Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:31
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2023-10-16 08:32:01
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1649.17 | 331.01 | 331.01 |
Net Site Energy | 1649.17 | 331.01 | 331.01 |
Total Source Energy | 4885.75 | 980.64 | 980.64 |
Net Source Energy | 4885.75 | 980.64 | 980.64 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 101.70 | 37.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 318.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 232.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 51.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 66.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 124.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1487.30 | 161.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 101.70 | 37.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 318.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 232.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 51.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 66.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 124.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 101.70 | 37.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 318.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 232.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 51.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 66.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 124.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 97.60 | 32.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 298.52 | 32.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 97.60 | 32.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 298.52 | 32.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1487.303 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1487.303 | 100.00 |
Total On-Site and Utility Electric Sources | 1487.303 | 100.00 |
Total Electricity End Uses | 1487.303 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 143.00 |
Time Setpoint Not Met During Occupied Cooling | 149.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1911.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:31 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.6636 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.6636 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.6636 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 6.6636 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.6636 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 03-FEB-07:40 | - | - | - | - | - | - | - | - | - | - | 03-JAN-12:20 |
Heating | 186005.08 | 63466.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8334.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 243.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5564.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8845.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 226940.08 | 72312.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 186005.08 | 63466.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 8334.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 243.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 5564.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8845.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 322.07 | 40.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1007.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 736.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 37.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 209.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 134.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4710.29 | 175.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 64.64 | 8.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 202.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 42.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 27.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 945.43 | 35.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 64.64 | 8.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 202.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 42.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 27.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 945.43 | 35.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.82 | 0.265592 | 0.226000 | 0.637732 | 0.708246 | 0.500000 | 0.001435 |
CORE_MID VAV BOX COMPONENT | 2.05 | 0.365742 | 0.311000 | 0.637280 | 0.975313 | 0.500000 | 0.001042 |
CORE_TOP VAV BOX COMPONENT | 2.19 | 0.341642 | 0.290000 | 0.636168 | 0.911046 | 0.500000 | 0.001115 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.705395 | 0.223976 | 0.190000 | 0.134025 | 0.597270 | 0.500000 | 0.001701 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.676890 | 0.147767 | 0.126000 | 0.085288 | 0.394045 | 0.500000 | 0.002578 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.818315 | 0.193070 | 0.164000 | 0.134204 | 0.514852 | 0.500000 | 0.001973 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.750680 | 0.133233 | 0.113000 | 0.084827 | 0.355287 | 0.500000 | 0.002860 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.563293 | 0.280479 | 0.238000 | 0.134064 | 0.747943 | 0.500000 | 0.001358 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.577806 | 0.173106 | 0.147000 | 0.084937 | 0.461617 | 0.500000 | 0.002201 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.661627 | 0.238793 | 0.203000 | 0.134310 | 0.636780 | 0.500000 | 0.001596 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.599876 | 0.166727 | 0.142000 | 0.085182 | 0.444604 | 0.500000 | 0.002285 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.609331 | 0.259287 | 0.220000 | 0.134053 | 0.691432 | 0.500000 | 0.001469 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.650658 | 0.409931 | 0.500000 | 0.002478 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.721310 | 0.219034 | 0.186000 | 0.134164 | 0.584092 | 0.500000 | 0.001739 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.679935 | 0.147095 | 0.125000 | 0.084992 | 0.392254 | 0.500000 | 0.002590 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 20535.64 |
CORE_MID VAV BOX REHEAT COIL | 21482.45 |
CORE_TOP VAV BOX REHEAT COIL | 36903.82 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 17492.57 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11362.24 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 17355.76 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11444.89 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 13018.98 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 8524.18 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 12905.52 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8598.01 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 13819.16 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 9018.62 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 13692.71 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 9093.24 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.61 | 1.08 | 5.22 | 1.76 | 4.74 | 4.74 | 0.300000 | 0.371418 | 4.74 |
PACU_VAV_MID | 2.36 | 1.08 | 4.71 | 2.08 | 4.14 | 4.14 | 0.300000 | 0.503391 | 4.14 |
PACU_VAV_TOP | 2.57 | 1.07 | 5.14 | 2.94 | 4.86 | 4.86 | 0.300000 | 0.604842 | 4.86 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.74 |
PACU_VAV_MID_OA_CONTROLLER | 4.14 |
PACU_VAV_TOP_OA_CONTROLLER | 4.86 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.74 | 103126.21 | 0.744887 | 1.58 | 34371.96 | 0.744887 |
PACU_VAV_MID COOLING COIL | 4.14 | 93458.92 | 0.731587 | 1.38 | 31149.86 | 0.731587 |
PACU_VAV_TOP COOLING COIL | 4.86 | 104973.25 | 0.746479 | 1.62 | 34987.58 | 0.746479 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 17860.95 |
PACU_VAV_MID HEATING COIL | 18569.91 |
PACU_VAV_TOP HEATING COIL | 18430.14 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.74 |
PACU_VAV_MID FAN | 4.14 |
PACU_VAV_TOP FAN | 4.86 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 31.498 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9622 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9482 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.202 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8052 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8206 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5978 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27384127E-12 | 0.12865281E-14 | -0.83346422E-13 | 0.81323336E-16 |
43 | 6 | 0.26454352E-07 | 0.26406074E-09 | 0.60786733E-08 | -0.12333448E-12 |
44 | 5 | -0.17878666E-03 | 0.22931636E-05 | -0.92101048E-04 | 0.60153540E-08 |
45 | 4 | 0.27880517 | 0.11305828E-02 | 0.94889811E-01 | -0.31698392E-04 |
46 | 3 | -7.0018852 | 0.35426556E-01 | -2.2604600 | 0.27713709E-01 |
47 | 2 | 39.998753 | 0.12720283 | 14.942758 | -0.32362551 |
48 | 1 | -79.877006 | 0.57894353E-01 | -28.852534 | 1.0643678 |
49 | 0 | 46.824343 | 0.11744712E-02 | 16.298269 | |
50 | 7 | -0.27620064E-12 | 0.12774393E-14 | -0.83964131E-13 | 0.81942822E-16 |
51 | 6 | 0.26622461E-07 | 0.26074659E-09 | 0.61157793E-08 | -0.12423095E-12 |
52 | 5 | -0.17965003E-03 | 0.22617301E-05 | -0.92535175E-04 | 0.60516003E-08 |
53 | 4 | 0.27982997 | 0.11139309E-02 | 0.95257664E-01 | -0.31841476E-04 |
54 | 3 | -7.0222151 | 0.34872839E-01 | -2.2664901 | 0.27813240E-01 |
55 | 2 | 40.065841 | 0.12511414 | 14.967577 | -0.32437249 |
56 | 1 | -79.928458 | 0.56904129E-01 | -28.874810 | 1.0654641 |
57 | 0 | 46.824343 | 0.11535943E-02 | 16.297719 | |
58 | 7 | -0.27931930E-12 | 0.13886628E-14 | -0.87137092E-13 | 0.18759942E-15 |
59 | 6 | 0.23561308E-07 | 0.31712788E-09 | 0.54400317E-08 | -0.10799411E-12 |
60 | 5 | -0.16378969E-03 | 0.28142694E-05 | -0.84539011E-04 | 0.53904798E-08 |
61 | 4 | 0.26080053 | 0.14141629E-02 | 0.88437074E-01 | -0.29205444E-04 |
62 | 3 | -6.6442204 | 0.45062581E-01 | -2.1544048 | 0.25964059E-01 |
63 | 2 | 38.817908 | 0.16418932 | 14.505027 | -0.31048073 |
64 | 1 | -78.970774 | 0.75677137E-01 | -28.459322 | 1.0450580 |
65 | 0 | 46.824349 | 0.15543837E-02 | 16.308247 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.424_SHGC_EAST_0.249 | 35 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
2 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 36 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
3 | WINDOW_U_0.424_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
4 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 38 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9876E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0268E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.5034E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5358E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3121E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.3378E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9048E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9212E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1007 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5921E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1122 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9771E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6206E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0413E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1945E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1958E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9904E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0437E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.5066E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5545E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3151E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.3510E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9047E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9210E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4493E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0494E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2883E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8840E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1659E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5527E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7535E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7678E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7894E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8053E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6401E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.6517E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2824E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2868E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3903E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3960E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9303E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9681E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4705E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5013E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1767E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2002E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9047E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9210E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7223E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5417E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1120E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1824E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9625E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.3066E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1945E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1958E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9294E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9674E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4691E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4983E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1741E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1911E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9048E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9212E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8870E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3300E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3808E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0040E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7587E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9122E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7535E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7679E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7839E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8175E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4043E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4384E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4155E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4331E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3905E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3961E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1088 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.6949E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1209 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.1608E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.3084E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.9068E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6447E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.6997E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.2765E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9482E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.1295E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7901E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.0446E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4791E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6836E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7257E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1220E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0325E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4696E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6078E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3197E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2232E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6447E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6997E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.7613E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2607E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2800E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9497E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6778E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8660E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6836E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7257E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1088 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.6943E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1209 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.1601E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.3079E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.9063E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6443E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.6995E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.2764E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9479E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.1293E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7899E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.0443E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4788E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6832E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7255E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1221E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0324E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4696E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6077E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3196E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2231E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6443E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6995E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.7613E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2606E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2800E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9496E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6775E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8658E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6833E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7255E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 37759.22946 | 37759.22946 | 2.82183 | 2.82183 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 7560.75541 | 7560.75541 | 0.32958 | 0.42469 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 27454.32411 | 27454.32411 | 2.04913 | 2.04913 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 15189.73453 | 15189.73453 | 0.66714 | 0.66714 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 29109.76480 | 29109.76480 | 2.19368 | 2.19368 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 34.02000 | 1.44726E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 25988.62145 | 25988.62145 | 1.14604 | 1.14604 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9359.82383 | 9359.82383 | 0.70539 | 0.70539 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 34.11500 | 1.44727E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 12283.61932 | 12283.61932 | 0.54323 | 0.54323 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 8981.62775 | 8981.62775 | 0.67689 | 0.67689 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.50250 | 1.44680E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 7978.32338 | 7978.32338 | 0.35285 | 0.35285 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 10858.17424 | 10858.17424 | 0.81831 | 0.81831 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 12187.79268 | 12187.79268 | 0.53898 | 0.53898 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 9960.76876 | 9960.76876 | 0.75068 | 0.75068 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 8036.20942 | 8036.20942 | 0.35542 | 0.35542 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7474.53294 | 7474.53294 | 0.56329 | 0.56329 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 9149.01851 | 9149.01851 | 0.40430 | 0.40430 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 7667.15036 | 7667.15036 | 0.57781 | 0.57781 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.50250 | 1.44680E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 5989.67062 | 5989.67062 | 0.26472 | 0.26472 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 8779.37938 | 8779.37938 | 0.66163 | 0.66163 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 34.40000 | 1.44733E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 9069.56625 | 9069.56625 | 0.40078 | 0.40078 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 7960.01313 | 7960.01313 | 0.59988 | 0.59988 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.59500 | 1.44700E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 6041.37450 | 6041.37450 | 0.26701 | 0.26701 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8085.24615 | 8085.24615 | 0.60933 | 0.60933 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 9710.17197 | 9710.17197 | 0.42915 | 0.42915 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 8633.66034 | 8633.66034 | 0.65066 | 0.65066 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 31.02750 | 1.44671E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 6336.45044 | 6336.45044 | 0.28007 | 0.28007 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 9571.11501 | 9571.11501 | 0.72131 | 0.72131 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40000 | 1.44733E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 9621.61257 | 9621.61257 | 0.42523 | 0.42523 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9022.15726 | 9022.15726 | 0.67994 | 0.67994 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.75333 | 1.44703E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 6388.70946 | 6388.70946 | 0.28239 | 0.28239 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 73428.77 | 4.74264 | 4.74264 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 21029.91 | 1.76150 | 1.76150 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 65308.52 | 4.13988 | 4.13988 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 21086.15 | 2.08398 | 2.08398 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 74540.94 | 4.85503 | 4.85503 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 21148.13 | 2.93653 | 2.93653 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.82183 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26559 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22600 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63773 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70825 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.43453E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20535.64055 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.04913 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36574 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31100 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63728 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97531 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04172E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21482.44713 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.19368 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34164 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29000 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63617 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91105 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.11520E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 36903.82150 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70539 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22398 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13402 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59727 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.70107E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17492.57140 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67689 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14777 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12600 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52881E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39404 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.57839E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11362.24082 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81831 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19307 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16400 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13420 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51485 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.97338E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17355.75802 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75068 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13323 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11300 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48269E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35529 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.85966E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11444.88760 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.56329 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28048 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23800 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13406 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74794 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.35839E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13018.98343 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.57781 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17311 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14700 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.49374E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46162 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.20096E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8524.17852 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66163 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23879 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20300 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13431 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63678 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.59553E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12905.52219 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59988 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16673 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14200 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51823E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44460 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.28518E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8598.01412 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.60933 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25929 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13405 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69143 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.46941E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13819.16274 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65066 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40993 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.47847E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9018.61762 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72131 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21903 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18600 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13416 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58409 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.73945E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13692.71348 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67994 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14710 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12500 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.49919E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39225 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.59016E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9093.23688 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.61221 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07623 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.22443 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.76150 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.74264 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.74264 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.37142 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.35518 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07572 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.71037 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.08398 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.13988 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.13988 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.50339 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.57248 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07451 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.14496 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.93653 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.85503 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.85503 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.60484 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.74264 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.13988 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.85503 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.74264 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.74264 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 103126.20626 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74489 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.58072 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34371.96455 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74489 |
152 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 17860.95256 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.74264 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.13988 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.13988 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 93458.91614 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73159 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.37982 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31149.85675 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73159 |
161 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 18569.90828 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.13988 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.85503 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.85503 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 104973.24865 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74648 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.61818 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34987.58377 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74648 |
170 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 18430.14300 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.85503 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 102501.72 | 349750.39 | 11.45 | 2.92 | 3.28 | 3.46 | 3.61 | 9.97 | 11.20 | 11.80 | 12.31 | 5.2886 | 4.2154 | 2.8379 | 1.1722 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 93015.29 | 317381.35 | 11.53 | 2.94 | 3.30 | 3.48 | 3.62 | 10.02 | 11.27 | 11.89 | 12.36 | 4.6165 | 3.6734 | 2.4717 | 1.0359 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 104316.35 | 355942.18 | 11.44 | 2.92 | 3.28 | 3.45 | 3.60 | 9.96 | 11.18 | 11.79 | 12.30 | 5.4140 | 4.3130 | 2.9027 | 1.1995 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.0324759754E-003 | 5.9779042297E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.7568831629E-002 | 4.6843103608E-002 | Pass | Pass | 9.9577522454E-002 | 0.2909372962 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.8020504639E-003 | 5.7166495105E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.4232899974E-003 | 5.0227321494E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.5579513985E-003 | 6.9429132272E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 4.5953184273E-002 | 5.9046750416E-002 | Pass | Pass | 9.9740675515E-002 | 0.2967314251 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 7.2497411276E-002 | 0.1141427084 | Pass | Pass | 0.2523975400 | 0.8772046007 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 7.4667160392E-002 | 0.1162972667 | Pass | Pass | 0.2419499373 | 0.8278466602 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.9361621094E-002 | 0.1024117157 | Pass | Pass | 0.2265456613 | 0.7620484205 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 7.7506380063E-002 | 0.1236656566 | Pass | Pass | 0.2524495620 | 0.8804933139 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.3854116360E-002 | 2.2857886361E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 2.4811686370E-002 | 2.4454327623E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 2.5163898082E-002 | 2.5427547334E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 2.4832555207E-002 | 2.3291864142E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.8900945927E-002 | 2.6453192473E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.0214456714E-002 | 2.8375555430E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 3.0571936394E-002 | 2.9773970480E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.0240759126E-002 | 2.7081096595E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2911.21 | 49.79 | 0.00 | 1096.48 | 1576.96 | 5634.44 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.424_SHGC_NORTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.424_SHGC_EAST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.424_SHGC_WEST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.424_SHGC_EAST_0.249 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.424_SHGC_EAST_0.249 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.424_SHGC_WEST_0.249 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.424_SHGC_WEST_0.249 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.424_SHGC_NORTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.424_SHGC_EAST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.424_SHGC_WEST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.409 | 0.250 | 0.275 | |||||||||||||||||
North Total or Average | 195.79 | 2.409 | 0.250 | 0.275 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.409 | 0.250 | 0.275 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.16 | 0.0000 | Y | 6.78 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.82 | 0.0000 | Y | 4.24 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.63 | 0.0000 | Y | 6.65 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.98 | 0.0000 | Y | 4.27 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.07 | 0.0000 | Y | 6.76 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.76 | 0.0000 | Y | 4.23 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.59 | 0.0000 | Y | 6.64 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.91 | 0.0000 | Y | 4.25 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.16 | 0.0000 | Y | 6.78 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.82 | 0.0000 | Y | 4.24 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.63 | 0.0000 | Y | 6.65 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.98 | 0.0000 | Y | 4.27 |
Interior Lighting Total | 6.6636 | 4982.19 | 33199.39 | 232.55 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 41.77 | 41.77 | 4.42 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.77 | 62.77 | 4.80 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.77 | 47.60 | 42.13 | |
Exterior Lighting Total | 5686.19 | 51.35 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 103126.21 | 76817.41 | 26308.80 | 0.74 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 93458.92 | 68373.32 | 25085.60 | 0.73 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 104973.25 | 78360.29 | 26612.96 | 0.75 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 102501.7 | 2.92 | 9.97 | N/A | N/A | 11.45 | |
PACU_VAV_MID COOLING COIL | 93015.3 | 2.94 | 10.02 | N/A | N/A | 11.53 | |
PACU_VAV_TOP COOLING COIL | 104316.4 | 2.92 | 9.96 | N/A | N/A | 11.44 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 20535.64 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 21482.45 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 36903.82 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17492.57 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11362.24 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17355.76 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11444.89 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13018.98 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8524.18 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12905.52 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8598.01 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13819.16 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9018.62 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13692.71 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9093.24 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 17860.95 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 18569.91 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 18430.14 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.74 | 10381.70 | 2189.01 | 1.00 | 1.14 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.14 | 9062.24 | 2189.01 | 1.00 | 1.14 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.86 | 10627.72 | 2189.01 | 1.00 | 1.13 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 102501.72 | 2.92 | 9.97 | 11.45 | 5.2886 | 3.28 | 11.20 | 4.2154 | 3.46 | 11.80 | 2.8379 | 3.61 | 12.31 | 1.1722 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 93015.29 | 2.94 | 10.02 | 11.53 | 4.6165 | 3.30 | 11.27 | 3.6734 | 3.48 | 11.89 | 2.4717 | 3.62 | 12.36 | 1.0359 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 104316.35 | 2.92 | 9.96 | 11.44 | 5.4140 | 3.28 | 11.18 | 4.3130 | 3.45 | 11.79 | 2.9027 | 3.60 | 12.30 | 1.1995 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 37759.23 | 37759.23 | 38.39 | 2.822 | 2.822 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00882 | 27.37 | 0.01446 | 0.425 | 0.00 |
CORE_MID | 27454.32 | 27454.32 | 27.91 | 2.049 | 2.049 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 27.37 | 0.01446 | 0.425 | 0.00 |
CORE_TOP | 29109.76 | 29109.76 | 29.60 | 2.194 | 2.194 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00891 | 34.02 | 0.01447 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9359.82 | 9359.82 | 45.14 | 0.705 | 0.705 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00899 | 34.12 | 0.01447 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 8981.63 | 8981.63 | 68.43 | 0.677 | 0.677 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.00 | 24.00 | 0.00884 | 31.50 | 0.01447 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 10858.17 | 10858.17 | 52.37 | 0.818 | 0.818 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00893 | 34.40 | 0.01447 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 9960.77 | 9960.77 | 75.89 | 0.751 | 0.751 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00880 | 32.91 | 0.01447 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7474.53 | 7474.53 | 36.05 | 0.563 | 0.563 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00899 | 34.30 | 0.01447 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7667.15 | 7667.15 | 58.41 | 0.578 | 0.578 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.00 | 24.00 | 0.00881 | 31.50 | 0.01447 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 8779.38 | 8779.38 | 42.34 | 0.662 | 0.662 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00891 | 34.40 | 0.01447 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 7960.01 | 7960.01 | 60.65 | 0.600 | 0.600 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00880 | 32.59 | 0.01447 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8085.25 | 8085.25 | 39.00 | 0.609 | 0.609 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00902 | 34.30 | 0.01447 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8633.66 | 8633.66 | 65.77 | 0.651 | 0.651 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00882 | 31.03 | 0.01447 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9571.12 | 9571.12 | 46.16 | 0.721 | 0.721 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00895 | 34.40 | 0.01447 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9022.16 | 9022.16 | 68.74 | 0.680 | 0.680 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00881 | 32.75 | 0.01447 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 7560.76 | 7560.76 | 7.69 | 0.330 | 0.425 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 0.425 | 0.00 |
CORE_MID | 15189.73 | 15189.73 | 15.44 | 0.667 | 0.667 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 0.425 | 0.00 |
CORE_TOP | 25988.62 | 25988.62 | 26.42 | 1.146 | 1.146 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 12283.62 | 12283.62 | 59.24 | 0.543 | 0.543 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00756 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 7978.32 | 7978.32 | 60.78 | 0.353 | 0.353 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00755 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12187.79 | 12187.79 | 58.78 | 0.539 | 0.539 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00756 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 8036.21 | 8036.21 | 61.23 | 0.355 | 0.355 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00755 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 9149.02 | 9149.02 | 44.13 | 0.404 | 0.404 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00762 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 5989.67 | 5989.67 | 45.63 | 0.265 | 0.265 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9069.57 | 9069.57 | 43.74 | 0.401 | 0.401 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00762 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 6041.37 | 6041.37 | 46.03 | 0.267 | 0.267 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9710.17 | 9710.17 | 46.83 | 0.429 | 0.429 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00752 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 6336.45 | 6336.45 | 48.27 | 0.280 | 0.280 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9621.61 | 9621.61 | 46.41 | 0.425 | 0.425 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 6388.71 | 6388.71 | 48.67 | 0.282 | 0.282 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00752 | -6.30 | 0.00230 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.74 | 4.74 | 1.76 | 1.76 | 4.7426 | 1.7615 | 4.7426 | 0.3714 | 0.3000 |
PACU_VAV_MID | 4.14 | 4.14 | 2.08 | 2.08 | 4.1399 | 2.0840 | 4.1399 | 0.5034 | 0.3000 |
PACU_VAV_TOP | 4.86 | 4.86 | 2.94 | 2.94 | 4.8550 | 2.9365 | 4.8550 | 0.6048 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 20535.641 | 20535.641 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20535.64 | 13675.49 | 0.424691 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 7560.76 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 21482.447 | 21482.447 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21482.45 | 21482.45 | 0.667135 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 15189.73 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 36903.821 | 36903.821 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 36903.82 | 36903.82 | 1.146045 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 25988.62 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 17492.571 | 17492.571 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17492.57 | 17492.57 | 0.543230 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00755979 | 47.1579 | 12283.62 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 11362.241 | 11362.241 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11362.24 | 11362.24 | 0.352853 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00754995 | 47.0975 | 7978.32 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 17355.758 | 17355.758 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17355.76 | 17355.76 | 0.538982 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00755634 | 47.1367 | 12187.79 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 11444.888 | 11444.888 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11444.89 | 11444.89 | 0.355420 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00755314 | 47.1171 | 8036.21 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 13018.983 | 13018.983 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13018.98 | 13018.98 | 0.404303 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00762453 | 47.5552 | 9149.02 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 8524.179 | 8524.179 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8524.18 | 8524.18 | 0.264718 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00762908 | 47.5833 | 5989.67 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 12905.522 | 12905.522 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12905.52 | 12905.52 | 0.400780 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00761800 | 47.5151 | 9069.57 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 8598.014 | 8598.014 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8598.01 | 8598.01 | 0.267011 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00763480 | 47.6185 | 6041.37 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 13819.163 | 13819.163 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13819.16 | 13819.16 | 0.429153 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00751521 | 46.8828 | 9710.17 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 9018.618 | 9018.618 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9018.62 | 9018.62 | 0.280072 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00751047 | 46.8537 | 6336.45 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 13692.713 | 13692.713 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13692.71 | 13692.71 | 0.425226 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00750959 | 46.8481 | 9621.61 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 9093.237 | 9093.237 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9093.24 | 9093.24 | 0.282390 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00751526 | 46.8832 | 6388.71 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 103126.206 | 76817.409 | 4.742643 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 102892.89 | 82264.10 | 4.742643 | 26.10 | 17.97 | 0.01001111 | 10.96 | 10.96 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 20.1596 | 24.00 | 0.00888138 | 46.0706 | 62798.03 | 0.00 | 106336.96 | 76747.72 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 17860.953 | 17860.953 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17860.95 | 17860.95 | 1.422793 | 2.04 | 1.16 | 0.00390226 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 67.1988 | 19.37 | 0.00654263 | 45.2144 | 13682.98 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 93458.916 | 68373.321 | 4.139879 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 93920.34 | 73077.87 | 4.139879 | 26.39 | 18.25 | 0.01025150 | 10.96 | 10.96 | 0.00850000 | 34.30 | 0.01447309 | 23.52 | 23.0949 | 24.00 | 0.00897541 | 46.5520 | 54657.64 | 0.00 | 96368.69 | 68356.97 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 18569.908 | 18569.908 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18569.91 | 18569.91 | 1.241964 | -0.02 | -0.64 | 0.00349194 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 76.9829 | 17.83 | 0.00732430 | 55.6697 | 16197.63 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 104973.249 | 78360.291 | 4.855033 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 104893.71 | 83660.10 | 4.855033 | 26.00 | 17.94 | 0.01001900 | 10.96 | 10.96 | 0.00850000 | 34.12 | 0.01447274 | 23.47 | 19.6930 | 24.00 | 0.00892320 | 46.2851 | 64250.27 | 0.00 | 108241.51 | 78249.70 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 18430.143 | 18430.143 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18430.14 | 18430.14 | 1.456510 | 1.95 | 1.25 | 0.00400171 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 65.6432 | 17.41 | 0.00691287 | 53.9956 | 19089.31 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 20535.641 | 20535.641 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20535.64 | 13675.49 | 1.0000 | 0.49305639 | 0.424691 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20535.64 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.58 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 7560.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 21482.447 | 21482.447 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21482.45 | 21482.45 | 1.0000 | 0.77452865 | 0.667135 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21482.45 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 15189.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 36903.821 | 36903.821 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 36903.82 | 36903.82 | 1.0000 | 1.33053124 | 1.146045 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36903.82 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 25988.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 17492.571 | 17492.571 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17492.57 | 17492.57 | 1.0000 | 0.63067758 | 0.543230 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17492.57 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00755979 | 21.00 | 0.00755979 | 47.1579 | 12283.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 11362.241 | 11362.241 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11362.24 | 11362.24 | 1.0000 | 0.40965450 | 0.352853 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11362.24 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00754995 | 21.00 | 0.00754995 | 47.0975 | 7978.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 17355.758 | 17355.758 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17355.76 | 17355.76 | 1.0000 | 0.62574491 | 0.538982 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17355.76 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00755634 | 21.00 | 0.00755634 | 47.1367 | 12187.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 11444.888 | 11444.888 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11444.89 | 11444.89 | 1.0000 | 0.41263425 | 0.355420 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11444.89 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00755314 | 21.00 | 0.00755314 | 47.1171 | 8036.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 13018.983 | 13018.983 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13018.98 | 13018.98 | 1.0000 | 0.46938673 | 0.404303 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13018.98 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00762453 | 21.00 | 0.00762453 | 47.5552 | 9149.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8524.179 | 8524.179 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8524.18 | 8524.18 | 1.0000 | 0.30733093 | 0.264718 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8524.18 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00762908 | 21.00 | 0.00762908 | 47.5833 | 5989.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 12905.522 | 12905.522 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12905.52 | 12905.52 | 1.0000 | 0.46529600 | 0.400780 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12905.52 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00761800 | 21.00 | 0.00761800 | 47.5151 | 9069.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 8598.014 | 8598.014 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8598.01 | 8598.01 | 1.0000 | 0.30999300 | 0.267011 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8598.01 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00763480 | 21.00 | 0.00763480 | 47.6185 | 6041.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 13819.163 | 13819.163 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13819.16 | 13819.16 | 1.0000 | 0.49823642 | 0.429153 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13819.16 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00751521 | 21.00 | 0.00751521 | 46.8828 | 9710.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9018.618 | 9018.618 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9018.62 | 9018.62 | 1.0000 | 0.32515745 | 0.280072 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9018.62 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00751047 | 21.00 | 0.00751047 | 46.8537 | 6336.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 13692.713 | 13692.713 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13692.71 | 13692.71 | 1.0000 | 0.49367741 | 0.425226 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13692.71 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00750959 | 21.00 | 0.00750959 | 46.8481 | 9621.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9093.237 | 9093.237 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9093.24 | 9093.24 | 1.0000 | 0.32784778 | 0.282390 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9093.24 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00751526 | 21.00 | 0.00751526 | 46.8832 | 6388.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 103126.206 | 76817.409 | 4.742643 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4501 | 1004.8586 | 1.1610 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.742643 | 5.50609690 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 102892.89 | 82264.10 | 0.9977 | 5.50609690 | 4.742643 | 26.10 | 17.97 | 0.01001111 | 51749.2 | 10.96 | 10.96 | 0.00850000 | 32441.9 | -999.0 | -999.00 | -999.00 | -999.00 | 10381.697 | 92511.19 | 34.40 | 0.01447326 | 23.54 | 0.95610000 | 20.1596 | 24.00 | 0.00888138 | 24.00 | 0.00888138 | 46.0706 | 62798.03 | 0.00 | 106336.96 | 76747.72 | 5.28864769 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.46 | 12.45 | 0.00899104 | 35215.7 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17860.953 | 17860.953 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.742643 | 5.50609690 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17860.95 | 17860.95 | 1.0000 | 1.65182907 | 1.422793 | 2.04 | 1.16 | 0.00390226 | 11823.4 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17860.95 | -6.30 | 0.00229779 | -6.30 | 0.95610000 | 67.1988 | 19.12 | 0.00718928 | 19.37 | 0.00654263 | 45.2144 | 13682.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 93458.916 | 68373.321 | 4.139879 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8970 | 1004.8586 | 1.1610 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.139879 | 4.80630200 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | Sensible | 93920.34 | 73077.87 | 1.0049 | 4.80630200 | 4.139879 | 26.39 | 18.25 | 0.01025150 | 52659.7 | 10.96 | 10.96 | 0.00850000 | 32442.7 | -999.0 | -999.00 | -999.00 | -999.00 | 9062.240 | 84858.10 | 34.30 | 0.01447309 | 23.52 | 0.95610000 | 23.0949 | 24.00 | 0.00897541 | 24.00 | 0.00897541 | 46.5520 | 54657.64 | 0.00 | 96368.69 | 68356.97 | 4.61648940 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.17 | 12.14 | 0.00880563 | 34447.5 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 18569.908 | 18569.908 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.139879 | 4.80630200 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18569.91 | 18569.91 | 1.0000 | 1.44189060 | 1.241964 | -0.02 | -0.64 | 0.00349194 | 8716.3 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18569.91 | -6.30 | 0.00229779 | -6.30 | 0.95610000 | 76.9829 | 21.00 | 0.00748586 | 17.83 | 0.00732430 | 55.6697 | 16197.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 104973.249 | 78360.291 | 4.855033 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4648 | 1004.8586 | 1.1610 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.855033 | 5.63657934 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | Sensible | 104893.71 | 83660.10 | 0.9992 | 5.63657934 | 4.855033 | 26.00 | 17.94 | 0.01001900 | 51662.9 | 10.96 | 10.96 | 0.00850000 | 32441.9 | -999.0 | -999.00 | -999.00 | -999.00 | 10627.720 | 94265.99 | 34.12 | 0.01447274 | 23.47 | 0.95610000 | 19.6930 | 24.00 | 0.00892320 | 24.00 | 0.00892320 | 46.2851 | 64250.27 | 0.00 | 108241.51 | 78249.70 | 5.41397707 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.52 | 12.49 | 0.00901267 | 35329.4 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 18430.143 | 18430.143 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.855033 | 5.63657934 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18430.14 | 18430.14 | 1.0000 | 1.69097380 | 1.456510 | 1.95 | 1.25 | 0.00400171 | 11985.6 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18430.14 | -6.30 | 0.00229779 | -6.30 | 0.95610000 | 65.6432 | 17.72 | 0.00725728 | 17.41 | 0.00691287 | 53.9956 | 19089.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.74 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.14 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.86 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2851.67 | 1949.17 | 24.83 |
