Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2023-10-16 08:32:04
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1715.74 | 344.37 | 344.37 |
Net Site Energy | 1715.74 | 344.37 | 344.37 |
Total Source Energy | 5176.09 | 1038.92 | 1038.92 |
Net Source Energy | 5176.09 | 1038.92 | 1038.92 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 7.23 | 6.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 440.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 231.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 144.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 117.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1592.05 | 123.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 7.23 | 6.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 440.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 231.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 50.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 144.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 117.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 7.23 | 6.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 440.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 231.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 50.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 144.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 117.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 118.86 | 24.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 319.55 | 24.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 118.86 | 24.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 319.55 | 24.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1592.045 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1592.045 | 100.00 |
Total On-Site and Utility Electric Sources | 1592.045 | 100.00 |
Total Electricity End Uses | 1592.045 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 73.67 |
Time Setpoint Not Met During Occupied Cooling | 518.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 917.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.6636 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.6636 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.6636 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 6.6636 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.6636 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-14:00 | 06-DEC-07:30 | - | - | - | - | - | - | - | - | - | - | 01-FEB-12:09 |
Heating | 0.00 | 31362.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 92791.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 40588.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 831.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25855.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8779.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 179744.45 | 40141.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 31362.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 92791.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 6054.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 46.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 831.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 25855.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8779.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 22.89 | 7.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1394.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 734.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 161.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 37.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 457.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 127.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5042.01 | 134.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 4.59 | 1.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 279.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 91.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 25.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1012.01 | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 4.59 | 1.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 279.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 91.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 25.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1012.01 | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.05 | 0.245460 | 0.209000 | 0.638132 | 0.654561 | 0.500000 | 0.001552 |
CORE_MID VAV BOX COMPONENT | 2.25 | 0.332462 | 0.283000 | 0.637955 | 0.886564 | 0.500000 | 0.001146 |
CORE_TOP VAV BOX COMPONENT | 2.49 | 0.301357 | 0.256000 | 0.636656 | 0.803617 | 0.500000 | 0.001264 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.885062 | 0.178509 | 0.152000 | 0.134529 | 0.476024 | 0.500000 | 0.002134 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.784344 | 0.127523 | 0.108000 | 0.084709 | 0.340061 | 0.500000 | 0.002988 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.977606 | 0.161611 | 0.137000 | 0.133932 | 0.430962 | 0.500000 | 0.002358 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.893482 | 0.111939 | 0.095000 | 0.084881 | 0.300000 | 0.500000 | 0.003404 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.726337 | 0.217518 | 0.185000 | 0.134372 | 0.580049 | 0.500000 | 0.001752 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.686398 | 0.145720 | 0.124000 | 0.085113 | 0.388586 | 0.500000 | 0.002615 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.809007 | 0.195291 | 0.166000 | 0.134295 | 0.520776 | 0.500000 | 0.001951 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.727203 | 0.137534 | 0.117000 | 0.085083 | 0.366758 | 0.500000 | 0.002770 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.758280 | 0.208355 | 0.177000 | 0.134216 | 0.555614 | 0.500000 | 0.001829 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.746136 | 0.357475 | 0.500000 | 0.002842 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.851079 | 0.185637 | 0.158000 | 0.134470 | 0.495032 | 0.500000 | 0.002052 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.801894 | 0.124724 | 0.106000 | 0.085001 | 0.332597 | 0.500000 | 0.003055 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 19348.80 |
CORE_MID VAV BOX REHEAT COIL | 19343.45 |
CORE_TOP VAV BOX REHEAT COIL | 29773.72 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 13105.60 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 8602.46 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 13150.97 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 8565.17 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 8441.81 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5637.47 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8501.41 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5598.03 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 10052.15 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 6671.82 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 10098.33 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 6633.10 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.00 | 1.08 | 6.00 | 1.35 | 5.52 | 5.52 | 0.300000 | 0.245419 | 5.52 |
PACU_VAV_MID | 2.71 | 1.08 | 5.41 | 1.65 | 4.85 | 4.85 | 0.300000 | 0.340151 | 4.85 |
PACU_VAV_TOP | 3.01 | 1.07 | 6.03 | 2.41 | 5.76 | 5.76 | 0.300000 | 0.419134 | 5.76 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.52 |
PACU_VAV_MID_OA_CONTROLLER | 4.85 |
PACU_VAV_TOP_OA_CONTROLLER | 5.76 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.52 | 105022.57 | 0.796722 | 1.84 | 35004.02 | 0.796722 |
PACU_VAV_MID COOLING COIL | 4.85 | 94601.88 | 0.785786 | 1.62 | 31530.81 | 0.785786 |
PACU_VAV_TOP COOLING COIL | 5.76 | 108259.98 | 0.800792 | 1.92 | 36083.05 | 0.800792 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 7295.56 |
PACU_VAV_MID HEATING COIL | 9396.57 |
PACU_VAV_TOP HEATING COIL | 8883.82 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.52 |
PACU_VAV_MID FAN | 4.85 |
PACU_VAV_TOP FAN | 5.76 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 31.498 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 1.015 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 1.000 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.258 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7516 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7656 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5610 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27848788E-12 | 0.13637022E-14 | -0.81023097E-13 | 0.79216012E-16 |
43 | 6 | 0.25824895E-07 | 0.27625343E-09 | 0.59397345E-08 | -0.11998209E-12 |
44 | 5 | -0.17554640E-03 | 0.24097886E-05 | -0.90470599E-04 | 0.58795774E-08 |
45 | 4 | 0.27494803 | 0.11927753E-02 | 0.93505830E-01 | -0.31160983E-04 |
46 | 3 | -6.9253412 | 0.37505722E-01 | -2.2377579 | 0.27339040E-01 |
47 | 2 | 39.746130 | 0.13507978 | 14.849253 | -0.32081291 |
48 | 1 | -79.683230 | 0.61641880E-01 | -28.768593 | 1.0602386 |
49 | 0 | 46.824344 | 0.12537427E-02 | 16.300359 | |
50 | 7 | -0.27402251E-12 | 0.13062726E-14 | -0.81664977E-13 | 0.79643054E-16 |
51 | 6 | 0.25995733E-07 | 0.27297844E-09 | 0.59774430E-08 | -0.12089174E-12 |
52 | 5 | -0.17642699E-03 | 0.23783059E-05 | -0.90913883E-04 | 0.59164366E-08 |
53 | 4 | 0.27599802 | 0.11759213E-02 | 0.93882490E-01 | -0.31307097E-04 |
54 | 3 | -6.9461820 | 0.36940511E-01 | -2.2439388 | 0.27441040E-01 |
55 | 2 | 39.814917 | 0.13293308 | 14.874721 | -0.32157873 |
56 | 1 | -79.735998 | 0.60618496E-01 | -28.791459 | 1.0613631 |
57 | 0 | 46.824344 | 0.12320537E-02 | 16.299787 | |
58 | 7 | -0.27749376E-12 | 0.16893975E-14 | -0.84125370E-13 | 0.18079425E-15 |
59 | 6 | 0.22886636E-07 | 0.32835403E-09 | 0.52910653E-08 | -0.10444131E-12 |
60 | 5 | -0.16025164E-03 | 0.29299438E-05 | -0.82748939E-04 | 0.52444335E-08 |
61 | 4 | 0.25649379 | 0.14793778E-02 | 0.86896489E-01 | -0.28615133E-04 |
62 | 3 | -6.5585231 | 0.47340314E-01 | -2.1290029 | 0.25545250E-01 |
63 | 2 | 38.534810 | 0.17312159 | 14.399826 | -0.30733026 |
64 | 1 | -78.753333 | 0.80044855E-01 | -28.364722 | 1.0404251 |
65 | 0 | 46.824351 | 0.16491755E-02 | 16.310723 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.455_SHGC_EAST_0.249 | 35 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 | ||
2 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 36 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 | ||
3 | WINDOW_U_0.455_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 | ||
4 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 38 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2186E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2606E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7931E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8285E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3995E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4281E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9048E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9212E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1048 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8423E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1175 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2927E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7888E-002 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1278E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1945E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1958E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2195E-003 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2673E-003 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7940E-003 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8359E-003 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4006E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4335E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9047E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9210E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8657E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7860E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5716E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5619E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7283E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3599E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7535E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7678E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4170E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4334E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1818E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1937E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0144E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0186E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3903E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3960E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9463E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9836E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4776E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5074E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1650E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1866E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9047E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9210E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7416E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5589E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1206E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1920E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9462E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.2358E-003 