 | 2540.00 | 1559.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2227.55 | 1590.96 | 636.59 | 2136.65 | 2184.16 | 0.00 | 0.00 | 0.00 |
February | 2836.75 | 2040.30 | 796.45 | 2988.33 | 1629.03 | 0.00 | 0.00 | 0.00 |
March | 2535.68 | 1423.92 | 1111.76 | 2661.85 | 1457.18 | 0.00 | 0.00 | 0.00 |
April | 2038.27 | 974.92 | 1063.35 | 2217.02 | 1092.48 | 0.00 | 0.00 | 0.00 |
May | 1810.95 | 601.47 | 1209.48 | 1997.25 | 870.68 | 0.00 | 0.00 | 0.00 |
June | 1799.36 | 524.78 | 1274.58 | 2250.90 | 611.49 | 0.00 | 0.00 | 0.00 |
July | 1939.89 | 716.59 | 1223.30 | 2706.28 | 490.76 | 0.00 | 0.00 | 0.00 |
August | 2305.43 | 1162.36 | 1143.07 | 3124.00 | 547.38 | 0.00 | 0.00 | 0.00 |
September | 2557.00 | 1566.76 | 990.24 | 3216.58 | 772.20 | 0.00 | 0.00 | 0.00 |
October | 2673.21 | 1848.49 | 824.72 | 3102.44 | 1064.28 | 0.00 | 0.00 | 0.00 |
November | 2437.17 | 1765.39 | 671.78 | 2598.73 | 1358.81 | 0.00 | 0.00 | 0.00 |
December | 2118.27 | 1529.61 | 588.67 | 2087.95 | 1842.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2269.38 | 1307.28 | 962.09 | 2587.62 | 1158.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1799.36 | 524.78 | 588.67 | 1997.25 | 490.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2836.75 | 2040.30 | 1274.58 | 3216.58 | 2184.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 438.19 | 176.60 | 261.60 | 237.93 | 1623.69 | 0.00 | 0.00 | 0.00 |
February | 747.93 | 367.65 | 380.28 | 601.18 | 1170.32 | 0.00 | 0.00 | 0.00 |
March | 957.17 | 350.72 | 606.45 | 798.48 | 979.92 | 0.00 | 0.00 | 0.00 |
April | 1249.59 | 553.63 | 695.96 | 1254.49 | 720.21 | 0.00 | 0.00 | 0.00 |
May | 1545.65 | 704.90 | 840.75 | 1685.21 | 573.07 | 0.00 | 0.00 | 0.00 |
June | 1681.61 | 772.43 | 909.18 | 2038.85 | 401.93 | 0.00 | 0.00 | 0.00 |
July | 1722.62 | 870.47 | 852.15 | 2266.63 | 337.35 | 0.00 | 0.00 | 0.00 |
August | 1462.74 | 717.88 | 744.86 | 1874.23 | 363.85 | 0.00 | 0.00 | 0.00 |
September | 1176.68 | 594.88 | 581.80 | 1385.32 | 514.91 | 0.00 | 0.00 | 0.00 |
October | 841.00 | 417.85 | 423.15 | 843.10 | 724.28 | 0.00 | 0.00 | 0.00 |
November | 595.35 | 295.34 | 300.01 | 489.34 | 978.92 | 0.00 | 0.00 | 0.00 |
December | 400.18 | 168.91 | 231.28 | 229.76 | 1357.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1069.68 | 499.75 | 569.93 | 1144.85 | 810.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 400.18 | 168.91 | 231.28 | 229.76 | 337.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1722.62 | 870.47 | 909.18 | 2266.63 | 1623.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.33 | 0.00 | 105.33 | 4.29 | 861.23 | 0.00 | 0.00 | 0.00 |
February | 148.72 | 0.00 | 148.72 | 31.49 | 632.99 | 0.00 | 0.00 | 0.00 |
March | 241.60 | 0.00 | 241.60 | 100.80 | 503.88 | 0.00 | 0.00 | 0.00 |
April | 275.47 | 1.61 | 273.86 | 168.84 | 348.70 | 0.00 | 0.00 | 0.00 |
May | 361.76 | 21.44 | 340.32 | 294.21 | 266.21 | 0.00 | 0.00 | 0.00 |
June | 421.25 | 48.42 | 372.83 | 449.62 | 174.47 | 0.00 | 0.00 | 0.00 |
July | 384.83 | 36.04 | 348.79 | 482.09 | 147.35 | 0.00 | 0.00 | 0.00 |
August | 308.37 | 8.27 | 300.10 | 351.07 | 169.91 | 0.00 | 0.00 | 0.00 |
September | 230.95 | 0.08 | 230.86 | 205.24 | 264.89 | 0.00 | 0.00 | 0.00 |
October | 168.46 | 0.00 | 168.46 | 79.96 | 393.80 | 0.00 | 0.00 | 0.00 |
November | 114.52 | 0.00 | 114.52 | 20.33 | 551.06 | 0.00 | 0.00 | 0.00 |
December | 88.33 | 0.00 | 88.33 | 2.51 | 747.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 237.94 | 9.70 | 228.24 | 183.47 | 421.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.33 | 0.00 | 88.33 | 2.51 | 147.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 421.25 | 48.42 | 372.83 | 482.09 | 861.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.34 | 0.00 | 105.34 | 4.29 | 861.28 | 0.00 | 0.00 | 0.00 |
February | 148.73 | 0.00 | 148.73 | 31.49 | 633.03 | 0.00 | 0.00 | 0.00 |
March | 241.60 | 0.00 | 241.60 | 100.80 | 503.91 | 0.00 | 0.00 | 0.00 |
April | 275.48 | 1.61 | 273.87 | 168.84 | 348.73 | 0.00 | 0.00 | 0.00 |
May | 361.77 | 21.44 | 340.33 | 294.22 | 266.23 | 0.00 | 0.00 | 0.00 |
June | 421.26 | 48.42 | 372.84 | 449.63 | 174.48 | 0.00 | 0.00 | 0.00 |
July | 384.85 | 36.05 | 348.80 | 482.10 | 147.36 | 0.00 | 0.00 | 0.00 |
August | 308.38 | 8.27 | 300.11 | 351.09 | 169.92 | 0.00 | 0.00 | 0.00 |
September | 230.96 | 0.08 | 230.87 | 205.25 | 264.91 | 0.00 | 0.00 | 0.00 |
October | 168.47 | 0.00 | 168.47 | 79.96 | 393.82 | 0.00 | 0.00 | 0.00 |
November | 114.53 | 0.00 | 114.53 | 20.33 | 551.09 | 0.00 | 0.00 | 0.00 |
December | 88.33 | 0.00 | 88.33 | 2.51 | 747.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 237.95 | 9.70 | 228.25 | 183.47 | 421.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.33 | 0.00 | 88.33 | 2.51 | 147.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 421.26 | 48.42 | 372.84 | 482.10 | 861.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.34 | 0.00 | 105.34 | 4.29 | 861.28 | 0.00 | 0.00 | 0.00 |
February | 148.73 | 0.00 | 148.73 | 31.49 | 633.03 | 0.00 | 0.00 | 0.00 |
March | 241.60 | 0.00 | 241.60 | 100.80 | 503.91 | 0.00 | 0.00 | 0.00 |
April | 275.48 | 1.61 | 273.87 | 168.84 | 348.73 | 0.00 | 0.00 | 0.00 |
May | 361.77 | 21.44 | 340.33 | 294.22 | 266.23 | 0.00 | 0.00 | 0.00 |
June | 421.26 | 48.42 | 372.84 | 449.63 | 174.48 | 0.00 | 0.00 | 0.00 |
July | 384.85 | 36.05 | 348.80 | 482.10 | 147.36 | 0.00 | 0.00 | 0.00 |
August | 308.38 | 8.27 | 300.11 | 351.09 | 169.92 | 0.00 | 0.00 | 0.00 |
September | 230.96 | 0.08 | 230.87 | 205.25 | 264.91 | 0.00 | 0.00 | 0.00 |
October | 168.47 | 0.00 | 168.47 | 79.96 | 393.82 | 0.00 | 0.00 | 0.00 |
November | 114.53 | 0.00 | 114.53 | 20.33 | 551.09 | 0.00 | 0.00 | 0.00 |
December | 88.33 | 0.00 | 88.33 | 2.51 | 747.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 237.95 | 9.70 | 228.25 | 183.47 | 421.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.33 | 0.00 | 88.33 | 2.51 | 147.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 421.26 | 48.42 | 372.84 | 482.10 | 861.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 465.36 | 213.35 | 252.01 | 262.64 | 1533.10 | 0.00 | 0.00 | 0.00 |
February | 727.87 | 361.37 | 366.50 | 574.73 | 1131.85 | 0.00 | 0.00 | 0.00 |
March | 978.68 | 404.95 | 573.73 | 841.23 | 933.61 | 0.00 | 0.00 | 0.00 |
April | 1248.71 | 618.85 | 629.86 | 1257.33 | 670.96 | 0.00 | 0.00 | 0.00 |
May | 1379.36 | 613.73 | 765.63 | 1476.92 | 536.89 | 0.00 | 0.00 | 0.00 |
June | 1785.40 | 918.76 | 866.64 | 2176.15 | 360.27 | 0.00 | 0.00 | 0.00 |
July | 1873.83 | 1059.32 | 814.51 | 2454.78 | 300.91 | 0.00 | 0.00 | 0.00 |
August | 1628.44 | 907.31 | 721.13 | 2083.34 | 340.17 | 0.00 | 0.00 | 0.00 |
September | 1151.96 | 594.64 | 557.33 | 1334.57 | 502.52 | 0.00 | 0.00 | 0.00 |
October | 826.47 | 419.67 | 406.80 | 794.76 | 735.32 | 0.00 | 0.00 | 0.00 |
November | 523.80 | 244.55 | 279.26 | 371.75 | 988.47 | 0.00 | 0.00 | 0.00 |
December | 386.33 | 165.93 | 220.40 | 204.43 | 1326.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1083.20 | 544.48 | 538.73 | 1156.02 | 778.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 386.33 | 165.93 | 220.40 | 204.43 | 300.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1873.83 | 1059.32 | 866.64 | 2454.78 | 1533.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.40 | 8.44 | 9.96 | 10.38 | 60.62 | 0.00 | 0.00 | 0.00 |
February | 28.78 | 14.29 | 14.49 | 22.72 | 44.75 | 0.00 | 0.00 | 0.00 |
March | 38.70 | 16.01 | 22.68 | 33.26 | 36.91 | 0.00 | 0.00 | 0.00 |
April | 49.37 | 24.47 | 24.90 | 49.71 | 26.53 | 0.00 | 0.00 | 0.00 |
May | 54.54 | 24.27 | 30.27 | 58.40 | 21.23 | 0.00 | 0.00 | 0.00 |
June | 70.59 | 36.33 | 34.27 | 86.04 | 14.24 | 0.00 | 0.00 | 0.00 |
July | 74.09 | 41.88 | 32.20 | 97.06 | 11.90 | 0.00 | 0.00 | 0.00 |
August | 64.39 | 35.87 | 28.51 | 82.37 | 13.45 | 0.00 | 0.00 | 0.00 |
September | 45.55 | 23.51 | 22.04 | 52.77 | 19.87 | 0.00 | 0.00 | 0.00 |
October | 32.68 | 16.59 | 16.08 | 31.42 | 29.07 | 0.00 | 0.00 | 0.00 |
November | 20.71 | 9.67 | 11.04 | 14.70 | 39.08 | 0.00 | 0.00 | 0.00 |
December | 15.28 | 6.56 | 8.71 | 8.08 | 52.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.83 | 21.53 | 21.30 | 45.71 | 30.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.28 | 6.56 | 8.71 | 8.08 | 11.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.09 | 41.88 | 34.27 | 97.06 | 60.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 742.50 | 530.31 | 212.19 | 720.79 | 742.45 | 0.00 | 0.00 | 0.00 |
February | 945.57 | 680.09 | 265.48 | 1006.60 | 568.29 | 0.00 | 0.00 | 0.00 |
March | 845.21 | 474.63 | 370.58 | 899.16 | 506.17 | 0.00 | 0.00 | 0.00 |
April | 679.41 | 324.97 | 354.45 | 751.90 | 371.98 | 0.00 | 0.00 | 0.00 |
May | 603.64 | 200.48 | 403.16 | 680.80 | 294.14 | 0.00 | 0.00 | 0.00 |
June | 599.78 | 174.92 | 424.86 | 763.67 | 204.00 | 0.00 | 0.00 | 0.00 |
July | 646.62 | 238.86 | 407.76 | 910.42 | 167.58 | 0.00 | 0.00 | 0.00 |
August | 768.47 | 387.44 | 381.02 | 1048.33 | 191.57 | 0.00 | 0.00 | 0.00 |
September | 852.32 | 522.24 | 330.08 | 1076.47 | 280.89 | 0.00 | 0.00 | 0.00 |
October | 891.05 | 616.15 | 274.90 | 1032.95 | 398.12 | 0.00 | 0.00 | 0.00 |
November | 812.38 | 588.45 | 223.92 | 862.36 | 499.47 | 0.00 | 0.00 | 0.00 |
December | 706.08 | 509.86 | 196.22 | 697.18 | 645.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 756.45 | 435.75 | 320.69 | 869.85 | 405.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 599.78 | 174.92 | 196.22 | 680.80 | 167.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 945.57 | 680.09 | 424.86 | 1076.47 | 742.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 742.50 | 530.31 | 212.19 | 720.79 | 742.45 | 0.00 | 0.00 | 0.00 |
February | 945.57 | 680.09 | 265.48 | 1006.60 | 568.29 | 0.00 | 0.00 | 0.00 |
March | 845.21 | 474.63 | 370.58 | 899.16 | 506.17 | 0.00 | 0.00 | 0.00 |
April | 679.41 | 324.97 | 354.45 | 751.90 | 371.98 | 0.00 | 0.00 | 0.00 |
May | 603.64 | 200.48 | 403.16 | 680.80 | 294.14 | 0.00 | 0.00 | 0.00 |
June | 599.78 | 174.92 | 424.86 | 763.67 | 204.00 | 0.00 | 0.00 | 0.00 |
July | 646.62 | 238.86 | 407.76 | 910.42 | 167.58 | 0.00 | 0.00 | 0.00 |
August | 768.47 | 387.44 | 381.02 | 1048.33 | 191.57 | 0.00 | 0.00 | 0.00 |
September | 852.32 | 522.24 | 330.08 | 1076.47 | 280.89 | 0.00 | 0.00 | 0.00 |
October | 891.05 | 616.15 | 274.90 | 1032.95 | 398.12 | 0.00 | 0.00 | 0.00 |
November | 812.38 | 588.45 | 223.92 | 862.36 | 499.47 | 0.00 | 0.00 | 0.00 |
December | 706.08 | 509.86 | 196.22 | 697.18 | 645.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 756.45 | 435.75 | 320.69 | 869.85 | 405.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 599.78 | 174.92 | 196.22 | 680.80 | 167.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 945.57 | 680.09 | 424.86 | 1076.47 | 742.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 742.46 | 530.28 | 212.18 | 720.75 | 742.40 | 0.00 | 0.00 | 0.00 |
February | 945.51 | 680.04 | 265.46 | 1006.54 | 568.26 | 0.00 | 0.00 | 0.00 |
March | 845.16 | 474.60 | 370.56 | 899.10 | 506.14 | 0.00 | 0.00 | 0.00 |
April | 679.37 | 324.94 | 354.42 | 751.85 | 371.96 | 0.00 | 0.00 | 0.00 |
May | 603.60 | 200.47 | 403.13 | 680.76 | 294.12 | 0.00 | 0.00 | 0.00 |
June | 599.74 | 174.91 | 424.83 | 763.62 | 203.99 | 0.00 | 0.00 | 0.00 |
July | 646.58 | 238.84 | 407.74 | 910.36 | 167.57 | 0.00 | 0.00 | 0.00 |
August | 768.42 | 387.42 | 381.00 | 1048.27 | 191.55 | 0.00 | 0.00 | 0.00 |
September | 852.27 | 522.21 | 330.06 | 1076.40 | 280.87 | 0.00 | 0.00 | 0.00 |
October | 891.00 | 616.11 | 274.89 | 1032.88 | 398.10 | 0.00 | 0.00 | 0.00 |
November | 812.32 | 588.41 | 223.91 | 862.30 | 499.44 | 0.00 | 0.00 | 0.00 |
December | 706.03 | 509.83 | 196.21 | 697.13 | 645.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 756.40 | 435.72 | 320.67 | 869.79 | 405.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 599.74 | 174.91 | 196.21 | 680.76 | 167.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 945.51 | 680.04 | 424.83 | 1076.40 | 742.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 421.52 | 169.88 | 251.65 | 230.69 | 1591.69 | 0.00 | 0.00 | 0.00 |
February | 719.47 | 353.66 | 365.82 | 584.07 | 1162.24 | 0.00 | 0.00 | 0.00 |
March | 920.75 | 337.38 | 583.37 | 781.23 | 970.35 | 0.00 | 0.00 | 0.00 |
April | 1202.04 | 532.56 | 669.48 | 1225.77 | 707.69 | 0.00 | 0.00 | 0.00 |
May | 1486.84 | 678.08 | 808.76 | 1638.34 | 573.14 | 0.00 | 0.00 | 0.00 |
June | 1617.63 | 743.03 | 874.59 | 1979.24 | 398.35 | 0.00 | 0.00 | 0.00 |
July | 1657.08 | 837.34 | 819.74 | 2193.12 | 338.06 | 0.00 | 0.00 | 0.00 |
August | 1407.08 | 690.56 | 716.52 | 1811.92 | 368.12 | 0.00 | 0.00 | 0.00 |
September | 1131.91 | 572.25 | 559.66 | 1333.29 | 537.35 | 0.00 | 0.00 | 0.00 |
October | 809.00 | 401.95 | 407.06 | 798.99 | 773.21 | 0.00 | 0.00 | 0.00 |
November | 572.70 | 284.11 | 288.59 | 462.22 | 1026.14 | 0.00 | 0.00 | 0.00 |
December | 384.96 | 162.48 | 222.48 | 220.04 | 1366.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1028.98 | 480.74 | 548.25 | 1107.60 | 816.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 384.96 | 162.48 | 222.48 | 220.04 | 338.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1657.08 | 837.34 | 874.59 | 2193.12 | 1591.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.67 | 6.72 | 9.95 | 9.12 | 62.93 | 0.00 | 0.00 | 0.00 |
February | 28.45 | 13.98 | 14.46 | 23.09 | 45.95 | 0.00 | 0.00 | 0.00 |
March | 36.41 | 13.34 | 23.07 | 30.89 | 38.37 | 0.00 | 0.00 | 0.00 |
April | 47.53 | 21.06 | 26.47 | 48.47 | 27.98 | 0.00 | 0.00 | 0.00 |
May | 58.79 | 26.81 | 31.98 | 64.78 | 22.66 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 29.38 | 34.58 | 78.26 | 15.75 | 0.00 | 0.00 | 0.00 |
July | 65.52 | 33.11 | 32.41 | 86.71 | 13.37 | 0.00 | 0.00 | 0.00 |
August | 55.63 | 27.30 | 28.33 | 71.64 | 14.55 | 0.00 | 0.00 | 0.00 |
September | 44.75 | 22.63 | 22.13 | 52.72 | 21.25 | 0.00 | 0.00 | 0.00 |
October | 31.99 | 15.89 | 16.09 | 31.59 | 30.57 | 0.00 | 0.00 | 0.00 |
November | 22.64 | 11.23 | 11.41 | 18.28 | 40.57 | 0.00 | 0.00 | 0.00 |
December | 15.22 | 6.42 | 8.80 | 8.70 | 54.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 19.01 | 21.68 | 43.79 | 32.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.22 | 6.42 | 8.80 | 8.70 | 13.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.52 | 33.11 | 34.58 | 86.71 | 62.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 316.01 | 0.00 | 316.01 | 12.13 | 2612.02 | 0.00 | 0.00 | 0.00 |
February | 446.19 | 0.00 | 446.19 | 85.84 | 1935.90 | 0.00 | 0.00 | 0.00 |
March | 724.82 | 0.00 | 724.82 | 273.30 | 1565.20 | 0.00 | 0.00 | 0.00 |
April | 826.45 | 4.82 | 821.63 | 456.09 | 1121.42 | 0.00 | 0.00 | 0.00 |
May | 1085.32 | 64.31 | 1021.01 | 829.71 | 840.76 | 0.00 | 0.00 | 0.00 |
June | 1263.80 | 145.26 | 1118.54 | 1311.40 | 547.32 | 0.00 | 0.00 | 0.00 |
July | 1154.55 | 108.14 | 1046.41 | 1422.03 | 458.53 | 0.00 | 0.00 | 0.00 |
August | 925.15 | 24.80 | 900.35 | 1035.43 | 524.59 | 0.00 | 0.00 | 0.00 |
September | 692.87 | 0.25 | 692.62 | 603.41 | 802.79 | 0.00 | 0.00 | 0.00 |
October | 505.41 | 0.00 | 505.41 | 236.12 | 1171.80 | 0.00 | 0.00 | 0.00 |
November | 343.58 | 0.00 | 343.58 | 59.55 | 1640.14 | 0.00 | 0.00 | 0.00 |
December | 265.00 | 0.00 | 265.00 | 6.85 | 2235.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 713.86 | 29.11 | 684.75 | 530.41 | 1285.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 265.00 | 0.00 | 265.00 | 6.85 | 458.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1263.80 | 145.26 | 1118.54 | 1422.03 | 2612.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 483.77 | 221.79 | 261.98 | 268.44 | 1600.22 | 0.00 | 0.00 | 0.00 |
February | 756.66 | 375.66 | 381.00 | 584.36 | 1189.00 | 0.00 | 0.00 | 0.00 |
March | 1017.40 | 420.97 | 596.43 | 849.42 | 989.28 | 0.00 | 0.00 | 0.00 |
April | 1298.10 | 643.33 | 654.77 | 1276.29 | 721.92 | 0.00 | 0.00 | 0.00 |
May | 1433.92 | 638.00 | 795.92 | 1508.55 | 569.75 | 0.00 | 0.00 | 0.00 |
June | 1856.02 | 955.11 | 900.91 | 2242.02 | 377.59 | 0.00 | 0.00 | 0.00 |
July | 1947.95 | 1101.23 | 846.72 | 2538.41 | 309.30 | 0.00 | 0.00 | 0.00 |
August | 1692.85 | 943.21 | 749.65 | 2153.55 | 349.05 | 0.00 | 0.00 | 0.00 |
September | 1197.53 | 618.16 | 579.37 | 1378.81 | 510.63 | 0.00 | 0.00 | 0.00 |
October | 859.16 | 436.27 | 422.89 | 822.32 | 741.40 | 0.00 | 0.00 | 0.00 |
November | 544.52 | 254.22 | 290.30 | 384.95 | 1007.08 | 0.00 | 0.00 | 0.00 |
December | 401.62 | 172.49 | 229.12 | 210.49 | 1370.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1126.05 | 566.02 | 560.03 | 1188.25 | 809.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 401.62 | 172.49 | 229.12 | 210.49 | 309.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1947.95 | 1101.23 | 900.91 | 2538.41 | 1600.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2227.55 | 1590.96 | 636.59 | 2123.15 | 2252.62 | 0.00 | 0.00 | 0.00 |
February | 2836.75 | 2040.30 | 796.45 | 2969.80 | 1703.45 | 0.00 | 0.00 | 0.00 |
March | 2535.68 | 1423.92 | 1111.76 | 2644.06 | 1534.06 | 0.00 | 0.00 | 0.00 |
April | 2038.27 | 974.92 | 1063.35 | 2202.44 | 1158.06 | 0.00 | 0.00 | 0.00 |
May | 1810.95 | 601.47 | 1209.48 | 1988.36 | 918.35 | 0.00 | 0.00 | 0.00 |
June | 1799.36 | 524.78 | 1274.58 | 2250.31 | 636.14 | 0.00 | 0.00 | 0.00 |
July | 1939.89 | 716.59 | 1223.30 | 2709.19 | 507.57 | 0.00 | 0.00 | 0.00 |
August | 2305.43 | 1162.36 | 1143.07 | 3125.41 | 570.56 | 0.00 | 0.00 | 0.00 |
September | 2557.00 | 1566.76 | 990.24 | 3210.59 | 816.03 | 0.00 | 0.00 | 0.00 |
October | 2673.21 | 1848.49 | 824.72 | 3082.89 | 1140.22 | 0.00 | 0.00 | 0.00 |
November | 2437.17 | 1765.39 | 671.78 | 2570.48 | 1448.68 | 0.00 | 0.00 | 0.00 |
December | 2118.27 | 1529.61 | 588.67 | 2067.83 | 1925.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2269.38 | 1307.28 | 962.09 | 2575.72 | 1215.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1799.36 | 524.78 | 588.67 | 1988.36 | 507.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2836.75 | 2040.30 | 1274.58 | 3210.59 | 2252.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 438.19 | 176.60 | 261.60 | 234.45 | 1667.86 | 0.00 | 0.00 | 0.00 |
February | 747.93 | 367.65 | 380.28 | 592.74 | 1221.53 | 0.00 | 0.00 | 0.00 |
March | 957.17 | 350.72 | 606.45 | 787.60 | 1031.58 | 0.00 | 0.00 | 0.00 |
April | 1249.59 | 553.63 | 695.96 | 1242.99 | 764.10 | 0.00 | 0.00 | 0.00 |
May | 1545.65 | 704.90 | 840.75 | 1678.68 | 604.60 | 0.00 | 0.00 | 0.00 |
June | 1681.61 | 772.43 | 909.18 | 2038.44 | 418.16 | 0.00 | 0.00 | 0.00 |
July | 1722.62 | 870.47 | 852.15 | 2268.47 | 348.55 | 0.00 | 0.00 | 0.00 |
August | 1462.74 | 717.88 | 744.86 | 1873.98 | 379.30 | 0.00 | 0.00 | 0.00 |
September | 1176.68 | 594.88 | 581.80 | 1379.33 | 546.10 | 0.00 | 0.00 | 0.00 |
October | 841.00 | 417.85 | 423.15 | 828.64 | 779.73 | 0.00 | 0.00 | 0.00 |
November | 595.35 | 295.34 | 300.01 | 477.56 | 1045.50 | 0.00 | 0.00 | 0.00 |
December | 400.18 | 168.91 | 231.28 | 224.83 | 1412.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1069.68 | 499.75 | 569.93 | 1138.47 | 850.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 400.18 | 168.91 | 231.28 | 224.83 | 348.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1722.62 | 870.47 | 909.18 | 2268.47 | 1667.86 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.846413E+09 | 0.00 | 0.846413E+09 | 40139495.35 | 0.680561E+10 |
February | 0.107943E+10 | 0.00 | 0.107943E+10 | 0.231618E+09 | 0.449380E+10 |
March | 0.194136E+10 | 0.00 | 0.194136E+10 | 0.776445E+09 | 0.398324E+10 |
April | 0.214215E+10 | 12501134.09 | 0.212965E+10 | 0.122933E+10 | 0.273168E+10 |
May | 0.290693E+10 | 0.172254E+09 | 0.273468E+10 | 0.226340E+10 | 0.213103E+10 |
June | 0.327577E+10 | 0.376522E+09 | 0.289925E+10 | 0.341621E+10 | 0.136865E+10 |
July | 0.309235E+10 | 0.289636E+09 | 0.280271E+10 | 0.381225E+10 | 0.119333E+10 |
August | 0.247791E+10 | 66419681.66 | 0.241150E+10 | 0.278481E+10 | 0.134802E+10 |
September | 0.179592E+10 | 644474.31 | 0.179528E+10 | 0.159372E+10 | 0.195750E+10 |
October | 0.135369E+10 | 0.00 | 0.135369E+10 | 0.692210E+09 | 0.290903E+10 |
November | 0.890565E+09 | 0.00 | 0.890565E+09 | 0.182067E+09 | 0.397673E+10 |
