Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:31
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 08:32:03
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1881.50 | 377.65 | 377.65 |
Net Site Energy | 1881.50 | 377.65 | 377.65 |
Total Source Energy | 5087.05 | 1021.05 | 1021.05 |
Net Source Energy | 5087.05 | 1021.05 | 1021.05 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 243.18 | 283.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 134.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 232.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 51.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 84.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 135.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1463.03 | 418.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 243.18 | 283.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 134.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 232.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 51.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 84.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 135.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 243.18 | 283.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 134.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 232.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 51.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 84.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 135.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 92.79 | 83.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 293.65 | 83.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 92.79 | 83.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 293.65 | 83.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1463.035 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1463.035 | 100.00 |
Total On-Site and Utility Electric Sources | 1463.035 | 100.00 |
Total Electricity End Uses | 1463.035 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 382.17 |
Time Setpoint Not Met During Occupied Cooling | 78.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2733.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:31 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.6636 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.6636 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.6636 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 6.6636 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.6636 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 06-FEB-08:20 | - | - | - | - | - | - | - | - | - | - | 03-JAN-12:09 |
Heating | 195085.73 | 111550.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8334.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 243.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6968.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 9275.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 237424.75 | 120826.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 195085.73 | 111550.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 8334.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 243.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6968.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 9275.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 770.15 | 306.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 424.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 735.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 37.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 268.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 146.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4633.43 | 453.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 154.58 | 61.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 85.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 53.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 29.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 930.00 | 91.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 154.58 | 61.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 85.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 53.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 29.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 930.00 | 91.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.86 | 0.261846 | 0.223000 | 0.638271 | 0.698255 | 0.500000 | 0.001455 |
CORE_MID VAV BOX COMPONENT | 2.09 | 0.358648 | 0.305000 | 0.637349 | 0.956394 | 0.500000 | 0.001062 |
CORE_TOP VAV BOX COMPONENT | 2.17 | 0.345152 | 0.293000 | 0.636213 | 0.920406 | 0.500000 | 0.001104 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.680918 | 0.232028 | 0.197000 | 0.134141 | 0.618740 | 0.500000 | 0.001642 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.800972 | 0.124876 | 0.106000 | 0.084903 | 0.333002 | 0.500000 | 0.003051 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.990837 | 0.159453 | 0.136000 | 0.134754 | 0.425207 | 0.500000 | 0.002389 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.878029 | 0.113909 | 0.097000 | 0.085169 | 0.303757 | 0.500000 | 0.003345 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.532324 | 0.296796 | 0.252000 | 0.134146 | 0.791456 | 0.500000 | 0.001284 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.655398 | 0.152612 | 0.130000 | 0.085202 | 0.406966 | 0.500000 | 0.002497 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.790358 | 0.199899 | 0.170000 | 0.134361 | 0.533064 | 0.500000 | 0.001906 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.686096 | 0.145774 | 0.124000 | 0.085076 | 0.388732 | 0.500000 | 0.002614 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.595587 | 0.265271 | 0.225000 | 0.134007 | 0.707388 | 0.500000 | 0.001436 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.786208 | 0.339255 | 0.500000 | 0.002995 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.903741 | 0.174820 | 0.149000 | 0.134657 | 0.466186 | 0.500000 | 0.002179 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.814126 | 0.122850 | 0.104000 | 0.084669 | 0.327599 | 0.500000 | 0.003101 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 20782.20 |
CORE_MID VAV BOX REHEAT COIL | 24633.77 |
CORE_TOP VAV BOX REHEAT COIL | 42255.39 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 20639.01 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13405.44 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 20624.55 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13511.55 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 15489.51 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10131.96 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 15489.49 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10224.71 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 16266.28 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 10614.21 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 16249.33 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 10709.98 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.76 | 1.08 | 5.53 | 2.00 | 4.88 | 4.88 | 0.300000 | 0.409912 | 4.88 |
PACU_VAV_MID | 2.59 | 1.08 | 5.19 | 2.41 | 4.34 | 4.34 | 0.300000 | 0.555111 | 4.34 |
PACU_VAV_TOP | 2.76 | 1.08 | 5.52 | 3.39 | 4.99 | 4.99 | 0.300000 | 0.680039 | 4.99 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.88 |
PACU_VAV_MID_OA_CONTROLLER | 4.34 |
PACU_VAV_TOP_OA_CONTROLLER | 4.99 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.88 | 97576.14 | 0.776520 | 1.63 | 32522.13 | 0.776520 |
PACU_VAV_MID COOLING COIL | 4.34 | 89405.49 | 0.764546 | 1.45 | 29798.85 | 0.764546 |
PACU_VAV_TOP COOLING COIL | 4.99 | 99325.12 | 0.777607 | 1.66 | 33105.06 | 0.777607 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 29230.47 |
PACU_VAV_MID HEATING COIL | 30639.63 |
PACU_VAV_TOP HEATING COIL | 29512.47 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.88 |
PACU_VAV_MID FAN | 4.34 |
PACU_VAV_TOP FAN | 4.99 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 31.498 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.8022 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7887 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.032 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2365 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2366 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.013 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.034 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7350 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.151 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.150 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.29755900E-12 | 0.81313074E-15 | -0.93602003E-13 | 0.14510957E-15 |
43 | 6 | 0.28367368E-07 | 0.22496401E-09 | 0.65009128E-08 | -0.13359594E-12 |
44 | 5 | -0.18856357E-03 | 0.19286971E-05 | -0.97009749E-04 | 0.64274374E-08 |
45 | 4 | 0.29034011 | 0.94012602E-03 | 0.99033658E-01 | -0.33316087E-04 |
46 | 3 | -7.2305496 | 0.29163423E-01 | -2.3282961 | 0.28833673E-01 |
47 | 2 | 40.753148 | 0.10379063 | 15.221555 | -0.33202618 |
48 | 1 | -80.455373 | 0.46876469E-01 | -29.102648 | 1.0766925 |
49 | 0 | 46.824339 | 0.94379271E-03 | 16.292168 | |
50 | 7 | -0.29905644E-12 | 0.21441847E-14 | -0.94350753E-13 | 0.15229914E-15 |
51 | 6 | 0.28527035E-07 | 0.22156944E-09 | 0.65361533E-08 | -0.13441220E-12 |
52 | 5 | -0.18937502E-03 | 0.18976302E-05 | -0.97416439E-04 | 0.64617957E-08 |
53 | 4 | 0.29129073 | 0.92413897E-03 | 0.99375489E-01 | -0.33450099E-04 |
54 | 3 | -7.2493786 | 0.28644335E-01 | -2.3338831 | 0.28925940E-01 |
55 | 2 | 40.815249 | 0.10187053 | 15.244478 | -0.33271782 |
56 | 1 | -80.502964 | 0.45980673E-01 | -29.123201 | 1.0777067 |
57 | 0 | 46.824339 | 0.92519179E-03 | 16.291675 | |
58 | 7 | -0.27570686E-12 | 0.13707328E-14 | -0.80264236E-13 | 0.78378346E-16 |
59 | 6 | 0.25615968E-07 | 0.28022365E-09 | 0.58936169E-08 | -0.11887149E-12 |
60 | 5 | -0.17446821E-03 | 0.24481169E-05 | -0.89927666E-04 | 0.58344893E-08 |
61 | 4 | 0.27366067 | 0.12133616E-02 | 0.93044102E-01 | -0.30982017E-04 |
62 | 3 | -6.8997845 | 0.38197916E-01 | -2.2301787 | 0.27213971E-01 |
63 | 2 | 39.661773 | 0.13771433 | 14.818013 | -0.31987377 |
64 | 1 | -79.618511 | 0.62899977E-01 | -28.740542 | 1.0588596 |
65 | 0 | 46.824345 | 0.12804488E-02 | 16.301062 | |
66 | 7 | -0.18778705E-08 | -0.48456698E-15 | 0.68415356E-14 | -0.90766841E-16 |
67 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
68 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
69 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
70 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
71 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
72 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
73 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
74 | 7 | -0.17777358E-08 | -0.41207670E-15 | 0.60771148E-14 | -0.79247013E-16 |
75 | 6 | 0.66205355E-05 | 0.45347915E-08 | 0.31869553E-02 | -0.26734852E-04 |
76 | 5 | -0.47643654E-03 | 0.26865296E-05 | -0.22355891 | 0.19546881E-02 |
77 | 4 | 0.10961386E-01 | 0.12229770E-03 | 4.8267865 | -0.45238458E-01 |
78 | 3 | -0.96263561E-01 | 0.97262436E-03 | -38.005829 | 0.39848146 |
79 | 2 | 0.34182167 | 0.16181264E-02 | 116.45361 | -1.4175335 |
80 | 1 | -0.49337445 | 0.49308431E-03 | -143.88945 | 2.0487464 |
81 | 0 | 0.24054552 | 0.11921404E-04 | 60.838472 | |
82 | 7 | -0.18778705E-08 | -0.48456747E-15 | 0.68415356E-14 | -0.90766840E-16 |
83 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
84 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
85 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
86 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
87 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
88 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
89 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
90 | 7 | -0.17776120E-08 | -0.41258204E-15 | 0.60425363E-14 | -0.82023253E-16 |
91 | 6 | 0.66209765E-05 | 0.45351028E-08 | 0.31869540E-02 | -0.26734841E-04 |
92 | 5 | -0.47646911E-03 | 0.26867147E-05 | -0.22355884 | 0.19546874E-02 |
93 | 4 | 0.10962140E-01 | 0.12230614E-03 | 4.8267853 | -0.45238446E-01 |
94 | 3 | -0.96270204E-01 | 0.97269154E-03 | -38.005822 | 0.39848139 |
95 | 2 | 0.34184528 | 0.16182383E-02 | 116.45360 | -1.4175333 |
96 | 1 | -0.49340854 | 0.49311848E-03 | -143.88944 | 2.0487463 |
97 | 0 | 0.24056214 | 0.11922214E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.378 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.378 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2215E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2280E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3534E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3589E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2168E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2616E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3510E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3752E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1695 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.9604E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1930 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1017 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1169 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9702E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8073E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8035E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2217E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2294E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3536E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3604E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2188E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2713E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3507E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3749E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.8402E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5311E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.5065E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2535E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.4943E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7697E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6444E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6601E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9839E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.0101E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.6980E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.7170E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2495E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.2562E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0780E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0864E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6493E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7071E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8871E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9338E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3774E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4123E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3507E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3749E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.4452E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5454E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4292E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9423E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1553E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3320E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8073E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8035E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6489E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7075E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8863E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9322E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3756E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4054E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3510E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3752E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5523E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9055E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8905E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4652E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.4595E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2827E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6444E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6601E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.1638E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.2366E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6637E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7435E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6191E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.6491E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0782E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0865E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1702 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1085 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1909 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1226 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1254 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.3015E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.4807E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.5582E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.5817E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.3824E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.2709E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.1176E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.3162E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.6635E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.5395E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5971E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.0636E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.3159E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.9790E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6051E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.7051E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9384E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.4807E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.5582E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.3353E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.7852E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.7076E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3654E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.3123E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.1973E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.5395E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.5971E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1702 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1085 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1909 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1226 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1254 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.3007E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.4802E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.5579E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.5816E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.3821E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.2708E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.1172E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.3158E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.6631E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.5390E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5968E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.0637E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.3158E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.9791E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6050E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.7048E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9382E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.4802E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.5579E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3353E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.7849E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.7076E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3652E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3119E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.1970E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.5390E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.5968E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 38726.95715 | 38726.95715 | 2.86220 | 2.86220 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 8969.03549 | 8969.03549 | 0.39503 | 0.42469 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 28309.21633 | 28309.21633 | 2.08967 | 2.08967 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 17402.46684 | 17402.46684 | 0.75656 | 0.75656 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 29135.10566 | 29135.10566 | 2.17137 | 2.17137 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 30.20700 | 1.33668E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 29740.10334 | 29740.10334 | 1.29776 | 1.29776 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9135.70623 | 9135.70623 | 0.68092 | 0.68092 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 14488.36189 | 14488.36189 | 0.63387 | 0.63387 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10746.51325 | 10746.51325 | 0.80097 | 0.80097 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.97550 | 1.33593E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 9410.02780 | 9410.02780 | 0.41171 | 0.41171 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13293.89259 | 13293.89259 | 0.99084 | 0.99084 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 14478.23525 | 14478.23525 | 0.63343 | 0.63343 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11780.40844 | 11780.40844 | 0.87803 | 0.87803 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 9484.35879 | 9484.35879 | 0.41497 | 0.41497 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7142.33084 | 7142.33084 | 0.53232 | 0.53232 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 10879.77141 | 10879.77141 | 0.47572 | 0.47572 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8793.72707 | 8793.72707 | 0.65540 | 0.65540 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 26.23900 | 1.33598E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 7116.03705 | 7116.03705 | 0.31118 | 0.31118 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10604.50208 | 10604.50208 | 0.79036 | 0.79036 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 30.22250 | 1.33668E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 10879.75508 | 10879.75508 | 0.47572 | 0.47572 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9205.62551 | 9205.62551 | 0.68610 | 0.68610 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 28.22300 | 1.33633E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 7180.99647 | 7180.99647 | 0.31403 | 0.31403 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7990.94542 | 7990.94542 | 0.59559 | 0.59559 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.30000 | 1.33670E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 11424.80525 | 11424.80525 | 0.49958 | 0.49958 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10548.59045 | 10548.59045 | 0.78621 | 0.78621 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.71200 | 1.33588E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 7454.45579 | 7454.45579 | 0.32599 | 0.32599 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 12125.50182 | 12125.50182 | 0.90374 | 0.90374 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.06750 | 1.33665E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 11412.93262 | 11412.93262 | 0.49906 | 0.49906 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10923.17464 | 10923.17464 | 0.81413 | 0.81413 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 7521.52967 | 7521.52967 | 0.32893 | 0.32893 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 71596.02 | 4.88234 | 4.88234 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 32544.19 | 2.00133 | 2.00133 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 64384.10 | 4.34167 | 4.34167 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 32496.73 | 2.41011 | 2.41011 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 72826.69 | 4.98758 | 4.98758 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 32807.31 | 3.39175 | 3.39175 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 01:30:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.86220 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26185 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22300 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63827 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69826 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.45506E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20782.20026 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.08967 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35865 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30500 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63735 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.95639 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.06232E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24633.77474 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.17137 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34515 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29300 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63621 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.92041 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10386E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 42255.38742 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68092 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23203 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19700 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13414 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61874 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.64205E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20639.00555 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80097 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12488 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10600 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.49030E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33300 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.05104E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13405.43502 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99084 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15945 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13600 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13475 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42521 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.38942E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20624.55014 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.87803 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11391 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.70000E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51688E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30376 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.34478E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13511.55137 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.53232 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29680 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25200 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13415 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79146 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.28371E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15489.51105 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65540 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15261 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52018E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40697 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.49652E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10131.96153 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79036 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19990 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13436 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53306 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.90596E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15489.48774 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68610 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14577 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12400 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50759E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38873 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.61363E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10224.71274 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59559 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26527 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22500 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13401 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70739 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.43627E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16266.28085 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78621 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33925 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.99480E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10614.21403 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90374 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17482 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14900 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13466 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46619 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.17939E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16249.33151 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81413 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12285 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10400 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.46691E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32760 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.10135E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10709.97723 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.76319 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07705 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.52638 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.00133 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.88234 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.88234 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.40991 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.59466 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07559 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.18933 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.41011 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.34167 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.34167 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.55511 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.76106 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07518 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.52213 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.39175 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.98758 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.98758 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.68004 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.88234 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.34167 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.98758 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.88234 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.88234 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 97576.14448 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.77652 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.62728 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32522.12895 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.77652 |
152 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 29230.47359 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.88234 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.34167 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.34167 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 89405.48999 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.76455 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.44708 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 29798.84981 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.76455 |
161 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 30639.62715 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.34167 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.98758 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.98758 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 99325.12020 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.77761 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.66236 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 33105.06256 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.77761 |
170 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 29512.46721 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.98758 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 96679.86 | 329885.39 | 11.26 | 2.88 | 3.22 | 3.39 | 3.57 | 9.84 | 10.99 | 11.57 | 12.17 | 5.5052 | 4.4003 | 2.9642 | 1.1874 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 88686.21 | 302609.91 | 11.32 | 2.90 | 3.24 | 3.41 | 3.58 | 9.89 | 11.06 | 11.65 | 12.21 | 4.8955 | 3.9071 | 2.6309 | 1.0668 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 98399.06 | 335751.54 | 11.25 | 2.88 | 3.22 | 3.39 | 3.57 | 9.84 | 10.99 | 11.56 | 12.17 | 5.6238 | 4.4935 | 3.0261 | 1.2130 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.237 | 0.224 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.237 | 0.224 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.3091014654E-002 | 2.4881744032E-002 | Pass | Pass | 0.5035144107 | 0.5054455123 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1157832898 | 7.5420058360E-002 | Pass | Pass | 0.4931990502 | 0.4783576236 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.5154116254E-002 | 3.4708406048E-002 | Pass | Pass | 0.4945144612 | 0.4659799458 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.7799916475E-002 | 3.5536565276E-002 | Pass | Pass | 0.4892185953 | 0.4635219641 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 7.5109739420E-003 | 7.2935189541E-003 | Pass | Pass | 0.5011675517 | 0.4950735994 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 8.4469276669E-002 | 8.6346694986E-002 | Pass | Pass | 36.7741305069 | 106.4698662607 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3891799893 | 0.3813496948 | Pass | Pass | 41.0310917151 | 169.2449985097 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4153977714 | 0.4015444312 | Pass | Pass | 50.9000757675 | 133.1114343946 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3807553738 | 0.3779732694 | Pass | Pass | 61.8571914564 | 231.6903905089 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4172553097 | 0.4054795120 | Pass | Pass | 54.5030321803 | 152.4919767510 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2774029199 | 0.2568144484 | Pass | Pass | 27.5707350169 | 81.1651488634 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2881715476 | 0.2683133428 | Pass | Pass | 34.6498600151 | 149.6812608601 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2484008812 | 0.2405733821 | Pass | Pass | 41.0538468478 | 245.3011765667 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2889559829 | 0.2704329442 | Pass | Pass | 34.6831679004 | 141.3252475529 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2920204711 | 0.2752526256 | Pass | Pass | 41.5126483772 | 127.7892996704 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3008871249 | 0.2857640212 | Pass | Pass | 36.5831491040 | 112.4360732239 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2671936305 | 0.2643269374 | Pass | Pass | 68.2409891445 | 275.7138771319 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3023249207 | 0.2888030624 | Pass | Pass | 46.1498148796 | 167.6160512034 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3514.57 | 186.15 | 0.00 | 1721.28 | 739.55 | 6161.56 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.378 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.378 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.378 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.378 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.378 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.378 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.378 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.378 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.378 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.378 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.062 | 0.379 | 0.417 | |||||||||||||||||
North Total or Average | 195.79 | 2.062 | 0.379 | 0.417 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.062 | 0.379 | 0.417 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.97 | 0.0000 | Y | 6.73 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.82 | 0.0000 | Y | 4.24 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.66 | 0.0000 | Y | 6.65 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.79 | 0.0000 | Y | 4.23 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.91 | 0.0000 | Y | 6.72 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.78 | 0.0000 | Y | 4.23 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.62 | 0.0000 | Y | 6.64 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.74 | 0.0000 | Y | 4.23 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.97 | 0.0000 | Y | 6.73 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.82 | 0.0000 | Y | 4.24 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.66 | 0.0000 | Y | 6.65 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.79 | 0.0000 | Y | 4.23 |
Interior Lighting Total | 6.6636 | 4982.19 | 33199.39 | 232.34 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 42.04 | 42.04 | 4.45 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.67 | 62.85 | 4.81 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.67 | 47.45 | 41.99 | |
Exterior Lighting Total | 5686.19 | 51.25 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 97576.14 | 75769.86 | 21806.29 | 0.78 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 89405.49 | 68354.60 | 21050.89 | 0.76 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 99325.12 | 77235.87 | 22089.25 | 0.78 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 96679.9 | 2.88 | 9.84 | N/A | N/A | 11.26 | |
PACU_VAV_MID COOLING COIL | 88686.2 | 2.90 | 9.89 | N/A | N/A | 11.32 | |
PACU_VAV_TOP COOLING COIL | 98399.1 | 2.88 | 9.84 | N/A | N/A | 11.25 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 20782.20 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 24633.77 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 42255.39 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 20639.01 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13405.44 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 20624.55 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13511.55 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15489.51 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10131.96 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15489.49 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10224.71 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16266.28 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10614.21 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16249.33 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10709.98 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 29230.47 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 30639.63 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 29512.47 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.88 | 11221.87 | 2298.46 | 1.00 | 1.14 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.34 | 10043.97 | 2313.39 | 1.00 | 1.14 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.99 | 10917.87 | 2189.01 | 1.00 | 1.13 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 96679.86 | 2.88 | 9.84 | 11.26 | 5.5052 | 3.22 | 10.99 | 4.4003 | 3.39 | 11.57 | 2.9642 | 3.57 | 12.17 | 1.1874 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 88686.21 | 2.90 | 9.89 | 11.32 | 4.8955 | 3.24 | 11.06 | 3.9071 | 3.41 | 11.65 | 2.6309 | 3.58 | 12.21 | 1.0668 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 98399.06 | 2.88 | 9.84 | 11.25 | 5.6238 | 3.22 | 10.99 | 4.4935 | 3.39 | 11.56 | 3.0261 | 3.57 | 12.17 | 1.2130 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 38726.96 | 38726.96 | 39.38 | 2.862 | 2.862 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00881 | 23.42 | 0.01335 | 0.425 | 0.00 |
CORE_MID | 28309.22 | 28309.22 | 28.78 | 2.090 | 2.090 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 23.42 | 0.01335 | 0.425 | 0.00 |
CORE_TOP | 29135.11 | 29135.11 | 29.62 | 2.171 | 2.171 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00891 | 30.21 | 0.01337 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9135.71 | 9135.71 | 44.06 | 0.681 | 0.681 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00904 | 30.30 | 0.01337 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10746.51 | 10746.51 | 81.87 | 0.801 | 0.801 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00881 | 25.98 | 0.01336 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13293.89 | 13293.89 | 64.12 | 0.991 | 0.991 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00888 | 30.14 | 0.01337 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11780.41 | 11780.41 | 89.75 | 0.878 | 0.878 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00878 | 28.84 | 0.01336 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7142.33 | 7142.33 | 34.45 | 0.532 | 0.532 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00903 | 30.30 | 0.01337 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8793.73 | 8793.73 | 66.99 | 0.655 | 0.655 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00878 | 26.24 | 0.01336 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10604.50 | 10604.50 | 51.15 | 0.790 | 0.790 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00886 | 30.22 | 0.01337 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9205.63 | 9205.63 | 70.14 | 0.686 | 0.686 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 24.00 | 24.00 | 0.00877 | 28.22 | 0.01336 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7990.95 | 7990.95 | 38.54 | 0.596 | 0.596 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00906 | 30.30 | 0.01337 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10548.59 | 10548.59 | 80.36 | 0.786 | 0.786 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00879 | 25.71 | 0.01336 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12125.50 | 12125.50 | 58.48 | 0.904 | 0.904 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00888 | 30.07 | 0.01337 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10923.17 | 10923.17 | 83.22 | 0.814 | 0.814 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00877 | 28.84 | 0.01336 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 8969.04 | 8969.04 | 9.12 | 0.395 | 0.425 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
CORE_MID | 17402.47 | 17402.47 | 17.69 | 0.757 | 0.757 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
CORE_TOP | 29740.10 | 29740.10 | 30.24 | 1.298 | 1.298 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 14488.36 | 14488.36 | 69.88 | 0.634 | 0.634 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9410.03 | 9410.03 | 71.69 | 0.412 | 0.412 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00752 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 14478.24 | 14478.24 | 69.83 | 0.633 | 0.633 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 9484.36 | 9484.36 | 72.26 | 0.415 | 0.415 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00752 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 10879.77 | 10879.77 | 52.47 | 0.476 | 0.476 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7116.04 | 7116.04 | 54.21 | 0.311 | 0.311 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10879.76 | 10879.76 | 52.47 | 0.476 | 0.476 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 7181.00 | 7181.00 | 54.71 | 0.314 | 0.314 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 11424.81 | 11424.81 | 55.10 | 0.500 | 0.500 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 7454.46 | 7454.46 | 56.79 | 0.326 | 0.326 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00749 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11412.93 | 11412.93 | 55.05 | 0.499 | 0.499 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 7521.53 | 7521.53 | 57.31 | 0.329 | 0.329 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00749 | -16.30 | 0.00092 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.88 | 4.88 | 2.00 | 2.00 | 4.8823 | 2.0013 | 4.8823 | 0.4099 | 0.3000 |
PACU_VAV_MID | 4.34 | 4.34 | 2.41 | 2.41 | 4.3417 | 2.4101 | 4.3417 | 0.5551 | 0.3000 |
PACU_VAV_TOP | 4.99 | 4.99 | 3.39 | 3.39 | 4.9876 | 3.3917 | 4.9876 | 0.6800 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 20782.200 | 20782.200 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 20782.20 | 13828.02 | 0.424691 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 8969.04 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 24633.775 | 24633.775 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24633.77 | 24633.77 | 0.756561 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 17402.47 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 42255.387 | 42255.387 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 42255.39 | 42255.39 | 1.297763 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 29740.10 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 20639.006 | 20639.006 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20639.01 | 20639.01 | 0.633873 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00752961 | 47.4972 | 14488.36 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 13405.435 | 13405.435 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13405.44 | 13405.44 | 0.411713 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00751824 | 47.4267 | 9410.03 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 20624.550 | 20624.550 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20624.55 | 20624.55 | 0.633429 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00752930 | 47.4953 | 14478.24 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 13511.551 | 13511.551 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13511.55 | 13511.55 | 0.414972 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00752184 | 47.4491 | 9484.36 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 15489.511 | 15489.511 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15489.51 | 15489.51 | 0.475720 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00764542 | 48.2159 | 10879.77 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 10131.962 | 10131.962 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10131.96 | 10131.96 | 0.311177 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00764216 | 48.1957 | 7116.04 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 15489.488 | 15489.488 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15489.49 | 15489.49 | 0.475719 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00764542 | 48.2159 | 10879.76 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 10224.713 | 10224.713 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10224.71 | 10224.71 | 0.314025 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00764605 | 48.2199 | 7181.00 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 16266.281 | 16266.281 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16266.28 | 16266.28 | 0.499576 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00749697 | 47.2930 | 11424.81 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 10614.214 | 10614.214 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10614.21 | 10614.21 | 0.325988 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00748867 | 47.2414 | 7454.46 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 16249.332 | 16249.332 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16249.33 | 16249.33 | 0.499055 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00749643 | 47.2896 | 11412.93 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 10709.977 | 10709.977 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10709.98 | 10709.98 | 0.328929 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00749337 | 47.2707 | 7521.53 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 97576.144 | 75769.857 | 4.882339 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 99301.44 | 81161.82 | 4.882339 | 25.23 | 17.59 | 0.00975506 | 10.89 | 10.89 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 19.5828 | 24.00 | 0.00887539 | 46.5535 | 65501.82 | 0.00 | 100614.10 | 75939.22 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 29230.474 | 29230.474 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29230.47 | 29230.47 | 1.464702 | -4.12 | -4.12 | 0.00315055 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 65.2761 | 18.29 | 0.00731926 | 54.6545 | 15615.72 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 89405.490 | 68354.597 | 4.341673 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 91342.18 | 72916.33 | 4.341673 | 25.39 | 17.79 | 0.00993458 | 10.87 | 10.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 22.0215 | 24.00 | 0.00896361 | 47.0103 | 58176.37 | 0.00 | 92189.06 | 68542.57 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 30639.627 | 30639.627 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30639.63 | 30639.63 | 1.302502 | -7.14 | -7.14 | 0.00258473 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 73.4049 | 17.60 | 0.00656227 | 51.2373 | 16294.65 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 99325.120 | 77235.871 | 4.987580 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 101103.48 | 82327.70 | 4.987580 | 25.21 | 17.61 | 0.00977857 | 10.98 | 10.98 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 19.1696 | 24.00 | 0.00892490 | 46.8103 | 66751.49 | 0.00 | 102417.53 | 77386.72 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 29512.467 | 29512.467 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 01:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29512.47 | 29512.47 | 1.496274 | -3.92 | -3.92 | 0.00315899 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 63.8987 | 16.01 | 0.00730003 | 62.9602 | 15585.89 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 20782.200 | 20782.200 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 20782.20 | 13828.02 | 1.0000 | 0.49855562 | 0.424691 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20782.20 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.03 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 8969.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 24633.775 | 24633.775 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24633.77 | 24633.77 | 1.0000 | 0.88814669 | 0.756561 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24633.77 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 17402.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 42255.387 | 42255.387 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 42255.39 | 42255.39 | 1.0000 | 1.52347673 | 1.297763 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 42255.39 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 29740.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 20639.006 | 20639.006 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20639.01 | 20639.01 | 1.0000 | 0.74411919 | 0.633873 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20639.01 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00752961 | 21.00 | 0.00752961 | 47.4972 | 14488.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 13405.435 | 13405.435 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13405.44 | 13405.44 | 1.0000 | 0.48331987 | 0.411713 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13405.44 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00751824 | 21.00 | 0.00751824 | 47.4267 | 9410.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 20624.550 | 20624.550 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20624.55 | 20624.55 | 1.0000 | 0.74359801 | 0.633429 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20624.55 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00752930 | 21.00 | 0.00752930 | 47.4953 | 14478.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 13511.551 | 13511.551 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13511.55 | 13511.55 | 1.0000 | 0.48714579 | 0.414972 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13511.55 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00752184 | 21.00 | 0.00752184 | 47.4491 | 9484.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 15489.511 | 15489.511 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15489.51 | 15489.51 | 1.0000 | 0.55845919 | 0.475720 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15489.51 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00764542 | 21.00 | 0.00764542 | 48.2159 | 10879.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10131.962 | 10131.962 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10131.96 | 10131.96 | 1.0000 | 0.36529798 | 0.311177 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10131.96 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00764216 | 21.00 | 0.00764216 | 48.1957 | 7116.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 15489.488 | 15489.488 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15489.49 | 15489.49 | 1.0000 | 0.55845835 | 0.475719 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15489.49 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00764542 | 21.00 | 0.00764542 | 48.2159 | 10879.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10224.713 | 10224.713 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10224.71 | 10224.71 | 1.0000 | 0.36864203 | 0.314025 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10224.71 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00764605 | 21.00 | 0.00764605 | 48.2199 | 7181.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 16266.281 | 16266.281 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16266.28 | 16266.28 | 1.0000 | 0.58646487 | 0.499576 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16266.28 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00749697 | 21.00 | 0.00749697 | 47.2930 | 11424.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10614.214 | 10614.214 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10614.21 | 10614.21 | 1.0000 | 0.38268512 | 0.325988 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10614.21 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00748867 | 21.00 | 0.00748867 | 47.2414 | 7454.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 16249.332 | 16249.332 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16249.33 | 16249.33 | 1.0000 | 0.58585378 | 0.499055 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16249.33 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00749643 | 21.00 | 0.00749643 | 47.2896 | 11412.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10709.977 | 10709.977 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10709.98 | 10709.98 | 1.0000 | 0.38613777 | 0.328929 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10709.98 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00749337 | 21.00 | 0.00749337 | 47.2707 | 7521.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 97576.144 | 75769.857 | 4.882339 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.9742 | 1004.8586 | 1.1739 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.882339 | 5.73150166 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 99301.44 | 81161.82 | 1.0177 | 5.73150166 | 4.882339 | 25.23 | 17.59 | 0.00975506 | 50209.2 | 10.89 | 10.89 | 0.00850000 | 32368.7 | -999.0 | -999.00 | -999.00 | -999.00 | 11221.869 | 88079.57 | 30.30 | 0.01336696 | 21.83 | 0.95610000 | 19.5828 | 24.00 | 0.00887539 | 24.00 | 0.00887539 | 46.5535 | 65501.82 | 0.00 | 100614.10 | 75939.22 | 5.50515068 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.17 | 13.16 | 0.00942731 | 37046.0 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29230.474 | 29230.474 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.882339 | 5.73150166 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 29230.47 | 29230.47 | 1.0000 | 1.71945050 | 1.464702 | -4.12 | -4.12 | 0.00315055 | 3717.6 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29230.47 | -16.30 | 0.00092409 | -16.30 | 0.95610000 | 65.2761 | 18.78 | 0.00733597 | 18.29 | 0.00731926 | 54.6545 | 15615.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 89405.490 | 68354.597 | 4.341673 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.3079 | 1004.8586 | 1.1739 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.341673 | 5.09679987 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 91342.18 | 72916.33 | 1.0217 | 5.09679987 | 4.341673 | 25.39 | 17.79 | 0.00993458 | 50825.4 | 10.87 | 10.87 | 0.00850000 | 32356.7 | -999.0 | -999.00 | -999.00 | -999.00 | 10043.968 | 81298.21 | 30.30 | 0.01336696 | 21.83 | 0.95610000 | 22.0215 | 24.00 | 0.00896361 | 24.00 | 0.00896361 | 47.0103 | 58176.37 | 0.00 | 92189.06 | 68542.57 | 4.89551481 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.97 | 12.95 | 0.00929083 | 36491.1 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30639.627 | 30639.627 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.341673 | 5.09679987 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30639.63 | 30639.63 | 1.0000 | 1.52903996 | 1.302502 | -7.14 | -7.14 | 0.00258473 | -746.2 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30639.63 | -16.30 | 0.00092409 | -16.30 | 0.95610000 | 73.4049 | 18.14 | 0.00716822 | 17.60 | 0.00656227 | 51.2373 | 16294.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 99325.120 | 77235.871 | 4.987580 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.0179 | 1004.8586 | 1.1739 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.987580 | 5.85504686 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 101103.48 | 82327.70 | 1.0179 | 5.85504686 | 4.987580 | 25.21 | 17.61 | 0.00977857 | 50245.2 | 10.98 | 10.98 | 0.00850000 | 32461.8 | -999.0 | -999.00 | -999.00 | -999.00 | 10917.868 | 90185.61 | 30.30 | 0.01336696 | 21.83 | 0.95610000 | 19.1696 | 24.00 | 0.00892490 | 24.00 | 0.00892490 | 46.8103 | 66751.49 | 0.00 | 102417.53 | 77386.72 | 5.62381677 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.21 | 13.19 | 0.00943958 | 37111.0 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29512.467 | 29512.467 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.987580 | 5.85504686 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 01:30:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 29512.47 | 29512.47 | 1.0000 | 1.75651406 | 1.496274 | -3.92 | -3.92 | 0.00315899 | 3938.0 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29512.47 | -16.30 | 0.00092409 | -16.30 | 0.95610000 | 63.8987 | 17.99 | 0.00711473 | 16.01 | 0.00730003 | 62.9602 | 15585.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.88 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.34 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.99 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2039.67 | 2845.33 | 110.33 |