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1945E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1958E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9461E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9836E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4772E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5064E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1640E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1829E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9048E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9212E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2175E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4845E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7792E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1926E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1412E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0911E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7535E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7679E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0026E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.0421E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6720E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7134E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6553E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.6742E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3905E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3961E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1052 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.9617E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1160 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.4964E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.3118E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.0034E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6447E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.6997E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.7100E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.6962E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.4338E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4823E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.6189E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2944E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6836E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7257E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1418E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0515E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4781E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6181E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3021E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2145E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6447E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6997E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.0817E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.4087E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6660E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1302E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.0489E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.0375E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6836E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7257E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1052 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.9610E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1160 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.4957E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.3113E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.0029E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6443E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.6995E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.7099E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.6960E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.4337E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4821E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.6186E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2942E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6832E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7255E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1419E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0514E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4781E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6180E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3020E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2144E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6443E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6995E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.0817E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.4086E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6659E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1301E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.0487E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.0372E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6833E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7255E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 38462.49722 | 38462.49722 | 3.05326 | 3.05326 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 4644.48544 | 4644.48544 | 0.21618 | 0.42469 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 28428.57061 | 28428.57061 | 2.25426 | 2.25426 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 11713.00605 | 11713.00605 | 0.54516 | 0.54516 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 31074.36148 | 31074.36148 | 2.48694 | 2.48694 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 40.26800 | 5.63027E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 20987.36477 | 20987.36477 | 0.98195 | 0.98195 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 11059.61976 | 11059.61976 | 0.88506 | 0.88506 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 40.53400 | 5.63070E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 9208.25593 | 9208.25593 | 0.43223 | 0.43223 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9801.11961 | 9801.11961 | 0.78434 | 0.78434 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 36.41100 | 5.62429E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 6043.59066 | 6043.59066 | 0.28371 | 0.28371 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 12216.04335 | 12216.04335 | 0.97761 | 0.97761 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 40.80000 | 5.63111E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 9240.02964 | 9240.02964 | 0.43372 | 0.43372 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11164.89840 | 11164.89840 | 0.89348 | 0.89348 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 6017.47528 | 6017.47528 | 0.28248 | 0.28248 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 9075.98082 | 9075.98082 | 0.72634 | 0.72634 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 5940.10419 | 5940.10419 | 0.27841 | 0.27841 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8576.97131 | 8576.97131 | 0.68640 | 0.68640 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 36.41100 | 5.62429E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 3965.99417 | 3965.99417 | 0.18593 | 0.18593 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10108.99903 | 10108.99903 | 0.80901 | 0.80901 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 40.80000 | 5.63111E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 5981.86050 | 5981.86050 | 0.28038 | 0.28038 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9086.85418 | 9086.85418 | 0.72720 | 0.72720 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 38.71633 | 5.62786E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 3938.35716 | 3938.35716 | 0.18463 | 0.18463 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 9475.27693 | 9475.27693 | 0.75828 | 0.75828 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 7069.34476 | 7069.34476 | 0.33152 | 0.33152 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9323.59177 | 9323.59177 | 0.74614 | 0.74614 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 35.74600 | 5.62327E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 4691.19908 | 4691.19908 | 0.22004 | 0.22004 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 10634.88157 | 10634.88157 | 0.85108 | 0.85108 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 40.80000 | 5.63111E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 7101.68801 | 7101.68801 | 0.33305 | 0.33305 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10020.33165 | 10020.33165 | 0.80189 | 0.80189 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 4664.08045 | 4664.08045 | 0.21876 | 0.21876 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 85378.22 | 5.51725 | 5.51725 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 12852.18 | 1.35404 | 1.35404 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 76891.78 | 4.84647 | 4.84647 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 12841.28 | 1.64853 | 1.64853 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 87974.21 | 5.75973 | 5.75973 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 12710.00 | 2.41410 | 2.41410 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.05326 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24546 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20900 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63813 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65456 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.55219E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19348.80020 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.25426 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33246 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28300 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63796 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88656 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14600E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19343.44959 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.48694 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30136 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25600 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63666 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80362 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.26428E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 29773.72278 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88506 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17851 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15200 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13453 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47602 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.13434E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13105.60171 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78434 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12752 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10800 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47092E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34006 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.98770E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8602.45845 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.97761 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16161 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13700 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13393 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43096 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.35752E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13150.97421 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.89348 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11194 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.50000E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48808E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.40365E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8565.16857 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72634 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21752 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18500 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13437 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58005 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.75158E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8441.81346 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68640 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14572 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12400 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51133E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38859 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.61461E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5637.46509 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80901 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19529 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16600 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13430 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52078 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.95094E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8501.40859 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72720 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13753 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11700 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50827E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36676 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.77022E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5598.03242 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75828 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20836 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17700 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13422 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55561 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.82861E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10052.14684 