Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 08:32:05
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1480.97 | 297.25 | 297.25 |
Net Site Energy | 1480.97 | 297.25 | 297.25 |
Total Source Energy | 4195.46 | 842.09 | 842.09 |
Net Source Energy | 4195.46 | 842.09 | 842.09 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 94.81 | 105.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 74.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 233.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 51.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 71.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 132.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1243.44 | 237.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 94.81 | 105.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 74.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 233.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 51.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 71.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 132.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 94.81 | 105.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 74.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 233.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 51.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 71.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 132.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 57.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 48.33 | 47.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 249.58 | 47.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 57.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 48.33 | 47.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 249.58 | 47.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1243.441 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1243.441 | 100.00 |
Total On-Site and Utility Electric Sources | 1243.441 | 100.00 |
Total Electricity End Uses | 1243.441 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 209.67 |
Time Setpoint Not Met During Occupied Cooling | 56.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1732.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.6636 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.6636 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.6636 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 6.6636 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.6636 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 26-DEC-08:20 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 178948.94 | 52153.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8334.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 243.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7145.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 9342.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 221465.13 | 61495.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 178948.94 | 52153.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 8334.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 243.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7145.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 9342.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 300.26 | 114.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 236.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 740.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 163.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 37.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 225.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 143.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3937.98 | 257.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 60.27 | 22.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 47.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 148.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 45.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 28.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 790.41 | 51.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 60.27 | 22.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 47.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 148.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 45.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 28.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 790.41 | 51.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.83 | 0.264769 | 0.225000 | 0.636885 | 0.706051 | 0.500000 | 0.001439 |
CORE_MID VAV BOX COMPONENT | 2.05 | 0.365546 | 0.311000 | 0.637623 | 0.974790 | 0.500000 | 0.001042 |
CORE_TOP VAV BOX COMPONENT | 2.10 | 0.357066 | 0.304000 | 0.638073 | 0.952176 | 0.500000 | 0.001067 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.602464 | 0.262243 | 0.223000 | 0.134349 | 0.699314 | 0.500000 | 0.001453 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.775654 | 0.128952 | 0.110000 | 0.085322 | 0.343871 | 0.500000 | 0.002955 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.17 | 0.134928 | 0.115000 | 0.134657 | 0.359808 | 0.500000 | 0.002824 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.857176 | 0.116680 | 0.099000 | 0.084860 | 0.311147 | 0.500000 | 0.003265 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.482152 | 0.327680 | 0.279000 | 0.134520 | 0.873814 | 0.500000 | 0.001163 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.643126 | 0.155524 | 0.132000 | 0.084893 | 0.414732 | 0.500000 | 0.002450 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.960592 | 0.164473 | 0.140000 | 0.134483 | 0.438595 | 0.500000 | 0.002316 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.716659 | 0.139558 | 0.119000 | 0.085282 | 0.372154 | 0.500000 | 0.002730 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.531574 | 0.297215 | 0.253000 | 0.134488 | 0.792573 | 0.500000 | 0.001282 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.777895 | 0.342880 | 0.500000 | 0.002963 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.09 | 0.145201 | 0.123000 | 0.133835 | 0.387204 | 0.500000 | 0.002624 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.800635 | 0.124920 | 0.106000 | 0.084867 | 0.333120 | 0.500000 | 0.003050 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 20967.87 |
CORE_MID VAV BOX REHEAT COIL | 20992.17 |
CORE_TOP VAV BOX REHEAT COIL | 31987.06 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 14975.32 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 9795.72 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 14894.18 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 9749.35 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 10974.58 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7279.41 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 10901.04 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 7230.97 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 11744.61 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 7731.01 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 11667.34 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 7688.50 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.82 | 1.08 | 5.63 | 1.53 | 4.94 | 4.94 | 0.300000 | 0.309935 | 4.94 |
PACU_VAV_MID | 2.62 | 1.08 | 5.25 | 1.74 | 4.36 | 4.36 | 0.300000 | 0.398560 | 4.36 |
PACU_VAV_TOP | 2.75 | 1.08 | 5.51 | 2.47 | 4.92 | 4.92 | 0.300000 | 0.502693 | 4.92 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.94 |
PACU_VAV_MID_OA_CONTROLLER | 4.36 |
PACU_VAV_TOP_OA_CONTROLLER | 4.92 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.94 | 85400.21 | 0.800773 | 1.65 | 28463.89 | 0.800773 |
PACU_VAV_MID COOLING COIL | 4.36 | 76359.14 | 0.800248 | 1.45 | 25450.50 | 0.800248 |
PACU_VAV_TOP COOLING COIL | 4.92 | 85145.92 | 0.800565 | 1.64 | 28379.13 | 0.800565 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 14254.73 |
PACU_VAV_MID HEATING COIL | 15954.66 |
PACU_VAV_TOP HEATING COIL | 14306.66 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.94 |
PACU_VAV_MID FAN | 4.36 |
PACU_VAV_TOP FAN | 4.92 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 31.498 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.8668 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.8532 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.101 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2365 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2366 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9196 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9381 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6745 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.151 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.150 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.29350128E-12 | 0.14024199E-14 | -0.85558835E-13 | 0.14795563E-15 |
43 | 6 | 0.27596652E-07 | 0.24107488E-09 | 0.63308017E-08 | -0.12943591E-12 |
44 | 5 | -0.18463709E-03 | 0.20772830E-05 | -0.95040309E-04 | 0.62615177E-08 |
45 | 4 | 0.28572581 | 0.10171039E-02 | 0.97375121E-01 | -0.32667087E-04 |
46 | 3 | -7.1391205 | 0.31676816E-01 | -2.3011695 | 0.28385744E-01 |
47 | 2 | 40.451560 | 0.11313072 | 15.110175 | -0.32866754 |
48 | 1 | -80.224209 | 0.51250674E-01 | -29.002757 | 1.0717664 |
49 | 0 | 46.824341 | 0.10349526E-02 | 16.294583 | |
50 | 7 | -0.29575366E-12 | 0.13916748E-14 | -0.86470795E-13 | 0.14800413E-15 |
51 | 6 | 0.27759747E-07 | 0.23770535E-09 | 0.63667993E-08 | -0.13030888E-12 |
52 | 5 | -0.18546937E-03 | 0.20460315E-05 | -0.95457978E-04 | 0.62966404E-08 |
53 | 4 | 0.28670590 | 0.10008406E-02 | 0.97727300E-01 | -0.32804728E-04 |
54 | 3 | -7.1585449 | 0.31143840E-01 | -2.3069324 | 0.28480895E-01 |
55 | 2 | 40.515639 | 0.11114407 | 15.133849 | -0.32938113 |
56 | 1 | -80.273331 | 0.50317938E-01 | -29.023991 | 1.0728132 |
57 | 0 | 46.824340 | 0.10154678E-02 | 16.294067 | |
58 | 7 | -0.28281898E-12 | 0.14025464E-14 | -0.82622143E-13 | 0.19904483E-15 |
59 | 6 | 0.24787521E-07 | 0.29557932E-09 | 0.57107416E-08 | -0.11447606E-12 |
60 | 5 | -0.17017937E-03 | 0.25981591E-05 | -0.87765911E-04 | 0.56555961E-08 |
61 | 4 | 0.26851995 | 0.12946983E-02 | 0.91201294E-01 | -0.30269387E-04 |
62 | 3 | -6.7976835 | 0.40953066E-01 | -2.1999024 | 0.26714449E-01 |
63 | 2 | 39.324706 | 0.14826279 | 14.693101 | -0.31612152 |
64 | 1 | -79.359856 | 0.67961194E-01 | -28.628348 | 1.0533482 |
65 | 0 | 46.824347 | 0.13883650E-02 | 16.303898 | |
66 | 7 | -0.18778705E-08 | -0.48456698E-15 | 0.68415356E-14 | -0.90766841E-16 |
67 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
68 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
69 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
70 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
71 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
72 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
73 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
74 | 7 | -0.17777358E-08 | -0.41207670E-15 | 0.60771148E-14 | -0.79247013E-16 |
75 | 6 | 0.66205355E-05 | 0.45347915E-08 | 0.31869553E-02 | -0.26734852E-04 |
76 | 5 | -0.47643654E-03 | 0.26865296E-05 | -0.22355891 | 0.19546881E-02 |
77 | 4 | 0.10961386E-01 | 0.12229770E-03 | 4.8267865 | -0.45238458E-01 |
78 | 3 | -0.96263561E-01 | 0.97262436E-03 | -38.005829 | 0.39848146 |
79 | 2 | 0.34182167 | 0.16181264E-02 | 116.45361 | -1.4175335 |
80 | 1 | -0.49337445 | 0.49308431E-03 | -143.88945 | 2.0487464 |
81 | 0 | 0.24054552 | 0.11921404E-04 | 60.838472 | |
82 | 7 | -0.18778705E-08 | -0.48456747E-15 | 0.68415356E-14 | -0.90766840E-16 |
83 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
84 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
85 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
86 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
87 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
88 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
89 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
90 | 7 | -0.17776120E-08 | -0.41258204E-15 | 0.60425363E-14 | -0.82023253E-16 |
91 | 6 | 0.66209765E-05 | 0.45351028E-08 | 0.31869540E-02 | -0.26734841E-04 |
92 | 5 | -0.47646911E-03 | 0.26867147E-05 | -0.22355884 | 0.19546874E-02 |
93 | 4 | 0.10962140E-01 | 0.12230614E-03 | 4.8267853 | -0.45238446E-01 |
94 | 3 | -0.96270204E-01 | 0.97269154E-03 | -38.005822 | 0.39848139 |
95 | 2 | 0.34184528 | 0.16182383E-02 | 116.45360 | -1.4175333 |
96 | 1 | -0.49340854 | 0.49311848E-03 | -143.88944 | 2.0487463 |
97 | 0 | 0.24056214 | 0.11922214E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.359 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2573E-002 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2641E-002 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4224E-002 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4284E-002 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6471E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.6944E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1337E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1567E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1623 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.9225E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1866 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1161 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1060 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7045E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5658E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7130E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2572E-002 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2644E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4224E-002 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4288E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6472E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.6962E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1335E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1565E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.2304E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2846E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8309E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9927E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8970E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5043E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3611E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5268E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5254E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.5531E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.1996E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.2197E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8087E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.8154E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8245E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8324E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6869E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7449E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9039E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9509E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3474E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3809E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1335E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1565E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6058E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6401E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5557E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0181E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2282E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3531E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5658E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7130E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6871E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7454E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9039E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9508E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3472E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3794E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1337E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1567E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.9163E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1214E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.4250E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7806E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.6747E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3962E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3611E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5268E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.3487E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.4506E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9713E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.0906E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6797E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7106E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.8247E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.8326E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1612 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1154 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1821 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1336 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1142 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.9166E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.2056E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.4300E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.9837E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.1443E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.6075E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.8659E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.7319E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.4067E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.2614E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4669E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.2170E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.4103E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0968E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6778E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.7687E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9509E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.2056E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.4300E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.6810E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.9904E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2167E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6662E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.5169E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3039E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.2615E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.4670E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1613 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1154 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1821 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1336 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1142 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.9159E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.2051E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.4297E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.9837E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.1440E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.6075E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.8657E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.7315E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.4064E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.2609E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4667E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.2172E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.4102E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0969E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6777E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.7684E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9507E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.2051E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.4297E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.6810E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.9902E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.2167E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6659E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.5165E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3036E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.2610E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.4667E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 38726.87516 | 38726.87516 | 2.83060 | 2.83060 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 6371.61145 | 6371.61145 | 0.27151 | 0.42469 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 28086.28149 | 28086.28149 | 2.05023 | 2.05023 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 12990.79778 | 12990.79778 | 0.55697 | 0.55697 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 28476.46105 | 28476.46105 | 2.09893 | 2.09893 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 29.19200 | 8.82116E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 22549.88372 | 22549.88372 | 0.97158 | 0.97158 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8173.82910 | 8173.82910 | 0.60246 | 0.60246 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 29.29600 | 8.82133E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 10520.88627 | 10520.88627 | 0.45486 | 0.45486 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10523.63674 | 10523.63674 | 0.77565 | 0.77565 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 6881.33206 | 6881.33206 | 0.29754 | 0.29754 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 15886.55029 | 15886.55029 | 1.17093 | 1.17093 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 10464.06345 | 10464.06345 | 0.45240 | 0.45240 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11629.68934 | 11629.68934 | 0.85718 | 0.85718 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 6848.85580 | 6848.85580 | 0.29613 | 0.29613 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 6541.49957 | 6541.49957 | 0.48215 | 0.48215 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.82150E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 7717.79171 | 7717.79171 | 0.33335 | 0.33335 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8725.59854 | 8725.59854 | 0.64313 | 0.64313 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 22.36267 | 8.81033E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 5118.26103 | 5118.26103 | 0.22111 | 0.22111 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 13032.74548 | 13032.74548 | 0.96059 | 0.96059 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31333 | 8.82136E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 7666.28745 | 7666.28745 | 0.33111 | 0.33111 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9723.22054 | 9723.22054 | 0.71666 | 0.71666 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 26.90400 | 8.81750E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 5084.33705 | 5084.33705 | 0.21964 | 0.21964 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7212.03316 | 7212.03316 | 0.53157 | 0.53157 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.82150E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 8257.75348 | 8257.75348 | 0.35673 | 0.35673 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10554.04848 | 10554.04848 | 0.77789 | 0.77789 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 23.35067 | 8.81188E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 5434.96205 | 5434.96205 | 0.23482 | 0.23482 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 14762.52153 | 14762.52153 | 1.08809 | 1.08809 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.82094E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 8203.64144 | 8203.64144 | 0.35439 | 0.35439 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10862.56218 | 10862.56218 | 0.80063 | 0.80063 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 5405.19415 | 5405.19415 | 0.23353 | 0.23353 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 72093.88 | 4.93616 | 4.93616 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 19159.91 | 1.52989 | 1.52989 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 64354.47 | 4.35681 | 4.35681 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 19092.79 | 1.73645 | 1.73645 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 71812.59 | 4.91855 | 4.91855 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 19384.40 | 2.47252 | 2.47252 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:30:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.83060 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26477 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22500 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63688 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70605 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.43899E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20967.87161 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.05023 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36555 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31100 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63762 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97479 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04228E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20992.16877 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.09893 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35707 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30400 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63807 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.95218 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.06703E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 31987.05573 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.60246 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26224 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22300 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13435 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69931 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.45285E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14975.31631 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77565 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12895 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.53219E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34387 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.95460E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9795.72249 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.17093 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13493 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11500 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13466 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35981 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.82373E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14894.18375 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85718 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11668 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.90000E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48604E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31115 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.26534E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9749.35456 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.48215 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32768 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27900 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13452 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.87381 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.16272E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10974.58437 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64313 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15552 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13200 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48926E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41473 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.44978E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7279.41047 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.96059 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16447 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13448 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43860 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.31649E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10901.04208 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71666 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13956 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11900 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52824E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37215 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.73005E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7230.97277 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.53157 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29721 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25300 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13449 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79257 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.28190E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11744.60985 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77789 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34288 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.96313E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7731.00728 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.08809 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14520 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12300 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13383 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38720 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.62394E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11667.34018 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80063 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12492 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10600 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48673E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33312 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.04995E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7688.50143 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.81656 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07606 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.63313 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.52989 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.93616 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.93616 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.30994 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.62421 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07560 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.24842 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.73645 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.35681 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.35681 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.39856 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.75258 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07726 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.50515 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.47252 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.91855 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.91855 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.50269 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.93616 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.35681 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.91855 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.93616 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.93616 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 85400.21304 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80077 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.64522 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 28463.89101 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80077 |
152 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 14254.72915 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.93616 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.35681 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.35681 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 76359.14323 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80025 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.45212 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 25450.50244 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80025 |
161 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 15954.65764 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.35681 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.91855 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.91855 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 85145.91580 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80056 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.63935 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 28379.13374 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80056 |
170 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 14306.65677 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.91855 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 84103.03 | 286971.46 | 10.91 | 2.82 | 3.12 | 3.29 | 3.47 | 9.62 | 10.65 | 11.21 | 11.82 | 5.6278 | 4.4596 | 2.9914 | 1.2268 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 75243.19 | 256740.43 | 10.94 | 2.82 | 3.13 | 3.30 | 3.48 | 9.64 | 10.68 | 11.25 | 11.86 | 4.9673 | 3.9391 | 2.6429 | 1.0791 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 83854.85 | 286124.62 | 10.91 | 2.82 | 3.12 | 3.29 | 3.47 | 9.62 | 10.65 | 11.22 | 11.82 | 5.6077 | 4.4438 | 2.9808 | 1.2226 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.237 | 0.224 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.237 | 0.224 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.6646087651E-002 | 3.8192804941E-002 | Pass | Pass | 0.3342121171 | 0.4738034029 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.2840892573E-002 | 5.3412207759E-002 | Pass | Pass | 0.4551778217 | 0.4753978017 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.3845589585E-002 | 3.4365209665E-002 | Pass | Pass | 0.3849328657 | 0.4600960256 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.6872015373E-002 | 3.8996877736E-002 | Pass | Pass | 0.3141466782 | 0.4355701406 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.8115114603E-002 | 1.2601403824E-002 | Pass | Pass | 1.9420165206 | 9.8338202882 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 2.3921411851E-002 | 2.9012512939E-002 | Pass | Pass | 9.6954784683 | 58.9483312917 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2572376605 | 0.2462272133 | Pass | Pass | 25.6874579098 | 69.5621613580 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2655666874 | 0.2558941495 | Pass | Pass | 25.6019872099 | 68.8532533917 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2496065210 | 0.2427915679 | Pass | Pass | 25.1833450389 | 67.6849414670 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2691646744 | 0.2583632820 | Pass | Pass | 25.6043071701 | 68.7131064141 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1395463979 | 0.1559432263 | Pass | Pass | 1.6873927180 | 5.5025234577 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1516664904 | 0.1710510517 | Pass | Pass | 1.6559222094 | 5.5990745106 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1328435525 | 0.1487397929 | Pass | Pass | 1.7427087204 | 5.4477612848 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1541917291 | 0.1733736416 | Pass | Pass | 1.6385403157 | 5.6012146079 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1594402346 | 0.1744691498 | Pass | Pass | 4.6194679766 | 14.3243537705 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1688149460 | 0.1854400297 | Pass | Pass | 4.7252236999 | 14.7715850853 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1541182654 | 0.1694650923 | Pass | Pass | 4.6494725075 | 14.3916595894 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1701356542 | 0.1869518612 | Pass | Pass | 4.7074938397 | 14.7297869935 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3028.87 | 127.88 | 0.00 | 2287.62 | 397.44 | 5841.82 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.359 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.359 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.359 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
North Total or Average | 195.79 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.062 | 0.360 | 0.396 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.71 | 0.0000 | Y | 6.93 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.43 | 0.0000 | Y | 4.34 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.16 | 0.0000 | Y | 6.78 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.38 | 0.0000 | Y | 4.33 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.62 | 0.0000 | Y | 6.90 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.37 | 0.0000 | Y | 4.33 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.11 | 0.0000 | Y | 6.77 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.32 | 0.0000 | Y | 4.32 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.71 | 0.0000 | Y | 6.93 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.43 | 0.0000 | Y | 4.34 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.16 | 0.0000 | Y | 6.78 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.38 | 0.0000 | Y | 4.33 |
Interior Lighting Total | 6.6636 | 4982.19 | 33199.39 | 233.88 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 42.59 | 42.59 | 4.51 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.55 | 63.07 | 4.83 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.55 | 47.80 | 42.30 | |
Exterior Lighting Total | 5686.19 | 51.64 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 85400.21 | 68386.16 | 17014.05 | 0.80 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 76359.14 | 61106.23 | 15252.92 | 0.80 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 85145.92 | 68164.80 | 16981.11 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 84103.0 | 2.82 | 9.62 | N/A | N/A | 10.91 | |
PACU_VAV_MID COOLING COIL | 75243.2 | 2.82 | 9.64 | N/A | N/A | 10.94 | |
PACU_VAV_TOP COOLING COIL | 83854.8 | 2.82 | 9.62 | N/A | N/A | 10.91 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 20967.87 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 20992.17 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 31987.06 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14975.32 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9795.72 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14894.18 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9749.35 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10974.58 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7279.41 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10901.04 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7230.97 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11744.61 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7731.01 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11667.34 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7688.50 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 14254.73 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 15954.66 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 14306.66 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.94 | 10805.31 | 2189.01 | 1.00 | 1.13 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.36 | 9537.10 | 2189.01 | 1.00 | 1.14 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.92 | 10766.76 | 2189.01 | 1.00 | 1.13 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 84103.03 | 2.82 | 9.62 | 10.91 | 5.6278 | 3.12 | 10.65 | 4.4596 | 3.29 | 11.21 | 2.9914 | 3.47 | 11.82 | 1.2268 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 75243.19 | 2.82 | 9.64 | 10.94 | 4.9673 | 3.13 | 10.68 | 3.9391 | 3.30 | 11.25 | 2.6429 | 3.48 | 11.86 | 1.0791 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 83854.85 | 2.82 | 9.62 | 10.91 | 5.6077 | 3.12 | 10.65 | 4.4438 | 3.29 | 11.22 | 2.9808 | 3.47 | 11.82 | 1.2226 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 38726.88 | 38726.88 | 39.38 | 2.831 | 2.831 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00881 | 21.70 | 0.00881 | 0.425 | 0.00 |
CORE_MID | 28086.28 | 28086.28 | 28.56 | 2.050 | 2.050 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 21.70 | 0.00881 | 0.425 | 0.00 |
CORE_TOP | 28476.46 | 28476.46 | 28.95 | 2.099 | 2.099 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00892 | 29.19 | 0.00882 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8173.83 | 8173.83 | 39.42 | 0.602 | 0.602 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00881 | 29.30 | 0.00882 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10523.64 | 10523.64 | 80.17 | 0.776 | 0.776 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.00 | 24.00 | 0.00866 | 23.68 | 0.00881 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15886.55 | 15886.55 | 76.62 | 1.171 | 1.171 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00866 | 29.14 | 0.00882 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11629.69 | 11629.69 | 88.60 | 0.857 | 0.857 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00864 | 27.94 | 0.00882 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6541.50 | 6541.50 | 31.55 | 0.482 | 0.482 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00888 | 29.40 | 0.00882 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8725.60 | 8725.60 | 66.47 | 0.643 | 0.643 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 24.00 | 24.00 | 0.00869 | 22.36 | 0.00881 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 13032.75 | 13032.75 | 62.86 | 0.961 | 0.961 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00870 | 29.31 | 0.00882 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9723.22 | 9723.22 | 74.08 | 0.717 | 0.717 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.00 | 24.00 | 0.00867 | 26.90 | 0.00882 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7212.03 | 7212.03 | 34.78 | 0.532 | 0.532 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00885 | 29.40 | 0.00882 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10554.05 | 10554.05 | 80.40 | 0.778 | 0.778 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00865 | 23.35 | 0.00881 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 14762.52 | 14762.52 | 71.20 | 1.088 | 1.088 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00867 | 29.05 | 0.00882 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10862.56 | 10862.56 | 82.76 | 0.801 | 0.801 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00865 | 27.94 | 0.00882 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 6371.61 | 6371.61 | 6.48 | 0.272 | 0.425 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.425 | 0.00 |
CORE_MID | 12990.80 | 12990.80 | 13.21 | 0.557 | 0.557 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.425 | 0.00 |
CORE_TOP | 22549.88 | 22549.88 | 22.93 | 0.972 | 0.972 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10520.89 | 10520.89 | 50.74 | 0.455 | 0.455 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00757 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 6881.33 | 6881.33 | 52.42 | 0.298 | 0.298 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00757 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 10464.06 | 10464.06 | 50.47 | 0.452 | 0.452 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00757 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 6848.86 | 6848.86 | 52.18 | 0.296 | 0.296 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00757 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7717.79 | 7717.79 | 37.22 | 0.333 | 0.333 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 5118.26 | 5118.26 | 38.99 | 0.221 | 0.221 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00754 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 7666.29 | 7666.29 | 36.97 | 0.331 | 0.331 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 5084.34 | 5084.34 | 38.74 | 0.220 | 0.220 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8257.75 | 8257.75 | 39.83 | 0.357 | 0.357 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00745 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 5434.96 | 5434.96 | 41.41 | 0.235 | 0.235 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00747 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 8203.64 | 8203.64 | 39.57 | 0.354 | 0.354 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00745 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 5405.19 | 5405.19 | 41.18 | 0.234 | 0.234 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00746 | -4.20 | 0.00269 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.94 | 4.94 | 1.53 | 1.53 | 4.9362 | 1.5299 | 4.9362 | 0.3099 | 0.3000 |
PACU_VAV_MID | 4.36 | 4.36 | 1.74 | 1.74 | 4.3568 | 1.7364 | 4.3568 | 0.3986 | 0.3000 |
PACU_VAV_TOP | 4.92 | 4.92 | 2.47 | 2.47 | 4.9185 | 2.4725 | 4.9185 | 0.5027 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 20967.872 | 20967.872 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20967.87 | 13981.92 | 0.424691 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 6371.61 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 20992.169 | 20992.169 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20992.17 | 18336.88 | 0.556970 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 12990.80 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 31987.056 | 31987.056 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 31987.06 | 31987.06 | 0.971585 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 22549.88 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 14975.316 | 14975.316 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14975.32 | 14975.32 | 0.454865 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00757132 | 48.2864 | 10520.89 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 9795.722 | 9795.722 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9795.72 | 9795.72 | 0.297538 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00756792 | 48.2651 | 6881.33 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 14894.184 | 14894.184 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14894.18 | 14894.18 | 0.452401 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00756846 | 48.2683 | 10464.06 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 9749.355 | 9749.355 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9749.35 | 9749.35 | 0.296130 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00756548 | 48.2497 | 6848.86 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 10974.584 | 10974.584 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10974.58 | 10974.58 | 0.333345 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00751450 | 47.9282 | 7717.79 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 7279.410 | 7279.410 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7279.41 | 7279.41 | 0.221107 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00753609 | 48.0642 | 5118.26 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 10901.042 | 10901.042 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10901.04 | 10901.04 | 0.331112 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00750807 | 47.8877 | 7666.29 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 7230.973 | 7230.973 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7230.97 | 7230.97 | 0.219636 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00753011 | 48.0265 | 5084.34 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 11744.610 | 11744.610 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11744.61 | 11744.61 | 0.356734 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00745433 | 47.5496 | 8257.75 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 7731.007 | 7731.007 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7731.01 | 7731.01 | 0.234824 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00746909 | 47.6426 | 5434.96 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 11667.340 | 11667.340 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11667.34 | 11667.34 | 0.354387 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00744719 | 47.5046 | 8203.64 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 7688.501 | 7688.501 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7688.50 | 7688.50 | 0.233533 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00746365 | 47.6083 | 5405.19 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 85400.213 | 68386.161 | 4.936159 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 86222.28 | 81652.12 | 4.936159 | 25.04 | 16.87 | 0.00880640 | 10.99 | 10.99 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 19.3693 | 24.00 | 0.00880277 | 46.6911 | 66969.96 | 0.00 | 88059.08 | 68821.48 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 14254.729 | 14254.729 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14254.73 | 14254.73 | 1.480848 | 4.73 | 3.55 | 0.00447065 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 64.5644 | 18.58 | 0.00757595 | 56.1375 | 15166.36 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 76359.143 | 61106.227 | 4.356808 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 77192.59 | 72736.87 | 4.356808 | 25.18 | 16.94 | 0.00883872 | 10.99 | 10.99 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 21.9450 | 24.00 | 0.00884356 | 46.9044 | 59109.01 | 0.00 | 78736.53 | 61492.76 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 15954.658 | 15954.658 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15954.66 | 15954.66 | 1.307043 | 2.57 | 1.73 | 0.00400106 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 73.1499 | 18.68 | 0.00746324 | 54.9738 | 18083.22 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 85145.916 | 68164.804 | 4.918549 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 85970.42 | 81384.63 | 4.918549 | 25.05 | 16.87 | 0.00880856 | 10.99 | 10.99 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 19.4387 | 24.00 | 0.00880543 | 46.7049 | 66684.28 | 0.00 | 87796.87 | 68599.82 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 14306.657 | 14306.657 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14306.66 | 14306.66 | 1.475565 | 4.67 | 3.43 | 0.00439883 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 64.7955 | 17.91 | 0.00746282 | 57.6880 | 18686.92 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 20967.872 | 20967.872 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 20967.87 | 13981.92 | 1.0000 | 0.50410441 | 0.424691 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20967.87 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.62 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 6371.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 20992.169 | 20992.169 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 20992.17 | 18336.88 | 1.0000 | 0.66111844 | 0.556970 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20992.17 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 12990.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 31987.056 | 31987.056 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 31987.06 | 31987.06 | 1.0000 | 1.15326206 | 0.971585 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31987.06 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 22549.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 14975.316 | 14975.316 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14975.32 | 14975.32 | 1.0000 | 0.53992040 | 0.454865 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14975.32 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00757132 | 21.00 | 0.00757132 | 48.2864 | 10520.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9795.722 | 9795.722 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9795.72 | 9795.72 | 1.0000 | 0.35317521 | 0.297538 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9795.72 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00756792 | 21.00 | 0.00756792 | 48.2651 | 6881.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 14894.184 | 14894.184 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14894.18 | 14894.18 | 1.0000 | 0.53699525 | 0.452401 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14894.18 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00756846 | 21.00 | 0.00756846 | 48.2683 | 10464.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9749.355 | 9749.355 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9749.35 | 9749.35 | 1.0000 | 0.35150346 | 0.296130 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9749.35 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00756548 | 21.00 | 0.00756548 | 48.2497 | 6848.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 10974.584 | 10974.584 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10974.58 | 10974.58 | 1.0000 | 0.39567792 | 0.333345 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10974.58 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00751450 | 21.00 | 0.00751450 | 47.9282 | 7717.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7279.410 | 7279.410 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7279.41 | 7279.41 | 1.0000 | 0.26245204 | 0.221107 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7279.41 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00753609 | 21.00 | 0.00753609 | 48.0642 | 5118.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 10901.042 | 10901.042 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10901.04 | 10901.04 | 1.0000 | 0.39302643 | 0.331112 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10901.04 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00750807 | 21.00 | 0.00750807 | 47.8877 | 7666.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7230.973 | 7230.973 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7230.97 | 7230.97 | 1.0000 | 0.26070566 | 0.219636 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7230.97 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00753011 | 21.00 | 0.00753011 | 48.0265 | 5084.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 11744.610 | 11744.610 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11744.61 | 11744.61 | 1.0000 | 0.42344044 | 0.356734 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11744.61 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00745433 | 21.00 | 0.00745433 | 47.5496 | 8257.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7731.007 | 7731.007 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7731.01 | 7731.01 | 1.0000 | 0.27873392 | 0.234824 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7731.01 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00746909 | 21.00 | 0.00746909 | 47.6426 | 5434.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 11667.340 | 11667.340 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11667.34 | 11667.34 | 1.0000 | 0.42065456 | 0.354387 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11667.34 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00744719 | 21.00 | 0.00744719 | 47.5046 | 8203.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7688.501 | 7688.501 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7688.50 | 7688.50 | 1.0000 | 0.27720141 | 0.233533 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7688.50 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00746365 | 21.00 | 0.00746365 | 47.6083 | 5405.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 85400.213 | 68386.161 | 4.936159 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2107 | 1004.8586 | 1.1870 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.936159 | 5.85917556 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 86222.28 | 81652.12 | 1.0096 | 5.85917556 | 4.936159 | 25.04 | 16.87 | 0.00880640 | 47600.5 | 10.99 | 10.99 | 0.00850000 | 32479.1 | -999.0 | -999.00 | -999.00 | -999.00 | 10805.307 | 75416.98 | 29.40 | 0.00882150 | 18.34 | 0.95610000 | 19.3693 | 24.00 | 0.00880277 | 24.00 | 0.00880277 | 46.6911 | 66969.96 | 0.00 | 88059.08 | 68821.48 | 5.62778242 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.71 | 14.16 | 0.00984441 | 39675.2 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14254.729 | 14254.729 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.936159 | 5.85917556 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14254.73 | 14254.73 | 1.0000 | 1.75775267 | 1.480848 | 4.73 | 3.55 | 0.00447065 | 15972.6 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14254.73 | -4.20 | 0.00269032 | -4.20 | 0.95610000 | 64.5644 | 21.00 | 0.00771444 | 18.58 | 0.00757595 | 56.1375 | 15166.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 76359.143 | 61106.227 | 4.356808 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2707 | 1004.8586 | 1.1870 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.356808 | 5.17149135 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 77192.59 | 72736.87 | 1.0109 | 5.17149135 | 4.356808 | 25.18 | 16.94 | 0.00883872 | 47824.9 | 10.99 | 10.99 | 0.00850000 | 32479.2 | -999.0 | -999.00 | -999.00 | -999.00 | 9537.101 | 67655.49 | 29.40 | 0.00882150 | 18.34 | 0.95610000 | 21.9450 | 24.00 | 0.00884356 | 24.00 | 0.00884356 | 46.9044 | 59109.01 | 0.00 | 78736.53 | 61492.76 | 4.96725653 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.57 | 14.08 | 0.00982357 | 39471.3 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 15954.658 | 15954.658 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.356808 | 5.17149135 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15954.66 | 15954.66 | 1.0000 | 1.55144740 | 1.307043 | 2.57 | 1.73 | 0.00400106 | 12603.9 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15954.66 | -4.20 | 0.00269032 | -4.20 | 0.95610000 | 73.1499 | 21.00 | 0.00757204 | 18.68 | 0.00746324 | 54.9738 | 18083.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 85145.916 | 68164.804 | 4.918549 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2147 | 1004.8586 | 1.1870 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.918549 | 5.83827208 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 85970.42 | 81384.63 | 1.0097 | 5.83827208 | 4.918549 | 25.05 | 16.87 | 0.00880856 | 47610.6 | 10.99 | 10.99 | 0.00850000 | 32479.1 | -999.0 | -999.00 | -999.00 | -999.00 | 10766.757 | 75203.66 | 29.40 | 0.00882150 | 18.34 | 0.95610000 | 19.4387 | 24.00 | 0.00880543 | 24.00 | 0.00880543 | 46.7049 | 66684.28 | 0.00 | 87796.87 | 68599.82 | 5.60770446 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.71 | 14.15 | 0.00984245 | 39665.9 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14306.657 | 14306.657 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.918549 | 5.83827208 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:30:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14306.66 | 14306.66 | 1.0000 | 1.75148162 | 1.475565 | 4.67 | 3.43 | 0.00439883 | 15733.2 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14306.66 | -4.20 | 0.00269032 | -4.20 | 0.95610000 | 64.7955 | 21.00 | 0.00754343 | 17.91 | 0.00746282 | 57.6880 | 18686.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.94 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.36 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.92 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1785.50 | 2288.00 | 33.67 |