December | 0.709765E+09 | 0.00 | 0.709765E+09 | 21644758.99 | 0.575381E+10 |
Annual Sum or Average | 0.225123E+11 | 0.917976E+09 | 0.215943E+11 | 0.170439E+11 | 0.386524E+11 |
Minimum of Months | 0.709765E+09 | 0.00 | 0.709765E+09 | 21644758.99 | 0.119333E+10 |
Maximum of Months | 0.327577E+10 | 0.376522E+09 | 0.289925E+10 | 0.381225E+10 | 0.680561E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129573E+10 | 0.594040E+09 | 0.701690E+09 | 0.734407E+09 | 0.417674E+10 |
February | 0.183051E+10 | 0.908805E+09 | 0.921705E+09 | 0.144548E+10 | 0.276019E+10 |
March | 0.272500E+10 | 0.112753E+10 | 0.159747E+10 | 0.231982E+10 | 0.251717E+10 |
April | 0.336467E+10 | 0.166751E+10 | 0.169717E+10 | 0.334724E+10 | 0.176400E+10 |
May | 0.384061E+10 | 0.170883E+10 | 0.213178E+10 | 0.406860E+10 | 0.144839E+10 |
June | 0.481081E+10 | 0.247564E+10 | 0.233517E+10 | 0.582291E+10 | 0.946309E+09 |
July | 0.521738E+10 | 0.294953E+10 | 0.226786E+10 | 0.680313E+10 | 0.804802E+09 |
August | 0.453414E+10 | 0.252628E+10 | 0.200786E+10 | 0.577820E+10 | 0.900166E+09 |
September | 0.310399E+10 | 0.160227E+10 | 0.150172E+10 | 0.359893E+10 | 0.125272E+10 |
October | 0.230118E+10 | 0.116850E+10 | 0.113268E+10 | 0.225438E+10 | 0.184840E+10 |
November | 0.141140E+10 | 0.658938E+09 | 0.752461E+09 | 0.104202E+10 | 0.244356E+10 |
December | 0.107569E+10 | 0.462010E+09 | 0.613678E+09 | 0.582057E+09 | 0.352747E+10 |
Annual Sum or Average | 0.355111E+11 | 0.178499E+11 | 0.176612E+11 | 0.377972E+11 | 0.243899E+11 |
Minimum of Months | 0.107569E+10 | 0.462010E+09 | 0.613678E+09 | 0.582057E+09 | 0.804802E+09 |
Maximum of Months | 0.521738E+10 | 0.294953E+10 | 0.233517E+10 | 0.680313E+10 | 0.417674E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.596627E+10 | 0.426123E+10 | 0.170504E+10 | 0.572281E+10 | 0.585006E+10 |
February | 0.686267E+10 | 0.493589E+10 | 0.192678E+10 | 0.722938E+10 | 0.394095E+10 |
March | 0.679158E+10 | 0.381384E+10 | 0.297774E+10 | 0.712950E+10 | 0.390292E+10 |
April | 0.528318E+10 | 0.252698E+10 | 0.275620E+10 | 0.574651E+10 | 0.283171E+10 |
May | 0.485044E+10 | 0.161096E+10 | 0.323948E+10 | 0.534944E+10 | 0.233202E+10 |
June | 0.466394E+10 | 0.136023E+10 | 0.330371E+10 | 0.583434E+10 | 0.158497E+10 |
July | 0.519580E+10 | 0.191931E+10 | 0.327649E+10 | 0.724851E+10 | 0.131445E+10 |
August | 0.617486E+10 | 0.311326E+10 | 0.306161E+10 | 0.836733E+10 | 0.146609E+10 |
September | 0.662774E+10 | 0.406103E+10 | 0.256671E+10 | 0.833738E+10 | 0.200155E+10 |
October | 0.715991E+10 | 0.495099E+10 | 0.220892E+10 | 0.830956E+10 | 0.285056E+10 |
November | 0.631715E+10 | 0.457589E+10 | 0.174126E+10 | 0.673592E+10 | 0.352205E+10 |
December | 0.567359E+10 | 0.409690E+10 | 0.157668E+10 | 0.559238E+10 | 0.493545E+10 |
Annual Sum or Average | 0.715671E+11 | 0.412265E+11 | 0.303406E+11 | 0.816031E+11 | 0.365328E+11 |
Minimum of Months | 0.466394E+10 | 0.136023E+10 | 0.157668E+10 | 0.534944E+10 | 0.131445E+10 |
Maximum of Months | 0.715991E+10 | 0.495099E+10 | 0.330371E+10 | 0.836733E+10 | 0.585006E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117366E+10 | 0.472992E+09 | 0.700664E+09 | 0.637264E+09 | 0.434888E+10 |
February | 0.180939E+10 | 0.889407E+09 | 0.919983E+09 | 0.145437E+10 | 0.283125E+10 |
March | 0.256368E+10 | 0.939370E+09 | 0.162431E+10 | 0.213864E+10 | 0.262463E+10 |
April | 0.323893E+10 | 0.143500E+10 | 0.180393E+10 | 0.325164E+10 | 0.186679E+10 |
May | 0.413987E+10 | 0.188800E+10 | 0.225187E+10 | 0.451367E+10 | 0.153491E+10 |
June | 0.435873E+10 | 0.200213E+10 | 0.235660E+10 | 0.528469E+10 | 0.104181E+10 |
July | 0.461387E+10 | 0.233145E+10 | 0.228241E+10 | 0.607095E+10 | 0.903568E+09 |
August | 0.391779E+10 | 0.192277E+10 | 0.199502E+10 | 0.501994E+10 | 0.974542E+09 |
September | 0.304996E+10 | 0.154193E+10 | 0.150802E+10 | 0.359076E+10 | 0.133466E+10 |
October | 0.225254E+10 | 0.111917E+10 | 0.113338E+10 | 0.225816E+10 | 0.193992E+10 |
November | 0.154315E+10 | 0.765533E+09 | 0.777615E+09 | 0.126836E+10 | 0.253735E+10 |
December | 0.107185E+10 | 0.452399E+09 | 0.619454E+09 | 0.615388E+09 | 0.363578E+10 |
Annual Sum or Average | 0.337334E+11 | 0.157602E+11 | 0.179733E+11 | 0.361038E+11 | 0.255741E+11 |
Minimum of Months | 0.107185E+10 | 0.452399E+09 | 0.619454E+09 | 0.615388E+09 | 0.903568E+09 |
Maximum of Months | 0.461387E+10 | 0.233145E+10 | 0.235660E+10 | 0.607095E+10 | 0.434888E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282124E+09 | 0.00 | 0.282124E+09 | 11483782.28 | 0.230671E+10 |
February | 0.359792E+09 | 0.00 | 0.359792E+09 | 76176148.90 | 0.153132E+10 |
March | 0.647089E+09 | 0.00 | 0.647089E+09 | 0.269980E+09 | 0.134959E+10 |
April | 0.714018E+09 | 4166847.54 | 0.709851E+09 | 0.437629E+09 | 0.903841E+09 |
May | 0.968932E+09 | 57415206.47 | 0.911517E+09 | 0.788023E+09 | 0.713017E+09 |
June | 0.109187E+10 | 0.125501E+09 | 0.966370E+09 | 0.116541E+10 | 0.452217E+09 |
July | 0.103073E+10 | 96540600.17 | 0.934193E+09 | 0.129122E+10 | 0.394666E+09 |
August | 0.825932E+09 | 22138846.40 | 0.803794E+09 | 0.940319E+09 | 0.455100E+09 |
September | 0.598612E+09 | 214814.61 | 0.598398E+09 | 0.531995E+09 | 0.686593E+09 |
October | 0.451208E+09 | 0.00 | 0.451208E+09 | 0.214171E+09 | 0.105475E+10 |
November | 0.296841E+09 | 0.00 | 0.296841E+09 | 52683042.55 | 0.142834E+10 |
December | 0.236577E+09 | 0.00 | 0.236577E+09 | 6720504.57 | 0.200097E+10 |
Annual Sum or Average | 0.750373E+10 | 0.305978E+09 | 0.719775E+10 | 0.578581E+10 | 0.132771E+11 |
Minimum of Months | 0.236577E+09 | 0.00 | 0.236577E+09 | 6720504.57 | 0.394666E+09 |
Maximum of Months | 0.109187E+10 | 0.125501E+09 | 0.966370E+09 | 0.129122E+10 | 0.230671E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282135E+09 | 0.00 | 0.282135E+09 | 11483221.66 | 0.230685E+10 |
February | 0.359807E+09 | 0.00 | 0.359807E+09 | 76176545.25 | 0.153142E+10 |
March | 0.647114E+09 | 0.00 | 0.647114E+09 | 0.269982E+09 | 0.134968E+10 |
April | 0.714046E+09 | 4166959.55 | 0.709879E+09 | 0.437640E+09 | 0.903898E+09 |
May | 0.968970E+09 | 57416749.81 | 0.911553E+09 | 0.788045E+09 | 0.713062E+09 |
June | 0.109191E+10 | 0.125505E+09 | 0.966410E+09 | 0.116545E+10 | 0.452244E+09 |
July | 0.103078E+10 | 96543195.21 | 0.934233E+09 | 0.129127E+10 | 0.394688E+09 |
August | 0.825967E+09 | 22139441.50 | 0.803827E+09 | 0.940357E+09 | 0.455126E+09 |
September | 0.598637E+09 | 214820.38 | 0.598422E+09 | 0.532015E+09 | 0.686635E+09 |
October | 0.451226E+09 | 0.00 | 0.451226E+09 | 0.214175E+09 | 0.105482E+10 |
November | 0.296852E+09 | 0.00 | 0.296852E+09 | 52682999.39 | 0.142843E+10 |
December | 0.236586E+09 | 0.00 | 0.236586E+09 | 6720138.46 | 0.200110E+10 |
Annual Sum or Average | 0.750403E+10 | 0.305986E+09 | 0.719805E+10 | 0.578600E+10 | 0.132779E+11 |
Minimum of Months | 0.236586E+09 | 0.00 | 0.236586E+09 | 6720138.46 | 0.394688E+09 |
Maximum of Months | 0.109191E+10 | 0.125505E+09 | 0.966410E+09 | 0.129127E+10 | 0.230685E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282135E+09 | 0.00 | 0.282135E+09 | 11483221.66 | 0.230685E+10 |
February | 0.359807E+09 | 0.00 | 0.359807E+09 | 76176545.25 | 0.153142E+10 |
March | 0.647114E+09 | 0.00 | 0.647114E+09 | 0.269982E+09 | 0.134968E+10 |
April | 0.714046E+09 | 4166959.55 | 0.709879E+09 | 0.437640E+09 | 0.903898E+09 |
May | 0.968970E+09 | 57416749.81 | 0.911553E+09 | 0.788045E+09 | 0.713062E+09 |
June | 0.109191E+10 | 0.125505E+09 | 0.966410E+09 | 0.116545E+10 | 0.452244E+09 |
July | 0.103078E+10 | 96543195.21 | 0.934233E+09 | 0.129127E+10 | 0.394688E+09 |
August | 0.825967E+09 | 22139441.50 | 0.803827E+09 | 0.940357E+09 | 0.455126E+09 |
September | 0.598637E+09 | 214820.38 | 0.598422E+09 | 0.532015E+09 | 0.686635E+09 |
October | 0.451226E+09 | 0.00 | 0.451226E+09 | 0.214175E+09 | 0.105482E+10 |
November | 0.296852E+09 | 0.00 | 0.296852E+09 | 52682999.39 | 0.142843E+10 |
December | 0.236586E+09 | 0.00 | 0.236586E+09 | 6720138.46 | 0.200110E+10 |
Annual Sum or Average | 0.750403E+10 | 0.305986E+09 | 0.719805E+10 | 0.578600E+10 | 0.132779E+11 |
Minimum of Months | 0.236586E+09 | 0.00 | 0.236586E+09 | 6720138.46 | 0.394688E+09 |
Maximum of Months | 0.109191E+10 | 0.125505E+09 | 0.966410E+09 | 0.129127E+10 | 0.230685E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.124643E+10 | 0.571434E+09 | 0.674992E+09 | 0.703464E+09 | 0.410624E+10 |
February | 0.176086E+10 | 0.874221E+09 | 0.886637E+09 | 0.139039E+10 | 0.273816E+10 |
March | 0.262131E+10 | 0.108462E+10 | 0.153669E+10 | 0.225316E+10 | 0.250057E+10 |
April | 0.323664E+10 | 0.160405E+10 | 0.163259E+10 | 0.325899E+10 | 0.173914E+10 |
May | 0.369447E+10 | 0.164380E+10 | 0.205067E+10 | 0.395578E+10 | 0.143800E+10 |
June | 0.462776E+10 | 0.238143E+10 | 0.224633E+10 | 0.564058E+10 | 0.933825E+09 |
July | 0.501886E+10 | 0.283728E+10 | 0.218157E+10 | 0.657489E+10 | 0.805970E+09 |
August | 0.436161E+10 | 0.243015E+10 | 0.193147E+10 | 0.558002E+10 | 0.911107E+09 |
September | 0.298588E+10 | 0.154130E+10 | 0.144459E+10 | 0.345920E+10 | 0.130254E+10 |
October | 0.221362E+10 | 0.112404E+10 | 0.108958E+10 | 0.212870E+10 | 0.196949E+10 |
November | 0.135769E+10 | 0.633862E+09 | 0.723832E+09 | 0.963571E+09 | 0.256213E+10 |
December | 0.103476E+10 | 0.444429E+09 | 0.590328E+09 | 0.547552E+09 | 0.355396E+10 |
Annual Sum or Average | 0.341599E+11 | 0.171706E+11 | 0.169893E+11 | 0.364563E+11 | 0.245611E+11 |
Minimum of Months | 0.103476E+10 | 0.444429E+09 | 0.590328E+09 | 0.547552E+09 | 0.805970E+09 |
Maximum of Months | 0.501886E+10 | 0.283728E+10 | 0.224633E+10 | 0.657489E+10 | 0.410624E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 49282560.53 | 22593984.42 | 26688576.11 | 27814342.32 | 0.162357E+09 |
February | 69622741.96 | 34565919.09 | 35056822.87 | 54974756.00 | 0.108264E+09 |
March | 0.103644E+09 | 42884921.75 | 60759293.88 | 89087772.40 | 98870318.94 |
April | 0.127974E+09 | 63422758.57 | 64551256.57 | 0.128858E+09 | 68764003.59 |
May | 0.146076E+09 | 64994474.23 | 81081693.83 | 0.156408E+09 | 56857241.94 |
June | 0.182977E+09 | 94159662.78 | 88817684.97 | 0.223024E+09 | 36922587.38 |
July | 0.198441E+09 | 0.112184E+09 | 86257492.47 | 0.259965E+09 | 31867315.98 |
August | 0.172454E+09 | 96085787.95 | 76368419.92 | 0.220629E+09 | 36024352.51 |
September | 0.118059E+09 | 60941443.07 | 57117668.76 | 0.136774E+09 | 51501215.08 |
October | 87524590.74 | 44443476.32 | 43081114.42 | 84166703.36 | 77871948.18 |
November | 53681997.10 | 25062350.78 | 28619646.32 | 38098732.35 | 0.101304E+09 |
December | 40913366.01 | 17572326.64 | 23341039.37 | 21649721.13 | 0.140521E+09 |
Annual Sum or Average | 0.135065E+10 | 0.678911E+09 | 0.671741E+09 | 0.144145E+10 | 0.971125E+09 |
Minimum of Months | 40913366.01 | 17572326.64 | 23341039.37 | 21649721.13 | 31867315.98 |
Maximum of Months | 0.198441E+09 | 0.112184E+09 | 88817684.97 | 0.259965E+09 | 0.162357E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198872E+10 | 0.142038E+10 | 0.568338E+09 | 0.193058E+10 | 0.198858E+10 |
February | 0.228751E+10 | 0.164526E+10 | 0.642252E+09 | 0.243518E+10 | 0.137481E+10 |
March | 0.226382E+10 | 0.127125E+10 | 0.992567E+09 | 0.240830E+10 | 0.135572E+10 |
April | 0.176103E+10 | 0.842310E+09 | 0.918725E+09 | 0.194892E+10 | 0.964185E+09 |
May | 0.161679E+10 | 0.536977E+09 | 0.107982E+10 | 0.182345E+10 | 0.787818E+09 |
June | 0.155463E+10 | 0.453399E+09 | 0.110123E+10 | 0.197942E+10 | 0.528772E+09 |
July | 0.173191E+10 | 0.639757E+09 | 0.109215E+10 | 0.243847E+10 | 0.448859E+09 |
August | 0.205826E+10 | 0.103773E+10 | 0.102053E+10 | 0.280785E+10 | 0.513093E+09 |
September | 0.220921E+10 | 0.135365E+10 | 0.855561E+09 | 0.279020E+10 | 0.728056E+09 |
October | 0.238660E+10 | 0.165030E+10 | 0.736299E+09 | 0.276664E+10 | 0.106633E+10 |
November | 0.210568E+10 | 0.152527E+10 | 0.580412E+09 | 0.223523E+10 | 0.129463E+10 |
December | 0.189116E+10 | 0.136561E+10 | 0.525553E+09 | 0.186732E+10 | 0.172955E+10 |
Annual Sum or Average | 0.238553E+11 | 0.137419E+11 | 0.101134E+11 | 0.274316E+11 | 0.127804E+11 |
Minimum of Months | 0.155463E+10 | 0.453399E+09 | 0.525553E+09 | 0.182345E+10 | 0.448859E+09 |
Maximum of Months | 0.238660E+10 | 0.165030E+10 | 0.110123E+10 | 0.280785E+10 | 0.198858E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198872E+10 | 0.142038E+10 | 0.568338E+09 | 0.193058E+10 | 0.198858E+10 |
February | 0.228751E+10 | 0.164526E+10 | 0.642252E+09 | 0.243518E+10 | 0.137481E+10 |
March | 0.226382E+10 | 0.127125E+10 | 0.992567E+09 | 0.240830E+10 | 0.135572E+10 |
April | 0.176103E+10 | 0.842310E+09 | 0.918725E+09 | 0.194892E+10 | 0.964185E+09 |
May | 0.161679E+10 | 0.536977E+09 | 0.107982E+10 | 0.182345E+10 | 0.787818E+09 |
June | 0.155463E+10 | 0.453399E+09 | 0.110123E+10 | 0.197942E+10 | 0.528772E+09 |
July | 0.173191E+10 | 0.639757E+09 | 0.109215E+10 | 0.243847E+10 | 0.448859E+09 |
August | 0.205826E+10 | 0.103773E+10 | 0.102053E+10 | 0.280785E+10 | 0.513093E+09 |
September | 0.220921E+10 | 0.135365E+10 | 0.855561E+09 | 0.279020E+10 | 0.728056E+09 |
October | 0.238660E+10 | 0.165030E+10 | 0.736299E+09 | 0.276664E+10 | 0.106633E+10 |
November | 0.210568E+10 | 0.152527E+10 | 0.580412E+09 | 0.223523E+10 | 0.129463E+10 |
December | 0.189116E+10 | 0.136561E+10 | 0.525553E+09 | 0.186732E+10 | 0.172955E+10 |
Annual Sum or Average | 0.238553E+11 | 0.137419E+11 | 0.101134E+11 | 0.274316E+11 | 0.127804E+11 |
Minimum of Months | 0.155463E+10 | 0.453399E+09 | 0.525553E+09 | 0.182345E+10 | 0.448859E+09 |
Maximum of Months | 0.238660E+10 | 0.165030E+10 | 0.110123E+10 | 0.280785E+10 | 0.198858E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198859E+10 | 0.142029E+10 | 0.568302E+09 | 0.193045E+10 | 0.198846E+10 |
February | 0.228737E+10 | 0.164516E+10 | 0.642211E+09 | 0.243502E+10 | 0.137473E+10 |
March | 0.226368E+10 | 0.127117E+10 | 0.992505E+09 | 0.240815E+10 | 0.135564E+10 |
April | 0.176092E+10 | 0.842257E+09 | 0.918667E+09 | 0.194880E+10 | 0.964124E+09 |
May | 0.161669E+10 | 0.536943E+09 | 0.107975E+10 | 0.182333E+10 | 0.787769E+09 |
June | 0.155453E+10 | 0.453371E+09 | 0.110116E+10 | 0.197930E+10 | 0.528739E+09 |
July | 0.173180E+10 | 0.639717E+09 | 0.109209E+10 | 0.243832E+10 | 0.448831E+09 |
August | 0.205813E+10 | 0.103767E+10 | 0.102046E+10 | 0.280768E+10 | 0.513061E+09 |
September | 0.220907E+10 | 0.135356E+10 | 0.855507E+09 | 0.279003E+10 | 0.728010E+09 |
October | 0.238644E+10 | 0.165019E+10 | 0.736253E+09 | 0.276647E+10 | 0.106627E+10 |
November | 0.210554E+10 | 0.152517E+10 | 0.580375E+09 | 0.223509E+10 | 0.129455E+10 |
December | 0.189104E+10 | 0.136552E+10 | 0.525520E+09 | 0.186720E+10 | 0.172944E+10 |
Annual Sum or Average | 0.238538E+11 | 0.137410E+11 | 0.101128E+11 | 0.274298E+11 | 0.127796E+11 |
Minimum of Months | 0.155453E+10 | 0.453371E+09 | 0.525520E+09 | 0.182333E+10 | 0.448831E+09 |
Maximum of Months | 0.238644E+10 | 0.165019E+10 | 0.110116E+10 | 0.280768E+10 | 0.198846E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112900E+10 | 0.454994E+09 | 0.674006E+09 | 0.617883E+09 | 0.426318E+10 |
February | 0.174055E+10 | 0.855565E+09 | 0.884982E+09 | 0.141298E+10 | 0.281169E+10 |
March | 0.246614E+10 | 0.903626E+09 | 0.156251E+10 | 0.209245E+10 | 0.259898E+10 |
April | 0.311570E+10 | 0.138039E+10 | 0.173530E+10 | 0.317720E+10 | 0.183434E+10 |
May | 0.398236E+10 | 0.181616E+10 | 0.216619E+10 | 0.438813E+10 | 0.153511E+10 |
June | 0.419289E+10 | 0.192594E+10 | 0.226695E+10 | 0.513019E+10 | 0.103252E+10 |
July | 0.443832E+10 | 0.224274E+10 | 0.219558E+10 | 0.587404E+10 | 0.905447E+09 |
August | 0.376873E+10 | 0.184961E+10 | 0.191912E+10 | 0.485306E+10 | 0.985961E+09 |
September | 0.293391E+10 | 0.148326E+10 | 0.145065E+10 | 0.345588E+10 | 0.139280E+10 |
October | 0.216684E+10 | 0.107658E+10 | 0.109026E+10 | 0.214001E+10 | 0.207097E+10 |
November | 0.148443E+10 | 0.736404E+09 | 0.748030E+09 | 0.119807E+10 | 0.265975E+10 |
December | 0.103107E+10 | 0.435185E+09 | 0.595886E+09 | 0.589348E+09 | 0.366016E+10 |
Annual Sum or Average | 0.324499E+11 | 0.151605E+11 | 0.172895E+11 | 0.349292E+11 | 0.257509E+11 |
Minimum of Months | 0.103107E+10 | 0.435185E+09 | 0.595886E+09 | 0.589348E+09 | 0.905447E+09 |
Maximum of Months | 0.443832E+10 | 0.224274E+10 | 0.226695E+10 | 0.587404E+10 | 0.426318E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44639550.14 | 17990008.39 | 26649541.75 | 24430432.22 | 0.168562E+09 |
February | 68819454.54 | 33828143.04 | 34991311.50 | 55867896.69 | 0.111172E+09 |
March | 97508508.38 | 35728456.44 | 61780051.94 | 82733166.99 | 0.102761E+09 |
April | 0.123191E+09 | 54579328.96 | 68612164.61 | 0.125623E+09 | 72528314.74 |
May | 0.157458E+09 | 71809164.42 | 85649193.40 | 0.173502E+09 | 60696851.53 |
June | 0.165783E+09 | 76149843.14 | 89632786.20 | 0.202842E+09 | 40824970.42 |
July | 0.175487E+09 | 88675655.80 | 86811074.97 | 0.232254E+09 | 35800550.58 |
August | 0.149012E+09 | 73131587.33 | 75880294.79 | 0.191885E+09 | 38984009.80 |
September | 0.116004E+09 | 58646641.15 | 57357250.15 | 0.136642E+09 | 55070048.08 |
October | 85674584.70 | 42566934.75 | 43107649.96 | 84613900.38 | 81884115.81 |
November | 58692998.15 | 29116645.43 | 29576352.72 | 47370404.77 | 0.105164E+09 |
December | 40767505.90 | 17206757.42 | 23560748.48 | 23302161.65 | 0.144719E+09 |
Annual Sum or Average | 0.128304E+10 | 0.599429E+09 | 0.683608E+09 | 0.138107E+10 | 0.101817E+10 |
Minimum of Months | 40767505.90 | 17206757.42 | 23560748.48 | 23302161.65 | 35800550.58 |
Maximum of Months | 0.175487E+09 | 88675655.80 | 89632786.20 | 0.232254E+09 | 0.168562E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.846413E+09 | 0.00 | 0.846413E+09 | 32493535.68 | 0.699603E+10 |
February | 0.107943E+10 | 0.00 | 0.107943E+10 | 0.207660E+09 | 0.468334E+10 |
March | 0.194136E+10 | 0.00 | 0.194136E+10 | 0.732007E+09 | 0.419223E+10 |
April | 0.214215E+10 | 12501134.09 | 0.212965E+10 | 0.118218E+10 | 0.290673E+10 |
May | 0.290693E+10 | 0.172254E+09 | 0.273468E+10 | 0.222228E+10 | 0.225189E+10 |
June | 0.327577E+10 | 0.376522E+09 | 0.289925E+10 | 0.339916E+10 | 0.141865E+10 |
July | 0.309235E+10 | 0.289636E+09 | 0.280271E+10 | 0.380878E+10 | 0.122813E+10 |
August | 0.247791E+10 | 66419681.66 | 0.241150E+10 | 0.277330E+10 | 0.140505E+10 |
September | 0.179592E+10 | 644474.31 | 0.179528E+10 | 0.156404E+10 | 0.208083E+10 |
October | 0.135369E+10 | 0.00 | 0.135369E+10 | 0.632423E+09 | 0.313854E+10 |
November | 0.890565E+09 | 0.00 | 0.890565E+09 | 0.154357E+09 | 0.425125E+10 |
December | 0.709765E+09 | 0.00 | 0.709765E+09 | 18336345.70 | 0.598759E+10 |
Annual Sum or Average | 0.225123E+11 | 0.917976E+09 | 0.215943E+11 | 0.167270E+11 | 0.405402E+11 |
Minimum of Months | 0.709765E+09 | 0.00 | 0.709765E+09 | 18336345.70 | 0.122813E+10 |
Maximum of Months | 0.327577E+10 | 0.376522E+09 | 0.289925E+10 | 0.380878E+10 | 0.699603E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129573E+10 | 0.594040E+09 | 0.701690E+09 | 0.718984E+09 | 0.428603E+10 |
February | 0.183051E+10 | 0.908805E+09 | 0.921705E+09 | 0.141368E+10 | 0.287642E+10 |
March | 0.272500E+10 | 0.112753E+10 | 0.159747E+10 | 0.227508E+10 | 0.264969E+10 |
April | 0.336467E+10 | 0.166751E+10 | 0.169717E+10 | 0.330813E+10 | 0.187121E+10 |
May | 0.384061E+10 | 0.170883E+10 | 0.213178E+10 | 0.404050E+10 | 0.152601E+10 |
June | 0.481081E+10 | 0.247564E+10 | 0.233517E+10 | 0.581131E+10 | 0.978716E+09 |
July | 0.521738E+10 | 0.294953E+10 | 0.226786E+10 | 0.679887E+10 | 0.828438E+09 |
August | 0.453414E+10 | 0.252628E+10 | 0.200786E+10 | 0.576807E+10 | 0.934889E+09 |
September | 0.310399E+10 | 0.160227E+10 | 0.150172E+10 | 0.357387E+10 | 0.132356E+10 |
October | 0.230118E+10 | 0.116850E+10 | 0.113268E+10 | 0.220251E+10 | 0.198576E+10 |
November | 0.141140E+10 | 0.658938E+09 | 0.752461E+09 | 0.997796E+09 | 0.261036E+10 |
December | 0.107569E+10 | 0.462010E+09 | 0.613678E+09 | 0.563782E+09 | 0.367040E+10 |
Annual Sum or Average | 0.355111E+11 | 0.178499E+11 | 0.176612E+11 | 0.374726E+11 | 0.255415E+11 |
Minimum of Months | 0.107569E+10 | 0.462010E+09 | 0.613678E+09 | 0.563782E+09 | 0.828438E+09 |
Maximum of Months | 0.521738E+10 | 0.294953E+10 | 0.233517E+10 | 0.679887E+10 | 0.428603E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.596627E+10 | 0.426123E+10 | 0.170504E+10 | 0.568666E+10 | 0.603340E+10 |
