Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:31
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 08:32:01
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1612.24 | 323.60 | 323.60 |
Net Site Energy | 1612.24 | 323.60 | 323.60 |
Total Source Energy | 4781.51 | 959.72 | 959.72 |
Net Source Energy | 4781.51 | 959.72 | 959.72 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 21.57 | 33.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 309.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 232.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 125.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 122.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1456.47 | 155.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 21.57 | 33.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 309.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 232.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 50.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 125.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 122.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 21.57 | 33.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 309.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 232.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 50.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 125.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 122.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 91.72 | 31.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 292.34 | 31.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 91.72 | 31.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 292.34 | 31.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1456.472 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1456.472 | 100.00 |
Total On-Site and Utility Electric Sources | 1456.472 | 100.00 |
Total Electricity End Uses | 1456.472 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 64.00 |
Time Setpoint Not Met During Occupied Cooling | 263.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1478.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:31 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.6636 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.6636 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.6636 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 6.6636 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.6636 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 20-JUL-15:09 | 27-DEC-07:40 | - | - | - | - | - | - | - | - | - | - | 05-JAN-12:09 |
Heating | 0.00 | 50925.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 73504.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 42072.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 831.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 34937.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8831.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 171024.51 | 59757.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 50925.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 73504.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 7527.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 831.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 34937.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8831.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 68.30 | 36.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 980.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 734.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 159.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 37.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 398.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 132.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4612.65 | 168.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 13.71 | 7.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 196.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 79.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 26.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 925.83 | 33.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 13.71 | 7.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 196.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 79.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 26.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 925.83 | 33.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.15 | 0.237653 | 0.202000 | 0.637019 | 0.633743 | 0.500000 | 0.001603 |
CORE_MID VAV BOX COMPONENT | 2.30 | 0.325763 | 0.277000 | 0.637269 | 0.868702 | 0.500000 | 0.001170 |
CORE_TOP VAV BOX COMPONENT | 2.52 | 0.297559 | 0.253000 | 0.637225 | 0.793491 | 0.500000 | 0.001280 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.857742 | 0.184195 | 0.157000 | 0.134666 | 0.491186 | 0.500000 | 0.002068 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.757012 | 0.132127 | 0.112000 | 0.084785 | 0.352339 | 0.500000 | 0.002884 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.946542 | 0.166915 | 0.142000 | 0.134409 | 0.445105 | 0.500000 | 0.002283 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.870781 | 0.114857 | 0.098000 | 0.085337 | 0.306285 | 0.500000 | 0.003317 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.690332 | 0.228863 | 0.195000 | 0.134615 | 0.610302 | 0.500000 | 0.001665 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.655685 | 0.152545 | 0.130000 | 0.085239 | 0.406788 | 0.500000 | 0.002498 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.770509 | 0.205048 | 0.174000 | 0.134069 | 0.546796 | 0.500000 | 0.001858 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.699534 | 0.142974 | 0.122000 | 0.085343 | 0.381264 | 0.500000 | 0.002665 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.737081 | 0.214348 | 0.182000 | 0.134149 | 0.571594 | 0.500000 | 0.001777 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.724819 | 0.367988 | 0.500000 | 0.002761 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.826885 | 0.191068 | 0.162000 | 0.133955 | 0.509516 | 0.500000 | 0.001994 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.782611 | 0.127797 | 0.109000 | 0.085305 | 0.340792 | 0.500000 | 0.002981 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 18451.74 |
CORE_MID VAV BOX REHEAT COIL | 19436.65 |
CORE_TOP VAV BOX REHEAT COIL | 34596.22 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 15340.74 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 10025.23 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 15244.30 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 9968.69 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 10778.77 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7144.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 10692.32 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 7086.72 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 11938.30 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 7856.45 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 11846.92 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 7804.92 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.98 | 1.08 | 5.97 | 1.66 | 5.50 | 5.50 | 0.300000 | 0.301128 | 5.50 |
PACU_VAV_MID | 2.69 | 1.08 | 5.37 | 2.03 | 4.83 | 4.83 | 0.300000 | 0.421034 | 4.83 |
PACU_VAV_TOP | 2.98 | 1.08 | 5.95 | 2.94 | 5.71 | 5.71 | 0.300000 | 0.515196 | 5.71 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.50 |
PACU_VAV_MID_OA_CONTROLLER | 4.83 |
PACU_VAV_TOP_OA_CONTROLLER | 5.71 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.50 | 95163.03 | 0.800965 | 1.83 | 31717.84 | 0.800965 |
PACU_VAV_MID COOLING COIL | 4.83 | 85325.84 | 0.800383 | 1.61 | 28439.10 | 0.800383 |
PACU_VAV_TOP COOLING COIL | 5.71 | 97937.95 | 0.800680 | 1.90 | 32642.72 | 0.800680 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 13137.09 |
PACU_VAV_MID HEATING COIL | 14857.30 |
PACU_VAV_TOP HEATING COIL | 14256.18 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.50 |
PACU_VAV_MID FAN | 4.83 |
PACU_VAV_TOP FAN | 5.71 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 31.498 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9622 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9482 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.202 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8052 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8206 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5978 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27384127E-12 | 0.12865281E-14 | -0.83346422E-13 | 0.81323336E-16 |
43 | 6 | 0.26454352E-07 | 0.26406074E-09 | 0.60786733E-08 | -0.12333448E-12 |
44 | 5 | -0.17878666E-03 | 0.22931636E-05 | -0.92101048E-04 | 0.60153540E-08 |
45 | 4 | 0.27880517 | 0.11305828E-02 | 0.94889811E-01 | -0.31698392E-04 |
46 | 3 | -7.0018852 | 0.35426556E-01 | -2.2604600 | 0.27713709E-01 |
47 | 2 | 39.998753 | 0.12720283 | 14.942758 | -0.32362551 |
48 | 1 | -79.877006 | 0.57894353E-01 | -28.852534 | 1.0643678 |
49 | 0 | 46.824343 | 0.11744712E-02 | 16.298269 | |
50 | 7 | -0.27620064E-12 | 0.12774393E-14 | -0.83964131E-13 | 0.81942822E-16 |
51 | 6 | 0.26622461E-07 | 0.26074659E-09 | 0.61157793E-08 | -0.12423095E-12 |
52 | 5 | -0.17965003E-03 | 0.22617301E-05 | -0.92535175E-04 | 0.60516003E-08 |
53 | 4 | 0.27982997 | 0.11139309E-02 | 0.95257664E-01 | -0.31841476E-04 |
54 | 3 | -7.0222151 | 0.34872839E-01 | -2.2664901 | 0.27813240E-01 |
55 | 2 | 40.065841 | 0.12511414 | 14.967577 | -0.32437249 |
56 | 1 | -79.928458 | 0.56904129E-01 | -28.874810 | 1.0654641 |
57 | 0 | 46.824343 | 0.11535943E-02 | 16.297719 | |
58 | 7 | -0.27931930E-12 | 0.13886628E-14 | -0.87137092E-13 | 0.18759942E-15 |
59 | 6 | 0.23561308E-07 | 0.31712788E-09 | 0.54400317E-08 | -0.10799411E-12 |
60 | 5 | -0.16378969E-03 | 0.28142694E-05 | -0.84539011E-04 | 0.53904798E-08 |
61 | 4 | 0.26080053 | 0.14141629E-02 | 0.88437074E-01 | -0.29205444E-04 |
62 | 3 | -6.6442204 | 0.45062581E-01 | -2.1544048 | 0.25964059E-01 |
63 | 2 | 38.817908 | 0.16418932 | 14.505027 | -0.31048073 |
64 | 1 | -78.970774 | 0.75677137E-01 | -28.459322 | 1.0450580 |
65 | 0 | 46.824349 | 0.15543837E-02 | 16.308247 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.424_SHGC_EAST_0.249 | 35 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
2 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 36 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
3 | WINDOW_U_0.424_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
4 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 38 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.1525E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1962E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7029E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7403E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3968E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4269E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9048E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9212E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1033 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7704E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1154 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1963E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7776E-002 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1171E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1945E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1958E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.1523E-003 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1970E-003 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7026E-003 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7411E-003 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3967E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4275E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9047E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9210E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5329E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6261E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1664E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3686E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4503E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2313E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7535E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7678E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1986E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2151E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9154E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9272E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8430E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8471E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3903E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3960E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9297E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9667E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4633E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4925E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1530E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1732E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9047E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9210E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7185E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5459E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1009E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1811E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9268E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.1570E-003 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1945E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1958E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9298E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9668E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4634E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4925E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1530E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1727E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9048E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9212E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4247E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5753E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0346E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3065E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.3508E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1855E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7535E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7679E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1370E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1781E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8401E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8835E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7865E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8059E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3905E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3961E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1030 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.8701E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1131 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.3739E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.2806E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.9907E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6447E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.6997E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.3878E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5433E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.0415E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2974E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.3491E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1712E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6836E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7257E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1171E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0360E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4570E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6050E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.2813E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2048E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6447E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6997E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.2832E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.4956E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.9140E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2392E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.2526E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1278E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6836E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7257E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1030 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.8694E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1131 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.3732E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.2800E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.9902E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6443E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.6995E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.3877E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5432E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.0414E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2973E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.3488E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1710E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6832E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7255E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1172E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0359E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4571E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6050E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.2812E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2047E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6443E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6995E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.2831E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.4954E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.9139E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2390E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.2524E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1276E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6833E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7255E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 37946.85816 | 37946.85816 | 3.15356 | 3.15356 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.48000 | 6.85626E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 6279.31033 | 6279.31033 | 0.30499 | 0.42469 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 27713.93077 | 27713.93077 | 2.30061 | 2.30061 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.48000 | 6.85626E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 13741.99682 | 13741.99682 | 0.67102 | 0.67102 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 30064.16122 | 30064.16122 | 2.51867 | 2.51867 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 37.71000 | 6.87086E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 24358.24540 | 24358.24540 | 1.19438 | 1.19438 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 10238.86775 | 10238.86775 | 0.85774 | 0.85774 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 37.84000 | 6.87107E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 10772.65879 | 10772.65879 | 0.52962 | 0.52962 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9036.49546 | 9036.49546 | 0.75701 | 0.75701 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 33.48500 | 6.86412E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 7039.43141 | 7039.43141 | 0.34611 | 0.34611 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 11298.88076 | 11298.88076 | 0.94654 | 0.94654 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 10705.11091 | 10705.11091 | 0.52629 | 0.52629 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10394.57326 | 10394.57326 | 0.87078 | 0.87078 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 6999.82584 | 6999.82584 | 0.34415 | 0.34415 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 8240.37359 | 8240.37359 | 0.69033 | 0.69033 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 7576.47568 | 7576.47568 | 0.37212 | 0.37212 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 7826.84820 | 7826.84820 | 0.65569 | 0.65569 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 33.48500 | 6.86412E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 5020.77502 | 5020.77502 | 0.24664 | 0.24664 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 9197.44224 | 9197.44224 | 0.77051 | 0.77051 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 7515.92771 | 7515.92771 | 0.36914 | 0.36914 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8350.26865 | 8350.26865 | 0.69953 | 0.69953 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 36.45333 | 6.86884E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 4980.66094 | 4980.66094 | 0.24466 | 0.24466 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8798.48439 | 8798.48439 | 0.73708 | 0.73708 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 8389.22702 | 8389.22702 | 0.41215 | 0.41215 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 8652.16322 | 8652.16322 | 0.72482 | 0.72482 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 32.79167 | 6.86302E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 5520.16726 | 5520.16726 | 0.27123 | 0.27123 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 9870.47868 | 9870.47868 | 0.82689 | 0.82689 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 8325.23568 | 8325.23568 | 0.40900 | 0.40900 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9342.03340 | 9342.03340 | 0.78261 | 0.78261 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 5484.08223 | 5484.08223 | 0.26945 | 0.26945 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 78754.40 | 5.50346 | 5.50346 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 17819.12 | 1.65724 | 1.65724 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 70691.90 | 4.82826 | 4.82826 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 17812.47 | 2.03286 | 2.03286 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 80905.90 | 5.70763 | 5.70763 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 17736.62 | 2.94055 | 2.94055 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.15356 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23765 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63702 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63374 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.60317E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18451.74232 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.30061 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32576 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27700 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63727 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.86870 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.16956E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19436.65487 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.51867 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29756 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25300 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63722 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79349 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.28042E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 34596.21901 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85774 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18419 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15700 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13467 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49119 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.06846E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15340.74450 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75701 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13213 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11200 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47853E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35234 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.88359E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10025.23440 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.94654 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16691 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14200 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13441 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44511 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.28261E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15244.29986 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.87078 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11486 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.80000E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.53365E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30629 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.31717E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9968.68686 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69033 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22886 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19500 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13461 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61030 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.66475E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10778.77029 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65569 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15255 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52391E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40679 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.49762E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7143.99839 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77051 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20505 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17400 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13407 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54680 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.85810E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10692.31549 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69953 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14297 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12200 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.53432E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38126 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.66482E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7086.72245 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73708 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21435 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18200 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13415 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57159 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.77749E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11938.29738 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72482 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36799 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.76096E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7856.44722 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82689 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19107 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16200 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13396 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50952 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.99405E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11846.92204 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78261 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12780 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10900 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.53046E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34079 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.98129E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7804.92165 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.98481 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07628 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.96962 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.65724 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.50346 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.50346 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.30113 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.68600 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07548 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.37201 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.03286 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.82826 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.82826 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.42103 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.97538 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07642 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.95075 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.94055 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.70763 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.70763 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.51520 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.50346 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.82826 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.70763 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.50346 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.50346 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 95163.02747 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80097 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.83430 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31717.83706 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80097 |
152 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 13137.08524 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.50346 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.82826 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.82826 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 85325.84232 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80038 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.60926 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 28439.10325 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80038 |
161 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 14857.30171 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.82826 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.70763 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.70763 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 97937.94887 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80068 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.90235 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32642.71836 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80068 |
170 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 14256.17508 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.70763 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 93715.23 | 319769.63 | 11.19 | 2.82 | 3.20 | 3.38 | 3.54 | 9.62 | 10.93 | 11.52 | 12.07 | 5.5205 | 4.3725 | 2.9335 | 1.2178 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 84109.91 | 286994.92 | 11.24 | 2.83 | 3.22 | 3.39 | 3.55 | 9.65 | 10.98 | 11.57 | 12.12 | 4.8432 | 3.8410 | 2.5780 | 1.0621 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 96414.15 | 328978.73 | 11.17 | 2.81 | 3.20 | 3.37 | 3.53 | 9.60 | 10.92 | 11.51 | 12.04 | 5.7253 | 4.5331 | 3.0405 | 1.2659 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 6.4061354523E-002 | 0.1333642330 | Pass | Pass | 8.5038631087E-002 | 0.2776259190 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.1362595962E-002 | 7.5168329190E-002 | Pass | Pass | 4.6037797615E-002 | 0.3243134434 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.5898103203E-002 | 3.1876161956E-002 | Pass | Pass | 0.1431432412 | 0.4951512433 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.3150723234E-002 | 2.7665609651E-002 | Pass | Pass | 0.2094788405 | 0.7509278800 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.4772567091E-002 | 9.2045974897E-002 | Pass | Pass | 7.7013584490E-002 | 0.2653236475 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 5.5758154805E-002 | 8.1683400797E-002 | Pass | Pass | 2.9312574169E-002 | 0.1667569433 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.7588252253E-002 | 5.4203872032E-002 | Pass | Pass | 2.8842201487E-002 | 0.1651460010 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 7.5594188624E-002 | 9.4459311519E-002 | Pass | Pass | 2.9004699540E-002 | 0.1665500707 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1468101397 | 0.1419680075 | Pass | Pass | 4.0183579555E-002 | 0.2335717430 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.7260208511E-002 | 0.1113917297 | Pass | Pass | 2.7470179634E-002 | 0.1585436808 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.6004196866E-002 | 7.4164080208E-002 | Pass | Pass | 8.4247530481E-002 | 0.2767131751 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 7.8676293984E-002 | 0.1012775144 | Pass | Pass | 8.5016888300E-002 | 0.2784704645 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1369810853 | 0.1797937547 | Pass | Pass | 8.6869018132E-002 | 0.2853082459 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.5876178143E-002 | 0.1191120574 | Pass | Pass | 8.2356541833E-002 | 0.2711247957 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.2059204774E-002 | 6.4256010609E-002 | Pass | Pass | 7.7111951150E-002 | 0.2645888671 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 7.8987636668E-002 | 0.1020811386 | Pass | Pass | 7.7538142677E-002 | 0.2671807203 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1428194726 | 0.1651811444 | Pass | Pass | 0.1005200897 | 0.3316064700 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.1859230182E-002 | 0.1220967239 | Pass | Pass | 7.4781301751E-002 | 0.2564079620 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3264.89 | 51.02 | 0.00 | 1245.64 | 1478.80 | 6040.38 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.424_SHGC_NORTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.424_SHGC_EAST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.424_SHGC_WEST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.424_SHGC_EAST_0.249 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.424_SHGC_EAST_0.249 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.424_SHGC_WEST_0.249 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.424_SHGC_WEST_0.249 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.424_SHGC_NORTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.424_SHGC_EAST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.424_SHGC_WEST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.409 | 0.250 | 0.275 | |||||||||||||||||
North Total or Average | 195.79 | 2.409 | 0.250 | 0.275 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.409 | 0.250 | 0.275 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.89 | 0.0000 | Y | 6.72 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.82 | 0.0000 | Y | 4.24 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.49 | 0.0000 | Y | 6.61 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.51 | 0.0000 | Y | 4.19 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.83 | 0.0000 | Y | 6.70 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.78 | 0.0000 | Y | 4.23 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.45 | 0.0000 | Y | 6.60 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.46 | 0.0000 | Y | 4.18 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.89 | 0.0000 | Y | 6.72 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.82 | 0.0000 | Y | 4.24 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.49 | 0.0000 | Y | 6.61 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.51 | 0.0000 | Y | 4.19 |
Interior Lighting Total | 6.6636 | 4982.19 | 33199.39 | 232.02 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 41.77 | 41.77 | 4.42 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.77 | 62.77 | 4.80 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.77 | 46.49 | 41.14 | |
Exterior Lighting Total | 5686.19 | 50.37 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 95163.03 | 76222.26 | 18940.77 | 0.80 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 85325.84 | 68293.35 | 17032.49 | 0.80 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 97937.95 | 78416.95 | 19521.00 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 93715.2 | 2.82 | 9.62 | N/A | N/A | 11.19 | |
PACU_VAV_MID COOLING COIL | 84109.9 | 2.83 | 9.65 | N/A | N/A | 11.24 | |
PACU_VAV_TOP COOLING COIL | 96414.1 | 2.81 | 9.60 | N/A | N/A | 11.17 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 18451.74 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 19436.65 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 34596.22 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15340.74 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10025.23 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15244.30 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9968.69 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10778.77 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7144.00 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10692.32 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7086.72 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11938.30 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7856.45 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11846.92 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7804.92 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 13137.09 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 14857.30 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 14256.18 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.50 | 11969.41 | 2174.89 | 1.00 | 1.14 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.83 | 10569.10 | 2189.01 | 1.00 | 1.14 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.71 | 12413.45 | 2174.89 | 1.00 | 1.13 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 93715.23 | 2.82 | 9.62 | 11.19 | 5.5205 | 3.20 | 10.93 | 4.3725 | 3.38 | 11.52 | 2.9335 | 3.54 | 12.07 | 1.2178 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 84109.91 | 2.83 | 9.65 | 11.24 | 4.8432 | 3.22 | 10.98 | 3.8410 | 3.39 | 11.57 | 2.5780 | 3.55 | 12.12 | 1.0621 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 96414.15 | 2.81 | 9.60 | 11.17 | 5.7253 | 3.20 | 10.92 | 4.5331 | 3.37 | 11.51 | 3.0405 | 3.53 | 12.04 | 1.2659 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 37946.86 | 37946.86 | 38.58 | 3.154 | 3.154 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00882 | 28.48 | 0.00686 | 0.425 | 0.00 |
CORE_MID | 27713.93 | 27713.93 | 28.18 | 2.301 | 2.301 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 28.48 | 0.00686 | 0.425 | 0.00 |
CORE_TOP | 30064.16 | 30064.16 | 30.57 | 2.519 | 2.519 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00890 | 37.71 | 0.00687 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10238.87 | 10238.87 | 49.38 | 0.858 | 0.858 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00869 | 37.84 | 0.00687 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9036.50 | 9036.50 | 68.84 | 0.757 | 0.757 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00863 | 33.48 | 0.00686 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 11298.88 | 11298.88 | 54.49 | 0.947 | 0.947 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00867 | 38.10 | 0.00687 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10394.57 | 10394.57 | 79.19 | 0.871 | 0.871 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00862 | 36.63 | 0.00687 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8240.37 | 8240.37 | 39.74 | 0.690 | 0.690 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00877 | 37.97 | 0.00687 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7826.85 | 7826.85 | 59.63 | 0.656 | 0.656 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00868 | 33.48 | 0.00686 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9197.44 | 9197.44 | 44.36 | 0.771 | 0.771 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00874 | 37.99 | 0.00687 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8350.27 | 8350.27 | 63.62 | 0.700 | 0.700 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00867 | 36.45 | 0.00687 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8798.48 | 8798.48 | 42.44 | 0.737 | 0.737 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00873 | 37.97 | 0.00687 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8652.16 | 8652.16 | 65.92 | 0.725 | 0.725 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00865 | 32.79 | 0.00686 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9870.48 | 9870.48 | 47.61 | 0.827 | 0.827 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00870 | 37.99 | 0.00687 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9342.03 | 9342.03 | 71.18 | 0.783 | 0.783 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00864 | 36.63 | 0.00687 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 6279.31 | 6279.31 | 6.38 | 0.305 | 0.425 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -5.20 | 0.00281 | 0.425 | 0.00 |
CORE_MID | 13742.00 | 13742.00 | 13.97 | 0.671 | 0.671 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -5.20 | 0.00281 | 0.425 | 0.00 |
CORE_TOP | 24358.25 | 24358.25 | 24.77 | 1.194 | 1.194 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -5.20 | 0.00281 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10772.66 | 10772.66 | 51.96 | 0.530 | 0.530 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 7039.43 | 7039.43 | 53.63 | 0.346 | 0.346 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 10705.11 | 10705.11 | 51.63 | 0.526 | 0.526 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 6999.83 | 6999.83 | 53.33 | 0.344 | 0.344 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7576.48 | 7576.48 | 36.54 | 0.372 | 0.372 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 5020.78 | 5020.78 | 38.25 | 0.247 | 0.247 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 7515.93 | 7515.93 | 36.25 | 0.369 | 0.369 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 4980.66 | 4980.66 | 37.95 | 0.245 | 0.245 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8389.23 | 8389.23 | 40.46 | 0.412 | 0.412 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 5520.17 | 5520.17 | 42.05 | 0.271 | 0.271 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 8325.24 | 8325.24 | 40.15 | 0.409 | 0.409 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 5484.08 | 5484.08 | 41.78 | 0.269 | 0.269 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -5.20 | 0.00281 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.50 | 5.50 | 1.66 | 1.66 | 5.5035 | 1.6572 | 5.5035 | 0.3011 | 0.3000 |
PACU_VAV_MID | 4.83 | 4.83 | 2.03 | 2.03 | 4.8283 | 2.0329 | 4.8283 | 0.4210 | 0.3000 |
PACU_VAV_TOP | 5.71 | 5.71 | 2.94 | 2.94 | 5.7076 | 2.9405 | 5.7076 | 0.5152 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 18451.742 | 18451.742 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18451.74 | 12301.49 | 0.424691 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 6279.31 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 19436.655 | 19436.655 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19436.65 | 19436.65 | 0.671022 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 13742.00 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 34596.219 | 34596.219 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 34596.22 | 34596.22 | 1.194384 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 24358.25 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 15340.744 | 15340.744 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15340.74 | 15340.74 | 0.529617 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00782043 | 43.8606 | 10772.66 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 10025.234 | 10025.234 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10025.23 | 10025.23 | 0.346107 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00781770 | 43.8456 | 7039.43 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 15244.300 | 15244.300 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15244.30 | 15244.30 | 0.526287 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00781916 | 43.8536 | 10705.11 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 9968.687 | 9968.687 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9968.69 | 9968.69 | 0.344154 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00781658 | 43.8394 | 6999.83 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 10778.770 | 10778.770 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10778.77 | 10778.77 | 0.372121 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00780837 | 43.7937 | 7576.48 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 7143.998 | 7143.998 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7144.00 | 7144.00 | 0.246636 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00781625 | 43.8373 | 5020.78 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 10692.315 | 10692.315 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10692.32 | 10692.32 | 0.369137 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00780516 | 43.7760 | 7515.93 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 7086.722 | 7086.722 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7086.72 | 7086.72 | 0.244659 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00781331 | 43.8211 | 4980.66 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 11938.297 | 11938.297 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11938.30 | 11938.30 | 0.412152 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00778251 | 43.6507 | 8389.23 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 7856.447 | 7856.447 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7856.45 | 7856.45 | 0.271232 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00778635 | 43.6720 | 5520.17 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 11846.922 | 11846.922 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11846.92 | 11846.92 | 0.408998 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00777931 | 43.6330 | 8325.24 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 7804.922 | 7804.922 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7804.92 | 7804.92 | 0.269453 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00778388 | 43.6583 | 5484.08 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 95163.027 | 76222.256 | 5.503460 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 89268.38 | 89268.38 | 5.503460 | 26.45 | 15.72 | 0.00845777 | 10.76 | 9.96 | 0.00845777 | 38.10 | 0.00687148 | 18.17 | 17.3727 | 24.00 | 0.00879174 | 41.0288 | 65620.85 | 0.00 | 98125.86 | 72047.11 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 13137.085 | 13137.085 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13137.09 | 13137.09 | 1.651038 | 5.22 | 3.37 | 0.00480928 | 12.80 | 10.33 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 57.9090 | 19.65 | 0.00751659 | 45.8512 | 12829.34 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 85325.842 | 68293.348 | 4.828256 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 80040.54 | 80040.54 | 4.828256 | 26.80 | 15.82 | 0.00843514 | 10.75 | 9.93 | 0.00843514 | 38.10 | 0.00687148 | 18.17 | 19.8022 | 24.00 | 0.00882292 | 41.1721 | 57431.80 | 0.00 | 87982.40 | 64574.01 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 14857.302 | 14857.302 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14857.30 | 14857.30 | 1.448477 | 3.03 | 1.73 | 0.00441659 | 12.80 | 10.33 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 66.0073 | 19.40 | 0.00731712 | 45.3355 | 15694.76 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 97937.949 | 78416.952 | 5.707628 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 91989.04 | 91989.04 | 5.707628 | 26.35 | 15.68 | 0.00844990 | 10.76 | 9.95 | 0.00844990 | 37.97 | 0.00687126 | 18.13 | 16.7513 | 24.00 | 0.00876863 | 40.9221 | 67938.75 | 0.00 | 100987.17 | 74127.38 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 14256.175 | 14256.175 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14256.18 | 14256.18 | 1.712289 | 4.87 | 3.35 | 0.00493398 | 12.80 | 10.33 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 55.8376 | 17.64 | 0.00748004 | 51.7451 | 18378.42 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 18451.742 | 18451.742 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 18451.74 | 12301.49 | 1.0000 | 0.44351838 | 0.424691 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18451.74 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.62 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 6279.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 19436.655 | 19436.655 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19436.65 | 19436.65 | 1.0000 | 0.70076961 | 0.671022 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19436.65 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 13742.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 34596.219 | 34596.219 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 34596.22 | 34596.22 | 1.0000 | 1.24733289 | 1.194384 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34596.22 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 24358.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 15340.744 | 15340.744 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15340.74 | 15340.74 | 1.0000 | 0.55309556 | 0.529617 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15340.74 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00782043 | 21.00 | 0.00782043 | 43.8606 | 10772.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10025.234 | 10025.234 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10025.23 | 10025.23 | 1.0000 | 0.36145004 | 0.346107 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10025.23 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00781770 | 21.00 | 0.00781770 | 43.8456 | 7039.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 15244.300 | 15244.300 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15244.30 | 15244.30 | 1.0000 | 0.54961834 | 0.526287 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15244.30 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00781916 | 21.00 | 0.00781916 | 43.8536 | 10705.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9968.687 | 9968.687 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9968.69 | 9968.69 | 1.0000 | 0.35941127 | 0.344154 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9968.69 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00781658 | 21.00 | 0.00781658 | 43.8394 | 6999.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 10778.770 | 10778.770 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10778.77 | 10778.77 | 1.0000 | 0.38861804 | 0.372121 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10778.77 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00780837 | 21.00 | 0.00780837 | 43.7937 | 7576.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7143.998 | 7143.998 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7144.00 | 7144.00 | 1.0000 | 0.25756989 | 0.246636 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7144.00 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00781625 | 21.00 | 0.00781625 | 43.8373 | 5020.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 10692.315 | 10692.315 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10692.32 | 10692.32 | 1.0000 | 0.38550099 | 0.369137 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10692.32 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00780516 | 21.00 | 0.00780516 | 43.7760 | 7515.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7086.722 | 7086.722 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7086.72 | 7086.72 | 1.0000 | 0.25550486 | 0.244659 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7086.72 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00781331 | 21.00 | 0.00781331 | 43.8211 | 4980.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 11938.297 | 11938.297 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11938.30 | 11938.30 | 1.0000 | 0.43042365 | 0.412152 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11938.30 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00778251 | 21.00 | 0.00778251 | 43.6507 | 8389.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7856.447 | 7856.447 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7856.45 | 7856.45 | 1.0000 | 0.28325653 | 0.271232 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7856.45 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00778635 | 21.00 | 0.00778635 | 43.6720 | 5520.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 11846.922 | 11846.922 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11846.92 | 11846.92 | 1.0000 | 0.42712920 | 0.408998 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11846.92 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00777931 | 21.00 | 0.00777931 | 43.6330 | 8325.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7804.922 | 7804.922 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7804.92 | 7804.92 | 1.0000 | 0.28139883 | 0.269453 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7804.92 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00778388 | 21.00 | 0.00778388 | 43.6583 | 5484.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 95163.027 | 76222.256 | 5.503460 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5626 | 1004.8586 | 1.0443 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.503460 | 5.74743768 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 89268.38 | 89268.38 | 0.9381 | 5.74743768 | 5.503460 | 26.45 | 15.72 | 0.00845777 | 48147.5 | 10.76 | 9.96 | 0.00845777 | 32133.0 | -999.0 | -999.00 | -999.00 | -999.00 | 11969.410 | 77298.97 | 38.10 | 0.00687148 | 18.17 | 0.95610000 | 17.3727 | 24.00 | 0.00879174 | 24.00 | 0.00879174 | 41.0288 | 65620.85 | 0.00 | 98125.86 | 72047.11 | 5.52045734 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.90 | 13.36 | 0.00933248 | 37547.4 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 13137.085 | 13137.085 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.503460 | 5.74743768 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13137.09 | 13137.09 | 1.0000 | 1.72423130 | 1.651038 | 5.22 | 3.37 | 0.00480928 | 17317.4 | 12.80 | 10.33 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13137.09 | -5.20 | 0.00280840 | -5.20 | 0.95610000 | 57.9090 | 19.55 | 0.00756211 | 19.65 | 0.00751659 | 45.8512 | 12829.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 85325.842 | 68293.348 | 4.828256 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5205 | 1004.8586 | 1.0443 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.828256 | 5.04230066 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 80040.54 | 80040.54 | 0.9381 | 5.04230066 | 4.828256 | 26.80 | 15.82 | 0.00843514 | 48446.8 | 10.75 | 9.93 | 0.00843514 | 32062.3 | -999.0 | -999.00 | -999.00 | -999.00 | 10569.105 | 69471.44 | 38.10 | 0.00687148 | 18.17 | 0.95610000 | 19.8022 | 24.00 | 0.00882292 | 24.00 | 0.00882292 | 41.1721 | 57431.80 | 0.00 | 87982.40 | 64574.01 | 4.84316790 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.62 | 13.21 | 0.00928964 | 37156.1 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14857.302 | 14857.302 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.828256 | 5.04230066 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14857.30 | 14857.30 | 1.0000 | 1.51269020 | 1.448477 | 3.03 | 1.73 | 0.00441659 | 14110.8 | 12.80 | 10.33 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14857.30 | -5.20 | 0.00280840 | -5.20 | 0.95610000 | 66.0073 | 19.00 | 0.00753940 | 19.40 | 0.00731712 | 45.3355 | 15694.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 97937.949 | 78416.952 | 5.707628 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5479 | 1004.8586 | 1.0443 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.707628 | 5.96065747 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 91989.04 | 91989.04 | 0.9393 | 5.96065747 | 5.707628 | 26.35 | 15.68 | 0.00844990 | 48019.9 | 10.76 | 9.95 | 0.00844990 | 32113.1 | -999.0 | -999.00 | -999.00 | -999.00 | 12413.454 | 79575.59 | 37.97 | 0.00687126 | 18.13 | 0.95610000 | 16.7513 | 24.00 | 0.00876863 | 24.00 | 0.00876863 | 40.9221 | 67938.75 | 0.00 | 100987.17 | 74127.38 | 5.72525656 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.00 | 13.41 | 0.00934525 | 37683.5 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14256.175 | 14256.175 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.707628 | 5.96065747 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14256.18 | 14256.18 | 1.0000 | 1.78819724 | 1.712289 | 4.87 | 3.35 | 0.00493398 | 17273.9 | 12.80 | 10.33 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14256.18 | -5.20 | 0.00280840 | -5.20 | 0.95610000 | 55.8376 | 17.59 | 0.00762149 | 17.64 | 0.00748004 | 51.7451 | 18378.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.50 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.83 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.71 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2445.00 | 1868.83 | 22.33 |