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74614 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35747 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.84216E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6671.81954 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85108 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18564 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15800 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13447 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49503 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.05239E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10098.33128 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80189 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12472 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10600 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50008E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33260 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.05475E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6633.09831 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.00110 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07700 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.00221 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.35404 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.51725 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.51725 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.24542 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.70582 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07670 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.41165 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.64853 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.84647 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.84647 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.34015 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.01372 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07471 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.02743 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.41410 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.75973 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.75973 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.41913 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.51725 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.84647 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.75973 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.51725 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.51725 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 105022.57182 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.79672 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.83890 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35004.02319 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.79672 |
152 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 7295.55695 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.51725 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.84647 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.84647 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 94601.88013 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.78579 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.61533 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31530.80665 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.78579 |
161 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 9396.56807 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.84647 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.75973 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.75973 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 108259.98451 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80079 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.91972 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 36083.05284 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80079 |
170 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 8883.82137 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.75973 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 103855.04 | 354368.10 | 11.30 | 2.86 | 3.23 | 3.40 | 3.58 | 9.77 | 11.04 | 11.61 | 12.23 | 5.7932 | 4.6370 | 3.1243 | 1.2402 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 93645.58 | 319531.97 | 11.35 | 2.87 | 3.25 | 3.42 | 3.59 | 9.81 | 11.09 | 11.68 | 12.26 | 5.0889 | 4.0662 | 2.7385 | 1.0998 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 107000.47 | 365100.75 | 11.27 | 2.86 | 3.23 | 3.40 | 3.58 | 9.75 | 11.01 | 11.59 | 12.21 | 6.0478 | 4.8370 | 3.2577 | 1.2922 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.0845319317E-002 | 0.1147094384 | Pass | Pass | 3.5948999143E-002 | 0.1845165711 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1073990989 | 6.9207311722E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.2478372397E-002 | 1.0791671658E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.6514786788E-002 | 3.0706841867E-002 | Pass | Pass | 0.1202790414 | 0.5198426843 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.2011083187E-002 | 7.1670002259E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.5015973883E-002 | 1.6487896141E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.4864913383E-002 | 2.8597666610E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.7873137324E-002 | 7.6685518172E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1370621234 | 9.7441537105E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1212911015 | 0.1013186344 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.1180429249E-002 | 5.8212088357E-002 | Pass | Pass | 3.5841401477E-002 | 0.1814017915 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 7.2068183559E-002 | 9.4533448816E-002 | Pass | Pass | 3.5894077419E-002 | 0.1836525208 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1223259235 | 0.1384321827 | Pass | Pass | 5.9951265691E-002 | 0.2941730619 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.7353263564E-002 | 0.1077236115 | Pass | Pass | 3.4396640430E-002 | 0.1773235826 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.7105834900E-002 | 2.1297089816E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.7755421705E-002 | 8.1166882952E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1171098494 | 9.5256746862E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1011867417 | 9.6939187519E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2857.50 | 21.04 | 0.00 | 1148.36 | 1981.79 | 6008.71 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.455_SHGC_NORTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.455_SHGC_EAST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.455_SHGC_WEST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.455_SHGC_EAST_0.249 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.455_SHGC_EAST_0.249 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.455_SHGC_WEST_0.249 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.455_SHGC_WEST_0.249 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.455_SHGC_NORTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.455_SHGC_EAST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.455_SHGC_WEST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.586 | 0.250 | 0.275 | |||||||||||||||||
North Total or Average | 195.79 | 2.586 | 0.250 | 0.275 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.586 | 0.250 | 0.275 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.89 | 0.0000 | Y | 6.71 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.51 | 0.0000 | Y | 4.19 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.38 | 0.0000 | Y | 6.58 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.74 | 0.0000 | Y | 4.23 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.82 | 0.0000 | Y | 6.70 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.46 | 0.0000 | Y | 4.18 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.34 | 0.0000 | Y | 6.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.68 | 0.0000 | Y | 4.22 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.89 | 0.0000 | Y | 6.71 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.51 | 0.0000 | Y | 4.19 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.38 | 0.0000 | Y | 6.58 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.74 | 0.0000 | Y | 4.23 |
Interior Lighting Total | 6.6636 | 4982.19 | 33199.39 | 231.88 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 41.79 | 41.79 | 4.42 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.79 | 62.79 | 4.80 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.79 | 47.06 | 41.65 | |
Exterior Lighting Total | 5686.19 | 50.88 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 105022.57 | 83673.75 | 21348.82 | 0.80 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 94601.88 | 74336.88 | 20265.00 | 0.79 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 108259.98 | 86693.75 | 21566.23 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 103855.0 | 2.86 | 9.77 | N/A | N/A | 11.30 | |
PACU_VAV_MID COOLING COIL | 93645.6 | 2.87 | 9.81 | N/A | N/A | 11.35 | |
PACU_VAV_TOP COOLING COIL | 107000.5 | 2.86 | 9.75 | N/A | N/A | 11.27 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 19348.80 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 19343.45 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 29773.72 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13105.60 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8602.46 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13150.97 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8565.17 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8441.81 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5637.47 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8501.41 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5598.03 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10052.15 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6671.82 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10098.33 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6633.10 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 7295.56 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 9396.57 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 8883.82 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.52 | 11999.40 | 2174.89 | 1.00 | 1.14 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.85 | 10608.97 | 2189.01 | 1.00 | 1.13 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.76 | 12526.78 | 2174.89 | 1.00 | 1.13 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 103855.04 | 2.86 | 9.77 | 11.30 | 5.7932 | 3.23 | 11.04 | 4.6370 | 3.40 | 11.61 | 3.1243 | 3.58 | 12.23 | 1.2402 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 93645.58 | 2.87 | 9.81 | 11.35 | 5.0889 | 3.25 | 11.09 | 4.0662 | 3.42 | 11.68 | 2.7385 | 3.59 | 12.26 | 1.0998 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 107000.47 | 2.86 | 9.75 | 11.27 | 6.0478 | 3.23 | 11.01 | 4.8370 | 3.40 | 11.59 | 3.2577 | 3.58 | 12.21 | 1.2922 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 38462.50 | 38462.50 | 39.11 | 3.053 | 3.053 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00882 | 30.96 | 0.00562 | 0.425 | 0.00 |
CORE_MID | 28428.57 | 28428.57 | 28.90 | 2.254 | 2.254 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 30.96 | 0.00562 | 0.425 | 0.00 |
CORE_TOP | 31074.36 | 31074.36 | 31.59 | 2.487 | 2.487 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00889 | 40.27 | 0.00563 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 11059.62 | 11059.62 | 53.34 | 0.885 | 0.885 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00861 | 40.53 | 0.00563 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9801.12 | 9801.12 | 74.67 | 0.784 | 0.784 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 24.00 | 24.00 | 0.00858 | 36.41 | 0.00562 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12216.04 | 12216.04 | 58.92 | 0.978 | 0.978 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00860 | 40.80 | 0.00563 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11164.90 | 11164.90 | 85.06 | 0.893 | 0.893 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00857 | 38.94 | 0.00563 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 9075.98 | 9075.98 | 43.77 | 0.726 | 0.726 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00870 | 40.67 | 0.00563 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8576.97 | 8576.97 | 65.34 | 0.686 | 0.686 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 24.00 | 24.00 | 0.00863 | 36.41 | 0.00562 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10109.00 | 10109.00 | 48.76 | 0.809 | 0.809 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00868 | 40.80 | 0.00563 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9086.85 | 9086.85 | 69.23 | 0.727 | 0.727 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00863 | 38.72 | 0.00563 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9475.28 | 9475.28 | 45.70 | 0.758 | 0.758 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00865 | 40.67 | 0.00563 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9323.59 | 9323.59 | 71.03 | 0.746 | 0.746 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 24.00 | 24.00 | 0.00859 | 35.75 | 0.00562 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 10634.88 | 10634.88 | 51.29 | 0.851 | 0.851 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00864 | 40.80 | 0.00563 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10020.33 | 10020.33 | 76.34 | 0.802 | 0.802 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00859 | 38.94 | 0.00563 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 4644.49 | 4644.49 | 4.72 | 0.216 | 0.425 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 0.425 | 0.00 |