CORE_MID | 1240.33 | 3373.67 | 210.17 |
CORE_TOP | 1537.33 | 3925.50 | 724.67 |
PERIMETER_TOP_ZN_3 | 2325.17 | 4357.00 | 1564.83 |
PERIMETER_TOP_ZN_2 | 2643.50 | 3908.33 | 1417.50 |
PERIMETER_TOP_ZN_1 | 2553.50 | 3786.17 | 1220.67 |
PERIMETER_TOP_ZN_4 | 2648.00 | 4084.00 | 1490.67 |
PERIMETER_BOT_ZN_3 | 1697.83 | 4403.00 | 1105.33 |
PERIMETER_BOT_ZN_2 | 2205.67 | 3734.83 | 950.50 |
PERIMETER_BOT_ZN_1 | 2076.00 | 3926.83 | 879.50 |
PERIMETER_BOT_ZN_4 | 2259.83 | 3758.50 | 978.33 |
PERIMETER_MID_ZN_3 | 1882.83 | 4046.50 | 1037.50 |
PERIMETER_MID_ZN_2 | 1966.00 | 3201.00 | 899.67 |
PERIMETER_MID_ZN_1 | 2255.50 | 3418.67 | 771.17 |
PERIMETER_MID_ZN_4 | 2269.17 | 3748.83 | 986.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4096.17 | 4748.33 | 1732.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.67 | 0.00 | 0.67 | 0.00 |
CORE_MID | 2.00 | 0.00 | 2.00 | 0.00 |
CORE_TOP | 2.00 | 0.00 | 1.67 | 0.00 |
PERIMETER_TOP_ZN_3 | 15.67 | 0.00 | 11.17 | 0.00 |
PERIMETER_TOP_ZN_2 | 9.17 | 11.67 | 3.00 | 11.50 |
PERIMETER_TOP_ZN_1 | 4.00 | 14.83 | 1.17 | 14.17 |
PERIMETER_TOP_ZN_4 | 8.83 | 20.33 | 3.67 | 12.00 |
PERIMETER_BOT_ZN_3 | 3.17 | 0.00 | 3.17 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.67 | 8.67 | 0.67 | 8.67 |
PERIMETER_BOT_ZN_1 | 200.17 | 7.50 | 200.17 | 7.50 |
PERIMETER_BOT_ZN_4 | 0.83 | 13.33 | 0.83 | 6.67 |
PERIMETER_MID_ZN_3 | 2.83 | 0.00 | 2.67 | 0.00 |
PERIMETER_MID_ZN_2 | 0.67 | 11.67 | 0.33 | 11.67 |
PERIMETER_MID_ZN_1 | 0.50 | 14.50 | 0.33 | 14.50 |
PERIMETER_MID_ZN_4 | 0.67 | 19.83 | 0.33 | 11.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 217.17 | 70.67 | 209.67 | 56.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.63 | 52.94 | 2698.04 | 1.005 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.63 | 52.94 | 2698.04 | 0.685 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.63 | 52.94 | 2698.04 | 0.662 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.56 | 11.16 | 568.77 | 0.707 | 0.079 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.89 | 7.07 | 360.08 | 1.030 | 0.083 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.56 | 11.16 | 568.77 | 1.125 | 0.079 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.89 | 7.06 | 360.05 | 1.029 | 0.083 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.56 | 11.16 | 568.77 | 0.617 | 0.042 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.89 | 7.07 | 360.08 | 0.920 | 0.044 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.56 | 11.16 | 568.77 | 0.893 | 0.853 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.89 | 7.06 | 360.05 | 0.901 | 0.044 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.56 | 11.16 | 568.77 | 0.715 | 0.066 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.53 | 7.07 | 360.08 | 0.939 | 0.074 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.56 | 11.16 | 568.77 | 1.135 | 0.066 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.89 | 7.06 | 360.05 | 1.025 | 0.069 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.63 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.63 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.63 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.56 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.89 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.56 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.89 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.56 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.89 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.56 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.89 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.56 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.53 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.56 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.89 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.63 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.63 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.63 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.56 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.89 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.56 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.89 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.56 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.89 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.56 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.89 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.56 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.53 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.56 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.89 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.20 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 15836219.74 | 0.00 | 15836219.74 | 0.00 | 15836219.74 | 13393058.27 | 4504.78 | 522.64 | 3732.59 | 44.42 |
CORE_MID | 10842192.60 | 0.00 | 10842192.60 | 0.00 | 10842192.60 | 13393058.27 | 4572.95 | 1122.34 | 3064.71 | 48.08 |
CORE_TOP | 10505712.00 | 0.00 | 10505712.00 | 0.00 | 10505712.00 | 13393058.27 | 4638.82 | 1283.08 | 2838.09 | 53.26 |
PERIMETER_TOP_ZN_3 | 2364964.99 | 0.00 | 2364964.99 | 539250.78 | 2904215.77 | 2823374.22 | 4493.17 | 1376.89 | 2889.94 | 53.26 |
PERIMETER_TOP_ZN_2 | 2173037.39 | 0.00 | 2173037.39 | 359498.36 | 2532535.75 | 1787429.43 | 4355.38 | 1137.53 | 3267.10 | 53.20 |
PERIMETER_TOP_ZN_1 | 3747253.70 | 0.00 | 3747253.70 | 539250.78 | 4286504.48 | 2823374.22 | 4307.60 | 1202.54 | 3249.86 | 53.26 |
PERIMETER_TOP_ZN_4 | 2187745.15 | 0.00 | 2187745.15 | 359498.36 | 2547243.51 | 1787312.18 | 4527.94 | 1396.16 | 2835.90 | 53.20 |
PERIMETER_BOT_ZN_3 | 2061468.62 | 0.00 | 2061468.62 | 286716.78 | 2348185.40 | 2823374.22 | 5514.00 | 533.56 | 2712.44 | 44.42 |
PERIMETER_BOT_ZN_2 | 1938320.74 | 0.00 | 1938320.74 | 191143.37 | 2129464.10 | 1787429.43 | 5335.06 | 618.70 | 2806.24 | 44.42 |
PERIMETER_BOT_ZN_1 | 2979419.56 | 0.00 | 2979419.56 | 2993637.78 | 5973057.34 | 2823374.22 | 4980.47 | 514.19 | 3265.35 | 44.42 |
PERIMETER_BOT_ZN_4 | 1906839.37 | 0.00 | 1906839.37 | 191143.37 | 2097982.74 | 1787312.18 | 5334.47 | 486.43 | 2939.10 | 44.42 |
PERIMETER_MID_ZN_3 | 2387671.86 | 0.00 | 2387671.86 | 448884.86 | 2836556.72 | 2823374.22 | 4505.70 | 1113.69 | 3140.61 | 48.08 |
PERIMETER_MID_ZN_2 | 2009521.82 | 0.00 | 2009521.82 | 299254.78 | 2308776.60 | 1601953.02 | 4367.03 | 1089.19 | 3303.78 | 957.08 |
PERIMETER_MID_ZN_1 | 3778063.27 | 0.00 | 3778063.27 | 448884.86 | 4226948.14 | 2823374.22 | 4382.23 | 1325.05 | 3052.72 | 48.08 |
PERIMETER_MID_ZN_4 | 2171839.39 | 0.00 | 2171839.39 | 299254.78 | 2471094.17 | 1787312.18 | 4511.53 | 1278.01 | 2970.46 | 48.08 |
Total Facility | 66890270.21 | 0.00 | 66890270.21 | 6956418.86 | 73846689.07 | 67658168.57 | 5816.15 | 1770.86 | 4323.19 | 987.92 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.7368 | 0.0000 | 0.7368 | 0.0000 | 0.7368 | 0.4247 | 1717.86 | 522.64 | 3702.50 |
CORE_MID | 0.5028 | 0.0000 | 0.5028 | 0.0000 | 0.5028 | 0.4247 | 1792.45 | 1122.34 | 3028.21 |
CORE_TOP | 0.4867 | 0.0000 | 0.4867 | 0.0000 | 0.4867 | 0.4247 | 1861.66 | 1283.08 | 2798.26 |
PERIMETER_TOP_ZN_3 | 0.1096 | 0.0000 | 0.1096 | 0.0123 | 0.1219 | 0.0895 | 1716.00 | 1376.89 | 2850.10 |
PERIMETER_TOP_ZN_2 | 0.1010 | 0.0000 | 0.1010 | 0.0082 | 0.1092 | 0.0567 | 1578.21 | 1137.53 | 3227.26 |
PERIMETER_TOP_ZN_1 | 0.1742 | 0.0000 | 0.1742 | 0.0123 | 0.1865 | 0.0895 | 1530.43 | 1202.54 | 3210.03 |
PERIMETER_TOP_ZN_4 | 0.1009 | 0.0000 | 0.1009 | 0.0082 | 0.1091 | 0.0567 | 1750.78 | 1396.16 | 2796.07 |
PERIMETER_BOT_ZN_3 | 0.0956 | 0.0000 | 0.0956 | 0.0065 | 0.1022 | 0.0895 | 2727.09 | 533.56 | 2682.36 |
PERIMETER_BOT_ZN_2 | 0.0901 | 0.0000 | 0.0901 | 0.0043 | 0.0945 | 0.0567 | 2548.17 | 618.70 | 2776.13 |
PERIMETER_BOT_ZN_1 | 0.1385 | 0.0000 | 0.1385 | 0.1330 | 0.2716 | 0.0895 | 2193.55 | 514.19 | 3235.26 |
PERIMETER_BOT_ZN_4 | 0.0883 | 0.0000 | 0.0883 | 0.0043 | 0.0927 | 0.0567 | 2547.57 | 486.43 | 2908.99 |
PERIMETER_MID_ZN_3 | 0.1108 | 0.0000 | 0.1108 | 0.0102 | 0.1210 | 0.0895 | 1725.20 | 1113.69 | 3104.11 |
PERIMETER_MID_ZN_2 | 0.0921 | 0.0000 | 0.0921 | 0.0072 | 0.0993 | 0.0567 | 1586.55 | 1089.19 | 2358.26 |
PERIMETER_MID_ZN_1 | 0.1758 | 0.0000 | 0.1758 | 0.0102 | 0.1860 | 0.0895 | 1601.73 | 1325.05 | 3016.22 |
PERIMETER_MID_ZN_4 | 0.1004 | 0.0000 | 0.1004 | 0.0068 | 0.1072 | 0.0567 | 1731.05 | 1278.01 | 2933.94 |
Total Facility | 3.1038 | 0.0000 | 3.1038 | 0.2235 | 3.3273 | 2.1513 | 3020.82 | 1770.86 | 4273.48 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 34832330.08 | 0.00 | 34832330.08 | 22614548.33 | 4102.43 | 3.45 | 4654.12 | 44.42 |
PACU_VAV_MID | 29854582.86 | 0.00 | 29854582.86 | 22429071.92 | 4080.61 | 3.44 | 4675.95 | 47.25 |
PACU_VAV_TOP | 29557834.93 | 0.00 | 29557834.93 | 22614548.33 | 4118.76 | 2.51 | 4638.73 | 53.03 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.6196 | 0.0000 | 1.6196 | 0.7171 | 1315.51 | 3.45 | 4624.04 |
PACU_VAV_MID | 1.3853 | 0.0000 | 1.3853 | 0.7084 | 1300.11 | 3.44 | 4639.45 |
PACU_VAV_TOP | 1.3701 | 0.0000 | 1.3701 | 0.7171 | 1341.59 | 2.51 | 4598.90 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 354.78 | 2976.55 | 0.00 | 0.00 | 0.00 | 1443.68 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 35.23 | 2855.01 | 0.00 | 0.00 | 0.00 | 1918.85 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 26.07 | 2789.69 | 0.00 | 0.00 | 0.00 | 1996.01 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.3254 | 2.5764 | 0.0000 | 0.0000 | 0.0000 | 1.1101 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.2282 | 2.2171 | 0.0000 | 0.0000 | 0.0000 | 1.0252 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.1527 | 2.2124 | 0.0000 | 0.0000 | 0.0000 | 1.0318 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 943 |
Defaulted Fields | 546 |
Fields with Defaults | 2233 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1243.44 | 12315.29 | 29-MAY-18:00 | 221465.13 | 02-JAN-07:10 |
Electricity:Building | 939.32 | 12146.72 | 23-APR-17:20 | 70741.68 | 28-DEC-08:10 |
Electricity:Zone:CORE_BOTTOM | 291.77 | 4006.86 | 01-JAN-00:10 | 23121.21 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 939.32 | 12146.72 | 23-APR-17:20 | 70741.68 | 28-DEC-08:10 |
InteriorLights:Electricity | 233.88 | 905.38 | 23-APR-17:20 | 25003.79 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 233.88 | 905.38 | 23-APR-17:20 | 25003.79 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity | 233.88 | 905.38 | 23-APR-17:20 | 25003.79 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 233.88 | 905.38 | 23-APR-17:20 | 25003.79 | 02-JAN-16:30 |
Electricity:Zone:CORE_MID | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 31.26 | 413.68 | 19-MAR-17:10 | 2475.80 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.93 | 27.57 | 08-JAN-10:30 | 1040.56 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.93 | 27.57 | 08-JAN-10:30 | 1040.56 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.74 | 261.88 | 09-APR-17:10 | 1567.33 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.34 | 17.46 | 01-JAN-09:50 | 658.76 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.34 | 17.46 | 01-JAN-09:50 | 658.76 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 31.12 | 413.67 | 19-MAR-17:10 | 2475.79 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.78 | 27.57 | 01-JAN-09:50 | 1040.56 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.78 | 27.57 | 01-JAN-09:50 | 1040.56 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.73 | 261.87 | 19-MAR-17:10 | 1567.28 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.33 | 17.46 | 01-JAN-13:00 | 658.71 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.33 | 17.46 | 01-JAN-13:00 | 658.71 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 31.24 | 413.68 | 19-MAR-17:10 | 2475.80 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.90 | 27.57 | 08-JAN-10:20 | 1040.56 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.90 | 27.57 | 08-JAN-10:20 | 1040.56 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.73 | 261.88 | 09-APR-17:10 | 1567.33 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.33 | 17.46 | 01-JAN-09:50 | 658.76 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.33 | 17.46 | 01-JAN-09:50 | 658.76 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 31.10 | 413.67 | 19-MAR-17:10 | 2475.79 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.77 | 27.57 | 01-JAN-09:50 | 1040.56 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.77 | 27.57 | 01-JAN-09:50 | 1040.56 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.72 | 261.87 | 19-MAR-17:10 | 1567.28 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.32 | 17.46 | 01-JAN-10:30 | 658.71 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.32 | 17.46 | 01-JAN-10:30 | 658.71 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 31.26 | 413.68 | 19-MAR-17:10 | 2475.80 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.93 | 27.57 | 08-JAN-10:30 | 1040.56 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.93 | 27.57 | 08-JAN-10:30 | 1040.56 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.74 | 261.88 | 09-APR-17:10 | 1567.33 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.34 | 17.46 | 01-JAN-09:50 | 658.76 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.34 | 17.46 | 01-JAN-09:50 | 658.76 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 31.12 | 413.67 | 19-MAR-17:10 | 2475.79 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.78 | 27.57 | 01-JAN-09:50 | 1040.56 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.78 | 27.57 | 01-JAN-09:50 | 1040.56 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.73 | 261.87 | 19-MAR-17:10 | 1567.28 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.33 | 17.46 | 01-JAN-13:00 | 658.71 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.33 | 17.46 | 01-JAN-13:00 | 658.71 | 02-JAN-16:30 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 252.34 | 168.57 | 30-APR-17:30 | 187895.86 | 02-JAN-06:30 |
ExteriorEquipment:Electricity | 11.69 | 168.34 | 01-JAN-00:10 | 839.99 | 28-DEC-08:20 |
Transformer:ExteriorEquipment:Electricity | 11.69 | 168.34 | 01-JAN-00:10 | 839.99 | 28-DEC-08:20 |
ElectricityPurchased:Facility | 1243.44 | 12315.29 | 29-MAY-18:00 | 221465.13 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 1243.44 | 12315.29 | 29-MAY-18:00 | 221465.13 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1243.44 | 12315.29 | 29-MAY-18:00 | 221465.13 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1243.44 | 12315.29 | 29-MAY-18:00 | 221465.13 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1243.44 | 12315.29 | 29-MAY-18:00 | 221465.13 | 02-JAN-07:10 |
ElectricityNet:Plant | 1243.44 | 12315.29 | 29-MAY-18:00 | 221465.13 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 1243.44 | 12315.29 | 29-MAY-18:00 | 221465.13 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1243.44 | 12315.29 | 29-MAY-18:00 | 221465.13 | 02-JAN-07:10 |
Heating:Electricity | 94.81 | 0.00 | 01-JAN-10:00 | 180407.71 | 02-JAN-06:30 |
General:Heating:Electricity | 94.81 | 0.00 | 01-JAN-10:00 | 180407.71 | 02-JAN-06:30 |
Fans:Electricity | 71.23 | 0.00 | 01-JAN-10:00 | 26438.00 | 10-AUG-15:10 |
General:Fans:Electricity | 71.23 | 0.00 | 01-JAN-10:00 | 26438.00 | 10-AUG-15:10 |
ExteriorLights:Electricity | 51.64 | 0.00 | 01-JAN-08:10 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 51.64 | 0.00 | 01-JAN-08:10 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 74.61 | 0.00 | 01-JAN-00:10 | 56870.60 | 29-AUG-15:30 |
General:Cooling:Electricity | 74.61 | 0.00 | 01-JAN-00:10 | 56870.60 | 29-AUG-15:30 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-08:10 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-08:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-08:10 |
WIRED_LTG_ELECTRICITY | 6.57 | 0.00 | 01-JAN-00:10 | 702.61 | 02-JAN-16:40 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 237.53 | 1886.44 | 04-JAN-06:20 | 61495.77 | 26-DEC-08:20 |
NaturalGas:HVAC | 105.50 | 0.00 | 01-JAN-00:40 | 53220.10 | 07-JAN-08:00 |
Heating:NaturalGas | 105.50 | 0.00 | 01-JAN-00:40 | 53220.10 | 07-JAN-08:00 |
General:Heating:NaturalGas | 105.50 | 0.00 | 01-JAN-00:40 | 53220.10 | 07-JAN-08:00 |
NaturalGas:Plant | 132.03 | 1886.44 | 03-JAN-08:10 | 10123.74 | 08-FEB-12:10 |
WaterSystems:NaturalGas | 132.03 | 1886.44 | 03-JAN-08:10 | 10123.74 | 08-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 132.03 | 1886.44 | 03-JAN-08:10 | 10123.74 | 08-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1414.22 | 0.00 | 01-JAN-19:30 | 368843.18 | 10-AUG-15:20 |
EnergyTransfer:Building | 882.96 | 0.00 | 01-JAN-10:00 | 173635.38 | 02-JAN-06:30 |
EnergyTransfer:Zone:CORE_BOTTOM | 204.56 | 0.00 | 01-JAN-00:10 | 25384.90 | 14-AUG-08:00 |
Heating:EnergyTransfer | 83.53 | 0.00 | 01-JAN-10:00 | 173635.38 | 02-JAN-06:30 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.21 | 0.00 | 01-JAN-00:10 | 16212.83 | 02-JAN-06:50 |
General:Heating:EnergyTransfer | 83.53 | 0.00 | 01-JAN-10:00 | 173635.38 | 02-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.21 | 0.00 | 01-JAN-00:10 | 16212.83 | 02-JAN-06:50 |
Cooling:EnergyTransfer | 799.43 | 0.00 | 01-JAN-00:10 | 155185.11 | 10-AUG-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 204.35 | 0.00 | 01-JAN-00:10 | 25384.90 | 14-AUG-08:00 |
General:Cooling:EnergyTransfer | 799.43 | 0.00 | 01-JAN-00:10 | 155185.11 | 10-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 204.35 | 0.00 | 01-JAN-00:10 | 25384.90 | 14-AUG-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 34.38 | 0.00 | 01-JAN-00:40 | 10176.22 | 02-JAN-06:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 14.67 | 0.00 | 01-JAN-00:40 | 10176.22 | 02-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 14.67 | 0.00 | 01-JAN-00:40 | 10176.22 | 02-JAN-06:30 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 19.72 | 0.00 | 01-JAN-00:10 | 9927.95 | 10-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 19.72 | 0.00 | 01-JAN-00:10 | 9927.95 | 10-AUG-14:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 17.49 | 0.00 | 01-JAN-00:10 | 8940.28 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 7.83 | 0.00 | 01-JAN-00:10 | 8940.28 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 7.83 | 0.00 | 01-JAN-00:10 | 8940.28 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 9.66 | 0.00 | 01-JAN-00:10 | 4604.48 | 14-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 9.66 | 0.00 | 01-JAN-00:10 | 4604.48 | 14-AUG-15:20 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 20.24 | 0.00 | 01-JAN-00:10 | 7788.83 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 6.00 | 0.00 | 01-JAN-00:10 | 7788.83 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 6.00 | 0.00 | 01-JAN-00:10 | 7788.83 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 14.24 | 0.00 | 01-JAN-00:10 | 5021.78 | 14-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 14.24 | 0.00 | 01-JAN-00:10 | 5021.78 | 14-AUG-15:50 |
EnergyTransfer:Zone:CORE_MID | 127.95 | 0.00 | 01-JAN-00:10 | 18440.25 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.77 | 0.00 | 01-JAN-00:10 | 18440.25 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.77 | 0.00 | 01-JAN-00:10 | 18440.25 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_MID | 127.17 | 0.00 | 01-JAN-00:10 | 17043.70 | 14-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 127.17 | 0.00 | 01-JAN-00:10 | 17043.70 | 14-AUG-14:00 |
EnergyTransfer:Zone:CORE_TOP | 117.03 | 0.00 | 01-JAN-00:40 | 28154.48 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 3.52 | 0.00 | 01-JAN-00:40 | 28154.48 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 3.52 | 0.00 | 01-JAN-00:40 | 28154.48 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 113.51 | 0.00 | 01-JAN-00:10 | 18625.53 | 24-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 113.51 | 0.00 | 01-JAN-00:10 | 18625.53 | 24-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 28.99 | 0.00 | 01-JAN-00:40 | 8087.14 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 7.36 | 0.00 | 01-JAN-00:40 | 8087.14 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 7.36 | 0.00 | 01-JAN-00:40 | 8087.14 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 21.63 | 0.00 | 01-JAN-00:10 | 6264.29 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 21.63 | 0.00 | 01-JAN-00:10 | 6264.29 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 26.34 | 0.00 | 01-JAN-00:40 | 8932.60 | 31-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.35 | 0.00 | 01-JAN-00:40 | 7281.39 | 02-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.35 | 0.00 | 01-JAN-00:40 | 7281.39 | 02-JAN-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 22.00 | 0.00 | 01-JAN-00:10 | 8932.60 | 31-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 22.00 | 0.00 | 01-JAN-00:10 | 8932.60 | 31-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 45.56 | 0.00 | 01-JAN-00:40 | 13664.33 | 04-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.47 | 0.00 | 01-JAN-00:40 | 11188.89 | 02-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.47 | 0.00 | 01-JAN-00:40 | 11188.89 | 02-JAN-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 40.10 | 0.00 | 01-JAN-00:10 | 13664.33 | 04-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 40.10 | 0.00 | 01-JAN-00:10 | 13664.33 | 04-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 27.13 | 0.00 | 01-JAN-00:40 | 9722.56 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.61 | 0.00 | 01-JAN-00:40 | 7249.28 | 02-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.61 | 0.00 | 01-JAN-00:40 | 7249.28 | 02-JAN-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 22.53 | 0.00 | 01-JAN-00:10 | 9722.56 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 22.53 | 0.00 | 01-JAN-00:10 | 9722.56 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 23.20 | 0.00 | 01-JAN-00:10 | 6506.89 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.86 | 0.00 | 01-JAN-00:10 | 6506.89 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.86 | 0.00 | 01-JAN-00:10 | 6506.89 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.34 | 0.00 | 01-JAN-00:10 | 4782.13 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.34 | 0.00 | 01-JAN-00:10 | 4782.13 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 22.69 | 0.00 | 01-JAN-00:10 | 7283.10 | 24-JUL-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.68 | 0.00 | 01-JAN-00:10 | 5880.57 | 02-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.68 | 0.00 | 01-JAN-00:10 | 5880.57 | 02-JAN-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 21.01 | 0.00 | 01-JAN-00:10 | 7283.10 | 24-JUL-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 21.01 | 0.00 | 01-JAN-00:10 | 7283.10 | 24-JUL-08:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 43.10 | 0.00 | 01-JAN-00:10 | 12848.29 | 10-AUG-16:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 14.27 | 0.00 | 01-JAN-00:10 | 10806.13 | 26-DEC-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 14.27 | 0.00 | 01-JAN-00:10 | 10806.13 | 26-DEC-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 28.84 | 0.00 | 01-JAN-00:10 | 12848.29 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 28.84 | 0.00 | 01-JAN-00:10 | 12848.29 | 10-AUG-16:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 22.80 | 0.00 | 01-JAN-00:10 | 7866.99 | 31-JUL-17:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.69 | 0.00 | 01-JAN-00:10 | 5708.16 | 02-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.69 | 0.00 | 01-JAN-00:10 | 5708.16 | 02-JAN-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 21.11 | 0.00 | 01-JAN-00:10 | 7866.99 | 31-JUL-17:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 21.11 | 0.00 | 01-JAN-00:10 | 7866.99 | 31-JUL-17:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 26.92 | 0.00 | 01-JAN-00:10 | 7121.69 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.77 | 0.00 | 01-JAN-00:10 | 7121.69 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.77 | 0.00 | 01-JAN-00:10 | 7121.69 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 24.14 | 0.00 | 01-JAN-00:10 | 5736.49 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 24.14 | 0.00 | 01-JAN-00:10 | 5736.49 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 23.73 | 0.00 | 01-JAN-00:10 | 8965.59 | 31-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.71 | 0.00 | 01-JAN-00:10 | 6045.99 | 02-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.71 | 0.00 | 01-JAN-00:10 | 6045.99 | 02-JAN-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 22.02 | 0.00 | 01-JAN-00:10 | 8965.59 | 31-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 22.02 | 0.00 | 01-JAN-00:10 | 8965.59 | 31-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 45.08 | 0.00 | 01-JAN-00:10 | 13483.65 | 04-OCT-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.02 | 0.00 | 01-JAN-00:10 | 9244.34 | 02-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.02 | 0.00 | 01-JAN-00:10 | 9244.34 | 02-JAN-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 43.06 | 0.00 | 01-JAN-00:10 | 13483.65 | 04-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 43.06 | 0.00 | 01-JAN-00:10 | 13483.65 | 04-OCT-12:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 25.77 | 0.00 | 01-JAN-00:10 | 9255.31 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.75 | 0.00 | 01-JAN-00:10 | 5965.55 | 02-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.75 | 0.00 | 01-JAN-00:10 | 5965.55 | 02-JAN-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 24.02 | 0.00 | 01-JAN-00:10 | 9255.31 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 24.02 | 0.00 | 01-JAN-00:10 | 9255.31 | 10-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 50.33 | 0.00 | 01-JAN-00:10 | 6131.02 | 13-FEB-12:10 |
PlantLoopHeatingDemand:Plant | 50.33 | 0.00 | 01-JAN-00:10 | 6131.02 | 13-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 50.33 | 0.00 | 01-JAN-00:10 | 6131.02 | 13-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 50.33 | 0.00 | 01-JAN-00:10 | 6131.02 | 13-FEB-12:10 |
EnergyTransfer:HVAC | 480.93 | 0.00 | 01-JAN-10:00 | 209614.79 | 10-AUG-15:20 |
HeatingCoils:EnergyTransfer | 179.21 | 0.00 | 01-JAN-10:00 | 188698.82 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 301.73 | 0.00 | 01-JAN-00:10 | 209614.79 | 10-AUG-15:20 |
EnergyTransfer:Plant | 50.33 | 0.00 | 01-JAN-00:10 | 6131.02 | 13-FEB-12:10 |
WaterSystems:EnergyTransfer | 50.33 | 0.00 | 01-JAN-00:10 | 6131.02 | 13-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 50.33 | 0.00 | 01-JAN-00:10 | 6131.02 | 13-FEB-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.212 | -204.345 | 0.000 | 0.000 | 32.916 | 55.599 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -120.549 |
CORE_MID | 0.000 | 0.000 | 0.774 | -127.172 | 0.000 | 0.000 | 34.114 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -78.740 |
CORE_TOP | 0.000 | 0.000 | 3.519 | -113.509 | 0.000 | 0.000 | 34.900 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -95.934 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 7.355 | -21.633 | 0.000 | 0.000 | 7.578 | 6.927 | 24.333 | 13.987 | 0.000 | 0.019 | 0.001 | 0.000 | -27.863 | 0.000 | -6.884 | -3.820 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 4.347 | -21.998 | 0.000 | 0.000 | 4.729 | 4.339 | 15.404 | 26.375 | 0.000 | 0.011 | 0.000 | 0.000 | -18.054 | 0.000 | -4.658 | -10.494 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 5.467 | -40.095 | 0.000 | 0.000 | 7.408 | 6.784 | 24.332 | 57.005 | 0.000 | 0.016 | 0.001 | 0.000 | -27.710 | 0.000 | -7.178 | -26.029 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 4.606 | -22.526 | 0.000 | 0.000 | 4.766 | 4.331 | 15.403 | 28.483 | 0.000 | 0.010 | 0.000 | 0.000 | -18.635 | 0.000 | -4.709 | -11.731 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 2.856 | -20.341 | 0.000 | 0.000 | 7.520 | 6.904 | 24.333 | 14.157 | 0.000 | 0.012 | 0.001 | 0.000 | -29.275 | 0.000 | -3.882 | -2.284 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 1.676 | -21.010 | 0.000 | 0.000 | 4.681 | 4.329 | 15.404 | 26.425 | 0.000 | 0.006 | 0.000 | 0.000 | -19.198 | 0.000 | -2.663 | -9.650 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 14.266 | -28.837 | 0.000 | 0.000 | 7.540 | 6.770 | 24.332 | 57.502 | 0.000 | 0.388 | 0.001 | 0.000 | -29.420 | 0.000 | -35.615 | -16.927 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 1.694 | -21.106 | 0.000 | 0.000 | 4.706 | 4.321 | 15.403 | 28.622 | 0.000 | 0.006 | 0.001 | 0.000 | -19.886 | 0.000 | -2.694 | -11.066 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 2.773 | -24.143 | 0.000 | 0.000 | 7.466 | 6.927 | 24.333 | 13.676 | 0.000 | 0.017 | 4.802 | 0.000 | -29.743 | 0.000 | -6.108 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.712 | -22.015 | 0.000 | 0.000 | 3.446 | 4.339 | 15.404 | 26.062 | 0.000 | 0.009 | 0.002 | 0.000 | -19.234 | 0.000 | -4.136 | -5.586 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 2.018 | -43.062 | 0.000 | 0.000 | 7.296 | 6.784 | 24.332 | 56.653 | 0.000 | 0.013 | 0.000 | 0.000 | -29.488 | 0.000 | -6.357 | -18.189 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 1.751 | -24.020 | 0.000 | 0.000 | 4.694 | 4.331 | 15.403 | 28.296 | 0.000 | 0.009 | 0.000 | 0.000 | -19.861 | 0.000 | -4.171 | -6.432 |
TOPFLOOR_PLENUM | 14.667 | -19.716 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.011 | 15.675 | 0.000 | 0.000 | 0.000 | -10.638 | -0.002 |
MIDFLOOR_PLENUM | 7.831 | -9.659 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.020 | 12.367 | 0.000 | 0.000 | 0.000 | -10.560 | -0.000 |
FIRSTFLOOR_PLENUM | 6.003 | -14.239 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.015 | 16.831 | 0.000 | 0.000 | 0.000 | -8.610 | -0.000 |
Total Facility | 28.501 | -43.614 | 55.027 | -755.811 | 0.000 | 0.000 | 173.762 | 233.882 | 705.434 | 377.242 | 0.000 | 0.563 | 49.682 | 0.000 | -288.368 | 0.000 | -118.862 | -417.435 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 14-AUG-05:12 | 0.00 | 0.00 | 0.00 | -41281.48 | 0.00 | 0.00 | 318.54 | 548.43 | 4989.51 | 0.00 | 0.00 | 0.00 | 35425.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 14-AUG-05:12 | 0.00 | 0.00 | 0.00 | -30388.28 | 0.00 | 0.00 | 327.84 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 26486.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 14-AUG-06:02 | 0.00 | 0.00 | 0.00 | -27820.93 | 0.00 | 0.00 | 714.45 | 1645.36 | 3025.92 | 0.00 | 0.00 | 0.00 | 22435.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -6264.28 | 0.00 | 0.00 | 737.22 | 496.34 | 1435.25 | 3576.41 | 0.00 | 44.75 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25.69 |
PERIMETER_TOP_ZN_2 | 25-JUN-08:52 | 0.00 | 0.00 | 0.00 | -13438.63 | 0.00 | 0.00 | 15.75 | 17.46 | 302.86 | 9398.65 | 0.00 | 0.00 | 3840.28 | 0.00 | -0.00 | 0.00 | -136.36 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-12:52 | 0.00 | 0.00 | 0.00 | -21737.87 | 0.00 | 0.00 | 22.17 | 27.57 | 478.41 | 15027.14 | 0.00 | 0.00 | 6400.66 | 0.00 | -0.00 | 0.00 | -218.09 | 0.00 |
PERIMETER_TOP_ZN_4 | 14-MAY-16:31 | 0.00 | 0.00 | 0.00 | -16193.57 | 0.00 | 0.00 | 13.08 | 17.46 | 302.86 | 11596.03 | 0.00 | 0.00 | 4501.24 | 0.00 | -0.00 | 0.00 | -237.09 | 0.00 |
PERIMETER_BOT_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -4782.14 | 0.00 | 0.00 | 737.22 | 496.34 | 1435.25 | 3623.65 | 0.00 | 23.98 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1534.31 |
PERIMETER_BOT_ZN_2 | 25-JUN-08:52 | 0.00 | 0.00 | 0.00 | -9878.21 | 0.00 | 0.00 | 17.31 | 17.46 | 302.86 | 9514.53 | 0.00 | 0.00 | 95.54 | 0.00 | -0.00 | 0.00 | -69.49 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-SEP-13:42 | 0.00 | 0.00 | 0.00 | -15472.82 | 0.00 | 0.00 | 24.36 | 27.57 | 478.41 | 13735.56 | 0.00 | 0.00 | 1270.60 | 0.00 | -0.00 | 0.00 | -63.69 | 0.00 |
PERIMETER_BOT_ZN_4 | 14-MAY-17:11 | 0.00 | 0.00 | 0.00 | -12780.69 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 10788.45 | 0.00 | 0.00 | 1829.96 | 0.00 | -0.00 | 0.00 | -99.60 | 0.00 |
PERIMETER_MID_ZN_3 | 24-JUL-06:03 | 0.00 | 0.00 | 0.00 | -7041.67 | 0.00 | 0.00 | 145.94 | 165.45 | 637.89 | 2162.64 | 0.00 | 0.00 | 3958.21 | 0.00 | -0.00 | 0.00 | -28.46 | 0.00 |
PERIMETER_MID_ZN_2 | 30-JUL-08:52 | 0.00 | 0.00 | 0.00 | -14399.03 | 0.00 | 0.00 | 14.17 | 17.46 | 302.86 | 10329.25 | 0.00 | 0.00 | 3835.51 | 0.00 | -0.00 | 0.00 | -100.21 | 0.00 |
PERIMETER_MID_ZN_1 | 30-JUL-12:12 | 0.00 | 0.00 | 0.00 | -19111.84 | 0.00 | 0.00 | 24.52 | 27.57 | 478.41 | 13000.73 | 0.00 | 0.00 | 5622.52 | 0.00 | -0.00 | 0.00 | -41.92 | 0.00 |
PERIMETER_MID_ZN_4 | 30-JUL-17:31 | 0.00 | 0.00 | 0.00 | -15587.67 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 11358.59 | 0.00 | 0.00 | 4029.57 | 0.00 | -0.00 | 0.00 | -62.37 | 0.00 |
TOPFLOOR_PLENUM | 10-AUG-14:50 | 0.00 | -9927.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.42 | 9886.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 14-AUG-15:20 | 0.00 | -4604.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.32 | 4582.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 14-AUG-06:13 | 0.00 | -5063.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5123.62 | 0.00 | -0.00 | 0.00 | -60.35 | 0.00 |
Total Facility | 14-AUG-06:02 | 0.00 | -3334.16 | 0.00 | -153623.66 | 0.00 | 0.00 | 3569.74 | 6631.45 | 21098.80 | 18532.48 | 0.00 | 0.00 | 117449.46 | 0.00 | -2808.93 | 0.00 | -7515.18 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-06:11 | 0.00 | 0.00 | 17811.83 | 0.00 | 0.00 | 0.00 | 508.78 | 548.43 | 4989.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23858.55 |
CORE_MID | 02-JAN-06:11 | 0.00 | 0.00 | 20143.84 | 0.00 | 0.00 | 0.00 | 528.23 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24246.42 |
CORE_TOP | 02-JAN-06:11 | 0.00 | 0.00 | 30464.69 | 0.00 | 0.00 | 0.00 | 536.72 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -34575.77 |
PERIMETER_TOP_ZN_3 | 17-JAN-05:11 | 0.00 | 0.00 | 8835.02 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1583.44 | 0.00 | -316.39 | -7494.63 |
PERIMETER_TOP_ZN_2 | 17-JAN-05:11 | 0.00 | 0.00 | 9760.06 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1053.83 | 0.00 | -215.86 | -8844.53 |
PERIMETER_TOP_ZN_1 | 17-JAN-05:11 | 0.00 | 0.00 | 14823.32 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1557.75 | 0.00 | -324.34 | -13500.67 |
PERIMETER_TOP_ZN_4 | 17-JAN-05:11 | 0.00 | 0.00 | 9709.12 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1032.95 | 0.00 | -215.89 | -8814.44 |
PERIMETER_BOT_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 7000.77 | 0.00 | 0.00 | 0.00 | 113.18 | 115.61 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1079.96 | 0.00 | -77.42 | -6710.07 |
PERIMETER_BOT_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 7117.42 | 0.00 | 0.00 | 0.00 | 71.65 | 73.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -733.91 | 0.00 | -52.59 | -6879.58 |
PERIMETER_BOT_ZN_1 | 26-DEC-08:00 | 0.00 | 0.00 | 10805.48 | 0.00 | 0.00 | 0.00 | 227.40 | 346.86 | 637.88 | 0.00 | 0.00 | 0.00 | 4734.73 | 0.00 | -2074.61 | 0.00 | -14677.74 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 7052.38 | 0.00 | 0.00 | 0.00 | 71.65 | 73.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -718.51 | 0.00 | -52.57 | -6829.95 |
PERIMETER_MID_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 7709.36 | 0.00 | 0.00 | 0.00 | 113.18 | 115.61 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1086.70 | 0.00 | -121.85 | -7367.48 |
PERIMETER_MID_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 7525.93 | 0.00 | 0.00 | 0.00 | 71.65 | 73.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -740.82 | 0.00 | -82.75 | -7251.02 |
PERIMETER_MID_ZN_1 | 02-JAN-06:11 | 0.00 | 0.00 | 11392.13 | 0.00 | 0.00 | 0.00 | 113.18 | 115.61 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1112.71 | 0.00 | -123.90 | -11022.19 |
PERIMETER_MID_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 7478.79 | 0.00 | 0.00 | 0.00 | 71.65 | 73.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -723.54 | 0.00 | -82.72 | -7221.17 |
TOPFLOOR_PLENUM | 26-DEC-06:12 | 12282.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -45.54 | -12237.05 |
MIDFLOOR_PLENUM | 02-JAN-07:02 | 9078.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -172.44 | -8905.58 |
FIRSTFLOOR_PLENUM | 02-JAN-07:02 | 8890.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -138.51 | -8751.81 |
Total Facility | 02-JAN-06:11 | 7838.12 | 0.00 | 176610.32 | 0.00 | 0.00 | 0.00 | 2682.69 | 2778.13 | 17291.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10882.08 | 0.00 | -2812.44 | -193506.25 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.6331 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9362 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.2484 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.3568 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.5052 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9185 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.8166 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0761 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.6242 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0756 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.7526 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0773 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8306 | 2.8306 | 0.6369 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0502 | 2.0502 | 0.6376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0989 | 2.0989 | 0.6381 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6025 | 0.6025 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7757 | 0.7757 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1709 | 1.1709 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8572 | 0.8572 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4822 | 0.4822 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6431 | 0.6431 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9606 | 0.9606 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7167 | 0.7167 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5316 | 0.5316 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7779 | 0.7779 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0881 | 1.0881 | 0.1338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8006 | 0.8006 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.6331 | 4.9362 | 5.6331 | 1.0761 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.2484 | 4.3568 | 5.2484 | 1.0756 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.5052 | 4.9185 | 5.5052 | 1.0773 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4153 | 1.4153 | 0.6369 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0251 | 1.0251 | 0.6376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0495 | 1.0495 | 0.6381 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3012 | 0.3012 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3878 | 0.3878 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5855 | 0.5855 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4286 | 0.4286 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2411 | 0.2411 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3216 | 0.3216 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4803 | 0.4803 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3583 | 0.3583 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2658 | 0.2658 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3889 | 0.3889 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5440 | 0.5440 | 0.1338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4003 | 0.4003 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.8166 | 1.0761 | 1.0761 | 1.0761 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.6242 | 1.0756 | 1.0756 | 1.0756 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.7526 | 1.0773 | 1.0773 | 1.0773 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 209.67 |
Number of hours cooling loads not met | 56.17 |
Number of hours not met | 265.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 94.81 | 180407.71 | 105.50 | 53220.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 74.61 | 56870.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 233.88 | 25003.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 51.64 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.69 | 839.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 71.23 | 26438.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 132.03 | 10123.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1243.44 |
Natural Gas | 0.00 | 237.53 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1480.97 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.94 |
Space Heating | 19.03 |
Space Cooling | 14.98 |
Fans (All) | 14.30 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 249.58 |
Subtotal | 249.58 |
Natural Gas [MJ/m2] | |
Space Heating | 21.17 |
Service Water Heating | 26.50 |
Miscellaneous (All) | 47.68 |
Subtotal | 47.68 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 15.79 |
Space Heating | 13.53 |
Space Cooling | 5.04 |
Fans (All) | 4.81 |
Service Water Heating | 8.92 |
Receptacle Equipment | 47.63 |
Miscellaneous | 4.29 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 862. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8744.00 | 16.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8740.00 | 20.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8731.50 | 28.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8750.00 | 10.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8744.33 | 15.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8739.50 | 20.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8746.17 | 13.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8743.17 | 16.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8732.67 | 27.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8723.00 | 37.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8723.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 37.00 | 0.00 | 0.00 | 0.00 |
Average | 8748.54 | 11.46 | 0.00 | 0.00 | 0.00 |
Sum | 157473.67 | 206.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8672.67 | 87.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8745.33 | 14.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8740.83 | 19.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8726.67 | 33.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8724.33 | 35.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8745.33 | 14.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8734.83 | 25.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8718.17 | 41.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8756.17 | 3.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8740.00 | 20.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8730.17 | 29.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8727.17 | 32.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8731.33 | 28.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8672.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 87.33 | 0.00 | 0.00 | 0.00 |
Average | 8738.36 | 21.64 | 0.00 | 0.00 | 0.00 |
Sum | 157290.50 | 389.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128256.33 | 47.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128298.67 | 5.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 47.67 | 0.00 | 0.00 | 0.00 |
Average | 34140.39 | 2.94 | 0.00 | 0.00 | 0.00 |
Sum | 614527.00 | 53.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:05
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.859700E+10 | 13217.29 | 12-JAN-08:10 | 6.70 | 6.12 | 0.187296E+10 | 2606.65 | 20-JAN-10:09 | 4.18 | 2.79 |
February | 0.991905E+10 | 16363.21 | 28-FEB-08:10 | 10.60 | 10.00 | 0.177107E+10 | 2606.65 | 08-FEB-10:09 | 10.60 | 10.00 |
March | 0.151385E+11 | 17207.37 | 28-MAR-07:02 | 3.45 | 1.22 | 0.214781E+10 | 2606.67 | 09-MAR-14:09 | 3.45 | 1.22 |
April | 0.164586E+11 | 37579.89 | 28-APR-06:02 | 11.10 | 10.22 | 0.191391E+10 | 2606.67 | 27-APR-13:20 | 11.10 | 10.22 |
May | 0.212580E+11 | 38195.91 | 08-MAY-06:02 | 9.90 | 9.62 | 0.207580E+10 | 2606.68 | 05-MAY-09:09 | 9.90 | 9.62 |
June | 0.229139E+11 | 40941.21 | 12-JUN-05:12 | 14.40 | 13.42 | 0.207093E+10 | 2606.70 | 05-JUN-13:00 | 14.40 | 13.42 |
July | 0.232763E+11 | 41256.00 | 10-JUL-05:12 | 13.13 | 11.62 | 0.192619E+10 | 2606.65 | 20-JUL-13:20 | 26.30 | 16.68 |
August | 0.255755E+11 | 41280.04 | 14-AUG-05:12 | 15.33 | 13.50 | 0.216118E+10 | 2606.87 | 09-AUG-09:00 | 15.33 | 13.50 |
September | 0.212142E+11 | 41195.17 | 05-SEP-05:12 | 10.77 | 9.27 | 0.191876E+10 | 2606.66 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.173084E+11 | 37900.65 | 10-OCT-06:02 | 12.12 | 10.88 | 0.199034E+10 | 2606.65 | 05-OCT-09:00 | 12.12 | 10.88 |
November | 0.124941E+11 | 17325.58 | 06-NOV-09:00 | 12.80 | 9.29 | 0.195466E+10 | 2606.63 | 10-NOV-10:09 | 6.88 | 5.74 |
December | 0.101920E+11 | 15602.87 | 07-DEC-08:06 | 6.20 | 3.27 | 0.187468E+10 | 2606.66 | 13-DEC-14:09 | 7.10 | 5.11 |
Annual Sum or Average | 0.204345E+12 | 0.236783E+11 | ||||||||
Minimum of Months | 0.859700E+10 | 13217.29 | 3.45 | 1.22 | 0.177107E+10 | 2606.63 | 3.45 | 1.22 | ||
Maximum of Months | 0.255755E+11 | 41280.04 | 15.33 | 13.50 | 0.216118E+10 | 2606.87 | 26.30 | 16.68 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 | 4.99 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 42464625.75 | 1684.91 | 27-FEB-15:30 | 19.70 | 12.30 | 0.00 | 0.00 | 01-FEB-00:10 | 19.70 | 12.30 |
March | 0.354292E+09 | 2688.68 | 14-MAR-14:50 | 16.02 | 10.35 | 0.00 | 0.00 | 01-MAR-00:10 | 16.02 | 10.35 |
April | 0.132680E+10 | 8366.75 | 27-APR-14:30 | 26.65 | 17.06 | 0.00 | 0.00 | 01-APR-00:10 | 26.65 | 17.06 |
May | 0.256919E+10 | 8719.59 | 15-MAY-14:20 | 23.30 | 13.21 | 0.00 | 0.00 | 01-MAY-00:10 | 23.30 | 13.21 |
June | 0.339634E+10 | 8584.26 | 28-JUN-14:30 | 25.55 | 15.61 | 0.00 | 0.00 | 01-JUN-00:10 | 25.55 | 15.61 |
July | 0.458711E+10 | 9875.28 | 24-JUL-14:00 | 29.40 | 18.12 | 0.00 | 0.00 | 01-JUL-00:10 | 29.40 | 18.12 |
August | 0.449234E+10 | 9927.95 | 10-AUG-14:50 | 30.07 | 18.95 | 0.00 | 0.00 | 01-AUG-00:10 | 30.07 | 18.95 |
September | 0.232790E+10 | 7710.57 | 14-SEP-14:40 | 23.90 | 17.01 | 0.00 | 0.00 | 01-SEP-00:10 | 23.90 | 17.01 |
October | 0.578952E+09 | 5342.16 | 04-OCT-14:50 | 21.60 | 11.48 | 0.00 | 0.00 | 01-OCT-00:10 | 21.60 | 11.48 |
November | 40484860.12 | 2234.73 | 04-NOV-14:30 | 21.10 | 15.94 | 0.00 | 0.00 | 01-NOV-00:10 | 21.10 | 15.94 |
December | 737052.29 | 168.60 | 02-DEC-15:10 | 11.52 | 5.36 | 0.00 | 0.00 | 01-DEC-00:10 | 11.52 | 5.36 |
Annual Sum or Average | 0.197166E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 5.92 | 4.99 | 0.00 | 0.00 | 5.92 | 4.99 | ||
Maximum of Months | 0.458711E+10 | 9927.95 | 30.07 | 18.95 | 0.00 | 0.00 | 30.07 | 18.95 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2909014.12 | 1627.93 | 14-JAN-06:11 | 2.20 | 1.14 | 0.00 | 0.00 | 01-JAN-00:10 | 2.20 | 1.14 |
February | 28684023.27 | 1419.48 | 18-FEB-06:01 | -1.8 | -2.6 | 0.00 | 0.00 | 01-FEB-00:10 | -1.8 | -2.6 |
March | 0.123222E+09 | 2395.55 | 01-MAR-07:02 | -0.1 | -1.7 | 0.00 | 0.00 | 01-MAR-00:10 | -0.1 | -1.7 |
April | 0.403812E+09 | 2855.51 | 27-APR-16:00 | 27.20 | 16.90 | 0.00 | 0.00 | 01-APR-00:10 | 27.20 | 16.90 |
May | 0.941510E+09 | 3142.25 | 15-MAY-15:20 | 23.50 | 12.70 | 0.00 | 0.00 | 01-MAY-00:10 | 23.50 | 12.70 |
June | 0.161978E+10 | 3287.64 | 28-JUN-15:50 | 26.10 | 16.17 | 0.00 | 0.00 | 01-JUN-00:10 | 26.10 | 16.17 |
July | 0.230032E+10 | 4504.71 | 31-JUL-15:20 | 28.50 | 19.00 | 0.00 | 0.00 | 01-JUL-00:10 | 28.50 | 19.00 |
August | 0.260577E+10 | 4604.48 | 14-AUG-15:20 | 27.17 | 17.34 | 0.00 | 0.00 | 01-AUG-00:10 | 27.17 | 17.34 |
September | 0.129129E+10 | 3584.67 | 11-SEP-15:30 | 23.30 | 15.99 | 0.00 | 0.00 | 01-SEP-00:10 | 23.30 | 15.99 |
October | 0.301902E+09 | 2116.68 | 04-OCT-15:50 | 21.20 | 11.42 | 0.00 | 0.00 | 01-OCT-00:10 | 21.20 | 11.42 |
November | 36224728.68 | 1212.04 | 22-NOV-06:11 | 3.13 | 2.35 | 0.00 | 0.00 | 01-NOV-00:10 | 3.13 | 2.35 |
December | 3516053.92 | 1292.06 | 23-DEC-06:11 | 3.90 | 3.43 | 0.00 | 0.00 | 01-DEC-00:10 | 3.90 | 3.43 |
Annual Sum or Average | 0.965894E+10 | 0.00 | ||||||||
Minimum of Months | 2909014.12 | 1212.04 | -1.8 | -2.6 | 0.00 | 0.00 | -1.8 | -2.6 | ||
Maximum of Months | 0.260577E+10 | 4604.48 | 28.50 | 19.00 | 0.00 | 0.00 | 28.50 | 19.00 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22586108.28 | 2191.10 | 13-JAN-06:11 | 3.13 | 2.22 | 0.00 | 0.00 | 01-JAN-00:10 | 3.13 | 2.22 |
February | 72141438.21 | 2305.48 | 10-FEB-07:02 | 0.60 | -0.1 | 0.00 | 0.00 | 01-FEB-00:10 | 0.60 | -0.1 |
March | 0.287151E+09 | 3065.64 | 01-MAR-07:02 | -0.1 | -1.7 | 0.00 | 0.00 | 01-MAR-00:10 | -0.1 | -1.7 |
April | 0.759475E+09 | 3254.11 | 27-APR-16:00 | 27.20 | 16.90 | 0.00 | 0.00 | 01-APR-00:10 | 27.20 | 16.90 |
May | 0.156621E+10 | 3535.21 | 15-MAY-16:00 | 23.90 | 12.85 | 0.00 | 0.00 | 01-MAY-00:10 | 23.90 | 12.85 |
June | 0.229330E+10 | 3696.79 | 28-JUN-16:00 | 26.10 | 16.29 | 0.00 | 0.00 | 01-JUN-00:10 | 26.10 | 16.29 |
July | 0.298700E+10 | 4855.92 | 24-JUL-15:10 | 30.32 | 18.75 | 0.00 | 0.00 | 01-JUL-00:10 | 30.32 | 18.75 |
August | 0.339507E+10 | 5063.10 | 14-AUG-06:13 | 15.73 | 13.91 | 0.00 | 0.00 | 01-AUG-00:10 | 15.73 | 13.91 |
September | 0.203939E+10 | 4298.95 | 11-SEP-16:00 | 23.30 | 16.14 | 0.00 | 0.00 | 01-SEP-00:10 | 23.30 | 16.14 |
October | 0.690003E+09 | 2993.00 | 04-OCT-16:00 | 21.10 | 11.40 | 0.00 | 0.00 | 01-OCT-00:10 | 21.10 | 11.40 |
November | 92032194.24 | 1880.53 | 16-NOV-07:03 | 3.48 | 2.25 | 0.00 | 0.00 | 01-NOV-00:10 | 3.48 | 2.25 |
December | 34758723.44 | 1871.08 | 20-DEC-06:11 | 5.93 | 5.05 | 0.00 | 0.00 | 01-DEC-00:10 | 5.93 | 5.05 |
Annual Sum or Average | 0.142391E+11 | 0.00 | ||||||||
Minimum of Months | 22586108.28 | 1871.08 | -0.1 | -1.7 | 0.00 | 0.00 | -0.1 | -1.7 | ||
Maximum of Months | 0.339507E+10 | 5063.10 | 30.32 | 18.75 | 0.00 | 0.00 | 30.32 | 18.75 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.554120E+10 | 5871.26 | 12-JAN-17:00 | 7.20 | 5.41 | 0.160802E+10 | 2394.43 | 12-JAN-14:00 | 7.20 | 5.41 |
February | 0.617862E+10 | 7173.82 | 28-FEB-17:00 | 14.40 | 10.82 | 0.155453E+10 | 2606.46 | 28-FEB-14:00 | 14.40 | 10.82 |
March | 0.870512E+10 | 8925.70 | 02-MAR-17:00 | 12.80 | 8.57 | 0.203087E+10 | 2606.61 | 03-MAR-14:09 | 8.40 | 8.40 |
April | 0.982131E+10 | 14026.84 | 27-APR-16:00 | 27.20 | 16.90 | 0.187113E+10 | 2607.88 | 10-APR-13:30 | 27.20 | 16.90 |
May | 0.132074E+11 | 14761.86 | 08-MAY-06:02 | 9.90 | 9.62 | 0.206086E+10 | 2606.66 | 05-MAY-09:09 | 9.90 | 9.62 |
June | 0.148387E+11 | 27256.90 | 12-JUN-06:02 | 14.60 | 13.50 | 0.206328E+10 | 2606.68 | 09-JUN-13:09 | 14.60 | 13.50 |
July | 0.156233E+11 | 29810.80 | 31-JUL-05:12 | 17.40 | 14.58 | 0.192036E+10 | 2606.65 | 31-JUL-09:20 | 22.57 | 17.16 |