CORE_MID | 2114.00 | 2712.50 | 40.33 |
CORE_TOP | 2295.33 | 3003.17 | 298.17 |
PERIMETER_TOP_ZN_3 | 3104.83 | 3340.50 | 1163.17 |
PERIMETER_TOP_ZN_2 | 3128.67 | 2993.17 | 908.33 |
PERIMETER_TOP_ZN_1 | 3057.83 | 2493.33 | 742.33 |
PERIMETER_TOP_ZN_4 | 3251.33 | 3020.50 | 1078.50 |
PERIMETER_BOT_ZN_3 | 2529.50 | 3240.50 | 556.33 |
PERIMETER_BOT_ZN_2 | 2732.33 | 2772.33 | 376.17 |
PERIMETER_BOT_ZN_1 | 2636.33 | 2436.17 | 330.00 |
PERIMETER_BOT_ZN_4 | 2726.67 | 2784.50 | 392.33 |
PERIMETER_MID_ZN_3 | 2642.50 | 3148.83 | 600.33 |
PERIMETER_MID_ZN_2 | 2440.33 | 2474.67 | 541.00 |
PERIMETER_MID_ZN_1 | 2838.67 | 2191.67 | 400.67 |
PERIMETER_MID_ZN_4 | 2874.50 | 2817.50 | 609.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4236.17 | 3803.33 | 1478.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.67 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.33 | 0.00 | 0.33 |
PERIMETER_TOP_ZN_3 | 1.33 | 32.67 | 0.33 | 21.83 |
PERIMETER_TOP_ZN_2 | 1.17 | 76.00 | 0.00 | 64.33 |
PERIMETER_TOP_ZN_1 | 0.50 | 64.00 | 0.00 | 53.50 |
PERIMETER_TOP_ZN_4 | 0.50 | 69.00 | 0.00 | 40.50 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 51.33 | 0.00 | 49.17 |
PERIMETER_BOT_ZN_1 | 63.67 | 104.50 | 63.67 | 103.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 48.50 | 0.00 | 30.67 |
PERIMETER_MID_ZN_3 | 0.00 | 10.17 | 0.00 | 7.00 |
PERIMETER_MID_ZN_2 | 0.00 | 68.67 | 0.00 | 64.00 |
PERIMETER_MID_ZN_1 | 0.00 | 54.17 | 0.00 | 51.00 |
PERIMETER_MID_ZN_4 | 0.00 | 59.17 | 0.00 | 37.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 65.17 | 310.17 | 64.00 | 263.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.10 | 52.94 | 2698.04 | 0.991 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.10 | 52.94 | 2698.04 | 0.690 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.10 | 52.94 | 2698.04 | 0.661 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.66 | 11.16 | 568.77 | 0.720 | 0.078 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.95 | 7.07 | 360.08 | 1.147 | 0.082 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.66 | 11.16 | 568.77 | 1.189 | 0.078 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.95 | 7.06 | 360.05 | 1.031 | 0.082 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.66 | 11.16 | 568.77 | 0.616 | 0.041 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.95 | 7.07 | 360.08 | 1.011 | 0.044 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.66 | 11.16 | 568.77 | 0.944 | 0.837 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.95 | 7.06 | 360.05 | 0.886 | 0.044 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.66 | 11.16 | 568.77 | 0.725 | 0.065 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.59 | 7.07 | 360.08 | 1.093 | 0.073 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.66 | 11.16 | 568.77 | 1.213 | 0.065 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.95 | 7.06 | 360.05 | 1.034 | 0.068 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.10 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.10 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.10 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.95 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.95 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.59 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 22.10 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 22.10 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 22.10 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.95 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.95 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.59 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 111.62 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 15689652.73 | 0.00 | 15689652.73 | 0.00 | 15689652.73 | 13393058.27 | 5265.03 | 142.71 | 3352.27 | 34.08 |
CORE_MID | 10927237.97 | 0.00 | 10927237.97 | 0.00 | 10927237.97 | 13393058.27 | 5780.32 | 228.05 | 2751.62 | 28.06 |
CORE_TOP | 10511327.96 | 0.00 | 10511327.96 | 0.00 | 10511327.96 | 13393058.27 | 5741.31 | 312.95 | 2705.74 | 55.57 |
PERIMETER_TOP_ZN_3 | 2415285.36 | 0.00 | 2415285.36 | 511255.28 | 2926540.64 | 2823374.22 | 4311.87 | 230.91 | 4217.22 | 55.57 |
PERIMETER_TOP_ZN_2 | 2423850.06 | 0.00 | 2423850.06 | 340834.81 | 2764684.86 | 1787429.43 | 4211.42 | 419.53 | 4129.05 | 55.57 |
PERIMETER_TOP_ZN_1 | 3971265.09 | 0.00 | 3971265.09 | 511255.28 | 4482520.37 | 2823374.22 | 4142.92 | 279.96 | 4337.12 | 55.57 |
PERIMETER_TOP_ZN_4 | 2184926.69 | 0.00 | 2184926.69 | 340834.81 | 2525761.50 | 1787312.18 | 4229.31 | 190.01 | 4340.68 | 55.57 |
PERIMETER_BOT_ZN_3 | 2063083.40 | 0.00 | 2063083.40 | 271832.90 | 2334916.31 | 2823374.22 | 6108.81 | 187.38 | 2463.81 | 34.08 |
PERIMETER_BOT_ZN_2 | 2132736.49 | 0.00 | 2132736.49 | 181220.85 | 2313957.34 | 1787429.43 | 4969.45 | 142.84 | 3647.71 | 34.08 |
PERIMETER_BOT_ZN_1 | 3152888.93 | 0.00 | 3152888.93 | 2920111.07 | 6073000.00 | 2823374.22 | 4878.56 | 187.16 | 3694.29 | 34.08 |
PERIMETER_BOT_ZN_4 | 1873180.71 | 0.00 | 1873180.71 | 181220.85 | 2054401.56 | 1787312.18 | 5078.86 | 149.20 | 3531.94 | 34.08 |
PERIMETER_MID_ZN_3 | 2419735.31 | 0.00 | 2419735.31 | 425581.69 | 2845317.00 | 2823374.22 | 4454.52 | 324.48 | 3981.00 | 28.06 |
PERIMETER_MID_ZN_2 | 2301346.92 | 0.00 | 2301346.92 | 283719.42 | 2585066.34 | 1601953.02 | 4172.86 | 308.69 | 4278.45 | 937.06 |
PERIMETER_MID_ZN_1 | 4041472.20 | 0.00 | 4041472.20 | 425581.69 | 4467053.88 | 2823374.22 | 4151.47 | 340.08 | 4268.46 | 28.06 |
PERIMETER_MID_ZN_4 | 2183617.19 | 0.00 | 2183617.19 | 283719.42 | 2467336.61 | 1787312.18 | 4315.33 | 164.38 | 4280.29 | 28.06 |
Total Facility | 68291607.03 | 0.00 | 68291607.03 | 6677168.04 | 74968775.08 | 67658168.57 | 6654.94 | 866.72 | 4790.96 | 983.02 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.7292 | 0.0000 | 0.7292 | 0.0000 | 0.7292 | 0.4247 | 2482.11 | 142.71 | 3318.19 |
CORE_MID | 0.5076 | 0.0000 | 0.5076 | 0.0000 | 0.5076 | 0.4247 | 2991.38 | 228.05 | 2723.57 |
CORE_TOP | 0.4863 | 0.0000 | 0.4863 | 0.0000 | 0.4863 | 0.4247 | 2968.79 | 312.95 | 2661.26 |
PERIMETER_TOP_ZN_3 | 0.1118 | 0.0000 | 0.1118 | 0.0120 | 0.1239 | 0.0895 | 1539.35 | 230.91 | 4172.74 |
PERIMETER_TOP_ZN_2 | 0.1126 | 0.0000 | 0.1126 | 0.0080 | 0.1206 | 0.0567 | 1438.90 | 419.53 | 4084.57 |
PERIMETER_TOP_ZN_1 | 0.1846 | 0.0000 | 0.1846 | 0.0120 | 0.1966 | 0.0895 | 1370.40 | 279.96 | 4292.64 |
PERIMETER_TOP_ZN_4 | 0.1012 | 0.0000 | 0.1012 | 0.0080 | 0.1093 | 0.0567 | 1456.79 | 190.01 | 4296.20 |
PERIMETER_BOT_ZN_3 | 0.0956 | 0.0000 | 0.0956 | 0.0064 | 0.1021 | 0.0895 | 3325.89 | 187.38 | 2429.73 |
PERIMETER_BOT_ZN_2 | 0.0992 | 0.0000 | 0.0992 | 0.0043 | 0.1034 | 0.0567 | 2186.53 | 142.84 | 3613.62 |
PERIMETER_BOT_ZN_1 | 0.1465 | 0.0000 | 0.1465 | 0.1302 | 0.2767 | 0.0895 | 2095.64 | 187.16 | 3660.21 |
PERIMETER_BOT_ZN_4 | 0.0869 | 0.0000 | 0.0869 | 0.0043 | 0.0912 | 0.0567 | 2295.94 | 149.20 | 3497.86 |
PERIMETER_MID_ZN_3 | 0.1124 | 0.0000 | 0.1124 | 0.0100 | 0.1225 | 0.0895 | 1665.58 | 324.48 | 3952.94 |
PERIMETER_MID_ZN_2 | 0.1073 | 0.0000 | 0.1073 | 0.0071 | 0.1144 | 0.0567 | 1383.92 | 308.69 | 3341.39 |
PERIMETER_MID_ZN_1 | 0.1882 | 0.0000 | 0.1882 | 0.0100 | 0.1983 | 0.0895 | 1362.52 | 340.08 | 4240.40 |
PERIMETER_MID_ZN_4 | 0.1015 | 0.0000 | 0.1015 | 0.0067 | 0.1082 | 0.0567 | 1526.39 | 164.38 | 4252.23 |
Total Facility | 3.1711 | 0.0000 | 3.1711 | 0.2191 | 3.3903 | 2.1513 | 3853.41 | 866.72 | 4728.03 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 27169208.41 | 0.00 | 27169208.41 | 22614548.33 | 4068.09 | 4.18 | 4687.73 | 34.08 |
PACU_VAV_MID | 23855724.84 | 0.00 | 23855724.84 | 22429071.92 | 4049.67 | 1.45 | 4708.88 | 28.06 |
PACU_VAV_TOP | 23455716.56 | 0.00 | 23455716.56 | 22614548.33 | 4048.39 | 1.34 | 4710.28 | 55.57 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.2624 | 0.0000 | 1.2624 | 0.7171 | 1285.18 | 4.18 | 4653.65 |
PACU_VAV_MID | 1.1091 | 0.0000 | 1.1091 | 0.7084 | 1260.73 | 1.45 | 4680.82 |
PACU_VAV_TOP | 1.0869 | 0.0000 | 1.0869 | 0.7171 | 1275.87 | 1.34 | 4665.80 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 704.25 | 2309.49 | 0.00 | 0.00 | 0.00 | 1798.30 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 102.82 | 2567.67 | 0.00 | 0.00 | 0.00 | 2159.86 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 53.17 | 2576.90 | 0.00 | 0.00 | 0.00 | 2230.27 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.0319 | 2.3159 | 0.0000 | 0.0000 | 0.0000 | 0.8378 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.0077 | 1.8414 | 0.0000 | 0.0000 | 0.0000 | 0.8391 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.9638 | 1.7990 | 0.0000 | 0.0000 | 0.0000 | 0.8397 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 943 |
Defaulted Fields | 546 |
Fields with Defaults | 2233 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1456.47 | 12317.57 | 16-JUL-17:30 | 171024.51 | 20-JUL-15:10 |
Electricity:Building | 937.45 | 12146.72 | 29-MAY-17:20 | 69360.88 | 13-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 291.77 | 4006.86 | 01-JAN-00:10 | 23121.21 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 937.45 | 12146.72 | 29-MAY-17:20 | 69360.88 | 13-OCT-07:10 |
InteriorLights:Electricity | 232.02 | 905.38 | 29-MAY-17:20 | 25003.79 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 232.02 | 905.38 | 29-MAY-17:20 | 25003.79 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity | 232.02 | 905.38 | 29-MAY-17:20 | 25003.79 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 232.02 | 905.38 | 29-MAY-17:20 | 25003.79 | 22-NOV-17:00 |
Electricity:Zone:CORE_MID | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 31.05 | 413.68 | 16-APR-17:10 | 2475.80 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.72 | 27.57 | 01-JAN-09:00 | 1040.56 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.72 | 27.57 | 01-JAN-09:00 | 1040.56 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.64 | 261.88 | 14-MAY-17:10 | 1567.33 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.24 | 17.46 | 01-JAN-08:10 | 658.76 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.24 | 17.46 | 01-JAN-08:10 | 658.76 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 30.94 | 413.67 | 19-MAR-17:10 | 2475.79 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.61 | 27.57 | 01-JAN-08:10 | 1040.56 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.61 | 27.57 | 01-JAN-08:10 | 1040.56 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.59 | 261.87 | 12-MAR-17:10 | 1567.28 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.19 | 17.46 | 01-JAN-09:00 | 658.71 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.19 | 17.46 | 01-JAN-09:00 | 658.71 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 31.03 | 413.68 | 02-APR-17:10 | 2475.80 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.70 | 27.57 | 01-JAN-09:00 | 1040.56 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.70 | 27.57 | 01-JAN-09:00 | 1040.56 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.64 | 261.88 | 07-MAY-17:10 | 1567.33 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.23 | 17.46 | 01-JAN-08:10 | 658.76 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.23 | 17.46 | 01-JAN-08:10 | 658.76 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 30.93 | 413.67 | 12-MAR-17:10 | 2475.79 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.60 | 27.57 | 01-JAN-08:10 | 1040.56 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.60 | 27.57 | 01-JAN-08:10 | 1040.56 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.58 | 261.87 | 12-MAR-17:10 | 1567.28 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.18 | 17.46 | 01-JAN-09:00 | 658.71 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.18 | 17.46 | 01-JAN-09:00 | 658.71 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 31.05 | 413.68 | 16-APR-17:10 | 2475.80 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.72 | 27.57 | 01-JAN-09:00 | 1040.56 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.72 | 27.57 | 01-JAN-09:00 | 1040.56 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.64 | 261.88 | 14-MAY-17:10 | 1567.33 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.24 | 17.46 | 01-JAN-08:10 | 658.76 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.24 | 17.46 | 01-JAN-08:10 | 658.76 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 30.94 | 413.67 | 19-MAR-17:10 | 2475.79 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.61 | 27.57 | 01-JAN-08:10 | 1040.56 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.61 | 27.57 | 01-JAN-08:10 | 1040.56 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.59 | 261.87 | 12-MAR-17:10 | 1567.28 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.19 | 17.46 | 01-JAN-09:00 | 658.71 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.19 | 17.46 | 01-JAN-09:00 | 658.71 | 22-NOV-17:00 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 468.51 | 168.34 | 01-JAN-00:10 | 109273.84 | 20-JUL-15:10 |
ExteriorEquipment:Electricity | 11.69 | 168.34 | 01-JAN-00:10 | 838.60 | 11-DEC-17:00 |
Transformer:ExteriorEquipment:Electricity | 11.69 | 168.34 | 01-JAN-00:10 | 838.60 | 11-DEC-17:00 |
ElectricityPurchased:Facility | 1456.47 | 12317.57 | 16-JUL-17:30 | 171024.51 | 20-JUL-15:10 |
ElectricityPurchased:Plant | 1456.47 | 12317.57 | 16-JUL-17:30 | 171024.51 | 20-JUL-15:10 |
Cogeneration:ElectricityPurchased | 1456.47 | 12317.57 | 16-JUL-17:30 | 171024.51 | 20-JUL-15:10 |
General:Cogeneration:ElectricityPurchased | 1456.47 | 12317.57 | 16-JUL-17:30 | 171024.51 | 20-JUL-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1456.47 | 12317.57 | 16-JUL-17:30 | 171024.51 | 20-JUL-15:10 |
ElectricityNet:Plant | 1456.47 | 12317.57 | 16-JUL-17:30 | 171024.51 | 20-JUL-15:10 |
Cogeneration:ElectricityNet | 1456.47 | 12317.57 | 16-JUL-17:30 | 171024.51 | 20-JUL-15:10 |
General:Cogeneration:ElectricityNet | 1456.47 | 12317.57 | 16-JUL-17:30 | 171024.51 | 20-JUL-15:10 |
Heating:Electricity | 21.57 | 0.00 | 01-JAN-00:10 | 88392.65 | 27-DEC-07:10 |
General:Heating:Electricity | 21.57 | 0.00 | 01-JAN-00:10 | 88392.65 | 27-DEC-07:10 |
Fans:Electricity | 125.81 | 0.00 | 01-JAN-00:10 | 34937.99 | 20-JUL-15:10 |
General:Fans:Electricity | 125.81 | 0.00 | 01-JAN-00:10 | 34937.99 | 20-JUL-15:10 |
ExteriorLights:Electricity | 50.37 | 0.00 | 01-JAN-07:20 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 50.37 | 0.00 | 01-JAN-07:20 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 309.45 | 0.00 | 01-JAN-00:10 | 76228.29 | 03-JUL-14:30 |
General:Cooling:Electricity | 309.45 | 0.00 | 01-JAN-00:10 | 76228.29 | 03-JUL-14:30 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-06:10 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-06:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 6.52 | 0.00 | 01-JAN-00:10 | 702.61 | 22-NOV-17:10 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 155.77 | 1886.44 | 10-JAN-06:20 | 59757.29 | 27-DEC-07:40 |
NaturalGas:HVAC | 33.34 | 0.00 | 01-JAN-00:10 | 51446.26 | 27-DEC-07:30 |
Heating:NaturalGas | 33.34 | 0.00 | 01-JAN-00:10 | 51446.26 | 27-DEC-07:30 |
General:Heating:NaturalGas | 33.34 | 0.00 | 01-JAN-00:10 | 51446.26 | 27-DEC-07:30 |
NaturalGas:Plant | 122.43 | 1886.44 | 10-JAN-06:20 | 9951.79 | 27-JAN-12:10 |
WaterSystems:NaturalGas | 122.43 | 1886.44 | 10-JAN-06:20 | 9951.79 | 27-JAN-12:10 |
Water Heater:WaterSystems:NaturalGas | 122.43 | 1886.44 | 10-JAN-06:20 | 9951.79 | 27-JAN-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2503.83 | 0.00 | 01-JAN-00:10 | 419759.91 | 20-JUL-15:10 |
EnergyTransfer:Building | 1250.21 | 0.00 | 01-JAN-00:10 | 168506.17 | 03-JUL-14:30 |
EnergyTransfer:Zone:CORE_BOTTOM | 257.18 | 0.00 | 01-JAN-00:10 | 28371.05 | 05-SEP-07:50 |
Heating:EnergyTransfer | 27.40 | 0.00 | 01-JAN-00:10 | 77715.60 | 27-DEC-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 27.40 | 0.00 | 01-JAN-00:10 | 77715.60 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1222.81 | 0.00 | 01-JAN-00:10 | 168506.17 | 03-JUL-14:30 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 257.18 | 0.00 | 01-JAN-00:10 | 28371.05 | 05-SEP-07:50 |
General:Cooling:EnergyTransfer | 1222.81 | 0.00 | 01-JAN-00:10 | 168506.17 | 03-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 257.18 | 0.00 | 01-JAN-00:10 | 28371.05 | 05-SEP-07:50 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 55.18 | 0.00 | 01-JAN-00:10 | 11959.50 | 03-JUL-13:00 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 8.01 | 0.00 | 01-JAN-00:10 | 8098.68 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 8.01 | 0.00 | 01-JAN-00:10 | 8098.68 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 47.17 | 0.00 | 01-JAN-00:10 | 11959.50 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 47.17 | 0.00 | 01-JAN-00:10 | 11959.50 | 03-JUL-13:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 28.44 | 0.00 | 01-JAN-00:10 | 5951.01 | 03-JUL-10:50 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.03 | 0.00 | 01-JAN-00:10 | 2818.22 | 04-DEC-12:00 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.03 | 0.00 | 01-JAN-00:10 | 2818.22 | 04-DEC-12:00 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 24.41 | 0.00 | 01-JAN-00:10 | 5951.01 | 03-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 24.41 | 0.00 | 01-JAN-00:10 | 5951.01 | 03-JUL-10:50 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 32.05 | 0.00 | 01-JAN-00:10 | 5706.30 | 03-JUL-06:30 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 1.99 | 0.00 | 01-JAN-00:10 | 2778.66 | 27-DEC-08:30 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 1.99 | 0.00 | 01-JAN-00:10 | 2778.66 | 27-DEC-08:30 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 30.06 | 0.00 | 01-JAN-00:10 | 5706.30 | 03-JUL-06:30 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 30.06 | 0.00 | 01-JAN-00:10 | 5706.30 | 03-JUL-06:30 |
EnergyTransfer:Zone:CORE_MID | 167.22 | 0.00 | 01-JAN-00:10 | 19900.81 | 19-JUN-07:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 1723.14 | 04-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 1723.14 | 04-DEC-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 167.22 | 0.00 | 01-JAN-00:10 | 19900.81 | 19-JUN-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 167.22 | 0.00 | 01-JAN-00:10 | 19900.81 | 19-JUN-07:20 |
EnergyTransfer:Zone:CORE_TOP | 163.18 | 0.00 | 01-JAN-00:10 | 21569.85 | 03-JUL-13:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.54 | 0.00 | 01-JAN-00:10 | 14300.22 | 04-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.54 | 0.00 | 01-JAN-00:10 | 14300.22 | 04-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 162.64 | 0.00 | 01-JAN-00:10 | 21569.85 | 03-JUL-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 162.64 | 0.00 | 01-JAN-00:10 | 21569.85 | 03-JUL-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 43.40 | 0.00 | 01-JAN-00:10 | 7863.24 | 03-JUL-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.85 | 0.00 | 01-JAN-00:10 | 7518.25 | 04-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.85 | 0.00 | 01-JAN-00:10 | 7518.25 | 04-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 40.55 | 0.00 | 01-JAN-00:10 | 7863.24 | 03-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 40.55 | 0.00 | 01-JAN-00:10 | 7863.24 | 03-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 41.37 | 0.00 | 01-JAN-00:10 | 8401.70 | 03-JUL-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.20 | 0.00 | 01-JAN-00:10 | 5067.29 | 04-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.20 | 0.00 | 01-JAN-00:10 | 5067.29 | 04-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 40.18 | 0.00 | 01-JAN-00:10 | 8401.70 | 03-JUL-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 40.18 | 0.00 | 01-JAN-00:10 | 8401.70 | 03-JUL-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 64.04 | 0.00 | 01-JAN-00:10 | 11493.20 | 03-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.46 | 0.00 | 01-JAN-00:10 | 7257.62 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.46 | 0.00 | 01-JAN-00:10 | 7257.62 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 62.58 | 0.00 | 01-JAN-00:10 | 11493.20 | 03-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 62.58 | 0.00 | 01-JAN-00:10 | 11493.20 | 03-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 41.45 | 0.00 | 01-JAN-00:10 | 9290.81 | 15-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 1.60 | 0.00 | 01-JAN-00:10 | 4884.36 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 1.60 | 0.00 | 01-JAN-00:10 | 4884.36 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 39.85 | 0.00 | 01-JAN-00:10 | 9290.81 | 15-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 39.85 | 0.00 | 01-JAN-00:10 | 9290.81 | 15-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 37.21 | 0.00 | 01-JAN-00:10 | 6792.39 | 03-JUL-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.39 | 0.00 | 01-JAN-00:10 | 2994.33 | 03-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.39 | 0.00 | 01-JAN-00:10 | 2994.33 | 03-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 36.83 | 0.00 | 01-JAN-00:10 | 6792.39 | 03-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 36.83 | 0.00 | 01-JAN-00:10 | 6792.39 | 03-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 38.08 | 0.00 | 01-JAN-00:10 | 7425.64 | 03-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.10 | 0.00 | 01-JAN-00:10 | 1993.57 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.10 | 0.00 | 01-JAN-00:10 | 1993.57 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 37.98 | 0.00 | 01-JAN-00:10 | 7425.64 | 03-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 37.98 | 0.00 | 01-JAN-00:10 | 7425.64 | 03-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 61.11 | 0.00 | 01-JAN-00:10 | 10684.57 | 03-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 3.78 | 0.00 | 01-JAN-00:10 | 9630.28 | 27-DEC-07:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 3.78 | 0.00 | 01-JAN-00:10 | 9630.28 | 27-DEC-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 57.33 | 0.00 | 01-JAN-00:10 | 10684.57 | 03-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 57.33 | 0.00 | 01-JAN-00:10 | 10684.57 | 03-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 36.95 | 0.00 | 01-JAN-00:10 | 7720.73 | 07-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.12 | 0.00 | 01-JAN-00:10 | 1961.99 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.12 | 0.00 | 01-JAN-00:10 | 1961.99 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 36.83 | 0.00 | 01-JAN-00:10 | 7720.73 | 07-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 36.83 | 0.00 | 01-JAN-00:10 | 7720.73 | 07-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 41.15 | 0.00 | 01-JAN-00:10 | 7158.75 | 03-JUL-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.55 | 0.00 | 01-JAN-00:10 | 4302.39 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.55 | 0.00 | 01-JAN-00:10 | 4302.39 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 40.60 | 0.00 | 01-JAN-00:10 | 7158.75 | 03-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 40.60 | 0.00 | 01-JAN-00:10 | 7158.75 | 03-JUL-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 38.55 | 0.00 | 01-JAN-00:10 | 8107.48 | 30-MAY-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.25 | 0.00 | 01-JAN-00:10 | 3032.42 | 27-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.25 | 0.00 | 01-JAN-00:10 | 3032.42 | 27-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 38.30 | 0.00 | 01-JAN-00:10 | 8107.48 | 30-MAY-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 38.30 | 0.00 | 01-JAN-00:10 | 8107.48 | 30-MAY-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 63.77 | 0.00 | 01-JAN-00:10 | 10310.30 | 03-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.24 | 0.00 | 01-JAN-00:10 | 4125.42 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.24 | 0.00 | 01-JAN-00:10 | 4125.42 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 63.54 | 0.00 | 01-JAN-00:10 | 10310.30 | 03-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 63.54 | 0.00 | 01-JAN-00:10 | 10310.30 | 03-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 39.86 | 0.00 | 01-JAN-00:10 | 8631.53 | 15-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.30 | 0.00 | 01-JAN-00:10 | 2937.58 | 27-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.30 | 0.00 | 01-JAN-00:10 | 2937.58 | 27-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 39.56 | 0.00 | 01-JAN-00:10 | 8631.53 | 15-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 39.56 | 0.00 | 01-JAN-00:10 | 8631.53 | 15-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 42.69 | 0.00 | 01-JAN-00:10 | 5648.81 | 02-FEB-12:10 |
PlantLoopHeatingDemand:Plant | 42.69 | 0.00 | 01-JAN-00:10 | 5648.81 | 02-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 42.69 | 0.00 | 01-JAN-00:10 | 5648.81 | 02-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 42.69 | 0.00 | 01-JAN-00:10 | 5648.81 | 02-FEB-12:10 |
EnergyTransfer:HVAC | 1210.93 | 0.00 | 01-JAN-00:10 | 326571.75 | 20-JUL-15:10 |
HeatingCoils:EnergyTransfer | 48.24 | 0.00 | 01-JAN-00:10 | 127284.17 | 27-DEC-07:10 |
CoolingCoils:EnergyTransfer | 1162.69 | 0.00 | 01-JAN-00:10 | 326571.75 | 20-JUL-15:10 |
EnergyTransfer:Plant | 42.69 | 0.00 | 01-JAN-00:10 | 5648.81 | 02-FEB-12:10 |
WaterSystems:EnergyTransfer | 42.69 | 0.00 | 01-JAN-00:10 | 5648.81 | 02-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 42.69 | 0.00 | 01-JAN-00:10 | 5648.81 | 02-FEB-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -257.180 | 0.000 | 0.000 | 32.691 | 55.599 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -67.278 |
CORE_MID | 0.000 | 0.000 | 0.003 | -167.216 | 0.000 | 0.000 | 33.048 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -36.860 |
CORE_TOP | 0.000 | 0.000 | 0.540 | -162.642 | 0.000 | 0.000 | 33.617 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -42.539 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 2.852 | -40.549 | 0.000 | 0.000 | 7.279 | 6.715 | 24.333 | 19.018 | 0.000 | 0.481 | 7.049 | 0.000 | -23.843 | 0.000 | -3.335 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 1.197 | -40.176 | 0.000 | 0.000 | 4.495 | 4.240 | 15.404 | 38.085 | 0.000 | 0.311 | 0.001 | 0.000 | -15.009 | 0.000 | -2.322 | -6.225 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 1.458 | -62.579 | 0.000 | 0.000 | 7.053 | 6.611 | 24.332 | 65.158 | 0.000 | 0.471 | 0.002 | 0.000 | -22.997 | 0.000 | -3.635 | -15.872 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 1.602 | -39.850 | 0.000 | 0.000 | 4.559 | 4.188 | 15.403 | 38.346 | 0.000 | 0.302 | 0.000 | 0.000 | -16.054 | 0.000 | -2.346 | -6.149 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.385 | -36.827 | 0.000 | 0.000 | 7.229 | 6.699 | 24.333 | 19.320 | 0.000 | 0.282 | 5.507 | 0.000 | -25.044 | 0.000 | -1.884 | -0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.097 | -37.983 | 0.000 | 0.000 | 4.447 | 4.233 | 15.404 | 38.205 | 0.000 | 0.172 | 0.003 | 0.000 | -16.161 | 0.000 | -1.348 | -7.065 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 3.783 | -57.326 | 0.000 | 0.000 | 7.072 | 6.601 | 24.332 | 65.590 | 0.000 | 5.298 | 0.000 | 0.000 | -24.853 | 0.000 | -18.202 | -12.296 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.118 | -36.832 | 0.000 | 0.000 | 4.499 | 4.181 | 15.403 | 38.570 | 0.000 | 0.166 | 0.000 | 0.000 | -17.333 | 0.000 | -1.362 | -7.409 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.549 | -40.603 | 0.000 | 0.000 | 7.185 | 6.715 | 24.333 | 18.891 | 0.000 | 0.412 | 11.013 | 0.000 | -25.498 | 0.000 | -2.996 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.245 | -38.301 | 0.000 | 0.000 | 3.279 | 4.240 | 15.404 | 37.838 | 0.000 | 0.261 | 0.000 | 0.000 | -15.979 | 0.000 | -2.081 | -4.905 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.237 | -63.536 | 0.000 | 0.000 | 6.986 | 6.611 | 24.332 | 64.978 | 0.000 | 0.401 | 0.002 | 0.000 | -24.394 | 0.000 | -3.232 | -12.383 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.303 | -39.558 | 0.000 | 0.000 | 4.505 | 4.188 | 15.403 | 38.290 | 0.000 | 0.255 | 0.000 | 0.000 | -17.108 | 0.000 | -2.096 | -4.182 |
TOPFLOOR_PLENUM | 8.010 | -47.174 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.567 | 43.759 | 0.000 | 0.000 | 0.000 | -5.162 | -0.001 |
MIDFLOOR_PLENUM | 4.034 | -24.408 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.626 | 25.066 | 0.000 | 0.000 | 0.000 | -5.318 | -0.000 |
FIRSTFLOOR_PLENUM | 1.989 | -30.058 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.490 | 31.904 | 0.000 | 0.000 | 0.000 | -4.326 | -0.000 |
Total Facility | 14.033 | -101.640 | 13.369 | -1121.158 | 0.000 | 0.000 | 167.942 | 232.017 | 705.434 | 482.289 | 0.000 | 10.494 | 124.307 | 0.000 | -244.273 | 0.000 | -59.645 | -223.163 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 30-MAY-04:02 | 0.00 | 0.00 | 0.00 | -42380.91 | 0.00 | 0.00 | 0.00 | 211.73 | 4405.64 | 0.00 | 0.00 | 0.00 | 37763.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 17-JUL-05:14 | 0.00 | 0.00 | 0.00 | -33065.19 | 0.00 | 0.00 | 315.56 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 29175.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 30-MAY-04:02 | 0.00 | 0.00 | 0.00 | -33415.79 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 30762.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 02-JUL-16:12 | 0.00 | 0.00 | 0.00 | -12573.55 | 0.00 | 0.00 | 25.16 | 27.57 | 478.42 | 3159.22 | 0.00 | 258.54 | 8624.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 17-SEP-09:12 | 0.00 | 0.00 | 0.00 | -11878.00 | 0.00 | 0.00 | 15.16 | 17.46 | 302.86 | 7303.85 | 0.00 | 0.00 | 4273.81 | 0.00 | -0.00 | 0.00 | -35.13 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-OCT-12:12 | 0.00 | 0.00 | 0.00 | -15634.50 | 0.00 | 0.00 | 22.58 | 27.57 | 478.41 | 11889.94 | 0.00 | 32.87 | 3183.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 16-APR-16:11 | 0.00 | 0.00 | 0.00 | -14363.75 | 0.00 | 0.00 | 13.15 | 17.46 | 302.86 | 9223.52 | 0.00 | 15.59 | 4791.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 27-AUG-17:01 | 0.00 | 0.00 | 0.00 | -8074.53 | 0.00 | 0.00 | 0.00 | 27.57 | 386.10 | 1642.31 | 0.00 | 144.67 | 5873.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-JUL-09:32 | 0.00 | 0.00 | 0.00 | -10448.14 | 0.00 | 0.00 | 15.52 | 17.46 | 302.86 | 6441.19 | 0.00 | 0.00 | 3672.41 | 0.00 | -0.00 | 0.00 | -1.29 | 0.00 |
PERIMETER_BOT_ZN_1 | 29-OCT-15:12 | 0.00 | 0.00 | 0.00 | -12200.31 | 0.00 | 0.00 | 24.67 | 27.57 | 478.41 | 7459.76 | 0.00 | 0.00 | 4320.92 | 0.00 | -0.00 | 0.00 | -111.03 | 0.00 |
PERIMETER_BOT_ZN_4 | 13-AUG-16:31 | 0.00 | 0.00 | 0.00 | -11510.81 | 0.00 | 0.00 | 14.14 | 17.46 | 302.86 | 7271.48 | 0.00 | 22.17 | 3882.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 18-JUN-16:11 | 0.00 | 0.00 | 0.00 | -10909.02 | 0.00 | 0.00 | 27.22 | 27.57 | 478.42 | 2994.06 | 0.00 | 173.02 | 7208.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUL-08:52 | 0.00 | 0.00 | 0.00 | -11875.25 | 0.00 | 0.00 | 14.33 | 17.46 | 302.86 | 7457.87 | 0.00 | 0.00 | 4096.32 | 0.00 | -0.00 | 0.00 | -13.59 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-12:32 | 0.00 | 0.00 | 0.00 | -13046.49 | 0.00 | 0.00 | 24.92 | 27.57 | 478.41 | 7625.26 | 0.00 | 20.66 | 4869.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 13-AUG-16:31 | 0.00 | 0.00 | 0.00 | -12942.34 | 0.00 | 0.00 | 12.96 | 17.46 | 302.86 | 7193.35 | 0.00 | 28.92 | 5386.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 03-JUL-13:00 | 0.00 | -11959.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.00 | 11892.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 03-JUL-10:10 | 0.00 | -6290.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.49 | 6281.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 03-JUL-12:08 | 0.00 | -7104.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 | 7097.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-JUL-06:03 | 0.00 | -12462.52 | 0.00 | -187813.43 | 0.00 | 0.00 | 3471.69 | 6738.11 | 21098.80 | 22739.02 | 0.00 | 2062.15 | 144166.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 27-DEC-07:01 | 0.00 | 0.00 | 13974.44 | 0.00 | 0.00 | 0.00 | 883.67 | 1645.36 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19529.39 |
CORE_TOP | 04-DEC-06:01 | 0.00 | 0.00 | 28356.98 | 0.00 | 0.00 | 0.00 | 492.87 | 211.73 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -32087.50 |
PERIMETER_TOP_ZN_3 | 04-DEC-05:01 | 0.00 | 0.00 | 10625.58 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2347.87 | 0.00 | -37.92 | -8799.23 |
PERIMETER_TOP_ZN_2 | 04-DEC-05:01 | 0.00 | 0.00 | 9302.95 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1560.10 | 0.00 | -25.57 | -8071.43 |
PERIMETER_TOP_ZN_1 | 26-DEC-05:01 | 0.00 | 0.00 | 11492.11 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2277.85 | 0.00 | -642.28 | -9131.42 |
PERIMETER_TOP_ZN_4 | 26-DEC-05:01 | 0.00 | 0.00 | 9380.49 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1488.27 | 0.00 | -425.08 | -7821.29 |
PERIMETER_BOT_ZN_3 | 27-DEC-06:01 | 0.00 | 0.00 | 7458.31 | 0.00 | 0.00 | 0.00 | 100.79 | 44.64 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3110.31 | 0.00 | -67.75 | -5063.56 |
PERIMETER_BOT_ZN_2 | 27-DEC-06:01 | 0.00 | 0.00 | 5694.17 | 0.00 | 0.00 | 0.00 | 63.75 | 28.26 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2116.60 | 0.00 | -45.42 | -4027.97 |
PERIMETER_BOT_ZN_1 | 27-DEC-07:10 | 0.00 | 0.00 | 9965.44 | 0.00 | 0.00 | 0.00 | 193.30 | 346.86 | 637.88 | 0.00 | 0.00 | 0.00 | 7646.34 | 0.00 | -3239.11 | 0.00 | -15550.71 | 0.00 |
PERIMETER_BOT_ZN_4 | 27-DEC-06:01 | 0.00 | 0.00 | 5536.58 | 0.00 | 0.00 | 0.00 | 63.68 | 28.26 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2081.07 | 0.00 | -45.44 | -3905.82 |
PERIMETER_MID_ZN_3 | 27-DEC-06:01 | 0.00 | 0.00 | 8351.93 | 0.00 | 0.00 | 0.00 | 104.99 | 44.64 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2992.34 | 0.00 | -101.55 | -6045.55 |
PERIMETER_MID_ZN_2 | 27-DEC-06:01 | 0.00 | 0.00 | 6772.78 | 0.00 | 0.00 | 0.00 | 66.88 | 28.26 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2022.98 | 0.00 | -67.67 | -5181.09 |
PERIMETER_MID_ZN_1 | 27-DEC-06:01 | 0.00 | 0.00 | 9294.49 | 0.00 | 0.00 | 0.00 | 104.59 | 44.64 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3068.83 | 0.00 | -102.35 | -6910.43 |
PERIMETER_MID_ZN_4 | 27-DEC-06:01 | 0.00 | 0.00 | 6616.31 | 0.00 | 0.00 | 0.00 | 66.73 | 28.26 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1987.65 | 0.00 | -67.81 | -5059.65 |
TOPFLOOR_PLENUM | 27-DEC-07:02 | 11077.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -160.71 | -10916.50 |
MIDFLOOR_PLENUM | 08-OCT-15:42 | 4542.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.34 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4609.57 |
FIRSTFLOOR_PLENUM | 27-DEC-08:06 | 4412.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -124.16 | -4287.99 |
Total Facility | 27-DEC-07:01 | 5496.04 | 5684.41 | 128705.41 | -5684.41 | 0.00 | 0.00 | 4478.70 | 8334.71 | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31909.00 | 0.00 | -19986.50 | -116218.15 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.9696 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.5035 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.3720 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.8283 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.9508 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.7076 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.9848 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0763 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.6860 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0755 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.9754 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0764 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1536 | 3.1536 | 0.6370 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3006 | 2.3006 | 0.6373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5187 | 2.5187 | 0.6372 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8577 | 0.8577 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7570 | 0.7570 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9465 | 0.9465 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8708 | 0.8708 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6903 | 0.6903 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6557 | 0.6557 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7705 | 0.7705 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6995 | 0.6995 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7371 | 0.7371 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7248 | 0.7248 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8269 | 0.8269 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7826 | 0.7826 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.9696 | 5.5035 | 5.9696 | 1.0763 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.3720 | 4.8283 | 5.3720 | 1.0755 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.9508 | 5.7076 | 5.9508 | 1.0764 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5768 | 1.5768 | 0.6370 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1503 | 1.1503 | 0.6373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2593 | 1.2593 | 0.6372 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4289 | 0.4289 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3785 | 0.3785 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4733 | 0.4733 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4354 | 0.4354 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3452 | 0.3452 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3278 | 0.3278 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3853 | 0.3853 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3498 | 0.3498 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3685 | 0.3685 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3624 | 0.3624 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4134 | 0.4134 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3913 | 0.3913 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.9848 | 1.0763 | 1.0763 | 1.0763 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.6860 | 1.0755 | 1.0755 | 1.0755 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.9754 | 1.0764 | 1.0764 | 1.0764 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 64.00 |
Number of hours cooling loads not met | 263.33 |
Number of hours not met | 327.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 21.57 | 88392.65 | 33.34 | 51446.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 309.45 | 76228.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 232.02 | 25003.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 50.37 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.69 | 838.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 125.81 | 34937.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 122.43 | 9951.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1456.47 |
Natural Gas | 0.00 | 155.77 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1612.24 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.57 |
Space Heating | 4.33 |
Space Cooling | 62.11 |
Fans (All) | 25.25 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 292.34 |
Subtotal | 292.34 |
Natural Gas [MJ/m2] | |
Space Heating | 6.69 |
Service Water Heating | 24.57 |
Miscellaneous (All) | 31.27 |
Subtotal | 31.27 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 14.39 |
Space Heating | 3.41 |
Space Cooling | 19.19 |
Fans (All) | 7.80 |
Service Water Heating | 7.59 |
Receptacle Equipment | 43.75 |
Miscellaneous | 3.86 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 925. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8714.67 | 45.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8750.33 | 9.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8756.00 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8730.83 | 29.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8670.33 | 89.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8705.67 | 54.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8664.83 | 95.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8697.00 | 63.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8728.33 | 31.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8692.67 | 67.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8748.83 | 11.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8679.83 | 80.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8717.67 | 42.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8673.33 | 86.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8507.17 | 252.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8507.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 252.83 | 0.00 | 0.00 | 0.00 |
Average | 8706.53 | 53.47 | 0.00 | 0.00 | 0.00 |
Sum | 156717.50 | 962.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128297.67 | 6.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 6.33 | 0.00 | 0.00 | 0.00 |
Average | 34142.98 | 0.35 | 0.00 | 0.00 | 0.00 |
Sum | 614573.67 | 6.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8491.17 | 268.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8592.83 | 167.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8715.00 | 45.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8518.33 | 241.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8450.00 | 310.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8481.17 | 278.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8444.17 | 315.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8575.67 | 184.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8458.67 | 301.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8487.67 | 272.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8437.67 | 322.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8493.67 | 266.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8422.17 | 337.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8451.33 | 308.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8416.17 | 343.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8496.33 | 263.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8617.83 | 142.17 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8661.50 | 98.50 | 0.00 | 0.00 | 0.00 |
Min | 8416.17 | 45.00 | 0.00 | 0.00 | 0.00 |
Max | 8715.00 | 343.83 | 0.00 | 0.00 | 0.00 |
Average | 8511.74 | 248.26 | 0.00 | 0.00 | 0.00 |
Sum | 153211.33 | 4468.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128173.33 | 130.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128243.33 | 60.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128258.67 | 45.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24888.17 | 20.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14007.67 | 8.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24886.67 | 22.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14006.83 | 9.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24902.00 | 7.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14013.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24785.00 | 124.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14015.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24899.17 | 9.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10132.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24899.00 | 10.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14015.17 | 0.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128258.67 | 130.67 | 0.00 | 0.00 | 0.00 |
Average | 34118.12 | 25.21 | 0.00 | 0.00 | 0.00 |
Sum | 614126.17 | 453.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:01
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141512E+11 | 17434.09 | 13-JAN-17:00 | 17.20 | 8.47 | 0.198438E+10 | 2606.66 | 02-JAN-10:09 | 17.20 | 8.47 |
February | 0.143405E+11 | 18724.81 | 23-FEB-09:00 | 12.20 | 6.66 | 0.180354E+10 | 2606.77 | 13-FEB-10:09 | 12.20 | 6.66 |
March | 0.186280E+11 | 19900.05 | 17-MAR-06:03 | 2.88 | -2.5 | 0.215678E+10 | 2606.63 | 17-MAR-09:20 | 7.57 | 1.14 |
April | 0.210550E+11 | 37388.98 | 17-APR-06:02 | 12.62 | 8.44 | 0.191784E+10 | 2606.70 | 27-APR-09:39 | 21.67 | 12.66 |
May | 0.255325E+11 | 42393.51 | 30-MAY-04:02 | 25.00 | 11.58 | 0.207795E+10 | 2606.70 | 08-MAY-09:09 | 25.00 | 11.58 |
June | 0.270480E+11 | 41689.87 | 09-JUN-05:02 | 23.80 | 14.62 | 0.207198E+10 | 2606.67 | 12-JUN-09:20 | 27.40 | 12.38 |
July | 0.265336E+11 | 40906.47 | 05-JUL-05:12 | 19.27 | 16.46 | 0.192635E+10 | 2705.83 | 20-JUL-15:20 | 24.97 | 22.86 |
August | 0.283713E+11 | 40359.12 | 14-AUG-05:12 | 17.40 | 16.29 | 0.216175E+10 | 2606.65 | 23-AUG-09:20 | 27.03 | 14.81 |
September | 0.253701E+11 | 40746.79 | 06-SEP-05:12 | 15.93 | 14.42 | 0.192026E+10 | 2606.67 | 12-SEP-09:20 | 25.17 | 14.97 |
October | 0.236450E+11 | 39849.21 | 23-OCT-05:12 | 12.80 | 9.86 | 0.199494E+10 | 2606.73 | 17-OCT-09:00 | 12.80 | 9.86 |
November | 0.186425E+11 | 37465.87 | 01-NOV-06:01 | 11.10 | 10.08 | 0.197214E+10 | 2606.64 | 16-NOV-10:20 | 8.33 | 4.44 |
December | 0.138621E+11 | 17325.27 | 29-DEC-08:03 | -0.1 | -2.4 | 0.191469E+10 | 2606.63 | 07-DEC-10:20 | -0.1 | -2.4 |
Annual Sum or Average | 0.257180E+12 | 0.239026E+11 | ||||||||
Minimum of Months | 0.138621E+11 | 17325.27 | -0.1 | -2.5 | 0.180354E+10 | 2606.63 | -0.1 | -2.4 | ||
Maximum of Months | 0.283713E+11 | 42393.51 | 25.00 | 16.46 | 0.216175E+10 | 2705.83 | 27.40 | 22.86 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.279186E+09 | 2941.69 | 12-JAN-15:20 | 18.90 | 10.07 | 0.00 | 0.00 | 01-JAN-00:10 | 18.90 | 10.07 |
February | 0.663030E+09 | 4550.15 | 22-FEB-14:10 | 21.78 | 7.94 | 0.00 | 0.00 | 01-FEB-00:10 | 21.78 | 7.94 |
March | 0.162979E+10 | 5699.85 | 16-MAR-14:20 | 22.80 | 9.14 | 0.00 | 0.00 | 01-MAR-00:10 | 22.80 | 9.14 |
April | 0.382519E+10 | 9017.87 | 19-APR-14:30 | 31.10 | 14.32 | 0.00 | 0.00 | 01-APR-00:10 | 31.10 | 14.32 |
May | 0.631054E+10 | 11026.77 | 30-MAY-14:20 | 34.40 | 17.58 | 0.00 | 0.00 | 01-MAY-00:10 | 34.40 | 17.58 |
June | 0.862497E+10 | 11548.52 | 15-JUN-14:40 | 38.13 | 15.82 | 0.00 | 0.00 | 01-JUN-00:10 | 38.13 | 15.82 |
July | 0.801427E+10 | 11959.50 | 03-JUL-13:00 | 36.70 | 18.58 | 0.00 | 0.00 | 01-JUL-00:10 | 36.70 | 18.58 |
August | 0.744550E+10 | 11450.40 | 07-AUG-14:50 | 35.00 | 18.73 | 0.00 | 0.00 | 01-AUG-00:10 | 35.00 | 18.73 |
September | 0.595385E+10 | 10055.62 | 19-SEP-15:00 | 33.30 | 16.48 | 0.00 | 0.00 | 01-SEP-00:10 | 33.30 | 16.48 |
October | 0.320583E+10 | 9138.42 | 03-OCT-14:30 | 32.25 | 19.38 | 0.00 | 0.00 | 01-OCT-00:10 | 32.25 | 19.38 |
November | 0.105721E+10 | 5072.01 | 03-NOV-15:20 | 23.50 | 13.53 | 0.00 | 0.00 | 01-NOV-00:10 | 23.50 | 13.53 |
December | 0.165499E+09 | 1234.04 | 09-DEC-13:40 | 17.40 | 7.21 | 0.00 | 0.00 | 01-DEC-00:10 | 17.40 | 7.21 |
Annual Sum or Average | 0.471749E+11 | 0.00 | ||||||||
Minimum of Months | 0.165499E+09 | 1234.04 | 17.40 | 7.21 | 0.00 | 0.00 | 17.40 | 7.21 | ||
Maximum of Months | 0.862497E+10 | 11959.50 | 38.13 | 19.38 | 0.00 | 0.00 | 38.13 | 19.38 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58035418.72 | 1796.38 | 28-JAN-06:01 | -3.3 | -6.4 | 0.00 | 0.00 | 01-JAN-00:10 | -3.3 | -6.4 |
February | 0.122701E+09 | 1698.68 | 10-FEB-07:02 | -2.8 | -5.3 | 0.00 | 0.00 | 01-FEB-00:10 | -2.8 | -5.3 |
March | 0.372570E+09 | 1838.94 | 16-MAR-16:00 | 22.20 | 8.37 | 0.00 | 0.00 | 01-MAR-00:10 | 22.20 | 8.37 |
April | 0.162893E+10 | 3419.91 | 21-APR-15:20 | 31.83 | 15.27 | 0.00 | 0.00 | 01-APR-00:10 | 31.83 | 15.27 |
May | 0.333867E+10 | 5338.91 | 30-MAY-16:00 | 33.90 | 17.46 | 0.00 | 0.00 | 01-MAY-00:10 | 33.90 | 17.46 |
June | 0.467148E+10 | 5819.35 | 19-JUN-10:10 | 29.18 | 18.04 | 0.00 | 0.00 | 01-JUN-00:10 | 29.18 | 18.04 |
July | 0.450209E+10 | 6289.73 | 03-JUL-10:10 | 32.67 | 18.80 | 0.00 | 0.00 | 01-JUL-00:10 | 32.67 | 18.80 |
August | 0.429867E+10 | 5861.83 | 07-AUG-10:10 | 31.78 | 18.15 | 0.00 | 0.00 | 01-AUG-00:10 | 31.78 | 18.15 |
September | 0.330906E+10 | 5179.58 | 05-SEP-06:15 | 17.43 | 15.20 | 0.00 | 0.00 | 01-SEP-00:10 | 17.43 | 15.20 |
October | 0.175651E+10 | 4038.45 | 05-OCT-16:00 | 31.10 | 17.21 | 0.00 | 0.00 | 01-OCT-00:10 | 31.10 | 17.21 |
November | 0.313525E+09 | 2081.92 | 10-NOV-15:50 | 15.10 | 9.99 | 0.00 | 0.00 | 01-NOV-00:10 | 15.10 | 9.99 |
December | 35895806.21 | 1646.80 | 30-DEC-06:01 | -2.9 | -4.1 | 0.00 | 0.00 | 01-DEC-00:10 | -2.9 | -4.1 |
Annual Sum or Average | 0.244081E+11 | 0.00 | ||||||||
Minimum of Months | 35895806.21 | 1646.80 | -3.3 | -6.4 | 0.00 | 0.00 | -3.3 | -6.4 | ||
Maximum of Months | 0.467148E+10 | 6289.73 | 33.90 | 18.80 | 0.00 | 0.00 | 33.90 | 18.80 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177841E+09 | 2124.58 | 27-JAN-07:01 | -4.3 | -7.5 | 0.00 | 0.00 | 01-JAN-00:10 | -4.3 | -7.5 |
February | 0.365751E+09 | 2494.60 | 10-FEB-07:02 | -2.8 | -5.3 | 0.00 | 0.00 | 01-FEB-00:10 | -2.8 | -5.3 |
March | 0.841422E+09 | 2217.24 | 02-MAR-07:02 | -1.6 | -4.8 | 0.00 | 0.00 | 01-MAR-00:10 | -1.6 | -4.8 |
April | 0.212834E+10 | 3608.30 | 21-APR-15:10 | 32.02 | 15.38 | 0.00 | 0.00 | 01-APR-00:10 | 32.02 | 15.38 |
May | 0.375766E+10 | 5380.66 | 30-MAY-12:10 | 31.20 | 15.49 | 0.00 | 0.00 | 01-MAY-00:10 | 31.20 | 15.49 |
June | 0.495823E+10 | 6300.21 | 05-JUN-12:07 | 34.68 | 16.27 | 0.00 | 0.00 | 01-JUN-00:10 | 34.68 | 16.27 |
July | 0.488903E+10 | 7105.09 | 03-JUL-12:08 | 35.78 | 18.54 | 0.00 | 0.00 | 01-JUL-00:10 | 35.78 | 18.54 |
August | 0.493546E+10 | 6093.96 | 07-AUG-06:10 | 25.18 | 16.26 | 0.00 | 0.00 | 01-AUG-00:10 | 25.18 | 16.26 |
September | 0.415995E+10 | 6255.15 | 05-SEP-06:15 | 17.43 | 15.20 | 0.00 | 0.00 | 01-SEP-00:10 | 17.43 | 15.20 |
October | 0.275207E+10 | 4353.04 | 02-OCT-12:50 | 26.70 | 16.73 | 0.00 | 0.00 | 01-OCT-00:10 | 26.70 | 16.73 |
November | 0.979770E+09 | 2891.25 | 10-NOV-16:10 | 14.90 | 9.82 | 0.00 | 0.00 | 01-NOV-00:10 | 14.90 | 9.82 |
December | 0.112286E+09 | 2304.17 | 22-DEC-07:02 | -3.0 | -4.9 | 0.00 | 0.00 | 01-DEC-00:10 | -3.0 | -4.9 |
Annual Sum or Average | 0.300578E+11 | 0.00 | ||||||||
Minimum of Months | 0.112286E+09 | 2124.58 | -4.3 | -7.5 | 0.00 | 0.00 | -4.3 | -7.5 | ||
Maximum of Months | 0.495823E+10 | 7105.09 | 35.78 | 18.54 | 0.00 | 0.00 | 35.78 | 18.54 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.747313E+10 | 9583.69 | 13-JAN-17:00 | 17.20 | 8.47 | 0.188819E+10 | 2606.62 | 12-JAN-10:20 | 17.20 | 8.47 |
February | 0.791709E+10 | 11219.27 | 22-FEB-17:00 | 21.70 | 8.09 | 0.175689E+10 | 2607.88 | 01-FEB-14:09 | 21.70 | 8.09 |
March | 0.108170E+11 | 12803.91 | 16-MAR-16:00 | 22.20 | 8.37 | 0.212809E+10 | 2606.62 | 20-MAR-09:20 | 10.93 | 4.72 |
April | 0.138842E+11 | 23528.41 | 17-APR-06:02 | 12.62 | 8.44 | 0.191017E+10 | 2606.69 | 27-APR-09:39 | 21.67 | 12.66 |
May | 0.180356E+11 | 29988.34 | 22-MAY-05:12 | 18.17 | 14.05 | 0.207461E+10 | 2606.68 | 08-MAY-09:09 | 18.17 | 14.05 |
June | 0.199009E+11 | 32910.93 | 19-JUN-05:14 | 22.80 | 15.92 | 0.207012E+10 | 2606.67 | 12-JUN-09:20 | 22.80 | 15.92 |
July | 0.196421E+11 | 33057.83 | 17-JUL-05:14 | 20.40 | 20.09 | 0.192395E+10 | 2655.47 | 20-JUL-15:20 | 24.97 | 22.86 |
August | 0.201952E+11 | 30413.32 | 14-AUG-05:12 | 17.40 | 16.29 | 0.215917E+10 | 2606.65 | 28-AUG-09:20 | 25.57 | 16.47 |
September | 0.173777E+11 | 30857.35 | 05-SEP-05:12 | 16.30 | 15.51 | 0.191668E+10 | 2606.68 | 05-SEP-09:20 | 23.53 | 17.86 |
October | 0.148916E+11 | 28608.78 | 02-OCT-04:02 | 24.82 | 15.04 | 0.198716E+10 | 2606.69 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.995634E+10 | 14129.20 | 10-NOV-16:50 | 14.50 | 9.32 | 0.192871E+10 | 2606.63 | 16-NOV-10:20 | 8.33 | 4.44 |
December | 0.712444E+10 | 8425.94 | 15-DEC-17:00 | 15.00 | 5.87 | 0.180235E+10 | 2606.58 | 14-DEC-10:00 | 15.00 | 5.87 |
Annual Sum or Average | 0.167215E+12 | 0.235461E+11 | ||||||||
Minimum of Months | 0.712444E+10 | 8425.94 | 12.62 | 5.87 | 0.175689E+10 | 2606.58 | 8.33 | 4.44 | ||
Maximum of Months | 0.201952E+11 | 33057.83 | 24.82 | 20.09 | 0.215917E+10 | 2655.47 | 25.57 | 22.86 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.613937E+10 | 8735.82 | 12-JAN-16:50 | 17.98 | 9.87 | 0.174953E+10 | 2606.60 | 12-JAN-14:20 | 17.98 | 9.87 |
February | 0.678905E+10 | 10792.39 | 22-FEB-15:30 | 22.50 | 8.27 | 0.166185E+10 | 2606.60 | 08-FEB-10:20 | 22.50 | 8.27 |
March | 0.959495E+10 | 13881.83 | 16-MAR-16:00 | 22.20 | 8.37 | 0.206233E+10 | 2606.61 | 22-MAR-09:30 | 16.65 | 6.43 |
April | 0.134918E+11 | 16875.54 | 28-APR-15:40 | 28.50 | 13.78 | 0.189694E+10 | 2606.68 | 27-APR-09:39 | 28.50 | 13.78 |
May | 0.185252E+11 | 33421.66 | 30-MAY-04:02 | 25.00 | 11.58 | 0.207208E+10 | 2606.67 | 08-MAY-09:09 | 25.00 | 11.58 |
June | 0.214548E+11 | 32498.26 | 09-JUN-05:02 | 23.80 | 14.62 | 0.207011E+10 | 2606.67 | 12-JUN-09:20 | 27.40 | 12.38 |
July | 0.210544E+11 | 33034.47 | 10-JUL-04:03 | 24.32 | 16.38 | 0.192493E+10 | 2700.51 | 20-JUL-15:30 | 25.25 | 22.87 |