CORE_MID | 2518.00 | 2916.33 | 325.50 |
CORE_TOP | 2811.33 | 3205.83 | 745.33 |
PERIMETER_TOP_ZN_3 | 3491.00 | 3484.67 | 1468.83 |
PERIMETER_TOP_ZN_2 | 3555.83 | 3215.67 | 1328.50 |
PERIMETER_TOP_ZN_1 | 3338.67 | 2971.17 | 1052.00 |
PERIMETER_TOP_ZN_4 | 3557.50 | 3256.50 | 1357.67 |
PERIMETER_BOT_ZN_3 | 3051.50 | 3531.00 | 1071.33 |
PERIMETER_BOT_ZN_2 | 3202.17 | 3086.83 | 861.33 |
PERIMETER_BOT_ZN_1 | 3012.00 | 3273.17 | 908.00 |
PERIMETER_BOT_ZN_4 | 3210.17 | 3111.00 | 898.83 |
PERIMETER_MID_ZN_3 | 3287.50 | 3293.67 | 1123.17 |
PERIMETER_MID_ZN_2 | 2861.50 | 2664.00 | 947.17 |
PERIMETER_MID_ZN_1 | 3216.00 | 2703.67 | 731.50 |
PERIMETER_MID_ZN_4 | 3420.33 | 3065.67 | 1040.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4586.50 | 4185.67 | 1911.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 1.33 | 0.00 | 1.33 | 0.00 |
CORE_TOP | 2.17 | 0.00 | 1.67 | 0.00 |
PERIMETER_TOP_ZN_3 | 31.50 | 9.67 | 14.67 | 6.67 |
PERIMETER_TOP_ZN_2 | 19.00 | 39.50 | 3.33 | 35.00 |
PERIMETER_TOP_ZN_1 | 16.17 | 29.00 | 4.67 | 25.83 |
PERIMETER_TOP_ZN_4 | 18.83 | 40.17 | 5.33 | 22.50 |
PERIMETER_BOT_ZN_3 | 4.00 | 0.00 | 3.50 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.50 | 17.17 | 0.17 | 17.17 |
PERIMETER_BOT_ZN_1 | 131.33 | 58.33 | 131.00 | 58.17 |
PERIMETER_BOT_ZN_4 | 0.50 | 22.83 | 0.17 | 13.00 |
PERIMETER_MID_ZN_3 | 6.00 | 1.50 | 4.00 | 1.17 |
PERIMETER_MID_ZN_2 | 3.33 | 29.83 | 1.00 | 28.83 |
PERIMETER_MID_ZN_1 | 1.67 | 18.67 | 1.17 | 18.33 |
PERIMETER_MID_ZN_4 | 2.67 | 33.17 | 1.17 | 19.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 162.17 | 178.17 | 143.00 | 149.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 0.681 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.524 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.518 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.591 | 0.084 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.742 | 0.088 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 0.749 | 0.084 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.742 | 0.088 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.518 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.652 | 0.047 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 0.664 | 0.841 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.636 | 0.047 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.585 | 0.070 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.680 | 0.078 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 0.757 | 0.070 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.737 | 0.074 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.55 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.93 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 10714571.15 | 0.00 | 10714571.15 | 0.00 | 10714571.15 | 13393058.27 | 5190.90 | 150.47 | 3418.63 | 6.28 |
CORE_MID | 8288800.75 | 0.00 | 8288800.75 | 0.00 | 8288800.75 | 13393058.27 | 5874.37 | 316.13 | 2569.50 | 31.08 |
CORE_TOP | 8220352.41 | 0.00 | 8220352.41 | 0.00 | 8220352.41 | 13393058.27 | 5902.01 | 448.11 | 2409.88 | 111.00 |
PERIMETER_TOP_ZN_3 | 1978284.14 | 0.00 | 1978284.14 | 563886.35 | 2542170.50 | 2823374.22 | 4457.87 | 426.19 | 3875.94 | 111.00 |
PERIMETER_TOP_ZN_2 | 1567409.91 | 0.00 | 1567409.91 | 375921.98 | 1943331.88 | 1787429.43 | 4333.17 | 193.89 | 4232.94 | 111.00 |
PERIMETER_TOP_ZN_1 | 2498388.64 | 0.00 | 2498388.64 | 563886.35 | 3062275.00 | 2823374.22 | 4440.44 | 366.82 | 3952.74 | 111.00 |
PERIMETER_TOP_ZN_4 | 1568108.34 | 0.00 | 1568108.34 | 375921.98 | 1944030.31 | 1787312.18 | 4410.60 | 404.11 | 3945.29 | 111.00 |
PERIMETER_BOT_ZN_3 | 1726567.66 | 0.00 | 1726567.66 | 299816.06 | 2026383.72 | 2823374.22 | 5883.94 | 256.35 | 2619.71 | 6.28 |
PERIMETER_BOT_ZN_2 | 1371678.83 | 0.00 | 1371678.83 | 199876.17 | 1571555.01 | 1787429.43 | 4783.68 | 206.02 | 3770.30 | 6.28 |
PERIMETER_BOT_ZN_1 | 2209961.96 | 0.00 | 2209961.96 | 2951634.14 | 5161596.10 | 2823374.22 | 4974.41 | 169.45 | 3616.14 | 6.28 |
PERIMETER_BOT_ZN_4 | 1338054.58 | 0.00 | 1338054.58 | 199876.17 | 1537930.76 | 1787312.18 | 5015.58 | 207.72 | 3536.70 | 6.28 |
PERIMETER_MID_ZN_3 | 1951509.39 | 0.00 | 1951509.39 | 469392.62 | 2420902.01 | 2823374.22 | 4486.78 | 396.22 | 3877.00 | 31.08 |
PERIMETER_MID_ZN_2 | 1432090.69 | 0.00 | 1432090.69 | 312926.53 | 1745017.22 | 1601953.02 | 4306.00 | 155.06 | 4298.94 | 940.08 |
PERIMETER_MID_ZN_1 | 2518983.94 | 0.00 | 2518983.94 | 469392.62 | 2988376.56 | 2823374.22 | 4399.85 | 332.10 | 4028.05 | 31.08 |
PERIMETER_MID_ZN_4 | 1552309.41 | 0.00 | 1552309.41 | 312926.53 | 1865235.94 | 1787312.18 | 4405.89 | 292.02 | 4062.08 | 31.08 |
Total Facility | 48937071.81 | 0.00 | 48937071.81 | 7095457.52 | 56032529.32 | 67658168.57 | 6479.21 | 1019.78 | 4502.17 | 1026.35 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.5005 | 0.0000 | 0.5005 | 0.0000 | 0.5005 | 0.4247 | 2374.90 | 150.47 | 3417.63 |
CORE_MID | 0.3862 | 0.0000 | 0.3862 | 0.0000 | 0.3862 | 0.4247 | 3061.79 | 316.13 | 2565.08 |
CORE_TOP | 0.3820 | 0.0000 | 0.3820 | 0.0000 | 0.3820 | 0.4247 | 3091.18 | 448.11 | 2403.71 |
PERIMETER_TOP_ZN_3 | 0.0920 | 0.0000 | 0.0920 | 0.0131 | 0.1050 | 0.0895 | 1647.04 | 426.19 | 3869.77 |
PERIMETER_TOP_ZN_2 | 0.0729 | 0.0000 | 0.0729 | 0.0087 | 0.0817 | 0.0567 | 1522.60 | 193.89 | 4226.51 |
PERIMETER_TOP_ZN_1 | 0.1163 | 0.0000 | 0.1163 | 0.0131 | 0.1294 | 0.0895 | 1629.61 | 366.82 | 3946.57 |
PERIMETER_TOP_ZN_4 | 0.0729 | 0.0000 | 0.0729 | 0.0087 | 0.0817 | 0.0567 | 1600.11 | 404.09 | 3938.79 |
PERIMETER_BOT_ZN_3 | 0.0806 | 0.0000 | 0.0806 | 0.0069 | 0.0876 | 0.0895 | 3068.00 | 256.35 | 2618.64 |
PERIMETER_BOT_ZN_2 | 0.0641 | 0.0000 | 0.0641 | 0.0046 | 0.0687 | 0.0567 | 1967.88 | 206.02 | 3769.10 |
PERIMETER_BOT_ZN_1 | 0.1032 | 0.0000 | 0.1032 | 0.1309 | 0.2341 | 0.0895 | 2158.48 | 169.41 | 3615.12 |
PERIMETER_BOT_ZN_4 | 0.0625 | 0.0000 | 0.0625 | 0.0046 | 0.0671 | 0.0567 | 2199.76 | 207.70 | 3535.54 |
PERIMETER_MID_ZN_3 | 0.0910 | 0.0000 | 0.0910 | 0.0109 | 0.1018 | 0.0895 | 1674.51 | 396.15 | 3872.34 |
PERIMETER_MID_ZN_2 | 0.0668 | 0.0000 | 0.0668 | 0.0077 | 0.0745 | 0.0567 | 1494.14 | 155.06 | 3384.80 |
PERIMETER_MID_ZN_1 | 0.1175 | 0.0000 | 0.1175 | 0.0109 | 0.1284 | 0.0895 | 1587.46 | 332.06 | 4023.48 |
PERIMETER_MID_ZN_4 | 0.0724 | 0.0000 | 0.0724 | 0.0073 | 0.0796 | 0.0567 | 1593.93 | 292.01 | 4057.06 |
Total Facility | 2.2809 | 0.0000 | 2.2809 | 0.2274 | 2.5083 | 2.1513 | 3662.55 | 1019.56 | 4493.94 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 23400037.53 | 0.00 | 23400037.53 | 22614548.33 | 4233.44 | 3.04 | 4523.52 | 6.28 |
PACU_VAV_MID | 21220400.68 | 0.00 | 21220400.68 | 22429071.92 | 4222.99 | 1.75 | 4535.27 | 31.08 |
PACU_VAV_TOP | 21340052.84 | 0.00 | 21340052.84 | 22614548.33 | 4253.17 | 2.28 | 4504.55 | 110.91 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.0931 | 0.0000 | 1.0931 | 0.7171 | 1417.48 | 3.04 | 4522.48 |
PACU_VAV_MID | 0.9891 | 0.0000 | 0.9891 | 0.7084 | 1410.61 | 1.71 | 4530.67 |
PACU_VAV_TOP | 0.9922 | 0.0000 | 0.9922 | 0.7171 | 1442.34 | 2.28 | 4498.38 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 230.32 | 2112.18 | 0.00 | 0.00 | 0.00 | 2230.57 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 108.71 | 2083.25 | 0.00 | 0.00 | 0.00 | 2422.12 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 73.86 | 2153.42 | 0.00 | 0.00 | 0.00 | 2484.01 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.2349 | 1.8306 | 0.0000 | 0.0000 | 0.0000 | 1.0577 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.1966 | 1.5707 | 0.0000 | 0.0000 | 0.0000 | 1.0428 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.2016 | 1.5682 | 0.0000 | 0.0000 | 0.0000 | 1.0494 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 943 |
Defaulted Fields | 546 |
Fields with Defaults | 2221 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1487.30 | 12315.29 | 09-JUL-17:40 | 226940.08 | 02-JAN-07:10 |
Electricity:Building | 937.99 | 12146.72 | 23-APR-17:20 | 70843.15 | 30-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 291.77 | 4006.86 | 01-JAN-00:10 | 23121.21 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 937.99 | 12146.72 | 23-APR-17:20 | 70843.15 | 30-OCT-07:10 |
InteriorLights:Electricity | 232.55 | 905.38 | 23-APR-17:20 | 24978.45 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 232.55 | 905.38 | 23-APR-17:20 | 24978.45 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity | 232.55 | 905.38 | 23-APR-17:20 | 24978.45 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 232.55 | 905.38 | 23-APR-17:20 | 24978.45 | 30-OCT-07:10 |
Electricity:Zone:CORE_MID | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 31.12 | 413.68 | 12-MAR-17:10 | 2473.26 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.78 | 27.57 | 01-JAN-11:00 | 1038.01 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.78 | 27.57 | 01-JAN-11:00 | 1038.01 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.64 | 261.88 | 23-APR-17:10 | 1565.70 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.24 | 17.46 | 01-JAN-09:10 | 657.13 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.24 | 17.46 | 01-JAN-09:10 | 657.13 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 30.98 | 413.67 | 12-MAR-17:10 | 2473.25 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.65 | 27.57 | 01-JAN-09:10 | 1038.01 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.65 | 27.57 | 01-JAN-09:10 | 1038.01 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.67 | 261.87 | 26-FEB-18:10 | 1565.65 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.27 | 17.46 | 01-JAN-10:50 | 657.08 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.27 | 17.46 | 01-JAN-10:50 | 657.08 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 31.09 | 413.68 | 12-MAR-17:10 | 2473.16 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.76 | 27.57 | 01-JAN-10:50 | 1037.91 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.76 | 27.57 | 01-JAN-10:50 | 1037.91 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.63 | 261.88 | 23-APR-17:10 | 1565.65 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.23 | 17.46 | 01-JAN-09:00 | 657.08 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.23 | 17.46 | 01-JAN-09:00 | 657.08 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 30.97 | 413.67 | 12-MAR-17:10 | 2473.15 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.64 | 27.57 | 01-JAN-09:10 | 1037.91 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.64 | 27.57 | 01-JAN-09:10 | 1037.91 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.66 | 261.87 | 20-FEB-18:10 | 1565.60 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.25 | 17.46 | 01-JAN-10:40 | 657.03 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.25 | 17.46 | 01-JAN-10:40 | 657.03 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 31.12 | 413.68 | 12-MAR-17:10 | 2473.26 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.78 | 27.57 | 01-JAN-11:00 | 1038.01 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.78 | 27.57 | 01-JAN-11:00 | 1038.01 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.64 | 261.88 | 23-APR-17:10 | 1565.70 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.24 | 17.46 | 01-JAN-09:10 | 657.13 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.24 | 17.46 | 01-JAN-09:10 | 657.13 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 30.98 | 413.67 | 12-MAR-17:10 | 2473.25 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.65 | 27.57 | 01-JAN-09:10 | 1038.01 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.65 | 27.57 | 01-JAN-09:10 | 1038.01 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.67 | 261.87 | 26-FEB-18:10 | 1565.65 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.27 | 17.46 | 01-JAN-10:50 | 657.08 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.27 | 17.46 | 01-JAN-10:50 | 657.08 | 30-OCT-07:10 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 497.82 | 168.57 | 09-JUL-17:40 | 191813.53 | 02-JAN-07:10 |
ExteriorEquipment:Electricity | 11.69 | 168.34 | 01-JAN-00:10 | 840.12 | 30-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 11.69 | 168.34 | 01-JAN-00:10 | 840.12 | 30-OCT-07:20 |
ElectricityPurchased:Facility | 1487.30 | 12315.29 | 09-JUL-17:40 | 226940.08 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 1487.30 | 12315.29 | 09-JUL-17:40 | 226940.08 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1487.30 | 12315.29 | 09-JUL-17:40 | 226940.08 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1487.30 | 12315.29 | 09-JUL-17:40 | 226940.08 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1487.30 | 12315.29 | 09-JUL-17:40 | 226940.08 | 02-JAN-07:10 |
ElectricityNet:Plant | 1487.30 | 12315.29 | 09-JUL-17:40 | 226940.08 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 1487.30 | 12315.29 | 09-JUL-17:40 | 226940.08 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1487.30 | 12315.29 | 09-JUL-17:40 | 226940.08 | 02-JAN-07:10 |
Heating:Electricity | 101.70 | 0.00 | 01-JAN-00:40 | 186005.08 | 02-JAN-07:10 |
General:Heating:Electricity | 101.70 | 0.00 | 01-JAN-00:40 | 186005.08 | 02-JAN-07:10 |
Fans:Electricity | 66.28 | 0.00 | 01-JAN-00:40 | 14092.49 | 02-AUG-15:50 |
General:Fans:Electricity | 66.28 | 0.00 | 01-JAN-00:40 | 14092.49 | 02-AUG-15:50 |
ExteriorLights:Electricity | 51.35 | 0.00 | 01-JAN-07:50 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 51.35 | 0.00 | 01-JAN-07:50 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 318.15 | 0.00 | 01-JAN-00:10 | 75463.76 | 07-JUL-16:00 |
General:Cooling:Electricity | 318.15 | 0.00 | 01-JAN-00:10 | 75463.76 | 07-JUL-16:00 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-07:10 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-07:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-07:10 |
WIRED_LTG_ELECTRICITY | 6.53 | 0.00 | 01-JAN-00:10 | 701.89 | 30-OCT-07:20 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 161.86 | 1886.44 | 06-JAN-05:10 | 72312.24 | 03-FEB-07:40 |
NaturalGas:HVAC | 37.44 | 0.00 | 01-JAN-00:10 | 63863.79 | 03-FEB-07:30 |
Heating:NaturalGas | 37.44 | 0.00 | 01-JAN-00:10 | 63863.79 | 03-FEB-07:30 |
General:Heating:NaturalGas | 37.44 | 0.00 | 01-JAN-00:10 | 63863.79 | 03-FEB-07:30 |
NaturalGas:Plant | 124.42 | 1886.44 | 02-JAN-08:10 | 10016.76 | 06-FEB-12:10 |
WaterSystems:NaturalGas | 124.42 | 1886.44 | 02-JAN-08:10 | 10016.76 | 06-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 124.42 | 1886.44 | 02-JAN-08:10 | 10016.76 | 06-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2584.98 | 0.00 | 01-JAN-00:40 | 405824.82 | 07-JUL-16:00 |
EnergyTransfer:Building | 1157.79 | 0.00 | 01-JAN-00:40 | 155795.31 | 02-AUG-15:50 |
EnergyTransfer:Zone:CORE_BOTTOM | 237.64 | 0.00 | 01-JAN-00:10 | 26943.71 | 21-AUG-08:00 |
Heating:EnergyTransfer | 71.02 | 0.00 | 01-JAN-00:40 | 148832.13 | 02-JAN-06:30 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.03 | 0.00 | 01-JAN-00:10 | 6383.50 | 02-JAN-07:10 |
General:Heating:EnergyTransfer | 71.02 | 0.00 | 01-JAN-00:40 | 148832.13 | 02-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.03 | 0.00 | 01-JAN-00:10 | 6383.50 | 02-JAN-07:10 |
Cooling:EnergyTransfer | 1086.77 | 0.00 | 01-JAN-00:40 | 155795.31 | 02-AUG-15:50 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 237.61 | 0.00 | 01-JAN-00:10 | 26943.71 | 21-AUG-08:00 |
General:Cooling:EnergyTransfer | 1086.77 | 0.00 | 01-JAN-00:40 | 155795.31 | 02-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 237.61 | 0.00 | 01-JAN-00:10 | 26943.71 | 21-AUG-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 45.45 | 0.00 | 01-JAN-00:40 | 13169.06 | 13-FEB-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 11.66 | 0.00 | 01-JAN-00:40 | 13169.06 | 13-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 11.66 | 0.00 | 01-JAN-00:40 | 13169.06 | 13-FEB-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 33.79 | 0.00 | 01-JAN-00:10 | 10247.23 | 01-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 33.79 | 0.00 | 01-JAN-00:10 | 10247.23 | 01-AUG-14:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 22.95 | 0.00 | 01-JAN-00:10 | 7237.20 | 09-JAN-07:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.82 | 0.00 | 01-JAN-00:10 | 7237.20 | 09-JAN-07:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.82 | 0.00 | 01-JAN-00:10 | 7237.20 | 09-JAN-07:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 18.13 | 0.00 | 01-JAN-00:10 | 4385.71 | 10-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 18.13 | 0.00 | 01-JAN-00:10 | 4385.71 | 10-JUL-15:30 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 25.19 | 0.00 | 01-JAN-00:10 | 4635.49 | 10-JUL-15:40 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 3.47 | 0.00 | 01-JAN-00:10 | 4240.33 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 3.47 | 0.00 | 01-JAN-00:10 | 4240.33 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 21.72 | 0.00 | 01-JAN-00:10 | 4635.49 | 10-JUL-15:40 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 21.72 | 0.00 | 01-JAN-00:10 | 4635.49 | 10-JUL-15:40 |
EnergyTransfer:Zone:CORE_MID | 166.26 | 0.00 | 01-JAN-00:10 | 18428.36 | 21-AUG-07:30 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.70 | 0.00 | 01-JAN-00:10 | 14697.47 | 02-JAN-07:50 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.70 | 0.00 | 01-JAN-00:10 | 14697.47 | 02-JAN-07:50 |
Cooling:EnergyTransfer:Zone:CORE_MID | 165.56 | 0.00 | 01-JAN-00:10 | 18428.36 | 21-AUG-07:30 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 165.56 | 0.00 | 01-JAN-00:10 | 18428.36 | 21-AUG-07:30 |
EnergyTransfer:Zone:CORE_TOP | 164.10 | 0.00 | 01-JAN-00:40 | 28551.68 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 4.07 | 0.00 | 01-JAN-00:10 | 28551.68 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 4.07 | 0.00 | 01-JAN-00:10 | 28551.68 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 160.03 | 0.00 | 01-JAN-00:40 | 19988.19 | 10-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 160.03 | 0.00 | 01-JAN-00:40 | 19988.19 | 10-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 45.96 | 0.00 | 01-JAN-00:40 | 9551.82 | 13-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 8.08 | 0.00 | 01-JAN-00:40 | 9551.82 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 8.08 | 0.00 | 01-JAN-00:40 | 9551.82 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 37.88 | 0.00 | 01-JAN-00:20 | 7172.03 | 14-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 37.88 | 0.00 | 01-JAN-00:20 | 7172.03 | 14-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 37.48 | 0.00 | 01-JAN-00:40 | 8086.54 | 07-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.11 | 0.00 | 01-JAN-00:40 | 7906.91 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.11 | 0.00 | 01-JAN-00:40 | 7906.91 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.36 | 0.00 | 01-JAN-00:20 | 8086.54 | 07-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.36 | 0.00 | 01-JAN-00:20 | 8086.54 | 07-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 56.02 | 0.00 | 01-JAN-00:40 | 10912.84 | 10-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.00 | 0.00 | 01-JAN-00:40 | 10068.33 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.00 | 0.00 | 01-JAN-00:40 | 10068.33 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 51.03 | 0.00 | 01-JAN-00:20 | 10912.84 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 51.03 | 0.00 | 01-JAN-00:20 | 10912.84 | 10-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 37.41 | 0.00 | 01-JAN-00:40 | 8159.08 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.73 | 0.00 | 01-JAN-00:40 | 7827.06 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.73 | 0.00 | 01-JAN-00:40 | 7827.06 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 32.68 | 0.00 | 01-JAN-00:20 | 8159.08 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 32.68 | 0.00 | 01-JAN-00:20 | 8159.08 | 02-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 37.70 | 0.00 | 01-JAN-00:10 | 7026.25 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 3.26 | 0.00 | 01-JAN-00:10 | 7026.25 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 3.26 | 0.00 | 01-JAN-00:10 | 7026.25 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 34.43 | 0.00 | 01-JAN-00:10 | 5878.58 | 10-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 34.43 | 0.00 | 01-JAN-00:10 | 5878.58 | 10-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 32.54 | 0.00 | 01-JAN-00:10 | 6687.22 | 07-JUL-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.50 | 0.00 | 01-JAN-00:10 | 5338.39 | 13-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.50 | 0.00 | 01-JAN-00:10 | 5338.39 | 13-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 31.04 | 0.00 | 01-JAN-00:10 | 6687.22 | 07-JUL-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 31.04 | 0.00 | 01-JAN-00:10 | 6687.22 | 07-JUL-09:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 54.62 | 0.00 | 01-JAN-00:10 | 10212.52 | 03-FEB-07:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 8.50 | 0.00 | 01-JAN-00:10 | 10212.52 | 03-FEB-07:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 8.50 | 0.00 | 01-JAN-00:10 | 10212.52 | 03-FEB-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 46.13 | 0.00 | 01-JAN-00:10 | 10156.25 | 18-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 46.13 | 0.00 | 01-JAN-00:10 | 10156.25 | 18-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 31.41 | 0.00 | 01-JAN-00:10 | 6618.40 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.63 | 0.00 | 01-JAN-00:10 | 5280.01 | 09-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.63 | 0.00 | 01-JAN-00:10 | 5280.01 | 09-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 29.79 | 0.00 | 01-JAN-00:10 | 6618.40 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 29.79 | 0.00 | 01-JAN-00:10 | 6618.40 | 02-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 41.71 | 0.00 | 01-JAN-00:10 | 7553.40 | 13-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 3.60 | 0.00 | 01-JAN-00:10 | 7553.40 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 3.60 | 0.00 | 01-JAN-00:10 | 7553.40 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 38.11 | 0.00 | 01-JAN-00:10 | 6402.95 | 10-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 38.11 | 0.00 | 01-JAN-00:10 | 6402.95 | 10-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 33.27 | 0.00 | 01-JAN-00:10 | 7887.04 | 07-JUL-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.81 | 0.00 | 01-JAN-00:10 | 5896.92 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.81 | 0.00 | 01-JAN-00:10 | 5896.92 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 31.46 | 0.00 | 01-JAN-00:10 | 7887.04 | 07-JUL-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 31.46 | 0.00 | 01-JAN-00:10 | 7887.04 | 07-JUL-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 53.58 | 0.00 | 01-JAN-00:10 | 9874.84 | 10-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.00 | 0.00 | 01-JAN-00:10 | 8454.45 | 02-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.00 | 0.00 | 01-JAN-00:10 | 8454.45 | 02-JAN-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 51.58 | 0.00 | 01-JAN-00:10 | 9874.84 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 51.58 | 0.00 | 01-JAN-00:10 | 9874.84 | 10-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 34.52 | 0.00 | 01-JAN-00:10 | 7533.57 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 2.05 | 0.00 | 01-JAN-00:10 | 5805.22 | 02-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 2.05 | 0.00 | 01-JAN-00:10 | 5805.22 | 02-JAN-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.47 | 0.00 | 01-JAN-00:10 | 7533.57 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.47 | 0.00 | 01-JAN-00:10 | 7533.57 | 02-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 44.21 | 0.00 | 01-JAN-00:10 | 5837.87 | 03-FEB-12:10 |
PlantLoopHeatingDemand:Plant | 44.21 | 0.00 | 01-JAN-00:10 | 5837.87 | 03-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 44.21 | 0.00 | 01-JAN-00:10 | 5837.87 | 03-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 44.21 | 0.00 | 01-JAN-00:10 | 5837.87 | 03-FEB-12:10 |
EnergyTransfer:HVAC | 1382.97 | 0.00 | 01-JAN-00:40 | 249486.68 | 07-JUL-16:00 |
HeatingCoils:EnergyTransfer | 131.65 | 0.00 | 01-JAN-00:40 | 203476.63 | 13-FEB-07:10 |
CoolingCoils:EnergyTransfer | 1251.32 | 0.00 | 01-JAN-00:10 | 249486.68 | 07-JUL-16:00 |
EnergyTransfer:Plant | 44.21 | 0.00 | 01-JAN-00:10 | 5837.87 | 03-FEB-12:10 |
WaterSystems:EnergyTransfer | 44.21 | 0.00 | 01-JAN-00:10 | 5837.87 | 03-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 44.21 | 0.00 | 01-JAN-00:10 | 5837.87 | 03-FEB-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.028 | -237.609 | 0.000 | 0.000 | 32.982 | 55.599 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -87.168 |
CORE_MID | 0.000 | 0.000 | 0.695 | -165.561 | 0.000 | 0.000 | 34.155 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -40.313 |
CORE_TOP | 0.000 | 0.000 | 4.068 | -160.031 | 0.000 | 0.000 | 34.737 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -49.798 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 8.083 | -37.875 | 0.000 | 0.000 | 7.448 | 6.784 | 24.333 | 18.089 | 0.000 | 0.287 | 2.343 | 0.000 | -24.343 | 0.000 | -5.149 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 4.114 | -33.360 | 0.000 | 0.000 | 4.638 | 4.239 | 15.404 | 29.163 | 0.000 | 0.179 | 0.000 | 0.000 | -15.074 | 0.000 | -3.526 | -5.775 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 4.997 | -51.025 | 0.000 | 0.000 | 7.254 | 6.648 | 24.332 | 51.396 | 0.000 | 0.269 | 0.000 | 0.000 | -22.882 | 0.000 | -5.489 | -15.500 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 4.728 | -32.679 | 0.000 | 0.000 | 4.677 | 4.265 | 15.403 | 29.417 | 0.000 | 0.177 | 0.001 | 0.000 | -16.118 | 0.000 | -3.554 | -6.316 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 3.263 | -34.433 | 0.000 | 0.000 | 7.410 | 6.762 | 24.333 | 18.456 | 0.000 | 0.168 | 2.452 | 0.000 | -25.483 | 0.000 | -2.928 | -0.002 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 1.498 | -31.037 | 0.000 | 0.000 | 4.594 | 4.230 | 15.404 | 29.327 | 0.000 | 0.100 | 0.001 | 0.000 | -16.069 | 0.000 | -2.036 | -6.012 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 8.498 | -46.125 | 0.000 | 0.000 | 7.325 | 6.636 | 24.332 | 51.944 | 0.000 | 4.009 | 0.000 | 0.000 | -24.374 | 0.000 | -22.079 | -10.166 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 1.626 | -29.785 | 0.000 | 0.000 | 4.629 | 4.254 | 15.403 | 29.678 | 0.000 | 0.097 | 0.002 | 0.000 | -17.205 | 0.000 | -2.051 | -6.648 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 3.599 | -38.105 | 0.000 | 0.000 | 7.373 | 6.784 | 24.333 | 17.980 | 0.000 | 0.247 | 8.192 | 0.000 | -25.829 | 0.000 | -4.575 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.815 | -31.455 | 0.000 | 0.000 | 3.388 | 4.239 | 15.404 | 28.922 | 0.000 | 0.150 | 0.000 | 0.000 | -15.971 | 0.000 | -3.140 | -3.351 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 1.999 | -51.580 | 0.000 | 0.000 | 7.177 | 6.648 | 24.332 | 51.198 | 0.000 | 0.231 | 0.000 | 0.000 | -24.222 | 0.000 | -4.869 | -10.915 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 2.049 | -32.470 | 0.000 | 0.000 | 4.629 | 4.265 | 15.403 | 29.354 | 0.000 | 0.149 | 0.000 | 0.000 | -17.082 | 0.000 | -3.152 | -3.146 |
TOPFLOOR_PLENUM | 11.664 | -33.786 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.270 | 29.711 | 0.000 | 0.000 | 0.000 | -7.859 | -0.003 |
MIDFLOOR_PLENUM | 4.819 | -18.126 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.350 | 20.952 | 0.000 | 0.000 | 0.000 | -7.995 | -0.000 |
FIRSTFLOOR_PLENUM | 3.471 | -21.721 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.269 | 24.563 | 0.000 | 0.000 | 0.000 | -6.582 | -0.000 |
Total Facility | 19.953 | -73.634 | 51.063 | -1013.128 | 0.000 | 0.000 | 172.415 | 232.552 | 705.434 | 384.923 | 0.000 | 6.953 | 88.220 | 0.000 | -244.652 | 0.000 | -84.984 | -245.115 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 07-JUL-04:03 | 0.00 | 0.00 | 0.00 | -41098.61 | 0.00 | 0.00 | 0.00 | 211.73 | 4405.64 | 0.00 | 0.00 | 0.00 | 36481.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 07-JUL-04:03 | 0.00 | 0.00 | 0.00 | -29249.31 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 26595.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 14-AUG-04:03 | 0.00 | 0.00 | 0.00 | -31795.21 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 29141.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-13:43 | 0.00 | 0.00 | 0.00 | -11544.14 | 0.00 | 0.00 | 26.87 | 27.57 | 478.42 | 3442.28 | 0.00 | 146.28 | 7422.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 27-AUG-09:22 | 0.00 | 0.00 | 0.00 | -11968.94 | 0.00 | 0.00 | 15.01 | 17.46 | 302.86 | 7780.15 | 0.00 | 0.00 | 3860.88 | 0.00 | -0.00 | 0.00 | -7.42 | 0.00 |
PERIMETER_TOP_ZN_1 | 24-SEP-13:13 | 0.00 | 0.00 | 0.00 | -14061.66 | 0.00 | 0.00 | 25.34 | 27.57 | 478.41 | 8074.46 | 0.00 | 45.56 | 5410.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 13-AUG-17:02 | 0.00 | 0.00 | 0.00 | -12914.76 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 7176.93 | 0.00 | 69.81 | 5406.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 16-JUL-15:23 | 0.00 | 0.00 | 0.00 | -6915.98 | 0.00 | 0.00 | 29.43 | 27.57 | 478.42 | 3292.75 | 0.00 | 101.16 | 2986.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 27-AUG-09:52 | 0.00 | 0.00 | 0.00 | -10102.46 | 0.00 | 0.00 | 16.12 | 17.46 | 302.86 | 7127.85 | 0.00 | 0.00 | 2639.92 | 0.00 | -0.00 | 0.00 | -1.74 | 0.00 |
PERIMETER_BOT_ZN_1 | 09-OCT-14:32 | 0.00 | 0.00 | 0.00 | -11536.29 | 0.00 | 0.00 | 25.51 | 27.57 | 478.41 | 8506.64 | 0.00 | 0.25 | 2497.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 27-AUG-15:52 | 0.00 | 0.00 | 0.00 | -10372.55 | 0.00 | 0.00 | 15.95 | 17.46 | 302.86 | 6843.74 | 0.00 | 57.25 | 3135.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-13:43 | 0.00 | 0.00 | 0.00 | -9776.19 | 0.00 | 0.00 | 28.12 | 27.57 | 478.42 | 3508.71 | 0.00 | 126.72 | 5606.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 27-AUG-09:52 | 0.00 | 0.00 | 0.00 | -11686.44 | 0.00 | 0.00 | 14.92 | 17.46 | 302.86 | 7045.44 | 0.00 | 0.00 | 4311.78 | 0.00 | -0.00 | 0.00 | -6.02 | 0.00 |
PERIMETER_MID_ZN_1 | 09-OCT-14:32 | 0.00 | 0.00 | 0.00 | -12470.69 | 0.00 | 0.00 | 25.47 | 27.57 | 478.41 | 8488.46 | 0.00 | 2.36 | 3448.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 23-JUL-17:52 | 0.00 | 0.00 | 0.00 | -12121.57 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 5661.14 | 0.00 | 19.23 | 6179.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 01-AUG-14:00 | 0.00 | -10247.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.68 | 10157.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 17-JUL-06:03 | 0.00 | -4439.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4458.51 | 0.00 | -0.00 | 0.00 | -18.84 | 0.00 |
FIRSTFLOOR_PLENUM | 10-JUL-15:40 | 0.00 | -4635.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.27 | 4538.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-05:12 | 0.00 | -2288.15 | 0.00 | -173023.09 | 0.00 | 0.00 | 1672.62 | 2778.13 | 17291.51 | 0.00 | 0.00 | 0.00 | 160199.83 | 0.00 | -6268.57 | 0.00 | -362.27 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 13-FEB-07:02 | 0.00 | 0.00 | 13906.98 | 0.00 | 0.00 | 0.00 | 895.18 | 1645.36 | 8796.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25244.32 |
CORE_MID | 09-JAN-05:01 | 0.00 | 0.00 | 16200.94 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18854.73 |
CORE_TOP | 02-JAN-06:11 | 0.00 | 0.00 | 31118.71 | 0.00 | 0.00 | 0.00 | 536.88 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -35229.94 |
PERIMETER_TOP_ZN_3 | 12-FEB-07:52 | 0.00 | 0.00 | 10752.20 | 0.00 | 0.00 | 0.00 | 60.06 | 48.28 | 478.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3401.72 | 0.00 | -1531.34 | -6405.90 |
PERIMETER_TOP_ZN_2 | 12-FEB-05:12 | 0.00 | 0.00 | 10117.64 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2388.44 | 0.00 | -1293.77 | -6708.11 |
PERIMETER_TOP_ZN_1 | 12-FEB-05:12 | 0.00 | 0.00 | 12277.66 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3606.33 | 0.00 | -1933.55 | -7168.52 |
PERIMETER_TOP_ZN_4 | 12-FEB-07:52 | 0.00 | 0.00 | 10786.31 | 0.00 | 0.00 | 0.00 | 38.08 | 30.80 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2267.81 | 0.00 | -1038.18 | -7852.05 |
PERIMETER_BOT_ZN_3 | 13-FEB-05:01 | 0.00 | 0.00 | 8043.21 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2990.30 | 0.00 | -792.45 | -4819.90 |
PERIMETER_BOT_ZN_2 | 13-FEB-05:01 | 0.00 | 0.00 | 7450.09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2024.52 | 0.00 | -539.50 | -5240.22 |
PERIMETER_BOT_ZN_1 | 03-FEB-07:10 | 0.00 | 0.00 | 10356.76 | 0.00 | 0.00 | 0.00 | 193.30 | 346.86 | 637.88 | 0.00 | 0.00 | 0.00 | 12146.41 | 0.00 | -3865.82 | 0.00 | -19815.39 | 0.00 |
PERIMETER_BOT_ZN_4 | 13-FEB-05:01 | 0.00 | 0.00 | 7409.99 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2000.18 | 0.00 | -544.82 | -5219.14 |
PERIMETER_MID_ZN_3 | 13-FEB-05:01 | 0.00 | 0.00 | 8770.46 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2949.61 | 0.00 | -1230.63 | -5149.66 |
PERIMETER_MID_ZN_2 | 13-FEB-05:01 | 0.00 | 0.00 | 7991.46 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1970.45 | 0.00 | -826.67 | -5548.49 |
PERIMETER_MID_ZN_1 | 13-FEB-05:01 | 0.00 | 0.00 | 10230.11 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2950.29 | 0.00 | -1252.28 | -6586.98 |
PERIMETER_MID_ZN_4 | 13-FEB-05:01 | 0.00 | 0.00 | 7974.60 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1938.32 | 0.00 | -831.22 | -5559.21 |
TOPFLOOR_PLENUM | 13-FEB-06:12 | 13861.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -587.85 | -13273.27 |
MIDFLOOR_PLENUM | 09-JAN-07:11 | 7679.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -365.97 | -7313.28 |
FIRSTFLOOR_PLENUM | 02-JAN-07:04 | 5435.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -141.49 | -5294.24 |
Total Facility | 02-JAN-06:11 | 6866.96 | 0.00 | 163628.70 | 0.00 | 0.00 | 0.00 | 2622.77 | 2778.13 | 17291.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16515.53 | 0.00 | -2631.97 | -174040.57 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.2244 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7426 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.7104 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.1399 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.1450 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.8550 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.6122 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0762 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.3552 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0757 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.5725 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0745 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8218 | 2.8218 | 0.6377 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0491 | 2.0491 | 0.6373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1937 | 2.1937 | 0.6362 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7054 | 0.7054 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6769 | 0.6769 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8183 | 0.8183 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7507 | 0.7507 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5633 | 0.5633 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5778 | 0.5778 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6616 | 0.6616 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5999 | 0.5999 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6093 | 0.6093 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6507 | 0.6507 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7213 | 0.7213 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6799 | 0.6799 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.2244 | 4.7426 | 5.2244 | 1.0762 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.7104 | 4.1399 | 4.7104 | 1.0757 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.1450 | 4.8550 | 5.1450 | 1.0745 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4109 | 1.4109 | 0.6377 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0246 | 1.0246 | 0.6373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0968 | 1.0968 | 0.6362 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3527 | 0.3527 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3384 | 0.3384 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4092 | 0.4092 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3753 | 0.3753 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2816 | 0.2816 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2889 | 0.2889 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3308 | 0.3308 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2999 | 0.2999 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3047 | 0.3047 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3253 | 0.3253 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3607 | 0.3607 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3400 | 0.3400 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.6122 | 1.0762 | 1.0762 | 1.0762 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.3552 | 1.0757 | 1.0757 | 1.0757 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.5725 | 1.0745 | 1.0745 | 1.0745 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 143.00 |
Number of hours cooling loads not met | 149.17 |
Number of hours not met | 292.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 101.70 | 186005.08 | 37.44 | 63863.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 318.15 | 75463.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 232.55 | 24978.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 51.35 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.69 | 840.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 66.28 | 14092.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 124.42 | 10016.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1487.30 |
Natural Gas | 0.00 | 161.86 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1649.17 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.68 |
Space Heating | 20.41 |
Space Cooling | 63.86 |
Fans (All) | 13.30 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 298.52 |
Subtotal | 298.52 |
Natural Gas [MJ/m2] | |
Space Heating | 7.52 |
Service Water Heating | 24.97 |
Miscellaneous (All) | 32.49 |
Subtotal | 32.49 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 14.10 |
Space Heating | 8.44 |
Space Cooling | 19.29 |
Fans (All) | 4.02 |
Service Water Heating | 7.54 |
Receptacle Equipment | 42.78 |
Miscellaneous | 3.83 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1034. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8732.67 | 27.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8716.83 | 43.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8642.17 | 117.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8686.17 | 73.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8603.00 | 157.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8753.00 | 7.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8688.33 | 71.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8729.83 | 30.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8666.50 | 93.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8741.33 | 18.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8649.50 | 110.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8692.00 | 68.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8601.17 | 158.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8546.00 | 214.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8546.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 214.00 | 0.00 | 0.00 | 0.00 |
Average | 8693.81 | 66.19 | 0.00 | 0.00 | 0.00 |
Sum | 156488.50 | 1191.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128303.67 | 0.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.33 | 0.00 | 0.00 | 0.00 |
Average | 34143.31 | 0.02 | 0.00 | 0.00 | 0.00 |
Sum | 614579.67 | 0.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8396.83 | 363.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7869.17 | 890.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7810.17 | 949.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7839.33 | 920.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7786.00 | 974.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8111.00 | 649.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7957.00 | 803.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7830.50 | 929.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7931.67 | 828.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7862.67 | 897.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7790.00 | 970.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7823.67 | 936.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7757.33 | 1002.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8164.67 | 595.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8216.17 | 543.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8311.83 | 448.17 | 0.00 | 0.00 | 0.00 |
Min | 7757.33 | 0.67 | 0.00 | 0.00 | 0.00 |
Max | 8759.33 | 1002.67 | 0.00 | 0.00 | 0.00 |
Average | 8054.20 | 705.80 | 0.00 | 0.00 | 0.00 |
Sum | 144975.67 | 12704.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128183.33 | 120.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24874.00 | 35.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14014.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24873.50 | 35.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14014.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24892.17 | 16.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 23758.17 | 1150.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24873.67 | 35.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10133.33 | 0.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24874.00 | 35.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14015.33 | 0.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 1150.83 | 0.00 | 0.00 | 0.00 |
Average | 34063.71 | 79.62 | 0.00 | 0.00 | 0.00 |
Sum | 613146.83 | 1433.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104096E+11 | 11851.28 | 31-JAN-17:00 | 19.40 | 13.37 | 0.182676E+10 | 2606.62 | 31-JAN-10:30 | 19.40 | 13.37 |
February | 0.114647E+11 | 17505.92 | 23-FEB-08:07 | 5.18 | 3.80 | 0.173663E+10 | 2606.65 | 22-FEB-14:20 | 5.18 | 3.80 |
March | 0.182614E+11 | 20897.80 | 31-MAR-08:00 | 18.30 | 16.52 | 0.214798E+10 | 2606.71 | 08-MAR-10:09 | 18.30 | 16.52 |
April | 0.189757E+11 | 25945.66 | 18-APR-06:03 | 13.30 | 12.06 | 0.191452E+10 | 2606.64 | 07-APR-13:20 | 13.30 | 12.06 |
May | 0.233588E+11 | 39947.22 | 30-MAY-05:12 | 19.07 | 17.52 | 0.207730E+10 | 2606.74 | 11-MAY-09:00 | 19.07 | 17.52 |
June | 0.260189E+11 | 40394.88 | 19-JUN-05:12 | 20.93 | 20.12 | 0.207097E+10 | 2606.68 | 09-JUN-09:00 | 20.93 | 20.12 |
July | 0.260985E+11 | 41100.19 | 07-JUL-04:03 | 25.22 | 21.53 | 0.192550E+10 | 2606.59 | 17-JUL-13:20 | 29.40 | 22.12 |
August | 0.285911E+11 | 41091.20 | 03-AUG-04:03 | 23.90 | 22.21 | 0.216079E+10 | 2606.59 | 18-AUG-13:20 | 34.03 | 22.77 |
September | 0.242247E+11 | 39984.12 | 06-SEP-05:12 | 21.30 | 20.11 | 0.191902E+10 | 2606.64 | 15-SEP-09:50 | 23.53 | 15.91 |
October | 0.207715E+11 | 35958.92 | 10-OCT-06:02 | 15.00 | 14.30 | 0.199052E+10 | 2606.63 | 04-OCT-13:20 | 15.00 | 14.30 |
November | 0.166663E+11 | 19539.49 | 06-NOV-09:00 | 12.20 | 10.90 | 0.196277E+10 | 2608.37 | 20-NOV-10:30 | 4.70 | 2.28 |
December | 0.127670E+11 | 19764.31 | 15-DEC-08:04 | 2.88 | 0.94 | 0.187917E+10 | 2606.69 | 11-DEC-10:20 | 2.88 | 0.94 |
Annual Sum or Average | 0.237608E+12 | 0.236119E+11 | ||||||||
Minimum of Months | 0.104096E+11 | 11851.28 | 2.88 | 0.94 | 0.173663E+10 | 2606.59 | 2.88 | 0.94 | ||
Maximum of Months | 0.285911E+11 | 41100.19 | 25.22 | 22.21 | 0.216079E+10 | 2608.37 | 34.03 | 22.77 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 76133900.04 | 1079.44 | 28-JAN-17:25 | 11.40 | 4.15 | 0.00 | 0.00 | 01-JAN-00:10 | 11.40 | 4.15 |
February | 0.380150E+09 | 3139.37 | 28-FEB-16:10 | 23.40 | 12.60 | 0.00 | 0.00 | 01-FEB-00:10 | 23.40 | 12.60 |
March | 0.131171E+10 | 6765.28 | 30-MAR-14:50 | 27.80 | 17.21 | 0.00 | 0.00 | 01-MAR-00:10 | 27.80 | 17.21 |
April | 0.253851E+10 | 7724.71 | 17-APR-15:00 | 28.90 | 16.41 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 16.41 |
May | 0.419987E+10 | 8546.04 | 30-MAY-15:00 | 30.60 | 21.44 | 0.00 | 0.00 | 01-MAY-00:10 | 30.60 | 21.44 |
June | 0.603765E+10 | 9169.35 | 12-JUN-15:00 | 33.30 | 22.72 | 0.00 | 0.00 | 01-JUN-00:10 | 33.30 | 22.72 |
July | 0.642737E+10 | 10082.19 | 07-JUL-15:20 | 35.20 | 23.90 | 0.00 | 0.00 | 01-JUL-00:10 | 35.20 | 23.90 |
August | 0.670866E+10 | 10247.23 | 01-AUG-14:00 | 33.90 | 23.66 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 23.66 |
September | 0.364621E+10 | 8790.75 | 06-SEP-14:20 | 30.53 | 23.42 | 0.00 | 0.00 | 01-SEP-00:10 | 30.53 | 23.42 |
October | 0.171525E+10 | 6839.98 | 10-OCT-14:40 | 29.07 | 20.78 | 0.00 | 0.00 | 01-OCT-00:10 | 29.07 | 20.78 |
November | 0.578159E+09 | 2670.84 | 06-NOV-15:00 | 20.60 | 10.48 | 0.00 | 0.00 | 01-NOV-00:10 | 20.60 | 10.48 |
December | 0.167026E+09 | 1800.08 | 10-DEC-15:10 | 18.40 | 8.76 | 0.00 | 0.00 | 01-DEC-00:10 | 18.40 | 8.76 |
Annual Sum or Average | 0.337867E+11 | 0.00 | ||||||||
Minimum of Months | 76133900.04 | 1079.44 | 11.40 | 4.15 | 0.00 | 0.00 | 11.40 | 4.15 | ||
Maximum of Months | 0.670866E+10 | 10247.23 | 35.20 | 23.90 | 0.00 | 0.00 | 35.20 | 23.90 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30430896.00 | 1727.92 | 14-JAN-05:01 | -6.2 | -7.4 | 0.00 | 0.00 | 01-JAN-00:10 | -6.2 | -7.4 |
February | 0.128026E+09 | 1991.93 | 23-FEB-07:03 | 5.00 | 3.70 | 0.00 | 0.00 | 01-FEB-00:10 | 5.00 | 3.70 |
March | 0.557635E+09 | 2274.30 | 30-MAR-16:00 | 27.80 | 17.47 | 0.00 | 0.00 | 01-MAR-00:10 | 27.80 | 17.47 |
April | 0.110295E+10 | 3047.43 | 06-APR-06:02 | 1.20 | -0.4 | 0.00 | 0.00 | 01-APR-00:10 | 1.20 | -0.4 |
May | 0.205050E+10 | 3695.41 | 30-MAY-15:20 | 29.67 | 21.52 | 0.00 | 0.00 | 01-MAY-00:10 | 29.67 | 21.52 |
June | 0.322146E+10 | 4288.05 | 26-JUN-06:03 | 23.30 | 21.67 | 0.00 | 0.00 | 01-JUN-00:10 | 23.30 | 21.67 |
July | 0.359905E+10 | 4439.94 | 17-JUL-06:03 | 21.70 | 19.38 | 0.00 | 0.00 | 01-JUL-00:10 | 21.70 | 19.38 |
August | 0.390274E+10 | 4305.59 | 07-AUG-06:03 | 22.88 | 22.15 | 0.00 | 0.00 | 01-AUG-00:10 | 22.88 | 22.15 |
September | 0.229717E+10 | 3827.69 | 11-SEP-16:00 | 30.00 | 22.85 | 0.00 | 0.00 | 01-SEP-00:10 | 30.00 | 22.85 |
October | 0.908936E+09 | 2713.50 | 11-OCT-16:00 | 26.10 | 17.12 | 0.00 | 0.00 | 01-OCT-00:10 | 26.10 | 17.12 |
November | 0.243378E+09 | 1751.70 | 18-NOV-07:03 | 3.98 | 1.87 | 0.00 | 0.00 | 01-NOV-00:10 | 3.98 | 1.87 |
December | 84388986.39 | 1786.02 | 09-DEC-06:11 | 2.20 | -1.0 | 0.00 | 0.00 | 01-DEC-00:10 | 2.20 | -1.0 |
Annual Sum or Average | 0.181267E+11 | 0.00 | ||||||||
Minimum of Months | 30430896.00 | 1727.92 | -6.2 | -7.4 | 0.00 | 0.00 | -6.2 | -7.4 | ||
Maximum of Months | 0.390274E+10 | 4439.94 | 30.00 | 22.85 | 0.00 | 0.00 | 30.00 | 22.85 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 37305247.03 | 1634.52 | 13-JAN-06:11 | 3.90 | 2.25 | 0.00 | 0.00 | 01-JAN-00:10 | 3.90 | 2.25 |
February | 0.177309E+09 | 2336.71 | 23-FEB-07:03 | 5.00 | 3.70 | 0.00 | 0.00 | 01-FEB-00:10 | 5.00 | 3.70 |
March | 0.811828E+09 | 2409.76 | 06-MAR-07:03 | 2.80 | 0.11 | 0.00 | 0.00 | 01-MAR-00:10 | 2.80 | 0.11 |
April | 0.140209E+10 | 3170.77 | 06-APR-06:02 | 1.20 | -0.4 | 0.00 | 0.00 | 01-APR-00:10 | 1.20 | -0.4 |
May | 0.236415E+10 | 3836.90 | 30-MAY-15:10 | 30.13 | 21.49 | 0.00 | 0.00 | 01-MAY-00:10 | 30.13 | 21.49 |
June | 0.358422E+10 | 4098.05 | 26-JUN-15:30 | 30.00 | 23.57 | 0.00 | 0.00 | 01-JUN-00:10 | 30.00 | 23.57 |
July | 0.396051E+10 | 4635.49 | 10-JUL-15:40 | 32.60 | 22.27 | 0.00 | 0.00 | 01-JUL-00:10 | 32.60 | 22.27 |
August | 0.443701E+10 | 4584.07 | 07-AUG-12:20 | 31.13 | 23.76 | 0.00 | 0.00 | 01-AUG-00:10 | 31.13 | 23.76 |
September | 0.297498E+10 | 4459.52 | 11-SEP-16:00 | 30.00 | 22.85 | 0.00 | 0.00 | 01-SEP-00:10 | 30.00 | 22.85 |
October | 0.142665E+10 | 3417.16 | 11-OCT-16:00 | 26.10 | 17.12 | 0.00 | 0.00 | 01-OCT-00:10 | 26.10 | 17.12 |
November | 0.427511E+09 | 1792.05 | 21-NOV-07:01 | -2.8 | -3.9 | 0.00 | 0.00 | 01-NOV-00:10 | -2.8 | -3.9 |
December | 0.118056E+09 | 1767.35 | 08-DEC-07:03 | 4.90 | 2.14 | 0.00 | 0.00 | 01-DEC-00:10 | 4.90 | 2.14 |
Annual Sum or Average | 0.217216E+11 | 0.00 | ||||||||
Minimum of Months | 37305247.03 | 1634.52 | -2.8 | -3.9 | 0.00 | 0.00 | -2.8 | -3.9 | ||
Maximum of Months | 0.443701E+10 | 4635.49 | 32.60 | 23.76 | 0.00 | 0.00 | 32.60 | 23.76 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.685634E+10 | 7657.31 | 31-JAN-17:00 | 19.40 | 13.37 | 0.154459E+10 | 2318.94 | 31-JAN-14:00 | 19.40 | 13.37 |
February | 0.808088E+10 | 10326.05 | 28-FEB-17:00 | 23.90 | 12.94 | 0.150560E+10 | 2606.61 | 28-FEB-14:20 | 23.90 | 12.94 |
March | 0.122882E+11 | 13514.47 | 30-MAR-16:00 | 27.80 | 17.47 | 0.204407E+10 | 2606.64 | 30-MAR-09:20 | 27.80 | 17.47 |
April | 0.131854E+11 | 14410.85 | 17-APR-16:00 | 28.90 | 16.41 | 0.188057E+10 | 2606.64 | 17-APR-09:20 | 28.90 | 16.41 |
May | 0.165487E+11 | 28949.20 | 30-MAY-05:12 | 19.07 | 17.52 | 0.206481E+10 | 2606.69 | 11-MAY-09:00 | 19.07 | 17.52 |
June | 0.188889E+11 | 29233.29 | 19-JUN-05:12 | 20.93 | 20.12 | 0.206587E+10 | 2606.68 | 09-JUN-09:50 | 20.93 | 20.12 |
July | 0.194330E+11 | 29250.30 | 07-JUL-04:03 | 25.22 | 21.53 | 0.192061E+10 | 2606.60 | 03-JUL-09:20 | 25.22 | 21.53 |
August | 0.208525E+11 | 29098.95 | 22-AUG-05:12 | 22.80 | 21.57 | 0.215748E+10 | 2606.59 | 28-AUG-13:20 | 28.30 | 22.11 |
September | 0.167496E+11 | 29131.52 | 11-SEP-05:12 | 20.20 | 19.05 | 0.190949E+10 | 2606.64 | 21-SEP-09:20 | 21.33 | 17.87 |
October | 0.133600E+11 | 14942.62 | 11-OCT-16:00 | 26.10 | 17.12 | 0.192899E+10 | 2606.63 | 10-OCT-09:20 | 26.10 | 17.12 |
November | 0.105009E+11 | 11391.68 | 06-NOV-17:00 | 18.90 | 9.61 | 0.181908E+10 | 2606.58 | 03-NOV-13:20 | 18.90 | 9.61 |
December | 0.881669E+10 | 8480.60 | 13-DEC-17:00 | 16.70 | 16.70 | 0.159812E+10 | 2577.48 | 13-DEC-14:00 | 16.70 | 16.70 |
Annual Sum or Average | 0.165561E+12 | 0.224393E+11 | ||||||||
Minimum of Months | 0.685634E+10 | 7657.31 | 16.70 | 9.61 | 0.150560E+10 | 2318.94 | 16.70 | 9.61 | ||
Maximum of Months | 0.208525E+11 | 29250.30 | 28.90 | 21.57 | 0.215748E+10 | 2606.69 | 28.90 | 22.11 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.504196E+10 | 7576.31 | 20-JAN-17:00 | 16.70 | 11.48 | 0.149549E+10 | 2274.72 | 31-JAN-14:00 | 21.10 | 12.97 |
February | 0.655946E+10 | 10493.11 | 28-FEB-17:00 | 23.90 | 12.94 | 0.143820E+10 | 2606.55 | 28-FEB-14:00 | 23.90 | 12.94 |
March | 0.115584E+11 | 15597.03 | 30-MAR-16:00 | 27.80 | 17.47 | 0.195062E+10 | 2606.61 | 29-MAR-13:20 | 27.80 | 17.47 |
April | 0.129546E+11 | 16758.85 | 17-APR-16:00 | 28.90 | 16.41 | 0.183826E+10 | 2606.63 | 17-APR-09:20 | 28.90 | 16.41 |
May | 0.169430E+11 | 18908.81 | 30-MAY-15:20 | 29.67 | 21.52 | 0.205342E+10 | 2606.69 | 24-MAY-09:20 | 29.67 | 21.52 |
June | 0.199536E+11 | 30420.84 | 26-JUN-05:12 | 23.30 | 21.67 | 0.206302E+10 | 2606.67 | 09-JUN-09:00 | 23.30 | 21.67 |
July | 0.206817E+11 | 31344.95 | 24-JUL-05:12 | 20.60 | 19.55 | 0.191996E+10 | 2606.61 | 03-JUL-09:20 | 20.60 | 19.55 |
August | 0.220256E+11 | 31787.13 | 14-AUG-04:03 | 24.22 | 20.90 | 0.215738E+10 | 2606.63 | 25-AUG-09:20 | 25.53 | 18.30 |
September | 0.164448E+11 | 31185.05 | 05-SEP-05:12 | 21.70 | 20.50 | 0.189821E+10 | 2606.65 | 25-SEP-09:09 | 24.78 | 19.25 |
October | 0.121936E+11 | 15963.50 | 11-OCT-15:50 | 26.28 | 17.62 | 0.185339E+10 | 2606.61 | 10-OCT-09:20 | 26.28 | 17.62 |
November | 0.913519E+10 | 10330.88 | 06-NOV-17:00 | 18.90 | 9.61 | 0.168563E+10 | 2606.44 | 06-NOV-14:20 | 18.90 | 9.61 |
December | 0.653921E+10 | 8280.31 | 13-DEC-17:00 | 16.70 | 16.70 | 0.150372E+10 | 2520.33 | 13-DEC-14:00 | 16.70 | 16.70 |
Annual Sum or Average | 0.160031E+12 | 0.218573E+11 | ||||||||
Minimum of Months | 0.504196E+10 | 7576.31 | 16.70 | 9.61 | 0.143820E+10 | 2274.72 | 16.70 | 9.61 | ||
Maximum of Months | 0.220256E+11 | 31787.13 | 29.67 | 21.67 | 0.215738E+10 | 2606.69 | 29.67 | 21.67 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.283591E+09 | 1561.51 | 31-JAN-16:40 | 19.60 | 13.44 | 0.308319E+09 | 477.84 | 31-JAN-14:00 | 19.60 | 13.44 |
February | 0.714373E+09 | 2606.13 | 28-FEB-15:30 | 24.15 | 13.12 | 0.291141E+09 | 549.49 | 28-FEB-14:20 | 24.15 | 13.12 |
March | 0.208766E+10 | 4685.50 | 30-MAR-15:50 | 27.80 | 17.41 | 0.387574E+09 | 549.49 | 29-MAR-13:20 | 27.80 | 17.41 |
April | 0.284795E+10 | 5018.00 | 19-APR-14:30 | 26.15 | 17.54 | 0.373015E+09 | 549.49 | 12-APR-13:00 | 26.15 | 17.54 |
May | 0.443468E+10 | 6499.51 | 30-MAY-15:00 | 30.60 | 21.44 | 0.428360E+09 | 549.50 | 24-MAY-09:20 | 30.60 | 21.44 |
June | 0.612605E+10 | 11325.96 | 25-JUN-17:02 | 32.43 | 22.44 | 0.434658E+09 | 549.50 | 09-JUN-09:20 | 32.43 | 22.44 |
July | 0.640015E+10 | 11544.11 | 16-JUL-13:43 | 33.62 | 23.40 | 0.405223E+09 | 549.49 | 03-JUL-09:20 | 33.62 | 23.40 |
August | 0.665168E+10 | 10193.50 | 06-AUG-16:42 | 32.30 | 23.28 | 0.455007E+09 | 549.49 | 25-AUG-09:20 | 25.53 | 18.30 |
September | 0.407392E+10 | 6268.15 | 06-SEP-14:30 | 30.25 | 23.24 | 0.395980E+09 | 549.49 | 25-SEP-09:20 | 25.17 | 19.30 |
October | 0.233222E+10 | 4395.51 | 02-OCT-14:40 | 26.70 | 20.10 | 0.369268E+09 | 549.49 | 05-OCT-13:20 | 20.00 | 14.95 |
November | 0.133889E+10 | 2002.53 | 02-NOV-15:30 | 22.50 | 16.22 | 0.331643E+09 | 549.46 | 03-NOV-13:00 | 21.70 | 17.40 |
December | 0.584728E+09 | 1690.10 | 13-DEC-15:00 | 18.30 | 16.86 | 0.302764E+09 | 519.53 | 13-DEC-14:00 | 18.30 | 16.86 |
Annual Sum or Average | 0.378759E+11 | 0.448295E+10 | ||||||||
Minimum of Months | 0.283591E+09 | 1561.51 | 18.30 | 13.12 | 0.291141E+09 | 477.84 | 18.30 | 13.12 | ||
Maximum of Months | 0.665168E+10 | 11544.11 | 33.62 | 23.40 | 0.455007E+09 | 549.50 | 33.62 | 23.40 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.315348E+09 | 1024.68 | 31-JAN-15:00 | 21.10 | 12.97 | 0.196879E+09 | 314.66 | 31-JAN-14:00 | 21.10 | 12.97 |
