Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2023-10-16 08:32:05
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1479.40 | 296.94 | 296.94 |
Net Site Energy | 1479.40 | 296.94 | 296.94 |
Total Source Energy | 4114.87 | 825.92 | 825.92 |
Net Source Energy | 4114.87 | 825.92 | 825.92 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 94.90 | 138.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 40.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 234.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 51.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 67.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 134.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1205.57 | 273.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 94.90 | 138.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 40.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 234.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 51.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 67.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 134.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 94.90 | 138.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 40.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 234.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 51.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 67.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 134.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 57.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 40.67 | 54.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 241.98 | 54.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 57.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 40.67 | 54.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 241.98 | 54.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1205.571 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1205.571 | 100.00 |
Total On-Site and Utility Electric Sources | 1205.571 | 100.00 |
Total Electricity End Uses | 1205.571 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 285.67 |
Time Setpoint Not Met During Occupied Cooling | 85.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1926.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.6636 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.6636 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.6636 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 6.6636 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.6636 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 10-JAN-08:09 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 158833.83 | 60648.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8334.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 243.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5799.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 9381.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 200003.49 | 70029.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 158833.83 | 60648.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 8334.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 243.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 5799.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 9381.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 300.54 | 150.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 127.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 741.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 163.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 37.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 213.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 146.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3818.04 | 296.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 60.32 | 30.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 25.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 148.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 42.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 29.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 766.34 | 59.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 60.32 | 30.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 25.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 148.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 42.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 29.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 766.34 | 59.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.80 | 0.267296 | 0.227000 | 0.636471 | 0.712790 | 0.500000 | 0.001425 |
CORE_MID VAV BOX COMPONENT | 2.02 | 0.371190 | 0.316000 | 0.638022 | 0.989841 | 0.500000 | 0.001026 |
CORE_TOP VAV BOX COMPONENT | 2.04 | 0.367793 | 0.313000 | 0.637802 | 0.980782 | 0.500000 | 0.001036 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.556119 | 0.284097 | 0.241000 | 0.134025 | 0.757591 | 0.500000 | 0.001341 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.757737 | 0.132001 | 0.112000 | 0.084867 | 0.352002 | 0.500000 | 0.002886 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.14 | 0.138618 | 0.118000 | 0.134492 | 0.369647 | 0.500000 | 0.002749 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.843783 | 0.118532 | 0.101000 | 0.085222 | 0.316085 | 0.500000 | 0.003214 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.440510 | 0.358656 | 0.305000 | 0.134356 | 0.956416 | 0.500000 | 0.001062 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.620002 | 0.161325 | 0.137000 | 0.084940 | 0.430200 | 0.500000 | 0.002362 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.928747 | 0.170113 | 0.145000 | 0.134668 | 0.453634 | 0.500000 | 0.002240 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.700353 | 0.142807 | 0.121000 | 0.084743 | 0.380818 | 0.500000 | 0.002668 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.495317 | 0.318971 | 0.271000 | 0.134231 | 0.850588 | 0.500000 | 0.001194 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.765135 | 0.348598 | 0.500000 | 0.002915 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.07 | 0.147878 | 0.126000 | 0.134617 | 0.394341 | 0.500000 | 0.002576 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.791811 | 0.126312 | 0.107000 | 0.084724 | 0.336832 | 0.500000 | 0.003016 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 21031.59 |
CORE_MID VAV BOX REHEAT COIL | 21082.86 |
CORE_TOP VAV BOX REHEAT COIL | 30355.41 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 13357.10 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 8759.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 13390.98 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 8729.07 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 10234.92 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6824.23 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 10280.27 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6794.46 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 10194.86 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 6756.19 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 10225.59 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 6726.20 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.75 | 1.08 | 5.49 | 1.46 | 4.79 | 4.79 | 0.300000 | 0.304612 | 4.79 |
PACU_VAV_MID | 2.57 | 1.08 | 5.14 | 1.53 | 4.22 | 4.22 | 0.300000 | 0.362089 | 4.22 |
PACU_VAV_TOP | 2.67 | 1.08 | 5.34 | 2.26 | 4.72 | 4.72 | 0.300000 | 0.477980 | 4.72 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.79 |
PACU_VAV_MID_OA_CONTROLLER | 4.22 |
PACU_VAV_TOP_OA_CONTROLLER | 4.72 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.79 | 79214.31 | 0.800655 | 1.59 | 26402.13 | 0.800655 |
PACU_VAV_MID COOLING COIL | 4.22 | 69910.59 | 0.800655 | 1.41 | 23301.20 | 0.800655 |
PACU_VAV_TOP COOLING COIL | 4.72 | 78176.75 | 0.800655 | 1.57 | 26056.31 | 0.800655 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 15559.49 |
PACU_VAV_MID HEATING COIL | 17192.29 |
PACU_VAV_TOP HEATING COIL | 16984.69 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.79 |
PACU_VAV_MID FAN | 4.22 |
PACU_VAV_TOP FAN | 4.72 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 31.498 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.8022 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7887 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.032 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2365 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2366 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.013 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.034 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7350 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.151 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.150 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.29755900E-12 | 0.81313074E-15 | -0.93602003E-13 | 0.14510957E-15 |
43 | 6 | 0.28367368E-07 | 0.22496401E-09 | 0.65009128E-08 | -0.13359594E-12 |
44 | 5 | -0.18856357E-03 | 0.19286971E-05 | -0.97009749E-04 | 0.64274374E-08 |
45 | 4 | 0.29034011 | 0.94012602E-03 | 0.99033658E-01 | -0.33316087E-04 |
46 | 3 | -7.2305496 | 0.29163423E-01 | -2.3282961 | 0.28833673E-01 |
47 | 2 | 40.753148 | 0.10379063 | 15.221555 | -0.33202618 |
48 | 1 | -80.455373 | 0.46876469E-01 | -29.102648 | 1.0766925 |
49 | 0 | 46.824339 | 0.94379271E-03 | 16.292168 | |
50 | 7 | -0.29905644E-12 | 0.21441847E-14 | -0.94350753E-13 | 0.15229914E-15 |
51 | 6 | 0.28527035E-07 | 0.22156944E-09 | 0.65361533E-08 | -0.13441220E-12 |
52 | 5 | -0.18937502E-03 | 0.18976302E-05 | -0.97416439E-04 | 0.64617957E-08 |
53 | 4 | 0.29129073 | 0.92413897E-03 | 0.99375489E-01 | -0.33450099E-04 |
54 | 3 | -7.2493786 | 0.28644335E-01 | -2.3338831 | 0.28925940E-01 |
55 | 2 | 40.815249 | 0.10187053 | 15.244478 | -0.33271782 |
56 | 1 | -80.502964 | 0.45980673E-01 | -29.123201 | 1.0777067 |
57 | 0 | 46.824339 | 0.92519179E-03 | 16.291675 | |
58 | 7 | -0.27570686E-12 | 0.13707328E-14 | -0.80264236E-13 | 0.78378346E-16 |
59 | 6 | 0.25615968E-07 | 0.28022365E-09 | 0.58936169E-08 | -0.11887149E-12 |
60 | 5 | -0.17446821E-03 | 0.24481169E-05 | -0.89927666E-04 | 0.58344893E-08 |
61 | 4 | 0.27366067 | 0.12133616E-02 | 0.93044102E-01 | -0.30982017E-04 |
62 | 3 | -6.8997845 | 0.38197916E-01 | -2.2301787 | 0.27213971E-01 |
63 | 2 | 39.661773 | 0.13771433 | 14.818013 | -0.31987377 |
64 | 1 | -79.618511 | 0.62899977E-01 | -28.740542 | 1.0588596 |
65 | 0 | 46.824345 | 0.12804488E-02 | 16.301062 | |
66 | 7 | -0.18778705E-08 | -0.48456698E-15 | 0.68415356E-14 | -0.90766841E-16 |
67 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
68 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
69 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
70 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
71 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
72 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
73 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
74 | 7 | -0.17777358E-08 | -0.41207670E-15 | 0.60771148E-14 | -0.79247013E-16 |
75 | 6 | 0.66205355E-05 | 0.45347915E-08 | 0.31869553E-02 | -0.26734852E-04 |
76 | 5 | -0.47643654E-03 | 0.26865296E-05 | -0.22355891 | 0.19546881E-02 |
77 | 4 | 0.10961386E-01 | 0.12229770E-03 | 4.8267865 | -0.45238458E-01 |
78 | 3 | -0.96263561E-01 | 0.97262436E-03 | -38.005829 | 0.39848146 |
79 | 2 | 0.34182167 | 0.16181264E-02 | 116.45361 | -1.4175335 |
80 | 1 | -0.49337445 | 0.49308431E-03 | -143.88945 | 2.0487464 |
81 | 0 | 0.24054552 | 0.11921404E-04 | 60.838472 | |
82 | 7 | -0.18778705E-08 | -0.48456747E-15 | 0.68415356E-14 | -0.90766840E-16 |
83 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
84 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
85 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
86 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
87 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
88 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
89 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
90 | 7 | -0.17776120E-08 | -0.41258204E-15 | 0.60425363E-14 | -0.82023253E-16 |
91 | 6 | 0.66209765E-05 | 0.45351028E-08 | 0.31869540E-02 | -0.26734841E-04 |
92 | 5 | -0.47646911E-03 | 0.26867147E-05 | -0.22355884 | 0.19546874E-02 |
93 | 4 | 0.10962140E-01 | 0.12230614E-03 | 4.8267853 | -0.45238446E-01 |
94 | 3 | -0.96270204E-01 | 0.97269154E-03 | -38.005822 | 0.39848139 |
95 | 2 | 0.34184528 | 0.16182383E-02 | 116.45360 | -1.4175333 |
96 | 1 | -0.49340854 | 0.49311848E-03 | -143.88944 | 2.0487463 |
97 | 0 | 0.24056214 | 0.11922214E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.378 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.378 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2903E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2970E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4504E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4563E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1204E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.1671E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3510E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3752E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1722 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1000 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1979 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1160 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1138 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9832E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8073E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8035E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2904E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2984E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4506E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4578E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1222E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.1761E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3507E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3749E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.0769E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7175E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.7964E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4765E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.5791E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8330E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6444E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6601E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.1587E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.1867E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9069E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.9273E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.3058E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.3129E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0780E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0864E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8453E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.9054E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0429E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.0919E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4793E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.5156E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3507E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3749E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7231E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7064E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6489E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0695E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3251E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3975E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8073E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8035E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8450E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.9062E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0421E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.0905E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4776E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.5092E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3510E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3752E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.8155E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.0821E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.1807E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.6586E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.6555E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3901E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6444E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6601E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.3607E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.4480E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8806E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.9797E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7440E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7750E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0782E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0865E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1729 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1198 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1955 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1382 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1225 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.2977E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.4807E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.5582E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.8041E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.5611E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.5440E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.3315E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.3966E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.7245E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.5395E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5971E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.3588E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.5048E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.2128E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7545E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.8880E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0197E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.4807E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.5582E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.5855E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.9546E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.9836E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.5511E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.5012E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3005E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.5395E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.5971E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1729 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1198 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1955 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1382 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1225 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.2969E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.4802E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.5579E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.8041E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.5608E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.5439E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.3312E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.3961E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.7241E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.5390E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5968E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.3590E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.5046E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.2129E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7544E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.8877E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0195E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.4802E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.5579E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.5855E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.9544E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.9835E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.5509E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.5009E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3001E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.5390E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.5968E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 38503.22943 | 38503.22943 | 2.80384 | 2.80384 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 5751.39348 | 5751.39348 | 0.24453 | 0.42469 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 27762.93877 | 27762.93877 | 2.01906 | 2.01906 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 11796.82617 | 11796.82617 | 0.50322 | 0.50322 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 27747.93214 | 27747.93214 | 2.03771 | 2.03771 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 26.21800 | 8.40679E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 21408.61251 | 21408.61251 | 0.91863 | 0.91863 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 7572.92675 | 7572.92675 | 0.55612 | 0.55612 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 26.30900 | 8.40693E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 9387.12072 | 9387.12072 | 0.40422 | 0.40422 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10318.54051 | 10318.54051 | 0.75774 | 0.75774 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 21.65283 | 8.39969E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 6154.94853 | 6154.94853 | 0.26507 | 0.26507 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 15520.84168 | 15520.84168 | 1.13977 | 1.13977 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 26.24833 | 8.40684E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 9410.84305 | 9410.84305 | 0.40525 | 0.40525 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11490.29822 | 11490.29822 | 0.84378 | 0.84378 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.97433 | 8.40484E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 6133.98958 | 6133.98958 | 0.26416 | 0.26416 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 5998.59798 | 5998.59798 | 0.44051 | 0.44051 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.40000 | 8.40708E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 7199.33247 | 7199.33247 | 0.30974 | 0.30974 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8442.90157 | 8442.90157 | 0.62000 | 0.62000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 21.91067 | 8.40008E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 4799.28505 | 4799.28505 | 0.20652 | 0.20652 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 12647.22439 | 12647.22439 | 0.92875 | 0.92875 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 26.32417 | 8.40696E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 7231.12502 | 7231.12502 | 0.31111 | 0.31111 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9537.07958 | 9537.07958 | 0.70035 | 0.70035 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.21600 | 8.40365E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 4778.43833 | 4778.43833 | 0.20562 | 0.20562 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 6744.94674 | 6744.94674 | 0.49532 | 0.49532 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.40000 | 8.40708E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 7172.04924 | 7172.04924 | 0.30852 | 0.30852 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10419.27404 | 10419.27404 | 0.76513 | 0.76513 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 21.10683 | 8.39884E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 4752.03228 | 4752.03228 | 0.20446 | 0.20446 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 14548.87334 | 14548.87334 | 1.06839 | 1.06839 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17250 | 8.40672E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 7193.56888 | 7193.56888 | 0.30945 | 0.30945 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10782.54865 | 10782.54865 | 0.79181 | 0.79181 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.97433 | 8.40484E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 4731.03209 | 4731.03209 | 0.20355 | 0.20355 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 66892.07 | 4.78534 | 4.78534 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 19303.89 | 1.45767 | 1.45767 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 59354.40 | 4.22330 | 4.22330 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 19283.40 | 1.52921 | 1.52921 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 65980.08 | 4.72266 | 4.72266 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 19378.35 | 2.25734 | 2.25734 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.80384 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26730 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22700 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63647 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71279 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.42538E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21031.58837 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.01906 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37119 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31600 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63802 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.98984 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.02643E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21082.85657 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.03771 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36779 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31300 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63780 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.98078 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.03591E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 30355.41353 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.55612 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28410 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24100 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13402 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75759 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34109E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13357.10359 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75774 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13200 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11200 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48665E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35200 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.88635E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8758.99733 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.13977 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13862 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11800 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13449 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36965 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.74857E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13390.97893 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84378 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11853 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10100 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52221E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31608 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.21433E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8729.07145 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.44051 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35866 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30500 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13436 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.95642 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.06230E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10234.92356 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62000 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16132 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13700 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.49403E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43020 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.36169E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6824.23008 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.92875 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17011 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14500 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13467 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45363 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.23969E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10280.26880 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70035 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14281 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12100 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47427E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38082 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.66794E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6794.46495 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.49532 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31897 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27100 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13423 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85059 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19447E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10194.86011 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76513 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34860 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.91453E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6756.18742 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.06839 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14788 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12600 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13462 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39434 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.57645E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10225.58918 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79181 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12631 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10700 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47238E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33683 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.01634E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6726.20373 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.74672 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07518 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.49345 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.45767 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.78534 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.78534 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.30461 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.56986 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07652 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.13971 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.52921 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.22330 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.22330 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.36209 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.66756 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07641 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.33511 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.25734 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.72266 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.72266 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.47798 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.78534 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.22330 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.72266 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.78534 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.78534 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 79214.31297 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.59495 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 26402.13051 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
152 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 15559.49267 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.78534 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.22330 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.22330 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 69910.58576 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.40763 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 23301.19823 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
161 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 17192.28533 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.22330 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.72266 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.72266 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 78176.75192 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.57406 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 26056.31142 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
170 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 16984.68767 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.72266 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 77851.23 | 265639.43 | 10.80 | 2.80 | 3.09 | 3.25 | 3.42 | 9.54 | 10.54 | 11.09 | 11.68 | 5.4760 | 4.3311 | 2.9031 | 1.2092 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 68707.60 | 234440.06 | 11.65 | 3.03 | 3.33 | 3.51 | 3.70 | 10.34 | 11.38 | 11.96 | 12.64 | 4.8328 | 3.8224 | 2.5621 | 1.0672 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 76831.52 | 262160.04 | 10.80 | 2.80 | 3.09 | 3.25 | 3.42 | 9.54 | 10.54 | 11.09 | 11.68 | 5.4042 | 4.2744 | 2.8651 | 1.1934 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.237 | 0.224 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.237 | 0.224 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 6.0162106186E-003 | 6.5353787945E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.8206208111E-002 | 6.5144957850E-002 | Pass | Pass | 0.3170758607 | 0.4495914645 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.1838195887E-002 | 9.8295955846E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.6578639544E-003 | 8.0772337026E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 8.6483213268E-003 | 7.9772171241E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 2.9942233912E-002 | 2.3527882780E-002 | Pass | Pass | 2.2170959384 | 14.3455593595 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1672382875 | 0.1831667271 | Pass | Pass | 6.2432604926 | 22.0647096583 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1450781394 | 0.1510949492 | Pass | Pass | 6.8513507515 | 26.0716921753 | Pass | Fail |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1148289881 | 0.1099141943 | Pass | Pass | 18.4927889705 | 133.8030242118 | Pass | Fail |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1590902273 | 0.1568555118 | Pass | Pass | 6.9485209601 | 26.2265055338 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.5551797772E-002 | 1.2569018834E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.8217229384E-002 | 6.2496861567E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 5.8549123979E-002 | 8.0014189144E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.4150323233E-002 | 4.3765368059E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.8563902585E-002 | 1.4616399098E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.8885124573E-002 | 7.2054866915E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.7398913853E-002 | 9.9063030034E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.1078390808E-002 | 5.0526025164E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3101.04 | 104.63 | 0.00 | 2454.49 | 234.79 | 5894.96 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.378 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.378 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.378 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.378 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.378 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.378 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.378 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.378 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.378 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.378 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.062 | 0.379 | 0.417 | |||||||||||||||||
North Total or Average | 195.79 | 2.062 | 0.379 | 0.417 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.062 | 0.379 | 0.417 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.75 | 0.0000 | Y | 6.94 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.44 | 0.0000 | Y | 4.34 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.26 | 0.0000 | Y | 6.81 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.54 | 0.0000 | Y | 4.36 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.68 | 0.0000 | Y | 6.92 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.39 | 0.0000 | Y | 4.33 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.22 | 0.0000 | Y | 6.80 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.48 | 0.0000 | Y | 4.35 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.75 | 0.0000 | Y | 6.94 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.44 | 0.0000 | Y | 4.34 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.26 | 0.0000 | Y | 6.81 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.54 | 0.0000 | Y | 4.36 |
Interior Lighting Total | 6.6636 | 4982.19 | 33199.39 | 234.09 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 42.50 | 42.50 | 4.50 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.54 | 63.02 | 4.82 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.54 | 47.95 | 42.44 | |
Exterior Lighting Total | 5686.19 | 51.76 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 79214.31 | 63423.36 | 15790.96 | 0.80 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 69910.59 | 55974.28 | 13936.31 | 0.80 | 3.73 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 78176.75 | 62592.63 | 15584.12 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 77851.2 | 2.80 | 9.54 | N/A | N/A | 10.80 | |
PACU_VAV_MID COOLING COIL | 68707.6 | 3.03 | 10.34 | N/A | N/A | 11.65 | |
PACU_VAV_TOP COOLING COIL | 76831.5 | 2.80 | 9.54 | N/A | N/A | 10.80 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 21031.59 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 21082.86 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 30355.41 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13357.10 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8759.00 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13390.98 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8729.07 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10234.92 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6824.23 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10280.27 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6794.46 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10194.86 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6756.19 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10225.59 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6726.20 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 15559.49 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 17192.29 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 16984.69 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.79 | 10475.15 | 2189.01 | 1.00 | 1.14 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.22 | 9244.85 | 2189.01 | 1.00 | 1.14 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.72 | 10337.95 | 2189.01 | 1.00 | 1.14 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 77851.23 | 2.80 | 9.54 | 10.80 | 5.4760 | 3.09 | 10.54 | 4.3311 | 3.25 | 11.09 | 2.9031 | 3.42 | 11.68 | 1.2092 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 68707.60 | 3.03 | 10.34 | 11.65 | 4.8328 | 3.33 | 11.38 | 3.8224 | 3.51 | 11.96 | 2.5621 | 3.70 | 12.64 | 1.0672 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 76831.52 | 2.80 | 9.54 | 10.80 | 5.4042 | 3.09 | 10.54 | 4.2744 | 3.25 | 11.09 | 2.8651 | 3.42 | 11.68 | 1.1934 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 38503.23 | 38503.23 | 39.15 | 2.804 | 2.804 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00882 | 19.67 | 0.00840 | 0.425 | 0.00 |
CORE_MID | 27762.94 | 27762.94 | 28.23 | 2.019 | 2.019 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 19.67 | 0.00840 | 0.425 | 0.00 |
CORE_TOP | 27747.93 | 27747.93 | 28.21 | 2.038 | 2.038 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00893 | 26.22 | 0.00841 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 7572.93 | 7572.93 | 36.52 | 0.556 | 0.556 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00882 | 26.31 | 0.00841 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10318.54 | 10318.54 | 78.61 | 0.758 | 0.758 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 24.00 | 24.00 | 0.00865 | 21.65 | 0.00840 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15520.84 | 15520.84 | 74.86 | 1.140 | 1.140 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00866 | 26.25 | 0.00841 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11490.30 | 11490.30 | 87.54 | 0.844 | 0.844 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00864 | 24.97 | 0.00840 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 5998.60 | 5998.60 | 28.93 | 0.441 | 0.441 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00891 | 26.40 | 0.00841 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8442.90 | 8442.90 | 64.32 | 0.620 | 0.620 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 24.00 | 24.00 | 0.00869 | 21.91 | 0.00840 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12647.22 | 12647.22 | 61.00 | 0.929 | 0.929 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00870 | 26.32 | 0.00841 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9537.08 | 9537.08 | 72.66 | 0.700 | 0.700 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.00 | 24.00 | 0.00866 | 24.22 | 0.00840 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 6744.95 | 6744.95 | 32.53 | 0.495 | 0.495 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00886 | 26.40 | 0.00841 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10419.27 | 10419.27 | 79.38 | 0.765 | 0.765 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00865 | 21.11 | 0.00840 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 14548.87 | 14548.87 | 70.17 | 1.068 | 1.068 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00867 | 26.17 | 0.00841 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10782.55 | 10782.55 | 82.15 | 0.792 | 0.792 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00865 | 24.97 | 0.00840 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 5751.39 | 5751.39 | 5.85 | 0.245 | 0.425 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 0.425 | 0.00 |
CORE_MID | 11796.83 | 11796.83 | 11.99 | 0.503 | 0.503 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 0.425 | 0.00 |
CORE_TOP | 21408.61 | 21408.61 | 21.77 | 0.919 | 0.919 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9387.12 | 9387.12 | 45.27 | 0.404 | 0.404 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 6154.95 | 6154.95 | 46.89 | 0.265 | 0.265 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -4.30 | 0.00266 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 9410.84 | 9410.84 | 45.39 | 0.405 | 0.405 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 6133.99 | 6133.99 | 46.73 | 0.264 | 0.264 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -4.30 | 0.00266 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7199.33 | 7199.33 | 34.72 | 0.310 | 0.310 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00780 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 4799.29 | 4799.29 | 36.56 | 0.207 | 0.207 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -4.30 | 0.00266 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 7231.13 | 7231.13 | 34.88 | 0.311 | 0.311 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00780 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 4778.44 | 4778.44 | 36.41 | 0.206 | 0.206 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -4.30 | 0.00266 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7172.05 | 7172.05 | 34.59 | 0.309 | 0.309 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 4752.03 | 4752.03 | 36.20 | 0.204 | 0.204 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -4.30 | 0.00266 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 7193.57 | 7193.57 | 34.69 | 0.309 | 0.309 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 4731.03 | 4731.03 | 36.04 | 0.204 | 0.204 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -4.30 | 0.00266 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.79 | 4.79 | 1.46 | 1.46 | 4.7853 | 1.4577 | 4.7853 | 0.3046 | 0.3000 |
PACU_VAV_MID | 4.22 | 4.22 | 1.53 | 1.53 | 4.2233 | 1.5292 | 4.2233 | 0.3621 | 0.3000 |
PACU_VAV_TOP | 4.72 | 4.72 | 2.26 | 2.26 | 4.7227 | 2.2573 | 4.7227 | 0.4780 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 21031.588 | 21031.588 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21031.59 | 14033.53 | 0.424691 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 5751.39 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 21082.857 | 21082.857 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21082.86 | 16628.51 | 0.503222 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 11796.83 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 30355.414 | 30355.414 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30355.41 | 30355.41 | 0.918634 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 21408.61 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 13357.104 | 13357.104 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13357.10 | 13357.10 | 0.404221 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00783812 | 50.1474 | 9387.12 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 8758.997 | 8758.997 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8759.00 | 8759.00 | 0.265070 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00784018 | 50.1604 | 6154.95 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 13390.979 | 13390.979 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13390.98 | 13390.98 | 0.405246 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00783896 | 50.1527 | 9410.84 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 8729.071 | 8729.071 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8729.07 | 8729.07 | 0.264164 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00783916 | 50.1540 | 6133.99 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 10234.924 | 10234.924 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10234.92 | 10234.92 | 0.309735 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00780201 | 49.9194 | 7199.33 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6824.230 | 6824.230 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6824.23 | 6824.23 | 0.206519 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00781389 | 49.9944 | 4799.29 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 10280.269 | 10280.269 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10280.27 | 10280.27 | 0.311108 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00780397 | 49.9318 | 7231.13 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 6794.465 | 6794.465 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6794.46 | 6794.46 | 0.205618 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00781204 | 49.9827 | 4778.44 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 10194.860 | 10194.860 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10194.86 | 10194.86 | 0.308523 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00772943 | 49.4614 | 7172.05 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 6756.187 | 6756.187 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6756.19 | 6756.19 | 0.204460 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00774187 | 49.5400 | 4752.03 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 10225.589 | 10225.589 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10225.59 | 10225.59 | 0.309453 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00773124 | 49.4728 | 7193.57 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 6726.204 | 6726.204 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6726.20 | 6726.20 | 0.203552 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00773956 | 49.5253 | 4731.03 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 79214.313 | 63423.356 | 4.785337 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 80971.32 | 77582.65 | 4.785337 | 24.48 | 16.64 | 0.00872831 | 11.00 | 11.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 19.9798 | 24.00 | 0.00880854 | 46.8937 | 65151.12 | 0.00 | 81680.59 | 63941.98 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 15559.493 | 15559.493 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15559.49 | 15559.49 | 1.435601 | 3.75 | 2.88 | 0.00434634 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 66.5993 | 19.70 | 0.00766652 | 53.1729 | 13267.54 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 69910.586 | 55974.278 | 4.223298 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 71503.77 | 68275.12 | 4.223298 | 24.54 | 16.68 | 0.00874839 | 11.00 | 11.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 22.6387 | 24.00 | 0.00884830 | 47.1023 | 57495.08 | 0.00 | 72087.20 | 56431.99 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 17192.285 | 17192.285 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17192.29 | 17192.29 | 1.266990 | 1.47 | 0.94 | 0.00387448 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 75.4623 | 19.60 | 0.00747332 | 52.1656 | 18481.61 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 78176.752 | 62592.628 | 4.722658 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 79915.00 | 76553.92 | 4.722658 | 24.49 | 16.65 | 0.00872962 | 11.00 | 11.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 20.2450 | 24.00 | 0.00881163 | 46.9098 | 64224.84 | 0.00 | 80610.72 | 63104.46 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 16984.688 | 16984.688 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16984.69 | 16984.69 | 1.416797 | 2.79 | 2.28 | 0.00429490 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 67.4832 | 17.60 | 0.00757486 | 59.9197 | 19732.82 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 21031.588 | 21031.588 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21031.59 | 14033.53 | 1.0000 | 0.50596508 | 0.424691 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21031.59 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.66 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 5751.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 21082.857 | 21082.857 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21082.86 | 16628.51 | 1.0000 | 0.59952453 | 0.503222 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21082.86 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 11796.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 30355.414 | 30355.414 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30355.41 | 30355.41 | 1.0000 | 1.09443479 | 0.918634 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30355.41 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 21408.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 13357.104 | 13357.104 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13357.10 | 13357.10 | 1.0000 | 0.48157733 | 0.404221 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13357.10 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00783812 | 21.00 | 0.00783812 | 50.1474 | 9387.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8758.997 | 8758.997 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8759.00 | 8759.00 | 1.0000 | 0.31579709 | 0.265070 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8759.00 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00784018 | 21.00 | 0.00784018 | 50.1604 | 6154.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 13390.979 | 13390.979 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13390.98 | 13390.98 | 1.0000 | 0.48279867 | 0.405246 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13390.98 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00783896 | 21.00 | 0.00783896 | 50.1527 | 9410.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 8729.071 | 8729.071 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8729.07 | 8729.07 | 1.0000 | 0.31471815 | 0.264164 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8729.07 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00783916 | 21.00 | 0.00783916 | 50.1540 | 6133.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 10234.924 | 10234.924 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10234.92 | 10234.92 | 1.0000 | 0.36901017 | 0.309735 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10234.92 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.91 | 0.00780201 | 21.00 | 0.00780201 | 49.9194 | 7199.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 6824.230 | 6824.230 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6824.23 | 6824.23 | 1.0000 | 0.24604095 | 0.206519 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6824.23 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00781389 | 21.00 | 0.00781389 | 49.9944 | 4799.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 10280.269 | 10280.269 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10280.27 | 10280.27 | 1.0000 | 0.37064505 | 0.311108 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10280.27 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.91 | 0.00780397 | 21.00 | 0.00780397 | 49.9318 | 7231.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 6794.465 | 6794.465 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6794.46 | 6794.46 | 1.0000 | 0.24496780 | 0.205618 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6794.46 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00781204 | 21.00 | 0.00781204 | 49.9827 | 4778.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 10194.860 | 10194.860 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10194.86 | 10194.86 | 1.0000 | 0.36756573 | 0.308523 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10194.86 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00772943 | 21.00 | 0.00772943 | 49.4614 | 7172.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 6756.187 | 6756.187 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6756.19 | 6756.19 | 1.0000 | 0.24358774 | 0.204460 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6756.19 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00774187 | 21.00 | 0.00774187 | 49.5400 | 4752.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 10225.589 | 10225.589 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10225.59 | 10225.59 | 1.0000 | 0.36867363 | 0.309453 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10225.59 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00773124 | 21.00 | 0.00773124 | 49.4728 | 7193.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 6726.204 | 6726.204 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6726.20 | 6726.20 | 1.0000 | 0.24250671 | 0.203552 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6726.20 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00773956 | 21.00 | 0.00773956 | 49.5253 | 4731.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 79214.313 | 63423.356 | 4.785337 | -999.0 | -999.000 | -999.0000 | 1.01592 | 1.00000 | 1021.0655 | 1004.8586 | 1.1914 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.785337 | 5.70111615 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 80971.32 | 77582.65 | 1.0222 | 5.70111615 | 4.785337 | 24.48 | 16.64 | 0.00872831 | 46823.3 | 11.00 | 11.00 | 0.00850000 | 32485.6 | -999.0 | -999.00 | -999.00 | -999.00 | 10475.155 | 70496.17 | 26.40 | 0.00840708 | 17.04 | 0.95610000 | 19.9798 | 24.00 | 0.00880854 | 24.00 | 0.00880854 | 46.8937 | 65151.12 | 0.00 | 81680.59 | 63941.98 | 5.47596515 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.26 | 14.43 | 0.00991458 | 40406.2 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 15559.493 | 15559.493 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.785337 | 5.70111615 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15559.49 | 15559.49 | 1.0000 | 1.71033484 | 1.435601 | 3.75 | 2.88 | 0.00434634 | 14665.0 | 12.80 | 11.50 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15559.49 | -4.30 | 0.00265759 | -4.30 | 0.95610000 | 66.5993 | 19.79 | 0.00771361 | 19.70 | 0.00766652 | 53.1729 | 13267.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 69910.586 | 55974.278 | 4.223298 | -999.0 | -999.000 | -999.0000 | 1.00859 | 1.00000 | 1021.1028 | 1004.8586 | 1.1914 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.223298 | 5.03151961 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 71503.77 | 68275.12 | 1.0228 | 5.03151961 | 4.223298 | 24.54 | 16.68 | 0.00874839 | 46939.7 | 11.00 | 11.00 | 0.00850000 | 32485.6 | -999.0 | -999.00 | -999.00 | -999.00 | 9244.847 | 62258.92 | 26.40 | 0.00840708 | 17.04 | 0.95610000 | 22.6387 | 24.00 | 0.00884830 | 24.00 | 0.00884830 | 47.1023 | 57495.08 | 0.00 | 72087.20 | 56431.99 | 4.83281262 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.26 | 14.43 | 0.00991458 | 40406.2 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17192.285 | 17192.285 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.223298 | 5.03151961 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17192.29 | 17192.29 | 1.0000 | 1.50945588 | 1.266990 | 1.47 | 0.94 | 0.00387448 | 11172.8 | 12.80 | 11.50 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17192.29 | -4.30 | 0.00265759 | -4.30 | 0.95610000 | 75.4623 | 19.20 | 0.00761689 | 19.60 | 0.00747332 | 52.1656 | 18481.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 78176.752 | 62592.628 | 4.722658 | -999.0 | -999.000 | -999.0000 | 1.01526 | 1.00000 | 1021.0679 | 1004.8586 | 1.1914 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.722658 | 5.62644206 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | Sensible | 79915.00 | 76553.92 | 1.0222 | 5.62644206 | 4.722658 | 24.49 | 16.65 | 0.00872962 | 46833.7 | 11.00 | 11.00 | 0.00850000 | 32485.6 | -999.0 | -999.00 | -999.00 | -999.00 | 10337.949 | 69577.05 | 26.40 | 0.00840708 | 17.04 | 0.95610000 | 20.2450 | 24.00 | 0.00881163 | 24.00 | 0.00881163 | 46.9098 | 64224.84 | 0.00 | 80610.72 | 63104.46 | 5.40424013 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.26 | 14.43 | 0.00991458 | 40406.2 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16984.688 | 16984.688 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.722658 | 5.62644206 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16984.69 | 16984.69 | 1.0000 | 1.68793262 | 1.416797 | 2.79 | 2.28 | 0.00429490 | 13563.3 | 12.80 | 11.50 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16984.69 | -4.30 | 0.00265759 | -4.30 | 0.95610000 | 67.4832 | 17.49 | 0.00769286 | 17.60 | 0.00757486 | 59.9197 | 19732.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.79 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.22 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.72 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1593.17 | 2563.33 | 20.83 |