August | 0.210002E+11 | 33205.74 | 14-AUG-05:12 | 17.40 | 16.29 | 0.215896E+10 | 2606.64 | 23-AUG-09:20 | 27.03 | 14.81 |
September | 0.172413E+11 | 33074.18 | 05-SEP-05:12 | 16.30 | 15.51 | 0.191387E+10 | 2606.66 | 12-SEP-09:20 | 25.17 | 14.97 |
October | 0.134875E+11 | 32105.22 | 02-OCT-04:02 | 24.82 | 15.04 | 0.197082E+10 | 2606.66 | 02-OCT-09:09 | 22.35 | 16.60 |
November | 0.818779E+10 | 13894.29 | 10-NOV-15:00 | 15.60 | 10.20 | 0.184415E+10 | 2606.64 | 01-NOV-09:09 | 15.60 | 10.20 |
December | 0.567578E+10 | 6784.96 | 15-DEC-16:40 | 15.20 | 5.96 | 0.165191E+10 | 2606.54 | 01-DEC-14:39 | 15.20 | 5.96 |
Annual Sum or Average | 0.162642E+12 | 0.229775E+11 | ||||||||
Minimum of Months | 0.567578E+10 | 6784.96 | 15.20 | 5.96 | 0.165191E+10 | 2606.54 | 15.20 | 5.96 | ||
Maximum of Months | 0.214548E+11 | 33421.66 | 28.50 | 16.38 | 0.215896E+10 | 2700.51 | 28.50 | 22.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.673526E+09 | 1242.31 | 12-JAN-14:30 | 18.60 | 9.87 | 0.329444E+09 | 534.38 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.948014E+09 | 2095.82 | 22-FEB-15:00 | 22.20 | 8.00 | 0.316529E+09 | 549.48 | 07-FEB-14:20 | 22.20 | 8.00 |
March | 0.163273E+10 | 3311.92 | 22-MAR-14:30 | 24.15 | 9.01 | 0.404608E+09 | 549.49 | 09-MAR-14:20 | 24.15 | 9.01 |
April | 0.309818E+10 | 5701.50 | 21-APR-15:00 | 32.20 | 15.49 | 0.390946E+09 | 549.50 | 27-APR-09:20 | 21.13 | 12.20 |
May | 0.527824E+10 | 10633.99 | 21-MAY-15:52 | 34.40 | 18.34 | 0.435875E+09 | 549.50 | 19-MAY-09:20 | 34.40 | 18.34 |
June | 0.705945E+10 | 12439.52 | 18-JUN-15:42 | 37.12 | 16.83 | 0.436823E+09 | 549.51 | 12-JUN-09:20 | 37.12 | 16.83 |
July | 0.673923E+10 | 12573.56 | 02-JUL-16:12 | 38.13 | 18.77 | 0.406456E+09 | 558.66 | 20-JUL-15:30 | 25.25 | 22.87 |
August | 0.608147E+10 | 12307.43 | 06-AUG-16:52 | 36.10 | 18.82 | 0.455077E+09 | 549.50 | 23-AUG-09:20 | 27.03 | 14.81 |
September | 0.449281E+10 | 6807.87 | 04-SEP-13:22 | 30.60 | 18.77 | 0.401480E+09 | 549.50 | 26-SEP-13:20 | 25.97 | 15.08 |
October | 0.276871E+10 | 7462.99 | 02-OCT-04:02 | 24.82 | 15.04 | 0.404187E+09 | 549.50 | 02-OCT-09:09 | 22.35 | 16.60 |
November | 0.122665E+10 | 2695.63 | 09-NOV-15:30 | 23.30 | 12.82 | 0.358669E+09 | 549.49 | 10-NOV-10:20 | 19.80 | 12.11 |
December | 0.550056E+09 | 1077.12 | 08-DEC-15:10 | 17.20 | 7.54 | 0.311272E+09 | 505.12 | 08-DEC-14:00 | 17.20 | 7.54 |
Annual Sum or Average | 0.405491E+11 | 0.465137E+10 | ||||||||
Minimum of Months | 0.550056E+09 | 1077.12 | 17.20 | 7.54 | 0.311272E+09 | 505.12 | 17.20 | 7.54 | ||
Maximum of Months | 0.705945E+10 | 12573.56 | 38.13 | 18.82 | 0.455077E+09 | 558.66 | 37.12 | 22.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.647170E+09 | 1404.08 | 04-JAN-10:10 | 9.60 | 3.11 | 0.230231E+09 | 347.87 | 31-JAN-10:20 | 12.07 | 4.59 |
February | 0.954385E+09 | 2923.53 | 21-FEB-10:30 | 18.35 | 7.04 | 0.222199E+09 | 347.87 | 10-FEB-10:00 | 18.35 | 7.04 |
March | 0.189005E+10 | 4179.46 | 16-MAR-10:10 | 19.18 | 7.83 | 0.275127E+09 | 347.88 | 06-MAR-10:20 | 19.18 | 7.83 |
April | 0.360741E+10 | 10584.07 | 30-APR-10:53 | 25.00 | 12.86 | 0.254076E+09 | 347.90 | 19-APR-09:09 | 25.00 | 12.86 |
May | 0.536063E+10 | 11094.74 | 29-MAY-09:12 | 23.13 | 15.75 | 0.277068E+09 | 348.27 | 17-MAY-09:50 | 23.13 | 15.75 |
June | 0.651874E+10 | 11498.76 | 18-JUN-09:42 | 31.13 | 16.72 | 0.276883E+09 | 348.24 | 27-JUN-09:00 | 25.60 | 15.68 |
July | 0.608633E+10 | 11566.87 | 02-JUL-09:32 | 30.37 | 19.85 | 0.257698E+09 | 348.35 | 03-JUL-09:00 | 32.20 | 18.73 |
August | 0.579862E+10 | 11535.37 | 06-AUG-09:32 | 29.83 | 17.77 | 0.288497E+09 | 348.22 | 01-AUG-09:00 | 29.83 | 17.77 |
September | 0.470477E+10 | 11875.68 | 17-SEP-09:12 | 25.00 | 16.09 | 0.255608E+09 | 348.39 | 11-SEP-09:00 | 25.00 | 16.09 |
October | 0.281700E+10 | 8720.85 | 01-OCT-09:32 | 23.67 | 13.35 | 0.261388E+09 | 347.89 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.123577E+10 | 4562.94 | 10-NOV-09:20 | 18.67 | 11.91 | 0.244879E+09 | 347.89 | 21-NOV-10:09 | 11.57 | 3.72 |
December | 0.554665E+09 | 777.56 | 01-DEC-10:40 | 13.33 | 5.28 | 0.214585E+09 | 347.86 | 01-DEC-10:50 | 13.62 | 5.49 |
Annual Sum or Average | 0.401755E+11 | 0.305824E+10 | ||||||||
Minimum of Months | 0.554665E+09 | 777.56 | 9.60 | 3.11 | 0.214585E+09 | 347.86 | 11.57 | 3.72 | ||
Maximum of Months | 0.651874E+10 | 11875.68 | 31.13 | 19.85 | 0.288497E+09 | 348.39 | 32.20 | 18.73 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.293439E+10 | 9318.75 | 12-JAN-14:05 | 18.40 | 9.78 | 0.387081E+09 | 549.56 | 12-JAN-14:00 | 18.90 | 10.02 |
February | 0.304000E+10 | 14218.01 | 20-FEB-14:13 | 22.57 | 8.60 | 0.355054E+09 | 549.77 | 22-FEB-14:09 | 21.78 | 7.94 |
March | 0.380153E+10 | 8634.09 | 16-MAR-13:30 | 22.50 | 9.16 | 0.428219E+09 | 549.70 | 16-MAR-13:00 | 22.80 | 9.34 |
April | 0.470535E+10 | 14217.50 | 30-APR-13:32 | 29.40 | 12.46 | 0.394284E+09 | 549.78 | 21-APR-13:39 | 29.40 | 12.46 |
May | 0.579427E+10 | 12364.77 | 21-MAY-15:12 | 34.40 | 17.95 | 0.435462E+09 | 549.50 | 03-MAY-13:00 | 34.40 | 17.95 |
June | 0.697085E+10 | 13655.99 | 18-JUN-15:42 | 37.12 | 16.83 | 0.436672E+09 | 549.50 | 12-JUN-09:20 | 37.12 | 16.83 |
July | 0.691530E+10 | 14184.06 | 30-JUL-12:53 | 30.60 | 19.90 | 0.406375E+09 | 554.73 | 20-JUL-15:20 | 30.60 | 19.90 |
August | 0.742860E+10 | 14131.96 | 13-AUG-13:23 | 30.55 | 19.31 | 0.455246E+09 | 550.27 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.743442E+10 | 14923.53 | 04-SEP-13:22 | 30.60 | 18.77 | 0.402903E+09 | 549.91 | 15-SEP-13:00 | 32.20 | 17.96 |
October | 0.647583E+10 | 15634.21 | 01-OCT-12:12 | 30.37 | 14.43 | 0.412667E+09 | 559.15 | 03-OCT-13:39 | 32.07 | 19.44 |
November | 0.441771E+10 | 14113.40 | 11-NOV-11:43 | 17.02 | 7.80 | 0.392623E+09 | 549.90 | 08-NOV-14:50 | 17.02 | 7.80 |
December | 0.266157E+10 | 7432.54 | 07-DEC-14:10 | 15.68 | 6.76 | 0.371078E+09 | 549.49 | 01-DEC-14:09 | 15.68 | 6.76 |
Annual Sum or Average | 0.625798E+11 | 0.487766E+10 | ||||||||
Minimum of Months | 0.266157E+10 | 7432.54 | 15.68 | 6.76 | 0.355054E+09 | 549.49 | 15.68 | 6.76 | ||
Maximum of Months | 0.743442E+10 | 15634.21 | 37.12 | 19.90 | 0.455246E+09 | 559.15 | 37.12 | 19.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.766081E+09 | 3640.17 | 12-JAN-15:30 | 18.90 | 10.10 | 0.221362E+09 | 347.84 | 13-JAN-14:20 | 17.97 | 8.78 |
February | 0.100803E+10 | 6061.39 | 20-FEB-16:13 | 22.93 | 8.52 | 0.208140E+09 | 347.84 | 14-FEB-14:20 | 22.93 | 8.52 |
March | 0.198421E+10 | 6168.01 | 14-MAR-16:00 | 24.40 | 10.33 | 0.260450E+09 | 347.85 | 09-MAR-14:20 | 24.40 | 10.33 |
April | 0.348542E+10 | 14363.66 | 16-APR-16:11 | 30.00 | 11.64 | 0.248386E+09 | 347.86 | 27-APR-09:20 | 21.13 | 12.20 |
May | 0.519096E+10 | 13718.96 | 29-MAY-16:32 | 32.97 | 16.56 | 0.275979E+09 | 347.86 | 19-MAY-09:20 | 32.97 | 16.56 |
June | 0.624120E+10 | 13687.06 | 25-JUN-16:32 | 31.50 | 16.81 | 0.276689E+09 | 347.86 | 12-JUN-09:20 | 31.50 | 16.81 |
July | 0.583106E+10 | 13633.58 | 09-JUL-16:32 | 32.97 | 19.28 | 0.257450E+09 | 347.86 | 03-JUL-09:20 | 32.97 | 19.28 |
August | 0.556603E+10 | 13691.28 | 06-AUG-16:52 | 36.10 | 18.82 | 0.288321E+09 | 347.85 | 23-AUG-09:20 | 27.03 | 14.81 |
September | 0.464710E+10 | 13422.32 | 17-SEP-15:52 | 32.80 | 15.88 | 0.254702E+09 | 347.86 | 26-SEP-13:20 | 25.97 | 15.08 |
October | 0.303852E+10 | 13685.84 | 01-OCT-14:52 | 32.80 | 15.90 | 0.257629E+09 | 347.85 | 02-OCT-09:09 | 22.35 | 16.60 |
November | 0.147555E+10 | 5667.70 | 09-NOV-15:30 | 23.30 | 12.82 | 0.233746E+09 | 347.85 | 10-NOV-10:20 | 19.80 | 12.11 |
December | 0.617405E+09 | 2691.52 | 15-DEC-15:50 | 15.60 | 6.12 | 0.210964E+09 | 347.83 | 01-DEC-14:00 | 15.60 | 6.12 |
Annual Sum or Average | 0.398516E+11 | 0.299382E+10 | ||||||||
Minimum of Months | 0.617405E+09 | 2691.52 | 15.60 | 6.12 | 0.208140E+09 | 347.83 | 15.60 | 6.12 | ||
Maximum of Months | 0.624120E+10 | 14363.66 | 36.10 | 19.28 | 0.288321E+09 | 347.86 | 32.97 | 19.28 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.980154E+09 | 1123.74 | 13-JAN-15:00 | 18.30 | 8.81 | 0.337849E+09 | 521.76 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.999106E+09 | 1201.42 | 22-FEB-13:30 | 21.15 | 7.71 | 0.315698E+09 | 548.75 | 23-FEB-14:50 | 21.28 | 7.21 |
March | 0.136555E+10 | 1523.48 | 22-MAR-14:40 | 24.07 | 8.96 | 0.396575E+09 | 549.49 | 09-MAR-14:20 | 24.07 | 8.96 |
April | 0.213967E+10 | 3788.54 | 21-APR-15:20 | 31.83 | 15.27 | 0.390188E+09 | 549.50 | 27-APR-09:20 | 21.13 | 12.20 |
May | 0.388028E+10 | 5078.84 | 30-MAY-15:20 | 34.23 | 17.67 | 0.435527E+09 | 549.50 | 19-MAY-09:20 | 34.23 | 17.67 |
June | 0.553495E+10 | 7712.17 | 19-JUN-06:03 | 23.07 | 16.06 | 0.436211E+09 | 549.50 | 12-JUN-09:20 | 23.07 | 16.06 |
July | 0.583733E+10 | 8070.51 | 03-JUL-06:03 | 26.88 | 16.13 | 0.406026E+09 | 557.59 | 20-JUL-15:20 | 24.97 | 22.86 |
August | 0.578069E+10 | 8074.45 | 27-AUG-17:01 | 34.72 | 16.31 | 0.455348E+09 | 549.50 | 23-AUG-09:20 | 34.72 | 16.31 |
September | 0.468517E+10 | 7513.78 | 11-SEP-06:02 | 16.05 | 10.85 | 0.403712E+09 | 549.50 | 12-SEP-09:20 | 25.17 | 14.97 |
October | 0.306647E+10 | 5670.94 | 02-OCT-06:03 | 22.70 | 15.09 | 0.415519E+09 | 549.50 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.157561E+10 | 2403.29 | 09-NOV-16:00 | 23.30 | 13.01 | 0.382085E+09 | 549.49 | 09-NOV-10:20 | 23.30 | 13.01 |
December | 0.982366E+09 | 1178.69 | 07-DEC-13:07 | 14.60 | 6.36 | 0.327152E+09 | 515.26 | 01-DEC-14:39 | 14.60 | 6.36 |
Annual Sum or Average | 0.368273E+11 | 0.470189E+10 | ||||||||
Minimum of Months | 0.980154E+09 | 1123.74 | 14.60 | 6.36 | 0.315698E+09 | 515.26 | 14.60 | 6.36 | ||
Maximum of Months | 0.583733E+10 | 8074.45 | 34.72 | 17.67 | 0.455348E+09 | 557.59 | 34.72 | 22.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.844083E+09 | 1484.60 | 04-JAN-10:10 | 9.60 | 3.11 | 0.240726E+09 | 347.88 | 11-JAN-10:20 | 8.00 | 1.33 |
February | 0.977997E+09 | 2540.11 | 21-FEB-10:30 | 18.35 | 7.04 | 0.225851E+09 | 347.87 | 24-FEB-10:20 | 7.77 | 2.42 |
March | 0.155172E+10 | 3018.27 | 31-MAR-09:40 | 17.60 | 6.03 | 0.276669E+09 | 347.88 | 27-MAR-09:20 | 17.60 | 6.03 |
April | 0.282792E+10 | 6952.10 | 30-APR-10:53 | 25.00 | 12.86 | 0.254581E+09 | 347.89 | 27-APR-09:39 | 25.00 | 12.86 |
May | 0.440369E+10 | 7626.66 | 29-MAY-09:12 | 23.13 | 15.75 | 0.277165E+09 | 348.23 | 15-MAY-09:00 | 23.13 | 15.75 |
June | 0.550297E+10 | 8759.36 | 18-JUN-09:42 | 31.13 | 16.72 | 0.276780E+09 | 348.11 | 09-JUN-09:00 | 31.13 | 16.72 |
July | 0.550250E+10 | 10447.76 | 04-JUL-09:32 | 27.57 | 18.80 | 0.257699E+09 | 352.67 | 21-JUL-10:30 | 24.75 | 21.90 |
August | 0.568750E+10 | 10307.50 | 20-AUG-09:52 | 28.30 | 16.66 | 0.288783E+09 | 348.09 | 04-AUG-09:00 | 28.30 | 16.66 |
September | 0.496542E+10 | 10139.12 | 17-SEP-10:02 | 27.77 | 16.01 | 0.256349E+09 | 348.25 | 15-SEP-09:50 | 27.77 | 16.01 |
October | 0.322658E+10 | 5749.83 | 05-OCT-09:10 | 25.37 | 18.00 | 0.265067E+09 | 347.89 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.166304E+10 | 4331.92 | 10-NOV-09:10 | 18.48 | 11.84 | 0.254858E+09 | 347.88 | 09-NOV-10:20 | 18.48 | 11.84 |
December | 0.830009E+09 | 1350.74 | 01-DEC-10:10 | 12.48 | 4.67 | 0.231708E+09 | 347.87 | 07-DEC-10:20 | 7.80 | 2.37 |
Annual Sum or Average | 0.379834E+11 | 0.310624E+10 | ||||||||
Minimum of Months | 0.830009E+09 | 1350.74 | 9.60 | 3.11 | 0.225851E+09 | 347.87 | 7.77 | 1.33 | ||
Maximum of Months | 0.568750E+10 | 10447.76 | 31.13 | 18.80 | 0.288783E+09 | 352.67 | 31.13 | 21.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226334E+10 | 7046.76 | 12-JAN-14:30 | 18.60 | 9.87 | 0.382789E+09 | 549.59 | 12-JAN-14:50 | 18.80 | 9.97 |
February | 0.203802E+10 | 7409.78 | 20-FEB-14:02 | 22.38 | 8.53 | 0.347920E+09 | 549.78 | 22-FEB-14:09 | 21.78 | 7.94 |
March | 0.232504E+10 | 5848.41 | 22-MAR-13:10 | 24.90 | 9.24 | 0.417694E+09 | 549.51 | 27-MAR-13:20 | 12.07 | 5.80 |
April | 0.334666E+10 | 9207.18 | 19-APR-12:00 | 30.60 | 14.04 | 0.388378E+09 | 549.51 | 24-APR-13:30 | 24.70 | 9.91 |
May | 0.482759E+10 | 10089.73 | 30-MAY-16:10 | 33.62 | 17.22 | 0.432414E+09 | 565.86 | 19-MAY-12:09 | 33.62 | 17.22 |
June | 0.655368E+10 | 10596.01 | 02-JUN-16:50 | 38.90 | 16.18 | 0.437238E+09 | 611.01 | 15-JUN-12:09 | 36.10 | 14.46 |
July | 0.690361E+10 | 10684.57 | 03-JUL-17:00 | 38.30 | 18.83 | 0.407244E+09 | 620.78 | 03-JUL-12:09 | 38.30 | 18.83 |
August | 0.781515E+10 | 11508.02 | 27-AUG-13:43 | 34.40 | 16.35 | 0.456425E+09 | 616.03 | 07-AUG-12:09 | 34.40 | 16.35 |
September | 0.806147E+10 | 12122.25 | 17-SEP-13:22 | 31.95 | 15.93 | 0.406038E+09 | 605.66 | 19-SEP-12:09 | 31.88 | 16.39 |
October | 0.667629E+10 | 12200.48 | 29-OCT-15:12 | 23.70 | 11.46 | 0.417574E+09 | 592.48 | 03-OCT-12:09 | 23.70 | 11.46 |
November | 0.433069E+10 | 11751.55 | 11-NOV-14:53 | 18.90 | 8.38 | 0.396794E+09 | 561.81 | 09-NOV-14:09 | 18.90 | 8.38 |
December | 0.218570E+10 | 8100.51 | 07-DEC-13:07 | 14.60 | 6.36 | 0.368183E+09 | 549.50 | 27-DEC-14:09 | 6.78 | 2.08 |
Annual Sum or Average | 0.573272E+11 | 0.485869E+10 | ||||||||
Minimum of Months | 0.203802E+10 | 5848.41 | 14.60 | 6.36 | 0.347920E+09 | 549.50 | 6.78 | 2.08 | ||
Maximum of Months | 0.806147E+10 | 12200.48 | 38.90 | 18.83 | 0.456425E+09 | 620.78 | 38.30 | 18.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.941899E+09 | 2656.69 | 30-JAN-16:30 | 15.60 | 6.05 | 0.230624E+09 | 347.84 | 13-JAN-14:20 | 15.60 | 6.05 |
February | 0.940233E+09 | 3822.71 | 21-FEB-16:50 | 22.30 | 7.87 | 0.212840E+09 | 347.84 | 24-FEB-14:20 | 12.40 | 3.64 |
March | 0.150023E+10 | 3905.22 | 14-MAR-16:00 | 24.40 | 10.33 | 0.265080E+09 | 347.84 | 10-MAR-14:20 | 24.40 | 10.33 |
April | 0.258766E+10 | 10984.39 | 16-APR-16:11 | 30.00 | 11.64 | 0.251309E+09 | 347.86 | 27-APR-09:20 | 21.13 | 12.20 |
May | 0.418467E+10 | 11061.49 | 07-MAY-16:31 | 29.07 | 14.12 | 0.276686E+09 | 347.86 | 19-MAY-09:20 | 26.83 | 16.66 |
June | 0.518270E+10 | 10674.28 | 25-JUN-17:12 | 31.50 | 16.72 | 0.276614E+09 | 347.86 | 12-JUN-09:20 | 31.50 | 16.72 |
July | 0.520483E+10 | 10713.06 | 04-JUL-15:31 | 34.23 | 18.80 | 0.257464E+09 | 347.88 | 21-JUL-09:00 | 23.90 | 21.52 |
August | 0.541316E+10 | 11511.64 | 13-AUG-16:31 | 31.30 | 18.50 | 0.288730E+09 | 347.85 | 23-AUG-09:20 | 27.03 | 14.81 |
September | 0.483964E+10 | 11242.41 | 17-SEP-16:42 | 31.88 | 15.56 | 0.256274E+09 | 347.86 | 12-SEP-09:20 | 31.88 | 15.56 |
October | 0.337508E+10 | 10876.31 | 08-OCT-16:22 | 25.25 | 17.49 | 0.265063E+09 | 347.86 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.175776E+10 | 5070.93 | 03-NOV-16:00 | 23.90 | 13.45 | 0.250692E+09 | 347.85 | 24-NOV-10:20 | 17.77 | 6.76 |
December | 0.905293E+09 | 2497.30 | 15-DEC-16:10 | 15.50 | 6.10 | 0.222635E+09 | 347.84 | 01-DEC-14:00 | 15.50 | 6.10 |
Annual Sum or Average | 0.368331E+11 | 0.305401E+10 | ||||||||
Minimum of Months | 0.905293E+09 | 2497.30 | 15.50 | 6.05 | 0.212840E+09 | 347.84 | 12.40 | 3.64 | ||
Maximum of Months | 0.541316E+10 | 11511.64 | 34.23 | 18.80 | 0.288730E+09 | 347.88 | 31.88 | 21.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103287E+10 | 1407.17 | 12-JAN-14:10 | 18.40 | 9.78 | 0.344088E+09 | 549.47 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.120485E+10 | 2254.28 | 23-FEB-14:30 | 21.65 | 7.41 | 0.331245E+09 | 549.48 | 07-FEB-14:20 | 21.65 | 7.41 |
March | 0.183527E+10 | 3145.77 | 22-MAR-14:30 | 24.15 | 9.01 | 0.420246E+09 | 549.49 | 22-MAR-13:20 | 24.15 | 9.01 |
April | 0.308893E+10 | 5125.91 | 21-APR-15:00 | 32.20 | 15.49 | 0.397024E+09 | 549.50 | 27-APR-09:20 | 21.13 | 12.20 |
May | 0.505806E+10 | 10476.00 | 29-MAY-17:01 | 32.52 | 16.27 | 0.436993E+09 | 549.50 | 08-MAY-09:09 | 32.52 | 16.27 |
June | 0.656870E+10 | 10909.02 | 18-JUN-16:11 | 37.20 | 16.86 | 0.436917E+09 | 549.51 | 12-JUN-09:20 | 37.20 | 16.86 |
July | 0.626281E+10 | 10610.17 | 02-JUL-16:12 | 38.13 | 18.77 | 0.406436E+09 | 558.88 | 20-JUL-15:20 | 24.97 | 22.86 |
August | 0.578446E+10 | 10488.93 | 13-AUG-16:31 | 31.30 | 18.50 | 0.455393E+09 | 549.50 | 28-AUG-09:20 | 25.57 | 16.47 |
September | 0.442208E+10 | 7294.12 | 10-SEP-15:51 | 31.10 | 16.68 | 0.403177E+09 | 549.51 | 05-SEP-09:20 | 31.10 | 16.68 |
October | 0.293112E+10 | 7147.83 | 02-OCT-04:02 | 24.82 | 15.04 | 0.412702E+09 | 549.50 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.151467E+10 | 2689.13 | 09-NOV-16:00 | 23.30 | 13.01 | 0.375986E+09 | 549.49 | 09-NOV-10:20 | 23.30 | 13.01 |
December | 0.899957E+09 | 1135.36 | 08-DEC-15:10 | 17.20 | 7.54 | 0.325382E+09 | 528.03 | 08-DEC-14:00 | 17.20 | 7.54 |
Annual Sum or Average | 0.406038E+11 | 0.474559E+10 | ||||||||
Minimum of Months | 0.899957E+09 | 1135.36 | 17.20 | 7.41 | 0.325382E+09 | 528.03 | 17.20 | 7.41 | ||
Maximum of Months | 0.656870E+10 | 10909.02 | 38.13 | 18.77 | 0.455393E+09 | 558.88 | 37.20 | 22.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.708994E+09 | 3817.40 | 31-JAN-13:02 | 14.50 | 4.97 | 0.177809E+09 | 356.46 | 19-JAN-11:09 | 14.50 | 4.97 |
February | 0.105003E+10 | 4806.48 | 08-FEB-13:02 | 12.20 | 4.98 | 0.168786E+09 | 356.45 | 02-FEB-11:09 | 12.20 | 4.98 |
March | 0.194890E+10 | 5431.31 | 16-MAR-10:05 | 19.18 | 7.83 | 0.206070E+09 | 356.46 | 22-MAR-12:09 | 24.50 | 9.37 |
April | 0.347524E+10 | 11325.61 | 30-APR-08:62 | 18.58 | 12.41 | 0.189057E+09 | 356.47 | 14-APR-10:09 | 18.58 | 12.41 |
May | 0.498969E+10 | 11762.45 | 29-MAY-09:02 | 22.67 | 15.59 | 0.205850E+09 | 356.46 | 08-MAY-10:09 | 22.67 | 15.59 |
June | 0.597977E+10 | 11723.82 | 04-JUN-09:02 | 26.38 | 17.02 | 0.205450E+09 | 356.47 | 12-JUN-10:09 | 30.10 | 14.01 |
July | 0.556995E+10 | 11873.94 | 04-JUL-08:52 | 26.10 | 18.11 | 0.191841E+09 | 356.47 | 03-JUL-10:09 | 26.10 | 18.11 |
August | 0.535695E+10 | 11629.79 | 20-AUG-09:12 | 26.83 | 16.55 | 0.214018E+09 | 356.47 | 30-AUG-10:09 | 25.18 | 16.45 |
September | 0.443761E+10 | 11800.09 | 04-SEP-08:32 | 22.57 | 17.97 | 0.190086E+09 | 356.46 | 12-SEP-10:09 | 26.88 | 15.77 |
October | 0.279775E+10 | 6942.49 | 05-OCT-10:05 | 27.30 | 18.49 | 0.195445E+09 | 356.47 | 17-OCT-10:09 | 21.47 | 16.47 |
November | 0.137588E+10 | 4992.14 | 10-NOV-08:50 | 18.22 | 11.69 | 0.185403E+09 | 356.46 | 09-NOV-11:09 | 18.22 | 11.69 |
December | 0.610418E+09 | 3836.07 | 15-DEC-13:02 | 14.08 | 5.59 | 0.167969E+09 | 356.50 | 06-DEC-11:09 | 14.08 | 5.59 |
Annual Sum or Average | 0.383012E+11 | 0.229778E+10 | ||||||||
Minimum of Months | 0.610418E+09 | 3817.40 | 12.20 | 4.97 | 0.167969E+09 | 356.45 | 12.20 | 4.97 | ||
Maximum of Months | 0.597977E+10 | 11873.94 | 27.30 | 18.49 | 0.214018E+09 | 356.50 | 30.10 | 18.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.355921E+10 | 9229.03 | 12-JAN-14:05 | 18.40 | 9.78 | 0.397925E+09 | 550.25 | 27-JAN-14:30 | 8.85 | 0.45 |
February | 0.349446E+10 | 12618.78 | 20-FEB-13:43 | 22.02 | 8.45 | 0.364902E+09 | 550.19 | 01-FEB-14:09 | 22.02 | 8.45 |
March | 0.411404E+10 | 8237.44 | 16-MAR-13:05 | 22.30 | 9.05 | 0.439161E+09 | 550.07 | 22-MAR-13:20 | 24.80 | 9.22 |
April | 0.465327E+10 | 12325.52 | 30-APR-13:23 | 29.40 | 12.42 | 0.399232E+09 | 550.43 | 28-APR-13:20 | 29.40 | 12.42 |
May | 0.553435E+10 | 11334.76 | 29-MAY-16:21 | 33.05 | 16.61 | 0.436901E+09 | 549.87 | 30-MAY-13:20 | 32.60 | 16.36 |
June | 0.648023E+10 | 12145.90 | 18-JUN-16:11 | 37.20 | 16.86 | 0.436808E+09 | 549.50 | 12-JUN-09:20 | 37.20 | 16.86 |
July | 0.643261E+10 | 12002.06 | 30-JUL-14:41 | 31.70 | 19.83 | 0.406389E+09 | 555.49 | 20-JUL-15:20 | 31.70 | 19.83 |
August | 0.706256E+10 | 12216.59 | 27-AUG-11:12 | 32.57 | 15.48 | 0.455634E+09 | 550.56 | 10-AUG-13:20 | 32.57 | 15.48 |
September | 0.723599E+10 | 13046.98 | 04-SEP-12:32 | 29.83 | 18.72 | 0.404283E+09 | 559.19 | 29-SEP-13:20 | 27.97 | 14.59 |
October | 0.663038E+10 | 12802.35 | 01-OCT-13:02 | 31.28 | 14.52 | 0.418084E+09 | 578.16 | 30-OCT-13:20 | 23.30 | 11.27 |
November | 0.499875E+10 | 12697.30 | 11-NOV-11:43 | 17.02 | 7.80 | 0.402661E+09 | 565.45 | 09-NOV-14:09 | 17.02 | 7.80 |
December | 0.334136E+10 | 8307.76 | 17-DEC-13:33 | 14.27 | 4.03 | 0.382567E+09 | 550.14 | 15-DEC-14:09 | 14.27 | 4.03 |
Annual Sum or Average | 0.635372E+11 | 0.494455E+10 | ||||||||
Minimum of Months | 0.334136E+10 | 8237.44 | 14.27 | 4.03 | 0.364902E+09 | 549.50 | 8.85 | 0.45 | ||
Maximum of Months | 0.723599E+10 | 13046.98 | 37.20 | 19.83 | 0.455634E+09 | 578.16 | 37.20 | 19.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101963E+10 | 3682.79 | 12-JAN-15:30 | 18.90 | 10.10 | 0.229441E+09 | 347.84 | 06-JAN-14:30 | 18.90 | 10.10 |
February | 0.118611E+10 | 5993.03 | 20-FEB-16:23 | 22.75 | 8.45 | 0.216456E+09 | 347.84 | 01-FEB-14:39 | 22.75 | 8.45 |
March | 0.212160E+10 | 6052.94 | 26-MAR-17:43 | 21.38 | 8.46 | 0.269891E+09 | 347.85 | 16-MAR-09:20 | 21.38 | 8.46 |
April | 0.340700E+10 | 12368.70 | 30-APR-18:02 | 29.63 | 12.67 | 0.252124E+09 | 347.86 | 27-APR-09:20 | 29.63 | 12.67 |
May | 0.497315E+10 | 12863.26 | 07-MAY-16:31 | 29.07 | 14.12 | 0.276858E+09 | 347.86 | 05-MAY-13:00 | 29.07 | 14.12 |
June | 0.586818E+10 | 12890.30 | 11-JUN-17:01 | 32.12 | 14.88 | 0.276761E+09 | 347.86 | 12-JUN-09:20 | 27.40 | 12.38 |
July | 0.545619E+10 | 12318.24 | 09-JUL-16:21 | 33.05 | 19.34 | 0.257472E+09 | 347.86 | 03-JUL-09:20 | 33.05 | 19.34 |
August | 0.530015E+10 | 12943.02 | 13-AUG-16:31 | 31.30 | 18.50 | 0.288539E+09 | 347.86 | 28-AUG-09:20 | 25.57 | 16.47 |
September | 0.451666E+10 | 12629.53 | 10-SEP-15:51 | 31.10 | 16.68 | 0.255685E+09 | 347.86 | 05-SEP-09:20 | 31.10 | 16.68 |
October | 0.313022E+10 | 11969.61 | 08-OCT-16:22 | 25.25 | 17.49 | 0.262546E+09 | 347.85 | 17-OCT-09:20 | 19.23 | 14.83 |
November | 0.170409E+10 | 5566.93 | 09-NOV-15:30 | 23.30 | 12.82 | 0.243502E+09 | 347.85 | 09-NOV-10:20 | 23.30 | 12.82 |
December | 0.875658E+09 | 2969.57 | 15-DEC-15:40 | 15.60 | 6.10 | 0.218660E+09 | 347.84 | 01-DEC-14:00 | 15.60 | 6.10 |
Annual Sum or Average | 0.395586E+11 | 0.304794E+10 | ||||||||
Minimum of Months | 0.875658E+09 | 2969.57 | 15.60 | 6.10 | 0.216456E+09 | 347.84 | 15.60 | 6.10 | ||
Maximum of Months | 0.586818E+10 | 12943.02 | 33.05 | 19.34 | 0.288539E+09 | 347.86 | 33.05 | 19.34 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.156119E+10 | 9284.21 | 28-JAN-07:03 | -2.9 |
February | 0.113651E+10 | 9711.60 | 03-FEB-07:01 | -5.1 |
March | 0.993754E+09 | 9277.71 | 02-MAR-07:02 | -1.6 |
April | 0.447716E+09 | 3496.73 | 16-APR-07:33 | 16.13 |
May | 0.198777E+09 | 5094.46 | 30-MAY-04:02 | 25.00 |
June | 57996387.52 | 4861.80 | 14-JUN-05:02 | 23.90 |
July | 33818765.76 | 4277.93 | 10-JUL-04:03 | 24.32 |
August | 65077931.96 | 3114.87 | 08-AUG-05:03 | 24.82 |
September | 0.198541E+09 | 4248.67 | 05-SEP-05:12 | 16.30 |
October | 0.470541E+09 | 3175.68 | 01-OCT-08:18 | 19.60 |
November | 0.101292E+10 | 8417.98 | 28-NOV-07:03 | 0.87 |
December | 0.183269E+10 | 11077.18 | 27-DEC-07:02 | -4.3 |
Annual Sum or Average | 0.800953E+10 | |||
Minimum of Months | 33818765.76 | 3114.87 | -5.1 | |
Maximum of Months | 0.183269E+10 | 11077.18 | 25.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108982E+10 | 2577.44 | 02-JAN-11:05 | 13.17 |
February | 0.662299E+09 | 3681.02 | 19-FEB-12:33 | 20.20 |
March | 0.374571E+09 | 2224.01 | 26-MAR-15:43 | 22.12 |
April | 43996992.00 | 2879.24 | 30-APR-14:42 | 29.90 |
May | 21657871.11 | 2526.05 | 29-MAY-16:21 | 33.05 |
June | 16608987.64 | 2847.44 | 04-JUN-15:41 | 35.40 |
July | 21320989.35 | 2699.55 | 09-JUL-16:21 | 33.05 |
August | 17540208.37 | 2660.04 | 27-AUG-15:11 | 35.00 |
September | 20770171.72 | 2901.22 | 10-SEP-15:51 | 31.10 |
October | 46809173.27 | 4542.11 | 08-OCT-15:42 | 26.20 |
November | 0.510858E+09 | 4073.35 | 19-NOV-12:23 | 15.55 |
December | 0.120756E+10 | 3905.34 | 17-DEC-13:33 | 14.27 |
Annual Sum or Average | 0.403382E+10 | |||
Minimum of Months | 16608987.64 | 2224.01 | 13.17 | |
Maximum of Months | 0.120756E+10 | 4542.11 | 35.40 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.588329E+09 | 3363.06 | 09-JAN-08:04 | 4.50 |
February | 0.258869E+09 | 2385.20 | 03-FEB-08:05 | -2.0 |
March | 0.104205E+09 | 2195.84 | 02-MAR-08:06 | -0.9 |
April | 15176491.65 | 1436.30 | 16-APR-16:51 | 30.00 |
May | 16787485.15 | 2443.75 | 31-MAY-04:03 | 26.32 |
June | 15576469.23 | 2922.04 | 09-JUN-05:02 | 23.80 |
July | 20807052.23 | 2770.21 | 07-JUL-04:03 | 24.40 |
August | 23270320.28 | 2986.67 | 24-AUG-04:03 | 25.50 |
September | 28911910.59 | 2178.87 | 17-SEP-15:21 | 32.80 |
October | 42571194.15 | 3187.07 | 08-OCT-15:42 | 26.20 |
November | 0.219018E+09 | 3299.85 | 17-NOV-06:03 | -0.5 |
December | 0.655330E+09 | 4412.14 | 27-DEC-08:06 | -3.4 |
Annual Sum or Average | 0.198885E+10 | |||
Minimum of Months | 15176491.65 | 1436.30 | -3.4 | |
Maximum of Months | 0.655330E+09 | 4412.14 | 32.80 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 845634.37 | 5637.56 | 17-JAN-07:03 | 5.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 2283536.32 | 13974.47 | 27-DEC-07:01 | -4.3 |
Annual Sum or Average | 3129170.69 | |||
Minimum of Months | 0.00 | 0.00 | -4.3 | |
Maximum of Months | 2283536.32 | 13974.47 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148332E+09 | 27562.22 | 17-JAN-06:11 | 4.60 |
February | 30814821.44 | 26008.75 | 03-FEB-07:01 | -5.1 |
March | 6401044.90 | 25647.40 | 02-MAR-07:02 | -1.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 53590039.68 | 27090.71 | 27-NOV-06:11 | 3.30 |
December | 0.300777E+09 | 28356.72 | 04-DEC-06:01 | -1.0 |
Annual Sum or Average | 0.539915E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.300777E+09 | 28356.72 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.816640E+09 | 10258.51 | 09-JAN-06:11 | 3.17 |
February | 0.415441E+09 | 9962.52 | 03-FEB-06:01 | -3.7 |
March | 0.180197E+09 | 9899.19 | 02-MAR-06:01 | -3.5 |
April | 5243681.53 | 7496.64 | 11-APR-06:03 | 4.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 706392.47 | 3751.79 | 25-OCT-06:03 | 6.88 |
November | 0.291838E+09 | 10264.69 | 27-NOV-06:11 | 3.30 |
December | 0.114178E+10 | 10626.23 | 04-DEC-05:01 | -0.7 |
Annual Sum or Average | 0.285185E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.114178E+10 | 10626.23 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.367845E+09 | 8970.69 | 09-JAN-06:11 | 3.17 |
February | 0.143587E+09 | 8701.74 | 03-FEB-06:01 | -3.7 |
March | 68304199.89 | 8648.25 | 02-MAR-06:01 | -3.5 |
April | 659219.23 | 2299.05 | 11-APR-06:03 | 4.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 426751.20 | 2734.51 | 25-OCT-06:03 | 6.88 |
November | 0.113242E+09 | 8994.01 | 27-NOV-06:11 | 3.30 |
December | 0.503239E+09 | 9303.89 | 04-DEC-05:01 | -0.7 |
Annual Sum or Average | 0.119730E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.503239E+09 | 9303.89 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.425667E+09 | 11046.11 | 09-JAN-06:11 | 3.17 |
February | 0.206241E+09 | 10728.41 | 03-FEB-06:01 | -3.7 |
March | 0.110477E+09 | 10785.89 | 02-MAR-06:01 | -3.5 |
April | 4963901.73 | 7595.58 | 11-APR-06:03 | 4.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 228057.40 | 1520.38 | 25-OCT-06:03 | 6.88 |
November | 0.141294E+09 | 11177.09 | 27-NOV-06:11 | 3.30 |
December | 0.569472E+09 | 11492.03 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.145834E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.569472E+09 | 11492.03 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.461552E+09 | 9107.38 | 09-JAN-06:11 | 3.17 |
February | 0.240238E+09 | 8727.86 | 03-FEB-06:01 | -3.7 |
March | 95342504.46 | 8708.33 | 02-MAR-06:01 | -3.5 |
April | 3203891.52 | 4895.26 | 11-APR-06:03 | 4.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 209654.21 | 1397.69 | 25-OCT-06:03 | 6.88 |
November | 0.164804E+09 | 9149.16 | 27-NOV-06:11 | 3.30 |
December | 0.636582E+09 | 9380.37 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.160193E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.636582E+09 | 9380.37 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116688E+09 | 7428.61 | 28-JAN-06:01 | -3.3 |
February | 83345680.04 | 7403.88 | 03-FEB-06:01 | -3.7 |
March | 41987743.30 | 7448.70 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 5873256.10 | 6991.53 | 28-NOV-07:03 | 0.87 |
December | 0.137246E+09 | 7458.35 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.385141E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.137246E+09 | 7458.35 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34173010.81 | 5465.76 | 26-JAN-07:02 | 0.60 |
February | 13936220.26 | 5537.44 | 10-FEB-07:02 | -2.8 |
March | 7756438.33 | 5523.70 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 777162.65 | 3411.51 | 28-NOV-07:03 | 0.87 |
December | 40509791.93 | 5694.27 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 97152623.97 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 40509791.93 | 5694.27 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.811925E+09 | 9414.32 | 27-JAN-07:10 | -4.3 |
February | 0.650951E+09 | 9598.09 | 03-FEB-07:10 | -5.1 |
March | 0.707991E+09 | 9245.19 | 02-MAR-07:10 | -1.6 |
April | 0.189776E+09 | 8263.40 | 12-APR-06:10 | 3.87 |
May | 13895864.25 | 7547.96 | 02-MAY-06:05 | 9.87 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 893621.68 | 3388.83 | 25-SEP-06:07 | 10.55 |
October | 68065311.83 | 7852.79 | 25-OCT-06:05 | 6.88 |
November | 0.464907E+09 | 8770.75 | 28-NOV-07:10 | 0.87 |
December | 0.875082E+09 | 9965.88 | 27-DEC-07:10 | -4.3 |
Annual Sum or Average | 0.378349E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.875082E+09 | 9965.88 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36108956.98 | 5406.72 | 26-JAN-07:02 | 0.60 |
February | 25626481.78 | 5500.02 | 01-FEB-07:02 | -1.6 |
March | 8883682.61 | 5234.21 | 02-MAR-07:02 | -1.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 1771114.60 | 4057.47 | 28-NOV-07:03 | 0.87 |
December | 45305204.98 | 5536.69 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.117695E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 45305204.98 | 5536.69 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159015E+09 | 8089.77 | 28-JAN-06:01 | -3.3 |
February | 64351267.17 | 7947.10 | 02-FEB-06:01 | -3.5 |
March | 18632896.44 | 7904.67 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 36099712.73 | 8094.13 | 28-NOV-06:01 | 1.02 |
December | 0.270478E+09 | 8351.90 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.548577E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 0.270478E+09 | 8351.90 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 77940976.14 | 6473.06 | 28-JAN-06:01 | -3.3 |
February | 22833090.07 | 6388.06 | 03-FEB-06:01 | -3.7 |
March | 8632126.91 | 6257.29 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 12917240.21 | 6495.35 | 28-NOV-06:01 | 1.02 |
December | 0.122696E+09 | 6772.79 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.245019E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.122696E+09 | 6772.79 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70782717.51 | 8862.99 | 17-JAN-06:11 | 4.60 |
February | 25404933.37 | 8491.20 | 02-FEB-07:01 | -4.0 |
March | 8265519.96 | 8414.08 | 02-MAR-07:02 | -1.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 13363270.31 | 8937.02 | 28-NOV-06:01 | 1.02 |
December | 0.119378E+09 | 9294.45 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.237195E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 0.119378E+09 | 9294.45 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 89350225.88 | 6267.80 | 26-JAN-06:01 | 1.52 |
February | 36981553.38 | 6233.74 | 02-FEB-06:01 | -3.5 |
March | 9459864.19 | 6382.89 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 18757680.58 | 6255.66 | 28-NOV-06:01 | 1.02 |
December | 0.148253E+09 | 6616.31 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.302802E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 0.148253E+09 | 6616.31 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.614047E+09 | 973.32 | 17-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.534768E+09 | 857.79 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.596825E+09 | 828.39 | 10-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.512356E+09 | 579.11 | 20-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.544562E+09 | 533.21 | 23-MAY-12:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.535402E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.505161E+09 | 575.40 | 07-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.573374E+09 | 572.85 | 17-AUG-07:19 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.523125E+09 | 645.88 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.570172E+09 | 892.96 | 13-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.600994E+09 | 1040.56 | 22-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.604538E+09 | 1040.56 | 01-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.671532E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.505161E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.614047E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.382026E+09 | 616.80 | 17-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335577E+09 | 558.08 | 13-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.376057E+09 | 532.29 | 10-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.325967E+09 | 354.26 | 20-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.347734E+09 | 344.90 | 24-MAY-15:39 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.342411E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.323510E+09 | 357.44 | 03-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.364576E+09 | 361.46 | 16-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.329515E+09 | 338.11 | 29-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.357826E+09 | 554.54 | 13-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.376481E+09 | 658.76 | 22-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.377953E+09 | 658.76 | 01-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.423963E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.323510E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.382026E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.582504E+09 | 968.68 | 17-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.516748E+09 | 819.23 | 23-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.590343E+09 | 818.12 | 10-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.514897E+09 | 579.02 | 20-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.549614E+09 | 537.51 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.541473E+09 | 496.34 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.511634E+09 | 578.65 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.576396E+09 | 575.58 | 17-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.520514E+09 | 545.63 | 18-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.558173E+09 | 886.98 | 13-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.572882E+09 | 1040.56 | 22-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.575510E+09 | 1040.56 | 01-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.661069E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.511634E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.590343E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.373791E+09 | 611.00 | 17-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.329380E+09 | 512.58 | 13-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.374676E+09 | 498.77 | 10-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324408E+09 | 431.39 | 20-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.344410E+09 | 353.78 | 03-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.339123E+09 | 335.59 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.320044E+09 | 369.42 | 07-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.363223E+09 | 435.15 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.329911E+09 | 418.53 | 18-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.355876E+09 | 567.46 | 13-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.364874E+09 | 658.71 | 22-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.368116E+09 | 658.71 | 01-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.418783E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.320044E+09 | 335.59 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.374676E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.611066E+09 | 970.76 | 17-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.532964E+09 | 849.28 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.595343E+09 | 820.26 | 10-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.511869E+09 | 576.14 | 20-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.544254E+09 | 528.33 | 23-MAY-12:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.535114E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.504706E+09 | 572.24 | 07-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.572694E+09 | 569.58 | 17-AUG-07:19 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.522006E+09 | 561.79 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.568667E+09 | 887.35 | 13-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.598579E+09 | 1040.56 | 22-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.602085E+09 | 1040.56 | 01-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.669935E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.504706E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.611066E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.381176E+09 | 615.50 | 17-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.334791E+09 | 554.99 | 13-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.375386E+09 | 528.42 | 10-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.325618E+09 | 351.84 | 20-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.347313E+09 | 342.82 | 24-MAY-15:39 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.342111E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.322996E+09 | 355.36 | 03-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.364098E+09 | 359.56 | 16-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.329076E+09 | 336.81 | 29-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.357293E+09 | 551.22 | 13-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.375627E+09 | 658.76 | 22-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.377050E+09 | 658.76 | 01-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.423253E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.322996E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.381176E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.580864E+09 | 965.88 | 17-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.515870E+09 | 810.52 | 23-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.589498E+09 | 809.51 | 10-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.514215E+09 | 576.05 | 20-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.549121E+09 | 532.61 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.540912E+09 | 496.34 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.510722E+09 | 575.68 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.575502E+09 | 572.46 | 17-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.519709E+09 | 542.04 | 18-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.557677E+09 | 881.08 | 13-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.572161E+09 | 1040.56 | 22-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.575116E+09 | 1040.56 | 01-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.660137E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.510722E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.589498E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.372761E+09 | 609.45 | 17-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.328696E+09 | 508.10 | 13-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.374010E+09 | 493.65 | 10-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.323990E+09 | 424.46 | 20-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.344128E+09 | 351.64 | 03-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.338828E+09 | 332.83 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.319630E+09 | 367.84 | 07-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.362611E+09 | 428.68 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.329302E+09 | 410.93 | 18-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.355178E+09 | 564.66 | 13-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.364007E+09 | 658.71 | 22-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.367438E+09 | 658.71 | 01-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.418058E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.319630E+09 | 332.83 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.374010E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.614046E+09 | 973.31 | 17-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.534766E+09 | 857.79 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.596824E+09 | 828.37 | 10-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.512355E+09 | 579.10 | 20-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.544562E+09 | 533.20 | 23-MAY-12:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.535402E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.505161E+09 | 575.40 | 07-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.573373E+09 | 572.85 | 17-AUG-07:19 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.523124E+09 | 645.88 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.570171E+09 | 892.94 | 13-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.600993E+09 | 1040.56 | 22-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.604520E+09 | 1040.56 | 01-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.671530E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.505161E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.614046E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.382026E+09 | 616.79 | 17-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335576E+09 | 558.08 | 13-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.376057E+09 | 532.28 | 10-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.325967E+09 | 354.26 | 20-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.347734E+09 | 344.89 | 24-MAY-15:39 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.342411E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.323510E+09 | 357.44 | 03-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.364576E+09 | 361.46 | 16-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.329515E+09 | 338.11 | 29-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.357825E+09 | 554.53 | 13-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.376480E+09 | 658.76 | 22-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.377953E+09 | 658.76 | 01-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.423963E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.323510E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.382026E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.582504E+09 | 968.67 | 17-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.516747E+09 | 819.21 | 23-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.590343E+09 | 818.10 | 10-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.514897E+09 | 579.02 | 20-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.549614E+09 | 537.50 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.541472E+09 | 496.34 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.511633E+09 | 578.64 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.576395E+09 | 575.57 | 17-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.520513E+09 | 545.62 | 18-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.558172E+09 | 886.96 | 13-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.572881E+09 | 1040.56 | 22-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.575510E+09 | 1040.56 | 01-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.661068E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.511633E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.590343E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.373791E+09 | 610.99 | 17-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.329379E+09 | 512.57 | 13-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.374676E+09 | 498.76 | 10-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324407E+09 | 431.37 | 20-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.344410E+09 | 353.78 | 03-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.339123E+09 | 335.58 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.320044E+09 | 369.41 | 07-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.363223E+09 | 435.14 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.329910E+09 | 418.53 | 18-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.355875E+09 | 567.45 | 13-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.364874E+09 | 658.71 | 22-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.368116E+09 | 658.71 | 01-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.418783E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.320044E+09 | 335.58 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.374676E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.614047E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537619E+09 |
February | 0.901968E+09 | 0.534768E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50779.54 | 0.465785E+09 |
March | 0.107774E+10 | 0.596825E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 205086.25 | 0.495840E+09 |
April | 0.956342E+09 | 0.512356E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29506791.19 | 0.276342E+09 |
May | 0.103597E+10 | 0.544562E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84123683.15 | 0.157897E+09 |
June | 0.103308E+10 | 0.535402E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131880E+09 | 60347947.13 |
July | 0.959235E+09 | 0.505161E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108624E+09 | 46330955.76 |
August | 0.107774E+10 | 0.573374E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87838735.61 | 59827136.85 |
September | 0.956342E+09 | 0.523125E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28041186.00 | 79074149.10 |
October | 0.994195E+09 | 0.570172E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10456107.12 | 0.242842E+09 |
November | 0.984487E+09 | 0.600994E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446617E+09 |
December | 0.959235E+09 | 0.604538E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466774E+09 |
Annual Sum or Average | 0.119305E+11 | 0.671532E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480726E+09 | 0.333530E+10 |
Minimum of Months | 0.901968E+09 | 0.505161E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46330955.76 |
Maximum of Months | 0.107774E+10 | 0.614047E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131880E+09 | 0.537619E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.382026E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369615E+09 |
February | 0.571020E+09 | 0.335577E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322924E+09 |
March | 0.682301E+09 | 0.376057E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108172.08 | 0.350892E+09 |
April | 0.605444E+09 | 0.325967E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17320832.96 | 0.194066E+09 |
May | 0.655854E+09 | 0.347734E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54910259.03 | 0.109973E+09 |
June | 0.654023E+09 | 0.342411E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86756470.71 | 41489981.83 |
July | 0.607275E+09 | 0.323510E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71236214.26 | 32298448.67 |
August | 0.682301E+09 | 0.364576E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56948446.27 | 41681577.36 |
September | 0.605444E+09 | 0.329515E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17699440.29 | 56657718.52 |
October | 0.629407E+09 | 0.357826E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6001705.48 | 0.170584E+09 |
November | 0.623262E+09 | 0.376481E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311598E+09 |
December | 0.607275E+09 | 0.377953E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320428E+09 |
Annual Sum or Average | 0.755301E+10 | 0.423963E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310982E+09 | 0.232221E+10 |
Minimum of Months | 0.571020E+09 | 0.323510E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32298448.67 |
Maximum of Months | 0.682301E+09 | 0.382026E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86756470.71 | 0.369615E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.582504E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597302E+09 |
February | 0.901968E+09 | 0.516748E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511114E+09 |
March | 0.107774E+10 | 0.590343E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 162213.93 | 0.545149E+09 |
April | 0.956342E+09 | 0.514897E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25331880.36 | 0.288693E+09 |
May | 0.103597E+10 | 0.549614E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83517586.74 | 0.157752E+09 |
June | 0.103308E+10 | 0.541473E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132858E+09 | 59414293.75 |
July | 0.959235E+09 | 0.511634E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109173E+09 | 45511130.75 |
August | 0.107774E+10 | 0.576396E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86157135.28 | 61186527.41 |
September | 0.956342E+09 | 0.520514E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25916811.55 | 85674691.06 |
October | 0.994195E+09 | 0.558173E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8162595.05 | 0.270023E+09 |
November | 0.984487E+09 | 0.572882E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497508E+09 |
December | 0.959235E+09 | 0.575510E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515912E+09 |
Annual Sum or Average | 0.119305E+11 | 0.661069E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471279E+09 | 0.363524E+10 |
Minimum of Months | 0.901968E+09 | 0.511634E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45511130.75 |
Maximum of Months | 0.107774E+10 | 0.590343E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132858E+09 | 0.597302E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.373791E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372647E+09 |
February | 0.570983E+09 | 0.329380E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325014E+09 |
March | 0.682256E+09 | 0.374676E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108205.04 | 0.353518E+09 |
April | 0.605404E+09 | 0.324408E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16124825.32 | 0.196702E+09 |
May | 0.655811E+09 | 0.344410E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52382249.15 | 0.111643E+09 |
June | 0.653980E+09 | 0.339123E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84903401.39 | 43406145.46 |
July | 0.607235E+09 | 0.320044E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69584078.59 | 33940310.89 |
August | 0.682256E+09 | 0.363223E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55309049.35 | 42593221.16 |
September | 0.605404E+09 | 0.329911E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17501092.01 | 57252215.01 |
October | 0.629366E+09 | 0.355876E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5705436.45 | 0.174210E+09 |
November | 0.623221E+09 | 0.364874E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312653E+09 |
December | 0.607235E+09 | 0.368116E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322666E+09 |
Annual Sum or Average | 0.755252E+10 | 0.418783E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301618E+09 | 0.234624E+10 |
Minimum of Months | 0.570983E+09 | 0.320044E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33940310.89 |
Maximum of Months | 0.682256E+09 | 0.374676E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84903401.39 | 0.372647E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.611066E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313665E+09 |
February | 0.901968E+09 | 0.532964E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 273274.38 | 0.258702E+09 |
March | 0.107774E+10 | 0.595343E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 216922.01 | 0.263919E+09 |
April | 0.956342E+09 | 0.511869E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19592436.32 | 0.143033E+09 |
May | 0.103597E+10 | 0.544254E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51456848.40 | 79764491.78 |
June | 0.103308E+10 | 0.535114E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76441090.35 | 28848750.93 |
July | 0.959235E+09 | 0.504706E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62336042.39 | 23424867.21 |
August | 0.107774E+10 | 0.572694E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49535864.36 | 32767051.61 |
September | 0.956342E+09 | 0.522006E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15925041.75 | 45393474.26 |
October | 0.994195E+09 | 0.568667E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6485151.77 | 0.143415E+09 |
November | 0.984487E+09 | 0.598579E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271338E+09 |
December | 0.959235E+09 | 0.602085E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279892E+09 |
Annual Sum or Average | 0.119305E+11 | 0.669935E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282263E+09 | 0.188416E+10 |
Minimum of Months | 0.901968E+09 | 0.504706E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23424867.21 |
Maximum of Months | 0.107774E+10 | 0.611066E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76441090.35 | 0.313665E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.381176E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219428E+09 |
February | 0.571020E+09 | 0.334791E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184413E+09 |
March | 0.682301E+09 | 0.375386E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65092.87 | 0.192972E+09 |
April | 0.605444E+09 | 0.325618E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10215159.15 | 0.105868E+09 |
May | 0.655854E+09 | 0.347313E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30883137.61 | 59146951.67 |
June | 0.654023E+09 | 0.342111E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48076101.32 | 21492724.96 |
July | 0.607275E+09 | 0.322996E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39006265.07 | 17651397.56 |
August | 0.682301E+09 | 0.364098E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30885023.17 | 24174247.04 |
September | 0.605444E+09 | 0.329076E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9609276.67 | 33556891.07 |
October | 0.629407E+09 | 0.357293E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3511025.18 | 0.102034E+09 |
November | 0.623262E+09 | 0.375627E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191760E+09 |
December | 0.607275E+09 | 0.377050E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195633E+09 |
Annual Sum or Average | 0.755301E+10 | 0.423253E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172251E+09 | 0.134813E+10 |
Minimum of Months | 0.571020E+09 | 0.322996E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17651397.56 |
Maximum of Months | 0.682301E+09 | 0.381176E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48076101.32 | 0.219428E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.580864E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332364E+10 |
February | 0.901968E+09 | 0.515870E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267102E+10 |
March | 0.107774E+10 | 0.589498E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3924341.87 | 0.250640E+10 |
April | 0.956342E+09 | 0.514215E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257061E+09 | 0.108642E+10 |
May | 0.103597E+10 | 0.549121E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719473E+09 | 0.447784E+09 |