February | 0.650104E+09 | 2198.49 | 27-FEB-10:40 | 14.27 | 6.32 | 0.193308E+09 | 347.87 | 24-FEB-10:20 | 14.27 | 6.32 |
March | 0.172221E+10 | 3740.52 | 30-MAR-11:00 | 22.20 | 17.83 | 0.263162E+09 | 347.88 | 08-MAR-10:20 | 22.20 | 17.83 |
April | 0.271657E+10 | 7670.15 | 16-APR-10:33 | 24.80 | 15.25 | 0.248307E+09 | 347.88 | 12-APR-13:00 | 24.80 | 15.25 |
May | 0.408158E+10 | 11123.15 | 07-MAY-10:02 | 25.37 | 20.20 | 0.274555E+09 | 347.89 | 11-MAY-09:50 | 16.73 | 12.76 |
June | 0.531940E+10 | 11345.49 | 25-JUN-09:02 | 27.15 | 22.14 | 0.276018E+09 | 347.89 | 09-JUN-09:00 | 27.15 | 22.14 |
July | 0.555696E+10 | 11384.28 | 09-JUL-10:22 | 28.85 | 23.10 | 0.256935E+09 | 347.87 | 03-JUL-09:20 | 28.85 | 23.10 |
August | 0.567138E+10 | 11963.79 | 27-AUG-09:22 | 26.10 | 21.69 | 0.288413E+09 | 347.88 | 25-AUG-09:20 | 26.10 | 21.69 |
September | 0.368889E+10 | 11304.16 | 04-SEP-09:32 | 26.13 | 22.05 | 0.252804E+09 | 347.88 | 15-SEP-09:00 | 23.90 | 16.09 |
October | 0.203444E+10 | 4523.54 | 11-OCT-10:30 | 24.20 | 19.54 | 0.245810E+09 | 347.87 | 04-OCT-13:20 | 24.20 | 19.54 |
November | 0.105142E+10 | 1943.13 | 06-NOV-10:40 | 16.27 | 12.91 | 0.222315E+09 | 347.87 | 07-NOV-10:20 | 12.43 | 6.30 |
December | 0.552416E+09 | 1096.25 | 13-DEC-13:30 | 19.45 | 17.14 | 0.196959E+09 | 335.12 | 13-DEC-14:20 | 18.30 | 16.86 |
Annual Sum or Average | 0.333607E+11 | 0.291546E+10 | ||||||||
Minimum of Months | 0.315348E+09 | 1024.68 | 14.27 | 6.32 | 0.193308E+09 | 314.66 | 12.43 | 6.30 | ||
Maximum of Months | 0.567138E+10 | 11963.79 | 28.85 | 23.10 | 0.288413E+09 | 347.89 | 28.85 | 23.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114389E+10 | 4468.67 | 11-JAN-14:30 | 6.70 | 2.05 | 0.342160E+09 | 549.47 | 05-JAN-14:00 | 6.70 | 2.05 |
February | 0.171139E+10 | 11171.34 | 26-FEB-14:33 | 24.80 | 12.68 | 0.319138E+09 | 549.50 | 22-FEB-14:20 | 24.80 | 12.68 |
March | 0.344123E+10 | 9603.29 | 30-MAR-13:40 | 27.43 | 17.97 | 0.411506E+09 | 549.50 | 13-MAR-13:00 | 27.43 | 17.97 |
April | 0.399290E+10 | 11725.10 | 16-APR-13:53 | 28.90 | 16.19 | 0.381064E+09 | 549.52 | 12-APR-13:00 | 28.90 | 16.19 |
May | 0.506882E+10 | 9534.66 | 29-MAY-13:43 | 28.40 | 20.38 | 0.428241E+09 | 549.50 | 24-MAY-09:20 | 28.40 | 20.38 |
June | 0.632235E+10 | 12133.26 | 25-JUN-16:22 | 33.05 | 22.20 | 0.433882E+09 | 549.50 | 09-JUN-09:20 | 33.05 | 22.20 |
July | 0.671992E+10 | 13389.28 | 09-JUL-13:43 | 32.62 | 23.65 | 0.405194E+09 | 549.49 | 03-JUL-09:20 | 32.62 | 23.65 |
August | 0.783156E+10 | 13808.12 | 06-AUG-13:23 | 32.50 | 23.69 | 0.455238E+09 | 549.49 | 25-AUG-09:20 | 25.53 | 18.30 |
September | 0.578075E+10 | 14059.46 | 24-SEP-13:13 | 28.70 | 19.86 | 0.397915E+09 | 549.49 | 22-SEP-13:50 | 28.70 | 19.86 |
October | 0.448103E+10 | 14022.05 | 09-OCT-13:32 | 26.83 | 19.20 | 0.389666E+09 | 551.94 | 10-OCT-13:50 | 29.22 | 21.00 |
November | 0.279481E+10 | 13694.57 | 11-NOV-13:43 | 21.10 | 11.67 | 0.368937E+09 | 549.49 | 14-NOV-14:30 | 19.15 | 8.88 |
December | 0.173777E+10 | 6114.88 | 12-DEC-13:40 | 22.23 | 16.93 | 0.343963E+09 | 549.48 | 12-DEC-14:30 | 22.80 | 16.62 |
Annual Sum or Average | 0.510264E+11 | 0.467691E+10 | ||||||||
Minimum of Months | 0.114389E+10 | 4468.67 | 6.70 | 2.05 | 0.319138E+09 | 549.47 | 6.70 | 2.05 | ||
Maximum of Months | 0.783156E+10 | 14059.46 | 33.05 | 23.69 | 0.455238E+09 | 551.94 | 33.05 | 23.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.336505E+09 | 1099.70 | 20-JAN-16:40 | 16.87 | 11.91 | 0.199520E+09 | 331.08 | 11-JAN-16:49 | 16.87 | 11.91 |
February | 0.669147E+09 | 4313.77 | 27-FEB-17:00 | 22.20 | 11.44 | 0.189360E+09 | 347.84 | 28-FEB-14:20 | 25.00 | 13.71 |
March | 0.191958E+10 | 6412.81 | 30-MAR-16:00 | 27.80 | 17.47 | 0.250783E+09 | 347.84 | 29-MAR-13:20 | 27.80 | 17.47 |
April | 0.277294E+10 | 12354.03 | 09-APR-17:23 | 21.40 | 11.01 | 0.238439E+09 | 347.85 | 12-APR-13:00 | 28.90 | 17.10 |
May | 0.393434E+10 | 11039.89 | 29-MAY-17:02 | 29.90 | 20.47 | 0.271406E+09 | 347.85 | 24-MAY-09:20 | 29.90 | 20.47 |
June | 0.505183E+10 | 12661.00 | 25-JUN-16:22 | 33.05 | 22.20 | 0.275025E+09 | 347.85 | 09-JUN-09:20 | 33.05 | 22.20 |
July | 0.523853E+10 | 12869.10 | 23-JUL-18:42 | 28.40 | 21.62 | 0.256695E+09 | 347.84 | 03-JUL-09:20 | 28.40 | 21.62 |
August | 0.552908E+10 | 12914.29 | 13-AUG-17:02 | 31.10 | 22.35 | 0.288309E+09 | 347.85 | 25-AUG-09:20 | 25.53 | 18.30 |
September | 0.353049E+10 | 11725.21 | 04-SEP-16:53 | 28.30 | 22.10 | 0.251407E+09 | 347.85 | 25-SEP-09:20 | 25.17 | 19.30 |
October | 0.207921E+10 | 11015.61 | 09-OCT-16:12 | 27.43 | 19.51 | 0.237704E+09 | 347.84 | 20-OCT-13:20 | 18.13 | 11.22 |
November | 0.109794E+10 | 3981.47 | 06-NOV-16:00 | 20.60 | 10.48 | 0.217795E+09 | 347.84 | 15-NOV-14:20 | 21.30 | 11.42 |
December | 0.520389E+09 | 1607.80 | 11-DEC-16:00 | 21.10 | 15.91 | 0.199098E+09 | 347.83 | 12-DEC-14:30 | 22.80 | 16.62 |
Annual Sum or Average | 0.326800E+11 | 0.287554E+10 | ||||||||
Minimum of Months | 0.336505E+09 | 1099.70 | 16.87 | 10.48 | 0.189360E+09 | 331.08 | 16.87 | 11.22 | ||
Maximum of Months | 0.552908E+10 | 12914.29 | 33.05 | 22.35 | 0.288309E+09 | 347.85 | 33.05 | 22.20 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.327051E+09 | 1495.09 | 31-JAN-16:30 | 19.70 | 13.48 | 0.309086E+09 | 462.11 | 31-JAN-14:00 | 19.70 | 13.48 |
February | 0.760566E+09 | 1718.96 | 28-FEB-15:10 | 24.72 | 13.51 | 0.289470E+09 | 530.97 | 28-FEB-14:00 | 24.72 | 13.51 |
March | 0.195076E+10 | 2693.96 | 30-MAR-16:00 | 27.80 | 17.47 | 0.379309E+09 | 549.48 | 30-MAR-13:20 | 27.80 | 17.47 |
April | 0.219707E+10 | 2988.56 | 19-APR-14:30 | 26.15 | 17.54 | 0.362349E+09 | 549.49 | 17-APR-13:20 | 26.15 | 17.54 |
May | 0.315863E+10 | 4498.99 | 30-MAY-15:00 | 30.60 | 21.44 | 0.425804E+09 | 549.50 | 17-MAY-09:20 | 30.60 | 21.44 |
June | 0.488644E+10 | 5266.88 | 28-JUN-14:30 | 30.85 | 23.20 | 0.434760E+09 | 549.50 | 09-JUN-09:20 | 30.85 | 23.20 |
July | 0.542380E+10 | 6915.63 | 16-JUL-15:23 | 33.30 | 22.52 | 0.405018E+09 | 549.49 | 03-JUL-09:20 | 33.30 | 22.52 |
August | 0.597616E+10 | 6403.75 | 21-AUG-06:03 | 22.20 | 22.20 | 0.454962E+09 | 549.49 | 18-AUG-13:20 | 22.20 | 22.20 |
September | 0.409507E+10 | 5550.93 | 06-SEP-14:20 | 30.53 | 23.42 | 0.401737E+09 | 549.49 | 20-SEP-09:20 | 20.93 | 15.94 |
October | 0.271787E+10 | 3975.23 | 02-OCT-14:30 | 26.70 | 20.05 | 0.391717E+09 | 549.49 | 10-OCT-09:20 | 21.50 | 18.02 |
November | 0.191718E+10 | 2072.27 | 03-NOV-14:00 | 21.70 | 17.40 | 0.356481E+09 | 549.48 | 03-NOV-13:20 | 21.70 | 17.40 |
December | 0.102281E+10 | 1691.28 | 13-DEC-13:30 | 19.45 | 17.14 | 0.309985E+09 | 518.69 | 13-DEC-14:20 | 18.30 | 16.86 |
Annual Sum or Average | 0.344334E+11 | 0.452068E+10 | ||||||||
Minimum of Months | 0.327051E+09 | 1495.09 | 19.45 | 13.48 | 0.289470E+09 | 462.11 | 18.30 | 13.48 | ||
Maximum of Months | 0.597616E+10 | 6915.63 | 33.30 | 23.42 | 0.454962E+09 | 549.50 | 33.30 | 23.20 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.404537E+09 | 1002.01 | 31-JAN-14:50 | 21.02 | 13.03 | 0.198583E+09 | 309.05 | 31-JAN-14:00 | 21.10 | 12.97 |
February | 0.687588E+09 | 1927.81 | 27-FEB-10:40 | 14.27 | 6.32 | 0.193952E+09 | 347.87 | 24-FEB-10:20 | 14.27 | 6.32 |
March | 0.154824E+10 | 2633.03 | 14-MAR-09:30 | 16.95 | 13.93 | 0.263314E+09 | 347.88 | 08-MAR-10:20 | 16.95 | 13.93 |
April | 0.204465E+10 | 4277.33 | 17-APR-10:10 | 23.27 | 15.57 | 0.246870E+09 | 347.88 | 17-APR-09:20 | 23.27 | 15.57 |
May | 0.311749E+10 | 7881.93 | 07-MAY-09:32 | 24.43 | 19.78 | 0.274358E+09 | 347.89 | 11-MAY-09:00 | 17.20 | 13.27 |
June | 0.448328E+10 | 8785.70 | 11-JUN-10:02 | 25.28 | 14.81 | 0.276110E+09 | 347.88 | 09-JUN-09:00 | 25.28 | 14.81 |
July | 0.490973E+10 | 9053.95 | 09-JUL-08:23 | 23.90 | 21.72 | 0.257050E+09 | 347.87 | 17-JUL-09:20 | 26.67 | 21.67 |
August | 0.527276E+10 | 10101.19 | 27-AUG-09:52 | 27.20 | 21.81 | 0.288540E+09 | 347.87 | 18-AUG-13:20 | 27.20 | 21.81 |
September | 0.379293E+10 | 9132.53 | 04-SEP-09:23 | 25.85 | 21.92 | 0.255231E+09 | 347.88 | 15-SEP-09:50 | 23.53 | 15.91 |
October | 0.242303E+10 | 4505.39 | 10-OCT-10:20 | 24.23 | 18.95 | 0.256319E+09 | 347.87 | 04-OCT-13:20 | 24.23 | 18.95 |
November | 0.144484E+10 | 2521.07 | 06-NOV-10:10 | 14.87 | 12.62 | 0.241563E+09 | 347.87 | 09-NOV-14:20 | 19.60 | 12.10 |
December | 0.907923E+09 | 1110.43 | 13-DEC-12:00 | 20.00 | 17.41 | 0.206874E+09 | 339.42 | 13-DEC-14:20 | 18.30 | 16.86 |
Annual Sum or Average | 0.310370E+11 | 0.295877E+10 | ||||||||
Minimum of Months | 0.404537E+09 | 1002.01 | 14.27 | 6.32 | 0.193952E+09 | 309.05 | 14.27 | 6.32 | ||
Maximum of Months | 0.527276E+10 | 10101.19 | 27.20 | 21.92 | 0.288540E+09 | 347.89 | 27.20 | 21.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.737276E+09 | 2639.10 | 28-JAN-14:40 | 11.67 | 4.40 | 0.316611E+09 | 540.94 | 31-JAN-14:50 | 21.02 | 13.03 |
February | 0.120802E+10 | 6152.45 | 21-FEB-14:30 | 22.25 | 10.82 | 0.302016E+09 | 549.50 | 27-FEB-14:20 | 20.77 | 9.86 |
March | 0.244300E+10 | 7688.37 | 30-MAR-16:10 | 27.62 | 17.53 | 0.397007E+09 | 549.50 | 13-MAR-13:00 | 27.62 | 17.53 |
April | 0.277271E+10 | 7748.97 | 17-APR-16:10 | 28.80 | 16.45 | 0.366566E+09 | 549.50 | 27-APR-13:20 | 20.97 | 11.53 |
May | 0.377024E+10 | 8833.89 | 30-MAY-12:00 | 29.40 | 21.24 | 0.418713E+09 | 549.50 | 10-MAY-13:20 | 29.40 | 21.24 |
June | 0.580994E+10 | 9549.43 | 06-JUN-16:30 | 33.90 | 21.77 | 0.432549E+09 | 572.22 | 06-JUN-12:09 | 33.90 | 21.77 |
July | 0.648662E+10 | 9965.56 | 07-JUL-16:10 | 35.50 | 23.98 | 0.405255E+09 | 596.05 | 14-JUL-12:09 | 33.40 | 24.44 |
August | 0.804933E+10 | 10988.40 | 27-AUG-13:53 | 31.70 | 22.32 | 0.457062E+09 | 621.37 | 18-AUG-12:09 | 31.70 | 22.32 |
September | 0.599699E+10 | 9839.43 | 07-SEP-12:00 | 31.10 | 23.22 | 0.400818E+09 | 599.74 | 07-SEP-12:09 | 31.02 | 23.18 |
October | 0.441968E+10 | 11534.70 | 09-OCT-14:32 | 27.60 | 19.53 | 0.396689E+09 | 589.78 | 10-OCT-13:00 | 29.40 | 21.05 |
November | 0.276667E+10 | 10920.93 | 12-NOV-14:03 | 19.08 | 10.60 | 0.376273E+09 | 549.50 | 09-NOV-14:20 | 19.08 | 10.60 |
December | 0.166531E+10 | 5776.73 | 12-DEC-13:50 | 22.52 | 17.00 | 0.336409E+09 | 549.49 | 27-DEC-14:20 | 17.23 | 8.31 |
Annual Sum or Average | 0.461258E+11 | 0.460597E+10 | ||||||||
Minimum of Months | 0.737276E+09 | 2639.10 | 11.67 | 4.40 | 0.302016E+09 | 540.94 | 17.23 | 8.31 | ||
Maximum of Months | 0.804933E+10 | 11534.70 | 35.50 | 23.98 | 0.457062E+09 | 621.37 | 33.90 | 24.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.378291E+09 | 1046.13 | 20-JAN-16:40 | 16.87 | 11.91 | 0.199537E+09 | 313.21 | 27-JAN-16:00 | 4.40 | -1.6 |
February | 0.669929E+09 | 3081.17 | 27-FEB-17:00 | 22.20 | 11.44 | 0.189342E+09 | 347.84 | 28-FEB-14:20 | 25.00 | 13.71 |
March | 0.164976E+10 | 4322.26 | 30-MAR-16:00 | 27.80 | 17.47 | 0.253176E+09 | 347.84 | 29-MAR-13:20 | 27.80 | 17.47 |
April | 0.201579E+10 | 4840.13 | 17-APR-16:00 | 28.90 | 16.41 | 0.238330E+09 | 347.85 | 18-APR-09:20 | 22.93 | 15.81 |
May | 0.290297E+10 | 6737.68 | 06-MAY-17:08 | 27.70 | 19.15 | 0.272264E+09 | 347.85 | 17-MAY-09:20 | 22.93 | 16.84 |
June | 0.418993E+10 | 8498.16 | 04-JUN-16:52 | 31.70 | 19.74 | 0.275754E+09 | 347.85 | 09-JUN-09:20 | 23.33 | 14.53 |
July | 0.456102E+10 | 10150.70 | 09-JUL-17:02 | 33.22 | 22.71 | 0.256843E+09 | 347.85 | 03-JUL-09:20 | 33.22 | 22.71 |
August | 0.511393E+10 | 10371.62 | 27-AUG-15:52 | 31.70 | 21.48 | 0.288511E+09 | 347.84 | 21-AUG-09:20 | 31.70 | 21.48 |
September | 0.360997E+10 | 9827.45 | 24-SEP-16:53 | 27.80 | 19.57 | 0.255142E+09 | 347.85 | 20-SEP-09:20 | 27.80 | 19.57 |
October | 0.236017E+10 | 7026.04 | 08-OCT-16:43 | 26.78 | 18.71 | 0.253416E+09 | 347.85 | 10-OCT-09:20 | 21.50 | 18.02 |
November | 0.149243E+10 | 3920.24 | 06-NOV-16:30 | 19.75 | 10.05 | 0.235907E+09 | 347.85 | 09-NOV-14:20 | 19.60 | 12.10 |
December | 0.841552E+09 | 1525.75 | 11-DEC-16:00 | 21.10 | 15.91 | 0.205034E+09 | 347.84 | 12-DEC-14:30 | 22.80 | 16.62 |
Annual Sum or Average | 0.297857E+11 | 0.292325E+10 | ||||||||
Minimum of Months | 0.378291E+09 | 1046.13 | 16.87 | 10.05 | 0.189342E+09 | 313.21 | 4.40 | -1.6 | ||
Maximum of Months | 0.511393E+10 | 10371.62 | 33.22 | 22.71 | 0.288511E+09 | 347.85 | 33.22 | 22.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.390034E+09 | 1574.40 | 31-JAN-16:40 | 19.60 | 13.44 | 0.310153E+09 | 483.57 | 31-JAN-14:00 | 19.60 | 13.44 |
February | 0.913453E+09 | 2581.43 | 28-FEB-15:00 | 25.00 | 13.71 | 0.295608E+09 | 549.49 | 28-FEB-14:20 | 25.00 | 13.71 |
March | 0.233576E+10 | 4147.38 | 30-MAR-15:50 | 27.80 | 17.41 | 0.400931E+09 | 549.49 | 30-MAR-09:20 | 27.80 | 17.41 |
April | 0.286847E+10 | 4545.92 | 18-APR-14:00 | 27.20 | 15.86 | 0.382002E+09 | 549.50 | 17-APR-09:20 | 27.20 | 15.86 |
May | 0.424736E+10 | 5849.11 | 30-MAY-15:00 | 30.60 | 21.44 | 0.432654E+09 | 549.50 | 17-MAY-09:20 | 30.60 | 21.44 |
June | 0.577124E+10 | 7878.16 | 26-JUN-05:12 | 23.30 | 21.67 | 0.435541E+09 | 549.50 | 09-JUN-09:50 | 23.30 | 21.67 |
July | 0.599342E+10 | 9775.20 | 16-JUL-13:43 | 33.62 | 23.40 | 0.405448E+09 | 549.49 | 03-JUL-09:20 | 33.62 | 23.40 |
August | 0.627757E+10 | 8673.65 | 06-AUG-17:12 | 32.20 | 23.00 | 0.455172E+09 | 549.49 | 18-AUG-13:20 | 34.03 | 22.77 |
September | 0.406580E+10 | 5692.95 | 06-SEP-14:20 | 30.53 | 23.42 | 0.400217E+09 | 549.49 | 21-SEP-09:20 | 21.33 | 17.87 |
October | 0.262739E+10 | 4077.38 | 02-OCT-14:30 | 26.70 | 20.05 | 0.383351E+09 | 549.49 | 10-OCT-09:20 | 21.50 | 18.02 |
November | 0.173319E+10 | 2178.17 | 03-NOV-14:00 | 21.70 | 17.40 | 0.347169E+09 | 549.48 | 03-NOV-13:20 | 21.70 | 17.40 |
December | 0.882473E+09 | 1726.41 | 13-DEC-13:30 | 19.45 | 17.14 | 0.308796E+09 | 530.58 | 13-DEC-14:00 | 18.30 | 16.86 |
Annual Sum or Average | 0.381062E+11 | 0.455705E+10 | ||||||||
Minimum of Months | 0.390034E+09 | 1574.40 | 19.45 | 13.44 | 0.295608E+09 | 483.57 | 18.30 | 13.44 | ||
Maximum of Months | 0.627757E+10 | 9775.20 | 33.62 | 23.42 | 0.455172E+09 | 549.50 | 34.03 | 23.40 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.332362E+09 | 1113.92 | 31-JAN-15:05 | 20.92 | 13.08 | 0.147462E+09 | 339.43 | 31-JAN-15:09 | 20.92 | 13.08 |
February | 0.677541E+09 | 4279.09 | 23-FEB-13:02 | 13.40 | 6.52 | 0.145343E+09 | 356.45 | 24-FEB-15:09 | 16.60 | 7.45 |
March | 0.171210E+10 | 5320.08 | 15-MAR-12:02 | 13.48 | 6.47 | 0.198308E+09 | 356.46 | 13-MAR-14:09 | 13.48 | 6.47 |
April | 0.258936E+10 | 7616.97 | 16-APR-09:33 | 21.83 | 14.45 | 0.185259E+09 | 356.46 | 12-APR-10:09 | 21.83 | 14.45 |
May | 0.376500E+10 | 10956.57 | 07-MAY-09:02 | 23.58 | 19.38 | 0.204264E+09 | 356.47 | 11-MAY-10:09 | 17.67 | 13.57 |
June | 0.485219E+10 | 11449.33 | 04-JUN-09:22 | 25.55 | 18.85 | 0.204753E+09 | 356.46 | 09-JUN-10:09 | 24.78 | 15.66 |
July | 0.505325E+10 | 11417.55 | 23-JUL-09:12 | 26.87 | 22.77 | 0.191252E+09 | 356.45 | 20-JUL-10:09 | 26.87 | 22.77 |
August | 0.518682E+10 | 11685.55 | 27-AUG-09:52 | 27.20 | 21.81 | 0.213880E+09 | 356.45 | 18-AUG-14:09 | 27.20 | 21.81 |
September | 0.349098E+10 | 10885.23 | 04-SEP-09:23 | 25.85 | 21.92 | 0.188621E+09 | 356.47 | 15-SEP-10:09 | 24.18 | 16.24 |
October | 0.209057E+10 | 5924.94 | 11-OCT-10:05 | 23.27 | 19.04 | 0.186054E+09 | 356.45 | 27-OCT-12:09 | 17.15 | 11.90 |
November | 0.110271E+10 | 3616.06 | 09-NOV-13:02 | 17.57 | 11.10 | 0.172702E+09 | 356.45 | 14-NOV-13:09 | 17.38 | 7.82 |
December | 0.602934E+09 | 2367.29 | 13-DEC-13:05 | 20.22 | 17.28 | 0.151204E+09 | 356.45 | 13-DEC-15:09 | 18.12 | 16.87 |
Annual Sum or Average | 0.314558E+11 | 0.218910E+10 | ||||||||
Minimum of Months | 0.332362E+09 | 1113.92 | 13.40 | 6.47 | 0.145343E+09 | 339.43 | 13.48 | 6.47 | ||
Maximum of Months | 0.518682E+10 | 11685.55 | 27.20 | 22.77 | 0.213880E+09 | 356.47 | 27.20 | 22.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136923E+10 | 4648.54 | 27-JAN-14:40 | 3.53 | -2.0 | 0.348146E+09 | 549.48 | 05-JAN-14:00 | 3.53 | -2.0 |
February | 0.197888E+10 | 10983.24 | 26-FEB-14:43 | 24.90 | 12.71 | 0.325376E+09 | 549.50 | 22-FEB-14:20 | 24.90 | 12.71 |
March | 0.371093E+10 | 8985.74 | 30-MAR-13:40 | 27.43 | 17.97 | 0.423488E+09 | 549.51 | 13-MAR-13:00 | 27.43 | 17.97 |
April | 0.398128E+10 | 10114.51 | 16-APR-13:33 | 28.70 | 16.13 | 0.388911E+09 | 549.51 | 12-APR-13:50 | 28.70 | 16.13 |
May | 0.484704E+10 | 7068.59 | 30-MAY-14:00 | 30.60 | 21.03 | 0.432544E+09 | 549.50 | 17-MAY-09:20 | 30.60 | 21.03 |
June | 0.593588E+10 | 8192.59 | 26-JUN-05:12 | 23.30 | 21.67 | 0.435168E+09 | 549.50 | 09-JUN-09:20 | 23.30 | 21.67 |
July | 0.627929E+10 | 11644.75 | 09-JUL-13:43 | 32.62 | 23.65 | 0.405565E+09 | 549.49 | 03-JUL-09:20 | 32.62 | 23.65 |
August | 0.738979E+10 | 12091.89 | 06-AUG-13:13 | 32.40 | 23.57 | 0.455472E+09 | 549.49 | 18-AUG-13:20 | 34.03 | 22.77 |
September | 0.571001E+10 | 10403.63 | 24-SEP-11:33 | 28.13 | 19.66 | 0.401426E+09 | 549.49 | 21-SEP-09:20 | 28.13 | 19.66 |
October | 0.483657E+10 | 12468.83 | 09-OCT-14:32 | 27.60 | 19.53 | 0.399816E+09 | 567.67 | 10-OCT-13:50 | 29.22 | 21.00 |
November | 0.332416E+10 | 12361.43 | 11-NOV-13:53 | 21.10 | 11.67 | 0.383310E+09 | 549.49 | 14-NOV-14:30 | 19.15 | 8.88 |
December | 0.221837E+10 | 6642.85 | 08-DEC-14:00 | 12.80 | 5.54 | 0.353902E+09 | 549.49 | 14-DEC-14:20 | 14.60 | 10.20 |
Annual Sum or Average | 0.515814E+11 | 0.475312E+10 | ||||||||
Minimum of Months | 0.136923E+10 | 4648.54 | 3.53 | -2.0 | 0.325376E+09 | 549.48 | 3.53 | -2.0 | ||
Maximum of Months | 0.738979E+10 | 12468.83 | 32.62 | 23.65 | 0.455472E+09 | 567.67 | 34.03 | 23.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.411366E+09 | 1105.38 | 20-JAN-16:40 | 16.87 | 11.91 | 0.201695E+09 | 331.72 | 11-JAN-16:00 | 16.87 | 11.91 |
February | 0.792858E+09 | 4174.81 | 27-FEB-17:00 | 22.20 | 11.44 | 0.192688E+09 | 347.84 | 28-FEB-14:20 | 25.00 | 13.71 |
March | 0.206458E+10 | 5975.96 | 30-MAR-16:00 | 27.80 | 17.47 | 0.259227E+09 | 347.85 | 30-MAR-09:20 | 27.80 | 17.47 |
April | 0.274159E+10 | 11190.91 | 09-APR-17:12 | 21.50 | 10.93 | 0.244130E+09 | 347.85 | 17-APR-09:20 | 20.93 | 14.77 |
May | 0.375504E+10 | 11619.36 | 21-MAY-16:42 | 26.70 | 19.84 | 0.274192E+09 | 347.85 | 17-MAY-09:20 | 26.70 | 19.84 |
June | 0.475426E+10 | 11908.62 | 11-JUN-16:22 | 32.50 | 21.22 | 0.275796E+09 | 347.85 | 09-JUN-09:20 | 32.50 | 21.22 |
July | 0.490378E+10 | 12117.96 | 23-JUL-17:52 | 28.90 | 22.63 | 0.256906E+09 | 347.85 | 03-JUL-09:20 | 28.90 | 22.63 |
August | 0.522133E+10 | 11862.77 | 13-AUG-16:51 | 31.10 | 22.45 | 0.288442E+09 | 347.84 | 21-AUG-09:20 | 23.50 | 22.59 |
September | 0.348771E+10 | 11243.97 | 04-SEP-16:12 | 27.97 | 22.70 | 0.253925E+09 | 347.85 | 21-SEP-09:20 | 21.33 | 17.87 |
October | 0.226139E+10 | 7927.85 | 09-OCT-15:13 | 27.80 | 19.57 | 0.246115E+09 | 347.85 | 10-OCT-09:20 | 21.50 | 18.02 |
November | 0.135643E+10 | 4086.84 | 06-NOV-15:50 | 20.60 | 10.48 | 0.227172E+09 | 347.84 | 14-NOV-14:30 | 19.15 | 8.88 |
December | 0.720489E+09 | 1776.18 | 11-DEC-15:40 | 21.10 | 15.44 | 0.203585E+09 | 347.84 | 12-DEC-14:30 | 22.80 | 16.62 |
Annual Sum or Average | 0.324708E+11 | 0.292387E+10 | ||||||||
Minimum of Months | 0.411366E+09 | 1105.38 | 16.87 | 10.48 | 0.192688E+09 | 331.72 | 16.87 | 8.88 | ||
Maximum of Months | 0.522133E+10 | 12117.96 | 32.50 | 22.70 | 0.288442E+09 | 347.85 | 32.50 | 22.63 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 27141116.93 | 13877.04 | 03-JAN-07:04 | 2.80 |
February | 1305990.42 | 13907.19 | 13-FEB-07:02 | -5.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 28447107.36 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 27141116.93 | 13907.19 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.374303E+10 | 12558.73 | 09-JAN-06:12 | -2.6 |
February | 0.236192E+10 | 13861.12 | 13-FEB-06:12 | -5.6 |
March | 0.766444E+09 | 5060.60 | 20-MAR-06:03 | 5.00 |
April | 0.455738E+09 | 5316.99 | 06-APR-05:02 | 0.18 |
May | 0.175059E+09 | 3003.42 | 10-MAY-05:03 | 8.98 |
June | 76468884.29 | 2633.73 | 08-JUN-05:03 | 11.70 |
July | 23478481.00 | 3064.98 | 15-JUL-05:03 | 23.98 |
August | 21862529.55 | 3949.42 | 10-AUG-05:03 | 24.40 |
September | 0.138413E+09 | 2558.19 | 29-SEP-05:03 | 12.30 |
October | 0.620397E+09 | 6008.29 | 26-OCT-06:03 | 2.20 |
November | 0.109059E+10 | 9961.45 | 22-NOV-07:02 | -3.2 |
December | 0.219012E+10 | 13060.85 | 18-DEC-06:13 | -5.0 |
Annual Sum or Average | 0.116635E+11 | |||
Minimum of Months | 21862529.55 | 2558.19 | -5.6 | |
Maximum of Months | 0.374303E+10 | 13861.12 | 24.40 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176940E+10 | 7679.25 | 09-JAN-07:11 | -3.3 |
February | 0.100155E+10 | 7141.06 | 13-FEB-07:11 | -5.6 |
March | 0.259604E+09 | 2163.33 | 26-MAR-13:33 | 18.53 |
April | 64523675.62 | 2584.44 | 09-APR-16:33 | 21.70 |
May | 10582677.18 | 1508.22 | 07-MAY-09:02 | 23.58 |
June | 8920929.48 | 1626.95 | 11-JUN-09:02 | 23.58 |
July | 13358822.34 | 1601.40 | 16-JUL-16:22 | 33.05 |
August | 11481160.36 | 2040.89 | 27-AUG-15:12 | 31.70 |
September | 10943780.91 | 1841.99 | 24-SEP-11:33 | 28.13 |
October | 0.166859E+09 | 2898.11 | 09-OCT-15:13 | 27.80 |
November | 0.481531E+09 | 3420.90 | 12-NOV-13:33 | 18.53 |
December | 0.101969E+10 | 4764.73 | 26-DEC-07:12 | 3.30 |
Annual Sum or Average | 0.481844E+10 | |||
Minimum of Months | 8920929.48 | 1508.22 | -5.6 | |
Maximum of Months | 0.176940E+10 | 7679.25 | 33.05 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139958E+10 | 5435.15 | 02-JAN-07:04 | 3.30 |
February | 0.789309E+09 | 4047.77 | 13-FEB-07:01 | -5.6 |
March | 0.111265E+09 | 2162.41 | 22-MAR-07:06 | 5.00 |
April | 14920746.12 | 1578.00 | 09-APR-16:27 | 21.70 |
May | 6822936.17 | 1257.82 | 14-MAY-10:07 | 22.07 |
June | 8364743.82 | 1255.83 | 11-JUN-07:27 | 20.85 |
July | 10083597.68 | 2570.15 | 07-JUL-04:03 | 25.22 |
August | 12731785.02 | 2740.92 | 04-AUG-04:03 | 23.90 |
September | 14481979.16 | 1654.67 | 03-SEP-12:30 | 27.50 |
October | 86506709.88 | 2062.87 | 08-OCT-15:23 | 27.20 |
November | 0.239464E+09 | 3073.32 | 22-NOV-08:07 | -2.2 |
December | 0.777441E+09 | 2783.87 | 01-DEC-08:16 | -2.4 |
Annual Sum or Average | 0.347098E+10 | |||
Minimum of Months | 6822936.17 | 1255.83 | -5.6 | |
Maximum of Months | 0.139958E+10 | 5435.15 | 27.50 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.474627E+09 | 16200.95 | 09-JAN-05:01 | -2.2 |
February | 0.152067E+09 | 15715.58 | 06-FEB-06:12 | 0.40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 221850.68 | 1139.89 | 24-NOV-07:03 | 8.30 |
December | 68315082.44 | 15093.21 | 18-DEC-07:12 | -5.2 |
Annual Sum or Average | 0.695231E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.2 | |
Maximum of Months | 0.474627E+09 | 16200.95 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217705E+10 | 31118.79 | 02-JAN-06:11 | 3.30 |
February | 0.954123E+09 | 30833.77 | 13-FEB-05:01 | -5.1 |
March | 20384409.89 | 24987.83 | 23-MAR-06:03 | 6.10 |
April | 821327.21 | 6844.39 | 07-APR-06:02 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 11977408.88 | 25138.87 | 30-OCT-06:03 | 8.90 |
November | 0.106741E+09 | 26594.19 | 22-NOV-06:01 | -3.3 |
December | 0.797341E+09 | 29643.65 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.406844E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.217705E+10 | 31118.79 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.356222E+10 | 10387.79 | 09-JAN-04:53 | -2.2 |
February | 0.199095E+10 | 10752.33 | 12-FEB-07:52 | -12.2 |
March | 0.187293E+09 | 8738.20 | 23-MAR-05:12 | 6.10 |
April | 46599677.21 | 8517.10 | 06-APR-05:02 | 0.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 77441870.60 | 8792.19 | 26-OCT-05:12 | 2.20 |
November | 0.499873E+09 | 9609.24 | 22-NOV-05:02 | -2.9 |
December | 0.171844E+10 | 10120.92 | 04-DEC-05:01 | -2.8 |
Annual Sum or Average | 0.808281E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.356222E+10 | 10752.33 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190448E+10 | 9776.77 | 09-JAN-04:53 | -2.2 |
February | 0.101862E+10 | 10117.81 | 12-FEB-05:12 | -11.9 |
March | 85829166.89 | 8297.55 | 23-MAR-05:12 | 6.10 |
April | 20307855.48 | 8039.75 | 06-APR-05:02 | 0.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 47101483.65 | 8320.86 | 26-OCT-05:12 | 2.20 |
November | 0.222279E+09 | 9082.79 | 22-NOV-05:02 | -2.9 |
December | 0.815706E+09 | 9613.70 | 04-DEC-05:01 | -2.8 |
Annual Sum or Average | 0.411432E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.9 | |
Maximum of Months | 0.190448E+10 | 10117.81 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.228080E+10 | 11938.94 | 09-JAN-04:53 | -2.2 |
February | 0.127228E+10 | 12277.88 | 12-FEB-05:12 | -11.9 |
March | 0.128085E+09 | 10070.29 | 23-MAR-05:12 | 6.10 |
April | 39703952.61 | 9739.54 | 06-APR-05:02 | 0.18 |
May | 217708.12 | 725.69 | 11-MAY-06:05 | 8.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 58862782.19 | 9955.22 | 26-OCT-05:12 | 2.20 |
November | 0.273661E+09 | 10852.75 | 22-NOV-05:02 | -2.9 |
December | 0.943706E+09 | 11595.74 | 04-DEC-05:01 | -2.8 |
Annual Sum or Average | 0.499732E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.9 | |
Maximum of Months | 0.228080E+10 | 12277.88 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.208852E+10 | 10315.37 | 09-JAN-04:53 | -2.2 |
February | 0.115757E+10 | 10786.39 | 12-FEB-07:52 | -12.2 |
March | 0.106189E+09 | 8612.88 | 23-MAR-05:12 | 6.10 |
April | 26287882.86 | 8194.56 | 06-APR-05:02 | 0.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 48054134.49 | 8586.00 | 26-OCT-05:12 | 2.20 |
November | 0.298063E+09 | 9561.50 | 22-NOV-05:02 | -2.9 |
December | 0.100334E+10 | 10182.77 | 04-DEC-05:01 | -2.8 |
Annual Sum or Average | 0.472803E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.208852E+10 | 10786.39 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189077E+10 | 7897.86 | 09-JAN-05:01 | -2.2 |
February | 0.936722E+09 | 8043.18 | 13-FEB-05:01 | -5.1 |
March | 46144614.76 | 6614.23 | 20-MAR-05:12 | 5.00 |
April | 12369383.66 | 6445.98 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 876928.89 | 3803.30 | 26-OCT-06:03 | 2.20 |
November | 24973769.38 | 6695.06 | 22-NOV-06:01 | -3.3 |
December | 0.350734E+09 | 7207.44 | 04-DEC-06:01 | -2.9 |
Annual Sum or Average | 0.326259E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.189077E+10 | 8043.18 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.942958E+09 | 7358.71 | 09-JAN-05:01 | -2.2 |
February | 0.397142E+09 | 7450.05 | 13-FEB-05:01 | -5.1 |
March | 17502781.06 | 5535.02 | 18-MAR-06:03 | 2.70 |
April | 3100838.51 | 5852.16 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 487284.16 | 1723.63 | 26-OCT-06:03 | 2.20 |
November | 5719387.36 | 5921.66 | 22-NOV-07:01 | -3.2 |
December | 0.131487E+09 | 6566.99 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.149840E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.942958E+09 | 7450.05 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.311199E+10 | 10136.62 | 09-JAN-08:00 | -3.3 |
February | 0.187413E+10 | 10356.98 | 03-FEB-07:10 | -8.9 |
March | 0.725939E+09 | 8343.61 | 06-MAR-07:50 | 2.80 |
April | 0.406385E+09 | 8731.27 | 06-APR-06:10 | 1.20 |
May | 96844890.43 | 7553.16 | 11-MAY-06:10 | 8.17 |
June | 10407781.38 | 5639.12 | 08-JUN-06:07 | 12.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 11301907.07 | 4165.69 | 14-SEP-06:07 | 12.30 |
October | 0.355604E+09 | 8343.19 | 26-OCT-07:00 | 2.20 |
November | 0.711454E+09 | 9198.31 | 22-NOV-07:10 | -3.2 |
December | 0.119456E+10 | 9717.91 | 18-DEC-07:10 | -5.1 |
Annual Sum or Average | 0.849861E+10 | |||
Minimum of Months | 0.00 | 0.00 | -8.9 | |
Maximum of Months | 0.311199E+10 | 10356.98 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.987339E+09 | 7392.92 | 09-JAN-05:01 | -2.2 |
February | 0.451769E+09 | 7409.95 | 13-FEB-05:01 | -5.1 |
March | 14399233.54 | 5456.74 | 23-MAR-06:03 | 6.10 |
April | 3369126.58 | 5817.02 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 230329.63 | 1535.53 | 31-OCT-06:03 | 8.22 |
November | 11079802.87 | 5899.42 | 22-NOV-07:01 | -3.2 |
December | 0.158110E+09 | 6572.72 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.162630E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.987339E+09 | 7409.95 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190046E+10 | 8607.28 | 02-JAN-06:11 | 3.30 |
February | 0.920056E+09 | 8770.45 | 13-FEB-05:01 | -5.1 |
March | 28960484.91 | 6904.60 | 23-MAR-06:03 | 6.10 |
April | 5639409.56 | 6950.68 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 8604731.43 | 6920.67 | 31-OCT-06:03 | 8.22 |
November | 0.108512E+09 | 7708.65 | 22-NOV-06:01 | -3.3 |
December | 0.626725E+09 | 8281.30 | 18-DEC-05:01 | -5.0 |
Annual Sum or Average | 0.359895E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.190046E+10 | 8770.45 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101136E+10 | 7770.45 | 09-JAN-05:01 | -2.2 |
February | 0.452218E+09 | 7991.45 | 13-FEB-05:01 | -5.1 |
March | 15649302.66 | 5538.72 | 18-MAR-06:03 | 2.70 |
April | 2798329.86 | 6306.29 | 07-APR-06:02 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 5940528.26 | 5537.47 | 26-OCT-06:03 | 2.20 |
November | 44055924.60 | 6831.18 | 22-NOV-06:01 | -3.3 |
December | 0.282771E+09 | 7444.47 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.181479E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.101136E+10 | 7991.45 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111208E+10 | 10159.11 | 02-JAN-06:11 | 3.30 |
February | 0.503845E+09 | 10230.11 | 13-FEB-05:01 | -5.1 |
March | 18322440.16 | 8117.50 | 23-MAR-06:03 | 6.10 |
April | 4445751.68 | 8183.79 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 7423539.83 | 8135.77 | 31-OCT-06:03 | 8.22 |
November | 49508721.65 | 8884.27 | 22-NOV-06:01 | -3.3 |
December | 0.303670E+09 | 9685.81 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.199930E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.111208E+10 | 10230.11 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108879E+10 | 7789.21 | 09-JAN-05:01 | -2.2 |
February | 0.513166E+09 | 7974.60 | 13-FEB-05:01 | -5.1 |
March | 16149811.21 | 5482.21 | 23-MAR-06:03 | 6.10 |
April | 3097011.65 | 5967.39 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 5922805.80 | 5436.58 | 26-OCT-06:03 | 2.20 |
November | 64838980.62 | 6829.31 | 22-NOV-06:01 | -3.3 |
December | 0.356961E+09 | 7462.73 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.204893E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.108879E+10 | 7974.60 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.621701E+09 | 950.03 | 03-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.560104E+09 | 1011.44 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.601732E+09 | 957.97 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.516580E+09 | 865.53 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.539682E+09 | 570.89 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.531085E+09 | 562.52 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.503002E+09 | 675.59 | 27-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.571568E+09 | 823.21 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.532828E+09 | 904.88 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.598181E+09 | 1038.01 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.601553E+09 | 1025.00 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.606438E+09 | 952.56 | 06-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.678446E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.503002E+09 | 562.52 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.621701E+09 | 1038.01 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.381030E+09 | 588.12 | 03-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.344466E+09 | 640.12 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.376158E+09 | 599.64 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.326188E+09 | 523.41 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.344041E+09 | 338.93 | 02-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.338944E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.320160E+09 | 362.00 | 27-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.362229E+09 | 493.31 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.334437E+09 | 555.99 | 29-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.366053E+09 | 657.13 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.373043E+09 | 643.36 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.372110E+09 | 589.92 | 06-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.423886E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.320160E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.381030E+09 | 657.13 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.586184E+09 | 936.67 | 03-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.535491E+09 | 1011.44 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.594583E+09 | 956.57 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.518448E+09 | 869.03 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.545919E+09 | 582.39 | 24-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.537539E+09 | 573.92 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.508833E+09 | 717.72 | 27-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.574766E+09 | 833.11 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.529757E+09 | 896.92 | 29-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.573051E+09 | 1038.01 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.574029E+09 | 1019.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.569357E+09 | 937.96 | 06-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.664796E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.508833E+09 | 573.92 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.594583E+09 | 1038.01 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.381858E+09 | 603.40 | 03-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.348211E+09 | 640.07 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.381215E+09 | 609.51 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.328317E+09 | 562.94 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.345332E+09 | 498.57 | 24-MAY-07:30 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.339498E+09 | 369.02 | 23-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.321841E+09 | 478.36 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.364292E+09 | 539.86 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.338538E+09 | 578.82 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.374689E+09 | 657.08 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.370521E+09 | 649.87 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.370858E+09 | 604.32 | 06-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.426517E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.321841E+09 | 369.02 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.381858E+09 | 657.08 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.617943E+09 | 946.55 | 03-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.556860E+09 | 1010.34 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.599850E+09 | 954.78 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.515537E+09 | 858.68 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.539643E+09 | 567.41 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.530785E+09 | 558.63 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.502609E+09 | 584.57 | 27-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.570834E+09 | 814.71 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.531435E+09 | 899.62 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.595446E+09 | 1037.91 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.598366E+09 | 1024.39 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.603024E+09 | 949.19 | 06-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.676233E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.502609E+09 | 558.63 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.617943E+09 | 1037.91 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379756E+09 | 585.72 | 03-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.343491E+09 | 639.54 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.375431E+09 | 597.68 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.325783E+09 | 518.60 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.343649E+09 | 335.77 | 02-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.338668E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.319779E+09 | 359.95 | 27-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.361880E+09 | 487.68 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.333853E+09 | 552.53 | 29-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.365116E+09 | 657.08 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.371974E+09 | 642.79 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.370931E+09 | 587.60 | 06-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.423031E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.319779E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.379756E+09 | 657.08 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.585062E+09 | 932.51 | 03-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.534720E+09 | 1010.34 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.593664E+09 | 953.32 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.517286E+09 | 862.34 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.545008E+09 | 579.67 | 24-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.536696E+09 | 570.78 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.508036E+09 | 705.22 | 27-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.573778E+09 | 825.09 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.528780E+09 | 891.27 | 29-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.571711E+09 | 1037.91 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.573121E+09 | 1018.74 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.567917E+09 | 933.85 | 06-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.663578E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.508036E+09 | 570.78 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.593664E+09 | 1037.91 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.380588E+09 | 601.69 | 03-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.346907E+09 | 639.50 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.380229E+09 | 608.00 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.327745E+09 | 560.01 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.344782E+09 | 493.97 | 24-MAY-07:30 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.338962E+09 | 367.49 | 23-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.321257E+09 | 472.85 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.363528E+09 | 536.22 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.337670E+09 | 576.37 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.373494E+09 | 657.03 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.369535E+09 | 649.60 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.369753E+09 | 602.64 | 06-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.425445E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.321257E+09 | 367.49 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.380588E+09 | 657.03 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.621697E+09 | 950.03 | 03-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.560101E+09 | 1011.44 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.601731E+09 | 957.96 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.516580E+09 | 865.52 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.539682E+09 | 570.88 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.531085E+09 | 562.51 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.503001E+09 | 675.55 | 27-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.571567E+09 | 823.19 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.532827E+09 | 904.86 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.598179E+09 | 1038.01 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.601550E+09 | 1025.00 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.606435E+09 | 952.55 | 06-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.678443E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.503001E+09 | 562.51 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.621697E+09 | 1038.01 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.381029E+09 | 588.11 | 03-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.344464E+09 | 640.11 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.376158E+09 | 599.63 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.326188E+09 | 523.40 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.344041E+09 | 338.92 | 02-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.338943E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.320160E+09 | 362.00 | 27-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.362228E+09 | 493.30 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.334436E+09 | 555.98 | 29-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.366052E+09 | 657.13 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.373042E+09 | 643.36 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.372109E+09 | 589.92 | 06-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.423885E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.320160E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.381029E+09 | 657.13 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.586183E+09 | 936.66 | 03-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.535489E+09 | 1011.44 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.594582E+09 | 956.57 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.518447E+09 | 869.01 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.545918E+09 | 582.38 | 24-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.537539E+09 | 573.91 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.508832E+09 | 717.69 | 27-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.574765E+09 | 833.09 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.529756E+09 | 896.91 | 29-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.573049E+09 | 1038.01 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.574028E+09 | 1019.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.569356E+09 | 937.95 | 06-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.664795E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.508832E+09 | 573.91 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.594582E+09 | 1038.01 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.381857E+09 | 603.39 | 03-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.348209E+09 | 640.07 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.381215E+09 | 609.50 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.328317E+09 | 562.93 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.345332E+09 | 498.55 | 24-MAY-07:30 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.339498E+09 | 369.01 | 23-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.321841E+09 | 478.34 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.364291E+09 | 539.84 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.338537E+09 | 578.82 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.374688E+09 | 657.08 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.370520E+09 | 649.87 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.370857E+09 | 604.32 | 06-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.426516E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.321841E+09 | 369.01 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.381857E+09 | 657.08 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.621701E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.999875E+09 |
February | 0.901968E+09 | 0.560104E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2136347.49 | 0.854613E+09 |
March | 0.107774E+10 | 0.601732E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2612663.24 | 0.554222E+09 |
April | 0.956342E+09 | 0.516580E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6597861.50 | 0.352500E+09 |
May | 0.103597E+10 | 0.539682E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17564000.84 | 0.233061E+09 |
June | 0.103308E+10 | 0.531085E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72773002.84 | 0.116579E+09 |
July | 0.959235E+09 | 0.503002E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78433894.40 | 77649193.51 |
August | 0.107774E+10 | 0.571568E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76262383.16 | 49278104.64 |
September | 0.956342E+09 | 0.532828E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22530135.55 | 0.116809E+09 |
October | 0.994195E+09 | 0.598181E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6870303.54 | 0.373653E+09 |
November | 0.984487E+09 | 0.601553E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 834457.36 | 0.526955E+09 |
December | 0.959235E+09 | 0.606438E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894103E+09 |
Annual Sum or Average | 0.119305E+11 | 0.678446E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286615E+09 | 0.514930E+10 |
Minimum of Months | 0.901968E+09 | 0.503002E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49278104.64 |
Maximum of Months | 0.107774E+10 | 0.621701E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78433894.40 | 0.999875E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.381030E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674762E+09 |
February | 0.571020E+09 | 0.344466E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 501756.97 | 0.582583E+09 |
March | 0.682301E+09 | 0.376158E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1529835.87 | 0.386889E+09 |
April | 0.605444E+09 | 0.326188E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3403253.12 | 0.245112E+09 |
May | 0.655854E+09 | 0.344041E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10159316.82 | 0.163452E+09 |
June | 0.654023E+09 | 0.338944E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47028695.49 | 80047718.32 |
July | 0.607275E+09 | 0.320160E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50073328.29 | 53943978.89 |
August | 0.682301E+09 | 0.362229E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49142249.12 | 34279696.61 |
September | 0.605444E+09 | 0.334437E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13246233.87 | 80101570.57 |
October | 0.629407E+09 | 0.366053E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3122108.11 | 0.259546E+09 |
November | 0.623262E+09 | 0.373043E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 452095.58 | 0.362996E+09 |
December | 0.607275E+09 | 0.372110E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602555E+09 |
Annual Sum or Average | 0.755301E+10 | 0.423886E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178659E+09 | 0.352627E+10 |
Minimum of Months | 0.571020E+09 | 0.320160E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34279696.61 |
Maximum of Months | 0.682301E+09 | 0.381030E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50073328.29 | 0.674762E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.586184E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106001E+10 |
February | 0.901968E+09 | 0.535491E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114308.27 | 0.911351E+09 |
March | 0.107774E+10 | 0.594583E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1986304.43 | 0.607077E+09 |
April | 0.956342E+09 | 0.518448E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4914989.58 | 0.366846E+09 |
May | 0.103597E+10 | 0.545919E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16114670.67 | 0.235458E+09 |
June | 0.103308E+10 | 0.537539E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72438370.64 | 0.115273E+09 |
July | 0.959235E+09 | 0.508833E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77704677.19 | 77389707.15 |
August | 0.107774E+10 | 0.574766E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74123915.50 | 50876237.15 |
September | 0.956342E+09 | 0.529757E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18849285.57 | 0.121723E+09 |
October | 0.994195E+09 | 0.573051E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3043901.30 | 0.408478E+09 |
November | 0.984487E+09 | 0.574029E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583470E+09 |
December | 0.959235E+09 | 0.569357E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951141E+09 |
Annual Sum or Average | 0.119305E+11 | 0.664796E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269290E+09 | 0.548909E+10 |
Minimum of Months | 0.901968E+09 | 0.508833E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50876237.15 |
Maximum of Months | 0.107774E+10 | 0.594583E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77704677.19 | 0.106001E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.381858E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677680E+09 |
February | 0.570983E+09 | 0.348211E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 690699.60 | 0.583736E+09 |
March | 0.682256E+09 | 0.381215E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1335018.64 | 0.396190E+09 |
April | 0.605404E+09 | 0.328317E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3581433.16 | 0.247562E+09 |
May | 0.655811E+09 | 0.345332E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10419316.90 | 0.162972E+09 |
June | 0.653980E+09 | 0.339498E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46628979.35 | 81184190.03 |
July | 0.607235E+09 | 0.321841E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49983878.21 | 54079913.34 |
August | 0.682256E+09 | 0.364292E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47875391.92 | 36543713.72 |
September | 0.605404E+09 | 0.338538E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13353347.24 | 82043294.65 |
October | 0.629366E+09 | 0.374689E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2752848.15 | 0.261841E+09 |
November | 0.623221E+09 | 0.370521E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1099.58 | 0.365473E+09 |
December | 0.607235E+09 | 0.370858E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605048E+09 |
Annual Sum or Average | 0.755252E+10 | 0.426517E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176622E+09 | 0.355435E+10 |
Minimum of Months | 0.570983E+09 | 0.321841E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36543713.72 |
Maximum of Months | 0.682256E+09 | 0.381858E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49983878.21 | 0.677680E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.617943E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571079E+09 |
February | 0.901968E+09 | 0.556860E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1281543.29 | 0.477841E+09 |
March | 0.107774E+10 | 0.599850E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2163638.52 | 0.296052E+09 |
April | 0.956342E+09 | 0.515537E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5293319.26 | 0.177438E+09 |
May | 0.103597E+10 | 0.539643E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11193070.23 | 0.117536E+09 |
June | 0.103308E+10 | 0.530785E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42103250.13 | 59370319.99 |
July | 0.959235E+09 | 0.502609E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46118734.94 | 40005024.39 |
August | 0.107774E+10 | 0.570834E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43808128.00 | 25349545.57 |
September | 0.956342E+09 | 0.531435E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12632327.48 | 69197688.55 |
October | 0.994195E+09 | 0.595446E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3573601.48 | 0.227253E+09 |
November | 0.984487E+09 | 0.598366E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85837.69 | 0.323340E+09 |
December | 0.959235E+09 | 0.603024E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543313E+09 |
Annual Sum or Average | 0.119305E+11 | 0.676233E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168253E+09 | 0.292777E+10 |
Minimum of Months | 0.901968E+09 | 0.502609E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25349545.57 |
Maximum of Months | 0.107774E+10 | 0.617943E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46118734.94 | 0.571079E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.379756E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387487E+09 |
February | 0.571020E+09 | 0.343491E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 303577.75 | 0.328993E+09 |
March | 0.682301E+09 | 0.375431E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1080551.61 | 0.212367E+09 |
April | 0.605444E+09 | 0.325783E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2319663.70 | 0.127658E+09 |
May | 0.655854E+09 | 0.343649E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6041790.12 | 85809012.53 |
June | 0.654023E+09 | 0.338668E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26153153.26 | 42482563.80 |
July | 0.607275E+09 | 0.319779E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27931096.56 | 29108942.67 |
August | 0.682301E+09 | 0.361880E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27051256.44 | 18964576.12 |
September | 0.605444E+09 | 0.333853E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7387202.84 | 48295393.79 |
October | 0.629407E+09 | 0.365116E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1603472.53 | 0.159653E+09 |
November | 0.623262E+09 | 0.371974E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10309.42 | 0.226182E+09 |
December | 0.607275E+09 | 0.370931E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369352E+09 |
Annual Sum or Average | 0.755301E+10 | 0.423031E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99882074.23 | 0.203635E+10 |
Minimum of Months | 0.571020E+09 | 0.319779E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18964576.12 |
Maximum of Months | 0.682301E+09 | 0.379756E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27931096.56 | 0.387487E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.585062E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461145E+10 |
February | 0.901968E+09 | 0.534720E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 656339.49 | 0.341695E+10 |
March | 0.107774E+10 | 0.593664E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27437418.96 | 0.245084E+10 |
April | 0.956342E+09 | 0.517286E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141996E+09 | 0.138917E+10 |
May | 0.103597E+10 | 0.545008E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338756E+09 | 0.751833E+09 |
June | 0.103308E+10 | 0.536696E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961207E+09 | 0.289747E+09 |
July | 0.959235E+09 | 0.508036E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.995641E+09 | 0.216737E+09 |
August | 0.107774E+10 | 0.573778E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109833E+10 | 0.135248E+09 |
September | 0.956342E+09 | 0.528780E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376685E+09 | 0.501286E+09 |
October | 0.994195E+09 | 0.571711E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68445595.86 | 0.190237E+10 |
November | 0.984487E+09 | 0.573121E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288630E+10 |
December | 0.959235E+09 | 0.567917E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352743E+10 |
Annual Sum or Average | 0.119305E+11 | 0.663578E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400916E+10 | 0.220794E+11 |
Minimum of Months | 0.901968E+09 | 0.508036E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135248E+09 |
Maximum of Months | 0.107774E+10 | 0.593664E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109833E+10 | 0.461145E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.380588E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388689E+09 |
February | 0.570983E+09 | 0.346907E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 360142.13 | 0.328442E+09 |
March | 0.682256E+09 | 0.380229E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 809733.50 | 0.217695E+09 |
April | 0.605404E+09 | 0.327745E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2173237.52 | 0.130020E+09 |
May | 0.655811E+09 | 0.344782E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5797060.06 | 85937200.99 |
June | 0.653980E+09 | 0.338962E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25690606.17 | 43306810.77 |
