Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2023-10-16 08:32:05
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1754.24 | 352.10 | 352.10 |
Net Site Energy | 1754.24 | 352.10 | 352.10 |
Total Source Energy | 4920.33 | 987.59 | 987.59 |
Net Source Energy | 4920.33 | 987.59 | 987.59 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 139.61 | 174.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 214.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 232.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 94.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 130.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1449.23 | 305.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 139.61 | 174.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 214.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 232.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 50.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 94.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 130.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 139.61 | 174.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 214.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 232.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 50.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 94.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 130.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 90.03 | 61.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 290.88 | 61.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 90.03 | 61.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 290.88 | 61.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1449.229 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1449.229 | 100.00 |
Total On-Site and Utility Electric Sources | 1449.229 | 100.00 |
Total Electricity End Uses | 1449.229 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 238.83 |
Time Setpoint Not Met During Occupied Cooling | 118.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2605.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.6636 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.6636 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.6636 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 6.6636 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.6636 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 06-FEB-08:20 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 204171.65 | 90234.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8334.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 243.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7067.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 9406.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 246609.27 | 99641.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 204171.65 | 90234.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 8334.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 243.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7067.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 9406.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 442.14 | 189.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 679.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 737.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 160.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 37.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 298.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 141.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4589.71 | 330.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 88.74 | 38.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 136.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 59.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 28.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 921.22 | 66.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 88.74 | 38.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 136.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 59.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 28.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 921.22 | 66.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.75 | 0.272234 | 0.231000 | 0.635939 | 0.725956 | 0.500000 | 0.001400 |
CORE_MID VAV BOX COMPONENT | 2.01 | 0.372040 | 0.316000 | 0.636565 | 0.992106 | 0.500000 | 0.001024 |
CORE_TOP VAV BOX COMPONENT | 2.16 | 0.347074 | 0.295000 | 0.637009 | 0.925530 | 0.500000 | 0.001098 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.700780 | 0.225451 | 0.192000 | 0.134550 | 0.601203 | 0.500000 | 0.001690 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.764229 | 0.130879 | 0.111000 | 0.084829 | 0.349011 | 0.500000 | 0.002911 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.950880 | 0.166153 | 0.141000 | 0.134074 | 0.443075 | 0.500000 | 0.002293 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.831802 | 0.120239 | 0.102000 | 0.084844 | 0.320638 | 0.500000 | 0.003169 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.554712 | 0.284817 | 0.242000 | 0.134240 | 0.759513 | 0.500000 | 0.001338 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.632758 | 0.158073 | 0.134000 | 0.084790 | 0.421527 | 0.500000 | 0.002410 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.767247 | 0.205920 | 0.175000 | 0.134268 | 0.549121 | 0.500000 | 0.001850 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.652522 | 0.153275 | 0.130000 | 0.084828 | 0.408733 | 0.500000 | 0.002486 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.608611 | 0.259594 | 0.221000 | 0.134503 | 0.692250 | 0.500000 | 0.001468 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.740112 | 0.360385 | 0.500000 | 0.002819 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.857859 | 0.184170 | 0.157000 | 0.134684 | 0.491119 | 0.500000 | 0.002069 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.764192 | 0.130877 | 0.111000 | 0.084825 | 0.349005 | 0.500000 | 0.002911 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 21229.63 |
CORE_MID VAV BOX REHEAT COIL | 23550.01 |
CORE_TOP VAV BOX REHEAT COIL | 39516.35 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 19832.10 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12898.28 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 19684.39 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12987.52 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 14468.01 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 9467.44 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 14348.44 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9546.22 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 15730.77 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 10275.26 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 15595.49 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 10355.48 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.68 | 1.07 | 5.36 | 1.86 | 4.82 | 4.82 | 0.300000 | 0.385448 | 4.82 |
PACU_VAV_MID | 2.49 | 1.08 | 4.99 | 2.26 | 4.28 | 4.28 | 0.300000 | 0.528326 | 4.28 |
PACU_VAV_TOP | 2.70 | 1.08 | 5.41 | 3.14 | 4.96 | 4.96 | 0.300000 | 0.633023 | 4.96 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.82 |
PACU_VAV_MID_OA_CONTROLLER | 4.28 |
PACU_VAV_TOP_OA_CONTROLLER | 4.96 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.82 | 102282.10 | 0.753737 | 1.61 | 34090.62 | 0.753737 |
PACU_VAV_MID COOLING COIL | 4.28 | 93858.77 | 0.741598 | 1.43 | 31283.13 | 0.741598 |
PACU_VAV_TOP COOLING COIL | 4.96 | 105317.16 | 0.753906 | 1.65 | 35102.21 | 0.753906 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 23488.46 |
PACU_VAV_MID HEATING COIL | 24871.56 |
PACU_VAV_TOP HEATING COIL | 23827.83 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.82 |
PACU_VAV_MID FAN | 4.28 |
PACU_VAV_TOP FAN | 4.96 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 31.498 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.8668 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.8532 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.101 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2365 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2366 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9196 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9381 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6745 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.151 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.150 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.29350128E-12 | 0.14024199E-14 | -0.85558835E-13 | 0.14795563E-15 |
43 | 6 | 0.27596652E-07 | 0.24107488E-09 | 0.63308017E-08 | -0.12943591E-12 |
44 | 5 | -0.18463709E-03 | 0.20772830E-05 | -0.95040309E-04 | 0.62615177E-08 |
45 | 4 | 0.28572581 | 0.10171039E-02 | 0.97375121E-01 | -0.32667087E-04 |
46 | 3 | -7.1391205 | 0.31676816E-01 | -2.3011695 | 0.28385744E-01 |
47 | 2 | 40.451560 | 0.11313072 | 15.110175 | -0.32866754 |
48 | 1 | -80.224209 | 0.51250674E-01 | -29.002757 | 1.0717664 |
49 | 0 | 46.824341 | 0.10349526E-02 | 16.294583 | |
50 | 7 | -0.29575366E-12 | 0.13916748E-14 | -0.86470795E-13 | 0.14800413E-15 |
51 | 6 | 0.27759747E-07 | 0.23770535E-09 | 0.63667993E-08 | -0.13030888E-12 |
52 | 5 | -0.18546937E-03 | 0.20460315E-05 | -0.95457978E-04 | 0.62966404E-08 |
53 | 4 | 0.28670590 | 0.10008406E-02 | 0.97727300E-01 | -0.32804728E-04 |
54 | 3 | -7.1585449 | 0.31143840E-01 | -2.3069324 | 0.28480895E-01 |
55 | 2 | 40.515639 | 0.11114407 | 15.133849 | -0.32938113 |
56 | 1 | -80.273331 | 0.50317938E-01 | -29.023991 | 1.0728132 |
57 | 0 | 46.824340 | 0.10154678E-02 | 16.294067 | |
58 | 7 | -0.28281898E-12 | 0.14025464E-14 | -0.82622143E-13 | 0.19904483E-15 |
59 | 6 | 0.24787521E-07 | 0.29557932E-09 | 0.57107416E-08 | -0.11447606E-12 |
60 | 5 | -0.17017937E-03 | 0.25981591E-05 | -0.87765911E-04 | 0.56555961E-08 |
61 | 4 | 0.26851995 | 0.12946983E-02 | 0.91201294E-01 | -0.30269387E-04 |
62 | 3 | -6.7976835 | 0.40953066E-01 | -2.1999024 | 0.26714449E-01 |
63 | 2 | 39.324706 | 0.14826279 | 14.693101 | -0.31612152 |
64 | 1 | -79.359856 | 0.67961194E-01 | -28.628348 | 1.0533482 |
65 | 0 | 46.824347 | 0.13883650E-02 | 16.303898 | |
66 | 7 | -0.18778705E-08 | -0.48456698E-15 | 0.68415356E-14 | -0.90766841E-16 |
67 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
68 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
69 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
70 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
71 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
72 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
73 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
74 | 7 | -0.17777358E-08 | -0.41207670E-15 | 0.60771148E-14 | -0.79247013E-16 |
75 | 6 | 0.66205355E-05 | 0.45347915E-08 | 0.31869553E-02 | -0.26734852E-04 |
76 | 5 | -0.47643654E-03 | 0.26865296E-05 | -0.22355891 | 0.19546881E-02 |
77 | 4 | 0.10961386E-01 | 0.12229770E-03 | 4.8267865 | -0.45238458E-01 |
78 | 3 | -0.96263561E-01 | 0.97262436E-03 | -38.005829 | 0.39848146 |
79 | 2 | 0.34182167 | 0.16181264E-02 | 116.45361 | -1.4175335 |
80 | 1 | -0.49337445 | 0.49308431E-03 | -143.88945 | 2.0487464 |
81 | 0 | 0.24054552 | 0.11921404E-04 | 60.838472 | |
82 | 7 | -0.18778705E-08 | -0.48456747E-15 | 0.68415356E-14 | -0.90766840E-16 |
83 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
84 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
85 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
86 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
87 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
88 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
89 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
90 | 7 | -0.17776120E-08 | -0.41258204E-15 | 0.60425363E-14 | -0.82023253E-16 |
91 | 6 | 0.66209765E-05 | 0.45351028E-08 | 0.31869540E-02 | -0.26734841E-04 |
92 | 5 | -0.47646911E-03 | 0.26867147E-05 | -0.22355884 | 0.19546874E-02 |
93 | 4 | 0.10962140E-01 | 0.12230614E-03 | 4.8267853 | -0.45238446E-01 |
94 | 3 | -0.96270204E-01 | 0.97269154E-03 | -38.005822 | 0.39848139 |
95 | 2 | 0.34184528 | 0.16182383E-02 | 116.45360 | -1.4175333 |
96 | 1 | -0.49340854 | 0.49311848E-03 | -143.88944 | 2.0487463 |
97 | 0 | 0.24056214 | 0.11922214E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.359 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1124E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1187E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2194E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2249E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8114E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8556E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1337E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1567E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1563 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.9739E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1765 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.9275E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1119 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6836E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5658E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7130E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1124E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1190E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2194E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2251E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8115E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8575E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1335E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1565E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.7428E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9320E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2596E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5853E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.6333E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3432E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3611E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5268E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.1671E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.1914E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.7866E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.8041E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6390E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6450E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8245E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8324E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3163E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3697E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6094E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6519E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1524E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.1828E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1335E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1565E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0803E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3362E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1402E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7783E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9035E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2280E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5658E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7130E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3164E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3700E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6094E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6517E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1521E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.1813E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1337E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1567E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.4526E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7922E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9000E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4113E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.3865E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2276E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3611E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5268E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9946E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.0637E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5721E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.6477E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4945E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5233E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.8247E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.8326E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1550 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.6090E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1720 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1070 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1194 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.9373E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.2056E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.4300E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.5226E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.8067E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.0667E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.4757E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.4791E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.2519E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.2614E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4669E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.6586E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0538E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6548E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3959E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.4190E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7955E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.2056E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.4300E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2420E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6743E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.7191E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3111E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2399E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.1418E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.2615E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.4670E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1550 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.6081E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1720 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1069 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1194 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.9365E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.2051E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.4297E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.5225E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.8064E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.0666E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.4754E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.4787E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.2515E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.2609E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4667E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.6588E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0537E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6549E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3958E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4187E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7954E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.2051E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.4297E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.2419E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6741E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.7190E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3109E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.2395E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.1415E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.2610E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.4667E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 38193.81412 | 38193.81412 | 2.75298 | 2.75298 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 8338.06158 | 8338.06158 | 0.35093 | 0.42469 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 27982.99724 | 27982.99724 | 2.01445 | 2.01445 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 16644.63242 | 16644.63242 | 0.70545 | 0.70545 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 29706.13774 | 29706.13774 | 2.15935 | 2.15935 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 32.10000 | 1.41196E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 27823.94020 | 27823.94020 | 1.18372 | 1.18372 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9639.71554 | 9639.71554 | 0.70078 | 0.70078 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 32.10000 | 1.41196E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 13924.32045 | 13924.32045 | 0.59408 | 0.59408 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10512.54866 | 10512.54866 | 0.76423 | 0.76423 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 28.44933 | 1.41131E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 9055.53566 | 9055.53566 | 0.38637 | 0.38637 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13080.06571 | 13080.06571 | 0.95088 | 0.95088 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 13820.85649 | 13820.85649 | 0.58965 | 0.58965 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11442.09802 | 11442.09802 | 0.83180 | 0.83180 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 9118.04779 | 9118.04779 | 0.38904 | 0.38904 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7630.78238 | 7630.78238 | 0.55471 | 0.55471 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.41196E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 10165.37004 | 10165.37004 | 0.43339 | 0.43339 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8704.46560 | 8704.46560 | 0.63276 | 0.63276 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 28.65900 | 1.41134E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 6651.27428 | 6651.27428 | 0.28360 | 0.28360 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10554.51703 | 10554.51703 | 0.76725 | 0.76725 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 10081.62846 | 10081.62846 | 0.42981 | 0.42981 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8976.35091 | 8976.35091 | 0.65252 | 0.65252 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.06400 | 1.41178E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 6706.44691 | 6706.44691 | 0.28596 | 0.28596 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8371.98450 | 8371.98450 | 0.60861 | 0.60861 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.41196E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 11050.80228 | 11050.80228 | 0.47122 | 0.47122 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10180.96515 | 10180.96515 | 0.74011 | 0.74011 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 28.23967 | 1.41127E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 7217.74005 | 7217.74005 | 0.30780 | 0.30780 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11800.67658 | 11800.67658 | 0.85786 | 0.85786 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 31.79167 | 1.41191E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 10956.05134 | 10956.05134 | 0.46717 | 0.46717 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10512.22823 | 10512.22823 | 0.76419 | 0.76419 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 7273.92317 | 7273.92317 | 0.31020 | 0.31020 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 74635.69 | 4.81895 | 4.81895 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 27122.95 | 1.85746 | 1.85746 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 67343.47 | 4.28114 | 4.28114 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 26936.54 | 2.26183 | 2.26183 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 76587.61 | 4.96486 | 4.96486 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 27153.36 | 3.14287 | 3.14287 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 03:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.75298 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27223 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23100 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63594 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72596 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.39953E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21229.62552 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.01445 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37204 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31600 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63657 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99211 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.02408E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23550.00985 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.15935 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34707 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29500 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63701 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.92553 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09775E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 39516.35378 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70078 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22545 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19200 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13455 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60120 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.68995E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19832.09543 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76423 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13088 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11100 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48295E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34901 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.91108E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12898.27692 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95088 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16615 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14100 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13407 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44308 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.29307E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19684.39162 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83180 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12024 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10200 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48438E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32064 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.16868E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12987.51994 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.55471 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28482 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24200 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13424 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75951 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.33770E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14468.01070 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63276 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15807 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13400 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47896E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42153 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.41028E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9467.44099 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76725 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20592 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17500 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13427 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54912 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.85023E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14348.43567 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65252 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15327 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48278E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40873 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.48573E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9546.22195 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.60861 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25959 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22100 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13450 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69225 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.46768E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15730.76875 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74011 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36038 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.81921E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10275.26353 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85786 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18417 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15700 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13468 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49112 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.06874E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15595.49336 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76419 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13088 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11100 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48254E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34901 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.91113E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10355.47767 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.68011 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07407 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.36022 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.85746 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.81895 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.81895 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.38545 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.49261 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07569 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.98522 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.26183 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.28114 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.28114 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.52833 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.70352 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07531 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.40704 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.14287 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.96486 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.96486 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.63302 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.81895 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.28114 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.96486 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.81895 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.81895 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 102282.10105 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.75374 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.60615 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34090.62428 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.75374 |
152 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 23488.46435 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.81895 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.28114 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.28114 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 93858.76896 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74160 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.42690 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31283.12770 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74160 |
161 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 24871.56175 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.28114 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.96486 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.96486 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 105317.15649 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.75391 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.65479 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35102.20826 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.75391 |
170 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 23827.83136 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.96486 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 101573.70 | 346583.86 | 11.33 | 2.91 | 3.25 | 3.42 | 3.58 | 9.93 | 11.08 | 11.66 | 12.21 | 5.5710 | 4.4361 | 2.9917 | 1.2215 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 93317.71 | 318413.24 | 11.40 | 2.92 | 3.27 | 3.44 | 3.59 | 9.98 | 11.14 | 11.75 | 12.26 | 4.9493 | 3.9352 | 2.6477 | 1.0970 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 104585.48 | 356860.48 | 11.33 | 2.91 | 3.25 | 3.42 | 3.58 | 9.93 | 11.07 | 11.66 | 12.21 | 5.7397 | 4.5704 | 3.0821 | 1.2582 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.237 | 0.224 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.237 | 0.224 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.4960385484E-002 | 2.0552658134E-002 | Pass | Pass | 0.4882449473 | 0.4916568092 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1705858089 | 0.1268612538 | Pass | Pass | 0.5276590060 | 0.4988108144 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.8794567165E-002 | 5.7501979918E-002 | Pass | Pass | 0.4947396872 | 0.4865275588 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.4660775055E-002 | 5.2873119339E-002 | Pass | Pass | 0.4852375017 | 0.4831769530 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.7770166466E-002 | 2.2146476959E-002 | Pass | Pass | 2.6509350642 | 17.8751306990 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1370828944 | 0.1473564851 | Pass | Pass | 2.2994717852 | 11.4975419400 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.6848723731 | 0.5902823189 | Pass | Pass | 0.6924861676 | 0.5893325891 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6238142333 | 0.6425692903 | Pass | Pass | 0.7950046000 | 0.8457967329 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5128943956 | 0.5766488799 | Pass | Pass | 4.6941524528 | 40.9499530552 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6850441841 | 0.6738449203 | Pass | Pass | 0.7743965733 | 0.8422769482 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4330965316 | 0.3971138222 | Pass | Pass | 3.5661569518 | 26.1199960089 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3507905116 | 0.4064920896 | Pass | Pass | 10.4706798522 | 87.0860084053 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2569960660 | 0.2923228233 | Pass | Pass | 1.8493044177 | 14.0589938092 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4235989945 | 0.4320636000 | Pass | Pass | 18.2460160518 | 183.4842998007 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5232229498 | 0.4658167220 | Pass | Pass | 0.7203111482 | 0.6388420721 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4643901968 | 0.5084517866 | Pass | Pass | 1.0766697428 | 3.0167733482 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3894960026 | 0.4304555451 | Pass | Pass | 0.8472761110 | 1.3307749815 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5238134310 | 0.5220234261 | Pass | Pass | 0.8328796662 | 0.9465978905 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3567.59 | 132.02 | 0.00 | 1475.63 | 1117.03 | 6292.28 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 172.00 | 59 | |||
Feb | 49.00 | 37 | |||
Mar | 40.00 | 38 | |||
Apr | 70.00 | 48 | |||
May | 70.00 | 36 | |||
Jun | 25.00 | 15 | |||
Jul | 64.00 | 20 | |||
Aug | 2.00 | 4 | |||
Sep | 73.00 | 32 | |||
Oct | 7.00 | 8 | |||
Nov | 88.00 | 34 | |||
Dec | 62.00 | 39 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.359 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.359 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.359 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
North Total or Average | 195.79 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.062 | 0.360 | 0.396 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.14 | 0.0000 | Y | 6.78 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.06 | 0.0000 | Y | 4.28 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.80 | 0.0000 | Y | 6.69 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.85 | 0.0000 | Y | 4.24 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.08 | 0.0000 | Y | 6.76 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.02 | 0.0000 | Y | 4.27 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.77 | 0.0000 | Y | 6.68 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.81 | 0.0000 | Y | 4.24 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.14 | 0.0000 | Y | 6.78 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.06 | 0.0000 | Y | 4.28 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.80 | 0.0000 | Y | 6.69 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.85 | 0.0000 | Y | 4.24 |
Interior Lighting Total | 6.6636 | 4982.19 | 33199.39 | 232.74 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 42.43 | 42.43 | 4.49 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.64 | 63.04 | 4.82 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.64 | 46.90 | 41.51 | |
Exterior Lighting Total | 5686.19 | 50.82 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 102282.10 | 77093.85 | 25188.26 | 0.75 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 93858.77 | 69605.46 | 24253.31 | 0.74 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 105317.16 | 79399.22 | 25917.93 | 0.75 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 101573.7 | 2.91 | 9.93 | N/A | N/A | 11.33 | |
PACU_VAV_MID COOLING COIL | 93317.7 | 2.92 | 9.98 | N/A | N/A | 11.40 | |
PACU_VAV_TOP COOLING COIL | 104585.5 | 2.91 | 9.93 | N/A | N/A | 11.33 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 21229.63 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 23550.01 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 39516.35 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 19832.10 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12898.28 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 19684.39 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12987.52 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14468.01 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9467.44 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14348.44 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9546.22 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15730.77 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10275.26 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15595.49 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10355.48 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 23488.46 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 24871.56 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 23827.83 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.82 | 10548.73 | 2189.01 | 1.00 | 1.14 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.28 | 9371.45 | 2189.01 | 1.00 | 1.14 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.96 | 10868.12 | 2189.01 | 1.00 | 1.13 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 101573.70 | 2.91 | 9.93 | 11.33 | 5.5710 | 3.25 | 11.08 | 4.4361 | 3.42 | 11.66 | 2.9917 | 3.58 | 12.21 | 1.2215 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 93317.71 | 2.92 | 9.98 | 11.40 | 4.9493 | 3.27 | 11.14 | 3.9352 | 3.44 | 11.75 | 2.6477 | 3.59 | 12.26 | 1.0970 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 104585.48 | 2.91 | 9.93 | 11.33 | 5.7397 | 3.25 | 11.07 | 4.5704 | 3.42 | 11.66 | 3.0821 | 3.58 | 12.21 | 1.2582 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 38193.81 | 38193.81 | 38.83 | 2.753 | 2.753 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00882 | 26.62 | 0.01411 | 0.425 | 0.00 |
CORE_MID | 27983.00 | 27983.00 | 28.45 | 2.014 | 2.014 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 26.62 | 0.01411 | 0.425 | 0.00 |
CORE_TOP | 29706.14 | 29706.14 | 30.20 | 2.159 | 2.159 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00890 | 32.10 | 0.01412 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9639.72 | 9639.72 | 46.49 | 0.701 | 0.701 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00905 | 32.10 | 0.01412 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10512.55 | 10512.55 | 80.09 | 0.764 | 0.764 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00884 | 28.45 | 0.01411 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13080.07 | 13080.07 | 63.09 | 0.951 | 0.951 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00891 | 31.85 | 0.01412 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11442.10 | 11442.10 | 87.18 | 0.832 | 0.832 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00881 | 31.26 | 0.01412 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7630.78 | 7630.78 | 36.80 | 0.555 | 0.555 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00903 | 32.10 | 0.01412 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8704.47 | 8704.47 | 66.31 | 0.633 | 0.633 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00880 | 28.66 | 0.01411 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10554.52 | 10554.52 | 50.90 | 0.767 | 0.767 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00889 | 31.85 | 0.01412 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8976.35 | 8976.35 | 68.39 | 0.653 | 0.653 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00879 | 31.06 | 0.01412 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8371.98 | 8371.98 | 40.38 | 0.609 | 0.609 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00908 | 32.10 | 0.01412 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10180.97 | 10180.97 | 77.56 | 0.740 | 0.740 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00882 | 28.24 | 0.01411 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11800.68 | 11800.68 | 56.92 | 0.858 | 0.858 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00892 | 31.79 | 0.01412 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10512.23 | 10512.23 | 80.09 | 0.764 | 0.764 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00881 | 31.26 | 0.01412 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 8338.06 | 8338.06 | 8.48 | 0.351 | 0.425 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.425 | 0.00 |
CORE_MID | 16644.63 | 16644.63 | 16.92 | 0.705 | 0.705 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.425 | 0.00 |
CORE_TOP | 27823.94 | 27823.94 | 28.29 | 1.184 | 1.184 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 13924.32 | 13924.32 | 67.16 | 0.594 | 0.594 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00736 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9055.54 | 9055.54 | 68.99 | 0.386 | 0.386 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00735 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13820.86 | 13820.86 | 66.66 | 0.590 | 0.590 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00735 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 9118.05 | 9118.05 | 69.47 | 0.389 | 0.389 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00735 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 10165.37 | 10165.37 | 49.03 | 0.433 | 0.433 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00749 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 6651.27 | 6651.27 | 50.67 | 0.284 | 0.284 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00748 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10081.63 | 10081.63 | 48.62 | 0.430 | 0.430 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00748 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 6706.45 | 6706.45 | 51.10 | 0.286 | 0.286 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00749 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 11050.80 | 11050.80 | 53.30 | 0.471 | 0.471 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00732 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 7217.74 | 7217.74 | 54.99 | 0.308 | 0.308 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00731 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 10956.05 | 10956.05 | 52.84 | 0.467 | 0.467 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00731 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 7273.92 | 7273.92 | 55.42 | 0.310 | 0.310 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00731 | -10.70 | 0.00150 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.82 | 4.82 | 1.86 | 1.86 | 4.8189 | 1.8575 | 4.8189 | 0.3854 | 0.3000 |
PACU_VAV_MID | 4.28 | 4.28 | 2.26 | 2.26 | 4.2811 | 2.2618 | 4.2811 | 0.5283 | 0.3000 |
PACU_VAV_TOP | 4.96 | 4.96 | 3.14 | 3.14 | 4.9649 | 3.1429 | 4.9649 | 0.6330 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 21229.626 | 21229.626 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21229.63 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 8338.06 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 23550.010 | 23550.010 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23550.01 | 23550.01 | 0.705447 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 16644.63 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 39516.354 | 39516.354 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39516.35 | 39516.35 | 1.183723 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 27823.94 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 19832.095 | 19832.095 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19832.10 | 19832.10 | 0.594076 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00735938 | 47.6119 | 13924.32 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 12898.277 | 12898.277 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12898.28 | 12898.28 | 0.386371 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00734545 | 47.5232 | 9055.54 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 19684.392 | 19684.392 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19684.39 | 19684.39 | 0.589651 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00735492 | 47.5834 | 13820.86 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 12987.520 | 12987.520 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12987.52 | 12987.52 | 0.389045 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00734959 | 47.5497 | 9118.05 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 14468.011 | 14468.011 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14468.01 | 14468.01 | 0.433393 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00748585 | 48.4169 | 10165.37 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 9467.441 | 9467.441 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9467.44 | 9467.44 | 0.283600 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00748398 | 48.4050 | 6651.27 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 14348.436 | 14348.436 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14348.44 | 14348.44 | 0.429811 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00747990 | 48.3789 | 10081.63 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 9546.222 | 9546.222 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9546.22 | 9546.22 | 0.285960 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00748946 | 48.4400 | 6706.45 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 15730.769 | 15730.769 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15730.77 | 15730.77 | 0.471220 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00731771 | 47.3444 | 11050.80 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 10275.264 | 10275.264 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10275.26 | 10275.26 | 0.307798 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00730817 | 47.2838 | 7217.74 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 15595.493 | 15595.493 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15595.49 | 15595.49 | 0.467167 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00731164 | 47.3057 | 10956.05 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 10355.478 | 10355.478 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10355.48 | 10355.48 | 0.310201 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00731357 | 47.3183 | 7273.92 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 102282.101 | 77093.845 | 4.818946 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 104055.83 | 83032.53 | 4.818946 | 25.61 | 18.12 | 0.00992107 | 11.02 | 11.02 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 19.8404 | 24.00 | 0.00888187 | 47.7645 | 66292.64 | 0.00 | 105466.58 | 78274.50 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 23488.464 | 23488.464 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23488.46 | 23488.46 | 1.445684 | -0.63 | -0.98 | 0.00335804 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 66.1348 | 18.33 | 0.00691924 | 52.8754 | 15015.92 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 93858.769 | 69605.460 | 4.281136 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 95979.98 | 74659.25 | 4.281136 | 25.81 | 18.35 | 0.01012566 | 11.02 | 11.02 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 22.3329 | 24.00 | 0.00897703 | 48.2697 | 58885.58 | 0.00 | 96780.99 | 70678.72 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 24871.562 | 24871.562 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24871.56 | 24871.56 | 1.284341 | -3.21 | -3.21 | 0.00290070 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 74.4429 | 17.66 | 0.00699734 | 55.7632 | 16032.37 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 105317.156 | 79399.224 | 4.964856 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 107130.95 | 85272.88 | 4.964856 | 25.56 | 18.11 | 0.00993390 | 11.02 | 11.02 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 19.2574 | 24.00 | 0.00893518 | 48.0481 | 68274.82 | 0.00 | 108596.13 | 80616.67 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 23827.831 | 23827.831 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 03:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23827.83 | 23827.83 | 1.489457 | -0.43 | -0.72 | 0.00345226 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 64.1912 | 15.89 | 0.00712983 | 63.5770 | 16016.45 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 21229.626 | 21229.626 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21229.63 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21229.63 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 8338.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 23550.010 | 23550.010 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23550.01 | 23550.01 | 1.0000 | 0.84907261 | 0.705447 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23550.01 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 16644.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 39516.354 | 39516.354 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39516.35 | 39516.35 | 1.0000 | 1.42472354 | 1.183723 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39516.35 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 27823.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 19832.095 | 19832.095 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19832.10 | 19832.10 | 1.0000 | 0.71502683 | 0.594076 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19832.10 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00735938 | 21.00 | 0.00735938 | 47.6119 | 13924.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 12898.277 | 12898.277 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12898.28 | 12898.28 | 1.0000 | 0.46503478 | 0.386371 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12898.28 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00734545 | 21.00 | 0.00734545 | 47.5232 | 9055.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 19684.392 | 19684.392 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19684.39 | 19684.39 | 1.0000 | 0.70970152 | 0.589651 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19684.39 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00735492 | 21.00 | 0.00735492 | 47.5834 | 13820.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 12987.520 | 12987.520 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12987.52 | 12987.52 | 1.0000 | 0.46825235 | 0.389045 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12987.52 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00734959 | 21.00 | 0.00734959 | 47.5497 | 9118.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 14468.011 | 14468.011 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14468.01 | 14468.01 | 1.0000 | 0.52163000 | 0.433393 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14468.01 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00748585 | 21.00 | 0.00748585 | 48.4169 | 10165.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9467.441 | 9467.441 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9467.44 | 9467.44 | 1.0000 | 0.34133934 | 0.283600 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9467.44 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00748398 | 21.00 | 0.00748398 | 48.4050 | 6651.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 14348.436 | 14348.436 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14348.44 | 14348.44 | 1.0000 | 0.51731884 | 0.429811 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14348.44 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00747990 | 21.00 | 0.00747990 | 48.3789 | 10081.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9546.222 | 9546.222 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9546.22 | 9546.22 | 1.0000 | 0.34417971 | 0.285960 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9546.22 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00748946 | 21.00 | 0.00748946 | 48.4400 | 6706.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 15730.769 | 15730.769 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15730.77 | 15730.77 | 1.0000 | 0.56715750 | 0.471220 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15730.77 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00731771 | 21.00 | 0.00731771 | 47.3444 | 11050.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10275.264 | 10275.264 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10275.26 | 10275.26 | 1.0000 | 0.37046459 | 0.307798 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10275.26 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00730817 | 21.00 | 0.00730817 | 47.2838 | 7217.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 15595.493 | 15595.493 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15595.49 | 15595.49 | 1.0000 | 0.56228028 | 0.467167 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15595.49 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00731164 | 21.00 | 0.00731164 | 47.3057 | 10956.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10355.478 | 10355.478 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10355.48 | 10355.48 | 1.0000 | 0.37335663 | 0.310201 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10355.48 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00731357 | 21.00 | 0.00731357 | 47.3183 | 7273.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 102282.101 | 77093.845 | 4.818946 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2828 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.818946 | 5.80005899 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 104055.83 | 83032.53 | 1.0173 | 5.80005899 | 4.818946 | 25.61 | 18.12 | 0.00992107 | 51014.0 | 11.02 | 11.02 | 0.00850000 | 32508.2 | -999.0 | -999.00 | -999.00 | -999.00 | 10548.725 | 93507.10 | 32.10 | 0.01411964 | 23.13 | 0.95610000 | 19.8404 | 24.00 | 0.00888187 | 24.00 | 0.00888187 | 47.7645 | 66292.64 | 0.00 | 105466.58 | 78274.50 | 5.57100050 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.92 | 12.91 | 0.00927093 | 36391.0 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23488.464 | 23488.464 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.818946 | 5.80005899 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23488.46 | 23488.46 | 1.0000 | 1.74001770 | 1.445684 | -0.63 | -0.98 | 0.00335804 | 7757.5 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23488.46 | -10.70 | 0.00150390 | -10.70 | 0.95610000 | 66.1348 | 19.02 | 0.00697895 | 18.33 | 0.00691924 | 52.8754 | 15015.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 93858.769 | 69605.460 | 4.281136 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6631 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.281136 | 5.15275338 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 95979.98 | 74659.25 | 1.0226 | 5.15275338 | 4.281136 | 25.81 | 18.35 | 0.01012566 | 51742.2 | 11.02 | 11.02 | 0.00850000 | 32508.8 | -999.0 | -999.00 | -999.00 | -999.00 | 9371.453 | 86608.52 | 32.10 | 0.01411964 | 23.13 | 0.95610000 | 22.3329 | 24.00 | 0.00897703 | 24.00 | 0.00897703 | 48.2697 | 58885.58 | 0.00 | 96780.99 | 70678.72 | 4.94925857 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.69 | 12.67 | 0.00911685 | 35767.7 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24871.562 | 24871.562 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.281136 | 5.15275338 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24871.56 | 24871.56 | 1.0000 | 1.54582601 | 1.284341 | -3.21 | -3.21 | 0.00290070 | 4009.9 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24871.56 | -10.70 | 0.00150390 | -10.70 | 0.95610000 | 74.4429 | 18.60 | 0.00696931 | 17.66 | 0.00699734 | 55.7632 | 16032.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 105317.156 | 79399.224 | 4.964856 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.3066 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.964856 | 5.97567540 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 107130.95 | 85272.88 | 1.0172 | 5.97567540 | 4.964856 | 25.56 | 18.11 | 0.00993390 | 50998.7 | 11.02 | 11.02 | 0.00850000 | 32508.2 | -999.0 | -999.00 | -999.00 | -999.00 | 10868.124 | 96262.83 | 32.10 | 0.01411964 | 23.13 | 0.95610000 | 19.2574 | 24.00 | 0.00893518 | 24.00 | 0.00893518 | 48.0481 | 68274.82 | 0.00 | 108596.13 | 80616.67 | 5.73968139 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.92 | 12.91 | 0.00927338 | 36402.2 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23827.831 | 23827.831 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.964856 | 5.97567540 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 03:20:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23827.83 | 23827.83 | 1.0000 | 1.79270262 | 1.489457 | -0.43 | -0.72 | 0.00345226 | 8201.8 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23827.83 | -10.70 | 0.00150390 | -10.70 | 0.95610000 | 64.1912 | 17.99 | 0.00694491 | 15.89 | 0.00712983 | 63.5770 | 16016.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.82 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.28 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.96 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2509.67 | 2483.33 | 59.67 |