CORE_MID | 2489.83 | 3527.50 | 1009.17 |
CORE_TOP | 3036.67 | 3817.67 | 1687.50 |
PERIMETER_TOP_ZN_3 | 3666.50 | 4136.00 | 2429.00 |
PERIMETER_TOP_ZN_2 | 3858.17 | 3826.50 | 2292.33 |
PERIMETER_TOP_ZN_1 | 3552.83 | 3804.17 | 2034.67 |
PERIMETER_TOP_ZN_4 | 3821.83 | 3976.83 | 2334.50 |
PERIMETER_BOT_ZN_3 | 3312.67 | 4171.17 | 2131.00 |
PERIMETER_BOT_ZN_2 | 3560.17 | 3713.67 | 1919.67 |
PERIMETER_BOT_ZN_1 | 3329.00 | 4042.67 | 1941.83 |
PERIMETER_BOT_ZN_4 | 3547.00 | 3806.33 | 1965.00 |
PERIMETER_MID_ZN_3 | 3411.17 | 3935.33 | 2072.00 |
PERIMETER_MID_ZN_2 | 3083.33 | 3180.33 | 1744.50 |
PERIMETER_MID_ZN_1 | 3292.17 | 3534.67 | 1639.50 |
PERIMETER_MID_ZN_4 | 3596.00 | 3747.83 | 1984.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4835.67 | 4627.00 | 2733.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 1.17 | 0.00 | 1.17 | 0.00 |
CORE_MID | 3.00 | 0.00 | 2.67 | 0.00 |
CORE_TOP | 8.67 | 0.00 | 6.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 155.50 | 3.33 | 70.50 | 2.83 |
PERIMETER_TOP_ZN_2 | 102.50 | 24.00 | 18.83 | 23.33 |
PERIMETER_TOP_ZN_1 | 81.67 | 23.50 | 14.67 | 22.50 |
PERIMETER_TOP_ZN_4 | 100.17 | 29.50 | 21.17 | 18.50 |
PERIMETER_BOT_ZN_3 | 42.83 | 0.00 | 29.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 12.50 | 10.67 | 0.33 | 10.67 |
PERIMETER_BOT_ZN_1 | 347.67 | 9.17 | 340.00 | 9.17 |
PERIMETER_BOT_ZN_4 | 13.00 | 19.17 | 0.50 | 11.33 |
PERIMETER_MID_ZN_3 | 54.17 | 0.50 | 22.67 | 0.50 |
PERIMETER_MID_ZN_2 | 30.67 | 21.50 | 1.00 | 21.33 |
PERIMETER_MID_ZN_1 | 24.17 | 20.67 | 1.00 | 20.50 |
PERIMETER_MID_ZN_4 | 31.50 | 26.17 | 1.33 | 15.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 494.67 | 97.50 | 382.17 | 78.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 0.926 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.671 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.663 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.769 | 0.114 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 1.098 | 0.120 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 1.048 | 0.114 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 1.055 | 0.120 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.642 | 0.061 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.938 | 0.064 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 0.861 | 0.877 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.885 | 0.064 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.747 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.981 | 0.106 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 1.030 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 1.017 | 0.100 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.55 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.93 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 14651485.41 | 0.00 | 14651485.41 | 0.00 | 14651485.41 | 13393058.27 | 4961.83 | 640.04 | 3158.13 | 128.55 |
CORE_MID | 10696832.21 | 0.00 | 10696832.21 | 0.00 | 10696832.21 | 13393058.27 | 4964.07 | 1161.35 | 2634.58 | 186.87 |
CORE_TOP | 10566896.27 | 0.00 | 10566896.27 | 0.00 | 10566896.27 | 13393058.27 | 5147.62 | 1166.56 | 2445.82 | 96.45 |
PERIMETER_TOP_ZN_3 | 2580964.62 | 0.00 | 2580964.62 | 750436.27 | 3331400.89 | 2823374.22 | 4397.20 | 1100.52 | 3262.28 | 96.45 |
PERIMETER_TOP_ZN_2 | 2323531.71 | 0.00 | 2323531.71 | 500287.84 | 2823819.55 | 1787429.43 | 4418.28 | 1135.79 | 3205.93 | 96.45 |
PERIMETER_TOP_ZN_1 | 3504749.32 | 0.00 | 3504749.32 | 750436.27 | 4255185.59 | 2823374.22 | 4345.39 | 882.11 | 3532.50 | 96.45 |
PERIMETER_TOP_ZN_4 | 2250526.60 | 0.00 | 2250526.60 | 500287.84 | 2750814.44 | 1787312.18 | 4322.74 | 964.08 | 3473.18 | 96.45 |
PERIMETER_BOT_ZN_3 | 2155610.47 | 0.00 | 2155610.47 | 399002.08 | 2554612.55 | 2823374.22 | 5602.44 | 699.77 | 2457.79 | 128.55 |
PERIMETER_BOT_ZN_2 | 1984044.28 | 0.00 | 1984044.28 | 265999.79 | 2250044.07 | 1787429.43 | 5240.95 | 651.59 | 2867.46 | 128.55 |
PERIMETER_BOT_ZN_1 | 2888475.03 | 0.00 | 2888475.03 | 3134132.70 | 6022607.72 | 2823374.22 | 4839.84 | 631.19 | 3288.97 | 128.55 |
PERIMETER_BOT_ZN_4 | 1880350.48 | 0.00 | 1880350.48 | 265999.79 | 2146350.26 | 1787312.18 | 5293.66 | 681.16 | 2785.18 | 128.55 |
PERIMETER_MID_ZN_3 | 2508785.63 | 0.00 | 2508785.63 | 624679.86 | 3133465.49 | 2823374.22 | 4546.75 | 1248.56 | 2964.69 | 186.87 |
PERIMETER_MID_ZN_2 | 2110571.00 | 0.00 | 2110571.00 | 416450.74 | 2527021.73 | 1601953.02 | 4331.13 | 980.55 | 3448.32 | 1095.84 |
PERIMETER_MID_ZN_1 | 3445103.35 | 0.00 | 3445103.35 | 624679.86 | 4069783.21 | 2823374.22 | 4332.95 | 984.90 | 3442.15 | 186.87 |
PERIMETER_MID_ZN_4 | 2165039.94 | 0.00 | 2165039.94 | 416450.74 | 2581490.67 | 1787312.18 | 4532.41 | 1297.41 | 2930.17 | 186.84 |
Total Facility | 65712966.32 | 0.00 | 65712966.32 | 8648843.76 | 74361810.08 | 67658168.57 | 6267.89 | 1785.56 | 4452.54 | 1174.12 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6797 | 0.0000 | 0.6797 | 0.0000 | 0.6797 | 0.4247 | 2183.05 | 640.04 | 3119.91 |
CORE_MID | 0.4936 | 0.0000 | 0.4936 | 0.0000 | 0.4936 | 0.4247 | 2196.77 | 1161.19 | 2585.04 |
CORE_TOP | 0.4874 | 0.0000 | 0.4874 | 0.0000 | 0.4874 | 0.4247 | 2390.35 | 1166.39 | 2386.26 |
PERIMETER_TOP_ZN_3 | 0.1192 | 0.0000 | 0.1192 | 0.0178 | 0.1370 | 0.0895 | 1639.92 | 1100.35 | 3202.72 |
PERIMETER_TOP_ZN_2 | 0.1077 | 0.0000 | 0.1077 | 0.0119 | 0.1196 | 0.0567 | 1661.00 | 1135.63 | 3146.37 |
PERIMETER_TOP_ZN_1 | 0.1624 | 0.0000 | 0.1624 | 0.0178 | 0.1802 | 0.0895 | 1588.11 | 881.95 | 3472.94 |
PERIMETER_TOP_ZN_4 | 0.1034 | 0.0000 | 0.1034 | 0.0119 | 0.1153 | 0.0567 | 1565.46 | 963.91 | 3413.63 |
PERIMETER_BOT_ZN_3 | 0.0997 | 0.0000 | 0.0997 | 0.0095 | 0.1091 | 0.0895 | 2823.66 | 699.77 | 2419.57 |
PERIMETER_BOT_ZN_2 | 0.0920 | 0.0000 | 0.0920 | 0.0063 | 0.0983 | 0.0567 | 2462.19 | 651.57 | 2829.24 |
PERIMETER_BOT_ZN_1 | 0.1339 | 0.0000 | 0.1339 | 0.1373 | 0.2712 | 0.0895 | 2061.07 | 631.19 | 3250.75 |
PERIMETER_BOT_ZN_4 | 0.0868 | 0.0000 | 0.0868 | 0.0063 | 0.0932 | 0.0567 | 2514.97 | 681.09 | 2746.94 |
PERIMETER_MID_ZN_3 | 0.1159 | 0.0000 | 0.1159 | 0.0148 | 0.1307 | 0.0895 | 1779.46 | 1248.23 | 2915.31 |
PERIMETER_MID_ZN_2 | 0.0962 | 0.0000 | 0.0962 | 0.0105 | 0.1067 | 0.0567 | 1564.12 | 980.27 | 2489.60 |
PERIMETER_MID_ZN_1 | 0.1596 | 0.0000 | 0.1596 | 0.0148 | 0.1745 | 0.0895 | 1565.65 | 984.73 | 3392.61 |
PERIMETER_MID_ZN_4 | 0.0997 | 0.0000 | 0.0997 | 0.0099 | 0.1096 | 0.0567 | 1765.45 | 1297.00 | 2880.55 |
Total Facility | 3.0374 | 0.0000 | 3.0374 | 0.2687 | 3.3061 | 2.1513 | 3476.39 | 1785.04 | 4381.06 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 32467931.67 | 0.00 | 32467931.67 | 22614548.33 | 4126.00 | 2.10 | 4631.90 | 128.55 |
PACU_VAV_MID | 28838581.33 | 0.00 | 28838581.33 | 22429071.92 | 4085.42 | 1.86 | 4672.72 | 186.77 |
PACU_VAV_TOP | 29252350.14 | 0.00 | 29252350.14 | 22614548.33 | 4090.33 | 2.45 | 4667.22 | 96.05 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.5051 | 0.0000 | 1.5051 | 0.7171 | 1347.22 | 2.10 | 4593.68 |
PACU_VAV_MID | 1.3321 | 0.0000 | 1.3321 | 0.7084 | 1318.21 | 1.86 | 4622.93 |
PACU_VAV_TOP | 1.3508 | 0.0000 | 1.3508 | 0.7171 | 1333.05 | 2.45 | 4607.50 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 355.09 | 2437.65 | 0.00 | 0.00 | 0.00 | 2079.76 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 68.45 | 2512.12 | 0.00 | 0.00 | 0.00 | 2399.34 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 49.59 | 2426.71 | 0.00 | 0.00 | 0.00 | 2416.44 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.3205 | 2.7045 | 0.0000 | 0.0000 | 0.0000 | 1.0739 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.2761 | 2.3165 | 0.0000 | 0.0000 | 0.0000 | 1.0187 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.2180 | 2.3466 | 0.0000 | 0.0000 | 0.0000 | 1.0350 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 943 |
Defaulted Fields | 546 |
Fields with Defaults | 2233 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1463.03 | 12315.29 | 16-APR-17:30 | 237424.75 | 02-JAN-07:10 |
Electricity:Building | 937.78 | 12146.72 | 26-MAR-17:20 | 70508.97 | 02-NOV-07:10 |
Electricity:Zone:CORE_BOTTOM | 291.77 | 4006.86 | 01-JAN-00:10 | 23121.21 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 937.78 | 12146.72 | 26-MAR-17:20 | 70508.97 | 02-NOV-07:10 |
InteriorLights:Electricity | 232.35 | 905.38 | 26-MAR-17:20 | 25003.79 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 232.35 | 905.38 | 26-MAR-17:20 | 25003.79 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 232.35 | 905.38 | 26-MAR-17:20 | 25003.79 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 232.35 | 905.38 | 26-MAR-17:20 | 25003.79 | 02-JAN-16:50 |
Electricity:Zone:CORE_MID | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 31.07 | 413.68 | 12-MAR-17:10 | 2475.80 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.73 | 27.57 | 01-JAN-10:30 | 1040.56 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.73 | 27.57 | 01-JAN-10:30 | 1040.56 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.64 | 261.88 | 26-MAR-17:10 | 1567.33 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.24 | 17.46 | 01-JAN-09:10 | 658.76 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.24 | 17.46 | 01-JAN-09:10 | 658.76 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 30.99 | 413.67 | 12-MAR-17:10 | 2475.79 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.65 | 27.57 | 01-JAN-09:10 | 1040.56 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.65 | 27.57 | 01-JAN-09:10 | 1040.56 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.64 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.23 | 17.46 | 01-JAN-10:00 | 658.71 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.23 | 17.46 | 01-JAN-10:00 | 658.71 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 31.05 | 413.68 | 12-MAR-17:10 | 2475.80 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.72 | 27.57 | 01-JAN-10:20 | 1040.56 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.72 | 27.57 | 01-JAN-10:20 | 1040.56 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.64 | 261.88 | 26-MAR-17:10 | 1567.33 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.23 | 17.46 | 01-JAN-09:10 | 658.76 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.23 | 17.46 | 01-JAN-09:10 | 658.76 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 30.98 | 413.67 | 12-MAR-17:10 | 2475.79 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.64 | 27.57 | 01-JAN-09:10 | 1040.56 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.64 | 27.57 | 01-JAN-09:10 | 1040.56 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.63 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.23 | 17.46 | 01-JAN-10:00 | 658.71 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.23 | 17.46 | 01-JAN-10:00 | 658.71 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 31.07 | 413.68 | 12-MAR-17:10 | 2475.80 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.73 | 27.57 | 01-JAN-10:30 | 1040.56 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.73 | 27.57 | 01-JAN-10:30 | 1040.56 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.64 | 261.88 | 26-MAR-17:10 | 1567.33 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.24 | 17.46 | 01-JAN-09:10 | 658.76 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.24 | 17.46 | 01-JAN-09:10 | 658.76 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 30.99 | 413.67 | 12-MAR-17:10 | 2475.79 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.65 | 27.57 | 01-JAN-09:10 | 1040.56 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.65 | 27.57 | 01-JAN-09:10 | 1040.56 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.64 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.23 | 17.46 | 01-JAN-10:00 | 658.71 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.23 | 17.46 | 01-JAN-10:00 | 658.71 | 02-JAN-16:50 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 473.86 | 168.57 | 18-JUN-17:50 | 202389.04 | 02-JAN-06:20 |
ExteriorEquipment:Electricity | 11.69 | 168.34 | 01-JAN-00:10 | 839.68 | 02-NOV-07:20 |
Transformer:ExteriorEquipment:Electricity | 11.69 | 168.34 | 01-JAN-00:10 | 839.68 | 02-NOV-07:20 |
ElectricityPurchased:Facility | 1463.03 | 12315.29 | 02-JUL-17:50 | 237424.75 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 1463.03 | 12315.29 | 02-JUL-17:50 | 237424.75 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1463.03 | 12315.29 | 02-JUL-17:50 | 237424.75 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1463.03 | 12315.29 | 02-JUL-17:50 | 237424.75 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1463.03 | 12315.29 | 02-JUL-17:50 | 237424.75 | 02-JAN-07:10 |
ElectricityNet:Plant | 1463.03 | 12315.29 | 02-JUL-17:50 | 237424.75 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 1463.03 | 12315.29 | 02-JUL-17:50 | 237424.75 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1463.03 | 12315.29 | 02-JUL-17:50 | 237424.75 | 02-JAN-07:10 |
Heating:Electricity | 243.18 | 0.00 | 01-JAN-00:40 | 195174.36 | 02-JAN-06:20 |
General:Heating:Electricity | 243.18 | 0.00 | 01-JAN-00:40 | 195174.36 | 02-JAN-06:20 |
Fans:Electricity | 84.91 | 0.00 | 01-JAN-00:40 | 28035.94 | 17-JUL-07:10 |
General:Fans:Electricity | 84.91 | 0.00 | 01-JAN-00:40 | 28035.94 | 17-JUL-07:10 |
ExteriorLights:Electricity | 51.25 | 0.00 | 01-JAN-08:00 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 51.25 | 0.00 | 01-JAN-08:00 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 134.07 | 0.00 | 01-JAN-00:10 | 71385.25 | 14-AUG-11:00 |
General:Cooling:Electricity | 134.07 | 0.00 | 01-JAN-00:10 | 71385.25 | 14-AUG-11:00 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-07:20 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-07:20 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-07:20 |
WIRED_LTG_ELECTRICITY | 6.53 | 0.00 | 01-JAN-00:10 | 702.61 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 418.47 | 1886.44 | 09-JAN-05:10 | 120826.41 | 06-FEB-08:20 |
NaturalGas:HVAC | 283.19 | 0.00 | 01-JAN-00:40 | 111728.21 | 07-FEB-07:20 |
Heating:NaturalGas | 283.19 | 0.00 | 01-JAN-00:40 | 111728.21 | 07-FEB-07:20 |
General:Heating:NaturalGas | 283.19 | 0.00 | 01-JAN-00:40 | 111728.21 | 07-FEB-07:20 |
NaturalGas:Plant | 135.27 | 1886.44 | 03-JAN-08:20 | 11169.68 | 09-FEB-12:40 |
WaterSystems:NaturalGas | 135.27 | 1886.44 | 03-JAN-08:20 | 11169.68 | 09-FEB-12:40 |
Water Heater:WaterSystems:NaturalGas | 135.27 | 1886.44 | 03-JAN-08:20 | 11169.68 | 09-FEB-12:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2098.19 | 0.00 | 01-JAN-00:40 | 456876.52 | 17-JUL-08:10 |
EnergyTransfer:Building | 1026.75 | 0.00 | 01-JAN-00:40 | 191026.02 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 197.12 | 0.00 | 01-JAN-00:40 | 26419.23 | 07-AUG-08:00 |
Heating:EnergyTransfer | 222.68 | 0.00 | 01-JAN-00:40 | 191026.02 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.34 | 0.00 | 01-JAN-00:10 | 16202.56 | 02-JAN-06:50 |
General:Heating:EnergyTransfer | 222.68 | 0.00 | 01-JAN-00:40 | 191026.02 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.34 | 0.00 | 01-JAN-00:10 | 16202.56 | 02-JAN-06:50 |
Cooling:EnergyTransfer | 804.06 | 0.00 | 01-JAN-00:40 | 156963.89 | 17-JUL-13:00 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 196.79 | 0.00 | 01-JAN-00:40 | 26419.23 | 07-AUG-08:00 |
General:Cooling:EnergyTransfer | 804.06 | 0.00 | 01-JAN-00:40 | 156963.89 | 17-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 196.79 | 0.00 | 01-JAN-00:40 | 26419.23 | 07-AUG-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 50.60 | 0.00 | 01-JAN-00:40 | 15525.24 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 27.56 | 0.00 | 01-JAN-00:40 | 15525.24 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 27.56 | 0.00 | 01-JAN-00:40 | 15525.24 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 23.04 | 0.00 | 01-JAN-00:10 | 10068.40 | 12-JUN-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 23.04 | 0.00 | 01-JAN-00:10 | 10068.40 | 12-JUN-13:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 25.73 | 0.00 | 01-JAN-00:40 | 9359.63 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 13.38 | 0.00 | 01-JAN-00:40 | 9359.63 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 13.38 | 0.00 | 01-JAN-00:40 | 9359.63 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 12.35 | 0.00 | 01-JAN-00:10 | 5528.45 | 17-JUL-07:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 12.35 | 0.00 | 01-JAN-00:10 | 5528.45 | 17-JUL-07:10 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 26.21 | 0.00 | 01-JAN-00:40 | 8007.89 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 10.18 | 0.00 | 01-JAN-00:40 | 8007.89 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 10.18 | 0.00 | 01-JAN-00:40 | 8007.89 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 16.02 | 0.00 | 01-JAN-00:10 | 5644.79 | 17-JUL-07:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 16.02 | 0.00 | 01-JAN-00:10 | 5644.79 | 17-JUL-07:10 |
EnergyTransfer:Zone:CORE_MID | 128.42 | 0.00 | 01-JAN-00:40 | 21094.58 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 2.84 | 0.00 | 01-JAN-00:20 | 21094.58 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 2.84 | 0.00 | 01-JAN-00:20 | 21094.58 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 125.58 | 0.00 | 01-JAN-00:40 | 19264.25 | 17-JUL-09:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 125.58 | 0.00 | 01-JAN-00:40 | 19264.25 | 17-JUL-09:10 |
EnergyTransfer:Zone:CORE_TOP | 126.31 | 0.00 | 01-JAN-00:40 | 27672.54 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 13.02 | 0.00 | 01-JAN-00:40 | 27672.54 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 13.02 | 0.00 | 01-JAN-00:40 | 27672.54 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 113.28 | 0.00 | 01-JAN-00:10 | 20330.60 | 17-JUL-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 113.28 | 0.00 | 01-JAN-00:10 | 20330.60 | 17-JUL-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 46.58 | 0.00 | 01-JAN-00:40 | 10064.77 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 22.61 | 0.00 | 01-JAN-00:40 | 10064.77 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 22.61 | 0.00 | 01-JAN-00:40 | 10064.77 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.97 | 0.00 | 01-JAN-00:10 | 6949.98 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.97 | 0.00 | 01-JAN-00:10 | 6949.98 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 37.26 | 0.00 | 01-JAN-00:40 | 9616.99 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 13.06 | 0.00 | 01-JAN-00:40 | 9616.99 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 13.06 | 0.00 | 01-JAN-00:40 | 9616.99 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 24.20 | 0.00 | 01-JAN-00:20 | 8867.06 | 17-JUL-07:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 24.20 | 0.00 | 01-JAN-00:20 | 8867.06 | 17-JUL-07:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 54.89 | 0.00 | 01-JAN-00:40 | 13829.93 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 16.61 | 0.00 | 01-JAN-00:40 | 13829.93 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 16.61 | 0.00 | 01-JAN-00:40 | 13829.93 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 38.28 | 0.00 | 01-JAN-00:20 | 12399.50 | 21-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 38.28 | 0.00 | 01-JAN-00:20 | 12399.50 | 21-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 37.94 | 0.00 | 01-JAN-00:40 | 9845.61 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 14.04 | 0.00 | 01-JAN-00:40 | 9845.61 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 14.04 | 0.00 | 01-JAN-00:40 | 9845.61 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 23.90 | 0.00 | 01-JAN-00:20 | 9107.58 | 18-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 23.90 | 0.00 | 01-JAN-00:20 | 9107.58 | 18-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 33.39 | 0.00 | 01-JAN-00:40 | 7371.76 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 12.45 | 0.00 | 01-JAN-00:40 | 7371.76 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 12.45 | 0.00 | 01-JAN-00:40 | 7371.76 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.94 | 0.00 | 01-JAN-00:20 | 5479.10 | 14-AUG-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.94 | 0.00 | 01-JAN-00:20 | 5479.10 | 14-AUG-12:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 28.64 | 0.00 | 01-JAN-00:40 | 7251.49 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 6.65 | 0.00 | 01-JAN-00:40 | 7251.49 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 6.65 | 0.00 | 01-JAN-00:40 | 7251.49 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 21.99 | 0.00 | 01-JAN-00:20 | 7237.04 | 17-JUL-08:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 21.99 | 0.00 | 01-JAN-00:20 | 7237.04 | 17-JUL-08:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 55.73 | 0.00 | 01-JAN-00:40 | 13826.60 | 07-FEB-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 27.43 | 0.00 | 01-JAN-00:40 | 13826.60 | 07-FEB-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 27.43 | 0.00 | 01-JAN-00:40 | 13826.60 | 07-FEB-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 28.30 | 0.00 | 01-JAN-00:20 | 11068.04 | 10-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 28.30 | 0.00 | 01-JAN-00:20 | 11068.04 | 10-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 28.49 | 0.00 | 01-JAN-00:40 | 7321.10 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 7.24 | 0.00 | 01-JAN-00:40 | 7321.10 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 7.24 | 0.00 | 01-JAN-00:40 | 7321.10 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 21.26 | 0.00 | 01-JAN-00:20 | 7260.87 | 04-AUG-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 21.26 | 0.00 | 01-JAN-00:20 | 7260.87 | 04-AUG-17:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 37.73 | 0.00 | 01-JAN-00:40 | 8425.29 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 12.38 | 0.00 | 01-JAN-00:40 | 8425.29 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 12.38 | 0.00 | 01-JAN-00:40 | 8425.29 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 25.35 | 0.00 | 01-JAN-00:20 | 6298.39 | 21-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 25.35 | 0.00 | 01-JAN-00:20 | 6298.39 | 21-JUL-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 30.81 | 0.00 | 01-JAN-00:40 | 8766.44 | 03-JUL-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 7.00 | 0.00 | 01-JAN-00:40 | 7432.81 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 7.00 | 0.00 | 01-JAN-00:40 | 7432.81 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 23.81 | 0.00 | 01-JAN-00:20 | 8766.44 | 03-JUL-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 23.81 | 0.00 | 01-JAN-00:20 | 8766.44 | 03-JUL-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 48.65 | 0.00 | 01-JAN-00:40 | 12090.11 | 11-OCT-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 8.32 | 0.00 | 01-JAN-00:40 | 10678.55 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 8.32 | 0.00 | 01-JAN-00:40 | 10678.55 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 40.33 | 0.00 | 01-JAN-00:20 | 12090.11 | 11-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 40.33 | 0.00 | 01-JAN-00:20 | 12090.11 | 11-OCT-12:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.25 | 0.00 | 01-JAN-00:40 | 8679.90 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 7.58 | 0.00 | 01-JAN-00:40 | 7542.90 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 7.58 | 0.00 | 01-JAN-00:40 | 7542.90 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 24.67 | 0.00 | 01-JAN-00:20 | 8679.90 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 24.67 | 0.00 | 01-JAN-00:20 | 8679.90 | 10-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 52.88 | 0.00 | 01-JAN-00:10 | 6711.23 | 17-FEB-12:20 |
PlantLoopHeatingDemand:Plant | 52.88 | 0.00 | 01-JAN-00:10 | 6711.23 | 17-FEB-12:20 |
WaterSystems:PlantLoopHeatingDemand | 52.88 | 0.00 | 01-JAN-00:10 | 6711.23 | 17-FEB-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 52.88 | 0.00 | 01-JAN-00:10 | 6711.23 | 17-FEB-12:20 |
EnergyTransfer:HVAC | 1018.57 | 0.00 | 01-JAN-00:40 | 316754.85 | 14-AUG-10:10 |
HeatingCoils:EnergyTransfer | 469.73 | 0.00 | 01-JAN-00:40 | 262376.09 | 11-DEC-07:10 |
CoolingCoils:EnergyTransfer | 548.83 | 0.00 | 01-JAN-00:10 | 316754.85 | 14-AUG-10:10 |
EnergyTransfer:Plant | 52.88 | 0.00 | 01-JAN-00:10 | 6711.23 | 17-FEB-12:20 |
WaterSystems:EnergyTransfer | 52.88 | 0.00 | 01-JAN-00:10 | 6711.23 | 17-FEB-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 52.88 | 0.00 | 01-JAN-00:10 | 6711.23 | 17-FEB-12:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.338 | -196.786 | 0.000 | 0.000 | 33.218 | 55.599 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -128.535 |
CORE_MID | 0.000 | 0.000 | 2.835 | -125.584 | 0.000 | 0.000 | 34.714 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -82.990 |
CORE_TOP | 0.000 | 0.000 | 13.022 | -113.283 | 0.000 | 0.000 | 35.350 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -106.112 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 22.611 | -23.966 | 0.000 | 0.000 | 7.612 | 6.735 | 24.333 | 16.875 | 0.000 | 0.061 | 0.001 | 0.000 | -33.648 | 0.000 | -11.653 | -8.959 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 13.060 | -24.198 | 0.000 | 0.000 | 4.752 | 4.240 | 15.404 | 30.970 | 0.000 | 0.039 | 0.000 | 0.000 | -21.250 | 0.000 | -7.876 | -15.140 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 16.608 | -38.282 | 0.000 | 0.000 | 7.454 | 6.654 | 24.332 | 57.647 | 0.000 | 0.058 | 0.001 | 0.000 | -31.899 | 0.000 | -12.026 | -30.545 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 14.037 | -23.904 | 0.000 | 0.000 | 4.788 | 4.234 | 15.403 | 31.104 | 0.000 | 0.039 | 0.000 | 0.000 | -22.052 | 0.000 | -7.915 | -15.736 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 12.449 | -20.939 | 0.000 | 0.000 | 7.587 | 6.720 | 24.333 | 17.203 | 0.000 | 0.039 | 0.001 | 0.000 | -34.814 | 0.000 | -6.490 | -6.086 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 6.651 | -21.991 | 0.000 | 0.000 | 4.722 | 4.233 | 15.404 | 31.131 | 0.000 | 0.022 | 0.000 | 0.000 | -22.288 | 0.000 | -4.435 | -13.451 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 27.428 | -28.301 | 0.000 | 0.000 | 7.642 | 6.645 | 24.332 | 58.441 | 0.000 | 0.790 | 0.001 | 0.000 | -33.248 | 0.000 | -45.018 | -18.711 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 7.237 | -21.256 | 0.000 | 0.000 | 4.752 | 4.227 | 15.403 | 31.355 | 0.000 | 0.022 | 0.001 | 0.000 | -23.132 | 0.000 | -4.455 | -14.153 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 12.381 | -25.354 | 0.000 | 0.000 | 7.537 | 6.735 | 24.333 | 16.639 | 0.000 | 0.052 | 3.159 | 0.000 | -35.336 | 0.000 | -10.145 | -0.002 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 6.999 | -23.806 | 0.000 | 0.000 | 3.479 | 4.239 | 15.404 | 30.709 | 0.000 | 0.032 | 0.000 | 0.000 | -22.286 | 0.000 | -6.857 | -7.912 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 8.317 | -40.329 | 0.000 | 0.000 | 7.371 | 6.654 | 24.332 | 57.352 | 0.000 | 0.049 | 0.000 | 0.000 | -33.533 | 0.000 | -10.490 | -19.725 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 7.582 | -24.668 | 0.000 | 0.000 | 4.740 | 4.234 | 15.403 | 30.960 | 0.000 | 0.033 | 0.000 | 0.000 | -23.155 | 0.000 | -6.886 | -8.243 |
TOPFLOOR_PLENUM | 27.562 | -23.043 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.047 | 13.172 | 0.000 | 0.000 | 0.000 | -17.737 | -0.001 |
MIDFLOOR_PLENUM | 13.382 | -12.346 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.071 | 16.262 | 0.000 | 0.000 | 0.000 | -17.369 | -0.000 |
FIRSTFLOOR_PLENUM | 10.182 | -16.024 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.056 | 19.917 | 0.000 | 0.000 | 0.000 | -14.131 | -0.000 |
Total Facility | 51.126 | -51.412 | 171.556 | -752.647 | 0.000 | 0.000 | 175.718 | 232.346 | 705.434 | 410.385 | 0.000 | 1.410 | 52.513 | 0.000 | -336.641 | 0.000 | -183.482 | -476.302 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 18-SEP-05:12 | 0.00 | 0.00 | 0.00 | -42522.97 | 0.00 | 0.00 | 315.25 | 548.43 | 4989.51 | 0.00 | 0.00 | 0.00 | 36669.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 14-AUG-05:14 | 0.00 | 0.00 | 0.00 | -33401.63 | 0.00 | 0.00 | 322.38 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 29504.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 17-JUL-05:14 | 0.00 | 0.00 | 0.00 | -35229.96 | 0.00 | 0.00 | 315.28 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 31340.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-12:53 | 0.00 | 0.00 | 0.00 | -11088.65 | 0.00 | 0.00 | 27.83 | 27.57 | 478.42 | 4097.07 | 0.00 | 17.16 | 6440.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-JUL-09:02 | 0.00 | 0.00 | 0.00 | -13680.57 | 0.00 | 0.00 | 13.56 | 17.46 | 302.86 | 10870.96 | 0.00 | 0.00 | 2637.18 | 0.00 | -0.00 | 0.00 | -161.45 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-13:02 | 0.00 | 0.00 | 0.00 | -17657.03 | 0.00 | 0.00 | 23.89 | 27.57 | 478.41 | 14586.32 | 0.00 | 0.00 | 2992.14 | 0.00 | -0.00 | 0.00 | -451.31 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-17:12 | 0.00 | 0.00 | 0.00 | -15680.28 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 11807.35 | 0.00 | 0.00 | 3715.27 | 0.00 | -0.00 | 0.00 | -104.22 | 0.00 |
PERIMETER_BOT_ZN_3 | 07-AUG-06:03 | 0.00 | 0.00 | 0.00 | -6057.71 | 0.00 | 0.00 | 148.10 | 180.83 | 637.89 | 330.59 | 0.00 | 0.00 | 4775.95 | 0.00 | -0.00 | 0.00 | -15.64 | 0.00 |
PERIMETER_BOT_ZN_2 | 16-JUL-09:53 | 0.00 | 0.00 | 0.00 | -11138.03 | 0.00 | 0.00 | 16.20 | 17.46 | 302.86 | 8609.62 | 0.00 | 35.25 | 2156.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-12:02 | 0.00 | 0.00 | 0.00 | -13296.61 | 0.00 | 0.00 | 26.89 | 27.57 | 478.41 | 13574.55 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -162.34 | -648.48 |
PERIMETER_BOT_ZN_4 | 02-JUL-17:52 | 0.00 | 0.00 | 0.00 | -11807.41 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 10459.04 | 0.00 | 0.00 | 1129.29 | 0.00 | -0.00 | 0.00 | -42.79 | 0.00 |
PERIMETER_MID_ZN_3 | 13-AUG-15:41 | 0.00 | 0.00 | 0.00 | -9580.02 | 0.00 | 0.00 | 28.94 | 27.57 | 478.42 | 2900.40 | 0.00 | 184.96 | 5959.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 06-AUG-09:12 | 0.00 | 0.00 | 0.00 | -13599.24 | 0.00 | 0.00 | 15.40 | 17.46 | 302.86 | 8495.99 | 0.00 | 0.00 | 4871.31 | 0.00 | -0.00 | 0.00 | -103.77 | 0.00 |
PERIMETER_MID_ZN_1 | 30-JUL-12:32 | 0.00 | 0.00 | 0.00 | -15959.68 | 0.00 | 0.00 | 24.55 | 27.57 | 478.41 | 11490.17 | 0.00 | 0.00 | 4053.21 | 0.00 | -0.00 | 0.00 | -114.23 | 0.00 |
PERIMETER_MID_ZN_4 | 02-JUL-17:12 | 0.00 | 0.00 | 0.00 | -14495.16 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 11852.46 | 0.00 | 0.00 | 2465.02 | 0.00 | -0.00 | 0.00 | -84.19 | 0.00 |
TOPFLOOR_PLENUM | 12-JUN-13:30 | 0.00 | -10068.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.69 | 9926.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 17-JUL-06:15 | 0.00 | -6383.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6416.86 | 0.00 | -0.00 | 0.00 | -33.31 | 0.00 |
FIRSTFLOOR_PLENUM | 17-JUL-06:15 | 0.00 | -6696.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6720.66 | 0.00 | -0.00 | 0.00 | -24.22 | 0.00 |
Total Facility | 07-AUG-05:12 | 0.00 | -314.48 | 0.00 | -177170.82 | 0.00 | 0.00 | 1646.56 | 2743.54 | 17291.51 | 0.00 | 0.00 | 0.00 | 162408.38 | 0.00 | -5595.43 | 0.00 | -1009.26 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 18479.11 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 4405.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23096.49 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 24260.66 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26914.45 |
CORE_TOP | 26-DEC-05:01 | 0.00 | 0.00 | 31204.92 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -33858.71 |
PERIMETER_TOP_ZN_3 | 13-FEB-05:11 | 0.00 | 0.00 | 10853.53 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2658.10 | 0.00 | -2905.52 | -5849.35 |
PERIMETER_TOP_ZN_2 | 13-FEB-05:11 | 0.00 | 0.00 | 12625.88 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1768.10 | 0.00 | -1963.04 | -9248.89 |
PERIMETER_TOP_ZN_1 | 13-FEB-05:11 | 0.00 | 0.00 | 15673.82 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2759.75 | 0.00 | -2932.29 | -10541.22 |
PERIMETER_TOP_ZN_4 | 13-FEB-05:11 | 0.00 | 0.00 | 13812.26 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1833.80 | 0.00 | -1967.81 | -10364.80 |
PERIMETER_BOT_ZN_3 | 13-FEB-05:11 | 0.00 | 0.00 | 7920.64 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2830.96 | 0.00 | -1666.48 | -3982.64 |
PERIMETER_BOT_ZN_2 | 13-FEB-05:11 | 0.00 | 0.00 | 9664.57 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1884.18 | 0.00 | -1121.43 | -7013.11 |
PERIMETER_BOT_ZN_1 | 07-FEB-08:00 | 0.00 | 0.00 | 13826.23 | 0.00 | 0.00 | 0.00 | 253.18 | 165.45 | 637.88 | 0.00 | 0.00 | 0.00 | 10019.65 | 0.00 | -567.54 | 0.00 | -24334.85 | 0.00 |
PERIMETER_BOT_ZN_4 | 13-FEB-05:11 | 0.00 | 0.00 | 10129.45 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1946.71 | 0.00 | -1120.04 | -7416.85 |
PERIMETER_MID_ZN_3 | 05-FEB-22:22 | 0.00 | 0.00 | 9025.57 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3294.30 | 0.00 | -2159.03 | -4002.98 |
PERIMETER_MID_ZN_2 | 05-FEB-22:22 | 0.00 | 0.00 | 11034.27 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2200.30 | 0.00 | -1465.02 | -7641.63 |
PERIMETER_MID_ZN_1 | 06-FEB-05:01 | 0.00 | 0.00 | 13372.58 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3563.93 | 0.00 | -1976.02 | -8392.07 |
PERIMETER_MID_ZN_4 | 05-FEB-22:22 | 0.00 | 0.00 | 11141.60 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2262.66 | 0.00 | -1465.40 | -7686.21 |
TOPFLOOR_PLENUM | 06-FEB-06:13 | 16154.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -889.69 | -15265.01 |
MIDFLOOR_PLENUM | 02-JAN-07:03 | 9949.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -270.63 | -9678.70 |
FIRSTFLOOR_PLENUM | 02-JAN-07:01 | 9392.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -209.91 | -9182.09 |
Total Facility | 02-JAN-05:01 | 14083.29 | 0.00 | 200230.23 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.56 | 14333.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -18389.48 | 0.00 | -8499.32 | -202831.21 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.5264 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.8823 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.1893 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.3417 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.5221 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9876 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.7632 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0771 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.5947 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0756 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.7611 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0752 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8622 | 2.8622 | 0.6383 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0897 | 2.0897 | 0.6373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1714 | 2.1714 | 0.6362 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6809 | 0.6809 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8010 | 0.8010 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9908 | 0.9908 | 0.1348 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8780 | 0.8780 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5323 | 0.5323 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6554 | 0.6554 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7904 | 0.7904 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6861 | 0.6861 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5956 | 0.5956 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7862 | 0.7862 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9037 | 0.9037 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8141 | 0.8141 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.5264 | 4.8823 | 5.5264 | 1.0771 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.1893 | 4.3417 | 5.1893 | 1.0756 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.5221 | 4.9876 | 5.5221 | 1.0752 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4311 | 1.4311 | 0.6383 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0448 | 1.0448 | 0.6373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0857 | 1.0857 | 0.6362 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3405 | 0.3405 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4005 | 0.4005 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4954 | 0.4954 | 0.1348 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4390 | 0.4390 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2662 | 0.2662 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3277 | 0.3277 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3952 | 0.3952 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3430 | 0.3430 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2978 | 0.2978 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3931 | 0.3931 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4519 | 0.4519 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4071 | 0.4071 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.7632 | 1.0771 | 1.0771 | 1.0771 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.5947 | 1.0756 | 1.0756 | 1.0756 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.7611 | 1.0752 | 1.0752 | 1.0752 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 382.17 |
Number of hours cooling loads not met | 78.00 |
Number of hours not met | 460.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 243.18 | 195174.36 | 283.19 | 111728.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 134.07 | 71385.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 232.35 | 25003.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 51.25 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.69 | 839.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 84.91 | 28035.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 135.27 | 11169.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1463.03 |
Natural Gas | 0.00 | 418.47 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1881.50 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.64 |
Space Heating | 48.81 |
Space Cooling | 26.91 |
Fans (All) | 17.04 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 293.65 |
Subtotal | 293.65 |
Natural Gas [MJ/m2] | |
Space Heating | 56.84 |
Service Water Heating | 27.15 |
Miscellaneous (All) | 83.99 |
Subtotal | 83.99 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.35 |
Space Heating | 27.98 |
Space Cooling | 7.13 |
Fans (All) | 4.51 |
Service Water Heating | 7.19 |
Receptacle Equipment | 37.49 |
Miscellaneous | 3.35 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 854. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8713.33 | 46.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8754.67 | 5.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8720.83 | 39.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8666.83 | 93.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8677.83 | 82.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8634.83 | 125.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8703.83 | 56.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8719.00 | 41.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8672.17 | 87.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8732.67 | 27.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8674.00 | 86.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8686.67 | 73.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8639.33 | 120.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8646.83 | 113.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8634.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 125.17 | 0.00 | 0.00 | 0.00 |
Average | 8704.21 | 55.79 | 0.00 | 0.00 | 0.00 |
Sum | 156675.83 | 1004.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128296.00 | 8.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128303.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 8.00 | 0.00 | 0.00 | 0.00 |
Average | 34142.83 | 0.50 | 0.00 | 0.00 | 0.00 |
Sum | 614571.00 | 9.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8236.33 | 523.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8387.83 | 372.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8443.17 | 316.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8301.67 | 458.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8246.83 | 513.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8266.67 | 493.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8228.33 | 531.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8369.00 | 391.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8271.17 | 488.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8216.00 | 544.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8225.67 | 534.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8283.50 | 476.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8226.33 | 533.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8252.00 | 508.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8208.67 | 551.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7993.83 | 766.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8244.33 | 515.67 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8259.67 | 500.33 | 0.00 | 0.00 | 0.00 |
Min | 7993.83 | 316.83 | 0.00 | 0.00 | 0.00 |
Max | 8443.17 | 766.17 | 0.00 | 0.00 | 0.00 |
Average | 8258.94 | 501.06 | 0.00 | 0.00 | 0.00 |
Sum | 148661.00 | 9019.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127910.67 | 393.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128123.00 | 181.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128154.00 | 150.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24875.17 | 33.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14006.17 | 9.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24876.17 | 32.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 13997.33 | 18.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24865.67 | 43.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14015.33 | 0.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24442.17 | 466.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14011.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24881.83 | 27.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10133.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24886.83 | 22.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14014.67 | 1.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128154.00 | 466.83 | 0.00 | 0.00 | 0.00 |
Average | 34066.31 | 77.02 | 0.00 | 0.00 | 0.00 |
Sum | 613193.67 | 1386.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:03
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.740250E+10 | 8846.40 | 20-JAN-17:00 | -1.1 | -3.7 | 0.179030E+10 | 2606.61 | 13-JAN-14:09 | -1.1 | -3.7 |
February | 0.731637E+10 | 9366.43 | 17-FEB-17:00 | 1.10 | 0.20 | 0.165767E+10 | 2606.63 | 17-FEB-10:00 | 1.10 | 0.20 |
March | 0.121186E+11 | 17794.46 | 17-MAR-08:00 | 9.40 | 9.07 | 0.211852E+10 | 2606.64 | 16-MAR-09:00 | 9.40 | 9.07 |
April | 0.139399E+11 | 17848.58 | 25-APR-08:00 | 6.10 | 5.81 | 0.190525E+10 | 2606.66 | 12-APR-13:09 | 6.10 | 5.81 |
May | 0.200193E+11 | 32895.79 | 31-MAY-06:03 | 14.68 | 12.32 | 0.207641E+10 | 2606.68 | 05-MAY-13:09 | 14.68 | 12.32 |
June | 0.245339E+11 | 41233.34 | 19-JUN-05:12 | 16.70 | 15.97 | 0.207098E+10 | 2606.83 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.252308E+11 | 41744.87 | 05-JUL-05:12 | 19.23 | 16.66 | 0.192635E+10 | 2606.69 | 12-JUL-09:00 | 20.60 | 14.64 |
August | 0.268080E+11 | 41538.11 | 21-AUG-05:12 | 14.40 | 13.12 | 0.216266E+10 | 2667.62 | 14-AUG-09:00 | 14.40 | 13.12 |
September | 0.223385E+11 | 42532.87 | 18-SEP-05:12 | 9.60 | 8.73 | 0.191884E+10 | 2606.82 | 12-SEP-13:09 | 9.60 | 8.73 |
October | 0.167179E+11 | 34025.29 | 13-OCT-06:02 | 10.00 | 9.62 | 0.198927E+10 | 2606.65 | 03-OCT-09:20 | 10.00 | 9.62 |
November | 0.120774E+11 | 17452.49 | 07-NOV-08:02 | 2.20 | 0.89 | 0.195250E+10 | 2608.68 | 06-NOV-10:30 | 2.20 | 0.89 |
December | 0.828341E+10 | 13775.17 | 01-DEC-08:15 | 11.83 | 10.29 | 0.180777E+10 | 2606.63 | 22-DEC-10:20 | -1.8 | -2.6 |
Annual Sum or Average | 0.196787E+12 | 0.233765E+11 | ||||||||
Minimum of Months | 0.731637E+10 | 8846.40 | -1.1 | -3.7 | 0.165767E+10 | 2606.61 | -1.8 | -3.7 | ||
Maximum of Months | 0.268080E+11 | 42532.87 | 19.23 | 16.66 | 0.216266E+10 | 2667.62 | 20.60 | 15.40 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 10555.42 | 35.18 | 22-FEB-17:30 | 12.25 | 5.87 | 0.00 | 0.00 | 01-FEB-00:10 | 12.25 | 5.87 |
March | 0.245122E+09 | 5305.60 | 15-MAR-14:10 | 26.02 | 16.09 | 0.00 | 0.00 | 01-MAR-00:10 | 26.02 | 16.09 |
April | 0.783684E+09 | 4489.32 | 21-APR-14:20 | 14.60 | 8.38 | 0.00 | 0.00 | 01-APR-00:10 | 14.60 | 8.38 |
May | 0.244937E+10 | 6949.03 | 26-MAY-14:20 | 21.70 | 13.62 | 0.00 | 0.00 | 01-MAY-00:10 | 21.70 | 13.62 |
June | 0.491250E+10 | 10068.40 | 12-JUN-13:30 | 30.00 | 19.98 | 0.00 | 0.00 | 01-JUN-00:10 | 30.00 | 19.98 |
July | 0.613128E+10 | 10021.37 | 21-JUL-13:30 | 31.15 | 21.91 | 0.00 | 0.00 | 01-JUL-00:10 | 31.15 | 21.91 |
August | 0.536715E+10 | 9957.72 | 09-AUG-15:00 | 29.40 | 18.10 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.10 |
September | 0.266872E+10 | 7827.63 | 21-SEP-15:30 | 26.10 | 16.91 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 16.91 |
October | 0.464067E+09 | 4263.51 | 11-OCT-15:00 | 22.20 | 14.61 | 0.00 | 0.00 | 01-OCT-00:10 | 22.20 | 14.61 |
November | 21568903.32 | 649.65 | 04-NOV-15:20 | 18.30 | 13.65 | 0.00 | 0.00 | 01-NOV-00:10 | 18.30 | 13.65 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
Annual Sum or Average | 0.230435E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -1.0 | -1.6 | 0.00 | 0.00 | -1.0 | -1.6 | ||
Maximum of Months | 0.613128E+10 | 10068.40 | 31.15 | 21.91 | 0.00 | 0.00 | 31.15 | 21.91 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3367827.64 | 2618.03 | 04-JAN-05:01 | -12.2 | -12.8 | 0.00 | 0.00 | 01-JAN-00:10 | -12.2 | -12.8 |
February | 3594105.60 | 2423.45 | 09-FEB-05:01 | -11.0 | -11.7 | 0.00 | 0.00 | 01-FEB-00:10 | -11.0 | -11.7 |
March | 78388380.21 | 2118.47 | 07-MAR-05:01 | -13.3 | -13.9 | 0.00 | 0.00 | 01-MAR-00:10 | -13.3 | -13.9 |
April | 0.153495E+09 | 1482.00 | 11-APR-06:03 | 3.30 | 2.15 | 0.00 | 0.00 | 01-APR-00:10 | 3.30 | 2.15 |
May | 0.889990E+09 | 2260.37 | 31-MAY-16:00 | 22.20 | 14.47 | 0.00 | 0.00 | 01-MAY-00:10 | 22.20 | 14.47 |
June | 0.262986E+10 | 4560.49 | 12-JUN-15:20 | 29.43 | 20.07 | 0.00 | 0.00 | 01-JUN-00:10 | 29.43 | 20.07 |
July | 0.356887E+10 | 6384.33 | 17-JUL-06:15 | 22.97 | 21.14 | 0.00 | 0.00 | 01-JUL-00:10 | 22.97 | 21.14 |
August | 0.325080E+10 | 4603.27 | 14-AUG-15:40 | 27.80 | 21.36 | 0.00 | 0.00 | 01-AUG-00:10 | 27.80 | 21.36 |
September | 0.155341E+10 | 3242.28 | 18-SEP-12:40 | 18.70 | 12.39 | 0.00 | 0.00 | 01-SEP-00:10 | 18.70 | 12.39 |
October | 0.193932E+09 | 1147.95 | 24-OCT-06:03 | 1.70 | 0.40 | 0.00 | 0.00 | 01-OCT-00:10 | 1.70 | 0.40 |
November | 17158074.50 | 1425.58 | 18-NOV-06:01 | 1.02 | -0.8 | 0.00 | 0.00 | 01-NOV-00:10 | 1.02 | -0.8 |
December | 2885224.77 | 2378.14 | 28-DEC-05:01 | -11.8 | -12.1 | 0.00 | 0.00 | 01-DEC-00:10 | -11.8 | -12.1 |
Annual Sum or Average | 0.123458E+11 | 0.00 | ||||||||
Minimum of Months | 2885224.77 | 1147.95 | -13.3 | -13.9 | 0.00 | 0.00 | -13.3 | -13.9 | ||
Maximum of Months | 0.356887E+10 | 6384.33 | 29.43 | 21.36 | 0.00 | 0.00 | 29.43 | 21.36 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11835288.64 | 2163.52 | 04-JAN-05:01 | -12.2 | -12.8 | 0.00 | 0.00 | 01-JAN-00:10 | -12.2 | -12.8 |
February | 15585317.71 | 1963.95 | 09-FEB-05:01 | -11.0 | -11.7 | 0.00 | 0.00 | 01-FEB-00:10 | -11.0 | -11.7 |
March | 0.154743E+09 | 2814.23 | 04-MAR-06:01 | -10.6 | -11.5 | 0.00 | 0.00 | 01-MAR-00:10 | -10.6 | -11.5 |
April | 0.359230E+09 | 2259.74 | 11-APR-06:03 | 3.30 | 2.15 | 0.00 | 0.00 | 01-APR-00:10 | 3.30 | 2.15 |
May | 0.139218E+10 | 2525.30 | 31-MAY-16:00 | 22.20 | 14.47 | 0.00 | 0.00 | 01-MAY-00:10 | 22.20 | 14.47 |
June | 0.312208E+10 | 4604.14 | 12-JUN-15:10 | 29.72 | 20.02 | 0.00 | 0.00 | 01-JUN-00:10 | 29.72 | 20.02 |
July | 0.402874E+10 | 6696.61 | 17-JUL-06:15 | 22.97 | 21.14 | 0.00 | 0.00 | 01-JUL-00:10 | 22.97 | 21.14 |
August | 0.398874E+10 | 5005.99 | 14-AUG-15:30 | 27.80 | 21.53 | 0.00 | 0.00 | 01-AUG-00:10 | 27.80 | 21.53 |
September | 0.238827E+10 | 4010.76 | 18-SEP-12:05 | 18.40 | 12.35 | 0.00 | 0.00 | 01-SEP-00:10 | 18.40 | 12.35 |
October | 0.501049E+09 | 2188.56 | 17-OCT-06:01 | -2.8 | -3.4 | 0.00 | 0.00 | 01-OCT-00:10 | -2.8 | -3.4 |
November | 54133186.15 | 1737.25 | 03-NOV-06:03 | 1.70 | 0.39 | 0.00 | 0.00 | 01-NOV-00:10 | 1.70 | 0.39 |
December | 7086753.62 | 1706.15 | 15-DEC-06:11 | 2.20 | 1.70 | 0.00 | 0.00 | 01-DEC-00:10 | 2.20 | 1.70 |
Annual Sum or Average | 0.160237E+11 | 0.00 | ||||||||
Minimum of Months | 7086753.62 | 1706.15 | -12.2 | -12.8 | 0.00 | 0.00 | -12.2 | -12.8 | ||
Maximum of Months | 0.402874E+10 | 6696.61 | 29.72 | 21.53 | 0.00 | 0.00 | 29.72 | 21.53 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.411010E+10 | 5229.45 | 12-JAN-17:00 | -6.7 | -8.2 | 0.152096E+10 | 2205.90 | 20-JAN-14:00 | 0.60 | -3.3 |
February | 0.408205E+10 | 5380.35 | 17-FEB-17:00 | 1.10 | 0.20 | 0.139669E+10 | 2265.18 | 17-FEB-14:00 | 1.10 | 0.20 |
March | 0.774455E+10 | 11517.43 | 16-MAR-16:00 | 15.60 | 13.95 | 0.188230E+10 | 2608.15 | 17-MAR-09:20 | 9.60 | 9.18 |
April | 0.847283E+10 | 10772.90 | 21-APR-16:00 | 13.30 | 8.77 | 0.180935E+10 | 2608.21 | 28-APR-13:30 | 9.70 | 8.94 |
May | 0.127733E+11 | 13812.90 | 31-MAY-16:00 | 22.20 | 14.47 | 0.205946E+10 | 2606.65 | 10-MAY-13:20 | 22.20 | 14.47 |
June | 0.168843E+11 | 30543.20 | 19-JUN-05:12 | 16.70 | 15.97 | 0.206640E+10 | 2606.79 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.181263E+11 | 33284.64 | 17-JUL-05:14 | 22.80 | 21.19 | 0.192258E+10 | 2611.68 | 17-JUL-09:09 | 25.10 | 20.50 |
August | 0.184229E+11 | 33404.51 | 14-AUG-05:14 | 22.80 | 21.58 | 0.215793E+10 | 2606.80 | 04-AUG-09:09 | 22.80 | 21.58 |
September | 0.141754E+11 | 30592.95 | 18-SEP-05:12 | 9.60 | 8.73 | 0.191031E+10 | 2606.78 | 12-SEP-13:09 | 9.60 | 8.73 |
October | 0.925508E+10 | 12256.72 | 12-OCT-16:00 | 18.30 | 14.87 | 0.191444E+10 | 2607.98 | 27-OCT-13:20 | 10.17 | 7.43 |
November | 0.682293E+10 | 8093.23 | 01-NOV-16:00 | 9.40 | 6.91 | 0.174378E+10 | 2606.57 | 01-NOV-13:00 | 9.40 | 6.91 |
December | 0.471451E+10 | 5676.33 | 01-DEC-17:00 | 7.20 | 4.89 | 0.149547E+10 | 2357.67 | 01-DEC-14:00 | 7.20 | 4.89 |
Annual Sum or Average | 0.125584E+12 | 0.218797E+11 | ||||||||
Minimum of Months | 0.408205E+10 | 5229.45 | -6.7 | -8.2 | 0.139669E+10 | 2205.90 | 0.60 | -3.3 | ||
Maximum of Months | 0.184229E+11 | 33404.51 | 22.80 | 21.58 | 0.215793E+10 | 2611.68 | 25.10 | 21.58 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234959E+10 | 4755.63 | 12-JAN-16:40 | -6.5 | -8.3 | 0.146998E+10 | 2082.74 | 06-JAN-14:00 | -6.5 | -8.3 |