August | 0.170135E+11 | 30388.77 | 14-AUG-05:12 | 15.33 | 13.50 | 0.215564E+10 | 2606.78 | 09-AUG-09:00 | 15.33 | 13.50 |
September | 0.131254E+11 | 27283.94 | 11-SEP-06:01 | 12.07 | 10.69 | 0.190763E+10 | 2606.65 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.975655E+10 | 13507.27 | 04-OCT-16:00 | 21.10 | 11.40 | 0.193204E+10 | 2606.65 | 12-OCT-09:09 | 9.18 | 7.86 |
November | 0.712702E+10 | 7847.05 | 06-NOV-17:00 | 11.70 | 10.80 | 0.176466E+10 | 2606.59 | 06-NOV-14:09 | 11.70 | 10.80 |
December | 0.623391E+10 | 6192.81 | 06-DEC-16:10 | 2.93 | 2.59 | 0.161060E+10 | 2503.15 | 06-DEC-14:00 | 2.93 | 2.59 |
Annual Sum or Average | 0.127172E+12 | 0.224796E+11 | ||||||||
Minimum of Months | 0.554120E+10 | 5871.26 | 2.93 | 2.59 | 0.155453E+10 | 2394.43 | 2.93 | 2.59 | ||
Maximum of Months | 0.170135E+11 | 30388.77 | 27.20 | 16.90 | 0.215564E+10 | 2607.88 | 27.20 | 17.16 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.374290E+10 | 5502.10 | 11-JAN-17:00 | 12.20 | 9.27 | 0.152598E+10 | 2274.73 | 11-JAN-14:00 | 12.20 | 9.27 |
February | 0.484494E+10 | 6482.67 | 28-FEB-17:00 | 14.40 | 10.82 | 0.145772E+10 | 2562.45 | 28-FEB-14:00 | 14.40 | 10.82 |
March | 0.768782E+10 | 8056.41 | 02-MAR-17:00 | 12.80 | 8.57 | 0.190461E+10 | 2606.56 | 02-MAR-14:00 | 12.80 | 8.57 |
April | 0.898724E+10 | 15449.30 | 27-APR-15:40 | 27.20 | 17.03 | 0.180544E+10 | 2606.66 | 27-APR-13:20 | 27.20 | 17.03 |
May | 0.123103E+11 | 16471.23 | 15-MAY-15:40 | 23.70 | 12.77 | 0.203482E+10 | 2607.37 | 23-MAY-09:20 | 10.57 | 8.99 |
June | 0.142409E+11 | 16839.33 | 28-JUN-16:00 | 26.10 | 16.29 | 0.205211E+10 | 2606.68 | 09-JUN-13:09 | 26.10 | 16.29 |
July | 0.153600E+11 | 20647.75 | 24-JUL-06:03 | 17.48 | 14.11 | 0.191308E+10 | 2606.65 | 20-JUL-13:20 | 17.48 | 14.11 |
August | 0.164367E+11 | 27822.08 | 14-AUG-06:02 | 15.47 | 13.75 | 0.214811E+10 | 2606.77 | 09-AUG-09:00 | 15.47 | 13.75 |
September | 0.118383E+11 | 16336.25 | 11-SEP-15:50 | 23.30 | 16.09 | 0.188320E+10 | 2606.65 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.832193E+10 | 13391.75 | 04-OCT-16:00 | 21.10 | 11.40 | 0.183767E+10 | 2606.62 | 05-OCT-09:20 | 12.43 | 7.97 |
November | 0.555004E+10 | 6349.14 | 02-NOV-16:00 | 13.30 | 10.88 | 0.163314E+10 | 2519.51 | 06-NOV-14:00 | 11.10 | 10.22 |
December | 0.418829E+10 | 5727.48 | 05-DEC-16:15 | 6.10 | 4.53 | 0.149823E+10 | 2352.91 | 06-DEC-14:00 | 5.00 | 4.36 |
Annual Sum or Average | 0.113509E+12 | 0.216941E+11 | ||||||||
Minimum of Months | 0.374290E+10 | 5502.10 | 6.10 | 4.53 | 0.145772E+10 | 2274.73 | 5.00 | 4.36 | ||
Maximum of Months | 0.164367E+11 | 27822.08 | 27.20 | 17.03 | 0.214811E+10 | 2607.37 | 27.20 | 17.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116555E+09 | 988.01 | 11-JAN-16:20 | 13.67 | 10.10 | 0.305760E+09 | 432.77 | 11-JAN-14:00 | 13.67 | 10.10 |
February | 0.388831E+09 | 1257.73 | 28-FEB-15:00 | 13.90 | 10.81 | 0.285136E+09 | 514.11 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.108110E+10 | 1340.44 | 10-MAR-14:50 | 16.20 | 11.59 | 0.364490E+09 | 541.12 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.163502E+10 | 4444.80 | 27-APR-15:20 | 27.20 | 17.16 | 0.356869E+09 | 549.50 | 27-APR-13:20 | 27.20 | 17.16 |
May | 0.268963E+10 | 4737.77 | 15-MAY-14:30 | 23.30 | 13.06 | 0.415975E+09 | 549.50 | 05-MAY-09:20 | 23.30 | 13.06 |
June | 0.337981E+10 | 5096.03 | 21-JUN-15:30 | 24.70 | 15.68 | 0.427292E+09 | 549.51 | 09-JUN-13:09 | 24.70 | 15.68 |
July | 0.393534E+10 | 6264.29 | 24-JUL-15:00 | 30.60 | 18.78 | 0.400604E+09 | 549.50 | 20-JUL-13:20 | 30.60 | 18.78 |
August | 0.402870E+10 | 5623.08 | 09-AUG-15:20 | 28.47 | 18.71 | 0.448819E+09 | 549.53 | 09-AUG-09:00 | 28.47 | 18.71 |
September | 0.238133E+10 | 4237.67 | 12-SEP-14:50 | 24.40 | 16.68 | 0.383405E+09 | 549.49 | 15-SEP-09:20 | 16.70 | 14.42 |
October | 0.131233E+10 | 2569.79 | 04-OCT-15:20 | 21.50 | 11.47 | 0.354410E+09 | 549.49 | 03-OCT-13:20 | 21.50 | 11.47 |
November | 0.531225E+09 | 1196.23 | 02-NOV-14:40 | 13.67 | 11.26 | 0.314156E+09 | 492.90 | 02-NOV-13:00 | 13.67 | 11.26 |
December | 0.153000E+09 | 920.08 | 05-DEC-15:10 | 9.35 | 6.62 | 0.295259E+09 | 418.09 | 05-DEC-14:00 | 9.35 | 6.62 |
Annual Sum or Average | 0.216329E+11 | 0.435218E+10 | ||||||||
Minimum of Months | 0.116555E+09 | 920.08 | 9.35 | 6.62 | 0.285136E+09 | 418.09 | 9.35 | 6.62 | ||
Maximum of Months | 0.402870E+10 | 6264.29 | 30.60 | 18.78 | 0.448819E+09 | 549.53 | 30.60 | 18.78 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114704E+09 | 635.42 | 11-JAN-16:10 | 14.03 | 10.30 | 0.194073E+09 | 278.05 | 11-JAN-14:00 | 14.03 | 10.30 |
February | 0.341555E+09 | 845.13 | 27-FEB-15:50 | 19.50 | 12.39 | 0.186682E+09 | 336.75 | 27-FEB-14:00 | 19.50 | 12.39 |
March | 0.909741E+09 | 2637.69 | 14-MAR-09:50 | 9.63 | 7.44 | 0.246956E+09 | 347.88 | 02-MAR-10:20 | 9.63 | 7.44 |
April | 0.179825E+10 | 6705.12 | 27-APR-09:20 | 18.17 | 12.47 | 0.239886E+09 | 347.88 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.267400E+10 | 10817.48 | 14-MAY-09:13 | 17.43 | 11.77 | 0.268391E+09 | 348.01 | 23-MAY-09:20 | 10.57 | 8.99 |
June | 0.363045E+10 | 13439.80 | 25-JUN-08:52 | 16.70 | 12.03 | 0.273316E+09 | 347.88 | 09-JUN-13:09 | 16.70 | 12.03 |
July | 0.395196E+10 | 12788.35 | 30-JUL-09:02 | 20.87 | 15.88 | 0.255073E+09 | 348.41 | 31-JUL-09:00 | 23.30 | 17.69 |
August | 0.428001E+10 | 12770.74 | 13-AUG-09:12 | 21.50 | 16.14 | 0.286151E+09 | 348.38 | 10-AUG-09:00 | 21.50 | 16.14 |
September | 0.254178E+10 | 10503.01 | 10-SEP-10:13 | 17.77 | 13.72 | 0.247515E+09 | 347.88 | 11-SEP-09:00 | 18.90 | 14.30 |
October | 0.118069E+10 | 4718.12 | 04-OCT-09:20 | 16.13 | 10.66 | 0.235743E+09 | 347.88 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.401598E+09 | 837.23 | 04-NOV-10:40 | 17.23 | 14.47 | 0.202194E+09 | 330.80 | 02-NOV-13:00 | 17.23 | 14.47 |
December | 0.173043E+09 | 676.46 | 05-DEC-10:40 | 7.77 | 5.32 | 0.188337E+09 | 290.86 | 05-DEC-10:50 | 8.03 | 5.37 |
Annual Sum or Average | 0.219978E+11 | 0.282432E+10 | ||||||||
Minimum of Months | 0.114704E+09 | 635.42 | 7.77 | 5.32 | 0.186682E+09 | 278.05 | 8.03 | 5.37 | ||
Maximum of Months | 0.428001E+10 | 13439.80 | 21.50 | 16.14 | 0.286151E+09 | 348.41 | 26.10 | 17.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.531556E+09 | 6682.90 | 20-JAN-13:30 | 6.70 | 4.72 | 0.321818E+09 | 549.49 | 20-JAN-14:50 | 7.12 | 4.90 |
February | 0.121947E+10 | 8650.31 | 27-FEB-14:30 | 19.15 | 11.80 | 0.313362E+09 | 549.49 | 27-FEB-14:00 | 20.00 | 12.17 |
March | 0.259015E+10 | 9911.12 | 14-MAR-13:40 | 15.20 | 10.17 | 0.395855E+09 | 549.50 | 02-MAR-14:00 | 15.20 | 10.17 |
April | 0.341868E+10 | 12055.66 | 27-APR-13:05 | 26.10 | 16.37 | 0.373307E+09 | 549.96 | 27-APR-13:50 | 26.10 | 16.74 |
May | 0.432173E+10 | 19332.30 | 14-MAY-15:12 | 23.30 | 12.32 | 0.419287E+09 | 549.51 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.474263E+10 | 11557.04 | 11-JUN-12:43 | 21.70 | 15.34 | 0.427183E+09 | 549.51 | 09-JUN-13:09 | 21.70 | 15.34 |
July | 0.589435E+10 | 18658.76 | 23-JUL-13:02 | 26.38 | 16.73 | 0.400776E+09 | 550.02 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.678296E+10 | 19211.91 | 13-AUG-13:12 | 26.73 | 18.53 | 0.449895E+09 | 550.36 | 29-AUG-13:30 | 29.30 | 20.07 |
September | 0.546864E+10 | 21738.02 | 10-SEP-12:52 | 20.60 | 14.10 | 0.389897E+09 | 550.13 | 15-SEP-13:50 | 21.70 | 16.50 |
October | 0.328611E+10 | 16703.39 | 08-OCT-13:43 | 19.63 | 14.09 | 0.377527E+09 | 549.82 | 04-OCT-13:00 | 19.63 | 14.09 |
November | 0.107962E+10 | 9218.65 | 04-NOV-13:30 | 20.85 | 16.00 | 0.335645E+09 | 550.17 | 15-NOV-14:39 | 9.27 | 6.62 |
December | 0.759884E+09 | 6618.76 | 05-DEC-12:30 | 10.30 | 6.13 | 0.317666E+09 | 549.50 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.400958E+11 | 0.452222E+10 | ||||||||
Minimum of Months | 0.531556E+09 | 6618.76 | 6.70 | 4.72 | 0.313362E+09 | 549.49 | 7.12 | 4.90 | ||
Maximum of Months | 0.678296E+10 | 21738.02 | 26.73 | 18.53 | 0.449895E+09 | 550.36 | 29.30 | 20.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127859E+09 | 778.39 | 05-JAN-15:50 | 6.20 | 4.71 | 0.195517E+09 | 314.14 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.343543E+09 | 3427.70 | 27-FEB-15:30 | 19.70 | 12.30 | 0.187086E+09 | 347.82 | 27-FEB-14:00 | 19.70 | 12.30 |
March | 0.965155E+09 | 5191.55 | 14-MAR-16:00 | 17.20 | 10.94 | 0.237288E+09 | 347.84 | 02-MAR-14:20 | 17.20 | 10.94 |
April | 0.176337E+10 | 8191.73 | 26-APR-16:00 | 24.40 | 14.49 | 0.228914E+09 | 347.85 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.287690E+10 | 16192.24 | 14-MAY-16:31 | 22.97 | 11.85 | 0.264154E+09 | 347.85 | 05-MAY-09:20 | 22.97 | 11.85 |
June | 0.332663E+10 | 14776.58 | 25-JUN-16:12 | 21.70 | 13.15 | 0.270332E+09 | 347.85 | 05-JUN-13:00 | 21.70 | 13.15 |
July | 0.443889E+10 | 15368.38 | 23-JUL-17:02 | 26.60 | 15.64 | 0.254030E+09 | 347.86 | 20-JUL-13:20 | 26.60 | 15.64 |
August | 0.425476E+10 | 15037.82 | 06-AUG-16:52 | 23.40 | 15.11 | 0.284552E+09 | 347.87 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.268667E+10 | 15214.92 | 10-SEP-15:32 | 22.40 | 14.43 | 0.244516E+09 | 347.85 | 15-SEP-09:20 | 16.70 | 14.42 |
October | 0.119429E+10 | 6643.08 | 04-OCT-16:00 | 21.10 | 11.40 | 0.228258E+09 | 347.85 | 05-OCT-13:20 | 16.10 | 10.57 |
November | 0.389267E+09 | 2730.70 | 04-NOV-15:30 | 20.55 | 15.94 | 0.201852E+09 | 347.80 | 10-NOV-14:00 | 10.00 | 6.84 |
December | 0.159126E+09 | 848.74 | 05-DEC-15:40 | 7.40 | 5.40 | 0.190343E+09 | 334.98 | 05-DEC-15:50 | 6.75 | 4.97 |
Annual Sum or Average | 0.225265E+11 | 0.278684E+10 | ||||||||
Minimum of Months | 0.127859E+09 | 778.39 | 6.20 | 4.71 | 0.187086E+09 | 314.14 | 6.10 | 4.61 | ||
Maximum of Months | 0.443889E+10 | 16192.24 | 26.60 | 15.94 | 0.284552E+09 | 347.87 | 26.60 | 16.46 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233262E+09 | 976.72 | 11-JAN-16:10 | 14.03 | 10.30 | 0.307326E+09 | 432.43 | 11-JAN-14:00 | 14.03 | 10.30 |
February | 0.498418E+09 | 1167.82 | 28-FEB-15:00 | 13.90 | 10.81 | 0.285462E+09 | 487.60 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.123866E+10 | 1222.45 | 10-MAR-14:40 | 16.30 | 11.68 | 0.364914E+09 | 504.45 | 10-MAR-14:50 | 16.20 | 11.59 |
April | 0.151384E+10 | 2624.94 | 27-APR-16:00 | 27.20 | 16.90 | 0.354493E+09 | 549.50 | 27-APR-13:20 | 27.20 | 16.90 |
May | 0.219454E+10 | 3121.61 | 05-MAY-15:30 | 24.70 | 17.20 | 0.419911E+09 | 549.50 | 05-MAY-09:20 | 24.70 | 17.20 |
June | 0.273982E+10 | 3842.36 | 21-JUN-15:40 | 24.80 | 15.84 | 0.430151E+09 | 549.50 | 09-JUN-13:20 | 24.80 | 15.84 |
July | 0.325856E+10 | 4782.13 | 24-JUL-15:00 | 30.60 | 18.78 | 0.402504E+09 | 549.50 | 20-JUL-13:20 | 30.60 | 18.78 |
August | 0.347493E+10 | 4427.39 | 09-AUG-15:30 | 28.70 | 18.83 | 0.451582E+09 | 549.52 | 09-AUG-09:00 | 28.70 | 18.83 |
September | 0.224123E+10 | 3292.18 | 14-SEP-15:50 | 24.32 | 17.03 | 0.392218E+09 | 549.50 | 05-SEP-09:20 | 24.32 | 17.03 |
October | 0.157859E+10 | 2026.78 | 04-OCT-15:30 | 21.40 | 11.45 | 0.373847E+09 | 549.49 | 03-OCT-13:20 | 21.40 | 11.45 |
November | 0.965325E+09 | 1230.69 | 06-NOV-12:00 | 13.90 | 10.05 | 0.329191E+09 | 503.56 | 06-NOV-14:09 | 11.60 | 10.16 |
December | 0.403845E+09 | 970.35 | 29-DEC-15:40 | 10.60 | 8.76 | 0.298809E+09 | 428.00 | 29-DEC-14:20 | 10.60 | 8.76 |
Annual Sum or Average | 0.203410E+11 | 0.441041E+10 | ||||||||
Minimum of Months | 0.233262E+09 | 970.35 | 10.60 | 8.76 | 0.285462E+09 | 428.00 | 10.60 | 8.76 | ||
Maximum of Months | 0.347493E+10 | 4782.13 | 30.60 | 18.83 | 0.451582E+09 | 549.52 | 30.60 | 18.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202445E+09 | 634.79 | 20-JAN-11:00 | 5.60 | 3.25 | 0.195411E+09 | 280.44 | 20-JAN-10:00 | 5.60 | 3.25 |
February | 0.415757E+09 | 775.22 | 27-FEB-15:40 | 19.60 | 12.34 | 0.187964E+09 | 319.60 | 27-FEB-14:00 | 19.60 | 12.34 |
March | 0.969784E+09 | 1529.20 | 14-MAR-10:00 | 10.00 | 7.75 | 0.249727E+09 | 347.88 | 02-MAR-10:20 | 10.00 | 7.75 |
April | 0.157104E+10 | 5004.83 | 27-APR-09:30 | 18.35 | 12.60 | 0.242660E+09 | 347.88 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.225791E+10 | 8454.45 | 15-MAY-06:02 | 11.97 | 9.44 | 0.271433E+09 | 347.89 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.320837E+10 | 9878.75 | 25-JUN-08:52 | 16.70 | 12.03 | 0.274874E+09 | 347.88 | 09-JUN-13:09 | 16.70 | 12.03 |
July | 0.352704E+10 | 8506.40 | 31-JUL-06:03 | 18.07 | 14.94 | 0.256076E+09 | 348.12 | 31-JUL-09:00 | 23.30 | 17.69 |
August | 0.403255E+10 | 8543.85 | 13-AUG-09:32 | 22.10 | 16.37 | 0.287407E+09 | 348.15 | 14-AUG-09:00 | 21.10 | 15.94 |
September | 0.246930E+10 | 5800.08 | 11-SEP-09:30 | 17.80 | 13.71 | 0.252079E+09 | 347.88 | 11-SEP-09:00 | 18.90 | 14.30 |
October | 0.136277E+10 | 3999.37 | 04-OCT-08:30 | 14.75 | 10.13 | 0.247511E+09 | 347.88 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.659760E+09 | 855.51 | 02-NOV-10:40 | 12.43 | 10.47 | 0.213860E+09 | 335.96 | 02-NOV-10:50 | 12.62 | 10.55 |
December | 0.332888E+09 | 726.73 | 05-DEC-10:30 | 7.50 | 5.28 | 0.192840E+09 | 306.85 | 05-DEC-10:39 | 7.77 | 5.32 |
Annual Sum or Average | 0.210096E+11 | 0.287184E+10 | ||||||||
Minimum of Months | 0.202445E+09 | 634.79 | 5.60 | 3.25 | 0.187964E+09 | 280.44 | 5.60 | 3.25 | ||
Maximum of Months | 0.403255E+10 | 9878.75 | 22.10 | 16.37 | 0.287407E+09 | 348.15 | 26.10 | 17.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240551E+09 | 2011.24 | 20-JAN-13:30 | 6.70 | 4.72 | 0.305186E+09 | 549.50 | 20-JAN-14:09 | 6.78 | 4.76 |
February | 0.665424E+09 | 5046.51 | 27-FEB-15:00 | 20.00 | 12.17 | 0.297751E+09 | 549.51 | 07-FEB-14:09 | 20.00 | 12.17 |
March | 0.148354E+10 | 7618.66 | 02-MAR-13:07 | 12.38 | 7.47 | 0.375119E+09 | 549.51 | 28-MAR-13:09 | 11.20 | 4.56 |
April | 0.206550E+10 | 9231.26 | 27-APR-13:40 | 26.10 | 16.65 | 0.356499E+09 | 549.51 | 19-APR-13:09 | 26.10 | 16.65 |
May | 0.263850E+10 | 11350.75 | 14-MAY-15:12 | 23.30 | 12.32 | 0.404396E+09 | 549.51 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.309567E+10 | 7100.77 | 28-JUN-13:30 | 24.70 | 15.69 | 0.416357E+09 | 549.52 | 28-JUN-13:50 | 24.90 | 15.66 |
July | 0.447700E+10 | 11452.52 | 30-JUL-13:42 | 26.60 | 17.69 | 0.396491E+09 | 549.57 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.588319E+10 | 13334.41 | 06-AUG-14:32 | 23.33 | 15.82 | 0.446159E+09 | 549.84 | 29-AUG-13:30 | 29.30 | 20.07 |
September | 0.433552E+10 | 15472.50 | 10-SEP-13:42 | 21.93 | 14.56 | 0.385392E+09 | 549.90 | 15-SEP-13:50 | 21.70 | 16.50 |
October | 0.258714E+10 | 11183.64 | 04-OCT-13:30 | 20.85 | 11.31 | 0.376400E+09 | 549.67 | 03-OCT-13:00 | 20.85 | 11.31 |
November | 0.879108E+09 | 6740.31 | 04-NOV-13:40 | 20.93 | 15.98 | 0.325232E+09 | 549.50 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.485812E+09 | 4026.51 | 05-DEC-13:10 | 10.60 | 6.22 | 0.305361E+09 | 549.50 | 06-DEC-14:09 | 5.08 | 4.26 |
Annual Sum or Average | 0.288370E+11 | 0.439034E+10 | ||||||||
Minimum of Months | 0.240551E+09 | 2011.24 | 6.70 | 4.72 | 0.297751E+09 | 549.50 | 5.08 | 4.26 | ||
Maximum of Months | 0.588319E+10 | 15472.50 | 26.60 | 17.69 | 0.446159E+09 | 549.90 | 29.30 | 20.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.197177E+09 | 732.39 | 20-JAN-15:50 | 5.87 | 4.23 | 0.196213E+09 | 299.32 | 20-JAN-15:00 | 5.60 | 4.08 |
February | 0.419895E+09 | 2075.73 | 27-FEB-15:40 | 19.60 | 12.34 | 0.187321E+09 | 347.83 | 27-FEB-14:00 | 19.60 | 12.34 |
March | 0.984073E+09 | 2997.53 | 02-MAR-16:30 | 13.05 | 8.47 | 0.241235E+09 | 347.83 | 02-MAR-14:00 | 13.05 | 8.47 |
April | 0.147916E+10 | 5812.50 | 26-APR-17:30 | 23.60 | 13.73 | 0.233878E+09 | 347.85 | 28-APR-09:20 | 11.70 | 11.07 |
May | 0.238290E+10 | 12780.41 | 14-MAY-17:11 | 22.60 | 11.84 | 0.270124E+09 | 347.85 | 05-MAY-09:20 | 22.60 | 11.84 |
June | 0.286591E+10 | 8229.54 | 18-JUN-17:22 | 16.95 | 12.25 | 0.273648E+09 | 347.85 | 28-JUN-13:00 | 25.00 | 15.65 |
July | 0.396064E+10 | 12514.67 | 30-JUL-17:42 | 26.70 | 17.71 | 0.256250E+09 | 347.85 | 03-JUL-09:20 | 26.70 | 17.71 |
August | 0.393785E+10 | 11702.89 | 06-AUG-17:52 | 23.80 | 15.26 | 0.287178E+09 | 347.88 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.255739E+10 | 10306.68 | 10-SEP-17:02 | 21.93 | 14.12 | 0.251879E+09 | 347.86 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.134908E+10 | 5838.74 | 04-OCT-16:00 | 21.10 | 11.40 | 0.243253E+09 | 347.85 | 05-OCT-09:20 | 12.43 | 7.97 |
November | 0.656267E+09 | 2247.66 | 04-NOV-15:30 | 20.55 | 15.94 | 0.211950E+09 | 347.76 | 10-NOV-14:00 | 10.00 | 6.84 |
December | 0.316525E+09 | 831.56 | 05-DEC-15:40 | 7.40 | 5.40 | 0.193108E+09 | 328.32 | 05-DEC-15:39 | 7.40 | 5.40 |
Annual Sum or Average | 0.211069E+11 | 0.284604E+10 | ||||||||
Minimum of Months | 0.197177E+09 | 732.39 | 5.87 | 4.23 | 0.187321E+09 | 299.32 | 5.60 | 4.08 | ||
Maximum of Months | 0.396064E+10 | 12780.41 | 26.70 | 17.71 | 0.287178E+09 | 347.88 | 26.70 | 17.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.305530E+09 | 1047.03 | 11-JAN-16:20 | 13.67 | 10.10 | 0.308260E+09 | 450.22 | 11-JAN-14:00 | 13.67 | 10.10 |
February | 0.640424E+09 | 1292.63 | 28-FEB-15:00 | 13.90 | 10.81 | 0.291359E+09 | 524.73 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.143739E+10 | 1353.33 | 10-MAR-14:50 | 16.20 | 11.59 | 0.382797E+09 | 544.65 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.183560E+10 | 4080.33 | 27-APR-15:20 | 27.20 | 17.16 | 0.371254E+09 | 549.50 | 27-APR-13:20 | 27.20 | 17.16 |
May | 0.284034E+10 | 4324.41 | 15-MAY-14:30 | 23.30 | 13.06 | 0.426313E+09 | 549.50 | 05-MAY-09:20 | 23.30 | 13.06 |
June | 0.349353E+10 | 4745.41 | 21-JUN-15:30 | 24.70 | 15.68 | 0.432209E+09 | 549.50 | 09-JUN-13:09 | 24.70 | 15.68 |
July | 0.397301E+10 | 7041.80 | 24-JUL-06:03 | 17.48 | 14.11 | 0.403293E+09 | 550.31 | 24-JUL-13:20 | 28.67 | 18.27 |
August | 0.411363E+10 | 6816.13 | 14-AUG-06:02 | 15.47 | 13.75 | 0.452300E+09 | 549.53 | 09-AUG-09:00 | 15.47 | 13.75 |
September | 0.257405E+10 | 4076.82 | 12-SEP-14:40 | 24.40 | 16.65 | 0.393973E+09 | 549.50 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.162971E+10 | 2648.85 | 04-OCT-15:30 | 21.40 | 11.45 | 0.375369E+09 | 549.49 | 05-OCT-13:20 | 16.10 | 10.57 |
November | 0.890815E+09 | 1251.43 | 02-NOV-14:10 | 14.22 | 11.35 | 0.327328E+09 | 511.67 | 02-NOV-13:00 | 14.22 | 11.35 |
December | 0.409034E+09 | 998.65 | 05-DEC-15:00 | 10.00 | 7.01 | 0.299617E+09 | 437.38 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.241431E+11 | 0.446407E+10 | ||||||||
Minimum of Months | 0.305530E+09 | 998.65 | 10.00 | 7.01 | 0.291359E+09 | 437.38 | 10.00 | 7.01 | ||
Maximum of Months | 0.411363E+10 | 7041.80 | 27.20 | 17.16 | 0.452300E+09 | 550.31 | 28.67 | 18.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189784E+09 | 712.32 | 20-JAN-11:10 | 5.60 | 3.32 | 0.144669E+09 | 299.71 | 20-JAN-11:09 | 5.60 | 3.32 |
February | 0.378704E+09 | 1757.02 | 08-FEB-11:05 | 4.08 | 2.58 | 0.142262E+09 | 352.76 | 08-FEB-11:09 | 4.08 | 2.58 |
March | 0.975750E+09 | 5687.10 | 01-MAR-13:01 | 10.78 | 5.75 | 0.189438E+09 | 356.46 | 14-MAR-10:09 | 10.28 | 7.92 |
April | 0.183023E+10 | 7411.76 | 27-APR-10:05 | 19.27 | 13.13 | 0.181039E+09 | 356.46 | 20-APR-10:09 | 19.27 | 13.13 |
May | 0.262753E+10 | 12254.04 | 14-MAY-08:43 | 16.32 | 11.34 | 0.201124E+09 | 356.47 | 15-MAY-10:09 | 19.18 | 13.24 |
June | 0.353182E+10 | 11959.47 | 25-JUN-07:42 | 15.32 | 11.39 | 0.203359E+09 | 356.46 | 07-JUN-10:09 | 15.32 | 11.39 |
July | 0.380292E+10 | 14400.76 | 30-JUL-08:52 | 20.60 | 15.79 | 0.190244E+09 | 356.46 | 07-JUL-12:09 | 20.60 | 15.79 |
August | 0.414408E+10 | 13246.96 | 13-AUG-08:52 | 20.90 | 15.90 | 0.212661E+09 | 356.51 | 09-AUG-10:09 | 20.90 | 15.90 |
September | 0.253097E+10 | 8533.43 | 10-SEP-09:02 | 16.28 | 13.48 | 0.186274E+09 | 356.46 | 11-SEP-10:09 | 19.08 | 14.37 |
October | 0.127419E+10 | 5902.27 | 04-OCT-10:05 | 17.48 | 10.97 | 0.181237E+09 | 356.46 | 05-OCT-10:09 | 14.08 | 9.36 |
November | 0.481724E+09 | 2926.68 | 02-NOV-12:02 | 13.48 | 11.00 | 0.156714E+09 | 356.45 | 02-NOV-10:09 | 13.48 | 11.00 |
December | 0.247554E+09 | 775.42 | 05-DEC-11:10 | 8.58 | 5.53 | 0.142605E+09 | 320.47 | 05-DEC-11:09 | 8.58 | 5.53 |
Annual Sum or Average | 0.220153E+11 | 0.213163E+10 | ||||||||
Minimum of Months | 0.189784E+09 | 712.32 | 4.08 | 2.58 | 0.142262E+09 | 299.71 | 4.08 | 2.58 | ||
Maximum of Months | 0.414408E+10 | 14400.76 | 20.90 | 15.90 | 0.212661E+09 | 356.51 | 20.90 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.768053E+09 | 7165.95 | 20-JAN-13:12 | 6.70 | 4.72 | 0.329506E+09 | 549.49 | 20-JAN-14:39 | 7.03 | 4.87 |
February | 0.159000E+10 | 8723.19 | 27-FEB-14:10 | 18.58 | 11.55 | 0.321749E+09 | 549.50 | 08-FEB-10:09 | 18.58 | 11.55 |
March | 0.304261E+10 | 10236.54 | 01-MAR-13:30 | 11.15 | 5.98 | 0.411563E+09 | 549.50 | 02-MAR-14:00 | 13.30 | 8.57 |
April | 0.368796E+10 | 11518.31 | 27-APR-13:05 | 26.10 | 16.37 | 0.384111E+09 | 550.61 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.446978E+10 | 12498.65 | 07-MAY-15:32 | 22.03 | 16.36 | 0.428137E+09 | 549.51 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.481848E+10 | 10615.31 | 11-JUN-12:33 | 21.70 | 15.39 | 0.432190E+09 | 549.52 | 28-JUN-13:39 | 24.80 | 15.68 |
July | 0.587277E+10 | 19113.07 | 30-JUL-12:12 | 26.10 | 17.39 | 0.403719E+09 | 550.83 | 31-JUL-13:20 | 27.57 | 18.47 |
August | 0.679675E+10 | 18441.03 | 06-AUG-12:32 | 20.97 | 14.99 | 0.453079E+09 | 550.87 | 14-AUG-13:20 | 25.93 | 17.49 |
September | 0.565936E+10 | 18650.75 | 10-SEP-13:02 | 20.87 | 14.20 | 0.397744E+09 | 550.61 | 12-SEP-13:20 | 23.33 | 16.02 |
October | 0.375584E+10 | 13483.65 | 04-OCT-12:50 | 20.60 | 11.27 | 0.393133E+09 | 550.16 | 04-OCT-13:20 | 20.77 | 11.28 |
November | 0.148826E+10 | 9332.76 | 04-NOV-13:30 | 20.85 | 16.00 | 0.352038E+09 | 549.49 | 24-NOV-10:39 | 5.93 | 4.25 |
December | 0.111248E+10 | 7533.80 | 05-DEC-12:30 | 10.30 | 6.13 | 0.327431E+09 | 549.50 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.430623E+11 | 0.463440E+10 | ||||||||
Minimum of Months | 0.768053E+09 | 7165.95 | 6.70 | 4.72 | 0.321749E+09 | 549.49 | 5.93 | 4.25 | ||
Maximum of Months | 0.679675E+10 | 19113.07 | 26.10 | 17.39 | 0.453079E+09 | 550.87 | 27.57 | 18.47 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244396E+09 | 808.43 | 05-JAN-15:50 | 6.20 | 4.71 | 0.197882E+09 | 322.69 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.519340E+09 | 3479.35 | 27-FEB-15:30 | 19.70 | 12.30 | 0.191338E+09 | 347.83 | 28-FEB-14:39 | 14.07 | 11.06 |
March | 0.119613E+10 | 5061.31 | 14-MAR-16:00 | 17.20 | 10.94 | 0.248274E+09 | 347.84 | 02-MAR-14:20 | 17.20 | 10.94 |
April | 0.189229E+10 | 7922.93 | 26-APR-16:00 | 24.40 | 14.49 | 0.237676E+09 | 347.85 | 28-APR-09:20 | 11.70 | 11.07 |
May | 0.296022E+10 | 15135.95 | 07-MAY-16:51 | 21.70 | 16.17 | 0.270510E+09 | 347.85 | 05-MAY-09:20 | 21.70 | 16.17 |
June | 0.337349E+10 | 14420.49 | 18-JUN-16:52 | 17.20 | 12.22 | 0.273618E+09 | 347.86 | 05-JUN-13:00 | 17.20 | 12.22 |
July | 0.441411E+10 | 15588.40 | 30-JUL-17:31 | 26.70 | 17.74 | 0.255758E+09 | 347.85 | 31-JUL-09:20 | 22.57 | 17.16 |
August | 0.426475E+10 | 13793.38 | 06-AUG-16:32 | 23.53 | 15.27 | 0.286739E+09 | 347.88 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.280817E+10 | 13070.69 | 10-SEP-16:22 | 22.20 | 14.33 | 0.250670E+09 | 347.86 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.141679E+10 | 6603.14 | 04-OCT-16:00 | 21.10 | 11.40 | 0.240759E+09 | 347.85 | 05-OCT-13:20 | 16.10 | 10.57 |
November | 0.611313E+09 | 2840.30 | 04-NOV-15:30 | 20.55 | 15.94 | 0.210635E+09 | 347.84 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.319854E+09 | 1142.99 | 05-DEC-15:30 | 8.05 | 5.82 | 0.194203E+09 | 343.14 | 05-DEC-14:00 | 8.05 | 5.82 |
Annual Sum or Average | 0.240209E+11 | 0.285806E+10 | ||||||||
Minimum of Months | 0.244396E+09 | 808.43 | 6.20 | 4.71 | 0.191338E+09 | 322.69 | 6.10 | 4.61 | ||
Maximum of Months | 0.441411E+10 | 15588.40 | 26.70 | 17.74 | 0.286739E+09 | 347.88 | 23.80 | 17.16 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.212417E+09 | 17811.84 | 02-JAN-06:11 | 6.10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.212417E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.212417E+09 | 17811.84 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334960E+10 | 11858.99 | 17-JAN-06:12 | 1.30 |
February | 0.208737E+10 | 11369.90 | 21-FEB-06:13 | 1.70 |
March | 0.128844E+10 | 6900.90 | 06-MAR-07:03 | 6.70 |
April | 0.729551E+09 | 4329.99 | 19-APR-05:02 | 1.78 |
May | 0.459803E+09 | 3571.25 | 14-MAY-08:32 | 15.93 |
June | 0.277348E+09 | 3134.84 | 19-JUN-06:02 | 11.88 |
July | 0.203751E+09 | 3266.71 | 23-JUL-07:42 | 17.52 |
August | 0.241054E+09 | 3343.00 | 06-AUG-08:13 | 14.57 |
September | 0.445845E+09 | 4208.16 | 10-SEP-08:12 | 14.97 |
October | 0.943719E+09 | 3947.28 | 16-OCT-06:03 | 6.60 |
November | 0.180414E+10 | 9765.48 | 24-NOV-06:22 | 1.65 |
December | 0.283639E+10 | 12282.61 | 26-DEC-06:12 | -1.0 |
Annual Sum or Average | 0.146670E+11 | |||
Minimum of Months | 0.203751E+09 | 3134.84 | -1.0 | |
Maximum of Months | 0.334960E+10 | 12282.61 | 17.52 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190549E+10 | 9078.01 | 02-JAN-07:02 | 6.20 |
February | 0.123251E+10 | 5932.03 | 21-FEB-07:03 | 1.60 |
March | 0.918933E+09 | 2666.34 | 14-MAR-12:02 | 13.48 |
April | 0.413862E+09 | 3175.69 | 02-APR-13:23 | 18.90 |
May | 0.100600E+09 | 4152.30 | 29-MAY-16:42 | 16.60 |
June | 31224941.77 | 2900.30 | 25-JUN-07:42 | 15.32 |
July | 30449575.05 | 4360.52 | 30-JUL-14:52 | 27.20 |
August | 22541648.52 | 4262.85 | 06-AUG-14:32 | 23.33 |
September | 72369638.68 | 4230.28 | 10-SEP-14:22 | 22.50 |
October | 0.498141E+09 | 4053.46 | 08-OCT-13:13 | 18.53 |
November | 0.108530E+10 | 2725.85 | 24-NOV-11:10 | 6.20 |
December | 0.151938E+10 | 7218.12 | 26-DEC-07:03 | -1.6 |
Annual Sum or Average | 0.783080E+10 | |||
Minimum of Months | 22541648.52 | 2666.34 | -1.6 | |
Maximum of Months | 0.190549E+10 | 9078.01 | 27.20 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176645E+10 | 8890.31 | 02-JAN-07:02 | 6.20 |
February | 0.104516E+10 | 3344.00 | 16-FEB-08:20 | 2.60 |
March | 0.533225E+09 | 3409.89 | 13-MAR-07:09 | 6.70 |
April | 0.139637E+09 | 2151.94 | 19-APR-07:05 | 4.18 |
May | 23209684.38 | 2998.36 | 14-MAY-15:12 | 23.30 |
June | 21066217.41 | 1831.47 | 25-JUN-08:52 | 16.70 |
July | 23995397.38 | 2023.13 | 30-JUL-15:42 | 27.70 |
August | 19276700.81 | 2455.00 | 06-AUG-14:32 | 23.33 |
September | 21592334.61 | 2833.50 | 10-SEP-16:22 | 22.20 |
October | 0.204526E+09 | 2178.62 | 08-OCT-13:13 | 18.53 |
November | 0.852050E+09 | 3809.36 | 13-NOV-08:07 | 0.78 |
December | 0.135211E+10 | 3743.10 | 06-DEC-08:06 | 1.07 |
Annual Sum or Average | 0.600229E+10 | |||
Minimum of Months | 19276700.81 | 1831.47 | 0.78 | |
Maximum of Months | 0.176645E+10 | 8890.31 | 27.70 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.583877E+09 | 20143.83 | 02-JAN-06:11 | 6.10 |
February | 66456832.11 | 17188.96 | 21-FEB-06:01 | 1.70 |
March | 2416550.94 | 15415.17 | 06-MAR-07:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 14564020.01 | 15228.34 | 27-NOV-07:03 | 11.70 |
December | 0.106234E+09 | 17523.48 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.773548E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.583877E+09 | 20143.83 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161998E+10 | 30464.68 | 02-JAN-06:11 | 6.10 |
February | 0.583898E+09 | 28886.95 | 21-FEB-05:51 | 1.70 |
March | 88242316.01 | 26466.17 | 06-MAR-06:11 | 6.70 |
April | 4716514.50 | 13937.31 | 18-APR-06:03 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 13573623.00 | 24358.58 | 23-OCT-06:03 | 10.40 |
November | 0.304048E+09 | 26954.39 | 27-NOV-06:11 | 11.70 |
December | 0.904689E+09 | 29336.93 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.351914E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.161998E+10 | 30464.68 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.260849E+10 | 8835.02 | 17-JAN-05:11 | 1.50 |
February | 0.135210E+10 | 8776.13 | 21-FEB-05:51 | 1.70 |
March | 0.351017E+09 | 8294.14 | 06-MAR-06:11 | 6.70 |
April | 85137251.90 | 7522.76 | 18-APR-05:12 | 3.30 |
May | 2961287.98 | 6968.52 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 1211915.89 | 3145.23 | 27-SEP-06:03 | 8.40 |
October | 0.108973E+09 | 7583.32 | 30-OCT-05:12 | 7.20 |
November | 0.873506E+09 | 8451.74 | 24-NOV-06:11 | 1.83 |
December | 0.197196E+10 | 8690.59 | 18-DEC-06:11 | 3.53 |
Annual Sum or Average | 0.735536E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.50 | |
Maximum of Months | 0.260849E+10 | 8835.02 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158158E+10 | 9760.07 | 17-JAN-05:11 | 1.50 |
February | 0.757301E+09 | 9676.66 | 21-FEB-05:51 | 1.70 |
March | 0.176597E+09 | 9092.70 | 06-MAR-06:11 | 6.70 |
April | 37059327.81 | 7968.75 | 18-APR-05:12 | 3.30 |
May | 2188123.21 | 5397.31 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 822385.46 | 2097.47 | 27-SEP-06:03 | 8.40 |
October | 67064127.68 | 7936.82 | 30-OCT-05:12 | 7.20 |
November | 0.527725E+09 | 9305.12 | 24-NOV-06:11 | 1.83 |
December | 0.119673E+10 | 9507.14 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.434707E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.158158E+10 | 9760.07 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.196670E+10 | 14823.32 | 17-JAN-05:11 | 1.50 |
February | 0.902667E+09 | 14661.87 | 21-FEB-05:51 | 1.70 |
March | 0.264075E+09 | 13767.17 | 06-MAR-06:11 | 6.70 |
April | 76684494.86 | 12236.10 | 11-APR-05:12 | 5.60 |
May | 3603988.36 | 8468.81 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 949599.89 | 2633.62 | 27-SEP-06:03 | 8.40 |
October | 81463523.41 | 12135.72 | 16-OCT-05:12 | 7.03 |
November | 0.660605E+09 | 14049.89 | 24-NOV-06:11 | 1.83 |
December | 0.151025E+10 | 14472.23 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.546701E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.196670E+10 | 14823.32 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163668E+10 | 9709.13 | 17-JAN-05:11 | 1.50 |
February | 0.807865E+09 | 9604.89 | 21-FEB-05:51 | 1.70 |
March | 0.224283E+09 | 8982.18 | 06-MAR-06:11 | 6.70 |
April | 57508795.73 | 8006.19 | 11-APR-05:12 | 5.60 |
May | 2602841.82 | 5413.12 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 593489.05 | 1425.02 | 27-SEP-06:03 | 8.40 |
October | 71138038.19 | 7889.27 | 16-OCT-05:12 | 7.03 |
November | 0.562351E+09 | 9195.67 | 24-NOV-06:11 | 1.83 |
December | 0.124337E+10 | 9433.90 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.460639E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.163668E+10 | 9709.13 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147106E+10 | 7000.76 | 02-JAN-06:11 | 6.10 |
February | 0.545756E+09 | 6561.94 | 21-FEB-05:51 | 1.70 |
March | 72193702.91 | 6021.27 | 06-MAR-06:11 | 6.70 |
April | 9900983.01 | 5595.25 | 18-APR-06:03 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 2519064.97 | 5528.41 | 30-OCT-06:03 | 7.20 |
November | 0.122236E+09 | 5957.86 | 24-NOV-06:11 | 1.83 |
December | 0.632084E+09 | 6486.77 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.285575E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.147106E+10 | 7000.76 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.895660E+09 | 7117.40 | 02-JAN-06:11 | 6.10 |
February | 0.265527E+09 | 6350.17 | 21-FEB-05:51 | 1.70 |
March | 26893481.95 | 5784.79 | 06-MAR-06:11 | 6.70 |
April | 3098577.98 | 4892.55 | 18-APR-06:03 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 933066.89 | 2042.14 | 31-OCT-06:03 | 10.18 |
November | 75760715.47 | 5879.94 | 30-NOV-06:11 | 5.60 |
December | 0.408022E+09 | 6419.17 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.167590E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.895660E+09 | 7117.40 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362222E+10 | 10708.03 | 06-JAN-07:10 | -2.3 |
February | 0.205162E+10 | 10245.34 | 21-FEB-08:00 | 1.10 |
March | 0.144853E+10 | 9736.52 | 01-MAR-07:10 | -0.1 |
April | 0.820294E+09 | 9355.92 | 19-APR-06:10 | 2.48 |
May | 0.503506E+09 | 8548.52 | 18-MAY-06:30 | 5.85 |
June | 0.214556E+09 | 7928.10 | 01-JUN-06:05 | 10.18 |
July | 32835383.02 | 4885.23 | 13-JUL-06:06 | 12.98 |
August | 50582263.25 | 6436.53 | 03-AUG-06:06 | 11.82 |
September | 0.201812E+09 | 8477.86 | 28-SEP-06:20 | 8.50 |
October | 0.730666E+09 | 8499.45 | 12-OCT-06:30 | 6.65 |
November | 0.183903E+10 | 10095.82 | 24-NOV-07:10 | 1.20 |
December | 0.275163E+10 | 10806.13 | 26-DEC-08:00 | -1.1 |
Annual Sum or Average | 0.142673E+11 | |||
Minimum of Months | 32835383.02 | 4885.23 | -2.3 | |
Maximum of Months | 0.362222E+10 | 10806.13 | 12.98 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.903965E+09 | 7052.37 | 02-JAN-06:11 | 6.10 |
February | 0.274746E+09 | 6084.55 | 21-FEB-06:01 | 1.70 |
March | 37370742.84 | 5665.57 | 06-MAR-06:12 | 6.70 |
April | 4568433.45 | 5348.46 | 19-APR-06:03 | 2.48 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 561378.73 | 1087.90 | 30-OCT-06:03 | 7.20 |
November | 77374975.79 | 5872.67 | 30-NOV-06:11 | 5.60 |
December | 0.395300E+09 | 6484.67 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.169389E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.903965E+09 | 7052.37 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129550E+10 | 7709.34 | 02-JAN-06:11 | 6.10 |
February | 0.448078E+09 | 7396.49 | 21-FEB-05:51 | 1.70 |
March | 56334897.47 | 6737.90 | 06-MAR-06:11 | 6.70 |
April | 7144699.83 | 6158.74 | 18-APR-06:03 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 8616525.94 | 6179.81 | 30-OCT-06:03 | 7.20 |
November | 0.226196E+09 | 6834.29 | 24-NOV-06:11 | 1.83 |
December | 0.731388E+09 | 7471.07 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.277326E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.129550E+10 | 7709.34 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.794606E+09 | 7525.90 | 02-JAN-06:11 | 6.10 |
February | 0.257706E+09 | 7142.50 | 21-FEB-05:51 | 1.70 |
March | 28406313.64 | 6215.51 | 06-MAR-06:11 | 6.70 |
April | 3463933.77 | 5359.48 | 18-APR-06:03 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 6071130.01 | 5411.29 | 30-OCT-06:03 | 7.20 |
November | 0.145965E+09 | 6387.74 | 24-NOV-06:11 | 1.83 |
December | 0.475751E+09 | 7264.85 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.171197E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.794606E+09 | 7525.90 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.943454E+09 | 11392.10 | 02-JAN-06:11 | 6.10 |
February | 0.293934E+09 | 10584.44 | 21-FEB-05:51 | 1.70 |
March | 41177116.65 | 9478.17 | 06-MAR-06:11 | 6.70 |
April | 6070975.33 | 7883.40 | 18-APR-06:03 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 4825545.73 | 6377.43 | 16-OCT-06:03 | 6.60 |
November | 0.160242E+09 | 9679.02 | 24-NOV-06:11 | 1.83 |
December | 0.567828E+09 | 10854.18 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.201753E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.943454E+09 | 11392.10 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.808971E+09 | 7478.77 | 02-JAN-06:11 | 6.10 |
February | 0.269992E+09 | 7034.08 | 21-FEB-05:51 | 1.70 |
March | 38009325.24 | 6140.44 | 06-MAR-06:11 | 6.70 |
April | 5200346.12 | 5426.85 | 19-APR-06:03 | 2.48 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 5565216.10 | 5067.30 | 30-OCT-06:03 | 7.20 |
November | 0.151001E+09 | 6293.76 | 24-NOV-06:11 | 1.83 |
December | 0.472050E+09 | 7204.23 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.175079E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.808971E+09 | 7478.77 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.679453E+09 | 1040.56 | 02-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.554537E+09 | 945.17 | 02-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.605089E+09 | 830.87 | 22-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.511857E+09 | 667.05 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.538145E+09 | 541.21 | 17-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.526145E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.494536E+09 | 579.72 | 12-JUL-08:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.558699E+09 | 574.20 | 02-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.528768E+09 | 837.22 | 25-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.592366E+09 | 1027.50 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.655754E+09 | 1040.56 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.681304E+09 | 1040.56 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.692665E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.494536E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.681304E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.416641E+09 | 658.76 | 02-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.346117E+09 | 604.68 | 02-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.380850E+09 | 502.99 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324117E+09 | 354.45 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.342443E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.335286E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.315061E+09 | 339.83 | 12-JUL-08:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.355534E+09 | 353.24 | 02-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.332304E+09 | 508.51 | 25-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.369493E+09 | 648.37 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.405418E+09 | 658.76 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.415515E+09 | 658.76 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.433878E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.315061E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.416641E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.642314E+09 | 1040.56 | 02-JAN-16:30 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.534339E+09 | 922.83 | 02-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.597697E+09 | 821.38 | 22-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.512097E+09 | 583.86 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.540637E+09 | 542.27 | 17-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.529261E+09 | 530.72 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.499149E+09 | 574.59 | 12-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.562266E+09 | 572.97 | 02-AUG-07:30 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.525585E+09 | 830.09 | 25-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.576811E+09 | 1025.02 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.626358E+09 | 1040.56 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.637362E+09 | 1040.56 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.678387E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.499149E+09 | 530.72 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.642314E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.416537E+09 | 658.71 | 02-JAN-16:30 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.342850E+09 | 582.59 | 02-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.380693E+09 | 534.11 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324033E+09 | 454.12 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.341100E+09 | 352.78 | 17-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.333466E+09 | 346.71 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314874E+09 | 468.46 | 12-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.354428E+09 | 462.90 | 28-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.334504E+09 | 537.17 | 25-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.369899E+09 | 650.62 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.403893E+09 | 658.71 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.415132E+09 | 658.71 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.433141E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.314874E+09 | 346.71 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.416537E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.675308E+09 | 1040.56 | 02-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.551908E+09 | 941.40 | 02-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.603183E+09 | 822.79 | 22-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.511139E+09 | 583.20 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.537733E+09 | 536.46 | 17-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.525872E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.494165E+09 | 576.91 | 12-JUL-08:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.558123E+09 | 571.03 | 02-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.527671E+09 | 829.44 | 25-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.589639E+09 | 1027.00 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.652193E+09 | 1040.56 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.677239E+09 | 1040.56 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.690417E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.494165E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.677239E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.415134E+09 | 658.76 | 02-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.345084E+09 | 602.99 | 02-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.380122E+09 | 497.81 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.323766E+09 | 352.14 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.342135E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.335012E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314770E+09 | 336.35 | 12-JUL-08:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.355113E+09 | 350.85 | 02-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.331724E+09 | 503.55 | 25-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.368473E+09 | 648.02 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.404154E+09 | 658.76 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.413878E+09 | 658.76 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.432936E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.314770E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.415134E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.639961E+09 | 1040.56 | 02-JAN-16:30 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.533044E+09 | 917.32 | 02-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.596618E+09 | 812.84 | 22-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.511517E+09 | 581.12 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.540106E+09 | 537.57 | 17-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.528748E+09 | 525.50 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.498606E+09 | 571.49 | 12-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.561629E+09 | 569.72 | 02-AUG-07:30 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.524892E+09 | 821.97 | 25-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.575517E+09 | 1024.40 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.624566E+09 | 1040.56 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.635200E+09 | 1040.56 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.677040E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.498606E+09 | 525.50 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.639961E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.414945E+09 | 658.71 | 02-JAN-16:30 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.341758E+09 | 580.25 | 02-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.379854E+09 | 530.30 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.323551E+09 | 447.91 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.340819E+09 | 350.54 | 17-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.333103E+09 | 344.24 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314379E+09 | 462.96 | 12-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.354011E+09 | 457.02 | 28-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.333740E+09 | 533.46 | 25-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.368822E+09 | 650.37 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.402363E+09 | 658.71 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.413301E+09 | 658.71 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.432064E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.314379E+09 | 344.24 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.414945E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.679449E+09 | 1040.56 | 02-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.554534E+09 | 945.17 | 02-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.605087E+09 | 830.85 | 22-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.511856E+09 | 667.02 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.538145E+09 | 541.20 | 17-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.526145E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.494536E+09 | 579.71 | 12-JUL-08:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.558698E+09 | 574.19 | 02-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.528767E+09 | 837.21 | 25-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.592363E+09 | 1027.50 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.655749E+09 | 1040.56 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.681299E+09 | 1040.56 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.692663E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.494536E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.681299E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.416639E+09 | 658.76 | 02-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.346115E+09 | 604.67 | 02-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.380849E+09 | 502.98 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324116E+09 | 354.45 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.342443E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.335285E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.315061E+09 | 339.83 | 12-JUL-08:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.355534E+09 | 353.24 | 02-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.332303E+09 | 508.50 | 25-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.369492E+09 | 648.37 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.405416E+09 | 658.76 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.415513E+09 | 658.76 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.433877E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.315061E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.416639E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.642312E+09 | 1040.56 | 02-JAN-16:30 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.534338E+09 | 922.82 | 02-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.597695E+09 | 821.36 | 22-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.512096E+09 | 583.85 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.540636E+09 | 542.25 | 17-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.529261E+09 | 530.71 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.499148E+09 | 574.59 | 12-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.562266E+09 | 572.96 | 02-AUG-07:30 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.525584E+09 | 830.07 | 25-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.576809E+09 | 1025.02 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.626356E+09 | 1040.56 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.637360E+09 | 1040.56 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.678386E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.499148E+09 | 530.71 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.642312E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.416535E+09 | 658.71 | 02-JAN-16:30 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.342848E+09 | 582.59 | 02-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.380692E+09 | 534.10 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324032E+09 | 454.11 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.341100E+09 | 352.77 | 17-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.333465E+09 | 346.70 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314873E+09 | 468.44 | 12-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.354427E+09 | 462.89 | 28-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.334503E+09 | 537.16 | 25-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.369898E+09 | 650.62 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.403861E+09 | 658.71 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.415130E+09 | 658.71 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.433136E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.314873E+09 | 346.70 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.416535E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.679453E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802375E+09 |
February | 0.901968E+09 | 0.554537E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720192E+09 |
March | 0.107774E+10 | 0.605089E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.713822E+09 |
April | 0.956342E+09 | 0.511857E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1677169.80 | 0.701731E+09 |
May | 0.103597E+10 | 0.538145E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42236.26 | 0.576439E+09 |
June | 0.103308E+10 | 0.526145E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 466740.76 | 0.484615E+09 |
July | 0.959235E+09 | 0.494536E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6199168.47 | 0.407650E+09 |
August | 0.107774E+10 | 0.558699E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10443666.14 | 0.330868E+09 |
September | 0.956342E+09 | 0.528768E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43169.12 | 0.265736E+09 |
October | 0.994195E+09 | 0.592366E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573307E+09 |
November | 0.984487E+09 | 0.655754E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627143E+09 |
December | 0.959235E+09 | 0.681304E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.679702E+09 |
Annual Sum or Average | 0.119305E+11 | 0.692665E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18872150.55 | 0.688358E+10 |
Minimum of Months | 0.901968E+09 | 0.494536E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265736E+09 |
Maximum of Months | 0.107774E+10 | 0.681304E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10443666.14 | 0.802375E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.416641E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534504E+09 |
February | 0.571020E+09 | 0.346117E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487016E+09 |
March | 0.682301E+09 | 0.380850E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483929E+09 |
April | 0.605444E+09 | 0.324117E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 878238.05 | 0.479490E+09 |
May | 0.655854E+09 | 0.342443E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28160.95 | 0.392747E+09 |
June | 0.654023E+09 | 0.335286E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 311169.71 | 0.331922E+09 |
July | 0.607275E+09 | 0.315061E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2903285.94 | 0.278026E+09 |
August | 0.682301E+09 | 0.355534E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6612683.61 | 0.227057E+09 |
September | 0.605444E+09 | 0.332304E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28781.53 | 0.181477E+09 |
October | 0.629407E+09 | 0.369493E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389826E+09 |
November | 0.623262E+09 | 0.405418E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418921E+09 |
December | 0.607275E+09 | 0.415515E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453338E+09 |
Annual Sum or Average | 0.755301E+10 | 0.433878E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10762319.79 | 0.465825E+10 |
Minimum of Months | 0.571020E+09 | 0.315061E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181477E+09 |
Maximum of Months | 0.682301E+09 | 0.416641E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6612683.61 | 0.534504E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.642314E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.823638E+09 |
February | 0.901968E+09 | 0.534339E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770076E+09 |
March | 0.107774E+10 | 0.597697E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750091E+09 |
April | 0.956342E+09 | 0.512097E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 980909.22 | 0.732519E+09 |
May | 0.103597E+10 | 0.540637E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42227.98 | 0.593580E+09 |
June | 0.103308E+10 | 0.529261E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 466709.36 | 0.495600E+09 |
July | 0.959235E+09 | 0.499149E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4189634.09 | 0.419752E+09 |
August | 0.107774E+10 | 0.562266E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9872863.49 | 0.344133E+09 |
September | 0.956342E+09 | 0.525585E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43066.45 | 0.281466E+09 |
October | 0.994195E+09 | 0.576811E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613814E+09 |
November | 0.984487E+09 | 0.626358E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649152E+09 |
December | 0.959235E+09 | 0.637362E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.704318E+09 |
Annual Sum or Average | 0.119305E+11 | 0.678387E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15595410.59 | 0.717814E+10 |
Minimum of Months | 0.901968E+09 | 0.499149E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281466E+09 |
Maximum of Months | 0.107774E+10 | 0.642314E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9872863.49 | 0.823638E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.416537E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536178E+09 |
February | 0.570983E+09 | 0.342850E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490253E+09 |
March | 0.682256E+09 | 0.380693E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487249E+09 |
April | 0.605404E+09 | 0.324033E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 441550.55 | 0.482487E+09 |
May | 0.655811E+09 | 0.341100E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28161.86 | 0.401405E+09 |
June | 0.653980E+09 | 0.333466E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 311158.78 | 0.334107E+09 |
July | 0.607235E+09 | 0.314874E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2846766.93 | 0.287538E+09 |
August | 0.682256E+09 | 0.354428E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6629811.90 | 0.232781E+09 |
September | 0.605404E+09 | 0.334504E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28781.19 | 0.187383E+09 |
October | 0.629366E+09 | 0.369899E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393495E+09 |
November | 0.623221E+09 | 0.403893E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420581E+09 |
December | 0.607235E+09 | 0.415132E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455203E+09 |
Annual Sum or Average | 0.755252E+10 | 0.433141E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10286231.20 | 0.470866E+10 |
Minimum of Months | 0.570983E+09 | 0.314874E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187383E+09 |
Maximum of Months | 0.682256E+09 | 0.416537E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6629811.90 | 0.536178E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.675308E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457607E+09 |
February | 0.901968E+09 | 0.551908E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412013E+09 |
March | 0.107774E+10 | 0.603183E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398831E+09 |