CORE_MID | 2553.17 | 3126.67 | 484.00 |
CORE_TOP | 3084.17 | 3372.83 | 1182.67 |
PERIMETER_TOP_ZN_3 | 3879.33 | 3771.50 | 2175.17 |
PERIMETER_TOP_ZN_2 | 3893.50 | 3550.17 | 1931.67 |
PERIMETER_TOP_ZN_1 | 3655.17 | 3312.17 | 1605.17 |
PERIMETER_TOP_ZN_4 | 3903.00 | 3580.33 | 1997.50 |
PERIMETER_BOT_ZN_3 | 3586.67 | 3715.67 | 1821.67 |
PERIMETER_BOT_ZN_2 | 3537.67 | 3324.83 | 1421.33 |
PERIMETER_BOT_ZN_1 | 3304.33 | 3579.50 | 1427.00 |
PERIMETER_BOT_ZN_4 | 3621.83 | 3372.17 | 1524.33 |
PERIMETER_MID_ZN_3 | 3588.50 | 3545.00 | 1730.17 |
PERIMETER_MID_ZN_2 | 3085.50 | 2925.17 | 1389.50 |
PERIMETER_MID_ZN_1 | 3410.67 | 3069.50 | 1193.67 |
PERIMETER_MID_ZN_4 | 3646.00 | 3363.33 | 1577.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4974.00 | 4324.50 | 2605.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 1.67 | 0.67 | 1.67 | 0.00 |
CORE_MID | 3.00 | 0.00 | 2.50 | 0.00 |
CORE_TOP | 4.17 | 0.00 | 3.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 58.17 | 7.00 | 24.83 | 6.17 |
PERIMETER_TOP_ZN_2 | 41.67 | 38.00 | 7.67 | 37.00 |
PERIMETER_TOP_ZN_1 | 30.17 | 32.33 | 6.67 | 30.50 |
PERIMETER_TOP_ZN_4 | 41.83 | 33.50 | 10.33 | 23.83 |
PERIMETER_BOT_ZN_3 | 17.67 | 0.00 | 11.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6.83 | 20.83 | 1.17 | 20.83 |
PERIMETER_BOT_ZN_1 | 223.33 | 34.00 | 218.17 | 33.67 |
PERIMETER_BOT_ZN_4 | 7.83 | 19.50 | 2.17 | 14.50 |
PERIMETER_MID_ZN_3 | 20.83 | 1.17 | 9.33 | 1.17 |
PERIMETER_MID_ZN_2 | 13.17 | 32.67 | 2.50 | 32.33 |
PERIMETER_MID_ZN_1 | 10.17 | 28.83 | 2.00 | 28.50 |
PERIMETER_MID_ZN_4 | 14.00 | 28.33 | 3.50 | 20.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 281.17 | 135.00 | 238.83 | 118.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.84 | 52.94 | 2698.04 | 0.800 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.84 | 52.94 | 2698.04 | 0.576 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.84 | 52.94 | 2698.04 | 0.567 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.652 | 0.106 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.892 | 0.112 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.965 | 0.107 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.902 | 0.112 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.558 | 0.057 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.790 | 0.060 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.812 | 0.864 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.774 | 0.060 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.644 | 0.089 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.818 | 0.100 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.971 | 0.089 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.890 | 0.093 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.56 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.30 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 12604410.83 | 0.00 | 12604410.83 | 0.00 | 12604410.83 | 13393058.27 | 5182.76 | 562.25 | 3014.99 | 27.26 |
CORE_MID | 9099797.59 | 0.00 | 9099797.59 | 0.00 | 9099797.59 | 13393058.27 | 5703.36 | 1052.74 | 2003.90 | 55.76 |
CORE_TOP | 8964370.76 | 0.00 | 8964370.76 | 0.00 | 8964370.76 | 13393058.27 | 5761.79 | 982.47 | 2015.74 | 48.12 |
PERIMETER_TOP_ZN_3 | 2171466.99 | 0.00 | 2171466.99 | 696839.46 | 2868306.45 | 2823374.22 | 4606.96 | 836.86 | 3316.17 | 48.12 |
PERIMETER_TOP_ZN_2 | 1877916.11 | 0.00 | 1877916.11 | 464556.85 | 2342472.96 | 1787429.43 | 4610.57 | 1030.87 | 3118.56 | 48.07 |
PERIMETER_TOP_ZN_1 | 3211237.96 | 0.00 | 3211237.96 | 696839.46 | 3908077.42 | 2823374.22 | 4473.86 | 1026.98 | 3259.15 | 48.12 |
PERIMETER_TOP_ZN_4 | 1902090.56 | 0.00 | 1902090.56 | 464556.85 | 2366647.41 | 1787312.18 | 4562.90 | 1020.92 | 3176.18 | 48.07 |
PERIMETER_BOT_ZN_3 | 1858739.47 | 0.00 | 1858739.47 | 370505.73 | 2229245.20 | 2823374.22 | 6193.36 | 550.37 | 2016.27 | 27.26 |
PERIMETER_BOT_ZN_2 | 1662944.92 | 0.00 | 1662944.92 | 247002.33 | 1909947.25 | 1787429.43 | 5410.06 | 600.80 | 2749.14 | 27.26 |
PERIMETER_BOT_ZN_1 | 2704907.94 | 0.00 | 2704907.94 | 3064686.73 | 5769594.68 | 2823374.22 | 5179.83 | 504.49 | 3075.68 | 27.26 |
PERIMETER_BOT_ZN_4 | 1629174.72 | 0.00 | 1629174.72 | 247002.33 | 1876177.05 | 1787312.18 | 5435.55 | 608.39 | 2716.06 | 27.26 |
PERIMETER_MID_ZN_3 | 2146781.93 | 0.00 | 2146781.93 | 580065.25 | 2726847.17 | 2823374.22 | 4709.84 | 919.70 | 3130.46 | 55.76 |
PERIMETER_MID_ZN_2 | 1728359.31 | 0.00 | 1728359.31 | 386707.84 | 2115067.15 | 1601953.02 | 4442.98 | 744.41 | 3572.61 | 964.76 |
PERIMETER_MID_ZN_1 | 3229071.96 | 0.00 | 3229071.96 | 580065.25 | 3809137.21 | 2823374.22 | 4365.58 | 762.98 | 3631.44 | 55.76 |
PERIMETER_MID_ZN_4 | 1875352.90 | 0.00 | 1875352.90 | 386707.84 | 2262060.74 | 1787312.18 | 4607.75 | 1088.96 | 3063.29 | 55.76 |
Total Facility | 56666623.96 | 0.00 | 56666623.96 | 8185535.92 | 64852159.88 | 67658168.57 | 6728.44 | 1636.14 | 4297.78 | 1005.88 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.5879 | 0.0000 | 0.5879 | 0.0000 | 0.5879 | 0.4247 | 2374.80 | 562.25 | 3005.95 |
CORE_MID | 0.4237 | 0.0000 | 0.4237 | 0.0000 | 0.4237 | 0.4247 | 2898.10 | 1052.74 | 1992.16 |
CORE_TOP | 0.4174 | 0.0000 | 0.4174 | 0.0000 | 0.4174 | 0.4247 | 2958.96 | 982.47 | 2001.57 |
PERIMETER_TOP_ZN_3 | 0.1011 | 0.0000 | 0.1011 | 0.0166 | 0.1177 | 0.0895 | 1804.13 | 836.86 | 3302.01 |
PERIMETER_TOP_ZN_2 | 0.0876 | 0.0000 | 0.0876 | 0.0111 | 0.0986 | 0.0567 | 1807.74 | 1030.87 | 3104.39 |
PERIMETER_TOP_ZN_1 | 0.1497 | 0.0000 | 0.1497 | 0.0166 | 0.1663 | 0.0895 | 1671.03 | 1026.98 | 3244.99 |
PERIMETER_TOP_ZN_4 | 0.0886 | 0.0000 | 0.0886 | 0.0111 | 0.0996 | 0.0567 | 1760.07 | 1020.92 | 3162.01 |
PERIMETER_BOT_ZN_3 | 0.0866 | 0.0000 | 0.0866 | 0.0088 | 0.0954 | 0.0895 | 3385.40 | 550.37 | 2007.23 |
PERIMETER_BOT_ZN_2 | 0.0776 | 0.0000 | 0.0776 | 0.0059 | 0.0834 | 0.0567 | 2602.12 | 600.80 | 2740.08 |
PERIMETER_BOT_ZN_1 | 0.1262 | 0.0000 | 0.1262 | 0.1348 | 0.2609 | 0.0895 | 2371.87 | 504.49 | 3066.64 |
PERIMETER_BOT_ZN_4 | 0.0759 | 0.0000 | 0.0759 | 0.0059 | 0.0818 | 0.0567 | 2627.66 | 608.39 | 2706.96 |
PERIMETER_MID_ZN_3 | 0.1000 | 0.0000 | 0.1000 | 0.0138 | 0.1138 | 0.0895 | 1904.58 | 919.70 | 3118.72 |
PERIMETER_MID_ZN_2 | 0.0803 | 0.0000 | 0.0803 | 0.0098 | 0.0901 | 0.0567 | 1637.71 | 744.41 | 2651.88 |
PERIMETER_MID_ZN_1 | 0.1506 | 0.0000 | 0.1506 | 0.0138 | 0.1644 | 0.0895 | 1560.31 | 762.98 | 3619.71 |
PERIMETER_MID_ZN_4 | 0.0874 | 0.0000 | 0.0874 | 0.0092 | 0.0966 | 0.0567 | 1802.48 | 1088.96 | 3051.56 |
Total Facility | 2.6403 | 0.0000 | 2.6403 | 0.2573 | 2.8976 | 2.1513 | 3916.83 | 1636.14 | 4279.39 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 29639425.91 | 0.00 | 29639425.91 | 22614548.33 | 4211.13 | 2.14 | 4546.73 | 27.26 |
PACU_VAV_MID | 26190505.74 | 0.00 | 26190505.74 | 22429071.92 | 4196.77 | 4.78 | 4558.45 | 55.76 |
PACU_VAV_TOP | 26259565.95 | 0.00 | 26259565.95 | 22614548.33 | 4216.34 | 1.51 | 4542.15 | 47.76 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.3822 | 0.0000 | 1.3822 | 0.7171 | 1403.17 | 2.14 | 4537.69 |
PACU_VAV_MID | 1.2199 | 0.0000 | 1.2199 | 0.7084 | 1391.50 | 4.78 | 4546.71 |
PACU_VAV_TOP | 1.2232 | 0.0000 | 1.2232 | 0.7171 | 1413.50 | 1.51 | 4527.98 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 305.23 | 1832.06 | 0.00 | 0.00 | 0.00 | 2553.12 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 91.01 | 1821.30 | 0.00 | 0.00 | 0.00 | 2825.87 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 56.59 | 1812.84 | 0.00 | 0.00 | 0.00 | 2867.14 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.3369 | 2.7235 | 0.0000 | 0.0000 | 0.0000 | 1.1328 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.2912 | 2.3048 | 0.0000 | 0.0000 | 0.0000 | 1.0853 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.2182 | 2.2997 | 0.0000 | 0.0000 | 0.0000 | 1.0959 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 943 |
Defaulted Fields | 546 |
Fields with Defaults | 2233 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1449.23 | 12319.79 | 30-APR-17:20 | 246609.27 | 02-JAN-07:10 |
Electricity:Building | 938.17 | 12146.72 | 16-APR-17:20 | 69450.14 | 03-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 291.77 | 4006.86 | 01-JAN-00:10 | 23121.21 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 938.17 | 12146.72 | 16-APR-17:20 | 69450.14 | 03-JAN-08:10 |
InteriorLights:Electricity | 232.74 | 905.38 | 16-APR-17:20 | 25003.79 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 232.74 | 905.38 | 16-APR-17:20 | 25003.79 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 232.74 | 905.38 | 16-APR-17:20 | 25003.79 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 232.74 | 905.38 | 16-APR-17:20 | 25003.79 | 02-JAN-16:40 |
Electricity:Zone:CORE_MID | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 31.11 | 413.68 | 02-APR-17:10 | 2475.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.78 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.78 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.68 | 261.88 | 09-APR-17:10 | 1567.33 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.28 | 17.46 | 01-JAN-07:50 | 658.76 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.28 | 17.46 | 01-JAN-07:50 | 658.76 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 31.02 | 413.67 | 19-MAR-17:10 | 2475.79 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.69 | 27.57 | 01-JAN-07:50 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.69 | 27.57 | 01-JAN-07:50 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.65 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.24 | 17.46 | 01-JAN-08:40 | 658.71 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.24 | 17.46 | 01-JAN-08:40 | 658.71 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 31.10 | 413.68 | 02-APR-17:10 | 2475.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.76 | 27.57 | 01-JAN-08:40 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.76 | 27.57 | 01-JAN-08:40 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.68 | 261.88 | 09-APR-17:10 | 1567.33 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.27 | 17.46 | 01-JAN-07:50 | 658.76 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.27 | 17.46 | 01-JAN-07:50 | 658.76 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 31.01 | 413.67 | 19-MAR-17:10 | 2475.79 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.68 | 27.57 | 01-JAN-07:50 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.68 | 27.57 | 01-JAN-07:50 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.64 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.24 | 17.46 | 01-JAN-08:40 | 658.71 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.24 | 17.46 | 01-JAN-08:40 | 658.71 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 31.11 | 413.68 | 02-APR-17:10 | 2475.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.78 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.78 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.68 | 261.88 | 09-APR-17:10 | 1567.33 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.28 | 17.46 | 01-JAN-07:50 | 658.76 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.28 | 17.46 | 01-JAN-07:50 | 658.76 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 31.02 | 413.67 | 19-MAR-17:10 | 2475.79 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.69 | 27.57 | 01-JAN-07:50 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.69 | 27.57 | 01-JAN-07:50 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.65 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.24 | 17.46 | 01-JAN-08:40 | 658.71 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.24 | 17.46 | 01-JAN-08:40 | 658.71 | 02-JAN-16:40 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 460.09 | 168.57 | 30-APR-17:30 | 212351.12 | 02-JAN-06:20 |
ExteriorEquipment:Electricity | 11.69 | 168.34 | 01-JAN-00:10 | 838.79 | 02-JAN-16:50 |
Transformer:ExteriorEquipment:Electricity | 11.69 | 168.34 | 01-JAN-00:10 | 838.79 | 02-JAN-16:50 |
ElectricityPurchased:Facility | 1449.23 | 12319.79 | 30-APR-17:20 | 246609.27 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 1449.23 | 12319.79 | 30-APR-17:20 | 246609.27 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1449.23 | 12319.79 | 30-APR-17:20 | 246609.27 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1449.23 | 12319.79 | 30-APR-17:20 | 246609.27 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1449.23 | 12319.79 | 30-APR-17:20 | 246609.27 | 02-JAN-07:10 |
ElectricityNet:Plant | 1449.23 | 12319.79 | 30-APR-17:20 | 246609.27 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 1449.23 | 12319.79 | 30-APR-17:20 | 246609.27 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1449.23 | 12319.79 | 30-APR-17:20 | 246609.27 | 02-JAN-07:10 |
Heating:Electricity | 139.61 | 0.00 | 01-JAN-00:40 | 204974.91 | 02-JAN-06:20 |
General:Heating:Electricity | 139.61 | 0.00 | 01-JAN-00:40 | 204974.91 | 02-JAN-06:20 |
Fans:Electricity | 94.15 | 0.00 | 01-JAN-00:40 | 27138.14 | 10-JUL-15:30 |
General:Fans:Electricity | 94.15 | 0.00 | 01-JAN-00:40 | 27138.14 | 10-JUL-15:30 |
ExteriorLights:Electricity | 50.82 | 0.00 | 01-JAN-07:30 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 50.82 | 0.00 | 01-JAN-07:30 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 214.64 | 0.00 | 01-JAN-00:10 | 81560.05 | 19-JUN-12:10 |
General:Cooling:Electricity | 214.64 | 0.00 | 01-JAN-00:10 | 81560.05 | 19-JUN-12:10 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-12:20 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-12:20 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-12:20 |
WIRED_LTG_ELECTRICITY | 6.54 | 0.00 | 01-JAN-00:10 | 702.61 | 02-JAN-16:50 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 305.01 | 1886.44 | 13-JAN-06:20 | 99641.29 | 06-FEB-08:20 |
NaturalGas:HVAC | 174.74 | 0.00 | 01-JAN-00:40 | 90234.82 | 06-FEB-07:50 |
Heating:NaturalGas | 174.74 | 0.00 | 01-JAN-00:40 | 90234.82 | 06-FEB-07:50 |
General:Heating:NaturalGas | 174.74 | 0.00 | 01-JAN-00:40 | 90234.82 | 06-FEB-07:50 |
NaturalGas:Plant | 130.27 | 1886.44 | 02-JAN-18:20 | 10203.36 | 06-FEB-12:10 |
WaterSystems:NaturalGas | 130.27 | 1886.44 | 02-JAN-18:20 | 10203.36 | 06-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 130.27 | 1886.44 | 02-JAN-18:20 | 10203.36 | 06-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2295.19 | 0.00 | 01-JAN-00:40 | 468930.91 | 02-JAN-07:10 |
EnergyTransfer:Building | 1099.45 | 0.00 | 01-JAN-00:40 | 207739.33 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 218.27 | 0.00 | 01-JAN-00:40 | 28344.45 | 05-SEP-07:20 |
Heating:EnergyTransfer | 126.42 | 0.00 | 01-JAN-00:40 | 207739.33 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.37 | 0.00 | 01-JAN-00:10 | 16923.87 | 02-JAN-07:00 |
General:Heating:EnergyTransfer | 126.42 | 0.00 | 01-JAN-00:40 | 207739.33 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.37 | 0.00 | 01-JAN-00:10 | 16923.87 | 02-JAN-07:00 |
Cooling:EnergyTransfer | 973.03 | 0.00 | 01-JAN-00:40 | 170873.18 | 14-AUG-14:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 217.90 | 0.00 | 01-JAN-00:40 | 28344.45 | 05-SEP-07:20 |
General:Cooling:EnergyTransfer | 973.03 | 0.00 | 01-JAN-00:40 | 170873.18 | 14-AUG-14:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 217.90 | 0.00 | 01-JAN-00:40 | 28344.45 | 05-SEP-07:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 49.76 | 0.00 | 01-JAN-00:40 | 15937.95 | 06-FEB-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 18.08 | 0.00 | 01-JAN-00:40 | 15937.95 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 18.08 | 0.00 | 01-JAN-00:40 | 15937.95 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 31.68 | 0.00 | 01-JAN-00:10 | 12254.78 | 19-JUN-13:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 31.68 | 0.00 | 01-JAN-00:10 | 12254.78 | 19-JUN-13:40 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 27.32 | 0.00 | 01-JAN-00:40 | 10055.58 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 9.73 | 0.00 | 01-JAN-00:40 | 10055.58 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 9.73 | 0.00 | 01-JAN-00:40 | 10055.58 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 17.59 | 0.00 | 01-JAN-00:10 | 5729.42 | 14-AUG-14:40 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 17.59 | 0.00 | 01-JAN-00:10 | 5729.42 | 14-AUG-14:40 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 29.18 | 0.00 | 01-JAN-00:40 | 8424.37 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 7.37 | 0.00 | 01-JAN-00:40 | 8424.37 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 7.37 | 0.00 | 01-JAN-00:40 | 8424.37 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 21.81 | 0.00 | 01-JAN-00:10 | 5820.03 | 14-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 21.81 | 0.00 | 01-JAN-00:10 | 5820.03 | 14-AUG-15:50 |
EnergyTransfer:Zone:CORE_MID | 144.21 | 0.00 | 01-JAN-00:40 | 20378.55 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 1.35 | 0.00 | 01-JAN-00:40 | 20378.55 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 1.35 | 0.00 | 01-JAN-00:40 | 20378.55 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 142.86 | 0.00 | 01-JAN-00:20 | 19394.83 | 05-SEP-07:40 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 142.86 | 0.00 | 01-JAN-00:20 | 19394.83 | 05-SEP-07:40 |
EnergyTransfer:Zone:CORE_TOP | 140.06 | 0.00 | 01-JAN-00:40 | 28489.80 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 6.70 | 0.00 | 01-JAN-00:40 | 28489.80 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 6.70 | 0.00 | 01-JAN-00:40 | 28489.80 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 133.35 | 0.00 | 01-JAN-00:20 | 20813.09 | 14-AUG-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 133.35 | 0.00 | 01-JAN-00:20 | 20813.09 | 14-AUG-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 44.41 | 0.00 | 01-JAN-00:40 | 10175.26 | 06-FEB-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 13.64 | 0.00 | 01-JAN-00:40 | 10175.26 | 06-FEB-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 13.64 | 0.00 | 01-JAN-00:40 | 10175.26 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.77 | 0.00 | 01-JAN-00:10 | 7931.10 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.77 | 0.00 | 01-JAN-00:10 | 7931.10 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 36.53 | 0.00 | 01-JAN-00:40 | 9487.98 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 7.13 | 0.00 | 01-JAN-00:40 | 9487.98 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 7.13 | 0.00 | 01-JAN-00:40 | 9487.98 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 29.40 | 0.00 | 01-JAN-00:10 | 9434.19 | 26-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 29.40 | 0.00 | 01-JAN-00:10 | 9434.19 | 26-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 59.02 | 0.00 | 01-JAN-00:40 | 13281.53 | 28-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 8.81 | 0.00 | 01-JAN-00:40 | 12472.57 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 8.81 | 0.00 | 01-JAN-00:40 | 12472.57 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 50.20 | 0.00 | 01-JAN-00:10 | 13281.53 | 28-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 50.20 | 0.00 | 01-JAN-00:10 | 13281.53 | 28-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 37.94 | 0.00 | 01-JAN-00:40 | 9938.18 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 8.15 | 0.00 | 01-JAN-00:40 | 9938.18 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 8.15 | 0.00 | 01-JAN-00:40 | 9938.18 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 29.79 | 0.00 | 01-JAN-00:10 | 9813.12 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 29.79 | 0.00 | 01-JAN-00:10 | 9813.12 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 33.87 | 0.00 | 01-JAN-00:40 | 7819.18 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 6.12 | 0.00 | 01-JAN-00:40 | 7819.18 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 6.12 | 0.00 | 01-JAN-00:40 | 7819.18 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 27.75 | 0.00 | 01-JAN-00:10 | 6196.39 | 10-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 27.75 | 0.00 | 01-JAN-00:10 | 6196.39 | 10-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 30.48 | 0.00 | 01-JAN-00:40 | 7866.91 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.74 | 0.00 | 01-JAN-00:40 | 7866.91 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.74 | 0.00 | 01-JAN-00:40 | 7866.91 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 27.74 | 0.00 | 01-JAN-00:20 | 7493.00 | 22-AUG-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 27.74 | 0.00 | 01-JAN-00:20 | 7493.00 | 22-AUG-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 58.00 | 0.00 | 01-JAN-00:40 | 13509.08 | 02-JAN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 15.93 | 0.00 | 01-JAN-00:40 | 13509.08 | 02-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 15.93 | 0.00 | 01-JAN-00:40 | 13509.08 | 02-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 42.07 | 0.00 | 01-JAN-00:20 | 12443.37 | 19-JUN-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 42.07 | 0.00 | 01-JAN-00:20 | 12443.37 | 19-JUN-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 30.66 | 0.00 | 01-JAN-00:40 | 8030.71 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 3.17 | 0.00 | 01-JAN-00:40 | 8030.71 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 3.17 | 0.00 | 01-JAN-00:40 | 8030.71 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 27.49 | 0.00 | 01-JAN-00:20 | 7796.30 | 21-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 27.49 | 0.00 | 01-JAN-00:20 | 7796.30 | 21-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 38.16 | 0.00 | 01-JAN-00:40 | 8567.85 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 6.39 | 0.00 | 01-JAN-00:40 | 8567.85 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 6.39 | 0.00 | 01-JAN-00:40 | 8567.85 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 31.78 | 0.00 | 01-JAN-00:10 | 7132.98 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 31.78 | 0.00 | 01-JAN-00:10 | 7132.98 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 31.77 | 0.00 | 01-JAN-00:40 | 9215.85 | 26-JUN-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 3.26 | 0.00 | 01-JAN-00:40 | 8475.27 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 3.26 | 0.00 | 01-JAN-00:40 | 8475.27 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 28.51 | 0.00 | 01-JAN-00:10 | 9215.85 | 26-JUN-08:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 28.51 | 0.00 | 01-JAN-00:10 | 9215.85 | 26-JUN-08:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 55.76 | 0.00 | 01-JAN-00:40 | 12284.73 | 28-SEP-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 3.72 | 0.00 | 01-JAN-00:40 | 10875.51 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 3.72 | 0.00 | 01-JAN-00:40 | 10875.51 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 52.03 | 0.00 | 01-JAN-00:10 | 12284.73 | 28-SEP-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 52.03 | 0.00 | 01-JAN-00:10 | 12284.73 | 28-SEP-12:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 34.04 | 0.00 | 01-JAN-00:40 | 9327.71 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 3.76 | 0.00 | 01-JAN-00:40 | 8540.59 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 3.76 | 0.00 | 01-JAN-00:40 | 8540.59 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 30.28 | 0.00 | 01-JAN-00:10 | 9327.71 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 30.28 | 0.00 | 01-JAN-00:10 | 9327.71 | 15-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 48.91 | 0.00 | 01-JAN-00:10 | 6339.48 | 07-FEB-12:10 |
PlantLoopHeatingDemand:Plant | 48.91 | 0.00 | 01-JAN-00:10 | 6339.48 | 07-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 48.91 | 0.00 | 01-JAN-00:10 | 6339.48 | 07-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 48.91 | 0.00 | 01-JAN-00:10 | 6339.48 | 07-FEB-12:10 |
EnergyTransfer:HVAC | 1146.84 | 0.00 | 01-JAN-00:40 | 284497.87 | 16-AUG-12:30 |
HeatingCoils:EnergyTransfer | 279.40 | 0.00 | 01-JAN-00:40 | 270064.24 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 867.44 | 0.00 | 01-JAN-00:10 | 284497.87 | 16-AUG-12:30 |
EnergyTransfer:Plant | 48.91 | 0.00 | 01-JAN-00:10 | 6339.48 | 07-FEB-12:10 |
WaterSystems:EnergyTransfer | 48.91 | 0.00 | 01-JAN-00:10 | 6339.48 | 07-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 48.91 | 0.00 | 01-JAN-00:10 | 6339.48 | 07-FEB-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.367 | -217.905 | 0.000 | 0.000 | 32.973 | 55.599 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -107.201 |
CORE_MID | 0.000 | 0.000 | 1.351 | -142.863 | 0.000 | 0.000 | 34.246 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -63.758 |
CORE_TOP | 0.000 | 0.000 | 6.704 | -133.354 | 0.000 | 0.000 | 34.873 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -79.248 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 13.641 | -30.773 | 0.000 | 0.000 | 7.514 | 6.780 | 24.333 | 18.838 | 0.000 | 0.137 | 0.000 | 0.000 | -27.513 | 0.000 | -9.111 | -3.845 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 7.126 | -29.404 | 0.000 | 0.000 | 4.685 | 4.279 | 15.404 | 33.411 | 0.000 | 0.088 | 0.001 | 0.000 | -17.476 | 0.000 | -6.184 | -11.929 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 8.814 | -50.200 | 0.000 | 0.000 | 7.296 | 6.690 | 24.332 | 68.085 | 0.000 | 0.133 | 0.001 | 0.000 | -26.230 | 0.000 | -9.546 | -29.374 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 8.148 | -29.792 | 0.000 | 0.000 | 4.715 | 4.244 | 15.403 | 34.028 | 0.000 | 0.088 | 0.001 | 0.000 | -18.007 | 0.000 | -6.223 | -12.605 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 6.121 | -27.748 | 0.000 | 0.000 | 7.481 | 6.765 | 24.333 | 19.099 | 0.000 | 0.081 | 0.001 | 0.000 | -28.880 | 0.000 | -5.168 | -2.084 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 2.739 | -27.744 | 0.000 | 0.000 | 4.649 | 4.272 | 15.404 | 33.539 | 0.000 | 0.049 | 0.000 | 0.000 | -18.672 | 0.000 | -3.558 | -10.677 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 15.925 | -42.071 | 0.000 | 0.000 | 7.438 | 6.682 | 24.332 | 68.728 | 0.000 | 2.025 | 0.000 | 0.000 | -28.110 | 0.000 | -35.417 | -19.533 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 3.167 | -27.492 | 0.000 | 0.000 | 4.676 | 4.237 | 15.403 | 34.222 | 0.000 | 0.049 | 0.000 | 0.000 | -19.259 | 0.000 | -3.579 | -11.423 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 6.388 | -31.777 | 0.000 | 0.000 | 7.448 | 6.780 | 24.333 | 18.658 | 0.000 | 0.117 | 5.233 | 0.000 | -29.154 | 0.000 | -8.024 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 3.263 | -28.506 | 0.000 | 0.000 | 3.425 | 4.279 | 15.404 | 33.171 | 0.000 | 0.072 | 0.000 | 0.000 | -18.505 | 0.000 | -5.455 | -7.148 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 3.724 | -52.032 | 0.000 | 0.000 | 7.218 | 6.690 | 24.332 | 67.852 | 0.000 | 0.112 | 0.000 | 0.000 | -27.785 | 0.000 | -8.417 | -21.694 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 3.763 | -30.280 | 0.000 | 0.000 | 4.669 | 4.244 | 15.403 | 33.912 | 0.000 | 0.074 | 0.001 | 0.000 | -19.077 | 0.000 | -5.478 | -7.231 |
TOPFLOOR_PLENUM | 18.081 | -31.678 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.133 | 27.447 | 0.000 | 0.000 | 0.000 | -13.983 | -0.000 |
MIDFLOOR_PLENUM | 9.729 | -17.595 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.156 | 21.608 | 0.000 | 0.000 | 0.000 | -13.898 | -0.000 |
FIRSTFLOOR_PLENUM | 7.371 | -21.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.123 | 25.680 | 0.000 | 0.000 | 0.000 | -11.369 | -0.000 |
Total Facility | 35.181 | -71.079 | 91.241 | -901.942 | 0.000 | 0.000 | 173.308 | 232.739 | 705.434 | 463.543 | 0.000 | 3.438 | 79.972 | 0.000 | -278.668 | 0.000 | -145.409 | -387.753 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 25-JUL-05:03 | 0.00 | 0.00 | 0.00 | -44979.17 | 0.00 | 0.00 | 294.92 | 211.73 | 4989.51 | 0.00 | 0.00 | 0.00 | 39483.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 19-JUN-05:03 | 0.00 | 0.00 | 0.00 | -33242.76 | 0.00 | 0.00 | 302.68 | 211.73 | 3025.92 | 0.00 | 0.00 | 0.00 | 29702.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 19-JUN-05:03 | 0.00 | 0.00 | 0.00 | -35815.29 | 0.00 | 0.00 | 302.71 | 211.73 | 3025.92 | 0.00 | 0.00 | 0.00 | 32274.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 13-AUG-15:12 | 0.00 | 0.00 | 0.00 | -11645.32 | 0.00 | 0.00 | 26.83 | 27.57 | 478.42 | 2955.54 | 0.00 | 120.40 | 8036.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-SEP-09:21 | 0.00 | 0.00 | 0.00 | -14613.41 | 0.00 | 0.00 | 13.69 | 17.46 | 302.86 | 8674.10 | 0.00 | 0.00 | 5660.75 | 0.00 | -0.00 | 0.00 | -55.44 | 0.00 |
PERIMETER_TOP_ZN_1 | 04-SEP-12:01 | 0.00 | 0.00 | 0.00 | -18524.53 | 0.00 | 0.00 | 21.15 | 27.57 | 478.41 | 13359.25 | 0.00 | 0.00 | 4736.40 | 0.00 | -0.00 | 0.00 | -98.26 | 0.00 |
PERIMETER_TOP_ZN_4 | 03-SEP-16:02 | 0.00 | 0.00 | 0.00 | -15079.20 | 0.00 | 0.00 | 14.28 | 17.46 | 302.86 | 8037.91 | 0.00 | 0.00 | 6774.37 | 0.00 | -0.00 | 0.00 | -67.67 | 0.00 |
PERIMETER_BOT_ZN_3 | 17-JUL-06:03 | 0.00 | 0.00 | 0.00 | -7605.75 | 0.00 | 0.00 | 144.49 | 165.45 | 637.89 | 2251.08 | 0.00 | 0.00 | 4414.61 | 0.00 | -0.00 | 0.00 | -7.76 | 0.00 |
PERIMETER_BOT_ZN_2 | 10-SEP-09:12 | 0.00 | 0.00 | 0.00 | -11214.68 | 0.00 | 0.00 | 16.47 | 17.46 | 302.86 | 9048.56 | 0.00 | 0.00 | 1958.81 | 0.00 | -0.00 | 0.00 | -129.47 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-SEP-13:12 | 0.00 | 0.00 | 0.00 | -13990.10 | 0.00 | 0.00 | 25.37 | 27.57 | 478.41 | 12085.68 | 0.00 | 0.00 | 1487.57 | 0.00 | -0.00 | 0.00 | -114.51 | 0.00 |
PERIMETER_BOT_ZN_4 | 10-SEP-16:31 | 0.00 | 0.00 | 0.00 | -12084.82 | 0.00 | 0.00 | 15.07 | 17.46 | 302.86 | 10045.51 | 0.00 | 0.00 | 1810.14 | 0.00 | -0.00 | 0.00 | -106.21 | 0.00 |
PERIMETER_MID_ZN_3 | 09-JUL-16:02 | 0.00 | 0.00 | 0.00 | -10109.86 | 0.00 | 0.00 | 28.37 | 27.57 | 478.42 | 2868.30 | 0.00 | 2.98 | 6704.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-09:01 | 0.00 | 0.00 | 0.00 | -14409.82 | 0.00 | 0.00 | 13.45 | 17.46 | 302.86 | 9822.41 | 0.00 | 0.00 | 4309.97 | 0.00 | -0.00 | 0.00 | -56.33 | 0.00 |
PERIMETER_MID_ZN_1 | 10-SEP-12:32 | 0.00 | 0.00 | 0.00 | -16126.24 | 0.00 | 0.00 | 23.42 | 27.57 | 478.41 | 13043.12 | 0.00 | 0.00 | 2791.27 | 0.00 | -0.00 | 0.00 | -237.56 | 0.00 |
PERIMETER_MID_ZN_4 | 10-SEP-15:51 | 0.00 | 0.00 | 0.00 | -14532.30 | 0.00 | 0.00 | 13.64 | 17.46 | 302.86 | 11128.11 | 0.00 | 0.00 | 3224.38 | 0.00 | -0.00 | 0.00 | -154.15 | 0.00 |
TOPFLOOR_PLENUM | 19-JUN-13:40 | 0.00 | -12254.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.27 | 12118.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 14-AUG-10:10 | 0.00 | -5744.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.84 | 5711.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 10-JUL-12:10 | 0.00 | -6469.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.49 | 6392.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-JUL-04:02 | 0.00 | 7587.61 | 0.00 | -210373.28 | 0.00 | 0.00 | 0.00 | 1072.56 | 14333.92 | 0.00 | 0.00 | 68.33 | 188836.76 | 0.00 | -1425.82 | 0.00 | -100.08 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 19306.50 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 4405.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23923.88 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 23262.81 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25916.60 |
CORE_TOP | 02-JAN-01:22 | 0.00 | 0.00 | 32151.43 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -34805.22 |
PERIMETER_TOP_ZN_3 | 01-JAN-22:42 | 0.00 | 0.00 | 11340.88 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2922.52 | 0.00 | -2186.35 | -6662.74 |
PERIMETER_TOP_ZN_2 | 06-FEB-00:42 | 0.00 | 0.00 | 12131.32 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2179.35 | 0.00 | -1821.01 | -8485.11 |
PERIMETER_TOP_ZN_1 | 02-JAN-01:22 | 0.00 | 0.00 | 15120.97 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2982.24 | 0.00 | -1720.59 | -10977.58 |
PERIMETER_TOP_ZN_4 | 06-FEB-00:42 | 0.00 | 0.00 | 13170.27 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2239.05 | 0.00 | -1825.51 | -9459.86 |
PERIMETER_BOT_ZN_3 | 01-JAN-22:42 | 0.00 | 0.00 | 8682.42 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2979.88 | 0.00 | -1204.18 | -4929.10 |
PERIMETER_BOT_ZN_2 | 01-JAN-22:42 | 0.00 | 0.00 | 9691.27 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1958.43 | 0.00 | -821.29 | -7184.23 |
PERIMETER_BOT_ZN_1 | 02-JAN-08:00 | 0.00 | 0.00 | 13508.91 | 0.00 | 0.00 | 0.00 | 251.07 | 165.45 | 637.88 | 1373.25 | 0.00 | 0.00 | 4871.08 | 0.00 | -0.00 | 0.00 | -20807.64 | 0.00 |
PERIMETER_BOT_ZN_4 | 01-JAN-22:42 | 0.00 | 0.00 | 9943.91 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1992.11 | 0.00 | -818.62 | -7405.84 |
PERIMETER_MID_ZN_3 | 01-JAN-20:42 | 0.00 | 0.00 | 9654.77 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2798.08 | 0.00 | -2065.05 | -5222.37 |
PERIMETER_MID_ZN_2 | 01-JAN-22:42 | 0.00 | 0.00 | 10895.92 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1944.49 | 0.00 | -1266.35 | -7957.75 |
PERIMETER_MID_ZN_1 | 01-JAN-22:42 | 0.00 | 0.00 | 13355.41 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2945.31 | 0.00 | -1897.62 | -8943.21 |
PERIMETER_MID_ZN_4 | 01-JAN-22:42 | 0.00 | 0.00 | 11011.83 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1989.15 | 0.00 | -1264.61 | -8030.74 |
TOPFLOOR_PLENUM | 06-FEB-06:06 | 16403.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -790.58 | -15613.20 |
MIDFLOOR_PLENUM | 02-JAN-07:07 | 10341.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -232.15 | -10108.91 |
FIRSTFLOOR_PLENUM | 02-JAN-07:01 | 9335.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -179.93 | -9155.83 |
Total Facility | 02-JAN-05:01 | 19568.36 | 0.00 | 200133.31 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.56 | 14333.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31806.94 | 0.00 | -9572.54 | -193728.65 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.3602 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.8189 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.9852 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.2811 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.4070 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9649 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.6801 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0741 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.4926 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0757 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.7035 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0753 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7530 | 2.7530 | 0.6359 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0144 | 2.0144 | 0.6366 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1594 | 2.1594 | 0.6370 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7008 | 0.7008 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7642 | 0.7642 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9509 | 0.9509 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8318 | 0.8318 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5547 | 0.5547 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6328 | 0.6328 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7672 | 0.7672 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6525 | 0.6525 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6086 | 0.6086 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7401 | 0.7401 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8579 | 0.8579 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7642 | 0.7642 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.3602 | 4.8189 | 5.3602 | 1.0741 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.9852 | 4.2811 | 4.9852 | 1.0757 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.4070 | 4.9649 | 5.4070 | 1.0753 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3765 | 1.3765 | 0.6359 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0072 | 1.0072 | 0.6366 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0797 | 1.0797 | 0.6370 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3504 | 0.3504 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3821 | 0.3821 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4754 | 0.4754 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4159 | 0.4159 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2774 | 0.2774 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3164 | 0.3164 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3836 | 0.3836 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3263 | 0.3263 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3043 | 0.3043 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3701 | 0.3701 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4289 | 0.4289 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3821 | 0.3821 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.6801 | 1.0741 | 1.0741 | 1.0741 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.4926 | 1.0757 | 1.0757 | 1.0757 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.7035 | 1.0753 | 1.0753 | 1.0753 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 238.83 |
Number of hours cooling loads not met | 118.33 |
Number of hours not met | 357.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 139.61 | 204974.91 | 174.74 | 90234.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 214.64 | 81560.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 232.74 | 25003.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 50.82 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.69 | 838.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 94.15 | 27138.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 130.27 | 10203.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1449.23 |
Natural Gas | 0.00 | 305.01 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1754.24 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.71 |
Space Heating | 28.02 |
Space Cooling | 43.08 |
Fans (All) | 18.90 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 290.88 |
Subtotal | 290.88 |
Natural Gas [MJ/m2] | |
Space Heating | 35.07 |
Service Water Heating | 26.15 |
Miscellaneous (All) | 61.22 |
Subtotal | 61.22 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 13.27 |
Space Heating | 17.92 |
Space Cooling | 12.24 |
Fans (All) | 5.37 |
Service Water Heating | 7.43 |
Receptacle Equipment | 40.21 |
Miscellaneous | 3.57 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 909. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8680.67 | 79.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8742.67 | 17.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8752.67 | 7.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8688.00 | 72.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8607.67 | 152.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8626.67 | 133.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8552.33 | 207.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8745.17 | 14.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8667.17 | 92.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8683.33 | 76.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8585.33 | 174.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8705.00 | 55.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8607.83 | 152.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8623.00 | 137.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8545.17 | 214.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8610.67 | 149.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8545.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 214.83 | 0.00 | 0.00 | 0.00 |
Average | 8663.43 | 96.57 | 0.00 | 0.00 | 0.00 |
Sum | 155941.67 | 1738.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128270.33 | 33.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128302.00 | 2.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128297.67 | 6.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128302.00 | 33.67 | 0.00 | 0.00 | 0.00 |
Average | 34141.00 | 2.33 | 0.00 | 0.00 | 0.00 |
Sum | 614538.00 | 42.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8002.67 | 757.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8245.17 | 514.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8359.33 | 400.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7929.67 | 830.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7888.50 | 871.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7904.67 | 855.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7862.67 | 897.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8025.67 | 734.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7900.67 | 859.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7667.00 | 1093.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7839.17 | 920.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7911.17 | 848.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7835.50 | 924.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7867.83 | 892.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7814.83 | 945.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7361.50 | 1398.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 7807.67 | 952.33 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 7836.33 | 923.67 | 0.00 | 0.00 | 0.00 |
Min | 7361.50 | 400.67 | 0.00 | 0.00 | 0.00 |
Max | 8359.33 | 1398.50 | 0.00 | 0.00 | 0.00 |
Average | 7892.22 | 867.78 | 0.00 | 0.00 | 0.00 |
Sum | 142060.00 | 15620.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127902.00 | 402.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128049.33 | 254.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128124.33 | 179.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24702.83 | 206.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 13904.83 | 111.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24723.50 | 185.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 13889.33 | 126.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24751.00 | 158.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 13944.83 | 71.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 23407.83 | 1501.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 13929.67 | 86.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24840.17 | 68.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10109.00 | 25.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24838.50 | 70.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 13947.17 | 68.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128124.33 | 1501.17 | 0.00 | 0.00 | 0.00 |
Average | 33948.02 | 195.31 | 0.00 | 0.00 | 0.00 |
Sum | 611064.33 | 3515.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.826322E+10 | 12163.72 | 27-JAN-08:30 | 2.20 | 0.28 | 0.184251E+10 | 2606.62 | 20-JAN-10:09 | 2.20 | 0.28 |
February | 0.871989E+10 | 13045.71 | 24-FEB-08:20 | 5.00 | 4.16 | 0.174238E+10 | 2606.64 | 01-FEB-10:20 | 5.00 | 4.16 |
March | 0.135244E+11 | 16665.53 | 16-MAR-07:03 | 1.78 | -1.5 | 0.213703E+10 | 2606.66 | 27-MAR-09:09 | 11.20 | 11.20 |
April | 0.156435E+11 | 33375.67 | 10-APR-06:03 | 15.78 | 13.94 | 0.190856E+10 | 2606.67 | 26-APR-09:00 | 16.10 | 12.59 |
May | 0.216415E+11 | 40832.29 | 30-MAY-05:12 | 18.53 | 14.51 | 0.207544E+10 | 2606.78 | 15-MAY-13:00 | 18.53 | 14.51 |
June | 0.254569E+11 | 44806.08 | 19-JUN-05:03 | 24.08 | 22.05 | 0.207201E+10 | 2606.66 | 22-JUN-09:20 | 25.77 | 16.91 |
July | 0.260533E+11 | 44989.83 | 25-JUL-05:03 | 23.90 | 23.41 | 0.192620E+10 | 2606.67 | 12-JUL-13:00 | 23.90 | 23.41 |
August | 0.284280E+11 | 42513.81 | 07-AUG-05:12 | 19.40 | 16.84 | 0.216229E+10 | 2606.67 | 23-AUG-13:20 | 25.60 | 17.10 |
September | 0.238496E+11 | 40829.55 | 11-SEP-05:12 | 12.03 | 8.93 | 0.191935E+10 | 2606.73 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.218716E+11 | 38577.56 | 16-OCT-06:01 | 9.18 | 8.72 | 0.199377E+10 | 2606.74 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.139588E+11 | 19258.77 | 03-NOV-16:00 | 15.00 | 10.26 | 0.195685E+10 | 2606.71 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.104941E+11 | 16755.80 | 21-DEC-08:05 | -0.5 | -3.2 | 0.188430E+10 | 2608.26 | 20-DEC-14:39 | -0.5 | -3.2 |
Annual Sum or Average | 0.217905E+12 | 0.236207E+11 | ||||||||
Minimum of Months | 0.826322E+10 | 12163.72 | -0.5 | -3.2 | 0.174238E+10 | 2606.62 | -0.5 | -3.2 | ||
Maximum of Months | 0.284280E+11 | 44989.83 | 24.08 | 23.41 | 0.216229E+10 | 2608.26 | 25.77 | 23.41 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 835397.46 | 153.94 | 17-JAN-14:50 | 10.68 | 5.08 | 0.00 | 0.00 | 01-JAN-00:10 | 10.68 | 5.08 |
February | 10071290.96 | 419.09 | 18-FEB-15:00 | 6.70 | 3.14 | 0.00 | 0.00 | 01-FEB-00:10 | 6.70 | 3.14 |
March | 0.399438E+09 | 2753.51 | 03-MAR-14:30 | 15.00 | 8.51 | 0.00 | 0.00 | 01-MAR-00:10 | 15.00 | 8.51 |
April | 0.135554E+10 | 7343.02 | 07-APR-13:05 | 26.60 | 16.32 | 0.00 | 0.00 | 01-APR-00:10 | 26.60 | 16.32 |
May | 0.327601E+10 | 10992.95 | 30-MAY-14:05 | 29.22 | 16.98 | 0.00 | 0.00 | 01-MAY-00:10 | 29.22 | 16.98 |
June | 0.577961E+10 | 12254.78 | 19-JUN-13:40 | 34.60 | 23.77 | 0.00 | 0.00 | 01-JUN-00:10 | 34.60 | 23.77 |
July | 0.715340E+10 | 11415.84 | 10-JUL-13:50 | 32.70 | 20.82 | 0.00 | 0.00 | 01-JUL-00:10 | 32.70 | 20.82 |
August | 0.773305E+10 | 10931.72 | 01-AUG-14:40 | 30.97 | 22.94 | 0.00 | 0.00 | 01-AUG-00:10 | 30.97 | 22.94 |
September | 0.380176E+10 | 9663.78 | 01-SEP-14:50 | 30.68 | 17.45 | 0.00 | 0.00 | 01-SEP-00:10 | 30.68 | 17.45 |
October | 0.200638E+10 | 6817.42 | 04-OCT-14:50 | 23.98 | 19.09 | 0.00 | 0.00 | 01-OCT-00:10 | 23.98 | 19.09 |
November | 0.162010E+09 | 2334.77 | 03-NOV-14:30 | 17.50 | 10.83 | 0.00 | 0.00 | 01-NOV-00:10 | 17.50 | 10.83 |
December | 610082.76 | 141.52 | 16-DEC-14:40 | 10.40 | 4.48 | 0.00 | 0.00 | 01-DEC-00:10 | 10.40 | 4.48 |
Annual Sum or Average | 0.316787E+11 | 0.00 | ||||||||
Minimum of Months | 610082.76 | 141.52 | 6.70 | 3.14 | 0.00 | 0.00 | 6.70 | 3.14 | ||
Maximum of Months | 0.773305E+10 | 12254.78 | 34.60 | 23.77 | 0.00 | 0.00 | 34.60 | 23.77 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3566705.68 | 2269.28 | 05-JAN-05:01 | -7.8 | -9.6 | 0.00 | 0.00 | 01-JAN-00:10 | -7.8 | -9.6 |
February | 4171580.81 | 2127.44 | 09-FEB-05:01 | -8.3 | -9.9 | 0.00 | 0.00 | 01-FEB-00:10 | -8.3 | -9.9 |
March | 77311271.81 | 1672.88 | 22-MAR-05:01 | -2.3 | -5.1 | 0.00 | 0.00 | 01-MAR-00:10 | -2.3 | -5.1 |
April | 0.441857E+09 | 2306.39 | 10-APR-15:50 | 20.00 | 11.21 | 0.00 | 0.00 | 01-APR-00:10 | 20.00 | 11.21 |
May | 0.145725E+10 | 5255.04 | 30-MAY-14:20 | 29.03 | 17.03 | 0.00 | 0.00 | 01-MAY-00:10 | 29.03 | 17.03 |
June | 0.326579E+10 | 5307.83 | 19-JUN-12:05 | 36.42 | 24.23 | 0.00 | 0.00 | 01-JUN-00:10 | 36.42 | 24.23 |
July | 0.421859E+10 | 5625.55 | 10-JUL-14:20 | 32.97 | 20.94 | 0.00 | 0.00 | 01-JUL-00:10 | 32.97 | 20.94 |
August | 0.458448E+10 | 5745.08 | 14-AUG-10:10 | 27.88 | 23.11 | 0.00 | 0.00 | 01-AUG-00:10 | 27.88 | 23.11 |
September | 0.242160E+10 | 5394.64 | 05-SEP-15:20 | 25.93 | 21.57 | 0.00 | 0.00 | 01-SEP-00:10 | 25.93 | 21.57 |
October | 0.104437E+10 | 3208.13 | 04-OCT-15:40 | 23.17 | 19.12 | 0.00 | 0.00 | 01-OCT-00:10 | 23.17 | 19.12 |
November | 72671403.80 | 1253.21 | 15-NOV-06:11 | 2.80 | 0.78 | 0.00 | 0.00 | 01-NOV-00:10 | 2.80 | 0.78 |
December | 3133519.40 | 1544.75 | 23-DEC-06:11 | 2.93 | 2.42 | 0.00 | 0.00 | 01-DEC-00:10 | 2.93 | 2.42 |
Annual Sum or Average | 0.175948E+11 | 0.00 | ||||||||
Minimum of Months | 3133519.40 | 1253.21 | -8.3 | -9.9 | 0.00 | 0.00 | -8.3 | -9.9 | ||
Maximum of Months | 0.458448E+10 | 5745.08 | 36.42 | 24.23 | 0.00 | 0.00 | 36.42 | 24.23 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9537334.44 | 1617.76 | 25-JAN-06:11 | 3.30 | 0.42 | 0.00 | 0.00 | 01-JAN-00:10 | 3.30 | 0.42 |
February | 15751957.14 | 1979.85 | 15-FEB-06:01 | -6.5 | -7.7 | 0.00 | 0.00 | 01-FEB-00:10 | -6.5 | -7.7 |
March | 0.159072E+09 | 2308.15 | 09-MAR-06:11 | 2.20 | 1.95 | 0.00 | 0.00 | 01-MAR-00:10 | 2.20 | 1.95 |
April | 0.704816E+09 | 2710.14 | 10-APR-15:50 | 20.00 | 11.21 | 0.00 | 0.00 | 01-APR-00:10 | 20.00 | 11.21 |
May | 0.190704E+10 | 5531.67 | 30-MAY-12:10 | 29.50 | 17.65 | 0.00 | 0.00 | 01-MAY-00:10 | 29.50 | 17.65 |
June | 0.371757E+10 | 6065.64 | 19-JUN-12:08 | 36.42 | 24.23 | 0.00 | 0.00 | 01-JUN-00:10 | 36.42 | 24.23 |
July | 0.463495E+10 | 6469.72 | 10-JUL-12:10 | 31.28 | 20.14 | 0.00 | 0.00 | 01-JUL-00:10 | 31.28 | 20.14 |
August | 0.520994E+10 | 5820.03 | 14-AUG-15:50 | 27.88 | 22.79 | 0.00 | 0.00 | 01-AUG-00:10 | 27.88 | 22.79 |
September | 0.323768E+10 | 5578.00 | 05-SEP-07:10 | 21.88 | 18.77 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 18.77 |
October | 0.196701E+10 | 3843.59 | 04-OCT-16:00 | 22.80 | 19.11 | 0.00 | 0.00 | 01-OCT-00:10 | 22.80 | 19.11 |
November | 0.225324E+09 | 1497.01 | 03-NOV-15:30 | 16.10 | 10.65 | 0.00 | 0.00 | 01-NOV-00:10 | 16.10 | 10.65 |
December | 17275232.06 | 1801.11 | 21-DEC-07:02 | -0.6 | -3.3 | 0.00 | 0.00 | 01-DEC-00:10 | -0.6 | -3.3 |
Annual Sum or Average | 0.218060E+11 | 0.00 | ||||||||
Minimum of Months | 9537334.44 | 1497.01 | -6.5 | -7.7 | 0.00 | 0.00 | -6.5 | -7.7 | ||
Maximum of Months | 0.520994E+10 | 6469.72 | 36.42 | 24.23 | 0.00 | 0.00 | 36.42 | 24.23 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.515431E+10 | 6066.76 | 20-JAN-17:00 | 5.60 | 3.19 | 0.157982E+10 | 2399.72 | 20-JAN-14:00 | 5.60 | 3.19 |
February | 0.547459E+10 | 6089.12 | 24-FEB-17:00 | 6.70 | 1.42 | 0.146821E+10 | 2421.50 | 24-FEB-14:00 | 6.70 | 1.42 |
March | 0.821112E+10 | 9379.01 | 29-MAR-16:00 | 7.20 | 4.88 | 0.194960E+10 | 2606.63 | 29-MAR-13:20 | 7.20 | 4.88 |
April | 0.967296E+10 | 13983.26 | 10-APR-16:00 | 20.00 | 11.13 | 0.184258E+10 | 2606.65 | 07-APR-13:20 | 20.00 | 11.13 |
May | 0.142027E+11 | 29761.18 | 30-MAY-05:12 | 18.53 | 14.51 | 0.206239E+10 | 2606.74 | 15-MAY-13:00 | 18.53 | 14.51 |
June | 0.177974E+11 | 33241.07 | 19-JUN-05:03 | 24.08 | 22.05 | 0.206834E+10 | 2606.70 | 26-JUN-09:20 | 25.37 | 19.69 |
July | 0.190930E+11 | 33149.57 | 25-JUL-05:03 | 23.90 | 23.41 | 0.192323E+10 | 2606.70 | 17-JUL-09:20 | 23.90 | 23.41 |
August | 0.203221E+11 | 32978.81 | 14-AUG-05:14 | 22.57 | 20.98 | 0.215933E+10 | 2606.68 | 02-AUG-09:20 | 22.57 | 20.98 |
September | 0.158531E+11 | 32395.93 | 05-SEP-05:14 | 20.60 | 18.00 | 0.191338E+10 | 2606.69 | 19-SEP-09:50 | 19.72 | 15.05 |
October | 0.130515E+11 | 15185.30 | 05-OCT-16:00 | 21.70 | 19.15 | 0.197744E+10 | 2606.72 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.759883E+10 | 11316.07 | 03-NOV-16:00 | 15.00 | 10.26 | 0.179151E+10 | 2606.66 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.643120E+10 | 6255.35 | 21-DEC-16:25 | 2.25 | -2.5 | 0.161185E+10 | 2493.81 | 21-DEC-14:00 | 2.25 | -2.5 |