CORE_MID | 932.00 | 3633.50 | 135.83 |
CORE_TOP | 1341.33 | 4242.17 | 714.67 |
PERIMETER_TOP_ZN_3 | 2278.83 | 4636.17 | 1693.50 |
PERIMETER_TOP_ZN_2 | 2695.33 | 3984.00 | 1509.67 |
PERIMETER_TOP_ZN_1 | 2524.33 | 4006.00 | 1334.33 |
PERIMETER_TOP_ZN_4 | 2605.67 | 4295.17 | 1593.67 |
PERIMETER_BOT_ZN_3 | 1518.50 | 4819.83 | 1206.33 |
PERIMETER_BOT_ZN_2 | 2194.33 | 3753.50 | 982.67 |
PERIMETER_BOT_ZN_1 | 1983.67 | 4160.67 | 927.67 |
PERIMETER_BOT_ZN_4 | 2110.50 | 4029.33 | 1032.83 |
PERIMETER_MID_ZN_3 | 1674.50 | 4337.00 | 1047.00 |
PERIMETER_MID_ZN_2 | 1875.00 | 3268.00 | 889.00 |
PERIMETER_MID_ZN_1 | 2066.00 | 3646.17 | 742.83 |
PERIMETER_MID_ZN_4 | 2097.83 | 3968.33 | 974.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4117.33 | 5053.67 | 1926.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.17 | 0.00 | 0.17 | 0.00 |
CORE_TOP | 1.17 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 13.50 | 0.00 | 11.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 3.00 | 13.67 | 0.83 | 13.67 |
PERIMETER_TOP_ZN_1 | 1.83 | 20.67 | 0.67 | 20.50 |
PERIMETER_TOP_ZN_4 | 2.83 | 21.33 | 1.00 | 13.33 |
PERIMETER_BOT_ZN_3 | 3.00 | 0.00 | 2.67 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.17 | 6.00 | 0.00 | 6.00 |
PERIMETER_BOT_ZN_1 | 277.00 | 10.33 | 277.00 | 10.33 |
PERIMETER_BOT_ZN_4 | 0.33 | 13.00 | 0.17 | 7.00 |
PERIMETER_MID_ZN_3 | 1.83 | 0.00 | 1.67 | 0.00 |
PERIMETER_MID_ZN_2 | 0.50 | 16.33 | 0.33 | 16.33 |
PERIMETER_MID_ZN_1 | 0.33 | 20.83 | 0.17 | 20.83 |
PERIMETER_MID_ZN_4 | 0.50 | 20.83 | 0.33 | 12.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 288.83 | 101.17 | 285.67 | 85.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.960 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.665 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.635 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.663 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 1.018 | 0.051 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 1.111 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 1.013 | 0.051 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.577 | 0.026 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.920 | 0.027 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.864 | 0.841 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.879 | 0.027 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.682 | 0.040 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.945 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 1.143 | 0.041 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 1.027 | 0.043 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.51 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 108.48 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 15166139.37 | 0.00 | 15166139.37 | 0.00 | 15166139.37 | 13393058.27 | 4420.83 | 634.85 | 3704.32 | 31.72 |
CORE_MID | 10552693.65 | 0.00 | 10552693.65 | 0.00 | 10552693.65 | 13393058.27 | 4485.44 | 1297.33 | 2977.23 | 40.00 |
CORE_TOP | 10103717.05 | 0.00 | 10103717.05 | 0.00 | 10103717.05 | 13393058.27 | 4607.46 | 1437.41 | 2715.13 | 52.37 |
PERIMETER_TOP_ZN_3 | 2223956.16 | 0.00 | 2223956.16 | 327463.48 | 2551419.64 | 2823374.22 | 4596.04 | 1690.35 | 2473.60 | 52.37 |
PERIMETER_TOP_ZN_2 | 2150685.55 | 0.00 | 2150685.55 | 218307.67 | 2368993.22 | 1787429.43 | 4491.05 | 1635.75 | 2633.20 | 52.37 |
PERIMETER_TOP_ZN_1 | 3706934.92 | 0.00 | 3706934.92 | 327463.48 | 4034398.40 | 2823374.22 | 4370.39 | 1382.97 | 3006.64 | 52.37 |
PERIMETER_TOP_ZN_4 | 2153759.83 | 0.00 | 2153759.83 | 218307.67 | 2372067.50 | 1787312.18 | 4440.61 | 1290.12 | 3029.27 | 52.37 |
PERIMETER_BOT_ZN_3 | 1934434.21 | 0.00 | 1934434.21 | 174110.49 | 2108544.70 | 2823374.22 | 5781.23 | 653.94 | 2324.83 | 31.72 |
PERIMETER_BOT_ZN_2 | 1943206.56 | 0.00 | 1943206.56 | 116072.96 | 2059279.52 | 1787429.43 | 5625.14 | 684.21 | 2450.65 | 31.72 |
PERIMETER_BOT_ZN_1 | 2891454.03 | 0.00 | 2891454.03 | 2905154.06 | 5796608.09 | 2823374.22 | 5260.35 | 545.53 | 2954.13 | 31.72 |
PERIMETER_BOT_ZN_4 | 1862939.01 | 0.00 | 1862939.01 | 116072.96 | 1979011.97 | 1787312.18 | 5695.72 | 733.49 | 2330.79 | 31.72 |
PERIMETER_MID_ZN_3 | 2284638.40 | 0.00 | 2284638.40 | 272588.12 | 2557226.52 | 2823374.22 | 4566.15 | 1505.47 | 2688.38 | 40.00 |
PERIMETER_MID_ZN_2 | 2040863.56 | 0.00 | 2040863.56 | 181724.32 | 2222587.88 | 1601953.02 | 4343.30 | 1253.34 | 3163.36 | 949.00 |
PERIMETER_MID_ZN_1 | 3810894.20 | 0.00 | 3810894.20 | 272588.12 | 4083482.31 | 2823374.22 | 4278.13 | 1197.33 | 3284.54 | 40.00 |
PERIMETER_MID_ZN_4 | 2180032.29 | 0.00 | 2180032.29 | 181724.32 | 2361756.61 | 1787312.18 | 4538.85 | 1674.17 | 2546.98 | 40.00 |
Total Facility | 65006348.79 | 0.00 | 65006348.79 | 5311577.65 | 70317926.44 | 67658168.57 | 6088.16 | 2048.97 | 4256.61 | 973.54 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.7057 | 0.0000 | 0.7057 | 0.0000 | 0.7057 | 0.4247 | 1634.22 | 634.85 | 3673.93 |
CORE_MID | 0.4894 | 0.0000 | 0.4894 | 0.0000 | 0.4894 | 0.4247 | 1705.85 | 1297.17 | 2939.98 |
CORE_TOP | 0.4681 | 0.0000 | 0.4681 | 0.0000 | 0.4681 | 0.4247 | 1830.12 | 1437.16 | 2675.71 |
PERIMETER_TOP_ZN_3 | 0.1031 | 0.0000 | 0.1031 | 0.0076 | 0.1107 | 0.0895 | 1818.71 | 1690.10 | 2434.19 |
PERIMETER_TOP_ZN_2 | 0.1000 | 0.0000 | 0.1000 | 0.0051 | 0.1050 | 0.0567 | 1713.72 | 1635.50 | 2593.79 |
PERIMETER_TOP_ZN_1 | 0.1724 | 0.0000 | 0.1724 | 0.0076 | 0.1800 | 0.0895 | 1593.06 | 1382.72 | 2967.22 |
PERIMETER_TOP_ZN_4 | 0.0995 | 0.0000 | 0.0995 | 0.0051 | 0.1045 | 0.0567 | 1663.28 | 1289.95 | 2989.77 |
PERIMETER_BOT_ZN_3 | 0.0898 | 0.0000 | 0.0898 | 0.0040 | 0.0938 | 0.0895 | 2994.62 | 653.94 | 2294.44 |
PERIMETER_BOT_ZN_2 | 0.0904 | 0.0000 | 0.0904 | 0.0027 | 0.0931 | 0.0567 | 2838.53 | 684.21 | 2420.26 |
PERIMETER_BOT_ZN_1 | 0.1345 | 0.0000 | 0.1345 | 0.1317 | 0.2662 | 0.0895 | 2473.74 | 545.53 | 2923.74 |
PERIMETER_BOT_ZN_4 | 0.0864 | 0.0000 | 0.0864 | 0.0027 | 0.0891 | 0.0567 | 2909.11 | 733.49 | 2300.41 |
PERIMETER_MID_ZN_3 | 0.1060 | 0.0000 | 0.1060 | 0.0063 | 0.1123 | 0.0895 | 1786.57 | 1505.30 | 2651.13 |
PERIMETER_MID_ZN_2 | 0.0929 | 0.0000 | 0.0929 | 0.0044 | 0.0973 | 0.0567 | 1563.71 | 1253.18 | 2217.11 |
PERIMETER_MID_ZN_1 | 0.1773 | 0.0000 | 0.1773 | 0.0063 | 0.1836 | 0.0895 | 1498.55 | 1197.16 | 3247.29 |
PERIMETER_MID_ZN_4 | 0.1009 | 0.0000 | 0.1009 | 0.0042 | 0.1051 | 0.0567 | 1759.35 | 1674.09 | 2509.56 |
Total Facility | 3.0163 | 0.0000 | 3.0163 | 0.1876 | 3.2039 | 2.1513 | 3291.22 | 2048.55 | 4206.77 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 33778308.59 | 0.00 | 33778308.59 | 22614548.33 | 4101.34 | 7.26 | 4651.40 | 31.72 |
PACU_VAV_MID | 29620966.96 | 0.00 | 29620966.96 | 22429071.92 | 4082.96 | 5.04 | 4672.00 | 40.00 |
PACU_VAV_TOP | 28868535.55 | 0.00 | 28868535.55 | 22614548.33 | 4136.87 | 3.51 | 4619.62 | 52.37 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.5709 | 0.0000 | 1.5709 | 0.7171 | 1314.73 | 7.26 | 4621.02 |
PACU_VAV_MID | 1.3746 | 0.0000 | 1.3746 | 0.7084 | 1303.79 | 5.04 | 4634.16 |
PACU_VAV_TOP | 1.3386 | 0.0000 | 1.3386 | 0.7171 | 1359.71 | 3.51 | 4579.79 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 327.94 | 2756.67 | 0.00 | 0.00 | 0.00 | 1708.94 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 26.16 | 2602.53 | 0.00 | 0.00 | 0.00 | 2208.98 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 13.34 | 2510.86 | 0.00 | 0.00 | 0.00 | 2308.37 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.3345 | 2.5568 | 0.0000 | 0.0000 | 0.0000 | 1.1313 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.2886 | 2.2879 | 0.0000 | 0.0000 | 0.0000 | 1.0305 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.0550 | 2.2548 | 0.0000 | 0.0000 | 0.0000 | 1.0395 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 943 |
Defaulted Fields | 546 |
Fields with Defaults | 2233 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1205.57 | 12315.29 | 02-APR-17:30 | 200003.49 | 02-JAN-07:10 |
Electricity:Building | 939.52 | 12146.72 | 02-APR-17:20 | 70868.50 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 291.77 | 4006.86 | 01-JAN-00:10 | 23121.21 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 939.52 | 12146.72 | 02-APR-17:20 | 70868.50 | 02-JAN-08:10 |
InteriorLights:Electricity | 234.09 | 905.38 | 02-APR-17:20 | 25003.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 234.09 | 905.38 | 02-APR-17:20 | 25003.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 234.09 | 905.38 | 02-APR-17:20 | 25003.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 234.09 | 905.38 | 02-APR-17:20 | 25003.79 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 31.27 | 413.68 | 02-APR-17:10 | 2475.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.94 | 27.57 | 01-JAN-10:00 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.94 | 27.57 | 01-JAN-10:00 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.74 | 261.88 | 02-APR-17:10 | 1567.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.34 | 17.46 | 01-JAN-08:40 | 658.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.34 | 17.46 | 01-JAN-08:40 | 658.76 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 31.14 | 413.67 | 02-APR-17:10 | 2475.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.81 | 27.57 | 01-JAN-08:40 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.81 | 27.57 | 01-JAN-08:40 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.76 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.36 | 17.46 | 01-JAN-10:00 | 658.71 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.36 | 17.46 | 01-JAN-10:00 | 658.71 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 31.25 | 413.68 | 02-APR-17:10 | 2475.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.92 | 27.57 | 01-JAN-10:00 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.92 | 27.57 | 01-JAN-10:00 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.74 | 261.88 | 02-APR-17:10 | 1567.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.33 | 17.46 | 01-JAN-08:40 | 658.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.33 | 17.46 | 01-JAN-08:40 | 658.76 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 31.13 | 413.67 | 02-APR-17:10 | 2475.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.80 | 27.57 | 01-JAN-08:40 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.80 | 27.57 | 01-JAN-08:40 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.75 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.35 | 17.46 | 01-JAN-09:50 | 658.71 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.35 | 17.46 | 01-JAN-09:50 | 658.71 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 31.27 | 413.68 | 02-APR-17:10 | 2475.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.94 | 27.57 | 01-JAN-10:00 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.94 | 27.57 | 01-JAN-10:00 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.74 | 261.88 | 02-APR-17:10 | 1567.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.34 | 17.46 | 01-JAN-08:40 | 658.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.34 | 17.46 | 01-JAN-08:40 | 658.76 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 31.14 | 413.67 | 02-APR-17:10 | 2475.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.81 | 27.57 | 01-JAN-08:40 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.81 | 27.57 | 01-JAN-08:40 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.76 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.36 | 17.46 | 01-JAN-10:00 | 658.71 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.36 | 17.46 | 01-JAN-10:00 | 658.71 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 214.15 | 168.34 | 01-JAN-00:10 | 164876.94 | 02-JAN-07:10 |
ExteriorEquipment:Electricity | 11.69 | 168.34 | 01-JAN-00:10 | 840.16 | 28-DEC-08:20 |
Transformer:ExteriorEquipment:Electricity | 11.69 | 168.34 | 01-JAN-00:10 | 840.16 | 28-DEC-08:20 |
ElectricityPurchased:Facility | 1205.57 | 12315.29 | 02-APR-17:30 | 200003.49 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 1205.57 | 12315.29 | 02-APR-17:30 | 200003.49 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1205.57 | 12315.29 | 02-APR-17:30 | 200003.49 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1205.57 | 12315.29 | 02-APR-17:30 | 200003.49 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1205.57 | 12315.29 | 02-APR-17:30 | 200003.49 | 02-JAN-07:10 |
ElectricityNet:Plant | 1205.57 | 12315.29 | 02-APR-17:30 | 200003.49 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 1205.57 | 12315.29 | 02-APR-17:30 | 200003.49 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1205.57 | 12315.29 | 02-APR-17:30 | 200003.49 | 02-JAN-07:10 |
Heating:Electricity | 94.90 | 0.00 | 01-JAN-00:10 | 158833.83 | 02-JAN-07:10 |
General:Heating:Electricity | 94.90 | 0.00 | 01-JAN-00:10 | 158833.83 | 02-JAN-07:10 |
Fans:Electricity | 67.41 | 0.00 | 01-JAN-00:10 | 21710.65 | 13-JUN-15:30 |
General:Fans:Electricity | 67.41 | 0.00 | 01-JAN-00:10 | 21710.65 | 13-JUN-15:30 |
ExteriorLights:Electricity | 51.76 | 0.00 | 01-JAN-08:20 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 51.76 | 0.00 | 01-JAN-08:20 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 40.15 | 0.00 | 01-JAN-00:10 | 42856.96 | 13-JUN-16:00 |
General:Cooling:Electricity | 40.15 | 0.00 | 01-JAN-00:10 | 42856.96 | 13-JUN-16:00 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-07:10 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-07:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-07:10 |
WIRED_LTG_ELECTRICITY | 6.58 | 0.00 | 01-JAN-00:10 | 702.61 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 273.83 | 1886.44 | 04-JAN-06:20 | 70029.61 | 10-JAN-08:10 |
NaturalGas:HVAC | 138.99 | 0.00 | 01-JAN-00:10 | 61361.77 | 10-JAN-08:00 |
Heating:NaturalGas | 138.99 | 0.00 | 01-JAN-00:10 | 61361.77 | 10-JAN-08:00 |
General:Heating:NaturalGas | 138.99 | 0.00 | 01-JAN-00:10 | 61361.77 | 10-JAN-08:00 |
NaturalGas:Plant | 134.83 | 1886.44 | 04-JAN-06:20 | 10175.40 | 22-FEB-12:10 |
WaterSystems:NaturalGas | 134.83 | 1886.44 | 04-JAN-06:20 | 10175.40 | 22-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 134.83 | 1886.44 | 04-JAN-06:20 | 10175.40 | 22-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1272.57 | 0.00 | 01-JAN-00:10 | 326899.46 | 13-JUN-15:30 |
EnergyTransfer:Building | 847.06 | 0.00 | 01-JAN-00:10 | 140579.55 | 02-JAN-07:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 199.29 | 0.00 | 01-JAN-00:10 | 24464.75 | 24-JUL-08:00 |
Heating:EnergyTransfer | 82.23 | 0.00 | 01-JAN-00:10 | 140053.82 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.03 | 0.00 | 01-JAN-00:10 | 7887.44 | 02-JAN-07:10 |
General:Heating:EnergyTransfer | 82.23 | 0.00 | 01-JAN-00:10 | 140053.82 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.03 | 0.00 | 01-JAN-00:10 | 7887.44 | 02-JAN-07:10 |
Cooling:EnergyTransfer | 764.83 | 0.00 | 01-JAN-00:10 | 140476.21 | 13-JUN-15:30 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 199.26 | 0.00 | 01-JAN-00:10 | 24464.75 | 24-JUL-08:00 |
General:Cooling:EnergyTransfer | 764.83 | 0.00 | 01-JAN-00:10 | 140476.21 | 13-JUN-15:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 199.26 | 0.00 | 01-JAN-00:10 | 24464.75 | 24-JUL-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 32.74 | 0.00 | 01-JAN-00:10 | 9642.14 | 26-DEC-06:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 15.40 | 0.00 | 01-JAN-00:10 | 9642.14 | 26-DEC-06:30 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 15.40 | 0.00 | 01-JAN-00:10 | 9642.14 | 26-DEC-06:30 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 17.34 | 0.00 | 01-JAN-00:10 | 8734.04 | 13-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 17.34 | 0.00 | 01-JAN-00:10 | 8734.04 | 13-JUN-14:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.63 | 0.00 | 01-JAN-00:10 | 7219.84 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 7.71 | 0.00 | 01-JAN-00:10 | 7219.84 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 7.71 | 0.00 | 01-JAN-00:10 | 7219.84 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 7.92 | 0.00 | 01-JAN-00:10 | 3752.27 | 24-JUL-15:50 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 7.92 | 0.00 | 01-JAN-00:10 | 3752.27 | 24-JUL-15:50 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 18.68 | 0.00 | 01-JAN-00:10 | 4103.51 | 24-JUL-16:00 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 5.92 | 0.00 | 01-JAN-00:10 | 4066.46 | 02-JAN-08:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 5.92 | 0.00 | 01-JAN-00:10 | 4066.46 | 02-JAN-08:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 12.76 | 0.00 | 01-JAN-00:10 | 4103.51 | 24-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 12.76 | 0.00 | 01-JAN-00:10 | 4103.51 | 24-JUL-16:00 |
EnergyTransfer:Zone:CORE_MID | 124.76 | 0.00 | 01-JAN-00:10 | 17110.74 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.34 | 0.00 | 01-JAN-00:10 | 17110.74 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.34 | 0.00 | 01-JAN-00:10 | 17110.74 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 124.42 | 0.00 | 01-JAN-00:10 | 16356.44 | 24-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 124.42 | 0.00 | 01-JAN-00:10 | 16356.44 | 24-JUL-14:00 |
EnergyTransfer:Zone:CORE_TOP | 111.69 | 0.00 | 01-JAN-00:10 | 25728.62 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 3.01 | 0.00 | 01-JAN-00:10 | 25728.62 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 3.01 | 0.00 | 01-JAN-00:10 | 25728.62 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 108.68 | 0.00 | 01-JAN-00:10 | 17590.39 | 24-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 108.68 | 0.00 | 01-JAN-00:10 | 17590.39 | 24-JUL-15:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 26.56 | 0.00 | 01-JAN-00:10 | 7472.49 | 26-DEC-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 7.28 | 0.00 | 01-JAN-00:10 | 7472.49 | 26-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 7.28 | 0.00 | 01-JAN-00:10 | 7472.49 | 26-DEC-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 19.29 | 0.00 | 01-JAN-00:10 | 5348.87 | 13-JUN-15:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 19.29 | 0.00 | 01-JAN-00:10 | 5348.87 | 13-JUN-15:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 25.74 | 0.00 | 01-JAN-00:10 | 8063.26 | 13-JUN-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.14 | 0.00 | 01-JAN-00:10 | 6587.94 | 26-DEC-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.14 | 0.00 | 01-JAN-00:10 | 6587.94 | 26-DEC-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 21.60 | 0.00 | 01-JAN-00:10 | 8063.26 | 13-JUN-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 21.60 | 0.00 | 01-JAN-00:10 | 8063.26 | 13-JUN-08:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 43.72 | 0.00 | 01-JAN-00:10 | 12814.40 | 11-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.16 | 0.00 | 01-JAN-00:10 | 9676.07 | 26-DEC-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.16 | 0.00 | 01-JAN-00:10 | 9676.07 | 26-DEC-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 38.57 | 0.00 | 01-JAN-00:10 | 12814.40 | 11-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 38.57 | 0.00 | 01-JAN-00:10 | 12814.40 | 11-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 25.75 | 0.00 | 01-JAN-00:10 | 9385.14 | 13-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.50 | 0.00 | 01-JAN-00:10 | 6534.72 | 26-DEC-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.50 | 0.00 | 01-JAN-00:10 | 6534.72 | 26-DEC-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 21.25 | 0.00 | 01-JAN-00:10 | 9385.14 | 13-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 21.25 | 0.00 | 01-JAN-00:10 | 9385.14 | 13-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.93 | 0.00 | 01-JAN-00:10 | 5676.08 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.83 | 0.00 | 01-JAN-00:10 | 5676.08 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.83 | 0.00 | 01-JAN-00:10 | 5676.08 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 18.11 | 0.00 | 01-JAN-00:10 | 3833.38 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 18.11 | 0.00 | 01-JAN-00:10 | 3833.38 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 22.23 | 0.00 | 01-JAN-00:10 | 6229.95 | 13-JUN-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.52 | 0.00 | 01-JAN-00:10 | 4847.62 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.52 | 0.00 | 01-JAN-00:10 | 4847.62 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 20.71 | 0.00 | 01-JAN-00:10 | 6229.95 | 13-JUN-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 20.71 | 0.00 | 01-JAN-00:10 | 6229.95 | 13-JUN-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 41.29 | 0.00 | 01-JAN-00:10 | 10372.69 | 11-SEP-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 15.97 | 0.00 | 01-JAN-00:10 | 10271.72 | 11-JAN-07:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 15.97 | 0.00 | 01-JAN-00:10 | 10271.72 | 11-JAN-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 25.32 | 0.00 | 01-JAN-00:10 | 10372.69 | 11-SEP-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 25.32 | 0.00 | 01-JAN-00:10 | 10372.69 | 11-SEP-13:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 21.18 | 0.00 | 01-JAN-00:10 | 7037.71 | 13-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.61 | 0.00 | 01-JAN-00:10 | 4858.70 | 02-JAN-07:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.61 | 0.00 | 01-JAN-00:10 | 4858.70 | 02-JAN-07:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 19.57 | 0.00 | 01-JAN-00:10 | 7037.71 | 13-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 19.57 | 0.00 | 01-JAN-00:10 | 7037.71 | 13-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 24.74 | 0.00 | 01-JAN-00:10 | 6313.29 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.37 | 0.00 | 01-JAN-00:10 | 6313.29 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.37 | 0.00 | 01-JAN-00:10 | 6313.29 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 22.37 | 0.00 | 01-JAN-00:10 | 4893.17 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 22.37 | 0.00 | 01-JAN-00:10 | 4893.17 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 23.67 | 0.00 | 01-JAN-00:10 | 8117.22 | 13-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.40 | 0.00 | 01-JAN-00:10 | 4834.35 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.40 | 0.00 | 01-JAN-00:10 | 4834.35 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 22.27 | 0.00 | 01-JAN-00:10 | 8117.22 | 13-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 22.27 | 0.00 | 01-JAN-00:10 | 8117.22 | 13-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 43.84 | 0.00 | 01-JAN-00:10 | 12497.03 | 11-SEP-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.55 | 0.00 | 01-JAN-00:10 | 6802.11 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.55 | 0.00 | 01-JAN-00:10 | 6802.11 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 42.29 | 0.00 | 01-JAN-00:10 | 12497.03 | 11-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 42.29 | 0.00 | 01-JAN-00:10 | 12497.03 | 11-SEP-13:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 24.61 | 0.00 | 01-JAN-00:10 | 8920.34 | 13-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.49 | 0.00 | 01-JAN-00:10 | 4816.90 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.49 | 0.00 | 01-JAN-00:10 | 4816.90 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 23.12 | 0.00 | 01-JAN-00:10 | 8920.34 | 13-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 23.12 | 0.00 | 01-JAN-00:10 | 8920.34 | 13-JUN-17:00 |
PlantLoopHeatingDemand:Facility | 52.59 | 0.00 | 01-JAN-00:10 | 6268.07 | 16-FEB-12:30 |
PlantLoopHeatingDemand:Plant | 52.59 | 0.00 | 01-JAN-00:10 | 6268.07 | 16-FEB-12:30 |
WaterSystems:PlantLoopHeatingDemand | 52.59 | 0.00 | 01-JAN-00:10 | 6268.07 | 16-FEB-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 52.59 | 0.00 | 01-JAN-00:10 | 6268.07 | 16-FEB-12:30 |
EnergyTransfer:HVAC | 372.93 | 0.00 | 01-JAN-00:10 | 181978.87 | 13-JUN-15:30 |
HeatingCoils:EnergyTransfer | 206.09 | 0.00 | 01-JAN-00:10 | 181703.45 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 166.83 | 0.00 | 01-JAN-00:10 | 181978.87 | 13-JUN-15:30 |
EnergyTransfer:Plant | 52.59 | 0.00 | 01-JAN-00:10 | 6268.07 | 16-FEB-12:30 |
WaterSystems:EnergyTransfer | 52.59 | 0.00 | 01-JAN-00:10 | 6268.07 | 16-FEB-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 52.59 | 0.00 | 01-JAN-00:10 | 6268.07 | 16-FEB-12:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.027 | -199.258 | 0.000 | 0.000 | 32.884 | 55.599 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -125.420 |
CORE_MID | 0.000 | 0.000 | 0.337 | -124.422 | 0.000 | 0.000 | 34.223 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -81.163 |
CORE_TOP | 0.000 | 0.000 | 3.013 | -108.679 | 0.000 | 0.000 | 35.112 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -100.471 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 7.276 | -19.285 | 0.000 | 0.000 | 7.621 | 6.937 | 24.333 | 14.251 | 0.000 | 0.002 | 0.000 | 0.000 | -31.464 | 0.000 | -4.663 | -5.008 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 4.139 | -21.599 | 0.000 | 0.000 | 4.744 | 4.341 | 15.404 | 30.534 | 0.000 | 0.001 | 0.000 | 0.000 | -20.415 | 0.000 | -3.188 | -13.960 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 5.158 | -38.567 | 0.000 | 0.000 | 7.429 | 6.811 | 24.332 | 61.088 | 0.000 | 0.002 | 0.001 | 0.000 | -31.591 | 0.000 | -4.878 | -29.784 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 4.504 | -21.249 | 0.000 | 0.000 | 4.790 | 4.357 | 15.403 | 29.834 | 0.000 | 0.001 | 0.000 | 0.000 | -21.204 | 0.000 | -3.202 | -13.234 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 2.827 | -18.106 | 0.000 | 0.000 | 7.575 | 6.918 | 24.333 | 14.482 | 0.000 | 0.001 | 0.000 | 0.000 | -32.854 | 0.000 | -2.604 | -2.572 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 1.521 | -20.711 | 0.000 | 0.000 | 4.707 | 4.333 | 15.404 | 30.579 | 0.000 | 0.001 | 0.000 | 0.000 | -21.620 | 0.000 | -1.809 | -12.404 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 15.966 | -25.321 | 0.000 | 0.000 | 7.610 | 6.800 | 24.332 | 61.606 | 0.000 | 0.044 | 0.001 | 0.000 | -33.339 | 0.000 | -39.091 | -18.607 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 1.607 | -19.570 | 0.000 | 0.000 | 4.737 | 4.348 | 15.403 | 29.962 | 0.000 | 0.001 | 0.000 | 0.000 | -22.476 | 0.000 | -1.819 | -12.193 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 2.373 | -22.368 | 0.000 | 0.000 | 7.499 | 6.937 | 24.333 | 13.856 | 0.000 | 0.002 | 4.998 | 0.000 | -33.511 | 0.000 | -4.119 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.400 | -22.273 | 0.000 | 0.000 | 3.455 | 4.341 | 15.404 | 30.177 | 0.000 | 0.001 | 0.002 | 0.000 | -21.693 | 0.000 | -2.812 | -8.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 1.552 | -42.288 | 0.000 | 0.000 | 7.308 | 6.811 | 24.332 | 60.666 | 0.000 | 0.002 | 0.000 | 0.000 | -33.558 | 0.000 | -4.296 | -20.528 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 1.493 | -23.120 | 0.000 | 0.000 | 4.711 | 4.357 | 15.403 | 29.592 | 0.000 | 0.001 | 0.000 | 0.000 | -22.554 | 0.000 | -2.823 | -7.060 |
TOPFLOOR_PLENUM | 15.401 | -17.339 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.001 | 9.197 | 0.000 | 0.000 | 0.000 | -7.260 | -0.001 |
MIDFLOOR_PLENUM | 7.711 | -7.915 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.002 | 7.339 | 0.000 | 0.000 | 0.000 | -7.137 | -0.000 |
FIRSTFLOOR_PLENUM | 5.924 | -12.759 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.002 | 12.600 | 0.000 | 0.000 | 0.000 | -5.766 | -0.000 |
Total Facility | 29.035 | -38.013 | 53.192 | -726.815 | 0.000 | 0.000 | 174.405 | 234.087 | 705.434 | 406.628 | 0.000 | 0.063 | 34.139 | 0.000 | -326.279 | 0.000 | -95.468 | -450.405 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 24-JUL-05:12 | 0.00 | 0.00 | 0.00 | -40959.30 | 0.00 | 0.00 | 321.93 | 548.43 | 4989.51 | 0.00 | 0.00 | 0.00 | 35099.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 24-JUL-05:12 | 0.00 | 0.00 | 0.00 | -29733.58 | 0.00 | 0.00 | 331.64 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 25827.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-06:02 | 0.00 | 0.00 | 0.00 | -18122.50 | 0.00 | 0.00 | 727.53 | 1645.36 | 3025.92 | 0.00 | 0.00 | 0.00 | 12723.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 13-JUN-15:20 | 0.00 | 0.00 | 0.00 | -5348.88 | 0.00 | 0.00 | 737.22 | 496.34 | 1435.25 | 2933.90 | 0.00 | 22.68 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -276.51 |
PERIMETER_TOP_ZN_2 | 16-JUL-08:52 | 0.00 | 0.00 | 0.00 | -13354.60 | 0.00 | 0.00 | 15.50 | 17.46 | 302.86 | 10132.37 | 0.00 | 0.00 | 3034.90 | 0.00 | -0.00 | 0.00 | -148.49 | 0.00 |
PERIMETER_TOP_ZN_1 | 24-SEP-13:42 | 0.00 | 0.00 | 0.00 | -20244.16 | 0.00 | 0.00 | 24.10 | 27.57 | 478.41 | 13198.06 | 0.00 | 0.00 | 6712.12 | 0.00 | -0.00 | 0.00 | -196.10 | 0.00 |
PERIMETER_TOP_ZN_4 | 09-JUL-16:51 | 0.00 | 0.00 | 0.00 | -16131.60 | 0.00 | 0.00 | 13.24 | 17.46 | 302.86 | 11984.30 | 0.00 | 0.00 | 3983.13 | 0.00 | -0.00 | 0.00 | -169.39 | 0.00 |
PERIMETER_BOT_ZN_3 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | -3833.37 | 0.00 | 0.00 | 737.23 | 496.34 | 1435.25 | 2796.81 | 0.00 | 12.25 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1644.50 |
PERIMETER_BOT_ZN_2 | 23-JUL-08:51 | 0.00 | 0.00 | 0.00 | -10628.04 | 0.00 | 0.00 | 15.99 | 17.46 | 302.86 | 10410.36 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -69.81 | -48.82 |
PERIMETER_BOT_ZN_1 | 30-APR-12:12 | 0.00 | 0.00 | 0.00 | -16323.06 | 0.00 | 0.00 | 26.00 | 27.57 | 478.41 | 16466.17 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -67.64 | -607.47 |
PERIMETER_BOT_ZN_4 | 30-APR-17:31 | 0.00 | 0.00 | 0.00 | -12753.08 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 9070.43 | 0.00 | 0.00 | 3440.00 | 0.00 | -0.00 | 0.00 | -19.22 | 0.00 |
PERIMETER_MID_ZN_3 | 26-JUN-06:03 | 0.00 | 0.00 | 0.00 | -6494.40 | 0.00 | 0.00 | 149.19 | 165.45 | 637.89 | 2497.45 | 0.00 | 0.00 | 3094.89 | 0.00 | -0.00 | 0.00 | -50.46 | 0.00 |
PERIMETER_MID_ZN_2 | 30-APR-09:32 | 0.00 | 0.00 | 0.00 | -13569.16 | 0.00 | 0.00 | 15.03 | 17.46 | 302.86 | 9217.65 | 0.00 | 0.00 | 4172.52 | 0.00 | -0.00 | 0.00 | -156.36 | 0.00 |
PERIMETER_MID_ZN_1 | 30-APR-12:12 | 0.00 | 0.00 | 0.00 | -19660.84 | 0.00 | 0.00 | 22.92 | 27.57 | 478.41 | 16316.76 | 0.00 | 0.00 | 2937.10 | 0.00 | -0.00 | 0.00 | -121.92 | 0.00 |
PERIMETER_MID_ZN_4 | 30-APR-16:11 | 0.00 | 0.00 | 0.00 | -14709.95 | 0.00 | 0.00 | 13.63 | 17.46 | 302.86 | 10895.79 | 0.00 | 0.00 | 3491.69 | 0.00 | -0.00 | 0.00 | -11.49 | 0.00 |
TOPFLOOR_PLENUM | 13-JUN-14:20 | 0.00 | -8734.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8740.36 | 0.00 | -0.00 | 0.00 | -6.30 | 0.00 |
MIDFLOOR_PLENUM | 24-JUL-15:50 | 0.00 | -3752.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3810.59 | 0.00 | -0.00 | 0.00 | -58.37 | 0.00 |
FIRSTFLOOR_PLENUM | 24-JUL-06:13 | 0.00 | -4118.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4208.55 | 0.00 | -0.00 | 0.00 | -90.45 | 0.00 |
Total Facility | 13-JUN-15:30 | 0.00 | -15912.61 | 0.00 | -124563.81 | 0.00 | 0.00 | 17714.92 | 19671.42 | 42072.41 | 63864.93 | 0.00 | 461.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3308.72 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-07:12 | 0.00 | 0.00 | 16050.11 | 0.00 | 0.00 | 0.00 | 875.15 | 1645.36 | 8796.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -27367.41 |
CORE_MID | 02-JAN-06:01 | 0.00 | 0.00 | 18405.87 | 0.00 | 0.00 | 0.00 | 500.41 | 211.73 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22143.93 |
CORE_TOP | 02-JAN-05:01 | 0.00 | 0.00 | 29019.04 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -31672.83 |
PERIMETER_TOP_ZN_3 | 09-JAN-05:11 | 0.00 | 0.00 | 8097.98 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2004.24 | 0.00 | 0.00 | -6653.18 |
PERIMETER_TOP_ZN_2 | 09-JAN-05:11 | 0.00 | 0.00 | 8626.54 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1333.22 | 0.00 | 0.00 | -7647.47 |
PERIMETER_TOP_ZN_1 | 09-JAN-05:11 | 0.00 | 0.00 | 13114.05 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2026.68 | 0.00 | 0.00 | -11646.81 |
PERIMETER_TOP_ZN_4 | 09-JAN-05:11 | 0.00 | 0.00 | 8562.69 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1340.02 | 0.00 | 0.00 | -7576.82 |
PERIMETER_BOT_ZN_3 | 02-JAN-05:01 | 0.00 | 0.00 | 6435.07 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1638.89 | 0.00 | 0.00 | -5355.62 |
PERIMETER_BOT_ZN_2 | 02-JAN-05:01 | 0.00 | 0.00 | 6486.21 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1133.00 | 0.00 | 0.00 | -5707.36 |
PERIMETER_BOT_ZN_1 | 17-FEB-07:10 | 0.00 | 0.00 | 10627.62 | 0.00 | 0.00 | 0.00 | 193.30 | 346.86 | 637.88 | 0.00 | 0.00 | 0.00 | 7702.84 | 0.00 | -2776.23 | 0.00 | -16732.27 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JAN-05:01 | 0.00 | 0.00 | 6488.38 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1119.64 | 0.00 | 0.00 | -5722.88 |
PERIMETER_MID_ZN_3 | 02-JAN-05:01 | 0.00 | 0.00 | 7224.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1639.33 | 0.00 | 0.00 | -6144.12 |
PERIMETER_MID_ZN_2 | 02-JAN-05:01 | 0.00 | 0.00 | 6605.12 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1101.97 | 0.00 | 0.00 | -5857.30 |
PERIMETER_MID_ZN_1 | 02-JAN-05:01 | 0.00 | 0.00 | 9652.11 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1719.47 | 0.00 | 0.00 | -8492.07 |
PERIMETER_MID_ZN_4 | 02-JAN-05:01 | 0.00 | 0.00 | 6581.01 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1100.51 | 0.00 | 0.00 | -5834.65 |
TOPFLOOR_PLENUM | 04-DEC-06:16 | 11760.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -139.95 | -11620.10 |
MIDFLOOR_PLENUM | 02-JAN-07:04 | 7736.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7736.03 |
FIRSTFLOOR_PLENUM | 02-JAN-07:01 | 5444.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5444.83 |
Total Facility | 02-JAN-06:01 | 14219.26 | 0.00 | 147459.60 | 0.00 | 0.00 | 0.00 | 2512.29 | 1072.56 | 17291.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17745.55 | 0.00 | -1965.20 | -162844.47 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.4934 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7853 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.1397 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.2233 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.3351 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7227 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.7467 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0752 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.5699 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0765 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.6676 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0764 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8038 | 2.8038 | 0.6365 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0191 | 2.0191 | 0.6380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0377 | 2.0377 | 0.6378 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5561 | 0.5561 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7577 | 0.7577 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1398 | 1.1398 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8438 | 0.8438 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4405 | 0.4405 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6200 | 0.6200 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9287 | 0.9287 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7004 | 0.7004 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4953 | 0.4953 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7651 | 0.7651 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0684 | 1.0684 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7918 | 0.7918 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.4934 | 4.7853 | 5.4934 | 1.0752 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.1397 | 4.2233 | 5.1397 | 1.0765 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.3351 | 4.7227 | 5.3351 | 1.0764 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4019 | 1.4019 | 0.6365 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0095 | 1.0095 | 0.6380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0189 | 1.0189 | 0.6378 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2781 | 0.2781 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3789 | 0.3789 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5699 | 0.5699 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4219 | 0.4219 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2203 | 0.2203 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3100 | 0.3100 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4644 | 0.4644 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3502 | 0.3502 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2477 | 0.2477 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3826 | 0.3826 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5342 | 0.5342 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3959 | 0.3959 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.7467 | 1.0752 | 1.0752 | 1.0752 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.5699 | 1.0765 | 1.0765 | 1.0765 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.6676 | 1.0764 | 1.0764 | 1.0764 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 285.67 |
Number of hours cooling loads not met | 85.83 |
Number of hours not met | 371.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 94.90 | 158833.83 | 138.99 | 61361.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 40.15 | 42856.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 234.09 | 25003.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 51.76 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.69 | 840.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 67.41 | 21710.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 134.83 | 10175.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1205.57 |
Natural Gas | 0.00 | 273.83 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1479.40 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.98 |
Space Heating | 19.05 |
Space Cooling | 8.06 |
Fans (All) | 13.53 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 241.98 |
Subtotal | 241.98 |
Natural Gas [MJ/m2] | |
Space Heating | 27.90 |
Service Water Heating | 27.06 |
Miscellaneous (All) | 54.96 |
Subtotal | 54.96 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 15.82 |
Space Heating | 15.81 |
Space Cooling | 2.71 |
Fans (All) | 4.56 |
Service Water Heating | 9.11 |
Receptacle Equipment | 47.68 |
Miscellaneous | 4.30 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 878. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8744.50 | 15.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8739.50 | 20.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8737.17 | 22.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8743.83 | 16.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8747.50 | 12.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8744.50 | 15.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8741.00 | 19.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8740.17 | 19.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8737.17 | 22.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8725.00 | 35.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 35.00 | 0.00 | 0.00 | 0.00 |
Average | 8748.91 | 11.09 | 0.00 | 0.00 | 0.00 |
Sum | 157480.33 | 199.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8710.83 | 49.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8752.83 | 7.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8749.17 | 10.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8747.67 | 12.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8743.17 | 16.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8751.50 | 8.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8753.00 | 7.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8748.67 | 11.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8748.00 | 12.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8748.00 | 12.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8740.00 | 20.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8746.67 | 13.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8710.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 49.17 | 0.00 | 0.00 | 0.00 |
Average | 8749.97 | 10.03 | 0.00 | 0.00 | 0.00 |
Sum | 157499.50 | 180.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128284.17 | 19.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128301.67 | 2.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 19.83 | 0.00 | 0.00 | 0.00 |
Average | 34142.10 | 1.23 | 0.00 | 0.00 | 0.00 |
Sum | 614557.83 | 22.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.998499E+10 | 15265.25 | 20-JAN-08:17 | 2.00 | 1.57 | 0.191641E+10 | 2608.23 | 17-JAN-14:39 | 2.00 | 1.57 |
February | 0.102954E+11 | 16002.35 | 10-FEB-08:05 | 4.33 | 4.19 | 0.178218E+10 | 2606.66 | 21-FEB-10:09 | 8.17 | 7.45 |
March | 0.129213E+11 | 17667.44 | 23-MAR-07:05 | 7.00 | 4.55 | 0.213499E+10 | 2608.70 | 10-MAR-14:00 | 7.00 | 4.55 |
April | 0.174907E+11 | 25606.74 | 20-APR-05:03 | 1.17 | -0.2 | 0.191393E+10 | 2606.76 | 14-APR-13:00 | 1.17 | -0.2 |
May | 0.203288E+11 | 37992.97 | 01-MAY-06:02 | 6.17 | 4.70 | 0.207562E+10 | 2606.65 | 16-MAY-13:20 | 9.67 | 8.29 |
June | 0.225835E+11 | 38209.27 | 14-JUN-06:02 | 12.00 | 12.00 | 0.207041E+10 | 2606.76 | 08-JUN-13:09 | 12.00 | 12.00 |
July | 0.225324E+11 | 40959.65 | 24-JUL-05:12 | 13.00 | 13.00 | 0.192481E+10 | 2606.68 | 03-JUL-09:09 | 13.00 | 13.00 |
August | 0.246509E+11 | 38196.84 | 21-AUG-06:01 | 11.50 | 10.26 | 0.215945E+10 | 2606.68 | 08-AUG-13:09 | 11.50 | 10.26 |
September | 0.210073E+11 | 38087.26 | 13-SEP-06:01 | 11.17 | 10.64 | 0.191674E+10 | 2606.78 | 19-SEP-13:39 | 14.67 | 13.92 |
October | 0.158600E+11 | 31133.89 | 02-OCT-06:02 | 10.00 | 7.49 | 0.198617E+10 | 2606.74 | 17-OCT-09:09 | 12.33 | 11.88 |
November | 0.119806E+11 | 17780.61 | 10-NOV-08:03 | 6.33 | 6.25 | 0.195313E+10 | 2608.69 | 02-NOV-09:09 | 6.33 | 6.25 |
December | 0.962197E+10 | 14722.09 | 22-DEC-08:20 | 3.33 | 2.75 | 0.187586E+10 | 2606.65 | 20-DEC-10:09 | 3.33 | 2.75 |
Annual Sum or Average | 0.199258E+12 | 0.237097E+11 | ||||||||
Minimum of Months | 0.962197E+10 | 14722.09 | 1.17 | -0.2 | 0.178218E+10 | 2606.65 | 1.17 | -0.2 | ||
Maximum of Months | 0.246509E+11 | 40959.65 | 13.00 | 13.00 | 0.215945E+10 | 2608.70 | 14.67 | 13.92 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5234072.12 | 493.99 | 21-JAN-12:50 | 7.83 | 5.99 | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 5.99 |
February | 22386296.44 | 777.64 | 04-FEB-16:10 | 7.00 | 5.54 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 5.54 |
March | 75833420.02 | 1500.05 | 25-MAR-12:40 | 13.33 | 10.44 | 0.00 | 0.00 | 01-MAR-00:10 | 13.33 | 10.44 |
April | 0.176693E+10 | 7290.95 | 28-APR-14:50 | 20.08 | 13.54 | 0.00 | 0.00 | 01-APR-00:10 | 20.08 | 13.54 |
May | 0.208051E+10 | 7910.05 | 22-MAY-14:50 | 23.83 | 16.03 | 0.00 | 0.00 | 01-MAY-00:10 | 23.83 | 16.03 |
June | 0.321213E+10 | 8734.04 | 13-JUN-14:20 | 25.40 | 17.58 | 0.00 | 0.00 | 01-JUN-00:10 | 25.40 | 17.58 |
July | 0.381592E+10 | 8726.21 | 21-JUL-14:50 | 27.00 | 15.89 | 0.00 | 0.00 | 01-JUL-00:10 | 27.00 | 15.89 |
August | 0.367555E+10 | 7977.11 | 14-AUG-15:00 | 25.00 | 16.02 | 0.00 | 0.00 | 01-AUG-00:10 | 25.00 | 16.02 |
September | 0.224271E+10 | 6733.99 | 12-SEP-14:40 | 21.67 | 15.81 | 0.00 | 0.00 | 01-SEP-00:10 | 21.67 | 15.81 |
October | 0.433932E+09 | 3130.96 | 03-OCT-14:30 | 14.00 | 9.18 | 0.00 | 0.00 | 01-OCT-00:10 | 14.00 | 9.18 |
November | 7769688.53 | 527.83 | 11-NOV-14:00 | 9.00 | 7.01 | 0.00 | 0.00 | 01-NOV-00:10 | 9.00 | 7.01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 |
Annual Sum or Average | 0.173389E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.00 | 3.53 | 0.00 | 0.00 | 4.00 | 3.53 | ||
Maximum of Months | 0.381592E+10 | 8734.04 | 27.00 | 17.58 | 0.00 | 0.00 | 27.00 | 17.58 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16777950.92 | 1334.27 | 04-JAN-06:11 | 2.00 | 1.57 | 0.00 | 0.00 | 01-JAN-00:10 | 2.00 | 1.57 |
February | 18846303.65 | 1310.19 | 17-FEB-06:01 | -3.1 | -3.1 | 0.00 | 0.00 | 01-FEB-00:10 | -3.1 | -3.1 |
March | 57583895.15 | 1655.91 | 21-MAR-06:02 | 1.00 | 0.24 | 0.00 | 0.00 | 01-MAR-00:10 | 1.00 | 0.24 |
April | 0.517110E+09 | 2494.09 | 28-APR-16:00 | 20.00 | 12.32 | 0.00 | 0.00 | 01-APR-00:10 | 20.00 | 12.32 |
May | 0.757992E+09 | 2686.96 | 23-MAY-16:00 | 18.00 | 14.38 | 0.00 | 0.00 | 01-MAY-00:10 | 18.00 | 14.38 |
June | 0.148454E+10 | 3599.69 | 26-JUN-15:30 | 22.50 | 17.36 | 0.00 | 0.00 | 01-JUN-00:10 | 22.50 | 17.36 |
July | 0.186602E+10 | 3752.27 | 24-JUL-15:50 | 19.83 | 16.14 | 0.00 | 0.00 | 01-JUL-00:10 | 19.83 | 16.14 |
August | 0.188969E+10 | 3223.83 | 14-AUG-15:50 | 25.83 | 15.90 | 0.00 | 0.00 | 01-AUG-00:10 | 25.83 | 15.90 |
September | 0.109546E+10 | 2892.14 | 12-SEP-16:00 | 21.00 | 15.99 | 0.00 | 0.00 | 01-SEP-00:10 | 21.00 | 15.99 |
October | 0.179220E+09 | 1040.63 | 28-OCT-06:03 | 6.50 | 6.06 | 0.00 | 0.00 | 01-OCT-00:10 | 6.50 | 6.06 |
November | 28508641.76 | 1229.31 | 17-NOV-07:02 | 1.17 | 0.28 | 0.00 | 0.00 | 01-NOV-00:10 | 1.17 | 0.28 |
December | 3368229.76 | 1421.06 | 30-DEC-06:01 | -1.0 | -2.5 | 0.00 | 0.00 | 01-DEC-00:10 | -1.0 | -2.5 |
Annual Sum or Average | 0.791512E+10 | 0.00 | ||||||||
Minimum of Months | 3368229.76 | 1040.63 | -3.1 | -3.1 | 0.00 | 0.00 | -3.1 | -3.1 | ||
Maximum of Months | 0.188969E+10 | 3752.27 | 25.83 | 17.36 | 0.00 | 0.00 | 25.83 | 17.36 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 83618917.87 | 2105.25 | 20-JAN-07:02 | 2.00 | 1.57 | 0.00 | 0.00 | 01-JAN-00:10 | 2.00 | 1.57 |
February | 91728295.05 | 2402.61 | 16-FEB-06:11 | 3.00 | 2.70 | 0.00 | 0.00 | 01-FEB-00:10 | 3.00 | 2.70 |
March | 0.177696E+09 | 2321.69 | 22-MAR-06:02 | 3.17 | 2.71 | 0.00 | 0.00 | 01-MAR-00:10 | 3.17 | 2.71 |
April | 0.102067E+10 | 2927.75 | 28-APR-16:00 | 20.00 | 12.32 | 0.00 | 0.00 | 01-APR-00:10 | 20.00 | 12.32 |
May | 0.139013E+10 | 3605.88 | 01-MAY-06:07 | 6.17 | 4.70 | 0.00 | 0.00 | 01-MAY-00:10 | 6.17 | 4.70 |
June | 0.217892E+10 | 3893.47 | 13-JUN-16:00 | 26.50 | 17.70 | 0.00 | 0.00 | 01-JUN-00:10 | 26.50 | 17.70 |
July | 0.254110E+10 | 4118.07 | 24-JUL-06:13 | 13.33 | 13.15 | 0.00 | 0.00 | 01-JUL-00:10 | 13.33 | 13.15 |
August | 0.269779E+10 | 3789.20 | 14-AUG-16:00 | 26.00 | 15.86 | 0.00 | 0.00 | 01-AUG-00:10 | 26.00 | 15.86 |
September | 0.191707E+10 | 3522.59 | 13-SEP-16:00 | 23.00 | 16.22 | 0.00 | 0.00 | 01-SEP-00:10 | 23.00 | 16.22 |
October | 0.511262E+09 | 2166.92 | 04-OCT-06:08 | 3.17 | 3.17 | 0.00 | 0.00 | 01-OCT-00:10 | 3.17 | 3.17 |
November | 0.108031E+09 | 2331.23 | 17-NOV-07:02 | 1.17 | 0.28 | 0.00 | 0.00 | 01-NOV-00:10 | 1.17 | 0.28 |
December | 41326954.25 | 2232.58 | 08-DEC-06:11 | 1.67 | 1.24 | 0.00 | 0.00 | 01-DEC-00:10 | 1.67 | 1.24 |
Annual Sum or Average | 0.127594E+11 | 0.00 | ||||||||
Minimum of Months | 41326954.25 | 2105.25 | 1.17 | 0.28 | 0.00 | 0.00 | 1.17 | 0.28 | ||
Maximum of Months | 0.269779E+10 | 4118.07 | 26.50 | 17.70 | 0.00 | 0.00 | 26.50 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.634619E+10 | 6407.23 | 20-JAN-17:00 | 5.00 | 4.51 | 0.167459E+10 | 2545.33 | 20-JAN-14:00 | 5.00 | 4.51 |
February | 0.645099E+10 | 6383.94 | 24-FEB-17:00 | 6.00 | 4.60 | 0.156938E+10 | 2509.77 | 10-FEB-14:00 | 6.00 | 4.60 |
March | 0.794950E+10 | 6707.83 | 31-MAR-16:00 | 9.00 | 4.96 | 0.192847E+10 | 2565.10 | 31-MAR-13:00 | 9.00 | 4.96 |
April | 0.104895E+11 | 13714.90 | 28-APR-16:00 | 20.00 | 12.32 | 0.188328E+10 | 2608.09 | 07-APR-09:50 | 20.00 | 12.32 |
May | 0.125711E+11 | 21569.12 | 01-MAY-06:02 | 6.17 | 4.70 | 0.205570E+10 | 2606.64 | 12-MAY-09:20 | 11.33 | 9.72 |
June | 0.145185E+11 | 21194.91 | 26-JUN-06:03 | 16.67 | 13.34 | 0.206156E+10 | 2606.68 | 08-JUN-13:09 | 16.67 | 13.34 |
July | 0.149561E+11 | 29733.87 | 24-JUL-05:12 | 13.00 | 13.00 | 0.191657E+10 | 2606.65 | 03-JUL-09:20 | 13.00 | 13.00 |
August | 0.159785E+11 | 22591.92 | 21-AUG-06:01 | 11.50 | 10.26 | 0.215285E+10 | 2606.67 | 08-AUG-13:09 | 11.50 | 10.26 |
September | 0.131301E+11 | 14635.68 | 13-SEP-16:00 | 23.00 | 16.22 | 0.190387E+10 | 2606.72 | 19-SEP-13:50 | 14.33 | 13.96 |
October | 0.893223E+10 | 11881.73 | 03-OCT-16:00 | 14.00 | 8.96 | 0.189349E+10 | 2606.66 | 12-OCT-09:09 | 9.00 | 9.00 |
November | 0.704726E+10 | 6926.44 | 10-NOV-16:30 | 9.00 | 7.52 | 0.174577E+10 | 2600.83 | 10-NOV-14:00 | 9.00 | 7.52 |
December | 0.605171E+10 | 5950.77 | 21-DEC-17:00 | 6.00 | 5.49 | 0.158555E+10 | 2424.45 | 21-DEC-14:00 | 6.00 | 5.49 |
Annual Sum or Average | 0.124422E+12 | 0.223711E+11 | ||||||||
Minimum of Months | 0.605171E+10 | 5950.77 | 5.00 | 4.51 | 0.156938E+10 | 2424.45 | 5.00 | 4.51 | ||
Maximum of Months | 0.159785E+11 | 29733.87 | 23.00 | 16.22 | 0.215285E+10 | 2608.09 | 20.00 | 13.96 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.457346E+10 | 6082.19 | 20-JAN-17:00 | 5.00 | 4.51 | 0.156463E+10 | 2437.20 | 20-JAN-14:00 | 5.00 | 4.51 |