June | 0.103308E+10 | 0.540912E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139465E+10 | 0.164199E+09 |
July | 0.959235E+09 | 0.510722E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114182E+10 | 0.113999E+09 |
August | 0.107774E+10 | 0.575502E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970569E+09 | 0.266893E+09 |
September | 0.956342E+09 | 0.519709E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666291E+09 | 0.414053E+09 |
October | 0.994195E+09 | 0.557677E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143860E+09 | 0.119107E+10 |
November | 0.984487E+09 | 0.572161E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253774E+10 |
December | 0.959235E+09 | 0.575116E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347889E+10 |
Annual Sum or Average | 0.119305E+11 | 0.660137E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529766E+10 | 0.182021E+11 |
Minimum of Months | 0.901968E+09 | 0.510722E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113999E+09 |
Maximum of Months | 0.107774E+10 | 0.589498E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139465E+10 | 0.347889E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.372761E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220697E+09 |
February | 0.570983E+09 | 0.328696E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184438E+09 |
March | 0.682256E+09 | 0.374010E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64101.23 | 0.194831E+09 |
April | 0.605404E+09 | 0.323990E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8990289.90 | 0.107266E+09 |
May | 0.655811E+09 | 0.344128E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29285651.69 | 60602210.31 |
June | 0.653980E+09 | 0.338828E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46853296.16 | 22639257.84 |
July | 0.607235E+09 | 0.319630E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38002727.71 | 18686228.31 |
August | 0.682256E+09 | 0.362611E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29872429.30 | 24968745.51 |
September | 0.605404E+09 | 0.329302E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9472371.47 | 34173465.22 |
October | 0.629366E+09 | 0.355178E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3321075.76 | 0.104747E+09 |
November | 0.623221E+09 | 0.364007E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192867E+09 |
December | 0.607235E+09 | 0.367438E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195589E+09 |
Annual Sum or Average | 0.755252E+10 | 0.418058E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165862E+09 | 0.136150E+10 |
Minimum of Months | 0.570983E+09 | 0.319630E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18686228.31 |
Maximum of Months | 0.682256E+09 | 0.374010E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46853296.16 | 0.220697E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.614046E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488539E+09 |
February | 0.901968E+09 | 0.534766E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40459.11 | 0.419515E+09 |
March | 0.107774E+10 | 0.596824E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 154904.26 | 0.441571E+09 |
April | 0.956342E+09 | 0.512355E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26200611.35 | 0.242956E+09 |
May | 0.103597E+10 | 0.544562E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72391170.15 | 0.138031E+09 |
June | 0.103308E+10 | 0.535402E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111815E+09 | 51566535.25 |
July | 0.959235E+09 | 0.505161E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92545409.98 | 39479886.23 |
August | 0.107774E+10 | 0.573373E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74919646.52 | 51833240.64 |
September | 0.956342E+09 | 0.523124E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24384862.67 | 69258171.34 |
October | 0.994195E+09 | 0.570171E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9154299.55 | 0.217237E+09 |
November | 0.984487E+09 | 0.600993E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409604E+09 |
December | 0.959235E+09 | 0.604520E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426318E+09 |
Annual Sum or Average | 0.119305E+11 | 0.671530E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411606E+09 | 0.299591E+10 |
Minimum of Months | 0.901968E+09 | 0.505161E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39479886.23 |
Maximum of Months | 0.107774E+10 | 0.614046E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111815E+09 | 0.488539E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.382026E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336196E+09 |
February | 0.421807E+09 | 0.335576E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290274E+09 |
March | 0.502994E+09 | 0.376057E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74986.63 | 0.311145E+09 |
April | 0.447140E+09 | 0.325967E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14748721.18 | 0.169484E+09 |
May | 0.484071E+09 | 0.347734E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46054950.05 | 96051820.88 |
June | 0.482240E+09 | 0.342411E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72715217.05 | 35502889.07 |
July | 0.448971E+09 | 0.323510E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59861154.95 | 27557977.89 |
August | 0.502994E+09 | 0.364576E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47888800.32 | 36148721.72 |
September | 0.447140E+09 | 0.329515E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14766780.66 | 49353140.67 |
October | 0.465148E+09 | 0.357825E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5070995.80 | 0.151746E+09 |
November | 0.460569E+09 | 0.376480E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284228E+09 |
December | 0.448971E+09 | 0.377953E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293131E+09 |
Annual Sum or Average | 0.557719E+10 | 0.423963E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261182E+09 | 0.208082E+10 |
Minimum of Months | 0.421807E+09 | 0.323510E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27557977.89 |
Maximum of Months | 0.502994E+09 | 0.382026E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72715217.05 | 0.336196E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.582504E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536478E+09 |
February | 0.901968E+09 | 0.516747E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455203E+09 |
March | 0.107774E+10 | 0.590343E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 142227.47 | 0.480221E+09 |
April | 0.956342E+09 | 0.514897E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21724625.44 | 0.252536E+09 |
May | 0.103597E+10 | 0.549614E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71439177.33 | 0.138120E+09 |
June | 0.103308E+10 | 0.541472E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112720E+09 | 50773216.91 |
July | 0.959235E+09 | 0.511633E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92996276.74 | 38779273.64 |
August | 0.107774E+10 | 0.576395E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73215510.03 | 52977531.34 |
September | 0.956342E+09 | 0.520513E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22002632.44 | 74752780.55 |
October | 0.994195E+09 | 0.558172E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6840091.10 | 0.238172E+09 |
November | 0.984487E+09 | 0.572881E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448279E+09 |
December | 0.959235E+09 | 0.575510E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465931E+09 |
Annual Sum or Average | 0.119305E+11 | 0.661068E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401081E+09 | 0.323222E+10 |
Minimum of Months | 0.901968E+09 | 0.511633E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38779273.64 |
Maximum of Months | 0.107774E+10 | 0.590343E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112720E+09 | 0.536478E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.373791E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337068E+09 |
February | 0.570983E+09 | 0.329379E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291229E+09 |
March | 0.682256E+09 | 0.374676E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95102.31 | 0.312798E+09 |
April | 0.605404E+09 | 0.324407E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13659684.51 | 0.172165E+09 |
May | 0.655811E+09 | 0.344410E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44294736.51 | 97551195.43 |
June | 0.653980E+09 | 0.339123E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71463191.25 | 37089447.08 |
July | 0.607235E+09 | 0.320044E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58723874.50 | 28983533.48 |
August | 0.682256E+09 | 0.363223E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46647607.35 | 36832856.99 |
September | 0.605404E+09 | 0.329910E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14790537.84 | 50002418.16 |
October | 0.629366E+09 | 0.355875E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4829328.23 | 0.154426E+09 |
November | 0.623221E+09 | 0.364874E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284383E+09 |
December | 0.607235E+09 | 0.368116E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293301E+09 |
Annual Sum or Average | 0.755252E+10 | 0.418783E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254504E+09 | 0.209583E+10 |
Minimum of Months | 0.570983E+09 | 0.320044E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28983533.48 |
Maximum of Months | 0.682256E+09 | 0.374676E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71463191.25 | 0.337068E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716740E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609204E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65294.55 | 0.635402E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27898421.49 | 0.341812E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85888649.48 | 0.188967E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138156E+09 | 65884289.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113583E+09 | 49340545.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89463178.70 | 69542328.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25802698.93 | 97753594.10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9375935.75 | 0.316242E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605627E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629229E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490233E+09 | 0.432574E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49340545.22 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138156E+09 | 0.716740E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862838E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748542E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119428.98 | 0.790229E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36907190.34 | 0.434434E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108846E+09 | 0.242960E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175097E+09 | 86366426.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143643E+09 | 64013167.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114814E+09 | 88705856.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34062200.03 | 0.122257E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12873467.15 | 0.389751E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.734268E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753845E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626363E+09 | 0.531821E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64013167.54 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175097E+09 | 0.862838E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.835652E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729603E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794880E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24255059.71 | 0.429370E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91610135.14 | 0.227147E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171934E+09 | 80699075.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134521E+09 | 62085232.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108773E+09 | 82850899.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25933530.74 | 0.119852E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9788534.82 | 0.384140E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698049E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717348E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566815E+09 | 0.516168E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62085232.75 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171934E+09 | 0.835652E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 973.32 | 17-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1468.26 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 857.79 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.49 | 20-FEB-16:00 | 1873.08 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 828.39 | 10-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.22 | 19-MAR-13:53 | 1363.29 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 579.11 | 20-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 275.34 | 01-APR-17:03 | 1527.46 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 533.21 | 23-MAY-12:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 502.32 | 14-MAY-15:25 | 685.12 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 484.37 | 04-JUN-18:53 | 567.76 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 575.40 | 07-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 601.11 | 02-JUL-20:57 | 286.82 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 572.85 | 17-AUG-07:19 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 374.39 | 26-AUG-17:02 | 503.73 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 645.88 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.23 | 10-SEP-14:53 | 283.14 | 23-SEP-17:10 |
October | 1306.65 | 02-OCT-09:09 | 892.96 | 13-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 289.22 | 01-OCT-15:00 | 722.91 | 23-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 22-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 843.06 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1102.69 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.14 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 601.11 | 1873.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 616.80 | 17-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 977.33 | 25-JAN-23:00 |
February | 827.22 | 01-FEB-10:09 | 558.08 | 13-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1250.81 | 09-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 532.29 | 10-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.16 | 22-MAR-13:00 | 941.70 | 19-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 354.26 | 20-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.33 | 01-APR-17:03 | 1019.00 | 10-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 344.90 | 24-MAY-15:39 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.07 | 14-MAY-15:25 | 452.53 | 04-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 322.39 | 04-JUN-18:53 | 377.28 | 28-JUN-02:00 |
July | 827.22 | 03-JUL-09:09 | 357.44 | 03-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 401.08 | 02-JUL-20:57 | 191.81 | 04-JUL-19:00 |
August | 827.22 | 01-AUG-09:09 | 361.46 | 16-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.03 | 27-AUG-12:53 | 340.29 | 14-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 338.11 | 29-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.07 | 10-SEP-15:26 | 226.51 | 24-SEP-10:30 |
October | 827.22 | 02-OCT-09:09 | 554.54 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.00 | 01-OCT-14:55 | 488.23 | 23-OCT-21:10 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 22-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 658.96 | 26-NOV-09:00 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 739.55 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.81 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 401.08 | 1250.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 968.68 | 17-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1494.34 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 819.23 | 23-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1917.69 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 818.12 | 10-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.24 | 22-MAR-13:00 | 1461.24 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 579.02 | 20-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.53 | 21-APR-15:00 | 1542.58 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 537.51 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 503.24 | 14-MAY-15:23 | 689.39 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 488.76 | 04-JUN-18:53 | 564.46 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 578.65 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 605.40 | 02-JUL-21:00 | 287.41 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 575.58 | 17-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 366.01 | 27-AUG-13:00 | 511.43 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 545.63 | 18-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.39 | 10-SEP-15:24 | 319.81 | 24-SEP-10:50 |
October | 1306.65 | 02-OCT-09:09 | 886.98 | 13-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 277.41 | 01-OCT-14:55 | 763.83 | 23-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 22-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 987.54 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1170.76 | 18-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.41 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 605.40 | 1917.69 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 611.00 | 17-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 976.95 | 25-JAN-23:00 |
February | 827.17 | 01-FEB-10:09 | 512.58 | 13-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1256.92 | 09-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 498.77 | 10-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 22-MAR-13:00 | 944.77 | 19-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 431.39 | 20-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.69 | 21-APR-15:00 | 1023.64 | 10-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 353.78 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 326.44 | 14-MAY-15:46 | 464.77 | 04-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 335.59 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 322.24 | 04-JUN-18:53 | 390.86 | 28-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 369.42 | 07-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 397.62 | 02-JUL-20:57 | 245.86 | 04-JUL-19:00 |
August | 827.17 | 01-AUG-09:09 | 435.15 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.05 | 27-AUG-12:53 | 348.57 | 14-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 418.53 | 18-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.84 | 10-SEP-15:00 | 205.97 | 24-SEP-16:00 |
October | 827.17 | 02-OCT-09:09 | 567.46 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.33 | 01-OCT-14:55 | 505.82 | 23-OCT-21:10 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 22-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 587.26 | 26-NOV-16:55 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 747.36 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 335.59 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.97 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 397.62 | 1256.92 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 970.76 | 17-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 862.66 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 849.28 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.82 | 20-FEB-15:50 | 1081.36 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 820.26 | 10-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 | 21-MAR-16:20 | 779.30 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 576.14 | 20-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.33 | 01-APR-17:03 | 870.33 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 528.33 | 23-MAY-12:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.28 | 14-MAY-16:00 | 376.52 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.53 | 04-JUN-19:00 | 300.04 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 572.24 | 07-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 336.25 | 02-JUL-21:20 | 153.62 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 569.58 | 17-AUG-07:19 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.16 | 26-AUG-18:00 | 262.58 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 561.79 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.26 | 10-SEP-15:10 | 159.77 | 24-SEP-07:00 |
October | 1306.65 | 02-OCT-09:09 | 887.35 | 13-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.89 | 01-OCT-14:52 | 421.91 | 24-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 22-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 550.26 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 709.87 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.62 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 336.25 | 1081.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 615.50 | 17-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 583.18 | 25-JAN-23:00 |
February | 827.22 | 01-FEB-10:09 | 554.99 | 13-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 740.98 | 09-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 528.42 | 10-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 22-MAR-13:00 | 563.69 | 19-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 351.84 | 20-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.04 | 01-APR-17:03 | 598.06 | 10-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 342.82 | 24-MAY-15:39 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.84 | 14-MAY-16:00 | 257.17 | 04-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.80 | 04-JUN-18:53 | 206.56 | 28-JUN-02:00 |
July | 827.22 | 03-JUL-09:09 | 355.36 | 03-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.86 | 02-JUL-21:20 | 107.12 | 04-JUL-19:40 |
August | 827.22 | 01-AUG-09:09 | 359.56 | 16-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.80 | 26-AUG-18:00 | 187.41 | 14-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 336.81 | 29-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.07 | 10-SEP-15:05 | 125.50 | 24-SEP-10:10 |
October | 827.22 | 02-OCT-09:09 | 551.22 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.88 | 01-OCT-14:52 | 290.06 | 24-OCT-02:00 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 22-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 413.86 | 26-NOV-09:00 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 488.89 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.12 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 213.86 | 740.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 965.88 | 17-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 18582.04 | 27-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 810.52 | 23-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 19196.82 | 03-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 809.51 | 10-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 635.19 | 21-MAR-16:10 | 16456.28 | 02-MAR-07:02 |
April | 1306.65 | 03-APR-09:09 | 576.05 | 20-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4934.39 | 19-APR-16:10 | 12253.85 | 12-APR-06:03 |
May | 1306.65 | 01-MAY-09:09 | 532.61 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7249.97 | 19-MAY-16:05 | 8335.88 | 02-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9715.06 | 02-JUN-16:03 | 4348.09 | 13-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 575.68 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9282.48 | 03-JUL-16:03 | 4217.56 | 05-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 572.46 | 17-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8540.97 | 07-AUG-16:03 | 4747.90 | 31-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 542.04 | 18-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6343.09 | 19-SEP-16:03 | 9082.87 | 25-SEP-06:01 |
October | 1306.65 | 02-OCT-09:09 | 881.08 | 13-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4257.75 | 04-OCT-16:05 | 11135.92 | 11-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 22-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 15485.24 | 17-NOV-07:03 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 18665.01 | 27-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4217.56 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 9715.06 | 19196.82 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 609.45 | 17-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 580.36 | 25-JAN-23:00 |
February | 827.17 | 01-FEB-10:09 | 508.10 | 13-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 742.26 | 09-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 493.65 | 10-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 22-MAR-13:00 | 562.87 | 19-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 424.46 | 20-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.30 | 21-APR-15:00 | 599.17 | 10-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 351.64 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.72 | 14-MAY-16:00 | 266.42 | 04-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 332.83 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.47 | 04-JUN-18:53 | 215.43 | 28-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 367.84 | 07-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.17 | 02-JUL-21:10 | 126.90 | 04-JUL-18:55 |
August | 827.17 | 01-AUG-09:09 | 428.68 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.32 | 27-AUG-13:05 | 193.65 | 14-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 410.93 | 18-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.85 | 10-SEP-15:03 | 108.19 | 24-SEP-07:00 |
October | 827.17 | 02-OCT-09:09 | 564.66 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.93 | 01-OCT-14:52 | 295.35 | 23-OCT-21:10 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 22-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 381.24 | 26-NOV-09:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 493.83 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 332.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.19 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 212.17 | 742.26 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 973.31 | 17-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1320.41 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 857.79 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.30 | 20-FEB-15:53 | 1687.67 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 828.37 | 10-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.03 | 22-MAR-13:00 | 1252.80 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 579.10 | 20-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.53 | 01-APR-17:03 | 1366.20 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 533.20 | 23-MAY-12:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 427.22 | 14-MAY-15:46 | 619.36 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 393.17 | 10-JUN-17:02 | 482.06 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 575.40 | 07-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 505.14 | 02-JUL-21:00 | 238.63 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 572.85 | 17-AUG-07:19 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 330.00 | 26-AUG-17:30 | 416.22 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 645.88 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.00 | 10-SEP-15:00 | 235.60 | 24-SEP-07:00 |
October | 1306.65 | 02-OCT-09:09 | 892.94 | 13-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.80 | 01-OCT-14:52 | 631.80 | 23-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 22-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 809.58 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1051.71 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.60 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 505.14 | 1687.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 616.79 | 17-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 879.84 | 25-JAN-23:00 |
February | 805.43 | 01-FEB-08:09 | 558.08 | 13-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1126.24 | 09-FEB-01:00 |
March | 805.43 | 01-MAR-08:09 | 532.28 | 10-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | 22-MAR-13:00 | 862.03 | 19-MAR-24:00 |
April | 805.43 | 03-APR-07:10 | 354.26 | 20-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.11 | 01-APR-17:03 | 911.83 | 10-APR-24:00 |
May | 805.43 | 01-MAY-07:10 | 344.89 | 24-MAY-15:39 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.49 | 14-MAY-15:46 | 410.03 | 04-MAY-02:00 |
June | 805.43 | 01-JUN-07:10 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.86 | 10-JUN-17:02 | 320.93 | 28-JUN-02:00 |
July | 805.43 | 03-JUL-07:10 | 357.44 | 03-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.88 | 02-JUL-21:00 | 159.60 | 18-JUL-21:10 |
August | 805.43 | 01-AUG-07:10 | 361.46 | 16-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.53 | 26-AUG-17:30 | 282.20 | 14-AUG-01:00 |
September | 805.43 | 01-SEP-07:10 | 338.11 | 29-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.91 | 10-SEP-15:54 | 197.48 | 24-SEP-10:20 |
October | 805.43 | 02-OCT-07:10 | 554.53 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.67 | 01-OCT-14:52 | 426.37 | 23-OCT-21:10 |
November | 805.43 | 01-NOV-07:10 | 658.76 | 22-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 620.42 | 26-NOV-09:00 |
December | 805.43 | 01-DEC-08:09 | 658.76 | 01-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 704.28 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.60 | |||||
Maximum of Months | 805.43 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 338.88 | 1126.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 968.67 | 17-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1345.08 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 819.21 | 23-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1723.80 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 818.10 | 10-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.99 | 22-MAR-13:00 | 1332.79 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 579.02 | 20-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.02 | 01-APR-17:03 | 1378.27 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 537.50 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 428.67 | 14-MAY-15:46 | 622.79 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 407.80 | 10-JUN-17:02 | 479.34 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 578.64 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 507.18 | 02-JUL-21:00 | 239.17 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 575.57 | 17-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.82 | 26-AUG-18:00 | 423.77 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 545.62 | 18-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.57 | 10-SEP-14:55 | 270.88 | 24-SEP-10:20 |
October | 1306.65 | 02-OCT-09:09 | 886.96 | 13-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.77 | 01-OCT-14:52 | 663.21 | 23-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 22-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 927.97 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1106.14 | 18-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.17 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 507.18 | 1723.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 610.99 | 17-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 878.68 | 25-JAN-23:00 |
February | 827.17 | 01-FEB-10:09 | 512.57 | 13-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1131.76 | 09-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 498.76 | 10-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | 22-MAR-13:00 | 864.62 | 19-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 431.37 | 20-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.01 | 21-APR-15:00 | 914.82 | 10-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 353.78 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.93 | 14-MAY-16:00 | 419.37 | 04-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 335.58 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.45 | 04-JUN-18:53 | 331.60 | 28-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 369.41 | 07-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 333.89 | 02-JUL-20:57 | 173.52 | 04-JUL-19:40 |
August | 827.17 | 01-AUG-09:09 | 435.14 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.80 | 27-AUG-12:53 | 289.70 | 14-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 418.53 | 18-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.05 | 10-SEP-14:55 | 165.19 | 04-SEP-20:00 |
October | 827.17 | 02-OCT-09:09 | 567.45 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.34 | 01-OCT-15:05 | 439.00 | 23-OCT-21:10 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 22-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 548.05 | 26-NOV-16:55 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 710.38 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 335.58 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.19 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 333.89 | 1131.76 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1924.62 | 25-JAN-23:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2454.66 | 09-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.10 | 22-MAR-13:00 | 1880.37 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.44 | 01-APR-17:03 | 1961.85 | 10-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573.89 | 14-MAY-16:00 | 883.26 | 04-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.87 | 04-JUN-19:00 | 658.90 | 28-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.19 | 02-JUL-20:53 | 326.89 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 411.27 | 26-AUG-17:02 | 555.93 | 14-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.27 | 10-SEP-14:53 | 331.94 | 24-SEP-07:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.94 | 01-OCT-14:52 | 908.62 | 24-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1201.13 | 26-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1598.59 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.89 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.19 | 2454.66 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2344.14 | 25-JAN-23:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3087.84 | 09-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.19 | 22-MAR-13:00 | 2310.34 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.93 | 01-APR-17:03 | 2490.57 | 10-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 717.15 | 14-MAY-16:00 | 1107.49 | 04-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 669.10 | 10-JUN-17:02 | 849.06 | 28-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 762.73 | 02-JUL-21:10 | 422.95 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.90 | 26-AUG-17:02 | 728.32 | 14-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.84 | 10-SEP-15:00 | 411.42 | 24-SEP-07:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.74 | 01-OCT-14:52 | 1137.24 | 23-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1428.59 | 26-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1897.34 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 411.42 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 762.73 | 3087.84 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2241.87 | 25-JAN-23:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2842.29 | 09-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2039.40 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.46 | 19-APR-21:03 | 2264.17 | 10-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 552.08 | 19-MAY-22:00 | 991.63 | 28-MAY-18:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 600.08 | 10-JUN-17:02 | 877.57 | 28-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788.28 | 02-JUL-21:20 | 456.43 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.14 | 26-AUG-17:02 | 784.01 | 14-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.58 | 10-SEP-15:00 | 478.85 | 23-SEP-17:05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.70 | 01-OCT-15:00 | 1139.69 | 23-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1347.70 | 26-NOV-14:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1665.56 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.43 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788.28 | 2842.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17434.09 | 13-JAN-17:00 | 6035.01 | 4936.01 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18724.81 | 23-FEB-09:00 | 6035.01 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19900.05 | 17-MAR-06:03 | 3811.58 | 4936.08 | 26390.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 37388.98 | 17-APR-06:02 | 7623.17 | 9872.16 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 42393.51 | 30-MAY-04:02 | 0.00 | 1058.67 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41689.87 | 09-JUN-05:02 | 3176.32 | 1058.67 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 40906.47 | 05-JUL-05:12 | 3176.32 | 2742.16 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 40359.12 | 14-AUG-05:12 | 3176.32 | 2742.16 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 40746.79 | 06-SEP-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 39849.21 | 23-OCT-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 37465.87 | 01-NOV-06:01 | 8893.70 | 11517.52 | 61577.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17325.27 | 29-DEC-08:03 | 54315.07 | 44424.13 | 163666.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17325.27 | 0.00 | 1058.67 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42393.51 | 54315.07 | 44424.13 | 163666.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2941.69 | 12-JAN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.15 |
February | 4550.15 | 22-FEB-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5699.85 | 16-MAR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.80 |
April | 9017.87 | 19-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.57 | 0.00 |
May | 11026.77 | 30-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.08 | 0.00 |
June | 11548.52 | 15-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.97 | 0.00 |
July | 11959.50 | 03-JUL-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.00 | 0.00 |
August | 11450.40 | 07-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.00 | 0.00 |
September | 10055.62 | 19-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.91 | 0.00 |
October | 9138.42 | 03-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.02 | 0.00 |
November | 5072.01 | 03-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.25 |
December | 1234.04 | 09-DEC-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1234.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11959.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.97 | 125.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1796.38 | 28-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.55 |
February | 1698.68 | 10-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.75 |
March | 1838.94 | 16-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.53 |
April | 3419.91 | 21-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.23 | 0.00 |
May | 5338.91 | 30-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.99 | 0.00 |
June | 5819.35 | 19-JUN-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.08 | 0.00 |
July | 6289.73 | 03-JUL-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.49 | 0.00 |
August | 5861.83 | 07-AUG-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.23 | 0.00 |
September | 5179.58 | 05-SEP-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.72 |
October | 4038.45 | 05-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.43 | 0.00 |
November | 2081.92 | 10-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.24 |
December | 1646.80 | 30-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1646.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6289.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.23 | 324.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2124.58 | 27-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.28 |
February | 2494.60 | 10-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.24 |
March | 2217.24 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.32 |
April | 3608.30 | 21-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.71 | 0.00 |
May | 5380.66 | 30-MAY-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.51 | 0.00 |
June | 6300.21 | 05-JUN-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.40 | 0.00 |
July | 7105.09 | 03-JUL-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 | 0.00 |
August | 6093.96 | 07-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 |
September | 6255.15 | 05-SEP-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.37 |
October | 4353.04 | 02-OCT-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.95 | 0.00 |
November | 2891.25 | 10-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.86 |
December | 2304.17 | 22-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2124.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7105.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.71 | 221.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9583.69 | 13-JAN-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11219.27 | 22-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12803.91 | 16-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23528.41 | 17-APR-06:02 | 7623.17 | 9872.16 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29988.34 | 22-MAY-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32910.93 | 19-JUN-05:14 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33057.83 | 17-JUL-05:14 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30413.32 | 14-AUG-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30857.35 | 05-SEP-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 28608.78 | 02-OCT-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14129.20 | 10-NOV-16:50 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8425.94 | 15-DEC-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 8425.94 | 0.00 | 1058.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33057.83 | 7623.17 | 9872.16 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8735.82 | 12-JAN-16:50 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10792.39 | 22-FEB-15:30 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13881.83 | 16-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16875.54 | 28-APR-15:40 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33421.66 | 30-MAY-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32498.26 | 09-JUN-05:02 | 3176.32 | 1058.67 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33034.47 | 10-JUL-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33205.74 | 14-AUG-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33074.18 | 05-SEP-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32105.22 | 02-OCT-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13894.29 | 10-NOV-15:00 | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6784.96 | 15-DEC-16:40 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6784.96 | 0.00 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33421.66 | 6198.29 | 4936.01 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1242.31 | 12-JAN-14:30 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.42 |
February | 2095.82 | 22-FEB-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3311.92 | 22-MAR-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.76 | 0.00 |
April | 5701.50 | 21-APR-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 233.53 | 0.00 |
May | 10633.99 | 21-MAY-15:52 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 391.03 | 0.00 |
June | 12439.52 | 18-JUN-15:42 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 188.47 | 0.00 |
July | 12573.56 | 02-JUL-16:12 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 258.54 | 0.00 |
August | 12307.43 | 06-AUG-16:52 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 290.22 | 0.00 |
September | 6807.87 | 04-SEP-13:22 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 61.38 | 0.00 |
October | 7462.99 | 02-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.39 |
November | 2695.63 | 09-NOV-15:30 | 1272.23 | 544.31 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.18 |
December | 1077.12 | 08-DEC-15:10 | 2544.47 | 1063.06 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1077.12 | 0.00 | 137.87 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12573.56 | 2544.47 | 1063.06 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 391.03 | 44.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1404.08 | 04-JAN-10:10 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.09 |
February | 2923.53 | 21-FEB-10:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 |
March | 4179.46 | 16-MAR-10:10 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.45 |
April | 10584.07 | 30-APR-10:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11094.74 | 29-MAY-09:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.11 |
June | 11498.76 | 18-JUN-09:42 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 63.28 | 0.00 |
July | 11566.87 | 02-JUL-09:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11535.37 | 06-AUG-09:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 40.53 | 0.00 |
September | 11875.68 | 17-SEP-09:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.13 |
October | 8720.85 | 01-OCT-09:32 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4562.94 | 10-NOV-09:20 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.97 |
December | 777.56 | 01-DEC-10:40 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 777.56 | 169.56 | 69.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11875.68 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 63.28 | 133.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9318.75 | 12-JAN-14:05 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.42 |
February | 14218.01 | 20-FEB-14:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.02 |
March | 8634.09 | 16-MAR-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.96 |
April | 14217.50 | 30-APR-13:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 33.12 | 0.00 |
May | 12364.77 | 21-MAY-15:12 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 308.71 | 0.00 |
June | 13655.99 | 18-JUN-15:42 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 189.79 | 0.00 |
July | 14184.06 | 30-JUL-12:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 69.99 | 0.00 |
August | 14131.96 | 13-AUG-13:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 63.17 | 0.00 |
September | 14923.53 | 04-SEP-13:22 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 42.85 | 0.00 |
October | 15634.21 | 01-OCT-12:12 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 32.87 | 0.00 |
November | 14113.40 | 11-NOV-11:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.24 |
December | 7432.54 | 07-DEC-14:10 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7432.54 | 267.84 | 110.30 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15634.21 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 308.71 | 244.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3640.17 | 12-JAN-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.60 |
February | 6061.39 | 20-FEB-16:13 | 127.16 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.92 |
March | 6168.01 | 14-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 0.00 |
April | 14363.66 | 16-APR-16:11 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 15.59 | 0.00 |
May | 13718.96 | 29-MAY-16:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 181.73 | 0.00 |
June | 13687.06 | 25-JUN-16:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 77.68 | 0.00 |
July | 13633.58 | 09-JUL-16:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 69.77 | 0.00 |
August | 13691.28 | 06-AUG-16:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 168.33 | 0.00 |
September | 13422.32 | 17-SEP-15:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 96.46 | 0.00 |
October | 13685.84 | 01-OCT-14:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 144.11 | 0.00 |
November | 5667.70 | 09-NOV-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.46 |
December | 2691.52 | 15-DEC-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2691.52 | 127.16 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14363.66 | 805.38 | 314.21 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 181.73 | 139.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1123.74 | 13-JAN-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.77 |
February | 1201.42 | 22-FEB-13:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
March | 1523.48 | 22-MAR-14:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 0.00 |
April | 3788.54 | 21-APR-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 115.45 | 0.00 |
May | 5078.84 | 30-MAY-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 44.78 | 0.00 |
June | 7712.17 | 19-JUN-06:03 | 803.52 | 496.35 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 |
July | 8070.51 | 03-JUL-06:03 | 803.52 | 496.35 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 12.61 | 0.00 |
August | 8074.45 | 27-AUG-17:01 | 0.00 | 193.02 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 144.67 | 0.00 |
September | 7513.78 | 11-SEP-06:02 | 1339.19 | 1298.80 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.64 |
October | 5670.94 | 02-OCT-06:03 | 803.52 | 1040.57 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.53 |
November | 2403.29 | 09-NOV-16:00 | 1272.23 | 692.28 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 |
December | 1178.69 | 07-DEC-13:07 | 3816.70 | 1489.03 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1123.74 | 0.00 | 193.02 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8074.45 | 3816.70 | 1489.03 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 144.67 | 48.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1484.60 | 04-JAN-10:10 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.51 |
February | 2540.11 | 21-FEB-10:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.72 |
March | 3018.27 | 31-MAR-09:40 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 |
April | 6952.10 | 30-APR-10:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7626.66 | 29-MAY-09:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.37 |
June | 8759.36 | 18-JUN-09:42 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 36.21 | 0.00 |
July | 10447.76 | 04-JUL-09:32 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.29 |
August | 10307.50 | 20-AUG-09:52 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.47 | 0.00 |
September | 10139.12 | 17-SEP-10:02 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 2.93 | 0.00 |
October | 5749.83 | 05-OCT-09:10 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.74 | 0.00 |
November | 4331.92 | 10-NOV-09:10 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.34 |
December | 1350.74 | 01-DEC-10:10 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1350.74 | 169.56 | 69.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10447.76 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 36.21 | 70.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7046.76 | 12-JAN-14:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.57 |
February | 7409.78 | 20-FEB-14:02 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.88 |
March | 5848.41 | 22-MAR-13:10 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 89.58 | 0.00 |
April | 9207.18 | 19-APR-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4571.27 | 0.00 |
May | 10089.73 | 30-MAY-16:10 | 401.76 | 275.75 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 6441.14 | 0.00 |
June | 10596.01 | 02-JUN-16:50 | 401.76 | 275.75 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 8827.95 | 0.00 |
July | 10684.57 | 03-JUL-17:00 | 401.76 | 380.60 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 8450.98 | 0.00 |
August | 11508.02 | 27-AUG-13:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 120.67 | 0.00 |
September | 12122.25 | 17-SEP-13:22 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 49.88 | 0.00 |
October | 12200.48 | 29-OCT-15:12 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.03 |
November | 11751.55 | 11-NOV-14:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.69 |
December | 8100.51 | 07-DEC-13:07 | 3816.70 | 1489.03 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 958.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5848.41 | 267.84 | 110.30 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12200.48 | 3816.70 | 1489.03 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 8827.95 | 958.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2656.69 | 30-JAN-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.55 |
February | 3822.71 | 21-FEB-16:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.26 |
March | 3905.22 | 14-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 | 0.00 |
April | 10984.39 | 16-APR-16:11 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 14.81 | 0.00 |
May | 11061.49 | 07-MAY-16:31 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 0.00 |
June | 10674.28 | 25-JUN-17:12 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 45.03 | 0.00 |
July | 10713.06 | 04-JUL-15:31 | 339.11 | 139.64 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 32.07 | 0.00 |
August | 11511.64 | 13-AUG-16:31 | 339.11 | 139.64 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 0.00 |
September | 11242.41 | 17-SEP-16:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 28.99 | 0.00 |
October | 10876.31 | 08-OCT-16:22 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.13 |
November | 5070.93 | 03-NOV-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
December | 2497.30 | 15-DEC-16:10 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2497.30 | 0.00 | 87.28 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11511.64 | 805.38 | 314.21 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 45.03 | 35.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1407.17 | 12-JAN-14:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.55 |
February | 2254.28 | 23-FEB-14:30 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.19 |
March | 3145.77 | 22-MAR-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.86 | 0.00 |
April | 5125.91 | 21-APR-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 195.01 | 0.00 |
May | 10476.00 | 29-MAY-17:01 | 0.00 | 248.17 | 3474.93 | 0.00 | 0.00 | 0.00 | 0.00 | 247.27 | 0.00 |
June | 10909.02 | 18-JUN-16:11 | 468.72 | 193.02 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 173.02 | 0.00 |
July | 10610.17 | 02-JUL-16:12 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 219.89 | 0.00 |