Annual Sum or Average | 0.142863E+12 | 0.223477E+11 | ||||||||
Minimum of Months | 0.515431E+10 | 6066.76 | 2.25 | -2.5 | 0.146821E+10 | 2399.72 | 2.25 | -2.5 | ||
Maximum of Months | 0.203221E+11 | 33241.07 | 24.08 | 23.41 | 0.215933E+10 | 2606.74 | 25.37 | 23.41 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.352159E+10 | 5754.58 | 20-JAN-16:40 | 6.13 | 3.40 | 0.150956E+10 | 2306.98 | 20-JAN-16:49 | 5.87 | 3.30 |
February | 0.369293E+10 | 5835.13 | 24-FEB-16:50 | 6.88 | 1.49 | 0.139198E+10 | 2342.27 | 02-FEB-14:00 | 6.88 | 1.49 |
March | 0.707954E+10 | 9039.15 | 29-MAR-16:00 | 7.20 | 4.88 | 0.183670E+10 | 2606.63 | 29-MAR-13:20 | 7.20 | 4.88 |
April | 0.887335E+10 | 14866.84 | 10-APR-15:50 | 20.00 | 11.21 | 0.177939E+10 | 2606.66 | 07-APR-13:20 | 20.00 | 11.21 |
May | 0.139004E+11 | 31852.43 | 30-MAY-05:12 | 18.53 | 14.51 | 0.204379E+10 | 2606.74 | 15-MAY-13:00 | 18.53 | 14.51 |
June | 0.182787E+11 | 35811.57 | 19-JUN-05:03 | 24.08 | 22.05 | 0.206651E+10 | 2606.67 | 23-JUN-09:20 | 27.80 | 18.74 |
July | 0.201002E+11 | 32567.10 | 24-JUL-05:12 | 20.97 | 20.39 | 0.192353E+10 | 2606.66 | 14-JUL-09:00 | 20.97 | 20.39 |
August | 0.210151E+11 | 32991.09 | 07-AUG-05:12 | 19.40 | 16.84 | 0.215850E+10 | 2606.70 | 29-AUG-09:09 | 23.77 | 18.41 |
September | 0.151909E+11 | 32625.78 | 05-SEP-05:12 | 20.60 | 18.00 | 0.190528E+10 | 2606.68 | 11-SEP-13:09 | 20.60 | 12.01 |
October | 0.114713E+11 | 15762.57 | 04-OCT-15:40 | 23.17 | 19.12 | 0.193545E+10 | 2606.70 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.602617E+10 | 10109.87 | 03-NOV-16:00 | 15.00 | 10.26 | 0.167479E+10 | 2606.64 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.420327E+10 | 5749.39 | 21-DEC-16:25 | 2.25 | -2.5 | 0.149515E+10 | 2346.31 | 20-DEC-14:00 | 2.25 | -2.5 |
Annual Sum or Average | 0.133353E+12 | 0.217206E+11 | ||||||||
Minimum of Months | 0.352159E+10 | 5749.39 | 2.25 | -2.5 | 0.139198E+10 | 2306.98 | 2.25 | -2.5 | ||
Maximum of Months | 0.210151E+11 | 35811.57 | 24.08 | 22.05 | 0.215850E+10 | 2606.74 | 27.80 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 90919024.95 | 943.70 | 20-JAN-15:20 | 7.60 | 3.92 | 0.305050E+09 | 420.72 | 20-JAN-14:00 | 7.60 | 3.92 |
February | 0.121767E+09 | 968.31 | 17-FEB-15:50 | 6.10 | 1.74 | 0.277575E+09 | 427.53 | 17-FEB-14:00 | 6.10 | 1.74 |
March | 0.741556E+09 | 1493.23 | 27-MAR-16:00 | 22.20 | 16.34 | 0.353495E+09 | 549.48 | 28-MAR-13:00 | 13.30 | 8.41 |
April | 0.159650E+10 | 4063.82 | 07-APR-15:20 | 25.60 | 16.01 | 0.352473E+09 | 549.50 | 07-APR-13:20 | 25.60 | 16.01 |
May | 0.337790E+10 | 8302.96 | 30-MAY-06:03 | 20.47 | 15.45 | 0.424194E+09 | 549.52 | 15-MAY-13:00 | 20.47 | 15.45 |
June | 0.540991E+10 | 9542.96 | 26-JUN-06:03 | 21.97 | 17.81 | 0.435407E+09 | 549.61 | 19-JUN-13:50 | 21.97 | 17.81 |
July | 0.639251E+10 | 11071.21 | 16-JUL-14:32 | 30.40 | 21.51 | 0.406136E+09 | 549.51 | 14-JUL-09:00 | 30.40 | 21.51 |
August | 0.635867E+10 | 11645.44 | 13-AUG-15:12 | 30.40 | 20.77 | 0.454923E+09 | 549.51 | 29-AUG-09:20 | 24.23 | 18.51 |
September | 0.371395E+10 | 9607.15 | 04-SEP-13:21 | 26.10 | 18.39 | 0.397599E+09 | 549.51 | 19-SEP-09:20 | 18.87 | 14.31 |
October | 0.221298E+10 | 4187.34 | 04-OCT-13:50 | 24.50 | 18.89 | 0.390358E+09 | 549.50 | 02-OCT-13:20 | 24.50 | 18.89 |
November | 0.664816E+09 | 1508.27 | 03-NOV-14:30 | 17.50 | 10.83 | 0.324220E+09 | 549.47 | 03-NOV-13:00 | 17.50 | 10.83 |
December | 92140826.88 | 971.48 | 20-DEC-14:10 | 9.72 | 5.77 | 0.295083E+09 | 429.26 | 20-DEC-14:20 | 9.43 | 5.62 |
Annual Sum or Average | 0.307736E+11 | 0.441651E+10 | ||||||||
Minimum of Months | 90919024.95 | 943.70 | 6.10 | 1.74 | 0.277575E+09 | 420.72 | 6.10 | 1.74 | ||
Maximum of Months | 0.639251E+10 | 11645.44 | 30.40 | 21.51 | 0.454923E+09 | 549.61 | 30.40 | 21.51 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135592E+09 | 751.09 | 19-JAN-10:20 | 7.80 | 4.36 | 0.195934E+09 | 310.31 | 19-JAN-10:30 | 7.80 | 4.48 |
February | 0.211794E+09 | 777.32 | 22-FEB-10:10 | 0.87 | -3.0 | 0.180203E+09 | 320.24 | 22-FEB-10:20 | 1.13 | -2.8 |
March | 0.797694E+09 | 3432.57 | 29-MAR-09:30 | 6.15 | 3.19 | 0.244263E+09 | 347.88 | 29-MAR-13:20 | 7.80 | 5.34 |
April | 0.173078E+10 | 6243.47 | 28-APR-08:50 | 15.82 | 8.80 | 0.236651E+09 | 347.89 | 26-APR-09:00 | 15.82 | 8.80 |
May | 0.348515E+10 | 13395.78 | 29-MAY-08:52 | 26.10 | 16.72 | 0.272182E+09 | 348.41 | 30-MAY-09:00 | 27.80 | 17.82 |
June | 0.473761E+10 | 12798.22 | 25-JUN-08:52 | 25.60 | 23.63 | 0.276138E+09 | 348.40 | 26-JUN-09:00 | 26.10 | 20.11 |
July | 0.551942E+10 | 13479.37 | 02-JUL-08:32 | 25.20 | 21.54 | 0.257472E+09 | 348.93 | 14-JUL-09:00 | 30.60 | 21.74 |
August | 0.613877E+10 | 12886.38 | 13-AUG-09:12 | 28.17 | 19.21 | 0.288430E+09 | 348.48 | 02-AUG-09:00 | 28.17 | 19.21 |
September | 0.358577E+10 | 14615.27 | 04-SEP-09:21 | 24.75 | 18.34 | 0.253783E+09 | 348.58 | 06-SEP-09:50 | 26.52 | 19.55 |
October | 0.225842E+10 | 5520.14 | 05-OCT-09:20 | 19.27 | 16.99 | 0.257260E+09 | 347.89 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.597995E+09 | 1983.03 | 03-NOV-09:30 | 13.05 | 8.24 | 0.216101E+09 | 347.87 | 03-NOV-13:20 | 17.40 | 10.62 |
December | 0.205313E+09 | 782.18 | 20-DEC-10:10 | 8.40 | 5.03 | 0.189995E+09 | 320.46 | 20-DEC-10:09 | 8.40 | 5.03 |
Annual Sum or Average | 0.294043E+11 | 0.286841E+10 | ||||||||
Minimum of Months | 0.135592E+09 | 751.09 | 0.87 | -3.0 | 0.180203E+09 | 310.31 | 1.13 | -2.8 | ||
Maximum of Months | 0.613877E+10 | 14615.27 | 28.17 | 23.63 | 0.288430E+09 | 348.93 | 30.60 | 21.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.765407E+09 | 5708.20 | 19-JAN-13:25 | 9.40 | 3.94 | 0.337416E+09 | 549.50 | 30-JAN-14:30 | 2.80 | -1.1 |
February | 0.104117E+10 | 6193.77 | 02-FEB-14:00 | 5.60 | -1.0 | 0.312075E+09 | 549.50 | 17-FEB-14:09 | 6.60 | 2.15 |
March | 0.234917E+10 | 8856.51 | 03-MAR-13:30 | 14.70 | 8.33 | 0.393823E+09 | 549.51 | 23-MAR-13:00 | 5.00 | 1.08 |
April | 0.296474E+10 | 10090.31 | 07-APR-12:30 | 26.15 | 15.90 | 0.366757E+09 | 549.83 | 07-APR-13:09 | 26.60 | 16.32 |
May | 0.445792E+10 | 12933.49 | 29-MAY-12:13 | 28.33 | 17.95 | 0.425109E+09 | 550.17 | 30-MAY-13:00 | 29.40 | 16.93 |
June | 0.622902E+10 | 13089.74 | 18-JUN-14:02 | 26.10 | 22.31 | 0.435273E+09 | 549.78 | 19-JUN-13:30 | 34.70 | 23.81 |
July | 0.746598E+10 | 16406.84 | 04-JUL-12:13 | 28.13 | 19.53 | 0.406263E+09 | 550.01 | 10-JUL-13:50 | 32.70 | 20.82 |
August | 0.913335E+10 | 16634.82 | 13-AUG-12:32 | 30.93 | 19.36 | 0.455329E+09 | 550.06 | 17-AUG-13:50 | 31.10 | 24.82 |
September | 0.674788E+10 | 18524.07 | 04-SEP-12:01 | 26.10 | 17.88 | 0.400409E+09 | 560.87 | 28-SEP-13:09 | 22.98 | 13.55 |
October | 0.605269E+10 | 17393.40 | 22-OCT-12:32 | 21.83 | 16.69 | 0.407010E+09 | 550.78 | 04-OCT-13:09 | 21.83 | 16.69 |
November | 0.199781E+10 | 10728.77 | 02-NOV-13:05 | 15.68 | 8.29 | 0.362840E+09 | 549.62 | 02-NOV-13:00 | 16.10 | 8.71 |
December | 0.996088E+09 | 5914.74 | 21-DEC-13:25 | 3.05 | -1.7 | 0.332238E+09 | 549.50 | 14-DEC-14:09 | 3.05 | -1.7 |
Annual Sum or Average | 0.502012E+11 | 0.463454E+10 | ||||||||
Minimum of Months | 0.765407E+09 | 5708.20 | 3.05 | -1.7 | 0.312075E+09 | 549.50 | 2.80 | -1.7 | ||
Maximum of Months | 0.913335E+10 | 18524.07 | 30.93 | 22.31 | 0.455329E+09 | 560.87 | 34.70 | 24.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152644E+09 | 1204.50 | 20-JAN-15:40 | 7.40 | 3.86 | 0.198301E+09 | 338.68 | 20-JAN-16:30 | 6.40 | 3.51 |
February | 0.223921E+09 | 1909.40 | 24-FEB-15:30 | 8.05 | 2.04 | 0.182762E+09 | 347.82 | 17-FEB-14:00 | 8.05 | 2.04 |
March | 0.953165E+09 | 5339.32 | 29-MAR-16:00 | 7.20 | 4.88 | 0.234620E+09 | 347.84 | 28-MAR-13:20 | 7.20 | 4.88 |
April | 0.182095E+10 | 11599.57 | 09-APR-15:43 | 17.30 | 14.24 | 0.226781E+09 | 347.85 | 07-APR-13:20 | 17.30 | 14.24 |
May | 0.333462E+10 | 11481.61 | 14-MAY-16:03 | 13.30 | 9.05 | 0.269071E+09 | 347.88 | 15-MAY-13:00 | 17.80 | 11.36 |
June | 0.495361E+10 | 14889.69 | 18-JUN-16:02 | 25.50 | 22.07 | 0.275784E+09 | 347.86 | 22-JUN-13:30 | 29.15 | 17.46 |
July | 0.549804E+10 | 14880.52 | 02-JUL-16:32 | 24.60 | 20.65 | 0.257320E+09 | 347.86 | 14-JUL-09:00 | 30.60 | 21.74 |
August | 0.613210E+10 | 14593.86 | 13-AUG-15:52 | 30.00 | 20.46 | 0.288295E+09 | 347.86 | 08-AUG-13:50 | 30.00 | 20.46 |
September | 0.355435E+10 | 15078.36 | 03-SEP-16:02 | 24.90 | 16.52 | 0.252387E+09 | 347.86 | 19-SEP-09:20 | 18.87 | 14.31 |
October | 0.242714E+10 | 10525.86 | 15-OCT-15:32 | 19.80 | 12.41 | 0.249961E+09 | 347.86 | 12-OCT-13:00 | 19.80 | 12.41 |
November | 0.572054E+09 | 3624.21 | 03-NOV-15:30 | 16.10 | 10.65 | 0.210633E+09 | 347.85 | 08-NOV-14:00 | 13.30 | 11.09 |
December | 0.169791E+09 | 866.14 | 08-DEC-15:40 | 6.30 | 2.04 | 0.191774E+09 | 338.00 | 08-DEC-15:50 | 6.20 | 1.96 |
Annual Sum or Average | 0.297924E+11 | 0.283769E+10 | ||||||||
Minimum of Months | 0.152644E+09 | 866.14 | 6.30 | 2.04 | 0.182762E+09 | 338.00 | 6.20 | 1.96 | ||
Maximum of Months | 0.613210E+10 | 15078.36 | 30.00 | 22.07 | 0.288295E+09 | 347.88 | 30.60 | 21.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166985E+09 | 949.39 | 20-JAN-15:00 | 7.80 | 3.97 | 0.305928E+09 | 424.12 | 20-JAN-14:00 | 7.80 | 3.97 |
February | 0.149513E+09 | 956.90 | 24-FEB-14:10 | 9.22 | 3.12 | 0.278553E+09 | 426.14 | 24-FEB-14:30 | 8.85 | 2.78 |
March | 0.798566E+09 | 1242.77 | 28-MAR-14:00 | 13.30 | 8.41 | 0.349197E+09 | 507.38 | 28-MAR-13:00 | 13.30 | 8.41 |
April | 0.135613E+10 | 2209.13 | 10-APR-14:00 | 20.60 | 10.45 | 0.346922E+09 | 549.50 | 07-APR-13:20 | 20.60 | 10.45 |
May | 0.246777E+10 | 4553.14 | 30-MAY-14:00 | 29.40 | 16.93 | 0.420977E+09 | 549.51 | 15-MAY-13:00 | 29.40 | 16.93 |
June | 0.422514E+10 | 7569.91 | 26-JUN-06:03 | 21.97 | 17.81 | 0.435096E+09 | 549.50 | 22-JUN-09:20 | 21.97 | 17.81 |
July | 0.533585E+10 | 7606.10 | 17-JUL-06:03 | 22.48 | 19.71 | 0.405600E+09 | 549.50 | 12-JUL-13:00 | 22.48 | 19.71 |
August | 0.563324E+10 | 7571.29 | 14-AUG-06:03 | 23.48 | 21.76 | 0.455006E+09 | 549.50 | 23-AUG-13:20 | 25.60 | 17.10 |
September | 0.367557E+10 | 7006.12 | 05-SEP-06:03 | 20.78 | 18.13 | 0.401636E+09 | 549.51 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.246699E+10 | 3769.77 | 05-OCT-14:00 | 23.30 | 18.86 | 0.407034E+09 | 549.51 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.110858E+10 | 1587.00 | 03-NOV-14:00 | 17.80 | 10.67 | 0.344596E+09 | 549.49 | 03-NOV-13:20 | 17.80 | 10.67 |
December | 0.364393E+09 | 1033.65 | 20-DEC-14:10 | 9.72 | 5.77 | 0.298511E+09 | 447.09 | 20-DEC-14:09 | 9.72 | 5.77 |
Annual Sum or Average | 0.277487E+11 | 0.444906E+10 | ||||||||
Minimum of Months | 0.149513E+09 | 949.39 | 7.80 | 3.12 | 0.278553E+09 | 424.12 | 7.80 | 2.78 | ||
Maximum of Months | 0.563324E+10 | 7606.10 | 29.40 | 21.76 | 0.455006E+09 | 549.51 | 29.40 | 19.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.197352E+09 | 747.76 | 27-JAN-10:30 | 4.70 | 1.53 | 0.197622E+09 | 310.94 | 27-JAN-10:39 | 4.80 | 1.56 |
February | 0.261973E+09 | 748.63 | 22-FEB-10:10 | 0.87 | -3.0 | 0.181666E+09 | 311.73 | 22-FEB-10:20 | 1.13 | -2.8 |
March | 0.839185E+09 | 2241.31 | 29-MAR-09:30 | 6.15 | 3.19 | 0.244339E+09 | 347.88 | 23-MAR-09:20 | 6.15 | 3.19 |
April | 0.146899E+10 | 4242.57 | 28-APR-09:10 | 16.28 | 8.96 | 0.237908E+09 | 347.88 | 26-APR-09:00 | 16.28 | 8.96 |
May | 0.273910E+10 | 9265.52 | 29-MAY-08:52 | 26.10 | 16.72 | 0.271970E+09 | 348.14 | 30-MAY-09:00 | 27.80 | 17.82 |
June | 0.396615E+10 | 8958.09 | 04-JUN-10:32 | 25.20 | 13.32 | 0.276157E+09 | 348.14 | 26-JUN-09:00 | 26.10 | 20.11 |
July | 0.483266E+10 | 9951.65 | 09-JUL-09:32 | 29.43 | 25.37 | 0.257385E+09 | 348.47 | 14-JUL-09:00 | 30.60 | 21.74 |
August | 0.575706E+10 | 10922.87 | 20-AUG-09:52 | 23.90 | 15.38 | 0.288631E+09 | 348.22 | 18-AUG-09:30 | 23.90 | 15.38 |
September | 0.366532E+10 | 11213.16 | 10-SEP-09:12 | 20.57 | 13.59 | 0.255560E+09 | 348.05 | 06-SEP-09:30 | 20.57 | 13.59 |
October | 0.265299E+10 | 4994.03 | 05-OCT-09:20 | 19.27 | 16.99 | 0.263255E+09 | 347.89 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.940156E+09 | 2371.56 | 03-NOV-09:30 | 13.05 | 8.24 | 0.231518E+09 | 347.88 | 07-NOV-10:20 | 10.37 | 7.28 |
December | 0.423322E+09 | 831.66 | 20-DEC-10:00 | 8.30 | 5.00 | 0.198185E+09 | 335.94 | 20-DEC-10:09 | 8.40 | 5.03 |
Annual Sum or Average | 0.277442E+11 | 0.290420E+10 | ||||||||
Minimum of Months | 0.197352E+09 | 747.76 | 0.87 | -3.0 | 0.181666E+09 | 310.94 | 1.13 | -2.8 | ||
Maximum of Months | 0.575706E+10 | 11213.16 | 29.43 | 25.37 | 0.288631E+09 | 348.47 | 30.60 | 21.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.348353E+09 | 1429.91 | 19-JAN-14:30 | 9.15 | 3.65 | 0.307782E+09 | 549.50 | 19-JAN-14:50 | 8.98 | 3.61 |
February | 0.420089E+09 | 2309.57 | 25-FEB-13:10 | 2.88 | -1.9 | 0.283021E+09 | 547.34 | 02-FEB-14:39 | 2.88 | -1.9 |
March | 0.112623E+10 | 5812.13 | 03-MAR-13:20 | 14.60 | 8.23 | 0.367242E+09 | 549.51 | 07-MAR-14:09 | 10.00 | 5.05 |
April | 0.173128E+10 | 6974.04 | 07-APR-12:00 | 25.60 | 15.40 | 0.348092E+09 | 549.51 | 12-APR-13:09 | 11.28 | 2.93 |
May | 0.274908E+10 | 10851.79 | 30-MAY-12:00 | 29.40 | 17.58 | 0.407632E+09 | 551.13 | 30-MAY-12:09 | 29.50 | 17.65 |
June | 0.495175E+10 | 12443.37 | 19-JUN-12:00 | 36.70 | 24.28 | 0.433000E+09 | 636.10 | 19-JUN-12:09 | 36.42 | 24.23 |
July | 0.701386E+10 | 11874.73 | 07-JUL-12:00 | 33.90 | 23.31 | 0.406358E+09 | 604.03 | 07-JUL-12:09 | 33.72 | 23.31 |
August | 0.915731E+10 | 13589.14 | 20-AUG-13:12 | 28.17 | 15.57 | 0.456386E+09 | 608.92 | 18-AUG-12:09 | 28.17 | 15.57 |
September | 0.646330E+10 | 13989.81 | 10-SEP-13:12 | 24.07 | 14.06 | 0.401751E+09 | 593.45 | 01-SEP-12:09 | 24.07 | 14.06 |
October | 0.570733E+10 | 13812.20 | 15-OCT-12:52 | 20.60 | 12.82 | 0.411223E+09 | 568.49 | 04-OCT-13:20 | 20.60 | 12.82 |
November | 0.168773E+10 | 8354.50 | 02-NOV-13:30 | 15.85 | 8.46 | 0.354615E+09 | 549.63 | 02-NOV-13:00 | 16.10 | 8.71 |
December | 0.715243E+09 | 3370.46 | 17-DEC-13:40 | 12.20 | 5.18 | 0.315245E+09 | 549.51 | 18-DEC-14:09 | 7.52 | 2.81 |
Annual Sum or Average | 0.420716E+11 | 0.449235E+10 | ||||||||
Minimum of Months | 0.348353E+09 | 1429.91 | 2.88 | -1.9 | 0.283021E+09 | 547.34 | 2.88 | -1.9 | ||
Maximum of Months | 0.915731E+10 | 13989.81 | 36.70 | 24.28 | 0.456386E+09 | 636.10 | 36.42 | 24.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.198755E+09 | 858.93 | 20-JAN-16:00 | 7.20 | 3.80 | 0.198149E+09 | 335.16 | 20-JAN-16:10 | 6.93 | 3.71 |
February | 0.234574E+09 | 1166.91 | 22-FEB-16:30 | 3.85 | -0.7 | 0.182244E+09 | 338.68 | 22-FEB-16:00 | 3.30 | -0.7 |
March | 0.893440E+09 | 3353.35 | 27-MAR-16:50 | 21.28 | 15.57 | 0.236563E+09 | 347.85 | 28-MAR-13:20 | 13.70 | 8.60 |
April | 0.145319E+10 | 6421.73 | 09-APR-16:43 | 16.28 | 13.85 | 0.230301E+09 | 347.85 | 07-APR-13:20 | 16.28 | 13.85 |
May | 0.251085E+10 | 7272.88 | 27-MAY-17:42 | 21.20 | 11.70 | 0.269691E+09 | 347.87 | 15-MAY-13:00 | 21.20 | 11.70 |
June | 0.416263E+10 | 11283.80 | 04-JUN-15:52 | 22.20 | 14.53 | 0.276137E+09 | 347.86 | 22-JUN-09:20 | 25.77 | 16.91 |
July | 0.481591E+10 | 11295.84 | 02-JUL-16:32 | 24.60 | 20.65 | 0.257320E+09 | 347.86 | 12-JUL-13:00 | 28.30 | 19.52 |
August | 0.572845E+10 | 11680.43 | 20-AUG-16:32 | 25.20 | 17.51 | 0.288639E+09 | 347.86 | 08-AUG-13:39 | 25.20 | 17.51 |
September | 0.358610E+10 | 12084.36 | 10-SEP-16:31 | 22.97 | 12.76 | 0.255201E+09 | 347.86 | 19-SEP-09:20 | 18.87 | 14.31 |
October | 0.270372E+10 | 8679.39 | 15-OCT-15:32 | 19.80 | 12.41 | 0.261995E+09 | 347.86 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.851896E+09 | 3422.08 | 03-NOV-15:30 | 16.10 | 10.65 | 0.224358E+09 | 347.85 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.352920E+09 | 859.53 | 08-DEC-15:40 | 6.30 | 2.04 | 0.195828E+09 | 335.68 | 21-DEC-15:50 | 2.88 | -2.1 |
Annual Sum or Average | 0.274924E+11 | 0.287643E+10 | ||||||||
Minimum of Months | 0.198755E+09 | 858.93 | 3.85 | -0.7 | 0.182244E+09 | 335.16 | 2.88 | -2.1 | ||
Maximum of Months | 0.572845E+10 | 12084.36 | 25.20 | 20.65 | 0.288639E+09 | 347.87 | 28.30 | 19.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193122E+09 | 1012.90 | 20-JAN-15:10 | 7.70 | 3.95 | 0.306743E+09 | 440.64 | 20-JAN-14:00 | 7.70 | 3.95 |
February | 0.230430E+09 | 1029.44 | 24-FEB-15:40 | 7.97 | 1.96 | 0.280116E+09 | 444.01 | 24-FEB-14:00 | 7.97 | 1.96 |
March | 0.107305E+10 | 1520.51 | 28-MAR-14:00 | 13.30 | 8.41 | 0.363539E+09 | 549.48 | 28-MAR-13:00 | 13.30 | 8.41 |
April | 0.180296E+10 | 3587.17 | 07-APR-15:20 | 25.60 | 16.01 | 0.364578E+09 | 549.50 | 07-APR-13:20 | 25.60 | 16.01 |
May | 0.342541E+10 | 8341.43 | 30-MAY-06:03 | 20.47 | 15.45 | 0.430145E+09 | 549.52 | 15-MAY-13:00 | 20.47 | 15.45 |
June | 0.526669E+10 | 8504.23 | 26-JUN-05:12 | 20.97 | 17.23 | 0.435910E+09 | 550.12 | 19-JUN-13:20 | 20.97 | 17.23 |
July | 0.608757E+10 | 10110.03 | 09-JUL-16:02 | 27.12 | 24.30 | 0.406188E+09 | 550.45 | 31-JUL-13:20 | 27.60 | 22.18 |
August | 0.612237E+10 | 8339.46 | 14-AUG-06:03 | 23.48 | 21.76 | 0.455277E+09 | 549.51 | 02-AUG-09:20 | 23.48 | 21.76 |
September | 0.381070E+10 | 7784.77 | 05-SEP-06:03 | 20.78 | 18.13 | 0.401000E+09 | 549.51 | 19-SEP-09:20 | 18.87 | 14.31 |
October | 0.248525E+10 | 4023.95 | 05-OCT-14:00 | 23.30 | 18.86 | 0.403416E+09 | 549.51 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.970437E+09 | 1836.94 | 03-NOV-14:00 | 17.80 | 10.67 | 0.338123E+09 | 549.49 | 03-NOV-13:20 | 17.80 | 10.67 |
December | 0.309106E+09 | 1057.60 | 20-DEC-14:00 | 10.00 | 5.91 | 0.297759E+09 | 453.53 | 20-DEC-14:20 | 9.43 | 5.62 |
Annual Sum or Average | 0.317771E+11 | 0.448279E+10 | ||||||||
Minimum of Months | 0.193122E+09 | 1012.90 | 7.70 | 1.96 | 0.280116E+09 | 440.64 | 7.70 | 1.96 | ||
Maximum of Months | 0.612237E+10 | 10110.03 | 27.12 | 24.30 | 0.455277E+09 | 550.45 | 27.60 | 22.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174703E+09 | 814.68 | 19-JAN-10:00 | 7.80 | 4.14 | 0.146106E+09 | 324.76 | 19-JAN-11:09 | 7.70 | 4.65 |
February | 0.234663E+09 | 864.34 | 22-FEB-09:50 | 0.50 | -3.2 | 0.136160E+09 | 339.25 | 22-FEB-11:09 | 2.38 | -2.1 |
March | 0.881788E+09 | 5545.75 | 29-MAR-12:02 | 7.80 | 5.26 | 0.184977E+09 | 356.45 | 29-MAR-12:09 | 7.80 | 5.26 |
April | 0.176393E+10 | 6699.10 | 28-APR-10:05 | 17.30 | 9.69 | 0.178072E+09 | 356.47 | 26-APR-10:09 | 17.30 | 9.69 |
May | 0.335266E+10 | 12950.31 | 29-MAY-08:32 | 25.37 | 16.74 | 0.203151E+09 | 356.47 | 15-MAY-14:09 | 25.37 | 16.74 |
June | 0.442453E+10 | 13874.59 | 25-JUN-08:42 | 25.40 | 23.51 | 0.204860E+09 | 356.46 | 02-JUN-12:09 | 25.40 | 23.51 |
July | 0.513080E+10 | 14408.60 | 02-JUL-09:01 | 25.68 | 21.69 | 0.191620E+09 | 356.46 | 11-JUL-10:09 | 25.18 | 17.11 |
August | 0.574983E+10 | 13080.79 | 27-AUG-09:12 | 24.97 | 21.75 | 0.213933E+09 | 356.46 | 08-AUG-10:09 | 24.97 | 21.75 |
September | 0.345934E+10 | 13706.06 | 10-SEP-08:32 | 19.63 | 13.49 | 0.189134E+09 | 356.47 | 19-SEP-10:09 | 20.00 | 15.38 |
October | 0.236387E+10 | 6483.83 | 04-OCT-10:05 | 21.38 | 18.15 | 0.192955E+09 | 356.46 | 02-OCT-10:09 | 21.38 | 18.15 |
November | 0.697217E+09 | 5224.48 | 01-NOV-12:02 | 12.88 | 7.12 | 0.166204E+09 | 356.46 | 09-NOV-15:09 | 13.80 | 12.65 |
December | 0.273334E+09 | 982.19 | 20-DEC-09:35 | 7.57 | 4.72 | 0.144871E+09 | 343.63 | 20-DEC-11:09 | 8.90 | 5.16 |
Annual Sum or Average | 0.285067E+11 | 0.215204E+10 | ||||||||
Minimum of Months | 0.174703E+09 | 814.68 | 0.50 | -3.2 | 0.136160E+09 | 324.76 | 2.38 | -2.1 | ||
Maximum of Months | 0.574983E+10 | 14408.60 | 25.68 | 23.51 | 0.213933E+09 | 356.47 | 25.40 | 23.51 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102668E+10 | 6016.12 | 19-JAN-13:25 | 9.40 | 3.94 | 0.343511E+09 | 549.50 | 30-JAN-14:39 | 2.80 | -1.1 |
February | 0.132449E+10 | 6648.82 | 02-FEB-13:40 | 5.97 | -0.5 | 0.319881E+09 | 549.50 | 17-FEB-14:09 | 6.60 | 2.15 |
March | 0.279530E+10 | 8758.02 | 29-MAR-13:00 | 7.80 | 5.26 | 0.405387E+09 | 549.51 | 23-MAR-13:00 | 7.80 | 5.26 |
April | 0.319901E+10 | 9505.73 | 07-APR-12:30 | 26.15 | 15.90 | 0.377072E+09 | 550.29 | 07-APR-13:20 | 26.50 | 16.25 |
May | 0.447908E+10 | 14974.88 | 29-MAY-11:53 | 28.90 | 18.44 | 0.430696E+09 | 550.59 | 30-MAY-13:20 | 29.80 | 17.64 |
June | 0.603855E+10 | 10190.17 | 18-JUN-13:53 | 26.10 | 22.26 | 0.435954E+09 | 550.64 | 19-JUN-13:20 | 34.80 | 23.85 |
July | 0.713341E+10 | 14915.01 | 09-JUL-13:22 | 31.70 | 25.11 | 0.406380E+09 | 550.77 | 13-JUL-13:20 | 30.77 | 23.58 |
August | 0.882399E+10 | 15463.62 | 20-AUG-12:32 | 27.43 | 15.69 | 0.455785E+09 | 557.77 | 30-AUG-13:20 | 27.77 | 15.58 |
September | 0.676902E+10 | 16126.15 | 10-SEP-12:32 | 23.53 | 13.85 | 0.403160E+09 | 575.68 | 28-SEP-13:20 | 23.17 | 13.55 |
October | 0.650238E+10 | 15240.54 | 22-OCT-12:02 | 21.28 | 16.35 | 0.414174E+09 | 567.02 | 04-OCT-13:20 | 21.28 | 16.35 |
November | 0.252270E+10 | 11065.41 | 02-NOV-12:40 | 15.40 | 8.14 | 0.376934E+09 | 550.20 | 06-NOV-10:39 | 10.03 | 5.70 |
December | 0.141835E+10 | 6962.45 | 21-DEC-13:15 | 2.97 | -1.7 | 0.343273E+09 | 549.50 | 14-DEC-14:09 | 2.97 | -1.7 |
Annual Sum or Average | 0.520329E+11 | 0.471221E+10 | ||||||||
Minimum of Months | 0.102668E+10 | 6016.12 | 2.97 | -1.7 | 0.319881E+09 | 549.50 | 2.80 | -1.7 | ||
Maximum of Months | 0.882399E+10 | 16126.15 | 31.70 | 25.11 | 0.455785E+09 | 575.68 | 34.80 | 23.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229480E+09 | 1411.02 | 20-JAN-15:50 | 7.30 | 3.83 | 0.200421E+09 | 343.44 | 19-JAN-14:00 | 7.30 | 3.83 |
February | 0.310877E+09 | 2302.46 | 24-FEB-15:30 | 8.05 | 2.04 | 0.185302E+09 | 347.83 | 17-FEB-14:00 | 8.05 | 2.04 |
March | 0.118258E+10 | 5387.46 | 29-MAR-16:00 | 7.20 | 4.88 | 0.241366E+09 | 347.85 | 29-MAR-13:20 | 7.20 | 4.88 |
April | 0.193751E+10 | 11357.31 | 09-APR-15:43 | 17.30 | 14.24 | 0.234354E+09 | 347.85 | 07-APR-13:20 | 17.30 | 14.24 |
May | 0.332918E+10 | 13297.84 | 21-MAY-15:22 | 20.00 | 13.23 | 0.272809E+09 | 347.87 | 15-MAY-13:00 | 20.00 | 13.23 |
June | 0.481420E+10 | 13979.47 | 25-JUN-16:42 | 25.68 | 22.47 | 0.276177E+09 | 347.86 | 26-JUN-09:20 | 25.37 | 19.69 |
July | 0.525984E+10 | 13945.37 | 02-JUL-16:21 | 24.70 | 20.69 | 0.257390E+09 | 347.86 | 17-JUL-09:20 | 27.97 | 21.33 |
August | 0.592479E+10 | 13897.99 | 20-AUG-16:32 | 25.20 | 17.51 | 0.288513E+09 | 347.86 | 02-AUG-09:20 | 25.20 | 17.51 |
September | 0.357806E+10 | 14529.55 | 10-SEP-15:51 | 23.30 | 12.88 | 0.254399E+09 | 347.86 | 19-SEP-09:20 | 18.87 | 14.31 |
October | 0.262894E+10 | 7240.75 | 04-OCT-15:30 | 23.35 | 19.12 | 0.257510E+09 | 347.86 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.781001E+09 | 3806.03 | 03-NOV-15:30 | 16.10 | 10.65 | 0.219489E+09 | 347.85 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.304408E+09 | 1230.24 | 08-DEC-15:30 | 6.40 | 2.12 | 0.195622E+09 | 347.83 | 21-DEC-14:00 | 3.30 | -1.8 |
Annual Sum or Average | 0.302809E+11 | 0.288335E+10 | ||||||||
Minimum of Months | 0.229480E+09 | 1230.24 | 6.40 | 2.04 | 0.185302E+09 | 343.44 | 3.30 | -1.8 | ||
Maximum of Months | 0.592479E+10 | 14529.55 | 25.68 | 22.47 | 0.288513E+09 | 347.87 | 27.97 | 21.33 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.366534E+09 | 19306.52 | 02-JAN-05:01 | -12.1 |
February | 622785.83 | 10379.76 | 06-FEB-07:01 | -13.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.367157E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.366534E+09 | 19306.52 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.494656E+10 | 15986.64 | 02-JAN-06:12 | -11.7 |
February | 0.402632E+10 | 16403.75 | 06-FEB-06:06 | -12.9 |
March | 0.178214E+10 | 11467.58 | 13-MAR-05:12 | -0.6 |
April | 0.871295E+09 | 8914.16 | 03-APR-06:02 | 2.38 |
May | 0.262926E+09 | 3251.76 | 30-MAY-05:12 | 18.53 |
June | 60810996.52 | 4942.81 | 19-JUN-05:02 | 24.08 |
July | 25511145.04 | 4284.85 | 25-JUL-05:02 | 23.90 |
August | 53142589.90 | 3581.61 | 04-AUG-05:03 | 24.08 |
September | 0.181422E+09 | 3118.95 | 01-SEP-05:02 | 24.08 |
October | 0.564200E+09 | 3356.54 | 19-OCT-05:03 | 5.37 |
November | 0.196032E+10 | 12227.22 | 24-NOV-06:13 | -4.4 |
December | 0.334616E+10 | 11578.19 | 11-DEC-06:12 | 1.70 |
Annual Sum or Average | 0.180808E+11 | |||
Minimum of Months | 25511145.04 | 3118.95 | -12.9 | |
Maximum of Months | 0.494656E+10 | 16403.75 | 24.08 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.262627E+10 | 10341.05 | 02-JAN-07:07 | -11.6 |
February | 0.201227E+10 | 8656.76 | 06-FEB-07:11 | -13.1 |
March | 0.129369E+10 | 3518.84 | 01-MAR-11:05 | 13.90 |
April | 0.495133E+09 | 2814.49 | 03-APR-10:05 | 8.17 |
May | 0.107889E+09 | 3461.72 | 28-MAY-14:23 | 26.15 |
June | 18271819.07 | 2310.71 | 19-JUN-05:02 | 24.08 |
July | 26886131.90 | 3001.19 | 09-JUL-14:41 | 27.95 |
August | 19807721.76 | 3343.54 | 20-AUG-13:52 | 28.90 |
September | 30126653.81 | 4063.66 | 10-SEP-09:52 | 21.70 |
October | 0.172383E+09 | 4282.56 | 09-OCT-13:33 | 13.70 |
November | 0.118275E+10 | 4344.71 | 24-NOV-07:02 | -4.3 |
December | 0.174299E+10 | 4716.71 | 26-DEC-07:03 | 6.70 |
Annual Sum or Average | 0.972846E+10 | |||
Minimum of Months | 18271819.07 | 2310.71 | -13.1 | |
Maximum of Months | 0.262627E+10 | 10341.05 | 28.90 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.220535E+10 | 9335.75 | 02-JAN-07:01 | -11.6 |
February | 0.158478E+10 | 4420.04 | 06-FEB-08:30 | -12.5 |
March | 0.924819E+09 | 3762.15 | 22-MAR-07:08 | -2.7 |
April | 0.263349E+09 | 3069.31 | 04-APR-07:08 | 4.87 |
May | 22197347.28 | 1534.80 | 21-MAY-07:20 | 16.13 |
June | 19838966.65 | 2552.90 | 19-JUN-05:02 | 24.08 |
July | 23982095.41 | 2916.45 | 25-JUL-05:02 | 23.90 |
August | 22470127.27 | 3054.08 | 22-AUG-04:03 | 25.92 |
September | 29976522.33 | 3461.43 | 01-SEP-05:02 | 24.08 |
October | 55949054.85 | 2896.74 | 09-OCT-13:33 | 13.70 |
November | 0.781255E+09 | 3796.98 | 21-NOV-08:09 | 0.18 |
December | 0.143706E+10 | 4085.96 | 21-DEC-08:05 | -0.5 |
Annual Sum or Average | 0.737102E+10 | |||
Minimum of Months | 19838966.65 | 1534.80 | -12.5 | |
Maximum of Months | 0.220535E+10 | 9335.75 | 25.92 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.957980E+09 | 23262.82 | 02-JAN-05:01 | -12.1 |
February | 0.269129E+09 | 20403.41 | 06-FEB-06:01 | -12.9 |
March | 11363316.11 | 18119.18 | 20-MAR-06:01 | -0.6 |
April | 1841810.97 | 18418.11 | 03-APR-06:02 | 2.38 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 37837358.40 | 18660.52 | 24-NOV-06:01 | -4.4 |
December | 72761767.04 | 19064.01 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.135091E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.9 | |
Maximum of Months | 0.957980E+09 | 23262.82 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.291548E+10 | 32151.24 | 02-JAN-01:22 | -11.4 |
February | 0.181508E+10 | 31381.64 | 06-FEB-05:01 | -13.2 |
March | 0.326899E+09 | 28427.64 | 20-MAR-05:01 | -1.5 |
April | 50994657.41 | 27234.69 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.588048E+09 | 29396.62 | 24-NOV-05:01 | -4.0 |
December | 0.100772E+10 | 29889.25 | 26-DEC-06:11 | 6.30 |
Annual Sum or Average | 0.670423E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.291548E+10 | 32151.24 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.457589E+10 | 11341.04 | 01-JAN-22:42 | -9.9 |
February | 0.378109E+10 | 11339.96 | 06-FEB-00:42 | -13.3 |
March | 0.104125E+10 | 10131.85 | 13-MAR-04:01 | -0.1 |
April | 0.213143E+09 | 9737.95 | 03-APR-05:11 | 2.60 |
May | 1749799.13 | 8183.13 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 30175785.61 | 8296.51 | 10-OCT-06:02 | 8.58 |
November | 0.123103E+10 | 10417.43 | 24-NOV-05:01 | -4.0 |
December | 0.276659E+10 | 11096.82 | 31-DEC-21:52 | -7.2 |
Annual Sum or Average | 0.136409E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.457589E+10 | 11341.04 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255959E+10 | 12127.19 | 01-JAN-22:42 | -9.9 |
February | 0.189247E+10 | 12131.54 | 06-FEB-00:42 | -13.3 |
March | 0.474034E+09 | 10853.75 | 13-MAR-04:01 | -0.1 |
April | 0.103239E+09 | 10449.18 | 03-APR-05:11 | 2.60 |
May | 209297.26 | 1395.32 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 13642014.56 | 8093.91 | 10-OCT-06:02 | 8.58 |
November | 0.619213E+09 | 11202.52 | 24-NOV-05:01 | -4.0 |
December | 0.146355E+10 | 11808.32 | 31-DEC-21:52 | -7.2 |
Annual Sum or Average | 0.712595E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.255959E+10 | 12131.54 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.313549E+10 | 15121.13 | 02-JAN-01:22 | -11.4 |
February | 0.231414E+10 | 15119.25 | 06-FEB-04:42 | -13.3 |
March | 0.676309E+09 | 13612.15 | 13-MAR-04:01 | -0.1 |
April | 0.181501E+09 | 12933.25 | 03-APR-05:11 | 2.60 |
May | 2595057.00 | 8652.36 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 13722531.72 | 9326.20 | 28-OCT-06:03 | 3.90 |
November | 0.718004E+09 | 13935.00 | 24-NOV-05:01 | -4.0 |
December | 0.177231E+10 | 14638.64 | 31-DEC-21:52 | -7.2 |
Annual Sum or Average | 0.881408E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.313549E+10 | 15121.13 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.278615E+10 | 13166.99 | 01-JAN-22:42 | -9.9 |
February | 0.222545E+10 | 13170.49 | 06-FEB-00:42 | -13.3 |
March | 0.570183E+09 | 11768.90 | 13-MAR-04:01 | -0.1 |
April | 0.130196E+09 | 11218.51 | 03-APR-05:11 | 2.60 |
May | 1606835.15 | 5473.44 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 17113976.62 | 7379.39 | 10-OCT-06:02 | 8.58 |
November | 0.752869E+09 | 12149.32 | 24-NOV-05:01 | -4.0 |
December | 0.166476E+10 | 12764.37 | 31-DEC-23:52 | -8.3 |
Annual Sum or Average | 0.814833E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.278615E+10 | 13170.49 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.260855E+10 | 8682.51 | 01-JAN-22:42 | -9.9 |
February | 0.205973E+10 | 8300.25 | 06-FEB-05:11 | -13.1 |
March | 0.438417E+09 | 7389.68 | 13-MAR-05:01 | -0.6 |
April | 54016842.02 | 7088.47 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.228380E+09 | 7294.67 | 24-NOV-06:01 | -4.4 |
December | 0.732233E+09 | 7262.03 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.612133E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.1 | |
Maximum of Months | 0.260855E+10 | 8682.51 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133162E+10 | 9691.33 | 01-JAN-22:42 | -9.9 |
February | 0.834196E+09 | 9298.19 | 06-FEB-05:11 | -13.1 |
March | 0.133613E+09 | 8181.21 | 13-MAR-05:01 | -0.6 |
April | 15608626.78 | 7892.76 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 85285686.24 | 8058.30 | 24-NOV-06:01 | -4.4 |
December | 0.338393E+09 | 8185.58 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.273872E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.1 | |
Maximum of Months | 0.133162E+10 | 9691.33 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.438181E+10 | 13509.08 | 02-JAN-08:00 | -11.1 |
February | 0.354147E+10 | 13001.93 | 06-FEB-08:00 | -12.8 |
March | 0.225557E+10 | 11282.54 | 23-MAR-06:10 | -4.7 |
April | 0.107486E+10 | 10507.33 | 03-APR-06:10 | 2.38 |
May | 0.294687E+09 | 9316.57 | 01-MAY-06:03 | 7.67 |
June | 216327.33 | 977.01 | 02-JUN-06:10 | 13.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 3625777.19 | 4424.91 | 20-SEP-06:07 | 12.48 |
October | 0.200932E+09 | 9069.80 | 31-OCT-06:05 | 5.68 |
November | 0.147580E+10 | 11289.65 | 24-NOV-07:10 | -4.3 |
December | 0.269665E+10 | 11220.15 | 15-DEC-07:10 | -3.6 |
Annual Sum or Average | 0.159256E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.438181E+10 | 13509.08 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148392E+10 | 9943.97 | 01-JAN-22:42 | -9.9 |
February | 0.101910E+10 | 9530.61 | 06-FEB-05:11 | -13.1 |
March | 0.138934E+09 | 8317.95 | 13-MAR-05:01 | -0.6 |
April | 21358871.11 | 7896.55 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.116659E+09 | 8204.07 | 24-NOV-06:01 | -4.4 |
December | 0.386804E+09 | 8307.62 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.316678E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.1 | |
Maximum of Months | 0.148392E+10 | 9943.97 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.261726E+10 | 9654.87 | 01-JAN-20:42 | -8.0 |
February | 0.190032E+10 | 9470.66 | 06-FEB-00:42 | -13.3 |
March | 0.321193E+09 | 8203.80 | 13-MAR-04:04 | -0.1 |
April | 35936827.13 | 7816.03 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 289631.54 | 1930.88 | 28-OCT-06:03 | 3.90 |
November | 0.430373E+09 | 8620.99 | 24-NOV-05:01 | -4.0 |
December | 0.108216E+10 | 8313.46 | 26-DEC-06:11 | 6.30 |
Annual Sum or Average | 0.638753E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.261726E+10 | 9654.87 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141739E+10 | 10896.03 | 01-JAN-22:42 | -9.9 |
February | 0.899766E+09 | 10695.27 | 06-FEB-00:42 | -13.3 |
March | 0.143311E+09 | 9063.19 | 13-MAR-05:01 | -0.6 |
April | 14180400.81 | 8718.61 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 142792.97 | 951.95 | 28-OCT-06:03 | 3.90 |
November | 0.212387E+09 | 9718.42 | 24-NOV-05:01 | -4.0 |
December | 0.575576E+09 | 9375.33 | 26-DEC-06:11 | 6.30 |
Annual Sum or Average | 0.326275E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.141739E+10 | 10896.03 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165706E+10 | 13355.57 | 01-JAN-22:42 | -9.9 |
February | 0.997596E+09 | 13089.33 | 06-FEB-04:42 | -13.3 |
March | 0.187777E+09 | 11290.51 | 13-MAR-05:01 | -0.6 |
April | 29628147.67 | 10768.14 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.213576E+09 | 11662.09 | 24-NOV-05:01 | -4.0 |
December | 0.638272E+09 | 11527.88 | 26-DEC-06:11 | 6.30 |
Annual Sum or Average | 0.372391E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.165706E+10 | 13355.57 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157877E+10 | 11011.95 | 01-JAN-22:42 | -9.9 |
February | 0.108371E+10 | 10803.84 | 06-FEB-00:42 | -13.3 |
March | 0.168477E+09 | 9102.98 | 13-MAR-05:01 | -0.6 |
April | 21857755.87 | 8633.71 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 95778.59 | 638.52 | 28-OCT-06:03 | 3.90 |
November | 0.262087E+09 | 9742.20 | 24-NOV-05:01 | -4.0 |
December | 0.647944E+09 | 9353.21 | 26-DEC-06:11 | 6.30 |
Annual Sum or Average | 0.376295E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.157877E+10 | 11011.95 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.644244E+09 | 1040.56 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.540313E+09 | 944.20 | 15-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.602358E+09 | 751.52 | 02-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.512788E+09 | 554.47 | 21-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.541448E+09 | 553.83 | 08-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.530653E+09 | 540.92 | 29-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.499456E+09 | 536.99 | 24-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.564589E+09 | 563.49 | 16-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.523330E+09 | 666.11 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.567236E+09 | 825.61 | 31-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.617021E+09 | 1040.56 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.636201E+09 | 1040.56 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.677964E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.499456E+09 | 536.99 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.644244E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.402565E+09 | 658.76 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.339440E+09 | 604.38 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.380303E+09 | 531.51 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.325197E+09 | 341.63 | 21-APR-15:00 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.344962E+09 | 351.28 | 19-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.338406E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.318275E+09 | 314.23 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.358725E+09 | 341.64 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330945E+09 | 359.20 | 26-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.357658E+09 | 527.10 | 31-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.388459E+09 | 658.76 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.394262E+09 | 658.76 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.427920E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.318275E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.402565E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620050E+09 | 1040.56 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.526134E+09 | 938.14 | 15-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.596151E+09 | 674.69 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.513467E+09 | 551.23 | 21-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.543718E+09 | 555.10 | 08-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.533869E+09 | 545.61 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.502314E+09 | 542.14 | 24-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.566536E+09 | 563.47 | 16-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.521669E+09 | 581.87 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.559325E+09 | 794.60 | 31-OCT-15:00 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.601635E+09 | 1040.56 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.605552E+09 | 1040.56 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.669042E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.502314E+09 | 542.14 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.620050E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.397171E+09 | 658.71 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335319E+09 | 589.25 | 15-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.377105E+09 | 469.58 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324691E+09 | 362.38 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.341884E+09 | 358.03 | 08-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.335905E+09 | 352.44 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.316481E+09 | 352.06 | 24-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.357096E+09 | 363.28 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330361E+09 | 447.97 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.355388E+09 | 507.61 | 06-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.382830E+09 | 658.71 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.389820E+09 | 658.71 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.424405E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.316481E+09 | 352.06 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.397171E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.641569E+09 | 1040.56 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.538491E+09 | 940.52 | 15-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.601060E+09 | 739.73 | 02-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.512239E+09 | 550.36 | 21-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.541075E+09 | 549.67 | 08-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.530240E+09 | 536.13 | 29-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.498993E+09 | 532.02 | 24-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.564288E+09 | 559.80 | 16-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.522407E+09 | 583.18 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.565999E+09 | 817.37 | 31-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.615321E+09 | 1040.56 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.632889E+09 | 1040.56 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.676457E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.498993E+09 | 532.02 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.641569E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.401317E+09 | 658.76 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.338640E+09 | 602.69 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.379737E+09 | 527.65 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324833E+09 | 338.94 | 21-APR-15:00 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.344702E+09 | 348.95 | 19-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.338143E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.317966E+09 | 314.23 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.358480E+09 | 338.63 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330505E+09 | 357.25 | 26-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.357051E+09 | 523.04 | 31-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.387679E+09 | 658.76 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.393000E+09 | 658.76 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.427205E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.317966E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.401317E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.618776E+09 | 1040.56 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.525562E+09 | 934.14 | 15-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.595550E+09 | 584.21 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.512927E+09 | 546.93 | 21-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.543330E+09 | 551.02 | 08-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.533335E+09 | 541.10 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.501808E+09 | 537.47 | 24-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.566180E+09 | 559.77 | 16-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.520903E+09 | 579.02 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.558835E+09 | 784.77 | 31-OCT-15:00 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.600854E+09 | 1040.56 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.604161E+09 | 1040.56 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.668222E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.501808E+09 | 537.47 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.618776E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.395748E+09 | 658.71 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.334608E+09 | 586.98 | 15-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.376640E+09 | 463.79 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324305E+09 | 360.76 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.341672E+09 | 356.00 | 08-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.335671E+09 | 350.18 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.316218E+09 | 349.80 | 24-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.356833E+09 | 361.47 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.329949E+09 | 441.55 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.355046E+09 | 502.98 | 06-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.382028E+09 | 658.71 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.388292E+09 | 658.71 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.423701E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.316218E+09 | 349.80 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.395748E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.644240E+09 | 1040.56 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.540311E+09 | 944.19 | 15-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.602357E+09 | 751.50 | 02-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.512787E+09 | 554.46 | 21-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.541447E+09 | 553.82 | 08-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.530653E+09 | 540.91 | 29-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.499456E+09 | 536.98 | 24-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.564589E+09 | 563.48 | 16-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.523329E+09 | 666.07 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.567235E+09 | 825.59 | 31-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.617019E+09 | 1040.56 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.636198E+09 | 1040.56 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.677962E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.499456E+09 | 536.98 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.644240E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.402563E+09 | 658.76 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.339439E+09 | 604.37 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.380302E+09 | 531.50 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.325197E+09 | 341.62 | 21-APR-15:00 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.344962E+09 | 351.28 | 19-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.338406E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.318273E+09 | 314.23 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.358756E+09 | 341.63 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330945E+09 | 359.20 | 26-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.357658E+09 | 527.09 | 31-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.388458E+09 | 658.76 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.394250E+09 | 658.76 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.427921E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.318273E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.402563E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620049E+09 | 1040.56 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.526133E+09 | 938.13 | 15-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.596133E+09 | 674.66 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.513466E+09 | 551.22 | 21-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.543718E+09 | 555.09 | 08-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.533868E+09 | 545.60 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.502314E+09 | 542.13 | 24-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.566536E+09 | 563.46 | 16-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.521668E+09 | 581.86 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.559325E+09 | 794.58 | 31-OCT-15:00 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.601635E+09 | 1040.56 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.605551E+09 | 1040.56 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.669039E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.502314E+09 | 542.13 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.620049E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.397170E+09 | 658.71 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335319E+09 | 589.24 | 15-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.377105E+09 | 469.56 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324690E+09 | 362.37 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.341884E+09 | 358.03 | 08-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.335903E+09 | 352.44 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.316481E+09 | 352.05 | 24-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.357096E+09 | 363.28 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330361E+09 | 447.95 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.355388E+09 | 507.59 | 06-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.382829E+09 | 658.71 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.389819E+09 | 658.71 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.424404E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.316481E+09 | 352.05 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.397170E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.644244E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158750E+10 |
February | 0.901968E+09 | 0.540313E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141769E+10 |
March | 0.107774E+10 | 0.602358E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113488E+10 |
April | 0.956342E+09 | 0.512788E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 627530.42 | 0.760738E+09 |
May | 0.103597E+10 | 0.541448E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2703449.63 | 0.472267E+09 |
June | 0.103308E+10 | 0.530653E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20071720.32 | 0.250784E+09 |
July | 0.959235E+09 | 0.499456E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47521759.37 | 92181121.14 |
August | 0.107774E+10 | 0.564589E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58282390.37 | 0.112844E+09 |
September | 0.956342E+09 | 0.523330E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7200340.42 | 0.256595E+09 |
October | 0.994195E+09 | 0.567236E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108568.09 | 0.616808E+09 |
November | 0.984487E+09 | 0.617021E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109190E+10 |
December | 0.959235E+09 | 0.636201E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131694E+10 |
Annual Sum or Average | 0.119305E+11 | 0.677964E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136516E+09 | 0.911113E+10 |
Minimum of Months | 0.901968E+09 | 0.499456E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92181121.14 |
Maximum of Months | 0.107774E+10 | 0.644244E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58282390.37 | 0.158750E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.402565E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105976E+10 |
February | 0.571020E+09 | 0.339440E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.953031E+09 |
March | 0.682301E+09 | 0.380303E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.771348E+09 |
April | 0.605444E+09 | 0.325197E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 417434.83 | 0.528730E+09 |
May | 0.655854E+09 | 0.344962E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1540909.32 | 0.324705E+09 |
June | 0.654023E+09 | 0.338406E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13087178.07 | 0.170924E+09 |
July | 0.607275E+09 | 0.318275E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30709682.34 | 63864311.07 |
August | 0.682301E+09 | 0.358725E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37784030.64 | 78963966.01 |
September | 0.605444E+09 | 0.330945E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4778084.49 | 0.180619E+09 |
October | 0.629407E+09 | 0.357658E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72369.69 | 0.429021E+09 |
November | 0.623262E+09 | 0.388459E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740856E+09 |
December | 0.607275E+09 | 0.394262E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882448E+09 |
Annual Sum or Average | 0.755301E+10 | 0.427920E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88389689.37 | 0.618427E+10 |
Minimum of Months | 0.571020E+09 | 0.318275E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63864311.07 |
Maximum of Months | 0.682301E+09 | 0.402565E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37784030.64 | 0.105976E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.620050E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162694E+10 |
February | 0.901968E+09 | 0.526134E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148108E+10 |
March | 0.107774E+10 | 0.596151E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119256E+10 |
April | 0.956342E+09 | 0.513467E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 625976.16 | 0.798438E+09 |
May | 0.103597E+10 | 0.543718E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2334165.14 | 0.480820E+09 |
June | 0.103308E+10 | 0.533869E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19736578.95 | 0.252369E+09 |
July | 0.959235E+09 | 0.502314E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46436931.15 | 94705111.01 |
August | 0.107774E+10 | 0.566536E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56388874.07 | 0.119111E+09 |
September | 0.956342E+09 | 0.521669E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7154198.50 | 0.277581E+09 |
October | 0.994195E+09 | 0.559325E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107535.22 | 0.683398E+09 |
November | 0.984487E+09 | 0.601635E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115492E+10 |
December | 0.959235E+09 | 0.605552E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138421E+10 |
Annual Sum or Average | 0.119305E+11 | 0.669042E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132784E+09 | 0.954613E+10 |
Minimum of Months | 0.901968E+09 | 0.502314E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94705111.01 |
Maximum of Months | 0.107774E+10 | 0.620050E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56388874.07 | 0.162694E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.397171E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106409E+10 |
February | 0.570983E+09 | 0.335319E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.957073E+09 |
March | 0.682256E+09 | 0.377105E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.782342E+09 |
April | 0.605404E+09 | 0.324691E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 417495.56 | 0.528931E+09 |
May | 0.655811E+09 | 0.341884E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1773812.89 | 0.327164E+09 |
June | 0.653980E+09 | 0.335905E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13036252.56 | 0.176771E+09 |
July | 0.607235E+09 | 0.316481E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30666532.45 | 69427340.68 |
August | 0.682256E+09 | 0.357096E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37381503.58 | 82442850.35 |
September | 0.605404E+09 | 0.330361E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4776058.73 | 0.180845E+09 |
October | 0.629366E+09 | 0.355388E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72416.89 | 0.433256E+09 |
November | 0.623221E+09 | 0.382830E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733702E+09 |
December | 0.607235E+09 | 0.389820E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.886679E+09 |
Annual Sum or Average | 0.755252E+10 | 0.424405E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88124072.66 | 0.622272E+10 |
Minimum of Months | 0.570983E+09 | 0.316481E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69427340.68 |
Maximum of Months | 0.682256E+09 | 0.397171E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37381503.58 | 0.106409E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.641569E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894306E+09 |
February | 0.901968E+09 | 0.538491E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791882E+09 |
March | 0.107774E+10 | 0.601060E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633074E+09 |
April | 0.956342E+09 | 0.512239E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 399696.84 | 0.418134E+09 |
May | 0.103597E+10 | 0.541075E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2495813.75 | 0.246754E+09 |
June | 0.103308E+10 | 0.530240E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12394255.92 | 0.128549E+09 |
July | 0.959235E+09 | 0.498993E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28818575.76 | 43735511.20 |
August | 0.107774E+10 | 0.564288E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33113206.66 | 59513435.61 |
September | 0.956342E+09 | 0.522407E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4068128.81 | 0.145391E+09 |
October | 0.994195E+09 | 0.565999E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65141.83 | 0.367712E+09 |
November | 0.984487E+09 | 0.615321E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663633E+09 |
December | 0.959235E+09 | 0.632889E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.775000E+09 |
Annual Sum or Average | 0.119305E+11 | 0.676457E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81354819.57 | 0.516768E+10 |
Minimum of Months | 0.901968E+09 | 0.498993E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43735511.20 |