February | 0.261427E+10 | 4993.42 | 28-FEB-17:00 | -0.6 | -3.0 | 0.134923E+10 | 2151.74 | 17-FEB-14:00 | -0.6 | -3.0 |
March | 0.627248E+10 | 11691.88 | 16-MAR-16:00 | 15.60 | 13.95 | 0.178849E+10 | 2606.63 | 16-MAR-09:20 | 15.60 | 13.95 |
April | 0.753778E+10 | 11540.63 | 21-APR-16:00 | 13.30 | 8.77 | 0.172836E+10 | 2606.62 | 20-APR-13:20 | 13.30 | 8.77 |
May | 0.120699E+11 | 15342.60 | 31-MAY-16:00 | 22.20 | 14.47 | 0.203372E+10 | 2606.65 | 17-MAY-09:50 | 22.20 | 14.47 |
June | 0.169441E+11 | 31068.30 | 26-JUN-05:12 | 20.60 | 16.90 | 0.206094E+10 | 2606.79 | 22-JUN-13:09 | 20.60 | 16.90 |
July | 0.186088E+11 | 35234.68 | 17-JUL-05:14 | 22.80 | 21.19 | 0.192137E+10 | 2606.66 | 25-JUL-09:39 | 23.33 | 17.69 |
August | 0.182142E+11 | 31655.12 | 07-AUG-05:12 | 20.20 | 18.58 | 0.215414E+10 | 2606.80 | 02-AUG-13:09 | 20.20 | 18.58 |
September | 0.129744E+11 | 16532.60 | 18-SEP-13:10 | 18.72 | 12.47 | 0.189450E+10 | 2606.77 | 12-SEP-13:09 | 18.72 | 12.47 |
October | 0.787556E+10 | 11986.18 | 12-OCT-16:00 | 18.30 | 14.87 | 0.181285E+10 | 2608.02 | 13-OCT-09:39 | 10.60 | 9.99 |
November | 0.517067E+10 | 6324.06 | 01-NOV-16:00 | 9.40 | 6.91 | 0.160571E+10 | 2565.61 | 01-NOV-13:00 | 9.40 | 6.91 |
December | 0.265170E+10 | 5157.78 | 01-DEC-16:30 | 7.20 | 5.14 | 0.142483E+10 | 2221.94 | 01-DEC-14:00 | 7.20 | 5.14 |
Annual Sum or Average | 0.113283E+12 | 0.212441E+11 | ||||||||
Minimum of Months | 0.234959E+10 | 4755.63 | -6.5 | -8.3 | 0.134923E+10 | 2082.74 | -6.5 | -8.3 | ||
Maximum of Months | 0.186088E+11 | 35234.68 | 22.80 | 21.19 | 0.215414E+10 | 2608.02 | 23.33 | 18.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9977789.80 | 796.36 | 14-JAN-17:03 | 3.22 | 2.72 | 0.304215E+09 | 406.69 | 23-JAN-14:09 | -7.3 | -8.9 |
February | 16775181.85 | 805.31 | 18-FEB-17:03 | 0.82 | -0.6 | 0.275677E+09 | 406.69 | 06-FEB-14:30 | 0.82 | -0.6 |
March | 0.637915E+09 | 3654.88 | 15-MAR-14:40 | 25.77 | 16.18 | 0.352798E+09 | 549.50 | 15-MAR-13:30 | 25.77 | 16.18 |
April | 0.116571E+10 | 2463.08 | 21-APR-15:20 | 14.43 | 8.49 | 0.335499E+09 | 549.49 | 20-APR-13:20 | 14.43 | 8.49 |
May | 0.257280E+10 | 4709.01 | 23-MAY-14:40 | 23.90 | 13.32 | 0.416223E+09 | 549.50 | 10-MAY-13:00 | 23.90 | 13.32 |
June | 0.463516E+10 | 7068.36 | 12-JUN-06:03 | 22.98 | 18.45 | 0.432761E+09 | 549.53 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.551616E+10 | 11092.22 | 16-JUL-12:53 | 27.20 | 20.32 | 0.405104E+09 | 549.50 | 12-JUL-09:00 | 27.20 | 20.32 |
August | 0.498286E+10 | 8222.16 | 13-AUG-16:33 | 27.93 | 22.80 | 0.452193E+09 | 549.54 | 02-AUG-13:09 | 27.93 | 22.80 |
September | 0.284131E+10 | 4715.13 | 15-SEP-14:00 | 25.60 | 21.03 | 0.389556E+09 | 549.52 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.120799E+10 | 2485.38 | 12-OCT-15:20 | 18.30 | 15.11 | 0.351823E+09 | 549.49 | 12-OCT-13:20 | 18.30 | 15.11 |
November | 0.350993E+09 | 1177.45 | 16-NOV-16:50 | 18.12 | 13.51 | 0.309577E+09 | 491.74 | 16-NOV-14:00 | 18.12 | 13.51 |
December | 28604902.52 | 901.80 | 01-DEC-13:30 | 11.10 | 9.57 | 0.293226E+09 | 407.27 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.239663E+11 | 0.431865E+10 | ||||||||
Minimum of Months | 9977789.80 | 796.36 | 0.82 | -0.6 | 0.275677E+09 | 406.69 | -7.3 | -8.9 | ||
Maximum of Months | 0.551616E+10 | 11092.22 | 27.93 | 22.80 | 0.452193E+09 | 549.54 | 27.93 | 22.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8299626.29 | 503.85 | 14-JAN-17:03 | 3.22 | 2.72 | 0.192972E+09 | 257.49 | 23-JAN-14:09 | -7.3 | -8.9 |
February | 77641790.37 | 735.53 | 28-FEB-10:10 | -3.6 | -5.3 | 0.176362E+09 | 313.16 | 28-FEB-10:20 | -3.3 | -5.1 |
March | 0.676016E+09 | 2852.89 | 15-MAR-14:00 | 26.10 | 16.06 | 0.235236E+09 | 347.88 | 15-MAR-13:30 | 26.10 | 16.06 |
April | 0.138301E+10 | 5328.29 | 24-APR-09:10 | 6.28 | 2.92 | 0.230330E+09 | 347.88 | 21-APR-13:00 | 6.28 | 2.92 |
May | 0.292380E+10 | 7554.77 | 31-MAY-08:50 | 17.70 | 13.18 | 0.270389E+09 | 347.88 | 26-MAY-09:00 | 17.70 | 13.18 |
June | 0.461130E+10 | 10627.82 | 18-JUN-10:32 | 25.40 | 21.05 | 0.275423E+09 | 348.34 | 12-JUN-09:00 | 25.40 | 21.05 |
July | 0.533750E+10 | 13683.40 | 04-JUL-09:02 | 21.28 | 17.22 | 0.257063E+09 | 348.50 | 17-JUL-09:09 | 25.10 | 20.50 |
August | 0.483889E+10 | 8912.75 | 06-AUG-13:23 | 26.95 | 18.29 | 0.287393E+09 | 348.29 | 10-AUG-09:50 | 27.33 | 20.25 |
September | 0.296737E+10 | 9783.46 | 04-SEP-09:53 | 17.80 | 13.22 | 0.250761E+09 | 347.89 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.105752E+10 | 4128.15 | 11-OCT-09:30 | 15.85 | 11.81 | 0.237996E+09 | 347.88 | 10-OCT-09:09 | 15.85 | 11.81 |
November | 0.294579E+09 | 852.57 | 03-NOV-09:50 | 5.32 | 2.80 | 0.201195E+09 | 347.33 | 03-NOV-09:00 | 5.60 | 2.99 |
December | 22232959.20 | 577.17 | 01-DEC-13:30 | 11.10 | 9.57 | 0.186144E+09 | 259.37 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.241982E+11 | 0.280127E+10 | ||||||||
Minimum of Months | 8299626.29 | 503.85 | -3.6 | -5.3 | 0.176362E+09 | 257.49 | -7.3 | -8.9 | ||
Maximum of Months | 0.533750E+10 | 13683.40 | 26.95 | 21.05 | 0.287393E+09 | 348.50 | 27.33 | 21.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.312500E+09 | 3461.70 | 12-JAN-13:40 | -6.5 | -9.0 | 0.318484E+09 | 549.50 | 05-JAN-14:20 | -6.5 | -9.0 |
February | 0.437564E+09 | 5940.78 | 28-FEB-13:50 | 0.00 | -3.0 | 0.293100E+09 | 549.50 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.176600E+10 | 10078.53 | 15-MAR-13:30 | 25.55 | 15.84 | 0.389085E+09 | 549.72 | 15-MAR-13:39 | 25.73 | 15.91 |
April | 0.232985E+10 | 8173.81 | 21-APR-13:10 | 15.40 | 7.97 | 0.356494E+09 | 549.52 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.394358E+10 | 11240.46 | 14-MAY-14:53 | 26.10 | 17.84 | 0.419004E+09 | 549.51 | 10-MAY-13:00 | 26.10 | 17.84 |
June | 0.573697E+10 | 12769.59 | 25-JUN-14:53 | 26.70 | 17.81 | 0.431931E+09 | 549.53 | 22-JUN-13:09 | 26.70 | 17.81 |
July | 0.691997E+10 | 16504.81 | 16-JUL-12:13 | 27.60 | 20.55 | 0.404962E+09 | 550.06 | 31-JUL-13:00 | 25.00 | 19.43 |
August | 0.716325E+10 | 16701.41 | 13-AUG-12:32 | 29.63 | 22.57 | 0.452748E+09 | 550.04 | 03-AUG-13:00 | 29.63 | 22.57 |
September | 0.555887E+10 | 17656.03 | 10-SEP-13:02 | 17.20 | 10.56 | 0.394539E+09 | 550.18 | 22-SEP-13:50 | 23.72 | 15.13 |
October | 0.287192E+10 | 12099.90 | 11-OCT-12:30 | 21.95 | 13.79 | 0.381298E+09 | 549.72 | 11-OCT-13:30 | 22.20 | 14.14 |
November | 0.100022E+10 | 7522.95 | 03-NOV-12:40 | 8.53 | 4.68 | 0.334544E+09 | 549.50 | 01-NOV-13:00 | 8.53 | 4.68 |
December | 0.242044E+09 | 3712.56 | 16-DEC-13:30 | 5.60 | 3.03 | 0.300609E+09 | 549.48 | 04-DEC-14:09 | 5.60 | 3.03 |
Annual Sum or Average | 0.382827E+11 | 0.447680E+10 | ||||||||
Minimum of Months | 0.242044E+09 | 3461.70 | -6.5 | -9.0 | 0.293100E+09 | 549.48 | -6.5 | -9.0 | ||
Maximum of Months | 0.716325E+10 | 17656.03 | 29.63 | 22.57 | 0.452748E+09 | 550.18 | 29.63 | 22.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31121351.30 | 656.38 | 06-JAN-15:40 | -2.2 | -4.8 | 0.193310E+09 | 281.59 | 06-JAN-15:50 | -2.2 | -4.8 |
February | 75513658.46 | 1716.10 | 28-FEB-16:30 | 0.00 | -2.6 | 0.177155E+09 | 338.67 | 28-FEB-16:00 | -0.6 | -3.0 |
March | 0.666549E+09 | 3781.04 | 15-MAR-14:20 | 25.93 | 16.12 | 0.231971E+09 | 347.85 | 15-MAR-13:30 | 25.93 | 16.12 |
April | 0.133482E+10 | 6423.33 | 24-APR-16:00 | 13.30 | 7.63 | 0.217913E+09 | 347.85 | 27-APR-13:20 | 13.30 | 8.09 |
May | 0.288131E+10 | 13207.77 | 27-MAY-17:05 | 20.32 | 11.21 | 0.264205E+09 | 347.86 | 10-MAY-13:00 | 20.32 | 11.21 |
June | 0.474702E+10 | 15234.57 | 11-JUN-16:32 | 25.60 | 17.82 | 0.273752E+09 | 347.87 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.515236E+10 | 15679.10 | 02-JUL-17:12 | 24.63 | 16.88 | 0.256535E+09 | 347.86 | 25-JUL-09:20 | 22.77 | 17.50 |
August | 0.477083E+10 | 14893.44 | 06-AUG-16:42 | 27.80 | 19.02 | 0.286575E+09 | 347.88 | 02-AUG-13:09 | 27.80 | 19.02 |
September | 0.280952E+10 | 15527.16 | 04-SEP-16:32 | 18.30 | 12.97 | 0.247790E+09 | 347.87 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.109114E+10 | 6103.90 | 11-OCT-16:00 | 21.70 | 14.52 | 0.228169E+09 | 347.85 | 04-OCT-13:20 | 21.70 | 14.52 |
November | 0.307294E+09 | 1630.33 | 03-NOV-15:00 | 10.00 | 5.48 | 0.200754E+09 | 347.83 | 15-NOV-14:00 | 11.70 | 6.59 |
December | 36704418.14 | 669.34 | 04-DEC-15:50 | -0.5 | -3.2 | 0.186319E+09 | 284.69 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.239042E+11 | 0.276445E+10 | ||||||||
Minimum of Months | 31121351.30 | 656.38 | -2.2 | -4.8 | 0.177155E+09 | 281.59 | -2.2 | -4.8 | ||
Maximum of Months | 0.515236E+10 | 15679.10 | 27.80 | 19.02 | 0.286575E+09 | 347.88 | 27.80 | 19.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12418764.94 | 806.97 | 14-JAN-17:03 | 3.22 | 2.72 | 0.304943E+09 | 406.71 | 03-JAN-14:39 | 3.22 | 2.72 |
February | 15317123.92 | 809.10 | 18-FEB-17:03 | 0.82 | -0.6 | 0.276808E+09 | 406.70 | 06-FEB-14:30 | 0.82 | -0.6 |
March | 0.523955E+09 | 1376.07 | 15-MAR-15:30 | 25.30 | 16.10 | 0.347430E+09 | 546.12 | 15-MAR-13:00 | 25.30 | 16.10 |
April | 0.104141E+10 | 1255.17 | 21-APR-15:40 | 13.87 | 8.65 | 0.325074E+09 | 517.09 | 27-APR-13:00 | 13.30 | 8.09 |
May | 0.184397E+10 | 2813.31 | 23-MAY-14:40 | 23.90 | 13.32 | 0.408065E+09 | 549.50 | 10-MAY-13:20 | 23.90 | 13.32 |
June | 0.345439E+10 | 4772.71 | 26-JUN-15:40 | 28.13 | 20.69 | 0.433061E+09 | 549.53 | 22-JUN-13:09 | 28.13 | 20.69 |
July | 0.442306E+10 | 5429.56 | 17-JUL-06:07 | 22.88 | 21.17 | 0.404766E+09 | 549.50 | 25-JUL-09:20 | 22.77 | 17.50 |
August | 0.437037E+10 | 6059.22 | 07-AUG-06:03 | 20.68 | 18.73 | 0.453751E+09 | 564.42 | 14-AUG-09:00 | 23.90 | 22.00 |
September | 0.275837E+10 | 4037.88 | 15-SEP-14:00 | 25.60 | 21.03 | 0.397647E+09 | 549.53 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.156492E+10 | 2246.73 | 05-OCT-14:40 | 18.90 | 12.59 | 0.373729E+09 | 549.50 | 03-OCT-13:20 | 18.90 | 12.59 |
November | 0.852162E+09 | 1194.74 | 01-NOV-13:10 | 11.52 | 6.96 | 0.323088E+09 | 502.14 | 01-NOV-13:39 | 10.97 | 6.90 |
December | 79200501.86 | 1006.89 | 01-DEC-13:30 | 11.10 | 9.57 | 0.295597E+09 | 438.19 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.209395E+11 | 0.434396E+10 | ||||||||
Minimum of Months | 12418764.94 | 806.97 | 0.82 | -0.6 | 0.276808E+09 | 406.70 | 0.82 | -0.6 | ||
Maximum of Months | 0.442306E+10 | 6059.22 | 28.13 | 21.17 | 0.453751E+09 | 564.42 | 28.13 | 22.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12952588.44 | 552.50 | 14-JAN-07:05 | 3.30 | 2.57 | 0.193599E+09 | 257.49 | 03-JAN-14:39 | 3.30 | 2.57 |
February | 68849372.45 | 654.28 | 28-FEB-10:05 | -3.6 | -5.3 | 0.176569E+09 | 288.17 | 28-FEB-10:20 | -3.3 | -5.1 |
March | 0.593068E+09 | 1529.93 | 15-MAR-14:00 | 26.10 | 16.06 | 0.232477E+09 | 347.87 | 15-MAR-13:20 | 26.10 | 16.06 |
April | 0.113538E+10 | 3841.49 | 24-APR-09:20 | 6.47 | 3.13 | 0.230706E+09 | 347.88 | 19-APR-09:20 | 6.47 | 3.13 |
May | 0.214402E+10 | 6025.56 | 31-MAY-06:03 | 14.68 | 12.32 | 0.270347E+09 | 347.88 | 26-MAY-09:00 | 14.68 | 12.32 |
June | 0.380666E+10 | 8505.41 | 23-JUN-06:02 | 13.90 | 11.85 | 0.275752E+09 | 348.08 | 12-JUN-09:00 | 13.90 | 11.85 |
July | 0.462909E+10 | 11138.25 | 16-JUL-09:53 | 28.90 | 22.64 | 0.257158E+09 | 356.85 | 17-JUL-08:09 | 24.08 | 20.74 |
August | 0.452559E+10 | 8528.54 | 02-AUG-06:02 | 11.85 | 10.72 | 0.288028E+09 | 349.99 | 14-AUG-09:00 | 23.90 | 22.00 |
September | 0.302626E+10 | 7885.27 | 04-SEP-10:02 | 17.98 | 13.30 | 0.254143E+09 | 347.90 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.134568E+10 | 3699.80 | 11-OCT-09:30 | 15.85 | 11.81 | 0.252034E+09 | 347.88 | 31-OCT-09:20 | 12.77 | 7.83 |
November | 0.646217E+09 | 1434.72 | 03-NOV-08:45 | 3.72 | 1.73 | 0.212496E+09 | 348.02 | 06-NOV-10:30 | 8.35 | 4.34 |
December | 56889492.29 | 644.46 | 01-DEC-13:30 | 11.10 | 9.57 | 0.187522E+09 | 278.55 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.219907E+11 | 0.283083E+10 | ||||||||
Minimum of Months | 12952588.44 | 552.50 | -3.6 | -5.3 | 0.176569E+09 | 257.49 | -3.3 | -5.1 | ||
Maximum of Months | 0.462909E+10 | 11138.25 | 28.90 | 22.64 | 0.288028E+09 | 356.85 | 26.10 | 22.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 67945277.47 | 1041.91 | 21-JAN-12:30 | -0.6 | -3.1 | 0.289015E+09 | 433.33 | 12-JAN-14:00 | -0.6 | -3.1 |
February | 87408466.99 | 1229.60 | 18-FEB-14:40 | 2.80 | 0.63 | 0.263202E+09 | 472.85 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.782284E+09 | 6145.21 | 15-MAR-13:30 | 25.55 | 15.84 | 0.351181E+09 | 549.50 | 15-MAR-13:20 | 25.55 | 15.84 |
April | 0.114973E+10 | 3876.83 | 22-APR-13:40 | 15.20 | 6.94 | 0.329668E+09 | 549.51 | 21-APR-13:00 | 15.20 | 6.94 |
May | 0.207748E+10 | 5332.11 | 16-MAY-12:10 | 19.18 | 11.50 | 0.396293E+09 | 549.51 | 08-MAY-13:09 | 19.18 | 11.50 |
June | 0.394447E+10 | 10713.72 | 27-JUN-12:00 | 30.00 | 22.87 | 0.424532E+09 | 549.53 | 22-JUN-13:09 | 30.00 | 22.87 |
July | 0.582867E+10 | 10986.45 | 21-JUL-12:00 | 30.00 | 21.57 | 0.402989E+09 | 552.72 | 21-JUL-12:09 | 30.10 | 21.65 |
August | 0.638193E+10 | 13243.76 | 13-AUG-12:32 | 29.63 | 22.57 | 0.450164E+09 | 556.60 | 10-AUG-12:09 | 29.63 | 22.57 |
September | 0.476230E+10 | 13294.70 | 04-SEP-12:02 | 18.98 | 12.67 | 0.394172E+09 | 549.84 | 22-SEP-13:00 | 23.90 | 15.30 |
October | 0.229807E+10 | 10089.22 | 11-OCT-12:30 | 21.95 | 13.79 | 0.377339E+09 | 549.74 | 11-OCT-13:39 | 22.20 | 14.14 |
November | 0.811485E+09 | 4942.21 | 01-NOV-12:08 | 11.20 | 6.39 | 0.327267E+09 | 549.51 | 03-NOV-13:09 | 8.98 | 4.94 |
December | 0.109539E+09 | 2013.85 | 16-DEC-13:30 | 5.60 | 3.03 | 0.282342E+09 | 459.57 | 04-DEC-14:00 | 5.60 | 3.03 |
Annual Sum or Average | 0.283013E+11 | 0.428816E+10 | ||||||||
Minimum of Months | 67945277.47 | 1041.91 | -0.6 | -3.1 | 0.263202E+09 | 433.33 | -0.6 | -3.1 | ||
Maximum of Months | 0.638193E+10 | 13294.70 | 30.00 | 22.87 | 0.450164E+09 | 556.60 | 30.10 | 22.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31161958.51 | 658.57 | 12-JAN-16:10 | -6.2 | -8.3 | 0.193760E+09 | 280.95 | 12-JAN-16:19 | -6.3 | -8.3 |
February | 61574034.50 | 816.50 | 28-FEB-16:40 | -0.2 | -2.7 | 0.176808E+09 | 328.45 | 28-FEB-16:49 | -0.4 | -2.9 |
March | 0.551106E+09 | 1864.98 | 15-MAR-14:20 | 25.93 | 16.12 | 0.228273E+09 | 347.85 | 15-MAR-13:20 | 25.93 | 16.12 |
April | 0.103889E+10 | 3930.24 | 24-APR-17:30 | 11.70 | 7.64 | 0.219458E+09 | 347.85 | 20-APR-13:20 | 11.70 | 7.64 |
May | 0.202951E+10 | 7899.83 | 07-MAY-18:03 | 13.80 | 5.19 | 0.265776E+09 | 347.85 | 24-MAY-09:20 | 15.00 | 14.57 |
June | 0.391351E+10 | 11710.12 | 25-JUN-18:22 | 26.15 | 17.91 | 0.275355E+09 | 347.87 | 22-JUN-13:09 | 26.15 | 17.91 |
July | 0.441759E+10 | 11807.49 | 02-JUL-17:52 | 23.90 | 16.61 | 0.256965E+09 | 347.86 | 03-JUL-13:39 | 25.20 | 16.81 |
August | 0.442964E+10 | 11140.20 | 06-AUG-16:42 | 27.80 | 19.02 | 0.288012E+09 | 350.05 | 14-AUG-09:00 | 23.90 | 22.00 |
September | 0.278980E+10 | 10469.92 | 10-SEP-17:12 | 16.10 | 10.54 | 0.253643E+09 | 347.87 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.129920E+10 | 5115.85 | 11-OCT-16:00 | 21.70 | 14.52 | 0.244093E+09 | 347.85 | 06-OCT-13:20 | 21.70 | 14.52 |
November | 0.625479E+09 | 1520.21 | 03-NOV-15:40 | 9.27 | 5.12 | 0.210520E+09 | 347.80 | 15-NOV-14:00 | 11.70 | 6.59 |
December | 69006732.91 | 674.94 | 04-DEC-15:50 | -0.5 | -3.2 | 0.187580E+09 | 286.45 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.212565E+11 | 0.280024E+10 | ||||||||
Minimum of Months | 31161958.51 | 658.57 | -6.2 | -8.3 | 0.176808E+09 | 280.95 | -6.3 | -8.3 | ||
Maximum of Months | 0.442964E+10 | 11807.49 | 27.80 | 19.02 | 0.288012E+09 | 350.05 | 26.15 | 22.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21940483.05 | 811.09 | 14-JAN-17:03 | 3.22 | 2.72 | 0.305114E+09 | 406.69 | 23-JAN-14:09 | -7.3 | -8.9 |
February | 46920982.15 | 868.65 | 17-FEB-15:10 | 3.12 | 1.05 | 0.276912E+09 | 407.01 | 17-FEB-14:00 | 3.12 | 1.05 |
March | 0.856083E+09 | 3222.23 | 15-MAR-14:40 | 25.77 | 16.18 | 0.359779E+09 | 549.50 | 15-MAR-13:20 | 25.77 | 16.18 |
April | 0.140717E+10 | 2351.01 | 21-APR-15:20 | 14.43 | 8.49 | 0.349215E+09 | 549.50 | 20-APR-13:20 | 14.43 | 8.49 |
May | 0.269448E+10 | 4466.78 | 23-MAY-14:40 | 23.90 | 13.32 | 0.425754E+09 | 549.50 | 10-MAY-13:20 | 23.90 | 13.32 |
June | 0.461045E+10 | 7706.46 | 12-JUN-06:03 | 22.98 | 18.45 | 0.434822E+09 | 549.92 | 12-JUN-13:20 | 29.80 | 19.89 |
July | 0.536185E+10 | 7874.21 | 16-JUL-16:12 | 29.47 | 22.29 | 0.405501E+09 | 552.24 | 17-JUL-09:09 | 25.10 | 20.50 |
August | 0.498101E+10 | 9580.18 | 13-AUG-15:41 | 29.50 | 23.39 | 0.454015E+09 | 551.76 | 14-AUG-10:00 | 24.40 | 21.66 |
September | 0.303818E+10 | 4485.74 | 13-SEP-13:30 | 22.20 | 19.01 | 0.397194E+09 | 549.52 | 12-SEP-13:09 | 22.20 | 19.01 |
October | 0.154697E+10 | 2604.22 | 12-OCT-14:50 | 18.30 | 15.17 | 0.370094E+09 | 549.49 | 12-OCT-13:20 | 18.30 | 15.17 |
November | 0.713578E+09 | 1231.91 | 16-NOV-17:00 | 18.30 | 13.48 | 0.320002E+09 | 512.73 | 01-NOV-13:50 | 18.30 | 13.48 |
December | 75452281.42 | 991.54 | 01-DEC-13:30 | 11.10 | 9.57 | 0.294911E+09 | 432.62 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.253541E+11 | 0.439331E+10 | ||||||||
Minimum of Months | 21940483.05 | 811.09 | 3.12 | 1.05 | 0.276912E+09 | 406.69 | -7.3 | -8.9 | ||
Maximum of Months | 0.536185E+10 | 9580.18 | 29.50 | 23.39 | 0.454015E+09 | 552.24 | 29.80 | 21.66 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36084779.65 | 597.10 | 06-JAN-11:10 | -5.3 | -7.0 | 0.141799E+09 | 267.47 | 06-JAN-11:09 | -5.3 | -7.0 |
February | 92217728.68 | 806.27 | 28-FEB-10:00 | -3.9 | -5.5 | 0.130537E+09 | 325.65 | 28-FEB-09:00 | -3.9 | -5.5 |
March | 0.696965E+09 | 4254.12 | 16-MAR-12:02 | 13.98 | 12.06 | 0.178354E+09 | 356.46 | 29-MAR-12:09 | 9.50 | 3.37 |
April | 0.145531E+10 | 6821.66 | 24-APR-12:01 | 10.68 | 5.95 | 0.174874E+09 | 356.87 | 24-APR-10:09 | 10.68 | 5.95 |
May | 0.289035E+10 | 7773.29 | 31-MAY-10:05 | 18.48 | 13.84 | 0.202119E+09 | 356.47 | 26-MAY-10:09 | 18.48 | 13.84 |
June | 0.438938E+10 | 12091.27 | 11-JUN-08:13 | 22.23 | 15.06 | 0.204482E+09 | 356.47 | 22-JUN-12:09 | 19.18 | 13.72 |
July | 0.500580E+10 | 13476.41 | 04-JUL-08:42 | 21.10 | 17.25 | 0.191469E+09 | 364.23 | 17-JUL-07:00 | 23.90 | 20.77 |
August | 0.464318E+10 | 13598.68 | 06-AUG-09:12 | 24.47 | 17.45 | 0.213299E+09 | 356.50 | 17-AUG-10:09 | 25.28 | 15.57 |
September | 0.296420E+10 | 11342.37 | 04-SEP-10:02 | 17.98 | 13.30 | 0.187668E+09 | 356.47 | 12-SEP-12:09 | 20.68 | 15.09 |
October | 0.116173E+10 | 5600.41 | 11-OCT-10:05 | 17.15 | 12.50 | 0.182446E+09 | 356.46 | 03-OCT-10:09 | 17.15 | 12.50 |
November | 0.419883E+09 | 4804.34 | 01-NOV-12:02 | 11.20 | 6.39 | 0.154083E+09 | 356.45 | 01-NOV-12:09 | 11.20 | 6.39 |
December | 51551590.90 | 661.91 | 01-DEC-13:10 | 12.97 | 11.34 | 0.137207E+09 | 282.04 | 01-DEC-13:09 | 12.97 | 11.34 |
Annual Sum or Average | 0.238067E+11 | 0.209834E+10 | ||||||||
Minimum of Months | 36084779.65 | 597.10 | -5.3 | -7.0 | 0.130537E+09 | 267.47 | -5.3 | -7.0 | ||
Maximum of Months | 0.500580E+10 | 13598.68 | 24.47 | 17.45 | 0.213299E+09 | 364.23 | 25.28 | 20.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.442536E+09 | 4493.59 | 12-JAN-13:30 | -6.7 | -9.2 | 0.323150E+09 | 549.50 | 12-JAN-14:20 | -5.9 | -8.5 |
February | 0.595956E+09 | 6236.65 | 28-FEB-13:40 | 0.00 | -2.9 | 0.297765E+09 | 549.50 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.212579E+10 | 9583.10 | 15-MAR-13:30 | 25.55 | 15.84 | 0.399501E+09 | 549.86 | 15-MAR-13:50 | 25.92 | 15.99 |
April | 0.262112E+10 | 8127.44 | 24-APR-13:10 | 11.38 | 6.04 | 0.369215E+09 | 549.52 | 21-APR-13:00 | 11.38 | 6.04 |
May | 0.407092E+10 | 9000.98 | 14-MAY-14:53 | 26.10 | 17.84 | 0.427367E+09 | 549.51 | 05-MAY-13:09 | 26.10 | 17.84 |
June | 0.565418E+10 | 10021.52 | 25-JUN-15:13 | 27.07 | 17.97 | 0.434374E+09 | 550.84 | 12-JUN-13:20 | 27.07 | 17.97 |
July | 0.669003E+10 | 15963.84 | 30-JUL-12:32 | 25.60 | 19.52 | 0.405679E+09 | 550.90 | 17-JUL-13:20 | 25.60 | 19.52 |
August | 0.712398E+10 | 15632.30 | 06-AUG-12:32 | 27.03 | 18.20 | 0.454457E+09 | 550.63 | 10-AUG-13:20 | 29.47 | 20.04 |
September | 0.576442E+10 | 15477.36 | 04-SEP-12:02 | 18.98 | 12.67 | 0.399970E+09 | 550.36 | 22-SEP-13:20 | 23.17 | 14.63 |
October | 0.337542E+10 | 12090.11 | 11-OCT-12:30 | 21.95 | 13.79 | 0.395735E+09 | 549.92 | 11-OCT-13:20 | 22.20 | 14.14 |
November | 0.147795E+10 | 8514.76 | 03-NOV-12:25 | 8.35 | 4.56 | 0.347573E+09 | 549.51 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.386840E+09 | 4323.95 | 16-DEC-13:30 | 5.60 | 3.03 | 0.304597E+09 | 549.50 | 11-DEC-14:20 | 5.60 | 3.03 |
Annual Sum or Average | 0.403291E+11 | 0.455938E+10 | ||||||||
Minimum of Months | 0.386840E+09 | 4323.95 | -6.7 | -9.2 | 0.297765E+09 | 549.50 | -5.9 | -8.5 | ||
Maximum of Months | 0.712398E+10 | 15963.84 | 27.07 | 19.52 | 0.454457E+09 | 550.90 | 29.47 | 20.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55958042.86 | 706.93 | 12-JAN-16:10 | -6.2 | -8.3 | 0.194103E+09 | 297.37 | 12-JAN-16:19 | -6.3 | -8.3 |
February | 0.112573E+09 | 1789.63 | 28-FEB-16:40 | -0.2 | -2.7 | 0.178028E+09 | 338.67 | 28-FEB-16:00 | -0.6 | -3.0 |
March | 0.820583E+09 | 3479.35 | 15-MAR-14:20 | 25.93 | 16.12 | 0.237240E+09 | 347.85 | 15-MAR-13:20 | 25.93 | 16.12 |
April | 0.148788E+10 | 6392.95 | 24-APR-16:00 | 13.30 | 7.63 | 0.226578E+09 | 347.85 | 20-APR-13:20 | 13.30 | 7.63 |
May | 0.294070E+10 | 12174.67 | 27-MAY-17:05 | 20.32 | 11.21 | 0.270255E+09 | 347.85 | 17-MAY-09:20 | 20.32 | 11.21 |
June | 0.467031E+10 | 13878.30 | 11-JUN-16:52 | 25.60 | 17.82 | 0.275298E+09 | 347.87 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.498883E+10 | 14495.05 | 02-JUL-17:12 | 24.63 | 16.88 | 0.256963E+09 | 348.70 | 17-JUL-09:09 | 25.10 | 20.50 |
August | 0.473556E+10 | 14468.87 | 13-AUG-15:41 | 29.50 | 23.39 | 0.287701E+09 | 347.88 | 02-AUG-13:09 | 29.50 | 23.39 |
September | 0.292504E+10 | 12376.11 | 04-SEP-15:23 | 18.60 | 13.14 | 0.252279E+09 | 347.87 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.132295E+10 | 6063.41 | 11-OCT-16:00 | 21.70 | 14.52 | 0.239201E+09 | 347.85 | 12-OCT-13:20 | 17.57 | 14.20 |
November | 0.531871E+09 | 2090.69 | 03-NOV-15:00 | 10.00 | 5.48 | 0.207964E+09 | 347.84 | 09-NOV-14:00 | 8.30 | 5.23 |
December | 76102810.20 | 706.98 | 04-DEC-15:50 | -0.5 | -3.2 | 0.187292E+09 | 296.84 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.246684E+11 | 0.281290E+10 | ||||||||
Minimum of Months | 55958042.86 | 706.93 | -6.2 | -8.3 | 0.178028E+09 | 296.84 | -6.3 | -8.3 | ||
Maximum of Months | 0.498883E+10 | 14495.05 | 29.50 | 23.39 | 0.287701E+09 | 348.70 | 29.50 | 23.39 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.321610E+09 | 18479.16 | 02-JAN-05:01 | -0.7 |
February | 10678323.73 | 16209.79 | 14-FEB-07:01 | -9.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 5808631.61 | 16068.08 | 12-DEC-07:01 | -9.3 |
Annual Sum or Average | 0.338097E+09 | |||
Minimum of Months | 0.00 | 0.00 | -9.4 | |
Maximum of Months | 0.321610E+09 | 18479.16 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.679261E+10 | 15391.18 | 24-JAN-06:12 | -12.0 |
February | 0.596429E+10 | 16154.68 | 06-FEB-06:13 | -13.9 |
March | 0.285715E+10 | 15729.84 | 06-MAR-06:12 | -11.1 |
April | 0.114736E+10 | 11835.13 | 17-APR-05:13 | -4.1 |
May | 0.476144E+09 | 3259.64 | 08-MAY-05:03 | 3.40 |
June | 0.181347E+09 | 3040.09 | 14-JUN-05:03 | 6.78 |
July | 96693977.66 | 3388.56 | 20-JUL-05:03 | 23.90 |
August | 0.155632E+09 | 2487.36 | 03-AUG-05:03 | 11.10 |
September | 0.384604E+09 | 4442.73 | 04-SEP-08:00 | 12.80 |
October | 0.109222E+10 | 9515.76 | 30-OCT-06:02 | -0.4 |
November | 0.223405E+10 | 11958.09 | 24-NOV-06:13 | -3.7 |
December | 0.617931E+10 | 16016.92 | 11-DEC-06:13 | -18.2 |
Annual Sum or Average | 0.275614E+11 | |||
Minimum of Months | 96693977.66 | 2487.36 | -18.2 | |
Maximum of Months | 0.679261E+10 | 16154.68 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.321663E+10 | 9949.31 | 02-JAN-07:03 | -1.1 |
February | 0.281385E+10 | 9114.85 | 06-FEB-07:03 | -14.1 |
March | 0.157241E+10 | 6708.98 | 06-MAR-07:11 | -10.5 |
April | 0.762105E+09 | 3474.32 | 17-APR-10:05 | 2.30 |
May | 0.124967E+09 | 3519.33 | 14-MAY-14:53 | 26.10 |
June | 24788776.06 | 3236.31 | 25-JUN-15:13 | 27.07 |
July | 28869516.92 | 2822.92 | 30-JUL-15:12 | 24.60 |
August | 19663248.14 | 4365.24 | 13-AUG-15:41 | 29.50 |
September | 47696201.16 | 4513.65 | 04-SEP-15:23 | 18.60 |
October | 0.706418E+09 | 3793.66 | 30-OCT-10:05 | 9.18 |
November | 0.128089E+10 | 4118.58 | 24-NOV-07:02 | -3.2 |
December | 0.278375E+10 | 9370.49 | 26-DEC-07:03 | -12.3 |
Annual Sum or Average | 0.133820E+11 | |||
Minimum of Months | 19663248.14 | 2822.92 | -14.1 | |
Maximum of Months | 0.321663E+10 | 9949.31 | 29.50 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.264143E+10 | 9391.99 | 02-JAN-07:01 | -1.1 |
February | 0.220603E+10 | 5630.45 | 06-FEB-07:01 | -14.1 |
March | 0.122669E+10 | 3941.63 | 06-MAR-08:16 | -9.0 |
April | 0.430907E+09 | 4086.38 | 05-APR-07:06 | 1.97 |
May | 25511052.40 | 2137.28 | 30-MAY-05:13 | 12.20 |
June | 19720291.35 | 1620.74 | 04-JUN-14:30 | 20.00 |
July | 23125571.78 | 2807.56 | 20-JUL-04:03 | 24.82 |
August | 21855144.50 | 2235.05 | 13-AUG-15:12 | 29.80 |
September | 26764605.68 | 2574.42 | 04-SEP-15:23 | 18.60 |
October | 0.304952E+09 | 3711.60 | 30-OCT-07:06 | 0.87 |
November | 0.103776E+10 | 3608.51 | 09-NOV-08:05 | 5.60 |
December | 0.221704E+10 | 5817.20 | 26-DEC-07:01 | -12.3 |
Annual Sum or Average | 0.101818E+11 | |||
Minimum of Months | 19720291.35 | 1620.74 | -14.1 | |
Maximum of Months | 0.264143E+10 | 9391.99 | 29.80 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124578E+10 | 24260.70 | 02-JAN-05:01 | -0.7 |
February | 0.836856E+09 | 22215.24 | 06-FEB-05:01 | -14.8 |
March | 89739184.08 | 20844.28 | 06-MAR-06:01 | -11.1 |
April | 8080887.40 | 19327.80 | 17-APR-06:01 | -4.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 358348.96 | 3583.49 | 30-OCT-06:02 | -0.4 |
November | 26653962.28 | 19267.29 | 24-NOV-07:01 | -3.2 |
December | 0.627969E+09 | 22464.61 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.283544E+10 | |||
Minimum of Months | 0.00 | 0.00 | -14.8 | |
Maximum of Months | 0.124578E+10 | 24260.70 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.432464E+10 | 30993.48 | 09-JAN-05:11 | -9.4 |
February | 0.354924E+10 | 31132.14 | 06-FEB-05:01 | -14.8 |
March | 0.987512E+09 | 29958.99 | 06-MAR-05:01 | -11.1 |
April | 0.152409E+09 | 28162.72 | 17-APR-05:01 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 94453497.21 | 27233.88 | 30-OCT-05:01 | -0.1 |
November | 0.510475E+09 | 28702.96 | 24-NOV-05:11 | -3.2 |
December | 0.340287E+10 | 31205.14 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.130216E+11 | |||
Minimum of Months | 0.00 | 0.00 | -14.8 | |
Maximum of Months | 0.432464E+10 | 31205.14 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.662637E+10 | 10504.91 | 09-JAN-01:52 | -8.3 |
February | 0.571845E+10 | 10853.66 | 13-FEB-05:11 | -9.1 |
March | 0.230370E+10 | 10240.36 | 06-MAR-04:42 | -11.1 |
April | 0.418192E+09 | 9836.35 | 17-APR-04:01 | -3.4 |
May | 4186004.77 | 7773.61 | 01-MAY-06:03 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 3482424.83 | 7763.27 | 30-SEP-06:03 | 7.30 |
October | 0.310963E+09 | 9430.03 | 30-OCT-04:02 | -0.5 |
November | 0.136387E+10 | 9804.90 | 24-NOV-05:11 | -3.2 |
December | 0.586215E+10 | 10728.15 | 26-DEC-01:42 | -11.6 |
Annual Sum or Average | 0.226114E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.6 | |
Maximum of Months | 0.662637E+10 | 10853.66 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.389732E+10 | 12042.75 | 09-JAN-01:52 | -8.3 |
February | 0.334280E+10 | 12626.23 | 13-FEB-05:11 | -9.1 |
March | 0.104862E+10 | 11662.02 | 06-MAR-04:42 | -11.1 |
April | 0.163248E+09 | 11389.70 | 17-APR-04:01 | -3.4 |
May | 979886.27 | 2675.03 | 02-MAY-06:03 | 7.98 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 1684196.00 | 5456.81 | 30-SEP-06:03 | 7.30 |
October | 0.154496E+09 | 10897.05 | 30-OCT-04:02 | -0.5 |
November | 0.779714E+09 | 11348.59 | 24-NOV-05:11 | -3.2 |
December | 0.367104E+10 | 12371.54 | 26-DEC-01:42 | -11.6 |
Annual Sum or Average | 0.130599E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.6 | |
Maximum of Months | 0.389732E+10 | 12626.23 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.485644E+10 | 14959.72 | 09-JAN-01:52 | -8.3 |
February | 0.432463E+10 | 15674.15 | 13-FEB-05:11 | -9.1 |
March | 0.135713E+10 | 14438.65 | 06-MAR-04:42 | -11.1 |
April | 0.340379E+09 | 14053.39 | 17-APR-04:01 | -3.4 |
May | 7046176.44 | 8811.95 | 01-MAY-06:03 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 2451003.98 | 7618.66 | 30-SEP-06:03 | 7.30 |
October | 0.203775E+09 | 13406.33 | 30-OCT-04:02 | -0.5 |
November | 0.996262E+09 | 14111.95 | 24-NOV-05:11 | -3.2 |
December | 0.451966E+10 | 15402.34 | 26-DEC-01:42 | -11.6 |
Annual Sum or Average | 0.166078E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.6 | |
Maximum of Months | 0.485644E+10 | 15674.15 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.418767E+10 | 13153.42 | 09-JAN-01:52 | -8.3 |
February | 0.358961E+10 | 13812.68 | 13-FEB-05:11 | -9.1 |
March | 0.123203E+10 | 12412.43 | 20-MAR-04:11 | -2.8 |
April | 0.246802E+09 | 12298.56 | 17-APR-04:01 | -3.4 |
May | 3622079.20 | 5483.93 | 01-MAY-06:03 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 2160212.32 | 5208.61 | 30-SEP-06:03 | 7.30 |
October | 0.185528E+09 | 11785.95 | 30-OCT-04:02 | -0.5 |
November | 0.854753E+09 | 12377.74 | 24-NOV-05:11 | -3.2 |
December | 0.373518E+10 | 13511.05 | 26-DEC-01:42 | -11.6 |
Annual Sum or Average | 0.140374E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.6 | |
Maximum of Months | 0.418767E+10 | 13812.68 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.422547E+10 | 7837.01 | 02-JAN-02:62 | -1.7 |
February | 0.350917E+10 | 7920.81 | 13-FEB-05:11 | -9.1 |
March | 0.148265E+10 | 7716.45 | 06-MAR-05:11 | -11.1 |
April | 0.190591E+09 | 6978.09 | 17-APR-05:01 | -4.0 |
May | 973744.39 | 3838.10 | 01-MAY-06:03 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 15743357.43 | 6195.64 | 17-OCT-06:01 | -2.8 |
November | 0.224003E+09 | 6776.32 | 24-NOV-06:01 | -3.8 |
December | 0.280057E+10 | 7771.88 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.124492E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.422547E+10 | 7920.81 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239680E+10 | 9335.80 | 09-JAN-05:11 | -9.4 |
February | 0.189920E+10 | 9664.93 | 13-FEB-05:11 | -9.1 |
March | 0.484023E+09 | 9139.64 | 06-MAR-05:11 | -11.1 |
April | 43620750.61 | 8417.23 | 17-APR-05:01 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 6926010.66 | 7462.05 | 17-OCT-06:01 | -2.8 |
November | 0.121318E+09 | 8258.68 | 24-NOV-06:01 | -3.8 |
December | 0.169967E+10 | 9471.62 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.665155E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.239680E+10 | 9664.93 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.699584E+10 | 13347.24 | 04-JAN-08:00 | -13.3 |
February | 0.602432E+10 | 13826.60 | 07-FEB-08:00 | -15.6 |
March | 0.311324E+10 | 12833.43 | 07-MAR-07:10 | -12.9 |
April | 0.161804E+10 | 11510.86 | 17-APR-06:50 | -3.5 |
May | 0.566412E+09 | 10056.15 | 01-MAY-06:10 | 2.35 |
June | 0.112558E+09 | 8959.91 | 06-JUN-06:10 | 7.67 |
July | 2656814.09 | 3333.02 | 07-JUL-06:08 | 13.17 |
August | 17144326.68 | 4893.17 | 31-AUG-06:08 | 11.78 |
September | 0.140713E+09 | 8965.55 | 05-SEP-06:04 | 6.38 |
October | 0.856144E+09 | 10740.42 | 17-OCT-06:10 | -2.8 |
November | 0.215726E+10 | 11336.62 | 24-NOV-07:10 | -3.2 |
December | 0.582429E+10 | 13560.87 | 11-DEC-08:00 | -15.0 |
Annual Sum or Average | 0.274286E+11 | |||
Minimum of Months | 2656814.09 | 3333.02 | -15.6 | |
Maximum of Months | 0.699584E+10 | 13826.60 | 13.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.263997E+10 | 9805.81 | 09-JAN-05:11 | -9.4 |
February | 0.209851E+10 | 10129.82 | 13-FEB-05:11 | -9.1 |
March | 0.549135E+09 | 9573.22 | 06-MAR-05:11 | -11.1 |
April | 66880650.45 | 8608.37 | 17-APR-05:01 | -4.0 |
May | 168684.35 | 1124.56 | 01-MAY-06:03 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 7336840.29 | 7822.69 | 17-OCT-06:01 | -2.8 |
November | 0.128981E+09 | 8558.19 | 24-NOV-06:01 | -3.8 |
December | 0.174556E+10 | 9914.10 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.723654E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.263997E+10 | 10129.82 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.407271E+10 | 8827.63 | 29-JAN-22:52 | -8.9 |
February | 0.337135E+10 | 9025.68 | 05-FEB-22:22 | -12.8 |
March | 0.103894E+10 | 8439.68 | 06-MAR-05:01 | -11.1 |
April | 0.108649E+09 | 7892.53 | 17-APR-04:01 | -3.4 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 53578119.55 | 7549.17 | 30-OCT-05:01 | -0.1 |
November | 0.417408E+09 | 7867.82 | 24-NOV-05:03 | -3.0 |
December | 0.331823E+10 | 8853.53 | 26-DEC-04:51 | -12.2 |
Annual Sum or Average | 0.123809E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.407271E+10 | 9025.68 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232215E+10 | 10625.67 | 29-JAN-22:52 | -8.9 |
February | 0.190796E+10 | 11034.34 | 05-FEB-22:22 | -12.8 |
March | 0.415828E+09 | 10248.86 | 06-MAR-05:01 | -11.1 |
April | 37816934.59 | 9301.26 | 17-APR-05:01 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 30083576.45 | 9137.69 | 30-OCT-05:01 | -0.1 |
November | 0.247818E+09 | 9427.14 | 25-NOV-06:01 | -1.7 |
December | 0.203750E+10 | 10822.08 | 26-DEC-04:51 | -12.2 |
Annual Sum or Average | 0.699915E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.232215E+10 | 11034.34 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.276659E+10 | 13115.24 | 30-JAN-04:52 | -9.4 |
February | 0.234183E+10 | 13372.52 | 06-FEB-05:01 | -14.8 |
March | 0.485755E+09 | 12647.40 | 06-MAR-05:01 | -11.1 |
April | 83891096.43 | 11544.78 | 17-APR-05:01 | -4.0 |
May | 101737.67 | 678.25 | 01-MAY-06:03 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 34266542.09 | 11213.32 | 30-OCT-05:01 | -0.1 |
November | 0.289102E+09 | 11527.06 | 24-NOV-06:01 | -3.8 |
December | 0.231592E+10 | 13276.50 | 26-DEC-04:51 | -12.2 |
Annual Sum or Average | 0.831746E+10 | |||
Minimum of Months | 0.00 | 0.00 | -14.8 | |
Maximum of Months | 0.276659E+10 | 13372.52 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255221E+10 | 10808.16 | 29-JAN-22:52 | -8.9 |
February | 0.207316E+10 | 11141.67 | 05-FEB-22:22 | -12.8 |
March | 0.504904E+09 | 10325.73 | 06-MAR-05:01 | -11.1 |
April | 60189707.99 | 9326.68 | 17-APR-05:01 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 33279971.68 | 9091.65 | 30-OCT-05:01 | -0.1 |
November | 0.267897E+09 | 9370.15 | 25-NOV-06:01 | -1.7 |
December | 0.208991E+10 | 10931.37 | 26-DEC-04:51 | -12.2 |
Annual Sum or Average | 0.758156E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.255221E+10 | 11141.67 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.627375E+09 | 1040.56 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.533192E+09 | 910.43 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.593041E+09 | 743.99 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.509657E+09 | 580.87 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.535804E+09 | 550.23 | 11-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.526102E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.495177E+09 | 542.18 | 11-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.559151E+09 | 549.56 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.522147E+09 | 714.78 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.574047E+09 | 1004.69 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.629334E+09 | 1040.56 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.629725E+09 | 1040.56 | 01-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.673475E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.495177E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.629725E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.390163E+09 | 658.76 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335322E+09 | 581.37 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.373985E+09 | 368.11 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.323022E+09 | 355.46 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.341027E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.335029E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.315043E+09 | 314.23 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.355401E+09 | 344.14 | 28-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.329794E+09 | 365.33 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.359053E+09 | 532.36 | 26-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.391202E+09 | 658.76 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.390466E+09 | 658.76 | 01-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.423951E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.315043E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.391202E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.604448E+09 | 1040.56 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.523779E+09 | 890.11 | 01-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.588652E+09 | 721.84 | 17-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.510705E+09 | 579.98 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.539104E+09 | 552.96 | 11-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.529231E+09 | 496.34 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.498254E+09 | 545.33 | 11-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.561324E+09 | 551.45 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.520806E+09 | 698.07 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.563432E+09 | 884.71 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.607893E+09 | 1040.56 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.606526E+09 | 1040.56 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.665415E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.498254E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.607893E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.388563E+09 | 658.71 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.334122E+09 | 573.49 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.373968E+09 | 496.26 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.322922E+09 | 430.24 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.339742E+09 | 357.18 | 11-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.333314E+09 | 342.04 | 21-JUN-08:09 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314075E+09 | 353.27 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.354205E+09 | 359.39 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330608E+09 | 477.89 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.361458E+09 | 635.98 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.390421E+09 | 658.71 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.390550E+09 | 658.71 | 01-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.423395E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.314075E+09 | 342.04 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.390550E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.624726E+09 | 1040.56 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.531842E+09 | 905.40 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.591970E+09 | 732.29 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.509252E+09 | 578.00 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.535244E+09 | 545.89 | 11-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.525872E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.494846E+09 | 537.48 | 11-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.558552E+09 | 545.18 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.521220E+09 | 702.09 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.572539E+09 | 1002.77 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.626993E+09 | 1040.56 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.627016E+09 | 1040.56 | 01-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.672007E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.494846E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.627016E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.388999E+09 | 658.76 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.334645E+09 | 578.98 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.373519E+09 | 366.33 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.322751E+09 | 353.15 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.340701E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.334831E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314811E+09 | 314.23 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.355124E+09 | 341.54 | 28-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.329332E+09 | 363.44 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.358506E+09 | 528.00 | 26-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.390373E+09 | 658.76 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.389530E+09 | 658.76 | 01-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.423312E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.314811E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.390373E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.603081E+09 | 1040.56 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.523148E+09 | 884.06 | 01-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.587957E+09 | 709.06 | 17-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.510175E+09 | 577.06 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.538371E+09 | 548.78 | 11-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.528795E+09 | 496.34 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.497784E+09 | 540.82 | 11-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.560765E+09 | 547.18 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.520047E+09 | 684.59 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.562656E+09 | 877.23 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.606890E+09 | 1040.56 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.605003E+09 | 1040.56 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.664467E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.497784E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.606890E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387499E+09 | 658.71 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.333511E+09 | 570.87 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.373526E+09 | 491.28 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.322451E+09 | 423.29 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.339380E+09 | 355.12 | 11-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.333069E+09 | 339.98 | 21-JUN-08:09 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.313812E+09 | 351.09 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.353865E+09 | 357.44 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330087E+09 | 472.37 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.360659E+09 | 634.93 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.389464E+09 | 658.71 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.389309E+09 | 658.71 | 01-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.422663E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.313812E+09 | 339.98 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.389464E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.627372E+09 | 1040.56 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.533190E+09 | 910.42 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.593040E+09 | 743.97 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.509656E+09 | 580.87 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.535803E+09 | 550.22 | 11-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.526102E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.495177E+09 | 542.17 | 11-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.559150E+09 | 549.55 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.522146E+09 | 714.75 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.574045E+09 | 1004.69 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.629331E+09 | 1040.56 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.629721E+09 | 1040.56 | 01-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.673473E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.495177E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.629721E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.390161E+09 | 658.76 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335322E+09 | 581.36 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.373985E+09 | 368.10 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.323021E+09 | 355.45 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.341026E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.335028E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.315043E+09 | 314.23 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.355401E+09 | 344.14 | 28-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.329793E+09 | 365.32 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.359053E+09 | 532.35 | 26-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.391200E+09 | 658.76 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.390464E+09 | 658.76 | 01-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.423950E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.315043E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.391200E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.604447E+09 | 1040.56 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.523778E+09 | 890.10 | 01-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.588651E+09 | 721.81 | 17-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.510704E+09 | 579.98 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.539103E+09 | 552.95 | 11-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.529231E+09 | 496.34 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.498253E+09 | 545.32 | 11-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.561323E+09 | 551.44 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.520806E+09 | 698.04 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.563431E+09 | 884.71 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.607892E+09 | 1040.56 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.606525E+09 | 1040.56 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.665414E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.498253E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.607892E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.388562E+09 | 658.71 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.334121E+09 | 573.48 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.373968E+09 | 496.25 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.322922E+09 | 430.22 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.339742E+09 | 357.18 | 11-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.333314E+09 | 342.03 | 21-JUN-08:09 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314075E+09 | 353.27 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.354204E+09 | 359.39 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330607E+09 | 477.87 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.361457E+09 | 635.98 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.390419E+09 | 658.71 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.390548E+09 | 658.71 | 01-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.423394E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.314075E+09 | 342.03 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.390548E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.627375E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187840E+10 |
February | 0.901968E+09 | 0.533192E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200093E+10 |
March | 0.107774E+10 | 0.593041E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 451501.15 | 0.122548E+10 |
April | 0.956342E+09 | 0.509657E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.996594E+09 |
May | 0.103597E+10 | 0.535804E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 256477.40 | 0.619284E+09 |
June | 0.103308E+10 | 0.526102E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10673142.99 | 0.364024E+09 |
July | 0.959235E+09 | 0.495177E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26405277.06 | 0.216834E+09 |
August | 0.107774E+10 | 0.559151E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21256140.39 | 0.247264E+09 |
September | 0.956342E+09 | 0.522147E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1515984.16 | 0.361304E+09 |
October | 0.994195E+09 | 0.574047E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758852E+09 |
November | 0.984487E+09 | 0.629334E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100419E+10 |
December | 0.959235E+09 | 0.629725E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197972E+10 |
Annual Sum or Average | 0.119305E+11 | 0.673475E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60558523.15 | 0.116529E+11 |
Minimum of Months | 0.901968E+09 | 0.495177E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216834E+09 |
Maximum of Months | 0.107774E+10 | 0.629725E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26405277.06 | 0.200093E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.390163E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125432E+10 |
February | 0.571020E+09 | 0.335322E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133730E+10 |
March | 0.682301E+09 | 0.373985E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 291708.93 | 0.827719E+09 |
April | 0.605444E+09 | 0.323022E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681428E+09 |
May | 0.655854E+09 | 0.341027E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 134598.68 | 0.431023E+09 |
June | 0.654023E+09 | 0.335029E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7027375.70 | 0.250769E+09 |
July | 0.607275E+09 | 0.315043E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17218766.84 | 0.149939E+09 |
August | 0.682301E+09 | 0.355401E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13412967.84 | 0.171542E+09 |
September | 0.605444E+09 | 0.329794E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 983860.74 | 0.250620E+09 |
October | 0.629407E+09 | 0.359053E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523499E+09 |
November | 0.623262E+09 | 0.391202E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676007E+09 |
December | 0.607275E+09 | 0.390466E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132197E+10 |
Annual Sum or Average | 0.755301E+10 | 0.423951E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39069278.73 | 0.787614E+10 |
Minimum of Months | 0.571020E+09 | 0.315043E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149939E+09 |
Maximum of Months | 0.682301E+09 | 0.391202E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17218766.84 | 0.133730E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.604448E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191348E+10 |
February | 0.901968E+09 | 0.523779E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202651E+10 |
March | 0.107774E+10 | 0.588652E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 437443.26 | 0.128968E+10 |
April | 0.956342E+09 | 0.510705E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103672E+10 |
May | 0.103597E+10 | 0.539104E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 202668.91 | 0.641096E+09 |
June | 0.103308E+10 | 0.529231E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10564827.83 | 0.368858E+09 |
July | 0.959235E+09 | 0.498254E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25845702.91 | 0.222291E+09 |
August | 0.107774E+10 | 0.561324E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19666954.58 | 0.258973E+09 |
September | 0.956342E+09 | 0.520806E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1383305.71 | 0.385439E+09 |
October | 0.994195E+09 | 0.563432E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818503E+09 |
November | 0.984487E+09 | 0.607893E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104779E+10 |
December | 0.959235E+09 | 0.606526E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201633E+10 |
Annual Sum or Average | 0.119305E+11 | 0.665415E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58100903.20 | 0.120257E+11 |
Minimum of Months | 0.901968E+09 | 0.498254E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222291E+09 |
Maximum of Months | 0.107774E+10 | 0.607893E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25845702.91 | 0.202651E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.388563E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125476E+10 |
February | 0.570983E+09 | 0.334122E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133982E+10 |
March | 0.682256E+09 | 0.373968E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 296944.81 | 0.841752E+09 |
April | 0.605404E+09 | 0.322922E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689568E+09 |
May | 0.655811E+09 | 0.339742E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 134622.12 | 0.435256E+09 |
June | 0.653980E+09 | 0.333314E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6790450.39 | 0.255684E+09 |
July | 0.607235E+09 | 0.314075E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17160296.64 | 0.155453E+09 |
August | 0.682256E+09 | 0.354205E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13362346.56 | 0.176907E+09 |
September | 0.605404E+09 | 0.330608E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 904000.85 | 0.252534E+09 |
October | 0.629366E+09 | 0.361458E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518937E+09 |
November | 0.623221E+09 | 0.390421E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672999E+09 |
December | 0.607235E+09 | 0.390550E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132126E+10 |
Annual Sum or Average | 0.755252E+10 | 0.423395E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38648661.36 | 0.791494E+10 |
Minimum of Months | 0.570983E+09 | 0.314075E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155453E+09 |
Maximum of Months | 0.682256E+09 | 0.390550E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17160296.64 | 0.133982E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.624726E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104211E+10 |
February | 0.901968E+09 | 0.531842E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110337E+10 |
March | 0.107774E+10 | 0.591970E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 460227.52 | 0.676841E+09 |
April | 0.956342E+09 | 0.509252E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541223E+09 |
May | 0.103597E+10 | 0.535244E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 485501.80 | 0.317870E+09 |
June | 0.103308E+10 | 0.525872E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8014330.34 | 0.188188E+09 |
July | 0.959235E+09 | 0.494846E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16134516.63 | 0.108439E+09 |
August | 0.107774E+10 | 0.558552E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13408633.38 | 0.131539E+09 |
September | 0.956342E+09 | 0.521220E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 888247.90 | 0.203714E+09 |
October | 0.994195E+09 | 0.572539E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454565E+09 |
November | 0.984487E+09 | 0.626993E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598786E+09 |
December | 0.959235E+09 | 0.627016E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112368E+10 |
Annual Sum or Average | 0.119305E+11 | 0.672007E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39391457.59 | 0.649033E+10 |
Minimum of Months | 0.901968E+09 | 0.494846E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108439E+09 |