July | 0.607235E+09 | 0.321257E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27796331.61 | 29099934.38 |
August | 0.682256E+09 | 0.363528E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26173476.38 | 20362927.89 |
September | 0.605404E+09 | 0.337670E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7227622.30 | 49523419.42 |
October | 0.629366E+09 | 0.373494E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1355804.93 | 0.161504E+09 |
November | 0.623221E+09 | 0.369535E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227018E+09 |
December | 0.607235E+09 | 0.369753E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369319E+09 |
Annual Sum or Average | 0.755252E+10 | 0.425445E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97384014.61 | 0.205092E+10 |
Minimum of Months | 0.570983E+09 | 0.321257E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20362927.89 |
Maximum of Months | 0.682256E+09 | 0.380588E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27796331.61 | 0.388689E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.621697E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877004E+09 |
February | 0.901968E+09 | 0.560101E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1595079.41 | 0.749073E+09 |
March | 0.107774E+10 | 0.601731E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2200810.79 | 0.493484E+09 |
April | 0.956342E+09 | 0.516580E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5919216.83 | 0.308944E+09 |
May | 0.103597E+10 | 0.539682E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15335198.38 | 0.202421E+09 |
June | 0.103308E+10 | 0.531085E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62838653.05 | 0.100127E+09 |
July | 0.959235E+09 | 0.503001E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68103497.97 | 66455359.86 |
August | 0.107774E+10 | 0.571567E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65735076.45 | 42215944.93 |
September | 0.956342E+09 | 0.532827E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19361127.67 | 0.104744E+09 |
October | 0.994195E+09 | 0.598179E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5599359.59 | 0.339083E+09 |
November | 0.984487E+09 | 0.601550E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 279389.62 | 0.481054E+09 |
December | 0.959235E+09 | 0.606435E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.810493E+09 |
Annual Sum or Average | 0.119305E+11 | 0.678443E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246967E+09 | 0.457510E+10 |
Minimum of Months | 0.901968E+09 | 0.503001E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42215944.93 |
Maximum of Months | 0.107774E+10 | 0.621697E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68103497.97 | 0.877004E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.381029E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593323E+09 |
February | 0.421807E+09 | 0.344464E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 341473.46 | 0.512447E+09 |
March | 0.502994E+09 | 0.376158E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1218330.27 | 0.344769E+09 |
April | 0.447140E+09 | 0.326188E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2888112.59 | 0.214375E+09 |
May | 0.484071E+09 | 0.344041E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8560822.45 | 0.141772E+09 |
June | 0.482240E+09 | 0.338943E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39334513.66 | 68785241.73 |
July | 0.448971E+09 | 0.320160E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42331191.74 | 46332195.79 |
August | 0.502994E+09 | 0.362228E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41124043.90 | 29528333.51 |
September | 0.447140E+09 | 0.334436E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11051281.56 | 72054335.70 |
October | 0.465148E+09 | 0.366052E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2581590.30 | 0.235095E+09 |
November | 0.460569E+09 | 0.373042E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 126267.48 | 0.332535E+09 |
December | 0.448971E+09 | 0.372109E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548676E+09 |
Annual Sum or Average | 0.557719E+10 | 0.423885E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149558E+09 | 0.313969E+10 |
Minimum of Months | 0.421807E+09 | 0.320160E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29528333.51 |
Maximum of Months | 0.502994E+09 | 0.381029E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42331191.74 | 0.593323E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.586183E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.933697E+09 |
February | 0.901968E+09 | 0.535489E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98652.68 | 0.800978E+09 |
March | 0.107774E+10 | 0.594582E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1691845.24 | 0.536289E+09 |
April | 0.956342E+09 | 0.518447E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4303992.06 | 0.320301E+09 |
May | 0.103597E+10 | 0.545918E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14094046.43 | 0.204367E+09 |
June | 0.103308E+10 | 0.537539E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62322237.46 | 99162462.44 |
July | 0.959235E+09 | 0.508832E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67010458.52 | 66318347.25 |
August | 0.107774E+10 | 0.574765E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63075703.95 | 43651089.27 |
September | 0.956342E+09 | 0.529756E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15983301.48 | 0.108669E+09 |
October | 0.994195E+09 | 0.573049E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2556303.81 | 0.366066E+09 |
November | 0.984487E+09 | 0.574028E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527208E+09 |
December | 0.959235E+09 | 0.569356E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862133E+09 |
Annual Sum or Average | 0.119305E+11 | 0.664795E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231137E+09 | 0.486884E+10 |
Minimum of Months | 0.901968E+09 | 0.508832E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43651089.27 |
Maximum of Months | 0.107774E+10 | 0.594582E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67010458.52 | 0.933697E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.381857E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594610E+09 |
February | 0.570983E+09 | 0.348209E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 479197.30 | 0.511786E+09 |
March | 0.682256E+09 | 0.381215E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1123902.84 | 0.350672E+09 |
April | 0.605404E+09 | 0.328317E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3052789.12 | 0.216305E+09 |
May | 0.655811E+09 | 0.345332E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8818038.37 | 0.141400E+09 |
June | 0.653980E+09 | 0.339498E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39454972.75 | 69742419.98 |
July | 0.607235E+09 | 0.321841E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42440789.33 | 46312786.13 |
August | 0.682256E+09 | 0.364291E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40436636.79 | 31297265.47 |
September | 0.605404E+09 | 0.338537E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11262956.73 | 73235394.85 |
October | 0.629366E+09 | 0.374688E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2240487.90 | 0.236109E+09 |
November | 0.623221E+09 | 0.370520E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332207E+09 |
December | 0.607235E+09 | 0.370857E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547863E+09 |
Annual Sum or Average | 0.755252E+10 | 0.426516E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149310E+09 | 0.315154E+10 |
Minimum of Months | 0.570983E+09 | 0.321841E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31297265.47 |
Maximum of Months | 0.682256E+09 | 0.381857E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42440789.33 | 0.594610E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124810E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 641565.08 | 0.107596E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1644243.38 | 0.713617E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5112027.65 | 0.430342E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15312031.95 | 0.277267E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70780359.53 | 0.132563E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79742634.07 | 87351172.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73341604.06 | 54748452.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18436077.27 | 0.149811E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3644621.78 | 0.501182E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205230.32 | 0.716805E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119419E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268860E+09 | 0.658194E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54748452.18 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79742634.07 | 0.124810E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151347E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1758508.97 | 0.130559E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2460337.76 | 0.878422E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7469970.68 | 0.542493E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20262315.66 | 0.353825E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90692352.98 | 0.170670E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101623E+09 | 0.111916E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93782265.64 | 70345209.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25137891.41 | 0.183381E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5883734.82 | 0.600443E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1416365.18 | 0.848070E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141658E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350487E+09 | 0.799520E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70345209.48 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101623E+09 | 0.151347E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149554E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5284.02 | 0.129168E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 924049.44 | 0.878185E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1986272.91 | 0.553798E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10363382.14 | 0.362553E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73575997.24 | 0.165299E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83354627.14 | 0.111444E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80339683.11 | 66178085.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17319689.18 | 0.175992E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2098223.46 | 0.586752E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375697.77 | 0.816091E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135516E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270343E+09 | 0.785867E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66178085.27 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83354627.14 | 0.149554E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 950.03 | 03-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1966.85 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1011.44 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 151.93 | 26-FEB-13:00 | 2420.64 | 12-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 957.97 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 69.12 | 11-MAR-16:00 | 1342.11 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 865.53 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.67 | 16-APR-12:00 | 774.07 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 570.89 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.90 | 07-MAY-12:20 | 614.35 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 562.52 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 381.27 | 11-JUN-15:00 | 455.17 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 675.59 | 27-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.40 | 08-JUL-18:53 | 329.59 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 823.21 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 369.41 | 06-AUG-13:52 | 212.40 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 904.88 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.83 | 24-SEP-12:57 | 410.46 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1038.01 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.86 | 08-OCT-14:00 | 806.49 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1025.00 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.43 | 19-NOV-15:00 | 1378.51 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 952.56 | 06-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1956.31 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 562.52 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.40 | |||||
Maximum of Months | 1306.65 | 1038.01 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 381.27 | 2420.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 588.12 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1306.81 | 07-JAN-18:05 |
February | 827.22 | 01-FEB-10:09 | 640.12 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.72 | 26-FEB-15:30 | 1613.75 | 12-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 599.64 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.20 | 30-MAR-16:00 | 886.88 | 22-MAR-03:00 |
April | 827.22 | 03-APR-09:09 | 523.41 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.31 | 16-APR-14:00 | 514.55 | 05-APR-05:00 |
May | 827.22 | 01-MAY-09:09 | 338.93 | 02-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.93 | 29-MAY-17:50 | 408.25 | 10-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.18 | 25-JUN-16:25 | 304.41 | 07-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 362.00 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.46 | 08-JUL-19:10 | 219.27 | 01-JUL-20:00 |
August | 827.22 | 01-AUG-09:09 | 493.31 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.74 | 06-AUG-14:08 | 140.29 | 25-AUG-05:00 |
September | 827.22 | 01-SEP-09:09 | 555.99 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.42 | 17-SEP-15:00 | 271.85 | 29-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 657.13 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.58 | 09-OCT-16:00 | 537.06 | 28-OCT-04:00 |
November | 827.22 | 01-NOV-09:09 | 643.36 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.94 | 19-NOV-15:00 | 917.69 | 30-NOV-22:03 |
December | 827.22 | 01-DEC-10:09 | 589.92 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1298.48 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.29 | |||||
Maximum of Months | 827.22 | 657.13 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 244.74 | 1613.75 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 936.67 | 03-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1989.51 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1011.44 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 | 28-FEB-15:00 | 2437.28 | 11-FEB-18:03 |
March | 1306.65 | 01-MAR-10:09 | 956.57 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.79 | 30-MAR-16:00 | 1349.23 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 869.03 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.09 | 16-APR-13:57 | 776.11 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 582.39 | 24-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.75 | 29-MAY-17:50 | 617.32 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 573.92 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 351.55 | 11-JUN-15:00 | 456.04 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 717.72 | 27-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.81 | 08-JUL-19:10 | 330.14 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 833.11 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 363.29 | 06-AUG-14:05 | 213.64 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 896.92 | 29-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.19 | 17-SEP-14:50 | 411.88 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1038.01 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.60 | 09-OCT-15:38 | 834.05 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1019.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1378.98 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 937.96 | 06-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1990.11 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 573.92 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.64 | |||||
Maximum of Months | 1306.65 | 1038.01 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 363.29 | 2437.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 603.40 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1319.57 | 07-JAN-18:05 |
February | 827.17 | 01-FEB-10:09 | 640.07 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 93.24 | 26-FEB-13:00 | 1678.75 | 11-FEB-18:03 |
March | 827.17 | 01-MAR-10:09 | 609.51 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.20 | 30-MAR-16:00 | 891.90 | 22-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 562.94 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.69 | 16-APR-12:00 | 512.27 | 05-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 498.57 | 24-MAY-07:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.22 | 07-MAY-12:17 | 415.51 | 10-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 369.02 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.80 | 25-JUN-16:00 | 308.15 | 07-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 478.36 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.52 | 08-JUL-19:10 | 222.20 | 28-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 539.86 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.39 | 06-AUG-14:05 | 144.22 | 25-AUG-05:00 |
September | 827.17 | 01-SEP-09:09 | 578.82 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.49 | 24-SEP-12:53 | 271.66 | 29-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 657.08 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.43 | 08-OCT-13:43 | 541.84 | 28-OCT-04:00 |
November | 827.17 | 01-NOV-09:09 | 649.87 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 19-NOV-15:00 | 918.30 | 30-NOV-22:03 |
December | 827.17 | 01-DEC-10:09 | 604.32 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1296.19 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 369.02 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.22 | |||||
Maximum of Months | 827.17 | 657.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 241.39 | 1678.75 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 946.55 | 03-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1096.27 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1010.34 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 78.88 | 26-FEB-13:20 | 1324.89 | 12-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 954.78 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 57.04 | 11-MAR-18:05 | 785.11 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 858.68 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.05 | 16-APR-11:53 | 412.71 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 567.41 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.62 | 07-MAY-11:53 | 348.22 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 558.63 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 243.56 | 11-JUN-15:00 | 247.26 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 584.57 | 27-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.59 | 08-JUL-18:53 | 183.10 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 814.71 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.95 | 06-AUG-13:52 | 121.54 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 899.62 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.32 | 17-SEP-15:00 | 256.05 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1037.91 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.55 | 08-OCT-13:53 | 504.12 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1024.39 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 19-NOV-15:00 | 751.25 | 21-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 949.19 | 06-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1263.41 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 558.63 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.54 | |||||
Maximum of Months | 1306.65 | 1037.91 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 243.56 | 1324.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 585.72 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 729.65 | 07-JAN-18:05 |
February | 827.22 | 01-FEB-10:09 | 639.54 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.78 | 26-FEB-16:00 | 880.73 | 12-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 597.68 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.62 | 11-MAR-16:00 | 532.44 | 22-MAR-03:00 |
April | 827.22 | 03-APR-09:09 | 518.60 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.94 | 08-APR-17:03 | 275.36 | 05-APR-05:00 |
May | 827.22 | 01-MAY-09:09 | 335.77 | 02-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.14 | 29-MAY-18:00 | 237.17 | 10-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.17 | 11-JUN-15:00 | 170.52 | 07-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 359.95 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.12 | 08-JUL-18:53 | 121.36 | 28-JUL-22:00 |
August | 827.22 | 01-AUG-09:09 | 487.68 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.05 | 06-AUG-14:08 | 81.04 | 25-AUG-05:00 |
September | 827.22 | 01-SEP-09:09 | 552.53 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.95 | 17-SEP-15:00 | 170.26 | 29-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 657.08 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.79 | 09-OCT-16:00 | 345.09 | 28-OCT-04:00 |
November | 827.22 | 01-NOV-09:09 | 642.79 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | 19-NOV-15:00 | 509.54 | 07-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 587.60 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 845.51 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.04 | |||||
Maximum of Months | 827.22 | 657.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 136.17 | 880.73 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 932.51 | 03-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 23158.94 | 27-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1010.34 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 115.15 | 28-FEB-15:00 | 25112.62 | 03-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 953.32 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2827.75 | 30-MAR-16:10 | 14362.33 | 06-MAR-07:03 |
April | 1306.65 | 03-APR-09:09 | 862.34 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3719.93 | 17-APR-16:10 | 15720.05 | 06-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 579.67 | 24-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5114.21 | 19-MAY-16:10 | 10395.76 | 11-MAY-06:05 |
June | 1306.65 | 01-JUN-09:09 | 570.78 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7190.09 | 06-JUN-16:05 | 7409.26 | 08-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 705.22 | 27-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8376.35 | 07-JUL-16:03 | 3625.56 | 03-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 825.09 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8017.71 | 01-AUG-16:03 | 3774.36 | 25-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 891.27 | 29-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5412.49 | 07-SEP-16:03 | 8121.12 | 14-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 1037.91 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3923.94 | 10-OCT-16:05 | 14888.15 | 26-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 1018.74 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 19679.77 | 22-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 933.85 | 06-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 21611.38 | 18-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 570.78 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3625.56 | |||||
Maximum of Months | 1306.65 | 1037.91 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8376.35 | 25112.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 601.69 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 734.19 | 07-JAN-18:05 |
February | 827.17 | 01-FEB-10:09 | 639.50 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.24 | 26-FEB-13:20 | 914.49 | 11-FEB-18:03 |
March | 827.17 | 01-MAR-10:09 | 608.00 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 | 30-MAR-16:00 | 535.12 | 22-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 560.01 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.88 | 16-APR-11:53 | 275.38 | 05-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 493.97 | 24-MAY-07:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 07-MAY-11:53 | 241.47 | 10-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 367.49 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.76 | 25-JUN-15:55 | 172.85 | 07-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 472.85 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.46 | 08-JUL-18:53 | 123.38 | 28-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 536.22 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.63 | 06-AUG-13:52 | 84.74 | 25-AUG-05:00 |
September | 827.17 | 01-SEP-09:09 | 576.37 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.05 | 24-SEP-13:00 | 170.36 | 29-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 657.03 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.34 | 08-OCT-13:53 | 347.15 | 28-OCT-04:00 |
November | 827.17 | 01-NOV-09:09 | 649.60 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 516.10 | 07-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 602.64 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 841.16 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 367.49 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.74 | |||||
Maximum of Months | 827.17 | 657.03 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 136.63 | 914.49 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 950.03 | 03-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1692.90 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1011.44 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 109.38 | 26-FEB-13:00 | 1988.61 | 11-FEB-19:00 |
March | 1306.65 | 01-MAR-10:09 | 957.96 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.26 | 11-MAR-16:00 | 1237.02 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 865.52 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.41 | 16-APR-11:53 | 684.90 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 570.88 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.22 | 07-MAY-11:57 | 552.29 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 562.51 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 345.57 | 11-JUN-14:53 | 394.30 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 675.55 | 27-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 316.48 | 08-JUL-18:53 | 285.74 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 823.19 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.41 | 06-AUG-14:00 | 189.62 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 904.86 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.15 | 17-SEP-15:00 | 378.42 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1038.01 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.73 | 08-OCT-14:00 | 745.54 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1025.00 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.69 | 19-NOV-15:00 | 1157.78 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 952.55 | 06-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1825.95 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 562.51 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.62 | |||||
Maximum of Months | 1306.65 | 1038.01 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 345.57 | 1988.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 588.11 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1123.13 | 07-JAN-18:05 |
February | 805.43 | 01-FEB-08:09 | 640.11 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.96 | 26-FEB-15:10 | 1324.63 | 11-FEB-18:03 |
March | 805.43 | 01-MAR-08:09 | 599.63 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.85 | 30-MAR-16:00 | 818.78 | 22-MAR-03:00 |
April | 805.43 | 03-APR-07:10 | 523.40 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.81 | 08-APR-17:03 | 455.61 | 05-APR-05:00 |
May | 805.43 | 01-MAY-07:10 | 338.92 | 02-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.81 | 29-MAY-18:00 | 367.23 | 10-MAY-04:00 |
June | 805.43 | 01-JUN-07:10 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.32 | 11-JUN-15:10 | 263.92 | 07-JUN-03:00 |
July | 805.43 | 03-JUL-07:10 | 362.00 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.15 | 08-JUL-18:53 | 189.37 | 28-JUL-22:00 |
August | 805.43 | 01-AUG-07:10 | 493.30 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.64 | 06-AUG-13:56 | 125.46 | 25-AUG-05:00 |
September | 805.43 | 01-SEP-07:10 | 555.98 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.34 | 17-SEP-15:00 | 250.88 | 29-SEP-05:00 |
October | 805.43 | 02-OCT-07:10 | 657.13 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.84 | 09-OCT-16:00 | 496.84 | 28-OCT-04:00 |
November | 805.43 | 01-NOV-07:10 | 643.36 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.48 | 19-NOV-15:00 | 771.02 | 30-NOV-22:03 |
December | 805.43 | 01-DEC-08:09 | 589.92 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1212.94 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.46 | |||||
Maximum of Months | 805.43 | 657.13 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 224.64 | 1324.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 936.66 | 03-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1710.96 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1011.44 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.31 | 28-FEB-15:00 | 2086.03 | 11-FEB-18:03 |
March | 1306.65 | 01-MAR-10:09 | 956.57 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.28 | 30-MAR-16:00 | 1243.43 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 869.01 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.07 | 08-APR-17:20 | 686.77 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 582.38 | 24-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.53 | 07-MAY-12:03 | 554.76 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 573.91 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.47 | 11-JUN-14:53 | 394.98 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 717.69 | 27-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 311.56 | 08-JUL-18:53 | 286.20 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 833.09 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.19 | 06-AUG-13:54 | 190.68 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 896.91 | 29-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.99 | 17-SEP-14:50 | 379.59 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1038.01 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.23 | 09-OCT-15:57 | 766.76 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1019.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1158.42 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 937.95 | 06-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1856.77 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 573.91 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.68 | |||||
Maximum of Months | 1306.65 | 1038.01 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 329.19 | 2086.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 603.39 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1134.68 | 07-JAN-18:05 |
February | 827.17 | 01-FEB-10:09 | 640.07 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 66.56 | 26-FEB-12:55 | 1436.21 | 11-FEB-18:03 |
March | 827.17 | 01-MAR-10:09 | 609.50 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.85 | 30-MAR-16:00 | 822.29 | 22-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 562.93 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.93 | 16-APR-11:53 | 453.63 | 05-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 498.55 | 24-MAY-07:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.44 | 07-MAY-11:57 | 373.04 | 10-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 369.01 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.72 | 25-JUN-15:58 | 266.78 | 07-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 478.34 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.54 | 08-JUL-19:10 | 192.26 | 28-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 539.84 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.60 | 06-AUG-13:56 | 128.54 | 25-AUG-05:00 |
September | 827.17 | 01-SEP-09:09 | 578.82 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.98 | 24-SEP-13:00 | 250.44 | 29-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 657.08 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.60 | 08-OCT-13:53 | 499.80 | 28-OCT-04:00 |
November | 827.17 | 01-NOV-09:09 | 649.87 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 771.31 | 30-NOV-22:03 |
December | 827.17 | 01-DEC-10:09 | 604.32 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1209.68 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 369.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.54 | |||||
Maximum of Months | 827.17 | 657.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 216.60 | 1436.21 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2388.01 | 07-JAN-18:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.19 | 26-FEB-14:43 | 2931.40 | 12-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.94 | 11-MAR-16:00 | 1832.55 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.93 | 16-APR-11:53 | 958.77 | 05-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.29 | 07-MAY-12:00 | 785.67 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.26 | 11-JUN-15:00 | 538.92 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.79 | 08-JUL-18:53 | 385.63 | 28-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.76 | 06-AUG-13:52 | 260.50 | 25-AUG-05:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.86 | 17-SEP-15:00 | 546.69 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.36 | 09-OCT-15:43 | 1108.89 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.48 | 19-NOV-15:00 | 1634.49 | 07-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2771.19 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.50 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.26 | 2931.40 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2981.92 | 07-JAN-18:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.79 | 26-FEB-13:17 | 3619.81 | 12-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.12 | 11-MAR-16:00 | 2240.55 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.94 | 16-APR-12:00 | 1217.82 | 05-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.97 | 07-MAY-12:10 | 996.56 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 575.10 | 11-JUN-14:53 | 689.42 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.98 | 08-JUL-18:53 | 487.37 | 28-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554.27 | 06-AUG-14:00 | 329.16 | 25-AUG-05:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.96 | 17-SEP-15:00 | 676.98 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.80 | 08-OCT-13:53 | 1330.19 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.53 | 19-NOV-15:00 | 2003.64 | 07-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3324.36 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.16 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 575.10 | 3619.81 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3174.32 | 07-JAN-18:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 | 26-FEB-15:00 | 3798.68 | 11-FEB-18:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.79 | 30-MAR-16:00 | 2044.04 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.38 | 16-APR-12:15 | 1161.20 | 05-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.55 | 19-MAY-13:00 | 894.43 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.37 | 11-JUN-15:00 | 677.09 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.57 | 08-JUL-18:50 | 525.75 | 01-JUL-20:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.16 | 06-AUG-13:52 | 315.57 | 23-AUG-05:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.55 | 06-SEP-12:00 | 585.92 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.25 | 09-OCT-16:00 | 1224.65 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.34 | 19-NOV-15:00 | 1998.53 | 30-NOV-22:03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2988.88 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.57 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.57 | 3798.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11851.28 | 31-JAN-17:00 | 6035.01 | 4936.01 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17505.92 | 23-FEB-08:07 | 36210.05 | 29616.09 | 109111.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20897.80 | 31-MAR-08:00 | 6035.01 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 25945.66 | 18-APR-06:03 | 5082.11 | 6581.44 | 35187.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39947.22 | 30-MAY-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 40394.88 | 19-JUN-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41100.19 | 07-JUL-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 41091.20 | 03-AUG-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 39984.12 | 06-SEP-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35958.92 | 10-OCT-06:02 | 6352.64 | 8226.80 | 43983.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19539.49 | 06-NOV-09:00 | 6035.01 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19764.31 | 15-DEC-08:04 | 48280.06 | 39488.12 | 145481.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11851.28 | 0.00 | 846.94 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41100.19 | 48280.06 | 39488.12 | 145481.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1079.44 | 28-JAN-17:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.34 |
February | 3139.37 | 28-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.04 |
March | 6765.28 | 30-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.65 | 0.00 |
April | 7724.71 | 17-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.98 | 0.00 |
May | 8546.04 | 30-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.54 | 0.00 |
June | 9169.35 | 12-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.52 | 0.00 |
July | 10082.19 | 07-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.57 | 0.00 |
August | 10247.23 | 01-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.68 | 0.00 |
September | 8790.75 | 06-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.77 | 0.00 |
October | 6839.98 | 10-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.68 | 0.00 |
November | 2670.84 | 06-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.74 |
December | 1800.08 | 10-DEC-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1079.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10247.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.52 | 159.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1727.92 | 14-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1593.88 |
February | 1991.93 | 23-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.53 |
March | 2274.30 | 30-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.76 | 0.00 |
April | 3047.43 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.47 |
May | 3695.41 | 30-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.83 | 0.00 |
June | 4288.05 | 26-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.72 |
July | 4439.94 | 17-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 |
August | 4305.59 | 07-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 |
September | 3827.69 | 11-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.39 | 0.00 |
October | 2713.50 | 11-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 | 0.00 |
November | 1751.70 | 18-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.61 |
December | 1786.02 | 09-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1727.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4439.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.76 | 1593.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1634.52 | 13-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.51 |
February | 2336.71 | 23-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.16 |
March | 2409.76 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.04 |
April | 3170.77 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.20 |
May | 3836.90 | 30-MAY-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.06 | 0.00 |
June | 4098.05 | 26-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.50 | 0.00 |
July | 4635.49 | 10-JUL-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.27 | 0.00 |
August | 4584.07 | 07-AUG-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.30 | 0.00 |
September | 4459.52 | 11-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.24 | 0.00 |
October | 3417.16 | 11-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.02 | 0.00 |
November | 1792.05 | 21-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.15 |
December | 1767.35 | 08-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1634.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4635.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.27 | 319.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7657.31 | 31-JAN-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10326.05 | 28-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13514.47 | 30-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14410.85 | 17-APR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28949.20 | 30-MAY-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29233.29 | 19-JUN-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29250.30 | 07-JUL-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29098.95 | 22-AUG-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29131.52 | 11-SEP-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14942.62 | 11-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11391.68 | 06-NOV-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8480.60 | 13-DEC-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7657.31 | 0.00 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29250.30 | 6035.01 | 4936.01 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7576.31 | 20-JAN-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10493.11 | 28-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15597.03 | 30-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16758.85 | 17-APR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18908.81 | 30-MAY-15:20 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30420.84 | 26-JUN-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31344.95 | 24-JUL-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31787.13 | 14-AUG-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31185.05 | 05-SEP-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15963.50 | 11-OCT-15:50 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10330.88 | 06-NOV-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8280.31 | 13-DEC-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7576.31 | 0.00 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31787.13 | 6035.01 | 4936.01 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1561.51 | 31-JAN-16:40 | 1272.23 | 558.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.55 |
February | 2606.13 | 28-FEB-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 | 0.00 |
March | 4685.50 | 30-MAR-15:50 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 58.11 | 0.00 |
April | 5018.00 | 19-APR-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.52 | 0.00 |
May | 6499.51 | 30-MAY-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 50.98 | 0.00 |
June | 11325.96 | 25-JUN-17:02 | 0.00 | 165.44 | 2316.62 | 0.00 | 0.00 | 0.00 | 0.00 | 262.40 | 0.00 |
July | 11544.11 | 16-JUL-13:43 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 146.28 | 0.00 |
August | 10193.50 | 06-AUG-16:42 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 286.10 | 0.00 |
September | 6268.15 | 06-SEP-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 51.54 | 0.00 |
October | 4395.51 | 02-OCT-14:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.79 | 0.00 |
November | 2002.53 | 02-NOV-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.97 |
December | 1690.10 | 13-DEC-15:00 | 1306.65 | 563.80 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1561.51 | 0.00 | 110.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11544.11 | 1306.65 | 563.80 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 286.10 | 36.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1024.68 | 31-JAN-15:00 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.34 |
February | 2198.49 | 27-FEB-10:40 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.51 |
March | 3740.52 | 30-MAR-11:00 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.64 |
April | 7670.15 | 16-APR-10:33 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.48 |
May | 11123.15 | 07-MAY-10:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.49 |
June | 11345.49 | 25-JUN-09:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 0.00 |
July | 11384.28 | 09-JUL-10:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 46.67 | 0.00 |
August | 11963.79 | 27-AUG-09:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.42 |
September | 11304.16 | 04-SEP-09:32 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.18 |
October | 4523.54 | 11-OCT-10:30 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 | 0.00 |
November | 1943.13 | 06-NOV-10:40 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.63 |
December | 1096.25 | 13-DEC-13:30 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1024.68 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11963.79 | 827.22 | 314.23 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 46.67 | 86.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4468.67 | 11-JAN-14:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.25 |
February | 11171.34 | 26-FEB-14:33 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.16 |
March | 9603.29 | 30-MAR-13:40 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 42.07 | 0.00 |
April | 11725.10 | 16-APR-13:53 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 46.43 | 0.00 |
May | 9534.66 | 29-MAY-13:43 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 29.98 | 0.00 |
June | 12133.26 | 25-JUN-16:22 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 318.02 | 0.00 |
July | 13389.28 | 09-JUL-13:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 191.56 | 0.00 |
August | 13808.12 | 06-AUG-13:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 214.37 | 0.00 |
September | 14059.46 | 24-SEP-13:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 45.56 | 0.00 |
October | 14022.05 | 09-OCT-13:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 |
November | 13694.57 | 11-NOV-13:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.82 |
December | 6114.88 | 12-DEC-13:40 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4468.67 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14059.46 | 1306.65 | 496.34 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 318.02 | 277.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1099.70 | 20-JAN-16:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.37 |
February | 4313.77 | 27-FEB-17:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 |
March | 6412.81 | 30-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 39.20 | 0.00 |
April | 12354.03 | 09-APR-17:23 | 0.00 | 69.82 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.57 |
May | 11039.89 | 29-MAY-17:02 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.33 | 0.00 |
June | 12661.00 | 25-JUN-16:22 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 188.01 | 0.00 |
July | 12869.10 | 23-JUL-18:42 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.08 | 0.00 |
August | 12914.29 | 13-AUG-17:02 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 69.81 | 0.00 |
September | 11725.21 | 04-SEP-16:53 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 0.00 |
October | 11015.61 | 09-OCT-16:12 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 13.04 | 0.00 |
November | 3981.47 | 06-NOV-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.94 |
December | 1607.80 | 11-DEC-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1099.70 | 0.00 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12914.29 | 805.38 | 314.21 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 188.01 | 59.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1495.09 | 31-JAN-16:30 | 1272.23 | 542.94 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.66 |
February | 1718.96 | 28-FEB-15:10 | 2544.47 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 12.70 | 0.00 |
March | 2693.96 | 30-MAR-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.69 | 0.00 |
April | 2988.56 | 19-APR-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.99 | 0.00 |
May | 4498.99 | 30-MAY-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.32 | 0.00 |
June | 5266.88 | 28-JUN-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 60.76 | 0.00 |
July | 6915.63 | 16-JUL-15:23 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 101.16 | 0.00 |
August | 6403.75 | 21-AUG-06:03 | 803.52 | 1023.10 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.58 |
September | 5550.93 | 06-SEP-14:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 28.24 | 0.00 |
October | 3975.23 | 02-OCT-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.13 | 0.00 |
November | 2072.27 | 03-NOV-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.49 |
December | 1691.28 | 13-DEC-13:30 | 1272.23 | 538.55 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1495.09 | 267.84 | 110.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6915.63 | 2544.47 | 1023.10 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 101.16 | 19.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1002.01 | 31-JAN-14:50 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.58 |
February | 1927.81 | 27-FEB-10:40 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.89 |
March | 2633.03 | 14-MAR-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.63 |
April | 4277.33 | 17-APR-10:10 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.22 |
May | 7881.93 | 07-MAY-09:32 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.32 |
June | 8785.70 | 11-JUN-10:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.69 |
July | 9053.95 | 09-JUL-08:23 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.83 |
August | 10101.19 | 27-AUG-09:52 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 |
September | 9132.53 | 04-SEP-09:23 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 |
October | 4505.39 | 10-OCT-10:20 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 | 0.00 |
November | 2521.07 | 06-NOV-10:10 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.10 |
December | 1110.43 | 13-DEC-12:00 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1002.01 | 169.56 | 69.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10101.19 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 | 46.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2639.10 | 28-JAN-14:40 | 137.54 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.40 |
February | 6152.45 | 21-FEB-14:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.80 |
March | 7688.37 | 30-MAR-16:10 | 401.76 | 275.75 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 2827.75 | 0.00 |
April | 7748.97 | 17-APR-16:10 | 401.76 | 275.75 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3719.93 | 0.00 |
May | 8833.89 | 30-MAY-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4168.60 | 0.00 |
June | 9549.43 | 06-JUN-16:30 | 401.76 | 275.75 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 6802.09 | 0.00 |
July | 9965.56 | 07-JUL-16:10 | 1607.03 | 1102.99 | 3189.42 | 0.00 | 0.00 | 0.00 | 0.00 | 7616.11 | 0.00 |
August | 10988.40 | 27-AUG-13:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 113.66 | 0.00 |
September | 9839.43 | 07-SEP-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4491.19 | 0.00 |
October | 11534.70 | 09-OCT-14:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 | 0.00 |
November | 10920.93 | 12-NOV-14:03 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.09 |
December | 5776.73 | 12-DEC-13:50 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2639.10 | 137.54 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11534.70 | 1607.03 | 1102.99 | 3189.42 | 0.00 | 0.00 | 0.00 | 0.00 | 7616.11 | 190.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1046.13 | 20-JAN-16:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.79 |
February | 3081.17 | 27-FEB-17:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 |
March | 4322.26 | 30-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 | 0.00 |
April | 4840.13 | 17-APR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7.94 | 0.00 |
May | 6737.68 | 06-MAY-17:08 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 10.82 | 0.00 |
June | 8498.16 | 04-JUN-16:52 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 46.63 | 0.00 |
July | 10150.70 | 09-JUL-17:02 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 72.84 | 0.00 |
August | 10371.62 | 27-AUG-15:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 57.25 | 0.00 |
September | 9827.45 | 24-SEP-16:53 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 6.45 | 0.00 |
October | 7026.04 | 08-OCT-16:43 | 127.16 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
November | 3920.24 | 06-NOV-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.70 |
December | 1525.75 | 11-DEC-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1046.13 | 0.00 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10371.62 | 805.38 | 314.21 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 72.84 | 26.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1574.40 | 31-JAN-16:40 | 1272.23 | 558.14 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.54 |
February | 2581.43 | 28-FEB-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.31 | 0.00 |
March | 4147.38 | 30-MAR-15:50 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 48.71 | 0.00 |
April | 4545.92 | 18-APR-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.70 | 0.00 |
May | 5849.11 | 30-MAY-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 42.60 | 0.00 |
June | 7878.16 | 26-JUN-05:12 | 535.68 | 462.46 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.12 |
July | 9775.20 | 16-JUL-13:43 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 126.72 | 0.00 |
August | 8673.65 | 06-AUG-17:12 | 0.00 | 165.44 | 2316.62 | 0.00 | 0.00 | 0.00 | 0.00 | 215.50 | 0.00 |
September | 5692.95 | 06-SEP-14:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 44.03 | 0.00 |
October | 4077.38 | 02-OCT-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 25.02 | 0.00 |
November | 2178.17 | 03-NOV-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.45 |
December | 1726.41 | 13-DEC-13:30 | 1272.23 | 542.86 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1574.40 | 0.00 | 110.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9775.20 | 1306.65 | 558.14 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 215.50 | 32.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1113.92 | 31-JAN-15:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.49 |