April | 0.956342E+09 | 0.511139E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1077221.86 | 0.383452E+09 |
May | 0.103597E+10 | 0.537733E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26257.47 | 0.312086E+09 |
June | 0.103308E+10 | 0.525872E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 263725.37 | 0.262499E+09 |
July | 0.959235E+09 | 0.494165E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4786606.66 | 0.220560E+09 |
August | 0.107774E+10 | 0.558123E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6253103.25 | 0.180070E+09 |
September | 0.956342E+09 | 0.527671E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26159.41 | 0.147953E+09 |
October | 0.994195E+09 | 0.589639E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335704E+09 |
November | 0.984487E+09 | 0.652193E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372737E+09 |
December | 0.959235E+09 | 0.677239E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398749E+09 |
Annual Sum or Average | 0.119305E+11 | 0.690417E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12433074.02 | 0.388226E+10 |
Minimum of Months | 0.901968E+09 | 0.494165E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147953E+09 |
Maximum of Months | 0.107774E+10 | 0.677239E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6253103.25 | 0.457607E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.415134E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305088E+09 |
February | 0.571020E+09 | 0.345084E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280001E+09 |
March | 0.682301E+09 | 0.380122E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274780E+09 |
April | 0.605444E+09 | 0.323766E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 522165.79 | 0.269200E+09 |
May | 0.655854E+09 | 0.342135E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17504.44 | 0.217219E+09 |
June | 0.654023E+09 | 0.335012E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 175815.86 | 0.184669E+09 |
July | 0.607275E+09 | 0.314770E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1784274.31 | 0.153553E+09 |
August | 0.682301E+09 | 0.355113E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3604468.45 | 0.127365E+09 |
September | 0.605444E+09 | 0.331724E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17439.49 | 0.102985E+09 |
October | 0.629407E+09 | 0.368473E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231270E+09 |
November | 0.623262E+09 | 0.404154E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250195E+09 |
December | 0.607275E+09 | 0.413878E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266577E+09 |
Annual Sum or Average | 0.755301E+10 | 0.432936E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6121668.34 | 0.266290E+10 |
Minimum of Months | 0.571020E+09 | 0.314770E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102985E+09 |
Maximum of Months | 0.682301E+09 | 0.415134E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3604468.45 | 0.305088E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.639961E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439675E+10 |
February | 0.901968E+09 | 0.533044E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383440E+10 |
March | 0.107774E+10 | 0.596618E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402197E+10 |
April | 0.956342E+09 | 0.511517E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14513516.63 | 0.305485E+10 |
May | 0.103597E+10 | 0.540106E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1619046.47 | 0.266396E+10 |
June | 0.103308E+10 | 0.528748E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15903611.06 | 0.204140E+10 |
July | 0.959235E+09 | 0.498606E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94640554.34 | 0.134622E+10 |
August | 0.107774E+10 | 0.561629E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257752E+09 | 0.127661E+10 |
September | 0.956342E+09 | 0.524892E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3514256.48 | 0.187133E+10 |
October | 0.994195E+09 | 0.575517E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305560E+10 |
November | 0.984487E+09 | 0.624566E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383202E+10 |
December | 0.959235E+09 | 0.635200E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421980E+10 |
Annual Sum or Average | 0.119305E+11 | 0.677040E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387943E+09 | 0.356149E+11 |
Minimum of Months | 0.901968E+09 | 0.498606E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127661E+10 |
Maximum of Months | 0.107774E+10 | 0.639961E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257752E+09 | 0.439675E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.414945E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306018E+09 |
February | 0.570983E+09 | 0.341758E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280768E+09 |
March | 0.682256E+09 | 0.379854E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275898E+09 |
April | 0.605404E+09 | 0.323551E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 280239.86 | 0.269204E+09 |
May | 0.655811E+09 | 0.340819E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17505.41 | 0.224031E+09 |
June | 0.653980E+09 | 0.333103E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 175816.64 | 0.185433E+09 |
July | 0.607235E+09 | 0.314379E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1654194.02 | 0.162182E+09 |
August | 0.682256E+09 | 0.354011E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3626665.47 | 0.131529E+09 |
September | 0.605404E+09 | 0.333740E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17439.61 | 0.107171E+09 |
October | 0.629366E+09 | 0.368822E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233284E+09 |
November | 0.623221E+09 | 0.402363E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250870E+09 |
December | 0.607235E+09 | 0.413301E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267354E+09 |
Annual Sum or Average | 0.755252E+10 | 0.432064E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5771861.01 | 0.269374E+10 |
Minimum of Months | 0.570983E+09 | 0.314379E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107171E+09 |
Maximum of Months | 0.682256E+09 | 0.414945E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3626665.47 | 0.306018E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.679449E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708204E+09 |
February | 0.901968E+09 | 0.554534E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642545E+09 |
March | 0.107774E+10 | 0.605087E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639821E+09 |
April | 0.956342E+09 | 0.511856E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1468073.07 | 0.621727E+09 |
May | 0.103597E+10 | 0.538145E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38098.70 | 0.502547E+09 |
June | 0.103308E+10 | 0.526145E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 400597.83 | 0.418854E+09 |
July | 0.959235E+09 | 0.494536E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6024870.18 | 0.351930E+09 |
August | 0.107774E+10 | 0.558698E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9134671.92 | 0.287512E+09 |
September | 0.956342E+09 | 0.528767E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38410.65 | 0.234480E+09 |
October | 0.994195E+09 | 0.592363E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520360E+09 |
November | 0.984487E+09 | 0.655749E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.568831E+09 |
December | 0.959235E+09 | 0.681299E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611403E+09 |
Annual Sum or Average | 0.119305E+11 | 0.692663E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17104722.34 | 0.610821E+10 |
Minimum of Months | 0.901968E+09 | 0.494536E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234480E+09 |
Maximum of Months | 0.107774E+10 | 0.681299E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9134671.92 | 0.708204E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.416639E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471672E+09 |
February | 0.421807E+09 | 0.346115E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435748E+09 |
March | 0.502994E+09 | 0.380849E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434581E+09 |
April | 0.447140E+09 | 0.324116E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 761896.20 | 0.424599E+09 |
May | 0.484071E+09 | 0.342443E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23767.51 | 0.342322E+09 |
June | 0.482240E+09 | 0.335285E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 257143.84 | 0.286919E+09 |
July | 0.448971E+09 | 0.315061E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2514974.28 | 0.240311E+09 |
August | 0.502994E+09 | 0.355534E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5386309.22 | 0.197279E+09 |
September | 0.447140E+09 | 0.332303E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24369.37 | 0.160089E+09 |
October | 0.465148E+09 | 0.369492E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353675E+09 |
November | 0.460569E+09 | 0.405416E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380694E+09 |
December | 0.448971E+09 | 0.415513E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408227E+09 |
Annual Sum or Average | 0.557719E+10 | 0.433877E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8968460.42 | 0.413612E+10 |
Minimum of Months | 0.421807E+09 | 0.315061E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160089E+09 |
Maximum of Months | 0.502994E+09 | 0.416639E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5386309.22 | 0.471672E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.642312E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729324E+09 |
February | 0.901968E+09 | 0.534338E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687284E+09 |
March | 0.107774E+10 | 0.597695E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669265E+09 |
April | 0.956342E+09 | 0.512096E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 883416.03 | 0.645863E+09 |
May | 0.103597E+10 | 0.540636E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38091.15 | 0.516684E+09 |
June | 0.103308E+10 | 0.529261E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 400568.03 | 0.428247E+09 |
July | 0.959235E+09 | 0.499148E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3573344.29 | 0.362108E+09 |
August | 0.107774E+10 | 0.562266E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8302857.00 | 0.298402E+09 |
September | 0.956342E+09 | 0.525584E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38182.22 | 0.246700E+09 |
October | 0.994195E+09 | 0.576809E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551579E+09 |
November | 0.984487E+09 | 0.626356E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587934E+09 |
December | 0.959235E+09 | 0.637360E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633530E+09 |
Annual Sum or Average | 0.119305E+11 | 0.678386E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13236458.72 | 0.635692E+10 |
Minimum of Months | 0.901968E+09 | 0.499148E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246700E+09 |
Maximum of Months | 0.107774E+10 | 0.642312E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8302857.00 | 0.729324E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.416535E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473349E+09 |
February | 0.570983E+09 | 0.342848E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437080E+09 |
March | 0.682256E+09 | 0.380692E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435762E+09 |
April | 0.605404E+09 | 0.324032E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 373312.61 | 0.426255E+09 |
May | 0.655811E+09 | 0.341100E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25397.73 | 0.349337E+09 |
June | 0.653980E+09 | 0.333465E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 267067.93 | 0.288606E+09 |
July | 0.607235E+09 | 0.314873E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2457948.01 | 0.248018E+09 |
August | 0.682256E+09 | 0.354427E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5618738.54 | 0.201939E+09 |
September | 0.605404E+09 | 0.334503E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25606.98 | 0.164384E+09 |
October | 0.629366E+09 | 0.369898E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355644E+09 |
November | 0.623221E+09 | 0.403861E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381205E+09 |
December | 0.607235E+09 | 0.415130E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409419E+09 |
Annual Sum or Average | 0.755252E+10 | 0.433136E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8768071.80 | 0.417100E+10 |
Minimum of Months | 0.570983E+09 | 0.314873E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164384E+09 |
Maximum of Months | 0.682256E+09 | 0.416535E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5618738.54 | 0.473349E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.994482E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.919953E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.908565E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1304590.91 | 0.866384E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3028.03 | 0.691953E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188235.33 | 0.573621E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5275926.46 | 0.482286E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8610819.27 | 0.399050E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1003.02 | 0.329083E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747512E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819649E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877716E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15383603.02 | 0.861025E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329083E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8610819.27 | 0.994482E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120227E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110866E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111445E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2035026.06 | 0.107726E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4059.56 | 0.871947E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240662.19 | 0.727189E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6838607.26 | 0.610302E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11142460.97 | 0.504334E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 916.08 | 0.411253E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905431E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.977193E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104936E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20261732.11 | 0.105597E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411253E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11142460.97 | 0.120227E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119422E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110459E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110552E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 871683.29 | 0.109875E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913941E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73119.09 | 0.767667E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2427328.03 | 0.649080E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7877153.63 | 0.520486E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418673E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.893751E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.949688E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102144E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11249284.04 | 0.106378E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418673E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7877153.63 | 0.119422E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1351.79 | 12-JAN-22:03 |
February | 1306.65 | 01-FEB-10:09 | 945.17 | 02-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1271.98 | 16-FEB-22:03 |
March | 1306.65 | 01-MAR-10:09 | 830.87 | 22-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1175.35 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 667.05 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.68 | 01-APR-17:03 | 1281.29 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 541.21 | 17-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.56 | 05-MAY-16:00 | 954.50 | 22-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 28-JUN-16:00 | 1242.96 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 579.72 | 12-JUL-08:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.85 | 23-JUL-13:53 | 633.37 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 574.20 | 02-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.54 | 08-AUG-17:00 | 896.93 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 837.22 | 25-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.64 | 14-SEP-17:00 | 603.76 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1027.50 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1163.62 | 31-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1269.96 | 29-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1051.83 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 603.76 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 197.68 | 1351.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 899.97 | 12-JAN-22:03 |
February | 827.22 | 01-FEB-10:09 | 604.68 | 02-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 847.22 | 16-FEB-22:03 |
March | 827.22 | 01-MAR-10:09 | 502.99 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 796.86 | 28-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 354.45 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.95 | 01-APR-17:03 | 865.64 | 07-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.71 | 05-MAY-16:00 | 635.51 | 22-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.11 | 28-JUN-16:00 | 824.55 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 339.83 | 12-JUL-08:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.84 | 23-JUL-15:46 | 426.42 | 02-JUL-10:00 |
August | 827.22 | 01-AUG-09:09 | 353.24 | 02-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.03 | 08-AUG-17:00 | 598.90 | 11-AUG-04:00 |
September | 827.22 | 01-SEP-09:09 | 508.51 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 | 14-SEP-17:00 | 401.32 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 648.37 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 774.34 | 31-OCT-21:05 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 845.68 | 29-NOV-22:03 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 700.56 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.32 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 102.95 | 899.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:30 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1352.35 | 12-JAN-22:03 |
February | 1306.65 | 01-FEB-10:09 | 922.83 | 02-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1316.01 | 19-FEB-12:00 |
March | 1306.65 | 01-MAR-10:09 | 821.38 | 22-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1230.13 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 583.86 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.55 | 01-APR-17:30 | 1306.89 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 542.27 | 17-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.56 | 05-MAY-16:00 | 959.93 | 22-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 530.72 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 28-JUN-16:00 | 1241.64 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 574.59 | 12-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.62 | 23-JUL-15:46 | 639.98 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 572.97 | 02-AUG-07:30 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.54 | 08-AUG-17:00 | 910.94 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 830.09 | 25-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.64 | 14-SEP-17:00 | 608.96 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1025.02 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1163.64 | 31-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1269.91 | 29-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1052.65 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 530.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 608.96 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 100.62 | 1352.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 899.91 | 12-JAN-22:03 |
February | 827.17 | 01-FEB-10:09 | 582.59 | 02-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 847.04 | 16-FEB-22:03 |
March | 827.17 | 01-MAR-10:09 | 534.11 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 794.52 | 28-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 454.12 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.63 | 01-APR-16:00 | 854.22 | 07-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 352.78 | 17-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.71 | 05-MAY-16:00 | 641.64 | 27-MAY-17:10 |
June | 827.17 | 01-JUN-09:09 | 346.71 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.11 | 28-JUN-16:00 | 821.57 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 468.46 | 12-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.44 | 23-JUL-15:44 | 428.47 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 462.90 | 28-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.03 | 08-AUG-17:00 | 615.15 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 537.17 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 | 14-SEP-17:00 | 401.85 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 650.62 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 773.89 | 31-OCT-21:05 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 845.50 | 29-NOV-22:03 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 700.76 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 346.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.85 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 57.03 | 899.91 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 771.04 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 941.40 | 02-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 706.52 | 16-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 822.79 | 22-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 664.84 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 583.20 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.87 | 01-APR-17:03 | 709.19 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 536.46 | 17-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.12 | 05-MAY-16:00 | 545.48 | 18-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 | 28-JUN-16:00 | 725.66 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 576.91 | 12-JUL-08:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.31 | 23-JUL-15:51 | 365.46 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 571.03 | 02-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.60 | 13-AUG-15:00 | 505.26 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 829.44 | 25-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.72 | 14-SEP-17:00 | 347.54 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1027.00 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 630.95 | 31-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 737.70 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 590.61 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.54 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 137.87 | 771.04 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 511.23 | 12-JAN-24:00 |
February | 827.22 | 01-FEB-10:09 | 602.99 | 02-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 468.41 | 16-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 497.81 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 467.53 | 28-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 352.14 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.72 | 01-APR-17:03 | 499.40 | 07-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.08 | 05-MAY-16:00 | 363.28 | 18-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 | 28-JUN-16:00 | 494.96 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 336.35 | 12-JUL-08:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.97 | 30-JUL-16:00 | 245.33 | 02-JUL-04:00 |
August | 827.22 | 01-AUG-09:09 | 350.85 | 02-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.59 | 08-AUG-17:00 | 351.06 | 11-AUG-04:00 |
September | 827.22 | 01-SEP-09:09 | 503.55 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.48 | 14-SEP-17:00 | 232.24 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 648.02 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 420.73 | 31-OCT-21:05 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 489.21 | 29-NOV-23:00 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 392.43 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.24 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 71.72 | 511.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:30 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 19201.03 | 06-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 917.32 | 02-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 17762.76 | 09-FEB-07:02 |
March | 1306.65 | 01-MAR-10:09 | 812.84 | 22-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 17344.42 | 01-MAR-07:02 |
April | 1306.65 | 03-APR-09:09 | 581.12 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2399.62 | 27-APR-16:10 | 14939.22 | 19-APR-06:03 |
May | 1306.65 | 01-MAY-09:09 | 537.57 | 17-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 509.42 | 05-MAY-16:10 | 12460.82 | 11-MAY-06:05 |
June | 1306.65 | 01-JUN-09:09 | 525.50 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2158.33 | 28-JUN-17:00 | 9660.34 | 15-JUN-06:05 |
July | 1306.65 | 03-JUL-09:09 | 571.49 | 12-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3823.36 | 31-JUL-16:10 | 8590.36 | 03-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 569.72 | 02-AUG-07:30 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6068.51 | 10-AUG-17:00 | 9684.99 | 01-AUG-06:01 |
September | 1306.65 | 01-SEP-09:09 | 821.97 | 25-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 804.50 | 14-SEP-17:00 | 10676.29 | 27-SEP-06:10 |
October | 1306.65 | 02-OCT-09:09 | 1024.40 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 12603.89 | 13-OCT-07:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 16206.04 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 18714.09 | 26-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 525.50 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8590.36 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 6068.51 | 19201.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 511.38 | 12-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 580.25 | 02-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 466.77 | 16-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 530.30 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 457.77 | 28-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 447.91 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 01-APR-16:00 | 477.52 | 07-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 350.54 | 17-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.08 | 05-MAY-16:00 | 366.37 | 22-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 344.24 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 | 28-JUN-16:00 | 484.16 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 462.96 | 12-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.18 | 23-JUL-13:43 | 254.36 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 457.02 | 28-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.59 | 08-AUG-17:00 | 363.57 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 533.46 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.48 | 14-SEP-17:00 | 232.61 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 650.37 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 421.52 | 31-OCT-21:10 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 488.33 | 29-NOV-23:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 393.05 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 344.24 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.61 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 32.18 | 511.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1188.26 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 945.17 | 02-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1087.45 | 16-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 830.85 | 22-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1063.85 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 667.02 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.57 | 01-APR-17:03 | 1134.40 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 541.20 | 17-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.75 | 05-MAY-16:00 | 841.54 | 18-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.85 | 28-JUN-16:00 | 1118.20 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 579.71 | 12-JUL-08:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.50 | 23-JUL-14:10 | 569.05 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 574.19 | 02-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.47 | 13-AUG-15:00 | 786.68 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 837.21 | 25-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 14-SEP-17:00 | 539.95 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1027.50 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 983.13 | 31-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1120.57 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 911.97 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.95 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 174.57 | 1188.26 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 658.76 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 786.59 | 12-JAN-24:00 |
February | 805.43 | 01-FEB-08:09 | 604.67 | 02-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 719.57 | 16-FEB-04:00 |
March | 805.43 | 01-MAR-08:09 | 502.98 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 719.91 | 28-MAR-24:00 |
April | 805.43 | 03-APR-07:10 | 354.45 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.56 | 01-APR-17:03 | 765.21 | 07-APR-24:00 |
May | 805.43 | 01-MAY-07:10 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 05-MAY-16:00 | 558.00 | 22-MAY-24:00 |
June | 805.43 | 01-JUN-07:10 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.90 | 28-JUN-16:00 | 742.71 | 13-JUN-03:00 |
July | 805.43 | 03-JUL-07:10 | 339.83 | 12-JUL-08:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.39 | 23-JUL-15:50 | 377.65 | 02-JUL-04:00 |
August | 805.43 | 01-AUG-07:10 | 353.24 | 02-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.69 | 08-AUG-17:00 | 525.62 | 11-AUG-04:00 |
September | 805.43 | 01-SEP-07:10 | 508.50 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 | 14-SEP-17:00 | 359.26 | 18-SEP-23:00 |
October | 805.43 | 02-OCT-07:10 | 648.37 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 654.40 | 31-OCT-21:05 |
November | 805.43 | 01-NOV-07:10 | 658.76 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 742.06 | 29-NOV-23:00 |
December | 805.43 | 01-DEC-08:09 | 658.76 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 604.80 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.26 | |||||
Maximum of Months | 805.43 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 91.56 | 786.59 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:30 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1192.60 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 922.82 | 02-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1183.65 | 19-FEB-12:00 |
March | 1306.65 | 01-MAR-10:09 | 821.36 | 22-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1107.39 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 583.85 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.22 | 01-APR-17:30 | 1154.45 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 542.25 | 17-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.75 | 05-MAY-16:00 | 841.78 | 22-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 530.71 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.85 | 28-JUN-16:00 | 1117.38 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 574.59 | 12-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.83 | 23-JUL-16:06 | 574.25 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 572.96 | 02-AUG-07:30 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.53 | 08-AUG-17:00 | 798.33 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 830.07 | 25-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 14-SEP-17:00 | 543.92 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1025.02 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 983.48 | 31-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1121.33 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 919.11 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 530.71 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 543.92 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 78.22 | 1192.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 786.55 | 12-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 582.59 | 02-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 717.08 | 16-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 534.10 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 718.12 | 28-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 454.11 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.23 | 01-APR-16:00 | 756.27 | 07-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 352.77 | 17-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 05-MAY-16:00 | 560.52 | 22-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 346.70 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.90 | 28-JUN-16:00 | 739.48 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 468.44 | 12-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.59 | 23-JUL-14:07 | 384.35 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 462.89 | 28-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.69 | 08-AUG-17:00 | 538.70 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 537.16 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 | 14-SEP-17:00 | 359.37 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 650.62 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 654.01 | 31-OCT-21:05 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 740.89 | 29-NOV-23:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 606.34 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 346.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.37 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 47.69 | 786.55 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1716.55 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1587.67 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1538.47 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.18 | 01-APR-17:03 | 1605.40 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 | 05-MAY-16:00 | 1203.75 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.71 | 28-JUN-15:10 | 1597.30 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.54 | 23-JUL-13:53 | 805.69 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.63 | 13-AUG-15:10 | 1096.56 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 | 14-SEP-17:00 | 748.39 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1403.44 | 31-OCT-21:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1608.79 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1298.37 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 748.39 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.18 | 1716.55 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2099.00 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1920.35 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1901.92 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.77 | 01-APR-17:03 | 2022.11 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 | 05-MAY-16:00 | 1495.81 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.11 | 28-JUN-15:00 | 2009.33 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.34 | 23-JUL-13:53 | 1009.22 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.34 | 13-AUG-15:10 | 1392.99 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 | 14-SEP-17:00 | 922.09 | 30-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1702.93 | 31-OCT-21:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1948.17 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1589.68 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 922.09 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.77 | 2099.00 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2009.44 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1816.89 | 16-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1780.96 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.95 | 01-APR-17:03 | 1977.57 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1443.20 | 22-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 28-JUN-17:00 | 1867.99 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.77 | 24-JUL-14:00 | 947.87 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.66 | 08-AUG-17:00 | 1354.63 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 912.73 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1734.68 | 31-OCT-21:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1929.68 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1632.13 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 912.73 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.95 | 2009.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13217.29 | 12-JAN-08:10 | 36210.05 | 29616.09 | 109111.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16363.21 | 28-FEB-08:10 | 12070.02 | 9872.03 | 36370.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17207.37 | 28-MAR-07:02 | 48280.06 | 39488.12 | 145481.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 37579.89 | 28-APR-06:02 | 7623.17 | 9872.16 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38195.91 | 08-MAY-06:02 | 6352.64 | 8226.80 | 43983.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 40941.21 | 12-JUN-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41256.00 | 10-JUL-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 41280.04 | 14-AUG-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41195.17 | 05-SEP-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 37900.65 | 10-OCT-06:02 | 7623.17 | 9872.16 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17325.58 | 06-NOV-09:00 | 6035.01 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15602.87 | 07-DEC-08:06 | 30175.04 | 24680.07 | 90925.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13217.29 | 2541.06 | 2193.73 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41280.04 | 48280.06 | 39488.12 | 145481.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 900.23 |
February | 1684.91 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.27 |
March | 2688.68 | 14-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.84 |
April | 8366.75 | 27-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.28 | 0.00 |
May | 8719.59 | 15-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.44 |
June | 8584.26 | 28-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.14 |
July | 9875.28 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.77 | 0.00 |
August | 9927.95 | 10-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.42 | 0.00 |
September | 7710.57 | 14-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.88 |
October | 5342.16 | 04-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.71 |
November | 2234.73 | 04-NOV-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.21 |
December | 168.60 | 02-DEC-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9927.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.77 | 900.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1627.93 | 14-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.01 |
February | 1419.48 | 18-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.76 |
March | 2395.55 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.12 |
April | 2855.51 | 27-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.24 | 0.00 |
May | 3142.25 | 15-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.87 |
June | 3287.64 | 28-JUN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.79 | 0.00 |
July | 4504.71 | 31-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.42 | 0.00 |
August | 4604.48 | 14-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.32 | 0.00 |
September | 3584.67 | 11-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.92 |
October | 2116.68 | 04-OCT-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.14 |
November | 1212.04 | 22-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.54 |
December | 1292.06 | 23-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1212.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4604.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.42 | 218.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2191.10 | 13-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.01 |
February | 2305.48 | 10-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.26 |
March | 3065.64 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.54 |
April | 3254.11 | 27-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.99 | 0.00 |
May | 3535.21 | 15-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 |
June | 3696.79 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.53 | 0.00 |
July | 4855.92 | 24-JUL-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.47 | 0.00 |
August | 5063.10 | 14-AUG-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.35 |
September | 4298.95 | 11-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.44 |
October | 2993.00 | 04-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.20 |
November | 1880.53 | 16-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.98 |
December | 1871.08 | 20-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1871.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5063.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.47 | 277.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5871.26 | 12-JAN-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7173.82 | 28-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8925.70 | 02-MAR-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14026.84 | 27-APR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14761.86 | 08-MAY-06:02 | 6352.64 | 8226.80 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 27256.90 | 12-JUN-06:02 | 6352.64 | 8226.80 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29810.80 | 31-JUL-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30388.77 | 14-AUG-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 27283.94 | 11-SEP-06:01 | 8893.70 | 11517.52 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13507.27 | 04-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7847.05 | 06-NOV-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6192.81 | 06-DEC-16:10 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5871.26 | 2541.06 | 2193.73 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30388.77 | 8893.70 | 11517.52 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5502.10 | 11-JAN-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6482.67 | 28-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8056.41 | 02-MAR-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15449.30 | 27-APR-15:40 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16471.23 | 15-MAY-15:40 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16839.33 | 28-JUN-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20647.75 | 24-JUL-06:03 | 5082.11 | 6581.44 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 27822.08 | 14-AUG-06:02 | 6352.64 | 8226.80 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16336.25 | 11-SEP-15:50 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13391.75 | 04-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6349.14 | 02-NOV-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5727.48 | 05-DEC-16:15 | 12070.02 | 9872.03 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5502.10 | 5082.11 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27822.08 | 12070.02 | 9872.03 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 988.01 | 11-JAN-16:20 | 1272.23 | 966.90 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.35 |
February | 1257.73 | 28-FEB-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1340.44 | 10-MAR-14:50 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.14 |
April | 4444.80 | 27-APR-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 28.75 | 0.00 |
May | 4737.77 | 15-MAY-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 |
June | 5096.03 | 21-JUN-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 | 0.00 |
July | 6264.29 | 24-JUL-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 44.75 | 0.00 |
August | 5623.08 | 09-AUG-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 52.43 | 0.00 |
September | 4237.67 | 12-SEP-14:50 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.44 | 0.00 |
October | 2569.79 | 04-OCT-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 |
November | 1196.23 | 02-NOV-14:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.76 |
December | 920.08 | 05-DEC-15:10 | 1272.23 | 697.95 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 920.08 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6264.29 | 1306.65 | 966.90 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 52.43 | 110.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 635.42 | 11-JAN-16:10 | 805.43 | 581.39 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.82 |
February | 845.13 | 27-FEB-15:50 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.21 |
March | 2637.69 | 14-MAR-09:50 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.10 |
April | 6705.12 | 27-APR-09:20 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.49 |
May | 10817.48 | 14-MAY-09:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.43 |
June | 13439.80 | 25-JUN-08:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.36 |
July | 12788.35 | 30-JUL-09:02 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.02 |
August | 12770.74 | 13-AUG-09:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.03 |
September | 10503.01 | 10-SEP-10:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.06 |
October | 4718.12 | 04-OCT-09:20 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.03 |
November | 837.23 | 04-NOV-10:40 | 254.35 | 104.74 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.72 |
December | 676.46 | 05-DEC-10:40 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 635.42 | 169.56 | 69.83 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.72 | |
Maximum of Months | 13439.80 | 827.22 | 581.39 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6682.90 | 20-JAN-13:30 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.52 |
February | 8650.31 | 27-FEB-14:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.25 |
March | 9911.12 | 14-MAR-13:40 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.75 |
April | 12055.66 | 27-APR-13:05 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 15.73 | 0.00 |
May | 19332.30 | 14-MAY-15:12 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.90 |
June | 11557.04 | 11-JUN-12:43 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.36 |
July | 18658.76 | 23-JUL-13:02 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.08 |
August | 19211.91 | 13-AUG-13:12 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 |
September | 21738.02 | 10-SEP-12:52 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.09 |
October | 16703.39 | 08-OCT-13:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.52 |
November | 9218.65 | 04-NOV-13:30 | 275.09 | 165.44 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6618.76 | 05-DEC-12:30 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6618.76 | 200.88 | 82.72 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21738.02 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 15.73 | 234.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 778.39 | 05-JAN-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.22 |
February | 3427.70 | 27-FEB-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.28 |
March | 5191.55 | 14-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.21 |
April | 8191.73 | 26-APR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 | 0.00 |
May | 16192.24 | 14-MAY-16:31 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.09 |
June | 14776.58 | 25-JUN-16:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.73 |
July | 15368.38 | 23-JUL-17:02 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.11 |
August | 15037.82 | 06-AUG-16:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.30 |
September | 15214.92 | 10-SEP-15:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.86 |
October | 6643.08 | 04-OCT-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.15 |
November | 2730.70 | 04-NOV-15:30 | 84.78 | 52.37 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 |
December | 848.74 | 05-DEC-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 778.39 | 0.00 | 52.37 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16192.24 | 805.38 | 314.21 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 | 237.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 976.72 | 11-JAN-16:10 | 1272.23 | 911.18 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.55 |
February | 1167.82 | 28-FEB-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1222.45 | 10-MAR-14:40 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.33 |
April | 2624.94 | 27-APR-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.54 | 0.00 |
May | 3121.61 | 05-MAY-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 0.00 |
June | 3842.36 | 21-JUN-15:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 0.00 |
July | 4782.13 | 24-JUL-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.98 | 0.00 |
August | 4427.39 | 09-AUG-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 28.63 | 0.00 |
September | 3292.18 | 14-SEP-15:50 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 | 0.00 |
October | 2026.78 | 04-OCT-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.26 |
November | 1230.69 | 06-NOV-12:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.39 |
December | 970.35 | 29-DEC-15:40 | 1272.23 | 869.41 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 970.35 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4782.13 | 1306.65 | 911.18 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 28.63 | 59.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 634.79 | 20-JAN-11:00 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.98 |
February | 775.22 | 27-FEB-15:40 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 |
March | 1529.20 | 14-MAR-10:00 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.84 |
April | 5004.83 | 27-APR-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.98 |
May | 8454.45 | 15-MAY-06:02 | 1017.38 | 628.46 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.90 |
June | 9878.75 | 25-JUN-08:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.49 |
July | 8506.40 | 31-JUL-06:03 | 678.26 | 418.98 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.95 |
August | 8543.85 | 13-AUG-09:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.99 |
September | 5800.08 | 11-SEP-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.47 |
October | 3999.37 | 04-OCT-08:30 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.57 |
November | 855.51 | 02-NOV-10:40 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.03 |
December | 726.73 | 05-DEC-10:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 634.79 | 211.95 | 87.28 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | |
Maximum of Months | 9878.75 | 1017.38 | 628.46 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2011.24 | 20-JAN-13:30 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1964.18 |
February | 5046.51 | 27-FEB-15:00 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.25 |
March | 7618.66 | 02-MAR-13:07 | 7633.40 | 2978.07 | 8611.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1302.82 |
April | 9231.26 | 27-APR-13:40 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 225.85 | 0.00 |
May | 11350.75 | 14-MAY-15:12 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.94 |
June | 7100.77 | 28-JUN-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 77.12 | 0.00 |
July | 11452.52 | 30-JUL-13:42 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.88 |
August | 13334.41 | 06-AUG-14:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.60 |
September | 15472.50 | 10-SEP-13:42 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.69 |
October | 11183.64 | 04-OCT-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.91 |
November | 6740.31 | 04-NOV-13:40 | 137.54 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4026.51 | 05-DEC-13:10 | 7633.40 | 2978.07 | 8611.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1495.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2011.24 | 137.54 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15472.50 | 7633.40 | 2978.07 | 8611.42 | 0.00 | 0.00 | 0.00 | 0.00 | 225.85 | 1964.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 732.39 | 20-JAN-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.70 |
February | 2075.73 | 27-FEB-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.29 |
March | 2997.53 | 02-MAR-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.64 |
April | 5812.50 | 26-APR-17:30 | 84.78 | 104.74 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 |
May | 12780.41 | 14-MAY-17:11 | 0.00 | 122.19 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.60 |
June | 8229.54 | 18-JUN-17:22 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.54 |
July | 12514.67 | 30-JUL-17:42 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.25 |
August | 11702.89 | 06-AUG-17:52 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.53 |
September | 10306.68 | 10-SEP-17:02 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.05 |
October | 5838.74 | 04-OCT-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.10 |
November | 2247.66 | 04-NOV-15:30 | 84.78 | 52.37 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.94 |
December | 831.56 | 05-DEC-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 732.39 | 0.00 | 52.37 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 | |
Maximum of Months | 12780.41 | 805.38 | 314.21 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1047.03 | 11-JAN-16:20 | 1272.23 | 966.89 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.61 |
February | 1292.63 | 28-FEB-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1353.33 | 10-MAR-14:50 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.74 |
April | 4080.33 | 27-APR-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 24.13 | 0.00 |