Maximum of Months | 0.107774E+10 | 0.627016E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16134516.63 | 0.112368E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.388999E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697962E+09 |
February | 0.571020E+09 | 0.334645E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738291E+09 |
March | 0.682301E+09 | 0.373519E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 171010.55 | 0.461026E+09 |
April | 0.605444E+09 | 0.322751E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379905E+09 |
May | 0.655854E+09 | 0.340701E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 177346.49 | 0.230661E+09 |
June | 0.654023E+09 | 0.334831E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3984526.27 | 0.134734E+09 |
July | 0.607275E+09 | 0.314811E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9656315.59 | 79679384.24 |
August | 0.682301E+09 | 0.355124E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7603502.43 | 94782811.59 |
September | 0.605444E+09 | 0.329332E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 554210.25 | 0.143635E+09 |
October | 0.629407E+09 | 0.358506E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317219E+09 |
November | 0.623262E+09 | 0.390373E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406386E+09 |
December | 0.607275E+09 | 0.389530E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750464E+09 |
Annual Sum or Average | 0.755301E+10 | 0.423312E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22146911.58 | 0.443475E+10 |
Minimum of Months | 0.571020E+09 | 0.314811E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79679384.24 |
Maximum of Months | 0.682301E+09 | 0.390373E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9656315.59 | 0.750464E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.603081E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.724431E+10 |
February | 0.901968E+09 | 0.523148E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673492E+10 |
March | 0.107774E+10 | 0.587957E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7765289.85 | 0.560649E+10 |
April | 0.956342E+09 | 0.510175E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384456E+10 |
May | 0.103597E+10 | 0.538371E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2377858.10 | 0.244850E+10 |
June | 0.103308E+10 | 0.528795E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129055E+09 | 0.131030E+10 |
July | 0.959235E+09 | 0.497784E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358800E+09 | 0.547962E+09 |
August | 0.107774E+10 | 0.560765E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277968E+09 | 0.929064E+09 |
September | 0.956342E+09 | 0.520047E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13754589.80 | 0.159390E+10 |
October | 0.994195E+09 | 0.562656E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349653E+10 |
November | 0.984487E+09 | 0.606890E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454345E+10 |
December | 0.959235E+09 | 0.605003E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671773E+10 |
Annual Sum or Average | 0.119305E+11 | 0.664467E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789720E+09 | 0.450177E+11 |
Minimum of Months | 0.901968E+09 | 0.497784E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547962E+09 |
Maximum of Months | 0.107774E+10 | 0.606890E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358800E+09 | 0.724431E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.387499E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695878E+09 |
February | 0.570983E+09 | 0.333511E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738971E+09 |
March | 0.682256E+09 | 0.373526E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 222548.46 | 0.467783E+09 |
April | 0.605404E+09 | 0.322451E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380974E+09 |
May | 0.655811E+09 | 0.339380E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74646.56 | 0.234847E+09 |
June | 0.653980E+09 | 0.333069E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3857248.09 | 0.139609E+09 |
July | 0.607235E+09 | 0.313812E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9718843.70 | 84284831.24 |
August | 0.682256E+09 | 0.353865E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7502301.16 | 99003476.10 |
September | 0.605404E+09 | 0.330087E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 500021.23 | 0.145397E+09 |
October | 0.629366E+09 | 0.360659E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313799E+09 |
November | 0.623221E+09 | 0.389464E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404342E+09 |
December | 0.607235E+09 | 0.389309E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749870E+09 |
Annual Sum or Average | 0.755252E+10 | 0.422663E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21875609.21 | 0.445476E+10 |
Minimum of Months | 0.570983E+09 | 0.313812E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84284831.24 |
Maximum of Months | 0.682256E+09 | 0.389464E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9718843.70 | 0.749870E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.627372E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160829E+10 |
February | 0.901968E+09 | 0.533190E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170953E+10 |
March | 0.107774E+10 | 0.593040E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 387710.38 | 0.107326E+10 |
April | 0.956342E+09 | 0.509656E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.881039E+09 |
May | 0.103597E+10 | 0.535803E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 343602.56 | 0.537631E+09 |
June | 0.103308E+10 | 0.526102E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9445997.21 | 0.311180E+09 |
July | 0.959235E+09 | 0.495177E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22715338.65 | 0.183459E+09 |
August | 0.107774E+10 | 0.559150E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18183098.17 | 0.212454E+09 |
September | 0.956342E+09 | 0.522146E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1322556.58 | 0.318434E+09 |
October | 0.994195E+09 | 0.574045E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689788E+09 |
November | 0.984487E+09 | 0.629331E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.907219E+09 |
December | 0.959235E+09 | 0.629721E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171289E+10 |
Annual Sum or Average | 0.119305E+11 | 0.673473E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52398303.56 | 0.101452E+11 |
Minimum of Months | 0.901968E+09 | 0.495177E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183459E+09 |
Maximum of Months | 0.107774E+10 | 0.629721E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22715338.65 | 0.171289E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.390161E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107314E+10 |
February | 0.421807E+09 | 0.335322E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114089E+10 |
March | 0.502994E+09 | 0.373985E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 201636.84 | 0.728051E+09 |
April | 0.447140E+09 | 0.323021E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602657E+09 |
May | 0.484071E+09 | 0.341026E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 125850.79 | 0.373324E+09 |
June | 0.482240E+09 | 0.335028E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5677053.21 | 0.215450E+09 |
July | 0.448971E+09 | 0.315043E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14031214.98 | 0.127803E+09 |
August | 0.502994E+09 | 0.355401E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10972331.50 | 0.147683E+09 |
September | 0.447140E+09 | 0.329793E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 770488.98 | 0.220298E+09 |
October | 0.465148E+09 | 0.359053E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474937E+09 |
November | 0.460569E+09 | 0.391200E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611592E+09 |
December | 0.448971E+09 | 0.390464E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114101E+10 |
Annual Sum or Average | 0.557719E+10 | 0.423950E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31778576.29 | 0.685684E+10 |
Minimum of Months | 0.421807E+09 | 0.315043E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127803E+09 |
Maximum of Months | 0.502994E+09 | 0.391200E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14031214.98 | 0.114101E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.604447E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164955E+10 |
February | 0.901968E+09 | 0.523778E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173852E+10 |
March | 0.107774E+10 | 0.588651E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 374437.26 | 0.113198E+10 |
April | 0.956342E+09 | 0.510704E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913956E+09 |
May | 0.103597E+10 | 0.539103E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 171932.95 | 0.555512E+09 |
June | 0.103308E+10 | 0.529231E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9029599.20 | 0.316556E+09 |
July | 0.959235E+09 | 0.498253E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21939366.03 | 0.189359E+09 |
August | 0.107774E+10 | 0.561323E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16647471.51 | 0.222542E+09 |
September | 0.956342E+09 | 0.520806E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1177444.39 | 0.336965E+09 |
October | 0.994195E+09 | 0.563431E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736935E+09 |
November | 0.984487E+09 | 0.607892E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.944968E+09 |
December | 0.959235E+09 | 0.606525E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175342E+10 |
Annual Sum or Average | 0.119305E+11 | 0.665414E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49340251.35 | 0.104903E+11 |
Minimum of Months | 0.901968E+09 | 0.498253E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189359E+09 |
Maximum of Months | 0.107774E+10 | 0.607892E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21939366.03 | 0.175342E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.388562E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107326E+10 |
February | 0.570983E+09 | 0.334121E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114307E+10 |
March | 0.682256E+09 | 0.373968E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 254187.55 | 0.737595E+09 |
April | 0.605404E+09 | 0.322922E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608151E+09 |
May | 0.655811E+09 | 0.339742E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114455.00 | 0.377250E+09 |
June | 0.653980E+09 | 0.333314E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5741202.11 | 0.219523E+09 |
July | 0.607235E+09 | 0.314075E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14582338.17 | 0.132727E+09 |
August | 0.682256E+09 | 0.354204E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11303317.94 | 0.152201E+09 |
September | 0.605404E+09 | 0.330607E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 764715.79 | 0.221645E+09 |
October | 0.629366E+09 | 0.361457E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470232E+09 |
November | 0.623221E+09 | 0.390419E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607859E+09 |
December | 0.607235E+09 | 0.390548E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114223E+10 |
Annual Sum or Average | 0.755252E+10 | 0.423394E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32760216.55 | 0.688575E+10 |
Minimum of Months | 0.570983E+09 | 0.314075E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132727E+09 |
Maximum of Months | 0.682256E+09 | 0.390548E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14582338.17 | 0.114307E+10 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221698E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234483E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 559027.12 | 0.150558E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123296E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434191.43 | 0.731385E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9532582.48 | 0.421709E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24227931.52 | 0.245007E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19970896.03 | 0.291813E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1039970.08 | 0.448133E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.991965E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130795E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239253E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55764598.67 | 0.141308E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245007E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24227931.52 | 0.239253E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272603E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288258E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 824687.68 | 0.185616E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153103E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 608598.02 | 0.927289E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12002488.80 | 0.539972E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30529096.14 | 0.314868E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25882401.79 | 0.370859E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1377600.99 | 0.558758E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119396E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155760E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291036E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71224873.41 | 0.173695E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314868E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30529096.14 | 0.291036E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277606E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295768E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37940.41 | 0.188572E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156434E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29531.11 | 0.991297E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7480685.56 | 0.586960E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22914151.60 | 0.350676E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15631893.85 | 0.394193E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 701473.48 | 0.579303E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118715E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152653E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293692E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46795676.01 | 0.177368E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350676E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22914151.60 | 0.295768E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3589.18 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 910.43 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3586.01 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 743.99 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.47 | 15-MAR-14:00 | 2009.45 | 01-MAR-22:02 |
April | 1306.65 | 03-APR-09:09 | 580.87 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1820.27 | 04-APR-21:03 |
May | 1306.65 | 01-MAY-09:09 | 550.23 | 11-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.35 | 14-MAY-15:00 | 1177.45 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.25 | 17-JUN-17:03 | 1036.85 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 542.18 | 11-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.94 | 15-JUL-15:00 | 744.36 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 549.56 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 358.06 | 13-AUG-12:53 | 492.95 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 714.78 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.38 | 16-SEP-13:00 | 827.03 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1004.69 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1000.58 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1783.18 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3373.18 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.95 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 358.06 | 3589.18 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2392.92 | 12-JAN-06:00 |
February | 827.22 | 01-FEB-10:09 | 581.37 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2503.13 | 13-FEB-06:00 |
March | 827.22 | 01-MAR-10:09 | 368.11 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 15-MAR-14:00 | 1340.48 | 01-MAR-22:02 |
April | 827.22 | 03-APR-09:09 | 355.46 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1212.70 | 04-APR-21:03 |
May | 827.22 | 01-MAY-09:09 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.58 | 10-MAY-14:00 | 860.00 | 29-MAY-14:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.03 | 17-JUN-17:03 | 693.61 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 314.23 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.63 | 15-JUL-15:00 | 494.52 | 06-JUL-02:00 |
August | 827.22 | 01-AUG-09:09 | 344.14 | 28-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.74 | 13-AUG-12:53 | 327.98 | 30-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 365.33 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.92 | 16-SEP-13:00 | 547.20 | 29-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 532.36 | 26-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 699.61 | 08-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1183.14 | 17-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2242.78 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.98 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 224.74 | 2503.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3589.40 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 890.11 | 01-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3754.71 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 721.84 | 17-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.47 | 15-MAR-14:00 | 2149.11 | 26-MAR-13:00 |
April | 1306.65 | 03-APR-09:09 | 579.98 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1820.17 | 04-APR-21:03 |
May | 1306.65 | 01-MAY-09:09 | 552.96 | 11-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 | 10-MAY-14:00 | 1286.19 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.85 | 17-JUN-17:03 | 1044.85 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 545.33 | 11-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.94 | 15-JUL-15:00 | 747.65 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 551.45 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 322.39 | 13-AUG-13:15 | 496.21 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 698.07 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.38 | 16-SEP-13:00 | 831.88 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 884.71 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1052.21 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1811.85 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3399.55 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496.21 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 322.39 | 3754.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2392.92 | 12-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 573.49 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2503.13 | 13-FEB-06:00 |
March | 827.17 | 01-MAR-10:09 | 496.26 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 15-MAR-14:00 | 1506.80 | 25-MAR-17:05 |
April | 827.17 | 03-APR-09:09 | 430.24 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1212.14 | 04-APR-21:03 |
May | 827.17 | 01-MAY-09:09 | 357.18 | 11-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.58 | 10-MAY-14:00 | 915.18 | 29-MAY-15:20 |
June | 827.17 | 01-JUN-09:09 | 342.04 | 21-JUN-08:09 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.15 | 12-JUN-13:00 | 697.53 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 353.27 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.63 | 15-JUL-15:00 | 503.48 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 359.39 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.63 | 13-AUG-12:53 | 391.10 | 27-AUG-16:30 |
September | 827.17 | 01-SEP-09:09 | 477.89 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.92 | 16-SEP-13:00 | 545.71 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 635.98 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 668.65 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1180.55 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2247.05 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 342.04 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.10 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 227.63 | 2503.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1904.55 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 905.40 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1992.56 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 732.29 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.88 | 14-MAR-14:00 | 1112.15 | 02-MAR-01:00 |
April | 1306.65 | 03-APR-09:09 | 578.00 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1074.49 | 16-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 545.89 | 11-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.88 | 14-MAY-14:53 | 573.17 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.86 | 17-JUN-17:03 | 571.09 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 537.48 | 11-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.71 | 21-JUL-03:00 | 415.77 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 545.18 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.33 | 13-AUG-13:00 | 273.22 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 702.09 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.35 | 16-SEP-17:03 | 509.83 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1002.77 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 645.88 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1087.13 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1886.88 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.22 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 223.33 | 1992.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1269.86 | 12-JAN-05:43 |
February | 827.22 | 01-FEB-10:09 | 578.98 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1330.54 | 13-FEB-05:54 |
March | 827.22 | 01-MAR-10:09 | 366.33 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.07 | 15-MAR-14:00 | 764.60 | 02-MAR-01:00 |
April | 827.22 | 03-APR-09:09 | 353.15 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 721.32 | 16-APR-07:00 |
May | 827.22 | 01-MAY-09:09 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.52 | 14-MAY-14:53 | 430.80 | 29-MAY-14:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.43 | 17-JUN-17:03 | 396.73 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 314.23 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.11 | 21-JUL-03:00 | 285.95 | 06-JUL-02:00 |
August | 827.22 | 01-AUG-09:09 | 341.54 | 28-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.62 | 13-AUG-12:53 | 183.06 | 30-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 363.44 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.11 | 16-SEP-13:00 | 339.66 | 29-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 528.00 | 26-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 447.91 | 08-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 733.31 | 17-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1256.10 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.06 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 132.62 | 1330.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 29113.20 | 04-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 884.06 | 01-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 32232.49 | 07-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 709.06 | 17-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 800.35 | 15-MAR-12:00 | 29845.08 | 07-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 577.06 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 20965.20 | 17-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 548.78 | 11-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.82 | 10-MAY-16:10 | 14775.99 | 01-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4684.85 | 27-JUN-12:00 | 11362.63 | 14-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 540.82 | 11-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4505.71 | 19-JUL-16:10 | 8177.73 | 03-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 547.18 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4372.28 | 10-AUG-12:00 | 9122.44 | 01-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 684.59 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1673.96 | 15-SEP-12:00 | 13565.52 | 05-SEP-06:01 |
October | 1306.65 | 02-OCT-09:09 | 877.23 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 19727.15 | 17-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 19904.77 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 32494.24 | 11-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8177.73 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 4684.85 | 32494.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1270.19 | 12-JAN-05:43 |
February | 827.17 | 01-FEB-10:09 | 570.87 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1329.84 | 13-FEB-05:54 |
March | 827.17 | 01-MAR-10:09 | 491.28 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.07 | 15-MAR-14:00 | 781.00 | 25-MAR-17:10 |
April | 827.17 | 03-APR-09:09 | 423.29 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 713.57 | 16-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 355.12 | 11-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.49 | 10-MAY-14:00 | 455.70 | 06-MAY-17:10 |
June | 827.17 | 01-JUN-09:09 | 339.98 | 21-JUN-08:09 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.46 | 12-JUN-13:00 | 401.04 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 351.09 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.54 | 21-JUL-03:00 | 292.94 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 357.44 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.89 | 13-AUG-12:53 | 184.24 | 27-AUG-18:40 |
September | 827.17 | 01-SEP-09:09 | 472.37 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.11 | 16-SEP-13:00 | 339.25 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 634.93 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 436.54 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 734.28 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1257.25 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 339.98 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.24 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 129.89 | 1329.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2984.82 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 910.42 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3118.63 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 743.97 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.68 | 15-MAR-14:00 | 1747.84 | 02-MAR-01:00 |
April | 1306.65 | 03-APR-09:09 | 580.87 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1643.88 | 16-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 550.22 | 11-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.44 | 14-MAY-15:00 | 993.28 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.48 | 17-JUN-17:03 | 901.17 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 542.17 | 11-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.69 | 15-JUL-15:00 | 654.15 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 549.55 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.17 | 13-AUG-12:53 | 424.47 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 714.75 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.93 | 16-SEP-17:03 | 762.55 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1004.69 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 950.91 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1631.83 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2902.61 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.47 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 293.17 | 3118.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 658.76 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1989.88 | 12-JAN-06:00 |
February | 805.43 | 01-FEB-08:09 | 581.36 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2081.68 | 13-FEB-06:00 |
March | 805.43 | 01-MAR-08:09 | 368.10 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.55 | 15-MAR-14:10 | 1176.95 | 02-MAR-01:00 |
April | 805.43 | 03-APR-07:10 | 355.45 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1101.68 | 16-APR-07:00 |
May | 805.43 | 01-MAY-07:10 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.72 | 14-MAY-15:00 | 723.60 | 29-MAY-14:00 |
June | 805.43 | 01-JUN-07:10 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.58 | 17-JUN-17:03 | 603.27 | 13-JUN-03:00 |
July | 805.43 | 03-JUL-07:10 | 314.23 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.79 | 15-JUL-15:00 | 435.24 | 06-JUL-02:00 |
August | 805.43 | 01-AUG-07:10 | 344.14 | 28-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.34 | 13-AUG-13:06 | 282.95 | 30-AUG-21:10 |
September | 805.43 | 01-SEP-07:10 | 365.32 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.34 | 16-SEP-13:00 | 504.98 | 29-SEP-04:00 |
October | 805.43 | 02-OCT-07:10 | 532.35 | 26-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 661.41 | 08-OCT-09:00 |
November | 805.43 | 01-NOV-07:10 | 658.76 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1084.39 | 17-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 658.76 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1927.80 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.95 | |||||
Maximum of Months | 805.43 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 193.34 | 2081.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2984.83 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 890.10 | 01-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3122.54 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 721.81 | 17-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 15-MAR-14:00 | 1912.82 | 26-MAR-13:00 |
April | 1306.65 | 03-APR-09:09 | 579.98 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1649.10 | 16-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 552.95 | 11-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.70 | 10-MAY-14:00 | 1085.12 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.03 | 17-JUN-17:03 | 907.87 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 545.32 | 11-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.69 | 15-JUL-15:00 | 656.94 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 551.44 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.96 | 13-AUG-13:04 | 426.67 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 698.04 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.51 | 16-SEP-13:00 | 765.72 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 884.71 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 993.02 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1656.85 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2926.77 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.67 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 284.96 | 3122.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1989.88 | 12-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 573.48 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2081.68 | 13-FEB-06:00 |
March | 827.17 | 01-MAR-10:09 | 496.25 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.12 | 15-MAR-14:00 | 1280.24 | 25-MAR-17:10 |
April | 827.17 | 03-APR-09:09 | 430.22 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1086.27 | 16-APR-02:00 |
May | 827.17 | 01-MAY-09:09 | 357.18 | 11-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.13 | 10-MAY-14:00 | 761.10 | 29-MAY-15:10 |
June | 827.17 | 01-JUN-09:09 | 342.03 | 21-JUN-08:09 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.08 | 12-JUN-13:00 | 606.33 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 353.27 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.79 | 15-JUL-15:00 | 442.21 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 359.39 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.57 | 13-AUG-13:06 | 314.36 | 27-AUG-16:30 |
September | 827.17 | 01-SEP-09:09 | 477.87 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.34 | 16-SEP-13:00 | 503.50 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 635.98 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 634.88 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1081.22 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1934.16 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 342.03 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.36 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 187.57 | 2081.68 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3990.64 | 12-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3900.74 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.87 | 15-MAR-14:00 | 2591.18 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2428.83 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.42 | 14-MAY-14:55 | 1213.49 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.49 | 17-JUN-17:03 | 1244.07 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.24 | 21-JUL-03:00 | 905.56 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.83 | 13-AUG-13:00 | 579.16 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.82 | 16-SEP-13:00 | 1102.78 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1374.04 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2409.27 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4056.01 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.16 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.83 | 4056.01 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4931.04 | 12-JAN-02:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4746.21 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.90 | 14-MAR-14:00 | 3206.04 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2951.78 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.15 | 14-MAY-14:53 | 1514.08 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.31 | 17-JUN-17:03 | 1592.83 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.42 | 21-JUL-03:00 | 1149.27 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 564.58 | 13-AUG-12:53 | 742.66 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.27 | 16-SEP-13:00 | 1353.86 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1637.58 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2930.45 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5040.12 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 742.66 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 564.58 | 5040.12 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4906.79 | 12-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4949.81 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.11 | 15-MAR-14:00 | 3016.04 | 25-MAR-17:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2752.55 | 16-APR-07:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.32 | 10-MAY-15:00 | 2017.61 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.52 | 17-JUN-17:03 | 1589.54 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.45 | 21-JUL-02:00 | 1123.48 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.23 | 13-AUG-13:00 | 769.52 | 30-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.61 | 16-SEP-13:00 | 1262.45 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1515.27 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2740.61 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5398.04 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 769.52 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.45 | 5398.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8846.40 | 20-JAN-17:00 | 6035.01 | 4936.01 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9366.43 | 17-FEB-17:00 | 6035.01 | 4936.01 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17794.46 | 17-MAR-08:00 | 6035.01 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17848.58 | 25-APR-08:00 | 6035.01 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32895.79 | 31-MAY-06:03 | 5082.11 | 6581.44 | 35187.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41233.34 | 19-JUN-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41744.87 | 05-JUL-05:12 | 3176.32 | 2742.16 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 41538.11 | 21-AUG-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 42532.87 | 18-SEP-05:12 | 3176.32 | 2742.16 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 34025.29 | 13-OCT-06:02 | 7623.17 | 9872.16 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17452.49 | 07-NOV-08:02 | 48280.06 | 39488.12 | 145481.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13775.17 | 01-DEC-08:15 | 12070.02 | 9872.03 | 36370.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 8846.40 | 2541.06 | 2193.73 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42532.87 | 48280.06 | 39488.12 | 145481.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 953.85 |
February | 35.18 | 22-FEB-17:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.24 |
March | 5305.60 | 15-MAR-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 | 0.00 |
April | 4489.32 | 21-APR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.70 |
May | 6949.03 | 26-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.92 |
June | 10068.40 | 12-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.69 | 0.00 |
July | 10021.37 | 21-JUL-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.64 | 0.00 |
August | 9957.72 | 09-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.36 | 0.00 |
September | 7827.63 | 21-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 | 0.00 |
October | 4263.51 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.33 |
November | 649.65 | 04-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.96 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1140.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10068.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.69 | 1140.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2618.03 | 04-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1063.79 |
February | 2423.45 | 09-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1474.50 |
March | 2118.47 | 07-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1139.89 |
April | 1482.00 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.30 |
May | 2260.37 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.31 |
June | 4560.49 | 12-JUN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.58 | 0.00 |
July | 6384.33 | 17-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.31 |
August | 4603.27 | 14-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.63 | 0.00 |
September | 3242.28 | 18-SEP-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.12 |
October | 1147.95 | 24-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.36 |
November | 1425.58 | 18-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.00 |
December | 2378.14 | 28-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1857.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1147.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6384.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.58 | 1857.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2163.52 | 04-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 835.20 |
February | 1963.95 | 09-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1177.85 |
March | 2814.23 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.77 |
April | 2259.74 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.47 |
May | 2525.30 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.75 |
June | 4604.14 | 12-JUN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.01 | 0.00 |
July | 6696.61 | 17-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.22 |
August | 5005.99 | 14-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.91 | 0.00 |
September | 4010.76 | 18-SEP-12:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.93 |
October | 2188.56 | 17-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.87 |
November | 1737.25 | 03-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.91 |
December | 1706.15 | 15-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1706.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6696.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.01 | 1177.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5229.45 | 12-JAN-17:00 | 12070.02 | 9872.03 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5380.35 | 17-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11517.43 | 16-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10772.90 | 21-APR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13812.90 | 31-MAY-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30543.20 | 19-JUN-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33284.64 | 17-JUL-05:14 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33404.51 | 14-AUG-05:14 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30592.95 | 18-SEP-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12256.72 | 12-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8093.23 | 01-NOV-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5676.33 | 01-DEC-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5229.45 | 2541.06 | 2193.73 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33404.51 | 12070.02 | 9872.03 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 4755.63 | 12-JAN-16:40 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4993.42 | 28-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11691.88 | 16-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11540.63 | 21-APR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15342.60 | 31-MAY-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31068.30 | 26-JUN-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35234.68 | 17-JUL-05:14 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31655.12 | 07-AUG-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16532.60 | 18-SEP-13:10 | 12396.58 | 9872.03 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11986.18 | 12-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6324.06 | 01-NOV-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5157.78 | 01-DEC-16:30 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 4755.63 | 2541.06 | 2193.73 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35234.68 | 12396.58 | 9872.03 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 796.36 | 14-JAN-17:03 | 200.88 | 173.42 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.36 |
February | 805.31 | 18-FEB-17:03 | 200.88 | 122.25 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.48 |
March | 3654.88 | 15-MAR-14:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 20.19 | 0.00 |
April | 2463.08 | 21-APR-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.10 |
May | 4709.01 | 23-MAY-14:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 |
June | 7068.36 | 12-JUN-06:03 | 803.52 | 496.35 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.49 |
July | 11092.22 | 16-JUL-12:53 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 17.16 | 0.00 |
August | 8222.16 | 13-AUG-16:33 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 81.66 | 0.00 |
September | 4715.13 | 15-SEP-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.72 | 0.00 |
October | 2485.38 | 12-OCT-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.00 |
November | 1177.45 | 16-NOV-16:50 | 1272.23 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.05 |
December | 901.80 | 01-DEC-13:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 796.36 | 200.88 | 110.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11092.22 | 1306.65 | 1040.56 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 81.66 | 312.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 503.85 | 14-JAN-17:03 | 127.17 | 109.79 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.57 |
February | 735.53 | 28-FEB-10:10 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.08 |
March | 2852.89 | 15-MAR-14:00 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 0.00 |
April | 5328.29 | 24-APR-09:10 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.26 |
May | 7554.77 | 31-MAY-08:50 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.55 |
June | 10627.82 | 18-JUN-10:32 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.10 |
July | 13683.40 | 04-JUL-09:02 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.45 |
August | 8912.75 | 06-AUG-13:23 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 4.75 | 0.00 |
September | 9783.46 | 04-SEP-09:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.63 |
October | 4128.15 | 11-OCT-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.09 |
November | 852.57 | 03-NOV-09:50 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.21 |
December | 577.17 | 01-DEC-13:30 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 503.85 | 127.17 | 69.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13683.40 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 201.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3461.70 | 12-JAN-13:40 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 906.37 |
February | 5940.78 | 28-FEB-13:50 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.13 |
March | 10078.53 | 15-MAR-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 23.93 | 0.00 |
April | 8173.81 | 21-APR-13:10 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.17 |
May | 11240.46 | 14-MAY-14:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.06 |
June | 12769.59 | 25-JUN-14:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.44 |
July | 16504.81 | 16-JUL-12:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 34.48 | 0.00 |
August | 16701.41 | 13-AUG-12:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 234.07 | 0.00 |
September | 17656.03 | 10-SEP-13:02 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.31 |
October | 12099.90 | 11-OCT-12:30 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.71 |
November | 7522.95 | 03-NOV-12:40 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.78 |
December | 3712.56 | 16-DEC-13:30 | 133.92 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3461.70 | 133.92 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17656.03 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 234.07 | 906.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 656.38 | 06-JAN-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.43 |
February | 1716.10 | 28-FEB-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.47 |
March | 3781.04 | 15-MAR-14:20 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 | 0.00 |
April | 6423.33 | 24-APR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.44 |
May | 13207.77 | 27-MAY-17:05 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.65 |
June | 15234.57 | 11-JUN-16:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.97 |
July | 15679.10 | 02-JUL-17:12 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.22 |
August | 14893.44 | 06-AUG-16:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 21.06 | 0.00 |
September | 15527.16 | 04-SEP-16:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.80 |
October | 6103.90 | 11-OCT-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.39 |
November | 1630.33 | 03-NOV-15:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.70 |
December | 669.34 | 04-DEC-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 656.38 | 0.00 | 104.73 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15679.10 | 805.38 | 314.21 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 21.06 | 280.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 806.97 | 14-JAN-17:03 | 200.88 | 173.42 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.57 |
February | 809.10 | 18-FEB-17:03 | 200.88 | 119.75 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.91 |
March | 1376.07 | 15-MAR-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.92 | 0.00 |
April | 1255.17 | 21-APR-15:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.82 |
May | 2813.31 | 23-MAY-14:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 |
June | 4772.71 | 26-JUN-15:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 46.43 | 0.00 |
July | 5429.56 | 17-JUL-06:07 | 803.52 | 496.35 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 |
August | 6059.22 | 07-AUG-06:03 | 803.52 | 542.50 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.64 |
September | 4037.88 | 15-SEP-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.89 | 0.00 |
October | 2246.73 | 05-OCT-14:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.00 |
November | 1194.74 | 01-NOV-13:10 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.62 |
December | 1006.89 | 01-DEC-13:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 806.97 | 200.88 | 119.75 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6059.22 | 1306.65 | 542.50 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 46.43 | 167.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 552.50 | 14-JAN-07:05 | 339.13 | 292.77 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.28 |
February | 654.28 | 28-FEB-10:05 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.86 |
March | 1529.93 | 15-MAR-14:00 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 11.07 | 0.00 |
April | 3841.49 | 24-APR-09:20 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.29 |
May | 6025.56 | 31-MAY-06:03 | 678.26 | 418.98 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.50 |
June | 8505.41 | 23-JUN-06:02 | 847.82 | 523.72 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.58 |
July | 11138.25 | 16-JUL-09:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 35.25 | 0.00 |
August | 8528.54 | 02-AUG-06:02 | 1017.38 | 628.46 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7885.27 | 04-SEP-10:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.74 |
October | 3699.80 | 11-OCT-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.65 |
November | 1434.72 | 03-NOV-08:45 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.45 |
December | 644.46 | 01-DEC-13:30 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 552.50 | 169.56 | 69.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11138.25 | 1654.44 | 628.46 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 35.25 | 122.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1041.91 | 21-JAN-12:30 | 137.54 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.09 |
February | 1229.60 | 18-FEB-14:40 | 137.54 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.68 |
March | 6145.21 | 15-MAR-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 173.51 | 0.00 |
April | 3876.83 | 22-APR-13:40 | 137.54 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.02 |
May | 5332.11 | 16-MAY-12:10 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.75 |
June | 10713.72 | 27-JUN-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4684.85 | 0.00 |
July | 10986.45 | 21-JUL-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4437.51 | 0.00 |
August | 13243.76 | 13-AUG-12:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 138.07 | 0.00 |
September | 13294.70 | 04-SEP-12:02 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.34 |
October | 10089.22 | 11-OCT-12:30 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.05 |
November | 4942.21 | 01-NOV-12:08 | 7633.40 | 2978.07 | 8611.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1462.99 |
December | 2013.85 | 16-DEC-13:30 | 133.92 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1041.91 | 133.92 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13294.70 | 7633.40 | 2978.07 | 8611.42 | 0.00 | 0.00 | 0.00 | 0.00 | 4684.85 | 1462.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 658.57 | 12-JAN-16:10 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.71 |
February | 816.50 | 28-FEB-16:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.51 |
March | 1864.98 | 15-MAR-14:20 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 | 0.00 |
April | 3930.24 | 24-APR-17:30 | 84.78 | 104.74 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.87 |
May | 7899.83 | 07-MAY-18:03 | 0.00 | 69.82 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.74 |
June | 11710.12 | 25-JUN-18:22 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.69 |
July | 11807.49 | 02-JUL-17:52 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.79 |
August | 11140.20 | 06-AUG-16:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 20.99 | 0.00 |
September | 10469.92 | 10-SEP-17:12 | 0.00 | 69.82 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.49 |
October | 5115.85 | 11-OCT-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 |
November | 1520.21 | 03-NOV-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.91 |
December | 674.94 | 04-DEC-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 658.57 | 0.00 | 69.82 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11807.49 | 805.38 | 314.21 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 20.99 | 267.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 811.09 | 14-JAN-17:03 | 200.88 | 173.42 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.15 |
February | 868.65 | 17-FEB-15:10 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.45 |
March | 3222.23 | 15-MAR-14:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 17.06 | 0.00 |
April | 2351.01 | 21-APR-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.46 |
May | 4466.78 | 23-MAY-14:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
June | 7706.46 | 12-JUN-06:03 | 803.52 | 496.35 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.55 |
July | 7874.21 | 16-JUL-16:12 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 104.69 | 0.00 |
August | 9580.18 | 13-AUG-15:41 | 468.72 | 193.02 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 184.96 | 0.00 |
September | 4485.74 | 13-SEP-13:30 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.12 |
October | 2604.22 | 12-OCT-14:50 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.40 |
November | 1231.91 | 16-NOV-17:00 | 1272.23 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.95 |
December | 991.54 | 01-DEC-13:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 811.09 | 200.88 | 165.44 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9580.18 | 1306.65 | 1040.56 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 184.96 | 261.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 597.10 | 06-JAN-11:10 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.09 |
February | 806.27 | 28-FEB-10:00 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.24 |
March | 4254.12 | 16-MAR-12:02 | 3221.71 | 1256.91 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.00 |
April | 6821.66 | 24-APR-12:01 | 5638.00 | 2199.59 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.66 |
May | 7773.29 | 31-MAY-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.09 |
June | 12091.27 | 11-JUN-08:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.40 |
July | 13476.41 | 04-JUL-08:42 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.25 |
August | 13598.68 | 06-AUG-09:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.77 |