February | 4279.09 | 23-FEB-13:02 | 4027.14 | 1571.14 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.48 |
March | 5320.08 | 15-MAR-12:02 | 4027.14 | 1571.14 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.37 |
April | 7616.97 | 16-APR-09:33 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.60 |
May | 10956.57 | 07-MAY-09:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.52 |
June | 11449.33 | 04-JUN-09:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 |
July | 11417.55 | 23-JUL-09:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.60 |
August | 11685.55 | 27-AUG-09:52 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.02 |
September | 10885.23 | 04-SEP-09:23 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.05 |
October | 5924.94 | 11-OCT-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.02 |
November | 3616.06 | 09-NOV-13:02 | 3221.71 | 1256.91 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.59 |
December | 2367.29 | 13-DEC-13:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1113.92 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.02 | |
Maximum of Months | 11685.55 | 4027.14 | 1571.14 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4648.54 | 27-JAN-14:40 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.45 |
February | 10983.24 | 26-FEB-14:43 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.04 |
March | 8985.74 | 30-MAR-13:40 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 35.29 | 0.00 |
April | 10114.51 | 16-APR-13:33 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 30.87 | 0.00 |
May | 7068.59 | 30-MAY-14:00 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 48.51 | 0.00 |
June | 8192.59 | 26-JUN-05:12 | 535.68 | 462.46 | 2551.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.90 |
July | 11644.75 | 09-JUL-13:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 168.24 | 0.00 |
August | 12091.89 | 06-AUG-13:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 156.12 | 0.00 |
September | 10403.63 | 24-SEP-11:33 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 33.35 | 0.00 |
October | 12468.83 | 09-OCT-14:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 2.36 | 0.00 |
November | 12361.43 | 11-NOV-13:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.51 |
December | 6642.85 | 08-DEC-14:00 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4648.54 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12468.83 | 1306.65 | 496.34 | 2551.53 | 0.00 | 0.00 | 0.00 | 0.00 | 168.24 | 244.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1105.38 | 20-JAN-16:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.48 |
February | 4174.81 | 27-FEB-17:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 |
March | 5975.96 | 30-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 32.85 | 0.00 |
April | 11190.91 | 09-APR-17:12 | 0.00 | 69.82 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 |
May | 11619.36 | 21-MAY-16:42 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.82 |
June | 11908.62 | 11-JUN-16:22 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 110.82 | 0.00 |
July | 12117.96 | 23-JUL-17:52 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 19.23 | 0.00 |
August | 11862.77 | 13-AUG-16:51 | 339.11 | 139.64 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 57.14 | 0.00 |
September | 11243.97 | 04-SEP-16:12 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 17.69 | 0.00 |
October | 7927.85 | 09-OCT-15:13 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | 0.00 |
November | 4086.84 | 06-NOV-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.66 |
December | 1776.18 | 11-DEC-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1105.38 | 0.00 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12117.96 | 805.38 | 314.21 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 110.82 | 45.67 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.135634E+12 | 226940.08 | 02-JAN-07:10 | 0.301640E+11 | 64282.46 | 27-JAN-07:40 |
February | 0.108297E+12 | 219045.23 | 13-FEB-07:10 | 0.196444E+11 | 72312.24 | 03-FEB-07:40 |
March | 0.105585E+12 | 107964.46 | 30-MAR-15:20 | 0.124336E+11 | 26871.70 | 18-MAR-06:49 |
April | 0.103809E+12 | 110467.83 | 17-APR-15:30 | 0.106779E+11 | 29772.63 | 06-APR-06:30 |
May | 0.124856E+12 | 128373.82 | 30-MAY-15:09 | 0.104875E+11 | 9741.25 | 01-MAY-11:09 |
June | 0.145115E+12 | 138001.65 | 27-JUN-15:39 | 0.990215E+10 | 9594.71 | 01-JUN-11:00 |
July | 0.152210E+12 | 151425.28 | 07-JUL-15:00 | 0.964297E+10 | 9495.40 | 03-JUL-11:30 |
August | 0.166163E+12 | 149934.03 | 01-AUG-15:20 | 0.100260E+11 | 9493.17 | 31-AUG-11:00 |
September | 0.127907E+12 | 142156.25 | 07-SEP-15:00 | 0.960817E+10 | 9586.21 | 29-SEP-11:09 |
October | 0.108215E+12 | 121730.04 | 10-OCT-15:50 | 0.104481E+11 | 27234.96 | 26-OCT-06:40 |
November | 0.996581E+11 | 126781.03 | 22-NOV-07:10 | 0.126923E+11 | 47633.86 | 22-NOV-07:19 |
December | 0.109853E+12 | 177999.13 | 18-DEC-07:10 | 0.161377E+11 | 58895.99 | 18-DEC-07:49 |
Annual Sum or Average | 0.148730E+13 | 0.161865E+12 | ||||
Minimum of Months | 0.996581E+11 | 107964.46 | 0.960817E+10 | 9493.17 | ||
Maximum of Months | 0.166163E+12 | 226940.08 | 0.301640E+11 | 72312.24 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.198175E+11 | 0.544208E+10 | 0.593559E+11 | 0.982808E+09 | 0.342182E+10 | 12379742.02 | 0.452703E+11 | 0.133094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179794E+11 | 0.447543E+10 | 0.537310E+11 | 0.889554E+09 | 0.316583E+10 | 11196021.66 | 0.246399E+11 | 0.340477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208723E+11 | 0.443078E+10 | 0.617796E+11 | 0.102915E+10 | 0.390194E+10 | 12675672.10 | 0.334314E+10 | 0.102159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.184586E+11 | 0.378945E+10 | 0.572952E+11 | 0.946259E+09 | 0.430836E+10 | 11960507.72 | 0.107149E+10 | 0.179279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197872E+11 | 0.345949E+10 | 0.605677E+11 | 0.100559E+10 | 0.592675E+10 | 12527707.06 | 0.166070E+09 | 0.339307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.196404E+11 | 0.317507E+10 | 0.594895E+11 | 0.989907E+09 | 0.827049E+10 | 12231776.97 | 22165751.06 | 0.535156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.184155E+11 | 0.336986E+10 | 0.583622E+11 | 0.961715E+09 | 0.904542E+10 | 12256437.81 | 0.00 | 0.620426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.206313E+11 | 0.373343E+10 | 0.617796E+11 | 0.102898E+10 | 0.100783E+11 | 12675672.10 | 0.00 | 0.688986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.185961E+11 | 0.405491E+10 | 0.572729E+11 | 0.946115E+09 | 0.683847E+10 | 11960507.72 | 21108758.98 | 0.401655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.196424E+11 | 0.470282E+10 | 0.593671E+11 | 0.982859E+09 | 0.463357E+10 | 12379742.02 | 0.159392E+10 | 0.172800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.195059E+11 | 0.511872E+10 | 0.580818E+11 | 0.964502E+09 | 0.345194E+10 | 12059151.09 | 0.558178E+10 | 0.694130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192055E+11 | 0.559902E+10 | 0.583511E+11 | 0.962151E+09 | 0.324118E+10 | 12256437.81 | 0.199854E+11 | 0.249633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232552E+12 | 0.513511E+11 | 0.705434E+12 | 0.116896E+11 | 0.662841E+11 | 0.146559E+09 | 0.101695E+12 | 0.318150E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.179794E+11 | 0.317507E+10 | 0.537310E+11 | 0.889554E+09 | 0.316583E+10 | 11196021.66 | 0.00 | 0.133094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.208723E+11 | 0.559902E+10 | 0.617796E+11 | 0.102915E+10 | 0.100783E+11 | 12675672.10 | 0.452703E+11 | 0.688986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.189144E+11 | 0.00 | 0.112496E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.945826E+10 | 0.00 | 0.101861E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.100330E+10 | 0.00 | 0.114303E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.317606E+09 | 0.00 | 0.103603E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.104875E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.990215E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.964297E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.100260E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.960817E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.184524E+09 | 0.00 | 0.102636E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.230772E+10 | 0.00 | 0.103846E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.525747E+10 | 0.00 | 0.108802E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.374433E+11 | 0.00 | 0.124422E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.960817E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.189144E+11 | 0.00 | 0.114303E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 24030.94 | 03-JAN-08:09 | 5686.19 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 838.86 | 03-JAN-08:20 | 5603.47 | 09-JAN-07:10 | 6.85 | 02-JAN-07:10 | 186005.08 | 02-JAN-07:10 |
February | 24713.90 | 01-FEB-08:09 | 5686.19 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 839.77 | 01-FEB-08:20 | 5409.07 | 13-FEB-07:10 | 6.85 | 01-FEB-06:10 | 178265.91 | 13-FEB-07:10 |
March | 24169.18 | 21-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 839.04 | 21-MAR-07:19 | 7825.51 | 30-MAR-15:00 | 6.85 | 06-MAR-08:09 | 63735.92 | 23-MAR-06:10 |
April | 23249.44 | 03-APR-07:10 | 5686.19 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 837.82 | 03-APR-07:19 | 8480.34 | 17-APR-15:50 | 6.85 | 01-APR-05:10 | 47917.15 | 07-APR-06:10 |
May | 20676.82 | 24-MAY-07:30 | 5686.19 | 01-MAY-05:10 | 45864.70 | 01-MAY-07:10 | 834.40 | 24-MAY-07:40 | 11116.40 | 30-MAY-15:09 | 6.85 | 01-MAY-05:10 | 12591.44 | 11-MAY-06:10 |
June | 20258.51 | 23-JUN-07:10 | 5686.19 | 01-JUN-05:10 | 45864.70 | 01-JUN-07:10 | 833.85 | 23-JUN-07:19 | 11783.48 | 26-JUN-15:30 | 6.85 | 01-JUN-05:10 | 4060.38 | 08-JUN-06:10 |
July | 21397.89 | 27-JUL-07:10 | 5686.19 | 01-JUL-05:10 | 45864.70 | 03-JUL-07:10 | 835.36 | 27-JUL-07:19 | 13383.18 | 10-JUL-15:30 | 6.85 | 09-JUL-16:19 | 0.00 | 01-JUL-00:10 |
August | 22850.66 | 24-AUG-07:10 | 5686.19 | 01-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 837.29 | 24-AUG-07:19 | 14092.49 | 02-AUG-15:50 | 6.85 | 13-AUG-16:19 | 0.00 | 01-AUG-00:10 |
September | 23601.02 | 29-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 838.29 | 29-SEP-07:19 | 13263.34 | 07-SEP-15:30 | 6.85 | 01-SEP-05:10 | 4047.80 | 29-SEP-06:19 |
October | 24978.45 | 30-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 840.12 | 30-OCT-07:19 | 9811.57 | 10-OCT-15:30 | 6.85 | 26-OCT-07:10 | 54870.93 | 26-OCT-06:10 |
November | 24819.27 | 01-NOV-07:10 | 5686.19 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 839.91 | 01-NOV-07:19 | 4959.05 | 06-NOV-15:30 | 6.85 | 13-NOV-12:09 | 88421.28 | 22-NOV-07:10 |
December | 24050.81 | 06-DEC-08:09 | 5686.19 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 838.89 | 06-DEC-08:20 | 3949.93 | 18-DEC-07:10 | 6.85 | 04-DEC-12:09 | 138678.96 | 18-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 20258.51 | 5686.19 | 45864.70 | 833.85 | 3949.93 | 6.85 | 0.00 | |||||||
Maximum of Months | 24978.45 | 5686.19 | 45864.70 | 840.12 | 14092.49 | 6.85 | 186005.08 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 13083.14 | 19-JAN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20048.76 | 28-FEB-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 37718.96 | 30-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40263.34 | 17-APR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 55006.96 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 63922.47 | 27-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 75463.76 | 07-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 73767.46 | 01-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 66504.62 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 49418.16 | 10-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20611.30 | 02-NOV-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19909.92 | 12-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 13083.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 75463.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 226940.08 | 02-JAN-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 5564.75 | 6.85 | 186005.08 | 0.00 | 0.00 |
February | 219045.23 | 13-FEB-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 5409.07 | 6.85 | 178265.91 | 0.00 | 0.00 |
March | 107964.46 | 30-MAR-15:20 | 19671.42 | 42072.41 | 0.00 | 831.72 | 7663.10 | 6.85 | 0.00 | 37718.96 | 0.00 |
April | 110467.83 | 17-APR-15:30 | 19671.42 | 42072.41 | 0.00 | 831.72 | 8455.30 | 6.85 | 0.00 | 39430.13 | 0.00 |
May | 128373.82 | 30-MAY-15:09 | 19671.42 | 42072.41 | 0.00 | 831.72 | 11116.40 | 6.85 | 0.00 | 54675.03 | 0.00 |
June | 138001.65 | 27-JUN-15:39 | 19671.42 | 42072.41 | 0.00 | 831.72 | 11550.98 | 6.85 | 0.00 | 63868.28 | 0.00 |
July | 151425.28 | 07-JUL-15:00 | 19671.42 | 42072.41 | 0.00 | 831.72 | 13379.12 | 6.85 | 0.00 | 75463.76 | 0.00 |
August | 149934.03 | 01-AUG-15:20 | 19671.42 | 42072.41 | 0.00 | 831.72 | 13584.17 | 6.85 | 0.00 | 73767.46 | 0.00 |
September | 142156.25 | 07-SEP-15:00 | 19671.42 | 42072.41 | 0.00 | 831.72 | 13069.24 | 6.85 | 0.00 | 66504.62 | 0.00 |
October | 121730.04 | 10-OCT-15:50 | 19671.42 | 42072.41 | 0.00 | 831.72 | 9746.78 | 6.85 | 0.00 | 49400.87 | 0.00 |
November | 126781.03 | 22-NOV-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 2989.50 | 6.85 | 88421.28 | 0.00 | 0.00 |
December | 177999.13 | 18-DEC-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 3949.93 | 6.85 | 138678.96 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 107964.46 | 8334.71 | 21098.80 | 0.00 | 243.70 | 2989.50 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 226940.08 | 19671.42 | 42072.41 | 5686.19 | 831.72 | 13584.17 | 6.85 | 186005.08 | 75463.76 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 55571.44 | 27-JAN-07:30 | 0.00 | 10014.47 | 31-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 63863.79 | 03-FEB-07:30 | 0.00 | 10016.76 | 06-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 18573.12 | 18-MAR-06:00 | 0.00 | 9976.85 | 02-MAR-12:20 | 0.00 |
April | 0.00 | 0.00 | 21457.04 | 06-APR-06:19 | 0.00 | 9860.14 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 9741.25 | 01-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9594.71 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9495.40 | 03-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9493.17 | 31-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 9586.21 | 29-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 18567.53 | 26-OCT-06:49 | 0.00 | 9726.07 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 38966.37 | 22-NOV-07:30 | 0.00 | 9853.65 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 50812.71 | 18-DEC-07:40 | 0.00 | 9959.54 | 26-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9493.17 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 63863.79 | 0.00 | 10016.76 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 19.75 | 1.17 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 |
February | 0.17 | 19.08 | 0.17 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.33 | 19.67 | 1.33 | 19.67 | 0.00 | 19.67 | 0.00 | 19.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 19.75 | 1.17 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 18.53 | 0.83 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 |
February | 0.67 | 18.10 | 0.33 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.24 | 0.50 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Annual Sum or Average | 2.17 | 18.56 | 1.67 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.24 | 0.83 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.50 | 16.68 | 7.17 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 |
February | 11.50 | 16.15 | 5.17 | 16.57 | 0.00 | 16.57 | 0.00 | 16.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.43 | 1.33 | 27.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.49 | 3.17 | 27.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.36 | 2.17 | 27.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 |
December | 4.17 | 17.87 | 2.33 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
Annual Sum or Average | 31.50 | 16.65 | 14.67 | 17.11 | 9.67 | 18.90 | 6.67 | 19.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.50 | 17.87 | 7.17 | 18.41 | 5.17 | 27.49 | 3.17 | 27.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.83 | 15.54 | 1.83 | 15.68 | 0.00 | 15.68 | 0.00 | 15.68 |
February | 7.17 | 15.10 | 1.17 | 15.20 | 0.00 | 15.20 | 0.00 | 15.20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.51 | 0.83 | 27.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.53 | 4.00 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.67 | 7.83 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.75 | 11.50 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.73 | 8.83 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.56 | 2.00 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 |
December | 1.67 | 16.68 | 0.33 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 |
Annual Sum or Average | 19.00 | 15.50 | 3.33 | 15.65 | 39.50 | 23.34 | 35.00 | 24.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.83 | 17.04 | 1.83 | 17.09 | 13.83 | 27.75 | 11.50 | 27.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.17 | 16.15 | 2.33 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 |
February | 6.33 | 15.85 | 1.83 | 16.24 | 0.67 | 17.09 | 0.67 | 17.82 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.51 | 1.00 | 27.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.43 | 1.17 | 27.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.47 | 2.83 | 27.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.54 | 6.17 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.68 | 5.50 | 27.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.59 | 3.00 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.63 | 4.17 | 27.63 |
November | 0.33 | 17.16 | 0.00 | 17.16 | 1.33 | 25.47 | 1.33 | 26.39 |
December | 1.33 | 17.73 | 0.50 | 18.11 | 0.00 | 18.11 | 0.00 | 18.11 |
Annual Sum or Average | 16.17 | 16.18 | 4.67 | 16.55 | 29.00 | 22.97 | 25.83 | 24.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.17 | 17.73 | 2.33 | 18.11 | 7.67 | 27.68 | 6.17 | 27.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.83 | 15.55 | 2.67 | 15.64 | 0.00 | 15.64 | 0.00 | 15.64 |
February | 7.17 | 14.98 | 2.17 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.63 | 1.67 | 27.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.88 | 2.17 | 27.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.99 | 4.17 | 28.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 28.08 | 6.17 | 28.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.07 | 4.33 | 28.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.66 | 3.00 | 27.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.66 | 1.00 | 27.67 |
November | 0.33 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 |
December | 1.50 | 16.90 | 0.50 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
Annual Sum or Average | 18.83 | 15.46 | 5.33 | 15.52 | 40.17 | 23.28 | 22.50 | 24.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.83 | 17.02 | 2.67 | 17.12 | 12.17 | 28.08 | 6.17 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 19.23 | 1.67 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
February | 2.17 | 19.38 | 1.83 | 19.58 | 0.00 | 19.58 | 0.00 | 19.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.00 | 19.31 | 3.50 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 19.38 | 1.83 | 19.58 | 0.00 | 19.58 | 0.00 | 19.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 17.98 | 0.17 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 |
February | 0.17 | 16.76 | 0.00 | 16.76 | 0.00 | 16.76 | 0.00 | 16.76 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.40 | 0.33 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.55 | 2.83 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.54 | 6.83 | 27.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.53 | 5.50 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.47 | 1.50 | 27.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 17.58 | 0.17 | 17.95 | 17.17 | 27.17 | 17.17 | 27.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 17.98 | 0.17 | 18.35 | 6.83 | 27.55 | 6.83 | 27.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 48.83 | 18.12 | 48.67 | 18.12 | 0.00 | 18.12 | 0.00 | 18.12 |
February | 31.17 | 18.30 | 31.00 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 |
March | 11.50 | 19.46 | 11.50 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
April | 5.17 | 18.94 | 5.17 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.70 | 3.50 | 24.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 24.88 | 14.17 | 24.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 25.23 | 22.83 | 25.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 25.18 | 7.50 | 25.18 |
October | 2.00 | 19.38 | 2.00 | 19.38 | 8.33 | 24.00 | 8.17 | 24.87 |
November | 12.00 | 19.50 | 12.00 | 19.50 | 2.00 | 20.12 | 2.00 | 20.64 |
December | 20.67 | 18.38 | 20.67 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 |
Annual Sum or Average | 131.33 | 18.50 | 131.00 | 18.50 | 58.33 | 19.74 | 58.17 | 20.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.83 | 19.50 | 48.67 | 19.50 | 22.83 | 25.23 | 22.83 | 25.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 17.96 | 0.17 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 |
February | 0.17 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.41 | 1.00 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.64 | 2.33 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.78 | 3.83 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.76 | 3.33 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.51 | 1.83 | 27.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.52 | 0.67 | 27.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 17.59 | 0.17 | 17.96 | 22.83 | 27.40 | 13.00 | 27.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 17.96 | 0.17 | 18.33 | 7.50 | 27.78 | 3.83 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 18.79 | 1.83 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
February | 2.83 | 17.14 | 1.83 | 17.49 | 0.00 | 17.49 | 0.00 | 17.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.35 | 1.17 | 27.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 18.22 | 0.33 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
Annual Sum or Average | 6.00 | 17.95 | 4.00 | 18.28 | 1.50 | 19.46 | 1.17 | 20.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 18.79 | 1.83 | 19.06 | 1.50 | 27.35 | 1.17 | 27.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 17.61 | 0.33 | 17.95 | 0.00 | 17.95 | 0.00 | 17.95 |
February | 1.67 | 15.06 | 0.50 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.51 | 1.00 | 27.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.58 | 2.67 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.69 | 5.50 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.65 | 10.50 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.67 | 7.00 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.57 | 2.00 | 27.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 17.92 | 0.17 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 |
Annual Sum or Average | 3.33 | 16.38 | 1.00 | 16.53 | 29.83 | 26.23 | 28.83 | 26.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 17.92 | 0.50 | 18.27 | 11.00 | 27.69 | 10.50 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 17.94 | 0.33 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 |
February | 0.83 | 16.20 | 0.67 | 16.15 | 0.83 | 20.20 | 0.83 | 22.12 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.39 | 0.67 | 27.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.42 | 2.67 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.51 | 4.83 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.50 | 2.50 | 27.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.64 | 4.17 | 27.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.58 | 2.33 | 27.58 |
December | 0.17 | 19.26 | 0.17 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Annual Sum or Average | 1.67 | 17.20 | 1.17 | 17.27 | 18.67 | 26.17 | 18.33 | 26.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 19.26 | 0.67 | 19.26 | 5.17 | 27.64 | 4.83 | 27.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 17.63 | 0.33 | 17.97 | 0.00 | 17.97 | 0.00 | 17.97 |
February | 1.17 | 15.13 | 0.67 | 15.04 | 0.00 | 15.04 | 0.00 | 15.04 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.55 | 1.50 | 27.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.76 | 1.67 | 27.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.83 | 3.33 | 27.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.97 | 5.00 | 27.99 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.91 | 3.67 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.61 | 2.50 | 27.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.54 | 1.33 | 27.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 18.27 | 0.17 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
Annual Sum or Average | 2.67 | 16.62 | 1.17 | 16.65 | 33.17 | 26.66 | 19.17 | 27.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 18.27 | 0.67 | 18.61 | 9.67 | 27.97 | 5.00 | 27.99 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.00 | 22.65 | 22.00 | 22.55 | 22.00 | 22.46 |
February | 420.67 | 23.26 | 4.50 | 23.25 | 2.83 | 23.23 |
March | 245.33 | 23.84 | 84.17 | 24.02 | 0.00 | 24.02 |
April | 69.17 | 23.86 | 182.17 | 24.43 | 0.00 | 24.43 |
May | 5.33 | 23.98 | 384.17 | 24.50 | 0.00 | 24.50 |
June | 0.00 | 0.00 | 435.33 | 24.39 | 0.00 | 24.39 |
July | 0.00 | 0.00 | 496.33 | 24.44 | 0.00 | 24.44 |
August | 0.00 | 0.00 | 513.83 | 24.37 | 0.00 | 24.37 |
September | 0.00 | 0.00 | 447.67 | 24.46 | 0.00 | 24.46 |
October | 33.17 | 23.70 | 215.00 | 24.54 | 0.00 | 24.54 |
November | 242.17 | 23.87 | 54.83 | 24.02 | 0.00 | 24.02 |
December | 434.33 | 23.45 | 11.67 | 23.47 | 0.00 | 23.47 |
Annual Sum or Average | 1949.17 | 23.32 | 2851.67 | 23.98 | 24.83 | 23.96 |
Minimum of Months | 0.00 | 0.00 | 4.50 | 22.55 | 0.00 | 22.46 |
Maximum of Months | 499.00 | 23.98 | 513.83 | 24.54 | 22.00 | 24.54 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.12 | 201.50 | 20.94 | 201.50 | 20.84 |
February | 450.33 | 21.83 | 83.33 | 21.63 | 83.33 | 21.49 |
March | 416.50 | 23.06 | 25.50 | 23.12 | 0.00 | 23.12 |
April | 236.50 | 23.40 | 96.83 | 23.67 | 0.00 | 23.67 |
May | 52.33 | 23.48 | 269.83 | 24.18 | 0.00 | 24.18 |
June | 24.00 | 23.69 | 392.50 | 24.25 | 0.00 | 24.25 |
July | 5.83 | 23.25 | 469.33 | 24.30 | 0.00 | 24.30 |
August | 0.00 | 0.00 | 499.17 | 24.28 | 0.00 | 24.28 |
September | 23.67 | 23.19 | 342.67 | 24.28 | 0.00 | 24.28 |
October | 258.33 | 23.14 | 96.17 | 23.43 | 0.00 | 23.43 |
November | 455.50 | 22.87 | 0.00 | 22.87 | 0.00 | 22.87 |
December | 491.33 | 21.77 | 41.17 | 21.70 | 40.67 | 21.64 |
Annual Sum or Average | 2916.33 | 22.34 | 2518.00 | 23.02 | 325.50 | 22.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 20.94 | 0.00 | 20.84 |
Maximum of Months | 502.00 | 23.69 | 499.17 | 24.30 | 201.50 | 24.30 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.61 | 332.50 | 20.45 | 332.50 | 20.38 |
February | 451.50 | 21.29 | 153.67 | 21.04 | 153.67 | 20.89 |
March | 445.33 | 22.53 | 40.67 | 22.56 | 14.67 | 22.50 |
April | 274.67 | 23.06 | 76.33 | 23.32 | 0.00 | 23.32 |
May | 98.33 | 23.36 | 255.50 | 24.00 | 0.00 | 24.00 |
June | 29.17 | 23.47 | 388.17 | 24.23 | 0.00 | 24.23 |
July | 12.17 | 23.12 | 465.50 | 24.31 | 0.00 | 24.31 |
August | 0.17 | 23.57 | 497.00 | 24.30 | 0.00 | 24.30 |
September | 70.00 | 23.12 | 289.00 | 24.08 | 0.00 | 24.08 |
October | 348.33 | 22.66 | 69.67 | 22.90 | 1.17 | 22.89 |
November | 479.33 | 22.06 | 44.33 | 21.93 | 44.33 | 21.82 |
December | 494.83 | 21.07 | 199.00 | 20.85 | 199.00 | 20.73 |
Annual Sum or Average | 3205.83 | 21.87 | 2811.33 | 22.50 | 745.33 | 22.26 |
Minimum of Months | 0.17 | 20.61 | 40.67 | 20.45 | 0.00 | 20.38 |
Maximum of Months | 502.00 | 23.57 | 497.00 | 24.31 | 332.50 | 24.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.06 | 418.33 | 19.96 | 418.33 | 19.92 |
February | 450.67 | 20.71 | 258.67 | 20.47 | 258.67 | 20.36 |
March | 454.67 | 21.79 | 119.17 | 21.71 | 84.67 | 21.53 |
April | 297.17 | 22.50 | 117.33 | 22.81 | 27.33 | 22.74 |
May | 121.67 | 23.01 | 286.83 | 23.90 | 6.00 | 23.91 |
June | 52.67 | 24.30 | 416.50 | 24.35 | 24.50 | 24.41 |
July | 55.33 | 25.29 | 477.67 | 24.55 | 48.00 | 24.64 |
August | 48.17 | 25.33 | 503.50 | 24.46 | 45.50 | 24.53 |
September | 135.00 | 23.38 | 297.00 | 24.05 | 26.50 | 24.12 |
October | 389.17 | 22.00 | 102.00 | 22.26 | 35.33 | 22.23 |
November | 481.17 | 21.28 | 154.67 | 21.03 | 154.67 | 20.88 |
December | 497.00 | 20.37 | 339.33 | 20.17 | 339.33 | 20.09 |
Annual Sum or Average | 3484.67 | 21.46 | 3491.00 | 22.10 | 1468.83 | 21.84 |
Minimum of Months | 48.17 | 20.06 | 102.00 | 19.96 | 6.00 | 19.92 |
Maximum of Months | 502.00 | 25.33 | 503.50 | 24.55 | 418.33 | 24.64 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.24 | 389.50 | 20.10 | 389.50 | 20.05 |
February | 441.83 | 21.06 | 213.17 | 20.72 | 213.17 | 20.55 |
March | 392.00 | 22.22 | 96.17 | 22.23 | 45.67 | 22.06 |
April | 195.67 | 22.65 | 178.67 | 23.37 | 19.50 | 23.34 |
May | 97.83 | 23.71 | 352.83 | 24.29 | 22.17 | 24.39 |
June | 58.17 | 25.43 | 452.83 | 24.54 | 42.83 | 24.68 |
July | 84.00 | 26.00 | 480.00 | 24.78 | 76.50 | 24.96 |
August | 69.83 | 25.98 | 509.00 | 24.63 | 68.67 | 24.78 |
September | 113.17 | 23.82 | 345.67 | 24.29 | 37.33 | 24.41 |
October | 302.17 | 22.13 | 153.83 | 22.70 | 32.33 | 22.65 |
November | 462.00 | 21.65 | 107.33 | 21.41 | 104.00 | 21.23 |
December | 497.00 | 20.58 | 276.83 | 20.30 | 276.83 | 20.17 |
Annual Sum or Average | 3215.67 | 21.77 | 3555.83 | 22.48 | 1328.50 | 22.27 |
Minimum of Months | 58.17 | 20.24 | 96.17 | 20.10 | 19.50 | 20.05 |
Maximum of Months | 502.00 | 26.00 | 509.00 | 24.78 | 389.50 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 483.83 | 20.86 | 287.17 | 20.51 | 284.17 | 20.33 |
February | 400.00 | 21.23 | 196.33 | 21.05 | 178.67 | 20.84 |
March | 335.50 | 22.02 | 134.00 | 22.28 | 52.33 | 22.08 |
April | 230.00 | 22.54 | 164.00 | 23.18 | 23.67 | 23.13 |
May | 123.17 | 23.06 | 296.83 | 23.96 | 8.67 | 23.99 |
June | 62.50 | 24.25 | 408.00 | 24.35 | 27.33 | 24.43 |
July | 65.83 | 25.53 | 471.50 | 24.61 | 58.33 | 24.74 |
August | 58.67 | 25.66 | 504.67 | 24.54 | 55.83 | 24.65 |
September | 118.50 | 23.79 | 330.83 | 24.28 | 37.17 | 24.41 |
October | 274.00 | 22.28 | 197.83 | 23.08 | 37.83 | 23.12 |
November | 373.83 | 21.80 | 129.33 | 21.88 | 81.00 | 21.67 |
December | 445.33 | 21.06 | 218.17 | 20.74 | 207.00 | 20.52 |
Annual Sum or Average | 2971.17 | 21.93 | 3338.67 | 22.68 | 1052.00 | 22.47 |
Minimum of Months | 58.67 | 20.86 | 129.33 | 20.51 | 8.67 | 20.33 |
Maximum of Months | 483.83 | 25.66 | 504.67 | 24.61 | 284.17 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.31 | 367.50 | 20.11 | 367.50 | 20.02 |
February | 432.50 | 20.89 | 232.67 | 20.65 | 226.83 | 20.50 |
March | 377.67 | 21.84 | 140.33 | 22.00 | 68.67 | 21.80 |
April | 242.83 | 22.60 | 177.67 | 23.22 | 29.17 | 23.22 |
May | 119.50 | 23.35 | 325.67 | 24.10 | 18.17 | 24.17 |
June | 67.83 | 24.71 | 426.50 | 24.45 | 36.83 | 24.56 |
July | 66.67 | 25.62 | 476.83 | 24.65 | 60.17 | 24.78 |
August | 60.67 | 25.74 | 506.50 | 24.57 | 58.50 | 24.69 |
September | 124.83 | 23.80 | 326.50 | 24.26 | 41.00 | 24.39 |
October | 332.33 | 22.07 | 148.17 | 22.63 | 34.83 | 22.63 |
November | 438.17 | 21.44 | 141.17 | 21.25 | 128.00 | 21.06 |
December | 491.50 | 20.62 | 288.00 | 20.33 | 288.00 | 20.20 |
Annual Sum or Average | 3256.50 | 21.66 | 3557.50 | 22.38 | 1357.67 | 22.16 |
Minimum of Months | 60.67 | 20.31 | 140.33 | 20.11 | 18.17 | 20.02 |
Maximum of Months | 502.00 | 25.74 | 506.50 | 24.65 | 367.50 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.39 | 403.50 | 20.30 | 403.50 | 20.27 |
February | 454.00 | 20.86 | 230.33 | 20.66 | 230.33 | 20.57 |
March | 495.00 | 21.78 | 63.50 | 21.67 | 57.67 | 21.57 |
April | 412.50 | 22.47 | 40.50 | 22.53 | 16.33 | 22.50 |
May | 201.83 | 23.21 | 197.50 | 23.71 | 11.00 | 23.75 |
June | 38.67 | 24.03 | 399.00 | 24.24 | 10.83 | 24.27 |
July | 26.83 | 24.85 | 478.33 | 24.41 | 21.33 | 24.44 |
August | 17.50 | 25.39 | 509.33 | 24.36 | 17.50 | 24.39 |
September | 62.50 | 23.96 | 354.33 | 24.28 | 18.83 | 24.33 |
October | 353.17 | 22.80 | 98.33 | 23.09 | 12.17 | 23.13 |
November | 470.00 | 22.11 | 40.17 | 22.02 | 35.17 | 21.93 |
December | 497.00 | 20.94 | 236.67 | 20.77 | 236.67 | 20.69 |
Annual Sum or Average | 3531.00 | 21.76 | 3051.50 | 22.35 | 1071.33 | 22.12 |
Minimum of Months | 17.50 | 20.39 | 40.17 | 20.30 | 10.83 | 20.27 |
Maximum of Months | 502.00 | 25.39 | 509.33 | 24.41 | 403.50 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.61 | 353.17 | 20.48 | 353.17 | 20.42 |
February | 444.83 | 21.30 | 175.67 | 21.02 | 175.67 | 20.87 |
March | 439.50 | 22.44 | 42.83 | 22.44 | 18.67 | 22.37 |
April | 280.17 | 22.88 | 108.83 | 23.26 | 8.33 | 23.26 |
May | 110.67 | 23.51 | 308.00 | 24.21 | 13.17 | 24.26 |
June | 26.50 | 25.33 | 450.33 | 24.45 | 17.83 | 24.52 |
July | 49.00 | 26.01 | 481.33 | 24.69 | 43.67 | 24.82 |
August | 35.67 | 26.32 | 513.17 | 24.57 | 35.67 | 24.68 |
September | 54.67 | 24.49 | 412.17 | 24.46 | 24.17 | 24.54 |
October | 224.67 | 22.90 | 173.17 | 23.56 | 12.67 | 23.59 |
November | 428.83 | 22.62 | 36.33 | 22.66 | 11.17 | 22.61 |
December | 490.33 | 21.27 | 147.17 | 21.06 | 147.17 | 20.93 |
Annual Sum or Average | 3086.83 | 22.09 | 3202.17 | 22.83 | 861.33 | 22.65 |
Minimum of Months | 26.50 | 20.61 | 36.33 | 20.48 | 8.33 | 20.42 |
Maximum of Months | 502.00 | 26.32 | 513.17 | 24.69 | 353.17 | 24.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 495.67 | 20.76 | 263.17 | 20.47 | 259.00 | 20.31 |
February | 410.67 | 21.13 | 158.83 | 20.94 | 146.67 | 20.73 |
March | 400.50 | 22.08 | 81.83 | 22.23 | 29.83 | 22.10 |
April | 341.83 | 22.49 | 91.00 | 22.78 | 16.50 | 22.75 |
May | 210.00 | 22.95 | 222.83 | 23.62 | 25.50 | 23.65 |
June | 104.50 | 23.68 | 398.83 | 24.14 | 61.67 | 24.13 |
July | 94.00 | 24.16 | 477.83 | 24.37 | 87.17 | 24.36 |
August | 104.67 | 24.51 | 510.33 | 24.45 | 103.67 | 24.46 |
September | 94.67 | 23.92 | 402.00 | 24.37 | 48.33 | 24.43 |
October | 225.83 | 22.78 | 223.00 | 23.65 | 37.33 | 23.72 |
November | 339.33 | 22.39 | 79.33 | 22.79 | 10.00 | 22.73 |
December | 451.50 | 21.48 | 103.00 | 21.34 | 82.33 | 21.14 |
Annual Sum or Average | 3273.17 | 22.10 | 3012.00 | 22.83 | 908.00 | 22.69 |
Minimum of Months | 94.00 | 20.76 | 79.33 | 20.47 | 10.00 | 20.31 |
Maximum of Months | 495.67 | 24.51 | 510.33 | 24.45 | 259.00 | 24.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.63 | 345.50 | 20.47 | 345.50 | 20.40 |
February | 442.33 | 21.13 | 184.50 | 20.90 | 183.33 | 20.77 |
March | 425.17 | 22.24 | 75.00 | 22.31 | 32.67 | 22.21 |
April | 296.83 | 22.81 | 104.33 | 23.18 | 9.83 | 23.18 |
May | 124.33 | 23.43 | 288.17 | 24.09 | 12.83 | 24.14 |
June | 38.50 | 24.75 | 431.83 | 24.41 | 18.50 | 24.48 |
July | 43.33 | 25.73 | 482.00 | 24.60 | 38.67 | 24.69 |
August | 32.83 | 26.25 | 512.50 | 24.55 | 32.83 | 24.65 |
September | 58.17 | 24.51 | 408.33 | 24.46 | 25.83 | 24.55 |
October | 244.00 | 22.93 | 167.33 | 23.53 | 13.17 | 23.57 |
November | 415.50 | 22.44 | 44.00 | 22.49 | 19.00 | 22.42 |
December | 488.00 | 21.24 | 166.67 | 21.02 | 166.67 | 20.89 |
Annual Sum or Average | 3111.00 | 22.01 | 3210.17 | 22.75 | 898.83 | 22.56 |
Minimum of Months | 32.83 | 20.63 | 44.00 | 20.47 | 9.83 | 20.40 |
Maximum of Months | 502.00 | 26.25 | 512.50 | 24.60 | 345.50 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.32 | 396.00 | 20.20 | 396.00 | 20.16 |
February | 450.50 | 20.97 | 203.67 | 20.71 | 203.67 | 20.58 |
March | 447.50 | 22.17 | 79.83 | 22.17 | 42.50 | 22.05 |
April | 271.33 | 22.79 | 104.83 | 23.16 | 9.00 | 23.16 |
May | 91.33 | 23.31 | 314.17 | 24.07 | 3.50 | 24.08 |
June | 32.00 | 24.42 | 426.00 | 24.34 | 16.67 | 24.38 |
July | 39.67 | 25.16 | 484.17 | 24.50 | 34.50 | 24.56 |
August | 31.50 | 25.22 | 508.17 | 24.41 | 31.50 | 24.46 |
September | 90.00 | 23.81 | 334.00 | 24.23 | 27.33 | 24.30 |
October | 365.67 | 22.46 | 96.67 | 22.77 | 19.00 | 22.79 |
November | 476.17 | 21.80 | 72.17 | 21.62 | 71.67 | 21.49 |
December | 496.00 | 20.75 | 267.83 | 20.54 | 267.83 | 20.45 |
Annual Sum or Average | 3293.67 | 21.70 | 3287.50 | 22.39 | 1123.17 | 22.15 |
Minimum of Months | 31.50 | 20.32 | 72.17 | 20.20 | 3.50 | 20.16 |
Maximum of Months | 502.00 | 25.22 | 508.17 | 24.50 | 396.00 | 24.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.43 | 299.00 | 20.25 | 299.00 | 20.18 |
February | 369.33 | 21.22 | 155.33 | 20.92 | 153.67 | 20.74 |
March | 324.67 | 22.49 | 60.00 | 22.59 | 17.67 | 22.49 |
April | 168.17 | 22.97 | 142.50 | 23.65 | 10.17 | 23.67 |
May | 72.33 | 24.06 | 297.33 | 24.48 | 18.17 | 24.57 |
June | 43.50 | 25.70 | 381.33 | 24.64 | 34.83 | 24.76 |
July | 72.00 | 26.16 | 413.33 | 24.89 | 67.67 | 25.07 |
August | 59.17 | 26.11 | 430.83 | 24.73 | 59.17 | 24.88 |
September | 79.33 | 24.40 | 306.83 | 24.50 | 36.00 | 24.64 |
October | 247.50 | 22.54 | 130.50 | 23.14 | 19.67 | 23.15 |
November | 385.50 | 22.13 | 53.50 | 22.03 | 40.17 | 21.88 |
December | 415.50 | 20.90 | 191.00 | 20.63 | 191.00 | 20.49 |
Annual Sum or Average | 2664.00 | 22.05 | 2861.50 | 22.77 | 947.17 | 22.60 |
Minimum of Months | 43.50 | 20.43 | 53.50 | 20.25 | 10.17 | 20.18 |
Maximum of Months | 427.00 | 26.16 | 430.83 | 24.89 | 299.00 | 25.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 468.00 | 21.12 | 247.83 | 20.80 | 243.33 | 20.62 |
February | 391.50 | 21.53 | 141.00 | 21.39 | 123.17 | 21.19 |
March | 317.50 | 22.44 | 109.50 | 22.81 | 19.83 | 22.71 |
April | 202.83 | 22.88 | 160.17 | 23.53 | 9.67 | 23.54 |
May | 86.00 | 23.27 | 322.33 | 24.12 | 4.00 | 24.13 |
June | 44.00 | 24.34 | 422.83 | 24.35 | 19.00 | 24.39 |
July | 46.67 | 25.44 | 484.00 | 24.56 | 41.50 | 24.64 |
August | 49.67 | 25.85 | 509.50 | 24.54 | 49.67 | 24.65 |
September | 82.83 | 24.28 | 370.67 | 24.42 | 34.50 | 24.53 |
October | 241.17 | 22.74 | 211.67 | 23.52 | 27.67 | 23.59 |
November | 346.83 | 22.32 | 94.17 | 22.61 | 30.83 | 22.50 |
December | 426.67 | 21.47 | 142.33 | 21.23 | 128.33 | 21.01 |
Annual Sum or Average | 2703.67 | 22.20 | 3216.00 | 23.03 | 731.50 | 22.86 |
Minimum of Months | 44.00 | 21.12 | 94.17 | 20.80 | 4.00 | 20.62 |
Maximum of Months | 468.00 | 25.85 | 509.50 | 24.56 | 243.33 | 24.65 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.58 | 335.67 | 20.37 | 335.67 | 20.28 |
February | 431.83 | 21.17 | 180.17 | 20.93 | 174.00 | 20.76 |
March | 366.00 | 22.27 | 109.33 | 22.51 | 32.50 | 22.39 |
April | 211.83 | 22.95 | 183.17 | 23.59 | 14.67 | 23.62 |
May | 88.33 | 23.71 | 356.67 | 24.24 | 14.00 | 24.30 |
June | 51.50 | 25.09 | 441.33 | 24.48 | 32.33 | 24.58 |
July | 58.83 | 25.76 | 488.33 | 24.64 | 54.33 | 24.76 |
August | 49.50 | 25.90 | 510.67 | 24.57 | 49.50 | 24.67 |
September | 90.33 | 24.30 | 371.50 | 24.41 | 39.17 | 24.53 |
October | 302.17 | 22.54 | 150.17 | 23.11 | 22.50 | 23.15 |
November | 427.00 | 21.96 | 79.00 | 21.90 | 57.67 | 21.75 |
December | 486.33 | 20.99 | 214.33 | 20.73 | 214.17 | 20.59 |
Annual Sum or Average | 3065.67 | 21.94 | 3420.33 | 22.71 | 1040.50 | 22.52 |
Minimum of Months | 49.50 | 20.58 | 79.00 | 20.37 | 14.00 | 20.28 |
Maximum of Months | 502.00 | 25.90 | 510.67 | 24.64 | 335.67 | 24.76 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.65824 | 27.06323 | -0.1480 | 6.55155 |
February | 454.00000 | 23.33158 | 27.67342 | 0.04365 | 5.99769 |
March | 514.00000 | 24.08781 | 30.66627 | 0.29240 | 7.11511 |
April | 485.00000 | 24.30271 | 35.58117 | 0.39614 | 8.56125 |
May | 508.00000 | 24.39732 | 42.14378 | -0.3710 | 8.34722 |
June | 496.00000 | 24.35859 | 44.22200 | -0.3365 | 7.81613 |
July | 497.00000 | 24.43441 | 46.23318 | -0.2948 | 7.27820 |
August | 514.00000 | 24.37119 | 46.55968 | -0.3031 | 7.33056 |
September | 485.00000 | 24.42147 | 44.83658 | -0.3210 | 7.65782 |
October | 502.00000 | 24.30747 | 38.05737 | 0.42206 | 8.98517 |
November | 489.00000 | 24.11119 | 28.88165 | 0.28150 | 6.98435 |
December | 497.00000 | 23.53139 | 28.72528 | 0.10341 | 5.73795 |
Annual Sum or Average | 5943.00000 | 24.03055 | 36.79483 | -0.0209 | 7.37258 |
Minimum of Months | 454.00000 | 22.65824 | 27.06323 | -0.3710 | 5.73795 |
Maximum of Months | 514.00000 | 24.43441 | 46.55968 | 0.42206 | 8.98517 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.12160 | 28.79350 | -0.4952 | 11.15735 |
February | 454.00000 | 21.85175 | 29.54369 | -0.2901 | 8.44969 |
March | 514.00000 | 23.25902 | 33.11013 | 0.10282 | 6.10094 |
April | 485.00000 | 23.79335 | 37.49701 | 0.27799 | 7.11313 |
May | 508.00000 | 24.09301 | 43.72033 | -0.4785 | 10.20530 |
June | 496.00000 | 24.20906 | 45.38768 | -0.4006 | 8.75474 |
July | 497.00000 | 24.28056 | 47.49712 | -0.3568 | 8.02097 |
August | 514.00000 | 24.26471 | 47.76584 | -0.3540 | 7.92276 |
September | 485.00000 | 24.17293 | 46.07300 | -0.4242 | 9.23387 |
October | 502.00000 | 23.61518 | 40.65797 | 0.25234 | 6.98021 |
November | 489.00000 | 22.94778 | 31.83417 | 0.00918 | 5.86803 |
December | 497.00000 | 21.79450 | 31.76995 | -0.2874 | 7.78080 |
Annual Sum or Average | 5943.00000 | 23.29415 | 38.71177 | -0.2038 | 8.13180 |
Minimum of Months | 454.00000 | 21.12160 | 28.79350 | -0.4952 | 5.86803 |
Maximum of Months | 514.00000 | 24.28056 | 47.76584 | 0.27799 | 11.15735 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.60637 | 27.79421 | -0.6546 | 16.12231 |
February | 454.00000 | 21.30706 | 30.06221 | -0.4405 | 11.49396 |
March | 514.00000 | 22.73033 | 33.50438 | -0.0275 | 6.63049 |
April | 485.00000 | 23.52367 | 37.40591 | 0.21109 | 6.88975 |
May | 508.00000 | 24.00242 | 43.13673 | -0.5071 | 11.02926 |
June | 496.00000 | 24.20251 | 44.94285 | -0.3938 | 8.73862 |
July | 497.00000 | 24.29786 | 47.08126 | -0.3400 | 7.85688 |
August | 514.00000 | 24.28386 | 47.45163 | -0.3371 | 7.69174 |
September | 485.00000 | 24.04487 | 45.75625 | -0.4729 | 10.40284 |
October | 502.00000 | 23.08308 | 41.52510 | 0.11852 | 6.58958 |
November | 489.00000 | 22.09297 | 32.90929 | -0.2031 | 7.27701 |
December | 497.00000 | 21.07805 | 32.37208 | -0.4857 | 11.58397 |
Annual Sum or Average | 5943.00000 | 22.95045 | 38.73088 | -0.2938 | 9.34308 |
Minimum of Months | 454.00000 | 20.60637 | 27.79421 | -0.6546 | 6.58958 |
Maximum of Months | 514.00000 | 24.29786 | 47.45163 | 0.21109 | 16.12231 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.06336 | 29.35686 | -0.8365 | 22.76344 |
February | 454.00000 | 20.73626 | 31.37464 | -0.6151 | 16.21837 |
March | 514.00000 | 22.04311 | 35.97661 | -0.1906 | 8.61198 |
April | 485.00000 | 23.11975 | 40.57971 | 0.13144 | 7.66895 |
May | 508.00000 | 23.91020 | 46.11842 | -0.5039 | 12.01918 |
June | 496.00000 | 24.25192 | 47.41756 | -0.3181 | 8.30263 |
July | 497.00000 | 24.42646 | 50.74773 | -0.2270 | 7.28015 |
August | 514.00000 | 24.35826 | 51.33329 | -0.2447 | 7.12594 |
September | 485.00000 | 23.95453 | 49.84801 | -0.4723 | 11.56714 |
October | 502.00000 | 22.44887 | 46.24270 | -0.0186 | 7.48718 |
November | 489.00000 | 21.32516 | 36.40076 | -0.3933 | 10.55057 |
December | 497.00000 | 20.36501 | 33.40415 | -0.6932 | 18.00600 |
Annual Sum or Average | 5943.00000 | 22.59826 | 41.64572 | -0.3636 | 11.42824 |
Minimum of Months | 454.00000 | 20.06336 | 29.35686 | -0.8365 | 7.12594 |
Maximum of Months | 514.00000 | 24.42646 | 51.33329 | 0.13144 | 22.76344 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.23655 | 30.02862 | -0.7691 | 20.32841 |
February | 454.00000 | 21.13816 | 31.57462 | -0.4967 | 14.21840 |
March | 514.00000 | 22.65579 | 35.34851 | -0.0304 | 7.80276 |
April | 485.00000 | 23.57505 | 39.39949 | 0.26928 | 8.66435 |
May | 508.00000 | 24.15033 | 45.09787 | -0.3676 | 10.18049 |
June | 496.00000 | 24.36312 | 46.75363 | -0.2175 | 7.53934 |
July | 497.00000 | 24.52980 | 49.94229 | -0.1279 | 7.29061 |
August | 514.00000 | 24.44052 | 50.65415 | -0.1559 | 6.91187 |
September | 485.00000 | 24.11079 | 49.09999 | -0.3681 | 10.33957 |
October | 502.00000 | 22.94542 | 45.06827 | 0.11645 | 8.16259 |
November | 489.00000 | 21.78374 | 36.38054 | -0.2693 | 9.11645 |
December | 497.00000 | 20.57536 | 33.95293 | -0.6183 | 16.04003 |
Annual Sum or Average | 5943.00000 | 22.88932 | 41.18234 | -0.2514 | 10.51697 |
Minimum of Months | 454.00000 | 20.23655 | 30.02862 | -0.7691 | 6.91187 |
Maximum of Months | 514.00000 | 24.52980 | 50.65415 | 0.26928 | 20.32841 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.98817 | 28.14015 | -0.5682 | 16.88259 |
February | 454.00000 | 21.63466 | 29.87329 | -0.3632 | 12.79562 |
March | 514.00000 | 22.81401 | 33.90912 | 0.01569 | 8.57887 |
April | 485.00000 | 23.42242 | 39.34505 | 0.22482 | 8.62812 |
May | 508.00000 | 23.94199 | 45.79799 | -0.4755 | 11.85165 |
June | 496.00000 | 24.23060 | 47.44764 | -0.3200 | 8.61213 |
July | 497.00000 | 24.43418 | 50.66161 | -0.2157 | 7.39161 |
August | 514.00000 | 24.39506 | 50.89489 | -0.2000 | 7.01786 |
September | 485.00000 | 24.09918 | 48.75593 | -0.3741 | 10.55857 |
October | 502.00000 | 23.16511 | 43.39093 | 0.18919 | 9.32178 |
November | 489.00000 | 22.42376 | 33.60900 | -0.1015 | 9.35562 |
December | 497.00000 | 21.38668 | 31.59306 | -0.4073 | 13.36450 |
Annual Sum or Average | 5943.00000 | 23.08928 | 40.36751 | -0.2157 | 10.34309 |
Minimum of Months | 454.00000 | 20.98817 | 28.14015 | -0.5682 | 7.01786 |
Maximum of Months | 514.00000 | 24.43418 | 50.89489 | 0.22482 | 16.88259 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.30622 | 29.93843 | -0.7593 | 20.65402 |
February | 454.00000 | 21.05912 | 31.60594 | -0.5216 | 14.85214 |
March | 514.00000 | 22.48206 | 35.42183 | -0.0673 | 8.82705 |
April | 485.00000 | 23.39182 | 40.03159 | 0.22779 | 8.85565 |
May | 508.00000 | 24.00599 | 45.85141 | -0.4238 | 11.24562 |
June | 496.00000 | 24.29214 | 47.38635 | -0.2559 | 8.21447 |
July | 497.00000 | 24.47269 | 50.73468 | -0.1653 | 7.36611 |
August | 514.00000 | 24.42286 | 51.10947 | -0.1701 | 7.01606 |
September | 485.00000 | 24.07458 | 49.54018 | -0.3887 | 10.76597 |
October | 502.00000 | 22.78761 | 45.64826 | 0.08086 | 8.38944 |
November | 489.00000 | 21.73295 | 36.24906 | -0.2850 | 10.01428 |
December | 497.00000 | 20.65280 | 33.87459 | -0.6101 | 16.32661 |
Annual Sum or Average | 5943.00000 | 22.82063 | 41.52545 | -0.2767 | 11.01160 |
Minimum of Months | 454.00000 | 20.30622 | 29.93843 | -0.7593 | 7.01606 |
Maximum of Months | 514.00000 | 24.47269 | 51.10947 | 0.22779 | 20.65402 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.39103 | 29.31171 | -0.7354 | 18.06857 |
February | 454.00000 | 20.85571 | 31.73538 | -0.5702 | 13.91029 |
March | 514.00000 | 21.85650 | 37.10795 | -0.2363 | 7.76941 |
April | 485.00000 | 22.69967 | 42.42146 | 0.01456 | 6.57851 |
May | 508.00000 | 23.73780 | 47.59781 | -0.6090 | 14.01332 |
June | 496.00000 | 24.18596 | 47.38865 | -0.3855 | 8.67341 |
July | 497.00000 | 24.35602 | 49.91879 | -0.2913 | 7.35094 |
August | 514.00000 | 24.32269 | 50.02236 | -0.2896 | 7.21153 |
September | 485.00000 | 24.17445 | 48.87222 | -0.4020 | 9.19621 |
October | 502.00000 | 23.16335 | 44.24821 | 0.15909 | 6.76809 |
November | 489.00000 | 22.17837 | 35.01874 | -0.1620 | 7.05470 |
December | 497.00000 | 20.93755 | 32.78512 | -0.5132 | 11.87763 |
Annual Sum or Average | 5943.00000 | 22.75181 | 41.44537 | -0.3342 | 9.85384 |
Minimum of Months | 454.00000 | 20.39103 | 29.31171 | -0.7354 | 6.57851 |
Maximum of Months | 514.00000 | 24.35602 | 50.02236 | 0.15909 | 18.06857 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.61230 | 30.03082 | -0.6575 | 15.71219 |
February | 454.00000 | 21.35745 | 31.93612 | -0.4301 | 11.64910 |
March | 514.00000 | 22.67441 | 36.33549 | -0.0302 | 6.78222 |
April | 485.00000 | 23.42696 | 40.84027 | 0.20972 | 7.36731 |
May | 508.00000 | 24.10741 | 46.13004 | -0.4325 | 10.65711 |
June | 496.00000 | 24.35701 | 46.53821 | -0.2649 | 7.39769 |
July | 497.00000 | 24.52864 | 49.04124 | -0.1687 | 6.94400 |
August | 514.00000 | 24.45210 | 49.26760 | -0.1826 | 6.69761 |
September | 485.00000 | 24.33154 | 48.14654 | -0.2932 | 8.08431 |
October | 502.00000 | 23.63813 | 42.99503 | 0.29250 | 8.17608 |
November | 489.00000 | 22.81445 | 34.59746 | -0.0020 | 6.54422 |
December | 497.00000 | 21.30469 | 33.16299 | -0.4056 | 10.01670 |
Annual Sum or Average | 5943.00000 | 23.14639 | 40.82235 | -0.1962 | 8.81978 |
Minimum of Months | 454.00000 | 20.61230 | 30.03082 | -0.6575 | 6.54422 |
Maximum of Months | 514.00000 | 24.52864 | 49.26760 | 0.29250 | 15.71219 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.82996 | 26.75949 | -0.5520 | 14.71265 |
February | 454.00000 | 21.46690 | 29.03814 | -0.3636 | 11.55672 |
March | 514.00000 | 22.57577 | 34.55128 | -0.0254 | 7.45780 |
April | 485.00000 | 22.99933 | 40.67284 | 0.11217 | 7.31494 |
May | 508.00000 | 23.65272 | 49.09262 | -0.5982 | 14.43242 |
June | 496.00000 | 24.12641 | 50.97013 | -0.3743 | 8.94848 |
July | 497.00000 | 24.38142 | 54.38450 | -0.2432 | 7.02534 |
August | 514.00000 | 24.43387 | 54.73757 | -0.1838 | 6.45858 |
September | 485.00000 | 24.26546 | 50.54159 | -0.2936 | 8.52036 |
October | 502.00000 | 23.64457 | 42.43772 | 0.33515 | 9.56906 |
November | 489.00000 | 23.03578 | 31.82716 | 0.09357 | 7.87558 |
December | 497.00000 | 21.74421 | 29.98675 | -0.2581 | 9.27136 |
Annual Sum or Average | 5943.00000 | 23.10782 | 41.35454 | -0.1956 | 9.42118 |
Minimum of Months | 454.00000 | 20.82996 | 26.75949 | -0.5982 | 6.45858 |
Maximum of Months | 514.00000 | 24.43387 | 54.73757 | 0.33515 | 14.71265 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.62985 | 29.99202 | -0.6564 | 15.98502 |
February | 454.00000 | 21.21992 | 32.02937 | -0.4653 | 12.22614 |
March | 514.00000 | 22.58057 | 36.20288 | -0.0499 | 7.19803 |
April | 485.00000 | 23.33954 | 41.10260 | 0.18708 | 7.35949 |
May | 508.00000 | 24.02135 | 46.62413 | -0.4721 | 11.14530 |
June | 496.00000 | 24.31042 | 46.99056 | -0.2949 | 7.77195 |
July | 497.00000 | 24.46751 | 49.61911 | -0.2063 | 7.00069 |
August | 514.00000 | 24.44441 | 49.51720 | -0.1929 | 6.73949 |
September | 485.00000 | 24.33123 | 48.34378 | -0.3025 | 8.18555 |
October | 502.00000 | 23.59934 | 43.28148 | 0.28091 | 8.06306 |
November | 489.00000 | 22.71478 | 34.55475 | -0.0251 | 6.87199 |
December | 497.00000 | 21.28332 | 33.17986 | -0.4157 | 10.39027 |
Annual Sum or Average | 5943.00000 | 23.09180 | 41.02423 | -0.2167 | 9.06048 |
Minimum of Months | 454.00000 | 20.62985 | 29.99202 | -0.6564 | 6.73949 |
Maximum of Months | 514.00000 | 24.46751 | 49.61911 | 0.28091 | 15.98502 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.31886 | 29.22029 | -0.7404 | 18.85771 |
February | 454.00000 | 20.98921 | 31.13787 | -0.5236 | 13.62795 |
March | 514.00000 | 22.40809 | 35.67111 | -0.0911 | 7.23248 |
April | 485.00000 | 23.37248 | 40.43381 | 0.19443 | 7.35403 |
May | 508.00000 | 24.03764 | 46.18783 | -0.4675 | 10.55602 |
June | 496.00000 | 24.27845 | 47.39689 | -0.3221 | 7.90497 |
July | 497.00000 | 24.42768 | 50.56636 | -0.2423 | 7.09628 |
August | 514.00000 | 24.35745 | 51.01204 | -0.2607 | 7.09089 |
September | 485.00000 | 24.10367 | 49.61626 | -0.4221 | 9.87804 |
October | 502.00000 | 22.88039 | 45.20701 | 0.09374 | 6.89959 |
November | 489.00000 | 21.85573 | 35.57075 | -0.2437 | 8.04602 |
December | 497.00000 | 20.75143 | 32.83082 | -0.5652 | 13.75103 |
Annual Sum or Average | 5943.00000 | 22.82909 | 41.31639 | -0.2981 | 9.82937 |
Minimum of Months | 454.00000 | 20.31886 | 29.22029 | -0.7404 | 6.89959 |
Maximum of Months | 514.00000 | 24.42768 | 51.01204 | 0.19443 | 18.85771 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.43443 | 29.60222 | -0.6943 | 17.52781 |
February | 385.00000 | 21.35087 | 31.17874 | -0.4224 | 12.31888 |
March | 433.00000 | 22.90286 | 34.61709 | 0.03375 | 7.09750 |
April | 410.00000 | 23.73730 | 39.17506 | 0.30029 | 8.51812 |
May | 430.00000 | 24.29038 | 44.90181 | -0.3479 | 9.59513 |
June | 418.00000 | 24.46430 | 46.59884 | -0.2218 | 7.46574 |
July | 422.00000 | 24.64690 | 49.74950 | -0.1287 | 7.25211 |
August | 433.00000 | 24.53486 | 50.43252 | -0.1635 | 7.02998 |
September | 410.00000 | 24.29179 | 48.90188 | -0.3266 | 9.18522 |
October | 427.00000 | 23.26263 | 44.12389 | 0.19578 | 7.94858 |
November | 417.00000 | 22.28216 | 35.22410 | -0.1352 | 7.50356 |
December | 422.00000 | 20.93966 | 33.27526 | -0.5037 | 12.61961 |
Annual Sum or Average | 5034.00000 | 23.10515 | 40.70995 | -0.2002 | 9.48713 |
Minimum of Months | 385.00000 | 20.43443 | 29.60222 | -0.6943 | 7.02998 |
Maximum of Months | 433.00000 | 24.64690 | 50.43252 | 0.30029 | 17.52781 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.35065 | 27.77712 | -0.4546 | 13.74193 |
February | 454.00000 | 21.94936 | 29.48968 | -0.2631 | 10.62978 |
March | 514.00000 | 23.15606 | 33.55508 | 0.10839 | 7.75498 |
April | 485.00000 | 23.66194 | 39.15449 | 0.28367 | 8.39431 |
May | 508.00000 | 24.07075 | 45.83723 | -0.4396 | 10.34402 |
June | 496.00000 | 24.26905 | 47.39930 | -0.3212 | 8.08917 |
July | 497.00000 | 24.44899 | 50.44718 | -0.2278 | 7.15114 |
August | 514.00000 | 24.40571 | 50.53814 | -0.2141 | 6.94164 |
September | 485.00000 | 24.24020 | 48.55651 | -0.3283 | 9.01931 |
October | 502.00000 | 23.52422 | 42.46448 | 0.28485 | 9.13359 |
November | 489.00000 | 22.93461 | 32.67172 | 0.03997 | 8.11972 |
December | 497.00000 | 21.85992 | 30.76967 | -0.2668 | 10.23598 |
Annual Sum or Average | 5943.00000 | 23.33290 | 39.97139 | -0.1497 | 9.11796 |
Minimum of Months | 454.00000 | 21.35065 | 27.77712 | -0.4546 | 6.94164 |
Maximum of Months | 514.00000 | 24.44899 | 50.53814 | 0.28485 | 13.74193 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.58454 | 29.82641 | -0.6597 | 16.99010 |
February | 454.00000 | 21.32584 | 31.36188 | -0.4287 | 12.42552 |
March | 514.00000 | 22.84454 | 35.08263 | 0.03035 | 7.67408 |
April | 485.00000 | 23.65234 | 39.81332 | 0.29081 | 8.61583 |
May | 508.00000 | 24.14187 | 45.85643 | -0.3865 | 9.71370 |
June | 496.00000 | 24.33722 | 47.31088 | -0.2558 | 7.66013 |
July | 497.00000 | 24.48915 | 50.50041 | -0.1774 | 7.07881 |
August | 514.00000 | 24.43292 | 50.74949 | -0.1845 | 6.90001 |
September | 485.00000 | 24.22107 | 49.30524 | -0.3407 | 9.17104 |
October | 502.00000 | 23.20175 | 44.60247 | 0.18832 | 7.95347 |
November | 489.00000 | 22.25331 | 35.34893 | -0.1394 | 7.89860 |
December | 497.00000 | 21.05667 | 33.27544 | -0.4804 | 12.40813 |
Annual Sum or Average | 5943.00000 | 23.05828 | 41.16192 | -0.2108 | 9.51741 |
Minimum of Months | 454.00000 | 20.58454 | 29.82641 | -0.6597 | 6.90001 |
Maximum of Months | 514.00000 | 24.48915 | 50.74949 | 0.29081 | 16.99010 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.169693E+10 | 0.457721E+09 | 52.87 | 0.103826E+10 | 0.658669E+09 | 0.00 | 0.55 | 19-JAN-22:00 | 0.00 | 01-JAN-00:05 | 17291.69 | 19-JAN-22:00 | 12916.94 | 31-JAN-15:00 | 8500.26 | 19-JAN-16:20 | 4474.27 | 19-JAN-22:00 | 0.00 |
February | 0.438401E+10 | 0.117119E+10 | 132.11 | 0.358988E+10 | 0.794132E+09 | 0.00 | 0.89 | 28-FEB-14:00 | 0.00 | 01-FEB-00:10 | 30310.42 | 28-FEB-14:00 | 30310.42 | 28-FEB-14:00 | 6998.55 | 18-FEB-16:30 | 7361.38 | 28-FEB-14:00 | 0.00 |
March | 0.142343E+11 | 0.362135E+10 | 267.83 | 0.110387E+11 | 0.319564E+10 | 0.00 | 1.00 | 29-MAR-15:00 | 0.00 | 01-MAR-00:10 | 48406.90 | 30-MAR-15:20 | 48406.90 | 30-MAR-15:20 | 12845.08 | 29-MAR-09:00 | 12192.82 | 30-MAR-15:20 | 0.00 |
April | 0.240395E+11 | 0.604956E+10 | 331.46 | 0.195729E+11 | 0.446654E+10 | 0.00 | 1.00 | 04-APR-12:20 | 0.00 | 01-APR-00:10 | 52074.40 | 17-APR-14:50 | 52074.40 | 17-APR-14:50 | 15753.69 | 04-APR-07:30 | 13526.62 | 17-APR-14:50 | 0.00 |
May | 0.467797E+11 | 0.115507E+11 | 411.66 | 0.351982E+11 | 0.115815E+11 | 0.00 | 1.00 | 01-MAY-15:10 | 0.00 | 01-MAY-00:10 | 69091.25 | 30-MAY-11:50 | 53874.08 | 30-MAY-15:10 | 22274.83 | 08-MAY-06:03 | 17923.87 | 30-MAY-15:10 | 0.00 |
June | 0.718038E+11 | 0.184168E+11 | 435.26 | 0.533718E+11 | 0.184319E+11 | 0.00 | 1.00 | 01-JUN-06:05 | 0.00 | 01-JUN-00:10 | 81549.77 | 27-JUN-12:00 | 67425.26 | 26-JUN-06:03 | 33025.91 | 29-JUN-06:03 | 21943.85 | 23-JUN-12:05 | 0.00 |