February | 0.493551E+10 | 6072.73 | 24-FEB-17:00 | 6.00 | 4.60 | 0.145635E+10 | 2406.28 | 24-FEB-16:00 | 6.00 | 4.60 |
March | 0.663378E+10 | 6321.56 | 31-MAR-16:00 | 9.00 | 4.96 | 0.179596E+10 | 2482.31 | 31-MAR-15:00 | 9.00 | 4.96 |
April | 0.954195E+10 | 14795.85 | 28-APR-16:00 | 20.00 | 12.32 | 0.182425E+10 | 2606.69 | 14-APR-13:00 | 20.00 | 12.32 |
May | 0.114366E+11 | 15684.40 | 23-MAY-15:40 | 18.00 | 14.38 | 0.201642E+10 | 2608.12 | 02-MAY-09:39 | 18.00 | 14.38 |
June | 0.137920E+11 | 17384.28 | 26-JUN-15:40 | 22.33 | 17.38 | 0.204702E+10 | 2606.67 | 09-JUN-13:00 | 22.33 | 17.38 |
July | 0.144137E+11 | 18122.37 | 24-JUL-06:02 | 13.17 | 13.07 | 0.190516E+10 | 2606.65 | 21-JUL-13:20 | 13.17 | 13.07 |
August | 0.149767E+11 | 16141.13 | 14-AUG-16:00 | 26.00 | 15.86 | 0.213951E+10 | 2606.67 | 15-AUG-09:09 | 16.00 | 13.59 |
September | 0.116337E+11 | 15253.87 | 13-SEP-16:00 | 23.00 | 16.22 | 0.187561E+10 | 2606.72 | 19-SEP-13:50 | 14.33 | 13.96 |
October | 0.756347E+10 | 10886.73 | 03-OCT-16:00 | 14.00 | 8.96 | 0.177166E+10 | 2606.61 | 11-OCT-13:20 | 16.00 | 10.47 |
November | 0.546915E+10 | 6332.10 | 10-NOV-16:50 | 7.67 | 6.84 | 0.160699E+10 | 2516.76 | 10-NOV-14:00 | 7.67 | 6.84 |
December | 0.370933E+10 | 5564.16 | 21-DEC-15:40 | 7.33 | 6.65 | 0.147815E+10 | 2305.68 | 21-DEC-14:00 | 7.33 | 6.65 |
Annual Sum or Average | 0.108679E+12 | 0.214817E+11 | ||||||||
Minimum of Months | 0.370933E+10 | 5564.16 | 5.00 | 4.51 | 0.145635E+10 | 2305.68 | 5.00 | 4.51 | ||
Maximum of Months | 0.149767E+11 | 18122.37 | 26.00 | 17.38 | 0.213951E+10 | 2608.12 | 22.33 | 17.38 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.257611E+09 | 1054.86 | 19-JAN-15:50 | 8.17 | 7.46 | 0.309280E+09 | 451.00 | 19-JAN-14:00 | 8.17 | 7.46 |
February | 0.361303E+09 | 1033.51 | 24-FEB-16:30 | 6.00 | 4.60 | 0.282182E+09 | 444.05 | 24-FEB-14:20 | 6.00 | 4.60 |
March | 0.739364E+09 | 1201.82 | 30-MAR-15:30 | 12.00 | 6.19 | 0.349581E+09 | 494.40 | 30-MAR-13:00 | 12.00 | 6.19 |
April | 0.175750E+10 | 3757.76 | 28-APR-15:30 | 20.05 | 13.01 | 0.364125E+09 | 549.50 | 14-APR-13:00 | 20.05 | 13.01 |
May | 0.226662E+10 | 4301.87 | 22-MAY-15:20 | 23.67 | 15.81 | 0.407988E+09 | 549.50 | 22-MAY-13:00 | 23.67 | 15.81 |
June | 0.320971E+10 | 5348.87 | 13-JUN-15:20 | 26.17 | 17.79 | 0.426320E+09 | 549.51 | 09-JUN-13:00 | 26.17 | 17.79 |
July | 0.349536E+10 | 5206.63 | 10-JUL-15:00 | 23.00 | 16.69 | 0.398376E+09 | 549.50 | 21-JUL-13:20 | 26.33 | 16.36 |
August | 0.335857E+10 | 4675.53 | 14-AUG-16:00 | 26.00 | 15.86 | 0.444451E+09 | 549.50 | 15-AUG-09:20 | 16.00 | 13.59 |
September | 0.223822E+10 | 3965.51 | 13-SEP-15:30 | 23.00 | 16.22 | 0.380351E+09 | 549.51 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.106641E+10 | 1768.38 | 06-OCT-15:50 | 17.00 | 9.21 | 0.341722E+09 | 549.44 | 06-OCT-13:00 | 17.00 | 9.21 |
November | 0.427538E+09 | 1139.71 | 10-NOV-15:30 | 11.50 | 8.42 | 0.310139E+09 | 478.44 | 10-NOV-14:00 | 11.50 | 8.42 |
December | 0.107275E+09 | 913.36 | 21-DEC-16:00 | 7.00 | 6.47 | 0.294845E+09 | 416.34 | 21-DEC-14:00 | 7.00 | 6.47 |
Annual Sum or Average | 0.192855E+11 | 0.430936E+10 | ||||||||
Minimum of Months | 0.107275E+09 | 913.36 | 6.00 | 4.60 | 0.282182E+09 | 416.34 | 6.00 | 4.60 | ||
Maximum of Months | 0.349536E+10 | 5348.87 | 26.17 | 17.79 | 0.444451E+09 | 549.51 | 26.33 | 17.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.254329E+09 | 789.73 | 20-JAN-10:50 | 5.67 | 5.18 | 0.199003E+09 | 324.96 | 20-JAN-10:50 | 5.67 | 5.18 |
February | 0.339512E+09 | 846.77 | 24-FEB-10:40 | 5.67 | 4.28 | 0.186024E+09 | 342.72 | 24-FEB-10:50 | 5.83 | 4.44 |
March | 0.566425E+09 | 832.54 | 25-MAR-10:00 | 11.00 | 7.91 | 0.228350E+09 | 332.65 | 31-MAR-09:00 | 9.00 | 5.32 |
April | 0.236896E+10 | 8447.25 | 30-APR-09:02 | 18.33 | 12.10 | 0.246382E+09 | 347.89 | 14-APR-13:00 | 18.33 | 12.10 |
May | 0.269921E+10 | 10268.15 | 21-MAY-09:23 | 13.00 | 9.81 | 0.268972E+09 | 348.33 | 02-MAY-09:39 | 13.00 | 9.81 |
June | 0.346503E+10 | 13153.23 | 25-JUN-09:52 | 18.00 | 12.90 | 0.273312E+09 | 348.28 | 13-JUN-09:50 | 18.00 | 12.90 |
July | 0.375479E+10 | 13358.03 | 16-JUL-08:52 | 16.00 | 13.59 | 0.255211E+09 | 348.21 | 10-JUL-09:50 | 16.00 | 13.59 |
August | 0.392523E+10 | 10656.82 | 20-AUG-10:02 | 16.17 | 13.12 | 0.285412E+09 | 347.89 | 14-AUG-09:39 | 16.17 | 13.12 |
September | 0.277255E+10 | 6576.03 | 12-SEP-09:10 | 17.83 | 14.41 | 0.250591E+09 | 347.89 | 06-SEP-09:09 | 17.83 | 14.41 |
October | 0.979078E+09 | 3314.20 | 04-OCT-10:00 | 13.00 | 9.81 | 0.227705E+09 | 347.88 | 03-OCT-09:20 | 13.00 | 9.81 |
November | 0.346980E+09 | 773.70 | 03-NOV-10:00 | 7.00 | 5.17 | 0.200401E+09 | 319.47 | 03-NOV-09:00 | 7.00 | 5.17 |
December | 0.126603E+09 | 662.41 | 06-DEC-10:40 | 6.00 | 4.49 | 0.187943E+09 | 286.96 | 06-DEC-10:39 | 6.00 | 4.49 |
Annual Sum or Average | 0.215987E+11 | 0.280930E+10 | ||||||||
Minimum of Months | 0.126603E+09 | 662.41 | 5.67 | 4.28 | 0.186024E+09 | 286.96 | 5.67 | 4.44 | ||
Maximum of Months | 0.392523E+10 | 13358.03 | 18.33 | 14.41 | 0.285412E+09 | 348.33 | 18.33 | 14.41 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.955199E+09 | 6177.65 | 20-JAN-12:00 | 8.00 | 6.08 | 0.338147E+09 | 549.49 | 17-JAN-14:50 | 8.00 | 6.08 |
February | 0.124772E+10 | 7651.65 | 17-FEB-13:40 | 6.00 | 3.25 | 0.316432E+09 | 549.50 | 24-FEB-14:39 | 6.00 | 4.60 |
March | 0.110145E+10 | 3820.38 | 28-MAR-12:05 | 11.67 | 7.18 | 0.372993E+09 | 549.91 | 20-MAR-13:20 | 11.67 | 7.18 |
April | 0.429217E+10 | 19617.16 | 30-APR-13:02 | 22.17 | 13.02 | 0.378902E+09 | 549.54 | 28-APR-13:09 | 22.17 | 13.02 |
May | 0.394972E+10 | 10170.08 | 22-MAY-13:10 | 22.17 | 14.96 | 0.414404E+09 | 549.80 | 01-MAY-09:39 | 22.17 | 14.96 |
June | 0.466812E+10 | 16599.98 | 25-JUN-15:52 | 25.00 | 14.76 | 0.425865E+09 | 549.53 | 08-JUN-13:09 | 25.00 | 14.76 |
July | 0.542062E+10 | 15417.24 | 30-JUL-13:13 | 17.00 | 12.42 | 0.398882E+09 | 549.52 | 21-JUL-13:09 | 17.00 | 12.42 |
August | 0.653451E+10 | 20009.47 | 06-AUG-13:32 | 17.67 | 13.76 | 0.447270E+09 | 549.51 | 21-AUG-13:39 | 21.00 | 14.82 |
September | 0.596872E+10 | 20245.06 | 24-SEP-13:42 | 20.67 | 15.34 | 0.391292E+09 | 550.01 | 25-SEP-13:00 | 21.00 | 13.56 |
October | 0.286057E+10 | 11704.18 | 01-OCT-13:33 | 12.67 | 9.47 | 0.366650E+09 | 549.51 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.104457E+10 | 6616.97 | 03-NOV-12:40 | 9.00 | 5.48 | 0.336296E+09 | 549.49 | 03-NOV-13:00 | 9.00 | 5.72 |
December | 0.523710E+09 | 4946.32 | 18-DEC-13:25 | 8.00 | 5.46 | 0.314421E+09 | 549.49 | 26-DEC-14:00 | 6.00 | 3.37 |
Annual Sum or Average | 0.385671E+11 | 0.450156E+10 | ||||||||
Minimum of Months | 0.523710E+09 | 3820.38 | 6.00 | 3.25 | 0.314421E+09 | 549.49 | 6.00 | 3.37 | ||
Maximum of Months | 0.653451E+10 | 20245.06 | 25.00 | 15.34 | 0.447270E+09 | 550.01 | 25.00 | 14.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243308E+09 | 1416.43 | 19-JAN-15:50 | 8.17 | 7.46 | 0.200428E+09 | 342.21 | 19-JAN-14:00 | 8.17 | 7.46 |
February | 0.386122E+09 | 2537.19 | 27-FEB-16:30 | 8.00 | 6.72 | 0.187913E+09 | 347.80 | 09-FEB-14:00 | 8.00 | 6.72 |
March | 0.583042E+09 | 2914.57 | 23-MAR-16:50 | 10.00 | 6.65 | 0.226295E+09 | 347.81 | 10-MAR-14:00 | 10.00 | 6.65 |
April | 0.218023E+10 | 14423.64 | 30-APR-16:22 | 24.00 | 12.86 | 0.232692E+09 | 347.85 | 14-APR-13:00 | 24.00 | 12.86 |
May | 0.267293E+10 | 13112.75 | 21-MAY-16:52 | 20.00 | 12.79 | 0.259625E+09 | 347.85 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.361373E+10 | 15983.30 | 25-JUN-17:11 | 21.33 | 16.05 | 0.269753E+09 | 347.86 | 09-JUN-13:00 | 21.33 | 16.05 |
July | 0.396582E+10 | 16131.75 | 09-JUL-16:51 | 21.00 | 15.03 | 0.252429E+09 | 347.86 | 21-JUL-13:20 | 26.33 | 16.36 |
August | 0.366530E+10 | 15355.64 | 13-AUG-16:32 | 19.67 | 15.02 | 0.282291E+09 | 347.86 | 15-AUG-09:20 | 16.00 | 13.59 |
September | 0.248075E+10 | 11968.24 | 24-SEP-16:23 | 21.50 | 15.22 | 0.242599E+09 | 347.86 | 19-SEP-13:50 | 21.50 | 15.22 |
October | 0.100220E+10 | 5188.03 | 03-OCT-15:40 | 14.00 | 8.96 | 0.220326E+09 | 347.85 | 02-OCT-13:20 | 14.00 | 8.96 |
November | 0.346849E+09 | 1585.80 | 10-NOV-15:40 | 11.33 | 8.41 | 0.200694E+09 | 347.83 | 15-NOV-14:00 | 12.00 | 8.90 |
December | 0.109208E+09 | 753.41 | 21-DEC-14:50 | 8.00 | 6.98 | 0.187943E+09 | 312.67 | 21-DEC-14:00 | 8.00 | 6.98 |
Annual Sum or Average | 0.212495E+11 | 0.276299E+10 | ||||||||
Minimum of Months | 0.109208E+09 | 753.41 | 8.00 | 6.65 | 0.187913E+09 | 312.67 | 8.00 | 6.65 | ||
Maximum of Months | 0.396582E+10 | 16131.75 | 24.00 | 16.05 | 0.282291E+09 | 347.86 | 26.33 | 16.36 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.369021E+09 | 1017.69 | 25-JAN-15:10 | 10.67 | 9.25 | 0.311246E+09 | 443.82 | 25-JAN-14:00 | 10.67 | 9.25 |
February | 0.475603E+09 | 996.80 | 10-FEB-15:50 | 7.00 | 5.15 | 0.283522E+09 | 437.77 | 10-FEB-14:00 | 7.00 | 5.15 |
March | 0.865918E+09 | 1127.75 | 30-MAR-14:00 | 13.00 | 7.37 | 0.349344E+09 | 476.60 | 30-MAR-13:00 | 13.00 | 7.37 |
April | 0.158056E+10 | 2206.37 | 28-APR-15:40 | 20.03 | 12.78 | 0.359933E+09 | 549.49 | 21-APR-13:20 | 20.03 | 12.78 |
May | 0.191732E+10 | 2581.27 | 23-MAY-14:00 | 19.00 | 14.77 | 0.409410E+09 | 549.50 | 24-MAY-09:20 | 13.00 | 10.81 |
June | 0.258755E+10 | 3833.38 | 13-JUN-16:00 | 26.50 | 17.70 | 0.428870E+09 | 549.50 | 20-JUN-09:20 | 16.67 | 13.34 |
July | 0.290095E+10 | 3737.97 | 21-JUL-16:00 | 28.00 | 16.11 | 0.400593E+09 | 549.50 | 03-JUL-09:20 | 28.00 | 16.11 |
August | 0.281378E+10 | 3285.64 | 14-AUG-16:00 | 26.00 | 15.86 | 0.447952E+09 | 549.50 | 23-AUG-09:20 | 16.33 | 12.16 |
September | 0.207045E+10 | 2944.82 | 13-SEP-15:30 | 23.00 | 16.22 | 0.388441E+09 | 549.50 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.141136E+10 | 1370.82 | 03-OCT-12:07 | 13.00 | 9.72 | 0.357657E+09 | 540.13 | 06-OCT-13:00 | 16.00 | 9.11 |
November | 0.825450E+09 | 1150.12 | 10-NOV-15:10 | 11.83 | 8.42 | 0.321017E+09 | 482.28 | 10-NOV-14:00 | 11.83 | 8.42 |
December | 0.288025E+09 | 951.93 | 22-DEC-13:50 | 7.00 | 5.54 | 0.297096E+09 | 426.02 | 22-DEC-14:09 | 7.00 | 5.54 |
Annual Sum or Average | 0.181060E+11 | 0.435508E+10 | ||||||||
Minimum of Months | 0.288025E+09 | 951.93 | 7.00 | 5.15 | 0.283522E+09 | 426.02 | 7.00 | 5.15 | ||
Maximum of Months | 0.290095E+10 | 3833.38 | 28.00 | 17.70 | 0.447952E+09 | 549.50 | 28.00 | 16.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.333499E+09 | 782.97 | 20-JAN-10:30 | 5.00 | 4.55 | 0.200981E+09 | 322.83 | 20-JAN-10:39 | 5.33 | 4.86 |
February | 0.420773E+09 | 824.99 | 24-FEB-10:40 | 5.67 | 4.28 | 0.187626E+09 | 335.76 | 24-FEB-10:50 | 5.83 | 4.44 |
March | 0.638352E+09 | 788.79 | 31-MAR-09:50 | 8.33 | 5.01 | 0.228025E+09 | 324.70 | 31-MAR-09:00 | 9.00 | 5.32 |
April | 0.204058E+10 | 10563.75 | 30-APR-09:32 | 19.33 | 12.50 | 0.248576E+09 | 347.89 | 14-APR-13:00 | 19.33 | 12.50 |
May | 0.239155E+10 | 8097.04 | 22-MAY-06:02 | 13.67 | 12.04 | 0.271846E+09 | 347.88 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.303735E+10 | 9999.50 | 25-JUN-09:52 | 18.00 | 12.90 | 0.274613E+09 | 347.89 | 20-JUN-09:09 | 18.00 | 12.90 |
July | 0.337929E+10 | 10628.53 | 23-JUL-08:51 | 20.00 | 15.65 | 0.256122E+09 | 347.88 | 03-JUL-09:09 | 20.00 | 15.65 |
August | 0.362720E+10 | 6576.99 | 13-AUG-09:53 | 16.00 | 13.60 | 0.287053E+09 | 347.88 | 23-AUG-09:09 | 16.17 | 12.09 |
September | 0.275318E+10 | 5330.48 | 12-SEP-09:20 | 17.67 | 14.44 | 0.253797E+09 | 347.89 | 06-SEP-09:09 | 17.67 | 14.44 |
October | 0.120534E+10 | 3026.57 | 04-OCT-10:00 | 13.00 | 9.81 | 0.238132E+09 | 347.88 | 03-OCT-09:20 | 13.00 | 9.81 |
November | 0.617231E+09 | 807.52 | 03-NOV-09:50 | 6.83 | 5.00 | 0.209067E+09 | 330.35 | 03-NOV-09:00 | 7.00 | 5.17 |
December | 0.266427E+09 | 699.40 | 08-DEC-10:40 | 5.33 | 3.83 | 0.190551E+09 | 298.01 | 08-DEC-10:50 | 5.67 | 3.99 |
Annual Sum or Average | 0.207108E+11 | 0.284639E+10 | ||||||||
Minimum of Months | 0.266427E+09 | 699.40 | 5.00 | 3.83 | 0.187626E+09 | 298.01 | 5.33 | 3.99 | ||
Maximum of Months | 0.362720E+10 | 10628.53 | 20.00 | 15.65 | 0.287053E+09 | 347.89 | 23.00 | 15.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.480080E+09 | 3353.15 | 21-JAN-11:30 | 6.00 | 5.05 | 0.315498E+09 | 549.28 | 17-JAN-14:09 | 6.00 | 5.05 |
February | 0.638766E+09 | 3753.72 | 04-FEB-14:00 | 9.00 | 6.13 | 0.294379E+09 | 549.50 | 13-FEB-14:00 | 6.00 | 3.74 |
March | 0.571244E+09 | 1333.95 | 25-MAR-11:50 | 11.92 | 8.82 | 0.339027E+09 | 501.39 | 10-MAR-14:00 | 11.92 | 8.82 |
April | 0.238194E+10 | 16322.88 | 30-APR-12:12 | 22.00 | 13.70 | 0.360739E+09 | 549.52 | 14-APR-13:50 | 22.00 | 13.70 |
May | 0.222407E+10 | 7252.32 | 22-MAY-13:40 | 22.67 | 15.44 | 0.392598E+09 | 549.51 | 09-MAY-13:09 | 22.67 | 15.44 |
June | 0.282003E+10 | 7527.63 | 13-JUN-13:40 | 24.73 | 17.32 | 0.410931E+09 | 549.52 | 08-JUN-13:09 | 24.73 | 17.32 |
July | 0.365021E+10 | 9758.65 | 23-JUL-11:32 | 21.00 | 15.99 | 0.393031E+09 | 549.50 | 31-JUL-09:20 | 14.33 | 10.86 |
August | 0.475127E+10 | 15754.81 | 06-AUG-13:32 | 17.67 | 13.76 | 0.444354E+09 | 549.51 | 21-AUG-13:39 | 21.00 | 14.82 |
September | 0.460329E+10 | 15016.43 | 24-SEP-14:53 | 22.00 | 15.41 | 0.391773E+09 | 549.72 | 25-SEP-13:50 | 21.17 | 13.49 |
October | 0.217591E+10 | 10218.07 | 03-OCT-12:07 | 13.00 | 9.72 | 0.359506E+09 | 549.51 | 11-OCT-13:20 | 16.00 | 10.47 |
November | 0.786499E+09 | 2995.66 | 11-NOV-13:25 | 9.00 | 7.22 | 0.322034E+09 | 549.51 | 27-NOV-14:09 | 7.83 | 5.50 |
December | 0.237895E+09 | 2034.39 | 18-DEC-13:50 | 8.00 | 5.60 | 0.296733E+09 | 549.51 | 18-DEC-14:09 | 8.00 | 5.67 |
Annual Sum or Average | 0.253212E+11 | 0.432060E+10 | ||||||||
Minimum of Months | 0.237895E+09 | 1333.95 | 6.00 | 5.05 | 0.294379E+09 | 501.39 | 6.00 | 3.74 | ||
Maximum of Months | 0.475127E+10 | 16322.88 | 24.73 | 17.32 | 0.444354E+09 | 549.72 | 24.73 | 17.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.317970E+09 | 860.86 | 19-JAN-15:50 | 8.17 | 7.46 | 0.201389E+09 | 337.53 | 19-JAN-15:00 | 8.00 | 7.45 |
February | 0.450378E+09 | 1641.77 | 27-FEB-16:30 | 8.00 | 6.72 | 0.188521E+09 | 338.68 | 16-FEB-16:00 | 8.00 | 6.72 |
March | 0.641422E+09 | 1874.77 | 23-MAR-17:00 | 10.00 | 6.65 | 0.225874E+09 | 338.67 | 31-MAR-15:00 | 9.00 | 4.96 |
April | 0.173880E+10 | 12753.38 | 30-APR-17:31 | 24.00 | 12.95 | 0.237083E+09 | 347.85 | 14-APR-13:00 | 24.00 | 12.95 |
May | 0.226589E+10 | 8079.93 | 21-MAY-17:32 | 20.00 | 13.07 | 0.266080E+09 | 347.85 | 12-MAY-09:20 | 20.00 | 13.07 |
June | 0.310721E+10 | 12488.43 | 25-JUN-17:11 | 21.33 | 16.05 | 0.273872E+09 | 347.86 | 20-JUN-09:20 | 21.33 | 16.05 |
July | 0.351454E+10 | 12582.98 | 09-JUL-17:31 | 21.00 | 15.03 | 0.255160E+09 | 347.86 | 03-JUL-09:20 | 21.00 | 15.03 |
August | 0.327152E+10 | 12224.74 | 13-AUG-17:12 | 18.67 | 14.49 | 0.286346E+09 | 347.86 | 15-AUG-09:20 | 16.00 | 13.59 |
September | 0.230304E+10 | 6067.05 | 12-SEP-16:00 | 21.00 | 15.99 | 0.250744E+09 | 347.86 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.116162E+10 | 4430.59 | 03-OCT-16:00 | 14.00 | 8.96 | 0.233222E+09 | 347.85 | 02-OCT-13:20 | 14.00 | 8.96 |
November | 0.598838E+09 | 1253.58 | 10-NOV-15:40 | 11.33 | 8.41 | 0.208132E+09 | 347.44 | 15-NOV-14:00 | 12.00 | 8.90 |
December | 0.199149E+09 | 727.96 | 21-DEC-14:50 | 8.00 | 6.98 | 0.189387E+09 | 306.27 | 21-DEC-14:00 | 8.00 | 6.98 |
Annual Sum or Average | 0.195704E+11 | 0.281581E+10 | ||||||||
Minimum of Months | 0.199149E+09 | 727.96 | 8.00 | 6.65 | 0.188521E+09 | 306.27 | 8.00 | 4.96 | ||
Maximum of Months | 0.351454E+10 | 12753.38 | 24.00 | 16.05 | 0.286346E+09 | 347.86 | 24.00 | 16.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.498021E+09 | 1110.73 | 19-JAN-15:40 | 8.33 | 7.46 | 0.315798E+09 | 469.27 | 19-JAN-14:00 | 8.33 | 7.46 |
February | 0.632734E+09 | 1100.69 | 24-FEB-16:20 | 6.00 | 4.60 | 0.290875E+09 | 464.33 | 24-FEB-14:09 | 6.00 | 4.60 |
March | 0.113918E+10 | 1250.70 | 30-MAR-14:00 | 13.00 | 7.37 | 0.364153E+09 | 513.18 | 30-MAR-13:00 | 13.00 | 7.37 |
April | 0.196661E+10 | 3543.64 | 28-APR-15:30 | 20.05 | 13.01 | 0.378619E+09 | 549.50 | 14-APR-13:00 | 20.05 | 13.01 |
May | 0.246416E+10 | 3911.00 | 22-MAY-15:20 | 23.67 | 15.81 | 0.422216E+09 | 549.50 | 12-MAY-09:20 | 23.67 | 15.81 |
June | 0.337593E+10 | 6494.81 | 26-JUN-06:03 | 16.67 | 13.34 | 0.432044E+09 | 549.51 | 08-JUN-13:09 | 16.67 | 13.34 |
July | 0.361956E+10 | 4782.77 | 10-JUL-15:00 | 23.00 | 16.69 | 0.402136E+09 | 549.50 | 03-JUL-09:20 | 23.00 | 16.69 |
August | 0.355088E+10 | 4378.76 | 14-AUG-16:00 | 26.00 | 15.86 | 0.450370E+09 | 549.50 | 15-AUG-09:20 | 16.00 | 13.59 |
September | 0.248535E+10 | 3841.66 | 13-SEP-15:30 | 23.00 | 16.22 | 0.392042E+09 | 549.51 | 19-SEP-13:50 | 14.33 | 13.96 |
October | 0.146899E+10 | 2060.75 | 06-OCT-15:40 | 17.00 | 9.21 | 0.363063E+09 | 549.49 | 02-OCT-13:20 | 17.00 | 9.21 |
November | 0.840390E+09 | 1198.36 | 10-NOV-15:20 | 11.67 | 8.42 | 0.322735E+09 | 496.03 | 10-NOV-14:00 | 11.67 | 8.42 |
December | 0.325985E+09 | 991.12 | 22-DEC-13:50 | 7.00 | 5.54 | 0.297959E+09 | 437.67 | 22-DEC-14:09 | 7.00 | 5.54 |
Annual Sum or Average | 0.223678E+11 | 0.443201E+10 | ||||||||
Minimum of Months | 0.325985E+09 | 991.12 | 6.00 | 4.60 | 0.290875E+09 | 437.67 | 6.00 | 4.60 | ||
Maximum of Months | 0.361956E+10 | 6494.81 | 26.00 | 16.69 | 0.450370E+09 | 549.51 | 23.67 | 16.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.312994E+09 | 2155.72 | 20-JAN-11:05 | 6.33 | 5.61 | 0.150974E+09 | 356.46 | 20-JAN-11:09 | 6.33 | 5.61 |
February | 0.390895E+09 | 2399.46 | 24-FEB-11:05 | 6.00 | 4.60 | 0.142946E+09 | 356.46 | 17-FEB-11:09 | 6.00 | 4.60 |
March | 0.627810E+09 | 2410.09 | 25-MAR-10:05 | 11.08 | 8.00 | 0.176281E+09 | 356.45 | 31-MAR-10:09 | 8.83 | 5.31 |
April | 0.248503E+10 | 13568.71 | 30-APR-09:32 | 19.33 | 12.50 | 0.184352E+09 | 356.47 | 14-APR-14:09 | 19.33 | 12.50 |
May | 0.277720E+10 | 12265.09 | 21-MAY-08:53 | 13.00 | 9.30 | 0.201435E+09 | 356.46 | 22-MAY-14:09 | 23.17 | 15.81 |
June | 0.341796E+10 | 11793.11 | 11-JUN-09:23 | 16.00 | 13.04 | 0.203339E+09 | 356.46 | 09-JUN-14:09 | 16.00 | 13.04 |
July | 0.368162E+10 | 13163.57 | 23-JUL-08:42 | 19.83 | 15.59 | 0.190261E+09 | 356.46 | 05-JUL-10:09 | 19.83 | 15.59 |
August | 0.389065E+10 | 11019.45 | 20-AUG-10:13 | 16.33 | 13.20 | 0.212307E+09 | 356.46 | 01-AUG-10:09 | 16.33 | 13.20 |
September | 0.287686E+10 | 7556.32 | 24-SEP-09:13 | 18.00 | 14.39 | 0.187427E+09 | 356.47 | 07-SEP-10:09 | 18.00 | 14.39 |
October | 0.112469E+10 | 5142.20 | 04-OCT-10:05 | 13.02 | 9.83 | 0.176097E+09 | 356.45 | 03-OCT-12:09 | 13.02 | 9.83 |
November | 0.475327E+09 | 2193.94 | 03-NOV-10:05 | 7.33 | 5.22 | 0.155118E+09 | 356.46 | 03-NOV-10:09 | 7.33 | 5.22 |
December | 0.211587E+09 | 763.22 | 08-DEC-11:10 | 6.17 | 4.24 | 0.141219E+09 | 314.95 | 08-DEC-11:09 | 6.17 | 4.24 |
Annual Sum or Average | 0.222726E+11 | 0.212176E+10 | ||||||||
Minimum of Months | 0.211587E+09 | 763.22 | 6.00 | 4.24 | 0.141219E+09 | 314.95 | 6.00 | 4.24 | ||
Maximum of Months | 0.389065E+10 | 13568.71 | 19.83 | 15.59 | 0.212307E+09 | 356.47 | 23.17 | 15.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134715E+10 | 7172.66 | 20-JAN-12:00 | 8.00 | 6.08 | 0.348270E+09 | 549.49 | 17-JAN-14:39 | 8.00 | 6.08 |
February | 0.168682E+10 | 8232.53 | 17-FEB-13:40 | 6.00 | 3.25 | 0.327215E+09 | 549.50 | 24-FEB-14:39 | 6.00 | 4.60 |
March | 0.151090E+10 | 4494.03 | 28-MAR-12:05 | 11.67 | 7.18 | 0.389405E+09 | 549.50 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.461245E+10 | 19661.86 | 30-APR-12:12 | 22.00 | 13.70 | 0.388711E+09 | 550.67 | 28-APR-13:20 | 22.00 | 13.70 |
May | 0.420430E+10 | 9863.39 | 21-MAY-12:53 | 17.00 | 10.30 | 0.425453E+09 | 549.51 | 22-MAY-13:50 | 22.83 | 15.60 |
June | 0.478492E+10 | 10569.41 | 25-JUN-15:23 | 24.50 | 14.94 | 0.431632E+09 | 549.53 | 08-JUN-13:09 | 24.50 | 14.94 |
July | 0.546533E+10 | 18033.39 | 23-JUL-13:23 | 21.50 | 16.21 | 0.402670E+09 | 549.50 | 12-JUL-13:50 | 21.50 | 16.21 |
August | 0.664603E+10 | 18192.03 | 13-AUG-13:23 | 21.00 | 15.45 | 0.452040E+09 | 550.74 | 30-AUG-13:20 | 20.00 | 14.96 |
September | 0.629200E+10 | 18211.46 | 10-SEP-11:32 | 20.33 | 15.24 | 0.398362E+09 | 550.63 | 13-SEP-13:20 | 22.33 | 15.98 |
October | 0.339826E+10 | 11509.74 | 03-OCT-13:05 | 13.17 | 9.32 | 0.383707E+09 | 549.84 | 03-OCT-13:20 | 13.33 | 9.34 |
November | 0.153958E+10 | 9698.82 | 11-NOV-13:03 | 9.00 | 7.36 | 0.351622E+09 | 549.50 | 17-NOV-14:09 | 8.00 | 6.02 |
December | 0.800494E+09 | 5610.38 | 18-DEC-13:25 | 8.00 | 5.46 | 0.323547E+09 | 549.49 | 26-DEC-14:00 | 6.00 | 3.37 |
Annual Sum or Average | 0.422882E+11 | 0.462263E+10 | ||||||||
Minimum of Months | 0.800494E+09 | 4494.03 | 6.00 | 3.25 | 0.323547E+09 | 549.49 | 6.00 | 3.37 | ||
Maximum of Months | 0.664603E+10 | 19661.86 | 24.50 | 16.21 | 0.452040E+09 | 550.74 | 24.50 | 16.21 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.409440E+09 | 1626.46 | 19-JAN-15:50 | 8.17 | 7.46 | 0.205322E+09 | 347.82 | 19-JAN-14:00 | 8.17 | 7.46 |
February | 0.593685E+09 | 2679.16 | 27-FEB-16:30 | 8.00 | 6.72 | 0.193475E+09 | 347.84 | 27-FEB-14:00 | 8.00 | 6.72 |
March | 0.827722E+09 | 3195.59 | 23-MAR-16:40 | 10.00 | 6.65 | 0.235620E+09 | 347.83 | 10-MAR-14:00 | 10.00 | 6.65 |
April | 0.231801E+10 | 14708.83 | 30-APR-17:31 | 24.00 | 12.95 | 0.241697E+09 | 347.86 | 14-APR-13:00 | 24.00 | 12.95 |
May | 0.281015E+10 | 12595.58 | 21-MAY-16:52 | 20.00 | 12.79 | 0.268155E+09 | 347.85 | 12-MAY-09:20 | 20.00 | 12.79 |
June | 0.368088E+10 | 13560.69 | 25-JUN-17:22 | 21.50 | 17.05 | 0.273587E+09 | 347.86 | 09-JUN-13:00 | 21.50 | 17.05 |
July | 0.398410E+10 | 13648.72 | 09-JUL-17:02 | 21.00 | 15.03 | 0.254886E+09 | 347.85 | 03-JUL-09:20 | 21.00 | 15.03 |
August | 0.375290E+10 | 12951.32 | 20-AUG-16:12 | 23.33 | 14.80 | 0.285852E+09 | 347.86 | 15-AUG-09:20 | 23.33 | 14.80 |
September | 0.264321E+10 | 11547.64 | 24-SEP-16:33 | 21.33 | 15.15 | 0.249647E+09 | 347.86 | 19-SEP-13:50 | 21.33 | 15.15 |
October | 0.126446E+10 | 5354.24 | 03-OCT-15:40 | 14.00 | 8.96 | 0.233334E+09 | 347.85 | 02-OCT-13:20 | 14.00 | 8.96 |
November | 0.605378E+09 | 1880.68 | 10-NOV-15:30 | 11.50 | 8.42 | 0.209100E+09 | 347.83 | 15-NOV-14:00 | 12.00 | 8.90 |
December | 0.230152E+09 | 794.81 | 21-DEC-14:50 | 8.00 | 6.98 | 0.190816E+09 | 326.39 | 21-DEC-14:00 | 8.00 | 6.98 |
Annual Sum or Average | 0.231201E+11 | 0.284149E+10 | ||||||||
Minimum of Months | 0.230152E+09 | 794.81 | 8.00 | 6.65 | 0.190816E+09 | 326.39 | 8.00 | 6.65 | ||
Maximum of Months | 0.398410E+10 | 14708.83 | 24.00 | 17.05 | 0.285852E+09 | 347.86 | 24.00 | 17.05 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 27483483.22 | 16050.68 | 02-JAN-07:12 | 1.67 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 27483483.22 | |||
Minimum of Months | 0.00 | 0.00 | 1.67 | |
Maximum of Months | 27483483.22 | 16050.68 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.276173E+10 | 11068.01 | 02-JAN-06:12 | 1.33 |
February | 0.188924E+10 | 9615.09 | 17-FEB-07:02 | -3.8 |
March | 0.166207E+10 | 7876.35 | 27-MAR-06:01 | 0.33 |
April | 0.735004E+09 | 3650.19 | 30-APR-07:07 | 16.23 |
May | 0.571934E+09 | 3703.00 | 21-MAY-08:43 | 13.00 |
June | 0.309728E+09 | 3197.42 | 08-JUN-05:03 | 6.17 |
July | 0.258561E+09 | 3650.34 | 16-JUL-07:32 | 15.33 |
August | 0.371426E+09 | 4036.71 | 20-AUG-08:62 | 16.17 |
September | 0.556065E+09 | 3391.58 | 04-SEP-08:10 | 12.33 |
October | 0.121082E+10 | 6162.88 | 23-OCT-06:03 | 4.00 |
November | 0.196947E+10 | 9773.91 | 27-NOV-06:22 | 4.00 |
December | 0.310463E+10 | 11759.28 | 04-DEC-06:16 | 3.00 |
Annual Sum or Average | 0.154007E+11 | |||
Minimum of Months | 0.258561E+09 | 3197.42 | -3.8 | |
Maximum of Months | 0.310463E+10 | 11759.28 | 16.23 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151470E+10 | 7736.25 | 02-JAN-07:04 | 1.83 |
February | 0.114233E+10 | 3202.09 | 19-FEB-13:40 | 6.00 |
March | 0.102368E+10 | 2033.98 | 06-MAR-07:13 | 4.67 |
April | 0.307592E+09 | 5370.24 | 30-APR-14:52 | 24.00 |
May | 0.199193E+09 | 3671.55 | 21-MAY-08:53 | 13.00 |
June | 26003357.11 | 3581.79 | 25-JUN-15:23 | 24.50 |
July | 33357085.83 | 3344.66 | 30-JUL-14:43 | 17.00 |
August | 30642368.83 | 4489.35 | 20-AUG-14:53 | 23.00 |
September | 82420116.69 | 4849.34 | 24-SEP-15:53 | 22.00 |
October | 0.665118E+09 | 3559.01 | 01-OCT-12:03 | 13.67 |
November | 0.112184E+10 | 4273.06 | 11-NOV-13:03 | 9.00 |
December | 0.156363E+10 | 5648.19 | 26-DEC-07:03 | 1.83 |
Annual Sum or Average | 0.771051E+10 | |||
Minimum of Months | 26003357.11 | 2033.98 | 1.83 | |
Maximum of Months | 0.156363E+10 | 7736.25 | 24.50 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128166E+10 | 5444.83 | 02-JAN-07:01 | 1.83 |
February | 0.921060E+09 | 4072.10 | 24-FEB-08:06 | 0.50 |
March | 0.853725E+09 | 3582.25 | 10-MAR-08:06 | 4.50 |
April | 73929300.42 | 3494.36 | 20-APR-05:03 | 1.17 |
May | 29207928.81 | 1835.83 | 28-MAY-15:37 | 13.00 |
June | 20386271.26 | 1734.51 | 18-JUN-16:30 | 14.00 |
July | 28171858.95 | 2146.53 | 09-JUL-16:51 | 21.00 |
August | 22858520.68 | 2902.10 | 06-AUG-15:32 | 17.33 |
September | 28813120.85 | 2498.56 | 24-SEP-13:32 | 20.33 |
October | 0.351623E+09 | 3137.01 | 23-OCT-07:06 | 4.50 |
November | 0.909146E+09 | 3896.60 | 13-NOV-08:07 | 6.33 |
December | 0.140294E+10 | 3512.05 | 08-DEC-08:18 | 1.00 |
Annual Sum or Average | 0.592353E+10 | |||
Minimum of Months | 20386271.26 | 1734.51 | 0.50 | |
Maximum of Months | 0.140294E+10 | 5444.83 | 21.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215157E+09 | 18406.69 | 02-JAN-06:01 | 1.17 |
February | 9950088.75 | 15292.65 | 13-FEB-07:01 | -0.7 |
March | 5029357.34 | 15398.06 | 06-MAR-07:02 | 4.33 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 11942264.55 | 15645.61 | 27-NOV-07:02 | 4.00 |
December | 95024197.14 | 17312.38 | 18-DEC-06:01 | 0.17 |
Annual Sum or Average | 0.337103E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 0.215157E+09 | 18406.69 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.978933E+09 | 29019.04 | 02-JAN-05:01 | 1.00 |
February | 0.368879E+09 | 26087.87 | 13-FEB-06:01 | -1.0 |
March | 0.221240E+09 | 25952.10 | 06-MAR-06:11 | 4.00 |
April | 2363465.23 | 9711.37 | 03-APR-06:03 | 3.17 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 38152626.22 | 23989.01 | 30-OCT-06:03 | 6.83 |
November | 0.331933E+09 | 26577.62 | 27-NOV-06:11 | 4.00 |
December | 0.107192E+10 | 28062.59 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.301342E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.107192E+10 | 29019.04 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193188E+10 | 8097.91 | 09-JAN-05:11 | -2.1 |
February | 0.112820E+10 | 7840.71 | 13-FEB-05:02 | -1.0 |
March | 0.682791E+09 | 7662.65 | 06-MAR-06:11 | 4.00 |
April | 56529822.77 | 6506.22 | 03-APR-06:03 | 3.17 |
May | 5231119.93 | 6398.06 | 06-MAY-06:03 | 3.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 2589303.03 | 3807.65 | 21-SEP-06:03 | 5.33 |
October | 0.223610E+09 | 7257.60 | 23-OCT-05:11 | 3.33 |
November | 0.970420E+09 | 7939.95 | 20-NOV-05:01 | 0.67 |
December | 0.227472E+10 | 8073.73 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.727597E+10 | |||
Minimum of Months | 0.00 | 0.00 | -2.1 | |
Maximum of Months | 0.227472E+10 | 8097.91 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108925E+10 | 8626.43 | 09-JAN-05:11 | -2.1 |
February | 0.612103E+09 | 8128.27 | 13-FEB-05:02 | -1.0 |
March | 0.390484E+09 | 8064.89 | 06-MAR-06:11 | 4.00 |
April | 12794012.62 | 5677.26 | 01-APR-06:03 | 3.17 |
May | 1500887.08 | 2750.95 | 17-MAY-06:03 | 6.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 648349.81 | 1664.37 | 21-SEP-06:03 | 5.33 |
October | 0.128705E+09 | 7402.94 | 23-OCT-05:11 | 3.33 |
November | 0.547070E+09 | 8386.45 | 27-NOV-06:11 | 4.00 |
December | 0.135635E+10 | 8523.17 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.413890E+10 | |||
Minimum of Months | 0.00 | 0.00 | -2.1 | |
Maximum of Months | 0.135635E+10 | 8626.43 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126265E+10 | 13113.84 | 09-JAN-05:11 | -2.1 |
February | 0.719991E+09 | 12197.22 | 27-FEB-06:11 | 6.00 |
March | 0.546585E+09 | 12280.08 | 06-MAR-06:11 | 4.00 |
April | 45402811.41 | 9461.17 | 01-APR-06:03 | 3.17 |
May | 12493806.03 | 8691.52 | 06-MAY-06:03 | 3.50 |
June | 20287.72 | 67.63 | 08-JUN-06:05 | 7.50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 749905.52 | 1403.02 | 20-SEP-06:05 | 6.17 |
October | 0.162376E+09 | 11092.42 | 23-OCT-05:11 | 3.33 |
November | 0.653408E+09 | 12732.47 | 27-NOV-06:11 | 4.00 |
December | 0.175423E+10 | 13034.95 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.515791E+10 | |||
Minimum of Months | 0.00 | 0.00 | -2.1 | |
Maximum of Months | 0.175423E+10 | 13113.84 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115406E+10 | 8562.57 | 09-JAN-05:11 | -2.1 |
February | 0.638870E+09 | 8090.09 | 13-FEB-05:02 | -1.0 |
March | 0.425092E+09 | 7960.59 | 06-MAR-06:11 | 4.00 |
April | 35084549.06 | 6144.80 | 01-APR-06:03 | 3.17 |
May | 8225744.24 | 5587.38 | 05-MAY-06:03 | 6.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 1060047.81 | 1778.09 | 21-SEP-06:03 | 5.33 |
October | 0.147557E+09 | 7179.26 | 23-OCT-05:11 | 3.33 |
November | 0.605755E+09 | 8349.78 | 27-NOV-06:11 | 4.00 |
December | 0.148798E+10 | 8468.92 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.450369E+10 | |||
Minimum of Months | 0.00 | 0.00 | -2.1 | |
Maximum of Months | 0.148798E+10 | 8562.57 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107732E+10 | 6435.15 | 02-JAN-05:01 | 1.00 |
February | 0.437912E+09 | 5660.75 | 13-FEB-06:01 | -1.0 |
March | 0.232636E+09 | 5605.58 | 06-MAR-06:11 | 4.00 |
April | 8297731.66 | 5163.93 | 03-APR-06:03 | 3.17 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 13291157.77 | 5178.77 | 30-OCT-06:03 | 6.83 |
November | 0.186781E+09 | 5581.91 | 27-NOV-06:11 | 4.00 |
December | 0.870516E+09 | 5896.32 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.282676E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.107732E+10 | 6435.15 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.564108E+09 | 6486.45 | 02-JAN-05:01 | 1.00 |
February | 0.200333E+09 | 5587.47 | 17-FEB-06:03 | -3.1 |
March | 0.125443E+09 | 5585.50 | 06-MAR-06:11 | 4.00 |
April | 1029862.04 | 4222.04 | 01-APR-06:03 | 3.17 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 7370784.62 | 5126.30 | 23-OCT-06:03 | 4.00 |
November | 0.102103E+09 | 5576.44 | 30-NOV-06:11 | 4.00 |
December | 0.520732E+09 | 5953.54 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.152112E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.1 | |
Maximum of Months | 0.564108E+09 | 6486.45 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.297679E+10 | 10396.85 | 11-JAN-07:10 | -3.2 |
February | 0.208564E+10 | 10628.17 | 17-FEB-07:10 | -3.8 |
March | 0.250280E+10 | 9996.07 | 08-MAR-07:10 | -0.5 |
April | 0.813149E+09 | 8629.80 | 03-APR-06:10 | 3.17 |
May | 0.817214E+09 | 8155.66 | 05-MAY-06:10 | 6.17 |
June | 0.294728E+09 | 7979.04 | 07-JUN-11:06 | 9.50 |
July | 98687140.18 | 7754.15 | 03-JUL-06:07 | 10.50 |
August | 81821214.90 | 7970.99 | 30-AUG-06:06 | 9.50 |
September | 0.269704E+09 | 7996.18 | 20-SEP-06:05 | 6.17 |
October | 0.105697E+10 | 8457.72 | 23-OCT-06:50 | 4.00 |
November | 0.195891E+10 | 9962.49 | 29-NOV-07:10 | -1.0 |
December | 0.301087E+10 | 10152.48 | 27-DEC-07:10 | -1.8 |
Annual Sum or Average | 0.159673E+11 | |||
Minimum of Months | 81821214.90 | 7754.15 | -3.8 | |
Maximum of Months | 0.301087E+10 | 10628.17 | 10.50 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.595848E+09 | 6488.64 | 02-JAN-05:01 | 1.00 |
February | 0.173356E+09 | 5552.62 | 03-FEB-06:11 | 2.67 |
March | 0.128439E+09 | 5545.18 | 04-MAR-06:11 | 3.00 |
April | 2860529.62 | 4625.47 | 01-APR-06:03 | 3.17 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 7511625.94 | 5292.69 | 30-OCT-06:03 | 6.83 |
November | 0.113642E+09 | 5483.99 | 30-NOV-06:11 | 4.00 |
December | 0.584969E+09 | 5828.69 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.160663E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.00 | |
Maximum of Months | 0.595848E+09 | 6488.64 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.790669E+09 | 7224.04 | 02-JAN-05:01 | 1.00 |
February | 0.277500E+09 | 6420.44 | 13-FEB-06:01 | -1.0 |
March | 0.135372E+09 | 6308.90 | 06-MAR-06:11 | 4.00 |
April | 2690721.76 | 5708.37 | 01-APR-06:03 | 3.17 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 20590652.58 | 5810.36 | 30-OCT-06:03 | 6.83 |
November | 0.240724E+09 | 6493.89 | 27-NOV-06:11 | 4.00 |
December | 0.905632E+09 | 6899.86 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.237318E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.905632E+09 | 7224.04 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.451281E+09 | 6605.24 | 02-JAN-05:01 | 1.00 |
February | 0.155651E+09 | 5468.68 | 07-FEB-06:11 | 5.67 |
March | 80219243.42 | 5473.04 | 27-MAR-05:01 | 0.83 |
April | 732037.37 | 2944.01 | 01-APR-06:03 | 3.17 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 14572931.82 | 5225.70 | 30-OCT-06:03 | 6.83 |
November | 0.145350E+09 | 5572.50 | 27-NOV-06:11 | 4.00 |
December | 0.552236E+09 | 6237.69 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.140004E+10 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 0.552236E+09 | 6605.24 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.478551E+09 | 9652.25 | 02-JAN-05:01 | 1.00 |
February | 0.156876E+09 | 8409.61 | 18-FEB-06:01 | -1.2 |
March | 0.103944E+09 | 8399.61 | 13-MAR-05:11 | 2.07 |
April | 1638204.07 | 4465.31 | 01-APR-06:03 | 3.17 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 15835786.15 | 7867.80 | 30-OCT-06:03 | 6.83 |
November | 0.151101E+09 | 8472.35 | 27-NOV-06:11 | 4.00 |
December | 0.643676E+09 | 9238.76 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.155162E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.2 | |
Maximum of Months | 0.643676E+09 | 9652.25 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.470635E+09 | 6581.14 | 02-JAN-05:01 | 1.00 |
February | 0.155599E+09 | 5517.24 | 03-FEB-06:11 | 2.67 |
March | 87857059.09 | 5461.65 | 08-MAR-06:01 | -0.2 |
April | 1464267.75 | 3513.70 | 01-APR-06:03 | 3.17 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 14943914.44 | 5194.87 | 30-OCT-06:03 | 6.83 |
November | 0.159219E+09 | 5536.48 | 27-NOV-06:11 | 4.00 |
December | 0.602804E+09 | 6194.30 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.149252E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.2 | |
Maximum of Months | 0.602804E+09 | 6581.14 | 12.43 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.678795E+09 | 1040.56 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.551220E+09 | 980.66 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.602776E+09 | 878.60 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.508258E+09 | 748.64 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.530329E+09 | 527.96 | 04-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.521376E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.490358E+09 | 496.34 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.559798E+09 | 578.28 | 22-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.522050E+09 | 680.25 | 08-SEP-07:30 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.599811E+09 | 1035.11 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.667236E+09 | 1040.56 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.705360E+09 | 1040.56 | 01-DEC-15:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.693737E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.490358E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.705360E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.416407E+09 | 658.76 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.342268E+09 | 617.54 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.379242E+09 | 536.81 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.321673E+09 | 442.01 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.337115E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.331596E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.311899E+09 | 314.23 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.354656E+09 | 356.64 | 22-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.328600E+09 | 364.60 | 08-SEP-07:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.373908E+09 | 655.08 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.412603E+09 | 658.76 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.430790E+09 | 658.76 | 01-DEC-15:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.434076E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.311899E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.430790E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.645943E+09 | 1040.56 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.534056E+09 | 977.77 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.596338E+09 | 871.02 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.509048E+09 | 743.80 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.532455E+09 | 530.04 | 04-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.523514E+09 | 496.34 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.492762E+09 | 526.97 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.561597E+09 | 577.17 | 22-AUG-07:30 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.520188E+09 | 585.14 | 08-SEP-07:30 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.585810E+09 | 1034.88 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.639933E+09 | 1040.56 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.669376E+09 | 1040.56 | 01-DEC-15:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.681102E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.492762E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.669376E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.420182E+09 | 658.71 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.344064E+09 | 620.99 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.380562E+09 | 563.58 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.321985E+09 | 486.74 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.336229E+09 | 348.90 | 04-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.330207E+09 | 314.21 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.310870E+09 | 344.88 | 07-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.355331E+09 | 369.51 | 22-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330569E+09 | 488.93 | 08-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.376601E+09 | 655.25 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.413253E+09 | 658.71 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.437063E+09 | 658.71 | 01-DEC-15:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.435692E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.310870E+09 | 314.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.437063E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.675520E+09 | 1040.56 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.548961E+09 | 978.39 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.600998E+09 | 872.33 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.507886E+09 | 737.44 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.530094E+09 | 496.34 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.521169E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.490156E+09 | 496.34 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.559339E+09 | 575.30 | 22-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.521255E+09 | 666.45 | 08-SEP-07:30 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.597815E+09 | 1034.90 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.663397E+09 | 1040.56 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.701741E+09 | 1040.56 | 01-DEC-15:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.691833E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.490156E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.701741E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.415193E+09 | 658.76 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.341516E+09 | 616.23 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.378611E+09 | 532.71 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.321461E+09 | 434.60 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.336916E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.331416E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.311712E+09 | 314.23 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.354380E+09 | 354.38 | 22-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.328270E+09 | 362.71 | 08-SEP-07:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.372826E+09 | 654.96 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.411249E+09 | 658.76 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.429162E+09 | 658.76 | 01-DEC-15:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.433271E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.311712E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.429162E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.644133E+09 | 1040.56 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.533193E+09 | 975.35 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.595434E+09 | 864.38 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.508619E+09 | 732.38 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.532062E+09 | 496.34 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.523196E+09 | 496.34 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.492430E+09 | 496.34 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.561030E+09 | 574.12 | 22-AUG-07:30 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.519735E+09 | 582.45 | 08-SEP-07:30 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.584697E+09 | 1034.66 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.638093E+09 | 1040.56 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.667315E+09 | 1040.56 | 01-DEC-15:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.679994E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.492430E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.667315E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.418950E+09 | 658.71 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.342924E+09 | 619.84 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.379790E+09 | 560.67 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.321641E+09 | 481.50 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.336038E+09 | 346.53 | 04-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.330024E+09 | 314.21 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.310713E+09 | 342.33 | 07-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.354970E+09 | 367.94 | 22-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330174E+09 | 483.91 | 08-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.375515E+09 | 655.15 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.411823E+09 | 658.71 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.435485E+09 | 658.71 | 01-DEC-15:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.434805E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.310713E+09 | 314.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.435485E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.678792E+09 | 1040.56 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.551217E+09 | 980.66 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.602757E+09 | 878.59 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.508258E+09 | 748.61 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.530329E+09 | 527.95 | 04-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.521376E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.490358E+09 | 496.34 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.559798E+09 | 578.28 | 22-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.522049E+09 | 680.22 | 08-SEP-07:30 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.599808E+09 | 1035.10 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.667214E+09 | 1040.56 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.705356E+09 | 1040.56 | 01-DEC-15:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.693731E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.490358E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.705356E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.416405E+09 | 658.76 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.342256E+09 | 617.53 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.379241E+09 | 536.80 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.321673E+09 | 441.99 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.337115E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.331596E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.311899E+09 | 314.23 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.354656E+09 | 356.63 | 22-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.328600E+09 | 364.60 | 08-SEP-07:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.373907E+09 | 655.08 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.412601E+09 | 658.76 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.430788E+09 | 658.76 | 01-DEC-15:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.434074E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.311899E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.430788E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.645942E+09 | 1040.56 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.534055E+09 | 977.76 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.596336E+09 | 871.00 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.509048E+09 | 743.77 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.532454E+09 | 530.02 | 04-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.523514E+09 | 496.34 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.492761E+09 | 526.96 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.561597E+09 | 577.17 | 22-AUG-07:30 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.520188E+09 | 585.13 | 08-SEP-07:30 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.585808E+09 | 1034.88 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.639931E+09 | 1040.56 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.669374E+09 | 1040.56 | 01-DEC-15:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.681101E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.492761E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.669374E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.420181E+09 | 658.71 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.344062E+09 | 620.99 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.380561E+09 | 563.57 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.321985E+09 | 486.73 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.336229E+09 | 348.89 | 04-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.330206E+09 | 314.21 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.310870E+09 | 344.88 | 07-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.355331E+09 | 369.50 | 22-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330569E+09 | 488.92 | 08-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.376589E+09 | 655.25 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.413251E+09 | 658.71 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.437061E+09 | 658.71 | 01-DEC-15:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.435690E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.310870E+09 | 314.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.437061E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.678795E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226229E+09 |
February | 0.901968E+09 | 0.551220E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324372E+09 |
March | 0.107774E+10 | 0.602776E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195050E+09 |
April | 0.956342E+09 | 0.508258E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260996E+09 |
May | 0.103597E+10 | 0.530329E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640912E+09 |
June | 0.103308E+10 | 0.521376E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 310325.12 | 0.504150E+09 |
July | 0.959235E+09 | 0.490358E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1421370.51 | 0.481798E+09 |
August | 0.107774E+10 | 0.559798E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 201934.31 | 0.345676E+09 |
September | 0.956342E+09 | 0.522050E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352520E+09 |
October | 0.994195E+09 | 0.599811E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353561E+09 |
November | 0.984487E+09 | 0.667236E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416170E+09 |
December | 0.959235E+09 | 0.705360E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561537E+09 |
Annual Sum or Average | 0.119305E+11 | 0.693737E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1933629.94 | 0.466297E+10 |
Minimum of Months | 0.901968E+09 | 0.490358E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195050E+09 |
Maximum of Months | 0.107774E+10 | 0.705360E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1421370.51 | 0.640912E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.416407E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152406E+09 |
February | 0.571020E+09 | 0.342268E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219394E+09 |
March | 0.682301E+09 | 0.379242E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132332E+09 |
April | 0.605444E+09 | 0.321673E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181548E+09 |
May | 0.655854E+09 | 0.337115E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440150E+09 |
June | 0.654023E+09 | 0.331596E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 206886.58 | 0.343196E+09 |
July | 0.607275E+09 | 0.311899E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 946199.05 | 0.333055E+09 |
August | 0.682301E+09 | 0.354656E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 134624.93 | 0.240214E+09 |
September | 0.605444E+09 | 0.328600E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248978E+09 |
October | 0.629407E+09 | 0.373908E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241726E+09 |
November | 0.623262E+09 | 0.412603E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279736E+09 |
December | 0.607275E+09 | 0.430790E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374980E+09 |
Annual Sum or Average | 0.755301E+10 | 0.434076E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1287710.56 | 0.318771E+10 |
Minimum of Months | 0.571020E+09 | 0.311899E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132332E+09 |
Maximum of Months | 0.682301E+09 | 0.430790E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 946199.05 | 0.440150E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.645943E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240393E+09 |
February | 0.901968E+09 | 0.534056E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344483E+09 |
March | 0.107774E+10 | 0.596338E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202544E+09 |
April | 0.956342E+09 | 0.509048E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276735E+09 |
May | 0.103597E+10 | 0.532455E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.661648E+09 |
June | 0.103308E+10 | 0.523514E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 310315.39 | 0.513130E+09 |
July | 0.959235E+09 | 0.492762E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1370355.85 | 0.498239E+09 |
August | 0.107774E+10 | 0.561597E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 201931.30 | 0.364558E+09 |
September | 0.956342E+09 | 0.520188E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381326E+09 |
October | 0.994195E+09 | 0.585810E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378987E+09 |
November | 0.984487E+09 | 0.639933E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437989E+09 |
December | 0.959235E+09 | 0.669376E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578374E+09 |
Annual Sum or Average | 0.119305E+11 | 0.681102E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1882602.54 | 0.487841E+10 |
Minimum of Months | 0.901968E+09 | 0.492762E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202544E+09 |
Maximum of Months | 0.107774E+10 | 0.669376E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1370355.85 | 0.661648E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.420182E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152333E+09 |
February | 0.570983E+09 | 0.344064E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220734E+09 |
March | 0.682256E+09 | 0.380562E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131553E+09 |
April | 0.605404E+09 | 0.321985E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180052E+09 |
May | 0.655811E+09 | 0.336229E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444997E+09 |
June | 0.653980E+09 | 0.330207E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 206869.10 | 0.348963E+09 |
July | 0.607235E+09 | 0.310870E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 832994.08 | 0.338060E+09 |
August | 0.682256E+09 | 0.355331E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 134630.32 | 0.243180E+09 |
September | 0.605404E+09 | 0.330569E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246442E+09 |
October | 0.629366E+09 | 0.376601E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242355E+09 |
November | 0.623221E+09 | 0.413253E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279668E+09 |
December | 0.607235E+09 | 0.437063E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374092E+09 |
Annual Sum or Average | 0.755252E+10 | 0.435692E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1174493.49 | 0.320243E+10 |
Minimum of Months | 0.570983E+09 | 0.310870E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131553E+09 |
Maximum of Months | 0.682256E+09 | 0.437063E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 832994.08 | 0.444997E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.675520E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127272E+09 |
February | 0.901968E+09 | 0.548961E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184042E+09 |
March | 0.107774E+10 | 0.600998E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107380E+09 |
April | 0.956342E+09 | 0.507886E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 922.35 | 0.140103E+09 |
May | 0.103597E+10 | 0.530094E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.68 | 0.348831E+09 |
June | 0.103308E+10 | 0.521169E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 170708.18 | 0.272925E+09 |
July | 0.959235E+09 | 0.490156E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 875850.70 | 0.260994E+09 |