August | 10488.93 | 13-AUG-16:31 | 535.68 | 220.59 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 84.65 | 0.00 |
September | 7294.12 | 10-SEP-15:51 | 468.72 | 193.02 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 146.23 | 0.00 |
October | 7147.83 | 02-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.90 |
November | 2689.13 | 09-NOV-16:00 | 1272.23 | 705.77 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.75 |
December | 1135.36 | 08-DEC-15:10 | 2544.47 | 1063.05 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1135.36 | 0.00 | 165.44 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10909.02 | 2613.31 | 1063.05 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 247.27 | 39.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3817.40 | 31-JAN-13:02 | 4027.14 | 1571.14 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.09 |
February | 4806.48 | 08-FEB-13:02 | 4832.57 | 1885.36 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.00 |
March | 5431.31 | 16-MAR-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.38 |
April | 11325.61 | 30-APR-08:62 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.67 |
May | 11762.45 | 29-MAY-09:02 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.39 |
June | 11723.82 | 04-JUN-09:02 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.70 |
July | 11873.94 | 04-JUL-08:52 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.59 |
August | 11629.79 | 20-AUG-09:12 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.74 |
September | 11800.09 | 04-SEP-08:32 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.57 |
October | 6942.49 | 05-OCT-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 14.31 | 0.00 |
November | 4992.14 | 10-NOV-08:50 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.44 |
December | 3836.07 | 15-DEC-13:02 | 4027.14 | 1571.14 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3817.40 | 211.95 | 87.28 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11873.94 | 4832.57 | 1885.36 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 14.31 | 138.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9229.03 | 12-JAN-14:05 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.95 |
February | 12618.78 | 20-FEB-13:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.86 |
March | 8237.44 | 16-MAR-13:05 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.36 |
April | 12325.52 | 30-APR-13:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 32.55 | 0.00 |
May | 11334.76 | 29-MAY-16:21 | 602.64 | 248.17 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 280.83 | 0.00 |
June | 12145.90 | 18-JUN-16:11 | 468.72 | 193.02 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 174.87 | 0.00 |
July | 12002.06 | 30-JUL-14:41 | 468.72 | 193.02 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 | 0.00 |
August | 12216.59 | 27-AUG-11:12 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 179.61 | 0.00 |
September | 13046.98 | 04-SEP-12:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 20.66 | 0.00 |
October | 12802.35 | 01-OCT-13:02 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 41.96 | 0.00 |
November | 12697.30 | 11-NOV-11:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.98 |
December | 8307.76 | 17-DEC-13:33 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8237.44 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13046.98 | 2613.31 | 992.69 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 280.83 | 295.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3682.79 | 12-JAN-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.44 |
February | 5993.03 | 20-FEB-16:23 | 127.16 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.16 |
March | 6052.94 | 26-MAR-17:43 | 0.00 | 52.37 | 733.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.64 |
April | 12368.70 | 30-APR-18:02 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 24.05 | 0.00 |
May | 12863.26 | 07-MAY-16:31 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 0.00 |
June | 12890.30 | 11-JUN-17:01 | 0.00 | 139.64 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 87.41 | 0.00 |
July | 12318.24 | 09-JUL-16:21 | 381.49 | 157.10 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 62.20 | 0.00 |
August | 12943.02 | 13-AUG-16:31 | 339.11 | 139.64 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 28.92 | 0.00 |
September | 12629.53 | 10-SEP-15:51 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 59.19 | 0.00 |
October | 11969.61 | 08-OCT-16:22 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.45 |
November | 5566.93 | 09-NOV-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.99 |
December | 2969.57 | 15-DEC-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2969.57 | 0.00 | 52.37 | 733.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12943.02 | 805.38 | 314.21 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 87.41 | 121.16 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.971535E+11 | 107854.84 | 17-JAN-07:10 | 0.196458E+11 | 58525.39 | 27-JAN-07:19 |
February | 0.872094E+11 | 100252.96 | 03-FEB-07:10 | 0.155168E+11 | 58996.78 | 03-FEB-07:19 |
March | 0.102241E+12 | 95859.30 | 16-MAR-15:20 | 0.145739E+11 | 49692.75 | 02-MAR-07:40 |
April | 0.108600E+12 | 131211.27 | 21-APR-15:09 | 0.105117E+11 | 23823.10 | 12-APR-06:19 |
May | 0.136907E+12 | 154799.43 | 30-MAY-14:39 | 0.102978E+11 | 9667.20 | 01-MAY-11:30 |
June | 0.158698E+12 | 162126.80 | 15-JUN-14:39 | 0.972871E+10 | 9538.45 | 02-JUN-11:09 |
July | 0.160313E+12 | 171024.51 | 20-JUL-15:09 | 0.949873E+10 | 9450.74 | 03-JUL-11:20 |
August | 0.159297E+12 | 157205.54 | 07-AUG-15:00 | 0.988308E+10 | 9449.77 | 31-AUG-11:39 |
September | 0.137403E+12 | 144776.78 | 05-SEP-15:30 | 0.949131E+10 | 9535.78 | 29-SEP-11:30 |
October | 0.115019E+12 | 132243.00 | 03-OCT-14:09 | 0.102625E+11 | 15961.21 | 11-OCT-06:30 |
November | 0.966036E+11 | 99936.85 | 09-NOV-16:10 | 0.135241E+11 | 41952.14 | 28-NOV-07:30 |
December | 0.970277E+11 | 121361.71 | 27-DEC-07:10 | 0.228377E+11 | 59757.29 | 27-DEC-07:40 |
Annual Sum or Average | 0.145647E+13 | 0.155772E+12 | ||||
Minimum of Months | 0.872094E+11 | 95859.30 | 0.949131E+10 | 9449.77 | ||
Maximum of Months | 0.160313E+12 | 171024.51 | 0.228377E+11 | 59757.29 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.197632E+11 | 0.537384E+10 | 0.593559E+11 | 0.982710E+09 | 0.422071E+10 | 12379742.02 | 0.598121E+10 | 0.146358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177661E+11 | 0.443448E+10 | 0.537310E+11 | 0.889286E+09 | 0.425084E+10 | 11196021.66 | 0.318158E+10 | 0.294490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208258E+11 | 0.433543E+10 | 0.617796E+11 | 0.102907E+10 | 0.578306E+10 | 12675672.10 | 0.196160E+10 | 0.651378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.184242E+11 | 0.368213E+10 | 0.572952E+11 | 0.946220E+09 | 0.889237E+10 | 11960507.72 | 0.288873E+09 | 0.190589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198216E+11 | 0.337896E+10 | 0.605677E+11 | 0.100559E+10 | 0.142821E+11 | 12527707.06 | 22046339.75 | 0.378169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.196750E+11 | 0.308173E+10 | 0.594895E+11 | 0.989917E+09 | 0.189276E+11 | 12231776.97 | 0.00 | 0.565220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.184349E+11 | 0.329899E+10 | 0.583622E+11 | 0.961721E+09 | 0.181147E+11 | 12256437.81 | 0.00 | 0.611276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.206456E+11 | 0.363867E+10 | 0.617796E+11 | 0.102897E+10 | 0.178536E+11 | 12675672.10 | 0.00 | 0.543383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.184994E+11 | 0.393727E+10 | 0.572729E+11 | 0.946023E+09 | 0.140050E+11 | 11960507.72 | 2365590.91 | 0.427283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194356E+11 | 0.466421E+10 | 0.593671E+11 | 0.982569E+09 | 0.961792E+10 | 12379742.02 | 0.100183E+09 | 0.208388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.194955E+11 | 0.503684E+10 | 0.580818E+11 | 0.964509E+09 | 0.575030E+10 | 12059151.09 | 0.214284E+10 | 0.511979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192302E+11 | 0.550349E+10 | 0.583511E+11 | 0.962175E+09 | 0.410958E+10 | 12256437.81 | 0.788595E+10 | 0.972888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232017E+12 | 0.503660E+11 | 0.705434E+12 | 0.116888E+11 | 0.125808E+12 | 0.146559E+09 | 0.215666E+11 | 0.309446E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.177661E+11 | 0.308173E+10 | 0.537310E+11 | 0.889286E+09 | 0.410958E+10 | 11196021.66 | 0.00 | 0.972888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.208258E+11 | 0.550349E+10 | 0.617796E+11 | 0.102907E+10 | 0.189276E+11 | 12675672.10 | 0.788595E+10 | 0.611276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.860441E+10 | 0.00 | 0.110414E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.551763E+10 | 0.00 | 0.999912E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.335400E+10 | 0.00 | 0.112199E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.342225E+09 | 0.00 | 0.101695E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 2974963.76 | 0.00 | 0.102948E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.972871E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.949873E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.988308E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 5575077.70 | 0.00 | 0.948573E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.126012E+09 | 0.00 | 0.101365E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.327152E+10 | 0.00 | 0.102526E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.121206E+11 | 0.00 | 0.107171E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.333450E+11 | 0.00 | 0.122427E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.948573E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.121206E+11 | 0.00 | 0.112199E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 24309.19 | 17-JAN-16:00 | 5686.19 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 837.55 | 17-JAN-16:00 | 6442.24 | 12-JAN-15:39 | 6.85 | 02-JAN-06:10 | 69357.31 | 17-JAN-07:10 |
February | 22883.31 | 23-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 836.77 | 13-FEB-08:20 | 8699.36 | 21-FEB-16:30 | 6.85 | 01-FEB-06:10 | 67500.21 | 03-FEB-07:10 |
March | 22814.96 | 10-MAR-16:00 | 5686.19 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 835.70 | 22-MAR-07:19 | 12259.90 | 16-MAR-15:30 | 6.85 | 02-MAR-06:10 | 59334.94 | 02-MAR-07:10 |
April | 20624.07 | 20-APR-07:10 | 5686.19 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 834.33 | 20-APR-07:19 | 20406.20 | 21-APR-15:09 | 6.85 | 15-APR-16:10 | 18347.43 | 11-APR-06:10 |
May | 19968.81 | 03-MAY-07:10 | 5686.19 | 01-MAY-05:10 | 45864.70 | 01-MAY-07:10 | 833.46 | 03-MAY-07:19 | 30112.99 | 30-MAY-14:39 | 6.85 | 14-MAY-15:20 | 5155.86 | 02-MAY-06:10 |
June | 19732.79 | 29-JUN-07:10 | 3328.83 | 01-JUN-19:10 | 45864.70 | 01-JUN-07:10 | 833.15 | 29-JUN-07:19 | 30631.58 | 19-JUN-14:30 | 6.85 | 04-JUN-15:09 | 0.00 | 01-JUN-00:10 |
July | 20434.76 | 07-JUL-07:30 | 5686.19 | 06-JUL-05:10 | 45864.70 | 03-JUL-07:10 | 834.08 | 07-JUL-07:40 | 34937.99 | 20-JUL-15:09 | 6.85 | 01-JUL-16:10 | 0.00 | 01-JUL-00:10 |
August | 20469.37 | 17-AUG-07:10 | 5686.19 | 01-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 834.13 | 17-AUG-07:19 | 26929.26 | 21-AUG-15:00 | 6.85 | 06-AUG-14:50 | 0.00 | 01-AUG-00:10 |
September | 20337.28 | 29-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 833.95 | 29-SEP-07:19 | 22335.37 | 05-SEP-15:30 | 6.85 | 17-SEP-15:50 | 1139.29 | 25-SEP-06:10 |
October | 23496.18 | 13-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 838.15 | 13-OCT-07:19 | 18351.60 | 03-OCT-15:39 | 6.85 | 01-OCT-05:10 | 10260.11 | 25-OCT-06:10 |
November | 25003.79 | 22-NOV-16:00 | 5686.19 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 838.53 | 28-NOV-16:00 | 12341.98 | 09-NOV-16:10 | 6.85 | 01-NOV-05:10 | 62189.08 | 28-NOV-07:10 |
December | 25003.79 | 01-DEC-16:00 | 5686.19 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 838.60 | 11-DEC-16:00 | 5000.03 | 07-DEC-15:09 | 6.85 | 01-DEC-17:10 | 88392.65 | 27-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 19732.79 | 3328.83 | 45864.70 | 833.15 | 5000.03 | 6.85 | 0.00 | |||||||
Maximum of Months | 25003.79 | 5686.19 | 45864.70 | 838.60 | 34937.99 | 6.85 | 88392.65 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 12389.09 | 12-JAN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18126.14 | 21-FEB-16:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23520.70 | 21-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 48360.97 | 21-APR-14:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 63588.51 | 30-MAY-14:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73279.75 | 15-JUN-14:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 76228.29 | 03-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 72247.54 | 07-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 59859.01 | 05-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 57992.06 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 24764.27 | 03-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7399.71 | 08-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 7399.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76228.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 107854.84 | 17-JAN-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 3127.28 | 6.85 | 69357.31 | 0.00 | 0.00 |
February | 100252.96 | 03-FEB-07:10 | 8334.71 | 21098.80 | 0.00 | 243.70 | 3068.69 | 6.85 | 67500.21 | 0.00 | 0.00 |
March | 95859.30 | 16-MAR-15:20 | 19671.42 | 42072.41 | 0.00 | 831.72 | 12217.08 | 6.85 | 0.00 | 21059.82 | 0.00 |
April | 131211.27 | 21-APR-15:09 | 19671.42 | 42072.41 | 0.00 | 831.72 | 20406.20 | 6.85 | 0.00 | 48222.68 | 0.00 |
May | 154799.43 | 30-MAY-14:39 | 19671.42 | 40588.47 | 0.00 | 831.19 | 30112.99 | 6.85 | 0.00 | 63588.51 | 0.00 |
June | 162126.80 | 15-JUN-14:39 | 19671.42 | 40588.47 | 0.00 | 831.19 | 27749.13 | 6.85 | 0.00 | 73279.75 | 0.00 |
July | 171024.51 | 20-JUL-15:09 | 19671.42 | 42072.41 | 0.00 | 831.72 | 34937.99 | 6.85 | 0.00 | 73504.13 | 0.00 |
August | 157205.54 | 07-AUG-15:00 | 19671.42 | 42072.41 | 0.00 | 831.72 | 22375.61 | 6.85 | 0.00 | 72247.54 | 0.00 |
September | 144776.78 | 05-SEP-15:30 | 19671.42 | 42072.41 | 0.00 | 831.72 | 22335.37 | 6.85 | 0.00 | 59859.01 | 0.00 |
October | 132243.00 | 03-OCT-14:09 | 19671.42 | 40588.47 | 0.00 | 831.19 | 13167.20 | 6.85 | 0.00 | 57977.88 | 0.00 |
November | 99936.85 | 09-NOV-16:10 | 20943.73 | 42072.41 | 0.00 | 833.05 | 12341.98 | 6.85 | 0.00 | 23738.83 | 0.00 |
December | 121361.71 | 27-DEC-07:10 | 8334.71 | 21098.80 | 0.00 | 243.70 | 3285.00 | 6.85 | 88392.65 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 95859.30 | 8334.71 | 21098.80 | 0.00 | 243.70 | 3068.69 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 171024.51 | 20943.73 | 42072.41 | 5686.19 | 833.05 | 34937.99 | 6.85 | 88392.65 | 73504.13 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 49683.18 | 27-JAN-07:19 | 0.00 | 9951.79 | 27-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 50153.16 | 03-FEB-07:19 | 0.00 | 9951.54 | 01-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 42622.20 | 02-MAR-07:19 | 0.00 | 9908.57 | 02-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 18906.61 | 12-APR-06:10 | 0.00 | 9790.41 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 1823.00 | 02-MAY-06:10 | 0.00 | 9667.20 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9538.45 | 02-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9450.74 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9449.77 | 31-AUG-11:39 | 0.00 |
September | 0.00 | 0.00 | 3890.02 | 30-SEP-06:10 | 0.00 | 9535.78 | 29-SEP-11:30 | 0.00 |
October | 0.00 | 0.00 | 10030.68 | 25-OCT-06:10 | 0.00 | 9670.64 | 31-OCT-11:00 | 0.00 |
November | 0.00 | 0.00 | 34374.05 | 28-NOV-07:19 | 0.00 | 9799.09 | 30-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 51446.26 | 27-DEC-07:30 | 0.00 | 9909.20 | 28-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9449.77 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 51446.26 | 0.00 | 9951.79 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.38 | 0.00 | 26.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.31 | 0.00 | 26.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.26 | 0.00 | 27.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 26.80 | 0.00 | 26.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.26 | 0.00 | 27.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.67 | 0.33 | 24.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 24.67 | 0.33 | 24.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.67 | 0.33 | 24.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.30 | 0.17 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.44 | 3.50 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.53 | 4.67 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.47 | 7.33 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.51 | 4.50 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.29 | 1.83 | 27.29 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 18.31 | 0.17 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 |
December | 0.67 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 |
Annual Sum or Average | 1.33 | 17.66 | 0.33 | 18.01 | 32.67 | 27.02 | 21.83 | 27.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 18.31 | 0.17 | 18.67 | 12.00 | 27.53 | 7.33 | 27.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.60 | 5.00 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.84 | 10.83 | 27.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.91 | 10.67 | 27.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 27.86 | 16.00 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.94 | 10.00 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.73 | 9.50 | 27.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.41 | 2.33 | 27.41 |
November | 0.17 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
December | 0.83 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 |
Annual Sum or Average | 1.17 | 17.08 | 0.00 | 17.08 | 76.00 | 27.67 | 64.33 | 27.77 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 17.21 | 0.00 | 17.21 | 20.33 | 27.94 | 16.00 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.52 | 2.50 | 27.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.52 | 4.17 | 27.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.57 | 5.33 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.55 | 5.50 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.57 | 9.00 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.79 | 6.50 | 27.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.87 | 7.67 | 27.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.97 | 7.50 | 27.98 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.56 | 5.00 | 27.56 |
December | 0.50 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
Annual Sum or Average | 0.50 | 17.07 | 0.00 | 17.07 | 64.00 | 27.60 | 53.50 | 27.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 17.07 | 0.00 | 17.07 | 12.50 | 27.97 | 9.00 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.48 | 0.67 | 27.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.52 | 1.17 | 27.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.09 | 4.67 | 28.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 28.27 | 5.83 | 28.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 28.30 | 5.17 | 28.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 28.10 | 8.00 | 28.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 28.19 | 5.83 | 28.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.15 | 5.17 | 28.18 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.88 | 3.83 | 27.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
December | 0.50 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
Annual Sum or Average | 0.50 | 16.95 | 0.00 | 16.95 | 69.00 | 28.06 | 40.50 | 28.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 16.95 | 0.00 | 16.95 | 16.50 | 28.30 | 8.00 | 28.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.52 | 1.50 | 27.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.53 | 6.33 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.63 | 7.50 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.58 | 13.17 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.62 | 10.00 | 27.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.58 | 9.50 | 27.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.47 | 1.17 | 27.47 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 51.33 | 27.59 | 49.17 | 27.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.63 | 13.17 | 27.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.67 | 19.27 | 18.67 | 19.27 | 0.33 | 19.34 | 0.33 | 19.41 |
February | 10.83 | 18.82 | 10.83 | 18.82 | 1.17 | 19.26 | 1.17 | 19.66 |
March | 10.17 | 19.25 | 10.17 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
April | 2.50 | 20.14 | 2.50 | 20.14 | 0.00 | 20.14 | 0.00 | 20.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.64 | 0.67 | 24.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 25.03 | 20.50 | 25.03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 25.11 | 17.67 | 25.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 25.66 | 19.17 | 25.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 25.92 | 20.67 | 25.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 26.28 | 15.67 | 26.26 |
November | 3.83 | 19.58 | 3.83 | 19.58 | 6.67 | 23.31 | 6.67 | 24.67 |
December | 17.67 | 18.87 | 17.67 | 18.87 | 0.50 | 18.98 | 0.50 | 19.10 |
Annual Sum or Average | 63.67 | 19.13 | 63.67 | 19.13 | 104.50 | 22.11 | 103.00 | 23.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.98 | 0.00 | 19.10 |
Maximum of Months | 18.67 | 20.14 | 18.67 | 20.14 | 21.17 | 26.28 | 20.67 | 26.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.78 | 2.33 | 27.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.85 | 4.50 | 27.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.90 | 4.00 | 27.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.78 | 6.33 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.97 | 4.50 | 28.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.82 | 5.17 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.72 | 3.67 | 27.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 48.50 | 27.84 | 30.67 | 27.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.97 | 6.33 | 28.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.33 | 27.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.36 | 2.50 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.34 | 2.33 | 27.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.33 | 1.83 | 27.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.17 | 27.34 | 7.00 | 27.35 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.36 | 2.50 | 27.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.66 | 4.83 | 27.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.71 | 11.33 | 27.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.78 | 10.67 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 27.74 | 15.83 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.77 | 10.17 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.66 | 9.00 | 27.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.51 | 2.17 | 27.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 68.67 | 27.72 | 64.00 | 27.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 27.78 | 15.83 | 27.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.27 | 0.50 | 27.27 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.48 | 4.17 | 27.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.50 | 27.30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.46 | 2.33 | 27.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.37 | 4.50 | 27.37 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.38 | 3.67 | 27.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.41 | 6.67 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.56 | 6.33 | 27.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.72 | 7.67 | 27.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.93 | 7.83 | 27.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.68 | 6.17 | 27.68 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.36 | 0.67 | 27.36 |
Annual Sum or Average | 0.00 | 0.00 | 54.17 | 27.58 | 51.00 | 27.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.27 | 0.50 | 27.27 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.93 | 7.83 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.46 | 0.83 | 27.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.50 | 1.33 | 27.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.00 | 4.33 | 28.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.16 | 5.33 | 28.22 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.16 | 5.00 | 28.24 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.96 | 6.83 | 28.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.10 | 4.83 | 28.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.98 | 5.00 | 28.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.78 | 4.17 | 27.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.35 | 0.17 | 27.35 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 59.17 | 28.01 | 37.83 | 28.06 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 28.16 | 6.83 | 28.24 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 409.83 | 24.01 | 0.00 | 24.01 | 0.00 | 24.01 |
February | 335.17 | 24.08 | 7.83 | 24.09 | 0.00 | 24.09 |
March | 339.33 | 24.03 | 7.17 | 24.05 | 0.00 | 24.05 |
April | 118.83 | 24.02 | 70.83 | 24.53 | 0.00 | 24.53 |
May | 13.33 | 24.00 | 221.00 | 24.74 | 0.00 | 24.74 |
June | 0.00 | 0.00 | 344.00 | 24.52 | 0.00 | 24.52 |
July | 19.67 | 24.29 | 495.33 | 24.45 | 19.67 | 24.44 |
August | 0.00 | 0.00 | 502.33 | 24.41 | 0.00 | 24.41 |
September | 2.67 | 26.42 | 436.50 | 24.52 | 2.67 | 24.53 |
October | 4.00 | 24.00 | 296.17 | 24.68 | 0.00 | 24.68 |
November | 188.50 | 24.02 | 63.83 | 24.26 | 0.00 | 24.26 |
December | 437.50 | 24.05 | 0.00 | 24.05 | 0.00 | 24.05 |
Annual Sum or Average | 1868.83 | 24.04 | 2445.00 | 24.34 | 22.33 | 24.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 24.01 | 0.00 | 24.01 |
Maximum of Months | 437.50 | 26.42 | 502.33 | 24.74 | 19.67 | 24.74 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.50 | 23.09 | 0.00 | 23.09 | 0.00 | 23.09 |
February | 447.00 | 23.45 | 0.00 | 23.45 | 0.00 | 23.45 |
March | 500.00 | 23.74 | 0.83 | 23.74 | 0.00 | 23.74 |
April | 233.17 | 23.96 | 22.50 | 24.06 | 0.00 | 24.06 |
May | 43.00 | 24.02 | 175.17 | 24.48 | 0.00 | 24.48 |
June | 1.33 | 24.00 | 316.50 | 24.45 | 0.00 | 24.45 |
July | 25.83 | 24.22 | 493.33 | 24.37 | 25.83 | 24.36 |
August | 4.00 | 24.00 | 487.67 | 24.32 | 4.00 | 24.32 |
September | 8.17 | 24.63 | 403.50 | 24.39 | 8.17 | 24.40 |
October | 64.17 | 23.87 | 201.83 | 24.25 | 1.17 | 24.25 |
November | 387.33 | 23.59 | 11.50 | 23.62 | 0.00 | 23.62 |
December | 497.00 | 22.98 | 1.17 | 22.97 | 1.17 | 22.97 |
Annual Sum or Average | 2712.50 | 23.45 | 2114.00 | 23.86 | 40.33 | 23.87 |
Minimum of Months | 1.33 | 22.98 | 0.00 | 22.97 | 0.00 | 22.97 |
Maximum of Months | 501.50 | 24.63 | 493.33 | 24.48 | 25.83 | 24.48 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.13 | 77.83 | 21.92 | 77.83 | 21.76 |
February | 454.00 | 22.69 | 35.17 | 22.56 | 35.17 | 22.45 |
March | 513.83 | 23.30 | 4.83 | 23.27 | 4.83 | 23.25 |
April | 267.83 | 23.79 | 21.33 | 23.86 | 0.00 | 23.86 |
May | 72.83 | 23.91 | 179.67 | 24.38 | 0.00 | 24.38 |
June | 4.50 | 24.00 | 331.33 | 24.46 | 0.00 | 24.46 |
July | 27.83 | 24.10 | 494.50 | 24.40 | 27.83 | 24.38 |
August | 4.17 | 24.00 | 485.50 | 24.34 | 4.17 | 24.34 |
September | 28.00 | 23.92 | 387.00 | 24.32 | 10.00 | 24.32 |
October | 193.17 | 23.58 | 141.17 | 23.84 | 1.33 | 23.84 |
November | 438.00 | 22.86 | 16.50 | 22.78 | 16.50 | 22.72 |
December | 497.00 | 21.89 | 120.50 | 21.63 | 120.50 | 21.46 |
Annual Sum or Average | 3003.17 | 22.81 | 2295.33 | 23.31 | 298.17 | 23.20 |
Minimum of Months | 4.17 | 21.89 | 4.83 | 21.63 | 0.00 | 21.46 |
Maximum of Months | 513.83 | 24.10 | 494.50 | 24.46 | 120.50 | 24.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.95 | 271.67 | 20.71 | 271.67 | 20.60 |
February | 454.00 | 21.58 | 160.50 | 21.30 | 160.50 | 21.13 |
March | 512.00 | 22.39 | 97.33 | 22.10 | 97.33 | 21.89 |
April | 290.17 | 23.24 | 55.00 | 23.35 | 10.00 | 23.28 |
May | 104.67 | 23.85 | 218.00 | 24.37 | 6.00 | 24.42 |
June | 17.83 | 25.98 | 402.33 | 24.59 | 11.50 | 24.65 |
July | 90.33 | 25.33 | 496.50 | 24.68 | 90.33 | 24.76 |
August | 34.50 | 25.00 | 482.50 | 24.44 | 28.33 | 24.49 |
September | 87.50 | 23.97 | 356.67 | 24.28 | 37.83 | 24.33 |
October | 286.67 | 22.96 | 124.33 | 23.34 | 9.67 | 23.35 |
November | 463.83 | 21.76 | 121.50 | 21.46 | 121.50 | 21.26 |
December | 497.00 | 20.74 | 318.50 | 20.54 | 318.50 | 20.45 |
Annual Sum or Average | 3340.50 | 22.07 | 3104.83 | 22.60 | 1163.17 | 22.37 |
Minimum of Months | 17.83 | 20.74 | 55.00 | 20.54 | 6.00 | 20.45 |
Maximum of Months | 512.00 | 25.98 | 496.50 | 24.68 | 318.50 | 24.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.58 | 163.83 | 21.21 | 163.83 | 20.99 |
February | 430.50 | 22.31 | 86.00 | 22.00 | 83.83 | 21.76 |
March | 393.67 | 22.76 | 58.67 | 22.55 | 50.83 | 22.34 |
April | 164.00 | 23.52 | 139.67 | 24.14 | 10.83 | 24.15 |
May | 78.33 | 25.05 | 328.50 | 24.72 | 31.17 | 24.89 |
June | 39.17 | 26.87 | 448.83 | 24.75 | 36.50 | 24.91 |
July | 118.67 | 25.87 | 497.00 | 24.88 | 118.67 | 25.04 |
August | 59.17 | 26.06 | 497.50 | 24.64 | 56.67 | 24.78 |
September | 84.00 | 25.41 | 412.33 | 24.63 | 61.83 | 24.81 |
October | 194.50 | 23.01 | 199.17 | 23.78 | 10.67 | 23.80 |
November | 432.17 | 22.39 | 81.67 | 22.15 | 68.00 | 21.92 |
December | 497.00 | 21.33 | 215.50 | 20.98 | 215.50 | 20.80 |
Annual Sum or Average | 2993.17 | 22.64 | 3128.67 | 23.21 | 908.33 | 23.10 |
Minimum of Months | 39.17 | 21.33 | 58.67 | 20.98 | 10.67 | 20.80 |
Maximum of Months | 502.00 | 26.87 | 497.50 | 24.88 | 215.50 | 25.04 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 376.67 | 21.80 | 154.33 | 21.61 | 124.00 | 21.32 |
February | 315.50 | 22.12 | 109.00 | 22.10 | 77.67 | 21.84 |
March | 341.33 | 22.55 | 89.17 | 22.47 | 64.00 | 22.23 |
April | 219.17 | 23.26 | 114.33 | 23.72 | 14.33 | 23.68 |
May | 114.00 | 23.98 | 240.00 | 24.40 | 13.17 | 24.49 |
June | 27.00 | 25.57 | 393.83 | 24.58 | 13.67 | 24.65 |
July | 95.33 | 25.38 | 495.67 | 24.68 | 95.33 | 24.78 |
August | 47.83 | 25.60 | 483.33 | 24.54 | 41.83 | 24.64 |
September | 84.33 | 24.95 | 399.00 | 24.55 | 55.83 | 24.69 |
October | 195.33 | 23.61 | 269.00 | 24.16 | 35.00 | 24.33 |
November | 294.67 | 22.22 | 155.50 | 22.52 | 66.67 | 22.28 |
December | 382.17 | 21.73 | 154.67 | 21.43 | 140.83 | 21.17 |
Annual Sum or Average | 2493.33 | 22.71 | 3057.83 | 23.38 | 742.33 | 23.25 |
Minimum of Months | 27.00 | 21.73 | 89.17 | 21.43 | 13.17 | 21.17 |
Maximum of Months | 382.17 | 25.60 | 495.67 | 24.68 | 140.83 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 475.67 | 21.36 | 212.00 | 21.01 | 211.83 | 20.82 |
February | 407.50 | 21.83 | 140.50 | 21.58 | 131.33 | 21.36 |
March | 401.17 | 22.38 | 106.33 | 22.23 | 84.67 | 22.00 |
April | 232.67 | 23.34 | 122.83 | 23.75 | 19.83 | 23.77 |
May | 116.33 | 24.37 | 285.33 | 24.55 | 25.33 | 24.70 |
June | 32.50 | 26.32 | 416.83 | 24.68 | 24.00 | 24.81 |
July | 101.83 | 25.50 | 496.17 | 24.75 | 101.83 | 24.86 |
August | 50.33 | 25.65 | 489.50 | 24.57 | 46.00 | 24.67 |
September | 87.67 | 24.64 | 390.67 | 24.48 | 57.17 | 24.59 |
October | 233.00 | 23.20 | 208.00 | 23.80 | 22.33 | 23.89 |
November | 389.50 | 21.90 | 129.67 | 21.75 | 100.67 | 21.51 |
December | 492.33 | 21.27 | 253.50 | 20.92 | 253.50 | 20.74 |
Annual Sum or Average | 3020.50 | 22.39 | 3251.33 | 22.98 | 1078.50 | 22.80 |
Minimum of Months | 32.50 | 21.27 | 106.33 | 20.92 | 19.83 | 20.74 |
Maximum of Months | 492.33 | 26.32 | 496.17 | 24.75 | 253.50 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.38 | 138.83 | 21.23 | 138.83 | 21.13 |
February | 454.00 | 21.65 | 117.33 | 21.46 | 117.33 | 21.34 |
March | 514.00 | 22.19 | 62.50 | 22.03 | 62.50 | 21.90 |
April | 398.67 | 23.37 | 3.00 | 23.37 | 1.50 | 23.36 |
May | 143.00 | 23.80 | 149.50 | 24.12 | 0.00 | 24.12 |
June | 6.50 | 24.09 | 342.33 | 24.43 | 0.00 | 24.43 |
July | 44.00 | 24.53 | 495.00 | 24.48 | 44.00 | 24.49 |
August | 8.67 | 24.21 | 501.00 | 24.38 | 8.67 | 24.38 |
September | 29.00 | 24.23 | 397.67 | 24.38 | 15.17 | 24.39 |
October | 190.50 | 23.65 | 157.00 | 23.89 | 3.00 | 23.90 |
November | 453.17 | 22.64 | 12.67 | 22.59 | 12.67 | 22.54 |
December | 497.00 | 21.44 | 152.67 | 21.26 | 152.67 | 21.15 |
Annual Sum or Average | 3240.50 | 22.30 | 2529.50 | 22.91 | 556.33 | 22.76 |
Minimum of Months | 6.50 | 21.38 | 3.00 | 21.23 | 0.00 | 21.13 |
Maximum of Months | 514.00 | 24.53 | 501.00 | 24.48 | 152.67 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.24 | 56.67 | 22.07 | 56.67 | 21.93 |
February | 439.00 | 22.67 | 36.33 | 22.54 | 34.67 | 22.41 |
March | 460.00 | 23.03 | 26.83 | 22.95 | 22.83 | 22.85 |
April | 192.50 | 23.69 | 97.50 | 24.20 | 1.00 | 24.22 |
May | 49.83 | 24.63 | 284.83 | 24.68 | 11.17 | 24.75 |
June | 17.50 | 27.03 | 436.33 | 24.64 | 17.17 | 24.72 |
July | 85.50 | 25.88 | 496.83 | 24.82 | 85.50 | 24.96 |
August | 33.50 | 26.48 | 511.50 | 24.62 | 33.50 | 24.72 |
September | 50.33 | 26.37 | 445.00 | 24.74 | 46.33 | 24.90 |
October | 81.50 | 23.76 | 252.17 | 24.35 | 4.17 | 24.37 |
November | 363.67 | 23.19 | 28.17 | 23.28 | 3.00 | 23.26 |
December | 497.00 | 22.32 | 60.17 | 22.14 | 60.17 | 21.99 |
Annual Sum or Average | 2772.33 | 23.04 | 2732.33 | 23.68 | 376.17 | 23.68 |
Minimum of Months | 17.50 | 22.24 | 26.83 | 22.07 | 1.00 | 21.93 |
Maximum of Months | 502.00 | 27.03 | 511.50 | 24.82 | 85.50 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 370.00 | 22.22 | 63.50 | 22.30 | 31.83 | 22.12 |
February | 346.17 | 22.37 | 48.00 | 22.53 | 20.50 | 22.38 |
March | 413.17 | 22.62 | 44.17 | 22.65 | 23.50 | 22.52 |
April | 284.00 | 23.19 | 61.83 | 23.50 | 4.17 | 23.46 |
May | 138.83 | 23.46 | 154.50 | 24.05 | 0.00 | 24.05 |
June | 20.17 | 23.49 | 326.33 | 24.46 | 0.50 | 24.46 |
July | 77.33 | 24.35 | 494.50 | 24.49 | 77.33 | 24.47 |
August | 37.83 | 24.47 | 500.83 | 24.46 | 35.83 | 24.47 |
September | 68.33 | 25.24 | 438.67 | 24.69 | 55.50 | 24.80 |
October | 87.83 | 24.16 | 322.83 | 24.56 | 32.50 | 24.71 |
November | 228.17 | 22.80 | 121.67 | 23.52 | 9.33 | 23.49 |
December | 364.33 | 22.24 | 59.50 | 22.22 | 39.00 | 22.01 |
Annual Sum or Average | 2436.17 | 22.82 | 2636.33 | 23.65 | 330.00 | 23.62 |
Minimum of Months | 20.17 | 22.22 | 44.17 | 22.22 | 0.00 | 22.01 |
Maximum of Months | 413.17 | 25.24 | 500.83 | 24.69 | 77.33 | 24.80 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 487.50 | 22.07 | 63.17 | 21.92 | 62.67 | 21.79 |
February | 437.00 | 22.31 | 57.17 | 22.19 | 51.83 | 22.05 |
March | 449.33 | 22.76 | 29.50 | 22.76 | 18.83 | 22.69 |
April | 248.33 | 23.58 | 83.50 | 23.94 | 2.00 | 23.96 |
May | 90.17 | 24.25 | 264.17 | 24.52 | 10.33 | 24.59 |
June | 15.83 | 26.65 | 404.67 | 24.61 | 13.67 | 24.68 |
July | 72.00 | 25.52 | 496.17 | 24.71 | 72.00 | 24.80 |
August | 30.17 | 26.13 | 510.83 | 24.59 | 30.17 | 24.67 |
September | 38.33 | 25.92 | 437.33 | 24.66 | 35.00 | 24.76 |
October | 77.33 | 24.16 | 258.33 | 24.43 | 12.67 | 24.50 |
November | 347.00 | 23.03 | 42.50 | 23.18 | 3.83 | 23.15 |
December | 491.50 | 22.13 | 79.33 | 21.93 | 79.33 | 21.77 |
Annual Sum or Average | 2784.50 | 22.83 | 2726.67 | 23.54 | 392.33 | 23.51 |
Minimum of Months | 15.83 | 22.07 | 29.50 | 21.92 | 2.00 | 21.77 |
Maximum of Months | 491.50 | 26.65 | 510.83 | 24.71 | 79.33 | 24.80 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.48 | 138.67 | 21.28 | 138.67 | 21.16 |
February | 454.00 | 22.11 | 72.33 | 21.91 | 72.33 | 21.77 |
March | 514.00 | 22.82 | 29.67 | 22.71 | 29.67 | 22.61 |
April | 277.17 | 23.57 | 33.17 | 23.68 | 0.00 | 23.68 |
May | 75.00 | 23.91 | 216.33 | 24.44 | 0.33 | 24.45 |
June | 2.83 | 27.25 | 388.50 | 24.57 | 2.83 | 24.59 |
July | 67.67 | 25.02 | 497.00 | 24.61 | 67.67 | 24.65 |
August | 16.67 | 24.61 | 494.50 | 24.41 | 16.67 | 24.41 |
September | 49.17 | 24.01 | 388.17 | 24.32 | 25.33 | 24.33 |
October | 239.67 | 23.42 | 143.67 | 23.71 | 6.33 | 23.72 |
November | 453.67 | 22.39 | 41.83 | 22.24 | 41.83 | 22.11 |
December | 497.00 | 21.31 | 198.67 | 21.09 | 198.67 | 20.97 |
Annual Sum or Average | 3148.83 | 22.42 | 2642.50 | 23.03 | 600.33 | 22.88 |
Minimum of Months | 2.83 | 21.31 | 29.67 | 21.09 | 0.00 | 20.97 |
Maximum of Months | 514.00 | 27.25 | 497.00 | 24.61 | 198.67 | 24.65 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 424.67 | 22.02 | 77.83 | 21.77 | 77.83 | 21.58 |
February | 348.50 | 22.61 | 43.33 | 22.48 | 36.83 | 22.31 |
March | 343.83 | 23.06 | 31.67 | 23.09 | 16.33 | 22.99 |
April | 137.33 | 23.76 | 114.33 | 24.41 | 5.50 | 24.47 |
May | 54.50 | 25.34 | 267.50 | 24.90 | 24.67 | 25.06 |
June | 32.83 | 27.03 | 368.83 | 24.88 | 32.67 | 25.04 |
July | 108.00 | 26.01 | 422.00 | 25.02 | 108.00 | 25.18 |
August | 49.83 | 26.26 | 425.00 | 24.74 | 49.83 | 24.89 |
September | 62.33 | 25.88 | 354.67 | 24.78 | 51.83 | 24.96 |
October | 150.67 | 23.56 | 187.00 | 24.16 | 8.67 | 24.21 |
November | 340.17 | 22.75 | 40.17 | 22.75 | 20.83 | 22.63 |
December | 422.00 | 21.89 | 108.00 | 21.59 | 108.00 | 21.39 |
Annual Sum or Average | 2474.67 | 23.01 | 2440.33 | 23.63 | 541.00 | 23.62 |
Minimum of Months | 32.83 | 21.89 | 31.67 | 21.59 | 5.50 | 21.39 |
Maximum of Months | 424.67 | 27.03 | 425.00 | 25.02 | 108.00 | 25.18 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 347.17 | 22.29 | 94.00 | 22.31 | 55.50 | 22.10 |
February | 293.33 | 22.63 | 63.50 | 22.82 | 28.67 | 22.67 |
March | 327.33 | 23.02 | 38.50 | 23.19 | 12.83 | 23.11 |
April | 191.67 | 23.55 | 99.00 | 24.03 | 1.00 | 24.04 |
May | 79.17 | 23.96 | 231.00 | 24.47 | 3.17 | 24.50 |
June | 8.83 | 25.26 | 383.17 | 24.55 | 3.33 | 24.57 |
July | 84.83 | 25.31 | 496.17 | 24.65 | 84.83 | 24.74 |
August | 34.50 | 25.90 | 497.00 | 24.53 | 34.50 | 24.61 |
September | 65.67 | 25.49 | 424.67 | 24.62 | 51.50 | 24.76 |
October | 145.83 | 24.14 | 296.00 | 24.43 | 32.67 | 24.59 |
November | 265.00 | 22.85 | 120.50 | 23.38 | 20.67 | 23.34 |
December | 348.33 | 22.25 | 95.17 | 22.14 | 72.00 | 21.90 |
Annual Sum or Average | 2191.67 | 23.08 | 2838.67 | 23.80 | 400.67 | 23.77 |
Minimum of Months | 8.83 | 22.25 | 38.50 | 22.14 | 1.00 | 21.90 |
Maximum of Months | 348.33 | 25.90 | 497.00 | 24.65 | 84.83 | 24.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 468.50 | 21.88 | 107.00 | 21.64 | 105.33 | 21.46 |
February | 400.50 | 22.35 | 64.83 | 22.24 | 54.83 | 22.08 |
March | 399.33 | 22.89 | 38.67 | 22.96 | 17.33 | 22.88 |
April | 211.83 | 23.70 | 109.00 | 24.09 | 8.00 | 24.17 |
May | 85.83 | 24.70 | 288.00 | 24.65 | 23.00 | 24.79 |
June | 21.83 | 26.94 | 414.33 | 24.69 | 20.50 | 24.80 |
July | 94.17 | 25.48 | 496.50 | 24.74 | 94.17 | 24.84 |
August | 41.83 | 25.79 | 501.83 | 24.57 | 41.83 | 24.65 |
September | 68.00 | 25.07 | 414.33 | 24.55 | 50.50 | 24.65 |
October | 176.50 | 23.68 | 228.67 | 24.12 | 19.83 | 24.20 |
November | 368.33 | 22.52 | 69.17 | 22.58 | 31.67 | 22.44 |
December | 480.83 | 21.79 | 142.17 | 21.49 | 142.17 | 21.30 |
Annual Sum or Average | 2817.50 | 22.79 | 2874.50 | 23.44 | 609.17 | 23.38 |
Minimum of Months | 21.83 | 21.79 | 38.67 | 21.49 | 8.00 | 21.30 |
Maximum of Months | 480.83 | 26.94 | 501.83 | 24.74 | 142.17 | 24.84 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.11007 | 20.90211 | 0.20088 | 5.94889 |
February | 454.00000 | 24.20442 | 17.47654 | 0.21435 | 6.06614 |
March | 514.00000 | 24.26351 | 17.03228 | 0.24192 | 6.35287 |
April | 485.00000 | 24.38023 | 20.41470 | 0.32485 | 7.44166 |
May | 508.00000 | 24.39478 | 29.01572 | -0.4399 | 9.54687 |
June | 496.00000 | 24.38660 | 35.09726 | -0.3799 | 8.48654 |
July | 497.00000 | 24.45321 | 46.42636 | -0.2808 | 7.10073 |
August | 514.00000 | 24.39898 | 44.33806 | -0.3112 | 7.43299 |
September | 485.00000 | 24.45911 | 41.88434 | -0.3158 | 7.69982 |
October | 502.00000 | 24.42228 | 34.14247 | 0.44515 | 9.46449 |
November | 489.00000 | 24.32759 | 21.96327 | 0.30157 | 7.12377 |
December | 497.00000 | 24.12018 | 17.99578 | 0.18309 | 5.81542 |
Annual Sum or Average | 5943.00000 | 24.32729 | 28.98068 | 0.01303 | 7.38399 |
Minimum of Months | 454.00000 | 24.11007 | 17.03228 | -0.4399 | 5.81542 |
Maximum of Months | 514.00000 | 24.45911 | 46.42636 | 0.44515 | 9.54687 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.08874 | 23.09885 | -0.0485 | 5.57001 |
February | 454.00000 | 23.46220 | 19.03533 | 0.02861 | 5.45124 |
March | 514.00000 | 23.77387 | 17.88855 | 0.11123 | 5.50566 |
April | 485.00000 | 24.14344 | 21.27956 | 0.25756 | 6.59267 |
May | 508.00000 | 24.28349 | 30.00600 | -0.4950 | 10.55144 |
June | 496.00000 | 24.32348 | 36.20217 | -0.4163 | 9.02258 |
July | 497.00000 | 24.37024 | 48.58134 | -0.3154 | 7.42238 |
August | 514.00000 | 24.31220 | 46.18811 | -0.3548 | 7.92407 |
September | 485.00000 | 24.33219 | 43.56428 | -0.3786 | 8.42479 |
October | 502.00000 | 24.17752 | 35.47155 | 0.36844 | 8.04979 |
November | 489.00000 | 23.72406 | 23.62390 | 0.13619 | 5.91098 |
December | 497.00000 | 22.97787 | 20.14845 | -0.0952 | 5.83602 |
Annual Sum or Average | 5943.00000 | 23.91721 | 30.51307 | -0.1019 | 7.20403 |
Minimum of Months | 454.00000 | 22.97787 | 17.88855 | -0.4950 | 5.45124 |
Maximum of Months | 514.00000 | 24.37024 | 48.58134 | 0.36844 | 10.55144 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.13103 | 24.36704 | -0.2835 | 7.96363 |
February | 454.00000 | 22.69177 | 19.92668 | -0.1602 | 6.74658 |
March | 514.00000 | 23.29780 | 18.49021 | -0.0082 | 5.83616 |
April | 485.00000 | 23.98969 | 21.17479 | 0.21775 | 6.43073 |
May | 508.00000 | 24.25422 | 29.67588 | -0.5002 | 10.81267 |
June | 496.00000 | 24.33629 | 35.70102 | -0.3969 | 8.75285 |
July | 497.00000 | 24.41447 | 47.68163 | -0.2905 | 7.23347 |
August | 514.00000 | 24.32469 | 45.36086 | -0.3470 | 7.88222 |
September | 485.00000 | 24.28746 | 43.05461 | -0.3976 | 8.83638 |
October | 502.00000 | 23.93357 | 35.64720 | 0.29920 | 7.27880 |
November | 489.00000 | 22.98095 | 24.76255 | -0.0505 | 6.50448 |
December | 497.00000 | 21.88892 | 21.23959 | -0.3635 | 9.23987 |
Annual Sum or Average | 5943.00000 | 23.55061 | 30.67312 | -0.1910 | 7.80290 |
Minimum of Months | 454.00000 | 21.88892 | 18.49021 | -0.5002 | 5.83616 |
Maximum of Months | 514.00000 | 24.41447 | 47.68163 | 0.29920 | 10.81267 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.94723 | 26.19256 | -0.5784 | 13.60810 |
February | 454.00000 | 21.58448 | 22.30109 | -0.4265 | 10.77194 |
March | 514.00000 | 22.39900 | 20.04838 | -0.2224 | 8.07930 |
April | 485.00000 | 23.65663 | 21.92009 | 0.14178 | 6.87503 |
May | 508.00000 | 24.24281 | 29.48711 | -0.4800 | 11.38170 |
June | 496.00000 | 24.44153 | 35.53253 | -0.3066 | 7.93316 |
July | 497.00000 | 24.55583 | 48.62694 | -0.1851 | 6.85308 |
August | 514.00000 | 24.36924 | 45.96772 | -0.2986 | 7.77871 |
September | 485.00000 | 24.20120 | 44.30789 | -0.4088 | 9.94375 |
October | 502.00000 | 23.46178 | 38.06019 | 0.19036 | 7.04880 |
November | 489.00000 | 21.87719 | 26.96810 | -0.3172 | 9.69123 |
December | 497.00000 | 20.73558 | 23.45680 | -0.6561 | 15.81441 |
Annual Sum or Average | 5943.00000 | 23.05043 | 31.97863 | -0.2953 | 9.63989 |
Minimum of Months | 454.00000 | 20.73558 | 20.04838 | -0.6561 | 6.85308 |
Maximum of Months | 514.00000 | 24.55583 | 48.62694 | 0.19036 | 15.81441 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.57530 | 26.26942 | -0.4116 | 11.03574 |
February | 454.00000 | 22.42050 | 21.76731 | -0.2084 | 8.64717 |
March | 514.00000 | 23.10581 | 18.76268 | -0.0247 | 7.34515 |
April | 485.00000 | 24.11542 | 20.80402 | 0.30750 | 8.60201 |
May | 508.00000 | 24.41926 | 28.95789 | -0.3269 | 9.44007 |
June | 496.00000 | 24.51796 | 35.20218 | -0.1884 | 7.30525 |
July | 497.00000 | 24.64735 | 48.03263 | -0.0720 | 7.00665 |
August | 514.00000 | 24.44982 | 45.54640 | -0.1837 | 7.25226 |
September | 485.00000 | 24.38315 | 43.33570 | -0.2571 | 8.49181 |
October | 502.00000 | 23.82235 | 36.75646 | 0.31060 | 8.73308 |
November | 489.00000 | 22.58698 | 26.22002 | -0.1291 | 8.21267 |
December | 497.00000 | 21.32784 | 23.77792 | -0.4949 | 12.60725 |
Annual Sum or Average | 5943.00000 | 23.45525 | 31.35896 | -0.1401 | 8.72058 |
Minimum of Months | 454.00000 | 21.32784 | 18.76268 | -0.4949 | 7.00665 |
Maximum of Months | 514.00000 | 24.64735 | 48.03263 | 0.31060 | 12.60725 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.43742 | 22.79775 | -0.1721 | 10.24267 |
February | 454.00000 | 22.84815 | 19.33648 | -0.0782 | 9.23601 |
March | 514.00000 | 23.16112 | 17.79423 | 0.00146 | 8.09133 |
April | 485.00000 | 23.87410 | 21.07933 | 0.22851 | 8.02953 |
May | 508.00000 | 24.24164 | 29.40654 | -0.4649 | 11.47393 |
June | 496.00000 | 24.41985 | 35.59294 | -0.3175 | 8.17107 |
July | 497.00000 | 24.54202 | 48.65075 | -0.1845 | 6.97374 |
August | 514.00000 | 24.39585 | 45.69448 | -0.2505 | 7.54140 |
September | 485.00000 | 24.34484 | 43.28219 | -0.2703 | 8.79940 |
October | 502.00000 | 23.97341 | 35.61709 | 0.38608 | 10.38059 |
November | 489.00000 | 23.11555 | 23.62932 | 0.04339 | 9.45551 |
December | 497.00000 | 22.31452 | 20.29836 | -0.2268 | 10.82961 |
Annual Sum or Average | 5943.00000 | 23.64462 | 30.34942 | -0.1099 | 9.10263 |
Minimum of Months | 454.00000 | 22.31452 | 17.79423 | -0.4649 | 6.97374 |
Maximum of Months | 514.00000 | 24.54202 | 48.65075 | 0.38608 | 11.47393 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.50902 | 25.65629 | -0.4295 | 12.07830 |
February | 454.00000 | 22.10890 | 21.82413 | -0.2856 | 10.08241 |
March | 514.00000 | 22.81588 | 19.37571 | -0.0910 | 8.34282 |
April | 485.00000 | 23.85161 | 21.55534 | 0.23868 | 8.47726 |
May | 508.00000 | 24.30569 | 29.34822 | -0.3802 | 10.77868 |
June | 496.00000 | 24.48329 | 35.46370 | -0.2206 | 7.76910 |
July | 497.00000 | 24.59987 | 48.54409 | -0.1073 | 7.06649 |
August | 514.00000 | 24.43036 | 45.80683 | -0.2074 | 7.61405 |
September | 485.00000 | 24.30677 | 43.87610 | -0.2911 | 9.10614 |
October | 502.00000 | 23.74591 | 37.24308 | 0.29969 | 8.87026 |
November | 489.00000 | 22.39070 | 26.04314 | -0.1708 | 9.42082 |
December | 497.00000 | 21.29886 | 23.23733 | -0.5072 | 13.76985 |
Annual Sum or Average | 5943.00000 | 23.32972 | 31.57178 | -0.1792 | 9.44218 |
Minimum of Months | 454.00000 | 21.29886 | 19.37571 | -0.5072 | 7.06649 |
Maximum of Months | 514.00000 | 24.59987 | 48.54409 | 0.29969 | 13.76985 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.38029 | 26.41534 | -0.4471 | 9.87371 |
February | 454.00000 | 21.65498 | 22.91319 | -0.4002 | 9.29357 |
March | 514.00000 | 22.18733 | 21.63012 | -0.2765 | 7.61811 |
April | 485.00000 | 23.50193 | 23.23362 | 0.07852 | 5.96808 |
May | 508.00000 | 24.13237 | 30.25775 | -0.5652 | 12.41668 |
June | 496.00000 | 24.33297 | 35.78241 | -0.3947 | 8.68400 |
July | 497.00000 | 24.47753 | 47.67755 | -0.2503 | 6.87460 |
August | 514.00000 | 24.37256 | 45.25877 | -0.3139 | 7.52800 |
September | 485.00000 | 24.32593 | 43.21832 | -0.3671 | 8.46627 |
October | 502.00000 | 23.93213 | 36.87617 | 0.30650 | 7.36029 |
November | 489.00000 | 22.74018 | 26.31112 | -0.0949 | 6.37443 |
December | 497.00000 | 21.44100 | 23.24992 | -0.4488 | 10.03114 |
Annual Sum or Average | 5943.00000 | 23.21662 | 31.97394 | -0.2646 | 8.37804 |
Minimum of Months | 454.00000 | 21.38029 | 21.63012 | -0.5652 | 5.96808 |
Maximum of Months | 514.00000 | 24.47753 | 47.67755 | 0.30650 | 12.41668 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.23866 | 26.22703 | -0.2319 | 7.49390 |
February | 454.00000 | 22.74137 | 22.20366 | -0.1271 | 6.87472 |
March | 514.00000 | 23.17927 | 20.12971 | -0.0169 | 6.40070 |
April | 485.00000 | 24.15951 | 21.49042 | 0.28887 | 7.69041 |
May | 508.00000 | 24.41781 | 29.30000 | -0.3748 | 9.35475 |
June | 496.00000 | 24.48921 | 35.19947 | -0.2486 | 7.36075 |
July | 497.00000 | 24.63772 | 46.89838 | -0.1137 | 6.62803 |
August | 514.00000 | 24.49295 | 44.68766 | -0.1824 | 6.76162 |
September | 485.00000 | 24.51391 | 42.26822 | -0.2074 | 7.31772 |
October | 502.00000 | 24.24343 | 35.66231 | 0.42163 | 9.44157 |
November | 489.00000 | 23.47041 | 25.00673 | 0.10089 | 6.41065 |
December | 497.00000 | 22.32132 | 23.18965 | -0.2296 | 7.55146 |
Annual Sum or Average | 5943.00000 | 23.74816 | 31.09429 | -0.0775 | 7.44611 |
Minimum of Months | 454.00000 | 22.23866 | 20.12971 | -0.3748 | 6.40070 |
Maximum of Months | 514.00000 | 24.63772 | 46.89838 | 0.42163 | 9.44157 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.81875 | 21.54074 | -0.0343 | 7.69105 |
February | 454.00000 | 22.94161 | 18.84469 | -0.0304 | 7.59725 |
March | 514.00000 | 22.99895 | 18.01937 | -0.0325 | 7.04675 |
April | 485.00000 | 23.71820 | 21.30078 | 0.16757 | 6.96247 |
May | 508.00000 | 24.08519 | 29.56745 | -0.5641 | 12.96093 |
June | 496.00000 | 24.33856 | 35.14580 | -0.4039 | 9.02547 |
July | 497.00000 | 24.51187 | 48.56937 | -0.2309 | 6.80217 |
August | 514.00000 | 24.43868 | 45.27170 | -0.2492 | 7.12280 |
September | 485.00000 | 24.50217 | 42.30365 | -0.2106 | 7.51088 |
October | 502.00000 | 24.30923 | 34.79984 | 0.48828 | 11.30549 |
November | 489.00000 | 23.70367 | 22.37645 | 0.22689 | 8.47252 |
December | 497.00000 | 22.83879 | 18.78858 | -0.0453 | 7.67575 |
Annual Sum or Average | 5943.00000 | 23.77169 | 29.79805 | -0.0782 | 8.36068 |
Minimum of Months | 454.00000 | 22.81875 | 18.01937 | -0.5641 | 6.80217 |
Maximum of Months | 514.00000 | 24.51187 | 48.56937 | 0.48828 | 12.96093 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.13549 | 25.76515 | -0.2543 | 7.92160 |
February | 454.00000 | 22.41609 | 22.38166 | -0.2065 | 7.62271 |
March | 514.00000 | 22.98298 | 20.57434 | -0.0656 | 6.74984 |
April | 485.00000 | 23.99082 | 22.09944 | 0.23857 | 7.33114 |
May | 508.00000 | 24.33858 | 29.60393 | -0.4156 | 10.08781 |
June | 496.00000 | 24.45226 | 35.43424 | -0.2797 | 7.68054 |
July | 497.00000 | 24.59318 | 47.31976 | -0.1458 | 6.61023 |
August | 514.00000 | 24.49120 | 44.85952 | -0.1993 | 6.92284 |
September | 485.00000 | 24.49583 | 42.53734 | -0.2233 | 7.28520 |
October | 502.00000 | 24.26662 | 35.70423 | 0.43120 | 9.60069 |
November | 489.00000 | 23.39122 | 25.03503 | 0.08435 | 6.61280 |
December | 497.00000 | 22.15077 | 22.87464 | -0.2684 | 8.07466 |
Annual Sum or Average | 5943.00000 | 23.64982 | 31.25419 | -0.1091 | 7.71324 |
Minimum of Months | 454.00000 | 22.13549 | 20.57434 | -0.4156 | 6.61023 |
Maximum of Months | 514.00000 | 24.59318 | 47.31976 | 0.43120 | 10.08781 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.48044 | 25.56833 | -0.4230 | 9.78256 |
February | 454.00000 | 22.10867 | 21.79247 | -0.2833 | 8.02061 |
March | 514.00000 | 22.82289 | 19.73417 | -0.1118 | 6.48432 |
April | 485.00000 | 23.85850 | 21.94558 | 0.19049 | 6.47980 |
May | 508.00000 | 24.30120 | 29.74516 | -0.4675 | 10.55457 |
June | 496.00000 | 24.44776 | 35.87507 | -0.3214 | 7.95089 |
July | 497.00000 | 24.54976 | 49.17552 | -0.2019 | 6.77468 |
August | 514.00000 | 24.38624 | 46.49296 | -0.3005 | 7.54508 |
September | 485.00000 | 24.28261 | 44.45436 | -0.3827 | 8.89487 |
October | 502.00000 | 23.77795 | 37.52534 | 0.27058 | 7.13034 |
November | 489.00000 | 22.50333 | 26.18431 | -0.1532 | 7.10825 |
December | 497.00000 | 21.31239 | 22.91038 | -0.4856 | 11.06740 |
Annual Sum or Average | 5943.00000 | 23.32823 | 31.86049 | -0.2227 | 8.15216 |
Minimum of Months | 454.00000 | 21.31239 | 19.73417 | -0.4856 | 6.47980 |
Maximum of Months | 514.00000 | 24.54976 | 49.17552 | 0.27058 | 11.06740 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.02918 | 25.41017 | -0.2821 | 8.49405 |
February | 385.00000 | 22.79941 | 20.61549 | -0.1063 | 7.27132 |
March | 433.00000 | 23.35994 | 18.17393 | 0.03847 | 6.73678 |
April | 410.00000 | 24.27030 | 20.61856 | 0.33153 | 8.58307 |
May | 430.00000 | 24.54286 | 28.83072 | -0.3164 | 9.16840 |
June | 418.00000 | 24.62221 | 34.89029 | -0.1983 | 7.47412 |
July | 422.00000 | 24.76228 | 48.01680 | -0.0729 | 7.06783 |
August | 433.00000 | 24.55582 | 45.41567 | -0.1830 | 7.21979 |
September | 410.00000 | 24.52240 | 43.07951 | -0.2384 | 8.15756 |
October | 427.00000 | 24.08258 | 36.22097 | 0.36734 | 9.02774 |
November | 417.00000 | 23.04578 | 24.89958 | -0.0082 | 6.96772 |
December | 422.00000 | 21.88713 | 22.93081 | -0.3384 | 9.33202 |
Annual Sum or Average | 5034.00000 | 23.71110 | 30.83201 | -0.0844 | 7.96206 |
Minimum of Months | 385.00000 | 21.88713 | 18.17393 | -0.3384 | 6.73678 |
Maximum of Months | 433.00000 | 24.76228 | 48.01680 | 0.36734 | 9.33202 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.93147 | 21.98902 | -0.0296 | 8.24588 |
February | 454.00000 | 23.29659 | 18.68785 | 0.04593 | 7.77257 |
March | 514.00000 | 23.51089 | 17.42460 | 0.09493 | 7.09558 |
April | 485.00000 | 24.06534 | 21.08211 | 0.27324 | 7.69074 |
May | 508.00000 | 24.31322 | 29.63348 | -0.4493 | 10.49960 |
June | 496.00000 | 24.42945 | 35.92009 | -0.3313 | 8.14216 |
July | 497.00000 | 24.53981 | 49.16371 | -0.2005 | 6.85955 |
August | 514.00000 | 24.41822 | 46.18264 | -0.2522 | 7.25519 |
September | 485.00000 | 24.42675 | 43.40833 | -0.2474 | 7.87665 |
October | 502.00000 | 24.21652 | 35.26348 | 0.44930 | 10.67708 |
November | 489.00000 | 23.58902 | 22.92310 | 0.17378 | 8.54258 |
December | 497.00000 | 22.87746 | 19.50521 | -0.0650 | 8.41424 |
Annual Sum or Average | 5943.00000 | 23.88839 | 30.18762 | -0.0465 | 8.26102 |
Minimum of Months | 454.00000 | 22.87746 | 17.42460 | -0.4493 | 6.85955 |
Maximum of Months | 514.00000 | 24.53981 | 49.16371 | 0.44930 | 10.67708 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.03268 | 24.90368 | -0.2786 | 8.80368 |
February | 454.00000 | 22.61225 | 21.21804 | -0.1486 | 7.74180 |
March | 514.00000 | 23.22124 | 18.99944 | 0.01420 | 6.95765 |
April | 485.00000 | 24.05984 | 21.51182 | 0.28667 | 8.11341 |
May | 508.00000 | 24.37955 | 29.53961 | -0.3648 | 9.77373 |
June | 496.00000 | 24.49524 | 35.76503 | -0.2349 | 7.62351 |
July | 497.00000 | 24.60112 | 49.04197 | -0.1231 | 6.84940 |
August | 514.00000 | 24.45362 | 46.29701 | -0.2090 | 7.26986 |
September | 485.00000 | 24.39415 | 43.99248 | -0.2658 | 8.08779 |
October | 502.00000 | 24.03109 | 36.73721 | 0.37203 | 9.03302 |
November | 489.00000 | 22.96037 | 25.26199 | -0.0198 | 7.44049 |
December | 497.00000 | 21.86889 | 22.51305 | -0.3411 | 9.71793 |
Annual Sum or Average | 5943.00000 | 23.59965 | 31.39327 | -0.1098 | 8.12014 |
Minimum of Months | 454.00000 | 21.86889 | 18.99944 | -0.3648 | 6.84940 |
Maximum of Months | 514.00000 | 24.60112 | 49.04197 | 0.37203 | 9.77373 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.411514E+10 | 0.109902E+10 | 143.13 | 0.406286E+10 | 52276603.09 | 0.00 | 0.81 | 12-JAN-15:30 | 0.00 | 01-JAN-00:10 | 25119.62 | 12-JAN-15:30 | 25119.62 | 12-JAN-15:30 | 1338.00 | 12-JAN-18:03 | 6059.86 | 12-JAN-15:30 | 0.00 |
February | 0.544566E+10 | 0.144948E+10 | 182.29 | 0.539890E+10 | 46754209.39 | 0.00 | 0.89 | 21-FEB-16:20 | 0.00 | 01-FEB-00:10 | 28204.64 | 21-FEB-16:20 | 28204.64 | 21-FEB-16:20 | 976.95 | 28-FEB-12:02 | 6652.50 | 21-FEB-16:20 | 0.00 |
March | 0.106015E+11 | 0.272822E+10 | 257.14 | 0.105686E+11 | 32862444.86 | 0.00 | 1.00 | 14-MAR-15:20 | 0.00 | 01-MAR-00:10 | 34485.52 | 21-MAR-16:00 | 34485.52 | 21-MAR-16:00 | 584.93 | 03-MAR-19:00 | 8102.65 | 21-MAR-16:00 | 0.00 |
April | 0.251599E+11 | 0.645719E+10 | 332.04 | 0.249609E+11 | 0.198974E+09 | 0.00 | 1.00 | 03-APR-11:30 | 0.00 | 01-APR-00:10 | 55003.83 | 21-APR-15:10 | 55003.83 | 21-APR-15:10 | 3423.65 | 18-APR-21:00 | 15611.77 | 21-APR-15:10 | 0.00 |