September | 11342.37 | 04-SEP-10:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.61 |
October | 5600.41 | 11-OCT-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.48 |
November | 4804.34 | 01-NOV-12:02 | 4832.57 | 1885.36 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.71 |
December | 661.91 | 01-DEC-13:10 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 597.10 | 169.56 | 69.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.09 | |
Maximum of Months | 13598.68 | 5638.00 | 2199.59 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4493.59 | 12-JAN-13:30 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.87 |
February | 6236.65 | 28-FEB-13:40 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.91 |
March | 9583.10 | 15-MAR-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 20.32 | 0.00 |
April | 8127.44 | 24-APR-13:10 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.73 |
May | 9000.98 | 14-MAY-14:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.77 |
June | 10021.52 | 25-JUN-15:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 15.37 | 0.00 |
July | 15963.84 | 30-JUL-12:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.23 |
August | 15632.30 | 06-AUG-12:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.12 |
September | 15477.36 | 04-SEP-12:02 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.07 |
October | 12090.11 | 11-OCT-12:30 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.30 |
November | 8514.76 | 03-NOV-12:25 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.32 |
December | 4323.95 | 16-DEC-13:30 | 133.92 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4323.95 | 133.92 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15963.84 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 20.32 | 775.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 706.93 | 12-JAN-16:10 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.86 |
February | 1789.63 | 28-FEB-16:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.46 |
March | 3479.35 | 15-MAR-14:20 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 14.11 | 0.00 |
April | 6392.95 | 24-APR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.95 |
May | 12174.67 | 27-MAY-17:05 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.44 |
June | 13878.30 | 11-JUN-16:52 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.34 |
July | 14495.05 | 02-JUL-17:12 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.19 |
August | 14468.87 | 13-AUG-15:41 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 54.65 | 0.00 |
September | 12376.11 | 04-SEP-15:23 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.39 |
October | 6063.41 | 11-OCT-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 |
November | 2090.69 | 03-NOV-15:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.53 |
December | 706.98 | 04-DEC-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 706.93 | 0.00 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14495.05 | 805.38 | 314.21 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 54.65 | 427.86 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.163599E+12 | 237424.75 | 02-JAN-07:10 | 0.829104E+11 | 114742.04 | 04-JAN-07:19 |
February | 0.142112E+12 | 226840.92 | 06-FEB-07:10 | 0.765961E+11 | 120826.41 | 06-FEB-08:20 |
March | 0.116469E+12 | 181155.98 | 06-MAR-07:10 | 0.525233E+11 | 106689.98 | 07-MAR-07:19 |
April | 0.908806E+11 | 142245.01 | 17-APR-06:10 | 0.244686E+11 | 70222.05 | 17-APR-06:30 |
May | 0.975493E+11 | 101525.91 | 23-MAY-14:30 | 0.124535E+11 | 39713.00 | 01-MAY-06:10 |
June | 0.120700E+12 | 148517.25 | 27-JUN-12:00 | 0.110825E+11 | 15238.51 | 14-JUN-06:19 |
July | 0.140349E+12 | 164708.94 | 17-JUL-07:10 | 0.106519E+11 | 9868.95 | 03-JUL-11:39 |
August | 0.138320E+12 | 159662.55 | 14-AUG-10:00 | 0.110592E+11 | 9811.90 | 29-AUG-11:09 |
September | 0.105476E+12 | 128903.31 | 15-SEP-10:00 | 0.106553E+11 | 21035.08 | 30-SEP-06:49 |
October | 0.945981E+11 | 121761.97 | 30-OCT-06:10 | 0.186763E+11 | 61776.88 | 17-OCT-06:19 |
November | 0.102987E+12 | 159091.58 | 24-NOV-07:10 | 0.337582E+11 | 66085.62 | 24-NOV-07:49 |
December | 0.149995E+12 | 225028.57 | 11-DEC-07:10 | 0.736306E+11 | 118996.32 | 11-DEC-08:30 |
Annual Sum or Average | 0.146303E+13 | 0.418466E+12 | ||||
Minimum of Months | 0.908806E+11 | 101525.91 | 0.106519E+11 | 9811.90 | ||
Maximum of Months | 0.163599E+12 | 237424.75 | 0.829104E+11 | 120826.41 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.199380E+11 | 0.597089E+10 | 0.593559E+11 | 0.982899E+09 | 0.427819E+10 | 12379742.02 | 0.730603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177968E+11 | 0.474836E+10 | 0.537310E+11 | 0.889285E+09 | 0.384025E+10 | 11196021.66 | 0.610950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208020E+11 | 0.441831E+10 | 0.617796E+11 | 0.102905E+10 | 0.406607E+10 | 12675672.10 | 0.229893E+11 | 0.137153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183905E+11 | 0.352418E+10 | 0.572952E+11 | 0.946204E+09 | 0.401366E+10 | 11960507.72 | 0.579756E+10 | 0.901404E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197292E+11 | 0.304929E+10 | 0.605677E+11 | 0.100555E+10 | 0.647200E+10 | 12527707.06 | 0.794762E+09 | 0.591825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.195711E+11 | 0.273786E+10 | 0.594895E+11 | 0.989872E+09 | 0.118665E+11 | 12231776.97 | 0.156354E+09 | 0.258762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.183225E+11 | 0.290320E+10 | 0.583622E+11 | 0.961664E+09 | 0.151515E+11 | 12256437.81 | 9058281.49 | 0.446269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.205041E+11 | 0.337878E+10 | 0.617796E+11 | 0.102890E+10 | 0.145825E+11 | 12675672.10 | 30068984.90 | 0.370039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.185006E+11 | 0.391430E+10 | 0.572729E+11 | 0.946030E+09 | 0.877685E+10 | 11960507.72 | 0.225458E+09 | 0.158279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194830E+11 | 0.488938E+10 | 0.593671E+11 | 0.982626E+09 | 0.444859E+10 | 12379742.02 | 0.322416E+10 | 0.219092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.198061E+11 | 0.553154E+10 | 0.580818E+11 | 0.964827E+09 | 0.344826E+10 | 12059151.09 | 0.147854E+11 | 0.357081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195017E+11 | 0.618583E+10 | 0.583511E+11 | 0.962485E+09 | 0.396855E+10 | 12256437.81 | 0.610133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232346E+12 | 0.512519E+11 | 0.705434E+12 | 0.116894E+11 | 0.849129E+11 | 0.146559E+09 | 0.243181E+12 | 0.134074E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.177968E+11 | 0.273786E+10 | 0.537310E+11 | 0.889285E+09 | 0.344826E+10 | 11196021.66 | 9058281.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.208020E+11 | 0.618583E+10 | 0.617796E+11 | 0.102905E+10 | 0.151515E+11 | 12675672.10 | 0.730603E+11 | 0.446269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.708938E+11 | 0.00 | 0.120166E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.656366E+11 | 0.00 | 0.109595E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.400799E+11 | 0.00 | 0.124434E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.131163E+11 | 0.00 | 0.113524E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.856271E+09 | 0.00 | 0.115972E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 65636897.23 | 0.00 | 0.110169E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.106519E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.110592E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.214467E+09 | 0.00 | 0.104409E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.764077E+10 | 0.00 | 0.110356E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.226501E+11 | 0.00 | 0.111080E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.620386E+11 | 0.00 | 0.115920E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.283192E+12 | 0.00 | 0.135273E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.104409E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.708938E+11 | 0.00 | 0.124434E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 25003.79 | 02-JAN-16:49 | 5686.19 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 838.79 | 02-JAN-16:00 | 6972.42 | 02-JAN-06:19 | 6.85 | 03-JAN-07:19 | 195174.36 | 02-JAN-06:19 |
February | 23594.14 | 01-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 838.20 | 01-FEB-08:20 | 6265.29 | 06-FEB-07:10 | 6.85 | 02-FEB-06:10 | 185205.38 | 06-FEB-07:10 |
March | 21767.34 | 17-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 835.85 | 17-MAR-07:19 | 7944.88 | 15-MAR-13:50 | 6.85 | 04-MAR-06:10 | 148124.34 | 06-MAR-07:10 |
April | 20632.63 | 12-APR-07:10 | 5686.19 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 834.34 | 12-APR-07:19 | 7849.99 | 21-APR-15:20 | 6.85 | 11-APR-07:10 | 110652.43 | 17-APR-06:10 |
May | 20121.25 | 11-MAY-07:10 | 5686.19 | 01-MAY-05:10 | 45864.70 | 01-MAY-07:10 | 833.67 | 11-MAY-07:19 | 13916.88 | 23-MAY-14:30 | 6.85 | 27-MAY-16:10 | 21884.16 | 01-MAY-06:10 |
June | 19752.85 | 21-JUN-08:09 | 3328.83 | 01-JUN-19:49 | 45864.70 | 01-JUN-07:10 | 833.16 | 19-JUN-07:19 | 26073.45 | 12-JUN-15:20 | 6.85 | 10-JUN-16:10 | 10515.42 | 14-JUN-06:10 |
July | 20057.74 | 11-JUL-07:30 | 3328.83 | 01-JUL-19:00 | 45864.70 | 03-JUL-07:10 | 833.58 | 11-JUL-07:40 | 28035.94 | 17-JUL-07:10 | 6.85 | 02-JUL-15:50 | 1382.35 | 13-JUL-06:10 |
August | 20121.30 | 24-AUG-07:10 | 5686.19 | 02-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 833.67 | 24-AUG-07:19 | 27333.60 | 14-AUG-15:30 | 6.85 | 06-AUG-16:40 | 4024.86 | 31-AUG-06:19 |
September | 21542.59 | 26-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 835.55 | 26-SEP-07:19 | 19466.06 | 21-SEP-15:39 | 6.85 | 01-SEP-05:10 | 11216.47 | 29-SEP-06:10 |
October | 23944.02 | 30-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 838.74 | 30-OCT-07:19 | 10680.32 | 11-OCT-15:00 | 6.85 | 13-OCT-11:09 | 83186.15 | 30-OCT-06:10 |
November | 25003.79 | 06-NOV-16:00 | 5686.19 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 839.68 | 02-NOV-07:19 | 4144.98 | 03-NOV-14:30 | 6.85 | 03-NOV-07:10 | 119914.87 | 24-NOV-07:10 |
December | 25003.79 | 01-DEC-16:40 | 5686.19 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 838.79 | 01-DEC-16:49 | 6174.70 | 26-DEC-07:10 | 6.85 | 04-DEC-17:10 | 183526.51 | 11-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 19752.85 | 3328.83 | 45864.70 | 833.16 | 4144.98 | 6.85 | 1382.35 | |||||||
Maximum of Months | 25003.79 | 5686.19 | 45864.70 | 839.68 | 28035.94 | 6.85 | 195174.36 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 24302.97 | 15-MAR-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10025.48 | 07-APR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28642.44 | 10-MAY-14:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 62752.91 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 71055.15 | 05-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 71385.25 | 14-AUG-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 51332.69 | 15-SEP-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19778.83 | 11-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6803.44 | 16-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 71385.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 237424.75 | 02-JAN-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 6968.77 | 6.85 | 195085.73 | 0.00 | 0.00 |
February | 226840.92 | 06-FEB-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 6265.29 | 6.85 | 185205.38 | 0.00 | 0.00 |
March | 181155.98 | 06-MAR-07:10 | 7072.83 | 21098.80 | 0.00 | 243.55 | 4609.60 | 6.85 | 148124.34 | 0.00 | 0.00 |
April | 142245.01 | 17-APR-06:10 | 6698.28 | 21098.80 | 0.00 | 243.48 | 3545.17 | 6.85 | 110652.43 | 0.00 | 0.00 |
May | 101525.91 | 23-MAY-14:30 | 19671.42 | 40588.47 | 0.00 | 831.19 | 13916.88 | 6.85 | 0.00 | 26511.10 | 0.00 |
June | 148517.25 | 27-JUN-12:00 | 19671.42 | 42402.18 | 0.00 | 831.83 | 22852.06 | 6.85 | 0.00 | 62752.91 | 0.00 |
July | 164708.94 | 17-JUL-07:10 | 19671.42 | 45864.70 | 0.00 | 815.84 | 28035.94 | 6.85 | 0.00 | 70314.19 | 0.00 |
August | 159662.55 | 14-AUG-10:00 | 19671.42 | 41577.77 | 0.00 | 831.54 | 26189.72 | 6.85 | 0.00 | 71385.25 | 0.00 |
September | 128903.31 | 15-SEP-10:00 | 19671.42 | 41577.77 | 0.00 | 831.54 | 15483.06 | 6.85 | 0.00 | 51332.69 | 0.00 |
October | 121761.97 | 30-OCT-06:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 3205.58 | 6.85 | 83186.15 | 0.00 | 0.00 |
November | 159091.58 | 24-NOV-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 3806.46 | 6.85 | 119914.87 | 0.00 | 0.00 |
December | 225028.57 | 11-DEC-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 6131.81 | 6.85 | 183526.51 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 101525.91 | 6698.28 | 21098.80 | 0.00 | 243.48 | 3205.58 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 237424.75 | 19671.42 | 45864.70 | 5686.19 | 831.83 | 28035.94 | 6.85 | 195085.73 | 71385.25 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 106013.11 | 04-JAN-07:40 | 0.00 | 10897.71 | 20-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 111728.21 | 07-FEB-07:19 | 0.00 | 11169.68 | 09-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 99485.28 | 07-MAR-07:30 | 0.00 | 11006.52 | 07-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 61328.67 | 17-APR-06:30 | 0.00 | 10241.16 | 06-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 30824.89 | 01-MAY-06:10 | 0.00 | 10132.87 | 02-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 7764.72 | 06-JUN-06:10 | 0.00 | 9987.47 | 01-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9868.95 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9811.90 | 29-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 13501.91 | 30-SEP-06:19 | 0.00 | 9879.34 | 29-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 53237.40 | 17-OCT-06:30 | 0.00 | 9987.90 | 30-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 58475.85 | 24-NOV-07:30 | 0.00 | 10122.22 | 29-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 110056.04 | 11-DEC-08:20 | 0.00 | 10250.18 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9811.90 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 111728.21 | 0.00 | 11169.68 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 19.67 | 1.17 | 19.67 | 0.00 | 19.67 | 0.00 | 19.67 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 19.67 | 1.17 | 19.67 | 0.00 | 19.67 | 0.00 | 19.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 19.67 | 1.17 | 19.67 | 0.00 | 19.67 | 0.00 | 19.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 19.20 | 1.83 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
February | 0.50 | 19.32 | 0.50 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.28 | 0.33 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
Annual Sum or Average | 3.00 | 19.23 | 2.67 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 19.32 | 1.83 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 18.61 | 2.50 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
February | 2.50 | 18.29 | 1.50 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 |
March | 0.17 | 19.10 | 0.17 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.44 | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
December | 2.33 | 18.71 | 1.67 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
Annual Sum or Average | 8.67 | 18.57 | 6.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.50 | 19.44 | 2.50 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 50.67 | 16.37 | 23.83 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
February | 50.67 | 16.37 | 21.83 | 16.92 | 0.00 | 16.92 | 0.00 | 16.92 |
March | 11.00 | 16.74 | 4.17 | 17.31 | 0.00 | 17.31 | 0.00 | 17.31 |
April | 0.83 | 17.06 | 0.33 | 17.70 | 0.00 | 17.70 | 0.00 | 17.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.46 | 1.50 | 27.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.33 | 1.33 | 27.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
November | 1.50 | 18.19 | 1.00 | 18.58 | 0.00 | 18.58 | 0.00 | 18.58 |
December | 40.50 | 16.33 | 19.33 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 |
Annual Sum or Average | 155.50 | 16.41 | 70.50 | 16.90 | 3.33 | 17.06 | 2.83 | 17.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.67 | 18.19 | 23.83 | 18.58 | 2.00 | 27.46 | 1.50 | 27.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 33.33 | 15.01 | 6.83 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 |
February | 32.17 | 14.94 | 4.50 | 15.02 | 0.00 | 15.02 | 0.00 | 15.02 |
March | 7.00 | 15.45 | 0.33 | 15.52 | 0.00 | 15.52 | 0.00 | 15.52 |
April | 0.50 | 15.55 | 0.00 | 15.55 | 0.00 | 15.55 | 0.00 | 15.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.44 | 0.67 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.56 | 6.83 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.77 | 9.83 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.63 | 4.33 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.48 | 1.67 | 27.48 |
October | 0.33 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
November | 1.33 | 16.56 | 0.17 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 |
December | 27.83 | 14.96 | 7.00 | 15.02 | 0.00 | 15.02 | 0.00 | 15.02 |
Annual Sum or Average | 102.50 | 15.03 | 18.83 | 15.10 | 24.00 | 17.17 | 23.33 | 18.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.02 | 0.00 | 15.02 |
Maximum of Months | 33.33 | 17.05 | 7.00 | 17.05 | 10.33 | 27.77 | 9.83 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.00 | 15.19 | 4.83 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 |
February | 28.00 | 15.25 | 4.67 | 15.51 | 0.00 | 15.51 | 0.00 | 15.51 |
March | 4.17 | 16.15 | 0.50 | 16.33 | 0.00 | 16.33 | 0.00 | 16.33 |
April | 0.17 | 16.85 | 0.00 | 16.85 | 0.33 | 23.84 | 0.33 | 25.24 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.50 | 0.67 | 27.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.55 | 3.83 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.65 | 8.33 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.74 | 5.00 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.74 | 4.33 | 27.74 |
October | 0.17 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
November | 0.67 | 17.08 | 0.17 | 17.53 | 0.00 | 17.53 | 0.00 | 17.53 |
December | 21.50 | 15.33 | 4.50 | 15.56 | 0.00 | 15.56 | 0.00 | 15.56 |
Annual Sum or Average | 81.67 | 15.32 | 14.67 | 15.52 | 23.50 | 17.91 | 22.50 | 19.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 | 0.00 | 15.32 |
Maximum of Months | 28.00 | 17.10 | 4.83 | 17.53 | 8.83 | 27.74 | 8.33 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.83 | 14.94 | 8.83 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
February | 31.33 | 14.84 | 5.33 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
March | 5.83 | 15.59 | 0.83 | 15.62 | 0.00 | 15.62 | 0.00 | 15.62 |
April | 0.17 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.72 | 2.17 | 27.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 28.18 | 4.00 | 28.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 28.12 | 6.33 | 28.10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.02 | 3.33 | 28.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.81 | 2.67 | 27.81 |
October | 0.17 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 |
November | 0.67 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 |
December | 27.17 | 14.92 | 6.17 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
Annual Sum or Average | 100.17 | 14.96 | 21.17 | 14.98 | 29.50 | 17.53 | 18.50 | 18.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.86 | 0.00 | 14.86 |
Maximum of Months | 34.83 | 17.02 | 8.83 | 17.02 | 10.33 | 28.18 | 6.33 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.67 | 18.09 | 10.17 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 |
February | 15.33 | 18.38 | 10.50 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 |
March | 3.17 | 18.97 | 2.50 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
April | 0.17 | 19.36 | 0.17 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7.50 | 18.74 | 5.67 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
Annual Sum or Average | 42.83 | 18.38 | 29.00 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 16.67 | 19.36 | 10.50 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.17 | 15.73 | 0.17 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 |
February | 4.33 | 15.81 | 0.17 | 15.94 | 0.00 | 15.94 | 0.00 | 15.94 |
March | 0.50 | 16.51 | 0.00 | 16.51 | 0.00 | 16.51 | 0.00 | 16.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.46 | 1.50 | 27.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.27 | 5.50 | 27.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.42 | 2.33 | 27.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.41 | 1.33 | 27.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 16.16 | 0.00 | 16.16 | 0.00 | 16.16 | 0.00 | 16.16 |
Annual Sum or Average | 12.50 | 15.84 | 0.33 | 15.93 | 10.67 | 21.11 | 10.67 | 23.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.17 | 16.51 | 0.17 | 16.51 | 5.50 | 27.46 | 5.50 | 27.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 85.33 | 16.85 | 80.83 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 |
February | 76.67 | 16.98 | 74.50 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 |
March | 44.67 | 18.14 | 44.50 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 |
April | 21.50 | 19.02 | 21.50 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
May | 4.00 | 19.83 | 4.00 | 19.83 | 0.00 | 19.83 | 0.00 | 19.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.35 | 2.67 | 27.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.52 | 3.00 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.61 | 3.33 | 27.61 |
October | 9.17 | 19.27 | 9.17 | 19.27 | 0.17 | 19.34 | 0.17 | 19.41 |
November | 35.00 | 19.25 | 35.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
December | 71.33 | 17.18 | 70.50 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
Annual Sum or Average | 347.67 | 17.59 | 340.00 | 17.60 | 9.17 | 17.73 | 9.17 | 17.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.33 | 19.83 | 80.83 | 19.83 | 3.33 | 27.61 | 3.33 | 27.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.33 | 15.70 | 0.33 | 15.77 | 0.00 | 15.77 | 0.00 | 15.77 |
February | 4.50 | 15.83 | 0.17 | 15.96 | 0.00 | 15.96 | 0.00 | 15.96 |
March | 0.50 | 16.54 | 0.00 | 16.54 | 0.00 | 16.54 | 0.00 | 16.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.46 | 0.50 | 27.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.71 | 2.83 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.80 | 3.67 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.70 | 2.50 | 27.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.61 | 1.83 | 27.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.67 | 16.04 | 0.00 | 16.04 | 0.00 | 16.04 | 0.00 | 16.04 |
Annual Sum or Average | 13.00 | 15.82 | 0.50 | 15.90 | 19.17 | 22.83 | 11.33 | 24.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.33 | 16.54 | 0.33 | 16.54 | 6.50 | 27.80 | 3.67 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.67 | 17.01 | 7.33 | 17.68 | 0.00 | 17.68 | 0.00 | 17.68 |
February | 20.17 | 17.11 | 8.50 | 17.82 | 0.00 | 17.82 | 0.00 | 17.82 |
March | 1.67 | 18.19 | 1.00 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.50 | 27.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13.67 | 17.11 | 5.83 | 17.78 | 0.00 | 17.78 | 0.00 | 17.78 |
Annual Sum or Average | 54.17 | 17.11 | 22.67 | 17.79 | 0.50 | 17.86 | 0.50 | 17.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.17 | 18.19 | 8.50 | 18.68 | 0.50 | 27.30 | 0.50 | 27.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.50 | 15.41 | 0.67 | 15.45 | 0.00 | 15.45 | 0.00 | 15.45 |
February | 10.50 | 15.18 | 0.00 | 15.18 | 0.00 | 15.18 | 0.00 | 15.18 |
March | 0.67 | 17.36 | 0.17 | 17.78 | 0.00 | 17.78 | 0.00 | 17.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.36 | 0.17 | 27.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.48 | 1.00 | 27.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.63 | 4.33 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.35 | 9.50 | 27.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.57 | 4.00 | 27.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.63 | 2.33 | 27.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8.00 | 15.36 | 0.17 | 15.45 | 0.00 | 15.45 | 0.00 | 15.45 |
Annual Sum or Average | 30.67 | 15.36 | 1.00 | 15.42 | 21.50 | 20.30 | 21.33 | 22.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.50 | 17.36 | 0.67 | 17.78 | 9.67 | 27.63 | 9.50 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.83 | 15.54 | 0.17 | 15.60 | 0.00 | 15.60 | 0.00 | 15.60 |
February | 9.17 | 15.37 | 0.17 | 15.45 | 0.00 | 15.45 | 0.00 | 15.45 |
March | 0.67 | 17.51 | 0.17 | 17.87 | 0.00 | 17.87 | 0.00 | 17.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.33 | 0.67 | 27.33 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.35 | 0.83 | 27.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.43 | 3.00 | 27.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.55 | 6.83 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.66 | 4.83 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.79 | 4.17 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5.50 | 15.82 | 0.50 | 16.11 | 0.00 | 16.11 | 0.00 | 16.11 |
Annual Sum or Average | 24.17 | 15.59 | 1.00 | 15.74 | 20.67 | 21.08 | 20.50 | 23.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.17 | 17.51 | 0.50 | 17.87 | 6.83 | 27.79 | 6.83 | 27.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.67 | 15.36 | 0.83 | 15.39 | 0.00 | 15.39 | 0.00 | 15.39 |
February | 10.00 | 15.18 | 0.00 | 15.18 | 0.00 | 15.18 | 0.00 | 15.18 |
March | 0.50 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.72 | 1.83 | 27.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.11 | 3.50 | 28.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.05 | 5.00 | 28.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.91 | 3.17 | 27.96 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.84 | 2.33 | 27.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8.33 | 15.44 | 0.50 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
Annual Sum or Average | 31.50 | 15.35 | 1.33 | 15.38 | 26.17 | 20.97 | 15.83 | 22.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.67 | 16.74 | 0.83 | 16.74 | 8.83 | 28.11 | 5.00 | 28.10 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.33 | 70.00 | 22.08 | 70.00 | 21.88 |
February | 454.00 | 22.61 | 24.50 | 22.53 | 24.50 | 22.45 |
March | 447.50 | 23.52 | 12.67 | 23.54 | 1.17 | 23.53 |
April | 296.00 | 23.83 | 17.83 | 23.91 | 0.00 | 23.91 |
May | 82.33 | 24.00 | 159.17 | 24.63 | 0.00 | 24.63 |
June | 0.00 | 0.00 | 344.50 | 24.50 | 0.00 | 24.50 |
July | 0.00 | 0.00 | 487.00 | 24.47 | 0.00 | 24.47 |
August | 0.00 | 0.00 | 478.83 | 24.43 | 0.00 | 24.43 |
September | 0.50 | 24.00 | 345.67 | 24.56 | 0.00 | 24.56 |
October | 147.50 | 23.97 | 79.00 | 24.26 | 0.00 | 24.26 |
November | 422.67 | 23.76 | 5.83 | 23.78 | 0.00 | 23.78 |
December | 492.83 | 22.87 | 14.67 | 22.81 | 14.67 | 22.76 |
Annual Sum or Average | 2845.33 | 23.16 | 2039.67 | 23.65 | 110.33 | 23.58 |
Minimum of Months | 0.00 | 0.00 | 5.83 | 22.08 | 0.00 | 21.88 |
Maximum of Months | 502.00 | 24.00 | 487.00 | 24.63 | 70.00 | 24.63 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.84 | 359.17 | 20.71 | 359.17 | 20.65 |
February | 454.00 | 21.02 | 283.83 | 20.87 | 283.83 | 20.81 |
March | 477.33 | 22.09 | 76.67 | 21.95 | 71.67 | 21.82 |
April | 448.67 | 23.07 | 3.67 | 23.05 | 3.67 | 23.04 |
May | 219.67 | 23.71 | 70.00 | 23.90 | 0.00 | 23.90 |
June | 29.67 | 23.93 | 282.83 | 24.28 | 0.00 | 24.28 |
July | 0.00 | 0.00 | 469.83 | 24.34 | 0.00 | 24.34 |
August | 0.00 | 0.00 | 420.17 | 24.34 | 0.00 | 24.34 |
September | 35.17 | 23.47 | 222.17 | 24.29 | 0.00 | 24.29 |
October | 375.00 | 23.17 | 10.67 | 23.21 | 0.00 | 23.21 |
November | 489.00 | 22.34 | 13.67 | 22.30 | 13.67 | 22.26 |
December | 497.00 | 21.06 | 277.17 | 20.90 | 277.17 | 20.83 |
Annual Sum or Average | 3527.50 | 22.03 | 2489.83 | 22.37 | 1009.17 | 22.11 |
Minimum of Months | 0.00 | 0.00 | 3.67 | 20.71 | 0.00 | 20.65 |
Maximum of Months | 502.00 | 23.93 | 469.83 | 24.34 | 359.17 | 24.34 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.36 | 458.17 | 20.31 | 458.17 | 20.29 |
February | 454.00 | 20.49 | 380.50 | 20.40 | 380.50 | 20.36 |
March | 481.50 | 21.43 | 200.33 | 21.19 | 195.50 | 21.04 |
April | 468.17 | 22.51 | 40.33 | 22.34 | 40.33 | 22.19 |
May | 277.67 | 23.49 | 54.33 | 23.62 | 0.00 | 23.62 |
June | 56.67 | 23.65 | 263.00 | 24.17 | 0.00 | 24.17 |
July | 3.67 | 23.68 | 454.67 | 24.35 | 0.00 | 24.35 |
August | 14.17 | 23.56 | 400.33 | 24.27 | 0.00 | 24.27 |
September | 132.50 | 23.34 | 167.50 | 23.89 | 0.00 | 23.89 |
October | 441.33 | 22.43 | 37.50 | 22.31 | 33.00 | 22.20 |
November | 489.00 | 21.40 | 156.50 | 21.16 | 156.50 | 21.02 |
December | 497.00 | 20.45 | 423.50 | 20.38 | 423.50 | 20.35 |
Annual Sum or Average | 3817.67 | 21.55 | 3036.67 | 21.79 | 1687.50 | 21.50 |
Minimum of Months | 3.67 | 20.36 | 37.50 | 20.31 | 0.00 | 20.29 |
Maximum of Months | 502.00 | 23.68 | 458.17 | 24.35 | 458.17 | 24.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.77 | 494.67 | 19.76 | 494.67 | 19.76 |
February | 454.00 | 19.82 | 454.00 | 19.82 | 454.00 | 19.82 |
March | 492.83 | 20.62 | 335.17 | 20.44 | 324.83 | 20.34 |
April | 473.83 | 21.57 | 131.67 | 21.23 | 131.67 | 21.01 |
May | 317.50 | 22.87 | 62.00 | 23.01 | 8.67 | 22.96 |
June | 96.00 | 23.70 | 274.83 | 24.15 | 17.67 | 24.22 |
July | 54.33 | 25.18 | 451.33 | 24.50 | 44.67 | 24.59 |
August | 67.17 | 23.71 | 379.00 | 24.19 | 15.33 | 24.23 |
September | 221.83 | 22.93 | 157.33 | 23.46 | 14.50 | 23.52 |
October | 470.50 | 21.45 | 125.50 | 21.16 | 122.00 | 20.95 |
November | 489.00 | 20.47 | 320.17 | 20.29 | 320.17 | 20.22 |
December | 497.00 | 19.77 | 480.83 | 19.75 | 480.83 | 19.75 |
Annual Sum or Average | 4136.00 | 20.99 | 3666.50 | 21.22 | 2429.00 | 20.95 |
Minimum of Months | 54.33 | 19.77 | 62.00 | 19.75 | 8.67 | 19.75 |
Maximum of Months | 502.00 | 25.18 | 494.67 | 24.50 | 494.67 | 24.59 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.83 | 494.50 | 19.83 | 494.50 | 19.82 |
February | 454.00 | 19.92 | 428.33 | 19.88 | 428.33 | 19.86 |
March | 480.00 | 20.89 | 275.50 | 20.67 | 255.00 | 20.49 |
April | 384.67 | 21.73 | 104.50 | 21.50 | 85.50 | 21.23 |
May | 214.33 | 22.98 | 157.17 | 23.58 | 8.50 | 23.59 |
June | 83.33 | 24.60 | 358.50 | 24.45 | 35.00 | 24.59 |
July | 79.83 | 26.22 | 478.00 | 24.77 | 78.00 | 24.95 |
August | 62.67 | 24.74 | 426.00 | 24.41 | 33.00 | 24.52 |
September | 162.83 | 23.17 | 263.83 | 23.92 | 18.67 | 24.00 |
October | 416.83 | 21.72 | 101.67 | 21.49 | 85.67 | 21.26 |
November | 489.00 | 20.66 | 290.33 | 20.43 | 290.33 | 20.32 |
December | 497.00 | 19.84 | 479.83 | 19.82 | 479.83 | 19.81 |
Annual Sum or Average | 3826.50 | 21.11 | 3858.17 | 21.52 | 2292.33 | 21.25 |
Minimum of Months | 62.67 | 19.83 | 101.67 | 19.82 | 8.50 | 19.81 |
Maximum of Months | 502.00 | 26.22 | 494.50 | 24.77 | 494.50 | 24.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.18 | 434.00 | 20.01 | 434.00 | 19.95 |
February | 449.83 | 20.21 | 373.00 | 20.00 | 373.00 | 19.92 |
March | 452.33 | 21.24 | 233.00 | 20.95 | 214.33 | 20.74 |
April | 375.83 | 21.64 | 133.17 | 21.52 | 101.67 | 21.27 |
May | 257.17 | 22.80 | 129.83 | 23.27 | 12.67 | 23.24 |
June | 110.17 | 23.82 | 311.33 | 24.21 | 27.33 | 24.33 |
July | 85.50 | 25.44 | 451.67 | 24.63 | 67.17 | 24.78 |
August | 77.67 | 24.30 | 405.50 | 24.35 | 28.83 | 24.45 |
September | 165.33 | 23.33 | 264.67 | 24.01 | 26.67 | 24.14 |
October | 369.17 | 21.81 | 141.00 | 21.86 | 76.50 | 21.61 |
November | 464.17 | 20.98 | 235.83 | 20.68 | 232.67 | 20.53 |
December | 495.00 | 20.11 | 439.83 | 19.99 | 439.83 | 19.95 |
Annual Sum or Average | 3804.17 | 21.32 | 3552.83 | 21.66 | 2034.67 | 21.38 |
Minimum of Months | 77.67 | 20.11 | 129.83 | 19.99 | 12.67 | 19.92 |
Maximum of Months | 502.00 | 25.44 | 451.67 | 24.63 | 439.83 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.84 | 490.17 | 19.83 | 490.17 | 19.82 |
February | 454.00 | 19.96 | 424.33 | 19.90 | 424.33 | 19.87 |
March | 479.50 | 20.95 | 282.33 | 20.70 | 267.67 | 20.53 |
April | 398.00 | 21.55 | 147.00 | 21.43 | 112.33 | 21.19 |
May | 266.33 | 22.94 | 143.17 | 23.41 | 18.83 | 23.44 |
June | 104.50 | 24.10 | 339.00 | 24.32 | 33.83 | 24.46 |
July | 83.00 | 25.52 | 459.33 | 24.66 | 67.33 | 24.81 |
August | 75.00 | 24.31 | 417.17 | 24.36 | 28.50 | 24.45 |
September | 194.33 | 23.18 | 226.83 | 23.82 | 27.00 | 23.95 |
October | 435.17 | 21.57 | 132.50 | 21.39 | 104.50 | 21.16 |
November | 488.00 | 20.62 | 287.50 | 20.38 | 287.50 | 20.27 |
December | 497.00 | 19.83 | 472.50 | 19.80 | 472.50 | 19.79 |
Annual Sum or Average | 3976.83 | 21.13 | 3821.83 | 21.48 | 2334.50 | 21.21 |
Minimum of Months | 75.00 | 19.83 | 132.50 | 19.80 | 18.83 | 19.79 |
Maximum of Months | 502.00 | 25.52 | 490.17 | 24.66 | 490.17 | 24.81 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.04 | 494.50 | 20.04 | 494.50 | 20.03 |
February | 454.00 | 20.13 | 454.00 | 20.13 | 454.00 | 20.13 |
March | 510.83 | 20.80 | 342.17 | 20.63 | 342.17 | 20.56 |
April | 485.00 | 21.45 | 119.50 | 21.24 | 119.50 | 21.10 |
May | 428.17 | 22.84 | 13.67 | 22.86 | 1.83 | 22.85 |
June | 119.33 | 23.69 | 228.33 | 24.02 | 9.33 | 24.04 |
July | 27.00 | 24.89 | 452.33 | 24.35 | 25.67 | 24.38 |
August | 35.17 | 23.86 | 387.67 | 24.22 | 11.00 | 24.23 |
September | 168.33 | 23.43 | 156.33 | 23.82 | 11.00 | 23.89 |
October | 455.33 | 22.29 | 20.33 | 22.24 | 18.17 | 22.18 |
November | 489.00 | 21.12 | 178.17 | 20.95 | 178.17 | 20.85 |
December | 497.00 | 20.23 | 465.67 | 20.20 | 465.67 | 20.19 |
Annual Sum or Average | 4171.17 | 21.29 | 3312.67 | 21.48 | 2131.00 | 21.23 |
Minimum of Months | 27.00 | 20.04 | 13.67 | 20.04 | 1.83 | 20.03 |
Maximum of Months | 510.83 | 24.89 | 494.50 | 24.35 | 494.50 | 24.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.13 | 494.17 | 20.13 | 494.17 | 20.12 |
February | 454.00 | 20.23 | 436.50 | 20.21 | 436.50 | 20.20 |
March | 493.00 | 21.09 | 244.50 | 20.85 | 244.50 | 20.73 |
April | 422.33 | 22.09 | 61.00 | 21.92 | 54.00 | 21.74 |
May | 268.00 | 23.14 | 97.00 | 23.54 | 0.00 | 23.54 |
June | 50.00 | 24.24 | 343.33 | 24.39 | 12.67 | 24.44 |
July | 46.50 | 26.15 | 488.00 | 24.65 | 46.50 | 24.77 |
August | 29.33 | 25.04 | 453.50 | 24.43 | 17.83 | 24.48 |
September | 81.00 | 23.74 | 308.17 | 24.27 | 13.00 | 24.34 |
October | 381.50 | 22.72 | 39.67 | 22.82 | 6.17 | 22.79 |
November | 489.00 | 21.42 | 132.50 | 21.21 | 132.50 | 21.07 |
December | 497.00 | 20.28 | 461.83 | 20.25 | 461.83 | 20.24 |
Annual Sum or Average | 3713.67 | 21.41 | 3560.17 | 21.84 | 1919.67 | 21.56 |
Minimum of Months | 29.33 | 20.13 | 39.67 | 20.13 | 0.00 | 20.12 |
Maximum of Months | 502.00 | 26.15 | 494.17 | 24.65 | 494.17 | 24.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.69 | 462.67 | 19.62 | 462.67 | 19.59 |
February | 454.00 | 19.74 | 416.00 | 19.66 | 416.00 | 19.63 |
March | 496.50 | 20.93 | 219.17 | 20.68 | 210.83 | 20.52 |
April | 442.33 | 21.48 | 91.50 | 21.34 | 80.67 | 21.16 |
May | 372.00 | 22.47 | 56.17 | 22.69 | 8.67 | 22.64 |
June | 160.00 | 23.13 | 244.17 | 23.84 | 33.00 | 23.85 |
July | 92.67 | 24.33 | 450.67 | 24.41 | 73.00 | 24.46 |
August | 95.17 | 23.75 | 421.50 | 24.27 | 52.67 | 24.32 |
September | 118.33 | 23.32 | 313.33 | 24.16 | 31.33 | 24.26 |
October | 347.50 | 22.22 | 92.00 | 22.58 | 12.17 | 22.49 |
November | 465.67 | 21.35 | 126.83 | 21.11 | 125.83 | 20.94 |
December | 496.50 | 19.99 | 435.00 | 19.88 | 435.00 | 19.84 |
Annual Sum or Average | 4042.67 | 21.19 | 3329.00 | 21.53 | 1941.83 | 21.26 |
Minimum of Months | 92.67 | 19.69 | 56.17 | 19.62 | 8.67 | 19.59 |
Maximum of Months | 502.00 | 24.33 | 462.67 | 24.41 | 462.67 | 24.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.11 | 489.00 | 20.09 | 489.00 | 20.09 |
February | 454.00 | 20.23 | 433.33 | 20.20 | 433.33 | 20.19 |
March | 502.83 | 21.17 | 255.50 | 20.92 | 255.33 | 20.79 |
April | 439.17 | 21.94 | 79.33 | 21.78 | 68.50 | 21.60 |
May | 285.33 | 23.06 | 93.50 | 23.45 | 0.17 | 23.45 |
June | 64.17 | 24.30 | 336.67 | 24.39 | 19.83 | 24.46 |
July | 48.83 | 25.89 | 475.83 | 24.63 | 47.67 | 24.74 |
August | 30.83 | 25.46 | 460.67 | 24.47 | 23.17 | 24.54 |
September | 94.17 | 23.81 | 278.00 | 24.26 | 15.33 | 24.34 |
October | 399.00 | 22.54 | 42.50 | 22.62 | 10.00 | 22.58 |
November | 489.00 | 21.35 | 143.83 | 21.15 | 143.83 | 21.03 |
December | 497.00 | 20.27 | 458.83 | 20.23 | 458.83 | 20.22 |
Annual Sum or Average | 3806.33 | 21.41 | 3547.00 | 21.81 | 1965.00 | 21.54 |
Minimum of Months | 30.83 | 20.11 | 42.50 | 20.09 | 0.17 | 20.09 |
Maximum of Months | 502.83 | 25.89 | 489.00 | 24.63 | 489.00 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.97 | 492.00 | 19.96 | 492.00 | 19.96 |
February | 454.00 | 20.06 | 440.67 | 20.04 | 440.67 | 20.04 |
March | 489.83 | 20.94 | 285.33 | 20.75 | 275.83 | 20.63 |
April | 474.00 | 22.04 | 64.67 | 21.80 | 64.67 | 21.62 |
May | 287.50 | 23.24 | 60.83 | 23.43 | 0.00 | 23.43 |
June | 63.50 | 23.94 | 282.83 | 24.24 | 8.83 | 24.27 |
July | 36.17 | 25.52 | 467.00 | 24.50 | 35.50 | 24.57 |
August | 31.83 | 24.05 | 407.67 | 24.28 | 10.50 | 24.31 |
September | 159.50 | 23.34 | 172.50 | 23.82 | 12.17 | 23.89 |
October | 451.00 | 22.05 | 54.83 | 21.92 | 49.00 | 21.79 |
November | 489.00 | 20.95 | 217.83 | 20.74 | 217.83 | 20.63 |
December | 497.00 | 20.05 | 465.00 | 20.02 | 465.00 | 20.01 |
Annual Sum or Average | 3935.33 | 21.24 | 3411.17 | 21.52 | 2072.00 | 21.24 |
Minimum of Months | 31.83 | 19.97 | 54.83 | 19.96 | 0.00 | 19.96 |
Maximum of Months | 502.00 | 25.52 | 492.00 | 24.50 | 492.00 | 24.57 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.87 | 419.00 | 19.86 | 419.00 | 19.85 |
February | 385.00 | 20.01 | 351.50 | 19.95 | 351.50 | 19.92 |
March | 405.67 | 21.18 | 199.67 | 20.95 | 185.00 | 20.78 |
April | 325.17 | 22.10 | 67.00 | 22.03 | 43.50 | 21.82 |
May | 179.17 | 23.33 | 122.17 | 23.88 | 4.67 | 23.93 |
June | 55.67 | 24.99 | 303.17 | 24.60 | 25.17 | 24.73 |
July | 68.83 | 26.33 | 410.00 | 24.89 | 68.83 | 25.07 |
August | 42.50 | 25.32 | 366.50 | 24.56 | 28.17 | 24.67 |
September | 109.67 | 23.69 | 225.17 | 24.26 | 19.67 | 24.37 |
October | 342.83 | 22.23 | 51.67 | 22.20 | 31.50 | 22.06 |
November | 416.83 | 21.07 | 173.33 | 20.82 | 173.33 | 20.68 |
December | 422.00 | 19.94 | 394.17 | 19.90 | 394.17 | 19.89 |
Annual Sum or Average | 3180.33 | 21.33 | 3083.33 | 21.75 | 1744.50 | 21.47 |
Minimum of Months | 42.50 | 19.87 | 51.67 | 19.86 | 4.67 | 19.85 |
Maximum of Months | 427.00 | 26.33 | 419.00 | 24.89 | 419.00 | 25.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.00 | 20.44 | 405.17 | 20.26 | 404.00 | 20.18 |
February | 447.67 | 20.52 | 342.50 | 20.29 | 342.50 | 20.20 |
March | 438.33 | 21.62 | 171.50 | 21.38 | 151.33 | 21.17 |
April | 361.83 | 22.14 | 77.50 | 22.13 | 46.50 | 21.94 |
May | 221.67 | 23.18 | 129.17 | 23.67 | 3.00 | 23.69 |
June | 77.17 | 24.11 | 322.50 | 24.31 | 18.00 | 24.39 |
July | 65.50 | 25.88 | 465.17 | 24.66 | 59.50 | 24.81 |
August | 48.67 | 25.03 | 432.17 | 24.45 | 26.67 | 24.54 |
September | 116.83 | 23.89 | 294.83 | 24.29 | 25.67 | 24.43 |
October | 324.00 | 22.36 | 108.33 | 22.65 | 24.83 | 22.53 |
November | 443.17 | 21.43 | 146.67 | 21.19 | 140.83 | 21.02 |
December | 492.83 | 20.44 | 396.67 | 20.29 | 396.67 | 20.23 |
Annual Sum or Average | 3534.67 | 21.60 | 3292.17 | 22.01 | 1639.50 | 21.74 |
Minimum of Months | 48.67 | 20.44 | 77.50 | 20.26 | 3.00 | 20.18 |
Maximum of Months | 497.00 | 25.88 | 465.17 | 24.66 | 404.00 | 24.81 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.03 | 478.17 | 20.00 | 478.17 | 19.99 |
February | 454.00 | 20.18 | 407.67 | 20.10 | 407.67 | 20.07 |
March | 471.00 | 21.28 | 228.67 | 21.04 | 214.33 | 20.87 |
April | 388.50 | 22.06 | 89.67 | 22.04 | 53.50 | 21.85 |
May | 224.83 | 23.32 | 148.83 | 23.80 | 8.00 | 23.86 |
June | 73.33 | 24.59 | 352.00 | 24.44 | 29.50 | 24.56 |
July | 66.17 | 25.93 | 472.67 | 24.69 | 60.83 | 24.84 |
August | 45.67 | 25.00 | 446.50 | 24.44 | 24.67 | 24.53 |
September | 138.67 | 23.69 | 254.67 | 24.15 | 23.83 | 24.28 |
October | 401.83 | 22.15 | 73.17 | 22.14 | 40.17 | 22.00 |
November | 484.83 | 21.11 | 193.17 | 20.86 | 193.17 | 20.72 |
December | 497.00 | 20.10 | 450.83 | 20.05 | 450.83 | 20.03 |
Annual Sum or Average | 3747.83 | 21.38 | 3596.00 | 21.78 | 1984.67 | 21.51 |
Minimum of Months | 45.67 | 20.03 | 73.17 | 20.00 | 8.00 | 19.99 |
Maximum of Months | 502.00 | 25.93 | 478.17 | 24.69 | 478.17 | 24.84 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.32761 | 18.98411 | -0.3085 | 8.65192 |
February | 454.00000 | 22.61029 | 18.35473 | -0.2377 | 6.96485 |
March | 514.00000 | 23.60063 | 24.65076 | 0.07693 | 5.89783 |
April | 485.00000 | 24.05735 | 28.43695 | 0.24301 | 6.55136 |
May | 508.00000 | 24.37441 | 32.38567 | -0.4827 | 10.39877 |
June | 496.00000 | 24.36055 | 43.22630 | -0.3578 | 8.15290 |
July | 497.00000 | 24.46131 | 51.29124 | -0.2564 | 6.88458 |
August | 514.00000 | 24.40216 | 48.01391 | -0.2965 | 7.31668 |
September | 485.00000 | 24.41432 | 43.56347 | -0.3506 | 8.16227 |
October | 502.00000 | 24.26361 | 33.64178 | 0.34887 | 7.76327 |
November | 489.00000 | 23.84102 | 28.00304 | 0.16661 | 5.93537 |
December | 497.00000 | 22.87478 | 21.67813 | -0.1466 | 6.33016 |
Annual Sum or Average | 5943.00000 | 23.80707 | 32.79026 | -0.1336 | 7.42510 |
Minimum of Months | 454.00000 | 22.32761 | 18.35473 | -0.4827 | 5.89783 |
Maximum of Months | 514.00000 | 24.46131 | 51.29124 | 0.34887 | 10.39877 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.83524 | 20.07426 | -0.6498 | 15.05166 |
February | 454.00000 | 21.01867 | 19.57620 | -0.6036 | 13.46337 |
March | 514.00000 | 22.22887 | 26.99476 | -0.2303 | 7.91374 |
April | 485.00000 | 23.15511 | 30.81220 | 0.03360 | 6.02306 |
May | 508.00000 | 24.01852 | 33.96404 | -0.6134 | 13.45035 |
June | 496.00000 | 24.20801 | 44.24234 | -0.4290 | 9.23780 |
July | 497.00000 | 24.32712 | 52.14473 | -0.3191 | 7.46320 |
August | 514.00000 | 24.27699 | 48.88841 | -0.3636 | 8.06783 |
September | 485.00000 | 24.17596 | 44.72537 | -0.4601 | 9.97057 |
October | 502.00000 | 23.40242 | 36.37940 | 0.13572 | 6.13850 |
November | 489.00000 | 22.33865 | 31.39665 | -0.1808 | 6.66624 |
December | 497.00000 | 21.05908 | 23.49493 | -0.5641 | 12.60696 |
Annual Sum or Average | 5943.00000 | 22.93429 | 34.49618 | -0.3527 | 9.65348 |
Minimum of Months | 454.00000 | 20.83524 | 19.57620 | -0.6498 | 6.02306 |
Maximum of Months | 514.00000 | 24.32712 | 52.14473 | 0.13572 | 15.05166 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.35746 | 20.07372 | -0.7987 | 20.19432 |
February | 454.00000 | 20.48988 | 19.92291 | -0.7605 | 18.87738 |
March | 514.00000 | 21.59184 | 27.60770 | -0.3991 | 11.09615 |
April | 485.00000 | 22.56553 | 31.73177 | -0.1126 | 7.06319 |
May | 508.00000 | 23.79574 | 34.43327 | -0.6930 | 16.13035 |
June | 496.00000 | 24.13751 | 44.45264 | -0.4492 | 9.81073 |
July | 497.00000 | 24.32040 | 52.06774 | -0.3152 | 7.48309 |
August | 514.00000 | 24.21726 | 48.91907 | -0.3843 | 8.42371 |
September | 485.00000 | 23.94879 | 45.28331 | -0.5471 | 12.27439 |
October | 502.00000 | 22.61928 | 38.01029 | -0.0584 | 6.84651 |
November | 489.00000 | 21.40489 | 32.76497 | -0.4195 | 10.07867 |
December | 497.00000 | 20.45231 | 24.08067 | -0.7438 | 18.28070 |
Annual Sum or Average | 5943.00000 | 22.50741 | 35.04942 | -0.4719 | 12.17402 |
Minimum of Months | 454.00000 | 20.35746 | 19.92291 | -0.7987 | 6.84651 |
Maximum of Months | 514.00000 | 24.32040 | 52.06774 | -0.0584 | 20.19432 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.77080 | 20.68069 | -1.0073 | 28.73117 |
February | 454.00000 | 19.82357 | 20.88445 | -0.9760 | 27.52099 |
March | 514.00000 | 20.75828 | 29.38681 | -0.6203 | 17.19721 |
April | 485.00000 | 21.62291 | 33.46623 | -0.3306 | 10.29669 |
May | 508.00000 | 23.32930 | 36.75071 | -0.8274 | 21.88451 |
June | 496.00000 | 24.06808 | 45.67139 | -0.4375 | 10.55504 |
July | 497.00000 | 24.36868 | 53.73706 | -0.2480 | 7.36685 |
August | 514.00000 | 24.12814 | 50.27499 | -0.3820 | 9.17470 |
September | 485.00000 | 23.53802 | 47.62802 | -0.6724 | 17.12304 |
October | 502.00000 | 21.60827 | 40.28004 | -0.2945 | 9.81828 |
November | 489.00000 | 20.46567 | 34.08362 | -0.6657 | 16.37106 |
December | 497.00000 | 19.77451 | 24.82497 | -0.9659 | 27.28547 |
Annual Sum or Average | 5943.00000 | 21.95571 | 36.58006 | -0.6166 | 16.87369 |
Minimum of Months | 454.00000 | 19.77080 | 20.68069 | -1.0073 | 7.36685 |
Maximum of Months | 514.00000 | 24.36868 | 53.73706 | -0.2480 | 28.73117 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83384 | 21.53282 | -0.9720 | 27.33266 |
February | 454.00000 | 19.92110 | 21.71386 | -0.9265 | 25.77087 |
March | 514.00000 | 21.09593 | 29.74962 | -0.5073 | 14.83070 |
April | 485.00000 | 22.24571 | 32.51903 | -0.1530 | 9.55208 |
May | 508.00000 | 23.70440 | 35.53595 | -0.6402 | 16.81911 |
June | 496.00000 | 24.24339 | 44.85055 | -0.3017 | 9.02066 |
July | 497.00000 | 24.50202 | 52.94696 | -0.1202 | 7.17765 |
August | 514.00000 | 24.25427 | 49.61009 | -0.2640 | 8.09873 |
September | 485.00000 | 23.86287 | 46.42434 | -0.5063 | 13.45570 |
October | 502.00000 | 22.11787 | 39.69334 | -0.1589 | 8.97851 |
November | 489.00000 | 20.65647 | 34.62471 | -0.6080 | 15.15973 |
December | 497.00000 | 19.83861 | 25.58279 | -0.9400 | 26.19467 |
Annual Sum or Average | 5943.00000 | 22.20789 | 36.33366 | -0.5054 | 15.12539 |
Minimum of Months | 454.00000 | 19.83384 | 21.53282 | -0.9720 | 7.17765 |
Maximum of Months | 514.00000 | 24.50202 | 52.94696 | -0.1202 | 27.33266 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.18333 | 20.46284 | -0.8600 | 24.24480 |
February | 454.00000 | 20.24164 | 20.55162 | -0.8248 | 23.58417 |
March | 514.00000 | 21.57153 | 28.00328 | -0.3814 | 13.11918 |
April | 485.00000 | 22.23497 | 31.68371 | -0.1594 | 9.87352 |
May | 508.00000 | 23.49787 | 35.73347 | -0.7294 | 19.89876 |
June | 496.00000 | 24.06908 | 45.40568 | -0.4033 | 10.81552 |
July | 497.00000 | 24.39956 | 53.37044 | -0.1960 | 7.67218 |
August | 514.00000 | 24.20608 | 49.59918 | -0.2929 | 8.68705 |
September | 485.00000 | 23.88248 | 45.84857 | -0.4743 | 13.58679 |
October | 502.00000 | 22.43764 | 37.67516 | -0.0629 | 9.27636 |
November | 489.00000 | 21.13384 | 32.68786 | -0.4822 | 13.51107 |
December | 497.00000 | 20.12233 | 24.55491 | -0.8469 | 23.29161 |
Annual Sum or Average | 5943.00000 | 22.34883 | 35.57019 | -0.4739 | 14.73843 |
Minimum of Months | 454.00000 | 20.12233 | 20.46284 | -0.8600 | 7.67218 |
Maximum of Months | 514.00000 | 24.39956 | 53.37044 | -0.0629 | 24.24480 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.84387 | 21.36146 | -0.9794 | 27.67183 |
February | 454.00000 | 19.96172 | 21.51622 | -0.9274 | 26.01914 |
March | 514.00000 | 21.15972 | 29.55111 | -0.5023 | 15.05596 |
April | 485.00000 | 22.04374 | 32.88240 | -0.2068 | 10.29115 |
May | 508.00000 | 23.52696 | 36.38085 | -0.7021 | 19.61742 |
June | 496.00000 | 24.14138 | 45.44951 | -0.3333 | 10.18771 |
July | 497.00000 | 24.43924 | 53.47834 | -0.1548 | 7.59119 |
August | 514.00000 | 24.21873 | 49.99666 | -0.2824 | 8.70342 |
September | 485.00000 | 23.73090 | 47.18408 | -0.5586 | 15.28604 |
October | 502.00000 | 21.90080 | 39.99373 | -0.2106 | 9.64559 |
November | 489.00000 | 20.62595 | 34.62427 | -0.6175 | 15.57995 |
December | 497.00000 | 19.83077 | 25.52295 | -0.9430 | 26.40056 |
Annual Sum or Average | 5943.00000 | 22.13659 | 36.59899 | -0.5321 | 15.93379 |
Minimum of Months | 454.00000 | 19.83077 | 21.36146 | -0.9794 | 7.59119 |
Maximum of Months | 514.00000 | 24.43924 | 53.47834 | -0.1548 | 27.67183 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.04458 | 20.83945 | -0.9206 | 24.53492 |
February | 454.00000 | 20.12650 | 21.04547 | -0.8890 | 23.17927 |
March | 514.00000 | 20.82105 | 29.89540 | -0.6097 | 15.15270 |
April | 485.00000 | 21.44656 | 34.42501 | -0.3803 | 9.35100 |
May | 508.00000 | 23.02112 | 38.38572 | -0.9684 | 26.41772 |
June | 496.00000 | 24.00989 | 46.20234 | -0.5046 | 11.05235 |
July | 497.00000 | 24.28328 | 53.94186 | -0.3186 | 7.54857 |
August | 514.00000 | 24.17197 | 50.24590 | -0.3906 | 8.64583 |
September | 485.00000 | 23.83634 | 47.12740 | -0.5779 | 13.16050 |
October | 502.00000 | 22.45007 | 38.95810 | -0.0820 | 6.58677 |
November | 489.00000 | 21.12109 | 33.45137 | -0.4669 | 10.51555 |
December | 497.00000 | 20.22578 | 24.85563 | -0.8174 | 20.58817 |
Annual Sum or Average | 5943.00000 | 22.14559 | 36.72471 | -0.5756 | 14.69380 |
Minimum of Months | 454.00000 | 20.04458 | 20.83945 | -0.9684 | 6.58677 |
Maximum of Months | 514.00000 | 24.28328 | 53.94186 | -0.0820 | 26.41772 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.13344 | 21.69127 | -0.8822 | 22.99779 |
February | 454.00000 | 20.23377 | 21.93488 | -0.8395 | 21.34774 |
March | 514.00000 | 21.20753 | 30.31117 | -0.4814 | 12.40039 |
April | 485.00000 | 22.37994 | 33.24397 | -0.1332 | 7.87188 |
May | 508.00000 | 23.68760 | 36.43031 | -0.6930 | 17.32836 |
June | 496.00000 | 24.27238 | 44.85697 | -0.3369 | 8.60350 |
July | 497.00000 | 24.50001 | 52.76370 | -0.1604 | 6.70387 |
August | 514.00000 | 24.33550 | 49.34682 | -0.2545 | 7.33245 |
September | 485.00000 | 24.16656 | 45.76259 | -0.4034 | 9.87806 |
October | 502.00000 | 23.05861 | 38.00480 | 0.07598 | 6.68843 |
November | 489.00000 | 21.41650 | 33.84320 | -0.3868 | 9.56857 |
December | 497.00000 | 20.28373 | 25.70447 | -0.7943 | 19.69319 |
Annual Sum or Average | 5943.00000 | 22.48953 | 36.25979 | -0.4387 | 12.48768 |
Minimum of Months | 454.00000 | 20.13344 | 21.69127 | -0.8822 | 6.68843 |
Maximum of Months | 514.00000 | 24.50001 | 52.76370 | 0.07598 | 22.99779 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.69262 | 18.59201 | -0.9229 | 25.40431 |
February | 454.00000 | 19.73562 | 18.95977 | -0.8966 | 24.17145 |
March | 514.00000 | 21.02840 | 26.98938 | -0.4715 | 12.54050 |
April | 485.00000 | 21.75667 | 31.59488 | -0.2578 | 8.93364 |
May | 508.00000 | 22.96276 | 36.51821 | -0.9252 | 26.05677 |
June | 496.00000 | 23.85332 | 46.51505 | -0.5060 | 12.30539 |
July | 497.00000 | 24.31721 | 54.55217 | -0.2532 | 7.69203 |
August | 514.00000 | 24.18286 | 50.14154 | -0.3055 | 8.53952 |
September | 485.00000 | 24.03338 | 45.63075 | -0.4048 | 11.11335 |
October | 502.00000 | 22.86023 | 35.64974 | 0.07499 | 7.47163 |
November | 489.00000 | 21.48780 | 30.20797 | -0.3372 | 9.58554 |
December | 497.00000 | 19.99053 | 22.75665 | -0.8151 | 21.22341 |
Annual Sum or Average | 5943.00000 | 22.17619 | 34.95772 | -0.4998 | 14.54385 |
Minimum of Months | 454.00000 | 19.69262 | 18.59201 | -0.9252 | 7.47163 |
Maximum of Months | 514.00000 | 24.31721 | 54.55217 | 0.07499 | 26.05677 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.10677 | 21.62686 | -0.8962 | 23.66110 |
February | 454.00000 | 20.23275 | 21.84507 | -0.8482 | 21.81108 |
March | 514.00000 | 21.22784 | 30.27886 | -0.4818 | 12.46301 |
April | 485.00000 | 22.16386 | 33.58002 | -0.1893 | 8.22001 |
May | 508.00000 | 23.60869 | 36.97309 | -0.7260 | 18.62249 |
June | 496.00000 | 24.25095 | 45.12223 | -0.3402 | 8.77072 |
July | 497.00000 | 24.48326 | 53.09075 | -0.1780 | 6.83314 |
August | 514.00000 | 24.35270 | 49.49788 | -0.2547 | 7.43935 |
September | 485.00000 | 24.12522 | 46.15854 | -0.4295 | 10.42034 |
October | 502.00000 | 22.85858 | 38.39053 | 0.02743 | 6.70334 |
November | 489.00000 | 21.35328 | 33.93868 | -0.4029 | 9.72573 |
December | 497.00000 | 20.27058 | 25.69858 | -0.7982 | 19.88706 |
Annual Sum or Average | 5943.00000 | 22.43631 | 36.45332 | -0.4576 | 12.83222 |
Minimum of Months | 454.00000 | 20.10677 | 21.62686 | -0.8962 | 6.70334 |
Maximum of Months | 514.00000 | 24.48326 | 53.09075 | 0.02743 | 23.66110 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.96944 | 20.77727 | -0.9178 | 24.79997 |
February | 454.00000 | 20.05617 | 20.90441 | -0.8799 | 23.26799 |
March | 514.00000 | 21.08344 | 29.07722 | -0.5119 | 13.78634 |
April | 485.00000 | 22.08454 | 32.77976 | -0.2072 | 8.09878 |
May | 508.00000 | 23.62164 | 36.07630 | -0.7286 | 17.65774 |
June | 496.00000 | 24.16146 | 45.26355 | -0.4104 | 9.37583 |
July | 497.00000 | 24.39629 | 53.51530 | -0.2470 | 7.03759 |
August | 514.00000 | 24.21887 | 49.96892 | -0.3539 | 8.29614 |
September | 485.00000 | 23.82979 | 46.79694 | -0.5690 | 13.25458 |
October | 502.00000 | 22.25022 | 38.96481 | -0.1274 | 7.36360 |
November | 489.00000 | 20.94585 | 33.41283 | -0.5135 | 11.88058 |
December | 497.00000 | 20.05451 | 24.70800 | -0.8546 | 22.46585 |
Annual Sum or Average | 5943.00000 | 22.23996 | 36.12635 | -0.5246 | 13.88355 |
Minimum of Months | 454.00000 | 19.96944 | 20.77727 | -0.9178 | 7.03759 |
Maximum of Months | 514.00000 | 24.39629 | 53.51530 | -0.1274 | 24.79997 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.86894 | 21.23615 | -0.9258 | 25.18086 |
February | 385.00000 | 20.01492 | 21.47432 | -0.8693 | 23.13175 |
March | 433.00000 | 21.35935 | 29.18496 | -0.4234 | 12.17028 |
April | 410.00000 | 22.55630 | 31.73231 | -0.0712 | 8.14220 |
May | 430.00000 | 23.90478 | 34.83325 | -0.5847 | 14.67804 |
June | 418.00000 | 24.37441 | 44.31039 | -0.2824 | 8.53339 |
July | 422.00000 | 24.62834 | 52.48663 | -0.1108 | 7.14961 |
August | 433.00000 | 24.38405 | 49.06026 | -0.2464 | 7.72768 |
September | 410.00000 | 24.10192 | 45.76630 | -0.4357 | 11.28507 |
October | 427.00000 | 22.60894 | 38.18034 | -0.0322 | 7.38036 |
November | 417.00000 | 21.07269 | 33.51673 | -0.4773 | 11.58468 |
December | 422.00000 | 19.93988 | 25.09798 | -0.8729 | 23.17055 |
Annual Sum or Average | 5034.00000 | 22.41621 | 35.65957 | -0.4420 | 13.28860 |
Minimum of Months | 385.00000 | 19.86894 | 21.23615 | -0.9258 | 7.14961 |
Maximum of Months | 433.00000 | 24.62834 | 52.48663 | -0.0322 | 25.18086 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.48703 | 20.29735 | -0.7519 | 20.24772 |
February | 454.00000 | 20.56938 | 20.32551 | -0.7120 | 19.13281 |
March | 514.00000 | 21.97845 | 27.44632 | -0.2600 | 10.33039 |
April | 485.00000 | 22.68409 | 30.92813 | -0.0402 | 8.10652 |
May | 508.00000 | 23.76888 | 35.07600 | -0.6376 | 15.92589 |
June | 496.00000 | 24.18153 | 44.93581 | -0.3722 | 9.40528 |
July | 497.00000 | 24.44996 | 53.06030 | -0.1900 | 7.17216 |
August | 514.00000 | 24.29684 | 49.27619 | -0.2662 | 7.79159 |
September | 485.00000 | 24.11780 | 45.21645 | -0.3884 | 10.62017 |
October | 502.00000 | 23.02423 | 36.39826 | 0.09100 | 7.94178 |
November | 489.00000 | 21.67848 | 31.82817 | -0.3201 | 9.96142 |
December | 497.00000 | 20.47407 | 24.26137 | -0.7229 | 18.59024 |
Annual Sum or Average | 5943.00000 | 22.65896 | 35.02509 | -0.3789 | 12.05872 |
Minimum of Months | 454.00000 | 20.47407 | 20.29735 | -0.7519 | 7.17216 |
Maximum of Months | 514.00000 | 24.44996 | 53.06030 | 0.09100 | 20.24772 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.03179 | 21.54580 | -0.8918 | 23.95799 |
February | 454.00000 | 20.18061 | 21.61192 | -0.8341 | 22.05370 |
March | 514.00000 | 21.51653 | 29.17938 | -0.3888 | 11.99724 |
April | 485.00000 | 22.50788 | 32.15240 | -0.0840 | 8.36982 |
May | 508.00000 | 23.81732 | 35.66163 | -0.6051 | 15.46006 |
June | 496.00000 | 24.25192 | 44.97391 | -0.3027 | 8.82357 |
July | 497.00000 | 24.48869 | 53.17852 | -0.1487 | 7.10203 |
August | 514.00000 | 24.31207 | 49.65973 | -0.2547 | 7.80264 |
September | 485.00000 | 24.00394 | 46.37588 | -0.4617 | 11.75983 |
October | 502.00000 | 22.53220 | 38.65185 | -0.0468 | 7.50007 |
November | 489.00000 | 21.12991 | 33.92888 | -0.4619 | 11.29377 |
December | 497.00000 | 20.10041 | 25.49160 | -0.8338 | 21.75100 |
Annual Sum or Average | 5943.00000 | 22.42381 | 36.13562 | -0.4403 | 13.09728 |
Minimum of Months | 454.00000 | 20.03179 | 21.54580 | -0.8918 | 7.10203 |