CORE_MID | 11713.01 | 11713.01 | 11.91 | 0.545 | 0.545 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 0.425 | 0.00 |
CORE_TOP | 20987.36 | 20987.36 | 21.34 | 0.982 | 0.982 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9208.26 | 9208.26 | 44.41 | 0.432 | 0.432 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 6043.59 | 6043.59 | 46.04 | 0.284 | 0.284 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 9240.03 | 9240.03 | 44.57 | 0.434 | 0.434 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 6017.48 | 6017.48 | 45.85 | 0.282 | 0.282 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00784 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 5940.10 | 5940.10 | 28.65 | 0.278 | 0.278 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 3965.99 | 3965.99 | 30.21 | 0.186 | 0.186 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 5981.86 | 5981.86 | 28.85 | 0.280 | 0.280 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 3938.36 | 3938.36 | 30.01 | 0.185 | 0.185 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7069.34 | 7069.34 | 34.10 | 0.332 | 0.332 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 4691.20 | 4691.20 | 35.74 | 0.220 | 0.220 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 7101.69 | 7101.69 | 34.25 | 0.333 | 0.333 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 4664.08 | 4664.08 | 35.53 | 0.219 | 0.219 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | 0.50 | 0.00432 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.52 | 5.52 | 1.35 | 1.35 | 5.5173 | 1.3540 | 5.5173 | 0.2454 | 0.3000 |
PACU_VAV_MID | 4.85 | 4.85 | 1.65 | 1.65 | 4.8465 | 1.6485 | 4.8465 | 0.3402 | 0.3000 |
PACU_VAV_TOP | 5.76 | 5.76 | 2.41 | 2.41 | 5.7597 | 2.4141 | 5.7597 | 0.4191 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 19348.800 | 19348.800 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19348.80 | 12877.06 | 0.424691 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 4644.49 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 19343.450 | 19343.450 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19343.45 | 16529.66 | 0.545155 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 11713.01 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 29773.723 | 29773.723 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 29773.72 | 29773.72 | 0.981950 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 20987.36 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 13105.602 | 13105.602 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13105.60 | 13105.60 | 0.432228 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00784543 | 46.0572 | 9208.26 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 8602.458 | 8602.458 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8602.46 | 8602.46 | 0.283713 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00784581 | 46.0594 | 6043.59 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 13150.974 | 13150.974 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13150.97 | 13150.97 | 0.433725 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00784625 | 46.0619 | 9240.03 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 8565.169 | 8565.169 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8565.17 | 8565.17 | 0.282483 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00784486 | 46.0539 | 6017.48 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 8441.813 | 8441.813 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8441.81 | 8441.81 | 0.278415 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00776501 | 45.5912 | 5940.10 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 5637.465 | 5637.465 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5637.47 | 5637.47 | 0.185926 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00777943 | 45.6748 | 3965.99 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 8501.409 | 8501.409 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8501.41 | 8501.41 | 0.280380 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00776858 | 45.6120 | 5981.86 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 5598.032 | 5598.032 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5598.03 | 5598.03 | 0.184626 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00777608 | 45.6554 | 3938.36 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 10052.147 | 10052.147 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10052.15 | 10052.15 | 0.331524 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00777977 | 45.6769 | 7069.34 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 6671.820 | 6671.820 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6671.82 | 6671.82 | 0.220040 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00778909 | 45.7309 | 4691.20 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 10098.331 | 10098.331 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10098.33 | 10098.33 | 0.333047 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00778172 | 45.6882 | 7101.69 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 6633.098 | 6633.098 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6633.10 | 6633.10 | 0.218762 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00778679 | 45.7176 | 4664.08 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 105022.572 | 83673.755 | 5.517251 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 95747.64 | 95747.64 | 5.517251 | 26.92 | 16.16 | 0.00821739 | 10.85 | 10.15 | 0.00821739 | 40.80 | 0.00563111 | 18.58 | 17.3293 | 24.00 | 0.00876089 | 42.7995 | 68796.18 | 0.00 | 108292.37 | 80872.18 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 7295.557 | 7295.557 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7295.56 | 7295.56 | 1.655175 | 8.79 | 6.54 | 0.00571848 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 57.7643 | 19.75 | 0.00756714 | 48.0169 | 12179.19 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 94601.880 | 74336.878 | 4.846465 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 86247.24 | 86247.24 | 4.846465 | 27.33 | 16.25 | 0.00815281 | 10.84 | 10.08 | 0.00815281 | 40.80 | 0.00563111 | 18.58 | 19.7278 | 24.00 | 0.00877746 | 42.8790 | 60176.59 | 0.00 | 97547.24 | 71929.16 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 9396.568 | 9396.568 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9396.57 | 9396.57 | 1.453940 | 6.92 | 5.32 | 0.00543613 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 65.7593 | 19.63 | 0.00737844 | 47.1824 | 14945.52 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 108259.985 | 86693.750 | 5.759733 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 98993.50 | 98993.50 | 5.759733 | 26.75 | 16.10 | 0.00820843 | 10.85 | 10.14 | 0.00820843 | 40.53 | 0.00563070 | 18.50 | 16.5997 | 24.00 | 0.00872368 | 42.6197 | 71716.92 | 0.00 | 111630.58 | 83759.04 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 8883.821 | 8883.821 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8883.82 | 8883.82 | 1.727920 | 8.12 | 6.33 | 0.00580486 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 55.3324 | 17.60 | 0.00748056 | 54.3065 | 16130.14 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 19348.800 | 19348.800 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19348.80 | 12877.06 | 1.0000 | 0.46426985 | 0.424691 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19348.80 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.72 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 4644.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 19343.450 | 19343.450 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19343.45 | 16529.66 | 1.0000 | 0.59596061 | 0.545155 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19343.45 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 11713.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 29773.723 | 29773.723 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 29773.72 | 29773.72 | 1.0000 | 1.07346250 | 0.981950 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29773.72 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 20987.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 13105.602 | 13105.602 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13105.60 | 13105.60 | 1.0000 | 0.47250967 | 0.432228 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13105.60 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00784543 | 21.00 | 0.00784543 | 46.0572 | 9208.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8602.458 | 8602.458 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8602.46 | 8602.46 | 1.0000 | 0.31015324 | 0.283713 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8602.46 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00784581 | 21.00 | 0.00784581 | 46.0594 | 6043.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 13150.974 | 13150.974 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13150.97 | 13150.97 | 1.0000 | 0.47414553 | 0.433725 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13150.97 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00784625 | 21.00 | 0.00784625 | 46.0619 | 9240.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 8565.169 | 8565.169 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8565.17 | 8565.17 | 1.0000 | 0.30880879 | 0.282483 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8565.17 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00784486 | 21.00 | 0.00784486 | 46.0539 | 6017.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 8441.813 | 8441.813 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8441.81 | 8441.81 | 1.0000 | 0.30436134 | 0.278415 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8441.81 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00776501 | 21.00 | 0.00776501 | 45.5912 | 5940.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 5637.465 | 5637.465 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5637.47 | 5637.47 | 1.0000 | 0.20325330 | 0.185926 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5637.47 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00777943 | 21.00 | 0.00777943 | 45.6748 | 3965.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 8501.409 | 8501.409 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8501.41 | 8501.41 | 1.0000 | 0.30650998 | 0.280380 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8501.41 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00776858 | 21.00 | 0.00776858 | 45.6120 | 5981.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5598.032 | 5598.032 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5598.03 | 5598.03 | 1.0000 | 0.20183159 | 0.184626 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5598.03 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00777608 | 21.00 | 0.00777608 | 45.6554 | 3938.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 10052.147 | 10052.147 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10052.15 | 10052.15 | 1.0000 | 0.36242034 | 0.331524 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10052.15 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00777977 | 21.00 | 0.00777977 | 45.6769 | 7069.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 6671.820 | 6671.820 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6671.82 | 6671.82 | 1.0000 | 0.24054594 | 0.220040 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6671.82 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00778909 | 21.00 | 0.00778909 | 45.7309 | 4691.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 10098.331 | 10098.331 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10098.33 | 10098.33 | 1.0000 | 0.36408547 | 0.333047 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10098.33 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00778172 | 21.00 | 0.00778172 | 45.6882 | 7101.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 6633.098 | 6633.098 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6633.10 | 6633.10 | 1.0000 | 0.23914988 | 0.218762 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6633.10 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00778679 | 21.00 | 0.00778679 | 45.7176 | 4664.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 105022.572 | 83673.755 | 5.517251 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1157 | 1004.8586 | 1.0932 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.517251 | 6.03142664 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 95747.64 | 95747.64 | 0.9117 | 6.03142664 | 5.517251 | 26.92 | 16.16 | 0.00821739 | 48009.2 | 10.85 | 10.15 | 0.00821739 | 31619.2 | -999.0 | -999.00 | -999.00 | -999.00 | 11999.404 | 83748.23 | 40.80 | 0.00563111 | 18.58 | 0.95610000 | 17.3293 | 24.00 | 0.00876089 | 24.00 | 0.00876089 | 42.7995 | 68796.18 | 0.00 | 108292.37 | 80872.18 | 5.79323088 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.01 | 13.00 | 0.00932890 | 36629.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7295.557 | 7295.557 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.517251 | 6.03142664 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7295.56 | 7295.56 | 1.0000 | 1.80942799 | 1.655175 | 8.79 | 6.54 | 0.00571848 | 23225.0 | 12.80 | 10.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7295.56 | 0.50 | 0.00431558 | 0.50 | 0.95610000 | 57.7643 | 20.12 | 0.00763716 | 19.75 | 0.00756714 | 48.0169 | 12179.