Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2023-10-16 08:32:04
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2165.02 | 434.55 | 434.55 |
Net Site Energy | 2165.02 | 434.55 | 434.55 |
Total Source Energy | 6005.01 | 1205.30 | 1205.30 |
Net Source Energy | 6005.01 | 1205.30 | 1205.30 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 583.98 | 259.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 51.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 56.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 84.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 21.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 149.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1756.18 | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 583.98 | 259.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 51.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 56.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 84.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 21.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 149.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 583.98 | 259.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 51.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 56.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 84.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 21.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 149.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 59.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 144.52 | 82.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 148.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 352.49 | 82.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 59.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 144.52 | 82.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 148.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 352.49 | 82.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1756.183 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1756.183 | 100.00 |
Total On-Site and Utility Electric Sources | 1756.183 | 100.00 |
Total Electricity End Uses | 1756.183 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 0.19 | 0.04 |
Air to Air Heat Recovery for Heating | 477.62 | 99.96 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 477.81 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 773.17 |
Time Setpoint Not Met During Occupied Cooling | 63.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3411.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.6636 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.6636 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.6636 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 6.6636 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.6636 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-08:09 | 12-JAN-08:20 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 189891.97 | 214217.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25003.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 45864.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 818.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6456.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2208.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 9635.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 275935.85 | 223852.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 189891.97 | 214217.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 25003.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 818.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6456.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 2208.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 9635.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 1849.46 | 281.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 161.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 764.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 177.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 37.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 268.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 68.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 161.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5561.83 | 443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 371.21 | 56.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 32.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 153.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 35.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 53.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 13.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 32.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1116.34 | 88.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 371.21 | 56.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 32.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 153.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 35.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 53.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 13.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 32.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1116.34 | 88.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.90 | 0.258818 | 0.220000 | 0.637049 | 0.690182 | 0.500000 | 0.001472 |
CORE_MID VAV BOX COMPONENT | 2.14 | 0.349968 | 0.297000 | 0.636024 | 0.933248 | 0.500000 | 0.001089 |
CORE_TOP VAV BOX COMPONENT | 2.07 | 0.362430 | 0.308000 | 0.636902 | 0.966479 | 0.500000 | 0.001051 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.670261 | 0.235716 | 0.220000 | 0.147458 | 0.628577 | 0.500000 | 0.001616 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.831171 | 0.120338 | 0.102000 | 0.084779 | 0.320902 | 0.500000 | 0.003166 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.31 | 0.120282 | 0.102000 | 0.133978 | 0.320751 | 0.500000 | 0.003168 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.866655 | 0.115404 | 0.098000 | 0.084932 | 0.307743 | 0.500000 | 0.003301 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.530308 | 0.297924 | 0.256000 | 0.135759 | 0.794465 | 0.500000 | 0.001279 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.682449 | 0.146563 | 0.125000 | 0.085306 | 0.390834 | 0.500000 | 0.002600 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.07 | 0.148172 | 0.126000 | 0.134350 | 0.395126 | 0.500000 | 0.002571 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.715940 | 0.139698 | 0.119000 | 0.085197 | 0.372527 | 0.500000 | 0.002727 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.588099 | 0.268648 | 0.228000 | 0.134087 | 0.716395 | 0.500000 | 0.001418 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.829439 | 0.321572 | 0.500000 | 0.003159 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.25 | 0.126640 | 0.108000 | 0.134737 | 0.337707 | 0.500000 | 0.003009 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.822859 | 0.121546 | 0.103000 | 0.084754 | 0.324123 | 0.500000 | 0.003135 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 20945.88 |
CORE_MID VAV BOX REHEAT COIL | 27073.77 |
CORE_TOP VAV BOX REHEAT COIL | 49798.59 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 22037.88 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14397.25 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 21939.66 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 14342.57 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 17436.27 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11503.49 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 17371.25 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11460.36 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 16719.96 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 10998.87 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 16629.75 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 10953.19 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.95 | 1.08 | 5.89 | 2.20 | 5.07 | 5.07 | 0.300000 | 0.434699 | 5.07 |
PACU_VAV_MID | 2.81 | 1.08 | 5.63 | 2.51 | 4.55 | 4.55 | 0.300000 | 0.551025 | 4.55 |
PACU_VAV_TOP | 2.87 | 1.09 | 5.75 | 3.73 | 4.96 | 4.96 | 0.300000 | 0.750696 | 4.96 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.07 |
PACU_VAV_MID_OA_CONTROLLER | 4.55 |
PACU_VAV_TOP_OA_CONTROLLER | 4.96 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT OA HEAT RECOVERY | 0.956100 |
PACU_VAV_MID OA HEAT RECOVERY | 0.956100 |
PACU_VAV_TOP OA HEAT RECOVERY | 0.956100 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.07 | 83917.70 | 0.800655 | 1.69 | 27969.77 | 0.800655 |
PACU_VAV_MID COOLING COIL | 4.55 | 75264.93 | 0.800655 | 1.52 | 25085.80 | 0.800655 |
PACU_VAV_TOP COOLING COIL | 4.96 | 82166.36 | 0.800655 | 1.65 | 27386.05 | 0.800655 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 58547.19 |
PACU_VAV_MID HEATING COIL | 59877.62 |
PACU_VAV_TOP HEATING COIL | 59016.04 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.07 |
PACU_VAV_MID FAN | 4.55 |
PACU_VAV_TOP FAN | 4.96 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 31.498 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6761 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.6631 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.8981 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1861 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1962 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1861 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1962 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.245 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.274 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8794 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.298 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.019 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.298 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.019 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
39 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
40 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
41 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
42 | 7 | -0.32863397E-12 | 0.12532498E-14 | -0.10432781E-12 | 0.10000009E-15 |
43 | 6 | 0.29860290E-07 | 0.19244976E-09 | 0.68304209E-08 | -0.14159436E-12 |
44 | 5 | -0.19612469E-03 | 0.16345755E-05 | -0.10079517E-03 | 0.67484823E-08 |
45 | 4 | 0.29915968 | 0.79015507E-03 | 0.10220689 | -0.34563380E-04 |
46 | 3 | -7.4051490 | 0.24331082E-01 | -2.3801101 | 0.29689509E-01 |
47 | 2 | 41.328906 | 0.86029560E-01 | 15.433920 | -0.33843907 |
48 | 1 | -80.896497 | 0.38634018E-01 | -29.293000 | 1.0860931 |
49 | 0 | 46.824336 | 0.77350051E-03 | 16.287644 | |
50 | 7 | -0.32990843E-12 | 0.11750686E-14 | -0.10494268E-12 | 0.10070323E-15 |
51 | 6 | 0.30013254E-07 | 0.18902410E-09 | 0.68641830E-08 | -0.14241961E-12 |
52 | 5 | -0.19689619E-03 | 0.16039916E-05 | -0.10118091E-03 | 0.67813509E-08 |
53 | 4 | 0.30005484 | 0.77472963E-03 | 0.10252920 | -0.34690470E-04 |
54 | 3 | -7.4228592 | 0.23838592E-01 | -2.3853666 | 0.29776351E-01 |
55 | 2 | 41.387294 | 0.84233400E-01 | 15.455437 | -0.33908948 |
56 | 1 | -80.941219 | 0.37805857E-01 | -29.312279 | 1.0870462 |
57 | 0 | 46.824336 | 0.75649625E-03 | 16.287191 | |
58 | 7 | -0.28528047E-12 | 0.14314274E-14 | -0.82259378E-13 | 0.81732043E-16 |
59 | 6 | 0.27222731E-07 | 0.24871836E-09 | 0.62482715E-08 | -0.12743522E-12 |
60 | 5 | -0.18272614E-03 | 0.21485338E-05 | -0.94080885E-04 | 0.61809713E-08 |
61 | 4 | 0.28347135 | 0.10543336E-02 | 0.96565215E-01 | -0.32350904E-04 |
62 | 3 | -7.0944292 | 0.32900988E-01 | -2.2879113 | 0.28166852E-01 |
63 | 2 | 40.304118 | 0.11770635 | 15.055686 | -0.32702567 |
64 | 1 | -80.111171 | 0.53403795E-01 | -28.953874 | 1.0693576 |
65 | 0 | 46.824341 | 0.10800274E-02 | 16.295775 | |
66 | 7 | -0.22718025E-08 | -0.85076432E-15 | 0.54602610E-14 | -0.81699313E-16 |
67 | 6 | 0.52504722E-05 | 0.35612887E-08 | 0.31909185E-02 | -0.26768099E-04 |
68 | 5 | -0.37481041E-03 | 0.21076474E-05 | -0.22378418 | 0.19566764E-02 |
69 | 4 | 0.86040017E-02 | 0.95918289E-04 | 4.8305385 | -0.45274525E-01 |
70 | 3 | -0.75502230E-01 | 0.76254733E-03 | -38.027025 | 0.39871575 |
71 | 2 | 0.26802071 | 0.12683646E-02 | 116.49487 | -1.4180853 |
72 | 1 | -0.38680241 | 0.38624458E-03 | -143.91373 | 2.0491456 |
73 | 0 | 0.18857406 | 0.93873709E-05 | 60.838472 | |
74 | 7 | -0.21518248E-08 | -0.72352508E-15 | 0.47198691E-14 | -0.69590188E-16 |
75 | 6 | 0.55239907E-05 | 0.37570600E-08 | 0.31901221E-02 | -0.26761418E-04 |
76 | 5 | -0.39518120E-03 | 0.22239456E-05 | -0.22373891 | 0.19562768E-02 |
77 | 4 | 0.90771213E-02 | 0.10121852E-03 | 4.8297846 | -0.45267278E-01 |
78 | 3 | -0.79671013E-01 | 0.80474906E-03 | -38.022767 | 0.39866868 |
79 | 2 | 0.28284274 | 0.13386367E-02 | 116.48658 | -1.4179745 |
80 | 1 | -0.40820825 | 0.40769430E-03 | -143.90886 | 2.0490654 |
81 | 0 | 0.19901349 | 0.99021926E-05 | 60.838472 | |
82 | 7 | -0.22718025E-08 | -0.85076409E-15 | 0.54602611E-14 | -0.81699316E-16 |
83 | 6 | 0.52504722E-05 | 0.35612887E-08 | 0.31909185E-02 | -0.26768099E-04 |
84 | 5 | -0.37481041E-03 | 0.21076474E-05 | -0.22378418 | 0.19566764E-02 |
85 | 4 | 0.86040017E-02 | 0.95918289E-04 | 4.8305385 | -0.45274525E-01 |
86 | 3 | -0.75502230E-01 | 0.76254733E-03 | -38.027025 | 0.39871575 |
87 | 2 | 0.26802071 | 0.12683646E-02 | 116.49487 | -1.4180853 |
88 | 1 | -0.38680241 | 0.38624458E-03 | -143.91373 | 2.0491456 |
89 | 0 | 0.18857406 | 0.93873709E-05 | 60.838472 | |
90 | 7 | -0.21516764E-08 | -0.72282083E-15 | 0.50090186E-14 | -0.71315031E-16 |
91 | 6 | 0.55243484E-05 | 0.37573175E-08 | 0.31901211E-02 | -0.26761409E-04 |
92 | 5 | -0.39520780E-03 | 0.22240973E-05 | -0.22373885 | 0.19562763E-02 |
93 | 4 | 0.90777390E-02 | 0.10122544E-03 | 4.8297836 | -0.45267268E-01 |
94 | 3 | -0.79676455E-01 | 0.80480411E-03 | -38.022761 | 0.39866862 |
95 | 2 | 0.28286209 | 0.13387285E-02 | 116.48657 | -1.4179743 |
96 | 1 | -0.40823619 | 0.40772215E-03 | -143.90885 | 2.0490653 |
97 | 0 | 0.19902711 | 0.99029315E-05 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.262_SHGC_EAST_0.399 | 35 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 | ||
2 | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 36 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 | ||
3 | WINDOW_U_0.262_SHGC_WEST_0.399 | 37 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 | ||
4 | WINDOW_U_0.262_SHGC_NORTH_0.399 | 38 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4670E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4746E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7334E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7402E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3365E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3814E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5636E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5883E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1611 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1088 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1884 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1319 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.5051E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2487E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0604E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8980E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4676E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4790E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7342E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7455E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3400E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3980E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5633E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5880E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 0.1057 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.5105E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 0.1101 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.7858E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.2097E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1934E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9382E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7963E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 9.1439E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.1778E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 9.4403E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.4664E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8209E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.8298E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3268E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3352E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.9917E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.0654E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0720E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.1371E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0531E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.0959E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5633E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.5880E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 6.2847E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.5557E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0236E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8218E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1357E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7054E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0604E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8980E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.9909E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.0691E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0695E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.1335E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0499E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.0831E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5636E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.5883E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.6340E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.6960E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.8841E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2247E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.6703E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4090E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9383E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7963E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.0787E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 7.1765E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5284E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.6452E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8541E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.8803E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3270E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3354E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1756 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1303 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2049 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1568 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1048 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.4448E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.7665E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.6893E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 0.1016 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 6.2782E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 0.1059 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 6.5428E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.0043E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.0716E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.8278E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7301E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 7.0388E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 4.5246E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.6949E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.6608E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.7749E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.4190E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.7665E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6893E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.3585E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.5436E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.6445E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0946E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.5160E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3198E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.8279E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7302E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1756 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1303 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2050 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1568 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1047 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.4443E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.7660E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.6889E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 0.1016 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 6.2778E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 0.1059 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 6.5423E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.0039E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.0711E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.8273E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7298E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 7.0390E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 4.5244E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.6950E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.6606E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.7746E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.4188E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.7660E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6889E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.3587E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.5434E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.6446E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0944E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.5156E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3195E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.8273E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7299E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 39563.37018 | 39563.37018 | 2.89568 | 2.89568 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 10501.58354 | 10501.58354 | 0.45730 | 0.45730 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 29293.41362 | 29293.41362 | 2.14149 | 2.14149 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 19111.34510 | 19111.34510 | 0.82342 | 0.82342 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 28289.21498 | 28289.21498 | 2.06786 | 2.06786 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 35027.85937 | 35027.85937 | 1.51458 | 1.51458 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8255.81502 | 8255.81502 | 0.60929 | 0.60929 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 21.53500 | 6.99833E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 15467.09077 | 15467.09077 | 0.67026 | 0.67026 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11262.38768 | 11262.38768 | 0.83117 | 0.83117 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 22.36800 | 6.99957E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 10103.98055 | 10103.98055 | 0.43788 | 0.43788 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 17798.10613 | 17798.10613 | 1.31351 | 1.31351 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 15398.29183 | 15398.29183 | 0.66727 | 0.66727 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11743.18691 | 11743.18691 | 0.86666 | 0.86666 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.69700 | 7.00305E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 10065.68205 | 10065.68205 | 0.43622 | 0.43622 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7098.72083 | 7098.72083 | 0.52390 | 0.52390 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 21.07600 | 6.99765E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 12242.85608 | 12242.85608 | 0.53031 | 0.53031 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9247.09942 | 9247.09942 | 0.68245 | 0.68245 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 22.65700 | 7.00000E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 8076.36819 | 8076.36819 | 0.34987 | 0.34987 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 14447.79701 | 14447.79701 | 1.06627 | 1.06627 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 12197.31311 | 12197.31311 | 0.52833 | 0.52833 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9700.89608 | 9700.89608 | 0.71594 | 0.71594 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 23.04800 | 7.00058E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 8046.16064 | 8046.16064 | 0.34856 | 0.34856 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7968.63797 | 7968.63797 | 0.58810 | 0.58810 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 21.38200 | 6.99811E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 11741.86482 | 11741.86482 | 0.50852 | 0.50852 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 11238.88321 | 11238.88321 | 0.82944 | 0.82944 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 22.07900 | 6.99914E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 7723.38620 | 7723.38620 | 0.33452 | 0.33452 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 16904.42698 | 16904.42698 | 1.24756 | 1.24756 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 11678.68159 | 11678.68159 | 0.50578 | 0.50578 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11149.70400 | 11149.70400 | 0.82286 | 0.82286 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.69700 | 7.00305E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 7691.39456 | 7691.39456 | 0.33313 | 0.33313 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 71424.11 | 5.06947 | 5.06947 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 61958.06 | 2.20369 | 2.20369 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 64419.98 | 4.54675 | 4.54675 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 62034.34 | 2.50537 | 2.50537 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 69784.08 | 4.96367 | 4.96367 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 62225.82 | 3.72621 | 3.72621 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.89568 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25882 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63705 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69018 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.47207E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20945.88329 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.14149 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34997 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29700 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63602 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93325 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08867E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 27073.77282 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.06786 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36243 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30800 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63690 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96648 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05124E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 49798.58777 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67026 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23572 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14746 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62858 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.61635E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22037.88045 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83117 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12034 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10200 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47795E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32090 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.16607E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14397.24713 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.31351 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12028 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10200 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13398 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32075 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.16757E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21939.65840 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86666 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11540 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.80000E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.49322E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30774 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.30145E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14342.57105 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.53031 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29792 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25600 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13576 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79447 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.27885E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17436.27363 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68245 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14656 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12500 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.53062E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39083 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.59957E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11503.49148 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.06627 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14817 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12600 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13435 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39513 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.57133E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17371.24848 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71594 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13970 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11900 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51969E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37253 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.72732E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11460.36389 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.58810 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26865 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22800 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13409 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71640 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.41821E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16719.96125 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82944 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32157 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.15948E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10998.86882 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.24756 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12664 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10800 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13474 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33771 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.00853E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16629.75141 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82286 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12155 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10300 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47545E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32412 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.13461E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10953.19424 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.94532 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07766 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.89065 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.20369 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.06947 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.06947 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.43470 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.81473 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07503 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.62946 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.50537 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.54675 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.54675 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.55102 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.87473 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08805 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.74947 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.72621 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.96367 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.96367 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.75070 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.06947 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.54675 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.96367 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.06947 |
146 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_BOT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 0.95610 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.06947 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 83917.70103 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.68965 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 27969.76975 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
153 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 58547.19369 |
154 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.06947 |
155 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.54675 |
156 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_MID OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 0.95610 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.54675 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 75264.92968 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.51543 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 25085.80106 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
163 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 59877.62484 |
164 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.54675 |
165 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.96367 |
166 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_TOP OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 0.95610 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.96367 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 82166.36304 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.65439 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 27386.04880 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 59016.03630 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.96367 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 82473.69 | 281411.90 | 10.81 | 2.80 | 3.09 | 3.26 | 3.43 | 9.54 | 10.55 | 11.11 | 11.69 | 5.7722 | 4.5657 | 3.0596 | 1.2751 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 73969.81 | 252395.46 | 10.81 | 2.80 | 3.09 | 3.26 | 3.43 | 9.54 | 10.55 | 11.11 | 11.69 | 5.1770 | 4.0949 | 2.7441 | 1.1436 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 80752.48 | 275538.91 | 10.81 | 2.80 | 3.09 | 3.26 | 3.43 | 9.54 | 10.55 | 11.11 | 11.69 | 5.6518 | 4.4704 | 2.9958 | 1.2485 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_NORTH_0.399 | N/A | 1.488 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_EAST_0.399 | N/A | 1.488 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_SOUTH_0.399 | N/A | 1.488 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_WEST_0.399 | N/A | 1.488 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_NORTH_0.399 | N/A | 1.488 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_NORTH_0.399 | N/A | 1.488 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_NORTH_0.399 | N/A | 1.488 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.186 | 0.178 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_EAST_0.399 | N/A | 1.488 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_EAST_0.399 | N/A | 1.488 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.196 | 0.187 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_SOUTH_0.399 | N/A | 1.488 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_SOUTH_0.399 | N/A | 1.488 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_SOUTH_0.399 | N/A | 1.488 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.186 | 0.178 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_WEST_0.399 | N/A | 1.488 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_WEST_0.399 | N/A | 1.488 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.196 | 0.187 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_NORTH_0.399 | N/A | 1.488 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_EAST_0.399 | N/A | 1.488 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_SOUTH_0.399 | N/A | 1.488 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_WEST_0.399 | N/A | 1.488 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 1.6646959878E-002 | 9.9186705252E-003 | Pass | Pass | 0.5799377026 | 0.5415915603 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.2243660545 | 0.1516805994 | Pass | Pass | 0.5399910344 | 0.5349250082 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1070087829 | 6.6147010605E-002 | Pass | Pass | 0.5059607766 | 0.4992184416 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.9890728584E-002 | 5.6852761555E-002 | Pass | Pass | 0.5023532190 | 0.5012180396 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 8.6092136432E-002 | 7.9728433560E-002 | Pass | Pass | 0.8173453591 | 0.7323007592 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.2227482779 | 0.2143555983 | Pass | Pass | 0.7249625382 | 0.6826155469 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.7561110596 | 0.6575225475 | Pass | Pass | 0.6222968195 | 0.5769087634 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.7818636424 | 0.7616257418 | Pass | Pass | 0.6484310222 | 0.6355331400 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.7426803816 | 0.7295454540 | Pass | Pass | 0.6564220278 | 0.6435162911 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.7799691093 | 0.7646754515 | Pass | Pass | 0.6526373777 | 0.6420624186 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.6102455499 | 0.5294911901 | Pass | Pass | 0.6257494567 | 0.6116512148 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6424358444 | 0.6206028038 | Pass | Pass | 0.6853391723 | 0.7051827598 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.6010750988 | 0.5858210295 | Pass | Pass | 0.7003872672 | 0.7287578063 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6408130653 | 0.6230125909 | Pass | Pass | 0.6910638009 | 0.7138866443 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5749191948 | 0.5178022760 | Pass | Pass | 0.6668429566 | 0.5822605668 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6068539265 | 0.6020677628 | Pass | Pass | 0.6808096582 | 0.6347601508 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5720294045 | 0.5687704789 | Pass | Pass | 0.6873173000 | 0.6345625387 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6048566487 | 0.5999457542 | Pass | Pass | 0.6803162545 | 0.6344266367 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2348.62 | 187.67 | 0.00 | 2548.19 | 312.13 | 5396.61 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.159 | 0.163 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.181 | 0.186 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.190 | 0.196 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.181 | 0.186 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.190 | 0.196 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.262_SHGC_NORTH_0.399 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.488 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.262_SHGC_EAST_0.399 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.488 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.488 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.262_SHGC_WEST_0.399 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.488 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.262_SHGC_NORTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.262_SHGC_NORTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.262_SHGC_NORTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.262_SHGC_EAST_0.399 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.262_SHGC_EAST_0.399 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.262_SHGC_WEST_0.399 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.262_SHGC_WEST_0.399 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.262_SHGC_NORTH_0.399 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.488 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.262_SHGC_EAST_0.399 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.488 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.488 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.262_SHGC_WEST_0.399 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.488 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 1.488 | 0.400 | 0.440 | |||||||||||||||||
North Total or Average | 195.79 | 1.488 | 0.400 | 0.440 | |||||||||||||||||
Non-North Total or Average | 456.84 | 1.488 | 0.400 | 0.440 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.85 | 0.0000 | Y | 7.74 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.44 | 0.0000 | Y | 4.83 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 28.82 | 0.0000 | Y | 7.48 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.32 | 0.0000 | Y | 4.81 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.76 | 0.0000 | Y | 7.72 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.38 | 0.0000 | Y | 4.82 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 28.75 | 0.0000 | Y | 7.46 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.24 | 0.0000 | Y | 4.80 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.85 | 0.0000 | Y | 7.74 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.44 | 0.0000 | Y | 4.83 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 28.82 | 0.0000 | Y | 7.48 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.32 | 0.0000 | Y | 4.81 |
Interior Lighting Total | 6.6636 | 4982.19 | 33199.39 | 241.32 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 44.84 | 44.84 | 4.75 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.06 | 63.95 | 4.89 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.06 | 52.41 | 46.38 | |
Exterior Lighting Total | 5686.19 | 56.02 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 83917.70 | 67189.15 | 16728.55 | 0.80 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 75264.93 | 60261.26 | 15003.67 | 0.80 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 82166.36 | 65786.93 | 16379.43 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 82473.7 | 2.80 | 9.54 | N/A | N/A | 10.81 | |
PACU_VAV_MID COOLING COIL | 73969.8 | 2.80 | 9.54 | N/A | N/A | 10.81 | |
PACU_VAV_TOP COOLING COIL | 80752.5 | 2.80 | 9.54 | N/A | N/A | 10.81 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 20945.88 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 27073.77 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 49798.59 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 22037.88 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14397.25 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 21939.66 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14342.57 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17436.27 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11503.49 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17371.25 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11460.36 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16719.96 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10998.87 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16629.75 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10953.19 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 58547.19 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 59877.62 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 59016.04 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.07 | 11651.98 | 2298.46 | 1.00 | 1.13 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.55 | 10518.40 | 2313.39 | 1.00 | 1.13 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.96 | 11408.80 | 2298.46 | 1.00 | 1.14 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 82473.69 | 2.80 | 9.54 | 10.81 | 5.7722 | 3.09 | 10.55 | 4.5657 | 3.26 | 11.11 | 3.0596 | 3.43 | 11.69 | 1.2751 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 73969.81 | 2.80 | 9.54 | 10.81 | 5.1770 | 3.09 | 10.55 | 4.0949 | 3.26 | 11.11 | 2.7441 | 3.43 | 11.69 | 1.1436 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 80752.48 | 2.80 | 9.54 | 10.81 | 5.6518 | 3.09 | 10.55 | 4.4704 | 3.26 | 11.11 | 2.9958 | 3.43 | 11.69 | 1.2485 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 39563.37 | 39563.37 | 40.23 | 2.896 | 2.896 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00881 | 19.85 | 0.00700 | 0.425 | 0.00 |
CORE_MID | 29293.41 | 29293.41 | 29.78 | 2.141 | 2.141 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 19.85 | 0.00700 | 0.425 | 0.00 |
CORE_TOP | 28289.21 | 28289.21 | 28.76 | 2.068 | 2.068 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 19.85 | 0.00700 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8255.82 | 8255.82 | 39.82 | 0.609 | 0.609 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 24.00 | 24.00 | 0.00874 | 21.54 | 0.00700 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11262.39 | 11262.39 | 85.80 | 0.831 | 0.831 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00861 | 22.37 | 0.00700 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 17798.11 | 17798.11 | 85.84 | 1.314 | 1.314 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00861 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11743.19 | 11743.19 | 89.47 | 0.867 | 0.867 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00861 | 24.70 | 0.00700 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7098.72 | 7098.72 | 34.24 | 0.524 | 0.524 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 24.00 | 24.00 | 0.00881 | 21.08 | 0.00700 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9247.10 | 9247.10 | 70.45 | 0.682 | 0.682 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00865 | 22.66 | 0.00700 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 14447.80 | 14447.80 | 69.68 | 1.066 | 1.066 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00866 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9700.90 | 9700.90 | 73.91 | 0.716 | 0.716 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.00 | 24.00 | 0.00865 | 23.05 | 0.00700 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7968.64 | 7968.64 | 38.43 | 0.588 | 0.588 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 24.00 | 24.00 | 0.00876 | 21.38 | 0.00700 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 11238.88 | 11238.88 | 85.62 | 0.829 | 0.829 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00862 | 22.08 | 0.00700 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 16904.43 | 16904.43 | 81.53 | 1.248 | 1.248 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00862 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11149.70 | 11149.70 | 84.95 | 0.823 | 0.823 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00862 | 24.70 | 0.00700 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 10501.58 | 10501.58 | 10.68 | 0.457 | 0.457 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
CORE_MID | 19111.35 | 19111.35 | 19.43 | 0.823 | 0.823 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
CORE_TOP | 35027.86 | 35027.86 | 35.61 | 1.515 | 1.515 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 15467.09 | 15467.09 | 74.60 | 0.670 | 0.670 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10103.98 | 10103.98 | 76.98 | 0.438 | 0.438 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15398.29 | 15398.29 | 74.27 | 0.667 | 0.667 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10065.68 | 10065.68 | 76.69 | 0.436 | 0.436 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 12242.86 | 12242.86 | 59.05 | 0.530 | 0.530 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8076.37 | 8076.37 | 61.53 | 0.350 | 0.350 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12197.31 | 12197.31 | 58.83 | 0.528 | 0.528 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8046.16 | 8046.16 | 61.30 | 0.349 | 0.349 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 11741.86 | 11741.86 | 56.63 | 0.509 | 0.509 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 7723.39 | 7723.39 | 58.84 | 0.335 | 0.335 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11678.68 | 11678.68 | 56.33 | 0.506 | 0.506 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 7691.39 | 7691.39 | 58.60 | 0.333 | 0.333 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -41.90 | 0.00006 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.07 | 5.07 | 2.20 | 2.20 | 5.0695 | 2.2037 | 5.0695 | 0.4347 | 0.3000 |
PACU_VAV_MID | 4.55 | 4.55 | 2.51 | 2.51 | 4.5468 | 2.5054 | 4.5468 | 0.5510 | 0.3000 |