May | 4324.41 | 15-MAY-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 |
June | 4745.41 | 21-JUN-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 | 0.00 |
July | 7041.80 | 24-JUL-06:03 | 1071.35 | 661.80 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.46 |
August | 6816.13 | 14-AUG-06:02 | 1339.19 | 827.25 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.24 |
September | 4076.82 | 12-SEP-14:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.18 | 0.00 |
October | 2648.85 | 04-OCT-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.70 |
November | 1251.43 | 02-NOV-14:10 | 2544.47 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.51 |
December | 998.65 | 05-DEC-15:00 | 1306.65 | 664.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 998.65 | 1071.35 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7041.80 | 2544.47 | 992.69 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 24.13 | 95.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 712.32 | 20-JAN-11:10 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.65 |
February | 1757.02 | 08-FEB-11:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.63 |
March | 5687.10 | 01-MAR-13:01 | 5638.00 | 2199.59 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.28 |
April | 7411.76 | 27-APR-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 |
May | 12254.04 | 14-MAY-08:43 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.59 |
June | 11959.47 | 25-JUN-07:42 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.62 |
July | 14400.76 | 30-JUL-08:52 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.21 |
August | 13246.96 | 13-AUG-08:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.55 |
September | 8533.43 | 10-SEP-09:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.18 |
October | 5902.27 | 04-OCT-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.12 |
November | 2926.68 | 02-NOV-12:02 | 4027.14 | 1571.14 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.04 |
December | 775.42 | 05-DEC-11:10 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 712.32 | 169.56 | 69.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 | |
Maximum of Months | 14400.76 | 5638.00 | 2199.59 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7165.95 | 20-JAN-13:12 | 6361.16 | 2481.72 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.47 |
February | 8723.19 | 27-FEB-14:10 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.09 |
March | 10236.54 | 01-MAR-13:30 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.07 |
April | 11518.31 | 27-APR-13:05 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 13.26 | 0.00 |
May | 12498.65 | 07-MAY-15:32 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.25 |
June | 10615.31 | 11-JUN-12:33 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.16 |
July | 19113.07 | 30-JUL-12:12 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.92 |
August | 18441.03 | 06-AUG-12:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.44 |
September | 18650.75 | 10-SEP-13:02 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.52 |
October | 13483.65 | 04-OCT-12:50 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.77 |
November | 9332.76 | 04-NOV-13:30 | 275.09 | 165.44 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7533.80 | 05-DEC-12:30 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7165.95 | 200.88 | 82.72 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19113.07 | 6361.16 | 2481.72 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 13.26 | 149.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 808.43 | 05-JAN-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.46 |
February | 3479.35 | 27-FEB-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.30 |
March | 5061.31 | 14-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.42 |
April | 7922.93 | 26-APR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 | 0.00 |
May | 15135.95 | 07-MAY-16:51 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.78 |
June | 14420.49 | 18-JUN-16:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.86 |
July | 15588.40 | 30-JUL-17:31 | 0.00 | 139.64 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.37 |
August | 13793.38 | 06-AUG-16:32 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.38 |
September | 13070.69 | 10-SEP-16:22 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.52 |
October | 6603.14 | 04-OCT-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.11 |
November | 2840.30 | 04-NOV-15:30 | 84.78 | 52.37 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.63 |
December | 1142.99 | 05-DEC-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 808.43 | 0.00 | 52.37 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15588.40 | 805.38 | 314.21 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 | 283.86 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.124450E+12 | 221465.13 | 02-JAN-07:10 | 0.409388E+11 | 61171.46 | 06-JAN-07:00 |
February | 0.965844E+11 | 172491.20 | 21-FEB-07:10 | 0.300519E+11 | 56912.73 | 18-FEB-07:30 |
March | 0.978074E+11 | 111182.85 | 06-MAR-07:10 | 0.216383E+11 | 49191.56 | 01-MAR-07:19 |
April | 0.895607E+11 | 118500.72 | 27-APR-15:09 | 0.152085E+11 | 40222.32 | 19-APR-06:10 |
May | 0.969660E+11 | 111661.93 | 15-MAY-15:20 | 0.123139E+11 | 25499.53 | 18-MAY-06:19 |
June | 0.101140E+12 | 119242.54 | 28-JUN-15:30 | 0.108990E+11 | 12062.27 | 15-JUN-06:30 |
July | 0.109739E+12 | 140939.44 | 31-JUL-15:20 | 0.106111E+11 | 9845.27 | 03-JUL-11:20 |
August | 0.124066E+12 | 145081.95 | 10-AUG-15:09 | 0.110684E+11 | 9819.29 | 01-AUG-11:09 |
September | 0.977976E+11 | 120060.33 | 14-SEP-15:09 | 0.105743E+11 | 16796.97 | 27-SEP-06:10 |
October | 0.929351E+11 | 98866.81 | 04-OCT-15:09 | 0.132521E+11 | 27528.21 | 16-OCT-06:40 |
November | 0.996603E+11 | 128924.92 | 24-NOV-07:10 | 0.248531E+11 | 49768.16 | 13-NOV-07:49 |
December | 0.112736E+12 | 182522.19 | 26-DEC-07:10 | 0.361192E+11 | 61495.77 | 26-DEC-08:20 |
Annual Sum or Average | 0.124344E+13 | 0.237529E+12 | ||||
Minimum of Months | 0.895607E+11 | 98866.81 | 0.105743E+11 | 9819.29 | ||
Maximum of Months | 0.124450E+12 | 221465.13 | 0.409388E+11 | 61495.77 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.203678E+11 | 0.628818E+10 | 0.593559E+11 | 0.983435E+09 | 0.351846E+10 | 12379742.02 | 0.339235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179483E+11 | 0.491554E+10 | 0.537310E+11 | 0.889436E+09 | 0.312336E+10 | 11196021.66 | 0.158133E+11 | 0.152210E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209041E+11 | 0.442863E+10 | 0.617796E+11 | 0.102914E+10 | 0.393614E+10 | 12675672.10 | 0.509991E+10 | 0.617225E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.184074E+11 | 0.340219E+10 | 0.572952E+11 | 0.946215E+09 | 0.471870E+10 | 11960507.72 | 0.178184E+10 | 0.299725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197496E+11 | 0.290318E+10 | 0.605677E+11 | 0.100556E+10 | 0.657642E+10 | 12527707.06 | 0.700377E+09 | 0.545057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.195722E+11 | 0.254241E+10 | 0.594895E+11 | 0.989873E+09 | 0.819445E+10 | 12231776.97 | 0.296915E+09 | 0.100420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.183254E+11 | 0.273940E+10 | 0.583622E+11 | 0.961670E+09 | 0.103444E+11 | 12256437.81 | 65714178.73 | 0.189280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.205063E+11 | 0.320959E+10 | 0.617796E+11 | 0.102890E+10 | 0.119946E+11 | 12675672.10 | 75155687.45 | 0.254587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.185536E+11 | 0.386004E+10 | 0.572729E+11 | 0.946074E+09 | 0.761021E+10 | 11960507.72 | 0.290659E+09 | 0.925222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.196323E+11 | 0.500879E+10 | 0.593671E+11 | 0.982780E+09 | 0.459260E+10 | 12379742.02 | 0.191646E+10 | 0.142271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.200207E+11 | 0.580107E+10 | 0.580818E+11 | 0.965090E+09 | 0.331993E+10 | 12059151.09 | 0.111676E+11 | 0.291947E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.198945E+11 | 0.653724E+10 | 0.583511E+11 | 0.962971E+09 | 0.330018E+10 | 12256437.81 | 0.236771E+11 | 177140.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233882E+12 | 0.516363E+11 | 0.705434E+12 | 0.116911E+11 | 0.712296E+11 | 0.146559E+09 | 0.948086E+11 | 0.746130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.179483E+11 | 0.254241E+10 | 0.537310E+11 | 0.889436E+09 | 0.312336E+10 | 11196021.66 | 65714178.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.209041E+11 | 0.653724E+10 | 0.617796E+11 | 0.102914E+10 | 0.119946E+11 | 12675672.10 | 0.339235E+11 | 0.254587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.294263E+11 | 0.00 | 0.115125E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.196020E+11 | 0.00 | 0.104499E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.976401E+10 | 0.00 | 0.118743E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.427869E+10 | 0.00 | 0.109298E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.102604E+10 | 0.00 | 0.112879E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 42392625.78 | 0.00 | 0.108566E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.106111E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.110684E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.150403E+09 | 0.00 | 0.104239E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.231915E+10 | 0.00 | 0.109330E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.139777E+11 | 0.00 | 0.108754E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.249102E+11 | 0.00 | 0.112090E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.105497E+12 | 0.00 | 0.132032E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.104239E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.294263E+11 | 0.00 | 0.118743E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 25003.79 | 02-JAN-16:30 | 5686.19 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 839.24 | 04-JAN-08:20 | 7245.14 | 02-JAN-06:30 | 6.85 | 02-JAN-08:09 | 180407.71 | 02-JAN-06:30 |
February | 23928.11 | 02-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 838.36 | 02-FEB-08:20 | 4337.04 | 21-FEB-06:10 | 6.85 | 03-FEB-12:09 | 132898.99 | 21-FEB-07:10 |
March | 22850.42 | 22-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 837.29 | 22-MAR-07:19 | 5093.96 | 02-MAR-15:09 | 6.85 | 01-MAR-08:09 | 79872.32 | 06-MAR-07:10 |
April | 20891.34 | 03-APR-07:10 | 5686.19 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 834.69 | 03-APR-07:19 | 17862.61 | 27-APR-14:30 | 6.85 | 07-APR-16:10 | 46345.61 | 18-APR-06:10 |
May | 20047.80 | 17-MAY-07:10 | 3328.83 | 01-MAY-19:19 | 45864.70 | 01-MAY-07:10 | 833.57 | 17-MAY-07:19 | 19187.62 | 15-MAY-15:09 | 6.85 | 09-MAY-16:10 | 20741.04 | 18-MAY-06:10 |
June | 19864.35 | 29-JUN-07:10 | 3328.83 | 01-JUN-19:00 | 45864.70 | 01-JUN-07:10 | 833.33 | 29-JUN-07:19 | 18803.46 | 28-JUN-15:30 | 6.85 | 06-JUN-16:10 | 8786.25 | 15-JUN-06:19 |
July | 20633.80 | 12-JUL-08:20 | 3328.83 | 01-JUL-20:10 | 45864.70 | 03-JUL-07:10 | 834.28 | 12-JUL-07:40 | 25912.14 | 31-JUL-15:09 | 6.85 | 15-JUL-16:10 | 3694.86 | 03-JUL-06:19 |
August | 20471.70 | 28-AUG-07:30 | 5686.19 | 16-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 834.13 | 28-AUG-07:40 | 26438.00 | 10-AUG-15:09 | 6.85 | 06-AUG-16:49 | 5644.57 | 18-AUG-06:19 |
September | 22922.38 | 25-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 837.38 | 25-SEP-07:19 | 21875.93 | 11-SEP-15:39 | 6.85 | 01-SEP-05:10 | 15187.97 | 28-SEP-06:10 |
October | 24860.84 | 31-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 839.97 | 31-OCT-07:19 | 15151.20 | 04-OCT-15:30 | 6.85 | 30-OCT-16:10 | 45046.66 | 30-OCT-06:10 |
November | 25003.79 | 06-NOV-16:49 | 5686.19 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 839.97 | 03-NOV-07:19 | 3677.82 | 04-NOV-14:09 | 6.85 | 14-NOV-06:19 | 90233.44 | 24-NOV-07:10 |
December | 25003.79 | 01-DEC-16:19 | 5686.19 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 839.99 | 28-DEC-08:20 | 4649.39 | 26-DEC-07:10 | 6.85 | 01-DEC-06:19 | 142502.55 | 26-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 19864.35 | 3328.83 | 45864.70 | 833.33 | 3677.82 | 6.85 | 3694.86 | |||||||
Maximum of Months | 25003.79 | 5686.19 | 45864.70 | 839.99 | 26438.00 | 6.85 | 180407.71 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9242.68 | 27-FEB-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8093.85 | 18-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 38424.54 | 27-APR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30971.02 | 04-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37856.68 | 28-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 54133.12 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 56870.60 | 29-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37324.11 | 14-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21587.68 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13297.57 | 04-NOV-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 210.29 | 05-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 56870.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 221465.13 | 02-JAN-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 7145.95 | 6.85 | 178948.94 | 0.00 | 0.00 |
February | 172491.20 | 21-FEB-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 4221.96 | 6.85 | 132898.99 | 0.00 | 0.00 |
March | 111182.85 | 06-MAR-07:10 | 6870.98 | 21098.80 | 0.00 | 243.53 | 3090.37 | 6.85 | 79872.32 | 0.00 | 0.00 |
April | 118500.72 | 27-APR-15:09 | 19671.42 | 42072.41 | 0.00 | 831.72 | 17493.78 | 6.85 | 0.00 | 38424.54 | 0.00 |
May | 111661.93 | 15-MAY-15:20 | 19671.42 | 42072.41 | 0.00 | 831.72 | 19018.36 | 6.85 | 0.00 | 30061.18 | 0.00 |
June | 119242.54 | 28-JUN-15:30 | 19671.42 | 42072.41 | 0.00 | 831.72 | 18803.46 | 6.85 | 0.00 | 37856.68 | 0.00 |
July | 140939.44 | 31-JUL-15:20 | 19671.42 | 42072.41 | 0.00 | 831.72 | 25687.01 | 6.85 | 0.00 | 52670.04 | 0.00 |
August | 145081.95 | 10-AUG-15:09 | 19671.42 | 42072.41 | 0.00 | 831.72 | 26438.00 | 6.85 | 0.00 | 56061.56 | 0.00 |
September | 120060.33 | 14-SEP-15:09 | 19671.42 | 42072.41 | 0.00 | 831.72 | 21080.21 | 6.85 | 0.00 | 36397.72 | 0.00 |
October | 98866.81 | 04-OCT-15:09 | 19671.42 | 42072.41 | 0.00 | 831.72 | 14874.90 | 6.85 | 0.00 | 21409.51 | 0.00 |
November | 128924.92 | 24-NOV-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 3321.23 | 6.85 | 90233.44 | 0.00 | 0.00 |
December | 182522.19 | 26-DEC-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 4649.39 | 6.85 | 142502.55 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 98866.81 | 6870.98 | 21098.80 | 0.00 | 243.53 | 3090.37 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 221465.13 | 19671.42 | 42072.41 | 5686.19 | 831.72 | 26438.00 | 6.85 | 178948.94 | 56061.56 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 53220.10 | 07-JAN-07:00 | 0.00 | 10112.23 | 20-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 48501.05 | 18-FEB-07:19 | 0.00 | 10123.74 | 08-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 40302.60 | 01-MAR-07:19 | 0.00 | 10114.67 | 01-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 31460.12 | 19-APR-06:19 | 0.00 | 10062.47 | 04-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 17156.65 | 18-MAY-06:30 | 0.00 | 9992.92 | 02-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 4164.29 | 15-JUN-06:10 | 0.00 | 9905.37 | 01-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9845.27 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9819.29 | 01-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 7988.52 | 28-SEP-06:10 | 0.00 | 9857.66 | 26-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 19387.27 | 16-OCT-06:00 | 0.00 | 9923.51 | 30-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 41315.08 | 13-NOV-07:00 | 0.00 | 10010.95 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 52411.23 | 26-DEC-08:09 | 0.00 | 10076.38 | 26-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9819.29 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 53220.10 | 0.00 | 10123.74 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 19.61 | 0.67 | 19.61 | 0.00 | 19.61 | 0.00 | 19.61 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 19.61 | 0.67 | 19.61 | 0.00 | 19.61 | 0.00 | 19.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.61 | 0.67 | 19.61 | 0.00 | 19.61 | 0.00 | 19.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 19.31 | 2.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.00 | 19.31 | 2.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 19.31 | 2.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 18.81 | 1.17 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
February | 0.17 | 19.26 | 0.17 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 18.53 | 0.33 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
Annual Sum or Average | 2.00 | 18.78 | 1.67 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 19.26 | 1.17 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.67 | 17.49 | 5.50 | 17.95 | 0.00 | 17.95 | 0.00 | 17.95 |
February | 2.67 | 17.72 | 2.00 | 18.10 | 0.00 | 18.10 | 0.00 | 18.10 |
March | 0.17 | 19.13 | 0.17 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 18.41 | 0.33 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 |
December | 3.67 | 18.72 | 3.17 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
Annual Sum or Average | 15.67 | 17.86 | 11.17 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.67 | 19.13 | 5.50 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.17 | 15.54 | 1.67 | 15.78 | 0.00 | 15.78 | 0.00 | 15.78 |
February | 1.17 | 16.26 | 0.67 | 16.60 | 0.00 | 16.60 | 0.00 | 16.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.63 | 1.00 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.66 | 1.50 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.82 | 4.33 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.85 | 3.67 | 27.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.73 | 1.00 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 18.22 | 0.17 | 18.58 | 0.00 | 18.58 | 0.00 | 18.58 |
December | 1.50 | 16.75 | 0.50 | 17.38 | 0.00 | 17.38 | 0.00 | 17.38 |
Annual Sum or Average | 9.17 | 15.93 | 3.00 | 16.28 | 11.67 | 21.91 | 11.50 | 23.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.17 | 18.22 | 1.67 | 18.58 | 4.33 | 27.85 | 4.33 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 16.07 | 0.67 | 16.62 | 0.00 | 16.62 | 0.00 | 16.62 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.44 | 0.83 | 27.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.61 | 2.33 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.48 | 1.83 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.83 | 3.50 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.92 | 3.33 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.10 | 1.83 | 28.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.66 | 0.50 | 27.66 |
November | 0.17 | 19.34 | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
December | 0.67 | 17.84 | 0.33 | 18.29 | 0.00 | 18.29 | 0.00 | 18.29 |
Annual Sum or Average | 4.00 | 16.50 | 1.17 | 17.12 | 14.83 | 25.03 | 14.17 | 26.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.34 | 0.67 | 19.34 | 3.67 | 28.10 | 3.50 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.17 | 15.54 | 2.00 | 15.75 | 0.00 | 15.75 | 0.00 | 15.75 |
February | 1.00 | 15.74 | 0.83 | 15.81 | 0.00 | 15.81 | 0.00 | 15.81 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.36 | 0.33 | 27.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.04 | 2.67 | 28.06 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.83 | 2.00 | 27.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.34 | 3.00 | 28.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.17 | 2.00 | 28.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.84 | 2.00 | 27.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 18.27 | 0.17 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
December | 1.33 | 16.41 | 0.67 | 16.64 | 0.00 | 16.64 | 0.00 | 16.64 |
Annual Sum or Average | 8.83 | 15.79 | 3.67 | 16.01 | 20.33 | 23.48 | 12.00 | 24.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.17 | 18.27 | 2.00 | 18.61 | 5.50 | 28.34 | 3.00 | 28.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 19.28 | 2.83 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
February | 0.17 | 19.40 | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.43 | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Annual Sum or Average | 3.17 | 19.30 | 3.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 19.43 | 2.83 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.30 | 0.67 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.35 | 0.67 | 27.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.44 | 0.83 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.64 | 2.67 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.53 | 3.67 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.53 | 0.83 | 27.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 18.30 | 0.67 | 18.30 | 8.67 | 26.31 | 8.67 | 26.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 18.30 | 0.67 | 18.30 | 3.67 | 27.64 | 3.67 | 27.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 58.67 | 18.85 | 58.67 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
February | 31.17 | 18.80 | 31.17 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
March | 21.17 | 19.33 | 21.17 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
April | 11.33 | 19.58 | 11.33 | 19.58 | 0.00 | 19.58 | 0.00 | 19.58 |
May | 1.50 | 19.91 | 1.50 | 19.91 | 0.50 | 20.98 | 0.50 | 21.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.50 | 2.00 | 27.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.62 | 2.67 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.84 | 1.83 | 27.84 |
October | 2.00 | 19.95 | 2.00 | 19.95 | 0.50 | 20.80 | 0.50 | 21.47 |
November | 26.17 | 19.31 | 26.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
December | 48.17 | 18.99 | 48.17 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
Annual Sum or Average | 200.17 | 19.05 | 200.17 | 19.05 | 7.50 | 19.20 | 7.50 | 19.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 58.67 | 19.95 | 58.67 | 19.95 | 2.67 | 27.84 | 2.67 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 18.66 | 0.83 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.70 | 1.33 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.52 | 0.83 | 27.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.00 | 1.83 | 27.99 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.85 | 1.67 | 27.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.75 | 1.00 | 27.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 18.66 | 0.83 | 18.66 | 13.33 | 26.80 | 6.67 | 27.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 18.66 | 0.83 | 18.66 | 4.33 | 28.00 | 1.83 | 27.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 19.24 | 2.17 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
February | 0.17 | 19.34 | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.32 | 0.33 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Annual Sum or Average | 2.83 | 19.26 | 2.67 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 19.34 | 2.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.34 | 0.33 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.71 | 1.17 | 27.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.61 | 2.33 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.08 | 3.00 | 28.08 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.85 | 3.83 | 27.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.79 | 1.33 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
Annual Sum or Average | 0.67 | 18.06 | 0.33 | 18.38 | 11.67 | 27.10 | 11.67 | 27.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 18.34 | 0.33 | 18.61 | 3.83 | 28.08 | 3.83 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.36 | 0.33 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.42 | 0.83 | 27.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.55 | 2.17 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.43 | 1.50 | 27.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.70 | 3.67 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.88 | 3.17 | 27.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.14 | 1.83 | 28.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.56 | 1.17 | 27.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 18.36 | 0.33 | 18.61 | 14.50 | 27.22 | 14.50 | 27.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 18.36 | 0.33 | 18.61 | 3.67 | 28.14 | 3.67 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.33 | 0.33 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.00 | 27.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.95 | 2.83 | 27.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.76 | 1.83 | 27.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.19 | 3.00 | 28.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.08 | 2.00 | 28.09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.77 | 2.00 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
Annual Sum or Average | 0.67 | 18.05 | 0.33 | 18.36 | 19.83 | 27.53 | 11.67 | 27.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 18.33 | 0.33 | 18.59 | 5.50 | 28.19 | 3.00 | 28.17 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.88 | 33.67 | 22.68 | 33.67 | 22.50 |
February | 435.83 | 23.53 | 0.00 | 23.53 | 0.00 | 23.53 |
March | 346.67 | 23.92 | 2.83 | 23.93 | 0.00 | 23.93 |
April | 123.83 | 23.94 | 68.00 | 24.34 | 0.00 | 24.34 |
May | 6.17 | 24.00 | 172.50 | 24.82 | 0.00 | 24.82 |
June | 0.00 | 0.00 | 236.50 | 24.75 | 0.00 | 24.75 |
July | 0.00 | 0.00 | 383.50 | 24.60 | 0.00 | 24.60 |
August | 0.00 | 0.00 | 456.33 | 24.43 | 0.00 | 24.43 |
September | 0.00 | 0.00 | 326.67 | 24.62 | 0.00 | 24.62 |
October | 57.67 | 23.87 | 81.33 | 24.78 | 0.00 | 24.78 |
November | 318.83 | 23.72 | 24.17 | 23.81 | 0.00 | 23.81 |
December | 497.00 | 23.45 | 0.00 | 23.45 | 0.00 | 23.45 |
Annual Sum or Average | 2288.00 | 23.49 | 1785.50 | 23.96 | 33.67 | 23.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.68 | 0.00 | 22.50 |
Maximum of Months | 502.00 | 24.00 | 456.33 | 24.82 | 33.67 | 24.82 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.31 | 123.17 | 21.08 | 123.17 | 20.92 |
February | 451.17 | 22.01 | 45.50 | 21.87 | 45.50 | 21.75 |
March | 507.67 | 23.07 | 0.50 | 23.07 | 0.50 | 23.07 |
April | 346.17 | 23.45 | 28.50 | 23.55 | 0.00 | 23.55 |
May | 171.33 | 23.70 | 60.33 | 23.92 | 0.00 | 23.92 |
June | 41.83 | 23.72 | 118.33 | 24.37 | 0.00 | 24.37 |
July | 1.83 | 23.69 | 278.33 | 24.45 | 0.00 | 24.45 |
August | 8.83 | 23.65 | 354.33 | 24.32 | 0.00 | 24.32 |
September | 49.17 | 23.48 | 181.17 | 24.27 | 0.00 | 24.27 |
October | 331.00 | 23.22 | 9.17 | 23.27 | 0.00 | 23.27 |
November | 465.67 | 22.43 | 1.67 | 22.42 | 1.67 | 22.41 |
December | 497.00 | 21.75 | 39.33 | 21.65 | 39.33 | 21.57 |
Annual Sum or Average | 3373.67 | 22.49 | 1240.33 | 22.82 | 210.17 | 22.71 |
Minimum of Months | 1.83 | 21.31 | 0.50 | 21.08 | 0.00 | 20.92 |
Maximum of Months | 507.67 | 23.72 | 354.33 | 24.45 | 123.17 | 24.45 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.68 | 250.33 | 20.43 | 250.33 | 20.31 |
February | 454.00 | 21.26 | 150.50 | 20.99 | 150.50 | 20.83 |
March | 512.00 | 22.30 | 30.83 | 22.20 | 30.83 | 22.11 |
April | 394.50 | 22.94 | 17.83 | 23.01 | 0.33 | 23.00 |
May | 246.00 | 23.34 | 45.33 | 23.49 | 0.00 | 23.49 |
June | 112.50 | 23.53 | 90.50 | 23.92 | 0.00 | 23.92 |
July | 55.17 | 23.62 | 246.00 | 24.20 | 0.00 | 24.20 |
August | 50.00 | 23.49 | 299.17 | 24.16 | 0.00 | 24.16 |
September | 170.67 | 23.32 | 114.17 | 23.69 | 0.00 | 23.69 |
October | 442.67 | 22.69 | 2.17 | 22.67 | 2.17 | 22.66 |
November | 489.00 | 21.62 | 87.67 | 21.42 | 87.67 | 21.26 |
December | 497.00 | 20.95 | 202.83 | 20.73 | 202.83 | 20.61 |
Annual Sum or Average | 3925.50 | 22.00 | 1537.33 | 22.10 | 724.67 | 21.87 |
Minimum of Months | 50.00 | 20.68 | 2.17 | 20.43 | 0.00 | 20.31 |
Maximum of Months | 512.00 | 23.62 | 299.17 | 24.20 | 250.33 | 24.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.03 | 408.33 | 19.92 | 408.33 | 19.88 |
February | 454.00 | 20.41 | 278.83 | 20.21 | 278.83 | 20.11 |
March | 514.00 | 21.26 | 147.50 | 21.01 | 147.50 | 20.85 |
April | 427.33 | 22.13 | 61.50 | 21.99 | 50.50 | 21.83 |
May | 298.17 | 22.68 | 53.33 | 22.90 | 1.17 | 22.89 |
June | 171.50 | 23.11 | 96.17 | 23.53 | 0.00 | 23.53 |
July | 116.17 | 23.30 | 243.67 | 23.94 | 0.00 | 23.94 |
August | 129.83 | 23.19 | 274.17 | 23.87 | 0.17 | 23.87 |
September | 273.33 | 22.73 | 83.33 | 23.06 | 0.00 | 23.06 |
October | 484.67 | 21.75 | 57.50 | 21.57 | 57.50 | 21.43 |
November | 489.00 | 20.68 | 236.33 | 20.44 | 236.33 | 20.32 |
December | 497.00 | 20.19 | 384.50 | 20.08 | 384.50 | 20.04 |
Annual Sum or Average | 4357.00 | 21.36 | 2325.17 | 21.35 | 1564.83 | 21.08 |
Minimum of Months | 116.17 | 20.03 | 53.33 | 19.92 | 0.00 | 19.88 |
Maximum of Months | 514.00 | 23.30 | 408.33 | 23.94 | 408.33 | 23.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.07 | 380.83 | 19.93 | 380.83 | 19.88 |
February | 454.00 | 20.67 | 245.83 | 20.41 | 245.83 | 20.29 |
March | 503.33 | 21.67 | 109.33 | 21.36 | 109.33 | 21.15 |
April | 311.83 | 22.21 | 88.67 | 22.29 | 36.00 | 22.12 |
May | 221.50 | 22.68 | 137.83 | 23.33 | 5.17 | 23.34 |
June | 117.17 | 23.26 | 221.83 | 24.03 | 4.83 | 24.07 |
July | 97.17 | 23.94 | 325.00 | 24.30 | 16.00 | 24.40 |
August | 94.67 | 23.82 | 353.83 | 24.21 | 14.83 | 24.30 |
September | 210.17 | 22.78 | 168.83 | 23.48 | 3.83 | 23.51 |
October | 410.50 | 21.82 | 55.83 | 21.70 | 45.17 | 21.55 |
November | 489.00 | 20.81 | 206.00 | 20.54 | 206.00 | 20.39 |
December | 497.00 | 20.24 | 349.67 | 20.09 | 349.67 | 20.03 |
Annual Sum or Average | 3908.33 | 21.39 | 2643.50 | 21.65 | 1417.50 | 21.37 |
Minimum of Months | 94.67 | 20.07 | 55.83 | 19.93 | 3.83 | 19.88 |
Maximum of Months | 503.33 | 23.94 | 380.83 | 24.30 | 380.83 | 24.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.83 | 20.43 | 324.17 | 20.17 | 323.67 | 20.06 |
February | 407.00 | 20.94 | 204.00 | 20.72 | 192.17 | 20.55 |
March | 418.17 | 21.54 | 135.67 | 21.40 | 106.50 | 21.19 |
April | 307.67 | 22.14 | 122.83 | 22.40 | 42.33 | 22.23 |
May | 248.67 | 22.69 | 142.17 | 23.32 | 10.00 | 23.37 |
June | 168.00 | 23.13 | 181.33 | 23.81 | 5.83 | 23.86 |
July | 124.00 | 23.58 | 291.17 | 24.17 | 12.83 | 24.26 |
August | 127.50 | 23.57 | 327.50 | 24.12 | 13.00 | 24.20 |
September | 205.33 | 22.90 | 206.33 | 23.65 | 7.50 | 23.71 |
October | 356.00 | 21.91 | 126.50 | 22.25 | 39.50 | 22.11 |
November | 453.67 | 21.01 | 196.33 | 20.86 | 173.83 | 20.67 |
December | 473.33 | 20.57 | 295.50 | 20.32 | 293.50 | 20.20 |
Annual Sum or Average | 3786.17 | 21.58 | 2553.50 | 21.89 | 1220.67 | 21.62 |
Minimum of Months | 124.00 | 20.43 | 122.83 | 20.17 | 5.83 | 20.06 |
Maximum of Months | 496.83 | 23.58 | 327.50 | 24.17 | 323.67 | 24.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.10 | 383.83 | 19.96 | 383.83 | 19.90 |
February | 445.50 | 20.64 | 249.83 | 20.38 | 249.33 | 20.26 |
March | 478.33 | 21.40 | 143.17 | 21.17 | 134.67 | 20.98 |
April | 354.00 | 22.07 | 102.17 | 22.19 | 47.50 | 22.02 |
May | 259.17 | 22.78 | 131.50 | 23.33 | 14.50 | 23.43 |
June | 162.00 | 23.18 | 188.00 | 23.82 | 6.83 | 23.88 |
July | 118.17 | 23.72 | 308.67 | 24.23 | 15.83 | 24.33 |
August | 125.33 | 23.52 | 322.33 | 24.10 | 11.17 | 24.17 |
September | 228.83 | 22.92 | 171.50 | 23.56 | 10.33 | 23.64 |
October | 430.50 | 21.77 | 78.17 | 21.75 | 50.67 | 21.59 |
November | 483.17 | 20.78 | 215.50 | 20.54 | 212.67 | 20.40 |
December | 497.00 | 20.30 | 353.33 | 20.14 | 353.33 | 20.07 |
Annual Sum or Average | 4084.00 | 21.42 | 2648.00 | 21.64 | 1490.67 | 21.38 |
Minimum of Months | 118.17 | 20.10 | 78.17 | 19.96 | 6.83 | 19.90 |
Maximum of Months | 502.00 | 23.72 | 383.83 | 24.23 | 383.83 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.36 | 370.33 | 20.25 | 370.33 | 20.21 |
February | 454.00 | 20.70 | 238.33 | 20.54 | 238.33 | 20.46 |
March | 514.00 | 21.39 | 81.00 | 21.26 | 81.00 | 21.16 |
April | 465.00 | 22.27 | 10.33 | 22.25 | 8.00 | 22.22 |
May | 373.00 | 23.08 | 19.33 | 23.13 | 0.00 | 23.13 |
June | 190.67 | 23.43 | 47.17 | 23.60 | 0.00 | 23.60 |
July | 83.67 | 23.58 | 195.00 | 24.02 | 0.00 | 24.02 |
August | 91.17 | 23.48 | 258.00 | 23.99 | 0.00 | 23.99 |
September | 259.50 | 23.20 | 70.67 | 23.41 | 0.00 | 23.41 |
October | 484.00 | 22.43 | 1.00 | 22.42 | 1.00 | 22.42 |
November | 489.00 | 21.32 | 107.83 | 21.15 | 107.83 | 21.04 |
December | 497.00 | 20.63 | 298.83 | 20.52 | 298.83 | 20.47 |
Annual Sum or Average | 4403.00 | 21.74 | 1697.83 | 21.71 | 1105.33 | 21.48 |
Minimum of Months | 83.67 | 20.36 | 1.00 | 20.25 | 0.00 | 20.21 |
Maximum of Months | 514.00 | 23.58 | 370.33 | 24.02 | 370.33 | 24.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.40 | 341.33 | 20.27 | 341.33 | 20.22 |
February | 454.00 | 20.99 | 198.17 | 20.79 | 198.17 | 20.68 |
March | 514.00 | 21.98 | 44.67 | 21.84 | 44.67 | 21.73 |
April | 336.50 | 22.70 | 38.17 | 22.81 | 4.17 | 22.78 |
May | 225.67 | 23.09 | 102.33 | 23.55 | 0.33 | 23.55 |
June | 82.83 | 23.46 | 215.17 | 24.22 | 0.83 | 24.22 |
July | 44.00 | 24.32 | 336.00 | 24.43 | 9.33 | 24.49 |
August | 44.17 | 24.32 | 375.00 | 24.35 | 10.33 | 24.41 |
September | 161.67 | 23.32 | 196.83 | 23.91 | 3.17 | 23.93 |
October | 385.33 | 22.60 | 19.83 | 22.70 | 0.00 | 22.70 |
November | 487.67 | 21.51 | 87.83 | 21.32 | 87.83 | 21.19 |
December | 497.00 | 20.74 | 250.33 | 20.58 | 250.33 | 20.50 |
Annual Sum or Average | 3734.83 | 21.76 | 2205.67 | 22.09 | 950.50 | 21.86 |
Minimum of Months | 44.00 | 20.40 | 19.83 | 20.27 | 0.00 | 20.22 |
Maximum of Months | 514.00 | 24.32 | 375.00 | 24.43 | 341.33 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.33 | 20.40 | 325.00 | 20.21 | 325.00 | 20.12 |
February | 432.83 | 21.07 | 141.67 | 20.81 | 140.83 | 20.65 |
March | 462.00 | 21.57 | 56.50 | 21.45 | 50.67 | 21.31 |
April | 364.00 | 22.11 | 65.33 | 22.34 | 14.17 | 22.25 |
May | 317.33 | 22.53 | 83.50 | 22.97 | 1.00 | 22.96 |
June | 214.83 | 22.79 | 116.17 | 23.44 | 0.00 | 23.44 |
July | 99.50 | 23.04 | 289.50 | 24.09 | 4.67 | 24.13 |
August | 91.00 | 23.14 | 333.17 | 24.10 | 8.83 | 24.16 |
September | 165.00 | 22.77 | 227.50 | 23.77 | 6.33 | 23.82 |
October | 342.33 | 22.28 | 90.00 | 22.80 | 2.50 | 22.81 |
November | 457.50 | 21.24 | 102.83 | 21.20 | 83.50 | 21.05 |
December | 481.17 | 20.74 | 244.83 | 20.54 | 242.00 | 20.42 |
Annual Sum or Average | 3926.83 | 21.61 | 2076.00 | 21.97 | 879.50 | 21.73 |
Minimum of Months | 91.00 | 20.40 | 56.50 | 20.21 | 0.00 | 20.12 |
Maximum of Months | 499.33 | 23.14 | 333.17 | 24.10 | 325.00 | 24.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.43 | 346.33 | 20.29 | 346.33 | 20.24 |
February | 452.67 | 20.97 | 196.33 | 20.76 | 196.33 | 20.64 |
March | 496.00 | 21.78 | 57.50 | 21.64 | 56.50 | 21.53 |
April | 370.00 | 22.50 | 46.67 | 22.69 | 4.00 | 22.67 |
May | 236.50 | 23.23 | 112.33 | 23.66 | 2.67 | 23.69 |
June | 109.33 | 23.46 | 172.83 | 24.05 | 1.00 | 24.07 |
July | 38.17 | 24.47 | 356.33 | 24.48 | 9.00 | 24.54 |
August | 39.67 | 24.08 | 378.00 | 24.31 | 7.50 | 24.36 |
September | 130.67 | 23.41 | 213.67 | 24.05 | 4.00 | 24.08 |
October | 404.50 | 22.58 | 25.83 | 22.71 | 0.00 | 22.71 |
November | 482.00 | 21.45 | 94.50 | 21.30 | 91.50 | 21.17 |
December | 497.00 | 20.75 | 259.50 | 20.59 | 259.50 | 20.51 |
Annual Sum or Average | 3758.50 | 21.73 | 2259.83 | 22.08 | 978.33 | 21.84 |
Minimum of Months | 38.17 | 20.43 | 25.83 | 20.29 | 0.00 | 20.24 |
Maximum of Months | 502.00 | 24.47 | 378.00 | 24.48 | 346.33 | 24.54 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.31 | 336.17 | 20.16 | 336.17 | 20.09 |
February | 454.00 | 20.78 | 204.00 | 20.55 | 204.00 | 20.43 |
March | 514.00 | 21.80 | 59.17 | 21.64 | 59.17 | 21.52 |
April | 412.50 | 22.61 | 23.50 | 22.65 | 5.67 | 22.62 |
May | 260.83 | 23.14 | 54.00 | 23.31 | 0.00 | 23.31 |
June | 117.17 | 23.44 | 98.00 | 23.82 | 0.00 | 23.82 |
July | 55.17 | 23.58 | 261.67 | 24.13 | 0.00 | 24.13 |
August | 62.33 | 23.44 | 307.17 | 24.07 | 0.00 | 24.07 |
September | 218.67 | 23.19 | 106.17 | 23.52 | 0.00 | 23.52 |
October | 463.83 | 22.35 | 8.33 | 22.31 | 7.83 | 22.28 |
November | 489.00 | 21.20 | 133.67 | 20.98 | 133.67 | 20.84 |
December | 497.00 | 20.55 | 291.00 | 20.41 | 291.00 | 20.34 |
Annual Sum or Average | 4046.50 | 21.68 | 1882.83 | 21.76 | 1037.50 | 21.51 |
Minimum of Months | 55.17 | 20.31 | 8.33 | 20.16 | 0.00 | 20.09 |
Maximum of Months | 514.00 | 23.58 | 336.17 | 24.13 | 336.17 | 24.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.24 | 286.17 | 20.06 | 286.17 | 19.98 |
February | 384.83 | 20.99 | 167.33 | 20.72 | 167.33 | 20.58 |
March | 418.17 | 22.04 | 43.83 | 21.86 | 43.83 | 21.71 |
April | 269.83 | 22.68 | 54.67 | 22.91 | 5.33 | 22.87 |
May | 184.83 | 23.16 | 109.50 | 23.70 | 3.83 | 23.74 |
June | 83.17 | 23.68 | 186.67 | 24.29 | 7.17 | 24.36 |
July | 42.50 | 24.55 | 275.83 | 24.54 | 11.83 | 24.63 |
August | 53.50 | 24.42 | 305.67 | 24.42 | 14.33 | 24.51 |
September | 160.67 | 23.29 | 158.50 | 23.88 | 4.33 | 23.92 |
October | 340.00 | 22.35 | 28.83 | 22.45 | 6.50 | 22.41 |
November | 414.50 | 21.26 | 111.50 | 21.01 | 111.50 | 20.85 |
December | 422.00 | 20.56 | 237.50 | 20.36 | 237.50 | 20.27 |
Annual Sum or Average | 3201.00 | 21.71 | 1966.00 | 22.02 | 899.67 | 21.77 |
Minimum of Months | 42.50 | 20.24 | 28.83 | 20.06 | 3.83 | 19.98 |
Maximum of Months | 427.00 | 24.55 | 305.67 | 24.54 | 286.17 | 24.63 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 490.33 | 20.76 | 253.83 | 20.49 | 251.67 | 20.35 |
February | 398.67 | 21.35 | 146.00 | 21.20 | 127.33 | 21.02 |
March | 399.17 | 22.06 | 73.17 | 22.07 | 39.50 | 21.93 |
April | 278.00 | 22.61 | 94.67 | 23.05 | 4.50 | 23.03 |
May | 213.17 | 23.18 | 148.17 | 23.71 | 6.67 | 23.76 |
June | 123.00 | 23.45 | 197.17 | 24.05 | 3.50 | 24.08 |
July | 74.50 | 24.06 | 315.17 | 24.36 | 11.67 | 24.44 |
August | 58.33 | 24.16 | 352.67 | 24.31 | 13.00 | 24.40 |
September | 151.50 | 23.40 | 237.67 | 24.02 | 7.50 | 24.07 |
October | 327.67 | 22.53 | 102.83 | 23.01 | 4.33 | 23.03 |
November | 442.50 | 21.54 | 122.00 | 21.49 | 94.33 | 21.30 |
December | 461.83 | 20.97 | 212.17 | 20.75 | 207.17 | 20.60 |
Annual Sum or Average | 3418.67 | 21.93 | 2255.50 | 22.37 | 771.17 | 22.15 |
Minimum of Months | 58.33 | 20.76 | 73.17 | 20.49 | 3.50 | 20.35 |
Maximum of Months | 490.33 | 24.16 | 352.67 | 24.36 | 251.67 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.40 | 312.17 | 20.21 | 312.17 | 20.12 |
February | 442.17 | 21.00 | 177.00 | 20.74 | 176.50 | 20.60 |
March | 472.00 | 21.94 | 61.67 | 21.81 | 53.00 | 21.68 |
April | 331.33 | 22.57 | 68.67 | 22.84 | 7.50 | 22.80 |
May | 220.50 | 23.28 | 135.83 | 23.75 | 11.50 | 23.85 |
June | 112.00 | 23.52 | 196.33 | 24.07 | 5.00 | 24.12 |
July | 64.00 | 24.30 | 335.17 | 24.42 | 13.83 | 24.50 |
August | 55.67 | 24.03 | 356.33 | 24.29 | 10.67 | 24.35 |
September | 170.33 | 23.42 | 201.50 | 23.96 | 10.00 | 24.04 |
October | 405.50 | 22.39 | 42.17 | 22.52 | 8.50 | 22.48 |
November | 476.33 | 21.28 | 124.67 | 21.08 | 120.00 | 20.93 |
December | 497.00 | 20.69 | 257.67 | 20.49 | 257.67 | 20.39 |
Annual Sum or Average | 3748.83 | 21.74 | 2269.17 | 22.07 | 986.33 | 21.84 |
Minimum of Months | 55.67 | 20.40 | 42.17 | 20.21 | 5.00 | 20.12 |
Maximum of Months | 502.00 | 24.30 | 356.33 | 24.42 | 312.17 | 24.50 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.88281 | 31.23912 | -0.0837 | 6.92809 |
February | 454.00000 | 23.55169 | 31.27187 | 0.10541 | 5.72561 |
March | 514.00000 | 24.04478 | 30.21919 | 0.25214 | 6.45990 |
April | 485.00000 | 24.27314 | 33.05117 | 0.35050 | 7.78279 |
May | 508.00000 | 24.33959 | 36.37656 | -0.4529 | 9.62934 |
June | 496.00000 | 24.36985 | 38.14298 | -0.4070 | 8.86552 |
July | 497.00000 | 24.46684 | 42.25774 | -0.3392 | 7.92624 |
August | 514.00000 | 24.38656 | 45.38198 | -0.3332 | 7.75656 |
September | 485.00000 | 24.42013 | 43.13550 | -0.3646 | 8.29338 |
October | 502.00000 | 24.30115 | 36.16592 | 0.38023 | 8.24503 |
November | 489.00000 | 23.91167 | 35.93687 | 0.24205 | 6.62884 |
December | 497.00000 | 23.44747 | 31.37600 | 0.07514 | 5.48446 |
Annual Sum or Average | 5943.00000 | 24.03617 | 36.24627 | -0.0499 | 7.49052 |
Minimum of Months | 454.00000 | 22.88281 | 30.21919 | -0.4529 | 5.48446 |
Maximum of Months | 514.00000 | 24.46684 | 45.38198 | 0.38023 | 9.62934 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.31102 | 34.07511 | -0.4316 | 10.46365 |
February | 454.00000 | 22.02335 | 34.61698 | -0.2384 | 7.40071 |
March | 514.00000 | 23.08284 | 33.24628 | 0.02553 | 5.60412 |
April | 485.00000 | 23.66511 | 35.18851 | 0.20043 | 6.33320 |
May | 508.00000 | 24.00134 | 38.03566 | -0.5870 | 12.60690 |
June | 496.00000 | 24.14632 | 39.47430 | -0.5039 | 10.54786 |
July | 497.00000 | 24.26543 | 43.34581 | -0.4282 | 9.11924 |
August | 514.00000 | 24.22238 | 46.53663 | -0.4135 | 8.84306 |
September | 485.00000 | 24.13252 | 44.76702 | -0.4871 | 10.31259 |
October | 502.00000 | 23.55558 | 39.12431 | 0.19534 | 6.33104 |
November | 489.00000 | 22.50500 | 39.89850 | -0.0830 | 6.28241 |
December | 497.00000 | 21.74826 | 34.96161 | -0.3089 | 7.70799 |
Annual Sum or Average | 5943.00000 | 23.23092 | 38.63025 | -0.2558 | 8.47404 |
Minimum of Months | 454.00000 | 21.31102 | 33.24628 | -0.5870 | 5.60412 |
Maximum of Months | 514.00000 | 24.26543 | 46.53663 | 0.20043 | 12.60690 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.68330 | 34.85745 | -0.6039 | 14.78026 |
February | 454.00000 | 21.25772 | 35.54030 | -0.4373 | 11.04511 |
March | 514.00000 | 22.30955 | 34.56363 | -0.1641 | 6.71875 |
April | 485.00000 | 23.16336 | 36.17609 | 0.07740 | 6.19838 |
May | 508.00000 | 23.73091 | 38.69091 | -0.6837 | 15.80773 |
June | 496.00000 | 24.00789 | 39.68739 | -0.5546 | 11.85851 |
July | 497.00000 | 24.14879 | 43.47003 | -0.4675 | 9.93590 |
August | 514.00000 | 24.10713 | 46.60018 | -0.4571 | 9.76304 |
September | 485.00000 | 23.83735 | 45.63975 | -0.5979 | 13.22214 |
October | 502.00000 | 22.84970 | 40.97425 | 0.01998 | 6.12008 |
November | 489.00000 | 21.62439 | 41.85055 | -0.3061 | 8.49155 |
December | 497.00000 | 20.95253 | 36.16278 | -0.5217 | 11.86589 |
Annual Sum or Average | 5943.00000 | 22.73447 | 39.53963 | -0.3916 | 10.48243 |
Minimum of Months | 454.00000 | 20.68330 | 34.56363 | -0.6837 | 6.12008 |
Maximum of Months | 514.00000 | 24.14879 | 46.60018 | 0.07740 | 15.80773 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.02514 | 36.30849 | -0.8017 | 21.18118 |
February | 454.00000 | 20.41485 | 37.07624 | -0.6635 | 16.96165 |
March | 514.00000 | 21.25591 | 37.20068 | -0.4121 | 10.21395 |
April | 485.00000 | 22.35913 | 38.21227 | -0.1046 | 7.40015 |
May | 508.00000 | 23.25039 | 40.40118 | -0.8282 | 21.99464 |
June | 496.00000 | 23.76302 | 40.94259 | -0.6197 | 14.32609 |
July | 497.00000 | 23.97074 | 44.18583 | -0.5055 | 11.35973 |
August | 514.00000 | 23.90093 | 47.91205 | -0.5105 | 11.55681 |
September | 485.00000 | 23.31293 | 48.08912 | -0.7710 | 19.53622 |
October | 502.00000 | 21.83042 | 44.19419 | -0.2157 | 7.68958 |
November | 489.00000 | 20.67668 | 43.85928 | -0.5495 | 13.35181 |
December | 497.00000 | 20.18526 | 38.05551 | -0.7426 | 18.41200 |
Annual Sum or Average | 5943.00000 | 22.09246 | 41.39349 | -0.5600 | 14.47966 |
Minimum of Months | 454.00000 | 20.02514 | 36.30849 | -0.8282 | 7.40015 |
Maximum of Months | 514.00000 | 23.97074 | 48.08912 | -0.1046 | 21.99464 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.06618 | 37.13456 | -0.7808 | 20.47298 |
February | 454.00000 | 20.67392 | 37.52057 | -0.5885 | 15.02020 |
March | 514.00000 | 21.71614 | 37.16455 | -0.2892 | 9.28694 |
April | 485.00000 | 22.88869 | 36.89810 | 0.04932 | 7.58474 |
May | 508.00000 | 23.53240 | 39.57447 | -0.6870 | 18.41644 |
June | 496.00000 | 24.00390 | 39.95047 | -0.4682 | 11.79088 |
July | 497.00000 | 24.17365 | 43.50250 | -0.3687 | 9.84302 |
August | 514.00000 | 24.09913 | 47.04247 | -0.3650 | 9.67492 |
September | 485.00000 | 23.57411 | 47.21175 | -0.6308 | 16.50404 |
October | 502.00000 | 22.22789 | 43.55906 | -0.1071 | 7.63624 |
November | 489.00000 | 20.80991 | 44.45025 | -0.5090 | 12.73650 |
December | 497.00000 | 20.24442 | 38.85066 | -0.7162 | 17.68891 |
Annual Sum or Average | 5943.00000 | 22.34786 | 41.09089 | -0.4544 | 13.03631 |
Minimum of Months | 454.00000 | 20.06618 | 36.89810 | -0.7808 | 7.58474 |
Maximum of Months | 514.00000 | 24.17365 | 47.21175 | 0.04932 | 20.47298 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.46887 | 35.51409 | -0.6702 | 18.02240 |
February | 454.00000 | 21.27198 | 35.12557 | -0.4305 | 13.11840 |
March | 514.00000 | 22.00970 | 34.92259 | -0.2021 | 9.42146 |
April | 485.00000 | 22.90113 | 36.00161 | 0.05964 | 8.28994 |
May | 508.00000 | 23.44903 | 39.20263 | -0.7133 | 19.87220 |
June | 496.00000 | 23.84203 | 40.23655 | -0.5516 | 13.89262 |
July | 497.00000 | 24.08017 | 43.51821 | -0.4101 | 10.92177 |
August | 514.00000 | 24.02630 | 46.94752 | -0.3901 | 10.55577 |
September | 485.00000 | 23.65636 | 46.08917 | -0.5629 | 15.66091 |
October | 502.00000 | 22.60614 | 41.29047 | 0.00579 | 8.42794 |
November | 489.00000 | 21.26074 | 42.37679 | -0.3936 | 11.75682 |
December | 497.00000 | 20.74469 | 36.79620 | -0.5828 | 15.73288 |
Annual Sum or Average | 5943.00000 | 22.53680 | 39.86353 | -0.4037 | 12.97334 |
Minimum of Months | 454.00000 | 20.46887 | 34.92259 | -0.7133 | 8.28994 |
Maximum of Months | 514.00000 | 24.08017 | 46.94752 | 0.05964 | 19.87220 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.10206 | 37.07923 | -0.7736 | 20.39733 |
February | 454.00000 | 20.70078 | 37.34102 | -0.5852 | 15.52154 |
March | 514.00000 | 21.58681 | 37.08993 | -0.3209 | 9.91351 |
April | 485.00000 | 22.64613 | 37.66663 | -0.0104 | 8.12122 |
May | 508.00000 | 23.43762 | 40.04944 | -0.7120 | 20.17550 |
June | 496.00000 | 23.84181 | 40.84884 | -0.5381 | 13.58746 |
July | 497.00000 | 24.11149 | 43.74014 | -0.3737 | 10.58776 |
August | 514.00000 | 24.01494 | 47.55787 | -0.3996 | 10.71000 |
September | 485.00000 | 23.57514 | 47.33630 | -0.6259 | 16.90223 |
October | 502.00000 | 22.12036 | 43.82672 | -0.1328 | 7.85172 |
November | 489.00000 | 20.82404 | 44.43741 | -0.5079 | 12.82854 |
December | 497.00000 | 20.30139 | 38.75608 | -0.7055 | 17.64554 |
Annual Sum or Average | 5943.00000 | 22.28478 | 41.33260 | -0.4733 | 13.67294 |
Minimum of Months | 454.00000 | 20.10206 | 37.07923 | -0.7736 | 7.85172 |
Maximum of Months | 514.00000 | 24.11149 | 47.55787 | -0.0104 | 20.39733 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.35815 | 36.16983 | -0.7015 | 16.86774 |
February | 454.00000 | 20.69963 | 37.00097 | -0.5788 | 13.35711 |
March | 514.00000 | 21.38743 | 37.22369 | -0.3743 | 8.62263 |
April | 485.00000 | 22.34125 | 38.91496 | -0.1146 | 6.42021 |
May | 508.00000 | 23.32990 | 40.89392 | -0.8284 | 20.71893 |
June | 496.00000 | 23.82945 | 41.38702 | -0.6261 | 13.76705 |
July | 497.00000 | 24.04049 | 44.44468 | -0.5097 | 10.79055 |
August | 514.00000 | 23.98860 | 48.07343 | -0.5017 | 10.69364 |
September | 485.00000 | 23.59427 | 47.56828 | -0.6852 | 15.72624 |
October | 502.00000 | 22.48609 | 42.69491 | -0.0546 | 5.92369 |
November | 489.00000 | 21.32450 | 42.69888 | -0.3627 | 8.91176 |
December | 497.00000 | 20.62859 | 37.44219 | -0.6002 | 13.12590 |
Annual Sum or Average | 5943.00000 | 22.34674 | 41.23426 | -0.4949 | 12.07690 |
Minimum of Months | 454.00000 | 20.35815 | 36.16983 | -0.8284 | 5.92369 |
Maximum of Months | 514.00000 | 24.04049 | 48.07343 | -0.0546 | 20.71893 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.40162 | 37.10442 | -0.6810 | 16.24968 |
February | 454.00000 | 20.99315 | 37.50307 | -0.4955 | 11.51545 |
March | 514.00000 | 21.97766 | 37.15559 | -0.2223 | 7.28534 |
April | 485.00000 | 23.13147 | 37.20747 | 0.09682 | 6.65945 |
May | 508.00000 | 23.71707 | 39.65100 | -0.6525 | 15.87734 |
June | 496.00000 | 24.14507 | 39.89387 | -0.4465 | 10.40849 |
July | 497.00000 | 24.28582 | 43.48624 | -0.3563 | 8.78070 |
August | 514.00000 | 24.22415 | 46.87133 | -0.3365 | 8.46700 |
September | 485.00000 | 23.90872 | 46.38742 | -0.5248 | 12.34730 |
October | 502.00000 | 22.95447 | 41.83487 | 0.07096 | 6.33699 |
November | 489.00000 | 21.51155 | 43.28715 | -0.3116 | 8.45421 |
December | 497.00000 | 20.73735 | 38.27184 | -0.5651 | 12.42227 |
Annual Sum or Average | 5943.00000 | 22.67840 | 40.74012 | -0.3684 | 10.39572 |
Minimum of Months | 454.00000 | 20.40162 | 37.10442 | -0.6810 | 6.33699 |
Maximum of Months | 514.00000 | 24.28582 | 46.87133 | 0.09682 | 16.24968 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.42507 | 33.63418 | -0.6445 | 15.68250 |
February | 454.00000 | 21.21640 | 33.69651 | -0.4022 | 10.68973 |
March | 514.00000 | 21.83987 | 33.75880 | -0.2121 | 7.80388 |
April | 485.00000 | 22.66871 | 35.81899 | 0.01683 | 7.17766 |
May | 508.00000 | 23.19726 | 39.47384 | -0.7943 | 21.22750 |
June | 496.00000 | 23.62384 | 40.69494 | -0.6303 | 15.51156 |
July | 497.00000 | 24.04856 | 43.76876 | -0.4356 | 10.78541 |
August | 514.00000 | 24.01474 | 47.17130 | -0.3943 | 10.03683 |
September | 485.00000 | 23.76455 | 45.41537 | -0.5095 | 13.49917 |
October | 502.00000 | 22.97216 | 39.18324 | 0.12182 | 7.53479 |
November | 489.00000 | 21.47156 | 39.84282 | -0.2906 | 8.95268 |
December | 497.00000 | 20.86383 | 34.56216 | -0.5040 | 12.30345 |
Annual Sum or Average | 5943.00000 | 22.51889 | 38.95344 | -0.3905 | 11.78478 |
Minimum of Months | 454.00000 | 20.42507 | 33.63418 | -0.7943 | 7.17766 |
Maximum of Months | 514.00000 | 24.04856 | 47.17130 | 0.12182 | 21.22750 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.42526 | 37.03418 | -0.6759 | 16.17934 |
February | 454.00000 | 20.98229 | 37.40054 | -0.4984 | 11.95574 |
March | 514.00000 | 21.85883 | 37.10575 | -0.2510 | 7.70077 |
April | 485.00000 | 22.91364 | 37.81801 | 0.04144 | 6.80692 |
May | 508.00000 | 23.75946 | 39.63391 | -0.6351 | 15.55183 |
June | 496.00000 | 24.04145 | 40.60766 | -0.4988 | 11.31248 |
July | 497.00000 | 24.33997 | 43.21970 | -0.3219 | 8.37268 |
August | 514.00000 | 24.21753 | 47.05469 | -0.3468 | 8.60587 |
September | 485.00000 | 24.01528 | 46.05398 | -0.4875 | 11.54946 |
October | 502.00000 | 22.90357 | 42.00607 | 0.05825 | 6.38201 |
November | 489.00000 | 21.49420 | 43.28253 | -0.3163 | 8.57563 |
December | 497.00000 | 20.75098 | 38.20933 | -0.5622 | 12.48690 |
Annual Sum or Average | 5943.00000 | 22.65456 | 40.80519 | -0.3742 | 10.45098 |
Minimum of Months | 454.00000 | 20.42526 | 37.03418 | -0.6759 | 6.38201 |
Maximum of Months | 514.00000 | 24.33997 | 47.05469 | 0.05825 | 16.17934 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.31030 | 35.94100 | -0.6977 | 17.16533 |
February | 454.00000 | 20.78179 | 36.51392 | -0.5420 | 13.15056 |
March | 514.00000 | 21.79518 | 36.27055 | -0.2653 | 7.60940 |
April | 485.00000 | 22.82787 | 37.32663 | 0.01329 | 6.40239 |
May | 508.00000 | 23.58703 | 39.57491 | -0.7136 | 17.02119 |
June | 496.00000 | 23.94489 | 40.49201 | -0.5570 | 12.03162 |
July | 497.00000 | 24.11406 | 43.90372 | -0.4581 | 9.80710 |
August | 514.00000 | 24.05104 | 47.58652 | -0.4581 | 9.88709 |
September | 485.00000 | 23.68281 | 46.98463 | -0.6413 | 14.63846 |
October | 502.00000 | 22.47867 | 42.60221 | -0.0510 | 6.25343 |
November | 489.00000 | 21.20068 | 42.78650 | -0.3935 | 9.75185 |
December | 497.00000 | 20.55122 | 37.32175 | -0.6148 | 13.87106 |
Annual Sum or Average | 5943.00000 | 22.45706 | 40.63255 | -0.4480 | 11.45478 |
Minimum of Months | 454.00000 | 20.31030 | 35.94100 | -0.7136 | 6.25343 |
Maximum of Months | 514.00000 | 24.11406 | 47.58652 | 0.01329 | 17.16533 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.23686 | 36.54385 | -0.7075 | 17.62972 |
February | 385.00000 | 20.99266 | 36.56719 | -0.4859 | 12.16060 |
March | 433.00000 | 22.10610 | 35.97484 | -0.1817 | 7.43423 |
April | 410.00000 | 23.20559 | 35.84083 | 0.12412 | 7.05138 |
May | 430.00000 | 23.77944 | 38.53826 | -0.6153 | 15.36489 |
June | 418.00000 | 24.16131 | 39.44582 | -0.4299 | 10.56980 |
July | 422.00000 | 24.34545 | 42.89616 | -0.3322 | 8.94032 |
August | 433.00000 | 24.24724 | 46.46229 | -0.3327 | 8.85230 |
September | 410.00000 | 23.87222 | 45.97864 | -0.5376 | 13.13871 |
October | 427.00000 | 22.71772 | 41.90413 | 0.01699 | 6.65591 |
November | 417.00000 | 21.27536 | 43.11762 | -0.3713 | 9.74994 |
December | 422.00000 | 20.55769 | 37.92626 | -0.6064 | 13.91528 |
Annual Sum or Average | 5034.00000 | 22.63453 | 40.11995 | -0.3713 | 10.94908 |
Minimum of Months | 385.00000 | 20.23686 | 35.84083 | -0.7075 | 6.65591 |
Maximum of Months | 433.00000 | 24.34545 | 46.46229 | 0.12412 | 17.62972 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.84842 | 35.00399 | -0.5488 | 14.37029 |
February | 454.00000 | 21.71126 | 34.39197 | -0.2974 | 10.33549 |
March | 514.00000 | 22.52035 | 33.92928 | -0.0634 | 7.52731 |
April | 485.00000 | 23.30947 | 35.16275 | 0.16419 | 7.65465 |
May | 508.00000 | 23.76450 | 38.42897 | -0.6059 | 15.23880 |
June | 496.00000 | 24.02925 | 39.79530 | -0.4887 | 11.45966 |
July | 497.00000 | 24.23385 | 43.20363 | -0.3618 | 9.22396 |
August | 514.00000 | 24.17231 | 46.63555 | -0.3410 | 8.93694 |
September | 485.00000 | 23.96582 | 45.17425 | -0.4525 | 11.71168 |
October | 502.00000 | 23.15593 | 39.85768 | 0.14929 | 7.79931 |
November | 489.00000 | 21.83007 | 41.20018 | -0.2304 | 9.04091 |
December | 497.00000 | 21.20999 | 35.86145 | -0.4381 | 11.80745 |
Annual Sum or Average | 5943.00000 | 22.90544 | 39.08311 | -0.2934 | 10.42835 |
Minimum of Months | 454.00000 | 20.84842 | 33.92928 | -0.6059 | 7.52731 |
Maximum of Months | 514.00000 | 24.23385 | 46.63555 | 0.16419 | 15.23880 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.39944 | 36.73813 | -0.6674 | 16.48984 |
February | 454.00000 | 21.08035 | 36.72911 | -0.4623 | 12.06861 |
March | 514.00000 | 22.11620 | 36.08610 | -0.1774 | 7.56749 |
April | 485.00000 | 23.10183 | 36.75132 | 0.10396 | 7.27440 |
May | 508.00000 | 23.76688 | 39.19176 | -0.6004 | 15.34616 |
June | 496.00000 | 24.02934 | 40.34858 | -0.4748 | 11.17422 |
July | 497.00000 | 24.26169 | 43.40204 | -0.3259 | 8.94219 |
August | 514.00000 | 24.16568 | 47.19740 | -0.3484 | 9.04948 |
September | 485.00000 | 23.91282 | 46.25824 | -0.5068 | 12.56269 |
October | 502.00000 | 22.73934 | 42.24848 | 0.02525 | 6.70810 |
November | 489.00000 | 21.35354 | 43.33630 | -0.3516 | 9.48874 |
December | 497.00000 | 20.68935 | 38.01393 | -0.5743 | 13.28910 |
Annual Sum or Average | 5943.00000 | 22.64712 | 40.54705 | -0.3631 | 10.82178 |
Minimum of Months | 454.00000 | 20.39944 | 36.08610 | -0.6674 | 6.70810 |
Maximum of Months | 514.00000 | 24.26169 | 47.19740 | 0.10396 | 16.48984 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.193674E+09 | 52950809.77 | 8.08 | 0.172559E+09 | 21114389.45 | 0.00 | 0.46 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 11614.32 | 27-FEB-15:00 | 11559.80 | 27-FEB-15:00 | 1344.55 | 27-FEB-17:13 | 3078.76 | 27-FEB-15:00 | 0.00 |
March | 0.153008E+10 | 0.429557E+09 | 106.28 | 0.139975E+10 | 0.130334E+09 | 0.00 | 0.46 | 17-MAR-16:00 | 0.00 | 01-MAR-00:10 | 11536.07 | 17-MAR-16:00 | 11536.07 | 17-MAR-16:00 | 1448.42 | 09-MAR-12:00 | 3060.18 | 17-MAR-16:00 | 0.00 |
April | 0.493690E+10 | 0.126877E+10 | 121.80 | 0.474250E+10 | 0.194399E+09 | 0.00 | 1.00 | 26-APR-13:20 | 0.00 | 01-APR-00:10 | 50618.50 | 27-APR-15:10 | 50618.50 | 27-APR-15:10 | 4377.59 | 28-APR-13:00 | 12556.75 | 27-APR-15:10 | 0.00 |
May | 0.767325E+10 | 0.191906E+10 | 170.35 | 0.681281E+10 | 0.860444E+09 | 0.00 | 1.00 | 04-MAY-12:40 | 0.00 | 01-MAY-00:10 | 45413.45 | 15-MAY-16:00 | 45413.45 | 15-MAY-16:00 | 6782.42 | 07-MAY-17:31 | 10390.77 | 15-MAY-16:00 | 0.00 |