August | 0.107774E+10 | 0.559339E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 110529.88 | 0.186920E+09 |
September | 0.956342E+09 | 0.521255E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197126E+09 |
October | 0.994195E+09 | 0.597815E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204394E+09 |
November | 0.984487E+09 | 0.663397E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245151E+09 |
December | 0.959235E+09 | 0.701741E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328704E+09 |
Annual Sum or Average | 0.119305E+11 | 0.691833E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1158013.79 | 0.260384E+10 |
Minimum of Months | 0.901968E+09 | 0.490156E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107380E+09 |
Maximum of Months | 0.107774E+10 | 0.701741E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 875850.70 | 0.348831E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.415193E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86235060.12 |
February | 0.571020E+09 | 0.341516E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124999E+09 |
March | 0.682301E+09 | 0.378611E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72922816.38 |
April | 0.605444E+09 | 0.321461E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100547E+09 |
May | 0.655854E+09 | 0.336916E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.76 | 0.246293E+09 |
June | 0.654023E+09 | 0.331416E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113627.69 | 0.189621E+09 |
July | 0.607275E+09 | 0.311712E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 546153.20 | 0.185339E+09 |
August | 0.682301E+09 | 0.354380E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73686.51 | 0.134118E+09 |
September | 0.605444E+09 | 0.328270E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142603E+09 |
October | 0.629407E+09 | 0.372826E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141469E+09 |
November | 0.623262E+09 | 0.411249E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165570E+09 |
December | 0.607275E+09 | 0.429162E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219551E+09 |
Annual Sum or Average | 0.755301E+10 | 0.433271E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 733469.16 | 0.180927E+10 |
Minimum of Months | 0.571020E+09 | 0.311712E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72922816.38 |
Maximum of Months | 0.682301E+09 | 0.429162E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 546153.20 | 0.246293E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.644133E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441775E+10 |
February | 0.901968E+09 | 0.533193E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388425E+10 |
March | 0.107774E+10 | 0.595434E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424393E+10 |
April | 0.956342E+09 | 0.508619E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316549E+10 |
May | 0.103597E+10 | 0.532062E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.38 | 0.340961E+10 |
June | 0.103308E+10 | 0.523196E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12642681.02 | 0.243743E+10 |
July | 0.959235E+09 | 0.492430E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21625778.34 | 0.189270E+10 |
August | 0.107774E+10 | 0.561030E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9492255.75 | 0.190734E+10 |
September | 0.956342E+09 | 0.519735E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223984E+10 |
October | 0.994195E+09 | 0.584697E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326473E+10 |
November | 0.984487E+09 | 0.638093E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393784E+10 |
December | 0.959235E+09 | 0.667315E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429009E+10 |
Annual Sum or Average | 0.119305E+11 | 0.679994E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43760798.50 | 0.390910E+11 |
Minimum of Months | 0.901968E+09 | 0.492430E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189270E+10 |
Maximum of Months | 0.107774E+10 | 0.667315E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21625778.34 | 0.441775E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.418950E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85954166.40 |
February | 0.570983E+09 | 0.342924E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125932E+09 |
March | 0.682256E+09 | 0.379790E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72446282.87 |
April | 0.605404E+09 | 0.321641E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99816121.88 |
May | 0.655811E+09 | 0.336038E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.84 | 0.249103E+09 |
June | 0.653980E+09 | 0.330024E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113629.31 | 0.194299E+09 |
July | 0.607235E+09 | 0.310713E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 458527.45 | 0.188678E+09 |
August | 0.682256E+09 | 0.354970E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73690.94 | 0.136061E+09 |
September | 0.605404E+09 | 0.330174E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141072E+09 |
October | 0.629366E+09 | 0.375515E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141632E+09 |
November | 0.623221E+09 | 0.411823E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165285E+09 |
December | 0.607235E+09 | 0.435485E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218771E+09 |
Annual Sum or Average | 0.755252E+10 | 0.434805E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 645849.55 | 0.181905E+10 |
Minimum of Months | 0.570983E+09 | 0.310713E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72446282.87 |
Maximum of Months | 0.682256E+09 | 0.435485E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 458527.45 | 0.249103E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.678792E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199776E+09 |
February | 0.901968E+09 | 0.551217E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290411E+09 |
March | 0.107774E+10 | 0.602757E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172106E+09 |
April | 0.956342E+09 | 0.508258E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229147E+09 |
May | 0.103597E+10 | 0.530329E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561172E+09 |
June | 0.103308E+10 | 0.521376E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 262560.27 | 0.435723E+09 |
July | 0.959235E+09 | 0.490358E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1263314.21 | 0.416423E+09 |
August | 0.107774E+10 | 0.559798E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 170537.76 | 0.300325E+09 |
September | 0.956342E+09 | 0.522049E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312837E+09 |
October | 0.994195E+09 | 0.599808E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319851E+09 |
November | 0.984487E+09 | 0.667214E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377087E+09 |
December | 0.959235E+09 | 0.705356E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504337E+09 |
Annual Sum or Average | 0.119305E+11 | 0.693731E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1696412.25 | 0.411919E+10 |
Minimum of Months | 0.901968E+09 | 0.490358E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172106E+09 |
Maximum of Months | 0.107774E+10 | 0.705356E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1263314.21 | 0.561172E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.416405E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135046E+09 |
February | 0.421807E+09 | 0.342256E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196776E+09 |
March | 0.502994E+09 | 0.379241E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117290E+09 |
April | 0.447140E+09 | 0.321673E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158650E+09 |
May | 0.484071E+09 | 0.337115E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383937E+09 |
June | 0.482240E+09 | 0.331596E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 167874.91 | 0.296406E+09 |
July | 0.448971E+09 | 0.311899E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 791403.28 | 0.287509E+09 |
August | 0.502994E+09 | 0.354656E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113595.66 | 0.208232E+09 |
September | 0.447140E+09 | 0.328600E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219416E+09 |
October | 0.465148E+09 | 0.373907E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218391E+09 |
November | 0.460569E+09 | 0.412601E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254011E+09 |
December | 0.448971E+09 | 0.430788E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336691E+09 |
Annual Sum or Average | 0.557719E+10 | 0.434074E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1072873.85 | 0.281235E+10 |
Minimum of Months | 0.421807E+09 | 0.311899E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117290E+09 |
Maximum of Months | 0.502994E+09 | 0.430788E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 791403.28 | 0.383937E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.645942E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213040E+09 |
February | 0.901968E+09 | 0.534055E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307289E+09 |
March | 0.107774E+10 | 0.596336E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178443E+09 |
April | 0.956342E+09 | 0.509048E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240939E+09 |
May | 0.103597E+10 | 0.532454E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576801E+09 |
June | 0.103308E+10 | 0.523514E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 262551.68 | 0.443032E+09 |
July | 0.959235E+09 | 0.492761E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1218200.44 | 0.430358E+09 |
August | 0.107774E+10 | 0.561597E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 170534.14 | 0.315661E+09 |
September | 0.956342E+09 | 0.520188E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334833E+09 |
October | 0.994195E+09 | 0.585808E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339402E+09 |
November | 0.984487E+09 | 0.639931E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395975E+09 |
December | 0.959235E+09 | 0.669374E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519995E+09 |
Annual Sum or Average | 0.119305E+11 | 0.681101E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1651286.26 | 0.429577E+10 |
Minimum of Months | 0.901968E+09 | 0.492761E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178443E+09 |
Maximum of Months | 0.107774E+10 | 0.669374E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1218200.44 | 0.576801E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.420181E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134695E+09 |
February | 0.570983E+09 | 0.344062E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197302E+09 |
March | 0.682256E+09 | 0.380561E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116017E+09 |
April | 0.605404E+09 | 0.321985E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157602E+09 |
May | 0.655811E+09 | 0.336229E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388217E+09 |
June | 0.653980E+09 | 0.330206E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 175022.99 | 0.301099E+09 |
July | 0.607235E+09 | 0.310870E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 703354.92 | 0.292063E+09 |
August | 0.682256E+09 | 0.355331E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113698.31 | 0.210762E+09 |
September | 0.605404E+09 | 0.330569E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217621E+09 |
October | 0.629366E+09 | 0.376589E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218422E+09 |
November | 0.623221E+09 | 0.413251E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253261E+09 |
December | 0.607235E+09 | 0.437061E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335982E+09 |
Annual Sum or Average | 0.755252E+10 | 0.435690E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 992076.22 | 0.282304E+10 |
Minimum of Months | 0.570983E+09 | 0.310870E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116017E+09 |
Maximum of Months | 0.682256E+09 | 0.437061E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 703354.92 | 0.388217E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280173E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411349E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237934E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314583E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.771432E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186368.00 | 0.592877E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1302337.18 | 0.571918E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129815.65 | 0.419750E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443346E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457768E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544441E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720555E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1618520.83 | 0.576613E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237934E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1302337.18 | 0.771432E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340536E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500365E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291887E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394680E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.971871E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237351.45 | 0.752450E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1693294.60 | 0.723342E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169427.01 | 0.531169E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552583E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557202E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.654749E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.866049E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2100073.06 | 0.713688E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291887E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1693294.60 | 0.971871E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342690E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496396E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300824E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418445E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100841E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85082.15 | 0.793588E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1016874.02 | 0.766527E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94903.20 | 0.551922E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560635E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547638E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630743E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842645E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1196859.38 | 0.726046E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300824E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1016874.02 | 0.100841E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 706.06 | 08-JAN-08:00 |
February | 1306.65 | 01-FEB-10:09 | 980.66 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 781.13 | 08-FEB-22:03 |
March | 1306.65 | 01-MAR-10:09 | 878.60 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 773.74 | 27-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 748.64 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 758.86 | 23-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 527.96 | 04-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1211.60 | 04-MAY-23:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.74 | 13-JUN-15:40 | 890.22 | 05-JUN-21:10 |
July | 1306.65 | 03-JUL-09:09 | 496.34 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.96 | 22-JUL-17:01 | 812.27 | 30-JUL-18:33 |
August | 1306.65 | 01-AUG-09:09 | 578.28 | 22-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.31 | 14-AUG-16:50 | 593.99 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 680.25 | 08-SEP-07:30 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 718.73 | 06-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1035.11 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 868.69 | 20-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 795.94 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-15:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1394.93 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 593.99 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 65.96 | 1394.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 469.64 | 08-JAN-08:00 |
February | 827.22 | 01-FEB-10:09 | 617.54 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 520.37 | 08-FEB-22:03 |
March | 827.22 | 01-MAR-10:09 | 536.81 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 515.36 | 27-MAR-21:05 |
April | 827.22 | 03-APR-09:09 | 442.01 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 504.28 | 23-APR-22:00 |
May | 827.22 | 01-MAY-09:09 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 803.61 | 04-MAY-23:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.16 | 13-JUN-15:40 | 687.13 | 18-JUN-10:55 |
July | 827.22 | 03-JUL-09:09 | 314.23 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 22-JUL-18:52 | 562.00 | 30-JUL-18:33 |
August | 827.22 | 01-AUG-09:09 | 356.64 | 22-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 | 14-AUG-16:50 | 396.36 | 22-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 364.60 | 08-SEP-07:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 482.51 | 06-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 655.08 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 576.15 | 20-OCT-22:00 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 529.12 | 16-NOV-22:05 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-15:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 929.10 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.36 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 929.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 726.58 | 08-JAN-08:00 |
February | 1306.65 | 01-FEB-10:09 | 977.77 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 783.47 | 08-FEB-22:03 |
March | 1306.65 | 01-MAR-10:09 | 871.02 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 773.99 | 27-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 743.80 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 855.53 | 16-APR-12:00 |
May | 1306.65 | 01-MAY-09:09 | 530.04 | 04-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1216.40 | 04-MAY-23:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.74 | 13-JUN-15:40 | 989.51 | 18-JUN-15:43 |
July | 1306.65 | 03-JUL-09:09 | 526.97 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.45 | 22-JUL-18:52 | 895.68 | 30-JUL-18:33 |
August | 1306.65 | 01-AUG-09:09 | 577.17 | 22-AUG-07:30 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.31 | 14-AUG-16:50 | 618.00 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 585.14 | 08-SEP-07:30 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 731.69 | 06-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1034.88 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 892.39 | 20-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 808.11 | 26-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-15:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1420.85 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 618.00 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 63.45 | 1420.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 469.28 | 08-JAN-08:00 |
February | 827.17 | 01-FEB-10:09 | 620.99 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 521.48 | 08-FEB-22:03 |
March | 827.17 | 01-MAR-10:09 | 563.58 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 515.48 | 27-MAR-21:05 |
April | 827.17 | 03-APR-09:09 | 486.74 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 508.29 | 15-APR-17:40 |
May | 827.17 | 01-MAY-09:09 | 348.90 | 04-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 811.08 | 04-MAY-23:00 |
June | 827.17 | 01-JUN-09:09 | 314.21 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.16 | 13-JUN-15:40 | 729.90 | 18-JUN-16:20 |
July | 827.17 | 03-JUL-09:09 | 344.88 | 07-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.49 | 22-JUL-19:05 | 721.36 | 30-JUL-17:10 |
August | 827.17 | 01-AUG-09:09 | 369.51 | 22-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 | 14-AUG-16:50 | 424.08 | 22-AUG-21:10 |
September | 827.17 | 01-SEP-09:09 | 488.93 | 08-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 481.90 | 06-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 655.25 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 587.72 | 20-OCT-22:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 529.72 | 16-NOV-22:05 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-15:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 928.48 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.08 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 33.49 | 928.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 429.79 | 08-JAN-08:00 |
February | 1306.65 | 01-FEB-10:09 | 978.39 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 417.29 | 08-FEB-22:03 |
March | 1306.65 | 01-MAR-10:09 | 872.33 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 414.38 | 27-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 737.44 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.38 | 30-APR-19:00 | 437.10 | 23-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 687.34 | 04-MAY-23:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.38 | 13-JUN-15:30 | 480.47 | 05-JUN-21:50 |
July | 1306.65 | 03-JUL-09:09 | 496.34 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.60 | 22-JUL-18:52 | 445.93 | 30-JUL-18:55 |
August | 1306.65 | 01-AUG-09:09 | 575.30 | 22-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.38 | 14-AUG-16:50 | 323.34 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 666.45 | 08-SEP-07:30 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 425.73 | 06-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1034.90 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 506.37 | 20-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 496.17 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-15:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 784.02 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.34 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 47.60 | 784.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 289.09 | 08-JAN-08:00 |
February | 827.22 | 01-FEB-10:09 | 616.23 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 278.18 | 08-FEB-22:03 |
March | 827.22 | 01-MAR-10:09 | 532.71 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 276.37 | 27-MAR-21:05 |
April | 827.22 | 03-APR-09:09 | 434.60 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 299.49 | 23-APR-22:00 |
May | 827.22 | 01-MAY-09:09 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 460.55 | 04-MAY-23:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.25 | 13-JUN-15:30 | 360.76 | 18-JUN-10:55 |
July | 827.22 | 03-JUL-09:09 | 314.23 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.95 | 22-JUL-18:52 | 316.77 | 30-JUL-18:55 |
August | 827.22 | 01-AUG-09:09 | 354.38 | 22-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.25 | 14-AUG-16:50 | 223.73 | 22-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 362.71 | 08-SEP-07:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 301.05 | 06-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 654.96 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 342.02 | 01-OCT-24:00 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 328.74 | 26-NOV-04:00 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-15:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 521.63 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.73 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 28.95 | 521.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 20954.74 | 10-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 975.35 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 20724.11 | 17-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 864.38 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 17530.53 | 08-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 732.38 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 14953.35 | 20-APR-06:03 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 | 22-MAY-15:00 | 13741.77 | 02-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2398.92 | 13-JUN-17:00 | 11365.76 | 08-JUN-06:05 |
July | 1306.65 | 03-JUL-09:09 | 496.34 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3978.46 | 21-JUL-17:00 | 9852.49 | 05-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 574.12 | 22-AUG-07:30 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2401.37 | 14-AUG-17:00 | 10409.75 | 30-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 582.45 | 08-SEP-07:30 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 13601.55 | 21-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 1034.66 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 15673.32 | 06-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 18244.54 | 29-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-15:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 19832.74 | 29-DEC-17:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9852.49 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 3978.46 | 20954.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 286.72 | 08-JAN-08:00 |
February | 827.17 | 01-FEB-10:09 | 619.84 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 278.73 | 08-FEB-22:03 |
March | 827.17 | 01-MAR-10:09 | 560.67 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 276.13 | 27-MAR-21:05 |
April | 827.17 | 03-APR-09:09 | 481.50 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 297.05 | 23-APR-22:00 |
May | 827.17 | 01-MAY-09:09 | 346.53 | 04-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 467.25 | 04-MAY-23:00 |
June | 827.17 | 01-JUN-09:09 | 314.21 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.25 | 13-JUN-15:30 | 368.08 | 18-JUN-16:00 |
July | 827.17 | 03-JUL-09:09 | 342.33 | 07-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 | 22-JUL-19:08 | 393.51 | 30-JUL-18:55 |
August | 827.17 | 01-AUG-09:09 | 367.94 | 22-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.25 | 14-AUG-16:50 | 240.45 | 22-AUG-21:10 |
September | 827.17 | 01-SEP-09:09 | 483.91 | 08-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 293.58 | 06-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 655.15 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 346.83 | 01-OCT-24:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 327.57 | 25-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-15:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 520.84 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.45 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 | 520.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 664.41 | 08-JAN-08:00 |
February | 1306.65 | 01-FEB-10:09 | 980.66 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 655.12 | 08-FEB-22:03 |
March | 1306.65 | 01-MAR-10:09 | 878.59 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 650.50 | 27-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 748.61 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 694.07 | 23-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 527.95 | 04-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1082.25 | 04-MAY-23:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.15 | 13-JUN-15:30 | 762.44 | 05-JUN-21:20 |
July | 1306.65 | 03-JUL-09:09 | 496.34 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.78 | 22-JUL-18:52 | 680.30 | 30-JUL-18:40 |
August | 1306.65 | 01-AUG-09:09 | 578.28 | 22-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 | 14-AUG-16:50 | 516.14 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 680.22 | 08-SEP-07:30 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 660.43 | 06-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1035.10 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 783.02 | 20-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 745.38 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-15:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1214.53 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.14 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 61.78 | 1214.53 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 658.76 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 442.40 | 08-JAN-08:00 |
February | 805.43 | 01-FEB-08:09 | 617.53 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 436.53 | 08-FEB-22:03 |
March | 805.43 | 01-MAR-08:09 | 536.80 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 433.43 | 27-MAR-21:05 |
April | 805.43 | 03-APR-07:10 | 441.99 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 461.21 | 23-APR-22:00 |
May | 805.43 | 01-MAY-07:10 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 717.74 | 04-MAY-23:00 |
June | 805.43 | 01-JUN-07:10 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.77 | 13-JUN-15:30 | 577.02 | 18-JUN-11:00 |
July | 805.43 | 03-JUL-07:10 | 314.23 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.47 | 22-JUL-18:52 | 468.29 | 30-JUL-18:40 |
August | 805.43 | 01-AUG-07:10 | 356.63 | 22-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.70 | 14-AUG-16:50 | 344.83 | 22-AUG-21:10 |
September | 805.43 | 01-SEP-07:10 | 364.60 | 08-SEP-07:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 442.58 | 06-SEP-04:00 |
October | 805.43 | 02-OCT-07:10 | 655.08 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 519.73 | 20-OCT-22:00 |
November | 805.43 | 01-NOV-07:10 | 658.76 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 492.48 | 25-NOV-05:00 |
December | 805.43 | 01-DEC-08:09 | 658.76 | 01-DEC-15:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 808.87 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.83 | |||||
Maximum of Months | 805.43 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 43.47 | 808.87 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 682.01 | 08-JAN-08:00 |
February | 1306.65 | 01-FEB-10:09 | 977.76 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 675.46 | 05-FEB-14:00 |
March | 1306.65 | 01-MAR-10:09 | 871.00 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 650.89 | 27-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 743.77 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 703.84 | 16-APR-11:55 |
May | 1306.65 | 01-MAY-09:09 | 530.02 | 04-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1084.86 | 04-MAY-23:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.15 | 13-JUN-15:30 | 813.54 | 18-JUN-15:43 |
July | 1306.65 | 03-JUL-09:09 | 526.96 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.43 | 22-JUL-18:52 | 745.44 | 30-JUL-18:40 |
August | 1306.65 | 01-AUG-09:09 | 577.17 | 22-AUG-07:30 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 | 14-AUG-16:50 | 534.34 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 585.13 | 08-SEP-07:30 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 670.00 | 06-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1034.88 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 812.16 | 01-OCT-24:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 758.28 | 26-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-15:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1239.01 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.34 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 61.43 | 1239.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 441.66 | 08-JAN-08:00 |
February | 827.17 | 01-FEB-10:09 | 620.99 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 437.63 | 08-FEB-22:03 |
March | 827.17 | 01-MAR-10:09 | 563.57 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 433.49 | 27-MAR-21:05 |
April | 827.17 | 03-APR-09:09 | 486.73 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 459.87 | 23-APR-22:00 |
May | 827.17 | 01-MAY-09:09 | 348.89 | 04-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 724.02 | 04-MAY-23:00 |
June | 827.17 | 01-JUN-09:09 | 314.21 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.77 | 13-JUN-15:30 | 605.13 | 18-JUN-16:20 |
July | 827.17 | 03-JUL-09:09 | 344.88 | 07-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.53 | 22-JUL-19:05 | 604.46 | 30-JUL-18:40 |
August | 827.17 | 01-AUG-09:09 | 369.50 | 22-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.70 | 14-AUG-16:50 | 365.71 | 22-AUG-21:10 |
September | 827.17 | 01-SEP-09:09 | 488.92 | 08-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 442.01 | 06-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 655.25 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 530.28 | 20-OCT-22:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 492.19 | 25-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-15:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 808.48 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.71 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 27.53 | 808.48 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 972.66 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 908.45 | 08-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 893.06 | 27-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 991.73 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1534.52 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 13-JUN-16:00 | 1041.50 | 05-JUN-21:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.14 | 22-JUL-18:52 | 976.01 | 30-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.61 | 14-AUG-17:00 | 722.95 | 22-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 952.41 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1129.96 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1118.22 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1764.47 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 722.95 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.14 | 1764.47 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1179.72 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1120.03 | 08-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1093.48 | 27-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1219.73 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1924.03 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.12 | 13-JUN-16:00 | 1335.23 | 05-JUN-21:05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.90 | 22-JUL-18:52 | 1212.80 | 30-JUL-18:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 14-AUG-17:00 | 922.16 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1178.98 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1372.25 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1322.18 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2142.66 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 922.16 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.90 | 2142.66 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1046.38 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1140.04 | 08-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1147.82 | 27-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1157.11 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1865.61 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.94 | 13-JUN-17:00 | 1594.91 | 18-JUN-15:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 22-JUL-18:52 | 1434.44 | 30-JUL-18:45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 | 14-AUG-18:00 | 932.97 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1063.84 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1305.36 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1206.44 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2274.94 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 932.97 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 2274.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 15265.25 | 20-JAN-08:17 | 18105.02 | 14808.04 | 54555.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16002.35 | 10-FEB-08:05 | 48280.06 | 39488.12 | 145481.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17667.44 | 23-MAR-07:05 | 36210.05 | 29616.09 | 109111.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 25606.74 | 20-APR-05:03 | 2541.06 | 846.94 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 37992.97 | 01-MAY-06:02 | 7623.17 | 9872.16 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38209.27 | 14-JUN-06:02 | 7623.17 | 9872.16 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 40959.65 | 24-JUL-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 38196.84 | 21-AUG-06:01 | 8893.70 | 11517.52 | 61577.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38087.26 | 13-SEP-06:01 | 8893.70 | 11517.52 | 61577.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31133.89 | 02-OCT-06:02 | 7623.17 | 9872.16 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17780.61 | 10-NOV-08:03 | 36210.05 | 29616.09 | 109111.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14722.09 | 22-DEC-08:20 | 12070.02 | 9872.03 | 36370.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14722.09 | 2541.06 | 846.94 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40959.65 | 48280.06 | 39488.12 | 145481.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 493.99 | 21-JAN-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.74 |
February | 777.64 | 04-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.88 |
March | 1500.05 | 25-MAR-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.98 |
April | 7290.95 | 28-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.96 |
May | 7910.05 | 22-MAY-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.09 |
June | 8734.04 | 13-JUN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.30 |
July | 8726.21 | 21-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.13 | 0.00 |
August | 7977.11 | 14-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.55 |
September | 6733.99 | 12-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.90 |
October | 3130.96 | 03-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.77 |
November | 527.83 | 11-NOV-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.05 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8734.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.13 | 519.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1334.27 | 04-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.31 |
February | 1310.19 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.28 |
March | 1655.91 | 21-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2494.09 | 28-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.41 |
May | 2686.96 | 23-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.80 |
June | 3599.69 | 26-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.98 |
July | 3752.27 | 24-JUL-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.37 |
August | 3223.83 | 14-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.96 | 0.00 |
September | 2892.14 | 12-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.67 |
October | 1040.63 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.78 |
November | 1229.31 | 17-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.19 |
December | 1421.06 | 30-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1040.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3752.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.96 | 167.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2105.25 | 20-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2402.61 | 16-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.59 |
March | 2321.69 | 22-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2927.75 | 28-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.76 |
May | 3605.88 | 01-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.82 |
June | 3893.47 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 0.00 |
July | 4118.07 | 24-JUL-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.45 |
August | 3789.20 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.65 | 0.00 |
September | 3522.59 | 13-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.93 |
October | 2166.92 | 04-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.53 |
November | 2331.23 | 17-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.03 |
December | 2232.58 | 08-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2105.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4118.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 200.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6407.23 | 20-JAN-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6383.94 | 24-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6707.83 | 31-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13714.90 | 28-APR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21569.12 | 01-MAY-06:02 | 7623.17 | 9872.16 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21194.91 | 26-JUN-06:03 | 5082.11 | 6581.44 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29733.87 | 24-JUL-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22591.92 | 21-AUG-06:01 | 8893.70 | 11517.52 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14635.68 | 13-SEP-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11881.73 | 03-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6926.44 | 10-NOV-16:30 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5950.77 | 21-DEC-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5950.77 | 2541.06 | 2193.73 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29733.87 | 8893.70 | 11517.52 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6082.19 | 20-JAN-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6072.73 | 24-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6321.56 | 31-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14795.85 | 28-APR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15684.40 | 23-MAY-15:40 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17384.28 | 26-JUN-15:40 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18122.37 | 24-JUL-06:02 | 7623.17 | 9872.16 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16141.13 | 14-AUG-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15253.87 | 13-SEP-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10886.73 | 03-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6332.10 | 10-NOV-16:50 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5564.16 | 21-DEC-15:40 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5564.16 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18122.37 | 7623.17 | 9872.16 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1054.86 | 19-JAN-15:50 | 1272.23 | 540.76 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1033.51 | 24-FEB-16:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.49 |
March | 1201.82 | 30-MAR-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.99 |
April | 3757.76 | 28-APR-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.25 |
May | 4301.87 | 22-MAY-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 |
June | 5348.87 | 13-JUN-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 22.68 | 0.00 |
July | 5206.63 | 10-JUL-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.82 |
August | 4675.53 | 14-AUG-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 | 0.00 |
September | 3965.51 | 13-SEP-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 |
October | 1768.38 | 06-OCT-15:50 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.09 |
November | 1139.71 | 10-NOV-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.41 |
December | 913.36 | 21-DEC-16:00 | 1272.23 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 913.36 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5348.87 | 1272.23 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 22.68 | 120.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 789.73 | 20-JAN-10:50 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 846.77 | 24-FEB-10:40 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.32 |
March | 832.54 | 25-MAR-10:00 | 261.23 | 104.74 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8447.25 | 30-APR-09:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.30 |
May | 10268.15 | 21-MAY-09:23 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.01 |
June | 13153.23 | 25-JUN-09:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13358.03 | 16-JUL-08:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.49 |
August | 10656.82 | 20-AUG-10:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.42 |
September | 6576.03 | 12-SEP-09:10 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.19 |
October | 3314.20 | 04-OCT-10:00 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 773.70 | 03-NOV-10:00 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.67 |
December | 662.41 | 06-DEC-10:40 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 662.41 | 169.56 | 69.83 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13358.03 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6177.65 | 20-JAN-12:00 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7651.65 | 17-FEB-13:40 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.74 |
March | 3820.38 | 28-MAR-12:05 | 5088.93 | 1985.38 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.46 |
April | 19617.16 | 30-APR-13:02 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.42 |
May | 10170.08 | 22-MAY-13:10 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.39 |
June | 16599.98 | 25-JUN-15:52 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 |
July | 15417.24 | 30-JUL-13:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.47 |
August | 20009.47 | 06-AUG-13:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.48 |
September | 20245.06 | 24-SEP-13:42 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.10 |
October | 11704.18 | 01-OCT-13:33 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.90 |
November | 6616.97 | 03-NOV-12:40 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.43 |
December | 4946.32 | 18-DEC-13:25 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3820.38 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20245.06 | 5088.93 | 1985.38 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1416.43 | 19-JAN-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2537.19 | 27-FEB-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2914.57 | 23-MAR-16:50 | 254.33 | 174.56 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.51 |
April | 14423.64 | 30-APR-16:22 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.24 |
May | 13112.75 | 21-MAY-16:52 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.73 |
June | 15983.30 | 25-JUN-17:11 | 0.00 | 122.19 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.08 |
July | 16131.75 | 09-JUL-16:51 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.39 |
August | 15355.64 | 13-AUG-16:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.63 |
September | 11968.24 | 24-SEP-16:23 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.94 |
October | 5188.03 | 03-OCT-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.48 |
November | 1585.80 | 10-NOV-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.14 |
December | 753.41 | 21-DEC-14:50 | 827.17 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 753.41 | 0.00 | 69.82 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16131.75 | 827.17 | 314.21 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1017.69 | 25-JAN-15:10 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.39 |
February | 996.80 | 10-FEB-15:50 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.00 |
March | 1127.75 | 30-MAR-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.27 |
April | 2206.37 | 28-APR-15:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.14 |
May | 2581.27 | 23-MAY-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.93 |
June | 3833.38 | 13-JUN-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.25 | 0.00 |
July | 3737.97 | 21-JUL-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3285.64 | 14-AUG-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.65 | 0.00 |
September | 2944.82 | 13-SEP-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.04 |
October | 1370.82 | 03-OCT-12:07 | 3816.70 | 1489.03 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.84 |
November | 1150.12 | 10-NOV-15:10 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.86 |
December | 951.93 | 22-DEC-13:50 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 951.93 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3833.38 | 3816.70 | 1489.03 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 12.25 | 63.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 782.97 | 20-JAN-10:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 824.99 | 24-FEB-10:40 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.36 |
March | 788.79 | 31-MAR-09:50 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.52 |
April | 10563.75 | 30-APR-09:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.89 |
May | 8097.04 | 22-MAY-06:02 | 847.82 | 523.72 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.04 |
June | 9999.50 | 25-JUN-09:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10628.53 | 23-JUL-08:51 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.81 |
August | 6576.99 | 13-AUG-09:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.92 |
September | 5330.48 | 12-SEP-09:20 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.94 |
October | 3026.57 | 04-OCT-10:00 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 807.52 | 03-NOV-09:50 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.12 |
December | 699.40 | 08-DEC-10:40 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 699.40 | 169.56 | 69.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10628.53 | 847.82 | 523.72 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3353.15 | 21-JAN-11:30 | 401.76 | 165.45 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3753.72 | 04-FEB-14:00 | 133.92 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.02 |
March | 1333.95 | 25-MAR-11:50 | 137.54 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16322.88 | 30-APR-12:12 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.64 |
May | 7252.32 | 22-MAY-13:40 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.00 |
June | 7527.63 | 13-JUN-13:40 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 80.35 | 0.00 |
July | 9758.65 | 23-JUL-11:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.45 |
August | 15754.81 | 06-AUG-13:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.16 |
September | 15016.43 | 24-SEP-14:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.88 |
October | 10218.07 | 03-OCT-12:07 | 3816.70 | 1489.03 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1264.97 |
November | 2995.66 | 11-NOV-13:25 | 133.92 | 55.15 | 956.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.42 |
December | 2034.39 | 18-DEC-13:50 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1849.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1333.95 | 133.92 | 55.15 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16322.88 | 3816.70 | 1489.03 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 80.35 | 1849.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 860.86 | 19-JAN-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1641.77 | 27-FEB-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1874.77 | 23-MAR-17:00 | 254.33 | 174.56 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.69 |
April | 12753.38 | 30-APR-17:31 | 0.00 | 122.19 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.22 |
May | 8079.93 | 21-MAY-17:32 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.18 |
June | 12488.43 | 25-JUN-17:11 | 0.00 | 122.19 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.14 |
July | 12582.98 | 09-JUL-17:31 | 0.00 | 122.19 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.37 |
August | 12224.74 | 13-AUG-17:12 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.89 |
September | 6067.05 | 12-SEP-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.77 |
October | 4430.59 | 03-OCT-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.79 |
November | 1253.58 | 10-NOV-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.02 |
December | 727.96 | 21-DEC-14:50 | 827.17 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 727.96 | 0.00 | 87.28 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12753.38 | 827.17 | 314.21 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1110.73 | 19-JAN-15:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1100.69 | 24-FEB-16:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.00 |
March | 1250.70 | 30-MAR-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.03 |
April | 3543.64 | 28-APR-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 |
May | 3911.00 | 22-MAY-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 |
June | 6494.81 | 26-JUN-06:03 | 1071.35 | 661.80 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.46 |
July | 4782.77 | 10-JUL-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.98 |
August | 4378.76 | 14-AUG-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.36 | 0.00 |
September | 3841.66 | 13-SEP-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.49 |
October | 2060.75 | 06-OCT-15:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.33 |
November | 1198.36 | 10-NOV-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.78 |
December | 991.12 | 22-DEC-13:50 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 991.12 | 1071.35 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6494.81 | 1306.65 | 661.80 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 13.36 | 53.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2155.72 | 20-JAN-11:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2399.46 | 24-FEB-11:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 |
March | 2410.09 | 25-MAR-10:05 | 508.69 | 209.49 | 1009.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13568.71 | 30-APR-09:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.36 |
May | 12265.09 | 21-MAY-08:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.16 |
June | 11793.11 | 11-JUN-09:23 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.24 |