PACU_VAV_TOP | 4.96 | 4.96 | 3.73 | 3.73 | 4.9637 | 3.7262 | 4.9637 | 0.7507 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 20945.883 | 20945.883 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 20945.88 | 15035.87 | 0.457302 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 10501.58 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 27073.773 | 27073.773 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27073.77 | 27073.77 | 0.823423 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 19111.35 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 49798.588 | 49798.588 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 49798.59 | 49798.59 | 1.514577 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 35027.86 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 22037.880 | 22037.880 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22037.88 | 22037.88 | 0.670261 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796518 | 50.6949 | 15467.09 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 14397.247 | 14397.247 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14397.25 | 14397.25 | 0.437879 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796449 | 50.6906 | 10103.98 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 21939.658 | 21939.658 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21939.66 | 21939.66 | 0.667274 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796502 | 50.6939 | 15398.29 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 14342.571 | 14342.571 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14342.57 | 14342.57 | 0.436216 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796435 | 50.6897 | 10065.68 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 17436.274 | 17436.274 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17436.27 | 17436.27 | 0.530308 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797593 | 50.7622 | 12242.86 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 11503.491 | 11503.491 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11503.49 | 11503.49 | 0.349868 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797587 | 50.7618 | 8076.37 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 17371.248 | 17371.248 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17371.25 | 17371.25 | 0.528330 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797582 | 50.7615 | 12197.31 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 11460.364 | 11460.364 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11460.36 | 11460.36 | 0.348556 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797576 | 50.7611 | 8046.16 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 16719.961 | 16719.961 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16719.96 | 16719.96 | 0.508522 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796086 | 50.6677 | 11741.86 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 10998.869 | 10998.869 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10998.87 | 10998.87 | 0.334520 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796058 | 50.6660 | 7723.39 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 16629.751 | 16629.751 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16629.75 | 16629.75 | 0.505778 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796061 | 50.6661 | 11678.68 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 10953.194 | 10953.194 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10953.19 | 10953.19 | 0.333131 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796040 | 50.6648 | 7691.39 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 83917.701 | 67189.149 | 5.069468 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 85241.91 | 85241.91 | 5.069468 | 24.64 | 16.41 | 0.00844626 | 10.90 | 10.90 | 0.00844626 | 27.40 | 0.00700714 | 16.15 | 18.8600 | 24.00 | 0.00878123 | 46.5174 | 68611.52 | 0.00 | 86530.41 | 67565.21 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 58547.194 | 58547.194 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 58547.19 | 58547.19 | 1.520840 | -19.52 | -19.52 | 0.00299158 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 62.8666 | 18.23 | 0.00794793 | 60.1018 | 16434.23 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 75264.930 | 60261.262 | 4.546754 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 76452.60 | 76452.60 | 4.546754 | 24.72 | 16.42 | 0.00842654 | 10.89 | 10.89 | 0.00842654 | 27.40 | 0.00700714 | 16.15 | 21.0282 | 24.00 | 0.00880535 | 46.6431 | 61497.46 | 0.00 | 77608.25 | 60598.55 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 59877.625 | 59877.625 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 59877.62 | 59877.62 | 1.364026 | -24.05 | -24.05 | 0.00241449 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 70.0940 | 17.60 | 0.00786425 | 61.8671 | 15600.54 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 82166.363 | 65786.931 | 4.963670 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 83506.90 | 83506.90 | 4.963670 | 24.64 | 16.40 | 0.00843439 | 10.90 | 10.90 | 0.00843439 | 27.30 | 0.00700699 | 16.11 | 19.2620 | 24.00 | 0.00877614 | 46.4905 | 67063.83 | 0.00 | 84724.55 | 66155.14 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 59016.036 | 59016.036 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 59016.04 | 59016.04 | 1.489101 | -20.47 | -20.47 | 0.00287767 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 64.2065 | 15.82 | 0.00794287 | 69.9813 | 16020.31 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 20945.883 | 20945.883 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 20945.88 | 15035.87 | 1.0000 | 0.54210373 | 0.457302 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20945.88 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 10501.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 27073.773 | 27073.773 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27073.77 | 27073.77 | 1.0000 | 0.97611844 | 0.823423 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27073.77 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 19111.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 49798.588 | 49798.588 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 49798.59 | 49798.59 | 1.0000 | 1.79543945 | 1.514577 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 49798.59 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 35027.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 22037.880 | 22037.880 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22037.88 | 22037.88 | 1.0000 | 0.79455426 | 0.670261 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22037.88 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796518 | 21.00 | 0.00796518 | 50.6949 | 15467.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 14397.247 | 14397.247 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14397.25 | 14397.25 | 1.0000 | 0.51907868 | 0.437879 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14397.25 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796449 | 21.00 | 0.00796449 | 50.6906 | 10103.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 21939.658 | 21939.658 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21939.66 | 21939.66 | 1.0000 | 0.79101296 | 0.667274 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21939.66 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796502 | 21.00 | 0.00796502 | 50.6939 | 15398.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 14342.571 | 14342.571 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14342.57 | 14342.57 | 1.0000 | 0.51710739 | 0.436216 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14342.57 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796435 | 21.00 | 0.00796435 | 50.6897 | 10065.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 17436.274 | 17436.274 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17436.27 | 17436.27 | 1.0000 | 0.62864782 | 0.530308 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17436.27 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797593 | 21.00 | 0.00797593 | 50.7622 | 12242.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 11503.491 | 11503.491 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11503.49 | 11503.49 | 1.0000 | 0.41474715 | 0.349868 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11503.49 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797587 | 21.00 | 0.00797587 | 50.7618 | 8076.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 17371.248 | 17371.248 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17371.25 | 17371.25 | 1.0000 | 0.62630340 | 0.528330 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17371.25 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797582 | 21.00 | 0.00797582 | 50.7615 | 12197.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 11460.364 | 11460.364 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11460.36 | 11460.36 | 1.0000 | 0.41319223 | 0.348556 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11460.36 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797576 | 21.00 | 0.00797576 | 50.7611 | 8046.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 16719.961 | 16719.961 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16719.96 | 16719.96 | 1.0000 | 0.60282187 | 0.508522 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16719.96 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796086 | 21.00 | 0.00796086 | 50.6677 | 11741.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10998.869 | 10998.869 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10998.87 | 10998.87 | 1.0000 | 0.39655347 | 0.334520 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10998.87 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796058 | 21.00 | 0.00796058 | 50.6660 | 7723.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 16629.751 | 16629.751 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16629.75 | 16629.75 | 1.0000 | 0.59956945 | 0.505778 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16629.75 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796061 | 21.00 | 0.00796061 | 50.6661 | 11678.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10953.194 | 10953.194 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10953.19 | 10953.19 | 1.0000 | 0.39490672 | 0.333131 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10953.19 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796040 | 21.00 | 0.00796040 | 50.6648 | 7691.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 83917.701 | 67189.149 | 5.069468 | -999.0 | -999.000 | -999.0000 | 1.03720 | 1.00000 | 1020.5412 | 1004.8586 | 1.1854 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.069468 | 6.00954694 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 85241.91 | 85241.91 | 1.0158 | 6.00954694 | 5.069468 | 24.64 | 16.41 | 0.00844626 | 46270.8 | 10.90 | 10.90 | 0.00844626 | 32247.6 | -999.0 | -999.00 | -999.00 | -999.00 | 11651.978 | 73589.93 | 27.40 | 0.00700714 | 16.15 | 0.95610000 | 18.8600 | 24.00 | 0.00878123 | 24.00 | 0.00878123 | 46.5174 | 68611.52 | 0.00 | 86530.41 | 67565.21 | 5.77221527 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 58547.194 | 58547.194 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.069468 | 6.00954694 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 58547.19 | 58547.19 | 1.0000 | 1.80286408 | 1.520840 | -19.52 | -19.52 | 0.00299158 | -12238.8 | 12.80 | 11.46 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 58547.19 | -41.90 | 0.00006450 | -41.90 | 0.95610000 | 62.8666 | 18.38 | 0.00794710 | 18.23 | 0.00794793 | 60.1018 | 16434.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 75264.930 | 60261.262 | 4.546754 | -999.0 | -999.000 | -999.0000 | 1.03092 | 1.00000 | 1020.5045 | 1004.8586 | 1.1854 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.546754 | 5.38990133 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 76452.60 | 76452.60 | 1.0158 | 5.38990133 | 4.546754 | 24.72 | 16.42 | 0.00842654 | 46296.5 | 10.89 | 10.89 | 0.00842654 | 32185.2 | -999.0 | -999.00 | -999.00 | -999.00 | 10518.401 | 65934.20 | 27.40 | 0.00700714 | 16.15 | 0.95610000 | 21.0282 | 24.00 | 0.00880535 | 24.00 | 0.00880535 | 46.6431 | 61497.46 | 0.00 | 77608.25 | 60598.55 | 5.17704097 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 59877.625 | 59877.625 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.546754 | 5.38990133 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 59877.62 | 59877.62 | 1.0000 | 1.61697040 | 1.364026 | -24.05 | -24.05 | 0.00241449 | -18237.6 | 12.80 | 11.46 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 59877.62 | -41.90 | 0.00006450 | -41.90 | 0.95610000 | 70.0940 | 17.78 | 0.00792239 | 17.60 | 0.00786425 | 61.8671 | 15600.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 82166.363 | 65786.931 | 4.963670 | -999.0 | -999.000 | -999.0000 | 1.03810 | 1.00000 | 1020.5191 | 1004.8586 | 1.1854 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.963670 | 5.88412945 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 83506.90 | 83506.90 | 1.0163 | 5.88412945 | 4.963670 | 24.64 | 16.40 | 0.00843439 | 46235.7 | 10.90 | 10.90 | 0.00843439 | 32217.6 | -999.0 | -999.00 | -999.00 | -999.00 | 11408.805 | 72098.10 | 27.30 | 0.00700699 | 16.11 | 0.95610000 | 19.2620 | 24.00 | 0.00877614 | 24.00 | 0.00877614 | 46.4905 | 67063.83 | 0.00 | 84724.55 | 66155.14 | 5.65175082 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 59016.036 | 59016.036 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.963670 | 5.88412945 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 59016.04 | 59016.04 | 1.0000 | 1.76523883 | 1.489101 | -20.47 | -20.47 | 0.00287767 | -13482.4 | 12.80 | 11.46 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 59016.04 | -41.90 | 0.00006450 | -41.90 | 0.95610000 | 64.2065 | 17.97 | 0.00792395 | 15.82 | 0.00794287 | 69.9813 | 16020.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.07 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.55 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.96 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1765.00 | 3645.17 | 833.83 |
CORE_MID | 2678.00 | 4174.00 | 2094.17 |
CORE_TOP | 3216.33 | 4445.00 | 2758.00 |
PERIMETER_TOP_ZN_3 | 3827.83 | 4575.83 | 3243.33 |
PERIMETER_TOP_ZN_2 | 4065.00 | 4137.00 | 3009.83 |
PERIMETER_TOP_ZN_1 | 3889.67 | 4118.67 | 2832.33 |
PERIMETER_TOP_ZN_4 | 3946.33 | 4361.50 | 3128.67 |
PERIMETER_BOT_ZN_3 | 3543.83 | 4692.83 | 3132.17 |
PERIMETER_BOT_ZN_2 | 3907.67 | 4039.33 | 2836.33 |
PERIMETER_BOT_ZN_1 | 3711.83 | 4273.83 | 2775.17 |
PERIMETER_BOT_ZN_4 | 3708.67 | 4348.50 | 2956.17 |
PERIMETER_MID_ZN_3 | 3645.83 | 4387.50 | 2970.50 |
PERIMETER_MID_ZN_2 | 3321.83 | 3412.00 | 2367.67 |
PERIMETER_MID_ZN_1 | 3672.33 | 3873.67 | 2499.33 |
PERIMETER_MID_ZN_4 | 3768.67 | 4158.50 | 2856.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5160.33 | 4957.00 | 3411.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 2.67 | 0.00 | 2.33 | 0.00 |
CORE_MID | 6.33 | 0.00 | 5.17 | 0.00 |
CORE_TOP | 38.67 | 0.00 | 29.67 | 0.00 |
PERIMETER_TOP_ZN_3 | 420.33 | 0.00 | 228.83 | 0.00 |
PERIMETER_TOP_ZN_2 | 248.17 | 10.67 | 65.00 | 10.50 |
PERIMETER_TOP_ZN_1 | 205.17 | 18.00 | 50.50 | 17.67 |
PERIMETER_TOP_ZN_4 | 250.17 | 17.00 | 69.50 | 6.17 |
PERIMETER_BOT_ZN_3 | 260.67 | 0.00 | 203.67 | 0.00 |
PERIMETER_BOT_ZN_2 | 68.17 | 9.17 | 16.17 | 8.83 |
PERIMETER_BOT_ZN_1 | 645.33 | 10.50 | 603.17 | 9.83 |
PERIMETER_BOT_ZN_4 | 70.33 | 7.33 | 16.50 | 1.83 |
PERIMETER_MID_ZN_3 | 146.83 | 0.33 | 85.83 | 0.00 |
PERIMETER_MID_ZN_2 | 82.50 | 14.33 | 20.17 | 13.33 |
PERIMETER_MID_ZN_1 | 61.00 | 19.17 | 12.33 | 18.83 |
PERIMETER_MID_ZN_4 | 83.17 | 17.67 | 20.83 | 6.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1034.00 | 87.17 | 773.17 | 63.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.84 | 52.94 | 2698.04 | 0.834 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.84 | 52.94 | 2698.04 | 0.645 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.84 | 52.94 | 2698.04 | 0.609 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.801 | 0.054 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 1.173 | 0.057 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 1.197 | 0.054 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.993 | 0.056 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.656 | 0.029 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 1.032 | 0.030 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 1.070 | 0.874 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.831 | 0.030 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.768 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 1.064 | 0.051 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 1.213 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.977 | 0.047 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.56 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.30 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 13206201.43 | 0.00 | 13206201.43 | 0.00 | 13206201.43 | 13393058.27 | 5924.54 | 402.83 | 2432.62 | 370.98 |
CORE_MID | 10284804.85 | 0.00 | 10284804.85 | 0.00 | 10284804.85 | 13393058.27 | 5808.46 | 1019.33 | 1932.21 | 385.79 |
CORE_TOP | 9687546.07 | 0.00 | 9687546.07 | 0.00 | 9687546.07 | 13393058.27 | 6344.46 | 744.81 | 1670.73 | 83.17 |
PERIMETER_TOP_ZN_3 | 2681882.24 | 0.00 | 2681882.24 | 370406.43 | 3052288.67 | 2823374.22 | 4375.78 | 48.98 | 4335.24 | 83.17 |
PERIMETER_TOP_ZN_2 | 2472512.04 | 0.00 | 2472512.04 | 246936.13 | 2719448.17 | 1787429.43 | 4861.06 | 645.95 | 3252.99 | 83.17 |
PERIMETER_TOP_ZN_1 | 3984465.54 | 0.00 | 3984465.54 | 370406.43 | 4354871.96 | 2823374.22 | 5028.20 | 680.93 | 3050.87 | 83.17 |
PERIMETER_TOP_ZN_4 | 2110827.09 | 0.00 | 2110827.09 | 246936.13 | 2357763.22 | 1787312.18 | 4888.37 | 681.22 | 3190.41 | 83.17 |
PERIMETER_BOT_ZN_3 | 2207281.99 | 0.00 | 2207281.99 | 196941.88 | 2404223.87 | 2823374.22 | 5437.54 | 293.93 | 3028.53 | 370.98 |
PERIMETER_BOT_ZN_2 | 2182572.92 | 0.00 | 2182572.92 | 131293.80 | 2313866.72 | 1787429.43 | 5249.63 | 406.32 | 3104.04 | 370.98 |
PERIMETER_BOT_ZN_1 | 3591904.66 | 0.00 | 3591904.66 | 3034889.02 | 6626793.69 | 2823374.22 | 4920.78 | 361.01 | 3478.20 | 370.98 |
PERIMETER_BOT_ZN_4 | 1764818.09 | 0.00 | 1764818.09 | 131293.80 | 1896111.89 | 1787312.18 | 5359.64 | 395.60 | 3004.76 | 370.98 |
PERIMETER_MID_ZN_3 | 2577291.64 | 0.00 | 2577291.64 | 308333.93 | 2885625.57 | 2823374.22 | 4948.00 | 965.27 | 2846.73 | 385.75 |
PERIMETER_MID_ZN_2 | 2337035.15 | 0.00 | 2337035.15 | 205554.72 | 2542589.87 | 1601953.02 | 4393.69 | 683.95 | 3682.36 | 1294.70 |
PERIMETER_MID_ZN_1 | 4044658.43 | 0.00 | 4044658.43 | 308333.93 | 4352992.36 | 2823374.22 | 4685.37 | 950.57 | 3124.06 | 385.75 |
PERIMETER_MID_ZN_4 | 2081578.49 | 0.00 | 2081578.49 | 205554.72 | 2287133.20 | 1787312.18 | 4911.78 | 962.92 | 2885.30 | 385.70 |
Total Facility | 65215380.61 | 0.00 | 65215380.61 | 5756880.91 | 70972261.53 | 67658168.57 | 7140.79 | 1633.67 | 4639.76 | 1453.86 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6105 | 0.0000 | 0.6105 | 0.0000 | 0.6105 | 0.4247 | 3145.90 | 402.83 | 2394.26 |
CORE_MID | 0.4731 | 0.0000 | 0.4731 | 0.0000 | 0.4731 | 0.4247 | 3046.38 | 1018.74 | 1877.88 |
CORE_TOP | 0.4471 | 0.0000 | 0.4471 | 0.0000 | 0.4471 | 0.4247 | 3579.74 | 744.81 | 1618.45 |
PERIMETER_TOP_ZN_3 | 0.1240 | 0.0000 | 0.1240 | 0.0083 | 0.1324 | 0.0895 | 1611.45 | 48.98 | 4282.57 |
PERIMETER_TOP_ZN_2 | 0.1148 | 0.0000 | 0.1148 | 0.0056 | 0.1203 | 0.0567 | 2096.56 | 645.95 | 3200.49 |
PERIMETER_TOP_ZN_1 | 0.1850 | 0.0000 | 0.1850 | 0.0083 | 0.1933 | 0.0895 | 2263.48 | 680.93 | 2998.59 |
PERIMETER_TOP_ZN_4 | 0.0972 | 0.0000 | 0.0972 | 0.0056 | 0.1028 | 0.0567 | 2123.79 | 681.22 | 3137.99 |
PERIMETER_BOT_ZN_3 | 0.1017 | 0.0000 | 0.1017 | 0.0044 | 0.1061 | 0.0895 | 2658.90 | 293.93 | 2990.17 |
PERIMETER_BOT_ZN_2 | 0.1010 | 0.0000 | 0.1010 | 0.0030 | 0.1040 | 0.0567 | 2471.46 | 406.18 | 3065.36 |
PERIMETER_BOT_ZN_1 | 0.1664 | 0.0000 | 0.1664 | 0.1371 | 0.3034 | 0.0895 | 2142.21 | 360.97 | 3439.82 |
PERIMETER_BOT_ZN_4 | 0.0813 | 0.0000 | 0.0813 | 0.0030 | 0.0843 | 0.0567 | 2581.17 | 395.58 | 2966.25 |
PERIMETER_MID_ZN_3 | 0.1188 | 0.0000 | 0.1188 | 0.0069 | 0.1257 | 0.0895 | 2186.50 | 964.77 | 2791.73 |
PERIMETER_MID_ZN_2 | 0.1041 | 0.0000 | 0.1041 | 0.0050 | 0.1090 | 0.0567 | 1632.54 | 683.68 | 2717.78 |
PERIMETER_MID_ZN_1 | 0.1874 | 0.0000 | 0.1874 | 0.0069 | 0.1943 | 0.0895 | 1923.45 | 949.99 | 3069.56 |
PERIMETER_MID_ZN_4 | 0.0956 | 0.0000 | 0.0956 | 0.0046 | 0.1002 | 0.0567 | 2149.88 | 962.34 | 2830.78 |
Total Facility | 3.0079 | 0.0000 | 3.0079 | 0.1986 | 3.2065 | 2.1513 | 4346.10 | 1632.56 | 4565.94 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 32254714.21 | 0.00 | 32254714.21 | 22614548.33 | 4181.27 | 2.65 | 4576.08 | 370.96 |
PACU_VAV_MID | 29967794.19 | 0.00 | 29967794.19 | 22429071.92 | 4141.21 | 2.64 | 4616.16 | 384.13 |
PACU_VAV_TOP | 29422321.32 | 0.00 | 29422321.32 | 22614548.33 | 4180.16 | 1.80 | 4578.05 | 83.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.4908 | 0.0000 | 1.4908 | 0.7171 | 1403.29 | 2.65 | 4537.06 |
PACU_VAV_MID | 1.3813 | 0.0000 | 1.3813 | 0.7084 | 1383.99 | 2.39 | 4556.63 |
PACU_VAV_TOP | 1.3605 | 0.0000 | 1.3605 | 0.7171 | 1416.68 | 1.80 | 4524.52 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 723.06 | 2388.10 | 0.00 | 0.00 | 0.00 | 2104.90 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 104.31 | 2487.90 | 0.00 | 0.00 | 0.00 | 2672.58 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 111.98 | 1944.86 | 0.00 | 0.00 | 0.00 | 2734.62 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.3300 | 2.7159 | 0.0000 | 0.0000 | 0.0000 | 1.1504 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.3115 | 2.4950 | 0.0000 | 0.0000 | 0.0000 | 1.0575 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.3128 | 2.6494 | 0.0000 | 0.0000 | 0.0000 | 1.1006 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 949 |
Defaulted Fields | 546 |
Fields with Defaults | 2293 |
Autosized Fields | 153 |
Autosizable Fields | 205 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1756.18 | 12315.29 | 09-APR-17:30 | 275935.85 | 02-JAN-08:10 |
Electricity:Building | 946.76 | 12146.72 | 02-APR-17:20 | 70868.50 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 291.77 | 4006.86 | 01-JAN-00:10 | 23121.21 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 946.76 | 12146.72 | 02-APR-17:20 | 70868.50 | 02-JAN-08:10 |
InteriorLights:Electricity | 241.33 | 905.38 | 02-APR-17:20 | 25003.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 241.33 | 905.38 | 02-APR-17:20 | 25003.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 241.33 | 905.38 | 02-APR-17:20 | 25003.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 241.33 | 905.38 | 02-APR-17:20 | 25003.79 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 32.07 | 413.68 | 02-APR-17:10 | 2475.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.74 | 27.57 | 12-FEB-11:30 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.74 | 27.57 | 12-FEB-11:30 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 20.24 | 261.88 | 02-APR-17:10 | 1567.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.83 | 17.46 | 16-JAN-12:10 | 658.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.83 | 17.46 | 16-JAN-12:10 | 658.76 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 31.81 | 413.67 | 12-MAR-17:10 | 2475.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.48 | 27.57 | 15-JAN-12:00 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.48 | 27.57 | 15-JAN-12:00 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 20.22 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.81 | 17.46 | 05-FEB-12:10 | 658.71 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.81 | 17.46 | 05-FEB-12:10 | 658.71 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 32.05 | 413.68 | 02-APR-17:10 | 2475.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.72 | 27.57 | 12-FEB-11:10 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.72 | 27.57 | 12-FEB-11:10 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 20.23 | 261.88 | 02-APR-17:10 | 1567.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.82 | 17.46 | 16-JAN-12:00 | 658.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.82 | 17.46 | 16-JAN-12:00 | 658.76 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 31.79 | 413.67 | 12-MAR-17:10 | 2475.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.46 | 27.57 | 15-JAN-11:50 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.46 | 27.57 | 15-JAN-11:50 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 20.20 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.80 | 17.46 | 05-FEB-11:50 | 658.71 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.80 | 17.46 | 05-FEB-11:50 | 658.71 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 32.07 | 413.68 | 02-APR-17:10 | 2475.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 7.74 | 27.57 | 12-FEB-11:30 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 7.74 | 27.57 | 12-FEB-11:30 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 20.24 | 261.88 | 02-APR-17:10 | 1567.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.83 | 17.46 | 16-JAN-12:10 | 658.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.83 | 17.46 | 16-JAN-12:10 | 658.76 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 31.81 | 413.67 | 12-MAR-17:10 | 2475.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 7.48 | 27.57 | 15-JAN-12:00 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 7.48 | 27.57 | 15-JAN-12:00 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 20.22 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.81 | 17.46 | 05-FEB-12:10 | 658.71 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.81 | 17.46 | 05-FEB-12:10 | 658.71 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 753.26 | 168.57 | 10-JUN-19:00 | 224918.06 | 02-JAN-07:10 |
ExteriorEquipment:Electricity | 11.70 | 168.34 | 01-JAN-00:10 | 840.16 | 02-JAN-08:30 |
Transformer:ExteriorEquipment:Electricity | 11.70 | 168.34 | 01-JAN-00:10 | 840.16 | 02-JAN-08:30 |
ElectricityPurchased:Facility | 1756.18 | 12315.29 | 09-APR-17:30 | 275935.85 | 02-JAN-08:10 |
ElectricityPurchased:Plant | 1756.18 | 12315.29 | 09-APR-17:30 | 275935.85 | 02-JAN-08:10 |
Cogeneration:ElectricityPurchased | 1756.18 | 12315.29 | 09-APR-17:30 | 275935.85 | 02-JAN-08:10 |
General:Cogeneration:ElectricityPurchased | 1756.18 | 12315.29 | 09-APR-17:30 | 275935.85 | 02-JAN-08:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1756.18 | 12315.29 | 09-APR-17:30 | 275935.85 | 02-JAN-08:10 |
ElectricityNet:Plant | 1756.18 | 12315.29 | 09-APR-17:30 | 275935.85 | 02-JAN-08:10 |
Cogeneration:ElectricityNet | 1756.18 | 12315.29 | 09-APR-17:30 | 275935.85 | 02-JAN-08:10 |
General:Cogeneration:ElectricityNet | 1756.18 | 12315.29 | 09-APR-17:30 | 275935.85 | 02-JAN-08:10 |
Heating:Electricity | 583.98 | 0.00 | 01-JAN-00:40 | 215791.96 | 02-JAN-06:20 |
General:Heating:Electricity | 583.98 | 0.00 | 01-JAN-00:40 | 215791.96 | 02-JAN-06:20 |
Fans:Electricity | 84.84 | 0.00 | 01-JAN-00:40 | 26564.64 | 12-JUL-15:10 |
General:Fans:Electricity | 84.84 | 0.00 | 01-JAN-00:40 | 26564.64 | 12-JUL-15:10 |
ExteriorLights:Electricity | 56.02 | 0.00 | 01-JAN-11:20 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 56.02 | 0.00 | 01-JAN-11:20 | 5686.19 | 01-JAN-06:10 |
HeatRecovery:Electricity | 21.66 | 0.00 | 01-JAN-00:10 | 2208.01 | 02-JAN-08:30 |
General:HeatRecovery:Electricity | 21.66 | 0.00 | 01-JAN-00:10 | 2208.01 | 02-JAN-08:30 |
Cooling:Electricity | 51.08 | 0.00 | 01-JAN-00:10 | 46348.45 | 30-JUN-14:30 |
General:Cooling:Electricity | 51.08 | 0.00 | 01-JAN-00:10 | 46348.45 | 30-JUN-14:30 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-22:10 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-22:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-22:10 |
WIRED_LTG_ELECTRICITY | 6.78 | 0.00 | 01-JAN-00:10 | 702.61 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 408.83 | 1886.44 | 09-JAN-05:10 | 223852.66 | 12-JAN-08:20 |
NaturalGas:HVAC | 259.56 | 0.00 | 01-JAN-00:40 | 214388.15 | 12-JAN-08:10 |
Heating:NaturalGas | 259.56 | 0.00 | 01-JAN-00:40 | 214388.15 | 12-JAN-08:10 |
General:Heating:NaturalGas | 259.56 | 0.00 | 01-JAN-00:40 | 214388.15 | 12-JAN-08:10 |
NaturalGas:Plant | 149.28 | 1886.44 | 07-JAN-05:10 | 14121.04 | 21-FEB-12:30 |
WaterSystems:NaturalGas | 149.28 | 1886.44 | 07-JAN-05:10 | 14121.04 | 21-FEB-12:30 |
Water Heater:WaterSystems:NaturalGas | 149.28 | 1886.44 | 07-JAN-05:10 | 14121.04 | 21-FEB-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2780.57 | 0.00 | 01-JAN-00:40 | 559513.66 | 27-FEB-07:10 |
EnergyTransfer:Building | 1237.97 | 0.00 | 01-JAN-00:40 | 217899.55 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 178.40 | 0.00 | 01-JAN-00:40 | 26543.77 | 24-JUL-08:00 |
Heating:EnergyTransfer | 549.20 | 0.00 | 01-JAN-00:40 | 217899.55 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 1.12 | 0.00 | 01-JAN-00:20 | 16409.62 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 549.20 | 0.00 | 01-JAN-00:40 | 217899.55 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 1.12 | 0.00 | 01-JAN-00:20 | 16409.62 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 688.78 | 0.00 | 01-JAN-00:40 | 151778.46 | 12-JUL-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 177.28 | 0.00 | 01-JAN-00:40 | 26543.77 | 24-JUL-08:00 |
General:Cooling:EnergyTransfer | 688.78 | 0.00 | 01-JAN-00:40 | 151778.46 | 12-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 177.28 | 0.00 | 01-JAN-00:40 | 26543.77 | 24-JUL-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 76.50 | 0.00 | 01-JAN-00:40 | 18787.34 | 27-FEB-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 62.13 | 0.00 | 01-JAN-00:40 | 18787.34 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 62.13 | 0.00 | 01-JAN-00:40 | 18787.34 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 14.37 | 0.00 | 01-JAN-00:10 | 7881.34 | 21-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 14.37 | 0.00 | 01-JAN-00:10 | 7881.34 | 21-JUL-14:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 34.29 | 0.00 | 01-JAN-00:40 | 11331.16 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 23.94 | 0.00 | 01-JAN-00:40 | 11331.16 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 23.94 | 0.00 | 01-JAN-00:40 | 11331.16 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.35 | 0.00 | 01-JAN-00:10 | 4473.57 | 24-JUL-06:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.35 | 0.00 | 01-JAN-00:10 | 4473.57 | 24-JUL-06:20 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 33.20 | 0.00 | 01-JAN-00:40 | 10474.66 | 02-JAN-08:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 18.60 | 0.00 | 01-JAN-00:40 | 10474.66 | 02-JAN-08:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 18.60 | 0.00 | 01-JAN-00:40 | 10474.66 | 02-JAN-08:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 14.59 | 0.00 | 01-JAN-00:10 | 4816.29 | 12-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 14.59 | 0.00 | 01-JAN-00:10 | 4816.29 | 12-JUL-16:00 |
EnergyTransfer:Zone:CORE_MID | 118.75 | 0.00 | 01-JAN-00:40 | 23603.99 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 10.35 | 0.00 | 01-JAN-00:40 | 23603.99 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 10.35 | 0.00 | 01-JAN-00:40 | 23603.99 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 108.40 | 0.00 | 01-JAN-00:20 | 18365.68 | 24-JUL-07:30 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 108.40 | 0.00 | 01-JAN-00:20 | 18365.68 | 24-JUL-07:30 |
EnergyTransfer:Zone:CORE_TOP | 127.97 | 0.00 | 01-JAN-00:40 | 27523.74 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 39.58 | 0.00 | 01-JAN-00:40 | 27523.74 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 39.58 | 0.00 | 01-JAN-00:40 | 27523.74 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 88.39 | 0.00 | 01-JAN-00:20 | 17898.77 | 24-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 88.39 | 0.00 | 01-JAN-00:20 | 17898.77 | 24-JUL-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 68.43 | 0.00 | 01-JAN-00:40 | 9782.63 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 49.68 | 0.00 | 01-JAN-00:40 | 9782.63 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 49.68 | 0.00 | 01-JAN-00:40 | 9782.63 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 18.75 | 0.00 | 01-JAN-00:10 | 6259.25 | 11-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 18.75 | 0.00 | 01-JAN-00:10 | 6259.25 | 11-JUL-06:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 52.89 | 0.00 | 01-JAN-00:40 | 10494.24 | 07-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 30.48 | 0.00 | 01-JAN-00:40 | 10289.75 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 30.48 | 0.00 | 01-JAN-00:40 | 10289.75 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 22.41 | 0.00 | 01-JAN-00:10 | 10494.24 | 07-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 22.41 | 0.00 | 01-JAN-00:10 | 10494.24 | 07-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 78.99 | 0.00 | 01-JAN-00:40 | 16128.32 | 30-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 40.80 | 0.00 | 01-JAN-00:40 | 16128.32 | 30-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 40.80 | 0.00 | 01-JAN-00:40 | 16128.32 | 30-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 38.19 | 0.00 | 01-JAN-00:10 | 14973.20 | 10-AUG-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 38.19 | 0.00 | 01-JAN-00:10 | 14973.20 | 10-AUG-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 49.44 | 0.00 | 01-JAN-00:40 | 10643.20 | 30-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 32.21 | 0.00 | 01-JAN-00:40 | 10643.20 | 30-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 32.21 | 0.00 | 01-JAN-00:40 | 10643.20 | 30-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 17.23 | 0.00 | 01-JAN-00:10 | 8420.41 | 11-JUL-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 17.23 | 0.00 | 01-JAN-00:10 | 8420.41 | 11-JUL-17:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 50.14 | 0.00 | 01-JAN-00:40 | 7495.00 | 27-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 34.65 | 0.00 | 01-JAN-00:40 | 7495.00 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 34.65 | 0.00 | 01-JAN-00:40 | 7495.00 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 15.49 | 0.00 | 01-JAN-00:10 | 5185.06 | 11-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 15.49 | 0.00 | 01-JAN-00:10 | 5185.06 | 11-JUL-06:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 41.54 | 0.00 | 01-JAN-00:40 | 8465.59 | 27-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 21.23 | 0.00 | 01-JAN-00:40 | 8465.59 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 21.23 | 0.00 | 01-JAN-00:40 | 8465.59 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 20.31 | 0.00 | 01-JAN-00:10 | 7969.43 | 07-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 20.31 | 0.00 | 01-JAN-00:10 | 7969.43 | 07-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 96.24 | 0.00 | 01-JAN-00:40 | 22631.77 | 12-JAN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 71.74 | 0.00 | 01-JAN-00:40 | 22631.77 | 12-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 71.74 | 0.00 | 01-JAN-00:40 | 22631.77 | 12-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 24.50 | 0.00 | 01-JAN-00:20 | 11632.70 | 11-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 24.50 | 0.00 | 01-JAN-00:20 | 11632.70 | 11-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 37.38 | 0.00 | 01-JAN-00:40 | 8757.61 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 22.76 | 0.00 | 01-JAN-00:40 | 8757.61 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 22.76 | 0.00 | 01-JAN-00:40 | 8757.61 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 14.62 | 0.00 | 01-JAN-00:20 | 6661.13 | 31-JUL-18:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 14.62 | 0.00 | 01-JAN-00:20 | 6661.13 | 31-JUL-18:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 50.01 | 0.00 | 01-JAN-00:40 | 8394.79 | 30-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 29.46 | 0.00 | 01-JAN-00:40 | 8394.79 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 29.46 | 0.00 | 01-JAN-00:40 | 8394.79 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 20.54 | 0.00 | 01-JAN-00:10 | 6725.03 | 11-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 20.54 | 0.00 | 01-JAN-00:10 | 6725.03 | 11-JUL-06:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 41.26 | 0.00 | 01-JAN-00:40 | 10419.01 | 07-JUL-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 18.14 | 0.00 | 01-JAN-00:40 | 8814.60 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 18.14 | 0.00 | 01-JAN-00:40 | 8814.60 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 23.12 | 0.00 | 01-JAN-00:20 | 10419.01 | 07-JUL-08:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 23.12 | 0.00 | 01-JAN-00:20 | 10419.01 | 07-JUL-08:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 64.71 | 0.00 | 01-JAN-00:40 | 14652.19 | 10-AUG-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 23.18 | 0.00 | 01-JAN-00:40 | 13328.07 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 23.18 | 0.00 | 01-JAN-00:40 | 13328.07 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 41.52 | 0.00 | 01-JAN-00:20 | 14652.19 | 10-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 41.52 | 0.00 | 01-JAN-00:20 | 14652.19 | 10-AUG-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 37.82 | 0.00 | 01-JAN-00:40 | 8836.43 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 19.13 | 0.00 | 01-JAN-00:40 | 8836.43 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 19.13 | 0.00 | 01-JAN-00:40 | 8836.43 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 18.69 | 0.00 | 01-JAN-00:20 | 8118.51 | 11-JUL-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 18.69 | 0.00 | 01-JAN-00:20 | 8118.51 | 11-JUL-17:40 |
PlantLoopHeatingDemand:Facility | 64.03 | 0.00 | 01-JAN-00:10 | 7551.87 | 03-JAN-12:30 |
PlantLoopHeatingDemand:Plant | 64.03 | 0.00 | 01-JAN-00:10 | 7551.87 | 03-JAN-12:30 |
WaterSystems:PlantLoopHeatingDemand | 64.03 | 0.00 | 01-JAN-00:10 | 7551.87 | 03-JAN-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 64.03 | 0.00 | 01-JAN-00:10 | 7551.87 | 03-JAN-12:30 |
EnergyTransfer:HVAC | 1478.57 | 0.00 | 01-JAN-00:40 | 350166.26 | 27-FEB-07:10 |
HeatingCoils:EnergyTransfer | 791.62 | 0.00 | 01-JAN-00:40 | 350166.26 | 27-FEB-07:10 |
HeatRecoveryForHeating:EnergyTransfer | 477.62 | 0.00 | 01-JAN-00:10 | 107004.01 | 07-NOV-07:40 |
HeatRecoveryForCooling:EnergyTransfer | 0.19 | 0.00 | 01-JAN-00:10 | 13215.16 | 29-JUL-16:00 |
CoolingCoils:EnergyTransfer | 209.14 | 0.00 | 01-JAN-00:10 | 191632.23 | 30-JUN-12:30 |
EnergyTransfer:Plant | 64.03 | 0.00 | 01-JAN-00:10 | 7551.87 | 03-JAN-12:30 |
WaterSystems:EnergyTransfer | 64.03 | 0.00 | 01-JAN-00:10 | 7551.87 | 03-JAN-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 64.03 | 0.00 | 01-JAN-00:10 | 7551.87 | 03-JAN-12:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 1.120 | -177.279 | 0.000 | 0.000 | 34.050 | 55.599 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -149.658 |
CORE_MID | 0.000 | 0.000 | 10.348 | -108.399 | 0.000 | 0.000 | 35.646 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -108.619 |
CORE_TOP | 0.000 | 0.000 | 39.578 | -88.395 | 0.000 | 0.000 | 36.217 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -158.425 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 49.683 | -18.751 | 0.000 | 0.000 | 7.755 | 7.742 | 24.333 | 14.798 | 0.000 | 0.005 | 0.001 | 0.000 | -48.302 | 0.000 | -8.409 | -28.854 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 30.480 | -22.411 | 0.000 | 0.000 | 4.831 | 4.834 | 15.404 | 33.673 | 0.000 | 0.003 | 0.000 | 0.000 | -30.814 | 0.000 | -5.688 | -30.312 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 40.799 | -38.188 | 0.000 | 0.000 | 7.597 | 7.475 | 24.332 | 66.224 | 0.000 | 0.004 | 0.001 | 0.000 | -44.225 | 0.000 | -8.655 | -55.363 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 32.209 | -17.232 | 0.000 | 0.000 | 4.885 | 4.814 | 15.403 | 23.449 | 0.000 | 0.003 | 0.000 | 0.000 | -31.628 | 0.000 | -5.712 | -26.191 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 34.649 | -15.487 | 0.000 | 0.000 | 7.747 | 7.719 | 24.333 | 15.060 | 0.000 | 0.003 | 0.001 | 0.000 | -49.010 | 0.000 | -4.557 | -20.456 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 21.232 | -20.310 | 0.000 | 0.000 | 4.813 | 4.823 | 15.404 | 33.772 | 0.000 | 0.002 | 0.000 | 0.000 | -31.479 | 0.000 | -3.124 | -25.133 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 71.741 | -24.503 | 0.000 | 0.000 | 7.870 | 7.457 | 24.332 | 66.749 | 0.000 | 0.082 | 0.001 | 0.000 | -44.772 | 0.000 | -75.366 | -33.592 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 22.757 | -14.623 | 0.000 | 0.000 | 4.860 | 4.801 | 15.403 | 23.606 | 0.000 | 0.002 | 0.000 | 0.000 | -32.273 | 0.000 | -3.121 | -21.413 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 29.464 | -20.544 | 0.000 | 0.000 | 7.680 | 7.742 | 24.333 | 14.540 | 0.000 | 0.004 | 0.001 | 0.000 | -49.776 | 0.000 | -7.241 | -6.203 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 18.136 | -23.124 | 0.000 | 0.000 | 3.545 | 4.834 | 15.404 | 33.435 | 0.000 | 0.002 | 0.000 | 0.000 | -31.684 | 0.000 | -4.894 | -15.654 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 23.185 | -41.521 | 0.000 | 0.000 | 7.527 | 7.475 | 24.332 | 65.923 | 0.000 | 0.004 | 0.001 | 0.000 | -45.631 | 0.000 | -7.452 | -33.841 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 19.135 | -18.688 | 0.000 | 0.000 | 4.843 | 4.814 | 15.403 | 23.307 | 0.000 | 0.002 | 0.000 | 0.000 | -32.582 | 0.000 | -4.910 | -11.324 |
TOPFLOOR_PLENUM | 62.134 | -14.370 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -12.746 | -35.021 |
MIDFLOOR_PLENUM | 23.940 | -10.354 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.004 | 0.000 | 0.000 | 0.000 | 0.000 | -12.266 | -1.324 |
FIRSTFLOOR_PLENUM | 18.603 | -14.595 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.003 | 5.760 | 0.000 | 0.000 | 0.000 | -9.771 | -0.000 |
Total Facility | 104.677 | -39.318 | 444.519 | -649.455 | 0.000 | 0.000 | 179.867 | 241.325 | 705.434 | 414.537 | 0.000 | 0.124 | 5.766 | 0.000 | -472.175 | 0.000 | -173.910 | -761.384 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 14-AUG-05:12 | 0.00 | 0.00 | 0.00 | -42527.32 | 0.00 | 0.00 | 318.16 | 548.43 | 4989.51 | 0.00 | 0.00 | 0.00 | 36671.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 24-JUL-06:03 | 0.00 | 0.00 | 0.00 | -31705.48 | 0.00 | 0.00 | 685.35 | 1645.36 | 3025.92 | 0.00 | 0.00 | 0.00 | 26348.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-05:12 | 0.00 | 0.00 | 0.00 | -29487.41 | 0.00 | 0.00 | 333.29 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 25579.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 11-JUL-05:12 | 0.00 | 0.00 | 0.00 | -10390.15 | 0.00 | 0.00 | 63.82 | 55.15 | 637.89 | 7875.79 | 0.00 | 0.00 | 1820.17 | 0.00 | -0.00 | 0.00 | -62.67 | 0.00 |
PERIMETER_TOP_ZN_2 | 14-MAY-09:41 | 0.00 | 0.00 | 0.00 | -15417.34 | 0.00 | 0.00 | 13.91 | 17.46 | 302.86 | 10350.11 | 0.00 | 0.00 | 4981.32 | 0.00 | -0.00 | 0.00 | -248.31 | 0.00 |
PERIMETER_TOP_ZN_1 | 14-MAY-12:22 | 0.00 | 0.00 | 0.00 | -23655.91 | 0.00 | 0.00 | 22.36 | 27.57 | 478.41 | 17320.54 | 0.00 | 0.00 | 6147.18 | 0.00 | -0.00 | 0.00 | -340.16 | 0.00 |
PERIMETER_TOP_ZN_4 | 14-MAY-18:22 | 0.00 | 0.00 | 0.00 | -14987.56 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 10141.48 | 0.00 | 0.00 | 4999.32 | 0.00 | -0.00 | 0.00 | -415.11 | 0.00 |
PERIMETER_BOT_ZN_3 | 11-JUL-05:14 | 0.00 | 0.00 | 0.00 | -8441.11 | 0.00 | 0.00 | 65.11 | 55.15 | 637.89 | 7930.93 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -31.08 | -216.88 |
PERIMETER_BOT_ZN_2 | 23-JUL-10:01 | 0.00 | 0.00 | 0.00 | -11723.09 | 0.00 | 0.00 | 15.29 | 17.46 | 302.86 | 10282.05 | 0.00 | 0.00 | 1137.15 | 0.00 | -0.00 | 0.00 | -31.72 | 0.00 |
PERIMETER_BOT_ZN_1 | 23-JUL-13:21 | 0.00 | 0.00 | 0.00 | -18610.47 | 0.00 | 0.00 | 23.61 | 27.57 | 478.41 | 17442.01 | 0.00 | 0.00 | 662.72 | 0.00 | -0.00 | 0.00 | -23.87 | 0.00 |
PERIMETER_BOT_ZN_4 | 09-JUL-19:42 | 0.00 | 0.00 | 0.00 | -8438.79 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 6917.34 | 0.00 | 0.00 | 1352.38 | 0.00 | -0.00 | 0.00 | -92.80 | 0.00 |
PERIMETER_MID_ZN_3 | 11-JUL-05:12 | 0.00 | 0.00 | 0.00 | -9383.99 | 0.00 | 0.00 | 62.58 | 55.15 | 637.89 | 7854.14 | 0.00 | 0.00 | 828.10 | 0.00 | -0.00 | 0.00 | -53.86 | 0.00 |
PERIMETER_MID_ZN_2 | 09-JUL-07:02 | 0.00 | 0.00 | 0.00 | -14523.52 | 0.00 | 0.00 | 15.02 | 17.46 | 302.86 | 10075.30 | 0.00 | 0.00 | 4290.68 | 0.00 | -0.00 | 0.00 | -177.79 | 0.00 |
PERIMETER_MID_ZN_1 | 27-AUG-13:11 | 0.00 | 0.00 | 0.00 | -23586.70 | 0.00 | 0.00 | 21.35 | 27.57 | 478.41 | 17590.73 | 0.00 | 0.00 | 5615.95 | 0.00 | -0.00 | 0.00 | -147.32 | 0.00 |
PERIMETER_MID_ZN_4 | 27-AUG-17:52 | 0.00 | 0.00 | 0.00 | -14556.85 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 8910.08 | 0.00 | 0.00 | 5590.42 | 0.00 | -0.00 | 0.00 | -205.52 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-14:30 | 0.00 | -7882.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.35 | 7871.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 24-JUL-06:13 | 0.00 | -5984.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6044.81 | 0.00 | -0.00 | 0.00 | -60.06 | 0.00 |
FIRSTFLOOR_PLENUM | 24-JUL-06:13 | 0.00 | -6387.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6433.75 | 0.00 | -0.00 | 0.00 | -46.18 | 0.00 |
Total Facility | 24-JUL-06:02 | 0.00 | -6895.85 | 0.00 | -189163.04 | 0.00 | 0.00 | 3500.40 | 6557.23 | 21098.80 | 28553.12 | 0.00 | 0.00 | 145109.86 | 0.00 | 0.00 | 0.00 | -8760.52 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 19962.28 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 4405.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24579.65 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 26855.37 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29509.16 |
CORE_TOP | 01-JAN-02:42 | 0.00 | 0.00 | 30440.29 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 1831.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -32483.56 |
PERIMETER_TOP_ZN_3 | 30-JAN-06:01 | 0.00 | 0.00 | 10676.47 | 0.00 | 0.00 | 0.00 | 121.00 | 44.64 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3466.44 | 0.00 | -363.59 | -7649.95 |
PERIMETER_TOP_ZN_2 | 29-JAN-09:22 | 0.00 | 0.00 | 12949.46 | 0.00 | 0.00 | 0.00 | 38.51 | 36.60 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2318.79 | 0.00 | -1087.10 | -9921.54 |
PERIMETER_TOP_ZN_1 | 29-JAN-09:22 | 0.00 | 0.00 | 20332.12 | 0.00 | 0.00 | 0.00 | 60.63 | 57.81 | 478.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3415.31 | 0.00 | -1637.55 | -15876.11 |
PERIMETER_TOP_ZN_4 | 29-JAN-09:22 | 0.00 | 0.00 | 13456.09 | 0.00 | 0.00 | 0.00 | 38.49 | 36.59 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2271.39 | 0.00 | -1089.55 | -10473.09 |
PERIMETER_BOT_ZN_3 | 01-JAN-06:42 | 0.00 | 0.00 | 8165.60 | 0.00 | 0.00 | 0.00 | 59.48 | 57.81 | 478.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2576.02 | 0.00 | -449.85 | -5735.43 |
PERIMETER_BOT_ZN_2 | 27-FEB-04:22 | 0.00 | 0.00 | 10279.31 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2729.72 | 0.00 | 0.00 | -7903.74 |
PERIMETER_BOT_ZN_1 | 12-JAN-08:00 | 0.00 | 0.00 | 22631.74 | 0.00 | 0.00 | 0.00 | 267.84 | 346.86 | 637.88 | 0.00 | 0.00 | 0.00 | 23375.23 | 0.00 | -3913.41 | 0.00 | -43346.13 | 0.00 |
PERIMETER_BOT_ZN_4 | 27-FEB-04:22 | 0.00 | 0.00 | 10750.36 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2731.23 | 0.00 | 0.00 | -8373.28 |
PERIMETER_MID_ZN_3 | 01-JAN-06:42 | 0.00 | 0.00 | 8998.50 | 0.00 | 0.00 | 0.00 | 59.34 | 57.81 | 478.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2615.73 | 0.00 | -708.55 | -6269.79 |
PERIMETER_MID_ZN_2 | 30-JAN-05:11 | 0.00 | 0.00 | 11419.54 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2297.48 | 0.00 | -781.87 | -8694.35 |
PERIMETER_MID_ZN_1 | 30-JAN-05:11 | 0.00 | 0.00 | 17221.60 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3453.52 | 0.00 | -1174.40 | -13153.11 |
PERIMETER_MID_ZN_4 | 30-JAN-05:11 | 0.00 | 0.00 | 11379.21 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2339.45 | 0.00 | -781.53 | -8612.37 |
TOPFLOOR_PLENUM | 12-JAN-06:13 | 19765.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19765.13 |
MIDFLOOR_PLENUM | 02-JAN-07:04 | 12256.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -277.39 | -11979.29 |
FIRSTFLOOR_PLENUM | 02-JAN-08:13 | 10774.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -248.97 | -10525.79 |
Total Facility | 02-JAN-05:01 | 21667.94 | 0.00 | 217212.27 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.56 | 14333.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -25643.55 | 0.00 | -4650.72 | -223992.41 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.8906 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0695 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.6295 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.5468 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.7495 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9637 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.9453 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0777 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.8147 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0750 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.8747 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0880 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8957 | 2.8957 | 0.6370 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1415 | 2.1415 | 0.6360 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0679 | 2.0679 | 0.6369 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6703 | 0.6703 | 0.1475 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8312 | 0.8312 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3135 | 1.3135 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8667 | 0.8667 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5303 | 0.5303 | 0.1358 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6824 | 0.6824 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0663 | 1.0663 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7159 | 0.7159 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5881 | 0.5881 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8294 | 0.8294 | 0.0854 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2476 | 1.2476 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8229 | 0.8229 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.8906 | 5.0695 | 5.8906 | 1.0777 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.6295 | 4.5468 | 5.6295 | 1.0750 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.7495 | 4.9637 | 5.7495 | 1.0880 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4478 | 1.4478 | 0.6370 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0707 | 1.0707 | 0.6360 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0339 | 1.0339 | 0.6369 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3351 | 0.3351 | 0.1475 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4156 | 0.4156 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6568 | 0.6568 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4333 | 0.4333 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2652 | 0.2652 | 0.1358 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3412 | 0.3412 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5331 | 0.5331 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3580 | 0.3580 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2940 | 0.2940 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4147 | 0.4147 | 0.0854 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6238 | 0.6238 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4114 | 0.4114 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.9453 | 1.0777 | 1.0777 | 1.0777 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.8147 | 1.0750 | 1.0750 | 1.0750 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.8747 | 1.0880 | 1.0880 | 1.0880 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 773.17 |
Number of hours cooling loads not met | 63.67 |
Number of hours not met | 836.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 583.98 | 215791.96 | 259.56 | 214388.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 51.08 | 46348.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 241.33 | 25003.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 56.02 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.70 | 840.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 84.84 | 26564.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 21.66 | 2208.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 149.28 | 14121.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1756.18 |
Natural Gas | 0.00 | 408.83 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 2165.02 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 48.44 |
Space Heating | 117.21 |
Space Cooling | 10.25 |
Fans (All) | 17.03 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 352.49 |
Subtotal | 352.49 |
Natural Gas [MJ/m2] | |
Space Heating | 52.10 |
Service Water Heating | 29.96 |
Miscellaneous (All) | 82.06 |
Subtotal | 82.06 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.15 |
Space Heating | 38.96 |
Space Cooling | 2.36 |
Fans (All) | 3.92 |
Service Water Heating | 6.89 |
Receptacle Equipment | 32.58 |
Miscellaneous | 4.14 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 815. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8747.67 | 12.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8744.67 | 15.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8746.17 | 13.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8750.33 | 9.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8745.67 | 14.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8740.17 | 19.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8740.00 | 20.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8747.33 | 12.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8754.17 | 5.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8740.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 20.00 | 0.00 | 0.00 | 0.00 |
Average | 8752.88 | 7.12 | 0.00 | 0.00 | 0.00 |
Sum | 157551.83 | 128.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8710.67 | 49.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8745.50 | 14.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8748.67 | 11.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8753.00 | 7.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8746.83 | 13.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8749.67 | 10.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8741.00 | 19.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8749.67 | 10.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8756.17 | 3.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8756.67 | 3.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8710.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 49.33 | 0.00 | 0.00 | 0.00 |
Average | 8751.73 | 8.27 | 0.00 | 0.00 | 0.00 |
Sum | 157531.17 | 148.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128274.67 | 29.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128299.00 | 5.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 29.33 | 0.00 | 0.00 | 0.00 |
Average | 34141.43 | 1.91 | 0.00 | 0.00 | 0.00 |
Sum | 614545.67 | 34.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.703953E+10 | 6178.88 | 27-JAN-17:00 | -12.2 | -12.5 | 0.164094E+10 | 2490.37 | 27-JAN-14:09 | -12.2 | -12.5 |
February | 0.748474E+10 | 7749.18 | 10-FEB-17:00 | -0.6 | -2.2 | 0.157587E+10 | 2606.63 | 17-FEB-14:20 | -13.0 | -14.1 |
March | 0.949293E+10 | 12277.47 | 24-MAR-07:30 | -9.4 | -9.9 | 0.202808E+10 | 2608.29 | 24-MAR-09:20 | -8.7 | -9.5 |
April | 0.136232E+11 | 23018.27 | 28-APR-05:03 | -1.5 | -2.2 | 0.189184E+10 | 2608.48 | 07-APR-09:20 | -1.5 | -2.2 |
May | 0.222046E+11 | 38432.10 | 15-MAY-06:02 | 8.07 | 2.53 | 0.207575E+10 | 2606.67 | 19-MAY-13:39 | 13.87 | 8.18 |
June | 0.252434E+11 | 41711.17 | 05-JUN-05:12 | 10.77 | 8.82 | 0.207243E+10 | 2606.70 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.246621E+11 | 42488.27 | 17-JUL-05:12 | 8.30 | 8.19 | 0.192687E+10 | 2607.04 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.252182E+11 | 42533.23 | 14-AUG-05:12 | 11.10 | 10.22 | 0.216141E+10 | 2606.66 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.174388E+11 | 36670.18 | 01-SEP-06:02 | 6.70 | 5.86 | 0.191368E+10 | 2608.54 | 29-SEP-09:20 | -3.9 | -4.4 |
October | 0.104780E+11 | 16449.60 | 03-OCT-07:06 | 0.00 | -0.3 | 0.193304E+10 | 2608.28 | 02-OCT-09:20 | 0.00 | -0.3 |
November | 0.723282E+10 | 7397.72 | 03-NOV-16:00 | -11.1 | -11.5 | 0.172691E+10 | 2604.99 | 03-NOV-13:09 | -11.1 | -11.5 |
December | 0.716063E+10 | 5959.73 | 22-DEC-17:00 | -21.7 | -22.0 | 0.159723E+10 | 2422.22 | 22-DEC-14:09 | -21.7 | -22.0 |
Annual Sum or Average | 0.177279E+12 | 0.225440E+11 | ||||||||
Minimum of Months | 0.703953E+10 | 5959.73 | -21.7 | -22.0 | 0.157587E+10 | 2422.22 | -21.7 | -22.0 | ||
Maximum of Months | 0.252434E+11 | 42533.23 | 11.10 | 10.22 | 0.216141E+10 | 2608.54 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 3343285.26 | 542.42 | 22-MAR-17:15 | 4.67 | 1.29 | 0.00 | 0.00 | 01-MAR-00:10 | 4.67 | 1.29 |
April | 0.572667E+09 | 3850.16 | 21-APR-15:30 | 14.15 | 5.54 | 0.00 | 0.00 | 01-APR-00:10 | 14.15 | 5.54 |
May | 0.232943E+10 | 6746.65 | 31-MAY-14:40 | 20.73 | 10.55 | 0.00 | 0.00 | 01-MAY-00:10 | 20.73 | 10.55 |
June | 0.430101E+10 | 7813.34 | 29-JUN-14:50 | 26.02 | 16.10 | 0.00 | 0.00 | 01-JUN-00:10 | 26.02 | 16.10 |
July | 0.422664E+10 | 7881.34 | 21-JUL-14:30 | 26.95 | 14.56 | 0.00 | 0.00 | 01-JUL-00:10 | 26.95 | 14.56 |
August | 0.262758E+10 | 6693.81 | 10-AUG-15:20 | 22.40 | 12.08 | 0.00 | 0.00 | 01-AUG-00:10 | 22.40 | 12.08 |
September | 0.307918E+09 | 2696.75 | 07-SEP-15:30 | 16.65 | 8.91 | 0.00 | 0.00 | 01-SEP-00:10 | 16.65 | 8.91 |
October | 1480980.11 | 349.10 | 03-OCT-16:40 | 11.30 | 5.55 | 0.00 | 0.00 | 01-OCT-00:10 | 11.30 | 5.55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.143701E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.00 | 0.00 | -25.8 | -26.0 | ||
Maximum of Months | 0.430101E+10 | 7881.34 | 26.95 | 16.10 | 0.00 | 0.00 | 26.95 | 16.10 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6817681.31 | 3129.00 | 11-JAN-05:01 | -27.4 | -27.5 | 0.00 | 0.00 | 01-JAN-00:10 | -27.4 | -27.5 |
February | 4499571.01 | 2944.33 | 18-FEB-05:01 | -23.9 | -24.3 | 0.00 | 0.00 | 01-FEB-00:10 | -23.9 | -24.3 |
March | 5869178.69 | 3340.99 | 03-MAR-05:01 | -25.6 | -26.1 | 0.00 | 0.00 | 01-MAR-00:10 | -25.6 | -26.1 |
April | 0.178760E+09 | 2155.80 | 01-APR-05:01 | -10.5 | -12.1 | 0.00 | 0.00 | 01-APR-00:10 | -10.5 | -12.1 |
May | 0.146348E+10 | 3292.50 | 31-MAY-15:50 | 22.02 | 10.78 | 0.00 | 0.00 | 01-MAY-00:10 | 22.02 | 10.78 |
June | 0.323183E+10 | 4273.61 | 22-JUN-06:13 | 15.57 | 11.82 | 0.00 | 0.00 | 01-JUN-00:10 | 15.57 | 11.82 |
July | 0.313101E+10 | 5984.68 | 24-JUL-06:13 | 14.47 | 13.19 | 0.00 | 0.00 | 01-JUL-00:10 | 14.47 | 13.19 |
August | 0.210122E+10 | 3706.77 | 11-AUG-16:00 | 25.60 | 14.77 | 0.00 | 0.00 | 01-AUG-00:10 | 25.60 | 14.77 |
September | 0.209938E+09 | 1166.89 | 29-SEP-06:02 | -4.6 | -5.0 | 0.00 | 0.00 | 01-SEP-00:10 | -4.6 | -5.0 |
October | 11214825.29 | 2398.48 | 27-OCT-04:01 | -17.7 | -18.2 | 0.00 | 0.00 | 01-OCT-00:10 | -17.7 | -18.2 |
November | 3669660.39 | 3204.63 | 30-NOV-05:01 | -27.8 | -28.0 | 0.00 | 0.00 | 01-NOV-00:10 | -27.8 | -28.0 |
December | 5492311.53 | 3214.70 | 22-DEC-05:01 | -28.2 | -28.4 | 0.00 | 0.00 | 01-DEC-00:10 | -28.2 | -28.4 |
Annual Sum or Average | 0.103538E+11 | 0.00 | ||||||||
Minimum of Months | 3669660.39 | 1166.89 | -28.2 | -28.4 | 0.00 | 0.00 | -28.2 | -28.4 | ||
Maximum of Months | 0.323183E+10 | 5984.68 | 25.60 | 14.77 | 0.00 | 0.00 | 25.60 | 14.77 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148487E+09 | 3411.20 | 26-JAN-05:01 | -23.9 | -24.2 | 0.00 | 0.00 | 01-JAN-00:10 | -23.9 | -24.2 |
February | 0.102949E+09 | 4057.63 | 18-FEB-05:01 | -23.9 | -24.3 | 0.00 | 0.00 | 01-FEB-00:10 | -23.9 | -24.3 |
March | 0.146336E+09 | 3943.07 | 03-MAR-05:01 | -25.6 | -26.1 | 0.00 | 0.00 | 01-MAR-00:10 | -25.6 | -26.1 |
April | 0.495033E+09 | 3064.65 | 05-APR-05:01 | -11.5 | -12.2 | 0.00 | 0.00 | 01-APR-00:10 | -11.5 | -12.2 |
May | 0.211977E+10 | 3394.16 | 31-MAY-16:00 | 22.20 | 10.79 | 0.00 | 0.00 | 01-MAY-00:10 | 22.20 | 10.79 |
June | 0.365371E+10 | 5246.73 | 12-JUN-06:07 | 10.18 | 7.56 | 0.00 | 0.00 | 01-JUN-00:10 | 10.18 | 7.56 |
July | 0.372240E+10 | 6387.36 | 24-JUL-06:13 | 14.47 | 13.19 | 0.00 | 0.00 | 01-JUL-00:10 | 14.47 | 13.19 |
August | 0.301247E+10 | 4314.78 | 11-AUG-15:50 | 25.40 | 14.66 | 0.00 | 0.00 | 01-AUG-00:10 | 25.40 | 14.66 |
September | 0.741161E+09 | 2601.35 | 01-SEP-06:05 | 6.70 | 5.86 | 0.00 | 0.00 | 01-SEP-00:10 | 6.70 | 5.86 |
October | 89261076.16 | 2186.09 | 27-OCT-06:10 | -18.4 | -18.8 | 0.00 | 0.00 | 01-OCT-00:10 | -18.4 | -18.8 |
November | 0.175734E+09 | 3103.78 | 30-NOV-05:01 | -27.8 | -28.0 | 0.00 | 0.00 | 01-NOV-00:10 | -27.8 | -28.0 |
December | 0.187543E+09 | 3362.79 | 14-DEC-05:01 | -26.0 | -26.3 | 0.00 | 0.00 | 01-DEC-00:10 | -26.0 | -26.3 |
Annual Sum or Average | 0.145948E+11 | 0.00 | ||||||||
Minimum of Months | 89261076.16 | 2186.09 | -27.8 | -28.0 | 0.00 | 0.00 | -27.8 | -28.0 | ||
Maximum of Months | 0.372240E+10 | 6387.36 | 25.40 | 14.66 | 0.00 | 0.00 | 25.40 | 14.66 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.264560E+10 | 4722.03 | 20-JAN-17:00 | -11.1 | -11.2 | 0.146787E+10 | 2066.64 | 20-JAN-14:00 | -11.1 | -11.2 |
February | 0.356411E+10 | 5385.30 | 09-FEB-15:10 | 0.10 | -1.0 | 0.137168E+10 | 2259.01 | 09-FEB-14:00 | 0.10 | -1.0 |
March | 0.585443E+10 | 5980.89 | 22-MAR-15:40 | 5.60 | 2.48 | 0.173232E+10 | 2428.69 | 23-MAR-13:00 | -1.7 | -4.1 |
April | 0.847271E+10 | 12199.85 | 21-APR-16:00 | 14.40 | 5.45 | 0.176637E+10 | 2606.67 | 24-APR-09:09 | 0.78 | -3.3 |
May | 0.147296E+11 | 25253.39 | 15-MAY-06:02 | 8.07 | 2.53 | 0.206555E+10 | 2606.66 | 16-MAY-09:20 | 6.33 | 4.90 |
June | 0.178730E+11 | 31430.13 | 05-JUN-06:03 | 11.20 | 8.82 | 0.206805E+10 | 2606.65 | 29-JUN-09:20 | 19.63 | 14.92 |
July | 0.173844E+11 | 31707.32 | 24-JUL-06:03 | 14.18 | 13.06 | 0.192250E+10 | 2606.91 | 19-JUL-09:09 | 14.18 | 13.06 |
August | 0.164062E+11 | 28792.56 | 07-AUG-06:01 | 10.68 | 10.30 | 0.215498E+10 | 2606.65 | 18-AUG-13:20 | 13.33 | 12.00 |
September | 0.983551E+10 | 12472.56 | 01-SEP-16:00 | 15.60 | 10.82 | 0.185475E+10 | 2606.66 | 01-SEP-09:20 | 15.60 | 10.82 |
October | 0.596363E+10 | 6912.45 | 05-OCT-16:00 | 11.10 | 5.87 | 0.165810E+10 | 2600.46 | 05-OCT-13:00 | 11.10 | 5.87 |