May | 0.494511E+11 | 0.129327E+11 | 442.15 | 0.480179E+11 | 0.143319E+10 | 0.00 | 1.00 | 01-MAY-15:10 | 0.00 | 01-MAY-00:10 | 71946.11 | 30-MAY-06:03 | 71946.11 | 30-MAY-06:03 | 12339.21 | 25-MAY-06:03 | 20893.05 | 30-MAY-15:10 | 0.00 |
June | 0.678033E+11 | 0.191784E+11 | 455.53 | 0.651937E+11 | 0.260957E+10 | 0.00 | 1.00 | 01-JUN-07:10 | 0.00 | 01-JUN-00:10 | 86504.63 | 19-JUN-06:03 | 77992.33 | 15-JUN-06:03 | 21799.10 | 19-JUN-18:00 | 24353.69 | 15-JUN-15:10 | 0.00 |
July | 0.797576E+11 | 0.214711E+11 | 468.32 | 0.645328E+11 | 0.152247E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 111618.40 | 20-JUL-15:05 | 89338.81 | 03-JUL-06:03 | 74564.50 | 21-JUL-06:03 | 25122.85 | 20-JUL-15:05 | 0.00 |
August | 0.744828E+11 | 0.196624E+11 | 481.14 | 0.640787E+11 | 0.104041E+11 | 0.00 | 1.00 | 01-AUG-05:12 | 0.00 | 01-AUG-00:10 | 105454.84 | 03-AUG-06:03 | 83381.10 | 07-AUG-06:03 | 59664.43 | 03-AUG-06:03 | 24479.62 | 07-AUG-16:00 | 0.00 |
September | 0.620070E+11 | 0.158838E+11 | 422.83 | 0.538133E+11 | 0.819373E+10 | 0.00 | 1.00 | 01-SEP-05:12 | 0.00 | 01-SEP-00:10 | 103200.02 | 22-SEP-06:03 | 68349.27 | 18-SEP-16:00 | 63888.81 | 22-SEP-06:03 | 23669.89 | 22-SEP-06:03 | 0.00 |
October | 0.322371E+11 | 0.796640E+10 | 347.30 | 0.287023E+11 | 0.353473E+10 | 0.00 | 1.00 | 01-OCT-14:22 | 0.00 | 01-OCT-00:10 | 74801.79 | 04-OCT-10:40 | 68775.59 | 02-OCT-04:02 | 28226.13 | 04-OCT-10:40 | 19809.98 | 03-OCT-14:00 | 0.00 |
November | 0.931457E+10 | 0.235455E+10 | 206.64 | 0.913364E+10 | 0.180936E+09 | 0.00 | 1.00 | 03-NOV-13:50 | 0.00 | 01-NOV-00:10 | 41072.08 | 03-NOV-16:00 | 41072.08 | 03-NOV-16:00 | 3157.15 | 02-NOV-14:30 | 9401.78 | 03-NOV-16:00 | 0.00 |
December | 0.310630E+10 | 0.840676E+09 | 123.74 | 0.307740E+10 | 28900018.83 | 0.00 | 0.64 | 07-DEC-15:40 | 0.00 | 01-DEC-00:10 | 18891.01 | 07-DEC-15:40 | 18891.01 | 07-DEC-15:40 | 997.55 | 14-DEC-17:01 | 4777.04 | 07-DEC-15:40 | 0.00 |
Annual Sum or Average | 0.423482E+12 | 0.112024E+12 | 3862.27 | 0.381541E+12 | 0.419407E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.310630E+10 | 0.840676E+09 | 123.74 | 0.307740E+10 | 28900018.83 | 0.00 | 0.64 | 0.00 | 18891.01 | 18891.01 | 584.93 | 4777.04 | 0.00 | ||||||
Maximum of Months | 0.797576E+11 | 0.214711E+11 | 481.14 | 0.651937E+11 | 0.152247E+11 | 0.00 | 1.00 | 0.00 | 111618.40 | 89338.81 | 74564.50 | 25122.85 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.677606E+09 | 0.187708E+09 | 48.19 | 0.664293E+09 | 13313234.42 | 0.00 | 0.52 | 12-JAN-15:05 | 0.00 | 01-JAN-00:10 | 13272.55 | 12-JAN-15:05 | 13272.55 | 12-JAN-15:05 | 589.22 | 12-JAN-17:05 | 3465.99 | 12-JAN-15:05 | 0.00 |
February | 0.284794E+10 | 0.753916E+09 | 109.08 | 0.282419E+10 | 23746106.79 | 0.00 | 0.87 | 21-FEB-15:05 | 0.00 | 01-FEB-00:10 | 24667.72 | 21-FEB-15:05 | 24667.72 | 21-FEB-15:05 | 845.49 | 27-FEB-15:10 | 5847.53 | 21-FEB-15:05 | 0.00 |
March | 0.730168E+10 | 0.188160E+10 | 215.67 | 0.727317E+10 | 28512296.55 | 0.00 | 1.00 | 14-MAR-15:20 | 0.00 | 01-MAR-00:10 | 32047.24 | 22-MAR-14:05 | 32047.24 | 22-MAR-14:05 | 535.73 | 12-MAR-14:57 | 7408.57 | 22-MAR-14:05 | 0.00 |
April | 0.233293E+11 | 0.599499E+10 | 345.42 | 0.231710E+11 | 0.158310E+09 | 0.00 | 1.00 | 03-APR-11:40 | 0.00 | 01-APR-00:10 | 53794.32 | 21-APR-14:05 | 53794.32 | 21-APR-14:05 | 3358.64 | 30-APR-08:62 | 15347.37 | 21-APR-14:05 | 0.00 |
May | 0.450016E+11 | 0.117831E+11 | 448.37 | 0.439058E+11 | 0.109574E+10 | 0.00 | 1.00 | 01-MAY-14:00 | 0.00 | 01-MAY-00:10 | 69830.95 | 30-MAY-06:03 | 69830.95 | 30-MAY-06:03 | 10463.57 | 22-MAY-06:03 | 20232.19 | 30-MAY-14:05 | 0.00 |
June | 0.619788E+11 | 0.175493E+11 | 459.59 | 0.599519E+11 | 0.202684E+10 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 78212.97 | 19-JUN-06:03 | 69825.19 | 15-JUN-06:03 | 19697.72 | 19-JUN-18:00 | 22888.70 | 15-JUN-14:05 | 0.00 |
July | 0.698032E+11 | 0.187892E+11 | 470.52 | 0.572930E+11 | 0.125101E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 100080.19 | 20-JUL-15:05 | 79411.93 | 03-JUL-06:03 | 65766.97 | 17-JUL-06:03 | 24523.02 | 03-JUL-14:05 | 0.00 |
August | 0.621451E+11 | 0.164902E+11 | 478.05 | 0.543702E+11 | 0.777486E+10 | 0.00 | 1.00 | 01-AUG-05:12 | 0.00 | 01-AUG-00:10 | 94553.77 | 03-AUG-06:03 | 71929.93 | 07-AUG-04:02 | 54067.07 | 03-AUG-06:03 | 22248.26 | 07-AUG-16:00 | 0.00 |
September | 0.499225E+11 | 0.128714E+11 | 417.63 | 0.438874E+11 | 0.603509E+10 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:10 | 76829.70 | 22-SEP-06:03 | 61742.75 | 18-SEP-15:20 | 47558.85 | 22-SEP-06:03 | 18228.53 | 05-SEP-15:30 | 0.00 |
October | 0.253169E+11 | 0.631271E+10 | 338.44 | 0.225832E+11 | 0.273374E+10 | 0.00 | 1.00 | 01-OCT-13:42 | 0.00 | 01-OCT-00:10 | 64519.52 | 03-OCT-14:05 | 62880.57 | 02-OCT-04:02 | 21317.08 | 04-OCT-10:40 | 18508.09 | 03-OCT-14:05 | 0.00 |
November | 0.560973E+10 | 0.144103E+10 | 161.92 | 0.543236E+10 | 0.177370E+09 | 0.00 | 1.00 | 03-NOV-14:05 | 0.00 | 01-NOV-00:10 | 34818.96 | 09-NOV-15:05 | 34818.96 | 09-NOV-15:05 | 3863.12 | 03-NOV-11:00 | 7949.14 | 09-NOV-15:05 | 0.00 |
December | 0.242856E+09 | 69804291.35 | 30.25 | 0.240362E+09 | 2494715.77 | 0.00 | 0.21 | 08-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5110.46 | 08-DEC-14:00 | 5110.46 | 08-DEC-14:00 | 417.49 | 10-DEC-13:00 | 1439.30 | 08-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.354177E+12 | 0.941248E+11 | 3523.11 | 0.321597E+12 | 0.325802E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.242856E+09 | 69804291.35 | 30.25 | 0.240362E+09 | 2494715.77 | 0.00 | 0.21 | 0.00 | 5110.46 | 5110.46 | 417.49 | 1439.30 | 0.00 | ||||||
Maximum of Months | 0.698032E+11 | 0.187892E+11 | 478.05 | 0.599519E+11 | 0.125101E+11 | 0.00 | 1.00 | 0.00 | 100080.19 | 79411.93 | 65766.97 | 24523.02 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.629637E+09 | 0.176845E+09 | 48.25 | 0.602888E+09 | 26748828.00 | 0.00 | 0.40 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 11318.16 | 12-JAN-15:00 | 11318.16 | 12-JAN-15:00 | 796.70 | 12-JAN-17:10 | 3048.36 | 12-JAN-15:00 | 0.00 |
February | 0.275336E+10 | 0.741501E+09 | 108.84 | 0.270903E+10 | 44330969.43 | 0.00 | 0.80 | 20-FEB-15:32 | 0.00 | 01-FEB-00:10 | 25644.33 | 20-FEB-15:32 | 25644.33 | 20-FEB-15:32 | 980.15 | 27-FEB-16:00 | 6195.68 | 20-FEB-15:32 | 0.00 |
March | 0.729517E+10 | 0.190396E+10 | 212.19 | 0.722390E+10 | 71263260.86 | 0.00 | 1.00 | 21-MAR-15:40 | 0.00 | 01-MAR-00:10 | 34303.52 | 21-MAR-16:00 | 34303.52 | 21-MAR-16:00 | 754.92 | 15-MAR-09:50 | 8060.34 | 21-MAR-16:00 | 0.00 |
April | 0.255305E+11 | 0.660672E+10 | 347.33 | 0.252741E+11 | 0.256340E+09 | 0.00 | 1.00 | 03-APR-11:50 | 0.00 | 01-APR-00:10 | 62095.60 | 21-APR-14:40 | 62095.60 | 21-APR-14:40 | 3707.92 | 18-APR-21:00 | 17715.39 | 21-APR-14:40 | 0.00 |
May | 0.496514E+11 | 0.131011E+11 | 450.69 | 0.482308E+11 | 0.142054E+10 | 0.00 | 1.00 | 02-MAY-14:30 | 0.00 | 01-MAY-00:10 | 75698.16 | 30-MAY-14:50 | 75698.16 | 30-MAY-14:50 | 10005.30 | 25-MAY-09:00 | 23054.38 | 30-MAY-14:50 | 0.00 |
June | 0.693618E+11 | 0.197943E+11 | 462.61 | 0.669172E+11 | 0.244466E+10 | 0.00 | 1.00 | 01-JUN-08:00 | 0.00 | 01-JUN-00:10 | 79737.34 | 19-JUN-14:30 | 79008.35 | 15-JUN-14:40 | 21399.50 | 19-JUN-18:00 | 27004.32 | 15-JUN-14:40 | 0.00 |
July | 0.769163E+11 | 0.208674E+11 | 475.90 | 0.636489E+11 | 0.132674E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 114949.13 | 20-JUL-14:55 | 82382.31 | 03-JUL-14:30 | 75433.31 | 17-JUL-06:03 | 27651.09 | 03-JUL-14:30 | 0.00 |
August | 0.678949E+11 | 0.181857E+11 | 480.27 | 0.594221E+11 | 0.847280E+10 | 0.00 | 1.00 | 01-AUG-05:12 | 0.00 | 01-AUG-00:10 | 91999.40 | 05-AUG-06:03 | 78270.96 | 07-AUG-14:50 | 44122.79 | 03-AUG-06:03 | 25519.66 | 07-AUG-16:00 | 0.00 |
September | 0.537165E+11 | 0.139732E+11 | 418.82 | 0.472555E+11 | 0.646098E+10 | 0.00 | 1.00 | 01-SEP-07:20 | 0.00 | 01-SEP-00:10 | 82984.52 | 14-SEP-10:00 | 70555.60 | 18-SEP-15:20 | 41235.30 | 14-SEP-10:00 | 20584.11 | 18-SEP-15:20 | 0.00 |
October | 0.259998E+11 | 0.655973E+10 | 335.11 | 0.229579E+11 | 0.304199E+10 | 0.00 | 1.00 | 01-OCT-11:32 | 0.00 | 01-OCT-00:10 | 71804.37 | 03-OCT-14:00 | 66134.33 | 02-OCT-04:02 | 19965.62 | 04-OCT-10:40 | 20671.56 | 03-OCT-14:00 | 0.00 |
November | 0.506382E+10 | 0.132420E+10 | 157.31 | 0.483058E+10 | 0.233247E+09 | 0.00 | 1.00 | 09-NOV-14:40 | 0.00 | 01-NOV-00:10 | 34105.14 | 09-NOV-15:00 | 34105.14 | 09-NOV-15:00 | 3450.45 | 03-NOV-11:50 | 7788.32 | 09-NOV-15:00 | 0.00 |
December | 0.216164E+09 | 62407837.45 | 28.67 | 0.207497E+09 | 8667310.00 | 0.00 | 0.18 | 20-DEC-15:00 | 0.00 | 01-DEC-00:10 | 4892.71 | 20-DEC-15:00 | 4892.71 | 20-DEC-15:00 | 326.04 | 08-DEC-16:00 | 1389.30 | 20-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.385029E+12 | 0.103297E+12 | 3525.99 | 0.349280E+12 | 0.357490E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.216164E+09 | 62407837.45 | 28.67 | 0.207497E+09 | 8667310.00 | 0.00 | 0.18 | 0.00 | 4892.71 | 4892.71 | 326.04 | 1389.30 | 0.00 | ||||||
Maximum of Months | 0.769163E+11 | 0.208674E+11 | 480.27 | 0.669172E+11 | 0.132674E+11 | 0.00 | 1.00 | 0.00 | 114949.13 | 82382.31 | 75433.31 | 27651.09 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 287.66 | 0.00 | 287.66 | 76.48 | 1360.38 | 0.00 | 0.00 | 0.00 |
February | 351.27 | 0.00 | 351.27 | 171.98 | 1237.75 | 0.00 | 0.00 | 0.00 |
March | 459.70 | 0.00 | 459.70 | 330.94 | 1061.25 | 0.00 | 0.00 | 0.00 |
April | 530.77 | 4.18 | 526.59 | 610.58 | 632.96 | 0.00 | 0.00 | 0.00 |
May | 629.52 | 45.52 | 583.99 | 1010.51 | 377.06 | 0.00 | 0.00 | 0.00 |
June | 669.38 | 82.41 | 586.97 | 1396.16 | 206.32 | 0.00 | 0.00 | 0.00 |
July | 618.64 | 60.22 | 558.42 | 1279.94 | 166.18 | 0.00 | 0.00 | 0.00 |
August | 521.65 | 10.67 | 510.98 | 997.68 | 221.97 | 0.00 | 0.00 | 0.00 |
September | 455.18 | 0.18 | 455.00 | 759.61 | 444.89 | 0.00 | 0.00 | 0.00 |
October | 377.93 | 0.00 | 377.93 | 403.03 | 706.81 | 0.00 | 0.00 | 0.00 |
November | 305.10 | 0.00 | 305.10 | 118.90 | 1182.80 | 0.00 | 0.00 | 0.00 |
December | 285.44 | 0.00 | 285.44 | 54.40 | 1503.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 458.21 | 17.02 | 441.19 | 603.06 | 756.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 285.44 | 0.00 | 285.44 | 54.40 | 166.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 669.38 | 82.41 | 586.97 | 1396.16 | 1503.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 512.94 | 278.25 | 234.69 | 515.15 | 844.72 | 0.00 | 0.00 | 0.00 |
February | 686.26 | 391.16 | 295.10 | 787.18 | 768.09 | 0.00 | 0.00 | 0.00 |
March | 847.31 | 466.84 | 380.47 | 1052.07 | 662.59 | 0.00 | 0.00 | 0.00 |
April | 1020.96 | 566.41 | 454.56 | 1488.81 | 406.16 | 0.00 | 0.00 | 0.00 |
May | 1053.58 | 572.58 | 481.00 | 1721.27 | 253.06 | 0.00 | 0.00 | 0.00 |
June | 1054.17 | 586.46 | 467.72 | 1935.90 | 135.93 | 0.00 | 0.00 | 0.00 |
July | 945.36 | 494.22 | 451.14 | 1739.55 | 111.45 | 0.00 | 0.00 | 0.00 |
August | 899.56 | 460.39 | 439.18 | 1599.13 | 148.16 | 0.00 | 0.00 | 0.00 |
September | 891.22 | 508.51 | 382.72 | 1484.30 | 281.88 | 0.00 | 0.00 | 0.00 |
October | 685.41 | 369.91 | 315.50 | 969.19 | 454.78 | 0.00 | 0.00 | 0.00 |
November | 614.41 | 357.69 | 256.72 | 693.79 | 735.65 | 0.00 | 0.00 | 0.00 |
December | 512.50 | 271.53 | 240.96 | 489.95 | 925.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 810.40 | 443.42 | 366.97 | 1207.67 | 475.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 512.50 | 271.53 | 234.69 | 489.95 | 111.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1054.17 | 586.46 | 481.00 | 1935.90 | 925.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1967.90 | 1490.89 | 477.01 | 2657.13 | 1264.36 | 0.00 | 0.00 | 0.00 |
February | 1825.45 | 1286.91 | 538.54 | 2502.19 | 1158.64 | 0.00 | 0.00 | 0.00 |
March | 1483.56 | 855.41 | 628.14 | 2091.43 | 1040.40 | 0.00 | 0.00 | 0.00 |
April | 1005.85 | 375.31 | 630.54 | 1591.68 | 661.32 | 0.00 | 0.00 | 0.00 |
May | 710.82 | 99.49 | 611.33 | 1244.12 | 402.21 | 0.00 | 0.00 | 0.00 |
June | 613.26 | 38.91 | 574.35 | 1318.76 | 210.75 | 0.00 | 0.00 | 0.00 |
July | 625.15 | 57.95 | 567.20 | 1330.99 | 172.10 | 0.00 | 0.00 | 0.00 |
August | 796.89 | 210.94 | 585.95 | 1602.76 | 234.46 | 0.00 | 0.00 | 0.00 |
September | 1243.86 | 646.23 | 597.63 | 2280.54 | 455.33 | 0.00 | 0.00 | 0.00 |
October | 1690.04 | 1142.58 | 547.46 | 2662.65 | 706.64 | 0.00 | 0.00 | 0.00 |
November | 2033.81 | 1550.53 | 483.28 | 2869.93 | 1106.36 | 0.00 | 0.00 | 0.00 |
December | 2015.58 | 1512.99 | 502.59 | 2677.07 | 1364.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1331.52 | 769.43 | 562.09 | 2066.13 | 729.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 613.26 | 38.91 | 477.01 | 1244.12 | 172.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2033.81 | 1550.53 | 630.54 | 2869.93 | 1364.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 540.32 | 304.29 | 236.03 | 601.16 | 888.11 | 0.00 | 0.00 | 0.00 |
February | 609.70 | 324.07 | 285.63 | 719.13 | 817.55 | 0.00 | 0.00 | 0.00 |
March | 830.84 | 445.30 | 385.54 | 1073.79 | 709.34 | 0.00 | 0.00 | 0.00 |
April | 954.99 | 515.80 | 439.18 | 1426.91 | 444.40 | 0.00 | 0.00 | 0.00 |
May | 1028.61 | 550.35 | 478.26 | 1707.37 | 280.17 | 0.00 | 0.00 | 0.00 |
June | 1001.27 | 537.79 | 463.48 | 1865.66 | 152.98 | 0.00 | 0.00 | 0.00 |
July | 888.56 | 441.54 | 447.02 | 1657.76 | 123.80 | 0.00 | 0.00 | 0.00 |
August | 860.52 | 438.56 | 421.97 | 1547.51 | 163.03 | 0.00 | 0.00 | 0.00 |
September | 880.02 | 490.26 | 389.76 | 1503.38 | 312.96 | 0.00 | 0.00 | 0.00 |
October | 757.55 | 442.13 | 315.42 | 1130.21 | 484.26 | 0.00 | 0.00 | 0.00 |
November | 635.85 | 387.17 | 248.69 | 791.18 | 779.97 | 0.00 | 0.00 | 0.00 |
December | 512.40 | 278.35 | 234.05 | 542.65 | 971.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 792.38 | 429.92 | 362.46 | 1215.95 | 509.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 512.40 | 278.35 | 234.05 | 542.65 | 123.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1028.61 | 550.35 | 478.26 | 1865.66 | 971.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.88 | 0.00 | 95.88 | 22.69 | 485.26 | 0.00 | 0.00 | 0.00 |
February | 117.08 | 0.00 | 117.08 | 59.23 | 423.55 | 0.00 | 0.00 | 0.00 |
March | 153.23 | 0.00 | 153.23 | 118.94 | 351.61 | 0.00 | 0.00 | 0.00 |
April | 176.92 | 1.39 | 175.52 | 215.10 | 204.69 | 0.00 | 0.00 | 0.00 |
May | 209.83 | 15.17 | 194.66 | 348.01 | 120.60 | 0.00 | 0.00 | 0.00 |
June | 223.12 | 27.47 | 195.65 | 476.28 | 63.74 | 0.00 | 0.00 | 0.00 |
July | 206.20 | 20.07 | 186.13 | 434.75 | 53.29 | 0.00 | 0.00 | 0.00 |
August | 173.87 | 3.56 | 170.32 | 335.77 | 76.13 | 0.00 | 0.00 | 0.00 |
September | 151.72 | 0.06 | 151.66 | 252.95 | 158.08 | 0.00 | 0.00 | 0.00 |
October | 125.97 | 0.00 | 125.97 | 130.76 | 258.05 | 0.00 | 0.00 | 0.00 |
November | 101.70 | 0.00 | 101.70 | 33.78 | 440.28 | 0.00 | 0.00 | 0.00 |
December | 95.14 | 0.00 | 95.14 | 13.37 | 550.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.73 | 5.67 | 147.06 | 204.20 | 264.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 95.14 | 0.00 | 95.14 | 13.37 | 53.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 223.12 | 27.47 | 195.65 | 476.28 | 550.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.89 | 0.00 | 95.89 | 22.69 | 485.29 | 0.00 | 0.00 | 0.00 |
February | 117.09 | 0.00 | 117.09 | 59.23 | 423.57 | 0.00 | 0.00 | 0.00 |
March | 153.23 | 0.00 | 153.23 | 118.94 | 351.63 | 0.00 | 0.00 | 0.00 |
April | 176.92 | 1.39 | 175.53 | 215.11 | 204.70 | 0.00 | 0.00 | 0.00 |
May | 209.84 | 15.17 | 194.66 | 348.02 | 120.60 | 0.00 | 0.00 | 0.00 |
June | 223.13 | 27.47 | 195.66 | 476.31 | 63.75 | 0.00 | 0.00 | 0.00 |
July | 206.21 | 20.07 | 186.14 | 434.77 | 53.29 | 0.00 | 0.00 | 0.00 |
August | 173.88 | 3.56 | 170.33 | 335.79 | 76.13 | 0.00 | 0.00 | 0.00 |
September | 151.73 | 0.06 | 151.67 | 252.97 | 158.09 | 0.00 | 0.00 | 0.00 |
October | 125.98 | 0.00 | 125.98 | 130.76 | 258.07 | 0.00 | 0.00 | 0.00 |
November | 101.70 | 0.00 | 101.70 | 33.78 | 440.31 | 0.00 | 0.00 | 0.00 |
December | 95.15 | 0.00 | 95.15 | 13.37 | 550.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.73 | 5.67 | 147.06 | 204.21 | 264.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 95.15 | 0.00 | 95.15 | 13.37 | 53.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 223.13 | 27.47 | 195.66 | 476.31 | 550.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.89 | 0.00 | 95.89 | 22.69 | 485.29 | 0.00 | 0.00 | 0.00 |
February | 117.09 | 0.00 | 117.09 | 59.23 | 423.57 | 0.00 | 0.00 | 0.00 |
March | 153.23 | 0.00 | 153.23 | 118.94 | 351.63 | 0.00 | 0.00 | 0.00 |
April | 176.92 | 1.39 | 175.53 | 215.11 | 204.70 | 0.00 | 0.00 | 0.00 |
May | 209.84 | 15.17 | 194.66 | 348.02 | 120.60 | 0.00 | 0.00 | 0.00 |
June | 223.13 | 27.47 | 195.66 | 476.31 | 63.75 | 0.00 | 0.00 | 0.00 |
July | 206.21 | 20.07 | 186.14 | 434.77 | 53.29 | 0.00 | 0.00 | 0.00 |
August | 173.88 | 3.56 | 170.33 | 335.79 | 76.13 | 0.00 | 0.00 | 0.00 |
September | 151.73 | 0.06 | 151.67 | 252.97 | 158.09 | 0.00 | 0.00 | 0.00 |
October | 125.98 | 0.00 | 125.98 | 130.76 | 258.07 | 0.00 | 0.00 | 0.00 |
November | 101.70 | 0.00 | 101.70 | 33.78 | 440.31 | 0.00 | 0.00 | 0.00 |
December | 95.15 | 0.00 | 95.15 | 13.37 | 550.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.73 | 5.67 | 147.06 | 204.21 | 264.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 95.15 | 0.00 | 95.15 | 13.37 | 53.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 223.13 | 27.47 | 195.66 | 476.31 | 550.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 493.42 | 267.66 | 225.76 | 485.52 | 887.37 | 0.00 | 0.00 | 0.00 |
February | 660.15 | 376.28 | 283.87 | 757.78 | 779.60 | 0.00 | 0.00 | 0.00 |
March | 815.07 | 449.07 | 365.99 | 1026.39 | 652.76 | 0.00 | 0.00 | 0.00 |
April | 982.12 | 544.85 | 437.26 | 1452.51 | 396.60 | 0.00 | 0.00 | 0.00 |
May | 1013.49 | 550.79 | 462.70 | 1676.38 | 245.39 | 0.00 | 0.00 | 0.00 |
June | 1014.06 | 564.14 | 449.92 | 1882.27 | 128.85 | 0.00 | 0.00 | 0.00 |
July | 909.39 | 475.41 | 433.98 | 1688.01 | 109.94 | 0.00 | 0.00 | 0.00 |
August | 865.34 | 442.87 | 422.47 | 1545.27 | 153.73 | 0.00 | 0.00 | 0.00 |
September | 857.31 | 489.16 | 368.15 | 1428.71 | 297.31 | 0.00 | 0.00 | 0.00 |
October | 659.33 | 355.83 | 303.50 | 927.27 | 485.56 | 0.00 | 0.00 | 0.00 |
November | 591.03 | 344.08 | 246.95 | 649.12 | 800.17 | 0.00 | 0.00 | 0.00 |
December | 493.00 | 261.20 | 231.80 | 450.27 | 994.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 779.56 | 426.55 | 353.01 | 1165.39 | 492.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 493.00 | 261.20 | 225.76 | 450.27 | 109.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1014.06 | 564.14 | 462.70 | 1882.27 | 994.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.51 | 10.58 | 8.93 | 19.20 | 35.09 | 0.00 | 0.00 | 0.00 |
February | 26.10 | 14.88 | 11.22 | 29.96 | 30.82 | 0.00 | 0.00 | 0.00 |
March | 32.23 | 17.76 | 14.47 | 40.58 | 25.81 | 0.00 | 0.00 | 0.00 |
April | 38.83 | 21.54 | 17.29 | 57.43 | 15.68 | 0.00 | 0.00 | 0.00 |
May | 40.07 | 21.78 | 18.29 | 66.28 | 9.70 | 0.00 | 0.00 | 0.00 |
June | 40.10 | 22.31 | 17.79 | 74.42 | 5.09 | 0.00 | 0.00 | 0.00 |
July | 35.96 | 18.80 | 17.16 | 66.74 | 4.35 | 0.00 | 0.00 | 0.00 |
August | 34.21 | 17.51 | 16.70 | 61.10 | 6.08 | 0.00 | 0.00 | 0.00 |
September | 33.90 | 19.34 | 14.56 | 56.49 | 11.76 | 0.00 | 0.00 | 0.00 |
October | 26.07 | 14.07 | 12.00 | 36.66 | 19.20 | 0.00 | 0.00 | 0.00 |
November | 23.37 | 13.60 | 9.76 | 25.67 | 31.64 | 0.00 | 0.00 | 0.00 |
December | 19.49 | 10.33 | 9.17 | 17.80 | 39.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30.82 | 16.87 | 13.96 | 46.08 | 19.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.49 | 10.33 | 8.93 | 17.80 | 4.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 40.10 | 22.31 | 18.29 | 74.42 | 39.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 655.96 | 496.95 | 159.00 | 886.42 | 470.48 | 0.00 | 0.00 | 0.00 |
February | 608.47 | 428.96 | 179.51 | 840.31 | 415.69 | 0.00 | 0.00 | 0.00 |
March | 494.51 | 285.13 | 209.38 | 710.18 | 357.80 | 0.00 | 0.00 | 0.00 |
April | 335.28 | 125.10 | 210.18 | 543.54 | 219.84 | 0.00 | 0.00 | 0.00 |
May | 236.94 | 33.16 | 203.78 | 426.72 | 129.90 | 0.00 | 0.00 | 0.00 |
June | 204.42 | 12.97 | 191.45 | 449.17 | 65.24 | 0.00 | 0.00 | 0.00 |
July | 208.38 | 19.32 | 189.06 | 450.92 | 55.80 | 0.00 | 0.00 | 0.00 |
August | 265.63 | 70.31 | 195.32 | 537.34 | 82.36 | 0.00 | 0.00 | 0.00 |
September | 414.61 | 215.41 | 199.21 | 761.52 | 167.01 | 0.00 | 0.00 | 0.00 |
October | 563.34 | 380.85 | 182.49 | 887.32 | 264.01 | 0.00 | 0.00 | 0.00 |
November | 677.92 | 516.83 | 161.09 | 951.22 | 420.82 | 0.00 | 0.00 | 0.00 |
December | 671.85 | 504.32 | 167.53 | 886.91 | 512.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 443.83 | 256.47 | 187.36 | 693.29 | 262.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 204.42 | 12.97 | 159.00 | 426.72 | 55.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 677.92 | 516.83 | 210.18 | 951.22 | 512.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 655.96 | 496.95 | 159.00 | 886.42 | 470.48 | 0.00 | 0.00 | 0.00 |
February | 608.47 | 428.96 | 179.51 | 840.31 | 415.69 | 0.00 | 0.00 | 0.00 |
March | 494.51 | 285.13 | 209.38 | 710.18 | 357.80 | 0.00 | 0.00 | 0.00 |
April | 335.28 | 125.10 | 210.18 | 543.54 | 219.84 | 0.00 | 0.00 | 0.00 |
May | 236.94 | 33.16 | 203.78 | 426.72 | 129.90 | 0.00 | 0.00 | 0.00 |
June | 204.42 | 12.97 | 191.45 | 449.17 | 65.24 | 0.00 | 0.00 | 0.00 |
July | 208.38 | 19.32 | 189.06 | 450.92 | 55.80 | 0.00 | 0.00 | 0.00 |
August | 265.63 | 70.31 | 195.32 | 537.34 | 82.36 | 0.00 | 0.00 | 0.00 |
September | 414.61 | 215.41 | 199.21 | 761.52 | 167.01 | 0.00 | 0.00 | 0.00 |
October | 563.34 | 380.85 | 182.49 | 887.32 | 264.01 | 0.00 | 0.00 | 0.00 |
November | 677.92 | 516.83 | 161.09 | 951.22 | 420.82 | 0.00 | 0.00 | 0.00 |
December | 671.85 | 504.32 | 167.53 | 886.91 | 512.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 443.83 | 256.47 | 187.36 | 693.29 | 262.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 204.42 | 12.97 | 159.00 | 426.72 | 55.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 677.92 | 516.83 | 210.18 | 951.22 | 512.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 655.91 | 496.92 | 158.99 | 886.36 | 470.45 | 0.00 | 0.00 | 0.00 |
February | 608.43 | 428.94 | 179.50 | 840.26 | 415.66 | 0.00 | 0.00 | 0.00 |
March | 494.48 | 285.11 | 209.37 | 710.14 | 357.77 | 0.00 | 0.00 | 0.00 |
April | 335.26 | 125.09 | 210.17 | 543.50 | 219.83 | 0.00 | 0.00 | 0.00 |
May | 236.92 | 33.16 | 203.76 | 426.70 | 129.90 | 0.00 | 0.00 | 0.00 |
June | 204.41 | 12.97 | 191.44 | 449.14 | 65.24 | 0.00 | 0.00 | 0.00 |
July | 208.37 | 19.32 | 189.05 | 450.89 | 55.79 | 0.00 | 0.00 | 0.00 |
August | 265.61 | 70.31 | 195.30 | 537.30 | 82.36 | 0.00 | 0.00 | 0.00 |
September | 414.59 | 215.39 | 199.20 | 761.47 | 167.00 | 0.00 | 0.00 | 0.00 |
October | 563.30 | 380.83 | 182.47 | 887.27 | 263.99 | 0.00 | 0.00 | 0.00 |
November | 677.88 | 516.80 | 161.08 | 951.16 | 420.80 | 0.00 | 0.00 | 0.00 |
December | 671.81 | 504.29 | 167.52 | 886.85 | 512.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 443.80 | 256.45 | 187.35 | 693.25 | 262.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 204.41 | 12.97 | 158.99 | 426.70 | 55.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 677.88 | 516.80 | 210.17 | 951.16 | 512.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 519.76 | 292.72 | 227.05 | 575.53 | 934.45 | 0.00 | 0.00 | 0.00 |
February | 586.50 | 311.74 | 274.76 | 699.54 | 829.44 | 0.00 | 0.00 | 0.00 |
March | 799.23 | 428.36 | 370.87 | 1052.25 | 703.42 | 0.00 | 0.00 | 0.00 |
April | 918.65 | 496.18 | 422.47 | 1393.64 | 436.54 | 0.00 | 0.00 | 0.00 |
May | 989.47 | 529.41 | 460.06 | 1664.07 | 273.94 | 0.00 | 0.00 | 0.00 |
June | 963.18 | 517.33 | 445.85 | 1813.42 | 145.25 | 0.00 | 0.00 | 0.00 |
July | 854.75 | 424.74 | 430.01 | 1608.11 | 122.18 | 0.00 | 0.00 | 0.00 |
August | 827.78 | 421.87 | 405.91 | 1495.55 | 169.74 | 0.00 | 0.00 | 0.00 |
September | 846.54 | 471.60 | 374.93 | 1448.40 | 331.04 | 0.00 | 0.00 | 0.00 |
October | 728.73 | 425.31 | 303.42 | 1082.67 | 520.38 | 0.00 | 0.00 | 0.00 |
November | 611.66 | 372.44 | 239.23 | 749.79 | 854.22 | 0.00 | 0.00 | 0.00 |
December | 492.91 | 267.76 | 225.15 | 511.72 | 1041.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 762.23 | 413.56 | 348.67 | 1176.52 | 528.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 492.91 | 267.76 | 225.15 | 511.72 | 122.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 989.47 | 529.41 | 460.06 | 1813.42 | 1041.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.55 | 11.57 | 8.98 | 22.76 | 36.95 | 0.00 | 0.00 | 0.00 |
February | 23.19 | 12.33 | 10.86 | 27.66 | 32.80 | 0.00 | 0.00 | 0.00 |
March | 31.60 | 16.94 | 14.66 | 41.60 | 27.81 | 0.00 | 0.00 | 0.00 |
April | 36.32 | 19.62 | 16.70 | 55.10 | 17.26 | 0.00 | 0.00 | 0.00 |
May | 39.12 | 20.93 | 18.19 | 65.80 | 10.83 | 0.00 | 0.00 | 0.00 |
June | 38.08 | 20.45 | 17.63 | 71.70 | 5.74 | 0.00 | 0.00 | 0.00 |
July | 33.80 | 16.79 | 17.00 | 63.58 | 4.83 | 0.00 | 0.00 | 0.00 |
August | 32.73 | 16.68 | 16.05 | 59.13 | 6.71 | 0.00 | 0.00 | 0.00 |
September | 33.47 | 18.65 | 14.82 | 57.27 | 13.09 | 0.00 | 0.00 | 0.00 |
October | 28.81 | 16.82 | 12.00 | 42.81 | 20.58 | 0.00 | 0.00 | 0.00 |
November | 24.18 | 14.73 | 9.46 | 29.65 | 33.78 | 0.00 | 0.00 | 0.00 |
December | 19.49 | 10.59 | 8.90 | 20.23 | 41.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30.14 | 16.35 | 13.79 | 46.52 | 20.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.49 | 10.59 | 8.90 | 20.23 | 4.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.12 | 20.93 | 18.19 | 71.70 | 41.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 287.66 | 0.00 | 287.66 | 62.65 | 1472.41 | 0.00 | 0.00 | 0.00 |
February | 351.27 | 0.00 | 351.27 | 156.46 | 1330.51 | 0.00 | 0.00 | 0.00 |
March | 459.70 | 0.00 | 459.70 | 317.05 | 1129.84 | 0.00 | 0.00 | 0.00 |
April | 530.77 | 4.18 | 526.59 | 608.17 | 666.31 | 0.00 | 0.00 | 0.00 |
May | 629.52 | 45.52 | 583.99 | 1013.57 | 389.61 | 0.00 | 0.00 | 0.00 |
June | 669.38 | 82.41 | 586.97 | 1405.69 | 209.18 | 0.00 | 0.00 | 0.00 |
July | 618.64 | 60.22 | 558.42 | 1291.45 | 168.06 | 0.00 | 0.00 | 0.00 |
August | 521.65 | 10.67 | 510.98 | 1005.37 | 228.63 | 0.00 | 0.00 | 0.00 |
September | 455.18 | 0.18 | 455.00 | 762.03 | 464.13 | 0.00 | 0.00 | 0.00 |
October | 377.93 | 0.00 | 377.93 | 394.58 | 754.99 | 0.00 | 0.00 | 0.00 |
November | 305.10 | 0.00 | 305.10 | 103.34 | 1290.37 | 0.00 | 0.00 | 0.00 |
December | 285.44 | 0.00 | 285.44 | 40.87 | 1629.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 458.21 | 17.02 | 441.19 | 599.04 | 808.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 285.44 | 0.00 | 285.44 | 40.87 | 168.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 669.38 | 82.41 | 586.97 | 1405.69 | 1629.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 512.94 | 278.25 | 234.69 | 495.58 | 914.26 | 0.00 | 0.00 | 0.00 |
February | 686.26 | 391.16 | 295.10 | 768.65 | 822.85 | 0.00 | 0.00 | 0.00 |
March | 847.31 | 466.84 | 380.47 | 1037.71 | 700.01 | 0.00 | 0.00 | 0.00 |
April | 1020.96 | 566.41 | 454.56 | 1485.02 | 423.08 | 0.00 | 0.00 | 0.00 |
May | 1053.58 | 572.58 | 481.00 | 1722.20 | 261.05 | 0.00 | 0.00 | 0.00 |
June | 1054.17 | 586.46 | 467.72 | 1940.22 | 138.26 | 0.00 | 0.00 | 0.00 |
July | 945.36 | 494.22 | 451.14 | 1745.04 | 113.19 | 0.00 | 0.00 | 0.00 |
August | 899.56 | 460.39 | 439.18 | 1601.88 | 152.62 | 0.00 | 0.00 | 0.00 |
September | 891.22 | 508.51 | 382.72 | 1483.10 | 292.62 | 0.00 | 0.00 | 0.00 |
October | 685.41 | 369.91 | 315.50 | 960.93 | 481.95 | 0.00 | 0.00 | 0.00 |
November | 614.41 | 357.69 | 256.72 | 674.23 | 795.45 | 0.00 | 0.00 | 0.00 |
December | 512.50 | 271.53 | 240.96 | 466.83 | 1003.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 810.40 | 443.42 | 366.97 | 1199.82 | 506.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 512.50 | 271.53 | 234.69 | 466.83 | 113.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1054.17 | 586.46 | 481.00 | 1940.22 | 1003.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1967.90 | 1490.89 | 477.01 | 2635.59 | 1358.67 | 0.00 | 0.00 | 0.00 |
February | 1825.45 | 1286.91 | 538.54 | 2483.55 | 1236.86 | 0.00 | 0.00 | 0.00 |
March | 1483.56 | 855.41 | 628.14 | 2079.59 | 1099.51 | 0.00 | 0.00 | 0.00 |
April | 1005.85 | 375.31 | 630.54 | 1592.23 | 693.40 | 0.00 | 0.00 | 0.00 |
May | 710.82 | 99.49 | 611.33 | 1249.56 | 417.29 | 0.00 | 0.00 | 0.00 |
June | 613.26 | 38.91 | 574.35 | 1328.24 | 214.48 | 0.00 | 0.00 | 0.00 |
July | 625.15 | 57.95 | 567.20 | 1342.99 | 174.65 | 0.00 | 0.00 | 0.00 |
August | 796.89 | 210.94 | 585.95 | 1611.94 | 241.59 | 0.00 | 0.00 | 0.00 |
September | 1243.86 | 646.23 | 597.63 | 2285.60 | 473.66 | 0.00 | 0.00 | 0.00 |
October | 1690.04 | 1142.58 | 547.46 | 2657.39 | 746.18 | 0.00 | 0.00 | 0.00 |
November | 2033.81 | 1550.53 | 483.28 | 2846.99 | 1187.44 | 0.00 | 0.00 | 0.00 |
December | 2015.58 | 1512.99 | 502.59 | 2646.44 | 1466.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1331.52 | 769.43 | 562.09 | 2060.44 | 773.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 613.26 | 38.91 | 477.01 | 1249.56 | 174.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2033.81 | 1550.53 | 630.54 | 2846.99 | 1466.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 540.32 | 304.29 | 236.03 | 590.90 | 958.88 | 0.00 | 0.00 | 0.00 |
February | 609.70 | 324.07 | 285.63 | 709.73 | 877.02 | 0.00 | 0.00 | 0.00 |
March | 830.84 | 445.30 | 385.54 | 1067.15 | 753.52 | 0.00 | 0.00 | 0.00 |
April | 954.99 | 515.80 | 439.18 | 1427.47 | 466.55 | 0.00 | 0.00 | 0.00 |
May | 1028.61 | 550.35 | 478.26 | 1712.51 | 290.52 | 0.00 | 0.00 | 0.00 |
June | 1001.27 | 537.79 | 463.48 | 1873.31 | 155.37 | 0.00 | 0.00 | 0.00 |
July | 888.56 | 441.54 | 447.02 | 1666.16 | 125.56 | 0.00 | 0.00 | 0.00 |
August | 860.52 | 438.56 | 421.97 | 1553.85 | 167.73 | 0.00 | 0.00 | 0.00 |
September | 880.02 | 490.26 | 389.76 | 1506.42 | 325.56 | 0.00 | 0.00 | 0.00 |
October | 757.55 | 442.13 | 315.42 | 1126.59 | 514.09 | 0.00 | 0.00 | 0.00 |
November | 635.85 | 387.17 | 248.69 | 780.38 | 845.43 | 0.00 | 0.00 | 0.00 |
December | 512.40 | 278.35 | 234.05 | 530.38 | 1049.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 792.38 | 429.92 | 362.46 | 1214.17 | 542.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 512.40 | 278.35 | 234.05 | 530.38 | 125.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1028.61 | 550.35 | 478.26 | 1873.31 | 1049.74 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.770482E+09 | 0.00 | 0.770482E+09 | 0.204857E+09 | 0.364364E+10 |
February | 0.849791E+09 | 0.00 | 0.849791E+09 | 0.416053E+09 | 0.299437E+10 |
March | 0.123126E+10 | 0.00 | 0.123126E+10 | 0.886384E+09 | 0.284244E+10 |
April | 0.137576E+10 | 10839023.03 | 0.136492E+10 | 0.158263E+10 | 0.164062E+10 |
May | 0.168610E+10 | 0.121928E+09 | 0.156417E+10 | 0.270655E+10 | 0.100992E+10 |
June | 0.173504E+10 | 0.213604E+09 | 0.152144E+10 | 0.361884E+10 | 0.534790E+09 |
July | 0.165696E+10 | 0.161293E+09 | 0.149567E+10 | 0.342819E+10 | 0.445098E+09 |
August | 0.139718E+10 | 28568732.44 | 0.136861E+10 | 0.267219E+10 | 0.594527E+09 |
September | 0.117984E+10 | 470797.93 | 0.117937E+10 | 0.196890E+10 | 0.115315E+10 |
October | 0.101224E+10 | 0.00 | 0.101224E+10 | 0.107948E+10 | 0.189312E+10 |
November | 0.790819E+09 | 0.00 | 0.790819E+09 | 0.308191E+09 | 0.306581E+10 |
December | 0.764515E+09 | 0.00 | 0.764515E+09 | 0.145712E+09 | 0.402575E+10 |
Annual Sum or Average | 0.144500E+11 | 0.536703E+09 | 0.139133E+11 | 0.190180E+11 | 0.238432E+11 |
Minimum of Months | 0.764515E+09 | 0.00 | 0.764515E+09 | 0.145712E+09 | 0.445098E+09 |
Maximum of Months | 0.173504E+10 | 0.213604E+09 | 0.156417E+10 | 0.361884E+10 | 0.402575E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137385E+10 | 0.745265E+09 | 0.628587E+09 | 0.137978E+10 | 0.226249E+10 |
February | 0.166020E+10 | 0.946305E+09 | 0.713898E+09 | 0.190434E+10 | 0.185815E+10 |
March | 0.226943E+10 | 0.125038E+10 | 0.101905E+10 | 0.281786E+10 | 0.177469E+10 |
April | 0.264634E+10 | 0.146813E+10 | 0.117821E+10 | 0.385900E+10 | 0.105278E+10 |
May | 0.282191E+10 | 0.153360E+10 | 0.128830E+10 | 0.461024E+10 | 0.677785E+09 |
June | 0.273241E+10 | 0.152009E+10 | 0.121232E+10 | 0.501786E+10 | 0.352322E+09 |
July | 0.253206E+10 | 0.132372E+10 | 0.120834E+10 | 0.465921E+10 | 0.298502E+09 |
August | 0.240939E+10 | 0.123310E+10 | 0.117629E+10 | 0.428310E+10 | 0.396831E+09 |
September | 0.231005E+10 | 0.131805E+10 | 0.991998E+09 | 0.384731E+10 | 0.730624E+09 |
October | 0.183579E+10 | 0.990761E+09 | 0.845034E+09 | 0.259588E+10 | 0.121810E+10 |
November | 0.159254E+10 | 0.927127E+09 | 0.665415E+09 | 0.179831E+10 | 0.190679E+10 |
December | 0.137267E+10 | 0.727272E+09 | 0.645400E+09 | 0.131228E+10 | 0.247988E+10 |
Annual Sum or Average | 0.255567E+11 | 0.139838E+11 | 0.115728E+11 | 0.380852E+11 | 0.150089E+11 |
Minimum of Months | 0.137267E+10 | 0.727272E+09 | 0.628587E+09 | 0.131228E+10 | 0.298502E+09 |
Maximum of Months | 0.282191E+10 | 0.153360E+10 | 0.128830E+10 | 0.501786E+10 | 0.247988E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.527083E+10 | 0.399320E+10 | 0.127763E+10 | 0.711686E+10 | 0.338645E+10 |
February | 0.441613E+10 | 0.311330E+10 | 0.130283E+10 | 0.605330E+10 | 0.280297E+10 |
March | 0.397356E+10 | 0.229114E+10 | 0.168242E+10 | 0.560169E+10 | 0.278661E+10 |
April | 0.260715E+10 | 0.972794E+09 | 0.163436E+10 | 0.412562E+10 | 0.171415E+10 |
May | 0.190386E+10 | 0.266478E+09 | 0.163738E+10 | 0.333224E+10 | 0.107727E+10 |
June | 0.158957E+10 | 0.100858E+09 | 0.148871E+10 | 0.341823E+10 | 0.546259E+09 |
July | 0.167440E+10 | 0.155220E+09 | 0.151918E+10 | 0.356492E+10 | 0.460960E+09 |
August | 0.213440E+10 | 0.564988E+09 | 0.156941E+10 | 0.429282E+10 | 0.627975E+09 |
September | 0.322408E+10 | 0.167502E+10 | 0.154906E+10 | 0.591115E+10 | 0.118022E+10 |
October | 0.452660E+10 | 0.306029E+10 | 0.146632E+10 | 0.713164E+10 | 0.189265E+10 |
November | 0.527163E+10 | 0.401897E+10 | 0.125266E+10 | 0.743887E+10 | 0.286769E+10 |
December | 0.539854E+10 | 0.405239E+10 | 0.134615E+10 | 0.717028E+10 | 0.365409E+10 |
Annual Sum or Average | 0.419907E+11 | 0.242646E+11 | 0.177261E+11 | 0.651576E+11 | 0.229973E+11 |
Minimum of Months | 0.158957E+10 | 0.100858E+09 | 0.125266E+10 | 0.333224E+10 | 0.460960E+09 |
Maximum of Months | 0.539854E+10 | 0.405239E+10 | 0.168242E+10 | 0.743887E+10 | 0.365409E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144720E+10 | 0.815021E+09 | 0.632177E+09 | 0.161014E+10 | 0.237872E+10 |
February | 0.147498E+10 | 0.783984E+09 | 0.690996E+09 | 0.173971E+10 | 0.197782E+10 |
March | 0.222533E+10 | 0.119270E+10 | 0.103263E+10 | 0.287604E+10 | 0.189991E+10 |
April | 0.247532E+10 | 0.133697E+10 | 0.113836E+10 | 0.369856E+10 | 0.115189E+10 |
May | 0.275503E+10 | 0.147407E+10 | 0.128096E+10 | 0.457301E+10 | 0.750413E+09 |
June | 0.259530E+10 | 0.139396E+10 | 0.120134E+10 | 0.483579E+10 | 0.396519E+09 |
July | 0.237991E+10 | 0.118263E+10 | 0.119729E+10 | 0.444013E+10 | 0.331578E+09 |
August | 0.230483E+10 | 0.117463E+10 | 0.113020E+10 | 0.414486E+10 | 0.436671E+09 |
September | 0.228101E+10 | 0.127075E+10 | 0.101026E+10 | 0.389676E+10 | 0.811205E+09 |
October | 0.202903E+10 | 0.118421E+10 | 0.844821E+09 | 0.302714E+10 | 0.129704E+10 |
November | 0.164813E+10 | 0.100354E+10 | 0.644595E+09 | 0.205074E+10 | 0.202167E+10 |
December | 0.137243E+10 | 0.745546E+09 | 0.626880E+09 | 0.145343E+10 | 0.260105E+10 |
Annual Sum or Average | 0.249885E+11 | 0.135580E+11 | 0.114305E+11 | 0.383463E+11 | 0.160545E+11 |
Minimum of Months | 0.137243E+10 | 0.745546E+09 | 0.626880E+09 | 0.145343E+10 | 0.331578E+09 |
Maximum of Months | 0.275503E+10 | 0.147407E+10 | 0.128096E+10 | 0.483579E+10 | 0.260105E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.256815E+09 | 0.00 | 0.256815E+09 | 60764567.13 | 0.129972E+10 |
February | 0.283250E+09 | 0.00 | 0.283250E+09 | 0.143281E+09 | 0.102465E+10 |
March | 0.410399E+09 | 0.00 | 0.410399E+09 | 0.318558E+09 | 0.941743E+09 |
April | 0.458566E+09 | 3612836.74 | 0.454953E+09 | 0.557529E+09 | 0.530551E+09 |
May | 0.562005E+09 | 40640821.64 | 0.521364E+09 | 0.932100E+09 | 0.323009E+09 |
June | 0.578319E+09 | 71197845.54 | 0.507121E+09 | 0.123453E+10 | 0.165222E+09 |
July | 0.552295E+09 | 53761700.40 | 0.498533E+09 | 0.116444E+10 | 0.142736E+09 |
August | 0.465705E+09 | 9522460.27 | 0.456183E+09 | 0.899331E+09 | 0.203903E+09 |
September | 0.393261E+09 | 156925.22 | 0.393104E+09 | 0.655656E+09 | 0.409743E+09 |
October | 0.337399E+09 | 0.00 | 0.337399E+09 | 0.350219E+09 | 0.691164E+09 |
November | 0.263594E+09 | 0.00 | 0.263594E+09 | 87562236.92 | 0.114121E+10 |
December | 0.254826E+09 | 0.00 | 0.254826E+09 | 35804652.20 | 0.147395E+10 |
Annual Sum or Average | 0.481644E+10 | 0.178893E+09 | 0.463754E+10 | 0.643977E+10 | 0.834759E+10 |
Minimum of Months | 0.254826E+09 | 0.00 | 0.254826E+09 | 35804652.20 | 0.142736E+09 |
Maximum of Months | 0.578319E+09 | 71197845.54 | 0.521364E+09 | 0.123453E+10 | 0.147395E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.256826E+09 | 0.00 | 0.256826E+09 | 60765002.28 | 0.129980E+10 |
February | 0.283262E+09 | 0.00 | 0.283262E+09 | 0.143286E+09 | 0.102471E+10 |
March | 0.410417E+09 | 0.00 | 0.410417E+09 | 0.318571E+09 | 0.941798E+09 |
April | 0.458586E+09 | 3612933.85 | 0.454973E+09 | 0.557556E+09 | 0.530580E+09 |
May | 0.562029E+09 | 40641914.08 | 0.521387E+09 | 0.932144E+09 | 0.323024E+09 |
June | 0.578344E+09 | 71199759.36 | 0.507144E+09 | 0.123459E+10 | 0.165229E+09 |
July | 0.552318E+09 | 53763145.52 | 0.498555E+09 | 0.116449E+10 | 0.142742E+09 |
August | 0.465725E+09 | 9522716.23 | 0.456202E+09 | 0.899377E+09 | 0.203913E+09 |
September | 0.393278E+09 | 156929.44 | 0.393121E+09 | 0.655690E+09 | 0.409764E+09 |
October | 0.337414E+09 | 0.00 | 0.337414E+09 | 0.350234E+09 | 0.691203E+09 |
November | 0.263605E+09 | 0.00 | 0.263605E+09 | 87565008.13 | 0.114127E+10 |
December | 0.254837E+09 | 0.00 | 0.254837E+09 | 35804627.27 | 0.147403E+10 |
Annual Sum or Average | 0.481664E+10 | 0.178897E+09 | 0.463774E+10 | 0.644008E+10 | 0.834807E+10 |
Minimum of Months | 0.254837E+09 | 0.00 | 0.254837E+09 | 35804627.27 | 0.142742E+09 |
Maximum of Months | 0.578344E+09 | 71199759.36 | 0.521387E+09 | 0.123459E+10 | 0.147403E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.256826E+09 | 0.00 | 0.256826E+09 | 60765002.28 | 0.129980E+10 |
February | 0.283262E+09 | 0.00 | 0.283262E+09 | 0.143286E+09 | 0.102471E+10 |
March | 0.410417E+09 | 0.00 | 0.410417E+09 | 0.318571E+09 | 0.941798E+09 |
April | 0.458586E+09 | 3612933.85 | 0.454973E+09 | 0.557556E+09 | 0.530580E+09 |
May | 0.562029E+09 | 40641914.08 | 0.521387E+09 | 0.932144E+09 | 0.323024E+09 |
June | 0.578344E+09 | 71199759.36 | 0.507144E+09 | 0.123459E+10 | 0.165229E+09 |
July | 0.552318E+09 | 53763145.52 | 0.498555E+09 | 0.116449E+10 | 0.142742E+09 |
August | 0.465725E+09 | 9522716.23 | 0.456202E+09 | 0.899377E+09 | 0.203913E+09 |
September | 0.393278E+09 | 156929.44 | 0.393121E+09 | 0.655690E+09 | 0.409764E+09 |
October | 0.337414E+09 | 0.00 | 0.337414E+09 | 0.350234E+09 | 0.691203E+09 |
November | 0.263605E+09 | 0.00 | 0.263605E+09 | 87565008.13 | 0.114127E+10 |
December | 0.254837E+09 | 0.00 | 0.254837E+09 | 35804627.27 | 0.147403E+10 |
Annual Sum or Average | 0.481664E+10 | 0.178897E+09 | 0.463774E+10 | 0.644008E+10 | 0.834807E+10 |
Minimum of Months | 0.254837E+09 | 0.00 | 0.254837E+09 | 35804627.27 | 0.142742E+09 |
Maximum of Months | 0.578344E+09 | 71199759.36 | 0.521387E+09 | 0.123459E+10 | 0.147403E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132158E+10 | 0.716905E+09 | 0.604671E+09 | 0.130041E+10 | 0.237672E+10 |
February | 0.159703E+10 | 0.910295E+09 | 0.686737E+09 | 0.183322E+10 | 0.188602E+10 |
March | 0.218308E+10 | 0.120280E+10 | 0.980276E+09 | 0.274909E+10 | 0.174836E+10 |
April | 0.254564E+10 | 0.141226E+10 | 0.113339E+10 | 0.376491E+10 | 0.102798E+10 |
May | 0.271453E+10 | 0.147524E+10 | 0.123929E+10 | 0.449001E+10 | 0.657243E+09 |
June | 0.262845E+10 | 0.146225E+10 | 0.116620E+10 | 0.487884E+10 | 0.333978E+09 |
July | 0.243571E+10 | 0.127334E+10 | 0.116237E+10 | 0.452117E+10 | 0.294468E+09 |
August | 0.231771E+10 | 0.118618E+10 | 0.113153E+10 | 0.413886E+10 | 0.411746E+09 |
September | 0.222215E+10 | 0.126790E+10 | 0.954257E+09 | 0.370321E+10 | 0.770622E+09 |
October | 0.176594E+10 | 0.953058E+09 | 0.812884E+09 | 0.248360E+10 | 0.130053E+10 |
November | 0.153195E+10 | 0.891847E+09 | 0.640099E+09 | 0.168253E+10 | 0.207403E+10 |
December | 0.132044E+10 | 0.699597E+09 | 0.620844E+09 | 0.120601E+10 | 0.266472E+10 |
Annual Sum or Average | 0.245842E+11 | 0.134517E+11 | 0.111325E+11 | 0.367519E+11 | 0.155464E+11 |
Minimum of Months | 0.132044E+10 | 0.699597E+09 | 0.604671E+09 | 0.120601E+10 | 0.294468E+09 |
Maximum of Months | 0.271453E+10 | 0.147524E+10 | 0.123929E+10 | 0.487884E+10 | 0.266472E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52253939.43 | 28345774.84 | 23908164.60 | 51416949.14 | 93973332.55 |
February | 63145188.07 | 35992234.95 | 27152953.12 | 72483809.14 | 74571413.39 |
March | 86316882.58 | 47557656.77 | 38759225.81 | 0.108697E+09 | 69128543.87 |
April | 0.100652E+09 | 55839413.91 | 44813068.32 | 0.148861E+09 | 40645425.60 |
May | 0.107330E+09 | 58329704.30 | 49000433.98 | 0.177531E+09 | 25986801.77 |
June | 0.103926E+09 | 57815999.01 | 46110385.16 | 0.192905E+09 | 13205174.16 |
July | 96305959.35 | 50346885.37 | 45959073.97 | 0.178763E+09 | 11643010.47 |
August | 91640328.22 | 46900482.29 | 44739845.93 | 0.163647E+09 | 16280078.23 |
September | 87861929.88 | 50131455.55 | 37730474.33 | 0.146422E+09 | 30469717.15 |
October | 69823766.24 | 37683058.67 | 32140707.57 | 98199497.17 | 51421893.41 |
November | 60571756.71 | 35262809.25 | 25308947.46 | 66525679.42 | 82005336.88 |
December | 52209059.66 | 27661427.61 | 24547632.05 | 47684486.13 | 0.105361E+09 |
Annual Sum or Average | 0.972038E+09 | 0.531867E+09 | 0.440171E+09 | 0.145314E+10 | 0.614692E+09 |
Minimum of Months | 52209059.66 | 27661427.61 | 23908164.60 | 47684486.13 | 11643010.47 |
Maximum of Months | 0.107330E+09 | 58329704.30 | 49000433.98 | 0.192905E+09 | 0.105361E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.175691E+10 | 0.133104E+10 | 0.425871E+09 | 0.237418E+10 | 0.126014E+10 |
February | 0.147202E+10 | 0.103775E+10 | 0.434271E+09 | 0.203289E+10 | 0.100564E+10 |
March | 0.132450E+10 | 0.763698E+09 | 0.560800E+09 | 0.190216E+10 | 0.958319E+09 |
April | 0.869040E+09 | 0.324258E+09 | 0.544783E+09 | 0.140885E+10 | 0.569830E+09 |
May | 0.634616E+09 | 88824167.27 | 0.545792E+09 | 0.114293E+10 | 0.347937E+09 |
June | 0.529854E+09 | 33618785.83 | 0.496235E+09 | 0.116425E+10 | 0.169113E+09 |
July | 0.558130E+09 | 51738867.55 | 0.506391E+09 | 0.120774E+10 | 0.149444E+09 |
August | 0.711459E+09 | 0.188326E+09 | 0.523134E+09 | 0.143920E+10 | 0.220596E+09 |
September | 0.107468E+10 | 0.558330E+09 | 0.516350E+09 | 0.197386E+10 | 0.432897E+09 |
October | 0.150884E+10 | 0.102007E+10 | 0.488768E+09 | 0.237660E+10 | 0.707126E+09 |
November | 0.175718E+10 | 0.133963E+10 | 0.417549E+09 | 0.246557E+10 | 0.109077E+10 |
December | 0.179948E+10 | 0.135077E+10 | 0.448711E+09 | 0.237550E+10 | 0.137259E+10 |
Annual Sum or Average | 0.139967E+11 | 0.808805E+10 | 0.590865E+10 | 0.218637E+11 | 0.828440E+10 |
Minimum of Months | 0.529854E+09 | 33618785.83 | 0.417549E+09 | 0.114293E+10 | 0.149444E+09 |
Maximum of Months | 0.179948E+10 | 0.135077E+10 | 0.560800E+09 | 0.246557E+10 | 0.137259E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.175691E+10 | 0.133104E+10 | 0.425871E+09 | 0.237418E+10 | 0.126014E+10 |
February | 0.147202E+10 | 0.103775E+10 | 0.434271E+09 | 0.203289E+10 | 0.100564E+10 |
March | 0.132450E+10 | 0.763698E+09 | 0.560800E+09 | 0.190216E+10 | 0.958319E+09 |
April | 0.869040E+09 | 0.324258E+09 | 0.544783E+09 | 0.140885E+10 | 0.569830E+09 |
May | 0.634616E+09 | 88824167.27 | 0.545792E+09 | 0.114293E+10 | 0.347937E+09 |
June | 0.529854E+09 | 33618785.83 | 0.496235E+09 | 0.116425E+10 | 0.169113E+09 |
July | 0.558130E+09 | 51738867.55 | 0.506391E+09 | 0.120774E+10 | 0.149444E+09 |
August | 0.711459E+09 | 0.188326E+09 | 0.523134E+09 | 0.143920E+10 | 0.220596E+09 |
September | 0.107468E+10 | 0.558330E+09 | 0.516350E+09 | 0.197386E+10 | 0.432897E+09 |
October | 0.150884E+10 | 0.102007E+10 | 0.488768E+09 | 0.237660E+10 | 0.707126E+09 |
November | 0.175718E+10 | 0.133963E+10 | 0.417549E+09 | 0.246557E+10 | 0.109077E+10 |
December | 0.179948E+10 | 0.135077E+10 | 0.448711E+09 | 0.237550E+10 | 0.137259E+10 |
Annual Sum or Average | 0.139967E+11 | 0.808805E+10 | 0.590865E+10 | 0.218637E+11 | 0.828440E+10 |
Minimum of Months | 0.529854E+09 | 33618785.83 | 0.417549E+09 | 0.114293E+10 | 0.149444E+09 |
Maximum of Months | 0.179948E+10 | 0.135077E+10 | 0.560800E+09 | 0.246557E+10 | 0.137259E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.175680E+10 | 0.133096E+10 | 0.425844E+09 | 0.237403E+10 | 0.126006E+10 |
February | 0.147192E+10 | 0.103768E+10 | 0.434243E+09 | 0.203276E+10 | 0.100557E+10 |
March | 0.132441E+10 | 0.763650E+09 | 0.560765E+09 | 0.190204E+10 | 0.958259E+09 |
April | 0.868986E+09 | 0.324237E+09 | 0.544748E+09 | 0.140876E+10 | 0.569794E+09 |
May | 0.634576E+09 | 88818554.08 | 0.545757E+09 | 0.114286E+10 | 0.347915E+09 |
June | 0.529820E+09 | 33616661.31 | 0.496203E+09 | 0.116418E+10 | 0.169102E+09 |
July | 0.558095E+09 | 51735597.94 | 0.506359E+09 | 0.120766E+10 | 0.149434E+09 |
August | 0.711414E+09 | 0.188314E+09 | 0.523101E+09 | 0.143911E+10 | 0.220583E+09 |
September | 0.107461E+10 | 0.558295E+09 | 0.516317E+09 | 0.197373E+10 | 0.432870E+09 |
October | 0.150875E+10 | 0.102001E+10 | 0.488737E+09 | 0.237645E+10 | 0.707081E+09 |
November | 0.175707E+10 | 0.133954E+10 | 0.417523E+09 | 0.246542E+10 | 0.109070E+10 |
December | 0.179936E+10 | 0.135068E+10 | 0.448683E+09 | 0.237535E+10 | 0.137250E+10 |
Annual Sum or Average | 0.139958E+11 | 0.808754E+10 | 0.590828E+10 | 0.218623E+11 | 0.828387E+10 |
Minimum of Months | 0.529820E+09 | 33616661.31 | 0.417523E+09 | 0.114286E+10 | 0.149434E+09 |
Maximum of Months | 0.179936E+10 | 0.135068E+10 | 0.560765E+09 | 0.246542E+10 | 0.137250E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139214E+10 | 0.784009E+09 | 0.608127E+09 | 0.154151E+10 | 0.250282E+10 |
February | 0.141886E+10 | 0.754152E+09 | 0.664708E+09 | 0.169232E+10 | 0.200659E+10 |
March | 0.214066E+10 | 0.114732E+10 | 0.993344E+09 | 0.281835E+10 | 0.188403E+10 |
April | 0.238114E+10 | 0.128609E+10 | 0.109505E+10 | 0.361230E+10 | 0.113150E+10 |
May | 0.265021E+10 | 0.141798E+10 | 0.123223E+10 | 0.445705E+10 | 0.733721E+09 |
June | 0.249655E+10 | 0.134092E+10 | 0.115563E+10 | 0.470038E+10 | 0.376493E+09 |
July | 0.228937E+10 | 0.113763E+10 | 0.115174E+10 | 0.430716E+10 | 0.327241E+09 |
August | 0.221713E+10 | 0.112993E+10 | 0.108720E+10 | 0.400568E+10 | 0.454645E+09 |
September | 0.219422E+10 | 0.122240E+10 | 0.971823E+09 | 0.375424E+10 | 0.858060E+09 |
October | 0.195183E+10 | 0.113915E+10 | 0.812681E+09 | 0.289983E+10 | 0.139378E+10 |
November | 0.158542E+10 | 0.965352E+09 | 0.620073E+09 | 0.194346E+10 | 0.221415E+10 |
December | 0.132021E+10 | 0.717177E+09 | 0.603031E+09 | 0.137059E+10 | 0.279040E+10 |
Annual Sum or Average | 0.240377E+11 | 0.130421E+11 | 0.109956E+11 | 0.371029E+11 | 0.166734E+11 |
Minimum of Months | 0.132021E+10 | 0.717177E+09 | 0.603031E+09 | 0.137059E+10 | 0.327241E+09 |
Maximum of Months | 0.265021E+10 | 0.141798E+10 | 0.123223E+10 | 0.470038E+10 | 0.279040E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55043652.16 | 30998916.52 | 24044735.65 | 60949707.44 | 98959168.78 |
February | 56100331.70 | 29818412.78 | 26281918.92 | 66912627.55 | 79338679.72 |
March | 84639537.56 | 45363691.56 | 39275846.00 | 0.111435E+09 | 74492756.49 |
April | 94147963.31 | 50850793.02 | 43297170.29 | 0.142827E+09 | 44738599.71 |
May | 0.104787E+09 | 56065315.14 | 48721237.05 | 0.176227E+09 | 29010613.73 |
June | 98711231.61 | 53018552.09 | 45692679.53 | 0.185848E+09 | 14886163.40 |
July | 90519227.34 | 44980594.47 | 45538632.87 | 0.170301E+09 | 12938811.56 |
August | 87663231.67 | 44676354.54 | 42986877.13 | 0.158380E+09 | 17976228.09 |
September | 86757331.28 | 48332410.25 | 38424921.03 | 0.148439E+09 | 33926895.49 |
October | 77173295.13 | 45040704.96 | 32132590.17 | 0.114656E+09 | 55108748.47 |
November | 62686080.96 | 38169018.84 | 24517062.12 | 76842293.38 | 87545512.09 |
December | 52199668.42 | 28356436.57 | 23843231.85 | 54191770.20 | 0.110330E+09 |
Annual Sum or Average | 0.950428E+09 | 0.515671E+09 | 0.434757E+09 | 0.146701E+10 | 0.659252E+09 |
Minimum of Months | 52199668.42 | 28356436.57 | 23843231.85 | 54191770.20 | 12938811.56 |
Maximum of Months | 0.104787E+09 | 56065315.14 | 48721237.05 | 0.185848E+09 | 0.110330E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.770482E+09 | 0.00 | 0.770482E+09 | 0.167799E+09 | 0.394370E+10 |
February | 0.849791E+09 | 0.00 | 0.849791E+09 | 0.378499E+09 | 0.321878E+10 |
March | 0.123126E+10 | 0.00 | 0.123126E+10 | 0.849195E+09 | 0.302616E+10 |
April | 0.137576E+10 | 10839023.03 | 0.136492E+10 | 0.157637E+10 | 0.172708E+10 |
May | 0.168610E+10 | 0.121928E+09 | 0.156417E+10 | 0.271473E+10 | 0.104352E+10 |
June | 0.173504E+10 | 0.213604E+09 | 0.152144E+10 | 0.364356E+10 | 0.542198E+09 |
July | 0.165696E+10 | 0.161293E+09 | 0.149567E+10 | 0.345901E+10 | 0.450145E+09 |
August | 0.139718E+10 | 28568732.44 | 0.136861E+10 | 0.269277E+10 | 0.612370E+09 |
September | 0.117984E+10 | 470797.93 | 0.117937E+10 | 0.197517E+10 | 0.120302E+10 |
October | 0.101224E+10 | 0.00 | 0.101224E+10 | 0.105685E+10 | 0.202216E+10 |
November | 0.790819E+09 | 0.00 | 0.790819E+09 | 0.267870E+09 | 0.334465E+10 |
December | 0.764515E+09 | 0.00 | 0.764515E+09 | 0.109463E+09 | 0.436437E+10 |
Annual Sum or Average | 0.144500E+11 | 0.536703E+09 | 0.139133E+11 | 0.188913E+11 | 0.254982E+11 |
Minimum of Months | 0.764515E+09 | 0.00 | 0.764515E+09 | 0.109463E+09 | 0.450145E+09 |
Maximum of Months | 0.173504E+10 | 0.213604E+09 | 0.156417E+10 | 0.364356E+10 | 0.436437E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137385E+10 | 0.745265E+09 | 0.628587E+09 | 0.132736E+10 | 0.244876E+10 |
February | 0.166020E+10 | 0.946305E+09 | 0.713898E+09 | 0.185951E+10 | 0.199064E+10 |
March | 0.226943E+10 | 0.125038E+10 | 0.101905E+10 | 0.277940E+10 | 0.187491E+10 |
April | 0.264634E+10 | 0.146813E+10 | 0.117821E+10 | 0.384918E+10 | 0.109661E+10 |
May | 0.282191E+10 | 0.153360E+10 | 0.128830E+10 | 0.461275E+10 | 0.699208E+09 |
June | 0.273241E+10 | 0.152009E+10 | 0.121232E+10 | 0.502904E+10 | 0.358368E+09 |
July | 0.253206E+10 | 0.132372E+10 | 0.120834E+10 | 0.467393E+10 | 0.303161E+09 |
August | 0.240939E+10 | 0.123310E+10 | 0.117629E+10 | 0.429049E+10 | 0.408776E+09 |
September | 0.231005E+10 | 0.131805E+10 | 0.991998E+09 | 0.384420E+10 | 0.758476E+09 |
October | 0.183579E+10 | 0.990761E+09 | 0.845034E+09 | 0.257375E+10 | 0.129087E+10 |
November | 0.159254E+10 | 0.927127E+09 | 0.665415E+09 | 0.174761E+10 | 0.206181E+10 |
December | 0.137267E+10 | 0.727272E+09 | 0.645400E+09 | 0.125037E+10 | 0.268768E+10 |
Annual Sum or Average | 0.255567E+11 | 0.139838E+11 | 0.115728E+11 | 0.378376E+11 | 0.159793E+11 |
Minimum of Months | 0.137267E+10 | 0.727272E+09 | 0.628587E+09 | 0.125037E+10 | 0.303161E+09 |
Maximum of Months | 0.282191E+10 | 0.153360E+10 | 0.128830E+10 | 0.502904E+10 | 0.268768E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.527083E+10 | 0.399320E+10 | 0.127763E+10 | 0.705916E+10 | 0.363906E+10 |
February | 0.441613E+10 | 0.311330E+10 | 0.130283E+10 | 0.600820E+10 | 0.299220E+10 |
March | 0.397356E+10 | 0.229114E+10 | 0.168242E+10 | 0.556997E+10 | 0.294493E+10 |
April | 0.260715E+10 | 0.972794E+09 | 0.163436E+10 | 0.412706E+10 | 0.179729E+10 |
May | 0.190386E+10 | 0.266478E+09 | 0.163738E+10 | 0.334682E+10 | 0.111766E+10 |
June | 0.158957E+10 | 0.100858E+09 | 0.148871E+10 | 0.344280E+10 | 0.555942E+09 |
July | 0.167440E+10 | 0.155220E+09 | 0.151918E+10 | 0.359706E+10 | 0.467771E+09 |
August | 0.213440E+10 | 0.564988E+09 | 0.156941E+10 | 0.431742E+10 | 0.647082E+09 |
September | 0.322408E+10 | 0.167502E+10 | 0.154906E+10 | 0.592428E+10 | 0.122772E+10 |
October | 0.452660E+10 | 0.306029E+10 | 0.146632E+10 | 0.711756E+10 | 0.199856E+10 |
November | 0.527163E+10 | 0.401897E+10 | 0.125266E+10 | 0.737939E+10 | 0.307786E+10 |
December | 0.539854E+10 | 0.405239E+10 | 0.134615E+10 | 0.708822E+10 | 0.392803E+10 |
Annual Sum or Average | 0.419907E+11 | 0.242646E+11 | 0.177261E+11 | 0.649779E+11 | 0.243941E+11 |
Minimum of Months | 0.158957E+10 | 0.100858E+09 | 0.125266E+10 | 0.334682E+10 | 0.467771E+09 |
Maximum of Months | 0.539854E+10 | 0.405239E+10 | 0.168242E+10 | 0.737939E+10 | 0.392803E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144720E+10 | 0.815021E+09 | 0.632177E+09 | 0.158266E+10 | 0.256826E+10 |
February | 0.147498E+10 | 0.783984E+09 | 0.690996E+09 | 0.171698E+10 | 0.212168E+10 |
March | 0.222533E+10 | 0.119270E+10 | 0.103263E+10 | 0.285826E+10 | 0.201823E+10 |
April | 0.247532E+10 | 0.133697E+10 | 0.113836E+10 | 0.370001E+10 | 0.120930E+10 |
May | 0.275503E+10 | 0.147407E+10 | 0.128096E+10 | 0.458678E+10 | 0.778117E+09 |
June | 0.259530E+10 | 0.139396E+10 | 0.120134E+10 | 0.485562E+10 | 0.402714E+09 |
July | 0.237991E+10 | 0.118263E+10 | 0.119729E+10 | 0.446265E+10 | 0.336294E+09 |
August | 0.230483E+10 | 0.117463E+10 | 0.113020E+10 | 0.416184E+10 | 0.449254E+09 |
September | 0.228101E+10 | 0.127075E+10 | 0.101026E+10 | 0.390464E+10 | 0.843854E+09 |
October | 0.202903E+10 | 0.118421E+10 | 0.844821E+09 | 0.301745E+10 | 0.137694E+10 |
November | 0.164813E+10 | 0.100354E+10 | 0.644595E+09 | 0.202274E+10 | 0.219135E+10 |
December | 0.137243E+10 | 0.745546E+09 | 0.626880E+09 | 0.142056E+10 | 0.281164E+10 |
Annual Sum or Average | 0.249885E+11 | 0.135580E+11 | 0.114305E+11 | 0.382902E+11 | 0.171076E+11 |
Minimum of Months | 0.137243E+10 | 0.745546E+09 | 0.626880E+09 | 0.142056E+10 | 0.336294E+09 |
Maximum of Months | 0.275503E+10 | 0.147407E+10 | 0.128096E+10 | 0.485562E+10 | 0.281164E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 76.48 | 1360.38 | 287.66 | 0.00 | 287.66 | 0.00 | 0.00 |
February | 171.98 | 1237.75 | 351.27 | 0.00 | 351.27 | 0.00 | 0.00 |
March | 330.94 | 1061.25 | 459.70 | 0.00 | 459.70 | 0.00 | 0.00 |
April | 610.58 | 632.96 | 530.77 | 4.18 | 526.59 | 0.00 | 0.00 |
May | 1010.51 | 377.06 | 629.52 | 45.52 | 583.99 | 0.00 | 0.00 |
June | 1396.16 | 206.32 | 669.38 | 82.41 | 586.97 | 0.00 | 0.00 |
July | 1279.94 | 166.18 | 618.64 | 60.22 | 558.42 | 0.00 | 0.00 |
August | 997.68 | 221.97 | 521.65 | 10.67 | 510.98 | 0.00 | 0.00 |
September | 759.61 | 444.89 | 455.18 | 0.18 | 455.00 | 0.00 | 0.00 |
October | 403.03 | 706.81 | 377.93 | 0.00 | 377.93 | 0.00 | 0.00 |
November | 118.90 | 1182.80 | 305.10 | 0.00 | 305.10 | 0.00 | 0.00 |
December | 54.40 | 1503.04 | 285.44 | 0.00 | 285.44 | 0.00 | 0.00 |
Annual Sum or Average | 603.06 | 756.06 | 458.21 | 17.02 | 441.19 | 0.00 | 0.00 |
Minimum of Months | 54.40 | 166.18 | 285.44 | 0.00 | 285.44 | 0.00 | 0.00 |
Maximum of Months | 1396.16 | 1503.04 | 669.38 | 82.41 | 586.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 515.15 | 844.72 | 512.94 | 278.25 | 234.69 | 0.00 | 0.00 |
February | 787.18 | 768.09 | 686.26 | 391.16 | 295.10 | 0.00 | 0.00 |
March | 1052.07 | 662.59 | 847.31 | 466.84 | 380.47 | 0.00 | 0.00 |
April | 1488.81 | 406.16 | 1020.96 | 566.41 | 454.56 | 0.00 | 0.00 |
May | 1721.27 | 253.06 | 1053.58 | 572.58 | 481.00 | 0.00 | 0.00 |
June | 1935.90 | 135.93 | 1054.17 | 586.46 | 467.72 | 0.00 | 0.00 |
July | 1739.55 | 111.45 | 945.36 | 494.22 | 451.14 | 0.00 | 0.00 |
August | 1599.13 | 148.16 | 899.56 | 460.39 | 439.18 | 0.00 | 0.00 |