July | 13163.57 | 23-JUL-08:42 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.63 |
August | 11019.45 | 20-AUG-10:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.10 |
September | 7556.32 | 24-SEP-09:13 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.66 |
October | 5142.20 | 04-OCT-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.90 |
November | 2193.94 | 03-NOV-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.96 |
December | 763.22 | 08-DEC-11:10 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 763.22 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13568.71 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7172.66 | 20-JAN-12:00 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8232.53 | 17-FEB-13:40 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.01 |
March | 4494.03 | 28-MAR-12:05 | 5088.93 | 1985.38 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.22 |
April | 19661.86 | 30-APR-12:12 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.92 |
May | 9863.39 | 21-MAY-12:53 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.02 |
June | 10569.41 | 25-JUN-15:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.84 |
July | 18033.39 | 23-JUL-13:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.10 |
August | 18192.03 | 13-AUG-13:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.76 |
September | 18211.46 | 10-SEP-11:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.16 |
October | 11509.74 | 03-OCT-13:05 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.58 |
November | 9698.82 | 11-NOV-13:03 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.15 |
December | 5610.38 | 18-DEC-13:25 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4494.03 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19661.86 | 5088.93 | 1985.38 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1626.46 | 19-JAN-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2679.16 | 27-FEB-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3195.59 | 23-MAR-16:40 | 254.33 | 174.56 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.41 |
April | 14708.83 | 30-APR-17:31 | 0.00 | 122.19 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.70 |
May | 12595.58 | 21-MAY-16:52 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.52 |
June | 13560.69 | 25-JUN-17:22 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.34 |
July | 13648.72 | 09-JUL-17:02 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.60 |
August | 12951.32 | 20-AUG-16:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.52 |
September | 11547.64 | 24-SEP-16:33 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.39 |
October | 5354.24 | 03-OCT-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.60 |
November | 1880.68 | 10-NOV-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.89 |
December | 794.81 | 21-DEC-14:50 | 827.17 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 794.81 | 0.00 | 69.82 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14708.83 | 827.17 | 314.21 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.52 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.114291E+12 | 200003.49 | 02-JAN-07:10 | 0.427588E+11 | 70029.61 | 10-JAN-08:09 |
February | 0.940480E+11 | 127285.91 | 13-FEB-07:10 | 0.348785E+11 | 66152.27 | 17-FEB-07:30 |
March | 0.102615E+12 | 120117.74 | 06-MAR-07:10 | 0.334345E+11 | 51837.58 | 08-MAR-07:19 |
April | 0.884999E+11 | 96904.35 | 28-APR-15:20 | 0.160984E+11 | 45968.12 | 08-APR-06:10 |
May | 0.935436E+11 | 107054.60 | 22-MAY-15:09 | 0.143695E+11 | 30923.07 | 06-MAY-06:40 |
June | 0.972944E+11 | 127110.78 | 13-JUN-15:30 | 0.113706E+11 | 16804.89 | 07-JUN-20:30 |
July | 0.100058E+12 | 123545.79 | 21-JUL-15:39 | 0.109540E+11 | 11747.20 | 03-JUL-20:49 |
August | 0.109484E+12 | 121594.15 | 14-AUG-15:39 | 0.114394E+11 | 14416.08 | 24-AUG-06:10 |
September | 0.950621E+11 | 110938.69 | 13-SEP-15:09 | 0.111993E+11 | 23250.68 | 20-SEP-06:10 |
October | 0.938191E+11 | 96493.29 | 23-OCT-06:10 | 0.171318E+11 | 37129.82 | 23-OCT-06:19 |
November | 0.100129E+12 | 139230.22 | 27-NOV-07:10 | 0.284763E+11 | 58004.56 | 29-NOV-07:19 |
December | 0.116726E+12 | 168301.34 | 26-DEC-07:10 | 0.417144E+11 | 60146.15 | 27-DEC-07:19 |
Annual Sum or Average | 0.120557E+13 | 0.273825E+12 | ||||
Minimum of Months | 0.884999E+11 | 96493.29 | 0.109540E+11 | 11747.20 | ||
Maximum of Months | 0.116726E+12 | 200003.49 | 0.427588E+11 | 70029.61 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.203890E+11 | 0.633936E+10 | 0.593559E+11 | 0.983453E+09 | 0.328935E+10 | 12379742.02 | 0.239197E+11 | 2160111.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179306E+11 | 0.494283E+10 | 0.537310E+11 | 0.889428E+09 | 0.301178E+10 | 11196021.66 | 0.135311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208884E+11 | 0.444618E+10 | 0.617796E+11 | 0.102913E+10 | 0.352548E+10 | 12675672.10 | 0.109264E+11 | 7017704.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183748E+11 | 0.339694E+10 | 0.572952E+11 | 0.946198E+09 | 0.534762E+10 | 11960507.72 | 0.152262E+10 | 0.160468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196715E+11 | 0.287507E+10 | 0.605677E+11 | 0.100553E+10 | 0.632207E+10 | 12527707.06 | 0.117289E+10 | 0.191621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.195204E+11 | 0.251338E+10 | 0.594895E+11 | 0.989850E+09 | 0.828309E+10 | 12231776.97 | 0.400800E+09 | 0.608520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182730E+11 | 0.270668E+10 | 0.583622E+11 | 0.961641E+09 | 0.935355E+10 | 12256437.81 | 0.144565E+09 | 0.102444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.205081E+11 | 0.320001E+10 | 0.617796E+11 | 0.102891E+10 | 0.100207E+11 | 12675672.10 | 0.126066E+09 | 0.128080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.184955E+11 | 0.386819E+10 | 0.572729E+11 | 0.946020E+09 | 0.766744E+10 | 11960507.72 | 0.386521E+09 | 0.641358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.197158E+11 | 0.502585E+10 | 0.593671E+11 | 0.982866E+09 | 0.419441E+10 | 12379742.02 | 0.346606E+10 | 0.105471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.201452E+11 | 0.583860E+10 | 0.580818E+11 | 0.965247E+09 | 0.321721E+10 | 12059151.09 | 0.118527E+11 | 16253979.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201752E+11 | 0.660206E+10 | 0.583511E+11 | 0.963310E+09 | 0.317494E+10 | 12256437.81 | 0.274472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234087E+12 | 0.517552E+11 | 0.705434E+12 | 0.116916E+11 | 0.674077E+11 | 0.146559E+09 | 0.948965E+11 | 0.401522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.179306E+11 | 0.251338E+10 | 0.537310E+11 | 0.889428E+09 | 0.301178E+10 | 11196021.66 | 0.126066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.208884E+11 | 0.660206E+10 | 0.617796E+11 | 0.102913E+10 | 0.100207E+11 | 12675672.10 | 0.274472E+11 | 0.128080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.311223E+11 | 0.00 | 0.116365E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.243136E+11 | 0.00 | 0.105649E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.213827E+11 | 0.00 | 0.120518E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.497126E+10 | 0.00 | 0.111271E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.281909E+10 | 0.00 | 0.115504E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.200787E+09 | 0.00 | 0.111698E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 17843258.23 | 0.00 | 0.109362E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 14809880.42 | 0.00 | 0.114246E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.476925E+09 | 0.00 | 0.107224E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.593298E+10 | 0.00 | 0.111988E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.173981E+11 | 0.00 | 0.110782E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.303435E+11 | 0.00 | 0.113709E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.138994E+12 | 0.00 | 0.134832E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 14809880.42 | 0.00 | 0.105649E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.311223E+11 | 0.00 | 0.120518E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 25003.79 | 02-JAN-08:09 | 5686.19 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 840.16 | 03-JAN-08:20 | 5799.41 | 02-JAN-07:10 | 6.85 | 02-JAN-07:10 | 158833.83 | 02-JAN-07:10 |
February | 24391.75 | 01-FEB-08:09 | 5686.19 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 839.34 | 01-FEB-08:20 | 3355.86 | 17-FEB-13:50 | 6.85 | 06-FEB-08:09 | 88606.02 | 13-FEB-07:10 |
March | 23338.09 | 15-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 837.94 | 15-MAR-07:19 | 3294.28 | 06-MAR-07:10 | 6.85 | 02-MAR-08:09 | 87738.12 | 06-MAR-07:10 |
April | 22036.26 | 10-APR-07:10 | 5686.19 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 836.21 | 10-APR-07:19 | 17074.96 | 28-APR-15:20 | 6.85 | 03-APR-07:10 | 34960.36 | 03-APR-06:10 |
May | 19903.70 | 04-MAY-07:10 | 3328.83 | 01-MAY-19:19 | 45864.70 | 01-MAY-07:10 | 833.38 | 04-MAY-07:19 | 16512.47 | 22-MAY-15:20 | 6.85 | 05-MAY-11:09 | 17731.71 | 05-MAY-06:10 |
June | 19671.42 | 01-JUN-07:10 | 3328.83 | 01-JUN-19:00 | 45864.70 | 01-JUN-07:10 | 833.07 | 01-JUN-07:19 | 21710.65 | 13-JUN-15:30 | 6.85 | 07-JUN-16:10 | 10827.58 | 08-JUN-06:10 |
July | 19821.26 | 07-JUL-07:10 | 3328.83 | 01-JUL-20:19 | 45864.70 | 03-JUL-07:10 | 833.27 | 07-JUL-07:19 | 20655.55 | 21-JUL-15:30 | 6.85 | 22-JUL-16:10 | 8246.61 | 05-JUL-06:19 |
August | 20442.98 | 22-AUG-07:30 | 5686.19 | 14-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 834.09 | 22-AUG-07:40 | 21194.12 | 14-AUG-15:30 | 6.85 | 19-AUG-16:10 | 7479.71 | 24-AUG-06:10 |
September | 21008.50 | 08-SEP-07:30 | 5686.19 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 834.84 | 08-SEP-07:40 | 19465.47 | 12-SEP-15:09 | 6.85 | 01-SEP-05:10 | 14662.44 | 20-SEP-06:10 |
October | 24948.33 | 31-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 840.08 | 31-OCT-07:19 | 9954.31 | 03-OCT-15:09 | 6.85 | 23-OCT-11:09 | 58295.67 | 23-OCT-06:10 |
November | 25003.79 | 06-NOV-16:49 | 5686.19 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 840.09 | 02-NOV-07:19 | 3557.47 | 27-NOV-07:10 | 6.85 | 03-NOV-11:09 | 100302.51 | 27-NOV-07:10 |
December | 25003.79 | 01-DEC-15:30 | 5686.19 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 840.16 | 28-DEC-08:20 | 4477.71 | 26-DEC-06:19 | 6.85 | 01-DEC-06:19 | 128525.06 | 26-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 19671.42 | 3328.83 | 45864.70 | 833.07 | 3294.28 | 6.85 | 7479.71 | |||||||
Maximum of Months | 25003.79 | 5686.19 | 45864.70 | 840.16 | 21710.65 | 6.85 | 158833.83 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 344.23 | 27-JAN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 716.08 | 31-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17247.42 | 28-APR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28284.65 | 22-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 42856.96 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 40615.08 | 21-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 38050.83 | 14-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29732.68 | 13-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10376.21 | 06-OCT-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1688.04 | 24-NOV-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42856.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 200003.49 | 02-JAN-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 5799.41 | 6.85 | 158833.83 | 0.00 | 0.00 |
February | 127285.91 | 13-FEB-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 3309.65 | 6.85 | 88606.02 | 0.00 | 0.00 |
March | 120117.74 | 06-MAR-07:10 | 7736.05 | 21098.80 | 0.00 | 243.63 | 3294.28 | 6.85 | 87738.12 | 0.00 | 0.00 |
April | 96904.35 | 28-APR-15:20 | 19671.42 | 42072.41 | 0.00 | 831.72 | 17074.96 | 6.85 | 0.00 | 17247.00 | 0.00 |
May | 107054.60 | 22-MAY-15:09 | 19671.42 | 42072.41 | 0.00 | 831.72 | 16488.79 | 6.85 | 0.00 | 27983.41 | 0.00 |
June | 127110.78 | 13-JUN-15:30 | 19671.42 | 42072.41 | 0.00 | 831.72 | 21710.65 | 6.85 | 0.00 | 42817.73 | 0.00 |
July | 123545.79 | 21-JUL-15:39 | 19671.42 | 42072.41 | 0.00 | 831.72 | 20534.18 | 6.85 | 0.00 | 40429.21 | 0.00 |
August | 121594.15 | 14-AUG-15:39 | 19671.42 | 42072.41 | 0.00 | 831.72 | 21054.99 | 6.85 | 0.00 | 37956.76 | 0.00 |
September | 110938.69 | 13-SEP-15:09 | 19671.42 | 42072.41 | 0.00 | 831.72 | 18644.25 | 6.85 | 0.00 | 29712.05 | 0.00 |
October | 96493.29 | 23-OCT-06:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 2827.36 | 6.85 | 58295.67 | 0.00 | 0.00 |
November | 139230.22 | 27-NOV-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 3557.47 | 6.85 | 100302.51 | 0.00 | 0.00 |
December | 168301.34 | 26-DEC-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 4406.03 | 6.85 | 128525.06 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 96493.29 | 7736.05 | 21098.80 | 0.00 | 243.63 | 2827.36 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 200003.49 | 19671.42 | 42072.41 | 5686.19 | 831.72 | 21710.65 | 6.85 | 158833.83 | 42817.73 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 61361.77 | 10-JAN-07:00 | 0.00 | 10166.96 | 31-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 58126.05 | 17-FEB-07:19 | 0.00 | 10175.40 | 22-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 42938.77 | 08-MAR-07:19 | 0.00 | 10162.79 | 01-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 37297.55 | 08-APR-06:10 | 0.00 | 10133.91 | 04-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 27235.08 | 06-MAY-06:10 | 0.00 | 10087.63 | 01-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 12089.53 | 07-JUN-20:00 | 0.00 | 10023.32 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 4504.86 | 03-JUL-20:00 | 0.00 | 9966.47 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 5603.97 | 24-AUG-06:10 | 0.00 | 9934.58 | 09-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 17488.85 | 21-SEP-06:10 | 0.00 | 9964.22 | 28-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 28513.26 | 07-OCT-06:00 | 0.00 | 10025.94 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 49120.34 | 29-NOV-07:19 | 0.00 | 10081.74 | 29-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 51775.88 | 27-DEC-07:30 | 0.00 | 10134.88 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 4504.86 | 0.00 | 9934.58 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 61361.77 | 0.00 | 10175.40 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.11 | 0.17 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.11 | 0.17 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.11 | 0.17 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.58 | 0.33 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 19.28 | 0.67 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
Annual Sum or Average | 1.17 | 18.98 | 1.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.28 | 0.67 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.83 | 18.81 | 3.83 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
February | 1.33 | 18.73 | 1.00 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
March | 0.33 | 19.22 | 0.33 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.00 | 18.81 | 0.83 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
December | 6.00 | 18.74 | 5.00 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
Annual Sum or Average | 13.50 | 18.78 | 11.00 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.00 | 19.22 | 5.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 16.41 | 0.00 | 16.41 | 0.00 | 16.41 | 0.00 | 16.41 |
February | 0.17 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.89 | 1.17 | 27.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.55 | 0.83 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.54 | 3.50 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.82 | 4.33 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.60 | 2.67 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.37 | 1.17 | 27.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 18.08 | 0.17 | 18.43 | 0.00 | 18.43 | 0.00 | 18.43 |
December | 1.33 | 17.77 | 0.67 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
Annual Sum or Average | 3.00 | 17.24 | 0.83 | 17.64 | 13.67 | 25.46 | 13.67 | 26.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 18.08 | 0.67 | 18.43 | 4.33 | 27.89 | 4.33 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 16.52 | 0.00 | 16.52 | 0.00 | 16.52 | 0.00 | 16.52 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.13 | 1.83 | 28.16 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.42 | 0.67 | 27.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.47 | 2.17 | 27.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.64 | 4.33 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.74 | 5.50 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.77 | 5.00 | 27.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.54 | 0.83 | 27.54 |
November | 0.33 | 18.20 | 0.17 | 18.52 | 0.17 | 20.71 | 0.17 | 22.02 |
December | 0.83 | 18.18 | 0.50 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
Annual Sum or Average | 1.83 | 17.58 | 0.67 | 17.96 | 20.67 | 26.66 | 20.50 | 27.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 18.20 | 0.50 | 18.52 | 5.50 | 28.13 | 5.50 | 28.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 16.30 | 0.00 | 16.30 | 0.00 | 16.30 | 0.00 | 16.30 |
February | 0.17 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
March | 0.17 | 19.44 | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.26 | 1.17 | 28.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.87 | 1.67 | 27.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.02 | 2.33 | 27.98 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.10 | 3.33 | 28.13 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.01 | 3.00 | 28.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.63 | 1.83 | 27.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 18.07 | 0.17 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
December | 1.17 | 18.15 | 0.67 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
Annual Sum or Average | 2.83 | 17.50 | 1.00 | 17.92 | 21.33 | 26.47 | 13.33 | 27.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 19.44 | 0.67 | 19.44 | 6.67 | 28.26 | 3.33 | 28.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 19.28 | 2.50 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.27 | 0.17 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
Annual Sum or Average | 3.00 | 19.28 | 2.67 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 19.28 | 2.50 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.54 | 1.00 | 27.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.42 | 0.67 | 27.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.61 | 2.83 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.38 | 1.50 | 27.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 17.14 | 0.00 | 17.14 | 6.00 | 27.24 | 6.00 | 27.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 17.14 | 0.00 | 17.14 | 2.83 | 27.61 | 2.83 | 27.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 55.00 | 18.50 | 55.00 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 |
February | 42.33 | 19.00 | 42.33 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
March | 47.50 | 19.02 | 47.50 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
April | 16.00 | 19.71 | 16.00 | 19.71 | 1.50 | 20.07 | 1.50 | 20.40 |
May | 8.50 | 20.10 | 8.50 | 20.10 | 0.00 | 20.10 | 0.00 | 20.10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.44 | 1.00 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.48 | 2.83 | 27.48 |
September | 0.17 | 20.39 | 0.17 | 20.39 | 3.83 | 26.95 | 3.83 | 27.23 |
October | 15.67 | 19.77 | 15.67 | 19.77 | 1.00 | 20.01 | 1.00 | 20.23 |
November | 35.83 | 19.19 | 35.83 | 19.19 | 0.17 | 19.21 | 0.17 | 19.23 |
December | 56.00 | 18.65 | 56.00 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
Annual Sum or Average | 277.00 | 18.98 | 277.00 | 18.98 | 10.33 | 19.13 | 10.33 | 19.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 56.00 | 20.39 | 56.00 | 20.39 | 3.83 | 27.48 | 3.83 | 27.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.25 | 0.17 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.87 | 0.83 | 27.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.60 | 0.50 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.71 | 0.83 | 27.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.73 | 2.33 | 27.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.60 | 1.83 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.43 | 0.67 | 27.43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 18.25 | 0.17 | 18.64 | 13.00 | 27.35 | 7.00 | 27.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 18.25 | 0.17 | 18.64 | 4.83 | 27.87 | 2.33 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 19.35 | 1.17 | 19.51 | 0.00 | 19.51 | 0.00 | 19.51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.14 | 0.50 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
Annual Sum or Average | 1.83 | 19.29 | 1.67 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 19.35 | 1.17 | 19.51 | 0.00 | 19.51 | 0.00 | 19.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.18 | 0.17 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.04 | 1.17 | 28.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.59 | 1.67 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.70 | 2.67 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.81 | 4.67 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.63 | 3.83 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.53 | 2.33 | 27.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.09 | 0.17 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
Annual Sum or Average | 0.50 | 18.48 | 0.33 | 18.78 | 16.33 | 27.27 | 16.33 | 27.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.09 | 0.17 | 19.09 | 4.67 | 28.04 | 4.67 | 28.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.11 | 1.83 | 28.11 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.40 | 0.83 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.40 | 1.67 | 27.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.56 | 4.17 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.71 | 5.17 | 27.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.77 | 5.50 | 27.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.65 | 1.17 | 27.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.38 | 0.50 | 27.38 |
December | 0.17 | 19.29 | 0.17 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
Annual Sum or Average | 0.33 | 18.25 | 0.17 | 18.60 | 20.83 | 27.47 | 20.83 | 27.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.29 | 0.17 | 19.29 | 5.50 | 28.11 | 5.50 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.16 | 0.17 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.16 | 1.17 | 28.16 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.84 | 1.67 | 27.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.01 | 1.83 | 27.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.02 | 3.17 | 28.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.94 | 2.83 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.57 | 2.17 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.07 | 0.17 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
Annual Sum or Average | 0.50 | 18.47 | 0.33 | 18.76 | 20.83 | 27.58 | 12.83 | 27.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.07 | 0.17 | 19.07 | 6.33 | 28.16 | 3.17 | 28.16 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 487.67 | 23.27 | 20.83 | 23.14 | 20.83 | 23.03 |
February | 448.17 | 23.68 | 0.00 | 23.68 | 0.00 | 23.68 |
March | 498.17 | 23.77 | 0.00 | 23.77 | 0.00 | 23.77 |
April | 115.50 | 23.96 | 49.33 | 24.45 | 0.00 | 24.45 |
May | 20.17 | 24.00 | 134.00 | 24.93 | 0.00 | 24.93 |
June | 0.00 | 0.00 | 306.00 | 24.56 | 0.00 | 24.56 |
July | 0.00 | 0.00 | 382.50 | 24.54 | 0.00 | 24.54 |
August | 0.00 | 0.00 | 376.67 | 24.44 | 0.00 | 24.44 |
September | 0.00 | 0.00 | 267.50 | 24.59 | 0.00 | 24.59 |
October | 136.33 | 23.84 | 56.33 | 24.25 | 0.00 | 24.25 |
November | 360.33 | 23.73 | 0.00 | 23.73 | 0.00 | 23.73 |
December | 497.00 | 23.38 | 0.00 | 23.38 | 0.00 | 23.38 |
Annual Sum or Average | 2563.33 | 23.59 | 1593.17 | 23.97 | 20.83 | 23.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.14 | 0.00 | 23.03 |
Maximum of Months | 498.17 | 24.00 | 382.50 | 24.93 | 20.83 | 24.93 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.80 | 53.17 | 21.65 | 53.17 | 21.52 |
February | 454.00 | 22.17 | 2.33 | 22.16 | 2.33 | 22.15 |
March | 514.00 | 22.50 | 1.50 | 22.49 | 1.50 | 22.48 |
April | 340.83 | 23.58 | 5.00 | 23.60 | 0.00 | 23.60 |
May | 217.50 | 23.58 | 28.50 | 23.69 | 0.00 | 23.69 |
June | 48.67 | 23.67 | 171.33 | 24.25 | 0.00 | 24.25 |
July | 40.00 | 23.57 | 252.33 | 24.25 | 0.00 | 24.25 |
August | 6.50 | 23.71 | 232.17 | 24.31 | 0.00 | 24.31 |
September | 103.33 | 23.55 | 106.83 | 23.98 | 0.00 | 23.98 |
October | 420.67 | 23.12 | 0.00 | 23.12 | 0.00 | 23.12 |
November | 489.00 | 22.40 | 3.50 | 22.39 | 3.50 | 22.38 |
December | 497.00 | 21.59 | 75.33 | 21.47 | 75.33 | 21.38 |
Annual Sum or Average | 3633.50 | 22.52 | 932.00 | 22.78 | 135.83 | 22.72 |
Minimum of Months | 6.50 | 21.59 | 0.00 | 21.47 | 0.00 | 21.38 |
Maximum of Months | 514.00 | 23.71 | 252.33 | 24.31 | 75.33 | 24.31 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.04 | 205.50 | 20.82 | 205.50 | 20.69 |
February | 454.00 | 21.30 | 113.00 | 21.08 | 113.00 | 20.93 |
March | 514.00 | 21.70 | 61.83 | 21.56 | 61.83 | 21.45 |
April | 393.83 | 23.12 | 0.50 | 23.12 | 0.00 | 23.12 |
May | 325.50 | 23.26 | 28.33 | 23.33 | 0.00 | 23.33 |
June | 132.00 | 23.39 | 130.33 | 23.81 | 0.00 | 23.81 |
July | 114.17 | 23.39 | 217.00 | 23.97 | 0.00 | 23.97 |
August | 100.83 | 23.42 | 182.67 | 23.92 | 0.00 | 23.92 |
September | 240.50 | 23.25 | 67.83 | 23.45 | 0.00 | 23.45 |
October | 479.33 | 22.35 | 9.33 | 22.31 | 9.33 | 22.27 |
November | 489.00 | 21.46 | 91.67 | 21.29 | 91.67 | 21.16 |
December | 497.00 | 20.83 | 233.33 | 20.62 | 233.33 | 20.51 |
Annual Sum or Average | 4242.17 | 22.00 | 1341.33 | 22.03 | 714.67 | 21.83 |
Minimum of Months | 100.83 | 20.83 | 0.50 | 20.62 | 0.00 | 20.51 |
Maximum of Months | 514.00 | 23.42 | 233.33 | 23.97 | 233.33 | 23.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.31 | 359.17 | 20.18 | 359.17 | 20.12 |
February | 454.00 | 20.44 | 281.17 | 20.27 | 281.17 | 20.20 |
March | 514.00 | 20.93 | 225.67 | 20.75 | 225.67 | 20.65 |
April | 417.17 | 22.30 | 46.17 | 22.14 | 41.67 | 21.99 |
May | 391.17 | 22.61 | 38.33 | 22.67 | 7.50 | 22.63 |
June | 189.33 | 22.99 | 140.00 | 23.50 | 0.00 | 23.50 |
July | 158.33 | 23.07 | 198.50 | 23.70 | 0.00 | 23.70 |
August | 200.17 | 23.05 | 164.83 | 23.52 | 0.00 | 23.52 |
September | 325.83 | 22.58 | 47.33 | 22.76 | 0.67 | 22.75 |
October | 498.17 | 21.41 | 99.83 | 21.19 | 99.83 | 21.03 |
November | 489.00 | 20.56 | 262.50 | 20.37 | 262.50 | 20.28 |
December | 497.00 | 20.10 | 415.33 | 20.02 | 415.33 | 19.99 |
Annual Sum or Average | 4636.17 | 21.37 | 2278.83 | 21.28 | 1693.50 | 21.03 |
Minimum of Months | 158.33 | 20.10 | 38.33 | 20.02 | 0.00 | 19.99 |
Maximum of Months | 514.00 | 23.07 | 415.33 | 23.70 | 415.33 | 23.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.47 | 330.00 | 20.30 | 330.00 | 20.22 |
February | 454.00 | 20.73 | 237.83 | 20.50 | 237.83 | 20.39 |
March | 514.00 | 21.15 | 188.50 | 20.93 | 188.50 | 20.80 |
April | 278.67 | 22.54 | 78.50 | 22.70 | 26.50 | 22.60 |
May | 236.33 | 22.72 | 125.33 | 23.26 | 5.50 | 23.25 |
June | 138.67 | 23.30 | 256.00 | 23.98 | 10.00 | 24.05 |
July | 109.83 | 23.79 | 307.67 | 24.32 | 18.00 | 24.43 |
August | 128.83 | 23.47 | 295.50 | 24.08 | 11.00 | 24.15 |
September | 195.50 | 22.75 | 190.67 | 23.59 | 1.83 | 23.60 |
October | 440.17 | 21.55 | 81.83 | 21.36 | 77.00 | 21.19 |
November | 489.00 | 20.72 | 219.00 | 20.49 | 219.00 | 20.37 |
December | 497.00 | 20.19 | 384.50 | 20.07 | 384.50 | 20.02 |
Annual Sum or Average | 3984.00 | 21.38 | 2695.33 | 21.65 | 1509.67 | 21.39 |
Minimum of Months | 109.83 | 20.19 | 78.50 | 20.07 | 1.83 | 20.02 |
Maximum of Months | 514.00 | 23.79 | 384.50 | 24.32 | 384.50 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 466.67 | 20.85 | 271.33 | 20.62 | 266.00 | 20.49 |
February | 408.67 | 21.09 | 199.67 | 20.87 | 186.83 | 20.70 |
March | 497.17 | 21.31 | 177.33 | 21.06 | 177.33 | 20.91 |
April | 286.33 | 22.42 | 129.83 | 22.73 | 39.50 | 22.62 |
May | 289.00 | 22.49 | 127.67 | 22.97 | 13.67 | 22.89 |
June | 186.00 | 23.03 | 219.17 | 23.72 | 7.17 | 23.77 |
July | 153.17 | 23.37 | 256.83 | 24.04 | 17.67 | 24.16 |
August | 162.17 | 23.51 | 266.67 | 24.02 | 21.50 | 24.16 |
September | 216.83 | 22.99 | 217.67 | 23.73 | 17.50 | 23.86 |
October | 395.50 | 21.68 | 124.67 | 21.81 | 64.33 | 21.65 |
November | 456.67 | 21.05 | 194.33 | 20.83 | 183.67 | 20.66 |
December | 487.83 | 20.55 | 339.17 | 20.34 | 339.17 | 20.25 |
Annual Sum or Average | 4006.00 | 21.65 | 2524.33 | 21.89 | 1334.33 | 21.66 |
Minimum of Months | 153.17 | 20.55 | 124.67 | 20.34 | 7.17 | 20.25 |
Maximum of Months | 497.17 | 23.51 | 339.17 | 24.04 | 339.17 | 24.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.83 | 20.48 | 329.67 | 20.29 | 329.67 | 20.21 |
February | 443.67 | 20.75 | 239.00 | 20.50 | 239.00 | 20.37 |
March | 505.83 | 21.07 | 203.00 | 20.85 | 203.00 | 20.73 |
April | 346.00 | 22.37 | 99.33 | 22.48 | 42.67 | 22.35 |
May | 316.00 | 22.61 | 120.00 | 23.01 | 16.00 | 23.00 |
June | 174.67 | 23.16 | 231.50 | 23.81 | 10.17 | 23.89 |
July | 140.50 | 23.32 | 274.50 | 24.01 | 15.83 | 24.12 |
August | 161.67 | 23.33 | 236.67 | 23.88 | 14.67 | 23.99 |
September | 268.33 | 22.69 | 137.17 | 23.27 | 7.50 | 23.33 |
October | 455.00 | 21.45 | 105.83 | 21.34 | 86.17 | 21.17 |
November | 485.67 | 20.70 | 231.33 | 20.47 | 231.33 | 20.35 |
December | 497.00 | 20.16 | 397.67 | 20.05 | 397.67 | 20.01 |
Annual Sum or Average | 4295.17 | 21.42 | 2605.67 | 21.57 | 1593.67 | 21.33 |
Minimum of Months | 140.50 | 20.16 | 99.33 | 20.05 | 7.50 | 20.01 |
Maximum of Months | 505.83 | 23.33 | 397.67 | 24.01 | 397.67 | 24.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.60 | 313.83 | 20.47 | 313.83 | 20.42 |
February | 454.00 | 20.73 | 237.17 | 20.60 | 237.17 | 20.54 |
March | 514.00 | 21.05 | 166.00 | 20.93 | 166.00 | 20.85 |
April | 477.00 | 22.42 | 11.67 | 22.37 | 11.67 | 22.33 |
May | 442.17 | 22.85 | 0.83 | 22.85 | 0.00 | 22.85 |
June | 219.83 | 23.32 | 77.00 | 23.53 | 0.00 | 23.53 |
July | 160.00 | 23.42 | 140.67 | 23.75 | 0.00 | 23.75 |
August | 209.33 | 23.36 | 73.33 | 23.53 | 0.00 | 23.53 |
September | 353.50 | 23.05 | 20.33 | 23.11 | 0.00 | 23.11 |
October | 502.00 | 21.99 | 10.83 | 21.95 | 10.83 | 21.92 |
November | 489.00 | 21.08 | 122.17 | 20.95 | 122.17 | 20.86 |
December | 497.00 | 20.54 | 344.67 | 20.45 | 344.67 | 20.41 |
Annual Sum or Average | 4819.83 | 21.75 | 1518.50 | 21.60 | 1206.33 | 21.40 |
Minimum of Months | 160.00 | 20.54 | 0.83 | 20.45 | 0.00 | 20.41 |
Maximum of Months | 514.00 | 23.42 | 344.67 | 23.75 | 344.67 | 23.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.78 | 269.00 | 20.63 | 269.00 | 20.56 |
February | 454.00 | 21.05 | 167.00 | 20.88 | 167.00 | 20.78 |
March | 514.00 | 21.26 | 127.67 | 21.11 | 127.67 | 21.01 |
April | 301.33 | 22.98 | 34.33 | 23.14 | 3.83 | 23.13 |
May | 225.83 | 23.15 | 112.00 | 23.61 | 0.00 | 23.61 |
June | 107.33 | 23.44 | 232.50 | 24.09 | 1.00 | 24.10 |
July | 49.17 | 24.25 | 324.33 | 24.47 | 10.83 | 24.54 |
August | 60.17 | 23.72 | 315.83 | 24.24 | 3.83 | 24.27 |
September | 130.83 | 23.35 | 206.17 | 24.03 | 0.17 | 24.04 |
October | 422.83 | 22.21 | 11.67 | 22.23 | 5.50 | 22.21 |
November | 489.00 | 21.29 | 83.67 | 21.17 | 83.67 | 21.07 |
December | 497.00 | 20.63 | 310.17 | 20.51 | 310.17 | 20.45 |
Annual Sum or Average | 3753.50 | 21.66 | 2194.33 | 22.03 | 982.67 | 21.81 |
Minimum of Months | 49.17 | 20.63 | 11.67 | 20.51 | 0.00 | 20.45 |
Maximum of Months | 514.00 | 24.25 | 324.33 | 24.47 | 310.17 | 24.54 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 490.17 | 20.81 | 225.67 | 20.57 | 222.83 | 20.43 |
February | 434.00 | 21.08 | 118.50 | 20.87 | 115.17 | 20.70 |
March | 514.00 | 20.90 | 153.67 | 20.70 | 153.67 | 20.57 |
April | 351.33 | 22.30 | 67.33 | 22.52 | 19.50 | 22.47 |
May | 361.50 | 22.32 | 64.67 | 22.66 | 3.00 | 22.64 |
June | 257.33 | 22.66 | 149.33 | 23.29 | 0.00 | 23.29 |
July | 142.00 | 22.92 | 229.00 | 23.85 | 4.17 | 23.89 |
August | 116.50 | 23.04 | 281.33 | 23.97 | 8.33 | 24.03 |
September | 147.33 | 23.02 | 240.33 | 23.95 | 11.17 | 24.03 |
October | 382.67 | 21.91 | 67.17 | 22.18 | 12.00 | 22.15 |
November | 467.67 | 21.21 | 87.50 | 21.11 | 78.67 | 20.96 |
December | 496.17 | 20.57 | 299.17 | 20.37 | 299.17 | 20.29 |
Annual Sum or Average | 4160.67 | 21.55 | 1983.67 | 21.84 | 927.67 | 21.63 |
Minimum of Months | 116.50 | 20.57 | 64.67 | 20.37 | 0.00 | 20.29 |
Maximum of Months | 514.00 | 23.04 | 299.17 | 23.97 | 299.17 | 24.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.77 | 274.83 | 20.61 | 274.83 | 20.53 |
February | 453.17 | 21.12 | 159.67 | 20.92 | 159.67 | 20.80 |
March | 512.33 | 21.22 | 138.50 | 21.07 | 138.50 | 20.97 |
April | 361.83 | 22.78 | 39.50 | 22.90 | 6.83 | 22.89 |
May | 298.33 | 23.08 | 87.00 | 23.41 | 0.50 | 23.41 |
June | 106.00 | 23.52 | 227.83 | 24.07 | 3.33 | 24.10 |
July | 81.50 | 23.81 | 318.00 | 24.26 | 10.33 | 24.32 |
August | 79.50 | 23.79 | 271.33 | 24.17 | 7.67 | 24.23 |
September | 196.33 | 23.27 | 146.83 | 23.75 | 1.33 | 23.76 |
October | 453.00 | 22.20 | 24.33 | 22.25 | 7.17 | 22.22 |
November | 488.33 | 21.27 | 91.33 | 21.13 | 91.33 | 21.03 |
December | 497.00 | 20.57 | 331.33 | 20.47 | 331.33 | 20.42 |
Annual Sum or Average | 4029.33 | 21.73 | 2110.50 | 21.98 | 1032.83 | 21.77 |
Minimum of Months | 79.50 | 20.57 | 24.33 | 20.47 | 0.50 | 20.42 |
Maximum of Months | 512.33 | 23.81 | 331.33 | 24.26 | 331.33 | 24.32 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.68 | 282.17 | 20.51 | 282.17 | 20.44 |
February | 454.00 | 20.87 | 183.67 | 20.69 | 183.67 | 20.59 |
March | 514.00 | 21.36 | 101.50 | 21.21 | 101.50 | 21.10 |
April | 406.83 | 22.82 | 9.50 | 22.82 | 4.83 | 22.79 |
May | 345.00 | 23.08 | 26.50 | 23.15 | 0.00 | 23.15 |
June | 137.33 | 23.41 | 149.33 | 23.81 | 0.00 | 23.81 |
July | 95.00 | 23.43 | 216.17 | 23.97 | 0.00 | 23.97 |
August | 130.83 | 23.40 | 175.33 | 23.78 | 0.00 | 23.78 |
September | 275.33 | 23.06 | 55.50 | 23.23 | 0.00 | 23.23 |
October | 490.67 | 22.05 | 17.17 | 21.99 | 17.17 | 21.93 |
November | 489.00 | 21.05 | 131.83 | 20.89 | 131.83 | 20.79 |
December | 497.00 | 20.47 | 325.83 | 20.35 | 325.83 | 20.30 |
Annual Sum or Average | 4337.00 | 21.73 | 1674.50 | 21.72 | 1047.00 | 21.50 |
Minimum of Months | 95.00 | 20.47 | 9.50 | 20.35 | 0.00 | 20.30 |
Maximum of Months | 514.00 | 23.43 | 325.83 | 23.97 | 325.83 | 23.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.78 | 216.50 | 20.58 | 216.50 | 20.49 |
February | 385.00 | 21.13 | 136.67 | 20.92 | 136.67 | 20.80 |
March | 432.83 | 21.51 | 82.17 | 21.33 | 82.17 | 21.20 |
April | 236.83 | 22.97 | 53.50 | 23.26 | 6.50 | 23.29 |
May | 187.67 | 23.13 | 109.17 | 23.68 | 3.67 | 23.72 |
June | 108.50 | 23.75 | 211.67 | 24.23 | 10.33 | 24.31 |
July | 56.50 | 24.55 | 261.67 | 24.63 | 17.83 | 24.75 |
August | 75.83 | 24.03 | 239.33 | 24.34 | 13.17 | 24.45 |
September | 147.33 | 23.33 | 158.00 | 24.00 | 7.67 | 24.08 |
October | 371.50 | 22.09 | 26.00 | 22.11 | 14.17 | 22.04 |
November | 417.00 | 21.18 | 107.50 | 21.00 | 107.50 | 20.88 |
December | 422.00 | 20.48 | 272.83 | 20.32 | 272.83 | 20.25 |
Annual Sum or Average | 3268.00 | 21.73 | 1875.00 | 22.06 | 889.00 | 21.85 |
Minimum of Months | 56.50 | 20.48 | 26.00 | 20.32 | 3.67 | 20.25 |
Maximum of Months | 432.83 | 24.55 | 272.83 | 24.63 | 272.83 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 457.50 | 21.26 | 178.33 | 21.06 | 171.17 | 20.91 |
February | 391.17 | 21.50 | 115.83 | 21.42 | 95.17 | 21.25 |
March | 490.83 | 21.77 | 74.17 | 21.60 | 74.17 | 21.46 |
April | 259.00 | 22.92 | 101.17 | 23.36 | 8.17 | 23.41 |
May | 240.00 | 22.94 | 120.67 | 23.46 | 0.50 | 23.47 |
June | 145.67 | 23.43 | 234.33 | 23.97 | 4.00 | 24.00 |
July | 101.67 | 23.85 | 283.50 | 24.29 | 15.83 | 24.39 |
August | 107.83 | 24.02 | 294.67 | 24.26 | 20.17 | 24.38 |
September | 161.00 | 23.58 | 239.50 | 24.12 | 20.33 | 24.26 |
October | 369.33 | 22.31 | 85.83 | 22.61 | 13.17 | 22.59 |
November | 440.83 | 21.55 | 92.17 | 21.51 | 74.33 | 21.37 |
December | 481.33 | 20.96 | 245.83 | 20.73 | 245.83 | 20.61 |
Annual Sum or Average | 3646.17 | 22.03 | 2066.00 | 22.41 | 742.83 | 22.25 |
Minimum of Months | 101.67 | 20.96 | 74.17 | 20.73 | 0.50 | 20.61 |
Maximum of Months | 490.83 | 24.02 | 294.67 | 24.29 | 245.83 | 24.39 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.17 | 20.86 | 241.00 | 20.65 | 241.00 | 20.54 |
February | 435.83 | 21.16 | 141.00 | 20.93 | 141.00 | 20.80 |
March | 503.67 | 21.51 | 92.50 | 21.34 | 92.00 | 21.22 |
April | 323.17 | 22.93 | 66.50 | 23.16 | 8.50 | 23.17 |
May | 261.17 | 23.10 | 112.50 | 23.50 | 5.67 | 23.56 |
June | 118.50 | 23.60 | 247.33 | 24.08 | 9.00 | 24.15 |
July | 96.67 | 23.87 | 308.00 | 24.26 | 15.17 | 24.36 |
August | 102.00 | 23.83 | 271.00 | 24.16 | 14.00 | 24.26 |
September | 208.67 | 23.20 | 154.50 | 23.71 | 7.67 | 23.78 |
October | 440.00 | 22.09 | 39.83 | 22.13 | 17.00 | 22.07 |
November | 482.50 | 21.20 | 115.67 | 21.02 | 115.67 | 20.90 |
December | 497.00 | 20.54 | 308.00 | 20.38 | 308.00 | 20.32 |
Annual Sum or Average | 3968.33 | 21.78 | 2097.83 | 22.05 | 974.67 | 21.85 |
Minimum of Months | 96.67 | 20.54 | 39.83 | 20.38 | 5.67 | 20.32 |
Maximum of Months | 503.67 | 23.87 | 308.00 | 24.26 | 308.00 | 24.36 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.28978 | 33.16473 | 0.04161 | 5.95884 |
February | 454.00000 | 23.68895 | 31.48274 | 0.14427 | 5.63729 |
March | 514.00000 | 23.78597 | 30.78574 | 0.17212 | 5.80082 |
April | 485.00000 | 24.27538 | 29.55328 | 0.33499 | 7.52425 |
May | 508.00000 | 24.34074 | 34.82518 | -0.4736 | 10.05652 |
June | 496.00000 | 24.35236 | 41.80053 | -0.3907 | 8.57640 |
July | 497.00000 | 24.41658 | 43.24087 | -0.3567 | 8.06766 |
August | 514.00000 | 24.32635 | 43.18349 | -0.3761 | 8.27455 |
September | 485.00000 | 24.33857 | 41.13538 | -0.4057 | 8.80200 |
October | 502.00000 | 24.19605 | 36.92721 | 0.34731 | 7.69530 |
November | 489.00000 | 23.86939 | 34.70368 | 0.21835 | 6.26377 |
December | 497.00000 | 23.37961 | 30.76193 | 0.04862 | 5.43571 |
Annual Sum or Average | 5943.00000 | 24.02337 | 36.00156 | -0.0604 | 7.35377 |
Minimum of Months | 454.00000 | 23.28978 | 29.55328 | -0.4736 | 5.43571 |
Maximum of Months | 514.00000 | 24.41658 | 43.24087 | 0.34731 | 10.05652 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.80292 | 36.14589 | -0.2913 | 7.80374 |
February | 454.00000 | 22.17150 | 34.99643 | -0.1974 | 6.36729 |
March | 514.00000 | 22.49606 | 34.27222 | -0.1192 | 5.83759 |
April | 485.00000 | 23.78176 | 31.37746 | 0.20927 | 6.28893 |
May | 508.00000 | 23.91687 | 36.66144 | -0.6326 | 13.87283 |
June | 496.00000 | 24.11288 | 43.20927 | -0.4936 | 10.35116 |
July | 497.00000 | 24.15959 | 44.47115 | -0.4632 | 9.78517 |
August | 514.00000 | 24.13759 | 44.36417 | -0.4666 | 9.73828 |
September | 485.00000 | 23.99918 | 42.60445 | -0.5451 | 11.53336 |
October | 502.00000 | 23.27595 | 40.04362 | 0.12420 | 5.89839 |
November | 489.00000 | 22.40206 | 38.68712 | -0.1174 | 6.02111 |
December | 497.00000 | 21.58703 | 34.25774 | -0.3536 | 8.27259 |
Annual Sum or Average | 5943.00000 | 23.15991 | 38.45498 | -0.2805 | 8.50069 |
Minimum of Months | 454.00000 | 21.58703 | 31.37746 | -0.6326 | 5.83759 |
Maximum of Months | 514.00000 | 24.15959 | 44.47115 | 0.20927 | 13.87283 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.04422 | 35.87918 | -0.4982 | 11.70283 |
February | 454.00000 | 21.29608 | 36.56612 | -0.4198 | 9.76379 |
March | 514.00000 | 21.70357 | 35.63177 | -0.3176 | 7.99142 |
April | 485.00000 | 23.29496 | 32.34392 | 0.09031 | 6.12718 |
May | 508.00000 | 23.54980 | 37.62165 | -0.7633 | 18.43868 |
June | 496.00000 | 23.92589 | 43.79464 | -0.5604 | 12.15092 |
July | 497.00000 | 23.98986 | 44.95361 | -0.5222 | 11.29398 |
August | 514.00000 | 23.96024 | 44.81227 | -0.5333 | 11.33523 |
September | 485.00000 | 23.65414 | 43.88863 | -0.6719 | 15.31519 |
October | 502.00000 | 22.42187 | 42.06695 | -0.0863 | 6.28381 |
November | 489.00000 | 21.46005 | 40.56878 | -0.3552 | 8.69859 |
December | 497.00000 | 20.83169 | 35.53807 | -0.5608 | 12.74103 |
Annual Sum or Average | 5943.00000 | 22.60318 | 39.49646 | -0.4343 | 11.00256 |
Minimum of Months | 454.00000 | 20.83169 | 32.34392 | -0.7633 | 6.12718 |
Maximum of Months | 514.00000 | 23.98986 | 44.95361 | 0.09031 | 18.43868 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.31474 | 38.25588 | -0.7092 | 17.48201 |
February | 454.00000 | 20.44027 | 38.72167 | -0.6532 | 15.54199 |
March | 514.00000 | 20.92921 | 38.12756 | -0.5159 | 11.66827 |
April | 485.00000 | 22.54907 | 34.50512 | -0.0816 | 7.24172 |
May | 508.00000 | 22.92986 | 39.44910 | -0.9591 | 26.83653 |
June | 496.00000 | 23.66149 | 44.75861 | -0.6347 | 15.02352 |
July | 497.00000 | 23.78556 | 45.61886 | -0.5754 | 13.37334 |
August | 514.00000 | 23.65304 | 46.12428 | -0.6310 | 14.69536 |
September | 485.00000 | 23.04572 | 45.59503 | -0.8803 | 23.67947 |
October | 502.00000 | 21.43352 | 45.53761 | -0.3209 | 8.76658 |
November | 489.00000 | 20.55607 | 42.88700 | -0.5949 | 13.88126 |
December | 497.00000 | 20.10434 | 37.10951 | -0.7789 | 19.81391 |
Annual Sum or Average | 5943.00000 | 21.96129 | 41.41446 | -0.6118 | 15.67343 |
Minimum of Months | 454.00000 | 20.10434 | 34.50512 | -0.9591 | 7.24172 |
Maximum of Months | 514.00000 | 23.78556 | 46.12428 | -0.0816 | 26.83653 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.47395 | 38.97926 | -0.6560 | 15.96700 |
February | 454.00000 | 20.73397 | 39.16560 | -0.5684 | 13.51768 |
March | 514.00000 | 21.14730 | 38.79205 | -0.4528 | 10.73134 |
April | 485.00000 | 23.21079 | 32.62065 | 0.12048 | 7.83366 |
May | 508.00000 | 23.49585 | 37.88950 | -0.7103 | 18.97705 |
June | 496.00000 | 23.92349 | 43.74225 | -0.4783 | 12.20472 |
July | 497.00000 | 24.15566 | 44.34793 | -0.3789 | 10.45655 |
August | 514.00000 | 24.00075 | 44.64175 | -0.4317 | 11.16987 |
September | 485.00000 | 23.66276 | 43.37020 | -0.6073 | 16.14357 |
October | 502.00000 | 21.86221 | 45.03816 | -0.2053 | 8.35536 |
November | 489.00000 | 20.71960 | 43.59199 | -0.5442 | 12.75162 |
December | 497.00000 | 20.18676 | 37.92665 | -0.7472 | 18.73672 |
Annual Sum or Average | 5943.00000 | 22.30822 | 40.86310 | -0.4720 | 13.06941 |
Minimum of Months | 454.00000 | 20.18676 | 32.62065 | -0.7472 | 7.83366 |
Maximum of Months | 514.00000 | 24.15566 | 45.03816 | 0.12048 | 18.97705 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.09044 | 36.43697 | -0.4942 | 13.67524 |
February | 454.00000 | 21.40198 | 36.36750 | -0.3933 | 11.98741 |
March | 514.00000 | 21.39613 | 37.09794 | -0.3932 | 10.39604 |
April | 485.00000 | 23.13350 | 32.06347 | 0.10909 | 8.53525 |
May | 508.00000 | 23.24611 | 37.96027 | -0.8044 | 23.09773 |
June | 496.00000 | 23.72377 | 44.03579 | -0.5689 | 14.64416 |
July | 497.00000 | 23.93168 | 44.71365 | -0.4686 | 12.74955 |
August | 514.00000 | 23.90244 | 44.52591 | -0.4553 | 12.45814 |
September | 485.00000 | 23.65506 | 42.68704 | -0.5634 | 16.75165 |
October | 502.00000 | 22.20102 | 42.78468 | -0.1030 | 8.72943 |
November | 489.00000 | 21.27116 | 41.17983 | -0.4034 | 11.51688 |
December | 497.00000 | 20.61506 | 36.00089 | -0.6360 | 16.33423 |
Annual Sum or Average | 5943.00000 | 22.47048 | 39.68810 | -0.4327 | 13.42490 |
Minimum of Months | 454.00000 | 20.61506 | 32.06347 | -0.8044 | 8.53525 |
Maximum of Months | 514.00000 | 23.93168 | 44.71365 | 0.10909 | 23.09773 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.49244 | 38.90889 | -0.6547 | 16.30846 |
February | 454.00000 | 20.82877 | 38.72658 | -0.5462 | 14.00479 |
March | 514.00000 | 21.11523 | 38.71584 | -0.4614 | 11.17092 |
April | 485.00000 | 22.87260 | 33.86110 | 0.03273 | 8.12790 |
May | 508.00000 | 23.19369 | 38.86810 | -0.8135 | 23.65710 |
June | 496.00000 | 23.78052 | 44.40955 | -0.5222 | 13.88270 |
July | 497.00000 | 23.92076 | 45.25071 | -0.4519 | 12.54527 |
August | 514.00000 | 23.83231 | 45.55442 | -0.5016 | 13.07526 |
September | 485.00000 | 23.34217 | 44.74542 | -0.7283 | 20.44181 |
October | 502.00000 | 21.70394 | 45.36207 | -0.2431 | 8.68800 |
November | 489.00000 | 20.72141 | 43.50576 | -0.5463 | 13.16856 |
December | 497.00000 | 20.15639 | 37.96785 | -0.7601 | 19.26298 |
Annual Sum or Average | 5943.00000 | 22.17276 | 41.34798 | -0.5170 | 14.53424 |
Minimum of Months | 454.00000 | 20.15639 | 33.86110 | -0.8135 | 8.12790 |
Maximum of Months | 514.00000 | 23.92076 | 45.55442 | 0.03273 | 23.65710 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.59629 | 37.96487 | -0.6233 | 14.30445 |
February | 454.00000 | 20.72631 | 38.50602 | -0.5670 | 12.29280 |
March | 514.00000 | 21.05279 | 37.95334 | -0.4757 | 10.22068 |
April | 485.00000 | 22.44586 | 35.33453 | -0.1125 | 6.32570 |
May | 508.00000 | 22.99524 | 39.83421 | -0.9601 | 25.77283 |
June | 496.00000 | 23.71534 | 45.23866 | -0.6456 | 14.43149 |
July | 497.00000 | 23.86151 | 45.93942 | -0.5751 | 12.45132 |
August | 514.00000 | 23.72757 | 46.55746 | -0.6271 | 13.77480 |
September | 485.00000 | 23.30986 | 45.46444 | -0.8023 | 19.57319 |
October | 502.00000 | 21.98628 | 44.43745 | -0.1747 | 6.50696 |
November | 489.00000 | 21.07764 | 41.98118 | -0.4377 | 9.65530 |
December | 497.00000 | 20.54111 | 36.59648 | -0.6394 | 14.22726 |
Annual Sum or Average | 5943.00000 | 22.17975 | 41.34226 | -0.5543 | 13.31890 |
Minimum of Months | 454.00000 | 20.54111 | 35.33453 | -0.9601 | 6.32570 |
Maximum of Months | 514.00000 | 23.86151 | 46.55746 | -0.1125 | 25.77283 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.78426 | 38.75168 | -0.5633 | 12.77160 |
February | 454.00000 | 21.04573 | 38.98463 | -0.4754 | 10.50528 |
March | 514.00000 | 21.26450 | 38.68374 | -0.4144 | 9.32159 |
April | 485.00000 | 23.44038 | 32.82617 | 0.16167 | 6.97725 |
May | 508.00000 | 23.75918 | 37.58796 | -0.6449 | 15.65290 |
June | 496.00000 | 24.05658 | 43.67005 | -0.4600 | 10.70333 |
July | 497.00000 | 24.29288 | 44.25566 | -0.3551 | 8.99298 |
August | 514.00000 | 24.16063 | 44.47633 | -0.3934 | 9.31786 |
September | 485.00000 | 24.01752 | 42.64087 | -0.4920 | 11.57586 |
October | 502.00000 | 22.51249 | 43.76669 | -0.0363 | 6.52953 |
November | 489.00000 | 21.29494 | 42.64949 | -0.3761 | 8.75669 |
December | 497.00000 | 20.63048 | 37.46974 | -0.6076 | 13.45612 |
Annual Sum or Average | 5943.00000 | 22.61437 | 40.50096 | -0.3888 | 10.38823 |
Minimum of Months | 454.00000 | 20.63048 | 32.82617 | -0.6449 | 6.52953 |
Maximum of Months | 514.00000 | 24.29288 | 44.47633 | 0.16167 | 15.65290 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.89591 | 34.45064 | -0.4947 | 12.46027 |
February | 454.00000 | 21.23176 | 34.82883 | -0.3857 | 10.11723 |
March | 514.00000 | 20.89838 | 35.17072 | -0.4755 | 10.64125 |
April | 485.00000 | 22.84944 | 31.78096 | 0.05069 | 7.44096 |
May | 508.00000 | 22.89864 | 37.89465 | -0.9052 | 25.63170 |
June | 496.00000 | 23.40131 | 44.73803 | -0.6771 | 16.99290 |
July | 497.00000 | 23.84496 | 45.23713 | -0.5065 | 12.45450 |
August | 514.00000 | 23.91550 | 44.84614 | -0.4513 | 11.33444 |
September | 485.00000 | 23.87283 | 41.97426 | -0.4753 | 12.71603 |
October | 502.00000 | 22.46157 | 40.70100 | -0.0054 | 7.47383 |
November | 489.00000 | 21.37777 | 38.75504 | -0.3238 | 8.96565 |
December | 497.00000 | 20.57134 | 33.87604 | -0.5918 | 13.66580 |
Annual Sum or Average | 5943.00000 | 22.35698 | 38.72612 | -0.4389 | 12.53360 |
Minimum of Months | 454.00000 | 20.57134 | 31.78096 | -0.9052 | 7.44096 |
Maximum of Months | 514.00000 | 23.91550 | 45.23713 | 0.05069 | 25.63170 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.77265 | 38.77041 | -0.5675 | 13.09374 |
February | 454.00000 | 21.12045 | 38.74339 | -0.4550 | 10.53241 |
March | 514.00000 | 21.23226 | 38.71257 | -0.4219 | 9.56082 |
April | 485.00000 | 23.13517 | 33.96528 | 0.07846 | 6.80575 |
May | 508.00000 | 23.56065 | 38.28621 | -0.7178 | 18.32253 |
June | 496.00000 | 24.04296 | 43.89518 | -0.4627 | 10.75886 |
July | 497.00000 | 24.15687 | 44.75608 | -0.3961 | 9.67731 |
August | 514.00000 | 24.08328 | 45.01541 | -0.4367 | 10.02103 |
September | 485.00000 | 23.81503 | 43.71729 | -0.5820 | 13.72671 |
October | 502.00000 | 22.39303 | 44.03659 | -0.0664 | 6.54454 |
November | 489.00000 | 21.27432 | 42.64914 | -0.3821 | 9.01456 |
December | 497.00000 | 20.57491 | 37.58781 | -0.6263 | 13.95169 |
Annual Sum or Average | 5943.00000 | 22.52227 | 40.86700 | -0.4206 | 11.01454 |
Minimum of Months | 454.00000 | 20.57491 | 33.96528 | -0.7178 | 6.54454 |
Maximum of Months | 514.00000 | 24.15687 | 45.01541 | 0.07846 | 18.32253 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.67695 | 37.64501 | -0.5860 | 13.59312 |
February | 454.00000 | 20.87118 | 37.99902 | -0.5135 | 11.33451 |
March | 514.00000 | 21.35884 | 37.37532 | -0.3841 | 8.89542 |
April | 485.00000 | 23.02619 | 33.61485 | 0.03736 | 6.23369 |
May | 508.00000 | 23.38064 | 38.41365 | -0.8049 | 20.02672 |
June | 496.00000 | 23.89030 | 44.03587 | -0.5552 | 12.11560 |
July | 497.00000 | 23.98485 | 45.04397 | -0.5068 | 10.96177 |
August | 514.00000 | 23.87206 | 45.48211 | -0.5523 | 11.88096 |
September | 485.00000 | 23.46798 | 44.38094 | -0.7318 | 17.44104 |
October | 502.00000 | 22.09197 | 43.92807 | -0.1466 | 6.63572 |
November | 489.00000 | 21.05480 | 41.89113 | -0.4402 | 9.98335 |
December | 497.00000 | 20.47446 | 36.45781 | -0.6492 | 14.86560 |
Annual Sum or Average | 5943.00000 | 22.35620 | 40.54602 | -0.4868 | 12.00791 |
Minimum of Months | 454.00000 | 20.47446 | 33.61485 | -0.8049 | 6.23369 |
Maximum of Months | 514.00000 | 23.98485 | 45.48211 | 0.03736 | 20.02672 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.77883 | 38.23351 | -0.5522 | 12.94867 |
February | 385.00000 | 21.12858 | 38.09718 | -0.4449 | 10.34276 |
March | 433.00000 | 21.51556 | 38.03664 | -0.3394 | 8.63193 |
April | 410.00000 | 23.49022 | 31.88211 | 0.18564 | 7.39401 |
May | 430.00000 | 23.76912 | 36.79069 | -0.6225 | 15.62569 |
June | 418.00000 | 24.10007 | 42.90424 | -0.4300 | 10.70628 |
July | 422.00000 | 24.34951 | 43.63129 | -0.3304 | 9.36381 |
August | 433.00000 | 24.17066 | 44.04477 | -0.3888 | 9.91356 |
September | 410.00000 | 23.94300 | 42.42544 | -0.5176 | 13.13343 |
October | 427.00000 | 22.36379 | 43.32077 | -0.0720 | 6.88636 |
November | 417.00000 | 21.17834 | 42.35513 | -0.4042 | 9.58242 |
December | 422.00000 | 20.47907 | 37.16233 | -0.6397 | 14.72919 |
Annual Sum or Average | 5034.00000 | 22.61218 | 39.93035 | -0.3803 | 10.77778 |
Minimum of Months | 385.00000 | 20.47907 | 31.88211 | -0.6397 | 6.88636 |
Maximum of Months | 433.00000 | 24.34951 | 44.04477 | 0.18564 | 15.62569 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.52357 | 35.66180 | -0.3593 | 10.65606 |
February | 454.00000 | 21.88916 | 35.47023 | -0.2458 | 9.21792 |
March | 514.00000 | 21.87389 | 36.21663 | -0.2538 | 8.08680 |
April | 485.00000 | 23.51615 | 31.29143 | 0.20752 | 7.92494 |
May | 508.00000 | 23.62778 | 37.02431 | -0.6708 | 17.30287 |
June | 496.00000 | 23.95099 | 43.35798 | -0.4915 | 11.66012 |
July | 497.00000 | 24.13363 | 44.15540 | -0.4016 | 10.27297 |
August | 514.00000 | 24.09862 | 44.01037 | -0.3860 | 10.01400 |
September | 485.00000 | 23.97383 | 41.82620 | -0.4463 | 12.34147 |
October | 502.00000 | 22.79330 | 41.27369 | 0.05589 | 7.49888 |
November | 489.00000 | 21.83960 | 39.98297 | -0.2378 | 8.70595 |
December | 497.00000 | 21.06233 | 35.19741 | -0.4921 | 12.23222 |
Annual Sum or Average | 5943.00000 | 22.86250 | 38.82345 | -0.3119 | 10.50771 |
Minimum of Months | 454.00000 | 21.06233 | 31.29143 | -0.6708 | 7.49888 |
Maximum of Months | 514.00000 | 24.13363 | 44.15540 | 0.20752 | 17.30287 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.87478 | 38.30996 | -0.5283 | 12.64161 |
February | 454.00000 | 21.27451 | 37.92861 | -0.4055 | 10.31754 |
March | 514.00000 | 21.56325 | 37.91833 | -0.3271 | 8.56209 |
April | 485.00000 | 23.33168 | 32.98403 | 0.14688 | 7.32133 |
May | 508.00000 | 23.61071 | 37.85078 | -0.6697 | 17.39717 |
June | 496.00000 | 24.00940 | 43.66054 | -0.4441 | 10.96745 |
July | 497.00000 | 24.12386 | 44.62890 | -0.3841 | 10.07501 |
August | 514.00000 | 24.04266 | 44.90013 | -0.4271 | 10.44232 |
September | 485.00000 | 23.73737 | 43.59117 | -0.5889 | 14.78629 |
October | 502.00000 | 22.34534 | 43.78467 | -0.0731 | 6.87617 |
November | 489.00000 | 21.23993 | 42.46704 | -0.3890 | 9.53607 |
December | 497.00000 | 20.53569 | 37.34804 | -0.6291 | 14.44541 |
Annual Sum or Average | 5943.00000 | 22.56606 | 40.47308 | -0.3941 | 11.12232 |
Minimum of Months | 454.00000 | 20.53569 | 32.98403 | -0.6697 | 6.87617 |
Maximum of Months | 514.00000 | 24.12386 | 44.90013 | 0.14688 | 17.39717 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 7367726.14 | 2160111.88 | 2.39 | 5639614.69 | 1728111.46 | 0.00 | 0.06 | 27-JAN-13:00 | 0.00 | 01-JAN-00:05 | 1177.08 | 27-JAN-13:00 | 903.39 | 27-JAN-13:00 | 278.72 | 27-JAN-13:10 | 344.23 | 27-JAN-13:00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 24050520.97 | 7017704.83 | 6.31 | 20324766.38 | 3725754.59 | 0.00 | 0.16 | 31-MAR-16:07 | 0.00 | 01-MAR-00:10 | 3460.69 | 31-MAR-16:07 | 3377.25 | 31-MAR-16:07 | 341.00 | 24-MAR-16:00 | 987.80 | 31-MAR-16:07 | 0.00 |
April | 0.301857E+10 | 0.809882E+09 | 127.83 | 0.288309E+10 | 0.135481E+09 | 0.00 | 1.00 | 30-APR-14:52 | 0.00 | 01-APR-00:10 | 35189.40 | 30-APR-16:11 | 35189.40 | 30-APR-16:11 | 5127.94 | 28-APR-07:55 | 8073.14 | 30-APR-16:11 | 0.00 |
May | 0.282935E+10 | 0.710442E+09 | 75.81 | 0.240690E+10 | 0.422450E+09 | 0.00 | 1.00 | 22-MAY-12:30 | 0.00 | 01-MAY-00:10 | 41747.13 | 22-MAY-15:10 | 41747.13 | 22-MAY-15:10 | 5443.29 | 23-MAY-15:20 | 9537.63 | 22-MAY-15:10 | 0.00 |
June | 0.884812E+10 | 0.215224E+10 | 152.67 | 0.731675E+10 | 0.153137E+10 | 0.00 | 1.00 | 12-JUN-11:50 | 0.00 | 01-JUN-00:10 | 60043.47 | 13-JUN-16:00 | 54780.16 | 13-JUN-16:00 | 19270.31 | 25-JUN-17:52 | 14624.35 | 13-JUN-16:00 | 0.00 |
July | 0.148365E+11 | 0.367904E+10 | 274.47 | 0.120233E+11 | 0.281321E+10 | 0.00 | 1.00 | 06-JUL-14:00 | 0.00 | 01-JUL-00:10 | 55706.60 | 21-JUL-16:00 | 55706.60 | 21-JUL-16:00 | 12522.56 | 24-JUL-15:20 | 14104.66 | 21-JUL-16:00 | 0.00 |
August | 0.192350E+11 | 0.474924E+10 | 358.69 | 0.152032E+11 | 0.403176E+10 | 0.00 | 1.00 | 07-AUG-15:00 | 0.00 | 01-AUG-00:10 | 55548.97 | 14-AUG-15:50 | 54543.86 | 14-AUG-16:00 | 11639.44 | 18-AUG-15:40 | 13337.10 | 14-AUG-16:00 | 0.00 |