July | 0.826753E+11 | 0.214246E+11 | 440.73 | 0.581133E+11 | 0.245620E+11 | 0.00 | 1.00 | 01-JUL-06:05 | 0.00 | 01-JUL-00:10 | 91364.53 | 06-JUL-06:03 | 72394.88 | 17-JUL-05:12 | 40719.81 | 26-JUL-06:03 | 25360.46 | 07-JUL-12:05 | 0.00 |
August | 0.947050E+11 | 0.242602E+11 | 466.46 | 0.652210E+11 | 0.294840E+11 | 0.00 | 1.00 | 01-AUG-06:03 | 0.00 | 01-AUG-00:10 | 103610.67 | 21-AUG-05:12 | 77617.94 | 21-AUG-05:12 | 50592.71 | 23-AUG-05:12 | 24757.23 | 01-AUG-15:20 | 0.00 |
September | 0.599638E+11 | 0.147309E+11 | 412.56 | 0.438694E+11 | 0.160943E+11 | 0.00 | 1.00 | 01-SEP-06:05 | 0.00 | 01-SEP-00:10 | 85688.77 | 06-SEP-12:03 | 70490.81 | 05-SEP-05:12 | 26861.99 | 07-SEP-06:03 | 23049.66 | 07-SEP-16:00 | 0.00 |
October | 0.264362E+11 | 0.649314E+10 | 304.38 | 0.194476E+11 | 0.698859E+10 | 0.00 | 1.00 | 02-OCT-06:03 | 0.00 | 01-OCT-00:10 | 67127.48 | 10-OCT-15:50 | 55435.82 | 10-OCT-16:00 | 29416.52 | 19-OCT-06:03 | 17749.51 | 10-OCT-16:00 | 0.00 |
November | 0.100977E+11 | 0.259816E+10 | 222.34 | 0.766644E+10 | 0.243127E+10 | 0.00 | 0.96 | 02-NOV-13:00 | 0.00 | 01-NOV-00:10 | 33880.38 | 02-NOV-13:00 | 27429.93 | 02-NOV-15:10 | 11422.23 | 02-NOV-10:50 | 7878.03 | 02-NOV-13:00 | 0.00 |
December | 0.351680E+10 | 0.913488E+09 | 113.37 | 0.226456E+10 | 0.125224E+10 | 0.00 | 0.90 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 30975.63 | 12-DEC-14:00 | 23596.29 | 12-DEC-14:00 | 14509.96 | 13-DEC-16:10 | 7311.86 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.440333E+12 | 0.111688E+12 | 3591.03 | 0.320392E+12 | 0.119941E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.169693E+10 | 0.457721E+09 | 52.87 | 0.103826E+10 | 0.658669E+09 | 0.00 | 0.55 | 0.00 | 17291.69 | 12916.94 | 6998.55 | 4474.27 | 0.00 | ||||||
Maximum of Months | 0.947050E+11 | 0.242602E+11 | 466.46 | 0.652210E+11 | 0.294840E+11 | 0.00 | 1.00 | 0.00 | 103610.67 | 77617.94 | 50592.71 | 25360.46 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.158728E+10 | 0.426735E+09 | 52.87 | 0.967346E+09 | 0.619929E+09 | 0.00 | 0.58 | 19-JAN-16:00 | 0.00 | 01-JAN-00:05 | 16705.15 | 19-JAN-16:00 | 11047.29 | 31-JAN-15:10 | 8247.90 | 19-JAN-16:00 | 4286.73 | 19-JAN-16:00 | 0.00 |
February | 0.409099E+10 | 0.109519E+10 | 134.58 | 0.334604E+10 | 0.744945E+09 | 0.00 | 0.88 | 28-FEB-15:05 | 0.00 | 01-FEB-00:10 | 27359.41 | 28-FEB-15:05 | 27359.41 | 28-FEB-15:05 | 7168.44 | 18-FEB-16:00 | 6606.81 | 28-FEB-15:05 | 0.00 |
March | 0.125215E+11 | 0.320842E+10 | 273.54 | 0.963535E+10 | 0.288612E+10 | 0.00 | 1.00 | 29-MAR-14:05 | 0.00 | 01-MAR-00:10 | 47803.38 | 30-MAR-15:20 | 47803.38 | 30-MAR-15:20 | 12082.69 | 31-MAR-08:40 | 12038.45 | 30-MAR-15:20 | 0.00 |
April | 0.226273E+11 | 0.569812E+10 | 341.72 | 0.185202E+11 | 0.410715E+10 | 0.00 | 1.00 | 04-APR-12:50 | 0.00 | 01-APR-00:10 | 53159.48 | 17-APR-15:30 | 53159.48 | 17-APR-15:30 | 13575.54 | 21-APR-10:50 | 13804.25 | 17-APR-15:30 | 0.00 |
May | 0.432382E+11 | 0.106957E+11 | 425.26 | 0.325840E+11 | 0.106542E+11 | 0.00 | 1.00 | 01-MAY-14:05 | 0.00 | 01-MAY-00:10 | 65525.89 | 30-MAY-14:05 | 52713.51 | 30-MAY-14:05 | 17494.66 | 31-MAY-10:05 | 17550.14 | 30-MAY-14:05 | 0.00 |
June | 0.657545E+11 | 0.168302E+11 | 442.01 | 0.480524E+11 | 0.177020E+11 | 0.00 | 1.00 | 01-JUN-07:40 | 0.00 | 01-JUN-00:10 | 89340.57 | 26-JUN-06:03 | 68926.80 | 26-JUN-05:12 | 24930.77 | 23-JUN-10:05 | 20514.52 | 26-JUN-06:03 | 0.00 |
July | 0.756439E+11 | 0.195197E+11 | 446.84 | 0.518482E+11 | 0.237957E+11 | 0.00 | 1.00 | 01-JUL-06:05 | 0.00 | 01-JUL-00:10 | 81278.42 | 06-JUL-06:03 | 68558.75 | 17-JUL-05:12 | 28136.99 | 06-JUL-06:03 | 23469.70 | 07-JUL-16:00 | 0.00 |
August | 0.846260E+11 | 0.215702E+11 | 466.85 | 0.562160E+11 | 0.284100E+11 | 0.00 | 1.00 | 01-AUG-06:03 | 0.00 | 01-AUG-00:10 | 102559.79 | 21-AUG-05:12 | 68844.20 | 07-AUG-05:12 | 37332.78 | 23-AUG-05:12 | 23466.24 | 21-AUG-05:12 | 0.00 |
September | 0.504734E+11 | 0.124443E+11 | 413.28 | 0.355598E+11 | 0.149136E+11 | 0.00 | 1.00 | 01-SEP-08:40 | 0.00 | 01-SEP-00:10 | 77838.52 | 06-SEP-14:05 | 55624.24 | 07-SEP-15:30 | 23267.86 | 16-SEP-13:00 | 20746.01 | 06-SEP-14:05 | 0.00 |
October | 0.215511E+11 | 0.533605E+10 | 303.33 | 0.153257E+11 | 0.622545E+10 | 0.00 | 1.00 | 02-OCT-09:00 | 0.00 | 01-OCT-00:10 | 60930.39 | 11-OCT-14:05 | 46894.84 | 10-OCT-15:40 | 23045.18 | 18-OCT-15:00 | 15662.85 | 10-OCT-14:05 | 0.00 |
November | 0.823031E+10 | 0.214729E+10 | 219.61 | 0.599037E+10 | 0.223994E+10 | 0.00 | 0.87 | 02-NOV-14:05 | 0.00 | 01-NOV-00:10 | 26906.26 | 02-NOV-14:05 | 21045.96 | 08-NOV-15:05 | 9950.80 | 27-NOV-18:00 | 6403.56 | 02-NOV-14:05 | 0.00 |
December | 0.294560E+10 | 0.777115E+09 | 112.94 | 0.188711E+10 | 0.105850E+10 | 0.00 | 0.83 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 25320.24 | 12-DEC-14:00 | 17786.73 | 12-DEC-14:00 | 10197.50 | 13-DEC-11:05 | 6094.41 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.393290E+12 | 0.997491E+11 | 3632.84 | 0.279932E+12 | 0.113358E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.158728E+10 | 0.426735E+09 | 52.87 | 0.967346E+09 | 0.619929E+09 | 0.00 | 0.58 | 0.00 | 16705.15 | 11047.29 | 7168.44 | 4286.73 | 0.00 | ||||||
Maximum of Months | 0.846260E+11 | 0.215702E+11 | 466.85 | 0.562160E+11 | 0.284100E+11 | 0.00 | 1.00 | 0.00 | 102559.79 | 68926.80 | 37332.78 | 23469.70 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.164725E+10 | 0.446479E+09 | 53.83 | 0.994962E+09 | 0.652290E+09 | 0.00 | 0.53 | 19-JAN-16:00 | 0.00 | 01-JAN-00:05 | 16908.16 | 19-JAN-16:00 | 11360.17 | 31-JAN-15:00 | 8367.04 | 19-JAN-16:00 | 4396.92 | 19-JAN-16:00 | 0.00 |
February | 0.422118E+10 | 0.113839E+10 | 133.78 | 0.339745E+10 | 0.823731E+09 | 0.00 | 0.78 | 28-FEB-15:30 | 0.00 | 01-FEB-00:10 | 26241.94 | 28-FEB-15:30 | 26241.94 | 28-FEB-15:30 | 7220.21 | 18-FEB-16:00 | 6475.52 | 28-FEB-15:00 | 0.00 |
March | 0.131092E+11 | 0.338616E+10 | 274.42 | 0.998532E+10 | 0.312392E+10 | 0.00 | 1.00 | 29-MAR-14:30 | 0.00 | 01-MAR-00:10 | 53557.79 | 30-MAR-15:20 | 53557.79 | 30-MAR-15:20 | 10704.20 | 28-MAR-12:50 | 13487.68 | 30-MAR-15:20 | 0.00 |
April | 0.244009E+11 | 0.618025E+10 | 343.39 | 0.199205E+11 | 0.448044E+10 | 0.00 | 1.00 | 04-APR-13:20 | 0.00 | 01-APR-00:10 | 59885.04 | 17-APR-16:00 | 59885.04 | 17-APR-16:00 | 13645.72 | 23-APR-13:03 | 15550.68 | 17-APR-16:00 | 0.00 |
May | 0.468896E+11 | 0.116843E+11 | 430.12 | 0.357362E+11 | 0.111534E+11 | 0.00 | 1.00 | 01-MAY-14:00 | 0.00 | 01-MAY-00:10 | 73796.93 | 30-MAY-15:00 | 61737.70 | 16-MAY-16:00 | 18303.00 | 24-MAY-16:00 | 19713.63 | 30-MAY-15:00 | 0.00 |
June | 0.709506E+11 | 0.182686E+11 | 444.14 | 0.527854E+11 | 0.181652E+11 | 0.00 | 1.00 | 01-JUN-09:00 | 0.00 | 01-JUN-00:10 | 89779.87 | 26-JUN-06:03 | 69670.60 | 26-JUN-05:12 | 24762.54 | 23-JUN-10:40 | 22647.57 | 12-JUN-15:00 | 0.00 |
July | 0.811768E+11 | 0.210983E+11 | 450.48 | 0.569859E+11 | 0.241909E+11 | 0.00 | 1.00 | 01-JUL-08:00 | 0.00 | 01-JUL-00:10 | 88293.04 | 07-JUL-16:00 | 70191.54 | 09-JUL-16:22 | 27852.43 | 26-JUL-10:40 | 26642.64 | 07-JUL-16:00 | 0.00 |
August | 0.899362E+11 | 0.230683E+11 | 469.41 | 0.610800E+11 | 0.288562E+11 | 0.00 | 1.00 | 01-AUG-06:03 | 0.00 | 01-AUG-00:10 | 89112.26 | 21-AUG-05:12 | 70201.74 | 02-AUG-16:00 | 34283.12 | 23-AUG-05:12 | 26073.22 | 01-AUG-15:00 | 0.00 |
September | 0.522279E+11 | 0.129902E+11 | 415.36 | 0.368162E+11 | 0.154117E+11 | 0.00 | 1.00 | 01-SEP-10:00 | 0.00 | 01-SEP-00:10 | 84309.34 | 06-SEP-14:00 | 63428.25 | 07-SEP-15:30 | 24275.71 | 16-SEP-13:40 | 22735.64 | 07-SEP-16:00 | 0.00 |
October | 0.217913E+11 | 0.545079E+10 | 300.97 | 0.152454E+11 | 0.654591E+10 | 0.00 | 1.00 | 02-OCT-10:20 | 0.00 | 01-OCT-00:10 | 64277.28 | 10-OCT-14:00 | 51871.38 | 10-OCT-15:30 | 23170.18 | 18-OCT-15:00 | 16634.34 | 10-OCT-14:00 | 0.00 |
November | 0.832019E+10 | 0.219585E+10 | 218.82 | 0.591448E+10 | 0.240571E+10 | 0.00 | 0.80 | 02-NOV-14:30 | 0.00 | 01-NOV-00:10 | 27293.32 | 02-NOV-14:30 | 19530.77 | 02-NOV-14:30 | 10310.16 | 27-NOV-18:00 | 6621.11 | 02-NOV-14:30 | 0.00 |
December | 0.303008E+10 | 0.805723E+09 | 111.96 | 0.192175E+10 | 0.110833E+10 | 0.00 | 0.78 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 26675.89 | 12-DEC-14:00 | 18381.30 | 12-DEC-14:15 | 9703.83 | 13-DEC-11:10 | 6503.65 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.417701E+12 | 0.106713E+12 | 3646.67 | 0.300783E+12 | 0.116918E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.164725E+10 | 0.446479E+09 | 53.83 | 0.994962E+09 | 0.652290E+09 | 0.00 | 0.53 | 0.00 | 16908.16 | 11360.17 | 7220.21 | 4396.92 | 0.00 | ||||||
Maximum of Months | 0.899362E+11 | 0.230683E+11 | 469.41 | 0.610800E+11 | 0.288562E+11 | 0.00 | 1.00 | 0.00 | 89779.87 | 70201.74 | 34283.12 | 26642.64 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 276.89 | 0.00 | 276.89 | 52.05 | 1655.91 | 0.00 | 0.00 | 0.00 |
February | 306.91 | 0.00 | 306.91 | 149.10 | 1360.94 | 0.00 | 0.00 | 0.00 |
March | 430.88 | 0.00 | 430.88 | 325.71 | 865.44 | 0.00 | 0.00 | 0.00 |
April | 521.19 | 2.31 | 518.87 | 594.50 | 700.48 | 0.00 | 0.00 | 0.00 |
May | 623.33 | 19.89 | 603.44 | 885.91 | 459.14 | 0.00 | 0.00 | 0.00 |
June | 686.00 | 45.29 | 640.71 | 1250.20 | 292.37 | 0.00 | 0.00 | 0.00 |
July | 647.25 | 31.46 | 615.78 | 1244.41 | 212.76 | 0.00 | 0.00 | 0.00 |
August | 575.62 | 6.27 | 569.35 | 1135.42 | 176.77 | 0.00 | 0.00 | 0.00 |
September | 435.11 | 0.06 | 435.05 | 661.21 | 388.56 | 0.00 | 0.00 | 0.00 |
October | 330.83 | 0.00 | 330.83 | 314.08 | 793.90 | 0.00 | 0.00 | 0.00 |
November | 296.08 | 0.00 | 296.08 | 183.71 | 1064.19 | 0.00 | 0.00 | 0.00 |
December | 255.96 | 0.00 | 255.96 | 58.72 | 1328.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 449.61 | 8.81 | 440.80 | 573.61 | 771.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 255.96 | 0.00 | 255.96 | 52.05 | 176.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 686.00 | 45.29 | 640.71 | 1250.20 | 1655.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 405.39 | 182.85 | 222.54 | 307.43 | 989.16 | 0.00 | 0.00 | 0.00 |
February | 511.07 | 274.59 | 236.48 | 519.29 | 821.01 | 0.00 | 0.00 | 0.00 |
March | 642.99 | 292.71 | 350.28 | 752.61 | 539.76 | 0.00 | 0.00 | 0.00 |
April | 777.54 | 354.54 | 423.00 | 1087.37 | 446.92 | 0.00 | 0.00 | 0.00 |
May | 853.79 | 361.06 | 492.74 | 1315.51 | 305.98 | 0.00 | 0.00 | 0.00 |
June | 883.96 | 370.49 | 513.47 | 1544.40 | 196.72 | 0.00 | 0.00 | 0.00 |
July | 861.90 | 362.35 | 499.54 | 1552.43 | 143.81 | 0.00 | 0.00 | 0.00 |
August | 788.35 | 312.77 | 475.59 | 1445.74 | 118.84 | 0.00 | 0.00 | 0.00 |
September | 647.92 | 287.08 | 360.84 | 1038.28 | 253.88 | 0.00 | 0.00 | 0.00 |
October | 552.73 | 287.60 | 265.13 | 726.49 | 499.41 | 0.00 | 0.00 | 0.00 |
November | 441.91 | 200.10 | 241.82 | 466.93 | 646.60 | 0.00 | 0.00 | 0.00 |
December | 382.78 | 174.49 | 208.29 | 315.26 | 795.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 646.51 | 288.34 | 358.17 | 924.74 | 477.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 382.78 | 174.49 | 208.29 | 307.43 | 118.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 883.96 | 370.49 | 513.47 | 1552.43 | 989.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1480.84 | 1032.44 | 448.40 | 1740.38 | 1398.65 | 0.00 | 0.00 | 0.00 |
February | 1382.12 | 926.47 | 455.65 | 1756.96 | 1209.52 | 0.00 | 0.00 | 0.00 |
March | 1242.99 | 647.78 | 595.22 | 1704.51 | 851.19 | 0.00 | 0.00 | 0.00 |
April | 930.92 | 303.03 | 627.89 | 1408.40 | 725.30 | 0.00 | 0.00 | 0.00 |
May | 752.14 | 87.42 | 664.73 | 1195.03 | 487.40 | 0.00 | 0.00 | 0.00 |
June | 695.44 | 38.70 | 656.74 | 1306.27 | 311.11 | 0.00 | 0.00 | 0.00 |
July | 703.07 | 52.43 | 650.65 | 1384.43 | 221.45 | 0.00 | 0.00 | 0.00 |
August | 839.42 | 156.81 | 682.61 | 1685.68 | 184.97 | 0.00 | 0.00 | 0.00 |
September | 923.15 | 343.37 | 579.79 | 1589.80 | 400.10 | 0.00 | 0.00 | 0.00 |
October | 1338.31 | 866.96 | 471.35 | 2004.66 | 779.49 | 0.00 | 0.00 | 0.00 |
November | 1439.78 | 955.42 | 484.37 | 1959.20 | 992.76 | 0.00 | 0.00 | 0.00 |
December | 1459.70 | 1026.91 | 432.79 | 1825.75 | 1176.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1097.78 | 534.66 | 563.12 | 1629.75 | 725.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 695.44 | 38.70 | 432.79 | 1195.03 | 184.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1480.84 | 1032.44 | 682.61 | 2004.66 | 1398.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 416.39 | 193.15 | 223.24 | 349.74 | 1029.81 | 0.00 | 0.00 | 0.00 |
February | 478.02 | 223.50 | 254.51 | 509.80 | 870.26 | 0.00 | 0.00 | 0.00 |
March | 704.57 | 340.46 | 364.10 | 893.55 | 579.39 | 0.00 | 0.00 | 0.00 |
April | 792.63 | 362.70 | 429.92 | 1142.13 | 483.04 | 0.00 | 0.00 | 0.00 |
May | 796.61 | 301.81 | 494.81 | 1251.31 | 330.71 | 0.00 | 0.00 | 0.00 |
June | 837.74 | 322.28 | 515.47 | 1480.50 | 215.33 | 0.00 | 0.00 | 0.00 |
July | 790.18 | 292.97 | 497.21 | 1443.84 | 154.28 | 0.00 | 0.00 | 0.00 |
August | 774.27 | 289.55 | 484.72 | 1430.79 | 130.79 | 0.00 | 0.00 | 0.00 |
September | 630.82 | 262.76 | 368.05 | 1020.72 | 269.18 | 0.00 | 0.00 | 0.00 |
October | 561.98 | 291.73 | 270.25 | 779.51 | 537.81 | 0.00 | 0.00 | 0.00 |
November | 448.50 | 201.31 | 247.19 | 527.27 | 702.81 | 0.00 | 0.00 | 0.00 |
December | 370.01 | 161.84 | 208.17 | 337.78 | 852.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 634.27 | 270.54 | 363.73 | 932.81 | 511.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 370.01 | 161.84 | 208.17 | 337.78 | 130.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 837.74 | 362.70 | 515.47 | 1480.50 | 1029.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.29 | 0.00 | 92.29 | 16.60 | 578.42 | 0.00 | 0.00 | 0.00 |
February | 102.30 | 0.00 | 102.30 | 51.39 | 468.61 | 0.00 | 0.00 | 0.00 |
March | 143.62 | 0.00 | 143.62 | 117.08 | 286.90 | 0.00 | 0.00 | 0.00 |
April | 173.72 | 0.77 | 172.95 | 214.15 | 221.72 | 0.00 | 0.00 | 0.00 |
May | 207.77 | 6.63 | 201.14 | 309.01 | 144.29 | 0.00 | 0.00 | 0.00 |
June | 228.66 | 15.10 | 213.56 | 426.47 | 93.46 | 0.00 | 0.00 | 0.00 |
July | 215.74 | 10.49 | 205.25 | 423.66 | 67.75 | 0.00 | 0.00 | 0.00 |
August | 191.86 | 2.09 | 189.77 | 384.24 | 57.62 | 0.00 | 0.00 | 0.00 |
September | 145.03 | 0.02 | 145.01 | 219.88 | 139.87 | 0.00 | 0.00 | 0.00 |
October | 110.27 | 0.00 | 110.27 | 99.01 | 296.36 | 0.00 | 0.00 | 0.00 |
November | 98.69 | 0.00 | 98.69 | 52.74 | 398.70 | 0.00 | 0.00 | 0.00 |
December | 85.32 | 0.00 | 85.32 | 17.01 | 490.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.86 | 2.94 | 146.93 | 195.07 | 269.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.32 | 0.00 | 85.32 | 16.60 | 57.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 228.66 | 15.10 | 213.56 | 426.47 | 578.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.30 | 0.00 | 92.30 | 16.60 | 578.46 | 0.00 | 0.00 | 0.00 |
February | 102.30 | 0.00 | 102.30 | 51.39 | 468.64 | 0.00 | 0.00 | 0.00 |
March | 143.63 | 0.00 | 143.63 | 117.08 | 286.92 | 0.00 | 0.00 | 0.00 |
April | 173.73 | 0.77 | 172.96 | 214.16 | 221.73 | 0.00 | 0.00 | 0.00 |
May | 207.78 | 6.63 | 201.14 | 309.03 | 144.30 | 0.00 | 0.00 | 0.00 |
June | 228.67 | 15.10 | 213.57 | 426.49 | 93.47 | 0.00 | 0.00 | 0.00 |
July | 215.75 | 10.49 | 205.26 | 423.68 | 67.75 | 0.00 | 0.00 | 0.00 |
August | 191.87 | 2.09 | 189.78 | 384.26 | 57.62 | 0.00 | 0.00 | 0.00 |
September | 145.04 | 0.02 | 145.02 | 219.89 | 139.88 | 0.00 | 0.00 | 0.00 |
October | 110.28 | 0.00 | 110.28 | 99.02 | 296.38 | 0.00 | 0.00 | 0.00 |
November | 98.69 | 0.00 | 98.69 | 52.74 | 398.72 | 0.00 | 0.00 | 0.00 |
December | 85.32 | 0.00 | 85.32 | 17.01 | 490.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.87 | 2.94 | 146.93 | 195.08 | 269.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.32 | 0.00 | 85.32 | 16.60 | 57.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 228.67 | 15.10 | 213.57 | 426.49 | 578.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.30 | 0.00 | 92.30 | 16.60 | 578.46 | 0.00 | 0.00 | 0.00 |
February | 102.30 | 0.00 | 102.30 | 51.39 | 468.64 | 0.00 | 0.00 | 0.00 |
March | 143.63 | 0.00 | 143.63 | 117.08 | 286.92 | 0.00 | 0.00 | 0.00 |
April | 173.73 | 0.77 | 172.96 | 214.16 | 221.73 | 0.00 | 0.00 | 0.00 |
May | 207.78 | 6.63 | 201.14 | 309.03 | 144.30 | 0.00 | 0.00 | 0.00 |
June | 228.67 | 15.10 | 213.57 | 426.49 | 93.47 | 0.00 | 0.00 | 0.00 |
July | 215.75 | 10.49 | 205.26 | 423.68 | 67.75 | 0.00 | 0.00 | 0.00 |
August | 191.87 | 2.09 | 189.78 | 384.26 | 57.62 | 0.00 | 0.00 | 0.00 |
September | 145.04 | 0.02 | 145.02 | 219.89 | 139.88 | 0.00 | 0.00 | 0.00 |
October | 110.28 | 0.00 | 110.28 | 99.02 | 296.38 | 0.00 | 0.00 | 0.00 |
November | 98.69 | 0.00 | 98.69 | 52.74 | 398.72 | 0.00 | 0.00 | 0.00 |
December | 85.32 | 0.00 | 85.32 | 17.01 | 490.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.87 | 2.94 | 146.93 | 195.08 | 269.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.32 | 0.00 | 85.32 | 16.60 | 57.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 228.67 | 15.10 | 213.57 | 426.49 | 578.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 389.97 | 175.89 | 214.07 | 291.06 | 1006.21 | 0.00 | 0.00 | 0.00 |
February | 491.62 | 264.15 | 227.48 | 502.40 | 827.36 | 0.00 | 0.00 | 0.00 |
March | 618.52 | 281.57 | 336.95 | 738.64 | 530.80 | 0.00 | 0.00 | 0.00 |
April | 747.95 | 341.04 | 406.91 | 1072.23 | 421.59 | 0.00 | 0.00 | 0.00 |
May | 821.31 | 347.32 | 473.99 | 1290.69 | 287.25 | 0.00 | 0.00 | 0.00 |
June | 850.33 | 356.39 | 493.94 | 1504.37 | 187.95 | 0.00 | 0.00 | 0.00 |
July | 829.10 | 348.57 | 480.54 | 1509.95 | 138.68 | 0.00 | 0.00 | 0.00 |
August | 758.36 | 300.87 | 457.49 | 1402.41 | 118.07 | 0.00 | 0.00 | 0.00 |
September | 623.27 | 276.15 | 347.11 | 999.48 | 268.84 | 0.00 | 0.00 | 0.00 |
October | 531.70 | 276.65 | 255.04 | 686.81 | 545.11 | 0.00 | 0.00 | 0.00 |
November | 425.10 | 192.48 | 232.62 | 423.42 | 711.86 | 0.00 | 0.00 | 0.00 |
December | 368.22 | 167.85 | 200.37 | 289.25 | 858.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 621.91 | 277.36 | 344.54 | 894.59 | 490.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 368.22 | 167.85 | 200.37 | 289.25 | 118.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 850.33 | 356.39 | 493.94 | 1509.95 | 1006.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.42 | 6.95 | 8.46 | 11.51 | 39.78 | 0.00 | 0.00 | 0.00 |
February | 19.44 | 10.44 | 8.99 | 19.86 | 32.71 | 0.00 | 0.00 | 0.00 |
March | 24.46 | 11.13 | 13.32 | 29.21 | 20.99 | 0.00 | 0.00 | 0.00 |
April | 29.57 | 13.48 | 16.09 | 42.39 | 16.67 | 0.00 | 0.00 | 0.00 |
May | 32.47 | 13.73 | 18.74 | 51.03 | 11.36 | 0.00 | 0.00 | 0.00 |
June | 33.62 | 14.09 | 19.53 | 59.48 | 7.43 | 0.00 | 0.00 | 0.00 |
July | 32.78 | 13.78 | 19.00 | 59.70 | 5.48 | 0.00 | 0.00 | 0.00 |
August | 29.98 | 11.90 | 18.09 | 55.45 | 4.67 | 0.00 | 0.00 | 0.00 |
September | 24.64 | 10.92 | 13.72 | 39.52 | 10.63 | 0.00 | 0.00 | 0.00 |
October | 21.02 | 10.94 | 10.08 | 27.16 | 21.55 | 0.00 | 0.00 | 0.00 |
November | 16.81 | 7.61 | 9.20 | 16.74 | 28.15 | 0.00 | 0.00 | 0.00 |
December | 14.56 | 6.64 | 7.92 | 11.44 | 33.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.59 | 10.97 | 13.62 | 35.37 | 19.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.56 | 6.64 | 7.92 | 11.44 | 4.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.62 | 14.09 | 19.53 | 59.70 | 39.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 493.60 | 344.14 | 149.47 | 585.03 | 497.99 | 0.00 | 0.00 | 0.00 |
February | 460.70 | 308.82 | 151.88 | 593.13 | 426.65 | 0.00 | 0.00 | 0.00 |
March | 414.32 | 215.92 | 198.40 | 580.64 | 292.45 | 0.00 | 0.00 | 0.00 |
April | 310.30 | 101.01 | 209.29 | 486.46 | 234.11 | 0.00 | 0.00 | 0.00 |
May | 250.71 | 29.14 | 221.57 | 413.28 | 153.72 | 0.00 | 0.00 | 0.00 |
June | 231.81 | 12.90 | 218.91 | 445.62 | 99.52 | 0.00 | 0.00 | 0.00 |
July | 234.36 | 17.47 | 216.88 | 469.96 | 71.12 | 0.00 | 0.00 | 0.00 |
August | 279.80 | 52.27 | 227.54 | 566.82 | 62.63 | 0.00 | 0.00 | 0.00 |
September | 307.71 | 114.45 | 193.26 | 530.89 | 145.90 | 0.00 | 0.00 | 0.00 |
October | 446.10 | 288.98 | 157.12 | 666.52 | 295.20 | 0.00 | 0.00 | 0.00 |
November | 479.92 | 318.47 | 161.45 | 646.08 | 379.71 | 0.00 | 0.00 | 0.00 |
December | 486.56 | 342.30 | 144.26 | 605.64 | 443.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 365.92 | 178.21 | 187.71 | 549.05 | 257.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 231.81 | 12.90 | 144.26 | 413.28 | 62.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 493.60 | 344.14 | 227.54 | 666.52 | 497.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 493.60 | 344.14 | 149.47 | 585.03 | 497.99 | 0.00 | 0.00 | 0.00 |
February | 460.70 | 308.82 | 151.88 | 593.13 | 426.65 | 0.00 | 0.00 | 0.00 |
March | 414.32 | 215.92 | 198.40 | 580.64 | 292.45 | 0.00 | 0.00 | 0.00 |
April | 310.30 | 101.01 | 209.29 | 486.46 | 234.11 | 0.00 | 0.00 | 0.00 |
May | 250.71 | 29.14 | 221.57 | 413.28 | 153.72 | 0.00 | 0.00 | 0.00 |
June | 231.81 | 12.90 | 218.91 | 445.62 | 99.52 | 0.00 | 0.00 | 0.00 |
July | 234.36 | 17.47 | 216.88 | 469.96 | 71.12 | 0.00 | 0.00 | 0.00 |
August | 279.80 | 52.27 | 227.54 | 566.82 | 62.63 | 0.00 | 0.00 | 0.00 |
September | 307.71 | 114.45 | 193.26 | 530.89 | 145.90 | 0.00 | 0.00 | 0.00 |
October | 446.10 | 288.98 | 157.12 | 666.52 | 295.20 | 0.00 | 0.00 | 0.00 |
November | 479.92 | 318.47 | 161.45 | 646.08 | 379.71 | 0.00 | 0.00 | 0.00 |
December | 486.56 | 342.30 | 144.26 | 605.64 | 443.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 365.92 | 178.21 | 187.71 | 549.05 | 257.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 231.81 | 12.90 | 144.26 | 413.28 | 62.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 493.60 | 344.14 | 227.54 | 666.52 | 497.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 493.57 | 344.12 | 149.46 | 584.99 | 497.96 | 0.00 | 0.00 | 0.00 |
February | 460.67 | 308.80 | 151.87 | 593.09 | 426.62 | 0.00 | 0.00 | 0.00 |
March | 414.30 | 215.91 | 198.39 | 580.61 | 292.43 | 0.00 | 0.00 | 0.00 |
April | 310.28 | 101.00 | 209.28 | 486.43 | 234.09 | 0.00 | 0.00 | 0.00 |
May | 250.70 | 29.14 | 221.56 | 413.26 | 153.72 | 0.00 | 0.00 | 0.00 |
June | 231.80 | 12.90 | 218.90 | 445.59 | 99.52 | 0.00 | 0.00 | 0.00 |
July | 234.34 | 17.47 | 216.87 | 469.93 | 71.12 | 0.00 | 0.00 | 0.00 |
August | 279.79 | 52.26 | 227.52 | 566.78 | 62.63 | 0.00 | 0.00 | 0.00 |
September | 307.69 | 114.45 | 193.25 | 530.85 | 145.90 | 0.00 | 0.00 | 0.00 |
October | 446.07 | 288.96 | 157.11 | 666.48 | 295.18 | 0.00 | 0.00 | 0.00 |
November | 479.89 | 318.45 | 161.44 | 646.04 | 379.69 | 0.00 | 0.00 | 0.00 |
December | 486.53 | 342.27 | 144.25 | 605.60 | 443.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 365.90 | 178.20 | 187.69 | 549.02 | 257.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 231.80 | 12.90 | 144.25 | 413.26 | 62.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 493.57 | 344.12 | 227.52 | 666.48 | 497.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 400.55 | 185.80 | 214.75 | 338.13 | 1048.18 | 0.00 | 0.00 | 0.00 |
February | 459.83 | 215.00 | 244.83 | 498.48 | 875.69 | 0.00 | 0.00 | 0.00 |
March | 677.76 | 327.51 | 350.25 | 877.80 | 573.94 | 0.00 | 0.00 | 0.00 |
April | 762.47 | 348.90 | 413.57 | 1126.46 | 460.57 | 0.00 | 0.00 | 0.00 |
May | 766.30 | 290.32 | 475.98 | 1227.53 | 313.00 | 0.00 | 0.00 | 0.00 |
June | 805.87 | 310.01 | 495.86 | 1443.76 | 207.31 | 0.00 | 0.00 | 0.00 |
July | 760.12 | 281.83 | 478.29 | 1405.03 | 148.70 | 0.00 | 0.00 | 0.00 |
August | 744.81 | 278.53 | 466.28 | 1387.52 | 130.30 | 0.00 | 0.00 | 0.00 |
September | 606.82 | 252.76 | 354.05 | 982.82 | 285.52 | 0.00 | 0.00 | 0.00 |
October | 540.60 | 280.63 | 259.97 | 741.72 | 589.32 | 0.00 | 0.00 | 0.00 |
November | 431.44 | 193.65 | 237.79 | 490.59 | 771.44 | 0.00 | 0.00 | 0.00 |
December | 355.93 | 155.69 | 200.25 | 317.83 | 915.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 610.14 | 260.24 | 349.90 | 905.28 | 524.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 355.93 | 155.69 | 200.25 | 317.83 | 130.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 805.87 | 348.90 | 495.86 | 1443.76 | 1048.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.84 | 7.35 | 8.49 | 13.37 | 41.44 | 0.00 | 0.00 | 0.00 |
February | 18.18 | 8.50 | 9.68 | 19.71 | 34.62 | 0.00 | 0.00 | 0.00 |
March | 26.80 | 12.95 | 13.85 | 34.71 | 22.69 | 0.00 | 0.00 | 0.00 |
April | 30.15 | 13.80 | 16.35 | 44.54 | 18.21 | 0.00 | 0.00 | 0.00 |
May | 30.30 | 11.48 | 18.82 | 48.54 | 12.38 | 0.00 | 0.00 | 0.00 |
June | 31.86 | 12.26 | 19.61 | 57.08 | 8.20 | 0.00 | 0.00 | 0.00 |
July | 30.05 | 11.14 | 18.91 | 55.55 | 5.88 | 0.00 | 0.00 | 0.00 |
August | 29.45 | 11.01 | 18.44 | 54.86 | 5.15 | 0.00 | 0.00 | 0.00 |
September | 23.99 | 9.99 | 14.00 | 38.86 | 11.29 | 0.00 | 0.00 | 0.00 |
October | 21.37 | 11.10 | 10.28 | 29.33 | 23.30 | 0.00 | 0.00 | 0.00 |
November | 17.06 | 7.66 | 9.40 | 19.40 | 30.50 | 0.00 | 0.00 | 0.00 |
December | 14.07 | 6.16 | 7.92 | 12.57 | 36.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.12 | 10.29 | 13.83 | 35.79 | 20.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.07 | 6.16 | 7.92 | 12.57 | 5.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 31.86 | 13.80 | 19.61 | 57.08 | 41.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 276.89 | 0.00 | 276.89 | 47.37 | 1741.15 | 0.00 | 0.00 | 0.00 |
February | 306.91 | 0.00 | 306.91 | 142.51 | 1436.70 | 0.00 | 0.00 | 0.00 |
March | 430.88 | 0.00 | 430.88 | 313.61 | 923.72 | 0.00 | 0.00 | 0.00 |
April | 521.19 | 2.31 | 518.87 | 588.92 | 735.12 | 0.00 | 0.00 | 0.00 |
May | 623.33 | 19.89 | 603.44 | 886.74 | 475.60 | 0.00 | 0.00 | 0.00 |
June | 686.00 | 45.29 | 640.71 | 1257.84 | 298.35 | 0.00 | 0.00 | 0.00 |
July | 647.25 | 31.46 | 615.78 | 1255.02 | 215.44 | 0.00 | 0.00 | 0.00 |
August | 575.62 | 6.27 | 569.35 | 1144.91 | 179.74 | 0.00 | 0.00 | 0.00 |
September | 435.11 | 0.06 | 435.05 | 659.49 | 411.23 | 0.00 | 0.00 | 0.00 |
October | 330.83 | 0.00 | 330.83 | 301.20 | 858.16 | 0.00 | 0.00 | 0.00 |
November | 296.08 | 0.00 | 296.08 | 164.58 | 1155.32 | 0.00 | 0.00 | 0.00 |
December | 255.96 | 0.00 | 255.96 | 50.76 | 1435.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 449.61 | 8.81 | 440.80 | 570.15 | 819.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 255.96 | 0.00 | 255.96 | 47.37 | 179.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 686.00 | 45.29 | 640.71 | 1257.84 | 1741.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 405.39 | 182.85 | 222.54 | 296.11 | 1040.84 | 0.00 | 0.00 | 0.00 |
February | 511.07 | 274.59 | 236.48 | 507.70 | 867.78 | 0.00 | 0.00 | 0.00 |
March | 642.99 | 292.71 | 350.28 | 738.73 | 574.22 | 0.00 | 0.00 | 0.00 |
April | 777.54 | 354.54 | 423.00 | 1080.48 | 466.29 | 0.00 | 0.00 | 0.00 |
May | 853.79 | 361.06 | 492.74 | 1313.91 | 315.50 | 0.00 | 0.00 | 0.00 |
June | 883.96 | 370.49 | 513.47 | 1546.56 | 200.57 | 0.00 | 0.00 | 0.00 |
July | 861.90 | 362.35 | 499.54 | 1556.48 | 146.00 | 0.00 | 0.00 | 0.00 |
August | 788.35 | 312.77 | 475.59 | 1448.95 | 121.19 | 0.00 | 0.00 | 0.00 |
September | 647.92 | 287.08 | 360.84 | 1034.49 | 267.51 | 0.00 | 0.00 | 0.00 |
October | 552.73 | 287.60 | 265.13 | 713.46 | 536.43 | 0.00 | 0.00 | 0.00 |
November | 441.91 | 200.10 | 241.82 | 443.86 | 701.81 | 0.00 | 0.00 | 0.00 |
December | 382.78 | 174.49 | 208.29 | 299.09 | 861.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 646.51 | 288.34 | 358.17 | 917.11 | 506.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 382.78 | 174.49 | 208.29 | 296.11 | 121.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 883.96 | 370.49 | 513.47 | 1556.48 | 1040.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1480.84 | 1032.44 | 448.40 | 1720.32 | 1475.52 | 0.00 | 0.00 | 0.00 |
February | 1382.12 | 926.47 | 455.65 | 1742.25 | 1279.25 | 0.00 | 0.00 | 0.00 |
March | 1242.99 | 647.78 | 595.22 | 1692.94 | 903.75 | 0.00 | 0.00 | 0.00 |
April | 930.92 | 303.03 | 627.89 | 1405.18 | 758.97 | 0.00 | 0.00 | 0.00 |
May | 752.14 | 87.42 | 664.73 | 1198.21 | 505.15 | 0.00 | 0.00 | 0.00 |
June | 695.44 | 38.70 | 656.74 | 1314.94 | 318.65 | 0.00 | 0.00 | 0.00 |
July | 703.07 | 52.43 | 650.65 | 1395.41 | 225.06 | 0.00 | 0.00 | 0.00 |
August | 839.42 | 156.81 | 682.61 | 1696.12 | 188.45 | 0.00 | 0.00 | 0.00 |
September | 923.15 | 343.37 | 579.79 | 1590.20 | 421.30 | 0.00 | 0.00 | 0.00 |
October | 1338.31 | 866.96 | 471.35 | 1993.96 | 834.83 | 0.00 | 0.00 | 0.00 |
November | 1439.78 | 955.42 | 484.37 | 1934.33 | 1070.68 | 0.00 | 0.00 | 0.00 |
December | 1459.70 | 1026.91 | 432.79 | 1801.16 | 1268.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1097.78 | 534.66 | 563.12 | 1623.46 | 768.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 695.44 | 38.70 | 432.79 | 1198.21 | 188.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1480.84 | 1032.44 | 682.61 | 1993.96 | 1475.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 416.39 | 193.15 | 223.24 | 343.73 | 1084.14 | 0.00 | 0.00 | 0.00 |
February | 478.02 | 223.50 | 254.51 | 504.75 | 919.61 | 0.00 | 0.00 | 0.00 |
March | 704.57 | 340.46 | 364.10 | 887.21 | 617.14 | 0.00 | 0.00 | 0.00 |
April | 792.63 | 362.70 | 429.92 | 1140.15 | 506.23 | 0.00 | 0.00 | 0.00 |
May | 796.61 | 301.81 | 494.81 | 1253.84 | 342.81 | 0.00 | 0.00 | 0.00 |
June | 837.74 | 322.28 | 515.47 | 1487.17 | 220.78 | 0.00 | 0.00 | 0.00 |
July | 790.18 | 292.97 | 497.21 | 1451.27 | 156.88 | 0.00 | 0.00 | 0.00 |
August | 774.27 | 289.55 | 484.72 | 1437.72 | 133.05 | 0.00 | 0.00 | 0.00 |
September | 630.82 | 262.76 | 368.05 | 1020.82 | 283.79 | 0.00 | 0.00 | 0.00 |
October | 561.98 | 291.73 | 270.25 | 772.78 | 579.09 | 0.00 | 0.00 | 0.00 |
November | 448.50 | 201.31 | 247.19 | 514.29 | 760.70 | 0.00 | 0.00 | 0.00 |
December | 370.01 | 161.84 | 208.17 | 328.97 | 919.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 634.27 | 270.54 | 363.73 | 930.81 | 541.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 370.01 | 161.84 | 208.17 | 328.97 | 133.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 837.74 | 362.70 | 515.47 | 1487.17 | 1084.14 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.741621E+09 | 0.00 | 0.741621E+09 | 0.139414E+09 | 0.443520E+10 |
February | 0.742465E+09 | 0.00 | 0.742465E+09 | 0.360707E+09 | 0.329239E+10 |
March | 0.115406E+10 | 0.00 | 0.115406E+10 | 0.872393E+09 | 0.231800E+10 |
April | 0.135092E+10 | 5991711.25 | 0.134492E+10 | 0.154094E+10 | 0.181565E+10 |
May | 0.166953E+10 | 53282288.90 | 0.161625E+10 | 0.237282E+10 | 0.122976E+10 |
June | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.324052E+10 | 0.757828E+09 |
July | 0.173358E+10 | 84270737.43 | 0.164931E+10 | 0.333303E+10 | 0.569854E+09 |
August | 0.154174E+10 | 16794811.96 | 0.152494E+10 | 0.304110E+10 | 0.473458E+09 |
September | 0.112781E+10 | 158764.78 | 0.112766E+10 | 0.171386E+10 | 0.100715E+10 |
October | 0.886097E+09 | 0.00 | 0.886097E+09 | 0.841221E+09 | 0.212638E+10 |
November | 0.767444E+09 | 0.00 | 0.767444E+09 | 0.476179E+09 | 0.275837E+10 |
December | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.157279E+09 | 0.355893E+10 |
Annual Sum or Average | 0.141790E+11 | 0.277896E+09 | 0.139011E+11 | 0.180895E+11 | 0.243430E+11 |
Minimum of Months | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.139414E+09 | 0.473458E+09 |
Maximum of Months | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.333303E+10 | 0.443520E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108580E+10 | 0.489750E+09 | 0.596049E+09 | 0.823428E+09 | 0.264938E+10 |
February | 0.123638E+10 | 0.664299E+09 | 0.572083E+09 | 0.125626E+10 | 0.198619E+10 |
March | 0.172217E+10 | 0.783984E+09 | 0.938190E+09 | 0.201579E+10 | 0.144568E+10 |
April | 0.201537E+10 | 0.918958E+09 | 0.109642E+10 | 0.281845E+10 | 0.115842E+10 |
May | 0.228680E+10 | 0.967054E+09 | 0.131974E+10 | 0.352347E+10 | 0.819527E+09 |
June | 0.229123E+10 | 0.960312E+09 | 0.133092E+10 | 0.400308E+10 | 0.509885E+09 |
July | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.415804E+10 | 0.385180E+09 |
August | 0.211153E+10 | 0.837717E+09 | 0.127381E+10 | 0.387227E+10 | 0.318295E+09 |
September | 0.167941E+10 | 0.744101E+09 | 0.935305E+09 | 0.269123E+10 | 0.658062E+09 |
October | 0.148043E+10 | 0.770305E+09 | 0.710127E+09 | 0.194582E+10 | 0.133762E+10 |
November | 0.114544E+10 | 0.518649E+09 | 0.626787E+09 | 0.121029E+10 | 0.167598E+10 |
December | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.844401E+09 | 0.212980E+10 |
Annual Sum or Average | 0.203883E+11 | 0.909301E+10 | 0.112953E+11 | 0.291625E+11 | 0.150740E+11 |
Minimum of Months | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.823428E+09 | 0.318295E+09 |
Maximum of Months | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.415804E+10 | 0.264938E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.396629E+10 | 0.276528E+10 | 0.120100E+10 | 0.466144E+10 | 0.374614E+10 |
February | 0.334363E+10 | 0.224132E+10 | 0.110230E+10 | 0.425045E+10 | 0.292607E+10 |
March | 0.332924E+10 | 0.173500E+10 | 0.159423E+10 | 0.456537E+10 | 0.227982E+10 |
April | 0.241294E+10 | 0.785465E+09 | 0.162748E+10 | 0.365058E+10 | 0.187999E+10 |
May | 0.201454E+10 | 0.234145E+09 | 0.178040E+10 | 0.320078E+10 | 0.130546E+10 |
June | 0.180257E+10 | 0.100306E+09 | 0.170227E+10 | 0.338585E+10 | 0.806396E+09 |
July | 0.188311E+10 | 0.140416E+09 | 0.174270E+10 | 0.370806E+10 | 0.593122E+09 |
August | 0.224830E+10 | 0.419991E+09 | 0.182831E+10 | 0.451494E+10 | 0.495430E+09 |
September | 0.239282E+10 | 0.890004E+09 | 0.150281E+10 | 0.412076E+10 | 0.103707E+10 |
October | 0.358453E+10 | 0.232207E+10 | 0.126247E+10 | 0.536927E+10 | 0.208779E+10 |
November | 0.373191E+10 | 0.247644E+10 | 0.125548E+10 | 0.507825E+10 | 0.257323E+10 |
December | 0.390966E+10 | 0.275048E+10 | 0.115918E+10 | 0.489009E+10 | 0.315149E+10 |
Annual Sum or Average | 0.346195E+11 | 0.168609E+11 | 0.177586E+11 | 0.513958E+11 | 0.228820E+11 |
Minimum of Months | 0.180257E+10 | 0.100306E+09 | 0.110230E+10 | 0.320078E+10 | 0.495430E+09 |
Maximum of Months | 0.396629E+10 | 0.276528E+10 | 0.182831E+10 | 0.536927E+10 | 0.374614E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111527E+10 | 0.517339E+09 | 0.597928E+09 | 0.936734E+09 | 0.275823E+10 |
February | 0.115642E+10 | 0.540695E+09 | 0.615722E+09 | 0.123330E+10 | 0.210534E+10 |
March | 0.188712E+10 | 0.911897E+09 | 0.975218E+09 | 0.239329E+10 | 0.155183E+10 |
April | 0.205449E+10 | 0.940125E+09 | 0.111436E+10 | 0.296040E+10 | 0.125203E+10 |
May | 0.213365E+10 | 0.808356E+09 | 0.132529E+10 | 0.335152E+10 | 0.885779E+09 |
June | 0.217143E+10 | 0.835339E+09 | 0.133609E+10 | 0.383746E+10 | 0.558139E+09 |
July | 0.211643E+10 | 0.784700E+09 | 0.133173E+10 | 0.386717E+10 | 0.413222E+09 |
August | 0.207380E+10 | 0.775518E+09 | 0.129828E+10 | 0.383223E+10 | 0.350312E+09 |
September | 0.163508E+10 | 0.681080E+09 | 0.953995E+09 | 0.264569E+10 | 0.697719E+09 |
October | 0.150521E+10 | 0.781371E+09 | 0.723842E+09 | 0.208784E+10 | 0.144046E+10 |
November | 0.116252E+10 | 0.521798E+09 | 0.640720E+09 | 0.136669E+10 | 0.182168E+10 |
December | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.904715E+09 | 0.228361E+10 |
Annual Sum or Average | 0.200024E+11 | 0.853170E+10 | 0.114707E+11 | 0.294170E+11 | 0.161184E+11 |
Minimum of Months | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.904715E+09 | 0.350312E+09 |
Maximum of Months | 0.217143E+10 | 0.940125E+09 | 0.133609E+10 | 0.386717E+10 | 0.275823E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247195E+09 | 0.00 | 0.247195E+09 | 44470952.88 | 0.154924E+10 |
February | 0.247477E+09 | 0.00 | 0.247477E+09 | 0.124322E+09 | 0.113365E+10 |
March | 0.384670E+09 | 0.00 | 0.384670E+09 | 0.313575E+09 | 0.768434E+09 |
April | 0.450284E+09 | 1997142.59 | 0.448287E+09 | 0.555068E+09 | 0.574686E+09 |
May | 0.556484E+09 | 17759922.67 | 0.538724E+09 | 0.827660E+09 | 0.386460E+09 |
June | 0.592679E+09 | 39130827.43 | 0.553548E+09 | 0.110540E+10 | 0.242259E+09 |
July | 0.577834E+09 | 28088916.80 | 0.549745E+09 | 0.113472E+10 | 0.181452E+09 |
August | 0.513888E+09 | 5598005.79 | 0.508290E+09 | 0.102916E+10 | 0.154316E+09 |
September | 0.375920E+09 | 52919.09 | 0.375867E+09 | 0.569932E+09 | 0.362546E+09 |
October | 0.295352E+09 | 0.00 | 0.295352E+09 | 0.265197E+09 | 0.793768E+09 |
November | 0.255803E+09 | 0.00 | 0.255803E+09 | 0.136695E+09 | 0.103343E+10 |
December | 0.228514E+09 | 0.00 | 0.228514E+09 | 45569624.37 | 0.131371E+10 |
Annual Sum or Average | 0.472610E+10 | 92627734.38 | 0.463347E+10 | 0.615177E+10 | 0.849395E+10 |
Minimum of Months | 0.228514E+09 | 0.00 | 0.228514E+09 | 44470952.88 | 0.154316E+09 |
Maximum of Months | 0.592679E+09 | 39130827.43 | 0.553548E+09 | 0.113472E+10 | 0.154924E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247205E+09 | 0.00 | 0.247205E+09 | 44471481.99 | 0.154934E+10 |
February | 0.247487E+09 | 0.00 | 0.247487E+09 | 0.124326E+09 | 0.113372E+10 |
March | 0.384685E+09 | 0.00 | 0.384685E+09 | 0.313585E+09 | 0.768479E+09 |
April | 0.450302E+09 | 1997196.27 | 0.448305E+09 | 0.555091E+09 | 0.574720E+09 |
May | 0.556506E+09 | 17760400.06 | 0.538746E+09 | 0.827694E+09 | 0.386482E+09 |
June | 0.592703E+09 | 39131879.28 | 0.553571E+09 | 0.110545E+10 | 0.242271E+09 |
July | 0.577857E+09 | 28089671.84 | 0.549767E+09 | 0.113477E+10 | 0.181461E+09 |
August | 0.513909E+09 | 5598156.26 | 0.508311E+09 | 0.102921E+10 | 0.154323E+09 |
September | 0.375935E+09 | 52920.51 | 0.375882E+09 | 0.569956E+09 | 0.362565E+09 |
October | 0.295364E+09 | 0.00 | 0.295364E+09 | 0.265207E+09 | 0.793815E+09 |
November | 0.255813E+09 | 0.00 | 0.255813E+09 | 0.136698E+09 | 0.103349E+10 |
December | 0.228523E+09 | 0.00 | 0.228523E+09 | 45569527.75 | 0.131379E+10 |
Annual Sum or Average | 0.472629E+10 | 92630224.23 | 0.463366E+10 | 0.615203E+10 | 0.849446E+10 |
Minimum of Months | 0.228523E+09 | 0.00 | 0.228523E+09 | 44471481.99 | 0.154323E+09 |
Maximum of Months | 0.592703E+09 | 39131879.28 | 0.553571E+09 | 0.113477E+10 | 0.154934E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247205E+09 | 0.00 | 0.247205E+09 | 44471481.99 | 0.154934E+10 |
February | 0.247487E+09 | 0.00 | 0.247487E+09 | 0.124326E+09 | 0.113372E+10 |
March | 0.384685E+09 | 0.00 | 0.384685E+09 | 0.313585E+09 | 0.768479E+09 |
April | 0.450302E+09 | 1997196.27 | 0.448305E+09 | 0.555091E+09 | 0.574720E+09 |
May | 0.556506E+09 | 17760400.06 | 0.538746E+09 | 0.827694E+09 | 0.386482E+09 |
June | 0.592703E+09 | 39131879.28 | 0.553571E+09 | 0.110545E+10 | 0.242271E+09 |
July | 0.577857E+09 | 28089671.84 | 0.549767E+09 | 0.113477E+10 | 0.181461E+09 |
August | 0.513909E+09 | 5598156.26 | 0.508311E+09 | 0.102921E+10 | 0.154323E+09 |
September | 0.375935E+09 | 52920.51 | 0.375882E+09 | 0.569956E+09 | 0.362565E+09 |
October | 0.295364E+09 | 0.00 | 0.295364E+09 | 0.265207E+09 | 0.793815E+09 |
November | 0.255813E+09 | 0.00 | 0.255813E+09 | 0.136698E+09 | 0.103349E+10 |
December | 0.228523E+09 | 0.00 | 0.228523E+09 | 45569527.75 | 0.131379E+10 |
Annual Sum or Average | 0.472629E+10 | 92630224.23 | 0.463366E+10 | 0.615203E+10 | 0.849446E+10 |
Minimum of Months | 0.228523E+09 | 0.00 | 0.228523E+09 | 44471481.99 | 0.154323E+09 |
Maximum of Months | 0.592703E+09 | 39131879.28 | 0.553571E+09 | 0.113477E+10 | 0.154934E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104448E+10 | 0.471113E+09 | 0.573371E+09 | 0.779567E+09 | 0.269502E+10 |
February | 0.118934E+10 | 0.639020E+09 | 0.550317E+09 | 0.121541E+10 | 0.200155E+10 |
March | 0.165665E+10 | 0.754150E+09 | 0.902495E+09 | 0.197837E+10 | 0.142168E+10 |
April | 0.193869E+10 | 0.883988E+09 | 0.105470E+10 | 0.277921E+10 | 0.109277E+10 |
May | 0.219979E+10 | 0.930254E+09 | 0.126953E+10 | 0.345697E+10 | 0.769380E+09 |
June | 0.220405E+10 | 0.923768E+09 | 0.128028E+10 | 0.389932E+10 | 0.487175E+09 |
July | 0.222067E+10 | 0.933599E+09 | 0.128707E+10 | 0.404426E+10 | 0.371445E+09 |
August | 0.203118E+10 | 0.805839E+09 | 0.122534E+10 | 0.375621E+10 | 0.316233E+09 |
September | 0.161550E+10 | 0.715785E+09 | 0.899719E+09 | 0.259064E+10 | 0.696837E+09 |
October | 0.142410E+10 | 0.740991E+09 | 0.683110E+09 | 0.183956E+10 | 0.146001E+10 |
November | 0.110185E+10 | 0.498912E+09 | 0.602939E+09 | 0.109750E+10 | 0.184513E+10 |
December | 0.986230E+09 | 0.449560E+09 | 0.536670E+09 | 0.774724E+09 | 0.230050E+10 |
Annual Sum or Average | 0.196125E+11 | 0.874698E+10 | 0.108656E+11 | 0.282118E+11 | 0.154577E+11 |
Minimum of Months | 0.986230E+09 | 0.449560E+09 | 0.536670E+09 | 0.774724E+09 | 0.316233E+09 |
Maximum of Months | 0.222067E+10 | 0.933599E+09 | 0.128707E+10 | 0.404426E+10 | 0.269502E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41297968.64 | 18627401.67 | 22670566.97 | 30823374.90 | 0.106559E+09 |
February | 47025321.95 | 25266263.70 | 21759058.25 | 48056306.27 | 79139421.93 |
March | 65502272.49 | 29818417.68 | 35683854.81 | 78223013.26 | 56212061.65 |
April | 76654026.86 | 34952094.60 | 41701932.26 | 0.109888E+09 | 43206971.70 |
May | 86977579.04 | 36781404.46 | 50196174.57 | 0.136686E+09 | 30420599.63 |
June | 87146182.83 | 36524961.51 | 50621221.33 | 0.154175E+09 | 19262474.08 |
July | 87803420.16 | 36913651.60 | 50889768.56 | 0.159906E+09 | 14686605.40 |
August | 80311103.59 | 31862138.09 | 48448965.50 | 0.148517E+09 | 12503562.62 |
September | 63875563.18 | 28301493.83 | 35574069.35 | 0.102432E+09 | 27552297.28 |
October | 56307668.25 | 29298132.82 | 27009535.43 | 72734573.50 | 57727471.34 |
November | 43566232.40 | 19726548.35 | 23839684.04 | 43394324.67 | 72954906.24 |
December | 38994650.79 | 17775203.84 | 21219446.95 | 30631879.16 | 90959844.92 |
Annual Sum or Average | 0.775462E+09 | 0.345848E+09 | 0.429614E+09 | 0.111547E+10 | 0.611185E+09 |
Minimum of Months | 38994650.79 | 17775203.84 | 21219446.95 | 30631879.16 | 12503562.62 |
Maximum of Months | 87803420.16 | 36913651.60 | 50889768.56 | 0.159906E+09 | 0.106559E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132207E+10 | 0.921741E+09 | 0.400330E+09 | 0.156694E+10 | 0.133383E+10 |
February | 0.111452E+10 | 0.747093E+09 | 0.367430E+09 | 0.143490E+10 | 0.103214E+10 |
March | 0.110973E+10 | 0.578322E+09 | 0.531406E+09 | 0.155520E+10 | 0.783296E+09 |
April | 0.804304E+09 | 0.261816E+09 | 0.542488E+09 | 0.126090E+10 | 0.606804E+09 |
May | 0.671509E+09 | 78046639.51 | 0.593462E+09 | 0.110694E+10 | 0.411737E+09 |
June | 0.600853E+09 | 33434677.84 | 0.567418E+09 | 0.115505E+10 | 0.257962E+09 |
July | 0.627698E+09 | 46804225.75 | 0.580894E+09 | 0.125874E+10 | 0.190493E+09 |
August | 0.749425E+09 | 0.139994E+09 | 0.609431E+09 | 0.151816E+10 | 0.167759E+09 |
September | 0.797594E+09 | 0.296662E+09 | 0.500933E+09 | 0.137606E+10 | 0.378184E+09 |
October | 0.119482E+10 | 0.774006E+09 | 0.420819E+09 | 0.178522E+10 | 0.790670E+09 |
November | 0.124395E+10 | 0.825462E+09 | 0.418487E+09 | 0.167465E+10 | 0.984221E+09 |
December | 0.130320E+10 | 0.916806E+09 | 0.386390E+09 | 0.162215E+10 | 0.118783E+10 |
Annual Sum or Average | 0.115397E+11 | 0.562019E+10 | 0.591949E+10 | 0.173149E+11 | 0.812493E+10 |
Minimum of Months | 0.600853E+09 | 33434677.84 | 0.367430E+09 | 0.110694E+10 | 0.167759E+09 |
Maximum of Months | 0.132207E+10 | 0.921741E+09 | 0.609431E+09 | 0.178522E+10 | 0.133383E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132207E+10 | 0.921741E+09 | 0.400330E+09 | 0.156694E+10 | 0.133383E+10 |
February | 0.111452E+10 | 0.747093E+09 | 0.367430E+09 | 0.143490E+10 | 0.103214E+10 |
March | 0.110973E+10 | 0.578322E+09 | 0.531406E+09 | 0.155520E+10 | 0.783296E+09 |
April | 0.804304E+09 | 0.261816E+09 | 0.542488E+09 | 0.126090E+10 | 0.606804E+09 |
May | 0.671509E+09 | 78046639.51 | 0.593462E+09 | 0.110694E+10 | 0.411737E+09 |
June | 0.600853E+09 | 33434677.84 | 0.567418E+09 | 0.115505E+10 | 0.257962E+09 |
July | 0.627698E+09 | 46804225.75 | 0.580894E+09 | 0.125874E+10 | 0.190493E+09 |
August | 0.749425E+09 | 0.139994E+09 | 0.609431E+09 | 0.151816E+10 | 0.167759E+09 |
September | 0.797594E+09 | 0.296662E+09 | 0.500933E+09 | 0.137606E+10 | 0.378184E+09 |
October | 0.119482E+10 | 0.774006E+09 | 0.420819E+09 | 0.178522E+10 | 0.790670E+09 |
November | 0.124395E+10 | 0.825462E+09 | 0.418487E+09 | 0.167465E+10 | 0.984221E+09 |
December | 0.130320E+10 | 0.916806E+09 | 0.386390E+09 | 0.162215E+10 | 0.118783E+10 |
Annual Sum or Average | 0.115397E+11 | 0.562019E+10 | 0.591949E+10 | 0.173149E+11 | 0.812493E+10 |
Minimum of Months | 0.600853E+09 | 33434677.84 | 0.367430E+09 | 0.110694E+10 | 0.167759E+09 |
Maximum of Months | 0.132207E+10 | 0.921741E+09 | 0.609431E+09 | 0.178522E+10 | 0.133383E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132199E+10 | 0.921683E+09 | 0.400305E+09 | 0.156684E+10 | 0.133374E+10 |
February | 0.111445E+10 | 0.747046E+09 | 0.367407E+09 | 0.143481E+10 | 0.103208E+10 |
March | 0.110966E+10 | 0.578285E+09 | 0.531372E+09 | 0.155510E+10 | 0.783247E+09 |
April | 0.804253E+09 | 0.261800E+09 | 0.542454E+09 | 0.126082E+10 | 0.606766E+09 |
May | 0.671466E+09 | 78041707.40 | 0.593424E+09 | 0.110687E+10 | 0.411711E+09 |
June | 0.600815E+09 | 33432564.96 | 0.567382E+09 | 0.115498E+10 | 0.257946E+09 |
July | 0.627659E+09 | 46801267.99 | 0.580857E+09 | 0.125866E+10 | 0.190481E+09 |
August | 0.749378E+09 | 0.139985E+09 | 0.609393E+09 | 0.151807E+10 | 0.167748E+09 |
September | 0.797544E+09 | 0.296643E+09 | 0.500901E+09 | 0.137597E+10 | 0.378160E+09 |
October | 0.119475E+10 | 0.773957E+09 | 0.420792E+09 | 0.178510E+10 | 0.790620E+09 |
November | 0.124387E+10 | 0.825410E+09 | 0.418461E+09 | 0.167454E+10 | 0.984159E+09 |
December | 0.130311E+10 | 0.916748E+09 | 0.386365E+09 | 0.162205E+10 | 0.118776E+10 |
Annual Sum or Average | 0.115389E+11 | 0.561983E+10 | 0.591911E+10 | 0.173138E+11 | 0.812441E+10 |
Minimum of Months | 0.600815E+09 | 33432564.96 | 0.367407E+09 | 0.110687E+10 | 0.167748E+09 |
Maximum of Months | 0.132199E+10 | 0.921683E+09 | 0.609393E+09 | 0.178510E+10 | 0.133374E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107283E+10 | 0.497654E+09 | 0.575180E+09 | 0.905645E+09 | 0.280745E+10 |
February | 0.111242E+10 | 0.520121E+09 | 0.592297E+09 | 0.120593E+10 | 0.211848E+10 |
March | 0.181531E+10 | 0.877198E+09 | 0.938116E+09 | 0.235109E+10 | 0.153724E+10 |
April | 0.197632E+10 | 0.904353E+09 | 0.107197E+10 | 0.291978E+10 | 0.119380E+10 |
May | 0.205247E+10 | 0.777597E+09 | 0.127487E+10 | 0.328782E+10 | 0.838346E+09 |
June | 0.208881E+10 | 0.803554E+09 | 0.128526E+10 | 0.374222E+10 | 0.537351E+09 |
July | 0.203590E+10 | 0.754841E+09 | 0.128106E+10 | 0.376323E+10 | 0.398283E+09 |
August | 0.199490E+10 | 0.746009E+09 | 0.124889E+10 | 0.371634E+10 | 0.349008E+09 |
September | 0.157286E+10 | 0.655165E+09 | 0.917700E+09 | 0.254748E+10 | 0.740072E+09 |
October | 0.144794E+10 | 0.751639E+09 | 0.696304E+09 | 0.198662E+10 | 0.157844E+10 |
November | 0.111829E+10 | 0.501943E+09 | 0.616344E+09 | 0.127160E+10 | 0.199957E+10 |
December | 0.953332E+09 | 0.416987E+09 | 0.536345E+09 | 0.851286E+09 | 0.245271E+10 |
Annual Sum or Average | 0.192414E+11 | 0.820706E+10 | 0.110343E+11 | 0.285491E+11 | 0.165507E+11 |
Minimum of Months | 0.953332E+09 | 0.416987E+09 | 0.536345E+09 | 0.851286E+09 | 0.349008E+09 |
Maximum of Months | 0.208881E+10 | 0.904353E+09 | 0.128526E+10 | 0.376323E+10 | 0.280745E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42418767.26 | 19676731.62 | 22742035.64 | 35808241.08 | 0.111004E+09 |
February | 43983894.94 | 20565053.16 | 23418841.78 | 47681364.15 | 83762789.12 |
March | 71775721.37 | 34683525.60 | 37092195.77 | 92959860.88 | 60781140.00 |
April | 78141703.59 | 35757173.75 | 42384529.84 | 0.115445E+09 | 47201593.13 |
May | 81152613.96 | 30745385.62 | 50407228.33 | 0.129997E+09 | 33147430.52 |
June | 82589595.18 | 31771686.60 | 50817908.58 | 0.147964E+09 | 21246357.66 |
July | 80497582.55 | 29845636.76 | 50651945.78 | 0.148794E+09 | 15747740.49 |
August | 78876146.14 | 29496422.79 | 49379723.36 | 0.146941E+09 | 13799445.08 |
September | 62189492.73 | 25904536.92 | 36284955.81 | 0.100725E+09 | 29261748.44 |
October | 57250228.41 | 29719041.32 | 27531187.09 | 78548933.65 | 62410200.67 |
November | 44215952.03 | 19846317.65 | 24369634.38 | 50277844.63 | 79061136.40 |
December | 37693793.36 | 16487250.69 | 21206542.66 | 33658930.41 | 96977771.39 |
Annual Sum or Average | 0.760785E+09 | 0.324499E+09 | 0.436287E+09 | 0.112880E+10 | 0.654401E+09 |
Minimum of Months | 37693793.36 | 16487250.69 | 21206542.66 | 33658930.41 | 13799445.08 |
Maximum of Months | 82589595.18 | 35757173.75 | 50817908.58 | 0.148794E+09 | 0.111004E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.741621E+09 | 0.00 | 0.741621E+09 | 0.126863E+09 | 0.466348E+10 |
February | 0.742465E+09 | 0.00 | 0.742465E+09 | 0.344765E+09 | 0.347566E+10 |
March | 0.115406E+10 | 0.00 | 0.115406E+10 | 0.839973E+09 | 0.247408E+10 |
April | 0.135092E+10 | 5991711.25 | 0.134492E+10 | 0.152648E+10 | 0.190542E+10 |
May | 0.166953E+10 | 53282288.90 | 0.161625E+10 | 0.237504E+10 | 0.127384E+10 |
June | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.326033E+10 | 0.773311E+09 |
July | 0.173358E+10 | 84270737.43 | 0.164931E+10 | 0.336145E+10 | 0.577045E+09 |
August | 0.154174E+10 | 16794811.96 | 0.152494E+10 | 0.306652E+10 | 0.481415E+09 |
September | 0.112781E+10 | 158764.78 | 0.112766E+10 | 0.170941E+10 | 0.106592E+10 |
October | 0.886097E+09 | 0.00 | 0.886097E+09 | 0.806731E+09 | 0.229849E+10 |
November | 0.767444E+09 | 0.00 | 0.767444E+09 | 0.426596E+09 | 0.299459E+10 |
December | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.135963E+09 | 0.384525E+10 |
Annual Sum or Average | 0.141790E+11 | 0.277896E+09 | 0.139011E+11 | 0.179801E+11 | 0.258285E+11 |
Minimum of Months | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.126863E+09 | 0.481415E+09 |
Maximum of Months | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.336145E+10 | 0.466348E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108580E+10 | 0.489750E+09 | 0.596049E+09 | 0.793094E+09 | 0.278778E+10 |
February | 0.123638E+10 | 0.664299E+09 | 0.572083E+09 | 0.122822E+10 | 0.209933E+10 |
March | 0.172217E+10 | 0.783984E+09 | 0.938190E+09 | 0.197861E+10 | 0.153798E+10 |
April | 0.201537E+10 | 0.918958E+09 | 0.109642E+10 | 0.280060E+10 | 0.120861E+10 |
May | 0.228680E+10 | 0.967054E+09 | 0.131974E+10 | 0.351919E+10 | 0.845023E+09 |
June | 0.229123E+10 | 0.960312E+09 | 0.133092E+10 | 0.400870E+10 | 0.519872E+09 |
July | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.416888E+10 | 0.391056E+09 |
August | 0.211153E+10 | 0.837717E+09 | 0.127381E+10 | 0.388086E+10 | 0.324599E+09 |
September | 0.167941E+10 | 0.744101E+09 | 0.935305E+09 | 0.268140E+10 | 0.693390E+09 |
October | 0.148043E+10 | 0.770305E+09 | 0.710127E+09 | 0.191094E+10 | 0.143677E+10 |
November | 0.114544E+10 | 0.518649E+09 | 0.626787E+09 | 0.115049E+10 | 0.181909E+10 |
December | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.801070E+09 | 0.230734E+10 |
Annual Sum or Average | 0.203883E+11 | 0.909301E+10 | 0.112953E+11 | 0.289220E+11 | 0.159709E+11 |
Minimum of Months | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.793094E+09 | 0.324599E+09 |
Maximum of Months | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.416888E+10 | 0.278778E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.396629E+10 | 0.276528E+10 | 0.120100E+10 | 0.460771E+10 | 0.395203E+10 |
February | 0.334363E+10 | 0.224132E+10 | 0.110230E+10 | 0.421486E+10 | 0.309477E+10 |
March | 0.332924E+10 | 0.173500E+10 | 0.159423E+10 | 0.453437E+10 | 0.242061E+10 |
April | 0.241294E+10 | 0.785465E+09 | 0.162748E+10 | 0.364224E+10 | 0.196726E+10 |
May | 0.201454E+10 | 0.234145E+09 | 0.178040E+10 | 0.320929E+10 | 0.135300E+10 |
June | 0.180257E+10 | 0.100306E+09 | 0.170227E+10 | 0.340833E+10 | 0.825937E+09 |
July | 0.188311E+10 | 0.140416E+09 | 0.174270E+10 | 0.373748E+10 | 0.602799E+09 |
August | 0.224830E+10 | 0.419991E+09 | 0.182831E+10 | 0.454289E+10 | 0.504752E+09 |
September | 0.239282E+10 | 0.890004E+09 | 0.150281E+10 | 0.412179E+10 | 0.109202E+10 |
October | 0.358453E+10 | 0.232207E+10 | 0.126247E+10 | 0.534061E+10 | 0.223602E+10 |
November | 0.373191E+10 | 0.247644E+10 | 0.125548E+10 | 0.501379E+10 | 0.277519E+10 |
December | 0.390966E+10 | 0.275048E+10 | 0.115918E+10 | 0.482422E+10 | 0.339743E+10 |
Annual Sum or Average | 0.346195E+11 | 0.168609E+11 | 0.177586E+11 | 0.511976E+11 | 0.242218E+11 |
Minimum of Months | 0.180257E+10 | 0.100306E+09 | 0.110230E+10 | 0.320929E+10 | 0.504752E+09 |
Maximum of Months | 0.396629E+10 | 0.276528E+10 | 0.182831E+10 | 0.534061E+10 | 0.395203E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111527E+10 | 0.517339E+09 | 0.597928E+09 | 0.920638E+09 | 0.290377E+10 |
February | 0.115642E+10 | 0.540695E+09 | 0.615722E+09 | 0.122108E+10 | 0.222473E+10 |
March | 0.188712E+10 | 0.911897E+09 | 0.975218E+09 | 0.237629E+10 | 0.165294E+10 |
April | 0.205449E+10 | 0.940125E+09 | 0.111436E+10 | 0.295526E+10 | 0.131214E+10 |
May | 0.213365E+10 | 0.808356E+09 | 0.132529E+10 | 0.335828E+10 | 0.918193E+09 |
June | 0.217143E+10 | 0.835339E+09 | 0.133609E+10 | 0.385475E+10 | 0.572271E+09 |
July | 0.211643E+10 | 0.784700E+09 | 0.133173E+10 | 0.388707E+10 | 0.420188E+09 |
August | 0.207380E+10 | 0.775518E+09 | 0.129828E+10 | 0.385080E+10 | 0.356353E+09 |
September | 0.163508E+10 | 0.681080E+09 | 0.953995E+09 | 0.264598E+10 | 0.735589E+09 |
October | 0.150521E+10 | 0.781371E+09 | 0.723842E+09 | 0.206981E+10 | 0.155105E+10 |
November | 0.116252E+10 | 0.521798E+09 | 0.640720E+09 | 0.133305E+10 | 0.197174E+10 |
December | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.881121E+09 | 0.246330E+10 |
Annual Sum or Average | 0.200024E+11 | 0.853170E+10 | 0.114707E+11 | 0.293541E+11 | 0.170823E+11 |
Minimum of Months | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.881121E+09 | 0.356353E+09 |
Maximum of Months | 0.217143E+10 | 0.940125E+09 | 0.133609E+10 | 0.388707E+10 | 0.290377E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 52.05 | 1655.91 | 276.89 | 0.00 | 276.89 | 0.00 | 0.00 |
February | 149.10 | 1360.94 | 306.91 | 0.00 | 306.91 | 0.00 | 0.00 |
March | 325.71 | 865.44 | 430.88 | 0.00 | 430.88 | 0.00 | 0.00 |
April | 594.50 | 700.48 | 521.19 | 2.31 | 518.87 | 0.00 | 0.00 |
May | 885.91 | 459.14 | 623.33 | 19.89 | 603.44 | 0.00 | 0.00 |
June | 1250.20 | 292.37 | 686.00 | 45.29 | 640.71 | 0.00 | 0.00 |
July | 1244.41 | 212.76 | 647.25 | 31.46 | 615.78 | 0.00 | 0.00 |
August | 1135.42 | 176.77 | 575.62 | 6.27 | 569.35 | 0.00 | 0.00 |
September | 661.21 | 388.56 | 435.11 | 0.06 | 435.05 | 0.00 | 0.00 |
October | 314.08 | 793.90 | 330.83 | 0.00 | 330.83 | 0.00 | 0.00 |
November | 183.71 | 1064.19 | 296.08 | 0.00 | 296.08 | 0.00 | 0.00 |
December | 58.72 | 1328.75 | 255.96 | 0.00 | 255.96 | 0.00 | 0.00 |
Annual Sum or Average | 573.61 | 771.91 | 449.61 | 8.81 | 440.80 | 0.00 | 0.00 |
Minimum of Months | 52.05 | 176.77 | 255.96 | 0.00 | 255.96 | 0.00 | 0.00 |
Maximum of Months | 1250.20 | 1655.91 | 686.00 | 45.29 | 640.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 307.43 | 989.16 | 405.39 | 182.85 | 222.54 | 0.00 | 0.00 |
February | 519.29 | 821.01 | 511.07 | 274.59 | 236.48 | 0.00 | 0.00 |
March | 752.61 | 539.76 | 642.99 | 292.71 | 350.28 | 0.00 | 0.00 |
April | 1087.37 | 446.92 | 777.54 | 354.54 | 423.00 | 0.00 | 0.00 |
May | 1315.51 | 305.98 | 853.79 | 361.06 | 492.74 | 0.00 | 0.00 |
June | 1544.40 | 196.72 | 883.96 | 370.49 | 513.47 | 0.00 | 0.00 |
July | 1552.43 | 143.81 | 861.90 | 362.35 | 499.54 | 0.00 | 0.00 |
August | 1445.74 | 118.84 | 788.35 | 312.77 | 475.59 | 0.00 | 0.00 |
September | 1038.28 | 253.88 | 647.92 | 287.08 | 360.84 | 0.00 | 0.00 |
October | 726.49 | 499.41 | 552.73 | 287.60 | 265.13 | 0.00 | 0.00 |
November | 466.93 | 646.60 | 441.91 | 200.10 | 241.82 | 0.00 | 0.00 |
December | 315.26 | 795.18 | 382.78 | 174.49 | 208.29 | 0.00 | 0.00 |
Annual Sum or Average | 924.74 | 477.99 | 646.51 | 288.34 | 358.17 | 0.00 | 0.00 |
Minimum of Months | 307.43 | 118.84 | 382.78 | 174.49 | 208.29 | 0.00 | 0.00 |
Maximum of Months | 1552.43 | 989.16 | 883.96 | 370.49 | 513.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1740.38 | 1398.65 | 1480.84 | 1032.44 | 448.40 | 0.00 | 0.00 |
February | 1756.96 | 1209.52 | 1382.12 | 926.47 | 455.65 | 0.00 | 0.00 |
March | 1704.51 | 851.19 | 1242.99 | 647.78 | 595.22 | 0.00 | 0.00 |
April | 1408.40 | 725.30 | 930.92 | 303.03 | 627.89 | 0.00 | 0.00 |
May | 1195.03 | 487.40 | 752.14 | 87.42 | 664.73 | 0.00 | 0.00 |