February | 0.686267E+10 | 0.493589E+10 | 0.192678E+10 | 0.718453E+10 | 0.412099E+10 |
March | 0.679158E+10 | 0.381384E+10 | 0.297774E+10 | 0.708186E+10 | 0.410882E+10 |
April | 0.528318E+10 | 0.252698E+10 | 0.275620E+10 | 0.570872E+10 | 0.300170E+10 |
May | 0.485044E+10 | 0.161096E+10 | 0.323948E+10 | 0.532564E+10 | 0.245971E+10 |
June | 0.466394E+10 | 0.136023E+10 | 0.330371E+10 | 0.583279E+10 | 0.164888E+10 |
July | 0.519580E+10 | 0.191931E+10 | 0.327649E+10 | 0.725630E+10 | 0.135948E+10 |
August | 0.617486E+10 | 0.311326E+10 | 0.306161E+10 | 0.837109E+10 | 0.152819E+10 |
September | 0.662774E+10 | 0.406103E+10 | 0.256671E+10 | 0.832185E+10 | 0.211515E+10 |
October | 0.715991E+10 | 0.495099E+10 | 0.220892E+10 | 0.825721E+10 | 0.305396E+10 |
November | 0.631715E+10 | 0.457589E+10 | 0.174126E+10 | 0.666268E+10 | 0.375499E+10 |
December | 0.567359E+10 | 0.409690E+10 | 0.157668E+10 | 0.553847E+10 | 0.515624E+10 |
Annual Sum or Average | 0.715671E+11 | 0.412265E+11 | 0.303406E+11 | 0.812278E+11 | 0.383415E+11 |
Minimum of Months | 0.466394E+10 | 0.136023E+10 | 0.157668E+10 | 0.532564E+10 | 0.135948E+10 |
Maximum of Months | 0.715991E+10 | 0.495099E+10 | 0.330371E+10 | 0.837109E+10 | 0.603340E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117366E+10 | 0.472992E+09 | 0.700664E+09 | 0.627945E+09 | 0.446720E+10 |
February | 0.180939E+10 | 0.889407E+09 | 0.919983E+09 | 0.143396E+10 | 0.295513E+10 |
March | 0.256368E+10 | 0.939370E+09 | 0.162431E+10 | 0.210951E+10 | 0.276298E+10 |
April | 0.323893E+10 | 0.143500E+10 | 0.180393E+10 | 0.322183E+10 | 0.198055E+10 |
May | 0.413987E+10 | 0.188800E+10 | 0.225187E+10 | 0.449617E+10 | 0.161935E+10 |
June | 0.435873E+10 | 0.200213E+10 | 0.235660E+10 | 0.528363E+10 | 0.108388E+10 |
July | 0.461387E+10 | 0.233145E+10 | 0.228241E+10 | 0.607586E+10 | 0.933546E+09 |
August | 0.391779E+10 | 0.192277E+10 | 0.199502E+10 | 0.501927E+10 | 0.101591E+10 |
September | 0.304996E+10 | 0.154193E+10 | 0.150802E+10 | 0.357522E+10 | 0.141549E+10 |
October | 0.225254E+10 | 0.111917E+10 | 0.113338E+10 | 0.221943E+10 | 0.208843E+10 |
November | 0.154315E+10 | 0.765533E+09 | 0.777615E+09 | 0.123784E+10 | 0.270993E+10 |
December | 0.107185E+10 | 0.452399E+09 | 0.619454E+09 | 0.602187E+09 | 0.378451E+10 |
Annual Sum or Average | 0.337334E+11 | 0.157602E+11 | 0.179733E+11 | 0.359028E+11 | 0.268169E+11 |
Minimum of Months | 0.107185E+10 | 0.452399E+09 | 0.619454E+09 | 0.602187E+09 | 0.933546E+09 |
Maximum of Months | 0.461387E+10 | 0.233145E+10 | 0.235660E+10 | 0.607586E+10 | 0.446720E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 14.99 | 2540.92 | 316.01 | 0.00 | 316.01 | 0.00 | 0.00 |
February | 95.74 | 1857.56 | 446.19 | 0.00 | 446.19 | 0.00 | 0.00 |
March | 289.89 | 1487.17 | 724.82 | 0.00 | 724.82 | 0.00 | 0.00 |
April | 474.28 | 1053.89 | 826.45 | 4.82 | 821.63 | 0.00 | 0.00 |
May | 845.06 | 795.64 | 1085.32 | 64.31 | 1021.01 | 0.00 | 0.00 |
June | 1317.98 | 528.03 | 1263.80 | 145.26 | 1118.54 | 0.00 | 0.00 |
July | 1423.33 | 445.54 | 1154.55 | 108.14 | 1046.41 | 0.00 | 0.00 |
August | 1039.73 | 503.29 | 925.15 | 24.80 | 900.35 | 0.00 | 0.00 |
September | 614.86 | 755.21 | 692.87 | 0.25 | 692.62 | 0.00 | 0.00 |
October | 258.44 | 1086.11 | 505.41 | 0.00 | 505.41 | 0.00 | 0.00 |
November | 70.24 | 1534.23 | 343.58 | 0.00 | 343.58 | 0.00 | 0.00 |
December | 8.08 | 2148.23 | 265.00 | 0.00 | 265.00 | 0.00 | 0.00 |
Annual Sum or Average | 540.46 | 1225.66 | 713.86 | 29.11 | 684.75 | 0.00 | 0.00 |
Minimum of Months | 8.08 | 445.54 | 265.00 | 0.00 | 265.00 | 0.00 | 0.00 |
Maximum of Months | 1423.33 | 2540.92 | 1263.80 | 145.26 | 1118.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 274.20 | 1559.41 | 483.77 | 221.79 | 261.98 | 0.00 | 0.00 |
February | 597.50 | 1140.95 | 756.66 | 375.66 | 381.00 | 0.00 | 0.00 |
March | 866.12 | 939.80 | 1017.40 | 420.97 | 596.43 | 0.00 | 0.00 |
April | 1291.37 | 680.56 | 1298.10 | 643.33 | 654.77 | 0.00 | 0.00 |
May | 1519.04 | 540.77 | 1433.92 | 638.00 | 795.92 | 0.00 | 0.00 |
June | 2246.49 | 365.09 | 1856.02 | 955.11 | 900.91 | 0.00 | 0.00 |
July | 2540.00 | 300.48 | 1947.95 | 1101.23 | 846.72 | 0.00 | 0.00 |
August | 2157.33 | 336.08 | 1692.85 | 943.21 | 749.65 | 0.00 | 0.00 |
September | 1388.47 | 483.30 | 1197.53 | 618.16 | 579.37 | 0.00 | 0.00 |
October | 841.69 | 690.11 | 859.16 | 436.27 | 422.89 | 0.00 | 0.00 |
November | 402.01 | 942.73 | 544.52 | 254.22 | 290.30 | 0.00 | 0.00 |
December | 217.32 | 1317.01 | 401.62 | 172.49 | 229.12 | 0.00 | 0.00 |
Annual Sum or Average | 1198.54 | 773.40 | 1126.05 | 566.02 | 560.03 | 0.00 | 0.00 |
Minimum of Months | 217.32 | 300.48 | 401.62 | 172.49 | 229.12 | 0.00 | 0.00 |
Maximum of Months | 2540.00 | 1559.41 | 1947.95 | 1101.23 | 900.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2136.65 | 2184.16 | 2227.55 | 1590.96 | 636.59 | 0.00 | 0.00 |
February | 2988.33 | 1629.03 | 2836.75 | 2040.30 | 796.45 | 0.00 | 0.00 |
March | 2661.85 | 1457.18 | 2535.68 | 1423.92 | 1111.76 | 0.00 | 0.00 |
April | 2217.02 | 1092.48 | 2038.27 | 974.92 | 1063.35 | 0.00 | 0.00 |
May | 1997.25 | 870.68 | 1810.95 | 601.47 | 1209.48 | 0.00 | 0.00 |
June | 2250.90 | 611.49 | 1799.36 | 524.78 | 1274.58 | 0.00 | 0.00 |
July | 2706.28 | 490.76 | 1939.89 | 716.59 | 1223.30 | 0.00 | 0.00 |
August | 3124.00 | 547.38 | 2305.43 | 1162.36 | 1143.07 | 0.00 | 0.00 |
September | 3216.58 | 772.20 | 2557.00 | 1566.76 | 990.24 | 0.00 | 0.00 |
October | 3102.44 | 1064.28 | 2673.21 | 1848.49 | 824.72 | 0.00 | 0.00 |
November | 2598.73 | 1358.81 | 2437.17 | 1765.39 | 671.78 | 0.00 | 0.00 |
December | 2087.95 | 1842.69 | 2118.27 | 1529.61 | 588.67 | 0.00 | 0.00 |
Annual Sum or Average | 2587.62 | 1158.45 | 2269.38 | 1307.28 | 962.09 | 0.00 | 0.00 |
Minimum of Months | 1997.25 | 490.76 | 1799.36 | 524.78 | 588.67 | 0.00 | 0.00 |
Maximum of Months | 3216.58 | 2184.16 | 2836.75 | 2040.30 | 1274.58 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 237.93 | 1623.69 | 438.19 | 176.60 | 261.60 | 0.00 | 0.00 |
February | 601.18 | 1170.32 | 747.93 | 367.65 | 380.28 | 0.00 | 0.00 |
March | 798.48 | 979.92 | 957.17 | 350.72 | 606.45 | 0.00 | 0.00 |
April | 1254.49 | 720.21 | 1249.59 | 553.63 | 695.96 | 0.00 | 0.00 |
May | 1685.21 | 573.07 | 1545.65 | 704.90 | 840.75 | 0.00 | 0.00 |
June | 2038.85 | 401.93 | 1681.61 | 772.43 | 909.18 | 0.00 | 0.00 |
July | 2266.63 | 337.35 | 1722.62 | 870.47 | 852.15 | 0.00 | 0.00 |
August | 1874.23 | 363.85 | 1462.74 | 717.88 | 744.86 | 0.00 | 0.00 |
September | 1385.32 | 514.91 | 1176.68 | 594.88 | 581.80 | 0.00 | 0.00 |
October | 843.10 | 724.28 | 841.00 | 417.85 | 423.15 | 0.00 | 0.00 |
November | 489.34 | 978.92 | 595.35 | 295.34 | 300.01 | 0.00 | 0.00 |
December | 229.76 | 1357.44 | 400.18 | 168.91 | 231.28 | 0.00 | 0.00 |
Annual Sum or Average | 1144.85 | 810.95 | 1069.68 | 499.75 | 569.93 | 0.00 | 0.00 |
Minimum of Months | 229.76 | 337.35 | 400.18 | 168.91 | 231.28 | 0.00 | 0.00 |
Maximum of Months | 2266.63 | 1623.69 | 1722.62 | 870.47 | 909.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 12.86 | 2583.79 | 316.01 | 0.00 | 316.01 | 0.00 | 0.00 |
February | 94.46 | 1899.04 | 446.18 | 0.00 | 446.18 | 0.00 | 0.00 |
March | 302.40 | 1511.70 | 724.80 | 0.00 | 724.80 | 0.00 | 0.00 |
April | 506.52 | 1046.16 | 826.43 | 4.82 | 821.61 | 0.00 | 0.00 |
May | 882.66 | 798.66 | 1085.30 | 64.31 | 1020.99 | 0.00 | 0.00 |
June | 1348.89 | 523.42 | 1263.77 | 145.26 | 1118.51 | 0.00 | 0.00 |
July | 1446.30 | 442.07 | 1154.53 | 108.13 | 1046.39 | 0.00 | 0.00 |
August | 1053.25 | 509.76 | 925.13 | 24.80 | 900.33 | 0.00 | 0.00 |
September | 615.75 | 794.70 | 692.86 | 0.25 | 692.61 | 0.00 | 0.00 |
October | 239.89 | 1181.45 | 505.40 | 0.00 | 505.40 | 0.00 | 0.00 |
November | 60.98 | 1653.24 | 343.57 | 0.00 | 343.57 | 0.00 | 0.00 |
December | 7.53 | 2241.33 | 264.99 | 0.00 | 264.99 | 0.00 | 0.00 |
Annual Sum or Average | 550.41 | 1263.10 | 713.84 | 29.11 | 684.74 | 0.00 | 0.00 |
Minimum of Months | 7.53 | 442.07 | 264.99 | 0.00 | 264.99 | 0.00 | 0.00 |
Maximum of Months | 1446.30 | 2583.79 | 1263.77 | 145.26 | 1118.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 273.03 | 1593.71 | 483.76 | 221.78 | 261.98 | 0.00 | 0.00 |
February | 597.46 | 1176.60 | 756.65 | 375.66 | 380.99 | 0.00 | 0.00 |
March | 874.49 | 970.52 | 1017.38 | 420.96 | 596.42 | 0.00 | 0.00 |
April | 1307.04 | 697.49 | 1298.08 | 643.32 | 654.76 | 0.00 | 0.00 |
May | 1535.31 | 558.12 | 1433.90 | 637.99 | 795.91 | 0.00 | 0.00 |
June | 2262.19 | 374.52 | 1855.99 | 955.09 | 900.90 | 0.00 | 0.00 |
July | 2551.84 | 312.81 | 1947.92 | 1101.21 | 846.71 | 0.00 | 0.00 |
August | 2165.71 | 353.62 | 1692.83 | 943.19 | 749.64 | 0.00 | 0.00 |
September | 1387.34 | 522.39 | 1197.51 | 618.15 | 579.36 | 0.00 | 0.00 |
October | 826.19 | 764.40 | 859.15 | 436.26 | 422.89 | 0.00 | 0.00 |
November | 386.45 | 1027.56 | 544.51 | 254.21 | 290.30 | 0.00 | 0.00 |
December | 212.52 | 1379.36 | 401.61 | 172.49 | 229.12 | 0.00 | 0.00 |
Annual Sum or Average | 1201.73 | 809.62 | 1126.03 | 566.00 | 560.03 | 0.00 | 0.00 |
Minimum of Months | 212.52 | 312.81 | 401.61 | 172.49 | 229.12 | 0.00 | 0.00 |
Maximum of Months | 2551.84 | 1593.71 | 1947.92 | 1101.21 | 900.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2162.34 | 2227.31 | 2227.46 | 1590.89 | 636.57 | 0.00 | 0.00 |
February | 3019.75 | 1704.84 | 2836.64 | 2040.21 | 796.43 | 0.00 | 0.00 |
March | 2697.42 | 1518.47 | 2535.59 | 1423.87 | 1111.72 | 0.00 | 0.00 |
April | 2255.65 | 1115.93 | 2038.19 | 974.88 | 1063.32 | 0.00 | 0.00 |
May | 2042.35 | 882.39 | 1810.89 | 601.44 | 1209.45 | 0.00 | 0.00 |
June | 2290.95 | 611.99 | 1799.30 | 524.76 | 1274.54 | 0.00 | 0.00 |
July | 2731.21 | 502.74 | 1939.82 | 716.56 | 1223.27 | 0.00 | 0.00 |
August | 3144.93 | 574.69 | 2305.35 | 1162.31 | 1143.04 | 0.00 | 0.00 |
September | 3229.33 | 842.64 | 2556.90 | 1566.69 | 990.21 | 0.00 | 0.00 |
October | 3098.77 | 1194.34 | 2673.10 | 1848.41 | 824.69 | 0.00 | 0.00 |
November | 2587.02 | 1498.38 | 2437.08 | 1765.32 | 671.76 | 0.00 | 0.00 |
December | 2091.49 | 1937.18 | 2118.19 | 1529.54 | 588.64 | 0.00 | 0.00 |
Annual Sum or Average | 2609.49 | 1215.77 | 2269.29 | 1307.23 | 962.06 | 0.00 | 0.00 |
Minimum of Months | 2042.35 | 502.74 | 1799.30 | 524.76 | 588.64 | 0.00 | 0.00 |
Maximum of Months | 3229.33 | 2227.31 | 2836.64 | 2040.21 | 1274.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 239.81 | 1654.62 | 438.19 | 176.59 | 261.59 | 0.00 | 0.00 |
February | 607.16 | 1208.19 | 747.92 | 367.64 | 380.28 | 0.00 | 0.00 |
March | 812.12 | 1008.71 | 957.15 | 350.71 | 606.44 | 0.00 | 0.00 |
April | 1274.24 | 735.68 | 1249.57 | 553.62 | 695.95 | 0.00 | 0.00 |
May | 1703.12 | 595.81 | 1545.63 | 704.89 | 840.74 | 0.00 | 0.00 |
June | 2057.50 | 414.10 | 1681.59 | 772.41 | 909.17 | 0.00 | 0.00 |
July | 2279.83 | 351.42 | 1722.60 | 870.45 | 852.15 | 0.00 | 0.00 |
August | 1883.57 | 382.67 | 1462.72 | 717.87 | 744.85 | 0.00 | 0.00 |
September | 1386.00 | 558.59 | 1176.66 | 594.87 | 581.79 | 0.00 | 0.00 |
October | 830.58 | 803.78 | 840.99 | 417.84 | 423.15 | 0.00 | 0.00 |
November | 480.49 | 1066.71 | 595.34 | 295.34 | 300.00 | 0.00 | 0.00 |
December | 228.74 | 1420.58 | 400.18 | 168.90 | 231.28 | 0.00 | 0.00 |
Annual Sum or Average | 1151.39 | 848.84 | 1069.67 | 499.74 | 569.92 | 0.00 | 0.00 |
Minimum of Months | 228.74 | 351.42 | 400.18 | 168.90 | 231.28 | 0.00 | 0.00 |
Maximum of Months | 2279.83 | 1654.62 | 1722.60 | 870.45 | 909.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 12.13 | 2612.02 | 316.01 | 0.00 | 316.01 | 0.00 | 0.00 |
February | 85.84 | 1935.90 | 446.19 | 0.00 | 446.19 | 0.00 | 0.00 |
March | 273.30 | 1565.20 | 724.82 | 0.00 | 724.82 | 0.00 | 0.00 |
April | 456.09 | 1121.42 | 826.45 | 4.82 | 821.63 | 0.00 | 0.00 |
May | 829.71 | 840.76 | 1085.32 | 64.31 | 1021.01 | 0.00 | 0.00 |
June | 1311.40 | 547.32 | 1263.80 | 145.26 | 1118.54 | 0.00 | 0.00 |
July | 1422.03 | 458.53 | 1154.55 | 108.14 | 1046.41 | 0.00 | 0.00 |
August | 1035.43 | 524.59 | 925.15 | 24.80 | 900.35 | 0.00 | 0.00 |
September | 603.41 | 802.79 | 692.87 | 0.25 | 692.62 | 0.00 | 0.00 |
October | 236.12 | 1171.80 | 505.41 | 0.00 | 505.41 | 0.00 | 0.00 |
November | 59.55 | 1640.14 | 343.58 | 0.00 | 343.58 | 0.00 | 0.00 |
December | 6.85 | 2235.51 | 265.00 | 0.00 | 265.00 | 0.00 | 0.00 |
Annual Sum or Average | 530.41 | 1285.52 | 713.86 | 29.11 | 684.75 | 0.00 | 0.00 |
Minimum of Months | 6.85 | 458.53 | 265.00 | 0.00 | 265.00 | 0.00 | 0.00 |
Maximum of Months | 1422.03 | 2612.02 | 1263.80 | 145.26 | 1118.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 268.44 | 1600.22 | 483.77 | 221.79 | 261.98 | 0.00 | 0.00 |
February | 584.36 | 1189.00 | 756.66 | 375.66 | 381.00 | 0.00 | 0.00 |
March | 849.42 | 989.28 | 1017.40 | 420.97 | 596.43 | 0.00 | 0.00 |
April | 1276.29 | 721.92 | 1298.10 | 643.33 | 654.77 | 0.00 | 0.00 |
May | 1508.55 | 569.75 | 1433.92 | 638.00 | 795.92 | 0.00 | 0.00 |
June | 2242.02 | 377.59 | 1856.02 | 955.11 | 900.91 | 0.00 | 0.00 |
July | 2538.41 | 309.30 | 1947.95 | 1101.23 | 846.72 | 0.00 | 0.00 |
August | 2153.55 | 349.05 | 1692.85 | 943.21 | 749.65 | 0.00 | 0.00 |
September | 1378.81 | 510.63 | 1197.53 | 618.16 | 579.37 | 0.00 | 0.00 |
October | 822.32 | 741.40 | 859.16 | 436.27 | 422.89 | 0.00 | 0.00 |
November | 384.95 | 1007.08 | 544.52 | 254.22 | 290.30 | 0.00 | 0.00 |
December | 210.49 | 1370.37 | 401.62 | 172.49 | 229.12 | 0.00 | 0.00 |
Annual Sum or Average | 1188.25 | 809.92 | 1126.05 | 566.02 | 560.03 | 0.00 | 0.00 |
Minimum of Months | 210.49 | 309.30 | 401.62 | 172.49 | 229.12 | 0.00 | 0.00 |
Maximum of Months | 2538.41 | 1600.22 | 1947.95 | 1101.23 | 900.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2123.15 | 2252.62 | 2227.55 | 1590.96 | 636.59 | 0.00 | 0.00 |
February | 2969.80 | 1703.45 | 2836.75 | 2040.30 | 796.45 | 0.00 | 0.00 |
March | 2644.06 | 1534.06 | 2535.68 | 1423.92 | 1111.76 | 0.00 | 0.00 |
April | 2202.44 | 1158.06 | 2038.27 | 974.92 | 1063.35 | 0.00 | 0.00 |
May | 1988.36 | 918.35 | 1810.95 | 601.47 | 1209.48 | 0.00 | 0.00 |
June | 2250.31 | 636.14 | 1799.36 | 524.78 | 1274.58 | 0.00 | 0.00 |
July | 2709.19 | 507.57 | 1939.89 | 716.59 | 1223.30 | 0.00 | 0.00 |
August | 3125.41 | 570.56 | 2305.43 | 1162.36 | 1143.07 | 0.00 | 0.00 |
September | 3210.59 | 816.03 | 2557.00 | 1566.76 | 990.24 | 0.00 | 0.00 |
October | 3082.89 | 1140.22 | 2673.21 | 1848.49 | 824.72 | 0.00 | 0.00 |
November | 2570.48 | 1448.68 | 2437.17 | 1765.39 | 671.78 | 0.00 | 0.00 |
December | 2067.83 | 1925.12 | 2118.27 | 1529.61 | 588.67 | 0.00 | 0.00 |
Annual Sum or Average | 2575.72 | 1215.80 | 2269.38 | 1307.28 | 962.09 | 0.00 | 0.00 |
Minimum of Months | 1988.36 | 507.57 | 1799.36 | 524.78 | 588.67 | 0.00 | 0.00 |
Maximum of Months | 3210.59 | 2252.62 | 2836.75 | 2040.30 | 1274.58 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 234.45 | 1667.86 | 438.19 | 176.60 | 261.60 | 0.00 | 0.00 |
February | 592.74 | 1221.53 | 747.93 | 367.65 | 380.28 | 0.00 | 0.00 |
March | 787.60 | 1031.58 | 957.17 | 350.72 | 606.45 | 0.00 | 0.00 |
April | 1242.99 | 764.10 | 1249.59 | 553.63 | 695.96 | 0.00 | 0.00 |
May | 1678.68 | 604.60 | 1545.65 | 704.90 | 840.75 | 0.00 | 0.00 |
June | 2038.44 | 418.16 | 1681.61 | 772.43 | 909.18 | 0.00 | 0.00 |
July | 2268.47 | 348.55 | 1722.62 | 870.47 | 852.15 | 0.00 | 0.00 |
August | 1873.98 | 379.30 | 1462.74 | 717.88 | 744.86 | 0.00 | 0.00 |
September | 1379.33 | 546.10 | 1176.68 | 594.88 | 581.80 | 0.00 | 0.00 |
October | 828.64 | 779.73 | 841.00 | 417.85 | 423.15 | 0.00 | 0.00 |
November | 477.56 | 1045.50 | 595.35 | 295.34 | 300.01 | 0.00 | 0.00 |
December | 224.83 | 1412.97 | 400.18 | 168.91 | 231.28 | 0.00 | 0.00 |
Annual Sum or Average | 1138.47 | 850.36 | 1069.68 | 499.75 | 569.93 | 0.00 | 0.00 |
Minimum of Months | 224.83 | 348.55 | 400.18 | 168.91 | 231.28 | 0.00 | 0.00 |
Maximum of Months | 2268.47 | 1667.86 | 1722.62 | 870.47 | 909.18 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 40139495.35 | 0.680561E+10 | 0.846413E+09 | 0.00 | 0.846413E+09 | 0.00 | 0.00 |
February | 0.231618E+09 | 0.449380E+10 | 0.107943E+10 | 0.00 | 0.107943E+10 | 0.00 | 0.00 |
March | 0.776445E+09 | 0.398324E+10 | 0.194136E+10 | 0.00 | 0.194136E+10 | 0.00 | 0.00 |
April | 0.122933E+10 | 0.273168E+10 | 0.214215E+10 | 12501134.09 | 0.212965E+10 | 0.00 | 0.00 |
May | 0.226340E+10 | 0.213103E+10 | 0.290693E+10 | 0.172254E+09 | 0.273468E+10 | 0.00 | 0.00 |
June | 0.341621E+10 | 0.136865E+10 | 0.327577E+10 | 0.376522E+09 | 0.289925E+10 | 0.00 | 0.00 |
July | 0.381225E+10 | 0.119333E+10 | 0.309235E+10 | 0.289636E+09 | 0.280271E+10 | 0.00 | 0.00 |
August | 0.278481E+10 | 0.134802E+10 | 0.247791E+10 | 66419681.66 | 0.241150E+10 | 0.00 | 0.00 |
September | 0.159372E+10 | 0.195750E+10 | 0.179592E+10 | 644474.31 | 0.179528E+10 | 0.00 | 0.00 |
October | 0.692210E+09 | 0.290903E+10 | 0.135369E+10 | 0.00 | 0.135369E+10 | 0.00 | 0.00 |
November | 0.182067E+09 | 0.397673E+10 | 0.890565E+09 | 0.00 | 0.890565E+09 | 0.00 | 0.00 |
December | 21644758.99 | 0.575381E+10 | 0.709765E+09 | 0.00 | 0.709765E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.170439E+11 | 0.386524E+11 | 0.225123E+11 | 0.917976E+09 | 0.215943E+11 | 0.00 | 0.00 |
Minimum of Months | 21644758.99 | 0.119333E+10 | 0.709765E+09 | 0.00 | 0.709765E+09 | 0.00 | 0.00 |
Maximum of Months | 0.381225E+10 | 0.680561E+10 | 0.327577E+10 | 0.376522E+09 | 0.289925E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.734407E+09 | 0.417674E+10 | 0.129573E+10 | 0.594040E+09 | 0.701690E+09 | 0.00 | 0.00 |
February | 0.144548E+10 | 0.276019E+10 | 0.183051E+10 | 0.908805E+09 | 0.921705E+09 | 0.00 | 0.00 |
March | 0.231982E+10 | 0.251717E+10 | 0.272500E+10 | 0.112753E+10 | 0.159747E+10 | 0.00 | 0.00 |
April | 0.334724E+10 | 0.176400E+10 | 0.336467E+10 | 0.166751E+10 | 0.169717E+10 | 0.00 | 0.00 |
May | 0.406860E+10 | 0.144839E+10 | 0.384061E+10 | 0.170883E+10 | 0.213178E+10 | 0.00 | 0.00 |
June | 0.582291E+10 | 0.946309E+09 | 0.481081E+10 | 0.247564E+10 | 0.233517E+10 | 0.00 | 0.00 |
July | 0.680313E+10 | 0.804802E+09 | 0.521738E+10 | 0.294953E+10 | 0.226786E+10 | 0.00 | 0.00 |
August | 0.577820E+10 | 0.900166E+09 | 0.453414E+10 | 0.252628E+10 | 0.200786E+10 | 0.00 | 0.00 |
September | 0.359893E+10 | 0.125272E+10 | 0.310399E+10 | 0.160227E+10 | 0.150172E+10 | 0.00 | 0.00 |
October | 0.225438E+10 | 0.184840E+10 | 0.230118E+10 | 0.116850E+10 | 0.113268E+10 | 0.00 | 0.00 |
November | 0.104202E+10 | 0.244356E+10 | 0.141140E+10 | 0.658938E+09 | 0.752461E+09 | 0.00 | 0.00 |
December | 0.582057E+09 | 0.352747E+10 | 0.107569E+10 | 0.462010E+09 | 0.613678E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.377972E+11 | 0.243899E+11 | 0.355111E+11 | 0.178499E+11 | 0.176612E+11 | 0.00 | 0.00 |
Minimum of Months | 0.582057E+09 | 0.804802E+09 | 0.107569E+10 | 0.462010E+09 | 0.613678E+09 | 0.00 | 0.00 |
Maximum of Months | 0.680313E+10 | 0.417674E+10 | 0.521738E+10 | 0.294953E+10 | 0.233517E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.572281E+10 | 0.585006E+10 | 0.596627E+10 | 0.426123E+10 | 0.170504E+10 | 0.00 | 0.00 |
February | 0.722938E+10 | 0.394095E+10 | 0.686267E+10 | 0.493589E+10 | 0.192678E+10 | 0.00 | 0.00 |
March | 0.712950E+10 | 0.390292E+10 | 0.679158E+10 | 0.381384E+10 | 0.297774E+10 | 0.00 | 0.00 |
April | 0.574651E+10 | 0.283171E+10 | 0.528318E+10 | 0.252698E+10 | 0.275620E+10 | 0.00 | 0.00 |
May | 0.534944E+10 | 0.233202E+10 | 0.485044E+10 | 0.161096E+10 | 0.323948E+10 | 0.00 | 0.00 |
June | 0.583434E+10 | 0.158497E+10 | 0.466394E+10 | 0.136023E+10 | 0.330371E+10 | 0.00 | 0.00 |
July | 0.724851E+10 | 0.131445E+10 | 0.519580E+10 | 0.191931E+10 | 0.327649E+10 | 0.00 | 0.00 |
August | 0.836733E+10 | 0.146609E+10 | 0.617486E+10 | 0.311326E+10 | 0.306161E+10 | 0.00 | 0.00 |
September | 0.833738E+10 | 0.200155E+10 | 0.662774E+10 | 0.406103E+10 | 0.256671E+10 | 0.00 | 0.00 |
October | 0.830956E+10 | 0.285056E+10 | 0.715991E+10 | 0.495099E+10 | 0.220892E+10 | 0.00 | 0.00 |
November | 0.673592E+10 | 0.352205E+10 | 0.631715E+10 | 0.457589E+10 | 0.174126E+10 | 0.00 | 0.00 |
December | 0.559238E+10 | 0.493545E+10 | 0.567359E+10 | 0.409690E+10 | 0.157668E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.816031E+11 | 0.365328E+11 | 0.715671E+11 | 0.412265E+11 | 0.303406E+11 | 0.00 | 0.00 |