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 94601.880 | 74336.878 | 4.846465 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9957 | 1004.8586 | 1.0932 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.846465 | 5.29812769 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 86247.24 | 86247.24 | 0.9117 | 5.29812769 | 4.846465 | 27.33 | 16.25 | 0.00815281 | 48270.8 | 10.84 | 10.08 | 0.00815281 | 31443.2 | -999.0 | -999.00 | -999.00 | -999.00 | 10608.966 | 75638.27 | 40.80 | 0.00563111 | 18.58 | 0.95610000 | 19.7278 | 24.00 | 0.00877746 | 24.00 | 0.00877746 | 42.8790 | 60176.59 | 0.00 | 97547.24 | 71929.16 | 5.08889170 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.84 | 12.82 | 0.00921090 | 36153.7 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9396.568 | 9396.568 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.846465 | 5.29812769 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9396.57 | 9396.57 | 1.0000 | 1.58943831 | 1.453940 | 6.92 | 5.32 | 0.00543613 | 20615.5 | 12.80 | 10.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9396.57 | 0.50 | 0.00431558 | 0.50 | 0.95610000 | 65.7593 | 19.24 | 0.00758814 | 19.63 | 0.00737844 | 47.1824 | 14945.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 108259.985 | 86693.750 | 5.759733 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0991 | 1004.8586 | 1.0932 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.759733 | 6.29650722 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 98993.50 | 98993.50 | 0.9144 | 6.29650722 | 5.759733 | 26.75 | 16.10 | 0.00820843 | 47820.1 | 10.85 | 10.14 | 0.00820843 | 31596.6 | -999.0 | -999.00 | -999.00 | -999.00 | 12526.777 | 86466.72 | 40.53 | 0.00563070 | 18.50 | 0.95610000 | 16.5997 | 24.00 | 0.00872368 | 24.00 | 0.00872368 | 42.6197 | 71716.92 | 0.00 | 111630.58 | 83759.04 | 6.04784278 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.12 | 13.09 | 0.00937777 | 36864.5 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8883.821 | 8883.821 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.759733 | 6.29650722 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8883.82 | 8883.82 | 1.0000 | 1.88895217 | 1.727920 | 8.12 | 6.33 | 0.00580486 | 22764.2 | 12.80 | 10.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8883.82 | 0.50 | 0.00431558 | 0.50 | 0.95610000 | 55.3324 | 17.56 | 0.00764972 | 17.60 | 0.00748056 | 54.3065 | 16130.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.52 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.85 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.76 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2123.00 | 964.00 | 2.33 |
CORE_MID | 1686.00 | 2237.67 | 13.17 |
CORE_TOP | 1708.17 | 2623.83 | 72.50 |
PERIMETER_TOP_ZN_3 | 2384.00 | 2996.33 | 556.17 |
PERIMETER_TOP_ZN_2 | 2820.33 | 2441.50 | 503.00 |
PERIMETER_TOP_ZN_1 | 2922.33 | 2025.67 | 414.67 |
PERIMETER_TOP_ZN_4 | 2798.50 | 2584.50 | 584.67 |
PERIMETER_BOT_ZN_3 | 1897.17 | 2967.33 | 145.33 |
PERIMETER_BOT_ZN_2 | 2571.67 | 2092.83 | 205.83 |
PERIMETER_BOT_ZN_1 | 2667.33 | 1895.83 | 288.33 |
PERIMETER_BOT_ZN_4 | 2481.00 | 2259.33 | 186.17 |
PERIMETER_MID_ZN_3 | 2028.33 | 2795.33 | 222.33 |
PERIMETER_MID_ZN_2 | 2214.33 | 1973.33 | 294.17 |
PERIMETER_MID_ZN_1 | 2777.00 | 1744.67 | 235.17 |
PERIMETER_MID_ZN_4 | 2562.67 | 2346.00 | 304.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4218.17 | 3579.83 | 917.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.17 | 53.67 | 0.17 | 33.33 |
PERIMETER_TOP_ZN_2 | 0.33 | 96.50 | 0.17 | 73.83 |
PERIMETER_TOP_ZN_1 | 0.00 | 88.83 | 0.00 | 67.50 |
PERIMETER_TOP_ZN_4 | 0.00 | 89.83 | 0.00 | 47.50 |
PERIMETER_BOT_ZN_3 | 0.00 | 14.33 | 0.00 | 9.17 |
PERIMETER_BOT_ZN_2 | 0.00 | 75.17 | 0.00 | 64.83 |
PERIMETER_BOT_ZN_1 | 73.50 | 357.17 | 73.50 | 349.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 69.33 | 0.00 | 38.00 |
PERIMETER_MID_ZN_3 | 0.00 | 29.83 | 0.00 | 19.33 |
PERIMETER_MID_ZN_2 | 0.00 | 82.00 | 0.00 | 70.00 |
PERIMETER_MID_ZN_1 | 0.00 | 77.50 | 0.00 | 67.67 |
PERIMETER_MID_ZN_4 | 0.00 | 74.33 | 0.00 | 42.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 73.83 | 591.17 | 73.67 | 518.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.96 | 52.94 | 2698.04 | 0.911 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.96 | 52.94 | 2698.04 | 0.623 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.96 | 52.94 | 2698.04 | 0.582 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.63 | 11.16 | 568.77 | 0.654 | 0.067 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 1.011 | 0.071 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.63 | 11.16 | 568.77 | 1.200 | 0.068 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 0.945 | 0.071 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.63 | 11.16 | 568.77 | 0.589 | 0.036 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 0.958 | 0.038 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.63 | 11.16 | 568.77 | 1.028 | 1.279 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.845 | 0.038 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.63 | 11.16 | 568.77 | 0.670 | 0.056 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 0.990 | 0.064 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.63 | 11.16 | 568.77 | 1.207 | 0.056 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 0.955 | 0.059 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.96 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.96 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.96 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.96 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.96 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.96 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.57 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.86 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 14451540.73 | 0.00 | 14451540.73 | 0.00 | 14451540.73 | 13393058.27 | 5851.68 | 73.88 | 2834.44 | 49.90 |
CORE_MID | 9880358.07 | 0.00 | 9880358.07 | 0.00 | 9880358.07 | 13393058.27 | 6317.50 | 139.37 | 2303.13 | 33.98 |
CORE_TOP | 9247749.76 | 0.00 | 9247749.76 | 0.00 | 9247749.76 | 13393058.27 | 6290.31 | 180.23 | 2289.47 | 39.01 |
PERIMETER_TOP_ZN_3 | 2187021.87 | 0.00 | 2187021.87 | 446659.24 | 2633681.11 | 2823374.22 | 4346.91 | 161.94 | 4251.15 | 39.01 |
PERIMETER_TOP_ZN_2 | 2132643.20 | 0.00 | 2132643.20 | 297771.03 | 2430414.23 | 1787429.43 | 4153.37 | 236.30 | 4370.33 | 39.01 |
PERIMETER_TOP_ZN_1 | 3999675.23 | 0.00 | 3999675.23 | 446659.24 | 4446334.46 | 2823374.22 | 4230.44 | 237.61 | 4291.95 | 39.01 |
PERIMETER_TOP_ZN_4 | 1998966.83 | 0.00 | 1998966.83 | 297771.03 | 2296737.87 | 1787312.18 | 4257.27 | 225.52 | 4277.21 | 39.01 |
PERIMETER_BOT_ZN_3 | 1977250.69 | 0.00 | 1977250.69 | 237487.89 | 2214738.58 | 2823374.22 | 5740.19 | 142.10 | 2877.70 | 49.90 |
PERIMETER_BOT_ZN_2 | 2027122.92 | 0.00 | 2027122.92 | 158324.31 | 2185447.23 | 1787429.43 | 4490.21 | 58.16 | 4211.63 | 49.90 |
PERIMETER_BOT_ZN_1 | 3438268.31 | 0.00 | 3438268.31 | 4361350.24 | 7799618.55 | 2823374.22 | 4440.76 | 66.87 | 4252.38 | 49.90 |
PERIMETER_BOT_ZN_4 | 1790390.94 | 0.00 | 1790390.94 | 158324.31 | 1948715.25 | 1787312.18 | 4776.23 | 106.07 | 3877.69 | 49.90 |
PERIMETER_MID_ZN_3 | 2238551.30 | 0.00 | 2238551.30 | 371810.73 | 2610362.02 | 2823374.22 | 4428.12 | 218.87 | 4113.00 | 33.98 |
PERIMETER_MID_ZN_2 | 2108534.24 | 0.00 | 2108534.24 | 247872.33 | 2356406.56 | 1601953.02 | 4151.34 | 158.50 | 4450.16 | 942.98 |
PERIMETER_MID_ZN_1 | 4019336.75 | 0.00 | 4019336.75 | 371810.73 | 4391147.48 | 2823374.22 | 4208.00 | 165.04 | 4386.96 | 33.98 |
PERIMETER_MID_ZN_4 | 2015445.79 | 0.00 | 2015445.79 | 247872.33 | 2263318.12 | 1787312.18 | 4262.58 | 200.00 | 4297.42 | 33.98 |
Total Facility | 63512856.61 | 0.00 | 63512856.61 | 7643713.41 | 71156570.02 | 67658168.57 | 6852.93 | 650.57 | 4760.85 | 984.66 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6695 | 0.0000 | 0.6695 | 0.0000 | 0.6695 | 0.4247 | 3084.37 | 73.88 | 2784.75 |
CORE_MID | 0.4578 | 0.0000 | 0.4578 | 0.0000 | 0.4578 | 0.4247 | 3534.49 | 139.37 | 2269.14 |
CORE_TOP | 0.4279 | 0.0000 | 0.4279 | 0.0000 | 0.4279 | 0.4247 | 3511.74 | 180.23 | 2251.04 |
PERIMETER_TOP_ZN_3 | 0.1013 | 0.0000 | 0.1013 | 0.0104 | 0.1117 | 0.0895 | 1568.34 | 161.94 | 4212.72 |
PERIMETER_TOP_ZN_2 | 0.0991 | 0.0000 | 0.0991 | 0.0070 | 0.1060 | 0.0567 | 1374.80 | 236.30 | 4331.90 |
PERIMETER_TOP_ZN_1 | 0.1860 | 0.0000 | 0.1860 | 0.0104 | 0.1964 | 0.0895 | 1451.87 | 237.61 | 4253.52 |
PERIMETER_TOP_ZN_4 | 0.0927 | 0.0000 | 0.0927 | 0.0070 | 0.0996 | 0.0567 | 1478.70 | 225.52 | 4238.78 |
PERIMETER_BOT_ZN_3 | 0.0912 | 0.0000 | 0.0912 | 0.0055 | 0.0968 | 0.0895 | 2972.89 | 142.10 | 2828.01 |
PERIMETER_BOT_ZN_2 | 0.0939 | 0.0000 | 0.0939 | 0.0037 | 0.0976 | 0.0567 | 1722.90 | 58.16 | 4161.94 |
PERIMETER_BOT_ZN_1 | 0.1594 | 0.0000 | 0.1594 | 0.1983 | 0.3577 | 0.0895 | 1673.45 | 66.87 | 4202.68 |
PERIMETER_BOT_ZN_4 | 0.0828 | 0.0000 | 0.0828 | 0.0037 | 0.0865 | 0.0567 | 2008.93 | 106.07 | 3828.00 |
PERIMETER_MID_ZN_3 | 0.1038 | 0.0000 | 0.1038 | 0.0087 | 0.1125 | 0.0895 | 1645.11 | 218.87 | 4079.02 |
PERIMETER_MID_ZN_2 | 0.0970 | 0.0000 | 0.0970 | 0.0062 | 0.1033 | 0.0567 | 1368.32 | 158.50 | 3507.18 |
PERIMETER_MID_ZN_1 | 0.1870 | 0.0000 | 0.1870 | 0.0087 | 0.1957 | 0.0895 | 1424.98 | 165.04 | 4352.98 |
PERIMETER_MID_ZN_4 | 0.0936 | 0.0000 | 0.0936 | 0.0058 | 0.0994 | 0.0567 | 1479.57 | 200.00 | 4263.44 |
Total Facility | 2.9430 | 0.0000 | 2.9430 | 0.2754 | 3.2184 | 2.1513 | 4050.78 | 650.57 | 4685.73 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 28304783.95 | 0.00 | 28304783.95 | 22614548.33 | 4026.68 | 3.51 | 4729.81 | 49.90 |
PACU_VAV_MID | 24214821.41 | 0.00 | 24214821.41 | 22429071.92 | 4066.52 | 4.74 | 4688.74 | 33.98 |
PACU_VAV_TOP | 23382851.72 | 0.00 | 23382851.72 | 22614548.33 | 4108.62 | 1.11 | 4650.27 | 39.01 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.3107 | 0.0000 | 1.3107 | 0.7171 | 1259.37 | 3.51 | 4680.11 |
PACU_VAV_MID | 1.1236 | 0.0000 | 1.1236 | 0.7084 | 1283.50 | 4.74 | 4654.76 |
PACU_VAV_TOP | 1.0839 | 0.0000 | 1.0839 | 0.7171 | 1330.05 | 1.11 | 4611.84 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 393.24 | 2250.07 | 0.00 | 0.00 | 0.00 | 2144.58 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 112.15 | 2327.78 | 0.00 | 0.00 | 0.00 | 2321.75 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 69.58 | 2306.17 | 0.00 | 0.00 | 0.00 | 2380.47 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.1249 | 2.4413 | 0.0000 | 0.0000 | 0.0000 | 0.9220 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.1011 | 1.9131 | 0.0000 | 0.0000 | 0.0000 | 0.9332 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.0614 | 1.8296 | 0.0000 | 0.0000 | 0.0000 | 0.9325 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 943 |
Defaulted Fields | 546 |
Fields with Defaults | 2233 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1592.05 | 12315.29 | 04-JUN-18:00 | 179744.45 | 28-JUN-15:00 |
Electricity:Building | 937.32 | 12146.72 | 02-APR-17:20 | 69450.33 | 20-JAN-08:30 |
Electricity:Zone:CORE_BOTTOM | 291.77 | 4006.86 | 01-JAN-00:10 | 23121.21 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 937.32 | 12146.72 | 02-APR-17:20 | 69450.33 | 20-JAN-08:30 |
InteriorLights:Electricity | 231.88 | 905.38 | 02-APR-17:20 | 25003.79 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 231.88 | 905.38 | 02-APR-17:20 | 25003.79 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity | 231.88 | 905.38 | 02-APR-17:20 | 25003.79 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 231.88 | 905.38 | 02-APR-17:20 | 25003.79 | 28-NOV-16:30 |
Electricity:Zone:CORE_MID | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 31.05 | 413.68 | 02-APR-17:10 | 2475.80 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.71 | 27.57 | 01-JAN-09:50 | 1040.56 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.71 | 27.57 | 01-JAN-09:50 | 1040.56 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.59 | 261.88 | 02-APR-17:10 | 1567.33 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.19 | 17.46 | 01-JAN-08:00 | 658.76 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.19 | 17.46 | 01-JAN-08:00 | 658.76 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 30.91 | 413.67 | 12-MAR-17:10 | 2475.79 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.58 | 27.57 | 01-JAN-07:50 | 1040.56 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.58 | 27.57 | 01-JAN-07:50 | 1040.56 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.63 | 261.87 | 12-MAR-17:10 | 1567.28 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.23 | 17.46 | 01-JAN-09:40 | 658.71 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.23 | 17.46 | 01-JAN-09:40 | 658.71 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 31.03 | 413.68 | 02-APR-17:10 | 2475.80 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.70 | 27.57 | 01-JAN-09:40 | 1040.56 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.70 | 27.57 | 01-JAN-09:40 | 1040.56 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.58 | 261.88 | 02-APR-17:10 | 1567.33 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.18 | 17.46 | 01-JAN-07:50 | 658.76 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.18 | 17.46 | 01-JAN-07:50 | 658.76 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 30.91 | 413.67 | 12-MAR-17:10 | 2475.79 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.57 | 27.57 | 01-JAN-07:50 | 1040.56 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.57 | 27.57 | 01-JAN-07:50 | 1040.56 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.62 | 261.87 | 12-MAR-17:10 | 1567.28 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.22 | 17.46 | 01-JAN-09:40 | 658.71 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.22 | 17.46 | 01-JAN-09:40 | 658.71 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 31.05 | 413.68 | 02-APR-17:10 | 2475.80 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.71 | 27.57 | 01-JAN-09:50 | 1040.56 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.71 | 27.57 | 01-JAN-09:50 | 1040.56 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.59 | 261.88 | 02-APR-17:10 | 1567.33 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.19 | 17.46 | 01-JAN-08:00 | 658.76 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.19 | 17.46 | 01-JAN-08:00 | 658.76 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 30.91 | 413.67 | 12-MAR-17:10 | 2475.79 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.58 | 27.57 | 01-JAN-07:50 | 1040.56 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.58 | 27.57 | 01-JAN-07:50 | 1040.56 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.63 | 261.87 | 12-MAR-17:10 | 1567.28 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.23 | 17.46 | 01-JAN-09:40 | 658.71 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.23 | 17.46 | 01-JAN-09:40 | 658.71 | 28-NOV-16:30 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 603.70 | 168.34 | 01-JAN-00:10 | 119477.71 | 28-JUN-15:00 |