Maximum of Months | 0.107774E+10 | 0.641569E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33113206.66 | 0.894306E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.401317E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598543E+09 |
February | 0.571020E+09 | 0.338640E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538403E+09 |
March | 0.682301E+09 | 0.379737E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436997E+09 |
April | 0.605444E+09 | 0.324833E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 229233.24 | 0.295969E+09 |
May | 0.655854E+09 | 0.344702E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 861035.77 | 0.175210E+09 |
June | 0.654023E+09 | 0.338143E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7339033.49 | 91221167.58 |
July | 0.607275E+09 | 0.317966E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17028126.22 | 33084169.37 |
August | 0.682301E+09 | 0.358480E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20489035.30 | 44587874.74 |
September | 0.605444E+09 | 0.330505E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2589758.20 | 0.105174E+09 |
October | 0.629407E+09 | 0.357051E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43423.85 | 0.258402E+09 |
November | 0.623262E+09 | 0.387679E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455972E+09 |
December | 0.607275E+09 | 0.393000E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524329E+09 |
Annual Sum or Average | 0.755301E+10 | 0.427205E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48579646.07 | 0.355789E+10 |
Minimum of Months | 0.571020E+09 | 0.317966E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33084169.37 |
Maximum of Months | 0.682301E+09 | 0.401317E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20489035.30 | 0.598543E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.618776E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582360E+10 |
February | 0.901968E+09 | 0.525562E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574442E+10 |
March | 0.107774E+10 | 0.595550E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513650E+10 |
April | 0.956342E+09 | 0.512927E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11069376.39 | 0.305370E+10 |
May | 0.103597E+10 | 0.543330E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45437395.40 | 0.181626E+10 |
June | 0.103308E+10 | 0.533335E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321405E+09 | 0.639694E+09 |
July | 0.959235E+09 | 0.501808E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681497E+09 | 0.104826E+09 |
August | 0.107774E+10 | 0.566180E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.828263E+09 | 0.226752E+09 |
September | 0.956342E+09 | 0.520903E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135146E+09 | 0.890877E+09 |
October | 0.994195E+09 | 0.558835E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1763959.99 | 0.238117E+10 |
November | 0.984487E+09 | 0.600854E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435496E+10 |
December | 0.959235E+09 | 0.604161E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524377E+10 |
Annual Sum or Average | 0.119305E+11 | 0.668222E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202458E+10 | 0.354165E+11 |
Minimum of Months | 0.901968E+09 | 0.501808E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104826E+09 |
Maximum of Months | 0.107774E+10 | 0.618776E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.828263E+09 | 0.582360E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.395748E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600776E+09 |
February | 0.570983E+09 | 0.334608E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538093E+09 |
March | 0.682256E+09 | 0.376640E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443660E+09 |
April | 0.605404E+09 | 0.324305E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 230567.67 | 0.297075E+09 |
May | 0.655811E+09 | 0.341672E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1197475.27 | 0.177522E+09 |
June | 0.653980E+09 | 0.335671E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7236117.00 | 96336888.89 |
July | 0.607235E+09 | 0.316218E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17038516.50 | 37224528.92 |
August | 0.682256E+09 | 0.356833E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20342103.82 | 47091103.44 |
September | 0.605404E+09 | 0.329949E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2588238.97 | 0.105519E+09 |
October | 0.629366E+09 | 0.355046E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43449.30 | 0.262433E+09 |
November | 0.623221E+09 | 0.382028E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449215E+09 |
December | 0.607235E+09 | 0.388292E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524541E+09 |
Annual Sum or Average | 0.755252E+10 | 0.423701E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48676468.53 | 0.357949E+10 |
Minimum of Months | 0.570983E+09 | 0.316218E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37224528.92 |
Maximum of Months | 0.682256E+09 | 0.395748E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20342103.82 | 0.600776E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.644240E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137284E+10 |
February | 0.901968E+09 | 0.540311E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122704E+10 |
March | 0.107774E+10 | 0.602357E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100496E+10 |
April | 0.956342E+09 | 0.512787E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 529784.65 | 0.676448E+09 |
May | 0.103597E+10 | 0.541447E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2464142.14 | 0.410726E+09 |
June | 0.103308E+10 | 0.530653E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17487119.41 | 0.214357E+09 |
July | 0.959235E+09 | 0.499456E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40749062.01 | 77772432.46 |
August | 0.107774E+10 | 0.564589E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49449713.18 | 97621407.71 |
September | 0.956342E+09 | 0.523329E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6135667.28 | 0.225586E+09 |
October | 0.994195E+09 | 0.567235E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95980.42 | 0.555466E+09 |
November | 0.984487E+09 | 0.617019E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.990652E+09 |
December | 0.959235E+09 | 0.636198E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117037E+10 |
Annual Sum or Average | 0.119305E+11 | 0.677962E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116911E+09 | 0.802382E+10 |
Minimum of Months | 0.901968E+09 | 0.499456E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77772432.46 |
Maximum of Months | 0.107774E+10 | 0.644240E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49449713.18 | 0.137284E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.402563E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.915979E+09 |
February | 0.421807E+09 | 0.339439E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829614E+09 |
March | 0.502994E+09 | 0.380302E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684847E+09 |
April | 0.447140E+09 | 0.325197E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 317768.98 | 0.469010E+09 |
May | 0.484071E+09 | 0.344962E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1271881.41 | 0.282725E+09 |
June | 0.482240E+09 | 0.338406E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10713055.36 | 0.147160E+09 |
July | 0.448971E+09 | 0.318273E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25282280.46 | 54406916.75 |
August | 0.502994E+09 | 0.358756E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30930618.18 | 68428177.86 |
September | 0.447140E+09 | 0.330945E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3794496.15 | 0.158929E+09 |
October | 0.465148E+09 | 0.357658E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36256.65 | 0.384192E+09 |
November | 0.460569E+09 | 0.388458E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672825E+09 |
December | 0.448971E+09 | 0.394250E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787088E+09 |
Annual Sum or Average | 0.557719E+10 | 0.427921E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72346357.20 | 0.545520E+10 |
Minimum of Months | 0.421807E+09 | 0.318273E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54406916.75 |
Maximum of Months | 0.502994E+09 | 0.402563E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30930618.18 | 0.915979E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.620049E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141490E+10 |
February | 0.901968E+09 | 0.526133E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129428E+10 |
March | 0.107774E+10 | 0.596133E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105408E+10 |
April | 0.956342E+09 | 0.513466E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 529466.65 | 0.707060E+09 |
May | 0.103597E+10 | 0.543718E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1976206.82 | 0.418109E+09 |
June | 0.103308E+10 | 0.533868E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16778837.53 | 0.216651E+09 |
July | 0.959235E+09 | 0.502314E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39398546.99 | 80574918.73 |
August | 0.107774E+10 | 0.566536E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47480248.76 | 0.103071E+09 |
September | 0.956342E+09 | 0.521668E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5989931.41 | 0.243281E+09 |
October | 0.994195E+09 | 0.559325E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73563.57 | 0.605122E+09 |
November | 0.984487E+09 | 0.601635E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104528E+10 |
December | 0.959235E+09 | 0.605551E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123487E+10 |
Annual Sum or Average | 0.119305E+11 | 0.669039E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112227E+09 | 0.841728E+10 |
Minimum of Months | 0.901968E+09 | 0.502314E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80574918.73 |
Maximum of Months | 0.107774E+10 | 0.620049E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47480248.76 | 0.141490E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.397170E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.920704E+09 |
February | 0.570983E+09 | 0.335319E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829430E+09 |
March | 0.682256E+09 | 0.377105E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691656E+09 |
April | 0.605404E+09 | 0.324690E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 353200.95 | 0.469057E+09 |
May | 0.655811E+09 | 0.341884E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1564318.89 | 0.284523E+09 |
June | 0.653980E+09 | 0.335903E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11049548.22 | 0.151748E+09 |
July | 0.607235E+09 | 0.316481E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25872020.19 | 59265552.22 |
August | 0.682256E+09 | 0.357096E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31553606.71 | 71317336.32 |
September | 0.605404E+09 | 0.330361E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4021377.82 | 0.158834E+09 |
October | 0.629366E+09 | 0.355388E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64030.49 | 0.387367E+09 |
November | 0.623221E+09 | 0.382829E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665286E+09 |
December | 0.607235E+09 | 0.389819E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.788642E+09 |
Annual Sum or Average | 0.755252E+10 | 0.424404E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74478103.27 | 0.547783E+10 |
Minimum of Months | 0.570983E+09 | 0.316481E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59265552.22 |
Maximum of Months | 0.682256E+09 | 0.397170E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31553606.71 | 0.920704E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190639E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173226E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142699E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482767.67 | 0.955923E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2854476.40 | 0.563114E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17927444.70 | 0.290341E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44016482.89 | 97640902.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52684416.08 | 0.131283E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5131578.00 | 0.321690E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7227.41 | 0.806709E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144257E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169367E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123104E+09 | 0.113686E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97640902.22 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52684416.08 | 0.190639E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232914E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211782E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175098E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 624673.77 | 0.117889E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3354755.87 | 0.713875E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22589266.54 | 0.371562E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55268624.17 | 0.126570E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67681390.86 | 0.166758E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6627395.97 | 0.399926E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14414.89 | 0.989217E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172409E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202909E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156161E+09 | 0.138979E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126570E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67681390.86 | 0.232914E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234765E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213545E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176498E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139309.17 | 0.120277E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1283806.95 | 0.756859E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18656302.49 | 0.399572E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45665952.61 | 0.144196E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61954171.93 | 0.167228E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5696189.89 | 0.411604E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.988883E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167494E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198882E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133396E+09 | 0.139829E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144196E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61954171.93 | 0.234765E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2699.16 | 01-JAN-21:00 |
February | 1306.65 | 01-FEB-10:09 | 944.20 | 15-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2938.63 | 06-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 751.52 | 02-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2216.28 | 21-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 554.47 | 21-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.18 | 07-APR-13:00 | 1650.13 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 553.83 | 08-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.02 | 29-MAY-11:53 | 963.52 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 540.92 | 29-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.95 | 19-JUN-21:03 | 606.05 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 536.99 | 24-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.50 | 09-JUL-13:52 | 296.59 | 02-JUL-18:33 |
August | 1306.65 | 01-AUG-09:09 | 563.49 | 16-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 348.20 | 04-AUG-21:03 | 384.54 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 666.11 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.07 | 14-SEP-14:00 | 505.26 | 23-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 825.61 | 31-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.49 | 25-OCT-11:00 | 1377.13 | 17-OCT-24:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2169.66 | 22-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2919.05 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 536.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.59 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 348.20 | 2938.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1799.46 | 01-JAN-21:00 |
February | 827.22 | 01-FEB-10:09 | 604.38 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1959.09 | 06-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 531.51 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1478.76 | 21-MAR-21:03 |
April | 827.22 | 03-APR-09:09 | 341.63 | 21-APR-15:00 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.79 | 07-APR-13:00 | 1097.02 | 11-APR-04:00 |
May | 827.22 | 01-MAY-09:09 | 351.28 | 19-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.94 | 29-MAY-11:53 | 643.91 | 03-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.43 | 19-JUN-21:03 | 403.95 | 02-JUN-22:00 |
July | 827.22 | 03-JUL-09:09 | 314.23 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.18 | 09-JUL-13:52 | 211.56 | 02-JUL-18:33 |
August | 827.22 | 01-AUG-09:09 | 341.64 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.35 | 04-AUG-21:03 | 269.42 | 20-AUG-06:00 |
September | 827.22 | 01-SEP-09:09 | 359.20 | 26-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.38 | 14-SEP-14:00 | 388.13 | 10-SEP-08:00 |
October | 827.22 | 02-OCT-09:09 | 527.10 | 31-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.99 | 25-OCT-11:00 | 1007.13 | 08-OCT-08:20 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1446.29 | 22-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1946.02 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.56 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 231.35 | 1959.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2699.20 | 01-JAN-21:00 |
February | 1306.65 | 01-FEB-10:09 | 938.14 | 15-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2938.66 | 06-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 674.69 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2226.39 | 21-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 551.23 | 21-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.09 | 07-APR-13:00 | 1674.80 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 555.10 | 08-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.91 | 29-MAY-11:53 | 977.00 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 545.61 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.78 | 19-JUN-21:03 | 606.68 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 542.14 | 24-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.28 | 09-JUL-13:52 | 305.28 | 02-JUL-18:33 |
August | 1306.65 | 01-AUG-09:09 | 563.47 | 16-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.09 | 04-AUG-21:03 | 387.42 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 581.87 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.94 | 14-SEP-14:00 | 535.77 | 30-SEP-24:00 |
October | 1306.65 | 02-OCT-09:09 | 794.60 | 31-OCT-15:00 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.48 | 25-OCT-11:00 | 1444.79 | 17-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2176.36 | 22-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2919.08 | 31-DEC-21:56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 542.14 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.28 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 347.09 | 2938.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1803.70 | 01-JAN-20:45 |
February | 827.17 | 01-FEB-10:09 | 589.25 | 15-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1959.09 | 06-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 469.58 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1483.08 | 21-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 362.38 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.79 | 07-APR-13:00 | 1114.62 | 11-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 358.03 | 08-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.41 | 29-MAY-11:53 | 657.81 | 03-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 352.44 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.90 | 19-JUN-21:03 | 466.97 | 03-JUN-19:00 |
July | 827.17 | 03-JUL-09:09 | 352.06 | 24-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.19 | 09-JUL-13:52 | 276.95 | 02-JUL-17:50 |
August | 827.17 | 01-AUG-09:09 | 363.28 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.20 | 04-AUG-21:03 | 262.07 | 20-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 447.97 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.38 | 14-SEP-14:00 | 363.04 | 10-SEP-20:00 |
October | 827.17 | 02-OCT-09:09 | 507.61 | 06-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.99 | 25-OCT-11:00 | 942.65 | 17-OCT-22:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1446.21 | 22-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1946.02 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 352.06 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.07 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 230.20 | 1959.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1535.03 | 31-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 940.52 | 15-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1559.66 | 06-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 739.73 | 02-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1183.35 | 21-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 550.36 | 21-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.16 | 07-APR-13:00 | 952.52 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 549.67 | 08-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.78 | 29-MAY-11:53 | 536.05 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 536.13 | 29-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.05 | 19-JUN-21:03 | 329.53 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 532.02 | 24-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.93 | 09-JUL-13:52 | 154.73 | 11-JUL-05:00 |
August | 1306.65 | 01-AUG-09:09 | 559.80 | 16-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.27 | 04-AUG-21:03 | 221.93 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 583.18 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.56 | 14-SEP-14:00 | 299.57 | 23-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 817.37 | 31-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.24 | 25-OCT-11:00 | 861.07 | 08-OCT-08:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1290.41 | 23-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1572.77 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 532.02 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.73 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 187.27 | 1572.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1033.59 | 31-JAN-01:00 |
February | 827.22 | 01-FEB-10:09 | 602.69 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1059.31 | 05-FEB-08:30 |
March | 827.22 | 01-MAR-10:09 | 527.65 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 819.04 | 12-MAR-10:00 |
April | 827.22 | 03-APR-09:09 | 338.94 | 21-APR-15:00 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 | 07-APR-13:00 | 651.51 | 11-APR-04:00 |
May | 827.22 | 01-MAY-09:09 | 348.95 | 19-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.26 | 29-MAY-11:53 | 377.86 | 03-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.61 | 19-JUN-21:03 | 229.13 | 02-JUN-22:00 |
July | 827.22 | 03-JUL-09:09 | 314.23 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.19 | 09-JUL-13:52 | 109.71 | 11-JUL-05:00 |
August | 827.22 | 01-AUG-09:09 | 338.63 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.51 | 04-AUG-21:03 | 160.50 | 20-AUG-06:00 |
September | 827.22 | 01-SEP-09:09 | 357.25 | 26-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.04 | 14-SEP-14:00 | 203.04 | 30-SEP-24:00 |
October | 827.22 | 02-OCT-09:09 | 523.04 | 31-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 25-OCT-11:00 | 636.08 | 08-OCT-08:00 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 876.03 | 23-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1056.92 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.71 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 123.51 | 1059.31 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 27435.82 | 02-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 934.14 | 15-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 29875.77 | 06-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 584.21 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 22031.85 | 23-MAR-06:01 |
April | 1306.65 | 03-APR-09:09 | 546.93 | 21-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1704.60 | 07-APR-17:00 | 15354.56 | 03-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 551.02 | 08-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4106.74 | 30-MAY-12:00 | 11090.67 | 01-MAY-06:10 |
June | 1306.65 | 01-JUN-09:09 | 541.10 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9204.52 | 19-JUN-11:02 | 7110.91 | 02-JUN-06:02 |
July | 1306.65 | 03-JUL-09:09 | 537.47 | 24-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7139.48 | 07-JUL-11:03 | 2603.08 | 11-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 559.77 | 16-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7389.75 | 24-AUG-16:05 | 4759.23 | 25-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 579.02 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4439.03 | 14-SEP-16:10 | 9736.00 | 11-SEP-06:01 |
October | 1306.65 | 02-OCT-09:09 | 784.77 | 31-OCT-15:00 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 661.29 | 25-OCT-11:10 | 13620.39 | 31-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 21660.05 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 22259.58 | 22-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 537.47 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2603.08 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 9204.52 | 29875.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1035.22 | 31-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 586.98 | 15-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1039.77 | 06-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 463.79 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 794.35 | 21-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 360.76 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 | 07-APR-13:00 | 673.10 | 11-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 356.00 | 08-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.47 | 29-MAY-11:53 | 381.64 | 03-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 350.18 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.51 | 19-JUN-21:03 | 241.27 | 03-JUN-19:00 |
July | 827.17 | 03-JUL-09:09 | 349.80 | 24-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.37 | 09-JUL-13:52 | 129.73 | 02-JUL-17:50 |
August | 827.17 | 01-AUG-09:09 | 361.47 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.98 | 04-AUG-21:03 | 160.17 | 20-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 441.55 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.04 | 14-SEP-14:00 | 212.42 | 30-SEP-24:00 |
October | 827.17 | 02-OCT-09:09 | 502.98 | 06-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 25-OCT-11:00 | 590.14 | 08-OCT-08:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 866.19 | 23-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1060.88 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 349.80 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.73 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 122.98 | 1060.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2316.92 | 31-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 944.19 | 15-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2444.01 | 06-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 751.50 | 02-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1854.59 | 21-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 554.46 | 21-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.25 | 07-APR-13:00 | 1489.20 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 553.82 | 08-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.62 | 29-MAY-12:00 | 872.50 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 540.91 | 29-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.21 | 19-JUN-21:03 | 525.12 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 536.98 | 24-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.42 | 09-JUL-13:52 | 248.16 | 11-JUL-05:00 |
August | 1306.65 | 01-AUG-09:09 | 563.48 | 16-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 297.88 | 12-AUG-19:00 | 346.42 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 666.07 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.96 | 14-SEP-14:00 | 450.88 | 23-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 825.59 | 31-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.09 | 25-OCT-11:00 | 1250.74 | 08-OCT-08:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1905.24 | 23-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2404.14 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 536.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.16 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 297.88 | 2444.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 658.76 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1543.88 | 31-JAN-01:00 |
February | 805.43 | 01-FEB-08:09 | 604.37 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1629.33 | 06-FEB-00:57 |
March | 805.43 | 01-MAR-08:09 | 531.50 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1298.13 | 12-MAR-10:00 |
April | 805.43 | 03-APR-07:10 | 341.62 | 21-APR-15:00 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 07-APR-13:00 | 990.59 | 11-APR-04:00 |
May | 805.43 | 01-MAY-07:10 | 351.28 | 19-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.53 | 29-MAY-11:55 | 583.11 | 03-MAY-04:00 |
June | 805.43 | 01-JUN-07:10 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.93 | 19-JUN-21:03 | 350.78 | 02-JUN-22:00 |
July | 805.43 | 03-JUL-07:10 | 314.23 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.36 | 09-JUL-13:26 | 168.79 | 11-JUL-05:00 |
August | 805.43 | 01-AUG-07:10 | 341.63 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.83 | 12-AUG-19:00 | 242.37 | 20-AUG-06:00 |
September | 805.43 | 01-SEP-07:10 | 359.20 | 26-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.11 | 14-SEP-14:10 | 313.03 | 10-SEP-07:50 |
October | 805.43 | 02-OCT-07:10 | 527.09 | 31-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.39 | 25-OCT-11:00 | 941.81 | 08-OCT-08:00 |
November | 805.43 | 01-NOV-07:10 | 658.76 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1270.54 | 23-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 658.76 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1602.92 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.79 | |||||
Maximum of Months | 805.43 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 193.83 | 1629.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2397.15 | 31-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 938.13 | 15-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2444.02 | 06-FEB-00:57 |
March | 1306.65 | 01-MAR-10:09 | 674.66 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1951.67 | 12-MAR-10:00 |
April | 1306.65 | 03-APR-09:09 | 551.22 | 21-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.19 | 07-APR-13:00 | 1509.24 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 555.09 | 08-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.88 | 29-MAY-11:55 | 883.56 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 545.60 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.04 | 19-JUN-21:03 | 525.83 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 542.13 | 24-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.24 | 09-JUL-13:50 | 244.42 | 11-JUL-05:00 |
August | 1306.65 | 01-AUG-09:09 | 563.46 | 16-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 291.70 | 12-AUG-19:00 | 348.80 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 581.86 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.85 | 14-SEP-14:00 | 476.11 | 30-SEP-24:00 |
October | 1306.65 | 02-OCT-09:09 | 794.58 | 31-OCT-15:00 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.05 | 25-OCT-11:00 | 1350.05 | 08-OCT-08:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1955.56 | 23-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2418.03 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 542.13 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.42 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 291.70 | 2444.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1546.64 | 31-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 589.24 | 15-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1629.33 | 06-FEB-00:57 |
March | 827.17 | 01-MAR-10:09 | 469.56 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1241.87 | 21-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 362.37 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.84 | 07-APR-13:00 | 1004.52 | 11-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 358.03 | 08-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.40 | 29-MAY-12:00 | 594.36 | 03-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 352.44 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.02 | 19-JUN-21:03 | 386.26 | 03-JUN-19:00 |
July | 827.17 | 03-JUL-09:09 | 352.05 | 24-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.63 | 09-JUL-13:26 | 214.41 | 02-JUL-17:40 |
August | 827.17 | 01-AUG-09:09 | 363.28 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.78 | 04-AUG-21:03 | 235.87 | 20-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 447.95 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.64 | 14-SEP-14:00 | 313.61 | 30-SEP-24:00 |
October | 827.17 | 02-OCT-09:09 | 507.59 | 06-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.40 | 25-OCT-11:00 | 845.90 | 17-OCT-24:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1268.56 | 23-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1603.82 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 352.05 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.41 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 192.78 | 1629.33 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3405.72 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3368.14 | 06-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2527.64 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.39 | 07-APR-13:00 | 2154.74 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.05 | 29-MAY-11:53 | 1250.45 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.05 | 19-JUN-21:03 | 714.73 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.71 | 09-JUL-14:00 | 325.09 | 11-JUL-05:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.52 | 12-AUG-18:55 | 475.43 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.19 | 14-SEP-14:00 | 639.91 | 30-SEP-24:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.15 | 25-OCT-11:00 | 1845.79 | 08-OCT-07:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2842.27 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3463.41 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.09 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.52 | 3463.41 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4170.16 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4070.48 | 06-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3160.91 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.63 | 07-APR-13:00 | 2711.31 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.49 | 29-MAY-12:00 | 1564.39 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.11 | 19-JUN-21:03 | 913.11 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.56 | 09-JUL-13:52 | 416.01 | 11-JUL-05:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458.21 | 12-AUG-19:00 | 600.50 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.45 | 14-SEP-14:00 | 795.00 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.97 | 25-OCT-11:00 | 2263.06 | 17-OCT-24:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3453.73 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4153.18 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.01 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458.21 | 4170.16 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3951.95 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4052.32 | 06-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3304.71 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.26 | 08-APR-10:00 | 2503.52 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.89 | 30-MAY-13:00 | 1459.89 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.86 | 19-JUN-21:03 | 900.50 | 03-JUN-18:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.96 | 07-JUL-22:00 | 540.01 | 02-JUL-18:33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496.21 | 04-AUG-21:03 | 533.24 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.49 | 14-SEP-14:00 | 762.27 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2106.79 | 17-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3176.17 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4064.37 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533.24 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496.21 | 4064.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12163.72 | 27-JAN-08:30 | 12070.02 | 9872.03 | 36370.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13045.71 | 24-FEB-08:20 | 12070.02 | 9872.03 | 36370.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16665.53 | 16-MAR-07:03 | 54315.07 | 44424.13 | 163666.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33375.67 | 10-APR-06:03 | 5082.11 | 6581.44 | 35187.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40832.29 | 30-MAY-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 44806.08 | 19-JUN-05:03 | 3811.58 | 1270.40 | 29937.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 44989.83 | 25-JUL-05:03 | 3811.58 | 1270.40 | 29937.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 42513.81 | 07-AUG-05:12 | 3176.32 | 2742.16 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 40829.55 | 11-SEP-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38577.56 | 16-OCT-06:01 | 10164.22 | 13162.88 | 70374.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19258.77 | 03-NOV-16:00 | 6035.01 | 4936.01 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16755.80 | 21-DEC-08:05 | 60350.08 | 49360.15 | 181851.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12163.72 | 2541.06 | 1270.40 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44989.83 | 60350.08 | 49360.15 | 181851.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 153.94 | 17-JAN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.23 |
February | 419.09 | 18-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.51 |
March | 2753.51 | 03-MAR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.08 |
April | 7343.02 | 07-APR-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.88 | 0.00 |
May | 10992.95 | 30-MAY-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.84 | 0.00 |
June | 12254.78 | 19-JUN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.27 | 0.00 |
July | 11415.84 | 10-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.03 | 0.00 |
August | 10931.72 | 01-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.37 | 0.00 |
September | 9663.78 | 01-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.66 | 0.00 |
October | 6817.42 | 04-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.37 |
November | 2334.77 | 03-NOV-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.35 |
December | 141.52 | 16-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 141.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12254.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.03 | 322.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2269.28 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1940.78 |
February | 2127.44 | 09-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2322.53 |
March | 1672.88 | 22-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 637.42 |
April | 2306.39 | 10-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.85 |
May | 5255.04 | 30-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.45 | 0.00 |
June | 5307.83 | 19-JUN-12:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.72 | 0.00 |
July | 5625.55 | 10-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.16 | 0.00 |
August | 5745.08 | 14-AUG-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.84 | 0.00 |
September | 5394.64 | 05-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.86 | 0.00 |
October | 3208.13 | 04-OCT-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.14 |
November | 1253.21 | 15-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.76 |
December | 1544.75 | 23-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1253.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5745.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.72 | 2322.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1617.76 | 25-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.47 |
February | 1979.85 | 15-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.58 |
March | 2308.15 | 09-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.79 |
April | 2710.14 | 10-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.77 |
May | 5531.67 | 30-MAY-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.53 | 0.00 |
June | 6065.64 | 19-JUN-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.60 | 0.00 |
July | 6469.72 | 10-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.49 | 0.00 |
August | 5820.03 | 14-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.41 | 0.00 |
September | 5578.00 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.87 |
October | 3843.59 | 04-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.79 |
November | 1497.01 | 03-NOV-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.25 |
December | 1801.11 | 21-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1497.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6469.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.60 | 366.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6066.76 | 20-JAN-17:00 | 12070.02 | 9872.03 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6089.12 | 24-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9379.01 | 29-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13983.26 | 10-APR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29761.18 | 30-MAY-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33241.07 | 19-JUN-05:03 | 3811.58 | 1270.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33149.57 | 25-JUL-05:03 | 3811.58 | 1270.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32978.81 | 14-AUG-05:14 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32395.93 | 05-SEP-05:14 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15185.30 | 05-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11316.07 | 03-NOV-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6255.35 | 21-DEC-16:25 | 12070.02 | 9872.03 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6066.76 | 2541.06 | 1270.40 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33241.07 | 12070.02 | 9872.03 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5754.58 | 20-JAN-16:40 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5835.13 | 24-FEB-16:50 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9039.15 | 29-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14866.84 | 10-APR-15:50 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31852.43 | 30-MAY-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35811.57 | 19-JUN-05:03 | 3811.58 | 1270.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32567.10 | 24-JUL-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32991.09 | 07-AUG-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32625.78 | 05-SEP-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15762.57 | 04-OCT-15:40 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10109.87 | 03-NOV-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5749.39 | 21-DEC-16:25 | 12070.02 | 9872.03 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5749.39 | 2541.06 | 1270.40 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35811.57 | 12070.02 | 9872.03 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 943.70 | 20-JAN-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.41 |
February | 968.31 | 17-FEB-15:50 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.44 |
March | 1493.23 | 27-MAR-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.65 |
April | 4063.82 | 07-APR-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.56 | 0.00 |
May | 8302.96 | 30-MAY-06:03 | 803.52 | 496.35 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.42 |
June | 9542.96 | 26-JUN-06:03 | 803.52 | 496.35 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.10 |
July | 11071.21 | 16-JUL-14:32 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 130.66 | 0.00 |
August | 11645.44 | 13-AUG-15:12 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 120.40 | 0.00 |
September | 9607.15 | 04-SEP-13:21 | 468.72 | 193.02 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.21 |
October | 4187.34 | 04-OCT-13:50 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 | 0.00 |
November | 1508.27 | 03-NOV-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.94 |
December | 971.48 | 20-DEC-14:10 | 1306.65 | 534.28 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 943.70 | 267.84 | 110.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11645.44 | 1306.65 | 534.28 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 130.66 | 159.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 751.09 | 19-JAN-10:20 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.70 |
February | 777.32 | 22-FEB-10:10 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.23 |
March | 3432.57 | 29-MAR-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.12 |
April | 6243.47 | 28-APR-08:50 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.17 |
May | 13395.78 | 29-MAY-08:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 |
June | 12798.22 | 25-JUN-08:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.67 |
July | 13479.37 | 02-JUL-08:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.43 |
August | 12886.38 | 13-AUG-09:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 34.66 | 0.00 |
September | 14615.27 | 04-SEP-09:21 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.44 |
October | 5520.14 | 05-OCT-09:20 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.21 |
November | 1983.03 | 03-NOV-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.44 |
December | 782.18 | 20-DEC-10:10 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 751.09 | 211.95 | 87.28 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14615.27 | 1654.44 | 628.45 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.66 | 229.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5708.20 | 19-JAN-13:25 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.57 |
February | 6193.77 | 02-FEB-14:00 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.89 |
March | 8856.51 | 03-MAR-13:30 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.67 |
April | 10090.31 | 07-APR-12:30 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 29.49 | 0.00 |
May | 12933.49 | 29-MAY-12:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 79.66 | 0.00 |
June | 13089.74 | 18-JUN-14:02 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.98 |
July | 16406.84 | 04-JUL-12:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 52.08 | 0.00 |
August | 16634.82 | 13-AUG-12:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 137.45 | 0.00 |
September | 18524.07 | 04-SEP-12:01 | 468.72 | 193.02 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.26 |
October | 17393.40 | 22-OCT-12:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.82 |
November | 10728.77 | 02-NOV-13:05 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.03 |
December | 5914.74 | 21-DEC-13:25 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5708.20 | 267.84 | 110.30 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18524.07 | 2613.31 | 992.69 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 137.45 | 307.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1204.50 | 20-JAN-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.14 |
February | 1909.40 | 24-FEB-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.27 |
March | 5339.32 | 29-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.31 |
April | 11599.57 | 09-APR-15:43 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.25 |
May | 11481.61 | 14-MAY-16:03 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.44 |
June | 14889.69 | 18-JUN-16:02 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.52 |
July | 14880.52 | 02-JUL-16:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.84 |
August | 14593.86 | 13-AUG-15:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 59.01 | 0.00 |
September | 15078.36 | 03-SEP-16:02 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.67 |
October | 10525.86 | 15-OCT-15:32 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.05 |
November | 3624.21 | 03-NOV-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.71 |
December | 866.14 | 08-DEC-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 866.14 | 169.55 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15078.36 | 805.38 | 314.21 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 59.01 | 400.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 949.39 | 20-JAN-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.71 |
February | 956.90 | 24-FEB-14:10 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.82 |
March | 1242.77 | 28-MAR-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.92 |
April | 2209.13 | 10-APR-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.90 |
May | 4553.14 | 30-MAY-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 29.90 | 0.00 |
June | 7569.91 | 26-JUN-06:03 | 803.52 | 496.35 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 |
July | 7606.10 | 17-JUL-06:03 | 803.52 | 496.35 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.76 |
August | 7571.29 | 14-AUG-06:03 | 803.52 | 496.35 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.36 |
September | 7006.12 | 05-SEP-06:03 | 1071.35 | 727.79 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.70 |
October | 3769.77 | 05-OCT-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 |
November | 1587.00 | 03-NOV-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.21 |
December | 1033.65 | 20-DEC-14:10 | 1306.65 | 529.74 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 949.39 | 803.52 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7606.10 | 1306.65 | 727.79 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 29.90 | 150.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 747.76 | 27-JAN-10:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.20 |
February | 748.63 | 22-FEB-10:10 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.09 |
March | 2241.31 | 29-MAR-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.21 |
April | 4242.57 | 28-APR-09:10 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.10 |
May | 9265.52 | 29-MAY-08:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.63 |
June | 8958.09 | 04-JUN-10:32 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.69 |
July | 9951.65 | 09-JUL-09:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 28.53 | 0.00 |
August | 10922.87 | 20-AUG-09:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.82 |
September | 11213.16 | 10-SEP-09:12 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.47 |
October | 4994.03 | 05-OCT-09:20 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.99 |
November | 2371.56 | 03-NOV-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.69 |
December | 831.66 | 20-DEC-10:00 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 747.76 | 169.56 | 69.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11213.16 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 28.53 | 129.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1429.91 | 19-JAN-14:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1819.12 |
February | 2309.57 | 25-FEB-13:10 | 133.92 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.20 |
March | 5812.13 | 03-MAR-13:20 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1153.76 |
April | 6974.04 | 07-APR-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1302.46 | 0.00 |
May | 10851.79 | 30-MAY-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4106.74 | 0.00 |
June | 12443.37 | 19-JUN-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8449.63 | 0.00 |
July | 11874.73 | 07-JUL-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 6778.77 | 0.00 |
August | 13589.14 | 20-AUG-13:12 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 13.05 | 0.00 |
September | 13989.81 | 10-SEP-13:12 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.51 |
October | 13812.20 | 15-OCT-12:52 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.33 |
November | 8354.50 | 02-NOV-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 959.37 |
December | 3370.46 | 17-DEC-13:40 | 133.92 | 55.15 | 956.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1429.91 | 133.92 | 55.15 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13989.81 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 8449.63 | 1819.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 858.93 | 20-JAN-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.61 |
February | 1166.91 | 22-FEB-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.70 |
March | 3353.35 | 27-MAR-16:50 | 254.33 | 174.56 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 |
April | 6421.73 | 09-APR-16:43 | 127.16 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
May | 7272.88 | 27-MAY-17:42 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.43 |
June | 11283.80 | 04-JUN-15:52 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.05 |
July | 11295.84 | 02-JUL-16:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.64 |
August | 11680.43 | 20-AUG-16:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.56 |
September | 12084.36 | 10-SEP-16:31 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.21 |
October | 8679.39 | 15-OCT-15:32 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.42 |
November | 3422.08 | 03-NOV-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.45 |
December | 859.53 | 08-DEC-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 858.93 | 127.16 | 52.37 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | |
Maximum of Months | 12084.36 | 805.38 | 314.21 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1012.90 | 20-JAN-15:10 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.93 |