June | 0.141281E+11 | 0.351051E+10 | 264.03 | 0.130974E+11 | 0.103065E+10 | 0.00 | 1.00 | 09-JUN-13:40 | 0.00 | 01-JUN-00:10 | 52148.69 | 28-JUN-15:30 | 52148.69 | 28-JUN-15:30 | 9896.78 | 12-JUN-06:02 | 12574.37 | 28-JUN-15:30 | 0.00 |
July | 0.271642E+11 | 0.664305E+10 | 349.56 | 0.239022E+11 | 0.326199E+10 | 0.00 | 1.00 | 06-JUL-14:40 | 0.00 | 01-JUL-00:10 | 69495.80 | 31-JUL-16:00 | 64845.51 | 24-JUL-15:10 | 16675.39 | 31-JUL-06:03 | 18369.13 | 24-JUL-15:10 | 0.00 |
August | 0.371711E+11 | 0.913853E+10 | 375.43 | 0.324226E+11 | 0.474852E+10 | 0.00 | 1.00 | 07-AUG-08:50 | 0.00 | 01-AUG-00:10 | 71271.88 | 10-AUG-16:10 | 66545.58 | 10-AUG-15:50 | 18161.32 | 30-AUG-13:00 | 19600.67 | 10-AUG-16:10 | 0.00 |
September | 0.137898E+11 | 0.336318E+10 | 230.54 | 0.114464E+11 | 0.234341E+10 | 0.00 | 1.00 | 08-SEP-13:50 | 0.00 | 01-SEP-00:10 | 57738.34 | 14-SEP-13:00 | 53638.02 | 12-SEP-15:10 | 15910.37 | 14-SEP-13:00 | 13256.09 | 14-SEP-13:00 | 0.00 |
October | 0.257288E+10 | 0.669969E+09 | 81.74 | 0.239580E+10 | 0.177081E+09 | 0.00 | 1.00 | 04-OCT-13:40 | 0.00 | 01-OCT-00:10 | 33802.09 | 04-OCT-15:10 | 33802.09 | 04-OCT-15:10 | 2814.74 | 08-OCT-13:53 | 7717.43 | 04-OCT-15:10 | 0.00 |
November | 0.439940E+09 | 0.118043E+09 | 22.51 | 0.311440E+09 | 0.128500E+09 | 0.00 | 0.63 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 | 16679.79 | 04-NOV-14:40 | 11896.25 | 04-NOV-14:40 | 5234.43 | 04-NOV-13:00 | 4227.84 | 04-NOV-14:40 | 0.00 |
December | 601630.40 | 177140.01 | 0.33 | 528814.65 | 72815.75 | 0.00 | 0.03 | 05-DEC-11:50 | 0.00 | 01-DEC-00:10 | 715.11 | 05-DEC-11:50 | 630.71 | 05-DEC-11:50 | 84.40 | 05-DEC-11:50 | 210.29 | 05-DEC-11:50 | 0.00 |
Annual Sum or Average | 0.109601E+12 | 0.271138E+11 | 1730.65 | 0.967040E+11 | 0.128965E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.371711E+11 | 0.913853E+10 | 375.43 | 0.324226E+11 | 0.474852E+10 | 0.00 | 1.00 | 0.00 | 71271.88 | 66545.58 | 18161.32 | 19600.67 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.178341E+09 | 48603099.38 | 8.00 | 0.161886E+09 | 16455375.34 | 0.00 | 0.53 | 27-FEB-15:05 | 0.00 | 01-FEB-00:10 | 12145.82 | 27-FEB-15:05 | 12145.82 | 27-FEB-15:05 | 1233.42 | 27-FEB-17:13 | 3163.30 | 27-FEB-15:05 | 0.00 |
March | 0.273502E+09 | 76101747.40 | 23.00 | 0.242711E+09 | 30791153.15 | 0.00 | 0.47 | 18-MAR-14:05 | 0.00 | 01-MAR-00:10 | 10696.28 | 18-MAR-14:05 | 10696.28 | 18-MAR-14:05 | 1211.51 | 09-MAR-12:00 | 2826.49 | 18-MAR-14:05 | 0.00 |
April | 0.333479E+10 | 0.837134E+09 | 72.44 | 0.320240E+10 | 0.132390E+09 | 0.00 | 1.00 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 49597.00 | 27-APR-14:05 | 49597.00 | 27-APR-14:05 | 4144.49 | 28-APR-13:00 | 12092.06 | 27-APR-15:00 | 0.00 |
May | 0.691614E+10 | 0.171797E+10 | 162.64 | 0.618898E+10 | 0.727157E+09 | 0.00 | 1.00 | 03-MAY-15:50 | 0.00 | 01-MAY-00:10 | 43340.29 | 04-MAY-15:00 | 43340.29 | 04-MAY-15:00 | 8062.25 | 07-MAY-15:32 | 10029.86 | 04-MAY-15:00 | 0.00 |
June | 0.127803E+11 | 0.317474E+10 | 270.43 | 0.118899E+11 | 0.890414E+09 | 0.00 | 1.00 | 09-JUN-13:00 | 0.00 | 01-JUN-00:10 | 48467.74 | 28-JUN-15:30 | 48467.74 | 28-JUN-15:30 | 7749.70 | 12-JUN-06:02 | 11685.49 | 28-JUN-15:30 | 0.00 |
July | 0.242717E+11 | 0.593608E+10 | 354.40 | 0.215178E+11 | 0.275385E+10 | 0.00 | 1.00 | 06-JUL-14:05 | 0.00 | 01-JUL-00:10 | 67115.69 | 31-JUL-14:05 | 60129.69 | 31-JUL-14:05 | 16201.14 | 31-JUL-06:03 | 17046.83 | 31-JUL-14:05 | 0.00 |
August | 0.321153E+11 | 0.791589E+10 | 375.44 | 0.281535E+11 | 0.396184E+10 | 0.00 | 1.00 | 04-AUG-14:05 | 0.00 | 01-AUG-00:10 | 66759.09 | 10-AUG-14:05 | 60749.03 | 10-AUG-15:10 | 15828.36 | 30-AUG-13:00 | 17925.54 | 29-AUG-15:20 | 0.00 |
September | 0.119794E+11 | 0.292518E+10 | 232.15 | 0.997478E+10 | 0.200464E+10 | 0.00 | 1.00 | 08-SEP-13:20 | 0.00 | 01-SEP-00:10 | 53592.62 | 13-SEP-14:05 | 49044.96 | 12-SEP-14:05 | 14918.78 | 14-SEP-13:00 | 12283.20 | 13-SEP-14:05 | 0.00 |
October | 0.151094E+10 | 0.390276E+09 | 57.94 | 0.141564E+10 | 95295421.72 | 0.00 | 1.00 | 04-OCT-13:40 | 0.00 | 01-OCT-00:10 | 30882.53 | 04-OCT-15:00 | 30882.53 | 04-OCT-15:00 | 2509.52 | 08-OCT-14:00 | 7050.58 | 04-OCT-15:00 | 0.00 |
November | 0.335049E+09 | 85489037.16 | 7.67 | 0.234432E+09 | 0.100617E+09 | 0.00 | 0.75 | 04-NOV-14:05 | 0.00 | 01-NOV-00:10 | 18369.85 | 04-NOV-14:05 | 14369.22 | 04-NOV-14:05 | 4815.28 | 04-NOV-16:00 | 4505.63 | 04-NOV-14:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.936954E+11 | 0.231075E+11 | 1564.11 | 0.829820E+11 | 0.107135E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.321153E+11 | 0.791589E+10 | 375.44 | 0.281535E+11 | 0.396184E+10 | 0.00 | 1.00 | 0.00 | 67115.69 | 60749.03 | 16201.14 | 17925.54 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.184762E+09 | 50655829.57 | 8.00 | 0.162487E+09 | 22275583.15 | 0.00 | 0.46 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 11710.93 | 27-FEB-15:00 | 11710.93 | 27-FEB-15:00 | 1433.84 | 27-FEB-17:05 | 3100.68 | 27-FEB-15:00 | 0.00 |
March | 0.400694E+09 | 0.111567E+09 | 27.50 | 0.363287E+09 | 37406582.84 | 0.00 | 0.42 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 10571.95 | 18-MAR-16:00 | 10571.95 | 18-MAR-16:00 | 1333.26 | 09-MAR-12:00 | 2828.30 | 18-MAR-16:00 | 0.00 |
April | 0.354056E+10 | 0.891352E+09 | 71.19 | 0.337338E+10 | 0.167180E+09 | 0.00 | 1.00 | 26-APR-13:20 | 0.00 | 01-APR-00:10 | 56529.69 | 27-APR-14:40 | 56529.69 | 27-APR-14:40 | 3945.11 | 28-APR-13:00 | 13960.43 | 27-APR-15:00 | 0.00 |
May | 0.728269E+10 | 0.181355E+10 | 161.68 | 0.645256E+10 | 0.830129E+09 | 0.00 | 1.00 | 04-MAY-12:40 | 0.00 | 01-MAY-00:10 | 47159.61 | 04-MAY-15:00 | 47159.61 | 04-MAY-15:00 | 6453.29 | 07-MAY-17:02 | 10914.42 | 04-MAY-15:00 | 0.00 |
June | 0.134641E+11 | 0.335678E+10 | 268.89 | 0.124257E+11 | 0.103838E+10 | 0.00 | 1.00 | 09-JUN-13:20 | 0.00 | 01-JUN-00:10 | 56465.68 | 28-JUN-15:20 | 56465.68 | 28-JUN-15:20 | 5241.26 | 12-JUN-12:40 | 13611.98 | 28-JUN-15:20 | 0.00 |
July | 0.258648E+11 | 0.634884E+10 | 353.27 | 0.227320E+11 | 0.313274E+10 | 0.00 | 1.00 | 06-JUL-14:50 | 0.00 | 01-JUL-00:10 | 73868.51 | 31-JUL-14:40 | 67616.39 | 24-JUL-14:00 | 12773.07 | 31-JUL-10:30 | 19179.65 | 24-JUL-15:00 | 0.00 |
August | 0.338996E+11 | 0.840430E+10 | 375.49 | 0.295973E+11 | 0.430222E+10 | 0.00 | 1.00 | 06-AUG-16:12 | 0.00 | 01-AUG-00:10 | 74333.67 | 10-AUG-14:50 | 69875.30 | 10-AUG-15:20 | 15895.24 | 30-AUG-13:00 | 19941.96 | 10-AUG-15:20 | 0.00 |
September | 0.120651E+11 | 0.296386E+10 | 229.39 | 0.992343E+10 | 0.214171E+10 | 0.00 | 1.00 | 08-SEP-14:00 | 0.00 | 01-SEP-00:10 | 53303.04 | 14-SEP-13:30 | 49554.62 | 12-SEP-15:20 | 14449.60 | 14-SEP-13:00 | 12227.32 | 14-SEP-13:30 | 0.00 |
October | 0.138471E+10 | 0.362468E+09 | 54.89 | 0.128050E+10 | 0.104214E+09 | 0.00 | 1.00 | 04-OCT-14:40 | 0.00 | 01-OCT-00:10 | 30261.14 | 04-OCT-15:00 | 30261.14 | 04-OCT-15:00 | 2840.98 | 08-OCT-13:53 | 6910.27 | 04-OCT-15:00 | 0.00 |
November | 0.342930E+09 | 88414663.88 | 7.67 | 0.232514E+09 | 0.110416E+09 | 0.00 | 0.69 | 04-NOV-14:20 | 0.00 | 01-NOV-00:10 | 18525.71 | 04-NOV-14:20 | 13801.42 | 04-NOV-14:20 | 5366.56 | 04-NOV-13:00 | 4619.77 | 04-NOV-14:20 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.984299E+11 | 0.243918E+11 | 1557.97 | 0.865432E+11 | 0.118867E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.338996E+11 | 0.840430E+10 | 375.49 | 0.295973E+11 | 0.430222E+10 | 0.00 | 1.00 | 0.00 | 74333.67 | 69875.30 | 15895.24 | 19941.96 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 240.22 | 0.00 | 240.22 | 12.56 | 1367.10 | 0.00 | 0.00 | 0.00 |
February | 373.79 | 0.00 | 373.79 | 88.43 | 1211.48 | 0.00 | 0.00 | 0.00 |
March | 550.72 | 0.00 | 550.72 | 252.79 | 1008.76 | 0.00 | 0.00 | 0.00 |
April | 779.33 | 2.76 | 776.56 | 525.80 | 822.90 | 0.00 | 0.00 | 0.00 |
May | 1002.80 | 29.79 | 973.01 | 829.33 | 679.37 | 0.00 | 0.00 | 0.00 |
June | 1054.42 | 69.63 | 984.79 | 955.58 | 529.64 | 0.00 | 0.00 | 0.00 |
July | 1002.17 | 78.57 | 923.59 | 1025.20 | 478.37 | 0.00 | 0.00 | 0.00 |
August | 811.26 | 21.93 | 789.33 | 845.74 | 468.00 | 0.00 | 0.00 | 0.00 |
September | 630.16 | 0.19 | 629.97 | 492.79 | 691.38 | 0.00 | 0.00 | 0.00 |
October | 431.76 | 0.00 | 431.76 | 212.49 | 895.12 | 0.00 | 0.00 | 0.00 |
November | 271.97 | 0.00 | 271.97 | 47.83 | 1097.62 | 0.00 | 0.00 | 0.00 |
December | 204.13 | 0.00 | 204.13 | 7.33 | 1371.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 613.91 | 17.03 | 596.88 | 443.52 | 883.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 204.13 | 0.00 | 204.13 | 7.33 | 468.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1054.42 | 78.57 | 984.79 | 1025.20 | 1371.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 257.34 | 65.24 | 192.09 | 98.65 | 865.03 | 0.00 | 0.00 | 0.00 |
February | 472.19 | 167.59 | 304.60 | 322.41 | 764.47 | 0.00 | 0.00 | 0.00 |
March | 705.01 | 255.22 | 449.79 | 599.40 | 647.56 | 0.00 | 0.00 | 0.00 |
April | 1092.89 | 454.11 | 638.78 | 1116.66 | 533.34 | 0.00 | 0.00 | 0.00 |
May | 1162.93 | 404.32 | 758.61 | 1242.21 | 459.20 | 0.00 | 0.00 | 0.00 |
June | 1392.74 | 605.99 | 786.75 | 1594.55 | 363.27 | 0.00 | 0.00 | 0.00 |
July | 1296.96 | 582.15 | 714.81 | 1551.32 | 321.98 | 0.00 | 0.00 | 0.00 |
August | 1274.74 | 637.70 | 637.04 | 1577.58 | 314.23 | 0.00 | 0.00 | 0.00 |
September | 942.48 | 434.68 | 507.80 | 1040.40 | 447.76 | 0.00 | 0.00 | 0.00 |
October | 614.31 | 261.02 | 353.28 | 569.56 | 579.72 | 0.00 | 0.00 | 0.00 |
November | 301.10 | 85.00 | 216.10 | 169.43 | 706.53 | 0.00 | 0.00 | 0.00 |
December | 246.97 | 79.51 | 167.46 | 122.93 | 877.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 814.80 | 336.78 | 478.02 | 836.36 | 572.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.97 | 65.24 | 167.46 | 98.65 | 314.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1392.74 | 637.70 | 786.75 | 1594.55 | 877.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1061.37 | 630.25 | 431.13 | 961.42 | 1241.78 | 0.00 | 0.00 | 0.00 |
February | 1632.23 | 1010.37 | 621.86 | 1681.79 | 1132.35 | 0.00 | 0.00 | 0.00 |
March | 1755.81 | 936.35 | 819.45 | 1881.66 | 1005.07 | 0.00 | 0.00 | 0.00 |
April | 1853.80 | 804.91 | 1048.89 | 2096.43 | 869.16 | 0.00 | 0.00 | 0.00 |
May | 1695.06 | 504.98 | 1190.09 | 1930.30 | 737.62 | 0.00 | 0.00 | 0.00 |
June | 1550.82 | 416.37 | 1134.44 | 1799.37 | 588.29 | 0.00 | 0.00 | 0.00 |
July | 1691.23 | 619.42 | 1071.81 | 2166.64 | 534.60 | 0.00 | 0.00 | 0.00 |
August | 1817.02 | 847.31 | 969.71 | 2407.81 | 516.37 | 0.00 | 0.00 | 0.00 |
September | 2013.18 | 1111.74 | 901.44 | 2507.39 | 711.65 | 0.00 | 0.00 | 0.00 |
October | 1823.60 | 1125.94 | 697.66 | 2084.84 | 895.28 | 0.00 | 0.00 | 0.00 |
November | 1078.17 | 617.88 | 460.29 | 1047.11 | 1045.90 | 0.00 | 0.00 | 0.00 |
December | 1128.08 | 730.02 | 398.05 | 1121.55 | 1281.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1591.01 | 778.19 | 812.82 | 1807.62 | 878.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1061.37 | 416.37 | 398.05 | 961.42 | 516.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2013.18 | 1125.94 | 1190.09 | 2507.39 | 1281.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 271.43 | 80.04 | 191.39 | 122.54 | 872.22 | 0.00 | 0.00 | 0.00 |
February | 486.65 | 182.90 | 303.75 | 355.31 | 776.36 | 0.00 | 0.00 | 0.00 |
March | 681.92 | 230.17 | 451.75 | 584.68 | 662.49 | 0.00 | 0.00 | 0.00 |
April | 1037.47 | 396.66 | 640.80 | 1057.04 | 560.83 | 0.00 | 0.00 | 0.00 |
May | 1334.98 | 542.33 | 792.65 | 1478.61 | 481.69 | 0.00 | 0.00 | 0.00 |
June | 1283.89 | 498.49 | 785.40 | 1450.66 | 382.76 | 0.00 | 0.00 | 0.00 |
July | 1586.07 | 833.72 | 752.35 | 1964.47 | 352.75 | 0.00 | 0.00 | 0.00 |
August | 1312.06 | 669.97 | 642.08 | 1649.78 | 343.40 | 0.00 | 0.00 | 0.00 |
September | 1068.47 | 512.67 | 555.79 | 1238.14 | 474.09 | 0.00 | 0.00 | 0.00 |
October | 608.28 | 247.85 | 360.44 | 572.98 | 596.76 | 0.00 | 0.00 | 0.00 |
November | 302.92 | 85.44 | 217.48 | 177.29 | 710.87 | 0.00 | 0.00 | 0.00 |
December | 254.66 | 87.27 | 167.40 | 143.83 | 887.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 854.63 | 365.34 | 489.29 | 903.19 | 590.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 254.66 | 80.04 | 167.40 | 122.54 | 343.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1586.07 | 833.72 | 792.65 | 1964.47 | 887.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.07 | 0.00 | 80.07 | 3.65 | 479.44 | 0.00 | 0.00 | 0.00 |
February | 124.59 | 0.00 | 124.59 | 28.63 | 424.31 | 0.00 | 0.00 | 0.00 |
March | 183.57 | 0.00 | 183.57 | 85.92 | 347.55 | 0.00 | 0.00 | 0.00 |
April | 259.76 | 0.92 | 258.84 | 181.26 | 277.96 | 0.00 | 0.00 | 0.00 |
May | 334.25 | 9.93 | 324.32 | 283.24 | 229.68 | 0.00 | 0.00 | 0.00 |
June | 351.46 | 23.21 | 328.25 | 325.06 | 178.62 | 0.00 | 0.00 | 0.00 |
July | 334.04 | 26.19 | 307.85 | 347.39 | 161.64 | 0.00 | 0.00 | 0.00 |
August | 270.41 | 7.31 | 263.10 | 285.59 | 159.27 | 0.00 | 0.00 | 0.00 |
September | 210.04 | 0.06 | 209.98 | 164.77 | 241.01 | 0.00 | 0.00 | 0.00 |
October | 143.91 | 0.00 | 143.91 | 66.41 | 324.83 | 0.00 | 0.00 | 0.00 |
November | 90.65 | 0.00 | 90.65 | 13.14 | 403.18 | 0.00 | 0.00 | 0.00 |
December | 68.04 | 0.00 | 68.04 | 1.57 | 492.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.63 | 5.68 | 198.95 | 149.63 | 309.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.04 | 0.00 | 68.04 | 1.57 | 159.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.46 | 26.19 | 328.25 | 347.39 | 492.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.07 | 0.00 | 80.07 | 3.65 | 479.47 | 0.00 | 0.00 | 0.00 |
February | 124.60 | 0.00 | 124.60 | 28.63 | 424.33 | 0.00 | 0.00 | 0.00 |
March | 183.57 | 0.00 | 183.57 | 85.92 | 347.57 | 0.00 | 0.00 | 0.00 |
April | 259.77 | 0.92 | 258.85 | 181.27 | 277.98 | 0.00 | 0.00 | 0.00 |
May | 334.26 | 9.93 | 324.33 | 283.24 | 229.69 | 0.00 | 0.00 | 0.00 |
June | 351.47 | 23.21 | 328.26 | 325.07 | 178.64 | 0.00 | 0.00 | 0.00 |
July | 334.05 | 26.19 | 307.86 | 347.40 | 161.64 | 0.00 | 0.00 | 0.00 |
August | 270.42 | 7.31 | 263.11 | 285.60 | 159.27 | 0.00 | 0.00 | 0.00 |
September | 210.05 | 0.06 | 209.99 | 164.77 | 241.03 | 0.00 | 0.00 | 0.00 |
October | 143.92 | 0.00 | 143.92 | 66.41 | 324.85 | 0.00 | 0.00 | 0.00 |
November | 90.66 | 0.00 | 90.66 | 13.14 | 403.20 | 0.00 | 0.00 | 0.00 |
December | 68.04 | 0.00 | 68.04 | 1.57 | 492.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.64 | 5.68 | 198.96 | 149.64 | 309.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.04 | 0.00 | 68.04 | 1.57 | 159.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.47 | 26.19 | 328.26 | 347.40 | 492.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.07 | 0.00 | 80.07 | 3.65 | 479.47 | 0.00 | 0.00 | 0.00 |
February | 124.60 | 0.00 | 124.60 | 28.63 | 424.33 | 0.00 | 0.00 | 0.00 |
March | 183.57 | 0.00 | 183.57 | 85.92 | 347.57 | 0.00 | 0.00 | 0.00 |
April | 259.77 | 0.92 | 258.85 | 181.27 | 277.98 | 0.00 | 0.00 | 0.00 |
May | 334.26 | 9.93 | 324.33 | 283.24 | 229.69 | 0.00 | 0.00 | 0.00 |
June | 351.47 | 23.21 | 328.26 | 325.07 | 178.64 | 0.00 | 0.00 | 0.00 |
July | 334.05 | 26.19 | 307.86 | 347.40 | 161.64 | 0.00 | 0.00 | 0.00 |
August | 270.42 | 7.31 | 263.11 | 285.60 | 159.27 | 0.00 | 0.00 | 0.00 |
September | 210.05 | 0.06 | 209.99 | 164.77 | 241.03 | 0.00 | 0.00 | 0.00 |
October | 143.92 | 0.00 | 143.92 | 66.41 | 324.85 | 0.00 | 0.00 | 0.00 |
November | 90.66 | 0.00 | 90.66 | 13.14 | 403.20 | 0.00 | 0.00 | 0.00 |
December | 68.04 | 0.00 | 68.04 | 1.57 | 492.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.64 | 5.68 | 198.96 | 149.64 | 309.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.04 | 0.00 | 68.04 | 1.57 | 159.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.47 | 26.19 | 328.26 | 347.40 | 492.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 247.55 | 62.76 | 184.78 | 92.17 | 875.62 | 0.00 | 0.00 | 0.00 |
February | 454.22 | 161.21 | 293.01 | 307.08 | 776.90 | 0.00 | 0.00 | 0.00 |
March | 678.19 | 245.51 | 432.68 | 579.16 | 654.15 | 0.00 | 0.00 | 0.00 |
April | 1051.30 | 436.83 | 614.47 | 1081.02 | 535.51 | 0.00 | 0.00 | 0.00 |
May | 1118.68 | 388.94 | 729.74 | 1204.97 | 457.62 | 0.00 | 0.00 | 0.00 |
June | 1339.75 | 582.93 | 756.82 | 1545.06 | 364.15 | 0.00 | 0.00 | 0.00 |
July | 1247.62 | 560.00 | 687.62 | 1502.21 | 321.19 | 0.00 | 0.00 | 0.00 |
August | 1226.23 | 613.43 | 612.80 | 1524.48 | 317.74 | 0.00 | 0.00 | 0.00 |
September | 906.62 | 418.14 | 488.48 | 1000.86 | 459.20 | 0.00 | 0.00 | 0.00 |
October | 590.93 | 251.09 | 339.84 | 538.21 | 615.83 | 0.00 | 0.00 | 0.00 |
November | 289.64 | 81.77 | 207.87 | 154.04 | 751.01 | 0.00 | 0.00 | 0.00 |
December | 237.57 | 76.48 | 161.09 | 112.97 | 909.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 783.80 | 323.97 | 459.83 | 806.05 | 585.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 237.57 | 62.76 | 161.09 | 92.17 | 317.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1339.75 | 613.43 | 756.82 | 1545.06 | 909.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.79 | 2.48 | 7.31 | 3.64 | 34.62 | 0.00 | 0.00 | 0.00 |
February | 17.96 | 6.37 | 11.59 | 12.14 | 30.72 | 0.00 | 0.00 | 0.00 |
March | 26.81 | 9.71 | 17.11 | 22.90 | 25.86 | 0.00 | 0.00 | 0.00 |
April | 41.57 | 17.27 | 24.30 | 42.74 | 21.17 | 0.00 | 0.00 | 0.00 |
May | 44.23 | 15.38 | 28.85 | 47.64 | 18.09 | 0.00 | 0.00 | 0.00 |
June | 52.97 | 23.05 | 29.92 | 61.09 | 14.40 | 0.00 | 0.00 | 0.00 |
July | 49.33 | 22.14 | 27.19 | 59.40 | 12.70 | 0.00 | 0.00 | 0.00 |
August | 48.48 | 24.25 | 24.23 | 60.28 | 12.56 | 0.00 | 0.00 | 0.00 |
September | 35.85 | 16.53 | 19.31 | 39.57 | 18.16 | 0.00 | 0.00 | 0.00 |
October | 23.36 | 9.93 | 13.44 | 21.28 | 24.35 | 0.00 | 0.00 | 0.00 |
November | 11.45 | 3.23 | 8.22 | 6.09 | 29.69 | 0.00 | 0.00 | 0.00 |
December | 9.39 | 3.02 | 6.37 | 4.47 | 35.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30.99 | 12.81 | 18.18 | 31.87 | 23.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.39 | 2.48 | 6.37 | 3.64 | 12.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.97 | 24.25 | 29.92 | 61.09 | 35.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 353.78 | 210.08 | 143.71 | 322.10 | 436.22 | 0.00 | 0.00 | 0.00 |
February | 544.07 | 336.78 | 207.28 | 563.67 | 403.29 | 0.00 | 0.00 | 0.00 |
March | 585.26 | 312.11 | 273.15 | 634.80 | 354.41 | 0.00 | 0.00 | 0.00 |
April | 617.92 | 268.30 | 349.63 | 709.46 | 299.53 | 0.00 | 0.00 | 0.00 |
May | 565.01 | 168.32 | 396.69 | 655.50 | 251.08 | 0.00 | 0.00 | 0.00 |
June | 516.93 | 138.79 | 378.14 | 611.61 | 199.37 | 0.00 | 0.00 | 0.00 |
July | 563.74 | 206.47 | 357.27 | 730.89 | 183.93 | 0.00 | 0.00 | 0.00 |
August | 605.66 | 282.43 | 323.23 | 809.31 | 180.66 | 0.00 | 0.00 | 0.00 |
September | 671.05 | 370.57 | 300.48 | 839.24 | 254.55 | 0.00 | 0.00 | 0.00 |
October | 607.86 | 375.31 | 232.55 | 694.80 | 331.34 | 0.00 | 0.00 | 0.00 |
November | 359.38 | 205.96 | 153.43 | 347.22 | 383.31 | 0.00 | 0.00 | 0.00 |
December | 376.02 | 243.34 | 132.68 | 373.24 | 459.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 530.33 | 259.39 | 270.94 | 607.80 | 310.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 353.78 | 138.79 | 132.68 | 322.10 | 180.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 671.05 | 375.31 | 396.69 | 839.24 | 459.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 353.78 | 210.08 | 143.71 | 322.10 | 436.22 | 0.00 | 0.00 | 0.00 |
February | 544.07 | 336.78 | 207.28 | 563.67 | 403.29 | 0.00 | 0.00 | 0.00 |
March | 585.26 | 312.11 | 273.15 | 634.80 | 354.41 | 0.00 | 0.00 | 0.00 |
April | 617.92 | 268.30 | 349.63 | 709.46 | 299.53 | 0.00 | 0.00 | 0.00 |
May | 565.01 | 168.32 | 396.69 | 655.50 | 251.08 | 0.00 | 0.00 | 0.00 |
June | 516.93 | 138.79 | 378.14 | 611.61 | 199.37 | 0.00 | 0.00 | 0.00 |
July | 563.74 | 206.47 | 357.27 | 730.89 | 183.93 | 0.00 | 0.00 | 0.00 |
August | 605.66 | 282.43 | 323.23 | 809.31 | 180.66 | 0.00 | 0.00 | 0.00 |
September | 671.05 | 370.57 | 300.48 | 839.24 | 254.55 | 0.00 | 0.00 | 0.00 |
October | 607.86 | 375.31 | 232.55 | 694.80 | 331.34 | 0.00 | 0.00 | 0.00 |
November | 359.38 | 205.96 | 153.43 | 347.22 | 383.31 | 0.00 | 0.00 | 0.00 |
December | 376.02 | 243.34 | 132.68 | 373.24 | 459.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 530.33 | 259.39 | 270.94 | 607.80 | 310.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 353.78 | 138.79 | 132.68 | 322.10 | 180.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 671.05 | 375.31 | 396.69 | 839.24 | 459.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 353.76 | 210.07 | 143.70 | 322.08 | 436.20 | 0.00 | 0.00 | 0.00 |
February | 544.03 | 336.76 | 207.27 | 563.63 | 403.26 | 0.00 | 0.00 | 0.00 |
March | 585.22 | 312.09 | 273.13 | 634.76 | 354.39 | 0.00 | 0.00 | 0.00 |
April | 617.88 | 268.28 | 349.60 | 709.42 | 299.51 | 0.00 | 0.00 | 0.00 |
May | 564.98 | 168.31 | 396.67 | 655.45 | 251.06 | 0.00 | 0.00 | 0.00 |
June | 516.90 | 138.78 | 378.12 | 611.57 | 199.35 | 0.00 | 0.00 | 0.00 |
July | 563.70 | 206.46 | 357.25 | 730.84 | 183.91 | 0.00 | 0.00 | 0.00 |
August | 605.63 | 282.41 | 323.21 | 809.26 | 180.65 | 0.00 | 0.00 | 0.00 |
September | 671.01 | 370.55 | 300.46 | 839.18 | 254.53 | 0.00 | 0.00 | 0.00 |
October | 607.82 | 375.28 | 232.54 | 694.76 | 331.32 | 0.00 | 0.00 | 0.00 |
November | 359.36 | 205.94 | 153.42 | 347.19 | 383.28 | 0.00 | 0.00 | 0.00 |
December | 376.00 | 243.32 | 132.67 | 373.22 | 459.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 530.30 | 259.38 | 270.92 | 607.77 | 310.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 353.76 | 138.78 | 132.67 | 322.08 | 180.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 671.01 | 375.28 | 396.67 | 839.18 | 459.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 261.10 | 76.99 | 184.11 | 117.58 | 884.23 | 0.00 | 0.00 | 0.00 |
February | 468.13 | 175.94 | 292.20 | 342.87 | 790.53 | 0.00 | 0.00 | 0.00 |
March | 655.97 | 221.41 | 434.57 | 567.79 | 670.51 | 0.00 | 0.00 | 0.00 |
April | 998.00 | 381.57 | 616.42 | 1028.49 | 561.69 | 0.00 | 0.00 | 0.00 |
May | 1284.19 | 521.69 | 762.49 | 1435.15 | 486.14 | 0.00 | 0.00 | 0.00 |
June | 1235.04 | 479.52 | 755.51 | 1409.82 | 384.13 | 0.00 | 0.00 | 0.00 |
July | 1525.72 | 801.99 | 723.73 | 1902.14 | 359.57 | 0.00 | 0.00 | 0.00 |
August | 1262.13 | 644.48 | 617.65 | 1596.12 | 350.25 | 0.00 | 0.00 | 0.00 |
September | 1027.82 | 493.17 | 534.65 | 1192.27 | 490.63 | 0.00 | 0.00 | 0.00 |
October | 585.14 | 238.42 | 346.72 | 543.35 | 635.14 | 0.00 | 0.00 | 0.00 |
November | 291.40 | 82.19 | 209.21 | 163.56 | 756.10 | 0.00 | 0.00 | 0.00 |
December | 244.97 | 83.95 | 161.03 | 136.28 | 920.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 822.11 | 351.44 | 470.67 | 873.08 | 606.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 244.97 | 76.99 | 161.03 | 117.58 | 350.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1525.72 | 801.99 | 762.49 | 1902.14 | 920.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.32 | 3.04 | 7.28 | 4.65 | 34.96 | 0.00 | 0.00 | 0.00 |
February | 18.51 | 6.96 | 11.55 | 13.56 | 31.26 | 0.00 | 0.00 | 0.00 |
March | 25.94 | 8.75 | 17.18 | 22.45 | 26.51 | 0.00 | 0.00 | 0.00 |
April | 39.46 | 15.09 | 24.37 | 40.67 | 22.21 | 0.00 | 0.00 | 0.00 |
May | 50.78 | 20.63 | 30.15 | 56.74 | 19.22 | 0.00 | 0.00 | 0.00 |
June | 48.83 | 18.96 | 29.87 | 55.74 | 15.19 | 0.00 | 0.00 | 0.00 |
July | 60.33 | 31.71 | 28.62 | 75.21 | 14.22 | 0.00 | 0.00 | 0.00 |
August | 49.90 | 25.48 | 24.42 | 63.11 | 13.85 | 0.00 | 0.00 | 0.00 |
September | 40.64 | 19.50 | 21.14 | 47.14 | 19.40 | 0.00 | 0.00 | 0.00 |
October | 23.14 | 9.43 | 13.71 | 21.48 | 25.11 | 0.00 | 0.00 | 0.00 |
November | 11.52 | 3.25 | 8.27 | 6.47 | 29.90 | 0.00 | 0.00 | 0.00 |
December | 9.69 | 3.32 | 6.37 | 5.39 | 36.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.51 | 13.90 | 18.61 | 34.52 | 23.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.69 | 3.04 | 6.37 | 4.65 | 13.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.33 | 31.71 | 30.15 | 75.21 | 36.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 240.22 | 0.00 | 240.22 | 9.82 | 1447.94 | 0.00 | 0.00 | 0.00 |
February | 373.79 | 0.00 | 373.79 | 78.51 | 1295.61 | 0.00 | 0.00 | 0.00 |
March | 550.72 | 0.00 | 550.72 | 234.93 | 1086.24 | 0.00 | 0.00 | 0.00 |
April | 779.33 | 2.76 | 776.56 | 508.54 | 877.21 | 0.00 | 0.00 | 0.00 |
May | 1002.80 | 29.79 | 973.01 | 816.24 | 715.97 | 0.00 | 0.00 | 0.00 |
June | 1054.42 | 69.63 | 984.79 | 948.69 | 552.90 | 0.00 | 0.00 | 0.00 |
July | 1002.17 | 78.57 | 923.59 | 1021.84 | 497.98 | 0.00 | 0.00 | 0.00 |
August | 811.26 | 21.93 | 789.33 | 840.97 | 489.24 | 0.00 | 0.00 | 0.00 |
September | 630.16 | 0.19 | 629.97 | 481.29 | 735.38 | 0.00 | 0.00 | 0.00 |
October | 431.76 | 0.00 | 431.76 | 193.47 | 975.03 | 0.00 | 0.00 | 0.00 |
November | 271.97 | 0.00 | 271.97 | 38.65 | 1194.50 | 0.00 | 0.00 | 0.00 |
December | 204.13 | 0.00 | 204.13 | 4.55 | 1470.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 613.91 | 17.03 | 596.88 | 433.67 | 943.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 204.13 | 0.00 | 204.13 | 4.55 | 489.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1054.42 | 78.57 | 984.79 | 1021.84 | 1470.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 257.34 | 65.24 | 192.09 | 93.20 | 915.50 | 0.00 | 0.00 | 0.00 |
February | 472.19 | 167.59 | 304.60 | 309.06 | 817.85 | 0.00 | 0.00 | 0.00 |
March | 705.01 | 255.22 | 449.79 | 582.28 | 696.85 | 0.00 | 0.00 | 0.00 |
April | 1092.89 | 454.11 | 638.78 | 1102.08 | 565.66 | 0.00 | 0.00 | 0.00 |
May | 1162.93 | 404.32 | 758.61 | 1232.39 | 482.29 | 0.00 | 0.00 | 0.00 |
June | 1392.74 | 605.99 | 786.75 | 1589.46 | 378.26 | 0.00 | 0.00 | 0.00 |
July | 1296.96 | 582.15 | 714.81 | 1546.86 | 334.03 | 0.00 | 0.00 | 0.00 |
August | 1274.74 | 637.70 | 637.04 | 1572.93 | 327.13 | 0.00 | 0.00 | 0.00 |
September | 942.48 | 434.68 | 507.80 | 1030.39 | 474.14 | 0.00 | 0.00 | 0.00 |
October | 614.31 | 261.02 | 353.28 | 553.21 | 629.09 | 0.00 | 0.00 | 0.00 |
November | 301.10 | 85.00 | 216.10 | 157.91 | 769.13 | 0.00 | 0.00 | 0.00 |
December | 246.97 | 79.51 | 167.46 | 115.78 | 940.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 814.80 | 336.78 | 478.02 | 826.42 | 609.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.97 | 65.24 | 167.46 | 93.20 | 327.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1392.74 | 637.70 | 786.75 | 1589.46 | 940.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1061.37 | 630.25 | 431.13 | 946.46 | 1316.83 | 0.00 | 0.00 | 0.00 |
February | 1632.23 | 1010.37 | 621.86 | 1661.25 | 1209.02 | 0.00 | 0.00 | 0.00 |
March | 1755.81 | 936.35 | 819.45 | 1864.97 | 1078.78 | 0.00 | 0.00 | 0.00 |
April | 1853.80 | 804.91 | 1048.89 | 2083.78 | 921.43 | 0.00 | 0.00 | 0.00 |
May | 1695.06 | 504.98 | 1190.09 | 1923.17 | 776.34 | 0.00 | 0.00 | 0.00 |
June | 1550.82 | 416.37 | 1134.44 | 1797.80 | 614.91 | 0.00 | 0.00 | 0.00 |
July | 1691.23 | 619.42 | 1071.81 | 2167.32 | 556.41 | 0.00 | 0.00 | 0.00 |
August | 1817.02 | 847.31 | 969.71 | 2407.97 | 539.02 | 0.00 | 0.00 | 0.00 |
September | 2013.18 | 1111.74 | 901.44 | 2499.16 | 751.81 | 0.00 | 0.00 | 0.00 |
October | 1823.60 | 1125.94 | 697.66 | 2066.94 | 967.04 | 0.00 | 0.00 | 0.00 |
November | 1078.17 | 617.88 | 460.29 | 1026.76 | 1133.50 | 0.00 | 0.00 | 0.00 |
December | 1128.08 | 730.02 | 398.05 | 1105.79 | 1372.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1591.01 | 778.19 | 812.82 | 1796.44 | 935.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1061.37 | 416.37 | 398.05 | 946.46 | 539.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2013.18 | 1125.94 | 1190.09 | 2499.16 | 1372.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 271.43 | 80.04 | 191.39 | 118.36 | 923.89 | 0.00 | 0.00 | 0.00 |
February | 486.65 | 182.90 | 303.75 | 346.16 | 829.59 | 0.00 | 0.00 | 0.00 |
March | 681.92 | 230.17 | 451.75 | 572.91 | 712.62 | 0.00 | 0.00 | 0.00 |
April | 1037.47 | 396.66 | 640.80 | 1046.98 | 596.26 | 0.00 | 0.00 | 0.00 |
May | 1334.98 | 542.33 | 792.65 | 1473.39 | 507.37 | 0.00 | 0.00 | 0.00 |
June | 1283.89 | 498.49 | 785.40 | 1449.74 | 400.30 | 0.00 | 0.00 | 0.00 |
July | 1586.07 | 833.72 | 752.35 | 1965.68 | 367.35 | 0.00 | 0.00 | 0.00 |
August | 1312.06 | 669.97 | 642.08 | 1649.65 | 358.58 | 0.00 | 0.00 | 0.00 |
September | 1068.47 | 512.67 | 555.79 | 1232.27 | 501.89 | 0.00 | 0.00 | 0.00 |
October | 608.28 | 247.85 | 360.44 | 560.68 | 648.11 | 0.00 | 0.00 | 0.00 |
November | 302.92 | 85.44 | 217.48 | 168.40 | 772.40 | 0.00 | 0.00 | 0.00 |
December | 254.66 | 87.27 | 167.40 | 139.42 | 950.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 854.63 | 365.34 | 489.29 | 897.25 | 629.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 254.66 | 80.04 | 167.40 | 118.36 | 358.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1586.07 | 833.72 | 792.65 | 1965.68 | 950.61 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.643410E+09 | 0.00 | 0.643410E+09 | 33651418.16 | 0.366164E+10 |
February | 0.904276E+09 | 0.00 | 0.904276E+09 | 0.213942E+09 | 0.293082E+10 |
March | 0.147506E+10 | 0.00 | 0.147506E+10 | 0.677078E+09 | 0.270186E+10 |
April | 0.202002E+10 | 7165624.79 | 0.201285E+10 | 0.136287E+10 | 0.213296E+10 |
May | 0.268590E+10 | 79794157.67 | 0.260611E+10 | 0.222128E+10 | 0.181962E+10 |
June | 0.273305E+10 | 0.180480E+09 | 0.255258E+10 | 0.247686E+10 | 0.137284E+10 |
July | 0.268421E+10 | 0.210454E+09 | 0.247375E+10 | 0.274590E+10 | 0.128125E+10 |
August | 0.217288E+10 | 58739581.33 | 0.211414E+10 | 0.226522E+10 | 0.125349E+10 |
September | 0.163337E+10 | 481656.94 | 0.163289E+10 | 0.127731E+10 | 0.179207E+10 |
October | 0.115644E+10 | 0.00 | 0.115644E+10 | 0.569142E+09 | 0.239750E+10 |
November | 0.704943E+09 | 0.00 | 0.704943E+09 | 0.123964E+09 | 0.284504E+10 |
December | 0.546732E+09 | 0.00 | 0.546732E+09 | 19636271.57 | 0.367376E+10 |
Annual Sum or Average | 0.193603E+11 | 0.537115E+09 | 0.188232E+11 | 0.139869E+11 | 0.278628E+11 |
Minimum of Months | 0.546732E+09 | 0.00 | 0.546732E+09 | 19636271.57 | 0.125349E+10 |
Maximum of Months | 0.273305E+10 | 0.210454E+09 | 0.260611E+10 | 0.274590E+10 | 0.367376E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.689252E+09 | 0.174748E+09 | 0.514504E+09 | 0.264212E+09 | 0.231690E+10 |
February | 0.114232E+10 | 0.405433E+09 | 0.736886E+09 | 0.779975E+09 | 0.184940E+10 |
March | 0.188830E+10 | 0.683582E+09 | 0.120472E+10 | 0.160544E+10 | 0.173443E+10 |
April | 0.283277E+10 | 0.117706E+10 | 0.165571E+10 | 0.289437E+10 | 0.138241E+10 |
May | 0.311479E+10 | 0.108294E+10 | 0.203185E+10 | 0.332714E+10 | 0.122991E+10 |
June | 0.360998E+10 | 0.157073E+10 | 0.203925E+10 | 0.413308E+10 | 0.941601E+09 |
July | 0.347379E+10 | 0.155924E+10 | 0.191455E+10 | 0.415507E+10 | 0.862387E+09 |
August | 0.341425E+10 | 0.170800E+10 | 0.170625E+10 | 0.422539E+10 | 0.841634E+09 |
September | 0.244291E+10 | 0.112669E+10 | 0.131622E+10 | 0.269672E+10 | 0.116059E+10 |
October | 0.164536E+10 | 0.699123E+09 | 0.946237E+09 | 0.152550E+10 | 0.155271E+10 |
November | 0.780449E+09 | 0.220329E+09 | 0.560121E+09 | 0.439158E+09 | 0.183133E+10 |
December | 0.661482E+09 | 0.212951E+09 | 0.448531E+09 | 0.329266E+09 | 0.235059E+10 |
Annual Sum or Average | 0.256957E+11 | 0.106208E+11 | 0.150748E+11 | 0.263753E+11 | 0.180539E+11 |
Minimum of Months | 0.661482E+09 | 0.174748E+09 | 0.448531E+09 | 0.264212E+09 | 0.841634E+09 |
Maximum of Months | 0.360998E+10 | 0.170800E+10 | 0.203925E+10 | 0.422539E+10 | 0.235059E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.284278E+10 | 0.168806E+10 | 0.115473E+10 | 0.257507E+10 | 0.332597E+10 |
February | 0.394869E+10 | 0.244429E+10 | 0.150440E+10 | 0.406859E+10 | 0.273937E+10 |
March | 0.470276E+10 | 0.250793E+10 | 0.219483E+10 | 0.503985E+10 | 0.269199E+10 |
April | 0.480505E+10 | 0.208633E+10 | 0.271872E+10 | 0.543395E+10 | 0.225287E+10 |
May | 0.454006E+10 | 0.135253E+10 | 0.318753E+10 | 0.517012E+10 | 0.197565E+10 |
June | 0.401972E+10 | 0.107924E+10 | 0.294047E+10 | 0.466396E+10 | 0.152484E+10 |
July | 0.452980E+10 | 0.165905E+10 | 0.287075E+10 | 0.580314E+10 | 0.143188E+10 |
August | 0.486670E+10 | 0.226942E+10 | 0.259728E+10 | 0.644908E+10 | 0.138305E+10 |
September | 0.521816E+10 | 0.288164E+10 | 0.233652E+10 | 0.649917E+10 | 0.184459E+10 |
October | 0.488433E+10 | 0.301571E+10 | 0.186862E+10 | 0.558403E+10 | 0.239791E+10 |
November | 0.279463E+10 | 0.160156E+10 | 0.119307E+10 | 0.271410E+10 | 0.271097E+10 |
December | 0.302144E+10 | 0.195530E+10 | 0.106615E+10 | 0.300395E+10 | 0.343122E+10 |
Annual Sum or Average | 0.501741E+11 | 0.245411E+11 | 0.256331E+11 | 0.570050E+11 | 0.277103E+11 |
Minimum of Months | 0.279463E+10 | 0.107924E+10 | 0.106615E+10 | 0.257507E+10 | 0.138305E+10 |
Maximum of Months | 0.521816E+10 | 0.301571E+10 | 0.318753E+10 | 0.649917E+10 | 0.343122E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.726993E+09 | 0.214377E+09 | 0.512616E+09 | 0.328215E+09 | 0.233616E+10 |
February | 0.117730E+10 | 0.442463E+09 | 0.734839E+09 | 0.859561E+09 | 0.187816E+10 |
March | 0.182646E+10 | 0.616478E+09 | 0.120998E+10 | 0.156601E+10 | 0.177441E+10 |
April | 0.268912E+10 | 0.102815E+10 | 0.166096E+10 | 0.273984E+10 | 0.145366E+10 |
May | 0.357561E+10 | 0.145258E+10 | 0.212303E+10 | 0.396031E+10 | 0.129017E+10 |
June | 0.332783E+10 | 0.129209E+10 | 0.203574E+10 | 0.376012E+10 | 0.992113E+09 |
July | 0.424812E+10 | 0.223303E+10 | 0.201509E+10 | 0.526164E+10 | 0.944795E+09 |
August | 0.351421E+10 | 0.179446E+10 | 0.171975E+10 | 0.441877E+10 | 0.919759E+09 |
September | 0.276947E+10 | 0.132885E+10 | 0.144062E+10 | 0.320926E+10 | 0.122883E+10 |
October | 0.162922E+10 | 0.663831E+09 | 0.965393E+09 | 0.153468E+10 | 0.159837E+10 |
November | 0.785171E+09 | 0.221451E+09 | 0.563720E+09 | 0.459524E+09 | 0.184259E+10 |
December | 0.682091E+09 | 0.233735E+09 | 0.448356E+09 | 0.385225E+09 | 0.237603E+10 |
Annual Sum or Average | 0.269516E+11 | 0.115215E+11 | 0.154301E+11 | 0.284831E+11 | 0.186350E+11 |
Minimum of Months | 0.682091E+09 | 0.214377E+09 | 0.448356E+09 | 0.328215E+09 | 0.919759E+09 |
Maximum of Months | 0.424812E+10 | 0.223303E+10 | 0.212303E+10 | 0.526164E+10 | 0.237603E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214460E+09 | 0.00 | 0.214460E+09 | 9768737.14 | 0.128412E+10 |
February | 0.301411E+09 | 0.00 | 0.301411E+09 | 69259892.25 | 0.102648E+10 |
March | 0.491662E+09 | 0.00 | 0.491662E+09 | 0.230123E+09 | 0.930869E+09 |
April | 0.673308E+09 | 2388428.59 | 0.670920E+09 | 0.469837E+09 | 0.720482E+09 |
May | 0.895257E+09 | 26596794.15 | 0.868661E+09 | 0.758622E+09 | 0.615170E+09 |
June | 0.910975E+09 | 60156990.47 | 0.850818E+09 | 0.842562E+09 | 0.462996E+09 |
July | 0.894693E+09 | 70148169.12 | 0.824545E+09 | 0.930449E+09 | 0.432924E+09 |
August | 0.724260E+09 | 19578934.08 | 0.704681E+09 | 0.764932E+09 | 0.426576E+09 |
September | 0.544432E+09 | 160544.72 | 0.544271E+09 | 0.427076E+09 | 0.624703E+09 |
October | 0.385461E+09 | 0.00 | 0.385461E+09 | 0.177861E+09 | 0.870033E+09 |
November | 0.234970E+09 | 0.00 | 0.234970E+09 | 34068091.39 | 0.104503E+10 |
December | 0.182235E+09 | 0.00 | 0.182235E+09 | 4212751.79 | 0.131842E+10 |
Annual Sum or Average | 0.645312E+10 | 0.179030E+09 | 0.627410E+10 | 0.471877E+10 | 0.975781E+10 |
Minimum of Months | 0.182235E+09 | 0.00 | 0.182235E+09 | 4212751.79 | 0.426576E+09 |
Maximum of Months | 0.910975E+09 | 70148169.12 | 0.868661E+09 | 0.930449E+09 | 0.131842E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214468E+09 | 0.00 | 0.214468E+09 | 9767818.62 | 0.128420E+10 |
February | 0.301422E+09 | 0.00 | 0.301422E+09 | 69258830.25 | 0.102655E+10 |
March | 0.491681E+09 | 0.00 | 0.491681E+09 | 0.230126E+09 | 0.930928E+09 |
April | 0.673334E+09 | 2388492.79 | 0.670946E+09 | 0.469849E+09 | 0.720527E+09 |
May | 0.895292E+09 | 26597509.08 | 0.868695E+09 | 0.758642E+09 | 0.615208E+09 |
June | 0.911011E+09 | 60158607.51 | 0.850852E+09 | 0.842587E+09 | 0.463024E+09 |
July | 0.894729E+09 | 70150054.72 | 0.824579E+09 | 0.930482E+09 | 0.432949E+09 |
August | 0.724290E+09 | 19579460.37 | 0.704710E+09 | 0.764960E+09 | 0.426601E+09 |
September | 0.544454E+09 | 160549.03 | 0.544293E+09 | 0.427089E+09 | 0.624740E+09 |
October | 0.385475E+09 | 0.00 | 0.385475E+09 | 0.177864E+09 | 0.870087E+09 |
November | 0.234979E+09 | 0.00 | 0.234979E+09 | 34066846.30 | 0.104510E+10 |
December | 0.182242E+09 | 0.00 | 0.182242E+09 | 4212332.48 | 0.131850E+10 |
Annual Sum or Average | 0.645338E+10 | 0.179035E+09 | 0.627434E+10 | 0.471890E+10 | 0.975842E+10 |
Minimum of Months | 0.182242E+09 | 0.00 | 0.182242E+09 | 4212332.48 | 0.426601E+09 |
Maximum of Months | 0.911011E+09 | 70150054.72 | 0.868695E+09 | 0.930482E+09 | 0.131850E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214468E+09 | 0.00 | 0.214468E+09 | 9767818.62 | 0.128420E+10 |
February | 0.301422E+09 | 0.00 | 0.301422E+09 | 69258830.25 | 0.102655E+10 |
March | 0.491681E+09 | 0.00 | 0.491681E+09 | 0.230126E+09 | 0.930928E+09 |
April | 0.673334E+09 | 2388492.79 | 0.670946E+09 | 0.469849E+09 | 0.720527E+09 |
May | 0.895292E+09 | 26597509.08 | 0.868695E+09 | 0.758642E+09 | 0.615208E+09 |
June | 0.911011E+09 | 60158607.51 | 0.850852E+09 | 0.842587E+09 | 0.463024E+09 |
July | 0.894729E+09 | 70150054.72 | 0.824579E+09 | 0.930482E+09 | 0.432949E+09 |
August | 0.724290E+09 | 19579460.37 | 0.704710E+09 | 0.764960E+09 | 0.426601E+09 |
September | 0.544454E+09 | 160549.03 | 0.544293E+09 | 0.427089E+09 | 0.624740E+09 |
October | 0.385475E+09 | 0.00 | 0.385475E+09 | 0.177864E+09 | 0.870087E+09 |
November | 0.234979E+09 | 0.00 | 0.234979E+09 | 34066846.30 | 0.104510E+10 |
December | 0.182242E+09 | 0.00 | 0.182242E+09 | 4212332.48 | 0.131850E+10 |
Annual Sum or Average | 0.645338E+10 | 0.179035E+09 | 0.627434E+10 | 0.471890E+10 | 0.975842E+10 |
Minimum of Months | 0.182242E+09 | 0.00 | 0.182242E+09 | 4212332.48 | 0.426601E+09 |
Maximum of Months | 0.911011E+09 | 70150054.72 | 0.868695E+09 | 0.930482E+09 | 0.131850E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.663026E+09 | 0.168099E+09 | 0.494928E+09 | 0.246867E+09 | 0.234527E+10 |
February | 0.109885E+10 | 0.390005E+09 | 0.708849E+09 | 0.742882E+09 | 0.187948E+10 |
March | 0.181645E+10 | 0.657569E+09 | 0.115888E+10 | 0.155123E+10 | 0.175208E+10 |
April | 0.272498E+10 | 0.113226E+10 | 0.159271E+10 | 0.280199E+10 | 0.138805E+10 |
May | 0.299628E+10 | 0.104173E+10 | 0.195454E+10 | 0.322740E+10 | 0.122568E+10 |
June | 0.347262E+10 | 0.151096E+10 | 0.196167E+10 | 0.400480E+10 | 0.943887E+09 |
July | 0.334161E+10 | 0.149990E+10 | 0.184171E+10 | 0.402352E+10 | 0.860271E+09 |
August | 0.328434E+10 | 0.164301E+10 | 0.164133E+10 | 0.408316E+10 | 0.851036E+09 |
September | 0.234995E+10 | 0.108382E+10 | 0.126614E+10 | 0.259422E+10 | 0.119025E+10 |
October | 0.158275E+10 | 0.672519E+09 | 0.910234E+09 | 0.144153E+10 | 0.164945E+10 |
November | 0.750753E+09 | 0.211944E+09 | 0.538809E+09 | 0.399265E+09 | 0.194662E+10 |
December | 0.636312E+09 | 0.204847E+09 | 0.431465E+09 | 0.302585E+09 | 0.243612E+10 |
Annual Sum or Average | 0.247179E+11 | 0.102167E+11 | 0.145013E+11 | 0.254194E+11 | 0.184682E+11 |
Minimum of Months | 0.636312E+09 | 0.168099E+09 | 0.431465E+09 | 0.246867E+09 | 0.851036E+09 |
Maximum of Months | 0.347262E+10 | 0.164301E+10 | 0.196167E+10 | 0.408316E+10 | 0.243612E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 26215457.77 | 6646464.26 | 19568993.51 | 9760912.90 | 92729993.54 |
February | 43447695.55 | 15420448.04 | 28027247.51 | 29372874.17 | 74312963.01 |
March | 71820864.26 | 25999666.84 | 45821197.41 | 61334101.34 | 69275546.16 |
April | 0.107743E+09 | 44768711.23 | 62974500.44 | 0.110788E+09 | 54882383.37 |
May | 0.118470E+09 | 41189145.54 | 77280911.26 | 0.127608E+09 | 48462325.49 |
June | 0.137304E+09 | 59741882.25 | 77562527.03 | 0.158346E+09 | 37320453.77 |
July | 0.132124E+09 | 59304779.97 | 72819649.84 | 0.159086E+09 | 34014324.26 |
August | 0.129860E+09 | 64963042.56 | 64896715.45 | 0.161445E+09 | 33649184.76 |
September | 92915081.92 | 42853079.58 | 50062002.35 | 0.102573E+09 | 47061319.68 |
October | 62580638.09 | 26590795.31 | 35989842.77 | 56996818.91 | 65217756.35 |
November | 29684100.24 | 8380085.62 | 21304014.63 | 15786593.26 | 76967619.42 |
December | 25159213.77 | 8099466.92 | 17059746.85 | 11963926.24 | 96322094.57 |
Annual Sum or Average | 0.977325E+09 | 0.403958E+09 | 0.573367E+09 | 0.100506E+10 | 0.730216E+09 |
Minimum of Months | 25159213.77 | 6646464.26 | 17059746.85 | 9760912.90 | 33649184.76 |
Maximum of Months | 0.137304E+09 | 64963042.56 | 77562527.03 | 0.161445E+09 | 96322094.57 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.947578E+09 | 0.562675E+09 | 0.384903E+09 | 0.862722E+09 | 0.116838E+10 |
February | 0.131621E+10 | 0.814748E+09 | 0.501459E+09 | 0.136363E+10 | 0.975632E+09 |
March | 0.156756E+10 | 0.835959E+09 | 0.731600E+09 | 0.170025E+10 | 0.949256E+09 |
April | 0.160166E+10 | 0.695428E+09 | 0.906231E+09 | 0.183892E+10 | 0.776381E+09 |
May | 0.151333E+10 | 0.450834E+09 | 0.106250E+10 | 0.175568E+10 | 0.672493E+09 |
June | 0.133989E+10 | 0.359740E+09 | 0.980149E+09 | 0.158529E+10 | 0.516760E+09 |
July | 0.150991E+10 | 0.553007E+09 | 0.956908E+09 | 0.195761E+10 | 0.492627E+09 |
August | 0.162221E+10 | 0.756459E+09 | 0.865751E+09 | 0.216767E+10 | 0.483876E+09 |
September | 0.173936E+10 | 0.960528E+09 | 0.778832E+09 | 0.217530E+10 | 0.659793E+09 |
October | 0.162808E+10 | 0.100522E+10 | 0.622864E+09 | 0.186095E+10 | 0.887470E+09 |
November | 0.931525E+09 | 0.533841E+09 | 0.397684E+09 | 0.899983E+09 | 0.993528E+09 |
December | 0.100713E+10 | 0.651752E+09 | 0.355377E+09 | 0.999698E+09 | 0.123074E+10 |
Annual Sum or Average | 0.167244E+11 | 0.818019E+10 | 0.854426E+10 | 0.191677E+11 | 0.980694E+10 |
Minimum of Months | 0.931525E+09 | 0.359740E+09 | 0.355377E+09 | 0.862722E+09 | 0.483876E+09 |
Maximum of Months | 0.173936E+10 | 0.100522E+10 | 0.106250E+10 | 0.217530E+10 | 0.123074E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.947578E+09 | 0.562675E+09 | 0.384903E+09 | 0.862722E+09 | 0.116838E+10 |
February | 0.131621E+10 | 0.814748E+09 | 0.501459E+09 | 0.136363E+10 | 0.975632E+09 |
March | 0.156756E+10 | 0.835959E+09 | 0.731600E+09 | 0.170025E+10 | 0.949256E+09 |
April | 0.160166E+10 | 0.695428E+09 | 0.906231E+09 | 0.183892E+10 | 0.776381E+09 |
May | 0.151333E+10 | 0.450834E+09 | 0.106250E+10 | 0.175568E+10 | 0.672493E+09 |
June | 0.133989E+10 | 0.359740E+09 | 0.980149E+09 | 0.158529E+10 | 0.516760E+09 |
July | 0.150991E+10 | 0.553007E+09 | 0.956908E+09 | 0.195761E+10 | 0.492627E+09 |
August | 0.162221E+10 | 0.756459E+09 | 0.865751E+09 | 0.216767E+10 | 0.483876E+09 |
September | 0.173936E+10 | 0.960528E+09 | 0.778832E+09 | 0.217530E+10 | 0.659793E+09 |
October | 0.162808E+10 | 0.100522E+10 | 0.622864E+09 | 0.186095E+10 | 0.887470E+09 |
November | 0.931525E+09 | 0.533841E+09 | 0.397684E+09 | 0.899983E+09 | 0.993528E+09 |
December | 0.100713E+10 | 0.651752E+09 | 0.355377E+09 | 0.999698E+09 | 0.123074E+10 |
Annual Sum or Average | 0.167244E+11 | 0.818019E+10 | 0.854426E+10 | 0.191677E+11 | 0.980694E+10 |
Minimum of Months | 0.931525E+09 | 0.359740E+09 | 0.355377E+09 | 0.862722E+09 | 0.483876E+09 |
Maximum of Months | 0.173936E+10 | 0.100522E+10 | 0.106250E+10 | 0.217530E+10 | 0.123074E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.947518E+09 | 0.562639E+09 | 0.384879E+09 | 0.862667E+09 | 0.116831E+10 |
February | 0.131612E+10 | 0.814697E+09 | 0.501427E+09 | 0.136354E+10 | 0.975570E+09 |
March | 0.156746E+10 | 0.835906E+09 | 0.731554E+09 | 0.170014E+10 | 0.949196E+09 |
April | 0.160156E+10 | 0.695384E+09 | 0.906174E+09 | 0.183881E+10 | 0.776332E+09 |
May | 0.151324E+10 | 0.450805E+09 | 0.106243E+10 | 0.175557E+10 | 0.672451E+09 |
June | 0.133981E+10 | 0.359718E+09 | 0.980087E+09 | 0.158519E+10 | 0.516727E+09 |
July | 0.150982E+10 | 0.552972E+09 | 0.956847E+09 | 0.195749E+10 | 0.492596E+09 |
August | 0.162211E+10 | 0.756411E+09 | 0.865696E+09 | 0.216753E+10 | 0.483846E+09 |
September | 0.173925E+10 | 0.960467E+09 | 0.778782E+09 | 0.217516E+10 | 0.659751E+09 |
October | 0.162798E+10 | 0.100515E+10 | 0.622825E+09 | 0.186083E+10 | 0.887414E+09 |
November | 0.931466E+09 | 0.533807E+09 | 0.397659E+09 | 0.899926E+09 | 0.993465E+09 |
December | 0.100707E+10 | 0.651711E+09 | 0.355355E+09 | 0.999635E+09 | 0.123066E+10 |
Annual Sum or Average | 0.167234E+11 | 0.817967E+10 | 0.854372E+10 | 0.191665E+11 | 0.980632E+10 |
Minimum of Months | 0.931466E+09 | 0.359718E+09 | 0.355355E+09 | 0.862667E+09 | 0.483846E+09 |
Maximum of Months | 0.173925E+10 | 0.100515E+10 | 0.106243E+10 | 0.217516E+10 | 0.123066E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.699333E+09 | 0.206220E+09 | 0.493113E+09 | 0.314924E+09 | 0.236833E+10 |
February | 0.113251E+10 | 0.425627E+09 | 0.706881E+09 | 0.829471E+09 | 0.191246E+10 |
March | 0.175696E+10 | 0.593020E+09 | 0.116394E+10 | 0.152077E+10 | 0.179591E+10 |
April | 0.258680E+10 | 0.989031E+09 | 0.159777E+10 | 0.266584E+10 | 0.145589E+10 |
May | 0.343957E+10 | 0.139731E+10 | 0.204226E+10 | 0.384391E+10 | 0.130208E+10 |
June | 0.320122E+10 | 0.124292E+10 | 0.195829E+10 | 0.365426E+10 | 0.995675E+09 |
July | 0.408649E+10 | 0.214806E+10 | 0.193843E+10 | 0.509469E+10 | 0.963081E+09 |
August | 0.338050E+10 | 0.172618E+10 | 0.165433E+10 | 0.427504E+10 | 0.938111E+09 |
September | 0.266410E+10 | 0.127829E+10 | 0.138581E+10 | 0.309036E+10 | 0.127172E+10 |
October | 0.156724E+10 | 0.638572E+09 | 0.928664E+09 | 0.145531E+10 | 0.170115E+10 |
November | 0.755297E+09 | 0.213025E+09 | 0.542273E+09 | 0.423952E+09 | 0.195981E+10 |
December | 0.656139E+09 | 0.224842E+09 | 0.431298E+09 | 0.365008E+09 | 0.246548E+10 |
Annual Sum or Average | 0.259262E+11 | 0.110831E+11 | 0.148431E+11 | 0.275335E+11 | 0.191297E+11 |
Minimum of Months | 0.656139E+09 | 0.206220E+09 | 0.431298E+09 | 0.314924E+09 | 0.938111E+09 |
Maximum of Months | 0.408649E+10 | 0.214806E+10 | 0.204226E+10 | 0.509469E+10 | 0.246548E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 27650915.06 | 8153722.29 | 19497192.77 | 12451739.63 | 93641694.06 |
February | 44778247.18 | 16828866.23 | 27949380.95 | 32796402.12 | 75616901.02 |
March | 69468548.27 | 23447401.83 | 46021146.44 | 60129693.78 | 71008472.02 |
April | 0.102280E+09 | 39105269.61 | 63174340.74 | 0.105405E+09 | 57564689.01 |
May | 0.135997E+09 | 55248024.25 | 80749036.80 | 0.151984E+09 | 51483233.29 |
June | 0.126573E+09 | 49143820.67 | 77429023.39 | 0.144486E+09 | 39368096.09 |
July | 0.161576E+09 | 84932032.48 | 76643484.53 | 0.201439E+09 | 38079358.36 |
August | 0.133662E+09 | 68251229.16 | 65410395.83 | 0.169031E+09 | 37092042.61 |
September | 0.105336E+09 | 50542232.62 | 54793546.51 | 0.122190E+09 | 50282600.30 |
October | 61966936.11 | 25248478.46 | 36718457.65 | 57541358.36 | 67262020.76 |
November | 29863697.12 | 8422773.34 | 21440923.78 | 16762610.43 | 77488953.23 |
December | 25943078.99 | 8890003.39 | 17053075.60 | 14432015.21 | 97482860.53 |
Annual Sum or Average | 0.102509E+10 | 0.438214E+09 | 0.586880E+09 | 0.108865E+10 | 0.756371E+09 |
Minimum of Months | 25943078.99 | 8153722.29 | 17053075.60 | 12451739.63 | 37092042.61 |
Maximum of Months | 0.161576E+09 | 84932032.48 | 80749036.80 | 0.201439E+09 | 97482860.53 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.643410E+09 | 0.00 | 0.643410E+09 | 26303819.50 | 0.387816E+10 |
February | 0.904276E+09 | 0.00 | 0.904276E+09 | 0.189925E+09 | 0.313433E+10 |
March | 0.147506E+10 | 0.00 | 0.147506E+10 | 0.629239E+09 | 0.290938E+10 |
April | 0.202002E+10 | 7165624.79 | 0.201285E+10 | 0.131812E+10 | 0.227372E+10 |
May | 0.268590E+10 | 79794157.67 | 0.260611E+10 | 0.218623E+10 | 0.191766E+10 |
June | 0.273305E+10 | 0.180480E+09 | 0.255258E+10 | 0.245902E+10 | 0.143311E+10 |
July | 0.268421E+10 | 0.210454E+09 | 0.247375E+10 | 0.273689E+10 | 0.133380E+10 |
August | 0.217288E+10 | 58739581.33 | 0.211414E+10 | 0.225245E+10 | 0.131038E+10 |
September | 0.163337E+10 | 481656.94 | 0.163289E+10 | 0.124751E+10 | 0.190612E+10 |
October | 0.115644E+10 | 0.00 | 0.115644E+10 | 0.518188E+09 | 0.261151E+10 |
November | 0.704943E+09 | 0.00 | 0.704943E+09 | 0.100184E+09 | 0.309614E+10 |
December | 0.546732E+09 | 0.00 | 0.546732E+09 | 12194877.74 | 0.393872E+10 |
Annual Sum or Average | 0.193603E+11 | 0.537115E+09 | 0.188232E+11 | 0.136762E+11 | 0.297430E+11 |
Minimum of Months | 0.546732E+09 | 0.00 | 0.546732E+09 | 12194877.74 | 0.131038E+10 |
Maximum of Months | 0.273305E+10 | 0.210454E+09 | 0.260611E+10 | 0.273689E+10 | 0.393872E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.689252E+09 | 0.174748E+09 | 0.514504E+09 | 0.249620E+09 | 0.245207E+10 |
February | 0.114232E+10 | 0.405433E+09 | 0.736886E+09 | 0.747673E+09 | 0.197855E+10 |
March | 0.188830E+10 | 0.683582E+09 | 0.120472E+10 | 0.155958E+10 | 0.186644E+10 |
April | 0.283277E+10 | 0.117706E+10 | 0.165571E+10 | 0.285658E+10 | 0.146620E+10 |
May | 0.311479E+10 | 0.108294E+10 | 0.203185E+10 | 0.330082E+10 | 0.129176E+10 |
June | 0.360998E+10 | 0.157073E+10 | 0.203925E+10 | 0.411989E+10 | 0.980438E+09 |
July | 0.347379E+10 | 0.155924E+10 | 0.191455E+10 | 0.414310E+10 | 0.894669E+09 |
August | 0.341425E+10 | 0.170800E+10 | 0.170625E+10 | 0.421293E+10 | 0.876176E+09 |
September | 0.244291E+10 | 0.112669E+10 | 0.131622E+10 | 0.267077E+10 | 0.122898E+10 |
October | 0.164536E+10 | 0.699123E+09 | 0.946237E+09 | 0.148172E+10 | 0.168495E+10 |
November | 0.780449E+09 | 0.220329E+09 | 0.560121E+09 | 0.409299E+09 | 0.199359E+10 |
December | 0.661482E+09 | 0.212951E+09 | 0.448531E+09 | 0.310101E+09 | 0.251970E+10 |
Annual Sum or Average | 0.256957E+11 | 0.106208E+11 | 0.150748E+11 | 0.260621E+11 | 0.192335E+11 |
Minimum of Months | 0.661482E+09 | 0.174748E+09 | 0.448531E+09 | 0.249620E+09 | 0.876176E+09 |
Maximum of Months | 0.360998E+10 | 0.170800E+10 | 0.203925E+10 | 0.421293E+10 | 0.251970E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.284278E+10 | 0.168806E+10 | 0.115473E+10 | 0.253501E+10 | 0.352698E+10 |
February | 0.394869E+10 | 0.244429E+10 | 0.150440E+10 | 0.401890E+10 | 0.292485E+10 |
March | 0.470276E+10 | 0.250793E+10 | 0.219483E+10 | 0.499512E+10 | 0.288940E+10 |
April | 0.480505E+10 | 0.208633E+10 | 0.271872E+10 | 0.540116E+10 | 0.238835E+10 |
May | 0.454006E+10 | 0.135253E+10 | 0.318753E+10 | 0.515102E+10 | 0.207935E+10 |
June | 0.401972E+10 | 0.107924E+10 | 0.294047E+10 | 0.465989E+10 | 0.159384E+10 |
July | 0.452980E+10 | 0.165905E+10 | 0.287075E+10 | 0.580495E+10 | 0.149030E+10 |
August | 0.486670E+10 | 0.226942E+10 | 0.259728E+10 | 0.644950E+10 | 0.144371E+10 |
September | 0.521816E+10 | 0.288164E+10 | 0.233652E+10 | 0.647782E+10 | 0.194868E+10 |
October | 0.488433E+10 | 0.301571E+10 | 0.186862E+10 | 0.553608E+10 | 0.259011E+10 |
November | 0.279463E+10 | 0.160156E+10 | 0.119307E+10 | 0.266137E+10 | 0.293804E+10 |
December | 0.302144E+10 | 0.195530E+10 | 0.106615E+10 | 0.296176E+10 | 0.367480E+10 |
Annual Sum or Average | 0.501741E+11 | 0.245411E+11 | 0.256331E+11 | 0.566526E+11 | 0.294884E+11 |
Minimum of Months | 0.279463E+10 | 0.107924E+10 | 0.106615E+10 | 0.253501E+10 | 0.144371E+10 |
Maximum of Months | 0.521816E+10 | 0.301571E+10 | 0.318753E+10 | 0.647782E+10 | 0.367480E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.726993E+09 | 0.214377E+09 | 0.512616E+09 | 0.317010E+09 | 0.247454E+10 |
February | 0.117730E+10 | 0.442463E+09 | 0.734839E+09 | 0.837442E+09 | 0.200695E+10 |
March | 0.182646E+10 | 0.616478E+09 | 0.120998E+10 | 0.153447E+10 | 0.190868E+10 |
April | 0.268912E+10 | 0.102815E+10 | 0.166096E+10 | 0.271377E+10 | 0.154552E+10 |
May | 0.357561E+10 | 0.145258E+10 | 0.212303E+10 | 0.394634E+10 | 0.135894E+10 |
June | 0.332783E+10 | 0.129209E+10 | 0.203574E+10 | 0.375772E+10 | 0.103757E+10 |
July | 0.424812E+10 | 0.223303E+10 | 0.201509E+10 | 0.526487E+10 | 0.983903E+09 |
August | 0.351421E+10 | 0.179446E+10 | 0.171975E+10 | 0.441842E+10 | 0.960416E+09 |
September | 0.276947E+10 | 0.132885E+10 | 0.144062E+10 | 0.319404E+10 | 0.130091E+10 |
October | 0.162922E+10 | 0.663831E+09 | 0.965393E+09 | 0.150174E+10 | 0.173589E+10 |
November | 0.785171E+09 | 0.221451E+09 | 0.563720E+09 | 0.436503E+09 | 0.200205E+10 |
December | 0.682091E+09 | 0.233735E+09 | 0.448356E+09 | 0.373418E+09 | 0.254612E+10 |
Annual Sum or Average | 0.269516E+11 | 0.115215E+11 | 0.154301E+11 | 0.282957E+11 | 0.198615E+11 |
Minimum of Months | 0.682091E+09 | 0.214377E+09 | 0.448356E+09 | 0.317010E+09 | 0.960416E+09 |
Maximum of Months | 0.424812E+10 | 0.223303E+10 | 0.212303E+10 | 0.526487E+10 | 0.254612E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 12.56 | 1367.10 | 240.22 | 0.00 | 240.22 | 0.00 | 0.00 |
February | 88.43 | 1211.48 | 373.79 | 0.00 | 373.79 | 0.00 | 0.00 |
March | 252.79 | 1008.76 | 550.72 | 0.00 | 550.72 | 0.00 | 0.00 |
April | 525.80 | 822.90 | 779.33 | 2.76 | 776.56 | 0.00 | 0.00 |
May | 829.33 | 679.37 | 1002.80 | 29.79 | 973.01 | 0.00 | 0.00 |
June | 955.58 | 529.64 | 1054.42 | 69.63 | 984.79 | 0.00 | 0.00 |
July | 1025.20 | 478.37 | 1002.17 | 78.57 | 923.59 | 0.00 | 0.00 |
August | 845.74 | 468.00 | 811.26 | 21.93 | 789.33 | 0.00 | 0.00 |
September | 492.79 | 691.38 | 630.16 | 0.19 | 629.97 | 0.00 | 0.00 |
October | 212.49 | 895.12 | 431.76 | 0.00 | 431.76 | 0.00 | 0.00 |
November | 47.83 | 1097.62 | 271.97 | 0.00 | 271.97 | 0.00 | 0.00 |
December | 7.33 | 1371.62 | 204.13 | 0.00 | 204.13 | 0.00 | 0.00 |
Annual Sum or Average | 443.52 | 883.53 | 613.91 | 17.03 | 596.88 | 0.00 | 0.00 |
Minimum of Months | 7.33 | 468.00 | 204.13 | 0.00 | 204.13 | 0.00 | 0.00 |
Maximum of Months | 1025.20 | 1371.62 | 1054.42 | 78.57 | 984.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 98.65 | 865.03 | 257.34 | 65.24 | 192.09 | 0.00 | 0.00 |
February | 322.41 | 764.47 | 472.19 | 167.59 | 304.60 | 0.00 | 0.00 |
March | 599.40 | 647.56 | 705.01 | 255.22 | 449.79 | 0.00 | 0.00 |
April | 1116.66 | 533.34 | 1092.89 | 454.11 | 638.78 | 0.00 | 0.00 |
May | 1242.21 | 459.20 | 1162.93 | 404.32 | 758.61 | 0.00 | 0.00 |
June | 1594.55 | 363.27 | 1392.74 | 605.99 | 786.75 | 0.00 | 0.00 |
July | 1551.32 | 321.98 | 1296.96 | 582.15 | 714.81 | 0.00 | 0.00 |
August | 1577.58 | 314.23 | 1274.74 | 637.70 | 637.04 | 0.00 | 0.00 |
September | 1040.40 | 447.76 | 942.48 | 434.68 | 507.80 | 0.00 | 0.00 |
October | 569.56 | 579.72 | 614.31 | 261.02 | 353.28 | 0.00 | 0.00 |
November | 169.43 | 706.53 | 301.10 | 85.00 | 216.10 | 0.00 | 0.00 |
December | 122.93 | 877.61 | 246.97 | 79.51 | 167.46 | 0.00 | 0.00 |
Annual Sum or Average | 836.36 | 572.49 | 814.80 | 336.78 | 478.02 | 0.00 | 0.00 |
Minimum of Months | 98.65 | 314.23 | 246.97 | 65.24 | 167.46 | 0.00 | 0.00 |
Maximum of Months | 1594.55 | 877.61 | 1392.74 | 637.70 | 786.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 961.42 | 1241.78 | 1061.37 | 630.25 | 431.13 | 0.00 | 0.00 |
February | 1681.79 | 1132.35 | 1632.23 | 1010.37 | 621.86 | 0.00 | 0.00 |
March | 1881.66 | 1005.07 | 1755.81 | 936.35 | 819.45 | 0.00 | 0.00 |
April | 2096.43 | 869.16 | 1853.80 | 804.91 | 1048.89 | 0.00 | 0.00 |
May | 1930.30 | 737.62 | 1695.06 | 504.98 | 1190.09 | 0.00 | 0.00 |
June | 1799.37 | 588.29 | 1550.82 | 416.37 | 1134.44 | 0.00 | 0.00 |
July | 2166.64 | 534.60 | 1691.23 | 619.42 | 1071.81 | 0.00 | 0.00 |
August | 2407.81 | 516.37 | 1817.02 | 847.31 | 969.71 | 0.00 | 0.00 |
September | 2507.39 | 711.65 | 2013.18 | 1111.74 | 901.44 | 0.00 | 0.00 |
October | 2084.84 | 895.28 | 1823.60 | 1125.94 | 697.66 | 0.00 | 0.00 |
November | 1047.11 | 1045.90 | 1078.17 | 617.88 | 460.29 | 0.00 | 0.00 |
December | 1121.55 | 1281.07 | 1128.08 | 730.02 | 398.05 | 0.00 | 0.00 |
Annual Sum or Average | 1807.62 | 878.69 | 1591.01 | 778.19 | 812.82 | 0.00 | 0.00 |
Minimum of Months | 961.42 | 516.37 | 1061.37 | 416.37 | 398.05 | 0.00 | 0.00 |
Maximum of Months | 2507.39 | 1281.07 | 2013.18 | 1125.94 | 1190.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 122.54 | 872.22 | 271.43 | 80.04 | 191.39 | 0.00 | 0.00 |