ExteriorEquipment:Electricity | 11.69 | 168.34 | 01-JAN-00:10 | 838.79 | 28-NOV-16:40 |
Transformer:ExteriorEquipment:Electricity | 11.69 | 168.34 | 01-JAN-00:10 | 838.79 | 28-NOV-16:40 |
ElectricityPurchased:Facility | 1592.05 | 12315.29 | 04-JUN-18:00 | 179744.45 | 28-JUN-15:00 |
ElectricityPurchased:Plant | 1592.05 | 12315.29 | 04-JUN-18:00 | 179744.45 | 28-JUN-15:00 |
Cogeneration:ElectricityPurchased | 1592.05 | 12315.29 | 04-JUN-18:00 | 179744.45 | 28-JUN-15:00 |
General:Cogeneration:ElectricityPurchased | 1592.05 | 12315.29 | 04-JUN-18:00 | 179744.45 | 28-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1592.05 | 12315.29 | 04-JUN-18:00 | 179744.45 | 28-JUN-15:00 |
ElectricityNet:Plant | 1592.05 | 12315.29 | 04-JUN-18:00 | 179744.45 | 28-JUN-15:00 |
Cogeneration:ElectricityNet | 1592.05 | 12315.29 | 04-JUN-18:00 | 179744.45 | 28-JUN-15:00 |
General:Cogeneration:ElectricityNet | 1592.05 | 12315.29 | 04-JUN-18:00 | 179744.45 | 28-JUN-15:00 |
Heating:Electricity | 7.23 | 0.00 | 01-JAN-00:10 | 75538.57 | 02-JAN-07:10 |
General:Heating:Electricity | 7.23 | 0.00 | 01-JAN-00:10 | 75538.57 | 02-JAN-07:10 |
Fans:Electricity | 144.32 | 0.00 | 01-JAN-00:10 | 28646.28 | 19-JUN-15:00 |
General:Fans:Electricity | 144.32 | 0.00 | 01-JAN-00:10 | 28646.28 | 19-JUN-15:00 |
ExteriorLights:Electricity | 50.88 | 0.00 | 01-JAN-07:30 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 50.88 | 0.00 | 01-JAN-07:30 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 440.47 | 0.00 | 01-JAN-00:10 | 92791.32 | 28-JUN-15:00 |
General:Cooling:Electricity | 440.47 | 0.00 | 01-JAN-00:10 | 92791.32 | 28-JUN-15:00 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 12-JAN-08:10 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 12-JAN-08:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 12-JAN-08:10 |
WIRED_LTG_ELECTRICITY | 6.52 | 0.00 | 01-JAN-00:10 | 702.61 | 28-NOV-16:40 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 123.70 | 1886.44 | 07-MAY-16:10 | 40141.95 | 06-DEC-07:30 |
NaturalGas:HVAC | 6.53 | 0.00 | 01-JAN-00:10 | 31873.91 | 06-DEC-07:20 |
Heating:NaturalGas | 6.53 | 0.00 | 01-JAN-00:10 | 31873.91 | 06-DEC-07:20 |
General:Heating:NaturalGas | 6.53 | 0.00 | 01-JAN-00:10 | 31873.91 | 06-DEC-07:20 |
NaturalGas:Plant | 117.17 | 1886.44 | 08-FEB-08:10 | 9787.80 | 01-FEB-12:10 |
WaterSystems:NaturalGas | 117.17 | 1886.44 | 08-FEB-08:10 | 9787.80 | 01-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 117.17 | 1886.44 | 08-FEB-08:10 | 9787.80 | 01-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3078.31 | 0.00 | 01-JAN-00:10 | 431931.85 | 05-SEP-08:00 |
EnergyTransfer:Building | 1487.37 | 0.00 | 01-JAN-00:10 | 177215.34 | 14-AUG-15:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 283.14 | 0.00 | 01-JAN-00:10 | 28391.44 | 05-SEP-08:00 |
Heating:EnergyTransfer | 12.68 | 0.00 | 01-JAN-00:10 | 65504.86 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 12.68 | 0.00 | 01-JAN-00:10 | 65504.86 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1474.69 | 0.00 | 01-JAN-00:10 | 177215.34 | 14-AUG-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 283.14 | 0.00 | 01-JAN-00:10 | 28391.44 | 05-SEP-08:00 |
General:Cooling:EnergyTransfer | 1474.69 | 0.00 | 01-JAN-00:10 | 177215.34 | 14-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 283.14 | 0.00 | 01-JAN-00:10 | 28391.44 | 05-SEP-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 67.82 | 0.00 | 01-JAN-00:10 | 13236.50 | 28-JUN-14:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.42 | 0.00 | 01-JAN-00:10 | 6700.56 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.42 | 0.00 | 01-JAN-00:10 | 6700.56 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 62.40 | 0.00 | 01-JAN-00:10 | 13236.50 | 28-JUN-14:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 62.40 | 0.00 | 01-JAN-00:10 | 13236.50 | 28-JUN-14:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 34.99 | 0.00 | 01-JAN-00:10 | 6385.71 | 19-JUN-14:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.85 | 0.00 | 01-JAN-00:10 | 2763.30 | 02-JAN-11:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.85 | 0.00 | 01-JAN-00:10 | 2763.30 | 02-JAN-11:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 33.14 | 0.00 | 01-JAN-00:10 | 6385.71 | 19-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 33.14 | 0.00 | 01-JAN-00:10 | 6385.71 | 19-JUN-14:20 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 40.60 | 0.00 | 01-JAN-00:10 | 6600.32 | 28-AUG-07:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.72 | 0.00 | 01-JAN-00:10 | 2267.12 | 02-JAN-09:00 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.72 | 0.00 | 01-JAN-00:10 | 2267.12 | 02-JAN-09:00 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 39.88 | 0.00 | 01-JAN-00:10 | 6600.32 | 28-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 39.88 | 0.00 | 01-JAN-00:10 | 6600.32 | 28-AUG-07:10 |
EnergyTransfer:Zone:CORE_MID | 189.06 | 0.00 | 01-JAN-00:10 | 20653.59 | 05-SEP-07:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 2222.36 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 2222.36 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 189.06 | 0.00 | 01-JAN-00:10 | 20653.59 | 05-SEP-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 189.06 | 0.00 | 01-JAN-00:10 | 20653.59 | 05-SEP-07:20 |
EnergyTransfer:Zone:CORE_TOP | 187.28 | 0.00 | 01-JAN-00:10 | 21845.85 | 19-JUN-13:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.09 | 0.00 | 01-JAN-00:10 | 12408.67 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.09 | 0.00 | 01-JAN-00:10 | 12408.67 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 187.19 | 0.00 | 01-JAN-00:10 | 21845.85 | 19-JUN-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 187.19 | 0.00 | 01-JAN-00:10 | 21845.85 | 19-JUN-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 52.84 | 0.00 | 01-JAN-00:10 | 8265.97 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.67 | 0.00 | 01-JAN-00:10 | 7232.20 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.67 | 0.00 | 01-JAN-00:10 | 7232.20 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 52.17 | 0.00 | 01-JAN-00:10 | 8265.97 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 52.17 | 0.00 | 01-JAN-00:10 | 8265.97 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 50.58 | 0.00 | 01-JAN-00:10 | 9012.39 | 19-JUN-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.27 | 0.00 | 01-JAN-00:10 | 4621.65 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.27 | 0.00 | 01-JAN-00:10 | 4621.65 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 50.31 | 0.00 | 01-JAN-00:10 | 9012.39 | 19-JUN-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 50.31 | 0.00 | 01-JAN-00:10 | 9012.39 | 19-JUN-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 79.21 | 0.00 | 01-JAN-00:10 | 12617.41 | 02-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.33 | 0.00 | 01-JAN-00:10 | 5824.01 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.33 | 0.00 | 01-JAN-00:10 | 5824.01 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 78.88 | 0.00 | 01-JAN-00:10 | 12617.41 | 02-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 78.88 | 0.00 | 01-JAN-00:10 | 12617.41 | 02-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 48.86 | 0.00 | 01-JAN-00:10 | 9746.28 | 26-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.39 | 0.00 | 01-JAN-00:10 | 4369.41 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.39 | 0.00 | 01-JAN-00:10 | 4369.41 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 48.48 | 0.00 | 01-JAN-00:10 | 9746.28 | 26-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 48.48 | 0.00 | 01-JAN-00:10 | 9746.28 | 26-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 48.88 | 0.00 | 01-JAN-00:10 | 7207.34 | 17-JUL-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.04 | 0.00 | 01-JAN-00:10 | 2800.57 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.04 | 0.00 | 01-JAN-00:10 | 2800.57 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 48.84 | 0.00 | 01-JAN-00:10 | 7207.34 | 17-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 48.84 | 0.00 | 01-JAN-00:10 | 7207.34 | 17-JUL-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 49.18 | 0.00 | 01-JAN-00:10 | 8042.63 | 14-AUG-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1345.50 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1345.50 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 49.18 | 0.00 | 01-JAN-00:10 | 8042.63 | 14-AUG-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 49.18 | 0.00 | 01-JAN-00:10 | 8042.63 | 14-AUG-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 85.14 | 0.00 | 01-JAN-00:10 | 14116.75 | 28-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.72 | 0.00 | 01-JAN-00:10 | 7929.81 | 27-MAR-06:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.72 | 0.00 | 01-JAN-00:10 | 7929.81 | 27-MAR-06:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 82.42 | 0.00 | 01-JAN-00:10 | 14116.75 | 28-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 82.42 | 0.00 | 01-JAN-00:10 | 14116.75 | 28-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 46.22 | 0.00 | 01-JAN-00:10 | 7994.11 | 26-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1263.64 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1263.64 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 46.21 | 0.00 | 01-JAN-00:10 | 7994.11 | 26-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 46.21 | 0.00 | 01-JAN-00:10 | 7994.11 | 26-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 50.90 | 0.00 | 01-JAN-00:10 | 7373.82 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.08 | 0.00 | 01-JAN-00:10 | 3464.20 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.08 | 0.00 | 01-JAN-00:10 | 3464.20 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 50.82 | 0.00 | 01-JAN-00:10 | 7373.82 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 50.82 | 0.00 | 01-JAN-00:10 | 7373.82 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 47.48 | 0.00 | 01-JAN-00:10 | 8756.44 | 19-JUN-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.03 | 0.00 | 01-JAN-00:10 | 2142.05 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.03 | 0.00 | 01-JAN-00:10 | 2142.05 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 47.45 | 0.00 | 01-JAN-00:10 | 8756.44 | 19-JUN-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 47.45 | 0.00 | 01-JAN-00:10 | 8756.44 | 19-JUN-08:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 78.00 | 0.00 | 01-JAN-00:10 | 11284.48 | 02-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.03 | 0.00 | 01-JAN-00:10 | 2346.27 | 07-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.03 | 0.00 | 01-JAN-00:10 | 2346.27 | 07-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 77.98 | 0.00 | 01-JAN-00:10 | 11284.48 | 02-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 77.98 | 0.00 | 01-JAN-00:10 | 11284.48 | 02-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 47.19 | 0.00 | 01-JAN-00:10 | 9089.08 | 26-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.04 | 0.00 | 01-JAN-00:10 | 1975.10 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.04 | 0.00 | 01-JAN-00:10 | 1975.10 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 47.15 | 0.00 | 01-JAN-00:10 | 9089.08 | 26-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 47.15 | 0.00 | 01-JAN-00:10 | 9089.08 | 26-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 38.47 | 0.00 | 01-JAN-00:10 | 5189.47 | 23-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 38.47 | 0.00 | 01-JAN-00:10 | 5189.47 | 23-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 38.47 | 0.00 | 01-JAN-00:10 | 5189.47 | 23-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 38.47 | 0.00 | 01-JAN-00:10 | 5189.47 | 23-JAN-12:10 |
EnergyTransfer:HVAC | 1552.47 | 0.00 | 01-JAN-00:10 | 291065.40 | 05-SEP-07:40 |
HeatingCoils:EnergyTransfer | 12.45 | 0.00 | 01-JAN-00:10 | 88634.72 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 1540.02 | 0.00 | 01-JAN-00:10 | 291065.40 | 05-SEP-07:40 |
EnergyTransfer:Plant | 38.47 | 0.00 | 01-JAN-00:10 | 5189.47 | 23-JAN-12:10 |
WaterSystems:EnergyTransfer | 38.47 | 0.00 | 01-JAN-00:10 | 5189.47 | 23-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 38.47 | 0.00 | 01-JAN-00:10 | 5189.47 | 23-JAN-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -283.145 | 0.000 | 0.000 | 32.670 | 55.599 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -41.292 |
CORE_MID | 0.000 | 0.000 | 0.001 | -189.064 | 0.000 | 0.000 | 32.833 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -14.794 |