Maximum of Months | 514.00000 | 24.48869 | 53.17852 | -0.0468 | 23.95799 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.180352E+10 | 0.462068E+09 | 34.63 | 0.147785E+10 | 0.325670E+09 | 0.00 | 0.91 | 15-MAR-14:00 | 0.00 | 01-MAR-00:10 | 29548.89 | 15-MAR-14:00 | 29548.89 | 15-MAR-14:00 | 7997.07 | 14-MAR-10:50 | 7320.72 | 15-MAR-14:00 | 0.00 |
April | 0.205654E+10 | 0.559192E+09 | 85.37 | 0.195557E+10 | 0.100968E+09 | 0.00 | 0.63 | 26-APR-14:10 | 0.00 | 01-APR-00:10 | 19201.38 | 26-APR-14:10 | 19201.38 | 26-APR-14:10 | 2764.74 | 08-APR-14:00 | 4861.71 | 26-APR-14:10 | 0.00 |
May | 0.801113E+10 | 0.207758E+10 | 206.68 | 0.732075E+10 | 0.690380E+09 | 0.00 | 1.00 | 10-MAY-13:00 | 0.00 | 01-MAY-00:10 | 37874.57 | 23-MAY-14:30 | 37874.57 | 23-MAY-14:30 | 7209.25 | 24-MAY-06:03 | 8916.69 | 10-MAY-15:10 | 0.00 |
June | 0.362604E+11 | 0.884609E+10 | 373.46 | 0.275349E+11 | 0.872552E+10 | 0.00 | 1.00 | 01-JUN-14:00 | 0.00 | 01-JUN-00:10 | 100883.75 | 27-JUN-07:40 | 61820.16 | 12-JUN-15:10 | 58089.84 | 27-JUN-06:03 | 22763.70 | 27-JUN-07:40 | 0.00 |
July | 0.641728E+11 | 0.154771E+11 | 426.50 | 0.456618E+11 | 0.185110E+11 | 0.00 | 1.00 | 03-JUL-10:00 | 0.00 | 01-JUL-00:10 | 114412.15 | 20-JUL-04:03 | 67226.98 | 21-JUL-06:03 | 68488.25 | 20-JUL-04:03 | 26100.84 | 21-JUL-04:03 | 0.00 |
August | 0.547863E+11 | 0.132564E+11 | 416.11 | 0.426165E+11 | 0.121698E+11 | 0.00 | 1.00 | 01-AUG-11:50 | 0.00 | 01-AUG-00:10 | 114387.47 | 14-AUG-08:00 | 64848.77 | 14-AUG-15:30 | 70169.14 | 14-AUG-05:12 | 25689.59 | 15-AUG-08:20 | 0.00 |
September | 0.243146E+11 | 0.588916E+10 | 303.82 | 0.184727E+11 | 0.584194E+10 | 0.00 | 1.00 | 08-SEP-12:00 | 0.00 | 01-SEP-00:10 | 80242.57 | 15-SEP-11:10 | 55030.35 | 21-SEP-16:00 | 42717.77 | 14-SEP-06:03 | 18439.23 | 15-SEP-11:10 | 0.00 |
October | 0.396399E+10 | 0.105583E+10 | 147.30 | 0.352546E+10 | 0.438527E+09 | 0.00 | 0.95 | 11-OCT-15:10 | 0.00 | 01-OCT-00:10 | 31612.77 | 11-OCT-15:10 | 31612.77 | 11-OCT-15:10 | 5382.88 | 12-OCT-15:00 | 7317.58 | 11-OCT-15:10 | 0.00 |
November | 0.639820E+09 | 0.179194E+09 | 35.34 | 0.519924E+09 | 0.119896E+09 | 0.00 | 0.37 | 01-NOV-12:30 | 0.00 | 01-NOV-00:10 | 10316.36 | 01-NOV-12:30 | 10316.36 | 01-NOV-12:30 | 2597.29 | 16-NOV-16:30 | 2800.16 | 01-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.196009E+12 | 0.478026E+11 | 2029.20 | 0.149085E+12 | 0.469237E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.641728E+11 | 0.154771E+11 | 426.50 | 0.456618E+11 | 0.185110E+11 | 0.00 | 1.00 | 0.00 | 114412.15 | 67226.98 | 70169.14 | 26100.84 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.171119E+10 | 0.434227E+09 | 33.50 | 0.140665E+10 | 0.304534E+09 | 0.00 | 1.00 | 15-MAR-13:40 | 0.00 | 01-MAR-00:10 | 33507.35 | 15-MAR-14:05 | 33507.35 | 15-MAR-14:05 | 7470.99 | 14-MAR-10:40 | 8071.42 | 15-MAR-14:05 | 0.00 |
April | 0.610301E+09 | 0.169338E+09 | 38.97 | 0.544156E+09 | 66145170.29 | 0.00 | 0.48 | 07-APR-14:05 | 0.00 | 01-APR-00:10 | 12646.81 | 07-APR-14:05 | 12646.81 | 07-APR-14:05 | 2138.90 | 08-APR-14:10 | 3338.39 | 07-APR-14:05 | 0.00 |
May | 0.733910E+10 | 0.188980E+10 | 198.39 | 0.663066E+10 | 0.708442E+09 | 0.00 | 1.00 | 10-MAY-12:40 | 0.00 | 01-MAY-00:10 | 38508.29 | 23-MAY-14:30 | 38508.29 | 23-MAY-14:30 | 6612.65 | 14-MAY-13:50 | 9274.35 | 10-MAY-15:00 | 0.00 |
June | 0.340094E+11 | 0.829281E+10 | 380.21 | 0.257825E+11 | 0.822692E+10 | 0.00 | 1.00 | 01-JUN-13:50 | 0.00 | 01-JUN-00:10 | 94371.70 | 12-JUN-06:03 | 62291.70 | 12-JUN-14:05 | 50940.14 | 27-JUN-06:03 | 21660.32 | 12-JUN-06:03 | 0.00 |
July | 0.585588E+11 | 0.141301E+11 | 432.91 | 0.414434E+11 | 0.171154E+11 | 0.00 | 1.00 | 02-JUL-15:12 | 0.00 | 01-JUL-00:10 | 104779.09 | 20-JUL-06:03 | 60707.16 | 21-JUL-14:05 | 62174.86 | 20-JUL-05:03 | 24027.38 | 21-JUL-04:03 | 0.00 |
August | 0.477792E+11 | 0.116016E+11 | 417.48 | 0.371748E+11 | 0.106044E+11 | 0.00 | 1.00 | 01-AUG-12:05 | 0.00 | 01-AUG-00:10 | 104508.94 | 14-AUG-10:05 | 61396.78 | 09-AUG-15:20 | 64375.57 | 14-AUG-05:12 | 23406.50 | 14-AUG-11:00 | 0.00 |
September | 0.203327E+11 | 0.496635E+10 | 302.75 | 0.153381E+11 | 0.499459E+10 | 0.00 | 1.00 | 08-SEP-12:05 | 0.00 | 01-SEP-00:10 | 73092.03 | 15-SEP-11:00 | 50858.72 | 21-SEP-15:40 | 33194.92 | 15-SEP-11:00 | 16730.45 | 15-SEP-11:00 | 0.00 |
October | 0.217810E+10 | 0.581928E+09 | 85.52 | 0.180453E+10 | 0.373566E+09 | 0.00 | 0.89 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 26700.08 | 11-OCT-15:00 | 26700.08 | 11-OCT-15:00 | 5152.79 | 12-OCT-15:00 | 6287.87 | 11-OCT-15:00 | 0.00 |
November | 0.309780E+09 | 87294261.82 | 19.50 | 0.206241E+09 | 0.103539E+09 | 0.00 | 0.29 | 16-NOV-18:00 | 0.00 | 01-NOV-00:10 | 7288.35 | 16-NOV-18:00 | 5299.51 | 16-NOV-12:40 | 2352.35 | 04-NOV-15:00 | 2016.88 | 16-NOV-18:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.172829E+12 | 0.421534E+11 | 1909.22 | 0.130331E+12 | 0.424976E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.585588E+11 | 0.141301E+11 | 432.91 | 0.414434E+11 | 0.171154E+11 | 0.00 | 1.00 | 0.00 | 104779.09 | 62291.70 | 64375.57 | 24027.38 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.187361E+10 | 0.475238E+09 | 33.67 | 0.156111E+10 | 0.312503E+09 | 0.00 | 1.00 | 15-MAR-13:05 | 0.00 | 01-MAR-00:10 | 39025.40 | 15-MAR-13:50 | 39025.40 | 15-MAR-13:50 | 8121.55 | 14-MAR-11:00 | 9414.84 | 15-MAR-14:00 | 0.00 |
April | 0.620457E+09 | 0.172874E+09 | 37.81 | 0.541424E+09 | 79033380.67 | 0.00 | 0.44 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 12904.26 | 08-APR-13:30 | 12707.46 | 07-APR-14:00 | 2494.01 | 08-APR-14:00 | 3436.84 | 08-APR-13:30 | 0.00 |
May | 0.754256E+10 | 0.195086E+10 | 197.69 | 0.675395E+10 | 0.788604E+09 | 0.00 | 1.00 | 10-MAY-12:50 | 0.00 | 01-MAY-00:10 | 44151.33 | 10-MAY-14:30 | 44151.33 | 10-MAY-14:30 | 7367.25 | 14-MAY-14:00 | 10650.12 | 10-MAY-14:30 | 0.00 |
June | 0.356732E+11 | 0.873731E+10 | 379.36 | 0.270808E+11 | 0.859246E+10 | 0.00 | 1.00 | 01-JUN-13:50 | 0.00 | 01-JUN-00:10 | 84692.39 | 27-JUN-13:05 | 69688.30 | 12-JUN-14:00 | 43681.76 | 27-JUN-07:40 | 22124.54 | 27-JUN-13:00 | 0.00 |
July | 0.620074E+11 | 0.150197E+11 | 434.21 | 0.441129E+11 | 0.178945E+11 | 0.00 | 1.00 | 02-JUL-15:52 | 0.00 | 01-JUL-00:10 | 116404.43 | 20-JUL-06:03 | 70454.59 | 21-JUL-13:30 | 69332.62 | 20-JUL-05:03 | 26737.19 | 21-JUL-04:03 | 0.00 |
August | 0.497518E+11 | 0.121459E+11 | 416.99 | 0.386558E+11 | 0.110961E+11 | 0.00 | 1.00 | 01-AUG-12:05 | 0.00 | 01-AUG-00:10 | 114986.84 | 14-AUG-06:03 | 69379.82 | 09-AUG-15:00 | 71420.78 | 14-AUG-05:12 | 25823.77 | 14-AUG-06:03 | 0.00 |
September | 0.201619E+11 | 0.497237E+10 | 301.56 | 0.149646E+11 | 0.519726E+10 | 0.00 | 1.00 | 08-SEP-12:40 | 0.00 | 01-SEP-00:10 | 80422.77 | 15-SEP-12:50 | 56565.26 | 21-SEP-15:30 | 36014.29 | 15-SEP-12:50 | 18616.76 | 15-SEP-12:50 | 0.00 |
October | 0.204409E+10 | 0.553161E+09 | 85.02 | 0.164249E+10 | 0.401602E+09 | 0.00 | 0.80 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 25883.88 | 11-OCT-15:00 | 25883.88 | 11-OCT-15:00 | 5445.39 | 12-OCT-15:00 | 6259.04 | 11-OCT-15:00 | 0.00 |
November | 0.320450E+09 | 90592925.33 | 18.83 | 0.209606E+09 | 0.110844E+09 | 0.00 | 0.34 | 27-NOV-07:03 | 0.00 | 01-NOV-00:10 | 9664.35 | 27-NOV-07:03 | 8352.65 | 27-NOV-07:03 | 2486.81 | 04-NOV-15:00 | 2640.78 | 27-NOV-07:03 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.179995E+12 | 0.441181E+11 | 1905.15 | 0.135523E+12 | 0.444728E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.620074E+11 | 0.150197E+11 | 434.21 | 0.441129E+11 | 0.178945E+11 | 0.00 | 1.00 | 0.00 | 116404.43 | 70454.59 | 71420.78 | 26737.19 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 360.55 | 0.00 | 360.55 | 7.43 | 2046.16 | 0.00 | 0.00 | 0.00 |
February | 549.34 | 0.00 | 549.34 | 44.61 | 1909.82 | 0.00 | 0.00 | 0.00 |
March | 666.20 | 0.00 | 666.20 | 233.79 | 1372.60 | 0.00 | 0.00 | 0.00 |
April | 848.87 | 3.39 | 845.48 | 483.68 | 977.68 | 0.00 | 0.00 | 0.00 |
May | 986.34 | 41.83 | 944.52 | 787.68 | 646.41 | 0.00 | 0.00 | 0.00 |
June | 1186.36 | 100.99 | 1085.38 | 1283.85 | 426.47 | 0.00 | 0.00 | 0.00 |
July | 1100.51 | 71.04 | 1029.47 | 1370.88 | 301.41 | 0.00 | 0.00 | 0.00 |
August | 952.25 | 14.49 | 937.76 | 1123.73 | 396.15 | 0.00 | 0.00 | 0.00 |
September | 724.68 | 0.15 | 724.53 | 663.35 | 636.39 | 0.00 | 0.00 | 0.00 |
October | 541.73 | 0.00 | 541.73 | 285.68 | 968.81 | 0.00 | 0.00 | 0.00 |
November | 364.03 | 0.00 | 364.03 | 92.90 | 1234.87 | 0.00 | 0.00 | 0.00 |
December | 337.46 | 0.00 | 337.46 | 8.38 | 1936.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 718.89 | 19.41 | 699.49 | 535.09 | 1066.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 337.46 | 0.00 | 337.46 | 7.43 | 301.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1186.36 | 100.99 | 1085.38 | 1370.88 | 2046.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 439.87 | 141.84 | 298.03 | 180.83 | 1239.80 | 0.00 | 0.00 | 0.00 |
February | 645.43 | 193.68 | 451.75 | 323.62 | 1172.92 | 0.00 | 0.00 | 0.00 |
March | 926.17 | 387.87 | 538.29 | 744.12 | 845.72 | 0.00 | 0.00 | 0.00 |
April | 1225.84 | 541.64 | 684.20 | 1170.78 | 625.12 | 0.00 | 0.00 | 0.00 |
May | 1373.38 | 607.52 | 765.86 | 1496.96 | 442.07 | 0.00 | 0.00 | 0.00 |
June | 1533.84 | 677.88 | 855.96 | 1863.90 | 291.47 | 0.00 | 0.00 | 0.00 |
July | 1472.88 | 648.49 | 824.39 | 1919.82 | 203.94 | 0.00 | 0.00 | 0.00 |
August | 1330.18 | 558.34 | 771.84 | 1698.56 | 264.77 | 0.00 | 0.00 | 0.00 |
September | 1106.94 | 491.00 | 615.94 | 1280.79 | 411.56 | 0.00 | 0.00 | 0.00 |
October | 751.15 | 310.70 | 440.45 | 687.54 | 617.08 | 0.00 | 0.00 | 0.00 |
November | 426.07 | 136.68 | 289.39 | 279.10 | 788.52 | 0.00 | 0.00 | 0.00 |
December | 343.00 | 70.87 | 272.13 | 96.33 | 1212.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 965.99 | 398.17 | 567.82 | 982.05 | 673.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 343.00 | 70.87 | 272.13 | 96.33 | 203.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1533.84 | 677.88 | 855.96 | 1919.82 | 1239.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1550.36 | 904.99 | 645.37 | 1284.38 | 1749.13 | 0.00 | 0.00 | 0.00 |
February | 1770.13 | 853.54 | 916.59 | 1448.55 | 1718.06 | 0.00 | 0.00 | 0.00 |
March | 2160.56 | 1214.00 | 946.55 | 2154.85 | 1277.15 | 0.00 | 0.00 | 0.00 |
April | 1789.28 | 715.00 | 1074.28 | 1857.20 | 1018.53 | 0.00 | 0.00 | 0.00 |
May | 1565.78 | 454.77 | 1111.01 | 1750.79 | 714.10 | 0.00 | 0.00 | 0.00 |
June | 1521.43 | 322.40 | 1199.03 | 1892.05 | 469.09 | 0.00 | 0.00 | 0.00 |
July | 1553.14 | 376.84 | 1176.30 | 2132.86 | 327.54 | 0.00 | 0.00 | 0.00 |
August | 1743.65 | 565.34 | 1178.32 | 2359.92 | 420.72 | 0.00 | 0.00 | 0.00 |
September | 2027.35 | 987.47 | 1039.88 | 2537.61 | 654.92 | 0.00 | 0.00 | 0.00 |
October | 1939.87 | 1108.09 | 831.78 | 2122.79 | 947.36 | 0.00 | 0.00 | 0.00 |
November | 1389.30 | 784.30 | 604.99 | 1347.24 | 1175.63 | 0.00 | 0.00 | 0.00 |
December | 1296.41 | 670.95 | 625.46 | 1020.96 | 1710.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1691.75 | 746.08 | 945.67 | 1827.96 | 1011.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1296.41 | 322.40 | 604.99 | 1020.96 | 327.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2160.56 | 1214.00 | 1199.03 | 2537.61 | 1749.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 377.40 | 88.60 | 288.80 | 112.42 | 1287.44 | 0.00 | 0.00 | 0.00 |
February | 611.66 | 157.20 | 454.46 | 279.26 | 1211.40 | 0.00 | 0.00 | 0.00 |
March | 958.67 | 410.48 | 548.19 | 785.66 | 869.48 | 0.00 | 0.00 | 0.00 |
April | 1173.77 | 481.29 | 692.48 | 1120.90 | 653.15 | 0.00 | 0.00 | 0.00 |
May | 1384.65 | 625.77 | 758.88 | 1522.16 | 467.50 | 0.00 | 0.00 | 0.00 |
June | 1670.62 | 785.79 | 884.83 | 2055.81 | 316.49 | 0.00 | 0.00 | 0.00 |
July | 1493.59 | 654.84 | 838.75 | 1956.26 | 225.36 | 0.00 | 0.00 | 0.00 |
August | 1350.87 | 574.40 | 776.47 | 1743.27 | 283.77 | 0.00 | 0.00 | 0.00 |
September | 1060.85 | 458.14 | 602.72 | 1230.61 | 432.91 | 0.00 | 0.00 | 0.00 |
October | 687.69 | 242.25 | 445.45 | 617.66 | 638.18 | 0.00 | 0.00 | 0.00 |
November | 407.53 | 117.44 | 290.09 | 257.66 | 803.89 | 0.00 | 0.00 | 0.00 |
December | 353.29 | 76.98 | 276.31 | 108.91 | 1231.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 962.47 | 390.56 | 571.91 | 986.31 | 699.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 353.29 | 76.98 | 276.31 | 108.91 | 225.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1670.62 | 785.79 | 884.83 | 2055.81 | 1287.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.18 | 0.00 | 120.18 | 1.57 | 698.52 | 0.00 | 0.00 | 0.00 |
February | 183.10 | 0.00 | 183.10 | 13.98 | 652.26 | 0.00 | 0.00 | 0.00 |
March | 222.05 | 0.00 | 222.05 | 82.25 | 464.97 | 0.00 | 0.00 | 0.00 |
April | 282.94 | 1.13 | 281.81 | 170.51 | 326.43 | 0.00 | 0.00 | 0.00 |
May | 328.77 | 13.94 | 314.82 | 277.80 | 208.39 | 0.00 | 0.00 | 0.00 |
June | 395.44 | 33.66 | 361.77 | 439.17 | 139.19 | 0.00 | 0.00 | 0.00 |
July | 366.82 | 23.68 | 343.14 | 466.95 | 97.48 | 0.00 | 0.00 | 0.00 |
August | 317.40 | 4.83 | 312.57 | 379.41 | 133.46 | 0.00 | 0.00 | 0.00 |
September | 241.55 | 0.05 | 241.50 | 221.41 | 224.18 | 0.00 | 0.00 | 0.00 |
October | 180.57 | 0.00 | 180.57 | 88.31 | 357.72 | 0.00 | 0.00 | 0.00 |
November | 121.34 | 0.00 | 121.34 | 26.61 | 452.17 | 0.00 | 0.00 | 0.00 |
December | 112.48 | 0.00 | 112.48 | 1.93 | 677.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 239.62 | 6.47 | 233.15 | 181.83 | 367.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 112.48 | 0.00 | 112.48 | 1.57 | 97.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 395.44 | 33.66 | 361.77 | 466.95 | 698.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.18 | 0.00 | 120.18 | 1.57 | 698.57 | 0.00 | 0.00 | 0.00 |
February | 183.11 | 0.00 | 183.11 | 13.98 | 652.31 | 0.00 | 0.00 | 0.00 |
March | 222.06 | 0.00 | 222.06 | 82.25 | 465.00 | 0.00 | 0.00 | 0.00 |
April | 282.95 | 1.13 | 281.83 | 170.51 | 326.45 | 0.00 | 0.00 | 0.00 |
May | 328.78 | 13.94 | 314.84 | 277.81 | 208.40 | 0.00 | 0.00 | 0.00 |
June | 395.45 | 33.66 | 361.79 | 439.18 | 139.20 | 0.00 | 0.00 | 0.00 |
July | 366.83 | 23.68 | 343.15 | 466.97 | 97.48 | 0.00 | 0.00 | 0.00 |
August | 317.41 | 4.83 | 312.58 | 379.43 | 133.47 | 0.00 | 0.00 | 0.00 |
September | 241.56 | 0.05 | 241.51 | 221.41 | 224.19 | 0.00 | 0.00 | 0.00 |
October | 180.57 | 0.00 | 180.57 | 88.31 | 357.74 | 0.00 | 0.00 | 0.00 |
November | 121.34 | 0.00 | 121.34 | 26.61 | 452.20 | 0.00 | 0.00 | 0.00 |
December | 112.49 | 0.00 | 112.49 | 1.93 | 677.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 239.63 | 6.47 | 233.16 | 181.83 | 367.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 112.49 | 0.00 | 112.49 | 1.57 | 97.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 395.45 | 33.66 | 361.79 | 466.97 | 698.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.18 | 0.00 | 120.18 | 1.57 | 698.57 | 0.00 | 0.00 | 0.00 |
February | 183.11 | 0.00 | 183.11 | 13.98 | 652.31 | 0.00 | 0.00 | 0.00 |
March | 222.06 | 0.00 | 222.06 | 82.25 | 465.00 | 0.00 | 0.00 | 0.00 |
April | 282.95 | 1.13 | 281.83 | 170.51 | 326.45 | 0.00 | 0.00 | 0.00 |
May | 328.78 | 13.94 | 314.84 | 277.81 | 208.40 | 0.00 | 0.00 | 0.00 |
June | 395.45 | 33.66 | 361.79 | 439.18 | 139.20 | 0.00 | 0.00 | 0.00 |
July | 366.83 | 23.68 | 343.15 | 466.97 | 97.48 | 0.00 | 0.00 | 0.00 |
August | 317.41 | 4.83 | 312.58 | 379.43 | 133.47 | 0.00 | 0.00 | 0.00 |
September | 241.56 | 0.05 | 241.51 | 221.41 | 224.19 | 0.00 | 0.00 | 0.00 |
October | 180.57 | 0.00 | 180.57 | 88.31 | 357.74 | 0.00 | 0.00 | 0.00 |
November | 121.34 | 0.00 | 121.34 | 26.61 | 452.20 | 0.00 | 0.00 | 0.00 |
December | 112.49 | 0.00 | 112.49 | 1.93 | 677.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 239.63 | 6.47 | 233.16 | 181.83 | 367.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 112.49 | 0.00 | 112.49 | 1.57 | 97.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 395.45 | 33.66 | 361.79 | 466.97 | 698.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 423.13 | 136.44 | 286.69 | 172.82 | 1228.30 | 0.00 | 0.00 | 0.00 |
February | 620.87 | 186.31 | 434.56 | 311.28 | 1161.22 | 0.00 | 0.00 | 0.00 |
March | 890.93 | 373.11 | 517.81 | 726.80 | 838.45 | 0.00 | 0.00 | 0.00 |
April | 1179.20 | 521.03 | 658.17 | 1139.37 | 620.49 | 0.00 | 0.00 | 0.00 |
May | 1321.12 | 584.40 | 736.72 | 1461.67 | 426.73 | 0.00 | 0.00 | 0.00 |
June | 1475.47 | 652.08 | 823.39 | 1811.64 | 284.37 | 0.00 | 0.00 | 0.00 |
July | 1416.84 | 623.81 | 793.03 | 1863.51 | 198.78 | 0.00 | 0.00 | 0.00 |
August | 1279.56 | 537.09 | 742.47 | 1643.77 | 265.86 | 0.00 | 0.00 | 0.00 |
September | 1064.82 | 472.31 | 592.51 | 1232.87 | 427.19 | 0.00 | 0.00 | 0.00 |
October | 722.57 | 298.87 | 423.70 | 644.99 | 668.43 | 0.00 | 0.00 | 0.00 |
November | 409.85 | 131.48 | 278.38 | 256.20 | 841.18 | 0.00 | 0.00 | 0.00 |
December | 329.95 | 68.18 | 261.78 | 89.47 | 1226.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 929.24 | 383.02 | 546.22 | 949.62 | 679.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 329.95 | 68.18 | 261.78 | 89.47 | 198.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1475.47 | 652.08 | 823.39 | 1863.51 | 1228.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.73 | 5.39 | 11.34 | 6.83 | 48.57 | 0.00 | 0.00 | 0.00 |
February | 24.55 | 7.37 | 17.18 | 12.31 | 45.91 | 0.00 | 0.00 | 0.00 |
March | 35.23 | 14.75 | 20.47 | 28.74 | 33.15 | 0.00 | 0.00 | 0.00 |
April | 46.62 | 20.60 | 26.02 | 45.05 | 24.53 | 0.00 | 0.00 | 0.00 |
May | 52.24 | 23.11 | 29.13 | 57.79 | 16.87 | 0.00 | 0.00 | 0.00 |
June | 58.34 | 25.78 | 32.56 | 71.63 | 11.24 | 0.00 | 0.00 | 0.00 |
July | 56.02 | 24.66 | 31.36 | 73.68 | 7.86 | 0.00 | 0.00 | 0.00 |
August | 50.59 | 21.24 | 29.36 | 64.99 | 10.51 | 0.00 | 0.00 | 0.00 |
September | 42.10 | 18.67 | 23.43 | 48.75 | 16.89 | 0.00 | 0.00 | 0.00 |
October | 28.57 | 11.82 | 16.75 | 25.50 | 26.43 | 0.00 | 0.00 | 0.00 |
November | 16.21 | 5.20 | 11.01 | 10.13 | 33.26 | 0.00 | 0.00 | 0.00 |
December | 13.05 | 2.70 | 10.35 | 3.54 | 48.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.74 | 15.14 | 21.60 | 37.55 | 26.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.05 | 2.70 | 10.35 | 3.54 | 7.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 58.34 | 25.78 | 32.56 | 73.68 | 48.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 516.78 | 301.66 | 215.12 | 435.84 | 597.26 | 0.00 | 0.00 | 0.00 |
February | 590.03 | 284.51 | 305.52 | 493.57 | 584.86 | 0.00 | 0.00 | 0.00 |
March | 720.17 | 404.66 | 315.51 | 733.98 | 441.67 | 0.00 | 0.00 | 0.00 |
April | 596.42 | 238.33 | 358.09 | 633.90 | 345.26 | 0.00 | 0.00 | 0.00 |
May | 521.92 | 151.59 | 370.33 | 601.52 | 232.52 | 0.00 | 0.00 | 0.00 |
June | 507.14 | 107.46 | 399.68 | 645.03 | 154.53 | 0.00 | 0.00 | 0.00 |
July | 517.71 | 125.61 | 392.10 | 721.93 | 108.75 | 0.00 | 0.00 | 0.00 |
August | 581.21 | 188.44 | 392.77 | 793.65 | 145.82 | 0.00 | 0.00 | 0.00 |
September | 675.77 | 329.15 | 346.62 | 849.41 | 236.20 | 0.00 | 0.00 | 0.00 |
October | 646.61 | 369.36 | 277.26 | 706.29 | 353.91 | 0.00 | 0.00 | 0.00 |
November | 463.09 | 261.43 | 201.66 | 446.27 | 435.38 | 0.00 | 0.00 | 0.00 |
December | 432.13 | 223.65 | 208.48 | 342.67 | 596.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 563.91 | 248.69 | 315.22 | 617.73 | 351.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 432.13 | 107.46 | 201.66 | 342.67 | 108.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 720.17 | 404.66 | 399.68 | 849.41 | 597.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 516.78 | 301.66 | 215.12 | 435.84 | 597.26 | 0.00 | 0.00 | 0.00 |
February | 590.03 | 284.51 | 305.52 | 493.57 | 584.86 | 0.00 | 0.00 | 0.00 |
March | 720.17 | 404.66 | 315.51 | 733.98 | 441.67 | 0.00 | 0.00 | 0.00 |
April | 596.42 | 238.33 | 358.09 | 633.90 | 345.26 | 0.00 | 0.00 | 0.00 |
May | 521.92 | 151.59 | 370.33 | 601.52 | 232.52 | 0.00 | 0.00 | 0.00 |
June | 507.14 | 107.46 | 399.68 | 645.03 | 154.53 | 0.00 | 0.00 | 0.00 |
July | 517.71 | 125.61 | 392.10 | 721.93 | 108.75 | 0.00 | 0.00 | 0.00 |
August | 581.21 | 188.44 | 392.77 | 793.65 | 145.82 | 0.00 | 0.00 | 0.00 |
September | 675.77 | 329.15 | 346.62 | 849.41 | 236.20 | 0.00 | 0.00 | 0.00 |
October | 646.61 | 369.36 | 277.26 | 706.29 | 353.91 | 0.00 | 0.00 | 0.00 |
November | 463.09 | 261.43 | 201.66 | 446.27 | 435.38 | 0.00 | 0.00 | 0.00 |
December | 432.13 | 223.65 | 208.48 | 342.67 | 596.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 563.91 | 248.69 | 315.22 | 617.73 | 351.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 432.13 | 107.46 | 201.66 | 342.67 | 108.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 720.17 | 404.66 | 399.68 | 849.41 | 597.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 516.75 | 301.64 | 215.11 | 435.81 | 597.22 | 0.00 | 0.00 | 0.00 |
February | 589.99 | 284.49 | 305.51 | 493.54 | 584.82 | 0.00 | 0.00 | 0.00 |
March | 720.13 | 404.63 | 315.49 | 733.93 | 441.64 | 0.00 | 0.00 | 0.00 |
April | 596.38 | 238.31 | 358.07 | 633.86 | 345.23 | 0.00 | 0.00 | 0.00 |
May | 521.89 | 151.58 | 370.31 | 601.49 | 232.51 | 0.00 | 0.00 | 0.00 |
June | 507.11 | 107.46 | 399.65 | 644.99 | 154.52 | 0.00 | 0.00 | 0.00 |
July | 517.67 | 125.60 | 392.07 | 721.88 | 108.74 | 0.00 | 0.00 | 0.00 |
August | 581.17 | 188.43 | 392.74 | 793.60 | 145.81 | 0.00 | 0.00 | 0.00 |
September | 675.73 | 329.13 | 346.60 | 849.36 | 236.18 | 0.00 | 0.00 | 0.00 |
October | 646.57 | 369.33 | 277.24 | 706.25 | 353.89 | 0.00 | 0.00 | 0.00 |
November | 463.06 | 261.41 | 201.65 | 446.24 | 435.35 | 0.00 | 0.00 | 0.00 |
December | 432.10 | 223.63 | 208.47 | 342.65 | 596.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 563.87 | 248.67 | 315.20 | 617.69 | 351.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 432.10 | 107.46 | 201.65 | 342.65 | 108.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 720.13 | 404.63 | 399.65 | 849.36 | 597.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 363.04 | 85.23 | 277.81 | 108.48 | 1270.26 | 0.00 | 0.00 | 0.00 |
February | 588.39 | 151.22 | 437.17 | 273.11 | 1196.61 | 0.00 | 0.00 | 0.00 |
March | 922.20 | 394.86 | 527.34 | 772.41 | 863.89 | 0.00 | 0.00 | 0.00 |
April | 1129.11 | 462.98 | 666.13 | 1097.02 | 647.41 | 0.00 | 0.00 | 0.00 |
May | 1331.96 | 601.96 | 730.00 | 1487.90 | 455.15 | 0.00 | 0.00 | 0.00 |
June | 1607.05 | 755.89 | 851.16 | 1998.96 | 314.04 | 0.00 | 0.00 | 0.00 |
July | 1436.77 | 629.93 | 806.84 | 1900.61 | 222.66 | 0.00 | 0.00 | 0.00 |
August | 1299.47 | 552.55 | 746.93 | 1687.21 | 287.73 | 0.00 | 0.00 | 0.00 |
September | 1020.49 | 440.70 | 579.79 | 1185.66 | 450.88 | 0.00 | 0.00 | 0.00 |
October | 661.53 | 233.03 | 428.50 | 580.86 | 689.13 | 0.00 | 0.00 | 0.00 |
November | 392.02 | 112.97 | 279.06 | 238.06 | 855.37 | 0.00 | 0.00 | 0.00 |
December | 339.85 | 74.05 | 265.80 | 103.12 | 1243.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 925.85 | 375.70 | 550.15 | 956.43 | 705.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 339.85 | 74.05 | 265.80 | 103.12 | 222.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1607.05 | 755.89 | 851.16 | 1998.96 | 1270.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.35 | 3.37 | 10.98 | 4.29 | 50.22 | 0.00 | 0.00 | 0.00 |
February | 23.26 | 5.98 | 17.29 | 10.80 | 47.31 | 0.00 | 0.00 | 0.00 |
March | 36.46 | 15.61 | 20.85 | 30.54 | 34.16 | 0.00 | 0.00 | 0.00 |
April | 44.64 | 18.31 | 26.34 | 43.38 | 25.60 | 0.00 | 0.00 | 0.00 |
May | 52.66 | 23.80 | 28.86 | 58.83 | 18.00 | 0.00 | 0.00 | 0.00 |
June | 63.54 | 29.89 | 33.65 | 79.04 | 12.42 | 0.00 | 0.00 | 0.00 |
July | 56.81 | 24.91 | 31.90 | 75.15 | 8.80 | 0.00 | 0.00 | 0.00 |
August | 51.38 | 21.85 | 29.53 | 66.71 | 11.38 | 0.00 | 0.00 | 0.00 |
September | 40.35 | 17.42 | 22.92 | 46.88 | 17.83 | 0.00 | 0.00 | 0.00 |
October | 26.16 | 9.21 | 16.94 | 22.97 | 27.25 | 0.00 | 0.00 | 0.00 |
November | 15.50 | 4.47 | 11.03 | 9.41 | 33.82 | 0.00 | 0.00 | 0.00 |
December | 13.44 | 2.93 | 10.51 | 4.08 | 49.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.61 | 14.85 | 21.75 | 37.82 | 27.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.44 | 2.93 | 10.51 | 4.08 | 8.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.54 | 29.89 | 33.65 | 79.04 | 50.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 360.55 | 0.00 | 360.55 | 4.82 | 2113.98 | 0.00 | 0.00 | 0.00 |
February | 549.34 | 0.00 | 549.34 | 38.58 | 1978.11 | 0.00 | 0.00 | 0.00 |
March | 666.20 | 0.00 | 666.20 | 223.11 | 1445.67 | 0.00 | 0.00 | 0.00 |
April | 848.87 | 3.39 | 845.48 | 465.71 | 1040.64 | 0.00 | 0.00 | 0.00 |
May | 986.34 | 41.83 | 944.52 | 776.20 | 679.02 | 0.00 | 0.00 | 0.00 |
June | 1186.36 | 100.99 | 1085.38 | 1283.21 | 440.49 | 0.00 | 0.00 | 0.00 |
July | 1100.51 | 71.04 | 1029.47 | 1375.43 | 308.71 | 0.00 | 0.00 | 0.00 |
August | 952.25 | 14.49 | 937.76 | 1123.64 | 410.40 | 0.00 | 0.00 | 0.00 |
September | 724.68 | 0.15 | 724.53 | 654.96 | 674.51 | 0.00 | 0.00 | 0.00 |
October | 541.73 | 0.00 | 541.73 | 264.30 | 1052.43 | 0.00 | 0.00 | 0.00 |
November | 364.03 | 0.00 | 364.03 | 80.16 | 1333.06 | 0.00 | 0.00 | 0.00 |
December | 337.46 | 0.00 | 337.46 | 5.92 | 2019.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 718.89 | 19.41 | 699.49 | 527.61 | 1120.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 337.46 | 0.00 | 337.46 | 4.82 | 308.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1186.36 | 100.99 | 1085.38 | 1375.43 | 2113.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 439.87 | 141.84 | 298.03 | 176.30 | 1279.75 | 0.00 | 0.00 | 0.00 |
February | 645.43 | 193.68 | 451.75 | 315.45 | 1213.06 | 0.00 | 0.00 | 0.00 |
March | 926.17 | 387.87 | 538.29 | 729.78 | 892.65 | 0.00 | 0.00 | 0.00 |
April | 1225.84 | 541.64 | 684.20 | 1154.16 | 663.16 | 0.00 | 0.00 | 0.00 |
May | 1373.38 | 607.52 | 765.86 | 1489.35 | 462.43 | 0.00 | 0.00 | 0.00 |
June | 1533.84 | 677.88 | 855.96 | 1861.87 | 300.73 | 0.00 | 0.00 | 0.00 |
July | 1472.88 | 648.49 | 824.39 | 1920.42 | 208.93 | 0.00 | 0.00 | 0.00 |
August | 1330.18 | 558.34 | 771.84 | 1696.73 | 273.99 | 0.00 | 0.00 | 0.00 |
September | 1106.94 | 491.00 | 615.94 | 1273.06 | 433.72 | 0.00 | 0.00 | 0.00 |
October | 751.15 | 310.70 | 440.45 | 668.14 | 668.58 | 0.00 | 0.00 | 0.00 |
November | 426.07 | 136.68 | 289.39 | 265.45 | 851.69 | 0.00 | 0.00 | 0.00 |
December | 343.00 | 70.87 | 272.13 | 92.25 | 1262.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 965.99 | 398.17 | 567.82 | 973.78 | 706.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 343.00 | 70.87 | 272.13 | 92.25 | 208.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1533.84 | 677.88 | 855.96 | 1920.42 | 1279.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1550.36 | 904.99 | 645.37 | 1272.04 | 1815.49 | 0.00 | 0.00 | 0.00 |
February | 1770.13 | 853.54 | 916.59 | 1434.33 | 1783.42 | 0.00 | 0.00 | 0.00 |
March | 2160.56 | 1214.00 | 946.55 | 2138.32 | 1348.58 | 0.00 | 0.00 | 0.00 |
April | 1789.28 | 715.00 | 1074.28 | 1841.54 | 1080.16 | 0.00 | 0.00 | 0.00 |
May | 1565.78 | 454.77 | 1111.01 | 1745.66 | 749.63 | 0.00 | 0.00 | 0.00 |
June | 1521.43 | 322.40 | 1199.03 | 1895.07 | 486.51 | 0.00 | 0.00 | 0.00 |
July | 1553.14 | 376.84 | 1176.30 | 2139.72 | 336.93 | 0.00 | 0.00 | 0.00 |
August | 1743.65 | 565.34 | 1178.32 | 2363.33 | 436.19 | 0.00 | 0.00 | 0.00 |
September | 2027.35 | 987.47 | 1039.88 | 2533.20 | 689.96 | 0.00 | 0.00 | 0.00 |
October | 1939.87 | 1108.09 | 831.78 | 2100.43 | 1023.16 | 0.00 | 0.00 | 0.00 |
November | 1389.30 | 784.30 | 604.99 | 1325.87 | 1267.84 | 0.00 | 0.00 | 0.00 |
December | 1296.41 | 670.95 | 625.46 | 1007.23 | 1788.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1691.75 | 746.08 | 945.67 | 1818.63 | 1063.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1296.41 | 322.40 | 604.99 | 1007.23 | 336.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2160.56 | 1214.00 | 1199.03 | 2533.20 | 1815.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 377.40 | 88.60 | 288.80 | 109.31 | 1330.12 | 0.00 | 0.00 | 0.00 |
February | 611.66 | 157.20 | 454.46 | 274.22 | 1253.80 | 0.00 | 0.00 | 0.00 |
March | 958.67 | 410.48 | 548.19 | 777.08 | 917.54 | 0.00 | 0.00 | 0.00 |
April | 1173.77 | 481.29 | 692.48 | 1109.75 | 694.35 | 0.00 | 0.00 | 0.00 |
May | 1384.65 | 625.77 | 758.88 | 1518.23 | 491.13 | 0.00 | 0.00 | 0.00 |
June | 1670.62 | 785.79 | 884.83 | 2058.84 | 328.21 | 0.00 | 0.00 | 0.00 |
July | 1493.59 | 654.84 | 838.75 | 1961.39 | 231.91 | 0.00 | 0.00 | 0.00 |
August | 1350.87 | 574.40 | 776.47 | 1745.38 | 294.04 | 0.00 | 0.00 | 0.00 |
September | 1060.85 | 458.14 | 602.72 | 1226.56 | 457.43 | 0.00 | 0.00 | 0.00 |
October | 687.69 | 242.25 | 445.45 | 602.85 | 692.17 | 0.00 | 0.00 | 0.00 |
November | 407.53 | 117.44 | 290.09 | 246.70 | 867.36 | 0.00 | 0.00 | 0.00 |
December | 353.29 | 76.98 | 276.31 | 105.24 | 1284.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 962.47 | 390.56 | 571.91 | 981.75 | 734.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 353.29 | 76.98 | 276.31 | 105.24 | 231.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1670.62 | 785.79 | 884.83 | 2058.84 | 1330.12 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.965694E+09 | 0.00 | 0.965694E+09 | 19893161.15 | 0.548043E+10 |
February | 0.132897E+10 | 0.00 | 0.132897E+10 | 0.107926E+09 | 0.462025E+10 |
March | 0.178434E+10 | 0.00 | 0.178434E+10 | 0.626183E+09 | 0.367638E+10 |
April | 0.220027E+10 | 8779947.19 | 0.219149E+10 | 0.125370E+10 | 0.253415E+10 |
May | 0.264182E+10 | 0.112028E+09 | 0.252980E+10 | 0.210973E+10 | 0.173135E+10 |
June | 0.307506E+10 | 0.261765E+09 | 0.281329E+10 | 0.332775E+10 | 0.110541E+10 |
July | 0.294761E+10 | 0.190275E+09 | 0.275733E+10 | 0.367177E+10 | 0.807306E+09 |
August | 0.255050E+10 | 38800324.88 | 0.251170E+10 | 0.300981E+10 | 0.106104E+10 |
September | 0.187837E+10 | 390244.61 | 0.187798E+10 | 0.171941E+10 | 0.164953E+10 |
October | 0.145097E+10 | 0.00 | 0.145097E+10 | 0.765175E+09 | 0.259486E+10 |
November | 0.943564E+09 | 0.00 | 0.943564E+09 | 0.240792E+09 | 0.320078E+10 |
December | 0.903860E+09 | 0.00 | 0.903860E+09 | 22457914.45 | 0.518612E+10 |
Annual Sum or Average | 0.226710E+11 | 0.612038E+09 | 0.220590E+11 | 0.168746E+11 | 0.336476E+11 |
Minimum of Months | 0.903860E+09 | 0.00 | 0.903860E+09 | 19893161.15 | 0.807306E+09 |
Maximum of Months | 0.307506E+10 | 0.261765E+09 | 0.281329E+10 | 0.367177E+10 | 0.548043E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117815E+10 | 0.379902E+09 | 0.798249E+09 | 0.484331E+09 | 0.332069E+10 |
February | 0.156141E+10 | 0.468541E+09 | 0.109287E+10 | 0.782901E+09 | 0.283752E+10 |
March | 0.248065E+10 | 0.103888E+10 | 0.144177E+10 | 0.199306E+10 | 0.226519E+10 |
April | 0.317738E+10 | 0.140394E+10 | 0.177344E+10 | 0.303466E+10 | 0.162030E+10 |
May | 0.367846E+10 | 0.162718E+10 | 0.205128E+10 | 0.400947E+10 | 0.118404E+10 |
June | 0.397570E+10 | 0.175706E+10 | 0.221864E+10 | 0.483122E+10 | 0.755485E+09 |
July | 0.394497E+10 | 0.173692E+10 | 0.220806E+10 | 0.514205E+10 | 0.546240E+09 |
August | 0.356274E+10 | 0.149545E+10 | 0.206730E+10 | 0.454943E+10 | 0.709154E+09 |
September | 0.286918E+10 | 0.127266E+10 | 0.159652E+10 | 0.331980E+10 | 0.106677E+10 |
October | 0.201188E+10 | 0.832167E+09 | 0.117971E+10 | 0.184151E+10 | 0.165279E+10 |
November | 0.110436E+10 | 0.354266E+09 | 0.750094E+09 | 0.723428E+09 | 0.204384E+10 |
December | 0.918702E+09 | 0.189824E+09 | 0.728878E+09 | 0.257998E+09 | 0.324777E+10 |
Annual Sum or Average | 0.304636E+11 | 0.125568E+11 | 0.179068E+11 | 0.309699E+11 | 0.212498E+11 |
Minimum of Months | 0.918702E+09 | 0.189824E+09 | 0.728878E+09 | 0.257998E+09 | 0.546240E+09 |
Maximum of Months | 0.397570E+10 | 0.175706E+10 | 0.221864E+10 | 0.514205E+10 | 0.332069E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.415250E+10 | 0.242393E+10 | 0.172856E+10 | 0.344008E+10 | 0.468488E+10 |
February | 0.428229E+10 | 0.206488E+10 | 0.221741E+10 | 0.350432E+10 | 0.415634E+10 |
March | 0.578684E+10 | 0.325159E+10 | 0.253525E+10 | 0.577156E+10 | 0.342072E+10 |
April | 0.463782E+10 | 0.185329E+10 | 0.278453E+10 | 0.481386E+10 | 0.264004E+10 |
May | 0.419379E+10 | 0.121805E+10 | 0.297573E+10 | 0.468932E+10 | 0.191263E+10 |
June | 0.394356E+10 | 0.835659E+09 | 0.310790E+10 | 0.490420E+10 | 0.121587E+10 |
July | 0.415992E+10 | 0.100933E+10 | 0.315059E+10 | 0.571265E+10 | 0.877291E+09 |
August | 0.467020E+10 | 0.151420E+10 | 0.315600E+10 | 0.632080E+10 | 0.112686E+10 |
September | 0.525489E+10 | 0.255952E+10 | 0.269537E+10 | 0.657747E+10 | 0.169754E+10 |
October | 0.519575E+10 | 0.296792E+10 | 0.222784E+10 | 0.568569E+10 | 0.253740E+10 |
November | 0.360106E+10 | 0.203292E+10 | 0.156814E+10 | 0.349204E+10 | 0.304724E+10 |
December | 0.347231E+10 | 0.179708E+10 | 0.167523E+10 | 0.273454E+10 | 0.458256E+10 |
Annual Sum or Average | 0.533509E+11 | 0.235284E+11 | 0.298226E+11 | 0.576465E+11 | 0.318994E+11 |
Minimum of Months | 0.347231E+10 | 0.835659E+09 | 0.156814E+10 | 0.273454E+10 | 0.877291E+09 |
Maximum of Months | 0.578684E+10 | 0.325159E+10 | 0.315600E+10 | 0.657747E+10 | 0.468488E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101083E+10 | 0.237304E+09 | 0.773529E+09 | 0.301105E+09 | 0.344828E+10 |
February | 0.147974E+10 | 0.380304E+09 | 0.109943E+10 | 0.675594E+09 | 0.293062E+10 |
March | 0.256771E+10 | 0.109944E+10 | 0.146828E+10 | 0.210430E+10 | 0.232883E+10 |
April | 0.304240E+10 | 0.124751E+10 | 0.179490E+10 | 0.290537E+10 | 0.169297E+10 |
May | 0.370864E+10 | 0.167606E+10 | 0.203257E+10 | 0.407694E+10 | 0.125215E+10 |
June | 0.433024E+10 | 0.203677E+10 | 0.229347E+10 | 0.532866E+10 | 0.820340E+09 |
July | 0.400044E+10 | 0.175393E+10 | 0.224651E+10 | 0.523964E+10 | 0.603595E+09 |
August | 0.361817E+10 | 0.153848E+10 | 0.207969E+10 | 0.466918E+10 | 0.760063E+09 |
September | 0.274972E+10 | 0.118749E+10 | 0.156224E+10 | 0.318973E+10 | 0.112210E+10 |
October | 0.184192E+10 | 0.648830E+09 | 0.119309E+10 | 0.165433E+10 | 0.170929E+10 |
November | 0.105632E+10 | 0.304393E+09 | 0.751925E+09 | 0.667865E+09 | 0.208369E+10 |
December | 0.946258E+09 | 0.206179E+09 | 0.740079E+09 | 0.291702E+09 | 0.329968E+10 |
Annual Sum or Average | 0.303524E+11 | 0.123167E+11 | 0.180357E+11 | 0.311044E+11 | 0.220516E+11 |
Minimum of Months | 0.946258E+09 | 0.206179E+09 | 0.740079E+09 | 0.291702E+09 | 0.603595E+09 |
Maximum of Months | 0.433024E+10 | 0.203677E+10 | 0.229347E+10 | 0.532866E+10 | 0.344828E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.321883E+09 | 0.00 | 0.321883E+09 | 4195862.10 | 0.187093E+10 |
February | 0.442968E+09 | 0.00 | 0.442968E+09 | 33818564.16 | 0.157796E+10 |
March | 0.594751E+09 | 0.00 | 0.594751E+09 | 0.220285E+09 | 0.124538E+10 |
April | 0.733388E+09 | 2926510.60 | 0.730462E+09 | 0.441961E+09 | 0.846094E+09 |
May | 0.880567E+09 | 37341032.44 | 0.843226E+09 | 0.744062E+09 | 0.558141E+09 |
June | 0.102497E+10 | 87250714.54 | 0.937720E+09 | 0.113832E+10 | 0.360784E+09 |
July | 0.982490E+09 | 63421910.74 | 0.919068E+09 | 0.125069E+10 | 0.261089E+09 |
August | 0.850126E+09 | 12932829.72 | 0.837194E+09 | 0.101622E+10 | 0.357472E+09 |
September | 0.626095E+09 | 130075.38 | 0.625965E+09 | 0.573887E+09 | 0.581065E+09 |
October | 0.483634E+09 | 0.00 | 0.483634E+09 | 0.236530E+09 | 0.958111E+09 |
November | 0.314506E+09 | 0.00 | 0.314506E+09 | 68978647.98 | 0.117204E+10 |
December | 0.301273E+09 | 0.00 | 0.301273E+09 | 5178672.08 | 0.181525E+10 |
Annual Sum or Average | 0.755665E+10 | 0.204003E+09 | 0.735265E+10 | 0.573414E+10 | 0.116043E+11 |
Minimum of Months | 0.301273E+09 | 0.00 | 0.301273E+09 | 4195862.10 | 0.261089E+09 |
Maximum of Months | 0.102497E+10 | 87250714.54 | 0.937720E+09 | 0.125069E+10 | 0.187093E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.321894E+09 | 0.00 | 0.321894E+09 | 4194993.40 | 0.187105E+10 |
February | 0.442984E+09 | 0.00 | 0.442984E+09 | 33815144.29 | 0.157807E+10 |
March | 0.594774E+09 | 0.00 | 0.594774E+09 | 0.220287E+09 | 0.124546E+10 |
April | 0.733417E+09 | 2926589.26 | 0.730491E+09 | 0.441971E+09 | 0.846148E+09 |
May | 0.880602E+09 | 37342036.17 | 0.843260E+09 | 0.744085E+09 | 0.558175E+09 |
June | 0.102501E+10 | 87253059.87 | 0.937758E+09 | 0.113836E+10 | 0.360805E+09 |
July | 0.982529E+09 | 63423615.54 | 0.919105E+09 | 0.125074E+10 | 0.261103E+09 |
August | 0.850160E+09 | 12933177.36 | 0.837227E+09 | 0.101626E+10 | 0.357492E+09 |
September | 0.626120E+09 | 130078.88 | 0.625990E+09 | 0.573907E+09 | 0.581100E+09 |
October | 0.483652E+09 | 0.00 | 0.483652E+09 | 0.236533E+09 | 0.958171E+09 |
November | 0.314518E+09 | 0.00 | 0.314518E+09 | 68978011.32 | 0.117211E+10 |
December | 0.301283E+09 | 0.00 | 0.301283E+09 | 5177989.47 | 0.181537E+10 |
Annual Sum or Average | 0.755695E+10 | 0.204009E+09 | 0.735294E+10 | 0.573432E+10 | 0.116051E+11 |
Minimum of Months | 0.301283E+09 | 0.00 | 0.301283E+09 | 4194993.40 | 0.261103E+09 |
Maximum of Months | 0.102501E+10 | 87253059.87 | 0.937758E+09 | 0.125074E+10 | 0.187105E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.321894E+09 | 0.00 | 0.321894E+09 | 4194993.40 | 0.187105E+10 |
February | 0.442984E+09 | 0.00 | 0.442984E+09 | 33815144.29 | 0.157807E+10 |
March | 0.594774E+09 | 0.00 | 0.594774E+09 | 0.220287E+09 | 0.124546E+10 |
April | 0.733417E+09 | 2926589.26 | 0.730491E+09 | 0.441971E+09 | 0.846148E+09 |
May | 0.880602E+09 | 37342036.17 | 0.843260E+09 | 0.744085E+09 | 0.558175E+09 |
June | 0.102501E+10 | 87253059.87 | 0.937758E+09 | 0.113836E+10 | 0.360805E+09 |
July | 0.982529E+09 | 63423615.54 | 0.919105E+09 | 0.125074E+10 | 0.261103E+09 |
August | 0.850160E+09 | 12933177.36 | 0.837227E+09 | 0.101626E+10 | 0.357492E+09 |
September | 0.626120E+09 | 130078.88 | 0.625990E+09 | 0.573907E+09 | 0.581100E+09 |
October | 0.483652E+09 | 0.00 | 0.483652E+09 | 0.236533E+09 | 0.958171E+09 |
November | 0.314518E+09 | 0.00 | 0.314518E+09 | 68978011.32 | 0.117211E+10 |
December | 0.301283E+09 | 0.00 | 0.301283E+09 | 5177989.47 | 0.181537E+10 |
Annual Sum or Average | 0.755695E+10 | 0.204009E+09 | 0.735294E+10 | 0.573432E+10 | 0.116051E+11 |
Minimum of Months | 0.301283E+09 | 0.00 | 0.301283E+09 | 4194993.40 | 0.261103E+09 |
Maximum of Months | 0.102501E+10 | 87253059.87 | 0.937758E+09 | 0.125074E+10 | 0.187105E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.113332E+10 | 0.365445E+09 | 0.767877E+09 | 0.462888E+09 | 0.328989E+10 |
February | 0.150200E+10 | 0.450711E+09 | 0.105129E+10 | 0.753049E+09 | 0.280922E+10 |
March | 0.238626E+10 | 0.999346E+09 | 0.138691E+10 | 0.194667E+10 | 0.224571E+10 |
April | 0.305648E+10 | 0.135051E+10 | 0.170597E+10 | 0.295324E+10 | 0.160830E+10 |
May | 0.353850E+10 | 0.156526E+10 | 0.197324E+10 | 0.391492E+10 | 0.114295E+10 |
June | 0.382443E+10 | 0.169020E+10 | 0.213423E+10 | 0.469576E+10 | 0.737088E+09 |
July | 0.379487E+10 | 0.167082E+10 | 0.212405E+10 | 0.499123E+10 | 0.532410E+09 |
August | 0.342718E+10 | 0.143854E+10 | 0.198864E+10 | 0.440267E+10 | 0.712077E+09 |
September | 0.276001E+10 | 0.122423E+10 | 0.153578E+10 | 0.319560E+10 | 0.110728E+10 |
October | 0.193532E+10 | 0.800499E+09 | 0.113482E+10 | 0.172755E+10 | 0.179033E+10 |
November | 0.106234E+10 | 0.340785E+09 | 0.721554E+09 | 0.664082E+09 | 0.218034E+10 |
December | 0.883745E+09 | 0.182600E+09 | 0.701145E+09 | 0.239627E+09 | 0.328456E+10 |
Annual Sum or Average | 0.293044E+11 | 0.120789E+11 | 0.172255E+11 | 0.299473E+11 | 0.214402E+11 |
Minimum of Months | 0.883745E+09 | 0.182600E+09 | 0.701145E+09 | 0.239627E+09 | 0.532410E+09 |
Maximum of Months | 0.382443E+10 | 0.169020E+10 | 0.213423E+10 | 0.499123E+10 | 0.328989E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44810523.56 | 14449365.94 | 30361157.62 | 18302183.49 | 0.130079E+09 |
February | 59387722.53 | 17820726.31 | 41566996.22 | 29774864.45 | 0.111074E+09 |
March | 94350443.65 | 39513227.60 | 54837216.06 | 76969634.86 | 88793321.51 |
April | 0.120850E+09 | 53398009.34 | 67452396.70 | 0.116768E+09 | 63590681.81 |
May | 0.139909E+09 | 61888992.73 | 78020017.97 | 0.154793E+09 | 45191378.34 |
June | 0.151214E+09 | 66829025.98 | 84385336.57 | 0.185666E+09 | 29143779.58 |
July | 0.150046E+09 | 66062729.07 | 83982888.72 | 0.197349E+09 | 21050992.76 |
August | 0.135508E+09 | 56878487.95 | 78629175.06 | 0.174078E+09 | 28154865.65 |
September | 0.109128E+09 | 48404925.38 | 60723331.69 | 0.126351E+09 | 43781022.02 |
October | 76520973.79 | 31651024.14 | 44869949.65 | 68305801.74 | 70787976.78 |
November | 42003934.70 | 13474328.15 | 28529606.55 | 26257213.41 | 86208662.99 |
December | 34942489.26 | 7219842.68 | 27722646.58 | 9474647.82 | 0.129868E+09 |
Annual Sum or Average | 0.115867E+10 | 0.477591E+09 | 0.681081E+09 | 0.118409E+10 | 0.847724E+09 |
Minimum of Months | 34942489.26 | 7219842.68 | 27722646.58 | 9474647.82 | 21050992.76 |
Maximum of Months | 0.151214E+09 | 66829025.98 | 84385336.57 | 0.197349E+09 | 0.130079E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138414E+10 | 0.807962E+09 | 0.576178E+09 | 0.116734E+10 | 0.159970E+10 |
February | 0.142741E+10 | 0.688280E+09 | 0.739125E+09 | 0.119404E+10 | 0.141489E+10 |
March | 0.192891E+10 | 0.108384E+10 | 0.845073E+09 | 0.196589E+10 | 0.118296E+10 |
April | 0.154592E+10 | 0.617749E+09 | 0.928168E+09 | 0.164307E+10 | 0.894905E+09 |
May | 0.139791E+10 | 0.406009E+09 | 0.991903E+09 | 0.161112E+10 | 0.622786E+09 |
June | 0.131451E+10 | 0.278547E+09 | 0.103596E+10 | 0.167191E+10 | 0.400545E+09 |
July | 0.138663E+10 | 0.336438E+09 | 0.105019E+10 | 0.193361E+10 | 0.291279E+09 |
August | 0.155671E+10 | 0.504722E+09 | 0.105199E+10 | 0.212570E+10 | 0.390575E+09 |
September | 0.175160E+10 | 0.853156E+09 | 0.898445E+09 | 0.220168E+10 | 0.612226E+09 |
October | 0.173189E+10 | 0.989285E+09 | 0.742603E+09 | 0.189173E+10 | 0.947906E+09 |
November | 0.120033E+10 | 0.677625E+09 | 0.522706E+09 | 0.115673E+10 | 0.112850E+10 |
December | 0.115742E+10 | 0.599014E+09 | 0.558402E+09 | 0.917815E+09 | 0.159655E+10 |
Annual Sum or Average | 0.177834E+11 | 0.784263E+10 | 0.994074E+10 | 0.194806E+11 | 0.110828E+11 |
Minimum of Months | 0.115742E+10 | 0.278547E+09 | 0.522706E+09 | 0.917815E+09 | 0.291279E+09 |
Maximum of Months | 0.192891E+10 | 0.108384E+10 | 0.105199E+10 | 0.220168E+10 | 0.159970E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138414E+10 | 0.807962E+09 | 0.576178E+09 | 0.116734E+10 | 0.159970E+10 |
February | 0.142741E+10 | 0.688280E+09 | 0.739125E+09 | 0.119404E+10 | 0.141489E+10 |
March | 0.192891E+10 | 0.108384E+10 | 0.845073E+09 | 0.196589E+10 | 0.118296E+10 |
April | 0.154592E+10 | 0.617749E+09 | 0.928168E+09 | 0.164307E+10 | 0.894905E+09 |
May | 0.139791E+10 | 0.406009E+09 | 0.991903E+09 | 0.161112E+10 | 0.622786E+09 |
June | 0.131451E+10 | 0.278547E+09 | 0.103596E+10 | 0.167191E+10 | 0.400545E+09 |
July | 0.138663E+10 | 0.336438E+09 | 0.105019E+10 | 0.193361E+10 | 0.291279E+09 |
August | 0.155671E+10 | 0.504722E+09 | 0.105199E+10 | 0.212570E+10 | 0.390575E+09 |
September | 0.175160E+10 | 0.853156E+09 | 0.898445E+09 | 0.220168E+10 | 0.612226E+09 |
October | 0.173189E+10 | 0.989285E+09 | 0.742603E+09 | 0.189173E+10 | 0.947906E+09 |
November | 0.120033E+10 | 0.677625E+09 | 0.522706E+09 | 0.115673E+10 | 0.112850E+10 |
December | 0.115742E+10 | 0.599014E+09 | 0.558402E+09 | 0.917815E+09 | 0.159655E+10 |
Annual Sum or Average | 0.177834E+11 | 0.784263E+10 | 0.994074E+10 | 0.194806E+11 | 0.110828E+11 |
Minimum of Months | 0.115742E+10 | 0.278547E+09 | 0.522706E+09 | 0.917815E+09 | 0.291279E+09 |
Maximum of Months | 0.192891E+10 | 0.108384E+10 | 0.105199E+10 | 0.220168E+10 | 0.159970E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138405E+10 | 0.807911E+09 | 0.576142E+09 | 0.116727E+10 | 0.159960E+10 |
February | 0.142732E+10 | 0.688237E+09 | 0.739078E+09 | 0.119396E+10 | 0.141480E+10 |
March | 0.192879E+10 | 0.108377E+10 | 0.845020E+09 | 0.196576E+10 | 0.118289E+10 |
April | 0.154582E+10 | 0.617710E+09 | 0.928109E+09 | 0.164297E+10 | 0.894849E+09 |
May | 0.139782E+10 | 0.405983E+09 | 0.991840E+09 | 0.161102E+10 | 0.622747E+09 |
June | 0.131442E+10 | 0.278530E+09 | 0.103589E+10 | 0.167181E+10 | 0.400519E+09 |
July | 0.138654E+10 | 0.336416E+09 | 0.105012E+10 | 0.193349E+10 | 0.291261E+09 |
August | 0.155661E+10 | 0.504690E+09 | 0.105192E+10 | 0.212557E+10 | 0.390550E+09 |
September | 0.175149E+10 | 0.853102E+09 | 0.898389E+09 | 0.220154E+10 | 0.612187E+09 |
October | 0.173178E+10 | 0.989222E+09 | 0.742556E+09 | 0.189161E+10 | 0.947846E+09 |
November | 0.120026E+10 | 0.677582E+09 | 0.522673E+09 | 0.115665E+10 | 0.112843E+10 |
December | 0.115734E+10 | 0.598976E+09 | 0.558367E+09 | 0.917757E+09 | 0.159645E+10 |
Annual Sum or Average | 0.177822E+11 | 0.784213E+10 | 0.994011E+10 | 0.194794E+11 | 0.110821E+11 |
Minimum of Months | 0.115734E+10 | 0.278530E+09 | 0.522673E+09 | 0.917757E+09 | 0.291261E+09 |
Maximum of Months | 0.192879E+10 | 0.108377E+10 | 0.105192E+10 | 0.220154E+10 | 0.159960E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.972373E+09 | 0.228274E+09 | 0.744099E+09 | 0.290556E+09 | 0.340226E+10 |
February | 0.142344E+10 | 0.365833E+09 | 0.105761E+10 | 0.660717E+09 | 0.289484E+10 |
March | 0.247002E+10 | 0.105760E+10 | 0.141242E+10 | 0.206883E+10 | 0.231384E+10 |
April | 0.292665E+10 | 0.120004E+10 | 0.172661E+10 | 0.284349E+10 | 0.167808E+10 |
May | 0.356753E+10 | 0.161229E+10 | 0.195524E+10 | 0.398518E+10 | 0.121908E+10 |
June | 0.416548E+10 | 0.195927E+10 | 0.220622E+10 | 0.518131E+10 | 0.813986E+09 |
July | 0.384824E+10 | 0.168719E+10 | 0.216104E+10 | 0.509060E+10 | 0.596365E+09 |
August | 0.348050E+10 | 0.147994E+10 | 0.200056E+10 | 0.451901E+10 | 0.770647E+09 |
September | 0.264510E+10 | 0.114230E+10 | 0.150280E+10 | 0.307324E+10 | 0.116867E+10 |
October | 0.177184E+10 | 0.624141E+09 | 0.114770E+10 | 0.155578E+10 | 0.184576E+10 |
November | 0.101613E+10 | 0.292811E+09 | 0.723317E+09 | 0.617053E+09 | 0.221711E+10 |
December | 0.910255E+09 | 0.198334E+09 | 0.711921E+09 | 0.276184E+09 | 0.333140E+10 |
Annual Sum or Average | 0.291976E+11 | 0.118480E+11 | 0.173495E+11 | 0.301620E+11 | 0.222520E+11 |
Minimum of Months | 0.910255E+09 | 0.198334E+09 | 0.711921E+09 | 0.276184E+09 | 0.596365E+09 |
Maximum of Months | 0.416548E+10 | 0.195927E+10 | 0.220622E+10 | 0.518131E+10 | 0.340226E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38446651.13 | 9025729.77 | 29420921.35 | 11488254.85 | 0.134522E+09 |
February | 56281302.24 | 14464650.00 | 41816652.25 | 26124004.71 | 0.114459E+09 |
March | 97662032.30 | 41816448.29 | 55845584.00 | 81799325.74 | 91487308.51 |
April | 0.115717E+09 | 47448342.57 | 68268400.37 | 0.112428E+09 | 66349845.72 |
May | 0.141057E+09 | 63748207.56 | 77308383.85 | 0.157570E+09 | 48201160.60 |
June | 0.164699E+09 | 77467326.20 | 87231744.49 | 0.204864E+09 | 32184254.59 |
July | 0.152155E+09 | 66709906.98 | 85445559.96 | 0.201277E+09 | 23579730.89 |
August | 0.137616E+09 | 58515243.79 | 79100356.54 | 0.178677E+09 | 30470662.34 |
September | 0.104585E+09 | 45165419.01 | 59419335.49 | 0.121513E+09 | 46208185.30 |
October | 70056742.45 | 24677899.62 | 45378842.83 | 61513856.31 | 72979624.46 |
November | 40176668.18 | 11577437.89 | 28599230.29 | 24397623.37 | 87662522.18 |
December | 35990571.65 | 7841913.52 | 28148658.13 | 10919991.01 | 0.131721E+09 |
Annual Sum or Average | 0.115444E+10 | 0.468459E+09 | 0.685984E+09 | 0.119257E+10 | 0.879826E+09 |
Minimum of Months | 35990571.65 | 7841913.52 | 28148658.13 | 10919991.01 | 23579730.89 |
Maximum of Months | 0.164699E+09 | 77467326.20 | 87231744.49 | 0.204864E+09 | 0.134522E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.965694E+09 | 0.00 | 0.965694E+09 | 12917111.43 | 0.566208E+10 |
February | 0.132897E+10 | 0.00 | 0.132897E+10 | 93324353.62 | 0.478546E+10 |
March | 0.178434E+10 | 0.00 | 0.178434E+10 | 0.597589E+09 | 0.387209E+10 |
April | 0.220027E+10 | 8779947.19 | 0.219149E+10 | 0.120713E+10 | 0.269735E+10 |
May | 0.264182E+10 | 0.112028E+09 | 0.252980E+10 | 0.207898E+10 | 0.181868E+10 |
June | 0.307506E+10 | 0.261765E+09 | 0.281329E+10 | 0.332608E+10 | 0.114176E+10 |
July | 0.294761E+10 | 0.190275E+09 | 0.275733E+10 | 0.368394E+10 | 0.826852E+09 |
August | 0.255050E+10 | 38800324.88 | 0.251170E+10 | 0.300957E+10 | 0.109922E+10 |
September | 0.187837E+10 | 390244.61 | 0.187798E+10 | 0.169765E+10 | 0.174832E+10 |
October | 0.145097E+10 | 0.00 | 0.145097E+10 | 0.707900E+09 | 0.281882E+10 |
November | 0.943564E+09 | 0.00 | 0.943564E+09 | 0.207764E+09 | 0.345530E+10 |
December | 0.903860E+09 | 0.00 | 0.903860E+09 | 15850049.82 | 0.541008E+10 |
Annual Sum or Average | 0.226710E+11 | 0.612038E+09 | 0.220590E+11 | 0.166387E+11 | 0.353360E+11 |
Minimum of Months | 0.903860E+09 | 0.00 | 0.903860E+09 | 12917111.43 | 0.826852E+09 |
Maximum of Months | 0.307506E+10 | 0.261765E+09 | 0.281329E+10 | 0.368394E+10 | 0.566208E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117815E+10 | 0.379902E+09 | 0.798249E+09 | 0.472191E+09 | 0.342769E+10 |
February | 0.156141E+10 | 0.468541E+09 | 0.109287E+10 | 0.763137E+09 | 0.293464E+10 |
March | 0.248065E+10 | 0.103888E+10 | 0.144177E+10 | 0.195465E+10 | 0.239087E+10 |
April | 0.317738E+10 | 0.140394E+10 | 0.177344E+10 | 0.299159E+10 | 0.171891E+10 |
May | 0.367846E+10 | 0.162718E+10 | 0.205128E+10 | 0.398908E+10 | 0.123858E+10 |
June | 0.397570E+10 | 0.175706E+10 | 0.221864E+10 | 0.482596E+10 | 0.779485E+09 |
July | 0.394497E+10 | 0.173692E+10 | 0.220806E+10 | 0.514365E+10 | 0.559611E+09 |
August | 0.356274E+10 | 0.149545E+10 | 0.206730E+10 | 0.454452E+10 | 0.733854E+09 |
September | 0.286918E+10 | 0.127266E+10 | 0.159652E+10 | 0.329977E+10 | 0.112420E+10 |
October | 0.201188E+10 | 0.832167E+09 | 0.117971E+10 | 0.178953E+10 | 0.179072E+10 |
November | 0.110436E+10 | 0.354266E+09 | 0.750094E+09 | 0.688055E+09 | 0.220758E+10 |
December | 0.918702E+09 | 0.189824E+09 | 0.728878E+09 | 0.247074E+09 | 0.338018E+10 |
Annual Sum or Average | 0.304636E+11 | 0.125568E+11 | 0.179068E+11 | 0.307092E+11 | 0.222863E+11 |
Minimum of Months | 0.918702E+09 | 0.189824E+09 | 0.728878E+09 | 0.247074E+09 | 0.559611E+09 |
Maximum of Months | 0.397570E+10 | 0.175706E+10 | 0.221864E+10 | 0.514365E+10 | 0.342769E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.415250E+10 | 0.242393E+10 | 0.172856E+10 | 0.340702E+10 | 0.486260E+10 |
February | 0.428229E+10 | 0.206488E+10 | 0.221741E+10 | 0.346994E+10 | 0.431445E+10 |
March | 0.578684E+10 | 0.325159E+10 | 0.253525E+10 | 0.572728E+10 | 0.361203E+10 |
April | 0.463782E+10 | 0.185329E+10 | 0.278453E+10 | 0.477327E+10 | 0.279978E+10 |
May | 0.419379E+10 | 0.121805E+10 | 0.297573E+10 | 0.467557E+10 | 0.200782E+10 |
June | 0.394356E+10 | 0.835659E+09 | 0.310790E+10 | 0.491201E+10 | 0.126103E+10 |
July | 0.415992E+10 | 0.100933E+10 | 0.315059E+10 | 0.573101E+10 | 0.902432E+09 |
August | 0.467020E+10 | 0.151420E+10 | 0.315600E+10 | 0.632995E+10 | 0.116829E+10 |
September | 0.525489E+10 | 0.255952E+10 | 0.269537E+10 | 0.656606E+10 | 0.178838E+10 |
October | 0.519575E+10 | 0.296792E+10 | 0.222784E+10 | 0.562579E+10 | 0.274043E+10 |
November | 0.360106E+10 | 0.203292E+10 | 0.156814E+10 | 0.343666E+10 | 0.328625E+10 |
December | 0.347231E+10 | 0.179708E+10 | 0.167523E+10 | 0.269776E+10 | 0.478987E+10 |
Annual Sum or Average | 0.533509E+11 | 0.235284E+11 | 0.298226E+11 | 0.573523E+11 | 0.335334E+11 |
Minimum of Months | 0.347231E+10 | 0.835659E+09 | 0.156814E+10 | 0.269776E+10 | 0.902432E+09 |
Maximum of Months | 0.578684E+10 | 0.325159E+10 | 0.315600E+10 | 0.656606E+10 | 0.486260E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101083E+10 | 0.237304E+09 | 0.773529E+09 | 0.292789E+09 | 0.356259E+10 |
February | 0.147974E+10 | 0.380304E+09 | 0.109943E+10 | 0.663387E+09 | 0.303318E+10 |
March | 0.256771E+10 | 0.109944E+10 | 0.146828E+10 | 0.208134E+10 | 0.245753E+10 |
April | 0.304240E+10 | 0.124751E+10 | 0.179490E+10 | 0.287647E+10 | 0.179975E+10 |
May | 0.370864E+10 | 0.167606E+10 | 0.203257E+10 | 0.406644E+10 | 0.131545E+10 |
June | 0.433024E+10 | 0.203677E+10 | 0.229347E+10 | 0.533652E+10 | 0.850720E+09 |
July | 0.400044E+10 | 0.175393E+10 | 0.224651E+10 | 0.525339E+10 | 0.621158E+09 |
August | 0.361817E+10 | 0.153848E+10 | 0.207969E+10 | 0.467483E+10 | 0.787557E+09 |
September | 0.274972E+10 | 0.118749E+10 | 0.156224E+10 | 0.317923E+10 | 0.118565E+10 |
October | 0.184192E+10 | 0.648830E+09 | 0.119309E+10 | 0.161468E+10 | 0.185390E+10 |
November | 0.105632E+10 | 0.304393E+09 | 0.751925E+09 | 0.639454E+09 | 0.224820E+10 |
December | 0.946258E+09 | 0.206179E+09 | 0.740079E+09 | 0.281869E+09 | 0.343926E+10 |
Annual Sum or Average | 0.303524E+11 | 0.123167E+11 | 0.180357E+11 | 0.309604E+11 | 0.231550E+11 |
Minimum of Months | 0.946258E+09 | 0.206179E+09 | 0.740079E+09 | 0.281869E+09 | 0.621158E+09 |
Maximum of Months | 0.433024E+10 | 0.203677E+10 | 0.229347E+10 | 0.533652E+10 | 0.356259E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7.43 | 2046.16 | 360.55 | 0.00 | 360.55 | 0.00 | 0.00 |
February | 44.61 | 1909.82 | 549.34 | 0.00 | 549.34 | 0.00 | 0.00 |
March | 233.79 | 1372.60 | 666.20 | 0.00 | 666.20 | 0.00 | 0.00 |
April | 483.68 | 977.68 | 848.87 | 3.39 | 845.48 | 0.00 | 0.00 |
May | 787.68 | 646.41 | 986.34 | 41.83 | 944.52 | 0.00 | 0.00 |
June | 1283.85 | 426.47 | 1186.36 | 100.99 | 1085.38 | 0.00 | 0.00 |
July | 1370.88 | 301.41 | 1100.51 | 71.04 | 1029.47 | 0.00 | 0.00 |
August | 1123.73 | 396.15 | 952.25 | 14.49 | 937.76 | 0.00 | 0.00 |
September | 663.35 | 636.39 | 724.68 | 0.15 | 724.53 | 0.00 | 0.00 |
October | 285.68 | 968.81 | 541.73 | 0.00 | 541.73 | 0.00 | 0.00 |
November | 92.90 | 1234.87 | 364.03 | 0.00 | 364.03 | 0.00 | 0.00 |
December | 8.38 | 1936.27 | 337.46 | 0.00 | 337.46 | 0.00 | 0.00 |
Annual Sum or Average | 535.09 | 1066.96 | 718.89 | 19.41 | 699.49 | 0.00 | 0.00 |
Minimum of Months | 7.43 | 301.41 | 337.46 | 0.00 | 337.46 | 0.00 | 0.00 |
Maximum of Months | 1370.88 | 2046.16 | 1186.36 | 100.99 | 1085.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 180.83 | 1239.80 | 439.87 | 141.84 | 298.03 | 0.00 | 0.00 |
February | 323.62 | 1172.92 | 645.43 | 193.68 | 451.75 | 0.00 | 0.00 |
March | 744.12 | 845.72 | 926.17 | 387.87 | 538.29 | 0.00 | 0.00 |
April | 1170.78 | 625.12 | 1225.84 | 541.64 | 684.20 | 0.00 | 0.00 |
May | 1496.96 | 442.07 | 1373.38 | 607.52 | 765.86 | 0.00 | 0.00 |
June | 1863.90 | 291.47 | 1533.84 | 677.88 | 855.96 | 0.00 | 0.00 |
July | 1919.82 | 203.94 | 1472.88 | 648.49 | 824.39 | 0.00 | 0.00 |
August | 1698.56 | 264.77 | 1330.18 | 558.34 | 771.84 | 0.00 | 0.00 |
September | 1280.79 | 411.56 | 1106.94 | 491.00 | 615.94 | 0.00 | 0.00 |
October | 687.54 | 617.08 | 751.15 | 310.70 | 440.45 | 0.00 | 0.00 |
November | 279.10 | 788.52 | 426.07 | 136.68 | 289.39 | 0.00 | 0.00 |
December | 96.33 | 1212.58 | 343.00 | 70.87 | 272.13 | 0.00 | 0.00 |
Annual Sum or Average | 982.05 | 673.83 | 965.99 | 398.17 | 567.82 | 0.00 | 0.00 |
Minimum of Months | 96.33 | 203.94 | 343.00 | 70.87 | 272.13 | 0.00 | 0.00 |
Maximum of Months | 1919.82 | 1239.80 | 1533.84 | 677.88 | 855.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1284.38 | 1749.13 | 1550.36 | 904.99 | 645.37 | 0.00 | 0.00 |
February | 1448.55 | 1718.06 | 1770.13 | 853.54 | 916.59 | 0.00 | 0.00 |
March | 2154.85 | 1277.15 | 2160.56 | 1214.00 | 946.55 | 0.00 | 0.00 |
April | 1857.20 | 1018.53 | 1789.28 | 715.00 | 1074.28 | 0.00 | 0.00 |
May | 1750.79 | 714.10 | 1565.78 | 454.77 | 1111.01 | 0.00 | 0.00 |
June | 1892.05 | 469.09 | 1521.43 | 322.40 | 1199.03 | 0.00 | 0.00 |
July | 2132.86 | 327.54 | 1553.14 | 376.84 | 1176.30 | 0.00 | 0.00 |
August | 2359.92 | 420.72 | 1743.65 | 565.34 | 1178.32 | 0.00 | 0.00 |
September | 2537.61 | 654.92 | 2027.35 | 987.47 | 1039.88 | 0.00 | 0.00 |
October | 2122.79 | 947.36 | 1939.87 | 1108.09 | 831.78 | 0.00 | 0.00 |
November | 1347.24 | 1175.63 | 1389.30 | 784.30 | 604.99 | 0.00 | 0.00 |
December | 1020.96 | 1710.93 | 1296.41 | 670.95 | 625.46 | 0.00 | 0.00 |
Annual Sum or Average | 1827.96 | 1011.52 | 1691.75 | 746.08 | 945.67 | 0.00 | 0.00 |
Minimum of Months | 1020.96 | 327.54 | 1296.41 | 322.40 | 604.99 | 0.00 | 0.00 |
Maximum of Months | 2537.61 | 1749.13 | 2160.56 | 1214.00 | 1199.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 112.42 | 1287.44 | 377.40 | 88.60 | 288.80 | 0.00 | 0.00 |
February | 279.26 | 1211.40 | 611.66 | 157.20 | 454.46 | 0.00 | 0.00 |
March | 785.66 | 869.48 | 958.67 | 410.48 | 548.19 | 0.00 | 0.00 |