Minimum of Months | 0.534944E+10 | 0.131445E+10 | 0.466394E+10 | 0.136023E+10 | 0.157668E+10 | 0.00 | 0.00 |
Maximum of Months | 0.836733E+10 | 0.585006E+10 | 0.715991E+10 | 0.495099E+10 | 0.330371E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.637264E+09 | 0.434888E+10 | 0.117366E+10 | 0.472992E+09 | 0.700664E+09 | 0.00 | 0.00 |
February | 0.145437E+10 | 0.283125E+10 | 0.180939E+10 | 0.889407E+09 | 0.919983E+09 | 0.00 | 0.00 |
March | 0.213864E+10 | 0.262463E+10 | 0.256368E+10 | 0.939370E+09 | 0.162431E+10 | 0.00 | 0.00 |
April | 0.325164E+10 | 0.186679E+10 | 0.323893E+10 | 0.143500E+10 | 0.180393E+10 | 0.00 | 0.00 |
May | 0.451367E+10 | 0.153491E+10 | 0.413987E+10 | 0.188800E+10 | 0.225187E+10 | 0.00 | 0.00 |
June | 0.528469E+10 | 0.104181E+10 | 0.435873E+10 | 0.200213E+10 | 0.235660E+10 | 0.00 | 0.00 |
July | 0.607095E+10 | 0.903568E+09 | 0.461387E+10 | 0.233145E+10 | 0.228241E+10 | 0.00 | 0.00 |
August | 0.501994E+10 | 0.974542E+09 | 0.391779E+10 | 0.192277E+10 | 0.199502E+10 | 0.00 | 0.00 |
September | 0.359076E+10 | 0.133466E+10 | 0.304996E+10 | 0.154193E+10 | 0.150802E+10 | 0.00 | 0.00 |
October | 0.225816E+10 | 0.193992E+10 | 0.225254E+10 | 0.111917E+10 | 0.113338E+10 | 0.00 | 0.00 |
November | 0.126836E+10 | 0.253735E+10 | 0.154315E+10 | 0.765533E+09 | 0.777615E+09 | 0.00 | 0.00 |
December | 0.615388E+09 | 0.363578E+10 | 0.107185E+10 | 0.452399E+09 | 0.619454E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.361038E+11 | 0.255741E+11 | 0.337334E+11 | 0.157602E+11 | 0.179733E+11 | 0.00 | 0.00 |
Minimum of Months | 0.615388E+09 | 0.903568E+09 | 0.107185E+10 | 0.452399E+09 | 0.619454E+09 | 0.00 | 0.00 |
Maximum of Months | 0.607095E+10 | 0.434888E+10 | 0.461387E+10 | 0.233145E+10 | 0.235660E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 34450225.60 | 0.692042E+10 | 0.846395E+09 | 0.00 | 0.846395E+09 | 0.00 | 0.00 |
February | 0.228529E+09 | 0.459415E+10 | 0.107941E+10 | 0.00 | 0.107941E+10 | 0.00 | 0.00 |
March | 0.809945E+09 | 0.404895E+10 | 0.194132E+10 | 0.00 | 0.194132E+10 | 0.00 | 0.00 |
April | 0.131291E+10 | 0.271164E+10 | 0.214211E+10 | 12500766.64 | 0.212961E+10 | 0.00 | 0.00 |
May | 0.236411E+10 | 0.213914E+10 | 0.290687E+10 | 0.172249E+09 | 0.273462E+10 | 0.00 | 0.00 |
June | 0.349631E+10 | 0.135671E+10 | 0.327570E+10 | 0.376511E+09 | 0.289919E+10 | 0.00 | 0.00 |
July | 0.387376E+10 | 0.118404E+10 | 0.309229E+10 | 0.289627E+09 | 0.280266E+10 | 0.00 | 0.00 |
August | 0.282103E+10 | 0.136535E+10 | 0.247787E+10 | 66417729.40 | 0.241145E+10 | 0.00 | 0.00 |
September | 0.159602E+10 | 0.205986E+10 | 0.179589E+10 | 644455.37 | 0.179524E+10 | 0.00 | 0.00 |
October | 0.642520E+09 | 0.316439E+10 | 0.135366E+10 | 0.00 | 0.135366E+10 | 0.00 | 0.00 |
November | 0.158049E+09 | 0.428519E+10 | 0.890546E+09 | 0.00 | 0.890546E+09 | 0.00 | 0.00 |
December | 20160781.49 | 0.600317E+10 | 0.709750E+09 | 0.00 | 0.709750E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.173578E+11 | 0.398330E+11 | 0.225118E+11 | 0.917949E+09 | 0.215938E+11 | 0.00 | 0.00 |
Minimum of Months | 20160781.49 | 0.118404E+10 | 0.709750E+09 | 0.00 | 0.709750E+09 | 0.00 | 0.00 |
Maximum of Months | 0.387376E+10 | 0.692042E+10 | 0.327570E+10 | 0.376511E+09 | 0.289919E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.731279E+09 | 0.426860E+10 | 0.129571E+10 | 0.594028E+09 | 0.701681E+09 | 0.00 | 0.00 |
February | 0.144536E+10 | 0.284643E+10 | 0.183048E+10 | 0.908787E+09 | 0.921694E+09 | 0.00 | 0.00 |
March | 0.234224E+10 | 0.259944E+10 | 0.272495E+10 | 0.112751E+10 | 0.159745E+10 | 0.00 | 0.00 |
April | 0.338785E+10 | 0.180790E+10 | 0.336462E+10 | 0.166747E+10 | 0.169714E+10 | 0.00 | 0.00 |
May | 0.411218E+10 | 0.149486E+10 | 0.384055E+10 | 0.170880E+10 | 0.213175E+10 | 0.00 | 0.00 |
June | 0.586360E+10 | 0.970747E+09 | 0.481073E+10 | 0.247559E+10 | 0.233514E+10 | 0.00 | 0.00 |
July | 0.683485E+10 | 0.837837E+09 | 0.521730E+10 | 0.294947E+10 | 0.226783E+10 | 0.00 | 0.00 |
August | 0.580064E+10 | 0.947131E+09 | 0.453407E+10 | 0.252623E+10 | 0.200783E+10 | 0.00 | 0.00 |
September | 0.359597E+10 | 0.135404E+10 | 0.310394E+10 | 0.160224E+10 | 0.150170E+10 | 0.00 | 0.00 |
October | 0.221286E+10 | 0.204736E+10 | 0.230115E+10 | 0.116848E+10 | 0.113266E+10 | 0.00 | 0.00 |
November | 0.100167E+10 | 0.266343E+10 | 0.141138E+10 | 0.658925E+09 | 0.752451E+09 | 0.00 | 0.00 |
December | 0.569202E+09 | 0.369448E+10 | 0.107567E+10 | 0.462001E+09 | 0.613669E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.378977E+11 | 0.255323E+11 | 0.355105E+11 | 0.178495E+11 | 0.176610E+11 | 0.00 | 0.00 |
Minimum of Months | 0.569202E+09 | 0.837837E+09 | 0.107567E+10 | 0.462001E+09 | 0.613669E+09 | 0.00 | 0.00 |
Maximum of Months | 0.683485E+10 | 0.426860E+10 | 0.521730E+10 | 0.294947E+10 | 0.233514E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.579161E+10 | 0.596562E+10 | 0.596603E+10 | 0.426105E+10 | 0.170498E+10 | 0.00 | 0.00 |
February | 0.730537E+10 | 0.412436E+10 | 0.686240E+10 | 0.493568E+10 | 0.192671E+10 | 0.00 | 0.00 |
March | 0.722476E+10 | 0.406708E+10 | 0.679132E+10 | 0.381368E+10 | 0.297764E+10 | 0.00 | 0.00 |
April | 0.584663E+10 | 0.289249E+10 | 0.528299E+10 | 0.252688E+10 | 0.275612E+10 | 0.00 | 0.00 |
May | 0.547023E+10 | 0.236341E+10 | 0.485028E+10 | 0.161090E+10 | 0.323938E+10 | 0.00 | 0.00 |
June | 0.593814E+10 | 0.158628E+10 | 0.466378E+10 | 0.136017E+10 | 0.330361E+10 | 0.00 | 0.00 |
July | 0.731527E+10 | 0.134655E+10 | 0.519563E+10 | 0.191923E+10 | 0.327639E+10 | 0.00 | 0.00 |
August | 0.842338E+10 | 0.153925E+10 | 0.617465E+10 | 0.311313E+10 | 0.306152E+10 | 0.00 | 0.00 |
September | 0.837044E+10 | 0.218412E+10 | 0.662749E+10 | 0.406086E+10 | 0.256663E+10 | 0.00 | 0.00 |
October | 0.829976E+10 | 0.319893E+10 | 0.715963E+10 | 0.495078E+10 | 0.220885E+10 | 0.00 | 0.00 |
November | 0.670556E+10 | 0.388381E+10 | 0.631690E+10 | 0.457570E+10 | 0.174120E+10 | 0.00 | 0.00 |
December | 0.560184E+10 | 0.518855E+10 | 0.567336E+10 | 0.409673E+10 | 0.157663E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.822930E+11 | 0.383404E+11 | 0.715645E+11 | 0.412248E+11 | 0.303397E+11 | 0.00 | 0.00 |
Minimum of Months | 0.547023E+10 | 0.134655E+10 | 0.466378E+10 | 0.136017E+10 | 0.157663E+10 | 0.00 | 0.00 |
Maximum of Months | 0.842338E+10 | 0.596562E+10 | 0.715963E+10 | 0.495078E+10 | 0.330361E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.642314E+09 | 0.443174E+10 | 0.117364E+10 | 0.472984E+09 | 0.700656E+09 | 0.00 | 0.00 |
February | 0.146885E+10 | 0.292286E+10 | 0.180937E+10 | 0.889393E+09 | 0.919973E+09 | 0.00 | 0.00 |
March | 0.217518E+10 | 0.270174E+10 | 0.256364E+10 | 0.939355E+09 | 0.162429E+10 | 0.00 | 0.00 |
April | 0.330282E+10 | 0.190687E+10 | 0.323889E+10 | 0.143497E+10 | 0.180392E+10 | 0.00 | 0.00 |
May | 0.456163E+10 | 0.159581E+10 | 0.413981E+10 | 0.188797E+10 | 0.225184E+10 | 0.00 | 0.00 |
June | 0.533303E+10 | 0.107335E+10 | 0.435867E+10 | 0.200209E+10 | 0.235658E+10 | 0.00 | 0.00 |
July | 0.610630E+10 | 0.941248E+09 | 0.461381E+10 | 0.233142E+10 | 0.228239E+10 | 0.00 | 0.00 |
August | 0.504494E+10 | 0.102495E+10 | 0.391774E+10 | 0.192274E+10 | 0.199500E+10 | 0.00 | 0.00 |
September | 0.359252E+10 | 0.144787E+10 | 0.304992E+10 | 0.154191E+10 | 0.150801E+10 | 0.00 | 0.00 |
October | 0.222463E+10 | 0.215285E+10 | 0.225251E+10 | 0.111915E+10 | 0.113336E+10 | 0.00 | 0.00 |
November | 0.124544E+10 | 0.276492E+10 | 0.154313E+10 | 0.765520E+09 | 0.777606E+09 | 0.00 | 0.00 |
December | 0.612650E+09 | 0.380488E+10 | 0.107184E+10 | 0.452392E+09 | 0.619447E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.363103E+11 | 0.267691E+11 | 0.337330E+11 | 0.157599E+11 | 0.179731E+11 | 0.00 | 0.00 |
Minimum of Months | 0.612650E+09 | 0.941248E+09 | 0.107184E+10 | 0.452392E+09 | 0.619447E+09 | 0.00 | 0.00 |
Maximum of Months | 0.610630E+10 | 0.443174E+10 | 0.461381E+10 | 0.233142E+10 | 0.235658E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 32493535.68 | 0.699603E+10 | 0.846413E+09 | 0.00 | 0.846413E+09 | 0.00 | 0.00 |
February | 0.207660E+09 | 0.468334E+10 | 0.107943E+10 | 0.00 | 0.107943E+10 | 0.00 | 0.00 |
March | 0.732007E+09 | 0.419223E+10 | 0.194136E+10 | 0.00 | 0.194136E+10 | 0.00 | 0.00 |
April | 0.118218E+10 | 0.290673E+10 | 0.214215E+10 | 12501134.09 | 0.212965E+10 | 0.00 | 0.00 |
May | 0.222228E+10 | 0.225189E+10 | 0.290693E+10 | 0.172254E+09 | 0.273468E+10 | 0.00 | 0.00 |
June | 0.339916E+10 | 0.141865E+10 | 0.327577E+10 | 0.376522E+09 | 0.289925E+10 | 0.00 | 0.00 |
July | 0.380878E+10 | 0.122813E+10 | 0.309235E+10 | 0.289636E+09 | 0.280271E+10 | 0.00 | 0.00 |
August | 0.277330E+10 | 0.140505E+10 | 0.247791E+10 | 66419681.66 | 0.241150E+10 | 0.00 | 0.00 |
September | 0.156404E+10 | 0.208083E+10 | 0.179592E+10 | 644474.31 | 0.179528E+10 | 0.00 | 0.00 |
October | 0.632423E+09 | 0.313854E+10 | 0.135369E+10 | 0.00 | 0.135369E+10 | 0.00 | 0.00 |
November | 0.154357E+09 | 0.425125E+10 | 0.890565E+09 | 0.00 | 0.890565E+09 | 0.00 | 0.00 |
December | 18336345.70 | 0.598759E+10 | 0.709765E+09 | 0.00 | 0.709765E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.167270E+11 | 0.405402E+11 | 0.225123E+11 | 0.917976E+09 | 0.215943E+11 | 0.00 | 0.00 |
Minimum of Months | 18336345.70 | 0.122813E+10 | 0.709765E+09 | 0.00 | 0.709765E+09 | 0.00 | 0.00 |
Maximum of Months | 0.380878E+10 | 0.699603E+10 | 0.327577E+10 | 0.376522E+09 | 0.289925E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.718984E+09 | 0.428603E+10 | 0.129573E+10 | 0.594040E+09 | 0.701690E+09 | 0.00 | 0.00 |
February | 0.141368E+10 | 0.287642E+10 | 0.183051E+10 | 0.908805E+09 | 0.921705E+09 | 0.00 | 0.00 |
March | 0.227508E+10 | 0.264969E+10 | 0.272500E+10 | 0.112753E+10 | 0.159747E+10 | 0.00 | 0.00 |
April | 0.330813E+10 | 0.187121E+10 | 0.336467E+10 | 0.166751E+10 | 0.169717E+10 | 0.00 | 0.00 |
May | 0.404050E+10 | 0.152601E+10 | 0.384061E+10 | 0.170883E+10 | 0.213178E+10 | 0.00 | 0.00 |
June | 0.581131E+10 | 0.978716E+09 | 0.481081E+10 | 0.247564E+10 | 0.233517E+10 | 0.00 | 0.00 |
July | 0.679887E+10 | 0.828438E+09 | 0.521738E+10 | 0.294953E+10 | 0.226786E+10 | 0.00 | 0.00 |
August | 0.576807E+10 | 0.934889E+09 | 0.453414E+10 | 0.252628E+10 | 0.200786E+10 | 0.00 | 0.00 |
September | 0.357387E+10 | 0.132356E+10 | 0.310399E+10 | 0.160227E+10 | 0.150172E+10 | 0.00 | 0.00 |
October | 0.220251E+10 | 0.198576E+10 | 0.230118E+10 | 0.116850E+10 | 0.113268E+10 | 0.00 | 0.00 |
November | 0.997796E+09 | 0.261036E+10 | 0.141140E+10 | 0.658938E+09 | 0.752461E+09 | 0.00 | 0.00 |
December | 0.563782E+09 | 0.367040E+10 | 0.107569E+10 | 0.462010E+09 | 0.613678E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.374726E+11 | 0.255415E+11 | 0.355111E+11 | 0.178499E+11 | 0.176612E+11 | 0.00 | 0.00 |
Minimum of Months | 0.563782E+09 | 0.828438E+09 | 0.107569E+10 | 0.462010E+09 | 0.613678E+09 | 0.00 | 0.00 |
Maximum of Months | 0.679887E+10 | 0.428603E+10 | 0.521738E+10 | 0.294953E+10 | 0.233517E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.568666E+10 | 0.603340E+10 | 0.596627E+10 | 0.426123E+10 | 0.170504E+10 | 0.00 | 0.00 |
February | 0.718453E+10 | 0.412099E+10 | 0.686267E+10 | 0.493589E+10 | 0.192678E+10 | 0.00 | 0.00 |
March | 0.708186E+10 | 0.410882E+10 | 0.679158E+10 | 0.381384E+10 | 0.297774E+10 | 0.00 | 0.00 |
April | 0.570872E+10 | 0.300170E+10 | 0.528318E+10 | 0.252698E+10 | 0.275620E+10 | 0.00 | 0.00 |
May | 0.532564E+10 | 0.245971E+10 | 0.485044E+10 | 0.161096E+10 | 0.323948E+10 | 0.00 | 0.00 |
June | 0.583279E+10 | 0.164888E+10 | 0.466394E+10 | 0.136023E+10 | 0.330371E+10 | 0.00 | 0.00 |
July | 0.725630E+10 | 0.135948E+10 | 0.519580E+10 | 0.191931E+10 | 0.327649E+10 | 0.00 | 0.00 |
August | 0.837109E+10 | 0.152819E+10 | 0.617486E+10 | 0.311326E+10 | 0.306161E+10 | 0.00 | 0.00 |
September | 0.832185E+10 | 0.211515E+10 | 0.662774E+10 | 0.406103E+10 | 0.256671E+10 | 0.00 | 0.00 |
October | 0.825721E+10 | 0.305396E+10 | 0.715991E+10 | 0.495099E+10 | 0.220892E+10 | 0.00 | 0.00 |
November | 0.666268E+10 | 0.375499E+10 | 0.631715E+10 | 0.457589E+10 | 0.174126E+10 | 0.00 | 0.00 |
December | 0.553847E+10 | 0.515624E+10 | 0.567359E+10 | 0.409690E+10 | 0.157668E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.812278E+11 | 0.383415E+11 | 0.715671E+11 | 0.412265E+11 | 0.303406E+11 | 0.00 | 0.00 |
Minimum of Months | 0.532564E+10 | 0.135948E+10 | 0.466394E+10 | 0.136023E+10 | 0.157668E+10 | 0.00 | 0.00 |
Maximum of Months | 0.837109E+10 | 0.603340E+10 | 0.715991E+10 | 0.495099E+10 | 0.330371E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.627945E+09 | 0.446720E+10 | 0.117366E+10 | 0.472992E+09 | 0.700664E+09 | 0.00 | 0.00 |
February | 0.143396E+10 | 0.295513E+10 | 0.180939E+10 | 0.889407E+09 | 0.919983E+09 | 0.00 | 0.00 |
March | 0.210951E+10 | 0.276298E+10 | 0.256368E+10 | 0.939370E+09 | 0.162431E+10 | 0.00 | 0.00 |
April | 0.322183E+10 | 0.198055E+10 | 0.323893E+10 | 0.143500E+10 | 0.180393E+10 | 0.00 | 0.00 |
May | 0.449617E+10 | 0.161935E+10 | 0.413987E+10 | 0.188800E+10 | 0.225187E+10 | 0.00 | 0.00 |
June | 0.528363E+10 | 0.108388E+10 | 0.435873E+10 | 0.200213E+10 | 0.235660E+10 | 0.00 | 0.00 |
July | 0.607586E+10 | 0.933546E+09 | 0.461387E+10 | 0.233145E+10 | 0.228241E+10 | 0.00 | 0.00 |
August | 0.501927E+10 | 0.101591E+10 | 0.391779E+10 | 0.192277E+10 | 0.199502E+10 | 0.00 | 0.00 |
September | 0.357522E+10 | 0.141549E+10 | 0.304996E+10 | 0.154193E+10 | 0.150802E+10 | 0.00 | 0.00 |
October | 0.221943E+10 | 0.208843E+10 | 0.225254E+10 | 0.111917E+10 | 0.113338E+10 | 0.00 | 0.00 |
November | 0.123784E+10 | 0.270993E+10 | 0.154315E+10 | 0.765533E+09 | 0.777615E+09 | 0.00 | 0.00 |
December | 0.602187E+09 | 0.378451E+10 | 0.107185E+10 | 0.452399E+09 | 0.619454E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.359028E+11 | 0.268169E+11 | 0.337334E+11 | 0.157602E+11 | 0.179733E+11 | 0.00 | 0.00 |
Minimum of Months | 0.602187E+09 | 0.933546E+09 | 0.107185E+10 | 0.452399E+09 | 0.619454E+09 | 0.00 | 0.00 |
Maximum of Months | 0.607586E+10 | 0.446720E+10 | 0.461387E+10 | 0.233145E+10 | 0.235660E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.580638E+10 | -0.506158E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -744791755.8 | 58.98 | 0.00 | 0.00 |
February | 0.533754E+10 | -0.468083E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -656708486.6 | 58.99 | 0.00 | 0.00 |
March | 0.619738E+10 | -0.548391E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -713471921.1 | 58.98 | 0.00 | 0.00 |
April | 0.543361E+10 | -0.475448E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -679129830.0 | 58.99 | 0.00 | 0.00 |
May | 0.551589E+10 | -0.482059E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -695291265.5 | 58.98 | 0.00 | 0.00 |
June | 0.516081E+10 | -0.449221E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668598825.5 | 58.98 | 0.00 | 0.00 |
July | 0.470445E+10 | -0.401719E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687260496.8 | 58.98 | 0.00 | 0.00 |
August | 0.503114E+10 | -0.434265E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688490274.6 | 58.98 | 0.00 | 0.00 |
September | 0.463108E+10 | -0.396351E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667577284.4 | 58.98 | 0.00 | 0.00 |
October | 0.498067E+10 | -0.428483E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -695841175.2 | 58.98 | 0.00 | 0.00 |
November | 0.516604E+10 | -0.448146E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -684574812.6 | 58.98 | 0.00 | 0.00 |
December | 0.543611E+10 | -0.470724E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -728877547.3 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.634011E+11 | -0.550905E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.831061E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.463108E+10 | -0.548391E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -744791755.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.619738E+10 | -0.396351E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -656708486.6 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.50 | 0.48 | 01-JAN-08:50 | 5944.25 | 36.69 | 217.17 | 230.00 | 5014.28 | 37.70 | 219.33 | 213.50 |
February | 275.00 | 0.50 | 0.48 | 01-FEB-08:09 | 8041.97 | 37.03 | 267.50 | 258.33 | 3500.79 | 31.87 | 238.83 | 246.33 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-07:49 | 9360.43 | 32.84 | 259.33 | 321.67 | 1962.01 | 22.44 | 212.00 | 293.17 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:39 | 2347.31 | 19.23 | 8.17 | 346.83 | 1365.28 | 21.50 | 191.50 | 313.67 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:19 | 2062.90 | 19.00 | 1.00 | 395.67 | 1174.07 | 21.23 | 212.83 | 354.17 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 1761.79 | 18.47 | 0.00 | 408.50 | 1035.97 | 20.74 | 221.67 | 362.00 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:40 | 1897.86 | 18.87 | 2.17 | 403.17 | 1148.54 | 21.17 | 190.00 | 368.00 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:30 | 2043.31 | 18.35 | 1.50 | 381.17 | 1241.93 | 20.62 | 182.50 | 345.83 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:49 | 2903.63 | 19.82 | 37.17 | 326.17 | 1487.68 | 20.99 | 167.67 | 297.67 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:20 | 8136.21 | 34.62 | 285.50 | 301.33 | 2364.24 | 25.11 | 208.67 | 284.83 |
November | 269.50 | 0.50 | 0.48 | 01-NOV-07:49 | 6064.13 | 36.88 | 260.33 | 249.83 | 5380.03 | 38.37 | 263.50 | 239.83 |
December | 236.83 | 0.50 | 0.48 | 01-DEC-08:50 | 4683.43 | 36.05 | 218.33 | 230.33 | 4152.61 | 38.73 | 239.00 | 218.33 |
Annual Sum or Average | 3965.83 | 0.50 | 4219.33 | 25.76 | 1558.17 | 3853.00 | 2207.41 | 25.40 | 2547.50 | 3537.33 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1761.79 | 18.35 | 0.00 | 230.00 | 1035.97 | 20.62 | 167.67 | 213.50 | |
Maximum of Months | 434.17 | 0.51 | 0.48 | 9360.43 | 37.03 | 285.50 | 408.50 | 5380.03 | 38.73 | 263.50 | 368.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.52 | 0.48 | 01-JAN-08:39 | 1850.09 | 23.62 | 89.67 | 214.50 | 1061.15 | 23.88 | 90.00 | 180.00 |
February | 275.00 | 0.51 | 0.48 | 01-FEB-08:09 | 2026.50 | 21.12 | 75.17 | 243.83 | 1083.01 | 21.87 | 90.50 | 211.33 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:40 | 3231.10 | 22.72 | 94.67 | 317.67 | 1805.07 | 23.62 | 130.50 | 285.33 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:39 | 3249.13 | 21.93 | 85.17 | 354.83 | 1818.93 | 23.03 | 76.17 | 319.00 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:40 | 3568.58 | 22.18 | 113.67 | 405.83 | 1574.09 | 22.13 | 62.33 | 367.17 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 4341.11 | 22.52 | 134.17 | 419.67 | 1902.34 | 23.13 | 91.00 | 389.00 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 4724.15 | 23.34 | 132.67 | 418.67 | 2036.55 | 22.97 | 77.50 | 393.00 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3730.22 | 21.64 | 115.67 | 388.00 | 2185.06 | 23.68 | 109.83 | 357.83 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:19 | 2833.91 | 21.92 | 104.17 | 325.50 | 1584.55 | 22.89 | 106.67 | 292.67 |
October | 317.67 | 0.51 | 0.48 | 01-OCT-08:09 | 2533.05 | 22.31 | 107.00 | 287.17 | 1461.12 | 23.50 | 122.00 | 252.00 |
November | 269.50 | 0.52 | 0.48 | 01-NOV-07:49 | 1598.28 | 21.01 | 83.17 | 229.00 | 916.86 | 23.04 | 100.50 | 196.00 |
December | 236.83 | 0.53 | 0.48 | 01-DEC-08:50 | 1436.00 | 23.53 | 100.67 | 206.83 | 858.98 | 24.04 | 98.17 | 164.33 |
Annual Sum or Average | 3965.83 | 0.50 | 3125.21 | 22.30 | 1235.83 | 3811.50 | 1602.50 | 23.12 | 1155.17 | 3407.67 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1436.00 | 21.01 | 75.17 | 206.83 | 858.98 | 21.87 | 62.33 | 164.33 | |
Maximum of Months | 434.17 | 0.53 | 0.48 | 4724.15 | 23.62 | 134.17 | 419.67 | 2185.06 | 24.04 | 130.50 | 393.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.55 | 0.48 | 01-JAN-10:09 | 596.47 | 14.85 | 0.00 | 189.33 | 354.35 | 17.31 | 0.00 | 118.67 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-10:30 | 652.62 | 15.86 | 0.00 | 228.17 | 403.48 | 18.34 | 0.00 | 170.50 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:00 | 1029.76 | 17.91 | 0.00 | 309.00 | 607.52 | 20.17 | 31.33 | 267.17 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:50 | 1072.56 | 18.59 | 0.00 | 350.17 | 642.45 | 20.76 | 57.33 | 310.17 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:00 | 1328.78 | 20.56 | 42.67 | 411.00 | 750.25 | 21.34 | 148.83 | 373.50 |