February | 1029.44 | 24-FEB-15:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.15 |
March | 1520.51 | 28-MAR-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.74 |
April | 3587.17 | 07-APR-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.93 | 0.00 |
May | 8341.43 | 30-MAY-06:03 | 803.52 | 496.35 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.44 |
June | 8504.23 | 26-JUN-05:12 | 669.60 | 275.74 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.75 |
July | 10110.03 | 09-JUL-16:02 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 | 0.00 |
August | 8339.46 | 14-AUG-06:03 | 803.52 | 496.35 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.69 |
September | 7784.77 | 05-SEP-06:03 | 1071.35 | 733.38 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.24 |
October | 4023.95 | 05-OCT-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.19 |
November | 1836.94 | 03-NOV-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.49 |
December | 1057.60 | 20-DEC-14:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1012.90 | 401.76 | 165.44 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10110.03 | 1306.65 | 733.38 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 19.93 | 259.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 814.68 | 19-JAN-10:00 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.14 |
February | 864.34 | 22-FEB-09:50 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.37 |
March | 5545.75 | 29-MAR-12:02 | 4832.57 | 1885.36 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.98 |
April | 6699.10 | 28-APR-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.23 |
May | 12950.31 | 29-MAY-08:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.64 |
June | 13874.59 | 25-JUN-08:42 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.01 |
July | 14408.60 | 02-JUL-09:01 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.33 |
August | 13080.79 | 27-AUG-09:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.55 |
September | 13706.06 | 10-SEP-08:32 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.71 |
October | 6483.83 | 04-OCT-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.54 |
November | 5224.48 | 01-NOV-12:02 | 4832.57 | 1885.36 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.12 |
December | 982.19 | 20-DEC-09:35 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 814.68 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.54 | |
Maximum of Months | 14408.60 | 4832.57 | 1885.36 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6016.12 | 19-JAN-13:25 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.57 |
February | 6648.82 | 02-FEB-13:40 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.63 |
March | 8758.02 | 29-MAR-13:00 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.92 |
April | 9505.73 | 07-APR-12:30 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 24.81 | 0.00 |
May | 14974.88 | 29-MAY-11:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 70.55 | 0.00 |
June | 10190.17 | 18-JUN-13:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.60 |
July | 14915.01 | 09-JUL-13:22 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 148.13 | 0.00 |
August | 15463.62 | 20-AUG-12:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 |
September | 16126.15 | 10-SEP-12:32 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.56 |
October | 15240.54 | 22-OCT-12:02 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.94 |
November | 11065.41 | 02-NOV-12:40 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.80 |
December | 6962.45 | 21-DEC-13:15 | 5088.93 | 1985.38 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6016.12 | 267.84 | 110.30 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16126.15 | 5088.93 | 1985.38 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 148.13 | 255.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1411.02 | 20-JAN-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.61 |
February | 2302.46 | 24-FEB-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.02 |
March | 5387.46 | 29-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.38 |
April | 11357.31 | 09-APR-15:43 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.28 |
May | 13297.84 | 21-MAY-15:22 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.95 |
June | 13979.47 | 25-JUN-16:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.91 |
July | 13945.37 | 02-JUL-16:21 | 339.11 | 139.64 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.44 |
August | 13897.99 | 20-AUG-16:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.17 |
September | 14529.55 | 10-SEP-15:51 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.15 |
October | 7240.75 | 04-OCT-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 |
November | 3806.03 | 03-NOV-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.12 |
December | 1230.24 | 08-DEC-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1230.24 | 169.55 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 | |
Maximum of Months | 14529.55 | 805.38 | 314.21 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.28 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.139339E+12 | 246609.27 | 02-JAN-07:10 | 0.570010E+11 | 99524.23 | 02-JAN-08:00 |
February | 0.116615E+12 | 212010.97 | 06-FEB-07:10 | 0.557090E+11 | 99641.29 | 06-FEB-08:20 |
March | 0.104041E+12 | 139209.03 | 13-MAR-06:10 | 0.374003E+11 | 68885.47 | 23-MAR-06:10 |
April | 0.919446E+11 | 106961.04 | 03-APR-06:10 | 0.175245E+11 | 41538.44 | 03-APR-06:00 |
May | 0.104843E+12 | 152460.91 | 30-MAY-14:09 | 0.111846E+11 | 20214.91 | 01-MAY-06:19 |
June | 0.135797E+12 | 165783.35 | 19-JUN-12:09 | 0.104891E+11 | 9800.55 | 01-JUN-11:00 |
July | 0.154523E+12 | 156245.34 | 07-JUL-14:30 | 0.101608E+11 | 9686.43 | 03-JUL-11:50 |
August | 0.163371E+12 | 160172.05 | 16-AUG-15:09 | 0.105521E+11 | 9652.32 | 31-AUG-11:09 |
September | 0.119461E+12 | 138367.53 | 07-SEP-15:20 | 0.100289E+11 | 9722.69 | 29-SEP-11:30 |
October | 0.104633E+12 | 115933.28 | 04-OCT-15:30 | 0.118315E+11 | 34992.92 | 28-OCT-06:30 |
November | 0.100198E+12 | 150998.41 | 24-NOV-07:10 | 0.269175E+11 | 73987.70 | 24-NOV-07:30 |
December | 0.114464E+12 | 158946.88 | 26-DEC-07:10 | 0.462068E+11 | 71534.37 | 22-DEC-07:30 |
Annual Sum or Average | 0.144923E+13 | 0.305006E+12 | ||||
Minimum of Months | 0.919446E+11 | 106961.04 | 0.100289E+11 | 9652.32 | ||
Maximum of Months | 0.163371E+12 | 246609.27 | 0.570010E+11 | 99641.29 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.200980E+11 | 0.583101E+10 | 0.593559E+11 | 0.983103E+09 | 0.381283E+10 | 12379742.02 | 0.492459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178406E+11 | 0.466989E+10 | 0.537310E+11 | 0.889346E+09 | 0.332333E+10 | 11196021.66 | 0.361493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208805E+11 | 0.435457E+10 | 0.617796E+11 | 0.102909E+10 | 0.382928E+10 | 12675672.10 | 0.117708E+11 | 0.384521E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.184198E+11 | 0.349082E+10 | 0.572952E+11 | 0.946215E+09 | 0.463557E+10 | 11960507.72 | 0.360219E+10 | 0.354290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197790E+11 | 0.313503E+10 | 0.605677E+11 | 0.100558E+10 | 0.762976E+10 | 12527707.06 | 0.415562E+09 | 0.122982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.196162E+11 | 0.283034E+10 | 0.594895E+11 | 0.989893E+09 | 0.127037E+11 | 12231776.97 | 1698669.39 | 0.401530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.183642E+11 | 0.300505E+10 | 0.583622E+11 | 0.961681E+09 | 0.159787E+11 | 12256437.81 | 0.00 | 0.578389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.205553E+11 | 0.336878E+10 | 0.617796E+11 | 0.102892E+10 | 0.176448E+11 | 12675672.10 | 0.00 | 0.589808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.185096E+11 | 0.386937E+10 | 0.572729E+11 | 0.946029E+09 | 0.102194E+11 | 11960507.72 | 13975739.74 | 0.286175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194288E+11 | 0.483138E+10 | 0.593671E+11 | 0.982559E+09 | 0.732502E+10 | 12379742.02 | 0.438354E+09 | 0.122477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197204E+11 | 0.542578E+10 | 0.580818E+11 | 0.964764E+09 | 0.368092E+10 | 12059151.09 | 0.117342E+11 | 0.577548E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195263E+11 | 0.601184E+10 | 0.583511E+11 | 0.962533E+09 | 0.336440E+10 | 12256437.81 | 0.262353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232739E+12 | 0.508239E+11 | 0.705434E+12 | 0.116897E+11 | 0.941476E+11 | 0.146559E+09 | 0.139607E+12 | 0.214641E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.178406E+11 | 0.283034E+10 | 0.537310E+11 | 0.889346E+09 | 0.332333E+10 | 11196021.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.208805E+11 | 0.601184E+10 | 0.617796E+11 | 0.102909E+10 | 0.176448E+11 | 12675672.10 | 0.492459E+11 | 0.589808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.453129E+11 | 0.00 | 0.116881E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.450796E+11 | 0.00 | 0.106294E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.253898E+11 | 0.00 | 0.120105E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.660600E+10 | 0.00 | 0.109185E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 95010094.14 | 0.00 | 0.110896E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.104891E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.101608E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.105521E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 1833288.50 | 0.00 | 0.100271E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.117119E+10 | 0.00 | 0.106603E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.161420E+11 | 0.00 | 0.107755E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.349389E+11 | 0.00 | 0.112679E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.174737E+12 | 0.00 | 0.130269E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.100271E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.453129E+11 | 0.00 | 0.120105E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 25003.79 | 02-JAN-16:40 | 5686.19 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 838.79 | 02-JAN-16:49 | 7133.95 | 02-JAN-06:19 | 6.85 | 02-JAN-12:20 | 204974.91 | 02-JAN-06:19 |
February | 24009.70 | 15-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 837.09 | 15-FEB-16:00 | 5271.50 | 06-FEB-06:10 | 6.85 | 02-FEB-06:19 | 177898.13 | 06-FEB-07:10 |
March | 21339.46 | 02-MAR-16:00 | 5686.19 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 835.28 | 16-MAR-07:19 | 5327.26 | 29-MAR-15:30 | 6.85 | 07-MAR-06:19 | 104787.63 | 20-MAR-06:10 |
April | 20132.52 | 21-APR-07:10 | 5686.19 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 833.68 | 21-APR-07:19 | 13513.34 | 10-APR-15:09 | 6.85 | 04-APR-07:10 | 75665.09 | 03-APR-06:10 |
May | 20181.62 | 08-MAY-07:10 | 3328.83 | 01-MAY-18:49 | 45864.70 | 01-MAY-07:10 | 833.75 | 08-MAY-07:19 | 27039.18 | 30-MAY-14:20 | 6.85 | 27-MAY-16:10 | 19635.66 | 01-MAY-06:10 |
June | 20056.07 | 29-JUN-07:10 | 3328.83 | 01-JUN-19:19 | 45864.70 | 01-JUN-07:10 | 833.58 | 29-JUN-07:19 | 26090.61 | 19-JUN-10:30 | 6.85 | 03-JUN-16:10 | 713.20 | 02-JUN-06:10 |
July | 20032.37 | 24-JUL-07:10 | 3328.83 | 01-JUL-19:30 | 45864.70 | 03-JUL-07:10 | 833.55 | 24-JUL-07:19 | 27138.14 | 10-JUL-15:30 | 6.85 | 01-JUL-16:10 | 0.00 | 01-JUL-00:10 |
August | 20291.44 | 16-AUG-07:10 | 5686.19 | 16-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 833.89 | 16-AUG-07:19 | 26589.73 | 14-AUG-15:09 | 6.85 | 13-AUG-15:09 | 0.00 | 01-AUG-00:10 |
September | 20877.95 | 27-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 834.67 | 27-SEP-07:19 | 22432.32 | 05-SEP-15:20 | 6.85 | 01-SEP-05:10 | 1723.32 | 20-SEP-06:10 |
October | 22695.91 | 31-OCT-15:00 | 5686.19 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 836.70 | 06-OCT-07:19 | 16142.79 | 04-OCT-15:50 | 6.85 | 16-OCT-06:10 | 20611.54 | 31-OCT-06:10 |
November | 25003.79 | 06-NOV-16:49 | 5686.19 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 838.79 | 06-NOV-16:00 | 7063.93 | 03-NOV-14:09 | 6.85 | 07-NOV-17:10 | 118949.76 | 24-NOV-07:10 |
December | 25003.79 | 01-DEC-16:30 | 5686.19 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 838.79 | 01-DEC-16:40 | 3614.05 | 11-DEC-07:10 | 6.85 | 02-DEC-06:10 | 119983.28 | 26-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 20032.37 | 3328.83 | 45864.70 | 833.55 | 3614.05 | 6.85 | 0.00 | |||||||
Maximum of Months | 25003.79 | 5686.19 | 45864.70 | 838.79 | 27138.14 | 6.85 | 204974.91 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15925.16 | 27-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31919.49 | 07-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 65159.82 | 30-MAY-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 81560.05 | 19-JUN-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 70715.56 | 07-JUL-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75589.98 | 16-AUG-12:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 59232.69 | 07-SEP-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 41817.98 | 04-OCT-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7489.12 | 03-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 81560.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 246609.27 | 02-JAN-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 7067.37 | 6.85 | 204171.65 | 0.00 | 0.00 |
February | 212010.97 | 06-FEB-07:10 | 7492.97 | 21098.80 | 0.00 | 243.70 | 5270.52 | 6.85 | 177898.13 | 0.00 | 0.00 |
March | 139209.03 | 13-MAR-06:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 3252.98 | 6.85 | 100585.80 | 0.00 | 0.00 |
April | 106961.04 | 03-APR-06:10 | 6967.06 | 21098.80 | 0.00 | 243.54 | 2979.71 | 6.85 | 75665.09 | 0.00 | 0.00 |
May | 152460.91 | 30-MAY-14:09 | 19671.42 | 40588.47 | 0.00 | 831.19 | 26220.11 | 6.85 | 0.00 | 65142.88 | 0.00 |
June | 165783.35 | 19-JUN-12:09 | 19671.42 | 42402.18 | 0.00 | 831.83 | 21311.02 | 6.85 | 0.00 | 81560.05 | 0.00 |
July | 156245.34 | 07-JUL-14:30 | 19671.42 | 40588.47 | 0.00 | 831.19 | 24580.22 | 6.85 | 0.00 | 70567.19 | 0.00 |
August | 160172.05 | 16-AUG-15:09 | 19671.42 | 42072.41 | 0.00 | 831.72 | 24327.25 | 6.85 | 0.00 | 73262.41 | 0.00 |
September | 138367.53 | 07-SEP-15:20 | 19671.42 | 42072.41 | 0.00 | 831.72 | 20955.57 | 6.85 | 0.00 | 54829.56 | 0.00 |
October | 115933.28 | 04-OCT-15:30 | 19671.42 | 42072.41 | 0.00 | 831.72 | 15262.88 | 6.85 | 0.00 | 38088.00 | 0.00 |
November | 150998.41 | 24-NOV-07:10 | 7120.16 | 21098.80 | 0.00 | 243.57 | 3579.28 | 6.85 | 118949.76 | 0.00 | 0.00 |
December | 158946.88 | 26-DEC-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 3593.35 | 6.85 | 119983.28 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 106961.04 | 6967.06 | 21098.80 | 0.00 | 243.54 | 2979.71 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 246609.27 | 19671.42 | 42402.18 | 5686.19 | 831.83 | 26220.11 | 6.85 | 204171.65 | 81560.05 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 90170.76 | 02-JAN-08:00 | 0.00 | 10195.34 | 30-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 90234.82 | 06-FEB-07:49 | 0.00 | 10203.36 | 06-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 60987.94 | 23-MAR-06:19 | 0.00 | 10176.14 | 02-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 35973.56 | 03-APR-06:19 | 0.00 | 10071.72 | 03-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 12489.07 | 01-MAY-06:10 | 0.00 | 9957.08 | 01-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9800.55 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9686.43 | 03-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9652.32 | 31-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 794.45 | 30-SEP-06:10 | 0.00 | 9722.69 | 29-SEP-11:30 | 0.00 |
October | 0.00 | 0.00 | 26570.23 | 28-OCT-06:00 | 0.00 | 9867.34 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 65159.39 | 24-NOV-07:30 | 0.00 | 9997.59 | 29-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 63206.04 | 22-DEC-07:19 | 0.00 | 10120.68 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9652.32 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 90234.82 | 0.00 | 10203.36 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 19.70 | 1.67 | 19.70 | 0.00 | 19.70 | 0.00 | 19.70 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.18 | 0.00 | 26.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.18 | 0.00 | 26.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.67 | 19.70 | 1.67 | 19.70 | 0.67 | 20.78 | 0.00 | 20.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.70 | 1.67 | 19.70 | 0.50 | 26.18 | 0.00 | 26.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 18.92 | 2.33 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
February | 0.17 | 19.42 | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.00 | 18.95 | 2.50 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 19.42 | 2.33 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 18.63 | 1.83 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
February | 1.17 | 18.20 | 0.67 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.42 | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
December | 0.33 | 19.16 | 0.33 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
Annual Sum or Average | 4.17 | 18.58 | 3.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 19.42 | 1.83 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.00 | 15.90 | 10.67 | 16.27 | 0.00 | 16.27 | 0.00 | 16.27 |
February | 23.00 | 16.14 | 10.00 | 16.55 | 0.00 | 16.55 | 0.00 | 16.55 |
March | 1.17 | 17.50 | 0.33 | 17.87 | 0.00 | 17.87 | 0.00 | 17.87 |
April | 0.17 | 19.19 | 0.17 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.32 | 0.50 | 27.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.41 | 4.00 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.49 | 1.50 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.50 | 16.87 | 0.67 | 17.36 | 0.00 | 17.36 | 0.00 | 17.36 |
December | 6.33 | 16.29 | 3.00 | 16.52 | 0.00 | 16.52 | 0.00 | 16.52 |
Annual Sum or Average | 58.17 | 16.12 | 24.83 | 16.49 | 7.00 | 17.34 | 6.17 | 17.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 25.00 | 19.19 | 10.67 | 19.19 | 4.50 | 27.49 | 4.00 | 27.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.17 | 14.99 | 4.17 | 15.09 | 0.00 | 15.09 | 0.00 | 15.09 |
February | 13.50 | 15.10 | 2.17 | 15.20 | 0.00 | 15.20 | 0.00 | 15.20 |
March | 0.83 | 16.83 | 0.00 | 16.83 | 0.00 | 16.83 | 0.00 | 16.83 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.83 | 6.50 | 27.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.63 | 5.50 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.83 | 12.33 | 27.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.81 | 6.50 | 27.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.83 | 6.17 | 27.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.83 | 16.22 | 0.17 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 |
December | 5.33 | 15.64 | 1.17 | 15.73 | 0.00 | 15.73 | 0.00 | 15.73 |
Annual Sum or Average | 41.67 | 15.20 | 7.67 | 15.29 | 38.00 | 20.73 | 37.00 | 22.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.17 | 16.83 | 4.17 | 16.83 | 13.00 | 27.83 | 12.33 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.17 | 15.31 | 3.50 | 15.57 | 0.00 | 15.57 | 0.00 | 15.57 |
February | 10.33 | 15.54 | 2.00 | 15.79 | 0.00 | 15.79 | 0.00 | 15.79 |
March | 1.00 | 17.36 | 0.17 | 17.65 | 0.00 | 17.65 | 0.00 | 17.65 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.67 | 3.83 | 27.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.51 | 3.83 | 27.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.72 | 8.83 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.98 | 5.17 | 28.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.16 | 5.83 | 28.18 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.74 | 3.00 | 27.74 |
November | 1.17 | 17.04 | 0.17 | 17.32 | 0.00 | 17.32 | 0.00 | 17.32 |
December | 3.50 | 15.93 | 0.83 | 16.05 | 0.00 | 16.05 | 0.00 | 16.05 |
Annual Sum or Average | 30.17 | 15.59 | 6.67 | 15.83 | 32.33 | 21.44 | 30.50 | 23.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.17 | 17.36 | 3.50 | 17.65 | 9.83 | 28.16 | 8.83 | 28.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.67 | 14.92 | 5.50 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
February | 13.50 | 14.95 | 3.17 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
March | 0.83 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.63 | 1.17 | 27.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.75 | 4.17 | 27.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.04 | 3.67 | 28.12 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 28.03 | 7.17 | 28.08 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.04 | 3.83 | 28.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.25 | 3.17 | 28.27 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.60 | 0.67 | 27.60 |
November | 2.00 | 15.76 | 0.17 | 15.70 | 0.00 | 15.70 | 0.00 | 15.70 |
December | 5.83 | 15.66 | 1.50 | 15.70 | 0.00 | 15.70 | 0.00 | 15.70 |
Annual Sum or Average | 41.83 | 15.11 | 10.33 | 15.13 | 33.50 | 20.16 | 23.83 | 21.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.95 | 0.00 | 14.95 |
Maximum of Months | 19.67 | 16.89 | 5.50 | 16.89 | 10.83 | 28.25 | 7.17 | 28.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.67 | 16.66 | 8.17 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 |
February | 4.00 | 18.67 | 2.83 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17.67 | 17.11 | 11.00 | 17.54 | 0.00 | 17.54 | 0.00 | 17.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.67 | 18.67 | 8.17 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.17 | 15.14 | 1.17 | 15.28 | 0.00 | 15.28 | 0.00 | 15.28 |
February | 0.67 | 16.36 | 0.00 | 16.36 | 0.00 | 16.36 | 0.00 | 16.36 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.57 | 3.17 | 27.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.54 | 1.67 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.63 | 6.33 | 27.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.56 | 4.67 | 27.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.67 | 5.00 | 27.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6.83 | 15.26 | 1.17 | 15.37 | 20.83 | 24.21 | 20.83 | 25.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.17 | 16.36 | 1.17 | 16.36 | 6.33 | 27.67 | 6.33 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 60.83 | 17.68 | 56.17 | 17.78 | 0.00 | 17.78 | 0.00 | 17.78 |
February | 54.17 | 17.92 | 53.67 | 17.93 | 0.00 | 17.93 | 0.00 | 17.93 |
March | 33.83 | 18.76 | 33.83 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 |
April | 11.50 | 19.58 | 11.50 | 19.58 | 0.00 | 19.58 | 0.00 | 19.58 |
May | 0.33 | 20.36 | 0.33 | 20.36 | 0.67 | 23.86 | 0.67 | 25.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.62 | 1.00 | 25.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 26.34 | 6.00 | 26.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 25.79 | 11.67 | 25.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 26.57 | 9.67 | 26.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.54 | 4.67 | 27.54 |
November | 17.17 | 19.03 | 17.17 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
December | 45.50 | 18.88 | 45.50 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
Annual Sum or Average | 223.33 | 18.35 | 218.17 | 18.39 | 34.00 | 18.96 | 33.67 | 19.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.78 | 0.00 | 17.78 |
Maximum of Months | 60.83 | 20.36 | 56.17 | 20.36 | 11.83 | 27.54 | 11.67 | 27.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.00 | 15.01 | 2.17 | 15.12 | 0.00 | 15.12 | 0.00 | 15.12 |
February | 0.83 | 16.04 | 0.00 | 16.04 | 0.00 | 16.04 | 0.00 | 16.04 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.39 | 0.17 | 27.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.37 | 1.67 | 27.37 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.67 | 2.50 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.72 | 4.50 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.83 | 2.33 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.85 | 2.67 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.44 | 0.67 | 27.44 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7.83 | 15.12 | 2.17 | 15.19 | 19.50 | 23.47 | 14.50 | 24.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.00 | 16.04 | 2.17 | 16.04 | 6.50 | 27.85 | 4.50 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.00 | 16.01 | 6.50 | 16.31 | 0.00 | 16.31 | 0.00 | 16.31 |
February | 6.67 | 17.03 | 2.67 | 17.71 | 0.00 | 17.71 | 0.00 | 17.71 |
March | 0.17 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.32 | 1.00 | 27.32 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 15.64 | 0.17 | 16.18 | 0.00 | 16.18 | 0.00 | 16.18 |
Annual Sum or Average | 20.83 | 16.33 | 9.33 | 16.75 | 1.17 | 17.14 | 1.17 | 17.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.00 | 17.20 | 6.50 | 17.71 | 1.00 | 27.32 | 1.00 | 27.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.00 | 15.06 | 2.33 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 |
February | 3.33 | 15.53 | 0.17 | 15.70 | 0.00 | 15.70 | 0.00 | 15.70 |
March | 0.17 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.78 | 6.33 | 27.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.67 | 3.83 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.76 | 10.50 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.74 | 5.83 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.89 | 5.17 | 27.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
Annual Sum or Average | 13.17 | 15.20 | 2.50 | 15.27 | 32.67 | 23.71 | 32.33 | 25.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.00 | 17.20 | 2.33 | 17.20 | 10.67 | 27.89 | 10.50 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.67 | 15.35 | 1.83 | 15.55 | 0.00 | 15.55 | 0.00 | 15.55 |
February | 2.50 | 15.64 | 0.17 | 15.84 | 0.00 | 15.84 | 0.00 | 15.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.56 | 2.83 | 27.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.40 | 2.33 | 27.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.60 | 7.33 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.83 | 5.00 | 27.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.06 | 6.00 | 28.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.63 | 4.83 | 27.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
Annual Sum or Average | 10.17 | 15.42 | 2.00 | 15.62 | 28.83 | 24.13 | 28.50 | 25.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.67 | 15.64 | 1.83 | 15.84 | 7.50 | 28.06 | 7.33 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.83 | 15.02 | 3.33 | 15.06 | 0.00 | 15.06 | 0.00 | 15.06 |
February | 3.33 | 15.39 | 0.17 | 15.57 | 0.00 | 15.57 | 0.00 | 15.57 |
March | 0.17 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.63 | 1.00 | 27.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.65 | 4.00 | 27.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.93 | 3.17 | 27.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.95 | 6.00 | 27.99 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.00 | 3.00 | 28.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.09 | 3.00 | 28.12 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.69 | 0.50 | 27.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 |
Annual Sum or Average | 14.00 | 15.13 | 3.50 | 15.18 | 28.33 | 23.04 | 20.67 | 24.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.83 | 17.20 | 3.33 | 17.20 | 8.83 | 28.09 | 6.00 | 28.12 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.66 | 56.17 | 22.39 | 56.17 | 22.18 |
February | 454.00 | 23.28 | 3.50 | 23.26 | 3.50 | 23.24 |
March | 453.67 | 23.78 | 0.00 | 23.78 | 0.00 | 23.78 |
April | 211.67 | 23.85 | 54.67 | 24.11 | 0.00 | 24.11 |
May | 28.67 | 24.00 | 235.33 | 24.53 | 0.00 | 24.53 |
June | 0.00 | 0.00 | 438.67 | 24.44 | 0.00 | 24.44 |
July | 0.00 | 0.00 | 497.00 | 24.46 | 0.00 | 24.46 |
August | 0.00 | 0.00 | 483.67 | 24.45 | 0.00 | 24.45 |
September | 1.17 | 24.00 | 393.50 | 24.52 | 0.00 | 24.52 |
October | 53.00 | 24.04 | 280.50 | 24.42 | 0.00 | 24.42 |
November | 282.17 | 23.67 | 66.67 | 23.94 | 0.00 | 23.94 |
December | 497.00 | 23.51 | 0.00 | 23.51 | 0.00 | 23.51 |
Annual Sum or Average | 2483.33 | 23.41 | 2509.67 | 23.91 | 59.67 | 23.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.39 | 0.00 | 22.18 |
Maximum of Months | 502.00 | 24.04 | 497.00 | 24.53 | 56.17 | 24.53 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.12 | 201.83 | 20.87 | 201.83 | 20.74 |
February | 454.00 | 21.54 | 146.17 | 21.37 | 146.17 | 21.26 |
March | 513.50 | 22.62 | 6.67 | 22.59 | 6.67 | 22.57 |
April | 370.83 | 23.13 | 17.67 | 23.20 | 0.17 | 23.20 |
May | 131.83 | 23.67 | 150.50 | 24.00 | 0.00 | 24.00 |
June | 0.00 | 0.00 | 414.67 | 24.31 | 0.00 | 24.31 |
July | 0.00 | 0.00 | 497.00 | 24.35 | 0.00 | 24.35 |
August | 0.00 | 0.00 | 465.33 | 24.36 | 0.00 | 24.36 |
September | 29.67 | 23.75 | 321.83 | 24.32 | 0.00 | 24.32 |
October | 179.17 | 23.69 | 198.33 | 23.98 | 0.00 | 23.98 |
November | 448.67 | 22.60 | 48.50 | 22.45 | 44.50 | 22.31 |
December | 497.00 | 21.72 | 84.67 | 21.56 | 84.67 | 21.44 |
Annual Sum or Average | 3126.67 | 22.25 | 2553.17 | 22.87 | 484.00 | 22.68 |
Minimum of Months | 0.00 | 0.00 | 6.67 | 20.87 | 0.00 | 20.74 |
Maximum of Months | 513.50 | 23.75 | 497.00 | 24.36 | 201.83 | 24.36 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.56 | 329.67 | 20.37 | 329.67 | 20.29 |
February | 454.00 | 20.86 | 311.50 | 20.70 | 311.50 | 20.63 |
March | 513.83 | 21.89 | 88.67 | 21.70 | 88.67 | 21.56 |
April | 394.50 | 22.59 | 34.17 | 22.56 | 18.33 | 22.47 |
May | 180.83 | 23.41 | 128.67 | 23.77 | 0.00 | 23.77 |
June | 11.00 | 23.68 | 405.33 | 24.28 | 0.00 | 24.28 |
July | 0.00 | 0.00 | 492.83 | 24.38 | 0.00 | 24.38 |
August | 1.50 | 23.71 | 445.17 | 24.36 | 0.00 | 24.36 |
September | 73.67 | 23.43 | 277.00 | 24.13 | 0.00 | 24.13 |
October | 270.00 | 23.11 | 140.00 | 23.43 | 3.67 | 23.41 |
November | 474.50 | 21.80 | 120.50 | 21.50 | 120.17 | 21.30 |
December | 497.00 | 20.89 | 310.67 | 20.70 | 310.67 | 20.62 |
Annual Sum or Average | 3372.83 | 21.70 | 3084.17 | 22.22 | 1182.67 | 21.93 |
Minimum of Months | 0.00 | 0.00 | 34.17 | 20.37 | 0.00 | 20.29 |
Maximum of Months | 513.83 | 23.71 | 492.83 | 24.38 | 329.67 | 24.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.90 | 448.33 | 19.84 | 448.33 | 19.81 |
February | 454.00 | 20.06 | 427.50 | 20.03 | 427.50 | 20.02 |
March | 513.00 | 20.89 | 266.50 | 20.65 | 266.50 | 20.53 |
April | 413.00 | 21.74 | 112.67 | 21.59 | 88.00 | 21.38 |
May | 239.83 | 23.02 | 133.67 | 23.48 | 13.67 | 23.49 |
June | 47.17 | 24.66 | 414.67 | 24.34 | 28.33 | 24.41 |
July | 78.67 | 25.89 | 496.50 | 24.69 | 78.67 | 24.84 |
August | 50.83 | 25.36 | 453.17 | 24.49 | 39.33 | 24.59 |
September | 145.17 | 23.24 | 259.67 | 23.91 | 12.83 | 23.93 |
October | 341.83 | 22.23 | 137.50 | 22.41 | 42.83 | 22.24 |
November | 489.00 | 20.83 | 258.17 | 20.53 | 258.17 | 20.39 |
December | 497.00 | 20.07 | 471.00 | 20.04 | 471.00 | 20.03 |
Annual Sum or Average | 3771.50 | 21.19 | 3879.33 | 21.65 | 2175.17 | 21.38 |
Minimum of Months | 47.17 | 19.90 | 112.67 | 19.84 | 12.83 | 19.81 |
Maximum of Months | 513.00 | 25.89 | 496.50 | 24.69 | 471.00 | 24.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.99 | 414.33 | 19.86 | 414.33 | 19.81 |
February | 454.00 | 20.29 | 369.17 | 20.15 | 369.17 | 20.10 |
March | 494.83 | 21.32 | 185.83 | 20.94 | 185.83 | 20.72 |
April | 346.17 | 21.98 | 139.17 | 22.16 | 62.33 | 21.94 |
May | 195.67 | 23.43 | 229.17 | 24.02 | 34.33 | 24.14 |
June | 48.33 | 25.67 | 448.83 | 24.50 | 40.17 | 24.62 |
July | 96.67 | 26.30 | 496.67 | 24.87 | 96.67 | 25.07 |
August | 56.67 | 26.23 | 482.33 | 24.63 | 53.67 | 24.79 |
September | 123.83 | 24.01 | 332.00 | 24.32 | 35.83 | 24.45 |
October | 261.17 | 22.52 | 179.17 | 23.00 | 23.00 | 22.87 |
November | 473.83 | 21.09 | 203.67 | 20.73 | 203.17 | 20.53 |
December | 497.00 | 20.22 | 413.17 | 20.11 | 413.17 | 20.07 |
Annual Sum or Average | 3550.17 | 21.45 | 3893.50 | 22.00 | 1931.67 | 21.74 |
Minimum of Months | 48.33 | 19.99 | 139.17 | 19.86 | 23.00 | 19.81 |
Maximum of Months | 502.00 | 26.30 | 496.67 | 24.87 | 414.33 | 25.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 490.67 | 20.47 | 334.33 | 20.13 | 334.33 | 19.98 |
February | 428.33 | 20.86 | 291.00 | 20.52 | 291.00 | 20.38 |
March | 426.67 | 21.27 | 199.50 | 21.06 | 173.33 | 20.85 |
April | 341.17 | 21.82 | 138.83 | 22.02 | 66.83 | 21.81 |
May | 224.83 | 23.12 | 196.50 | 23.71 | 24.00 | 23.79 |
June | 58.00 | 24.76 | 423.00 | 24.38 | 34.17 | 24.47 |
July | 88.67 | 26.05 | 495.50 | 24.76 | 88.67 | 24.93 |
August | 61.00 | 25.86 | 469.83 | 24.60 | 52.00 | 24.75 |
September | 117.00 | 24.02 | 337.00 | 24.32 | 34.00 | 24.45 |
October | 201.17 | 22.64 | 262.17 | 23.46 | 31.00 | 23.39 |
November | 409.67 | 21.27 | 188.83 | 21.02 | 163.00 | 20.78 |
December | 465.00 | 20.77 | 318.67 | 20.48 | 312.83 | 20.33 |
Annual Sum or Average | 3312.17 | 21.66 | 3655.17 | 22.23 | 1605.17 | 21.97 |
Minimum of Months | 58.00 | 20.47 | 138.83 | 20.13 | 24.00 | 19.98 |
Maximum of Months | 490.67 | 26.05 | 495.50 | 24.76 | 334.33 | 24.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.08 | 406.50 | 19.92 | 406.50 | 19.86 |
February | 453.83 | 20.37 | 365.50 | 20.19 | 365.50 | 20.12 |
March | 463.50 | 21.10 | 223.33 | 20.85 | 212.83 | 20.68 |
April | 362.00 | 21.77 | 135.83 | 21.86 | 77.17 | 21.65 |
May | 218.50 | 23.27 | 209.17 | 23.81 | 35.67 | 23.93 |
June | 60.17 | 25.15 | 437.00 | 24.46 | 41.50 | 24.58 |
July | 93.33 | 26.12 | 496.33 | 24.81 | 93.33 | 24.99 |
August | 60.67 | 25.87 | 474.00 | 24.62 | 52.00 | 24.76 |
September | 128.17 | 23.64 | 304.67 | 24.15 | 27.00 | 24.25 |
October | 273.00 | 22.31 | 204.00 | 22.83 | 40.17 | 22.68 |
November | 468.17 | 20.89 | 229.50 | 20.58 | 228.67 | 20.42 |
December | 497.00 | 20.27 | 417.17 | 20.14 | 417.17 | 20.09 |
Annual Sum or Average | 3580.33 | 21.38 | 3903.00 | 21.93 | 1997.50 | 21.67 |
Minimum of Months | 60.17 | 20.08 | 135.83 | 19.92 | 27.00 | 19.86 |
Maximum of Months | 502.00 | 26.12 | 496.33 | 24.81 | 417.17 | 24.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.21 | 434.00 | 20.15 | 434.00 | 20.13 |
February | 454.00 | 20.37 | 423.50 | 20.34 | 423.50 | 20.33 |
March | 514.00 | 20.98 | 254.67 | 20.83 | 254.67 | 20.75 |
April | 463.00 | 21.93 | 57.00 | 21.78 | 55.33 | 21.65 |
May | 341.33 | 23.12 | 72.83 | 23.29 | 11.67 | 23.31 |
June | 32.17 | 24.29 | 389.00 | 24.23 | 14.67 | 24.25 |
July | 39.50 | 25.52 | 497.00 | 24.49 | 39.50 | 24.56 |
August | 23.50 | 25.82 | 464.83 | 24.42 | 23.17 | 24.49 |
September | 90.17 | 23.69 | 300.33 | 24.14 | 8.17 | 24.16 |
October | 274.50 | 23.04 | 137.00 | 23.37 | 0.50 | 23.37 |
November | 484.50 | 21.66 | 136.17 | 21.38 | 136.17 | 21.21 |
December | 497.00 | 20.57 | 420.33 | 20.52 | 420.33 | 20.50 |
Annual Sum or Average | 3715.67 | 21.48 | 3586.67 | 21.93 | 1821.67 | 21.66 |
Minimum of Months | 23.50 | 20.21 | 57.00 | 20.15 | 0.50 | 20.13 |
Maximum of Months | 514.00 | 25.82 | 497.00 | 24.49 | 434.00 | 24.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.34 | 389.00 | 20.22 | 389.00 | 20.17 |
February | 454.00 | 20.68 | 334.83 | 20.55 | 334.83 | 20.49 |
March | 511.17 | 21.61 | 127.83 | 21.35 | 127.83 | 21.18 |
April | 366.33 | 22.33 | 61.33 | 22.44 | 21.33 | 22.34 |
May | 209.17 | 23.25 | 177.33 | 23.88 | 19.33 | 23.92 |
June | 20.17 | 25.59 | 452.33 | 24.41 | 17.83 | 24.46 |
July | 65.33 | 26.30 | 497.00 | 24.77 | 65.33 | 24.93 |
August | 37.83 | 26.51 | 500.17 | 24.61 | 37.83 | 24.74 |
September | 58.67 | 24.77 | 382.33 | 24.50 | 24.17 | 24.60 |
October | 172.17 | 23.45 | 226.67 | 23.90 | 1.00 | 23.90 |
November | 431.00 | 21.93 | 100.83 | 21.68 | 94.83 | 21.48 |
December | 497.00 | 20.88 | 288.00 | 20.70 | 288.00 | 20.61 |
Annual Sum or Average | 3324.83 | 21.73 | 3537.67 | 22.37 | 1421.33 | 22.13 |
Minimum of Months | 20.17 | 20.34 | 61.33 | 20.22 | 1.00 | 20.17 |
Maximum of Months | 511.17 | 26.51 | 500.17 | 24.77 | 389.00 | 24.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.29 | 325.17 | 20.03 | 325.17 | 19.91 |
February | 446.33 | 20.71 | 271.00 | 20.44 | 270.17 | 20.31 |
March | 483.83 | 21.30 | 119.17 | 21.06 | 116.00 | 20.89 |
April | 396.50 | 21.80 | 77.00 | 21.89 | 38.17 | 21.75 |
May | 324.17 | 22.65 | 92.17 | 23.07 | 17.50 | 23.08 |
June | 115.00 | 23.83 | 399.17 | 24.17 | 87.83 | 24.15 |
July | 125.33 | 24.80 | 495.50 | 24.55 | 125.33 | 24.59 |
August | 75.83 | 25.21 | 490.67 | 24.58 | 72.83 | 24.66 |
September | 105.00 | 24.20 | 387.50 | 24.45 | 58.50 | 24.53 |
October | 132.83 | 23.25 | 303.33 | 24.14 | 15.83 | 24.20 |
November | 397.83 | 21.70 | 98.17 | 21.66 | 64.33 | 21.48 |
December | 474.83 | 21.00 | 245.50 | 20.81 | 235.33 | 20.65 |
Annual Sum or Average | 3579.50 | 21.71 | 3304.33 | 22.34 | 1427.00 | 22.14 |
Minimum of Months | 75.83 | 20.29 | 77.00 | 20.03 | 15.83 | 19.91 |
Maximum of Months | 502.00 | 25.21 | 495.50 | 24.58 | 325.17 | 24.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.38 | 384.00 | 20.25 | 384.00 | 20.19 |
February | 454.00 | 20.68 | 348.67 | 20.53 | 348.67 | 20.48 |
March | 497.00 | 21.56 | 153.67 | 21.34 | 150.33 | 21.19 |
April | 384.33 | 22.21 | 71.50 | 22.30 | 31.83 | 22.18 |
May | 230.83 | 23.20 | 167.83 | 23.73 | 17.00 | 23.74 |
June | 32.33 | 25.53 | 447.83 | 24.46 | 25.50 | 24.54 |
July | 61.00 | 26.25 | 497.00 | 24.74 | 61.00 | 24.89 |
August | 34.17 | 26.45 | 498.83 | 24.61 | 34.17 | 24.72 |
September | 59.67 | 24.42 | 359.67 | 24.42 | 18.50 | 24.50 |
October | 168.00 | 23.36 | 240.17 | 23.89 | 1.17 | 23.90 |
November | 451.83 | 21.77 | 120.83 | 21.50 | 120.33 | 21.32 |
December | 497.00 | 20.83 | 331.83 | 20.68 | 331.83 | 20.61 |
Annual Sum or Average | 3372.17 | 21.69 | 3621.83 | 22.31 | 1524.33 | 22.06 |
Minimum of Months | 32.33 | 20.38 | 71.50 | 20.25 | 1.17 | 20.19 |
Maximum of Months | 502.00 | 26.45 | 498.83 | 24.74 | 384.00 | 24.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.13 | 409.33 | 20.03 | 409.33 | 20.00 |
February | 454.00 | 20.34 | 386.00 | 20.27 | 386.00 | 20.24 |
March | 512.17 | 21.26 | 180.67 | 21.03 | 180.67 | 20.89 |
April | 405.83 | 22.19 | 59.67 | 22.13 | 37.00 | 22.00 |
May | 186.00 | 23.29 | 138.00 | 23.73 | 0.00 | 23.73 |
June | 27.67 | 24.92 | 430.33 | 24.35 | 20.00 | 24.39 |
July | 60.67 | 25.83 | 497.00 | 24.65 | 60.67 | 24.76 |
August | 31.83 | 25.86 | 470.67 | 24.49 | 31.33 | 24.57 |
September | 104.00 | 23.58 | 295.17 | 24.10 | 11.33 | 24.12 |
October | 281.50 | 22.76 | 135.00 | 23.12 | 7.17 | 23.08 |
November | 482.33 | 21.35 | 163.50 | 21.05 | 163.50 | 20.87 |
December | 497.00 | 20.40 | 423.17 | 20.34 | 423.17 | 20.32 |
Annual Sum or Average | 3545.00 | 21.42 | 3588.50 | 21.95 | 1730.17 | 21.68 |
Minimum of Months | 27.67 | 20.13 | 59.67 | 20.03 | 0.00 | 20.00 |
Maximum of Months | 512.17 | 25.86 | 497.00 | 24.65 | 423.17 | 24.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.09 | 331.67 | 19.92 | 331.67 | 19.86 |
February | 385.00 | 20.56 | 274.83 | 20.36 | 274.83 | 20.28 |
March | 416.17 | 21.58 | 116.83 | 21.28 | 115.83 | 21.08 |
April | 292.50 | 22.34 | 77.33 | 22.64 | 16.83 | 22.55 |
May | 137.50 | 23.73 | 189.00 | 24.26 | 18.67 | 24.40 |
June | 36.83 | 25.95 | 388.50 | 24.60 | 33.17 | 24.72 |
July | 90.50 | 26.37 | 422.00 | 25.00 | 90.50 | 25.20 |
August | 50.00 | 26.44 | 412.67 | 24.75 | 50.00 | 24.92 |
September | 80.50 | 24.48 | 291.50 | 24.53 | 30.17 | 24.66 |
October | 198.33 | 22.99 | 157.17 | 23.52 | 7.00 | 23.51 |
November | 388.83 | 21.46 | 130.67 | 21.13 | 127.50 | 20.92 |
December | 422.00 | 20.55 | 293.33 | 20.36 | 293.33 | 20.28 |
Annual Sum or Average | 2925.17 | 21.70 | 3085.50 | 22.28 | 1389.50 | 22.05 |
Minimum of Months | 36.83 | 20.09 | 77.33 | 19.92 | 7.00 | 19.86 |
Maximum of Months | 427.00 | 26.44 | 422.00 | 25.00 | 331.67 | 25.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 483.67 | 20.75 | 287.50 | 20.39 | 287.50 | 20.23 |
February | 418.67 | 21.24 | 234.67 | 20.94 | 228.33 | 20.76 |
March | 417.83 | 21.72 | 129.67 | 21.58 | 102.33 | 21.39 |
April | 329.00 | 22.30 | 96.33 | 22.59 | 22.83 | 22.48 |
May | 169.50 | 23.34 | 200.00 | 23.93 | 6.17 | 23.98 |
June | 41.33 | 25.23 | 441.83 | 24.42 | 29.33 | 24.50 |
July | 82.33 | 26.11 | 497.00 | 24.76 | 82.33 | 24.93 |
August | 49.33 | 26.37 | 484.67 | 24.63 | 49.33 | 24.78 |
September | 81.33 | 24.63 | 368.67 | 24.48 | 33.33 | 24.61 |
October | 161.33 | 23.29 | 279.67 | 24.02 | 10.83 | 24.09 |
November | 385.50 | 21.80 | 134.67 | 21.67 | 95.17 | 21.43 |
December | 449.67 | 21.18 | 256.00 | 20.93 | 246.17 | 20.75 |
Annual Sum or Average | 3069.50 | 21.98 | 3410.67 | 22.63 | 1193.67 | 22.40 |
Minimum of Months | 41.33 | 20.75 | 96.33 | 20.39 | 6.17 | 20.23 |
Maximum of Months | 483.67 | 26.37 | 497.00 | 24.76 | 287.50 | 24.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.33 | 359.00 | 20.13 | 359.00 | 20.05 |
February | 453.50 | 20.68 | 321.67 | 20.47 | 321.67 | 20.38 |
March | 459.50 | 21.52 | 148.83 | 21.31 | 138.00 | 21.13 |
April | 351.50 | 22.27 | 93.83 | 22.45 | 32.33 | 22.33 |
May | 156.67 | 23.54 | 224.17 | 24.06 | 16.00 | 24.16 |
June | 44.50 | 25.63 | 452.17 | 24.50 | 36.83 | 24.61 |
July | 85.17 | 26.18 | 497.00 | 24.81 | 85.17 | 24.99 |
August | 47.17 | 26.32 | 488.33 | 24.63 | 47.17 | 24.77 |
September | 89.50 | 24.14 | 337.83 | 24.33 | 25.50 | 24.43 |
October | 221.50 | 22.90 | 213.67 | 23.51 | 8.33 | 23.50 |
November | 455.33 | 21.40 | 152.67 | 21.11 | 150.83 | 20.92 |
December | 497.00 | 20.66 | 356.83 | 20.49 | 356.83 | 20.41 |
Annual Sum or Average | 3363.33 | 21.66 | 3646.00 | 22.27 | 1577.67 | 22.03 |
Minimum of Months | 44.50 | 20.33 | 93.83 | 20.13 | 8.33 | 20.05 |
Maximum of Months | 502.00 | 26.32 | 497.00 | 24.81 | 359.00 | 24.99 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.65673 | 23.62268 | -0.1893 | 8.18976 |
February | 454.00000 | 23.27720 | 19.46493 | -0.0550 | 5.61031 |
March | 514.00000 | 23.83292 | 26.88232 | 0.16315 | 5.85859 |
April | 485.00000 | 24.13454 | 32.62393 | 0.30620 | 7.31098 |
May | 508.00000 | 24.32475 | 39.78616 | -0.4272 | 9.23212 |
June | 496.00000 | 24.39657 | 49.47569 | -0.2921 | 7.25785 |
July | 497.00000 | 24.45799 | 52.76158 | -0.2384 | 6.67252 |
August | 514.00000 | 24.42602 | 49.49689 | -0.2639 | 7.05866 |
September | 485.00000 | 24.42907 | 45.09370 | -0.3193 | 7.66232 |
October | 502.00000 | 24.38940 | 38.53892 | 0.45510 | 9.78038 |
November | 489.00000 | 23.99734 | 29.83561 | 0.23442 | 6.96032 |
December | 497.00000 | 23.50654 | 22.34915 | 0.03234 | 5.33125 |
Annual Sum or Average | 5943.00000 | 23.99027 | 35.95240 | -0.0504 | 7.25709 |
Minimum of Months | 454.00000 | 22.65673 | 19.46493 | -0.4272 | 5.33125 |
Maximum of Months | 514.00000 | 24.45799 | 52.76158 | 0.45510 | 9.78038 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.12030 | 25.57810 | -0.5328 | 12.94916 |
February | 454.00000 | 21.54382 | 21.32781 | -0.4466 | 9.95572 |
March | 514.00000 | 22.61675 | 29.79606 | -0.1148 | 6.14790 |
April | 485.00000 | 23.37095 | 35.07240 | 0.12622 | 6.35446 |
May | 508.00000 | 24.04927 | 41.45803 | -0.5349 | 11.48212 |
June | 496.00000 | 24.26996 | 50.35299 | -0.3553 | 7.96876 |
July | 497.00000 | 24.35062 | 53.96461 | -0.2879 | 7.06727 |
August | 514.00000 | 24.32456 | 50.58678 | -0.3168 | 7.52932 |
September | 485.00000 | 24.24059 | 46.11393 | -0.4090 | 8.93584 |
October | 502.00000 | 24.00036 | 40.14846 | 0.34340 | 8.11114 |
November | 489.00000 | 22.72216 | 32.98244 | -0.0678 | 7.02047 |
December | 497.00000 | 21.72153 | 25.14057 | -0.3723 | 8.63738 |
Annual Sum or Average | 5943.00000 | 23.20626 | 37.83428 | -0.2467 | 8.50777 |
Minimum of Months | 454.00000 | 21.12030 | 21.32781 | -0.5349 | 6.14790 |
Maximum of Months | 514.00000 | 24.35062 | 53.96461 | 0.34340 | 12.94916 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.55936 | 26.37335 | -0.6917 | 17.42454 |
February | 454.00000 | 20.86163 | 21.26713 | -0.6390 | 15.03210 |
March | 514.00000 | 21.89563 | 30.76410 | -0.2954 | 8.30387 |
April | 485.00000 | 22.87039 | 36.02335 | 0.00285 | 6.86899 |
May | 508.00000 | 23.88050 | 41.99956 | -0.5905 | 13.25469 |
June | 496.00000 | 24.24469 | 50.18425 | -0.3583 | 8.05812 |
July | 497.00000 | 24.37243 | 53.71973 | -0.2695 | 6.89716 |
August | 514.00000 | 24.31348 | 50.41533 | -0.3128 | 7.50410 |
September | 485.00000 | 24.11741 | 46.24327 | -0.4568 | 10.10492 |
October | 502.00000 | 23.54065 | 41.31022 | 0.22701 | 7.49825 |
November | 489.00000 | 21.86153 | 34.41008 | -0.2884 | 9.33095 |
December | 497.00000 | 20.88988 | 25.74511 | -0.5981 | 13.85822 |
Annual Sum or Average | 5943.00000 | 22.79863 | 38.33177 | -0.3544 | 10.31498 |
Minimum of Months | 454.00000 | 20.55936 | 21.26713 | -0.6917 | 6.86899 |
Maximum of Months | 514.00000 | 24.37243 | 53.71973 | 0.22701 | 17.42454 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.90014 | 27.60061 | -0.8996 | 24.84035 |
February | 454.00000 | 20.06044 | 22.17436 | -0.8802 | 23.58899 |
March | 514.00000 | 20.89620 | 32.56914 | -0.5441 | 13.40690 |
April | 485.00000 | 22.08790 | 37.80147 | -0.1774 | 8.89307 |
May | 508.00000 | 23.62466 | 43.23067 | -0.6564 | 16.44490 |
June | 496.00000 | 24.23970 | 52.28127 | -0.3067 | 7.89160 |
July | 497.00000 | 24.50191 | 56.97551 | -0.1497 | 6.65573 |
August | 514.00000 | 24.33482 | 52.54815 | -0.2496 | 7.34422 |
September | 485.00000 | 23.90085 | 48.72615 | -0.5071 | 12.20565 |
October | 502.00000 | 22.78317 | 43.73982 | 0.05609 | 8.18602 |
November | 489.00000 | 20.82554 | 36.29978 | -0.5473 | 14.46345 |
December | 497.00000 | 20.06703 | 27.57746 | -0.8363 | 21.76356 |
Annual Sum or Average | 5943.00000 | 22.28612 | 40.25952 | -0.4722 | 13.73933 |
Minimum of Months | 454.00000 | 19.90014 | 22.17436 | -0.8996 | 6.65573 |
Maximum of Months | 514.00000 | 24.50191 | 56.97551 | 0.05609 | 24.84035 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.98662 | 28.42065 | -0.8536 | 23.47972 |
February | 454.00000 | 20.28578 | 22.88675 | -0.7901 | 20.73756 |
March | 514.00000 | 21.41759 | 32.49271 | -0.3953 | 11.68775 |
April | 485.00000 | 22.64284 | 36.65429 | -0.0191 | 8.88781 |
May | 508.00000 | 23.89939 | 42.39074 | -0.5010 | 13.70713 |
June | 496.00000 | 24.33781 | 51.83332 | -0.2155 | 7.42386 |
July | 497.00000 | 24.58803 | 56.29320 | -0.0560 | 6.95533 |
August | 514.00000 | 24.41622 | 51.87981 | -0.1312 | 6.81080 |
September | 485.00000 | 24.13774 | 47.85332 | -0.3682 | 10.39838 |
October | 502.00000 | 23.27034 | 42.37243 | 0.19976 | 8.76109 |
November | 489.00000 | 21.18154 | 36.40953 | -0.4437 | 13.14397 |
December | 497.00000 | 20.21752 | 28.26307 | -0.7747 | 19.85267 |
Annual Sum or Average | 5943.00000 | 22.54930 | 39.93857 | -0.3595 | 12.59603 |
Minimum of Months | 454.00000 | 19.98662 | 22.88675 | -0.8536 | 6.81080 |
Maximum of Months | 514.00000 | 24.58803 | 56.29320 | 0.19976 | 23.47972 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.54921 | 26.73521 | -0.6944 | 20.35924 |
February | 454.00000 | 21.04869 | 20.92314 | -0.5849 | 17.19012 |
March | 514.00000 | 21.73953 | 30.46795 | -0.3012 | 11.28401 |
April | 485.00000 | 22.54604 | 36.16160 | -0.0404 | 9.25384 |
May | 508.00000 | 23.70228 | 42.72339 | -0.5977 | 15.82481 |
June | 496.00000 | 24.24869 | 52.10025 | -0.2797 | 7.97675 |
July | 497.00000 | 24.52331 | 56.65786 | -0.1107 | 6.84329 |
August | 514.00000 | 24.39303 | 51.88549 | -0.1526 | 7.01044 |
September | 485.00000 | 24.13898 | 47.36115 | -0.3357 | 10.32381 |
October | 502.00000 | 23.59585 | 40.59268 | 0.32213 | 10.62362 |
November | 489.00000 | 21.71777 | 34.13096 | -0.2935 | 11.66060 |
December | 497.00000 | 21.01006 | 26.13535 | -0.5655 | 16.52966 |
Annual Sum or Average | 5943.00000 | 22.78134 | 38.95665 | -0.3012 | 12.04275 |
Minimum of Months | 454.00000 | 20.54921 | 20.92314 | -0.6944 | 6.84329 |
Maximum of Months | 514.00000 | 24.52331 | 56.65786 | 0.32213 | 20.35924 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.07748 | 28.25084 | -0.8412 | 23.23256 |
February | 454.00000 | 20.36996 | 22.63585 | -0.7853 | 21.31299 |
March | 514.00000 | 21.39010 | 32.07478 | -0.4030 | 12.15508 |
April | 485.00000 | 22.38967 | 37.35565 | -0.0761 | 9.48291 |
May | 508.00000 | 23.75740 | 43.07861 | -0.5559 | 15.16667 |
June | 496.00000 | 24.30446 | 52.00239 | -0.2179 | 7.72703 |
July | 497.00000 | 24.56288 | 56.69407 | -0.0679 | 6.99943 |
August | 514.00000 | 24.41231 | 52.14566 | -0.1356 | 6.98025 |
September | 485.00000 | 24.02998 | 48.33657 | -0.4072 | 11.22263 |
October | 502.00000 | 23.13379 | 42.79545 | 0.17262 | 9.19850 |
November | 489.00000 | 21.02096 | 36.58799 | -0.4890 | 13.83713 |
December | 497.00000 | 20.26673 | 28.17309 | -0.7735 | 20.08971 |
Annual Sum or Average | 5943.00000 | 22.49358 | 40.13790 | -0.3788 | 13.05758 |
Minimum of Months | 454.00000 | 20.07748 | 22.63585 | -0.8412 | 6.98025 |
Maximum of Months | 514.00000 | 24.56288 | 56.69407 | 0.17262 | 23.23256 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.21388 | 27.52218 | -0.8006 | 20.44037 |
February | 454.00000 | 20.36800 | 22.34136 | -0.7880 | 19.34348 |
March | 514.00000 | 20.98319 | 32.88768 | -0.5184 | 11.60259 |
April | 485.00000 | 22.02606 | 38.68887 | -0.2002 | 7.62230 |
May | 508.00000 | 23.43782 | 44.25096 | -0.7611 | 18.63347 |
June | 496.00000 | 24.17410 | 52.62773 | -0.3736 | 8.33925 |
July | 497.00000 | 24.40636 | 56.16031 | -0.2290 | 6.66045 |
August | 514.00000 | 24.32195 | 51.97478 | -0.2846 | 7.30079 |
September | 485.00000 | 24.09557 | 48.07543 | -0.4472 | 9.87948 |
October | 502.00000 | 23.46616 | 42.23260 | 0.21895 | 7.31323 |
November | 489.00000 | 21.67939 | 34.99788 | -0.3116 | 9.25229 |
December | 497.00000 | 20.57106 | 27.09874 | -0.6672 | 15.04730 |
Annual Sum or Average | 5943.00000 | 22.49404 | 40.03642 | -0.4284 | 11.75065 |
Minimum of Months | 454.00000 | 20.21388 | 22.34136 | -0.8006 | 6.66045 |
Maximum of Months | 514.00000 | 24.40636 | 56.16031 | 0.21895 | 20.44037 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.34130 | 28.35880 | -0.7460 | 18.83836 |
February | 454.00000 | 20.67633 | 23.05859 | -0.6789 | 16.01391 |
March | 514.00000 | 21.62834 | 32.82498 | -0.3378 | 9.18032 |
April | 485.00000 | 22.80331 | 37.03271 | 0.00921 | 7.48439 |
May | 508.00000 | 23.88490 | 42.76607 | -0.5516 | 13.84052 |
June | 496.00000 | 24.33240 | 51.90643 | -0.2598 | 7.29820 |
July | 497.00000 | 24.56591 | 55.28706 | -0.1092 | 6.50209 |
August | 514.00000 | 24.45813 | 51.06890 | -0.1421 | 6.44945 |
September | 485.00000 | 24.34787 | 47.06410 | -0.2976 | 8.25823 |
October | 502.00000 | 23.92802 | 40.63121 | 0.36321 | 8.85842 |
November | 489.00000 | 22.17786 | 34.67892 | -0.1779 | 8.35996 |
December | 497.00000 | 20.88067 | 27.69388 | -0.5726 | 12.90888 |
Annual Sum or Average | 5943.00000 | 22.85064 | 39.48852 | -0.2897 | 10.30273 |
Minimum of Months | 454.00000 | 20.34130 | 23.05859 | -0.7460 | 6.44945 |
Maximum of Months | 514.00000 | 24.56591 | 55.28706 | 0.36321 | 18.83836 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.28731 | 24.89651 | -0.7014 | 18.32674 |
February | 454.00000 | 20.78714 | 19.46979 | -0.5860 | 15.09447 |
March | 514.00000 | 21.46642 | 29.55836 | -0.3300 | 9.56114 |
April | 485.00000 | 22.25628 | 35.91624 | -0.0999 | 7.98154 |
May | 508.00000 | 23.25341 | 43.84132 | -0.7681 | 20.17534 |
June | 496.00000 | 24.14984 | 54.47810 | -0.3384 | 8.35844 |
July | 497.00000 | 24.48703 | 58.80366 | -0.1479 | 6.35256 |
August | 514.00000 | 24.44473 | 53.14831 | -0.1455 | 6.50863 |
September | 485.00000 | 24.30200 | 47.96578 | -0.2628 | 8.41066 |
October | 502.00000 | 24.07730 | 39.64277 | 0.46830 | 11.27183 |
November | 489.00000 | 22.15383 | 31.59549 | -0.1320 | 8.45552 |
December | 497.00000 | 21.19838 | 23.85321 | -0.4505 | 11.97972 |
Annual Sum or Average | 5943.00000 | 22.75238 | 38.74393 | -0.2900 | 11.03184 |
Minimum of Months | 454.00000 | 20.28731 | 19.46979 | -0.7681 | 6.35256 |
Maximum of Months | 514.00000 | 24.48703 | 58.80366 | 0.46830 | 20.17534 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.37889 | 28.27413 | -0.7436 | 18.84900 |
February | 454.00000 | 20.67721 | 22.98544 | -0.6882 | 16.71464 |
March | 514.00000 | 21.64460 | 32.43575 | -0.3348 | 9.35448 |
April | 485.00000 | 22.62864 | 37.56355 | -0.0325 | 7.62586 |
May | 508.00000 | 23.79813 | 43.32386 | -0.5917 | 14.56709 |
June | 496.00000 | 24.34709 | 51.79778 | -0.2450 | 7.22052 |
July | 497.00000 | 24.55786 | 55.48485 | -0.1132 | 6.51271 |
August | 514.00000 | 24.47198 | 51.23316 | -0.1398 | 6.44968 |
September | 485.00000 | 24.28530 | 47.36721 | -0.3230 | 8.47581 |
October | 502.00000 | 23.92301 | 40.77868 | 0.36368 | 8.99369 |
November | 489.00000 | 21.93843 | 35.13664 | -0.2396 | 8.83569 |
December | 497.00000 | 20.83129 | 27.71296 | -0.5906 | 13.40103 |
Annual Sum or Average | 5943.00000 | 22.80601 | 39.63124 | -0.3043 | 10.54978 |
Minimum of Months | 454.00000 | 20.37889 | 22.98544 | -0.7436 | 6.44968 |
Maximum of Months | 514.00000 | 24.55786 | 55.48485 | 0.36368 | 18.84900 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.12979 | 27.46359 | -0.8065 | 21.07185 |
February | 454.00000 | 20.33715 | 21.98623 | -0.7721 | 19.29667 |
March | 514.00000 | 21.26658 | 32.07708 | -0.4278 | 10.39321 |
April | 485.00000 | 22.49540 | 37.12023 | -0.0697 | 7.38923 |
May | 508.00000 | 23.83164 | 42.58241 | -0.5892 | 13.60128 |
June | 496.00000 | 24.27844 | 52.09769 | -0.3011 | 7.50870 |
July | 497.00000 | 24.50473 | 56.69118 | -0.1644 | 6.57472 |
August | 514.00000 | 24.36200 | 52.34966 | -0.2512 | 7.13822 |
September | 485.00000 | 24.05901 | 48.23243 | -0.4520 | 10.24612 |
October | 502.00000 | 23.28262 | 42.44416 | 0.17908 | 7.47671 |
November | 489.00000 | 21.38596 | 35.26871 | -0.3858 | 10.80053 |
December | 497.00000 | 20.40266 | 27.07817 | -0.7101 | 16.82619 |
Annual Sum or Average | 5943.00000 | 22.54474 | 39.74742 | -0.3937 | 11.47599 |
Minimum of Months | 454.00000 | 20.12979 | 21.98623 | -0.8065 | 6.57472 |
Maximum of Months | 514.00000 | 24.50473 | 56.69118 | 0.17908 | 21.07185 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.08829 | 27.89022 | -0.7966 | 21.23591 |
February | 385.00000 | 20.56038 | 22.26641 | -0.6944 | 17.38865 |
March | 433.00000 | 21.68140 | 31.69967 | -0.3119 | 9.57210 |
April | 410.00000 | 22.92637 | 35.97951 | 0.05430 | 8.00225 |
May | 430.00000 | 24.08527 | 41.57903 | -0.4532 | 12.03635 |
June | 418.00000 | 24.44923 | 51.30361 | -0.2072 | 7.29372 |
July | 422.00000 | 24.70207 | 55.85660 | -0.0556 | 7.04981 |
August | 433.00000 | 24.52571 | 51.61538 | -0.1316 | 6.85340 |
September | 410.00000 | 24.31993 | 47.33661 | -0.3225 | 9.28504 |
October | 427.00000 | 23.60724 | 40.95173 | 0.27537 | 8.46930 |
November | 417.00000 | 21.63207 | 35.12775 | -0.3134 | 10.33549 |
December | 422.00000 | 20.54619 | 27.52504 | -0.6592 | 15.82842 |
Annual Sum or Average | 5034.00000 | 22.77397 | 39.20586 | -0.2991 | 11.07821 |
Minimum of Months | 385.00000 | 20.08829 | 22.26641 | -0.7966 | 6.85340 |
Maximum of Months | 433.00000 | 24.70207 | 55.85660 | 0.27537 | 21.23591 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.87563 | 26.33955 | -0.5845 | 16.78098 |
February | 454.00000 | 21.48907 | 20.47863 | -0.4493 | 13.39240 |
March | 514.00000 | 22.15875 | 29.79160 | -0.1791 | 8.85783 |
April | 485.00000 | 22.93133 | 35.44056 | 0.06146 | 8.01837 |
May | 508.00000 | 23.90887 | 42.03721 | -0.5317 | 12.97711 |
June | 496.00000 | 24.30425 | 51.86059 | -0.2702 | 7.49374 |
July | 497.00000 | 24.53660 | 56.29288 | -0.1233 | 6.69339 |
August | 514.00000 | 24.42708 | 51.62880 | -0.1543 | 6.73887 |
September | 485.00000 | 24.28378 | 46.92155 | -0.2868 | 8.75689 |
October | 502.00000 | 23.95341 | 39.62147 | 0.41581 | 10.71887 |
November | 489.00000 | 22.28611 | 32.95998 | -0.1339 | 9.18250 |