February | 355.31 | 776.36 | 486.65 | 182.90 | 303.75 | 0.00 | 0.00 |
March | 584.68 | 662.49 | 681.92 | 230.17 | 451.75 | 0.00 | 0.00 |
April | 1057.04 | 560.83 | 1037.47 | 396.66 | 640.80 | 0.00 | 0.00 |
May | 1478.61 | 481.69 | 1334.98 | 542.33 | 792.65 | 0.00 | 0.00 |
June | 1450.66 | 382.76 | 1283.89 | 498.49 | 785.40 | 0.00 | 0.00 |
July | 1964.47 | 352.75 | 1586.07 | 833.72 | 752.35 | 0.00 | 0.00 |
August | 1649.78 | 343.40 | 1312.06 | 669.97 | 642.08 | 0.00 | 0.00 |
September | 1238.14 | 474.09 | 1068.47 | 512.67 | 555.79 | 0.00 | 0.00 |
October | 572.98 | 596.76 | 608.28 | 247.85 | 360.44 | 0.00 | 0.00 |
November | 177.29 | 710.87 | 302.92 | 85.44 | 217.48 | 0.00 | 0.00 |
December | 143.83 | 887.11 | 254.66 | 87.27 | 167.40 | 0.00 | 0.00 |
Annual Sum or Average | 903.19 | 590.91 | 854.63 | 365.34 | 489.29 | 0.00 | 0.00 |
Minimum of Months | 122.54 | 343.40 | 254.66 | 80.04 | 167.40 | 0.00 | 0.00 |
Maximum of Months | 1964.47 | 887.11 | 1586.07 | 833.72 | 792.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10.94 | 1438.37 | 240.22 | 0.00 | 240.22 | 0.00 | 0.00 |
February | 85.89 | 1272.97 | 373.78 | 0.00 | 373.78 | 0.00 | 0.00 |
March | 257.76 | 1042.68 | 550.71 | 0.00 | 550.71 | 0.00 | 0.00 |
April | 543.80 | 833.93 | 779.31 | 2.76 | 776.55 | 0.00 | 0.00 |
May | 849.73 | 689.06 | 1002.78 | 29.79 | 972.99 | 0.00 | 0.00 |
June | 975.21 | 535.90 | 1054.40 | 69.63 | 984.77 | 0.00 | 0.00 |
July | 1042.19 | 484.92 | 1002.15 | 78.57 | 923.57 | 0.00 | 0.00 |
August | 856.80 | 477.81 | 811.25 | 21.93 | 789.32 | 0.00 | 0.00 |
September | 494.31 | 723.06 | 630.15 | 0.19 | 629.96 | 0.00 | 0.00 |
October | 199.22 | 974.54 | 431.75 | 0.00 | 431.75 | 0.00 | 0.00 |
November | 39.43 | 1209.58 | 271.96 | 0.00 | 271.96 | 0.00 | 0.00 |
December | 4.72 | 1476.79 | 204.12 | 0.00 | 204.12 | 0.00 | 0.00 |
Annual Sum or Average | 448.90 | 928.29 | 613.90 | 17.03 | 596.87 | 0.00 | 0.00 |
Minimum of Months | 4.72 | 477.81 | 204.12 | 0.00 | 204.12 | 0.00 | 0.00 |
Maximum of Months | 1042.19 | 1476.79 | 1054.40 | 78.57 | 984.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 95.81 | 910.25 | 257.33 | 65.24 | 192.09 | 0.00 | 0.00 |
February | 319.22 | 807.62 | 472.18 | 167.59 | 304.59 | 0.00 | 0.00 |
March | 602.06 | 680.02 | 705.00 | 255.22 | 449.79 | 0.00 | 0.00 |
April | 1123.76 | 556.69 | 1092.87 | 454.10 | 638.77 | 0.00 | 0.00 |
May | 1252.62 | 475.71 | 1162.91 | 404.32 | 758.60 | 0.00 | 0.00 |
June | 1606.15 | 378.55 | 1392.72 | 605.98 | 786.74 | 0.00 | 0.00 |
July | 1561.60 | 333.89 | 1296.95 | 582.14 | 714.80 | 0.00 | 0.00 |
August | 1584.75 | 330.30 | 1274.72 | 637.68 | 637.03 | 0.00 | 0.00 |
September | 1040.43 | 477.36 | 942.47 | 434.67 | 507.79 | 0.00 | 0.00 |
October | 559.49 | 640.18 | 614.30 | 261.02 | 353.28 | 0.00 | 0.00 |
November | 160.13 | 780.71 | 301.09 | 85.00 | 216.09 | 0.00 | 0.00 |
December | 117.44 | 945.51 | 246.97 | 79.51 | 167.46 | 0.00 | 0.00 |
Annual Sum or Average | 837.92 | 608.78 | 814.79 | 336.78 | 478.01 | 0.00 | 0.00 |
Minimum of Months | 95.81 | 330.30 | 246.97 | 65.24 | 167.46 | 0.00 | 0.00 |
Maximum of Months | 1606.15 | 945.51 | 1392.72 | 637.68 | 786.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 966.29 | 1308.65 | 1061.33 | 630.22 | 431.11 | 0.00 | 0.00 |
February | 1690.97 | 1209.84 | 1632.17 | 1010.33 | 621.84 | 0.00 | 0.00 |
March | 1904.36 | 1063.21 | 1755.74 | 936.31 | 819.43 | 0.00 | 0.00 |
April | 2128.34 | 898.57 | 1853.73 | 804.88 | 1048.86 | 0.00 | 0.00 |
May | 1966.45 | 753.23 | 1695.00 | 504.96 | 1190.05 | 0.00 | 0.00 |
June | 1834.79 | 598.09 | 1550.77 | 416.36 | 1134.41 | 0.00 | 0.00 |
July | 2192.62 | 551.77 | 1691.18 | 619.39 | 1071.78 | 0.00 | 0.00 |
August | 2427.89 | 541.96 | 1816.95 | 847.27 | 969.68 | 0.00 | 0.00 |
September | 2517.66 | 763.63 | 2013.11 | 1111.70 | 901.41 | 0.00 | 0.00 |
October | 2084.35 | 994.01 | 1823.53 | 1125.89 | 697.64 | 0.00 | 0.00 |
November | 1041.63 | 1149.89 | 1078.13 | 617.86 | 460.27 | 0.00 | 0.00 |
December | 1119.71 | 1378.48 | 1128.03 | 729.99 | 398.04 | 0.00 | 0.00 |
Annual Sum or Average | 1823.37 | 932.91 | 1590.95 | 778.16 | 812.79 | 0.00 | 0.00 |
Minimum of Months | 966.29 | 541.96 | 1061.33 | 416.36 | 398.04 | 0.00 | 0.00 |
Maximum of Months | 2517.66 | 1378.48 | 2013.11 | 1125.89 | 1190.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 122.23 | 919.20 | 271.42 | 80.04 | 191.39 | 0.00 | 0.00 |
February | 356.43 | 821.79 | 486.64 | 182.89 | 303.75 | 0.00 | 0.00 |
March | 590.24 | 697.03 | 681.91 | 230.16 | 451.75 | 0.00 | 0.00 |
April | 1069.15 | 583.90 | 1037.45 | 396.66 | 640.80 | 0.00 | 0.00 |
May | 1491.90 | 505.36 | 1334.96 | 542.32 | 792.64 | 0.00 | 0.00 |
June | 1465.57 | 399.32 | 1283.87 | 498.48 | 785.39 | 0.00 | 0.00 |
July | 1977.35 | 373.79 | 1586.04 | 833.70 | 752.34 | 0.00 | 0.00 |
August | 1659.23 | 364.10 | 1312.04 | 669.96 | 642.08 | 0.00 | 0.00 |
September | 1239.41 | 510.03 | 1068.45 | 512.67 | 555.79 | 0.00 | 0.00 |
October | 564.83 | 660.25 | 608.27 | 247.84 | 360.43 | 0.00 | 0.00 |
November | 170.03 | 785.99 | 302.92 | 85.43 | 217.48 | 0.00 | 0.00 |
December | 141.67 | 956.90 | 254.66 | 87.27 | 167.39 | 0.00 | 0.00 |
Annual Sum or Average | 907.60 | 630.58 | 854.62 | 365.34 | 489.28 | 0.00 | 0.00 |
Minimum of Months | 122.23 | 364.10 | 254.66 | 80.04 | 167.39 | 0.00 | 0.00 |
Maximum of Months | 1977.35 | 956.90 | 1586.04 | 833.70 | 792.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 9.82 | 1447.94 | 240.22 | 0.00 | 240.22 | 0.00 | 0.00 |
February | 78.51 | 1295.61 | 373.79 | 0.00 | 373.79 | 0.00 | 0.00 |
March | 234.93 | 1086.24 | 550.72 | 0.00 | 550.72 | 0.00 | 0.00 |
April | 508.54 | 877.21 | 779.33 | 2.76 | 776.56 | 0.00 | 0.00 |
May | 816.24 | 715.97 | 1002.80 | 29.79 | 973.01 | 0.00 | 0.00 |
June | 948.69 | 552.90 | 1054.42 | 69.63 | 984.79 | 0.00 | 0.00 |
July | 1021.84 | 497.98 | 1002.17 | 78.57 | 923.59 | 0.00 | 0.00 |
August | 840.97 | 489.24 | 811.26 | 21.93 | 789.33 | 0.00 | 0.00 |
September | 481.29 | 735.38 | 630.16 | 0.19 | 629.97 | 0.00 | 0.00 |
October | 193.47 | 975.03 | 431.76 | 0.00 | 431.76 | 0.00 | 0.00 |
November | 38.65 | 1194.50 | 271.97 | 0.00 | 271.97 | 0.00 | 0.00 |
December | 4.55 | 1470.55 | 204.13 | 0.00 | 204.13 | 0.00 | 0.00 |
Annual Sum or Average | 433.67 | 943.15 | 613.91 | 17.03 | 596.88 | 0.00 | 0.00 |
Minimum of Months | 4.55 | 489.24 | 204.13 | 0.00 | 204.13 | 0.00 | 0.00 |
Maximum of Months | 1021.84 | 1470.55 | 1054.42 | 78.57 | 984.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 93.20 | 915.50 | 257.34 | 65.24 | 192.09 | 0.00 | 0.00 |
February | 309.06 | 817.85 | 472.19 | 167.59 | 304.60 | 0.00 | 0.00 |
March | 582.28 | 696.85 | 705.01 | 255.22 | 449.79 | 0.00 | 0.00 |
April | 1102.08 | 565.66 | 1092.89 | 454.11 | 638.78 | 0.00 | 0.00 |
May | 1232.39 | 482.29 | 1162.93 | 404.32 | 758.61 | 0.00 | 0.00 |
June | 1589.46 | 378.26 | 1392.74 | 605.99 | 786.75 | 0.00 | 0.00 |
July | 1546.86 | 334.03 | 1296.96 | 582.15 | 714.81 | 0.00 | 0.00 |
August | 1572.93 | 327.13 | 1274.74 | 637.70 | 637.04 | 0.00 | 0.00 |
September | 1030.39 | 474.14 | 942.48 | 434.68 | 507.80 | 0.00 | 0.00 |
October | 553.21 | 629.09 | 614.31 | 261.02 | 353.28 | 0.00 | 0.00 |
November | 157.91 | 769.13 | 301.10 | 85.00 | 216.10 | 0.00 | 0.00 |
December | 115.78 | 940.75 | 246.97 | 79.51 | 167.46 | 0.00 | 0.00 |
Annual Sum or Average | 826.42 | 609.89 | 814.80 | 336.78 | 478.02 | 0.00 | 0.00 |
Minimum of Months | 93.20 | 327.13 | 246.97 | 65.24 | 167.46 | 0.00 | 0.00 |
Maximum of Months | 1589.46 | 940.75 | 1392.74 | 637.70 | 786.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 946.46 | 1316.83 | 1061.37 | 630.25 | 431.13 | 0.00 | 0.00 |
February | 1661.25 | 1209.02 | 1632.23 | 1010.37 | 621.86 | 0.00 | 0.00 |
March | 1864.97 | 1078.78 | 1755.81 | 936.35 | 819.45 | 0.00 | 0.00 |
April | 2083.78 | 921.43 | 1853.80 | 804.91 | 1048.89 | 0.00 | 0.00 |
May | 1923.17 | 776.34 | 1695.06 | 504.98 | 1190.09 | 0.00 | 0.00 |
June | 1797.80 | 614.91 | 1550.82 | 416.37 | 1134.44 | 0.00 | 0.00 |
July | 2167.32 | 556.41 | 1691.23 | 619.42 | 1071.81 | 0.00 | 0.00 |
August | 2407.97 | 539.02 | 1817.02 | 847.31 | 969.71 | 0.00 | 0.00 |
September | 2499.16 | 751.81 | 2013.18 | 1111.74 | 901.44 | 0.00 | 0.00 |
October | 2066.94 | 967.04 | 1823.60 | 1125.94 | 697.66 | 0.00 | 0.00 |
November | 1026.76 | 1133.50 | 1078.17 | 617.88 | 460.29 | 0.00 | 0.00 |
December | 1105.79 | 1372.01 | 1128.08 | 730.02 | 398.05 | 0.00 | 0.00 |
Annual Sum or Average | 1796.44 | 935.07 | 1591.01 | 778.19 | 812.82 | 0.00 | 0.00 |
Minimum of Months | 946.46 | 539.02 | 1061.37 | 416.37 | 398.05 | 0.00 | 0.00 |
Maximum of Months | 2499.16 | 1372.01 | 2013.18 | 1125.94 | 1190.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 118.36 | 923.89 | 271.43 | 80.04 | 191.39 | 0.00 | 0.00 |
February | 346.16 | 829.59 | 486.65 | 182.90 | 303.75 | 0.00 | 0.00 |
March | 572.91 | 712.62 | 681.92 | 230.17 | 451.75 | 0.00 | 0.00 |
April | 1046.98 | 596.26 | 1037.47 | 396.66 | 640.80 | 0.00 | 0.00 |
May | 1473.39 | 507.37 | 1334.98 | 542.33 | 792.65 | 0.00 | 0.00 |
June | 1449.74 | 400.30 | 1283.89 | 498.49 | 785.40 | 0.00 | 0.00 |
July | 1965.68 | 367.35 | 1586.07 | 833.72 | 752.35 | 0.00 | 0.00 |
August | 1649.65 | 358.58 | 1312.06 | 669.97 | 642.08 | 0.00 | 0.00 |
September | 1232.27 | 501.89 | 1068.47 | 512.67 | 555.79 | 0.00 | 0.00 |
October | 560.68 | 648.11 | 608.28 | 247.85 | 360.44 | 0.00 | 0.00 |
November | 168.40 | 772.40 | 302.92 | 85.44 | 217.48 | 0.00 | 0.00 |
December | 139.42 | 950.61 | 254.66 | 87.27 | 167.40 | 0.00 | 0.00 |
Annual Sum or Average | 897.25 | 629.80 | 854.63 | 365.34 | 489.29 | 0.00 | 0.00 |
Minimum of Months | 118.36 | 358.58 | 254.66 | 80.04 | 167.40 | 0.00 | 0.00 |
Maximum of Months | 1965.68 | 950.61 | 1586.07 | 833.72 | 792.65 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 33651418.16 | 0.366164E+10 | 0.643410E+09 | 0.00 | 0.643410E+09 | 0.00 | 0.00 |
February | 0.213942E+09 | 0.293082E+10 | 0.904276E+09 | 0.00 | 0.904276E+09 | 0.00 | 0.00 |
March | 0.677078E+09 | 0.270186E+10 | 0.147506E+10 | 0.00 | 0.147506E+10 | 0.00 | 0.00 |
April | 0.136287E+10 | 0.213296E+10 | 0.202002E+10 | 7165624.79 | 0.201285E+10 | 0.00 | 0.00 |
May | 0.222128E+10 | 0.181962E+10 | 0.268590E+10 | 79794157.67 | 0.260611E+10 | 0.00 | 0.00 |
June | 0.247686E+10 | 0.137284E+10 | 0.273305E+10 | 0.180480E+09 | 0.255258E+10 | 0.00 | 0.00 |
July | 0.274590E+10 | 0.128125E+10 | 0.268421E+10 | 0.210454E+09 | 0.247375E+10 | 0.00 | 0.00 |
August | 0.226522E+10 | 0.125349E+10 | 0.217288E+10 | 58739581.33 | 0.211414E+10 | 0.00 | 0.00 |
September | 0.127731E+10 | 0.179207E+10 | 0.163337E+10 | 481656.94 | 0.163289E+10 | 0.00 | 0.00 |
October | 0.569142E+09 | 0.239750E+10 | 0.115644E+10 | 0.00 | 0.115644E+10 | 0.00 | 0.00 |
November | 0.123964E+09 | 0.284504E+10 | 0.704943E+09 | 0.00 | 0.704943E+09 | 0.00 | 0.00 |
December | 19636271.57 | 0.367376E+10 | 0.546732E+09 | 0.00 | 0.546732E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.139869E+11 | 0.278628E+11 | 0.193603E+11 | 0.537115E+09 | 0.188232E+11 | 0.00 | 0.00 |
Minimum of Months | 19636271.57 | 0.125349E+10 | 0.546732E+09 | 0.00 | 0.546732E+09 | 0.00 | 0.00 |
Maximum of Months | 0.274590E+10 | 0.367376E+10 | 0.273305E+10 | 0.210454E+09 | 0.260611E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.264212E+09 | 0.231690E+10 | 0.689252E+09 | 0.174748E+09 | 0.514504E+09 | 0.00 | 0.00 |
February | 0.779975E+09 | 0.184940E+10 | 0.114232E+10 | 0.405433E+09 | 0.736886E+09 | 0.00 | 0.00 |
March | 0.160544E+10 | 0.173443E+10 | 0.188830E+10 | 0.683582E+09 | 0.120472E+10 | 0.00 | 0.00 |
April | 0.289437E+10 | 0.138241E+10 | 0.283277E+10 | 0.117706E+10 | 0.165571E+10 | 0.00 | 0.00 |
May | 0.332714E+10 | 0.122991E+10 | 0.311479E+10 | 0.108294E+10 | 0.203185E+10 | 0.00 | 0.00 |
June | 0.413308E+10 | 0.941601E+09 | 0.360998E+10 | 0.157073E+10 | 0.203925E+10 | 0.00 | 0.00 |
July | 0.415507E+10 | 0.862387E+09 | 0.347379E+10 | 0.155924E+10 | 0.191455E+10 | 0.00 | 0.00 |
August | 0.422539E+10 | 0.841634E+09 | 0.341425E+10 | 0.170800E+10 | 0.170625E+10 | 0.00 | 0.00 |
September | 0.269672E+10 | 0.116059E+10 | 0.244291E+10 | 0.112669E+10 | 0.131622E+10 | 0.00 | 0.00 |
October | 0.152550E+10 | 0.155271E+10 | 0.164536E+10 | 0.699123E+09 | 0.946237E+09 | 0.00 | 0.00 |
November | 0.439158E+09 | 0.183133E+10 | 0.780449E+09 | 0.220329E+09 | 0.560121E+09 | 0.00 | 0.00 |
December | 0.329266E+09 | 0.235059E+10 | 0.661482E+09 | 0.212951E+09 | 0.448531E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.263753E+11 | 0.180539E+11 | 0.256957E+11 | 0.106208E+11 | 0.150748E+11 | 0.00 | 0.00 |
Minimum of Months | 0.264212E+09 | 0.841634E+09 | 0.661482E+09 | 0.174748E+09 | 0.448531E+09 | 0.00 | 0.00 |
Maximum of Months | 0.422539E+10 | 0.235059E+10 | 0.360998E+10 | 0.170800E+10 | 0.203925E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.257507E+10 | 0.332597E+10 | 0.284278E+10 | 0.168806E+10 | 0.115473E+10 | 0.00 | 0.00 |
February | 0.406859E+10 | 0.273937E+10 | 0.394869E+10 | 0.244429E+10 | 0.150440E+10 | 0.00 | 0.00 |
March | 0.503985E+10 | 0.269199E+10 | 0.470276E+10 | 0.250793E+10 | 0.219483E+10 | 0.00 | 0.00 |
April | 0.543395E+10 | 0.225287E+10 | 0.480505E+10 | 0.208633E+10 | 0.271872E+10 | 0.00 | 0.00 |
May | 0.517012E+10 | 0.197565E+10 | 0.454006E+10 | 0.135253E+10 | 0.318753E+10 | 0.00 | 0.00 |
June | 0.466396E+10 | 0.152484E+10 | 0.401972E+10 | 0.107924E+10 | 0.294047E+10 | 0.00 | 0.00 |
July | 0.580314E+10 | 0.143188E+10 | 0.452980E+10 | 0.165905E+10 | 0.287075E+10 | 0.00 | 0.00 |
August | 0.644908E+10 | 0.138305E+10 | 0.486670E+10 | 0.226942E+10 | 0.259728E+10 | 0.00 | 0.00 |
September | 0.649917E+10 | 0.184459E+10 | 0.521816E+10 | 0.288164E+10 | 0.233652E+10 | 0.00 | 0.00 |
October | 0.558403E+10 | 0.239791E+10 | 0.488433E+10 | 0.301571E+10 | 0.186862E+10 | 0.00 | 0.00 |
November | 0.271410E+10 | 0.271097E+10 | 0.279463E+10 | 0.160156E+10 | 0.119307E+10 | 0.00 | 0.00 |
December | 0.300395E+10 | 0.343122E+10 | 0.302144E+10 | 0.195530E+10 | 0.106615E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.570050E+11 | 0.277103E+11 | 0.501741E+11 | 0.245411E+11 | 0.256331E+11 | 0.00 | 0.00 |
Minimum of Months | 0.257507E+10 | 0.138305E+10 | 0.279463E+10 | 0.107924E+10 | 0.106615E+10 | 0.00 | 0.00 |
Maximum of Months | 0.649917E+10 | 0.343122E+10 | 0.521816E+10 | 0.301571E+10 | 0.318753E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.328215E+09 | 0.233616E+10 | 0.726993E+09 | 0.214377E+09 | 0.512616E+09 | 0.00 | 0.00 |
February | 0.859561E+09 | 0.187816E+10 | 0.117730E+10 | 0.442463E+09 | 0.734839E+09 | 0.00 | 0.00 |
March | 0.156601E+10 | 0.177441E+10 | 0.182646E+10 | 0.616478E+09 | 0.120998E+10 | 0.00 | 0.00 |
April | 0.273984E+10 | 0.145366E+10 | 0.268912E+10 | 0.102815E+10 | 0.166096E+10 | 0.00 | 0.00 |
May | 0.396031E+10 | 0.129017E+10 | 0.357561E+10 | 0.145258E+10 | 0.212303E+10 | 0.00 | 0.00 |
June | 0.376012E+10 | 0.992113E+09 | 0.332783E+10 | 0.129209E+10 | 0.203574E+10 | 0.00 | 0.00 |
July | 0.526164E+10 | 0.944795E+09 | 0.424812E+10 | 0.223303E+10 | 0.201509E+10 | 0.00 | 0.00 |
August | 0.441877E+10 | 0.919759E+09 | 0.351421E+10 | 0.179446E+10 | 0.171975E+10 | 0.00 | 0.00 |
September | 0.320926E+10 | 0.122883E+10 | 0.276947E+10 | 0.132885E+10 | 0.144062E+10 | 0.00 | 0.00 |
October | 0.153468E+10 | 0.159837E+10 | 0.162922E+10 | 0.663831E+09 | 0.965393E+09 | 0.00 | 0.00 |
November | 0.459524E+09 | 0.184259E+10 | 0.785171E+09 | 0.221451E+09 | 0.563720E+09 | 0.00 | 0.00 |
December | 0.385225E+09 | 0.237603E+10 | 0.682091E+09 | 0.233735E+09 | 0.448356E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.284831E+11 | 0.186350E+11 | 0.269516E+11 | 0.115215E+11 | 0.154301E+11 | 0.00 | 0.00 |
Minimum of Months | 0.328215E+09 | 0.919759E+09 | 0.682091E+09 | 0.214377E+09 | 0.448356E+09 | 0.00 | 0.00 |
Maximum of Months | 0.526164E+10 | 0.237603E+10 | 0.424812E+10 | 0.223303E+10 | 0.212303E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 29304374.39 | 0.385253E+10 | 0.643395E+09 | 0.00 | 0.643395E+09 | 0.00 | 0.00 |
February | 0.207778E+09 | 0.307958E+10 | 0.904256E+09 | 0.00 | 0.904256E+09 | 0.00 | 0.00 |
March | 0.690376E+09 | 0.279273E+10 | 0.147502E+10 | 0.00 | 0.147502E+10 | 0.00 | 0.00 |
April | 0.140953E+10 | 0.216154E+10 | 0.201998E+10 | 7165414.18 | 0.201281E+10 | 0.00 | 0.00 |
May | 0.227591E+10 | 0.184559E+10 | 0.268584E+10 | 79791812.30 | 0.260605E+10 | 0.00 | 0.00 |
June | 0.252774E+10 | 0.138904E+10 | 0.273300E+10 | 0.180474E+09 | 0.255252E+10 | 0.00 | 0.00 |
July | 0.279141E+10 | 0.129882E+10 | 0.268415E+10 | 0.210448E+09 | 0.247370E+10 | 0.00 | 0.00 |
August | 0.229485E+10 | 0.127978E+10 | 0.217284E+10 | 58737854.82 | 0.211410E+10 | 0.00 | 0.00 |
September | 0.128125E+10 | 0.187418E+10 | 0.163334E+10 | 481642.78 | 0.163286E+10 | 0.00 | 0.00 |
October | 0.533589E+09 | 0.261021E+10 | 0.115641E+10 | 0.00 | 0.115641E+10 | 0.00 | 0.00 |
November | 0.102202E+09 | 0.313522E+10 | 0.704927E+09 | 0.00 | 0.704927E+09 | 0.00 | 0.00 |
December | 12637416.75 | 0.395543E+10 | 0.546720E+09 | 0.00 | 0.546720E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.141566E+11 | 0.292746E+11 | 0.193599E+11 | 0.537099E+09 | 0.188228E+11 | 0.00 | 0.00 |
Minimum of Months | 12637416.75 | 0.127978E+10 | 0.546720E+09 | 0.00 | 0.546720E+09 | 0.00 | 0.00 |
Maximum of Months | 0.279141E+10 | 0.395543E+10 | 0.273300E+10 | 0.210448E+09 | 0.260605E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.256628E+09 | 0.243800E+10 | 0.689242E+09 | 0.174745E+09 | 0.514497E+09 | 0.00 | 0.00 |
February | 0.772255E+09 | 0.195379E+10 | 0.114230E+10 | 0.405425E+09 | 0.736876E+09 | 0.00 | 0.00 |
March | 0.161256E+10 | 0.182135E+10 | 0.188827E+10 | 0.683568E+09 | 0.120470E+10 | 0.00 | 0.00 |
April | 0.291278E+10 | 0.144294E+10 | 0.283272E+10 | 0.117703E+10 | 0.165569E+10 | 0.00 | 0.00 |
May | 0.335501E+10 | 0.127414E+10 | 0.311475E+10 | 0.108292E+10 | 0.203182E+10 | 0.00 | 0.00 |
June | 0.416314E+10 | 0.981208E+09 | 0.360993E+10 | 0.157070E+10 | 0.203923E+10 | 0.00 | 0.00 |
July | 0.418260E+10 | 0.894285E+09 | 0.347374E+10 | 0.155921E+10 | 0.191453E+10 | 0.00 | 0.00 |
August | 0.424461E+10 | 0.884685E+09 | 0.341420E+10 | 0.170797E+10 | 0.170623E+10 | 0.00 | 0.00 |
September | 0.269680E+10 | 0.123731E+10 | 0.244287E+10 | 0.112667E+10 | 0.131620E+10 | 0.00 | 0.00 |
October | 0.149853E+10 | 0.171467E+10 | 0.164533E+10 | 0.699110E+09 | 0.946224E+09 | 0.00 | 0.00 |
November | 0.415052E+09 | 0.202359E+10 | 0.780437E+09 | 0.220324E+09 | 0.560113E+09 | 0.00 | 0.00 |
December | 0.314549E+09 | 0.253244E+10 | 0.661471E+09 | 0.212946E+09 | 0.448525E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.264245E+11 | 0.191984E+11 | 0.256953E+11 | 0.106206E+11 | 0.150746E+11 | 0.00 | 0.00 |
Minimum of Months | 0.256628E+09 | 0.884685E+09 | 0.661471E+09 | 0.174745E+09 | 0.448525E+09 | 0.00 | 0.00 |
Maximum of Months | 0.424461E+10 | 0.253244E+10 | 0.360993E+10 | 0.170797E+10 | 0.203923E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.258811E+10 | 0.350508E+10 | 0.284267E+10 | 0.168799E+10 | 0.115468E+10 | 0.00 | 0.00 |
February | 0.409080E+10 | 0.292683E+10 | 0.394854E+10 | 0.244419E+10 | 0.150435E+10 | 0.00 | 0.00 |
March | 0.510064E+10 | 0.284771E+10 | 0.470258E+10 | 0.250782E+10 | 0.219475E+10 | 0.00 | 0.00 |
April | 0.551666E+10 | 0.232909E+10 | 0.480488E+10 | 0.208624E+10 | 0.271864E+10 | 0.00 | 0.00 |
May | 0.526693E+10 | 0.201744E+10 | 0.453990E+10 | 0.135247E+10 | 0.318743E+10 | 0.00 | 0.00 |
June | 0.475578E+10 | 0.155025E+10 | 0.401958E+10 | 0.107920E+10 | 0.294039E+10 | 0.00 | 0.00 |
July | 0.587272E+10 | 0.147785E+10 | 0.452965E+10 | 0.165899E+10 | 0.287066E+10 | 0.00 | 0.00 |
August | 0.650286E+10 | 0.145160E+10 | 0.486653E+10 | 0.226933E+10 | 0.259720E+10 | 0.00 | 0.00 |
September | 0.652577E+10 | 0.197934E+10 | 0.521797E+10 | 0.288152E+10 | 0.233645E+10 | 0.00 | 0.00 |
October | 0.558273E+10 | 0.266235E+10 | 0.488414E+10 | 0.301559E+10 | 0.186855E+10 | 0.00 | 0.00 |
November | 0.269989E+10 | 0.298052E+10 | 0.279452E+10 | 0.160149E+10 | 0.119303E+10 | 0.00 | 0.00 |
December | 0.299903E+10 | 0.369213E+10 | 0.302132E+10 | 0.195522E+10 | 0.106611E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.575019E+11 | 0.294202E+11 | 0.501723E+11 | 0.245400E+11 | 0.256322E+11 | 0.00 | 0.00 |
Minimum of Months | 0.258811E+10 | 0.145160E+10 | 0.279452E+10 | 0.107920E+10 | 0.106611E+10 | 0.00 | 0.00 |
Maximum of Months | 0.652577E+10 | 0.369213E+10 | 0.521797E+10 | 0.301559E+10 | 0.318743E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.327376E+09 | 0.246197E+10 | 0.726984E+09 | 0.214374E+09 | 0.512610E+09 | 0.00 | 0.00 |
February | 0.862268E+09 | 0.198808E+10 | 0.117729E+10 | 0.442456E+09 | 0.734831E+09 | 0.00 | 0.00 |
March | 0.158090E+10 | 0.186691E+10 | 0.182643E+10 | 0.616467E+09 | 0.120996E+10 | 0.00 | 0.00 |
April | 0.277125E+10 | 0.151346E+10 | 0.268908E+10 | 0.102814E+10 | 0.166095E+10 | 0.00 | 0.00 |
May | 0.399589E+10 | 0.135357E+10 | 0.357557E+10 | 0.145255E+10 | 0.212301E+10 | 0.00 | 0.00 |
June | 0.379875E+10 | 0.103504E+10 | 0.332779E+10 | 0.129206E+10 | 0.203572E+10 | 0.00 | 0.00 |
July | 0.529613E+10 | 0.100116E+10 | 0.424806E+10 | 0.223299E+10 | 0.201507E+10 | 0.00 | 0.00 |
August | 0.444407E+10 | 0.975203E+09 | 0.351416E+10 | 0.179443E+10 | 0.171974E+10 | 0.00 | 0.00 |
September | 0.321255E+10 | 0.132200E+10 | 0.276943E+10 | 0.132883E+10 | 0.144060E+10 | 0.00 | 0.00 |
October | 0.151285E+10 | 0.176841E+10 | 0.162920E+10 | 0.663820E+09 | 0.965383E+09 | 0.00 | 0.00 |
November | 0.440715E+09 | 0.203729E+10 | 0.785161E+09 | 0.221447E+09 | 0.563714E+09 | 0.00 | 0.00 |
December | 0.379440E+09 | 0.256296E+10 | 0.682082E+09 | 0.233732E+09 | 0.448351E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.286222E+11 | 0.198861E+11 | 0.269512E+11 | 0.115213E+11 | 0.154299E+11 | 0.00 | 0.00 |
Minimum of Months | 0.327376E+09 | 0.975203E+09 | 0.682082E+09 | 0.214374E+09 | 0.448351E+09 | 0.00 | 0.00 |
Maximum of Months | 0.529613E+10 | 0.256296E+10 | 0.424806E+10 | 0.223299E+10 | 0.212301E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 26303819.50 | 0.387816E+10 | 0.643410E+09 | 0.00 | 0.643410E+09 | 0.00 | 0.00 |
February | 0.189925E+09 | 0.313433E+10 | 0.904276E+09 | 0.00 | 0.904276E+09 | 0.00 | 0.00 |
March | 0.629239E+09 | 0.290938E+10 | 0.147506E+10 | 0.00 | 0.147506E+10 | 0.00 | 0.00 |
April | 0.131812E+10 | 0.227372E+10 | 0.202002E+10 | 7165624.79 | 0.201285E+10 | 0.00 | 0.00 |
May | 0.218623E+10 | 0.191766E+10 | 0.268590E+10 | 79794157.67 | 0.260611E+10 | 0.00 | 0.00 |
June | 0.245902E+10 | 0.143311E+10 | 0.273305E+10 | 0.180480E+09 | 0.255258E+10 | 0.00 | 0.00 |
July | 0.273689E+10 | 0.133380E+10 | 0.268421E+10 | 0.210454E+09 | 0.247375E+10 | 0.00 | 0.00 |
August | 0.225245E+10 | 0.131038E+10 | 0.217288E+10 | 58739581.33 | 0.211414E+10 | 0.00 | 0.00 |
September | 0.124751E+10 | 0.190612E+10 | 0.163337E+10 | 481656.94 | 0.163289E+10 | 0.00 | 0.00 |
October | 0.518188E+09 | 0.261151E+10 | 0.115644E+10 | 0.00 | 0.115644E+10 | 0.00 | 0.00 |
November | 0.100184E+09 | 0.309614E+10 | 0.704943E+09 | 0.00 | 0.704943E+09 | 0.00 | 0.00 |
December | 12194877.74 | 0.393872E+10 | 0.546732E+09 | 0.00 | 0.546732E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136762E+11 | 0.297430E+11 | 0.193603E+11 | 0.537115E+09 | 0.188232E+11 | 0.00 | 0.00 |
Minimum of Months | 12194877.74 | 0.131038E+10 | 0.546732E+09 | 0.00 | 0.546732E+09 | 0.00 | 0.00 |
Maximum of Months | 0.273689E+10 | 0.393872E+10 | 0.273305E+10 | 0.210454E+09 | 0.260611E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.249620E+09 | 0.245207E+10 | 0.689252E+09 | 0.174748E+09 | 0.514504E+09 | 0.00 | 0.00 |
February | 0.747673E+09 | 0.197855E+10 | 0.114232E+10 | 0.405433E+09 | 0.736886E+09 | 0.00 | 0.00 |
March | 0.155958E+10 | 0.186644E+10 | 0.188830E+10 | 0.683582E+09 | 0.120472E+10 | 0.00 | 0.00 |
April | 0.285658E+10 | 0.146620E+10 | 0.283277E+10 | 0.117706E+10 | 0.165571E+10 | 0.00 | 0.00 |
May | 0.330082E+10 | 0.129176E+10 | 0.311479E+10 | 0.108294E+10 | 0.203185E+10 | 0.00 | 0.00 |
June | 0.411989E+10 | 0.980438E+09 | 0.360998E+10 | 0.157073E+10 | 0.203925E+10 | 0.00 | 0.00 |
July | 0.414310E+10 | 0.894669E+09 | 0.347379E+10 | 0.155924E+10 | 0.191455E+10 | 0.00 | 0.00 |
August | 0.421293E+10 | 0.876176E+09 | 0.341425E+10 | 0.170800E+10 | 0.170625E+10 | 0.00 | 0.00 |
September | 0.267077E+10 | 0.122898E+10 | 0.244291E+10 | 0.112669E+10 | 0.131622E+10 | 0.00 | 0.00 |
October | 0.148172E+10 | 0.168495E+10 | 0.164536E+10 | 0.699123E+09 | 0.946237E+09 | 0.00 | 0.00 |
November | 0.409299E+09 | 0.199359E+10 | 0.780449E+09 | 0.220329E+09 | 0.560121E+09 | 0.00 | 0.00 |
December | 0.310101E+09 | 0.251970E+10 | 0.661482E+09 | 0.212951E+09 | 0.448531E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.260621E+11 | 0.192335E+11 | 0.256957E+11 | 0.106208E+11 | 0.150748E+11 | 0.00 | 0.00 |
Minimum of Months | 0.249620E+09 | 0.876176E+09 | 0.661482E+09 | 0.174748E+09 | 0.448531E+09 | 0.00 | 0.00 |
Maximum of Months | 0.421293E+10 | 0.251970E+10 | 0.360998E+10 | 0.170800E+10 | 0.203925E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.253501E+10 | 0.352698E+10 | 0.284278E+10 | 0.168806E+10 | 0.115473E+10 | 0.00 | 0.00 |
February | 0.401890E+10 | 0.292485E+10 | 0.394869E+10 | 0.244429E+10 | 0.150440E+10 | 0.00 | 0.00 |
March | 0.499512E+10 | 0.288940E+10 | 0.470276E+10 | 0.250793E+10 | 0.219483E+10 | 0.00 | 0.00 |
April | 0.540116E+10 | 0.238835E+10 | 0.480505E+10 | 0.208633E+10 | 0.271872E+10 | 0.00 | 0.00 |
May | 0.515102E+10 | 0.207935E+10 | 0.454006E+10 | 0.135253E+10 | 0.318753E+10 | 0.00 | 0.00 |
June | 0.465989E+10 | 0.159384E+10 | 0.401972E+10 | 0.107924E+10 | 0.294047E+10 | 0.00 | 0.00 |
July | 0.580495E+10 | 0.149030E+10 | 0.452980E+10 | 0.165905E+10 | 0.287075E+10 | 0.00 | 0.00 |
August | 0.644950E+10 | 0.144371E+10 | 0.486670E+10 | 0.226942E+10 | 0.259728E+10 | 0.00 | 0.00 |
September | 0.647782E+10 | 0.194868E+10 | 0.521816E+10 | 0.288164E+10 | 0.233652E+10 | 0.00 | 0.00 |
October | 0.553608E+10 | 0.259011E+10 | 0.488433E+10 | 0.301571E+10 | 0.186862E+10 | 0.00 | 0.00 |
November | 0.266137E+10 | 0.293804E+10 | 0.279463E+10 | 0.160156E+10 | 0.119307E+10 | 0.00 | 0.00 |
December | 0.296176E+10 | 0.367480E+10 | 0.302144E+10 | 0.195530E+10 | 0.106615E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.566526E+11 | 0.294884E+11 | 0.501741E+11 | 0.245411E+11 | 0.256331E+11 | 0.00 | 0.00 |
Minimum of Months | 0.253501E+10 | 0.144371E+10 | 0.279463E+10 | 0.107924E+10 | 0.106615E+10 | 0.00 | 0.00 |
Maximum of Months | 0.647782E+10 | 0.367480E+10 | 0.521816E+10 | 0.301571E+10 | 0.318753E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.317010E+09 | 0.247454E+10 | 0.726993E+09 | 0.214377E+09 | 0.512616E+09 | 0.00 | 0.00 |
February | 0.837442E+09 | 0.200695E+10 | 0.117730E+10 | 0.442463E+09 | 0.734839E+09 | 0.00 | 0.00 |
March | 0.153447E+10 | 0.190868E+10 | 0.182646E+10 | 0.616478E+09 | 0.120998E+10 | 0.00 | 0.00 |
April | 0.271377E+10 | 0.154552E+10 | 0.268912E+10 | 0.102815E+10 | 0.166096E+10 | 0.00 | 0.00 |
May | 0.394634E+10 | 0.135894E+10 | 0.357561E+10 | 0.145258E+10 | 0.212303E+10 | 0.00 | 0.00 |
June | 0.375772E+10 | 0.103757E+10 | 0.332783E+10 | 0.129209E+10 | 0.203574E+10 | 0.00 | 0.00 |
July | 0.526487E+10 | 0.983903E+09 | 0.424812E+10 | 0.223303E+10 | 0.201509E+10 | 0.00 | 0.00 |
August | 0.441842E+10 | 0.960416E+09 | 0.351421E+10 | 0.179446E+10 | 0.171975E+10 | 0.00 | 0.00 |
September | 0.319404E+10 | 0.130091E+10 | 0.276947E+10 | 0.132885E+10 | 0.144062E+10 | 0.00 | 0.00 |
October | 0.150174E+10 | 0.173589E+10 | 0.162922E+10 | 0.663831E+09 | 0.965393E+09 | 0.00 | 0.00 |
November | 0.436503E+09 | 0.200205E+10 | 0.785171E+09 | 0.221451E+09 | 0.563720E+09 | 0.00 | 0.00 |
December | 0.373418E+09 | 0.254612E+10 | 0.682091E+09 | 0.233735E+09 | 0.448356E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.282957E+11 | 0.198615E+11 | 0.269516E+11 | 0.115215E+11 | 0.154301E+11 | 0.00 | 0.00 |
Minimum of Months | 0.317010E+09 | 0.960416E+09 | 0.682091E+09 | 0.214377E+09 | 0.448356E+09 | 0.00 | 0.00 |
Maximum of Months | 0.526487E+10 | 0.254612E+10 | 0.424812E+10 | 0.223303E+10 | 0.212303E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.522142E+10 | -0.448749E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -733931319.0 | 58.98 | 0.00 | 0.00 |
February | 0.475452E+10 | -0.410683E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -647692071.0 | 58.98 | 0.00 | 0.00 |
March | 0.551027E+10 | -0.480667E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -703604267.6 | 58.99 | 0.00 | 0.00 |
April | 0.488000E+10 | -0.420625E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -673754093.9 | 58.99 | 0.00 | 0.00 |
May | 0.503683E+10 | -0.434405E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692782334.3 | 58.98 | 0.00 | 0.00 |
June | 0.482103E+10 | -0.415280E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668231044.1 | 58.98 | 0.00 | 0.00 |
July | 0.449106E+10 | -0.380332E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687737775.1 | 58.98 | 0.00 | 0.00 |
August | 0.486001E+10 | -0.417058E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689430469.3 | 58.98 | 0.00 | 0.00 |
September | 0.447277E+10 | -0.380554E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667225373.3 | 58.98 | 0.00 | 0.00 |
October | 0.475106E+10 | -0.405560E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -695460399.7 | 58.99 | 0.00 | 0.00 |
November | 0.483328E+10 | -0.414864E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -684635583.5 | 58.98 | 0.00 | 0.00 |
December | 0.497631E+10 | -0.425680E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -719515960.6 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.586086E+11 | -0.503446E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.826400E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.447277E+10 | -0.480667E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -733931319.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.551027E+10 | -0.380332E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -647692071.0 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.50 | 0.48 | 01-JAN-09:50 | 2744.45 | 32.28 | 222.33 | 218.83 | 2191.41 | 33.53 | 225.83 | 187.33 |
February | 259.50 | 0.50 | 0.48 | 01-FEB-08:30 | 4676.02 | 33.24 | 243.17 | 243.33 | 2064.71 | 29.38 | 222.17 | 221.00 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-07:30 | 7743.27 | 33.05 | 208.83 | 311.67 | 1686.13 | 21.83 | 155.83 | 267.00 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 2183.74 | 18.64 | 2.83 | 344.33 | 1216.73 | 20.87 | 212.67 | 307.00 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:10 | 1995.02 | 18.53 | 4.83 | 384.83 | 1093.07 | 20.71 | 209.50 | 343.00 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:00 | 1742.44 | 18.10 | 0.00 | 393.83 | 1003.97 | 20.32 | 190.50 | 343.67 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-05:30 | 1552.52 | 16.89 | 0.00 | 392.83 | 913.22 | 19.11 | 150.83 | 337.00 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:00 | 1846.74 | 17.94 | 2.67 | 372.67 | 1111.28 | 20.18 | 159.50 | 326.33 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2983.68 | 20.78 | 41.67 | 319.00 | 1478.49 | 21.66 | 186.50 | 287.50 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-07:49 | 7195.48 | 34.58 | 220.50 | 284.67 | 1968.69 | 23.02 | 157.50 | 256.17 |
November | 242.67 | 0.50 | 0.48 | 01-NOV-08:09 | 3058.65 | 31.81 | 224.67 | 224.17 | 2456.87 | 33.15 | 229.50 | 193.17 |
December | 160.33 | 0.50 | 0.48 | 01-DEC-09:39 | 3686.25 | 35.42 | 149.50 | 206.83 | 3141.89 | 36.90 | 149.67 | 167.17 |
Annual Sum or Average | 3714.00 | 0.51 | 3101.84 | 23.95 | 1321.00 | 3697.00 | 1520.01 | 23.68 | 2250.00 | 3236.33 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1552.52 | 16.89 | 0.00 | 206.83 | 913.22 | 19.11 | 149.67 | 167.17 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 7743.27 | 35.42 | 243.17 | 393.83 | 3141.89 | 36.90 | 229.50 | 343.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-09:50 | 911.09 | 18.95 | 61.50 | 198.67 | 567.91 | 21.21 | 75.67 | 128.67 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-08:30 | 1469.22 | 19.69 | 68.33 | 226.67 | 787.99 | 21.90 | 79.83 | 178.83 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:30 | 2659.52 | 22.08 | 79.00 | 302.00 | 1191.45 | 23.02 | 90.67 | 252.67 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:19 | 2796.72 | 21.11 | 105.50 | 346.33 | 1584.43 | 23.20 | 103.83 | 306.17 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-06:00 | 2887.52 | 21.03 | 132.50 | 390.83 | 1263.95 | 21.35 | 91.67 | 349.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:10 | 3031.04 | 20.26 | 89.00 | 402.67 | 1682.49 | 22.31 | 77.67 | 355.83 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 2859.15 | 20.72 | 148.50 | 406.33 | 1302.06 | 21.66 | 101.67 | 370.17 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:30 | 3343.46 | 22.20 | 116.33 | 377.50 | 1464.14 | 21.98 | 74.00 | 337.33 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2730.18 | 21.78 | 82.67 | 322.83 | 1531.78 | 23.01 | 77.67 | 284.33 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:40 | 2444.16 | 21.98 | 83.00 | 270.50 | 1096.07 | 22.64 | 89.17 | 224.67 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-07:00 | 1135.34 | 20.34 | 79.17 | 207.17 | 596.33 | 21.16 | 71.67 | 143.50 |
December | 160.33 | 0.53 | 0.48 | 01-DEC-09:39 | 1069.58 | 21.49 | 56.33 | 182.00 | 582.30 | 22.14 | 57.00 | 104.17 |
Annual Sum or Average | 3714.00 | 0.51 | 2458.32 | 20.98 | 1101.83 | 3633.50 | 1218.50 | 22.12 | 990.50 | 3035.50 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 911.09 | 18.95 | 56.33 | 182.00 | 567.91 | 21.16 | 57.00 | 104.17 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 3343.46 | 22.20 | 148.50 | 406.33 | 1682.49 | 23.20 | 103.83 | 370.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.55 | 0.48 | 02-JAN-10:00 | 490.08 | 14.23 | 0.00 | 176.83 | 269.03 | 16.43 | 0.00 | 45.33 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-09:20 | 620.74 | 15.47 | 0.00 | 213.83 | 353.27 | 17.73 | 0.00 | 126.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 834.48 | 17.01 | 0.00 | 297.33 | 497.24 | 19.27 | 4.00 | 214.67 |
April | 379.50 | 0.50 | 0.48 | 01-APR-07:10 | 980.20 | 17.76 | 0.00 | 347.83 | 570.78 | 19.89 | 31.83 | 300.33 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 1222.56 | 20.01 | 40.00 | 399.33 | 700.78 | 22.06 | 162.17 | 366.67 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:19 | 1281.10 | 21.20 | 60.83 | 412.67 | 757.07 | 23.27 | 193.50 | 383.67 |
July | 471.00 | 0.51 | 0.48 | 01-JUL-04:00 | 1083.92 | 20.32 | 79.33 | 423.50 | 651.77 | 22.39 | 180.00 | 382.17 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-05:49 | 951.82 | 17.84 | 0.00 | 390.67 | 584.43 | 20.03 | 53.83 | 344.67 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 906.39 | 17.88 | 0.00 | 313.17 | 553.58 | 20.10 | 16.50 | 254.83 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:09 | 675.74 | 16.03 | 0.00 | 258.50 | 412.10 | 18.37 | 0.33 | 163.83 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-09:00 | 527.98 | 14.57 | 0.00 | 189.67 | 289.61 | 16.71 | 0.00 | 64.00 |
December | 160.33 | 0.57 | 0.48 | 01-DEC-10:09 | 456.51 | 14.21 | 0.00 | 151.17 | 269.27 | 16.68 | 0.00 | 35.50 |
Annual Sum or Average | 3714.00 | 0.52 | 904.42 | 17.80 | 180.17 | 3574.50 | 533.52 | 19.97 | 642.17 | 2682.33 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 456.51 | 14.21 | 0.00 | 151.17 | 269.03 | 16.43 | 0.00 | 35.50 | |
Maximum of Months | 471.00 | 0.57 | 0.48 | 1281.10 | 21.20 | 79.33 | 423.50 | 757.07 | 23.27 | 193.50 | 383.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-10:30 | 1020.26 | 18.86 | 65.17 | 199.50 | 560.81 | 21.16 | 68.33 | 136.33 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-09:20 | 1467.67 | 19.86 | 66.67 | 228.83 | 768.83 | 21.67 | 71.67 | 181.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 2351.12 | 22.14 | 78.17 | 304.67 | 1270.38 | 23.10 | 93.67 | 251.17 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:30 | 2820.83 | 20.83 | 105.50 | 344.17 | 1239.75 | 20.75 | 59.67 | 305.83 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:30 | 2912.82 | 17.71 | 52.50 | 390.33 | 1579.16 | 18.62 | 11.67 | 354.67 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-06:10 | 2981.49 | 17.33 | 42.83 | 401.67 | 1352.65 | 18.42 | 1.17 | 361.00 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-06:10 | 3282.06 | 16.47 | 58.83 | 402.67 | 1444.99 | 17.24 | 4.67 | 360.50 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-06:19 | 3109.00 | 19.27 | 75.83 | 380.00 | 1798.21 | 20.73 | 54.50 | 341.50 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3432.57 | 22.97 | 100.50 | 314.67 | 1944.62 | 23.91 | 95.67 | 270.67 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-08:20 | 2348.42 | 22.32 | 87.33 | 272.00 | 1070.48 | 23.22 | 84.83 | 224.33 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-09:50 | 1090.60 | 18.82 | 63.33 | 208.50 | 583.82 | 20.51 | 59.83 | 140.17 |
December | 160.33 | 0.53 | 0.48 | 01-DEC-09:00 | 1090.76 | 20.31 | 48.67 | 182.00 | 585.68 | 21.07 | 49.83 | 100.67 |
Annual Sum or Average | 3714.00 | 0.51 | 2524.17 | 19.42 | 845.33 | 3629.00 | 1271.95 | 20.49 | 655.50 | 3028.50 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1020.26 | 16.47 | 42.83 | 182.00 | 560.81 | 17.24 | 1.17 | 100.67 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 3432.57 | 22.97 | 105.50 | 402.67 | 1944.62 | 23.91 | 95.67 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.51 | 0.48 | 01-JAN-09:50 | 2628.31 | 30.49 | 207.17 | 216.17 | 2123.85 | 33.20 | 222.50 | 182.50 |
February | 259.50 | 0.50 | 0.48 | 01-FEB-08:39 | 4546.28 | 32.09 | 231.50 | 240.50 | 1973.39 | 27.94 | 157.17 | 219.00 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-07:30 | 7587.42 | 32.25 | 207.67 | 309.83 | 1574.26 | 18.97 | 12.33 | 263.33 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 2076.41 | 14.68 | 0.00 | 342.83 | 1140.44 | 18.19 | 10.50 | 302.67 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:10 | 1906.79 | 14.64 | 0.00 | 382.67 | 1033.46 | 18.09 | 3.33 | 339.67 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:00 | 1665.73 | 14.46 | 0.00 | 392.00 | 952.27 | 17.92 | 0.00 | 340.00 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-05:30 | 1481.39 | 13.10 | 0.00 | 389.33 | 863.25 | 16.60 | 1.00 | 331.67 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:00 | 1751.18 | 14.23 | 0.00 | 369.33 | 1040.53 | 17.80 | 5.67 | 322.17 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2846.76 | 17.24 | 27.00 | 317.83 | 1375.12 | 19.08 | 29.67 | 282.67 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-07:49 | 7032.68 | 33.75 | 218.00 | 282.33 | 1850.18 | 20.32 | 28.33 | 254.50 |
November | 242.67 | 0.51 | 0.48 | 01-NOV-08:09 | 2948.99 | 30.64 | 215.33 | 222.17 | 2389.04 | 32.83 | 227.00 | 189.67 |
December | 160.33 | 0.50 | 0.48 | 01-DEC-09:39 | 3551.89 | 34.93 | 149.17 | 204.83 | 3041.51 | 36.50 | 149.67 | 161.33 |
Annual Sum or Average | 3714.00 | 0.51 | 2992.81 | 21.19 | 1255.83 | 3669.83 | 1443.68 | 21.56 | 847.17 | 3189.17 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1481.39 | 13.10 | 0.00 | 204.83 | 863.25 | 16.60 | 0.00 | 161.33 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 7587.42 | 34.93 | 231.50 | 392.00 | 3041.51 | 36.50 | 227.00 | 340.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-09:50 | 881.63 | 18.45 | 61.33 | 197.00 | 546.64 | 20.98 | 72.50 | 124.00 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-08:30 | 1425.96 | 19.19 | 68.00 | 225.50 | 754.71 | 21.67 | 74.33 | 174.83 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:30 | 2589.99 | 21.61 | 79.00 | 300.00 | 1137.92 | 22.82 | 80.50 | 248.83 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:19 | 2721.69 | 20.65 | 105.33 | 344.50 | 1525.45 | 23.02 | 95.33 | 303.00 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-06:00 | 2816.61 | 20.60 | 132.33 | 388.33 | 1209.34 | 21.17 | 85.17 | 344.00 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:10 | 2941.69 | 19.80 | 89.00 | 400.67 | 1614.57 | 22.11 | 75.83 | 351.33 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 2778.71 | 20.13 | 146.50 | 404.00 | 1243.00 | 20.67 | 87.17 | 365.50 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:30 | 3196.03 | 20.22 | 98.50 | 373.50 | 1398.18 | 21.80 | 71.33 | 332.83 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2656.31 | 21.30 | 82.67 | 319.67 | 1474.21 | 22.80 | 67.67 | 280.33 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:40 | 2374.30 | 21.29 | 81.00 | 267.83 | 1047.40 | 22.42 | 76.83 | 221.17 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-07:00 | 1081.37 | 18.45 | 65.67 | 203.67 | 572.12 | 20.92 | 67.83 | 137.83 |
December | 160.33 | 0.53 | 0.48 | 01-DEC-09:39 | 1034.38 | 21.01 | 56.33 | 178.83 | 556.71 | 21.88 | 54.83 | 98.33 |
Annual Sum or Average | 3714.00 | 0.51 | 2383.52 | 20.24 | 1065.67 | 3603.50 | 1167.51 | 21.81 | 909.33 | 2982.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 881.63 | 18.45 | 56.33 | 178.83 | 546.64 | 20.67 | 54.83 | 98.33 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 3196.03 | 21.61 | 146.50 | 404.00 | 1614.57 | 23.02 | 95.33 | 365.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.56 | 0.48 | 02-JAN-11:09 | 471.86 | 10.05 | 0.00 | 172.50 | 258.54 | 13.60 | 0.00 | 33.50 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-09:20 | 598.02 | 11.55 | 0.00 | 210.33 | 340.49 | 15.12 | 0.00 | 120.17 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 804.54 | 13.48 | 0.00 | 293.00 | 480.87 | 17.02 | 0.00 | 205.67 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 945.73 | 14.26 | 0.00 | 346.00 | 551.71 | 17.70 | 0.17 | 294.67 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 1176.28 | 16.05 | 26.67 | 397.83 | 676.44 | 19.98 | 51.33 | 362.00 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:30 | 1236.96 | 18.31 | 59.00 | 411.00 | 732.10 | 21.51 | 73.17 | 380.67 |
July | 471.00 | 0.51 | 0.48 | 01-JUL-04:00 | 1043.28 | 15.66 | 44.67 | 420.83 | 631.63 | 20.52 | 86.50 | 378.33 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-05:49 | 919.73 | 14.48 | 0.00 | 389.17 | 567.23 | 18.09 | 1.50 | 339.67 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 873.52 | 14.66 | 0.00 | 311.17 | 535.98 | 18.16 | 0.00 | 247.50 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:20 | 650.67 | 12.50 | 0.00 | 255.67 | 398.59 | 16.11 | 0.00 | 156.00 |
November | 242.67 | 0.55 | 0.48 | 01-NOV-10:09 | 508.67 | 10.41 | 0.00 | 184.00 | 278.51 | 13.91 | 0.00 | 53.00 |
December | 160.33 | 0.57 | 0.48 | 01-DEC-10:09 | 438.08 | 10.25 | 0.00 | 145.00 | 259.03 | 14.04 | 0.00 | 28.67 |
Annual Sum or Average | 3714.00 | 0.52 | 871.66 | 14.06 | 130.33 | 3536.50 | 515.85 | 17.78 | 212.67 | 2599.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 438.08 | 10.05 | 0.00 | 145.00 | 258.54 | 13.60 | 0.00 | 28.67 | |
Maximum of Months | 471.00 | 0.57 | 0.48 | 1236.96 | 18.31 | 59.00 | 420.83 | 732.10 | 21.51 | 86.50 | 380.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-12:00 | 989.65 | 18.46 | 64.83 | 197.67 | 538.11 | 21.05 | 67.50 | 129.83 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-09:20 | 1422.40 | 19.45 | 66.50 | 227.17 | 721.52 | 20.56 | 60.67 | 175.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 2286.33 | 21.74 | 78.17 | 302.17 | 1215.08 | 22.90 | 91.33 | 245.50 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:30 | 2709.70 | 20.40 | 105.50 | 342.00 | 1185.20 | 20.61 | 55.00 | 303.17 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:30 | 2827.03 | 17.22 | 52.33 | 389.67 | 1514.42 | 18.45 | 8.33 | 351.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-06:10 | 2862.82 | 16.84 | 42.83 | 398.50 | 1290.58 | 18.24 | 0.83 | 358.83 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-06:19 | 3151.66 | 15.98 | 58.83 | 399.00 | 1377.42 | 17.07 | 4.00 | 357.83 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-06:19 | 3022.21 | 18.82 | 75.83 | 376.67 | 1722.52 | 20.58 | 54.17 | 337.50 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3341.71 | 22.57 | 100.50 | 312.67 | 1840.65 | 23.51 | 90.83 | 266.00 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-08:30 | 2285.19 | 21.93 | 87.33 | 269.00 | 991.96 | 21.85 | 73.50 | 218.83 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-09:50 | 1057.57 | 18.40 | 62.83 | 206.83 | 559.45 | 20.38 | 58.50 | 132.67 |
December | 160.33 | 0.54 | 0.48 | 01-DEC-09:00 | 1056.11 | 19.91 | 48.67 | 180.50 | 560.32 | 20.96 | 49.67 | 94.00 |
Annual Sum or Average | 3714.00 | 0.51 | 2441.21 | 18.98 | 844.17 | 3601.83 | 1211.87 | 20.17 | 614.33 | 2971.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 989.65 | 15.98 | 42.83 | 180.50 | 538.11 | 17.07 | 0.83 | 94.00 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 3341.71 | 22.57 | 105.50 | 399.00 | 1840.65 | 23.51 | 91.33 | 358.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.51 | 0.48 | 01-JAN-09:50 | 2628.29 | 30.49 | 207.17 | 216.17 | 2123.78 | 33.20 | 222.50 | 182.50 |
February | 259.50 | 0.50 | 0.48 | 01-FEB-08:39 | 4546.23 | 32.09 | 231.50 | 240.50 | 1973.30 | 27.94 | 157.17 | 219.00 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-07:30 | 7587.32 | 32.25 | 207.67 | 309.83 | 1574.14 | 18.97 | 12.33 | 263.33 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 2076.28 | 14.68 | 0.00 | 342.83 | 1140.35 | 18.19 | 10.50 | 302.67 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:10 | 1906.67 | 14.64 | 0.00 | 382.67 | 1033.37 | 18.09 | 3.33 | 339.67 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:00 | 1665.64 | 14.46 | 0.00 | 392.00 | 952.20 | 17.92 | 0.00 | 340.00 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-05:30 | 1481.30 | 13.10 | 0.00 | 389.33 | 863.19 | 16.60 | 1.00 | 331.67 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:00 | 1751.09 | 14.23 | 0.00 | 369.33 | 1040.46 | 17.80 | 5.83 | 322.17 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2846.65 | 17.25 | 27.00 | 317.83 | 1375.02 | 19.08 | 29.67 | 282.50 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-07:49 | 7032.63 | 33.75 | 218.00 | 282.33 | 1850.07 | 20.32 | 28.33 | 254.50 |
November | 242.67 | 0.51 | 0.48 | 01-NOV-08:09 | 2948.96 | 30.64 | 215.33 | 222.17 | 2388.97 | 32.83 | 227.00 | 189.67 |
December | 160.33 | 0.50 | 0.48 | 01-DEC-09:39 | 3551.91 | 34.93 | 149.17 | 204.83 | 3041.45 | 36.50 | 149.67 | 161.33 |
Annual Sum or Average | 3714.00 | 0.51 | 2992.73 | 21.19 | 1255.83 | 3669.83 | 1443.60 | 21.56 | 847.33 | 3189.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1481.30 | 13.10 | 0.00 | 204.83 | 863.19 | 16.60 | 0.00 | 161.33 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 7587.32 | 34.93 | 231.50 | 392.00 | 3041.45 | 36.50 | 227.00 | 340.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-09:50 | 881.60 | 18.45 | 61.33 | 197.00 | 546.60 | 20.98 | 72.50 | 124.00 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-08:30 | 1425.92 | 19.19 | 68.00 | 225.50 | 754.66 | 21.67 | 74.33 | 174.83 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:30 | 2589.95 | 21.61 | 79.00 | 300.00 | 1137.86 | 22.82 | 80.50 | 248.83 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:19 | 2721.63 | 20.65 | 105.33 | 344.50 | 1525.38 | 23.02 | 95.33 | 303.00 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-06:00 | 2816.53 | 20.60 | 132.33 | 388.33 | 1209.26 | 21.17 | 85.17 | 344.00 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:10 | 2941.63 | 19.81 | 89.00 | 400.83 | 1614.50 | 22.11 | 75.83 | 351.33 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 2778.66 | 20.14 | 146.50 | 404.00 | 1242.95 | 20.67 | 87.17 | 365.50 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:30 | 3195.99 | 20.23 | 98.50 | 373.50 | 1398.12 | 21.80 | 71.33 | 332.83 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2656.27 | 21.30 | 82.67 | 319.67 | 1474.15 | 22.80 | 67.67 | 280.33 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:40 | 2374.28 | 21.29 | 81.00 | 267.83 | 1047.35 | 22.42 | 76.83 | 221.00 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-07:00 | 1081.33 | 18.45 | 65.67 | 203.67 | 572.09 | 20.92 | 67.83 | 137.83 |
December | 160.33 | 0.53 | 0.48 | 01-DEC-09:39 | 1034.36 | 21.01 | 56.33 | 178.83 | 556.68 | 21.89 | 54.83 | 98.33 |
Annual Sum or Average | 3714.00 | 0.51 | 2383.47 | 20.24 | 1065.67 | 3603.67 | 1167.45 | 21.81 | 909.33 | 2981.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 881.60 | 18.45 | 56.33 | 178.83 | 546.60 | 20.67 | 54.83 | 98.33 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 3195.99 | 21.61 | 146.50 | 404.00 | 1614.50 | 23.02 | 95.33 | 365.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.56 | 0.48 | 02-JAN-11:09 | 471.83 | 10.05 | 0.00 | 172.50 | 258.52 | 13.60 | 0.00 | 33.50 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-09:20 | 597.99 | 11.55 | 0.00 | 210.33 | 340.46 | 15.12 | 0.00 | 120.17 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 804.51 | 13.48 | 0.00 | 293.00 | 480.83 | 17.02 | 0.00 | 205.67 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 945.69 | 14.26 | 0.00 | 346.00 | 551.68 | 17.70 | 0.17 | 294.67 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 1176.23 | 16.06 | 26.67 | 397.83 | 676.39 | 19.98 | 51.33 | 362.00 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:30 | 1236.93 | 18.31 | 59.00 | 411.00 | 732.06 | 21.51 | 73.33 | 380.67 |
July | 471.00 | 0.51 | 0.48 | 01-JUL-04:00 | 1043.25 | 15.66 | 44.67 | 420.83 | 631.59 | 20.52 | 86.50 | 378.33 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-05:49 | 919.70 | 14.48 | 0.00 | 389.17 | 567.20 | 18.09 | 1.50 | 339.67 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 873.50 | 14.66 | 0.00 | 311.17 | 535.95 | 18.16 | 0.00 | 247.50 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:20 | 650.65 | 12.50 | 0.00 | 255.67 | 398.56 | 16.11 | 0.00 | 156.00 |
November | 242.67 | 0.55 | 0.48 | 01-NOV-10:09 | 508.64 | 10.42 | 0.00 | 184.00 | 278.48 | 13.91 | 0.00 | 53.00 |
December | 160.33 | 0.57 | 0.48 | 01-DEC-10:09 | 438.06 | 10.25 | 0.00 | 145.00 | 259.01 | 14.04 | 0.00 | 28.67 |
Annual Sum or Average | 3714.00 | 0.52 | 871.63 | 14.06 | 130.33 | 3536.50 | 515.82 | 17.78 | 212.83 | 2599.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 438.06 | 10.05 | 0.00 | 145.00 | 258.52 | 13.60 | 0.00 | 28.67 | |
Maximum of Months | 471.00 | 0.57 | 0.48 | 1236.93 | 18.31 | 59.00 | 420.83 | 732.06 | 21.51 | 86.50 | 380.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-12:00 | 989.62 | 18.46 | 64.83 | 197.67 | 538.07 | 21.05 | 67.50 | 129.83 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-09:20 | 1422.37 | 19.45 | 66.50 | 227.17 | 721.47 | 20.56 | 60.67 | 175.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 2286.28 | 21.75 | 78.17 | 302.17 | 1215.01 | 22.90 | 91.33 | 245.50 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:30 | 2709.64 | 20.41 | 105.50 | 342.00 | 1185.12 | 20.61 | 55.00 | 303.17 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:30 | 2826.95 | 17.22 | 52.33 | 389.67 | 1514.34 | 18.45 | 8.33 | 351.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-06:10 | 2862.76 | 16.84 | 42.83 | 398.50 | 1290.51 | 18.24 | 0.83 | 358.83 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-06:19 | 3151.60 | 15.98 | 58.83 | 399.00 | 1377.35 | 17.08 | 4.00 | 357.83 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-06:19 | 3022.18 | 18.82 | 75.83 | 376.67 | 1722.46 | 20.58 | 54.17 | 337.50 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3341.68 | 22.57 | 100.50 | 312.67 | 1840.58 | 23.51 | 90.83 | 266.00 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-08:30 | 2285.16 | 21.93 | 87.33 | 269.00 | 991.91 | 21.85 | 73.50 | 218.83 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-09:50 | 1057.54 | 18.41 | 62.83 | 206.83 | 559.41 | 20.39 | 58.50 | 132.67 |
December | 160.33 | 0.54 | 0.48 | 01-DEC-09:00 | 1056.10 | 19.91 | 48.67 | 180.50 | 560.29 | 20.96 | 49.67 | 94.00 |