June | 434.17 | 0.49 | 0.48 | 01-JUN-13:39 | 1379.97 | 22.12 | 98.33 | 439.17 | 785.07 | 22.63 | 225.67 | 413.00 |
July | 417.33 | 0.48 | 0.48 | 01-JUL-06:40 | 1351.91 | 21.69 | 77.00 | 425.17 | 782.50 | 21.59 | 172.33 | 397.83 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1047.27 | 18.21 | 0.00 | 398.67 | 668.79 | 20.44 | 90.83 | 375.17 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:00 | 855.62 | 17.21 | 0.00 | 321.83 | 533.12 | 19.47 | 10.83 | 275.17 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:50 | 706.51 | 16.24 | 0.00 | 269.83 | 432.45 | 18.64 | 0.00 | 207.00 |
November | 269.50 | 0.54 | 0.48 | 01-NOV-08:39 | 559.58 | 14.96 | 0.00 | 206.00 | 338.17 | 17.45 | 0.00 | 127.83 |
December | 236.83 | 0.55 | 0.48 | 01-DEC-09:39 | 486.97 | 14.27 | 0.00 | 180.83 | 293.24 | 16.85 | 0.00 | 79.33 |
Annual Sum or Average | 3965.83 | 0.51 | 979.81 | 18.18 | 218.00 | 3729.17 | 582.30 | 19.92 | 737.17 | 3115.33 | ||
Minimum of Months | 226.83 | 0.48 | 0.48 | 486.97 | 14.27 | 0.00 | 180.83 | 293.24 | 16.85 | 0.00 | 79.33 | |
Maximum of Months | 434.17 | 0.55 | 0.48 | 1379.97 | 22.12 | 98.33 | 439.17 | 785.07 | 22.63 | 225.67 | 413.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.53 | 0.48 | 01-JAN-09:00 | 1719.09 | 22.28 | 85.00 | 207.17 | 1008.70 | 22.82 | 82.17 | 170.00 |
February | 275.00 | 0.51 | 0.48 | 01-FEB-10:20 | 2141.46 | 21.09 | 77.33 | 241.17 | 1220.03 | 23.60 | 108.17 | 213.17 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-08:09 | 3019.01 | 22.28 | 92.17 | 314.17 | 1689.45 | 24.26 | 125.50 | 283.67 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:50 | 3160.30 | 20.65 | 75.83 | 347.17 | 1783.59 | 21.90 | 62.17 | 311.17 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-06:40 | 3604.24 | 19.60 | 75.00 | 401.17 | 1691.93 | 19.16 | 1.33 | 366.00 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 3690.88 | 17.74 | 52.00 | 423.33 | 1675.96 | 18.84 | 3.33 | 387.50 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:49 | 4281.89 | 19.70 | 79.67 | 408.83 | 1948.77 | 19.17 | 4.00 | 378.33 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-06:40 | 3288.04 | 19.45 | 88.50 | 386.17 | 1851.28 | 20.94 | 64.50 | 356.33 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:00 | 3268.69 | 21.37 | 98.67 | 325.83 | 1399.61 | 22.30 | 85.33 | 293.50 |
October | 317.67 | 0.51 | 0.48 | 01-OCT-08:50 | 2169.56 | 20.91 | 85.00 | 283.67 | 1240.37 | 23.10 | 108.67 | 249.17 |
November | 269.50 | 0.52 | 0.48 | 01-NOV-08:50 | 1919.30 | 23.05 | 102.83 | 227.67 | 1098.22 | 23.71 | 102.67 | 193.00 |
December | 236.83 | 0.53 | 0.48 | 01-DEC-09:30 | 1310.94 | 20.99 | 78.17 | 207.67 | 764.04 | 23.07 | 89.83 | 168.83 |
Annual Sum or Average | 3965.83 | 0.51 | 2964.75 | 20.52 | 990.17 | 3774.00 | 1511.78 | 21.59 | 837.67 | 3370.67 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1310.94 | 17.74 | 52.00 | 207.17 | 764.04 | 18.84 | 1.33 | 168.83 | |
Maximum of Months | 434.17 | 0.53 | 0.48 | 4281.89 | 23.05 | 102.83 | 423.33 | 1948.77 | 24.26 | 125.50 | 387.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.50 | 0.48 | 01-JAN-08:50 | 5761.76 | 36.42 | 216.17 | 229.67 | 4871.14 | 37.41 | 215.33 | 212.00 |
February | 275.00 | 0.50 | 0.48 | 01-FEB-08:20 | 7824.34 | 35.80 | 256.33 | 255.83 | 3350.81 | 30.45 | 179.83 | 245.00 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-07:49 | 9178.21 | 32.07 | 253.50 | 320.00 | 1828.97 | 19.60 | 20.00 | 290.00 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:39 | 2225.75 | 15.42 | 0.00 | 345.50 | 1276.15 | 18.99 | 18.83 | 310.33 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:30 | 1968.68 | 15.31 | 0.00 | 393.17 | 1108.99 | 18.81 | 14.17 | 351.33 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 1683.39 | 14.87 | 0.00 | 405.67 | 983.14 | 18.45 | 0.50 | 357.33 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:40 | 1808.88 | 15.29 | 0.00 | 401.00 | 1086.52 | 18.90 | 10.00 | 365.33 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:40 | 1935.56 | 14.60 | 0.00 | 379.50 | 1161.54 | 18.19 | 8.83 | 342.17 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:00 | 2762.12 | 16.17 | 29.50 | 325.17 | 1378.76 | 18.36 | 22.17 | 294.17 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:20 | 7955.56 | 33.77 | 279.67 | 298.83 | 2232.34 | 22.69 | 83.00 | 283.33 |
November | 269.50 | 0.50 | 0.48 | 01-NOV-07:49 | 5853.77 | 35.14 | 246.17 | 247.17 | 5248.20 | 38.16 | 263.00 | 238.83 |
December | 236.83 | 0.50 | 0.48 | 01-DEC-08:50 | 4447.55 | 32.89 | 196.83 | 226.50 | 4026.70 | 38.53 | 232.17 | 217.17 |
Annual Sum or Average | 3965.83 | 0.50 | 4075.89 | 23.06 | 1478.17 | 3828.00 | 2107.42 | 23.42 | 1067.83 | 3507.00 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1683.39 | 14.60 | 0.00 | 226.50 | 983.14 | 18.19 | 0.50 | 212.00 | |
Maximum of Months | 434.17 | 0.51 | 0.48 | 9178.21 | 36.42 | 279.67 | 405.67 | 5248.20 | 38.53 | 263.00 | 365.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.52 | 0.48 | 01-JAN-08:50 | 1711.82 | 20.99 | 74.83 | 210.67 | 1021.88 | 23.66 | 81.67 | 175.67 |
February | 275.00 | 0.51 | 0.48 | 01-FEB-08:09 | 1960.13 | 20.62 | 75.00 | 242.00 | 1030.76 | 21.64 | 80.83 | 208.17 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:40 | 3143.21 | 22.27 | 94.17 | 316.33 | 1735.74 | 23.42 | 117.33 | 282.17 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:39 | 3160.03 | 21.46 | 85.17 | 353.17 | 1748.36 | 22.83 | 65.50 | 316.17 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:40 | 3482.36 | 21.73 | 113.33 | 404.00 | 1505.53 | 21.94 | 58.33 | 363.50 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 4238.69 | 22.07 | 134.17 | 417.17 | 1808.12 | 22.25 | 79.33 | 383.83 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 4613.72 | 22.89 | 132.67 | 417.50 | 1947.76 | 22.81 | 75.67 | 390.17 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3611.31 | 20.95 | 112.67 | 386.67 | 2105.12 | 23.51 | 103.50 | 354.50 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:19 | 2661.53 | 19.80 | 85.17 | 321.67 | 1519.74 | 22.70 | 96.50 | 289.67 |
October | 317.67 | 0.51 | 0.48 | 01-OCT-08:09 | 2469.49 | 21.84 | 107.00 | 284.17 | 1410.59 | 23.29 | 114.83 | 248.33 |
November | 269.50 | 0.52 | 0.48 | 01-NOV-07:49 | 1548.68 | 20.33 | 80.83 | 226.83 | 878.76 | 22.81 | 89.17 | 193.33 |
December | 236.83 | 0.53 | 0.48 | 01-DEC-08:50 | 1322.48 | 20.56 | 80.00 | 202.33 | 829.04 | 23.81 | 90.50 | 158.83 |
Annual Sum or Average | 3965.83 | 0.50 | 3024.26 | 21.38 | 1175.00 | 3782.50 | 1536.53 | 22.84 | 1053.17 | 3364.33 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1322.48 | 19.80 | 74.83 | 202.33 | 829.04 | 21.64 | 58.33 | 158.83 | |
Maximum of Months | 434.17 | 0.53 | 0.48 | 4613.72 | 22.89 | 134.17 | 417.50 | 2105.12 | 23.81 | 117.33 | 390.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.55 | 0.48 | 01-JAN-10:09 | 573.79 | 11.13 | 0.00 | 186.33 | 341.89 | 14.79 | 0.00 | 110.00 |
February | 275.00 | 0.53 | 0.48 | 01-FEB-10:30 | 628.42 | 12.21 | 0.00 | 224.83 | 390.59 | 15.95 | 0.00 | 164.17 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-08:09 | 993.33 | 14.46 | 0.00 | 307.17 | 587.52 | 17.98 | 0.00 | 263.33 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:50 | 1035.26 | 15.27 | 0.00 | 349.33 | 622.33 | 18.79 | 3.83 | 304.67 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:00 | 1283.33 | 17.43 | 38.50 | 409.83 | 756.27 | 20.68 | 54.17 | 374.00 |
June | 434.17 | 0.49 | 0.48 | 01-JUN-13:39 | 1332.20 | 19.42 | 96.33 | 437.50 | 757.81 | 20.67 | 66.67 | 410.00 |
July | 417.33 | 0.48 | 0.48 | 01-JUL-06:40 | 1307.02 | 18.88 | 72.17 | 423.50 | 757.88 | 19.58 | 38.67 | 394.67 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1011.69 | 14.86 | 0.00 | 395.83 | 649.88 | 18.48 | 6.67 | 373.00 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:00 | 825.57 | 13.88 | 0.00 | 319.33 | 517.36 | 17.42 | 0.00 | 270.00 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:00 | 680.72 | 12.69 | 0.00 | 266.33 | 418.66 | 16.36 | 0.00 | 202.17 |
November | 269.50 | 0.55 | 0.48 | 01-NOV-08:50 | 538.36 | 11.19 | 0.00 | 202.50 | 326.65 | 14.96 | 0.00 | 118.67 |
December | 236.83 | 0.56 | 0.48 | 01-DEC-09:39 | 467.29 | 10.41 | 0.00 | 174.67 | 282.46 | 14.21 | 0.00 | 68.33 |
Annual Sum or Average | 3965.83 | 0.51 | 945.47 | 14.86 | 207.00 | 3697.17 | 566.58 | 17.89 | 170.00 | 3053.00 | ||
Minimum of Months | 226.83 | 0.48 | 0.48 | 467.29 | 10.41 | 0.00 | 174.67 | 282.46 | 14.21 | 0.00 | 68.33 | |
Maximum of Months | 434.17 | 0.56 | 0.48 | 1332.20 | 19.42 | 96.33 | 437.50 | 757.88 | 20.68 | 66.67 | 410.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.53 | 0.48 | 01-JAN-10:09 | 1673.03 | 21.93 | 84.83 | 205.50 | 973.58 | 22.74 | 79.50 | 164.83 |
February | 275.00 | 0.51 | 0.48 | 01-FEB-10:30 | 2080.41 | 20.68 | 77.33 | 239.50 | 1170.56 | 23.51 | 107.17 | 210.50 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-08:09 | 2938.65 | 21.87 | 91.67 | 312.83 | 1601.63 | 23.28 | 113.33 | 279.17 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:00 | 3067.16 | 20.20 | 75.83 | 345.00 | 1711.93 | 21.75 | 55.83 | 309.00 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:40 | 3445.83 | 19.14 | 75.00 | 398.00 | 1615.06 | 19.00 | 0.50 | 363.67 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 3598.24 | 17.23 | 52.00 | 421.33 | 1604.31 | 18.66 | 2.33 | 384.33 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:49 | 4179.09 | 19.23 | 79.67 | 407.00 | 1868.12 | 19.01 | 3.83 | 376.00 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-06:40 | 3199.99 | 18.99 | 88.33 | 384.17 | 1781.87 | 20.78 | 62.67 | 353.83 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-07:10 | 3190.79 | 20.95 | 98.67 | 324.00 | 1335.09 | 22.19 | 83.17 | 291.17 |
October | 317.67 | 0.51 | 0.48 | 01-OCT-08:00 | 2086.05 | 20.13 | 80.83 | 281.00 | 1188.93 | 23.00 | 106.83 | 246.17 |
November | 269.50 | 0.52 | 0.48 | 01-NOV-08:50 | 1770.99 | 20.47 | 82.33 | 224.67 | 1058.16 | 23.62 | 101.50 | 189.00 |
December | 236.83 | 0.53 | 0.48 | 01-DEC-09:39 | 1270.44 | 20.61 | 77.67 | 205.00 | 732.97 | 22.98 | 88.67 | 163.17 |
Annual Sum or Average | 3965.83 | 0.51 | 2872.26 | 19.90 | 964.17 | 3748.00 | 1448.12 | 21.39 | 805.33 | 3330.83 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1270.44 | 17.23 | 52.00 | 205.00 | 732.97 | 18.66 | 0.50 | 163.17 | |
Maximum of Months | 434.17 | 0.53 | 0.48 | 4179.09 | 21.93 | 98.67 | 421.33 | 1868.12 | 23.62 | 113.33 | 384.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.50 | 0.48 | 01-JAN-08:50 | 5761.76 | 36.42 | 216.17 | 229.67 | 4871.05 | 37.41 | 215.33 | 212.00 |
February | 275.00 | 0.50 | 0.48 | 01-FEB-08:20 | 7824.31 | 35.80 | 256.33 | 255.83 | 3350.71 | 30.45 | 179.83 | 245.00 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-07:49 | 9178.09 | 32.07 | 253.50 | 320.00 | 1828.84 | 19.60 | 20.17 | 290.00 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:39 | 2225.63 | 15.42 | 0.00 | 345.50 | 1276.05 | 18.99 | 18.83 | 310.33 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:30 | 1968.56 | 15.31 | 0.00 | 393.17 | 1108.91 | 18.81 | 14.17 | 351.33 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 1683.31 | 14.88 | 0.00 | 405.67 | 983.07 | 18.45 | 0.50 | 357.33 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:40 | 1808.79 | 15.30 | 0.00 | 401.00 | 1086.45 | 18.90 | 10.00 | 365.33 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:40 | 1935.47 | 14.60 | 0.00 | 379.50 | 1161.47 | 18.19 | 8.83 | 342.17 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:00 | 2762.03 | 16.18 | 29.50 | 325.17 | 1378.67 | 18.36 | 22.33 | 294.17 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:20 | 7955.51 | 33.77 | 279.67 | 298.83 | 2232.24 | 22.69 | 83.00 | 283.33 |
November | 269.50 | 0.50 | 0.48 | 01-NOV-07:49 | 5853.77 | 35.14 | 246.17 | 247.17 | 5248.11 | 38.16 | 263.00 | 238.83 |
December | 236.83 | 0.50 | 0.48 | 01-DEC-08:50 | 4447.57 | 32.89 | 196.83 | 226.50 | 4026.64 | 38.53 | 232.17 | 217.17 |
Annual Sum or Average | 3965.83 | 0.50 | 4075.82 | 23.06 | 1478.17 | 3828.00 | 2107.34 | 23.43 | 1068.17 | 3507.00 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1683.31 | 14.60 | 0.00 | 226.50 | 983.07 | 18.19 | 0.50 | 212.00 | |
Maximum of Months | 434.17 | 0.51 | 0.48 | 9178.09 | 36.42 | 279.67 | 405.67 | 5248.11 | 38.53 | 263.00 | 365.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.52 | 0.48 | 01-JAN-08:50 | 1711.79 | 20.99 | 74.83 | 210.67 | 1021.84 | 23.66 | 81.67 | 175.67 |
February | 275.00 | 0.51 | 0.48 | 01-FEB-08:09 | 1960.11 | 20.62 | 75.00 | 242.00 | 1030.72 | 21.64 | 81.00 | 208.17 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:40 | 3143.16 | 22.27 | 94.17 | 316.33 | 1735.66 | 23.43 | 117.33 | 282.17 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:39 | 3159.98 | 21.46 | 85.17 | 353.17 | 1748.29 | 22.84 | 65.50 | 316.17 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:40 | 3482.29 | 21.73 | 113.33 | 404.00 | 1505.45 | 21.94 | 58.50 | 363.50 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 4238.64 | 22.07 | 134.17 | 417.17 | 1808.05 | 22.25 | 79.33 | 383.83 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 4613.69 | 22.90 | 132.67 | 417.50 | 1947.69 | 22.81 | 75.67 | 390.17 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3611.27 | 20.95 | 112.67 | 386.67 | 2105.05 | 23.51 | 103.50 | 354.50 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:19 | 2661.50 | 19.80 | 85.17 | 321.67 | 1519.68 | 22.70 | 96.50 | 289.67 |
October | 317.67 | 0.51 | 0.48 | 01-OCT-08:09 | 2469.46 | 21.85 | 107.00 | 284.17 | 1410.54 | 23.29 | 114.83 | 248.33 |
November | 269.50 | 0.52 | 0.48 | 01-NOV-07:49 | 1548.66 | 20.33 | 80.83 | 226.83 | 878.72 | 22.81 | 89.17 | 193.33 |
December | 236.83 | 0.53 | 0.48 | 01-DEC-08:50 | 1322.46 | 20.57 | 80.00 | 202.33 | 829.00 | 23.81 | 90.50 | 158.83 |
Annual Sum or Average | 3965.83 | 0.50 | 3024.22 | 21.38 | 1175.00 | 3782.50 | 1536.47 | 22.84 | 1053.50 | 3364.33 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1322.46 | 19.80 | 74.83 | 202.33 | 829.00 | 21.64 | 58.50 | 158.83 | |
Maximum of Months | 434.17 | 0.53 | 0.48 | 4613.69 | 22.90 | 134.17 | 417.50 | 2105.05 | 23.81 | 117.33 | 390.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.55 | 0.48 | 01-JAN-10:09 | 573.77 | 11.13 | 0.00 | 186.33 | 341.86 | 14.80 | 0.00 | 110.00 |
February | 275.00 | 0.53 | 0.48 | 01-FEB-10:30 | 628.41 | 12.21 | 0.00 | 224.83 | 390.57 | 15.95 | 0.00 | 164.17 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-08:09 | 993.29 | 14.47 | 0.00 | 307.17 | 587.48 | 17.98 | 0.00 | 263.33 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:50 | 1035.23 | 15.27 | 0.00 | 349.33 | 622.29 | 18.79 | 3.83 | 304.67 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:00 | 1283.29 | 17.43 | 38.50 | 409.83 | 756.22 | 20.68 | 54.17 | 374.00 |
June | 434.17 | 0.49 | 0.48 | 01-JUN-13:39 | 1332.17 | 19.42 | 96.33 | 437.50 | 757.76 | 20.67 | 66.67 | 410.00 |
July | 417.33 | 0.48 | 0.48 | 01-JUL-06:40 | 1307.00 | 18.88 | 72.17 | 423.50 | 757.84 | 19.58 | 38.67 | 394.67 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1011.67 | 14.86 | 0.00 | 395.83 | 649.84 | 18.48 | 6.67 | 373.00 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:00 | 825.55 | 13.88 | 0.00 | 319.33 | 517.33 | 17.42 | 0.00 | 270.00 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:00 | 680.70 | 12.69 | 0.00 | 266.33 | 418.63 | 16.36 | 0.00 | 202.17 |
November | 269.50 | 0.55 | 0.48 | 01-NOV-08:50 | 538.35 | 11.20 | 0.00 | 202.50 | 326.63 | 14.96 | 0.00 | 118.67 |
December | 236.83 | 0.56 | 0.48 | 01-DEC-09:39 | 467.28 | 10.41 | 0.00 | 174.67 | 282.44 | 14.21 | 0.00 | 68.17 |
Annual Sum or Average | 3965.83 | 0.51 | 945.45 | 14.86 | 207.00 | 3697.17 | 566.54 | 17.89 | 170.00 | 3052.83 | ||
Minimum of Months | 226.83 | 0.48 | 0.48 | 467.28 | 10.41 | 0.00 | 174.67 | 282.44 | 14.21 | 0.00 | 68.17 | |
Maximum of Months | 434.17 | 0.56 | 0.48 | 1332.17 | 19.42 | 96.33 | 437.50 | 757.84 | 20.68 | 66.67 | 410.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.53 | 0.48 | 01-JAN-10:09 | 1673.00 | 21.93 | 84.83 | 205.50 | 973.54 | 22.74 | 79.50 | 164.83 |
February | 275.00 | 0.51 | 0.48 | 01-FEB-10:30 | 2080.38 | 20.68 | 77.33 | 239.50 | 1170.52 | 23.51 | 107.17 | 210.50 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-08:09 | 2938.58 | 21.88 | 91.67 | 312.83 | 1601.55 | 23.28 | 113.33 | 279.17 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:00 | 3067.10 | 20.20 | 75.83 | 345.00 | 1711.85 | 21.75 | 56.00 | 309.00 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:40 | 3445.77 | 19.14 | 75.00 | 398.00 | 1614.98 | 19.00 | 0.50 | 363.67 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 3598.18 | 17.24 | 52.00 | 421.33 | 1604.23 | 18.66 | 2.33 | 384.33 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:49 | 4179.05 | 19.23 | 79.67 | 407.00 | 1868.04 | 19.01 | 3.83 | 376.00 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-06:40 | 3199.95 | 18.99 | 88.33 | 384.17 | 1781.80 | 20.78 | 62.67 | 353.83 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-07:10 | 3190.76 | 20.95 | 98.67 | 324.00 | 1335.03 | 22.19 | 83.17 | 291.17 |
October | 317.67 | 0.51 | 0.48 | 01-OCT-08:00 | 2086.02 | 20.13 | 80.83 | 281.00 | 1188.88 | 23.00 | 106.83 | 246.17 |
November | 269.50 | 0.52 | 0.48 | 01-NOV-08:50 | 1770.97 | 20.47 | 82.33 | 224.67 | 1058.12 | 23.62 | 101.50 | 189.00 |
December | 236.83 | 0.53 | 0.48 | 01-DEC-09:39 | 1270.42 | 20.61 | 77.67 | 205.00 | 732.94 | 22.99 | 88.67 | 163.17 |
Annual Sum or Average | 3965.83 | 0.51 | 2872.22 | 19.91 | 964.17 | 3748.00 | 1448.05 | 21.39 | 805.50 | 3330.83 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1270.42 | 17.24 | 52.00 | 205.00 | 732.94 | 18.66 | 0.50 | 163.17 | |