December | 497.00000 | 21.50028 | 25.36424 | -0.4133 | 12.51966 |
Annual Sum or Average | 5943.00000 | 23.06638 | 38.36181 | -0.2197 | 10.16089 |
Minimum of Months | 454.00000 | 20.87563 | 20.47863 | -0.5845 | 6.69339 |
Maximum of Months | 514.00000 | 24.53660 | 56.29288 | 0.41581 | 16.78098 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.32740 | 28.13023 | -0.7446 | 19.58172 |
February | 454.00000 | 20.68622 | 22.41399 | -0.6712 | 17.20021 |
March | 514.00000 | 21.78796 | 31.49351 | -0.2836 | 9.48045 |
April | 485.00000 | 22.80119 | 36.61101 | 0.03107 | 8.11602 |
May | 508.00000 | 23.96636 | 42.37375 | -0.4896 | 12.34263 |
June | 496.00000 | 24.35605 | 51.77157 | -0.2098 | 7.23898 |
July | 497.00000 | 24.57825 | 56.35869 | -0.0798 | 6.80576 |
August | 514.00000 | 24.44362 | 51.94776 | -0.1375 | 6.70690 |
September | 485.00000 | 24.18463 | 47.84223 | -0.3545 | 9.40304 |
October | 502.00000 | 23.58933 | 41.58024 | 0.28596 | 8.78953 |
November | 489.00000 | 21.58005 | 35.51135 | -0.3291 | 10.39580 |
December | 497.00000 | 20.65766 | 27.64206 | -0.6382 | 15.31952 |
Annual Sum or Average | 5943.00000 | 22.76280 | 39.59906 | -0.2993 | 10.90505 |
Minimum of Months | 454.00000 | 20.32740 | 22.41399 | -0.7446 | 6.70690 |
Maximum of Months | 514.00000 | 24.57825 | 56.35869 | 0.28596 | 19.58172 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.545388E+09 | 0.146118E+09 | 26.39 | 0.395988E+09 | 0.149401E+09 | 0.00 | 0.70 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 22788.75 | 27-MAR-16:00 | 18812.61 | 27-MAR-16:00 | 7819.41 | 27-MAR-12:55 | 5661.35 | 27-MAR-16:00 | 0.00 |
April | 0.495430E+10 | 0.129349E+10 | 129.69 | 0.453334E+10 | 0.420956E+09 | 0.00 | 1.00 | 07-APR-11:50 | 0.00 | 01-APR-00:10 | 42903.81 | 07-APR-15:30 | 42903.81 | 07-APR-15:30 | 6591.94 | 10-APR-06:03 | 10226.24 | 07-APR-15:30 | 0.00 |
May | 0.164041E+11 | 0.419043E+10 | 287.97 | 0.137943E+11 | 0.260987E+10 | 0.00 | 1.00 | 30-MAY-06:03 | 0.00 | 01-MAY-00:10 | 80835.95 | 30-MAY-14:00 | 80835.95 | 30-MAY-14:00 | 23448.94 | 31-MAY-06:03 | 21229.22 | 30-MAY-14:00 | 0.00 |
June | 0.570290E+11 | 0.139154E+11 | 425.12 | 0.440906E+11 | 0.129384E+11 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 113421.24 | 27-JUN-06:03 | 78959.14 | 19-JUN-06:03 | 52895.04 | 27-JUN-06:03 | 28493.36 | 19-JUN-12:03 | 0.00 |
July | 0.811990E+11 | 0.200195E+11 | 441.64 | 0.601900E+11 | 0.210091E+11 | 0.00 | 1.00 | 01-JUL-05:13 | 0.00 | 01-JUL-00:10 | 116073.44 | 22-JUL-05:03 | 87697.18 | 10-JUL-06:03 | 67297.45 | 24-JUL-05:12 | 26541.21 | 22-JUL-06:03 | 0.00 |
August | 0.834865E+11 | 0.208540E+11 | 455.07 | 0.666881E+11 | 0.167984E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 113168.94 | 17-AUG-06:03 | 87067.92 | 22-AUG-15:40 | 48263.91 | 17-AUG-04:03 | 26830.70 | 05-AUG-06:03 | 0.00 |
September | 0.436341E+11 | 0.105696E+11 | 388.53 | 0.352787E+11 | 0.835546E+10 | 0.00 | 1.00 | 01-SEP-05:02 | 0.00 | 01-SEP-00:10 | 112264.90 | 08-SEP-06:03 | 84076.06 | 05-SEP-05:12 | 46511.61 | 08-SEP-06:03 | 26026.12 | 01-SEP-06:03 | 0.00 |
October | 0.197058E+11 | 0.476298E+10 | 239.25 | 0.141212E+11 | 0.558456E+10 | 0.00 | 1.00 | 02-OCT-12:50 | 0.00 | 01-OCT-00:10 | 64844.43 | 05-OCT-12:30 | 51551.50 | 04-OCT-15:20 | 33474.65 | 25-OCT-06:03 | 14907.51 | 05-OCT-12:30 | 0.00 |
November | 0.142100E+10 | 0.390521E+09 | 64.86 | 0.131146E+10 | 0.109533E+09 | 0.00 | 0.60 | 01-NOV-14:00 | 0.00 | 01-NOV-00:10 | 18700.56 | 01-NOV-14:00 | 18700.56 | 01-NOV-14:00 | 4349.39 | 10-NOV-10:00 | 4784.14 | 01-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.308379E+12 | 0.761420E+11 | 2458.53 | 0.240404E+12 | 0.679757E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.834865E+11 | 0.208540E+11 | 455.07 | 0.666881E+11 | 0.210091E+11 | 0.00 | 1.00 | 0.00 | 116073.44 | 87697.18 | 67297.45 | 28493.36 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.435089E+09 | 0.116097E+09 | 17.74 | 0.305754E+09 | 0.129335E+09 | 0.00 | 0.68 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 19952.53 | 27-MAR-16:00 | 15730.39 | 27-MAR-16:00 | 7046.31 | 27-MAR-12:55 | 4993.71 | 27-MAR-16:00 | 0.00 |
April | 0.433191E+10 | 0.112055E+10 | 104.83 | 0.390092E+10 | 0.430985E+09 | 0.00 | 1.00 | 07-APR-12:05 | 0.00 | 01-APR-00:10 | 46136.11 | 07-APR-14:05 | 46136.11 | 07-APR-14:05 | 5597.45 | 09-APR-12:03 | 11107.47 | 07-APR-14:05 | 0.00 |
May | 0.155016E+11 | 0.394917E+10 | 293.99 | 0.132348E+11 | 0.226682E+10 | 0.00 | 1.00 | 22-MAY-10:05 | 0.00 | 01-MAY-00:10 | 81598.96 | 30-MAY-14:05 | 81598.96 | 30-MAY-14:05 | 23131.83 | 31-MAY-06:03 | 21309.84 | 30-MAY-14:05 | 0.00 |
June | 0.520315E+11 | 0.127122E+11 | 431.21 | 0.398492E+11 | 0.121823E+11 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 103952.29 | 19-JUN-05:02 | 73404.17 | 26-JUN-06:03 | 49061.43 | 20-JUN-06:03 | 29088.52 | 19-JUN-12:02 | 0.00 |
July | 0.742746E+11 | 0.182784E+11 | 445.46 | 0.539367E+11 | 0.203379E+11 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:10 | 110136.05 | 22-JUL-05:03 | 76465.99 | 10-JUL-06:03 | 66409.05 | 24-JUL-05:12 | 24735.90 | 22-JUL-05:03 | 0.00 |
August | 0.740242E+11 | 0.184775E+11 | 454.57 | 0.583420E+11 | 0.156822E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 105750.99 | 17-AUG-05:03 | 81276.30 | 22-AUG-15:10 | 44950.80 | 17-AUG-05:03 | 24754.01 | 05-AUG-06:03 | 0.00 |
September | 0.365417E+11 | 0.890830E+10 | 386.78 | 0.289348E+11 | 0.760692E+10 | 0.00 | 1.00 | 01-SEP-05:02 | 0.00 | 01-SEP-00:10 | 96825.54 | 01-SEP-05:02 | 70647.77 | 05-SEP-06:03 | 35671.16 | 01-SEP-05:02 | 22278.65 | 01-SEP-05:02 | 0.00 |
October | 0.155947E+11 | 0.379871E+10 | 229.00 | 0.108981E+11 | 0.469662E+10 | 0.00 | 1.00 | 02-OCT-13:00 | 0.00 | 01-OCT-00:10 | 59478.20 | 04-OCT-14:05 | 47156.97 | 04-OCT-14:05 | 22244.64 | 24-OCT-09:10 | 13812.31 | 04-OCT-14:05 | 0.00 |
November | 0.351740E+09 | 99343333.82 | 24.67 | 0.293365E+09 | 58374620.15 | 0.00 | 0.34 | 03-NOV-14:05 | 0.00 | 01-NOV-00:10 | 9125.36 | 03-NOV-14:05 | 9125.36 | 03-NOV-14:05 | 2721.54 | 10-NOV-10:00 | 2493.66 | 03-NOV-14:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.273087E+12 | 0.674602E+11 | 2388.25 | 0.209695E+12 | 0.633915E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.742746E+11 | 0.184775E+11 | 454.57 | 0.583420E+11 | 0.203379E+11 | 0.00 | 1.00 | 0.00 | 110136.05 | 81598.96 | 66409.05 | 29088.52 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.454398E+09 | 0.122306E+09 | 18.16 | 0.311466E+09 | 0.142932E+09 | 0.00 | 0.64 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 20829.63 | 27-MAR-16:00 | 15704.89 | 27-MAR-16:00 | 7259.05 | 27-MAR-13:00 | 5270.10 | 27-MAR-16:00 | 0.00 |
April | 0.436818E+10 | 0.112886E+10 | 94.18 | 0.391565E+10 | 0.452533E+09 | 0.00 | 1.00 | 07-APR-12:00 | 0.00 | 01-APR-00:10 | 49538.75 | 07-APR-14:30 | 49538.75 | 07-APR-14:30 | 6639.03 | 09-APR-11:53 | 11878.27 | 07-APR-14:30 | 0.00 |
May | 0.162256E+11 | 0.415862E+10 | 293.20 | 0.138787E+11 | 0.234698E+10 | 0.00 | 1.00 | 29-MAY-10:12 | 0.00 | 01-MAY-00:10 | 89372.78 | 30-MAY-14:00 | 89372.78 | 30-MAY-14:00 | 14724.82 | 19-MAY-12:07 | 23464.81 | 30-MAY-14:00 | 0.00 |
June | 0.550103E+11 | 0.135254E+11 | 430.67 | 0.427398E+11 | 0.122705E+11 | 0.00 | 1.00 | 01-JUN-09:50 | 0.00 | 01-JUN-00:10 | 116624.24 | 19-JUN-05:02 | 81137.97 | 19-JUN-13:40 | 47050.32 | 20-JUN-06:03 | 28905.18 | 19-JUN-12:05 | 0.00 |
July | 0.791150E+11 | 0.195410E+11 | 447.82 | 0.585221E+11 | 0.205929E+11 | 0.00 | 1.00 | 01-JUL-09:05 | 0.00 | 01-JUL-00:10 | 123581.59 | 22-JUL-05:03 | 86125.02 | 10-JUL-04:02 | 68258.89 | 22-JUL-05:03 | 27755.69 | 22-JUL-05:03 | 0.00 |
August | 0.784007E+11 | 0.196493E+11 | 454.29 | 0.626930E+11 | 0.157077E+11 | 0.00 | 1.00 | 01-AUG-05:03 | 0.00 | 01-AUG-00:10 | 119241.46 | 17-AUG-05:03 | 92810.43 | 22-AUG-14:40 | 56821.48 | 17-AUG-05:03 | 27769.37 | 05-AUG-06:03 | 0.00 |
September | 0.371507E+11 | 0.913961E+10 | 385.56 | 0.292894E+11 | 0.786132E+10 | 0.00 | 1.00 | 01-SEP-05:02 | 0.00 | 01-SEP-00:10 | 86511.47 | 01-SEP-14:10 | 86511.47 | 01-SEP-14:10 | 30771.53 | 01-SEP-05:02 | 23673.40 | 01-SEP-14:10 | 0.00 |
October | 0.149412E+11 | 0.368603E+10 | 223.89 | 0.103865E+11 | 0.455461E+10 | 0.00 | 1.00 | 03-OCT-11:30 | 0.00 | 01-OCT-00:10 | 60800.28 | 04-OCT-13:50 | 51325.58 | 04-OCT-15:00 | 22161.80 | 24-OCT-10:00 | 14205.25 | 04-OCT-13:40 | 0.00 |
November | 0.307646E+09 | 87683029.50 | 24.17 | 0.242693E+09 | 64953272.61 | 0.00 | 0.26 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 7674.19 | 03-NOV-14:00 | 7674.19 | 03-NOV-14:00 | 2110.88 | 10-NOV-10:00 | 2138.57 | 03-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.285974E+12 | 0.710389E+11 | 2371.94 | 0.221979E+12 | 0.639944E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.791150E+11 | 0.196493E+11 | 454.29 | 0.626930E+11 | 0.205929E+11 | 0.00 | 1.00 | 0.00 | 123581.59 | 92810.43 | 68258.89 | 28905.18 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 327.71 | 0.00 | 327.71 | 28.33 | 1671.29 | 0.00 | 0.00 | 0.00 |
February | 448.46 | 0.00 | 448.46 | 51.82 | 1735.32 | 0.00 | 0.00 | 0.00 |
March | 621.90 | 0.00 | 621.90 | 247.25 | 1150.41 | 0.00 | 0.00 | 0.00 |
April | 746.98 | 2.12 | 744.86 | 494.94 | 828.16 | 0.00 | 0.00 | 0.00 |
May | 991.01 | 33.02 | 957.99 | 943.72 | 528.23 | 0.00 | 0.00 | 0.00 |
June | 1050.95 | 56.47 | 994.48 | 1306.70 | 291.70 | 0.00 | 0.00 | 0.00 |
July | 1015.65 | 36.73 | 978.92 | 1445.29 | 165.90 | 0.00 | 0.00 | 0.00 |
August | 899.81 | 10.71 | 889.10 | 1267.85 | 222.07 | 0.00 | 0.00 | 0.00 |
September | 678.31 | 0.13 | 678.18 | 733.24 | 440.36 | 0.00 | 0.00 | 0.00 |
October | 587.03 | 0.00 | 587.03 | 450.69 | 791.79 | 0.00 | 0.00 | 0.00 |
November | 411.74 | 0.00 | 411.74 | 135.07 | 1165.34 | 0.00 | 0.00 | 0.00 |
December | 285.85 | 0.00 | 285.85 | 19.56 | 1537.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 673.41 | 11.66 | 661.75 | 597.35 | 872.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 285.85 | 0.00 | 285.85 | 19.56 | 165.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1050.95 | 56.47 | 994.48 | 1445.29 | 1735.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 456.37 | 182.97 | 273.40 | 294.70 | 1037.38 | 0.00 | 0.00 | 0.00 |
February | 707.73 | 330.16 | 377.57 | 515.65 | 1044.24 | 0.00 | 0.00 | 0.00 |
March | 902.84 | 383.99 | 518.86 | 807.89 | 744.75 | 0.00 | 0.00 | 0.00 |
April | 1083.48 | 474.60 | 608.88 | 1115.68 | 541.91 | 0.00 | 0.00 | 0.00 |
May | 1314.03 | 525.17 | 788.86 | 1531.42 | 362.19 | 0.00 | 0.00 | 0.00 |
June | 1217.83 | 440.84 | 776.98 | 1594.37 | 199.93 | 0.00 | 0.00 | 0.00 |
July | 1223.16 | 441.41 | 781.75 | 1732.26 | 112.81 | 0.00 | 0.00 | 0.00 |
August | 1377.31 | 621.03 | 756.28 | 1943.49 | 149.87 | 0.00 | 0.00 | 0.00 |
September | 1027.20 | 460.87 | 566.34 | 1287.47 | 288.03 | 0.00 | 0.00 | 0.00 |
October | 931.23 | 422.07 | 509.17 | 1046.01 | 517.96 | 0.00 | 0.00 | 0.00 |
November | 575.90 | 221.15 | 354.75 | 482.12 | 736.61 | 0.00 | 0.00 | 0.00 |
December | 448.66 | 210.66 | 237.99 | 317.47 | 946.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 940.30 | 393.35 | 546.95 | 1059.45 | 554.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 448.66 | 182.97 | 237.99 | 294.70 | 112.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1377.31 | 621.03 | 788.86 | 1943.49 | 1044.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1695.32 | 1110.10 | 585.21 | 1702.34 | 1498.31 | 0.00 | 0.00 | 0.00 |
February | 2236.06 | 1480.09 | 755.97 | 2281.25 | 1522.16 | 0.00 | 0.00 | 0.00 |
March | 2017.35 | 1119.66 | 897.69 | 2173.52 | 1128.74 | 0.00 | 0.00 | 0.00 |
April | 1565.39 | 619.00 | 946.39 | 1740.75 | 859.48 | 0.00 | 0.00 | 0.00 |
May | 1371.84 | 286.14 | 1085.69 | 1608.88 | 568.70 | 0.00 | 0.00 | 0.00 |
June | 1287.43 | 196.80 | 1090.63 | 1738.83 | 312.45 | 0.00 | 0.00 | 0.00 |
July | 1349.48 | 234.40 | 1115.08 | 2017.59 | 170.68 | 0.00 | 0.00 | 0.00 |
August | 1802.08 | 668.42 | 1133.66 | 2720.31 | 236.10 | 0.00 | 0.00 | 0.00 |
September | 1955.30 | 1011.36 | 943.94 | 2622.04 | 454.64 | 0.00 | 0.00 | 0.00 |
October | 2678.59 | 1679.67 | 998.92 | 3357.14 | 801.67 | 0.00 | 0.00 | 0.00 |
November | 1857.37 | 1115.44 | 741.93 | 2018.20 | 1105.48 | 0.00 | 0.00 | 0.00 |
December | 1837.47 | 1304.48 | 532.99 | 1922.05 | 1370.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1802.44 | 899.21 | 903.23 | 2158.98 | 831.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1287.43 | 196.80 | 532.99 | 1608.88 | 170.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2678.59 | 1679.67 | 1133.66 | 3357.14 | 1522.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 450.54 | 184.54 | 266.00 | 290.63 | 1060.79 | 0.00 | 0.00 | 0.00 |
February | 664.38 | 291.80 | 372.58 | 472.80 | 1091.13 | 0.00 | 0.00 | 0.00 |
March | 981.04 | 452.92 | 528.12 | 906.63 | 742.92 | 0.00 | 0.00 | 0.00 |
April | 1072.24 | 458.78 | 613.45 | 1115.70 | 557.81 | 0.00 | 0.00 | 0.00 |
May | 1249.05 | 474.34 | 774.71 | 1460.90 | 374.55 | 0.00 | 0.00 | 0.00 |
June | 1367.04 | 551.37 | 815.68 | 1802.98 | 211.57 | 0.00 | 0.00 | 0.00 |
July | 1280.31 | 482.12 | 798.18 | 1810.83 | 120.37 | 0.00 | 0.00 | 0.00 |
August | 1416.37 | 655.69 | 760.68 | 2007.98 | 161.87 | 0.00 | 0.00 | 0.00 |
September | 1005.51 | 439.41 | 566.10 | 1274.38 | 301.95 | 0.00 | 0.00 | 0.00 |
October | 996.89 | 484.76 | 512.13 | 1140.60 | 534.01 | 0.00 | 0.00 | 0.00 |
November | 468.13 | 135.29 | 332.84 | 336.12 | 755.75 | 0.00 | 0.00 | 0.00 |
December | 416.40 | 180.18 | 236.22 | 276.88 | 974.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 949.31 | 400.18 | 549.13 | 1079.02 | 571.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 416.40 | 135.29 | 236.22 | 276.88 | 120.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1416.37 | 655.69 | 815.68 | 2007.98 | 1091.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.23 | 0.00 | 109.23 | 8.84 | 580.94 | 0.00 | 0.00 | 0.00 |
February | 149.48 | 0.00 | 149.48 | 17.04 | 599.71 | 0.00 | 0.00 | 0.00 |
March | 207.29 | 0.00 | 207.29 | 85.91 | 394.63 | 0.00 | 0.00 | 0.00 |
April | 248.98 | 0.71 | 248.27 | 171.78 | 279.64 | 0.00 | 0.00 | 0.00 |
May | 330.32 | 11.01 | 319.31 | 327.90 | 171.41 | 0.00 | 0.00 | 0.00 |
June | 350.30 | 18.82 | 331.48 | 445.29 | 94.52 | 0.00 | 0.00 | 0.00 |
July | 338.53 | 12.24 | 326.29 | 490.90 | 52.22 | 0.00 | 0.00 | 0.00 |
August | 299.92 | 3.57 | 296.35 | 427.26 | 74.32 | 0.00 | 0.00 | 0.00 |
September | 226.09 | 0.04 | 226.05 | 244.70 | 156.07 | 0.00 | 0.00 | 0.00 |
October | 195.67 | 0.00 | 195.67 | 144.44 | 290.37 | 0.00 | 0.00 | 0.00 |
November | 137.24 | 0.00 | 137.24 | 38.53 | 434.17 | 0.00 | 0.00 | 0.00 |
December | 95.28 | 0.00 | 95.28 | 4.94 | 555.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 224.46 | 3.89 | 220.57 | 201.87 | 305.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 95.28 | 0.00 | 95.28 | 4.94 | 52.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 350.30 | 18.82 | 331.48 | 490.90 | 599.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.24 | 0.00 | 109.24 | 8.84 | 580.97 | 0.00 | 0.00 | 0.00 |
February | 149.48 | 0.00 | 149.48 | 17.04 | 599.75 | 0.00 | 0.00 | 0.00 |
March | 207.30 | 0.00 | 207.30 | 85.91 | 394.65 | 0.00 | 0.00 | 0.00 |
April | 248.99 | 0.71 | 248.28 | 171.79 | 279.65 | 0.00 | 0.00 | 0.00 |
May | 330.33 | 11.01 | 319.33 | 327.91 | 171.42 | 0.00 | 0.00 | 0.00 |
June | 350.32 | 18.82 | 331.49 | 445.31 | 94.52 | 0.00 | 0.00 | 0.00 |
July | 338.55 | 12.24 | 326.30 | 490.92 | 52.22 | 0.00 | 0.00 | 0.00 |
August | 299.94 | 3.57 | 296.37 | 427.28 | 74.32 | 0.00 | 0.00 | 0.00 |
September | 226.10 | 0.04 | 226.06 | 244.70 | 156.08 | 0.00 | 0.00 | 0.00 |
October | 195.67 | 0.00 | 195.67 | 144.44 | 290.39 | 0.00 | 0.00 | 0.00 |
November | 137.25 | 0.00 | 137.25 | 38.53 | 434.19 | 0.00 | 0.00 | 0.00 |
December | 95.28 | 0.00 | 95.28 | 4.94 | 555.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 224.47 | 3.89 | 220.58 | 201.88 | 305.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 95.28 | 0.00 | 95.28 | 4.94 | 52.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 350.32 | 18.82 | 331.49 | 490.92 | 599.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.24 | 0.00 | 109.24 | 8.84 | 580.97 | 0.00 | 0.00 | 0.00 |
February | 149.48 | 0.00 | 149.48 | 17.04 | 599.75 | 0.00 | 0.00 | 0.00 |
March | 207.30 | 0.00 | 207.30 | 85.91 | 394.65 | 0.00 | 0.00 | 0.00 |
April | 248.99 | 0.71 | 248.28 | 171.79 | 279.65 | 0.00 | 0.00 | 0.00 |
May | 330.33 | 11.01 | 319.33 | 327.91 | 171.42 | 0.00 | 0.00 | 0.00 |
June | 350.32 | 18.82 | 331.49 | 445.31 | 94.52 | 0.00 | 0.00 | 0.00 |
July | 338.55 | 12.24 | 326.30 | 490.92 | 52.22 | 0.00 | 0.00 | 0.00 |
August | 299.94 | 3.57 | 296.37 | 427.28 | 74.32 | 0.00 | 0.00 | 0.00 |
September | 226.10 | 0.04 | 226.06 | 244.70 | 156.08 | 0.00 | 0.00 | 0.00 |
October | 195.67 | 0.00 | 195.67 | 144.44 | 290.39 | 0.00 | 0.00 | 0.00 |
November | 137.25 | 0.00 | 137.25 | 38.53 | 434.19 | 0.00 | 0.00 | 0.00 |
December | 95.28 | 0.00 | 95.28 | 4.94 | 555.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 224.47 | 3.89 | 220.58 | 201.88 | 305.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 95.28 | 0.00 | 95.28 | 4.94 | 52.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 350.32 | 18.82 | 331.49 | 490.92 | 599.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 439.00 | 176.00 | 263.00 | 282.65 | 1048.75 | 0.00 | 0.00 | 0.00 |
February | 680.80 | 317.59 | 363.21 | 494.77 | 1056.13 | 0.00 | 0.00 | 0.00 |
March | 868.49 | 369.37 | 499.12 | 785.11 | 751.74 | 0.00 | 0.00 | 0.00 |
April | 1042.25 | 456.54 | 585.71 | 1084.19 | 543.18 | 0.00 | 0.00 | 0.00 |
May | 1264.03 | 505.18 | 758.85 | 1495.15 | 350.12 | 0.00 | 0.00 | 0.00 |
June | 1171.49 | 424.07 | 747.42 | 1551.19 | 193.42 | 0.00 | 0.00 | 0.00 |
July | 1176.62 | 424.61 | 752.01 | 1682.21 | 108.95 | 0.00 | 0.00 | 0.00 |
August | 1324.90 | 597.39 | 727.50 | 1879.26 | 153.07 | 0.00 | 0.00 | 0.00 |
September | 988.12 | 443.33 | 544.79 | 1240.49 | 302.30 | 0.00 | 0.00 | 0.00 |
October | 895.80 | 406.01 | 489.80 | 996.58 | 558.50 | 0.00 | 0.00 | 0.00 |
November | 553.98 | 212.73 | 341.25 | 445.21 | 802.94 | 0.00 | 0.00 | 0.00 |
December | 431.58 | 202.64 | 228.94 | 296.33 | 998.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 904.52 | 378.38 | 526.14 | 1023.07 | 569.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 431.58 | 176.00 | 228.94 | 282.65 | 108.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1324.90 | 597.39 | 758.85 | 1879.26 | 1056.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.36 | 6.96 | 10.40 | 11.18 | 41.47 | 0.00 | 0.00 | 0.00 |
February | 26.92 | 12.56 | 14.36 | 19.56 | 41.76 | 0.00 | 0.00 | 0.00 |
March | 34.34 | 14.60 | 19.73 | 31.04 | 29.72 | 0.00 | 0.00 | 0.00 |
April | 41.21 | 18.05 | 23.16 | 42.87 | 21.48 | 0.00 | 0.00 | 0.00 |
May | 49.98 | 19.97 | 30.00 | 59.12 | 13.84 | 0.00 | 0.00 | 0.00 |
June | 46.32 | 16.77 | 29.55 | 61.33 | 7.65 | 0.00 | 0.00 | 0.00 |
July | 46.52 | 16.79 | 29.73 | 66.51 | 4.31 | 0.00 | 0.00 | 0.00 |
August | 52.39 | 23.62 | 28.76 | 74.30 | 6.05 | 0.00 | 0.00 | 0.00 |
September | 39.07 | 17.53 | 21.54 | 49.05 | 11.95 | 0.00 | 0.00 | 0.00 |
October | 35.42 | 16.05 | 19.37 | 39.40 | 22.08 | 0.00 | 0.00 | 0.00 |
November | 21.90 | 8.41 | 13.49 | 17.60 | 31.75 | 0.00 | 0.00 | 0.00 |
December | 17.06 | 8.01 | 9.05 | 11.72 | 39.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.76 | 14.96 | 20.80 | 40.45 | 22.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.06 | 6.96 | 9.05 | 11.18 | 4.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.39 | 23.62 | 30.00 | 74.30 | 41.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 565.09 | 370.03 | 195.07 | 575.89 | 528.07 | 0.00 | 0.00 | 0.00 |
February | 745.34 | 493.35 | 251.99 | 769.39 | 541.04 | 0.00 | 0.00 | 0.00 |
March | 672.44 | 373.21 | 299.23 | 736.12 | 397.37 | 0.00 | 0.00 | 0.00 |
April | 521.79 | 206.33 | 315.46 | 591.53 | 294.43 | 0.00 | 0.00 | 0.00 |
May | 457.27 | 95.38 | 361.89 | 552.99 | 185.16 | 0.00 | 0.00 | 0.00 |
June | 429.14 | 65.60 | 363.54 | 590.66 | 102.58 | 0.00 | 0.00 | 0.00 |
July | 449.82 | 78.13 | 371.69 | 681.49 | 55.77 | 0.00 | 0.00 | 0.00 |
August | 600.69 | 222.80 | 377.88 | 912.21 | 83.75 | 0.00 | 0.00 | 0.00 |
September | 651.76 | 337.11 | 314.64 | 876.71 | 167.11 | 0.00 | 0.00 | 0.00 |
October | 892.85 | 559.88 | 332.97 | 1118.82 | 304.91 | 0.00 | 0.00 | 0.00 |
November | 619.11 | 371.81 | 247.31 | 669.30 | 417.27 | 0.00 | 0.00 | 0.00 |
December | 612.48 | 434.82 | 177.66 | 640.92 | 505.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 600.80 | 299.73 | 301.07 | 726.47 | 297.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 429.14 | 65.60 | 177.66 | 552.99 | 55.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 892.85 | 559.88 | 377.88 | 1118.82 | 541.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 565.09 | 370.03 | 195.07 | 575.89 | 528.07 | 0.00 | 0.00 | 0.00 |
February | 745.34 | 493.35 | 251.99 | 769.39 | 541.04 | 0.00 | 0.00 | 0.00 |
March | 672.44 | 373.21 | 299.23 | 736.12 | 397.37 | 0.00 | 0.00 | 0.00 |
April | 521.79 | 206.33 | 315.46 | 591.53 | 294.43 | 0.00 | 0.00 | 0.00 |
May | 457.27 | 95.38 | 361.89 | 552.99 | 185.16 | 0.00 | 0.00 | 0.00 |
June | 429.14 | 65.60 | 363.54 | 590.66 | 102.58 | 0.00 | 0.00 | 0.00 |
July | 449.82 | 78.13 | 371.69 | 681.49 | 55.77 | 0.00 | 0.00 | 0.00 |
August | 600.69 | 222.80 | 377.88 | 912.21 | 83.75 | 0.00 | 0.00 | 0.00 |
September | 651.76 | 337.11 | 314.64 | 876.71 | 167.11 | 0.00 | 0.00 | 0.00 |
October | 892.85 | 559.88 | 332.97 | 1118.82 | 304.91 | 0.00 | 0.00 | 0.00 |
November | 619.11 | 371.81 | 247.31 | 669.30 | 417.27 | 0.00 | 0.00 | 0.00 |
December | 612.48 | 434.82 | 177.66 | 640.92 | 505.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 600.80 | 299.73 | 301.07 | 726.47 | 297.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 429.14 | 65.60 | 177.66 | 552.99 | 55.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 892.85 | 559.88 | 377.88 | 1118.82 | 541.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 565.06 | 370.00 | 195.06 | 575.86 | 528.03 | 0.00 | 0.00 | 0.00 |
February | 745.29 | 493.32 | 251.97 | 769.34 | 541.01 | 0.00 | 0.00 | 0.00 |
March | 672.40 | 373.19 | 299.21 | 736.07 | 397.34 | 0.00 | 0.00 | 0.00 |
April | 521.76 | 206.32 | 315.44 | 591.49 | 294.41 | 0.00 | 0.00 | 0.00 |
May | 457.24 | 95.37 | 361.87 | 552.96 | 185.15 | 0.00 | 0.00 | 0.00 |
June | 429.11 | 65.59 | 363.52 | 590.63 | 102.57 | 0.00 | 0.00 | 0.00 |
July | 449.79 | 78.13 | 371.67 | 681.45 | 55.77 | 0.00 | 0.00 | 0.00 |
August | 600.65 | 222.79 | 377.86 | 912.16 | 83.74 | 0.00 | 0.00 | 0.00 |
September | 651.71 | 337.09 | 314.62 | 876.65 | 167.10 | 0.00 | 0.00 | 0.00 |
October | 892.79 | 559.84 | 332.95 | 1118.75 | 304.89 | 0.00 | 0.00 | 0.00 |
November | 619.07 | 371.78 | 247.29 | 669.26 | 417.24 | 0.00 | 0.00 | 0.00 |
December | 612.44 | 434.79 | 177.65 | 640.88 | 505.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 600.77 | 299.71 | 301.06 | 726.42 | 297.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 429.11 | 65.59 | 177.65 | 552.96 | 55.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 892.79 | 559.84 | 377.86 | 1118.75 | 541.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 433.40 | 177.52 | 255.88 | 281.90 | 1070.64 | 0.00 | 0.00 | 0.00 |
February | 639.11 | 280.70 | 358.41 | 460.36 | 1101.26 | 0.00 | 0.00 | 0.00 |
March | 943.72 | 435.69 | 508.03 | 882.20 | 753.93 | 0.00 | 0.00 | 0.00 |
April | 1031.44 | 441.32 | 590.11 | 1085.83 | 561.56 | 0.00 | 0.00 | 0.00 |
May | 1201.52 | 456.29 | 745.23 | 1426.79 | 364.44 | 0.00 | 0.00 | 0.00 |
June | 1315.03 | 530.39 | 784.64 | 1752.65 | 208.56 | 0.00 | 0.00 | 0.00 |
July | 1231.60 | 463.78 | 767.82 | 1758.62 | 118.31 | 0.00 | 0.00 | 0.00 |
August | 1362.48 | 630.74 | 731.74 | 1941.61 | 166.78 | 0.00 | 0.00 | 0.00 |
September | 967.25 | 422.69 | 544.57 | 1227.46 | 317.00 | 0.00 | 0.00 | 0.00 |
October | 958.96 | 466.32 | 492.64 | 1087.66 | 578.75 | 0.00 | 0.00 | 0.00 |
November | 450.32 | 130.15 | 320.18 | 309.20 | 818.94 | 0.00 | 0.00 | 0.00 |
December | 400.55 | 173.32 | 227.23 | 262.39 | 1024.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 913.19 | 384.96 | 528.24 | 1043.89 | 587.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 400.55 | 130.15 | 227.23 | 262.39 | 118.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1362.48 | 630.74 | 784.64 | 1941.61 | 1101.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.14 | 7.02 | 10.12 | 11.15 | 42.33 | 0.00 | 0.00 | 0.00 |
February | 25.27 | 11.10 | 14.17 | 18.20 | 43.54 | 0.00 | 0.00 | 0.00 |
March | 37.31 | 17.23 | 20.09 | 34.88 | 29.81 | 0.00 | 0.00 | 0.00 |
April | 40.78 | 17.45 | 23.33 | 42.93 | 22.20 | 0.00 | 0.00 | 0.00 |
May | 47.51 | 18.04 | 29.47 | 56.41 | 14.41 | 0.00 | 0.00 | 0.00 |
June | 51.99 | 20.97 | 31.02 | 69.30 | 8.25 | 0.00 | 0.00 | 0.00 |
July | 48.70 | 18.34 | 30.36 | 69.53 | 4.68 | 0.00 | 0.00 | 0.00 |
August | 53.87 | 24.94 | 28.93 | 76.77 | 6.59 | 0.00 | 0.00 | 0.00 |
September | 38.24 | 16.71 | 21.53 | 48.53 | 12.53 | 0.00 | 0.00 | 0.00 |
October | 37.92 | 18.44 | 19.48 | 43.00 | 22.88 | 0.00 | 0.00 | 0.00 |
November | 17.81 | 5.15 | 12.66 | 12.23 | 32.38 | 0.00 | 0.00 | 0.00 |
December | 15.84 | 6.85 | 8.98 | 10.37 | 40.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.11 | 15.22 | 20.89 | 41.27 | 23.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.84 | 5.15 | 8.98 | 10.37 | 4.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.87 | 24.94 | 31.02 | 76.77 | 43.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 327.71 | 0.00 | 327.71 | 24.87 | 1745.19 | 0.00 | 0.00 | 0.00 |
February | 448.46 | 0.00 | 448.46 | 46.35 | 1821.79 | 0.00 | 0.00 | 0.00 |
March | 621.90 | 0.00 | 621.90 | 235.30 | 1227.00 | 0.00 | 0.00 | 0.00 |
April | 746.98 | 2.12 | 744.86 | 480.68 | 885.94 | 0.00 | 0.00 | 0.00 |
May | 991.01 | 33.02 | 957.99 | 936.56 | 552.61 | 0.00 | 0.00 | 0.00 |
June | 1050.95 | 56.47 | 994.48 | 1310.20 | 301.12 | 0.00 | 0.00 | 0.00 |
July | 1015.65 | 36.73 | 978.92 | 1452.91 | 169.40 | 0.00 | 0.00 | 0.00 |
August | 899.81 | 10.71 | 889.10 | 1272.18 | 229.72 | 0.00 | 0.00 | 0.00 |
September | 678.31 | 0.13 | 678.18 | 729.82 | 465.29 | 0.00 | 0.00 | 0.00 |
October | 587.03 | 0.00 | 587.03 | 433.53 | 852.82 | 0.00 | 0.00 | 0.00 |
November | 411.74 | 0.00 | 411.74 | 118.20 | 1262.97 | 0.00 | 0.00 | 0.00 |
December | 285.85 | 0.00 | 285.85 | 14.97 | 1641.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 673.41 | 11.66 | 661.75 | 591.63 | 924.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 285.85 | 0.00 | 285.85 | 14.97 | 169.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1050.95 | 56.47 | 994.48 | 1452.91 | 1821.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 456.37 | 182.97 | 273.40 | 288.47 | 1083.39 | 0.00 | 0.00 | 0.00 |
February | 707.73 | 330.16 | 377.57 | 503.55 | 1098.50 | 0.00 | 0.00 | 0.00 |
March | 902.84 | 383.99 | 518.86 | 794.79 | 794.62 | 0.00 | 0.00 | 0.00 |
April | 1083.48 | 474.60 | 608.88 | 1103.60 | 577.13 | 0.00 | 0.00 | 0.00 |
May | 1314.03 | 525.17 | 788.86 | 1525.88 | 377.81 | 0.00 | 0.00 | 0.00 |
June | 1217.83 | 440.84 | 776.98 | 1594.13 | 206.37 | 0.00 | 0.00 | 0.00 |
July | 1223.16 | 441.41 | 781.75 | 1734.68 | 115.54 | 0.00 | 0.00 | 0.00 |
August | 1377.31 | 621.03 | 756.28 | 1944.25 | 155.03 | 0.00 | 0.00 | 0.00 |
September | 1027.20 | 460.87 | 566.34 | 1282.99 | 303.09 | 0.00 | 0.00 | 0.00 |
October | 931.23 | 422.07 | 509.17 | 1033.42 | 554.49 | 0.00 | 0.00 | 0.00 |
November | 575.90 | 221.15 | 354.75 | 464.57 | 797.15 | 0.00 | 0.00 | 0.00 |
December | 448.66 | 210.66 | 237.99 | 306.47 | 1012.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 940.30 | 393.35 | 546.95 | 1051.85 | 586.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 448.66 | 182.97 | 237.99 | 288.47 | 115.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1377.31 | 621.03 | 788.86 | 1944.25 | 1098.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1695.32 | 1110.10 | 585.21 | 1691.49 | 1571.65 | 0.00 | 0.00 | 0.00 |
February | 2236.06 | 1480.09 | 755.97 | 2263.01 | 1604.66 | 0.00 | 0.00 | 0.00 |
March | 2017.35 | 1119.66 | 897.69 | 2160.76 | 1203.00 | 0.00 | 0.00 | 0.00 |
April | 1565.39 | 619.00 | 946.39 | 1729.64 | 915.91 | 0.00 | 0.00 | 0.00 |
May | 1371.84 | 286.14 | 1085.69 | 1605.79 | 595.23 | 0.00 | 0.00 | 0.00 |
June | 1287.43 | 196.80 | 1090.63 | 1743.85 | 323.04 | 0.00 | 0.00 | 0.00 |
July | 1349.48 | 234.40 | 1115.08 | 2026.35 | 174.82 | 0.00 | 0.00 | 0.00 |
August | 1802.08 | 668.42 | 1133.66 | 2727.45 | 244.24 | 0.00 | 0.00 | 0.00 |
September | 1955.30 | 1011.36 | 943.94 | 2621.58 | 477.65 | 0.00 | 0.00 | 0.00 |
October | 2678.59 | 1679.67 | 998.92 | 3347.09 | 854.52 | 0.00 | 0.00 | 0.00 |
November | 1857.37 | 1115.44 | 741.93 | 1994.30 | 1193.04 | 0.00 | 0.00 | 0.00 |
December | 1837.47 | 1304.48 | 532.99 | 1901.62 | 1465.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1802.44 | 899.21 | 903.23 | 2151.57 | 881.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1287.43 | 196.80 | 532.99 | 1605.79 | 174.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2678.59 | 1679.67 | 1133.66 | 3347.09 | 1604.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 450.54 | 184.54 | 266.00 | 286.85 | 1108.84 | 0.00 | 0.00 | 0.00 |
February | 664.38 | 291.80 | 372.58 | 466.98 | 1146.83 | 0.00 | 0.00 | 0.00 |
March | 981.04 | 452.92 | 528.12 | 898.09 | 792.45 | 0.00 | 0.00 | 0.00 |
April | 1072.24 | 458.78 | 613.45 | 1107.28 | 595.81 | 0.00 | 0.00 | 0.00 |
May | 1249.05 | 474.34 | 774.71 | 1458.61 | 392.13 | 0.00 | 0.00 | 0.00 |
June | 1367.04 | 551.37 | 815.68 | 1807.14 | 218.77 | 0.00 | 0.00 | 0.00 |
July | 1280.31 | 482.12 | 798.18 | 1817.03 | 123.38 | 0.00 | 0.00 | 0.00 |
August | 1416.37 | 655.69 | 760.68 | 2012.64 | 167.29 | 0.00 | 0.00 | 0.00 |
September | 1005.51 | 439.41 | 566.10 | 1273.20 | 317.94 | 0.00 | 0.00 | 0.00 |
October | 996.89 | 484.76 | 512.13 | 1130.87 | 572.67 | 0.00 | 0.00 | 0.00 |
November | 468.13 | 135.29 | 332.84 | 322.97 | 818.12 | 0.00 | 0.00 | 0.00 |
December | 416.40 | 180.18 | 236.22 | 270.26 | 1042.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 949.31 | 400.18 | 549.13 | 1075.34 | 604.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 416.40 | 135.29 | 236.22 | 270.26 | 123.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1416.37 | 655.69 | 815.68 | 2012.64 | 1146.83 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.877739E+09 | 0.00 | 0.877739E+09 | 75868128.06 | 0.447637E+10 |
February | 0.108491E+10 | 0.00 | 0.108491E+10 | 0.125369E+09 | 0.419809E+10 |
March | 0.166569E+10 | 0.00 | 0.166569E+10 | 0.662222E+09 | 0.308126E+10 |
April | 0.193618E+10 | 5507101.70 | 0.193068E+10 | 0.128288E+10 | 0.214658E+10 |
May | 0.265432E+10 | 88443495.07 | 0.256588E+10 | 0.252766E+10 | 0.141482E+10 |
June | 0.272407E+10 | 0.146376E+09 | 0.257770E+10 | 0.338696E+10 | 0.756099E+09 |
July | 0.272030E+10 | 98375305.77 | 0.262193E+10 | 0.387106E+10 | 0.444355E+09 |
August | 0.241006E+10 | 28683108.84 | 0.238138E+10 | 0.339582E+10 | 0.594791E+09 |
September | 0.175818E+10 | 329235.52 | 0.175785E+10 | 0.190056E+10 | 0.114142E+10 |
October | 0.157230E+10 | 0.00 | 0.157230E+10 | 0.120712E+10 | 0.212074E+10 |
November | 0.106724E+10 | 0.00 | 0.106724E+10 | 0.350104E+09 | 0.302057E+10 |
December | 0.765622E+09 | 0.00 | 0.765622E+09 | 52391567.24 | 0.411778E+10 |
Annual Sum or Average | 0.212366E+11 | 0.367714E+09 | 0.208689E+11 | 0.188380E+11 | 0.275129E+11 |
Minimum of Months | 0.765622E+09 | 0.00 | 0.765622E+09 | 52391567.24 | 0.444355E+09 |
Maximum of Months | 0.272407E+10 | 0.146376E+09 | 0.262193E+10 | 0.387106E+10 | 0.447637E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122234E+10 | 0.490060E+09 | 0.732281E+09 | 0.789330E+09 | 0.277852E+10 |
February | 0.171214E+10 | 0.798716E+09 | 0.913427E+09 | 0.124746E+10 | 0.252623E+10 |
March | 0.241818E+10 | 0.102847E+10 | 0.138971E+10 | 0.216386E+10 | 0.199473E+10 |
April | 0.280837E+10 | 0.123015E+10 | 0.157822E+10 | 0.289184E+10 | 0.140462E+10 |
May | 0.351950E+10 | 0.140660E+10 | 0.211289E+10 | 0.410175E+10 | 0.970101E+09 |
June | 0.315661E+10 | 0.114267E+10 | 0.201394E+10 | 0.413261E+10 | 0.518224E+09 |
July | 0.327611E+10 | 0.118227E+10 | 0.209384E+10 | 0.463968E+10 | 0.302160E+09 |
August | 0.368898E+10 | 0.166336E+10 | 0.202562E+10 | 0.520544E+10 | 0.401404E+09 |
September | 0.266251E+10 | 0.119456E+10 | 0.146794E+10 | 0.333713E+10 | 0.746584E+09 |
October | 0.249422E+10 | 0.113046E+10 | 0.136375E+10 | 0.280164E+10 | 0.138731E+10 |
November | 0.149272E+10 | 0.573221E+09 | 0.919503E+09 | 0.124966E+10 | 0.190929E+10 |
December | 0.120168E+10 | 0.564236E+09 | 0.637445E+09 | 0.850302E+09 | 0.253637E+10 |
Annual Sum or Average | 0.296533E+11 | 0.124048E+11 | 0.172486E+11 | 0.334107E+11 | 0.174755E+11 |
Minimum of Months | 0.120168E+10 | 0.490060E+09 | 0.637445E+09 | 0.789330E+09 | 0.302160E+09 |
Maximum of Months | 0.368898E+10 | 0.166336E+10 | 0.211289E+10 | 0.520544E+10 | 0.277852E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454073E+10 | 0.297330E+10 | 0.156743E+10 | 0.455955E+10 | 0.401307E+10 |
February | 0.540948E+10 | 0.358064E+10 | 0.182885E+10 | 0.551879E+10 | 0.368240E+10 |
March | 0.540327E+10 | 0.299891E+10 | 0.240436E+10 | 0.582155E+10 | 0.302322E+10 |
April | 0.405750E+10 | 0.160446E+10 | 0.245304E+10 | 0.451202E+10 | 0.222777E+10 |
May | 0.367432E+10 | 0.766406E+09 | 0.290792E+10 | 0.430924E+10 | 0.152321E+10 |
June | 0.333701E+10 | 0.510096E+09 | 0.282691E+10 | 0.450705E+10 | 0.809864E+09 |
July | 0.361445E+10 | 0.627829E+09 | 0.298662E+10 | 0.540391E+10 | 0.457148E+09 |
August | 0.482670E+10 | 0.179030E+10 | 0.303640E+10 | 0.728608E+10 | 0.632365E+09 |
September | 0.506813E+10 | 0.262144E+10 | 0.244668E+10 | 0.679633E+10 | 0.117842E+10 |
October | 0.717434E+10 | 0.449882E+10 | 0.267551E+10 | 0.899177E+10 | 0.214719E+10 |
November | 0.481431E+10 | 0.289122E+10 | 0.192309E+10 | 0.523118E+10 | 0.286541E+10 |
December | 0.492147E+10 | 0.349392E+10 | 0.142756E+10 | 0.514801E+10 | 0.367014E+10 |
Annual Sum or Average | 0.568417E+11 | 0.283574E+11 | 0.284844E+11 | 0.680855E+11 | 0.262302E+11 |
Minimum of Months | 0.333701E+10 | 0.510096E+09 | 0.142756E+10 | 0.430924E+10 | 0.457148E+09 |
Maximum of Months | 0.717434E+10 | 0.449882E+10 | 0.303640E+10 | 0.899177E+10 | 0.401307E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120672E+10 | 0.494277E+09 | 0.712445E+09 | 0.778423E+09 | 0.284121E+10 |
February | 0.160728E+10 | 0.705922E+09 | 0.901354E+09 | 0.114380E+10 | 0.263966E+10 |
March | 0.262763E+10 | 0.121310E+10 | 0.141452E+10 | 0.242831E+10 | 0.198983E+10 |
April | 0.277923E+10 | 0.118916E+10 | 0.159007E+10 | 0.289189E+10 | 0.144584E+10 |
May | 0.334544E+10 | 0.127047E+10 | 0.207497E+10 | 0.391288E+10 | 0.100321E+10 |
June | 0.354337E+10 | 0.142914E+10 | 0.211423E+10 | 0.467332E+10 | 0.548397E+09 |
July | 0.342918E+10 | 0.129132E+10 | 0.213786E+10 | 0.485012E+10 | 0.322409E+09 |
August | 0.379360E+10 | 0.175619E+10 | 0.203741E+10 | 0.537818E+10 | 0.433552E+09 |
September | 0.260628E+10 | 0.113894E+10 | 0.146734E+10 | 0.330320E+10 | 0.782663E+09 |
October | 0.267006E+10 | 0.129839E+10 | 0.137168E+10 | 0.305499E+10 | 0.143029E+10 |
November | 0.121341E+10 | 0.350683E+09 | 0.862723E+09 | 0.871226E+09 | 0.195892E+10 |
December | 0.111528E+10 | 0.482583E+09 | 0.632693E+09 | 0.741603E+09 | 0.261122E+10 |
Annual Sum or Average | 0.299375E+11 | 0.126202E+11 | 0.173173E+11 | 0.340279E+11 | 0.180072E+11 |
Minimum of Months | 0.111528E+10 | 0.350683E+09 | 0.632693E+09 | 0.741603E+09 | 0.322409E+09 |
Maximum of Months | 0.379360E+10 | 0.175619E+10 | 0.213786E+10 | 0.537818E+10 | 0.284121E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292566E+09 | 0.00 | 0.292566E+09 | 23677142.17 | 0.155598E+10 |
February | 0.361619E+09 | 0.00 | 0.361619E+09 | 41213606.41 | 0.145082E+10 |
March | 0.555204E+09 | 0.00 | 0.555204E+09 | 0.230106E+09 | 0.105697E+10 |
April | 0.645364E+09 | 1835613.72 | 0.643528E+09 | 0.445264E+09 | 0.724819E+09 |
May | 0.884732E+09 | 29479770.21 | 0.855252E+09 | 0.878253E+09 | 0.459114E+09 |
June | 0.907981E+09 | 48789636.46 | 0.859192E+09 | 0.115420E+10 | 0.244995E+09 |
July | 0.906725E+09 | 32790217.14 | 0.873935E+09 | 0.131483E+10 | 0.139857E+09 |
August | 0.803315E+09 | 9560583.93 | 0.793755E+09 | 0.114437E+10 | 0.199056E+09 |
September | 0.586032E+09 | 109739.98 | 0.585922E+09 | 0.634251E+09 | 0.404527E+09 |
October | 0.524074E+09 | 0.00 | 0.524074E+09 | 0.386869E+09 | 0.777737E+09 |
November | 0.355730E+09 | 0.00 | 0.355730E+09 | 99858308.17 | 0.112536E+10 |
December | 0.255195E+09 | 0.00 | 0.255195E+09 | 13237035.25 | 0.148708E+10 |
Annual Sum or Average | 0.707854E+10 | 0.122566E+09 | 0.695597E+10 | 0.636612E+10 | 0.962631E+10 |
Minimum of Months | 0.255195E+09 | 0.00 | 0.255195E+09 | 13237035.25 | 0.139857E+09 |
Maximum of Months | 0.907981E+09 | 48789636.46 | 0.873935E+09 | 0.131483E+10 | 0.155598E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292577E+09 | 0.00 | 0.292577E+09 | 23675757.33 | 0.155608E+10 |
February | 0.361633E+09 | 0.00 | 0.361633E+09 | 41212673.75 | 0.145091E+10 |
March | 0.555226E+09 | 0.00 | 0.555226E+09 | 0.230109E+09 | 0.105704E+10 |
April | 0.645390E+09 | 1835663.06 | 0.643554E+09 | 0.445277E+09 | 0.724865E+09 |
May | 0.884767E+09 | 29480562.63 | 0.855286E+09 | 0.878280E+09 | 0.459141E+09 |
June | 0.908017E+09 | 48790947.93 | 0.859226E+09 | 0.115424E+10 | 0.245008E+09 |
July | 0.906761E+09 | 32791098.55 | 0.873970E+09 | 0.131488E+10 | 0.139864E+09 |
August | 0.803349E+09 | 9560840.92 | 0.793788E+09 | 0.114442E+10 | 0.199065E+09 |
September | 0.586056E+09 | 109742.93 | 0.585946E+09 | 0.634275E+09 | 0.404549E+09 |
October | 0.524095E+09 | 0.00 | 0.524095E+09 | 0.386881E+09 | 0.777783E+09 |
November | 0.355744E+09 | 0.00 | 0.355744E+09 | 99857849.13 | 0.112543E+10 |
December | 0.255205E+09 | 0.00 | 0.255205E+09 | 13236251.92 | 0.148717E+10 |
Annual Sum or Average | 0.707882E+10 | 0.122569E+09 | 0.695625E+10 | 0.636634E+10 | 0.962692E+10 |
Minimum of Months | 0.255205E+09 | 0.00 | 0.255205E+09 | 13236251.92 | 0.139864E+09 |
Maximum of Months | 0.908017E+09 | 48790947.93 | 0.873970E+09 | 0.131488E+10 | 0.155608E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292577E+09 | 0.00 | 0.292577E+09 | 23675757.33 | 0.155608E+10 |
February | 0.361633E+09 | 0.00 | 0.361633E+09 | 41212673.75 | 0.145091E+10 |
March | 0.555226E+09 | 0.00 | 0.555226E+09 | 0.230109E+09 | 0.105704E+10 |
April | 0.645390E+09 | 1835663.06 | 0.643554E+09 | 0.445277E+09 | 0.724865E+09 |
May | 0.884767E+09 | 29480562.63 | 0.855286E+09 | 0.878280E+09 | 0.459141E+09 |
June | 0.908017E+09 | 48790947.93 | 0.859226E+09 | 0.115424E+10 | 0.245008E+09 |
July | 0.906761E+09 | 32791098.55 | 0.873970E+09 | 0.131488E+10 | 0.139864E+09 |
August | 0.803349E+09 | 9560840.92 | 0.793788E+09 | 0.114442E+10 | 0.199065E+09 |
September | 0.586056E+09 | 109742.93 | 0.585946E+09 | 0.634275E+09 | 0.404549E+09 |
October | 0.524095E+09 | 0.00 | 0.524095E+09 | 0.386881E+09 | 0.777783E+09 |
November | 0.355744E+09 | 0.00 | 0.355744E+09 | 99857849.13 | 0.112543E+10 |
December | 0.255205E+09 | 0.00 | 0.255205E+09 | 13236251.92 | 0.148717E+10 |
Annual Sum or Average | 0.707882E+10 | 0.122569E+09 | 0.695625E+10 | 0.636634E+10 | 0.962692E+10 |
Minimum of Months | 0.255205E+09 | 0.00 | 0.255205E+09 | 13236251.92 | 0.139864E+09 |
Maximum of Months | 0.908017E+09 | 48790947.93 | 0.873970E+09 | 0.131488E+10 | 0.155608E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117583E+10 | 0.471411E+09 | 0.704419E+09 | 0.757045E+09 | 0.280896E+10 |
February | 0.164699E+10 | 0.768321E+09 | 0.878673E+09 | 0.119695E+10 | 0.255498E+10 |
March | 0.232617E+10 | 0.989331E+09 | 0.133684E+10 | 0.210285E+10 | 0.201346E+10 |
April | 0.270151E+10 | 0.118334E+10 | 0.151817E+10 | 0.281021E+10 | 0.140792E+10 |
May | 0.338558E+10 | 0.135308E+10 | 0.203250E+10 | 0.400461E+10 | 0.937769E+09 |
June | 0.303650E+10 | 0.109919E+10 | 0.193731E+10 | 0.402069E+10 | 0.501357E+09 |
July | 0.315145E+10 | 0.113728E+10 | 0.201418E+10 | 0.450563E+10 | 0.291809E+09 |
August | 0.354861E+10 | 0.160006E+10 | 0.194855E+10 | 0.503341E+10 | 0.409996E+09 |
September | 0.256120E+10 | 0.114910E+10 | 0.141209E+10 | 0.321535E+10 | 0.783556E+09 |
October | 0.239931E+10 | 0.108745E+10 | 0.131187E+10 | 0.266925E+10 | 0.149588E+10 |
November | 0.143592E+10 | 0.551408E+09 | 0.884517E+09 | 0.115397E+10 | 0.208122E+10 |
December | 0.115596E+10 | 0.542764E+09 | 0.613192E+09 | 0.793684E+09 | 0.267499E+10 |
Annual Sum or Average | 0.285250E+11 | 0.119327E+11 | 0.165923E+11 | 0.322637E+11 | 0.179619E+11 |
Minimum of Months | 0.115596E+10 | 0.471411E+09 | 0.613192E+09 | 0.757045E+09 | 0.291809E+09 |
Maximum of Months | 0.354861E+10 | 0.160006E+10 | 0.203250E+10 | 0.503341E+10 | 0.280896E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 46491248.53 | 18639173.47 | 27852075.06 | 29932861.31 | 0.111064E+09 |
February | 65120688.91 | 30378734.06 | 34741954.85 | 47326480.70 | 0.101022E+09 |
March | 91974516.67 | 39117249.61 | 52857267.06 | 83144718.06 | 79610243.10 |
April | 0.106815E+09 | 46788213.91 | 60027079.77 | 0.111113E+09 | 55667969.02 |
May | 0.133863E+09 | 53499380.13 | 80363332.10 | 0.158339E+09 | 37078556.12 |
June | 0.120060E+09 | 43460819.36 | 76599620.23 | 0.158975E+09 | 19823198.01 |
July | 0.124606E+09 | 44966859.13 | 79638710.84 | 0.178148E+09 | 11537872.21 |
August | 0.140309E+09 | 63265002.36 | 77043847.34 | 0.199016E+09 | 16210860.51 |
September | 0.101267E+09 | 45434569.04 | 55832907.16 | 0.127132E+09 | 30981098.00 |
October | 94866683.40 | 42996643.49 | 51870039.91 | 0.105540E+09 | 59145912.41 |
November | 56775167.18 | 21802171.41 | 34972995.77 | 45627062.66 | 82289481.16 |
December | 45705453.17 | 21460412.81 | 24245040.36 | 31381544.06 | 0.105767E+09 |
Annual Sum or Average | 0.112785E+10 | 0.471809E+09 | 0.656045E+09 | 0.127568E+10 | 0.710197E+09 |
Minimum of Months | 45705453.17 | 18639173.47 | 24245040.36 | 29932861.31 | 11537872.21 |
Maximum of Months | 0.140309E+09 | 63265002.36 | 80363332.10 | 0.199016E+09 | 0.111064E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151355E+10 | 0.991081E+09 | 0.522470E+09 | 0.154247E+10 | 0.141437E+10 |
February | 0.180313E+10 | 0.119352E+10 | 0.609607E+09 | 0.186130E+10 | 0.130889E+10 |
March | 0.180106E+10 | 0.999616E+09 | 0.801445E+09 | 0.197162E+10 | 0.106431E+10 |
April | 0.135248E+10 | 0.534808E+09 | 0.817672E+09 | 0.153324E+10 | 0.763150E+09 |
May | 0.122476E+10 | 0.255463E+09 | 0.969297E+09 | 0.148114E+10 | 0.495926E+09 |
June | 0.111232E+10 | 0.170029E+09 | 0.942296E+09 | 0.153100E+10 | 0.265886E+09 |
July | 0.120480E+10 | 0.209272E+09 | 0.995531E+09 | 0.182532E+10 | 0.149372E+09 |
August | 0.160888E+10 | 0.596755E+09 | 0.101212E+10 | 0.244327E+10 | 0.224309E+09 |
September | 0.168935E+10 | 0.873796E+09 | 0.815553E+09 | 0.227243E+10 | 0.433143E+09 |
October | 0.239140E+10 | 0.149958E+10 | 0.891826E+09 | 0.299666E+10 | 0.816665E+09 |
November | 0.160474E+10 | 0.963721E+09 | 0.641020E+09 | 0.173483E+10 | 0.108157E+10 |
December | 0.164046E+10 | 0.116462E+10 | 0.475845E+09 | 0.171665E+10 | 0.135268E+10 |
Annual Sum or Average | 0.189469E+11 | 0.945226E+10 | 0.949469E+10 | 0.229099E+11 | 0.937027E+10 |
Minimum of Months | 0.111232E+10 | 0.170029E+09 | 0.475845E+09 | 0.148114E+10 | 0.149372E+09 |
Maximum of Months | 0.239140E+10 | 0.149958E+10 | 0.101212E+10 | 0.299666E+10 | 0.141437E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151355E+10 | 0.991081E+09 | 0.522470E+09 | 0.154247E+10 | 0.141437E+10 |
February | 0.180313E+10 | 0.119352E+10 | 0.609607E+09 | 0.186130E+10 | 0.130889E+10 |
March | 0.180106E+10 | 0.999616E+09 | 0.801445E+09 | 0.197162E+10 | 0.106431E+10 |
April | 0.135248E+10 | 0.534808E+09 | 0.817672E+09 | 0.153324E+10 | 0.763150E+09 |
May | 0.122476E+10 | 0.255463E+09 | 0.969297E+09 | 0.148114E+10 | 0.495926E+09 |
June | 0.111232E+10 | 0.170029E+09 | 0.942296E+09 | 0.153100E+10 | 0.265886E+09 |
July | 0.120480E+10 | 0.209272E+09 | 0.995531E+09 | 0.182532E+10 | 0.149372E+09 |
August | 0.160888E+10 | 0.596755E+09 | 0.101212E+10 | 0.244327E+10 | 0.224309E+09 |
September | 0.168935E+10 | 0.873796E+09 | 0.815553E+09 | 0.227243E+10 | 0.433143E+09 |
October | 0.239140E+10 | 0.149958E+10 | 0.891826E+09 | 0.299666E+10 | 0.816665E+09 |
November | 0.160474E+10 | 0.963721E+09 | 0.641020E+09 | 0.173483E+10 | 0.108157E+10 |
December | 0.164046E+10 | 0.116462E+10 | 0.475845E+09 | 0.171665E+10 | 0.135268E+10 |
Annual Sum or Average | 0.189469E+11 | 0.945226E+10 | 0.949469E+10 | 0.229099E+11 | 0.937027E+10 |
Minimum of Months | 0.111232E+10 | 0.170029E+09 | 0.475845E+09 | 0.148114E+10 | 0.149372E+09 |
Maximum of Months | 0.239140E+10 | 0.149958E+10 | 0.101212E+10 | 0.299666E+10 | 0.141437E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151345E+10 | 0.991018E+09 | 0.522437E+09 | 0.154238E+10 | 0.141428E+10 |
February | 0.180302E+10 | 0.119345E+10 | 0.609569E+09 | 0.186119E+10 | 0.130881E+10 |
March | 0.180095E+10 | 0.999553E+09 | 0.801394E+09 | 0.197149E+10 | 0.106425E+10 |
April | 0.135240E+10 | 0.534774E+09 | 0.817621E+09 | 0.153315E+10 | 0.763102E+09 |
May | 0.122468E+10 | 0.255447E+09 | 0.969236E+09 | 0.148105E+10 | 0.495895E+09 |
June | 0.111225E+10 | 0.170018E+09 | 0.942237E+09 | 0.153090E+10 | 0.265870E+09 |
July | 0.120473E+10 | 0.209259E+09 | 0.995468E+09 | 0.182520E+10 | 0.149362E+09 |
August | 0.160878E+10 | 0.596718E+09 | 0.101206E+10 | 0.244312E+10 | 0.224295E+09 |
September | 0.168924E+10 | 0.873741E+09 | 0.815501E+09 | 0.227229E+10 | 0.433115E+09 |
October | 0.239125E+10 | 0.149948E+10 | 0.891770E+09 | 0.299647E+10 | 0.816614E+09 |
November | 0.160464E+10 | 0.963660E+09 | 0.640979E+09 | 0.173472E+10 | 0.108150E+10 |
December | 0.164036E+10 | 0.116454E+10 | 0.475815E+09 | 0.171654E+10 | 0.135259E+10 |
Annual Sum or Average | 0.189457E+11 | 0.945166E+10 | 0.949409E+10 | 0.229085E+11 | 0.936968E+10 |
Minimum of Months | 0.111225E+10 | 0.170018E+09 | 0.475815E+09 | 0.148105E+10 | 0.149362E+09 |
Maximum of Months | 0.239125E+10 | 0.149948E+10 | 0.101206E+10 | 0.299647E+10 | 0.141428E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116081E+10 | 0.475470E+09 | 0.685340E+09 | 0.755033E+09 | 0.286760E+10 |
February | 0.154612E+10 | 0.679061E+09 | 0.867062E+09 | 0.111371E+10 | 0.266417E+10 |
March | 0.252765E+10 | 0.116694E+10 | 0.136071E+10 | 0.236288E+10 | 0.201934E+10 |
April | 0.267349E+10 | 0.114391E+10 | 0.152958E+10 | 0.281448E+10 | 0.145558E+10 |
May | 0.321816E+10 | 0.122213E+10 | 0.199603E+10 | 0.382152E+10 | 0.976125E+09 |
June | 0.340856E+10 | 0.137476E+10 | 0.203379E+10 | 0.454286E+10 | 0.540585E+09 |
July | 0.329871E+10 | 0.124219E+10 | 0.205652E+10 | 0.471029E+10 | 0.316882E+09 |
August | 0.364927E+10 | 0.168936E+10 | 0.195990E+10 | 0.520041E+10 | 0.446697E+09 |
September | 0.250712E+10 | 0.109560E+10 | 0.141152E+10 | 0.318159E+10 | 0.821662E+09 |
October | 0.256847E+10 | 0.124898E+10 | 0.131949E+10 | 0.291318E+10 | 0.155013E+10 |
November | 0.116724E+10 | 0.337339E+09 | 0.829900E+09 | 0.801459E+09 | 0.212269E+10 |
December | 0.107284E+10 | 0.464221E+09 | 0.608622E+09 | 0.702787E+09 | 0.274500E+10 |
Annual Sum or Average | 0.287984E+11 | 0.121400E+11 | 0.166585E+11 | 0.329202E+11 | 0.185264E+11 |
Minimum of Months | 0.107284E+10 | 0.337339E+09 | 0.608622E+09 | 0.702787E+09 | 0.316882E+09 |
Maximum of Months | 0.364927E+10 | 0.168936E+10 | 0.205652E+10 | 0.520041E+10 | 0.286760E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45897219.76 | 18799578.49 | 27097641.27 | 29853188.25 | 0.113382E+09 |
February | 61132159.56 | 26849383.05 | 34282776.51 | 44035074.27 | 0.105339E+09 |
March | 99940809.17 | 46139769.68 | 53801039.48 | 93425908.93 | 79842766.78 |
April | 0.105707E+09 | 45229190.01 | 60477938.52 | 0.111282E+09 | 57552163.24 |
May | 0.127243E+09 | 48321638.08 | 78921059.36 | 0.151099E+09 | 38595104.92 |
June | 0.134771E+09 | 54356766.41 | 80414196.70 | 0.179620E+09 | 21374234.36 |
July | 0.130428E+09 | 49114806.49 | 81312788.21 | 0.186240E+09 | 12529195.30 |
August | 0.144288E+09 | 66795753.60 | 77492599.82 | 0.205619E+09 | 17661963.94 |
September | 99128965.29 | 43318956.13 | 55810009.16 | 0.125797E+09 | 32487745.01 |
October | 0.101555E+09 | 49383479.05 | 52171383.98 | 0.115184E+09 | 61290598.06 |
November | 46151441.29 | 13338037.77 | 32813403.52 | 31688808.05 | 83929269.99 |
December | 42419103.52 | 18354807.59 | 24064295.94 | 27787426.51 | 0.108535E+09 |
Annual Sum or Average | 0.113866E+10 | 0.480002E+09 | 0.658659E+09 | 0.130163E+10 | 0.732519E+09 |
Minimum of Months | 42419103.52 | 13338037.77 | 24064295.94 | 27787426.51 | 12529195.30 |
Maximum of Months | 0.144288E+09 | 66795753.60 | 81312788.21 | 0.205619E+09 | 0.113382E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.877739E+09 | 0.00 | 0.877739E+09 | 66611236.78 | 0.467431E+10 |
February | 0.108491E+10 | 0.00 | 0.108491E+10 | 0.112120E+09 | 0.440728E+10 |
March | 0.166569E+10 | 0.00 | 0.166569E+10 | 0.630220E+09 | 0.328641E+10 |
April | 0.193618E+10 | 5507101.70 | 0.193068E+10 | 0.124591E+10 | 0.229635E+10 |
May | 0.265432E+10 | 88443495.07 | 0.256588E+10 | 0.250849E+10 | 0.148012E+10 |
June | 0.272407E+10 | 0.146376E+09 | 0.257770E+10 | 0.339605E+10 | 0.780492E+09 |
July | 0.272030E+10 | 98375305.77 | 0.262193E+10 | 0.389148E+10 | 0.453717E+09 |
August | 0.241006E+10 | 28683108.84 | 0.238138E+10 | 0.340740E+10 | 0.615274E+09 |
September | 0.175818E+10 | 329235.52 | 0.175785E+10 | 0.189168E+10 | 0.120603E+10 |
October | 0.157230E+10 | 0.00 | 0.157230E+10 | 0.116117E+10 | 0.228420E+10 |
November | 0.106724E+10 | 0.00 | 0.106724E+10 | 0.306367E+09 | 0.327362E+10 |
December | 0.765622E+09 | 0.00 | 0.765622E+09 | 40093911.10 | 0.439643E+10 |
Annual Sum or Average | 0.212366E+11 | 0.367714E+09 | 0.208689E+11 | 0.186576E+11 | 0.291542E+11 |
Minimum of Months | 0.765622E+09 | 0.00 | 0.765622E+09 | 40093911.10 | 0.453717E+09 |
Maximum of Months | 0.272407E+10 | 0.146376E+09 | 0.262193E+10 | 0.389148E+10 | 0.467431E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122234E+10 | 0.490060E+09 | 0.732281E+09 | 0.772649E+09 | 0.290176E+10 |
February | 0.171214E+10 | 0.798716E+09 | 0.913427E+09 | 0.121818E+10 | 0.265749E+10 |
March | 0.241818E+10 | 0.102847E+10 | 0.138971E+10 | 0.212876E+10 | 0.212831E+10 |
April | 0.280837E+10 | 0.123015E+10 | 0.157822E+10 | 0.286052E+10 | 0.149591E+10 |
May | 0.351950E+10 | 0.140660E+10 | 0.211289E+10 | 0.408691E+10 | 0.101194E+10 |
June | 0.315661E+10 | 0.114267E+10 | 0.201394E+10 | 0.413199E+10 | 0.534910E+09 |
July | 0.327611E+10 | 0.118227E+10 | 0.209384E+10 | 0.464616E+10 | 0.309476E+09 |
August | 0.368898E+10 | 0.166336E+10 | 0.202562E+10 | 0.520749E+10 | 0.415232E+09 |
September | 0.266251E+10 | 0.119456E+10 | 0.146794E+10 | 0.332552E+10 | 0.785598E+09 |
October | 0.249422E+10 | 0.113046E+10 | 0.136375E+10 | 0.276791E+10 | 0.148514E+10 |
November | 0.149272E+10 | 0.573221E+09 | 0.919503E+09 | 0.120418E+10 | 0.206622E+10 |
December | 0.120168E+10 | 0.564236E+09 | 0.637445E+09 | 0.820861E+09 | 0.271264E+10 |
Annual Sum or Average | 0.296533E+11 | 0.124048E+11 | 0.172486E+11 | 0.331711E+11 | 0.185046E+11 |
Minimum of Months | 0.120168E+10 | 0.490060E+09 | 0.637445E+09 | 0.772649E+09 | 0.309476E+09 |
Maximum of Months | 0.368898E+10 | 0.166336E+10 | 0.211289E+10 | 0.520749E+10 | 0.290176E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454073E+10 | 0.297330E+10 | 0.156743E+10 | 0.453048E+10 | 0.420952E+10 |
February | 0.540948E+10 | 0.358064E+10 | 0.182885E+10 | 0.547466E+10 | 0.388200E+10 |
March | 0.540327E+10 | 0.299891E+10 | 0.240436E+10 | 0.578737E+10 | 0.322212E+10 |
April | 0.405750E+10 | 0.160446E+10 | 0.245304E+10 | 0.448322E+10 | 0.237404E+10 |
May | 0.367432E+10 | 0.766406E+09 | 0.290792E+10 | 0.430095E+10 | 0.159427E+10 |
June | 0.333701E+10 | 0.510096E+09 | 0.282691E+10 | 0.452007E+10 | 0.837330E+09 |
July | 0.361445E+10 | 0.627829E+09 | 0.298662E+10 | 0.542738E+10 | 0.468251E+09 |
August | 0.482670E+10 | 0.179030E+10 | 0.303640E+10 | 0.730520E+10 | 0.654173E+09 |
September | 0.506813E+10 | 0.262144E+10 | 0.244668E+10 | 0.679513E+10 | 0.123806E+10 |
October | 0.717434E+10 | 0.449882E+10 | 0.267551E+10 | 0.896484E+10 | 0.228876E+10 |
November | 0.481431E+10 | 0.289122E+10 | 0.192309E+10 | 0.516923E+10 | 0.309235E+10 |
December | 0.492147E+10 | 0.349392E+10 | 0.142756E+10 | 0.509329E+10 | 0.392449E+10 |
Annual Sum or Average | 0.568417E+11 | 0.283574E+11 | 0.284844E+11 | 0.678518E+11 | 0.277853E+11 |
Minimum of Months | 0.333701E+10 | 0.510096E+09 | 0.142756E+10 | 0.430095E+10 | 0.468251E+09 |
Maximum of Months | 0.717434E+10 | 0.449882E+10 | 0.303640E+10 | 0.896484E+10 | 0.420952E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120672E+10 | 0.494277E+09 | 0.712445E+09 | 0.768307E+09 | 0.296992E+10 |
February | 0.160728E+10 | 0.705922E+09 | 0.901354E+09 | 0.112971E+10 | 0.277440E+10 |
March | 0.262763E+10 | 0.121310E+10 | 0.141452E+10 | 0.240544E+10 | 0.212250E+10 |
April | 0.277923E+10 | 0.118916E+10 | 0.159007E+10 | 0.287007E+10 | 0.154435E+10 |
May | 0.334544E+10 | 0.127047E+10 | 0.207497E+10 | 0.390674E+10 | 0.105029E+10 |
June | 0.354337E+10 | 0.142914E+10 | 0.211423E+10 | 0.468410E+10 | 0.567060E+09 |
July | 0.342918E+10 | 0.129132E+10 | 0.213786E+10 | 0.486673E+10 | 0.330472E+09 |
August | 0.379360E+10 | 0.175619E+10 | 0.203741E+10 | 0.539065E+10 | 0.448064E+09 |
September | 0.260628E+10 | 0.113894E+10 | 0.146734E+10 | 0.330014E+10 | 0.824099E+09 |
October | 0.267006E+10 | 0.129839E+10 | 0.137168E+10 | 0.302892E+10 | 0.153383E+10 |
November | 0.121341E+10 | 0.350683E+09 | 0.862723E+09 | 0.837150E+09 | 0.212056E+10 |
December | 0.111528E+10 | 0.482583E+09 | 0.632693E+09 | 0.723854E+09 | 0.279113E+10 |
Annual Sum or Average | 0.299375E+11 | 0.126202E+11 | 0.173173E+11 | 0.339118E+11 | 0.190767E+11 |
Minimum of Months | 0.111528E+10 | 0.350683E+09 | 0.632693E+09 | 0.723854E+09 | 0.330472E+09 |
Maximum of Months | 0.379360E+10 | 0.175619E+10 | 0.213786E+10 | 0.539065E+10 | 0.296992E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 28.33 | 1671.29 | 327.71 | 0.00 | 327.71 | 0.00 | 0.00 |
February | 51.82 | 1735.32 | 448.46 | 0.00 | 448.46 | 0.00 | 0.00 |
March | 247.25 | 1150.41 | 621.90 | 0.00 | 621.90 | 0.00 | 0.00 |
April | 494.94 | 828.16 | 746.98 | 2.12 | 744.86 | 0.00 | 0.00 |
May | 943.72 | 528.23 | 991.01 | 33.02 | 957.99 | 0.00 | 0.00 |
June | 1306.70 | 291.70 | 1050.95 | 56.47 | 994.48 | 0.00 | 0.00 |
July | 1445.29 | 165.90 | 1015.65 | 36.73 | 978.92 | 0.00 | 0.00 |
August | 1267.85 | 222.07 | 899.81 | 10.71 | 889.10 | 0.00 | 0.00 |
September | 733.24 | 440.36 | 678.31 | 0.13 | 678.18 | 0.00 | 0.00 |
October | 450.69 | 791.79 | 587.03 | 0.00 | 587.03 | 0.00 | 0.00 |
November | 135.07 | 1165.34 | 411.74 | 0.00 | 411.74 | 0.00 | 0.00 |
December | 19.56 | 1537.40 | 285.85 | 0.00 | 285.85 | 0.00 | 0.00 |
Annual Sum or Average | 597.35 | 872.43 | 673.41 | 11.66 | 661.75 | 0.00 | 0.00 |
Minimum of Months | 19.56 | 165.90 | 285.85 | 0.00 | 285.85 | 0.00 | 0.00 |
Maximum of Months | 1445.29 | 1735.32 | 1050.95 | 56.47 | 994.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 294.70 | 1037.38 | 456.37 | 182.97 | 273.40 | 0.00 | 0.00 |
February | 515.65 | 1044.24 | 707.73 | 330.16 | 377.57 | 0.00 | 0.00 |
March | 807.89 | 744.75 | 902.84 | 383.99 | 518.86 | 0.00 | 0.00 |
April | 1115.68 | 541.91 | 1083.48 | 474.60 | 608.88 | 0.00 | 0.00 |
May | 1531.42 | 362.19 | 1314.03 | 525.17 | 788.86 | 0.00 | 0.00 |
June | 1594.37 | 199.93 | 1217.83 | 440.84 | 776.98 | 0.00 | 0.00 |
July | 1732.26 | 112.81 | 1223.16 | 441.41 | 781.75 | 0.00 | 0.00 |
August | 1943.49 | 149.87 | 1377.31 | 621.03 | 756.28 | 0.00 | 0.00 |
September | 1287.47 | 288.03 | 1027.20 | 460.87 | 566.34 | 0.00 | 0.00 |
October | 1046.01 | 517.96 | 931.23 | 422.07 | 509.17 | 0.00 | 0.00 |
November | 482.12 | 736.61 | 575.90 | 221.15 | 354.75 | 0.00 | 0.00 |
December | 317.47 | 946.97 | 448.66 | 210.66 | 237.99 | 0.00 | 0.00 |