November | 0.315625E+10 | 4919.06 | 02-NOV-16:00 | -8.9 | -9.4 | 0.147433E+10 | 2121.33 | 08-NOV-14:00 | -13.9 | -14.6 |
December | 0.251326E+10 | 4548.31 | 21-DEC-17:00 | -16.7 | -17.3 | 0.141180E+10 | 2018.95 | 21-DEC-14:00 | -16.7 | -17.3 |
Annual Sum or Average | 0.108399E+12 | 0.209483E+11 | ||||||||
Minimum of Months | 0.251326E+10 | 4548.31 | -16.7 | -17.3 | 0.137168E+10 | 2018.95 | -16.7 | -17.3 | ||
Maximum of Months | 0.178730E+11 | 31707.32 | 15.60 | 13.06 | 0.215498E+10 | 2606.91 | 19.63 | 14.92 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.798231E+09 | 3992.10 | 21-JAN-17:02 | -5.5 | -5.8 | 0.144893E+10 | 1929.06 | 30-JAN-10:39 | -25.2 | -25.6 |
February | 0.161214E+10 | 4959.11 | 09-FEB-16:10 | 0.13 | -0.8 | 0.132577E+10 | 2143.26 | 09-FEB-14:00 | 0.13 | -0.8 |
March | 0.373236E+10 | 5834.53 | 22-MAR-16:00 | 5.60 | 2.61 | 0.163563E+10 | 2335.66 | 22-MAR-15:00 | 5.60 | 2.61 |
April | 0.699056E+10 | 11979.20 | 21-APR-16:00 | 14.40 | 5.45 | 0.166978E+10 | 2606.61 | 26-APR-13:20 | 10.93 | 4.19 |
May | 0.133412E+11 | 16123.63 | 31-MAY-16:00 | 22.20 | 10.79 | 0.204686E+10 | 2606.67 | 26-MAY-09:09 | 22.20 | 10.79 |
June | 0.172147E+11 | 26583.27 | 12-JUN-06:01 | 10.18 | 7.56 | 0.206473E+10 | 2606.64 | 27-JUN-09:20 | 13.90 | 13.13 |
July | 0.166502E+11 | 29485.98 | 24-JUL-05:12 | 13.17 | 12.61 | 0.191896E+10 | 2606.86 | 19-JUL-09:09 | 13.17 | 12.61 |
August | 0.147093E+11 | 16308.11 | 01-AUG-14:40 | 19.80 | 14.38 | 0.214199E+10 | 2606.64 | 18-AUG-13:20 | 13.33 | 12.00 |
September | 0.783127E+10 | 11434.54 | 01-SEP-16:00 | 15.60 | 10.82 | 0.175417E+10 | 2606.67 | 01-SEP-09:20 | 15.60 | 10.82 |
October | 0.376018E+10 | 6063.92 | 04-OCT-16:00 | 10.00 | 4.57 | 0.153565E+10 | 2457.98 | 04-OCT-13:00 | 10.00 | 4.57 |
November | 0.102447E+10 | 4223.08 | 02-NOV-16:00 | -8.9 | -9.4 | 0.143643E+10 | 1943.19 | 08-NOV-14:00 | -13.9 | -14.6 |
December | 0.730342E+09 | 3985.52 | 23-DEC-17:02 | -2.6 | -3.4 | 0.139776E+10 | 1928.99 | 11-DEC-10:09 | -2.6 | -3.4 |
Annual Sum or Average | 0.883950E+11 | 0.203767E+11 | ||||||||
Minimum of Months | 0.730342E+09 | 3985.52 | -8.9 | -9.4 | 0.132577E+10 | 1928.99 | -25.2 | -25.6 | ||
Maximum of Months | 0.172147E+11 | 29485.98 | 22.20 | 14.38 | 0.214199E+10 | 2606.86 | 22.20 | 13.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5561503.51 | 883.50 | 21-JAN-17:02 | -5.5 | -5.8 | 0.301802E+09 | 406.73 | 03-JAN-14:00 | -5.5 | -5.8 |
February | 6755715.31 | 891.90 | 11-FEB-17:03 | -1.2 | -2.7 | 0.274641E+09 | 406.70 | 27-FEB-14:39 | -28.5 | -28.7 |
March | 79108503.81 | 1159.35 | 22-MAR-15:40 | 5.60 | 2.48 | 0.331522E+09 | 444.51 | 22-MAR-13:00 | 5.60 | 2.48 |
April | 0.102066E+10 | 2177.65 | 28-APR-15:20 | 12.20 | 4.90 | 0.323745E+09 | 549.49 | 28-APR-13:20 | 12.20 | 4.90 |
May | 0.297386E+10 | 9226.02 | 31-MAY-06:02 | 14.08 | 8.75 | 0.424756E+09 | 549.50 | 19-MAY-13:20 | 14.08 | 8.75 |
June | 0.510183E+10 | 10252.34 | 29-JUN-05:12 | 12.57 | 11.17 | 0.435221E+09 | 549.50 | 27-JUN-09:20 | 12.57 | 11.17 |
July | 0.477522E+10 | 10391.06 | 11-JUL-05:12 | 15.37 | 12.05 | 0.404420E+09 | 549.54 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.334468E+10 | 4682.08 | 02-AUG-15:30 | 22.75 | 14.69 | 0.443436E+09 | 549.50 | 07-AUG-09:20 | 11.87 | 11.33 |
September | 0.125126E+10 | 2217.32 | 01-SEP-16:00 | 15.60 | 10.82 | 0.335951E+09 | 549.49 | 01-SEP-13:20 | 15.60 | 10.82 |
October | 0.179655E+09 | 1185.11 | 04-OCT-15:50 | 10.18 | 4.62 | 0.308238E+09 | 456.05 | 04-OCT-13:00 | 10.18 | 4.62 |
November | 5216859.43 | 880.94 | 04-NOV-16:02 | -9.6 | -11.3 | 0.299928E+09 | 406.71 | 17-NOV-10:09 | -25.0 | -25.3 |
December | 7556428.19 | 883.40 | 23-DEC-17:02 | -2.6 | -3.4 | 0.291499E+09 | 406.78 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.187514E+11 | 0.417516E+10 | ||||||||
Minimum of Months | 5216859.43 | 880.94 | -9.6 | -11.3 | 0.274641E+09 | 406.70 | -28.5 | -28.7 | ||
Maximum of Months | 0.510183E+10 | 10391.06 | 22.75 | 14.69 | 0.443436E+09 | 549.54 | 17.38 | 14.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4970161.33 | 508.06 | 21-JAN-17:02 | -5.5 | -5.8 | 0.192756E+09 | 257.50 | 03-JAN-14:00 | -5.5 | -5.8 |
February | 15701997.18 | 579.95 | 09-FEB-11:25 | -2.5 | -2.7 | 0.175149E+09 | 258.83 | 15-FEB-10:00 | -15.6 | -15.8 |
March | 0.319769E+09 | 1815.11 | 22-MAR-10:30 | 2.25 | 0.43 | 0.221946E+09 | 347.87 | 27-MAR-09:00 | -9.4 | -11.6 |
April | 0.138936E+10 | 5719.86 | 22-APR-09:15 | 8.87 | 3.75 | 0.230101E+09 | 347.93 | 21-APR-09:20 | 8.87 | 3.75 |
May | 0.447978E+10 | 15417.85 | 14-MAY-09:41 | 15.92 | 8.37 | 0.274981E+09 | 348.31 | 12-MAY-09:00 | 15.92 | 8.37 |
June | 0.541645E+10 | 12403.21 | 13-JUN-05:12 | 12.40 | 9.24 | 0.276077E+09 | 348.39 | 07-JUN-09:50 | 12.40 | 9.24 |
July | 0.533963E+10 | 14328.11 | 23-JUL-09:32 | 20.17 | 14.57 | 0.256806E+09 | 348.72 | 07-JUL-09:50 | 20.17 | 14.57 |
August | 0.398243E+10 | 11392.69 | 10-AUG-06:01 | 10.78 | 7.96 | 0.286539E+09 | 348.31 | 10-AUG-09:00 | 17.80 | 11.30 |
September | 0.122556E+10 | 4591.13 | 10-SEP-10:33 | 13.87 | 7.59 | 0.230117E+09 | 347.91 | 12-SEP-09:20 | 7.57 | 6.07 |
October | 0.226788E+09 | 1640.57 | 03-OCT-09:45 | 3.43 | 2.35 | 0.201114E+09 | 347.87 | 03-OCT-09:30 | 3.43 | 2.35 |
November | 4668828.08 | 506.51 | 04-NOV-16:02 | -9.6 | -11.3 | 0.190980E+09 | 257.49 | 29-NOV-14:39 | -25.2 | -25.5 |
December | 6038096.70 | 507.79 | 23-DEC-17:02 | -2.6 | -3.4 | 0.185851E+09 | 257.54 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.224112E+11 | 0.272242E+10 | ||||||||
Minimum of Months | 4668828.08 | 506.51 | -9.6 | -11.3 | 0.175149E+09 | 257.49 | -25.2 | -25.5 | ||
Maximum of Months | 0.541645E+10 | 15417.85 | 20.17 | 14.57 | 0.286539E+09 | 348.72 | 20.17 | 14.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 27449409.25 | 980.83 | 25-JAN-13:40 | -19.5 | -19.7 | 0.304733E+09 | 434.91 | 25-JAN-14:09 | -18.9 | -19.2 |
February | 0.289717E+09 | 3840.00 | 15-FEB-13:50 | -8.5 | -9.4 | 0.288060E+09 | 549.49 | 09-FEB-14:00 | -8.5 | -9.4 |
March | 0.140264E+10 | 7766.89 | 31-MAR-13:50 | -11.2 | -13.1 | 0.373408E+09 | 549.49 | 01-MAR-14:20 | -11.2 | -13.1 |
April | 0.403954E+10 | 13905.01 | 23-APR-13:13 | 10.00 | 3.85 | 0.363089E+09 | 549.64 | 20-APR-13:50 | 10.00 | 3.85 |
May | 0.634215E+10 | 23654.11 | 14-MAY-12:22 | 18.35 | 9.42 | 0.426721E+09 | 549.62 | 12-MAY-13:39 | 18.35 | 9.42 |
June | 0.760320E+10 | 17732.67 | 18-JUN-13:13 | 15.20 | 11.37 | 0.434576E+09 | 549.50 | 28-JUN-13:00 | 17.80 | 14.79 |
July | 0.753802E+10 | 23408.46 | 23-JUL-13:32 | 25.00 | 15.26 | 0.404210E+09 | 550.00 | 12-JUL-13:00 | 25.00 | 15.26 |
August | 0.694852E+10 | 22365.73 | 27-AUG-13:22 | 18.60 | 13.91 | 0.448506E+09 | 549.85 | 25-AUG-13:00 | 18.60 | 13.91 |
September | 0.306772E+10 | 10571.85 | 07-SEP-14:30 | 15.85 | 8.58 | 0.363089E+09 | 549.51 | 08-SEP-13:09 | 11.28 | 7.64 |
October | 0.843383E+09 | 8880.66 | 03-OCT-13:30 | 10.85 | 6.24 | 0.329998E+09 | 549.49 | 04-OCT-13:39 | 11.30 | 4.92 |
November | 76797146.16 | 1539.01 | 08-NOV-13:40 | -13.5 | -14.3 | 0.303892E+09 | 549.50 | 08-NOV-14:20 | -13.5 | -14.2 |
December | 9827739.89 | 804.37 | 23-DEC-17:02 | -2.6 | -3.4 | 0.293601E+09 | 406.77 | 27-DEC-14:39 | -23.9 | -24.1 |
Annual Sum or Average | 0.381890E+11 | 0.433388E+10 | ||||||||
Minimum of Months | 9827739.89 | 804.37 | -19.5 | -19.7 | 0.288060E+09 | 406.77 | -23.9 | -24.1 | ||
Maximum of Months | 0.760320E+10 | 23654.11 | 25.00 | 15.26 | 0.448506E+09 | 550.00 | 25.00 | 15.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5180593.86 | 508.50 | 21-JAN-17:02 | -5.5 | -5.8 | 0.192741E+09 | 257.49 | 03-JAN-14:00 | -5.5 | -5.8 |
February | 14827990.79 | 575.87 | 09-FEB-07:04 | -0.3 | -0.7 | 0.175106E+09 | 258.24 | 09-FEB-14:00 | 0.00 | -1.0 |
March | 0.160468E+09 | 864.43 | 22-MAR-16:00 | 5.60 | 2.61 | 0.213388E+09 | 337.74 | 22-MAR-15:00 | 5.60 | 2.61 |
April | 0.149562E+10 | 9927.06 | 22-APR-17:42 | 13.07 | 5.65 | 0.214167E+09 | 347.85 | 26-APR-13:20 | 10.93 | 4.19 |
May | 0.289841E+10 | 14987.22 | 14-MAY-18:22 | 16.70 | 9.19 | 0.268000E+09 | 347.85 | 19-MAY-13:20 | 14.43 | 8.20 |
June | 0.442216E+10 | 13862.89 | 10-JUN-17:05 | 21.20 | 10.81 | 0.275161E+09 | 347.85 | 27-JUN-09:20 | 13.90 | 13.13 |
July | 0.395341E+10 | 10943.38 | 09-JUL-19:53 | 19.40 | 13.11 | 0.255743E+09 | 347.88 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.308324E+10 | 11520.18 | 27-AUG-17:22 | 20.85 | 12.52 | 0.281524E+09 | 347.85 | 07-AUG-09:20 | 20.85 | 12.52 |
September | 0.103634E+10 | 6048.09 | 02-SEP-17:43 | 16.70 | 10.38 | 0.218213E+09 | 347.84 | 01-SEP-13:20 | 16.70 | 10.38 |
October | 0.151810E+09 | 875.50 | 03-OCT-15:20 | 12.43 | 6.74 | 0.197087E+09 | 338.64 | 03-OCT-15:30 | 12.25 | 6.65 |
November | 5070937.60 | 508.09 | 04-NOV-16:02 | -9.6 | -11.3 | 0.190971E+09 | 257.48 | 29-NOV-14:00 | -25.6 | -25.8 |
December | 6141769.71 | 508.44 | 23-DEC-17:02 | -2.6 | -3.4 | 0.185839E+09 | 257.52 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.172327E+11 | 0.266794E+10 | ||||||||
Minimum of Months | 5070937.60 | 508.09 | -9.6 | -11.3 | 0.175106E+09 | 257.48 | -25.6 | -25.8 | ||
Maximum of Months | 0.442216E+10 | 14987.22 | 21.20 | 13.11 | 0.281524E+09 | 347.88 | 20.85 | 14.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6517297.18 | 815.62 | 21-JAN-17:02 | -5.5 | -5.8 | 0.297889E+09 | 406.71 | 11-JAN-14:39 | -5.5 | -5.8 |
February | 6630156.57 | 816.70 | 11-FEB-17:03 | -1.2 | -2.7 | 0.271383E+09 | 406.69 | 24-FEB-10:00 | -24.4 | -24.9 |
March | 30614714.33 | 891.44 | 22-MAR-15:10 | 5.60 | 2.29 | 0.330995E+09 | 408.43 | 22-MAR-13:00 | 5.60 | 2.29 |
April | 0.761782E+09 | 1250.72 | 28-APR-15:40 | 12.20 | 5.02 | 0.311815E+09 | 508.66 | 28-APR-13:00 | 12.20 | 5.02 |
May | 0.206720E+10 | 2654.97 | 31-MAY-14:30 | 20.55 | 10.45 | 0.417207E+09 | 549.50 | 12-MAY-09:20 | 20.55 | 10.45 |
June | 0.369251E+10 | 7803.66 | 13-JUN-05:12 | 12.40 | 9.24 | 0.434737E+09 | 549.50 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.389717E+10 | 8442.33 | 11-JUL-05:14 | 15.37 | 12.05 | 0.404524E+09 | 549.54 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.307274E+10 | 6838.10 | 02-AUG-06:01 | 11.28 | 10.30 | 0.449224E+09 | 549.50 | 18-AUG-13:20 | 13.33 | 12.00 |
September | 0.150763E+10 | 1838.80 | 01-SEP-15:50 | 15.50 | 10.82 | 0.358891E+09 | 549.49 | 01-SEP-13:20 | 15.50 | 10.82 |
October | 0.429587E+09 | 1162.28 | 06-OCT-15:00 | 10.60 | 4.90 | 0.314600E+09 | 484.84 | 06-OCT-13:00 | 10.60 | 4.90 |
November | 5974644.36 | 827.76 | 04-NOV-16:02 | -9.6 | -11.3 | 0.300749E+09 | 406.70 | 29-NOV-14:39 | -25.2 | -25.5 |
December | 8950275.16 | 820.37 | 23-DEC-17:02 | -2.6 | -3.4 | 0.291218E+09 | 406.76 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.154873E+11 | 0.418323E+10 | ||||||||
Minimum of Months | 5974644.36 | 815.62 | -9.6 | -11.3 | 0.271383E+09 | 406.69 | -25.2 | -25.5 | ||
Maximum of Months | 0.389717E+10 | 8442.33 | 20.55 | 12.05 | 0.449224E+09 | 549.54 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4853352.51 | 511.56 | 21-JAN-17:02 | -5.5 | -5.8 | 0.192944E+09 | 257.50 | 30-JAN-14:09 | -23.8 | -24.3 |
February | 11679518.70 | 554.42 | 15-FEB-10:40 | -16.3 | -16.5 | 0.175301E+09 | 257.95 | 15-FEB-10:50 | -16.0 | -16.2 |
March | 0.254021E+09 | 1250.22 | 31-MAR-09:10 | -17.5 | -18.6 | 0.218442E+09 | 347.88 | 31-MAR-09:00 | -16.1 | -17.3 |
April | 0.110824E+10 | 3829.24 | 22-APR-08:30 | 6.65 | 2.48 | 0.227835E+09 | 347.88 | 28-APR-09:20 | 6.70 | 3.17 |
May | 0.363483E+10 | 10163.68 | 14-MAY-09:31 | 15.73 | 8.25 | 0.275552E+09 | 347.88 | 19-MAY-09:09 | 12.15 | 6.94 |
June | 0.449667E+10 | 10388.40 | 13-JUN-05:12 | 12.40 | 9.24 | 0.276064E+09 | 348.24 | 07-JUN-09:20 | 12.40 | 9.24 |
July | 0.480406E+10 | 11723.92 | 23-JUL-10:01 | 21.38 | 14.90 | 0.257051E+09 | 348.36 | 07-JUL-09:50 | 21.38 | 14.90 |
August | 0.397920E+10 | 9140.26 | 10-AUG-06:01 | 10.78 | 7.96 | 0.287648E+09 | 348.20 | 11-AUG-09:09 | 16.97 | 10.66 |
September | 0.156833E+10 | 8658.48 | 10-SEP-08:32 | 10.17 | 5.74 | 0.242792E+09 | 347.88 | 08-SEP-13:20 | 10.17 | 5.74 |
October | 0.437098E+09 | 2120.55 | 03-OCT-09:30 | 2.50 | 1.67 | 0.208970E+09 | 347.88 | 13-OCT-09:00 | -6.7 | -7.8 |
November | 4566306.45 | 549.83 | 02-NOV-06:03 | -10.7 | -11.1 | 0.191373E+09 | 257.49 | 29-NOV-14:39 | -25.2 | -25.5 |
December | 6261415.13 | 514.16 | 23-DEC-17:02 | -2.6 | -3.4 | 0.186103E+09 | 257.53 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.203098E+11 | 0.274007E+10 | ||||||||
Minimum of Months | 4566306.45 | 511.56 | -17.5 | -18.6 | 0.175301E+09 | 257.49 | -25.2 | -25.5 | ||
Maximum of Months | 0.480406E+10 | 11723.92 | 21.38 | 14.90 | 0.287648E+09 | 348.36 | 21.38 | 14.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8154090.01 | 807.71 | 21-JAN-17:02 | -5.5 | -5.8 | 0.267229E+09 | 406.67 | 30-JAN-14:09 | -23.8 | -24.3 |
February | 75753006.14 | 1074.66 | 18-FEB-13:30 | -14.4 | -15.8 | 0.254862E+09 | 447.51 | 09-FEB-14:09 | -14.4 | -15.8 |
March | 0.237614E+09 | 1291.47 | 11-MAR-13:50 | -3.8 | -5.8 | 0.322678E+09 | 511.56 | 22-MAR-14:50 | 5.60 | 2.17 |
April | 0.182996E+10 | 8060.63 | 22-APR-14:00 | 15.60 | 7.03 | 0.339783E+09 | 549.51 | 27-APR-13:09 | 10.68 | 4.13 |
May | 0.345032E+10 | 12473.62 | 14-MAY-12:52 | 18.90 | 9.36 | 0.412076E+09 | 549.51 | 05-MAY-13:20 | 18.90 | 9.36 |
June | 0.493768E+10 | 12806.63 | 18-JUN-12:22 | 16.40 | 11.93 | 0.426715E+09 | 549.54 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.576679E+10 | 18610.98 | 23-JUL-13:21 | 25.00 | 15.26 | 0.399066E+09 | 549.54 | 31-JUL-13:20 | 22.07 | 13.34 |
August | 0.535335E+10 | 15621.42 | 27-AUG-13:22 | 18.60 | 13.91 | 0.441782E+09 | 549.54 | 11-AUG-13:20 | 18.60 | 13.91 |
September | 0.229874E+10 | 10449.45 | 10-SEP-11:53 | 15.60 | 8.34 | 0.354382E+09 | 549.51 | 08-SEP-13:09 | 15.60 | 8.34 |
October | 0.519674E+09 | 5761.99 | 03-OCT-13:40 | 11.13 | 6.36 | 0.312059E+09 | 549.51 | 13-OCT-13:09 | 0.18 | -2.9 |
November | 15856213.25 | 927.57 | 08-NOV-13:14 | -13.7 | -14.5 | 0.272920E+09 | 406.66 | 29-NOV-14:00 | -25.6 | -25.8 |
December | 9049156.09 | 806.98 | 23-DEC-17:02 | -2.6 | -3.4 | 0.256908E+09 | 406.74 | 22-DEC-10:50 | -2.6 | -3.4 |
Annual Sum or Average | 0.245029E+11 | 0.406046E+10 | ||||||||
Minimum of Months | 8154090.01 | 806.98 | -14.4 | -15.8 | 0.254862E+09 | 406.66 | -25.6 | -25.8 | ||
Maximum of Months | 0.576679E+10 | 18610.98 | 25.00 | 15.26 | 0.441782E+09 | 549.54 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4966550.51 | 510.35 | 21-JAN-17:02 | -5.5 | -5.8 | 0.192931E+09 | 257.48 | 03-JAN-14:00 | -5.5 | -5.8 |
February | 5952959.84 | 511.39 | 11-FEB-17:03 | -1.2 | -2.7 | 0.175223E+09 | 257.47 | 27-FEB-14:39 | -28.5 | -28.7 |
March | 90555960.81 | 738.83 | 31-MAR-17:01 | -9.4 | -11.7 | 0.211316E+09 | 288.20 | 29-MAR-15:00 | -9.4 | -11.7 |
April | 0.110663E+10 | 5231.35 | 21-APR-18:20 | 14.03 | 5.87 | 0.214012E+09 | 347.83 | 26-APR-13:00 | 10.60 | 4.23 |
May | 0.206665E+10 | 6129.65 | 14-MAY-19:53 | 15.60 | 7.57 | 0.268554E+09 | 347.85 | 19-MAY-09:20 | 12.60 | 7.05 |
June | 0.344979E+10 | 7813.15 | 10-JUN-17:07 | 21.20 | 10.81 | 0.275340E+09 | 347.85 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.335498E+10 | 8438.72 | 09-JUL-19:42 | 19.50 | 13.10 | 0.256229E+09 | 347.88 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.297844E+10 | 7307.65 | 27-AUG-17:22 | 20.85 | 12.52 | 0.285926E+09 | 347.85 | 07-AUG-09:20 | 20.85 | 12.52 |
September | 0.124447E+10 | 3564.34 | 08-SEP-16:00 | 14.40 | 9.03 | 0.233531E+09 | 347.86 | 01-SEP-09:20 | 14.40 | 9.03 |
October | 0.308046E+09 | 853.89 | 03-OCT-15:20 | 12.43 | 6.74 | 0.201524E+09 | 335.97 | 03-OCT-15:30 | 12.25 | 6.65 |
November | 5967139.03 | 519.07 | 04-NOV-16:02 | -9.6 | -11.3 | 0.191362E+09 | 257.48 | 29-NOV-14:00 | -25.6 | -25.8 |
December | 6363210.21 | 513.34 | 23-DEC-17:02 | -2.6 | -3.4 | 0.186090E+09 | 257.51 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.146228E+11 | 0.269204E+10 | ||||||||
Minimum of Months | 4966550.51 | 510.35 | -9.6 | -11.7 | 0.175223E+09 | 257.47 | -28.5 | -28.7 | ||
Maximum of Months | 0.344979E+10 | 8438.72 | 21.20 | 13.10 | 0.285926E+09 | 347.88 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7254466.85 | 818.83 | 21-JAN-17:02 | -5.5 | -5.8 | 0.303579E+09 | 406.72 | 03-JAN-14:00 | -5.5 | -5.8 |
February | 15008932.46 | 823.48 | 11-FEB-17:03 | -1.2 | -2.7 | 0.276129E+09 | 406.70 | 27-FEB-14:39 | -28.5 | -28.7 |
March | 0.181396E+09 | 1108.39 | 22-MAR-15:40 | 5.60 | 2.48 | 0.334337E+09 | 464.61 | 22-MAR-13:00 | 5.60 | 2.48 |
April | 0.123545E+10 | 2442.93 | 28-APR-15:20 | 12.20 | 4.90 | 0.340063E+09 | 549.49 | 20-APR-13:20 | 12.20 | 4.90 |
May | 0.325795E+10 | 8872.10 | 31-MAY-05:12 | 12.43 | 7.84 | 0.432781E+09 | 549.50 | 16-MAY-09:20 | 12.43 | 7.84 |
June | 0.529451E+10 | 9262.72 | 07-JUN-05:12 | 7.40 | 5.52 | 0.436044E+09 | 549.51 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.494745E+10 | 9384.69 | 11-JUL-05:12 | 15.37 | 12.05 | 0.405473E+09 | 549.55 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.364170E+10 | 7811.98 | 02-AUG-06:01 | 11.28 | 10.30 | 0.450707E+09 | 549.50 | 18-AUG-13:20 | 13.33 | 12.00 |
September | 0.155315E+10 | 2632.85 | 01-SEP-13:40 | 14.63 | 10.60 | 0.361654E+09 | 549.50 | 08-SEP-13:20 | 11.47 | 7.77 |
October | 0.394978E+09 | 1194.00 | 04-OCT-16:00 | 10.00 | 4.57 | 0.314721E+09 | 494.31 | 06-OCT-13:00 | 10.60 | 4.48 |
November | 6030329.13 | 818.31 | 04-NOV-16:02 | -9.6 | -11.3 | 0.301488E+09 | 406.71 | 17-NOV-10:09 | -25.0 | -25.3 |
December | 8811659.86 | 816.82 | 23-DEC-17:02 | -2.6 | -3.4 | 0.293304E+09 | 406.77 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.205437E+11 | 0.425028E+10 | ||||||||
Minimum of Months | 6030329.13 | 816.82 | -9.6 | -11.3 | 0.276129E+09 | 406.70 | -28.5 | -28.7 | ||
Maximum of Months | 0.529451E+10 | 9384.69 | 15.37 | 12.05 | 0.450707E+09 | 549.55 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7019342.84 | 571.85 | 20-JAN-13:02 | -9.8 | -10.1 | 0.141303E+09 | 250.73 | 10-JAN-16:00 | -9.8 | -10.1 |
February | 40557928.67 | 673.15 | 15-FEB-11:10 | -14.9 | -15.2 | 0.128826E+09 | 284.86 | 15-FEB-11:09 | -14.9 | -15.2 |
March | 0.384904E+09 | 7397.03 | 31-MAR-12:01 | -12.6 | -14.4 | 0.167948E+09 | 356.46 | 31-MAR-12:09 | -12.6 | -14.4 |
April | 0.159745E+10 | 7709.28 | 28-APR-12:01 | 9.27 | 4.21 | 0.173689E+09 | 356.46 | 28-APR-10:09 | 9.27 | 4.21 |
May | 0.461833E+10 | 14026.04 | 14-MAY-09:12 | 15.37 | 8.02 | 0.204767E+09 | 356.46 | 19-MAY-14:09 | 13.48 | 8.19 |
June | 0.533235E+10 | 12477.44 | 19-JUN-05:12 | 8.73 | 7.50 | 0.204865E+09 | 356.46 | 13-JUN-12:09 | 8.73 | 7.50 |
July | 0.527190E+10 | 14524.74 | 09-JUL-07:02 | 15.18 | 12.43 | 0.191295E+09 | 356.47 | 20-JUL-12:09 | 25.10 | 14.82 |
August | 0.409274E+10 | 11029.48 | 27-AUG-10:32 | 13.17 | 10.82 | 0.212851E+09 | 356.47 | 24-AUG-12:09 | 13.17 | 10.82 |
September | 0.144586E+10 | 7408.63 | 08-SEP-12:01 | 9.68 | 5.58 | 0.178090E+09 | 356.46 | 01-SEP-10:09 | 9.68 | 5.58 |
October | 0.319418E+09 | 6180.80 | 03-OCT-12:01 | 8.17 | 5.20 | 0.152438E+09 | 356.72 | 03-OCT-10:09 | 8.17 | 5.20 |
November | 6346165.58 | 573.36 | 08-NOV-13:02 | -13.8 | -14.6 | 0.140005E+09 | 250.72 | 07-NOV-09:09 | -13.8 | -14.6 |
December | 7035255.74 | 565.06 | 21-DEC-13:02 | -14.2 | -14.5 | 0.136249E+09 | 250.74 | 27-DEC-13:00 | -23.9 | -24.1 |
Annual Sum or Average | 0.231239E+11 | 0.203233E+10 | ||||||||
Minimum of Months | 6346165.58 | 565.06 | -14.9 | -15.2 | 0.128826E+09 | 250.72 | -23.9 | -24.1 | ||
Maximum of Months | 0.533235E+10 | 14524.74 | 15.37 | 12.43 | 0.212851E+09 | 356.72 | 25.10 | 14.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 62969062.22 | 1136.77 | 25-JAN-13:40 | -19.5 | -19.7 | 0.305933E+09 | 477.52 | 25-JAN-14:09 | -18.9 | -19.2 |
February | 0.451252E+09 | 4723.30 | 15-FEB-13:40 | -8.7 | -9.6 | 0.293604E+09 | 549.50 | 13-FEB-14:20 | -8.7 | -9.6 |
March | 0.183139E+10 | 8899.63 | 31-MAR-13:30 | -11.4 | -13.3 | 0.382222E+09 | 550.13 | 03-MAR-14:50 | -11.4 | -13.3 |
April | 0.461658E+10 | 16681.56 | 23-APR-13:13 | 10.00 | 3.85 | 0.372988E+09 | 550.45 | 21-APR-13:20 | 10.00 | 3.85 |
May | 0.668520E+10 | 20105.68 | 14-MAY-12:32 | 18.53 | 9.40 | 0.432972E+09 | 550.69 | 12-MAY-13:20 | 18.53 | 9.40 |
June | 0.772684E+10 | 21489.32 | 18-JUN-12:22 | 16.40 | 11.93 | 0.435769E+09 | 549.55 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.766847E+10 | 22067.43 | 23-JUL-13:12 | 25.00 | 15.26 | 0.405487E+09 | 550.95 | 20-JUL-13:20 | 25.00 | 15.26 |
August | 0.734229E+10 | 23589.77 | 27-AUG-13:11 | 18.33 | 13.81 | 0.452747E+09 | 550.77 | 09-AUG-13:20 | 18.33 | 13.81 |
September | 0.375455E+10 | 18937.51 | 10-SEP-11:23 | 15.00 | 8.08 | 0.380111E+09 | 549.51 | 08-SEP-13:09 | 15.00 | 8.08 |
October | 0.123410E+10 | 9702.62 | 03-OCT-13:30 | 10.85 | 6.24 | 0.341118E+09 | 549.66 | 05-OCT-13:39 | 10.40 | 5.34 |
November | 0.137258E+09 | 2771.62 | 08-NOV-13:30 | -13.6 | -14.4 | 0.306401E+09 | 549.49 | 08-NOV-14:20 | -13.5 | -14.2 |
December | 11011944.63 | 821.34 | 23-DEC-17:02 | -2.6 | -3.4 | 0.294007E+09 | 406.75 | 22-DEC-10:50 | -2.6 | -3.4 |
Annual Sum or Average | 0.415219E+11 | 0.440336E+10 | ||||||||
Minimum of Months | 11011944.63 | 821.34 | -19.5 | -19.7 | 0.293604E+09 | 406.75 | -18.9 | -19.2 | ||
Maximum of Months | 0.772684E+10 | 23589.77 | 25.00 | 15.26 | 0.452747E+09 | 550.95 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6178750.74 | 516.68 | 21-JAN-17:02 | -5.5 | -5.8 | 0.193001E+09 | 257.48 | 03-JAN-14:00 | -5.5 | -5.8 |
February | 29862303.56 | 616.50 | 09-FEB-15:10 | 0.10 | -1.0 | 0.175580E+09 | 270.09 | 09-FEB-14:00 | 0.10 | -1.0 |
March | 0.251246E+09 | 1261.49 | 31-MAR-16:00 | -9.4 | -11.8 | 0.215872E+09 | 338.67 | 22-MAR-15:00 | -9.4 | -11.8 |
April | 0.174684E+10 | 10628.57 | 22-APR-17:42 | 13.07 | 5.65 | 0.222859E+09 | 347.85 | 24-APR-13:20 | 4.40 | -1.0 |
May | 0.311596E+10 | 12368.20 | 28-MAY-17:12 | 16.70 | 8.41 | 0.273245E+09 | 347.86 | 16-MAY-09:20 | 16.70 | 8.41 |
June | 0.451235E+10 | 13133.41 | 10-JUN-17:05 | 21.20 | 10.81 | 0.275907E+09 | 347.86 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.405853E+10 | 10896.03 | 09-JUL-19:42 | 19.50 | 13.10 | 0.256565E+09 | 347.89 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.331997E+10 | 14555.70 | 27-AUG-17:52 | 20.60 | 12.18 | 0.285440E+09 | 347.85 | 07-AUG-09:20 | 20.60 | 12.18 |
September | 0.134209E+10 | 6588.76 | 02-SEP-17:43 | 16.70 | 10.38 | 0.231780E+09 | 347.85 | 01-SEP-09:39 | 16.70 | 10.38 |
October | 0.290916E+09 | 1265.60 | 03-OCT-15:00 | 12.80 | 6.92 | 0.201489E+09 | 338.68 | 03-OCT-15:00 | 11.70 | 6.37 |
November | 7574925.30 | 575.89 | 08-NOV-15:40 | -15.4 | -15.8 | 0.191228E+09 | 257.67 | 08-NOV-15:50 | -15.7 | -16.1 |
December | 6675339.03 | 515.37 | 23-DEC-17:02 | -2.6 | -3.4 | 0.186078E+09 | 257.51 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.186882E+11 | 0.270904E+10 | ||||||||
Minimum of Months | 6178750.74 | 515.37 | -15.4 | -15.8 | 0.175580E+09 | 257.48 | -23.9 | -24.1 | ||
Maximum of Months | 0.451235E+10 | 14555.70 | 21.20 | 13.10 | 0.285440E+09 | 347.89 | 25.00 | 15.96 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.802646E+09 | 19962.30 | 02-JAN-05:01 | -15.6 |
February | 0.114938E+09 | 17193.95 | 06-FEB-06:01 | -12.9 |
March | 7384712.75 | 13625.23 | 07-MAR-07:01 | -9.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 1082304.14 | 12417.09 | 30-OCT-06:01 | -15.1 |
November | 60821317.17 | 16692.11 | 13-NOV-06:03 | -18.1 |
December | 0.133498E+09 | 16084.21 | 13-DEC-07:03 | -25.6 |
Annual Sum or Average | 0.112037E+10 | |||
Minimum of Months | 0.00 | 0.00 | -25.6 | |
Maximum of Months | 0.802646E+09 | 19962.30 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124802E+11 | 19765.12 | 12-JAN-06:13 | -38.3 |
February | 0.917469E+10 | 19402.60 | 27-FEB-06:07 | -35.9 |
March | 0.664045E+10 | 18550.44 | 01-MAR-06:12 | -28.5 |
April | 0.222065E+10 | 17528.44 | 03-APR-05:12 | -21.3 |
May | 0.478407E+09 | 5894.33 | 21-MAY-07:32 | 8.50 |
June | 0.107395E+09 | 6406.94 | 07-JUN-05:12 | 7.40 |
July | 0.119999E+09 | 5477.46 | 21-JUL-05:12 | 11.50 |
August | 0.376647E+09 | 3592.03 | 31-AUG-07:30 | 0.80 |
September | 0.133792E+10 | 7802.02 | 28-SEP-06:02 | -2.8 |
October | 0.490908E+10 | 16323.46 | 27-OCT-05:12 | -17.6 |
November | 0.110697E+11 | 18733.44 | 29-NOV-06:12 | -28.9 |
December | 0.132187E+11 | 18522.53 | 15-DEC-06:13 | -33.0 |
Annual Sum or Average | 0.621338E+11 | |||
Minimum of Months | 0.107395E+09 | 3592.03 | -38.3 | |
Maximum of Months | 0.132187E+11 | 19765.12 | 11.50 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.494681E+10 | 12256.66 | 02-JAN-07:04 | -14.4 |
February | 0.349142E+10 | 11324.80 | 27-FEB-07:04 | -34.9 |
March | 0.274080E+10 | 8513.51 | 06-MAR-07:02 | -20.9 |
April | 0.111586E+10 | 6415.77 | 03-APR-06:02 | -21.5 |
May | 91020030.05 | 5256.39 | 28-MAY-15:53 | 16.10 |
June | 34739738.30 | 4184.65 | 18-JUN-12:22 | 16.40 |
July | 36883111.90 | 4810.85 | 23-JUL-11:12 | 23.17 |
August | 41016427.13 | 5149.54 | 27-AUG-15:52 | 20.60 |
September | 0.549249E+09 | 6579.58 | 10-SEP-11:23 | 15.00 |
October | 0.212557E+10 | 8970.33 | 30-OCT-06:11 | -15.2 |
November | 0.397806E+10 | 11038.49 | 27-NOV-07:03 | -26.7 |
December | 0.478810E+10 | 11292.39 | 04-DEC-07:03 | -19.4 |
Annual Sum or Average | 0.239395E+11 | |||
Minimum of Months | 34739738.30 | 4184.65 | -34.9 | |
Maximum of Months | 0.494681E+10 | 12256.66 | 23.17 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.413732E+10 | 10774.69 | 02-JAN-08:13 | -14.8 |
February | 0.291523E+10 | 7526.28 | 21-FEB-07:01 | -23.2 |
March | 0.207189E+10 | 4976.19 | 06-MAR-07:01 | -20.9 |
April | 0.647224E+09 | 3949.24 | 03-APR-07:16 | -19.7 |
May | 24775122.99 | 3070.32 | 13-MAY-05:12 | 9.07 |
June | 22407207.01 | 3109.22 | 16-JUN-05:12 | 9.60 |
July | 28036951.97 | 4104.86 | 06-JUL-05:12 | 9.23 |
August | 26276703.47 | 5382.72 | 31-AUG-05:03 | -1.2 |
September | 0.235018E+09 | 5090.81 | 18-SEP-05:03 | 1.78 |
October | 0.160308E+10 | 5364.76 | 30-OCT-06:01 | -15.1 |
November | 0.305437E+10 | 7336.60 | 13-NOV-07:01 | -17.1 |
December | 0.383696E+10 | 7623.54 | 04-DEC-07:01 | -19.4 |
Annual Sum or Average | 0.186026E+11 | |||
Minimum of Months | 22407207.01 | 3070.32 | -23.2 | |
Maximum of Months | 0.413732E+10 | 10774.69 | 9.60 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.326537E+10 | 26855.38 | 02-JAN-05:01 | -15.6 |
February | 0.163680E+10 | 25906.42 | 21-FEB-05:11 | -23.0 |
March | 0.388807E+09 | 24024.12 | 06-MAR-06:01 | -21.1 |
April | 48900820.17 | 22879.68 | 03-APR-05:01 | -21.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.291785E+09 | 23992.12 | 30-OCT-05:01 | -14.5 |
November | 0.188850E+10 | 25904.53 | 13-NOV-05:01 | -20.2 |
December | 0.282828E+10 | 25825.01 | 04-DEC-05:01 | -19.9 |
Annual Sum or Average | 0.103484E+11 | |||
Minimum of Months | 0.00 | 0.00 | -23.0 | |
Maximum of Months | 0.326537E+10 | 26855.38 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.988183E+10 | 30440.26 | 01-JAN-02:42 | -14.5 |
February | 0.613770E+10 | 30379.21 | 27-FEB-04:22 | -35.2 |
March | 0.306984E+10 | 29744.60 | 06-MAR-05:01 | -20.2 |
April | 0.577139E+09 | 28521.11 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 53700126.46 | 24243.26 | 28-SEP-06:02 | -2.8 |
October | 0.225232E+10 | 29843.57 | 30-OCT-04:01 | -14.4 |
November | 0.782453E+10 | 30268.93 | 27-NOV-04:52 | -25.6 |
December | 0.978159E+10 | 30127.94 | 04-DEC-04:52 | -20.0 |
Annual Sum or Average | 0.395787E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.2 | |
Maximum of Months | 0.988183E+10 | 30440.26 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107359E+11 | 10676.58 | 30-JAN-06:01 | -25.6 |
February | 0.800893E+10 | 10648.17 | 26-FEB-05:02 | -25.6 |
March | 0.543441E+10 | 10189.08 | 06-MAR-04:12 | -20.0 |
April | 0.128072E+10 | 10203.42 | 03-APR-03:42 | -21.1 |
May | 1721369.24 | 6385.35 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 4477408.23 | 7684.91 | 31-AUG-06:03 | -1.5 |
September | 0.317630E+09 | 8907.98 | 30-SEP-05:01 | -4.5 |
October | 0.386036E+10 | 10219.06 | 22-OCT-21:42 | -15.9 |
November | 0.920615E+10 | 10451.08 | 27-NOV-04:52 | -25.6 |
December | 0.108329E+11 | 10445.07 | 04-DEC-02:12 | -20.9 |
Annual Sum or Average | 0.496832E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.6 | |
Maximum of Months | 0.108329E+11 | 10676.58 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.712210E+10 | 12949.46 | 29-JAN-09:22 | -25.9 |
February | 0.476745E+10 | 12902.58 | 26-FEB-05:02 | -25.6 |
March | 0.243155E+10 | 12431.03 | 01-MAR-05:11 | -28.3 |
April | 0.549161E+09 | 12177.14 | 03-APR-03:42 | -21.1 |
May | 92980.11 | 619.87 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 1621775.59 | 5447.03 | 31-AUG-06:03 | -1.5 |
September | 0.135781E+09 | 10867.69 | 30-SEP-05:01 | -4.5 |
October | 0.212776E+10 | 12333.06 | 30-OCT-04:01 | -14.4 |
November | 0.604623E+10 | 12607.26 | 27-NOV-04:52 | -25.6 |
December | 0.729846E+10 | 12593.12 | 04-DEC-02:12 | -20.9 |
Annual Sum or Average | 0.304802E+11 | |||
Minimum of Months | 0.00 | 0.00 | -28.3 | |
Maximum of Months | 0.729846E+10 | 12949.46 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.985017E+10 | 20332.14 | 29-JAN-09:22 | -25.9 |
February | 0.577196E+10 | 20270.48 | 26-FEB-05:02 | -25.6 |
March | 0.312948E+10 | 19503.22 | 01-MAR-05:11 | -28.3 |
April | 0.759449E+09 | 18364.87 | 03-APR-04:01 | -21.1 |
May | 2178864.79 | 7631.64 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 2287672.35 | 5203.27 | 31-AUG-06:03 | -1.5 |
September | 0.188426E+09 | 17000.64 | 25-SEP-05:01 | -1.2 |
October | 0.267523E+10 | 19427.38 | 30-OCT-04:01 | -14.4 |
November | 0.777436E+10 | 19828.66 | 27-NOV-04:52 | -25.6 |
December | 0.106456E+11 | 19816.44 | 04-DEC-02:12 | -20.9 |
Annual Sum or Average | 0.407991E+11 | |||
Minimum of Months | 0.00 | 0.00 | -28.3 | |
Maximum of Months | 0.106456E+11 | 20332.14 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.720892E+10 | 13456.08 | 29-JAN-09:22 | -25.9 |
February | 0.515281E+10 | 13435.36 | 26-FEB-05:02 | -25.6 |
March | 0.318813E+10 | 12936.08 | 01-MAR-05:11 | -28.3 |
April | 0.666837E+09 | 12247.29 | 01-APR-04:01 | -10.1 |
May | 2298997.13 | 5395.82 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 2658950.48 | 4555.08 | 31-AUG-06:03 | -1.5 |
September | 0.186894E+09 | 11335.61 | 30-SEP-05:01 | -4.5 |
October | 0.244994E+10 | 12841.36 | 30-OCT-04:01 | -14.4 |
November | 0.603793E+10 | 13109.43 | 27-NOV-04:52 | -25.6 |
December | 0.731262E+10 | 13086.43 | 04-DEC-02:12 | -20.9 |
Annual Sum or Average | 0.322090E+11 | |||
Minimum of Months | 0.00 | 0.00 | -28.3 | |
Maximum of Months | 0.731262E+10 | 13456.08 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.816808E+10 | 8165.57 | 01-JAN-06:42 | -15.5 |
February | 0.647296E+10 | 8155.80 | 27-FEB-04:22 | -35.2 |
March | 0.465417E+10 | 7957.77 | 06-MAR-05:11 | -20.4 |
April | 0.903286E+09 | 7712.63 | 03-APR-04:11 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 21424308.25 | 6183.16 | 28-SEP-06:02 | -2.8 |
October | 0.149450E+10 | 7640.17 | 30-OCT-04:01 | -14.4 |
November | 0.555178E+10 | 7861.90 | 13-NOV-03:42 | -19.9 |
December | 0.738286E+10 | 7906.53 | 04-DEC-04:52 | -20.0 |
Annual Sum or Average | 0.346491E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.2 | |
Maximum of Months | 0.816808E+10 | 8165.57 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.565814E+10 | 10249.41 | 01-JAN-06:42 | -15.5 |
February | 0.392443E+10 | 10279.32 | 27-FEB-04:22 | -35.2 |
March | 0.175992E+10 | 10046.44 | 06-MAR-05:11 | -20.4 |
April | 0.259861E+09 | 9610.73 | 03-APR-04:11 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 8460634.04 | 6635.47 | 28-SEP-06:02 | -2.8 |
October | 0.757262E+09 | 9724.34 | 30-OCT-04:01 | -14.4 |
November | 0.371850E+10 | 9973.67 | 13-NOV-05:01 | -20.2 |
December | 0.514557E+10 | 9953.09 | 11-DEC-05:11 | -19.0 |
Annual Sum or Average | 0.212321E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.2 | |
Maximum of Months | 0.565814E+10 | 10279.32 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155837E+11 | 22631.77 | 12-JAN-08:00 | -38.3 |
February | 0.105218E+11 | 22055.57 | 27-FEB-08:00 | -34.4 |
March | 0.771600E+10 | 20640.73 | 01-MAR-08:00 | -28.3 |
April | 0.233222E+10 | 18296.27 | 03-APR-06:10 | -21.5 |
May | 0.648013E+09 | 12306.86 | 04-MAY-06:10 | 4.18 |
June | 0.128372E+09 | 11663.75 | 02-JUN-06:05 | 7.15 |
July | 90923942.60 | 8382.11 | 05-JUL-06:06 | 8.30 |
August | 0.293193E+09 | 12758.74 | 31-AUG-06:10 | -1.5 |
September | 0.136904E+10 | 14193.54 | 29-SEP-07:00 | -5.6 |
October | 0.502136E+10 | 18182.63 | 31-OCT-07:00 | -19.4 |
November | 0.123930E+11 | 20466.09 | 29-NOV-08:00 | -28.9 |
December | 0.156440E+11 | 21528.72 | 15-DEC-08:00 | -33.9 |
Annual Sum or Average | 0.717415E+11 | |||
Minimum of Months | 90923942.60 | 8382.11 | -38.3 | |
Maximum of Months | 0.156440E+11 | 22631.77 | 8.30 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.574792E+10 | 10718.05 | 01-JAN-06:42 | -15.5 |
February | 0.431492E+10 | 10750.37 | 27-FEB-04:22 | -35.2 |
March | 0.257007E+10 | 10575.05 | 06-MAR-05:11 | -20.4 |
April | 0.293359E+09 | 9750.29 | 03-APR-04:11 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 12259476.64 | 6718.02 | 28-SEP-06:02 | -2.8 |
October | 0.941700E+09 | 10232.53 | 30-OCT-04:01 | -14.4 |
November | 0.371649E+10 | 10443.40 | 13-NOV-05:01 | -20.2 |
December | 0.516066E+10 | 10423.76 | 11-DEC-05:11 | -19.0 |
Annual Sum or Average | 0.227574E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.2 | |
Maximum of Months | 0.574792E+10 | 10750.37 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.713094E+10 | 8998.48 | 01-JAN-06:42 | -15.5 |
February | 0.483773E+10 | 8882.55 | 21-FEB-04:32 | -22.8 |
March | 0.281208E+10 | 8629.57 | 06-MAR-05:01 | -20.2 |
April | 0.444750E+09 | 8533.79 | 03-APR-04:11 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 36407240.96 | 7148.34 | 30-SEP-05:01 | -4.5 |
October | 0.174163E+10 | 8629.21 | 30-OCT-04:01 | -14.4 |
November | 0.549832E+10 | 8707.52 | 13-NOV-04:52 | -20.6 |
December | 0.696257E+10 | 8859.05 | 04-DEC-02:12 | -20.9 |
Annual Sum or Average | 0.294644E+11 | |||
Minimum of Months | 0.00 | 0.00 | -22.8 | |
Maximum of Months | 0.713094E+10 | 8998.48 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.473484E+10 | 11419.53 | 30-JAN-05:11 | -25.6 |
February | 0.278244E+10 | 11292.33 | 21-FEB-05:11 | -23.0 |
March | 0.114220E+10 | 10957.55 | 06-MAR-05:01 | -20.2 |
April | 0.181549E+09 | 10785.47 | 03-APR-04:11 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 21123180.31 | 7989.69 | 30-SEP-05:01 | -4.5 |
October | 0.953488E+09 | 10985.56 | 30-OCT-04:01 | -14.4 |
November | 0.360827E+10 | 10903.44 | 30-NOV-05:01 | -27.8 |
December | 0.471223E+10 | 11171.87 | 04-DEC-03:32 | -20.2 |
Annual Sum or Average | 0.181361E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.8 | |
Maximum of Months | 0.473484E+10 | 11419.53 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.630521E+10 | 17221.58 | 30-JAN-05:11 | -25.6 |
February | 0.314781E+10 | 16951.46 | 21-FEB-05:11 | -23.0 |
March | 0.135841E+10 | 16530.04 | 06-MAR-05:01 | -20.2 |
April | 0.228139E+09 | 15902.32 | 03-APR-04:11 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 24988806.80 | 10811.43 | 28-SEP-06:02 | -2.8 |
October | 0.108751E+10 | 16565.98 | 30-OCT-04:01 | -14.4 |
November | 0.432015E+10 | 16440.10 | 13-NOV-05:01 | -20.2 |
December | 0.671270E+10 | 16851.47 | 04-DEC-04:52 | -20.0 |
Annual Sum or Average | 0.231849E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.6 | |
Maximum of Months | 0.671270E+10 | 17221.58 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.481171E+10 | 11379.19 | 30-JAN-05:11 | -25.6 |
February | 0.307552E+10 | 11245.59 | 21-FEB-05:11 | -23.0 |
March | 0.157264E+10 | 10923.69 | 06-MAR-05:01 | -20.2 |
April | 0.216424E+09 | 10626.26 | 03-APR-04:11 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 25786612.55 | 8779.50 | 30-SEP-05:01 | -4.5 |
October | 0.110788E+10 | 10943.00 | 30-OCT-04:01 | -14.4 |
November | 0.359644E+10 | 10851.51 | 30-NOV-05:01 | -27.8 |
December | 0.472816E+10 | 11129.66 | 04-DEC-04:52 | -20.0 |
Annual Sum or Average | 0.191346E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.8 | |
Maximum of Months | 0.481171E+10 | 11379.19 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.910813E+09 | 1040.56 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.680428E+09 | 1040.56 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.633234E+09 | 1040.56 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.492170E+09 | 577.90 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.516884E+09 | 496.34 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.506059E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.478662E+09 | 525.87 | 26-JUL-14:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.548034E+09 | 543.08 | 18-AUG-15:00 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.535883E+09 | 987.44 | 28-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.670391E+09 | 1040.56 | 03-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.845374E+09 | 1040.56 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.924150E+09 | 1040.56 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.774208E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.478662E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.924150E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.557671E+09 | 658.76 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.415364E+09 | 658.76 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.395043E+09 | 658.76 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.312187E+09 | 314.23 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.332290E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.324553E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.306994E+09 | 314.23 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.349967E+09 | 344.78 | 18-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.336864E+09 | 556.95 | 28-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.412701E+09 | 658.76 | 03-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.511112E+09 | 658.76 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.578924E+09 | 658.76 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.483367E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.306994E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.578924E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.849388E+09 | 1040.56 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.628688E+09 | 1040.56 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.614060E+09 | 1040.56 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.494622E+09 | 577.69 | 04-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.522879E+09 | 496.34 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.511570E+09 | 496.34 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.483491E+09 | 496.34 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.550493E+09 | 496.34 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.527227E+09 | 944.98 | 28-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.634941E+09 | 1040.56 | 03-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.767295E+09 | 1040.56 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.890487E+09 | 1040.56 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.747514E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.483491E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.890487E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.562383E+09 | 658.71 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.410074E+09 | 658.71 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.393653E+09 | 658.71 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.313505E+09 | 461.13 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.326402E+09 | 314.21 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.320180E+09 | 314.21 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.302630E+09 | 342.36 | 25-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.345518E+09 | 342.48 | 07-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.336094E+09 | 626.76 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.410152E+09 | 658.71 | 03-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.511505E+09 | 658.71 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.581462E+09 | 658.71 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.481356E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.302630E+09 | 314.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.581462E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.907302E+09 | 1040.56 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.676747E+09 | 1040.56 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.631134E+09 | 1040.56 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.491556E+09 | 574.88 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.516572E+09 | 496.34 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.505820E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.478297E+09 | 496.34 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.547616E+09 | 538.56 | 18-AUG-15:00 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.534147E+09 | 984.55 | 28-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.665711E+09 | 1040.56 | 03-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.840735E+09 | 1040.56 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.923077E+09 | 1040.56 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.771871E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.478297E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.923077E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.556024E+09 | 658.76 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.413902E+09 | 658.76 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.394173E+09 | 658.76 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.311854E+09 | 314.23 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.331981E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.324263E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.306711E+09 | 314.23 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.349587E+09 | 342.17 | 18-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.336274E+09 | 550.48 | 28-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.411655E+09 | 658.76 | 03-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.508745E+09 | 658.76 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.578044E+09 | 658.76 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.482321E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.306711E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.578044E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.846435E+09 | 1040.56 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.626031E+09 | 1040.56 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.613256E+09 | 1040.56 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.493993E+09 | 574.65 | 04-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.522453E+09 | 496.34 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.511185E+09 | 496.34 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.483067E+09 | 496.34 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.549922E+09 | 496.34 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.526299E+09 | 939.38 | 28-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.633149E+09 | 1040.56 | 03-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.764577E+09 | 1040.56 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.886612E+09 | 1040.56 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.745698E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.483067E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.886612E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.560598E+09 | 658.71 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.407554E+09 | 658.71 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.392707E+09 | 658.71 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.313042E+09 | 455.12 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.326237E+09 | 314.21 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.320067E+09 | 314.21 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.302327E+09 | 339.76 | 25-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.345145E+09 | 339.88 | 07-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.335154E+09 | 625.23 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.408797E+09 | 658.71 | 03-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.508965E+09 | 658.71 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.580746E+09 | 658.71 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.480134E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.302327E+09 | 314.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.580746E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.910811E+09 | 1040.56 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.680425E+09 | 1040.56 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.633233E+09 | 1040.56 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.492169E+09 | 577.90 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.516883E+09 | 496.34 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.506058E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.478662E+09 | 525.86 | 26-JUL-14:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.548033E+09 | 543.07 | 18-AUG-15:00 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.535881E+09 | 987.44 | 28-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.670387E+09 | 1040.56 | 03-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.845370E+09 | 1040.56 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.924149E+09 | 1040.56 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.774206E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.478662E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.924149E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.557670E+09 | 658.76 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.415352E+09 | 658.76 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.395043E+09 | 658.76 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.312187E+09 | 314.23 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.332290E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.324552E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.306994E+09 | 314.23 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.349966E+09 | 344.77 | 18-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.336863E+09 | 556.96 | 28-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.412700E+09 | 658.76 | 03-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.511110E+09 | 658.76 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.578924E+09 | 658.76 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.483365E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.306994E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.578924E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.849387E+09 | 1040.56 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.628688E+09 | 1040.56 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.614059E+09 | 1040.56 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.494621E+09 | 577.68 | 04-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.522879E+09 | 496.34 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.511570E+09 | 496.34 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.483488E+09 | 496.34 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.550493E+09 | 496.34 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.527226E+09 | 944.99 | 28-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.634940E+09 | 1040.56 | 03-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.767295E+09 | 1040.56 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.890488E+09 | 1040.56 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.747513E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.483488E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.890488E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.562381E+09 | 658.71 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.410073E+09 | 658.71 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.393653E+09 | 658.71 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.313505E+09 | 461.11 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.326402E+09 | 314.21 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.320180E+09 | 314.21 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.302628E+09 | 342.35 | 25-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.345518E+09 | 342.48 | 07-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.336093E+09 | 626.76 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.410151E+09 | 658.71 | 03-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.511503E+09 | 658.71 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.581462E+09 | 658.71 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.481355E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.302628E+09 | 314.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.581462E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.910813E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.940195E+09 |
February | 0.901968E+09 | 0.680428E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754601E+09 |
March | 0.107774E+10 | 0.633234E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110549E+10 |
April | 0.956342E+09 | 0.492170E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122631E+10 |
May | 0.103597E+10 | 0.516884E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760435E+09 |
June | 0.103308E+10 | 0.506059E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1007875.55 | 0.458841E+09 |
July | 0.959235E+09 | 0.478662E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3099019.62 | 0.342129E+09 |
August | 0.107774E+10 | 0.548034E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 459034.19 | 0.396249E+09 |
September | 0.956342E+09 | 0.535883E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451356E+09 |
October | 0.994195E+09 | 0.670391E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.945567E+09 |
November | 0.984487E+09 | 0.845374E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345292E+09 |
December | 0.959235E+09 | 0.924150E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682558E+09 |
Annual Sum or Average | 0.119305E+11 | 0.774208E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4565929.36 | 0.840901E+10 |
Minimum of Months | 0.901968E+09 | 0.478662E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342129E+09 |
Maximum of Months | 0.107774E+10 | 0.924150E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3099019.62 | 0.122631E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.557671E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627767E+09 |
February | 0.571020E+09 | 0.415364E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503768E+09 |
March | 0.682301E+09 | 0.395043E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743403E+09 |
April | 0.605444E+09 | 0.312187E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841515E+09 |
May | 0.655854E+09 | 0.332290E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523794E+09 |
June | 0.654023E+09 | 0.324553E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 671929.20 | 0.310353E+09 |
July | 0.607275E+09 | 0.306994E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1921149.92 | 0.233191E+09 |
August | 0.682301E+09 | 0.349967E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 306029.97 | 0.270785E+09 |
September | 0.605444E+09 | 0.336864E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312422E+09 |
October | 0.629407E+09 | 0.412701E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634994E+09 |
November | 0.623262E+09 | 0.511112E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230219E+09 |
December | 0.607275E+09 | 0.578924E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455383E+09 |
Annual Sum or Average | 0.755301E+10 | 0.483367E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2899109.09 | 0.568759E+10 |
Minimum of Months | 0.571020E+09 | 0.306994E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230219E+09 |
Maximum of Months | 0.682301E+09 | 0.578924E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1921149.92 | 0.841515E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.849388E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.943079E+09 |
February | 0.901968E+09 | 0.628688E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760855E+09 |
March | 0.107774E+10 | 0.614060E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113860E+10 |
April | 0.956342E+09 | 0.494622E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130993E+10 |
May | 0.103597E+10 | 0.522879E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791497E+09 |
June | 0.103308E+10 | 0.511570E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1007842.01 | 0.465359E+09 |
July | 0.959235E+09 | 0.483491E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2653988.66 | 0.351410E+09 |
August | 0.107774E+10 | 0.550493E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 458435.64 | 0.414587E+09 |
September | 0.956342E+09 | 0.527227E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479042E+09 |
October | 0.994195E+09 | 0.634941E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970144E+09 |
November | 0.984487E+09 | 0.767295E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346297E+09 |
December | 0.959235E+09 | 0.890487E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683778E+09 |
Annual Sum or Average | 0.119305E+11 | 0.747514E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4120266.31 | 0.865458E+10 |
Minimum of Months | 0.901968E+09 | 0.483491E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346297E+09 |
Maximum of Months | 0.107774E+10 | 0.890487E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2653988.66 | 0.130993E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.562383E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627782E+09 |
February | 0.570983E+09 | 0.410074E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503679E+09 |
March | 0.682256E+09 | 0.393653E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741851E+09 |
April | 0.605404E+09 | 0.313505E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.859947E+09 |
May | 0.655811E+09 | 0.326402E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529065E+09 |
June | 0.653980E+09 | 0.320180E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 671935.58 | 0.312845E+09 |
July | 0.607235E+09 | 0.302630E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1707621.09 | 0.236091E+09 |
August | 0.682256E+09 | 0.345518E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 306035.21 | 0.273557E+09 |
September | 0.605404E+09 | 0.336094E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309137E+09 |
October | 0.629366E+09 | 0.410152E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632270E+09 |
November | 0.623221E+09 | 0.511505E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230281E+09 |
December | 0.607235E+09 | 0.581462E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455386E+09 |
Annual Sum or Average | 0.755252E+10 | 0.481356E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2685591.88 | 0.571189E+10 |
Minimum of Months | 0.570983E+09 | 0.302630E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230281E+09 |
Maximum of Months | 0.682256E+09 | 0.581462E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1707621.09 | 0.859947E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.907302E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504333E+09 |
February | 0.901968E+09 | 0.676747E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404290E+09 |
March | 0.107774E+10 | 0.631134E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598137E+09 |
April | 0.956342E+09 | 0.491556E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659477E+09 |
May | 0.103597E+10 | 0.516572E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398590E+09 |
June | 0.103308E+10 | 0.505820E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 555313.20 | 0.241107E+09 |
July | 0.959235E+09 | 0.478297E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1942640.03 | 0.180395E+09 |
August | 0.107774E+10 | 0.547616E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 259882.75 | 0.217810E+09 |
September | 0.956342E+09 | 0.534147E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257722E+09 |
October | 0.994195E+09 | 0.665711E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537821E+09 |
November | 0.984487E+09 | 0.840735E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188789E+09 |
December | 0.959235E+09 | 0.923077E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368537E+09 |