June | 1306.27 | 311.11 | 695.44 | 38.70 | 656.74 | 0.00 | 0.00 |
July | 1384.43 | 221.45 | 703.07 | 52.43 | 650.65 | 0.00 | 0.00 |
August | 1685.68 | 184.97 | 839.42 | 156.81 | 682.61 | 0.00 | 0.00 |
September | 1589.80 | 400.10 | 923.15 | 343.37 | 579.79 | 0.00 | 0.00 |
October | 2004.66 | 779.49 | 1338.31 | 866.96 | 471.35 | 0.00 | 0.00 |
November | 1959.20 | 992.76 | 1439.78 | 955.42 | 484.37 | 0.00 | 0.00 |
December | 1825.75 | 1176.63 | 1459.70 | 1026.91 | 432.79 | 0.00 | 0.00 |
Annual Sum or Average | 1629.75 | 725.58 | 1097.78 | 534.66 | 563.12 | 0.00 | 0.00 |
Minimum of Months | 1195.03 | 184.97 | 695.44 | 38.70 | 432.79 | 0.00 | 0.00 |
Maximum of Months | 2004.66 | 1398.65 | 1480.84 | 1032.44 | 682.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 349.74 | 1029.81 | 416.39 | 193.15 | 223.24 | 0.00 | 0.00 |
February | 509.80 | 870.26 | 478.02 | 223.50 | 254.51 | 0.00 | 0.00 |
March | 893.55 | 579.39 | 704.57 | 340.46 | 364.10 | 0.00 | 0.00 |
April | 1142.13 | 483.04 | 792.63 | 362.70 | 429.92 | 0.00 | 0.00 |
May | 1251.31 | 330.71 | 796.61 | 301.81 | 494.81 | 0.00 | 0.00 |
June | 1480.50 | 215.33 | 837.74 | 322.28 | 515.47 | 0.00 | 0.00 |
July | 1443.84 | 154.28 | 790.18 | 292.97 | 497.21 | 0.00 | 0.00 |
August | 1430.79 | 130.79 | 774.27 | 289.55 | 484.72 | 0.00 | 0.00 |
September | 1020.72 | 269.18 | 630.82 | 262.76 | 368.05 | 0.00 | 0.00 |
October | 779.51 | 537.81 | 561.98 | 291.73 | 270.25 | 0.00 | 0.00 |
November | 527.27 | 702.81 | 448.50 | 201.31 | 247.19 | 0.00 | 0.00 |
December | 337.78 | 852.60 | 370.01 | 161.84 | 208.17 | 0.00 | 0.00 |
Annual Sum or Average | 932.81 | 511.11 | 634.27 | 270.54 | 363.73 | 0.00 | 0.00 |
Minimum of Months | 337.78 | 130.79 | 370.01 | 161.84 | 208.17 | 0.00 | 0.00 |
Maximum of Months | 1480.50 | 1029.81 | 837.74 | 362.70 | 515.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 49.81 | 1735.34 | 276.88 | 0.00 | 276.88 | 0.00 | 0.00 |
February | 154.17 | 1405.88 | 306.90 | 0.00 | 306.90 | 0.00 | 0.00 |
March | 351.23 | 860.73 | 430.87 | 0.00 | 430.87 | 0.00 | 0.00 |
April | 642.46 | 665.17 | 521.18 | 2.31 | 518.86 | 0.00 | 0.00 |
May | 927.06 | 432.88 | 623.32 | 19.89 | 603.43 | 0.00 | 0.00 |
June | 1279.44 | 280.40 | 685.99 | 45.29 | 640.70 | 0.00 | 0.00 |
July | 1271.01 | 203.25 | 647.23 | 31.46 | 615.77 | 0.00 | 0.00 |
August | 1152.77 | 172.85 | 575.61 | 6.27 | 569.34 | 0.00 | 0.00 |
September | 659.66 | 419.63 | 435.10 | 0.06 | 435.04 | 0.00 | 0.00 |
October | 297.05 | 889.11 | 330.82 | 0.00 | 330.82 | 0.00 | 0.00 |
November | 158.21 | 1196.14 | 296.08 | 0.00 | 296.08 | 0.00 | 0.00 |
December | 51.04 | 1471.51 | 255.96 | 0.00 | 255.96 | 0.00 | 0.00 |
Annual Sum or Average | 585.23 | 808.06 | 449.60 | 8.81 | 440.79 | 0.00 | 0.00 |
Minimum of Months | 49.81 | 172.85 | 255.96 | 0.00 | 255.96 | 0.00 | 0.00 |
Maximum of Months | 1279.44 | 1735.34 | 685.99 | 45.29 | 640.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 302.57 | 1045.99 | 405.38 | 182.85 | 222.54 | 0.00 | 0.00 |
February | 522.27 | 860.07 | 511.06 | 274.59 | 236.47 | 0.00 | 0.00 |
March | 767.84 | 551.78 | 642.98 | 292.70 | 350.28 | 0.00 | 0.00 |
April | 1114.62 | 438.26 | 777.52 | 354.53 | 423.00 | 0.00 | 0.00 |
May | 1341.72 | 298.61 | 853.78 | 361.05 | 492.73 | 0.00 | 0.00 |
June | 1563.85 | 195.38 | 883.95 | 370.48 | 513.47 | 0.00 | 0.00 |
July | 1569.66 | 144.17 | 861.89 | 362.35 | 499.54 | 0.00 | 0.00 |
August | 1457.86 | 122.74 | 788.34 | 312.76 | 475.58 | 0.00 | 0.00 |
September | 1039.00 | 279.47 | 647.91 | 287.07 | 360.84 | 0.00 | 0.00 |
October | 713.97 | 566.66 | 552.72 | 287.59 | 265.13 | 0.00 | 0.00 |
November | 440.16 | 740.00 | 441.91 | 200.09 | 241.81 | 0.00 | 0.00 |
December | 300.69 | 892.87 | 382.78 | 174.48 | 208.29 | 0.00 | 0.00 |
Annual Sum or Average | 929.96 | 509.54 | 646.50 | 288.33 | 358.17 | 0.00 | 0.00 |
Minimum of Months | 300.69 | 122.74 | 382.78 | 174.48 | 208.29 | 0.00 | 0.00 |
Maximum of Months | 1569.66 | 1045.99 | 883.95 | 370.48 | 513.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1755.05 | 1493.95 | 1480.78 | 1032.39 | 448.39 | 0.00 | 0.00 |
February | 1779.35 | 1279.91 | 1382.07 | 926.44 | 455.63 | 0.00 | 0.00 |
March | 1741.89 | 877.33 | 1242.95 | 647.75 | 595.20 | 0.00 | 0.00 |
April | 1459.35 | 702.31 | 930.89 | 303.02 | 627.87 | 0.00 | 0.00 |
May | 1239.83 | 461.17 | 752.12 | 87.42 | 664.71 | 0.00 | 0.00 |
June | 1336.84 | 298.56 | 695.42 | 38.70 | 656.72 | 0.00 | 0.00 |
July | 1409.85 | 213.36 | 703.05 | 52.42 | 650.63 | 0.00 | 0.00 |
August | 1700.42 | 187.90 | 839.39 | 156.80 | 682.59 | 0.00 | 0.00 |
September | 1592.63 | 437.70 | 923.12 | 343.35 | 579.77 | 0.00 | 0.00 |
October | 1999.53 | 885.59 | 1338.26 | 866.92 | 471.34 | 0.00 | 0.00 |
November | 1938.21 | 1139.12 | 1439.73 | 955.38 | 484.35 | 0.00 | 0.00 |
December | 1816.89 | 1330.43 | 1459.64 | 1026.87 | 432.78 | 0.00 | 0.00 |
Annual Sum or Average | 1647.12 | 772.90 | 1097.74 | 534.63 | 563.11 | 0.00 | 0.00 |
Minimum of Months | 1239.83 | 187.90 | 695.42 | 38.70 | 432.78 | 0.00 | 0.00 |
Maximum of Months | 1999.53 | 1493.95 | 1480.78 | 1032.39 | 682.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 351.50 | 1089.63 | 416.39 | 193.15 | 223.24 | 0.00 | 0.00 |
February | 518.19 | 910.32 | 478.01 | 223.50 | 254.51 | 0.00 | 0.00 |
March | 912.51 | 596.63 | 704.56 | 340.46 | 364.10 | 0.00 | 0.00 |
April | 1171.00 | 478.78 | 792.62 | 362.70 | 429.92 | 0.00 | 0.00 |
May | 1276.07 | 325.38 | 796.60 | 301.80 | 494.80 | 0.00 | 0.00 |
June | 1500.84 | 215.51 | 837.73 | 322.27 | 515.46 | 0.00 | 0.00 |
July | 1460.58 | 154.58 | 790.17 | 292.97 | 497.21 | 0.00 | 0.00 |
August | 1442.39 | 135.46 | 774.26 | 289.54 | 484.72 | 0.00 | 0.00 |
September | 1021.68 | 296.81 | 630.81 | 262.76 | 368.05 | 0.00 | 0.00 |
October | 771.05 | 612.62 | 561.97 | 291.73 | 270.25 | 0.00 | 0.00 |
November | 509.98 | 801.94 | 448.50 | 201.31 | 247.19 | 0.00 | 0.00 |
December | 330.40 | 951.94 | 370.01 | 161.84 | 208.17 | 0.00 | 0.00 |
Annual Sum or Average | 941.08 | 545.57 | 634.27 | 270.53 | 363.73 | 0.00 | 0.00 |
Minimum of Months | 330.40 | 135.46 | 370.01 | 161.84 | 208.17 | 0.00 | 0.00 |
Maximum of Months | 1500.84 | 1089.63 | 837.73 | 362.70 | 515.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 47.37 | 1741.15 | 276.89 | 0.00 | 276.89 | 0.00 | 0.00 |
February | 142.51 | 1436.70 | 306.91 | 0.00 | 306.91 | 0.00 | 0.00 |
March | 313.61 | 923.72 | 430.88 | 0.00 | 430.88 | 0.00 | 0.00 |
April | 588.92 | 735.12 | 521.19 | 2.31 | 518.87 | 0.00 | 0.00 |
May | 886.74 | 475.60 | 623.33 | 19.89 | 603.44 | 0.00 | 0.00 |
June | 1257.84 | 298.35 | 686.00 | 45.29 | 640.71 | 0.00 | 0.00 |
July | 1255.02 | 215.44 | 647.25 | 31.46 | 615.78 | 0.00 | 0.00 |
August | 1144.91 | 179.74 | 575.62 | 6.27 | 569.35 | 0.00 | 0.00 |
September | 659.49 | 411.23 | 435.11 | 0.06 | 435.05 | 0.00 | 0.00 |
October | 301.20 | 858.16 | 330.83 | 0.00 | 330.83 | 0.00 | 0.00 |
November | 164.58 | 1155.32 | 296.08 | 0.00 | 296.08 | 0.00 | 0.00 |
December | 50.76 | 1435.65 | 255.96 | 0.00 | 255.96 | 0.00 | 0.00 |
Annual Sum or Average | 570.15 | 819.02 | 449.61 | 8.81 | 440.80 | 0.00 | 0.00 |
Minimum of Months | 47.37 | 179.74 | 255.96 | 0.00 | 255.96 | 0.00 | 0.00 |
Maximum of Months | 1257.84 | 1741.15 | 686.00 | 45.29 | 640.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 296.11 | 1040.84 | 405.39 | 182.85 | 222.54 | 0.00 | 0.00 |
February | 507.70 | 867.78 | 511.07 | 274.59 | 236.48 | 0.00 | 0.00 |
March | 738.73 | 574.22 | 642.99 | 292.71 | 350.28 | 0.00 | 0.00 |
April | 1080.48 | 466.29 | 777.54 | 354.54 | 423.00 | 0.00 | 0.00 |
May | 1313.91 | 315.50 | 853.79 | 361.06 | 492.74 | 0.00 | 0.00 |
June | 1546.56 | 200.57 | 883.96 | 370.49 | 513.47 | 0.00 | 0.00 |
July | 1556.48 | 146.00 | 861.90 | 362.35 | 499.54 | 0.00 | 0.00 |
August | 1448.95 | 121.19 | 788.35 | 312.77 | 475.59 | 0.00 | 0.00 |
September | 1034.49 | 267.51 | 647.92 | 287.08 | 360.84 | 0.00 | 0.00 |
October | 713.46 | 536.43 | 552.73 | 287.60 | 265.13 | 0.00 | 0.00 |
November | 443.86 | 701.81 | 441.91 | 200.10 | 241.82 | 0.00 | 0.00 |
December | 299.09 | 861.46 | 382.78 | 174.49 | 208.29 | 0.00 | 0.00 |
Annual Sum or Average | 917.11 | 506.43 | 646.51 | 288.34 | 358.17 | 0.00 | 0.00 |
Minimum of Months | 296.11 | 121.19 | 382.78 | 174.49 | 208.29 | 0.00 | 0.00 |
Maximum of Months | 1556.48 | 1040.84 | 883.96 | 370.49 | 513.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1720.32 | 1475.52 | 1480.84 | 1032.44 | 448.40 | 0.00 | 0.00 |
February | 1742.25 | 1279.25 | 1382.12 | 926.47 | 455.65 | 0.00 | 0.00 |
March | 1692.94 | 903.75 | 1242.99 | 647.78 | 595.22 | 0.00 | 0.00 |
April | 1405.18 | 758.97 | 930.92 | 303.03 | 627.89 | 0.00 | 0.00 |
May | 1198.21 | 505.15 | 752.14 | 87.42 | 664.73 | 0.00 | 0.00 |
June | 1314.94 | 318.65 | 695.44 | 38.70 | 656.74 | 0.00 | 0.00 |
July | 1395.41 | 225.06 | 703.07 | 52.43 | 650.65 | 0.00 | 0.00 |
August | 1696.12 | 188.45 | 839.42 | 156.81 | 682.61 | 0.00 | 0.00 |
September | 1590.20 | 421.30 | 923.15 | 343.37 | 579.79 | 0.00 | 0.00 |
October | 1993.96 | 834.83 | 1338.31 | 866.96 | 471.35 | 0.00 | 0.00 |
November | 1934.33 | 1070.68 | 1439.78 | 955.42 | 484.37 | 0.00 | 0.00 |
December | 1801.16 | 1268.46 | 1459.70 | 1026.91 | 432.79 | 0.00 | 0.00 |
Annual Sum or Average | 1623.46 | 768.07 | 1097.78 | 534.66 | 563.12 | 0.00 | 0.00 |
Minimum of Months | 1198.21 | 188.45 | 695.44 | 38.70 | 432.79 | 0.00 | 0.00 |
Maximum of Months | 1993.96 | 1475.52 | 1480.84 | 1032.44 | 682.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 343.73 | 1084.14 | 416.39 | 193.15 | 223.24 | 0.00 | 0.00 |
February | 504.75 | 919.61 | 478.02 | 223.50 | 254.51 | 0.00 | 0.00 |
March | 887.21 | 617.14 | 704.57 | 340.46 | 364.10 | 0.00 | 0.00 |
April | 1140.15 | 506.23 | 792.63 | 362.70 | 429.92 | 0.00 | 0.00 |
May | 1253.84 | 342.81 | 796.61 | 301.81 | 494.81 | 0.00 | 0.00 |
June | 1487.17 | 220.78 | 837.74 | 322.28 | 515.47 | 0.00 | 0.00 |
July | 1451.27 | 156.88 | 790.18 | 292.97 | 497.21 | 0.00 | 0.00 |
August | 1437.72 | 133.05 | 774.27 | 289.55 | 484.72 | 0.00 | 0.00 |
September | 1020.82 | 283.79 | 630.82 | 262.76 | 368.05 | 0.00 | 0.00 |
October | 772.78 | 579.09 | 561.98 | 291.73 | 270.25 | 0.00 | 0.00 |
November | 514.29 | 760.70 | 448.50 | 201.31 | 247.19 | 0.00 | 0.00 |
December | 328.97 | 919.69 | 370.01 | 161.84 | 208.17 | 0.00 | 0.00 |
Annual Sum or Average | 930.81 | 541.67 | 634.27 | 270.54 | 363.73 | 0.00 | 0.00 |
Minimum of Months | 328.97 | 133.05 | 370.01 | 161.84 | 208.17 | 0.00 | 0.00 |
Maximum of Months | 1487.17 | 1084.14 | 837.74 | 362.70 | 515.47 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.139414E+09 | 0.443520E+10 | 0.741621E+09 | 0.00 | 0.741621E+09 | 0.00 | 0.00 |
February | 0.360707E+09 | 0.329239E+10 | 0.742465E+09 | 0.00 | 0.742465E+09 | 0.00 | 0.00 |
March | 0.872393E+09 | 0.231800E+10 | 0.115406E+10 | 0.00 | 0.115406E+10 | 0.00 | 0.00 |
April | 0.154094E+10 | 0.181565E+10 | 0.135092E+10 | 5991711.25 | 0.134492E+10 | 0.00 | 0.00 |
May | 0.237282E+10 | 0.122976E+10 | 0.166953E+10 | 53282288.90 | 0.161625E+10 | 0.00 | 0.00 |
June | 0.324052E+10 | 0.757828E+09 | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.00 | 0.00 |
July | 0.333303E+10 | 0.569854E+09 | 0.173358E+10 | 84270737.43 | 0.164931E+10 | 0.00 | 0.00 |
August | 0.304110E+10 | 0.473458E+09 | 0.154174E+10 | 16794811.96 | 0.152494E+10 | 0.00 | 0.00 |
September | 0.171386E+10 | 0.100715E+10 | 0.112781E+10 | 158764.78 | 0.112766E+10 | 0.00 | 0.00 |
October | 0.841221E+09 | 0.212638E+10 | 0.886097E+09 | 0.00 | 0.886097E+09 | 0.00 | 0.00 |
November | 0.476179E+09 | 0.275837E+10 | 0.767444E+09 | 0.00 | 0.767444E+09 | 0.00 | 0.00 |
December | 0.157279E+09 | 0.355893E+10 | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.180895E+11 | 0.243430E+11 | 0.141790E+11 | 0.277896E+09 | 0.139011E+11 | 0.00 | 0.00 |
Minimum of Months | 0.139414E+09 | 0.473458E+09 | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.00 | 0.00 |
Maximum of Months | 0.333303E+10 | 0.443520E+10 | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.823428E+09 | 0.264938E+10 | 0.108580E+10 | 0.489750E+09 | 0.596049E+09 | 0.00 | 0.00 |
February | 0.125626E+10 | 0.198619E+10 | 0.123638E+10 | 0.664299E+09 | 0.572083E+09 | 0.00 | 0.00 |
March | 0.201579E+10 | 0.144568E+10 | 0.172217E+10 | 0.783984E+09 | 0.938190E+09 | 0.00 | 0.00 |
April | 0.281845E+10 | 0.115842E+10 | 0.201537E+10 | 0.918958E+09 | 0.109642E+10 | 0.00 | 0.00 |
May | 0.352347E+10 | 0.819527E+09 | 0.228680E+10 | 0.967054E+09 | 0.131974E+10 | 0.00 | 0.00 |
June | 0.400308E+10 | 0.509885E+09 | 0.229123E+10 | 0.960312E+09 | 0.133092E+10 | 0.00 | 0.00 |
July | 0.415804E+10 | 0.385180E+09 | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.00 | 0.00 |
August | 0.387227E+10 | 0.318295E+09 | 0.211153E+10 | 0.837717E+09 | 0.127381E+10 | 0.00 | 0.00 |
September | 0.269123E+10 | 0.658062E+09 | 0.167941E+10 | 0.744101E+09 | 0.935305E+09 | 0.00 | 0.00 |
October | 0.194582E+10 | 0.133762E+10 | 0.148043E+10 | 0.770305E+09 | 0.710127E+09 | 0.00 | 0.00 |
November | 0.121029E+10 | 0.167598E+10 | 0.114544E+10 | 0.518649E+09 | 0.626787E+09 | 0.00 | 0.00 |
December | 0.844401E+09 | 0.212980E+10 | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.291625E+11 | 0.150740E+11 | 0.203883E+11 | 0.909301E+10 | 0.112953E+11 | 0.00 | 0.00 |
Minimum of Months | 0.823428E+09 | 0.318295E+09 | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.00 | 0.00 |
Maximum of Months | 0.415804E+10 | 0.264938E+10 | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.466144E+10 | 0.374614E+10 | 0.396629E+10 | 0.276528E+10 | 0.120100E+10 | 0.00 | 0.00 |
February | 0.425045E+10 | 0.292607E+10 | 0.334363E+10 | 0.224132E+10 | 0.110230E+10 | 0.00 | 0.00 |
March | 0.456537E+10 | 0.227982E+10 | 0.332924E+10 | 0.173500E+10 | 0.159423E+10 | 0.00 | 0.00 |
April | 0.365058E+10 | 0.187999E+10 | 0.241294E+10 | 0.785465E+09 | 0.162748E+10 | 0.00 | 0.00 |
May | 0.320078E+10 | 0.130546E+10 | 0.201454E+10 | 0.234145E+09 | 0.178040E+10 | 0.00 | 0.00 |
June | 0.338585E+10 | 0.806396E+09 | 0.180257E+10 | 0.100306E+09 | 0.170227E+10 | 0.00 | 0.00 |
July | 0.370806E+10 | 0.593122E+09 | 0.188311E+10 | 0.140416E+09 | 0.174270E+10 | 0.00 | 0.00 |
August | 0.451494E+10 | 0.495430E+09 | 0.224830E+10 | 0.419991E+09 | 0.182831E+10 | 0.00 | 0.00 |
September | 0.412076E+10 | 0.103707E+10 | 0.239282E+10 | 0.890004E+09 | 0.150281E+10 | 0.00 | 0.00 |
October | 0.536927E+10 | 0.208779E+10 | 0.358453E+10 | 0.232207E+10 | 0.126247E+10 | 0.00 | 0.00 |
November | 0.507825E+10 | 0.257323E+10 | 0.373191E+10 | 0.247644E+10 | 0.125548E+10 | 0.00 | 0.00 |
December | 0.489009E+10 | 0.315149E+10 | 0.390966E+10 | 0.275048E+10 | 0.115918E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.513958E+11 | 0.228820E+11 | 0.346195E+11 | 0.168609E+11 | 0.177586E+11 | 0.00 | 0.00 |
Minimum of Months | 0.320078E+10 | 0.495430E+09 | 0.180257E+10 | 0.100306E+09 | 0.110230E+10 | 0.00 | 0.00 |
Maximum of Months | 0.536927E+10 | 0.374614E+10 | 0.396629E+10 | 0.276528E+10 | 0.182831E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.936734E+09 | 0.275823E+10 | 0.111527E+10 | 0.517339E+09 | 0.597928E+09 | 0.00 | 0.00 |
February | 0.123330E+10 | 0.210534E+10 | 0.115642E+10 | 0.540695E+09 | 0.615722E+09 | 0.00 | 0.00 |
March | 0.239329E+10 | 0.155183E+10 | 0.188712E+10 | 0.911897E+09 | 0.975218E+09 | 0.00 | 0.00 |
April | 0.296040E+10 | 0.125203E+10 | 0.205449E+10 | 0.940125E+09 | 0.111436E+10 | 0.00 | 0.00 |
May | 0.335152E+10 | 0.885779E+09 | 0.213365E+10 | 0.808356E+09 | 0.132529E+10 | 0.00 | 0.00 |
June | 0.383746E+10 | 0.558139E+09 | 0.217143E+10 | 0.835339E+09 | 0.133609E+10 | 0.00 | 0.00 |
July | 0.386717E+10 | 0.413222E+09 | 0.211643E+10 | 0.784700E+09 | 0.133173E+10 | 0.00 | 0.00 |
August | 0.383223E+10 | 0.350312E+09 | 0.207380E+10 | 0.775518E+09 | 0.129828E+10 | 0.00 | 0.00 |
September | 0.264569E+10 | 0.697719E+09 | 0.163508E+10 | 0.681080E+09 | 0.953995E+09 | 0.00 | 0.00 |
October | 0.208784E+10 | 0.144046E+10 | 0.150521E+10 | 0.781371E+09 | 0.723842E+09 | 0.00 | 0.00 |
November | 0.136669E+10 | 0.182168E+10 | 0.116252E+10 | 0.521798E+09 | 0.640720E+09 | 0.00 | 0.00 |
December | 0.904715E+09 | 0.228361E+10 | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.294170E+11 | 0.161184E+11 | 0.200024E+11 | 0.853170E+10 | 0.114707E+11 | 0.00 | 0.00 |
Minimum of Months | 0.904715E+09 | 0.350312E+09 | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.00 | 0.00 |
Maximum of Months | 0.386717E+10 | 0.275823E+10 | 0.217143E+10 | 0.940125E+09 | 0.133609E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.133414E+09 | 0.464792E+10 | 0.741606E+09 | 0.00 | 0.741606E+09 | 0.00 | 0.00 |
February | 0.372973E+09 | 0.340110E+10 | 0.742450E+09 | 0.00 | 0.742450E+09 | 0.00 | 0.00 |
March | 0.940745E+09 | 0.230539E+10 | 0.115404E+10 | 0.00 | 0.115404E+10 | 0.00 | 0.00 |
April | 0.166525E+10 | 0.172413E+10 | 0.135089E+10 | 5991535.14 | 0.134490E+10 | 0.00 | 0.00 |
May | 0.248305E+10 | 0.115942E+10 | 0.166950E+10 | 53280722.79 | 0.161622E+10 | 0.00 | 0.00 |
June | 0.331631E+10 | 0.726801E+09 | 0.177808E+10 | 0.117395E+09 | 0.166069E+10 | 0.00 | 0.00 |
July | 0.340427E+10 | 0.544374E+09 | 0.173355E+10 | 84268260.49 | 0.164928E+10 | 0.00 | 0.00 |
August | 0.308757E+10 | 0.462963E+09 | 0.154171E+10 | 16794318.31 | 0.152491E+10 | 0.00 | 0.00 |
September | 0.170984E+10 | 0.108768E+10 | 0.112779E+10 | 158760.12 | 0.112763E+10 | 0.00 | 0.00 |
October | 0.795611E+09 | 0.238140E+10 | 0.886080E+09 | 0.00 | 0.886080E+09 | 0.00 | 0.00 |
November | 0.410090E+09 | 0.310040E+10 | 0.767428E+09 | 0.00 | 0.767428E+09 | 0.00 | 0.00 |
December | 0.136709E+09 | 0.394130E+10 | 0.685560E+09 | 0.00 | 0.685560E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.184558E+11 | 0.254829E+11 | 0.141787E+11 | 0.277888E+09 | 0.139008E+11 | 0.00 | 0.00 |
Minimum of Months | 0.133414E+09 | 0.462963E+09 | 0.685560E+09 | 0.00 | 0.685560E+09 | 0.00 | 0.00 |
Maximum of Months | 0.340427E+10 | 0.464792E+10 | 0.177808E+10 | 0.117395E+09 | 0.166069E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.810390E+09 | 0.280158E+10 | 0.108578E+10 | 0.489741E+09 | 0.596041E+09 | 0.00 | 0.00 |
February | 0.126347E+10 | 0.208069E+10 | 0.123636E+10 | 0.664286E+09 | 0.572077E+09 | 0.00 | 0.00 |
March | 0.205659E+10 | 0.147789E+10 | 0.172215E+10 | 0.783969E+09 | 0.938179E+09 | 0.00 | 0.00 |
April | 0.288910E+10 | 0.113597E+10 | 0.201534E+10 | 0.918940E+09 | 0.109640E+10 | 0.00 | 0.00 |
May | 0.359366E+10 | 0.799801E+09 | 0.228676E+10 | 0.967035E+09 | 0.131973E+10 | 0.00 | 0.00 |
June | 0.405349E+10 | 0.506438E+09 | 0.229120E+10 | 0.960293E+09 | 0.133090E+10 | 0.00 | 0.00 |
July | 0.420417E+10 | 0.386132E+09 | 0.230848E+10 | 0.970512E+09 | 0.133796E+10 | 0.00 | 0.00 |
August | 0.390472E+10 | 0.328736E+09 | 0.211149E+10 | 0.837701E+09 | 0.127379E+10 | 0.00 | 0.00 |
September | 0.269308E+10 | 0.724389E+09 | 0.167938E+10 | 0.744086E+09 | 0.935293E+09 | 0.00 | 0.00 |
October | 0.191230E+10 | 0.151774E+10 | 0.148041E+10 | 0.770290E+09 | 0.710119E+09 | 0.00 | 0.00 |
November | 0.114090E+10 | 0.191809E+10 | 0.114542E+10 | 0.518639E+09 | 0.626779E+09 | 0.00 | 0.00 |
December | 0.805356E+09 | 0.239146E+10 | 0.102522E+10 | 0.467335E+09 | 0.557889E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.293272E+11 | 0.160689E+11 | 0.203880E+11 | 0.909283E+10 | 0.112952E+11 | 0.00 | 0.00 |
Minimum of Months | 0.805356E+09 | 0.328736E+09 | 0.102522E+10 | 0.467335E+09 | 0.557889E+09 | 0.00 | 0.00 |
Maximum of Months | 0.420417E+10 | 0.280158E+10 | 0.230848E+10 | 0.970512E+09 | 0.133796E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.470072E+10 | 0.400140E+10 | 0.396613E+10 | 0.276517E+10 | 0.120096E+10 | 0.00 | 0.00 |
February | 0.430460E+10 | 0.309636E+10 | 0.334350E+10 | 0.224123E+10 | 0.110227E+10 | 0.00 | 0.00 |
March | 0.466549E+10 | 0.234984E+10 | 0.332911E+10 | 0.173493E+10 | 0.159418E+10 | 0.00 | 0.00 |
April | 0.378263E+10 | 0.182037E+10 | 0.241286E+10 | 0.785432E+09 | 0.162743E+10 | 0.00 | 0.00 |
May | 0.332075E+10 | 0.123518E+10 | 0.201448E+10 | 0.234135E+09 | 0.178035E+10 | 0.00 | 0.00 |
June | 0.346509E+10 | 0.773870E+09 | 0.180252E+10 | 0.100302E+09 | 0.170222E+10 | 0.00 | 0.00 |
July | 0.377615E+10 | 0.571467E+09 | 0.188306E+10 | 0.140410E+09 | 0.174265E+10 | 0.00 | 0.00 |
August | 0.455440E+10 | 0.503266E+09 | 0.224823E+10 | 0.419973E+09 | 0.182826E+10 | 0.00 | 0.00 |
September | 0.412809E+10 | 0.113453E+10 | 0.239273E+10 | 0.889967E+09 | 0.150277E+10 | 0.00 | 0.00 |
October | 0.535554E+10 | 0.237196E+10 | 0.358440E+10 | 0.232197E+10 | 0.126243E+10 | 0.00 | 0.00 |
November | 0.502384E+10 | 0.295260E+10 | 0.373177E+10 | 0.247633E+10 | 0.125544E+10 | 0.00 | 0.00 |
December | 0.486635E+10 | 0.356342E+10 | 0.390951E+10 | 0.275036E+10 | 0.115915E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.519437E+11 | 0.243743E+11 | 0.346183E+11 | 0.168602E+11 | 0.177581E+11 | 0.00 | 0.00 |
Minimum of Months | 0.332075E+10 | 0.503266E+09 | 0.180252E+10 | 0.100302E+09 | 0.110227E+10 | 0.00 | 0.00 |
Maximum of Months | 0.535554E+10 | 0.400140E+10 | 0.396613E+10 | 0.276517E+10 | 0.182826E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.941453E+09 | 0.291845E+10 | 0.111525E+10 | 0.517331E+09 | 0.597922E+09 | 0.00 | 0.00 |
February | 0.125362E+10 | 0.220224E+10 | 0.115640E+10 | 0.540686E+09 | 0.615716E+09 | 0.00 | 0.00 |
March | 0.244405E+10 | 0.159802E+10 | 0.188709E+10 | 0.911882E+09 | 0.975209E+09 | 0.00 | 0.00 |
April | 0.303522E+10 | 0.124100E+10 | 0.205446E+10 | 0.940110E+09 | 0.111435E+10 | 0.00 | 0.00 |
May | 0.341781E+10 | 0.871494E+09 | 0.213362E+10 | 0.808342E+09 | 0.132528E+10 | 0.00 | 0.00 |
June | 0.389018E+10 | 0.558597E+09 | 0.217140E+10 | 0.835325E+09 | 0.133608E+10 | 0.00 | 0.00 |
July | 0.391203E+10 | 0.414031E+09 | 0.211640E+10 | 0.784687E+09 | 0.133171E+10 | 0.00 | 0.00 |
August | 0.386328E+10 | 0.362808E+09 | 0.207377E+10 | 0.775505E+09 | 0.129827E+10 | 0.00 | 0.00 |
September | 0.264820E+10 | 0.769334E+09 | 0.163505E+10 | 0.681069E+09 | 0.953985E+09 | 0.00 | 0.00 |
October | 0.206517E+10 | 0.164085E+10 | 0.150519E+10 | 0.781358E+09 | 0.723836E+09 | 0.00 | 0.00 |
November | 0.132188E+10 | 0.207863E+10 | 0.116250E+10 | 0.521790E+09 | 0.640714E+09 | 0.00 | 0.00 |
December | 0.884945E+09 | 0.254968E+10 | 0.991026E+09 | 0.433475E+09 | 0.557551E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.296779E+11 | 0.172051E+11 | 0.200022E+11 | 0.853156E+10 | 0.114706E+11 | 0.00 | 0.00 |
Minimum of Months | 0.884945E+09 | 0.362808E+09 | 0.991026E+09 | 0.433475E+09 | 0.557551E+09 | 0.00 | 0.00 |
Maximum of Months | 0.391203E+10 | 0.291845E+10 | 0.217140E+10 | 0.940110E+09 | 0.133608E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.126863E+09 | 0.466348E+10 | 0.741621E+09 | 0.00 | 0.741621E+09 | 0.00 | 0.00 |
February | 0.344765E+09 | 0.347566E+10 | 0.742465E+09 | 0.00 | 0.742465E+09 | 0.00 | 0.00 |
March | 0.839973E+09 | 0.247408E+10 | 0.115406E+10 | 0.00 | 0.115406E+10 | 0.00 | 0.00 |
April | 0.152648E+10 | 0.190542E+10 | 0.135092E+10 | 5991711.25 | 0.134492E+10 | 0.00 | 0.00 |
May | 0.237504E+10 | 0.127384E+10 | 0.166953E+10 | 53282288.90 | 0.161625E+10 | 0.00 | 0.00 |
June | 0.326033E+10 | 0.773311E+09 | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.00 | 0.00 |
July | 0.336145E+10 | 0.577045E+09 | 0.173358E+10 | 84270737.43 | 0.164931E+10 | 0.00 | 0.00 |
August | 0.306652E+10 | 0.481415E+09 | 0.154174E+10 | 16794811.96 | 0.152494E+10 | 0.00 | 0.00 |
September | 0.170941E+10 | 0.106592E+10 | 0.112781E+10 | 158764.78 | 0.112766E+10 | 0.00 | 0.00 |
October | 0.806731E+09 | 0.229849E+10 | 0.886097E+09 | 0.00 | 0.886097E+09 | 0.00 | 0.00 |
November | 0.426596E+09 | 0.299459E+10 | 0.767444E+09 | 0.00 | 0.767444E+09 | 0.00 | 0.00 |
December | 0.135963E+09 | 0.384525E+10 | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.179801E+11 | 0.258285E+11 | 0.141790E+11 | 0.277896E+09 | 0.139011E+11 | 0.00 | 0.00 |
Minimum of Months | 0.126863E+09 | 0.481415E+09 | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.00 | 0.00 |
Maximum of Months | 0.336145E+10 | 0.466348E+10 | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.793094E+09 | 0.278778E+10 | 0.108580E+10 | 0.489750E+09 | 0.596049E+09 | 0.00 | 0.00 |
February | 0.122822E+10 | 0.209933E+10 | 0.123638E+10 | 0.664299E+09 | 0.572083E+09 | 0.00 | 0.00 |
March | 0.197861E+10 | 0.153798E+10 | 0.172217E+10 | 0.783984E+09 | 0.938190E+09 | 0.00 | 0.00 |
April | 0.280060E+10 | 0.120861E+10 | 0.201537E+10 | 0.918958E+09 | 0.109642E+10 | 0.00 | 0.00 |
May | 0.351919E+10 | 0.845023E+09 | 0.228680E+10 | 0.967054E+09 | 0.131974E+10 | 0.00 | 0.00 |
June | 0.400870E+10 | 0.519872E+09 | 0.229123E+10 | 0.960312E+09 | 0.133092E+10 | 0.00 | 0.00 |
July | 0.416888E+10 | 0.391056E+09 | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.00 | 0.00 |
August | 0.388086E+10 | 0.324599E+09 | 0.211153E+10 | 0.837717E+09 | 0.127381E+10 | 0.00 | 0.00 |
September | 0.268140E+10 | 0.693390E+09 | 0.167941E+10 | 0.744101E+09 | 0.935305E+09 | 0.00 | 0.00 |
October | 0.191094E+10 | 0.143677E+10 | 0.148043E+10 | 0.770305E+09 | 0.710127E+09 | 0.00 | 0.00 |
November | 0.115049E+10 | 0.181909E+10 | 0.114544E+10 | 0.518649E+09 | 0.626787E+09 | 0.00 | 0.00 |
December | 0.801070E+09 | 0.230734E+10 | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.289220E+11 | 0.159709E+11 | 0.203883E+11 | 0.909301E+10 | 0.112953E+11 | 0.00 | 0.00 |
Minimum of Months | 0.793094E+09 | 0.324599E+09 | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.00 | 0.00 |
Maximum of Months | 0.416888E+10 | 0.278778E+10 | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.460771E+10 | 0.395203E+10 | 0.396629E+10 | 0.276528E+10 | 0.120100E+10 | 0.00 | 0.00 |
February | 0.421486E+10 | 0.309477E+10 | 0.334363E+10 | 0.224132E+10 | 0.110230E+10 | 0.00 | 0.00 |
March | 0.453437E+10 | 0.242061E+10 | 0.332924E+10 | 0.173500E+10 | 0.159423E+10 | 0.00 | 0.00 |
April | 0.364224E+10 | 0.196726E+10 | 0.241294E+10 | 0.785465E+09 | 0.162748E+10 | 0.00 | 0.00 |
May | 0.320929E+10 | 0.135300E+10 | 0.201454E+10 | 0.234145E+09 | 0.178040E+10 | 0.00 | 0.00 |
June | 0.340833E+10 | 0.825937E+09 | 0.180257E+10 | 0.100306E+09 | 0.170227E+10 | 0.00 | 0.00 |
July | 0.373748E+10 | 0.602799E+09 | 0.188311E+10 | 0.140416E+09 | 0.174270E+10 | 0.00 | 0.00 |
August | 0.454289E+10 | 0.504752E+09 | 0.224830E+10 | 0.419991E+09 | 0.182831E+10 | 0.00 | 0.00 |
September | 0.412179E+10 | 0.109202E+10 | 0.239282E+10 | 0.890004E+09 | 0.150281E+10 | 0.00 | 0.00 |
October | 0.534061E+10 | 0.223602E+10 | 0.358453E+10 | 0.232207E+10 | 0.126247E+10 | 0.00 | 0.00 |
November | 0.501379E+10 | 0.277519E+10 | 0.373191E+10 | 0.247644E+10 | 0.125548E+10 | 0.00 | 0.00 |
December | 0.482422E+10 | 0.339743E+10 | 0.390966E+10 | 0.275048E+10 | 0.115918E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.511976E+11 | 0.242218E+11 | 0.346195E+11 | 0.168609E+11 | 0.177586E+11 | 0.00 | 0.00 |
Minimum of Months | 0.320929E+10 | 0.504752E+09 | 0.180257E+10 | 0.100306E+09 | 0.110230E+10 | 0.00 | 0.00 |
Maximum of Months | 0.534061E+10 | 0.395203E+10 | 0.396629E+10 | 0.276528E+10 | 0.182831E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.920638E+09 | 0.290377E+10 | 0.111527E+10 | 0.517339E+09 | 0.597928E+09 | 0.00 | 0.00 |
February | 0.122108E+10 | 0.222473E+10 | 0.115642E+10 | 0.540695E+09 | 0.615722E+09 | 0.00 | 0.00 |
March | 0.237629E+10 | 0.165294E+10 | 0.188712E+10 | 0.911897E+09 | 0.975218E+09 | 0.00 | 0.00 |
April | 0.295526E+10 | 0.131214E+10 | 0.205449E+10 | 0.940125E+09 | 0.111436E+10 | 0.00 | 0.00 |
May | 0.335828E+10 | 0.918193E+09 | 0.213365E+10 | 0.808356E+09 | 0.132529E+10 | 0.00 | 0.00 |
June | 0.385475E+10 | 0.572271E+09 | 0.217143E+10 | 0.835339E+09 | 0.133609E+10 | 0.00 | 0.00 |
July | 0.388707E+10 | 0.420188E+09 | 0.211643E+10 | 0.784700E+09 | 0.133173E+10 | 0.00 | 0.00 |
August | 0.385080E+10 | 0.356353E+09 | 0.207380E+10 | 0.775518E+09 | 0.129828E+10 | 0.00 | 0.00 |
September | 0.264598E+10 | 0.735589E+09 | 0.163508E+10 | 0.681080E+09 | 0.953995E+09 | 0.00 | 0.00 |
October | 0.206981E+10 | 0.155105E+10 | 0.150521E+10 | 0.781371E+09 | 0.723842E+09 | 0.00 | 0.00 |
November | 0.133305E+10 | 0.197174E+10 | 0.116252E+10 | 0.521798E+09 | 0.640720E+09 | 0.00 | 0.00 |
December | 0.881121E+09 | 0.246330E+10 | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.293541E+11 | 0.170823E+11 | 0.200024E+11 | 0.853170E+10 | 0.114707E+11 | 0.00 | 0.00 |
Minimum of Months | 0.881121E+09 | 0.356353E+09 | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.00 | 0.00 |
Maximum of Months | 0.388707E+10 | 0.290377E+10 | 0.217143E+10 | 0.940125E+09 | 0.133609E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.500923E+10 | -0.427283E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -736406540.5 | 58.98 | 0.00 | 0.00 |
February | 0.454199E+10 | -0.389177E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -650221378.1 | 58.98 | 0.00 | 0.00 |
March | 0.515100E+10 | -0.445076E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -700238331.4 | 58.99 | 0.00 | 0.00 |
April | 0.442093E+10 | -0.374963E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -671302778.5 | 58.98 | 0.00 | 0.00 |
May | 0.438984E+10 | -0.370013E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689711199.1 | 58.98 | 0.00 | 0.00 |
June | 0.404892E+10 | -0.338180E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667116230.6 | 58.98 | 0.00 | 0.00 |
July | 0.370849E+10 | -0.302124E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687256706.5 | 58.98 | 0.00 | 0.00 |
August | 0.401971E+10 | -0.333103E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688679763.8 | 58.98 | 0.00 | 0.00 |
September | 0.381084E+10 | -0.314527E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -665572510.8 | 58.98 | 0.00 | 0.00 |
October | 0.420846E+10 | -0.351561E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692855404.0 | 58.98 | 0.00 | 0.00 |
November | 0.444154E+10 | -0.376445E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -677093099.5 | 58.98 | 0.00 | 0.00 |
December | 0.470788E+10 | -0.399243E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -715449811.5 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.524588E+11 | -0.442169E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.824190E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.370849E+10 | -0.445076E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -736406540.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.515100E+10 | -0.302124E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -650221378.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.50 | 0.48 | 01-JAN-09:09 | 5920.38 | 33.55 | 265.83 | 271.17 | 1650.66 | 25.57 | 177.00 | 250.00 |
February | 263.00 | 0.51 | 0.48 | 01-FEB-10:30 | 6934.78 | 33.58 | 230.83 | 246.83 | 1105.41 | 19.24 | 74.17 | 210.83 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:39 | 1633.21 | 18.11 | 6.83 | 317.67 | 957.68 | 20.20 | 123.00 | 283.00 |
April | 369.33 | 0.51 | 0.48 | 01-APR-08:20 | 1344.75 | 17.74 | 0.00 | 324.00 | 770.22 | 19.89 | 103.50 | 279.83 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:40 | 1215.20 | 17.92 | 0.00 | 357.83 | 681.12 | 20.08 | 88.50 | 310.33 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-06:00 | 1129.01 | 17.67 | 0.00 | 358.33 | 638.99 | 19.83 | 89.50 | 310.67 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-07:19 | 1190.49 | 17.84 | 0.00 | 362.33 | 665.84 | 19.97 | 116.50 | 312.50 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:10 | 1455.23 | 18.47 | 0.00 | 349.17 | 798.32 | 20.59 | 173.00 | 311.33 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-07:30 | 1557.93 | 18.58 | 6.50 | 307.67 | 877.00 | 20.45 | 120.83 | 268.00 |
October | 293.50 | 0.50 | 0.48 | 01-OCT-08:20 | 2820.72 | 23.84 | 119.17 | 291.83 | 1066.59 | 19.62 | 82.67 | 254.83 |
November | 299.00 | 0.50 | 0.48 | 01-NOV-08:20 | 5827.00 | 34.49 | 285.50 | 272.50 | 1198.31 | 24.23 | 166.50 | 252.67 |
December | 285.17 | 0.49 | 0.48 | 01-DEC-07:00 | 5579.70 | 34.34 | 269.83 | 267.67 | 1592.15 | 26.53 | 179.17 | 245.17 |
Annual Sum or Average | 4071.00 | 0.51 | 2765.65 | 22.91 | 1184.50 | 3727.00 | 959.12 | 21.18 | 1494.33 | 3289.17 | ||
Minimum of Months | 263.00 | 0.49 | 0.48 | 1129.01 | 17.67 | 0.00 | 246.83 | 638.99 | 19.24 | 74.17 | 210.83 | |
Maximum of Months | 411.67 | 0.51 | 0.48 | 6934.78 | 34.49 | 285.50 | 362.33 | 1650.66 | 26.53 | 179.17 | 312.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.52 | 0.48 | 01-JAN-08:00 | 1397.54 | 19.11 | 71.83 | 240.67 | 712.40 | 19.97 | 55.00 | 178.00 |
February | 263.00 | 0.53 | 0.48 | 01-FEB-10:30 | 1855.92 | 18.92 | 60.17 | 222.50 | 1026.20 | 21.06 | 50.00 | 176.67 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:39 | 2233.61 | 20.54 | 105.50 | 309.50 | 877.58 | 20.09 | 47.50 | 266.67 |
April | 369.33 | 0.51 | 0.48 | 01-APR-07:00 | 2150.98 | 19.95 | 93.33 | 324.50 | 1159.31 | 21.17 | 67.17 | 287.17 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-06:00 | 2452.55 | 20.31 | 108.50 | 366.17 | 1014.10 | 20.19 | 50.00 | 327.17 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-06:19 | 2476.13 | 20.23 | 110.50 | 368.17 | 1037.98 | 20.90 | 64.00 | 332.00 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-05:00 | 2450.90 | 20.27 | 105.50 | 371.67 | 1038.64 | 20.27 | 51.83 | 330.50 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-06:30 | 2246.61 | 20.62 | 102.17 | 350.33 | 1185.56 | 21.91 | 73.50 | 313.00 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-06:00 | 2074.68 | 19.38 | 67.33 | 302.83 | 1118.49 | 21.63 | 55.33 | 259.00 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-07:49 | 2480.84 | 20.86 | 90.67 | 267.17 | 925.34 | 19.91 | 43.67 | 214.00 |
November | 299.00 | 0.52 | 0.48 | 01-NOV-08:09 | 1694.77 | 21.16 | 97.00 | 246.83 | 915.18 | 21.99 | 75.50 | 200.33 |
December | 285.17 | 0.52 | 0.48 | 01-DEC-07:49 | 1434.68 | 19.72 | 73.17 | 236.17 | 768.26 | 21.40 | 60.00 | 176.83 |
Annual Sum or Average | 4071.00 | 0.51 | 2122.25 | 20.13 | 1085.67 | 3606.50 | 992.83 | 20.86 | 693.50 | 3061.33 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1397.54 | 18.92 | 60.17 | 222.50 | 712.40 | 19.91 | 43.67 | 176.67 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 2480.84 | 21.16 | 110.50 | 371.67 | 1185.56 | 21.99 | 75.50 | 332.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-10:50 | 498.44 | 14.33 | 0.00 | 211.17 | 301.36 | 16.73 | 0.00 | 87.17 |
February | 263.00 | 0.55 | 0.48 | 01-FEB-13:39 | 529.36 | 14.53 | 0.00 | 190.00 | 329.03 | 16.88 | 0.00 | 110.67 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-08:00 | 675.39 | 16.35 | 0.00 | 299.33 | 412.09 | 18.56 | 0.00 | 225.83 |
April | 369.33 | 0.51 | 0.48 | 01-APR-08:30 | 806.72 | 17.26 | 0.00 | 327.83 | 483.64 | 19.37 | 0.67 | 270.50 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-07:30 | 1008.63 | 20.32 | 51.83 | 382.33 | 581.94 | 20.46 | 65.17 | 341.83 |
June | 411.67 | 0.49 | 0.48 | 01-JUN-06:40 | 1097.26 | 21.04 | 66.83 | 385.17 | 645.83 | 23.05 | 176.50 | 363.33 |
July | 411.00 | 0.50 | 0.48 | 01-JUL-06:10 | 1105.58 | 20.47 | 53.33 | 384.83 | 615.06 | 21.44 | 145.00 | 348.33 |
August | 390.50 | 0.50 | 0.48 | 01-AUG-06:00 | 986.07 | 18.22 | 0.00 | 359.17 | 575.97 | 20.30 | 52.50 | 324.83 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-07:30 | 749.92 | 17.07 | 0.00 | 302.50 | 454.78 | 19.17 | 0.00 | 218.83 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:39 | 553.98 | 15.06 | 0.00 | 236.33 | 354.52 | 17.45 | 0.00 | 142.67 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-09:50 | 515.74 | 14.64 | 0.00 | 224.00 | 313.81 | 16.98 | 0.00 | 120.33 |
December | 285.17 | 0.55 | 0.48 | 01-DEC-09:30 | 481.59 | 14.41 | 0.00 | 203.00 | 292.19 | 16.85 | 0.00 | 80.83 |
Annual Sum or Average | 4071.00 | 0.52 | 785.86 | 17.33 | 172.00 | 3505.67 | 465.50 | 19.23 | 439.83 | 2635.17 | ||
Minimum of Months | 263.00 | 0.49 | 0.48 | 481.59 | 14.33 | 0.00 | 190.00 | 292.19 | 16.73 | 0.00 | 80.83 | |
Maximum of Months | 411.67 | 0.55 | 0.48 | 1105.58 | 21.04 | 66.83 | 385.17 | 645.83 | 23.05 | 176.50 | 363.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.52 | 0.48 | 01-JAN-10:39 | 1717.65 | 21.12 | 89.67 | 243.33 | 951.84 | 21.82 | 68.00 | 190.67 |
February | 263.00 | 0.53 | 0.48 | 01-FEB-13:39 | 1641.64 | 18.88 | 64.00 | 214.00 | 853.54 | 19.70 | 40.33 | 165.00 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-09:20 | 2213.33 | 20.88 | 98.17 | 309.33 | 1177.37 | 21.79 | 72.00 | 265.67 |
April | 369.33 | 0.51 | 0.48 | 01-APR-09:00 | 2359.32 | 18.66 | 78.67 | 330.50 | 1299.47 | 20.02 | 51.83 | 288.67 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-07:00 | 2358.91 | 17.03 | 50.83 | 364.00 | 1004.51 | 18.01 | 0.00 | 325.50 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-07:30 | 2480.11 | 14.70 | 1.67 | 367.50 | 1061.85 | 17.97 | 0.00 | 330.67 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-07:30 | 2461.49 | 17.01 | 52.00 | 367.17 | 1039.12 | 18.01 | 0.00 | 327.50 |
August | 390.50 | 0.50 | 0.48 | 01-AUG-07:30 | 2413.60 | 19.51 | 89.00 | 352.67 | 1053.24 | 18.70 | 7.67 | 318.83 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-08:09 | 2166.48 | 21.46 | 90.83 | 305.00 | 1144.91 | 22.22 | 62.67 | 256.50 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-10:39 | 2341.93 | 20.89 | 92.67 | 262.33 | 899.11 | 19.97 | 42.83 | 209.17 |
November | 299.00 | 0.52 | 0.48 | 01-NOV-09:39 | 1590.18 | 19.46 | 80.83 | 248.00 | 854.44 | 21.74 | 68.33 | 199.00 |
December | 285.17 | 0.52 | 0.48 | 01-DEC-09:20 | 1388.01 | 19.35 | 74.17 | 236.50 | 754.13 | 21.33 | 63.33 | 177.33 |
Annual Sum or Average | 4071.00 | 0.51 | 2142.30 | 18.87 | 862.50 | 3600.33 | 1020.79 | 19.92 | 477.00 | 3054.50 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1388.01 | 14.70 | 1.67 | 214.00 | 754.13 | 17.97 | 0.00 | 165.00 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 2480.11 | 21.46 | 98.17 | 367.50 | 1299.47 | 22.22 | 72.00 | 330.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.50 | 0.48 | 01-JAN-09:09 | 5799.80 | 33.11 | 258.00 | 269.83 | 1555.30 | 23.28 | 103.33 | 248.83 |
February | 263.00 | 0.51 | 0.48 | 01-FEB-10:30 | 6826.34 | 33.21 | 229.50 | 245.67 | 1055.84 | 18.03 | 25.83 | 213.83 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:39 | 1546.96 | 14.21 | 6.67 | 314.67 | 893.23 | 17.61 | 0.33 | 278.67 |
April | 369.33 | 0.51 | 0.48 | 01-APR-08:30 | 1284.74 | 14.00 | 0.00 | 321.00 | 728.96 | 17.50 | 0.00 | 276.83 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:40 | 1167.83 | 14.24 | 0.00 | 355.67 | 651.76 | 17.72 | 0.00 | 307.17 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-07:10 | 1086.73 | 14.05 | 0.00 | 356.17 | 613.77 | 17.52 | 0.00 | 306.33 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-07:19 | 1144.77 | 14.23 | 0.00 | 358.83 | 638.15 | 17.66 | 0.00 | 308.17 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:19 | 1395.04 | 14.84 | 0.00 | 347.17 | 759.70 | 18.27 | 0.00 | 307.00 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-07:30 | 1484.19 | 14.97 | 6.50 | 304.83 | 825.43 | 18.10 | 0.00 | 265.17 |
October | 293.50 | 0.50 | 0.48 | 01-OCT-10:39 | 2717.02 | 21.23 | 117.33 | 290.17 | 984.16 | 16.84 | 2.00 | 250.83 |
November | 299.00 | 0.51 | 0.48 | 01-NOV-08:20 | 5713.98 | 34.08 | 281.17 | 271.67 | 1111.17 | 21.75 | 82.17 | 249.33 |
December | 285.17 | 0.50 | 0.48 | 01-DEC-07:00 | 5407.84 | 32.28 | 249.33 | 263.67 | 1495.07 | 24.33 | 116.17 | 242.67 |
Annual Sum or Average | 4071.00 | 0.51 | 2684.52 | 20.10 | 1148.50 | 3699.33 | 904.89 | 18.86 | 329.83 | 3254.83 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1086.73 | 14.00 | 0.00 | 245.67 | 613.77 | 16.84 | 0.00 | 213.83 | |
Maximum of Months | 411.67 | 0.51 | 0.48 | 6826.34 | 34.08 | 281.17 | 358.83 | 1555.30 | 24.33 | 116.17 | 308.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.52 | 0.48 | 01-JAN-09:09 | 1358.32 | 18.61 | 71.33 | 238.67 | 681.94 | 19.72 | 48.67 | 171.33 |
February | 263.00 | 0.53 | 0.48 | 01-FEB-10:30 | 1806.26 | 18.42 | 60.17 | 219.17 | 985.15 | 20.85 | 48.50 | 173.33 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:39 | 2182.55 | 20.07 | 105.33 | 307.50 | 836.12 | 19.88 | 47.33 | 262.17 |
April | 369.33 | 0.51 | 0.48 | 01-APR-07:00 | 2090.24 | 19.48 | 93.00 | 322.50 | 1111.38 | 20.99 | 67.17 | 283.17 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-06:00 | 2381.81 | 19.85 | 108.33 | 363.17 | 963.64 | 20.02 | 50.17 | 323.17 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-06:19 | 2412.05 | 19.78 | 110.33 | 365.50 | 988.18 | 20.74 | 64.00 | 329.00 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-05:00 | 2383.04 | 19.82 | 105.33 | 368.83 | 987.46 | 20.10 | 51.83 | 328.00 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-06:30 | 2175.50 | 20.16 | 102.17 | 348.67 | 1136.05 | 21.73 | 73.50 | 309.17 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-07:10 | 2015.65 | 18.88 | 67.33 | 301.00 | 1070.50 | 21.43 | 55.33 | 252.67 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-07:00 | 2427.12 | 20.38 | 90.50 | 264.50 | 880.94 | 19.70 | 42.67 | 209.00 |
November | 299.00 | 0.53 | 0.48 | 01-NOV-08:09 | 1652.64 | 20.69 | 97.00 | 243.83 | 881.95 | 21.77 | 72.83 | 195.33 |
December | 285.17 | 0.52 | 0.48 | 01-DEC-07:49 | 1394.67 | 19.20 | 73.00 | 233.33 | 736.12 | 21.16 | 57.50 | 172.33 |
Annual Sum or Average | 4071.00 | 0.51 | 2064.99 | 19.66 | 1083.83 | 3576.67 | 948.66 | 20.66 | 679.50 | 3008.67 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1358.32 | 18.42 | 60.17 | 219.17 | 681.94 | 19.70 | 42.67 | 171.33 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 2427.12 | 20.69 | 110.33 | 368.83 | 1136.05 | 21.77 | 73.50 | 329.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-10:00 | 481.03 | 10.45 | 0.00 | 205.33 | 291.98 | 14.18 | 0.00 | 78.50 |
February | 263.00 | 0.55 | 0.48 | 01-FEB-13:39 | 511.45 | 10.76 | 0.00 | 184.33 | 319.62 | 14.45 | 0.00 | 106.00 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-09:09 | 652.25 | 12.84 | 0.00 | 296.17 | 399.71 | 16.41 | 0.00 | 219.17 |
April | 369.33 | 0.51 | 0.48 | 01-APR-08:30 | 779.27 | 13.79 | 0.00 | 325.50 | 468.71 | 17.31 | 0.00 | 265.67 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-07:30 | 972.34 | 17.27 | 51.83 | 379.83 | 571.59 | 20.44 | 52.50 | 348.00 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-06:40 | 1057.03 | 18.06 | 65.67 | 384.67 | 622.27 | 21.21 | 68.17 | 361.00 |
July | 411.00 | 0.50 | 0.48 | 01-JUL-06:10 | 1061.59 | 16.15 | 27.33 | 383.00 | 601.99 | 20.57 | 54.00 | 350.50 |
August | 390.50 | 0.50 | 0.48 | 01-AUG-06:00 | 950.10 | 14.78 | 0.00 | 357.83 | 555.66 | 18.24 | 0.00 | 320.33 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-07:40 | 723.09 | 13.75 | 0.00 | 299.33 | 440.23 | 17.22 | 0.00 | 209.83 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:39 | 535.53 | 11.50 | 0.00 | 230.33 | 345.08 | 15.24 | 0.00 | 134.50 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-09:50 | 497.27 | 10.88 | 0.00 | 218.67 | 303.86 | 14.53 | 0.00 | 108.50 |
December | 285.17 | 0.55 | 0.48 | 01-DEC-09:30 | 464.14 | 10.49 | 0.00 | 197.67 | 282.77 | 14.27 | 0.00 | 68.50 |
Annual Sum or Average | 4071.00 | 0.52 | 757.50 | 13.77 | 144.83 | 3462.67 | 451.98 | 17.38 | 174.67 | 2570.50 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 464.14 | 10.45 | 0.00 | 184.33 | 282.77 | 14.18 | 0.00 | 68.50 | |
Maximum of Months | 411.67 | 0.55 | 0.48 | 1061.59 | 18.06 | 65.67 | 384.67 | 622.27 | 21.21 | 68.17 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.52 | 0.48 | 01-JAN-10:50 | 1675.90 | 20.73 | 89.17 | 240.67 | 918.99 | 21.71 | 68.00 | 185.17 |
February | 263.00 | 0.53 | 0.48 | 01-FEB-13:39 | 1591.15 | 18.45 | 63.83 | 211.33 | 813.80 | 19.57 | 40.00 | 161.83 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-09:20 | 2087.83 | 18.80 | 77.50 | 306.50 | 1129.42 | 21.66 | 72.17 | 263.00 |
April | 369.33 | 0.51 | 0.48 | 01-APR-09:00 | 2298.56 | 18.19 | 78.50 | 327.67 | 1251.60 | 19.86 | 51.83 | 285.00 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-08:09 | 2291.09 | 16.52 | 50.83 | 361.67 | 957.87 | 17.82 | 0.00 | 322.50 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-07:30 | 2393.35 | 14.16 | 1.67 | 363.83 | 1014.43 | 17.77 | 0.00 | 327.50 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-07:30 | 2376.73 | 16.50 | 52.00 | 364.83 | 991.75 | 17.81 | 0.00 | 323.67 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:40 | 2340.46 | 18.88 | 86.50 | 351.00 | 996.68 | 18.53 | 7.83 | 313.83 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-08:20 | 2062.88 | 19.38 | 75.50 | 301.00 | 1097.64 | 22.09 | 62.67 | 252.00 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-10:39 | 2289.71 | 20.47 | 92.50 | 260.00 | 856.37 | 19.84 | 42.83 | 206.00 |
November | 299.00 | 0.53 | 0.48 | 01-NOV-09:50 | 1545.84 | 19.03 | 80.83 | 245.67 | 820.14 | 21.63 | 68.00 | 196.00 |
December | 285.17 | 0.52 | 0.48 | 01-DEC-09:30 | 1349.25 | 18.93 | 73.67 | 233.33 | 723.46 | 21.22 | 63.00 | 173.00 |
Annual Sum or Average | 4071.00 | 0.51 | 2071.25 | 18.13 | 822.50 | 3567.50 | 976.51 | 19.77 | 476.33 | 3009.50 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1349.25 | 14.16 | 1.67 | 211.33 | 723.46 | 17.77 | 0.00 | 161.83 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 2393.35 | 20.73 | 92.50 | 364.83 | 1251.60 | 22.09 | 72.17 | 327.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.50 | 0.48 | 01-JAN-09:09 | 5799.76 | 33.11 | 258.00 | 269.83 | 1555.23 | 23.28 | 103.33 | 248.83 |
February | 263.00 | 0.51 | 0.48 | 01-FEB-10:30 | 6826.27 | 33.21 | 229.50 | 245.67 | 1055.77 | 18.03 | 25.83 | 213.83 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:39 | 1546.87 | 14.21 | 6.67 | 314.67 | 893.17 | 17.61 | 0.50 | 278.67 |
April | 369.33 | 0.51 | 0.48 | 01-APR-08:30 | 1284.67 | 14.00 | 0.00 | 321.00 | 728.90 | 17.51 | 0.00 | 276.83 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:40 | 1167.76 | 14.24 | 0.00 | 355.67 | 651.71 | 17.72 | 0.00 | 307.17 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-07:10 | 1086.67 | 14.05 | 0.00 | 356.17 | 613.72 | 17.52 | 0.00 | 306.33 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-07:19 | 1144.71 | 14.23 | 0.00 | 358.83 | 638.10 | 17.66 | 0.00 | 308.17 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:19 | 1394.95 | 14.84 | 0.00 | 347.17 | 759.64 | 18.27 | 0.00 | 307.00 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-07:30 | 1484.10 | 14.97 | 6.50 | 304.67 | 825.37 | 18.11 | 0.00 | 265.17 |
October | 293.50 | 0.50 | 0.48 | 01-OCT-10:39 | 2716.95 | 21.23 | 117.33 | 290.17 | 984.10 | 16.84 | 2.00 | 250.83 |
November | 299.00 | 0.51 | 0.48 | 01-NOV-08:20 | 5713.93 | 34.08 | 281.17 | 271.67 | 1111.09 | 21.75 | 82.17 | 249.33 |
December | 285.17 | 0.50 | 0.48 | 01-DEC-07:00 | 5407.81 | 32.29 | 249.33 | 263.67 | 1495.00 | 24.33 | 116.17 | 242.67 |
Annual Sum or Average | 4071.00 | 0.51 | 2684.45 | 20.11 | 1148.50 | 3699.17 | 904.83 | 18.86 | 330.00 | 3254.83 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1086.67 | 14.00 | 0.00 | 245.67 | 613.72 | 16.84 | 0.00 | 213.83 | |
Maximum of Months | 411.67 | 0.51 | 0.48 | 6826.27 | 34.08 | 281.17 | 358.83 | 1555.23 | 24.33 | 116.17 | 308.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.52 | 0.48 | 01-JAN-09:09 | 1358.29 | 18.61 | 71.33 | 238.67 | 681.91 | 19.73 | 48.67 | 171.33 |
February | 263.00 | 0.53 | 0.48 | 01-FEB-10:30 | 1806.24 | 18.42 | 60.17 | 219.17 | 985.12 | 20.85 | 48.50 | 173.33 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:39 | 2182.51 | 20.07 | 105.33 | 307.50 | 836.07 | 19.88 | 47.33 | 262.17 |
April | 369.33 | 0.51 | 0.48 | 01-APR-07:00 | 2090.19 | 19.48 | 93.00 | 322.50 | 1111.33 | 20.99 | 67.17 | 283.17 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-06:00 | 2381.75 | 19.85 | 108.33 | 363.17 | 963.58 | 20.02 | 50.17 | 323.17 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-06:19 | 2411.99 | 19.78 | 110.33 | 365.50 | 988.12 | 20.74 | 64.00 | 329.00 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-05:00 | 2382.98 | 19.82 | 105.33 | 368.83 | 987.40 | 20.10 | 51.83 | 328.00 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-06:30 | 2175.44 | 20.16 | 102.17 | 348.67 | 1135.99 | 21.73 | 73.50 | 309.17 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-07:10 | 2015.61 | 18.88 | 67.33 | 301.00 | 1070.45 | 21.43 | 55.33 | 252.67 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-07:00 | 2427.10 | 20.38 | 90.50 | 264.50 | 880.91 | 19.70 | 42.67 | 209.00 |
November | 299.00 | 0.53 | 0.48 | 01-NOV-08:09 | 1652.61 | 20.69 | 97.00 | 244.00 | 881.91 | 21.77 | 72.83 | 195.33 |
December | 285.17 | 0.52 | 0.48 | 01-DEC-07:49 | 1394.64 | 19.20 | 73.00 | 233.33 | 736.09 | 21.16 | 57.50 | 172.33 |
Annual Sum or Average | 4071.00 | 0.51 | 2064.95 | 19.66 | 1083.83 | 3576.83 | 948.62 | 20.66 | 679.50 | 3008.67 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1358.29 | 18.42 | 60.17 | 219.17 | 681.91 | 19.70 | 42.67 | 171.33 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 2427.10 | 20.69 | 110.33 | 368.83 | 1135.99 | 21.77 | 73.50 | 329.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-10:00 | 481.02 | 10.45 | 0.00 | 205.33 | 291.96 | 14.18 | 0.00 | 78.50 |
February | 263.00 | 0.55 | 0.48 | 01-FEB-13:39 | 511.43 | 10.76 | 0.00 | 184.33 | 319.60 | 14.45 | 0.00 | 106.00 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-09:09 | 652.23 | 12.84 | 0.00 | 296.17 | 399.69 | 16.41 | 0.00 | 219.17 |
April | 369.33 | 0.51 | 0.48 | 01-APR-08:30 | 779.24 | 13.79 | 0.00 | 325.50 | 468.68 | 17.31 | 0.00 | 265.67 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-07:30 | 972.30 | 17.27 | 51.83 | 379.83 | 571.55 | 20.44 | 52.50 | 348.00 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-06:40 | 1056.99 | 18.07 | 65.67 | 384.67 | 622.23 | 21.22 | 68.17 | 361.00 |
July | 411.00 | 0.50 | 0.48 | 01-JUL-06:10 | 1061.55 | 16.15 | 27.33 | 383.00 | 601.95 | 20.57 | 54.00 | 350.50 |
August | 390.50 | 0.50 | 0.48 | 01-AUG-06:00 | 950.06 | 14.78 | 0.00 | 357.83 | 555.62 | 18.25 | 0.00 | 320.33 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-07:40 | 723.07 | 13.76 | 0.00 | 299.33 | 440.20 | 17.22 | 0.00 | 209.50 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:39 | 535.52 | 11.50 | 0.00 | 230.17 | 345.06 | 15.24 | 0.00 | 134.50 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-09:50 | 497.25 | 10.88 | 0.00 | 218.67 | 303.84 | 14.54 | 0.00 | 108.50 |
December | 285.17 | 0.55 | 0.48 | 01-DEC-09:30 | 464.12 | 10.49 | 0.00 | 197.67 | 282.75 | 14.27 | 0.00 | 68.50 |
Annual Sum or Average | 4071.00 | 0.52 | 757.47 | 13.78 | 144.83 | 3462.50 | 451.95 | 17.38 | 174.67 | 2570.17 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 464.12 | 10.45 | 0.00 | 184.33 | 282.75 | 14.18 | 0.00 | 68.50 | |
Maximum of Months | 411.67 | 0.55 | 0.48 | 1061.55 | 18.07 | 65.67 | 384.67 | 622.23 | 21.22 | 68.17 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.52 | 0.48 | 01-JAN-10:50 | 1675.87 | 20.73 | 89.17 | 240.67 | 918.95 | 21.72 | 68.00 | 185.17 |
February | 263.00 | 0.53 | 0.48 | 01-FEB-13:39 | 1591.12 | 18.46 | 63.83 | 211.33 | 813.76 | 19.57 | 40.00 | 161.83 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-09:20 | 2087.79 | 18.80 | 77.50 | 306.50 | 1129.37 | 21.66 | 72.17 | 263.00 |
April | 369.33 | 0.51 | 0.48 | 01-APR-09:00 | 2298.51 | 18.19 | 78.50 | 327.67 | 1251.55 | 19.86 | 51.83 | 285.00 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-08:09 | 2291.03 | 16.52 | 50.83 | 361.67 | 957.81 | 17.82 | 0.00 | 322.50 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-07:30 | 2393.29 | 14.16 | 1.67 | 363.83 | 1014.37 | 17.77 | 0.00 | 327.50 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-07:30 | 2376.67 | 16.51 | 52.00 | 364.83 | 991.69 | 17.81 | 0.00 | 323.67 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:40 | 2340.39 | 18.88 | 86.50 | 351.00 | 996.61 | 18.53 | 7.83 | 313.83 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-08:20 | 2062.83 | 19.38 | 75.50 | 301.00 | 1097.58 | 22.09 | 62.67 | 252.00 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-10:39 | 2289.69 | 20.47 | 92.50 | 260.00 | 856.33 | 19.84 | 42.83 | 206.00 |
November | 299.00 | 0.53 | 0.48 | 01-NOV-09:50 | 1545.81 | 19.04 | 80.83 | 245.67 | 820.10 | 21.63 | 68.00 | 196.00 |
December | 285.17 | 0.52 | 0.48 | 01-DEC-09:30 | 1349.22 | 18.93 | 73.67 | 233.33 | 723.43 | 21.22 | 63.00 | 173.00 |