Annual Sum or Average | 1059.45 | 554.15 | 940.30 | 393.35 | 546.95 | 0.00 | 0.00 |
Minimum of Months | 294.70 | 112.81 | 448.66 | 182.97 | 237.99 | 0.00 | 0.00 |
Maximum of Months | 1943.49 | 1044.24 | 1377.31 | 621.03 | 788.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1702.34 | 1498.31 | 1695.32 | 1110.10 | 585.21 | 0.00 | 0.00 |
February | 2281.25 | 1522.16 | 2236.06 | 1480.09 | 755.97 | 0.00 | 0.00 |
March | 2173.52 | 1128.74 | 2017.35 | 1119.66 | 897.69 | 0.00 | 0.00 |
April | 1740.75 | 859.48 | 1565.39 | 619.00 | 946.39 | 0.00 | 0.00 |
May | 1608.88 | 568.70 | 1371.84 | 286.14 | 1085.69 | 0.00 | 0.00 |
June | 1738.83 | 312.45 | 1287.43 | 196.80 | 1090.63 | 0.00 | 0.00 |
July | 2017.59 | 170.68 | 1349.48 | 234.40 | 1115.08 | 0.00 | 0.00 |
August | 2720.31 | 236.10 | 1802.08 | 668.42 | 1133.66 | 0.00 | 0.00 |
September | 2622.04 | 454.64 | 1955.30 | 1011.36 | 943.94 | 0.00 | 0.00 |
October | 3357.14 | 801.67 | 2678.59 | 1679.67 | 998.92 | 0.00 | 0.00 |
November | 2018.20 | 1105.48 | 1857.37 | 1115.44 | 741.93 | 0.00 | 0.00 |
December | 1922.05 | 1370.27 | 1837.47 | 1304.48 | 532.99 | 0.00 | 0.00 |
Annual Sum or Average | 2158.98 | 831.75 | 1802.44 | 899.21 | 903.23 | 0.00 | 0.00 |
Minimum of Months | 1608.88 | 170.68 | 1287.43 | 196.80 | 532.99 | 0.00 | 0.00 |
Maximum of Months | 3357.14 | 1522.16 | 2678.59 | 1679.67 | 1133.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 290.63 | 1060.79 | 450.54 | 184.54 | 266.00 | 0.00 | 0.00 |
February | 472.80 | 1091.13 | 664.38 | 291.80 | 372.58 | 0.00 | 0.00 |
March | 906.63 | 742.92 | 981.04 | 452.92 | 528.12 | 0.00 | 0.00 |
April | 1115.70 | 557.81 | 1072.24 | 458.78 | 613.45 | 0.00 | 0.00 |
May | 1460.90 | 374.55 | 1249.05 | 474.34 | 774.71 | 0.00 | 0.00 |
June | 1802.98 | 211.57 | 1367.04 | 551.37 | 815.68 | 0.00 | 0.00 |
July | 1810.83 | 120.37 | 1280.31 | 482.12 | 798.18 | 0.00 | 0.00 |
August | 2007.98 | 161.87 | 1416.37 | 655.69 | 760.68 | 0.00 | 0.00 |
September | 1274.38 | 301.95 | 1005.51 | 439.41 | 566.10 | 0.00 | 0.00 |
October | 1140.60 | 534.01 | 996.89 | 484.76 | 512.13 | 0.00 | 0.00 |
November | 336.12 | 755.75 | 468.13 | 135.29 | 332.84 | 0.00 | 0.00 |
December | 276.88 | 974.92 | 416.40 | 180.18 | 236.22 | 0.00 | 0.00 |
Annual Sum or Average | 1079.02 | 571.00 | 949.31 | 400.18 | 549.13 | 0.00 | 0.00 |
Minimum of Months | 276.88 | 120.37 | 416.40 | 135.29 | 236.22 | 0.00 | 0.00 |
Maximum of Months | 2007.98 | 1091.13 | 1416.37 | 655.69 | 815.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 26.52 | 1742.88 | 327.70 | 0.00 | 327.70 | 0.00 | 0.00 |
February | 51.11 | 1799.21 | 448.45 | 0.00 | 448.45 | 0.00 | 0.00 |
March | 257.74 | 1183.94 | 621.88 | 0.00 | 621.88 | 0.00 | 0.00 |
April | 515.36 | 838.95 | 746.97 | 2.12 | 744.84 | 0.00 | 0.00 |
May | 983.73 | 514.26 | 990.99 | 33.02 | 957.97 | 0.00 | 0.00 |
June | 1335.91 | 283.57 | 1050.93 | 56.47 | 994.46 | 0.00 | 0.00 |
July | 1472.74 | 156.65 | 1015.62 | 36.73 | 978.90 | 0.00 | 0.00 |
August | 1281.81 | 222.96 | 899.80 | 10.71 | 889.09 | 0.00 | 0.00 |
September | 734.11 | 468.22 | 678.30 | 0.13 | 678.17 | 0.00 | 0.00 |
October | 433.33 | 871.16 | 587.02 | 0.00 | 587.02 | 0.00 | 0.00 |
November | 115.58 | 1302.56 | 411.74 | 0.00 | 411.74 | 0.00 | 0.00 |
December | 14.83 | 1665.70 | 285.84 | 0.00 | 285.84 | 0.00 | 0.00 |
Annual Sum or Average | 605.62 | 915.78 | 673.39 | 11.66 | 661.73 | 0.00 | 0.00 |
Minimum of Months | 14.83 | 156.65 | 285.84 | 0.00 | 285.84 | 0.00 | 0.00 |
Maximum of Months | 1472.74 | 1799.21 | 1050.93 | 56.47 | 994.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 293.82 | 1090.21 | 456.36 | 182.96 | 273.40 | 0.00 | 0.00 |
February | 514.34 | 1097.88 | 707.72 | 330.15 | 377.57 | 0.00 | 0.00 |
March | 816.16 | 781.46 | 902.83 | 383.98 | 518.85 | 0.00 | 0.00 |
April | 1127.06 | 564.66 | 1083.46 | 474.59 | 608.87 | 0.00 | 0.00 |
May | 1554.27 | 363.97 | 1314.01 | 525.15 | 788.85 | 0.00 | 0.00 |
June | 1612.53 | 201.07 | 1217.81 | 440.84 | 776.97 | 0.00 | 0.00 |
July | 1748.72 | 113.26 | 1223.14 | 441.40 | 781.74 | 0.00 | 0.00 |
August | 1953.56 | 159.13 | 1377.28 | 621.02 | 756.27 | 0.00 | 0.00 |
September | 1289.54 | 314.25 | 1027.19 | 460.86 | 566.33 | 0.00 | 0.00 |
October | 1035.99 | 580.58 | 931.22 | 422.06 | 509.16 | 0.00 | 0.00 |
November | 462.81 | 834.69 | 575.89 | 221.15 | 354.74 | 0.00 | 0.00 |
December | 308.04 | 1038.21 | 448.65 | 210.66 | 237.99 | 0.00 | 0.00 |
Annual Sum or Average | 1063.53 | 592.09 | 940.29 | 393.35 | 546.94 | 0.00 | 0.00 |
Minimum of Months | 293.82 | 113.26 | 448.65 | 182.96 | 237.99 | 0.00 | 0.00 |
Maximum of Months | 1953.56 | 1097.88 | 1377.28 | 621.02 | 788.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1727.65 | 1584.16 | 1695.25 | 1110.06 | 585.19 | 0.00 | 0.00 |
February | 2308.12 | 1623.10 | 2235.98 | 1480.03 | 755.95 | 0.00 | 0.00 |
March | 2208.31 | 1192.08 | 2017.28 | 1119.62 | 897.66 | 0.00 | 0.00 |
April | 1774.55 | 883.26 | 1565.34 | 618.98 | 946.36 | 0.00 | 0.00 |
May | 1658.95 | 555.46 | 1371.79 | 286.13 | 1085.66 | 0.00 | 0.00 |
June | 1771.95 | 307.73 | 1287.39 | 196.79 | 1090.60 | 0.00 | 0.00 |
July | 2044.44 | 167.30 | 1349.44 | 234.39 | 1115.04 | 0.00 | 0.00 |
August | 2736.58 | 251.24 | 1802.02 | 668.39 | 1133.63 | 0.00 | 0.00 |
September | 2630.07 | 501.31 | 1955.22 | 1011.32 | 943.91 | 0.00 | 0.00 |
October | 3356.40 | 914.70 | 2678.49 | 1679.60 | 998.89 | 0.00 | 0.00 |
November | 2007.86 | 1251.79 | 1857.30 | 1115.39 | 741.91 | 0.00 | 0.00 |
December | 1922.73 | 1515.06 | 1837.40 | 1304.43 | 532.97 | 0.00 | 0.00 |
Annual Sum or Average | 2179.36 | 891.37 | 1802.37 | 899.17 | 903.20 | 0.00 | 0.00 |
Minimum of Months | 1658.95 | 167.30 | 1287.39 | 196.79 | 532.97 | 0.00 | 0.00 |
Maximum of Months | 3356.40 | 1623.10 | 2678.49 | 1679.60 | 1133.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 293.04 | 1112.97 | 450.53 | 184.54 | 265.99 | 0.00 | 0.00 |
February | 478.57 | 1144.80 | 664.37 | 291.80 | 372.58 | 0.00 | 0.00 |
March | 917.08 | 783.74 | 981.03 | 452.91 | 528.12 | 0.00 | 0.00 |
April | 1128.77 | 583.77 | 1072.22 | 458.77 | 613.45 | 0.00 | 0.00 |
May | 1483.21 | 378.85 | 1249.03 | 474.33 | 774.70 | 0.00 | 0.00 |
June | 1821.94 | 216.81 | 1367.03 | 551.36 | 815.67 | 0.00 | 0.00 |
July | 1828.15 | 122.99 | 1280.29 | 482.12 | 798.18 | 0.00 | 0.00 |
August | 2018.38 | 173.37 | 1416.35 | 655.68 | 760.68 | 0.00 | 0.00 |
September | 1276.00 | 329.53 | 1005.50 | 439.40 | 566.10 | 0.00 | 0.00 |
October | 1130.66 | 601.63 | 996.87 | 484.75 | 512.12 | 0.00 | 0.00 |
November | 321.43 | 851.32 | 468.13 | 135.29 | 332.84 | 0.00 | 0.00 |
December | 272.77 | 1065.39 | 416.39 | 180.17 | 236.22 | 0.00 | 0.00 |
Annual Sum or Average | 1085.17 | 610.70 | 949.30 | 400.18 | 549.12 | 0.00 | 0.00 |
Minimum of Months | 272.77 | 122.99 | 416.39 | 135.29 | 236.22 | 0.00 | 0.00 |
Maximum of Months | 2018.38 | 1144.80 | 1416.35 | 655.68 | 815.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 24.87 | 1745.19 | 327.71 | 0.00 | 327.71 | 0.00 | 0.00 |
February | 46.35 | 1821.79 | 448.46 | 0.00 | 448.46 | 0.00 | 0.00 |
March | 235.30 | 1227.00 | 621.90 | 0.00 | 621.90 | 0.00 | 0.00 |
April | 480.68 | 885.94 | 746.98 | 2.12 | 744.86 | 0.00 | 0.00 |
May | 936.56 | 552.61 | 991.01 | 33.02 | 957.99 | 0.00 | 0.00 |
June | 1310.20 | 301.12 | 1050.95 | 56.47 | 994.48 | 0.00 | 0.00 |
July | 1452.91 | 169.40 | 1015.65 | 36.73 | 978.92 | 0.00 | 0.00 |
August | 1272.18 | 229.72 | 899.81 | 10.71 | 889.10 | 0.00 | 0.00 |
September | 729.82 | 465.29 | 678.31 | 0.13 | 678.18 | 0.00 | 0.00 |
October | 433.53 | 852.82 | 587.03 | 0.00 | 587.03 | 0.00 | 0.00 |
November | 118.20 | 1262.97 | 411.74 | 0.00 | 411.74 | 0.00 | 0.00 |
December | 14.97 | 1641.44 | 285.85 | 0.00 | 285.85 | 0.00 | 0.00 |
Annual Sum or Average | 591.63 | 924.47 | 673.41 | 11.66 | 661.75 | 0.00 | 0.00 |
Minimum of Months | 14.97 | 169.40 | 285.85 | 0.00 | 285.85 | 0.00 | 0.00 |
Maximum of Months | 1452.91 | 1821.79 | 1050.95 | 56.47 | 994.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 288.47 | 1083.39 | 456.37 | 182.97 | 273.40 | 0.00 | 0.00 |
February | 503.55 | 1098.50 | 707.73 | 330.16 | 377.57 | 0.00 | 0.00 |
March | 794.79 | 794.62 | 902.84 | 383.99 | 518.86 | 0.00 | 0.00 |
April | 1103.60 | 577.13 | 1083.48 | 474.60 | 608.88 | 0.00 | 0.00 |
May | 1525.88 | 377.81 | 1314.03 | 525.17 | 788.86 | 0.00 | 0.00 |
June | 1594.13 | 206.37 | 1217.83 | 440.84 | 776.98 | 0.00 | 0.00 |
July | 1734.68 | 115.54 | 1223.16 | 441.41 | 781.75 | 0.00 | 0.00 |
August | 1944.25 | 155.03 | 1377.31 | 621.03 | 756.28 | 0.00 | 0.00 |
September | 1282.99 | 303.09 | 1027.20 | 460.87 | 566.34 | 0.00 | 0.00 |
October | 1033.42 | 554.49 | 931.23 | 422.07 | 509.17 | 0.00 | 0.00 |
November | 464.57 | 797.15 | 575.90 | 221.15 | 354.75 | 0.00 | 0.00 |
December | 306.47 | 1012.78 | 448.66 | 210.66 | 237.99 | 0.00 | 0.00 |
Annual Sum or Average | 1051.85 | 586.78 | 940.30 | 393.35 | 546.95 | 0.00 | 0.00 |
Minimum of Months | 288.47 | 115.54 | 448.66 | 182.97 | 237.99 | 0.00 | 0.00 |
Maximum of Months | 1944.25 | 1098.50 | 1377.31 | 621.03 | 788.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1691.49 | 1571.65 | 1695.32 | 1110.10 | 585.21 | 0.00 | 0.00 |
February | 2263.01 | 1604.66 | 2236.06 | 1480.09 | 755.97 | 0.00 | 0.00 |
March | 2160.76 | 1203.00 | 2017.35 | 1119.66 | 897.69 | 0.00 | 0.00 |
April | 1729.64 | 915.91 | 1565.39 | 619.00 | 946.39 | 0.00 | 0.00 |
May | 1605.79 | 595.23 | 1371.84 | 286.14 | 1085.69 | 0.00 | 0.00 |
June | 1743.85 | 323.04 | 1287.43 | 196.80 | 1090.63 | 0.00 | 0.00 |
July | 2026.35 | 174.82 | 1349.48 | 234.40 | 1115.08 | 0.00 | 0.00 |
August | 2727.45 | 244.24 | 1802.08 | 668.42 | 1133.66 | 0.00 | 0.00 |
September | 2621.58 | 477.65 | 1955.30 | 1011.36 | 943.94 | 0.00 | 0.00 |
October | 3347.09 | 854.52 | 2678.59 | 1679.67 | 998.92 | 0.00 | 0.00 |
November | 1994.30 | 1193.04 | 1857.37 | 1115.44 | 741.93 | 0.00 | 0.00 |
December | 1901.62 | 1465.23 | 1837.47 | 1304.48 | 532.99 | 0.00 | 0.00 |
Annual Sum or Average | 2151.57 | 881.07 | 1802.44 | 899.21 | 903.23 | 0.00 | 0.00 |
Minimum of Months | 1605.79 | 174.82 | 1287.43 | 196.80 | 532.99 | 0.00 | 0.00 |
Maximum of Months | 3347.09 | 1604.66 | 2678.59 | 1679.67 | 1133.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 286.85 | 1108.84 | 450.54 | 184.54 | 266.00 | 0.00 | 0.00 |
February | 466.98 | 1146.83 | 664.38 | 291.80 | 372.58 | 0.00 | 0.00 |
March | 898.09 | 792.45 | 981.04 | 452.92 | 528.12 | 0.00 | 0.00 |
April | 1107.28 | 595.81 | 1072.24 | 458.78 | 613.45 | 0.00 | 0.00 |
May | 1458.61 | 392.13 | 1249.05 | 474.34 | 774.71 | 0.00 | 0.00 |
June | 1807.14 | 218.77 | 1367.04 | 551.37 | 815.68 | 0.00 | 0.00 |
July | 1817.03 | 123.38 | 1280.31 | 482.12 | 798.18 | 0.00 | 0.00 |
August | 2012.64 | 167.29 | 1416.37 | 655.69 | 760.68 | 0.00 | 0.00 |
September | 1273.20 | 317.94 | 1005.51 | 439.41 | 566.10 | 0.00 | 0.00 |
October | 1130.87 | 572.67 | 996.89 | 484.76 | 512.13 | 0.00 | 0.00 |
November | 322.97 | 818.12 | 468.13 | 135.29 | 332.84 | 0.00 | 0.00 |
December | 270.26 | 1042.09 | 416.40 | 180.18 | 236.22 | 0.00 | 0.00 |
Annual Sum or Average | 1075.34 | 604.92 | 949.31 | 400.18 | 549.13 | 0.00 | 0.00 |
Minimum of Months | 270.26 | 123.38 | 416.40 | 135.29 | 236.22 | 0.00 | 0.00 |
Maximum of Months | 2012.64 | 1146.83 | 1416.37 | 655.69 | 815.68 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 75868128.06 | 0.447637E+10 | 0.877739E+09 | 0.00 | 0.877739E+09 | 0.00 | 0.00 |
February | 0.125369E+09 | 0.419809E+10 | 0.108491E+10 | 0.00 | 0.108491E+10 | 0.00 | 0.00 |
March | 0.662222E+09 | 0.308126E+10 | 0.166569E+10 | 0.00 | 0.166569E+10 | 0.00 | 0.00 |
April | 0.128288E+10 | 0.214658E+10 | 0.193618E+10 | 5507101.70 | 0.193068E+10 | 0.00 | 0.00 |
May | 0.252766E+10 | 0.141482E+10 | 0.265432E+10 | 88443495.07 | 0.256588E+10 | 0.00 | 0.00 |
June | 0.338696E+10 | 0.756099E+09 | 0.272407E+10 | 0.146376E+09 | 0.257770E+10 | 0.00 | 0.00 |
July | 0.387106E+10 | 0.444355E+09 | 0.272030E+10 | 98375305.77 | 0.262193E+10 | 0.00 | 0.00 |
August | 0.339582E+10 | 0.594791E+09 | 0.241006E+10 | 28683108.84 | 0.238138E+10 | 0.00 | 0.00 |
September | 0.190056E+10 | 0.114142E+10 | 0.175818E+10 | 329235.52 | 0.175785E+10 | 0.00 | 0.00 |
October | 0.120712E+10 | 0.212074E+10 | 0.157230E+10 | 0.00 | 0.157230E+10 | 0.00 | 0.00 |
November | 0.350104E+09 | 0.302057E+10 | 0.106724E+10 | 0.00 | 0.106724E+10 | 0.00 | 0.00 |
December | 52391567.24 | 0.411778E+10 | 0.765622E+09 | 0.00 | 0.765622E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.188380E+11 | 0.275129E+11 | 0.212366E+11 | 0.367714E+09 | 0.208689E+11 | 0.00 | 0.00 |
Minimum of Months | 52391567.24 | 0.444355E+09 | 0.765622E+09 | 0.00 | 0.765622E+09 | 0.00 | 0.00 |
Maximum of Months | 0.387106E+10 | 0.447637E+10 | 0.272407E+10 | 0.146376E+09 | 0.262193E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.789330E+09 | 0.277852E+10 | 0.122234E+10 | 0.490060E+09 | 0.732281E+09 | 0.00 | 0.00 |
February | 0.124746E+10 | 0.252623E+10 | 0.171214E+10 | 0.798716E+09 | 0.913427E+09 | 0.00 | 0.00 |
March | 0.216386E+10 | 0.199473E+10 | 0.241818E+10 | 0.102847E+10 | 0.138971E+10 | 0.00 | 0.00 |
April | 0.289184E+10 | 0.140462E+10 | 0.280837E+10 | 0.123015E+10 | 0.157822E+10 | 0.00 | 0.00 |
May | 0.410175E+10 | 0.970101E+09 | 0.351950E+10 | 0.140660E+10 | 0.211289E+10 | 0.00 | 0.00 |
June | 0.413261E+10 | 0.518224E+09 | 0.315661E+10 | 0.114267E+10 | 0.201394E+10 | 0.00 | 0.00 |
July | 0.463968E+10 | 0.302160E+09 | 0.327611E+10 | 0.118227E+10 | 0.209384E+10 | 0.00 | 0.00 |
August | 0.520544E+10 | 0.401404E+09 | 0.368898E+10 | 0.166336E+10 | 0.202562E+10 | 0.00 | 0.00 |
September | 0.333713E+10 | 0.746584E+09 | 0.266251E+10 | 0.119456E+10 | 0.146794E+10 | 0.00 | 0.00 |
October | 0.280164E+10 | 0.138731E+10 | 0.249422E+10 | 0.113046E+10 | 0.136375E+10 | 0.00 | 0.00 |
November | 0.124966E+10 | 0.190929E+10 | 0.149272E+10 | 0.573221E+09 | 0.919503E+09 | 0.00 | 0.00 |
December | 0.850302E+09 | 0.253637E+10 | 0.120168E+10 | 0.564236E+09 | 0.637445E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.334107E+11 | 0.174755E+11 | 0.296533E+11 | 0.124048E+11 | 0.172486E+11 | 0.00 | 0.00 |
Minimum of Months | 0.789330E+09 | 0.302160E+09 | 0.120168E+10 | 0.490060E+09 | 0.637445E+09 | 0.00 | 0.00 |
Maximum of Months | 0.520544E+10 | 0.277852E+10 | 0.368898E+10 | 0.166336E+10 | 0.211289E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.455955E+10 | 0.401307E+10 | 0.454073E+10 | 0.297330E+10 | 0.156743E+10 | 0.00 | 0.00 |
February | 0.551879E+10 | 0.368240E+10 | 0.540948E+10 | 0.358064E+10 | 0.182885E+10 | 0.00 | 0.00 |
March | 0.582155E+10 | 0.302322E+10 | 0.540327E+10 | 0.299891E+10 | 0.240436E+10 | 0.00 | 0.00 |
April | 0.451202E+10 | 0.222777E+10 | 0.405750E+10 | 0.160446E+10 | 0.245304E+10 | 0.00 | 0.00 |
May | 0.430924E+10 | 0.152321E+10 | 0.367432E+10 | 0.766406E+09 | 0.290792E+10 | 0.00 | 0.00 |
June | 0.450705E+10 | 0.809864E+09 | 0.333701E+10 | 0.510096E+09 | 0.282691E+10 | 0.00 | 0.00 |
July | 0.540391E+10 | 0.457148E+09 | 0.361445E+10 | 0.627829E+09 | 0.298662E+10 | 0.00 | 0.00 |
August | 0.728608E+10 | 0.632365E+09 | 0.482670E+10 | 0.179030E+10 | 0.303640E+10 | 0.00 | 0.00 |
September | 0.679633E+10 | 0.117842E+10 | 0.506813E+10 | 0.262144E+10 | 0.244668E+10 | 0.00 | 0.00 |
October | 0.899177E+10 | 0.214719E+10 | 0.717434E+10 | 0.449882E+10 | 0.267551E+10 | 0.00 | 0.00 |
November | 0.523118E+10 | 0.286541E+10 | 0.481431E+10 | 0.289122E+10 | 0.192309E+10 | 0.00 | 0.00 |
December | 0.514801E+10 | 0.367014E+10 | 0.492147E+10 | 0.349392E+10 | 0.142756E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.680855E+11 | 0.262302E+11 | 0.568417E+11 | 0.283574E+11 | 0.284844E+11 | 0.00 | 0.00 |
Minimum of Months | 0.430924E+10 | 0.457148E+09 | 0.333701E+10 | 0.510096E+09 | 0.142756E+10 | 0.00 | 0.00 |
Maximum of Months | 0.899177E+10 | 0.401307E+10 | 0.717434E+10 | 0.449882E+10 | 0.303640E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.778423E+09 | 0.284121E+10 | 0.120672E+10 | 0.494277E+09 | 0.712445E+09 | 0.00 | 0.00 |
February | 0.114380E+10 | 0.263966E+10 | 0.160728E+10 | 0.705922E+09 | 0.901354E+09 | 0.00 | 0.00 |
March | 0.242831E+10 | 0.198983E+10 | 0.262763E+10 | 0.121310E+10 | 0.141452E+10 | 0.00 | 0.00 |
April | 0.289189E+10 | 0.144584E+10 | 0.277923E+10 | 0.118916E+10 | 0.159007E+10 | 0.00 | 0.00 |
May | 0.391288E+10 | 0.100321E+10 | 0.334544E+10 | 0.127047E+10 | 0.207497E+10 | 0.00 | 0.00 |
June | 0.467332E+10 | 0.548397E+09 | 0.354337E+10 | 0.142914E+10 | 0.211423E+10 | 0.00 | 0.00 |
July | 0.485012E+10 | 0.322409E+09 | 0.342918E+10 | 0.129132E+10 | 0.213786E+10 | 0.00 | 0.00 |
August | 0.537818E+10 | 0.433552E+09 | 0.379360E+10 | 0.175619E+10 | 0.203741E+10 | 0.00 | 0.00 |
September | 0.330320E+10 | 0.782663E+09 | 0.260628E+10 | 0.113894E+10 | 0.146734E+10 | 0.00 | 0.00 |
October | 0.305499E+10 | 0.143029E+10 | 0.267006E+10 | 0.129839E+10 | 0.137168E+10 | 0.00 | 0.00 |
November | 0.871226E+09 | 0.195892E+10 | 0.121341E+10 | 0.350683E+09 | 0.862723E+09 | 0.00 | 0.00 |
December | 0.741603E+09 | 0.261122E+10 | 0.111528E+10 | 0.482583E+09 | 0.632693E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.340279E+11 | 0.180072E+11 | 0.299375E+11 | 0.126202E+11 | 0.173173E+11 | 0.00 | 0.00 |
Minimum of Months | 0.741603E+09 | 0.322409E+09 | 0.111528E+10 | 0.350683E+09 | 0.632693E+09 | 0.00 | 0.00 |
Maximum of Months | 0.537818E+10 | 0.284121E+10 | 0.379360E+10 | 0.175619E+10 | 0.213786E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 71028656.83 | 0.466813E+10 | 0.877720E+09 | 0.00 | 0.877720E+09 | 0.00 | 0.00 |
February | 0.123639E+09 | 0.435265E+10 | 0.108489E+10 | 0.00 | 0.108489E+10 | 0.00 | 0.00 |
March | 0.690325E+09 | 0.317106E+10 | 0.166566E+10 | 0.00 | 0.166566E+10 | 0.00 | 0.00 |
April | 0.133582E+10 | 0.217455E+10 | 0.193614E+10 | 5506939.83 | 0.193064E+10 | 0.00 | 0.00 |
May | 0.263481E+10 | 0.137740E+10 | 0.265427E+10 | 88440895.47 | 0.256582E+10 | 0.00 | 0.00 |
June | 0.346268E+10 | 0.735011E+09 | 0.272402E+10 | 0.146372E+09 | 0.257764E+10 | 0.00 | 0.00 |
July | 0.394459E+10 | 0.419584E+09 | 0.272025E+10 | 98372414.25 | 0.262187E+10 | 0.00 | 0.00 |
August | 0.343320E+10 | 0.597187E+09 | 0.241001E+10 | 28682265.77 | 0.238133E+10 | 0.00 | 0.00 |
September | 0.190280E+10 | 0.121363E+10 | 0.175814E+10 | 329225.84 | 0.175781E+10 | 0.00 | 0.00 |
October | 0.116063E+10 | 0.233330E+10 | 0.157226E+10 | 0.00 | 0.157226E+10 | 0.00 | 0.00 |
November | 0.299574E+09 | 0.337623E+10 | 0.106722E+10 | 0.00 | 0.106722E+10 | 0.00 | 0.00 |
December | 39709539.08 | 0.446142E+10 | 0.765605E+09 | 0.00 | 0.765605E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.190988E+11 | 0.288801E+11 | 0.212362E+11 | 0.367703E+09 | 0.208685E+11 | 0.00 | 0.00 |
Minimum of Months | 39709539.08 | 0.419584E+09 | 0.765605E+09 | 0.00 | 0.765605E+09 | 0.00 | 0.00 |
Maximum of Months | 0.394459E+10 | 0.466813E+10 | 0.272402E+10 | 0.146372E+09 | 0.262187E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.786977E+09 | 0.292003E+10 | 0.122232E+10 | 0.490050E+09 | 0.732271E+09 | 0.00 | 0.00 |
February | 0.124428E+10 | 0.265600E+10 | 0.171212E+10 | 0.798700E+09 | 0.913415E+09 | 0.00 | 0.00 |
March | 0.218599E+10 | 0.209307E+10 | 0.241814E+10 | 0.102845E+10 | 0.138969E+10 | 0.00 | 0.00 |
April | 0.292133E+10 | 0.146359E+10 | 0.280833E+10 | 0.123013E+10 | 0.157820E+10 | 0.00 | 0.00 |
May | 0.416295E+10 | 0.974848E+09 | 0.351944E+10 | 0.140657E+10 | 0.211287E+10 | 0.00 | 0.00 |
June | 0.417967E+10 | 0.521180E+09 | 0.315656E+10 | 0.114265E+10 | 0.201391E+10 | 0.00 | 0.00 |
July | 0.468378E+10 | 0.303347E+09 | 0.327606E+10 | 0.118224E+10 | 0.209381E+10 | 0.00 | 0.00 |
August | 0.523242E+10 | 0.426207E+09 | 0.368892E+10 | 0.166333E+10 | 0.202559E+10 | 0.00 | 0.00 |
September | 0.334248E+10 | 0.814537E+09 | 0.266247E+10 | 0.119454E+10 | 0.146793E+10 | 0.00 | 0.00 |
October | 0.277479E+10 | 0.155503E+10 | 0.249418E+10 | 0.113044E+10 | 0.136374E+10 | 0.00 | 0.00 |
November | 0.119960E+10 | 0.216351E+10 | 0.149270E+10 | 0.573210E+09 | 0.919490E+09 | 0.00 | 0.00 |
December | 0.825065E+09 | 0.278075E+10 | 0.120166E+10 | 0.564225E+09 | 0.637437E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.335393E+11 | 0.186721E+11 | 0.296529E+11 | 0.124045E+11 | 0.172484E+11 | 0.00 | 0.00 |
Minimum of Months | 0.786977E+09 | 0.303347E+09 | 0.120166E+10 | 0.490050E+09 | 0.637437E+09 | 0.00 | 0.00 |
Maximum of Months | 0.523242E+10 | 0.292003E+10 | 0.368892E+10 | 0.166333E+10 | 0.211287E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.462733E+10 | 0.424302E+10 | 0.454055E+10 | 0.297318E+10 | 0.156738E+10 | 0.00 | 0.00 |
February | 0.558379E+10 | 0.392660E+10 | 0.540927E+10 | 0.358049E+10 | 0.182878E+10 | 0.00 | 0.00 |
March | 0.591473E+10 | 0.319288E+10 | 0.540307E+10 | 0.299879E+10 | 0.240428E+10 | 0.00 | 0.00 |
April | 0.459963E+10 | 0.228940E+10 | 0.405736E+10 | 0.160439E+10 | 0.245297E+10 | 0.00 | 0.00 |
May | 0.444333E+10 | 0.148775E+10 | 0.367420E+10 | 0.766374E+09 | 0.290783E+10 | 0.00 | 0.00 |
June | 0.459290E+10 | 0.797642E+09 | 0.333690E+10 | 0.510075E+09 | 0.282683E+10 | 0.00 | 0.00 |
July | 0.547583E+10 | 0.448105E+09 | 0.361433E+10 | 0.627803E+09 | 0.298653E+10 | 0.00 | 0.00 |
August | 0.732966E+10 | 0.672912E+09 | 0.482653E+10 | 0.179023E+10 | 0.303630E+10 | 0.00 | 0.00 |
September | 0.681714E+10 | 0.129940E+10 | 0.506794E+10 | 0.262133E+10 | 0.244661E+10 | 0.00 | 0.00 |
October | 0.898979E+10 | 0.244994E+10 | 0.717406E+10 | 0.449864E+10 | 0.267542E+10 | 0.00 | 0.00 |
November | 0.520438E+10 | 0.324463E+10 | 0.481412E+10 | 0.289110E+10 | 0.192302E+10 | 0.00 | 0.00 |
December | 0.514985E+10 | 0.405794E+10 | 0.492128E+10 | 0.349377E+10 | 0.142751E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.687284E+11 | 0.281102E+11 | 0.568396E+11 | 0.283562E+11 | 0.284835E+11 | 0.00 | 0.00 |
Minimum of Months | 0.444333E+10 | 0.448105E+09 | 0.333690E+10 | 0.510075E+09 | 0.142751E+10 | 0.00 | 0.00 |
Maximum of Months | 0.898979E+10 | 0.424302E+10 | 0.717406E+10 | 0.449864E+10 | 0.303630E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.784886E+09 | 0.298098E+10 | 0.120671E+10 | 0.494269E+09 | 0.712437E+09 | 0.00 | 0.00 |
February | 0.115775E+10 | 0.276950E+10 | 0.160726E+10 | 0.705911E+09 | 0.901345E+09 | 0.00 | 0.00 |
March | 0.245631E+10 | 0.209918E+10 | 0.262759E+10 | 0.121308E+10 | 0.141451E+10 | 0.00 | 0.00 |
April | 0.292576E+10 | 0.151313E+10 | 0.277920E+10 | 0.118914E+10 | 0.159005E+10 | 0.00 | 0.00 |
May | 0.397262E+10 | 0.101472E+10 | 0.334540E+10 | 0.127045E+10 | 0.207495E+10 | 0.00 | 0.00 |
June | 0.472248E+10 | 0.561959E+09 | 0.354333E+10 | 0.142912E+10 | 0.211421E+10 | 0.00 | 0.00 |
July | 0.489653E+10 | 0.329411E+09 | 0.342914E+10 | 0.129130E+10 | 0.213783E+10 | 0.00 | 0.00 |
August | 0.540603E+10 | 0.464359E+09 | 0.379356E+10 | 0.175616E+10 | 0.203739E+10 | 0.00 | 0.00 |
September | 0.330739E+10 | 0.854149E+09 | 0.260625E+10 | 0.113892E+10 | 0.146733E+10 | 0.00 | 0.00 |
October | 0.302837E+10 | 0.161142E+10 | 0.267003E+10 | 0.129837E+10 | 0.137166E+10 | 0.00 | 0.00 |
November | 0.833147E+09 | 0.220662E+10 | 0.121339E+10 | 0.350677E+09 | 0.862713E+09 | 0.00 | 0.00 |
December | 0.730574E+09 | 0.285354E+10 | 0.111526E+10 | 0.482575E+09 | 0.632686E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.342218E+11 | 0.192590E+11 | 0.299371E+11 | 0.126200E+11 | 0.173171E+11 | 0.00 | 0.00 |
Minimum of Months | 0.730574E+09 | 0.329411E+09 | 0.111526E+10 | 0.350677E+09 | 0.632686E+09 | 0.00 | 0.00 |
Maximum of Months | 0.540603E+10 | 0.298098E+10 | 0.379356E+10 | 0.175616E+10 | 0.213783E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 66611236.78 | 0.467431E+10 | 0.877739E+09 | 0.00 | 0.877739E+09 | 0.00 | 0.00 |
February | 0.112120E+09 | 0.440728E+10 | 0.108491E+10 | 0.00 | 0.108491E+10 | 0.00 | 0.00 |
March | 0.630220E+09 | 0.328641E+10 | 0.166569E+10 | 0.00 | 0.166569E+10 | 0.00 | 0.00 |
April | 0.124591E+10 | 0.229635E+10 | 0.193618E+10 | 5507101.70 | 0.193068E+10 | 0.00 | 0.00 |
May | 0.250849E+10 | 0.148012E+10 | 0.265432E+10 | 88443495.07 | 0.256588E+10 | 0.00 | 0.00 |
June | 0.339605E+10 | 0.780492E+09 | 0.272407E+10 | 0.146376E+09 | 0.257770E+10 | 0.00 | 0.00 |
July | 0.389148E+10 | 0.453717E+09 | 0.272030E+10 | 98375305.77 | 0.262193E+10 | 0.00 | 0.00 |
August | 0.340740E+10 | 0.615274E+09 | 0.241006E+10 | 28683108.84 | 0.238138E+10 | 0.00 | 0.00 |
September | 0.189168E+10 | 0.120603E+10 | 0.175818E+10 | 329235.52 | 0.175785E+10 | 0.00 | 0.00 |
October | 0.116117E+10 | 0.228420E+10 | 0.157230E+10 | 0.00 | 0.157230E+10 | 0.00 | 0.00 |
November | 0.306367E+09 | 0.327362E+10 | 0.106724E+10 | 0.00 | 0.106724E+10 | 0.00 | 0.00 |
December | 40093911.10 | 0.439643E+10 | 0.765622E+09 | 0.00 | 0.765622E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.186576E+11 | 0.291542E+11 | 0.212366E+11 | 0.367714E+09 | 0.208689E+11 | 0.00 | 0.00 |
Minimum of Months | 40093911.10 | 0.453717E+09 | 0.765622E+09 | 0.00 | 0.765622E+09 | 0.00 | 0.00 |
Maximum of Months | 0.389148E+10 | 0.467431E+10 | 0.272407E+10 | 0.146376E+09 | 0.262193E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.772649E+09 | 0.290176E+10 | 0.122234E+10 | 0.490060E+09 | 0.732281E+09 | 0.00 | 0.00 |
February | 0.121818E+10 | 0.265749E+10 | 0.171214E+10 | 0.798716E+09 | 0.913427E+09 | 0.00 | 0.00 |
March | 0.212876E+10 | 0.212831E+10 | 0.241818E+10 | 0.102847E+10 | 0.138971E+10 | 0.00 | 0.00 |
April | 0.286052E+10 | 0.149591E+10 | 0.280837E+10 | 0.123015E+10 | 0.157822E+10 | 0.00 | 0.00 |
May | 0.408691E+10 | 0.101194E+10 | 0.351950E+10 | 0.140660E+10 | 0.211289E+10 | 0.00 | 0.00 |
June | 0.413199E+10 | 0.534910E+09 | 0.315661E+10 | 0.114267E+10 | 0.201394E+10 | 0.00 | 0.00 |
July | 0.464616E+10 | 0.309476E+09 | 0.327611E+10 | 0.118227E+10 | 0.209384E+10 | 0.00 | 0.00 |
August | 0.520749E+10 | 0.415232E+09 | 0.368898E+10 | 0.166336E+10 | 0.202562E+10 | 0.00 | 0.00 |
September | 0.332552E+10 | 0.785598E+09 | 0.266251E+10 | 0.119456E+10 | 0.146794E+10 | 0.00 | 0.00 |
October | 0.276791E+10 | 0.148514E+10 | 0.249422E+10 | 0.113046E+10 | 0.136375E+10 | 0.00 | 0.00 |
November | 0.120418E+10 | 0.206622E+10 | 0.149272E+10 | 0.573221E+09 | 0.919503E+09 | 0.00 | 0.00 |
December | 0.820861E+09 | 0.271264E+10 | 0.120168E+10 | 0.564236E+09 | 0.637445E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.331711E+11 | 0.185046E+11 | 0.296533E+11 | 0.124048E+11 | 0.172486E+11 | 0.00 | 0.00 |
Minimum of Months | 0.772649E+09 | 0.309476E+09 | 0.120168E+10 | 0.490060E+09 | 0.637445E+09 | 0.00 | 0.00 |
Maximum of Months | 0.520749E+10 | 0.290176E+10 | 0.368898E+10 | 0.166336E+10 | 0.211289E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.453048E+10 | 0.420952E+10 | 0.454073E+10 | 0.297330E+10 | 0.156743E+10 | 0.00 | 0.00 |
February | 0.547466E+10 | 0.388200E+10 | 0.540948E+10 | 0.358064E+10 | 0.182885E+10 | 0.00 | 0.00 |
March | 0.578737E+10 | 0.322212E+10 | 0.540327E+10 | 0.299891E+10 | 0.240436E+10 | 0.00 | 0.00 |
April | 0.448322E+10 | 0.237404E+10 | 0.405750E+10 | 0.160446E+10 | 0.245304E+10 | 0.00 | 0.00 |
May | 0.430095E+10 | 0.159427E+10 | 0.367432E+10 | 0.766406E+09 | 0.290792E+10 | 0.00 | 0.00 |
June | 0.452007E+10 | 0.837330E+09 | 0.333701E+10 | 0.510096E+09 | 0.282691E+10 | 0.00 | 0.00 |
July | 0.542738E+10 | 0.468251E+09 | 0.361445E+10 | 0.627829E+09 | 0.298662E+10 | 0.00 | 0.00 |
August | 0.730520E+10 | 0.654173E+09 | 0.482670E+10 | 0.179030E+10 | 0.303640E+10 | 0.00 | 0.00 |
September | 0.679513E+10 | 0.123806E+10 | 0.506813E+10 | 0.262144E+10 | 0.244668E+10 | 0.00 | 0.00 |
October | 0.896484E+10 | 0.228876E+10 | 0.717434E+10 | 0.449882E+10 | 0.267551E+10 | 0.00 | 0.00 |
November | 0.516923E+10 | 0.309235E+10 | 0.481431E+10 | 0.289122E+10 | 0.192309E+10 | 0.00 | 0.00 |
December | 0.509329E+10 | 0.392449E+10 | 0.492147E+10 | 0.349392E+10 | 0.142756E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.678518E+11 | 0.277853E+11 | 0.568417E+11 | 0.283574E+11 | 0.284844E+11 | 0.00 | 0.00 |
Minimum of Months | 0.430095E+10 | 0.468251E+09 | 0.333701E+10 | 0.510096E+09 | 0.142756E+10 | 0.00 | 0.00 |
Maximum of Months | 0.896484E+10 | 0.420952E+10 | 0.717434E+10 | 0.449882E+10 | 0.303640E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.768307E+09 | 0.296992E+10 | 0.120672E+10 | 0.494277E+09 | 0.712445E+09 | 0.00 | 0.00 |
February | 0.112971E+10 | 0.277440E+10 | 0.160728E+10 | 0.705922E+09 | 0.901354E+09 | 0.00 | 0.00 |
March | 0.240544E+10 | 0.212250E+10 | 0.262763E+10 | 0.121310E+10 | 0.141452E+10 | 0.00 | 0.00 |
April | 0.287007E+10 | 0.154435E+10 | 0.277923E+10 | 0.118916E+10 | 0.159007E+10 | 0.00 | 0.00 |
May | 0.390674E+10 | 0.105029E+10 | 0.334544E+10 | 0.127047E+10 | 0.207497E+10 | 0.00 | 0.00 |
June | 0.468410E+10 | 0.567060E+09 | 0.354337E+10 | 0.142914E+10 | 0.211423E+10 | 0.00 | 0.00 |
July | 0.486673E+10 | 0.330472E+09 | 0.342918E+10 | 0.129132E+10 | 0.213786E+10 | 0.00 | 0.00 |
August | 0.539065E+10 | 0.448064E+09 | 0.379360E+10 | 0.175619E+10 | 0.203741E+10 | 0.00 | 0.00 |
September | 0.330014E+10 | 0.824099E+09 | 0.260628E+10 | 0.113894E+10 | 0.146734E+10 | 0.00 | 0.00 |
October | 0.302892E+10 | 0.153383E+10 | 0.267006E+10 | 0.129839E+10 | 0.137168E+10 | 0.00 | 0.00 |
November | 0.837150E+09 | 0.212056E+10 | 0.121341E+10 | 0.350683E+09 | 0.862723E+09 | 0.00 | 0.00 |
December | 0.723854E+09 | 0.279113E+10 | 0.111528E+10 | 0.482583E+09 | 0.632693E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.339118E+11 | 0.190767E+11 | 0.299375E+11 | 0.126202E+11 | 0.173173E+11 | 0.00 | 0.00 |
Minimum of Months | 0.723854E+09 | 0.330472E+09 | 0.111528E+10 | 0.350683E+09 | 0.632693E+09 | 0.00 | 0.00 |
Maximum of Months | 0.539065E+10 | 0.296992E+10 | 0.379360E+10 | 0.175619E+10 | 0.213786E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.536370E+10 | -0.462439E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -739310773.4 | 58.98 | 0.00 | 0.00 |
February | 0.489905E+10 | -0.424507E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -653980037.5 | 58.98 | 0.00 | 0.00 |
March | 0.562070E+10 | -0.491105E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -709654729.4 | 58.99 | 0.00 | 0.00 |
April | 0.487011E+10 | -0.419246E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -677651811.4 | 58.98 | 0.00 | 0.00 |
May | 0.487944E+10 | -0.418690E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692542072.4 | 58.99 | 0.00 | 0.00 |
June | 0.452316E+10 | -0.385679E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666374271.0 | 58.98 | 0.00 | 0.00 |
July | 0.412762E+10 | -0.344129E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -686326869.5 | 58.98 | 0.00 | 0.00 |
August | 0.444067E+10 | -0.375349E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687175903.7 | 58.98 | 0.00 | 0.00 |
September | 0.415182E+10 | -0.348633E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -665494734.9 | 58.98 | 0.00 | 0.00 |
October | 0.452962E+10 | -0.383929E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690323396.0 | 58.98 | 0.00 | 0.00 |
November | 0.475404E+10 | -0.407198E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -682063596.2 | 58.98 | 0.00 | 0.00 |
December | 0.502400E+10 | -0.430584E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -718154844.3 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.571839E+11 | -0.489149E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.826905E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.412762E+10 | -0.491105E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -739310773.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.562070E+10 | -0.344129E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -653980037.5 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.50 | 0.48 | 01-JAN-07:49 | 6502.60 | 36.69 | 196.17 | 241.50 | 3388.99 | 33.30 | 185.67 | 196.67 |
February | 216.00 | 0.49 | 0.48 | 01-FEB-07:40 | 9259.17 | 37.54 | 210.00 | 258.33 | 2126.96 | 26.55 | 176.83 | 233.50 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-06:00 | 3276.47 | 21.57 | 57.00 | 318.33 | 1592.25 | 21.71 | 170.17 | 285.00 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 2073.87 | 18.95 | 1.83 | 339.00 | 1227.90 | 21.18 | 149.83 | 299.00 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-05:00 | 1803.96 | 18.85 | 0.00 | 390.67 | 1014.36 | 21.02 | 225.17 | 347.50 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:40 | 1718.13 | 18.83 | 0.00 | 382.50 | 978.98 | 21.06 | 208.00 | 340.50 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:40 | 1896.16 | 19.09 | 1.00 | 390.33 | 1057.77 | 21.32 | 237.83 | 344.33 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:00 | 2107.07 | 19.07 | 7.83 | 370.67 | 1223.37 | 21.27 | 238.00 | 340.00 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 3805.78 | 21.30 | 36.50 | 323.83 | 1466.81 | 21.48 | 178.50 | 289.50 |
October | 305.50 | 0.49 | 0.48 | 01-OCT-14:39 | 10128.99 | 36.12 | 283.50 | 307.00 | 2052.87 | 23.60 | 258.83 | 289.00 |
November | 240.83 | 0.50 | 0.48 | 01-NOV-06:49 | 6447.57 | 36.31 | 235.17 | 257.17 | 2274.92 | 29.45 | 223.33 | 236.00 |
December | 211.17 | 0.50 | 0.48 | 01-DEC-07:30 | 6063.17 | 36.57 | 198.50 | 243.33 | 5410.95 | 39.04 | 208.00 | 214.67 |
Annual Sum or Average | 3472.67 | 0.50 | 4187.37 | 25.32 | 1227.50 | 3822.67 | 1789.52 | 24.15 | 2460.17 | 3415.67 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1718.13 | 18.83 | 0.00 | 241.50 | 978.98 | 21.02 | 149.83 | 196.67 | |
Maximum of Months | 389.17 | 0.51 | 0.48 | 10128.99 | 37.54 | 283.50 | 390.67 | 5410.95 | 39.04 | 258.83 | 347.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-07:49 | 1978.73 | 21.31 | 61.00 | 221.17 | 1125.41 | 23.69 | 88.67 | 158.83 |
February | 216.00 | 0.50 | 0.48 | 01-FEB-07:40 | 2816.44 | 24.01 | 80.67 | 245.50 | 1626.39 | 24.64 | 92.17 | 207.17 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-06:49 | 2919.56 | 21.40 | 71.50 | 313.50 | 1635.57 | 22.57 | 77.67 | 260.17 |
April | 261.17 | 0.50 | 0.48 | 01-APR-06:10 | 3823.68 | 22.28 | 80.67 | 341.33 | 1557.02 | 22.91 | 53.33 | 302.33 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:40 | 3178.29 | 21.15 | 99.17 | 396.67 | 1725.36 | 22.44 | 73.50 | 354.83 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-04:00 | 2835.16 | 20.46 | 80.67 | 387.17 | 1588.14 | 22.72 | 69.83 | 353.17 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-04:49 | 2929.24 | 21.08 | 89.67 | 396.00 | 1588.94 | 22.48 | 69.50 | 358.33 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:30 | 3910.50 | 23.17 | 128.17 | 373.17 | 1632.37 | 22.85 | 82.67 | 346.33 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-05:49 | 3397.81 | 22.17 | 82.67 | 320.67 | 1492.55 | 22.75 | 64.17 | 285.83 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 3017.01 | 23.06 | 91.17 | 293.50 | 1597.73 | 23.88 | 137.67 | 265.33 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-06:49 | 2042.55 | 22.03 | 73.33 | 244.50 | 1050.61 | 22.55 | 114.17 | 200.67 |
December | 211.17 | 0.53 | 0.48 | 01-DEC-07:30 | 1895.84 | 23.20 | 81.17 | 221.17 | 1103.75 | 24.08 | 91.33 | 157.33 |
Annual Sum or Average | 3472.67 | 0.51 | 2983.12 | 22.03 | 1019.83 | 3754.33 | 1511.35 | 23.03 | 1014.67 | 3250.33 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1895.84 | 20.46 | 61.00 | 221.17 | 1050.61 | 22.44 | 53.33 | 157.33 | |
Maximum of Months | 389.17 | 0.53 | 0.48 | 3910.50 | 24.01 | 128.17 | 396.67 | 1725.36 | 24.64 | 137.67 | 358.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.54 | 0.48 | 01-JAN-08:39 | 634.71 | 15.57 | 0.00 | 207.50 | 385.93 | 17.99 | 0.00 | 118.00 |
February | 216.00 | 0.52 | 0.48 | 01-FEB-08:39 | 688.41 | 16.52 | 0.00 | 230.33 | 443.21 | 19.04 | 0.00 | 162.67 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-07:19 | 911.03 | 17.40 | 0.00 | 308.00 | 564.74 | 19.64 | 13.33 | 237.50 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 1025.43 | 18.38 | 0.00 | 344.00 | 638.11 | 20.58 | 51.17 | 295.83 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:49 | 1322.13 | 19.16 | 7.50 | 403.67 | 759.55 | 21.28 | 168.33 | 363.17 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-04:00 | 1491.61 | 22.44 | 74.50 | 401.83 | 837.60 | 23.66 | 239.00 | 373.33 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:00 | 1468.07 | 20.28 | 26.83 | 407.50 | 829.27 | 23.22 | 244.50 | 371.50 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:49 | 1208.24 | 18.79 | 0.00 | 377.83 | 726.71 | 20.97 | 164.67 | 350.00 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 940.22 | 17.95 | 0.00 | 320.17 | 590.55 | 20.22 | 27.50 | 269.67 |
October | 305.50 | 0.51 | 0.48 | 01-OCT-14:39 | 854.25 | 17.60 | 0.00 | 289.17 | 548.00 | 20.01 | 0.00 | 243.83 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-07:30 | 707.70 | 16.27 | 0.00 | 233.83 | 421.69 | 18.60 | 0.00 | 155.83 |
December | 211.17 | 0.56 | 0.48 | 01-DEC-08:39 | 512.50 | 14.57 | 0.00 | 196.00 | 321.08 | 17.16 | 0.00 | 89.17 |
Annual Sum or Average | 3472.67 | 0.51 | 1043.72 | 18.29 | 108.83 | 3719.83 | 622.82 | 20.54 | 908.50 | 3030.50 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 512.50 | 14.57 | 0.00 | 196.00 | 321.08 | 17.16 | 0.00 | 89.17 | |
Maximum of Months | 389.17 | 0.56 | 0.48 | 1491.61 | 22.44 | 74.50 | 407.50 | 837.60 | 23.66 | 244.50 | 373.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.51 | 0.48 | 01-JAN-08:39 | 1970.59 | 23.24 | 73.33 | 228.67 | 1113.66 | 23.83 | 78.83 | 162.50 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-08:39 | 2197.29 | 21.43 | 57.00 | 244.33 | 1186.09 | 23.37 | 76.00 | 204.50 |
March | 275.00 | 0.50 | 0.48 | 01-MAR-07:30 | 3178.88 | 23.68 | 95.83 | 317.00 | 1797.95 | 24.57 | 92.50 | 272.33 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 3617.58 | 21.96 | 76.83 | 340.17 | 1503.45 | 21.51 | 40.33 | 299.67 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-06:10 | 3412.56 | 19.22 | 69.33 | 395.17 | 1516.69 | 19.00 | 0.00 | 357.17 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:00 | 3301.34 | 15.87 | 1.83 | 391.17 | 1787.28 | 19.18 | 2.50 | 351.83 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:49 | 3106.44 | 18.53 | 49.00 | 397.17 | 1665.56 | 19.30 | 6.17 | 355.83 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-06:10 | 3988.07 | 20.31 | 86.33 | 373.33 | 1740.05 | 19.43 | 19.50 | 346.33 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:40 | 3220.56 | 22.40 | 85.33 | 322.17 | 1683.18 | 23.13 | 68.50 | 284.67 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 3451.04 | 24.12 | 109.33 | 303.50 | 1464.97 | 23.44 | 119.17 | 275.83 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-07:30 | 1669.38 | 21.05 | 68.83 | 245.33 | 913.53 | 23.40 | 99.67 | 203.83 |
December | 211.17 | 0.53 | 0.48 | 01-DEC-08:39 | 1561.79 | 21.16 | 67.50 | 220.17 | 890.50 | 23.26 | 76.33 | 162.67 |
Annual Sum or Average | 3472.67 | 0.50 | 3026.26 | 20.80 | 840.50 | 3778.17 | 1491.57 | 21.57 | 679.50 | 3277.17 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1561.79 | 15.87 | 1.83 | 220.17 | 890.50 | 19.00 | 0.00 | 162.50 | |
Maximum of Months | 389.17 | 0.53 | 0.48 | 3988.07 | 24.12 | 109.33 | 397.17 | 1797.95 | 24.57 | 119.17 | 357.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.50 | 0.48 | 01-JAN-07:49 | 6326.56 | 36.47 | 196.17 | 238.33 | 3258.62 | 32.19 | 144.00 | 194.00 |
February | 216.00 | 0.49 | 0.48 | 01-FEB-07:40 | 9075.85 | 37.27 | 210.00 | 256.83 | 2002.17 | 24.94 | 80.00 | 233.67 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-07:10 | 3153.97 | 18.16 | 45.83 | 318.33 | 1479.48 | 19.19 | 40.50 | 279.67 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 1969.95 | 15.24 | 0.00 | 338.33 | 1152.51 | 18.82 | 7.67 | 295.00 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-05:00 | 1727.85 | 15.23 | 0.00 | 389.17 | 964.77 | 18.66 | 0.50 | 342.50 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:49 | 1648.46 | 15.22 | 0.00 | 380.33 | 935.04 | 18.73 | 0.00 | 335.67 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:49 | 1817.89 | 15.42 | 0.00 | 388.67 | 1007.82 | 18.91 | 1.83 | 341.00 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:00 | 2007.75 | 15.51 | 0.00 | 368.67 | 1154.27 | 19.00 | 19.33 | 335.83 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 3670.97 | 17.87 | 29.50 | 322.33 | 1365.47 | 18.97 | 20.33 | 287.00 |
October | 305.50 | 0.49 | 0.48 | 01-OCT-14:39 | 9929.84 | 35.44 | 281.00 | 306.17 | 1907.88 | 20.87 | 46.33 | 287.33 |
November | 240.83 | 0.50 | 0.48 | 01-NOV-06:49 | 6268.79 | 35.30 | 228.83 | 255.83 | 2152.12 | 27.59 | 121.17 | 234.00 |
December | 211.17 | 0.51 | 0.48 | 01-DEC-07:40 | 5883.17 | 35.73 | 195.50 | 239.17 | 5278.82 | 38.86 | 208.00 | 212.00 |
Annual Sum or Average | 3472.67 | 0.50 | 4061.83 | 22.74 | 1186.83 | 3802.17 | 1699.27 | 22.02 | 689.67 | 3377.67 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1648.46 | 15.22 | 0.00 | 238.33 | 935.04 | 18.66 | 0.00 | 194.00 | |
Maximum of Months | 389.17 | 0.51 | 0.48 | 9929.84 | 37.27 | 281.00 | 389.17 | 5278.82 | 38.86 | 208.00 | 342.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-07:49 | 1921.04 | 20.83 | 61.00 | 218.83 | 1081.84 | 23.47 | 82.50 | 156.00 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2748.16 | 23.56 | 80.67 | 243.50 | 1572.21 | 24.44 | 82.67 | 202.67 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-06:49 | 2742.96 | 19.56 | 58.83 | 311.00 | 1573.44 | 22.36 | 67.83 | 252.67 |
April | 261.17 | 0.50 | 0.48 | 01-APR-06:10 | 3732.76 | 21.83 | 80.67 | 338.83 | 1485.02 | 22.73 | 52.00 | 298.50 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-05:40 | 3083.31 | 20.70 | 99.17 | 395.67 | 1656.52 | 22.27 | 72.83 | 351.00 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-04:00 | 2751.88 | 19.99 | 80.67 | 385.00 | 1526.79 | 22.55 | 69.00 | 351.17 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-04:00 | 2838.36 | 20.58 | 89.17 | 394.33 | 1524.45 | 22.31 | 67.00 | 354.67 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:30 | 3767.85 | 21.40 | 111.67 | 371.00 | 1554.94 | 22.54 | 74.17 | 344.33 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-05:49 | 3312.24 | 21.69 | 82.67 | 319.67 | 1400.88 | 21.70 | 49.00 | 281.33 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 2932.16 | 22.58 | 91.17 | 291.00 | 1532.35 | 23.67 | 119.67 | 261.67 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-06:49 | 1976.18 | 21.37 | 72.00 | 242.17 | 1002.42 | 22.32 | 102.00 | 197.00 |
December | 211.17 | 0.53 | 0.48 | 01-DEC-07:30 | 1757.84 | 20.40 | 64.00 | 214.83 | 1064.80 | 23.86 | 86.33 | 152.17 |
Annual Sum or Average | 3472.67 | 0.51 | 2883.09 | 21.15 | 971.67 | 3725.83 | 1447.10 | 22.76 | 925.00 | 3203.17 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1757.84 | 19.56 | 58.83 | 214.83 | 1002.42 | 21.70 | 49.00 | 152.17 | |
Maximum of Months | 389.17 | 0.53 | 0.48 | 3767.85 | 23.56 | 111.67 | 395.67 | 1656.52 | 24.44 | 119.67 | 354.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.54 | 0.48 | 01-JAN-08:50 | 610.06 | 12.00 | 0.00 | 203.17 | 372.57 | 15.62 | 0.00 | 112.33 |
February | 216.00 | 0.52 | 0.48 | 01-FEB-08:39 | 662.22 | 13.10 | 0.00 | 226.67 | 429.60 | 16.87 | 0.00 | 157.67 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-07:30 | 878.27 | 14.16 | 0.00 | 306.50 | 547.39 | 17.66 | 0.00 | 229.83 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 989.39 | 15.16 | 0.00 | 342.50 | 619.11 | 18.71 | 0.00 | 291.33 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:49 | 1274.56 | 15.68 | 3.00 | 401.83 | 732.99 | 19.16 | 36.67 | 359.00 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-05:10 | 1434.32 | 18.89 | 62.67 | 398.83 | 807.88 | 21.82 | 76.67 | 371.50 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:00 | 1411.99 | 15.75 | 0.00 | 405.00 | 799.54 | 21.32 | 63.17 | 368.17 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:49 | 1165.38 | 15.59 | 0.00 | 377.50 | 703.61 | 19.10 | 8.17 | 346.50 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-06:19 | 906.59 | 14.77 | 0.00 | 317.83 | 572.88 | 18.32 | 0.00 | 263.83 |
October | 305.50 | 0.51 | 0.48 | 01-OCT-14:39 | 821.12 | 14.41 | 0.00 | 286.67 | 530.68 | 18.03 | 0.00 | 239.83 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-07:30 | 680.86 | 12.60 | 0.00 | 230.83 | 406.95 | 16.20 | 0.00 | 146.83 |
December | 211.17 | 0.56 | 0.48 | 01-DEC-08:50 | 492.02 | 10.88 | 0.00 | 190.33 | 310.15 | 14.69 | 0.00 | 84.17 |
Annual Sum or Average | 3472.67 | 0.51 | 1004.99 | 14.78 | 65.67 | 3687.67 | 602.17 | 18.51 | 184.67 | 2971.00 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 492.02 | 10.88 | 0.00 | 190.33 | 310.15 | 14.69 | 0.00 | 84.17 | |
Maximum of Months | 389.17 | 0.56 | 0.48 | 1434.32 | 18.89 | 62.67 | 405.00 | 807.88 | 21.82 | 76.67 | 371.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-08:39 | 1832.28 | 20.59 | 57.17 | 224.50 | 1070.81 | 23.70 | 77.00 | 158.33 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-08:39 | 2128.10 | 21.00 | 57.00 | 242.83 | 1100.33 | 22.17 | 66.50 | 199.67 |
March | 275.00 | 0.50 | 0.48 | 01-MAR-07:30 | 3094.28 | 23.30 | 95.83 | 316.17 | 1729.71 | 24.39 | 88.83 | 265.00 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 3526.55 | 21.53 | 76.83 | 337.83 | 1431.94 | 21.36 | 38.83 | 297.17 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-06:19 | 3325.85 | 18.75 | 69.17 | 393.50 | 1452.61 | 18.82 | 0.00 | 353.17 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:00 | 3198.87 | 15.34 | 1.83 | 389.50 | 1714.55 | 19.00 | 1.50 | 347.67 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:00 | 3008.69 | 18.05 | 49.00 | 395.33 | 1596.86 | 19.13 | 4.50 | 352.33 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-06:10 | 3842.14 | 19.86 | 86.33 | 371.17 | 1664.28 | 19.28 | 14.83 | 344.17 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:40 | 3136.61 | 21.99 | 85.33 | 320.83 | 1615.36 | 23.01 | 66.50 | 280.50 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 3358.70 | 23.74 | 109.33 | 302.17 | 1395.36 | 23.33 | 115.83 | 272.83 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-07:30 | 1619.51 | 20.64 | 68.83 | 243.67 | 874.07 | 23.11 | 94.33 | 197.83 |
December | 211.17 | 0.53 | 0.48 | 01-DEC-08:50 | 1513.50 | 20.77 | 67.50 | 218.00 | 820.02 | 21.77 | 65.50 | 155.33 |
Annual Sum or Average | 3472.67 | 0.50 | 2932.74 | 20.23 | 824.17 | 3755.50 | 1424.33 | 21.26 | 634.17 | 3224.00 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1513.50 | 15.34 | 1.83 | 218.00 | 820.02 | 18.82 | 0.00 | 155.33 | |
Maximum of Months | 389.17 | 0.53 | 0.48 | 3842.14 | 23.74 | 109.33 | 395.33 | 1729.71 | 24.39 | 115.83 | 353.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.50 | 0.48 | 01-JAN-07:49 | 6326.55 | 36.47 | 196.17 | 238.33 | 3258.51 | 32.19 | 144.00 | 193.83 |
February | 216.00 | 0.49 | 0.48 | 01-FEB-07:40 | 9075.80 | 37.27 | 210.00 | 256.83 | 2002.06 | 24.94 | 80.00 | 233.67 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-07:10 | 3153.85 | 18.16 | 45.83 | 318.33 | 1479.37 | 19.19 | 40.50 | 279.67 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 1969.85 | 15.25 | 0.00 | 338.33 | 1152.43 | 18.82 | 7.67 | 295.00 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-05:00 | 1727.75 | 15.24 | 0.00 | 389.17 | 964.70 | 18.67 | 0.83 | 342.50 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:49 | 1648.37 | 15.22 | 0.00 | 380.33 | 934.97 | 18.73 | 0.00 | 335.67 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:49 | 1817.78 | 15.42 | 0.00 | 388.67 | 1007.74 | 18.91 | 1.83 | 341.00 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:00 | 2007.65 | 15.51 | 0.00 | 368.67 | 1154.19 | 19.00 | 19.50 | 335.83 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 3670.85 | 17.87 | 29.50 | 322.33 | 1365.37 | 18.97 | 20.33 | 287.00 |
October | 305.50 | 0.49 | 0.48 | 01-OCT-14:39 | 9929.75 | 35.44 | 281.00 | 306.17 | 1907.75 | 20.87 | 46.33 | 287.33 |
November | 240.83 | 0.50 | 0.48 | 01-NOV-06:49 | 6268.75 | 35.30 | 228.83 | 255.83 | 2152.00 | 27.59 | 121.17 | 234.00 |
December | 211.17 | 0.51 | 0.48 | 01-DEC-07:40 | 5883.19 | 35.73 | 195.50 | 239.17 | 5278.73 | 38.86 | 208.00 | 212.00 |
Annual Sum or Average | 3472.67 | 0.50 | 4061.74 | 22.74 | 1186.83 | 3802.17 | 1699.18 | 22.02 | 690.17 | 3377.50 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1648.37 | 15.22 | 0.00 | 238.33 | 934.97 | 18.67 | 0.00 | 193.83 | |
Maximum of Months | 389.17 | 0.51 | 0.48 | 9929.75 | 37.27 | 281.00 | 389.17 | 5278.73 | 38.86 | 208.00 | 342.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-07:49 | 1921.02 | 20.83 | 61.00 | 218.83 | 1081.80 | 23.47 | 82.50 | 156.00 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2748.14 | 23.56 | 80.67 | 243.50 | 1572.16 | 24.44 | 82.67 | 202.67 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-06:49 | 2742.93 | 19.56 | 58.83 | 311.00 | 1573.37 | 22.36 | 67.83 | 252.67 |
April | 261.17 | 0.50 | 0.48 | 01-APR-06:10 | 3732.71 | 21.83 | 80.67 | 338.83 | 1484.95 | 22.73 | 52.00 | 298.50 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-05:40 | 3083.25 | 20.70 | 99.17 | 395.67 | 1656.44 | 22.27 | 72.83 | 351.00 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-04:00 | 2751.81 | 19.99 | 80.67 | 385.00 | 1526.72 | 22.56 | 69.00 | 351.00 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-04:00 | 2838.80 | 20.62 | 89.67 | 394.33 | 1524.37 | 22.31 | 67.00 | 354.67 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:30 | 3815.01 | 22.74 | 128.17 | 372.00 | 1554.86 | 22.54 | 74.33 | 344.33 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-05:49 | 3312.20 | 21.70 | 82.67 | 319.67 | 1400.81 | 21.70 | 49.00 | 281.33 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 2932.14 | 22.59 | 91.17 | 291.00 | 1532.29 | 23.67 | 119.67 | 261.67 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-06:49 | 1976.15 | 21.37 | 72.00 | 242.17 | 1002.36 | 22.32 | 102.00 | 197.00 |
December | 211.17 | 0.53 | 0.48 | 01-DEC-07:30 | 1757.83 | 20.40 | 64.00 | 214.83 | 1064.76 | 23.86 | 86.33 | 152.17 |
Annual Sum or Average | 3472.67 | 0.51 | 2888.39 | 21.30 | 988.67 | 3726.83 | 1447.03 | 22.76 | 925.17 | 3203.00 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1757.83 | 19.56 | 58.83 | 214.83 | 1002.36 | 21.70 | 49.00 | 152.17 | |
Maximum of Months | 389.17 | 0.53 | 0.48 | 3815.01 | 23.56 | 128.17 | 395.67 | 1656.44 | 24.44 | 119.67 | 354.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.54 | 0.48 | 01-JAN-08:50 | 610.05 | 12.00 | 0.00 | 203.17 | 372.54 | 15.62 | 0.00 | 112.17 |
February | 216.00 | 0.52 | 0.48 | 01-FEB-08:39 | 662.22 | 13.10 | 0.00 | 226.67 | 429.58 | 16.87 | 0.00 | 157.67 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-07:30 | 878.25 | 14.16 | 0.00 | 306.50 | 547.36 | 17.66 | 0.00 | 229.83 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 989.37 | 15.16 | 0.00 | 342.50 | 619.08 | 18.71 | 0.00 | 291.33 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:49 | 1274.51 | 15.68 | 3.00 | 401.83 | 732.94 | 19.17 | 36.67 | 359.00 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-05:10 | 1434.27 | 18.89 | 62.83 | 398.83 | 807.83 | 21.83 | 76.67 | 371.50 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:00 | 1411.94 | 15.75 | 0.00 | 405.00 | 799.49 | 21.32 | 63.33 | 368.17 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:49 | 1165.35 | 15.59 | 0.00 | 377.50 | 703.57 | 19.10 | 8.17 | 346.50 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-06:19 | 906.57 | 14.77 | 0.00 | 317.83 | 572.84 | 18.32 | 0.00 | 263.83 |
October | 305.50 | 0.51 | 0.48 | 01-OCT-14:39 | 821.11 | 14.41 | 0.00 | 286.67 | 530.65 | 18.03 | 0.00 | 239.83 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-07:30 | 680.84 | 12.61 | 0.00 | 230.83 | 406.92 | 16.20 | 0.00 | 146.83 |
December | 211.17 | 0.56 | 0.48 | 01-DEC-08:50 | 492.02 | 10.88 | 0.00 | 190.33 | 310.14 | 14.69 | 0.00 | 84.17 |
Annual Sum or Average | 3472.67 | 0.51 | 1004.96 | 14.78 | 65.83 | 3687.67 | 602.13 | 18.51 | 184.83 | 2970.83 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 492.02 | 10.88 | 0.00 | 190.33 | 310.14 | 14.69 | 0.00 | 84.17 | |
Maximum of Months | 389.17 | 0.56 | 0.48 | 1434.27 | 18.89 | 62.83 | 405.00 | 807.83 | 21.83 | 76.67 | 371.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-08:39 | 1832.26 | 20.59 | 57.17 | 224.50 | 1070.77 | 23.70 | 77.17 | 158.33 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-08:39 | 2128.09 | 21.01 | 57.00 | 242.83 | 1100.28 | 22.17 | 66.50 | 199.67 |
March | 275.00 | 0.50 | 0.48 | 01-MAR-07:30 | 3094.25 | 23.30 | 95.83 | 316.17 | 1729.64 | 24.40 | 88.83 | 265.00 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 3526.51 | 21.53 | 76.83 | 337.83 | 1431.87 | 21.36 | 38.83 | 297.17 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-06:19 | 3325.77 | 18.75 | 69.17 | 393.50 | 1452.53 | 18.82 | 0.00 | 353.17 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:00 | 3198.79 | 15.34 | 1.83 | 389.50 | 1714.46 | 19.00 | 1.50 | 347.50 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:00 | 3008.61 | 18.05 | 49.00 | 395.33 | 1596.77 | 19.13 | 4.50 | 352.33 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-06:10 | 3842.09 | 19.86 | 86.33 | 371.17 | 1664.20 | 19.28 | 15.00 | 344.17 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:40 | 3136.57 | 21.99 | 85.33 | 320.83 | 1615.29 | 23.01 | 66.50 | 280.50 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 3358.68 | 23.74 | 109.33 | 302.17 | 1395.29 | 23.33 | 115.83 | 272.83 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-07:30 | 1619.48 | 20.64 | 68.83 | 243.67 | 874.02 | 23.11 | 94.50 | 197.83 |
December | 211.17 | 0.53 | 0.48 | 01-DEC-08:50 | 1513.49 | 20.77 | 67.50 | 218.00 | 819.98 | 21.77 | 65.50 | 155.33 |
Annual Sum or Average | 3472.67 | 0.50 | 2932.70 | 20.23 | 824.17 | 3755.50 | 1424.26 | 21.26 | 634.67 | 3223.83 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1513.49 | 15.34 | 1.83 | 218.00 | 819.98 | 18.82 | 0.00 | 155.33 | |