April | 1120.90 | 653.15 | 1173.77 | 481.29 | 692.48 | 0.00 | 0.00 |
May | 1522.16 | 467.50 | 1384.65 | 625.77 | 758.88 | 0.00 | 0.00 |
June | 2055.81 | 316.49 | 1670.62 | 785.79 | 884.83 | 0.00 | 0.00 |
July | 1956.26 | 225.36 | 1493.59 | 654.84 | 838.75 | 0.00 | 0.00 |
August | 1743.27 | 283.77 | 1350.87 | 574.40 | 776.47 | 0.00 | 0.00 |
September | 1230.61 | 432.91 | 1060.85 | 458.14 | 602.72 | 0.00 | 0.00 |
October | 617.66 | 638.18 | 687.69 | 242.25 | 445.45 | 0.00 | 0.00 |
November | 257.66 | 803.89 | 407.53 | 117.44 | 290.09 | 0.00 | 0.00 |
December | 108.91 | 1231.96 | 353.29 | 76.98 | 276.31 | 0.00 | 0.00 |
Annual Sum or Average | 986.31 | 699.25 | 962.47 | 390.56 | 571.91 | 0.00 | 0.00 |
Minimum of Months | 108.91 | 225.36 | 353.29 | 76.98 | 276.31 | 0.00 | 0.00 |
Maximum of Months | 2055.81 | 1287.44 | 1670.62 | 785.79 | 884.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4.70 | 2095.66 | 360.54 | 0.00 | 360.54 | 0.00 | 0.00 |
February | 41.93 | 1956.88 | 549.33 | 0.00 | 549.33 | 0.00 | 0.00 |
March | 246.74 | 1394.98 | 666.18 | 0.00 | 666.18 | 0.00 | 0.00 |
April | 511.54 | 979.32 | 848.85 | 3.39 | 845.46 | 0.00 | 0.00 |
May | 833.42 | 625.18 | 986.32 | 41.83 | 944.50 | 0.00 | 0.00 |
June | 1317.54 | 417.59 | 1186.34 | 100.99 | 1085.35 | 0.00 | 0.00 |
July | 1400.90 | 292.45 | 1100.49 | 71.04 | 1029.45 | 0.00 | 0.00 |
August | 1138.27 | 400.41 | 952.23 | 14.49 | 937.74 | 0.00 | 0.00 |
September | 664.24 | 672.56 | 724.67 | 0.15 | 724.52 | 0.00 | 0.00 |
October | 264.93 | 1073.20 | 541.72 | 0.00 | 541.72 | 0.00 | 0.00 |
November | 79.84 | 1356.58 | 364.02 | 0.00 | 364.02 | 0.00 | 0.00 |
December | 5.80 | 2033.30 | 337.45 | 0.00 | 337.45 | 0.00 | 0.00 |
Annual Sum or Average | 545.50 | 1103.96 | 718.88 | 19.41 | 699.47 | 0.00 | 0.00 |
Minimum of Months | 4.70 | 292.45 | 337.45 | 0.00 | 337.45 | 0.00 | 0.00 |
Maximum of Months | 1400.90 | 2095.66 | 1186.34 | 100.99 | 1085.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 179.66 | 1276.87 | 439.86 | 141.84 | 298.03 | 0.00 | 0.00 |
February | 323.59 | 1207.13 | 645.41 | 193.67 | 451.74 | 0.00 | 0.00 |
March | 755.54 | 871.60 | 926.15 | 387.87 | 538.29 | 0.00 | 0.00 |
April | 1184.42 | 645.02 | 1225.82 | 541.63 | 684.19 | 0.00 | 0.00 |
May | 1519.46 | 443.60 | 1373.36 | 607.51 | 765.85 | 0.00 | 0.00 |
June | 1883.27 | 295.61 | 1533.81 | 677.87 | 855.95 | 0.00 | 0.00 |
July | 1937.19 | 206.64 | 1472.86 | 648.48 | 824.38 | 0.00 | 0.00 |
August | 1708.76 | 276.37 | 1330.16 | 558.32 | 771.83 | 0.00 | 0.00 |
September | 1281.62 | 444.08 | 1106.92 | 490.99 | 615.93 | 0.00 | 0.00 |
October | 670.50 | 694.86 | 751.14 | 310.69 | 440.45 | 0.00 | 0.00 |
November | 266.33 | 874.44 | 426.06 | 136.67 | 289.38 | 0.00 | 0.00 |
December | 93.00 | 1274.80 | 343.00 | 70.87 | 272.13 | 0.00 | 0.00 |
Annual Sum or Average | 987.17 | 706.74 | 965.98 | 398.17 | 567.81 | 0.00 | 0.00 |
Minimum of Months | 93.00 | 206.64 | 343.00 | 70.87 | 272.13 | 0.00 | 0.00 |
Maximum of Months | 1937.19 | 1276.87 | 1533.81 | 677.87 | 855.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1307.48 | 1791.74 | 1550.30 | 904.96 | 645.35 | 0.00 | 0.00 |
February | 1480.67 | 1754.54 | 1770.06 | 853.50 | 916.55 | 0.00 | 0.00 |
March | 2201.89 | 1324.98 | 2160.48 | 1213.95 | 946.52 | 0.00 | 0.00 |
April | 1901.67 | 1035.75 | 1789.22 | 714.97 | 1074.25 | 0.00 | 0.00 |
May | 1804.53 | 697.55 | 1565.73 | 454.75 | 1110.98 | 0.00 | 0.00 |
June | 1935.04 | 463.58 | 1521.39 | 322.39 | 1199.00 | 0.00 | 0.00 |
July | 2165.74 | 326.25 | 1553.09 | 376.83 | 1176.26 | 0.00 | 0.00 |
August | 2380.89 | 437.46 | 1743.59 | 565.31 | 1178.28 | 0.00 | 0.00 |
September | 2548.18 | 708.58 | 2027.27 | 987.43 | 1039.85 | 0.00 | 0.00 |
October | 2118.83 | 1061.70 | 1939.80 | 1108.05 | 831.75 | 0.00 | 0.00 |
November | 1338.77 | 1306.11 | 1389.24 | 784.27 | 604.97 | 0.00 | 0.00 |
December | 1028.00 | 1788.21 | 1296.36 | 670.92 | 625.44 | 0.00 | 0.00 |
Annual Sum or Average | 1853.14 | 1054.28 | 1691.68 | 746.05 | 945.64 | 0.00 | 0.00 |
Minimum of Months | 1028.00 | 326.25 | 1296.36 | 322.39 | 604.97 | 0.00 | 0.00 |
Maximum of Months | 2548.18 | 1791.74 | 2160.48 | 1213.95 | 1199.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 112.77 | 1320.48 | 377.40 | 88.60 | 288.80 | 0.00 | 0.00 |
February | 283.91 | 1243.92 | 611.66 | 157.20 | 454.46 | 0.00 | 0.00 |
March | 802.95 | 898.05 | 958.66 | 410.48 | 548.19 | 0.00 | 0.00 |
April | 1140.40 | 673.01 | 1173.75 | 481.28 | 692.47 | 0.00 | 0.00 |
May | 1546.73 | 473.15 | 1384.63 | 625.76 | 758.87 | 0.00 | 0.00 |
June | 2078.00 | 326.45 | 1670.60 | 785.78 | 884.82 | 0.00 | 0.00 |
July | 1975.76 | 231.46 | 1493.58 | 654.83 | 838.74 | 0.00 | 0.00 |
August | 1753.92 | 299.10 | 1350.85 | 574.39 | 776.46 | 0.00 | 0.00 |
September | 1232.54 | 468.70 | 1060.84 | 458.13 | 602.71 | 0.00 | 0.00 |
October | 603.83 | 716.37 | 687.69 | 242.24 | 445.44 | 0.00 | 0.00 |
November | 247.47 | 889.19 | 407.52 | 117.43 | 290.09 | 0.00 | 0.00 |
December | 107.19 | 1292.98 | 353.29 | 76.98 | 276.31 | 0.00 | 0.00 |
Annual Sum or Average | 994.25 | 733.51 | 962.46 | 390.55 | 571.90 | 0.00 | 0.00 |
Minimum of Months | 107.19 | 231.46 | 353.29 | 76.98 | 276.31 | 0.00 | 0.00 |
Maximum of Months | 2078.00 | 1320.48 | 1670.60 | 785.78 | 884.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4.82 | 2113.98 | 360.55 | 0.00 | 360.55 | 0.00 | 0.00 |
February | 38.58 | 1978.11 | 549.34 | 0.00 | 549.34 | 0.00 | 0.00 |
March | 223.11 | 1445.67 | 666.20 | 0.00 | 666.20 | 0.00 | 0.00 |
April | 465.71 | 1040.64 | 848.87 | 3.39 | 845.48 | 0.00 | 0.00 |
May | 776.20 | 679.02 | 986.34 | 41.83 | 944.52 | 0.00 | 0.00 |
June | 1283.21 | 440.49 | 1186.36 | 100.99 | 1085.38 | 0.00 | 0.00 |
July | 1375.43 | 308.71 | 1100.51 | 71.04 | 1029.47 | 0.00 | 0.00 |
August | 1123.64 | 410.40 | 952.25 | 14.49 | 937.76 | 0.00 | 0.00 |
September | 654.96 | 674.51 | 724.68 | 0.15 | 724.53 | 0.00 | 0.00 |
October | 264.30 | 1052.43 | 541.73 | 0.00 | 541.73 | 0.00 | 0.00 |
November | 80.16 | 1333.06 | 364.03 | 0.00 | 364.03 | 0.00 | 0.00 |
December | 5.92 | 2019.89 | 337.46 | 0.00 | 337.46 | 0.00 | 0.00 |
Annual Sum or Average | 527.61 | 1120.50 | 718.89 | 19.41 | 699.49 | 0.00 | 0.00 |
Minimum of Months | 4.82 | 308.71 | 337.46 | 0.00 | 337.46 | 0.00 | 0.00 |
Maximum of Months | 1375.43 | 2113.98 | 1186.36 | 100.99 | 1085.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 176.30 | 1279.75 | 439.87 | 141.84 | 298.03 | 0.00 | 0.00 |
February | 315.45 | 1213.06 | 645.43 | 193.68 | 451.75 | 0.00 | 0.00 |
March | 729.78 | 892.65 | 926.17 | 387.87 | 538.29 | 0.00 | 0.00 |
April | 1154.16 | 663.16 | 1225.84 | 541.64 | 684.20 | 0.00 | 0.00 |
May | 1489.35 | 462.43 | 1373.38 | 607.52 | 765.86 | 0.00 | 0.00 |
June | 1861.87 | 300.73 | 1533.84 | 677.88 | 855.96 | 0.00 | 0.00 |
July | 1920.42 | 208.93 | 1472.88 | 648.49 | 824.39 | 0.00 | 0.00 |
August | 1696.73 | 273.99 | 1330.18 | 558.34 | 771.84 | 0.00 | 0.00 |
September | 1273.06 | 433.72 | 1106.94 | 491.00 | 615.94 | 0.00 | 0.00 |
October | 668.14 | 668.58 | 751.15 | 310.70 | 440.45 | 0.00 | 0.00 |
November | 265.45 | 851.69 | 426.07 | 136.68 | 289.39 | 0.00 | 0.00 |
December | 92.25 | 1262.01 | 343.00 | 70.87 | 272.13 | 0.00 | 0.00 |
Annual Sum or Average | 973.78 | 706.69 | 965.99 | 398.17 | 567.82 | 0.00 | 0.00 |
Minimum of Months | 92.25 | 208.93 | 343.00 | 70.87 | 272.13 | 0.00 | 0.00 |
Maximum of Months | 1920.42 | 1279.75 | 1533.84 | 677.88 | 855.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1272.04 | 1815.49 | 1550.36 | 904.99 | 645.37 | 0.00 | 0.00 |
February | 1434.33 | 1783.42 | 1770.13 | 853.54 | 916.59 | 0.00 | 0.00 |
March | 2138.32 | 1348.58 | 2160.56 | 1214.00 | 946.55 | 0.00 | 0.00 |
April | 1841.54 | 1080.16 | 1789.28 | 715.00 | 1074.28 | 0.00 | 0.00 |
May | 1745.66 | 749.63 | 1565.78 | 454.77 | 1111.01 | 0.00 | 0.00 |
June | 1895.07 | 486.51 | 1521.43 | 322.40 | 1199.03 | 0.00 | 0.00 |
July | 2139.72 | 336.93 | 1553.14 | 376.84 | 1176.30 | 0.00 | 0.00 |
August | 2363.33 | 436.19 | 1743.65 | 565.34 | 1178.32 | 0.00 | 0.00 |
September | 2533.20 | 689.96 | 2027.35 | 987.47 | 1039.88 | 0.00 | 0.00 |
October | 2100.43 | 1023.16 | 1939.87 | 1108.09 | 831.78 | 0.00 | 0.00 |
November | 1325.87 | 1267.84 | 1389.30 | 784.30 | 604.99 | 0.00 | 0.00 |
December | 1007.23 | 1788.33 | 1296.41 | 670.95 | 625.46 | 0.00 | 0.00 |
Annual Sum or Average | 1818.63 | 1063.34 | 1691.75 | 746.08 | 945.67 | 0.00 | 0.00 |
Minimum of Months | 1007.23 | 336.93 | 1296.41 | 322.40 | 604.99 | 0.00 | 0.00 |
Maximum of Months | 2533.20 | 1815.49 | 2160.56 | 1214.00 | 1199.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 109.31 | 1330.12 | 377.40 | 88.60 | 288.80 | 0.00 | 0.00 |
February | 274.22 | 1253.80 | 611.66 | 157.20 | 454.46 | 0.00 | 0.00 |
March | 777.08 | 917.54 | 958.67 | 410.48 | 548.19 | 0.00 | 0.00 |
April | 1109.75 | 694.35 | 1173.77 | 481.29 | 692.48 | 0.00 | 0.00 |
May | 1518.23 | 491.13 | 1384.65 | 625.77 | 758.88 | 0.00 | 0.00 |
June | 2058.84 | 328.21 | 1670.62 | 785.79 | 884.83 | 0.00 | 0.00 |
July | 1961.39 | 231.91 | 1493.59 | 654.84 | 838.75 | 0.00 | 0.00 |
August | 1745.38 | 294.04 | 1350.87 | 574.40 | 776.47 | 0.00 | 0.00 |
September | 1226.56 | 457.43 | 1060.85 | 458.14 | 602.72 | 0.00 | 0.00 |
October | 602.85 | 692.17 | 687.69 | 242.25 | 445.45 | 0.00 | 0.00 |
November | 246.70 | 867.36 | 407.53 | 117.44 | 290.09 | 0.00 | 0.00 |
December | 105.24 | 1284.07 | 353.29 | 76.98 | 276.31 | 0.00 | 0.00 |
Annual Sum or Average | 981.75 | 734.24 | 962.47 | 390.56 | 571.91 | 0.00 | 0.00 |
Minimum of Months | 105.24 | 231.91 | 353.29 | 76.98 | 276.31 | 0.00 | 0.00 |
Maximum of Months | 2058.84 | 1330.12 | 1670.62 | 785.79 | 884.83 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 19893161.15 | 0.548043E+10 | 0.965694E+09 | 0.00 | 0.965694E+09 | 0.00 | 0.00 |
February | 0.107926E+09 | 0.462025E+10 | 0.132897E+10 | 0.00 | 0.132897E+10 | 0.00 | 0.00 |
March | 0.626183E+09 | 0.367638E+10 | 0.178434E+10 | 0.00 | 0.178434E+10 | 0.00 | 0.00 |
April | 0.125370E+10 | 0.253415E+10 | 0.220027E+10 | 8779947.19 | 0.219149E+10 | 0.00 | 0.00 |
May | 0.210973E+10 | 0.173135E+10 | 0.264182E+10 | 0.112028E+09 | 0.252980E+10 | 0.00 | 0.00 |
June | 0.332775E+10 | 0.110541E+10 | 0.307506E+10 | 0.261765E+09 | 0.281329E+10 | 0.00 | 0.00 |
July | 0.367177E+10 | 0.807306E+09 | 0.294761E+10 | 0.190275E+09 | 0.275733E+10 | 0.00 | 0.00 |
August | 0.300981E+10 | 0.106104E+10 | 0.255050E+10 | 38800324.88 | 0.251170E+10 | 0.00 | 0.00 |
September | 0.171941E+10 | 0.164953E+10 | 0.187837E+10 | 390244.61 | 0.187798E+10 | 0.00 | 0.00 |
October | 0.765175E+09 | 0.259486E+10 | 0.145097E+10 | 0.00 | 0.145097E+10 | 0.00 | 0.00 |
November | 0.240792E+09 | 0.320078E+10 | 0.943564E+09 | 0.00 | 0.943564E+09 | 0.00 | 0.00 |
December | 22457914.45 | 0.518612E+10 | 0.903860E+09 | 0.00 | 0.903860E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.168746E+11 | 0.336476E+11 | 0.226710E+11 | 0.612038E+09 | 0.220590E+11 | 0.00 | 0.00 |
Minimum of Months | 19893161.15 | 0.807306E+09 | 0.903860E+09 | 0.00 | 0.903860E+09 | 0.00 | 0.00 |
Maximum of Months | 0.367177E+10 | 0.548043E+10 | 0.307506E+10 | 0.261765E+09 | 0.281329E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.484331E+09 | 0.332069E+10 | 0.117815E+10 | 0.379902E+09 | 0.798249E+09 | 0.00 | 0.00 |
February | 0.782901E+09 | 0.283752E+10 | 0.156141E+10 | 0.468541E+09 | 0.109287E+10 | 0.00 | 0.00 |
March | 0.199306E+10 | 0.226519E+10 | 0.248065E+10 | 0.103888E+10 | 0.144177E+10 | 0.00 | 0.00 |
April | 0.303466E+10 | 0.162030E+10 | 0.317738E+10 | 0.140394E+10 | 0.177344E+10 | 0.00 | 0.00 |
May | 0.400947E+10 | 0.118404E+10 | 0.367846E+10 | 0.162718E+10 | 0.205128E+10 | 0.00 | 0.00 |
June | 0.483122E+10 | 0.755485E+09 | 0.397570E+10 | 0.175706E+10 | 0.221864E+10 | 0.00 | 0.00 |
July | 0.514205E+10 | 0.546240E+09 | 0.394497E+10 | 0.173692E+10 | 0.220806E+10 | 0.00 | 0.00 |
August | 0.454943E+10 | 0.709154E+09 | 0.356274E+10 | 0.149545E+10 | 0.206730E+10 | 0.00 | 0.00 |
September | 0.331980E+10 | 0.106677E+10 | 0.286918E+10 | 0.127266E+10 | 0.159652E+10 | 0.00 | 0.00 |
October | 0.184151E+10 | 0.165279E+10 | 0.201188E+10 | 0.832167E+09 | 0.117971E+10 | 0.00 | 0.00 |
November | 0.723428E+09 | 0.204384E+10 | 0.110436E+10 | 0.354266E+09 | 0.750094E+09 | 0.00 | 0.00 |
December | 0.257998E+09 | 0.324777E+10 | 0.918702E+09 | 0.189824E+09 | 0.728878E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.309699E+11 | 0.212498E+11 | 0.304636E+11 | 0.125568E+11 | 0.179068E+11 | 0.00 | 0.00 |
Minimum of Months | 0.257998E+09 | 0.546240E+09 | 0.918702E+09 | 0.189824E+09 | 0.728878E+09 | 0.00 | 0.00 |
Maximum of Months | 0.514205E+10 | 0.332069E+10 | 0.397570E+10 | 0.175706E+10 | 0.221864E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.344008E+10 | 0.468488E+10 | 0.415250E+10 | 0.242393E+10 | 0.172856E+10 | 0.00 | 0.00 |
February | 0.350432E+10 | 0.415634E+10 | 0.428229E+10 | 0.206488E+10 | 0.221741E+10 | 0.00 | 0.00 |
March | 0.577156E+10 | 0.342072E+10 | 0.578684E+10 | 0.325159E+10 | 0.253525E+10 | 0.00 | 0.00 |
April | 0.481386E+10 | 0.264004E+10 | 0.463782E+10 | 0.185329E+10 | 0.278453E+10 | 0.00 | 0.00 |
May | 0.468932E+10 | 0.191263E+10 | 0.419379E+10 | 0.121805E+10 | 0.297573E+10 | 0.00 | 0.00 |
June | 0.490420E+10 | 0.121587E+10 | 0.394356E+10 | 0.835659E+09 | 0.310790E+10 | 0.00 | 0.00 |
July | 0.571265E+10 | 0.877291E+09 | 0.415992E+10 | 0.100933E+10 | 0.315059E+10 | 0.00 | 0.00 |
August | 0.632080E+10 | 0.112686E+10 | 0.467020E+10 | 0.151420E+10 | 0.315600E+10 | 0.00 | 0.00 |
September | 0.657747E+10 | 0.169754E+10 | 0.525489E+10 | 0.255952E+10 | 0.269537E+10 | 0.00 | 0.00 |
October | 0.568569E+10 | 0.253740E+10 | 0.519575E+10 | 0.296792E+10 | 0.222784E+10 | 0.00 | 0.00 |
November | 0.349204E+10 | 0.304724E+10 | 0.360106E+10 | 0.203292E+10 | 0.156814E+10 | 0.00 | 0.00 |
December | 0.273454E+10 | 0.458256E+10 | 0.347231E+10 | 0.179708E+10 | 0.167523E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.576465E+11 | 0.318994E+11 | 0.533509E+11 | 0.235284E+11 | 0.298226E+11 | 0.00 | 0.00 |
Minimum of Months | 0.273454E+10 | 0.877291E+09 | 0.347231E+10 | 0.835659E+09 | 0.156814E+10 | 0.00 | 0.00 |
Maximum of Months | 0.657747E+10 | 0.468488E+10 | 0.578684E+10 | 0.325159E+10 | 0.315600E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.301105E+09 | 0.344828E+10 | 0.101083E+10 | 0.237304E+09 | 0.773529E+09 | 0.00 | 0.00 |
February | 0.675594E+09 | 0.293062E+10 | 0.147974E+10 | 0.380304E+09 | 0.109943E+10 | 0.00 | 0.00 |
March | 0.210430E+10 | 0.232883E+10 | 0.256771E+10 | 0.109944E+10 | 0.146828E+10 | 0.00 | 0.00 |
April | 0.290537E+10 | 0.169297E+10 | 0.304240E+10 | 0.124751E+10 | 0.179490E+10 | 0.00 | 0.00 |
May | 0.407694E+10 | 0.125215E+10 | 0.370864E+10 | 0.167606E+10 | 0.203257E+10 | 0.00 | 0.00 |
June | 0.532866E+10 | 0.820340E+09 | 0.433024E+10 | 0.203677E+10 | 0.229347E+10 | 0.00 | 0.00 |
July | 0.523964E+10 | 0.603595E+09 | 0.400044E+10 | 0.175393E+10 | 0.224651E+10 | 0.00 | 0.00 |
August | 0.466918E+10 | 0.760063E+09 | 0.361817E+10 | 0.153848E+10 | 0.207969E+10 | 0.00 | 0.00 |
September | 0.318973E+10 | 0.112210E+10 | 0.274972E+10 | 0.118749E+10 | 0.156224E+10 | 0.00 | 0.00 |
October | 0.165433E+10 | 0.170929E+10 | 0.184192E+10 | 0.648830E+09 | 0.119309E+10 | 0.00 | 0.00 |
November | 0.667865E+09 | 0.208369E+10 | 0.105632E+10 | 0.304393E+09 | 0.751925E+09 | 0.00 | 0.00 |
December | 0.291702E+09 | 0.329968E+10 | 0.946258E+09 | 0.206179E+09 | 0.740079E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.311044E+11 | 0.220516E+11 | 0.303524E+11 | 0.123167E+11 | 0.180357E+11 | 0.00 | 0.00 |
Minimum of Months | 0.291702E+09 | 0.603595E+09 | 0.946258E+09 | 0.206179E+09 | 0.740079E+09 | 0.00 | 0.00 |
Maximum of Months | 0.532866E+10 | 0.344828E+10 | 0.433024E+10 | 0.203677E+10 | 0.229347E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 12585848.91 | 0.561302E+10 | 0.965672E+09 | 0.00 | 0.965672E+09 | 0.00 | 0.00 |
February | 0.101449E+09 | 0.473409E+10 | 0.132894E+10 | 0.00 | 0.132894E+10 | 0.00 | 0.00 |
March | 0.660859E+09 | 0.373631E+10 | 0.178430E+10 | 0.00 | 0.178430E+10 | 0.00 | 0.00 |
April | 0.132590E+10 | 0.253839E+10 | 0.220022E+10 | 8779689.12 | 0.219144E+10 | 0.00 | 0.00 |
May | 0.223223E+10 | 0.167449E+10 | 0.264177E+10 | 0.112025E+09 | 0.252975E+10 | 0.00 | 0.00 |
June | 0.341505E+10 | 0.108239E+10 | 0.307499E+10 | 0.261757E+09 | 0.281324E+10 | 0.00 | 0.00 |
July | 0.375217E+10 | 0.783296E+09 | 0.294755E+10 | 0.190269E+09 | 0.275728E+10 | 0.00 | 0.00 |
August | 0.304875E+10 | 0.107246E+10 | 0.255045E+10 | 38799184.43 | 0.251165E+10 | 0.00 | 0.00 |
September | 0.172170E+10 | 0.174326E+10 | 0.187833E+10 | 390233.14 | 0.187794E+10 | 0.00 | 0.00 |
October | 0.709597E+09 | 0.287445E+10 | 0.145094E+10 | 0.00 | 0.145094E+10 | 0.00 | 0.00 |
November | 0.206935E+09 | 0.351626E+10 | 0.943542E+09 | 0.00 | 0.943542E+09 | 0.00 | 0.00 |
December | 15534651.02 | 0.544598E+10 | 0.903839E+09 | 0.00 | 0.903839E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.172028E+11 | 0.348144E+11 | 0.226705E+11 | 0.612020E+09 | 0.220585E+11 | 0.00 | 0.00 |
Minimum of Months | 12585848.91 | 0.783296E+09 | 0.903839E+09 | 0.00 | 0.903839E+09 | 0.00 | 0.00 |
Maximum of Months | 0.375217E+10 | 0.561302E+10 | 0.307499E+10 | 0.261757E+09 | 0.281324E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.481190E+09 | 0.341997E+10 | 0.117813E+10 | 0.379894E+09 | 0.798238E+09 | 0.00 | 0.00 |
February | 0.782823E+09 | 0.292030E+10 | 0.156139E+10 | 0.468532E+09 | 0.109286E+10 | 0.00 | 0.00 |
March | 0.202364E+10 | 0.233450E+10 | 0.248061E+10 | 0.103886E+10 | 0.144175E+10 | 0.00 | 0.00 |
April | 0.307001E+10 | 0.167189E+10 | 0.317733E+10 | 0.140391E+10 | 0.177342E+10 | 0.00 | 0.00 |
May | 0.406972E+10 | 0.118815E+10 | 0.367841E+10 | 0.162715E+10 | 0.205126E+10 | 0.00 | 0.00 |
June | 0.488142E+10 | 0.766231E+09 | 0.397564E+10 | 0.175703E+10 | 0.221861E+10 | 0.00 | 0.00 |
July | 0.518858E+10 | 0.553461E+09 | 0.394491E+10 | 0.173688E+10 | 0.220803E+10 | 0.00 | 0.00 |
August | 0.457675E+10 | 0.740231E+09 | 0.356269E+10 | 0.149542E+10 | 0.206727E+10 | 0.00 | 0.00 |
September | 0.332196E+10 | 0.115107E+10 | 0.286914E+10 | 0.127263E+10 | 0.159650E+10 | 0.00 | 0.00 |
October | 0.179586E+10 | 0.186112E+10 | 0.201185E+10 | 0.832150E+09 | 0.117969E+10 | 0.00 | 0.00 |
November | 0.690339E+09 | 0.226655E+10 | 0.110434E+10 | 0.354259E+09 | 0.750084E+09 | 0.00 | 0.00 |
December | 0.249102E+09 | 0.341442E+10 | 0.918688E+09 | 0.189820E+09 | 0.728868E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.311314E+11 | 0.222879E+11 | 0.304631E+11 | 0.125565E+11 | 0.179066E+11 | 0.00 | 0.00 |
Minimum of Months | 0.249102E+09 | 0.553461E+09 | 0.918688E+09 | 0.189820E+09 | 0.728868E+09 | 0.00 | 0.00 |
Maximum of Months | 0.518858E+10 | 0.341997E+10 | 0.397564E+10 | 0.175703E+10 | 0.221861E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.350196E+10 | 0.479900E+10 | 0.415233E+10 | 0.242383E+10 | 0.172850E+10 | 0.00 | 0.00 |
February | 0.358204E+10 | 0.424459E+10 | 0.428213E+10 | 0.206480E+10 | 0.221733E+10 | 0.00 | 0.00 |
March | 0.589753E+10 | 0.354882E+10 | 0.578662E+10 | 0.325145E+10 | 0.253517E+10 | 0.00 | 0.00 |
April | 0.492912E+10 | 0.268466E+10 | 0.463765E+10 | 0.185321E+10 | 0.278444E+10 | 0.00 | 0.00 |
May | 0.483326E+10 | 0.186832E+10 | 0.419365E+10 | 0.121800E+10 | 0.297565E+10 | 0.00 | 0.00 |
June | 0.501563E+10 | 0.120161E+10 | 0.394343E+10 | 0.835625E+09 | 0.310781E+10 | 0.00 | 0.00 |
July | 0.580071E+10 | 0.873819E+09 | 0.415979E+10 | 0.100929E+10 | 0.315050E+10 | 0.00 | 0.00 |
August | 0.637697E+10 | 0.117170E+10 | 0.467004E+10 | 0.151413E+10 | 0.315590E+10 | 0.00 | 0.00 |
September | 0.660489E+10 | 0.183664E+10 | 0.525469E+10 | 0.255941E+10 | 0.269528E+10 | 0.00 | 0.00 |
October | 0.567507E+10 | 0.284366E+10 | 0.519555E+10 | 0.296779E+10 | 0.222776E+10 | 0.00 | 0.00 |
November | 0.347010E+10 | 0.338544E+10 | 0.360092E+10 | 0.203283E+10 | 0.156808E+10 | 0.00 | 0.00 |
December | 0.275339E+10 | 0.478955E+10 | 0.347217E+10 | 0.179700E+10 | 0.167517E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.584407E+11 | 0.332478E+11 | 0.533490E+11 | 0.235274E+11 | 0.298216E+11 | 0.00 | 0.00 |
Minimum of Months | 0.275339E+10 | 0.873819E+09 | 0.347217E+10 | 0.835625E+09 | 0.156808E+10 | 0.00 | 0.00 |
Maximum of Months | 0.660489E+10 | 0.479900E+10 | 0.578662E+10 | 0.325145E+10 | 0.315590E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.302044E+09 | 0.353678E+10 | 0.101082E+10 | 0.237300E+09 | 0.773520E+09 | 0.00 | 0.00 |
February | 0.686841E+09 | 0.300930E+10 | 0.147972E+10 | 0.380297E+09 | 0.109942E+10 | 0.00 | 0.00 |
March | 0.215063E+10 | 0.240533E+10 | 0.256768E+10 | 0.109942E+10 | 0.146826E+10 | 0.00 | 0.00 |
April | 0.295591E+10 | 0.174443E+10 | 0.304237E+10 | 0.124749E+10 | 0.179488E+10 | 0.00 | 0.00 |
May | 0.414275E+10 | 0.126728E+10 | 0.370859E+10 | 0.167604E+10 | 0.203255E+10 | 0.00 | 0.00 |
June | 0.538617E+10 | 0.846170E+09 | 0.433018E+10 | 0.203673E+10 | 0.229345E+10 | 0.00 | 0.00 |
July | 0.529188E+10 | 0.619945E+09 | 0.400039E+10 | 0.175390E+10 | 0.224649E+10 | 0.00 | 0.00 |
August | 0.469769E+10 | 0.801117E+09 | 0.361812E+10 | 0.153845E+10 | 0.207967E+10 | 0.00 | 0.00 |
September | 0.319475E+10 | 0.121488E+10 | 0.274969E+10 | 0.118747E+10 | 0.156222E+10 | 0.00 | 0.00 |
October | 0.161729E+10 | 0.191874E+10 | 0.184190E+10 | 0.648819E+09 | 0.119308E+10 | 0.00 | 0.00 |
November | 0.641451E+09 | 0.230477E+10 | 0.105630E+10 | 0.304388E+09 | 0.751916E+09 | 0.00 | 0.00 |
December | 0.287104E+09 | 0.346312E+10 | 0.946246E+09 | 0.206176E+09 | 0.740070E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.313545E+11 | 0.231319E+11 | 0.303520E+11 | 0.123165E+11 | 0.180355E+11 | 0.00 | 0.00 |
Minimum of Months | 0.287104E+09 | 0.619945E+09 | 0.946246E+09 | 0.206176E+09 | 0.740070E+09 | 0.00 | 0.00 |
Maximum of Months | 0.538617E+10 | 0.353678E+10 | 0.433018E+10 | 0.203673E+10 | 0.229345E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 12917111.43 | 0.566208E+10 | 0.965694E+09 | 0.00 | 0.965694E+09 | 0.00 | 0.00 |
February | 93324353.62 | 0.478546E+10 | 0.132897E+10 | 0.00 | 0.132897E+10 | 0.00 | 0.00 |
March | 0.597589E+09 | 0.387209E+10 | 0.178434E+10 | 0.00 | 0.178434E+10 | 0.00 | 0.00 |
April | 0.120713E+10 | 0.269735E+10 | 0.220027E+10 | 8779947.19 | 0.219149E+10 | 0.00 | 0.00 |
May | 0.207898E+10 | 0.181868E+10 | 0.264182E+10 | 0.112028E+09 | 0.252980E+10 | 0.00 | 0.00 |
June | 0.332608E+10 | 0.114176E+10 | 0.307506E+10 | 0.261765E+09 | 0.281329E+10 | 0.00 | 0.00 |
July | 0.368394E+10 | 0.826852E+09 | 0.294761E+10 | 0.190275E+09 | 0.275733E+10 | 0.00 | 0.00 |
August | 0.300957E+10 | 0.109922E+10 | 0.255050E+10 | 38800324.88 | 0.251170E+10 | 0.00 | 0.00 |
September | 0.169765E+10 | 0.174832E+10 | 0.187837E+10 | 390244.61 | 0.187798E+10 | 0.00 | 0.00 |
October | 0.707900E+09 | 0.281882E+10 | 0.145097E+10 | 0.00 | 0.145097E+10 | 0.00 | 0.00 |
November | 0.207764E+09 | 0.345530E+10 | 0.943564E+09 | 0.00 | 0.943564E+09 | 0.00 | 0.00 |
December | 15850049.82 | 0.541008E+10 | 0.903860E+09 | 0.00 | 0.903860E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.166387E+11 | 0.353360E+11 | 0.226710E+11 | 0.612038E+09 | 0.220590E+11 | 0.00 | 0.00 |
Minimum of Months | 12917111.43 | 0.826852E+09 | 0.903860E+09 | 0.00 | 0.903860E+09 | 0.00 | 0.00 |
Maximum of Months | 0.368394E+10 | 0.566208E+10 | 0.307506E+10 | 0.261765E+09 | 0.281329E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.472191E+09 | 0.342769E+10 | 0.117815E+10 | 0.379902E+09 | 0.798249E+09 | 0.00 | 0.00 |
February | 0.763137E+09 | 0.293464E+10 | 0.156141E+10 | 0.468541E+09 | 0.109287E+10 | 0.00 | 0.00 |
March | 0.195465E+10 | 0.239087E+10 | 0.248065E+10 | 0.103888E+10 | 0.144177E+10 | 0.00 | 0.00 |
April | 0.299159E+10 | 0.171891E+10 | 0.317738E+10 | 0.140394E+10 | 0.177344E+10 | 0.00 | 0.00 |
May | 0.398908E+10 | 0.123858E+10 | 0.367846E+10 | 0.162718E+10 | 0.205128E+10 | 0.00 | 0.00 |
June | 0.482596E+10 | 0.779485E+09 | 0.397570E+10 | 0.175706E+10 | 0.221864E+10 | 0.00 | 0.00 |
July | 0.514365E+10 | 0.559611E+09 | 0.394497E+10 | 0.173692E+10 | 0.220806E+10 | 0.00 | 0.00 |
August | 0.454452E+10 | 0.733854E+09 | 0.356274E+10 | 0.149545E+10 | 0.206730E+10 | 0.00 | 0.00 |
September | 0.329977E+10 | 0.112420E+10 | 0.286918E+10 | 0.127266E+10 | 0.159652E+10 | 0.00 | 0.00 |
October | 0.178953E+10 | 0.179072E+10 | 0.201188E+10 | 0.832167E+09 | 0.117971E+10 | 0.00 | 0.00 |
November | 0.688055E+09 | 0.220758E+10 | 0.110436E+10 | 0.354266E+09 | 0.750094E+09 | 0.00 | 0.00 |
December | 0.247074E+09 | 0.338018E+10 | 0.918702E+09 | 0.189824E+09 | 0.728878E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.307092E+11 | 0.222863E+11 | 0.304636E+11 | 0.125568E+11 | 0.179068E+11 | 0.00 | 0.00 |
Minimum of Months | 0.247074E+09 | 0.559611E+09 | 0.918702E+09 | 0.189824E+09 | 0.728878E+09 | 0.00 | 0.00 |
Maximum of Months | 0.514365E+10 | 0.342769E+10 | 0.397570E+10 | 0.175706E+10 | 0.221864E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.340702E+10 | 0.486260E+10 | 0.415250E+10 | 0.242393E+10 | 0.172856E+10 | 0.00 | 0.00 |
February | 0.346994E+10 | 0.431445E+10 | 0.428229E+10 | 0.206488E+10 | 0.221741E+10 | 0.00 | 0.00 |
March | 0.572728E+10 | 0.361203E+10 | 0.578684E+10 | 0.325159E+10 | 0.253525E+10 | 0.00 | 0.00 |
April | 0.477327E+10 | 0.279978E+10 | 0.463782E+10 | 0.185329E+10 | 0.278453E+10 | 0.00 | 0.00 |
May | 0.467557E+10 | 0.200782E+10 | 0.419379E+10 | 0.121805E+10 | 0.297573E+10 | 0.00 | 0.00 |
June | 0.491201E+10 | 0.126103E+10 | 0.394356E+10 | 0.835659E+09 | 0.310790E+10 | 0.00 | 0.00 |
July | 0.573101E+10 | 0.902432E+09 | 0.415992E+10 | 0.100933E+10 | 0.315059E+10 | 0.00 | 0.00 |
August | 0.632995E+10 | 0.116829E+10 | 0.467020E+10 | 0.151420E+10 | 0.315600E+10 | 0.00 | 0.00 |
September | 0.656606E+10 | 0.178838E+10 | 0.525489E+10 | 0.255952E+10 | 0.269537E+10 | 0.00 | 0.00 |
October | 0.562579E+10 | 0.274043E+10 | 0.519575E+10 | 0.296792E+10 | 0.222784E+10 | 0.00 | 0.00 |
November | 0.343666E+10 | 0.328625E+10 | 0.360106E+10 | 0.203292E+10 | 0.156814E+10 | 0.00 | 0.00 |
December | 0.269776E+10 | 0.478987E+10 | 0.347231E+10 | 0.179708E+10 | 0.167523E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.573523E+11 | 0.335334E+11 | 0.533509E+11 | 0.235284E+11 | 0.298226E+11 | 0.00 | 0.00 |
Minimum of Months | 0.269776E+10 | 0.902432E+09 | 0.347231E+10 | 0.835659E+09 | 0.156814E+10 | 0.00 | 0.00 |
Maximum of Months | 0.656606E+10 | 0.486260E+10 | 0.578684E+10 | 0.325159E+10 | 0.315600E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.292789E+09 | 0.356259E+10 | 0.101083E+10 | 0.237304E+09 | 0.773529E+09 | 0.00 | 0.00 |
February | 0.663387E+09 | 0.303318E+10 | 0.147974E+10 | 0.380304E+09 | 0.109943E+10 | 0.00 | 0.00 |
March | 0.208134E+10 | 0.245753E+10 | 0.256771E+10 | 0.109944E+10 | 0.146828E+10 | 0.00 | 0.00 |
April | 0.287647E+10 | 0.179975E+10 | 0.304240E+10 | 0.124751E+10 | 0.179490E+10 | 0.00 | 0.00 |
May | 0.406644E+10 | 0.131545E+10 | 0.370864E+10 | 0.167606E+10 | 0.203257E+10 | 0.00 | 0.00 |
June | 0.533652E+10 | 0.850720E+09 | 0.433024E+10 | 0.203677E+10 | 0.229347E+10 | 0.00 | 0.00 |
July | 0.525339E+10 | 0.621158E+09 | 0.400044E+10 | 0.175393E+10 | 0.224651E+10 | 0.00 | 0.00 |
August | 0.467483E+10 | 0.787557E+09 | 0.361817E+10 | 0.153848E+10 | 0.207969E+10 | 0.00 | 0.00 |
September | 0.317923E+10 | 0.118565E+10 | 0.274972E+10 | 0.118749E+10 | 0.156224E+10 | 0.00 | 0.00 |
October | 0.161468E+10 | 0.185390E+10 | 0.184192E+10 | 0.648830E+09 | 0.119309E+10 | 0.00 | 0.00 |
November | 0.639454E+09 | 0.224820E+10 | 0.105632E+10 | 0.304393E+09 | 0.751925E+09 | 0.00 | 0.00 |
December | 0.281869E+09 | 0.343926E+10 | 0.946258E+09 | 0.206179E+09 | 0.740079E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.309604E+11 | 0.231550E+11 | 0.303524E+11 | 0.123167E+11 | 0.180357E+11 | 0.00 | 0.00 |
Minimum of Months | 0.281869E+09 | 0.621158E+09 | 0.946258E+09 | 0.206179E+09 | 0.740079E+09 | 0.00 | 0.00 |
Maximum of Months | 0.533652E+10 | 0.356259E+10 | 0.433024E+10 | 0.203677E+10 | 0.229347E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.562725E+10 | -0.488019E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -747061469.8 | 58.99 | 0.00 | 0.00 |
February | 0.516798E+10 | -0.449946E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -668528368.7 | 58.98 | 0.00 | 0.00 |
March | 0.596957E+10 | -0.525362E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -715949770.3 | 58.98 | 0.00 | 0.00 |
April | 0.522135E+10 | -0.454105E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -680301538.0 | 58.98 | 0.00 | 0.00 |
May | 0.528804E+10 | -0.459553E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692509304.0 | 58.98 | 0.00 | 0.00 |
June | 0.494987E+10 | -0.428186E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668000685.8 | 58.98 | 0.00 | 0.00 |
July | 0.452412E+10 | -0.383718E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -686945463.3 | 58.98 | 0.00 | 0.00 |
August | 0.485236E+10 | -0.416403E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688324608.4 | 58.98 | 0.00 | 0.00 |
September | 0.448391E+10 | -0.381728E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666627669.1 | 58.98 | 0.00 | 0.00 |
October | 0.483643E+10 | -0.413957E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -696861908.8 | 58.98 | 0.00 | 0.00 |
November | 0.502138E+10 | -0.433462E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -686758170.0 | 58.98 | 0.00 | 0.00 |
December | 0.528316E+10 | -0.454949E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -733673916.5 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.612254E+11 | -0.528939E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.833154E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.448391E+10 | -0.525362E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -747061469.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.596957E+10 | -0.381728E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -666627669.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.49 | 0.48 | 01-JAN-09:09 | 4409.99 | 32.57 | 236.00 | 250.83 | 3547.55 | 33.71 | 243.00 | 223.67 |
February | 262.50 | 0.49 | 0.48 | 01-FEB-09:39 | 5535.09 | 32.76 | 245.83 | 256.00 | 1857.02 | 26.99 | 240.67 | 237.50 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-07:30 | 7905.28 | 29.81 | 254.83 | 326.67 | 1499.97 | 21.81 | 189.33 | 294.00 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:00 | 2070.52 | 18.76 | 3.00 | 345.50 | 1163.89 | 20.95 | 200.33 | 311.50 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:30 | 1876.12 | 18.83 | 0.17 | 384.00 | 1106.58 | 21.09 | 184.00 | 337.17 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:10 | 1690.38 | 18.63 | 0.00 | 393.17 | 973.96 | 20.85 | 222.83 | 353.17 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-06:10 | 1773.28 | 18.66 | 1.00 | 399.67 | 1007.74 | 20.88 | 219.83 | 354.83 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:19 | 2103.04 | 19.14 | 4.50 | 377.17 | 1170.06 | 21.35 | 252.33 | 337.67 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3000.87 | 20.64 | 32.00 | 324.00 | 1543.80 | 21.98 | 220.00 | 292.17 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-07:19 | 6397.20 | 32.22 | 277.50 | 298.17 | 1578.78 | 22.39 | 196.33 | 276.67 |
November | 258.33 | 0.50 | 0.48 | 01-NOV-07:40 | 4149.34 | 32.38 | 240.17 | 240.50 | 1687.51 | 27.88 | 219.00 | 217.00 |
December | 230.67 | 0.49 | 0.48 | 01-DEC-08:09 | 3716.76 | 31.19 | 209.00 | 238.67 | 2910.88 | 33.07 | 223.33 | 208.00 |
Annual Sum or Average | 3928.50 | 0.50 | 3518.03 | 24.41 | 1504.00 | 3834.33 | 1549.75 | 23.65 | 2611.00 | 3443.33 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1690.38 | 18.63 | 0.00 | 238.67 | 973.96 | 20.85 | 184.00 | 208.00 | |
Maximum of Months | 439.00 | 0.50 | 0.48 | 7905.28 | 32.76 | 277.50 | 399.67 | 3547.55 | 33.71 | 252.33 | 354.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:09 | 1514.74 | 20.81 | 70.67 | 236.00 | 758.64 | 21.56 | 83.83 | 188.17 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:39 | 2093.95 | 21.96 | 83.33 | 248.17 | 1088.09 | 22.83 | 111.67 | 217.00 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:19 | 2821.96 | 21.66 | 104.33 | 319.67 | 1243.29 | 22.41 | 90.00 | 284.83 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:30 | 3064.73 | 21.09 | 104.33 | 350.33 | 1719.67 | 22.35 | 87.33 | 314.83 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-05:30 | 4094.18 | 22.57 | 103.50 | 391.67 | 1740.29 | 22.33 | 58.83 | 347.33 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-05:49 | 3723.57 | 21.82 | 133.17 | 402.67 | 1640.42 | 22.07 | 78.83 | 372.50 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-04:00 | 3520.87 | 21.96 | 135.17 | 409.33 | 1553.38 | 22.08 | 80.17 | 371.33 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:49 | 3243.51 | 21.35 | 110.33 | 378.33 | 1449.14 | 22.31 | 76.83 | 345.67 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3305.47 | 22.80 | 85.83 | 323.50 | 1822.47 | 23.77 | 101.17 | 288.33 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-06:00 | 2095.18 | 20.80 | 81.50 | 288.00 | 1134.61 | 22.64 | 94.33 | 254.00 |
November | 258.33 | 0.51 | 0.48 | 01-NOV-07:40 | 1525.66 | 21.13 | 87.00 | 229.83 | 837.79 | 21.96 | 91.00 | 178.00 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-07:00 | 1305.58 | 20.08 | 60.33 | 225.83 | 656.02 | 21.04 | 68.83 | 173.33 |
Annual Sum or Average | 3928.50 | 0.50 | 2842.58 | 21.55 | 1159.50 | 3803.33 | 1360.72 | 22.29 | 1022.83 | 3335.33 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1305.58 | 20.08 | 60.33 | 225.83 | 656.02 | 21.04 | 58.83 | 173.33 | |
Maximum of Months | 439.00 | 0.51 | 0.48 | 4094.18 | 22.80 | 135.17 | 409.33 | 1822.47 | 23.77 | 111.67 | 372.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.48 | 01-JAN-10:20 | 652.27 | 15.89 | 0.00 | 220.17 | 366.45 | 18.14 | 0.00 | 135.67 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-10:20 | 857.00 | 16.98 | 0.00 | 241.83 | 478.49 | 19.13 | 0.50 | 191.33 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-08:09 | 906.58 | 17.54 | 0.00 | 313.50 | 532.80 | 19.77 | 2.33 | 265.50 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:49 | 1045.75 | 18.10 | 0.00 | 349.83 | 617.56 | 20.21 | 57.00 | 315.50 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-05:00 | 1256.64 | 20.30 | 26.50 | 401.50 | 763.84 | 22.42 | 161.33 | 362.67 |
June | 430.67 | 0.49 | 0.48 | 01-JUN-05:00 | 1406.69 | 21.74 | 80.83 | 412.83 | 826.47 | 22.67 | 234.50 | 389.00 |
July | 439.00 | 0.49 | 0.48 | 01-JUL-05:19 | 1338.40 | 21.41 | 75.17 | 419.00 | 784.55 | 22.41 | 232.83 | 389.17 |
August | 406.00 | 0.49 | 0.48 | 01-AUG-05:00 | 1184.65 | 18.82 | 0.00 | 387.00 | 705.91 | 20.97 | 138.50 | 353.67 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 989.84 | 18.34 | 0.00 | 320.50 | 614.69 | 20.56 | 40.50 | 272.17 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:40 | 795.65 | 16.74 | 0.00 | 280.83 | 459.56 | 18.97 | 0.33 | 221.67 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-08:20 | 632.64 | 15.37 | 0.00 | 217.33 | 353.64 | 17.52 | 0.00 | 126.83 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-11:00 | 656.75 | 15.82 | 0.00 | 207.33 | 360.77 | 17.99 | 0.00 | 117.17 |
Annual Sum or Average | 3928.50 | 0.50 | 1025.88 | 18.46 | 182.50 | 3771.67 | 602.41 | 20.37 | 867.83 | 3140.33 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 632.64 | 15.37 | 0.00 | 207.33 | 353.64 | 17.52 | 0.00 | 117.17 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 1406.69 | 21.74 | 80.83 | 419.00 | 826.47 | 22.67 | 234.50 | 389.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:00 | 1419.14 | 21.25 | 85.83 | 234.83 | 774.14 | 22.20 | 86.50 | 188.50 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-10:09 | 1916.63 | 20.38 | 68.17 | 247.50 | 1037.53 | 22.70 | 96.33 | 217.00 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-08:09 | 2770.71 | 21.50 | 101.67 | 321.83 | 1568.08 | 22.73 | 98.33 | 286.67 |
April | 371.17 | 0.50 | 0.48 | 01-APR-07:19 | 3279.77 | 20.84 | 104.67 | 346.17 | 1392.37 | 20.87 | 55.33 | 312.17 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:40 | 3511.46 | 18.14 | 43.00 | 390.33 | 1945.35 | 18.88 | 0.00 | 352.83 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:30 | 3713.55 | 17.90 | 52.83 | 400.83 | 1601.45 | 18.85 | 0.17 | 369.50 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-06:10 | 3312.96 | 17.96 | 54.83 | 407.00 | 1508.05 | 19.03 | 5.83 | 370.83 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:30 | 3101.20 | 19.90 | 85.50 | 382.67 | 1685.23 | 21.27 | 62.67 | 346.17 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3388.78 | 22.38 | 83.50 | 321.67 | 1498.52 | 22.17 | 68.50 | 290.00 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-07:00 | 1965.70 | 20.48 | 79.67 | 287.50 | 1055.88 | 22.41 | 91.50 | 254.00 |
November | 258.33 | 0.52 | 0.48 | 01-NOV-08:20 | 1458.06 | 20.75 | 86.83 | 228.00 | 778.04 | 21.53 | 82.00 | 181.17 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-11:39 | 1348.99 | 19.72 | 56.33 | 221.17 | 725.20 | 21.69 | 72.00 | 173.00 |
Annual Sum or Average | 3928.50 | 0.50 | 2745.98 | 19.94 | 902.83 | 3789.50 | 1357.87 | 21.00 | 719.17 | 3341.83 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1348.99 | 17.90 | 43.00 | 221.17 | 725.20 | 18.85 | 0.00 | 173.00 | |
Maximum of Months | 439.00 | 0.52 | 0.48 | 3713.55 | 22.38 | 104.67 | 407.00 | 1945.35 | 22.73 | 98.33 | 370.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.49 | 0.48 | 01-JAN-09:09 | 4276.44 | 32.11 | 233.33 | 248.33 | 3450.68 | 33.23 | 233.00 | 221.17 |
February | 262.50 | 0.49 | 0.48 | 01-FEB-09:50 | 5389.36 | 32.39 | 241.83 | 254.50 | 1755.52 | 24.97 | 107.00 | 235.67 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-07:30 | 7766.52 | 28.70 | 234.67 | 325.67 | 1398.15 | 19.03 | 19.00 | 291.17 |
April | 371.17 | 0.51 | 0.48 | 01-APR-06:00 | 1971.60 | 14.92 | 0.00 | 343.50 | 1093.86 | 18.40 | 10.83 | 308.83 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:30 | 1791.55 | 15.19 | 0.00 | 380.67 | 1048.88 | 18.76 | 3.83 | 333.17 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-06:10 | 1620.29 | 15.03 | 0.00 | 390.33 | 928.82 | 18.53 | 0.17 | 350.00 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-06:19 | 1698.13 | 14.99 | 0.00 | 397.17 | 958.47 | 18.48 | 6.83 | 351.33 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:19 | 2007.98 | 15.41 | 0.00 | 374.17 | 1105.40 | 18.89 | 17.67 | 334.17 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2860.03 | 17.08 | 17.00 | 321.83 | 1441.02 | 19.51 | 28.17 | 289.00 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-07:19 | 6263.65 | 31.62 | 270.67 | 297.50 | 1478.04 | 19.50 | 25.17 | 274.67 |
November | 258.33 | 0.50 | 0.48 | 01-NOV-07:40 | 4030.02 | 32.04 | 237.50 | 239.50 | 1604.13 | 26.20 | 135.33 | 215.00 |
December | 230.67 | 0.49 | 0.48 | 01-DEC-08:09 | 3573.39 | 29.71 | 195.33 | 236.33 | 2823.84 | 32.68 | 216.83 | 206.50 |
Annual Sum or Average | 3928.50 | 0.50 | 3407.92 | 21.98 | 1430.33 | 3809.50 | 1473.03 | 21.48 | 803.83 | 3410.67 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1620.29 | 14.92 | 0.00 | 236.33 | 928.82 | 18.40 | 0.17 | 206.50 | |
Maximum of Months | 439.00 | 0.51 | 0.48 | 7766.52 | 32.39 | 270.67 | 397.17 | 3450.68 | 33.23 | 233.00 | 351.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:09 | 1469.47 | 20.29 | 70.00 | 234.67 | 724.47 | 21.30 | 77.50 | 183.83 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:50 | 1994.70 | 20.22 | 69.33 | 246.17 | 1042.95 | 22.61 | 98.00 | 214.33 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:30 | 2740.95 | 21.10 | 103.17 | 317.17 | 1187.98 | 22.20 | 79.50 | 281.17 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:30 | 2981.93 | 20.63 | 104.00 | 348.67 | 1655.21 | 22.16 | 81.83 | 311.50 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-05:30 | 3997.94 | 22.12 | 103.50 | 389.17 | 1666.27 | 22.15 | 58.00 | 344.17 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-05:00 | 3634.38 | 21.38 | 132.83 | 400.33 | 1573.95 | 21.90 | 76.83 | 369.33 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-04:00 | 3432.47 | 21.52 | 135.17 | 406.83 | 1487.26 | 21.91 | 77.50 | 369.33 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:49 | 3156.72 | 20.89 | 110.17 | 376.83 | 1382.38 | 22.14 | 69.33 | 342.83 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3212.71 | 22.34 | 85.83 | 322.33 | 1749.37 | 23.58 | 87.17 | 284.00 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-06:00 | 2033.20 | 20.32 | 81.17 | 286.00 | 1086.18 | 22.42 | 83.50 | 249.50 |
November | 258.33 | 0.52 | 0.48 | 01-NOV-07:40 | 1482.13 | 20.68 | 86.83 | 227.83 | 805.93 | 21.73 | 84.67 | 173.00 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-08:09 | 1265.44 | 19.58 | 59.67 | 224.33 | 626.96 | 20.78 | 63.67 | 169.00 |
Annual Sum or Average | 3928.50 | 0.50 | 2764.42 | 21.00 | 1141.67 | 3780.33 | 1303.73 | 22.09 | 937.50 | 3292.00 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1265.44 | 19.58 | 59.67 | 224.33 | 626.96 | 20.78 | 58.00 | 169.00 | |
Maximum of Months | 439.00 | 0.52 | 0.48 | 3997.94 | 22.34 | 135.17 | 406.83 | 1749.37 | 23.58 | 98.00 | 369.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.48 | 01-JAN-10:30 | 628.20 | 11.90 | 0.00 | 216.67 | 352.78 | 15.49 | 0.00 | 125.83 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-10:30 | 826.59 | 13.26 | 0.00 | 240.00 | 461.15 | 16.68 | 0.00 | 186.50 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-08:09 | 874.73 | 14.02 | 0.00 | 311.17 | 515.32 | 17.53 | 0.00 | 259.67 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:49 | 1014.56 | 14.65 | 0.00 | 349.17 | 597.48 | 18.09 | 0.17 | 310.67 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-05:00 | 1213.03 | 17.20 | 26.17 | 399.67 | 740.05 | 20.54 | 40.00 | 359.17 |
June | 430.67 | 0.49 | 0.48 | 01-JUN-05:00 | 1357.26 | 18.94 | 74.50 | 411.83 | 798.28 | 20.67 | 69.50 | 386.67 |
July | 439.00 | 0.49 | 0.48 | 01-JUL-05:19 | 1291.34 | 18.55 | 71.00 | 418.00 | 757.88 | 20.40 | 61.83 | 386.00 |
August | 406.00 | 0.49 | 0.48 | 01-AUG-05:00 | 1142.53 | 15.40 | 0.00 | 385.33 | 682.64 | 18.90 | 11.33 | 349.50 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 953.81 | 15.22 | 0.00 | 319.00 | 595.57 | 18.72 | 0.00 | 267.00 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:49 | 767.15 | 13.06 | 0.00 | 277.83 | 443.69 | 16.56 | 0.00 | 214.67 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-08:20 | 609.53 | 11.43 | 0.00 | 214.17 | 340.49 | 14.88 | 0.00 | 118.83 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-11:00 | 632.78 | 11.79 | 0.00 | 204.67 | 346.96 | 15.31 | 0.00 | 108.50 |
Annual Sum or Average | 3928.50 | 0.50 | 990.01 | 15.06 | 171.67 | 3747.50 | 582.12 | 18.16 | 182.83 | 3073.00 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 609.53 | 11.43 | 0.00 | 204.67 | 340.49 | 14.88 | 0.00 | 108.50 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 1357.26 | 18.94 | 74.50 | 418.00 | 798.28 | 20.67 | 69.50 | 386.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.51 | 0.48 | 01-JAN-09:00 | 1379.95 | 20.88 | 85.00 | 233.33 | 745.46 | 22.10 | 85.00 | 182.33 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-10:20 | 1858.71 | 19.97 | 68.17 | 246.83 | 994.48 | 22.60 | 95.00 | 214.33 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-08:09 | 2698.14 | 21.09 | 101.50 | 320.50 | 1509.44 | 22.60 | 94.83 | 284.33 |
April | 371.17 | 0.50 | 0.48 | 01-APR-07:19 | 3142.96 | 20.41 | 104.33 | 343.83 | 1332.74 | 20.72 | 53.50 | 309.50 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:40 | 3405.90 | 17.65 | 43.00 | 388.83 | 1853.04 | 18.71 | 0.00 | 348.67 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:30 | 3567.43 | 17.41 | 52.67 | 399.17 | 1525.89 | 18.67 | 0.00 | 366.67 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-06:19 | 3186.66 | 17.47 | 54.67 | 404.00 | 1439.77 | 18.86 | 3.67 | 369.00 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:30 | 3015.25 | 19.45 | 85.50 | 379.83 | 1618.30 | 21.12 | 59.50 | 341.83 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3302.57 | 21.95 | 83.50 | 320.17 | 1428.94 | 22.04 | 65.17 | 287.67 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:00 | 1907.40 | 20.06 | 78.67 | 286.17 | 1011.40 | 22.30 | 89.33 | 250.83 |
November | 258.33 | 0.52 | 0.48 | 01-NOV-08:20 | 1417.04 | 20.38 | 86.50 | 226.00 | 748.18 | 21.42 | 81.17 | 175.33 |
December | 230.67 | 0.51 | 0.48 | 01-DEC-11:50 | 1306.76 | 19.14 | 53.67 | 219.33 | 695.59 | 21.58 | 71.17 | 167.17 |
Annual Sum or Average | 3928.50 | 0.50 | 2656.24 | 19.49 | 897.17 | 3768.00 | 1299.41 | 20.86 | 698.33 | 3297.67 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1306.76 | 17.41 | 43.00 | 219.33 | 695.59 | 18.67 | 0.00 | 167.17 | |
Maximum of Months | 439.00 | 0.52 | 0.48 | 3567.43 | 21.95 | 104.33 | 404.00 | 1853.04 | 22.60 | 95.00 | 369.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.49 | 0.48 | 01-JAN-09:09 | 4276.41 | 32.11 | 233.33 | 248.33 | 3450.58 | 33.23 | 233.00 | 221.17 |
February | 262.50 | 0.49 | 0.48 | 01-FEB-09:50 | 5389.27 | 32.39 | 241.83 | 254.50 | 1755.39 | 24.97 | 107.00 | 235.67 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-07:30 | 7766.41 | 28.70 | 234.67 | 325.67 | 1398.05 | 19.03 | 19.00 | 291.17 |
April | 371.17 | 0.51 | 0.48 | 01-APR-06:00 | 1971.48 | 14.92 | 0.00 | 343.50 | 1093.77 | 18.40 | 10.83 | 308.83 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:30 | 1791.46 | 15.20 | 0.00 | 380.67 | 1048.81 | 18.77 | 3.83 | 333.17 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-06:10 | 1620.20 | 15.03 | 0.00 | 390.33 | 928.75 | 18.53 | 0.17 | 350.00 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-06:19 | 1698.03 | 14.99 | 0.00 | 397.17 | 958.40 | 18.48 | 6.83 | 351.33 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:19 | 2007.86 | 15.41 | 0.00 | 374.17 | 1105.31 | 18.89 | 17.67 | 334.17 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2859.89 | 17.08 | 17.00 | 321.83 | 1440.91 | 19.51 | 28.17 | 289.00 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-07:19 | 6263.56 | 31.62 | 270.67 | 297.50 | 1477.93 | 19.50 | 25.17 | 274.67 |
November | 258.33 | 0.50 | 0.48 | 01-NOV-07:40 | 4029.97 | 32.04 | 237.50 | 239.50 | 1604.03 | 26.20 | 135.33 | 215.00 |
December | 230.67 | 0.49 | 0.48 | 01-DEC-08:09 | 3573.35 | 29.71 | 195.33 | 236.33 | 2823.74 | 32.68 | 216.83 | 206.50 |
Annual Sum or Average | 3928.50 | 0.50 | 3407.83 | 21.98 | 1430.33 | 3809.50 | 1472.94 | 21.48 | 803.83 | 3410.67 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1620.20 | 14.92 | 0.00 | 236.33 | 928.75 | 18.40 | 0.17 | 206.50 | |
Maximum of Months | 439.00 | 0.51 | 0.48 | 7766.41 | 32.39 | 270.67 | 397.17 | 3450.58 | 33.23 | 233.00 | 351.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:09 | 1469.43 | 20.30 | 70.00 | 234.67 | 724.42 | 21.30 | 77.50 | 183.83 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:50 | 1994.64 | 20.22 | 69.33 | 246.17 | 1042.88 | 22.61 | 98.00 | 214.33 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:30 | 2740.90 | 21.10 | 103.17 | 317.17 | 1187.91 | 22.20 | 79.50 | 281.17 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:30 | 2981.86 | 20.63 | 104.00 | 348.67 | 1655.14 | 22.16 | 82.17 | 311.50 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-05:30 | 3997.88 | 22.13 | 103.50 | 389.17 | 1666.19 | 22.15 | 58.17 | 344.17 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-05:00 | 3634.32 | 21.38 | 132.83 | 400.33 | 1573.87 | 21.90 | 76.83 | 369.33 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-04:00 | 3432.40 | 21.52 | 135.17 | 406.83 | 1487.18 | 21.91 | 77.50 | 369.17 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:49 | 3156.66 | 20.89 | 110.17 | 376.83 | 1382.30 | 22.14 | 69.33 | 342.83 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3212.67 | 22.34 | 85.83 | 322.33 | 1749.29 | 23.58 | 87.17 | 284.00 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-06:00 | 2033.15 | 20.32 | 81.17 | 286.00 | 1086.12 | 22.42 | 83.67 | 249.50 |
November | 258.33 | 0.52 | 0.48 | 01-NOV-07:40 | 1482.09 | 20.68 | 86.83 | 227.83 | 805.88 | 21.73 | 84.67 | 173.00 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-08:09 | 1265.40 | 19.58 | 59.67 | 224.33 | 626.91 | 20.78 | 63.83 | 169.00 |
Annual Sum or Average | 3928.50 | 0.50 | 2764.36 | 21.00 | 1141.67 | 3780.33 | 1303.66 | 22.09 | 938.33 | 3291.83 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1265.40 | 19.58 | 59.67 | 224.33 | 626.91 | 20.78 | 58.17 | 169.00 | |
Maximum of Months | 439.00 | 0.52 | 0.48 | 3997.88 | 22.34 | 135.17 | 406.83 | 1749.29 | 23.58 | 98.00 | 369.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.48 | 01-JAN-10:30 | 628.17 | 11.90 | 0.00 | 216.67 | 352.76 | 15.49 | 0.00 | 125.83 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-10:30 | 826.55 | 13.26 | 0.00 | 240.00 | 461.11 | 16.69 | 0.00 | 186.50 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-08:09 | 874.69 | 14.02 | 0.00 | 311.17 | 515.28 | 17.53 | 0.00 | 259.67 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:49 | 1014.52 | 14.65 | 0.00 | 349.17 | 597.44 | 18.09 | 0.17 | 310.67 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-05:00 | 1213.01 | 17.20 | 26.17 | 399.67 | 740.01 | 20.54 | 40.00 | 359.17 |
June | 430.67 | 0.49 | 0.48 | 01-JUN-05:00 | 1357.21 | 18.94 | 74.50 | 411.83 | 798.23 | 20.67 | 69.67 | 386.67 |
July | 439.00 | 0.49 | 0.48 | 01-JUL-05:19 | 1291.29 | 18.56 | 71.00 | 418.00 | 757.83 | 20.40 | 61.83 | 386.00 |
August | 406.00 | 0.49 | 0.48 | 01-AUG-05:00 | 1142.48 | 15.40 | 0.00 | 385.33 | 682.59 | 18.91 | 11.33 | 349.33 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 953.79 | 15.22 | 0.00 | 319.00 | 595.53 | 18.72 | 0.00 | 267.00 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:49 | 767.12 | 13.06 | 0.00 | 277.83 | 443.65 | 16.57 | 0.00 | 214.67 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-08:20 | 609.50 | 11.43 | 0.00 | 214.17 | 340.46 | 14.88 | 0.00 | 118.83 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-11:00 | 632.74 | 11.79 | 0.00 | 204.67 | 346.93 | 15.31 | 0.00 | 108.50 |
Annual Sum or Average | 3928.50 | 0.50 | 989.98 | 15.06 | 171.67 | 3747.50 | 582.08 | 18.16 | 183.00 | 3072.83 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 609.50 | 11.43 | 0.00 | 204.67 | 340.46 | 14.88 | 0.00 | 108.50 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 1357.21 | 18.94 | 74.50 | 418.00 | 798.23 | 20.67 | 69.67 | 386.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.51 | 0.48 | 01-JAN-09:00 | 1379.90 | 20.88 | 85.00 | 233.33 | 745.41 | 22.10 | 85.00 | 182.33 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-10:20 | 1858.65 | 19.97 | 68.17 | 246.83 | 994.42 | 22.60 | 95.00 | 214.33 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-08:09 | 2698.09 | 21.09 | 101.50 | 320.50 | 1509.37 | 22.61 | 94.83 | 284.33 |
April | 371.17 | 0.50 | 0.48 | 01-APR-07:19 | 3142.89 | 20.41 | 104.33 | 343.83 | 1332.66 | 20.72 | 53.67 | 309.50 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:40 | 3405.85 | 17.65 | 43.00 | 388.83 | 1852.97 | 18.71 | 0.00 | 348.67 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:30 | 3567.36 | 17.41 | 52.67 | 399.17 | 1525.81 | 18.67 | 0.00 | 366.67 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-06:19 | 3186.59 | 17.47 | 54.67 | 404.00 | 1439.69 | 18.86 | 3.67 | 369.00 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:30 | 3015.17 | 19.45 | 85.50 | 379.83 | 1618.22 | 21.12 | 59.50 | 341.83 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3302.53 | 21.96 | 83.50 | 320.17 | 1428.87 | 22.04 | 65.33 | 287.67 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:00 | 1907.35 | 20.06 | 78.67 | 286.17 | 1011.34 | 22.30 | 89.50 | 250.83 |
November | 258.33 | 0.52 | 0.48 | 01-NOV-08:20 | 1416.99 | 20.38 | 86.50 | 226.00 | 748.13 | 21.42 | 81.33 | 175.33 |
December | 230.67 | 0.51 | 0.48 | 01-DEC-11:50 | 1306.72 | 19.14 | 53.67 | 219.33 | 695.54 | 21.58 | 71.17 | 167.17 |
Annual Sum or Average | 3928.50 | 0.50 | 2656.18 | 19.49 | 897.17 | 3768.00 | 1299.34 | 20.86 | 699.00 | 3297.67 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1306.72 | 17.41 | 43.00 | 219.33 | 695.54 | 18.67 | 0.00 | 167.17 | |