Annual Sum or Average | 0.119305E+11 | 0.771871E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2757835.97 | 0.455701E+10 |
Minimum of Months | 0.901968E+09 | 0.478297E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180395E+09 |
Maximum of Months | 0.107774E+10 | 0.923077E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1942640.03 | 0.659477E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.556024E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336528E+09 |
February | 0.571020E+09 | 0.413902E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270064E+09 |
March | 0.682301E+09 | 0.394173E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404705E+09 |
April | 0.605444E+09 | 0.311854E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463661E+09 |
May | 0.655854E+09 | 0.331981E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286458E+09 |
June | 0.654023E+09 | 0.324263E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 370210.71 | 0.167351E+09 |
July | 0.607275E+09 | 0.306711E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1110070.30 | 0.126989E+09 |
August | 0.682301E+09 | 0.349587E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173254.99 | 0.151500E+09 |
September | 0.605444E+09 | 0.336274E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181104E+09 |
October | 0.629407E+09 | 0.411655E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364470E+09 |
November | 0.623262E+09 | 0.508745E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125562E+09 |
December | 0.607275E+09 | 0.578044E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245298E+09 |
Annual Sum or Average | 0.755301E+10 | 0.482321E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1653536.00 | 0.312369E+10 |
Minimum of Months | 0.571020E+09 | 0.306711E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125562E+09 |
Maximum of Months | 0.682301E+09 | 0.578044E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1110070.30 | 0.463661E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.846435E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106802E+11 |
February | 0.901968E+09 | 0.626031E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841149E+10 |
March | 0.107774E+10 | 0.613256E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939177E+10 |
April | 0.956342E+09 | 0.493993E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552700E+10 |
May | 0.103597E+10 | 0.522453E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331769E+10 |
June | 0.103308E+10 | 0.511185E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29067516.54 | 0.193036E+10 |
July | 0.959235E+09 | 0.483067E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43224057.16 | 0.146872E+10 |
August | 0.107774E+10 | 0.549922E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10101319.76 | 0.263927E+10 |
September | 0.956342E+09 | 0.526299E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404149E+10 |
October | 0.994195E+09 | 0.633149E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686158E+10 |
November | 0.984487E+09 | 0.764577E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103035E+11 |
December | 0.959235E+09 | 0.886612E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107925E+11 |
Annual Sum or Average | 0.119305E+11 | 0.745698E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82392893.47 | 0.753655E+11 |
Minimum of Months | 0.901968E+09 | 0.483067E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146872E+10 |
Maximum of Months | 0.107774E+10 | 0.886612E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43224057.16 | 0.107925E+11 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.560598E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336503E+09 |
February | 0.570983E+09 | 0.407554E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269790E+09 |
March | 0.682256E+09 | 0.392707E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401768E+09 |
April | 0.605404E+09 | 0.313042E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472756E+09 |
May | 0.655811E+09 | 0.326237E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283901E+09 |
June | 0.653980E+09 | 0.320067E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 370219.31 | 0.168015E+09 |
July | 0.607235E+09 | 0.302327E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 966596.07 | 0.126478E+09 |
August | 0.682256E+09 | 0.345145E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173260.23 | 0.151986E+09 |
September | 0.605404E+09 | 0.335154E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178255E+09 |
October | 0.629366E+09 | 0.408797E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360385E+09 |
November | 0.623221E+09 | 0.508965E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125640E+09 |
December | 0.607235E+09 | 0.580746E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245294E+09 |
Annual Sum or Average | 0.755252E+10 | 0.480134E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1510075.61 | 0.312077E+10 |
Minimum of Months | 0.570983E+09 | 0.302327E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125640E+09 |
Maximum of Months | 0.682256E+09 | 0.580746E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 966596.07 | 0.472756E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.910811E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791124E+09 |
February | 0.901968E+09 | 0.680425E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637700E+09 |
March | 0.107774E+10 | 0.633233E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.947857E+09 |
April | 0.956342E+09 | 0.492169E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107203E+10 |
May | 0.103597E+10 | 0.516883E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662398E+09 |
June | 0.103308E+10 | 0.506058E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 854159.34 | 0.394408E+09 |
July | 0.959235E+09 | 0.478662E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2697991.09 | 0.292908E+09 |
August | 0.107774E+10 | 0.548033E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 394406.82 | 0.344892E+09 |
September | 0.956342E+09 | 0.535881E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403067E+09 |
October | 0.994195E+09 | 0.670387E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826845E+09 |
November | 0.984487E+09 | 0.845370E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292266E+09 |
December | 0.959235E+09 | 0.924149E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575373E+09 |
Annual Sum or Average | 0.119305E+11 | 0.774206E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3946557.26 | 0.724087E+10 |
Minimum of Months | 0.901968E+09 | 0.478662E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292266E+09 |
Maximum of Months | 0.107774E+10 | 0.924149E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2697991.09 | 0.107203E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.557670E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526837E+09 |
February | 0.421807E+09 | 0.415352E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424931E+09 |
March | 0.502994E+09 | 0.395043E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640017E+09 |
April | 0.447140E+09 | 0.312187E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736105E+09 |
May | 0.484071E+09 | 0.332290E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454247E+09 |
June | 0.482240E+09 | 0.324552E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 546646.70 | 0.266727E+09 |
July | 0.448971E+09 | 0.306994E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1643445.81 | 0.199575E+09 |
August | 0.502994E+09 | 0.349966E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 262931.31 | 0.234814E+09 |
September | 0.447140E+09 | 0.336863E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277434E+09 |
October | 0.465148E+09 | 0.412700E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556434E+09 |
November | 0.460569E+09 | 0.511110E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194247E+09 |
December | 0.448971E+09 | 0.578924E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382589E+09 |
Annual Sum or Average | 0.557719E+10 | 0.483365E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2453023.82 | 0.489396E+10 |
Minimum of Months | 0.421807E+09 | 0.306994E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194247E+09 |
Maximum of Months | 0.502994E+09 | 0.578924E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1643445.81 | 0.736105E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.849387E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792861E+09 |
February | 0.901968E+09 | 0.628688E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645322E+09 |
March | 0.107774E+10 | 0.614059E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.983186E+09 |
April | 0.956342E+09 | 0.494621E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114348E+10 |
May | 0.103597E+10 | 0.522879E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685162E+09 |
June | 0.103308E+10 | 0.511570E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 854127.14 | 0.399210E+09 |
July | 0.959235E+09 | 0.483488E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2316665.69 | 0.300032E+09 |
August | 0.107774E+10 | 0.550493E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 393369.67 | 0.358076E+09 |
September | 0.956342E+09 | 0.527226E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423146E+09 |
October | 0.994195E+09 | 0.634940E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.852061E+09 |
November | 0.984487E+09 | 0.767295E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293759E+09 |
December | 0.959235E+09 | 0.890488E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576021E+09 |
Annual Sum or Average | 0.119305E+11 | 0.747513E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3564162.50 | 0.745231E+10 |
Minimum of Months | 0.901968E+09 | 0.483488E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293759E+09 |
Maximum of Months | 0.107774E+10 | 0.890488E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2316665.69 | 0.114348E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.562381E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527301E+09 |
February | 0.570983E+09 | 0.410073E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425033E+09 |
March | 0.682256E+09 | 0.393653E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637217E+09 |
April | 0.605404E+09 | 0.313505E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750597E+09 |
May | 0.655811E+09 | 0.326402E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458196E+09 |
June | 0.653980E+09 | 0.320180E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 569455.70 | 0.268441E+09 |
July | 0.607235E+09 | 0.302628E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1448060.03 | 0.201528E+09 |
August | 0.682256E+09 | 0.345518E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 262948.17 | 0.236772E+09 |
September | 0.605404E+09 | 0.336093E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274454E+09 |
October | 0.629366E+09 | 0.410151E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552993E+09 |
November | 0.623221E+09 | 0.511503E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194605E+09 |
December | 0.607235E+09 | 0.581462E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383048E+09 |
Annual Sum or Average | 0.755252E+10 | 0.481355E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2280463.90 | 0.491019E+10 |
Minimum of Months | 0.570983E+09 | 0.302628E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194605E+09 |
Maximum of Months | 0.682256E+09 | 0.581462E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1448060.03 | 0.750597E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103383E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.843511E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128546E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148391E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892085E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567456.10 | 0.520689E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2257607.77 | 0.386783E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128587.80 | 0.468946E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559432E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114498E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392896E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758850E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2953651.68 | 0.977138E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386783E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2257607.77 | 0.148391E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130517E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106518E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161487E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185700E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113452E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 713256.52 | 0.665596E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2884827.64 | 0.494260E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168172.51 | 0.593474E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690594E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139921E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490523E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.955236E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3766256.66 | 0.122656E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490523E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2884827.64 | 0.185700E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136857E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111166E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166779E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191245E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119208E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479537.78 | 0.713709E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1887960.58 | 0.536846E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42023.97 | 0.622721E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.699044E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141602E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506174E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.998848E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2409522.34 | 0.127459E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506174E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1887960.58 | 0.191245E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4207.54 | 28-JAN-23:51 |
February | 1306.65 | 01-FEB-10:09 | 1040.56 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2499.52 | 25-FEB-00:52 |
March | 1306.65 | 01-MAR-10:09 | 1040.56 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1886.80 | 14-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 577.90 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2559.23 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1235.34 | 26-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.16 | 30-JUN-15:00 | 1183.49 | 24-JUN-21:00 |
July | 1306.65 | 03-JUL-09:09 | 525.87 | 26-JUL-14:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.46 | 21-JUL-16:00 | 899.82 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 543.08 | 18-AUG-15:00 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.41 | 11-AUG-16:00 | 967.31 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 987.44 | 28-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 734.85 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 03-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1560.57 | 21-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1344.40 | 09-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1436.38 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 734.85 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 144.46 | 4207.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2803.72 | 28-JAN-23:51 |
February | 827.22 | 01-FEB-10:09 | 658.76 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1665.71 | 25-FEB-00:52 |
March | 827.22 | 01-MAR-10:09 | 658.76 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1258.24 | 14-MAR-21:02 |
April | 827.22 | 03-APR-09:09 | 314.23 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1704.26 | 01-APR-18:55 |
May | 827.22 | 01-MAY-09:09 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 829.46 | 26-MAY-22:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.77 | 30-JUN-15:00 | 788.61 | 24-JUN-21:00 |
July | 827.22 | 03-JUL-09:09 | 314.23 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.31 | 21-JUL-16:00 | 603.92 | 04-JUL-17:00 |
August | 827.22 | 01-AUG-09:09 | 344.78 | 18-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 11-AUG-16:00 | 644.83 | 30-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 556.95 | 28-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 496.88 | 04-SEP-14:00 |
October | 827.22 | 02-OCT-09:09 | 658.76 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1042.38 | 21-OCT-04:04 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 895.94 | 09-NOV-22:01 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 956.91 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496.88 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 96.31 | 2803.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4210.28 | 28-JAN-23:51 |
February | 1306.65 | 01-FEB-10:09 | 1040.56 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2501.37 | 25-FEB-00:52 |
March | 1306.65 | 01-MAR-10:09 | 1040.56 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1895.52 | 12-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 577.69 | 04-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2809.33 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1254.29 | 26-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.16 | 30-JUN-15:00 | 1199.79 | 18-JUN-13:53 |
July | 1306.65 | 03-JUL-09:09 | 496.34 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.46 | 21-JUL-16:00 | 918.54 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 496.34 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.41 | 11-AUG-16:00 | 975.19 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 944.98 | 28-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 758.25 | 30-SEP-21:00 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 03-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1560.58 | 21-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1345.46 | 09-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1436.79 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 758.25 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 144.46 | 4210.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2804.21 | 28-JAN-23:51 |
February | 827.17 | 01-FEB-10:09 | 658.71 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1665.33 | 25-FEB-00:52 |
March | 827.17 | 01-MAR-10:09 | 658.71 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1258.44 | 14-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 461.13 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2078.24 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 314.21 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 828.70 | 26-MAY-22:00 |
June | 827.17 | 01-JUN-09:09 | 314.21 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.77 | 30-JUN-15:00 | 787.09 | 24-JUN-21:00 |
July | 827.17 | 03-JUL-09:09 | 342.36 | 25-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.31 | 21-JUL-16:00 | 612.31 | 04-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 342.48 | 07-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 11-AUG-16:00 | 644.77 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 626.76 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 488.61 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 658.71 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1041.66 | 21-OCT-04:04 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 896.10 | 09-NOV-22:01 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 957.05 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.61 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 96.31 | 2804.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2257.74 | 28-JAN-23:52 |
February | 1306.65 | 01-FEB-10:09 | 1040.56 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1339.70 | 25-FEB-00:54 |
March | 1306.65 | 01-MAR-10:09 | 1040.56 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1003.38 | 14-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 574.88 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1399.79 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 679.04 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.30 | 30-JUN-15:00 | 664.09 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 496.34 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.12 | 29-JUL-19:55 | 481.92 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 538.56 | 18-AUG-15:00 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 | 11-AUG-16:00 | 555.42 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 984.55 | 28-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 433.08 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 03-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 858.48 | 21-OCT-04:01 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 732.88 | 10-NOV-01:53 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 769.69 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.08 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 81.12 | 2257.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1505.15 | 28-JAN-23:52 |
February | 827.22 | 01-FEB-10:09 | 658.76 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 893.12 | 25-FEB-00:54 |
March | 827.22 | 01-MAR-10:09 | 658.76 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 669.82 | 14-MAR-21:02 |
April | 827.22 | 03-APR-09:09 | 314.23 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 947.25 | 01-APR-18:55 |
May | 827.22 | 01-MAY-09:09 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 471.72 | 26-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.86 | 30-JUN-15:00 | 447.71 | 25-JUN-06:00 |
July | 827.22 | 03-JUL-09:09 | 314.23 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 21-JUL-16:00 | 331.08 | 04-JUL-17:00 |
August | 827.22 | 01-AUG-09:09 | 342.17 | 18-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 | 11-AUG-16:00 | 376.40 | 30-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 550.48 | 28-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 302.19 | 04-SEP-14:00 |
October | 827.22 | 02-OCT-09:09 | 658.76 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 573.96 | 21-OCT-04:01 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 486.94 | 10-NOV-01:53 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 513.22 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.19 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 1505.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 55717.28 | 12-JAN-12:01 |
February | 1306.65 | 01-FEB-10:09 | 1040.56 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 50524.51 | 27-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 1040.56 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 45581.19 | 01-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 574.65 | 04-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 38043.34 | 03-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 15195.21 | 16-MAY-07:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1668.35 | 21-JUN-17:00 | 12192.87 | 01-JUN-06:02 |
July | 1306.65 | 03-JUL-09:09 | 496.34 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3959.08 | 21-JUL-16:10 | 11766.04 | 17-JUL-06:01 |
August | 1306.65 | 01-AUG-09:09 | 496.34 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1277.73 | 11-AUG-16:10 | 19942.16 | 31-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 939.38 | 28-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 20907.74 | 29-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 03-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 34957.13 | 27-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 45488.81 | 29-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 51461.83 | 15-DEC-12:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11766.04 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 3959.08 | 55717.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1505.15 | 28-JAN-23:52 |
February | 827.17 | 01-FEB-10:09 | 658.71 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 893.31 | 25-FEB-00:54 |
March | 827.17 | 01-MAR-10:09 | 658.71 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 669.52 | 14-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 455.12 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1113.32 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 314.21 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 457.51 | 26-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 314.21 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.86 | 30-JUN-15:00 | 443.53 | 25-JUN-06:00 |
July | 827.17 | 03-JUL-09:09 | 339.76 | 25-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 21-JUL-16:00 | 333.42 | 04-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 339.88 | 07-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 | 11-AUG-16:00 | 375.46 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 625.23 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 295.53 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 658.71 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 570.63 | 21-OCT-04:01 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 487.78 | 10-NOV-01:53 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 513.20 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.53 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 1505.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3537.00 | 28-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 1040.56 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2090.54 | 25-FEB-00:52 |
March | 1306.65 | 01-MAR-10:09 | 1040.56 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1574.82 | 14-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 577.90 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2223.22 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1093.35 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.70 | 30-JUN-15:00 | 1054.85 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 525.86 | 26-JUL-14:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.83 | 21-JUL-16:00 | 779.66 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 543.07 | 18-AUG-15:00 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 | 11-AUG-16:00 | 857.26 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 987.44 | 28-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 672.59 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 03-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1298.24 | 21-OCT-04:01 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1125.69 | 10-NOV-01:53 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1206.14 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 672.59 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 120.83 | 3537.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 658.76 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2357.99 | 28-JAN-23:59 |
February | 805.43 | 01-FEB-08:09 | 658.76 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1393.13 | 25-FEB-00:52 |
March | 805.43 | 01-MAR-08:09 | 658.76 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1050.38 | 14-MAR-21:02 |
April | 805.43 | 03-APR-07:10 | 314.23 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1482.38 | 01-APR-18:55 |
May | 805.43 | 01-MAY-07:10 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 732.15 | 26-MAY-02:00 |
June | 805.43 | 01-JUN-07:10 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 30-JUN-15:00 | 703.25 | 25-JUN-06:00 |
July | 805.43 | 03-JUL-07:10 | 314.23 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.56 | 21-JUL-16:00 | 523.41 | 04-JUL-17:00 |
August | 805.43 | 01-AUG-07:10 | 344.77 | 18-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.08 | 11-AUG-16:00 | 571.01 | 30-AUG-01:00 |
September | 805.43 | 01-SEP-07:10 | 556.96 | 28-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 454.00 | 04-SEP-14:00 |
October | 805.43 | 02-OCT-07:10 | 658.76 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 864.02 | 21-OCT-04:01 |
November | 805.43 | 01-NOV-07:10 | 658.76 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 747.46 | 09-NOV-22:01 |
December | 805.43 | 01-DEC-08:09 | 658.76 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 804.25 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.00 | |||||
Maximum of Months | 805.43 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 80.56 | 2357.99 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3537.00 | 28-JAN-23:57 |
February | 1306.65 | 01-FEB-10:09 | 1040.56 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2092.33 | 25-FEB-00:52 |
March | 1306.65 | 01-MAR-10:09 | 1040.56 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1710.28 | 12-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 577.68 | 04-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2429.08 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1107.71 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.70 | 30-JUN-15:00 | 1045.57 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 496.34 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.83 | 21-JUL-16:00 | 795.58 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 496.34 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 | 11-AUG-16:00 | 862.33 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 944.99 | 28-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 686.46 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 03-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1325.15 | 22-OCT-18:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1135.64 | 10-NOV-01:53 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1205.97 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 686.46 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 120.83 | 3537.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2357.99 | 28-JAN-23:57 |
February | 827.17 | 01-FEB-10:09 | 658.71 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1392.87 | 25-FEB-00:52 |
March | 827.17 | 01-MAR-10:09 | 658.71 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1050.40 | 14-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 461.11 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1791.60 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 314.21 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 732.01 | 26-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 314.21 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 30-JUN-15:00 | 692.16 | 25-JUN-06:00 |
July | 827.17 | 03-JUL-09:09 | 342.35 | 25-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.56 | 21-JUL-16:00 | 530.68 | 04-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 342.48 | 07-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.08 | 11-AUG-16:00 | 570.68 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 626.76 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 447.41 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 658.71 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 862.20 | 21-OCT-04:01 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 748.65 | 10-NOV-01:53 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 804.21 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 447.41 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 80.56 | 2357.99 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4711.95 | 28-JAN-23:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2840.38 | 25-FEB-00:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2005.82 | 25-MAR-04:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3141.23 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1506.89 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.82 | 30-JUN-15:00 | 1447.77 | 25-JUN-06:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.54 | 21-JUL-16:00 | 990.68 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.65 | 11-AUG-16:00 | 1183.39 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 906.96 | 04-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1856.75 | 21-OCT-04:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1561.47 | 10-NOV-01:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1626.65 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 906.96 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.54 | 4711.95 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 5902.43 | 28-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3610.61 | 25-FEB-00:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2544.52 | 14-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3919.40 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1915.19 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.84 | 30-JUN-15:00 | 1803.51 | 25-JUN-06:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.10 | 21-JUL-16:00 | 1244.89 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.23 | 11-AUG-16:00 | 1496.21 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1086.14 | 04-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2277.65 | 21-OCT-04:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1960.93 | 10-NOV-01:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2069.56 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1086.14 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.10 | 5902.43 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 6056.33 | 28-JAN-23:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3741.36 | 25-FEB-00:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2746.34 | 14-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4233.46 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1899.17 | 26-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.99 | 30-JUN-15:00 | 1842.05 | 18-JUN-13:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.00 | 21-JUL-16:00 | 1420.16 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.75 | 11-AUG-16:00 | 1451.93 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1158.77 | 04-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2254.88 | 21-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1983.71 | 10-NOV-01:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2126.60 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1158.77 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.00 | 6056.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6178.88 | 27-JAN-17:00 | 6035.01 | 4936.01 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7749.18 | 10-FEB-17:00 | 6035.01 | 4936.01 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12277.47 | 24-MAR-07:30 | 12070.02 | 9872.03 | 36370.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23018.27 | 28-APR-05:03 | 2541.06 | 846.94 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38432.10 | 15-MAY-06:02 | 7623.17 | 9872.16 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41711.17 | 05-JUN-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 42488.27 | 17-JUL-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 42533.23 | 14-AUG-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 36670.18 | 01-SEP-06:02 | 7623.17 | 9872.16 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16449.60 | 03-OCT-07:06 | 42245.05 | 34552.10 | 127296.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7397.72 | 03-NOV-16:00 | 6035.01 | 4936.01 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5959.73 | 22-DEC-17:00 | 6035.01 | 4936.01 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5959.73 | 2541.06 | 846.94 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42533.23 | 42245.05 | 34552.10 | 127296.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1219.29 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 999.88 |
March | 542.42 | 22-MAR-17:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.76 |
April | 3850.16 | 21-APR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.38 |
May | 6746.65 | 31-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.75 |
June | 7813.34 | 29-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.44 | 0.00 |
July | 7881.34 | 21-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.35 | 0.00 |
August | 6693.81 | 10-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.21 |
September | 2696.75 | 07-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.92 |
October | 349.10 | 03-OCT-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.29 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1108.80 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7881.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.35 | 1219.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3129.00 | 11-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2944.33 | 18-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1162.13 |
March | 3340.99 | 03-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1294.94 |
April | 2155.80 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551.19 |
May | 3292.50 | 31-MAY-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.18 |
June | 4273.61 | 22-JUN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.14 |
July | 5984.68 | 24-JUL-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.06 |
August | 3706.77 | 11-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.23 | 0.00 |
September | 1166.89 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.39 |
October | 2398.48 | 27-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2071.66 |
November | 3204.63 | 30-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3214.70 | 22-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1166.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5984.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.23 | 2071.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3411.20 | 26-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.92 |
February | 4057.63 | 18-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 922.19 |
March | 3943.07 | 03-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1020.32 |
April | 3064.65 | 05-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.89 |
May | 3394.16 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.90 |
June | 5246.73 | 12-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.77 |
July | 6387.36 | 24-JUL-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.18 |
August | 4314.78 | 11-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.77 | 0.00 |
September | 2601.35 | 01-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.76 |
October | 2186.09 | 27-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.37 |
November | 3103.78 | 30-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3362.79 | 14-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2186.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6387.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.77 | 1020.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 4722.03 | 20-JAN-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5385.30 | 09-FEB-15:10 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5980.89 | 22-MAR-15:40 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12199.85 | 21-APR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25253.39 | 15-MAY-06:02 | 7623.17 | 9872.16 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31430.13 | 05-JUN-06:03 | 8893.70 | 11517.52 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31707.32 | 24-JUL-06:03 | 7623.17 | 9872.16 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28792.56 | 07-AUG-06:01 | 8893.70 | 11517.52 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12472.56 | 01-SEP-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6912.45 | 05-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4919.06 | 02-NOV-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4548.31 | 21-DEC-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 4548.31 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31707.32 | 8893.70 | 11517.52 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 3992.10 | 21-JAN-17:02 | 1588.16 | 1371.08 | 11347.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4959.11 | 09-FEB-16:10 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5834.53 | 22-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11979.20 | 21-APR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16123.63 | 31-MAY-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26583.27 | 12-JUN-06:01 | 8893.70 | 11517.52 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29485.98 | 24-JUL-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16308.11 | 01-AUG-14:40 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11434.54 | 01-SEP-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6063.92 | 04-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4223.08 | 02-NOV-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3985.52 | 23-DEC-17:02 | 1588.16 | 1371.08 | 11347.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 3985.52 | 1588.16 | 1371.08 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29485.98 | 8893.70 | 11517.52 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 883.50 | 21-JAN-17:02 | 334.80 | 289.04 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.06 |
February | 891.90 | 11-FEB-17:03 | 267.84 | 231.23 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.05 |
March | 1159.35 | 22-MAR-15:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2177.65 | 28-APR-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.11 |
May | 9226.02 | 31-MAY-06:02 | 1339.19 | 827.25 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.41 |
June | 10252.34 | 29-JUN-05:12 | 669.60 | 275.74 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.96 |
July | 10391.06 | 11-JUL-05:12 | 669.60 | 275.74 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.67 |
August | 4682.08 | 02-AUG-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.21 |
September | 2217.32 | 01-SEP-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.40 |
October | 1185.11 | 04-OCT-15:50 | 1272.23 | 562.54 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.83 |
November | 880.94 | 04-NOV-16:02 | 334.80 | 289.04 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 883.40 | 23-DEC-17:02 | 334.80 | 289.04 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 880.94 | 267.84 | 231.23 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10391.06 | 1339.19 | 827.25 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 508.06 | 21-JAN-17:02 | 211.95 | 182.98 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.71 |
February | 579.95 | 09-FEB-11:25 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.06 |
March | 1815.11 | 22-MAR-10:30 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.01 |
April | 5719.86 | 22-APR-09:15 | 522.45 | 209.49 | 1009.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.14 |
May | 15417.85 | 14-MAY-09:41 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.31 |
June | 12403.21 | 13-JUN-05:12 | 423.91 | 174.57 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.24 |
July | 14328.11 | 23-JUL-09:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.40 |
August | 11392.69 | 10-AUG-06:01 | 1186.95 | 733.21 | 2826.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.31 |
September | 4591.13 | 10-SEP-10:33 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.79 |
October | 1640.57 | 03-OCT-09:45 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.61 |
November | 506.51 | 04-NOV-16:02 | 211.95 | 182.98 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 507.79 | 23-DEC-17:02 | 211.95 | 182.98 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 506.51 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15417.85 | 1654.44 | 733.21 | 2826.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 980.83 | 25-JAN-13:40 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.40 |
February | 3840.00 | 15-FEB-13:50 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7766.89 | 31-MAR-13:50 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.02 |
April | 13905.01 | 23-APR-13:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 748.57 |
May | 23654.11 | 14-MAY-12:22 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.16 |
June | 17732.67 | 18-JUN-13:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650.14 |
July | 23408.46 | 23-JUL-13:32 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.76 |
August | 22365.73 | 27-AUG-13:22 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.45 |
September | 10571.85 | 07-SEP-14:30 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.75 |
October | 8880.66 | 03-OCT-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.47 |
November | 1539.01 | 08-NOV-13:40 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.76 |
December | 804.37 | 23-DEC-17:02 | 334.80 | 289.04 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 804.37 | 267.84 | 110.30 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23654.11 | 1306.65 | 496.34 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 748.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 508.50 | 21-JAN-17:02 | 211.94 | 182.97 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.71 |
February | 575.87 | 09-FEB-07:04 | 847.76 | 1097.87 | 2019.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.87 |
March | 864.43 | 22-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9927.06 | 22-APR-17:42 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 680.99 |
May | 14987.22 | 14-MAY-18:22 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.11 |
June | 13862.89 | 10-JUN-17:05 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.13 |
July | 10943.38 | 09-JUL-19:53 | 0.00 | 69.82 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.63 |
August | 11520.18 | 27-AUG-17:22 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.32 |
September | 6048.09 | 02-SEP-17:43 | 127.16 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.84 |
October | 875.50 | 03-OCT-15:20 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.80 |
November | 508.09 | 04-NOV-16:02 | 211.94 | 182.97 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 508.44 | 23-DEC-17:02 | 211.94 | 182.97 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 508.09 | 0.00 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14987.22 | 847.76 | 1097.87 | 2019.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 680.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 815.62 | 21-JAN-17:02 | 334.80 | 289.04 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.53 |
February | 816.70 | 11-FEB-17:03 | 267.84 | 231.23 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.18 |
March | 891.44 | 22-MAR-15:10 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1250.72 | 28-APR-15:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.42 |
May | 2654.97 | 31-MAY-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.22 |
June | 7803.66 | 13-JUN-05:12 | 669.60 | 275.74 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.94 |
July | 8442.33 | 11-JUL-05:14 | 669.60 | 275.74 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.08 |
August | 6838.10 | 02-AUG-06:01 | 1874.87 | 1158.15 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.01 |
September | 1838.80 | 01-SEP-15:50 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.06 |
October | 1162.28 | 06-OCT-15:00 | 1272.23 | 546.51 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.69 |
November | 827.76 | 04-NOV-16:02 | 334.80 | 289.04 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 820.37 | 23-DEC-17:02 | 334.80 | 289.04 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 815.62 | 267.84 | 231.23 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8442.33 | 1874.87 | 1158.15 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 511.56 | 21-JAN-17:02 | 211.95 | 182.98 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.69 |
February | 554.42 | 15-FEB-10:40 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.05 |
March | 1250.22 | 31-MAR-09:10 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 |
April | 3829.24 | 22-APR-08:30 | 254.35 | 104.74 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.20 |
May | 10163.68 | 14-MAY-09:31 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.58 |
June | 10388.40 | 13-JUN-05:12 | 423.91 | 174.57 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.62 |
July | 11723.92 | 23-JUL-10:01 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.72 |
August | 9140.26 | 10-AUG-06:01 | 1186.95 | 733.21 | 2826.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.60 |
September | 8658.48 | 10-SEP-08:32 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.08 |
October | 2120.55 | 03-OCT-09:30 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.08 |
November | 549.83 | 02-NOV-06:03 | 1695.64 | 2195.89 | 4038.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 514.16 | 23-DEC-17:02 | 211.95 | 182.98 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 511.56 | 169.56 | 69.83 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11723.92 | 1695.64 | 2195.89 | 4038.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 807.71 | 21-JAN-17:02 | 334.80 | 289.04 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 |
February | 1074.66 | 18-FEB-13:30 | 133.92 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.79 |
March | 1291.47 | 11-MAR-13:50 | 133.92 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.89 |
April | 8060.63 | 22-APR-14:00 | 137.54 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.80 |
May | 12473.62 | 14-MAY-12:52 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.73 |
June | 12806.63 | 18-JUN-12:22 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.22 |
July | 18610.98 | 23-JUL-13:21 | 602.64 | 248.17 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.87 |
August | 15621.42 | 27-AUG-13:22 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.05 |
September | 10449.45 | 10-SEP-11:53 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.35 |
October | 5761.99 | 03-OCT-13:40 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1485.11 |
November | 927.57 | 08-NOV-13:14 | 6361.16 | 2481.72 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4252.54 |
December | 806.98 | 23-DEC-17:02 | 334.80 | 289.04 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 806.98 | 133.92 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 | |
Maximum of Months | 18610.98 | 6361.16 | 2481.72 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4252.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 510.35 | 21-JAN-17:02 | 211.94 | 182.97 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.69 |
February | 511.39 | 11-FEB-17:03 | 169.55 | 146.38 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.77 |
March | 738.83 | 31-MAR-17:01 | 847.76 | 1047.37 | 4038.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.00 |
April | 5231.35 | 21-APR-18:20 | 84.78 | 104.74 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.23 |
May | 6129.65 | 14-MAY-19:53 | 0.00 | 69.82 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.37 |
June | 7813.15 | 10-JUN-17:07 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.84 |
July | 8438.72 | 09-JUL-19:42 | 0.00 | 69.82 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.80 |
August | 7307.65 | 27-AUG-17:22 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.62 |
September | 3564.34 | 08-SEP-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.55 |
October | 853.89 | 03-OCT-15:20 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.35 |
November | 519.07 | 04-NOV-16:02 | 211.94 | 182.97 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 513.34 | 23-DEC-17:02 | 211.94 | 182.97 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 510.35 | 0.00 | 69.82 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8438.72 | 847.76 | 1047.37 | 4038.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 818.83 | 21-JAN-17:02 | 334.80 | 289.04 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.41 |
February | 823.48 | 11-FEB-17:03 | 267.84 | 231.23 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.73 |
March | 1108.39 | 22-MAR-15:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2442.93 | 28-APR-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.83 |
May | 8872.10 | 31-MAY-05:12 | 669.60 | 275.74 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.90 |
June | 9262.72 | 07-JUN-05:12 | 669.60 | 275.74 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.85 |
July | 9384.69 | 11-JUL-05:12 | 669.60 | 275.74 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.86 |
August | 7811.98 | 02-AUG-06:01 | 1874.87 | 1158.15 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.30 |
September | 2632.85 | 01-SEP-13:40 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.74 |
October | 1194.00 | 04-OCT-16:00 | 1272.23 | 575.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.49 |
November | 818.31 | 04-NOV-16:02 | 334.80 | 289.04 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 816.82 | 23-DEC-17:02 | 334.80 | 289.04 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 816.82 | 267.84 | 231.23 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9384.69 | 1874.87 | 1158.15 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 571.85 | 20-JAN-13:02 | 8054.28 | 4912.06 | 9085.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 673.15 | 15-FEB-11:10 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.06 |
March | 7397.03 | 31-MAR-12:01 | 8054.28 | 3142.27 | 9085.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.66 |
April | 7709.28 | 28-APR-12:01 | 5638.00 | 2199.59 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.12 |
May | 14026.04 | 14-MAY-09:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.24 |
June | 12477.44 | 19-JUN-05:12 | 423.91 | 174.57 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.77 |
July | 14524.74 | 09-JUL-07:02 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.79 |
August | 11029.48 | 27-AUG-10:32 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.59 |
September | 7408.63 | 08-SEP-12:01 | 5638.00 | 2199.59 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.34 |
October | 6180.80 | 03-OCT-12:01 | 6443.43 | 2513.82 | 7268.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.10 |
November | 573.36 | 08-NOV-13:02 | 8054.28 | 3563.57 | 9085.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.31 |
December | 565.06 | 21-DEC-13:02 | 8054.28 | 6314.79 | 9085.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 565.06 | 169.56 | 69.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14524.74 | 8054.28 | 6314.79 | 9085.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1136.77 | 25-JAN-13:40 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.13 |
February | 4723.30 | 15-FEB-13:40 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8899.63 | 31-MAR-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.91 |
April | 16681.56 | 23-APR-13:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 624.54 |
May | 20105.68 | 14-MAY-12:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.16 |
June | 21489.32 | 18-JUN-12:22 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.14 |
July | 22067.43 | 23-JUL-13:12 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.06 |
August | 23589.77 | 27-AUG-13:11 | 468.72 | 193.02 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.32 |
September | 18937.51 | 10-SEP-11:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.23 |
October | 9702.62 | 03-OCT-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.96 |
November | 2771.62 | 08-NOV-13:30 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.69 |
December | 821.34 | 23-DEC-17:02 | 334.80 | 289.04 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 821.34 | 267.84 | 110.30 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23589.77 | 1306.65 | 496.34 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 624.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 516.68 | 21-JAN-17:02 | 211.94 | 182.97 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.94 |
February | 616.50 | 09-FEB-15:10 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.40 |
March | 1261.49 | 31-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.86 |
April | 10628.57 | 22-APR-17:42 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 566.64 |