Maximum of Months | 389.17 | 0.53 | 0.48 | 3842.09 | 23.74 | 109.33 | 395.33 | 1729.64 | 24.40 | 115.83 | 353.17 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.707678E+09 | 21229.63 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1365012.29 | 16306.59 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.709043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.707678E+09 | 21229.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.549764E+10 | 12401.23 | 02-JAN-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.445489E+10 | 12938.33 | 06-FEB-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.294574E+10 | 11484.65 | 06-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146755E+10 | 11513.38 | 21-APR-16:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.397659E+09 | 11444.15 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1698669.39 | 1869.59 | 02-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13975739.74 | 5683.00 | 20-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.268686E+09 | 11581.20 | 18-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193924E+10 | 11482.94 | 14-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.352713E+10 | 11461.03 | 04-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.549764E+10 | 12938.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.196834E+10 | 9467.44 | 31-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132176E+10 | 9467.44 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.306439E+09 | 9410.36 | 09-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 69115110.34 | 9372.77 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.200264E+09 | 9451.57 | 27-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.716174E+09 | 9435.65 | 30-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.458209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.196834E+10 | 9467.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.373315E+10 | 8968.12 | 02-JAN-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308747E+10 | 9357.25 | 06-FEB-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101981E+10 | 8303.15 | 06-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202108E+09 | 8286.88 | 22-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 58272.56 | 388.48 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.498109E+09 | 8301.69 | 27-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157417E+10 | 8276.89 | 26-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.373315E+10 | 9357.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.213382E+10 | 9546.22 | 01-JAN-01:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155861E+10 | 9546.22 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.324842E+09 | 9546.22 | 01-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 73553049.38 | 9546.22 | 03-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.264854E+09 | 9546.22 | 20-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.827727E+09 | 9546.22 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.518340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.213382E+10 | 9546.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.226165E+10 | 23550.01 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.936341E+09 | 23550.01 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 44158229.73 | 23550.01 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6474866.98 | 23412.08 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.219674E+09 | 23550.01 | 20-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.369471E+09 | 23550.01 | 04-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.383777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.226165E+10 | 23550.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.237484E+10 | 12860.22 | 04-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152525E+10 | 12809.34 | 07-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.368346E+09 | 12801.56 | 01-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 87513602.48 | 12649.90 | 03-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 27222.78 | 28.31 | 28-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.409640E+09 | 12811.03 | 27-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114876E+10 | 12855.27 | 26-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.591437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.237484E+10 | 12860.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.195366E+10 | 10275.26 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130927E+10 | 10275.26 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.284905E+09 | 10275.26 | 01-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 45971063.90 | 10275.26 | 03-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 709633.12 | 1510.45 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.375449E+09 | 10275.26 | 20-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.966830E+09 | 10275.26 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.493680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.195366E+10 | 10275.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.371870E+10 | 9123.48 | 04-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.284932E+10 | 9780.75 | 06-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.707935E+09 | 9107.99 | 13-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115947E+09 | 9065.63 | 03-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1890035.48 | 2813.30 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.821515E+09 | 9137.92 | 27-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199107E+10 | 9134.31 | 28-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.371870E+10 | 9780.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.220933E+10 | 10355.48 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159606E+10 | 10355.48 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.336848E+09 | 10355.48 | 01-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 65283785.32 | 10355.48 | 03-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 820922.39 | 1195.31 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.480798E+09 | 10355.48 | 20-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114908E+10 | 10355.48 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.583821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.220933E+10 | 10355.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.580529E+10 | 32360.00 | 23-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.411192E+10 | 32557.86 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.846470E+09 | 32281.12 | 20-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.193457E+09 | 32334.24 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146782E+10 | 32374.30 | 27-NOV-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.307311E+10 | 32388.21 | 26-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.580529E+10 | 32557.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.408708E+10 | 14282.13 | 24-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.305442E+10 | 14336.39 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111885E+10 | 14273.12 | 06-MAR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.364752E+09 | 14179.51 | 03-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7307355.52 | 11098.16 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31605212.73 | 11961.02 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110592E+10 | 14274.45 | 27-NOV-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.251515E+10 | 14235.64 | 26-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.408708E+10 | 14336.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.332577E+10 | 11428.39 | 19-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.249742E+10 | 11522.38 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.785891E+09 | 11420.02 | 01-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.218659E+09 | 11396.22 | 03-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 654536.24 | 1960.20 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 27558626.24 | 10384.09 | 10-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.935235E+09 | 11412.64 | 27-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.208088E+10 | 11427.93 | 30-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.987207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.332577E+10 | 11522.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.590015E+10 | 10781.68 | 31-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.495406E+10 | 11279.45 | 06-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174900E+10 | 10519.01 | 06-MAR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.438434E+09 | 10508.43 | 25-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5304475.80 | 10494.13 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 68955470.58 | 10468.99 | 19-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188810E+10 | 10543.23 | 27-NOV-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.395902E+10 | 10510.84 | 26-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.590015E+10 | 11279.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.356883E+10 | 12438.94 | 19-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.289118E+10 | 12541.18 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.931610E+09 | 12429.80 | 01-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.253381E+09 | 12360.39 | 21-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4578428.82 | 7020.80 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38100862.07 | 9470.99 | 10-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112762E+10 | 12421.75 | 27-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.233669E+10 | 12438.39 | 30-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.356883E+10 | 12541.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115949E+11 | 23488.46 | 02-JAN-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116107E+11 | 23488.46 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.622986E+10 | 18142.93 | 23-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122820E+10 | 9580.31 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10436541.78 | 2799.96 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120352E+09 | 6466.58 | 28-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.371132E+10 | 18936.18 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.874759E+10 | 18282.85 | 22-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.432533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116107E+11 | 23488.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.118194E+11 | 24871.56 | 02-JAN-08:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117946E+11 | 24871.56 | 06-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.685308E+10 | 19513.58 | 23-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.188569E+10 | 9264.13 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23695710.80 | 3532.14 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.329097E+09 | 6829.63 | 28-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.440773E+10 | 18379.26 | 24-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.929766E+10 | 19965.50 | 22-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.464110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.118194E+11 | 24871.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.128361E+11 | 23827.83 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126584E+11 | 23827.83 | 03-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.722887E+10 | 19750.78 | 23-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217090E+10 | 11265.66 | 03-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41875822.73 | 4523.97 | 01-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1466630.80 | 648.33 | 30-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.487501E+09 | 9478.46 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.479456E+10 | 19011.91 | 24-NOV-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.990588E+10 | 20966.80 | 22-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.501255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.128361E+11 | 23827.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.545388E+09 | 0.395988E+09 | 22788.75 | 27-MAR-16:00 | 18812.61 | 0.00 |
April | 0.00 | 0.00 | 0.495430E+10 | 0.453334E+10 | 42903.81 | 07-APR-15:30 | 42903.81 | 0.00 |
May | 0.00 | 0.00 | 0.164041E+11 | 0.137943E+11 | 80835.95 | 30-MAY-14:00 | 80835.95 | 0.00 |
June | 0.00 | 0.00 | 0.570290E+11 | 0.440906E+11 | 113421.24 | 27-JUN-06:03 | 60526.20 | 0.00 |
July | 0.00 | 0.00 | 0.811990E+11 | 0.601900E+11 | 116073.44 | 22-JUL-05:03 | 61603.57 | 0.00 |
August | 0.00 | 0.00 | 0.834865E+11 | 0.666881E+11 | 113168.94 | 17-AUG-06:03 | 70673.68 | 0.00 |
September | 0.00 | 0.00 | 0.436341E+11 | 0.352787E+11 | 112264.90 | 08-SEP-06:03 | 65753.29 | 0.00 |
October | 0.00 | 0.00 | 0.197058E+11 | 0.141212E+11 | 64844.43 | 05-OCT-12:30 | 47427.68 | 0.00 |
November | 0.00 | 0.00 | 0.142100E+10 | 0.131146E+10 | 18700.56 | 01-NOV-14:00 | 18700.56 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.308379E+12 | 0.240404E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.834865E+11 | 0.666881E+11 | 116073.44 | 80835.95 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.435089E+09 | 0.305754E+09 | 19952.53 | 27-MAR-16:00 | 15730.39 | 0.00 |
April | 0.00 | 0.00 | 0.433191E+10 | 0.390092E+10 | 46136.11 | 07-APR-14:05 | 46136.11 | 0.00 |
May | 0.00 | 0.00 | 0.155016E+11 | 0.132348E+11 | 81598.96 | 30-MAY-14:05 | 81598.96 | 0.00 |
June | 0.00 | 0.00 | 0.520315E+11 | 0.398492E+11 | 103952.29 | 19-JUN-05:02 | 67922.50 | 0.00 |
July | 0.00 | 0.00 | 0.742746E+11 | 0.539367E+11 | 110136.05 | 22-JUL-05:03 | 52394.63 | 0.00 |
August | 0.00 | 0.00 | 0.740242E+11 | 0.583420E+11 | 105750.99 | 17-AUG-05:03 | 60800.20 | 0.00 |
September | 0.00 | 0.00 | 0.365417E+11 | 0.289348E+11 | 96825.54 | 01-SEP-05:02 | 61154.38 | 0.00 |
October | 0.00 | 0.00 | 0.155947E+11 | 0.108981E+11 | 59478.20 | 04-OCT-14:05 | 47156.97 | 0.00 |
November | 0.00 | 0.00 | 0.351740E+09 | 0.293365E+09 | 9125.36 | 03-NOV-14:05 | 9125.36 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.273087E+12 | 0.209695E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.742746E+11 | 0.583420E+11 | 110136.05 | 81598.96 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.454398E+09 | 0.311466E+09 | 20829.63 | 27-MAR-16:00 | 15704.89 | 0.00 |
April | 0.00 | 0.00 | 0.436818E+10 | 0.391565E+10 | 49538.75 | 07-APR-14:30 | 49538.75 | 0.00 |
May | 0.00 | 0.00 | 0.162256E+11 | 0.138787E+11 | 89372.78 | 30-MAY-14:00 | 89372.78 | 0.00 |
June | 0.00 | 0.00 | 0.550103E+11 | 0.427398E+11 | 116624.24 | 19-JUN-05:02 | 74424.62 | 0.00 |
July | 0.00 | 0.00 | 0.791150E+11 | 0.585221E+11 | 123581.59 | 22-JUL-05:03 | 55322.69 | 0.00 |
August | 0.00 | 0.00 | 0.784007E+11 | 0.626930E+11 | 119241.46 | 17-AUG-05:03 | 62419.98 | 0.00 |
September | 0.00 | 0.00 | 0.371507E+11 | 0.292894E+11 | 86511.47 | 01-SEP-14:10 | 86511.47 | 0.00 |
October | 0.00 | 0.00 | 0.149412E+11 | 0.103865E+11 | 60800.28 | 04-OCT-13:50 | 50222.27 | 0.00 |
November | 0.00 | 0.00 | 0.307646E+09 | 0.242693E+09 | 7674.19 | 03-NOV-14:00 | 7674.19 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.285974E+12 | 0.221979E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.791150E+11 | 0.626930E+11 | 123581.59 | 89372.78 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 1879.06 | 6590.02 | 30-JAN-12:07 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1907.54 | 6606.79 | 06-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1990.19 | 6528.45 | 03-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1770.52 | 6251.89 | 03-APR-11:06 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1718.67 | 5909.29 | 01-MAY-11:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1644.33 | 5477.83 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1436.86 | 5113.00 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1558.86 | 5002.89 | 29-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1498.55 | 5226.19 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1586.39 | 5661.97 | 31-OCT-11:06 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1725.11 | 6035.57 | 30-NOV-12:15 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1758.99 | 6373.13 | 29-DEC-12:13 |
Annual Sum or Average | 0.00 | 1705.11 | ||||
Minimum of Months | 0.00 | 0.00 | 1436.86 | 5002.89 | ||
Maximum of Months | 0.00 | 0.00 | 1990.19 | 6606.79 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.121059E+10 | 0.31 | 2421.32 | 02-JAN-07:01 | 0.75 |
February | 0.106811E+10 | 0.30 | 1328.50 | 01-FEB-07:02 | 0.56 |
March | 0.139237E+10 | 0.31 | 1849.04 | 16-MAR-07:03 | 0.65 |
April | 0.170916E+10 | 0.31 | 4422.59 | 10-APR-15:10 | 1.04 |
May | 0.273497E+10 | 0.38 | 8806.16 | 30-MAY-12:10 | 1.59 |
June | 0.458333E+10 | 0.49 | 10544.51 | 19-JUN-05:02 | 1.78 |
July | 0.578299E+10 | 0.54 | 10544.51 | 07-JUL-06:03 | 1.78 |
August | 0.636422E+10 | 0.58 | 10544.51 | 05-AUG-06:03 | 1.78 |
September | 0.412147E+10 | 0.46 | 10544.51 | 05-SEP-05:12 | 1.79 |
October | 0.318273E+10 | 0.39 | 6557.51 | 05-OCT-16:00 | 1.32 |
November | 0.146734E+10 | 0.29 | 3232.64 | 03-NOV-15:10 | 0.87 |
December | 0.115858E+10 | 0.28 | 1753.23 | 22-DEC-08:05 | 0.63 |
Annual Sum or Average | 0.347759E+11 | 0.39 | |||
Minimum of Months | 0.106811E+10 | 0.28 | 1328.50 | 0.56 | |
Maximum of Months | 0.636422E+10 | 0.58 | 10544.51 | 1.79 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.111458E+10 | 0.30 | 2376.45 | 02-JAN-05:01 | 0.79 |
February | 0.981608E+09 | 0.30 | 2376.45 | 06-FEB-06:01 | 0.79 |
March | 0.115748E+10 | 0.30 | 2376.45 | 13-MAR-06:01 | 0.78 |
April | 0.145324E+10 | 0.31 | 5118.14 | 10-APR-14:05 | 1.23 |
May | 0.249423E+10 | 0.38 | 9367.70 | 30-MAY-14:05 | 1.79 |
June | 0.415165E+10 | 0.49 | 9367.70 | 19-JUN-05:02 | 1.78 |
July | 0.517942E+10 | 0.54 | 9367.70 | 03-JUL-06:03 | 1.78 |
August | 0.573530E+10 | 0.58 | 9367.70 | 03-AUG-06:03 | 1.78 |
September | 0.319038E+10 | 0.42 | 9367.70 | 05-SEP-06:03 | 1.78 |
October | 0.220725E+10 | 0.35 | 5953.60 | 04-OCT-15:50 | 1.33 |
November | 0.105213E+10 | 0.28 | 2573.54 | 03-NOV-14:05 | 0.82 |
December | 0.991317E+09 | 0.28 | 2376.45 | 07-DEC-07:01 | 0.78 |
Annual Sum or Average | 0.297086E+11 | 0.38 | |||
Minimum of Months | 0.981608E+09 | 0.28 | 2376.45 | 0.78 | |
Maximum of Months | 0.573530E+10 | 0.58 | 9367.70 | 1.79 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148766E+10 | 0.39 | 2385.27 | 01-JAN-01:22 | 0.73 |
February | 0.127361E+10 | 0.37 | 2385.27 | 01-FEB-06:01 | 0.73 |
March | 0.127943E+10 | 0.33 | 2385.27 | 01-MAR-06:11 | 0.72 |
April | 0.147317E+10 | 0.32 | 4630.43 | 07-APR-15:20 | 1.05 |
May | 0.240056E+10 | 0.37 | 9610.70 | 30-MAY-14:10 | 1.65 |
June | 0.396871E+10 | 0.46 | 10863.78 | 19-JUN-05:02 | 1.78 |
July | 0.501628E+10 | 0.50 | 10863.78 | 10-JUL-04:02 | 1.78 |
August | 0.554525E+10 | 0.53 | 10069.32 | 14-AUG-14:40 | 1.69 |
September | 0.290752E+10 | 0.39 | 8468.81 | 05-SEP-15:10 | 1.52 |
October | 0.193503E+10 | 0.33 | 5549.76 | 04-OCT-15:30 | 1.17 |
November | 0.116145E+10 | 0.31 | 2385.27 | 20-NOV-06:01 | 0.72 |
December | 0.121450E+10 | 0.33 | 2385.27 | 02-DEC-06:01 | 0.73 |
Annual Sum or Average | 0.296632E+11 | 0.39 | |||
Minimum of Months | 0.116145E+10 | 0.31 | 2385.27 | 0.72 | |
Maximum of Months | 0.554525E+10 | 0.53 | 10863.78 | 1.78 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:02 | 2.06 | 2.06 | 57.14 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 55.55 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:05 | 2.06 | 2.06 | 56.04 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 55.29 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 55.97 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:05 | 2.06 | 2.06 | 56.25 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 57.16 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 56.78 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:02 | 2.06 | 2.06 | 56.26 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.82 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 56.00 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:05 | 2.06 | 2.06 | 55.40 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 55.29 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.82 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 56.91 | 56.91 | 1879.06 | 6590.02 | 30-JAN-12:07 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 55.90 | 55.90 | 1907.54 | 6606.79 | 06-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.84 | 56.84 | 1990.19 | 6528.45 | 03-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 55.94 | 55.94 | 1770.52 | 6251.89 | 03-APR-11:06 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.70 | 56.70 | 1718.67 | 5909.29 | 01-MAY-11:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.68 | 56.68 | 1644.33 | 5477.83 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.57 | 57.57 | 1436.86 | 5113.00 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.11 | 57.11 | 1558.86 | 5002.89 | 29-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.55 | 56.55 | 1498.55 | 5226.19 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 55.63 | 55.63 | 1586.39 | 5661.97 | 31-OCT-11:06 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.96 | 56.96 | 1725.11 | 6035.57 | 30-NOV-12:15 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.36 | 56.36 | 1758.99 | 6373.13 | 29-DEC-12:13 |
Annual Sum or Average | 0.00 | 1705.11 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.63 | 55.63 | 1436.86 | 5002.89 | ||
Maximum of Months | 0.00 | 0.00 | 57.57 | 57.57 | 1990.19 | 6606.79 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.152512E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.114922E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.613532E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.481497E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.732312E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.185004E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.258024E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.272182E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.147051E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.821440E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.476032E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.780378E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.152021E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.476032E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.272182E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.136328E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.919785E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.301577E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.289498E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.644340E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.168638E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.234578E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.242128E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.120987E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.600940E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.345855E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.661652E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.127902E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.289498E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.242128E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.241748E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.187826E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.683356E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.407072E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.657703E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.174941E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.245573E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.251946E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.120471E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.578728E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.777384E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.151794E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.168472E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.407072E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.251946E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.121059E+10 | 0.00 | 0.256355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106811E+10 | 0.00 | 0.220348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139237E+10 | 0.545388E+09 | 0.108267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170916E+10 | 0.495430E+10 | 0.304052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.273497E+10 | 0.164041E+11 | 0.408154E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.458333E+10 | 0.570290E+11 | 1698669.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.578299E+10 | 0.811990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.636422E+10 | 0.834865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.412147E+10 | 0.436341E+11 | 13975739.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.318273E+10 | 0.197058E+11 | 0.389038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146734E+10 | 0.142100E+10 | 0.661378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115858E+10 | 0.00 | 0.153928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.347759E+11 | 0.308379E+12 | 0.843569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.106811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.636422E+10 | 0.834865E+11 | 0.256355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.111458E+10 | 0.00 | 0.243376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.981608E+09 | 0.00 | 0.200109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115748E+10 | 0.435089E+09 | 0.859527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145324E+10 | 0.433191E+10 | 0.220689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.249423E+10 | 0.155016E+11 | 23695710.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.415165E+10 | 0.520315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.517942E+10 | 0.742746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.573530E+10 | 0.740242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.319038E+10 | 0.365417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.220725E+10 | 0.155947E+11 | 0.332545E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105213E+10 | 0.351740E+09 | 0.671481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.991317E+09 | 0.00 | 0.149229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.297086E+11 | 0.273087E+12 | 0.771445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.981608E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.573530E+10 | 0.742746E+11 | 0.243376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148766E+10 | 0.00 | 0.355232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127361E+10 | 0.00 | 0.301674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127943E+10 | 0.454398E+09 | 0.126607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147317E+10 | 0.436818E+10 | 0.363958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.240056E+10 | 0.162256E+11 | 59720619.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.396871E+10 | 0.550103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.501628E+10 | 0.791150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.554525E+10 | 0.784007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.290752E+10 | 0.371507E+11 | 1466630.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.193503E+10 | 0.149412E+11 | 0.653721E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116145E+10 | 0.307646E+09 | 0.113193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121450E+10 | 0.00 | 0.238707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296632E+11 | 0.285974E+12 | 0.117896E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.116145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.554525E+10 | 0.791150E+11 | 0.355232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.121059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139237E+10 | 0.00 | 0.00 | 0.00 | 0.146118E+09 | 0.459683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170916E+10 | 0.00 | 0.00 | 0.00 | 0.129349E+10 | 0.181232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.273497E+10 | 0.00 | 0.00 | 0.00 | 0.419043E+10 | 0.397718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.458333E+10 | 0.00 | 0.00 | 0.00 | 0.139154E+11 | 1698669.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.578299E+10 | 0.00 | 0.00 | 0.00 | 0.200195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.636422E+10 | 0.00 | 0.00 | 0.00 | 0.208540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.412147E+10 | 0.00 | 0.00 | 0.00 | 0.105696E+11 | 13975739.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.318273E+10 | 0.00 | 0.00 | 0.00 | 0.476298E+10 | 0.268686E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146734E+10 | 0.00 | 0.00 | 0.00 | 0.390521E+09 | 0.290246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.347759E+11 | 0.00 | 0.00 | 0.00 | 0.761420E+11 | 0.411036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.106811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.636422E+10 | 0.00 | 0.00 | 0.00 | 0.208540E+11 | 0.140406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.111458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.981608E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115748E+10 | 0.00 | 0.00 | 0.00 | 0.116097E+09 | 0.174219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145324E+10 | 0.00 | 0.00 | 0.00 | 0.112055E+10 | 0.321191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.249423E+10 | 0.00 | 0.00 | 0.00 | 0.394917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.415165E+10 | 0.00 | 0.00 | 0.00 | 0.127122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.517942E+10 | 0.00 | 0.00 | 0.00 | 0.182784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.573530E+10 | 0.00 | 0.00 | 0.00 | 0.184775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.319038E+10 | 0.00 | 0.00 | 0.00 | 0.890830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.220725E+10 | 0.00 | 0.00 | 0.00 | 0.379871E+10 | 3447813.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105213E+10 | 0.00 | 0.00 | 0.00 | 99343333.82 | 0.230708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.991317E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.297086E+11 | 0.00 | 0.00 | 0.00 | 0.674602E+11 | 0.307335E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.981608E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.573530E+10 | 0.00 | 0.00 | 0.00 | 0.184775E+11 | 0.125182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.148766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127943E+10 | 0.00 | 0.00 | 0.00 | 0.122306E+09 | 0.543182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147317E+10 | 0.00 | 0.00 | 0.00 | 0.112886E+10 | 0.146868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.240056E+10 | 0.00 | 0.00 | 0.00 | 0.415862E+10 | 17844796.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.396871E+10 | 0.00 | 0.00 | 0.00 | 0.135254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.501628E+10 | 0.00 | 0.00 | 0.00 | 0.195410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.554525E+10 | 0.00 | 0.00 | 0.00 | 0.196493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.290752E+10 | 0.00 | 0.00 | 0.00 | 0.913961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.193503E+10 | 0.00 | 0.00 | 0.00 | 0.368603E+10 | 0.166220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116145E+10 | 0.00 | 0.00 | 0.00 | 87683029.50 | 0.652470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296632E+11 | 0.00 | 0.00 | 0.00 | 0.710389E+11 | 0.677702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.116145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.554525E+10 | 0.00 | 0.00 | 0.00 | 0.196493E+11 | 0.226871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.927889E+10 | 0.00 | 0.00 | 6785791.05 | 0.00 | 0.618185E+09 | 0.535525E+10 | 0.00 | 0.30 |
February | 0.822002E+10 | 0.00 | 0.00 | 9381420.03 | 0.00 | 795976.43 | 0.730334E+10 | 0.00 | 0.31 |
March | 0.442105E+10 | 0.00 | 0.00 | 25116516.94 | 0.00 | 0.00 | 0.140819E+11 | 0.00 | 0.44 |
April | 0.160557E+10 | 8066808.90 | 0.00 | 29562661.82 | 0.00 | 0.00 | 0.145536E+11 | 0.00 | 0.58 |
May | 0.838931E+09 | 0.104444E+09 | 0.00 | 39142445.24 | 0.00 | 0.00 | 0.161504E+11 | 0.00 | 0.94 |
June | 0.194238E+09 | 0.324452E+10 | 0.00 | 17011906.03 | 41150626.77 | 0.00 | 0.354016E+10 | 0.00 | 0.65 |
July | 6517883.20 | 0.796139E+10 | 0.00 | 1423586.40 | 0.107227E+09 | 0.00 | 0.133900E+09 | 0.00 | 0.29 |
August | 0.124191E+09 | 0.624617E+10 | 0.00 | 13703106.91 | 88774277.61 | 0.00 | 0.158763E+10 | 0.00 | 0.54 |
September | 0.506740E+09 | 0.202598E+10 | 0.00 | 27073329.90 | 17715792.47 | 0.00 | 0.811674E+10 | 0.00 | 0.79 |
October | 0.950975E+09 | 0.171651E+09 | 0.00 | 41444254.46 | 0.00 | 0.00 | 0.154440E+11 | 0.00 | 0.86 |
November | 0.273396E+10 | 0.00 | 0.00 | 27061367.85 | 0.00 | 0.00 | 0.145844E+11 | 0.00 | 0.49 |
December | 0.631281E+10 | 0.00 | 0.00 | 15285631.73 | 0.00 | 0.00 | 0.101021E+11 | 0.00 | 0.33 |
Annual Sum or Average | 0.351939E+11 | 0.197622E+11 | 0.00 | 0.252992E+09 | 0.254868E+09 | 0.618981E+09 | 0.110953E+12 | 0.00 | 0.54 |
Minimum of Months | 6517883.20 | 0.00 | 0.00 | 1423586.40 | 0.00 | 0.00 | 0.133900E+09 | 0.00 | 0.29 |
Maximum of Months | 0.927889E+10 | 0.796139E+10 | 0.00 | 41444254.46 | 0.107227E+09 | 0.618185E+09 | 0.161504E+11 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152921E+10 | 0.00 | 0.00 | 0.28 |
February | 0.130126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669869E+09 | 0.00 | 0.00 | 0.28 |
March | 0.117499E+11 | 0.00 | 0.00 | 1694893.65 | 0.00 | 19508264.07 | 0.187767E+10 | 0.00 | 0.32 |
April | 0.535228E+10 | 4201431.32 | 0.00 | 9528397.29 | 0.00 | 766327.07 | 0.594154E+10 | 0.00 | 0.41 |
May | 0.212327E+10 | 83887990.46 | 0.00 | 20203350.93 | 0.00 | 0.00 | 0.903440E+10 | 0.00 | 0.62 |
June | 0.298646E+09 | 0.250906E+10 | 0.00 | 10936597.75 | 39262488.32 | 0.00 | 0.230771E+10 | 0.00 | 0.47 |
July | 8237788.55 | 0.664237E+10 | 0.00 | 1042463.85 | 0.105373E+09 | 0.00 | 97727772.90 | 0.00 | 0.24 |
August | 0.153105E+09 | 0.533388E+10 | 0.00 | 9137395.37 | 88450448.90 | 0.00 | 0.106786E+10 | 0.00 | 0.41 |
September | 0.802893E+09 | 0.164556E+10 | 0.00 | 14945980.47 | 18228810.04 | 0.00 | 0.468418E+10 | 0.00 | 0.53 |
October | 0.223392E+10 | 0.140143E+09 | 0.00 | 18228519.16 | 2293552.15 | 0.00 | 0.758530E+10 | 0.00 | 0.52 |
November | 0.874441E+10 | 0.00 | 0.00 | 4161322.62 | 0.00 | 75081175.36 | 0.302882E+10 | 0.00 | 0.33 |
December | 0.131092E+11 | 0.00 | 0.00 | 15952.39 | 0.00 | 94801282.13 | 0.117166E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.700738E+11 | 0.163591E+11 | 0.00 | 89894873.48 | 0.253608E+09 | 0.238924E+10 | 0.357424E+11 | 0.00 | 0.39 |
Minimum of Months | 8237788.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.131092E+11 | 0.664237E+10 | 0.00 | 20203350.93 | 0.105373E+09 | 0.152921E+10 | 0.903440E+10 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.913946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400925E+10 | 0.00 | 0.00 | 0.27 |
February | 0.970656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311711E+10 | 0.00 | 0.00 | 0.28 |
March | 0.116446E+11 | 0.00 | 0.00 | 844646.14 | 0.00 | 0.480391E+09 | 0.980384E+09 | 0.00 | 0.32 |
April | 0.636094E+10 | 2172417.57 | 0.00 | 7511774.11 | 0.00 | 58529756.38 | 0.449002E+10 | 0.00 | 0.40 |
May | 0.289886E+10 | 69650323.32 | 0.00 | 17743822.46 | 0.00 | 0.00 | 0.827203E+10 | 0.00 | 0.61 |
June | 0.427263E+09 | 0.240159E+10 | 0.00 | 10668163.45 | 35685374.71 | 0.00 | 0.229690E+10 | 0.00 | 0.48 |
July | 12267014.46 | 0.645260E+10 | 0.00 | 1156859.41 | 95620512.45 | 0.00 | 93608142.41 | 0.00 | 0.25 |
August | 0.165083E+09 | 0.515180E+10 | 0.00 | 9022124.57 | 82227035.34 | 0.00 | 0.100735E+10 | 0.00 | 0.43 |
September | 0.140499E+10 | 0.160497E+10 | 0.00 | 11601475.24 | 17920946.06 | 0.00 | 0.364963E+10 | 0.00 | 0.51 |
October | 0.350548E+10 | 85927889.13 | 0.00 | 11539661.22 | 899725.66 | 0.00 | 0.509840E+10 | 0.00 | 0.48 |
November | 0.857108E+10 | 0.00 | 0.00 | 1483237.10 | 0.00 | 0.867400E+09 | 0.136953E+10 | 0.00 | 0.31 |
December | 0.103341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202387E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.641707E+11 | 0.157687E+11 | 0.00 | 71571763.70 | 0.232354E+09 | 0.105566E+11 | 0.272578E+11 | 0.00 | 0.39 |
Minimum of Months | 12267014.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.116446E+11 | 0.645260E+10 | 0.00 | 17743822.46 | 95620512.45 | 0.400925E+10 | 0.827203E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.338274E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283529E+10 | 0.00 | 0.00 | 0.31 |
February | 0.409464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265732E+10 | 0.00 | 0.00 | 0.31 |
March | 0.154835E+10 | 0.00 | 0.00 | 41499.76 | 0.00 | 0.120620E+10 | 52303069.32 | 0.00 | 0.32 |
April | 0.145260E+10 | 555240.06 | 0.00 | 1206575.28 | 0.00 | 0.278533E+09 | 0.570361E+09 | 0.00 | 0.41 |
May | 0.797778E+09 | 22150820.14 | 0.00 | 4231795.72 | 0.00 | 2898463.15 | 0.177205E+10 | 0.00 | 0.70 |
June | 99216476.07 | 0.766654E+09 | 0.00 | 2953057.18 | 8172265.03 | 0.00 | 0.615978E+09 | 0.00 | 0.65 |
July | 2173651.53 | 0.213332E+10 | 0.00 | 366171.22 | 20239000.82 | 0.00 | 25919959.08 | 0.00 | 0.38 |
August | 42568360.39 | 0.168872E+10 | 0.00 | 2439632.67 | 18290223.32 | 0.00 | 0.256803E+09 | 0.00 | 0.59 |
September | 0.398372E+09 | 0.417950E+09 | 0.00 | 2450969.72 | 6646178.15 | 0.00 | 0.712994E+09 | 0.00 | 0.57 |
October | 0.103655E+10 | 19230278.55 | 0.00 | 1642737.29 | 1746575.12 | 42971731.39 | 0.618484E+09 | 0.00 | 0.47 |
November | 0.119056E+10 | 0.00 | 0.00 | 32152.21 | 0.00 | 0.109732E+10 | 30679923.55 | 0.00 | 0.31 |
December | 0.406707E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231433E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.772262E+10 | 0.504858E+10 | 0.00 | 15364591.05 | 55094242.44 | 0.104349E+11 | 0.465557E+10 | 0.00 | 0.44 |
Minimum of Months | 2173651.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.154835E+10 | 0.213332E+10 | 0.00 | 4231795.72 | 20239000.82 | 0.283529E+10 | 0.177205E+10 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.409745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153226E+10 | 0.00 | 0.00 | 0.30 |
February | 0.605486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122063E+10 | 0.00 | 0.00 | 0.30 |
March | 0.102727E+10 | 0.00 | 0.00 | 689915.60 | 0.00 | 0.476664E+09 | 0.397604E+09 | 0.00 | 0.35 |
April | 0.679870E+09 | 1188458.23 | 0.00 | 2587113.22 | 0.00 | 0.141379E+09 | 0.125150E+10 | 0.00 | 0.62 |
May | 0.384627E+09 | 23385576.42 | 0.00 | 5750022.89 | 0.00 | 166777.13 | 0.224716E+10 | 0.00 | 1.11 |
June | 37958934.70 | 0.628136E+09 | 0.00 | 3516910.97 | 5246021.11 | 0.00 | 0.746668E+09 | 0.00 | 0.93 |
July | 704189.96 | 0.177489E+10 | 0.00 | 443725.29 | 12816459.00 | 0.00 | 37336816.70 | 0.00 | 0.53 |
August | 17782621.45 | 0.152570E+10 | 0.00 | 2846263.03 | 10950042.53 | 0.00 | 0.332065E+09 | 0.00 | 0.93 |
September | 0.176906E+09 | 0.342829E+09 | 0.00 | 3624266.68 | 3878419.80 | 0.00 | 0.963821E+09 | 0.00 | 0.87 |
October | 0.438618E+09 | 17361639.23 | 0.00 | 2984697.30 | 417923.01 | 15000490.13 | 0.111303E+10 | 0.00 | 0.72 |
November | 0.788895E+09 | 0.00 | 0.00 | 279028.05 | 0.00 | 0.488536E+09 | 0.213369E+09 | 0.00 | 0.32 |
December | 0.611847E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109336E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.517971E+10 | 0.431349E+10 | 0.00 | 22721943.02 | 33308865.44 | 0.496799E+10 | 0.730256E+10 | 0.00 | 0.61 |
Minimum of Months | 704189.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.102727E+10 | 0.177489E+10 | 0.00 | 5750022.89 | 12816459.00 | 0.153226E+10 | 0.224716E+10 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.801481E+09 | 0.00 | 0.00 | 1088023.71 | 0.00 | 0.176874E+10 | 0.754583E+09 | 0.00 | 0.32 |
February | 0.931267E+09 | 0.00 | 0.00 | 1600745.32 | 0.00 | 0.142474E+10 | 0.109735E+10 | 0.00 | 0.35 |
March | 0.137584E+10 | 0.00 | 0.00 | 4282943.01 | 0.00 | 0.618985E+09 | 0.232299E+10 | 0.00 | 0.52 |
April | 0.112342E+10 | 1485624.78 | 0.00 | 4672719.64 | 0.00 | 0.223225E+09 | 0.218446E+10 | 0.00 | 0.67 |
May | 0.736351E+09 | 27931347.44 | 0.00 | 6614176.11 | 0.00 | 6339130.78 | 0.264528E+10 | 0.00 | 0.92 |
June | 0.110092E+09 | 0.865568E+09 | 0.00 | 3626033.13 | 8203220.95 | 0.00 | 0.738254E+09 | 0.00 | 0.74 |
July | 4294261.94 | 0.244163E+10 | 0.00 | 471642.01 | 20549904.53 | 0.00 | 25003804.64 | 0.00 | 0.43 |
August | 37986509.73 | 0.223375E+10 | 0.00 | 4042208.81 | 18102132.58 | 0.00 | 0.396301E+09 | 0.00 | 0.84 |
September | 0.277471E+09 | 0.619757E+09 | 0.00 | 7461668.54 | 5995454.68 | 0.00 | 0.189208E+10 | 0.00 | 1.05 |
October | 0.541157E+09 | 54235487.62 | 0.00 | 9528145.66 | 68386.59 | 19508187.92 | 0.370050E+10 | 0.00 | 1.17 |
November | 0.108152E+10 | 0.00 | 0.00 | 3044217.10 | 0.00 | 0.575506E+09 | 0.171715E+10 | 0.00 | 0.50 |
December | 0.917595E+09 | 0.00 | 0.00 | 1370617.81 | 0.00 | 0.135465E+10 | 0.857265E+09 | 0.00 | 0.33 |
Annual Sum or Average | 0.793848E+10 | 0.624435E+10 | 0.00 | 47803140.86 | 52919099.34 | 0.599170E+10 | 0.183312E+11 | 0.00 | 0.66 |
Minimum of Months | 4294261.94 | 0.00 | 0.00 | 471642.01 | 0.00 | 0.00 | 25003804.64 | 0.00 | 0.32 |
Maximum of Months | 0.137584E+10 | 0.244163E+10 | 0.00 | 9528145.66 | 20549904.53 | 0.176874E+10 | 0.370050E+10 | 0.00 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.392615E+09 | 0.00 | 0.00 | 20722.33 | 0.00 | 0.158168E+10 | 28914180.35 | 0.00 | 0.31 |
February | 0.450142E+09 | 0.00 | 0.00 | 96291.47 | 0.00 | 0.141014E+10 | 0.102247E+09 | 0.00 | 0.31 |
March | 0.899879E+09 | 0.00 | 0.00 | 1201725.90 | 0.00 | 0.580087E+09 | 0.715160E+09 | 0.00 | 0.41 |
April | 0.757053E+09 | 420211.53 | 0.00 | 2799065.85 | 0.00 | 0.154031E+09 | 0.130062E+10 | 0.00 | 0.67 |
May | 0.404953E+09 | 21402166.49 | 0.00 | 5501013.38 | 0.00 | 3798584.84 | 0.206790E+10 | 0.00 | 1.08 |
June | 59691964.40 | 0.666754E+09 | 0.00 | 3073029.17 | 3697976.52 | 0.00 | 0.588036E+09 | 0.00 | 0.93 |
July | 2701776.77 | 0.181403E+10 | 0.00 | 407352.87 | 5703278.00 | 0.00 | 16180771.52 | 0.00 | 0.51 |
August | 25136595.54 | 0.159026E+10 | 0.00 | 2463020.76 | 6555323.36 | 0.00 | 0.227752E+09 | 0.00 | 0.89 |
September | 0.213968E+09 | 0.382690E+09 | 0.00 | 3381168.95 | 3331203.10 | 0.00 | 0.836663E+09 | 0.00 | 0.86 |
October | 0.517593E+09 | 26949533.70 | 0.00 | 2867770.53 | 43275.94 | 25776407.15 | 0.112613E+10 | 0.00 | 0.76 |
November | 0.723647E+09 | 0.00 | 0.00 | 331345.17 | 0.00 | 0.607167E+09 | 0.235288E+09 | 0.00 | 0.34 |
December | 0.429418E+09 | 0.00 | 0.00 | 6015.27 | 0.00 | 0.128469E+10 | 13845612.11 | 0.00 | 0.29 |
Annual Sum or Average | 0.487680E+10 | 0.450250E+10 | 0.00 | 22148521.65 | 19331056.92 | 0.564738E+10 | 0.725873E+10 | 0.00 | 0.61 |
Minimum of Months | 2701776.77 | 0.00 | 0.00 | 6015.27 | 0.00 | 0.00 | 13845612.11 | 0.00 | 0.29 |
Maximum of Months | 0.899879E+09 | 0.181403E+10 | 0.00 | 5501013.38 | 6555323.36 | 0.158168E+10 | 0.206790E+10 | 0.00 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.549419E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267854E+10 | 0.00 | 0.00 | 0.29 |
February | 0.515565E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262556E+10 | 0.00 | 0.00 | 0.29 |
March | 0.184632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959171E+09 | 0.00 | 0.00 | 0.31 |
April | 0.172994E+10 | 517034.15 | 0.00 | 315524.27 | 337358.08 | 0.148581E+09 | 0.166519E+09 | 0.00 | 0.33 |
May | 0.110240E+10 | 18101007.25 | 0.00 | 2045643.58 | 0.00 | 0.00 | 0.814417E+09 | 0.00 | 0.52 |
June | 92111540.24 | 0.584976E+09 | 0.00 | 2051277.28 | 9207935.59 | 0.00 | 0.434687E+09 | 0.00 | 0.48 |
July | 1997432.59 | 0.165702E+10 | 0.00 | 236637.51 | 22634571.16 | 0.00 | 21744540.94 | 0.00 | 0.28 |
August | 49027976.13 | 0.137002E+10 | 0.00 | 2043545.77 | 18739344.91 | 0.00 | 0.218168E+09 | 0.00 | 0.47 |
September | 0.329852E+09 | 0.349245E+09 | 0.00 | 2704624.56 | 3739623.17 | 0.00 | 0.797526E+09 | 0.00 | 0.54 |
October | 0.983792E+09 | 26420294.02 | 0.00 | 2156769.90 | 94883.90 | 0.00 | 0.854480E+09 | 0.00 | 0.47 |
November | 0.170318E+10 | 0.00 | 0.00 | 90006.24 | 0.00 | 0.500600E+09 | 0.135538E+09 | 0.00 | 0.29 |
December | 0.118581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164268E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.100894E+11 | 0.400630E+10 | 0.00 | 11644029.11 | 54753716.81 | 0.855514E+10 | 0.344308E+10 | 0.00 | 0.38 |
Minimum of Months | 1997432.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.184632E+10 | 0.165702E+10 | 0.00 | 2704624.56 | 22634571.16 | 0.267854E+10 | 0.854480E+09 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.621473E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139555E+10 | 0.00 | 0.00 | 0.29 |
February | 0.756595E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116320E+10 | 0.00 | 0.00 | 0.29 |
March | 0.130060E+10 | 0.00 | 0.00 | 314873.56 | 0.00 | 0.294153E+09 | 0.221067E+09 | 0.00 | 0.32 |
April | 0.838033E+09 | 1551357.27 | 0.00 | 1773972.58 | 0.00 | 50775631.50 | 0.802542E+09 | 0.00 | 0.49 |
May | 0.459772E+09 | 21560937.34 | 0.00 | 3896055.74 | 0.00 | 0.00 | 0.151173E+10 | 0.00 | 0.86 |
June | 32480551.86 | 0.512766E+09 | 0.00 | 2725983.24 | 5589346.79 | 0.00 | 0.591370E+09 | 0.00 | 0.75 |
July | 1117842.83 | 0.146612E+10 | 0.00 | 300025.38 | 14352874.36 | 0.00 | 30503728.02 | 0.00 | 0.41 |
August | 20236545.78 | 0.131224E+10 | 0.00 | 2543270.64 | 11836244.23 | 0.00 | 0.300819E+09 | 0.00 | 0.79 |
September | 0.115108E+09 | 0.311376E+09 | 0.00 | 3829294.40 | 2362040.58 | 0.00 | 0.107782E+10 | 0.00 | 0.85 |
October | 0.357314E+09 | 25980883.46 | 0.00 | 4005449.49 | 0.00 | 0.00 | 0.151159E+10 | 0.00 | 0.79 |
November | 0.977538E+09 | 0.00 | 0.00 | 791013.06 | 0.00 | 0.228112E+09 | 0.396876E+09 | 0.00 | 0.33 |
December | 0.104315E+10 | 0.00 | 0.00 | 217.80 | 0.00 | 0.744349E+09 | 2427645.30 | 0.00 | 0.27 |
Annual Sum or Average | 0.652342E+10 | 0.365159E+10 | 0.00 | 20180155.89 | 34140505.97 | 0.387615E+10 | 0.644674E+10 | 0.00 | 0.54 |
Minimum of Months | 1117842.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.130060E+10 | 0.146612E+10 | 0.00 | 4005449.49 | 14352874.36 | 0.139555E+10 | 0.151173E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.881538E+09 | 0.00 | 0.00 | 16319.29 | 0.00 | 0.329701E+10 | 28719651.70 | 0.00 | 0.38 |
February | 0.952966E+09 | 0.00 | 0.00 | 72405.00 | 0.00 | 0.301671E+10 | 95249862.45 | 0.00 | 0.38 |
March | 0.151305E+10 | 0.00 | 0.00 | 659971.68 | 0.00 | 0.173456E+10 | 0.405997E+09 | 0.00 | 0.40 |
April | 0.133905E+10 | 2843587.26 | 0.00 | 1464202.93 | 0.00 | 0.699460E+09 | 0.565613E+09 | 0.00 | 0.46 |
May | 0.115685E+10 | 27536509.18 | 0.00 | 2162034.00 | 153323.79 | 0.171139E+09 | 0.812456E+09 | 0.00 | 0.59 |
June | 0.139118E+09 | 0.717282E+09 | 0.00 | 2026427.72 | 21333674.43 | 527121.50 | 0.400071E+09 | 0.00 | 0.53 |
July | 6642331.72 | 0.217666E+10 | 0.00 | 274672.56 | 25912185.79 | 0.00 | 15560088.35 | 0.00 | 0.36 |
August | 65932882.39 | 0.218428E+10 | 0.00 | 3212546.50 | 21708522.51 | 0.00 | 0.283394E+09 | 0.00 | 0.72 |
September | 0.271646E+09 | 0.577690E+09 | 0.00 | 6288276.13 | 8443906.55 | 9223459.31 | 0.159945E+10 | 0.00 | 0.93 |
October | 0.506240E+09 | 73484679.37 | 0.00 | 8558681.94 | 0.00 | 0.109652E+09 | 0.319254E+10 | 0.00 | 1.06 |
November | 0.142743E+10 | 0.00 | 0.00 | 1725086.03 | 0.00 | 0.982030E+09 | 0.956694E+09 | 0.00 | 0.45 |
December | 0.126570E+10 | 0.00 | 0.00 | 267681.30 | 0.00 | 0.220342E+10 | 0.223163E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.952618E+10 | 0.575978E+10 | 0.00 | 26728305.09 | 77551613.06 | 0.122237E+11 | 0.857891E+10 | 0.00 | 0.55 |
Minimum of Months | 6642331.72 | 0.00 | 0.00 | 16319.29 | 0.00 | 0.00 | 15560088.35 | 0.00 | 0.35 |
Maximum of Months | 0.151305E+10 | 0.218428E+10 | 0.00 | 8558681.94 | 25912185.79 | 0.329701E+10 | 0.319254E+10 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.580372E+09 | 0.00 | 0.00 | 2782.52 | 0.00 | 0.146358E+10 | 4970143.19 | 0.00 | 0.29 |
February | 0.624494E+09 | 0.00 | 0.00 | 26173.21 | 0.00 | 0.131915E+10 | 33628212.28 | 0.00 | 0.29 |
March | 0.126803E+10 | 0.00 | 0.00 | 595361.37 | 0.00 | 0.302534E+09 | 0.322776E+09 | 0.00 | 0.34 |
April | 0.888129E+09 | 891239.58 | 0.00 | 1735902.49 | 0.00 | 65775677.45 | 0.718094E+09 | 0.00 | 0.48 |
May | 0.503565E+09 | 20046087.67 | 0.00 | 3404310.78 | 0.00 | 0.00 | 0.127955E+10 | 0.00 | 0.80 |
June | 45674678.06 | 0.581364E+09 | 0.00 | 2251313.89 | 4402129.13 | 0.00 | 0.455427E+09 | 0.00 | 0.74 |
July | 1262197.79 | 0.152684E+10 | 0.00 | 204058.95 | 8370758.31 | 0.00 | 15419385.17 | 0.00 | 0.40 |
August | 24829496.67 | 0.139712E+10 | 0.00 | 2112563.85 | 8070172.28 | 0.00 | 0.203678E+09 | 0.00 | 0.74 |
September | 0.152259E+09 | 0.344449E+09 | 0.00 | 3350403.89 | 1973414.28 | 0.00 | 0.890261E+09 | 0.00 | 0.82 |
October | 0.373563E+09 | 35781437.91 | 0.00 | 3704892.16 | 0.00 | 0.00 | 0.141385E+10 | 0.00 | 0.79 |
November | 0.102268E+10 | 0.00 | 0.00 | 478776.21 | 0.00 | 0.276334E+09 | 0.276527E+09 | 0.00 | 0.32 |
December | 0.942319E+09 | 0.00 | 0.00 | 7116.25 | 0.00 | 0.834411E+09 | 14199855.21 | 0.00 | 0.27 |
Annual Sum or Average | 0.642718E+10 | 0.390649E+10 | 0.00 | 17873655.57 | 22816474.00 | 0.426179E+10 | 0.562838E+10 | 0.00 | 0.53 |
Minimum of Months | 1262197.79 | 0.00 | 0.00 | 2782.52 | 0.00 | 0.00 | 4970143.19 | 0.00 | 0.27 |
Maximum of Months | 0.126803E+10 | 0.152684E+10 | 0.00 | 3704892.16 | 8370758.31 | 0.146358E+10 | 0.141385E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.594847E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254573E+10 | 0.00 | 0.00 | 0.30 |
February | 0.746761E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229397E+10 | 0.00 | 0.00 | 0.30 |
March | 0.218558E+10 | 0.00 | 0.00 | 49264.44 | 0.00 | 0.650913E+09 | 44168518.71 | 0.00 | 0.32 |
April | 0.164380E+10 | 1245062.66 | 0.00 | 1252441.06 | 0.00 | 69919269.20 | 0.612953E+09 | 0.00 | 0.41 |
May | 0.692334E+09 | 27467023.24 | 0.00 | 4522801.96 | 0.00 | 0.00 | 0.181764E+10 | 0.00 | 0.70 |
June | 74382051.37 | 0.828895E+09 | 0.00 | 2899201.26 | 8295963.50 | 0.00 | 0.587984E+09 | 0.00 | 0.63 |
July | 1681774.53 | 0.224619E+10 | 0.00 | 273958.74 | 22264718.72 | 0.00 | 25478244.78 | 0.00 | 0.38 |
August | 43169493.04 | 0.178676E+10 | 0.00 | 2274292.75 | 18689128.65 | 0.00 | 0.244278E+09 | 0.00 | 0.56 |
September | 0.343012E+09 | 0.439180E+09 | 0.00 | 2760733.01 | 3852648.87 | 0.00 | 0.806109E+09 | 0.00 | 0.58 |
October | 0.103775E+10 | 35297058.06 | 0.00 | 2079783.05 | 111482.40 | 327848.09 | 0.793910E+09 | 0.00 | 0.49 |
November | 0.160881E+10 | 0.00 | 0.00 | 105738.78 | 0.00 | 0.684759E+09 | 0.142183E+09 | 0.00 | 0.32 |
December | 0.105399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178284E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.100261E+11 | 0.536503E+10 | 0.00 | 16218215.05 | 53213942.14 | 0.802846E+10 | 0.507470E+10 | 0.00 | 0.44 |
Minimum of Months | 1681774.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.218558E+10 | 0.224619E+10 | 0.00 | 4522801.96 | 22264718.72 | 0.254573E+10 | 0.181764E+10 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.504587E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117229E+10 | 0.00 | 0.00 | 0.25 |
February | 0.628165E+09 | 0.00 | 0.00 | 5636.36 | 0.00 | 0.939963E+09 | 9515534.99 | 0.00 | 0.24 |
March | 0.104000E+10 | 0.00 | 0.00 | 854798.70 | 0.00 | 0.246431E+09 | 0.465897E+09 | 0.00 | 0.31 |
April | 0.698678E+09 | 1578070.18 | 0.00 | 2642811.62 | 0.00 | 27314722.09 | 0.121188E+10 | 0.00 | 0.58 |
May | 0.300708E+09 | 25222520.57 | 0.00 | 5535602.94 | 0.00 | 0.00 | 0.212945E+10 | 0.00 | 1.04 |
June | 30331578.14 | 0.635992E+09 | 0.00 | 3256773.13 | 5278231.90 | 0.00 | 0.686149E+09 | 0.00 | 0.86 |
July | 793696.84 | 0.176866E+10 | 0.00 | 316710.30 | 14154734.09 | 0.00 | 35672399.98 | 0.00 | 0.49 |
August | 20384101.22 | 0.151932E+10 | 0.00 | 2644597.82 | 11826384.34 | 0.00 | 0.316584E+09 | 0.00 | 0.85 |
September | 0.138234E+09 | 0.337618E+09 | 0.00 | 3716796.30 | 2469009.78 | 0.00 | 0.992877E+09 | 0.00 | 0.82 |
October | 0.436478E+09 | 28277036.17 | 0.00 | 3292978.94 | 0.00 | 207460.58 | 0.120278E+10 | 0.00 | 0.71 |
November | 0.792063E+09 | 0.00 | 0.00 | 541910.42 | 0.00 | 0.282560E+09 | 0.325311E+09 | 0.00 | 0.29 |
December | 0.675868E+09 | 0.00 | 0.00 | 7442.39 | 0.00 | 0.809592E+09 | 4491175.99 | 0.00 | 0.23 |
Annual Sum or Average | 0.526629E+10 | 0.431667E+10 | 0.00 | 22816058.91 | 33728360.10 | 0.347836E+10 | 0.738061E+10 | 0.00 | 0.56 |
Minimum of Months | 793696.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
Maximum of Months | 0.104000E+10 | 0.176866E+10 | 0.00 | 5535602.94 | 14154734.09 | 0.117229E+10 | 0.212945E+10 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.118119E+10 | 0.00 | 0.00 | 1438423.08 | 0.00 | 0.139355E+10 | 0.969956E+09 | 0.00 | 0.34 |
February | 0.131085E+10 | 0.00 | 0.00 | 2048072.73 | 0.00 | 0.108642E+10 | 0.136490E+10 | 0.00 | 0.37 |
March | 0.172926E+10 | 0.00 | 0.00 | 4873815.26 | 0.00 | 0.302552E+09 | 0.242733E+10 | 0.00 | 0.54 |
April | 0.132627E+10 | 3279518.39 | 0.00 | 4832398.88 | 0.00 | 57641533.09 | 0.205938E+10 | 0.00 | 0.67 |
May | 0.655459E+09 | 35557456.05 | 0.00 | 6460818.82 | 0.00 | 0.00 | 0.255811E+10 | 0.00 | 0.91 |
June | 89647095.37 | 0.953200E+09 | 0.00 | 3393254.52 | 8307121.53 | 0.00 | 0.660811E+09 | 0.00 | 0.72 |
July | 1684036.51 | 0.260549E+10 | 0.00 | 304282.51 | 22372894.73 | 0.00 | 24845603.94 | 0.00 | 0.43 |
August | 42680479.12 | 0.240702E+10 | 0.00 | 3596800.08 | 18714265.44 | 0.00 | 0.340322E+09 | 0.00 | 0.79 |
September | 0.242550E+09 | 0.666272E+09 | 0.00 | 7640877.50 | 3902839.69 | 0.00 | 0.184643E+10 | 0.00 | 1.05 |
October | 0.519633E+09 | 98214092.24 | 0.00 | 10201848.26 | 0.00 | 0.00 | 0.385901E+10 | 0.00 | 1.19 |
November | 0.129685E+10 | 0.00 | 0.00 | 4032074.58 | 0.00 | 0.322204E+09 | 0.218146E+10 | 0.00 | 0.55 |
December | 0.136159E+10 | 0.00 | 0.00 | 2020308.26 | 0.00 | 0.941065E+09 | 0.123814E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.975766E+10 | 0.676903E+10 | 0.00 | 50842974.48 | 53297121.39 | 0.410343E+10 | 0.195307E+11 | 0.00 | 0.66 |
Minimum of Months | 1684036.51 | 0.00 | 0.00 | 304282.51 | 0.00 | 0.00 | 24845603.94 | 0.00 | 0.34 |
Maximum of Months | 0.172926E+10 | 0.260549E+10 | 0.00 | 10201848.26 | 22372894.73 | 0.139355E+10 | 0.385901E+10 | 0.00 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.560968E+09 | 0.00 | 0.00 | 34875.04 | 0.00 | 0.139619E+10 | 40329755.26 | 0.00 | 0.30 |
February | 0.656507E+09 | 0.00 | 0.00 | 121346.52 | 0.00 | 0.120116E+10 | 0.120768E+09 | 0.00 | 0.31 |
March | 0.124623E+10 | 0.00 | 0.00 | 1302271.24 | 0.00 | 0.271078E+09 | 0.723602E+09 | 0.00 | 0.41 |
April | 0.865978E+09 | 1076690.41 | 0.00 | 2817670.01 | 0.00 | 44933177.49 | 0.121931E+10 | 0.00 | 0.66 |
May | 0.346089E+09 | 28097515.72 | 0.00 | 5329512.69 | 0.00 | 0.00 | 0.198689E+10 | 0.00 | 1.06 |
June | 47614525.93 | 0.744902E+09 | 0.00 | 2754735.80 | 3874024.69 | 0.00 | 0.524302E+09 | 0.00 | 0.90 |
July | 1060623.91 | 0.195422E+10 | 0.00 | 219741.03 | 6347388.15 | 0.00 | 16535871.44 | 0.00 | 0.51 |
August | 26465223.80 | 0.171944E+10 | 0.00 | 2185860.88 | 6958255.03 | 0.00 | 0.200239E+09 | 0.00 | 0.85 |
September | 0.180302E+09 | 0.408285E+09 | 0.00 | 3362898.90 | 1875351.84 | 0.00 | 0.851535E+09 | 0.00 | 0.86 |
October | 0.509598E+09 | 47215906.86 | 0.00 | 3194277.44 | 0.00 | 206759.89 | 0.121917E+10 | 0.00 | 0.78 |
November | 0.975833E+09 | 0.00 | 0.00 | 488985.62 | 0.00 | 0.381914E+09 | 0.309574E+09 | 0.00 | 0.35 |
December | 0.787651E+09 | 0.00 | 0.00 | 32519.95 | 0.00 | 0.972355E+09 | 38747429.04 | 0.00 | 0.28 |
Annual Sum or Average | 0.620429E+10 | 0.490324E+10 | 0.00 | 21844695.11 | 19055019.70 | 0.426784E+10 | 0.725100E+10 | 0.00 | 0.61 |
Minimum of Months | 1060623.91 | 0.00 | 0.00 | 32519.95 | 0.00 | 0.00 | 16535871.44 | 0.00 | 0.28 |
Maximum of Months | 0.124623E+10 | 0.195422E+10 | 0.00 | 5329512.69 | 6958255.03 | 0.139619E+10 | 0.198689E+10 | 0.00 | 1.06 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.132404E+12 | 0.259510E+11 | 0.00 | 0.131233E+12 | 0.906258E+10 |
February | 0.205813E+12 | 0.240922E+11 | 0.00 | 0.137285E+12 | 0.901593E+10 |
March | 0.334412E+12 | 0.205797E+11 | 0.00 | 0.179249E+12 | 0.689735E+10 |
April | 0.353036E+12 | 0.133559E+11 | 0.00 | 0.191335E+12 | 0.185185E+11 |
May | 0.448153E+12 | 0.758242E+10 | 0.00 | 0.199191E+12 | 0.604486E+11 |
June | 0.431113E+12 | -784211501.8 | 0.00 | 0.438077E+11 | 0.204224E+12 |
July | 0.422955E+12 | -0.812598E+10 | 0.00 | -0.413439E+11 | 0.292428E+12 |
August | 0.409976E+12 | -0.488091E+10 | 0.00 | -629310568.4 | 0.294892E+12 |
September | 0.292253E+12 | 0.193242E+10 | 0.00 | 0.104213E+12 | 0.145944E+12 |
October | 0.286822E+12 | 0.101958E+11 | 0.00 | 0.204131E+12 | 0.627236E+11 |
November | 0.143653E+12 | 0.194278E+11 | 0.00 | 0.178404E+12 | 0.588633E+10 |
December | 0.106997E+12 | 0.226937E+11 | 0.00 | 0.148754E+12 | 0.698778E+10 |
Annual Sum or Average | 0.356759E+13 | 0.132020E+12 | 0.00 | 0.147563E+13 | 0.111703E+13 |
Minimum of Months | 0.106997E+12 | -0.812598E+10 | 0.00 | -0.413439E+11 | 0.588633E+10 |
Maximum of Months | 0.448153E+12 | 0.259510E+11 | 0.00 | 0.204131E+12 | 0.294892E+12 |