Maximum of Months | 434.17 | 0.53 | 0.48 | 4179.05 | 21.93 | 98.67 | 421.33 | 1868.04 | 23.62 | 113.33 | 384.33 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.252462E+09 | 18593.75 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21689957.33 | 18593.75 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1365759.38 | 18593.75 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6343979.09 | 18593.75 | 26-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281862E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.252462E+09 | 18593.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.897809E+10 | 14476.58 | 27-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.491661E+10 | 13809.80 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.376473E+10 | 12794.47 | 21-MAR-17:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.210760E+10 | 12814.43 | 22-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173346E+10 | 13064.41 | 22-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.312116E+09 | 12838.16 | 16-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 27267688.39 | 9146.88 | 05-JUL-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.182995E+09 | 12148.69 | 17-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.583881E+09 | 13024.41 | 12-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101493E+10 | 12937.39 | 17-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.269204E+10 | 12777.50 | 28-NOV-13:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.573618E+10 | 14164.07 | 29-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.320499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 27267688.39 | 9146.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.897809E+10 | 14476.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.400136E+10 | 11158.03 | 27-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179805E+10 | 10662.68 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.814115E+09 | 9857.57 | 11-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113576E+09 | 9892.67 | 22-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 59394209.55 | 9776.46 | 09-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16426571.64 | 9779.98 | 10-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.584027E+09 | 9826.11 | 28-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.210249E+10 | 10935.15 | 29-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.948944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.400136E+10 | 11158.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.680955E+10 | 9162.13 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.359283E+10 | 8526.14 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.202037E+10 | 7891.44 | 18-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.416473E+09 | 7913.10 | 22-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173046E+09 | 7890.76 | 02-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2080070.04 | 2513.47 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 67061389.73 | 7892.21 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113444E+10 | 7902.78 | 25-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379136E+10 | 8744.08 | 29-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.680955E+10 | 9162.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.425913E+10 | 11261.06 | 06-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.187193E+10 | 11261.06 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.956196E+09 | 10725.14 | 11-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147772E+09 | 10709.60 | 01-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 69160189.96 | 10636.80 | 09-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23955195.49 | 10640.72 | 10-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.585777E+09 | 10664.12 | 14-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221311E+10 | 11261.06 | 29-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.425913E+10 | 11261.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.330472E+10 | 26831.59 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102921E+10 | 26831.59 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.391330E+09 | 26831.59 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16499301.90 | 26289.40 | 08-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8549638.65 | 26831.59 | 10-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.399313E+09 | 26831.59 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145644E+10 | 26831.59 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.660606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.330472E+10 | 26831.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.445762E+10 | 14732.39 | 12-JAN-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169504E+10 | 14772.99 | 07-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.854254E+09 | 14653.49 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112738E+09 | 14606.32 | 28-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127885E+09 | 14623.30 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4452495.30 | 5106.33 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 66213933.53 | 14625.08 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.893522E+09 | 14727.82 | 28-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.251608E+10 | 14702.11 | 29-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.445762E+10 | 14772.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.382362E+10 | 11376.02 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157792E+10 | 11376.02 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.666070E+09 | 11376.02 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 53385528.44 | 11376.02 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 60397238.96 | 11376.02 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2227762.99 | 4314.30 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 56230302.34 | 11376.02 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.787622E+09 | 11376.02 | 13-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.228595E+10 | 11376.02 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.931342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.382362E+10 | 11376.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.661354E+10 | 10219.01 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.302840E+10 | 9037.79 | 01-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133590E+10 | 8905.51 | 08-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138498E+09 | 8864.96 | 21-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116868E+09 | 8906.33 | 08-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6341449.79 | 6713.55 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134424E+09 | 8932.36 | 10-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141793E+10 | 8925.36 | 29-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.406149E+10 | 9162.48 | 29-DEC-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.661354E+10 | 10219.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.412869E+10 | 11483.01 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170872E+10 | 11483.01 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.800048E+09 | 11483.01 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 84590992.10 | 11483.01 | 28-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 78538529.46 | 11483.01 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4212160.59 | 4594.64 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 75005008.28 | 11483.01 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.838509E+09 | 11483.01 | 13-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246509E+10 | 11483.01 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.412869E+10 | 11483.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.939578E+10 | 32178.45 | 02-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.413870E+10 | 32224.47 | 13-FEB-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193201E+10 | 32224.94 | 10-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214086E+09 | 31866.26 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.282130E+09 | 32210.72 | 08-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1165896.01 | 4852.38 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.198870E+09 | 32277.56 | 10-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.221920E+10 | 32217.14 | 29-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.610319E+10 | 32153.65 | 11-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.244851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.939578E+10 | 32277.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.750192E+10 | 16102.78 | 12-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.332724E+10 | 16089.51 | 15-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.216655E+10 | 16076.96 | 09-MAR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.550988E+09 | 16087.19 | 29-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.456341E+09 | 16090.42 | 09-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6830514.93 | 9895.66 | 17-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3090858.87 | 5645.21 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 72165051.68 | 15067.77 | 19-SEP-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.380428E+09 | 16012.50 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.206134E+10 | 16080.01 | 22-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.502306E+10 | 16105.91 | 06-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.750192E+10 | 16105.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.618370E+10 | 11959.00 | 07-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285968E+10 | 12008.10 | 15-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158194E+10 | 11998.74 | 09-MAR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.292100E+09 | 11929.26 | 15-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.215612E+09 | 11978.88 | 02-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 865539.45 | 796.45 | 16-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 44150947.53 | 10745.54 | 19-SEP-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.302121E+09 | 11951.13 | 06-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177114E+10 | 12001.08 | 22-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.433298E+10 | 11990.23 | 02-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.618370E+10 | 12008.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.101699E+11 | 12264.48 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.522168E+10 | 10728.58 | 01-FEB-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.303407E+10 | 10219.59 | 31-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.664391E+09 | 10234.53 | 04-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.443656E+09 | 10214.79 | 08-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1901392.71 | 3528.76 | 17-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1209831.59 | 2970.60 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103737E+09 | 10258.21 | 13-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.664519E+09 | 10258.44 | 07-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316644E+10 | 10241.69 | 04-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.733839E+10 | 11289.04 | 29-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.308099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.101699E+11 | 12264.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.650213E+10 | 13584.33 | 31-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.306020E+10 | 13643.36 | 15-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183224E+10 | 13573.65 | 09-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.387936E+09 | 13552.55 | 22-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.286695E+09 | 13560.83 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4342360.71 | 6335.61 | 17-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2379950.99 | 4078.17 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 60029848.77 | 10989.51 | 19-SEP-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.375069E+09 | 13578.69 | 06-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.186895E+10 | 13635.37 | 22-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.452467E+10 | 13623.07 | 02-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.650213E+10 | 13643.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.227157E+11 | 36660.94 | 06-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133981E+11 | 36660.94 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.884089E+10 | 34933.94 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.268668E+10 | 17244.89 | 29-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164547E+10 | 13734.01 | 08-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 36307441.14 | 5467.37 | 16-JUN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29270.18 | 146.35 | 08-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1324983.29 | 1238.41 | 17-AUG-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.256086E+09 | 6883.55 | 19-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173336E+10 | 17727.07 | 10-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.617524E+10 | 29142.23 | 27-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157787E+11 | 36660.94 | 28-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.732679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 29270.18 | 146.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.227157E+11 | 36660.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.219907E+11 | 38016.92 | 06-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130881E+11 | 38016.92 | 01-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.947326E+10 | 34523.17 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.382162E+10 | 18197.53 | 29-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.244256E+10 | 13307.55 | 08-MAY-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.201398E+09 | 6639.96 | 16-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1348412.33 | 851.44 | 05-JUL-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32182324.05 | 2178.57 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.871562E+09 | 7671.05 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.278153E+10 | 16797.36 | 10-OCT-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.688682E+10 | 27043.15 | 27-NOV-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154180E+11 | 38016.92 | 29-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.770091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1348412.33 | 851.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.219907E+11 | 38016.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.251480E+11 | 36587.00 | 05-JAN-21:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145445E+11 | 36587.00 | 01-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104744E+11 | 35423.13 | 04-MAR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.423384E+10 | 18251.07 | 29-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.266297E+10 | 16037.52 | 08-MAY-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.309992E+09 | 7530.77 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9607876.32 | 1497.06 | 08-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.107339E+09 | 3291.82 | 18-AUG-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108234E+10 | 10317.93 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.322230E+10 | 21101.97 | 10-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.780242E+10 | 25905.39 | 27-NOV-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176489E+11 | 36587.00 | 28-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.872465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9607876.32 | 1497.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.251480E+11 | 36587.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.342348E+09 | 0.340562E+09 | 14372.80 | 28-FEB-16:30 | 14372.80 | 0.00 |
March | 0.00 | 0.00 | 0.802299E+09 | 0.800917E+09 | 12773.97 | 01-MAR-16:20 | 12773.97 | 0.00 |
April | 0.00 | 0.00 | 0.345471E+10 | 0.341901E+10 | 31376.01 | 06-APR-16:00 | 31376.01 | 0.00 |
May | 0.00 | 0.00 | 0.863717E+10 | 0.836751E+10 | 51666.21 | 19-MAY-15:30 | 51666.21 | 0.00 |
June | 0.00 | 0.00 | 0.273280E+11 | 0.260477E+11 | 64312.12 | 20-JUN-16:00 | 56350.58 | 0.00 |
July | 0.00 | 0.00 | 0.472985E+11 | 0.455731E+11 | 80411.29 | 17-JUL-16:00 | 80411.29 | 0.00 |
August | 0.00 | 0.00 | 0.404883E+11 | 0.400165E+11 | 73437.29 | 07-AUG-16:00 | 73437.29 | 0.00 |
September | 0.00 | 0.00 | 0.208345E+11 | 0.190333E+11 | 103009.41 | 07-SEP-14:55 | 54359.62 | 0.00 |
October | 0.00 | 0.00 | 0.688767E+10 | 0.682540E+10 | 47463.08 | 18-OCT-15:50 | 47463.08 | 0.00 |
November | 0.00 | 0.00 | 0.155957E+10 | 0.153615E+10 | 23511.39 | 03-NOV-15:30 | 23511.39 | 0.00 |
December | 0.00 | 0.00 | 2754552.26 | 2644562.71 | 838.66 | 07-DEC-15:00 | 807.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.157636E+12 | 0.151963E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.472985E+11 | 0.455731E+11 | 103009.41 | 80411.29 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.288782E+09 | 0.288196E+09 | 10336.14 | 28-FEB-15:10 | 10336.14 | 0.00 |
March | 0.00 | 0.00 | 0.193987E+09 | 0.193511E+09 | 8929.00 | 01-MAR-15:10 | 8929.00 | 0.00 |
April | 0.00 | 0.00 | 0.193474E+10 | 0.191390E+10 | 27225.37 | 06-APR-16:00 | 27225.37 | 0.00 |
May | 0.00 | 0.00 | 0.713833E+10 | 0.694132E+10 | 52594.25 | 19-MAY-15:30 | 52594.25 | 0.00 |
June | 0.00 | 0.00 | 0.256998E+11 | 0.245488E+11 | 62057.21 | 21-JUN-14:05 | 55894.50 | 0.00 |
July | 0.00 | 0.00 | 0.432731E+11 | 0.418694E+11 | 76846.15 | 17-JUL-15:40 | 76846.15 | 0.00 |
August | 0.00 | 0.00 | 0.365075E+11 | 0.360969E+11 | 72889.83 | 07-AUG-15:20 | 72889.83 | 0.00 |
September | 0.00 | 0.00 | 0.168267E+11 | 0.154014E+11 | 92342.61 | 07-SEP-15:00 | 48730.59 | 0.00 |
October | 0.00 | 0.00 | 0.332911E+10 | 0.329809E+10 | 41924.62 | 18-OCT-15:50 | 41924.62 | 0.00 |
November | 0.00 | 0.00 | 0.276943E+09 | 0.264399E+09 | 6650.39 | 09-NOV-14:00 | 6650.39 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.135469E+12 | 0.130816E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.432731E+11 | 0.418694E+11 | 92342.61 | 76846.15 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.264634E+09 | 0.262962E+09 | 9163.99 | 27-FEB-15:30 | 9163.99 | 0.00 |
March | 0.00 | 0.00 | 0.285920E+09 | 0.285462E+09 | 10762.11 | 28-MAR-15:50 | 10762.11 | 0.00 |
April | 0.00 | 0.00 | 0.195571E+10 | 0.192233E+10 | 28314.75 | 06-APR-16:00 | 28314.75 | 0.00 |
May | 0.00 | 0.00 | 0.752284E+10 | 0.725734E+10 | 61099.81 | 19-MAY-15:30 | 61099.81 | 0.00 |
June | 0.00 | 0.00 | 0.275800E+11 | 0.262681E+11 | 69804.56 | 20-JUN-15:10 | 62054.42 | 0.00 |
July | 0.00 | 0.00 | 0.465471E+11 | 0.449437E+11 | 88467.67 | 17-JUL-15:30 | 88467.67 | 0.00 |
August | 0.00 | 0.00 | 0.384518E+11 | 0.378865E+11 | 83742.27 | 06-AUG-16:11 | 83742.27 | 0.00 |
September | 0.00 | 0.00 | 0.170974E+11 | 0.155200E+11 | 93359.50 | 07-SEP-15:20 | 50709.05 | 0.00 |
October | 0.00 | 0.00 | 0.302517E+10 | 0.296285E+10 | 42971.39 | 18-OCT-15:00 | 42971.39 | 0.00 |
November | 0.00 | 0.00 | 0.174467E+09 | 0.154719E+09 | 4183.28 | 04-NOV-14:00 | 3987.91 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.142905E+12 | 0.137464E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.465471E+11 | 0.449437E+11 | 93359.50 | 88467.67 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2041.85 | 7189.09 | 26-JAN-12:12 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2087.36 | 7241.39 | 22-FEB-12:07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2202.99 | 7219.58 | 03-MAR-12:14 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1986.76 | 7033.39 | 04-APR-11:08 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1954.16 | 6705.33 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1889.12 | 6313.52 | 01-JUN-11:13 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1651.41 | 5925.53 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1777.91 | 5748.88 | 02-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1682.15 | 5873.64 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1753.07 | 6222.59 | 31-OCT-11:13 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1883.10 | 6600.11 | 29-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1908.60 | 6970.73 | 29-DEC-12:10 |
Annual Sum or Average | 0.00 | 1900.47 | ||||
Minimum of Months | 0.00 | 0.00 | 1651.41 | 5748.88 | ||
Maximum of Months | 0.00 | 0.00 | 2202.99 | 7241.39 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.164882E+10 | 0.45 | 3078.73 | 02-JAN-06:01 | 0.91 |
February | 0.139768E+10 | 0.41 | 3078.73 | 06-FEB-07:01 | 0.91 |
March | 0.168252E+10 | 0.41 | 2583.82 | 06-MAR-07:01 | 0.83 |
April | 0.179214E+10 | 0.38 | 3730.52 | 25-APR-16:00 | 1.01 |
May | 0.240742E+10 | 0.40 | 6503.81 | 19-MAY-15:30 | 1.39 |
June | 0.462338E+10 | 0.55 | 9159.64 | 29-JUN-15:10 | 1.73 |
July | 0.609783E+10 | 0.62 | 12572.02 | 25-JUL-12:10 | 2.11 |
August | 0.587837E+10 | 0.60 | 12876.11 | 07-AUG-06:03 | 2.15 |
September | 0.375549E+10 | 0.50 | 12876.11 | 05-SEP-06:03 | 2.14 |
October | 0.235477E+10 | 0.39 | 5390.90 | 18-OCT-16:00 | 1.25 |
November | 0.161671E+10 | 0.37 | 3363.53 | 03-NOV-15:30 | 0.95 |
December | 0.143506E+10 | 0.39 | 3078.73 | 26-DEC-07:01 | 0.91 |
Annual Sum or Average | 0.346902E+11 | 0.46 | |||
Minimum of Months | 0.139768E+10 | 0.37 | 2583.82 | 0.83 | |
Maximum of Months | 0.609783E+10 | 0.62 | 12876.11 | 2.15 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.154951E+10 | 0.44 | 3117.18 | 02-JAN-06:01 | 0.97 |
February | 0.126905E+10 | 0.41 | 3117.18 | 01-FEB-06:01 | 0.98 |
March | 0.145908E+10 | 0.42 | 3117.18 | 06-MAR-06:01 | 0.98 |
April | 0.153477E+10 | 0.39 | 4850.45 | 25-APR-15:50 | 1.26 |
May | 0.214855E+10 | 0.41 | 7671.03 | 19-MAY-15:30 | 1.65 |
June | 0.428164E+10 | 0.56 | 11093.89 | 26-JUN-06:02 | 2.09 |
July | 0.567126E+10 | 0.62 | 11542.77 | 17-JUL-11:00 | 2.14 |
August | 0.526432E+10 | 0.60 | 11542.77 | 07-AUG-09:10 | 2.14 |
September | 0.292359E+10 | 0.47 | 11542.77 | 07-SEP-14:55 | 2.12 |