May | 12368.20 | 28-MAY-17:12 | 0.00 | 69.82 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.99 |
June | 13133.41 | 10-JUN-17:05 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.73 |
July | 10896.03 | 09-JUL-19:42 | 0.00 | 69.82 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.25 |
August | 14555.70 | 27-AUG-17:52 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.52 |
September | 6588.76 | 02-SEP-17:43 | 127.16 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.01 |
October | 1265.60 | 03-OCT-15:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.53 |
November | 575.89 | 08-NOV-15:40 | 805.38 | 581.47 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.50 |
December | 515.37 | 23-DEC-17:02 | 211.94 | 182.97 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 515.37 | 0.00 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.94 | |
Maximum of Months | 14555.70 | 805.38 | 581.47 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 566.64 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.236207E+12 | 275935.85 | 02-JAN-08:09 | 0.759786E+11 | 223852.66 | 12-JAN-08:20 |
February | 0.178922E+12 | 259173.10 | 27-FEB-07:10 | 0.495126E+11 | 198540.51 | 27-FEB-08:30 |
March | 0.153645E+12 | 226857.71 | 06-MAR-07:10 | 0.277673E+11 | 179907.01 | 01-MAR-07:49 |
April | 0.100058E+12 | 196032.74 | 03-APR-06:10 | 0.134613E+11 | 34180.91 | 03-APR-07:10 |
May | 0.965138E+11 | 105852.67 | 31-MAY-15:50 | 0.131067E+11 | 29158.73 | 05-MAY-06:10 |
June | 0.109357E+12 | 134921.85 | 30-JUN-12:30 | 0.125241E+11 | 13390.02 | 02-JUN-11:30 |
July | 0.112317E+12 | 134700.65 | 11-JUL-15:50 | 0.120748E+11 | 12067.04 | 13-JUL-11:30 |
August | 0.108123E+12 | 128634.89 | 11-AUG-15:50 | 0.126004E+11 | 13162.39 | 30-AUG-06:10 |
September | 0.921997E+11 | 109314.20 | 25-SEP-06:10 | 0.118641E+11 | 13843.97 | 26-SEP-12:20 |
October | 0.132258E+12 | 215594.99 | 30-OCT-06:10 | 0.163772E+11 | 32176.34 | 31-OCT-07:10 |
November | 0.201746E+12 | 250731.58 | 27-NOV-07:10 | 0.678409E+11 | 183215.45 | 29-NOV-08:09 |
December | 0.234837E+12 | 246876.74 | 04-DEC-07:10 | 0.957260E+11 | 204804.72 | 15-DEC-08:09 |
Annual Sum or Average | 0.175618E+13 | 0.408834E+12 | ||||
Minimum of Months | 0.921997E+11 | 105852.67 | 0.118641E+11 | 12067.04 | ||
Maximum of Months | 0.236207E+12 | 275935.85 | 0.957260E+11 | 223852.66 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.225434E+11 | 0.882650E+10 | 0.593559E+11 | 0.986177E+09 | 0.564675E+10 | 12379742.02 | 0.135980E+12 | 2007677.51 | 0.00 | 0.00 | 0.285363E+10 | 0.00 | 0.00 |
February | 0.190142E+11 | 0.607552E+10 | 0.537310E+11 | 0.890744E+09 | 0.468071E+10 | 11196021.66 | 0.918997E+11 | 4248388.28 | 0.00 | 0.00 | 0.261516E+10 | 0.00 | 0.00 |
March | 0.211190E+11 | 0.473450E+10 | 0.617796E+11 | 0.102935E+10 | 0.445152E+10 | 12675672.10 | 0.574173E+11 | 8973498.97 | 0.00 | 0.00 | 0.309209E+10 | 0.00 | 0.00 |
April | 0.182286E+11 | 0.291276E+10 | 0.572952E+11 | 0.946138E+09 | 0.475503E+10 | 11960507.72 | 0.130558E+11 | 0.746793E+09 | 0.00 | 0.00 | 0.210538E+10 | 0.00 | 0.00 |
May | 0.195583E+11 | 0.175545E+10 | 0.605677E+11 | 0.100548E+10 | 0.876307E+10 | 12527707.06 | 0.876997E+09 | 0.354490E+10 | 0.00 | 0.00 | 0.429295E+09 | 0.00 | 0.00 |
June | 0.193872E+11 | 0.925713E+09 | 0.594895E+11 | 0.989792E+09 | 0.135625E+11 | 12231776.97 | 0.178932E+09 | 0.146486E+11 | 0.00 | 0.00 | 0.162378E+09 | 0.00 | 0.00 |
July | 0.181701E+11 | 0.131570E+10 | 0.583622E+11 | 0.961597E+09 | 0.134047E+11 | 12256437.81 | 0.127696E+09 | 0.197145E+11 | 0.00 | 0.00 | 0.247942E+09 | 0.00 | 0.00 |
August | 0.203959E+11 | 0.241310E+10 | 0.617796E+11 | 0.102885E+10 | 0.107292E+11 | 12675672.10 | 0.415887E+09 | 0.110932E+11 | 0.00 | 0.00 | 0.254202E+09 | 0.00 | 0.00 |
September | 0.185972E+11 | 0.381882E+10 | 0.572729E+11 | 0.946101E+09 | 0.467543E+10 | 11960507.72 | 0.400492E+10 | 0.127983E+10 | 0.00 | 0.00 | 0.159255E+10 | 0.00 | 0.00 |
October | 0.202884E+11 | 0.580314E+10 | 0.593671E+11 | 0.983503E+09 | 0.389590E+10 | 12379742.02 | 0.391551E+11 | 36331119.08 | 0.00 | 0.00 | 0.271616E+10 | 0.00 | 0.00 |
November | 0.216482E+11 | 0.774574E+10 | 0.580818E+11 | 0.967140E+09 | 0.475881E+10 | 12059151.09 | 0.105764E+12 | 1766778.82 | 0.00 | 0.00 | 0.276619E+10 | 0.00 | 0.00 |
December | 0.223748E+11 | 0.969307E+10 | 0.583511E+11 | 0.966050E+09 | 0.551664E+10 | 12256437.81 | 0.135100E+12 | 1145361.28 | 0.00 | 0.00 | 0.282183E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241325E+12 | 0.560200E+11 | 0.705434E+12 | 0.117009E+11 | 0.848402E+11 | 0.146559E+09 | 0.583977E+12 | 0.510824E+11 | 0.00 | 0.00 | 0.216568E+11 | 0.00 | 0.00 |
Minimum of Months | 0.181701E+11 | 0.925713E+09 | 0.537310E+11 | 0.890744E+09 | 0.389590E+10 | 11196021.66 | 0.127696E+09 | 1145361.28 | 0.00 | 0.00 | 0.162378E+09 | 0.00 | 0.00 |
Maximum of Months | 0.225434E+11 | 0.969307E+10 | 0.617796E+11 | 0.102935E+10 | 0.135625E+11 | 12675672.10 | 0.135980E+12 | 0.197145E+11 | 0.00 | 0.00 | 0.309209E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.630759E+11 | 0.00 | 0.129027E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.378386E+11 | 0.00 | 0.116740E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.143838E+11 | 0.00 | 0.133835E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.104398E+10 | 0.00 | 0.124173E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 88240519.70 | 0.00 | 0.130185E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 3669457.23 | 0.00 | 0.125204E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 2447608.28 | 0.00 | 0.120723E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 38799926.90 | 0.00 | 0.125616E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.171352E+09 | 0.00 | 0.116928E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.414291E+10 | 0.00 | 0.122343E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.556419E+11 | 0.00 | 0.121990E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.831265E+11 | 0.00 | 0.125994E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.259558E+12 | 0.00 | 0.149276E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 2447608.28 | 0.00 | 0.116740E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.831265E+11 | 0.00 | 0.133835E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 25003.79 | 02-JAN-08:09 | 5686.19 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 840.16 | 02-JAN-08:30 | 8187.90 | 02-JAN-06:19 | 6.85 | 02-JAN-22:10 | 215791.96 | 02-JAN-06:19 |
February | 25003.79 | 01-FEB-08:09 | 5686.19 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 840.16 | 06-FEB-08:30 | 7742.42 | 27-FEB-07:10 | 6.85 | 02-FEB-17:10 | 213852.43 | 27-FEB-07:10 |
March | 25003.79 | 01-MAR-08:09 | 5686.19 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 840.16 | 01-MAR-08:30 | 6025.83 | 06-MAR-07:10 | 6.85 | 01-MAR-17:19 | 183212.55 | 06-MAR-07:10 |
April | 20588.77 | 04-APR-07:10 | 5686.19 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 834.29 | 04-APR-07:19 | 12163.15 | 21-APR-15:50 | 6.85 | 01-APR-05:10 | 153534.68 | 03-APR-06:10 |
May | 19671.42 | 01-MAY-07:10 | 3328.83 | 01-MAY-21:10 | 45864.70 | 01-MAY-07:10 | 833.07 | 01-MAY-07:19 | 19461.49 | 31-MAY-15:09 | 6.85 | 02-MAY-16:10 | 16284.85 | 03-MAY-06:10 |
June | 19671.42 | 01-JUN-07:10 | 3328.83 | 01-JUN-22:49 | 45864.70 | 01-JUN-07:10 | 833.07 | 01-JUN-07:19 | 24293.65 | 20-JUN-15:30 | 6.85 | 01-JUN-05:10 | 9816.50 | 02-JUN-06:19 |
July | 19753.26 | 25-JUL-07:10 | 3328.83 | 11-JUL-22:00 | 45864.70 | 03-JUL-07:10 | 833.18 | 25-JUL-07:19 | 26564.64 | 12-JUL-15:09 | 6.85 | 05-JUL-11:09 | 8090.37 | 05-JUL-06:19 |
August | 19896.12 | 18-AUG-15:00 | 5686.19 | 24-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 833.18 | 07-AUG-07:19 | 23898.56 | 10-AUG-15:50 | 6.85 | 01-AUG-06:10 | 24229.41 | 31-AUG-06:10 |
September | 24139.64 | 28-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 839.00 | 28-SEP-07:19 | 9811.13 | 08-SEP-15:30 | 6.85 | 05-SEP-16:10 | 68136.39 | 25-SEP-06:10 |
October | 25003.79 | 03-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 840.16 | 11-OCT-07:19 | 5514.40 | 30-OCT-06:10 | 6.85 | 03-OCT-12:09 | 172396.70 | 30-OCT-06:10 |
November | 25003.79 | 01-NOV-07:10 | 5686.19 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 840.16 | 06-NOV-08:30 | 7226.24 | 27-NOV-07:10 | 6.85 | 01-NOV-07:19 | 205927.08 | 27-NOV-07:10 |
December | 25003.79 | 01-DEC-08:09 | 5686.19 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 840.16 | 04-DEC-08:30 | 6976.62 | 04-DEC-07:10 | 6.85 | 21-DEC-07:19 | 202321.86 | 04-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 19671.42 | 3328.83 | 45864.70 | 833.07 | 5514.40 | 6.85 | 8090.37 | |||||||
Maximum of Months | 25003.79 | 5686.19 | 45864.70 | 840.16 | 26564.64 | 6.85 | 215791.96 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 493.66 | 19-JAN-07:10 | 0.00 | 0.00 | 2208.01 | 02-JAN-08:30 | 0.00 | 0.00 |
February | 742.62 | 09-FEB-07:10 | 0.00 | 0.00 | 2208.01 | 01-FEB-12:30 | 0.00 | 0.00 |
March | 583.75 | 23-MAR-06:10 | 0.00 | 0.00 | 2208.01 | 01-MAR-08:30 | 0.00 | 0.00 |
April | 12063.83 | 21-APR-15:09 | 0.00 | 0.00 | 2208.01 | 01-APR-16:10 | 0.00 | 0.00 |
May | 25105.27 | 31-MAY-15:00 | 0.00 | 0.00 | 2208.01 | 01-MAY-19:00 | 0.00 | 0.00 |
June | 46348.45 | 30-JUN-14:30 | 0.00 | 0.00 | 2208.01 | 02-JUN-06:19 | 0.00 | 0.00 |
July | 44320.53 | 11-JUL-15:00 | 0.00 | 0.00 | 2208.01 | 11-JUL-12:50 | 0.00 | 0.00 |
August | 39994.14 | 11-AUG-15:50 | 0.00 | 0.00 | 2208.01 | 30-AUG-06:10 | 0.00 | 0.00 |
September | 11780.48 | 08-SEP-12:00 | 0.00 | 0.00 | 2208.01 | 02-SEP-09:09 | 0.00 | 0.00 |
October | 1641.54 | 05-OCT-15:00 | 0.00 | 0.00 | 2208.01 | 03-OCT-08:09 | 0.00 | 0.00 |
November | 516.72 | 04-NOV-06:10 | 0.00 | 0.00 | 2208.01 | 01-NOV-11:20 | 0.00 | 0.00 |
December | 501.45 | 23-DEC-07:10 | 0.00 | 0.00 | 2208.01 | 02-DEC-17:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 493.66 | 0.00 | 0.00 | 2208.01 | 0.00 | 0.00 | ||
Maximum of Months | 46348.45 | 0.00 | 0.00 | 2208.01 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 275935.85 | 02-JAN-08:09 | 25003.79 | 45864.70 | 5686.19 | 818.16 | 6456.18 | 6.85 | 189891.97 | 0.00 | 0.00 |
February | 259173.10 | 27-FEB-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 7742.42 | 6.85 | 213852.43 | 0.00 | 0.00 |
March | 226857.71 | 06-MAR-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 6025.83 | 6.85 | 183212.55 | 41.07 | 0.00 |
April | 196032.74 | 03-APR-06:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 4919.80 | 6.85 | 153534.68 | 0.00 | 0.00 |
May | 105852.67 | 31-MAY-15:50 | 19671.42 | 42072.41 | 0.00 | 831.72 | 18508.91 | 6.85 | 0.00 | 24761.36 | 0.00 |
June | 134921.85 | 30-JUN-12:30 | 19671.42 | 42402.18 | 0.00 | 831.83 | 23524.61 | 6.85 | 0.00 | 46276.96 | 0.00 |
July | 134700.65 | 11-JUL-15:50 | 19671.42 | 42072.41 | 0.00 | 831.72 | 25707.19 | 6.85 | 0.00 | 44203.06 | 0.00 |
August | 128634.89 | 11-AUG-15:50 | 19671.42 | 42072.41 | 0.00 | 831.72 | 23850.35 | 6.85 | 0.00 | 39994.14 | 0.00 |
September | 109314.20 | 25-SEP-06:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 3141.70 | 6.85 | 68136.39 | 457.85 | 0.00 |
October | 215594.99 | 30-OCT-06:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 5514.40 | 6.85 | 172396.70 | 105.63 | 0.00 |
November | 250731.58 | 27-NOV-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 7226.24 | 6.85 | 205927.08 | 0.00 | 0.00 |
December | 246876.74 | 04-DEC-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 6976.62 | 6.85 | 202321.86 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 105852.67 | 8334.71 | 21098.80 | 0.00 | 243.70 | 3141.70 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 275935.85 | 25003.79 | 45864.70 | 5686.19 | 831.83 | 25707.19 | 6.85 | 213852.43 | 46276.96 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 214388.15 | 12-JAN-08:09 | 0.00 | 14106.40 | 02-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 189159.65 | 27-FEB-08:50 | 0.00 | 14121.04 | 21-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 170916.38 | 01-MAR-07:49 | 0.00 | 14073.83 | 03-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 24548.65 | 03-APR-07:10 | 0.00 | 14047.68 | 21-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 20473.23 | 04-MAY-06:10 | 0.00 | 14048.77 | 04-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 1686.09 | 01-JUN-06:19 | 0.00 | 13390.02 | 02-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 1118.98 | 05-JUL-08:09 | 0.00 | 12067.04 | 13-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 4228.24 | 30-AUG-06:10 | 0.00 | 11551.29 | 04-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 4499.38 | 26-SEP-17:19 | 0.00 | 11405.48 | 27-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 23011.37 | 31-OCT-06:00 | 0.00 | 12186.77 | 31-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 173956.30 | 29-NOV-07:00 | 0.00 | 13194.62 | 30-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 195586.23 | 15-DEC-07:00 | 0.00 | 14051.13 | 27-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 1118.98 | 0.00 | 11405.48 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 214388.15 | 0.00 | 14121.04 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 18.94 | 2.33 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.67 | 18.94 | 2.33 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 18.94 | 2.33 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 18.88 | 2.83 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
February | 0.67 | 18.51 | 0.50 | 18.79 | 0.00 | 18.79 | 0.00 | 18.79 |
March | 0.17 | 19.40 | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.39 | 0.17 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
November | 0.83 | 19.28 | 0.83 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
December | 0.83 | 18.67 | 0.67 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
Annual Sum or Average | 6.33 | 18.89 | 5.17 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 19.40 | 2.83 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.50 | 18.80 | 8.17 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
February | 6.83 | 18.86 | 5.33 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
March | 2.33 | 18.59 | 1.67 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
April | 0.33 | 18.15 | 0.17 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.67 | 18.68 | 1.17 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
November | 8.00 | 18.86 | 6.17 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
December | 9.00 | 18.84 | 7.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
Annual Sum or Average | 38.67 | 18.81 | 29.67 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.50 | 18.86 | 8.17 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 95.33 | 16.47 | 53.00 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 |
February | 76.33 | 16.44 | 41.50 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 |
March | 40.50 | 17.27 | 20.33 | 17.93 | 0.00 | 17.93 | 0.00 | 17.93 |
April | 8.33 | 16.60 | 3.50 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20.33 | 16.51 | 9.67 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
November | 80.67 | 16.58 | 46.00 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 |
December | 98.83 | 16.72 | 54.83 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
Annual Sum or Average | 420.33 | 16.63 | 228.83 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 98.83 | 17.27 | 54.83 | 17.93 | 0.00 | 17.93 | 0.00 | 17.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 56.67 | 14.60 | 17.17 | 14.60 | 0.00 | 14.60 | 0.00 | 14.60 |
February | 43.17 | 14.79 | 10.67 | 14.81 | 0.00 | 14.81 | 0.00 | 14.81 |
March | 17.17 | 15.24 | 0.67 | 15.31 | 0.00 | 15.31 | 0.00 | 15.31 |
April | 4.83 | 15.48 | 0.50 | 15.55 | 0.00 | 15.55 | 0.00 | 15.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.11 | 2.83 | 28.11 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.66 | 1.33 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.86 | 5.33 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.54 | 0.50 | 27.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.37 | 0.50 | 27.37 |
October | 13.67 | 15.25 | 2.67 | 15.28 | 0.00 | 15.28 | 0.00 | 15.28 |
November | 51.83 | 14.88 | 16.83 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
December | 60.83 | 14.74 | 16.50 | 14.72 | 0.00 | 14.72 | 0.00 | 14.72 |
Annual Sum or Average | 248.17 | 14.82 | 65.00 | 14.82 | 10.67 | 15.25 | 10.50 | 15.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.60 | 0.00 | 14.60 |
Maximum of Months | 60.83 | 15.48 | 17.17 | 15.55 | 5.50 | 28.11 | 5.33 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 52.33 | 14.66 | 15.83 | 14.67 | 0.00 | 14.67 | 0.00 | 14.67 |
February | 33.00 | 14.85 | 4.83 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 |
March | 12.00 | 15.57 | 0.83 | 15.65 | 0.00 | 15.65 | 0.00 | 15.65 |
April | 2.33 | 15.90 | 0.33 | 16.05 | 1.17 | 19.55 | 1.17 | 21.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.84 | 4.83 | 27.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.81 | 3.33 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.94 | 5.50 | 27.95 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.96 | 2.50 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.48 | 0.33 | 27.48 |
October | 9.83 | 15.25 | 1.83 | 15.25 | 0.00 | 15.25 | 0.00 | 15.25 |
November | 41.17 | 14.97 | 11.33 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
December | 54.50 | 14.78 | 15.50 | 14.75 | 0.00 | 14.75 | 0.00 | 14.75 |
Annual Sum or Average | 205.17 | 14.88 | 50.50 | 14.87 | 18.00 | 15.73 | 17.67 | 16.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 0.00 | 14.67 |
Maximum of Months | 54.50 | 15.90 | 15.83 | 16.05 | 5.67 | 27.96 | 5.50 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 57.83 | 14.60 | 17.67 | 14.59 | 0.00 | 14.59 | 0.00 | 14.59 |
February | 45.50 | 14.73 | 12.83 | 14.72 | 0.00 | 14.72 | 0.00 | 14.72 |
March | 18.17 | 15.24 | 1.67 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
April | 3.17 | 15.68 | 0.83 | 15.71 | 0.50 | 17.04 | 0.17 | 17.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.82 | 1.50 | 27.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.93 | 1.50 | 27.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.69 | 2.00 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.82 | 0.83 | 27.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.43 | 0.17 | 27.43 |
October | 14.50 | 15.21 | 3.50 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
November | 50.67 | 14.87 | 16.67 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
December | 60.33 | 14.74 | 16.33 | 14.71 | 0.00 | 14.71 | 0.00 | 14.71 |
Annual Sum or Average | 250.17 | 14.81 | 69.50 | 14.80 | 17.00 | 15.45 | 6.17 | 15.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.59 | 0.00 | 14.59 |
Maximum of Months | 60.33 | 15.68 | 17.67 | 15.71 | 5.17 | 27.93 | 2.00 | 27.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 92.50 | 18.17 | 72.17 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 |
February | 72.67 | 18.34 | 56.83 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 |
March | 23.00 | 19.04 | 18.83 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
April | 2.67 | 18.83 | 2.00 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.83 | 18.96 | 1.33 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
November | 25.67 | 18.75 | 19.50 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
December | 42.33 | 18.84 | 33.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
Annual Sum or Average | 260.67 | 18.47 | 203.67 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.50 | 19.04 | 72.17 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.17 | 15.05 | 10.33 | 15.04 | 0.00 | 15.04 | 0.00 | 15.04 |
February | 16.50 | 15.28 | 3.50 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 |
March | 2.67 | 16.76 | 0.17 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 |
April | 0.33 | 16.21 | 0.00 | 16.21 | 0.00 | 16.21 | 0.00 | 16.21 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.65 | 2.50 | 27.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.37 | 0.50 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.63 | 4.17 | 27.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.31 | 0.83 | 27.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.40 | 0.83 | 27.40 |
October | 0.33 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
November | 6.83 | 15.87 | 0.17 | 15.95 | 0.00 | 15.95 | 0.00 | 15.95 |
December | 11.33 | 15.63 | 2.00 | 15.59 | 0.00 | 15.59 | 0.00 | 15.59 |
Annual Sum or Average | 68.17 | 15.36 | 16.17 | 15.34 | 9.17 | 16.54 | 8.83 | 17.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.04 | 0.00 | 15.04 |
Maximum of Months | 30.17 | 16.95 | 10.33 | 16.95 | 4.50 | 27.65 | 4.17 | 27.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 155.17 | 15.64 | 135.50 | 15.68 | 0.00 | 15.68 | 0.00 | 15.68 |
February | 93.83 | 15.80 | 86.17 | 15.81 | 0.00 | 15.81 | 0.00 | 15.81 |
March | 79.67 | 16.66 | 78.00 | 16.66 | 0.00 | 16.66 | 0.00 | 16.66 |
April | 26.00 | 18.18 | 26.00 | 18.18 | 0.83 | 18.33 | 0.83 | 18.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.48 | 2.00 | 27.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.40 | 1.83 | 27.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.67 | 3.33 | 27.69 |
August | 2.00 | 20.20 | 2.00 | 20.20 | 1.83 | 22.62 | 1.50 | 23.73 |
September | 7.83 | 19.20 | 7.83 | 19.20 | 0.33 | 19.37 | 0.33 | 19.54 |
October | 51.67 | 17.52 | 51.33 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 |
November | 98.67 | 15.11 | 95.17 | 15.09 | 0.00 | 15.09 | 0.00 | 15.09 |
December | 130.50 | 15.30 | 121.17 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
Annual Sum or Average | 645.33 | 15.95 | 603.17 | 15.97 | 10.50 | 16.06 | 9.83 | 16.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.09 | 0.00 | 15.09 |
Maximum of Months | 155.17 | 20.20 | 135.50 | 20.20 | 3.67 | 27.67 | 3.33 | 27.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.67 | 14.99 | 10.83 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
February | 17.50 | 15.14 | 3.67 | 15.11 | 0.00 | 15.11 | 0.00 | 15.11 |
March | 3.00 | 16.67 | 0.17 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
April | 0.33 | 16.71 | 0.00 | 16.71 | 0.33 | 22.03 | 0.17 | 23.09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.38 | 0.00 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.52 | 0.50 | 27.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.39 | 0.50 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.63 | 0.33 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
October | 0.50 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 |
November | 6.83 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 |
December | 11.50 | 15.56 | 1.83 | 15.48 | 0.00 | 15.48 | 0.00 | 15.48 |
Annual Sum or Average | 70.33 | 15.29 | 16.50 | 15.23 | 7.33 | 16.18 | 1.83 | 16.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.95 | 0.00 | 14.95 |
Maximum of Months | 30.67 | 17.00 | 10.83 | 17.00 | 2.50 | 27.63 | 0.50 | 27.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 52.33 | 16.64 | 29.67 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
February | 30.00 | 16.98 | 17.33 | 17.42 | 0.00 | 17.42 | 0.00 | 17.42 |
March | 7.83 | 18.53 | 4.83 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
April | 1.00 | 17.92 | 0.50 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.00 | 27.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.83 | 18.64 | 1.83 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
November | 22.67 | 17.77 | 13.83 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 |
December | 30.17 | 17.51 | 17.83 | 18.00 | 0.00 | 18.00 | 0.00 | 18.00 |
Annual Sum or Average | 146.83 | 17.21 | 85.83 | 17.67 | 0.33 | 17.68 | 0.00 | 17.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.33 | 18.64 | 29.67 | 19.05 | 0.33 | 27.30 | 0.00 | 27.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.00 | 14.90 | 11.33 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
February | 14.83 | 15.05 | 3.00 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 |
March | 2.17 | 16.67 | 0.00 | 16.67 | 0.00 | 16.67 | 0.00 | 16.67 |
April | 0.33 | 15.97 | 0.00 | 15.97 | 0.50 | 22.78 | 0.50 | 24.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.14 | 3.33 | 28.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.62 | 1.83 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.80 | 5.50 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.50 | 1.17 | 27.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.59 | 1.00 | 27.59 |
October | 1.33 | 16.05 | 0.00 | 16.05 | 0.00 | 16.05 | 0.00 | 16.05 |
November | 11.33 | 15.54 | 1.83 | 15.58 | 0.00 | 15.58 | 0.00 | 15.58 |
December | 18.50 | 15.26 | 4.00 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
Annual Sum or Average | 82.50 | 15.17 | 20.17 | 15.11 | 14.33 | 16.66 | 13.33 | 17.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.86 | 0.00 | 14.86 |
Maximum of Months | 34.00 | 16.67 | 11.33 | 16.67 | 6.17 | 28.14 | 5.50 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.83 | 15.00 | 7.67 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
February | 9.00 | 15.22 | 1.83 | 15.14 | 0.00 | 15.14 | 0.00 | 15.14 |
March | 1.33 | 16.92 | 0.00 | 16.92 | 0.00 | 16.92 | 0.00 | 16.92 |
April | 0.33 | 16.43 | 0.00 | 16.43 | 1.50 | 25.62 | 1.50 | 26.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.83 | 5.50 | 27.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.77 | 3.33 | 27.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.93 | 5.00 | 27.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.89 | 3.00 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.69 | 0.50 | 27.69 |
October | 0.83 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 |
November | 7.83 | 15.81 | 0.33 | 15.96 | 0.00 | 15.96 | 0.00 | 15.96 |
December | 13.83 | 15.42 | 2.50 | 15.34 | 0.00 | 15.34 | 0.00 | 15.34 |
Annual Sum or Average | 61.00 | 15.31 | 12.33 | 15.24 | 19.17 | 17.85 | 18.83 | 19.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.95 | 0.00 | 14.95 |
Maximum of Months | 27.83 | 16.92 | 7.67 | 16.92 | 5.50 | 27.93 | 5.50 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.00 | 14.90 | 11.33 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
February | 15.50 | 15.05 | 3.50 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
March | 2.17 | 16.71 | 0.00 | 16.71 | 0.00 | 16.71 | 0.00 | 16.71 |
April | 0.33 | 16.17 | 0.00 | 16.17 | 0.50 | 23.12 | 0.17 | 23.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.78 | 1.67 | 27.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.85 | 1.67 | 27.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.65 | 1.83 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.79 | 0.83 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.51 | 0.17 | 27.51 |
October | 1.50 | 16.17 | 0.00 | 16.17 | 0.00 | 16.17 | 0.00 | 16.17 |
November | 10.67 | 15.58 | 1.67 | 15.62 | 0.00 | 15.62 | 0.00 | 15.62 |
December | 19.00 | 15.27 | 4.33 | 15.21 | 0.00 | 15.21 | 0.00 | 15.21 |
Annual Sum or Average | 83.17 | 15.18 | 20.83 | 15.11 | 17.67 | 16.95 | 6.33 | 17.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.86 | 0.00 | 14.86 |
Maximum of Months | 34.00 | 16.71 | 11.33 | 16.71 | 5.17 | 27.85 | 1.83 | 27.86 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.36 | 259.00 | 21.08 | 259.00 | 20.94 |
February | 454.00 | 21.98 | 146.83 | 21.69 | 146.83 | 21.51 |
March | 514.00 | 22.88 | 30.50 | 22.79 | 30.50 | 22.70 |
April | 421.33 | 23.73 | 1.00 | 23.72 | 1.00 | 23.72 |
May | 109.67 | 24.00 | 33.50 | 24.46 | 0.00 | 24.46 |
June | 0.00 | 0.00 | 211.00 | 24.95 | 0.00 | 24.95 |
July | 0.00 | 0.00 | 370.67 | 24.66 | 0.00 | 24.66 |
August | 11.00 | 24.00 | 264.67 | 24.70 | 0.00 | 24.70 |
September | 151.33 | 23.96 | 51.33 | 24.44 | 0.00 | 24.44 |
October | 495.83 | 23.44 | 3.33 | 23.42 | 3.33 | 23.41 |
November | 489.00 | 22.07 | 125.00 | 21.84 | 125.00 | 21.69 |
December | 497.00 | 21.54 | 268.17 | 21.32 | 268.17 | 21.21 |
Annual Sum or Average | 3645.17 | 22.52 | 1765.00 | 22.66 | 833.83 | 22.41 |
Minimum of Months | 0.00 | 0.00 | 1.00 | 21.08 | 0.00 | 20.94 |
Maximum of Months | 514.00 | 24.00 | 370.67 | 24.95 | 268.17 | 24.95 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.43 | 466.67 | 20.39 | 466.67 | 20.38 |
February | 454.00 | 20.75 | 328.00 | 20.62 | 328.00 | 20.57 |
March | 514.00 | 21.39 | 226.67 | 21.20 | 226.67 | 21.10 |
April | 479.00 | 22.89 | 50.17 | 22.70 | 50.17 | 22.54 |
May | 310.17 | 23.88 | 2.83 | 23.89 | 0.00 | 23.89 |
June | 16.33 | 23.97 | 141.50 | 24.70 | 0.00 | 24.70 |
July | 0.00 | 0.00 | 292.67 | 24.56 | 0.00 | 24.56 |
August | 57.17 | 23.80 | 146.33 | 24.45 | 0.00 | 24.45 |
September | 353.33 | 23.32 | 0.50 | 23.32 | 0.00 | 23.32 |
October | 502.00 | 21.75 | 117.33 | 21.54 | 117.33 | 21.40 |
November | 489.00 | 20.67 | 418.00 | 20.61 | 418.00 | 20.58 |
December | 497.00 | 20.49 | 487.33 | 20.48 | 487.33 | 20.48 |
Annual Sum or Average | 4174.00 | 21.62 | 2678.00 | 21.54 | 2094.17 | 21.29 |
Minimum of Months | 0.00 | 0.00 | 0.50 | 20.39 | 0.00 | 20.38 |
Maximum of Months | 514.00 | 23.97 | 487.33 | 24.70 | 487.33 | 24.70 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.06 | 502.00 | 20.06 | 502.00 | 20.06 |
February | 454.00 | 20.22 | 423.67 | 20.18 | 423.67 | 20.16 |
March | 514.00 | 20.76 | 389.17 | 20.64 | 389.17 | 20.59 |
April | 485.00 | 22.20 | 127.33 | 21.82 | 127.33 | 21.58 |
May | 376.33 | 23.64 | 0.83 | 23.65 | 0.00 | 23.65 |
June | 42.17 | 23.86 | 104.33 | 24.42 | 0.00 | 24.42 |
July | 5.33 | 23.60 | 252.33 | 24.48 | 0.00 | 24.48 |
August | 119.67 | 23.50 | 100.83 | 24.00 | 0.00 | 24.00 |
September | 458.50 | 22.74 | 22.83 | 22.64 | 22.83 | 22.56 |
October | 502.00 | 20.86 | 307.33 | 20.66 | 307.33 | 20.57 |
November | 489.00 | 20.11 | 488.67 | 20.11 | 488.67 | 20.11 |
December | 497.00 | 20.06 | 497.00 | 20.06 | 497.00 | 20.06 |
Annual Sum or Average | 4445.00 | 21.20 | 3216.33 | 21.04 | 2758.00 | 20.81 |
Minimum of Months | 5.33 | 20.06 | 0.83 | 20.06 | 0.00 | 20.06 |
Maximum of Months | 514.00 | 23.86 | 502.00 | 24.48 | 502.00 | 24.48 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.61 | 502.00 | 19.61 | 502.00 | 19.61 |
February | 454.00 | 19.73 | 454.00 | 19.73 | 454.00 | 19.73 |
March | 514.00 | 20.10 | 494.67 | 20.08 | 494.67 | 20.07 |
April | 485.00 | 21.20 | 245.17 | 20.82 | 245.17 | 20.63 |
May | 390.00 | 23.29 | 7.50 | 23.24 | 6.67 | 23.20 |
June | 46.17 | 23.47 | 167.33 | 24.28 | 0.00 | 24.28 |
July | 23.83 | 23.50 | 321.83 | 24.36 | 0.00 | 24.36 |
August | 192.33 | 23.05 | 99.17 | 23.43 | 4.67 | 23.39 |
September | 480.50 | 21.78 | 112.50 | 21.54 | 112.50 | 21.37 |
October | 502.00 | 20.15 | 437.67 | 20.07 | 437.67 | 20.04 |
November | 489.00 | 19.67 | 489.00 | 19.67 | 489.00 | 19.67 |
December | 497.00 | 19.59 | 497.00 | 19.59 | 497.00 | 19.59 |
Annual Sum or Average | 4575.83 | 20.66 | 3827.83 | 20.60 | 3243.33 | 20.38 |
Minimum of Months | 23.83 | 19.59 | 7.50 | 19.59 | 0.00 | 19.59 |
Maximum of Months | 514.00 | 23.50 | 502.00 | 24.36 | 502.00 | 24.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.72 | 502.00 | 19.72 | 502.00 | 19.72 |
February | 454.00 | 19.85 | 448.00 | 19.84 | 448.00 | 19.84 |
March | 513.50 | 20.53 | 405.33 | 20.34 | 405.33 | 20.26 |
April | 420.00 | 21.84 | 171.67 | 21.42 | 162.67 | 21.14 |
May | 192.67 | 23.51 | 120.17 | 23.92 | 11.17 | 23.98 |
June | 38.00 | 23.88 | 299.17 | 24.39 | 4.83 | 24.42 |
July | 35.50 | 25.66 | 404.00 | 24.62 | 21.83 | 24.73 |
August | 105.17 | 23.36 | 247.67 | 24.02 | 4.17 | 24.01 |
September | 388.67 | 22.10 | 86.83 | 21.98 | 69.67 | 21.77 |
October | 501.50 | 20.38 | 394.17 | 20.21 | 394.17 | 20.14 |
November | 489.00 | 19.74 | 489.00 | 19.74 | 489.00 | 19.74 |
December | 497.00 | 19.69 | 497.00 | 19.69 | 497.00 | 19.69 |
Annual Sum or Average | 4137.00 | 20.71 | 4065.00 | 20.91 | 3009.83 | 20.65 |
Minimum of Months | 35.50 | 19.69 | 86.83 | 19.69 | 4.17 | 19.69 |
Maximum of Months | 513.50 | 25.66 | 502.00 | 24.62 | 502.00 | 24.73 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.75 | 499.33 | 19.74 | 499.33 | 19.74 |
February | 453.83 | 20.19 | 407.83 | 20.06 | 407.83 | 20.01 |
March | 476.50 | 20.87 | 335.83 | 20.56 | 335.83 | 20.43 |
April | 340.33 | 21.75 | 200.00 | 21.68 | 139.17 | 21.38 |
May | 249.00 | 23.18 | 126.50 | 23.62 | 16.67 | 23.64 |
June | 80.33 | 23.99 | 259.17 | 24.32 | 12.83 | 24.42 |
July | 63.67 | 24.67 | 358.50 | 24.52 | 21.50 | 24.64 |
August | 140.17 | 23.35 | 246.33 | 24.00 | 13.50 | 24.04 |
September | 343.33 | 22.03 | 130.50 | 22.19 | 63.50 | 21.99 |
October | 483.50 | 20.61 | 348.17 | 20.39 | 344.67 | 20.29 |
November | 489.00 | 19.83 | 480.50 | 19.80 | 480.50 | 19.79 |
December | 497.00 | 19.70 | 497.00 | 19.70 | 497.00 | 19.70 |
Annual Sum or Average | 4118.67 | 20.88 | 3889.67 | 21.04 | 2832.33 | 20.77 |
Minimum of Months | 63.67 | 19.70 | 126.50 | 19.70 | 12.83 | 19.70 |
Maximum of Months | 502.00 | 24.67 | 499.33 | 24.52 | 499.33 | 24.64 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.72 | 502.00 | 19.72 | 502.00 | 19.72 |
February | 454.00 | 19.83 | 450.67 | 19.83 | 450.67 | 19.83 |
March | 514.00 | 20.32 | 451.50 | 20.21 | 451.50 | 20.17 |
April | 412.00 | 21.48 | 213.33 | 21.16 | 192.50 | 20.91 |
May | 288.17 | 23.10 | 60.33 | 23.31 | 10.33 | 23.26 |
June | 65.17 | 23.70 | 226.00 | 24.35 | 6.17 | 24.40 |
July | 50.17 | 24.14 | 343.67 | 24.42 | 9.83 | 24.48 |
August | 160.50 | 23.10 | 189.50 | 23.75 | 8.00 | 23.74 |
September | 427.50 | 21.89 | 103.83 | 21.71 | 92.17 | 21.53 |
October | 502.00 | 20.23 | 419.50 | 20.12 | 419.50 | 20.07 |
November | 489.00 | 19.75 | 489.00 | 19.75 | 489.00 | 19.75 |
December | 497.00 | 19.69 | 497.00 | 19.69 | 497.00 | 19.69 |
Annual Sum or Average | 4361.50 | 20.70 | 3946.33 | 20.77 | 3128.67 | 20.54 |
Minimum of Months | 50.17 | 19.69 | 60.33 | 19.69 | 6.17 | 19.69 |
Maximum of Months | 514.00 | 24.14 | 502.00 | 24.42 | 502.00 | 24.48 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.63 | 502.00 | 19.63 | 502.00 | 19.63 |
February | 454.00 | 19.73 | 454.00 | 19.73 | 454.00 | 19.73 |
March | 514.00 | 20.22 | 510.17 | 20.22 | 510.17 | 20.21 |
April | 485.00 | 20.98 | 285.33 | 20.76 | 285.33 | 20.66 |
May | 506.83 | 23.19 | 0.00 | 23.19 | 0.00 | 23.19 |
June | 95.67 | 23.77 | 81.67 | 24.09 | 0.00 | 24.09 |
July | 10.67 | 23.70 | 259.17 | 24.41 | 0.00 | 24.41 |
August | 155.33 | 23.42 | 70.83 | 23.76 | 0.00 | 23.76 |
September | 481.33 | 22.49 | 34.00 | 22.38 | 34.00 | 22.28 |
October | 502.00 | 20.69 | 360.67 | 20.56 | 360.67 | 20.51 |
November | 489.00 | 19.89 | 489.00 | 19.89 | 489.00 | 19.89 |
December | 497.00 | 19.74 | 497.00 | 19.74 | 497.00 | 19.74 |
Annual Sum or Average | 4692.83 | 20.89 | 3543.83 | 20.72 | 3132.17 | 20.51 |
Minimum of Months | 10.67 | 19.63 | 0.00 | 19.63 | 0.00 | 19.63 |
Maximum of Months | 514.00 | 23.77 | 510.17 | 24.41 | 510.17 | 24.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.81 | 502.00 | 19.81 | 502.00 | 19.81 |
February | 454.00 | 19.94 | 454.00 | 19.94 | 454.00 | 19.94 |
March | 514.00 | 20.61 | 431.67 | 20.49 | 431.67 | 20.44 |
April | 455.83 | 22.08 | 156.50 | 21.71 | 152.33 | 21.46 |
May | 203.33 | 23.64 | 85.17 | 24.01 | 2.00 | 24.03 |
June | 30.17 | 23.71 | 263.50 | 24.40 | 0.33 | 24.40 |
July | 19.50 | 25.91 | 418.33 | 24.61 | 13.00 | 24.68 |
August | 46.83 | 23.72 | 285.33 | 24.32 | 0.67 | 24.33 |
September | 326.17 | 22.81 | 43.50 | 22.98 | 12.67 | 22.91 |
October | 501.50 | 21.07 | 281.67 | 20.83 | 281.67 | 20.72 |
November | 489.00 | 19.94 | 489.00 | 19.94 | 489.00 | 19.94 |
December | 497.00 | 19.81 | 497.00 | 19.81 | 497.00 | 19.81 |
Annual Sum or Average | 4039.33 | 20.89 | 3907.67 | 21.09 | 2836.33 | 20.82 |
Minimum of Months | 19.50 | 19.81 | 43.50 | 19.81 | 0.33 | 19.81 |
Maximum of Months | 514.00 | 25.91 | 502.00 | 24.61 | 502.00 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 18.46 | 502.00 | 18.46 | 502.00 | 18.46 |
February | 454.00 | 19.20 | 437.83 | 19.16 | 437.83 | 19.15 |
March | 514.00 | 20.08 | 413.50 | 19.89 | 413.50 | 19.82 |
April | 400.67 | 21.68 | 143.00 | 21.47 | 118.83 | 21.20 |
May | 304.17 | 22.82 | 53.67 | 23.19 | 2.33 | 23.19 |
June | 104.67 | 22.93 | 190.83 | 23.97 | 1.33 | 23.98 |
July | 59.67 | 23.06 | 361.50 | 24.32 | 8.67 | 24.37 |
August | 124.17 | 22.82 | 258.67 | 23.99 | 6.17 | 24.04 |
September | 333.67 | 22.16 | 84.00 | 22.51 | 18.83 | 22.41 |
October | 490.83 | 20.72 | 283.00 | 20.43 | 281.83 | 20.29 |
November | 489.00 | 18.85 | 486.83 | 18.85 | 486.83 | 18.85 |
December | 497.00 | 18.38 | 497.00 | 18.38 | 497.00 | 18.38 |
Annual Sum or Average | 4273.83 | 20.23 | 3711.83 | 20.34 | 2775.17 | 20.01 |
Minimum of Months | 59.67 | 18.38 | 53.67 | 18.38 | 1.33 | 18.38 |
Maximum of Months | 514.00 | 23.06 | 502.00 | 24.32 | 502.00 | 24.37 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.81 | 502.00 | 19.81 | 502.00 | 19.81 |
February | 454.00 | 19.90 | 454.00 | 19.90 | 454.00 | 19.90 |
March | 514.00 | 20.36 | 487.00 | 20.32 | 487.00 | 20.31 |
April | 441.67 | 21.80 | 173.00 | 21.44 | 168.83 | 21.22 |
May | 370.00 | 23.37 | 13.67 | 23.45 | 0.50 | 23.45 |
June | 64.33 | 23.71 | 184.00 | 24.35 | 0.67 | 24.36 |
July | 14.17 | 23.72 | 345.33 | 24.44 | 0.67 | 24.44 |
August | 94.50 | 23.53 | 198.83 | 24.16 | 0.67 | 24.16 |
September | 405.83 | 22.70 | 28.00 | 22.67 | 19.00 | 22.59 |
October | 502.00 | 20.79 | 336.83 | 20.63 | 336.83 | 20.56 |
November | 489.00 | 19.94 | 489.00 | 19.94 | 489.00 | 19.94 |
December | 497.00 | 19.81 | 497.00 | 19.81 | 497.00 | 19.81 |
Annual Sum or Average | 4348.50 | 20.94 | 3708.67 | 20.94 | 2956.17 | 20.70 |
Minimum of Months | 14.17 | 19.81 | 13.67 | 19.81 | 0.50 | 19.81 |
Maximum of Months | 514.00 | 23.72 | 502.00 | 24.44 | 502.00 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.80 | 502.00 | 19.80 | 502.00 | 19.80 |
February | 454.00 | 19.92 | 450.83 | 19.92 | 450.83 | 19.91 |
March | 514.00 | 20.38 | 468.00 | 20.34 | 468.00 | 20.32 |
April | 485.00 | 21.77 | 169.83 | 21.37 | 169.83 | 21.14 |
May | 348.67 | 23.69 | 1.00 | 23.69 | 0.00 | 23.69 |
June | 14.67 | 23.63 | 190.83 | 24.52 | 0.00 | 24.52 |
July | 2.83 | 23.72 | 357.00 | 24.49 | 0.00 | 24.49 |
August | 111.83 | 23.40 | 126.50 | 23.93 | 0.00 | 23.93 |
September | 466.50 | 22.50 | 40.33 | 22.36 | 40.33 | 22.24 |
October | 502.00 | 20.57 | 353.50 | 20.41 | 353.50 | 20.35 |
November | 489.00 | 19.84 | 489.00 | 19.84 | 489.00 | 19.84 |
December | 497.00 | 19.78 | 497.00 | 19.78 | 497.00 | 19.78 |
Annual Sum or Average | 4387.50 | 20.89 | 3645.83 | 20.86 | 2970.50 | 20.62 |
Minimum of Months | 2.83 | 19.78 | 1.00 | 19.78 | 0.00 | 19.78 |
Maximum of Months | 514.00 | 23.72 | 502.00 | 24.52 | 502.00 | 24.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.64 | 427.00 | 19.64 | 427.00 | 19.64 |
February | 385.00 | 19.85 | 376.33 | 19.83 | 376.33 | 19.82 |
March | 431.67 | 20.76 | 302.50 | 20.54 | 302.50 | 20.45 |
April | 345.50 | 22.17 | 104.50 | 21.87 | 91.00 | 21.60 |
May | 155.50 | 23.91 | 117.00 | 24.34 | 9.33 | 24.43 |
June | 17.00 | 25.00 | 248.33 | 24.62 | 7.00 | 24.68 |
July | 25.50 | 26.60 | 359.17 | 24.80 | 22.50 | 24.92 |
August | 54.33 | 23.67 | 226.00 | 24.33 | 2.33 | 24.35 |
September | 305.67 | 22.62 | 52.00 | 22.78 | 20.67 | 22.68 |
October | 425.83 | 20.73 | 270.00 | 20.50 | 270.00 | 20.39 |
November | 417.00 | 19.66 | 417.00 | 19.66 | 417.00 | 19.66 |
December | 422.00 | 19.59 | 422.00 | 19.59 | 422.00 | 19.59 |
Annual Sum or Average | 3412.00 | 20.80 | 3321.83 | 21.04 | 2367.67 | 20.76 |
Minimum of Months | 17.00 | 19.59 | 52.00 | 19.59 | 2.33 | 19.59 |
Maximum of Months | 431.67 | 26.60 | 427.00 | 24.80 | 427.00 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.90 | 494.67 | 19.89 | 494.67 | 19.88 |
February | 449.83 | 20.49 | 372.67 | 20.31 | 372.67 | 20.25 |
March | 458.83 | 21.17 | 272.33 | 20.87 | 269.83 | 20.72 |
April | 321.00 | 22.27 | 152.83 | 22.31 | 83.00 | 22.03 |
May | 215.50 | 23.66 | 124.50 | 24.06 | 10.17 | 24.14 |
June | 41.67 | 24.65 | 279.83 | 24.48 | 12.17 | 24.57 |
July | 25.50 | 26.29 | 392.83 | 24.64 | 20.17 | 24.74 |
August | 87.50 | 23.84 | 269.00 | 24.32 | 9.50 | 24.39 |
September | 308.67 | 22.67 | 98.50 | 23.00 | 16.17 | 22.92 |
October | 477.17 | 21.14 | 251.33 | 20.85 | 247.17 | 20.70 |
November | 489.00 | 20.05 | 466.83 | 20.00 | 466.83 | 19.98 |
December | 497.00 | 19.83 | 497.00 | 19.83 | 497.00 | 19.83 |
Annual Sum or Average | 3873.67 | 21.09 | 3672.33 | 21.30 | 2499.33 | 21.02 |
Minimum of Months | 25.50 | 19.83 | 98.50 | 19.83 | 9.50 | 19.83 |
Maximum of Months | 502.00 | 26.29 | 497.00 | 24.64 | 497.00 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.84 | 502.00 | 19.84 | 502.00 | 19.84 |
February | 454.00 | 19.97 | 444.00 | 19.96 | 444.00 | 19.95 |
March | 514.00 | 20.60 | 417.33 | 20.46 | 417.33 | 20.41 |
April | 398.50 | 21.99 | 146.00 | 21.71 | 122.50 | 21.44 |
May | 250.83 | 23.55 | 54.00 | 23.80 | 2.17 | 23.83 |
June | 34.83 | 24.26 | 246.17 | 24.52 | 6.33 | 24.58 |
July | 13.17 | 25.76 | 382.83 | 24.55 | 8.67 | 24.60 |
August | 102.00 | 23.51 | 211.33 | 24.12 | 3.50 | 24.16 |
September | 401.17 | 22.54 | 44.50 | 22.50 | 29.33 | 22.39 |
October | 502.00 | 20.66 | 335.17 | 20.47 | 335.17 | 20.39 |
November | 489.00 | 19.86 | 488.33 | 19.86 | 488.33 | 19.86 |
December | 497.00 | 19.81 | 497.00 | 19.81 | 497.00 | 19.81 |
Annual Sum or Average | 4158.50 | 20.88 | 3768.67 | 20.99 | 2856.33 | 20.74 |
Minimum of Months | 13.17 | 19.81 | 44.50 | 19.81 | 2.17 | 19.81 |
Maximum of Months | 514.00 | 25.76 | 502.00 | 24.55 | 502.00 | 24.60 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.35942 | 15.09843 | -0.5699 | 13.60648 |
February | 454.00000 | 21.98468 | 16.86198 | -0.3975 | 9.86119 |
March | 514.00000 | 22.88239 | 17.76942 | -0.1696 | 6.51714 |
April | 485.00000 | 23.88288 | 16.92894 | 0.11685 | 5.92260 |
May | 508.00000 | 24.33175 | 21.24251 | -0.5515 | 11.66864 |
June | 496.00000 | 24.41738 | 32.81211 | -0.4066 | 8.99829 |
July | 497.00000 | 24.48956 | 40.93479 | -0.3260 | 7.85496 |
August | 514.00000 | 24.39912 | 36.32985 | -0.3962 | 8.84410 |
September | 485.00000 | 24.27892 | 27.60834 | -0.5651 | 12.27085 |
October | 502.00000 | 23.45952 | 22.54099 | 0.01948 | 5.80275 |
November | 489.00000 | 22.07500 | 15.76544 | -0.3872 | 9.10459 |
December | 497.00000 | 21.53679 | 12.83739 | -0.5343 | 11.71143 |
Annual Sum or Average | 5943.00000 | 23.26815 | 23.12940 | -0.3473 | 9.33996 |
Minimum of Months | 454.00000 | 21.35942 | 12.83739 | -0.5699 | 5.80275 |
Maximum of Months | 514.00000 | 24.48956 | 40.93479 | 0.11685 | 13.60648 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.42620 | 17.21533 | -0.7903 | 19.78846 |
February | 454.00000 | 20.75251 | 19.59351 | -0.6784 | 16.17103 |
March | 514.00000 | 21.38989 | 20.57165 | -0.4955 | 11.04390 |
April | 485.00000 | 22.91643 | 18.62866 | -0.1049 | 6.95751 |
May | 508.00000 | 24.06180 | 22.04724 | -0.6610 | 14.55765 |
June | 496.00000 | 24.26913 | 33.68440 | -0.4746 | 10.01317 |
July | 497.00000 | 24.33502 | 41.87213 | -0.3972 | 8.66131 |
August | 514.00000 | 24.21618 | 37.42529 | -0.4857 | 10.34195 |
September | 485.00000 | 23.57603 | 30.31888 | -0.8178 | 20.40311 |
October | 502.00000 | 21.75343 | 26.59334 | -0.3647 | 9.16241 |
November | 489.00000 | 20.67155 | 18.35902 | -0.7135 | 16.68005 |
December | 497.00000 | 20.48820 | 14.31864 | -0.7918 | 19.20346 |
Annual Sum or Average | 5943.00000 | 22.41841 | 25.11345 | -0.5638 | 13.54608 |
Minimum of Months | 454.00000 | 20.42620 | 14.31864 | -0.8178 | 6.95751 |
Maximum of Months | 514.00000 | 24.33502 | 41.87213 | -0.1049 | 20.40311 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.05550 | 17.35754 | -0.9247 | 25.18813 |
February | 454.00000 | 20.21732 | 20.04413 | -0.8459 | 22.36830 |
March | 514.00000 | 20.76108 | 20.63352 | -0.6808 | 16.22861 |
April | 485.00000 | 22.19561 | 19.30979 | -0.2885 | 9.59260 |
May | 508.00000 | 23.79616 | 22.63139 | -0.7606 | 18.10924 |
June | 496.00000 | 24.19450 | 33.67116 | -0.5049 | 10.61314 |
July | 497.00000 | 24.25420 | 41.94558 | -0.4301 | 9.15683 |
August | 514.00000 | 24.03355 | 37.88110 | -0.5618 | 12.31908 |
September | 485.00000 | 22.80869 | 32.31755 | -1.0923 | 32.03382 |
October | 502.00000 | 20.86380 | 27.56566 | -0.6061 | 14.59559 |
November | 489.00000 | 20.11123 | 18.60821 | -0.8941 | 23.84544 |
December | 497.00000 | 20.05628 | 14.54505 | -0.9427 | 25.61840 |
Annual Sum or Average | 5943.00000 | 21.96152 | 25.59989 | -0.7096 | 18.23932 |
Minimum of Months | 454.00000 | 20.05550 | 14.54505 | -1.0923 | 9.15683 |
Maximum of Months | 514.00000 | 24.25420 | 41.94558 | -0.2885 | 32.03382 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.61416 | 17.10556 | -1.1416 | 34.22065 |
February | 454.00000 | 19.73393 | 20.22279 | -1.0633 | 31.10930 |
March | 514.00000 | 20.10255 | 21.07000 | -0.9101 | 24.64517 |
April | 485.00000 | 21.19709 | 20.03451 | -0.5347 | 14.82471 |
May | 508.00000 | 23.47208 | 23.18906 | -0.8555 | 22.05378 |
June | 496.00000 | 24.15873 | 33.93170 | -0.4701 | 10.21467 |
July | 497.00000 | 24.26013 | 41.93802 | -0.3931 | 8.79217 |
August | 514.00000 | 23.72223 | 39.14254 | -0.6557 | 15.76616 |
September | 485.00000 | 21.80326 | 34.52949 | -1.4341 | 48.05130 |
October | 502.00000 | 20.15011 | 27.94639 | -0.8341 | 22.03575 |
November | 489.00000 | 19.66708 | 18.62095 | -1.1119 | 32.96424 |
December | 497.00000 | 19.59285 | 14.08164 | -1.1705 | 35.38281 |
Annual Sum or Average | 5943.00000 | 21.47411 | 26.04200 | -0.8788 | 24.89902 |
Minimum of Months | 454.00000 | 19.59285 | 14.08164 | -1.4341 | 8.79217 |
Maximum of Months | 514.00000 | 24.26013 | 41.93802 | -0.3931 | 48.05130 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.71908 | 17.65827 | -1.1189 | 33.19000 |
February | 454.00000 | 19.84567 | 21.26040 | -1.0138 | 29.10870 |
March | 514.00000 | 20.53124 | 21.98990 | -0.7514 | 19.98388 |
April | 485.00000 | 22.15860 | 19.30790 | -0.2678 | 11.65454 |
May | 508.00000 | 23.95569 | 21.74274 | -0.5735 | 14.70457 |
June | 496.00000 | 24.26229 | 33.40815 | -0.3370 | 8.72481 |
July | 497.00000 | 24.42098 | 41.21026 | -0.2343 | 7.81969 |
August | 514.00000 | 24.04006 | 37.92384 | -0.4631 | 11.23500 |
September | 485.00000 | 22.55741 | 33.82200 | -1.1534 | 36.50805 |
October | 502.00000 | 20.38036 | 28.79131 | -0.7544 | 19.93001 |
November | 489.00000 | 19.74482 | 19.26269 | -1.0921 | 32.10002 |
December | 497.00000 | 19.68790 | 14.48829 | -1.1540 | 34.60101 |
Annual Sum or Average | 5943.00000 | 21.79332 | 25.95507 | -0.7398 | 21.51513 |
Minimum of Months | 454.00000 | 19.68790 | 14.48829 | -1.1540 | 7.81969 |
Maximum of Months | 514.00000 | 24.42098 | 41.21026 | -0.2343 | 36.50805 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.74711 | 17.35181 | -1.0919 | 32.15480 |
February | 454.00000 | 20.18675 | 20.30554 | -0.8962 | 25.38753 |
March | 514.00000 | 21.10189 | 20.02780 | -0.5926 | 17.62026 |
April | 485.00000 | 22.50798 | 17.52462 | -0.1519 | 11.78304 |
May | 508.00000 | 23.72689 | 21.82070 | -0.6705 | 18.72422 |
June | 496.00000 | 24.18014 | 33.42395 | -0.3913 | 9.90779 |
July | 497.00000 | 24.31518 | 41.41426 | -0.2943 | 8.69996 |
August | 514.00000 | 23.99111 | 37.66086 | -0.4637 | 12.53960 |
September | 485.00000 | 22.70119 | 32.18810 | -1.0737 | 34.20912 |
October | 502.00000 | 20.73702 | 27.28535 | -0.6522 | 17.93000 |
November | 489.00000 | 19.82590 | 18.96072 | -1.0406 | 30.22744 |
December | 497.00000 | 19.70239 | 14.19358 | -1.1420 | 34.09823 |
Annual Sum or Average | 5943.00000 | 21.90986 | 25.23326 | -0.7029 | 21.02557 |
Minimum of Months | 454.00000 | 19.70239 | 14.19358 | -1.1420 | 8.69996 |
Maximum of Months | 514.00000 | 24.31518 | 41.41426 | -0.1519 | 34.20912 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.71861 | 17.59613 | -1.1222 | 33.31071 |
February | 454.00000 | 19.83240 | 21.04917 | -1.0327 | 29.82782 |
March | 514.00000 | 20.31654 | 22.01433 | -0.8369 | 22.51369 |
April | 485.00000 | 21.88415 | 19.65385 | -0.3353 | 13.29699 |
May | 508.00000 | 23.59413 | 23.16059 | -0.7679 | 20.64729 |
June | 496.00000 | 24.18809 | 34.06860 | -0.4101 | 10.02957 |
July | 497.00000 | 24.28264 | 42.14415 | -0.3453 | 8.77734 |
August | 514.00000 | 23.84974 | 39.07264 | -0.5687 | 14.11884 |
September | 485.00000 | 22.16309 | 34.58249 | -1.2976 | 42.61862 |
October | 502.00000 | 20.23370 | 28.93659 | -0.8043 | 21.29153 |
November | 489.00000 | 19.74739 | 19.23508 | -1.0915 | 32.07777 |
December | 497.00000 | 19.68829 | 14.47844 | -1.1545 | 34.61863 |
Annual Sum or Average | 5943.00000 | 21.64184 | 26.38904 | -0.8115 | 23.49279 |
Minimum of Months | 454.00000 | 19.68829 | 14.47844 | -1.2976 | 8.77734 |
Maximum of Months | 514.00000 | 24.28264 | 42.14415 | -0.3353 | 42.61862 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.63123 | 15.95179 | -1.1243 | 33.25928 |
February | 454.00000 | 19.72509 | 18.65897 | -1.0699 | 31.10019 |
March | 514.00000 | 20.21856 | 20.27776 | -0.9012 | 23.64198 |
April | 485.00000 | 20.98326 | 20.78087 | -0.6017 | 14.49190 |
May | 508.00000 | 23.19260 | 24.86541 | -0.9914 | 26.77844 |
June | 496.00000 | 24.09975 | 34.72726 | -0.5436 | 11.52332 |
July | 497.00000 | 24.23104 | 42.52986 | -0.4345 | 9.23862 |
August | 514.00000 | 23.91770 | 39.11051 | -0.6020 | 13.45537 |
September | 485.00000 | 22.50380 | 32.82886 | -1.1851 | 35.97349 |
October | 502.00000 | 20.68611 | 26.41686 | -0.6644 | 15.73486 |
November | 489.00000 | 19.89405 | 17.52294 | -1.0128 | 28.32025 |
December | 497.00000 | 19.74153 | 13.53358 | -1.1014 | 32.03711 |
Annual Sum or Average | 5943.00000 | 21.58668 | 25.66972 | -0.8506 | 22.87396 |
Minimum of Months | 454.00000 | 19.63123 | 13.53358 | -1.1851 | 9.23862 |
Maximum of Months | 514.00000 | 24.23104 | 42.52986 | -0.4345 | 35.97349 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.80911 | 16.42835 | -1.0913 | 31.75816 |
February | 454.00000 | 19.94050 | 19.50136 | -1.0052 | 28.27572 |
March | 514.00000 | 20.60800 | 21.22805 | -0.7490 | 18.61909 |
April | 485.00000 | 22.21835 | 19.89083 | -0.2682 | 10.07588 |
May | 508.00000 | 24.03752 | 22.21513 | -0.5888 | 14.02813 |
June | 496.00000 | 24.27287 | 33.75776 | -0.3799 | 8.87877 |
July | 497.00000 | 24.46244 | 41.41148 | -0.2458 | 7.44592 |
August | 514.00000 | 24.22307 | 37.60460 | -0.4029 | 9.32111 |
September | 485.00000 | 23.32051 | 31.44358 | -0.8791 | 24.47328 |
October | 502.00000 | 21.07590 | 26.90405 | -0.5521 | 13.52807 |
November | 489.00000 | 19.93719 | 18.37348 | -1.0023 | 27.89079 |
December | 497.00000 | 19.81195 | 14.03775 | -1.0934 | 31.69616 |
Annual Sum or Average | 5943.00000 | 21.99408 | 25.29290 | -0.6854 | 18.72974 |
Minimum of Months | 454.00000 | 19.80911 | 14.03775 | -1.0934 | 7.44592 |
Maximum of Months | 514.00000 | 24.46244 | 41.41148 | -0.2458 | 31.75816 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 18.46150 | 13.79451 | -1.3358 | 42.50239 |
February | 454.00000 | 19.20090 | 15.80959 | -1.1047 | 32.58901 |
March | 514.00000 | 20.08254 | 16.34091 | -0.8035 | 21.41640 |
April | 485.00000 | 22.17139 | 16.50449 | -0.2126 | 10.29168 |
May | 508.00000 | 23.45447 | 22.19999 | -0.7790 | 21.03306 |
June | 496.00000 | 23.99414 | 34.05824 | -0.4869 | 11.62701 |
July | 497.00000 | 24.20688 | 41.82772 | -0.3467 | 9.38206 |
August | 514.00000 | 23.95779 | 37.51653 | -0.4546 | 11.87964 |
September | 485.00000 | 22.89160 | 29.33010 | -0.9492 | 28.48695 |
October | 502.00000 | 20.79272 | 22.58738 | -0.5801 | 15.21761 |
November | 489.00000 | 18.85280 | 14.43175 | -1.1909 | 36.24896 |
December | 497.00000 | 18.38402 | 11.57779 | -1.3668 | 43.75596 |
Annual Sum or Average | 5943.00000 | 21.38950 | 23.07318 | -0.7984 | 23.60420 |
Minimum of Months | 454.00000 | 18.38402 | 11.57779 | -1.3668 | 9.38206 |
Maximum of Months | 514.00000 | 24.20688 | 41.82772 | -0.2126 | 43.75596 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.80702 | 16.36344 | -1.0949 | 31.90563 |
February | 454.00000 | 19.89901 | 19.34591 | -1.0298 | 29.31397 |
March | 514.00000 | 20.35817 | 21.24960 | -0.8439 | 21.64629 |
April | 485.00000 | 22.01028 | 20.13233 | -0.3182 | 10.77949 |
May | 508.00000 | 23.61947 | 24.05574 | -0.8049 | 20.41500 |
June | 496.00000 | 24.20513 | 34.45052 | -0.4526 | 10.15149 |
July | 497.00000 | 24.31811 | 42.42619 | -0.3625 | 8.42863 |
August | 514.00000 | 24.10623 | 38.57496 | -0.4886 | 10.96203 |
September | 485.00000 | 22.95003 | 32.43026 | -1.0184 | 29.51498 |
October | 502.00000 | 20.79362 | 27.28161 | -0.6311 | 15.07232 |
November | 489.00000 | 19.93869 | 18.35674 | -1.0020 | 27.88094 |
December | 497.00000 | 19.81174 | 14.02668 | -1.0941 | 31.72133 |
Annual Sum or Average | 5943.00000 | 21.83462 | 25.79116 | -0.7596 | 20.56019 |
Minimum of Months | 454.00000 | 19.80702 | 14.02668 | -1.0949 | 8.42863 |
Maximum of Months | 514.00000 | 24.31811 | 42.42619 | -0.3182 | 31.90563 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.80018 | 17.73149 | -1.0437 | 29.98311 |
February | 454.00000 | 19.92003 | 20.54812 | -0.9636 | 26.89706 |
March | 514.00000 | 20.38098 | 21.33210 | -0.7952 | 19.94844 |
April | 485.00000 | 21.77034 | 19.69092 | -0.3766 | 11.22665 |
May | 508.00000 | 23.82962 | 22.55642 | -0.7293 | 16.98669 |
June | 496.00000 | 24.24584 | 33.80875 | -0.4365 | 9.42126 |
July | 497.00000 | 24.36335 | 41.80370 | -0.3539 | 8.13350 |
August | 514.00000 | 24.00033 | 38.49876 | -0.5540 | 12.31462 |
September | 485.00000 | 22.56103 | 33.03219 | -1.1586 | 35.12430 |
October | 502.00000 | 20.56501 | 27.61309 | -0.6851 | 16.89179 |
November | 489.00000 | 19.83908 | 19.34720 | -1.0060 | 28.40835 |
December | 497.00000 | 19.78441 | 14.74994 | -1.0666 | 30.75631 |
Annual Sum or Average | 5943.00000 | 21.77248 | 25.94840 | -0.7620 | 20.41528 |
Minimum of Months | 454.00000 | 19.78441 | 14.74994 | -1.1586 | 8.13350 |
Maximum of Months | 514.00000 | 24.36335 | 41.80370 | -0.3539 | 35.12430 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.64014 | 17.83251 | -1.0796 | 31.63935 |
February | 385.00000 | 19.84546 | 21.04010 | -0.9626 | 26.96092 |
March | 433.00000 | 20.76982 | 21.56055 | -0.6626 | 16.73850 |
April | 410.00000 | 22.52037 | 18.22107 | -0.1697 | 9.62659 |
May | 430.00000 | 24.19626 | 21.14189 | -0.5017 | 12.52252 |
June | 418.00000 | 24.38752 | 33.15216 | -0.3127 | 8.33246 |
July | 422.00000 | 24.57811 | 40.94465 | -0.2002 | 7.55186 |
August | 433.00000 | 24.22670 | 37.22343 | -0.4076 | 9.85152 |
September | 410.00000 | 23.09680 | 31.74808 | -0.9542 | 27.94887 |
October | 427.00000 | 20.74341 | 27.78693 | -0.6284 | 15.96144 |
November | 417.00000 | 19.66481 | 19.74855 | -1.0416 | 30.04659 |
December | 422.00000 | 19.59246 | 14.83378 | -1.1105 | 32.80683 |
Annual Sum or Average | 5034.00000 | 21.95260 | 25.47537 | -0.6671 | 19.08092 |
Minimum of Months | 385.00000 | 19.59246 | 14.83378 | -1.1105 | 7.55186 |
Maximum of Months | 433.00000 | 24.57811 | 40.94465 | -0.1697 | 32.80683 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.89894 | 17.88231 | -1.0006 | 28.30677 |
February | 454.00000 | 20.51870 | 20.11068 | -0.7723 | 20.85433 |
March | 514.00000 | 21.49817 | 19.68773 | -0.4587 | 13.92102 |
April | 485.00000 | 22.96388 | 16.92909 | -0.0209 | 9.66379 |
May | 508.00000 | 24.01471 | 21.32616 | -0.5658 | 14.43593 |
June | 496.00000 | 24.27976 | 33.28052 | -0.3554 | 8.84516 |
July | 497.00000 | 24.42047 | 41.24865 | -0.2560 | 7.82276 |
August | 514.00000 | 24.18512 | 37.17723 | -0.3872 | 10.11694 |
September | 485.00000 | 23.27339 | 30.62240 | -0.8532 | 24.50577 |
October | 502.00000 | 21.28139 | 26.37995 | -0.4825 | 13.36514 |
November | 489.00000 | 20.04544 | 19.33746 | -0.9278 | 25.54844 |
December | 497.00000 | 19.83171 | 14.88914 | -1.0498 | 30.05693 |
Annual Sum or Average | 5943.00000 | 22.19958 | 24.96017 | -0.5923 | 17.22278 |
Minimum of Months | 454.00000 | 19.83171 | 14.88914 | -1.0498 | 7.82276 |
Maximum of Months | 514.00000 | 24.42047 | 41.24865 | -0.0209 | 30.05693 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.84397 | 18.39708 | -1.0355 | 29.62438 |
February | 454.00000 | 19.97069 | 21.40979 | -0.9424 | 26.10236 |
March | 514.00000 | 20.59872 | 22.07586 | -0.7231 | 18.27149 |
April | 485.00000 | 22.38785 | 19.04232 | -0.1931 | 10.32481 |
May | 508.00000 | 23.91210 | 22.49380 | -0.6533 | 15.85769 |
June | 496.00000 | 24.28787 | 33.87258 | -0.3734 | 8.98525 |
July | 497.00000 | 24.38994 | 41.93887 | -0.3054 | 7.91035 |
August | 514.00000 | 24.07993 | 38.39882 | -0.4810 | 11.17157 |
September | 485.00000 | 22.82206 | 32.86339 | -1.0513 | 31.26152 |
October | 502.00000 | 20.66104 | 28.40410 | -0.6550 | 16.31326 |
November | 489.00000 | 19.86460 | 20.21610 | -0.9957 | 28.02151 |
December | 497.00000 | 19.80802 | 15.35100 | -1.0642 | 30.66658 |
Annual Sum or Average | 5943.00000 | 21.90243 | 26.25928 | -0.7040 | 19.45178 |
Minimum of Months | 454.00000 | 19.80802 | 15.35100 | -1.0642 | 7.91035 |