Annual Sum or Average | 4071.00 | 0.51 | 2071.20 | 18.13 | 822.50 | 3567.50 | 976.46 | 19.77 | 476.33 | 3009.50 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1349.22 | 14.16 | 1.67 | 211.33 | 723.43 | 17.77 | 0.00 | 161.83 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 2393.29 | 20.73 | 92.50 | 364.83 | 1251.55 | 22.09 | 72.17 | 327.50 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.191128E+09 | 20535.64 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3355806.85 | 20535.64 | 13-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194484E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.191128E+09 | 20535.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.454399E+10 | 10684.12 | 19-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.288572E+10 | 10676.56 | 11-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111481E+10 | 10642.16 | 24-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.614611E+09 | 10656.55 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.162111E+09 | 10594.61 | 11-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22165751.06 | 8111.57 | 08-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21108758.98 | 5949.51 | 14-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.524343E+09 | 10693.27 | 20-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102912E+10 | 10672.43 | 28-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184723E+10 | 10652.33 | 14-DEC-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.454399E+10 | 10693.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.173101E+10 | 8524.18 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.879348E+09 | 8524.18 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 67862375.16 | 7917.27 | 18-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9152208.53 | 8524.18 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3396807.89 | 2541.58 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 32091712.55 | 8524.18 | 21-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.433211E+09 | 8524.18 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.315608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.173101E+10 | 8524.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.342291E+10 | 9086.43 | 02-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.190802E+10 | 9110.16 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261553E+09 | 9055.98 | 24-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 54524546.11 | 9013.50 | 27-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6405245.64 | 5439.45 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157986E+09 | 9042.19 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116202E+10 | 9064.76 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.697342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.342291E+10 | 9110.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.181351E+10 | 8598.01 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.963550E+09 | 8598.01 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 82824609.09 | 7784.16 | 23-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11774442.02 | 8598.01 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2242435.63 | 2359.20 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 52462225.69 | 8598.01 | 21-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.531664E+09 | 8598.01 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.345803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.181351E+10 | 8598.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.267572E+10 | 21482.45 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109834E+10 | 21482.45 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7872784.21 | 7257.97 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.581050E+09 | 21482.45 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.436299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.267572E+10 | 21482.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.203204E+10 | 11626.80 | 02-JAN-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107829E+10 | 11578.39 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 83214300.19 | 11539.01 | 22-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16509376.94 | 11490.77 | 07-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35238114.48 | 11575.08 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152028E+09 | 11551.50 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.740147E+09 | 11597.72 | 26-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.413746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.203204E+10 | 11626.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.172572E+10 | 9018.62 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.865236E+09 | 9018.62 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 55572916.23 | 7889.51 | 18-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7373139.76 | 9018.62 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 28590489.60 | 7884.80 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141514E+09 | 9018.62 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.679836E+09 | 9018.62 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.350385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.172572E+10 | 9018.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.342095E+10 | 9821.66 | 02-JAN-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182211E+10 | 9796.77 | 02-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145611E+09 | 9747.65 | 22-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19879983.88 | 9706.89 | 07-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 49699875.01 | 9783.40 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.375553E+09 | 9784.77 | 01-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159534E+10 | 9815.52 | 26-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.742914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.342095E+10 | 9821.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.192774E+10 | 9093.24 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101309E+10 | 9093.24 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 75772279.59 | 7807.18 | 23-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10986909.34 | 9093.24 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 28528753.64 | 7741.65 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.203486E+09 | 9093.24 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.866015E+09 | 9093.24 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.412562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.192774E+10 | 9093.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.654053E+10 | 35253.03 | 02-JAN-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.326954E+10 | 35228.22 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138727E+09 | 34958.88 | 23-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8390864.12 | 12930.26 | 07-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 91117887.94 | 35172.28 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.632680E+09 | 35156.95 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.339468E+10 | 35295.33 | 26-DEC-06:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.654053E+10 | 35295.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.356918E+10 | 13202.64 | 18-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212004E+10 | 13204.59 | 08-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.334032E+09 | 13090.23 | 22-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97758260.25 | 13048.43 | 07-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2574520.95 | 2025.63 | 11-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.204582E+09 | 13154.59 | 30-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.596007E+09 | 13138.60 | 25-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174850E+10 | 13161.62 | 01-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.867267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.356918E+10 | 13204.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.299492E+10 | 10894.46 | 19-JAN-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167282E+10 | 10881.73 | 11-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207924E+09 | 10827.70 | 22-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40956137.03 | 10787.87 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156585E+09 | 10880.99 | 30-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.480090E+09 | 10868.00 | 25-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152800E+10 | 10874.83 | 22-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.708130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.299492E+10 | 10894.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.549032E+10 | 11380.77 | 18-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.320647E+10 | 11463.14 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.497612E+09 | 11366.03 | 24-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.114891E+09 | 11303.32 | 26-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 585925.51 | 1224.39 | 11-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.296350E+09 | 11373.61 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109760E+10 | 11377.73 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.309873E+10 | 11399.40 | 12-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.549032E+10 | 11463.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.319065E+10 | 11444.89 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185399E+10 | 11444.89 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.277623E+09 | 11444.89 | 18-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 64677937.69 | 11444.89 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 798541.55 | 757.21 | 11-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166840E+09 | 11444.89 | 26-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.623288E+09 | 11444.89 | 14-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177894E+10 | 11444.89 | 01-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.795681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.319065E+10 | 11444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.482381E+10 | 14672.47 | 14-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.232353E+10 | 17044.26 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147134E+09 | 4281.88 | 18-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 48341720.45 | 4987.31 | 06-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18680839.98 | 4115.29 | 26-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.384545E+09 | 9689.92 | 22-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114420E+10 | 13018.73 | 18-DEC-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.889025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.482381E+10 | 17044.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.500216E+10 | 14781.80 | 14-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.251852E+10 | 17158.29 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.270647E+09 | 4726.35 | 18-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82456000.02 | 5477.41 | 06-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 41967836.01 | 4832.75 | 26-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.633237E+09 | 10371.28 | 22-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141122E+10 | 13426.01 | 18-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.996021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.500216E+10 | 17158.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.530554E+10 | 16841.96 | 27-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.272456E+10 | 18430.14 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384860E+09 | 5850.26 | 18-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123287E+09 | 7085.98 | 06-APR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86970678.97 | 6217.42 | 26-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.828397E+09 | 12863.12 | 22-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165055E+10 | 14651.35 | 18-DEC-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.530554E+10 | 18430.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.169693E+10 | 0.103826E+10 | 17291.69 | 19-JAN-22:00 | 9268.72 | 0.00 |
February | 0.00 | 0.00 | 0.438401E+10 | 0.358988E+10 | 30310.42 | 28-FEB-14:00 | 30310.42 | 0.00 |
March | 0.00 | 0.00 | 0.142343E+11 | 0.110387E+11 | 48406.90 | 30-MAR-15:20 | 48406.90 | 0.00 |
April | 0.00 | 0.00 | 0.240395E+11 | 0.195729E+11 | 52074.40 | 17-APR-14:50 | 52074.40 | 0.00 |
May | 0.00 | 0.00 | 0.467797E+11 | 0.351982E+11 | 69091.25 | 30-MAY-11:50 | 53063.69 | 0.00 |
June | 0.00 | 0.00 | 0.718038E+11 | 0.533718E+11 | 81549.77 | 27-JUN-12:00 | 54240.13 | 0.00 |
July | 0.00 | 0.00 | 0.826753E+11 | 0.581133E+11 | 91364.53 | 06-JUL-06:03 | 61088.67 | 0.00 |
August | 0.00 | 0.00 | 0.947050E+11 | 0.652210E+11 | 103610.67 | 21-AUG-05:12 | 77617.94 | 0.00 |
September | 0.00 | 0.00 | 0.599638E+11 | 0.438694E+11 | 85688.77 | 06-SEP-12:03 | 59740.87 | 0.00 |
October | 0.00 | 0.00 | 0.264362E+11 | 0.194476E+11 | 67127.48 | 10-OCT-15:50 | 55181.67 | 0.00 |
November | 0.00 | 0.00 | 0.100977E+11 | 0.766644E+10 | 33880.38 | 02-NOV-13:00 | 26505.85 | 0.00 |
December | 0.00 | 0.00 | 0.351680E+10 | 0.226456E+10 | 30975.63 | 12-DEC-14:00 | 23596.29 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.440333E+12 | 0.320392E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.169693E+10 | 0.103826E+10 | 17291.69 | 9268.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.947050E+11 | 0.652210E+11 | 103610.67 | 77617.94 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.158728E+10 | 0.967346E+09 | 16705.15 | 19-JAN-16:00 | 8457.25 | 0.00 |
February | 0.00 | 0.00 | 0.409099E+10 | 0.334604E+10 | 27359.41 | 28-FEB-15:05 | 27359.41 | 0.00 |
March | 0.00 | 0.00 | 0.125215E+11 | 0.963535E+10 | 47803.38 | 30-MAR-15:20 | 47803.38 | 0.00 |
April | 0.00 | 0.00 | 0.226273E+11 | 0.185202E+11 | 53159.48 | 17-APR-15:30 | 53159.48 | 0.00 |
May | 0.00 | 0.00 | 0.432382E+11 | 0.325840E+11 | 65525.89 | 30-MAY-14:05 | 52713.51 | 0.00 |
June | 0.00 | 0.00 | 0.657545E+11 | 0.480524E+11 | 89340.57 | 26-JUN-06:03 | 65877.06 | 0.00 |
July | 0.00 | 0.00 | 0.756439E+11 | 0.518482E+11 | 81278.42 | 06-JUL-06:03 | 53141.42 | 0.00 |
August | 0.00 | 0.00 | 0.846260E+11 | 0.562160E+11 | 102559.79 | 21-AUG-05:12 | 67233.34 | 0.00 |
September | 0.00 | 0.00 | 0.504734E+11 | 0.355598E+11 | 77838.52 | 06-SEP-14:05 | 55492.32 | 0.00 |
October | 0.00 | 0.00 | 0.215511E+11 | 0.153257E+11 | 60930.39 | 11-OCT-14:05 | 45395.35 | 0.00 |
November | 0.00 | 0.00 | 0.823031E+10 | 0.599037E+10 | 26906.26 | 02-NOV-14:05 | 20172.46 | 0.00 |
December | 0.00 | 0.00 | 0.294560E+10 | 0.188711E+10 | 25320.24 | 12-DEC-14:00 | 17786.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.393290E+12 | 0.279932E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.158728E+10 | 0.967346E+09 | 16705.15 | 8457.25 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.846260E+11 | 0.562160E+11 | 102559.79 | 67233.34 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.164725E+10 | 0.994962E+09 | 16908.16 | 19-JAN-16:00 | 8541.12 | 0.00 |
February | 0.00 | 0.00 | 0.422118E+10 | 0.339745E+10 | 26241.94 | 28-FEB-15:30 | 26241.94 | 0.00 |
March | 0.00 | 0.00 | 0.131092E+11 | 0.998532E+10 | 53557.79 | 30-MAR-15:20 | 53557.79 | 0.00 |
April | 0.00 | 0.00 | 0.244009E+11 | 0.199205E+11 | 59885.04 | 17-APR-16:00 | 59885.04 | 0.00 |
May | 0.00 | 0.00 | 0.468896E+11 | 0.357362E+11 | 73796.93 | 30-MAY-15:00 | 60360.81 | 0.00 |
June | 0.00 | 0.00 | 0.709506E+11 | 0.527854E+11 | 89779.87 | 26-JUN-06:03 | 67024.29 | 0.00 |
July | 0.00 | 0.00 | 0.811768E+11 | 0.569859E+11 | 88293.04 | 07-JUL-16:00 | 70114.64 | 0.00 |
August | 0.00 | 0.00 | 0.899362E+11 | 0.610800E+11 | 89112.26 | 21-AUG-05:12 | 57950.18 | 0.00 |
September | 0.00 | 0.00 | 0.522279E+11 | 0.368162E+11 | 84309.34 | 06-SEP-14:00 | 62064.40 | 0.00 |
October | 0.00 | 0.00 | 0.217913E+11 | 0.152454E+11 | 64277.28 | 10-OCT-14:00 | 50592.90 | 0.00 |
November | 0.00 | 0.00 | 0.832019E+10 | 0.591448E+10 | 27293.32 | 02-NOV-14:30 | 19530.77 | 0.00 |
December | 0.00 | 0.00 | 0.303008E+10 | 0.192175E+10 | 26675.89 | 12-DEC-14:00 | 18301.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.417701E+12 | 0.300783E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.164725E+10 | 0.994962E+09 | 16908.16 | 8541.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.899362E+11 | 0.610800E+11 | 89779.87 | 70114.64 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1748.37 | 6089.06 | 30-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1761.51 | 6098.89 | 01-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1818.64 | 5967.10 | 02-MAR-12:17 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1599.79 | 5639.94 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1537.04 | 5290.57 | 01-MAY-11:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1461.80 | 4839.56 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1280.74 | 4516.27 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1401.21 | 4498.90 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1366.98 | 4786.70 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1466.10 | 5238.80 | 31-OCT-11:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1606.48 | 5612.18 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1642.51 | 5936.35 | 27-DEC-12:10 |
Annual Sum or Average | 0.00 | 1556.46 | ||||
Minimum of Months | 0.00 | 0.00 | 1280.74 | 4498.90 | ||
Maximum of Months | 0.00 | 0.00 | 1818.64 | 6098.89 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.108084E+10 | 0.30 | 2334.24 | 02-JAN-06:11 | 0.76 |
February | 0.104584E+10 | 0.31 | 2334.24 | 13-FEB-07:01 | 0.76 |
March | 0.142298E+10 | 0.32 | 2360.60 | 30-MAR-16:00 | 0.76 |
April | 0.152682E+10 | 0.31 | 2570.53 | 17-APR-15:50 | 0.80 |
May | 0.208080E+10 | 0.35 | 3876.84 | 22-MAY-06:03 | 1.00 |
June | 0.301893E+10 | 0.43 | 8061.66 | 26-JUN-06:03 | 1.57 |
July | 0.335779E+10 | 0.44 | 9741.15 | 17-JUL-06:03 | 1.77 |
August | 0.387628E+10 | 0.48 | 10377.54 | 07-AUG-06:03 | 1.85 |
September | 0.278958E+10 | 0.40 | 8935.18 | 05-SEP-06:03 | 1.68 |
October | 0.188028E+10 | 0.33 | 3876.84 | 10-OCT-06:02 | 1.00 |
November | 0.132819E+10 | 0.30 | 2162.45 | 06-NOV-16:10 | 0.73 |
December | 0.110449E+10 | 0.29 | 1364.30 | 15-DEC-08:04 | 0.59 |
Annual Sum or Average | 0.245128E+11 | 0.35 | |||
Minimum of Months | 0.104584E+10 | 0.29 | 1364.30 | 0.59 | |
Maximum of Months | 0.387628E+10 | 0.48 | 10377.54 | 1.85 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.101442E+10 | 0.29 | 2184.25 | 02-JAN-06:11 | 0.79 |
February | 0.965034E+09 | 0.30 | 2184.25 | 03-FEB-07:01 | 0.79 |
March | 0.119840E+10 | 0.31 | 2658.75 | 30-MAR-16:00 | 0.87 |
April | 0.136373E+10 | 0.31 | 2850.41 | 17-APR-15:50 | 0.91 |
May | 0.189762E+10 | 0.36 | 3849.87 | 30-MAY-14:05 | 1.08 |
June | 0.260767E+10 | 0.42 | 9058.61 | 26-JUN-05:12 | 1.84 |
July | 0.282481E+10 | 0.42 | 9058.61 | 17-JUL-06:03 | 1.85 |
August | 0.310815E+10 | 0.45 | 9058.61 | 07-AUG-06:03 | 1.85 |
September | 0.207094E+10 | 0.37 | 5469.21 | 05-SEP-06:03 | 1.34 |
October | 0.138870E+10 | 0.31 | 3164.60 | 11-OCT-14:05 | 0.96 |
November | 0.101709E+10 | 0.29 | 1681.75 | 06-NOV-15:05 | 0.69 |
December | 0.970945E+09 | 0.28 | 2184.25 | 04-DEC-06:01 | 0.79 |
Annual Sum or Average | 0.204275E+11 | 0.34 | |||
Minimum of Months | 0.965034E+09 | 0.28 | 1681.75 | 0.69 | |
Maximum of Months | 0.310815E+10 | 0.45 | 9058.61 | 1.85 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132656E+10 | 0.36 | 2203.59 | 02-JAN-06:11 | 0.73 |
February | 0.115496E+10 | 0.35 | 2203.59 | 01-FEB-07:02 | 0.73 |
March | 0.128056E+10 | 0.33 | 2806.16 | 30-MAR-16:00 | 0.82 |
April | 0.141780E+10 | 0.33 | 3061.45 | 17-APR-15:40 | 0.87 |
May | 0.194833E+10 | 0.36 | 3863.11 | 30-MAY-15:00 | 0.99 |
June | 0.264388E+10 | 0.41 | 7824.69 | 26-JUN-06:03 | 1.52 |
July | 0.286281E+10 | 0.41 | 7446.96 | 17-JUL-06:03 | 1.47 |
August | 0.309390E+10 | 0.43 | 7172.39 | 07-AUG-06:03 | 1.44 |
September | 0.197795E+10 | 0.36 | 4205.11 | 07-SEP-15:30 | 1.04 |
October | 0.136459E+10 | 0.32 | 2913.51 | 11-OCT-15:20 | 0.84 |
November | 0.110667E+10 | 0.32 | 2203.59 | 21-NOV-06:01 | 0.73 |
December | 0.116574E+10 | 0.33 | 2203.59 | 01-DEC-06:01 | 0.73 |
Annual Sum or Average | 0.213438E+11 | 0.36 | |||
Minimum of Months | 0.110667E+10 | 0.32 | 2203.59 | 0.73 | |
Maximum of Months | 0.309390E+10 | 0.43 | 7824.69 | 1.52 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 57.83 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 55.82 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 55.95 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 55.59 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 56.77 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.70 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 56.26 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 56.45 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 56.90 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.00 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 56.05 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:01 | 2.06 | 2.06 | 55.93 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 55.59 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.00 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.20 | 57.20 | 1748.37 | 6089.06 | 30-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.18 | 56.18 | 1761.51 | 6098.89 | 01-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.44 | 56.44 | 1818.64 | 5967.10 | 02-MAR-12:17 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.10 | 56.10 | 1599.79 | 5639.94 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.18 | 57.18 | 1537.04 | 5290.57 | 01-MAY-11:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.86 | 57.86 | 1461.80 | 4839.56 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.54 | 56.54 | 1280.74 | 4516.27 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.91 | 56.91 | 1401.21 | 4498.90 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.18 | 57.18 | 1366.98 | 4786.70 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.03 | 56.03 | 1466.10 | 5238.80 | 31-OCT-11:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.48 | 56.48 | 1606.48 | 5612.18 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.28 | 56.28 | 1642.51 | 5936.35 | 27-DEC-12:10 |
Annual Sum or Average | 0.00 | 1556.46 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.03 | 56.03 | 1280.74 | 4498.90 | ||
Maximum of Months | 0.00 | 0.00 | 57.86 | 57.86 | 1818.64 | 6098.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.132411E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.885702E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.657138E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.826644E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.137936E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.214579E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.247824E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.281365E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.175416E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.890980E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.519801E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.599210E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.162748E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.519801E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.281365E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.132233E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.793729E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.476699E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.711660E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.125934E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.194379E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.223445E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.246783E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.145153E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.686681E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.404484E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.621045E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.143736E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.404484E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.246783E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.235586E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.144162E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.612264E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.792473E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.136366E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.209124E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.239611E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.261622E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.149681E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.773086E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.673218E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.135203E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.179646E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.612264E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.261622E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.108084E+10 | 0.169693E+10 | 0.165264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104584E+10 | 0.438401E+10 | 0.896352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142298E+10 | 0.142343E+11 | 0.167418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152682E+10 | 0.240395E+11 | 0.738404E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.208080E+10 | 0.467797E+11 | 0.162111E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.301893E+10 | 0.718038E+11 | 22165751.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.335779E+10 | 0.826753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.387628E+10 | 0.947050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.278958E+10 | 0.599638E+11 | 21108758.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.188028E+10 | 0.264362E+11 | 0.555068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132819E+10 | 0.100977E+11 | 0.165621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110449E+10 | 0.351680E+10 | 0.511832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.245128E+11 | 0.440333E+12 | 0.354375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.104584E+10 | 0.169693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.387628E+10 | 0.947050E+11 | 0.165264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.101442E+10 | 0.158728E+10 | 0.167843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.965034E+09 | 0.409099E+10 | 0.839558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119840E+10 | 0.125215E+11 | 0.630817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136373E+10 | 0.226273E+11 | 0.137205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.189762E+10 | 0.432382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.260767E+10 | 0.657545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.282481E+10 | 0.756439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.310815E+10 | 0.846260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.207094E+10 | 0.504734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138870E+10 | 0.215511E+11 | 0.184025E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101709E+10 | 0.823031E+10 | 0.151369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.970945E+09 | 0.294560E+10 | 0.587362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204275E+11 | 0.393290E+12 | 0.335193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.965034E+09 | 0.158728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.310815E+10 | 0.846260E+11 | 0.167843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.132656E+10 | 0.164725E+10 | 0.270911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115496E+10 | 0.422118E+10 | 0.148474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128056E+10 | 0.131092E+11 | 0.184078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141780E+10 | 0.244009E+11 | 0.449961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.194833E+10 | 0.468896E+11 | 3958988.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.264388E+10 | 0.709506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.286281E+10 | 0.811768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.309390E+10 | 0.899362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.197795E+10 | 0.522279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136459E+10 | 0.217913E+11 | 0.100245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110667E+10 | 0.832019E+10 | 0.425806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116574E+10 | 0.303008E+10 | 0.131994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213438E+11 | 0.417701E+12 | 0.626932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110667E+10 | 0.164725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.309390E+10 | 0.899362E+11 | 0.270911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.108084E+10 | 0.00 | 0.00 | 0.00 | 0.457721E+09 | 0.117026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104584E+10 | 0.00 | 0.00 | 0.00 | 0.117119E+10 | 0.663999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142298E+10 | 0.00 | 0.00 | 0.00 | 0.362135E+10 | 0.152705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152682E+10 | 0.00 | 0.00 | 0.00 | 0.604956E+10 | 0.690062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.208080E+10 | 0.00 | 0.00 | 0.00 | 0.115507E+11 | 0.162111E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.301893E+10 | 0.00 | 0.00 | 0.00 | 0.184168E+11 | 22165751.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.335779E+10 | 0.00 | 0.00 | 0.00 | 0.214246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.387628E+10 | 0.00 | 0.00 | 0.00 | 0.242602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.278958E+10 | 0.00 | 0.00 | 0.00 | 0.147309E+11 | 21108758.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.188028E+10 | 0.00 | 0.00 | 0.00 | 0.649314E+10 | 0.536387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132819E+10 | 0.00 | 0.00 | 0.00 | 0.259816E+10 | 0.127166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110449E+10 | 0.00 | 0.00 | 0.00 | 0.913488E+09 | 0.397412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.245128E+11 | 0.00 | 0.00 | 0.00 | 0.111688E+12 | 0.265472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.104584E+10 | 0.00 | 0.00 | 0.00 | 0.457721E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.387628E+10 | 0.00 | 0.00 | 0.00 | 0.242602E+11 | 0.117026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.101442E+10 | 0.00 | 0.00 | 0.00 | 0.426735E+09 | 0.117822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.965034E+09 | 0.00 | 0.00 | 0.00 | 0.109519E+10 | 0.587706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119840E+10 | 0.00 | 0.00 | 0.00 | 0.320842E+10 | 0.360171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136373E+10 | 0.00 | 0.00 | 0.00 | 0.569812E+10 | 54749409.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.189762E+10 | 0.00 | 0.00 | 0.00 | 0.106957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.260767E+10 | 0.00 | 0.00 | 0.00 | 0.168302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.282481E+10 | 0.00 | 0.00 | 0.00 | 0.195197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.310815E+10 | 0.00 | 0.00 | 0.00 | 0.215702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.207094E+10 | 0.00 | 0.00 | 0.00 | 0.124443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138870E+10 | 0.00 | 0.00 | 0.00 | 0.533605E+10 | 0.142057E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101709E+10 | 0.00 | 0.00 | 0.00 | 0.214729E+10 | 0.880453E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.970945E+09 | 0.00 | 0.00 | 0.00 | 0.777115E+09 | 0.446239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204275E+11 | 0.00 | 0.00 | 0.00 | 0.997491E+11 | 0.235591E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.965034E+09 | 0.00 | 0.00 | 0.00 | 0.426735E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.310815E+10 | 0.00 | 0.00 | 0.00 | 0.215702E+11 | 0.117822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.132656E+10 | 0.00 | 0.00 | 0.00 | 0.446479E+09 | 0.217856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115496E+10 | 0.00 | 0.00 | 0.00 | 0.113839E+10 | 0.121229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128056E+10 | 0.00 | 0.00 | 0.00 | 0.338616E+10 | 0.145592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141780E+10 | 0.00 | 0.00 | 0.00 | 0.618025E+10 | 0.326674E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.194833E+10 | 0.00 | 0.00 | 0.00 | 0.116843E+11 | 3958988.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.264388E+10 | 0.00 | 0.00 | 0.00 | 0.182686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.286281E+10 | 0.00 | 0.00 | 0.00 | 0.210983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.309390E+10 | 0.00 | 0.00 | 0.00 | 0.230683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.197795E+10 | 0.00 | 0.00 | 0.00 | 0.129902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136459E+10 | 0.00 | 0.00 | 0.00 | 0.545079E+10 | 0.915475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110667E+10 | 0.00 | 0.00 | 0.00 | 0.219585E+10 | 0.342967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116574E+10 | 0.00 | 0.00 | 0.00 | 0.805723E+09 | 0.115488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213438E+11 | 0.00 | 0.00 | 0.00 | 0.106713E+12 | 0.515890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110667E+10 | 0.00 | 0.00 | 0.00 | 0.446479E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.309390E+10 | 0.00 | 0.00 | 0.00 | 0.230683E+11 | 0.217856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.950838E+10 | 0.00 | 0.00 | 5855576.40 | 7352933.33 | 70130997.23 | 0.360365E+10 | 0.00 | 0.33 |
February | 0.538369E+10 | 0.00 | 0.00 | 12459468.02 | 0.00 | 1200560.32 | 0.600680E+10 | 0.00 | 0.42 |
March | 0.171332E+10 | 0.255557E+09 | 0.00 | 28314880.57 | 35655100.52 | 0.00 | 0.109580E+11 | 0.00 | 0.60 |
April | 0.637030E+09 | 0.493186E+09 | 0.00 | 28294431.45 | 41421150.73 | 0.00 | 0.746100E+10 | 0.00 | 0.62 |
May | 0.221223E+09 | 0.280136E+10 | 0.00 | 13844038.45 | 53657352.95 | 0.00 | 0.260559E+10 | 0.00 | 0.52 |
June | 61521696.05 | 0.808495E+10 | 0.00 | 6531503.65 | 74376037.29 | 0.00 | 0.122386E+10 | 0.00 | 0.41 |
July | 0.00 | 0.104944E+11 | 0.00 | 0.00 | 0.194175E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 1325917.41 | 0.125704E+11 | 0.00 | 309771.14 | 0.146062E+09 | 0.00 | 11393313.97 | 0.00 | 0.30 |
September | 71409169.48 | 0.509043E+10 | 0.00 | 14300342.59 | 0.101244E+09 | 0.00 | 0.189473E+10 | 0.00 | 0.48 |
October | 0.627860E+09 | 0.154971E+10 | 0.00 | 29103926.71 | 7828059.37 | 0.00 | 0.107572E+11 | 0.00 | 0.60 |
November | 0.171025E+10 | 0.126802E+09 | 0.00 | 28913720.27 | 62756701.20 | 0.00 | 0.119023E+11 | 0.00 | 0.57 |
December | 0.504892E+10 | 12250648.85 | 0.00 | 16082208.63 | 0.00 | 0.00 | 0.756228E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.249849E+11 | 0.414790E+11 | 0.00 | 0.184010E+09 | 0.724528E+09 | 71331557.54 | 0.639867E+11 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.950838E+10 | 0.125704E+11 | 0.00 | 29103926.71 | 0.194175E+09 | 70130997.23 | 0.119023E+11 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.113756E+11 | 0.00 | 0.00 | 0.00 | 14750764.39 | 0.108803E+10 | 0.00 | 0.00 | 0.32 |
February | 0.939428E+10 | 0.00 | 0.00 | 700770.71 | 1967372.34 | 0.221411E+09 | 0.333615E+09 | 0.00 | 0.37 |
March | 0.624576E+10 | 84429137.37 | 0.00 | 5825950.83 | 0.135483E+09 | 0.00 | 0.296246E+10 | 0.00 | 0.44 |
April | 0.254188E+10 | 0.215689E+09 | 0.00 | 10587868.85 | 0.190034E+09 | 0.00 | 0.317498E+10 | 0.00 | 0.45 |
May | 0.616763E+09 | 0.192508E+10 | 0.00 | 6887261.75 | 0.141508E+09 | 0.00 | 0.142162E+10 | 0.00 | 0.37 |
June | 0.202576E+09 | 0.674127E+10 | 0.00 | 3639847.32 | 86925195.07 | 0.00 | 0.726123E+09 | 0.00 | 0.32 |
July | 859406.19 | 0.887429E+10 | 0.00 | 37176.34 | 0.332468E+09 | 0.00 | 187928.18 | 0.00 | 0.24 |
August | 7783693.92 | 0.111135E+11 | 0.00 | 203043.22 | 0.145216E+09 | 0.00 | 8903481.38 | 0.00 | 0.27 |
September | 0.295419E+09 | 0.427266E+10 | 0.00 | 6955128.06 | 0.244144E+09 | 0.00 | 0.976744E+09 | 0.00 | 0.36 |
October | 0.377579E+10 | 0.122982E+10 | 0.00 | 7909111.34 | 28865504.16 | 0.00 | 0.351802E+10 | 0.00 | 0.41 |
November | 0.728217E+10 | 18618242.48 | 0.00 | 2752710.98 | 0.201817E+09 | 1308896.45 | 0.183703E+10 | 0.00 | 0.39 |
December | 0.987652E+10 | 9904508.26 | 0.00 | 266549.90 | 15002346.76 | 0.158097E+09 | 0.253886E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.516154E+11 | 0.344853E+11 | 0.00 | 45765419.29 | 0.153818E+10 | 0.146885E+10 | 0.152136E+11 | 0.00 | 0.36 |
Minimum of Months | 859406.19 | 0.00 | 0.00 | 0.00 | 1967372.34 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.113756E+11 | 0.111135E+11 | 0.00 | 10587868.85 | 0.332468E+09 | 0.108803E+10 | 0.351802E+10 | 0.00 | 0.45 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.869190E+10 | 0.00 | 0.00 | 0.00 | 15035614.84 | 0.317231E+10 | 0.00 | 0.00 | 0.32 |
February | 0.771797E+10 | 0.00 | 0.00 | 400518.11 | 5138624.88 | 0.134102E+10 | 0.226177E+09 | 0.00 | 0.36 |
March | 0.700167E+10 | 96149249.90 | 0.00 | 3124832.46 | 0.131382E+09 | 20702441.80 | 0.152239E+10 | 0.00 | 0.43 |
April | 0.285082E+10 | 0.194440E+09 | 0.00 | 9751525.87 | 0.166071E+09 | 685643.05 | 0.237775E+10 | 0.00 | 0.46 |
May | 0.620810E+09 | 0.177217E+10 | 0.00 | 5705595.20 | 0.176551E+09 | 0.00 | 0.113052E+10 | 0.00 | 0.37 |
June | 0.288439E+09 | 0.653350E+10 | 0.00 | 3035021.50 | 82665034.81 | 0.00 | 0.546217E+09 | 0.00 | 0.32 |
July | 0.00 | 0.864885E+10 | 0.00 | 0.00 | 0.363672E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 7247474.40 | 0.108863E+11 | 0.00 | 48678.79 | 0.134072E+09 | 0.00 | 3657507.38 | 0.00 | 0.27 |
September | 0.369931E+09 | 0.403160E+10 | 0.00 | 5525170.76 | 0.509605E+09 | 0.00 | 0.631676E+09 | 0.00 | 0.35 |
October | 0.450095E+10 | 0.114832E+10 | 0.00 | 3732029.68 | 99618058.65 | 14466811.64 | 0.183884E+10 | 0.00 | 0.40 |
November | 0.754504E+10 | 10861872.93 | 3004060.68 | 731736.76 | 0.228332E+09 | 0.159878E+09 | 0.535706E+09 | 42040.82 | 0.38 |
December | 0.856177E+10 | 774140.27 | 0.00 | 62705.66 | 37649951.02 | 0.104866E+10 | 9589477.22 | 0.00 | 0.34 |
Annual Sum or Average | 0.481565E+11 | 0.333230E+11 | 3004060.68 | 32117814.79 | 0.194979E+10 | 0.575772E+10 | 0.882251E+10 | 42040.82 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5138624.88 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.869190E+10 | 0.108863E+11 | 3004060.68 | 9751525.87 | 0.509605E+09 | 0.317231E+10 | 0.237775E+10 | 42040.82 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.424454E+09 | 0.00 | 0.00 | 0.00 | 3167633.25 | 0.243220E+10 | 0.00 | 0.00 | 0.35 |
February | 0.743782E+09 | 0.00 | 285249.67 | 86888.21 | 795710.87 | 0.135515E+10 | 20404945.94 | 1621.01 | 0.38 |
March | 0.142021E+10 | 24160972.20 | 0.00 | 500741.40 | 26021852.20 | 0.234832E+09 | 0.147326E+09 | 0.00 | 0.44 |
April | 0.747460E+09 | 67746479.85 | 0.00 | 1943677.22 | 18349954.72 | 48602095.85 | 0.316857E+09 | 0.00 | 0.49 |
May | 0.182237E+09 | 0.520625E+09 | 0.00 | 1185291.69 | 31975922.38 | 0.00 | 0.202593E+09 | 0.00 | 0.44 |
June | 66633171.15 | 0.215093E+10 | 0.00 | 805171.32 | 19667470.70 | 0.00 | 0.125378E+09 | 0.00 | 0.45 |
July | 0.00 | 0.290041E+10 | 0.00 | 0.00 | 51514146.63 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 2081205.71 | 0.342698E+10 | 0.00 | 882.05 | 31937508.79 | 0.00 | 78469.52 | 0.00 | 0.38 |
September | 0.106786E+09 | 0.110385E+10 | 0.00 | 1124386.33 | 85181137.66 | 0.00 | 0.115216E+09 | 0.00 | 0.40 |
October | 0.104515E+10 | 0.275235E+09 | 0.00 | 389722.11 | 25663843.87 | 0.118749E+09 | 0.157553E+09 | 0.00 | 0.40 |
November | 0.126153E+10 | 2333137.10 | 3745046.30 | 36812.07 | 45048383.92 | 0.483678E+09 | 18303985.46 | 14664.75 | 0.39 |
December | 0.808443E+09 | 0.00 | 0.00 | 0.00 | 8095008.45 | 0.135814E+10 | 0.00 | 0.00 | 0.36 |
Annual Sum or Average | 0.680877E+10 | 0.104723E+11 | 4030295.97 | 6073572.41 | 0.347419E+09 | 0.603135E+10 | 0.110371E+10 | 16285.75 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 795710.87 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.142021E+10 | 0.342698E+10 | 3745046.30 | 1943677.22 | 85181137.66 | 0.243220E+10 | 0.316857E+09 | 14664.75 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.540461E+09 | 0.00 | 0.00 | 0.00 | 2015754.90 | 0.123617E+10 | 0.00 | 0.00 | 0.35 |
February | 0.549538E+09 | 0.00 | 181210.83 | 327149.41 | 506358.52 | 0.664994E+09 | 0.124661E+09 | 1342.17 | 0.39 |
March | 0.693901E+09 | 25187513.86 | 0.00 | 1362366.55 | 10002507.13 | 92908264.36 | 0.466819E+09 | 0.00 | 0.50 |
April | 0.293777E+09 | 57438900.70 | 0.00 | 3217010.94 | 6114197.56 | 17245395.25 | 0.647124E+09 | 0.00 | 0.71 |
May | 78360482.95 | 0.500172E+09 | 0.00 | 1655308.52 | 15291559.43 | 0.00 | 0.300814E+09 | 0.00 | 0.64 |
June | 30214298.87 | 0.181269E+10 | 0.00 | 1065485.03 | 9679985.40 | 0.00 | 0.185134E+09 | 0.00 | 0.64 |
July | 0.00 | 0.253956E+10 | 0.00 | 0.00 | 31108739.61 | 0.00 | 0.00 | 0.00 | 0.49 |
August | 1306457.93 | 0.289782E+10 | 0.00 | 701.92 | 17759015.98 | 0.00 | 67732.25 | 0.00 | 0.52 |
September | 59292378.83 | 0.103283E+10 | 0.00 | 1379386.54 | 38703506.97 | 0.00 | 0.145968E+09 | 0.00 | 0.58 |
October | 0.505262E+09 | 0.234490E+09 | 0.00 | 1178239.94 | 9308028.85 | 64172747.23 | 0.458191E+09 | 0.00 | 0.50 |
November | 0.806241E+09 | 2268498.87 | 2171116.09 | 267629.46 | 28473644.78 | 0.201750E+09 | 0.120142E+09 | 7962.31 | 0.39 |
December | 0.738658E+09 | 526989.73 | 0.00 | 7121.08 | 4624349.35 | 0.616146E+09 | 1610835.88 | 0.00 | 0.36 |
Annual Sum or Average | 0.429701E+10 | 0.910299E+10 | 2352326.92 | 10460399.39 | 0.173588E+09 | 0.289339E+10 | 0.245053E+10 | 9304.48 | 0.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 506358.52 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.806241E+09 | 0.289782E+10 | 2171116.09 | 3217010.94 | 38703506.97 | 0.123617E+10 | 0.647124E+09 | 7962.31 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.866200E+09 | 0.00 | 0.00 | 945743.01 | 3171855.70 | 0.145910E+10 | 0.578970E+09 | 0.00 | 0.36 |
February | 0.829572E+09 | 0.00 | 286471.33 | 2000115.77 | 796771.55 | 0.834963E+09 | 0.733443E+09 | 781.74 | 0.48 |
March | 0.101844E+10 | 60096833.47 | 0.00 | 3704987.27 | 11468741.87 | 0.162809E+09 | 0.116206E+10 | 0.00 | 0.62 |
April | 0.559722E+09 | 88232321.19 | 0.00 | 4232184.61 | 12474610.53 | 43227835.04 | 0.804434E+09 | 0.00 | 0.66 |
May | 0.175835E+09 | 0.593579E+09 | 0.00 | 1558745.48 | 32927391.45 | 351835.91 | 0.264380E+09 | 0.00 | 0.50 |
June | 74310335.13 | 0.219534E+10 | 0.00 | 820737.90 | 25900567.24 | 0.00 | 0.124534E+09 | 0.00 | 0.46 |
July | 0.00 | 0.302841E+10 | 0.00 | 0.00 | 53167644.44 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 2083979.95 | 0.398054E+10 | 0.00 | 1197.13 | 28667706.98 | 0.00 | 78260.22 | 0.00 | 0.44 |
September | 98476095.99 | 0.152776E+10 | 0.00 | 2164921.93 | 66287060.03 | 0.00 | 0.216869E+09 | 0.00 | 0.57 |
October | 0.693135E+09 | 0.446187E+09 | 0.00 | 4094130.34 | 12913321.39 | 80177727.05 | 0.133884E+10 | 0.00 | 0.67 |
November | 0.970848E+09 | 7333854.14 | 1384869.34 | 3556132.94 | 44208530.97 | 0.264272E+09 | 0.116782E+10 | 9642.63 | 0.57 |
December | 0.975549E+09 | 5478364.95 | 0.00 | 2011382.69 | 4208128.06 | 0.663056E+09 | 0.831643E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.626417E+10 | 0.119330E+11 | 1671340.66 | 25090279.08 | 0.296192E+09 | 0.350796E+10 | 0.722307E+10 | 10424.37 | 0.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 796771.55 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.101844E+10 | 0.398054E+10 | 1384869.34 | 4232184.61 | 66287060.03 | 0.145910E+10 | 0.133884E+10 | 9642.63 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.463249E+09 | 0.00 | 0.00 | 5976.97 | 2004853.08 | 0.134060E+10 | 8399088.94 | 0.00 | 0.36 |
February | 0.522455E+09 | 0.00 | 181127.36 | 393115.22 | 503619.98 | 0.751372E+09 | 0.126437E+09 | 438.34 | 0.41 |
March | 0.753576E+09 | 35677047.13 | 0.00 | 1484298.81 | 8687252.03 | 0.133615E+09 | 0.473141E+09 | 0.00 | 0.56 |
April | 0.368057E+09 | 56693357.27 | 0.00 | 3079647.00 | 9250470.25 | 27174730.24 | 0.567380E+09 | 0.00 | 0.73 |
May | 0.103315E+09 | 0.443561E+09 | 0.00 | 1349777.09 | 14259421.78 | 0.00 | 0.249939E+09 | 0.00 | 0.61 |
June | 46366354.16 | 0.172326E+10 | 0.00 | 760404.61 | 9273411.28 | 0.00 | 0.112369E+09 | 0.00 | 0.59 |
July | 0.00 | 0.233972E+10 | 0.00 | 0.00 | 24945364.64 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 1261603.65 | 0.286561E+10 | 0.00 | 1141.07 | 7364193.49 | 0.00 | 104711.55 | 0.00 | 0.50 |
September | 64229266.80 | 0.957884E+09 | 0.00 | 1206867.95 | 38914786.14 | 0.00 | 0.115192E+09 | 0.00 | 0.55 |
October | 0.567591E+09 | 0.225921E+09 | 0.00 | 1206436.52 | 11384121.79 | 64698298.06 | 0.402678E+09 | 0.00 | 0.52 |
November | 0.709151E+09 | 1877427.13 | 2160068.74 | 587714.25 | 28473068.17 | 0.276814E+09 | 0.221540E+09 | 7918.49 | 0.43 |
December | 0.598325E+09 | 380114.97 | 0.00 | 75752.51 | 4772710.84 | 0.748512E+09 | 34388080.40 | 0.00 | 0.36 |
Annual Sum or Average | 0.419758E+10 | 0.865059E+10 | 2341196.10 | 10151131.98 | 0.159833E+09 | 0.334279E+10 | 0.231157E+10 | 8356.83 | 0.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 503619.98 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.753576E+09 | 0.286561E+10 | 2160068.74 | 3079647.00 | 38914786.14 | 0.134060E+10 | 0.567380E+09 | 7918.49 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.631107E+09 | 0.00 | 0.00 | 0.00 | 1545728.97 | 0.221582E+10 | 0.00 | 0.00 | 0.33 |
February | 0.993582E+09 | 0.00 | 0.00 | 8562.03 | 0.00 | 0.123272E+10 | 3657553.35 | 0.00 | 0.37 |
March | 0.173758E+10 | 8907559.23 | 0.00 | 66652.10 | 39978865.33 | 0.120528E+09 | 21725393.72 | 0.00 | 0.41 |
April | 0.990362E+09 | 20487357.50 | 0.00 | 430621.62 | 63440580.10 | 20442185.61 | 78995110.06 | 0.00 | 0.39 |
May | 0.269936E+09 | 0.367971E+09 | 0.00 | 429049.92 | 67233007.59 | 0.00 | 88851970.48 | 0.00 | 0.33 |
June | 77338066.51 | 0.160412E+10 | 0.00 | 620348.92 | 18643362.53 | 0.00 | 0.100694E+09 | 0.00 | 0.34 |
July | 0.00 | 0.226373E+10 | 0.00 | 0.00 | 48221916.75 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 1373394.60 | 0.271018E+10 | 0.00 | 11402.30 | 30705098.07 | 0.00 | 565238.66 | 0.00 | 0.30 |
September | 0.112792E+09 | 0.944904E+09 | 0.00 | 1302378.17 | 24922563.67 | 0.00 | 0.153589E+09 | 0.00 | 0.36 |
October | 0.123608E+10 | 0.239783E+09 | 0.00 | 659108.73 | 5401026.63 | 691619.83 | 0.270212E+09 | 0.00 | 0.39 |
November | 0.183605E+10 | 1554764.39 | 0.00 | 128248.70 | 31447555.15 | 75836119.82 | 74814248.70 | 0.00 | 0.39 |
December | 0.163609E+10 | 0.00 | 0.00 | 0.00 | 1512952.32 | 0.720631E+09 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.952230E+10 | 0.816164E+10 | 0.00 | 3656372.50 | 0.333053E+09 | 0.438667E+10 | 0.793105E+09 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.183605E+10 | 0.271018E+10 | 0.00 | 1302378.17 | 67233007.59 | 0.221582E+10 | 0.270212E+09 | 0.00 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.737403E+09 | 0.00 | 0.00 | 0.00 | 979312.23 | 0.106674E+10 | 0.00 | 0.00 | 0.33 |
February | 0.727053E+09 | 0.00 | 0.00 | 254341.54 | 0.00 | 0.584158E+09 | 0.104371E+09 | 0.00 | 0.38 |
March | 0.909641E+09 | 11000490.48 | 0.00 | 779406.84 | 21969195.93 | 36538278.37 | 0.292667E+09 | 0.00 | 0.44 |
April | 0.414924E+09 | 30100962.12 | 0.00 | 1851042.38 | 28951272.22 | 4916312.50 | 0.415010E+09 | 0.00 | 0.52 |
May | 0.102796E+09 | 0.399912E+09 | 0.00 | 1223309.86 | 27349987.64 | 0.00 | 0.233958E+09 | 0.00 | 0.50 |
June | 31689253.68 | 0.143366E+10 | 0.00 | 987227.10 | 10005396.37 | 0.00 | 0.173222E+09 | 0.00 | 0.51 |
July | 0.00 | 0.207814E+10 | 0.00 | 0.00 | 30711089.94 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 866451.43 | 0.238170E+10 | 0.00 | 12200.46 | 19453525.58 | 0.00 | 373208.14 | 0.00 | 0.42 |
September | 60607008.83 | 0.871849E+09 | 0.00 | 1590369.29 | 14785037.84 | 0.00 | 0.189475E+09 | 0.00 | 0.54 |
October | 0.545320E+09 | 0.206201E+09 | 0.00 | 1969957.32 | 1042592.65 | 384085.56 | 0.702694E+09 | 0.00 | 0.52 |
November | 0.992749E+09 | 4094392.17 | 0.00 | 699057.59 | 17137137.39 | 12093809.14 | 0.314777E+09 | 0.00 | 0.41 |
December | 0.126022E+10 | 745674.64 | 0.00 | 13478.83 | 212871.61 | 0.230265E+09 | 2785867.15 | 0.00 | 0.35 |
Annual Sum or Average | 0.578326E+10 | 0.741741E+10 | 0.00 | 9380391.21 | 0.172597E+09 | 0.193509E+10 | 0.242933E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.126022E+10 | 0.238170E+10 | 0.00 | 1969957.32 | 30711089.94 | 0.106674E+10 | 0.702694E+09 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106683E+10 | 0.00 | 0.00 | 78689.41 | 1548571.97 | 0.242805E+10 | 54618661.81 | 0.00 | 0.40 |
February | 0.949364E+09 | 0.00 | 0.00 | 922562.03 | 0.00 | 0.154546E+10 | 0.252438E+09 | 0.00 | 0.47 |
March | 0.133447E+10 | 48830794.51 | 0.00 | 1106255.64 | 17016877.91 | 0.528631E+09 | 0.318851E+09 | 0.00 | 0.49 |
April | 0.822751E+09 | 49133083.35 | 0.00 | 1531324.93 | 49299940.18 | 0.278303E+09 | 0.142342E+09 | 0.00 | 0.48 |
May | 0.252429E+09 | 0.479271E+09 | 0.00 | 465144.31 | 72526407.81 | 62494246.01 | 80641309.24 | 0.00 | 0.38 |
June | 91104587.43 | 0.189657E+10 | 0.00 | 485765.62 | 63336071.51 | 15116154.16 | 66123324.24 | 0.00 | 0.38 |
July | 0.00 | 0.265643E+10 | 0.00 | 0.00 | 95693302.97 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 1928751.51 | 0.360632E+10 | 0.00 | 1084.92 | 44727621.06 | 0.00 | 21464.55 | 0.00 | 0.39 |
September | 0.130138E+09 | 0.138463E+10 | 0.00 | 1939934.77 | 41221745.59 | 12394798.99 | 0.185493E+09 | 0.00 | 0.52 |
October | 0.819778E+09 | 0.399996E+09 | 0.00 | 3366849.91 | 6127697.16 | 0.249699E+09 | 0.105080E+10 | 0.00 | 0.62 |
November | 0.120557E+10 | 11639438.23 | 0.00 | 2913382.73 | 23550921.97 | 0.471184E+09 | 0.970585E+09 | 0.00 | 0.55 |
December | 0.147411E+10 | 1906845.46 | 0.00 | 863375.22 | 398555.93 | 0.923064E+09 | 0.407004E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.814848E+10 | 0.105347E+11 | 0.00 | 13674369.50 | 0.415448E+09 | 0.651440E+10 | 0.352892E+10 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.147411E+10 | 0.360632E+10 | 0.00 | 3366849.91 | 95693302.97 | 0.242805E+10 | 0.105080E+10 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.607814E+09 | 0.00 | 0.00 | 0.00 | 982136.06 | 0.120267E+10 | 0.00 | 0.00 | 0.33 |
February | 0.724299E+09 | 0.00 | 0.00 | 227752.62 | 0.00 | 0.647168E+09 | 59482355.66 | 0.00 | 0.38 |
March | 0.100018E+10 | 29201747.30 | 0.00 | 764631.55 | 11644370.22 | 42096642.95 | 0.219607E+09 | 0.00 | 0.46 |
April | 0.505149E+09 | 38102900.02 | 0.00 | 1487442.47 | 24927432.82 | 8920150.60 | 0.267282E+09 | 0.00 | 0.51 |
May | 0.131488E+09 | 0.372157E+09 | 0.00 | 771201.79 | 22390573.46 | 0.00 | 0.158474E+09 | 0.00 | 0.46 |
June | 50399924.38 | 0.137893E+10 | 0.00 | 634038.73 | 8290646.80 | 0.00 | 87726645.71 | 0.00 | 0.47 |
July | 0.00 | 0.193556E+10 | 0.00 | 0.00 | 22756868.94 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 765740.36 | 0.238048E+10 | 0.00 | 16444.19 | 11568291.63 | 0.00 | 470647.62 | 0.00 | 0.41 |
September | 61730562.18 | 0.846944E+09 | 0.00 | 1338067.34 | 13560914.93 | 0.00 | 0.140631E+09 | 0.00 | 0.50 |
October | 0.602147E+09 | 0.207517E+09 | 0.00 | 1597957.45 | 1045598.95 | 182590.89 | 0.539681E+09 | 0.00 | 0.51 |
November | 0.104642E+10 | 4198191.92 | 0.00 | 781687.31 | 16964127.21 | 26319181.31 | 0.279055E+09 | 0.00 | 0.44 |
December | 0.114525E+10 | 493940.21 | 0.00 | 75064.67 | 483045.92 | 0.312348E+09 | 41411028.09 | 0.00 | 0.36 |
Annual Sum or Average | 0.587564E+10 | 0.719360E+10 | 0.00 | 7694288.13 | 0.134614E+09 | 0.223970E+10 | 0.179382E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.114525E+10 | 0.238048E+10 | 0.00 | 1597957.45 | 24927432.82 | 0.120267E+10 | 0.539681E+09 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.629281E+09 | 0.00 | 0.00 | 0.00 | 3102843.87 | 0.212113E+10 | 0.00 | 0.00 | 0.33 |
February | 0.102887E+10 | 0.00 | 0.00 | 97710.90 | 413839.52 | 0.111028E+10 | 18965419.22 | 0.00 | 0.37 |
March | 0.170161E+10 | 25118719.69 | 0.00 | 529772.12 | 24537917.95 | 71646846.68 | 0.151865E+09 | 0.00 | 0.44 |
April | 0.816156E+09 | 81857110.09 | 0.00 | 1687463.81 | 15334069.91 | 14840582.97 | 0.340708E+09 | 0.00 | 0.46 |
May | 0.204966E+09 | 0.582388E+09 | 0.00 | 1220848.63 | 17772245.64 | 0.00 | 0.214066E+09 | 0.00 | 0.43 |
June | 71704559.15 | 0.227987E+10 | 0.00 | 838552.22 | 15553172.50 | 0.00 | 0.131225E+09 | 0.00 | 0.45 |
July | 196692.32 | 0.305886E+10 | 0.00 | 0.00 | 46591089.10 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 2345884.46 | 0.357770E+10 | 0.00 | 15071.34 | 30546288.53 | 0.00 | 899639.14 | 0.00 | 0.39 |
September | 0.129792E+09 | 0.116782E+10 | 0.00 | 1136950.55 | 34789572.82 | 0.00 | 0.125053E+09 | 0.00 | 0.40 |
October | 0.122338E+10 | 0.296409E+09 | 0.00 | 545136.44 | 9778722.99 | 17661998.78 | 0.217948E+09 | 0.00 | 0.40 |
November | 0.160866E+10 | 3949830.00 | 216251.83 | 83390.04 | 42331583.10 | 0.250198E+09 | 55043641.76 | 4750.18 | 0.39 |
December | 0.131703E+10 | 519259.07 | 0.00 | 5561.75 | 4719932.64 | 0.888262E+09 | 1254013.81 | 0.00 | 0.35 |
Annual Sum or Average | 0.873398E+10 | 0.110745E+11 | 216251.83 | 6160457.79 | 0.245471E+09 | 0.447403E+10 | 0.125703E+10 | 4750.18 | 0.40 |
Minimum of Months | 196692.32 | 0.00 | 0.00 | 0.00 | 413839.52 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.170161E+10 | 0.357770E+10 | 216251.83 | 1687463.81 | 46591089.10 | 0.212113E+10 | 0.340708E+09 | 4750.18 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.514958E+09 | 0.00 | 0.00 | 524.89 | 1972912.66 | 0.973944E+09 | 125304.41 | 0.00 | 0.28 |
February | 0.543567E+09 | 0.00 | 0.00 | 440470.53 | 263135.77 | 0.490400E+09 | 0.164734E+09 | 0.00 | 0.34 |
March | 0.677276E+09 | 24025177.31 | 0.00 | 1500574.13 | 7711071.39 | 29272723.55 | 0.527830E+09 | 0.00 | 0.46 |
April | 0.320251E+09 | 62957550.55 | 0.00 | 2916936.33 | 5709584.94 | 4713619.36 | 0.666059E+09 | 0.00 | 0.64 |
May | 91637491.22 | 0.496823E+09 | 0.00 | 1691394.08 | 10522135.69 | 0.00 | 0.316019E+09 | 0.00 | 0.60 |
June | 31814765.39 | 0.179862E+10 | 0.00 | 1097550.97 | 9679802.27 | 0.00 | 0.194229E+09 | 0.00 | 0.61 |
July | 125064.87 | 0.252280E+10 | 0.00 | 0.00 | 28645826.94 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 1434737.96 | 0.286083E+10 | 0.00 | 17009.70 | 19430160.88 | 0.00 | 660043.02 | 0.00 | 0.49 |
September | 69793188.60 | 0.977332E+09 | 0.00 | 1338833.73 | 19166630.48 | 0.00 | 0.155242E+09 | 0.00 | 0.54 |
October | 0.504085E+09 | 0.218490E+09 | 0.00 | 1509470.69 | 4809944.54 | 11689616.20 | 0.557295E+09 | 0.00 | 0.47 |
November | 0.782931E+09 | 3105490.04 | 101305.01 | 496421.14 | 23246758.09 | 93395568.94 | 0.195666E+09 | 2209.96 | 0.35 |
December | 0.789545E+09 | 1356251.15 | 0.00 | 27596.48 | 1038901.68 | 0.359963E+09 | 5602545.51 | 0.00 | 0.29 |
Annual Sum or Average | 0.432742E+10 | 0.896635E+10 | 101305.01 | 11036782.69 | 0.132197E+09 | 0.196338E+10 | 0.278346E+10 | 2209.96 | 0.46 |
Minimum of Months | 125064.87 | 0.00 | 0.00 | 0.00 | 263135.77 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.789545E+09 | 0.286083E+10 | 101305.01 | 2916936.33 | 28645826.94 | 0.973944E+09 | 0.666059E+09 | 2209.96 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107489E+10 | 0.00 | 0.00 | 1306986.95 | 3105407.60 | 0.118452E+10 | 0.718589E+09 | 0.00 | 0.36 |
February | 0.107628E+10 | 0.00 | 0.00 | 2337150.07 | 414181.45 | 0.614158E+09 | 0.834672E+09 | 0.00 | 0.49 |
March | 0.119577E+10 | 71120174.03 | 0.00 | 3910264.61 | 7910076.81 | 41891232.19 | 0.124091E+10 | 0.00 | 0.62 |
April | 0.645115E+09 | 0.111046E+09 | 0.00 | 3752780.37 | 10131243.67 | 14475966.82 | 0.770034E+09 | 0.00 | 0.62 |
May | 0.208714E+09 | 0.674606E+09 | 0.00 | 1479355.56 | 17614402.40 | 0.00 | 0.252192E+09 | 0.00 | 0.49 |
June | 84738400.03 | 0.234232E+10 | 0.00 | 799043.90 | 15757421.43 | 0.00 | 0.117136E+09 | 0.00 | 0.46 |
July | 196854.84 | 0.321621E+10 | 0.00 | 0.00 | 46629584.98 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 2258308.87 | 0.418787E+10 | 0.00 | 15285.50 | 30571527.40 | 0.00 | 987459.44 | 0.00 | 0.45 |
September | 0.123187E+09 | 0.160855E+10 | 0.00 | 2045777.99 | 29086395.79 | 0.00 | 0.205864E+09 | 0.00 | 0.56 |
October | 0.805505E+09 | 0.463596E+09 | 0.00 | 4628288.78 | 6246159.88 | 17296949.39 | 0.148529E+10 | 0.00 | 0.70 |
November | 0.116484E+10 | 15575031.04 | 0.00 | 4543191.37 | 33711907.58 | 77705819.14 | 0.146002E+10 | 0.00 | 0.61 |
December | 0.126981E+10 | 9049424.45 | 0.00 | 2643888.24 | 394283.51 | 0.369970E+09 | 0.104373E+10 | 0.00 | 0.45 |
Annual Sum or Average | 0.765132E+10 | 0.126999E+11 | 0.00 | 27462013.34 | 0.201573E+09 | 0.232002E+10 | 0.812942E+10 | 0.00 | 0.51 |
Minimum of Months | 196854.84 | 0.00 | 0.00 | 0.00 | 394283.51 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.126981E+10 | 0.418787E+10 | 0.00 | 4628288.78 | 46629584.98 | 0.118452E+10 | 0.148529E+10 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.559827E+09 | 0.00 | 0.00 | 11833.13 | 1967258.26 | 0.117183E+10 | 24091155.34 | 0.00 | 0.33 |
February | 0.688651E+09 | 0.00 | 0.00 | 416758.82 | 262381.62 | 0.609156E+09 | 0.124556E+09 | 0.00 | 0.41 |
March | 0.914517E+09 | 44310783.98 | 0.00 | 1468181.82 | 6358461.28 | 41290957.27 | 0.459469E+09 | 0.00 | 0.56 |
April | 0.423681E+09 | 73997731.47 | 0.00 | 2634723.87 | 6902078.98 | 9397712.29 | 0.522439E+09 | 0.00 | 0.68 |
May | 0.120475E+09 | 0.514747E+09 | 0.00 | 1262433.95 | 6029990.20 | 0.00 | 0.232187E+09 | 0.00 | 0.60 |
June | 51923985.66 | 0.187869E+10 | 0.00 | 729467.68 | 5718709.84 | 0.00 | 0.100891E+09 | 0.00 | 0.60 |
July | 114616.02 | 0.253332E+10 | 0.00 | 950.56 | 20018016.48 | 0.00 | 9139.85 | 0.00 | 0.47 |
August | 1300421.62 | 0.305176E+10 | 0.00 | 12011.07 | 8211245.33 | 0.00 | 765325.75 | 0.00 | 0.51 |
September | 78644975.88 | 0.101780E+10 | 0.00 | 1136440.80 | 18167799.73 | 0.00 | 0.107514E+09 | 0.00 | 0.54 |
October | 0.668741E+09 | 0.242777E+09 | 0.00 | 1348300.14 | 4500618.83 | 11008819.75 | 0.435784E+09 | 0.00 | 0.52 |
November | 0.941501E+09 | 2922966.55 | 102345.04 | 721769.04 | 26747454.38 | 0.126731E+09 | 0.244509E+09 | 2233.08 | 0.44 |
December | 0.883790E+09 | 1446071.09 | 0.00 | 102457.82 | 2076404.54 | 0.469735E+09 | 56652328.22 | 0.00 | 0.36 |
Annual Sum or Average | 0.533317E+10 | 0.936178E+10 | 102345.04 | 9845328.71 | 0.106960E+09 | 0.243915E+10 | 0.230887E+10 | 2233.08 | 0.50 |
Minimum of Months | 114616.02 | 0.00 | 0.00 | 950.56 | 262381.62 | 0.00 | 9139.85 | 0.00 | 0.33 |
Maximum of Months | 0.941501E+09 | 0.305176E+10 | 102345.04 | 2634723.87 | 26747454.38 | 0.117183E+10 | 0.522439E+09 | 2233.08 | 0.68 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.185998E+12 | 0.177299E+11 | 0.00 | 0.179241E+12 | 0.100453E+11 |
February | 0.184494E+12 | 0.149263E+11 | 0.00 | 0.175527E+12 | 0.179926E+11 |
March | 0.266349E+12 | 0.967659E+10 | 0.00 | 0.194160E+12 | 0.502816E+11 |
April | 0.295870E+12 | 0.465650E+10 | 0.00 | 0.130449E+12 | 0.890592E+11 |
May | 0.324713E+12 | 82203177.99 | 0.00 | 0.448652E+11 | 0.170838E+12 |
June | 0.314920E+12 | -0.573515E+10 | 0.00 | -0.168945E+11 | 0.262024E+12 |
July | 0.305340E+12 | -0.864458E+10 | 0.00 | -0.599891E+11 | 0.301539E+12 |
August | 0.284873E+12 | -0.104804E+11 | 0.00 | -0.730411E+11 | 0.338166E+12 |
September | 0.223326E+12 | -0.269543E+10 | 0.00 | 47422604.90 | 0.202830E+12 |
October | 0.215024E+12 | 0.488588E+10 | 0.00 | 0.144045E+12 | 0.870955E+11 |
November | 0.158476E+12 | 0.957700E+10 | 0.00 | 0.178891E+12 | 0.340511E+11 |
December | 0.151825E+12 | 0.158133E+11 | 0.00 | 0.199159E+12 | 0.130403E+11 |
Annual Sum or Average | 0.291121E+13 | 0.497922E+11 | 0.00 | 0.109646E+13 | 0.157696E+13 |
Minimum of Months | 0.151825E+12 | -0.104804E+11 | 0.00 | -0.730411E+11 | 0.100453E+11 |