September | 0.973763E+10 | 0.239575E+10 | 200.37 | 0.800780E+10 | 0.172984E+10 | 0.00 | 1.00 | 11-SEP-12:05 | 0.00 | 01-SEP-00:10 | 47263.42 | 13-SEP-15:20 | 42884.99 | 13-SEP-15:30 | 12134.46 | 12-SEP-14:00 | 10780.84 | 13-SEP-15:20 | 0.00 |
October | 0.365363E+10 | 0.906093E+09 | 76.33 | 0.352616E+10 | 0.127466E+09 | 0.00 | 1.00 | 05-OCT-15:20 | 0.00 | 01-OCT-00:10 | 29041.55 | 06-OCT-15:30 | 29041.55 | 06-OCT-15:30 | 2391.52 | 12-OCT-16:01 | 6631.43 | 06-OCT-15:30 | 0.00 |
November | 51244886.14 | 14834918.91 | 9.13 | 45102394.91 | 6142491.23 | 0.00 | 0.15 | 03-NOV-15:20 | 0.00 | 01-NOV-00:10 | 3206.95 | 03-NOV-15:20 | 3013.86 | 03-NOV-15:20 | 704.72 | 24-NOV-12:00 | 917.81 | 03-NOV-15:20 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.622414E+11 | 0.154267E+11 | 1283.99 | 0.514383E+11 | 0.108032E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.192350E+11 | 0.474924E+10 | 358.69 | 0.152032E+11 | 0.403176E+10 | 0.00 | 1.00 | 0.00 | 60043.47 | 55706.60 | 19270.31 | 14624.35 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.162530E+10 | 0.381260E+09 | 53.84 | 0.156242E+10 | 62876659.34 | 0.00 | 1.00 | 28-APR-14:05 | 0.00 | 01-APR-00:10 | 41222.67 | 30-APR-14:52 | 41222.67 | 30-APR-14:52 | 3473.85 | 28-APR-07:55 | 8607.84 | 30-APR-14:52 | 0.00 |
May | 0.251196E+10 | 0.565446E+09 | 66.13 | 0.215682E+10 | 0.355144E+09 | 0.00 | 1.00 | 22-MAY-12:05 | 0.00 | 01-MAY-00:10 | 41151.49 | 22-MAY-15:00 | 41085.29 | 22-MAY-15:00 | 5187.02 | 23-MAY-15:00 | 8593.02 | 22-MAY-15:00 | 0.00 |
June | 0.827283E+10 | 0.182692E+10 | 154.11 | 0.685814E+10 | 0.141468E+10 | 0.00 | 1.00 | 12-JUN-11:50 | 0.00 | 01-JUN-00:10 | 57069.47 | 13-JUN-14:05 | 51544.81 | 13-JUN-15:30 | 15983.20 | 26-JUN-16:00 | 12556.27 | 13-JUN-15:30 | 0.00 |
July | 0.136121E+11 | 0.306467E+10 | 276.93 | 0.110714E+11 | 0.254068E+10 | 0.00 | 1.00 | 06-JUL-13:50 | 0.00 | 01-JUL-00:10 | 51549.32 | 21-JUL-14:05 | 51119.76 | 21-JUL-15:40 | 12264.29 | 24-JUL-14:05 | 11754.07 | 21-JUL-16:00 | 0.00 |
August | 0.171013E+11 | 0.383594E+10 | 359.77 | 0.135473E+11 | 0.355400E+10 | 0.00 | 1.00 | 07-AUG-15:00 | 0.00 | 01-AUG-00:10 | 51977.51 | 14-AUG-15:30 | 50187.87 | 14-AUG-15:40 | 11201.77 | 18-AUG-14:05 | 11258.41 | 14-AUG-15:40 | 0.00 |
September | 0.871265E+10 | 0.194799E+10 | 199.50 | 0.716601E+10 | 0.154664E+10 | 0.00 | 1.00 | 10-SEP-11:32 | 0.00 | 01-SEP-00:10 | 45087.35 | 13-SEP-14:05 | 40488.47 | 13-SEP-14:05 | 11576.42 | 12-SEP-13:00 | 9364.92 | 13-SEP-14:05 | 0.00 |
October | 0.293691E+09 | 74729492.50 | 22.17 | 0.281754E+09 | 11936857.01 | 0.00 | 0.46 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 9520.65 | 07-OCT-15:00 | 9520.65 | 07-OCT-15:00 | 928.65 | 17-OCT-15:00 | 2298.29 | 07-OCT-15:00 | 0.00 |
November | 2383287.08 | 632955.82 | 0.67 | 1577474.37 | 805812.71 | 0.00 | 0.09 | 24-NOV-12:00 | 0.00 | 01-NOV-00:10 | 1790.96 | 24-NOV-12:00 | 1207.23 | 24-NOV-12:00 | 583.73 | 24-NOV-12:00 | 472.70 | 24-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.521323E+11 | 0.116976E+11 | 1133.10 | 0.426455E+11 | 0.948676E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.171013E+11 | 0.383594E+10 | 359.77 | 0.135473E+11 | 0.355400E+10 | 0.00 | 1.00 | 0.00 | 57069.47 | 51544.81 | 15983.20 | 12556.27 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.159044E+10 | 0.413533E+09 | 50.56 | 0.151331E+10 | 77131003.44 | 0.00 | 1.00 | 30-APR-13:42 | 0.00 | 01-APR-00:10 | 37259.78 | 30-APR-15:42 | 37259.78 | 30-APR-15:42 | 2169.19 | 28-APR-07:55 | 8546.85 | 30-APR-15:42 | 0.00 |
May | 0.257969E+10 | 0.640325E+09 | 62.67 | 0.219697E+10 | 0.382714E+09 | 0.00 | 1.00 | 22-MAY-12:30 | 0.00 | 01-MAY-00:10 | 44609.36 | 22-MAY-15:00 | 44609.36 | 22-MAY-15:00 | 5578.67 | 23-MAY-15:00 | 10228.30 | 22-MAY-15:00 | 0.00 |
June | 0.865126E+10 | 0.210604E+10 | 151.29 | 0.715520E+10 | 0.149605E+10 | 0.00 | 1.00 | 12-JUN-12:00 | 0.00 | 01-JUN-00:10 | 65986.57 | 13-JUN-14:40 | 59640.03 | 13-JUN-15:30 | 30824.43 | 25-JUN-17:52 | 15775.27 | 13-JUN-15:30 | 0.00 |
July | 0.140654E+11 | 0.350073E+10 | 273.97 | 0.114365E+11 | 0.262882E+10 | 0.00 | 1.00 | 06-JUL-14:00 | 0.00 | 01-JUL-00:10 | 59381.03 | 21-JUL-15:40 | 59381.03 | 21-JUL-15:40 | 12221.42 | 24-JUL-15:30 | 14894.75 | 21-JUL-15:40 | 0.00 |
August | 0.169694E+11 | 0.422278E+10 | 359.60 | 0.133235E+11 | 0.364593E+10 | 0.00 | 1.00 | 13-AUG-13:13 | 0.00 | 01-AUG-00:10 | 56426.92 | 14-AUG-15:40 | 56426.92 | 14-AUG-15:40 | 11276.37 | 18-AUG-15:30 | 13506.46 | 14-AUG-16:00 | 0.00 |
September | 0.834007E+10 | 0.206984E+10 | 193.28 | 0.679422E+10 | 0.154584E+10 | 0.00 | 1.00 | 11-SEP-12:30 | 0.00 | 01-SEP-00:10 | 43753.34 | 13-SEP-14:50 | 39915.04 | 13-SEP-14:50 | 11480.39 | 12-SEP-14:00 | 9981.89 | 13-SEP-14:50 | 0.00 |
October | 0.261818E+09 | 73889105.41 | 21.67 | 0.246261E+09 | 15556279.22 | 0.00 | 0.40 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 9212.56 | 07-OCT-15:00 | 9212.56 | 07-OCT-15:00 | 998.11 | 17-OCT-15:00 | 2476.82 | 07-OCT-15:00 | 0.00 |
November | 2694271.40 | 786104.90 | 0.67 | 1758271.05 | 936000.35 | 0.00 | 0.09 | 24-NOV-12:00 | 0.00 | 01-NOV-00:10 | 1923.28 | 24-NOV-12:00 | 1276.41 | 24-NOV-12:00 | 646.87 | 24-NOV-12:00 | 557.82 | 24-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.524607E+11 | 0.130279E+11 | 1113.71 | 0.426677E+11 | 0.979299E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.169694E+11 | 0.422278E+10 | 359.60 | 0.133235E+11 | 0.364593E+10 | 0.00 | 1.00 | 0.00 | 65986.57 | 59640.03 | 30824.43 | 15775.27 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 257.09 | 0.00 | 257.09 | 27.41 | 1417.52 | 0.00 | 0.00 | 0.00 |
February | 401.46 | 0.00 | 401.46 | 80.10 | 1331.03 | 0.00 | 0.00 | 0.00 |
March | 555.55 | 0.00 | 555.55 | 215.42 | 1104.60 | 0.00 | 0.00 | 0.00 |
April | 904.52 | 4.05 | 900.47 | 592.26 | 943.49 | 0.00 | 0.00 | 0.00 |
May | 1130.88 | 54.56 | 1076.32 | 751.28 | 761.79 | 0.00 | 0.00 | 0.00 |
June | 1250.12 | 78.39 | 1171.73 | 1052.13 | 609.81 | 0.00 | 0.00 | 0.00 |
July | 1185.81 | 67.61 | 1118.20 | 1064.80 | 564.36 | 0.00 | 0.00 | 0.00 |
August | 932.10 | 14.60 | 917.50 | 818.56 | 631.27 | 0.00 | 0.00 | 0.00 |
September | 709.46 | 0.16 | 709.30 | 541.50 | 831.32 | 0.00 | 0.00 | 0.00 |
October | 454.62 | 0.00 | 454.62 | 210.40 | 1043.69 | 0.00 | 0.00 | 0.00 |
November | 273.16 | 0.00 | 273.16 | 41.86 | 1243.13 | 0.00 | 0.00 | 0.00 |
December | 186.02 | 0.00 | 186.02 | 4.74 | 1511.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 688.01 | 18.40 | 669.60 | 451.91 | 997.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.02 | 0.00 | 186.02 | 4.74 | 564.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1250.12 | 78.39 | 1171.73 | 1064.80 | 1511.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 350.33 | 140.73 | 209.60 | 218.20 | 891.30 | 0.00 | 0.00 | 0.00 |
February | 522.40 | 192.98 | 329.42 | 358.73 | 847.20 | 0.00 | 0.00 | 0.00 |
March | 545.92 | 107.58 | 438.34 | 354.08 | 704.51 | 0.00 | 0.00 | 0.00 |
April | 1465.83 | 688.80 | 777.03 | 1538.81 | 608.65 | 0.00 | 0.00 | 0.00 |
May | 1541.28 | 672.12 | 869.15 | 1572.37 | 527.27 | 0.00 | 0.00 | 0.00 |
June | 1525.58 | 609.30 | 916.28 | 1652.55 | 419.24 | 0.00 | 0.00 | 0.00 |
July | 1557.32 | 661.86 | 895.46 | 1759.79 | 389.05 | 0.00 | 0.00 | 0.00 |
August | 1475.22 | 704.85 | 770.37 | 1717.00 | 423.39 | 0.00 | 0.00 | 0.00 |
September | 1328.48 | 706.43 | 622.06 | 1498.59 | 534.74 | 0.00 | 0.00 | 0.00 |
October | 641.28 | 265.76 | 375.52 | 580.02 | 677.51 | 0.00 | 0.00 | 0.00 |
November | 334.32 | 113.94 | 220.38 | 206.33 | 794.60 | 0.00 | 0.00 | 0.00 |
December | 247.77 | 92.12 | 155.65 | 136.12 | 962.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 962.70 | 413.57 | 549.13 | 968.21 | 647.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 247.77 | 92.12 | 155.65 | 136.12 | 389.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1557.32 | 706.43 | 916.28 | 1759.79 | 962.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1459.60 | 944.86 | 514.74 | 1474.35 | 1296.25 | 0.00 | 0.00 | 0.00 |
February | 1782.63 | 1087.78 | 694.84 | 1841.75 | 1280.46 | 0.00 | 0.00 | 0.00 |
March | 1102.14 | 320.89 | 781.24 | 923.04 | 1079.40 | 0.00 | 0.00 | 0.00 |
April | 2288.68 | 1034.46 | 1254.22 | 2614.63 | 990.24 | 0.00 | 0.00 | 0.00 |
May | 1892.95 | 616.28 | 1276.67 | 1997.10 | 861.32 | 0.00 | 0.00 | 0.00 |
June | 1743.81 | 422.10 | 1321.71 | 1909.77 | 675.45 | 0.00 | 0.00 | 0.00 |
July | 1889.39 | 591.68 | 1297.70 | 2226.64 | 628.84 | 0.00 | 0.00 | 0.00 |
August | 2213.95 | 995.92 | 1218.03 | 2763.87 | 684.93 | 0.00 | 0.00 | 0.00 |
September | 2616.31 | 1532.68 | 1083.63 | 3239.36 | 858.40 | 0.00 | 0.00 | 0.00 |
October | 1797.51 | 1050.56 | 746.95 | 2002.80 | 1042.87 | 0.00 | 0.00 | 0.00 |
November | 1274.43 | 775.27 | 499.16 | 1291.22 | 1198.48 | 0.00 | 0.00 | 0.00 |
December | 1010.11 | 647.18 | 362.93 | 993.35 | 1442.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1753.27 | 831.73 | 921.54 | 1937.08 | 1001.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1010.11 | 320.89 | 362.93 | 923.04 | 628.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2616.31 | 1532.68 | 1321.71 | 3239.36 | 1442.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 340.68 | 112.56 | 228.12 | 216.57 | 907.90 | 0.00 | 0.00 | 0.00 |
February | 603.18 | 254.68 | 348.50 | 493.33 | 874.17 | 0.00 | 0.00 | 0.00 |
March | 545.41 | 104.34 | 441.07 | 352.59 | 714.65 | 0.00 | 0.00 | 0.00 |
April | 1286.91 | 511.17 | 775.74 | 1329.15 | 642.44 | 0.00 | 0.00 | 0.00 |
May | 1509.84 | 613.95 | 895.89 | 1545.37 | 554.58 | 0.00 | 0.00 | 0.00 |
June | 1630.46 | 671.20 | 959.26 | 1797.02 | 442.86 | 0.00 | 0.00 | 0.00 |
July | 1660.56 | 732.14 | 928.41 | 1910.48 | 413.05 | 0.00 | 0.00 | 0.00 |
August | 1394.76 | 603.89 | 790.87 | 1621.16 | 451.82 | 0.00 | 0.00 | 0.00 |
September | 1118.96 | 501.77 | 617.20 | 1251.66 | 567.26 | 0.00 | 0.00 | 0.00 |
October | 596.92 | 214.65 | 382.27 | 536.55 | 697.20 | 0.00 | 0.00 | 0.00 |
November | 323.03 | 94.30 | 228.74 | 207.54 | 817.42 | 0.00 | 0.00 | 0.00 |
December | 182.85 | 38.58 | 144.26 | 73.11 | 997.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 933.78 | 371.25 | 562.53 | 946.04 | 672.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 182.85 | 38.58 | 144.26 | 73.11 | 413.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1660.56 | 732.14 | 959.26 | 1910.48 | 997.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.69 | 0.00 | 85.69 | 8.29 | 492.92 | 0.00 | 0.00 | 0.00 |
February | 133.81 | 0.00 | 133.81 | 25.20 | 463.91 | 0.00 | 0.00 | 0.00 |
March | 185.17 | 0.00 | 185.17 | 72.62 | 380.52 | 0.00 | 0.00 | 0.00 |
April | 301.49 | 1.35 | 300.14 | 206.13 | 317.08 | 0.00 | 0.00 | 0.00 |
May | 376.94 | 18.19 | 358.76 | 257.91 | 258.36 | 0.00 | 0.00 | 0.00 |
June | 416.69 | 26.13 | 390.56 | 359.10 | 205.84 | 0.00 | 0.00 | 0.00 |
July | 395.25 | 22.54 | 372.71 | 361.34 | 191.44 | 0.00 | 0.00 | 0.00 |
August | 310.69 | 4.87 | 305.82 | 278.17 | 214.21 | 0.00 | 0.00 | 0.00 |
September | 236.48 | 0.05 | 236.42 | 181.70 | 287.99 | 0.00 | 0.00 | 0.00 |
October | 151.53 | 0.00 | 151.53 | 66.59 | 374.41 | 0.00 | 0.00 | 0.00 |
November | 91.05 | 0.00 | 91.05 | 11.46 | 448.77 | 0.00 | 0.00 | 0.00 |
December | 62.00 | 0.00 | 62.00 | 0.64 | 538.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 229.33 | 6.13 | 223.19 | 153.07 | 347.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.00 | 0.00 | 62.00 | 0.64 | 191.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 416.69 | 26.13 | 390.56 | 361.34 | 538.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.70 | 0.00 | 85.70 | 8.29 | 492.95 | 0.00 | 0.00 | 0.00 |
February | 133.82 | 0.00 | 133.82 | 25.20 | 463.94 | 0.00 | 0.00 | 0.00 |
March | 185.18 | 0.00 | 185.18 | 72.62 | 380.55 | 0.00 | 0.00 | 0.00 |
April | 301.50 | 1.35 | 300.16 | 206.13 | 317.10 | 0.00 | 0.00 | 0.00 |
May | 376.96 | 18.19 | 358.77 | 257.92 | 258.38 | 0.00 | 0.00 | 0.00 |
June | 416.70 | 26.13 | 390.57 | 359.10 | 205.85 | 0.00 | 0.00 | 0.00 |
July | 395.27 | 22.54 | 372.73 | 361.35 | 191.45 | 0.00 | 0.00 | 0.00 |
August | 310.70 | 4.87 | 305.83 | 278.18 | 214.22 | 0.00 | 0.00 | 0.00 |
September | 236.48 | 0.05 | 236.43 | 181.71 | 288.01 | 0.00 | 0.00 | 0.00 |
October | 151.54 | 0.00 | 151.54 | 66.59 | 374.43 | 0.00 | 0.00 | 0.00 |
November | 91.05 | 0.00 | 91.05 | 11.46 | 448.80 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 0.00 | 62.01 | 0.64 | 538.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 229.33 | 6.13 | 223.20 | 153.07 | 347.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.01 | 0.00 | 62.01 | 0.64 | 191.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 416.70 | 26.13 | 390.57 | 361.35 | 538.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.70 | 0.00 | 85.70 | 8.29 | 492.95 | 0.00 | 0.00 | 0.00 |
February | 133.82 | 0.00 | 133.82 | 25.20 | 463.94 | 0.00 | 0.00 | 0.00 |
March | 185.18 | 0.00 | 185.18 | 72.62 | 380.55 | 0.00 | 0.00 | 0.00 |
April | 301.50 | 1.35 | 300.16 | 206.13 | 317.10 | 0.00 | 0.00 | 0.00 |
May | 376.96 | 18.19 | 358.77 | 257.92 | 258.38 | 0.00 | 0.00 | 0.00 |
June | 416.70 | 26.13 | 390.57 | 359.10 | 205.85 | 0.00 | 0.00 | 0.00 |
July | 395.27 | 22.54 | 372.73 | 361.35 | 191.45 | 0.00 | 0.00 | 0.00 |
August | 310.70 | 4.87 | 305.83 | 278.18 | 214.22 | 0.00 | 0.00 | 0.00 |
September | 236.48 | 0.05 | 236.43 | 181.71 | 288.01 | 0.00 | 0.00 | 0.00 |
October | 151.54 | 0.00 | 151.54 | 66.59 | 374.43 | 0.00 | 0.00 | 0.00 |
November | 91.05 | 0.00 | 91.05 | 11.46 | 448.80 | 0.00 | 0.00 | 0.00 |
December | 62.01 | 0.00 | 62.01 | 0.64 | 538.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 229.33 | 6.13 | 223.20 | 153.07 | 347.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.01 | 0.00 | 62.01 | 0.64 | 191.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 416.70 | 26.13 | 390.57 | 361.35 | 538.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 337.00 | 135.37 | 201.62 | 206.78 | 899.48 | 0.00 | 0.00 | 0.00 |
February | 502.52 | 185.63 | 316.89 | 340.70 | 857.11 | 0.00 | 0.00 | 0.00 |
March | 525.15 | 103.49 | 421.66 | 342.03 | 702.97 | 0.00 | 0.00 | 0.00 |
April | 1410.06 | 662.59 | 747.46 | 1488.37 | 610.18 | 0.00 | 0.00 | 0.00 |
May | 1482.63 | 646.55 | 836.08 | 1519.95 | 532.42 | 0.00 | 0.00 | 0.00 |
June | 1467.53 | 586.12 | 881.42 | 1601.15 | 418.72 | 0.00 | 0.00 | 0.00 |
July | 1498.06 | 636.67 | 861.39 | 1702.31 | 391.92 | 0.00 | 0.00 | 0.00 |
August | 1419.09 | 678.02 | 741.06 | 1659.18 | 428.40 | 0.00 | 0.00 | 0.00 |
September | 1277.93 | 679.55 | 598.39 | 1442.09 | 550.50 | 0.00 | 0.00 | 0.00 |
October | 616.88 | 255.65 | 361.23 | 549.13 | 711.71 | 0.00 | 0.00 | 0.00 |
November | 321.60 | 109.60 | 211.99 | 190.52 | 832.06 | 0.00 | 0.00 | 0.00 |
December | 238.34 | 88.61 | 149.73 | 125.84 | 990.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 926.07 | 397.83 | 528.24 | 932.78 | 659.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 238.34 | 88.61 | 149.73 | 125.84 | 391.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1498.06 | 679.55 | 881.42 | 1702.31 | 990.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.32 | 5.35 | 7.97 | 8.18 | 35.56 | 0.00 | 0.00 | 0.00 |
February | 19.87 | 7.34 | 12.53 | 13.47 | 33.89 | 0.00 | 0.00 | 0.00 |
March | 20.76 | 4.09 | 16.67 | 13.52 | 27.79 | 0.00 | 0.00 | 0.00 |
April | 55.75 | 26.20 | 29.55 | 58.85 | 24.13 | 0.00 | 0.00 | 0.00 |
May | 58.62 | 25.56 | 33.06 | 60.10 | 21.05 | 0.00 | 0.00 | 0.00 |
June | 58.02 | 23.17 | 34.85 | 63.31 | 16.56 | 0.00 | 0.00 | 0.00 |
July | 59.23 | 25.17 | 34.06 | 67.31 | 15.50 | 0.00 | 0.00 | 0.00 |
August | 56.11 | 26.81 | 29.30 | 65.60 | 16.94 | 0.00 | 0.00 | 0.00 |
September | 50.53 | 26.87 | 23.66 | 57.02 | 21.77 | 0.00 | 0.00 | 0.00 |
October | 24.39 | 10.11 | 14.28 | 21.71 | 28.14 | 0.00 | 0.00 | 0.00 |
November | 12.72 | 4.33 | 8.38 | 7.53 | 32.90 | 0.00 | 0.00 | 0.00 |
December | 9.42 | 3.50 | 5.92 | 4.98 | 39.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.62 | 15.73 | 20.89 | 36.88 | 26.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.42 | 3.50 | 5.92 | 4.98 | 15.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.23 | 26.87 | 34.85 | 67.31 | 39.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 486.52 | 314.95 | 171.58 | 493.59 | 455.05 | 0.00 | 0.00 | 0.00 |
February | 594.20 | 362.59 | 231.61 | 616.78 | 452.72 | 0.00 | 0.00 | 0.00 |
March | 367.37 | 106.96 | 260.41 | 314.92 | 370.31 | 0.00 | 0.00 | 0.00 |
April | 762.88 | 344.81 | 418.07 | 882.40 | 341.41 | 0.00 | 0.00 | 0.00 |
May | 630.98 | 205.42 | 425.55 | 677.61 | 295.12 | 0.00 | 0.00 | 0.00 |
June | 581.26 | 140.70 | 440.57 | 649.22 | 228.50 | 0.00 | 0.00 | 0.00 |
July | 629.79 | 197.22 | 432.56 | 751.36 | 216.60 | 0.00 | 0.00 | 0.00 |
August | 737.97 | 331.97 | 406.01 | 928.06 | 240.36 | 0.00 | 0.00 | 0.00 |
September | 872.09 | 510.88 | 361.21 | 1083.00 | 309.07 | 0.00 | 0.00 | 0.00 |
October | 599.16 | 350.18 | 248.98 | 666.86 | 380.98 | 0.00 | 0.00 | 0.00 |
November | 424.80 | 258.42 | 166.39 | 429.96 | 435.03 | 0.00 | 0.00 | 0.00 |
December | 336.70 | 215.72 | 120.97 | 331.32 | 510.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 584.42 | 277.24 | 307.18 | 651.19 | 352.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 336.70 | 106.96 | 120.97 | 314.92 | 216.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 872.09 | 510.88 | 440.57 | 1083.00 | 510.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 486.52 | 314.95 | 171.58 | 493.59 | 455.05 | 0.00 | 0.00 | 0.00 |
February | 594.20 | 362.59 | 231.61 | 616.78 | 452.72 | 0.00 | 0.00 | 0.00 |
March | 367.37 | 106.96 | 260.41 | 314.92 | 370.31 | 0.00 | 0.00 | 0.00 |
April | 762.88 | 344.81 | 418.07 | 882.40 | 341.41 | 0.00 | 0.00 | 0.00 |
May | 630.98 | 205.42 | 425.55 | 677.61 | 295.12 | 0.00 | 0.00 | 0.00 |
June | 581.26 | 140.70 | 440.57 | 649.22 | 228.50 | 0.00 | 0.00 | 0.00 |
July | 629.79 | 197.22 | 432.56 | 751.36 | 216.60 | 0.00 | 0.00 | 0.00 |
August | 737.97 | 331.97 | 406.01 | 928.06 | 240.36 | 0.00 | 0.00 | 0.00 |
September | 872.09 | 510.88 | 361.21 | 1083.00 | 309.07 | 0.00 | 0.00 | 0.00 |
October | 599.16 | 350.18 | 248.98 | 666.86 | 380.98 | 0.00 | 0.00 | 0.00 |
November | 424.80 | 258.42 | 166.39 | 429.96 | 435.03 | 0.00 | 0.00 | 0.00 |
December | 336.70 | 215.72 | 120.97 | 331.32 | 510.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 584.42 | 277.24 | 307.18 | 651.19 | 352.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 336.70 | 106.96 | 120.97 | 314.92 | 216.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 872.09 | 510.88 | 440.57 | 1083.00 | 510.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 486.49 | 314.93 | 171.57 | 493.56 | 455.02 | 0.00 | 0.00 | 0.00 |
February | 594.16 | 362.56 | 231.60 | 616.74 | 452.70 | 0.00 | 0.00 | 0.00 |
March | 367.35 | 106.96 | 260.39 | 314.90 | 370.28 | 0.00 | 0.00 | 0.00 |
April | 762.83 | 344.79 | 418.04 | 882.34 | 341.38 | 0.00 | 0.00 | 0.00 |
May | 630.94 | 205.41 | 425.52 | 677.57 | 295.10 | 0.00 | 0.00 | 0.00 |
June | 581.23 | 140.69 | 440.54 | 649.18 | 228.49 | 0.00 | 0.00 | 0.00 |
July | 629.75 | 197.21 | 432.54 | 751.31 | 216.59 | 0.00 | 0.00 | 0.00 |
August | 737.92 | 331.94 | 405.98 | 928.00 | 240.35 | 0.00 | 0.00 | 0.00 |
September | 872.03 | 510.85 | 361.18 | 1082.93 | 309.06 | 0.00 | 0.00 | 0.00 |
October | 599.12 | 350.16 | 248.96 | 666.82 | 380.95 | 0.00 | 0.00 | 0.00 |
November | 424.78 | 258.40 | 166.37 | 429.94 | 435.00 | 0.00 | 0.00 | 0.00 |
December | 336.67 | 215.71 | 120.97 | 331.30 | 510.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 584.38 | 277.22 | 307.16 | 651.14 | 352.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 336.67 | 106.96 | 120.97 | 314.90 | 216.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 872.03 | 510.85 | 440.54 | 1082.93 | 510.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 327.71 | 108.28 | 219.44 | 207.71 | 915.94 | 0.00 | 0.00 | 0.00 |
February | 580.23 | 244.99 | 335.24 | 473.99 | 887.10 | 0.00 | 0.00 | 0.00 |
March | 524.66 | 100.37 | 424.29 | 343.70 | 714.32 | 0.00 | 0.00 | 0.00 |
April | 1237.94 | 491.72 | 746.22 | 1290.15 | 641.90 | 0.00 | 0.00 | 0.00 |
May | 1452.39 | 590.59 | 861.80 | 1496.86 | 561.67 | 0.00 | 0.00 | 0.00 |
June | 1568.43 | 645.66 | 922.77 | 1742.07 | 447.32 | 0.00 | 0.00 | 0.00 |
July | 1597.37 | 704.28 | 893.09 | 1849.93 | 418.83 | 0.00 | 0.00 | 0.00 |
August | 1341.69 | 580.91 | 760.78 | 1569.31 | 458.61 | 0.00 | 0.00 | 0.00 |
September | 1076.39 | 482.68 | 593.71 | 1205.06 | 582.99 | 0.00 | 0.00 | 0.00 |
October | 574.21 | 206.48 | 367.73 | 508.60 | 731.64 | 0.00 | 0.00 | 0.00 |
November | 310.74 | 90.71 | 220.03 | 194.69 | 855.58 | 0.00 | 0.00 | 0.00 |
December | 175.89 | 37.12 | 138.77 | 67.92 | 1023.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 898.26 | 357.13 | 541.13 | 913.96 | 685.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.89 | 37.12 | 138.77 | 67.92 | 418.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1597.37 | 704.28 | 922.77 | 1849.93 | 1023.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.96 | 4.28 | 8.68 | 8.21 | 36.22 | 0.00 | 0.00 | 0.00 |
February | 22.94 | 9.69 | 13.26 | 18.74 | 35.08 | 0.00 | 0.00 | 0.00 |
March | 20.74 | 3.97 | 16.78 | 13.59 | 28.24 | 0.00 | 0.00 | 0.00 |
April | 48.95 | 19.44 | 29.50 | 51.01 | 25.38 | 0.00 | 0.00 | 0.00 |
May | 57.43 | 23.35 | 34.07 | 59.18 | 22.21 | 0.00 | 0.00 | 0.00 |
June | 62.01 | 25.53 | 36.49 | 68.88 | 17.69 | 0.00 | 0.00 | 0.00 |
July | 63.16 | 27.85 | 35.31 | 73.14 | 16.56 | 0.00 | 0.00 | 0.00 |
August | 53.05 | 22.97 | 30.08 | 62.05 | 18.13 | 0.00 | 0.00 | 0.00 |
September | 42.56 | 19.08 | 23.47 | 47.65 | 23.05 | 0.00 | 0.00 | 0.00 |
October | 22.70 | 8.16 | 14.54 | 20.11 | 28.93 | 0.00 | 0.00 | 0.00 |
November | 12.29 | 3.59 | 8.70 | 7.70 | 33.83 | 0.00 | 0.00 | 0.00 |
December | 6.95 | 1.47 | 5.49 | 2.69 | 40.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.52 | 14.12 | 21.40 | 36.14 | 27.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.95 | 1.47 | 5.49 | 2.69 | 16.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.16 | 27.85 | 36.49 | 73.14 | 40.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 257.09 | 0.00 | 257.09 | 21.55 | 1505.13 | 0.00 | 0.00 | 0.00 |
February | 401.46 | 0.00 | 401.46 | 66.60 | 1423.67 | 0.00 | 0.00 | 0.00 |
March | 555.55 | 0.00 | 555.55 | 197.76 | 1179.09 | 0.00 | 0.00 | 0.00 |
April | 904.52 | 4.05 | 900.47 | 575.27 | 999.59 | 0.00 | 0.00 | 0.00 |
May | 1130.88 | 54.56 | 1076.32 | 728.70 | 805.63 | 0.00 | 0.00 | 0.00 |
June | 1250.12 | 78.39 | 1171.73 | 1041.75 | 637.27 | 0.00 | 0.00 | 0.00 |
July | 1185.81 | 67.61 | 1118.20 | 1055.84 | 588.69 | 0.00 | 0.00 | 0.00 |
August | 932.10 | 14.60 | 917.50 | 810.24 | 661.51 | 0.00 | 0.00 | 0.00 |
September | 709.46 | 0.16 | 709.30 | 527.09 | 882.67 | 0.00 | 0.00 | 0.00 |
October | 454.62 | 0.00 | 454.62 | 190.59 | 1132.61 | 0.00 | 0.00 | 0.00 |
November | 273.16 | 0.00 | 273.16 | 32.70 | 1345.06 | 0.00 | 0.00 | 0.00 |
December | 186.02 | 0.00 | 186.02 | 1.95 | 1613.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 688.01 | 18.40 | 669.60 | 439.38 | 1062.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.02 | 0.00 | 186.02 | 1.95 | 588.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1250.12 | 78.39 | 1171.73 | 1055.84 | 1613.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 350.33 | 140.73 | 209.60 | 208.78 | 947.08 | 0.00 | 0.00 | 0.00 |
February | 522.40 | 192.98 | 329.42 | 343.04 | 906.55 | 0.00 | 0.00 | 0.00 |
March | 545.92 | 107.58 | 438.34 | 336.16 | 752.43 | 0.00 | 0.00 | 0.00 |
April | 1465.83 | 688.80 | 777.03 | 1525.55 | 640.47 | 0.00 | 0.00 | 0.00 |
May | 1541.28 | 672.12 | 869.15 | 1559.24 | 554.41 | 0.00 | 0.00 | 0.00 |
June | 1525.58 | 609.30 | 916.28 | 1645.14 | 436.83 | 0.00 | 0.00 | 0.00 |
July | 1557.32 | 661.86 | 895.46 | 1753.47 | 404.68 | 0.00 | 0.00 | 0.00 |
August | 1475.22 | 704.85 | 770.37 | 1710.58 | 441.38 | 0.00 | 0.00 | 0.00 |
September | 1328.48 | 706.43 | 622.06 | 1487.36 | 563.28 | 0.00 | 0.00 | 0.00 |
October | 641.28 | 265.76 | 375.52 | 563.51 | 733.72 | 0.00 | 0.00 | 0.00 |
November | 334.32 | 113.94 | 220.38 | 194.57 | 860.47 | 0.00 | 0.00 | 0.00 |
December | 247.77 | 92.12 | 155.65 | 129.26 | 1026.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 962.70 | 413.57 | 549.13 | 956.92 | 687.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 247.77 | 92.12 | 155.65 | 129.26 | 404.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1557.32 | 706.43 | 916.28 | 1753.47 | 1026.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1459.60 | 944.86 | 514.74 | 1457.12 | 1377.21 | 0.00 | 0.00 | 0.00 |
February | 1782.63 | 1087.78 | 694.84 | 1819.31 | 1365.36 | 0.00 | 0.00 | 0.00 |
March | 1102.14 | 320.89 | 781.24 | 901.13 | 1151.52 | 0.00 | 0.00 | 0.00 |
April | 2288.68 | 1034.46 | 1254.22 | 2602.52 | 1043.29 | 0.00 | 0.00 | 0.00 |
May | 1892.95 | 616.28 | 1276.67 | 1984.38 | 909.61 | 0.00 | 0.00 | 0.00 |
June | 1743.81 | 422.10 | 1321.71 | 1903.76 | 706.44 | 0.00 | 0.00 | 0.00 |
July | 1889.39 | 591.68 | 1297.70 | 2222.44 | 656.91 | 0.00 | 0.00 | 0.00 |
August | 2213.95 | 995.92 | 1218.03 | 2760.81 | 716.29 | 0.00 | 0.00 | 0.00 |
September | 2616.31 | 1532.68 | 1083.63 | 3230.22 | 904.83 | 0.00 | 0.00 | 0.00 |
October | 1797.51 | 1050.56 | 746.95 | 1983.50 | 1125.62 | 0.00 | 0.00 | 0.00 |
November | 1274.43 | 775.27 | 499.16 | 1272.63 | 1294.23 | 0.00 | 0.00 | 0.00 |
December | 1010.11 | 647.18 | 362.93 | 978.78 | 1537.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1753.27 | 831.73 | 921.54 | 1923.69 | 1064.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1010.11 | 320.89 | 362.93 | 901.13 | 656.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2616.31 | 1532.68 | 1321.71 | 3230.22 | 1537.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 340.68 | 112.56 | 228.12 | 209.90 | 964.06 | 0.00 | 0.00 | 0.00 |
February | 603.18 | 254.68 | 348.50 | 482.29 | 933.67 | 0.00 | 0.00 | 0.00 |
March | 545.41 | 104.34 | 441.07 | 339.55 | 763.12 | 0.00 | 0.00 | 0.00 |
April | 1286.91 | 511.17 | 775.74 | 1318.74 | 678.48 | 0.00 | 0.00 | 0.00 |
May | 1509.84 | 613.95 | 895.89 | 1535.41 | 585.94 | 0.00 | 0.00 | 0.00 |
June | 1630.46 | 671.20 | 959.26 | 1793.92 | 463.34 | 0.00 | 0.00 | 0.00 |
July | 1660.56 | 732.14 | 928.41 | 1908.23 | 431.70 | 0.00 | 0.00 | 0.00 |
August | 1394.76 | 603.89 | 790.87 | 1618.67 | 472.96 | 0.00 | 0.00 | 0.00 |
September | 1118.96 | 501.77 | 617.20 | 1243.55 | 600.41 | 0.00 | 0.00 | 0.00 |
October | 596.92 | 214.65 | 382.27 | 523.27 | 754.88 | 0.00 | 0.00 | 0.00 |
November | 323.03 | 94.30 | 228.74 | 199.38 | 883.81 | 0.00 | 0.00 | 0.00 |
December | 182.85 | 38.58 | 144.26 | 69.22 | 1063.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 933.78 | 371.25 | 562.53 | 938.36 | 715.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 182.85 | 38.58 | 144.26 | 69.22 | 431.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1660.56 | 732.14 | 959.26 | 1908.23 | 1063.55 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.688596E+09 | 0.00 | 0.688596E+09 | 73422361.18 | 0.379669E+10 |
February | 0.971213E+09 | 0.00 | 0.971213E+09 | 0.193773E+09 | 0.322003E+10 |
March | 0.148799E+10 | 0.00 | 0.148799E+10 | 0.576972E+09 | 0.295856E+10 |
April | 0.234452E+10 | 10493085.83 | 0.233403E+10 | 0.153514E+10 | 0.244552E+10 |
May | 0.302895E+10 | 0.146132E+09 | 0.288282E+10 | 0.201222E+10 | 0.204037E+10 |
June | 0.324031E+10 | 0.203188E+09 | 0.303712E+10 | 0.272713E+10 | 0.158064E+10 |
July | 0.317606E+10 | 0.181084E+09 | 0.299498E+10 | 0.285196E+10 | 0.151159E+10 |
August | 0.249655E+10 | 39114720.84 | 0.245743E+10 | 0.219244E+10 | 0.169079E+10 |
September | 0.183892E+10 | 406915.76 | 0.183851E+10 | 0.140358E+10 | 0.215478E+10 |
October | 0.121764E+10 | 0.00 | 0.121764E+10 | 0.563543E+09 | 0.279542E+10 |
November | 0.708023E+09 | 0.00 | 0.708023E+09 | 0.108496E+09 | 0.322218E+10 |
December | 0.498234E+09 | 0.00 | 0.498234E+09 | 12685898.69 | 0.404780E+10 |
Annual Sum or Average | 0.216970E+11 | 0.580420E+09 | 0.211166E+11 | 0.142514E+11 | 0.314644E+11 |
Minimum of Months | 0.498234E+09 | 0.00 | 0.498234E+09 | 12685898.69 | 0.151159E+10 |
Maximum of Months | 0.324031E+10 | 0.203188E+09 | 0.303712E+10 | 0.285196E+10 | 0.404780E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.938315E+09 | 0.376923E+09 | 0.561392E+09 | 0.584419E+09 | 0.238726E+10 |
February | 0.126379E+10 | 0.466852E+09 | 0.796934E+09 | 0.867836E+09 | 0.204954E+10 |
March | 0.146219E+10 | 0.288143E+09 | 0.117404E+10 | 0.948358E+09 | 0.188696E+10 |
April | 0.379944E+10 | 0.178538E+10 | 0.201406E+10 | 0.398860E+10 | 0.157763E+10 |
May | 0.412816E+10 | 0.180022E+10 | 0.232794E+10 | 0.421144E+10 | 0.141225E+10 |
June | 0.395431E+10 | 0.157931E+10 | 0.237500E+10 | 0.428341E+10 | 0.108668E+10 |
July | 0.417112E+10 | 0.177273E+10 | 0.239840E+10 | 0.471343E+10 | 0.104203E+10 |
August | 0.395123E+10 | 0.188786E+10 | 0.206337E+10 | 0.459881E+10 | 0.113401E+10 |
September | 0.344343E+10 | 0.183106E+10 | 0.161237E+10 | 0.388435E+10 | 0.138605E+10 |
October | 0.171760E+10 | 0.711816E+09 | 0.100578E+10 | 0.155353E+10 | 0.181465E+10 |
November | 0.866549E+09 | 0.295332E+09 | 0.571217E+09 | 0.534814E+09 | 0.205962E+10 |
December | 0.663626E+09 | 0.246727E+09 | 0.416899E+09 | 0.364597E+09 | 0.257833E+10 |
Annual Sum or Average | 0.303597E+11 | 0.130423E+11 | 0.173174E+11 | 0.305336E+11 | 0.204150E+11 |
Minimum of Months | 0.663626E+09 | 0.246727E+09 | 0.416899E+09 | 0.364597E+09 | 0.104203E+10 |
Maximum of Months | 0.417112E+10 | 0.188786E+10 | 0.239840E+10 | 0.471343E+10 | 0.257833E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.390938E+10 | 0.253070E+10 | 0.137868E+10 | 0.394890E+10 | 0.347188E+10 |
February | 0.431253E+10 | 0.263157E+10 | 0.168097E+10 | 0.445556E+10 | 0.309770E+10 |
March | 0.295197E+10 | 0.859480E+09 | 0.209249E+10 | 0.247227E+10 | 0.289108E+10 |
April | 0.593226E+10 | 0.268131E+10 | 0.325095E+10 | 0.677712E+10 | 0.256671E+10 |
May | 0.507008E+10 | 0.165065E+10 | 0.341943E+10 | 0.534902E+10 | 0.230695E+10 |
June | 0.451996E+10 | 0.109409E+10 | 0.342587E+10 | 0.495014E+10 | 0.175075E+10 |
July | 0.506053E+10 | 0.158476E+10 | 0.347577E+10 | 0.596384E+10 | 0.168428E+10 |
August | 0.592984E+10 | 0.266746E+10 | 0.326238E+10 | 0.740275E+10 | 0.183451E+10 |
September | 0.678147E+10 | 0.397270E+10 | 0.280877E+10 | 0.839641E+10 | 0.222498E+10 |
October | 0.481445E+10 | 0.281383E+10 | 0.200062E+10 | 0.536429E+10 | 0.279323E+10 |
November | 0.330333E+10 | 0.200950E+10 | 0.129383E+10 | 0.334684E+10 | 0.310647E+10 |
December | 0.270547E+10 | 0.173341E+10 | 0.972062E+09 | 0.266060E+10 | 0.386233E+10 |
Annual Sum or Average | 0.552913E+11 | 0.262295E+11 | 0.290618E+11 | 0.610877E+11 | 0.315909E+11 |
Minimum of Months | 0.270547E+10 | 0.859480E+09 | 0.972062E+09 | 0.247227E+10 | 0.168428E+10 |
Maximum of Months | 0.678147E+10 | 0.397270E+10 | 0.347577E+10 | 0.839641E+10 | 0.386233E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.912466E+09 | 0.301482E+09 | 0.610983E+09 | 0.580051E+09 | 0.243173E+10 |
February | 0.145922E+10 | 0.616130E+09 | 0.843091E+09 | 0.119347E+10 | 0.211478E+10 |
March | 0.146082E+10 | 0.279454E+09 | 0.118136E+10 | 0.944378E+09 | 0.191412E+10 |
April | 0.333566E+10 | 0.132495E+10 | 0.201071E+10 | 0.344515E+10 | 0.166520E+10 |
May | 0.404395E+10 | 0.164441E+10 | 0.239954E+10 | 0.413912E+10 | 0.148538E+10 |
June | 0.422616E+10 | 0.173975E+10 | 0.248641E+10 | 0.465787E+10 | 0.114788E+10 |
July | 0.444763E+10 | 0.196097E+10 | 0.248666E+10 | 0.511703E+10 | 0.110632E+10 |
August | 0.373571E+10 | 0.161746E+10 | 0.211825E+10 | 0.434211E+10 | 0.121016E+10 |
September | 0.290036E+10 | 0.130059E+10 | 0.159977E+10 | 0.324429E+10 | 0.147034E+10 |
October | 0.159880E+10 | 0.574922E+09 | 0.102388E+10 | 0.143709E+10 | 0.186739E+10 |
November | 0.837306E+09 | 0.244420E+09 | 0.592886E+09 | 0.537934E+09 | 0.211874E+10 |
December | 0.489738E+09 | 0.103345E+09 | 0.386393E+09 | 0.195813E+09 | 0.267176E+10 |
Annual Sum or Average | 0.294478E+11 | 0.117079E+11 | 0.177399E+11 | 0.298343E+11 | 0.212038E+11 |
Minimum of Months | 0.489738E+09 | 0.103345E+09 | 0.386393E+09 | 0.195813E+09 | 0.110632E+10 |
Maximum of Months | 0.444763E+10 | 0.196097E+10 | 0.248666E+10 | 0.511703E+10 | 0.267176E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229521E+09 | 0.00 | 0.229521E+09 | 22201334.33 | 0.132024E+10 |
February | 0.323722E+09 | 0.00 | 0.323722E+09 | 60954212.45 | 0.112230E+10 |
March | 0.495972E+09 | 0.00 | 0.495972E+09 | 0.194508E+09 | 0.101919E+10 |
April | 0.781469E+09 | 3497529.79 | 0.777972E+09 | 0.534287E+09 | 0.821870E+09 |
May | 0.100960E+10 | 48708519.74 | 0.960895E+09 | 0.690791E+09 | 0.691999E+09 |
June | 0.108005E+10 | 67726247.31 | 0.101233E+10 | 0.930775E+09 | 0.533541E+09 |
July | 0.105864E+10 | 60358525.20 | 0.998279E+09 | 0.967818E+09 | 0.512755E+09 |
August | 0.832143E+09 | 13037623.41 | 0.819106E+09 | 0.745053E+09 | 0.573736E+09 |
September | 0.612944E+09 | 135632.17 | 0.612808E+09 | 0.470969E+09 | 0.746482E+09 |
October | 0.405862E+09 | 0.00 | 0.405862E+09 | 0.178366E+09 | 0.100282E+10 |
November | 0.235997E+09 | 0.00 | 0.235997E+09 | 29702913.10 | 0.116321E+10 |
December | 0.166070E+09 | 0.00 | 0.166070E+09 | 1727092.67 | 0.144267E+10 |
Annual Sum or Average | 0.723199E+10 | 0.193464E+09 | 0.703853E+10 | 0.482715E+10 | 0.109508E+11 |
Minimum of Months | 0.166070E+09 | 0.00 | 0.166070E+09 | 1727092.67 | 0.512755E+09 |
Maximum of Months | 0.108005E+10 | 67726247.31 | 0.101233E+10 | 0.967818E+09 | 0.144267E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229530E+09 | 0.00 | 0.229530E+09 | 22200208.40 | 0.132032E+10 |
February | 0.323734E+09 | 0.00 | 0.323734E+09 | 60952071.21 | 0.112237E+10 |
March | 0.495990E+09 | 0.00 | 0.495990E+09 | 0.194507E+09 | 0.101925E+10 |
April | 0.781500E+09 | 3497623.81 | 0.778003E+09 | 0.534300E+09 | 0.821921E+09 |
May | 0.100964E+10 | 48709829.04 | 0.960933E+09 | 0.690805E+09 | 0.692042E+09 |
June | 0.108009E+10 | 67728067.81 | 0.101237E+10 | 0.930800E+09 | 0.533574E+09 |
July | 0.105868E+10 | 60360147.65 | 0.998319E+09 | 0.967847E+09 | 0.512786E+09 |
August | 0.832177E+09 | 13037973.87 | 0.819139E+09 | 0.745078E+09 | 0.573769E+09 |
September | 0.612969E+09 | 135635.81 | 0.612833E+09 | 0.470984E+09 | 0.746526E+09 |
October | 0.405878E+09 | 0.00 | 0.405878E+09 | 0.178368E+09 | 0.100288E+10 |
November | 0.236005E+09 | 0.00 | 0.236005E+09 | 29701582.36 | 0.116328E+10 |
December | 0.166076E+09 | 0.00 | 0.166076E+09 | 1726653.85 | 0.144276E+10 |
Annual Sum or Average | 0.723227E+10 | 0.193469E+09 | 0.703880E+10 | 0.482727E+10 | 0.109515E+11 |
Minimum of Months | 0.166076E+09 | 0.00 | 0.166076E+09 | 1726653.85 | 0.512786E+09 |
Maximum of Months | 0.108009E+10 | 67728067.81 | 0.101237E+10 | 0.967847E+09 | 0.144276E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229530E+09 | 0.00 | 0.229530E+09 | 22200208.40 | 0.132032E+10 |
February | 0.323734E+09 | 0.00 | 0.323734E+09 | 60952071.21 | 0.112237E+10 |
March | 0.495990E+09 | 0.00 | 0.495990E+09 | 0.194507E+09 | 0.101925E+10 |
April | 0.781500E+09 | 3497623.81 | 0.778003E+09 | 0.534300E+09 | 0.821921E+09 |
May | 0.100964E+10 | 48709829.04 | 0.960933E+09 | 0.690805E+09 | 0.692042E+09 |
June | 0.108009E+10 | 67728067.81 | 0.101237E+10 | 0.930800E+09 | 0.533574E+09 |
July | 0.105868E+10 | 60360147.65 | 0.998319E+09 | 0.967847E+09 | 0.512786E+09 |
August | 0.832177E+09 | 13037973.87 | 0.819139E+09 | 0.745078E+09 | 0.573769E+09 |
September | 0.612969E+09 | 135635.81 | 0.612833E+09 | 0.470984E+09 | 0.746526E+09 |
October | 0.405878E+09 | 0.00 | 0.405878E+09 | 0.178368E+09 | 0.100288E+10 |
November | 0.236005E+09 | 0.00 | 0.236005E+09 | 29701582.36 | 0.116328E+10 |
December | 0.166076E+09 | 0.00 | 0.166076E+09 | 1726653.85 | 0.144276E+10 |
Annual Sum or Average | 0.723227E+10 | 0.193469E+09 | 0.703880E+10 | 0.482727E+10 | 0.109515E+11 |
Minimum of Months | 0.166076E+09 | 0.00 | 0.166076E+09 | 1726653.85 | 0.512786E+09 |
Maximum of Months | 0.108009E+10 | 67728067.81 | 0.101237E+10 | 0.967847E+09 | 0.144276E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.902611E+09 | 0.362579E+09 | 0.540032E+09 | 0.553849E+09 | 0.240917E+10 |
February | 0.121570E+10 | 0.449086E+09 | 0.766611E+09 | 0.824213E+09 | 0.207353E+10 |
March | 0.140655E+10 | 0.277178E+09 | 0.112937E+10 | 0.916095E+09 | 0.188284E+10 |
April | 0.365487E+10 | 0.171744E+10 | 0.193743E+10 | 0.385784E+10 | 0.158160E+10 |
May | 0.397108E+10 | 0.173171E+10 | 0.223937E+10 | 0.407103E+10 | 0.142602E+10 |
June | 0.380385E+10 | 0.151921E+10 | 0.228464E+10 | 0.415019E+10 | 0.108531E+10 |
July | 0.401241E+10 | 0.170527E+10 | 0.230714E+10 | 0.455947E+10 | 0.104971E+10 |
August | 0.380088E+10 | 0.181602E+10 | 0.198486E+10 | 0.444396E+10 | 0.114742E+10 |
September | 0.331241E+10 | 0.176138E+10 | 0.155103E+10 | 0.373791E+10 | 0.142689E+10 |
October | 0.165224E+10 | 0.684728E+09 | 0.967512E+09 | 0.147078E+10 | 0.190624E+10 |
November | 0.833576E+09 | 0.284094E+09 | 0.549482E+09 | 0.493840E+09 | 0.215671E+10 |
December | 0.638374E+09 | 0.237338E+09 | 0.401036E+09 | 0.337058E+09 | 0.265219E+10 |
Annual Sum or Average | 0.292045E+11 | 0.125460E+11 | 0.166585E+11 | 0.294162E+11 | 0.207976E+11 |
Minimum of Months | 0.638374E+09 | 0.237338E+09 | 0.401036E+09 | 0.337058E+09 | 0.104971E+10 |
Maximum of Months | 0.401241E+10 | 0.181602E+10 | 0.230714E+10 | 0.455947E+10 | 0.265219E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 35688433.57 | 14336054.52 | 21352379.06 | 21898677.90 | 95256363.37 |
February | 48067583.21 | 17756461.15 | 30311122.05 | 32588653.49 | 81985609.23 |
March | 55613667.58 | 10959376.85 | 44654290.74 | 36221589.21 | 74445858.52 |
April | 0.144510E+09 | 67906042.39 | 76604120.90 | 0.152536E+09 | 62534968.62 |
May | 0.157013E+09 | 68470360.95 | 88542535.08 | 0.160965E+09 | 56383729.86 |
June | 0.150401E+09 | 60068315.12 | 90332427.42 | 0.164095E+09 | 42912362.04 |
July | 0.158647E+09 | 67424684.75 | 91222378.64 | 0.180277E+09 | 41504509.14 |
August | 0.150283E+09 | 71803713.28 | 78479670.53 | 0.175710E+09 | 45367949.70 |
September | 0.130970E+09 | 69643426.43 | 61326165.45 | 0.147793E+09 | 56417970.22 |
October | 65328092.61 | 27073547.32 | 38254545.29 | 58153432.34 | 75371152.16 |
November | 32958855.49 | 11232815.18 | 21726040.31 | 19526001.32 | 85274301.15 |
December | 25240733.93 | 9384121.59 | 15856612.34 | 13326966.17 | 0.104865E+09 |
Annual Sum or Average | 0.115472E+10 | 0.496059E+09 | 0.658662E+09 | 0.116309E+10 | 0.822320E+09 |
Minimum of Months | 25240733.93 | 9384121.59 | 15856612.34 | 13326966.17 | 41504509.14 |
Maximum of Months | 0.158647E+09 | 71803713.28 | 91222378.64 | 0.180277E+09 | 0.104865E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130310E+10 | 0.843550E+09 | 0.459552E+09 | 0.132204E+10 | 0.121881E+10 |
February | 0.143749E+10 | 0.877171E+09 | 0.560314E+09 | 0.149211E+10 | 0.109523E+10 |
March | 0.983973E+09 | 0.286487E+09 | 0.697485E+09 | 0.843495E+09 | 0.991829E+09 |
April | 0.197739E+10 | 0.893752E+09 | 0.108364E+10 | 0.228717E+10 | 0.884924E+09 |
May | 0.169000E+10 | 0.550206E+09 | 0.113980E+10 | 0.181491E+10 | 0.790437E+09 |
June | 0.150663E+10 | 0.364690E+09 | 0.114194E+10 | 0.168277E+10 | 0.592282E+09 |
July | 0.168682E+10 | 0.528243E+09 | 0.115858E+10 | 0.201244E+10 | 0.580140E+09 |
August | 0.197658E+10 | 0.889135E+09 | 0.108745E+10 | 0.248571E+10 | 0.643783E+09 |
September | 0.226045E+10 | 0.132421E+10 | 0.936246E+09 | 0.280714E+10 | 0.801122E+09 |
October | 0.160479E+10 | 0.937925E+09 | 0.666865E+09 | 0.178613E+10 | 0.102041E+10 |
November | 0.110109E+10 | 0.669821E+09 | 0.431271E+09 | 0.111446E+10 | 0.112759E+10 |
December | 0.901806E+09 | 0.577791E+09 | 0.324016E+09 | 0.887406E+09 | 0.136666E+10 |
Annual Sum or Average | 0.184301E+11 | 0.874298E+10 | 0.968716E+10 | 0.205358E+11 | 0.111132E+11 |
Minimum of Months | 0.901806E+09 | 0.286487E+09 | 0.324016E+09 | 0.843495E+09 | 0.580140E+09 |
Maximum of Months | 0.226045E+10 | 0.132421E+10 | 0.115858E+10 | 0.280714E+10 | 0.136666E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130310E+10 | 0.843550E+09 | 0.459552E+09 | 0.132204E+10 | 0.121881E+10 |
February | 0.143749E+10 | 0.877171E+09 | 0.560314E+09 | 0.149211E+10 | 0.109523E+10 |
March | 0.983973E+09 | 0.286487E+09 | 0.697485E+09 | 0.843495E+09 | 0.991829E+09 |
April | 0.197739E+10 | 0.893752E+09 | 0.108364E+10 | 0.228717E+10 | 0.884924E+09 |
May | 0.169000E+10 | 0.550206E+09 | 0.113980E+10 | 0.181491E+10 | 0.790437E+09 |
June | 0.150663E+10 | 0.364690E+09 | 0.114194E+10 | 0.168277E+10 | 0.592282E+09 |
July | 0.168682E+10 | 0.528243E+09 | 0.115858E+10 | 0.201244E+10 | 0.580140E+09 |
August | 0.197658E+10 | 0.889135E+09 | 0.108745E+10 | 0.248571E+10 | 0.643783E+09 |
September | 0.226045E+10 | 0.132421E+10 | 0.936246E+09 | 0.280714E+10 | 0.801122E+09 |
October | 0.160479E+10 | 0.937925E+09 | 0.666865E+09 | 0.178613E+10 | 0.102041E+10 |
November | 0.110109E+10 | 0.669821E+09 | 0.431271E+09 | 0.111446E+10 | 0.112759E+10 |
December | 0.901806E+09 | 0.577791E+09 | 0.324016E+09 | 0.887406E+09 | 0.136666E+10 |
Annual Sum or Average | 0.184301E+11 | 0.874298E+10 | 0.968716E+10 | 0.205358E+11 | 0.111132E+11 |
Minimum of Months | 0.901806E+09 | 0.286487E+09 | 0.324016E+09 | 0.843495E+09 | 0.580140E+09 |
Maximum of Months | 0.226045E+10 | 0.132421E+10 | 0.115858E+10 | 0.280714E+10 | 0.136666E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130302E+10 | 0.843497E+09 | 0.459523E+09 | 0.132196E+10 | 0.121873E+10 |
February | 0.143739E+10 | 0.877116E+09 | 0.560279E+09 | 0.149202E+10 | 0.109516E+10 |
March | 0.983911E+09 | 0.286469E+09 | 0.697441E+09 | 0.843441E+09 | 0.991766E+09 |
April | 0.197726E+10 | 0.893695E+09 | 0.108357E+10 | 0.228703E+10 | 0.884868E+09 |
May | 0.168990E+10 | 0.550171E+09 | 0.113973E+10 | 0.181480E+10 | 0.790387E+09 |
June | 0.150654E+10 | 0.364667E+09 | 0.114187E+10 | 0.168266E+10 | 0.592245E+09 |
July | 0.168672E+10 | 0.528210E+09 | 0.115851E+10 | 0.201231E+10 | 0.580103E+09 |
August | 0.197646E+10 | 0.889079E+09 | 0.108738E+10 | 0.248556E+10 | 0.643742E+09 |
September | 0.226031E+10 | 0.132412E+10 | 0.936187E+09 | 0.280696E+10 | 0.801071E+09 |
October | 0.160469E+10 | 0.937865E+09 | 0.666823E+09 | 0.178602E+10 | 0.102034E+10 |
November | 0.110102E+10 | 0.669778E+09 | 0.431244E+09 | 0.111439E+10 | 0.112752E+10 |
December | 0.901749E+09 | 0.577754E+09 | 0.323995E+09 | 0.887350E+09 | 0.136657E+10 |
Annual Sum or Average | 0.184290E+11 | 0.874243E+10 | 0.968654E+10 | 0.205345E+11 | 0.111125E+11 |
Minimum of Months | 0.901749E+09 | 0.286469E+09 | 0.323995E+09 | 0.843441E+09 | 0.580103E+09 |
Maximum of Months | 0.226031E+10 | 0.132412E+10 | 0.115851E+10 | 0.280696E+10 | 0.136657E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.877748E+09 | 0.290011E+09 | 0.587737E+09 | 0.556320E+09 | 0.245327E+10 |
February | 0.140370E+10 | 0.592685E+09 | 0.811014E+09 | 0.114668E+10 | 0.214606E+10 |
March | 0.140524E+10 | 0.268821E+09 | 0.113642E+10 | 0.920566E+09 | 0.191322E+10 |
April | 0.320875E+10 | 0.127454E+10 | 0.193421E+10 | 0.334406E+10 | 0.166380E+10 |
May | 0.389009E+10 | 0.158184E+10 | 0.230825E+10 | 0.400919E+10 | 0.150438E+10 |
June | 0.406537E+10 | 0.167355E+10 | 0.239181E+10 | 0.451544E+10 | 0.115944E+10 |
July | 0.427841E+10 | 0.188636E+10 | 0.239205E+10 | 0.495484E+10 | 0.112180E+10 |
August | 0.359358E+10 | 0.155591E+10 | 0.203767E+10 | 0.420323E+10 | 0.122834E+10 |
September | 0.279000E+10 | 0.125110E+10 | 0.153891E+10 | 0.312352E+10 | 0.151110E+10 |
October | 0.153797E+10 | 0.553046E+09 | 0.984925E+09 | 0.136223E+10 | 0.195962E+10 |
November | 0.805448E+09 | 0.235120E+09 | 0.570329E+09 | 0.504631E+09 | 0.221766E+10 |
December | 0.471105E+09 | 99413033.89 | 0.371692E+09 | 0.181922E+09 | 0.274210E+10 |
Annual Sum or Average | 0.283274E+11 | 0.112624E+11 | 0.170650E+11 | 0.288226E+11 | 0.216208E+11 |
Minimum of Months | 0.471105E+09 | 99413033.89 | 0.371692E+09 | 0.181922E+09 | 0.112180E+10 |
Maximum of Months | 0.427841E+10 | 0.188636E+10 | 0.239205E+10 | 0.495484E+10 | 0.274210E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 34705274.31 | 11466723.53 | 23238550.78 | 21996274.68 | 96999939.08 |
February | 55500860.21 | 23434170.63 | 32066689.58 | 45338313.88 | 84853442.78 |
March | 55561665.87 | 10628902.52 | 44932763.35 | 36398162.49 | 75647168.11 |
April | 0.126871E+09 | 50393898.87 | 76476705.75 | 0.132221E+09 | 65784950.66 |
May | 0.153810E+09 | 62544284.35 | 91265892.71 | 0.158519E+09 | 59482018.19 |
June | 0.160740E+09 | 66170469.65 | 94569975.45 | 0.178536E+09 | 45843236.61 |
July | 0.169164E+09 | 74584584.73 | 94579399.25 | 0.195909E+09 | 44354958.33 |
August | 0.142086E+09 | 61519228.31 | 80567267.66 | 0.166192E+09 | 48567540.40 |
September | 0.110314E+09 | 49467080.63 | 60846879.02 | 0.123501E+09 | 59747433.68 |
October | 60809835.81 | 21866872.39 | 38942963.42 | 53861089.36 | 77481719.60 |
November | 31846619.64 | 9296391.31 | 22550228.34 | 19952547.22 | 87684349.52 |
December | 18627009.98 | 3930689.11 | 14696320.87 | 7192992.26 | 0.108420E+09 |
Annual Sum or Average | 0.112004E+10 | 0.445303E+09 | 0.674734E+09 | 0.113962E+10 | 0.854867E+09 |
Minimum of Months | 18627009.98 | 3930689.11 | 14696320.87 | 7192992.26 | 44354958.33 |
Maximum of Months | 0.169164E+09 | 74584584.73 | 94579399.25 | 0.195909E+09 | 0.108420E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.688596E+09 | 0.00 | 0.688596E+09 | 57710369.90 | 0.403134E+10 |
February | 0.971213E+09 | 0.00 | 0.971213E+09 | 0.161130E+09 | 0.344414E+10 |
March | 0.148799E+10 | 0.00 | 0.148799E+10 | 0.529667E+09 | 0.315807E+10 |
April | 0.234452E+10 | 10493085.83 | 0.233403E+10 | 0.149111E+10 | 0.259093E+10 |
May | 0.302895E+10 | 0.146132E+09 | 0.288282E+10 | 0.195174E+10 | 0.215781E+10 |
June | 0.324031E+10 | 0.203188E+09 | 0.303712E+10 | 0.270021E+10 | 0.165180E+10 |
July | 0.317606E+10 | 0.181084E+09 | 0.299498E+10 | 0.282795E+10 | 0.157676E+10 |
August | 0.249655E+10 | 39114720.84 | 0.245743E+10 | 0.217015E+10 | 0.177178E+10 |
September | 0.183892E+10 | 406915.76 | 0.183851E+10 | 0.136621E+10 | 0.228789E+10 |
October | 0.121764E+10 | 0.00 | 0.121764E+10 | 0.510470E+09 | 0.303358E+10 |
November | 0.708023E+09 | 0.00 | 0.708023E+09 | 84759485.47 | 0.348639E+10 |
December | 0.498234E+09 | 0.00 | 0.498234E+09 | 5209955.78 | 0.432034E+10 |
Annual Sum or Average | 0.216970E+11 | 0.580420E+09 | 0.211166E+11 | 0.138563E+11 | 0.335108E+11 |
Minimum of Months | 0.498234E+09 | 0.00 | 0.498234E+09 | 5209955.78 | 0.157676E+10 |
Maximum of Months | 0.324031E+10 | 0.203188E+09 | 0.303712E+10 | 0.282795E+10 | 0.432034E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.938315E+09 | 0.376923E+09 | 0.561392E+09 | 0.559196E+09 | 0.253665E+10 |
February | 0.126379E+10 | 0.466852E+09 | 0.796934E+09 | 0.829876E+09 | 0.219313E+10 |
March | 0.146219E+10 | 0.288143E+09 | 0.117404E+10 | 0.900358E+09 | 0.201531E+10 |
April | 0.379944E+10 | 0.178538E+10 | 0.201406E+10 | 0.395422E+10 | 0.166010E+10 |
May | 0.412816E+10 | 0.180022E+10 | 0.232794E+10 | 0.417626E+10 | 0.148492E+10 |
June | 0.395431E+10 | 0.157931E+10 | 0.237500E+10 | 0.426420E+10 | 0.113225E+10 |
July | 0.417112E+10 | 0.177273E+10 | 0.239840E+10 | 0.469649E+10 | 0.108390E+10 |
August | 0.395123E+10 | 0.188786E+10 | 0.206337E+10 | 0.458161E+10 | 0.118220E+10 |
September | 0.344343E+10 | 0.183106E+10 | 0.161237E+10 | 0.385523E+10 | 0.146002E+10 |
October | 0.171760E+10 | 0.711816E+09 | 0.100578E+10 | 0.150930E+10 | 0.196519E+10 |
November | 0.866549E+09 | 0.295332E+09 | 0.571217E+09 | 0.504314E+09 | 0.223034E+10 |
December | 0.663626E+09 | 0.246727E+09 | 0.416899E+09 | 0.346218E+09 | 0.274900E+10 |
Annual Sum or Average | 0.303597E+11 | 0.130423E+11 | 0.173174E+11 | 0.301773E+11 | 0.216930E+11 |
Minimum of Months | 0.663626E+09 | 0.246727E+09 | 0.416899E+09 | 0.346218E+09 | 0.108390E+10 |
Maximum of Months | 0.417112E+10 | 0.188786E+10 | 0.239840E+10 | 0.469649E+10 | 0.274900E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.390938E+10 | 0.253070E+10 | 0.137868E+10 | 0.390275E+10 | 0.368873E+10 |
February | 0.431253E+10 | 0.263157E+10 | 0.168097E+10 | 0.440127E+10 | 0.330307E+10 |
March | 0.295197E+10 | 0.859480E+09 | 0.209249E+10 | 0.241357E+10 | 0.308424E+10 |
April | 0.593226E+10 | 0.268131E+10 | 0.325095E+10 | 0.674572E+10 | 0.270420E+10 |
May | 0.507008E+10 | 0.165065E+10 | 0.341943E+10 | 0.531496E+10 | 0.243629E+10 |
June | 0.451996E+10 | 0.109409E+10 | 0.342587E+10 | 0.493455E+10 | 0.183110E+10 |
July | 0.506053E+10 | 0.158476E+10 | 0.347577E+10 | 0.595258E+10 | 0.175946E+10 |
August | 0.592984E+10 | 0.266746E+10 | 0.326238E+10 | 0.739456E+10 | 0.191851E+10 |
September | 0.678147E+10 | 0.397270E+10 | 0.280877E+10 | 0.837272E+10 | 0.234533E+10 |
October | 0.481445E+10 | 0.281383E+10 | 0.200062E+10 | 0.531261E+10 | 0.301486E+10 |
November | 0.330333E+10 | 0.200950E+10 | 0.129383E+10 | 0.329865E+10 | 0.335465E+10 |
December | 0.270547E+10 | 0.173341E+10 | 0.972062E+09 | 0.262156E+10 | 0.411753E+10 |
Annual Sum or Average | 0.552913E+11 | 0.262295E+11 | 0.290618E+11 | 0.606655E+11 | 0.335579E+11 |
Minimum of Months | 0.270547E+10 | 0.859480E+09 | 0.972062E+09 | 0.241357E+10 | 0.175946E+10 |
Maximum of Months | 0.678147E+10 | 0.397270E+10 | 0.347577E+10 | 0.837272E+10 | 0.411753E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.912466E+09 | 0.301482E+09 | 0.610983E+09 | 0.562205E+09 | 0.258213E+10 |
February | 0.145922E+10 | 0.616130E+09 | 0.843091E+09 | 0.116676E+10 | 0.225874E+10 |
March | 0.146082E+10 | 0.279454E+09 | 0.118136E+10 | 0.909456E+09 | 0.204395E+10 |
April | 0.333566E+10 | 0.132495E+10 | 0.201071E+10 | 0.341817E+10 | 0.175861E+10 |
May | 0.404395E+10 | 0.164441E+10 | 0.239954E+10 | 0.411244E+10 | 0.156939E+10 |
June | 0.422616E+10 | 0.173975E+10 | 0.248641E+10 | 0.464985E+10 | 0.120098E+10 |
July | 0.444763E+10 | 0.196097E+10 | 0.248666E+10 | 0.511099E+10 | 0.115627E+10 |
August | 0.373571E+10 | 0.161746E+10 | 0.211825E+10 | 0.433543E+10 | 0.126677E+10 |
September | 0.290036E+10 | 0.130059E+10 | 0.159977E+10 | 0.322328E+10 | 0.155626E+10 |
October | 0.159880E+10 | 0.574922E+09 | 0.102388E+10 | 0.140153E+10 | 0.202186E+10 |
November | 0.837306E+09 | 0.244420E+09 | 0.592886E+09 | 0.516780E+09 | 0.229084E+10 |
December | 0.489738E+09 | 0.103345E+09 | 0.386393E+09 | 0.185389E+09 | 0.284862E+10 |
Annual Sum or Average | 0.294478E+11 | 0.117079E+11 | 0.177399E+11 | 0.295923E+11 | 0.225544E+11 |
Minimum of Months | 0.489738E+09 | 0.103345E+09 | 0.386393E+09 | 0.185389E+09 | 0.115627E+10 |
Maximum of Months | 0.444763E+10 | 0.196097E+10 | 0.248666E+10 | 0.511099E+10 | 0.284862E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 27.41 | 1417.52 | 257.09 | 0.00 | 257.09 | 0.00 | 0.00 |
February | 80.10 | 1331.03 | 401.46 | 0.00 | 401.46 | 0.00 | 0.00 |
March | 215.42 | 1104.60 | 555.55 | 0.00 | 555.55 | 0.00 | 0.00 |
April | 592.26 | 943.49 | 904.52 | 4.05 | 900.47 | 0.00 | 0.00 |
May | 751.28 | 761.79 | 1130.88 | 54.56 | 1076.32 | 0.00 | 0.00 |
June | 1052.13 | 609.81 | 1250.12 | 78.39 | 1171.73 | 0.00 | 0.00 |
July | 1064.80 | 564.36 | 1185.81 | 67.61 | 1118.20 | 0.00 | 0.00 |
August | 818.56 | 631.27 | 932.10 | 14.60 | 917.50 | 0.00 | 0.00 |
September | 541.50 | 831.32 | 709.46 | 0.16 | 709.30 | 0.00 | 0.00 |
October | 210.40 | 1043.69 | 454.62 | 0.00 | 454.62 | 0.00 | 0.00 |
November | 41.86 | 1243.13 | 273.16 | 0.00 | 273.16 | 0.00 | 0.00 |
December | 4.74 | 1511.28 | 186.02 | 0.00 | 186.02 | 0.00 | 0.00 |
Annual Sum or Average | 451.91 | 997.73 | 688.01 | 18.40 | 669.60 | 0.00 | 0.00 |
Minimum of Months | 4.74 | 564.36 | 186.02 | 0.00 | 186.02 | 0.00 | 0.00 |
Maximum of Months | 1064.80 | 1511.28 | 1250.12 | 78.39 | 1171.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 218.20 | 891.30 | 350.33 | 140.73 | 209.60 | 0.00 | 0.00 |
February | 358.73 | 847.20 | 522.40 | 192.98 | 329.42 | 0.00 | 0.00 |
March | 354.08 | 704.51 | 545.92 | 107.58 | 438.34 | 0.00 | 0.00 |
April | 1538.81 | 608.65 | 1465.83 | 688.80 | 777.03 | 0.00 | 0.00 |
May | 1572.37 | 527.27 | 1541.28 | 672.12 | 869.15 | 0.00 | 0.00 |
June | 1652.55 | 419.24 | 1525.58 | 609.30 | 916.28 | 0.00 | 0.00 |
July | 1759.79 | 389.05 | 1557.32 | 661.86 | 895.46 | 0.00 | 0.00 |
August | 1717.00 | 423.39 | 1475.22 | 704.85 | 770.37 | 0.00 | 0.00 |
September | 1498.59 | 534.74 | 1328.48 | 706.43 | 622.06 | 0.00 | 0.00 |
October | 580.02 | 677.51 | 641.28 | 265.76 | 375.52 | 0.00 | 0.00 |
November | 206.33 | 794.60 | 334.32 | 113.94 | 220.38 | 0.00 | 0.00 |
December | 136.12 | 962.64 | 247.77 | 92.12 | 155.65 | 0.00 | 0.00 |
Annual Sum or Average | 968.21 | 647.36 | 962.70 | 413.57 | 549.13 | 0.00 | 0.00 |
Minimum of Months | 136.12 | 389.05 | 247.77 | 92.12 | 155.65 | 0.00 | 0.00 |
Maximum of Months | 1759.79 | 962.64 | 1557.32 | 706.43 | 916.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1474.35 | 1296.25 | 1459.60 | 944.86 | 514.74 | 0.00 | 0.00 |
February | 1841.75 | 1280.46 | 1782.63 | 1087.78 | 694.84 | 0.00 | 0.00 |
March | 923.04 | 1079.40 | 1102.14 | 320.89 | 781.24 | 0.00 | 0.00 |
April | 2614.63 | 990.24 | 2288.68 | 1034.46 | 1254.22 | 0.00 | 0.00 |
May | 1997.10 | 861.32 | 1892.95 | 616.28 | 1276.67 | 0.00 | 0.00 |
June | 1909.77 | 675.45 | 1743.81 | 422.10 | 1321.71 | 0.00 | 0.00 |
July | 2226.64 | 628.84 | 1889.39 | 591.68 | 1297.70 | 0.00 | 0.00 |
August | 2763.87 | 684.93 | 2213.95 | 995.92 | 1218.03 | 0.00 | 0.00 |
September | 3239.36 | 858.40 | 2616.31 | 1532.68 | 1083.63 | 0.00 | 0.00 |
October | 2002.80 | 1042.87 | 1797.51 | 1050.56 | 746.95 | 0.00 | 0.00 |
November | 1291.22 | 1198.48 | 1274.43 | 775.27 | 499.16 | 0.00 | 0.00 |
December | 993.35 | 1442.03 | 1010.11 | 647.18 | 362.93 | 0.00 | 0.00 |
Annual Sum or Average | 1937.08 | 1001.74 | 1753.27 | 831.73 | 921.54 | 0.00 | 0.00 |
Minimum of Months | 923.04 | 628.84 | 1010.11 | 320.89 | 362.93 | 0.00 | 0.00 |
Maximum of Months | 3239.36 | 1442.03 | 2616.31 | 1532.68 | 1321.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 216.57 | 907.90 | 340.68 | 112.56 | 228.12 | 0.00 | 0.00 |
February | 493.33 | 874.17 | 603.18 | 254.68 | 348.50 | 0.00 | 0.00 |
March | 352.59 | 714.65 | 545.41 | 104.34 | 441.07 | 0.00 | 0.00 |
April | 1329.15 | 642.44 | 1286.91 | 511.17 | 775.74 | 0.00 | 0.00 |
May | 1545.37 | 554.58 | 1509.84 | 613.95 | 895.89 | 0.00 | 0.00 |
June | 1797.02 | 442.86 | 1630.46 | 671.20 | 959.26 | 0.00 | 0.00 |
July | 1910.48 | 413.05 | 1660.56 | 732.14 | 928.41 | 0.00 | 0.00 |
August | 1621.16 | 451.82 | 1394.76 | 603.89 | 790.87 | 0.00 | 0.00 |
September | 1251.66 | 567.26 | 1118.96 | 501.77 | 617.20 | 0.00 | 0.00 |
October | 536.55 | 697.20 | 596.92 | 214.65 | 382.27 | 0.00 | 0.00 |
November | 207.54 | 817.42 | 323.03 | 94.30 | 228.74 | 0.00 | 0.00 |
December | 73.11 | 997.52 | 182.85 | 38.58 | 144.26 | 0.00 | 0.00 |
Annual Sum or Average | 946.04 | 672.37 | 933.78 | 371.25 | 562.53 | 0.00 | 0.00 |
Minimum of Months | 73.11 | 413.05 | 182.85 | 38.58 | 144.26 | 0.00 | 0.00 |
Maximum of Months | 1910.48 | 997.52 | 1660.56 | 732.14 | 959.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 24.87 | 1478.82 | 257.09 | 0.00 | 257.09 | 0.00 | 0.00 |
February | 75.59 | 1391.80 | 401.45 | 0.00 | 401.45 | 0.00 | 0.00 |