September | 1484.30 | 281.88 | 891.22 | 508.51 | 382.72 | 0.00 | 0.00 |
October | 969.19 | 454.78 | 685.41 | 369.91 | 315.50 | 0.00 | 0.00 |
November | 693.79 | 735.65 | 614.41 | 357.69 | 256.72 | 0.00 | 0.00 |
December | 489.95 | 925.88 | 512.50 | 271.53 | 240.96 | 0.00 | 0.00 |
Annual Sum or Average | 1207.67 | 475.93 | 810.40 | 443.42 | 366.97 | 0.00 | 0.00 |
Minimum of Months | 489.95 | 111.45 | 512.50 | 271.53 | 234.69 | 0.00 | 0.00 |
Maximum of Months | 1935.90 | 925.88 | 1054.17 | 586.46 | 481.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2657.13 | 1264.36 | 1967.90 | 1490.89 | 477.01 | 0.00 | 0.00 |
February | 2502.19 | 1158.64 | 1825.45 | 1286.91 | 538.54 | 0.00 | 0.00 |
March | 2091.43 | 1040.40 | 1483.56 | 855.41 | 628.14 | 0.00 | 0.00 |
April | 1591.68 | 661.32 | 1005.85 | 375.31 | 630.54 | 0.00 | 0.00 |
May | 1244.12 | 402.21 | 710.82 | 99.49 | 611.33 | 0.00 | 0.00 |
June | 1318.76 | 210.75 | 613.26 | 38.91 | 574.35 | 0.00 | 0.00 |
July | 1330.99 | 172.10 | 625.15 | 57.95 | 567.20 | 0.00 | 0.00 |
August | 1602.76 | 234.46 | 796.89 | 210.94 | 585.95 | 0.00 | 0.00 |
September | 2280.54 | 455.33 | 1243.86 | 646.23 | 597.63 | 0.00 | 0.00 |
October | 2662.65 | 706.64 | 1690.04 | 1142.58 | 547.46 | 0.00 | 0.00 |
November | 2869.93 | 1106.36 | 2033.81 | 1550.53 | 483.28 | 0.00 | 0.00 |
December | 2677.07 | 1364.28 | 2015.58 | 1512.99 | 502.59 | 0.00 | 0.00 |
Annual Sum or Average | 2066.13 | 729.24 | 1331.52 | 769.43 | 562.09 | 0.00 | 0.00 |
Minimum of Months | 1244.12 | 172.10 | 613.26 | 38.91 | 477.01 | 0.00 | 0.00 |
Maximum of Months | 2869.93 | 1364.28 | 2033.81 | 1550.53 | 630.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 601.16 | 888.11 | 540.32 | 304.29 | 236.03 | 0.00 | 0.00 |
February | 719.13 | 817.55 | 609.70 | 324.07 | 285.63 | 0.00 | 0.00 |
March | 1073.79 | 709.34 | 830.84 | 445.30 | 385.54 | 0.00 | 0.00 |
April | 1426.91 | 444.40 | 954.99 | 515.80 | 439.18 | 0.00 | 0.00 |
May | 1707.37 | 280.17 | 1028.61 | 550.35 | 478.26 | 0.00 | 0.00 |
June | 1865.66 | 152.98 | 1001.27 | 537.79 | 463.48 | 0.00 | 0.00 |
July | 1657.76 | 123.80 | 888.56 | 441.54 | 447.02 | 0.00 | 0.00 |
August | 1547.51 | 163.03 | 860.52 | 438.56 | 421.97 | 0.00 | 0.00 |
September | 1503.38 | 312.96 | 880.02 | 490.26 | 389.76 | 0.00 | 0.00 |
October | 1130.21 | 484.26 | 757.55 | 442.13 | 315.42 | 0.00 | 0.00 |
November | 791.18 | 779.97 | 635.85 | 387.17 | 248.69 | 0.00 | 0.00 |
December | 542.65 | 971.12 | 512.40 | 278.35 | 234.05 | 0.00 | 0.00 |
Annual Sum or Average | 1215.95 | 509.08 | 792.38 | 429.92 | 362.46 | 0.00 | 0.00 |
Minimum of Months | 542.65 | 123.80 | 512.40 | 278.35 | 234.05 | 0.00 | 0.00 |
Maximum of Months | 1865.66 | 971.12 | 1028.61 | 550.35 | 478.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 68.06 | 1455.84 | 287.66 | 0.00 | 287.66 | 0.00 | 0.00 |
February | 177.68 | 1270.70 | 351.26 | 0.00 | 351.26 | 0.00 | 0.00 |
March | 356.82 | 1054.86 | 459.69 | 0.00 | 459.69 | 0.00 | 0.00 |
April | 645.31 | 614.09 | 530.76 | 4.18 | 526.58 | 0.00 | 0.00 |
May | 1044.05 | 361.80 | 629.50 | 45.52 | 583.98 | 0.00 | 0.00 |
June | 1428.90 | 191.23 | 669.37 | 82.41 | 586.96 | 0.00 | 0.00 |
July | 1304.30 | 159.88 | 618.63 | 60.22 | 558.41 | 0.00 | 0.00 |
August | 1007.35 | 228.39 | 521.64 | 10.67 | 510.97 | 0.00 | 0.00 |
September | 758.89 | 474.26 | 455.18 | 0.18 | 454.99 | 0.00 | 0.00 |
October | 392.28 | 774.18 | 377.92 | 0.00 | 377.92 | 0.00 | 0.00 |
November | 101.35 | 1320.89 | 305.09 | 0.00 | 305.09 | 0.00 | 0.00 |
December | 40.10 | 1650.99 | 285.43 | 0.00 | 285.43 | 0.00 | 0.00 |
Annual Sum or Average | 612.63 | 794.13 | 458.20 | 17.02 | 441.18 | 0.00 | 0.00 |
Minimum of Months | 40.10 | 159.88 | 285.43 | 0.00 | 285.43 | 0.00 | 0.00 |
Maximum of Months | 1428.90 | 1650.99 | 669.37 | 82.41 | 586.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 504.71 | 922.45 | 512.93 | 278.24 | 234.68 | 0.00 | 0.00 |
February | 787.74 | 810.43 | 686.25 | 391.16 | 295.09 | 0.00 | 0.00 |
March | 1066.97 | 678.57 | 847.29 | 466.83 | 380.46 | 0.00 | 0.00 |
April | 1509.94 | 412.28 | 1020.95 | 566.40 | 454.55 | 0.00 | 0.00 |
May | 1742.66 | 255.09 | 1053.56 | 572.57 | 480.99 | 0.00 | 0.00 |
June | 1956.69 | 133.94 | 1054.16 | 586.44 | 467.71 | 0.00 | 0.00 |
July | 1754.75 | 114.29 | 945.35 | 494.21 | 451.14 | 0.00 | 0.00 |
August | 1606.37 | 159.81 | 899.55 | 460.38 | 439.17 | 0.00 | 0.00 |
September | 1485.20 | 309.06 | 891.21 | 508.50 | 382.71 | 0.00 | 0.00 |
October | 963.94 | 504.76 | 685.40 | 369.90 | 315.50 | 0.00 | 0.00 |
November | 674.79 | 831.80 | 614.40 | 357.68 | 256.72 | 0.00 | 0.00 |
December | 468.08 | 1034.23 | 512.49 | 271.53 | 240.96 | 0.00 | 0.00 |
Annual Sum or Average | 1211.47 | 512.47 | 810.38 | 443.42 | 366.97 | 0.00 | 0.00 |
Minimum of Months | 468.08 | 114.29 | 512.49 | 271.53 | 234.68 | 0.00 | 0.00 |
Maximum of Months | 1956.69 | 1034.23 | 1054.16 | 586.44 | 480.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2659.19 | 1411.42 | 1967.83 | 1490.83 | 477.00 | 0.00 | 0.00 |
February | 2520.89 | 1247.04 | 1825.38 | 1286.86 | 538.52 | 0.00 | 0.00 |
March | 2130.51 | 1073.36 | 1483.50 | 855.38 | 628.12 | 0.00 | 0.00 |
April | 1630.58 | 659.51 | 1005.81 | 375.29 | 630.52 | 0.00 | 0.00 |
May | 1280.14 | 389.71 | 710.80 | 99.49 | 611.31 | 0.00 | 0.00 |
June | 1347.48 | 195.73 | 613.24 | 38.91 | 574.33 | 0.00 | 0.00 |
July | 1352.72 | 167.38 | 625.13 | 57.95 | 567.18 | 0.00 | 0.00 |
August | 1611.97 | 247.08 | 796.87 | 210.93 | 585.93 | 0.00 | 0.00 |
September | 2284.51 | 501.03 | 1243.82 | 646.20 | 597.61 | 0.00 | 0.00 |
October | 2661.91 | 792.01 | 1689.98 | 1142.53 | 547.44 | 0.00 | 0.00 |
November | 2853.61 | 1262.44 | 2033.73 | 1550.46 | 483.26 | 0.00 | 0.00 |
December | 2660.67 | 1537.37 | 2015.50 | 1512.92 | 502.58 | 0.00 | 0.00 |
Annual Sum or Average | 2079.84 | 788.07 | 1331.47 | 769.40 | 562.07 | 0.00 | 0.00 |
Minimum of Months | 1280.14 | 167.38 | 613.24 | 38.91 | 477.00 | 0.00 | 0.00 |
Maximum of Months | 2853.61 | 1537.37 | 2033.73 | 1550.46 | 630.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 598.29 | 971.39 | 540.31 | 304.29 | 236.03 | 0.00 | 0.00 |
February | 727.20 | 862.24 | 609.69 | 324.06 | 285.63 | 0.00 | 0.00 |
March | 1093.86 | 731.23 | 830.83 | 445.30 | 385.54 | 0.00 | 0.00 |
April | 1448.74 | 453.80 | 954.97 | 515.80 | 439.18 | 0.00 | 0.00 |
May | 1729.87 | 284.77 | 1028.60 | 550.34 | 478.25 | 0.00 | 0.00 |
June | 1885.12 | 150.99 | 1001.26 | 537.78 | 463.48 | 0.00 | 0.00 |
July | 1671.69 | 127.01 | 888.55 | 441.54 | 447.01 | 0.00 | 0.00 |
August | 1554.68 | 176.46 | 860.51 | 438.55 | 421.96 | 0.00 | 0.00 |
September | 1505.66 | 344.13 | 880.01 | 490.25 | 389.76 | 0.00 | 0.00 |
October | 1125.48 | 540.95 | 757.54 | 442.13 | 315.42 | 0.00 | 0.00 |
November | 779.44 | 888.00 | 635.85 | 387.16 | 248.68 | 0.00 | 0.00 |
December | 531.95 | 1083.01 | 512.40 | 278.35 | 234.05 | 0.00 | 0.00 |
Annual Sum or Average | 1223.04 | 549.62 | 792.37 | 429.91 | 362.46 | 0.00 | 0.00 |
Minimum of Months | 531.95 | 127.01 | 512.40 | 278.35 | 234.05 | 0.00 | 0.00 |
Maximum of Months | 1885.12 | 1083.01 | 1028.60 | 550.34 | 478.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 62.65 | 1472.41 | 287.66 | 0.00 | 287.66 | 0.00 | 0.00 |
February | 156.46 | 1330.51 | 351.27 | 0.00 | 351.27 | 0.00 | 0.00 |
March | 317.05 | 1129.84 | 459.70 | 0.00 | 459.70 | 0.00 | 0.00 |
April | 608.17 | 666.31 | 530.77 | 4.18 | 526.59 | 0.00 | 0.00 |
May | 1013.57 | 389.61 | 629.52 | 45.52 | 583.99 | 0.00 | 0.00 |
June | 1405.69 | 209.18 | 669.38 | 82.41 | 586.97 | 0.00 | 0.00 |
July | 1291.45 | 168.06 | 618.64 | 60.22 | 558.42 | 0.00 | 0.00 |
August | 1005.37 | 228.63 | 521.65 | 10.67 | 510.98 | 0.00 | 0.00 |
September | 762.03 | 464.13 | 455.18 | 0.18 | 455.00 | 0.00 | 0.00 |
October | 394.58 | 754.99 | 377.93 | 0.00 | 377.93 | 0.00 | 0.00 |
November | 103.34 | 1290.37 | 305.10 | 0.00 | 305.10 | 0.00 | 0.00 |
December | 40.87 | 1629.47 | 285.44 | 0.00 | 285.44 | 0.00 | 0.00 |
Annual Sum or Average | 599.04 | 808.54 | 458.21 | 17.02 | 441.19 | 0.00 | 0.00 |
Minimum of Months | 40.87 | 168.06 | 285.44 | 0.00 | 285.44 | 0.00 | 0.00 |
Maximum of Months | 1405.69 | 1629.47 | 669.38 | 82.41 | 586.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 495.58 | 914.26 | 512.94 | 278.25 | 234.69 | 0.00 | 0.00 |
February | 768.65 | 822.85 | 686.26 | 391.16 | 295.10 | 0.00 | 0.00 |
March | 1037.71 | 700.01 | 847.31 | 466.84 | 380.47 | 0.00 | 0.00 |
April | 1485.02 | 423.08 | 1020.96 | 566.41 | 454.56 | 0.00 | 0.00 |
May | 1722.20 | 261.05 | 1053.58 | 572.58 | 481.00 | 0.00 | 0.00 |
June | 1940.22 | 138.26 | 1054.17 | 586.46 | 467.72 | 0.00 | 0.00 |
July | 1745.04 | 113.19 | 945.36 | 494.22 | 451.14 | 0.00 | 0.00 |
August | 1601.88 | 152.62 | 899.56 | 460.39 | 439.18 | 0.00 | 0.00 |
September | 1483.10 | 292.62 | 891.22 | 508.51 | 382.72 | 0.00 | 0.00 |
October | 960.93 | 481.95 | 685.41 | 369.91 | 315.50 | 0.00 | 0.00 |
November | 674.23 | 795.45 | 614.41 | 357.69 | 256.72 | 0.00 | 0.00 |
December | 466.83 | 1003.47 | 512.50 | 271.53 | 240.96 | 0.00 | 0.00 |
Annual Sum or Average | 1199.82 | 506.70 | 810.40 | 443.42 | 366.97 | 0.00 | 0.00 |
Minimum of Months | 466.83 | 113.19 | 512.50 | 271.53 | 234.69 | 0.00 | 0.00 |
Maximum of Months | 1940.22 | 1003.47 | 1054.17 | 586.46 | 481.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2635.59 | 1358.67 | 1967.90 | 1490.89 | 477.01 | 0.00 | 0.00 |
February | 2483.55 | 1236.86 | 1825.45 | 1286.91 | 538.54 | 0.00 | 0.00 |
March | 2079.59 | 1099.51 | 1483.56 | 855.41 | 628.14 | 0.00 | 0.00 |
April | 1592.23 | 693.40 | 1005.85 | 375.31 | 630.54 | 0.00 | 0.00 |
May | 1249.56 | 417.29 | 710.82 | 99.49 | 611.33 | 0.00 | 0.00 |
June | 1328.24 | 214.48 | 613.26 | 38.91 | 574.35 | 0.00 | 0.00 |
July | 1342.99 | 174.65 | 625.15 | 57.95 | 567.20 | 0.00 | 0.00 |
August | 1611.94 | 241.59 | 796.89 | 210.94 | 585.95 | 0.00 | 0.00 |
September | 2285.60 | 473.66 | 1243.86 | 646.23 | 597.63 | 0.00 | 0.00 |
October | 2657.39 | 746.18 | 1690.04 | 1142.58 | 547.46 | 0.00 | 0.00 |
November | 2846.99 | 1187.44 | 2033.81 | 1550.53 | 483.28 | 0.00 | 0.00 |
December | 2646.44 | 1466.56 | 2015.58 | 1512.99 | 502.59 | 0.00 | 0.00 |
Annual Sum or Average | 2060.44 | 773.53 | 1331.52 | 769.43 | 562.09 | 0.00 | 0.00 |
Minimum of Months | 1249.56 | 174.65 | 613.26 | 38.91 | 477.01 | 0.00 | 0.00 |
Maximum of Months | 2846.99 | 1466.56 | 2033.81 | 1550.53 | 630.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 590.90 | 958.88 | 540.32 | 304.29 | 236.03 | 0.00 | 0.00 |
February | 709.73 | 877.02 | 609.70 | 324.07 | 285.63 | 0.00 | 0.00 |
March | 1067.15 | 753.52 | 830.84 | 445.30 | 385.54 | 0.00 | 0.00 |
April | 1427.47 | 466.55 | 954.99 | 515.80 | 439.18 | 0.00 | 0.00 |
May | 1712.51 | 290.52 | 1028.61 | 550.35 | 478.26 | 0.00 | 0.00 |
June | 1873.31 | 155.37 | 1001.27 | 537.79 | 463.48 | 0.00 | 0.00 |
July | 1666.16 | 125.56 | 888.56 | 441.54 | 447.02 | 0.00 | 0.00 |
August | 1553.85 | 167.73 | 860.52 | 438.56 | 421.97 | 0.00 | 0.00 |
September | 1506.42 | 325.56 | 880.02 | 490.26 | 389.76 | 0.00 | 0.00 |
October | 1126.59 | 514.09 | 757.55 | 442.13 | 315.42 | 0.00 | 0.00 |
November | 780.38 | 845.43 | 635.85 | 387.17 | 248.69 | 0.00 | 0.00 |
December | 530.38 | 1049.74 | 512.40 | 278.35 | 234.05 | 0.00 | 0.00 |
Annual Sum or Average | 1214.17 | 542.48 | 792.38 | 429.92 | 362.46 | 0.00 | 0.00 |
Minimum of Months | 530.38 | 125.56 | 512.40 | 278.35 | 234.05 | 0.00 | 0.00 |
Maximum of Months | 1873.31 | 1049.74 | 1028.61 | 550.35 | 478.26 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.204857E+09 | 0.364364E+10 | 0.770482E+09 | 0.00 | 0.770482E+09 | 0.00 | 0.00 |
February | 0.416053E+09 | 0.299437E+10 | 0.849791E+09 | 0.00 | 0.849791E+09 | 0.00 | 0.00 |
March | 0.886384E+09 | 0.284244E+10 | 0.123126E+10 | 0.00 | 0.123126E+10 | 0.00 | 0.00 |
April | 0.158263E+10 | 0.164062E+10 | 0.137576E+10 | 10839023.03 | 0.136492E+10 | 0.00 | 0.00 |
May | 0.270655E+10 | 0.100992E+10 | 0.168610E+10 | 0.121928E+09 | 0.156417E+10 | 0.00 | 0.00 |
June | 0.361884E+10 | 0.534790E+09 | 0.173504E+10 | 0.213604E+09 | 0.152144E+10 | 0.00 | 0.00 |
July | 0.342819E+10 | 0.445098E+09 | 0.165696E+10 | 0.161293E+09 | 0.149567E+10 | 0.00 | 0.00 |
August | 0.267219E+10 | 0.594527E+09 | 0.139718E+10 | 28568732.44 | 0.136861E+10 | 0.00 | 0.00 |
September | 0.196890E+10 | 0.115315E+10 | 0.117984E+10 | 470797.93 | 0.117937E+10 | 0.00 | 0.00 |
October | 0.107948E+10 | 0.189312E+10 | 0.101224E+10 | 0.00 | 0.101224E+10 | 0.00 | 0.00 |
November | 0.308191E+09 | 0.306581E+10 | 0.790819E+09 | 0.00 | 0.790819E+09 | 0.00 | 0.00 |
December | 0.145712E+09 | 0.402575E+10 | 0.764515E+09 | 0.00 | 0.764515E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.190180E+11 | 0.238432E+11 | 0.144500E+11 | 0.536703E+09 | 0.139133E+11 | 0.00 | 0.00 |
Minimum of Months | 0.145712E+09 | 0.445098E+09 | 0.764515E+09 | 0.00 | 0.764515E+09 | 0.00 | 0.00 |
Maximum of Months | 0.361884E+10 | 0.402575E+10 | 0.173504E+10 | 0.213604E+09 | 0.156417E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.137978E+10 | 0.226249E+10 | 0.137385E+10 | 0.745265E+09 | 0.628587E+09 | 0.00 | 0.00 |
February | 0.190434E+10 | 0.185815E+10 | 0.166020E+10 | 0.946305E+09 | 0.713898E+09 | 0.00 | 0.00 |
March | 0.281786E+10 | 0.177469E+10 | 0.226943E+10 | 0.125038E+10 | 0.101905E+10 | 0.00 | 0.00 |
April | 0.385900E+10 | 0.105278E+10 | 0.264634E+10 | 0.146813E+10 | 0.117821E+10 | 0.00 | 0.00 |
May | 0.461024E+10 | 0.677785E+09 | 0.282191E+10 | 0.153360E+10 | 0.128830E+10 | 0.00 | 0.00 |
June | 0.501786E+10 | 0.352322E+09 | 0.273241E+10 | 0.152009E+10 | 0.121232E+10 | 0.00 | 0.00 |
July | 0.465921E+10 | 0.298502E+09 | 0.253206E+10 | 0.132372E+10 | 0.120834E+10 | 0.00 | 0.00 |
August | 0.428310E+10 | 0.396831E+09 | 0.240939E+10 | 0.123310E+10 | 0.117629E+10 | 0.00 | 0.00 |
September | 0.384731E+10 | 0.730624E+09 | 0.231005E+10 | 0.131805E+10 | 0.991998E+09 | 0.00 | 0.00 |
October | 0.259588E+10 | 0.121810E+10 | 0.183579E+10 | 0.990761E+09 | 0.845034E+09 | 0.00 | 0.00 |
November | 0.179831E+10 | 0.190679E+10 | 0.159254E+10 | 0.927127E+09 | 0.665415E+09 | 0.00 | 0.00 |
December | 0.131228E+10 | 0.247988E+10 | 0.137267E+10 | 0.727272E+09 | 0.645400E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.380852E+11 | 0.150089E+11 | 0.255567E+11 | 0.139838E+11 | 0.115728E+11 | 0.00 | 0.00 |
Minimum of Months | 0.131228E+10 | 0.298502E+09 | 0.137267E+10 | 0.727272E+09 | 0.628587E+09 | 0.00 | 0.00 |
Maximum of Months | 0.501786E+10 | 0.247988E+10 | 0.282191E+10 | 0.153360E+10 | 0.128830E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.711686E+10 | 0.338645E+10 | 0.527083E+10 | 0.399320E+10 | 0.127763E+10 | 0.00 | 0.00 |
February | 0.605330E+10 | 0.280297E+10 | 0.441613E+10 | 0.311330E+10 | 0.130283E+10 | 0.00 | 0.00 |
March | 0.560169E+10 | 0.278661E+10 | 0.397356E+10 | 0.229114E+10 | 0.168242E+10 | 0.00 | 0.00 |
April | 0.412562E+10 | 0.171415E+10 | 0.260715E+10 | 0.972794E+09 | 0.163436E+10 | 0.00 | 0.00 |
May | 0.333224E+10 | 0.107727E+10 | 0.190386E+10 | 0.266478E+09 | 0.163738E+10 | 0.00 | 0.00 |
June | 0.341823E+10 | 0.546259E+09 | 0.158957E+10 | 0.100858E+09 | 0.148871E+10 | 0.00 | 0.00 |
July | 0.356492E+10 | 0.460960E+09 | 0.167440E+10 | 0.155220E+09 | 0.151918E+10 | 0.00 | 0.00 |
August | 0.429282E+10 | 0.627975E+09 | 0.213440E+10 | 0.564988E+09 | 0.156941E+10 | 0.00 | 0.00 |
September | 0.591115E+10 | 0.118022E+10 | 0.322408E+10 | 0.167502E+10 | 0.154906E+10 | 0.00 | 0.00 |
October | 0.713164E+10 | 0.189265E+10 | 0.452660E+10 | 0.306029E+10 | 0.146632E+10 | 0.00 | 0.00 |
November | 0.743887E+10 | 0.286769E+10 | 0.527163E+10 | 0.401897E+10 | 0.125266E+10 | 0.00 | 0.00 |
December | 0.717028E+10 | 0.365409E+10 | 0.539854E+10 | 0.405239E+10 | 0.134615E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.651576E+11 | 0.229973E+11 | 0.419907E+11 | 0.242646E+11 | 0.177261E+11 | 0.00 | 0.00 |
Minimum of Months | 0.333224E+10 | 0.460960E+09 | 0.158957E+10 | 0.100858E+09 | 0.125266E+10 | 0.00 | 0.00 |
Maximum of Months | 0.743887E+10 | 0.365409E+10 | 0.539854E+10 | 0.405239E+10 | 0.168242E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.161014E+10 | 0.237872E+10 | 0.144720E+10 | 0.815021E+09 | 0.632177E+09 | 0.00 | 0.00 |
February | 0.173971E+10 | 0.197782E+10 | 0.147498E+10 | 0.783984E+09 | 0.690996E+09 | 0.00 | 0.00 |
March | 0.287604E+10 | 0.189991E+10 | 0.222533E+10 | 0.119270E+10 | 0.103263E+10 | 0.00 | 0.00 |
April | 0.369856E+10 | 0.115189E+10 | 0.247532E+10 | 0.133697E+10 | 0.113836E+10 | 0.00 | 0.00 |
May | 0.457301E+10 | 0.750413E+09 | 0.275503E+10 | 0.147407E+10 | 0.128096E+10 | 0.00 | 0.00 |
June | 0.483579E+10 | 0.396519E+09 | 0.259530E+10 | 0.139396E+10 | 0.120134E+10 | 0.00 | 0.00 |
July | 0.444013E+10 | 0.331578E+09 | 0.237991E+10 | 0.118263E+10 | 0.119729E+10 | 0.00 | 0.00 |
August | 0.414486E+10 | 0.436671E+09 | 0.230483E+10 | 0.117463E+10 | 0.113020E+10 | 0.00 | 0.00 |
September | 0.389676E+10 | 0.811205E+09 | 0.228101E+10 | 0.127075E+10 | 0.101026E+10 | 0.00 | 0.00 |
October | 0.302714E+10 | 0.129704E+10 | 0.202903E+10 | 0.118421E+10 | 0.844821E+09 | 0.00 | 0.00 |
November | 0.205074E+10 | 0.202167E+10 | 0.164813E+10 | 0.100354E+10 | 0.644595E+09 | 0.00 | 0.00 |
December | 0.145343E+10 | 0.260105E+10 | 0.137243E+10 | 0.745546E+09 | 0.626880E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.383463E+11 | 0.160545E+11 | 0.249885E+11 | 0.135580E+11 | 0.114305E+11 | 0.00 | 0.00 |
Minimum of Months | 0.145343E+10 | 0.331578E+09 | 0.137243E+10 | 0.745546E+09 | 0.626880E+09 | 0.00 | 0.00 |
Maximum of Months | 0.483579E+10 | 0.260105E+10 | 0.275503E+10 | 0.147407E+10 | 0.128096E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.182295E+09 | 0.389931E+10 | 0.770467E+09 | 0.00 | 0.770467E+09 | 0.00 | 0.00 |
February | 0.429853E+09 | 0.307407E+10 | 0.849775E+09 | 0.00 | 0.849775E+09 | 0.00 | 0.00 |
March | 0.955700E+09 | 0.282534E+10 | 0.123123E+10 | 0.00 | 0.123123E+10 | 0.00 | 0.00 |
April | 0.167264E+10 | 0.159171E+10 | 0.137574E+10 | 10838704.44 | 0.136490E+10 | 0.00 | 0.00 |
May | 0.279639E+10 | 0.969056E+09 | 0.168606E+10 | 0.121925E+09 | 0.156414E+10 | 0.00 | 0.00 |
June | 0.370372E+10 | 0.495680E+09 | 0.173501E+10 | 0.213597E+09 | 0.152141E+10 | 0.00 | 0.00 |
July | 0.349342E+10 | 0.428220E+09 | 0.165693E+10 | 0.161288E+09 | 0.149564E+10 | 0.00 | 0.00 |
August | 0.269808E+10 | 0.611730E+09 | 0.139716E+10 | 28567892.73 | 0.136859E+10 | 0.00 | 0.00 |
September | 0.196704E+10 | 0.122927E+10 | 0.117982E+10 | 470784.09 | 0.117935E+10 | 0.00 | 0.00 |
October | 0.105069E+10 | 0.207357E+10 | 0.101223E+10 | 0.00 | 0.101223E+10 | 0.00 | 0.00 |
November | 0.262692E+09 | 0.342375E+10 | 0.790805E+09 | 0.00 | 0.790805E+09 | 0.00 | 0.00 |
December | 0.107414E+09 | 0.442201E+10 | 0.764500E+09 | 0.00 | 0.764500E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.193199E+11 | 0.250437E+11 | 0.144497E+11 | 0.536687E+09 | 0.139130E+11 | 0.00 | 0.00 |
Minimum of Months | 0.107414E+09 | 0.428220E+09 | 0.764500E+09 | 0.00 | 0.764500E+09 | 0.00 | 0.00 |
Maximum of Months | 0.370372E+10 | 0.442201E+10 | 0.173501E+10 | 0.213597E+09 | 0.156414E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.135182E+10 | 0.247069E+10 | 0.137383E+10 | 0.745251E+09 | 0.628580E+09 | 0.00 | 0.00 |
February | 0.190570E+10 | 0.196059E+10 | 0.166018E+10 | 0.946287E+09 | 0.713890E+09 | 0.00 | 0.00 |
March | 0.285779E+10 | 0.181749E+10 | 0.226939E+10 | 0.125036E+10 | 0.101904E+10 | 0.00 | 0.00 |
April | 0.391377E+10 | 0.106863E+10 | 0.264630E+10 | 0.146810E+10 | 0.117820E+10 | 0.00 | 0.00 |
May | 0.466754E+10 | 0.683230E+09 | 0.282186E+10 | 0.153357E+10 | 0.128829E+10 | 0.00 | 0.00 |
June | 0.507174E+10 | 0.347183E+09 | 0.273237E+10 | 0.152006E+10 | 0.121231E+10 | 0.00 | 0.00 |
July | 0.469993E+10 | 0.306111E+09 | 0.253202E+10 | 0.132369E+10 | 0.120833E+10 | 0.00 | 0.00 |
August | 0.430250E+10 | 0.428026E+09 | 0.240935E+10 | 0.123308E+10 | 0.117627E+10 | 0.00 | 0.00 |
September | 0.384963E+10 | 0.801092E+09 | 0.231001E+10 | 0.131803E+10 | 0.991988E+09 | 0.00 | 0.00 |
October | 0.258180E+10 | 0.135195E+10 | 0.183577E+10 | 0.990741E+09 | 0.845025E+09 | 0.00 | 0.00 |
November | 0.174905E+10 | 0.215604E+10 | 0.159252E+10 | 0.927109E+09 | 0.665408E+09 | 0.00 | 0.00 |
December | 0.125369E+10 | 0.277009E+10 | 0.137265E+10 | 0.727258E+09 | 0.645392E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.382050E+11 | 0.161611E+11 | 0.255563E+11 | 0.139835E+11 | 0.115727E+11 | 0.00 | 0.00 |
Minimum of Months | 0.125369E+10 | 0.306111E+09 | 0.137265E+10 | 0.727258E+09 | 0.628580E+09 | 0.00 | 0.00 |
Maximum of Months | 0.507174E+10 | 0.277009E+10 | 0.282186E+10 | 0.153357E+10 | 0.128829E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.712238E+10 | 0.378033E+10 | 0.527062E+10 | 0.399304E+10 | 0.127758E+10 | 0.00 | 0.00 |
February | 0.609853E+10 | 0.301685E+10 | 0.441596E+10 | 0.311317E+10 | 0.130279E+10 | 0.00 | 0.00 |
March | 0.570635E+10 | 0.287490E+10 | 0.397341E+10 | 0.229105E+10 | 0.168237E+10 | 0.00 | 0.00 |
April | 0.422647E+10 | 0.170945E+10 | 0.260707E+10 | 0.972753E+09 | 0.163431E+10 | 0.00 | 0.00 |
May | 0.342873E+10 | 0.104379E+10 | 0.190381E+10 | 0.266467E+09 | 0.163734E+10 | 0.00 | 0.00 |
June | 0.349268E+10 | 0.507327E+09 | 0.158953E+10 | 0.100854E+09 | 0.148867E+10 | 0.00 | 0.00 |
July | 0.362314E+10 | 0.448322E+09 | 0.167436E+10 | 0.155213E+09 | 0.151914E+10 | 0.00 | 0.00 |
August | 0.431751E+10 | 0.661775E+09 | 0.213433E+10 | 0.564965E+09 | 0.156937E+10 | 0.00 | 0.00 |
September | 0.592145E+10 | 0.129866E+10 | 0.322397E+10 | 0.167495E+10 | 0.154902E+10 | 0.00 | 0.00 |
October | 0.712966E+10 | 0.212133E+10 | 0.452643E+10 | 0.306016E+10 | 0.146627E+10 | 0.00 | 0.00 |
November | 0.739656E+10 | 0.327225E+10 | 0.527142E+10 | 0.401880E+10 | 0.125262E+10 | 0.00 | 0.00 |
December | 0.712634E+10 | 0.411768E+10 | 0.539832E+10 | 0.405222E+10 | 0.134610E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.655898E+11 | 0.248527E+11 | 0.419892E+11 | 0.242636E+11 | 0.177256E+11 | 0.00 | 0.00 |
Minimum of Months | 0.342873E+10 | 0.448322E+09 | 0.158953E+10 | 0.100854E+09 | 0.125262E+10 | 0.00 | 0.00 |
Maximum of Months | 0.739656E+10 | 0.411768E+10 | 0.539832E+10 | 0.405222E+10 | 0.168237E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.160246E+10 | 0.260178E+10 | 0.144718E+10 | 0.815008E+09 | 0.632172E+09 | 0.00 | 0.00 |
February | 0.175923E+10 | 0.208593E+10 | 0.147496E+10 | 0.783971E+09 | 0.690990E+09 | 0.00 | 0.00 |
March | 0.292979E+10 | 0.195852E+10 | 0.222530E+10 | 0.119268E+10 | 0.103262E+10 | 0.00 | 0.00 |
April | 0.375513E+10 | 0.117624E+10 | 0.247529E+10 | 0.133694E+10 | 0.113835E+10 | 0.00 | 0.00 |
May | 0.463328E+10 | 0.762731E+09 | 0.275499E+10 | 0.147404E+10 | 0.128095E+10 | 0.00 | 0.00 |
June | 0.488623E+10 | 0.391379E+09 | 0.259527E+10 | 0.139394E+10 | 0.120133E+10 | 0.00 | 0.00 |
July | 0.447746E+10 | 0.340180E+09 | 0.237989E+10 | 0.118261E+10 | 0.119728E+10 | 0.00 | 0.00 |
August | 0.416406E+10 | 0.472621E+09 | 0.230480E+10 | 0.117461E+10 | 0.113019E+10 | 0.00 | 0.00 |
September | 0.390268E+10 | 0.891987E+09 | 0.228098E+10 | 0.127073E+10 | 0.101025E+10 | 0.00 | 0.00 |
October | 0.301448E+10 | 0.144889E+10 | 0.202900E+10 | 0.118419E+10 | 0.844813E+09 | 0.00 | 0.00 |
November | 0.202030E+10 | 0.230170E+10 | 0.164811E+10 | 0.100352E+10 | 0.644590E+09 | 0.00 | 0.00 |
December | 0.142478E+10 | 0.290073E+10 | 0.137241E+10 | 0.745533E+09 | 0.626874E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.385699E+11 | 0.173327E+11 | 0.249882E+11 | 0.135578E+11 | 0.114304E+11 | 0.00 | 0.00 |
Minimum of Months | 0.142478E+10 | 0.340180E+09 | 0.137241E+10 | 0.745533E+09 | 0.626874E+09 | 0.00 | 0.00 |
Maximum of Months | 0.488623E+10 | 0.290073E+10 | 0.275499E+10 | 0.147404E+10 | 0.128095E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.167799E+09 | 0.394370E+10 | 0.770482E+09 | 0.00 | 0.770482E+09 | 0.00 | 0.00 |
February | 0.378499E+09 | 0.321878E+10 | 0.849791E+09 | 0.00 | 0.849791E+09 | 0.00 | 0.00 |
March | 0.849195E+09 | 0.302616E+10 | 0.123126E+10 | 0.00 | 0.123126E+10 | 0.00 | 0.00 |
April | 0.157637E+10 | 0.172708E+10 | 0.137576E+10 | 10839023.03 | 0.136492E+10 | 0.00 | 0.00 |
May | 0.271473E+10 | 0.104352E+10 | 0.168610E+10 | 0.121928E+09 | 0.156417E+10 | 0.00 | 0.00 |
June | 0.364356E+10 | 0.542198E+09 | 0.173504E+10 | 0.213604E+09 | 0.152144E+10 | 0.00 | 0.00 |
July | 0.345901E+10 | 0.450145E+09 | 0.165696E+10 | 0.161293E+09 | 0.149567E+10 | 0.00 | 0.00 |
August | 0.269277E+10 | 0.612370E+09 | 0.139718E+10 | 28568732.44 | 0.136861E+10 | 0.00 | 0.00 |
September | 0.197517E+10 | 0.120302E+10 | 0.117984E+10 | 470797.93 | 0.117937E+10 | 0.00 | 0.00 |
October | 0.105685E+10 | 0.202216E+10 | 0.101224E+10 | 0.00 | 0.101224E+10 | 0.00 | 0.00 |
November | 0.267870E+09 | 0.334465E+10 | 0.790819E+09 | 0.00 | 0.790819E+09 | 0.00 | 0.00 |
December | 0.109463E+09 | 0.436437E+10 | 0.764515E+09 | 0.00 | 0.764515E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.188913E+11 | 0.254982E+11 | 0.144500E+11 | 0.536703E+09 | 0.139133E+11 | 0.00 | 0.00 |
Minimum of Months | 0.109463E+09 | 0.450145E+09 | 0.764515E+09 | 0.00 | 0.764515E+09 | 0.00 | 0.00 |
Maximum of Months | 0.364356E+10 | 0.436437E+10 | 0.173504E+10 | 0.213604E+09 | 0.156417E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.132736E+10 | 0.244876E+10 | 0.137385E+10 | 0.745265E+09 | 0.628587E+09 | 0.00 | 0.00 |
February | 0.185951E+10 | 0.199064E+10 | 0.166020E+10 | 0.946305E+09 | 0.713898E+09 | 0.00 | 0.00 |
March | 0.277940E+10 | 0.187491E+10 | 0.226943E+10 | 0.125038E+10 | 0.101905E+10 | 0.00 | 0.00 |
April | 0.384918E+10 | 0.109661E+10 | 0.264634E+10 | 0.146813E+10 | 0.117821E+10 | 0.00 | 0.00 |
May | 0.461275E+10 | 0.699208E+09 | 0.282191E+10 | 0.153360E+10 | 0.128830E+10 | 0.00 | 0.00 |
June | 0.502904E+10 | 0.358368E+09 | 0.273241E+10 | 0.152009E+10 | 0.121232E+10 | 0.00 | 0.00 |
July | 0.467393E+10 | 0.303161E+09 | 0.253206E+10 | 0.132372E+10 | 0.120834E+10 | 0.00 | 0.00 |
August | 0.429049E+10 | 0.408776E+09 | 0.240939E+10 | 0.123310E+10 | 0.117629E+10 | 0.00 | 0.00 |
September | 0.384420E+10 | 0.758476E+09 | 0.231005E+10 | 0.131805E+10 | 0.991998E+09 | 0.00 | 0.00 |
October | 0.257375E+10 | 0.129087E+10 | 0.183579E+10 | 0.990761E+09 | 0.845034E+09 | 0.00 | 0.00 |
November | 0.174761E+10 | 0.206181E+10 | 0.159254E+10 | 0.927127E+09 | 0.665415E+09 | 0.00 | 0.00 |
December | 0.125037E+10 | 0.268768E+10 | 0.137267E+10 | 0.727272E+09 | 0.645400E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.378376E+11 | 0.159793E+11 | 0.255567E+11 | 0.139838E+11 | 0.115728E+11 | 0.00 | 0.00 |
Minimum of Months | 0.125037E+10 | 0.303161E+09 | 0.137267E+10 | 0.727272E+09 | 0.628587E+09 | 0.00 | 0.00 |
Maximum of Months | 0.502904E+10 | 0.268768E+10 | 0.282191E+10 | 0.153360E+10 | 0.128830E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.705916E+10 | 0.363906E+10 | 0.527083E+10 | 0.399320E+10 | 0.127763E+10 | 0.00 | 0.00 |
February | 0.600820E+10 | 0.299220E+10 | 0.441613E+10 | 0.311330E+10 | 0.130283E+10 | 0.00 | 0.00 |
March | 0.556997E+10 | 0.294493E+10 | 0.397356E+10 | 0.229114E+10 | 0.168242E+10 | 0.00 | 0.00 |
April | 0.412706E+10 | 0.179729E+10 | 0.260715E+10 | 0.972794E+09 | 0.163436E+10 | 0.00 | 0.00 |
May | 0.334682E+10 | 0.111766E+10 | 0.190386E+10 | 0.266478E+09 | 0.163738E+10 | 0.00 | 0.00 |
June | 0.344280E+10 | 0.555942E+09 | 0.158957E+10 | 0.100858E+09 | 0.148871E+10 | 0.00 | 0.00 |
July | 0.359706E+10 | 0.467771E+09 | 0.167440E+10 | 0.155220E+09 | 0.151918E+10 | 0.00 | 0.00 |
August | 0.431742E+10 | 0.647082E+09 | 0.213440E+10 | 0.564988E+09 | 0.156941E+10 | 0.00 | 0.00 |
September | 0.592428E+10 | 0.122772E+10 | 0.322408E+10 | 0.167502E+10 | 0.154906E+10 | 0.00 | 0.00 |
October | 0.711756E+10 | 0.199856E+10 | 0.452660E+10 | 0.306029E+10 | 0.146632E+10 | 0.00 | 0.00 |
November | 0.737939E+10 | 0.307786E+10 | 0.527163E+10 | 0.401897E+10 | 0.125266E+10 | 0.00 | 0.00 |
December | 0.708822E+10 | 0.392803E+10 | 0.539854E+10 | 0.405239E+10 | 0.134615E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.649779E+11 | 0.243941E+11 | 0.419907E+11 | 0.242646E+11 | 0.177261E+11 | 0.00 | 0.00 |
Minimum of Months | 0.334682E+10 | 0.467771E+09 | 0.158957E+10 | 0.100858E+09 | 0.125266E+10 | 0.00 | 0.00 |
Maximum of Months | 0.737939E+10 | 0.392803E+10 | 0.539854E+10 | 0.405239E+10 | 0.168242E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.158266E+10 | 0.256826E+10 | 0.144720E+10 | 0.815021E+09 | 0.632177E+09 | 0.00 | 0.00 |
February | 0.171698E+10 | 0.212168E+10 | 0.147498E+10 | 0.783984E+09 | 0.690996E+09 | 0.00 | 0.00 |
March | 0.285826E+10 | 0.201823E+10 | 0.222533E+10 | 0.119270E+10 | 0.103263E+10 | 0.00 | 0.00 |
April | 0.370001E+10 | 0.120930E+10 | 0.247532E+10 | 0.133697E+10 | 0.113836E+10 | 0.00 | 0.00 |
May | 0.458678E+10 | 0.778117E+09 | 0.275503E+10 | 0.147407E+10 | 0.128096E+10 | 0.00 | 0.00 |
June | 0.485562E+10 | 0.402714E+09 | 0.259530E+10 | 0.139396E+10 | 0.120134E+10 | 0.00 | 0.00 |
July | 0.446265E+10 | 0.336294E+09 | 0.237991E+10 | 0.118263E+10 | 0.119729E+10 | 0.00 | 0.00 |
August | 0.416184E+10 | 0.449254E+09 | 0.230483E+10 | 0.117463E+10 | 0.113020E+10 | 0.00 | 0.00 |
September | 0.390464E+10 | 0.843854E+09 | 0.228101E+10 | 0.127075E+10 | 0.101026E+10 | 0.00 | 0.00 |
October | 0.301745E+10 | 0.137694E+10 | 0.202903E+10 | 0.118421E+10 | 0.844821E+09 | 0.00 | 0.00 |
November | 0.202274E+10 | 0.219135E+10 | 0.164813E+10 | 0.100354E+10 | 0.644595E+09 | 0.00 | 0.00 |
December | 0.142056E+10 | 0.281164E+10 | 0.137243E+10 | 0.745546E+09 | 0.626880E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.382902E+11 | 0.171076E+11 | 0.249885E+11 | 0.135580E+11 | 0.114305E+11 | 0.00 | 0.00 |
Minimum of Months | 0.142056E+10 | 0.336294E+09 | 0.137243E+10 | 0.745546E+09 | 0.626880E+09 | 0.00 | 0.00 |
Maximum of Months | 0.485562E+10 | 0.281164E+10 | 0.275503E+10 | 0.147407E+10 | 0.128096E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.484108E+10 | -0.413881E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -702275074.2 | 58.98 | 0.00 | 0.00 |
February | 0.438967E+10 | -0.375852E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -631145817.3 | 58.98 | 0.00 | 0.00 |
March | 0.498122E+10 | -0.428474E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -696482948.1 | 58.98 | 0.00 | 0.00 |
April | 0.426801E+10 | -0.359976E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668251732.6 | 58.98 | 0.00 | 0.00 |
May | 0.423500E+10 | -0.354631E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688690979.8 | 58.98 | 0.00 | 0.00 |
June | 0.390826E+10 | -0.324231E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -665945480.5 | 58.98 | 0.00 | 0.00 |
July | 0.359115E+10 | -0.290439E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -686763566.4 | 58.98 | 0.00 | 0.00 |
August | 0.390410E+10 | -0.321574E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688359609.7 | 58.98 | 0.00 | 0.00 |
September | 0.371321E+10 | -0.304921E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -663998942.1 | 58.98 | 0.00 | 0.00 |
October | 0.410540E+10 | -0.341651E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688891401.3 | 58.99 | 0.00 | 0.00 |
November | 0.433130E+10 | -0.366006E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -671240207.4 | 58.98 | 0.00 | 0.00 |
December | 0.457865E+10 | -0.387690E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -701755803.0 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.508471E+11 | -0.426932E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.815380E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.359115E+10 | -0.428474E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -702275074.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.498122E+10 | -0.290439E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -631145817.3 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.49 | 0.48 | 01-JAN-08:09 | 8786.70 | 38.51 | 276.00 | 279.17 | 1902.10 | 26.35 | 156.67 | 262.67 |
February | 268.33 | 0.49 | 0.48 | 01-FEB-07:00 | 9446.72 | 36.87 | 261.67 | 269.17 | 1392.03 | 22.43 | 122.00 | 246.33 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-07:10 | 1979.47 | 18.29 | 10.67 | 322.17 | 1041.48 | 20.00 | 105.50 | 291.67 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:49 | 1239.36 | 17.73 | 0.00 | 336.00 | 769.39 | 19.91 | 69.67 | 295.17 |
May | 408.83 | 0.52 | 0.48 | 01-MAY-06:30 | 1010.19 | 17.46 | 0.00 | 360.67 | 621.84 | 19.64 | 34.83 | 321.67 |
June | 398.00 | 0.51 | 0.48 | 01-JUN-06:30 | 903.03 | 17.35 | 0.00 | 351.33 | 569.42 | 19.63 | 11.83 | 312.00 |
July | 400.17 | 0.52 | 0.48 | 01-JUL-06:30 | 963.89 | 17.38 | 0.00 | 358.83 | 585.76 | 19.60 | 29.17 | 301.50 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-06:30 | 1144.12 | 17.72 | 0.00 | 346.17 | 695.36 | 19.88 | 58.17 | 298.33 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-07:10 | 1472.73 | 18.09 | 11.00 | 318.33 | 876.71 | 19.82 | 82.00 | 281.50 |
October | 318.83 | 0.50 | 0.48 | 01-OCT-06:00 | 3594.03 | 24.78 | 131.00 | 311.50 | 1238.25 | 20.85 | 98.17 | 286.50 |
November | 295.83 | 0.50 | 0.48 | 01-NOV-12:39 | 8953.31 | 37.39 | 288.50 | 287.50 | 1556.03 | 24.73 | 129.17 | 274.00 |
December | 289.50 | 0.49 | 0.48 | 01-DEC-07:19 | 7951.39 | 37.77 | 284.17 | 276.00 | 1873.02 | 26.39 | 166.00 | 269.33 |
Annual Sum or Average | 4125.67 | 0.51 | 3478.90 | 23.71 | 1263.00 | 3816.83 | 1030.19 | 21.29 | 1063.17 | 3440.67 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 903.03 | 17.35 | 0.00 | 269.17 | 569.42 | 19.60 | 11.83 | 246.33 | |
Maximum of Months | 408.83 | 0.52 | 0.48 | 9446.72 | 38.51 | 288.50 | 360.67 | 1902.10 | 26.39 | 166.00 | 321.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.52 | 0.48 | 01-JAN-08:09 | 2397.89 | 22.29 | 92.50 | 246.83 | 1317.98 | 22.74 | 68.00 | 197.50 |
February | 268.33 | 0.51 | 0.48 | 01-FEB-07:40 | 2882.19 | 22.18 | 89.67 | 249.00 | 1076.14 | 20.91 | 41.00 | 209.00 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-06:00 | 2621.03 | 21.06 | 101.33 | 308.83 | 1409.93 | 21.83 | 71.17 | 273.50 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:10 | 3321.83 | 20.93 | 109.83 | 336.83 | 1279.27 | 20.20 | 50.83 | 307.33 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-05:49 | 2655.79 | 20.11 | 103.67 | 366.50 | 1465.55 | 21.27 | 72.67 | 334.67 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-05:49 | 2705.89 | 20.14 | 100.00 | 357.67 | 1501.26 | 21.34 | 70.00 | 326.17 |
July | 400.17 | 0.51 | 0.48 | 01-JUL-05:49 | 2394.68 | 19.99 | 99.33 | 365.83 | 1303.44 | 21.30 | 70.33 | 320.00 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-05:49 | 2999.62 | 20.63 | 109.67 | 348.33 | 1204.68 | 21.15 | 63.33 | 314.00 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-05:00 | 2889.53 | 21.38 | 114.50 | 319.00 | 1128.90 | 20.62 | 57.67 | 283.33 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-06:40 | 2501.99 | 20.89 | 89.83 | 288.33 | 1376.23 | 22.00 | 63.67 | 249.17 |
November | 295.83 | 0.52 | 0.48 | 01-NOV-12:39 | 2003.88 | 19.93 | 77.50 | 255.33 | 1104.16 | 21.90 | 61.83 | 209.33 |
December | 289.50 | 0.52 | 0.48 | 01-DEC-07:10 | 1812.91 | 21.10 | 81.33 | 249.17 | 939.45 | 21.52 | 60.33 | 210.67 |
Annual Sum or Average | 4125.67 | 0.51 | 2624.54 | 20.82 | 1169.17 | 3691.67 | 1272.94 | 21.36 | 750.83 | 3234.67 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 1812.91 | 19.93 | 77.50 | 246.83 | 939.45 | 20.20 | 41.00 | 197.50 | |
Maximum of Months | 408.83 | 0.52 | 0.48 | 3321.83 | 22.29 | 114.50 | 366.50 | 1501.26 | 22.74 | 72.67 | 334.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.54 | 0.48 | 01-JAN-08:00 | 503.81 | 14.65 | 0.00 | 224.83 | 336.29 | 17.33 | 0.00 | 131.33 |
February | 268.33 | 0.53 | 0.48 | 01-FEB-08:00 | 573.64 | 15.43 | 0.00 | 231.67 | 382.26 | 17.96 | 0.00 | 159.67 |
March | 351.83 | 0.52 | 0.48 | 01-MAR-07:49 | 675.88 | 16.31 | 0.00 | 301.67 | 434.97 | 18.60 | 0.00 | 236.33 |
April | 373.83 | 0.50 | 0.48 | 01-APR-06:30 | 801.75 | 17.54 | 0.00 | 349.33 | 513.66 | 19.70 | 4.50 | 308.50 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-05:00 | 988.64 | 18.30 | 3.00 | 385.00 | 575.20 | 20.35 | 75.67 | 359.33 |
June | 398.00 | 0.49 | 0.48 | 01-JUN-05:00 | 1061.67 | 21.40 | 84.33 | 381.33 | 603.82 | 20.68 | 84.83 | 357.83 |
July | 400.17 | 0.49 | 0.48 | 01-JUL-05:00 | 1006.54 | 19.68 | 37.50 | 390.00 | 577.79 | 20.54 | 77.17 | 346.83 |
August | 377.83 | 0.50 | 0.48 | 01-AUG-05:00 | 858.74 | 17.82 | 0.00 | 361.00 | 535.34 | 19.96 | 24.50 | 322.00 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-07:30 | 672.50 | 16.71 | 0.00 | 308.67 | 440.90 | 18.97 | 0.17 | 240.17 |
October | 318.83 | 0.52 | 0.48 | 01-OCT-07:30 | 603.13 | 15.78 | 0.00 | 278.17 | 398.55 | 18.21 | 0.00 | 205.83 |
November | 295.83 | 0.54 | 0.48 | 01-NOV-12:39 | 488.53 | 14.67 | 0.00 | 234.17 | 329.69 | 17.30 | 0.00 | 132.33 |
December | 289.50 | 0.54 | 0.48 | 01-DEC-08:30 | 504.20 | 14.63 | 0.00 | 227.17 | 330.73 | 17.27 | 0.00 | 135.17 |
Annual Sum or Average | 4125.67 | 0.51 | 754.72 | 17.17 | 124.83 | 3673.00 | 468.13 | 19.08 | 266.83 | 2935.33 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 488.53 | 14.63 | 0.00 | 224.83 | 329.69 | 17.27 | 0.00 | 131.33 | |
Maximum of Months | 408.83 | 0.54 | 0.48 | 1061.67 | 21.40 | 84.33 | 390.00 | 603.82 | 20.68 | 84.83 | 359.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.51 | 0.48 | 01-JAN-08:00 | 1962.10 | 21.17 | 81.83 | 258.50 | 1097.81 | 23.02 | 65.83 | 208.83 |
February | 268.33 | 0.50 | 0.48 | 01-FEB-08:00 | 2312.98 | 22.27 | 88.33 | 251.33 | 1255.44 | 22.83 | 61.33 | 209.83 |
March | 351.83 | 0.50 | 0.48 | 01-MAR-07:00 | 2921.47 | 21.51 | 111.33 | 320.33 | 1118.24 | 20.49 | 52.50 | 281.50 |
April | 373.83 | 0.50 | 0.48 | 01-APR-07:19 | 3246.84 | 20.93 | 111.83 | 342.33 | 1299.09 | 20.34 | 51.83 | 309.83 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-06:49 | 2551.24 | 13.78 | 0.00 | 374.50 | 1425.00 | 17.46 | 0.00 | 345.00 |
June | 398.00 | 0.49 | 0.48 | 01-JUN-06:30 | 2646.23 | 13.89 | 0.00 | 371.50 | 1460.86 | 17.59 | 0.00 | 337.50 |
July | 400.17 | 0.50 | 0.48 | 01-JUL-06:40 | 2367.05 | 14.23 | 3.67 | 378.83 | 1306.08 | 17.63 | 0.00 | 331.83 |
August | 377.83 | 0.50 | 0.48 | 01-AUG-06:49 | 2419.83 | 17.37 | 57.17 | 350.83 | 1263.92 | 17.71 | 3.67 | 311.00 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-07:40 | 2860.72 | 20.94 | 110.33 | 317.67 | 1136.87 | 20.50 | 56.17 | 280.50 |
October | 318.83 | 0.50 | 0.48 | 01-OCT-07:30 | 2417.72 | 20.60 | 86.17 | 298.83 | 1331.25 | 22.62 | 69.00 | 258.67 |
November | 295.83 | 0.51 | 0.48 | 01-NOV-12:39 | 1857.93 | 20.97 | 86.33 | 265.17 | 934.83 | 21.26 | 54.50 | 216.50 |
December | 289.50 | 0.51 | 0.48 | 01-DEC-08:30 | 2038.65 | 22.99 | 105.67 | 255.83 | 835.79 | 21.88 | 53.33 | 214.00 |
Annual Sum or Average | 4125.67 | 0.50 | 2501.52 | 18.84 | 842.67 | 3785.67 | 1222.33 | 20.00 | 468.17 | 3305.00 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 1857.93 | 13.78 | 0.00 | 251.33 | 835.79 | 17.46 | 0.00 | 208.83 | |
Maximum of Months | 408.83 | 0.51 | 0.48 | 3246.84 | 22.99 | 111.83 | 378.83 | 1460.86 | 23.02 | 69.00 | 345.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.49 | 0.48 | 01-JAN-08:09 | 8586.97 | 37.06 | 265.17 | 276.33 | 1770.19 | 23.88 | 97.17 | 261.50 |
February | 268.33 | 0.50 | 0.48 | 01-FEB-07:00 | 9310.46 | 36.61 | 261.50 | 268.17 | 1281.93 | 19.72 | 35.33 | 243.50 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-07:19 | 1884.79 | 14.50 | 10.67 | 318.67 | 967.75 | 17.54 | 2.17 | 288.50 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:00 | 1181.81 | 14.22 | 0.00 | 333.17 | 729.13 | 17.79 | 0.00 | 291.50 |
May | 408.83 | 0.52 | 0.48 | 01-MAY-06:30 | 971.92 | 14.11 | 0.00 | 357.83 | 598.85 | 17.63 | 0.00 | 316.33 |
June | 398.00 | 0.51 | 0.48 | 01-JUN-06:30 | 871.67 | 13.92 | 0.00 | 348.83 | 552.01 | 17.55 | 0.00 | 306.67 |
July | 400.17 | 0.52 | 0.48 | 01-JUL-06:30 | 928.19 | 13.96 | 0.00 | 355.17 | 564.87 | 17.52 | 0.00 | 295.67 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-06:30 | 1095.26 | 14.25 | 0.00 | 343.00 | 663.24 | 17.78 | 0.00 | 293.50 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-07:10 | 1398.12 | 14.48 | 11.00 | 316.33 | 820.34 | 17.56 | 0.00 | 278.33 |
October | 318.83 | 0.50 | 0.48 | 01-OCT-06:00 | 3476.85 | 22.13 | 131.00 | 310.83 | 1142.72 | 18.24 | 14.50 | 283.33 |
November | 295.83 | 0.50 | 0.48 | 01-NOV-12:39 | 8812.42 | 37.10 | 288.33 | 287.00 | 1438.19 | 22.23 | 90.17 | 273.50 |
December | 289.50 | 0.49 | 0.48 | 01-DEC-07:19 | 7791.94 | 37.52 | 284.00 | 275.17 | 1744.59 | 23.92 | 101.50 | 268.33 |
Annual Sum or Average | 4125.67 | 0.51 | 3391.63 | 21.08 | 1251.67 | 3790.50 | 965.47 | 19.00 | 340.83 | 3400.67 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 871.67 | 13.92 | 0.00 | 268.17 | 552.01 | 17.52 | 0.00 | 243.50 | |
Maximum of Months | 408.83 | 0.52 | 0.48 | 9310.46 | 37.52 | 288.33 | 357.83 | 1770.19 | 23.92 | 101.50 | 316.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.52 | 0.48 | 01-JAN-08:09 | 2345.58 | 21.81 | 92.50 | 243.50 | 1274.84 | 22.52 | 63.50 | 194.67 |
February | 268.33 | 0.51 | 0.48 | 01-FEB-07:40 | 2818.03 | 21.71 | 89.67 | 247.50 | 1026.25 | 20.70 | 41.00 | 207.17 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-06:00 | 2451.58 | 18.83 | 82.50 | 306.00 | 1353.26 | 21.65 | 71.17 | 271.67 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:10 | 3239.44 | 20.47 | 109.83 | 334.33 | 1214.84 | 20.02 | 50.83 | 304.67 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-05:49 | 2498.32 | 18.37 | 87.50 | 363.00 | 1405.13 | 21.10 | 72.67 | 331.67 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-05:49 | 2633.79 | 19.63 | 99.50 | 356.50 | 1440.01 | 21.17 | 70.00 | 324.17 |
July | 400.17 | 0.51 | 0.48 | 01-JUL-05:49 | 2270.08 | 18.30 | 84.17 | 362.67 | 1246.41 | 21.13 | 70.33 | 317.83 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-05:49 | 2920.26 | 20.17 | 109.67 | 346.33 | 1148.28 | 20.97 | 63.33 | 311.83 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-06:10 | 2824.64 | 20.92 | 114.50 | 315.50 | 1075.27 | 20.43 | 57.67 | 281.33 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-06:40 | 2440.20 | 20.41 | 89.83 | 286.67 | 1325.23 | 21.80 | 63.67 | 246.50 |
November | 295.83 | 0.52 | 0.48 | 01-NOV-12:39 | 1946.62 | 19.41 | 77.50 | 252.83 | 1058.50 | 21.69 | 61.00 | 205.00 |
December | 289.50 | 0.52 | 0.48 | 01-DEC-07:10 | 1760.37 | 20.61 | 81.33 | 246.67 | 898.57 | 21.29 | 51.33 | 205.67 |
Annual Sum or Average | 4125.67 | 0.51 | 2534.71 | 19.94 | 1118.50 | 3661.50 | 1218.70 | 21.17 | 736.50 | 3202.17 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 1760.37 | 18.30 | 77.50 | 243.50 | 898.57 | 20.02 | 41.00 | 194.67 | |
Maximum of Months | 408.83 | 0.52 | 0.48 | 3239.44 | 21.81 | 114.50 | 363.00 | 1440.01 | 22.52 | 72.67 | 331.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.54 | 0.48 | 01-JAN-08:00 | 485.65 | 11.04 | 0.00 | 220.00 | 327.21 | 14.99 | 0.00 | 121.33 |
February | 268.33 | 0.53 | 0.48 | 01-FEB-08:00 | 553.68 | 12.01 | 0.00 | 227.00 | 372.34 | 15.82 | 0.00 | 152.33 |
March | 351.83 | 0.52 | 0.48 | 01-MAR-07:00 | 653.94 | 12.96 | 0.00 | 298.00 | 423.85 | 16.60 | 0.00 | 230.17 |
April | 373.83 | 0.50 | 0.48 | 01-APR-06:30 | 775.50 | 14.34 | 0.00 | 348.50 | 500.21 | 17.94 | 0.00 | 303.67 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-06:10 | 956.15 | 14.91 | 3.00 | 383.83 | 557.46 | 18.43 | 1.83 | 357.50 |
June | 398.00 | 0.49 | 0.48 | 01-JUN-05:00 | 1026.97 | 18.58 | 83.17 | 380.50 | 586.06 | 18.60 | 2.00 | 354.00 |
July | 400.17 | 0.50 | 0.48 | 01-JUL-05:49 | 972.37 | 16.47 | 37.33 | 388.50 | 589.76 | 19.94 | 37.50 | 348.67 |
August | 377.83 | 0.50 | 0.48 | 01-AUG-05:00 | 829.53 | 14.51 | 0.00 | 359.17 | 519.89 | 18.11 | 0.00 | 316.50 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-07:30 | 650.06 | 13.49 | 0.00 | 305.83 | 429.66 | 17.13 | 0.00 | 235.17 |
October | 318.83 | 0.52 | 0.48 | 01-OCT-07:30 | 582.62 | 12.44 | 0.00 | 275.17 | 388.32 | 16.17 | 0.00 | 198.00 |
November | 295.83 | 0.54 | 0.48 | 01-NOV-12:39 | 471.44 | 11.10 | 0.00 | 226.67 | 321.29 | 15.03 | 0.00 | 124.33 |
December | 289.50 | 0.54 | 0.48 | 01-DEC-08:30 | 485.36 | 11.06 | 0.00 | 223.83 | 321.10 | 14.92 | 0.00 | 121.00 |
Annual Sum or Average | 4125.67 | 0.51 | 729.27 | 13.85 | 123.50 | 3637.00 | 457.92 | 17.18 | 41.33 | 2862.67 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 471.44 | 11.04 | 0.00 | 220.00 | 321.10 | 14.92 | 0.00 | 121.00 | |
Maximum of Months | 408.83 | 0.54 | 0.48 | 1026.97 | 18.58 | 83.17 | 388.50 | 589.76 | 19.94 | 37.50 | 357.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.51 | 0.48 | 01-JAN-08:00 | 1905.45 | 20.76 | 81.83 | 256.67 | 995.43 | 21.55 | 54.33 | 203.83 |
February | 268.33 | 0.51 | 0.48 | 01-FEB-08:00 | 2255.73 | 21.86 | 88.33 | 250.00 | 1210.76 | 22.71 | 61.33 | 208.33 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-07:00 | 2860.02 | 21.09 | 111.33 | 317.83 | 1066.47 | 20.36 | 52.67 | 279.67 |
April | 373.83 | 0.50 | 0.48 | 01-APR-07:30 | 3175.34 | 20.48 | 111.83 | 340.17 | 1240.95 | 20.18 | 51.83 | 306.33 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-06:49 | 2472.38 | 13.24 | 0.00 | 373.00 | 1368.22 | 17.27 | 0.00 | 341.67 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-06:40 | 2578.61 | 13.35 | 0.00 | 369.50 | 1405.99 | 17.39 | 0.00 | 335.17 |
July | 400.17 | 0.50 | 0.48 | 01-JUL-06:49 | 2301.18 | 13.68 | 3.67 | 376.83 | 1255.99 | 17.43 | 0.00 | 328.50 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-06:00 | 2346.39 | 16.87 | 57.17 | 349.00 | 1210.32 | 17.53 | 3.67 | 307.50 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-07:49 | 2796.47 | 20.50 | 110.17 | 314.83 | 1083.67 | 20.35 | 56.17 | 277.33 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-07:30 | 2351.16 | 20.17 | 86.17 | 297.17 | 1277.03 | 22.50 | 69.00 | 256.33 |
November | 295.83 | 0.51 | 0.48 | 01-NOV-12:39 | 1805.11 | 20.55 | 86.33 | 261.17 | 891.42 | 21.15 | 54.33 | 212.00 |
December | 289.50 | 0.51 | 0.48 | 01-DEC-08:30 | 1990.34 | 22.61 | 105.67 | 254.00 | 797.71 | 21.79 | 53.00 | 211.00 |
Annual Sum or Average | 4125.67 | 0.51 | 2436.80 | 18.38 | 842.50 | 3760.17 | 1167.49 | 19.76 | 456.33 | 3267.67 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 1805.11 | 13.24 | 0.00 | 250.00 | 797.71 | 17.27 | 0.00 | 203.83 | |
Maximum of Months | 408.83 | 0.51 | 0.48 | 3175.34 | 22.61 | 111.83 | 376.83 | 1405.99 | 22.71 | 69.00 | 341.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.49 | 0.48 | 01-JAN-08:09 | 8586.94 | 37.06 | 265.17 | 276.33 | 1770.11 | 23.89 | 97.17 | 261.50 |
February | 268.33 | 0.50 | 0.48 | 01-FEB-07:00 | 9310.39 | 36.61 | 261.50 | 268.17 | 1281.86 | 19.72 | 35.33 | 243.50 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-07:19 | 1884.72 | 14.51 | 10.67 | 318.67 | 967.69 | 17.54 | 2.17 | 288.50 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:00 | 1181.76 | 14.22 | 0.00 | 333.17 | 729.09 | 17.79 | 0.00 | 291.50 |
May | 408.83 | 0.52 | 0.48 | 01-MAY-06:30 | 971.88 | 14.11 | 0.00 | 357.83 | 598.81 | 17.63 | 0.00 | 316.33 |
June | 398.00 | 0.51 | 0.48 | 01-JUN-06:30 | 871.64 | 13.92 | 0.00 | 348.83 | 551.98 | 17.55 | 0.00 | 306.67 |
July | 400.17 | 0.52 | 0.48 | 01-JUL-06:30 | 928.15 | 13.96 | 0.00 | 355.17 | 564.83 | 17.52 | 0.00 | 295.50 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-06:30 | 1095.21 | 14.26 | 0.00 | 343.00 | 663.20 | 17.78 | 0.00 | 293.50 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-07:10 | 1398.07 | 14.48 | 11.00 | 316.33 | 820.29 | 17.56 | 0.00 | 278.33 |
October | 318.83 | 0.50 | 0.48 | 01-OCT-06:00 | 3476.79 | 22.13 | 131.00 | 310.83 | 1142.66 | 18.24 | 14.50 | 283.33 |
November | 295.83 | 0.50 | 0.48 | 01-NOV-12:39 | 8812.39 | 37.10 | 288.33 | 287.00 | 1438.13 | 22.23 | 90.17 | 273.50 |
December | 289.50 | 0.49 | 0.48 | 01-DEC-07:19 | 7791.92 | 37.52 | 284.00 | 275.17 | 1744.51 | 23.92 | 101.50 | 268.33 |
Annual Sum or Average | 4125.67 | 0.51 | 3391.58 | 21.08 | 1251.67 | 3790.50 | 965.42 | 19.00 | 340.83 | 3400.50 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 871.64 | 13.92 | 0.00 | 268.17 | 551.98 | 17.52 | 0.00 | 243.50 | |
Maximum of Months | 408.83 | 0.52 | 0.48 | 9310.39 | 37.52 | 288.33 | 357.83 | 1770.11 | 23.92 | 101.50 | 316.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.52 | 0.48 | 01-JAN-08:09 | 2345.57 | 21.81 | 92.50 | 243.50 | 1274.81 | 22.52 | 63.50 | 194.67 |
February | 268.33 | 0.51 | 0.48 | 01-FEB-07:40 | 2818.02 | 21.72 | 89.67 | 247.50 | 1026.21 | 20.70 | 41.00 | 207.17 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-06:00 | 2451.55 | 18.83 | 82.50 | 306.00 | 1353.21 | 21.65 | 71.17 | 271.67 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:10 | 3239.42 | 20.47 | 109.83 | 334.33 | 1214.79 | 20.02 | 50.83 | 304.67 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-05:49 | 2498.30 | 18.37 | 87.50 | 363.00 | 1405.09 | 21.10 | 72.67 | 331.67 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-05:49 | 2633.77 | 19.64 | 99.50 | 356.50 | 1439.97 | 21.17 | 70.00 | 324.17 |
July | 400.17 | 0.51 | 0.48 | 01-JUL-05:49 | 2270.05 | 18.30 | 84.17 | 362.67 | 1246.36 | 21.13 | 70.33 | 317.83 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-05:49 | 2920.23 | 20.17 | 109.67 | 346.33 | 1148.23 | 20.97 | 63.33 | 311.83 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-06:10 | 2824.62 | 20.92 | 114.50 | 315.50 | 1075.22 | 20.43 | 57.67 | 281.33 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-06:40 | 2440.18 | 20.41 | 89.83 | 286.67 | 1325.19 | 21.80 | 63.67 | 246.50 |
November | 295.83 | 0.52 | 0.48 | 01-NOV-12:39 | 1946.61 | 19.42 | 77.50 | 252.83 | 1058.47 | 21.69 | 61.00 | 205.00 |
December | 289.50 | 0.52 | 0.48 | 01-DEC-07:10 | 1760.36 | 20.61 | 81.33 | 246.67 | 898.53 | 21.29 | 51.33 | 205.67 |
Annual Sum or Average | 4125.67 | 0.51 | 2534.69 | 19.94 | 1118.50 | 3661.50 | 1218.66 | 21.17 | 736.50 | 3202.17 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 1760.36 | 18.30 | 77.50 | 243.50 | 898.53 | 20.02 | 41.00 | 194.67 | |
Maximum of Months | 408.83 | 0.52 | 0.48 | 3239.42 | 21.81 | 114.50 | 363.00 | 1439.97 | 22.52 | 72.67 | 331.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.54 | 0.48 | 01-JAN-08:00 | 485.65 | 11.05 | 0.00 | 220.00 | 327.19 | 14.99 | 0.00 | 121.33 |
February | 268.33 | 0.53 | 0.48 | 01-FEB-08:00 | 553.68 | 12.02 | 0.00 | 227.00 | 372.32 | 15.82 | 0.00 | 152.33 |
March | 351.83 | 0.52 | 0.48 | 01-MAR-07:00 | 653.93 | 12.96 | 0.00 | 298.00 | 423.83 | 16.60 | 0.00 | 230.17 |
April | 373.83 | 0.50 | 0.48 | 01-APR-06:30 | 775.48 | 14.34 | 0.00 | 348.50 | 500.19 | 17.94 | 0.00 | 303.67 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-06:10 | 956.13 | 14.91 | 3.00 | 383.83 | 557.43 | 18.43 | 1.83 | 357.50 |
June | 398.00 | 0.49 | 0.48 | 01-JUN-05:00 | 1026.94 | 18.58 | 83.17 | 380.50 | 586.03 | 18.60 | 2.00 | 354.00 |
July | 400.17 | 0.50 | 0.48 | 01-JUL-05:49 | 972.34 | 16.47 | 37.33 | 388.50 | 589.73 | 19.94 | 37.50 | 348.67 |
August | 377.83 | 0.50 | 0.48 | 01-AUG-05:00 | 829.51 | 14.51 | 0.00 | 359.17 | 519.86 | 18.11 | 0.00 | 316.50 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-07:30 | 650.05 | 13.49 | 0.00 | 305.83 | 429.64 | 17.13 | 0.00 | 235.17 |
October | 318.83 | 0.52 | 0.48 | 01-OCT-07:30 | 582.61 | 12.44 | 0.00 | 275.17 | 388.30 | 16.17 | 0.00 | 198.00 |
November | 295.83 | 0.54 | 0.48 | 01-NOV-12:39 | 471.44 | 11.10 | 0.00 | 226.67 | 321.28 | 15.03 | 0.00 | 124.33 |
December | 289.50 | 0.54 | 0.48 | 01-DEC-08:30 | 485.35 | 11.06 | 0.00 | 223.83 | 321.08 | 14.92 | 0.00 | 120.83 |
Annual Sum or Average | 4125.67 | 0.51 | 729.26 | 13.85 | 123.50 | 3637.00 | 457.89 | 17.18 | 41.33 | 2862.50 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 471.44 | 11.05 | 0.00 | 220.00 | 321.08 | 14.92 | 0.00 | 120.83 | |
Maximum of Months | 408.83 | 0.54 | 0.48 | 1026.94 | 18.58 | 83.17 | 388.50 | 589.73 | 19.94 | 37.50 | 357.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.51 | 0.48 | 01-JAN-08:00 | 1905.44 | 20.76 | 81.83 | 256.67 | 995.39 | 21.55 | 54.33 | 203.83 |
February | 268.33 | 0.51 | 0.48 | 01-FEB-08:00 | 2255.71 | 21.86 | 88.33 | 250.00 | 1210.72 | 22.71 | 61.33 | 208.33 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-07:00 | 2859.99 | 21.09 | 111.33 | 317.83 | 1066.43 | 20.36 | 52.67 | 279.67 |
April | 373.83 | 0.50 | 0.48 | 01-APR-07:30 | 3175.31 | 20.48 | 111.83 | 340.17 | 1240.91 | 20.18 | 51.83 | 306.33 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-06:49 | 2472.35 | 13.24 | 0.00 | 373.00 | 1368.17 | 17.27 | 0.00 | 341.67 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-06:40 | 2578.59 | 13.35 | 0.00 | 369.50 | 1405.95 | 17.40 | 0.00 | 335.17 |
July | 400.17 | 0.50 | 0.48 | 01-JUL-06:49 | 2301.15 | 13.68 | 3.67 | 376.83 | 1255.94 | 17.43 | 0.00 | 328.50 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-06:00 | 2346.36 | 16.87 | 57.17 | 349.00 | 1210.27 | 17.53 | 3.67 | 307.50 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-07:49 | 2796.45 | 20.50 | 110.17 | 314.83 | 1083.63 | 20.36 | 56.17 | 277.33 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-07:30 | 2351.14 | 20.17 | 86.17 | 297.17 | 1276.99 | 22.50 | 69.00 | 256.33 |
November | 295.83 | 0.51 | 0.48 | 01-NOV-12:39 | 1805.11 | 20.55 | 86.33 | 261.17 | 891.39 | 21.15 | 54.33 | 212.00 |
December | 289.50 | 0.51 | 0.48 | 01-DEC-08:30 | 1990.33 | 22.61 | 105.67 | 254.00 | 797.68 | 21.79 | 53.00 | 211.00 |
Annual Sum or Average | 4125.67 | 0.51 | 2436.78 | 18.38 | 842.50 | 3760.17 | 1167.45 | 19.76 | 456.33 | 3267.67 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 1805.11 | 13.24 | 0.00 | 250.00 | 797.68 | 17.27 | 0.00 | 203.83 | |