Maximum of Months | 514.00000 | 24.38994 | 41.93887 | -0.1931 | 31.26152 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3750222.28 | 1073688.74 | 0.82 | 3735435.99 | 14786.29 | 0.00 | 0.31 | 19-JAN-07:01 | 0.00 | 01-JAN-00:02 | 7350.20 | 19-JAN-07:01 | 7350.20 | 19-JAN-07:01 | 26.69 | 07-JAN-07:05 | 2024.09 | 19-JAN-07:01 | 0.00 |
February | 9420584.80 | 2752930.91 | 5.31 | 8887937.07 | 532647.73 | 0.00 | 0.31 | 07-FEB-07:01 | 0.00 | 01-FEB-00:10 | 7357.69 | 07-FEB-07:01 | 7357.69 | 07-FEB-07:01 | 137.97 | 09-FEB-18:13 | 2026.01 | 07-FEB-07:01 | 0.00 |
March | 18327030.92 | 5381897.09 | 10.53 | 17742470.07 | 584560.85 | 0.00 | 0.11 | 24-MAR-07:18 | 0.00 | 01-MAR-00:10 | 2513.27 | 24-MAR-07:18 | 2513.27 | 24-MAR-07:18 | 122.13 | 21-MAR-17:02 | 725.66 | 24-MAR-07:18 | 0.00 |
April | 0.214911E+10 | 0.561438E+09 | 85.76 | 0.214897E+10 | 142003.88 | 0.00 | 0.91 | 21-APR-16:00 | 0.00 | 01-APR-00:10 | 25752.26 | 21-APR-16:00 | 25752.26 | 21-APR-16:00 | 62.65 | 18-APR-16:01 | 6030.59 | 21-APR-16:00 | 0.00 |
May | 0.576633E+10 | 0.149648E+10 | 185.23 | 0.574228E+10 | 24055388.71 | 0.00 | 1.00 | 31-MAY-14:50 | 0.00 | 01-MAY-00:10 | 35435.84 | 31-MAY-16:00 | 35435.84 | 31-MAY-16:00 | 619.72 | 16-MAY-18:20 | 8089.45 | 31-MAY-16:00 | 0.00 |
June | 0.200118E+11 | 0.490215E+10 | 313.37 | 0.191429E+11 | 0.868914E+09 | 0.00 | 1.00 | 09-JUN-12:05 | 0.00 | 01-JUN-00:10 | 62495.75 | 30-JUN-11:40 | 55398.53 | 20-JUN-15:50 | 15601.99 | 30-JUN-06:02 | 14973.78 | 30-JUN-12:30 | 0.00 |
July | 0.284737E+11 | 0.681989E+10 | 335.08 | 0.261871E+11 | 0.228659E+10 | 0.00 | 1.00 | 03-JUL-14:40 | 0.00 | 01-JUL-00:10 | 63270.65 | 11-JUL-15:50 | 60614.58 | 12-JUL-16:00 | 31370.10 | 03-JUL-15:00 | 15249.34 | 11-JUL-16:00 | 0.00 |
August | 0.167614E+11 | 0.409209E+10 | 274.69 | 0.156166E+11 | 0.114486E+10 | 0.00 | 1.00 | 01-AUG-14:20 | 0.00 | 01-AUG-00:10 | 59042.90 | 11-AUG-15:50 | 59042.90 | 11-AUG-15:50 | 7954.14 | 03-AUG-12:20 | 13985.66 | 11-AUG-15:50 | 0.00 |
September | 0.349108E+10 | 0.902781E+09 | 120.15 | 0.338451E+10 | 0.106566E+09 | 0.00 | 1.00 | 07-SEP-15:30 | 0.00 | 01-SEP-00:10 | 29409.24 | 07-SEP-16:00 | 29409.24 | 07-SEP-16:00 | 1735.29 | 05-SEP-15:00 | 6715.89 | 07-SEP-16:00 | 0.00 |
October | 98663962.01 | 28336419.12 | 21.79 | 96654144.02 | 2009817.99 | 0.00 | 0.25 | 05-OCT-16:00 | 0.00 | 01-OCT-00:10 | 5877.04 | 05-OCT-16:00 | 5877.04 | 05-OCT-16:00 | 228.43 | 04-OCT-17:05 | 1641.54 | 05-OCT-16:00 | 0.00 |
November | 3542096.11 | 1031520.88 | 1.54 | 3476746.69 | 65349.42 | 0.00 | 0.18 | 21-NOV-07:01 | 0.00 | 01-NOV-00:10 | 4285.63 | 21-NOV-07:01 | 4285.63 | 21-NOV-07:01 | 38.65 | 02-NOV-15:30 | 1215.80 | 21-NOV-07:01 | 0.00 |
December | 2134069.17 | 617423.20 | 0.78 | 2132515.29 | 1553.88 | 0.00 | 0.22 | 20-DEC-07:01 | 0.00 | 01-DEC-00:10 | 5248.28 | 20-DEC-07:01 | 5248.28 | 20-DEC-07:01 | 2.59 | 19-DEC-18:40 | 1474.91 | 20-DEC-07:01 | 0.00 |
Annual Sum or Average | 0.767893E+11 | 0.188140E+11 | 1355.04 | 0.723550E+11 | 0.443434E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2134069.17 | 617423.20 | 0.78 | 2132515.29 | 1553.88 | 0.00 | 0.11 | 0.00 | 2513.27 | 2513.27 | 2.59 | 725.66 | 0.00 | ||||||
Maximum of Months | 0.284737E+11 | 0.681989E+10 | 335.08 | 0.261871E+11 | 0.228659E+10 | 0.00 | 1.00 | 0.00 | 63270.65 | 60614.58 | 31370.10 | 15249.34 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3243479.74 | 919144.47 | 0.37 | 3243479.74 | -0.0 | 0.00 | 0.28 | 19-JAN-07:01 | 0.00 | 01-JAN-00:02 | 5946.68 | 19-JAN-07:01 | 5946.68 | 19-JAN-07:01 | 0.00 | 05-JAN-07:01 | 1648.94 | 19-JAN-07:01 | 0.00 |
February | 4826356.62 | 1351680.16 | 0.51 | 4805218.08 | 21138.55 | 0.00 | 0.34 | 10-FEB-07:01 | 0.00 | 01-FEB-00:10 | 7428.57 | 10-FEB-07:01 | 7428.57 | 10-FEB-07:01 | 53.21 | 10-FEB-13:01 | 2027.60 | 10-FEB-07:01 | 0.00 |
March | 9898226.33 | 2815866.55 | 3.86 | 9760791.88 | 137434.45 | 0.00 | 0.41 | 21-MAR-06:01 | 0.00 | 01-MAR-00:10 | 9100.60 | 21-MAR-06:01 | 9100.60 | 21-MAR-06:01 | 87.22 | 22-MAR-06:03 | 2440.85 | 21-MAR-06:01 | 0.00 |
April | 0.103667E+09 | 30027497.19 | 38.82 | 0.103420E+09 | 246870.45 | 0.00 | 0.28 | 05-APR-06:01 | 0.00 | 01-APR-00:10 | 6059.20 | 05-APR-06:01 | 6059.20 | 05-APR-06:01 | 63.63 | 29-APR-09:10 | 1678.12 | 05-APR-06:01 | 0.00 |
May | 0.402554E+10 | 0.103917E+10 | 157.81 | 0.401365E+10 | 11892717.67 | 0.00 | 1.00 | 12-MAY-12:50 | 0.00 | 01-MAY-00:10 | 36396.43 | 31-MAY-16:00 | 36396.43 | 31-MAY-16:00 | 378.14 | 14-MAY-11:54 | 8306.39 | 31-MAY-16:00 | 0.00 |
June | 0.197918E+11 | 0.481528E+10 | 323.40 | 0.189666E+11 | 0.825207E+09 | 0.00 | 1.00 | 08-JUN-12:05 | 0.00 | 01-JUN-00:10 | 64360.06 | 30-JUN-12:05 | 56284.80 | 29-JUN-14:05 | 16511.60 | 30-JUN-06:02 | 15406.69 | 30-JUN-12:05 | 0.00 |
July | 0.266432E+11 | 0.637546E+10 | 344.72 | 0.245262E+11 | 0.211701E+10 | 0.00 | 1.00 | 03-JUL-14:30 | 0.00 | 01-JUL-00:10 | 59970.75 | 11-JUL-15:30 | 56853.05 | 21-JUL-14:05 | 30825.36 | 03-JUL-15:00 | 14360.29 | 11-JUL-16:00 | 0.00 |
August | 0.144453E+11 | 0.352516E+10 | 270.99 | 0.133910E+11 | 0.105428E+10 | 0.00 | 1.00 | 01-AUG-12:50 | 0.00 | 01-AUG-00:10 | 54007.05 | 11-AUG-15:20 | 54007.05 | 11-AUG-15:20 | 6969.63 | 04-AUG-10:40 | 12646.06 | 11-AUG-15:40 | 0.00 |
September | 0.571795E+09 | 0.156284E+09 | 57.28 | 0.551157E+09 | 20637809.26 | 0.00 | 0.71 | 07-SEP-13:10 | 0.00 | 01-SEP-00:10 | 16985.67 | 07-SEP-13:10 | 16985.67 | 07-SEP-13:10 | 537.95 | 02-SEP-17:55 | 4210.94 | 07-SEP-13:10 | 0.00 |
October | 21102258.20 | 6022510.02 | 4.23 | 20159079.42 | 943178.78 | 0.00 | 0.38 | 12-OCT-06:01 | 0.00 | 01-OCT-00:10 | 8400.35 | 12-OCT-06:01 | 8400.35 | 12-OCT-06:01 | 189.83 | 03-OCT-13:10 | 2269.54 | 12-OCT-06:01 | 0.00 |
November | 2590156.68 | 735257.94 | 0.23 | 2590156.68 | -0.0 | 0.00 | 0.25 | 02-NOV-06:01 | 0.00 | 01-NOV-00:10 | 5364.95 | 02-NOV-06:01 | 5364.95 | 02-NOV-06:01 | 0.00 | 01-NOV-06:01 | 1496.98 | 02-NOV-06:01 | 0.00 |
December | 1843989.97 | 527938.08 | 0.53 | 1840015.83 | 3974.14 | 0.00 | 0.24 | 23-DEC-07:03 | 0.00 | 01-DEC-00:10 | 4996.83 | 23-DEC-07:03 | 4996.83 | 23-DEC-07:03 | 7.73 | 23-DEC-14:10 | 1399.83 | 23-DEC-07:03 | 0.00 |
Annual Sum or Average | 0.656248E+11 | 0.159538E+11 | 1202.74 | 0.615944E+11 | 0.403039E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 1843989.97 | 527938.08 | 0.23 | 1840015.83 | -0.0 | 0.00 | 0.24 | 0.00 | 4996.83 | 4996.83 | 0.00 | 1399.83 | 0.00 | ||||||
Maximum of Months | 0.266432E+11 | 0.637546E+10 | 344.72 | 0.245262E+11 | 0.211701E+10 | 0.00 | 1.00 | 0.00 | 64360.06 | 56853.05 | 30825.36 | 15406.69 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 50470.84 | 14844.29 | 0.02 | 50470.84 | 0.00 | 0.00 | 0.03 | 19-JAN-07:01 | 0.00 | 01-JAN-00:02 | 672.94 | 19-JAN-07:01 | 672.94 | 19-JAN-07:01 | 0.00 | 19-JAN-07:01 | 197.92 | 19-JAN-07:01 | 0.00 |
February | 499609.85 | 143777.21 | 0.09 | 499609.85 | 0.00 | 0.00 | 0.15 | 09-FEB-07:02 | 0.00 | 01-FEB-00:10 | 3343.61 | 09-FEB-07:02 | 3343.61 | 09-FEB-07:02 | 0.00 | 07-FEB-07:01 | 956.76 | 09-FEB-07:02 | 0.00 |
March | 2644461.16 | 775735.33 | 2.37 | 2497650.96 | 146810.19 | 0.00 | 0.15 | 23-MAR-06:02 | 0.00 | 01-MAR-00:10 | 3363.02 | 23-MAR-06:02 | 3363.02 | 23-MAR-06:02 | 57.98 | 22-MAR-10:40 | 962.13 | 23-MAR-06:02 | 0.00 |
April | 0.596498E+09 | 0.155327E+09 | 57.51 | 0.595759E+09 | 739077.17 | 0.00 | 0.98 | 21-APR-15:10 | 0.00 | 01-APR-00:10 | 27626.70 | 21-APR-15:10 | 27626.70 | 21-APR-15:10 | 43.16 | 18-APR-11:50 | 6342.51 | 21-APR-15:10 | 0.00 |
May | 0.388751E+10 | 0.100925E+10 | 159.95 | 0.386812E+10 | 19390984.26 | 0.00 | 1.00 | 12-MAY-13:20 | 0.00 | 01-MAY-00:10 | 38159.07 | 31-MAY-16:00 | 38159.07 | 31-MAY-16:00 | 533.85 | 31-MAY-06:02 | 8709.43 | 31-MAY-16:00 | 0.00 |
June | 0.201598E+11 | 0.493122E+10 | 320.83 | 0.193024E+11 | 0.857344E+09 | 0.00 | 1.00 | 12-JUN-13:00 | 0.00 | 01-JUN-00:10 | 67113.25 | 30-JUN-12:30 | 61110.22 | 29-JUN-14:30 | 13960.69 | 30-JUN-06:02 | 16387.30 | 30-JUN-14:30 | 0.00 |
July | 0.271059E+11 | 0.651916E+10 | 343.09 | 0.249614E+11 | 0.214448E+10 | 0.00 | 1.00 | 03-JUL-14:40 | 0.00 | 01-JUL-00:10 | 61943.53 | 21-JUL-14:30 | 61943.53 | 21-JUL-14:30 | 30540.72 | 03-JUL-15:00 | 15266.95 | 21-JUL-14:40 | 0.00 |
August | 0.141398E+11 | 0.347599E+10 | 267.59 | 0.130102E+11 | 0.112964E+10 | 0.00 | 1.00 | 02-AUG-12:05 | 0.00 | 01-AUG-00:10 | 56553.23 | 11-AUG-15:50 | 56553.23 | 11-AUG-15:50 | 6839.51 | 03-AUG-14:40 | 13396.88 | 11-AUG-15:50 | 0.00 |
September | 0.823024E+09 | 0.220768E+09 | 54.40 | 0.795710E+09 | 27313856.23 | 0.00 | 0.76 | 08-SEP-15:40 | 0.00 | 01-SEP-00:10 | 20127.23 | 08-SEP-15:40 | 20127.23 | 08-SEP-15:40 | 851.42 | 09-SEP-16:06 | 4921.24 | 08-SEP-15:40 | 0.00 |
October | 6761681.27 | 1972189.94 | 3.64 | 6376430.50 | 385250.77 | 0.00 | 0.19 | 02-OCT-06:03 | 0.00 | 01-OCT-00:10 | 4393.72 | 02-OCT-06:03 | 4393.72 | 02-OCT-06:03 | 154.28 | 03-OCT-06:03 | 1243.99 | 02-OCT-06:03 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.667224E+11 | 0.163146E+11 | 1209.49 | 0.625430E+11 | 0.417944E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.271059E+11 | 0.651916E+10 | 343.09 | 0.249614E+11 | 0.214448E+10 | 0.00 | 1.00 | 0.00 | 67113.25 | 61943.53 | 30540.72 | 16387.30 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 39.96 | 0.00 | 39.96 | 0.00 | 2953.81 | 0.00 | 0.00 | 0.00 |
February | 176.66 | 0.00 | 176.66 | 0.00 | 2635.45 | 0.00 | 0.00 | 0.00 |
March | 472.48 | 0.00 | 472.48 | 44.60 | 1933.38 | 0.00 | 0.00 | 0.00 |
April | 853.72 | 17.68 | 836.04 | 365.55 | 1019.88 | 0.00 | 0.00 | 0.00 |
May | 1306.08 | 204.17 | 1101.90 | 1034.04 | 466.93 | 0.00 | 0.00 | 0.00 |
June | 1706.65 | 377.36 | 1329.29 | 1704.30 | 218.67 | 0.00 | 0.00 | 0.00 |
July | 1431.90 | 230.38 | 1201.52 | 1461.14 | 267.71 | 0.00 | 0.00 | 0.00 |
August | 914.28 | 49.35 | 864.93 | 762.13 | 443.70 | 0.00 | 0.00 | 0.00 |
September | 511.03 | 0.45 | 510.58 | 204.45 | 876.96 | 0.00 | 0.00 | 0.00 |
October | 248.69 | 0.00 | 248.69 | 22.26 | 1629.73 | 0.00 | 0.00 | 0.00 |
November | 77.18 | 0.00 | 77.18 | 0.00 | 2889.75 | 0.00 | 0.00 | 0.00 |
December | 12.12 | 0.00 | 12.12 | 0.00 | 3114.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 648.20 | 73.60 | 574.60 | 469.26 | 1531.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.12 | 0.00 | 12.12 | 0.00 | 218.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1706.65 | 377.36 | 1329.29 | 1704.30 | 3114.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.53 | 21.43 | 48.10 | 6.29 | 1911.41 | 0.00 | 0.00 | 0.00 |
February | 386.82 | 184.08 | 202.74 | 211.27 | 1588.97 | 0.00 | 0.00 | 0.00 |
March | 1107.49 | 561.55 | 545.95 | 962.51 | 1157.32 | 0.00 | 0.00 | 0.00 |
April | 1523.07 | 771.86 | 751.22 | 1444.56 | 633.65 | 0.00 | 0.00 | 0.00 |
May | 2215.71 | 1250.43 | 965.29 | 2473.86 | 340.71 | 0.00 | 0.00 | 0.00 |
June | 2036.67 | 951.32 | 1085.34 | 2347.39 | 168.83 | 0.00 | 0.00 | 0.00 |
July | 1935.00 | 939.55 | 995.45 | 2285.11 | 193.93 | 0.00 | 0.00 | 0.00 |
August | 1532.21 | 746.91 | 785.31 | 1731.85 | 302.01 | 0.00 | 0.00 | 0.00 |
September | 947.02 | 415.27 | 531.75 | 901.35 | 556.25 | 0.00 | 0.00 | 0.00 |
October | 499.30 | 200.20 | 299.10 | 371.08 | 989.02 | 0.00 | 0.00 | 0.00 |
November | 105.42 | 36.29 | 69.13 | 8.93 | 1854.88 | 0.00 | 0.00 | 0.00 |
December | 14.99 | 3.44 | 11.55 | 0.00 | 2064.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1035.06 | 509.11 | 525.95 | 1067.76 | 977.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.99 | 3.44 | 11.55 | 0.00 | 168.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2215.71 | 1250.43 | 1085.34 | 2473.86 | 2064.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 482.83 | 319.27 | 163.57 | 291.56 | 2653.17 | 0.00 | 0.00 | 0.00 |
February | 1660.68 | 1158.50 | 502.19 | 1450.10 | 2124.59 | 0.00 | 0.00 | 0.00 |
March | 2844.95 | 1932.19 | 912.76 | 2859.96 | 1619.06 | 0.00 | 0.00 | 0.00 |
April | 3462.47 | 2156.39 | 1306.08 | 3869.80 | 1060.82 | 0.00 | 0.00 | 0.00 |
May | 2844.60 | 1471.39 | 1373.21 | 3260.27 | 591.07 | 0.00 | 0.00 | 0.00 |
June | 2594.00 | 1058.45 | 1535.55 | 3052.86 | 319.85 | 0.00 | 0.00 | 0.00 |
July | 2501.55 | 1086.34 | 1415.21 | 3015.42 | 341.14 | 0.00 | 0.00 | 0.00 |
August | 2598.35 | 1432.92 | 1165.43 | 3088.13 | 499.52 | 0.00 | 0.00 | 0.00 |
September | 2104.55 | 1269.97 | 834.58 | 2277.91 | 854.07 | 0.00 | 0.00 | 0.00 |
October | 1518.69 | 966.47 | 552.22 | 1428.98 | 1375.42 | 0.00 | 0.00 | 0.00 |
November | 815.96 | 571.54 | 244.41 | 558.86 | 2469.59 | 0.00 | 0.00 | 0.00 |
December | 144.90 | 102.47 | 42.44 | 26.47 | 2960.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1963.89 | 1125.40 | 838.49 | 2099.94 | 1402.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 144.90 | 102.47 | 42.44 | 26.47 | 319.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3462.47 | 2156.39 | 1535.55 | 3869.80 | 2960.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.63 | 6.30 | 30.33 | 0.00 | 1949.30 | 0.00 | 0.00 | 0.00 |
February | 216.80 | 74.65 | 142.16 | 46.30 | 1651.93 | 0.00 | 0.00 | 0.00 |
March | 653.44 | 280.50 | 372.94 | 387.92 | 1183.60 | 0.00 | 0.00 | 0.00 |
April | 1555.07 | 807.21 | 747.86 | 1529.12 | 680.04 | 0.00 | 0.00 | 0.00 |
May | 1512.25 | 690.28 | 821.96 | 1566.21 | 360.43 | 0.00 | 0.00 | 0.00 |
June | 1657.01 | 708.17 | 948.85 | 1862.97 | 197.02 | 0.00 | 0.00 | 0.00 |
July | 1385.83 | 525.34 | 860.48 | 1570.50 | 213.85 | 0.00 | 0.00 | 0.00 |
August | 1138.81 | 482.97 | 655.83 | 1225.46 | 317.29 | 0.00 | 0.00 | 0.00 |
September | 688.77 | 288.64 | 400.14 | 580.41 | 568.37 | 0.00 | 0.00 | 0.00 |
October | 268.77 | 80.21 | 188.55 | 107.03 | 1030.84 | 0.00 | 0.00 | 0.00 |
November | 107.07 | 38.39 | 68.68 | 12.12 | 1850.34 | 0.00 | 0.00 | 0.00 |
December | 9.62 | 0.95 | 8.67 | 0.00 | 2071.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 771.16 | 332.67 | 438.49 | 743.58 | 1002.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.62 | 0.95 | 8.67 | 0.00 | 197.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1657.01 | 807.21 | 948.85 | 1862.97 | 2071.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.32 | 0.00 | 13.32 | 0.00 | 989.26 | 0.00 | 0.00 | 0.00 |
February | 58.88 | 0.00 | 58.88 | 0.00 | 879.15 | 0.00 | 0.00 | 0.00 |
March | 157.49 | 0.00 | 157.49 | 15.56 | 646.01 | 0.00 | 0.00 | 0.00 |
April | 284.56 | 5.89 | 278.67 | 130.03 | 339.17 | 0.00 | 0.00 | 0.00 |
May | 435.34 | 68.05 | 367.28 | 357.59 | 151.71 | 0.00 | 0.00 | 0.00 |
June | 568.86 | 125.78 | 443.08 | 578.81 | 70.88 | 0.00 | 0.00 | 0.00 |
July | 477.28 | 76.79 | 400.49 | 493.37 | 88.64 | 0.00 | 0.00 | 0.00 |
August | 304.74 | 16.45 | 288.30 | 254.22 | 152.20 | 0.00 | 0.00 | 0.00 |
September | 170.34 | 0.15 | 170.19 | 63.83 | 313.56 | 0.00 | 0.00 | 0.00 |
October | 82.89 | 0.00 | 82.89 | 5.79 | 573.44 | 0.00 | 0.00 | 0.00 |
November | 25.73 | 0.00 | 25.73 | 0.00 | 984.75 | 0.00 | 0.00 | 0.00 |
December | 4.04 | 0.00 | 4.04 | 0.00 | 1050.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 216.06 | 24.53 | 191.52 | 159.18 | 518.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.04 | 0.00 | 4.04 | 0.00 | 70.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 568.86 | 125.78 | 443.08 | 578.81 | 1050.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.32 | 0.00 | 13.32 | 0.00 | 989.32 | 0.00 | 0.00 | 0.00 |
February | 58.89 | 0.00 | 58.89 | 0.00 | 879.21 | 0.00 | 0.00 | 0.00 |
March | 157.49 | 0.00 | 157.49 | 15.55 | 646.06 | 0.00 | 0.00 | 0.00 |
April | 284.57 | 5.89 | 278.68 | 130.03 | 339.19 | 0.00 | 0.00 | 0.00 |
May | 435.35 | 68.06 | 367.30 | 357.60 | 151.72 | 0.00 | 0.00 | 0.00 |
June | 568.88 | 125.78 | 443.09 | 578.82 | 70.88 | 0.00 | 0.00 | 0.00 |
July | 477.29 | 76.79 | 400.50 | 493.38 | 88.65 | 0.00 | 0.00 | 0.00 |
August | 304.76 | 16.45 | 288.31 | 254.23 | 152.21 | 0.00 | 0.00 | 0.00 |
September | 170.34 | 0.15 | 170.19 | 63.83 | 313.58 | 0.00 | 0.00 | 0.00 |
October | 82.90 | 0.00 | 82.90 | 5.79 | 573.48 | 0.00 | 0.00 | 0.00 |
November | 25.73 | 0.00 | 25.73 | 0.00 | 984.82 | 0.00 | 0.00 | 0.00 |
December | 4.04 | 0.00 | 4.04 | 0.00 | 1050.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 216.07 | 24.53 | 191.53 | 159.19 | 518.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.04 | 0.00 | 4.04 | 0.00 | 70.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 568.88 | 125.78 | 443.09 | 578.82 | 1050.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.32 | 0.00 | 13.32 | 0.00 | 989.32 | 0.00 | 0.00 | 0.00 |
February | 58.89 | 0.00 | 58.89 | 0.00 | 879.21 | 0.00 | 0.00 | 0.00 |
March | 157.49 | 0.00 | 157.49 | 15.55 | 646.06 | 0.00 | 0.00 | 0.00 |
April | 284.57 | 5.89 | 278.68 | 130.03 | 339.19 | 0.00 | 0.00 | 0.00 |
May | 435.35 | 68.06 | 367.30 | 357.60 | 151.72 | 0.00 | 0.00 | 0.00 |
June | 568.88 | 125.78 | 443.09 | 578.82 | 70.88 | 0.00 | 0.00 | 0.00 |
July | 477.29 | 76.79 | 400.50 | 493.38 | 88.65 | 0.00 | 0.00 | 0.00 |
August | 304.76 | 16.45 | 288.31 | 254.23 | 152.21 | 0.00 | 0.00 | 0.00 |
September | 170.34 | 0.15 | 170.19 | 63.83 | 313.58 | 0.00 | 0.00 | 0.00 |
October | 82.90 | 0.00 | 82.90 | 5.79 | 573.48 | 0.00 | 0.00 | 0.00 |
November | 25.73 | 0.00 | 25.73 | 0.00 | 984.82 | 0.00 | 0.00 | 0.00 |
December | 4.04 | 0.00 | 4.04 | 0.00 | 1050.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 216.07 | 24.53 | 191.53 | 159.19 | 518.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.04 | 0.00 | 4.04 | 0.00 | 70.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 568.88 | 125.78 | 443.09 | 578.82 | 1050.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.88 | 20.62 | 46.27 | 6.23 | 1849.47 | 0.00 | 0.00 | 0.00 |
February | 372.10 | 177.07 | 195.03 | 204.12 | 1534.15 | 0.00 | 0.00 | 0.00 |
March | 1065.35 | 540.18 | 525.17 | 933.17 | 1125.38 | 0.00 | 0.00 | 0.00 |
April | 1465.12 | 742.49 | 722.63 | 1400.55 | 624.43 | 0.00 | 0.00 | 0.00 |
May | 2131.40 | 1202.84 | 928.56 | 2392.81 | 334.97 | 0.00 | 0.00 | 0.00 |
June | 1959.17 | 915.12 | 1044.05 | 2272.93 | 163.33 | 0.00 | 0.00 | 0.00 |
July | 1861.37 | 903.79 | 957.57 | 2206.73 | 191.74 | 0.00 | 0.00 | 0.00 |
August | 1473.91 | 718.49 | 755.43 | 1667.03 | 305.83 | 0.00 | 0.00 | 0.00 |
September | 910.99 | 399.47 | 511.52 | 854.77 | 582.57 | 0.00 | 0.00 | 0.00 |
October | 480.30 | 192.58 | 287.72 | 348.80 | 1013.86 | 0.00 | 0.00 | 0.00 |
November | 101.41 | 34.91 | 66.50 | 8.34 | 1823.35 | 0.00 | 0.00 | 0.00 |
December | 14.42 | 3.31 | 11.11 | 0.00 | 2008.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 995.68 | 489.74 | 505.94 | 1030.17 | 960.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.42 | 3.31 | 11.11 | 0.00 | 163.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2131.40 | 1202.84 | 1044.05 | 2392.81 | 2008.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.64 | 0.82 | 1.83 | 0.25 | 73.13 | 0.00 | 0.00 | 0.00 |
February | 14.71 | 7.00 | 7.71 | 8.07 | 60.66 | 0.00 | 0.00 | 0.00 |
March | 42.12 | 21.36 | 20.76 | 36.90 | 44.50 | 0.00 | 0.00 | 0.00 |
April | 57.93 | 29.36 | 28.57 | 55.38 | 24.69 | 0.00 | 0.00 | 0.00 |
May | 84.27 | 47.56 | 36.71 | 94.61 | 13.24 | 0.00 | 0.00 | 0.00 |
June | 77.46 | 36.18 | 41.28 | 89.87 | 6.46 | 0.00 | 0.00 | 0.00 |
July | 73.60 | 35.74 | 37.86 | 87.25 | 7.58 | 0.00 | 0.00 | 0.00 |
August | 58.28 | 28.41 | 29.87 | 65.91 | 12.09 | 0.00 | 0.00 | 0.00 |
September | 36.02 | 15.79 | 20.22 | 33.80 | 23.03 | 0.00 | 0.00 | 0.00 |
October | 18.99 | 7.61 | 11.38 | 13.79 | 40.09 | 0.00 | 0.00 | 0.00 |
November | 4.01 | 1.38 | 2.63 | 0.33 | 72.09 | 0.00 | 0.00 | 0.00 |
December | 0.57 | 0.13 | 0.44 | 0.00 | 79.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.37 | 19.36 | 20.00 | 40.73 | 37.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.57 | 0.13 | 0.44 | 0.00 | 6.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.27 | 47.56 | 41.28 | 94.61 | 79.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.94 | 106.42 | 54.52 | 99.57 | 871.66 | 0.00 | 0.00 | 0.00 |
February | 553.55 | 386.16 | 167.39 | 489.96 | 703.49 | 0.00 | 0.00 | 0.00 |
March | 948.30 | 644.05 | 304.25 | 967.61 | 544.44 | 0.00 | 0.00 | 0.00 |
April | 1154.14 | 718.78 | 435.36 | 1300.52 | 369.17 | 0.00 | 0.00 | 0.00 |
May | 948.19 | 490.45 | 457.73 | 1098.20 | 201.29 | 0.00 | 0.00 | 0.00 |
June | 864.65 | 352.81 | 511.84 | 1028.27 | 107.46 | 0.00 | 0.00 | 0.00 |
July | 833.84 | 362.11 | 471.73 | 1012.31 | 117.08 | 0.00 | 0.00 | 0.00 |
August | 866.10 | 477.63 | 388.47 | 1033.61 | 176.87 | 0.00 | 0.00 | 0.00 |
September | 701.50 | 423.31 | 278.19 | 758.20 | 308.97 | 0.00 | 0.00 | 0.00 |
October | 506.22 | 322.15 | 184.07 | 473.87 | 486.74 | 0.00 | 0.00 | 0.00 |
November | 271.98 | 190.51 | 81.47 | 188.29 | 828.92 | 0.00 | 0.00 | 0.00 |
December | 48.30 | 34.16 | 14.15 | 9.98 | 976.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 654.62 | 375.13 | 279.49 | 705.55 | 473.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.30 | 34.16 | 14.15 | 9.98 | 107.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1154.14 | 718.78 | 511.84 | 1300.52 | 976.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.94 | 106.42 | 54.52 | 99.57 | 871.66 | 0.00 | 0.00 | 0.00 |
February | 553.55 | 386.16 | 167.39 | 489.96 | 703.49 | 0.00 | 0.00 | 0.00 |
March | 948.30 | 644.05 | 304.25 | 967.61 | 544.44 | 0.00 | 0.00 | 0.00 |
April | 1154.14 | 718.78 | 435.36 | 1300.52 | 369.17 | 0.00 | 0.00 | 0.00 |
May | 948.19 | 490.45 | 457.73 | 1098.20 | 201.29 | 0.00 | 0.00 | 0.00 |
June | 864.65 | 352.81 | 511.84 | 1028.27 | 107.46 | 0.00 | 0.00 | 0.00 |
July | 833.84 | 362.11 | 471.73 | 1012.31 | 117.08 | 0.00 | 0.00 | 0.00 |
August | 866.10 | 477.63 | 388.47 | 1033.61 | 176.87 | 0.00 | 0.00 | 0.00 |
September | 701.50 | 423.31 | 278.19 | 758.20 | 308.97 | 0.00 | 0.00 | 0.00 |
October | 506.22 | 322.15 | 184.07 | 473.87 | 486.74 | 0.00 | 0.00 | 0.00 |
November | 271.98 | 190.51 | 81.47 | 188.29 | 828.92 | 0.00 | 0.00 | 0.00 |
December | 48.30 | 34.16 | 14.15 | 9.98 | 976.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 654.62 | 375.13 | 279.49 | 705.55 | 473.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.30 | 34.16 | 14.15 | 9.98 | 107.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1154.14 | 718.78 | 511.84 | 1300.52 | 976.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.93 | 106.41 | 54.52 | 99.56 | 871.61 | 0.00 | 0.00 | 0.00 |
February | 553.52 | 386.13 | 167.38 | 489.93 | 703.45 | 0.00 | 0.00 | 0.00 |
March | 948.24 | 644.01 | 304.23 | 967.55 | 544.41 | 0.00 | 0.00 | 0.00 |
April | 1154.06 | 718.74 | 435.33 | 1300.44 | 369.15 | 0.00 | 0.00 | 0.00 |
May | 948.13 | 490.42 | 457.70 | 1098.13 | 201.27 | 0.00 | 0.00 | 0.00 |
June | 864.60 | 352.79 | 511.81 | 1028.21 | 107.45 | 0.00 | 0.00 | 0.00 |
July | 833.78 | 362.08 | 471.70 | 1012.24 | 117.07 | 0.00 | 0.00 | 0.00 |
August | 866.05 | 477.60 | 388.45 | 1033.54 | 176.86 | 0.00 | 0.00 | 0.00 |
September | 701.46 | 423.29 | 278.17 | 758.15 | 308.95 | 0.00 | 0.00 | 0.00 |
October | 506.19 | 322.13 | 184.06 | 473.84 | 486.71 | 0.00 | 0.00 | 0.00 |
November | 271.96 | 190.50 | 81.46 | 188.28 | 828.87 | 0.00 | 0.00 | 0.00 |
December | 48.30 | 34.15 | 14.14 | 9.98 | 976.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 654.58 | 375.10 | 279.48 | 705.51 | 473.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.30 | 34.15 | 14.14 | 9.98 | 107.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1154.06 | 718.74 | 511.81 | 1300.44 | 976.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.24 | 6.06 | 29.18 | 0.00 | 1886.20 | 0.00 | 0.00 | 0.00 |
February | 208.55 | 71.81 | 136.75 | 45.42 | 1594.15 | 0.00 | 0.00 | 0.00 |
March | 628.57 | 269.82 | 358.75 | 380.89 | 1146.59 | 0.00 | 0.00 | 0.00 |
April | 1495.90 | 776.49 | 719.41 | 1485.89 | 673.90 | 0.00 | 0.00 | 0.00 |
May | 1454.71 | 664.02 | 790.69 | 1525.07 | 350.86 | 0.00 | 0.00 | 0.00 |
June | 1593.97 | 681.22 | 912.75 | 1808.69 | 190.21 | 0.00 | 0.00 | 0.00 |
July | 1333.10 | 505.35 | 827.74 | 1522.17 | 209.21 | 0.00 | 0.00 | 0.00 |
August | 1095.48 | 464.60 | 630.88 | 1180.91 | 321.48 | 0.00 | 0.00 | 0.00 |
September | 662.57 | 277.65 | 384.91 | 548.49 | 593.69 | 0.00 | 0.00 | 0.00 |
October | 258.54 | 77.16 | 181.38 | 98.04 | 1050.13 | 0.00 | 0.00 | 0.00 |
November | 103.00 | 36.93 | 66.06 | 11.26 | 1819.80 | 0.00 | 0.00 | 0.00 |
December | 9.25 | 0.91 | 8.34 | 0.00 | 2014.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 741.82 | 320.01 | 421.80 | 720.06 | 984.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.25 | 0.91 | 8.34 | 0.00 | 190.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1593.97 | 776.49 | 912.75 | 1808.69 | 2014.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.39 | 0.24 | 1.15 | 0.00 | 74.58 | 0.00 | 0.00 | 0.00 |
February | 8.25 | 2.84 | 5.41 | 1.80 | 63.03 | 0.00 | 0.00 | 0.00 |
March | 24.85 | 10.67 | 14.18 | 15.06 | 45.34 | 0.00 | 0.00 | 0.00 |
April | 59.15 | 30.70 | 28.44 | 58.75 | 26.65 | 0.00 | 0.00 | 0.00 |
May | 57.52 | 26.25 | 31.26 | 60.30 | 13.87 | 0.00 | 0.00 | 0.00 |
June | 63.02 | 26.93 | 36.09 | 71.51 | 7.52 | 0.00 | 0.00 | 0.00 |
July | 52.71 | 19.98 | 32.73 | 60.18 | 8.27 | 0.00 | 0.00 | 0.00 |
August | 43.31 | 18.37 | 24.94 | 46.69 | 12.71 | 0.00 | 0.00 | 0.00 |
September | 26.20 | 10.98 | 15.22 | 21.69 | 23.47 | 0.00 | 0.00 | 0.00 |
October | 10.22 | 3.05 | 7.17 | 3.88 | 41.52 | 0.00 | 0.00 | 0.00 |
November | 4.07 | 1.46 | 2.61 | 0.45 | 71.95 | 0.00 | 0.00 | 0.00 |
December | 0.37 | 0.04 | 0.33 | 0.00 | 79.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.33 | 12.65 | 16.68 | 28.47 | 38.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.37 | 0.04 | 0.33 | 0.00 | 7.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.02 | 30.70 | 36.09 | 71.51 | 79.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 39.96 | 0.00 | 39.96 | 0.00 | 3006.65 | 0.00 | 0.00 | 0.00 |
February | 176.66 | 0.00 | 176.66 | 0.00 | 2694.18 | 0.00 | 0.00 | 0.00 |
March | 472.48 | 0.00 | 472.48 | 40.77 | 1997.66 | 0.00 | 0.00 | 0.00 |
April | 853.72 | 17.68 | 836.04 | 345.87 | 1079.25 | 0.00 | 0.00 | 0.00 |
May | 1306.08 | 204.17 | 1101.90 | 1011.48 | 488.22 | 0.00 | 0.00 | 0.00 |
June | 1706.65 | 377.36 | 1329.29 | 1696.95 | 226.29 | 0.00 | 0.00 | 0.00 |
July | 1431.90 | 230.38 | 1201.52 | 1454.06 | 276.92 | 0.00 | 0.00 | 0.00 |
August | 914.28 | 49.35 | 864.93 | 749.20 | 465.17 | 0.00 | 0.00 | 0.00 |
September | 511.03 | 0.45 | 510.58 | 185.39 | 944.86 | 0.00 | 0.00 | 0.00 |
October | 248.69 | 0.00 | 248.69 | 16.84 | 1709.94 | 0.00 | 0.00 | 0.00 |
November | 77.18 | 0.00 | 77.18 | 0.00 | 2953.28 | 0.00 | 0.00 | 0.00 |
December | 12.12 | 0.00 | 12.12 | 0.00 | 3170.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 648.20 | 73.60 | 574.60 | 461.07 | 1578.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.12 | 0.00 | 12.12 | 0.00 | 226.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1706.65 | 377.36 | 1329.29 | 1696.95 | 3170.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.53 | 21.43 | 48.10 | 6.23 | 1941.88 | 0.00 | 0.00 | 0.00 |
February | 386.82 | 184.08 | 202.74 | 207.94 | 1622.86 | 0.00 | 0.00 | 0.00 |
March | 1107.49 | 561.55 | 545.95 | 950.92 | 1197.40 | 0.00 | 0.00 | 0.00 |
April | 1523.07 | 771.86 | 751.22 | 1426.81 | 667.01 | 0.00 | 0.00 | 0.00 |
May | 2215.71 | 1250.43 | 965.29 | 2462.45 | 354.10 | 0.00 | 0.00 | 0.00 |
June | 2036.67 | 951.32 | 1085.34 | 2341.67 | 174.12 | 0.00 | 0.00 | 0.00 |
July | 1935.00 | 939.55 | 995.45 | 2279.92 | 200.04 | 0.00 | 0.00 | 0.00 |
August | 1532.21 | 746.91 | 785.31 | 1723.95 | 314.45 | 0.00 | 0.00 | 0.00 |
September | 947.02 | 415.27 | 531.75 | 884.35 | 594.37 | 0.00 | 0.00 | 0.00 |
October | 499.30 | 200.20 | 299.10 | 360.88 | 1038.88 | 0.00 | 0.00 | 0.00 |
November | 105.42 | 36.29 | 69.13 | 8.62 | 1892.33 | 0.00 | 0.00 | 0.00 |
December | 14.99 | 3.44 | 11.55 | 0.00 | 2096.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1035.06 | 509.11 | 525.95 | 1060.22 | 1004.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.99 | 3.44 | 11.55 | 0.00 | 174.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2215.71 | 1250.43 | 1085.34 | 2462.45 | 2096.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 482.83 | 319.27 | 163.57 | 287.96 | 2702.17 | 0.00 | 0.00 | 0.00 |
February | 1660.68 | 1158.50 | 502.19 | 1436.92 | 2179.79 | 0.00 | 0.00 | 0.00 |
March | 2844.95 | 1932.19 | 912.76 | 2842.73 | 1679.57 | 0.00 | 0.00 | 0.00 |
April | 3462.47 | 2156.39 | 1306.08 | 3853.22 | 1114.99 | 0.00 | 0.00 | 0.00 |
May | 2844.60 | 1471.39 | 1373.21 | 3252.31 | 620.08 | 0.00 | 0.00 | 0.00 |
June | 2594.00 | 1058.45 | 1535.55 | 3051.28 | 332.15 | 0.00 | 0.00 | 0.00 |
July | 2501.55 | 1086.34 | 1415.21 | 3013.74 | 353.95 | 0.00 | 0.00 | 0.00 |
August | 2598.35 | 1432.92 | 1165.43 | 3083.16 | 522.05 | 0.00 | 0.00 | 0.00 |
September | 2104.55 | 1269.97 | 834.58 | 2258.31 | 909.84 | 0.00 | 0.00 | 0.00 |
October | 1518.69 | 966.47 | 552.22 | 1408.43 | 1447.11 | 0.00 | 0.00 | 0.00 |
November | 815.96 | 571.54 | 244.41 | 551.15 | 2529.59 | 0.00 | 0.00 | 0.00 |
December | 144.90 | 102.47 | 42.44 | 26.00 | 3014.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1963.89 | 1125.40 | 838.49 | 2090.40 | 1446.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 144.90 | 102.47 | 42.44 | 26.00 | 332.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3462.47 | 2156.39 | 1535.55 | 3853.22 | 3014.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.63 | 6.30 | 30.33 | 0.00 | 1982.21 | 0.00 | 0.00 | 0.00 |
February | 216.80 | 74.65 | 142.16 | 45.22 | 1688.56 | 0.00 | 0.00 | 0.00 |
March | 653.44 | 280.50 | 372.94 | 382.67 | 1224.20 | 0.00 | 0.00 | 0.00 |
April | 1555.07 | 807.21 | 747.86 | 1516.89 | 717.29 | 0.00 | 0.00 | 0.00 |
May | 1512.25 | 690.28 | 821.96 | 1558.45 | 379.26 | 0.00 | 0.00 | 0.00 |
June | 1657.01 | 708.17 | 948.85 | 1861.23 | 204.91 | 0.00 | 0.00 | 0.00 |
July | 1385.83 | 525.34 | 860.48 | 1568.67 | 222.22 | 0.00 | 0.00 | 0.00 |
August | 1138.81 | 482.97 | 655.83 | 1220.50 | 332.67 | 0.00 | 0.00 | 0.00 |
September | 688.77 | 288.64 | 400.14 | 567.44 | 609.49 | 0.00 | 0.00 | 0.00 |
October | 268.77 | 80.21 | 188.55 | 101.12 | 1081.97 | 0.00 | 0.00 | 0.00 |
November | 107.07 | 38.39 | 68.68 | 11.61 | 1890.09 | 0.00 | 0.00 | 0.00 |
December | 9.62 | 0.95 | 8.67 | 0.00 | 2105.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 771.16 | 332.67 | 438.49 | 739.06 | 1033.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.62 | 0.95 | 8.67 | 0.00 | 204.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1657.01 | 807.21 | 948.85 | 1861.23 | 2105.72 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107039E+09 | 0.00 | 0.107039E+09 | 0.00 | 0.791148E+10 |
February | 0.427372E+09 | 0.00 | 0.427372E+09 | 0.00 | 0.637568E+10 |
March | 0.126550E+10 | 0.00 | 0.126550E+10 | 0.119449E+09 | 0.517836E+10 |
April | 0.221284E+10 | 45829192.81 | 0.216701E+10 | 0.947512E+09 | 0.264352E+10 |
May | 0.349819E+10 | 0.546861E+09 | 0.295133E+10 | 0.276956E+10 | 0.125063E+10 |
June | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.441754E+10 | 0.566793E+09 |
July | 0.383519E+10 | 0.617040E+09 | 0.321815E+10 | 0.391352E+10 | 0.717023E+09 |
August | 0.244879E+10 | 0.132169E+09 | 0.231663E+10 | 0.204129E+10 | 0.118842E+10 |
September | 0.132460E+10 | 1167627.48 | 0.132343E+10 | 0.529945E+09 | 0.227308E+10 |
October | 0.666103E+09 | 0.00 | 0.666103E+09 | 59625417.17 | 0.436506E+10 |
November | 0.200047E+09 | 0.00 | 0.200047E+09 | 0.00 | 0.749023E+10 |
December | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.834161E+10 |
Annual Sum or Average | 0.204418E+11 | 0.232118E+10 | 0.181206E+11 | 0.147984E+11 | 0.483019E+11 |
Minimum of Months | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.566793E+09 |
Maximum of Months | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.441754E+10 | 0.834161E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186224E+09 | 57402514.18 | 0.128821E+09 | 16850329.82 | 0.511952E+10 |
February | 0.935792E+09 | 0.445324E+09 | 0.490467E+09 | 0.511095E+09 | 0.384402E+10 |
March | 0.296630E+10 | 0.150404E+10 | 0.146226E+10 | 0.257799E+10 | 0.309976E+10 |
April | 0.394781E+10 | 0.200066E+10 | 0.194715E+10 | 0.374431E+10 | 0.164241E+10 |
May | 0.593457E+10 | 0.334914E+10 | 0.258543E+10 | 0.662598E+10 | 0.912571E+09 |
June | 0.527904E+10 | 0.246583E+10 | 0.281321E+10 | 0.608444E+10 | 0.437597E+09 |
July | 0.518269E+10 | 0.251648E+10 | 0.266621E+10 | 0.612045E+10 | 0.519419E+09 |
August | 0.410388E+10 | 0.200052E+10 | 0.210336E+10 | 0.463858E+10 | 0.808900E+09 |
September | 0.245468E+10 | 0.107638E+10 | 0.137830E+10 | 0.233630E+10 | 0.144181E+10 |
October | 0.133733E+10 | 0.536219E+09 | 0.801112E+09 | 0.993894E+09 | 0.264899E+10 |
November | 0.273252E+09 | 94067965.17 | 0.179184E+09 | 23146076.92 | 0.480784E+10 |
December | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.553074E+10 |
Annual Sum or Average | 0.326417E+11 | 0.160553E+11 | 0.165864E+11 | 0.336730E+11 | 0.308136E+11 |
Minimum of Months | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.437597E+09 |
Maximum of Months | 0.593457E+10 | 0.334914E+10 | 0.281321E+10 | 0.662598E+10 | 0.553074E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129323E+10 | 0.855128E+09 | 0.438097E+09 | 0.780904E+09 | 0.710625E+10 |
February | 0.401753E+10 | 0.280264E+10 | 0.121489E+10 | 0.350808E+10 | 0.513980E+10 |
March | 0.761990E+10 | 0.517517E+10 | 0.244474E+10 | 0.766011E+10 | 0.433650E+10 |
April | 0.897472E+10 | 0.558935E+10 | 0.338536E+10 | 0.100305E+11 | 0.274965E+10 |
May | 0.761899E+10 | 0.394098E+10 | 0.367801E+10 | 0.873231E+10 | 0.158312E+10 |
June | 0.672366E+10 | 0.274351E+10 | 0.398014E+10 | 0.791302E+10 | 0.829040E+09 |
July | 0.670015E+10 | 0.290965E+10 | 0.379050E+10 | 0.807649E+10 | 0.913713E+09 |
August | 0.695943E+10 | 0.383795E+10 | 0.312148E+10 | 0.827124E+10 | 0.133790E+10 |
September | 0.545499E+10 | 0.329176E+10 | 0.216323E+10 | 0.590433E+10 | 0.221374E+10 |
October | 0.406766E+10 | 0.258859E+10 | 0.147907E+10 | 0.382739E+10 | 0.368391E+10 |
November | 0.211496E+10 | 0.148144E+10 | 0.633523E+09 | 0.144857E+10 | 0.640118E+10 |
December | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 70906288.93 | 0.793008E+10 |
Annual Sum or Average | 0.619333E+11 | 0.354906E+11 | 0.264427E+11 | 0.662239E+11 | 0.442249E+11 |
Minimum of Months | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 70906288.93 | 0.829040E+09 |
Maximum of Months | 0.897472E+10 | 0.558935E+10 | 0.398014E+10 | 0.100305E+11 | 0.793008E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98112947.39 | 16875249.29 | 81237698.10 | 0.00 | 0.522100E+10 |
February | 0.524491E+09 | 0.180586E+09 | 0.343905E+09 | 0.111999E+09 | 0.399635E+10 |
March | 0.175016E+10 | 0.751280E+09 | 0.998882E+09 | 0.103900E+10 | 0.317015E+10 |
April | 0.403074E+10 | 0.209229E+10 | 0.193845E+10 | 0.396347E+10 | 0.176266E+10 |
May | 0.405040E+10 | 0.184886E+10 | 0.220155E+10 | 0.419494E+10 | 0.965387E+09 |
June | 0.429498E+10 | 0.183556E+10 | 0.245941E+10 | 0.482882E+10 | 0.510675E+09 |
July | 0.371179E+10 | 0.140708E+10 | 0.230472E+10 | 0.420643E+10 | 0.572784E+09 |
August | 0.305018E+10 | 0.129360E+10 | 0.175658E+10 | 0.328227E+10 | 0.849830E+09 |
September | 0.178530E+10 | 0.748147E+09 | 0.103716E+10 | 0.150442E+10 | 0.147322E+10 |
October | 0.719868E+09 | 0.214845E+09 | 0.505023E+09 | 0.286669E+09 | 0.276101E+10 |
November | 0.277525E+09 | 99513390.80 | 0.178012E+09 | 31413976.66 | 0.479607E+10 |
December | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.554869E+10 |
Annual Sum or Average | 0.243193E+11 | 0.104912E+11 | 0.138281E+11 | 0.234494E+11 | 0.316278E+11 |
Minimum of Months | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.510675E+09 |
Maximum of Months | 0.429498E+10 | 0.209229E+10 | 0.245941E+10 | 0.482882E+10 | 0.554869E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 35677821.11 | 0.00 | 35677821.11 | 0.00 | 0.264963E+10 |
February | 0.142450E+09 | 0.00 | 0.142450E+09 | 0.00 | 0.212684E+10 |
March | 0.421814E+09 | 0.00 | 0.421814E+09 | 41664080.26 | 0.173028E+10 |
April | 0.737577E+09 | 15275674.84 | 0.722302E+09 | 0.337028E+09 | 0.879124E+09 |
May | 0.116601E+10 | 0.182278E+09 | 0.983730E+09 | 0.957777E+09 | 0.406341E+09 |
June | 0.147447E+10 | 0.326021E+09 | 0.114845E+10 | 0.150027E+10 | 0.183709E+09 |
July | 0.127834E+10 | 0.205670E+09 | 0.107267E+10 | 0.132144E+10 | 0.237415E+09 |
August | 0.816226E+09 | 44054132.18 | 0.772172E+09 | 0.680909E+09 | 0.407659E+09 |
September | 0.441512E+09 | 389190.75 | 0.441123E+09 | 0.165445E+09 | 0.812744E+09 |
October | 0.222024E+09 | 0.00 | 0.222024E+09 | 15498387.63 | 0.153590E+10 |
November | 66679304.90 | 0.00 | 66679304.90 | 0.00 | 0.255248E+10 |
December | 10822788.22 | 0.00 | 10822788.22 | 0.00 | 0.281394E+10 |
Annual Sum or Average | 0.681360E+10 | 0.773689E+09 | 0.603991E+10 | 0.502003E+10 | 0.163361E+11 |
Minimum of Months | 10822788.22 | 0.00 | 10822788.22 | 0.00 | 0.183709E+09 |
Maximum of Months | 0.147447E+10 | 0.326021E+09 | 0.114845E+10 | 0.150027E+10 | 0.281394E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 35679076.65 | 0.00 | 35679076.65 | 0.00 | 0.264980E+10 |
February | 0.142456E+09 | 0.00 | 0.142456E+09 | 0.00 | 0.212697E+10 |
March | 0.421831E+09 | 0.00 | 0.421831E+09 | 41662352.64 | 0.173040E+10 |
April | 0.737606E+09 | 15276085.46 | 0.722330E+09 | 0.337033E+09 | 0.879183E+09 |
May | 0.116605E+10 | 0.182283E+09 | 0.983768E+09 | 0.957800E+09 | 0.406366E+09 |
June | 0.147453E+10 | 0.326030E+09 | 0.114850E+10 | 0.150031E+10 | 0.183721E+09 |
July | 0.127838E+10 | 0.205676E+09 | 0.107271E+10 | 0.132147E+10 | 0.237430E+09 |
August | 0.816257E+09 | 44055316.37 | 0.772202E+09 | 0.680927E+09 | 0.407684E+09 |
September | 0.441529E+09 | 389201.21 | 0.441139E+09 | 0.165446E+09 | 0.812796E+09 |
October | 0.222032E+09 | 0.00 | 0.222032E+09 | 15497747.49 | 0.153600E+10 |
November | 66681651.46 | 0.00 | 66681651.46 | 0.00 | 0.255264E+10 |
December | 10823155.80 | 0.00 | 10823155.80 | 0.00 | 0.281412E+10 |
Annual Sum or Average | 0.681385E+10 | 0.773710E+09 | 0.604014E+10 | 0.502015E+10 | 0.163371E+11 |
Minimum of Months | 10823155.80 | 0.00 | 10823155.80 | 0.00 | 0.183721E+09 |
Maximum of Months | 0.147453E+10 | 0.326030E+09 | 0.114850E+10 | 0.150031E+10 | 0.281412E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 35679076.65 | 0.00 | 35679076.65 | 0.00 | 0.264980E+10 |
February | 0.142456E+09 | 0.00 | 0.142456E+09 | 0.00 | 0.212697E+10 |
March | 0.421831E+09 | 0.00 | 0.421831E+09 | 41662352.64 | 0.173040E+10 |
April | 0.737606E+09 | 15276085.46 | 0.722330E+09 | 0.337033E+09 | 0.879183E+09 |
May | 0.116605E+10 | 0.182283E+09 | 0.983768E+09 | 0.957800E+09 | 0.406366E+09 |
June | 0.147453E+10 | 0.326030E+09 | 0.114850E+10 | 0.150031E+10 | 0.183721E+09 |
July | 0.127838E+10 | 0.205676E+09 | 0.107271E+10 | 0.132147E+10 | 0.237430E+09 |
August | 0.816257E+09 | 44055316.37 | 0.772202E+09 | 0.680927E+09 | 0.407684E+09 |
September | 0.441529E+09 | 389201.21 | 0.441139E+09 | 0.165446E+09 | 0.812796E+09 |
October | 0.222032E+09 | 0.00 | 0.222032E+09 | 15497747.49 | 0.153600E+10 |
November | 66681651.46 | 0.00 | 66681651.46 | 0.00 | 0.255264E+10 |
December | 10823155.80 | 0.00 | 10823155.80 | 0.00 | 0.281412E+10 |
Annual Sum or Average | 0.681385E+10 | 0.773710E+09 | 0.604014E+10 | 0.502015E+10 | 0.163371E+11 |
Minimum of Months | 10823155.80 | 0.00 | 10823155.80 | 0.00 | 0.183721E+09 |
Maximum of Months | 0.147453E+10 | 0.326030E+09 | 0.114850E+10 | 0.150031E+10 | 0.281412E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179138E+09 | 55218116.69 | 0.123919E+09 | 16676040.98 | 0.495361E+10 |
February | 0.900183E+09 | 0.428378E+09 | 0.471805E+09 | 0.493804E+09 | 0.371142E+10 |
March | 0.285343E+10 | 0.144681E+10 | 0.140662E+10 | 0.249940E+10 | 0.301421E+10 |
April | 0.379759E+10 | 0.192452E+10 | 0.187306E+10 | 0.363022E+10 | 0.161853E+10 |
May | 0.570875E+10 | 0.322170E+10 | 0.248705E+10 | 0.640890E+10 | 0.897170E+09 |
June | 0.507816E+10 | 0.237199E+10 | 0.270617E+10 | 0.589144E+10 | 0.423343E+09 |
July | 0.498549E+10 | 0.242072E+10 | 0.256477E+10 | 0.591052E+10 | 0.513547E+09 |
August | 0.394773E+10 | 0.192439E+10 | 0.202333E+10 | 0.446496E+10 | 0.819139E+09 |
September | 0.236128E+10 | 0.103542E+10 | 0.132586E+10 | 0.221557E+10 | 0.151001E+10 |
October | 0.128644E+10 | 0.515813E+09 | 0.770629E+09 | 0.934236E+09 | 0.271553E+10 |
November | 0.262854E+09 | 90488299.20 | 0.172366E+09 | 21617964.22 | 0.472611E+10 |
December | 38623368.56 | 8872006.07 | 29751362.49 | 0.00 | 0.537860E+10 |
Annual Sum or Average | 0.313997E+11 | 0.154443E+11 | 0.159553E+11 | 0.324873E+11 | 0.302812E+11 |
Minimum of Months | 38623368.56 | 8872006.07 | 29751362.49 | 0.00 | 0.423343E+09 |
Maximum of Months | 0.570875E+10 | 0.322170E+10 | 0.270617E+10 | 0.640890E+10 | 0.537860E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7082936.28 | 2183274.62 | 4899661.66 | 659355.65 | 0.195861E+09 |
February | 35592418.46 | 16937678.99 | 18654739.47 | 19524566.63 | 0.146746E+09 |
March | 0.112822E+09 | 57205554.86 | 55616515.73 | 98824005.44 | 0.119179E+09 |
April | 0.150153E+09 | 76093951.76 | 74059270.83 | 0.143536E+09 | 63995147.58 |
May | 0.225719E+09 | 0.127383E+09 | 98335906.32 | 0.253402E+09 | 35473304.49 |
June | 0.200786E+09 | 93786470.86 | 0.107000E+09 | 0.232942E+09 | 16738613.51 |
July | 0.197122E+09 | 95713028.32 | 0.101409E+09 | 0.233697E+09 | 20305200.83 |
August | 0.156090E+09 | 76088825.43 | 80000707.63 | 0.176541E+09 | 32388024.86 |
September | 93362824.18 | 40939699.31 | 52423124.87 | 87601551.31 | 59704484.83 |
October | 50864781.68 | 20394799.44 | 30469982.24 | 36938835.19 | 0.107370E+09 |
November | 10393016.29 | 3577825.88 | 6815190.41 | 854754.84 | 0.186866E+09 |
December | 1527133.22 | 350791.13 | 1176342.09 | 0.00 | 0.212665E+09 |
Annual Sum or Average | 0.124151E+10 | 0.610655E+09 | 0.630860E+09 | 0.128452E+10 | 0.119729E+10 |
Minimum of Months | 1527133.22 | 350791.13 | 1176342.09 | 0.00 | 16738613.51 |
Maximum of Months | 0.225719E+09 | 0.127383E+09 | 0.107000E+09 | 0.253402E+09 | 0.212665E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.431067E+09 | 0.285037E+09 | 0.146030E+09 | 0.266690E+09 | 0.233466E+10 |
February | 0.133915E+10 | 0.934194E+09 | 0.404956E+09 | 0.118531E+10 | 0.170189E+10 |
March | 0.253992E+10 | 0.172502E+10 | 0.814901E+09 | 0.259165E+10 | 0.145823E+10 |
April | 0.299152E+10 | 0.186308E+10 | 0.112844E+10 | 0.337095E+10 | 0.956897E+09 |
May | 0.253962E+10 | 0.131363E+10 | 0.122599E+10 | 0.294143E+10 | 0.539126E+09 |
June | 0.224119E+10 | 0.914485E+09 | 0.132670E+10 | 0.266528E+10 | 0.278530E+09 |
July | 0.223335E+10 | 0.969863E+09 | 0.126349E+10 | 0.271136E+10 | 0.313592E+09 |
August | 0.231977E+10 | 0.127929E+10 | 0.104048E+10 | 0.276841E+10 | 0.473736E+09 |
September | 0.181830E+10 | 0.109723E+10 | 0.721067E+09 | 0.196525E+10 | 0.800844E+09 |
October | 0.135586E+10 | 0.862846E+09 | 0.493016E+09 | 0.126920E+10 | 0.130368E+10 |
November | 0.704973E+09 | 0.493802E+09 | 0.211171E+09 | 0.488041E+09 | 0.214856E+10 |
December | 0.129368E+09 | 91482228.09 | 37886262.73 | 26724163.86 | 0.261463E+10 |
Annual Sum or Average | 0.206441E+11 | 0.118300E+11 | 0.881412E+10 | 0.222503E+11 | 0.149244E+11 |
Minimum of Months | 0.129368E+09 | 91482228.09 | 37886262.73 | 26724163.86 | 0.278530E+09 |
Maximum of Months | 0.299152E+10 | 0.186308E+10 | 0.132670E+10 | 0.337095E+10 | 0.261463E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.431067E+09 | 0.285037E+09 | 0.146030E+09 | 0.266690E+09 | 0.233466E+10 |
February | 0.133915E+10 | 0.934194E+09 | 0.404956E+09 | 0.118531E+10 | 0.170189E+10 |
March | 0.253992E+10 | 0.172502E+10 | 0.814901E+09 | 0.259165E+10 | 0.145823E+10 |
April | 0.299152E+10 | 0.186308E+10 | 0.112844E+10 | 0.337095E+10 | 0.956897E+09 |
May | 0.253962E+10 | 0.131363E+10 | 0.122599E+10 | 0.294143E+10 | 0.539126E+09 |
June | 0.224119E+10 | 0.914485E+09 | 0.132670E+10 | 0.266528E+10 | 0.278530E+09 |
July | 0.223335E+10 | 0.969863E+09 | 0.126349E+10 | 0.271136E+10 | 0.313592E+09 |
August | 0.231977E+10 | 0.127929E+10 | 0.104048E+10 | 0.276841E+10 | 0.473736E+09 |
September | 0.181830E+10 | 0.109723E+10 | 0.721067E+09 | 0.196525E+10 | 0.800844E+09 |
October | 0.135586E+10 | 0.862846E+09 | 0.493016E+09 | 0.126920E+10 | 0.130368E+10 |
November | 0.704973E+09 | 0.493802E+09 | 0.211171E+09 | 0.488041E+09 | 0.214856E+10 |
December | 0.129368E+09 | 91482228.09 | 37886262.73 | 26724163.86 | 0.261463E+10 |
Annual Sum or Average | 0.206441E+11 | 0.118300E+11 | 0.881412E+10 | 0.222503E+11 | 0.149244E+11 |
Minimum of Months | 0.129368E+09 | 91482228.09 | 37886262.73 | 26724163.86 | 0.278530E+09 |
Maximum of Months | 0.299152E+10 | 0.186308E+10 | 0.132670E+10 | 0.337095E+10 | 0.261463E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.431039E+09 | 0.285019E+09 | 0.146020E+09 | 0.266673E+09 | 0.233451E+10 |
February | 0.133907E+10 | 0.934135E+09 | 0.404930E+09 | 0.118523E+10 | 0.170179E+10 |
March | 0.253976E+10 | 0.172491E+10 | 0.814849E+09 | 0.259148E+10 | 0.145814E+10 |
April | 0.299133E+10 | 0.186296E+10 | 0.112837E+10 | 0.337074E+10 | 0.956837E+09 |
May | 0.253946E+10 | 0.131355E+10 | 0.122591E+10 | 0.294124E+10 | 0.539092E+09 |
June | 0.224104E+10 | 0.914427E+09 | 0.132662E+10 | 0.266511E+10 | 0.278513E+09 |
July | 0.223321E+10 | 0.969802E+09 | 0.126341E+10 | 0.271119E+10 | 0.313572E+09 |
August | 0.231962E+10 | 0.127921E+10 | 0.104042E+10 | 0.276824E+10 | 0.473706E+09 |
September | 0.181818E+10 | 0.109716E+10 | 0.721022E+09 | 0.196512E+10 | 0.800793E+09 |
October | 0.135578E+10 | 0.862792E+09 | 0.492985E+09 | 0.126912E+10 | 0.130360E+10 |
November | 0.704928E+09 | 0.493771E+09 | 0.211157E+09 | 0.488010E+09 | 0.214843E+10 |
December | 0.129360E+09 | 91476446.93 | 37883868.53 | 26722475.04 | 0.261446E+10 |
Annual Sum or Average | 0.206428E+11 | 0.118292E+11 | 0.881357E+10 | 0.222489E+11 | 0.149234E+11 |
Minimum of Months | 0.129360E+09 | 91476446.93 | 37883868.53 | 26722475.04 | 0.278513E+09 |
Maximum of Months | 0.299133E+10 | 0.186296E+10 | 0.132662E+10 | 0.337074E+10 | 0.261446E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94379988.23 | 16233130.55 | 78146857.69 | 0.00 | 0.505199E+10 |
February | 0.504535E+09 | 0.173715E+09 | 0.330821E+09 | 0.109881E+09 | 0.385658E+10 |
March | 0.168357E+10 | 0.722693E+09 | 0.960879E+09 | 0.102017E+10 | 0.307102E+10 |
April | 0.387737E+10 | 0.201267E+10 | 0.186470E+10 | 0.385144E+10 | 0.174674E+10 |
May | 0.389630E+10 | 0.177851E+10 | 0.211779E+10 | 0.408474E+10 | 0.939751E+09 |
June | 0.413156E+10 | 0.176572E+10 | 0.236584E+10 | 0.468812E+10 | 0.493020E+09 |
July | 0.357057E+10 | 0.135354E+10 | 0.221703E+10 | 0.407697E+10 | 0.560354E+09 |
August | 0.293413E+10 | 0.124438E+10 | 0.168975E+10 | 0.316294E+10 | 0.861040E+09 |
September | 0.171738E+10 | 0.719680E+09 | 0.997697E+09 | 0.142168E+10 | 0.153885E+10 |
October | 0.692479E+09 | 0.206670E+09 | 0.485809E+09 | 0.262596E+09 | 0.281267E+10 |
November | 0.266966E+09 | 95726814.84 | 0.171239E+09 | 29188849.37 | 0.471692E+10 |
December | 24777092.81 | 2448507.06 | 22328585.75 | 0.00 | 0.539669E+10 |
Annual Sum or Average | 0.233940E+11 | 0.100920E+11 | 0.133020E+11 | 0.227077E+11 | 0.310456E+11 |
Minimum of Months | 24777092.81 | 2448507.06 | 22328585.75 | 0.00 | 0.493020E+09 |
Maximum of Months | 0.413156E+10 | 0.201267E+10 | 0.236584E+10 | 0.468812E+10 | 0.539669E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 3731689.67 | 641841.29 | 3089848.39 | 0.00 | 0.199751E+09 |
February | 19948822.89 | 6868508.39 | 13080314.50 | 4344559.08 | 0.152486E+09 |
March | 66566767.86 | 28574556.87 | 37992210.99 | 40336316.42 | 0.121425E+09 |
April | 0.153307E+09 | 79579087.00 | 73728338.57 | 0.152282E+09 | 69064487.47 |
May | 0.154056E+09 | 70320337.58 | 83735270.13 | 0.161506E+09 | 37156928.95 |
June | 0.163358E+09 | 69814733.93 | 93543143.14 | 0.185363E+09 | 19493564.26 |
July | 0.141177E+09 | 53517485.69 | 87659226.27 | 0.161199E+09 | 22155889.46 |
August | 0.116012E+09 | 49201345.84 | 66811020.47 | 0.125059E+09 | 34044730.83 |
September | 67903320.69 | 28455387.71 | 39447932.98 | 56211528.81 | 60844549.03 |
October | 27379904.01 | 8171502.04 | 19208401.96 | 10382732.91 | 0.111210E+09 |
November | 10555562.71 | 3784939.80 | 6770622.91 | 1154087.58 | 0.186503E+09 |
December | 979661.29 | 96811.45 | 882849.84 | 0.00 | 0.213380E+09 |
Annual Sum or Average | 0.924976E+09 | 0.399027E+09 | 0.525949E+09 | 0.897839E+09 | 0.122752E+10 |
Minimum of Months | 979661.29 | 96811.45 | 882849.84 | 0.00 | 19493564.26 |
Maximum of Months | 0.163358E+09 | 79579087.00 | 93543143.14 | 0.185363E+09 | 0.213380E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107039E+09 | 0.00 | 0.107039E+09 | 0.00 | 0.805301E+10 |
February | 0.427372E+09 | 0.00 | 0.427372E+09 | 0.00 | 0.651776E+10 |
March | 0.126550E+10 | 0.00 | 0.126550E+10 | 0.109193E+09 | 0.535053E+10 |
April | 0.221284E+10 | 45829192.81 | 0.216701E+10 | 0.896489E+09 | 0.279741E+10 |
May | 0.349819E+10 | 0.546861E+09 | 0.295133E+10 | 0.270915E+10 | 0.130765E+10 |
June | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.439850E+10 | 0.586551E+09 |
July | 0.383519E+10 | 0.617040E+09 | 0.321815E+10 | 0.389454E+10 | 0.741698E+09 |
August | 0.244879E+10 | 0.132169E+09 | 0.231663E+10 | 0.200666E+10 | 0.124590E+10 |
September | 0.132460E+10 | 1167627.48 | 0.132343E+10 | 0.480532E+09 | 0.244908E+10 |
October | 0.666103E+09 | 0.00 | 0.666103E+09 | 45111922.90 | 0.457991E+10 |
November | 0.200047E+09 | 0.00 | 0.200047E+09 | 0.00 | 0.765491E+10 |
December | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.849109E+10 |
Annual Sum or Average | 0.204418E+11 | 0.232118E+10 | 0.181206E+11 | 0.145402E+11 | 0.497755E+11 |
Minimum of Months | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.586551E+09 |
Maximum of Months | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.439850E+10 | 0.849109E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186224E+09 | 57402514.18 | 0.128821E+09 | 16675809.78 | 0.520112E+10 |
February | 0.935792E+09 | 0.445324E+09 | 0.490467E+09 | 0.503048E+09 | 0.392602E+10 |
March | 0.296630E+10 | 0.150404E+10 | 0.146226E+10 | 0.254695E+10 | 0.320712E+10 |
April | 0.394781E+10 | 0.200066E+10 | 0.194715E+10 | 0.369830E+10 | 0.172890E+10 |
May | 0.593457E+10 | 0.334914E+10 | 0.258543E+10 | 0.659543E+10 | 0.948434E+09 |
June | 0.527904E+10 | 0.246583E+10 | 0.281321E+10 | 0.606962E+10 | 0.451332E+09 |
July | 0.518269E+10 | 0.251648E+10 | 0.266621E+10 | 0.610655E+10 | 0.535776E+09 |
August | 0.410388E+10 | 0.200052E+10 | 0.210336E+10 | 0.461743E+10 | 0.842225E+09 |
September | 0.245468E+10 | 0.107638E+10 | 0.137830E+10 | 0.229225E+10 | 0.154060E+10 |
October | 0.133733E+10 | 0.536219E+09 | 0.801112E+09 | 0.966587E+09 | 0.278255E+10 |
November | 0.273252E+09 | 94067965.17 | 0.179184E+09 | 22351764.10 | 0.490492E+10 |
December | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.561516E+10 |
Annual Sum or Average | 0.326417E+11 | 0.160553E+11 | 0.165864E+11 | 0.334352E+11 | 0.316842E+11 |
Minimum of Months | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.451332E+09 |
Maximum of Months | 0.593457E+10 | 0.334914E+10 | 0.281321E+10 | 0.659543E+10 | 0.561516E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129323E+10 | 0.855128E+09 | 0.438097E+09 | 0.771277E+09 | 0.723748E+10 |
February | 0.401753E+10 | 0.280264E+10 | 0.121489E+10 | 0.347619E+10 | 0.527335E+10 |
March | 0.761990E+10 | 0.517517E+10 | 0.244474E+10 | 0.761398E+10 | 0.449856E+10 |
April | 0.897472E+10 | 0.558935E+10 | 0.338536E+10 | 0.998755E+10 | 0.289004E+10 |
May | 0.761899E+10 | 0.394098E+10 | 0.367801E+10 | 0.871097E+10 | 0.166081E+10 |
June | 0.672366E+10 | 0.274351E+10 | 0.398014E+10 | 0.790891E+10 | 0.860932E+09 |
July | 0.670015E+10 | 0.290965E+10 | 0.379050E+10 | 0.807199E+10 | 0.948012E+09 |
August | 0.695943E+10 | 0.383795E+10 | 0.312148E+10 | 0.825792E+10 | 0.139826E+10 |
September | 0.545499E+10 | 0.329176E+10 | 0.216323E+10 | 0.585354E+10 | 0.235831E+10 |
October | 0.406766E+10 | 0.258859E+10 | 0.147907E+10 | 0.377235E+10 | 0.387594E+10 |
November | 0.211496E+10 | 0.148144E+10 | 0.633523E+09 | 0.142859E+10 | 0.655669E+10 |
December | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 69651517.72 | 0.807276E+10 |
Annual Sum or Average | 0.619333E+11 | 0.354906E+11 | 0.264427E+11 | 0.659229E+11 | 0.456312E+11 |
Minimum of Months | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 69651517.72 | 0.860932E+09 |
Maximum of Months | 0.897472E+10 | 0.558935E+10 | 0.398014E+10 | 0.998755E+10 | 0.807276E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98112947.39 | 16875249.29 | 81237698.10 | 0.00 | 0.530916E+10 |
February | 0.524491E+09 | 0.180586E+09 | 0.343905E+09 | 0.109400E+09 | 0.408496E+10 |
March | 0.175016E+10 | 0.751280E+09 | 0.998882E+09 | 0.102494E+10 | 0.327890E+10 |
April | 0.403074E+10 | 0.209229E+10 | 0.193845E+10 | 0.393178E+10 | 0.185921E+10 |
May | 0.405040E+10 | 0.184886E+10 | 0.220155E+10 | 0.417416E+10 | 0.101580E+10 |
June | 0.429498E+10 | 0.183556E+10 | 0.245941E+10 | 0.482431E+10 | 0.531122E+09 |
July | 0.371179E+10 | 0.140708E+10 | 0.230472E+10 | 0.420152E+10 | 0.595182E+09 |
August | 0.305018E+10 | 0.129360E+10 | 0.175658E+10 | 0.326898E+10 | 0.891016E+09 |
September | 0.178530E+10 | 0.748147E+09 | 0.103716E+10 | 0.147081E+10 | 0.157979E+10 |
October | 0.719868E+09 | 0.214845E+09 | 0.505023E+09 | 0.270844E+09 | 0.289795E+10 |
November | 0.277525E+09 | 99513390.80 | 0.178012E+09 | 30093714.62 | 0.489911E+10 |
December | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.563997E+10 |
Annual Sum or Average | 0.243193E+11 | 0.104912E+11 | 0.138281E+11 | 0.233068E+11 | 0.325822E+11 |
Minimum of Months | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.531122E+09 |
Maximum of Months | 0.429498E+10 | 0.209229E+10 | 0.245941E+10 | 0.482431E+10 | 0.563997E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2953.81 | 39.96 | 0.00 | 39.96 | 0.00 | 0.00 |
February | 0.00 | 2635.45 | 176.66 | 0.00 | 176.66 | 0.00 | 0.00 |
March | 44.60 | 1933.38 | 472.48 | 0.00 | 472.48 | 0.00 | 0.00 |
April | 365.55 | 1019.88 | 853.72 | 17.68 | 836.04 | 0.00 | 0.00 |
May | 1034.04 | 466.93 | 1306.08 | 204.17 | 1101.90 | 0.00 | 0.00 |
June | 1704.30 | 218.67 | 1706.65 | 377.36 | 1329.29 | 0.00 | 0.00 |
July | 1461.14 | 267.71 | 1431.90 | 230.38 | 1201.52 | 0.00 | 0.00 |
August | 762.13 | 443.70 | 914.28 | 49.35 | 864.93 | 0.00 | 0.00 |
September | 204.45 | 876.96 | 511.03 | 0.45 | 510.58 | 0.00 | 0.00 |
October | 22.26 | 1629.73 | 248.69 | 0.00 | 248.69 | 0.00 | 0.00 |
November | 0.00 | 2889.75 | 77.18 | 0.00 | 77.18 | 0.00 | 0.00 |
December | 0.00 | 3114.40 | 12.12 | 0.00 | 12.12 | 0.00 | 0.00 |
Annual Sum or Average | 469.26 | 1531.64 | 648.20 | 73.60 | 574.60 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 218.67 | 12.12 | 0.00 | 12.12 | 0.00 | 0.00 |
Maximum of Months | 1704.30 | 3114.40 | 1706.65 | 377.36 | 1329.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.29 | 1911.41 | 69.53 | 21.43 | 48.10 | 0.00 | 0.00 |
February | 211.27 | 1588.97 | 386.82 | 184.08 | 202.74 | 0.00 | 0.00 |
March | 962.51 | 1157.32 | 1107.49 | 561.55 | 545.95 | 0.00 | 0.00 |
April | 1444.56 | 633.65 | 1523.07 | 771.86 | 751.22 | 0.00 | 0.00 |
May | 2473.86 | 340.71 | 2215.71 | 1250.43 | 965.29 | 0.00 | 0.00 |
June | 2347.39 | 168.83 | 2036.67 | 951.32 | 1085.34 | 0.00 | 0.00 |
July | 2285.11 | 193.93 | 1935.00 | 939.55 | 995.45 | 0.00 | 0.00 |
August | 1731.85 | 302.01 | 1532.21 | 746.91 | 785.31 | 0.00 | 0.00 |
September | 901.35 | 556.25 | 947.02 | 415.27 | 531.75 | 0.00 | 0.00 |
October | 371.08 | 989.02 | 499.30 | 200.20 | 299.10 | 0.00 | 0.00 |
November | 8.93 | 1854.88 | 105.42 | 36.29 | 69.13 | 0.00 | 0.00 |
December | 0.00 | 2064.94 | 14.99 | 3.44 | 11.55 | 0.00 | 0.00 |
Annual Sum or Average | 1067.76 | 977.09 | 1035.06 | 509.11 | 525.95 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 168.83 | 14.99 | 3.44 | 11.55 | 0.00 | 0.00 |
Maximum of Months | 2473.86 | 2064.94 | 2215.71 | 1250.43 | 1085.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 291.56 | 2653.17 | 482.83 | 319.27 | 163.57 | 0.00 | 0.00 |
February | 1450.10 | 2124.59 | 1660.68 | 1158.50 | 502.19 | 0.00 | 0.00 |
March | 2859.96 | 1619.06 | 2844.95 | 1932.19 | 912.76 | 0.00 | 0.00 |
April | 3869.80 | 1060.82 | 3462.47 | 2156.39 | 1306.08 | 0.00 | 0.00 |
May | 3260.27 | 591.07 | 2844.60 | 1471.39 | 1373.21 | 0.00 | 0.00 |
June | 3052.86 | 319.85 | 2594.00 | 1058.45 | 1535.55 | 0.00 | 0.00 |
July | 3015.42 | 341.14 | 2501.55 | 1086.34 | 1415.21 | 0.00 | 0.00 |
August | 3088.13 | 499.52 | 2598.35 | 1432.92 | 1165.43 | 0.00 | 0.00 |
September | 2277.91 | 854.07 | 2104.55 | 1269.97 | 834.58 | 0.00 | 0.00 |
October | 1428.98 | 1375.42 | 1518.69 | 966.47 | 552.22 | 0.00 | 0.00 |
November | 558.86 | 2469.59 | 815.96 | 571.54 | 244.41 | 0.00 | 0.00 |
December | 26.47 | 2960.75 | 144.90 | 102.47 | 42.44 | 0.00 | 0.00 |
Annual Sum or Average | 2099.94 | 1402.36 | 1963.89 | 1125.40 | 838.49 | 0.00 | 0.00 |
Minimum of Months | 26.47 | 319.85 | 144.90 | 102.47 | 42.44 | 0.00 | 0.00 |
Maximum of Months | 3869.80 | 2960.75 | 3462.47 | 2156.39 | 1535.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1949.30 | 36.63 | 6.30 | 30.33 | 0.00 | 0.00 |
February | 46.30 | 1651.93 | 216.80 | 74.65 | 142.16 | 0.00 | 0.00 |