CORE_TOP | 0.000 | 0.000 | 0.089 | -187.193 | 0.000 | 0.000 | 33.164 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -17.083 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.669 | -52.169 | 0.000 | 0.000 | 7.133 | 6.714 | 24.333 | 25.106 | 0.000 | 0.969 | 9.255 | 0.000 | -19.809 | 0.000 | -2.201 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.266 | -50.310 | 0.000 | 0.000 | 4.422 | 4.189 | 15.404 | 43.429 | 0.000 | 0.629 | 0.000 | 0.000 | -12.557 | 0.000 | -1.538 | -3.934 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.331 | -78.878 | 0.000 | 0.000 | 6.990 | 6.581 | 24.332 | 71.461 | 0.000 | 0.949 | 0.001 | 0.000 | -19.744 | 0.000 | -2.408 | -9.614 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.385 | -48.476 | 0.000 | 0.000 | 4.492 | 4.226 | 15.403 | 41.731 | 0.000 | 0.621 | 0.000 | 0.000 | -13.669 | 0.000 | -1.545 | -3.169 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.035 | -48.844 | 0.000 | 0.000 | 7.055 | 6.696 | 24.333 | 25.187 | 0.000 | 0.539 | 7.344 | 0.000 | -21.076 | 0.000 | -1.270 | -0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.005 | -49.177 | 0.000 | 0.000 | 4.387 | 4.181 | 15.404 | 43.461 | 0.000 | 0.341 | 0.003 | 0.000 | -13.668 | 0.000 | -0.910 | -4.023 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 2.723 | -82.415 | 0.000 | 0.000 | 6.959 | 6.573 | 24.332 | 71.592 | 0.000 | 14.889 | 0.002 | 0.000 | -21.528 | 0.000 | -16.184 | -6.942 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.006 | -46.210 | 0.000 | 0.000 | 4.424 | 4.217 | 15.403 | 41.838 | 0.000 | 0.335 | 0.001 | 0.000 | -14.928 | 0.000 | -0.915 | -4.169 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.077 | -50.819 | 0.000 | 0.000 | 7.046 | 6.714 | 24.333 | 25.005 | 0.000 | 0.819 | 9.957 | 0.000 | -21.147 | 0.000 | -1.985 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.032 | -47.450 | 0.000 | 0.000 | 3.239 | 4.189 | 15.404 | 43.239 | 0.000 | 0.526 | 0.002 | 0.000 | -13.313 | 0.000 | -1.380 | -4.486 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.026 | -77.975 | 0.000 | 0.000 | 6.939 | 6.581 | 24.332 | 71.393 | 0.000 | 0.801 | 0.001 | 0.000 | -20.880 | 0.000 | -2.145 | -9.074 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.043 | -47.145 | 0.000 | 0.000 | 4.441 | 4.226 | 15.403 | 41.721 | 0.000 | 0.521 | 0.000 | 0.000 | -14.538 | 0.000 | -1.385 | -3.287 |
TOPFLOOR_PLENUM | 5.420 | -62.401 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.242 | 59.090 | 0.000 | 0.000 | 0.000 | -3.351 | -0.000 |
MIDFLOOR_PLENUM | 1.850 | -33.136 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.269 | 33.559 | 0.000 | 0.000 | 0.000 | -3.542 | -0.000 |
FIRSTFLOOR_PLENUM | 0.721 | -39.878 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.983 | 41.050 | 0.000 | 0.000 | 0.000 | -2.876 | -0.000 |
Total Facility | 7.990 | -135.415 | 4.689 | -1339.271 | 0.000 | 0.000 | 166.196 | 231.883 | 705.434 | 545.163 | 0.000 | 25.435 | 160.267 | 0.000 | -206.857 | 0.000 | -43.634 | -121.868 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 30-MAY-05:12 | 0.00 | 0.00 | 0.00 | -41666.40 | 0.00 | 0.00 | 313.61 | 548.43 | 4989.51 | 0.00 | 0.00 | 0.00 | 35814.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-SEP-05:14 | 0.00 | 0.00 | 0.00 | -33893.68 | 0.00 | 0.00 | 315.76 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 30003.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 21-AUG-04:02 | 0.00 | 0.00 | 0.00 | -34417.32 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 31763.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-17:51 | 0.00 | 0.00 | 0.00 | -13837.81 | 0.00 | 0.00 | 0.00 | 27.57 | 386.10 | 3664.84 | 0.00 | 647.38 | 9111.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JUL-09:32 | 0.00 | 0.00 | 0.00 | -13189.43 | 0.00 | 0.00 | 14.32 | 17.46 | 302.86 | 6902.62 | 0.00 | 20.73 | 5931.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 15-OCT-12:52 | 0.00 | 0.00 | 0.00 | -16777.38 | 0.00 | 0.00 | 22.52 | 27.57 | 478.41 | 11615.87 | 0.00 | 58.18 | 4574.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 13-AUG-16:51 | 0.00 | 0.00 | 0.00 | -15177.12 | 0.00 | 0.00 | 10.11 | 17.46 | 302.86 | 8807.22 | 0.00 | 387.66 | 5651.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 27-AUG-17:41 | 0.00 | 0.00 | 0.00 | -11320.41 | 0.00 | 0.00 | 0.00 | 27.57 | 386.10 | 2365.26 | 0.00 | 242.44 | 8299.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 30-JUL-09:31 | 0.00 | 0.00 | 0.00 | -11710.18 | 0.00 | 0.00 | 14.89 | 17.46 | 302.86 | 7609.05 | 0.00 | 24.18 | 3741.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 28-JUN-17:00 | 0.00 | 0.00 | 0.00 | -14112.90 | 0.00 | 0.00 | 155.92 | 275.75 | 797.35 | 3220.32 | 0.00 | 14496.51 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4832.95 |
PERIMETER_BOT_ZN_4 | 27-AUG-17:41 | 0.00 | 0.00 | 0.00 | -12804.52 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 6495.83 | 0.00 | 136.83 | 5909.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-JUL-19:01 | 0.00 | 0.00 | 0.00 | -11705.19 | 0.00 | 0.00 | 0.00 | 31.02 | 386.10 | 2255.61 | 0.00 | 295.40 | 8737.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 30-JUL-09:31 | 0.00 | 0.00 | 0.00 | -13087.00 | 0.00 | 0.00 | 13.68 | 17.46 | 302.86 | 7534.41 | 0.00 | 31.79 | 5186.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 25-DEC-13:52 | 0.00 | 0.00 | 0.00 | -14631.47 | 0.00 | 0.00 | 23.13 | 27.57 | 478.41 | 13030.32 | 0.00 | 0.00 | 1114.64 | 0.00 | -0.00 | 0.00 | -42.60 | 0.00 |
PERIMETER_MID_ZN_4 | 30-JUL-17:32 | 0.00 | 0.00 | 0.00 | -13562.83 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 8749.34 | 0.00 | 353.67 | 4197.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 28-JUN-14:50 | 0.00 | -13236.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.33 | 12930.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 19-JUN-12:03 | 0.00 | -6824.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.13 | 6598.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 19-JUN-12:08 | 0.00 | -7958.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.38 | 7784.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-JUL-04:02 | 0.00 | 9246.30 | 0.00 | -214476.05 | 0.00 | 0.00 | 0.00 | 1072.56 | 14333.92 | 0.00 | 0.00 | 339.55 | 192932.18 | 0.00 | -3448.46 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-07:02 | 0.00 | 0.00 | 11111.87 | 0.00 | 0.00 | 0.00 | 888.56 | 1645.36 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -16671.71 |
CORE_TOP | 02-JAN-06:11 | 0.00 | 0.00 | 25410.84 | 0.00 | 0.00 | 0.00 | 482.40 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29467.59 |
PERIMETER_TOP_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 11247.26 | 0.00 | 0.00 | 0.00 | 110.24 | 115.61 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1903.72 | 0.00 | -47.07 | -10160.22 |
PERIMETER_TOP_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 7994.26 | 0.00 | 0.00 | 0.00 | 69.58 | 73.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1293.98 | 0.00 | -31.80 | -7215.06 |
PERIMETER_TOP_ZN_1 | 02-JAN-06:11 | 0.00 | 0.00 | 11924.98 | 0.00 | 0.00 | 0.00 | 107.20 | 115.61 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2057.65 | 0.00 | -50.58 | -10677.45 |
PERIMETER_TOP_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 7767.11 | 0.00 | 0.00 | 0.00 | 69.08 | 73.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1302.84 | 0.00 | -32.34 | -6978.01 |
PERIMETER_BOT_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 6928.94 | 0.00 | 0.00 | 0.00 | 101.61 | 115.61 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2228.83 | 0.00 | -29.37 | -5525.86 |
PERIMETER_BOT_ZN_2 | 27-MAR-06:01 | 0.00 | 0.00 | 4340.38 | 0.00 | 0.00 | 0.00 | 119.31 | 219.59 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1931.76 | 0.00 | -55.46 | -3095.86 |
PERIMETER_BOT_ZN_1 | 27-MAR-06:10 | 0.00 | 0.00 | 8090.66 | 0.00 | 0.00 | 0.00 | 193.30 | 346.86 | 637.88 | 0.00 | 0.00 | 0.00 | 11236.00 | 0.00 | -2892.69 | 0.00 | -17612.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 13-FEB-07:02 | 0.00 | 0.00 | 4286.36 | 0.00 | 0.00 | 0.00 | 121.17 | 219.57 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1156.12 | 0.00 | -5.72 | -3869.07 |
PERIMETER_MID_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 8727.36 | 0.00 | 0.00 | 0.00 | 103.28 | 115.61 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2177.51 | 0.00 | -44.93 | -7361.70 |
PERIMETER_MID_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 5340.79 | 0.00 | 0.00 | 0.00 | 65.19 | 73.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1479.87 | 0.00 | -30.09 | -4373.02 |
PERIMETER_MID_ZN_1 | 02-JAN-06:11 | 0.00 | 0.00 | 8209.95 | 0.00 | 0.00 | 0.00 | 99.90 | 115.61 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2333.98 | 0.00 | -47.63 | -6681.74 |
PERIMETER_MID_ZN_4 | 18-DEC-06:11 | 0.00 | 0.00 | 5121.37 | 0.00 | 0.00 | 0.00 | 63.03 | 73.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1637.09 | 0.00 | -45.50 | -3978.81 |
TOPFLOOR_PLENUM | 02-JAN-07:02 | 9654.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -88.89 | -9566.08 |
MIDFLOOR_PLENUM | 25-DEC-15:52 | 5368.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.22 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5424.47 |
FIRSTFLOOR_PLENUM | 07-SEP-04:02 | 3843.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5.02 | -3838.66 |
Total Facility | 02-JAN-07:02 | 4626.47 | 4880.53 | 113861.57 | -4880.53 | 0.00 | 0.00 | 4508.80 | 8334.71 | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21429.70 | 0.00 | -17161.78 | -113838.86 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 6.0022 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.5173 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.4116 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.8465 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.0274 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.7597 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.0011 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0770 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.7058 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0767 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.0137 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0747 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0533 | 3.0533 | 0.6381 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2543 | 2.2543 | 0.6380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4869 | 2.4869 | 0.6367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8851 | 0.8851 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7843 | 0.7843 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9776 | 0.9776 | 0.1339 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8935 | 0.8935 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7263 | 0.7263 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6864 | 0.6864 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8090 | 0.8090 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7272 | 0.7272 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7583 | 0.7583 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7461 | 0.7461 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8511 | 0.8511 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8019 | 0.8019 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 6.0022 | 5.5173 | 6.0022 | 1.0770 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.4116 | 4.8465 | 5.4116 | 1.0767 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.0274 | 5.7597 | 6.0274 | 1.0747 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5266 | 1.5266 | 0.6381 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1271 | 1.1271 | 0.6380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2435 | 1.2435 | 0.6367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4425 | 0.4425 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3922 | 0.3922 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4888 | 0.4888 | 0.1339 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4467 | 0.4467 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3632 | 0.3632 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3432 | 0.3432 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4045 | 0.4045 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3636 | 0.3636 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3791 | 0.3791 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3731 | 0.3731 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4255 | 0.4255 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4009 | 0.4009 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.0011 | 1.0770 | 1.0770 | 1.0770 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.7058 | 1.0767 | 1.0767 | 1.0767 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.0137 | 1.0747 | 1.0747 | 1.0747 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 73.67 |
Number of hours cooling loads not met | 518.50 |
Number of hours not met | 592.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 7.23 | 75538.57 | 6.53 | 31873.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 440.47 | 92791.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 231.88 | 25003.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 50.88 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.69 | 838.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 144.32 | 28646.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 117.17 | 9787.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1592.05 |
Natural Gas | 0.00 | 123.70 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1715.74 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.54 |
Space Heating | 1.45 |
Space Cooling | 88.41 |
Fans (All) | 28.97 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 319.55 |
Subtotal | 319.55 |
Natural Gas [MJ/m2] | |
Space Heating | 1.31 |
Service Water Heating | 23.52 |
Miscellaneous (All) | 24.83 |
Subtotal | 24.83 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 13.52 |
Space Heating | 0.80 |
Space Cooling | 25.67 |
Fans (All) | 8.41 |
Service Water Heating | 6.83 |
Receptacle Equipment | 41.12 |
Miscellaneous | 3.66 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 901. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8651.00 | 109.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8745.83 | 14.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8746.00 | 14.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8670.67 | 89.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8600.67 | 159.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8627.33 | 132.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8563.50 | 196.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8735.00 | 25.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8586.33 | 173.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8592.00 | 168.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8577.67 | 182.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8694.00 | 66.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8613.00 | 147.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8642.50 | 117.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8576.00 | 184.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8470.00 | 290.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8735.67 | 24.33 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8751.00 | 9.00 | 0.00 | 0.00 | 0.00 |