October | 0.166874E+10 | 0.38 | 5699.60 | 18-OCT-15:50 | 1.38 |
November | 0.129840E+10 | 0.39 | 3117.18 | 27-NOV-06:01 | 0.98 |
December | 0.138372E+10 | 0.42 | 3117.18 | 04-DEC-06:01 | 0.97 |
Annual Sum or Average | 0.304526E+11 | 0.46 | |||
Minimum of Months | 0.126905E+10 | 0.38 | 3117.18 | 0.97 | |
Maximum of Months | 0.567126E+10 | 0.62 | 11542.77 | 2.14 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.199265E+10 | 0.52 | 2877.28 | 02-JAN-05:01 | 0.84 |
February | 0.146589E+10 | 0.46 | 2877.28 | 01-FEB-06:01 | 0.84 |
March | 0.159304E+10 | 0.45 | 2877.28 | 01-MAR-07:01 | 0.84 |
April | 0.149925E+10 | 0.40 | 4292.10 | 25-APR-15:50 | 1.05 |
May | 0.202489E+10 | 0.41 | 7373.78 | 19-MAY-15:30 | 1.44 |
June | 0.378237E+10 | 0.50 | 8790.42 | 29-JUN-14:30 | 1.62 |
July | 0.503378E+10 | 0.54 | 12598.21 | 17-JUL-15:00 | 2.02 |
August | 0.455517E+10 | 0.53 | 12362.36 | 07-AUG-15:40 | 2.00 |
September | 0.250397E+10 | 0.44 | 9048.27 | 05-SEP-14:40 | 1.64 |
October | 0.151374E+10 | 0.39 | 4468.05 | 18-OCT-15:40 | 1.07 |
November | 0.143542E+10 | 0.43 | 2877.28 | 13-NOV-05:01 | 0.84 |
December | 0.180457E+10 | 0.51 | 2877.28 | 01-DEC-06:01 | 0.84 |
Annual Sum or Average | 0.292048E+11 | 0.47 | |||
Minimum of Months | 0.143542E+10 | 0.39 | 2877.28 | 0.84 | |
Maximum of Months | 0.503378E+10 | 0.54 | 12598.21 | 2.02 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:03 | 2.06 | 2.06 | 57.20 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 55.69 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 56.05 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 55.43 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:01 | 2.06 | 2.06 | 56.53 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 55.92 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 55.51 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 55.98 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:05 | 2.06 | 2.06 | 55.98 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 56.96 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:05 | 2.06 | 2.06 | 55.33 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:01 | 2.06 | 2.06 | 55.44 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 55.33 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.20 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56.68 | 56.68 | 2041.85 | 7189.09 | 26-JAN-12:12 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.22 | 56.22 | 2087.36 | 7241.39 | 22-FEB-12:07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.48 | 56.48 | 2202.99 | 7219.58 | 03-MAR-12:14 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.22 | 56.22 | 1986.76 | 7033.39 | 04-APR-11:08 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.56 | 57.56 | 1954.16 | 6705.33 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.27 | 57.27 | 1889.12 | 6313.52 | 01-JUN-11:13 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.01 | 56.01 | 1651.41 | 5925.53 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.39 | 56.39 | 1777.91 | 5748.88 | 02-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.52 | 57.52 | 1682.15 | 5873.64 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 55.57 | 55.57 | 1753.07 | 6222.59 | 31-OCT-11:13 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.11 | 56.11 | 1883.10 | 6600.11 | 29-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 55.89 | 55.89 | 1908.60 | 6970.73 | 29-DEC-12:10 |
Annual Sum or Average | 0.00 | 1900.47 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.57 | 55.57 | 1651.41 | 5748.88 | ||
Maximum of Months | 0.00 | 0.00 | 57.56 | 57.56 | 2202.99 | 7241.39 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.259494E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.136919E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.946205E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.549269E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.668053E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.118116E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.183881E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.164186E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.962291E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.522641E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.703568E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.152854E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.145065E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.522641E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.259494E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.238777E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.103881E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.556088E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.243293E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.436168E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.107278E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.169011E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.146364E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.720306E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.285453E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.571459E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.141688E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.118828E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.243293E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.238777E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.417461E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.201477E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.122201E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.413134E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.563273E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.107639E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.172132E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.145360E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.717018E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.421940E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.125730E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.291269E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.179480E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.413134E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.417461E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.164882E+10 | 0.00 | 0.470163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139768E+10 | 0.342348E+09 | 0.255993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168252E+10 | 0.802299E+09 | 0.163977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179214E+10 | 0.345471E+10 | 0.547210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.240742E+10 | 0.863717E+10 | 0.368052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.462338E+10 | 0.273280E+11 | 0.348423E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.609783E+10 | 0.472985E+11 | 27296958.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587837E+10 | 0.404883E+11 | 0.184320E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.375549E+10 | 0.208345E+11 | 0.842046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.235477E+10 | 0.688767E+10 | 0.285572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161671E+10 | 0.155957E+10 | 0.111715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143506E+10 | 2754552.26 | 0.296282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.346902E+11 | 0.157636E+12 | 0.143223E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139768E+10 | 0.00 | 27296958.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.609783E+10 | 0.472985E+11 | 0.470163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.154951E+10 | 0.00 | 0.443189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126905E+10 | 0.288782E+09 | 0.221274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145908E+10 | 0.193987E+09 | 0.135209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153477E+10 | 0.193474E+10 | 0.421083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.214855E+10 | 0.713833E+10 | 0.284275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.428164E+10 | 0.256998E+11 | 0.201398E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.567126E+10 | 0.432731E+11 | 1348412.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.526432E+10 | 0.365075E+11 | 32182324.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.292359E+10 | 0.168267E+11 | 0.888796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166874E+10 | 0.332911E+10 | 0.312195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129840E+10 | 0.276943E+09 | 0.112237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138372E+10 | 0.00 | 0.282030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.304526E+11 | 0.135469E+12 | 0.130693E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126905E+10 | 0.00 | 1348412.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.567126E+10 | 0.432731E+11 | 0.443189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.199265E+10 | 0.00 | 0.649014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146589E+10 | 0.264634E+09 | 0.331520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159304E+10 | 0.285920E+09 | 0.210212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149925E+10 | 0.195571E+10 | 0.634334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.202489E+10 | 0.752284E+10 | 0.434741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.378237E+10 | 0.275800E+11 | 0.323932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.503378E+10 | 0.465471E+11 | 9607876.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.455517E+10 | 0.384518E+11 | 0.114020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.250397E+10 | 0.170974E+11 | 0.136359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151374E+10 | 0.302517E+10 | 0.514331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143542E+10 | 0.174467E+09 | 0.188895E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.180457E+10 | 0.00 | 0.449712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.292048E+11 | 0.142905E+12 | 0.200580E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143542E+10 | 0.00 | 9607876.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.503378E+10 | 0.465471E+11 | 0.649014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.164882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139768E+10 | 0.00 | 0.00 | 0.00 | 93105349.85 | 0.122011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168252E+10 | 0.00 | 0.00 | 0.00 | 0.222753E+09 | 0.755678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179214E+10 | 0.00 | 0.00 | 0.00 | 0.915127E+09 | 0.278543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.240742E+10 | 0.00 | 0.00 | 0.00 | 0.223806E+10 | 0.203506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.462338E+10 | 0.00 | 0.00 | 0.00 | 0.687609E+10 | 0.312116E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.609783E+10 | 0.00 | 0.00 | 0.00 | 0.122630E+11 | 27267688.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587837E+10 | 0.00 | 0.00 | 0.00 | 0.103572E+11 | 0.182995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.375549E+10 | 0.00 | 0.00 | 0.00 | 0.528147E+10 | 0.585961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.235477E+10 | 0.00 | 0.00 | 0.00 | 0.174928E+10 | 0.112237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161671E+10 | 0.00 | 0.00 | 0.00 | 0.422675E+09 | 0.499629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143506E+10 | 0.00 | 0.00 | 0.00 | 810028.89 | 0.138495E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.346902E+11 | 0.00 | 0.00 | 0.00 | 0.404196E+11 | 0.699554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27267688.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.609783E+10 | 0.00 | 0.00 | 0.00 | 0.122630E+11 | 0.243006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.154951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126905E+10 | 0.00 | 0.00 | 0.00 | 79783256.71 | 0.903930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145908E+10 | 0.00 | 0.00 | 0.00 | 54209183.80 | 0.404760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153477E+10 | 0.00 | 0.00 | 0.00 | 0.508952E+09 | 0.389212E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.214855E+10 | 0.00 | 0.00 | 0.00 | 0.181294E+10 | 0.400188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.428164E+10 | 0.00 | 0.00 | 0.00 | 0.644619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.567126E+10 | 0.00 | 0.00 | 0.00 | 0.112299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.526432E+10 | 0.00 | 0.00 | 0.00 | 0.937207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.292359E+10 | 0.00 | 0.00 | 0.00 | 0.426224E+10 | 17233868.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166874E+10 | 0.00 | 0.00 | 0.00 | 0.845371E+09 | 0.340422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129840E+10 | 0.00 | 0.00 | 0.00 | 79292070.51 | 0.433690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.304526E+11 | 0.00 | 0.00 | 0.00 | 0.346909E+11 | 0.536841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.567126E+10 | 0.00 | 0.00 | 0.00 | 0.112299E+11 | 0.223282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.199265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146589E+10 | 0.00 | 0.00 | 0.00 | 74280598.64 | 0.186075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159304E+10 | 0.00 | 0.00 | 0.00 | 80231868.06 | 0.105468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149925E+10 | 0.00 | 0.00 | 0.00 | 0.522587E+09 | 0.210950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.202489E+10 | 0.00 | 0.00 | 0.00 | 0.192341E+10 | 0.168443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.378237E+10 | 0.00 | 0.00 | 0.00 | 0.696758E+10 | 13939807.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.503378E+10 | 0.00 | 0.00 | 0.00 | 0.121794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.455517E+10 | 0.00 | 0.00 | 0.00 | 0.997416E+10 | 6680641.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.250397E+10 | 0.00 | 0.00 | 0.00 | 0.438496E+10 | 0.281249E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151374E+10 | 0.00 | 0.00 | 0.00 | 0.784653E+09 | 0.192101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143542E+10 | 0.00 | 0.00 | 0.00 | 50471081.35 | 0.110871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.180457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.292048E+11 | 0.00 | 0.00 | 0.00 | 0.369417E+11 | 0.113334E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.503378E+10 | 0.00 | 0.00 | 0.00 | 0.121794E+11 | 0.397535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.127938E+11 | 0.00 | 0.00 | 3384563.14 | 0.00 | 0.136334E+09 | 0.482779E+10 | 0.00 | 0.27 |
February | 0.782849E+10 | 0.00 | 0.00 | 10213758.99 | 0.00 | 5551865.30 | 0.795900E+10 | 0.00 | 0.34 |
March | 0.451066E+10 | 0.00 | 0.00 | 24323666.49 | 0.00 | 1398685.53 | 0.142992E+11 | 0.00 | 0.40 |
April | 0.128402E+10 | 0.00 | 0.00 | 30106170.98 | 0.00 | 0.00 | 0.151851E+11 | 0.00 | 0.51 |
May | 0.108164E+10 | 17798376.01 | 0.00 | 36318047.39 | 2854117.11 | 0.00 | 0.164770E+11 | 0.00 | 0.72 |
June | 0.500636E+09 | 0.186186E+09 | 0.00 | 42895102.22 | 28813134.19 | 0.00 | 0.153055E+11 | 0.00 | 1.04 |
July | 0.487827E+09 | 0.385109E+09 | 0.00 | 35196840.43 | 23197376.88 | 0.00 | 0.801052E+10 | 0.00 | 0.85 |
August | 0.441728E+09 | 0.216272E+09 | 0.00 | 43846517.06 | 20144875.53 | 0.00 | 0.127462E+11 | 0.00 | 1.01 |
September | 0.599096E+09 | 0.262531E+09 | 0.00 | 40701481.03 | 19771486.41 | 0.00 | 0.158917E+11 | 0.00 | 0.90 |
October | 0.914884E+09 | 0.00 | 0.00 | 39273192.45 | 0.00 | 0.00 | 0.173834E+11 | 0.00 | 0.65 |
November | 0.329203E+10 | 0.00 | 0.00 | 25631653.83 | 0.00 | 0.00 | 0.134637E+11 | 0.00 | 0.44 |
December | 0.964132E+10 | 0.00 | 0.00 | 11485673.69 | 0.00 | 3194988.13 | 0.803929E+10 | 0.00 | 0.32 |
Annual Sum or Average | 0.433762E+11 | 0.106790E+10 | 0.00 | 0.343377E+09 | 94780990.12 | 0.146479E+09 | 0.149588E+12 | 0.00 | 0.62 |
Minimum of Months | 0.441728E+09 | 0.00 | 0.00 | 3384563.14 | 0.00 | 0.00 | 0.482779E+10 | 0.00 | 0.27 |
Maximum of Months | 0.127938E+11 | 0.385109E+09 | 0.00 | 43846517.06 | 28813134.19 | 0.136334E+09 | 0.173834E+11 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418520E+10 | 0.00 | 0.00 | 0.27 |
February | 0.123243E+11 | 0.00 | 0.00 | 397356.89 | 0.00 | 0.124812E+10 | 0.269163E+09 | 0.00 | 0.29 |
March | 0.112103E+11 | 0.00 | 0.00 | 2285015.78 | 0.00 | 0.388784E+09 | 0.273530E+10 | 0.00 | 0.31 |
April | 0.554001E+10 | 0.00 | 0.00 | 8815566.54 | 0.00 | 0.00 | 0.649761E+10 | 0.00 | 0.39 |
May | 0.417227E+10 | 9640687.26 | 0.00 | 14915112.52 | 6123631.21 | 2098281.87 | 0.792764E+10 | 0.00 | 0.49 |
June | 0.108924E+10 | 0.136708E+09 | 0.00 | 26137420.50 | 23690246.43 | 0.00 | 0.953511E+10 | 0.00 | 0.71 |
July | 0.732341E+09 | 0.269723E+09 | 0.00 | 23363416.24 | 16387402.05 | 0.00 | 0.518109E+10 | 0.00 | 0.61 |
August | 0.872796E+09 | 0.154765E+09 | 0.00 | 27317659.08 | 19606296.73 | 0.00 | 0.788302E+10 | 0.00 | 0.69 |
September | 0.195289E+10 | 0.193153E+09 | 0.00 | 19920430.33 | 18551170.87 | 0.00 | 0.888610E+10 | 0.00 | 0.59 |
October | 0.481886E+10 | 0.00 | 0.00 | 11875052.27 | 0.00 | 2627879.06 | 0.713201E+10 | 0.00 | 0.42 |
November | 0.919497E+10 | 0.00 | 0.00 | 3148466.20 | 0.00 | 0.388363E+09 | 0.237961E+10 | 0.00 | 0.31 |
December | 0.132383E+11 | 0.00 | 0.00 | 20081.37 | 0.00 | 0.193007E+10 | 72053529.96 | 0.00 | 0.28 |
Annual Sum or Average | 0.783942E+11 | 0.763989E+09 | 0.00 | 0.138196E+09 | 84358747.29 | 0.814527E+10 | 0.584987E+11 | 0.00 | 0.45 |
Minimum of Months | 0.732341E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.132479E+11 | 0.269723E+09 | 0.00 | 27317659.08 | 23690246.43 | 0.418520E+10 | 0.953511E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.649136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901917E+10 | 0.00 | 0.00 | 0.26 |
February | 0.875834E+10 | 0.00 | 0.00 | 159478.36 | 0.00 | 0.375486E+10 | 0.118345E+09 | 0.00 | 0.28 |
March | 0.110284E+11 | 0.00 | 0.00 | 705513.63 | 0.00 | 0.153667E+10 | 0.705594E+09 | 0.00 | 0.30 |
April | 0.740866E+10 | 0.00 | 0.00 | 5195852.69 | 0.00 | 96000601.27 | 0.365254E+10 | 0.00 | 0.37 |
May | 0.520088E+10 | 3573180.20 | 0.00 | 11578188.34 | 1812621.13 | 0.101354E+09 | 0.629166E+10 | 0.00 | 0.48 |
June | 0.157123E+10 | 98934814.73 | 0.00 | 24283331.16 | 5279852.94 | 0.00 | 0.847631E+10 | 0.00 | 0.71 |
July | 0.949473E+09 | 0.206114E+09 | 0.00 | 22248054.99 | 17195196.74 | 0.00 | 0.456457E+10 | 0.00 | 0.62 |
August | 0.123794E+10 | 0.107291E+09 | 0.00 | 24579133.40 | 16719099.23 | 0.00 | 0.655613E+10 | 0.00 | 0.66 |
September | 0.322750E+10 | 0.186381E+09 | 0.00 | 13987644.05 | 13390439.40 | 895911.35 | 0.603790E+10 | 0.00 | 0.54 |
October | 0.661101E+10 | 0.00 | 0.00 | 5337506.39 | 0.00 | 0.113109E+09 | 0.356690E+10 | 0.00 | 0.38 |
November | 0.842285E+10 | 0.00 | 0.00 | 645924.31 | 0.00 | 0.157991E+10 | 0.722289E+09 | 0.00 | 0.29 |
December | 0.813225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545676E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.690398E+11 | 0.602294E+09 | 0.00 | 0.108721E+09 | 54397209.43 | 0.216587E+11 | 0.406922E+11 | 0.00 | 0.43 |
Minimum of Months | 0.949473E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.110284E+11 | 0.206114E+09 | 0.00 | 24579133.40 | 17195196.74 | 0.901917E+10 | 0.847631E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 61199581.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557848E+10 | 0.00 | 0.00 | 0.40 |
February | 0.442767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306388E+10 | 0.00 | 0.00 | 0.35 |
March | 0.127067E+10 | 0.00 | 0.00 | 1736.97 | 0.00 | 0.178050E+10 | 8458557.81 | 0.00 | 0.32 |
April | 0.149971E+10 | 0.00 | 0.00 | 572545.60 | 0.00 | 0.429207E+09 | 0.376496E+09 | 0.00 | 0.36 |
May | 0.114044E+10 | 1729313.60 | 0.00 | 2485568.14 | 381827.14 | 0.257786E+09 | 0.113304E+10 | 0.00 | 0.53 |
June | 0.455087E+09 | 33763217.44 | 0.00 | 6373083.53 | 1112196.66 | 735069.95 | 0.192369E+10 | 0.00 | 0.88 |