March | 217.86 | 1141.61 | 555.54 | 0.00 | 555.54 | 0.00 | 0.00 |
April | 618.40 | 951.28 | 904.50 | 4.05 | 900.45 | 0.00 | 0.00 |
May | 773.75 | 775.12 | 1130.86 | 54.56 | 1076.30 | 0.00 | 0.00 |
June | 1077.30 | 617.55 | 1250.09 | 78.39 | 1171.70 | 0.00 | 0.00 |
July | 1084.05 | 574.35 | 1185.78 | 67.61 | 1118.17 | 0.00 | 0.00 |
August | 834.53 | 642.65 | 932.09 | 14.60 | 917.48 | 0.00 | 0.00 |
September | 545.11 | 864.02 | 709.44 | 0.16 | 709.29 | 0.00 | 0.00 |
October | 199.78 | 1123.28 | 454.61 | 0.00 | 454.61 | 0.00 | 0.00 |
November | 34.38 | 1346.37 | 273.15 | 0.00 | 273.15 | 0.00 | 0.00 |
December | 1.93 | 1615.96 | 186.01 | 0.00 | 186.01 | 0.00 | 0.00 |
Annual Sum or Average | 459.21 | 1041.79 | 687.99 | 18.40 | 669.59 | 0.00 | 0.00 |
Minimum of Months | 1.93 | 574.35 | 186.01 | 0.00 | 186.01 | 0.00 | 0.00 |
Maximum of Months | 1084.05 | 1615.96 | 1250.09 | 78.39 | 1171.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 214.96 | 935.05 | 350.32 | 140.72 | 209.60 | 0.00 | 0.00 |
February | 354.17 | 891.00 | 522.39 | 192.97 | 329.42 | 0.00 | 0.00 |
March | 355.55 | 730.77 | 545.91 | 107.58 | 438.33 | 0.00 | 0.00 |
April | 1547.21 | 634.31 | 1465.81 | 688.79 | 777.02 | 0.00 | 0.00 |
May | 1580.04 | 553.47 | 1541.25 | 672.11 | 869.14 | 0.00 | 0.00 |
June | 1664.46 | 435.27 | 1525.56 | 609.29 | 916.27 | 0.00 | 0.00 |
July | 1769.62 | 407.41 | 1557.29 | 661.85 | 895.45 | 0.00 | 0.00 |
August | 1724.79 | 445.34 | 1475.20 | 704.83 | 770.36 | 0.00 | 0.00 |
September | 1499.11 | 572.26 | 1328.46 | 706.41 | 622.05 | 0.00 | 0.00 |
October | 570.84 | 739.85 | 641.27 | 265.76 | 375.51 | 0.00 | 0.00 |
November | 198.06 | 864.96 | 334.31 | 113.94 | 220.37 | 0.00 | 0.00 |
December | 130.82 | 1029.36 | 247.77 | 92.12 | 155.65 | 0.00 | 0.00 |
Annual Sum or Average | 969.66 | 685.56 | 962.69 | 413.56 | 549.12 | 0.00 | 0.00 |
Minimum of Months | 130.82 | 407.41 | 247.77 | 92.12 | 155.65 | 0.00 | 0.00 |
Maximum of Months | 1769.62 | 1029.36 | 1557.29 | 706.41 | 916.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1480.75 | 1365.12 | 1459.54 | 944.82 | 514.72 | 0.00 | 0.00 |
February | 1850.30 | 1358.14 | 1782.56 | 1087.74 | 694.82 | 0.00 | 0.00 |
March | 944.75 | 1110.90 | 1102.10 | 320.88 | 781.22 | 0.00 | 0.00 |
April | 2647.13 | 1024.20 | 2288.60 | 1034.41 | 1254.18 | 0.00 | 0.00 |
May | 2032.79 | 885.33 | 1892.89 | 616.26 | 1276.63 | 0.00 | 0.00 |
June | 1947.61 | 685.50 | 1743.75 | 422.09 | 1321.67 | 0.00 | 0.00 |
July | 2254.03 | 649.78 | 1889.32 | 591.66 | 1297.67 | 0.00 | 0.00 |
August | 2784.12 | 721.07 | 2213.87 | 995.87 | 1217.99 | 0.00 | 0.00 |
September | 3248.93 | 927.20 | 2616.21 | 1532.61 | 1083.60 | 0.00 | 0.00 |
October | 2000.55 | 1142.90 | 1797.44 | 1050.52 | 746.92 | 0.00 | 0.00 |
November | 1289.86 | 1305.06 | 1274.38 | 775.24 | 499.15 | 0.00 | 0.00 |
December | 993.94 | 1530.72 | 1010.07 | 647.15 | 362.91 | 0.00 | 0.00 |
Annual Sum or Average | 1953.52 | 1057.17 | 1753.21 | 831.70 | 921.51 | 0.00 | 0.00 |
Minimum of Months | 944.75 | 649.78 | 1010.07 | 320.88 | 362.91 | 0.00 | 0.00 |
Maximum of Months | 3248.93 | 1530.72 | 2616.21 | 1532.61 | 1321.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 215.92 | 952.16 | 340.67 | 112.56 | 228.11 | 0.00 | 0.00 |
February | 492.73 | 922.17 | 603.17 | 254.68 | 348.50 | 0.00 | 0.00 |
March | 357.29 | 742.56 | 545.40 | 104.33 | 441.07 | 0.00 | 0.00 |
April | 1341.16 | 667.28 | 1286.89 | 511.16 | 775.73 | 0.00 | 0.00 |
May | 1556.04 | 583.88 | 1509.82 | 613.94 | 895.88 | 0.00 | 0.00 |
June | 1810.95 | 465.00 | 1630.44 | 671.19 | 959.25 | 0.00 | 0.00 |
July | 1923.07 | 435.39 | 1660.53 | 732.13 | 928.40 | 0.00 | 0.00 |
August | 1631.36 | 476.74 | 1394.74 | 603.88 | 790.86 | 0.00 | 0.00 |
September | 1252.71 | 606.04 | 1118.95 | 501.76 | 617.19 | 0.00 | 0.00 |
October | 528.71 | 760.57 | 596.92 | 214.65 | 382.27 | 0.00 | 0.00 |
November | 202.39 | 889.41 | 323.03 | 94.30 | 228.73 | 0.00 | 0.00 |
December | 70.61 | 1064.26 | 182.84 | 38.58 | 144.26 | 0.00 | 0.00 |
Annual Sum or Average | 950.10 | 712.70 | 933.77 | 371.25 | 562.52 | 0.00 | 0.00 |
Minimum of Months | 70.61 | 435.39 | 182.84 | 38.58 | 144.26 | 0.00 | 0.00 |
Maximum of Months | 1923.07 | 1064.26 | 1660.53 | 732.13 | 959.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 21.55 | 1505.13 | 257.09 | 0.00 | 257.09 | 0.00 | 0.00 |
February | 66.60 | 1423.67 | 401.46 | 0.00 | 401.46 | 0.00 | 0.00 |
March | 197.76 | 1179.09 | 555.55 | 0.00 | 555.55 | 0.00 | 0.00 |
April | 575.27 | 999.59 | 904.52 | 4.05 | 900.47 | 0.00 | 0.00 |
May | 728.70 | 805.63 | 1130.88 | 54.56 | 1076.32 | 0.00 | 0.00 |
June | 1041.75 | 637.27 | 1250.12 | 78.39 | 1171.73 | 0.00 | 0.00 |
July | 1055.84 | 588.69 | 1185.81 | 67.61 | 1118.20 | 0.00 | 0.00 |
August | 810.24 | 661.51 | 932.10 | 14.60 | 917.50 | 0.00 | 0.00 |
September | 527.09 | 882.67 | 709.46 | 0.16 | 709.30 | 0.00 | 0.00 |
October | 190.59 | 1132.61 | 454.62 | 0.00 | 454.62 | 0.00 | 0.00 |
November | 32.70 | 1345.06 | 273.16 | 0.00 | 273.16 | 0.00 | 0.00 |
December | 1.95 | 1613.03 | 186.02 | 0.00 | 186.02 | 0.00 | 0.00 |
Annual Sum or Average | 439.38 | 1062.62 | 688.01 | 18.40 | 669.60 | 0.00 | 0.00 |
Minimum of Months | 1.95 | 588.69 | 186.02 | 0.00 | 186.02 | 0.00 | 0.00 |
Maximum of Months | 1055.84 | 1613.03 | 1250.12 | 78.39 | 1171.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 208.78 | 947.08 | 350.33 | 140.73 | 209.60 | 0.00 | 0.00 |
February | 343.04 | 906.55 | 522.40 | 192.98 | 329.42 | 0.00 | 0.00 |
March | 336.16 | 752.43 | 545.92 | 107.58 | 438.34 | 0.00 | 0.00 |
April | 1525.55 | 640.47 | 1465.83 | 688.80 | 777.03 | 0.00 | 0.00 |
May | 1559.24 | 554.41 | 1541.28 | 672.12 | 869.15 | 0.00 | 0.00 |
June | 1645.14 | 436.83 | 1525.58 | 609.30 | 916.28 | 0.00 | 0.00 |
July | 1753.47 | 404.68 | 1557.32 | 661.86 | 895.46 | 0.00 | 0.00 |
August | 1710.58 | 441.38 | 1475.22 | 704.85 | 770.37 | 0.00 | 0.00 |
September | 1487.36 | 563.28 | 1328.48 | 706.43 | 622.06 | 0.00 | 0.00 |
October | 563.51 | 733.72 | 641.28 | 265.76 | 375.52 | 0.00 | 0.00 |
November | 194.57 | 860.47 | 334.32 | 113.94 | 220.38 | 0.00 | 0.00 |
December | 129.26 | 1026.36 | 247.77 | 92.12 | 155.65 | 0.00 | 0.00 |
Annual Sum or Average | 956.92 | 687.88 | 962.70 | 413.57 | 549.13 | 0.00 | 0.00 |
Minimum of Months | 129.26 | 404.68 | 247.77 | 92.12 | 155.65 | 0.00 | 0.00 |
Maximum of Months | 1753.47 | 1026.36 | 1557.32 | 706.43 | 916.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1457.12 | 1377.21 | 1459.60 | 944.86 | 514.74 | 0.00 | 0.00 |
February | 1819.31 | 1365.36 | 1782.63 | 1087.78 | 694.84 | 0.00 | 0.00 |
March | 901.13 | 1151.52 | 1102.14 | 320.89 | 781.24 | 0.00 | 0.00 |
April | 2602.52 | 1043.29 | 2288.68 | 1034.46 | 1254.22 | 0.00 | 0.00 |
May | 1984.38 | 909.61 | 1892.95 | 616.28 | 1276.67 | 0.00 | 0.00 |
June | 1903.76 | 706.44 | 1743.81 | 422.10 | 1321.71 | 0.00 | 0.00 |
July | 2222.44 | 656.91 | 1889.39 | 591.68 | 1297.70 | 0.00 | 0.00 |
August | 2760.81 | 716.29 | 2213.95 | 995.92 | 1218.03 | 0.00 | 0.00 |
September | 3230.22 | 904.83 | 2616.31 | 1532.68 | 1083.63 | 0.00 | 0.00 |
October | 1983.50 | 1125.62 | 1797.51 | 1050.56 | 746.95 | 0.00 | 0.00 |
November | 1272.63 | 1294.23 | 1274.43 | 775.27 | 499.16 | 0.00 | 0.00 |
December | 978.78 | 1537.31 | 1010.11 | 647.18 | 362.93 | 0.00 | 0.00 |
Annual Sum or Average | 1923.69 | 1064.12 | 1753.27 | 831.73 | 921.54 | 0.00 | 0.00 |
Minimum of Months | 901.13 | 656.91 | 1010.11 | 320.89 | 362.93 | 0.00 | 0.00 |
Maximum of Months | 3230.22 | 1537.31 | 2616.31 | 1532.68 | 1321.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 209.90 | 964.06 | 340.68 | 112.56 | 228.12 | 0.00 | 0.00 |
February | 482.29 | 933.67 | 603.18 | 254.68 | 348.50 | 0.00 | 0.00 |
March | 339.55 | 763.12 | 545.41 | 104.34 | 441.07 | 0.00 | 0.00 |
April | 1318.74 | 678.48 | 1286.91 | 511.17 | 775.74 | 0.00 | 0.00 |
May | 1535.41 | 585.94 | 1509.84 | 613.95 | 895.89 | 0.00 | 0.00 |
June | 1793.92 | 463.34 | 1630.46 | 671.20 | 959.26 | 0.00 | 0.00 |
July | 1908.23 | 431.70 | 1660.56 | 732.14 | 928.41 | 0.00 | 0.00 |
August | 1618.67 | 472.96 | 1394.76 | 603.89 | 790.87 | 0.00 | 0.00 |
September | 1243.55 | 600.41 | 1118.96 | 501.77 | 617.20 | 0.00 | 0.00 |
October | 523.27 | 754.88 | 596.92 | 214.65 | 382.27 | 0.00 | 0.00 |
November | 199.38 | 883.81 | 323.03 | 94.30 | 228.74 | 0.00 | 0.00 |
December | 69.22 | 1063.55 | 182.85 | 38.58 | 144.26 | 0.00 | 0.00 |
Annual Sum or Average | 938.36 | 715.20 | 933.78 | 371.25 | 562.53 | 0.00 | 0.00 |
Minimum of Months | 69.22 | 431.70 | 182.85 | 38.58 | 144.26 | 0.00 | 0.00 |
Maximum of Months | 1908.23 | 1063.55 | 1660.56 | 732.14 | 959.26 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 73422361.18 | 0.379669E+10 | 0.688596E+09 | 0.00 | 0.688596E+09 | 0.00 | 0.00 |
February | 0.193773E+09 | 0.322003E+10 | 0.971213E+09 | 0.00 | 0.971213E+09 | 0.00 | 0.00 |
March | 0.576972E+09 | 0.295856E+10 | 0.148799E+10 | 0.00 | 0.148799E+10 | 0.00 | 0.00 |
April | 0.153514E+10 | 0.244552E+10 | 0.234452E+10 | 10493085.83 | 0.233403E+10 | 0.00 | 0.00 |
May | 0.201222E+10 | 0.204037E+10 | 0.302895E+10 | 0.146132E+09 | 0.288282E+10 | 0.00 | 0.00 |
June | 0.272713E+10 | 0.158064E+10 | 0.324031E+10 | 0.203188E+09 | 0.303712E+10 | 0.00 | 0.00 |
July | 0.285196E+10 | 0.151159E+10 | 0.317606E+10 | 0.181084E+09 | 0.299498E+10 | 0.00 | 0.00 |
August | 0.219244E+10 | 0.169079E+10 | 0.249655E+10 | 39114720.84 | 0.245743E+10 | 0.00 | 0.00 |
September | 0.140358E+10 | 0.215478E+10 | 0.183892E+10 | 406915.76 | 0.183851E+10 | 0.00 | 0.00 |
October | 0.563543E+09 | 0.279542E+10 | 0.121764E+10 | 0.00 | 0.121764E+10 | 0.00 | 0.00 |
November | 0.108496E+09 | 0.322218E+10 | 0.708023E+09 | 0.00 | 0.708023E+09 | 0.00 | 0.00 |
December | 12685898.69 | 0.404780E+10 | 0.498234E+09 | 0.00 | 0.498234E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.142514E+11 | 0.314644E+11 | 0.216970E+11 | 0.580420E+09 | 0.211166E+11 | 0.00 | 0.00 |
Minimum of Months | 12685898.69 | 0.151159E+10 | 0.498234E+09 | 0.00 | 0.498234E+09 | 0.00 | 0.00 |
Maximum of Months | 0.285196E+10 | 0.404780E+10 | 0.324031E+10 | 0.203188E+09 | 0.303712E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.584419E+09 | 0.238726E+10 | 0.938315E+09 | 0.376923E+09 | 0.561392E+09 | 0.00 | 0.00 |
February | 0.867836E+09 | 0.204954E+10 | 0.126379E+10 | 0.466852E+09 | 0.796934E+09 | 0.00 | 0.00 |
March | 0.948358E+09 | 0.188696E+10 | 0.146219E+10 | 0.288143E+09 | 0.117404E+10 | 0.00 | 0.00 |
April | 0.398860E+10 | 0.157763E+10 | 0.379944E+10 | 0.178538E+10 | 0.201406E+10 | 0.00 | 0.00 |
May | 0.421144E+10 | 0.141225E+10 | 0.412816E+10 | 0.180022E+10 | 0.232794E+10 | 0.00 | 0.00 |
June | 0.428341E+10 | 0.108668E+10 | 0.395431E+10 | 0.157931E+10 | 0.237500E+10 | 0.00 | 0.00 |
July | 0.471343E+10 | 0.104203E+10 | 0.417112E+10 | 0.177273E+10 | 0.239840E+10 | 0.00 | 0.00 |
August | 0.459881E+10 | 0.113401E+10 | 0.395123E+10 | 0.188786E+10 | 0.206337E+10 | 0.00 | 0.00 |
September | 0.388435E+10 | 0.138605E+10 | 0.344343E+10 | 0.183106E+10 | 0.161237E+10 | 0.00 | 0.00 |
October | 0.155353E+10 | 0.181465E+10 | 0.171760E+10 | 0.711816E+09 | 0.100578E+10 | 0.00 | 0.00 |
November | 0.534814E+09 | 0.205962E+10 | 0.866549E+09 | 0.295332E+09 | 0.571217E+09 | 0.00 | 0.00 |
December | 0.364597E+09 | 0.257833E+10 | 0.663626E+09 | 0.246727E+09 | 0.416899E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.305336E+11 | 0.204150E+11 | 0.303597E+11 | 0.130423E+11 | 0.173174E+11 | 0.00 | 0.00 |
Minimum of Months | 0.364597E+09 | 0.104203E+10 | 0.663626E+09 | 0.246727E+09 | 0.416899E+09 | 0.00 | 0.00 |
Maximum of Months | 0.471343E+10 | 0.257833E+10 | 0.417112E+10 | 0.188786E+10 | 0.239840E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.394890E+10 | 0.347188E+10 | 0.390938E+10 | 0.253070E+10 | 0.137868E+10 | 0.00 | 0.00 |
February | 0.445556E+10 | 0.309770E+10 | 0.431253E+10 | 0.263157E+10 | 0.168097E+10 | 0.00 | 0.00 |
March | 0.247227E+10 | 0.289108E+10 | 0.295197E+10 | 0.859480E+09 | 0.209249E+10 | 0.00 | 0.00 |
April | 0.677712E+10 | 0.256671E+10 | 0.593226E+10 | 0.268131E+10 | 0.325095E+10 | 0.00 | 0.00 |
May | 0.534902E+10 | 0.230695E+10 | 0.507008E+10 | 0.165065E+10 | 0.341943E+10 | 0.00 | 0.00 |
June | 0.495014E+10 | 0.175075E+10 | 0.451996E+10 | 0.109409E+10 | 0.342587E+10 | 0.00 | 0.00 |
July | 0.596384E+10 | 0.168428E+10 | 0.506053E+10 | 0.158476E+10 | 0.347577E+10 | 0.00 | 0.00 |
August | 0.740275E+10 | 0.183451E+10 | 0.592984E+10 | 0.266746E+10 | 0.326238E+10 | 0.00 | 0.00 |
September | 0.839641E+10 | 0.222498E+10 | 0.678147E+10 | 0.397270E+10 | 0.280877E+10 | 0.00 | 0.00 |
October | 0.536429E+10 | 0.279323E+10 | 0.481445E+10 | 0.281383E+10 | 0.200062E+10 | 0.00 | 0.00 |
November | 0.334684E+10 | 0.310647E+10 | 0.330333E+10 | 0.200950E+10 | 0.129383E+10 | 0.00 | 0.00 |
December | 0.266060E+10 | 0.386233E+10 | 0.270547E+10 | 0.173341E+10 | 0.972062E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.610877E+11 | 0.315909E+11 | 0.552913E+11 | 0.262295E+11 | 0.290618E+11 | 0.00 | 0.00 |
Minimum of Months | 0.247227E+10 | 0.168428E+10 | 0.270547E+10 | 0.859480E+09 | 0.972062E+09 | 0.00 | 0.00 |
Maximum of Months | 0.839641E+10 | 0.386233E+10 | 0.678147E+10 | 0.397270E+10 | 0.347577E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.580051E+09 | 0.243173E+10 | 0.912466E+09 | 0.301482E+09 | 0.610983E+09 | 0.00 | 0.00 |
February | 0.119347E+10 | 0.211478E+10 | 0.145922E+10 | 0.616130E+09 | 0.843091E+09 | 0.00 | 0.00 |
March | 0.944378E+09 | 0.191412E+10 | 0.146082E+10 | 0.279454E+09 | 0.118136E+10 | 0.00 | 0.00 |
April | 0.344515E+10 | 0.166520E+10 | 0.333566E+10 | 0.132495E+10 | 0.201071E+10 | 0.00 | 0.00 |
May | 0.413912E+10 | 0.148538E+10 | 0.404395E+10 | 0.164441E+10 | 0.239954E+10 | 0.00 | 0.00 |
June | 0.465787E+10 | 0.114788E+10 | 0.422616E+10 | 0.173975E+10 | 0.248641E+10 | 0.00 | 0.00 |
July | 0.511703E+10 | 0.110632E+10 | 0.444763E+10 | 0.196097E+10 | 0.248666E+10 | 0.00 | 0.00 |
August | 0.434211E+10 | 0.121016E+10 | 0.373571E+10 | 0.161746E+10 | 0.211825E+10 | 0.00 | 0.00 |
September | 0.324429E+10 | 0.147034E+10 | 0.290036E+10 | 0.130059E+10 | 0.159977E+10 | 0.00 | 0.00 |
October | 0.143709E+10 | 0.186739E+10 | 0.159880E+10 | 0.574922E+09 | 0.102388E+10 | 0.00 | 0.00 |
November | 0.537934E+09 | 0.211874E+10 | 0.837306E+09 | 0.244420E+09 | 0.592886E+09 | 0.00 | 0.00 |
December | 0.195813E+09 | 0.267176E+10 | 0.489738E+09 | 0.103345E+09 | 0.386393E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.298343E+11 | 0.212038E+11 | 0.294478E+11 | 0.117079E+11 | 0.177399E+11 | 0.00 | 0.00 |
Minimum of Months | 0.195813E+09 | 0.110632E+10 | 0.489738E+09 | 0.103345E+09 | 0.386393E+09 | 0.00 | 0.00 |
Maximum of Months | 0.511703E+10 | 0.267176E+10 | 0.444763E+10 | 0.196097E+10 | 0.248666E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 66601751.14 | 0.396088E+10 | 0.688580E+09 | 0.00 | 0.688580E+09 | 0.00 | 0.00 |
February | 0.182858E+09 | 0.336704E+10 | 0.971191E+09 | 0.00 | 0.971191E+09 | 0.00 | 0.00 |
March | 0.583523E+09 | 0.305770E+10 | 0.148795E+10 | 0.00 | 0.148795E+10 | 0.00 | 0.00 |
April | 0.160289E+10 | 0.246571E+10 | 0.234447E+10 | 10492777.41 | 0.233398E+10 | 0.00 | 0.00 |
May | 0.207240E+10 | 0.207608E+10 | 0.302889E+10 | 0.146128E+09 | 0.288276E+10 | 0.00 | 0.00 |
June | 0.279237E+10 | 0.160069E+10 | 0.324024E+10 | 0.203182E+09 | 0.303706E+10 | 0.00 | 0.00 |
July | 0.290351E+10 | 0.153833E+10 | 0.317599E+10 | 0.181079E+09 | 0.299492E+10 | 0.00 | 0.00 |
August | 0.223521E+10 | 0.172127E+10 | 0.249650E+10 | 39113571.15 | 0.245738E+10 | 0.00 | 0.00 |
September | 0.141294E+10 | 0.223953E+10 | 0.183888E+10 | 406903.80 | 0.183847E+10 | 0.00 | 0.00 |
October | 0.535102E+09 | 0.300859E+10 | 0.121762E+10 | 0.00 | 0.121762E+10 | 0.00 | 0.00 |
November | 89106077.82 | 0.348978E+10 | 0.708007E+09 | 0.00 | 0.708007E+09 | 0.00 | 0.00 |
December | 5180400.37 | 0.432818E+10 | 0.498222E+09 | 0.00 | 0.498222E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.144817E+11 | 0.328538E+11 | 0.216965E+11 | 0.580403E+09 | 0.211161E+11 | 0.00 | 0.00 |
Minimum of Months | 5180400.37 | 0.153833E+10 | 0.498222E+09 | 0.00 | 0.498222E+09 | 0.00 | 0.00 |
Maximum of Months | 0.290351E+10 | 0.432818E+10 | 0.324024E+10 | 0.203182E+09 | 0.303706E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.575747E+09 | 0.250443E+10 | 0.938300E+09 | 0.376915E+09 | 0.561384E+09 | 0.00 | 0.00 |
February | 0.856802E+09 | 0.215552E+10 | 0.126377E+10 | 0.466843E+09 | 0.796922E+09 | 0.00 | 0.00 |
March | 0.952317E+09 | 0.195729E+10 | 0.146216E+10 | 0.288138E+09 | 0.117402E+10 | 0.00 | 0.00 |
April | 0.401038E+10 | 0.164413E+10 | 0.379938E+10 | 0.178535E+10 | 0.201403E+10 | 0.00 | 0.00 |
May | 0.423199E+10 | 0.148241E+10 | 0.412809E+10 | 0.180018E+10 | 0.232791E+10 | 0.00 | 0.00 |
June | 0.431429E+10 | 0.112823E+10 | 0.395425E+10 | 0.157928E+10 | 0.237497E+10 | 0.00 | 0.00 |
July | 0.473975E+10 | 0.109121E+10 | 0.417106E+10 | 0.177269E+10 | 0.239837E+10 | 0.00 | 0.00 |
August | 0.461967E+10 | 0.119279E+10 | 0.395116E+10 | 0.188782E+10 | 0.206334E+10 | 0.00 | 0.00 |
September | 0.388570E+10 | 0.148331E+10 | 0.344338E+10 | 0.183102E+10 | 0.161235E+10 | 0.00 | 0.00 |
October | 0.152894E+10 | 0.198161E+10 | 0.171757E+10 | 0.711802E+09 | 0.100577E+10 | 0.00 | 0.00 |
November | 0.513366E+09 | 0.224198E+10 | 0.866535E+09 | 0.295327E+09 | 0.571208E+09 | 0.00 | 0.00 |
December | 0.350385E+09 | 0.275705E+10 | 0.663615E+09 | 0.246722E+09 | 0.416893E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.305793E+11 | 0.216200E+11 | 0.303593E+11 | 0.130421E+11 | 0.173172E+11 | 0.00 | 0.00 |
Minimum of Months | 0.350385E+09 | 0.109121E+10 | 0.663615E+09 | 0.246722E+09 | 0.416893E+09 | 0.00 | 0.00 |
Maximum of Months | 0.473975E+10 | 0.275705E+10 | 0.417106E+10 | 0.188782E+10 | 0.239837E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.396604E+10 | 0.365634E+10 | 0.390923E+10 | 0.253060E+10 | 0.137863E+10 | 0.00 | 0.00 |
February | 0.447624E+10 | 0.328562E+10 | 0.431236E+10 | 0.263146E+10 | 0.168091E+10 | 0.00 | 0.00 |
March | 0.253043E+10 | 0.297542E+10 | 0.295186E+10 | 0.859444E+09 | 0.209241E+10 | 0.00 | 0.00 |
April | 0.686137E+10 | 0.265472E+10 | 0.593204E+10 | 0.268120E+10 | 0.325084E+10 | 0.00 | 0.00 |
May | 0.544463E+10 | 0.237126E+10 | 0.506990E+10 | 0.165058E+10 | 0.341932E+10 | 0.00 | 0.00 |
June | 0.504821E+10 | 0.177681E+10 | 0.451981E+10 | 0.109405E+10 | 0.342576E+10 | 0.00 | 0.00 |
July | 0.603719E+10 | 0.174038E+10 | 0.506036E+10 | 0.158470E+10 | 0.347567E+10 | 0.00 | 0.00 |
August | 0.745698E+10 | 0.193131E+10 | 0.592962E+10 | 0.266735E+10 | 0.326227E+10 | 0.00 | 0.00 |
September | 0.842123E+10 | 0.240331E+10 | 0.678121E+10 | 0.397253E+10 | 0.280868E+10 | 0.00 | 0.00 |
October | 0.535827E+10 | 0.306116E+10 | 0.481427E+10 | 0.281371E+10 | 0.200055E+10 | 0.00 | 0.00 |
November | 0.334332E+10 | 0.338271E+10 | 0.330320E+10 | 0.200942E+10 | 0.129379E+10 | 0.00 | 0.00 |
December | 0.266216E+10 | 0.409988E+10 | 0.270536E+10 | 0.173334E+10 | 0.972027E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.616061E+11 | 0.333389E+11 | 0.552892E+11 | 0.262284E+11 | 0.290609E+11 | 0.00 | 0.00 |
Minimum of Months | 0.253043E+10 | 0.174038E+10 | 0.270536E+10 | 0.859444E+09 | 0.972027E+09 | 0.00 | 0.00 |
Maximum of Months | 0.842123E+10 | 0.409988E+10 | 0.678121E+10 | 0.397253E+10 | 0.347567E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.578316E+09 | 0.255027E+10 | 0.912453E+09 | 0.301477E+09 | 0.610976E+09 | 0.00 | 0.00 |
February | 0.119201E+10 | 0.223092E+10 | 0.145920E+10 | 0.616120E+09 | 0.843081E+09 | 0.00 | 0.00 |
March | 0.956964E+09 | 0.198887E+10 | 0.146080E+10 | 0.279450E+09 | 0.118135E+10 | 0.00 | 0.00 |
April | 0.347628E+10 | 0.172958E+10 | 0.333562E+10 | 0.132493E+10 | 0.201069E+10 | 0.00 | 0.00 |
May | 0.416771E+10 | 0.156387E+10 | 0.404390E+10 | 0.164438E+10 | 0.239952E+10 | 0.00 | 0.00 |
June | 0.469398E+10 | 0.120528E+10 | 0.422611E+10 | 0.173972E+10 | 0.248638E+10 | 0.00 | 0.00 |
July | 0.515075E+10 | 0.116616E+10 | 0.444757E+10 | 0.196094E+10 | 0.248663E+10 | 0.00 | 0.00 |
August | 0.436942E+10 | 0.127691E+10 | 0.373567E+10 | 0.161743E+10 | 0.211823E+10 | 0.00 | 0.00 |
September | 0.324702E+10 | 0.157085E+10 | 0.290032E+10 | 0.130056E+10 | 0.159975E+10 | 0.00 | 0.00 |
October | 0.141609E+10 | 0.203710E+10 | 0.159878E+10 | 0.574913E+09 | 0.102387E+10 | 0.00 | 0.00 |
November | 0.524583E+09 | 0.230535E+10 | 0.837295E+09 | 0.244416E+09 | 0.592879E+09 | 0.00 | 0.00 |
December | 0.189115E+09 | 0.285052E+10 | 0.489732E+09 | 0.103344E+09 | 0.386388E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.299622E+11 | 0.224757E+11 | 0.294474E+11 | 0.117077E+11 | 0.177397E+11 | 0.00 | 0.00 |
Minimum of Months | 0.189115E+09 | 0.116616E+10 | 0.489732E+09 | 0.103344E+09 | 0.386388E+09 | 0.00 | 0.00 |
Maximum of Months | 0.515075E+10 | 0.285052E+10 | 0.444757E+10 | 0.196094E+10 | 0.248663E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 57710369.90 | 0.403134E+10 | 0.688596E+09 | 0.00 | 0.688596E+09 | 0.00 | 0.00 |
February | 0.161130E+09 | 0.344414E+10 | 0.971213E+09 | 0.00 | 0.971213E+09 | 0.00 | 0.00 |
March | 0.529667E+09 | 0.315807E+10 | 0.148799E+10 | 0.00 | 0.148799E+10 | 0.00 | 0.00 |
April | 0.149111E+10 | 0.259093E+10 | 0.234452E+10 | 10493085.83 | 0.233403E+10 | 0.00 | 0.00 |
May | 0.195174E+10 | 0.215781E+10 | 0.302895E+10 | 0.146132E+09 | 0.288282E+10 | 0.00 | 0.00 |
June | 0.270021E+10 | 0.165180E+10 | 0.324031E+10 | 0.203188E+09 | 0.303712E+10 | 0.00 | 0.00 |
July | 0.282795E+10 | 0.157676E+10 | 0.317606E+10 | 0.181084E+09 | 0.299498E+10 | 0.00 | 0.00 |
August | 0.217015E+10 | 0.177178E+10 | 0.249655E+10 | 39114720.84 | 0.245743E+10 | 0.00 | 0.00 |
September | 0.136621E+10 | 0.228789E+10 | 0.183892E+10 | 406915.76 | 0.183851E+10 | 0.00 | 0.00 |
October | 0.510470E+09 | 0.303358E+10 | 0.121764E+10 | 0.00 | 0.121764E+10 | 0.00 | 0.00 |
November | 84759485.47 | 0.348639E+10 | 0.708023E+09 | 0.00 | 0.708023E+09 | 0.00 | 0.00 |
December | 5209955.78 | 0.432034E+10 | 0.498234E+09 | 0.00 | 0.498234E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.138563E+11 | 0.335108E+11 | 0.216970E+11 | 0.580420E+09 | 0.211166E+11 | 0.00 | 0.00 |
Minimum of Months | 5209955.78 | 0.157676E+10 | 0.498234E+09 | 0.00 | 0.498234E+09 | 0.00 | 0.00 |
Maximum of Months | 0.282795E+10 | 0.432034E+10 | 0.324031E+10 | 0.203188E+09 | 0.303712E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.559196E+09 | 0.253665E+10 | 0.938315E+09 | 0.376923E+09 | 0.561392E+09 | 0.00 | 0.00 |
February | 0.829876E+09 | 0.219313E+10 | 0.126379E+10 | 0.466852E+09 | 0.796934E+09 | 0.00 | 0.00 |
March | 0.900358E+09 | 0.201531E+10 | 0.146219E+10 | 0.288143E+09 | 0.117404E+10 | 0.00 | 0.00 |
April | 0.395422E+10 | 0.166010E+10 | 0.379944E+10 | 0.178538E+10 | 0.201406E+10 | 0.00 | 0.00 |
May | 0.417626E+10 | 0.148492E+10 | 0.412816E+10 | 0.180022E+10 | 0.232794E+10 | 0.00 | 0.00 |
June | 0.426420E+10 | 0.113225E+10 | 0.395431E+10 | 0.157931E+10 | 0.237500E+10 | 0.00 | 0.00 |
July | 0.469649E+10 | 0.108390E+10 | 0.417112E+10 | 0.177273E+10 | 0.239840E+10 | 0.00 | 0.00 |
August | 0.458161E+10 | 0.118220E+10 | 0.395123E+10 | 0.188786E+10 | 0.206337E+10 | 0.00 | 0.00 |
September | 0.385523E+10 | 0.146002E+10 | 0.344343E+10 | 0.183106E+10 | 0.161237E+10 | 0.00 | 0.00 |
October | 0.150930E+10 | 0.196519E+10 | 0.171760E+10 | 0.711816E+09 | 0.100578E+10 | 0.00 | 0.00 |
November | 0.504314E+09 | 0.223034E+10 | 0.866549E+09 | 0.295332E+09 | 0.571217E+09 | 0.00 | 0.00 |
December | 0.346218E+09 | 0.274900E+10 | 0.663626E+09 | 0.246727E+09 | 0.416899E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.301773E+11 | 0.216930E+11 | 0.303597E+11 | 0.130423E+11 | 0.173174E+11 | 0.00 | 0.00 |
Minimum of Months | 0.346218E+09 | 0.108390E+10 | 0.663626E+09 | 0.246727E+09 | 0.416899E+09 | 0.00 | 0.00 |
Maximum of Months | 0.469649E+10 | 0.274900E+10 | 0.417112E+10 | 0.188786E+10 | 0.239840E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.390275E+10 | 0.368873E+10 | 0.390938E+10 | 0.253070E+10 | 0.137868E+10 | 0.00 | 0.00 |
February | 0.440127E+10 | 0.330307E+10 | 0.431253E+10 | 0.263157E+10 | 0.168097E+10 | 0.00 | 0.00 |
March | 0.241357E+10 | 0.308424E+10 | 0.295197E+10 | 0.859480E+09 | 0.209249E+10 | 0.00 | 0.00 |
April | 0.674572E+10 | 0.270420E+10 | 0.593226E+10 | 0.268131E+10 | 0.325095E+10 | 0.00 | 0.00 |
May | 0.531496E+10 | 0.243629E+10 | 0.507008E+10 | 0.165065E+10 | 0.341943E+10 | 0.00 | 0.00 |
June | 0.493455E+10 | 0.183110E+10 | 0.451996E+10 | 0.109409E+10 | 0.342587E+10 | 0.00 | 0.00 |
July | 0.595258E+10 | 0.175946E+10 | 0.506053E+10 | 0.158476E+10 | 0.347577E+10 | 0.00 | 0.00 |
August | 0.739456E+10 | 0.191851E+10 | 0.592984E+10 | 0.266746E+10 | 0.326238E+10 | 0.00 | 0.00 |
September | 0.837272E+10 | 0.234533E+10 | 0.678147E+10 | 0.397270E+10 | 0.280877E+10 | 0.00 | 0.00 |
October | 0.531261E+10 | 0.301486E+10 | 0.481445E+10 | 0.281383E+10 | 0.200062E+10 | 0.00 | 0.00 |
November | 0.329865E+10 | 0.335465E+10 | 0.330333E+10 | 0.200950E+10 | 0.129383E+10 | 0.00 | 0.00 |
December | 0.262156E+10 | 0.411753E+10 | 0.270547E+10 | 0.173341E+10 | 0.972062E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.606655E+11 | 0.335579E+11 | 0.552913E+11 | 0.262295E+11 | 0.290618E+11 | 0.00 | 0.00 |
Minimum of Months | 0.241357E+10 | 0.175946E+10 | 0.270547E+10 | 0.859480E+09 | 0.972062E+09 | 0.00 | 0.00 |
Maximum of Months | 0.837272E+10 | 0.411753E+10 | 0.678147E+10 | 0.397270E+10 | 0.347577E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.562205E+09 | 0.258213E+10 | 0.912466E+09 | 0.301482E+09 | 0.610983E+09 | 0.00 | 0.00 |
February | 0.116676E+10 | 0.225874E+10 | 0.145922E+10 | 0.616130E+09 | 0.843091E+09 | 0.00 | 0.00 |
March | 0.909456E+09 | 0.204395E+10 | 0.146082E+10 | 0.279454E+09 | 0.118136E+10 | 0.00 | 0.00 |
April | 0.341817E+10 | 0.175861E+10 | 0.333566E+10 | 0.132495E+10 | 0.201071E+10 | 0.00 | 0.00 |
May | 0.411244E+10 | 0.156939E+10 | 0.404395E+10 | 0.164441E+10 | 0.239954E+10 | 0.00 | 0.00 |
June | 0.464985E+10 | 0.120098E+10 | 0.422616E+10 | 0.173975E+10 | 0.248641E+10 | 0.00 | 0.00 |
July | 0.511099E+10 | 0.115627E+10 | 0.444763E+10 | 0.196097E+10 | 0.248666E+10 | 0.00 | 0.00 |
August | 0.433543E+10 | 0.126677E+10 | 0.373571E+10 | 0.161746E+10 | 0.211825E+10 | 0.00 | 0.00 |
September | 0.322328E+10 | 0.155626E+10 | 0.290036E+10 | 0.130059E+10 | 0.159977E+10 | 0.00 | 0.00 |
October | 0.140153E+10 | 0.202186E+10 | 0.159880E+10 | 0.574922E+09 | 0.102388E+10 | 0.00 | 0.00 |
November | 0.516780E+09 | 0.229084E+10 | 0.837306E+09 | 0.244420E+09 | 0.592886E+09 | 0.00 | 0.00 |
December | 0.185389E+09 | 0.284862E+10 | 0.489738E+09 | 0.103345E+09 | 0.386393E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.295923E+11 | 0.225544E+11 | 0.294478E+11 | 0.117079E+11 | 0.177399E+11 | 0.00 | 0.00 |
Minimum of Months | 0.185389E+09 | 0.115627E+10 | 0.489738E+09 | 0.103345E+09 | 0.386393E+09 | 0.00 | 0.00 |
Maximum of Months | 0.511099E+10 | 0.284862E+10 | 0.444763E+10 | 0.196097E+10 | 0.248666E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.531946E+10 | -0.459587E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -723588818.2 | 58.99 | 0.00 | 0.00 |
February | 0.484924E+10 | -0.420481E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -644428330.0 | 58.98 | 0.00 | 0.00 |
March | 0.565523E+10 | -0.494452E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -710713607.5 | 58.98 | 0.00 | 0.00 |
April | 0.503807E+10 | -0.436490E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -673171890.3 | 58.99 | 0.00 | 0.00 |
May | 0.525057E+10 | -0.455726E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -693303334.8 | 58.98 | 0.00 | 0.00 |
June | 0.507417E+10 | -0.440498E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -669188152.0 | 58.99 | 0.00 | 0.00 |
July | 0.475229E+10 | -0.406267E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689617729.5 | 58.98 | 0.00 | 0.00 |
August | 0.514920E+10 | -0.445807E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691139292.0 | 58.98 | 0.00 | 0.00 |
September | 0.471268E+10 | -0.404362E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -669057842.1 | 58.98 | 0.00 | 0.00 |
October | 0.496393E+10 | -0.426522E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -698703626.3 | 58.98 | 0.00 | 0.00 |
November | 0.499936E+10 | -0.431345E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -685903052.9 | 58.98 | 0.00 | 0.00 |
December | 0.510567E+10 | -0.438408E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -721588037.2 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.608699E+11 | -0.525995E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.827040E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.471268E+10 | -0.494452E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -723588818.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.565523E+10 | -0.404362E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -644428330.0 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.51 | 0.48 | 01-JAN-08:39 | 3977.40 | 36.18 | 191.00 | 221.17 | 3342.09 | 37.45 | 190.17 | 194.33 |
February | 217.00 | 0.50 | 0.48 | 01-FEB-11:39 | 5705.26 | 35.88 | 213.50 | 245.83 | 2725.45 | 31.76 | 199.00 | 221.67 |
March | 215.50 | 0.50 | 0.48 | 01-MAR-11:39 | 4201.49 | 30.93 | 182.17 | 309.83 | 1202.32 | 21.48 | 171.33 | 266.50 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:00 | 2640.16 | 19.55 | 24.00 | 353.83 | 1500.32 | 21.78 | 251.17 | 328.83 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:49 | 2094.72 | 19.17 | 0.17 | 408.83 | 1181.09 | 21.38 | 256.17 | 372.83 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-05:49 | 2035.25 | 19.47 | 0.00 | 411.17 | 1134.16 | 21.67 | 269.67 | 370.83 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-05:40 | 2030.81 | 19.23 | 2.00 | 419.83 | 1160.88 | 21.45 | 266.83 | 382.17 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:10 | 2357.99 | 19.20 | 15.83 | 381.50 | 1367.32 | 21.44 | 259.50 | 347.67 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 3496.91 | 21.23 | 53.83 | 329.83 | 1665.32 | 21.99 | 229.50 | 302.83 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:49 | 7215.65 | 35.01 | 216.83 | 279.50 | 2149.85 | 24.52 | 186.33 | 238.83 |
November | 171.33 | 0.50 | 0.48 | 01-NOV-11:39 | 4580.16 | 36.02 | 167.00 | 215.33 | 3827.32 | 37.35 | 168.00 | 173.00 |
December | 131.67 | 0.50 | 0.48 | 02-DEC-08:50 | 3851.35 | 37.06 | 128.50 | 182.00 | 3245.46 | 38.42 | 128.67 | 132.50 |
Annual Sum or Average | 3515.67 | 0.50 | 3284.66 | 24.70 | 1194.83 | 3758.67 | 1760.96 | 24.70 | 2576.33 | 3332.00 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 2030.81 | 19.17 | 0.00 | 182.00 | 1134.16 | 21.38 | 128.67 | 132.50 | |
Maximum of Months | 429.00 | 0.51 | 0.48 | 7215.65 | 37.06 | 216.83 | 419.83 | 3827.32 | 38.42 | 269.67 | 382.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.53 | 0.48 | 01-JAN-08:39 | 1446.63 | 23.17 | 82.50 | 208.67 | 863.46 | 23.76 | 80.00 | 142.83 |
February | 217.00 | 0.50 | 0.48 | 01-FEB-11:39 | 1716.84 | 21.23 | 62.33 | 236.17 | 983.39 | 23.88 | 85.17 | 192.83 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 1978.67 | 21.80 | 71.33 | 302.67 | 891.29 | 22.59 | 66.67 | 249.67 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:10 | 3675.92 | 22.80 | 107.17 | 363.00 | 2162.07 | 25.01 | 129.33 | 337.50 |
May | 417.17 | 0.49 | 0.48 | 01-MAY-06:40 | 3806.71 | 22.83 | 133.33 | 421.83 | 1716.82 | 22.72 | 76.00 | 380.50 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:49 | 3824.23 | 22.74 | 129.50 | 419.33 | 1756.65 | 23.52 | 81.50 | 387.83 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 3743.27 | 22.98 | 139.67 | 430.33 | 1710.40 | 23.57 | 89.67 | 400.33 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3612.02 | 23.33 | 127.83 | 389.67 | 1599.71 | 23.04 | 88.33 | 359.67 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 3414.77 | 23.60 | 109.33 | 336.83 | 1894.80 | 24.44 | 130.17 | 305.67 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:40 | 2664.16 | 23.03 | 82.33 | 271.17 | 1229.04 | 23.76 | 99.00 | 212.83 |
November | 171.33 | 0.51 | 0.48 | 01-NOV-11:39 | 1446.57 | 21.33 | 55.67 | 201.83 | 849.94 | 23.72 | 79.50 | 134.67 |
December | 131.67 | 0.51 | 0.48 | 02-DEC-08:50 | 1246.92 | 23.75 | 52.67 | 163.83 | 872.64 | 25.88 | 70.50 | 97.50 |
Annual Sum or Average | 3515.67 | 0.50 | 3068.71 | 22.80 | 1153.67 | 3745.33 | 1520.44 | 23.71 | 1075.83 | 3201.83 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1246.92 | 21.23 | 52.67 | 163.83 | 849.94 | 22.59 | 66.67 | 97.50 | |
Maximum of Months | 429.00 | 0.53 | 0.48 | 3824.23 | 23.75 | 139.67 | 430.33 | 2162.07 | 25.88 | 130.17 | 400.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.56 | 0.48 | 01-JAN-09:00 | 523.70 | 14.44 | 0.00 | 184.67 | 305.55 | 16.83 | 0.00 | 70.67 |
February | 217.00 | 0.52 | 0.48 | 01-FEB-11:39 | 694.17 | 16.21 | 0.00 | 221.33 | 407.49 | 18.50 | 0.00 | 139.17 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 858.10 | 16.97 | 0.00 | 299.00 | 466.99 | 19.03 | 2.83 | 216.17 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:00 | 1135.17 | 18.76 | 0.00 | 360.17 | 678.36 | 20.88 | 103.83 | 328.00 |
May | 417.17 | 0.49 | 0.48 | 01-MAY-06:49 | 1347.23 | 20.64 | 46.17 | 425.17 | 776.71 | 22.77 | 212.33 | 398.67 |
June | 410.67 | 0.48 | 0.48 | 01-JUN-04:00 | 1534.96 | 21.78 | 83.83 | 427.17 | 883.71 | 23.84 | 249.17 | 403.17 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 1426.11 | 21.55 | 72.67 | 438.50 | 840.06 | 23.64 | 253.50 | 416.00 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1154.45 | 18.80 | 0.00 | 391.00 | 699.58 | 20.99 | 142.50 | 359.50 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:49 | 928.26 | 18.12 | 0.00 | 324.83 | 582.88 | 20.38 | 22.00 | 280.67 |
October | 234.00 | 0.52 | 0.48 | 01-OCT-07:30 | 786.45 | 16.91 | 0.00 | 261.17 | 472.28 | 19.19 | 0.50 | 175.83 |
November | 171.33 | 0.54 | 0.48 | 01-NOV-11:00 | 580.67 | 15.22 | 0.00 | 177.67 | 340.84 | 17.57 | 0.00 | 76.33 |
December | 131.67 | 0.55 | 0.48 | 02-DEC-10:20 | 491.37 | 14.62 | 0.00 | 128.17 | 290.59 | 17.10 | 0.00 | 38.00 |
Annual Sum or Average | 3515.67 | 0.51 | 1072.25 | 18.66 | 202.67 | 3638.83 | 631.86 | 20.85 | 986.67 | 2902.17 | ||
Minimum of Months | 131.67 | 0.48 | 0.48 | 491.37 | 14.44 | 0.00 | 128.17 | 290.59 | 16.83 | 0.00 | 38.00 | |
Maximum of Months | 429.00 | 0.56 | 0.48 | 1534.96 | 21.78 | 83.83 | 438.50 | 883.71 | 23.84 | 253.50 | 416.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.54 | 0.48 | 01-JAN-09:50 | 1262.68 | 20.23 | 64.33 | 200.67 | 751.46 | 22.89 | 75.67 | 142.33 |
February | 217.00 | 0.52 | 0.48 | 01-FEB-11:39 | 2002.63 | 20.83 | 58.33 | 231.83 | 1108.11 | 22.73 | 77.67 | 180.50 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 1872.06 | 21.70 | 72.33 | 302.17 | 1018.25 | 22.69 | 70.50 | 248.67 |
April | 359.67 | 0.50 | 0.48 | 01-APR-07:49 | 3549.29 | 21.73 | 102.33 | 354.50 | 1612.59 | 21.82 | 80.50 | 326.17 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-07:10 | 3189.91 | 19.51 | 73.83 | 411.00 | 1788.78 | 21.15 | 46.83 | 381.33 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-05:49 | 3720.20 | 18.59 | 50.67 | 415.83 | 1669.25 | 19.56 | 1.50 | 378.50 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-05:49 | 3691.97 | 18.48 | 53.33 | 426.50 | 1697.60 | 19.51 | 4.33 | 393.50 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-06:19 | 3277.05 | 20.42 | 86.83 | 381.00 | 1843.44 | 21.75 | 74.83 | 348.50 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:00 | 3173.19 | 22.07 | 96.83 | 322.83 | 1757.65 | 23.37 | 101.00 | 294.83 |
October | 234.00 | 0.51 | 0.48 | 01-OCT-07:30 | 2511.70 | 22.43 | 79.83 | 268.00 | 1146.00 | 22.99 | 95.83 | 209.00 |
November | 171.33 | 0.52 | 0.48 | 01-NOV-11:39 | 1410.04 | 20.59 | 51.67 | 193.33 | 772.83 | 22.57 | 70.83 | 130.17 |
December | 131.67 | 0.53 | 0.48 | 02-DEC-09:39 | 1028.15 | 20.16 | 37.67 | 154.83 | 540.47 | 20.65 | 38.83 | 80.83 |
Annual Sum or Average | 3515.67 | 0.51 | 2883.93 | 20.38 | 828.00 | 3662.50 | 1462.82 | 21.58 | 738.33 | 3114.33 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1028.15 | 18.48 | 37.67 | 154.83 | 540.47 | 19.51 | 1.50 | 80.83 | |
Maximum of Months | 429.00 | 0.54 | 0.48 | 3720.20 | 22.43 | 102.33 | 426.50 | 1843.44 | 23.37 | 101.00 | 393.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.51 | 0.48 | 01-JAN-08:39 | 3801.28 | 33.96 | 177.17 | 220.00 | 3238.77 | 37.22 | 190.00 | 191.00 |
February | 217.00 | 0.50 | 0.48 | 01-FEB-11:39 | 5552.98 | 35.66 | 213.50 | 245.00 | 2608.75 | 30.41 | 141.83 | 219.33 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 4093.91 | 30.15 | 181.17 | 308.17 | 1130.51 | 18.51 | 7.50 | 262.67 |
April | 359.67 | 0.51 | 0.48 | 01-APR-06:00 | 2507.10 | 15.84 | 0.00 | 353.33 | 1404.27 | 19.36 | 38.83 | 326.33 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:49 | 1999.46 | 15.50 | 0.00 | 406.83 | 1115.76 | 18.98 | 14.00 | 370.00 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-05:49 | 1948.24 | 15.82 | 0.00 | 409.33 | 1076.70 | 19.27 | 7.17 | 367.33 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-05:49 | 1939.11 | 15.61 | 0.00 | 418.67 | 1098.52 | 19.10 | 15.67 | 378.33 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:10 | 2239.45 | 15.51 | 0.00 | 379.67 | 1282.10 | 19.03 | 36.83 | 344.17 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 3340.20 | 17.72 | 29.50 | 328.00 | 1546.61 | 19.46 | 44.83 | 300.00 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:49 | 7043.84 | 34.57 | 216.17 | 278.83 | 2023.73 | 21.94 | 45.50 | 236.00 |
November | 171.33 | 0.50 | 0.48 | 01-NOV-11:39 | 4427.27 | 35.78 | 166.83 | 213.50 | 3719.69 | 37.14 | 167.50 | 170.33 |
December | 131.67 | 0.50 | 0.48 | 02-DEC-08:50 | 3695.43 | 36.26 | 126.00 | 179.33 | 3137.99 | 38.18 | 128.67 | 129.50 |
Annual Sum or Average | 3515.67 | 0.50 | 3159.46 | 22.01 | 1110.33 | 3740.67 | 1673.03 | 22.61 | 838.33 | 3295.00 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1939.11 | 15.50 | 0.00 | 179.33 | 1076.70 | 18.51 | 7.17 | 129.50 | |
Maximum of Months | 429.00 | 0.51 | 0.48 | 7043.84 | 36.26 | 216.17 | 418.67 | 3719.69 | 38.18 | 190.00 | 378.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.53 | 0.48 | 01-JAN-08:39 | 1405.84 | 22.75 | 82.50 | 206.67 | 832.78 | 23.54 | 76.67 | 137.50 |
February | 217.00 | 0.50 | 0.48 | 01-FEB-11:39 | 1662.06 | 20.73 | 62.33 | 234.50 | 941.17 | 23.65 | 80.50 | 188.00 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 1923.17 | 21.35 | 71.33 | 301.17 | 850.45 | 22.38 | 60.17 | 245.00 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:10 | 3568.29 | 22.35 | 107.17 | 362.00 | 2034.44 | 23.64 | 96.33 | 333.00 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:40 | 3713.41 | 22.39 | 133.33 | 419.83 | 1644.19 | 22.54 | 72.33 | 376.67 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:49 | 3729.36 | 22.30 | 129.50 | 417.50 | 1685.96 | 23.32 | 81.00 | 384.50 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 3641.32 | 22.41 | 137.67 | 428.50 | 1629.61 | 22.79 | 78.17 | 396.67 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3470.99 | 21.51 | 109.83 | 386.33 | 1524.86 | 22.86 | 77.83 | 356.33 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 3318.08 | 23.15 | 109.33 | 335.00 | 1811.62 | 24.07 | 117.33 | 301.83 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:40 | 2591.40 | 22.58 | 82.33 | 268.67 | 1137.87 | 22.50 | 84.17 | 207.83 |
November | 171.33 | 0.51 | 0.48 | 01-NOV-11:39 | 1400.44 | 20.85 | 55.67 | 198.83 | 816.09 | 23.49 | 74.33 | 127.67 |
December | 131.67 | 0.51 | 0.48 | 02-DEC-08:50 | 1196.95 | 22.79 | 50.17 | 159.33 | 841.78 | 25.67 | 66.67 | 95.83 |
Annual Sum or Average | 3515.67 | 0.50 | 2979.90 | 22.16 | 1131.17 | 3718.33 | 1448.53 | 23.23 | 965.50 | 3150.83 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1196.95 | 20.73 | 50.17 | 159.33 | 816.09 | 22.38 | 60.17 | 95.83 | |
Maximum of Months | 429.00 | 0.53 | 0.48 | 3729.36 | 23.15 | 137.67 | 428.50 | 2034.44 | 25.67 | 117.33 | 396.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.56 | 0.48 | 01-JAN-09:00 | 502.83 | 10.71 | 0.00 | 181.83 | 293.90 | 14.31 | 0.00 | 61.17 |
February | 217.00 | 0.53 | 0.48 | 01-FEB-11:39 | 667.57 | 12.59 | 0.00 | 219.83 | 392.77 | 16.15 | 0.00 | 129.83 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 828.06 | 13.19 | 0.00 | 296.67 | 449.57 | 16.56 | 0.00 | 202.83 |
April | 359.67 | 0.50 | 0.48 | 01-APR-07:10 | 1094.60 | 15.60 | 0.00 | 358.67 | 656.34 | 19.06 | 8.00 | 324.00 |
May | 417.17 | 0.49 | 0.48 | 01-MAY-06:49 | 1299.86 | 17.55 | 38.00 | 423.17 | 750.13 | 20.85 | 71.83 | 394.83 |
June | 410.67 | 0.48 | 0.48 | 01-JUN-04:00 | 1480.79 | 18.76 | 56.83 | 426.00 | 852.65 | 21.97 | 105.17 | 401.00 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 1368.53 | 17.39 | 34.00 | 436.50 | 811.46 | 21.85 | 106.33 | 413.50 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1112.78 | 15.54 | 0.00 | 390.00 | 677.09 | 19.08 | 13.17 | 356.50 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:49 | 893.55 | 15.03 | 0.00 | 321.83 | 564.61 | 18.57 | 0.00 | 276.67 |
October | 234.00 | 0.52 | 0.48 | 01-OCT-07:30 | 756.51 | 13.49 | 0.00 | 258.33 | 455.94 | 17.01 | 0.00 | 168.33 |
November | 171.33 | 0.54 | 0.48 | 01-NOV-11:00 | 557.73 | 11.47 | 0.00 | 173.83 | 328.08 | 15.08 | 0.00 | 70.83 |
December | 131.67 | 0.56 | 0.48 | 02-DEC-10:30 | 471.24 | 10.68 | 0.00 | 122.83 | 279.41 | 14.48 | 0.00 | 33.33 |
Annual Sum or Average | 3515.67 | 0.51 | 1032.59 | 15.22 | 128.83 | 3609.50 | 610.29 | 18.81 | 304.50 | 2832.83 | ||
Minimum of Months | 131.67 | 0.48 | 0.48 | 471.24 | 10.68 | 0.00 | 122.83 | 279.41 | 14.31 | 0.00 | 33.33 | |
Maximum of Months | 429.00 | 0.56 | 0.48 | 1480.79 | 18.76 | 56.83 | 436.50 | 852.65 | 21.97 | 106.33 | 413.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.54 | 0.48 | 01-JAN-09:00 | 1222.50 | 19.84 | 64.17 | 198.83 | 721.68 | 22.79 | 75.50 | 136.50 |
February | 217.00 | 0.52 | 0.48 | 01-FEB-11:39 | 1939.02 | 20.42 | 58.33 | 230.00 | 1019.41 | 21.45 | 68.17 | 175.50 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 1818.31 | 21.31 | 72.33 | 301.33 | 977.54 | 22.47 | 66.83 | 244.67 |
April | 359.67 | 0.50 | 0.48 | 01-APR-07:49 | 3384.41 | 21.30 | 102.00 | 351.17 | 1544.29 | 21.67 | 74.33 | 322.83 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-07:10 | 3097.31 | 19.04 | 73.83 | 409.33 | 1717.93 | 21.00 | 46.83 | 379.67 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-05:49 | 3619.31 | 18.11 | 50.50 | 414.33 | 1592.39 | 19.40 | 0.00 | 376.33 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-05:49 | 3591.53 | 17.99 | 53.33 | 425.00 | 1617.93 | 19.35 | 3.67 | 390.00 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:19 | 3184.55 | 19.97 | 86.83 | 379.17 | 1758.38 | 21.60 | 71.33 | 345.83 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:00 | 3089.88 | 21.64 | 96.83 | 320.83 | 1668.98 | 22.98 | 95.83 | 290.33 |
October | 234.00 | 0.51 | 0.48 | 01-OCT-07:40 | 2443.09 | 22.05 | 79.83 | 266.67 | 1070.58 | 22.02 | 87.33 | 204.67 |
November | 171.33 | 0.53 | 0.48 | 01-NOV-11:50 | 1365.55 | 20.19 | 51.67 | 191.17 | 740.44 | 22.47 | 69.83 | 125.67 |
December | 131.67 | 0.54 | 0.48 | 02-DEC-09:50 | 995.53 | 19.75 | 37.67 | 150.83 | 517.15 | 20.55 | 38.50 | 77.83 |
Annual Sum or Average | 3515.67 | 0.51 | 2796.19 | 19.94 | 827.33 | 3638.67 | 1393.52 | 21.28 | 698.17 | 3069.83 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 995.53 | 17.99 | 37.67 | 150.83 | 517.15 | 19.35 | 0.00 | 77.83 | |
Maximum of Months | 429.00 | 0.54 | 0.48 | 3619.31 | 22.05 | 102.00 | 425.00 | 1758.38 | 22.98 | 95.83 | 390.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.51 | 0.48 | 01-JAN-08:39 | 3801.29 | 33.96 | 177.17 | 220.00 | 3238.70 | 37.22 | 190.00 | 191.00 |
February | 217.00 | 0.50 | 0.48 | 01-FEB-11:39 | 5552.95 | 35.66 | 213.50 | 245.00 | 2608.64 | 30.41 | 141.83 | 219.33 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 4093.79 | 30.15 | 181.17 | 308.17 | 1130.40 | 18.51 | 7.50 | 262.67 |
April | 359.67 | 0.51 | 0.48 | 01-APR-06:00 | 2506.95 | 15.85 | 0.00 | 353.33 | 1404.16 | 19.36 | 39.33 | 326.33 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:49 | 1999.34 | 15.50 | 0.00 | 406.83 | 1115.67 | 18.98 | 14.17 | 370.00 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-05:49 | 1948.12 | 15.83 | 0.00 | 409.33 | 1076.62 | 19.27 | 7.17 | 367.17 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-05:49 | 1939.00 | 15.61 | 0.00 | 418.67 | 1098.44 | 19.10 | 15.83 | 378.33 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:10 | 2239.32 | 15.51 | 0.00 | 379.67 | 1282.01 | 19.03 | 36.83 | 344.17 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 3340.09 | 17.72 | 29.50 | 328.00 | 1546.50 | 19.46 | 44.83 | 300.00 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:49 | 7043.78 | 34.57 | 216.17 | 278.83 | 2023.60 | 21.94 | 45.50 | 236.00 |
November | 171.33 | 0.50 | 0.48 | 01-NOV-11:39 | 4427.28 | 35.78 | 166.83 | 213.50 | 3719.60 | 37.14 | 167.50 | 170.33 |
December | 131.67 | 0.50 | 0.48 | 02-DEC-08:50 | 3695.45 | 36.26 | 126.00 | 179.33 | 3137.92 | 38.18 | 128.67 | 129.50 |
Annual Sum or Average | 3515.67 | 0.50 | 3159.37 | 22.01 | 1110.33 | 3740.67 | 1672.93 | 22.61 | 839.17 | 3294.83 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1939.00 | 15.50 | 0.00 | 179.33 | 1076.62 | 18.51 | 7.17 | 129.50 | |
Maximum of Months | 429.00 | 0.51 | 0.48 | 7043.78 | 36.26 | 216.17 | 418.67 | 3719.60 | 38.18 | 190.00 | 378.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.53 | 0.48 | 01-JAN-08:39 | 1405.82 | 22.75 | 82.50 | 206.67 | 832.74 | 23.54 | 76.67 | 137.50 |
February | 217.00 | 0.50 | 0.48 | 01-FEB-11:39 | 1662.04 | 20.73 | 62.33 | 234.50 | 941.12 | 23.66 | 80.50 | 188.00 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 1923.10 | 21.35 | 71.33 | 301.17 | 850.38 | 22.38 | 60.17 | 245.00 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:10 | 3568.24 | 22.35 | 107.17 | 362.00 | 2034.36 | 23.64 | 96.33 | 333.00 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:40 | 3713.34 | 22.40 | 133.33 | 419.83 | 1644.11 | 22.54 | 72.33 | 376.67 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:49 | 3729.28 | 22.30 | 129.50 | 417.50 | 1685.87 | 23.32 | 81.00 | 384.50 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 3641.25 | 22.41 | 137.67 | 428.33 | 1629.52 | 22.79 | 78.17 | 396.67 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3470.95 | 21.51 | 109.83 | 386.33 | 1524.78 | 22.86 | 77.83 | 356.33 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 3318.06 | 23.16 | 109.33 | 335.00 | 1811.55 | 24.07 | 117.33 | 301.83 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:40 | 2591.37 | 22.58 | 82.33 | 268.67 | 1137.81 | 22.50 | 84.17 | 207.83 |
November | 171.33 | 0.51 | 0.48 | 01-NOV-11:39 | 1400.41 | 20.85 | 55.67 | 198.83 | 816.05 | 23.49 | 74.33 | 127.67 |
December | 131.67 | 0.51 | 0.48 | 02-DEC-08:50 | 1196.93 | 22.79 | 50.17 | 159.33 | 841.74 | 25.67 | 66.67 | 95.83 |
Annual Sum or Average | 3515.67 | 0.50 | 2979.85 | 22.16 | 1131.17 | 3718.17 | 1448.46 | 23.23 | 965.50 | 3150.83 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1196.93 | 20.73 | 50.17 | 159.33 | 816.05 | 22.38 | 60.17 | 95.83 | |
Maximum of Months | 429.00 | 0.53 | 0.48 | 3729.28 | 23.16 | 137.67 | 428.33 | 2034.36 | 25.67 | 117.33 | 396.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.56 | 0.48 | 01-JAN-09:00 | 502.82 | 10.71 | 0.00 | 181.83 | 293.88 | 14.31 | 0.00 | 61.17 |
February | 217.00 | 0.53 | 0.48 | 01-FEB-11:39 | 667.55 | 12.59 | 0.00 | 219.83 | 392.74 | 16.15 | 0.00 | 129.67 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 828.01 | 13.19 | 0.00 | 296.67 | 449.53 | 16.56 | 0.00 | 202.67 |
April | 359.67 | 0.50 | 0.48 | 01-APR-07:10 | 1094.57 | 15.60 | 0.00 | 358.67 | 656.29 | 19.06 | 8.00 | 324.00 |
May | 417.17 | 0.49 | 0.48 | 01-MAY-06:49 | 1299.82 | 17.55 | 38.00 | 423.17 | 750.08 | 20.85 | 71.83 | 394.83 |
June | 410.67 | 0.48 | 0.48 | 01-JUN-04:00 | 1480.73 | 18.76 | 56.83 | 426.00 | 852.59 | 21.97 | 105.17 | 401.00 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 1368.49 | 17.39 | 34.00 | 436.50 | 811.41 | 21.85 | 106.50 | 413.50 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1112.76 | 15.54 | 0.00 | 390.00 | 677.04 | 19.09 | 13.17 | 356.50 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:49 | 893.54 | 15.03 | 0.00 | 321.83 | 564.57 | 18.57 | 0.00 | 276.67 |
October | 234.00 | 0.52 | 0.48 | 01-OCT-07:30 | 756.49 | 13.49 | 0.00 | 258.33 | 455.91 | 17.01 | 0.00 | 168.33 |
November | 171.33 | 0.54 | 0.48 | 01-NOV-11:00 | 557.71 | 11.47 | 0.00 | 173.83 | 328.06 | 15.08 | 0.00 | 70.83 |
December | 131.67 | 0.56 | 0.48 | 02-DEC-10:30 | 471.23 | 10.68 | 0.00 | 122.67 | 279.39 | 14.48 | 0.00 | 33.33 |
Annual Sum or Average | 3515.67 | 0.51 | 1032.56 | 15.23 | 128.83 | 3609.33 | 610.25 | 18.81 | 304.67 | 2832.50 | ||
Minimum of Months | 131.67 | 0.48 | 0.48 | 471.23 | 10.68 | 0.00 | 122.67 | 279.39 | 14.31 | 0.00 | 33.33 | |
Maximum of Months | 429.00 | 0.56 | 0.48 | 1480.73 | 18.76 | 56.83 | 436.50 | 852.59 | 21.97 | 106.50 | 413.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.54 | 0.48 | 01-JAN-09:00 | 1222.48 | 19.85 | 64.17 | 198.83 | 721.64 | 22.79 | 75.50 | 136.50 |
February | 217.00 | 0.52 | 0.48 | 01-FEB-11:39 | 1938.99 | 20.42 | 58.33 | 230.00 | 1019.35 | 21.45 | 68.17 | 175.50 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 1818.24 | 21.31 | 72.33 | 301.33 | 977.47 | 22.47 | 66.83 | 244.67 |
April | 359.67 | 0.50 | 0.48 | 01-APR-07:49 | 3384.35 | 21.31 | 102.00 | 351.17 | 1544.20 | 21.68 | 74.33 | 322.83 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-07:10 | 3097.24 | 19.04 | 73.83 | 409.33 | 1717.84 | 21.00 | 46.83 | 379.67 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-05:49 | 3619.23 | 18.12 | 50.50 | 414.33 | 1592.29 | 19.40 | 0.00 | 376.33 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-05:49 | 3591.46 | 18.00 | 53.33 | 425.00 | 1617.84 | 19.35 | 3.67 | 390.00 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:19 | 3184.49 | 19.97 | 86.83 | 379.17 | 1758.30 | 21.60 | 71.33 | 345.83 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:00 | 3089.85 | 21.64 | 96.83 | 320.83 | 1668.91 | 22.98 | 95.83 | 290.33 |
October | 234.00 | 0.51 | 0.48 | 01-OCT-07:40 | 2443.06 | 22.05 | 79.83 | 266.67 | 1070.52 | 22.02 | 87.33 | 204.50 |
November | 171.33 | 0.53 | 0.48 | 01-NOV-11:50 | 1365.52 | 20.20 | 51.67 | 191.17 | 740.39 | 22.47 | 69.83 | 125.67 |
December | 131.67 | 0.54 | 0.48 | 02-DEC-09:50 | 995.51 | 19.76 | 37.67 | 150.83 | 517.11 | 20.56 | 38.50 | 77.83 |
Annual Sum or Average | 3515.67 | 0.51 | 2796.14 | 19.94 | 827.33 | 3638.67 | 1393.44 | 21.28 | 698.17 | 3069.67 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 995.51 | 18.00 | 37.67 | 150.83 | 517.11 | 19.35 | 0.00 | 77.83 | |