Maximum of Months | 439.00 | 0.52 | 0.48 | 3567.36 | 21.96 | 104.33 | 404.00 | 1852.97 | 22.61 | 95.00 | 369.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.657127E+09 | 20782.20 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 32892469.95 | 20782.20 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20668942.34 | 20782.20 | 11-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.710689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.657127E+09 | 20782.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.837547E+10 | 11557.58 | 11-JAN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.723254E+10 | 12528.60 | 07-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.401948E+10 | 11616.40 | 07-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214677E+10 | 11517.62 | 28-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.741725E+09 | 11530.35 | 12-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156354E+09 | 11844.50 | 14-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9058281.49 | 4261.78 | 07-JUL-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30068984.90 | 6288.60 | 31-AUG-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196668E+09 | 11651.55 | 05-SEP-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109143E+10 | 11592.21 | 05-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.290348E+10 | 11539.18 | 20-NOV-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.706812E+10 | 12348.45 | 11-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.339712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9058281.49 | 4261.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.837547E+10 | 12528.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.326244E+10 | 9543.04 | 09-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.262864E+10 | 9557.15 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.829894E+09 | 9634.14 | 07-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105825E+09 | 9515.84 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13326389.72 | 9484.43 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.295857E+09 | 9524.93 | 20-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.245436E+10 | 9546.52 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.959033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.326244E+10 | 9634.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.558504E+10 | 7782.90 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.473991E+10 | 8439.48 | 07-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.234804E+10 | 7824.63 | 07-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.460282E+09 | 7764.04 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3385400.35 | 4911.10 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 46267935.63 | 7723.00 | 16-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.595087E+09 | 7753.98 | 14-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.398749E+10 | 8320.15 | 11-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.558504E+10 | 8439.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.351189E+10 | 9990.00 | 09-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285988E+10 | 10004.78 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.935976E+09 | 10085.51 | 07-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153792E+09 | 9945.22 | 05-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 625875.39 | 1668.14 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16550235.89 | 9928.67 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.317600E+09 | 9960.50 | 21-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.249533E+10 | 9993.66 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.351189E+10 | 10085.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.339772E+10 | 24633.77 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.257795E+10 | 24633.77 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.320756E+09 | 24633.77 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 28165078.20 | 24633.77 | 17-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1694558.27 | 7539.45 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137216E+09 | 24633.77 | 13-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.222318E+10 | 24633.77 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.868669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.339772E+10 | 24633.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.378323E+10 | 13194.54 | 04-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.318187E+10 | 13176.21 | 27-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.795269E+09 | 13201.74 | 06-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165555E+09 | 13160.46 | 17-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 256658.59 | 1541.72 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 66054016.11 | 13013.67 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.595606E+09 | 13149.89 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.330587E+10 | 13182.48 | 13-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.378323E+10 | 13201.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.304469E+10 | 10614.21 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.250713E+10 | 10614.21 | 01-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.660602E+09 | 10614.21 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 76057941.52 | 10614.21 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 55776865.69 | 10614.21 | 17-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.492909E+09 | 10614.21 | 13-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271137E+10 | 10614.21 | 02-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.954853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.304469E+10 | 10614.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.539596E+10 | 8739.91 | 19-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.455499E+10 | 8845.92 | 07-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168135E+10 | 8700.29 | 06-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.234112E+09 | 8697.08 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122958E+09 | 8677.25 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.918990E+09 | 8702.92 | 14-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.453070E+10 | 8744.32 | 20-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.539596E+10 | 8845.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.337694E+10 | 10709.98 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.278346E+10 | 10709.98 | 01-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.808780E+09 | 10709.98 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123807E+09 | 10709.98 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 66943429.70 | 10709.98 | 17-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.548529E+09 | 10709.98 | 07-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.285337E+10 | 10709.98 | 02-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.337694E+10 | 10709.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.826704E+10 | 31717.12 | 19-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.681474E+10 | 31664.20 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225128E+10 | 31659.91 | 21-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.348874E+09 | 31748.30 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.206296E+09 | 31745.55 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152890E+10 | 31699.92 | 25-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.696612E+10 | 31748.27 | 19-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.263832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.826704E+10 | 31748.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.613080E+10 | 14502.42 | 18-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.542891E+10 | 14591.51 | 07-FEB-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.191743E+10 | 14443.02 | 13-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.557662E+09 | 14486.46 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20947594.66 | 11297.66 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6770208.88 | 9794.72 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.354286E+09 | 14484.52 | 16-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160430E+10 | 14468.05 | 20-NOV-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.578249E+10 | 14471.62 | 14-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.613080E+10 | 14591.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.488463E+10 | 11656.44 | 14-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.417347E+10 | 11686.86 | 15-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147330E+10 | 11675.44 | 13-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.272568E+09 | 11611.90 | 05-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3123433.70 | 3440.40 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4325404.08 | 7011.75 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271576E+09 | 11626.83 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127352E+10 | 11687.66 | 21-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.461115E+10 | 11698.75 | 14-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.488463E+10 | 11698.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.818729E+10 | 9966.15 | 18-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.710565E+10 | 10359.11 | 07-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.322907E+10 | 9989.80 | 14-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.716215E+09 | 9963.64 | 05-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14112972.72 | 9945.51 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10919342.74 | 9933.89 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.579987E+09 | 9959.58 | 11-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.222155E+10 | 9969.78 | 15-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.731681E+10 | 10061.32 | 11-DEC-08:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.818729E+10 | 10359.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.520005E+10 | 12777.79 | 14-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.447298E+10 | 12742.26 | 14-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171810E+10 | 12718.78 | 11-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.407869E+09 | 12729.03 | 05-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10584610.68 | 7031.00 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6775327.07 | 6694.07 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.331013E+09 | 12691.41 | 30-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135181E+10 | 12805.20 | 14-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.468630E+10 | 12824.22 | 14-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.520005E+10 | 12824.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.186712E+11 | 28979.17 | 04-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172443E+11 | 29230.47 | 06-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102945E+11 | 29230.47 | 07-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.282737E+10 | 18061.94 | 17-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101242E+09 | 7916.84 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1689400.09 | 1478.91 | 10-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14403805.47 | 2957.55 | 30-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130385E+10 | 14611.66 | 17-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.517244E+10 | 16702.45 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160506E+11 | 29230.47 | 11-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.716816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.186712E+11 | 29230.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.181026E+11 | 28799.55 | 04-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168216E+11 | 30639.63 | 06-FEB-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.105636E+11 | 26984.20 | 07-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.365719E+10 | 16376.10 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.219960E+09 | 7946.52 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11742858.32 | 2504.33 | 06-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 51477333.27 | 3855.34 | 06-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.220418E+10 | 16289.24 | 17-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.620298E+10 | 16907.96 | 24-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159319E+11 | 30639.63 | 11-DEC-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.737671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.181026E+11 | 30639.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.199413E+11 | 29512.47 | 04-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184434E+11 | 29512.47 | 06-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112059E+11 | 29512.47 | 07-MAR-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.400844E+10 | 18782.41 | 17-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.363814E+09 | 10656.59 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 39077259.37 | 3844.38 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105692E+09 | 4973.90 | 06-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.260458E+10 | 16560.72 | 17-OCT-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.674469E+10 | 17717.04 | 24-NOV-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176484E+11 | 29512.47 | 11-DEC-08:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.811053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.199413E+11 | 29512.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.180352E+10 | 0.147785E+10 | 29548.89 | 15-MAR-14:00 | 29548.89 | 0.00 |
April | 0.00 | 0.00 | 0.205654E+10 | 0.195557E+10 | 19201.38 | 26-APR-14:10 | 19201.38 | 0.00 |
May | 0.00 | 0.00 | 0.801113E+10 | 0.732075E+10 | 37874.57 | 23-MAY-14:30 | 37874.57 | 0.00 |
June | 0.00 | 0.00 | 0.362604E+11 | 0.275349E+11 | 100883.75 | 27-JUN-07:40 | 43541.76 | 0.00 |
July | 0.00 | 0.00 | 0.641728E+11 | 0.456618E+11 | 114412.15 | 20-JUL-04:03 | 45923.90 | 0.00 |
August | 0.00 | 0.00 | 0.547863E+11 | 0.426165E+11 | 114387.47 | 14-AUG-08:00 | 49097.62 | 0.00 |
September | 0.00 | 0.00 | 0.243146E+11 | 0.184727E+11 | 80242.57 | 15-SEP-11:10 | 44689.12 | 0.00 |
October | 0.00 | 0.00 | 0.396399E+10 | 0.352546E+10 | 31612.77 | 11-OCT-15:10 | 31612.77 | 0.00 |
November | 0.00 | 0.00 | 0.639820E+09 | 0.519924E+09 | 10316.36 | 01-NOV-12:30 | 10316.36 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.196009E+12 | 0.149085E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.641728E+11 | 0.456618E+11 | 114412.15 | 49097.62 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.171119E+10 | 0.140665E+10 | 33507.35 | 15-MAR-14:05 | 33507.35 | 0.00 |
April | 0.00 | 0.00 | 0.610301E+09 | 0.544156E+09 | 12646.81 | 07-APR-14:05 | 12646.81 | 0.00 |
May | 0.00 | 0.00 | 0.733910E+10 | 0.663066E+10 | 38508.29 | 23-MAY-14:30 | 38508.29 | 0.00 |
June | 0.00 | 0.00 | 0.340094E+11 | 0.257825E+11 | 94371.70 | 12-JUN-06:03 | 56657.10 | 0.00 |
July | 0.00 | 0.00 | 0.585588E+11 | 0.414434E+11 | 104779.09 | 20-JUL-06:03 | 43225.01 | 0.00 |
August | 0.00 | 0.00 | 0.477792E+11 | 0.371748E+11 | 104508.94 | 14-AUG-10:05 | 43271.21 | 0.00 |
September | 0.00 | 0.00 | 0.203327E+11 | 0.153381E+11 | 73092.03 | 15-SEP-11:00 | 39897.11 | 0.00 |
October | 0.00 | 0.00 | 0.217810E+10 | 0.180453E+10 | 26700.08 | 11-OCT-15:00 | 26700.08 | 0.00 |
November | 0.00 | 0.00 | 0.309780E+09 | 0.206241E+09 | 7288.35 | 16-NOV-18:00 | 4974.22 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.172829E+12 | 0.130331E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.585588E+11 | 0.414434E+11 | 104779.09 | 56657.10 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.187361E+10 | 0.156111E+10 | 39025.40 | 15-MAR-13:50 | 39025.40 | 0.00 |
April | 0.00 | 0.00 | 0.620457E+09 | 0.541424E+09 | 12904.26 | 08-APR-13:30 | 10731.79 | 0.00 |
May | 0.00 | 0.00 | 0.754256E+10 | 0.675395E+10 | 44151.33 | 10-MAY-14:30 | 44151.33 | 0.00 |
June | 0.00 | 0.00 | 0.356732E+11 | 0.270808E+11 | 84692.39 | 27-JUN-13:05 | 64676.69 | 0.00 |
July | 0.00 | 0.00 | 0.620074E+11 | 0.441129E+11 | 116404.43 | 20-JUL-06:03 | 48284.36 | 0.00 |
August | 0.00 | 0.00 | 0.497518E+11 | 0.386558E+11 | 114986.84 | 14-AUG-06:03 | 43898.61 | 0.00 |
September | 0.00 | 0.00 | 0.201619E+11 | 0.149646E+11 | 80422.77 | 15-SEP-12:50 | 44408.48 | 0.00 |
October | 0.00 | 0.00 | 0.204409E+10 | 0.164249E+10 | 25883.88 | 11-OCT-15:00 | 25883.88 | 0.00 |
November | 0.00 | 0.00 | 0.320450E+09 | 0.209606E+09 | 9664.35 | 27-NOV-07:03 | 8352.65 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.179995E+12 | 0.135523E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.620074E+11 | 0.441129E+11 | 116404.43 | 64676.69 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1974.83 | 6953.27 | 31-JAN-12:14 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2012.47 | 6978.06 | 14-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2117.33 | 6946.93 | 01-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1904.71 | 6716.53 | 06-APR-11:09 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1870.44 | 6416.50 | 02-MAY-11:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1808.26 | 6012.95 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1584.72 | 5665.94 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1711.47 | 5521.12 | 31-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1625.58 | 5696.41 | 29-SEP-11:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1698.85 | 6016.80 | 30-OCT-11:13 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1826.38 | 6399.60 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1849.77 | 6735.10 | 29-DEC-12:13 |
Annual Sum or Average | 0.00 | 1831.03 | ||||
Minimum of Months | 0.00 | 0.00 | 1584.72 | 5521.12 | ||
Maximum of Months | 0.00 | 0.00 | 2117.33 | 6978.06 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134714E+10 | 0.35 | 2674.47 | 02-JAN-05:01 | 0.82 |
February | 0.119267E+10 | 0.34 | 2674.47 | 06-FEB-07:01 | 0.82 |
March | 0.143011E+10 | 0.34 | 2124.96 | 15-MAR-13:50 | 0.72 |
April | 0.152483E+10 | 0.32 | 2522.95 | 24-APR-16:00 | 0.79 |
May | 0.237248E+10 | 0.36 | 5494.07 | 31-MAY-06:03 | 1.23 |
June | 0.428565E+10 | 0.50 | 8568.50 | 12-JUN-15:10 | 1.61 |
July | 0.558336E+10 | 0.55 | 11217.38 | 05-JUL-15:50 | 1.91 |
August | 0.568276E+10 | 0.56 | 11217.38 | 14-AUG-05:12 | 1.91 |
September | 0.367541E+10 | 0.45 | 7668.85 | 18-SEP-12:20 | 1.51 |
October | 0.188686E+10 | 0.33 | 4648.16 | 11-OCT-16:00 | 1.11 |
November | 0.132322E+10 | 0.31 | 2142.67 | 07-NOV-08:02 | 0.73 |
December | 0.122954E+10 | 0.32 | 2674.47 | 11-DEC-07:01 | 0.82 |
Annual Sum or Average | 0.315341E+11 | 0.40 | |||
Minimum of Months | 0.119267E+10 | 0.31 | 2124.96 | 0.72 | |
Maximum of Months | 0.568276E+10 | 0.56 | 11217.38 | 1.91 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.128254E+10 | 0.35 | 2699.58 | 02-JAN-05:01 | 0.88 |
February | 0.114384E+10 | 0.35 | 2699.58 | 02-FEB-07:01 | 0.88 |
March | 0.124112E+10 | 0.33 | 3155.08 | 15-MAR-14:05 | 0.95 |
April | 0.124736E+10 | 0.31 | 2948.66 | 21-APR-14:05 | 0.92 |
May | 0.216217E+10 | 0.37 | 5158.82 | 23-MAY-14:30 | 1.28 |
June | 0.401752E+10 | 0.51 | 9373.23 | 12-JUN-14:05 | 1.84 |
July | 0.505500E+10 | 0.55 | 10039.95 | 05-JUL-15:50 | 1.92 |
August | 0.476812E+10 | 0.54 | 10039.95 | 14-AUG-05:12 | 1.92 |
September | 0.278587E+10 | 0.42 | 7416.61 | 21-SEP-15:40 | 1.59 |
October | 0.131444E+10 | 0.31 | 3610.49 | 11-OCT-15:30 | 1.03 |
November | 0.101598E+10 | 0.30 | 2699.58 | 24-NOV-07:01 | 0.88 |
December | 0.119775E+10 | 0.34 | 2699.58 | 04-DEC-06:01 | 0.88 |
Annual Sum or Average | 0.272317E+11 | 0.39 | |||
Minimum of Months | 0.101598E+10 | 0.30 | 2699.58 | 0.88 | |
Maximum of Months | 0.505500E+10 | 0.55 | 10039.95 | 1.92 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.164851E+10 | 0.43 | 2481.37 | 02-JAN-05:01 | 0.76 |
February | 0.150373E+10 | 0.43 | 2481.37 | 01-FEB-06:11 | 0.76 |
March | 0.139484E+10 | 0.37 | 3019.20 | 15-MAR-13:50 | 0.84 |
April | 0.124147E+10 | 0.32 | 2596.17 | 21-APR-15:20 | 0.77 |
May | 0.193735E+10 | 0.35 | 4541.84 | 31-MAY-16:00 | 1.06 |
June | 0.356331E+10 | 0.45 | 8746.20 | 12-JUN-14:00 | 1.58 |
July | 0.451314E+10 | 0.48 | 10913.50 | 17-JUL-05:12 | 1.82 |
August | 0.413157E+10 | 0.47 | 10913.50 | 14-AUG-05:12 | 1.82 |
September | 0.231557E+10 | 0.37 | 6595.85 | 21-SEP-15:30 | 1.33 |
October | 0.124729E+10 | 0.31 | 2847.79 | 11-OCT-15:20 | 0.81 |
November | 0.110906E+10 | 0.32 | 2481.37 | 13-NOV-06:11 | 0.76 |
December | 0.154125E+10 | 0.40 | 2481.37 | 02-DEC-06:11 | 0.76 |
Annual Sum or Average | 0.261471E+11 | 0.39 | |||
Minimum of Months | 0.110906E+10 | 0.31 | 2481.37 | 0.76 | |
Maximum of Months | 0.451314E+10 | 0.48 | 10913.50 | 1.82 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:03 | 2.06 | 2.06 | 57.08 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:05 | 2.06 | 2.06 | 55.99 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 56.08 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:02 | 2.06 | 2.06 | 55.61 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 55.95 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:05 | 2.06 | 2.06 | 55.49 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 55.74 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 56.16 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:05 | 2.06 | 2.06 | 55.73 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.20 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 56.06 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:05 | 2.06 | 2.06 | 56.17 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 55.49 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.20 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 56.65 | 56.65 | 1974.83 | 6953.27 | 31-JAN-12:14 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.91 | 56.91 | 2012.47 | 6978.06 | 14-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.47 | 56.47 | 2117.33 | 6946.93 | 01-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.09 | 56.09 | 1904.71 | 6716.53 | 06-APR-11:09 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.03 | 57.03 | 1870.44 | 6416.50 | 02-MAY-11:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.21 | 56.21 | 1808.26 | 6012.95 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.21 | 56.21 | 1584.72 | 5665.94 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.10 | 57.10 | 1711.47 | 5521.12 | 31-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.26 | 56.26 | 1625.58 | 5696.41 | 29-SEP-11:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.55 | 56.55 | 1698.85 | 6016.80 | 30-OCT-11:13 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.59 | 56.59 | 1826.38 | 6399.60 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.24 | 57.24 | 1849.77 | 6735.10 | 29-DEC-12:13 |
Annual Sum or Average | 0.00 | 1831.03 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.09 | 56.09 | 1584.72 | 5521.12 | ||
Maximum of Months | 0.00 | 0.00 | 57.24 | 57.24 | 2117.33 | 6978.06 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.227391E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.186865E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.100256E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.495069E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.519580E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.132881E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.210695E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.189692E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.976124E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.411026E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.561444E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.172555E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.151666E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.411026E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.227391E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.202811E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.167492E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.594211E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.204439E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.405223E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.123103E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.191851E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.163697E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.775222E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.220980E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.379652E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.168222E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.127515E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.204439E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.202811E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.343183E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.294995E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.124593E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.371753E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.393698E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.123006E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.195329E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.162775E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.731673E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.354361E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.917974E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.309041E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.182987E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.354361E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.343183E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.134714E+10 | 0.00 | 0.400631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119267E+10 | 0.00 | 0.347382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143011E+10 | 0.180352E+10 | 0.184279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152483E+10 | 0.205654E+10 | 0.569404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.237248E+10 | 0.801113E+10 | 0.846979E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.428565E+10 | 0.362604E+11 | 0.158044E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.558336E+10 | 0.641728E+11 | 9058281.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.568276E+10 | 0.547863E+11 | 30068984.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.367541E+10 | 0.243146E+11 | 0.211072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.188686E+10 | 0.396399E+10 | 0.247143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132322E+10 | 0.639820E+09 | 0.928447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122954E+10 | 0.00 | 0.320765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.315341E+11 | 0.196009E+12 | 0.144011E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119267E+10 | 0.00 | 9058281.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.568276E+10 | 0.641728E+11 | 0.400631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.128254E+10 | 0.00 | 0.371011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114384E+10 | 0.00 | 0.324270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124112E+10 | 0.171119E+10 | 0.148303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124736E+10 | 0.610301E+09 | 0.428488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.216217E+10 | 0.733910E+10 | 0.220217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.401752E+10 | 0.340094E+11 | 11742858.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.505500E+10 | 0.585588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.476812E+10 | 0.477792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.278587E+10 | 0.203327E+11 | 51477333.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131444E+10 | 0.217810E+10 | 0.251761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101598E+10 | 0.309780E+09 | 0.889623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119775E+10 | 0.00 | 0.315563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.272317E+11 | 0.172829E+12 | 0.131897E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.101598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.505500E+10 | 0.585588E+11 | 0.371011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.164851E+10 | 0.00 | 0.526111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150373E+10 | 0.00 | 0.464391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139484E+10 | 0.187361E+10 | 0.217951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124147E+10 | 0.620457E+09 | 0.631163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.193735E+10 | 0.754256E+10 | 0.412583E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.356331E+10 | 0.356732E+11 | 39077259.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.451314E+10 | 0.620074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.413157E+10 | 0.497518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.231557E+10 | 0.201619E+11 | 0.134482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124729E+10 | 0.204409E+10 | 0.434774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110906E+10 | 0.320450E+09 | 0.147248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154125E+10 | 0.00 | 0.470113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.261471E+11 | 0.179995E+12 | 0.193827E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.451314E+10 | 0.620074E+11 | 0.526111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.134714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174939E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143011E+10 | 0.00 | 0.00 | 0.00 | 0.462068E+09 | 0.813339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152483E+10 | 0.00 | 0.00 | 0.00 | 0.559192E+09 | 0.286667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.237248E+10 | 0.00 | 0.00 | 0.00 | 0.207758E+10 | 0.745737E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.428565E+10 | 0.00 | 0.00 | 0.00 | 0.884609E+10 | 0.156354E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.558336E+10 | 0.00 | 0.00 | 0.00 | 0.154771E+11 | 9058281.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.568276E+10 | 0.00 | 0.00 | 0.00 | 0.132564E+11 | 30068984.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.367541E+10 | 0.00 | 0.00 | 0.00 | 0.588916E+10 | 0.196668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.188686E+10 | 0.00 | 0.00 | 0.00 | 0.105583E+10 | 0.116757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132322E+10 | 0.00 | 0.00 | 0.00 | 0.179194E+09 | 0.411203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.315341E+11 | 0.00 | 0.00 | 0.00 | 0.478026E+11 | 0.723293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9058281.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.568276E+10 | 0.00 | 0.00 | 0.00 | 0.154771E+11 | 0.213920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.128254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124112E+10 | 0.00 | 0.00 | 0.00 | 0.434227E+09 | 0.426676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124736E+10 | 0.00 | 0.00 | 0.00 | 0.169338E+09 | 0.627697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.216217E+10 | 0.00 | 0.00 | 0.00 | 0.188980E+10 | 256658.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.401752E+10 | 0.00 | 0.00 | 0.00 | 0.829281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.505500E+10 | 0.00 | 0.00 | 0.00 | 0.141301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.476812E+10 | 0.00 | 0.00 | 0.00 | 0.116016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.278587E+10 | 0.00 | 0.00 | 0.00 | 0.496635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131444E+10 | 0.00 | 0.00 | 0.00 | 0.581928E+09 | 0.313427E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101598E+10 | 0.00 | 0.00 | 0.00 | 87294261.82 | 0.269325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.272317E+11 | 0.00 | 0.00 | 0.00 | 0.421534E+11 | 0.581298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.101598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.505500E+10 | 0.00 | 0.00 | 0.00 | 0.141301E+11 | 0.189985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.164851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139484E+10 | 0.00 | 0.00 | 0.00 | 0.475238E+09 | 0.105892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124147E+10 | 0.00 | 0.00 | 0.00 | 0.172874E+09 | 0.230319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.193735E+10 | 0.00 | 0.00 | 0.00 | 0.195086E+10 | 48768611.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.356331E+10 | 0.00 | 0.00 | 0.00 | 0.873731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.451314E+10 | 0.00 | 0.00 | 0.00 | 0.150197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.413157E+10 | 0.00 | 0.00 | 0.00 | 0.121459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.231557E+10 | 0.00 | 0.00 | 0.00 | 0.497237E+10 | 28790282.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124729E+10 | 0.00 | 0.00 | 0.00 | 0.553161E+09 | 0.174316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110906E+10 | 0.00 | 0.00 | 0.00 | 90592925.33 | 0.798009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.261471E+11 | 0.00 | 0.00 | 0.00 | 0.441181E+11 | 0.112722E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.451314E+10 | 0.00 | 0.00 | 0.00 | 0.150197E+11 | 0.326698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.136943E+11 | 0.00 | 0.00 | 2203875.60 | 0.00 | 0.451056E+09 | 0.314767E+10 | 0.00 | 0.28 |
February | 0.126381E+11 | 0.00 | 0.00 | 2641893.75 | 0.00 | 11478170.80 | 0.356101E+10 | 0.00 | 0.29 |
March | 0.663818E+10 | 7447544.90 | 0.00 | 18250471.48 | 0.00 | 0.00 | 0.115934E+11 | 0.00 | 0.41 |
April | 0.215453E+10 | 0.00 | 0.00 | 27138158.84 | 0.00 | 0.00 | 0.142195E+11 | 0.00 | 0.46 |
May | 0.819946E+09 | 4243588.59 | 0.00 | 41199707.79 | 3335591.74 | 0.00 | 0.188767E+11 | 0.00 | 0.87 |
June | 0.386250E+09 | 0.164571E+10 | 0.00 | 35741024.94 | 0.181747E+09 | 0.00 | 0.121271E+11 | 0.00 | 1.07 |
July | 0.176053E+09 | 0.573498E+10 | 0.00 | 19419598.28 | 0.394963E+09 | 0.00 | 0.368677E+10 | 0.00 | 0.84 |
August | 0.300975E+09 | 0.317307E+10 | 0.00 | 35823659.88 | 0.150128E+09 | 0.00 | 0.799320E+10 | 0.00 | 1.02 |
September | 0.835952E+09 | 0.111800E+10 | 0.00 | 38266702.11 | 14750140.14 | 0.00 | 0.145166E+11 | 0.00 | 1.07 |
October | 0.758994E+09 | 0.00 | 0.00 | 36531231.22 | 402001.41 | 0.00 | 0.174824E+11 | 0.00 | 0.59 |
November | 0.326790E+10 | 0.00 | 0.00 | 20597047.99 | 3261124.66 | 0.00 | 0.128054E+11 | 0.00 | 0.40 |
December | 0.109596E+11 | 0.00 | 0.00 | 6527387.65 | 0.00 | 6506834.35 | 0.591250E+10 | 0.00 | 0.29 |
Annual Sum or Average | 0.526308E+11 | 0.116834E+11 | 0.00 | 0.284341E+09 | 0.748587E+09 | 0.469041E+09 | 0.125922E+12 | 0.00 | 0.63 |
Minimum of Months | 0.176053E+09 | 0.00 | 0.00 | 2203875.60 | 0.00 | 0.00 | 0.314767E+10 | 0.00 | 0.28 |
Maximum of Months | 0.136943E+11 | 0.573498E+10 | 0.00 | 41199707.79 | 0.394963E+09 | 0.451056E+09 | 0.188767E+11 | 0.00 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.141155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289333E+10 | 0.00 | 0.00 | 0.28 |
February | 0.130726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265928E+10 | 0.00 | 0.00 | 0.28 |
March | 0.133813E+11 | 2724725.59 | 0.00 | 2200810.72 | 3082762.79 | 0.177473E+09 | 0.142891E+10 | 0.00 | 0.33 |
April | 0.745414E+10 | 0.00 | 0.00 | 6109910.35 | 0.00 | 41760780.24 | 0.476597E+10 | 0.00 | 0.35 |
May | 0.254462E+10 | 823408.29 | 0.00 | 20021798.71 | 19456699.02 | 0.00 | 0.106574E+11 | 0.00 | 0.58 |
June | 0.709190E+09 | 0.122803E+10 | 0.00 | 22035731.12 | 0.169285E+09 | 0.00 | 0.769109E+10 | 0.00 | 0.74 |
July | 0.324402E+09 | 0.423088E+10 | 0.00 | 12825858.51 | 0.375437E+09 | 0.00 | 0.240488E+10 | 0.00 | 0.62 |
August | 0.538834E+09 | 0.227351E+10 | 0.00 | 22342477.44 | 0.147956E+09 | 0.00 | 0.504665E+10 | 0.00 | 0.70 |
September | 0.156340E+10 | 0.719667E+09 | 0.00 | 20392371.44 | 23090247.66 | 0.00 | 0.809199E+10 | 0.00 | 0.68 |
October | 0.598240E+10 | 0.00 | 0.00 | 8788334.07 | 2004774.92 | 893019.64 | 0.587775E+10 | 0.00 | 0.38 |
November | 0.105303E+11 | 0.00 | 0.00 | 870443.65 | 7175223.14 | 50158973.82 | 0.126798E+10 | 0.00 | 0.30 |
December | 0.141334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180155E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.843501E+11 | 0.845563E+10 | 0.00 | 0.115588E+09 | 0.747488E+09 | 0.762445E+10 | 0.472326E+11 | 0.00 | 0.46 |
Minimum of Months | 0.324402E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.141334E+11 | 0.423088E+10 | 0.00 | 22342477.44 | 0.375437E+09 | 0.289333E+10 | 0.106574E+11 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.752260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808154E+10 | 0.00 | 0.00 | 0.27 |
February | 0.799954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659556E+10 | 0.00 | 0.00 | 0.27 |
March | 0.114196E+11 | 112030.28 | 0.00 | 1893907.32 | 0.00 | 0.173976E+10 | 0.927746E+09 | 0.00 | 0.32 |
April | 0.836540E+10 | 0.00 | 0.00 | 3574473.24 | 0.00 | 0.189543E+09 | 0.308481E+10 | 0.00 | 0.34 |
May | 0.341354E+10 | 2124795.90 | 0.00 | 17085150.51 | 15538511.17 | 0.00 | 0.933866E+10 | 0.00 | 0.56 |
June | 0.104052E+10 | 0.118520E+10 | 0.00 | 20680257.71 | 0.180587E+09 | 0.00 | 0.737493E+10 | 0.00 | 0.76 |
July | 0.409978E+09 | 0.423657E+10 | 0.00 | 12221071.42 | 0.360986E+09 | 0.00 | 0.225618E+10 | 0.00 | 0.66 |
August | 0.719946E+09 | 0.225952E+10 | 0.00 | 20111590.58 | 0.195386E+09 | 0.00 | 0.442768E+10 | 0.00 | 0.72 |
September | 0.238821E+10 | 0.681791E+09 | 0.00 | 14965583.25 | 34468471.26 | 0.00 | 0.618793E+10 | 0.00 | 0.64 |
October | 0.719169E+10 | 0.00 | 0.00 | 4612640.26 | 0.00 | 0.106188E+09 | 0.331196E+10 | 0.00 | 0.35 |
November | 0.100298E+11 | 0.00 | 450990.63 | 101944.81 | 11113919.94 | 0.721498E+09 | 0.163342E+09 | 34912.34 | 0.29 |
December | 0.796023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655371E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.684610E+11 | 0.836533E+10 | 450990.63 | 95246619.10 | 0.798080E+09 | 0.239878E+11 | 0.370732E+11 | 34912.34 | 0.46 |
Minimum of Months | 0.409978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.114196E+11 | 0.423657E+10 | 450990.63 | 20680257.71 | 0.360986E+09 | 0.808154E+10 | 0.933866E+10 | 34912.34 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 44915672.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421281E+10 | 0.00 | 0.00 | 0.34 |
February | 85402095.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381990E+10 | 0.00 | 0.00 | 0.34 |
March | 0.101877E+10 | 27794.83 | 0.00 | 328979.81 | 0.00 | 0.207147E+10 | 0.102331E+09 | 0.00 | 0.35 |
April | 0.173554E+10 | 0.00 | 0.00 | 361796.49 | 0.00 | 0.449951E+09 | 0.265394E+09 | 0.00 | 0.34 |
May | 0.104784E+10 | 0.00 | 0.00 | 3292750.27 | 3724178.93 | 10592151.99 | 0.164963E+10 | 0.00 | 0.59 |
June | 0.296058E+09 | 0.402222E+09 | 0.00 | 5273551.54 | 32237791.54 | 0.00 | 0.170864E+10 | 0.00 | 0.96 |
July | 99288935.36 | 0.135343E+10 | 0.00 | 3334722.96 | 66334875.56 | 0.00 | 0.578392E+09 | 0.00 | 0.87 |
August | 0.252583E+09 | 0.682158E+09 | 0.00 | 4953228.09 | 33233662.49 | 0.00 | 0.962676E+09 | 0.00 | 0.89 |
September | 0.754366E+09 | 0.177721E+09 | 0.00 | 2718585.59 | 10126313.45 | 5985139.08 | 0.101666E+10 | 0.00 | 0.68 |
October | 0.162543E+10 | 0.00 | 0.00 | 388353.27 | 0.00 | 0.324080E+09 | 0.252432E+09 | 0.00 | 0.35 |
November | 0.849988E+09 | 0.00 | 692299.86 | 0.00 | 1789681.57 | 0.150652E+10 | 0.00 | 13680.70 | 0.30 |
December | 0.129571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371423E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.793976E+10 | 0.261556E+10 | 692299.86 | 20651968.02 | 0.147447E+09 | 0.161156E+11 | 0.653616E+10 | 13680.70 | 0.53 |
Minimum of Months | 44915672.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.173554E+10 | 0.135343E+10 | 692299.86 | 5273551.54 | 66334875.56 | 0.421281E+10 | 0.170864E+10 | 13680.70 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 38846293.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252932E+10 | 0.00 | 0.00 | 0.32 |
February | 0.317471E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203987E+10 | 0.00 | 0.00 | 0.32 |
March | 0.989226E+09 | 34978.61 | 0.00 | 524337.87 | 0.00 | 0.806672E+09 | 0.185581E+09 | 0.00 | 0.36 |
April | 0.892847E+09 | 0.00 | 0.00 | 1994104.84 | 0.00 | 0.137014E+09 | 0.110265E+10 | 0.00 | 0.48 |
May | 0.446315E+09 | 20749.04 | 0.00 | 5228720.79 | 2336431.09 | 1212326.33 | 0.258152E+10 | 0.00 | 1.02 |
June | 0.126285E+09 | 0.372650E+09 | 0.00 | 6307555.41 | 9489744.79 | 0.00 | 0.227787E+10 | 0.00 | 1.52 |
July | 38749204.87 | 0.115752E+10 | 0.00 | 5259668.45 | 34829361.36 | 0.00 | 0.897655E+09 | 0.00 | 1.43 |
August | 0.106820E+09 | 0.547604E+09 | 0.00 | 5900885.55 | 15609040.69 | 0.00 | 0.121680E+10 | 0.00 | 1.39 |
September | 0.353551E+09 | 0.154499E+09 | 0.00 | 4120667.88 | 4313231.53 | 1766019.14 | 0.158677E+10 | 0.00 | 1.10 |
October | 0.911903E+09 | 0.00 | 0.00 | 962402.25 | 0.00 | 0.132676E+09 | 0.513159E+09 | 0.00 | 0.41 |
November | 0.640885E+09 | 0.00 | 412308.09 | 8630.66 | 1164288.96 | 0.836555E+09 | 10936574.49 | 7548.62 | 0.30 |
December | 92877660.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228933E+10 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.495578E+10 | 0.223233E+10 | 412308.09 | 30306973.70 | 67742098.43 | 0.877441E+10 | 0.103729E+11 | 7548.62 | 0.75 |
Minimum of Months | 38749204.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.989226E+09 | 0.115752E+10 | 412308.09 | 6307555.41 | 34829361.36 | 0.252932E+10 | 0.258152E+10 | 7548.62 | 1.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.708063E+09 | 0.00 | 0.00 | 255619.77 | 0.00 | 0.300385E+10 | 0.206885E+09 | 0.00 | 0.31 |
February | 0.785170E+09 | 0.00 | 0.00 | 503316.38 | 0.00 | 0.259841E+10 | 0.389864E+09 | 0.00 | 0.33 |
March | 0.137233E+10 | 146586.77 | 0.00 | 2612068.31 | 0.00 | 0.102217E+10 | 0.139013E+10 | 0.00 | 0.45 |
April | 0.132939E+10 | 0.00 | 0.00 | 3681422.84 | 0.00 | 0.321990E+09 | 0.207386E+10 | 0.00 | 0.54 |
May | 0.870919E+09 | 3336475.23 | 0.00 | 6678606.82 | 1771761.26 | 13231319.60 | 0.320807E+10 | 0.00 | 0.90 |
June | 0.327561E+09 | 0.465318E+09 | 0.00 | 6914849.98 | 24025626.10 | 0.00 | 0.227283E+10 | 0.00 | 1.19 |
July | 0.118290E+09 | 0.163149E+10 | 0.00 | 4675292.13 | 59971204.66 | 0.00 | 0.723050E+09 | 0.00 | 1.06 |
August | 0.232602E+09 | 0.856647E+09 | 0.00 | 7840663.86 | 23800541.94 | 0.00 | 0.144273E+10 | 0.00 | 1.22 |
September | 0.508528E+09 | 0.269170E+09 | 0.00 | 8462693.08 | 9614661.16 | 4428024.29 | 0.293144E+10 | 0.00 | 1.28 |
October | 0.123926E+10 | 0.00 | 0.00 | 4419984.35 | 0.00 | 0.167409E+09 | 0.221108E+10 | 0.00 | 0.65 |
November | 0.107218E+10 | 0.00 | 527630.99 | 1231434.45 | 1974233.34 | 0.982006E+09 | 0.644204E+09 | 9390.73 | 0.35 |
December | 0.555407E+09 | 0.00 | 0.00 | 141243.12 | 0.00 | 0.288976E+10 | 0.125908E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.911970E+10 | 0.322610E+10 | 527630.99 | 47417195.08 | 0.121158E+09 | 0.110033E+11 | 0.176200E+11 | 9390.73 | 0.72 |
Minimum of Months | 0.118290E+09 | 0.00 | 0.00 | 141243.12 | 0.00 | 0.00 | 0.125908E+09 | 0.00 | 0.31 |
Maximum of Months | 0.137233E+10 | 0.163149E+10 | 527630.99 | 8462693.08 | 59971204.66 | 0.300385E+10 | 0.320807E+10 | 9390.73 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258419E+10 | 0.00 | 0.00 | 0.34 |
February | 0.219857E+09 | 0.00 | 0.00 | 16398.69 | 0.00 | 0.224661E+10 | 18354047.92 | 0.00 | 0.34 |
March | 0.809529E+09 | 21871.33 | 0.00 | 574575.12 | 0.00 | 0.999156E+09 | 0.317315E+09 | 0.00 | 0.37 |
April | 0.892662E+09 | 0.00 | 0.00 | 1834946.73 | 0.00 | 0.246315E+09 | 0.109754E+10 | 0.00 | 0.51 |
May | 0.524211E+09 | 1447339.78 | 0.00 | 5225036.64 | 1575271.40 | 6871986.47 | 0.241381E+10 | 0.00 | 1.03 |
June | 0.175605E+09 | 0.368884E+09 | 0.00 | 6581317.38 | 13287242.28 | 0.00 | 0.191335E+10 | 0.00 | 1.54 |
July | 70327344.27 | 0.118815E+10 | 0.00 | 3474877.26 | 23018430.89 | 0.00 | 0.497093E+09 | 0.00 | 1.22 |
August | 0.147395E+09 | 0.588810E+09 | 0.00 | 5129412.16 | 9333418.55 | 0.00 | 0.863824E+09 | 0.00 | 1.25 |
September | 0.385869E+09 | 0.142446E+09 | 0.00 | 3928106.75 | 4532585.15 | 3330172.99 | 0.130287E+10 | 0.00 | 1.03 |
October | 0.929316E+09 | 0.00 | 0.00 | 1002533.47 | 0.00 | 0.172393E+09 | 0.542774E+09 | 0.00 | 0.44 |
November | 0.615181E+09 | 0.00 | 412824.52 | 48690.84 | 1167934.11 | 0.861144E+09 | 35774066.76 | 7898.67 | 0.31 |
December | 0.137999E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231255E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.503798E+10 | 0.228975E+10 | 412824.52 | 27815895.03 | 52914882.37 | 0.943256E+10 | 0.900271E+10 | 7898.67 | 0.73 |
Minimum of Months | 70327344.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.929316E+09 | 0.118815E+10 | 412824.52 | 6581317.38 | 23018430.89 | 0.258419E+10 | 0.241381E+10 | 7898.67 | 1.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 74365890.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412372E+10 | 0.00 | 0.00 | 0.31 |
February | 88362271.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381976E+10 | 0.00 | 0.00 | 0.32 |
March | 0.108707E+10 | 0.00 | 0.00 | 37611.80 | 896756.60 | 0.210510E+10 | 13314946.80 | 0.00 | 0.32 |
April | 0.182742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402281E+09 | 0.00 | 0.00 | 0.29 |
May | 0.149463E+10 | 0.00 | 0.00 | 1037696.70 | 1349484.76 | 1131166.78 | 0.534917E+09 | 0.00 | 0.42 |
June | 0.314245E+09 | 0.279093E+09 | 0.00 | 3587257.10 | 44799163.73 | 0.00 | 0.114773E+10 | 0.00 | 0.69 |
July | 88157946.01 | 0.103146E+10 | 0.00 | 2504956.66 | 93007239.86 | 0.00 | 0.448433E+09 | 0.00 | 0.65 |
August | 0.216433E+09 | 0.580279E+09 | 0.00 | 4362951.74 | 33538998.21 | 0.00 | 0.874709E+09 | 0.00 | 0.74 |
September | 0.687916E+09 | 0.169225E+09 | 0.00 | 2827898.06 | 4702558.91 | 0.00 | 0.107335E+10 | 0.00 | 0.64 |
October | 0.177135E+10 | 0.00 | 0.00 | 547192.21 | 84488.83 | 35093430.68 | 0.328271E+09 | 0.00 | 0.32 |
November | 0.181327E+10 | 0.00 | 11615.18 | 0.00 | 671169.96 | 0.577781E+09 | 0.00 | 3257.04 | 0.28 |
December | 0.341087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340354E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.980431E+10 | 0.206006E+10 | 11615.18 | 14905564.27 | 0.179050E+09 | 0.144684E+11 | 0.442072E+10 | 3257.04 | 0.44 |
Minimum of Months | 74365890.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.182742E+10 | 0.103146E+10 | 11615.18 | 4362951.74 | 93007239.86 | 0.412372E+10 | 0.114773E+10 | 3257.04 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 94633750.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252846E+10 | 0.00 | 0.00 | 0.31 |
February | 0.331611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209915E+10 | 0.00 | 0.00 | 0.31 |
March | 0.117519E+10 | 588841.31 | 0.00 | 141218.47 | 0.00 | 0.757590E+09 | 46382079.37 | 0.00 | 0.32 |
April | 0.100619E+10 | 0.00 | 0.00 | 1226812.36 | 0.00 | 89205735.14 | 0.542351E+09 | 0.00 | 0.35 |
May | 0.553728E+09 | 46581.99 | 0.00 | 3487100.20 | 816458.00 | 0.00 | 0.156245E+10 | 0.00 | 0.73 |
June | 0.116639E+09 | 0.290359E+09 | 0.00 | 5062362.33 | 19338771.42 | 0.00 | 0.177368E+10 | 0.00 | 1.21 |
July | 32939819.31 | 0.964200E+09 | 0.00 | 3997574.61 | 50482123.10 | 0.00 | 0.757243E+09 | 0.00 | 1.14 |
August | 99786443.08 | 0.502678E+09 | 0.00 | 5552927.02 | 18846219.66 | 0.00 | 0.114925E+10 | 0.00 | 1.23 |
September | 0.263094E+09 | 0.153080E+09 | 0.00 | 4529159.11 | 2724659.44 | 0.00 | 0.172181E+10 | 0.00 | 1.09 |
October | 0.855668E+09 | 0.00 | 0.00 | 1514376.33 | 53662.57 | 12982912.78 | 0.728074E+09 | 0.00 | 0.40 |
November | 0.118788E+10 | 0.00 | 8509.20 | 78994.51 | 426289.57 | 0.288831E+09 | 49949908.94 | 523.94 | 0.28 |
December | 0.238119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212548E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.595548E+10 | 0.191095E+10 | 8509.20 | 25590524.94 | 92688183.76 | 0.790170E+10 | 0.833119E+10 | 523.94 | 0.64 |
Minimum of Months | 32939819.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.118788E+10 | 0.964200E+09 | 8509.20 | 5552927.02 | 50482123.10 | 0.252846E+10 | 0.177368E+10 | 523.94 | 1.23 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.285417E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573264E+10 | 0.00 | 0.00 | 0.44 |
February | 0.292752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517466E+10 | 0.00 | 0.00 | 0.44 |
March | 0.137097E+10 | 2599459.89 | 0.00 | 269152.68 | 0.00 | 0.267535E+10 | 43665665.45 | 0.00 | 0.40 |
April | 0.144169E+10 | 0.00 | 0.00 | 653445.92 | 0.00 | 0.110664E+10 | 0.295411E+09 | 0.00 | 0.37 |
May | 0.133600E+10 | 81492.15 | 0.00 | 1887954.90 | 1287531.70 | 0.322264E+09 | 0.773709E+09 | 0.00 | 0.53 |
June | 0.545752E+09 | 0.341288E+09 | 0.00 | 3290137.29 | 47795424.70 | 76209736.42 | 0.919042E+09 | 0.00 | 0.76 |
July | 0.146286E+09 | 0.132418E+10 | 0.00 | 2777376.02 | 87580454.45 | 6448384.46 | 0.413796E+09 | 0.00 | 0.76 |
August | 0.326202E+09 | 0.802782E+09 | 0.00 | 5987907.76 | 29013268.26 | 19047688.36 | 0.930226E+09 | 0.00 | 0.98 |
September | 0.524513E+09 | 0.255845E+09 | 0.00 | 6696837.68 | 6447472.42 | 0.100659E+09 | 0.216091E+10 | 0.00 | 1.09 |
October | 0.132953E+10 | 21781.80 | 0.00 | 2506530.09 | 75780.63 | 0.518160E+09 | 0.118282E+10 | 0.00 | 0.52 |
November | 0.119986E+10 | 0.00 | 37571.19 | 327220.05 | 646890.21 | 0.172277E+10 | 0.217542E+09 | 2030.47 | 0.36 |
December | 0.246867E+09 | 0.00 | 0.00 | 25406.82 | 0.00 | 0.496722E+10 | 25877623.94 | 0.00 | 0.41 |
Annual Sum or Average | 0.904584E+10 | 0.272680E+10 | 37571.19 | 24421969.22 | 0.172847E+09 | 0.224221E+11 | 0.696300E+10 | 2030.47 | 0.59 |
Minimum of Months | 0.146286E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6448384.46 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.144169E+10 | 0.132418E+10 | 37571.19 | 6696837.68 | 87580454.45 | 0.573264E+10 | 0.216091E+10 | 2030.47 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.163863E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254064E+10 | 0.00 | 0.00 | 0.32 |
February | 0.248607E+09 | 0.00 | 0.00 | 202.25 | 0.00 | 0.225164E+10 | 2107517.72 | 0.00 | 0.32 |
March | 0.107160E+10 | 91251.73 | 0.00 | 129118.39 | 477476.38 | 0.864376E+09 | 65144631.92 | 0.00 | 0.32 |
April | 0.105854E+10 | 0.00 | 0.00 | 855086.39 | 0.00 | 0.142311E+09 | 0.405023E+09 | 0.00 | 0.35 |
May | 0.625863E+09 | 149825.77 | 0.00 | 3086802.71 | 815251.79 | 257831.89 | 0.131689E+10 | 0.00 | 0.70 |
June | 0.137397E+09 | 0.307876E+09 | 0.00 | 4850028.31 | 16251292.49 | 0.00 | 0.149646E+10 | 0.00 | 1.22 |
July | 47234640.24 | 0.991964E+09 | 0.00 | 2819322.75 | 31887787.36 | 0.00 | 0.436219E+09 | 0.00 | 0.97 |
August | 0.101097E+09 | 0.557075E+09 | 0.00 | 4708425.61 | 10393485.90 | 0.00 | 0.844762E+09 | 0.00 | 1.11 |
September | 0.294422E+09 | 0.138261E+09 | 0.00 | 4092686.99 | 1651922.80 | 0.00 | 0.138578E+10 | 0.00 | 1.00 |
October | 0.931673E+09 | 0.00 | 0.00 | 1242068.35 | 53583.29 | 17039066.51 | 0.607962E+09 | 0.00 | 0.41 |
November | 0.117169E+10 | 0.00 | 8587.26 | 49178.06 | 425659.78 | 0.317597E+09 | 34940694.24 | 432.54 | 0.28 |
December | 0.281475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210529E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.613347E+10 | 0.199542E+10 | 8587.26 | 21832919.81 | 61956459.80 | 0.823915E+10 | 0.659529E+10 | 432.54 | 0.61 |
Minimum of Months | 47234640.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.117169E+10 | 0.991964E+09 | 8587.26 | 4850028.31 | 31887787.36 | 0.254064E+10 | 0.149646E+10 | 432.54 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.123705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389347E+10 | 0.00 | 0.00 | 0.31 |
February | 0.340020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340736E+10 | 0.00 | 0.00 | 0.31 |
March | 0.156737E+10 | 802607.74 | 0.00 | 346554.51 | 490475.32 | 0.151171E+10 | 0.123353E+09 | 0.00 | 0.33 |
April | 0.196633E+10 | 0.00 | 0.00 | 447180.41 | 0.00 | 0.200522E+09 | 0.331631E+09 | 0.00 | 0.34 |
May | 0.945013E+09 | 71505.42 | 0.00 | 3777569.29 | 4168913.73 | 0.00 | 0.177429E+10 | 0.00 | 0.60 |
June | 0.224623E+09 | 0.414162E+09 | 0.00 | 5361162.67 | 36310033.27 | 0.00 | 0.174084E+10 | 0.00 | 0.92 |
July | 83830421.02 | 0.134680E+10 | 0.00 | 3287325.48 | 77450190.69 | 0.00 | 0.584743E+09 | 0.00 | 0.82 |
August | 0.208232E+09 | 0.679030E+09 | 0.00 | 5127142.95 | 31033111.45 | 0.00 | 0.102979E+10 | 0.00 | 0.85 |
September | 0.664506E+09 | 0.190798E+09 | 0.00 | 3253636.10 | 5587364.88 | 0.00 | 0.122194E+10 | 0.00 | 0.70 |
October | 0.184092E+10 | 0.00 | 0.00 | 678600.93 | 421518.09 | 0.101867E+09 | 0.395512E+09 | 0.00 | 0.36 |
November | 0.169273E+10 | 0.00 | 51624.06 | 0.00 | 1470979.45 | 0.806178E+09 | 0.00 | 4690.14 | 0.30 |
December | 0.318135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337343E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.997541E+10 | 0.263166E+10 | 51624.06 | 22279172.34 | 0.156933E+09 | 0.132945E+11 | 0.720210E+10 | 4690.14 | 0.51 |
Minimum of Months | 83830421.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.196633E+10 | 0.134680E+10 | 51624.06 | 5361162.67 | 77450190.69 | 0.389347E+10 | 0.177429E+10 | 4690.14 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.172700E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204725E+10 | 0.00 | 0.00 | 0.27 |
February | 0.370382E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165738E+10 | 0.00 | 0.00 | 0.27 |
March | 0.965110E+09 | 1416817.65 | 0.00 | 538430.27 | 2237.18 | 0.552027E+09 | 0.222049E+09 | 0.00 | 0.30 |
April | 0.825258E+09 | 0.00 | 0.00 | 2207375.33 | 0.00 | 61537756.60 | 0.117627E+10 | 0.00 | 0.46 |
May | 0.394571E+09 | 73443.69 | 0.00 | 5325653.02 | 2613891.57 | 0.00 | 0.248303E+10 | 0.00 | 0.98 |
June | 0.101531E+09 | 0.364381E+09 | 0.00 | 6046557.05 | 10222635.55 | 0.00 | 0.214330E+10 | 0.00 | 1.39 |
July | 31131192.62 | 0.107654E+10 | 0.00 | 4855469.43 | 41069603.67 | 0.00 | 0.870007E+09 | 0.00 | 1.27 |
August | 0.102146E+09 | 0.508237E+09 | 0.00 | 5789497.41 | 17232899.01 | 0.00 | 0.120438E+10 | 0.00 | 1.27 |
September | 0.288430E+09 | 0.150883E+09 | 0.00 | 4400815.70 | 3138506.72 | 0.00 | 0.165351E+10 | 0.00 | 1.06 |
October | 0.827852E+09 | 0.00 | 0.00 | 1325816.93 | 267085.16 | 38937439.05 | 0.650420E+09 | 0.00 | 0.39 |
November | 0.862643E+09 | 0.00 | 28761.34 | 67975.21 | 932052.00 | 0.418996E+09 | 44964629.97 | 2603.90 | 0.25 |
December | 0.183318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186873E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.512507E+10 | 0.210153E+10 | 28761.34 | 30557590.34 | 75478910.84 | 0.664486E+10 | 0.104479E+11 | 2603.90 | 0.68 |
Minimum of Months | 31131192.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.965110E+09 | 0.107654E+10 | 28761.34 | 6046557.05 | 41069603.67 | 0.204725E+10 | 0.248303E+10 | 2603.90 | 1.39 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100474E+10 | 0.00 | 0.00 | 433675.70 | 0.00 | 0.267548E+10 | 0.329039E+09 | 0.00 | 0.31 |
February | 0.113926E+10 | 0.00 | 0.00 | 675300.38 | 0.00 | 0.223056E+10 | 0.482104E+09 | 0.00 | 0.33 |
March | 0.176001E+10 | 6628807.15 | 0.00 | 3013660.81 | 0.00 | 0.620408E+09 | 0.167186E+10 | 0.00 | 0.44 |
April | 0.150583E+10 | 0.00 | 0.00 | 4083806.67 | 0.00 | 0.144329E+09 | 0.210280E+10 | 0.00 | 0.56 |
May | 0.803471E+09 | 4164528.42 | 0.00 | 7055845.88 | 1464580.02 | 446279.00 | 0.315778E+10 | 0.00 | 0.91 |
June | 0.275789E+09 | 0.478064E+09 | 0.00 | 6807673.24 | 28510144.26 | 0.00 | 0.216139E+10 | 0.00 | 1.13 |
July | 0.101133E+09 | 0.161883E+10 | 0.00 | 4076060.62 | 64690393.71 | 0.00 | 0.661263E+09 | 0.00 | 0.96 |
August | 0.208673E+09 | 0.858845E+09 | 0.00 | 7712730.52 | 23447304.19 | 0.00 | 0.139915E+10 | 0.00 | 1.15 |
September | 0.481002E+09 | 0.288238E+09 | 0.00 | 8813745.49 | 4998757.77 | 0.00 | 0.295105E+10 | 0.00 | 1.29 |
October | 0.123437E+10 | 420208.41 | 0.00 | 5573409.57 | 90167.59 | 49644516.95 | 0.262132E+10 | 0.00 | 0.70 |
November | 0.160770E+10 | 0.00 | 36189.23 | 1709774.17 | 1478118.62 | 0.542733E+09 | 0.872363E+09 | 1655.47 | 0.37 |
December | 0.956302E+09 | 0.00 | 0.00 | 214106.34 | 0.00 | 0.249777E+10 | 0.177760E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.110783E+11 | 0.325519E+10 | 36189.23 | 50169789.39 | 0.124679E+09 | 0.876137E+10 | 0.185879E+11 | 1655.47 | 0.71 |
Minimum of Months | 0.101133E+09 | 0.00 | 0.00 | 214106.34 | 0.00 | 0.00 | 0.177760E+09 | 0.00 | 0.30 |
Maximum of Months | 0.176001E+10 | 0.161883E+10 | 36189.23 | 8813745.49 | 64690393.71 | 0.267548E+10 | 0.315778E+10 | 1655.47 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.237357E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233820E+10 | 0.00 | 0.00 | 0.31 |
February | 0.421614E+09 | 0.00 | 0.00 | 20417.14 | 0.00 | 0.196185E+10 | 19834057.31 | 0.00 | 0.32 |
March | 0.110061E+10 | 772952.09 | 0.00 | 658990.60 | 255501.87 | 0.675556E+09 | 0.383346E+09 | 0.00 | 0.36 |
April | 0.102434E+10 | 0.00 | 0.00 | 1961905.14 | 0.00 | 0.109825E+09 | 0.108666E+10 | 0.00 | 0.51 |
May | 0.462482E+09 | 736103.95 | 0.00 | 5465104.41 | 1960566.00 | 0.00 | 0.236628E+10 | 0.00 | 1.03 |
June | 0.147755E+09 | 0.391839E+09 | 0.00 | 6045529.64 | 12720459.90 | 0.00 | 0.180384E+10 | 0.00 | 1.46 |
July | 57154543.86 | 0.119878E+10 | 0.00 | 3212571.03 | 22671173.02 | 0.00 | 0.460727E+09 | 0.00 | 1.11 |
August | 0.121384E+09 | 0.579988E+09 | 0.00 | 4983765.10 | 9758187.03 | 0.00 | 0.859988E+09 | 0.00 | 1.17 |
September | 0.339895E+09 | 0.154623E+09 | 0.00 | 4228425.16 | 1783473.53 | 0.00 | 0.136779E+10 | 0.00 | 1.04 |
October | 0.100696E+10 | 0.00 | 0.00 | 1349980.04 | 266326.06 | 53265834.62 | 0.679476E+09 | 0.00 | 0.46 |
November | 0.106669E+10 | 0.00 | 28643.86 | 89925.59 | 929402.95 | 0.458910E+09 | 75006360.12 | 2593.06 | 0.30 |
December | 0.284060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207232E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.627030E+10 | 0.232674E+10 | 28643.86 | 28016613.85 | 50345090.38 | 0.766993E+10 | 0.910294E+10 | 2593.06 | 0.70 |
Minimum of Months | 57154543.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.110061E+10 | 0.119878E+10 | 28643.86 | 6045529.64 | 22671173.02 | 0.233820E+10 | 0.236628E+10 | 2593.06 | 1.46 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:03
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.136425E+12 | 0.307596E+11 | 0.00 | 0.134656E+12 | 0.141788E+11 |
February | 0.210384E+12 | 0.315291E+11 | 0.00 | 0.125711E+12 | 0.131273E+11 |
March | 0.311044E+12 | 0.217198E+11 | 0.00 | 0.161687E+12 | 0.147758E+11 |
April | 0.368051E+12 | 0.172444E+11 | 0.00 | 0.193680E+12 | 0.681195E+10 |
May | 0.448012E+12 | 0.103141E+11 | 0.00 | 0.215589E+12 | 0.289823E+11 |
June | 0.481421E+12 | 0.397606E+10 | 0.00 | 0.122667E+12 | 0.131832E+12 |
July | 0.447428E+12 | -943092575.5 | 0.00 | 0.131663E+11 | 0.229366E+12 |
August | 0.383482E+12 | 0.147027E+10 | 0.00 | 0.855485E+11 | 0.189321E+12 |
September | 0.295600E+12 | 0.579483E+10 | 0.00 | 0.173057E+12 | 0.806799E+11 |
October | 0.203095E+12 | 0.140870E+11 | 0.00 | 0.200688E+12 | 0.119052E+11 |
November | 0.107493E+12 | 0.184783E+11 | 0.00 | 0.157408E+12 | 0.615716E+10 |
December | 0.122136E+12 | 0.317207E+11 | 0.00 | 0.137418E+12 | 0.124077E+11 |
Annual Sum or Average | 0.351457E+13 | 0.186151E+12 | 0.00 | 0.172128E+13 | 0.739546E+12 |
Minimum of Months | 0.107493E+12 | -943092575.5 | 0.00 | 0.131663E+11 | 0.615716E+10 |
Maximum of Months | 0.481421E+12 | 0.317207E+11 | 0.00 | 0.215589E+12 | 0.229366E+12 |