July | 0.218937E+09 | 73857050.06 | 0.00 | 6308261.14 | 3085190.90 | 0.00 | 0.111272E+10 | 0.00 | 0.78 |
August | 0.413649E+09 | 41237689.18 | 0.00 | 5668517.85 | 3521864.44 | 246559.47 | 0.128002E+10 | 0.00 | 0.75 |
September | 0.960997E+09 | 55483990.77 | 0.00 | 2303767.10 | 2821461.50 | 69031184.10 | 0.796570E+09 | 0.00 | 0.54 |
October | 0.140975E+10 | 0.00 | 0.00 | 421691.88 | 0.00 | 0.448518E+09 | 0.244805E+09 | 0.00 | 0.36 |
November | 0.788687E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172157E+10 | 0.00 | 0.00 | 0.31 |
December | 0.224394E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383833E+10 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.888629E+10 | 0.206071E+09 | 0.00 | 24135172.22 | 10922540.64 | 0.171883E+11 | 0.687580E+10 | 0.00 | 0.49 |
Minimum of Months | 61199581.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.149971E+10 | 73857050.06 | 0.00 | 6373083.53 | 3521864.44 | 0.557848E+10 | 0.192369E+10 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.148957E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321786E+10 | 0.00 | 0.00 | 0.38 |
February | 0.463487E+09 | 0.00 | 0.00 | 99792.26 | 0.00 | 0.162390E+10 | 60619581.10 | 0.00 | 0.34 |
March | 0.868783E+09 | 0.00 | 0.00 | 722151.08 | 0.00 | 0.819744E+09 | 0.375089E+09 | 0.00 | 0.35 |
April | 0.742452E+09 | 0.00 | 0.00 | 2531460.37 | 0.00 | 0.181747E+09 | 0.134999E+10 | 0.00 | 0.59 |
May | 0.499533E+09 | 1338364.43 | 0.00 | 4424408.54 | 232389.78 | 0.121816E+09 | 0.215514E+10 | 0.00 | 0.92 |
June | 0.188751E+09 | 27484894.07 | 0.00 | 9609411.44 | 695603.80 | 344240.46 | 0.271295E+10 | 0.00 | 1.65 |
July | 87744967.35 | 62228985.56 | 0.00 | 10577665.76 | 1117432.51 | 0.00 | 0.186661E+10 | 0.00 | 1.65 |
August | 0.186915E+09 | 42514779.67 | 0.00 | 8198744.03 | 1640827.36 | 0.00 | 0.212946E+10 | 0.00 | 1.54 |
September | 0.451427E+09 | 48003681.11 | 0.00 | 3845599.11 | 1171606.72 | 25181394.77 | 0.146042E+10 | 0.00 | 0.93 |
October | 0.766195E+09 | 0.00 | 0.00 | 1272347.70 | 0.00 | 0.176735E+09 | 0.649838E+09 | 0.00 | 0.47 |
November | 0.654657E+09 | 0.00 | 0.00 | 55126.97 | 0.00 | 0.885961E+09 | 42644490.21 | 0.00 | 0.31 |
December | 0.260995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223970E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.531990E+10 | 0.181571E+09 | 0.00 | 41336707.25 | 4857860.15 | 0.929299E+10 | 0.128028E+11 | 0.00 | 0.79 |
Minimum of Months | 87744967.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.868783E+09 | 62228985.56 | 0.00 | 10577665.76 | 1640827.36 | 0.321786E+10 | 0.271295E+10 | 0.00 | 1.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.589627E+09 | 0.00 | 0.00 | 769374.90 | 0.00 | 0.372634E+10 | 0.630911E+09 | 0.00 | 0.36 |
February | 0.837837E+09 | 0.00 | 0.00 | 2851914.94 | 0.00 | 0.177953E+10 | 0.147313E+10 | 0.00 | 0.48 |
March | 0.119301E+10 | 0.00 | 0.00 | 4850625.73 | 0.00 | 0.113420E+10 | 0.240438E+10 | 0.00 | 0.53 |
April | 0.108048E+10 | 0.00 | 0.00 | 5002205.88 | 0.00 | 0.350325E+09 | 0.261649E+10 | 0.00 | 0.71 |
May | 0.851116E+09 | 2704656.26 | 0.00 | 6310285.76 | 364947.82 | 0.257782E+09 | 0.292564E+10 | 0.00 | 0.88 |
June | 0.453830E+09 | 47231701.17 | 0.00 | 9557637.87 | 1079679.75 | 4280400.80 | 0.270457E+10 | 0.00 | 1.18 |
July | 0.233604E+09 | 0.107681E+09 | 0.00 | 10031911.92 | 1475142.71 | 0.00 | 0.163031E+10 | 0.00 | 1.10 |
August | 0.358876E+09 | 82573441.61 | 0.00 | 11536720.44 | 2008349.91 | 1014936.15 | 0.249104E+10 | 0.00 | 1.35 |
September | 0.677565E+09 | 0.136432E+09 | 0.00 | 8711618.42 | 667815.72 | 43418455.25 | 0.313268E+10 | 0.00 | 1.26 |
October | 0.912317E+09 | 0.00 | 0.00 | 7832199.50 | 0.00 | 0.216867E+09 | 0.351828E+10 | 0.00 | 0.95 |
November | 0.864451E+09 | 0.00 | 0.00 | 3621048.04 | 0.00 | 0.100226E+10 | 0.191452E+10 | 0.00 | 0.50 |
December | 0.793795E+09 | 0.00 | 0.00 | 1246184.23 | 0.00 | 0.248389E+10 | 0.767060E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.884651E+10 | 0.376622E+09 | 0.00 | 72321727.62 | 5595935.92 | 0.109999E+11 | 0.262090E+11 | 0.00 | 0.81 |
Minimum of Months | 0.233604E+09 | 0.00 | 0.00 | 769374.90 | 0.00 | 0.00 | 0.630911E+09 | 0.00 | 0.36 |
Maximum of Months | 0.119301E+10 | 0.136432E+09 | 0.00 | 11536720.44 | 2008349.91 | 0.372634E+10 | 0.351828E+10 | 0.00 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.195078E+09 | 0.00 | 0.00 | 43.62 | 0.00 | 0.336005E+10 | 1069927.10 | 0.00 | 0.40 |
February | 0.423089E+09 | 0.00 | 0.00 | 283707.54 | 0.00 | 0.171130E+10 | 0.142194E+09 | 0.00 | 0.37 |
March | 0.772511E+09 | 0.00 | 0.00 | 942215.11 | 0.00 | 0.980480E+09 | 0.498672E+09 | 0.00 | 0.38 |
April | 0.788847E+09 | 0.00 | 0.00 | 2338918.97 | 0.00 | 0.232210E+09 | 0.120612E+10 | 0.00 | 0.63 |
May | 0.520221E+09 | 1524772.53 | 0.00 | 5068956.86 | 240590.12 | 0.153733E+09 | 0.212939E+10 | 0.00 | 0.98 |
June | 0.264882E+09 | 38560376.93 | 0.00 | 7874834.98 | 67101.90 | 2702755.47 | 0.198167E+10 | 0.00 | 1.38 |
July | 0.126543E+09 | 86639136.36 | 0.00 | 7687458.16 | 493566.48 | 0.00 | 0.108989E+10 | 0.00 | 1.17 |
August | 0.236800E+09 | 46807427.52 | 0.00 | 6474292.87 | 787454.30 | 1431699.58 | 0.130947E+10 | 0.00 | 1.19 |
September | 0.507629E+09 | 80244506.68 | 0.00 | 3330899.62 | 253504.52 | 40634682.83 | 0.117685E+10 | 0.00 | 0.89 |
October | 0.753916E+09 | 0.00 | 0.00 | 1557342.35 | 0.00 | 0.240472E+09 | 0.783963E+09 | 0.00 | 0.54 |
November | 0.565921E+09 | 0.00 | 0.00 | 274055.83 | 0.00 | 0.914035E+09 | 0.206077E+09 | 0.00 | 0.34 |
December | 0.290125E+09 | 0.00 | 0.00 | 9433.25 | 0.00 | 0.226637E+10 | 9737376.65 | 0.00 | 0.35 |
Annual Sum or Average | 0.544556E+10 | 0.253776E+09 | 0.00 | 35842159.17 | 1842217.32 | 0.990341E+10 | 0.105351E+11 | 0.00 | 0.72 |
Minimum of Months | 0.126543E+09 | 0.00 | 0.00 | 43.62 | 0.00 | 0.00 | 1069927.10 | 0.00 | 0.34 |
Maximum of Months | 0.788847E+09 | 86639136.36 | 0.00 | 7874834.98 | 787454.30 | 0.336005E+10 | 0.212939E+10 | 0.00 | 1.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 71300246.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523974E+10 | 0.00 | 0.00 | 0.36 |
February | 0.476069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295725E+10 | 0.00 | 0.00 | 0.32 |
March | 0.112034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180524E+10 | 0.00 | 0.00 | 0.29 |
April | 0.158209E+10 | 0.00 | 0.00 | 17488.61 | 0.00 | 0.388863E+09 | 7150845.71 | 0.00 | 0.28 |
May | 0.141477E+10 | 1582737.40 | 0.00 | 891097.90 | 1676117.70 | 0.131031E+09 | 0.355414E+09 | 0.00 | 0.37 |
June | 0.471956E+09 | 32974949.83 | 0.00 | 4061460.13 | 6084242.36 | 0.00 | 0.127140E+10 | 0.00 | 0.62 |
July | 0.210153E+09 | 86022441.23 | 0.00 | 4449275.97 | 4898407.17 | 0.00 | 0.870173E+09 | 0.00 | 0.59 |
August | 0.377093E+09 | 48040253.68 | 0.00 | 4245844.50 | 4253834.52 | 0.00 | 0.109052E+10 | 0.00 | 0.61 |
September | 0.901891E+09 | 47593298.48 | 0.00 | 2229577.89 | 4174988.89 | 481299.59 | 0.794736E+09 | 0.00 | 0.49 |
October | 0.158948E+10 | 0.00 | 0.00 | 486882.49 | 0.00 | 75524459.52 | 0.254319E+09 | 0.00 | 0.31 |
November | 0.130941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108449E+10 | 0.00 | 0.00 | 0.28 |
December | 0.424695E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328613E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.994925E+10 | 0.216214E+09 | 0.00 | 16381627.49 | 21087590.63 | 0.149687E+11 | 0.464371E+10 | 0.00 | 0.40 |
Minimum of Months | 71300246.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.158948E+10 | 86022441.23 | 0.00 | 4449275.97 | 6084242.36 | 0.523974E+10 | 0.127140E+10 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.189044E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311943E+10 | 0.00 | 0.00 | 0.35 |
February | 0.548802E+09 | 0.00 | 0.00 | 74040.23 | 0.00 | 0.153433E+10 | 43819123.49 | 0.00 | 0.32 |
March | 0.100384E+10 | 0.00 | 0.00 | 342802.92 | 0.00 | 0.694136E+09 | 0.173416E+09 | 0.00 | 0.29 |
April | 0.837031E+09 | 0.00 | 0.00 | 1457490.43 | 0.00 | 0.103385E+09 | 0.670282E+09 | 0.00 | 0.39 |
May | 0.593885E+09 | 2714056.53 | 0.00 | 3056254.09 | 381912.75 | 50046292.38 | 0.125661E+10 | 0.00 | 0.64 |
June | 0.155257E+09 | 37749392.57 | 0.00 | 7266019.62 | 3725245.56 | 0.00 | 0.217879E+10 | 0.00 | 1.32 |
July | 65590161.52 | 88921216.68 | 0.00 | 8247945.93 | 2174263.35 | 0.00 | 0.162996E+10 | 0.00 | 1.37 |
August | 0.128868E+09 | 55137522.26 | 0.00 | 7378515.42 | 2592262.52 | 0.00 | 0.203419E+10 | 0.00 | 1.38 |
September | 0.339990E+09 | 43531877.07 | 0.00 | 4235399.36 | 2161948.85 | 0.00 | 0.153572E+10 | 0.00 | 0.89 |
October | 0.708305E+09 | 0.00 | 0.00 | 2055129.00 | 0.00 | 14958446.59 | 0.864952E+09 | 0.00 | 0.46 |
November | 0.852115E+09 | 0.00 | 0.00 | 218544.06 | 0.00 | 0.552626E+09 | 0.128633E+09 | 0.00 | 0.28 |
December | 0.510250E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182829E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.593298E+10 | 0.228054E+09 | 0.00 | 34332141.07 | 11035633.04 | 0.789721E+10 | 0.105164E+11 | 0.00 | 0.67 |
Minimum of Months | 65590161.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.100384E+10 | 88921216.68 | 0.00 | 8247945.93 | 3725245.56 | 0.311943E+10 | 0.217879E+10 | 0.00 | 1.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.511784E+09 | 0.00 | 0.00 | 22395.07 | 0.00 | 0.700132E+10 | 28288693.13 | 0.00 | 0.50 |
February | 0.746176E+09 | 0.00 | 0.00 | 1059200.56 | 0.00 | 0.381125E+10 | 0.486874E+09 | 0.00 | 0.50 |
March | 0.113402E+10 | 0.00 | 0.00 | 1049974.66 | 0.00 | 0.249744E+10 | 0.520622E+09 | 0.00 | 0.41 |
April | 0.959089E+09 | 0.00 | 0.00 | 1261581.48 | 0.00 | 0.122158E+10 | 0.592295E+09 | 0.00 | 0.41 |
May | 0.106565E+10 | 4390394.28 | 0.00 | 2153086.86 | 961692.38 | 0.839154E+09 | 0.708887E+09 | 0.00 | 0.53 |
June | 0.678840E+09 | 59499311.56 | 0.00 | 4622882.10 | 5827473.90 | 0.124699E+09 | 0.112106E+10 | 0.00 | 0.75 |
July | 0.286538E+09 | 0.156715E+09 | 0.00 | 6384419.85 | 3523388.12 | 14377268.49 | 0.989543E+09 | 0.00 | 0.81 |
August | 0.384683E+09 | 0.111608E+09 | 0.00 | 8398683.08 | 3235054.79 | 88152365.06 | 0.168257E+10 | 0.00 | 1.07 |
September | 0.619526E+09 | 0.126772E+09 | 0.00 | 6866547.32 | 942469.02 | 0.236503E+09 | 0.212891E+10 | 0.00 | 1.01 |
October | 0.952871E+09 | 0.00 | 0.00 | 5924806.74 | 0.00 | 0.505741E+09 | 0.214409E+10 | 0.00 | 0.73 |
November | 0.115102E+10 | 0.00 | 0.00 | 1764766.63 | 0.00 | 0.166674E+10 | 0.854673E+09 | 0.00 | 0.43 |
December | 0.851926E+09 | 0.00 | 0.00 | 173662.89 | 0.00 | 0.443308E+10 | 0.159743E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.934213E+10 | 0.458984E+09 | 0.00 | 39682007.25 | 14490078.21 | 0.224400E+11 | 0.114176E+11 | 0.00 | 0.63 |
Minimum of Months | 0.286538E+09 | 0.00 | 0.00 | 22395.07 | 0.00 | 14377268.49 | 28288693.13 | 0.00 | 0.41 |
Maximum of Months | 0.115102E+10 | 0.156715E+09 | 0.00 | 8398683.08 | 5827473.90 | 0.700132E+10 | 0.214409E+10 | 0.00 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.181053E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327964E+10 | 0.00 | 0.00 | 0.37 |
February | 0.519795E+09 | 0.00 | 0.00 | 143527.77 | 0.00 | 0.157938E+10 | 68099577.23 | 0.00 | 0.33 |
March | 0.975833E+09 | 0.00 | 0.00 | 387024.15 | 0.00 | 0.794046E+09 | 0.169625E+09 | 0.00 | 0.30 |
April | 0.924193E+09 | 0.00 | 0.00 | 1029343.68 | 0.00 | 0.119687E+09 | 0.458017E+09 | 0.00 | 0.38 |
May | 0.598019E+09 | 1913309.55 | 0.00 | 3193325.57 | 985180.18 | 48389690.96 | 0.115662E+10 | 0.00 | 0.64 |
June | 0.215449E+09 | 47924398.62 | 0.00 | 5283441.36 | 1615093.39 | 0.00 | 0.152871E+10 | 0.00 | 1.04 |
July | 90771500.31 | 0.112436E+09 | 0.00 | 5487563.30 | 1390877.55 | 0.00 | 0.971401E+09 | 0.00 | 0.98 |
August | 0.166695E+09 | 62311859.53 | 0.00 | 5398676.67 | 1415054.37 | 0.00 | 0.124637E+10 | 0.00 | 1.04 |
September | 0.398152E+09 | 67496723.93 | 0.00 | 3440265.64 | 1028561.27 | 0.00 | 0.116788E+10 | 0.00 | 0.80 |
October | 0.788721E+09 | 0.00 | 0.00 | 1785733.57 | 0.00 | 21875919.99 | 0.737354E+09 | 0.00 | 0.46 |
November | 0.867412E+09 | 0.00 | 0.00 | 305287.60 | 0.00 | 0.547451E+09 | 0.172069E+09 | 0.00 | 0.29 |
December | 0.448141E+09 | 0.00 | 0.00 | 4774.20 | 0.00 | 0.192717E+10 | 6793429.57 | 0.00 | 0.30 |
Annual Sum or Average | 0.617424E+10 | 0.292082E+09 | 0.00 | 26458963.51 | 6434766.76 | 0.831764E+10 | 0.768293E+10 | 0.00 | 0.58 |
Minimum of Months | 90771500.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.975833E+09 | 0.112436E+09 | 0.00 | 5487563.30 | 1615093.39 | 0.327964E+10 | 0.152871E+10 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.122264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501070E+10 | 0.00 | 0.00 | 0.35 |
February | 0.732747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254273E+10 | 0.00 | 0.00 | 0.32 |
March | 0.193477E+10 | 0.00 | 0.00 | 11683.57 | 0.00 | 0.111371E+10 | 27162187.58 | 0.00 | 0.31 |
April | 0.179341E+10 | 0.00 | 0.00 | 722049.70 | 0.00 | 0.135591E+09 | 0.447579E+09 | 0.00 | 0.36 |
May | 0.123408E+10 | 4046370.15 | 0.00 | 2788269.21 | 1287485.41 | 85329169.53 | 0.119535E+10 | 0.00 | 0.53 |
June | 0.366718E+09 | 47856656.26 | 0.00 | 6496065.38 | 4980843.16 | 0.00 | 0.206992E+10 | 0.00 | 0.86 |
July | 0.183223E+09 | 0.101015E+09 | 0.00 | 6111734.96 | 3445429.73 | 0.00 | 0.120020E+10 | 0.00 | 0.76 |
August | 0.343968E+09 | 60511686.82 | 0.00 | 5693062.53 | 4122198.10 | 0.00 | 0.144246E+10 | 0.00 | 0.76 |
September | 0.967850E+09 | 59458405.54 | 0.00 | 2797994.41 | 3900359.28 | 5344779.87 | 0.101195E+10 | 0.00 | 0.56 |
October | 0.167735E+10 | 0.00 | 0.00 | 745038.39 | 0.00 | 0.134857E+09 | 0.420001E+09 | 0.00 | 0.37 |
November | 0.138247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117423E+10 | 0.00 | 0.00 | 0.30 |
December | 0.498093E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325891E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.112369E+11 | 0.272889E+09 | 0.00 | 25365898.16 | 17736315.68 | 0.134614E+11 | 0.781461E+10 | 0.00 | 0.48 |
Minimum of Months | 0.122264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.193477E+10 | 0.101015E+09 | 0.00 | 6496065.38 | 4980843.16 | 0.501070E+10 | 0.206992E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.203050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272017E+10 | 0.00 | 0.00 | 0.31 |
February | 0.472596E+09 | 0.00 | 0.00 | 199125.78 | 0.00 | 0.126980E+10 | 98675570.66 | 0.00 | 0.28 |
March | 0.927977E+09 | 0.00 | 0.00 | 946874.98 | 0.00 | 0.509309E+09 | 0.466230E+09 | 0.00 | 0.31 |
April | 0.756057E+09 | 0.00 | 0.00 | 2804911.12 | 0.00 | 38255727.08 | 0.139269E+10 | 0.00 | 0.56 |
May | 0.469874E+09 | 4659840.12 | 0.00 | 4589563.13 | 424008.32 | 46976500.21 | 0.210341E+10 | 0.00 | 0.87 |
June | 0.139664E+09 | 39365855.92 | 0.00 | 9236399.73 | 2558928.97 | 0.00 | 0.268670E+10 | 0.00 | 1.55 |
July | 72213699.22 | 81911153.94 | 0.00 | 9745031.66 | 1543027.45 | 0.00 | 0.186680E+10 | 0.00 | 1.52 |
August | 0.144456E+09 | 54882270.46 | 0.00 | 7969603.35 | 2556145.72 | 0.00 | 0.219207E+10 | 0.00 | 1.47 |
September | 0.388574E+09 | 47979782.03 | 0.00 | 4268220.34 | 2106606.11 | 1158605.93 | 0.161032E+10 | 0.00 | 0.92 |
October | 0.729134E+09 | 0.00 | 0.00 | 1826918.64 | 0.00 | 47987120.24 | 0.875317E+09 | 0.00 | 0.47 |
November | 0.709433E+09 | 0.00 | 0.00 | 219477.50 | 0.00 | 0.572743E+09 | 0.150437E+09 | 0.00 | 0.27 |
December | 0.396431E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172693E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.540946E+10 | 0.228799E+09 | 0.00 | 41806126.23 | 9188716.56 | 0.693333E+10 | 0.134427E+11 | 0.00 | 0.74 |
Minimum of Months | 72213699.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.927977E+09 | 81911153.94 | 0.00 | 9745031.66 | 2558928.97 | 0.272017E+10 | 0.268670E+10 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.829839E+09 | 0.00 | 0.00 | 1159750.65 | 0.00 | 0.328768E+10 | 0.914337E+09 | 0.00 | 0.36 |
February | 0.105903E+10 | 0.00 | 0.00 | 3617134.63 | 0.00 | 0.144146E+10 | 0.180962E+10 | 0.00 | 0.51 |
March | 0.160962E+10 | 0.00 | 0.00 | 5652730.55 | 0.00 | 0.736292E+09 | 0.262148E+10 | 0.00 | 0.56 |
April | 0.130450E+10 | 0.00 | 0.00 | 5565065.80 | 0.00 | 0.104372E+09 | 0.270511E+10 | 0.00 | 0.73 |
May | 0.957117E+09 | 11585649.09 | 0.00 | 6644375.92 | 670870.15 | 93514435.13 | 0.283374E+10 | 0.00 | 0.87 |
June | 0.389795E+09 | 74065751.19 | 0.00 | 9053396.27 | 2321794.15 | 0.00 | 0.267808E+10 | 0.00 | 1.14 |
July | 0.212229E+09 | 0.150656E+09 | 0.00 | 8986624.84 | 2055583.53 | 0.00 | 0.154356E+10 | 0.00 | 1.02 |
August | 0.303348E+09 | 0.122767E+09 | 0.00 | 10971159.12 | 2892208.84 | 0.00 | 0.246432E+10 | 0.00 | 1.31 |
September | 0.640366E+09 | 0.150020E+09 | 0.00 | 9253995.13 | 1089017.11 | 2152160.98 | 0.332141E+10 | 0.00 | 1.28 |
October | 0.100034E+10 | 0.00 | 0.00 | 9511332.81 | 0.00 | 61085578.53 | 0.403354E+10 | 0.00 | 1.02 |
November | 0.110982E+10 | 0.00 | 0.00 | 4983595.69 | 0.00 | 0.703792E+09 | 0.244914E+10 | 0.00 | 0.55 |
December | 0.107991E+10 | 0.00 | 0.00 | 1856819.20 | 0.00 | 0.201965E+10 | 0.114720E+10 | 0.00 | 0.37 |
Annual Sum or Average | 0.104959E+11 | 0.509095E+09 | 0.00 | 77255980.60 | 9029473.78 | 0.845000E+10 | 0.285215E+11 | 0.00 | 0.81 |
Minimum of Months | 0.212229E+09 | 0.00 | 0.00 | 1159750.65 | 0.00 | 0.00 | 0.914337E+09 | 0.00 | 0.36 |
Maximum of Months | 0.160962E+10 | 0.150656E+09 | 0.00 | 10971159.12 | 2892208.84 | 0.328768E+10 | 0.403354E+10 | 0.00 | 1.31 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.248537E+09 | 0.00 | 0.00 | 2980.70 | 0.00 | 0.303093E+10 | 3694351.64 | 0.00 | 0.36 |
February | 0.600147E+09 | 0.00 | 0.00 | 348283.05 | 0.00 | 0.139741E+10 | 0.168619E+09 | 0.00 | 0.34 |
March | 0.111343E+10 | 0.00 | 0.00 | 1068482.30 | 0.00 | 0.650794E+09 | 0.533593E+09 | 0.00 | 0.38 |
April | 0.917168E+09 | 0.00 | 0.00 | 2526787.60 | 0.00 | 81835777.89 | 0.125336E+10 | 0.00 | 0.64 |
May | 0.584624E+09 | 3539193.82 | 0.00 | 5234387.18 | 814686.49 | 53406124.49 | 0.204860E+10 | 0.00 | 0.95 |
June | 0.221782E+09 | 58308460.29 | 0.00 | 7061448.40 | 1297998.07 | 0.00 | 0.195759E+10 | 0.00 | 1.31 |
July | 0.106576E+09 | 0.123607E+09 | 0.00 | 6757387.41 | 838627.31 | 0.00 | 0.106600E+10 | 0.00 | 1.10 |
August | 0.199440E+09 | 71970057.74 | 0.00 | 6103918.54 | 771160.42 | 0.00 | 0.134886E+10 | 0.00 | 1.17 |
September | 0.500529E+09 | 86364132.55 | 0.00 | 3658026.28 | 728738.08 | 4521955.26 | 0.129818E+10 | 0.00 | 0.91 |
October | 0.869634E+09 | 0.00 | 0.00 | 2012059.89 | 0.00 | 69366516.81 | 0.961590E+09 | 0.00 | 0.56 |
November | 0.810935E+09 | 0.00 | 0.00 | 435807.70 | 0.00 | 0.665984E+09 | 0.299361E+09 | 0.00 | 0.34 |
December | 0.468476E+09 | 0.00 | 0.00 | 20051.94 | 0.00 | 0.192596E+10 | 17220634.79 | 0.00 | 0.31 |
Annual Sum or Average | 0.664128E+10 | 0.343789E+09 | 0.00 | 35229620.99 | 4451210.37 | 0.788020E+10 | 0.109567E+11 | 0.00 | 0.70 |
Minimum of Months | 0.106576E+09 | 0.00 | 0.00 | 2980.70 | 0.00 | 0.00 | 3694351.64 | 0.00 | 0.31 |
Maximum of Months | 0.111343E+10 | 0.123607E+09 | 0.00 | 7061448.40 | 1297998.07 | 0.303093E+10 | 0.204860E+10 | 0.00 | 1.31 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.146811E+12 | 0.294435E+11 | 0.00 | 0.147501E+12 | 0.174636E+11 |
February | 0.198235E+12 | 0.228090E+11 | 0.00 | 0.140847E+12 | 0.114006E+11 |
March | 0.324092E+12 | 0.219081E+11 | 0.00 | 0.169842E+12 | 0.883654E+10 |
April | 0.343231E+12 | 0.154550E+11 | 0.00 | 0.195711E+12 | 0.119774E+11 |
May | 0.450907E+12 | 0.150503E+11 | 0.00 | 0.205626E+12 | 0.309605E+11 |
June | 0.487082E+12 | 0.739452E+10 | 0.00 | 0.188660E+12 | 0.101035E+12 |
July | 0.484232E+12 | 0.408544E+10 | 0.00 | 0.157569E+12 | 0.172794E+12 |
August | 0.406142E+12 | 0.540546E+10 | 0.00 | 0.183006E+12 | 0.145186E+12 |
September | 0.311337E+12 | 0.100360E+11 | 0.00 | 0.187188E+12 | 0.692398E+11 |
October | 0.208856E+12 | 0.150762E+11 | 0.00 | 0.211564E+12 | 0.185556E+11 |
November | 0.118000E+12 | 0.205298E+11 | 0.00 | 0.166176E+12 | 0.777954E+10 |
December | 0.956403E+11 | 0.256299E+11 | 0.00 | 0.144742E+12 | 0.122150E+11 |
Annual Sum or Average | 0.357457E+13 | 0.192823E+12 | 0.00 | 0.209843E+13 | 0.607443E+12 |
Minimum of Months | 0.956403E+11 | 0.408544E+10 | 0.00 | 0.140847E+12 | 0.777954E+10 |