Maximum of Months | 408.83 | 0.51 | 0.48 | 3175.31 | 22.61 | 111.83 | 376.83 | 1405.95 | 22.71 | 69.00 | 341.67 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.101041E+10 | 10107.86 | 27-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.814530E+09 | 10283.35 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.889951E+09 | 9993.36 | 08-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.249937E+09 | 10113.20 | 11-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22046339.75 | 9859.58 | 02-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2365590.91 | 4328.13 | 25-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 94979574.93 | 10142.21 | 25-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.595998E+09 | 10180.73 | 03-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109192E+10 | 10334.08 | 27-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.477213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109192E+10 | 10334.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 79292555.31 | 7144.00 | 26-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30178228.14 | 7144.00 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18477446.45 | 7144.00 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2678490.10 | 4377.98 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 92267123.01 | 7144.00 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222894E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 92267123.01 | 7144.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.324657E+09 | 9057.11 | 27-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.229429E+09 | 9214.62 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113165E+09 | 8935.85 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20306614.25 | 8915.57 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.340971E+09 | 9261.24 | 27-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.340971E+09 | 9261.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 85940715.72 | 7086.72 | 26-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 61236686.21 | 7086.72 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22398555.50 | 7086.72 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4956561.49 | 5205.31 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106404E+09 | 7086.72 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106404E+09 | 7086.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3022304.62 | 9252.40 | 17-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8492733.20 | 17838.68 | 27-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 11515037.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8492733.20 | 17838.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.140420E+09 | 10706.65 | 27-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 50618794.74 | 10867.60 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19360332.98 | 10600.98 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 32490484.07 | 10635.90 | 27-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207287E+09 | 10666.53 | 27-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.450176E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.207287E+09 | 10867.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.148120E+09 | 7856.45 | 09-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 42616380.58 | 7856.45 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17128359.75 | 7856.45 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 32671659.31 | 7856.45 | 27-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220879E+09 | 7856.45 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.461415E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.220879E+09 | 7856.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.351536E+09 | 9566.25 | 24-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146700E+09 | 9687.32 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 47800460.37 | 9520.01 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 89199723.80 | 9549.43 | 30-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.544990E+09 | 9539.78 | 28-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.544990E+09 | 9687.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.179462E+09 | 7804.92 | 09-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 79505133.88 | 7804.92 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21265243.47 | 7804.92 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 45274572.58 | 7804.92 | 27-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.276161E+09 | 7804.92 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.601668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.276161E+09 | 7804.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.416959E+09 | 32425.19 | 17-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103828E+09 | 32399.70 | 03-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22194730.58 | 32106.43 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142490E+09 | 32524.01 | 29-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.721911E+09 | 32600.64 | 28-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.721911E+09 | 32600.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.637226E+09 | 12317.56 | 17-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.322527E+09 | 12287.75 | 16-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193034E+09 | 12170.82 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13682634.96 | 9814.02 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 711997.50 | 2298.08 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.239089E+09 | 12283.01 | 28-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.822075E+09 | 12307.10 | 05-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.822075E+09 | 12317.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.561329E+09 | 9820.67 | 24-JAN-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.229295E+09 | 9742.04 | 16-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114521E+09 | 9733.81 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1217035.62 | 2975.23 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 794608.03 | 3515.01 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183582E+09 | 9823.76 | 28-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.744286E+09 | 9816.07 | 14-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.744286E+09 | 9823.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.132458E+10 | 11161.92 | 17-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.689592E+09 | 11150.44 | 27-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.314939E+09 | 11094.35 | 29-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15062348.63 | 9686.42 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2602143.22 | 4824.05 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.483338E+09 | 11149.74 | 13-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175571E+10 | 11158.58 | 15-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.458582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.175571E+10 | 11161.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.718253E+09 | 9968.69 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.381528E+09 | 9968.69 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167363E+09 | 9968.69 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8973518.22 | 6324.54 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1094729.56 | 1890.85 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.270765E+09 | 9968.69 | 20-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.952604E+09 | 9968.69 | 01-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.250058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.952604E+09 | 9968.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.164108E+10 | 13137.09 | 27-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.999980E+09 | 13137.09 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.532930E+09 | 11429.90 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13508280.24 | 4833.30 | 12-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 249431.13 | 794.09 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1693206.31 | 2069.78 | 25-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.428254E+09 | 9013.96 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.255776E+10 | 13137.09 | 27-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.617545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.255776E+10 | 13137.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.240661E+10 | 14857.30 | 27-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154650E+10 | 14857.30 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.939101E+09 | 12287.98 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 89135980.30 | 5404.54 | 12-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 120227.55 | 406.97 | 02-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 590759.65 | 1084.47 | 30-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 27627582.60 | 3034.69 | 25-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.953464E+09 | 10343.89 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.334011E+10 | 14857.30 | 27-DEC-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.930326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.334011E+10 | 14857.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.283584E+10 | 14256.18 | 05-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.186763E+10 | 14256.18 | 02-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121117E+10 | 13749.72 | 02-MAR-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171135E+09 | 7272.88 | 12-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2259743.46 | 1268.16 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3619871.38 | 1990.66 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 71488832.71 | 4129.10 | 25-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123550E+10 | 12747.04 | 17-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379863E+10 | 14256.18 | 19-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.379863E+10 | 14256.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.411514E+10 | 0.406286E+10 | 25119.62 | 12-JAN-15:30 | 25119.62 | 0.00 |
February | 0.00 | 0.00 | 0.544566E+10 | 0.539890E+10 | 28204.64 | 21-FEB-16:20 | 28204.64 | 0.00 |
March | 0.00 | 0.00 | 0.106015E+11 | 0.105686E+11 | 34485.52 | 21-MAR-16:00 | 34485.52 | 0.00 |
April | 0.00 | 0.00 | 0.251599E+11 | 0.249609E+11 | 55003.83 | 21-APR-15:10 | 55003.83 | 0.00 |
May | 0.00 | 0.00 | 0.494511E+11 | 0.480179E+11 | 71946.11 | 30-MAY-06:03 | 71946.11 | 0.00 |
June | 0.00 | 0.00 | 0.678033E+11 | 0.651937E+11 | 86504.63 | 19-JUN-06:03 | 66853.42 | 0.00 |
July | 0.00 | 0.00 | 0.797576E+11 | 0.645328E+11 | 111618.40 | 20-JUL-15:05 | 40459.83 | 0.00 |
August | 0.00 | 0.00 | 0.744828E+11 | 0.640787E+11 | 105454.84 | 03-AUG-06:03 | 45790.41 | 0.00 |
September | 0.00 | 0.00 | 0.620070E+11 | 0.538133E+11 | 103200.02 | 22-SEP-06:03 | 39311.21 | 0.00 |
October | 0.00 | 0.00 | 0.322371E+11 | 0.287023E+11 | 74801.79 | 04-OCT-10:40 | 46575.66 | 0.00 |
November | 0.00 | 0.00 | 0.931457E+10 | 0.913364E+10 | 41072.08 | 03-NOV-16:00 | 41072.08 | 0.00 |
December | 0.00 | 0.00 | 0.310630E+10 | 0.307740E+10 | 18891.01 | 07-DEC-15:40 | 18891.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.423482E+12 | 0.381541E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.310630E+10 | 0.307740E+10 | 18891.01 | 18891.01 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.797576E+11 | 0.651937E+11 | 111618.40 | 71946.11 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.677606E+09 | 0.664293E+09 | 13272.55 | 12-JAN-15:05 | 13272.55 | 0.00 |
February | 0.00 | 0.00 | 0.284794E+10 | 0.282419E+10 | 24667.72 | 21-FEB-15:05 | 24667.72 | 0.00 |
March | 0.00 | 0.00 | 0.730168E+10 | 0.727317E+10 | 32047.24 | 22-MAR-14:05 | 32047.24 | 0.00 |
April | 0.00 | 0.00 | 0.233293E+11 | 0.231710E+11 | 53794.32 | 21-APR-14:05 | 53794.32 | 0.00 |
May | 0.00 | 0.00 | 0.450016E+11 | 0.439058E+11 | 69830.95 | 30-MAY-06:03 | 69830.95 | 0.00 |
June | 0.00 | 0.00 | 0.619788E+11 | 0.599519E+11 | 78212.97 | 19-JUN-06:03 | 60727.59 | 0.00 |
July | 0.00 | 0.00 | 0.698032E+11 | 0.572930E+11 | 100080.19 | 20-JUL-15:05 | 36281.53 | 0.00 |
August | 0.00 | 0.00 | 0.621451E+11 | 0.543702E+11 | 94553.77 | 03-AUG-06:03 | 40486.70 | 0.00 |
September | 0.00 | 0.00 | 0.499225E+11 | 0.438874E+11 | 76829.70 | 22-SEP-06:03 | 29270.85 | 0.00 |
October | 0.00 | 0.00 | 0.253169E+11 | 0.225832E+11 | 64519.52 | 03-OCT-14:05 | 56174.52 | 0.00 |
November | 0.00 | 0.00 | 0.560973E+10 | 0.543236E+10 | 34818.96 | 09-NOV-15:05 | 34818.96 | 0.00 |
December | 0.00 | 0.00 | 0.242856E+09 | 0.240362E+09 | 5110.46 | 08-DEC-14:00 | 5110.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.354177E+12 | 0.321597E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.242856E+09 | 0.240362E+09 | 5110.46 | 5110.46 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.698032E+11 | 0.599519E+11 | 100080.19 | 69830.95 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.629637E+09 | 0.602888E+09 | 11318.16 | 12-JAN-15:00 | 11318.16 | 0.00 |
February | 0.00 | 0.00 | 0.275336E+10 | 0.270903E+10 | 25644.33 | 20-FEB-15:32 | 25644.33 | 0.00 |
March | 0.00 | 0.00 | 0.729517E+10 | 0.722390E+10 | 34303.52 | 21-MAR-16:00 | 34303.52 | 0.00 |
April | 0.00 | 0.00 | 0.255305E+11 | 0.252741E+11 | 62095.60 | 21-APR-14:40 | 62095.60 | 0.00 |
May | 0.00 | 0.00 | 0.496514E+11 | 0.482308E+11 | 75698.16 | 30-MAY-14:50 | 75698.16 | 0.00 |
June | 0.00 | 0.00 | 0.693618E+11 | 0.669172E+11 | 79737.34 | 19-JUN-14:30 | 77136.01 | 0.00 |
July | 0.00 | 0.00 | 0.769163E+11 | 0.636489E+11 | 114949.13 | 20-JUL-14:55 | 40230.29 | 0.00 |
August | 0.00 | 0.00 | 0.678949E+11 | 0.594221E+11 | 91999.40 | 05-AUG-06:03 | 55360.38 | 0.00 |
September | 0.00 | 0.00 | 0.537165E+11 | 0.472555E+11 | 82984.52 | 14-SEP-10:00 | 41749.22 | 0.00 |
October | 0.00 | 0.00 | 0.259998E+11 | 0.229579E+11 | 71804.37 | 03-OCT-14:00 | 63455.39 | 0.00 |
November | 0.00 | 0.00 | 0.506382E+10 | 0.483058E+10 | 34105.14 | 09-NOV-15:00 | 34105.14 | 0.00 |
December | 0.00 | 0.00 | 0.216164E+09 | 0.207497E+09 | 4892.71 | 20-DEC-15:00 | 4892.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.385029E+12 | 0.349280E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.216164E+09 | 0.207497E+09 | 4892.71 | 4892.71 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.769163E+11 | 0.669172E+11 | 114949.13 | 77136.01 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1698.36 | 5907.61 | 27-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1707.15 | 5907.91 | 01-FEB-12:06 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1756.94 | 5785.76 | 02-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1541.84 | 5431.48 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1479.61 | 5059.57 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1408.04 | 4643.31 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1236.90 | 4350.86 | 03-JUL-11:15 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1358.10 | 4377.62 | 31-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1330.37 | 4644.30 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1429.61 | 5076.84 | 31-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1566.49 | 5482.41 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1599.39 | 5781.89 | 28-DEC-12:06 |
Annual Sum or Average | 0.00 | 1508.30 | ||||
Minimum of Months | 0.00 | 0.00 | 1236.90 | 4350.86 | ||
Maximum of Months | 0.00 | 0.00 | 1756.94 | 5907.91 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.166654E+10 | 0.35 | 2714.72 | 12-JAN-15:30 | 0.84 |
February | 0.167464E+10 | 0.37 | 3467.87 | 21-FEB-16:30 | 0.97 |
March | 0.221888E+10 | 0.39 | 3828.86 | 16-MAR-15:30 | 1.02 |
April | 0.322861E+10 | 0.45 | 6577.29 | 21-APR-15:10 | 1.41 |
May | 0.513870E+10 | 0.57 | 9850.52 | 30-MAY-15:10 | 1.80 |
June | 0.664320E+10 | 0.67 | 11516.45 | 05-JUN-12:07 | 1.99 |
July | 0.655606E+10 | 0.65 | 11964.62 | 03-JUL-06:03 | 2.05 |
August | 0.660924E+10 | 0.66 | 11964.62 | 03-AUG-06:03 | 2.03 |
September | 0.542491E+10 | 0.59 | 11964.62 | 18-SEP-06:03 | 2.04 |
October | 0.408029E+10 | 0.50 | 10831.76 | 02-OCT-06:03 | 1.91 |
November | 0.253437E+10 | 0.40 | 5478.25 | 09-NOV-16:50 | 1.26 |
December | 0.162491E+10 | 0.35 | 2362.66 | 15-DEC-16:10 | 0.79 |
Annual Sum or Average | 0.474003E+11 | 0.50 | |||
Minimum of Months | 0.162491E+10 | 0.35 | 2362.66 | 0.79 | |
Maximum of Months | 0.664320E+10 | 0.67 | 11964.62 | 2.05 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.123656E+10 | 0.34 | 2026.22 | 12-JAN-15:50 | 0.78 |
February | 0.126900E+10 | 0.36 | 2908.67 | 21-FEB-16:30 | 0.95 |
March | 0.180678E+10 | 0.40 | 4382.12 | 16-MAR-15:30 | 1.20 |
April | 0.291329E+10 | 0.46 | 7124.47 | 21-APR-14:40 | 1.61 |
May | 0.469448E+10 | 0.57 | 10494.18 | 30-MAY-14:20 | 2.05 |
June | 0.619667E+10 | 0.68 | 10564.88 | 19-JUN-05:12 | 2.05 |
July | 0.585178E+10 | 0.65 | 10564.88 | 03-JUL-06:03 | 2.06 |
August | 0.574799E+10 | 0.64 | 10564.88 | 07-AUG-04:02 | 2.05 |
September | 0.440502E+10 | 0.55 | 9158.62 | 05-SEP-10:10 | 1.87 |
October | 0.289749E+10 | 0.45 | 9653.71 | 02-OCT-04:02 | 1.94 |
November | 0.164186E+10 | 0.37 | 4468.44 | 09-NOV-16:10 | 1.21 |
December | 0.118727E+10 | 0.34 | 1680.89 | 27-DEC-07:01 | 0.71 |
Annual Sum or Average | 0.398482E+11 | 0.49 | |||
Minimum of Months | 0.118727E+10 | 0.34 | 1680.89 | 0.71 | |
Maximum of Months | 0.619667E+10 | 0.68 | 10564.88 | 2.06 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.131761E+10 | 0.38 | 2489.54 | 09-JAN-06:11 | 0.79 |
February | 0.130720E+10 | 0.40 | 2489.54 | 02-FEB-07:01 | 0.79 |
March | 0.175741E+10 | 0.42 | 4048.93 | 16-MAR-15:30 | 1.04 |
April | 0.275048E+10 | 0.45 | 6948.62 | 21-APR-14:40 | 1.42 |
May | 0.444893E+10 | 0.53 | 10254.34 | 30-MAY-14:50 | 1.81 |
June | 0.608771E+10 | 0.63 | 11585.05 | 19-JUN-05:12 | 1.95 |
July | 0.570687E+10 | 0.60 | 12408.49 | 20-JUL-14:55 | 2.02 |
August | 0.549633E+10 | 0.59 | 10573.71 | 07-AUG-14:50 | 1.84 |
September | 0.417510E+10 | 0.51 | 8383.30 | 05-SEP-15:20 | 1.59 |
October | 0.264015E+10 | 0.43 | 8298.51 | 02-OCT-04:02 | 1.58 |
November | 0.157408E+10 | 0.40 | 3857.95 | 09-NOV-15:50 | 1.00 |
December | 0.129739E+10 | 0.38 | 2489.54 | 04-DEC-06:01 | 0.79 |
Annual Sum or Average | 0.385592E+11 | 0.48 | |||
Minimum of Months | 0.129739E+10 | 0.38 | 2489.54 | 0.79 | |
Maximum of Months | 0.608771E+10 | 0.63 | 12408.49 | 2.02 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 56.65 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 55.86 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 56.81 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 56.18 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 56.64 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:05 | 2.06 | 2.06 | 56.99 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 57.04 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:05 | 2.06 | 2.06 | 56.46 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.08 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.73 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 56.57 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:05 | 2.06 | 2.06 | 55.69 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 55.69 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.73 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 57.05 | 57.05 | 1698.36 | 5907.61 | 27-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.19 | 56.19 | 1707.15 | 5907.91 | 01-FEB-12:06 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.17 | 57.17 | 1756.94 | 5785.76 | 02-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.67 | 56.67 | 1541.84 | 5431.48 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.92 | 56.92 | 1479.61 | 5059.57 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.29 | 57.29 | 1408.04 | 4643.31 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.02 | 58.02 | 1236.90 | 4350.86 | 03-JUL-11:15 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.89 | 56.89 | 1358.10 | 4377.62 | 31-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.33 | 57.33 | 1330.37 | 4644.30 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.17 | 57.17 | 1429.61 | 5076.84 | 31-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.72 | 57.72 | 1566.49 | 5482.41 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.33 | 56.33 | 1599.39 | 5781.89 | 28-DEC-12:06 |
Annual Sum or Average | 0.00 | 1508.30 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.19 | 56.19 | 1236.90 | 4350.86 | ||
Maximum of Months | 0.00 | 0.00 | 58.02 | 58.02 | 1756.94 | 5907.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.426586E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.425949E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.599109E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.993573E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.180934E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.258216E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.280272E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.262717E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.213110E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.121417E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.551286E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.409715E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.165729E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.409715E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.280272E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.224682E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.234236E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.379394E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.890828E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.164776E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.237460E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.246409E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.222382E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.172764E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.921020E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.328252E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.251489E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.136678E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.224682E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.246409E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.515281E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.377547E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.447342E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.939614E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.175500E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.258820E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.265742E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.236821E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.181483E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.920509E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.421755E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.635638E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.154413E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.377547E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.265742E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.166654E+10 | 0.411514E+10 | 0.314138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167464E+10 | 0.544566E+10 | 0.213535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.221888E+10 | 0.106015E+11 | 0.157692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.322861E+10 | 0.251599E+11 | 0.263445E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.513870E+10 | 0.494511E+11 | 22046339.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.664320E+10 | 0.678033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.655606E+10 | 0.797576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.660924E+10 | 0.744828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.542491E+10 | 0.620070E+11 | 2615022.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.408029E+10 | 0.322371E+11 | 96672781.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.253437E+10 | 0.931457E+10 | 0.105219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162491E+10 | 0.310630E+10 | 0.418931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.474003E+11 | 0.423482E+12 | 0.124799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.162491E+10 | 0.310630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.664320E+10 | 0.797576E+11 | 0.418931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.123656E+10 | 0.677606E+09 | 0.322918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126900E+10 | 0.284794E+10 | 0.186594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180678E+10 | 0.730168E+10 | 0.104466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.291329E+10 | 0.233293E+11 | 89135980.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.469448E+10 | 0.450016E+11 | 120227.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.619667E+10 | 0.619788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.585178E+10 | 0.698032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.574799E+10 | 0.621451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.440502E+10 | 0.499225E+11 | 590759.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.289749E+10 | 0.253169E+11 | 27627582.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164186E+10 | 0.560973E+10 | 0.115310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118727E+10 | 0.242856E+09 | 0.459792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.398482E+11 | 0.354177E+12 | 0.120083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118727E+10 | 0.242856E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.619667E+10 | 0.698032E+11 | 0.459792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.131761E+10 | 0.629637E+09 | 0.649418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130720E+10 | 0.275336E+10 | 0.359440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175741E+10 | 0.729517E+10 | 0.202322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.275048E+10 | 0.255305E+11 | 0.210071E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.444893E+10 | 0.496514E+11 | 2259743.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.608771E+10 | 0.693618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.570687E+10 | 0.769163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.549633E+10 | 0.678949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.417510E+10 | 0.537165E+11 | 3619871.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.264015E+10 | 0.259998E+11 | 76692311.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157408E+10 | 0.506382E+10 | 0.255476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129739E+10 | 0.216164E+09 | 0.879521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.385592E+11 | 0.385029E+12 | 0.237544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129739E+10 | 0.216164E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.608771E+10 | 0.769163E+11 | 0.879521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.166654E+10 | 0.00 | 0.00 | 0.00 | 0.109902E+10 | 0.150030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167464E+10 | 0.00 | 0.00 | 0.00 | 0.144948E+10 | 0.113537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.221888E+10 | 0.00 | 0.00 | 0.00 | 0.272822E+10 | 0.104399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.322861E+10 | 0.00 | 0.00 | 0.00 | 0.645719E+10 | 0.249937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.513870E+10 | 0.00 | 0.00 | 0.00 | 0.129327E+11 | 22046339.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.664320E+10 | 0.00 | 0.00 | 0.00 | 0.191784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.655606E+10 | 0.00 | 0.00 | 0.00 | 0.214711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.660924E+10 | 0.00 | 0.00 | 0.00 | 0.196624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.542491E+10 | 0.00 | 0.00 | 0.00 | 0.158838E+11 | 2365590.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.408029E+10 | 0.00 | 0.00 | 0.00 | 0.796640E+10 | 94979574.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.253437E+10 | 0.00 | 0.00 | 0.00 | 0.235455E+10 | 0.623939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162491E+10 | 0.00 | 0.00 | 0.00 | 0.840676E+09 | 0.163156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.474003E+11 | 0.00 | 0.00 | 0.00 | 0.112024E+12 | 0.630449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.162491E+10 | 0.00 | 0.00 | 0.00 | 0.840676E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.664320E+10 | 0.00 | 0.00 | 0.00 | 0.214711E+11 | 0.163156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.123656E+10 | 0.00 | 0.00 | 0.00 | 0.187708E+09 | 0.822561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126900E+10 | 0.00 | 0.00 | 0.00 | 0.753916E+09 | 0.319440E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180678E+10 | 0.00 | 0.00 | 0.00 | 0.188160E+10 | 0.105554E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.291329E+10 | 0.00 | 0.00 | 0.00 | 0.599499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.469448E+10 | 0.00 | 0.00 | 0.00 | 0.117831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.619667E+10 | 0.00 | 0.00 | 0.00 | 0.175493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.585178E+10 | 0.00 | 0.00 | 0.00 | 0.187892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.574799E+10 | 0.00 | 0.00 | 0.00 | 0.164902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.440502E+10 | 0.00 | 0.00 | 0.00 | 0.128714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.289749E+10 | 0.00 | 0.00 | 0.00 | 0.631271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164186E+10 | 0.00 | 0.00 | 0.00 | 0.144103E+10 | 0.199636E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118727E+10 | 0.00 | 0.00 | 0.00 | 69804291.35 | 0.125781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.398482E+11 | 0.00 | 0.00 | 0.00 | 0.941248E+11 | 0.270500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118727E+10 | 0.00 | 0.00 | 0.00 | 69804291.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.619667E+10 | 0.00 | 0.00 | 0.00 | 0.187892E+11 | 0.125781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.131761E+10 | 0.00 | 0.00 | 0.00 | 0.176845E+09 | 0.365835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130720E+10 | 0.00 | 0.00 | 0.00 | 0.741501E+09 | 0.172677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175741E+10 | 0.00 | 0.00 | 0.00 | 0.190396E+10 | 0.812053E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.275048E+10 | 0.00 | 0.00 | 0.00 | 0.660672E+10 | 38935537.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.444893E+10 | 0.00 | 0.00 | 0.00 | 0.131011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.608771E+10 | 0.00 | 0.00 | 0.00 | 0.197943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.570687E+10 | 0.00 | 0.00 | 0.00 | 0.208674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.549633E+10 | 0.00 | 0.00 | 0.00 | 0.181857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.417510E+10 | 0.00 | 0.00 | 0.00 | 0.139732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.264015E+10 | 0.00 | 0.00 | 0.00 | 0.655973E+10 | 5203478.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157408E+10 | 0.00 | 0.00 | 0.00 | 0.132420E+10 | 0.131926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129739E+10 | 0.00 | 0.00 | 0.00 | 62407837.45 | 0.499658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.385592E+11 | 0.00 | 0.00 | 0.00 | 0.103297E+12 | 0.125572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129739E+10 | 0.00 | 0.00 | 0.00 | 62407837.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.608771E+10 | 0.00 | 0.00 | 0.00 | 0.208674E+11 | 0.499658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.977360E+09 | 0.00 | 0.00 | 31213141.10 | 0.00 | 0.00 | 0.137725E+11 | 0.00 | 0.46 |
February | 0.658645E+09 | 0.00 | 0.00 | 32426933.76 | 0.00 | 0.00 | 0.134564E+11 | 0.00 | 0.62 |
March | 0.618741E+09 | 0.00 | 0.00 | 39784464.99 | 0.00 | 0.00 | 0.152195E+11 | 0.00 | 0.78 |
April | 0.421492E+09 | 0.165195E+09 | 0.00 | 36914798.81 | 14128023.27 | 0.00 | 0.108194E+11 | 0.00 | 0.86 |
May | 0.287688E+09 | 0.668428E+09 | 0.00 | 26307486.58 | 63438034.78 | 0.00 | 0.470938E+10 | 0.00 | 0.72 |
June | 0.124240E+09 | 0.200576E+10 | 0.00 | 12995954.15 | 67779025.19 | 0.00 | 0.102540E+10 | 0.00 | 0.52 |
July | 6868823.38 | 0.681738E+10 | 0.00 | 822338.88 | 0.290008E+09 | 0.00 | 48398883.89 | 0.00 | 0.48 |
August | 68405812.34 | 0.324030E+10 | 0.00 | 11066192.99 | 0.133582E+09 | 0.00 | 0.112670E+10 | 0.00 | 0.67 |
September | 0.238674E+09 | 0.217144E+10 | 0.00 | 19089100.80 | 0.170935E+09 | 0.00 | 0.265440E+10 | 0.00 | 0.68 |
October | 0.459584E+09 | 0.526814E+09 | 0.00 | 39353328.16 | 48498842.02 | 0.00 | 0.126468E+11 | 0.00 | 1.04 |
November | 0.103075E+10 | 0.00 | 0.00 | 38740486.45 | 0.00 | 0.00 | 0.163205E+11 | 0.00 | 0.83 |
December | 0.141725E+10 | 0.00 | 0.00 | 31380084.28 | 0.00 | 0.00 | 0.141666E+11 | 0.00 | 0.46 |
Annual Sum or Average | 0.630970E+10 | 0.155953E+11 | 0.00 | 0.320094E+09 | 0.788369E+09 | 0.00 | 0.105966E+12 | 0.00 | 0.68 |
Minimum of Months | 6868823.38 | 0.00 | 0.00 | 822338.88 | 0.00 | 0.00 | 48398883.89 | 0.00 | 0.46 |
Maximum of Months | 0.141725E+10 | 0.681738E+10 | 0.00 | 39784464.99 | 0.290008E+09 | 0.00 | 0.163205E+11 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.674595E+10 | 0.00 | 0.00 | 4510817.49 | 0.00 | 938079.87 | 0.357826E+10 | 0.00 | 0.34 |
February | 0.428367E+10 | 0.00 | 0.00 | 8242848.31 | 0.00 | 0.00 | 0.519444E+10 | 0.00 | 0.42 |
March | 0.317546E+10 | 0.00 | 0.00 | 15339652.81 | 0.00 | 0.00 | 0.772294E+10 | 0.00 | 0.54 |
April | 0.990308E+09 | 89272263.04 | 0.00 | 21477633.14 | 33220882.18 | 0.00 | 0.634926E+10 | 0.00 | 0.57 |
May | 0.524364E+09 | 0.441997E+09 | 0.00 | 18409016.41 | 64266501.47 | 0.00 | 0.305496E+10 | 0.00 | 0.51 |
June | 0.164322E+09 | 0.149473E+10 | 0.00 | 10607530.69 | 66237810.06 | 0.00 | 0.787432E+09 | 0.00 | 0.41 |
July | 10542512.81 | 0.488784E+10 | 0.00 | 938967.95 | 0.276733E+09 | 0.00 | 50518433.60 | 0.00 | 0.39 |
August | 0.101356E+09 | 0.219072E+10 | 0.00 | 9420685.38 | 0.113600E+09 | 0.00 | 0.847129E+09 | 0.00 | 0.51 |
September | 0.301495E+09 | 0.139754E+10 | 0.00 | 13335329.77 | 0.129990E+09 | 0.00 | 0.169279E+10 | 0.00 | 0.49 |
October | 0.863877E+09 | 0.341192E+09 | 0.00 | 21937491.23 | 37377109.13 | 0.00 | 0.718099E+10 | 0.00 | 0.66 |
November | 0.384779E+10 | 0.00 | 0.00 | 13036156.19 | 0.00 | 0.00 | 0.661942E+10 | 0.00 | 0.50 |
December | 0.756302E+10 | 0.00 | 0.00 | 3482312.31 | 0.00 | 2234776.58 | 0.303864E+10 | 0.00 | 0.32 |
Annual Sum or Average | 0.285722E+11 | 0.108433E+11 | 0.00 | 0.140738E+09 | 0.721426E+09 | 3172856.46 | 0.461168E+11 | 0.00 | 0.47 |
Minimum of Months | 10542512.81 | 0.00 | 0.00 | 938967.95 | 0.00 | 0.00 | 50518433.60 | 0.00 | 0.32 |
Maximum of Months | 0.756302E+10 | 0.488784E+10 | 0.00 | 21937491.23 | 0.276733E+09 | 2234776.58 | 0.772294E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.765987E+10 | 0.00 | 0.00 | 1438261.95 | 0.00 | 0.264810E+09 | 0.145644E+10 | 0.00 | 0.32 |
February | 0.572652E+10 | 0.00 | 0.00 | 4092005.60 | 0.00 | 79879083.27 | 0.281080E+10 | 0.00 | 0.39 |
March | 0.436292E+10 | 0.00 | 0.00 | 10354771.95 | 0.00 | 13297377.92 | 0.558576E+10 | 0.00 | 0.51 |
April | 0.134459E+10 | 55843612.31 | 0.00 | 19363219.76 | 13693263.76 | 0.00 | 0.531542E+10 | 0.00 | 0.57 |
May | 0.599824E+09 | 0.376680E+09 | 0.00 | 17773940.95 | 87662657.04 | 0.00 | 0.250276E+10 | 0.00 | 0.52 |
June | 0.151926E+09 | 0.138034E+10 | 0.00 | 10513436.34 | 77958549.30 | 0.00 | 0.571855E+09 | 0.00 | 0.40 |
July | 8037087.41 | 0.484061E+10 | 0.00 | 959610.79 | 0.431622E+09 | 0.00 | 24859008.81 | 0.00 | 0.38 |
August | 90238151.47 | 0.221226E+10 | 0.00 | 8926628.78 | 0.157573E+09 | 0.00 | 0.577233E+09 | 0.00 | 0.49 |
September | 0.360844E+09 | 0.140885E+10 | 0.00 | 11072804.34 | 0.220431E+09 | 0.00 | 0.110197E+10 | 0.00 | 0.47 |
October | 0.149674E+10 | 0.356659E+09 | 0.00 | 15740790.28 | 43293111.91 | 0.00 | 0.520819E+10 | 0.00 | 0.61 |
November | 0.492816E+10 | 0.00 | 0.00 | 7447185.45 | 0.00 | 66342496.88 | 0.414977E+10 | 0.00 | 0.45 |
December | 0.830396E+10 | 0.00 | 0.00 | 816555.33 | 0.00 | 0.412010E+09 | 0.892982E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.350336E+11 | 0.106312E+11 | 0.00 | 0.108499E+09 | 0.103223E+10 | 0.836340E+09 | 0.301980E+11 | 0.00 | 0.45 |
Minimum of Months | 8037087.41 | 0.00 | 0.00 | 816555.33 | 0.00 | 0.00 | 24859008.81 | 0.00 | 0.31 |
Maximum of Months | 0.830396E+10 | 0.484061E+10 | 0.00 | 19363219.76 | 0.431622E+09 | 0.412010E+09 | 0.558576E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126742E+10 | 0.00 | 0.00 | 12413.69 | 0.00 | 0.730856E+09 | 20236355.07 | 0.00 | 0.32 |
February | 0.127841E+10 | 0.00 | 0.00 | 220313.32 | 0.00 | 0.362379E+09 | 0.127106E+09 | 0.00 | 0.38 |
March | 0.122776E+10 | 0.00 | 0.00 | 1191551.36 | 0.00 | 0.192377E+09 | 0.550106E+09 | 0.00 | 0.49 |
April | 0.504323E+09 | 19921629.85 | 0.00 | 3858958.42 | 1598521.54 | 11071003.29 | 0.792340E+09 | 0.00 | 0.58 |
May | 0.159413E+09 | 0.125558E+09 | 0.00 | 4449933.73 | 18804053.56 | 0.00 | 0.511778E+09 | 0.00 | 0.63 |
June | 39432413.88 | 0.501811E+09 | 0.00 | 2970211.77 | 14496473.73 | 0.00 | 0.138511E+09 | 0.00 | 0.58 |
July | 2396727.15 | 0.150668E+10 | 0.00 | 244867.62 | 86757925.67 | 0.00 | 4712126.71 | 0.00 | 0.53 |
August | 27801232.07 | 0.634332E+09 | 0.00 | 2150787.03 | 35088262.22 | 0.00 | 0.119009E+09 | 0.00 | 0.60 |
September | 0.101964E+09 | 0.361503E+09 | 0.00 | 2395061.77 | 50489180.40 | 0.00 | 0.192383E+09 | 0.00 | 0.51 |
October | 0.568388E+09 | 89976507.19 | 0.00 | 2398799.19 | 9708682.89 | 1159463.83 | 0.667590E+09 | 0.00 | 0.58 |
November | 0.126001E+10 | 0.00 | 0.00 | 537971.41 | 0.00 | 0.252115E+09 | 0.269839E+09 | 0.00 | 0.41 |
December | 0.111504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.996541E+09 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.755236E+10 | 0.323978E+10 | 0.00 | 20430869.30 | 0.216943E+09 | 0.254650E+10 | 0.339361E+10 | 0.00 | 0.49 |
Minimum of Months | 2396727.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.127841E+10 | 0.150668E+10 | 0.00 | 4449933.73 | 86757925.67 | 0.996541E+09 | 0.792340E+09 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.861921E+09 | 0.00 | 0.00 | 190725.72 | 0.00 | 0.263704E+09 | 0.157824E+09 | 0.00 | 0.33 |
February | 0.641551E+09 | 0.00 | 0.00 | 947414.81 | 0.00 | 91152026.37 | 0.556955E+09 | 0.00 | 0.45 |
March | 0.527973E+09 | 0.00 | 0.00 | 2961104.07 | 0.00 | 61672205.16 | 0.139135E+10 | 0.00 | 0.77 |
April | 0.162855E+09 | 17847395.56 | 0.00 | 6247258.72 | 968252.40 | 387824.91 | 0.159664E+10 | 0.00 | 1.16 |
May | 56938393.78 | 0.120557E+09 | 0.00 | 6177524.84 | 8022430.00 | 0.00 | 0.916920E+09 | 0.00 | 1.21 |
June | 20576128.65 | 0.418614E+09 | 0.00 | 3359693.79 | 6864534.99 | 0.00 | 0.171314E+09 | 0.00 | 0.91 |
July | 919024.63 | 0.142801E+10 | 0.00 | 241303.13 | 35867940.05 | 0.00 | 5707341.44 | 0.00 | 0.80 |
August | 13781965.33 | 0.656654E+09 | 0.00 | 2184279.15 | 13260584.38 | 0.00 | 0.132033E+09 | 0.00 | 0.96 |
September | 47110372.63 | 0.470615E+09 | 0.00 | 3112372.22 | 17244494.95 | 0.00 | 0.333371E+09 | 0.00 | 1.00 |
October | 0.252377E+09 | 76273535.96 | 0.00 | 3541294.44 | 4983639.64 | 354742.45 | 0.112000E+10 | 0.00 | 0.95 |
November | 0.587857E+09 | 0.00 | 0.00 | 1535952.22 | 0.00 | 94627699.09 | 0.723928E+09 | 0.00 | 0.54 |
December | 0.890042E+09 | 0.00 | 0.00 | 20386.35 | 0.00 | 0.374290E+09 | 48801246.04 | 0.00 | 0.31 |
Annual Sum or Average | 0.406390E+10 | 0.318858E+10 | 0.00 | 30519309.45 | 87211876.42 | 0.886189E+09 | 0.715485E+10 | 0.00 | 0.78 |
Minimum of Months | 919024.63 | 0.00 | 0.00 | 20386.35 | 0.00 | 0.00 | 5707341.44 | 0.00 | 0.31 |
Maximum of Months | 0.890042E+09 | 0.142801E+10 | 0.00 | 6247258.72 | 35867940.05 | 0.374290E+09 | 0.159664E+10 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.811812E+09 | 0.00 | 0.00 | 5464006.51 | 0.00 | 0.271804E+09 | 0.305475E+10 | 0.00 | 0.70 |
February | 0.715273E+09 | 0.00 | 0.00 | 5920851.47 | 0.00 | 0.134918E+09 | 0.284844E+10 | 0.00 | 0.83 |
March | 0.715206E+09 | 0.00 | 0.00 | 6604828.69 | 0.00 | 0.113707E+09 | 0.304069E+10 | 0.00 | 1.00 |
April | 0.389387E+09 | 34605450.62 | 0.00 | 6964620.54 | 1566354.24 | 10181253.43 | 0.155029E+10 | 0.00 | 0.87 |
May | 0.170868E+09 | 0.142067E+09 | 0.00 | 4857926.98 | 18630335.01 | 0.00 | 0.560253E+09 | 0.00 | 0.67 |
June | 41218871.09 | 0.490156E+09 | 0.00 | 2859560.15 | 16477770.72 | 0.00 | 0.124539E+09 | 0.00 | 0.55 |
July | 2747113.72 | 0.149471E+10 | 0.00 | 251171.40 | 88710551.63 | 0.00 | 3817976.26 | 0.00 | 0.52 |
August | 27514753.41 | 0.743007E+09 | 0.00 | 2630057.07 | 33310792.60 | 0.00 | 0.140683E+09 | 0.00 | 0.69 |
September | 73026491.03 | 0.578500E+09 | 0.00 | 4736259.87 | 38815529.95 | 0.00 | 0.397145E+09 | 0.00 | 0.79 |
October | 0.336787E+09 | 0.169485E+09 | 0.00 | 8948265.35 | 3452002.08 | 213856.67 | 0.249171E+10 | 0.00 | 1.34 |
November | 0.673163E+09 | 0.00 | 0.00 | 8030289.38 | 0.00 | 0.126550E+09 | 0.371883E+10 | 0.00 | 1.15 |
December | 0.831864E+09 | 0.00 | 0.00 | 5024563.53 | 0.00 | 0.356721E+09 | 0.281195E+10 | 0.00 | 0.63 |
Annual Sum or Average | 0.478887E+10 | 0.365253E+10 | 0.00 | 62292400.93 | 0.200963E+09 | 0.101409E+10 | 0.207431E+11 | 0.00 | 0.81 |
Minimum of Months | 2747113.72 | 0.00 | 0.00 | 251171.40 | 0.00 | 0.00 | 3817976.26 | 0.00 | 0.52 |
Maximum of Months | 0.831864E+09 | 0.149471E+10 | 0.00 | 8948265.35 | 88710551.63 | 0.356721E+09 | 0.371883E+10 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.671366E+09 | 0.00 | 0.00 | 731358.51 | 0.00 | 0.372864E+09 | 0.497112E+09 | 0.00 | 0.40 |
February | 0.652904E+09 | 0.00 | 0.00 | 1172425.43 | 0.00 | 0.181543E+09 | 0.619364E+09 | 0.00 | 0.51 |
March | 0.590243E+09 | 0.00 | 0.00 | 2975695.32 | 0.00 | 0.100097E+09 | 0.131936E+10 | 0.00 | 0.86 |
April | 0.259078E+09 | 24779030.94 | 0.00 | 5221339.33 | 311881.51 | 6058650.54 | 0.106598E+10 | 0.00 | 0.95 |
May | 0.103351E+09 | 0.131523E+09 | 0.00 | 4098718.60 | 6924107.90 | 0.00 | 0.418644E+09 | 0.00 | 0.86 |
June | 24109603.83 | 0.462422E+09 | 0.00 | 2365055.97 | 6609321.45 | 0.00 | 94592173.77 | 0.00 | 0.71 |
July | 1486490.02 | 0.122113E+10 | 0.00 | 201276.95 | 45704662.94 | 0.00 | 2900759.33 | 0.00 | 0.65 |
August | 16806281.61 | 0.539470E+09 | 0.00 | 1841388.91 | 18743249.36 | 0.00 | 88129343.82 | 0.00 | 0.78 |
September | 54469259.89 | 0.331421E+09 | 0.00 | 2955604.16 | 25746768.11 | 0.00 | 0.219432E+09 | 0.00 | 0.73 |
October | 0.283259E+09 | 92007235.81 | 0.00 | 3626840.54 | 3323400.12 | 135778.03 | 0.945499E+09 | 0.00 | 0.98 |
November | 0.631921E+09 | 0.00 | 0.00 | 1867641.19 | 0.00 | 0.141420E+09 | 0.909445E+09 | 0.00 | 0.67 |
December | 0.637311E+09 | 0.00 | 0.00 | 465850.12 | 0.00 | 0.494692E+09 | 0.378670E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.392631E+10 | 0.280275E+10 | 0.00 | 27523195.01 | 0.107363E+09 | 0.129681E+10 | 0.655912E+10 | 0.00 | 0.71 |
Minimum of Months | 1486490.02 | 0.00 | 0.00 | 201276.95 | 0.00 | 0.00 | 2900759.33 | 0.00 | 0.36 |
Maximum of Months | 0.671366E+09 | 0.122113E+10 | 0.00 | 5221339.33 | 45704662.94 | 0.494692E+09 | 0.131936E+10 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.159969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259633E+09 | 0.00 | 0.00 | 0.27 |
February | 0.140345E+10 | 0.00 | 0.00 | 32045.99 | 0.00 | 0.176362E+09 | 21120240.09 | 0.00 | 0.32 |
March | 0.142724E+10 | 0.00 | 0.00 | 216418.68 | 0.00 | 0.104641E+09 | 94643209.87 | 0.00 | 0.36 |
April | 0.656615E+09 | 20031988.81 | 0.00 | 1816405.79 | 8526832.16 | 0.00 | 0.378219E+09 | 0.00 | 0.40 |
May | 0.205395E+09 | 0.124670E+09 | 0.00 | 2584077.31 | 14205192.94 | 0.00 | 0.342036E+09 | 0.00 | 0.44 |
June | 55272308.97 | 0.458357E+09 | 0.00 | 1797359.75 | 17546446.94 | 0.00 | 0.114238E+09 | 0.00 | 0.45 |
July | 1672049.42 | 0.139004E+10 | 0.00 | 85026.23 | 75160143.06 | 0.00 | 6962771.70 | 0.00 | 0.46 |
August | 30720534.26 | 0.668430E+09 | 0.00 | 1531351.45 | 30546869.96 | 0.00 | 0.138383E+09 | 0.00 | 0.57 |
September | 0.102810E+09 | 0.423582E+09 | 0.00 | 2289731.83 | 37925901.30 | 0.00 | 0.271887E+09 | 0.00 | 0.52 |
October | 0.447627E+09 | 96469657.70 | 0.00 | 3071282.06 | 11586064.13 | 0.00 | 0.957897E+09 | 0.00 | 0.60 |
November | 0.135438E+10 | 0.00 | 0.00 | 805176.70 | 0.00 | 13407608.91 | 0.394210E+09 | 0.00 | 0.38 |
December | 0.163244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350986E+09 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.891732E+10 | 0.318158E+10 | 0.00 | 14228875.78 | 0.195497E+09 | 0.905030E+09 | 0.271960E+10 | 0.00 | 0.42 |
Minimum of Months | 1672049.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.163244E+10 | 0.139004E+10 | 0.00 | 3071282.06 | 75160143.06 | 0.350986E+09 | 0.957897E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.957951E+09 | 0.00 | 0.00 | 303953.06 | 0.00 | 59179485.43 | 0.181935E+09 | 0.00 | 0.28 |
February | 0.707074E+09 | 0.00 | 0.00 | 848894.13 | 0.00 | 21651197.25 | 0.419315E+09 | 0.00 | 0.38 |
March | 0.610008E+09 | 0.00 | 0.00 | 2196965.53 | 0.00 | 13064197.48 | 0.823571E+09 | 0.00 | 0.53 |
April | 0.176590E+09 | 26690201.46 | 0.00 | 4572132.43 | 1890460.36 | 0.00 | 0.124798E+10 | 0.00 | 0.87 |
May | 67727662.23 | 0.128974E+09 | 0.00 | 4489817.66 | 6238536.08 | 0.00 | 0.765457E+09 | 0.00 | 0.93 |
June | 21889796.12 | 0.419526E+09 | 0.00 | 2365391.70 | 7095556.76 | 0.00 | 0.160947E+09 | 0.00 | 0.76 |
July | 770818.07 | 0.133966E+10 | 0.00 | 130774.93 | 27704765.33 | 0.00 | 8539616.56 | 0.00 | 0.70 |
August | 14877018.02 | 0.681798E+09 | 0.00 | 1676259.82 | 11613072.53 | 0.00 | 0.159016E+09 | 0.00 | 0.92 |
September | 45205614.06 | 0.477290E+09 | 0.00 | 3217882.77 | 12890103.65 | 0.00 | 0.451723E+09 | 0.00 | 0.99 |
October | 0.179262E+09 | 86137632.03 | 0.00 | 4584317.56 | 5706554.26 | 0.00 | 0.144421E+10 | 0.00 | 1.04 |
November | 0.580564E+09 | 0.00 | 0.00 | 2573768.13 | 0.00 | 710233.04 | 0.103435E+10 | 0.00 | 0.59 |
December | 0.989986E+09 | 0.00 | 0.00 | 308813.81 | 0.00 | 90756798.96 | 0.195250E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.435190E+10 | 0.316007E+10 | 0.00 | 27268971.54 | 73139048.97 | 0.185362E+09 | 0.689229E+10 | 0.00 | 0.69 |
Minimum of Months | 770818.07 | 0.00 | 0.00 | 130774.93 | 0.00 | 0.00 | 8539616.56 | 0.00 | 0.28 |
Maximum of Months | 0.989986E+09 | 0.133966E+10 | 0.00 | 4584317.56 | 27704765.33 | 90756798.96 | 0.144421E+10 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108161E+10 | 0.00 | 0.00 | 2944148.88 | 0.00 | 0.519046E+09 | 0.132483E+10 | 0.00 | 0.45 |
February | 0.907858E+09 | 0.00 | 0.00 | 2758962.49 | 0.00 | 0.387831E+09 | 0.108438E+10 | 0.00 | 0.56 |
March | 0.995420E+09 | 0.00 | 0.00 | 2766184.94 | 0.00 | 0.386377E+09 | 0.914978E+09 | 0.00 | 0.57 |
April | 0.561271E+09 | 55676794.30 | 0.00 | 3603952.31 | 2973417.19 | 0.106174E+09 | 0.605150E+09 | 0.00 | 0.56 |
May | 0.252244E+09 | 0.173652E+09 | 0.00 | 2683837.14 | 14393821.85 | 8235105.83 | 0.277450E+09 | 0.00 | 0.48 |
June | 78715683.42 | 0.547289E+09 | 0.00 | 1556992.91 | 19466555.42 | 0.00 | 65454594.07 | 0.00 | 0.46 |
July | 4462939.07 | 0.149344E+10 | 0.00 | 27618.41 | 96214516.76 | 0.00 | 1650679.28 | 0.00 | 0.48 |
August | 48163728.28 | 0.882557E+09 | 0.00 | 1544809.80 | 34886559.69 | 0.00 | 0.116670E+09 | 0.00 | 0.66 |
September | 0.107038E+09 | 0.700969E+09 | 0.00 | 3925326.11 | 32564864.53 | 1053513.24 | 0.399798E+09 | 0.00 | 0.78 |
October | 0.310001E+09 | 0.202255E+09 | 0.00 | 8967405.20 | 3402820.86 | 43222390.94 | 0.230976E+10 | 0.00 | 1.27 |
November | 0.612548E+09 | 0.00 | 0.00 | 7902536.45 | 0.00 | 0.262721E+09 | 0.302273E+10 | 0.00 | 1.00 |
December | 0.111693E+10 | 0.00 | 0.00 | 2924935.83 | 0.00 | 0.611380E+09 | 0.140866E+10 | 0.00 | 0.46 |
Annual Sum or Average | 0.607627E+10 | 0.405584E+10 | 0.00 | 41606710.46 | 0.203903E+09 | 0.232604E+10 | 0.115315E+11 | 0.00 | 0.64 |
Minimum of Months | 4462939.07 | 0.00 | 0.00 | 27618.41 | 0.00 | 0.00 | 1650679.28 | 0.00 | 0.45 |
Maximum of Months | 0.111693E+10 | 0.149344E+10 | 0.00 | 8967405.20 | 96214516.76 | 0.611380E+09 | 0.302273E+10 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.937677E+09 | 0.00 | 0.00 | 594110.40 | 0.00 | 86123398.61 | 0.270471E+09 | 0.00 | 0.30 |
February | 0.808199E+09 | 0.00 | 0.00 | 701819.75 | 0.00 | 54672459.32 | 0.263259E+09 | 0.00 | 0.38 |
March | 0.722951E+09 | 0.00 | 0.00 | 1743380.97 | 0.00 | 15716129.29 | 0.576575E+09 | 0.00 | 0.52 |
April | 0.280387E+09 | 34732876.54 | 0.00 | 3337075.49 | 1722973.58 | 0.00 | 0.716751E+09 | 0.00 | 0.68 |
May | 0.103152E+09 | 0.148540E+09 | 0.00 | 2777277.13 | 5319378.94 | 0.00 | 0.351182E+09 | 0.00 | 0.67 |
June | 27661928.76 | 0.464906E+09 | 0.00 | 1469294.63 | 6674119.47 | 0.00 | 93242849.42 | 0.00 | 0.61 |
July | 938120.39 | 0.120880E+10 | 0.00 | 71696.06 | 32516644.78 | 0.00 | 4930592.98 | 0.00 | 0.59 |
August | 14771133.02 | 0.620592E+09 | 0.00 | 1253665.72 | 13008704.55 | 0.00 | 0.109638E+09 | 0.00 | 0.77 |
September | 41584728.77 | 0.415067E+09 | 0.00 | 2704211.07 | 16331487.81 | 0.00 | 0.301037E+09 | 0.00 | 0.77 |
October | 0.171293E+09 | 0.103635E+09 | 0.00 | 4388459.51 | 3782665.52 | 0.00 | 0.122568E+10 | 0.00 | 1.02 |
November | 0.603661E+09 | 0.00 | 0.00 | 2397849.76 | 0.00 | 4344035.12 | 0.982019E+09 | 0.00 | 0.63 |
December | 0.992834E+09 | 0.00 | 0.00 | 498983.53 | 0.00 | 0.110497E+09 | 0.261635E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.470511E+10 | 0.299628E+10 | 0.00 | 21937824.01 | 79355974.65 | 0.271353E+09 | 0.515642E+10 | 0.00 | 0.61 |
Minimum of Months | 938120.39 | 0.00 | 0.00 | 71696.06 | 0.00 | 0.00 | 4930592.98 | 0.00 | 0.30 |
Maximum of Months | 0.992834E+09 | 0.120880E+10 | 0.00 | 4388459.51 | 32516644.78 | 0.110497E+09 | 0.122568E+10 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.179835E+10 | 0.00 | 0.00 | 35481.72 | 0.00 | 0.276709E+09 | 32499569.03 | 0.00 | 0.32 |
February | 0.150173E+10 | 0.00 | 0.00 | 319491.99 | 0.00 | 0.122466E+09 | 0.192432E+09 | 0.00 | 0.38 |
March | 0.138130E+10 | 0.00 | 0.00 | 1399862.15 | 0.00 | 40449827.37 | 0.581131E+09 | 0.00 | 0.48 |
April | 0.484690E+09 | 34541119.18 | 0.00 | 3735808.73 | 3226747.78 | 0.00 | 0.856131E+09 | 0.00 | 0.55 |
May | 0.150865E+09 | 0.159154E+09 | 0.00 | 4239145.15 | 13557592.51 | 0.00 | 0.585737E+09 | 0.00 | 0.61 |
June | 45505052.29 | 0.567152E+09 | 0.00 | 2792185.30 | 13450201.29 | 0.00 | 0.180537E+09 | 0.00 | 0.59 |
July | 2364756.98 | 0.153751E+10 | 0.00 | 193572.28 | 59226137.06 | 0.00 | 10587822.87 | 0.00 | 0.54 |
August | 32587995.45 | 0.653067E+09 | 0.00 | 2112322.34 | 22859882.63 | 0.00 | 0.161479E+09 | 0.00 | 0.62 |
September | 0.111909E+09 | 0.379662E+09 | 0.00 | 2409920.83 | 29815731.25 | 0.00 | 0.247656E+09 | 0.00 | 0.52 |
October | 0.531393E+09 | 89885704.72 | 0.00 | 2943145.83 | 8042593.62 | 0.00 | 0.829340E+09 | 0.00 | 0.58 |
November | 0.141693E+10 | 0.00 | 0.00 | 793952.04 | 0.00 | 70862543.95 | 0.391488E+09 | 0.00 | 0.41 |
December | 0.171134E+10 | 0.00 | 0.00 | 10.44 | 0.00 | 0.480036E+09 | 765937.46 | 0.00 | 0.31 |
Annual Sum or Average | 0.916896E+10 | 0.342097E+10 | 0.00 | 20974898.81 | 0.150179E+09 | 0.990524E+09 | 0.406978E+10 | 0.00 | 0.49 |
Minimum of Months | 2364756.98 | 0.00 | 0.00 | 10.44 | 0.00 | 0.00 | 765937.46 | 0.00 | 0.31 |
Maximum of Months | 0.179835E+10 | 0.153751E+10 | 0.00 | 4239145.15 | 59226137.06 | 0.480036E+09 | 0.856131E+09 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.786819E+09 | 0.00 | 0.00 | 439452.83 | 0.00 | 0.111608E+09 | 0.289728E+09 | 0.00 | 0.29 |
February | 0.582916E+09 | 0.00 | 0.00 | 1319881.82 | 0.00 | 28413973.87 | 0.697286E+09 | 0.00 | 0.43 |
March | 0.516783E+09 | 0.00 | 0.00 | 3218185.92 | 0.00 | 11402511.66 | 0.142207E+10 | 0.00 | 0.73 |
April | 0.151920E+09 | 29460158.77 | 0.00 | 5987883.81 | 1950038.18 | 0.00 | 0.163386E+10 | 0.00 | 1.07 |
May | 61491512.81 | 0.133975E+09 | 0.00 | 5815267.24 | 6473934.31 | 0.00 | 0.964849E+09 | 0.00 | 1.12 |
June | 19698988.47 | 0.444309E+09 | 0.00 | 3320867.30 | 7096454.58 | 0.00 | 0.220097E+09 | 0.00 | 0.90 |
July | 1109686.47 | 0.136176E+10 | 0.00 | 258841.61 | 25090697.37 | 0.00 | 11890677.60 | 0.00 | 0.78 |
August | 17473185.29 | 0.620158E+09 | 0.00 | 2076922.06 | 9650220.54 | 0.00 | 0.171278E+09 | 0.00 | 0.94 |
September | 51390381.09 | 0.407061E+09 | 0.00 | 3207413.16 | 13462092.05 | 0.00 | 0.417387E+09 | 0.00 | 0.95 |
October | 0.233726E+09 | 70174712.40 | 0.00 | 3909596.65 | 4458725.05 | 0.00 | 0.119759E+10 | 0.00 | 0.90 |
November | 0.593886E+09 | 0.00 | 0.00 | 2046719.53 | 0.00 | 26776809.67 | 0.850957E+09 | 0.00 | 0.53 |
December | 0.828584E+09 | 0.00 | 0.00 | 250178.48 | 0.00 | 0.186750E+09 | 0.177222E+09 | 0.00 | 0.26 |
Annual Sum or Average | 0.384580E+10 | 0.306690E+10 | 0.00 | 31851210.42 | 68182162.09 | 0.364951E+09 | 0.805421E+10 | 0.00 | 0.74 |
Minimum of Months | 1109686.47 | 0.00 | 0.00 | 250178.48 | 0.00 | 0.00 | 11890677.60 | 0.00 | 0.26 |
Maximum of Months | 0.828584E+09 | 0.136176E+10 | 0.00 | 5987883.81 | 25090697.37 | 0.186750E+09 | 0.163386E+10 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.938468E+09 | 0.00 | 0.00 | 6740042.36 | 0.00 | 0.121193E+09 | 0.354526E+10 | 0.00 | 0.77 |
February | 0.812700E+09 | 0.00 | 0.00 | 6955848.50 | 0.00 | 44124270.86 | 0.307362E+10 | 0.00 | 0.89 |
March | 0.784251E+09 | 0.00 | 0.00 | 7295121.07 | 0.00 | 16167848.81 | 0.304305E+10 | 0.00 | 1.01 |
April | 0.396480E+09 | 65254408.88 | 0.00 | 6357529.06 | 3071603.76 | 0.00 | 0.152023E+10 | 0.00 | 0.82 |
May | 0.170266E+09 | 0.185000E+09 | 0.00 | 4479875.60 | 13650458.05 | 0.00 | 0.595974E+09 | 0.00 | 0.65 |
June | 49253818.61 | 0.563180E+09 | 0.00 | 2604658.09 | 14081181.25 | 0.00 | 0.156168E+09 | 0.00 | 0.56 |
July | 2416230.64 | 0.153472E+10 | 0.00 | 178936.12 | 62174823.87 | 0.00 | 9204242.87 | 0.00 | 0.53 |
August | 32324228.11 | 0.776791E+09 | 0.00 | 2475196.51 | 23800729.40 | 0.00 | 0.179121E+09 | 0.00 | 0.70 |
September | 81137796.23 | 0.609183E+09 | 0.00 | 4401822.28 | 26407197.18 | 0.00 | 0.438672E+09 | 0.00 | 0.78 |
October | 0.330029E+09 | 0.175540E+09 | 0.00 | 9514453.46 | 3236337.55 | 0.00 | 0.250800E+10 | 0.00 | 1.29 |
November | 0.710496E+09 | 0.00 | 0.00 | 9600140.49 | 0.00 | 25302553.98 | 0.392562E+10 | 0.00 | 1.19 |
December | 0.102045E+10 | 0.00 | 0.00 | 6400658.11 | 0.00 | 0.170712E+09 | 0.339360E+10 | 0.00 | 0.72 |
Annual Sum or Average | 0.532828E+10 | 0.390967E+10 | 0.00 | 67004281.66 | 0.146422E+09 | 0.377500E+09 | 0.223885E+11 | 0.00 | 0.83 |
Minimum of Months | 2416230.64 | 0.00 | 0.00 | 178936.12 | 0.00 | 0.00 | 9204242.87 | 0.00 | 0.53 |
Maximum of Months | 0.102045E+10 | 0.153472E+10 | 0.00 | 9600140.49 | 62174823.87 | 0.170712E+09 | 0.392562E+10 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.942327E+09 | 0.00 | 0.00 | 903923.59 | 0.00 | 0.143549E+09 | 0.558253E+09 | 0.00 | 0.42 |
February | 0.773596E+09 | 0.00 | 0.00 | 1369544.26 | 0.00 | 66725316.36 | 0.658506E+09 | 0.00 | 0.53 |
March | 0.675640E+09 | 0.00 | 0.00 | 3170860.41 | 0.00 | 16375465.44 | 0.125974E+10 | 0.00 | 0.83 |
April | 0.256726E+09 | 48129852.34 | 0.00 | 4644041.71 | 661302.04 | 0.00 | 0.103520E+10 | 0.00 | 0.89 |
May | 99831407.02 | 0.175430E+09 | 0.00 | 3628505.11 | 4050414.26 | 0.00 | 0.444558E+09 | 0.00 | 0.83 |
June | 28140945.06 | 0.548869E+09 | 0.00 | 2055289.55 | 4907003.93 | 0.00 | 0.116749E+09 | 0.00 | 0.74 |
July | 1503738.65 | 0.127018E+10 | 0.00 | 124000.18 | 29563985.21 | 0.00 | 6249326.07 | 0.00 | 0.66 |
August | 20100372.35 | 0.575721E+09 | 0.00 | 1689990.26 | 11111903.01 | 0.00 | 0.112297E+09 | 0.00 | 0.80 |
September | 59003801.82 | 0.354206E+09 | 0.00 | 2732266.70 | 14509641.74 | 0.00 | 0.248219E+09 | 0.00 | 0.73 |
October | 0.258703E+09 | 93257445.12 | 0.00 | 3898936.96 | 3545190.27 | 0.00 | 0.100358E+10 | 0.00 | 0.95 |
November | 0.726510E+09 | 0.00 | 0.00 | 2223972.09 | 0.00 | 29132894.87 | 0.973692E+09 | 0.00 | 0.69 |
December | 0.950454E+09 | 0.00 | 0.00 | 630207.22 | 0.00 | 0.225894E+09 | 0.451657E+09 | 0.00 | 0.38 |
Annual Sum or Average | 0.479254E+10 | 0.306579E+10 | 0.00 | 27071538.04 | 68349440.46 | 0.481677E+09 | 0.686870E+10 | 0.00 | 0.71 |
Minimum of Months | 1503738.65 | 0.00 | 0.00 | 124000.18 | 0.00 | 0.00 | 6249326.07 | 0.00 | 0.38 |
Maximum of Months | 0.950454E+09 | 0.127018E+10 | 0.00 | 4644041.71 | 29563985.21 | 0.225894E+09 | 0.125974E+10 | 0.00 | 0.95 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:01
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.214646E+12 | 0.112074E+11 | 0.00 | 0.182223E+12 | 0.860684E+10 |
February | 0.217496E+12 | 0.912254E+10 | 0.00 | 0.161918E+12 | 0.150954E+11 |
March | 0.310962E+12 | 0.962830E+10 | 0.00 | 0.196127E+12 | 0.323829E+11 |
April | 0.318244E+12 | 0.478466E+10 | 0.00 | 0.151315E+12 | 0.931470E+11 |
May | 0.329786E+12 | 0.166726E+10 | 0.00 | 0.102150E+12 | 0.181922E+12 |
June | 0.318393E+12 | -0.158996E+10 | 0.00 | 0.160296E+11 | 0.255666E+12 |
July | 0.316803E+12 | -0.450770E+10 | 0.00 | -0.833122E+11 | 0.287605E+12 |
August | 0.295828E+12 | -0.208386E+10 | 0.00 | -0.206671E+11 | 0.258861E+12 |
September | 0.279867E+12 | -323329802.3 | 0.00 | 0.128828E+11 | 0.208375E+12 |
October | 0.260867E+12 | 0.384872E+10 | 0.00 | 0.151509E+12 | 0.104418E+12 |
November | 0.216272E+12 | 0.902873E+10 | 0.00 | 0.201628E+12 | 0.257622E+11 |
December | 0.185727E+12 | 0.102385E+11 | 0.00 | 0.173777E+12 | 0.696233E+10 |
Annual Sum or Average | 0.326489E+13 | 0.510212E+11 | 0.00 | 0.124558E+13 | 0.147880E+13 |
Minimum of Months | 0.185727E+12 | -0.450770E+10 | 0.00 | -0.833122E+11 | 0.696233E+10 |
Maximum of Months | 0.329786E+12 | 0.112074E+11 | 0.00 | 0.201628E+12 | 0.287605E+12 |