March | 387.92 | 1183.60 | 653.44 | 280.50 | 372.94 | 0.00 | 0.00 |
April | 1529.12 | 680.04 | 1555.07 | 807.21 | 747.86 | 0.00 | 0.00 |
May | 1566.21 | 360.43 | 1512.25 | 690.28 | 821.96 | 0.00 | 0.00 |
June | 1862.97 | 197.02 | 1657.01 | 708.17 | 948.85 | 0.00 | 0.00 |
July | 1570.50 | 213.85 | 1385.83 | 525.34 | 860.48 | 0.00 | 0.00 |
August | 1225.46 | 317.29 | 1138.81 | 482.97 | 655.83 | 0.00 | 0.00 |
September | 580.41 | 568.37 | 688.77 | 288.64 | 400.14 | 0.00 | 0.00 |
October | 107.03 | 1030.84 | 268.77 | 80.21 | 188.55 | 0.00 | 0.00 |
November | 12.12 | 1850.34 | 107.07 | 38.39 | 68.68 | 0.00 | 0.00 |
December | 0.00 | 2071.64 | 9.62 | 0.95 | 8.67 | 0.00 | 0.00 |
Annual Sum or Average | 743.58 | 1002.91 | 771.16 | 332.67 | 438.49 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 197.02 | 9.62 | 0.95 | 8.67 | 0.00 | 0.00 |
Maximum of Months | 1862.97 | 2071.64 | 1657.01 | 807.21 | 948.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2967.90 | 39.96 | 0.00 | 39.96 | 0.00 | 0.00 |
February | 0.00 | 2637.56 | 176.65 | 0.00 | 176.65 | 0.00 | 0.00 |
March | 46.67 | 1938.13 | 472.47 | 0.00 | 472.47 | 0.00 | 0.00 |
April | 390.08 | 1017.55 | 853.70 | 17.68 | 836.02 | 0.00 | 0.00 |
May | 1072.80 | 455.15 | 1306.05 | 204.17 | 1101.88 | 0.00 | 0.00 |
June | 1736.46 | 212.64 | 1706.61 | 377.35 | 1329.26 | 0.00 | 0.00 |
July | 1480.13 | 265.93 | 1431.86 | 230.37 | 1201.49 | 0.00 | 0.00 |
August | 762.68 | 456.63 | 914.25 | 49.34 | 864.91 | 0.00 | 0.00 |
September | 191.49 | 940.72 | 511.02 | 0.45 | 510.57 | 0.00 | 0.00 |
October | 17.36 | 1720.39 | 248.69 | 0.00 | 248.69 | 0.00 | 0.00 |
November | 0.00 | 2954.38 | 77.18 | 0.00 | 77.18 | 0.00 | 0.00 |
December | 0.00 | 3151.95 | 12.12 | 0.00 | 12.12 | 0.00 | 0.00 |
Annual Sum or Average | 477.56 | 1554.11 | 648.19 | 73.60 | 574.59 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 212.64 | 12.12 | 0.00 | 12.12 | 0.00 | 0.00 |
Maximum of Months | 1736.46 | 3151.95 | 1706.61 | 377.35 | 1329.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.47 | 1922.59 | 69.53 | 21.43 | 48.10 | 0.00 | 0.00 |
February | 212.19 | 1594.81 | 386.81 | 184.08 | 202.74 | 0.00 | 0.00 |
March | 970.07 | 1169.88 | 1107.47 | 561.53 | 545.94 | 0.00 | 0.00 |
April | 1455.93 | 649.12 | 1523.05 | 771.84 | 751.21 | 0.00 | 0.00 |
May | 2487.42 | 348.21 | 2215.68 | 1250.40 | 965.27 | 0.00 | 0.00 |
June | 2362.80 | 169.78 | 2036.63 | 951.30 | 1085.33 | 0.00 | 0.00 |
July | 2293.99 | 199.32 | 1934.96 | 939.53 | 995.44 | 0.00 | 0.00 |
August | 1732.94 | 317.92 | 1532.19 | 746.89 | 785.29 | 0.00 | 0.00 |
September | 888.57 | 605.60 | 947.01 | 415.26 | 531.74 | 0.00 | 0.00 |
October | 362.60 | 1053.95 | 499.29 | 200.20 | 299.10 | 0.00 | 0.00 |
November | 8.67 | 1895.44 | 105.42 | 36.29 | 69.13 | 0.00 | 0.00 |
December | 0.00 | 2087.54 | 14.99 | 3.44 | 11.55 | 0.00 | 0.00 |
Annual Sum or Average | 1070.90 | 998.18 | 1035.05 | 509.10 | 525.94 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 169.78 | 14.99 | 3.44 | 11.55 | 0.00 | 0.00 |
Maximum of Months | 2487.42 | 2087.54 | 2215.68 | 1250.40 | 1085.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 298.71 | 2614.93 | 482.82 | 319.25 | 163.56 | 0.00 | 0.00 |
February | 1469.84 | 2110.44 | 1660.62 | 1158.45 | 502.17 | 0.00 | 0.00 |
March | 2902.77 | 1633.29 | 2844.83 | 1932.11 | 912.73 | 0.00 | 0.00 |
April | 3901.48 | 1107.50 | 3462.34 | 2156.30 | 1306.04 | 0.00 | 0.00 |
May | 3294.54 | 603.85 | 2844.50 | 1471.33 | 1373.17 | 0.00 | 0.00 |
June | 3084.75 | 322.37 | 2593.91 | 1058.41 | 1535.50 | 0.00 | 0.00 |
July | 3036.86 | 351.24 | 2501.46 | 1086.29 | 1415.16 | 0.00 | 0.00 |
August | 3100.75 | 530.61 | 2598.26 | 1432.87 | 1165.39 | 0.00 | 0.00 |
September | 2274.55 | 926.88 | 2104.47 | 1269.92 | 834.55 | 0.00 | 0.00 |
October | 1421.57 | 1460.18 | 1518.63 | 966.43 | 552.20 | 0.00 | 0.00 |
November | 564.85 | 2486.71 | 815.92 | 571.52 | 244.41 | 0.00 | 0.00 |
December | 29.93 | 2928.51 | 144.90 | 102.46 | 42.43 | 0.00 | 0.00 |
Annual Sum or Average | 2116.61 | 1419.72 | 1963.82 | 1125.35 | 838.46 | 0.00 | 0.00 |
Minimum of Months | 29.93 | 322.37 | 144.90 | 102.46 | 42.43 | 0.00 | 0.00 |
Maximum of Months | 3901.48 | 2928.51 | 3462.34 | 2156.30 | 1535.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1960.77 | 36.63 | 6.30 | 30.33 | 0.00 | 0.00 |
February | 47.22 | 1657.19 | 216.80 | 74.65 | 142.15 | 0.00 | 0.00 |
March | 395.95 | 1191.92 | 653.43 | 280.49 | 372.94 | 0.00 | 0.00 |
April | 1544.65 | 700.54 | 1555.05 | 807.20 | 747.85 | 0.00 | 0.00 |
May | 1585.37 | 364.74 | 1512.23 | 690.27 | 821.95 | 0.00 | 0.00 |
June | 1880.20 | 197.73 | 1656.99 | 708.15 | 948.84 | 0.00 | 0.00 |
July | 1582.35 | 217.48 | 1385.81 | 525.33 | 860.47 | 0.00 | 0.00 |
August | 1227.60 | 334.19 | 1138.79 | 482.97 | 655.82 | 0.00 | 0.00 |
September | 570.17 | 617.16 | 688.77 | 288.63 | 400.13 | 0.00 | 0.00 |
October | 101.92 | 1091.65 | 268.76 | 80.21 | 188.55 | 0.00 | 0.00 |
November | 11.71 | 1891.75 | 107.07 | 38.39 | 68.68 | 0.00 | 0.00 |
December | 0.00 | 2094.56 | 9.62 | 0.95 | 8.67 | 0.00 | 0.00 |
Annual Sum or Average | 748.53 | 1023.37 | 771.15 | 332.67 | 438.48 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 197.73 | 9.62 | 0.95 | 8.67 | 0.00 | 0.00 |
Maximum of Months | 1880.20 | 2094.56 | 1656.99 | 807.20 | 948.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 3006.65 | 39.96 | 0.00 | 39.96 | 0.00 | 0.00 |
February | 0.00 | 2694.18 | 176.66 | 0.00 | 176.66 | 0.00 | 0.00 |
March | 40.77 | 1997.66 | 472.48 | 0.00 | 472.48 | 0.00 | 0.00 |
April | 345.87 | 1079.25 | 853.72 | 17.68 | 836.04 | 0.00 | 0.00 |
May | 1011.48 | 488.22 | 1306.08 | 204.17 | 1101.90 | 0.00 | 0.00 |
June | 1696.95 | 226.29 | 1706.65 | 377.36 | 1329.29 | 0.00 | 0.00 |
July | 1454.06 | 276.92 | 1431.90 | 230.38 | 1201.52 | 0.00 | 0.00 |
August | 749.20 | 465.17 | 914.28 | 49.35 | 864.93 | 0.00 | 0.00 |
September | 185.39 | 944.86 | 511.03 | 0.45 | 510.58 | 0.00 | 0.00 |
October | 16.84 | 1709.94 | 248.69 | 0.00 | 248.69 | 0.00 | 0.00 |
November | 0.00 | 2953.28 | 77.18 | 0.00 | 77.18 | 0.00 | 0.00 |
December | 0.00 | 3170.21 | 12.12 | 0.00 | 12.12 | 0.00 | 0.00 |
Annual Sum or Average | 461.07 | 1578.37 | 648.20 | 73.60 | 574.60 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 226.29 | 12.12 | 0.00 | 12.12 | 0.00 | 0.00 |
Maximum of Months | 1696.95 | 3170.21 | 1706.65 | 377.36 | 1329.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.23 | 1941.88 | 69.53 | 21.43 | 48.10 | 0.00 | 0.00 |
February | 207.94 | 1622.86 | 386.82 | 184.08 | 202.74 | 0.00 | 0.00 |
March | 950.92 | 1197.40 | 1107.49 | 561.55 | 545.95 | 0.00 | 0.00 |
April | 1426.81 | 667.01 | 1523.07 | 771.86 | 751.22 | 0.00 | 0.00 |
May | 2462.45 | 354.10 | 2215.71 | 1250.43 | 965.29 | 0.00 | 0.00 |
June | 2341.67 | 174.12 | 2036.67 | 951.32 | 1085.34 | 0.00 | 0.00 |
July | 2279.92 | 200.04 | 1935.00 | 939.55 | 995.45 | 0.00 | 0.00 |
August | 1723.95 | 314.45 | 1532.21 | 746.91 | 785.31 | 0.00 | 0.00 |
September | 884.35 | 594.37 | 947.02 | 415.27 | 531.75 | 0.00 | 0.00 |
October | 360.88 | 1038.88 | 499.30 | 200.20 | 299.10 | 0.00 | 0.00 |
November | 8.62 | 1892.33 | 105.42 | 36.29 | 69.13 | 0.00 | 0.00 |
December | 0.00 | 2096.46 | 14.99 | 3.44 | 11.55 | 0.00 | 0.00 |
Annual Sum or Average | 1060.22 | 1004.70 | 1035.06 | 509.11 | 525.95 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 174.12 | 14.99 | 3.44 | 11.55 | 0.00 | 0.00 |
Maximum of Months | 2462.45 | 2096.46 | 2215.71 | 1250.43 | 1085.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 287.96 | 2702.17 | 482.83 | 319.27 | 163.57 | 0.00 | 0.00 |
February | 1436.92 | 2179.79 | 1660.68 | 1158.50 | 502.19 | 0.00 | 0.00 |
March | 2842.73 | 1679.57 | 2844.95 | 1932.19 | 912.76 | 0.00 | 0.00 |
April | 3853.22 | 1114.99 | 3462.47 | 2156.39 | 1306.08 | 0.00 | 0.00 |
May | 3252.31 | 620.08 | 2844.60 | 1471.39 | 1373.21 | 0.00 | 0.00 |
June | 3051.28 | 332.15 | 2594.00 | 1058.45 | 1535.55 | 0.00 | 0.00 |
July | 3013.74 | 353.95 | 2501.55 | 1086.34 | 1415.21 | 0.00 | 0.00 |
August | 3083.16 | 522.05 | 2598.35 | 1432.92 | 1165.43 | 0.00 | 0.00 |
September | 2258.31 | 909.84 | 2104.55 | 1269.97 | 834.58 | 0.00 | 0.00 |
October | 1408.43 | 1447.11 | 1518.69 | 966.47 | 552.22 | 0.00 | 0.00 |
November | 551.15 | 2529.59 | 815.96 | 571.54 | 244.41 | 0.00 | 0.00 |
December | 26.00 | 3014.02 | 144.90 | 102.47 | 42.44 | 0.00 | 0.00 |
Annual Sum or Average | 2090.40 | 1446.95 | 1963.89 | 1125.40 | 838.49 | 0.00 | 0.00 |
Minimum of Months | 26.00 | 332.15 | 144.90 | 102.47 | 42.44 | 0.00 | 0.00 |
Maximum of Months | 3853.22 | 3014.02 | 3462.47 | 2156.39 | 1535.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1982.21 | 36.63 | 6.30 | 30.33 | 0.00 | 0.00 |
February | 45.22 | 1688.56 | 216.80 | 74.65 | 142.16 | 0.00 | 0.00 |
March | 382.67 | 1224.20 | 653.44 | 280.50 | 372.94 | 0.00 | 0.00 |
April | 1516.89 | 717.29 | 1555.07 | 807.21 | 747.86 | 0.00 | 0.00 |
May | 1558.45 | 379.26 | 1512.25 | 690.28 | 821.96 | 0.00 | 0.00 |
June | 1861.23 | 204.91 | 1657.01 | 708.17 | 948.85 | 0.00 | 0.00 |
July | 1568.67 | 222.22 | 1385.83 | 525.34 | 860.48 | 0.00 | 0.00 |
August | 1220.50 | 332.67 | 1138.81 | 482.97 | 655.83 | 0.00 | 0.00 |
September | 567.44 | 609.49 | 688.77 | 288.64 | 400.14 | 0.00 | 0.00 |
October | 101.12 | 1081.97 | 268.77 | 80.21 | 188.55 | 0.00 | 0.00 |
November | 11.61 | 1890.09 | 107.07 | 38.39 | 68.68 | 0.00 | 0.00 |
December | 0.00 | 2105.72 | 9.62 | 0.95 | 8.67 | 0.00 | 0.00 |
Annual Sum or Average | 739.06 | 1033.17 | 771.16 | 332.67 | 438.49 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 204.91 | 9.62 | 0.95 | 8.67 | 0.00 | 0.00 |
Maximum of Months | 1861.23 | 2105.72 | 1657.01 | 807.21 | 948.85 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.791148E+10 | 0.107039E+09 | 0.00 | 0.107039E+09 | 0.00 | 0.00 |
February | 0.00 | 0.637568E+10 | 0.427372E+09 | 0.00 | 0.427372E+09 | 0.00 | 0.00 |
March | 0.119449E+09 | 0.517836E+10 | 0.126550E+10 | 0.00 | 0.126550E+10 | 0.00 | 0.00 |
April | 0.947512E+09 | 0.264352E+10 | 0.221284E+10 | 45829192.81 | 0.216701E+10 | 0.00 | 0.00 |
May | 0.276956E+10 | 0.125063E+10 | 0.349819E+10 | 0.546861E+09 | 0.295133E+10 | 0.00 | 0.00 |
June | 0.441754E+10 | 0.566793E+09 | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.00 | 0.00 |
July | 0.391352E+10 | 0.717023E+09 | 0.383519E+10 | 0.617040E+09 | 0.321815E+10 | 0.00 | 0.00 |
August | 0.204129E+10 | 0.118842E+10 | 0.244879E+10 | 0.132169E+09 | 0.231663E+10 | 0.00 | 0.00 |
September | 0.529945E+09 | 0.227308E+10 | 0.132460E+10 | 1167627.48 | 0.132343E+10 | 0.00 | 0.00 |
October | 59625417.17 | 0.436506E+10 | 0.666103E+09 | 0.00 | 0.666103E+09 | 0.00 | 0.00 |
November | 0.00 | 0.749023E+10 | 0.200047E+09 | 0.00 | 0.200047E+09 | 0.00 | 0.00 |
December | 0.00 | 0.834161E+10 | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.00 |
Annual Sum or Average | 0.147984E+11 | 0.483019E+11 | 0.204418E+11 | 0.232118E+10 | 0.181206E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.566793E+09 | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.00 |
Maximum of Months | 0.441754E+10 | 0.834161E+10 | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 16850329.82 | 0.511952E+10 | 0.186224E+09 | 57402514.18 | 0.128821E+09 | 0.00 | 0.00 |
February | 0.511095E+09 | 0.384402E+10 | 0.935792E+09 | 0.445324E+09 | 0.490467E+09 | 0.00 | 0.00 |
March | 0.257799E+10 | 0.309976E+10 | 0.296630E+10 | 0.150404E+10 | 0.146226E+10 | 0.00 | 0.00 |
April | 0.374431E+10 | 0.164241E+10 | 0.394781E+10 | 0.200066E+10 | 0.194715E+10 | 0.00 | 0.00 |
May | 0.662598E+10 | 0.912571E+09 | 0.593457E+10 | 0.334914E+10 | 0.258543E+10 | 0.00 | 0.00 |
June | 0.608444E+10 | 0.437597E+09 | 0.527904E+10 | 0.246583E+10 | 0.281321E+10 | 0.00 | 0.00 |
July | 0.612045E+10 | 0.519419E+09 | 0.518269E+10 | 0.251648E+10 | 0.266621E+10 | 0.00 | 0.00 |
August | 0.463858E+10 | 0.808900E+09 | 0.410388E+10 | 0.200052E+10 | 0.210336E+10 | 0.00 | 0.00 |
September | 0.233630E+10 | 0.144181E+10 | 0.245468E+10 | 0.107638E+10 | 0.137830E+10 | 0.00 | 0.00 |
October | 0.993894E+09 | 0.264899E+10 | 0.133733E+10 | 0.536219E+09 | 0.801112E+09 | 0.00 | 0.00 |
November | 23146076.92 | 0.480784E+10 | 0.273252E+09 | 94067965.17 | 0.179184E+09 | 0.00 | 0.00 |
December | 0.00 | 0.553074E+10 | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.00 |
Annual Sum or Average | 0.336730E+11 | 0.308136E+11 | 0.326417E+11 | 0.160553E+11 | 0.165864E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.437597E+09 | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.00 |
Maximum of Months | 0.662598E+10 | 0.553074E+10 | 0.593457E+10 | 0.334914E+10 | 0.281321E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.780904E+09 | 0.710625E+10 | 0.129323E+10 | 0.855128E+09 | 0.438097E+09 | 0.00 | 0.00 |
February | 0.350808E+10 | 0.513980E+10 | 0.401753E+10 | 0.280264E+10 | 0.121489E+10 | 0.00 | 0.00 |
March | 0.766011E+10 | 0.433650E+10 | 0.761990E+10 | 0.517517E+10 | 0.244474E+10 | 0.00 | 0.00 |
April | 0.100305E+11 | 0.274965E+10 | 0.897472E+10 | 0.558935E+10 | 0.338536E+10 | 0.00 | 0.00 |
May | 0.873231E+10 | 0.158312E+10 | 0.761899E+10 | 0.394098E+10 | 0.367801E+10 | 0.00 | 0.00 |
June | 0.791302E+10 | 0.829040E+09 | 0.672366E+10 | 0.274351E+10 | 0.398014E+10 | 0.00 | 0.00 |
July | 0.807649E+10 | 0.913713E+09 | 0.670015E+10 | 0.290965E+10 | 0.379050E+10 | 0.00 | 0.00 |
August | 0.827124E+10 | 0.133790E+10 | 0.695943E+10 | 0.383795E+10 | 0.312148E+10 | 0.00 | 0.00 |
September | 0.590433E+10 | 0.221374E+10 | 0.545499E+10 | 0.329176E+10 | 0.216323E+10 | 0.00 | 0.00 |
October | 0.382739E+10 | 0.368391E+10 | 0.406766E+10 | 0.258859E+10 | 0.147907E+10 | 0.00 | 0.00 |
November | 0.144857E+10 | 0.640118E+10 | 0.211496E+10 | 0.148144E+10 | 0.633523E+09 | 0.00 | 0.00 |
December | 70906288.93 | 0.793008E+10 | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.662239E+11 | 0.442249E+11 | 0.619333E+11 | 0.354906E+11 | 0.264427E+11 | 0.00 | 0.00 |
Minimum of Months | 70906288.93 | 0.829040E+09 | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 0.00 | 0.00 |
Maximum of Months | 0.100305E+11 | 0.793008E+10 | 0.897472E+10 | 0.558935E+10 | 0.398014E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.522100E+10 | 98112947.39 | 16875249.29 | 81237698.10 | 0.00 | 0.00 |
February | 0.111999E+09 | 0.399635E+10 | 0.524491E+09 | 0.180586E+09 | 0.343905E+09 | 0.00 | 0.00 |
March | 0.103900E+10 | 0.317015E+10 | 0.175016E+10 | 0.751280E+09 | 0.998882E+09 | 0.00 | 0.00 |
April | 0.396347E+10 | 0.176266E+10 | 0.403074E+10 | 0.209229E+10 | 0.193845E+10 | 0.00 | 0.00 |
May | 0.419494E+10 | 0.965387E+09 | 0.405040E+10 | 0.184886E+10 | 0.220155E+10 | 0.00 | 0.00 |
June | 0.482882E+10 | 0.510675E+09 | 0.429498E+10 | 0.183556E+10 | 0.245941E+10 | 0.00 | 0.00 |
July | 0.420643E+10 | 0.572784E+09 | 0.371179E+10 | 0.140708E+10 | 0.230472E+10 | 0.00 | 0.00 |
August | 0.328227E+10 | 0.849830E+09 | 0.305018E+10 | 0.129360E+10 | 0.175658E+10 | 0.00 | 0.00 |
September | 0.150442E+10 | 0.147322E+10 | 0.178530E+10 | 0.748147E+09 | 0.103716E+10 | 0.00 | 0.00 |
October | 0.286669E+09 | 0.276101E+10 | 0.719868E+09 | 0.214845E+09 | 0.505023E+09 | 0.00 | 0.00 |
November | 31413976.66 | 0.479607E+10 | 0.277525E+09 | 99513390.80 | 0.178012E+09 | 0.00 | 0.00 |
December | 0.00 | 0.554869E+10 | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.00 |
Annual Sum or Average | 0.234494E+11 | 0.316278E+11 | 0.243193E+11 | 0.104912E+11 | 0.138281E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.510675E+09 | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.00 |
Maximum of Months | 0.482882E+10 | 0.554869E+10 | 0.429498E+10 | 0.209229E+10 | 0.245941E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.794922E+10 | 0.107036E+09 | 0.00 | 0.107036E+09 | 0.00 | 0.00 |
February | 0.00 | 0.638078E+10 | 0.427362E+09 | 0.00 | 0.427362E+09 | 0.00 | 0.00 |
March | 0.124989E+09 | 0.519108E+10 | 0.126548E+10 | 0.00 | 0.126548E+10 | 0.00 | 0.00 |
April | 0.101109E+10 | 0.263749E+10 | 0.221279E+10 | 45827845.76 | 0.216696E+10 | 0.00 | 0.00 |
May | 0.287338E+10 | 0.121907E+10 | 0.349811E+10 | 0.546845E+09 | 0.295127E+10 | 0.00 | 0.00 |
June | 0.450089E+10 | 0.551151E+09 | 0.442353E+10 | 0.978081E+09 | 0.344545E+10 | 0.00 | 0.00 |
July | 0.396438E+10 | 0.712275E+09 | 0.383510E+10 | 0.617022E+09 | 0.321808E+10 | 0.00 | 0.00 |
August | 0.204276E+10 | 0.122303E+10 | 0.244874E+10 | 0.132165E+09 | 0.231658E+10 | 0.00 | 0.00 |
September | 0.496337E+09 | 0.243834E+10 | 0.132457E+10 | 1167593.16 | 0.132340E+10 | 0.00 | 0.00 |
October | 46493882.62 | 0.460789E+10 | 0.666088E+09 | 0.00 | 0.666088E+09 | 0.00 | 0.00 |
November | 0.00 | 0.765777E+10 | 0.200043E+09 | 0.00 | 0.200043E+09 | 0.00 | 0.00 |
December | 0.00 | 0.844218E+10 | 32469099.83 | 0.00 | 32469099.83 | 0.00 | 0.00 |
Annual Sum or Average | 0.150603E+11 | 0.490103E+11 | 0.204413E+11 | 0.232111E+10 | 0.181202E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.551151E+09 | 32469099.83 | 0.00 | 32469099.83 | 0.00 | 0.00 |
Maximum of Months | 0.450089E+10 | 0.844218E+10 | 0.442353E+10 | 0.978081E+09 | 0.344545E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 17335396.63 | 0.514947E+10 | 0.186220E+09 | 57401391.31 | 0.128819E+09 | 0.00 | 0.00 |
February | 0.513329E+09 | 0.385816E+10 | 0.935775E+09 | 0.445316E+09 | 0.490460E+09 | 0.00 | 0.00 |
March | 0.259822E+10 | 0.313339E+10 | 0.296625E+10 | 0.150402E+10 | 0.146224E+10 | 0.00 | 0.00 |
April | 0.377376E+10 | 0.168252E+10 | 0.394774E+10 | 0.200062E+10 | 0.194712E+10 | 0.00 | 0.00 |
May | 0.666230E+10 | 0.932644E+09 | 0.593447E+10 | 0.334908E+10 | 0.258539E+10 | 0.00 | 0.00 |
June | 0.612439E+10 | 0.440082E+09 | 0.527895E+10 | 0.246578E+10 | 0.281317E+10 | 0.00 | 0.00 |
July | 0.614422E+10 | 0.533853E+09 | 0.518261E+10 | 0.251643E+10 | 0.266618E+10 | 0.00 | 0.00 |
August | 0.464150E+10 | 0.851527E+09 | 0.410382E+10 | 0.200048E+10 | 0.210333E+10 | 0.00 | 0.00 |
September | 0.230317E+10 | 0.156972E+10 | 0.245464E+10 | 0.107636E+10 | 0.137828E+10 | 0.00 | 0.00 |
October | 0.971174E+09 | 0.282290E+10 | 0.133731E+10 | 0.536208E+09 | 0.801099E+09 | 0.00 | 0.00 |
November | 22472719.06 | 0.491298E+10 | 0.273247E+09 | 94066125.08 | 0.179181E+09 | 0.00 | 0.00 |
December | 0.00 | 0.559126E+10 | 40150501.78 | 9222797.20 | 30927704.58 | 0.00 | 0.00 |
Annual Sum or Average | 0.337719E+11 | 0.314785E+11 | 0.326412E+11 | 0.160550E+11 | 0.165862E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.440082E+09 | 40150501.78 | 9222797.20 | 30927704.58 | 0.00 | 0.00 |
Maximum of Months | 0.666230E+10 | 0.559126E+10 | 0.593447E+10 | 0.334908E+10 | 0.281317E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.800053E+09 | 0.700383E+10 | 0.129317E+10 | 0.855092E+09 | 0.438080E+09 | 0.00 | 0.00 |
February | 0.355584E+10 | 0.510558E+10 | 0.401737E+10 | 0.280252E+10 | 0.121484E+10 | 0.00 | 0.00 |
March | 0.777478E+10 | 0.437461E+10 | 0.761960E+10 | 0.517495E+10 | 0.244465E+10 | 0.00 | 0.00 |
April | 0.101126E+11 | 0.287063E+10 | 0.897437E+10 | 0.558912E+10 | 0.338525E+10 | 0.00 | 0.00 |
May | 0.882409E+10 | 0.161734E+10 | 0.761871E+10 | 0.394082E+10 | 0.367789E+10 | 0.00 | 0.00 |
June | 0.799568E+10 | 0.835573E+09 | 0.672341E+10 | 0.274340E+10 | 0.398002E+10 | 0.00 | 0.00 |
July | 0.813391E+10 | 0.940756E+09 | 0.669991E+10 | 0.290953E+10 | 0.379038E+10 | 0.00 | 0.00 |
August | 0.830506E+10 | 0.142118E+10 | 0.695917E+10 | 0.383779E+10 | 0.312138E+10 | 0.00 | 0.00 |
September | 0.589562E+10 | 0.240248E+10 | 0.545478E+10 | 0.329163E+10 | 0.216316E+10 | 0.00 | 0.00 |
October | 0.380753E+10 | 0.391096E+10 | 0.406750E+10 | 0.258848E+10 | 0.147902E+10 | 0.00 | 0.00 |
November | 0.146409E+10 | 0.644555E+10 | 0.211487E+10 | 0.148137E+10 | 0.633498E+09 | 0.00 | 0.00 |
December | 80170802.75 | 0.784372E+10 | 0.388097E+09 | 0.274441E+09 | 0.113656E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.667495E+11 | 0.447722E+11 | 0.619310E+11 | 0.354891E+11 | 0.264418E+11 | 0.00 | 0.00 |
Minimum of Months | 80170802.75 | 0.835573E+09 | 0.388097E+09 | 0.274441E+09 | 0.113656E+09 | 0.00 | 0.00 |
Maximum of Months | 0.101126E+11 | 0.784372E+10 | 0.897437E+10 | 0.558912E+10 | 0.398002E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.525174E+10 | 98111677.91 | 16874971.83 | 81236706.08 | 0.00 | 0.00 |
February | 0.114225E+09 | 0.400906E+10 | 0.524484E+09 | 0.180583E+09 | 0.343901E+09 | 0.00 | 0.00 |
March | 0.106050E+10 | 0.319245E+10 | 0.175014E+10 | 0.751268E+09 | 0.998871E+09 | 0.00 | 0.00 |
April | 0.400372E+10 | 0.181580E+10 | 0.403068E+10 | 0.209225E+10 | 0.193843E+10 | 0.00 | 0.00 |
May | 0.424624E+10 | 0.976908E+09 | 0.405035E+10 | 0.184883E+10 | 0.220152E+10 | 0.00 | 0.00 |
June | 0.487348E+10 | 0.512513E+09 | 0.429492E+10 | 0.183553E+10 | 0.245939E+10 | 0.00 | 0.00 |
July | 0.423817E+10 | 0.582510E+09 | 0.371175E+10 | 0.140706E+10 | 0.230469E+10 | 0.00 | 0.00 |
August | 0.328800E+10 | 0.895084E+09 | 0.305014E+10 | 0.129358E+10 | 0.175656E+10 | 0.00 | 0.00 |
September | 0.147789E+10 | 0.159969E+10 | 0.178528E+10 | 0.748135E+09 | 0.103714E+10 | 0.00 | 0.00 |
October | 0.272978E+09 | 0.292388E+10 | 0.719858E+09 | 0.214841E+09 | 0.505017E+09 | 0.00 | 0.00 |
November | 30342936.96 | 0.490342E+10 | 0.277522E+09 | 99511754.63 | 0.178010E+09 | 0.00 | 0.00 |
December | 0.00 | 0.561007E+10 | 25756754.09 | 2545318.51 | 23211435.58 | 0.00 | 0.00 |
Annual Sum or Average | 0.236055E+11 | 0.322731E+11 | 0.243190E+11 | 0.104910E+11 | 0.138280E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.512513E+09 | 25756754.09 | 2545318.51 | 23211435.58 | 0.00 | 0.00 |
Maximum of Months | 0.487348E+10 | 0.561007E+10 | 0.429492E+10 | 0.209225E+10 | 0.245939E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.805301E+10 | 0.107039E+09 | 0.00 | 0.107039E+09 | 0.00 | 0.00 |
February | 0.00 | 0.651776E+10 | 0.427372E+09 | 0.00 | 0.427372E+09 | 0.00 | 0.00 |
March | 0.109193E+09 | 0.535053E+10 | 0.126550E+10 | 0.00 | 0.126550E+10 | 0.00 | 0.00 |
April | 0.896489E+09 | 0.279741E+10 | 0.221284E+10 | 45829192.81 | 0.216701E+10 | 0.00 | 0.00 |
May | 0.270915E+10 | 0.130765E+10 | 0.349819E+10 | 0.546861E+09 | 0.295133E+10 | 0.00 | 0.00 |
June | 0.439850E+10 | 0.586551E+09 | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.00 | 0.00 |
July | 0.389454E+10 | 0.741698E+09 | 0.383519E+10 | 0.617040E+09 | 0.321815E+10 | 0.00 | 0.00 |
August | 0.200666E+10 | 0.124590E+10 | 0.244879E+10 | 0.132169E+09 | 0.231663E+10 | 0.00 | 0.00 |
September | 0.480532E+09 | 0.244908E+10 | 0.132460E+10 | 1167627.48 | 0.132343E+10 | 0.00 | 0.00 |
October | 45111922.90 | 0.457991E+10 | 0.666103E+09 | 0.00 | 0.666103E+09 | 0.00 | 0.00 |
November | 0.00 | 0.765491E+10 | 0.200047E+09 | 0.00 | 0.200047E+09 | 0.00 | 0.00 |
December | 0.00 | 0.849109E+10 | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.00 |
Annual Sum or Average | 0.145402E+11 | 0.497755E+11 | 0.204418E+11 | 0.232118E+10 | 0.181206E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.586551E+09 | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.00 |
Maximum of Months | 0.439850E+10 | 0.849109E+10 | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 16675809.78 | 0.520112E+10 | 0.186224E+09 | 57402514.18 | 0.128821E+09 | 0.00 | 0.00 |
February | 0.503048E+09 | 0.392602E+10 | 0.935792E+09 | 0.445324E+09 | 0.490467E+09 | 0.00 | 0.00 |
March | 0.254695E+10 | 0.320712E+10 | 0.296630E+10 | 0.150404E+10 | 0.146226E+10 | 0.00 | 0.00 |
April | 0.369830E+10 | 0.172890E+10 | 0.394781E+10 | 0.200066E+10 | 0.194715E+10 | 0.00 | 0.00 |
May | 0.659543E+10 | 0.948434E+09 | 0.593457E+10 | 0.334914E+10 | 0.258543E+10 | 0.00 | 0.00 |
June | 0.606962E+10 | 0.451332E+09 | 0.527904E+10 | 0.246583E+10 | 0.281321E+10 | 0.00 | 0.00 |
July | 0.610655E+10 | 0.535776E+09 | 0.518269E+10 | 0.251648E+10 | 0.266621E+10 | 0.00 | 0.00 |
August | 0.461743E+10 | 0.842225E+09 | 0.410388E+10 | 0.200052E+10 | 0.210336E+10 | 0.00 | 0.00 |
September | 0.229225E+10 | 0.154060E+10 | 0.245468E+10 | 0.107638E+10 | 0.137830E+10 | 0.00 | 0.00 |
October | 0.966587E+09 | 0.278255E+10 | 0.133733E+10 | 0.536219E+09 | 0.801112E+09 | 0.00 | 0.00 |
November | 22351764.10 | 0.490492E+10 | 0.273252E+09 | 94067965.17 | 0.179184E+09 | 0.00 | 0.00 |
December | 0.00 | 0.561516E+10 | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.00 |
Annual Sum or Average | 0.334352E+11 | 0.316842E+11 | 0.326417E+11 | 0.160553E+11 | 0.165864E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.451332E+09 | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.00 |
Maximum of Months | 0.659543E+10 | 0.561516E+10 | 0.593457E+10 | 0.334914E+10 | 0.281321E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.771277E+09 | 0.723748E+10 | 0.129323E+10 | 0.855128E+09 | 0.438097E+09 | 0.00 | 0.00 |
February | 0.347619E+10 | 0.527335E+10 | 0.401753E+10 | 0.280264E+10 | 0.121489E+10 | 0.00 | 0.00 |
March | 0.761398E+10 | 0.449856E+10 | 0.761990E+10 | 0.517517E+10 | 0.244474E+10 | 0.00 | 0.00 |
April | 0.998755E+10 | 0.289004E+10 | 0.897472E+10 | 0.558935E+10 | 0.338536E+10 | 0.00 | 0.00 |
May | 0.871097E+10 | 0.166081E+10 | 0.761899E+10 | 0.394098E+10 | 0.367801E+10 | 0.00 | 0.00 |
June | 0.790891E+10 | 0.860932E+09 | 0.672366E+10 | 0.274351E+10 | 0.398014E+10 | 0.00 | 0.00 |
July | 0.807199E+10 | 0.948012E+09 | 0.670015E+10 | 0.290965E+10 | 0.379050E+10 | 0.00 | 0.00 |
August | 0.825792E+10 | 0.139826E+10 | 0.695943E+10 | 0.383795E+10 | 0.312148E+10 | 0.00 | 0.00 |
September | 0.585354E+10 | 0.235831E+10 | 0.545499E+10 | 0.329176E+10 | 0.216323E+10 | 0.00 | 0.00 |
October | 0.377235E+10 | 0.387594E+10 | 0.406766E+10 | 0.258859E+10 | 0.147907E+10 | 0.00 | 0.00 |
November | 0.142859E+10 | 0.655669E+10 | 0.211496E+10 | 0.148144E+10 | 0.633523E+09 | 0.00 | 0.00 |
December | 69651517.72 | 0.807276E+10 | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.659229E+11 | 0.456312E+11 | 0.619333E+11 | 0.354906E+11 | 0.264427E+11 | 0.00 | 0.00 |
Minimum of Months | 69651517.72 | 0.860932E+09 | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 0.00 | 0.00 |
Maximum of Months | 0.998755E+10 | 0.807276E+10 | 0.897472E+10 | 0.558935E+10 | 0.398014E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.530916E+10 | 98112947.39 | 16875249.29 | 81237698.10 | 0.00 | 0.00 |
February | 0.109400E+09 | 0.408496E+10 | 0.524491E+09 | 0.180586E+09 | 0.343905E+09 | 0.00 | 0.00 |
March | 0.102494E+10 | 0.327890E+10 | 0.175016E+10 | 0.751280E+09 | 0.998882E+09 | 0.00 | 0.00 |
April | 0.393178E+10 | 0.185921E+10 | 0.403074E+10 | 0.209229E+10 | 0.193845E+10 | 0.00 | 0.00 |
May | 0.417416E+10 | 0.101580E+10 | 0.405040E+10 | 0.184886E+10 | 0.220155E+10 | 0.00 | 0.00 |
June | 0.482431E+10 | 0.531122E+09 | 0.429498E+10 | 0.183556E+10 | 0.245941E+10 | 0.00 | 0.00 |
July | 0.420152E+10 | 0.595182E+09 | 0.371179E+10 | 0.140708E+10 | 0.230472E+10 | 0.00 | 0.00 |
August | 0.326898E+10 | 0.891016E+09 | 0.305018E+10 | 0.129360E+10 | 0.175658E+10 | 0.00 | 0.00 |
September | 0.147081E+10 | 0.157979E+10 | 0.178530E+10 | 0.748147E+09 | 0.103716E+10 | 0.00 | 0.00 |
October | 0.270844E+09 | 0.289795E+10 | 0.719868E+09 | 0.214845E+09 | 0.505023E+09 | 0.00 | 0.00 |
November | 30093714.62 | 0.489911E+10 | 0.277525E+09 | 99513390.80 | 0.178012E+09 | 0.00 | 0.00 |
December | 0.00 | 0.563997E+10 | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.00 |
Annual Sum or Average | 0.233068E+11 | 0.325822E+11 | 0.243193E+11 | 0.104912E+11 | 0.138281E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.531122E+09 | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.00 |
Maximum of Months | 0.482431E+10 | 0.563997E+10 | 0.429498E+10 | 0.209229E+10 | 0.245941E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.634234E+10 | -0.557263E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -769713861.1 | 58.99 | 0.00 | 0.00 |
February | 0.574650E+10 | -0.506458E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -681928623.1 | 58.99 | 0.00 | 0.00 |
March | 0.673099E+10 | -0.599669E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -734301335.4 | 58.99 | 0.00 | 0.00 |
April | 0.608001E+10 | -0.539554E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -684474947.9 | 58.98 | 0.00 | 0.00 |
May | 0.643730E+10 | -0.574475E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692546294.3 | 58.98 | 0.00 | 0.00 |
June | 0.616478E+10 | -0.549824E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666537384.7 | 58.98 | 0.00 | 0.00 |
July | 0.567026E+10 | -0.498393E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -686325600.4 | 58.98 | 0.00 | 0.00 |
August | 0.606778E+10 | -0.537851E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689269647.9 | 58.99 | 0.00 | 0.00 |
September | 0.549702E+10 | -0.482439E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -672624592.0 | 58.98 | 0.00 | 0.00 |
October | 0.580037E+10 | -0.508125E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -719121063.3 | 58.98 | 0.00 | 0.00 |
November | 0.590489E+10 | -0.517719E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -727703444.3 | 58.98 | 0.00 | 0.00 |
December | 0.609804E+10 | -0.533405E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -763983808.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.725403E+11 | -0.640517E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.848853E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.549702E+10 | -0.599669E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -769713861.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.673099E+10 | -0.482439E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -666537384.7 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.61 | 0.48 | 10-JAN-10:00 | 628.12 | 11.79 | 5.83 | 65.33 | 539.44 | 22.88 | 45.50 | 42.33 |
February | 205.83 | 0.54 | 0.48 | 01-FEB-11:30 | 2627.31 | 32.59 | 169.33 | 172.00 | 2310.45 | 35.94 | 191.17 | 156.33 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:20 | 5962.17 | 32.46 | 277.33 | 298.33 | 5205.57 | 33.91 | 286.67 | 281.17 |
April | 421.83 | 0.52 | 0.48 | 01-APR-07:30 | 8380.75 | 30.96 | 285.50 | 381.17 | 1682.82 | 21.17 | 255.50 | 337.83 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-05:30 | 4087.88 | 21.29 | 123.33 | 451.50 | 1214.76 | 19.90 | 272.83 | 393.33 |
June | 583.50 | 0.54 | 0.48 | 01-JUN-05:10 | 1983.04 | 17.35 | 8.17 | 474.33 | 1105.06 | 19.65 | 286.00 | 409.17 |
July | 562.83 | 0.54 | 0.48 | 01-JUL-04:49 | 2362.03 | 17.96 | 23.00 | 471.33 | 1130.43 | 19.69 | 274.17 | 398.67 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-05:49 | 5983.27 | 26.49 | 248.17 | 404.83 | 1288.14 | 20.29 | 240.00 | 353.33 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:49 | 4860.00 | 30.47 | 274.67 | 316.50 | 1697.09 | 21.83 | 198.67 | 278.83 |
October | 265.50 | 0.52 | 0.48 | 01-OCT-07:49 | 2695.35 | 31.14 | 222.50 | 234.33 | 2251.68 | 33.46 | 238.00 | 209.67 |
November | 135.83 | 0.55 | 0.48 | 01-NOV-09:00 | 931.72 | 21.39 | 55.83 | 116.67 | 847.59 | 31.80 | 105.17 | 90.67 |
December | 71.17 | 0.77 | 0.48 | 05-DEC-11:20 | 179.75 | 6.06 | 0.00 | 7.00 | 123.19 | 10.09 | 0.00 | 0.33 |
Annual Sum or Average | 4053.17 | 0.54 | 3998.16 | 24.28 | 1693.67 | 3393.33 | 1685.25 | 23.33 | 2393.67 | 2951.67 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 179.75 | 6.06 | 0.00 | 7.00 | 123.19 | 10.09 | 0.00 | 0.33 | |
Maximum of Months | 583.50 | 0.77 | 0.48 | 8380.75 | 32.59 | 285.50 | 474.33 | 5205.57 | 35.94 | 286.67 | 409.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.70 | 0.48 | 16-JAN-11:00 | 285.98 | 10.33 | 1.67 | 29.83 | 174.87 | 13.23 | 4.67 | 12.00 |
February | 205.83 | 0.59 | 0.48 | 01-FEB-12:20 | 938.97 | 16.95 | 45.67 | 140.00 | 637.64 | 21.56 | 79.83 | 96.83 |
March | 329.50 | 0.53 | 0.48 | 01-MAR-09:20 | 2386.78 | 21.20 | 113.00 | 277.17 | 1552.97 | 23.76 | 154.17 | 238.33 |
April | 421.83 | 0.51 | 0.48 | 01-APR-06:49 | 3087.86 | 22.83 | 135.50 | 385.17 | 1899.56 | 24.11 | 183.00 | 344.50 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-04:40 | 4047.70 | 22.19 | 181.33 | 460.00 | 2129.07 | 23.33 | 195.50 | 417.33 |
June | 583.50 | 0.53 | 0.48 | 01-JUN-03:39 | 3496.86 | 21.68 | 195.83 | 493.83 | 1563.95 | 22.22 | 203.33 | 434.83 |
July | 562.83 | 0.53 | 0.48 | 01-JUL-03:49 | 3484.70 | 21.74 | 198.83 | 478.67 | 1823.58 | 22.84 | 215.17 | 424.67 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-04:49 | 2868.91 | 21.06 | 146.67 | 406.50 | 1480.53 | 22.36 | 170.17 | 357.67 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:19 | 2228.83 | 21.05 | 131.17 | 298.00 | 1172.91 | 22.16 | 141.33 | 252.17 |
October | 265.50 | 0.55 | 0.48 | 01-OCT-07:49 | 1176.10 | 19.69 | 95.50 | 209.50 | 690.70 | 20.70 | 83.00 | 151.67 |
November | 135.83 | 0.64 | 0.48 | 01-NOV-09:00 | 388.22 | 15.83 | 33.83 | 67.00 | 228.87 | 18.34 | 35.83 | 19.50 |
December | 71.17 | 0.88 | 0.55 | 04-DEC-11:30 | 97.58 | 6.08 | 0.00 | 0.00 | 56.81 | 8.43 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 2720.71 | 20.57 | 1279.00 | 3245.67 | 1453.34 | 22.04 | 1466.00 | 2749.50 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 97.58 | 6.08 | 0.00 | 0.00 | 56.81 | 8.43 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.88 | 0.55 | 4047.70 | 22.83 | 198.83 | 493.83 | 2129.07 | 24.11 | 215.17 | 434.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.79 | 0.52 | 31-JAN-11:30 | 167.46 | 7.85 | 0.00 | 4.33 | 97.38 | 10.35 | 0.00 | 0.00 |
February | 205.83 | 0.62 | 0.48 | 11-FEB-12:20 | 368.20 | 12.17 | 0.00 | 106.50 | 216.92 | 14.68 | 0.00 | 23.17 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:00 | 677.10 | 15.55 | 0.00 | 268.83 | 401.64 | 17.91 | 7.00 | 196.17 |
April | 421.83 | 0.51 | 0.48 | 01-APR-07:40 | 891.96 | 17.88 | 0.00 | 394.33 | 553.01 | 20.22 | 56.50 | 337.50 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-04:40 | 1100.12 | 21.51 | 130.33 | 498.50 | 657.34 | 23.68 | 215.17 | 467.50 |
June | 583.50 | 0.51 | 0.48 | 01-JUN-03:39 | 1305.26 | 21.93 | 153.33 | 535.00 | 760.31 | 24.31 | 297.17 | 499.33 |
July | 562.83 | 0.51 | 0.48 | 01-JUL-03:49 | 1185.97 | 21.59 | 140.67 | 516.17 | 673.50 | 22.89 | 231.00 | 463.67 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-04:00 | 919.26 | 19.42 | 64.17 | 422.17 | 525.60 | 19.68 | 71.17 | 360.50 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:49 | 661.48 | 15.64 | 0.00 | 293.33 | 382.37 | 17.86 | 5.17 | 198.33 |
October | 265.50 | 0.57 | 0.48 | 01-OCT-08:09 | 461.32 | 13.61 | 0.00 | 186.00 | 256.46 | 15.89 | 0.00 | 29.67 |
November | 135.83 | 0.73 | 0.48 | 01-NOV-13:30 | 223.61 | 9.68 | 0.00 | 23.33 | 128.30 | 12.40 | 0.00 | 0.00 |
December | 71.17 | 0.92 | 0.77 | 04-DEC-11:30 | 66.17 | 3.36 | 0.00 | 0.00 | 38.84 | 5.50 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 874.56 | 17.89 | 488.50 | 3248.50 | 511.18 | 19.84 | 883.17 | 2575.83 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 66.17 | 3.36 | 0.00 | 0.00 | 38.84 | 5.50 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.92 | 0.77 | 1305.26 | 21.93 | 153.33 | 535.00 | 760.31 | 24.31 | 297.17 | 499.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.72 | 0.48 | 23-JAN-13:20 | 241.30 | 9.89 | 1.67 | 20.67 | 144.92 | 12.74 | 1.83 | 4.17 |
February | 205.83 | 0.56 | 0.48 | 02-FEB-11:09 | 802.73 | 19.52 | 61.50 | 151.17 | 497.05 | 21.80 | 69.83 | 82.67 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:00 | 1800.71 | 20.96 | 97.83 | 288.17 | 1090.89 | 23.20 | 118.33 | 252.33 |
April | 421.83 | 0.51 | 0.48 | 01-APR-08:20 | 3478.80 | 22.73 | 139.50 | 384.67 | 1768.81 | 22.76 | 148.50 | 343.33 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-06:40 | 2761.43 | 19.46 | 117.83 | 479.17 | 1380.71 | 20.19 | 78.33 | 433.33 |
June | 583.50 | 0.52 | 0.48 | 01-JUN-05:40 | 2919.10 | 18.89 | 111.33 | 506.17 | 1480.15 | 19.90 | 79.17 | 451.50 |
July | 562.83 | 0.52 | 0.48 | 01-JUL-04:00 | 2527.98 | 18.82 | 114.50 | 498.17 | 1311.24 | 19.78 | 90.00 | 437.83 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-06:10 | 2292.88 | 20.07 | 117.50 | 419.83 | 1387.76 | 21.65 | 121.00 | 371.83 |
September | 356.33 | 0.52 | 0.48 | 01-SEP-06:00 | 1830.48 | 21.90 | 120.17 | 312.83 | 1112.14 | 22.95 | 114.17 | 256.83 |
October | 265.50 | 0.54 | 0.48 | 01-OCT-08:30 | 920.17 | 19.46 | 82.67 | 214.83 | 531.89 | 20.85 | 65.50 | 137.50 |
November | 135.83 | 0.64 | 0.48 | 01-NOV-10:30 | 374.94 | 15.40 | 33.83 | 64.50 | 250.34 | 20.06 | 45.17 | 24.33 |
December | 71.17 | 0.90 | 0.71 | 04-DEC-11:30 | 84.88 | 5.41 | 0.00 | 0.00 | 48.96 | 7.76 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 2197.80 | 19.40 | 998.33 | 3340.17 | 1184.54 | 20.72 | 931.83 | 2795.67 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 84.88 | 5.41 | 0.00 | 0.00 | 48.96 | 7.76 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.90 | 0.71 | 3478.80 | 22.73 | 139.50 | 506.17 | 1768.81 | 23.20 | 148.50 | 451.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.62 | 0.48 | 10-JAN-10:00 | 571.03 | 7.16 | 5.50 | 61.33 | 434.82 | 11.81 | 6.00 | 38.17 |
February | 205.83 | 0.54 | 0.48 | 01-FEB-11:30 | 2456.01 | 29.41 | 153.17 | 168.50 | 2214.90 | 35.68 | 190.50 | 154.50 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:20 | 5783.24 | 31.76 | 272.33 | 297.00 | 5074.25 | 33.50 | 281.00 | 279.67 |
April | 421.83 | 0.52 | 0.48 | 01-APR-07:40 | 8215.56 | 29.76 | 283.67 | 378.33 | 1557.11 | 18.46 | 33.00 | 332.67 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-05:30 | 3977.66 | 18.43 | 114.67 | 447.00 | 1133.74 | 17.35 | 12.67 | 389.50 |
June | 583.50 | 0.54 | 0.48 | 01-JUN-05:19 | 1886.72 | 13.48 | 0.00 | 470.67 | 1037.98 | 17.01 | 9.83 | 403.00 |
July | 562.83 | 0.54 | 0.48 | 01-JUL-04:49 | 2262.85 | 14.19 | 15.67 | 467.33 | 1060.15 | 17.01 | 11.83 | 394.17 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-05:49 | 5863.49 | 24.67 | 238.50 | 402.00 | 1198.87 | 17.50 | 12.33 | 349.17 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:49 | 4728.88 | 29.45 | 267.17 | 314.83 | 1602.68 | 19.12 | 39.50 | 274.33 |
October | 265.50 | 0.52 | 0.48 | 01-OCT-07:00 | 2544.99 | 28.57 | 204.50 | 231.50 | 2174.45 | 32.70 | 232.00 | 208.50 |
November | 135.83 | 0.56 | 0.48 | 01-NOV-09:00 | 693.64 | 7.78 | 0.00 | 112.00 | 783.61 | 28.40 | 94.17 | 84.83 |
December | 71.17 | 0.79 | 0.48 | 05-DEC-11:30 | 164.36 | 2.18 | 0.00 | 4.33 | 115.60 | 5.95 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 3870.30 | 21.36 | 1555.17 | 3354.83 | 1597.60 | 20.81 | 922.83 | 2908.50 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 164.36 | 2.18 | 0.00 | 4.33 | 115.60 | 5.95 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.79 | 0.48 | 8215.56 | 31.76 | 283.67 | 470.67 | 5074.25 | 35.68 | 281.00 | 403.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.71 | 0.48 | 16-JAN-12:09 | 274.91 | 9.69 | 1.67 | 26.67 | 167.26 | 12.88 | 2.17 | 10.50 |
February | 205.83 | 0.59 | 0.48 | 02-FEB-10:09 | 904.49 | 16.44 | 45.67 | 137.83 | 611.40 | 21.34 | 76.83 | 92.50 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:20 | 2308.03 | 20.76 | 112.67 | 275.17 | 1427.40 | 22.14 | 127.83 | 234.17 |
April | 421.83 | 0.51 | 0.48 | 01-APR-06:00 | 2908.42 | 20.71 | 109.67 | 382.00 | 1827.71 | 23.91 | 172.33 | 340.67 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-04:40 | 3949.61 | 21.76 | 181.33 | 457.50 | 2050.65 | 23.15 | 184.00 | 413.83 |
June | 583.50 | 0.53 | 0.48 | 01-JUN-03:49 | 3409.86 | 21.22 | 194.83 | 491.00 | 1497.87 | 22.01 | 183.00 | 431.17 |
July | 562.83 | 0.53 | 0.48 | 01-JUL-03:00 | 3362.23 | 20.41 | 173.00 | 476.33 | 1749.34 | 22.08 | 184.17 | 419.00 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-04:49 | 2788.24 | 20.61 | 146.17 | 404.50 | 1417.89 | 22.17 | 151.00 | 354.17 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:19 | 2138.16 | 20.38 | 128.00 | 294.50 | 1122.92 | 21.95 | 134.83 | 247.83 |
October | 265.50 | 0.55 | 0.48 | 01-OCT-07:49 | 1078.20 | 17.57 | 73.17 | 207.00 | 663.02 | 20.47 | 81.00 | 147.67 |
November | 135.83 | 0.65 | 0.48 | 01-NOV-09:00 | 374.43 | 15.30 | 33.83 | 63.50 | 219.25 | 18.08 | 35.17 | 16.50 |
December | 71.17 | 0.88 | 0.55 | 04-DEC-11:30 | 93.53 | 5.55 | 0.00 | 0.00 | 54.13 | 8.12 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 2626.65 | 19.68 | 1200.00 | 3216.00 | 1389.96 | 21.64 | 1332.33 | 2708.00 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 93.53 | 5.55 | 0.00 | 0.00 | 54.13 | 8.12 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.88 | 0.55 | 3949.61 | 21.76 | 194.83 | 491.00 | 2050.65 | 23.91 | 184.17 | 431.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.80 | 0.52 | 31-JAN-11:30 | 159.74 | 4.04 | 0.00 | 2.67 | 93.01 | 7.46 | 0.00 | 0.00 |
February | 205.83 | 0.63 | 0.48 | 12-FEB-11:30 | 352.51 | 8.25 | 0.00 | 98.83 | 208.16 | 11.95 | 0.00 | 18.50 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:00 | 650.76 | 11.93 | 0.00 | 264.83 | 387.13 | 15.55 | 0.00 | 186.33 |
April | 421.83 | 0.51 | 0.48 | 01-APR-07:49 | 857.77 | 14.48 | 0.00 | 392.67 | 534.62 | 18.22 | 1.83 | 331.50 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-04:40 | 1059.99 | 18.88 | 128.67 | 496.83 | 634.19 | 21.97 | 133.67 | 464.50 |
June | 583.50 | 0.51 | 0.48 | 01-JUN-03:39 | 1257.46 | 19.27 | 150.00 | 532.50 | 730.92 | 22.48 | 152.50 | 495.17 |
July | 562.83 | 0.51 | 0.48 | 01-JUL-03:00 | 1142.89 | 18.94 | 137.00 | 514.50 | 646.95 | 20.45 | 105.50 | 458.33 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-04:00 | 885.48 | 16.33 | 62.33 | 419.83 | 527.69 | 19.56 | 68.17 | 357.67 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:49 | 636.51 | 11.96 | 0.00 | 290.00 | 368.43 | 15.50 | 0.00 | 185.67 |
October | 265.50 | 0.58 | 0.48 | 01-OCT-08:09 | 443.75 | 9.55 | 0.00 | 179.00 | 246.38 | 13.15 | 0.00 | 23.67 |
November | 135.83 | 0.74 | 0.48 | 06-NOV-13:09 | 213.77 | 5.54 | 0.00 | 18.83 | 122.71 | 9.37 | 0.00 | 0.00 |
December | 71.17 | 0.92 | 0.78 | 04-DEC-11:30 | 62.92 | 0.81 | 0.00 | 0.00 | 37.00 | 3.10 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 841.97 | 14.71 | 478.00 | 3210.50 | 494.62 | 17.85 | 461.67 | 2521.33 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 62.92 | 0.81 | 0.00 | 0.00 | 37.00 | 3.10 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.92 | 0.78 | 1257.46 | 19.27 | 150.00 | 532.50 | 730.92 | 22.48 | 152.50 | 495.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.73 | 0.48 | 23-JAN-13:20 | 232.25 | 9.37 | 1.33 | 18.83 | 138.78 | 12.72 | 1.83 | 3.50 |
February | 205.83 | 0.57 | 0.48 | 02-FEB-11:20 | 735.63 | 16.69 | 44.67 | 146.50 | 477.88 | 21.72 | 70.00 | 77.00 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:00 | 1742.06 | 20.48 | 96.17 | 286.33 | 1024.83 | 21.95 | 103.67 | 246.83 |
April | 421.83 | 0.51 | 0.48 | 01-APR-08:20 | 3391.46 | 22.31 | 139.50 | 383.00 | 1701.11 | 22.62 | 145.00 | 339.00 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-06:40 | 2690.88 | 18.99 | 117.83 | 475.67 | 1324.73 | 20.02 | 75.33 | 428.83 |
June | 583.50 | 0.52 | 0.48 | 01-JUN-05:40 | 2847.77 | 18.40 | 111.33 | 502.67 | 1424.23 | 19.71 | 70.00 | 446.33 |
July | 562.83 | 0.52 | 0.48 | 01-JUL-04:00 | 2453.06 | 18.35 | 114.50 | 492.33 | 1261.54 | 19.60 | 83.83 | 432.00 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-06:19 | 2219.41 | 19.43 | 114.50 | 416.83 | 1339.98 | 21.49 | 117.17 | 366.00 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:00 | 1748.20 | 20.01 | 103.67 | 310.33 | 1073.49 | 22.82 | 112.33 | 253.17 |
October | 265.50 | 0.54 | 0.48 | 01-OCT-08:30 | 893.19 | 19.08 | 82.50 | 211.67 | 511.77 | 20.74 | 65.17 | 127.33 |
November | 135.83 | 0.65 | 0.48 | 01-NOV-10:39 | 360.23 | 15.03 | 33.83 | 61.00 | 239.82 | 20.02 | 45.33 | 22.83 |
December | 71.17 | 0.90 | 0.72 | 04-DEC-11:30 | 81.49 | 5.13 | 0.00 | 0.00 | 46.73 | 7.83 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 2132.11 | 18.68 | 959.83 | 3305.17 | 1137.89 | 20.48 | 889.67 | 2742.83 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 81.49 | 5.13 | 0.00 | 0.00 | 46.73 | 7.83 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.90 | 0.72 | 3391.46 | 22.31 | 139.50 | 502.67 | 1701.11 | 22.82 | 145.00 | 446.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.62 | 0.48 | 10-JAN-10:00 | 571.05 | 7.16 | 5.50 | 61.33 | 434.81 | 11.81 | 6.00 | 38.17 |
February | 205.83 | 0.54 | 0.48 | 01-FEB-11:30 | 2456.05 | 29.41 | 153.17 | 168.50 | 2214.86 | 35.68 | 190.50 | 154.50 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:20 | 5783.23 | 31.76 | 272.33 | 297.00 | 5074.15 | 33.50 | 281.00 | 279.67 |
April | 421.83 | 0.52 | 0.48 | 01-APR-07:40 | 8215.50 | 29.76 | 283.67 | 378.33 | 1557.00 | 18.46 | 33.00 | 332.67 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-05:30 | 3977.57 | 18.43 | 114.67 | 447.00 | 1133.65 | 17.35 | 12.83 | 389.50 |
June | 583.50 | 0.54 | 0.48 | 01-JUN-05:19 | 1886.61 | 13.48 | 0.00 | 470.67 | 1037.90 | 17.01 | 9.83 | 403.00 |
July | 562.83 | 0.54 | 0.48 | 01-JUL-04:49 | 2262.74 | 14.19 | 15.67 | 467.33 | 1060.06 | 17.01 | 11.83 | 394.17 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-05:49 | 5863.40 | 24.67 | 238.50 | 402.00 | 1198.77 | 17.50 | 12.33 | 349.17 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:49 | 4728.84 | 29.45 | 267.17 | 314.83 | 1602.59 | 19.12 | 39.50 | 274.33 |
October | 265.50 | 0.52 | 0.48 | 01-OCT-07:00 | 2544.97 | 28.57 | 204.50 | 231.50 | 2174.40 | 32.71 | 232.00 | 208.50 |
November | 135.83 | 0.56 | 0.48 | 01-NOV-09:00 | 693.67 | 7.78 | 0.00 | 112.00 | 783.59 | 28.40 | 94.17 | 84.83 |
December | 71.17 | 0.79 | 0.48 | 05-DEC-11:30 | 164.37 | 2.18 | 0.00 | 4.33 | 115.60 | 5.95 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 3870.24 | 21.36 | 1555.17 | 3354.83 | 1597.52 | 20.81 | 923.00 | 2908.50 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 164.37 | 2.18 | 0.00 | 4.33 | 115.60 | 5.95 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.79 | 0.48 | 8215.50 | 31.76 | 283.67 | 470.67 | 5074.15 | 35.68 | 281.00 | 403.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.71 | 0.48 | 16-JAN-12:09 | 274.91 | 9.69 | 1.67 | 26.67 | 167.25 | 12.88 | 2.17 | 10.50 |
February | 205.83 | 0.59 | 0.48 | 02-FEB-10:09 | 904.48 | 16.44 | 45.67 | 137.83 | 611.37 | 21.34 | 76.83 | 92.50 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:20 | 2308.02 | 20.76 | 112.67 | 275.17 | 1427.35 | 22.14 | 127.83 | 234.17 |
April | 421.83 | 0.51 | 0.48 | 01-APR-06:00 | 2908.41 | 20.72 | 109.67 | 382.00 | 1827.65 | 23.91 | 172.33 | 340.67 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-04:40 | 3949.58 | 21.76 | 181.33 | 457.50 | 2050.57 | 23.16 | 184.00 | 413.83 |
June | 583.50 | 0.53 | 0.48 | 01-JUN-03:49 | 3410.55 | 21.26 | 195.83 | 491.00 | 1497.79 | 22.01 | 183.00 | 431.17 |
July | 562.83 | 0.53 | 0.48 | 01-JUL-03:00 | 3396.93 | 21.33 | 198.17 | 476.33 | 1749.26 | 22.08 | 184.17 | 419.00 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-04:49 | 2788.20 | 20.61 | 146.17 | 404.50 | 1417.82 | 22.17 | 151.17 | 354.17 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:19 | 2138.13 | 20.38 | 128.00 | 294.50 | 1122.87 | 21.95 | 134.83 | 247.83 |
October | 265.50 | 0.55 | 0.48 | 01-OCT-07:49 | 1078.18 | 17.57 | 73.17 | 207.00 | 662.98 | 20.47 | 81.00 | 147.50 |
November | 135.83 | 0.65 | 0.48 | 01-NOV-09:00 | 374.43 | 15.31 | 33.83 | 63.50 | 219.24 | 18.08 | 35.17 | 16.50 |
December | 71.17 | 0.88 | 0.55 | 04-DEC-11:30 | 93.53 | 5.55 | 0.00 | 0.00 | 54.13 | 8.12 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 2631.55 | 19.82 | 1226.17 | 3216.00 | 1389.90 | 21.64 | 1332.50 | 2707.83 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 93.53 | 5.55 | 0.00 | 0.00 | 54.13 | 8.12 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.88 | 0.55 | 3949.58 | 21.76 | 198.17 | 491.00 | 2050.57 | 23.91 | 184.17 | 431.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.80 | 0.52 | 31-JAN-11:30 | 159.74 | 4.04 | 0.00 | 2.67 | 93.00 | 7.47 | 0.00 | 0.00 |
February | 205.83 | 0.63 | 0.48 | 12-FEB-11:30 | 352.51 | 8.25 | 0.00 | 98.83 | 208.14 | 11.95 | 0.00 | 18.50 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:00 | 650.74 | 11.93 | 0.00 | 264.83 | 387.10 | 15.55 | 0.00 | 186.33 |
April | 421.83 | 0.51 | 0.48 | 01-APR-07:49 | 857.76 | 14.49 | 0.00 | 392.67 | 534.59 | 18.22 | 1.83 | 331.33 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-04:40 | 1059.97 | 18.88 | 128.67 | 496.83 | 634.15 | 21.97 | 133.67 | 464.50 |
June | 583.50 | 0.51 | 0.48 | 01-JUN-03:39 | 1257.43 | 19.27 | 150.00 | 532.50 | 730.88 | 22.48 | 152.50 | 495.17 |
July | 562.83 | 0.51 | 0.48 | 01-JUL-03:00 | 1142.86 | 18.94 | 137.00 | 514.50 | 646.90 | 20.45 | 105.50 | 458.33 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-04:00 | 885.45 | 16.34 | 62.33 | 419.83 | 527.66 | 19.57 | 68.17 | 357.67 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:49 | 636.49 | 11.96 | 0.00 | 290.00 | 368.40 | 15.50 | 0.00 | 185.67 |
October | 265.50 | 0.58 | 0.48 | 01-OCT-08:09 | 443.73 | 9.55 | 0.00 | 179.00 | 246.36 | 13.15 | 0.00 | 23.67 |
November | 135.83 | 0.74 | 0.48 | 06-NOV-13:09 | 213.76 | 5.55 | 0.00 | 18.83 | 122.70 | 9.37 | 0.00 | 0.00 |
December | 71.17 | 0.92 | 0.78 | 04-DEC-11:30 | 62.92 | 0.81 | 0.00 | 0.00 | 36.99 | 3.10 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 841.95 | 14.71 | 478.00 | 3210.50 | 494.59 | 17.85 | 461.67 | 2521.17 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 62.92 | 0.81 | 0.00 | 0.00 | 36.99 | 3.10 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.92 | 0.78 | 1257.43 | 19.27 | 150.00 | 532.50 | 730.88 | 22.48 | 152.50 | 495.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.73 | 0.48 | 23-JAN-13:20 | 232.25 | 9.38 | 1.33 | 18.83 | 138.77 | 12.72 | 1.83 | 3.50 |
February | 205.83 | 0.57 | 0.48 | 02-FEB-11:20 | 735.62 | 16.70 | 44.67 | 146.50 | 477.86 | 21.72 | 70.00 | 77.00 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:00 | 1742.04 | 20.49 | 96.17 | 286.33 | 1024.79 | 21.95 | 103.67 | 246.83 |
April | 421.83 | 0.51 | 0.48 | 01-APR-08:20 | 3391.45 | 22.31 | 139.50 | 383.00 | 1701.04 | 22.62 | 145.17 | 339.00 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-06:40 | 2690.85 | 18.99 | 117.83 | 475.67 | 1324.67 | 20.02 | 75.33 | 428.83 |
June | 583.50 | 0.52 | 0.48 | 01-JUN-05:40 | 2847.72 | 18.40 | 111.33 | 502.67 | 1424.16 | 19.71 | 70.00 | 446.33 |
July | 562.83 | 0.52 | 0.48 | 01-JUL-04:00 | 2453.01 | 18.35 | 114.50 | 492.33 | 1261.48 | 19.60 | 83.83 | 432.00 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-06:19 | 2219.37 | 19.43 | 114.50 | 416.83 | 1339.92 | 21.49 | 117.50 | 365.83 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:00 | 1748.17 | 20.01 | 103.67 | 310.33 | 1073.44 | 22.82 | 112.33 | 253.17 |
October | 265.50 | 0.54 | 0.48 | 01-OCT-08:30 | 893.17 | 19.08 | 82.50 | 211.67 | 511.74 | 20.74 | 65.17 | 127.33 |
November | 135.83 | 0.65 | 0.48 | 01-NOV-10:39 | 360.22 | 15.03 | 33.83 | 61.00 | 239.81 | 20.02 | 45.33 | 22.83 |