Annual Sum or Average | 3714.00 | 0.51 | 2441.16 | 18.98 | 844.17 | 3601.83 | 1211.81 | 20.17 | 614.33 | 2971.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 989.62 | 15.98 | 42.83 | 180.50 | 538.07 | 17.08 | 0.83 | 94.00 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 3341.68 | 22.57 | 105.50 | 399.00 | 1840.58 | 23.51 | 91.33 | 358.83 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.459083E+09 | 20967.87 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.459083E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.459083E+09 | 20967.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.491468E+10 | 10901.04 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.283715E+10 | 10901.04 | 01-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196344E+10 | 10901.04 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109891E+10 | 10901.04 | 03-APR-11:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.666630E+09 | 10901.04 | 10-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.296915E+09 | 10350.15 | 01-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 65714178.73 | 6283.17 | 13-JUL-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75155687.45 | 8287.97 | 03-AUG-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.278510E+09 | 10901.04 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.960715E+09 | 10901.04 | 05-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.257788E+10 | 10901.04 | 01-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.384054E+10 | 10901.04 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 65714178.73 | 6283.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.491468E+10 | 10901.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.147875E+10 | 7279.41 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.591974E+09 | 7279.41 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 86774258.16 | 7279.41 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8387044.44 | 6261.32 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5372096.06 | 2624.35 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.248594E+09 | 7279.41 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.848282E+09 | 7279.41 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.326814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.147875E+10 | 7279.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.245862E+10 | 7229.15 | 07-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117448E+10 | 7143.03 | 25-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.268451E+09 | 7117.58 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 36031277.93 | 7117.00 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13414931.72 | 7089.53 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.434961E+09 | 7126.07 | 18-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142259E+10 | 7327.31 | 26-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.580855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.245862E+10 | 7327.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.149975E+10 | 7230.97 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.609200E+09 | 7230.97 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109533E+09 | 7230.97 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14187341.69 | 6845.49 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4261548.24 | 1642.44 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.257732E+09 | 7230.97 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.856606E+09 | 7230.97 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.149975E+10 | 7230.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.143630E+10 | 20992.17 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.268747E+09 | 20992.17 | 06-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10657153.87 | 20992.17 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 84691139.65 | 20992.17 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455112E+09 | 20992.17 | 11-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.225551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.143630E+10 | 20992.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.159704E+10 | 11667.34 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.603463E+09 | 11667.34 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104501E+09 | 11667.34 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19220274.35 | 10088.20 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21622391.61 | 8170.62 | 16-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.427003E+09 | 11667.34 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110353E+10 | 11667.34 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.387637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.159704E+10 | 11667.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125918E+10 | 7731.01 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.508528E+09 | 7731.01 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 72607685.37 | 7731.01 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8379408.76 | 6856.11 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19427700.90 | 6932.40 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.347707E+09 | 7731.01 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.870893E+09 | 7731.01 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.308672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.125918E+10 | 7731.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.221080E+10 | 7877.46 | 19-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.967610E+09 | 7880.13 | 21-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159416E+09 | 7865.09 | 06-MAR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22123414.62 | 7800.11 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31693083.67 | 7832.51 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.611017E+09 | 7891.51 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152517E+10 | 7887.18 | 27-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.552783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.221080E+10 | 7891.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.135708E+10 | 7688.50 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.558627E+09 | 7688.50 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 97854884.25 | 7688.50 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15033726.90 | 6950.16 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20736223.07 | 6493.38 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.382732E+09 | 7688.50 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.936098E+09 | 7688.50 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.336817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.135708E+10 | 7688.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.401514E+10 | 31056.67 | 02-JAN-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167947E+10 | 30979.74 | 17-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.250832E+09 | 30852.58 | 08-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19636876.05 | 18040.29 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 48807391.33 | 30832.88 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115202E+10 | 30958.40 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.277389E+10 | 31113.90 | 18-DEC-06:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.993979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.401514E+10 | 31113.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.285474E+10 | 14894.18 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144237E+10 | 14894.18 | 01-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.497182E+09 | 14894.18 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157276E+09 | 14894.18 | 18-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10564855.00 | 10878.83 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3393426.43 | 3510.34 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189808E+09 | 14894.18 | 16-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118138E+10 | 14894.18 | 10-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229463E+10 | 14894.18 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.863135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.285474E+10 | 14894.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.228778E+10 | 9795.72 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118407E+10 | 9795.72 | 01-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.336161E+09 | 9795.72 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 73469721.15 | 9795.72 | 11-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6293241.76 | 6932.88 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1171559.79 | 2690.57 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149354E+09 | 9795.72 | 16-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.922012E+09 | 9795.72 | 10-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182014E+10 | 9795.72 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.678046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.228778E+10 | 9795.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.375954E+10 | 9462.71 | 06-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212480E+10 | 8929.28 | 16-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.715871E+09 | 8931.59 | 06-MAR-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.190712E+09 | 8903.26 | 04-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9139675.02 | 8880.87 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4948608.17 | 4035.47 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.281141E+09 | 8910.66 | 27-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156369E+10 | 8964.71 | 27-NOV-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.304454E+10 | 8925.37 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.375954E+10 | 9462.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.233499E+10 | 9749.35 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126286E+10 | 9749.35 | 01-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.426629E+09 | 9749.35 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118475E+09 | 9749.35 | 11-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7748432.21 | 6953.14 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2635548.40 | 1977.65 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170103E+09 | 9749.35 | 16-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.976211E+09 | 9749.35 | 10-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188504E+10 | 9749.35 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.718470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.233499E+10 | 9749.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.741100E+10 | 14254.73 | 06-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.476227E+10 | 14237.63 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174573E+10 | 11093.14 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.666364E+09 | 8354.75 | 19-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86358411.26 | 3360.91 | 18-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1594206.72 | 1349.51 | 27-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.234108E+09 | 4395.21 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.302691E+10 | 10934.07 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.599868E+10 | 14254.73 | 26-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.741100E+10 | 14254.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.780232E+10 | 14796.40 | 07-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.526287E+10 | 14159.86 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.281618E+10 | 11668.94 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123278E+10 | 8858.56 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.289251E+09 | 4933.64 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8191776.47 | 1224.28 | 15-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 36021898.26 | 2475.72 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.666336E+09 | 5190.12 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.389507E+10 | 10788.27 | 24-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.670948E+10 | 15440.70 | 26-DEC-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.287185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.780232E+10 | 15440.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.832770E+10 | 14306.66 | 06-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.565649E+10 | 14306.66 | 18-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.324929E+10 | 14306.66 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152381E+10 | 10970.83 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.445219E+09 | 6263.32 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 25722324.16 | 2111.18 | 15-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 82706338.12 | 3481.33 | 27-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.954876E+09 | 5924.49 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.426017E+10 | 13702.19 | 24-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.721998E+10 | 14306.66 | 26-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.317460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.832770E+10 | 14306.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.193674E+09 | 0.172559E+09 | 11614.32 | 27-FEB-15:00 | 11559.80 | 0.00 |
March | 0.00 | 0.00 | 0.153008E+10 | 0.139975E+10 | 11536.07 | 17-MAR-16:00 | 11536.07 | 0.00 |
April | 0.00 | 0.00 | 0.493690E+10 | 0.474250E+10 | 50618.50 | 27-APR-15:10 | 50618.50 | 0.00 |
May | 0.00 | 0.00 | 0.767325E+10 | 0.681281E+10 | 45413.45 | 15-MAY-16:00 | 45413.45 | 0.00 |
June | 0.00 | 0.00 | 0.141281E+11 | 0.130974E+11 | 52148.69 | 28-JUN-15:30 | 52148.69 | 0.00 |
July | 0.00 | 0.00 | 0.271642E+11 | 0.239022E+11 | 69495.80 | 31-JUL-16:00 | 63024.86 | 0.00 |
August | 0.00 | 0.00 | 0.371711E+11 | 0.324226E+11 | 71271.88 | 10-AUG-16:10 | 59636.81 | 0.00 |
September | 0.00 | 0.00 | 0.137898E+11 | 0.114464E+11 | 57738.34 | 14-SEP-13:00 | 41827.97 | 0.00 |
October | 0.00 | 0.00 | 0.257288E+10 | 0.239580E+10 | 33802.09 | 04-OCT-15:10 | 33802.09 | 0.00 |
November | 0.00 | 0.00 | 0.439940E+09 | 0.311440E+09 | 16679.79 | 04-NOV-14:40 | 11896.25 | 0.00 |
December | 0.00 | 0.00 | 601630.40 | 528814.65 | 715.11 | 05-DEC-11:50 | 630.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.109601E+12 | 0.967040E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.371711E+11 | 0.324226E+11 | 71271.88 | 63024.86 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.178341E+09 | 0.161886E+09 | 12145.82 | 27-FEB-15:05 | 12145.82 | 0.00 |
March | 0.00 | 0.00 | 0.273502E+09 | 0.242711E+09 | 10696.28 | 18-MAR-14:05 | 10696.28 | 0.00 |
April | 0.00 | 0.00 | 0.333479E+10 | 0.320240E+10 | 49597.00 | 27-APR-14:05 | 49597.00 | 0.00 |
May | 0.00 | 0.00 | 0.691614E+10 | 0.618898E+10 | 43340.29 | 04-MAY-15:00 | 43340.29 | 0.00 |
June | 0.00 | 0.00 | 0.127803E+11 | 0.118899E+11 | 48467.74 | 28-JUN-15:30 | 48467.74 | 0.00 |
July | 0.00 | 0.00 | 0.242717E+11 | 0.215178E+11 | 67115.69 | 31-JUL-14:05 | 60129.69 | 0.00 |
August | 0.00 | 0.00 | 0.321153E+11 | 0.281535E+11 | 66759.09 | 10-AUG-14:05 | 60369.28 | 0.00 |
September | 0.00 | 0.00 | 0.119794E+11 | 0.997478E+10 | 53592.62 | 13-SEP-14:05 | 41600.43 | 0.00 |
October | 0.00 | 0.00 | 0.151094E+10 | 0.141564E+10 | 30882.53 | 04-OCT-15:00 | 30882.53 | 0.00 |
November | 0.00 | 0.00 | 0.335049E+09 | 0.234432E+09 | 18369.85 | 04-NOV-14:05 | 14369.22 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.936954E+11 | 0.829820E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.321153E+11 | 0.281535E+11 | 67115.69 | 60369.28 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.184762E+09 | 0.162487E+09 | 11710.93 | 27-FEB-15:00 | 11710.93 | 0.00 |
March | 0.00 | 0.00 | 0.400694E+09 | 0.363287E+09 | 10571.95 | 18-MAR-16:00 | 10571.95 | 0.00 |
April | 0.00 | 0.00 | 0.354056E+10 | 0.337338E+10 | 56529.69 | 27-APR-14:40 | 56529.69 | 0.00 |
May | 0.00 | 0.00 | 0.728269E+10 | 0.645256E+10 | 47159.61 | 04-MAY-15:00 | 47159.61 | 0.00 |
June | 0.00 | 0.00 | 0.134641E+11 | 0.124257E+11 | 56465.68 | 28-JUN-15:20 | 56465.68 | 0.00 |
July | 0.00 | 0.00 | 0.258648E+11 | 0.227320E+11 | 73868.51 | 31-JUL-14:40 | 67062.22 | 0.00 |
August | 0.00 | 0.00 | 0.338996E+11 | 0.295973E+11 | 74333.67 | 10-AUG-14:50 | 69093.60 | 0.00 |
September | 0.00 | 0.00 | 0.120651E+11 | 0.992343E+10 | 53303.04 | 14-SEP-13:30 | 42232.83 | 0.00 |
October | 0.00 | 0.00 | 0.138471E+10 | 0.128050E+10 | 30261.14 | 04-OCT-15:00 | 30261.14 | 0.00 |
November | 0.00 | 0.00 | 0.342930E+09 | 0.232514E+09 | 18525.71 | 04-NOV-14:20 | 13801.42 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.984299E+11 | 0.865432E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.338996E+11 | 0.295973E+11 | 74333.67 | 69093.60 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1828.67 | 6363.06 | 20-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1850.74 | 6395.44 | 08-FEB-12:07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1951.32 | 6369.30 | 01-MAR-12:07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1775.83 | 6219.86 | 04-APR-11:06 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1776.81 | 6029.22 | 02-MAY-11:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1758.48 | 5797.83 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1571.78 | 5585.78 | 03-JUL-11:15 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1713.91 | 5518.06 | 01-AUG-11:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1621.62 | 5633.87 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1667.73 | 5853.44 | 31-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1754.56 | 6069.72 | 30-NOV-12:06 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1740.90 | 6256.35 | 26-DEC-12:07 |
Annual Sum or Average | 0.00 | 1750.47 | ||||
Minimum of Months | 0.00 | 0.00 | 1571.78 | 5518.06 | ||
Maximum of Months | 0.00 | 0.00 | 1951.32 | 6395.44 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.119958E+10 | 0.31 | 2621.32 | 02-JAN-06:11 | 0.77 |
February | 0.110558E+10 | 0.30 | 1426.95 | 28-FEB-08:10 | 0.58 |
March | 0.152267E+10 | 0.32 | 2220.02 | 02-MAR-13:07 | 0.71 |
April | 0.180058E+10 | 0.32 | 5613.82 | 27-APR-15:10 | 1.20 |
May | 0.248565E+10 | 0.36 | 6155.38 | 15-MAY-15:10 | 1.28 |
June | 0.310661E+10 | 0.40 | 6281.57 | 28-JUN-15:10 | 1.28 |
July | 0.388129E+10 | 0.43 | 8775.06 | 24-JUL-15:10 | 1.58 |
August | 0.461612E+10 | 0.48 | 9286.69 | 14-AUG-15:10 | 1.64 |
September | 0.302328E+10 | 0.39 | 7981.12 | 11-SEP-15:40 | 1.49 |
October | 0.190925E+10 | 0.32 | 5910.57 | 04-OCT-15:30 | 1.25 |
November | 0.128235E+10 | 0.29 | 1609.72 | 10-NOV-08:62 | 0.61 |
December | 0.117932E+10 | 0.29 | 1416.99 | 11-DEC-06:11 | 0.58 |
Annual Sum or Average | 0.271123E+11 | 0.35 | |||
Minimum of Months | 0.110558E+10 | 0.29 | 1416.99 | 0.58 | |
Maximum of Months | 0.461612E+10 | 0.48 | 9286.69 | 1.64 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.103638E+10 | 0.30 | 2609.10 | 02-JAN-06:11 | 0.83 |
February | 0.927501E+09 | 0.29 | 2609.10 | 14-FEB-07:01 | 0.83 |
March | 0.116990E+10 | 0.30 | 2204.97 | 01-MAR-13:01 | 0.75 |
April | 0.146998E+10 | 0.31 | 6554.60 | 27-APR-14:05 | 1.42 |
May | 0.210049E+10 | 0.36 | 6779.06 | 15-MAY-14:05 | 1.46 |
June | 0.263446E+10 | 0.40 | 6252.73 | 28-JUN-14:05 | 1.38 |
July | 0.332757E+10 | 0.42 | 8862.73 | 31-JUL-14:05 | 1.72 |
August | 0.383633E+10 | 0.46 | 8977.48 | 14-AUG-14:05 | 1.74 |
September | 0.241716E+10 | 0.37 | 7668.54 | 11-SEP-15:00 | 1.57 |
October | 0.137206E+10 | 0.30 | 5256.77 | 04-OCT-15:10 | 1.25 |
November | 0.963836E+09 | 0.28 | 2609.10 | 24-NOV-07:01 | 0.83 |
December | 0.978238E+09 | 0.28 | 2609.10 | 18-DEC-07:02 | 0.83 |
Annual Sum or Average | 0.222339E+11 | 0.34 | |||
Minimum of Months | 0.927501E+09 | 0.28 | 2204.97 | 0.75 | |
Maximum of Months | 0.383633E+10 | 0.46 | 8977.48 | 1.74 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.128250E+10 | 0.36 | 2504.54 | 04-JAN-06:11 | 0.76 |
February | 0.109028E+10 | 0.33 | 2504.54 | 09-FEB-07:02 | 0.76 |
March | 0.124357E+10 | 0.33 | 2504.54 | 06-MAR-06:11 | 0.76 |
April | 0.144814E+10 | 0.32 | 6256.69 | 27-APR-14:30 | 1.28 |
May | 0.199028E+10 | 0.35 | 6655.32 | 15-MAY-14:50 | 1.34 |
June | 0.245338E+10 | 0.38 | 6402.60 | 28-JUN-15:20 | 1.30 |
July | 0.313558E+10 | 0.40 | 8711.33 | 31-JUL-14:50 | 1.58 |
August | 0.354219E+10 | 0.43 | 8847.49 | 10-AUG-15:20 | 1.59 |
September | 0.216977E+10 | 0.36 | 6844.09 | 11-SEP-15:10 | 1.36 |
October | 0.131130E+10 | 0.31 | 4480.75 | 04-OCT-14:50 | 1.05 |
November | 0.107375E+10 | 0.31 | 2504.54 | 24-NOV-06:11 | 0.76 |
December | 0.114263E+10 | 0.32 | 2504.54 | 04-DEC-06:11 | 0.76 |
Annual Sum or Average | 0.218834E+11 | 0.35 | |||
Minimum of Months | 0.107375E+10 | 0.31 | 2504.54 | 0.76 | |
Maximum of Months | 0.354219E+10 | 0.43 | 8847.49 | 1.59 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:05 | 2.06 | 2.06 | 57.67 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:05 | 2.06 | 2.06 | 55.52 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:02 | 2.06 | 2.06 | 56.36 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 55.48 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:05 | 2.06 | 2.06 | 56.10 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.04 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 55.85 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 55.92 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 55.79 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.52 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:05 | 2.06 | 2.06 | 56.00 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:05 | 2.06 | 2.06 | 56.43 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 55.48 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.67 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 57.63 | 57.63 | 1828.67 | 6363.06 | 20-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.26 | 56.26 | 1850.74 | 6395.44 | 08-FEB-12:07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.84 | 56.84 | 1951.32 | 6369.30 | 01-MAR-12:07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.12 | 56.12 | 1775.83 | 6219.86 | 04-APR-11:06 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.81 | 57.81 | 1776.81 | 6029.22 | 02-MAY-11:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.49 | 56.49 | 1758.48 | 5797.83 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.32 | 56.32 | 1571.78 | 5585.78 | 03-JUL-11:15 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.52 | 56.52 | 1713.91 | 5518.06 | 01-AUG-11:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.26 | 56.26 | 1621.62 | 5633.87 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.65 | 56.65 | 1667.73 | 5853.44 | 31-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.60 | 56.60 | 1754.56 | 6069.72 | 30-NOV-12:06 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.38 | 57.38 | 1740.90 | 6256.35 | 26-DEC-12:07 |
Annual Sum or Average | 0.00 | 1750.47 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.12 | 56.12 | 1571.78 | 5518.06 | ||
Maximum of Months | 0.00 | 0.00 | 57.81 | 57.81 | 1951.32 | 6395.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.120105E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.637133E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.438042E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.422685E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.507134E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.691404E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.105901E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.138298E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.666497E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.356298E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.491956E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.814751E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.866894E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.356298E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.138298E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.889678E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.388308E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.169104E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.237187E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.381846E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.580919E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.926365E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.117522E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.534234E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.185581E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.290248E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.586904E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.634560E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.169104E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.117522E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.165347E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.883451E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.358181E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.289906E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.383758E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.581016E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.948443E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.119465E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.514578E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.251298E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.695747E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.129609E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.905058E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.251298E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.165347E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.119958E+10 | 0.00 | 0.182219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110558E+10 | 0.193674E+09 | 0.997507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152267E+10 | 0.153008E+10 | 0.417393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180058E+10 | 0.493690E+10 | 0.182388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.248565E+10 | 0.767325E+10 | 0.752989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.310661E+10 | 0.141281E+11 | 0.296915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.388129E+10 | 0.271642E+11 | 65714178.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.461612E+10 | 0.371711E+11 | 75155687.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.302328E+10 | 0.137898E+11 | 0.280104E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.190925E+10 | 0.257288E+10 | 0.121787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128235E+10 | 0.439940E+09 | 0.654608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117932E+10 | 601630.40 | 0.129667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271123E+11 | 0.109601E+12 | 0.563963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110558E+10 | 0.00 | 65714178.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.461612E+10 | 0.371711E+11 | 0.182219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.103638E+10 | 0.00 | 0.156627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.927501E+09 | 0.178341E+09 | 0.816984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116990E+10 | 0.273502E+09 | 0.326122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146998E+10 | 0.333479E+10 | 0.129754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.210049E+10 | 0.691614E+10 | 0.289251E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.263446E+10 | 0.127803E+11 | 8191776.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.332757E+10 | 0.242717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.383633E+10 | 0.321153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.241716E+10 | 0.119794E+11 | 36021898.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137206E+10 | 0.151094E+10 | 0.759815E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.963836E+09 | 0.335049E+09 | 0.574822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.978238E+09 | 0.00 | 0.116003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222339E+11 | 0.936954E+11 | 0.468331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.927501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.383633E+10 | 0.321153E+11 | 0.156627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.128250E+10 | 0.00 | 0.235799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109028E+10 | 0.184762E+09 | 0.133501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124357E+10 | 0.400694E+09 | 0.547596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144814E+10 | 0.354056E+10 | 0.208338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.199028E+10 | 0.728269E+10 | 0.478965E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.245338E+10 | 0.134641E+11 | 25722324.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.313558E+10 | 0.258648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.354219E+10 | 0.338996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.216977E+10 | 0.120651E+11 | 94855480.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131130E+10 | 0.138471E+10 | 0.179409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107375E+10 | 0.342930E+09 | 0.100555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114263E+10 | 0.00 | 0.190382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218834E+11 | 0.984299E+11 | 0.759766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.354219E+10 | 0.338996E+11 | 0.235799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.119958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110558E+10 | 0.00 | 0.00 | 0.00 | 52950809.77 | 0.521280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152267E+10 | 0.00 | 0.00 | 0.00 | 0.429557E+09 | 0.242820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180058E+10 | 0.00 | 0.00 | 0.00 | 0.126877E+10 | 0.115751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.248565E+10 | 0.00 | 0.00 | 0.00 | 0.191906E+10 | 0.666630E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.310661E+10 | 0.00 | 0.00 | 0.00 | 0.351051E+10 | 0.296915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.388129E+10 | 0.00 | 0.00 | 0.00 | 0.664305E+10 | 65714178.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.461612E+10 | 0.00 | 0.00 | 0.00 | 0.913853E+10 | 75155687.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.302328E+10 | 0.00 | 0.00 | 0.00 | 0.336318E+10 | 0.278510E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.190925E+10 | 0.00 | 0.00 | 0.00 | 0.669969E+09 | 0.983763E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128235E+10 | 0.00 | 0.00 | 0.00 | 0.118043E+09 | 0.351917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117932E+10 | 0.00 | 0.00 | 0.00 | 177140.01 | 0.696802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271123E+11 | 0.00 | 0.00 | 0.00 | 0.271138E+11 | 0.324633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65714178.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.461612E+10 | 0.00 | 0.00 | 0.00 | 0.913853E+10 | 0.108109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.103638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.786040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.927501E+09 | 0.00 | 0.00 | 0.00 | 48603099.38 | 0.290697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116990E+10 | 0.00 | 0.00 | 0.00 | 76101747.40 | 0.445037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146998E+10 | 0.00 | 0.00 | 0.00 | 0.837134E+09 | 64756824.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.210049E+10 | 0.00 | 0.00 | 0.00 | 0.171797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.263446E+10 | 0.00 | 0.00 | 0.00 | 0.317474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.332757E+10 | 0.00 | 0.00 | 0.00 | 0.593608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.383633E+10 | 0.00 | 0.00 | 0.00 | 0.791589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.241716E+10 | 0.00 | 0.00 | 0.00 | 0.292518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137206E+10 | 0.00 | 0.00 | 0.00 | 0.390276E+09 | 93479399.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.963836E+09 | 0.00 | 0.00 | 0.00 | 85489037.16 | 0.185315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.978238E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222339E+11 | 0.00 | 0.00 | 0.00 | 0.231075E+11 | 0.181146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.927501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.383633E+10 | 0.00 | 0.00 | 0.00 | 0.791589E+10 | 0.786040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.128250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109028E+10 | 0.00 | 0.00 | 0.00 | 50655829.57 | 0.769357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124357E+10 | 0.00 | 0.00 | 0.00 | 0.111567E+09 | 0.222668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144814E+10 | 0.00 | 0.00 | 0.00 | 0.891352E+09 | 0.559570E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.199028E+10 | 0.00 | 0.00 | 0.00 | 0.181355E+10 | 33746203.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.245338E+10 | 0.00 | 0.00 | 0.00 | 0.335678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.313558E+10 | 0.00 | 0.00 | 0.00 | 0.634884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.354219E+10 | 0.00 | 0.00 | 0.00 | 0.840430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.216977E+10 | 0.00 | 0.00 | 0.00 | 0.296386E+10 | 12149142.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131130E+10 | 0.00 | 0.00 | 0.00 | 0.362468E+09 | 0.839214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107375E+10 | 0.00 | 0.00 | 0.00 | 88414663.88 | 0.579531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218834E+11 | 0.00 | 0.00 | 0.00 | 0.243918E+11 | 0.442307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.354219E+10 | 0.00 | 0.00 | 0.00 | 0.840430E+10 | 0.152522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.733837E+10 | 0.00 | 0.00 | 7795567.09 | 0.00 | 0.231683E+09 | 0.590107E+10 | 0.00 | 0.31 |
February | 0.475642E+10 | 0.00 | 0.00 | 14761775.56 | 0.00 | 0.00 | 0.878167E+10 | 0.00 | 0.37 |
March | 0.165531E+10 | 0.00 | 0.00 | 30068089.71 | 0.00 | 0.00 | 0.156456E+11 | 0.00 | 0.47 |
April | 0.721221E+09 | 12601179.18 | 0.00 | 34979892.43 | 989252.47 | 0.00 | 0.163876E+11 | 0.00 | 0.58 |
May | 0.938035E+09 | 8266456.60 | 0.00 | 44418814.03 | 0.00 | 0.00 | 0.208804E+11 | 0.00 | 0.90 |
June | 0.703304E+09 | 9197860.45 | 0.00 | 47425907.13 | 1332301.30 | 0.00 | 0.199216E+11 | 0.00 | 1.09 |
July | 0.531987E+09 | 0.143228E+09 | 0.00 | 42418100.61 | 17105605.66 | 0.00 | 0.141552E+11 | 0.00 | 1.04 |
August | 0.420217E+09 | 0.426339E+09 | 0.00 | 41746050.09 | 16504266.69 | 0.00 | 0.124251E+11 | 0.00 | 1.01 |
September | 0.780904E+09 | 7438768.97 | 0.00 | 44030584.70 | 0.00 | 0.00 | 0.182313E+11 | 0.00 | 1.00 |
October | 0.774640E+09 | 0.00 | 0.00 | 35913420.68 | 0.00 | 0.00 | 0.185615E+11 | 0.00 | 0.66 |
November | 0.306106E+10 | 0.00 | 0.00 | 20636313.71 | 0.00 | 0.00 | 0.124543E+11 | 0.00 | 0.43 |
December | 0.605910E+10 | 0.00 | 0.00 | 12911840.63 | 0.00 | 0.00 | 0.827834E+10 | 0.00 | 0.33 |
Annual Sum or Average | 0.277406E+11 | 0.607072E+09 | 0.00 | 0.377106E+09 | 35931426.11 | 0.231683E+09 | 0.171624E+12 | 0.00 | 0.68 |
Minimum of Months | 0.420217E+09 | 0.00 | 0.00 | 7795567.09 | 0.00 | 0.00 | 0.590107E+10 | 0.00 | 0.31 |
Maximum of Months | 0.733837E+10 | 0.426339E+09 | 0.00 | 47425907.13 | 17105605.66 | 0.231683E+09 | 0.208804E+11 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762921E+09 | 0.00 | 0.00 | 0.29 |
February | 0.100423E+11 | 0.00 | 0.00 | 335137.28 | 0.00 | 72911076.65 | 0.620548E+09 | 0.00 | 0.30 |
March | 0.826233E+10 | 0.00 | 0.00 | 3879016.58 | 0.00 | 2623502.25 | 0.402596E+10 | 0.00 | 0.34 |
April | 0.478347E+10 | 5026548.45 | 0.00 | 11190545.82 | 5701471.93 | 0.00 | 0.683191E+10 | 0.00 | 0.39 |
May | 0.250693E+10 | 4498066.52 | 0.00 | 21791129.37 | 0.00 | 0.00 | 0.114417E+11 | 0.00 | 0.58 |
June | 0.125762E+10 | 4723242.85 | 0.00 | 26925292.96 | 1269417.82 | 0.00 | 0.121293E+11 | 0.00 | 0.71 |
July | 0.107041E+10 | 99109123.52 | 0.00 | 25514501.62 | 9448795.79 | 0.00 | 0.871261E+10 | 0.00 | 0.69 |
August | 0.799034E+09 | 0.295457E+09 | 0.00 | 24851920.94 | 10217559.05 | 0.00 | 0.768741E+10 | 0.00 | 0.68 |
September | 0.186044E+10 | 4412326.20 | 0.00 | 22196244.04 | 0.00 | 0.00 | 0.990181E+10 | 0.00 | 0.63 |
October | 0.487282E+10 | 0.00 | 0.00 | 10275198.64 | 0.00 | 0.00 | 0.705337E+10 | 0.00 | 0.40 |
November | 0.930822E+10 | 0.00 | 0.00 | 1585886.71 | 0.00 | 16575840.55 | 0.165578E+10 | 0.00 | 0.31 |
December | 0.114510E+11 | 0.00 | 0.00 | 20964.24 | 0.00 | 0.257256E+09 | 0.110727E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.676287E+11 | 0.413226E+09 | 0.00 | 0.148566E+09 | 26637244.59 | 0.111229E+10 | 0.701712E+11 | 0.00 | 0.47 |
Minimum of Months | 0.799034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.114510E+11 | 0.295457E+09 | 0.00 | 26925292.96 | 10217559.05 | 0.762921E+09 | 0.121293E+11 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.908634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233170E+10 | 0.00 | 0.00 | 0.28 |
February | 0.903227E+10 | 0.00 | 0.00 | 107263.95 | 0.00 | 0.893382E+09 | 0.148797E+09 | 0.00 | 0.30 |
March | 0.985270E+10 | 0.00 | 0.00 | 1321139.56 | 0.00 | 83295661.36 | 0.157979E+10 | 0.00 | 0.33 |
April | 0.583985E+10 | 1208010.84 | 0.00 | 7521108.80 | 104741.01 | 4737767.07 | 0.512863E+10 | 0.00 | 0.38 |
May | 0.358632E+10 | 1207249.78 | 0.00 | 17859513.74 | 0.00 | 0.00 | 0.972750E+10 | 0.00 | 0.55 |
June | 0.200083E+10 | 1565490.85 | 0.00 | 23260004.91 | 761225.74 | 0.00 | 0.109769E+11 | 0.00 | 0.70 |
July | 0.163843E+10 | 81118494.27 | 0.00 | 22193671.94 | 12503884.98 | 0.00 | 0.789922E+10 | 0.00 | 0.70 |
August | 0.123742E+10 | 0.225363E+09 | 0.00 | 21491454.43 | 26679533.74 | 0.00 | 0.638617E+10 | 0.00 | 0.66 |
September | 0.298997E+10 | 963851.74 | 0.00 | 16065174.52 | 0.00 | 0.00 | 0.746358E+10 | 0.00 | 0.58 |
October | 0.665676E+10 | 0.00 | 0.00 | 4823750.15 | 0.00 | 4263341.38 | 0.378107E+10 | 0.00 | 0.37 |
November | 0.923985E+10 | 0.00 | 0.00 | 162057.51 | 0.00 | 0.338066E+09 | 0.433314E+09 | 0.00 | 0.30 |
December | 0.941436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147647E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.705751E+11 | 0.311426E+09 | 0.00 | 0.114805E+09 | 40049385.47 | 0.513191E+10 | 0.535250E+11 | 0.00 | 0.45 |
Minimum of Months | 0.123742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.985270E+10 | 0.225363E+09 | 0.00 | 23260004.91 | 26679533.74 | 0.233170E+10 | 0.109769E+11 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.462630E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203781E+10 | 0.00 | 0.00 | 0.29 |
February | 0.865619E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130564E+10 | 0.00 | 0.00 | 0.30 |
March | 0.199208E+10 | 0.00 | 0.00 | 10302.28 | 0.00 | 0.409564E+09 | 25271428.43 | 0.00 | 0.33 |
April | 0.153494E+10 | 340904.03 | 0.00 | 1008672.04 | 22053.72 | 0.111216E+09 | 0.607038E+09 | 0.00 | 0.38 |
May | 0.107977E+10 | 554376.36 | 0.00 | 3582084.64 | 0.00 | 5536273.17 | 0.181644E+10 | 0.00 | 0.60 |
June | 0.607411E+09 | 476749.51 | 0.00 | 5317890.45 | 160279.72 | 0.00 | 0.232545E+10 | 0.00 | 0.80 |
July | 0.433308E+09 | 25211562.59 | 0.00 | 5473506.60 | 2632752.83 | 0.00 | 0.183425E+10 | 0.00 | 0.84 |
August | 0.407702E+09 | 68691598.11 | 0.00 | 4656479.48 | 5483925.05 | 0.00 | 0.126318E+10 | 0.00 | 0.74 |
September | 0.101440E+10 | 261881.82 | 0.00 | 2664051.95 | 0.00 | 757899.20 | 0.110075E+10 | 0.00 | 0.58 |
October | 0.169265E+10 | 0.00 | 0.00 | 323755.17 | 0.00 | 0.153992E+09 | 0.256644E+09 | 0.00 | 0.35 |
November | 0.110469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102694E+10 | 0.00 | 0.00 | 0.30 |
December | 0.535035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182911E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.117302E+11 | 95537072.42 | 0.00 | 23036742.63 | 8299011.32 | 0.688056E+10 | 0.922903E+10 | 0.00 | 0.48 |
Minimum of Months | 0.407702E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.199208E+10 | 68691598.11 | 0.00 | 5473506.60 | 5483925.05 | 0.203781E+10 | 0.232545E+10 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.427560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116514E+10 | 0.00 | 0.00 | 0.29 |
February | 0.661881E+09 | 0.00 | 0.00 | 4546.66 | 0.00 | 0.711139E+09 | 6023498.80 | 0.00 | 0.30 |
March | 0.110139E+10 | 0.00 | 0.00 | 547986.77 | 0.00 | 0.176170E+09 | 0.352738E+09 | 0.00 | 0.35 |
April | 0.698895E+09 | 311902.98 | 0.00 | 2765845.63 | 0.00 | 37257344.19 | 0.140357E+10 | 0.00 | 0.59 |
May | 0.505513E+09 | 505098.39 | 0.00 | 4745027.18 | 0.00 | 4068197.18 | 0.229131E+10 | 0.00 | 0.92 |
June | 0.258380E+09 | 334319.91 | 0.00 | 6999528.93 | 101789.61 | 0.00 | 0.303259E+10 | 0.00 | 1.34 |
July | 0.210992E+09 | 21821621.45 | 0.00 | 7152439.38 | 726210.19 | 0.00 | 0.213899E+10 | 0.00 | 1.34 |
August | 0.162976E+09 | 63811311.04 | 0.00 | 6794886.05 | 745707.48 | 0.00 | 0.165084E+10 | 0.00 | 1.30 |
September | 0.495942E+09 | 304705.08 | 0.00 | 4249420.36 | 0.00 | 491001.94 | 0.165641E+10 | 0.00 | 0.96 |
October | 0.856987E+09 | 0.00 | 0.00 | 1152346.24 | 0.00 | 79458570.42 | 0.692253E+09 | 0.00 | 0.44 |
November | 0.780770E+09 | 0.00 | 0.00 | 1598.77 | 0.00 | 0.571341E+09 | 4077436.49 | 0.00 | 0.30 |
December | 0.468456E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104367E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.662975E+10 | 87088958.86 | 0.00 | 34413625.97 | 1573707.28 | 0.378873E+10 | 0.132288E+11 | 0.00 | 0.70 |
Minimum of Months | 0.162976E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.110139E+10 | 63811311.04 | 0.00 | 7152439.38 | 745707.48 | 0.116514E+10 | 0.303259E+10 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.916804E+09 | 0.00 | 0.00 | 306985.94 | 0.00 | 0.145676E+10 | 0.208914E+09 | 0.00 | 0.30 |
February | 0.978309E+09 | 0.00 | 0.00 | 1846858.40 | 0.00 | 0.815676E+09 | 0.960982E+09 | 0.00 | 0.39 |
March | 0.144961E+10 | 0.00 | 0.00 | 4320776.45 | 0.00 | 0.267932E+09 | 0.219665E+10 | 0.00 | 0.54 |
April | 0.103402E+10 | 994014.11 | 0.00 | 5864176.29 | 0.00 | 96592953.94 | 0.289997E+10 | 0.00 | 0.73 |
May | 0.865755E+09 | 1055313.30 | 0.00 | 7835302.27 | 0.00 | 6858473.42 | 0.368985E+10 | 0.00 | 0.96 |
June | 0.573536E+09 | 611741.75 | 0.00 | 8345422.90 | 160647.08 | 0.00 | 0.349380E+10 | 0.00 | 1.12 |
July | 0.416109E+09 | 46166197.83 | 0.00 | 9030838.33 | 382959.48 | 0.00 | 0.276313E+10 | 0.00 | 1.23 |
August | 0.354509E+09 | 0.145462E+09 | 0.00 | 8560785.14 | 682918.32 | 0.00 | 0.206830E+10 | 0.00 | 1.19 |
September | 0.720734E+09 | 1460048.14 | 0.00 | 9767235.31 | 0.00 | 754130.41 | 0.350001E+10 | 0.00 | 1.31 |
October | 0.115273E+10 | 0.00 | 0.00 | 5176604.33 | 0.00 | 99495024.01 | 0.290102E+10 | 0.00 | 0.74 |
November | 0.120604E+10 | 0.00 | 0.00 | 1028613.51 | 0.00 | 0.749651E+09 | 0.406324E+09 | 0.00 | 0.36 |
December | 0.865429E+09 | 0.00 | 0.00 | 917540.25 | 0.00 | 0.127106E+10 | 0.483057E+09 | 0.00 | 0.32 |
Annual Sum or Average | 0.105336E+11 | 0.195749E+09 | 0.00 | 63001139.13 | 1226524.88 | 0.476478E+10 | 0.255720E+11 | 0.00 | 0.77 |
Minimum of Months | 0.354509E+09 | 0.00 | 0.00 | 306985.94 | 0.00 | 0.00 | 0.208914E+09 | 0.00 | 0.30 |
Maximum of Months | 0.144961E+10 | 0.145462E+09 | 0.00 | 9767235.31 | 682918.32 | 0.145676E+10 | 0.368985E+10 | 0.00 | 1.31 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.384152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120730E+10 | 0.00 | 0.00 | 0.29 |
February | 0.555368E+09 | 0.00 | 0.00 | 135958.65 | 0.00 | 0.751827E+09 | 99655289.57 | 0.00 | 0.31 |
March | 0.104958E+10 | 0.00 | 0.00 | 810636.58 | 0.00 | 0.244594E+09 | 0.496882E+09 | 0.00 | 0.39 |
April | 0.798913E+09 | 529266.62 | 0.00 | 2423982.79 | 0.00 | 70251297.39 | 0.121143E+10 | 0.00 | 0.60 |
May | 0.535586E+09 | 445330.02 | 0.00 | 5681183.54 | 0.00 | 4663642.51 | 0.227575E+10 | 0.00 | 1.01 |
June | 0.342258E+09 | 1202181.27 | 0.00 | 6004644.92 | 101239.03 | 0.00 | 0.223920E+10 | 0.00 | 1.23 |
July | 0.240211E+09 | 44651887.40 | 0.00 | 7472477.48 | 457297.09 | 0.00 | 0.194246E+10 | 0.00 | 1.45 |
August | 0.227823E+09 | 96105704.31 | 0.00 | 5579221.17 | 1482829.62 | 0.00 | 0.122314E+10 | 0.00 | 1.11 |
September | 0.494543E+09 | 512710.69 | 0.00 | 4455359.58 | 0.00 | 475249.42 | 0.154841E+10 | 0.00 | 1.02 |
October | 0.927593E+09 | 0.00 | 0.00 | 1091234.46 | 0.00 | 96533038.88 | 0.650493E+09 | 0.00 | 0.47 |
November | 0.697486E+09 | 0.00 | 0.00 | 58856.18 | 0.00 | 0.626417E+09 | 30042001.91 | 0.00 | 0.31 |
December | 0.419444E+09 | 0.00 | 0.00 | 2380.05 | 0.00 | 0.108028E+10 | 4736381.44 | 0.00 | 0.29 |
Annual Sum or Average | 0.667296E+10 | 0.143447E+09 | 0.00 | 33715935.40 | 2041365.74 | 0.408234E+10 | 0.117222E+11 | 0.00 | 0.71 |
Minimum of Months | 0.227823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.104958E+10 | 96105704.31 | 0.00 | 7472477.48 | 1482829.62 | 0.120730E+10 | 0.227575E+10 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.782009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187111E+10 | 0.00 | 0.00 | 0.29 |
February | 0.120148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106859E+10 | 0.00 | 0.00 | 0.29 |
March | 0.217525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183576E+09 | 0.00 | 0.00 | 0.30 |
April | 0.182364E+10 | 994786.27 | 0.00 | 212519.97 | 1158362.25 | 28916508.61 | 0.148386E+09 | 0.00 | 0.31 |
May | 0.123868E+10 | 1596760.34 | 0.00 | 2094607.36 | 0.00 | 0.00 | 0.109212E+10 | 0.00 | 0.48 |
June | 0.631340E+09 | 1322177.38 | 0.00 | 3969706.39 | 281403.74 | 0.00 | 0.171016E+10 | 0.00 | 0.64 |
July | 0.383434E+09 | 25486360.35 | 0.00 | 4485213.76 | 3612982.55 | 0.00 | 0.146224E+10 | 0.00 | 0.68 |
August | 0.387824E+09 | 74448574.33 | 0.00 | 3877138.85 | 3485969.97 | 0.00 | 0.113614E+10 | 0.00 | 0.63 |
September | 0.100373E+10 | 1088802.81 | 0.00 | 2370260.47 | 22350.28 | 0.00 | 0.100638E+10 | 0.00 | 0.53 |
October | 0.187456E+10 | 0.00 | 0.00 | 352351.23 | 0.00 | 3541569.15 | 0.275754E+09 | 0.00 | 0.34 |
November | 0.179753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439695E+09 | 0.00 | 0.00 | 0.29 |
December | 0.111566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138882E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.144151E+11 | 0.104937E+09 | 0.00 | 17361798.03 | 8561068.79 | 0.498425E+10 | 0.683118E+10 | 0.00 | 0.42 |
Minimum of Months | 0.383434E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.217525E+10 | 74448574.33 | 0.00 | 4485213.76 | 3612982.55 | 0.187111E+10 | 0.171016E+10 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.616418E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107055E+10 | 0.00 | 0.00 | 0.29 |
February | 0.927660E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508252E+09 | 0.00 | 0.00 | 0.29 |
March | 0.128527E+10 | 0.00 | 0.00 | 296729.58 | 0.00 | 55665099.75 | 0.182249E+09 | 0.00 | 0.31 |
April | 0.760319E+09 | 1310424.88 | 0.00 | 2124729.32 | 731014.78 | 5529428.48 | 0.940566E+09 | 0.00 | 0.46 |
May | 0.525134E+09 | 1837201.89 | 0.00 | 3771896.67 | 0.00 | 0.00 | 0.172519E+10 | 0.00 | 0.76 |
June | 0.232435E+09 | 1178714.92 | 0.00 | 6123338.22 | 177587.18 | 0.00 | 0.251752E+10 | 0.00 | 1.17 |
July | 0.148149E+09 | 28298879.58 | 0.00 | 6092475.01 | 2094492.18 | 0.00 | 0.182884E+10 | 0.00 | 1.15 |
August | 0.131585E+09 | 81533267.69 | 0.00 | 6017343.68 | 1123237.04 | 0.00 | 0.158482E+10 | 0.00 | 1.16 |
September | 0.424328E+09 | 1393859.23 | 0.00 | 4242364.84 | 0.00 | 0.00 | 0.162494E+10 | 0.00 | 0.91 |
October | 0.916974E+09 | 0.00 | 0.00 | 1427257.53 | 0.00 | 879876.92 | 0.776866E+09 | 0.00 | 0.44 |
November | 0.117061E+10 | 0.00 | 0.00 | 7194.73 | 0.00 | 0.236279E+09 | 7409449.26 | 0.00 | 0.29 |
December | 0.804830E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.783213E+09 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.794372E+10 | 0.115552E+09 | 0.00 | 30103329.59 | 4126331.19 | 0.266037E+10 | 0.111884E+11 | 0.00 | 0.63 |
Minimum of Months | 0.131585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.128527E+10 | 81533267.69 | 0.00 | 6123338.22 | 2094492.18 | 0.107055E+10 | 0.251752E+10 | 0.00 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.603239E+09 | 0.00 | 0.00 | 16886.77 | 0.00 | 0.312886E+10 | 20940169.16 | 0.00 | 0.40 |
February | 0.105812E+10 | 0.00 | 0.00 | 276885.70 | 0.00 | 0.180024E+10 | 0.176094E+09 | 0.00 | 0.39 |
March | 0.160966E+10 | 0.00 | 0.00 | 1041148.39 | 0.00 | 0.100341E+10 | 0.563323E+09 | 0.00 | 0.41 |
April | 0.133956E+10 | 6725387.06 | 0.00 | 1764026.56 | 0.00 | 0.541606E+09 | 0.775891E+09 | 0.00 | 0.47 |
May | 0.131679E+10 | 3550842.72 | 0.00 | 2936039.40 | 0.00 | 0.280923E+09 | 0.123976E+10 | 0.00 | 0.64 |
June | 0.939760E+09 | 2052337.15 | 0.00 | 3999801.02 | 281325.39 | 0.140087E+09 | 0.145153E+10 | 0.00 | 0.75 |
July | 0.497035E+09 | 54918082.88 | 0.00 | 5563134.27 | 3272985.23 | 45689257.96 | 0.155780E+10 | 0.00 | 0.89 |
August | 0.478425E+09 | 0.180094E+09 | 0.00 | 5748735.76 | 1467734.53 | 39473026.15 | 0.131232E+10 | 0.00 | 0.93 |
September | 0.831484E+09 | 5904243.21 | 0.00 | 6859407.51 | 0.00 | 0.127921E+09 | 0.216673E+10 | 0.00 | 1.05 |
October | 0.129463E+10 | 0.00 | 0.00 | 3148286.64 | 0.00 | 0.411235E+09 | 0.171702E+10 | 0.00 | 0.60 |
November | 0.134188E+10 | 0.00 | 0.00 | 344317.60 | 0.00 | 0.150399E+10 | 99815130.98 | 0.00 | 0.39 |
December | 0.839353E+09 | 0.00 | 0.00 | 210926.44 | 0.00 | 0.255886E+10 | 0.147066E+09 | 0.00 | 0.38 |
Annual Sum or Average | 0.121499E+11 | 0.253245E+09 | 0.00 | 31909596.06 | 5022045.15 | 0.115823E+11 | 0.112283E+11 | 0.00 | 0.61 |
Minimum of Months | 0.478425E+09 | 0.00 | 0.00 | 16886.77 | 0.00 | 39473026.15 | 20940169.16 | 0.00 | 0.38 |
Maximum of Months | 0.160966E+10 | 0.180094E+09 | 0.00 | 6859407.51 | 3272985.23 | 0.312886E+10 | 0.216673E+10 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.568573E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112628E+10 | 0.00 | 0.00 | 0.29 |
February | 0.895939E+09 | 0.00 | 0.00 | 51936.19 | 0.00 | 0.510800E+09 | 42812068.97 | 0.00 | 0.30 |
March | 0.128570E+10 | 0.00 | 0.00 | 390692.24 | 0.00 | 90723427.93 | 0.199147E+09 | 0.00 | 0.33 |
April | 0.898974E+09 | 2389195.96 | 0.00 | 1523542.24 | 281400.51 | 11930524.34 | 0.643886E+09 | 0.00 | 0.43 |
May | 0.495639E+09 | 1662154.04 | 0.00 | 4296438.49 | 0.00 | 0.00 | 0.169750E+10 | 0.00 | 0.81 |
June | 0.274419E+09 | 3427123.76 | 0.00 | 5092357.07 | 178402.61 | 0.00 | 0.185328E+10 | 0.00 | 1.03 |
July | 0.148334E+09 | 48125758.86 | 0.00 | 5884556.68 | 449826.73 | 0.00 | 0.173256E+10 | 0.00 | 1.24 |
August | 0.161563E+09 | 0.104279E+09 | 0.00 | 5108291.74 | 1623334.31 | 0.00 | 0.123937E+10 | 0.00 | 1.01 |
September | 0.388395E+09 | 2003027.52 | 0.00 | 4317733.95 | 0.00 | 0.00 | 0.150748E+10 | 0.00 | 0.93 |
October | 0.989603E+09 | 0.00 | 0.00 | 1183980.97 | 0.00 | 711244.74 | 0.658248E+09 | 0.00 | 0.45 |
November | 0.114730E+10 | 0.00 | 0.00 | 44506.35 | 0.00 | 0.245620E+09 | 29376332.03 | 0.00 | 0.29 |
December | 0.800421E+09 | 0.00 | 0.00 | 310.09 | 0.00 | 0.793153E+09 | 1843229.06 | 0.00 | 0.27 |
Annual Sum or Average | 0.805486E+10 | 0.161886E+09 | 0.00 | 27894346.01 | 2532964.17 | 0.277922E+10 | 0.960550E+10 | 0.00 | 0.62 |
Minimum of Months | 0.148334E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.128570E+10 | 0.104279E+09 | 0.00 | 5884556.68 | 1623334.31 | 0.112628E+10 | 0.185328E+10 | 0.00 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.934725E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166339E+10 | 0.00 | 0.00 | 0.29 |
February | 0.145135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824949E+09 | 0.00 | 0.00 | 0.30 |
March | 0.237589E+10 | 0.00 | 0.00 | 23256.28 | 0.00 | 0.117933E+09 | 66052155.32 | 0.00 | 0.33 |
April | 0.157305E+10 | 1433350.76 | 0.00 | 1233393.17 | 1202561.81 | 19388498.53 | 0.730739E+09 | 0.00 | 0.38 |
May | 0.940056E+09 | 1940426.98 | 0.00 | 4130583.00 | 0.00 | 0.00 | 0.199890E+10 | 0.00 | 0.62 |
June | 0.467496E+09 | 1503824.77 | 0.00 | 5932869.21 | 267747.24 | 0.00 | 0.248962E+10 | 0.00 | 0.80 |
July | 0.326268E+09 | 31720935.18 | 0.00 | 5859219.90 | 1992952.19 | 0.00 | 0.192162E+10 | 0.00 | 0.83 |
August | 0.321069E+09 | 90959139.76 | 0.00 | 5025669.55 | 2155100.73 | 0.00 | 0.146589E+10 | 0.00 | 0.74 |
September | 0.888304E+09 | 1145173.50 | 0.00 | 3321742.77 | 0.00 | 0.00 | 0.136337E+10 | 0.00 | 0.61 |
October | 0.182055E+10 | 0.00 | 0.00 | 599016.28 | 0.00 | 18636438.48 | 0.436558E+09 | 0.00 | 0.36 |
November | 0.178053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529152E+09 | 0.00 | 0.00 | 0.30 |
December | 0.114197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137176E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.140213E+11 | 0.128703E+09 | 0.00 | 26125750.15 | 5618361.97 | 0.454521E+10 | 0.104728E+11 | 0.00 | 0.49 |
Minimum of Months | 0.321069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.237589E+10 | 90959139.76 | 0.00 | 5932869.21 | 2155100.73 | 0.166339E+10 | 0.248962E+10 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.505941E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.865424E+09 | 0.00 | 0.00 | 0.24 |
February | 0.756322E+09 | 0.00 | 0.00 | 28988.18 | 0.00 | 0.397418E+09 | 34284083.47 | 0.00 | 0.25 |
March | 0.103555E+10 | 0.00 | 0.00 | 832546.16 | 0.00 | 38091620.61 | 0.467626E+09 | 0.00 | 0.31 |
April | 0.614841E+09 | 1816402.81 | 0.00 | 2941518.93 | 18636.28 | 7407388.07 | 0.144786E+10 | 0.00 | 0.55 |
May | 0.445438E+09 | 1653994.73 | 0.00 | 4782511.26 | 0.00 | 0.00 | 0.217154E+10 | 0.00 | 0.87 |
June | 0.221385E+09 | 1043008.25 | 0.00 | 6971323.02 | 168806.18 | 0.00 | 0.286443E+10 | 0.00 | 1.26 |
July | 0.152746E+09 | 26395186.25 | 0.00 | 7051119.30 | 1122463.82 | 0.00 | 0.204547E+10 | 0.00 | 1.24 |
August | 0.136463E+09 | 77054946.00 | 0.00 | 6600699.61 | 538104.18 | 0.00 | 0.170335E+10 | 0.00 | 1.22 |
September | 0.394836E+09 | 1017135.52 | 0.00 | 4483197.88 | 456.09 | 0.00 | 0.172308E+10 | 0.00 | 0.92 |
October | 0.803251E+09 | 0.00 | 0.00 | 1470094.98 | 0.00 | 11388747.45 | 0.806823E+09 | 0.00 | 0.42 |
November | 0.897453E+09 | 0.00 | 0.00 | 33660.34 | 0.00 | 0.289676E+09 | 21889429.84 | 0.00 | 0.25 |
December | 0.620836E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710050E+09 | 0.00 | 0.00 | 0.23 |
Annual Sum or Average | 0.658506E+10 | 0.108981E+09 | 0.00 | 35195659.66 | 1848466.55 | 0.231946E+10 | 0.132863E+11 | 0.00 | 0.65 |
Minimum of Months | 0.136463E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
Maximum of Months | 0.103555E+10 | 77054946.00 | 0.00 | 7051119.30 | 1122463.82 | 0.865424E+09 | 0.286443E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128440E+10 | 0.00 | 0.00 | 501774.72 | 0.00 | 0.111859E+10 | 0.319922E+09 | 0.00 | 0.30 |
February | 0.139385E+10 | 0.00 | 0.00 | 2288526.22 | 0.00 | 0.471659E+09 | 0.112871E+10 | 0.00 | 0.41 |
March | 0.168054E+10 | 0.00 | 0.00 | 5109986.08 | 0.00 | 68960817.51 | 0.246840E+10 | 0.00 | 0.57 |
April | 0.107015E+10 | 9035389.46 | 0.00 | 6239877.36 | 1275.01 | 13013173.18 | 0.297524E+10 | 0.00 | 0.73 |
May | 0.781032E+09 | 3655931.54 | 0.00 | 8258210.73 | 0.00 | 0.00 | 0.365520E+10 | 0.00 | 0.98 |
June | 0.491741E+09 | 1889028.63 | 0.00 | 8718101.49 | 266446.10 | 0.00 | 0.343404E+10 | 0.00 | 1.11 |
July | 0.351962E+09 | 54881059.43 | 0.00 | 8761705.13 | 1663443.82 | 0.00 | 0.262727E+10 | 0.00 | 1.19 |
August | 0.286234E+09 | 0.179319E+09 | 0.00 | 8417808.50 | 722115.55 | 0.00 | 0.215221E+10 | 0.00 | 1.14 |
September | 0.616943E+09 | 6019116.91 | 0.00 | 10316456.69 | 0.00 | 0.00 | 0.357287E+10 | 0.00 | 1.33 |
October | 0.121683E+10 | 0.00 | 0.00 | 6150906.91 | 0.00 | 7949567.39 | 0.324099E+10 | 0.00 | 0.79 |
November | 0.171661E+10 | 0.00 | 0.00 | 1398174.59 | 0.00 | 0.323541E+09 | 0.577968E+09 | 0.00 | 0.37 |
December | 0.135823E+10 | 0.00 | 0.00 | 1276055.51 | 0.00 | 0.868737E+09 | 0.660485E+09 | 0.00 | 0.33 |
Annual Sum or Average | 0.122485E+11 | 0.254799E+09 | 0.00 | 67437583.93 | 2653280.49 | 0.287245E+10 | 0.268133E+11 | 0.00 | 0.77 |
Minimum of Months | 0.286234E+09 | 0.00 | 0.00 | 501774.72 | 0.00 | 0.00 | 0.319922E+09 | 0.00 | 0.30 |
Maximum of Months | 0.171661E+10 | 0.179319E+09 | 0.00 | 10316456.69 | 1663443.82 | 0.111859E+10 | 0.365520E+10 | 0.00 | 1.33 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.659208E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.990490E+09 | 0.00 | 0.00 | 0.29 |
February | 0.913569E+09 | 0.00 | 0.00 | 175547.63 | 0.00 | 0.442797E+09 | 0.127396E+09 | 0.00 | 0.32 |
March | 0.127550E+10 | 0.00 | 0.00 | 965406.68 | 0.00 | 71159049.23 | 0.554774E+09 | 0.00 | 0.40 |
April | 0.817482E+09 | 4004751.34 | 0.00 | 2571533.07 | 164544.58 | 14111857.97 | 0.124290E+10 | 0.00 | 0.59 |
May | 0.473982E+09 | 1677144.72 | 0.00 | 5973504.89 | 0.00 | 0.00 | 0.225228E+10 | 0.00 | 1.02 |
June | 0.273814E+09 | 3905470.05 | 0.00 | 6292926.11 | 168958.94 | 0.00 | 0.222953E+10 | 0.00 | 1.20 |
July | 0.198087E+09 | 53706741.69 | 0.00 | 6700811.02 | 270738.18 | 0.00 | 0.184963E+10 | 0.00 | 1.38 |
August | 0.180199E+09 | 0.122260E+09 | 0.00 | 5544860.52 | 1152270.90 | 0.00 | 0.129975E+10 | 0.00 | 1.08 |
September | 0.427762E+09 | 2161685.74 | 0.00 | 4847257.52 | 0.00 | 0.00 | 0.164269E+10 | 0.00 | 1.04 |
October | 0.997181E+09 | 0.00 | 0.00 | 1370699.47 | 0.00 | 13746357.05 | 0.789174E+09 | 0.00 | 0.49 |
November | 0.109952E+10 | 0.00 | 0.00 | 94685.64 | 0.00 | 0.315889E+09 | 53696732.09 | 0.00 | 0.31 |
December | 0.795635E+09 | 0.00 | 0.00 | 11386.22 | 0.00 | 0.782508E+09 | 16615547.52 | 0.00 | 0.28 |
Annual Sum or Average | 0.811194E+10 | 0.187716E+09 | 0.00 | 34548618.76 | 1756512.60 | 0.263070E+10 | 0.120584E+11 | 0.00 | 0.70 |
Minimum of Months | 0.180199E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.127550E+10 | 0.122260E+09 | 0.00 | 6700811.02 | 1152270.90 | 0.990490E+09 | 0.225228E+10 | 0.00 | 1.38 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:05
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.638922E+11 | 0.152736E+11 | 0.00 | 0.134748E+12 | 0.588525E+10 |
February | 0.125608E+12 | 0.137994E+11 | 0.00 | 0.145184E+12 | 0.462939E+10 |
March | 0.219879E+12 | 0.138660E+11 | 0.00 | 0.187552E+12 | 0.477430E+10 |
April | 0.338923E+12 | 0.125378E+11 | 0.00 | 0.211203E+12 | 0.156652E+11 |
May | 0.441551E+12 | 0.102493E+11 | 0.00 | 0.232604E+12 | 0.275279E+11 |
June | 0.443314E+12 | 0.815357E+10 | 0.00 | 0.218897E+12 | 0.504230E+11 |
July | 0.469473E+12 | 0.618143E+10 | 0.00 | 0.216765E+12 | 0.962286E+11 |
August | 0.369737E+12 | 0.477353E+10 | 0.00 | 0.171065E+12 | 0.128645E+12 |
September | 0.264699E+12 | 0.539365E+10 | 0.00 | 0.226160E+12 | 0.471167E+11 |
October | 0.169829E+12 | 0.111501E+11 | 0.00 | 0.218880E+12 | 0.735507E+10 |
November | 0.721395E+11 | 0.128321E+11 | 0.00 | 0.173430E+12 | 0.420540E+10 |
December | 0.498250E+11 | 0.136738E+11 | 0.00 | 0.151130E+12 | 0.498282E+10 |
Annual Sum or Average | 0.302887E+13 | 0.127884E+12 | 0.00 | 0.228762E+13 | 0.397438E+12 |
Minimum of Months | 0.498250E+11 | 0.477353E+10 | 0.00 | 0.134748E+12 | 0.420540E+10 |
Maximum of Months | 0.469473E+12 | 0.152736E+11 | 0.00 | 0.232604E+12 | 0.128645E+12 |