Maximum of Months | 429.00 | 0.54 | 0.48 | 3619.23 | 22.05 | 102.00 | 425.00 | 1758.30 | 22.98 | 95.83 | 390.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 85629962.43 | 21031.59 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85629962.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 85629962.43 | 21031.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.402454E+10 | 10280.27 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.290397E+10 | 10280.27 | 01-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.356667E+10 | 10280.27 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108338E+10 | 10280.27 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108764E+10 | 10280.27 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.400472E+09 | 10280.27 | 01-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144565E+09 | 10280.27 | 03-JUL-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.126066E+09 | 10280.27 | 24-AUG-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.366760E+09 | 10280.27 | 05-SEP-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142010E+10 | 10280.27 | 03-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.271986E+10 | 10280.27 | 01-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.420000E+10 | 10280.27 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.126066E+09 | 10280.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.420000E+10 | 10280.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102869E+10 | 6824.23 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.519846E+09 | 6824.23 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.382987E+09 | 6824.23 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1380564.42 | 5426.81 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 28421877.01 | 6555.43 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.290150E+09 | 6824.23 | 03-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101978E+10 | 6824.23 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102869E+10 | 6824.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.193903E+10 | 6778.44 | 10-JAN-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107799E+10 | 6603.33 | 17-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.728830E+09 | 6531.70 | 18-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32962746.05 | 6501.66 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 70472484.49 | 6508.78 | 24-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.592957E+09 | 6521.85 | 25-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177100E+10 | 6511.96 | 12-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.621324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.193903E+10 | 6778.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107859E+10 | 6794.46 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.482957E+09 | 6794.46 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384853E+09 | 6794.46 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11206088.99 | 5944.22 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 34604833.18 | 6794.46 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.319163E+09 | 6794.46 | 03-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114609E+10 | 6794.46 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.345746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114609E+10 | 6794.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.650320E+09 | 21082.86 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 43269404.21 | 21082.86 | 13-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20163912.75 | 21082.86 | 06-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 48424532.39 | 21082.86 | 20-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.496759E+09 | 21082.86 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.650320E+09 | 21082.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.926862E+09 | 10225.59 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.418630E+09 | 10225.59 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.303893E+09 | 10225.59 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6605665.49 | 5730.65 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 51773568.76 | 10225.59 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.379393E+09 | 10225.59 | 03-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129876E+10 | 10225.59 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.338591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.129876E+10 | 10225.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.810623E+09 | 6756.19 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.398755E+09 | 6756.19 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.232144E+09 | 6756.19 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 939814.26 | 3777.30 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 44696772.17 | 6756.19 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.339464E+09 | 6756.19 | 03-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.979081E+09 | 6756.19 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.979081E+09 | 6756.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.153860E+10 | 7403.35 | 30-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.793271E+09 | 7364.06 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.430813E+09 | 7354.26 | 27-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10270500.62 | 7292.01 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 82932699.72 | 7325.57 | 17-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.647222E+09 | 7370.86 | 27-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177761E+10 | 7396.01 | 12-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.528072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.177761E+10 | 7403.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.885191E+09 | 6726.20 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.406215E+09 | 6726.20 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.249790E+09 | 6726.20 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5798220.36 | 4507.28 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29424.17 | 196.16 | 05-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 52948139.22 | 6726.20 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.382906E+09 | 6726.20 | 03-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114458E+10 | 6726.20 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.312746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114458E+10 | 6726.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.264417E+10 | 30272.19 | 30-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125713E+10 | 30309.80 | 02-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.758550E+09 | 30294.06 | 27-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11319242.90 | 13869.86 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147047E+09 | 29995.90 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114559E+10 | 30190.60 | 20-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.334765E+10 | 30289.39 | 12-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.931146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.334765E+10 | 30309.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.197049E+10 | 13390.98 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123501E+10 | 13390.98 | 01-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103129E+10 | 13390.98 | 01-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108783E+09 | 12112.35 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36251688.10 | 11151.77 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 283115.52 | 943.72 | 08-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3703771.46 | 2278.73 | 20-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.366412E+09 | 13390.98 | 23-OCT-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118933E+10 | 13390.98 | 03-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.264530E+10 | 13390.98 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.858685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.264530E+10 | 13390.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.165690E+10 | 8759.00 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102405E+10 | 8759.00 | 01-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.731905E+09 | 8759.00 | 01-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31234974.00 | 7268.22 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5539351.50 | 3533.18 | 17-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1055183.79 | 2217.44 | 21-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.290767E+09 | 8759.00 | 23-OCT-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.986991E+09 | 8759.00 | 03-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203080E+10 | 8759.00 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.675924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.203080E+10 | 8759.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.293368E+10 | 8569.52 | 10-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.190177E+10 | 8504.37 | 17-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131810E+10 | 8277.88 | 20-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137479E+09 | 8220.39 | 06-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19818369.53 | 8214.64 | 05-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10087905.84 | 4884.01 | 21-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.544940E+09 | 8259.88 | 30-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.175108E+10 | 8275.75 | 24-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.340297E+10 | 8278.97 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.340297E+10 | 8569.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.174637E+10 | 8729.07 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106823E+10 | 8729.07 | 01-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.786439E+09 | 8729.07 | 01-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 81252899.25 | 7865.46 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23606264.71 | 7170.52 | 05-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 45270.44 | 150.90 | 08-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4914397.66 | 2333.54 | 21-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.330944E+09 | 8729.07 | 23-OCT-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106015E+10 | 8729.07 | 03-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.218678E+10 | 8729.07 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.728873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.218678E+10 | 8729.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.777116E+10 | 15559.49 | 10-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.586847E+10 | 15559.49 | 17-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.485599E+10 | 12334.18 | 08-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.826578E+09 | 9382.45 | 08-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.352030E+09 | 6770.65 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12947321.30 | 2730.97 | 07-JUN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 255609.30 | 426.02 | 03-JUL-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 35447.12 | 295.39 | 30-AUG-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 28311857.95 | 3960.25 | 21-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.949879E+09 | 7006.37 | 07-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373328E+10 | 13594.79 | 29-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.754104E+10 | 15098.98 | 27-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 35447.12 | 295.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.777116E+10 | 15559.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.828703E+10 | 16734.53 | 10-JAN-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.657889E+10 | 17192.29 | 17-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.591913E+10 | 13260.29 | 08-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141146E+10 | 9642.40 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.776437E+09 | 6996.94 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 49696789.47 | 3296.47 | 07-JUN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3391840.67 | 1438.93 | 03-JUL-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2806390.83 | 1777.40 | 24-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127103E+09 | 5138.62 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169022E+10 | 7619.44 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.484757E+10 | 13193.90 | 29-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.808075E+10 | 13625.78 | 27-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.377745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2806390.83 | 1438.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.828703E+10 | 17192.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.883962E+10 | 16984.69 | 10-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.700351E+10 | 16984.69 | 17-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.633101E+10 | 13116.45 | 27-MAR-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173897E+10 | 13240.98 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112681E+10 | 9417.44 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 97985286.69 | 4164.19 | 08-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10627156.61 | 2161.60 | 05-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9006066.38 | 2734.25 | 24-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.226125E+09 | 6333.27 | 21-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.210629E+10 | 9855.79 | 06-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.533763E+10 | 15633.37 | 29-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.865298E+10 | 15829.61 | 27-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.414806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9006066.38 | 2161.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.883962E+10 | 16984.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 7367726.14 | 5639614.69 | 1177.08 | 27-JAN-13:00 | 903.39 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 24050520.97 | 20324766.38 | 3460.69 | 31-MAR-16:07 | 3377.25 | 0.00 |
April | 0.00 | 0.00 | 0.301857E+10 | 0.288309E+10 | 35189.40 | 30-APR-16:11 | 35189.40 | 0.00 |
May | 0.00 | 0.00 | 0.282935E+10 | 0.240690E+10 | 41747.13 | 22-MAY-15:10 | 41747.13 | 0.00 |
June | 0.00 | 0.00 | 0.884812E+10 | 0.731675E+10 | 60043.47 | 13-JUN-16:00 | 54780.16 | 0.00 |
July | 0.00 | 0.00 | 0.148365E+11 | 0.120233E+11 | 55706.60 | 21-JUL-16:00 | 55706.60 | 0.00 |
August | 0.00 | 0.00 | 0.192350E+11 | 0.152032E+11 | 55548.97 | 14-AUG-15:50 | 54448.60 | 0.00 |
September | 0.00 | 0.00 | 0.973763E+10 | 0.800780E+10 | 47263.42 | 13-SEP-15:20 | 42870.56 | 0.00 |
October | 0.00 | 0.00 | 0.365363E+10 | 0.352616E+10 | 29041.55 | 06-OCT-15:30 | 29041.55 | 0.00 |
November | 0.00 | 0.00 | 51244886.14 | 45102394.91 | 3206.95 | 03-NOV-15:20 | 3013.86 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.622414E+11 | 0.514383E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.192350E+11 | 0.152032E+11 | 60043.47 | 55706.60 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.162530E+10 | 0.156242E+10 | 41222.67 | 30-APR-14:52 | 41222.67 | 0.00 |
May | 0.00 | 0.00 | 0.251196E+10 | 0.215682E+10 | 41151.49 | 22-MAY-15:00 | 41085.29 | 0.00 |
June | 0.00 | 0.00 | 0.827283E+10 | 0.685814E+10 | 57069.47 | 13-JUN-14:05 | 50448.12 | 0.00 |
July | 0.00 | 0.00 | 0.136121E+11 | 0.110714E+11 | 51549.32 | 21-JUL-14:05 | 50475.99 | 0.00 |
August | 0.00 | 0.00 | 0.171013E+11 | 0.135473E+11 | 51977.51 | 14-AUG-15:30 | 50149.47 | 0.00 |
September | 0.00 | 0.00 | 0.871265E+10 | 0.716601E+10 | 45087.35 | 13-SEP-14:05 | 40488.47 | 0.00 |
October | 0.00 | 0.00 | 0.293691E+09 | 0.281754E+09 | 9520.65 | 07-OCT-15:00 | 9520.65 | 0.00 |
November | 0.00 | 0.00 | 2383287.08 | 1577474.37 | 1790.96 | 24-NOV-12:00 | 1207.23 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.521323E+11 | 0.426455E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.171013E+11 | 0.135473E+11 | 57069.47 | 50475.99 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.159044E+10 | 0.151331E+10 | 37259.78 | 30-APR-15:42 | 37259.78 | 0.00 |
May | 0.00 | 0.00 | 0.257969E+10 | 0.219697E+10 | 44609.36 | 22-MAY-15:00 | 44609.36 | 0.00 |
June | 0.00 | 0.00 | 0.865126E+10 | 0.715520E+10 | 65986.57 | 13-JUN-14:40 | 58099.15 | 0.00 |
July | 0.00 | 0.00 | 0.140654E+11 | 0.114365E+11 | 59381.03 | 21-JUL-15:40 | 59381.03 | 0.00 |
August | 0.00 | 0.00 | 0.169694E+11 | 0.133235E+11 | 56426.92 | 14-AUG-15:40 | 56426.92 | 0.00 |
September | 0.00 | 0.00 | 0.834007E+10 | 0.679422E+10 | 43753.34 | 13-SEP-14:50 | 39915.04 | 0.00 |
October | 0.00 | 0.00 | 0.261818E+09 | 0.246261E+09 | 9212.56 | 07-OCT-15:00 | 9212.56 | 0.00 |
November | 0.00 | 0.00 | 2694271.40 | 1758271.05 | 1923.28 | 24-NOV-12:00 | 1276.41 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.524607E+11 | 0.426677E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.169694E+11 | 0.133235E+11 | 65986.57 | 59381.03 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1869.16 | 6506.60 | 23-JAN-12:07 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1890.68 | 6534.17 | 22-FEB-12:07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2002.12 | 6501.61 | 03-MAR-12:13 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1836.86 | 6431.16 | 03-APR-11:09 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1856.31 | 6290.23 | 01-MAY-11:06 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1855.49 | 6110.22 | 01-JUN-11:08 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1668.53 | 5946.40 | 05-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1821.08 | 5853.42 | 22-AUG-11:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1712.79 | 5945.45 | 28-SEP-11:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1745.50 | 6118.97 | 31-OCT-11:07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1818.23 | 6279.57 | 28-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1788.24 | 6424.49 | 29-DEC-12:07 |
Annual Sum or Average | 0.00 | 1821.70 | ||||
Minimum of Months | 0.00 | 0.00 | 1668.53 | 5853.42 | ||
Maximum of Months | 0.00 | 0.00 | 2002.12 | 6534.17 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.117106E+10 | 0.29 | 2574.31 | 02-JAN-06:01 | 0.77 |
February | 0.110513E+10 | 0.29 | 1432.58 | 10-FEB-08:05 | 0.58 |
March | 0.134923E+10 | 0.31 | 1940.09 | 31-MAR-07:03 | 0.67 |
April | 0.199515E+10 | 0.33 | 5271.99 | 28-APR-15:10 | 1.17 |
May | 0.241020E+10 | 0.35 | 5476.27 | 23-MAY-06:02 | 1.20 |
June | 0.308532E+10 | 0.41 | 7033.23 | 13-JUN-16:00 | 1.40 |
July | 0.347174E+10 | 0.42 | 6984.29 | 24-JUL-06:02 | 1.39 |
August | 0.379772E+10 | 0.45 | 7173.97 | 14-AUG-15:30 | 1.42 |
September | 0.303852E+10 | 0.40 | 6792.32 | 12-SEP-15:10 | 1.37 |
October | 0.171856E+10 | 0.31 | 3943.22 | 03-OCT-15:10 | 0.99 |
November | 0.123177E+10 | 0.29 | 2162.03 | 03-NOV-07:03 | 0.71 |
December | 0.112703E+10 | 0.28 | 1379.75 | 04-DEC-06:11 | 0.58 |
Annual Sum or Average | 0.255014E+11 | 0.34 | |||
Minimum of Months | 0.110513E+10 | 0.28 | 1379.75 | 0.58 | |
Maximum of Months | 0.379772E+10 | 0.45 | 7173.97 | 1.42 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.984053E+09 | 0.28 | 2588.33 | 02-JAN-06:01 | 0.83 |
February | 0.913694E+09 | 0.28 | 2588.33 | 13-FEB-07:01 | 0.83 |
March | 0.103577E+10 | 0.30 | 2337.30 | 06-MAR-07:02 | 0.79 |
April | 0.174131E+10 | 0.33 | 6112.51 | 28-APR-14:05 | 1.39 |
May | 0.203593E+10 | 0.35 | 5859.04 | 23-MAY-14:05 | 1.35 |
June | 0.270690E+10 | 0.41 | 7202.58 | 13-JUN-15:30 | 1.54 |
July | 0.306219E+10 | 0.42 | 7177.57 | 24-JUL-14:05 | 1.53 |
August | 0.330230E+10 | 0.44 | 7076.73 | 14-AUG-15:20 | 1.52 |
September | 0.249556E+10 | 0.39 | 6734.67 | 12-SEP-15:00 | 1.47 |
October | 0.126350E+10 | 0.29 | 3657.21 | 03-OCT-14:05 | 1.02 |
November | 0.945980E+09 | 0.28 | 2588.33 | 20-NOV-07:01 | 0.83 |
December | 0.954625E+09 | 0.27 | 2588.33 | 04-DEC-07:02 | 0.83 |
Annual Sum or Average | 0.214418E+11 | 0.34 | |||
Minimum of Months | 0.913694E+09 | 0.27 | 2337.30 | 0.79 | |
Maximum of Months | 0.330230E+10 | 0.44 | 7202.58 | 1.54 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.113424E+10 | 0.31 | 2453.33 | 02-JAN-05:01 | 0.76 |
February | 0.992952E+09 | 0.30 | 2453.33 | 02-FEB-07:01 | 0.76 |
March | 0.114048E+10 | 0.32 | 2453.33 | 06-MAR-06:11 | 0.76 |
April | 0.161117E+10 | 0.32 | 5833.64 | 28-APR-15:20 | 1.26 |
May | 0.187594E+10 | 0.34 | 5837.42 | 22-MAY-15:20 | 1.26 |
June | 0.249086E+10 | 0.38 | 7513.15 | 13-JUN-15:30 | 1.47 |
July | 0.281961E+10 | 0.39 | 7035.65 | 21-JUL-15:40 | 1.41 |
August | 0.292069E+10 | 0.41 | 6952.42 | 14-AUG-15:30 | 1.40 |
September | 0.213336E+10 | 0.36 | 6072.05 | 12-SEP-15:00 | 1.29 |
October | 0.121235E+10 | 0.30 | 2602.85 | 03-OCT-14:40 | 0.79 |
November | 0.103946E+10 | 0.30 | 2453.33 | 13-NOV-06:11 | 0.76 |
December | 0.109328E+10 | 0.30 | 2453.33 | 04-DEC-06:11 | 0.76 |
Annual Sum or Average | 0.204644E+11 | 0.34 | |||
Minimum of Months | 0.992952E+09 | 0.30 | 2453.33 | 0.76 | |
Maximum of Months | 0.292069E+10 | 0.41 | 7513.15 | 1.47 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:05 | 2.06 | 2.06 | 57.53 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:05 | 2.06 | 2.06 | 55.25 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 56.34 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 55.69 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 56.39 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.00 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 56.70 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:05 | 2.06 | 2.06 | 55.57 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 56.61 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.33 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 55.62 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:05 | 2.06 | 2.06 | 56.59 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 55.25 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.53 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56.93 | 56.93 | 1869.16 | 6506.60 | 23-JAN-12:07 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.56 | 56.56 | 1890.68 | 6534.17 | 22-FEB-12:07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.99 | 56.99 | 2002.12 | 6501.61 | 03-MAR-12:13 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.36 | 56.36 | 1836.86 | 6431.16 | 03-APR-11:09 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.88 | 57.88 | 1856.31 | 6290.23 | 01-MAY-11:06 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.35 | 57.35 | 1855.49 | 6110.22 | 01-JUN-11:08 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.25 | 57.25 | 1668.53 | 5946.40 | 05-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.25 | 56.25 | 1821.08 | 5853.42 | 22-AUG-11:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.07 | 57.07 | 1712.79 | 5945.45 | 28-SEP-11:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.10 | 56.10 | 1745.50 | 6118.97 | 31-OCT-11:07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.52 | 56.52 | 1818.23 | 6279.57 | 28-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.23 | 57.23 | 1788.24 | 6424.49 | 29-DEC-12:07 |
Annual Sum or Average | 0.00 | 1821.70 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.10 | 56.10 | 1668.53 | 5853.42 | ||
Maximum of Months | 0.00 | 0.00 | 57.88 | 57.88 | 2002.12 | 6534.17 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.932970E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.608989E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.641959E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.393396E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.420828E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.563803E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.729534E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.867303E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.580103E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.417825E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.516873E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.926391E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.759997E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.393396E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.932970E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.579565E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.297383E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.227257E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.214618E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.260140E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.453382E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.612686E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.713824E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.444355E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.157058E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.274402E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.665141E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.489981E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.157058E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.713824E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.120858E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.747914E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.576676E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.239477E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.260149E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.459723E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.632034E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.714347E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.422296E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.296635E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.717339E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.147068E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.774585E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.239477E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.147068E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.117106E+10 | 7367726.14 | 0.159276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110513E+10 | 0.00 | 0.108532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134923E+10 | 24050520.97 | 0.991932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.199515E+10 | 0.301857E+10 | 0.195551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.241020E+10 | 0.282935E+10 | 0.143967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.308532E+10 | 0.884812E+10 | 0.413419E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.347174E+10 | 0.148365E+11 | 0.144821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.379772E+10 | 0.192350E+11 | 0.126102E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.303852E+10 | 0.973763E+10 | 0.395072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171856E+10 | 0.365363E+10 | 0.250348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123177E+10 | 51244886.14 | 0.765541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112703E+10 | 0.00 | 0.156779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.255014E+11 | 0.622414E+11 | 0.670116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110513E+10 | 0.00 | 0.126102E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.379772E+10 | 0.192350E+11 | 0.159276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.984053E+09 | 0.00 | 0.130986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.913694E+09 | 0.00 | 0.863903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103577E+10 | 0.00 | 0.715594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174131E+10 | 0.162530E+10 | 0.143507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.203593E+10 | 0.251196E+10 | 0.776466E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.270690E+10 | 0.827283E+10 | 49696789.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.306219E+10 | 0.136121E+11 | 3391840.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.330230E+10 | 0.171013E+11 | 2806390.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.249556E+10 | 0.871265E+10 | 0.127103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126350E+10 | 0.293691E+09 | 0.192257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.945980E+09 | 2383287.08 | 0.664498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.954625E+09 | 0.00 | 0.137775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214418E+11 | 0.521323E+11 | 0.536332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.913694E+09 | 0.00 | 2806390.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.330230E+10 | 0.171013E+11 | 0.137775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.113424E+10 | 0.00 | 0.197912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.992952E+09 | 0.00 | 0.134897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114048E+10 | 0.00 | 0.109573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161117E+10 | 0.159044E+10 | 0.210904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.187594E+10 | 0.257969E+10 | 0.121202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.249086E+10 | 0.865126E+10 | 98313672.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.281961E+10 | 0.140654E+11 | 10627156.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.292069E+10 | 0.169694E+11 | 9006066.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.213336E+10 | 0.834007E+10 | 0.245886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121235E+10 | 0.261818E+09 | 0.378640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103946E+10 | 2694271.40 | 0.114708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109328E+10 | 0.00 | 0.222665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204644E+11 | 0.524607E+11 | 0.854468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.992952E+09 | 0.00 | 9006066.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.292069E+10 | 0.169694E+11 | 0.222665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.117106E+10 | 0.00 | 0.00 | 0.00 | 2160111.88 | 0.815648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134923E+10 | 0.00 | 0.00 | 0.00 | 7017704.83 | 0.506334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.199515E+10 | 0.00 | 0.00 | 0.00 | 0.809882E+09 | 0.112893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.241020E+10 | 0.00 | 0.00 | 0.00 | 0.710442E+09 | 0.108764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.308532E+10 | 0.00 | 0.00 | 0.00 | 0.215224E+10 | 0.400472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.347174E+10 | 0.00 | 0.00 | 0.00 | 0.367904E+10 | 0.144565E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.379772E+10 | 0.00 | 0.00 | 0.00 | 0.474924E+10 | 0.126066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.303852E+10 | 0.00 | 0.00 | 0.00 | 0.239575E+10 | 0.366760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171856E+10 | 0.00 | 0.00 | 0.00 | 0.906093E+09 | 0.155360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123177E+10 | 0.00 | 0.00 | 0.00 | 14834918.91 | 0.392213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.813687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.255014E+11 | 0.00 | 0.00 | 0.00 | 0.154267E+11 | 0.350716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.379772E+10 | 0.00 | 0.00 | 0.00 | 0.474924E+10 | 0.815648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.984053E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.913694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174131E+10 | 0.00 | 0.00 | 0.00 | 0.381260E+09 | 23614200.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.203593E+10 | 0.00 | 0.00 | 0.00 | 0.565446E+09 | 29424.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.270690E+10 | 0.00 | 0.00 | 0.00 | 0.182692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.306219E+10 | 0.00 | 0.00 | 0.00 | 0.306467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.330230E+10 | 0.00 | 0.00 | 0.00 | 0.383594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.249556E+10 | 0.00 | 0.00 | 0.00 | 0.194799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126350E+10 | 0.00 | 0.00 | 0.00 | 74729492.50 | 0.232351E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.945980E+09 | 0.00 | 0.00 | 0.00 | 632955.82 | 0.179741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.954625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.569679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214418E+11 | 0.00 | 0.00 | 0.00 | 0.116976E+11 | 0.158587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.913694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.330230E+10 | 0.00 | 0.00 | 0.00 | 0.383594E+10 | 0.569679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.113424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.992952E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161117E+10 | 0.00 | 0.00 | 0.00 | 0.413533E+09 | 0.370069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.187594E+10 | 0.00 | 0.00 | 0.00 | 0.640325E+09 | 85215673.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.249086E+10 | 0.00 | 0.00 | 0.00 | 0.210604E+10 | 328385.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.281961E+10 | 0.00 | 0.00 | 0.00 | 0.350073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.292069E+10 | 0.00 | 0.00 | 0.00 | 0.422278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.213336E+10 | 0.00 | 0.00 | 0.00 | 0.206984E+10 | 19761258.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121235E+10 | 0.00 | 0.00 | 0.00 | 73889105.41 | 0.168011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103946E+10 | 0.00 | 0.00 | 0.00 | 786104.90 | 0.613314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204644E+11 | 0.00 | 0.00 | 0.00 | 0.130279E+11 | 0.439662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.992952E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.292069E+10 | 0.00 | 0.00 | 0.00 | 0.422278E+10 | 0.136135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.700769E+10 | 0.00 | 0.00 | 12624063.72 | 0.00 | 51207849.41 | 0.832966E+10 | 0.00 | 0.33 |
February | 0.533560E+10 | 0.00 | 0.00 | 16302954.88 | 0.00 | 0.00 | 0.943089E+10 | 0.00 | 0.35 |
March | 0.486595E+10 | 0.00 | 0.00 | 19152057.46 | 0.00 | 0.00 | 0.123884E+11 | 0.00 | 0.40 |
April | 0.107155E+10 | 349036.69 | 0.00 | 38666866.81 | 0.00 | 0.00 | 0.186813E+11 | 0.00 | 0.61 |
May | 0.991111E+09 | 0.00 | 0.00 | 44222655.60 | 0.00 | 0.00 | 0.223878E+11 | 0.00 | 0.74 |
June | 0.937623E+09 | 15448922.65 | 0.00 | 47455024.12 | 29668542.70 | 0.00 | 0.224543E+11 | 0.00 | 1.01 |
July | 0.916586E+09 | 16469431.56 | 0.00 | 44939440.37 | 3071122.23 | 0.00 | 0.191445E+11 | 0.00 | 1.04 |
August | 0.103596E+10 | 0.00 | 0.00 | 48895605.02 | 0.00 | 0.00 | 0.186933E+11 | 0.00 | 1.18 |
September | 0.105736E+10 | 0.00 | 0.00 | 43661831.27 | 503253.13 | 0.00 | 0.195978E+11 | 0.00 | 0.99 |
October | 0.137026E+10 | 0.00 | 0.00 | 30999359.95 | 0.00 | 0.00 | 0.154489E+11 | 0.00 | 0.48 |
November | 0.340618E+10 | 0.00 | 0.00 | 18956762.25 | 0.00 | 0.00 | 0.119786E+11 | 0.00 | 0.38 |
December | 0.629831E+10 | 0.00 | 0.00 | 12241949.64 | 0.00 | 0.00 | 0.822420E+10 | 0.00 | 0.32 |
Annual Sum or Average | 0.342942E+11 | 32267390.89 | 0.00 | 0.378119E+09 | 33242918.06 | 51207849.41 | 0.186760E+12 | 0.00 | 0.65 |
Minimum of Months | 0.916586E+09 | 0.00 | 0.00 | 12241949.64 | 0.00 | 0.00 | 0.822420E+10 | 0.00 | 0.32 |
Maximum of Months | 0.700769E+10 | 16469431.56 | 0.00 | 48895605.02 | 29668542.70 | 51207849.41 | 0.224543E+11 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124332E+11 | 0.00 | 0.00 | 103208.77 | 0.00 | 0.532575E+09 | 0.243622E+09 | 0.00 | 0.28 |
February | 0.114658E+11 | 0.00 | 0.00 | 111255.08 | 0.00 | 11159508.31 | 0.348425E+09 | 0.00 | 0.29 |
March | 0.124822E+11 | 0.00 | 0.00 | 477108.95 | 0.00 | 9903870.55 | 0.105710E+10 | 0.00 | 0.31 |
April | 0.413561E+10 | 809321.08 | 0.00 | 14523405.39 | 0.00 | 0.00 | 0.917255E+10 | 0.00 | 0.41 |
May | 0.375446E+10 | 0.00 | 0.00 | 20175254.24 | 0.00 | 0.00 | 0.114502E+11 | 0.00 | 0.48 |
June | 0.165748E+10 | 12930447.07 | 0.00 | 26072707.20 | 26169878.61 | 0.00 | 0.134553E+11 | 0.00 | 0.65 |
July | 0.179901E+10 | 13850867.18 | 0.00 | 25971082.16 | 3813579.59 | 0.00 | 0.115183E+11 | 0.00 | 0.69 |
August | 0.152009E+10 | 0.00 | 0.00 | 28080259.48 | 0.00 | 0.00 | 0.113552E+11 | 0.00 | 0.77 |
September | 0.249859E+10 | 0.00 | 0.00 | 20907468.71 | 81356.96 | 0.00 | 0.104847E+11 | 0.00 | 0.63 |
October | 0.677371E+10 | 0.00 | 0.00 | 6455652.56 | 0.00 | 0.00 | 0.521984E+10 | 0.00 | 0.35 |
November | 0.105336E+11 | 0.00 | 0.00 | 497914.86 | 0.00 | 22208763.52 | 0.991464E+09 | 0.00 | 0.29 |
December | 0.123784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167107E+09 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.814323E+11 | 27590635.33 | 0.00 | 0.143375E+09 | 30064815.16 | 0.742954E+09 | 0.752966E+11 | 0.00 | 0.45 |
Minimum of Months | 0.152009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.124822E+11 | 13850867.18 | 0.00 | 28080259.48 | 26169878.61 | 0.532575E+09 | 0.134553E+11 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151479E+10 | 0.00 | 0.00 | 0.28 |
February | 0.104742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575889E+09 | 0.00 | 0.00 | 0.28 |
March | 0.121262E+11 | 0.00 | 0.00 | 39752.41 | 0.00 | 0.378292E+09 | 0.175859E+09 | 0.00 | 0.31 |
April | 0.574034E+10 | 1942890.16 | 0.00 | 10084731.81 | 433010.60 | 2029164.63 | 0.694119E+10 | 0.00 | 0.39 |
May | 0.493137E+10 | 0.00 | 0.00 | 15186407.16 | 0.00 | 0.00 | 0.947201E+10 | 0.00 | 0.45 |
June | 0.261488E+10 | 6059319.28 | 0.00 | 22587858.85 | 19481761.49 | 0.00 | 0.120361E+11 | 0.00 | 0.63 |
July | 0.263825E+10 | 13676135.10 | 0.00 | 22256920.56 | 1765277.36 | 0.00 | 0.104978E+11 | 0.00 | 0.67 |
August | 0.224676E+10 | 0.00 | 0.00 | 22536327.42 | 0.00 | 0.00 | 0.100680E+11 | 0.00 | 0.73 |
September | 0.382456E+10 | 0.00 | 0.00 | 14501603.37 | 0.00 | 0.00 | 0.783306E+10 | 0.00 | 0.57 |
October | 0.832037E+10 | 0.00 | 0.00 | 2573715.05 | 0.00 | 56629339.72 | 0.230321E+10 | 0.00 | 0.33 |
November | 0.100684E+11 | 0.00 | 0.00 | 44657.28 | 0.00 | 0.412848E+09 | 0.113458E+09 | 0.00 | 0.29 |
December | 0.932399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221721E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.830660E+11 | 21678344.54 | 0.00 | 0.109812E+09 | 21680049.46 | 0.515768E+10 | 0.594407E+11 | 0.00 | 0.43 |
Minimum of Months | 0.224676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.121262E+11 | 13676135.10 | 0.00 | 22587858.85 | 19481761.49 | 0.221721E+10 | 0.120361E+11 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.653771E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200780E+10 | 0.00 | 0.00 | 0.29 |
February | 0.962376E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139747E+10 | 0.00 | 0.00 | 0.29 |
March | 0.175578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.928950E+09 | 0.00 | 0.00 | 0.31 |
April | 0.151204E+10 | 0.00 | 0.00 | 1379443.79 | 498755.53 | 97868904.03 | 0.989406E+09 | 0.00 | 0.38 |
May | 0.151650E+10 | 0.00 | 0.00 | 2335802.78 | 0.00 | 7924124.58 | 0.144361E+10 | 0.00 | 0.46 |
June | 0.710434E+09 | 2126315.86 | 0.00 | 5103871.02 | 4093804.95 | 0.00 | 0.258641E+10 | 0.00 | 0.71 |
July | 0.629906E+09 | 3778126.43 | 0.00 | 5303609.50 | 370947.01 | 0.00 | 0.244808E+10 | 0.00 | 0.78 |
August | 0.679252E+09 | 0.00 | 0.00 | 4826307.80 | 0.00 | 0.00 | 0.206766E+10 | 0.00 | 0.79 |
September | 0.119547E+10 | 0.00 | 0.00 | 2193126.49 | 0.00 | 3804738.92 | 0.113206E+10 | 0.00 | 0.54 |
October | 0.166257E+10 | 0.00 | 0.00 | 159161.45 | 0.00 | 0.363373E+09 | 0.160963E+09 | 0.00 | 0.32 |
November | 0.107838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117898E+10 | 0.00 | 0.00 | 0.29 |
December | 0.452431E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206397E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.128089E+11 | 5904442.29 | 0.00 | 21301322.82 | 4963507.49 | 0.805014E+10 | 0.108282E+11 | 0.00 | 0.45 |
Minimum of Months | 0.452431E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.175578E+10 | 3778126.43 | 0.00 | 5303609.50 | 4093804.95 | 0.206397E+10 | 0.258641E+10 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.611126E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107699E+10 | 0.00 | 0.00 | 0.29 |
February | 0.767164E+09 | 0.00 | 0.00 | 2202.28 | 0.00 | 0.723807E+09 | 4068114.14 | 0.00 | 0.29 |
March | 0.120601E+10 | 0.00 | 0.00 | 415.20 | 0.00 | 0.495316E+09 | 1670721.92 | 0.00 | 0.31 |
April | 0.549819E+09 | 1898981.30 | 0.00 | 4573782.22 | 0.00 | 13451877.17 | 0.243764E+10 | 0.00 | 0.73 |
May | 0.575303E+09 | 0.00 | 0.00 | 5047784.59 | 0.00 | 2477215.13 | 0.264992E+10 | 0.00 | 0.81 |
June | 0.302758E+09 | 2614786.78 | 0.00 | 6938717.33 | 1605366.27 | 0.00 | 0.316715E+10 | 0.00 | 1.20 |
July | 0.264175E+09 | 11552176.38 | 0.00 | 7455603.70 | 234889.40 | 0.00 | 0.299057E+10 | 0.00 | 1.29 |
August | 0.281301E+09 | 0.00 | 0.00 | 7331672.46 | 0.00 | 0.00 | 0.288803E+10 | 0.00 | 1.43 |
September | 0.502421E+09 | 0.00 | 0.00 | 4794981.44 | 0.00 | 766842.16 | 0.214738E+10 | 0.00 | 1.01 |
October | 0.931426E+09 | 0.00 | 0.00 | 839719.48 | 0.00 | 0.181355E+09 | 0.514068E+09 | 0.00 | 0.38 |
November | 0.800246E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633336E+09 | 0.00 | 0.00 | 0.29 |
December | 0.393156E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120792E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.718490E+10 | 16065944.46 | 0.00 | 36984878.70 | 1840255.67 | 0.433542E+10 | 0.168005E+11 | 0.00 | 0.69 |
Minimum of Months | 0.264175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.120601E+10 | 11552176.38 | 0.00 | 7455603.70 | 1605366.27 | 0.120792E+10 | 0.316715E+10 | 0.00 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109280E+10 | 0.00 | 0.00 | 1172178.36 | 0.00 | 0.124473E+10 | 0.702150E+09 | 0.00 | 0.33 |
February | 0.112807E+10 | 0.00 | 0.00 | 1766255.86 | 0.00 | 0.832472E+09 | 0.101996E+10 | 0.00 | 0.36 |
March | 0.175529E+10 | 0.00 | 0.00 | 480767.55 | 0.00 | 0.695501E+09 | 0.360502E+09 | 0.00 | 0.32 |
April | 0.903296E+09 | 19735.55 | 0.00 | 9000920.83 | 480760.57 | 79156247.92 | 0.470401E+10 | 0.00 | 0.87 |
May | 0.108641E+10 | 0.00 | 0.00 | 7133240.99 | 0.00 | 20325143.85 | 0.389915E+10 | 0.00 | 0.78 |
June | 0.667414E+09 | 4628808.12 | 0.00 | 8525486.05 | 2544108.19 | 530328.21 | 0.408950E+10 | 0.00 | 1.05 |
July | 0.539385E+09 | 3634571.74 | 0.00 | 9916287.58 | 1086159.88 | 0.00 | 0.412760E+10 | 0.00 | 1.19 |
August | 0.480799E+09 | 0.00 | 0.00 | 12108762.87 | 0.00 | 0.00 | 0.463095E+10 | 0.00 | 1.51 |
September | 0.726645E+09 | 0.00 | 0.00 | 11244321.92 | 0.00 | 2026974.89 | 0.487984E+10 | 0.00 | 1.40 |
October | 0.124144E+10 | 0.00 | 0.00 | 4538523.44 | 0.00 | 0.229557E+09 | 0.267506E+10 | 0.00 | 0.63 |
November | 0.124895E+10 | 0.00 | 0.00 | 1114653.86 | 0.00 | 0.756702E+09 | 0.565881E+09 | 0.00 | 0.33 |
December | 0.799301E+09 | 0.00 | 0.00 | 503899.05 | 0.00 | 0.157847E+10 | 0.257273E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.116698E+11 | 8283115.41 | 0.00 | 67505298.35 | 4111028.63 | 0.543947E+10 | 0.319119E+11 | 0.00 | 0.76 |
Minimum of Months | 0.480799E+09 | 0.00 | 0.00 | 480767.55 | 0.00 | 0.00 | 0.257273E+09 | 0.00 | 0.30 |
Maximum of Months | 0.175529E+10 | 4628808.12 | 0.00 | 12108762.87 | 2544108.19 | 0.157847E+10 | 0.487984E+10 | 0.00 | 1.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.567643E+09 | 0.00 | 0.00 | 21415.67 | 0.00 | 0.111152E+10 | 24211086.47 | 0.00 | 0.29 |
February | 0.667425E+09 | 0.00 | 0.00 | 207742.97 | 0.00 | 0.729016E+09 | 0.172861E+09 | 0.00 | 0.30 |
March | 0.110518E+10 | 0.00 | 0.00 | 158759.60 | 0.00 | 0.531470E+09 | 0.123543E+09 | 0.00 | 0.32 |
April | 0.746823E+09 | 0.00 | 0.00 | 4068754.95 | 317143.03 | 58082400.06 | 0.208805E+10 | 0.00 | 0.71 |
May | 0.709326E+09 | 0.00 | 0.00 | 4784579.59 | 0.00 | 13816918.45 | 0.256187E+10 | 0.00 | 0.84 |
June | 0.371346E+09 | 13869873.38 | 0.00 | 6987683.62 | 344886.97 | 0.00 | 0.316039E+10 | 0.00 | 1.25 |
July | 0.320720E+09 | 2817220.20 | 0.00 | 7923378.42 | 345176.33 | 0.00 | 0.298669E+10 | 0.00 | 1.36 |
August | 0.310421E+09 | 0.00 | 0.00 | 6851376.62 | 0.00 | 0.00 | 0.254675E+10 | 0.00 | 1.32 |
September | 0.596356E+09 | 0.00 | 0.00 | 3905240.14 | 0.00 | 1597875.79 | 0.174148E+10 | 0.00 | 0.93 |
October | 0.955365E+09 | 0.00 | 0.00 | 893257.69 | 0.00 | 0.213724E+09 | 0.574584E+09 | 0.00 | 0.41 |
November | 0.728819E+09 | 0.00 | 0.00 | 48518.46 | 0.00 | 0.679450E+09 | 42924423.18 | 0.00 | 0.29 |
December | 0.327673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128601E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.740710E+10 | 16687093.58 | 0.00 | 35850707.72 | 1007206.33 | 0.462469E+10 | 0.160233E+11 | 0.00 | 0.70 |
Minimum of Months | 0.310421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.110518E+10 | 13869873.38 | 0.00 | 7923378.42 | 345176.33 | 0.128601E+10 | 0.316039E+10 | 0.00 | 1.36 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.959009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183822E+10 | 0.00 | 0.00 | 0.28 |
February | 0.119174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124487E+10 | 0.00 | 0.00 | 0.27 |
March | 0.197889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710166E+09 | 0.00 | 0.00 | 0.29 |
April | 0.190536E+10 | 0.00 | 0.00 | 304547.81 | 23229.56 | 19081565.71 | 0.287631E+09 | 0.00 | 0.32 |
May | 0.174712E+10 | 0.00 | 0.00 | 1118807.57 | 0.00 | 0.00 | 0.719157E+09 | 0.00 | 0.37 |
June | 0.817557E+09 | 2701618.95 | 0.00 | 3542423.38 | 6262874.71 | 0.00 | 0.181755E+10 | 0.00 | 0.57 |
July | 0.697539E+09 | 2855836.51 | 0.00 | 4122589.37 | 648297.89 | 0.00 | 0.180622E+10 | 0.00 | 0.64 |
August | 0.794124E+09 | 0.00 | 0.00 | 3655788.54 | 0.00 | 0.00 | 0.148953E+10 | 0.00 | 0.66 |
September | 0.130906E+10 | 0.00 | 0.00 | 1740244.52 | 106234.11 | 0.00 | 0.880507E+09 | 0.00 | 0.49 |
October | 0.202071E+10 | 0.00 | 0.00 | 79378.43 | 0.00 | 33759194.50 | 65450307.76 | 0.00 | 0.28 |
November | 0.185524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490760E+09 | 0.00 | 0.00 | 0.27 |
December | 0.959338E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171246E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.162357E+11 | 5557455.46 | 0.00 | 14563779.63 | 7040636.27 | 0.604931E+10 | 0.706605E+10 | 0.00 | 0.39 |
Minimum of Months | 0.697539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.202071E+10 | 2855836.51 | 0.00 | 4122589.37 | 6262874.71 | 0.183822E+10 | 0.181755E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.831704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937513E+09 | 0.00 | 0.00 | 0.28 |
February | 0.975090E+09 | 0.00 | 0.00 | 156.15 | 0.00 | 0.568852E+09 | 2071463.92 | 0.00 | 0.27 |
March | 0.133274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373023E+09 | 0.00 | 0.00 | 0.29 |
April | 0.584222E+09 | 73885.70 | 0.00 | 3693540.64 | 0.00 | 641590.06 | 0.181513E+10 | 0.00 | 0.59 |
May | 0.510998E+09 | 0.00 | 0.00 | 4422597.07 | 0.00 | 0.00 | 0.223026E+10 | 0.00 | 0.70 |
June | 0.298671E+09 | 2649948.24 | 0.00 | 5863012.17 | 3959420.64 | 0.00 | 0.263245E+10 | 0.00 | 1.05 |
July | 0.212106E+09 | 5941013.97 | 0.00 | 6598903.39 | 409857.16 | 0.00 | 0.262908E+10 | 0.00 | 1.15 |
August | 0.236013E+09 | 0.00 | 0.00 | 6863220.78 | 0.00 | 0.00 | 0.261215E+10 | 0.00 | 1.31 |
September | 0.387420E+09 | 0.00 | 0.00 | 5046115.15 | 67161.74 | 0.00 | 0.224620E+10 | 0.00 | 1.00 |
October | 0.110967E+10 | 0.00 | 0.00 | 1019929.99 | 0.00 | 16332700.41 | 0.377649E+09 | 0.00 | 0.32 |
November | 0.124250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244028E+09 | 0.00 | 0.00 | 0.27 |
December | 0.744555E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.953052E+09 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.846569E+10 | 8664847.91 | 0.00 | 33507475.34 | 4436439.54 | 0.309344E+10 | 0.145450E+11 | 0.00 | 0.63 |
Minimum of Months | 0.212106E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.133274E+10 | 5941013.97 | 0.00 | 6863220.78 | 3959420.64 | 0.953052E+09 | 0.263245E+10 | 0.00 | 1.31 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.926072E+09 | 0.00 | 0.00 | 162800.82 | 0.00 | 0.289935E+10 | 0.128728E+09 | 0.00 | 0.38 |
February | 0.122409E+10 | 0.00 | 0.00 | 206092.02 | 0.00 | 0.195704E+10 | 0.170350E+09 | 0.00 | 0.37 |
March | 0.135529E+10 | 0.00 | 0.00 | 1813.53 | 0.00 | 0.232844E+10 | 3055563.71 | 0.00 | 0.39 |
April | 0.129868E+10 | 0.00 | 0.00 | 3146325.98 | 23283.63 | 0.570420E+09 | 0.155551E+10 | 0.00 | 0.54 |
May | 0.144675E+10 | 0.00 | 0.00 | 2214329.31 | 0.00 | 0.502235E+09 | 0.129086E+10 | 0.00 | 0.52 |
June | 0.122284E+10 | 4682569.35 | 0.00 | 3158541.68 | 6277452.65 | 0.179231E+09 | 0.145465E+10 | 0.00 | 0.67 |
July | 0.764419E+09 | 4950427.88 | 0.00 | 5162988.56 | 645862.06 | 76831053.48 | 0.209379E+10 | 0.00 | 0.80 |
August | 0.614847E+09 | 0.00 | 0.00 | 7930508.56 | 0.00 | 67679902.23 | 0.283424E+10 | 0.00 | 1.11 |
September | 0.704611E+09 | 179282.43 | 0.00 | 7930826.75 | 18692.20 | 0.180896E+09 | 0.333359E+10 | 0.00 | 1.10 |
October | 0.134678E+10 | 0.00 | 0.00 | 2556546.84 | 0.00 | 0.709550E+09 | 0.112132E+10 | 0.00 | 0.44 |
November | 0.140364E+10 | 0.00 | 0.00 | 169952.68 | 0.00 | 0.162860E+10 | 0.131478E+09 | 0.00 | 0.36 |
December | 0.588365E+09 | 0.00 | 0.00 | 13467.36 | 0.00 | 0.314555E+10 | 16275603.53 | 0.00 | 0.38 |
Annual Sum or Average | 0.128964E+11 | 9812279.65 | 0.00 | 32654194.10 | 6965290.54 | 0.142458E+11 | 0.141338E+11 | 0.00 | 0.59 |
Minimum of Months | 0.588365E+09 | 0.00 | 0.00 | 1813.53 | 0.00 | 67679902.23 | 3055563.71 | 0.00 | 0.36 |
Maximum of Months | 0.144675E+10 | 4950427.88 | 0.00 | 7930826.75 | 6277452.65 | 0.314555E+10 | 0.333359E+10 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.789208E+09 | 0.00 | 0.00 | 4683.89 | 0.00 | 0.975615E+09 | 6812099.67 | 0.00 | 0.28 |
February | 0.100186E+10 | 0.00 | 0.00 | 78627.64 | 0.00 | 0.487797E+09 | 67098735.74 | 0.00 | 0.28 |
March | 0.131021E+10 | 0.00 | 0.00 | 44091.93 | 0.00 | 0.366287E+09 | 32939867.85 | 0.00 | 0.29 |
April | 0.832836E+09 | 14651.68 | 0.00 | 2661644.53 | 0.00 | 6131917.91 | 0.122525E+10 | 0.00 | 0.52 |
May | 0.662358E+09 | 0.00 | 0.00 | 3786319.75 | 0.00 | 0.00 | 0.194390E+10 | 0.00 | 0.69 |
June | 0.281971E+09 | 14583929.09 | 0.00 | 5809202.46 | 497205.40 | 0.00 | 0.261002E+10 | 0.00 | 1.05 |
July | 0.264931E+09 | 4034327.45 | 0.00 | 6779670.25 | 74384.47 | 0.00 | 0.255596E+10 | 0.00 | 1.20 |
August | 0.265762E+09 | 0.00 | 0.00 | 5940379.23 | 0.00 | 0.00 | 0.218563E+10 | 0.00 | 1.17 |
September | 0.514907E+09 | 68114.08 | 0.00 | 3549063.97 | 13983.51 | 0.00 | 0.160061E+10 | 0.00 | 0.85 |
October | 0.113425E+10 | 0.00 | 0.00 | 821700.68 | 0.00 | 17366161.74 | 0.340330E+09 | 0.00 | 0.32 |
November | 0.117691E+10 | 0.00 | 0.00 | 31475.74 | 0.00 | 0.279848E+09 | 29315308.92 | 0.00 | 0.27 |
December | 0.613275E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108291E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.884848E+10 | 18701022.30 | 0.00 | 29506860.06 | 585573.38 | 0.321595E+10 | 0.125979E+11 | 0.00 | 0.60 |
Minimum of Months | 0.264931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.131021E+10 | 14583929.09 | 0.00 | 6779670.25 | 497205.40 | 0.108291E+10 | 0.261002E+10 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.135542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145098E+10 | 0.00 | 0.00 | 0.29 |
February | 0.168378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.811490E+09 | 0.00 | 0.00 | 0.29 |
March | 0.247715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379905E+09 | 0.00 | 0.00 | 0.31 |
April | 0.149929E+10 | 102198.75 | 0.00 | 1852155.05 | 0.00 | 7450612.09 | 0.115606E+10 | 0.00 | 0.39 |
May | 0.126663E+10 | 0.00 | 0.00 | 3090121.98 | 0.00 | 0.00 | 0.177139E+10 | 0.00 | 0.47 |
June | 0.565034E+09 | 4654633.86 | 0.00 | 5787339.62 | 5505777.76 | 0.00 | 0.280639E+10 | 0.00 | 0.73 |
July | 0.525333E+09 | 5007336.25 | 0.00 | 5821283.75 | 802324.00 | 0.00 | 0.254936E+10 | 0.00 | 0.79 |
August | 0.610296E+09 | 0.00 | 0.00 | 5465614.17 | 0.00 | 0.00 | 0.218018E+10 | 0.00 | 0.82 |
September | 0.112924E+10 | 0.00 | 0.00 | 2824366.11 | 17116.37 | 0.00 | 0.136760E+10 | 0.00 | 0.58 |
October | 0.204897E+10 | 0.00 | 0.00 | 298801.21 | 0.00 | 50943455.78 | 0.277578E+09 | 0.00 | 0.33 |
November | 0.190372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532175E+09 | 0.00 | 0.00 | 0.29 |
December | 0.104927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161287E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.161141E+11 | 9764168.85 | 0.00 | 25139681.88 | 6325218.13 | 0.484581E+10 | 0.121085E+11 | 0.00 | 0.47 |
Minimum of Months | 0.525333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.247715E+10 | 5007336.25 | 0.00 | 5821283.75 | 5505777.76 | 0.161287E+10 | 0.280639E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.801740E+09 | 0.00 | 0.00 | 6103.75 | 0.00 | 0.688481E+09 | 6380757.79 | 0.00 | 0.24 |
February | 0.891426E+09 | 0.00 | 0.00 | 50023.98 | 0.00 | 0.403375E+09 | 35174131.15 | 0.00 | 0.24 |
March | 0.124565E+10 | 0.00 | 0.00 | 48361.59 | 0.00 | 0.207770E+09 | 54579451.89 | 0.00 | 0.26 |
April | 0.534686E+09 | 464149.35 | 0.00 | 4960290.45 | 0.00 | 471772.39 | 0.245966E+10 | 0.00 | 0.73 |
May | 0.498848E+09 | 0.00 | 0.00 | 5429954.23 | 0.00 | 0.00 | 0.267396E+10 | 0.00 | 0.80 |
June | 0.267329E+09 | 3357592.18 | 0.00 | 6907112.82 | 3483588.63 | 0.00 | 0.303930E+10 | 0.00 | 1.16 |
July | 0.196316E+09 | 8729123.85 | 0.00 | 7491127.18 | 507642.50 | 0.00 | 0.286667E+10 | 0.00 | 1.23 |
August | 0.240278E+09 | 0.00 | 0.00 | 7554744.51 | 0.00 | 0.00 | 0.280760E+10 | 0.00 | 1.39 |
September | 0.421830E+09 | 0.00 | 0.00 | 5415225.50 | 10829.79 | 0.00 | 0.228622E+10 | 0.00 | 1.02 |
October | 0.943303E+09 | 0.00 | 0.00 | 1153072.62 | 0.00 | 30718585.65 | 0.647364E+09 | 0.00 | 0.36 |
November | 0.994772E+09 | 0.00 | 0.00 | 7252.37 | 0.00 | 0.285586E+09 | 8958347.37 | 0.00 | 0.24 |
December | 0.577299E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838679E+09 | 0.00 | 0.00 | 0.23 |
Annual Sum or Average | 0.761348E+10 | 12550865.39 | 0.00 | 39023268.99 | 4002060.91 | 0.245508E+10 | 0.168859E+11 | 0.00 | 0.66 |
Minimum of Months | 0.196316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
Maximum of Months | 0.124565E+10 | 8729123.85 | 0.00 | 7554744.51 | 3483588.63 | 0.838679E+09 | 0.303930E+10 | 0.00 | 1.39 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.160001E+10 | 0.00 | 0.00 | 1587826.15 | 0.00 | 0.834673E+09 | 0.923905E+09 | 0.00 | 0.34 |
February | 0.165734E+10 | 0.00 | 0.00 | 2297812.97 | 0.00 | 0.364889E+09 | 0.126887E+10 | 0.00 | 0.39 |
March | 0.225372E+10 | 0.00 | 0.00 | 758942.42 | 0.00 | 0.247683E+09 | 0.544368E+09 | 0.00 | 0.34 |
April | 0.970203E+09 | 162271.93 | 0.00 | 9817168.04 | 0.00 | 2250869.70 | 0.466203E+10 | 0.00 | 0.90 |
May | 0.974980E+09 | 0.00 | 0.00 | 7892708.38 | 0.00 | 0.00 | 0.399581E+10 | 0.00 | 0.80 |
June | 0.579027E+09 | 6354124.97 | 0.00 | 8865692.69 | 5521626.36 | 0.00 | 0.406545E+10 | 0.00 | 1.05 |
July | 0.480570E+09 | 7697362.06 | 0.00 | 10031014.10 | 804633.52 | 0.00 | 0.394965E+10 | 0.00 | 1.19 |
August | 0.456616E+09 | 0.00 | 0.00 | 12472679.68 | 0.00 | 0.00 | 0.438602E+10 | 0.00 | 1.53 |
September | 0.657117E+09 | 64171.79 | 0.00 | 12062742.87 | 488.42 | 0.00 | 0.493100E+10 | 0.00 | 1.46 |
October | 0.144346E+10 | 0.00 | 0.00 | 5454260.40 | 0.00 | 34190027.85 | 0.303173E+10 | 0.00 | 0.69 |
November | 0.175948E+10 | 0.00 | 0.00 | 1617528.74 | 0.00 | 0.319163E+09 | 0.813830E+09 | 0.00 | 0.35 |
December | 0.130921E+10 | 0.00 | 0.00 | 714552.83 | 0.00 | 0.119150E+10 | 0.363023E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.141417E+11 | 14277930.75 | 0.00 | 73572929.26 | 6326748.30 | 0.299435E+10 | 0.329357E+11 | 0.00 | 0.78 |
Minimum of Months | 0.456616E+09 | 0.00 | 0.00 | 714552.83 | 0.00 | 0.00 | 0.363023E+09 | 0.00 | 0.31 |
Maximum of Months | 0.225372E+10 | 7697362.06 | 0.00 | 12472679.68 | 5521626.36 | 0.119150E+10 | 0.493100E+10 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.968795E+09 | 0.00 | 0.00 | 39366.95 | 0.00 | 0.783938E+09 | 36559929.12 | 0.00 | 0.29 |
February | 0.110265E+10 | 0.00 | 0.00 | 304807.40 | 0.00 | 0.348530E+09 | 0.226258E+09 | 0.00 | 0.30 |
March | 0.150798E+10 | 0.00 | 0.00 | 214889.15 | 0.00 | 0.203163E+09 | 0.162420E+09 | 0.00 | 0.32 |
April | 0.714635E+09 | 64505.73 | 0.00 | 4510876.51 | 0.00 | 3731375.85 | 0.212250E+10 | 0.00 | 0.72 |
May | 0.581330E+09 | 0.00 | 0.00 | 5273118.02 | 0.00 | 0.00 | 0.266312E+10 | 0.00 | 0.85 |
June | 0.288735E+09 | 18524193.55 | 0.00 | 7170699.15 | 495549.89 | 0.00 | 0.315439E+10 | 0.00 | 1.25 |
July | 0.277941E+09 | 6174413.01 | 0.00 | 7953515.23 | 91755.36 | 0.00 | 0.287203E+10 | 0.00 | 1.36 |
August | 0.284771E+09 | 0.00 | 0.00 | 7109448.54 | 0.00 | 0.00 | 0.247545E+10 | 0.00 | 1.35 |
September | 0.532084E+09 | 36090.92 | 0.00 | 4314200.03 | 0.00 | 0.00 | 0.184575E+10 | 0.00 | 0.97 |
October | 0.114860E+10 | 0.00 | 0.00 | 1101691.56 | 0.00 | 33186985.16 | 0.691541E+09 | 0.00 | 0.43 |
November | 0.116670E+10 | 0.00 | 0.00 | 83206.58 | 0.00 | 0.325772E+09 | 69428172.82 | 0.00 | 0.29 |
December | 0.673446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101837E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.924767E+10 | 24799203.21 | 0.00 | 38075819.11 | 587305.25 | 0.271669E+10 | 0.163195E+11 | 0.00 | 0.70 |
Minimum of Months | 0.277941E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.150798E+10 | 18524193.55 | 0.00 | 7953515.23 | 495549.89 | 0.101837E+10 | 0.315439E+10 | 0.00 | 1.36 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.852506E+11 | 0.785770E+10 | 0.00 | 0.160626E+12 | 0.623398E+10 |
February | 0.131076E+12 | 0.861323E+10 | 0.00 | 0.152859E+12 | 0.486272E+10 |
March | 0.152836E+12 | 0.745321E+10 | 0.00 | 0.180490E+12 | 0.430760E+10 |
April | 0.392883E+12 | 0.699227E+10 | 0.00 | 0.230767E+12 | 0.883323E+10 |
May | 0.468744E+12 | 0.120938E+11 | 0.00 | 0.242303E+12 | 0.104010E+11 |
June | 0.469375E+12 | 0.916107E+10 | 0.00 | 0.246818E+12 | 0.318976E+11 |
July | 0.475499E+12 | 0.804361E+10 | 0.00 | 0.247426E+12 | 0.527620E+11 |
August | 0.392979E+12 | 0.634616E+10 | 0.00 | 0.231231E+12 | 0.661166E+11 |
September | 0.298525E+12 | 0.728462E+10 | 0.00 | 0.246470E+12 | 0.332993E+11 |
October | 0.140488E+12 | 0.850305E+10 | 0.00 | 0.199651E+12 | 0.645044E+10 |
November | 0.623037E+11 | 0.100349E+11 | 0.00 | 0.168565E+12 | 0.355220E+10 |
December | 0.310827E+11 | 0.122439E+11 | 0.00 | 0.147278E+12 | 0.606869E+10 |
Annual Sum or Average | 0.310104E+13 | 0.104628E+12 | 0.00 | 0.245448E+13 | 0.234785E+12 |
Minimum of Months | 0.310827E+11 | 0.634616E+10 | 0.00 | 0.147278E+12 | 0.355220E+10 |
Maximum of Months | 0.475499E+12 | 0.122439E+11 | 0.00 | 0.247426E+12 | 0.661166E+11 |