December | 71.17 | 0.90 | 0.72 | 04-DEC-11:30 | 81.48 | 5.13 | 0.00 | 0.00 | 46.72 | 7.83 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 2132.08 | 18.68 | 959.83 | 3305.17 | 1137.84 | 20.48 | 890.17 | 2742.67 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 81.48 | 5.13 | 0.00 | 0.00 | 46.72 | 7.83 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.90 | 0.72 | 3391.45 | 22.31 | 139.50 | 502.67 | 1701.04 | 22.82 | 145.17 | 446.33 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.168249E+10 | 20945.88 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.448501E+09 | 20945.88 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28547499.72 | 20945.88 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1850222.98 | 20945.88 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.279934E+09 | 20945.88 | 06-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.638144E+09 | 20945.88 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.168249E+10 | 20945.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.176173E+11 | 15735.02 | 05-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121012E+11 | 15718.60 | 07-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.909859E+10 | 15673.30 | 21-MAR-16:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.289748E+10 | 15647.87 | 13-APR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.841334E+09 | 16026.67 | 19-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.178932E+09 | 15353.29 | 02-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.127696E+09 | 10805.54 | 05-JUL-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.387000E+09 | 16032.61 | 21-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.178614E+10 | 15967.77 | 05-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.614287E+10 | 15687.93 | 16-OCT-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141618E+11 | 15725.86 | 14-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178008E+11 | 15704.26 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.831412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.127696E+09 | 10805.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.178008E+11 | 16032.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.699772E+10 | 10048.66 | 24-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.495488E+10 | 10054.85 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.246742E+10 | 10029.40 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.432179E+09 | 9979.53 | 07-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21688507.73 | 8479.45 | 28-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117851E+10 | 10039.80 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.474721E+10 | 10050.12 | 21-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.646114E+10 | 10054.79 | 20-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.272607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.699772E+10 | 10054.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.997767E+10 | 7828.26 | 05-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.798443E+10 | 7818.83 | 07-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.616988E+10 | 7793.40 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146428E+10 | 7777.32 | 18-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103929E+09 | 7791.25 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.233838E+10 | 7801.33 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.706709E+10 | 7824.32 | 14-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.922618E+10 | 7813.07 | 20-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.443318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.997767E+10 | 7828.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.711013E+10 | 10541.79 | 24-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.540407E+10 | 10548.26 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.347404E+10 | 10521.58 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.487301E+09 | 10469.27 | 07-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 260564.26 | 391.62 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41808439.02 | 8584.60 | 28-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145384E+10 | 10532.51 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.474693E+10 | 10543.33 | 21-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.648036E+10 | 10548.21 | 20-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.291987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.711013E+10 | 10548.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.700779E+10 | 27073.77 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.409512E+10 | 27073.77 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153799E+10 | 27073.77 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.185554E+09 | 27073.77 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108119E+10 | 27073.77 | 10-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.486972E+10 | 27073.77 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.665023E+10 | 27073.77 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.254276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.700779E+10 | 27073.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.785671E+10 | 16629.75 | 01-JAN-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.415722E+10 | 16629.75 | 01-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.200400E+10 | 16629.75 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.371739E+09 | 16629.75 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 60307221.79 | 13822.35 | 28-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168265E+10 | 16629.75 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.563582E+10 | 16629.75 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.839569E+10 | 16629.75 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.839569E+10 | 16629.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.580167E+10 | 10998.87 | 01-JAN-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.353298E+10 | 10998.87 | 01-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161614E+10 | 10998.87 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.281951E+09 | 10998.87 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 51622222.51 | 9729.91 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136944E+10 | 10998.87 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.453318E+10 | 10998.87 | 01-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.583818E+10 | 10998.87 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.583818E+10 | 10998.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.876493E+10 | 8901.77 | 12-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.616907E+10 | 8702.98 | 13-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.404361E+10 | 8719.00 | 21-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.742393E+09 | 8700.00 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133494E+09 | 8616.77 | 28-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.262362E+10 | 8728.69 | 11-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.695655E+10 | 8717.85 | 07-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.865709E+10 | 8709.34 | 30-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.380908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.876493E+10 | 8901.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.592789E+10 | 10953.19 | 01-JAN-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.393739E+10 | 10953.19 | 01-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225875E+10 | 10953.19 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.354563E+09 | 10953.19 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 70683369.19 | 10689.50 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164740E+10 | 10953.19 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.456302E+10 | 10953.19 | 01-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.588391E+10 | 10953.19 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.592789E+10 | 10953.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.153307E+11 | 30641.83 | 27-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102781E+11 | 30600.73 | 10-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.627394E+10 | 30591.43 | 10-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127817E+10 | 30488.43 | 01-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.202821E+09 | 30131.22 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.483499E+10 | 30654.39 | 10-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128912E+11 | 30641.12 | 16-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153921E+11 | 30563.84 | 20-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.664820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.153921E+11 | 30654.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.118731E+11 | 19288.96 | 24-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.710790E+10 | 19239.19 | 23-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.411180E+10 | 19322.46 | 18-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105284E+10 | 19180.95 | 08-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8083626.67 | 9818.78 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7716082.83 | 6698.79 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.337749E+09 | 19224.31 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.358918E+10 | 19253.36 | 31-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.951743E+10 | 19293.87 | 07-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129122E+11 | 19271.25 | 22-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.505180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.129122E+11 | 19322.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.855480E+10 | 12205.77 | 24-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.581139E+10 | 12174.30 | 23-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.317427E+10 | 12227.46 | 18-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.750306E+09 | 12189.14 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176609.38 | 1177.40 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2251060.49 | 7002.26 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.223231E+09 | 12179.34 | 28-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.282340E+10 | 12183.30 | 31-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.733811E+10 | 12209.07 | 07-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.884834E+10 | 12194.59 | 22-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.375263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.884834E+10 | 12227.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.128130E+11 | 9931.23 | 27-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.966638E+10 | 9909.36 | 10-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.704665E+10 | 9929.04 | 22-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182825E+10 | 9907.34 | 06-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15854771.02 | 8219.55 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 12473962.27 | 9823.07 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.630288E+09 | 9879.67 | 05-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.516854E+10 | 9924.05 | 19-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111189E+11 | 9931.68 | 16-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130488E+11 | 9904.68 | 20-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.613492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.130488E+11 | 9931.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.866414E+10 | 12726.85 | 24-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.625109E+10 | 12694.03 | 23-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.411170E+10 | 12749.46 | 18-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.928746E+09 | 12655.79 | 08-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11287626.12 | 6939.02 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6446018.88 | 5859.61 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.341166E+09 | 12692.22 | 28-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.321924E+10 | 12703.42 | 31-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.733754E+10 | 12730.31 | 07-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.886693E+10 | 12715.19 | 22-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.397383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.886693E+10 | 12749.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.155287E+11 | 58547.19 | 12-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.906959E+10 | 54717.97 | 27-FEB-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.291850E+10 | 49228.23 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123079E+09 | 5894.18 | 24-APR-17:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29853652.07 | 4808.11 | 16-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 277970.91 | 865.10 | 02-JUN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15551461.10 | 11576.19 | 31-AUG-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 65927095.63 | 10267.07 | 15-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.441103E+09 | 5586.06 | 31-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135420E+11 | 50316.55 | 28-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.214040E+11 | 56700.63 | 15-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.631387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.214040E+11 | 58547.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.147969E+11 | 59877.62 | 12-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.874376E+10 | 52781.57 | 27-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.325257E+10 | 48637.02 | 01-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173623E+09 | 6429.81 | 03-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22320491.50 | 5990.48 | 05-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1373999.24 | 1348.87 | 01-JUN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 625504.39 | 2343.42 | 05-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9769386.25 | 4951.77 | 28-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11926228.16 | 4070.36 | 28-SEP-12:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.848961E+09 | 5842.72 | 12-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130891E+11 | 48048.01 | 29-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.196199E+11 | 54321.86 | 15-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.605708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 625504.39 | 1348.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.196199E+11 | 59877.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.201351E+11 | 59016.04 | 12-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124575E+11 | 49392.39 | 22-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.533596E+10 | 48466.08 | 04-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.538479E+09 | 8998.08 | 03-APR-04:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18418272.19 | 6964.35 | 04-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1283595.64 | 1691.94 | 01-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1332582.23 | 895.19 | 05-JUL-08:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5719094.17 | 3884.20 | 10-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 59228517.31 | 3005.94 | 28-SEP-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202426E+10 | 9580.04 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178824E+11 | 48409.56 | 29-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.254773E+11 | 54492.83 | 15-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.839370E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1283595.64 | 895.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.254773E+11 | 59016.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3750222.28 | 3735435.99 | 7350.20 | 19-JAN-07:01 | 7350.20 | 0.00 |
February | 0.00 | 0.00 | 9420584.80 | 8887937.07 | 7357.69 | 07-FEB-07:01 | 7357.69 | 0.00 |
March | 0.00 | 0.00 | 18327030.92 | 17742470.07 | 2513.27 | 24-MAR-07:18 | 2513.27 | 0.00 |
April | 0.00 | 0.00 | 0.214911E+10 | 0.214897E+10 | 25752.26 | 21-APR-16:00 | 25752.26 | 0.00 |
May | 0.00 | 0.00 | 0.576633E+10 | 0.574228E+10 | 35435.84 | 31-MAY-16:00 | 35435.84 | 0.00 |
June | 0.00 | 0.00 | 0.200118E+11 | 0.191429E+11 | 62495.75 | 30-JUN-11:40 | 50015.49 | 0.00 |
July | 0.00 | 0.00 | 0.284737E+11 | 0.261871E+11 | 63270.65 | 11-JUL-15:50 | 59745.42 | 0.00 |
August | 0.00 | 0.00 | 0.167614E+11 | 0.156166E+11 | 59042.90 | 11-AUG-15:50 | 59042.90 | 0.00 |
September | 0.00 | 0.00 | 0.349108E+10 | 0.338451E+10 | 29409.24 | 07-SEP-16:00 | 29409.24 | 0.00 |
October | 0.00 | 0.00 | 98663962.01 | 96654144.02 | 5877.04 | 05-OCT-16:00 | 5877.04 | 0.00 |
November | 0.00 | 0.00 | 3542096.11 | 3476746.69 | 4285.63 | 21-NOV-07:01 | 4285.63 | 0.00 |
December | 0.00 | 0.00 | 2134069.17 | 2132515.29 | 5248.28 | 20-DEC-07:01 | 5248.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.767893E+11 | 0.723550E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 2134069.17 | 2132515.29 | 2513.27 | 2513.27 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.284737E+11 | 0.261871E+11 | 63270.65 | 59745.42 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3243479.74 | 3243479.74 | 5946.68 | 19-JAN-07:01 | 5946.68 | 0.00 |
February | 0.00 | 0.00 | 4826356.62 | 4805218.08 | 7428.57 | 10-FEB-07:01 | 7428.57 | 0.00 |
March | 0.00 | 0.00 | 9898226.33 | 9760791.88 | 9100.60 | 21-MAR-06:01 | 9100.60 | 0.00 |
April | 0.00 | 0.00 | 0.103667E+09 | 0.103420E+09 | 6059.20 | 05-APR-06:01 | 6059.20 | 0.00 |
May | 0.00 | 0.00 | 0.402554E+10 | 0.401365E+10 | 36396.43 | 31-MAY-16:00 | 36396.43 | 0.00 |
June | 0.00 | 0.00 | 0.197918E+11 | 0.189666E+11 | 64360.06 | 30-JUN-12:05 | 55448.48 | 0.00 |
July | 0.00 | 0.00 | 0.266432E+11 | 0.245262E+11 | 59970.75 | 11-JUL-15:30 | 56322.18 | 0.00 |
August | 0.00 | 0.00 | 0.144453E+11 | 0.133910E+11 | 54007.05 | 11-AUG-15:20 | 54007.05 | 0.00 |
September | 0.00 | 0.00 | 0.571795E+09 | 0.551157E+09 | 16985.67 | 07-SEP-13:10 | 16985.67 | 0.00 |
October | 0.00 | 0.00 | 21102258.20 | 20159079.42 | 8400.35 | 12-OCT-06:01 | 8400.35 | 0.00 |
November | 0.00 | 0.00 | 2590156.68 | 2590156.68 | 5364.95 | 02-NOV-06:01 | 5364.95 | 0.00 |
December | 0.00 | 0.00 | 1843989.97 | 1840015.83 | 4996.83 | 23-DEC-07:03 | 4996.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.656248E+11 | 0.615944E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1843989.97 | 1840015.83 | 4996.83 | 4996.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.266432E+11 | 0.245262E+11 | 64360.06 | 56322.18 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 50470.84 | 50470.84 | 672.94 | 19-JAN-07:01 | 672.94 | 0.00 |
February | 0.00 | 0.00 | 499609.85 | 499609.85 | 3343.61 | 09-FEB-07:02 | 3343.61 | 0.00 |
March | 0.00 | 0.00 | 2644461.16 | 2497650.96 | 3363.02 | 23-MAR-06:02 | 3363.02 | 0.00 |
April | 0.00 | 0.00 | 0.596498E+09 | 0.595759E+09 | 27626.70 | 21-APR-15:10 | 27626.70 | 0.00 |
May | 0.00 | 0.00 | 0.388751E+10 | 0.386812E+10 | 38159.07 | 31-MAY-16:00 | 38159.07 | 0.00 |
June | 0.00 | 0.00 | 0.201598E+11 | 0.193024E+11 | 67113.25 | 30-JUN-12:30 | 59634.26 | 0.00 |
July | 0.00 | 0.00 | 0.271059E+11 | 0.249614E+11 | 61943.53 | 21-JUL-14:30 | 61943.53 | 0.00 |
August | 0.00 | 0.00 | 0.141398E+11 | 0.130102E+11 | 56553.23 | 11-AUG-15:50 | 56553.23 | 0.00 |
September | 0.00 | 0.00 | 0.823024E+09 | 0.795710E+09 | 20127.23 | 08-SEP-15:40 | 20127.23 | 0.00 |
October | 0.00 | 0.00 | 6761681.27 | 6376430.50 | 4393.72 | 02-OCT-06:03 | 4393.72 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.667224E+11 | 0.625430E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.271059E+11 | 0.249614E+11 | 67113.25 | 61943.53 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 2232.62 | 7808.38 | 10-JAN-12:16 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2245.39 | 7808.44 | 27-FEB-12:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2393.99 | 7807.51 | 31-MAR-11:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2233.00 | 7808.05 | 26-APR-11:09 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 2298.00 | 7802.94 | 03-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 2276.00 | 7583.98 | 01-JUN-11:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 2011.64 | 7285.93 | 05-JUL-11:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 2164.19 | 7058.60 | 07-AUG-11:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 2013.52 | 7025.36 | 28-SEP-11:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 2049.56 | 7250.49 | 31-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 2150.50 | 7530.17 | 30-NOV-12:12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2141.95 | 7805.89 | 29-DEC-12:07 |
Annual Sum or Average | 0.00 | 2183.87 | ||||
Minimum of Months | 0.00 | 0.00 | 2011.64 | 7025.36 | ||
Maximum of Months | 0.00 | 0.00 | 2393.99 | 7808.44 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.194459E+10 | 0.42 | 2940.89 | 02-JAN-05:01 | 0.84 |
February | 0.160908E+10 | 0.42 | 2940.89 | 01-FEB-07:01 | 0.84 |
March | 0.148098E+10 | 0.37 | 2940.89 | 01-MAR-07:01 | 0.84 |
April | 0.162888E+10 | 0.33 | 3511.90 | 21-APR-16:00 | 0.92 |
May | 0.299844E+10 | 0.40 | 6253.79 | 17-MAY-06:03 | 1.29 |
June | 0.455943E+10 | 0.50 | 10256.32 | 12-JUN-06:01 | 1.76 |
July | 0.482641E+10 | 0.49 | 9990.59 | 10-JUL-06:02 | 1.73 |
August | 0.420451E+10 | 0.47 | 8673.34 | 11-AUG-15:50 | 1.58 |
September | 0.194563E+10 | 0.34 | 4287.56 | 08-SEP-12:06 | 1.03 |
October | 0.132096E+10 | 0.31 | 2940.89 | 30-OCT-06:01 | 0.84 |
November | 0.147198E+10 | 0.35 | 2940.89 | 06-NOV-07:01 | 0.84 |
December | 0.179494E+10 | 0.38 | 2940.89 | 04-DEC-06:01 | 0.84 |
Annual Sum or Average | 0.297858E+11 | 0.40 | |||
Minimum of Months | 0.132096E+10 | 0.31 | 2940.89 | 0.84 | |
Maximum of Months | 0.482641E+10 | 0.50 | 10256.32 | 1.76 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.162439E+10 | 0.41 | 3063.29 | 02-JAN-05:01 | 0.91 |
February | 0.134405E+10 | 0.40 | 3063.29 | 01-FEB-06:01 | 0.91 |
March | 0.129841E+10 | 0.35 | 3063.29 | 01-MAR-06:01 | 0.91 |
April | 0.157487E+10 | 0.34 | 4720.67 | 21-APR-15:30 | 1.17 |
May | 0.310626E+10 | 0.43 | 7365.86 | 31-MAY-14:05 | 1.54 |
June | 0.475150E+10 | 0.54 | 10514.19 | 05-JUN-06:01 | 1.92 |
July | 0.453106E+10 | 0.51 | 10514.19 | 10-JUL-06:02 | 1.92 |
August | 0.353705E+10 | 0.45 | 8333.78 | 10-AUG-15:30 | 1.66 |
September | 0.142714E+10 | 0.33 | 3965.93 | 08-SEP-12:01 | 1.05 |
October | 0.115342E+10 | 0.32 | 3063.29 | 11-OCT-06:01 | 0.91 |
November | 0.137382E+10 | 0.37 | 3063.29 | 01-NOV-05:01 | 0.91 |
December | 0.156271E+10 | 0.39 | 3063.29 | 01-DEC-06:01 | 0.91 |
Annual Sum or Average | 0.272847E+11 | 0.40 | |||
Minimum of Months | 0.115342E+10 | 0.32 | 3063.29 | 0.91 | |
Maximum of Months | 0.475150E+10 | 0.54 | 10514.19 | 1.92 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.207778E+10 | 0.46 | 2859.47 | 02-JAN-07:03 | 0.83 |
February | 0.172758E+10 | 0.46 | 2859.47 | 01-FEB-07:02 | 0.83 |
March | 0.167213E+10 | 0.43 | 2859.47 | 01-MAR-07:02 | 0.83 |
April | 0.155128E+10 | 0.35 | 3961.38 | 21-APR-15:50 | 1.00 |
May | 0.265837E+10 | 0.40 | 6949.97 | 31-MAY-14:50 | 1.40 |
June | 0.425152E+10 | 0.49 | 9107.29 | 22-JUN-06:02 | 1.65 |
July | 0.404728E+10 | 0.46 | 10311.13 | 24-JUL-06:02 | 1.78 |
August | 0.298761E+10 | 0.41 | 7708.97 | 10-AUG-15:20 | 1.49 |
September | 0.130265E+10 | 0.33 | 2544.94 | 08-SEP-15:30 | 0.78 |
October | 0.142152E+10 | 0.38 | 2859.47 | 10-OCT-05:01 | 0.83 |
November | 0.191301E+10 | 0.46 | 2859.47 | 03-NOV-06:01 | 0.83 |
December | 0.215900E+10 | 0.48 | 2859.47 | 01-DEC-07:01 | 0.83 |
Annual Sum or Average | 0.277697E+11 | 0.43 | |||
Minimum of Months | 0.130265E+10 | 0.33 | 2544.94 | 0.78 | |
Maximum of Months | 0.425152E+10 | 0.49 | 10311.13 | 1.78 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:02 | 2.06 | 2.06 | 56.62 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 55.34 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 55.46 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:01 | 2.06 | 2.06 | 55.91 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 55.55 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 55.93 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 55.10 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 55.20 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 55.71 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 56.83 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:01 | 2.06 | 2.06 | 55.34 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:01 | 2.06 | 2.06 | 54.96 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 54.96 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 56.83 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 56.36 | 56.36 | 2232.62 | 7808.38 | 10-JAN-12:16 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 55.59 | 55.59 | 2245.39 | 7808.44 | 27-FEB-12:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 55.92 | 55.92 | 2393.99 | 7807.51 | 31-MAR-11:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.41 | 56.41 | 2233.00 | 7808.05 | 26-APR-11:09 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.22 | 57.22 | 2298.00 | 7802.94 | 03-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.61 | 56.61 | 2276.00 | 7583.98 | 01-JUN-11:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.82 | 56.82 | 2011.64 | 7285.93 | 05-JUL-11:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 55.78 | 55.78 | 2164.19 | 7058.60 | 07-AUG-11:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.95 | 56.95 | 2013.52 | 7025.36 | 28-SEP-11:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 54.57 | 54.57 | 2049.56 | 7250.49 | 31-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 55.78 | 55.78 | 2150.50 | 7530.17 | 30-NOV-12:12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 55.54 | 55.54 | 2141.95 | 7805.89 | 29-DEC-12:07 |
Annual Sum or Average | 0.00 | 2183.87 | ||||||
Minimum of Months | 0.00 | 0.00 | 54.57 | 54.57 | 2011.64 | 7025.36 | ||
Maximum of Months | 0.00 | 0.00 | 57.22 | 57.22 | 2393.99 | 7808.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.453310E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.325049E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.227248E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.747156E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.533651E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.964051E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.117740E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.868360E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.480198E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.124647E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.324760E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.424022E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.235612E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.480198E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.453310E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.369843E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.232372E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.127617E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.354110E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.414544E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.956678E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.109065E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.706221E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.189953E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.956376E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.279329E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.369883E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.184590E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.189953E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.369883E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.593136E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.408426E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.263913E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.754492E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.370302E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.918274E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.105664E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.649249E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.325867E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.210588E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.501162E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.612273E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.299698E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.325867E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.612273E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.194459E+10 | 3750222.28 | 0.589140E+11 | 0.286341E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160908E+10 | 9420584.80 | 0.399627E+11 | 0.241221E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148098E+10 | 18327030.92 | 0.241570E+11 | 0.275414E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162888E+10 | 0.214911E+10 | 0.540432E+10 | 0.879944E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.299844E+10 | 0.576633E+10 | 0.871448E+09 | 0.447236E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.455943E+10 | 0.200118E+11 | 0.179210E+09 | 57621142.29 | 5593154.21 | 0.00 | 0.00 | 0.00 |
July | 0.482641E+10 | 0.284737E+11 | 0.127696E+09 | 0.125135E+09 | 60624524.76 | 0.00 | 0.00 | 0.00 |
August | 0.420451E+10 | 0.167614E+11 | 0.402551E+09 | 97929765.77 | 66762.80 | 0.00 | 0.00 | 0.00 |
September | 0.194563E+10 | 0.349108E+10 | 0.201949E+10 | 0.363041E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132096E+10 | 98663962.01 | 0.115565E+11 | 0.185598E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147198E+10 | 3542096.11 | 0.445450E+11 | 0.269320E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179494E+10 | 2134069.17 | 0.620107E+11 | 0.253302E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.297858E+11 | 0.767893E+11 | 0.250151E+12 | 0.164277E+12 | 66284441.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132096E+10 | 2134069.17 | 0.127696E+09 | 57621142.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.482641E+10 | 0.284737E+11 | 0.620107E+11 | 0.286341E+11 | 60624524.76 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.162439E+10 | 3243479.74 | 0.501559E+11 | 0.250227E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134405E+10 | 4826356.62 | 0.306355E+11 | 0.218253E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129841E+10 | 9898226.33 | 0.147131E+11 | 0.265209E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157487E+10 | 0.103667E+09 | 0.210982E+10 | 0.936750E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.310626E+10 | 0.402554E+10 | 22320491.50 | 0.718659E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.475150E+10 | 0.197918E+11 | 1373999.24 | 69950891.66 | 6561863.35 | 0.00 | 0.00 | 0.00 |
July | 0.453106E+10 | 0.266432E+11 | 625504.39 | 0.156543E+09 | 62804776.32 | 0.00 | 0.00 | 0.00 |
August | 0.353705E+10 | 0.144453E+11 | 9769386.25 | 0.329828E+09 | 53305.62 | 0.00 | 0.00 | 0.00 |
September | 0.142714E+10 | 0.571795E+09 | 0.328033E+09 | 0.529445E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115342E+10 | 21102258.20 | 0.925328E+10 | 0.184127E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137382E+10 | 2590156.68 | 0.396474E+11 | 0.242683E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156271E+10 | 1843989.97 | 0.550450E+11 | 0.222352E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.272847E+11 | 0.656248E+11 | 0.201922E+12 | 0.154222E+12 | 69419945.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.115342E+10 | 1843989.97 | 625504.39 | 69950891.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.475150E+10 | 0.266432E+11 | 0.550450E+11 | 0.265209E+11 | 62804776.32 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.207778E+10 | 50470.84 | 0.773709E+11 | 0.256732E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172758E+10 | 499609.85 | 0.515724E+11 | 0.222158E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167213E+10 | 2644461.16 | 0.300543E+11 | 0.265586E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155128E+10 | 0.596498E+09 | 0.637679E+10 | 0.992228E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.265837E+10 | 0.388751E+10 | 53820905.39 | 0.106063E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.425152E+10 | 0.201598E+11 | 1283595.64 | 50819302.93 | 6265475.33 | 0.00 | 0.00 | 0.00 |
July | 0.404728E+10 | 0.271059E+11 | 1332582.23 | 0.134088E+09 | 48370494.91 | 0.00 | 0.00 | 0.00 |
August | 0.298761E+10 | 0.141398E+11 | 34606218.64 | 0.582024E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130265E+10 | 0.823024E+09 | 0.179448E+10 | 0.616242E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142152E+10 | 6761681.27 | 0.216596E+11 | 0.189659E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191301E+10 | 0.00 | 0.660856E+11 | 0.247953E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.215900E+10 | 0.00 | 0.845456E+11 | 0.229983E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.277697E+11 | 0.667224E+11 | 0.339551E+12 | 0.159119E+12 | 54635970.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130265E+10 | 0.00 | 1283595.64 | 50819302.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.425152E+10 | 0.271059E+11 | 0.845456E+11 | 0.265586E+11 | 48370494.91 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.194459E+10 | 0.00 | 0.00 | 0.00 | 1073688.74 | 0.433853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160908E+10 | 0.00 | 0.00 | 0.00 | 2752930.91 | 0.308931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148098E+10 | 0.00 | 0.00 | 0.00 | 5381897.09 | 0.212385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162888E+10 | 0.00 | 0.00 | 0.00 | 0.561438E+09 | 0.528124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.299844E+10 | 0.00 | 0.00 | 0.00 | 0.149648E+10 | 0.841595E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.455943E+10 | 0.00 | 0.00 | 0.00 | 0.490215E+10 | 0.178932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.482641E+10 | 0.00 | 0.00 | 0.00 | 0.681989E+10 | 0.127696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.420451E+10 | 0.00 | 0.00 | 0.00 | 0.409209E+10 | 0.387000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.194563E+10 | 0.00 | 0.00 | 0.00 | 0.902781E+09 | 0.195356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132096E+10 | 0.00 | 0.00 | 0.00 | 28336419.12 | 0.111154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147198E+10 | 0.00 | 0.00 | 0.00 | 1031520.88 | 0.310030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179494E+10 | 0.00 | 0.00 | 0.00 | 617423.20 | 0.406067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.297858E+11 | 0.00 | 0.00 | 0.00 | 0.188140E+11 | 0.187012E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132096E+10 | 0.00 | 0.00 | 0.00 | 617423.20 | 0.127696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.482641E+10 | 0.00 | 0.00 | 0.00 | 0.681989E+10 | 0.433853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.162439E+10 | 0.00 | 0.00 | 0.00 | 919144.47 | 0.353590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134405E+10 | 0.00 | 0.00 | 0.00 | 1351680.16 | 0.218918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129841E+10 | 0.00 | 0.00 | 0.00 | 2815866.55 | 0.114605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157487E+10 | 0.00 | 0.00 | 0.00 | 30027497.19 | 0.193620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.310626E+10 | 0.00 | 0.00 | 0.00 | 0.103917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.475150E+10 | 0.00 | 0.00 | 0.00 | 0.481528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.453106E+10 | 0.00 | 0.00 | 0.00 | 0.637546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.353705E+10 | 0.00 | 0.00 | 0.00 | 0.352516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142714E+10 | 0.00 | 0.00 | 0.00 | 0.156284E+09 | 0.316107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115342E+10 | 0.00 | 0.00 | 0.00 | 6022510.02 | 0.840431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137382E+10 | 0.00 | 0.00 | 0.00 | 735257.94 | 0.265583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156271E+10 | 0.00 | 0.00 | 0.00 | 527938.08 | 0.354251E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.272847E+11 | 0.00 | 0.00 | 0.00 | 0.159538E+11 | 0.141351E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.115342E+10 | 0.00 | 0.00 | 0.00 | 527938.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.475150E+10 | 0.00 | 0.00 | 0.00 | 0.637546E+10 | 0.354251E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.207778E+10 | 0.00 | 0.00 | 0.00 | 14844.29 | 0.572358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172758E+10 | 0.00 | 0.00 | 0.00 | 143777.21 | 0.391148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167213E+10 | 0.00 | 0.00 | 0.00 | 775735.33 | 0.247183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155128E+10 | 0.00 | 0.00 | 0.00 | 0.155327E+09 | 0.583832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.265837E+10 | 0.00 | 0.00 | 0.00 | 0.100925E+10 | 35402633.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.425152E+10 | 0.00 | 0.00 | 0.00 | 0.493122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.404728E+10 | 0.00 | 0.00 | 0.00 | 0.651916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.298761E+10 | 0.00 | 0.00 | 0.00 | 0.347599E+10 | 28887124.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130265E+10 | 0.00 | 0.00 | 0.00 | 0.220768E+09 | 0.173525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142152E+10 | 0.00 | 0.00 | 0.00 | 1972189.94 | 0.196353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.215900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.590683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.277697E+11 | 0.00 | 0.00 | 0.00 | 0.163146E+11 | 0.255614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.425152E+10 | 0.00 | 0.00 | 0.00 | 0.651916E+10 | 0.590683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.113849E+11 | 0.00 | 0.00 | 5177.25 | 0.00 | 0.874758E+09 | 18413231.69 | 0.00 | 0.25 |
February | 0.903195E+10 | 0.00 | 0.00 | 1207180.79 | 0.00 | 0.490613E+09 | 0.843033E+09 | 0.00 | 0.27 |
March | 0.682148E+10 | 0.00 | 0.00 | 7920438.75 | 0.00 | 16594647.36 | 0.363630E+10 | 0.00 | 0.31 |
April | 0.252372E+10 | 0.00 | 0.00 | 27947126.82 | 0.00 | 0.00 | 0.116468E+11 | 0.00 | 0.39 |
May | 0.124628E+10 | 0.00 | 0.00 | 45534912.08 | 0.00 | 0.00 | 0.228173E+11 | 0.00 | 0.87 |
June | 0.859610E+09 | 6455295.40 | 0.00 | 52133475.39 | 0.00 | 0.00 | 0.205123E+11 | 0.00 | 1.19 |
July | 0.105900E+10 | 57822500.93 | 0.00 | 48645906.67 | 6405748.49 | 0.00 | 0.155735E+11 | 0.00 | 1.11 |
August | 0.782341E+09 | 188325.65 | 0.00 | 54893369.46 | 0.00 | 0.00 | 0.220897E+11 | 0.00 | 1.07 |
September | 0.121757E+10 | 0.00 | 0.00 | 37298785.28 | 0.00 | 0.00 | 0.172641E+11 | 0.00 | 0.52 |
October | 0.384365E+10 | 0.00 | 0.00 | 15008755.84 | 0.00 | 560648.51 | 0.716034E+10 | 0.00 | 0.34 |
November | 0.113998E+11 | 0.00 | 0.00 | 458517.80 | 0.00 | 0.113731E+09 | 0.599045E+09 | 0.00 | 0.26 |
December | 0.145317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146800E+09 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.647021E+11 | 64466121.99 | 0.00 | 0.291054E+09 | 6405748.49 | 0.164306E+10 | 0.122161E+12 | 0.00 | 0.57 |
Minimum of Months | 0.782341E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.145317E+11 | 57822500.93 | 0.00 | 54893369.46 | 6405748.49 | 0.874758E+09 | 0.228173E+11 | 0.00 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.712410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594313E+10 | 0.00 | 0.00 | 0.27 |
February | 0.622188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422071E+10 | 0.00 | 0.00 | 0.28 |
March | 0.873980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819710E+09 | 0.00 | 0.00 | 0.30 |
April | 0.591693E+10 | 0.00 | 0.00 | 7030555.92 | 0.00 | 45262691.82 | 0.439948E+10 | 0.00 | 0.32 |
May | 0.227516E+10 | 0.00 | 0.00 | 26070173.07 | 0.00 | 0.00 | 0.147398E+11 | 0.00 | 0.62 |
June | 0.141366E+10 | 5094632.61 | 0.00 | 34077643.95 | 0.00 | 0.00 | 0.137494E+11 | 0.00 | 0.84 |
July | 0.156001E+10 | 40222698.85 | 0.00 | 31669788.18 | 8131177.75 | 0.00 | 0.101857E+11 | 0.00 | 0.78 |
August | 0.147934E+10 | 184233.30 | 0.00 | 32174418.27 | 0.00 | 0.00 | 0.136238E+11 | 0.00 | 0.71 |
September | 0.479823E+10 | 0.00 | 0.00 | 11563605.98 | 0.00 | 0.00 | 0.714653E+10 | 0.00 | 0.38 |
October | 0.718645E+10 | 0.00 | 0.00 | 543636.68 | 0.00 | 0.380368E+09 | 0.604832E+09 | 0.00 | 0.28 |
November | 0.836387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452401E+10 | 0.00 | 0.00 | 0.27 |
December | 0.890628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670814E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.639857E+11 | 45501564.76 | 0.00 | 0.143130E+09 | 8131177.75 | 0.226413E+11 | 0.644496E+11 | 0.00 | 0.44 |
Minimum of Months | 0.141366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.890628E+10 | 40222698.85 | 0.00 | 34077643.95 | 8131177.75 | 0.670814E+10 | 0.147398E+11 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.998948E+10 | 0.00 | 0.00 | 0.25 |
February | 0.236110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657652E+10 | 0.00 | 0.00 | 0.26 |
March | 0.530180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315198E+10 | 0.00 | 0.00 | 0.29 |
April | 0.609239E+10 | 0.00 | 0.00 | 3261141.80 | 0.00 | 0.404125E+09 | 0.240161E+10 | 0.00 | 0.30 |
May | 0.317477E+10 | 0.00 | 0.00 | 20822322.37 | 0.00 | 0.00 | 0.123256E+11 | 0.00 | 0.58 |
June | 0.150149E+10 | 10328623.76 | 0.00 | 31140663.90 | 0.00 | 0.00 | 0.129804E+11 | 0.00 | 0.82 |
July | 0.169979E+10 | 36428038.61 | 0.00 | 28178854.73 | 10606083.99 | 0.00 | 0.926610E+10 | 0.00 | 0.76 |
August | 0.204571E+10 | 470752.00 | 0.00 | 25045387.05 | 0.00 | 0.00 | 0.111355E+11 | 0.00 | 0.66 |
September | 0.592149E+10 | 0.00 | 0.00 | 4376195.28 | 0.00 | 54885367.78 | 0.343790E+10 | 0.00 | 0.33 |
October | 0.511652E+10 | 0.00 | 0.00 | 303.61 | 0.00 | 0.185262E+10 | 9607596.30 | 0.00 | 0.27 |
November | 0.167720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936399E+10 | 0.00 | 0.00 | 0.25 |
December | 0.818597E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124210E+11 | 0.00 | 0.00 | 0.24 |
Annual Sum or Average | 0.369129E+11 | 47227414.37 | 0.00 | 0.112825E+09 | 10606083.99 | 0.438146E+11 | 0.515568E+11 | 0.00 | 0.42 |
Minimum of Months | 0.818597E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.609239E+10 | 36428038.61 | 0.00 | 31140663.90 | 10606083.99 | 0.124210E+11 | 0.129804E+11 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17734456.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449386E+10 | 0.00 | 0.00 | 0.43 |
February | 18378788.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317692E+10 | 0.00 | 0.00 | 0.39 |
March | 0.211079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218157E+10 | 0.00 | 0.00 | 0.36 |
April | 0.138653E+10 | 0.00 | 0.00 | 189880.53 | 0.00 | 0.482665E+09 | 0.163928E+09 | 0.00 | 0.33 |
May | 0.102368E+10 | 0.00 | 0.00 | 4117995.42 | 0.00 | 2750449.41 | 0.246704E+10 | 0.00 | 0.63 |
June | 0.274968E+09 | 3820240.08 | 0.00 | 10016966.19 | 0.00 | 0.00 | 0.387268E+10 | 0.00 | 1.15 |
July | 0.374518E+09 | 11386877.79 | 0.00 | 8429534.26 | 2453509.30 | 0.00 | 0.257359E+10 | 0.00 | 1.03 |
August | 0.757063E+09 | 121032.88 | 0.00 | 4990084.48 | 0.00 | 5638775.46 | 0.218032E+10 | 0.00 | 0.73 |
September | 0.163609E+10 | 0.00 | 0.00 | 170511.15 | 0.00 | 0.254566E+09 | 0.200883E+09 | 0.00 | 0.35 |
October | 0.376123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138824E+10 | 0.00 | 0.00 | 0.33 |
November | 13937672.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412017E+10 | 0.00 | 0.00 | 0.41 |
December | 21550853.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543314E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.611165E+10 | 15328150.76 | 0.00 | 27914972.03 | 2453509.30 | 0.215395E+11 | 0.114584E+11 | 0.00 | 0.55 |
Minimum of Months | 13937672.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.163609E+10 | 11386877.79 | 0.00 | 10016966.19 | 2453509.30 | 0.543314E+10 | 0.387268E+10 | 0.00 | 1.15 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 10211310.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293015E+10 | 0.00 | 0.00 | 0.43 |
February | 35220263.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184139E+10 | 0.00 | 0.00 | 0.36 |
March | 0.389053E+09 | 0.00 | 0.00 | 116880.73 | 0.00 | 0.931495E+09 | 46021942.76 | 0.00 | 0.32 |
April | 0.496630E+09 | 0.00 | 0.00 | 2382162.71 | 0.00 | 0.158209E+09 | 0.110474E+10 | 0.00 | 0.43 |
May | 0.287137E+09 | 0.00 | 0.00 | 9709686.84 | 0.00 | 71697.78 | 0.483405E+10 | 0.00 | 1.39 |
June | 0.116660E+09 | 3018328.40 | 0.00 | 11559273.71 | 0.00 | 0.00 | 0.467833E+10 | 0.00 | 1.92 |
July | 0.131114E+09 | 8778567.58 | 0.00 | 11430632.23 | 1343306.51 | 0.00 | 0.339538E+10 | 0.00 | 1.83 |
August | 0.237080E+09 | 84430.43 | 0.00 | 8011950.73 | 0.00 | 464616.54 | 0.341013E+10 | 0.00 | 1.31 |
September | 0.692167E+09 | 0.00 | 0.00 | 1508092.99 | 0.00 | 73251043.13 | 0.776436E+09 | 0.00 | 0.39 |
October | 0.325208E+09 | 0.00 | 0.00 | 38141.31 | 0.00 | 0.696938E+09 | 11399080.21 | 0.00 | 0.30 |
November | 8015932.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265323E+10 | 0.00 | 0.00 | 0.41 |
December | 12390486.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358854E+10 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.274089E+10 | 11881326.42 | 0.00 | 44756821.25 | 1343306.51 | 0.128737E+11 | 0.182565E+11 | 0.00 | 0.80 |
Minimum of Months | 8015932.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.692167E+09 | 8778567.58 | 0.00 | 11559273.71 | 1343306.51 | 0.358854E+10 | 0.483405E+10 | 0.00 | 1.92 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 70321433.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402257E+10 | 0.00 | 0.00 | 0.39 |
February | 0.289406E+09 | 0.00 | 0.00 | 197530.59 | 0.00 | 0.232480E+10 | 73800573.86 | 0.00 | 0.33 |
March | 0.516883E+09 | 0.00 | 0.00 | 2575723.37 | 0.00 | 0.122740E+10 | 0.976800E+09 | 0.00 | 0.41 |
April | 0.551726E+09 | 0.00 | 0.00 | 8813124.58 | 0.00 | 0.218742E+09 | 0.430310E+10 | 0.00 | 0.72 |
May | 0.622766E+09 | 0.00 | 0.00 | 13281495.81 | 0.00 | 2566736.81 | 0.673971E+10 | 0.00 | 1.37 |
June | 0.310788E+09 | 5675852.63 | 0.00 | 14457080.13 | 0.00 | 0.00 | 0.563166E+10 | 0.00 | 1.74 |
July | 0.343042E+09 | 22088673.63 | 0.00 | 14588277.54 | 1499509.09 | 0.00 | 0.377557E+10 | 0.00 | 1.61 |
August | 0.457906E+09 | 163512.21 | 0.00 | 13407695.00 | 0.00 | 2782393.29 | 0.515348E+10 | 0.00 | 1.49 |
September | 0.906089E+09 | 0.00 | 0.00 | 5339890.03 | 0.00 | 0.110486E+09 | 0.268264E+10 | 0.00 | 0.59 |
October | 0.536004E+09 | 0.00 | 0.00 | 1062860.21 | 0.00 | 0.846162E+09 | 0.496192E+09 | 0.00 | 0.34 |
November | 0.118141E+09 | 0.00 | 0.00 | 12944.60 | 0.00 | 0.345708E+10 | 8429336.28 | 0.00 | 0.36 |
December | 19580897.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517419E+10 | 0.00 | 0.00 | 0.43 |
Annual Sum or Average | 0.474265E+10 | 27928038.46 | 0.00 | 73736621.86 | 1499509.09 | 0.173868E+11 | 0.298414E+11 | 0.00 | 0.82 |
Minimum of Months | 19580897.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.906089E+09 | 22088673.63 | 0.00 | 14588277.54 | 1499509.09 | 0.517419E+10 | 0.673971E+10 | 0.00 | 1.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 10235863.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298257E+10 | 0.00 | 0.00 | 0.44 |
February | 30178903.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200640E+10 | 0.00 | 0.00 | 0.38 |
March | 0.249083E+09 | 0.00 | 0.00 | 8714.89 | 0.00 | 0.120474E+10 | 13548389.43 | 0.00 | 0.34 |
April | 0.524218E+09 | 0.00 | 0.00 | 2572764.37 | 0.00 | 0.214681E+09 | 0.138379E+10 | 0.00 | 0.51 |
May | 0.448900E+09 | 0.00 | 0.00 | 5561979.01 | 0.00 | 3022747.53 | 0.279709E+10 | 0.00 | 0.98 |
June | 0.180000E+09 | 3897590.13 | 0.00 | 8452433.03 | 0.00 | 0.00 | 0.298738E+10 | 0.00 | 1.56 |
July | 0.225322E+09 | 14884987.02 | 0.00 | 6937928.22 | 615195.76 | 0.00 | 0.182597E+10 | 0.00 | 1.32 |
August | 0.359966E+09 | 127754.77 | 0.00 | 5354672.79 | 0.00 | 3779069.63 | 0.200032E+10 | 0.00 | 1.06 |
September | 0.767220E+09 | 0.00 | 0.00 | 999334.09 | 0.00 | 0.119188E+09 | 0.593202E+09 | 0.00 | 0.39 |
October | 0.262895E+09 | 0.00 | 0.00 | 5914.96 | 0.00 | 0.786055E+09 | 6207153.30 | 0.00 | 0.31 |
November | 10185193.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266815E+10 | 0.00 | 0.00 | 0.41 |
December | 12412805.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359976E+10 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.308062E+10 | 18910331.92 | 0.00 | 29893741.37 | 615195.76 | 0.135883E+11 | 0.116075E+11 | 0.00 | 0.68 |
Minimum of Months | 10185193.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.767220E+09 | 14884987.02 | 0.00 | 8452433.03 | 615195.76 | 0.359976E+10 | 0.298738E+10 | 0.00 | 1.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 36406921.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426284E+10 | 0.00 | 0.00 | 0.39 |
February | 37364019.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331953E+10 | 0.00 | 0.00 | 0.38 |
March | 0.108355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247839E+10 | 0.00 | 0.00 | 0.35 |
April | 0.131097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.699678E+09 | 0.00 | 0.00 | 0.27 |
May | 0.152050E+10 | 0.00 | 0.00 | 1428287.61 | 0.00 | 0.00 | 0.932947E+09 | 0.00 | 0.42 |
June | 0.294423E+09 | 1064204.00 | 0.00 | 7028271.97 | 0.00 | 0.00 | 0.269677E+10 | 0.00 | 0.83 |
July | 0.311433E+09 | 9820280.50 | 0.00 | 6977294.03 | 1365101.19 | 0.00 | 0.210545E+10 | 0.00 | 0.83 |
August | 0.622263E+09 | 28034.27 | 0.00 | 4900397.83 | 0.00 | 0.00 | 0.210426E+10 | 0.00 | 0.65 |
September | 0.177310E+10 | 0.00 | 0.00 | 321003.40 | 0.00 | 48346164.06 | 0.262439E+09 | 0.00 | 0.28 |
October | 0.830449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106379E+10 | 0.00 | 0.00 | 0.28 |
November | 22914238.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360284E+10 | 0.00 | 0.00 | 0.34 |
December | 48612060.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495943E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.691678E+10 | 10912518.77 | 0.00 | 20655254.83 | 1365101.19 | 0.204348E+11 | 0.810187E+10 | 0.00 | 0.45 |
Minimum of Months | 22914238.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.177310E+10 | 9820280.50 | 0.00 | 7028271.97 | 1365101.19 | 0.495943E+10 | 0.269677E+10 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 22603177.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298444E+10 | 0.00 | 0.00 | 0.43 |
February | 45833621.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215320E+10 | 0.00 | 0.00 | 0.38 |
March | 0.410261E+09 | 0.00 | 0.00 | 21530.70 | 0.00 | 0.112536E+10 | 11151032.29 | 0.00 | 0.32 |
April | 0.714877E+09 | 0.00 | 0.00 | 1472264.74 | 0.00 | 0.195299E+09 | 0.635994E+09 | 0.00 | 0.32 |
May | 0.295919E+09 | 0.00 | 0.00 | 7617343.25 | 0.00 | 0.00 | 0.372598E+10 | 0.00 | 1.09 |
June | 0.116519E+09 | 1357924.21 | 0.00 | 9497152.28 | 0.00 | 0.00 | 0.379047E+10 | 0.00 | 1.59 |
July | 0.121559E+09 | 10066599.07 | 0.00 | 10166611.32 | 779320.24 | 0.00 | 0.294916E+10 | 0.00 | 1.62 |
August | 0.160600E+09 | 23357.02 | 0.00 | 8363729.66 | 0.00 | 0.00 | 0.341404E+10 | 0.00 | 1.27 |
September | 0.739184E+09 | 0.00 | 0.00 | 2356688.15 | 0.00 | 12986121.80 | 0.100983E+10 | 0.00 | 0.38 |
October | 0.611820E+09 | 0.00 | 0.00 | 86050.91 | 0.00 | 0.552818E+09 | 37516413.34 | 0.00 | 0.28 |
November | 15075496.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240572E+10 | 0.00 | 0.00 | 0.35 |
December | 30491693.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340143E+10 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.328474E+10 | 11447880.30 | 0.00 | 39581371.01 | 779320.24 | 0.128313E+11 | 0.155741E+11 | 0.00 | 0.71 |
Minimum of Months | 15075496.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.739184E+09 | 10066599.07 | 0.00 | 10166611.32 | 779320.24 | 0.340143E+10 | 0.379047E+10 | 0.00 | 1.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 35228907.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.793502E+10 | 0.00 | 0.00 | 0.72 |
February | 0.144234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511197E+10 | 0.00 | 0.00 | 0.60 |
March | 0.380300E+09 | 0.00 | 0.00 | 542.18 | 0.00 | 0.345730E+10 | 2729141.45 | 0.00 | 0.50 |
April | 0.951010E+09 | 0.00 | 0.00 | 2227706.73 | 0.00 | 0.103272E+10 | 0.113480E+10 | 0.00 | 0.44 |
May | 0.109925E+10 | 0.00 | 0.00 | 5134874.86 | 0.00 | 0.330686E+09 | 0.262741E+10 | 0.00 | 0.77 |
June | 0.532022E+09 | 2344354.56 | 0.00 | 8229723.06 | 0.00 | 84703010.12 | 0.298857E+10 | 0.00 | 1.11 |
July | 0.507360E+09 | 21719400.35 | 0.00 | 10108599.42 | 582228.08 | 71599335.46 | 0.228075E+10 | 0.00 | 1.20 |
August | 0.637781E+09 | 49207.40 | 0.00 | 9208727.04 | 0.00 | 0.171350E+09 | 0.327217E+10 | 0.00 | 1.16 |
September | 0.115793E+10 | 0.00 | 0.00 | 2802463.39 | 0.00 | 0.724057E+09 | 0.135232E+10 | 0.00 | 0.45 |
October | 0.552873E+09 | 0.00 | 0.00 | 305757.25 | 0.00 | 0.215673E+10 | 0.193578E+09 | 0.00 | 0.43 |
November | 47833851.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716716E+10 | 0.00 | 0.00 | 0.66 |
December | 42572887.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.998148E+10 | 0.00 | 0.00 | 0.75 |
Annual Sum or Average | 0.608839E+10 | 24112962.31 | 0.00 | 38018393.93 | 582228.08 | 0.382248E+11 | 0.138523E+11 | 0.00 | 0.73 |
Minimum of Months | 35228907.05 | 0.00 | 0.00 | 0.00 | 0.00 | 71599335.46 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.115793E+10 | 21719400.35 | 0.00 | 10108599.42 | 582228.08 | 0.998148E+10 | 0.327217E+10 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 22867981.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303510E+10 | 0.00 | 0.00 | 0.43 |
February | 33613643.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232280E+10 | 0.00 | 0.00 | 0.40 |
March | 0.195750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145748E+10 | 0.00 | 0.00 | 0.34 |
April | 0.772665E+09 | 0.00 | 0.00 | 1313989.44 | 0.00 | 0.216981E+09 | 0.604809E+09 | 0.00 | 0.34 |
May | 0.589056E+09 | 0.00 | 0.00 | 3129393.67 | 0.00 | 0.00 | 0.162972E+10 | 0.00 | 0.66 |
June | 0.183988E+09 | 792937.89 | 0.00 | 6413168.06 | 0.00 | 0.00 | 0.226802E+10 | 0.00 | 1.20 |
July | 0.214992E+09 | 12777526.92 | 0.00 | 5782815.16 | 721340.06 | 0.00 | 0.155133E+10 | 0.00 | 1.09 |
August | 0.287974E+09 | 30816.50 | 0.00 | 5393468.42 | 0.00 | 0.00 | 0.201991E+10 | 0.00 | 0.98 |
September | 0.882716E+09 | 0.00 | 0.00 | 1195271.25 | 0.00 | 21547615.59 | 0.584692E+09 | 0.00 | 0.33 |
October | 0.559568E+09 | 0.00 | 0.00 | 4652.27 | 0.00 | 0.631934E+09 | 5978705.74 | 0.00 | 0.28 |
November | 19088773.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241035E+10 | 0.00 | 0.00 | 0.35 |
December | 30507074.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341262E+10 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.379279E+10 | 13601281.31 | 0.00 | 23232758.27 | 721340.06 | 0.135088E+11 | 0.866446E+10 | 0.00 | 0.57 |
Minimum of Months | 19088773.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.882716E+09 | 12777526.92 | 0.00 | 6413168.06 | 721340.06 | 0.341262E+10 | 0.226802E+10 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 23480371.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403410E+10 | 0.00 | 0.00 | 0.36 |
February | 65954451.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291430E+10 | 0.00 | 0.00 | 0.34 |
March | 0.415788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187847E+10 | 0.00 | 0.00 | 0.32 |
April | 0.140796E+10 | 0.00 | 0.00 | 446497.48 | 0.00 | 0.310200E+09 | 0.362922E+09 | 0.00 | 0.31 |
May | 0.667059E+09 | 0.00 | 0.00 | 5593333.54 | 0.00 | 0.00 | 0.308095E+10 | 0.00 | 0.67 |
June | 0.228558E+09 | 1692381.97 | 0.00 | 11028450.96 | 0.00 | 0.00 | 0.411050E+10 | 0.00 | 1.17 |
July | 0.278427E+09 | 12519679.70 | 0.00 | 9455415.15 | 1714214.10 | 0.00 | 0.283909E+10 | 0.00 | 1.04 |
August | 0.517494E+09 | 47332.37 | 0.00 | 6452664.20 | 0.00 | 0.00 | 0.270774E+10 | 0.00 | 0.78 |
September | 0.161956E+10 | 0.00 | 0.00 | 720986.12 | 0.00 | 57848778.64 | 0.567213E+09 | 0.00 | 0.34 |
October | 0.716404E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106594E+10 | 0.00 | 0.00 | 0.29 |
November | 20291022.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359591E+10 | 0.00 | 0.00 | 0.34 |
December | 29622949.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474492E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.599059E+10 | 14259394.05 | 0.00 | 33697347.45 | 1714214.10 | 0.186017E+11 | 0.136684E+11 | 0.00 | 0.53 |
Minimum of Months | 20291022.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.161956E+10 | 12519679.70 | 0.00 | 11028450.96 | 1714214.10 | 0.474492E+10 | 0.411050E+10 | 0.00 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 18471887.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260684E+10 | 0.00 | 0.00 | 0.36 |
February | 92097636.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162224E+10 | 0.00 | 0.00 | 0.30 |
March | 0.433898E+09 | 0.00 | 0.00 | 276556.43 | 0.00 | 0.760408E+09 | 94689941.16 | 0.00 | 0.27 |
April | 0.503993E+09 | 0.00 | 0.00 | 2957804.73 | 0.00 | 0.105996E+09 | 0.139988E+10 | 0.00 | 0.45 |
May | 0.242214E+09 | 0.00 | 0.00 | 10148532.31 | 0.00 | 0.00 | 0.498700E+10 | 0.00 | 1.39 |
June | 0.113178E+09 | 1577207.63 | 0.00 | 11671224.54 | 0.00 | 0.00 | 0.455103E+10 | 0.00 | 1.84 |
July | 0.121528E+09 | 9947997.90 | 0.00 | 11565214.27 | 1038817.72 | 0.00 | 0.336275E+10 | 0.00 | 1.75 |
August | 0.180986E+09 | 33186.99 | 0.00 | 8663181.21 | 0.00 | 0.00 | 0.359776E+10 | 0.00 | 1.30 |
September | 0.649803E+09 | 0.00 | 0.00 | 2237549.99 | 0.00 | 22973821.33 | 0.110406E+10 | 0.00 | 0.41 |
October | 0.401579E+09 | 0.00 | 0.00 | 116437.88 | 0.00 | 0.517273E+09 | 56598643.96 | 0.00 | 0.25 |
November | 17689208.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229336E+10 | 0.00 | 0.00 | 0.33 |
December | 21093605.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314285E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.279653E+10 | 11558392.52 | 0.00 | 47636501.37 | 1038817.72 | 0.110719E+11 | 0.191538E+11 | 0.00 | 0.76 |
Minimum of Months | 17689208.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.649803E+09 | 9947997.90 | 0.00 | 11671224.54 | 1038817.72 | 0.314285E+10 | 0.498700E+10 | 0.00 | 1.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143920E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361028E+10 | 0.00 | 0.00 | 0.34 |
February | 0.479615E+09 | 0.00 | 0.00 | 453409.54 | 0.00 | 0.211496E+10 | 0.153263E+09 | 0.00 | 0.33 |
March | 0.774111E+09 | 0.00 | 0.00 | 3633166.84 | 0.00 | 0.102221E+10 | 0.121093E+10 | 0.00 | 0.43 |
April | 0.714003E+09 | 0.00 | 0.00 | 10147253.27 | 0.00 | 0.138696E+09 | 0.486605E+10 | 0.00 | 0.81 |
May | 0.562414E+09 | 0.00 | 0.00 | 14097326.04 | 0.00 | 0.00 | 0.695780E+10 | 0.00 | 1.42 |
June | 0.286469E+09 | 3648179.06 | 0.00 | 15032018.94 | 0.00 | 0.00 | 0.563407E+10 | 0.00 | 1.74 |
July | 0.317666E+09 | 25457067.43 | 0.00 | 15164020.56 | 1084573.35 | 0.00 | 0.380119E+10 | 0.00 | 1.60 |
August | 0.384459E+09 | 62675.07 | 0.00 | 14921879.34 | 0.00 | 0.00 | 0.544114E+10 | 0.00 | 1.53 |
September | 0.100548E+10 | 0.00 | 0.00 | 6882845.17 | 0.00 | 32045991.64 | 0.351712E+10 | 0.00 | 0.70 |
October | 0.829311E+09 | 0.00 | 0.00 | 1613328.18 | 0.00 | 0.697555E+09 | 0.698208E+09 | 0.00 | 0.35 |
November | 0.230923E+09 | 0.00 | 0.00 | 78800.01 | 0.00 | 0.312180E+10 | 25255675.74 | 0.00 | 0.32 |
December | 31821327.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454606E+10 | 0.00 | 0.00 | 0.36 |
Annual Sum or Average | 0.576020E+10 | 29167921.56 | 0.00 | 82024047.91 | 1084573.35 | 0.152836E+11 | 0.323050E+11 | 0.00 | 0.83 |
Minimum of Months | 31821327.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.100548E+10 | 25457067.43 | 0.00 | 15164020.56 | 1084573.35 | 0.454606E+10 | 0.695780E+10 | 0.00 | 1.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 16272337.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268107E+10 | 0.00 | 0.00 | 0.38 |
February | 73483710.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185841E+10 | 0.00 | 0.00 | 0.34 |
March | 0.384709E+09 | 0.00 | 0.00 | 89969.83 | 0.00 | 0.105197E+10 | 33739303.16 | 0.00 | 0.32 |
April | 0.634297E+09 | 0.00 | 0.00 | 2997417.48 | 0.00 | 0.133665E+09 | 0.156102E+10 | 0.00 | 0.54 |
May | 0.368002E+09 | 0.00 | 0.00 | 6194231.44 | 0.00 | 0.00 | 0.305873E+10 | 0.00 | 1.04 |
June | 0.167490E+09 | 1106841.17 | 0.00 | 8879434.80 | 0.00 | 0.00 | 0.304615E+10 | 0.00 | 1.57 |
July | 0.201441E+09 | 15288724.69 | 0.00 | 7339956.80 | 715170.40 | 0.00 | 0.192420E+10 | 0.00 | 1.32 |
August | 0.307824E+09 | 48249.98 | 0.00 | 6154970.39 | 0.00 | 0.00 | 0.225967E+10 | 0.00 | 1.10 |
September | 0.847599E+09 | 0.00 | 0.00 | 1538257.05 | 0.00 | 32197759.90 | 0.922991E+09 | 0.00 | 0.44 |
October | 0.482353E+09 | 0.00 | 0.00 | 12526.85 | 0.00 | 0.640856E+09 | 12796298.97 | 0.00 | 0.29 |
November | 19315349.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234480E+10 | 0.00 | 0.00 | 0.35 |
December | 19972273.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316422E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.352276E+10 | 16443815.85 | 0.00 | 33206764.63 | 715170.40 | 0.119072E+11 | 0.128193E+11 | 0.00 | 0.67 |
Minimum of Months | 16272337.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.847599E+09 | 15288724.69 | 0.00 | 8879434.80 | 715170.40 | 0.316422E+10 | 0.305873E+10 | 0.00 | 1.57 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.973390E+10 | 0.227804E+11 | 0.00 | 0.188193E+12 | 0.126242E+11 |
February | 0.455989E+11 | 0.185245E+11 | 0.00 | 0.163236E+12 | 0.758672E+10 |
March | 0.204716E+12 | 0.246480E+11 | 0.00 | 0.194093E+12 | 0.291660E+10 |
April | 0.350839E+12 | 0.218101E+11 | 0.00 | 0.207528E+12 | 0.380487E+10 |
May | 0.426999E+12 | 0.132644E+11 | 0.00 | 0.267287E+12 | 0.172419E+11 |
June | 0.436370E+12 | 0.735033E+10 | 0.00 | 0.236099E+12 | 0.746127E+11 |
July | 0.396487E+12 | 0.567827E+10 | 0.00 | 0.242220E+12 | 0.101938E+12 |
August | 0.299834E+12 | 0.786223E+10 | 0.00 | 0.245070E+12 | 0.564475E+11 |
September | 0.145606E+12 | 0.105209E+11 | 0.00 | 0.229052E+12 | 0.620000E+10 |
October | 0.650378E+11 | 0.201068E+11 | 0.00 | 0.186461E+12 | 0.991441E+09 |
November | 0.572413E+10 | 0.154509E+11 | 0.00 | 0.190930E+12 | 0.111363E+11 |
December | -0.188594E+11 | 0.196712E+11 | 0.00 | 0.198019E+12 | 0.166304E+11 |
Annual Sum or Average | 0.234862E+13 | 0.187668E+12 | 0.00 | 0.254819E+13 | 0.312131E+12 |
Minimum of Months | -0.188594E+11 | 0.567827E+10 | 0.00 | 0.163236E+12 | 0.991441E+09 |
Maximum of Months | 0.436370E+12 | 0.246480E+11 | 0.00 | 0.267287E+12 | 0.101938E+12 |