Min | 8470.00 | 9.00 | 0.00 | 0.00 | 0.00 |
Max | 8751.00 | 290.00 | 0.00 | 0.00 | 0.00 |
Average | 8643.23 | 116.77 | 0.00 | 0.00 | 0.00 |
Sum | 155578.17 | 2101.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128277.00 | 27.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128299.67 | 4.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24830.67 | 78.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 78.33 | 0.00 | 0.00 | 0.00 |
Average | 34137.24 | 6.09 | 0.00 | 0.00 | 0.00 |
Sum | 614470.33 | 109.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8460.00 | 300.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8511.83 | 248.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8595.83 | 164.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8403.50 | 356.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8359.33 | 400.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8381.67 | 378.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8346.83 | 413.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8410.33 | 349.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8344.00 | 416.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8320.33 | 439.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8343.17 | 416.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8346.50 | 413.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8300.50 | 459.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8324.67 | 435.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8300.83 | 459.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8054.17 | 705.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8461.83 | 298.17 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8462.83 | 297.17 | 0.00 | 0.00 | 0.00 |
Min | 8054.17 | 164.17 | 0.00 | 0.00 | 0.00 |
Max | 8595.83 | 705.83 | 0.00 | 0.00 | 0.00 |
Average | 8373.79 | 386.21 | 0.00 | 0.00 | 0.00 |
Sum | 150728.17 | 6951.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128134.17 | 169.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128195.67 | 108.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128236.50 | 67.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24858.17 | 50.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 13986.83 | 29.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24874.83 | 34.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 13984.33 | 31.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24903.00 | 6.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24713.50 | 195.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24866.17 | 42.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10120.00 | 14.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24877.83 | 31.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 13984.00 | 32.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128236.50 | 195.50 | 0.00 | 0.00 | 0.00 |
Average | 34098.17 | 45.17 | 0.00 | 0.00 | 0.00 |
Sum | 613767.00 | 813.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:04
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.192612E+11 | 36710.82 | 17-JAN-07:01 | 12.83 | 4.51 | 0.199007E+10 | 2606.68 | 23-JAN-14:09 | 21.83 | 11.36 |
February | 0.156793E+11 | 36643.20 | 01-FEB-07:01 | 5.00 | 3.59 | 0.180571E+10 | 2606.74 | 15-FEB-14:00 | 20.00 | 13.98 |
March | 0.205343E+11 | 36932.02 | 17-MAR-06:02 | 14.30 | 9.49 | 0.215891E+10 | 2606.71 | 17-MAR-09:00 | 21.60 | 14.25 |
April | 0.238014E+11 | 40788.52 | 17-APR-05:12 | 14.67 | 9.61 | 0.191818E+10 | 2606.68 | 03-APR-09:30 | 14.67 | 9.61 |
May | 0.266910E+11 | 41665.03 | 30-MAY-05:12 | 18.00 | 8.93 | 0.207824E+10 | 2606.66 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.287579E+11 | 41323.80 | 20-JUN-05:12 | 21.33 | 9.32 | 0.207209E+10 | 2606.67 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.281736E+11 | 41147.92 | 26-JUL-04:03 | 25.00 | 16.63 | 0.192624E+10 | 2606.71 | 28-JUL-13:50 | 29.50 | 20.43 |
August | 0.296813E+11 | 41357.17 | 08-AUG-04:03 | 24.83 | 18.27 | 0.216160E+10 | 2606.78 | 29-AUG-13:39 | 28.67 | 21.18 |
September | 0.270058E+11 | 41134.72 | 26-SEP-05:12 | 19.43 | 15.76 | 0.192101E+10 | 2606.66 | 15-SEP-09:20 | 19.43 | 15.76 |
October | 0.247958E+11 | 40965.64 | 11-OCT-05:12 | 17.67 | 11.75 | 0.199614E+10 | 2606.67 | 17-OCT-09:30 | 25.00 | 10.00 |
November | 0.210650E+11 | 41298.21 | 13-NOV-06:12 | 16.67 | 16.67 | 0.197482E+10 | 2606.76 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.176973E+11 | 35807.55 | 27-DEC-07:02 | 6.17 | 2.23 | 0.192063E+10 | 2606.65 | 13-DEC-10:09 | 6.17 | 2.23 |
Annual Sum or Average | 0.283144E+12 | 0.239236E+11 | ||||||||
Minimum of Months | 0.156793E+11 | 35807.55 | 5.00 | 2.23 | 0.180571E+10 | 2606.65 | 6.17 | 2.23 | ||
Maximum of Months | 0.296813E+11 | 41665.03 | 25.00 | 18.27 | 0.216160E+10 | 2606.78 | 33.33 | 21.18 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179409E+10 | 5938.41 | 31-JAN-16:10 | 29.00 | 10.73 | 0.00 | 0.00 | 01-JAN-00:10 | 29.00 | 10.73 |
February | 0.916679E+09 | 4449.48 | 23-FEB-14:30 | 18.00 | 10.57 | 0.00 | 0.00 | 01-FEB-00:10 | 18.00 | 10.57 |
March | 0.215792E+10 | 7035.79 | 16-MAR-15:30 | 28.80 | 13.83 | 0.00 | 0.00 | 01-MAR-00:10 | 28.80 | 13.83 |
April | 0.607784E+10 | 11030.42 | 14-APR-15:00 | 35.00 | 14.57 | 0.00 | 0.00 | 01-APR-00:10 | 35.00 | 14.57 |
May | 0.781477E+10 | 10927.96 | 15-MAY-15:20 | 36.00 | 15.08 | 0.00 | 0.00 | 01-MAY-00:10 | 36.00 | 15.08 |
June | 0.107930E+11 | 13236.50 | 28-JUN-14:50 | 41.83 | 19.32 | 0.00 | 0.00 | 01-JUN-00:10 | 41.83 | 19.32 |
July | 0.944183E+10 | 12454.49 | 20-JUL-14:20 | 39.33 | 20.22 | 0.00 | 0.00 | 01-JUL-00:10 | 39.33 | 20.22 |
August | 0.927353E+10 | 12454.44 | 25-AUG-15:00 | 41.00 | 17.61 | 0.00 | 0.00 | 01-AUG-00:10 | 41.00 | 17.61 |
September | 0.714283E+10 | 11561.80 | 07-SEP-15:00 | 37.20 | 19.77 | 0.00 | 0.00 | 01-SEP-00:10 | 37.20 | 19.77 |
October | 0.414970E+10 | 10571.24 | 02-OCT-14:10 | 35.00 | 19.69 | 0.00 | 0.00 | 01-OCT-00:10 | 35.00 | 19.69 |
November | 0.191604E+10 | 7036.81 | 01-NOV-15:40 | 28.33 | 15.88 | 0.00 | 0.00 | 01-NOV-00:10 | 28.33 | 15.88 |
December | 0.923817E+09 | 4663.59 | 22-DEC-16:00 | 25.00 | 10.09 | 0.00 | 0.00 | 01-DEC-00:10 | 25.00 | 10.09 |
Annual Sum or Average | 0.624021E+11 | 0.00 | ||||||||
Minimum of Months | 0.916679E+09 | 4449.48 | 18.00 | 10.09 | 0.00 | 0.00 | 18.00 | 10.09 | ||
Maximum of Months | 0.107930E+11 | 13236.50 | 41.83 | 20.22 | 0.00 | 0.00 | 41.83 | 20.22 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.573916E+09 | 2119.65 | 27-JAN-16:50 | 26.17 | 9.31 | 0.00 | 0.00 | 01-JAN-00:10 | 26.17 | 9.31 |
February | 0.273846E+09 | 1132.87 | 01-FEB-16:20 | 15.67 | 6.89 | 0.00 | 0.00 | 01-FEB-00:10 | 15.67 | 6.89 |
March | 0.761367E+09 | 2503.48 | 17-MAR-16:00 | 26.60 | 14.13 | 0.00 | 0.00 | 01-MAR-00:10 | 26.60 | 14.13 |
April | 0.297975E+10 | 4717.09 | 24-APR-15:50 | 33.83 | 13.43 | 0.00 | 0.00 | 01-APR-00:10 | 33.83 | 13.43 |
May | 0.415352E+10 | 5209.64 | 08-MAY-12:08 | 32.17 | 13.12 | 0.00 | 0.00 | 01-MAY-00:10 | 32.17 | 13.12 |
June | 0.582343E+10 | 6824.41 | 19-JUN-12:03 | 37.17 | 17.20 | 0.00 | 0.00 | 01-JUN-00:10 | 37.17 | 17.20 |
July | 0.539106E+10 | 6257.26 | 17-JUL-12:03 | 35.83 | 21.43 | 0.00 | 0.00 | 01-JUL-00:10 | 35.83 | 21.43 |
August | 0.534479E+10 | 6403.73 | 28-AUG-10:10 | 34.33 | 21.40 | 0.00 | 0.00 | 01-AUG-00:10 | 34.33 | 21.40 |
September | 0.438106E+10 | 6526.74 | 11-SEP-06:10 | 21.60 | 18.24 | 0.00 | 0.00 | 01-SEP-00:10 | 21.60 | 18.24 |
October | 0.238389E+10 | 5563.90 | 02-OCT-14:30 | 35.00 | 19.50 | 0.00 | 0.00 | 01-OCT-00:10 | 35.00 | 19.50 |
November | 0.836645E+09 | 2942.80 | 01-NOV-16:00 | 28.00 | 15.72 | 0.00 | 0.00 | 01-NOV-00:10 | 28.00 | 15.72 |
December | 0.232792E+09 | 2626.77 | 05-DEC-07:01 | -0.5 | -4.0 | 0.00 | 0.00 | 01-DEC-00:10 | -0.5 | -4.0 |
Annual Sum or Average | 0.331361E+11 | 0.00 | ||||||||
Minimum of Months | 0.232792E+09 | 1132.87 | -0.5 | -4.0 | 0.00 | 0.00 | -0.5 | -4.0 | ||
Maximum of Months | 0.582343E+10 | 6824.41 | 37.17 | 21.43 | 0.00 | 0.00 | 37.17 | 21.43 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136087E+10 | 2861.17 | 27-JAN-17:00 | 26.00 | 9.22 | 0.00 | 0.00 | 01-JAN-00:10 | 26.00 | 9.22 |
February | 0.709708E+09 | 2413.41 | 01-FEB-07:06 | 5.00 | 3.59 | 0.00 | 0.00 | 01-FEB-00:10 | 5.00 | 3.59 |
March | 0.138071E+10 | 3052.89 | 20-MAR-16:00 | 28.30 | 14.35 | 0.00 | 0.00 | 01-MAR-00:10 | 28.30 | 14.35 |
April | 0.349746E+10 | 4893.94 | 24-APR-12:10 | 31.33 | 12.22 | 0.00 | 0.00 | 01-APR-00:10 | 31.33 | 12.22 |
May | 0.453005E+10 | 5735.95 | 08-MAY-12:08 | 32.17 | 13.12 | 0.00 | 0.00 | 01-MAY-00:10 | 32.17 | 13.12 |
June | 0.594022E+10 | 7958.27 | 19-JUN-12:08 | 37.17 | 17.20 | 0.00 | 0.00 | 01-JUN-00:10 | 37.17 | 17.20 |
July | 0.565528E+10 | 7823.52 | 10-JUL-12:08 | 37.00 | 19.54 | 0.00 | 0.00 | 01-JUL-00:10 | 37.00 | 19.54 |
August | 0.578160E+10 | 6856.77 | 08-AUG-12:09 | 36.83 | 20.66 | 0.00 | 0.00 | 01-AUG-00:10 | 36.83 | 20.66 |
September | 0.503146E+10 | 6682.87 | 05-SEP-06:10 | 20.78 | 19.22 | 0.00 | 0.00 | 01-SEP-00:10 | 20.78 | 19.22 |
October | 0.338057E+10 | 6263.56 | 02-OCT-06:10 | 25.00 | 16.71 | 0.00 | 0.00 | 01-OCT-00:10 | 25.00 | 16.71 |
November | 0.184143E+10 | 3622.86 | 02-NOV-16:00 | 26.00 | 15.13 | 0.00 | 0.00 | 01-NOV-00:10 | 26.00 | 15.13 |
December | 0.768466E+09 | 2549.94 | 26-DEC-17:00 | 23.00 | 10.75 | 0.00 | 0.00 | 01-DEC-00:10 | 23.00 | 10.75 |
Annual Sum or Average | 0.398778E+11 | 0.00 | ||||||||
Minimum of Months | 0.709708E+09 | 2413.41 | 5.00 | 3.59 | 0.00 | 0.00 | 5.00 | 3.59 | ||
Maximum of Months | 0.594022E+10 | 7958.27 | 37.17 | 20.66 | 0.00 | 0.00 | 37.17 | 20.66 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110611E+11 | 13381.13 | 27-JAN-17:00 | 26.00 | 9.22 | 0.195887E+10 | 2606.64 | 23-JAN-14:20 | 26.00 | 9.22 |
February | 0.881102E+10 | 12270.42 | 01-FEB-17:00 | 15.00 | 6.61 | 0.177397E+10 | 2606.65 | 10-FEB-14:09 | 15.83 | 11.90 |
March | 0.120434E+11 | 14065.86 | 20-MAR-16:00 | 28.30 | 14.35 | 0.214115E+10 | 2606.67 | 17-MAR-09:00 | 28.30 | 14.35 |
April | 0.165584E+11 | 30086.33 | 17-APR-05:12 | 14.67 | 9.61 | 0.191373E+10 | 2606.66 | 03-APR-09:30 | 14.67 | 9.61 |
May | 0.193317E+11 | 31164.24 | 30-MAY-05:12 | 18.00 | 8.93 | 0.207533E+10 | 2606.66 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.217794E+11 | 33522.46 | 19-JUN-05:14 | 22.33 | 10.28 | 0.207032E+10 | 2606.67 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.212103E+11 | 32596.07 | 05-JUL-05:14 | 23.00 | 11.31 | 0.192431E+10 | 2606.70 | 21-JUL-09:20 | 31.33 | 20.88 |
August | 0.216701E+11 | 30410.72 | 10-AUG-05:12 | 23.00 | 18.70 | 0.215938E+10 | 2606.70 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.191426E+11 | 33895.12 | 05-SEP-05:14 | 21.63 | 18.84 | 0.191844E+10 | 2606.67 | 22-SEP-09:09 | 24.00 | 17.33 |
October | 0.159680E+11 | 31019.09 | 10-OCT-05:12 | 17.33 | 11.48 | 0.198891E+10 | 2606.67 | 03-OCT-13:39 | 17.33 | 11.48 |
November | 0.120634E+11 | 15550.23 | 03-NOV-06:02 | 15.83 | 12.39 | 0.195957E+10 | 2606.71 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.942404E+10 | 12443.53 | 27-DEC-17:00 | 19.00 | 9.46 | 0.187684E+10 | 2606.66 | 13-DEC-10:09 | 19.00 | 9.46 |
Annual Sum or Average | 0.189064E+12 | 0.237608E+11 | ||||||||
Minimum of Months | 0.881102E+10 | 12270.42 | 14.67 | 6.61 | 0.177397E+10 | 2606.64 | 14.67 | 9.22 | ||
Maximum of Months | 0.217794E+11 | 33895.12 | 28.30 | 18.84 | 0.215938E+10 | 2606.71 | 33.33 | 20.88 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.942789E+10 | 13374.68 | 27-JAN-17:00 | 26.00 | 9.22 | 0.190294E+10 | 2606.63 | 23-JAN-14:20 | 26.00 | 9.22 |
February | 0.766712E+10 | 11812.25 | 22-FEB-17:00 | 20.00 | 11.26 | 0.171354E+10 | 2606.65 | 10-FEB-14:09 | 20.00 | 11.26 |
March | 0.108954E+11 | 15231.44 | 17-MAR-16:00 | 26.60 | 14.13 | 0.209673E+10 | 2606.66 | 14-MAR-13:50 | 26.60 | 14.13 |
April | 0.166616E+11 | 28460.28 | 24-APR-06:02 | 16.50 | 5.42 | 0.190819E+10 | 2606.67 | 03-APR-09:20 | 16.50 | 5.42 |
May | 0.201218E+11 | 33938.38 | 30-MAY-05:12 | 18.00 | 8.93 | 0.207436E+10 | 2606.65 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.238610E+11 | 33752.42 | 12-JUN-05:12 | 20.33 | 10.58 | 0.207085E+10 | 2606.67 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.230263E+11 | 34057.18 | 24-JUL-04:02 | 25.42 | 19.04 | 0.192544E+10 | 2606.72 | 21-JUL-09:09 | 25.42 | 19.04 |
August | 0.230499E+11 | 34407.48 | 21-AUG-04:02 | 25.00 | 16.17 | 0.215970E+10 | 2606.71 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.196785E+11 | 34115.67 | 08-SEP-04:02 | 25.92 | 19.60 | 0.191813E+10 | 2606.67 | 22-SEP-09:09 | 24.00 | 17.33 |
October | 0.147252E+11 | 33886.81 | 02-OCT-04:02 | 26.00 | 17.05 | 0.197192E+10 | 2606.66 | 03-OCT-13:30 | 33.00 | 20.21 |
November | 0.103195E+11 | 15683.42 | 01-NOV-16:00 | 28.00 | 15.72 | 0.191770E+10 | 2606.69 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.775864E+10 | 11985.17 | 22-DEC-17:00 | 24.00 | 9.52 | 0.177043E+10 | 2606.60 | 20-DEC-14:20 | 24.00 | 9.52 |
Annual Sum or Average | 0.187193E+12 | 0.234299E+11 | ||||||||
Minimum of Months | 0.766712E+10 | 11812.25 | 16.50 | 5.42 | 0.171354E+10 | 2606.60 | 16.50 | 5.42 | ||
Maximum of Months | 0.238610E+11 | 34407.48 | 28.00 | 19.60 | 0.215970E+10 | 2606.72 | 33.33 | 20.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160048E+10 | 3018.76 | 31-JAN-16:30 | 29.00 | 10.73 | 0.375169E+09 | 549.49 | 23-JAN-14:20 | 29.00 | 10.73 |
February | 0.123902E+10 | 2266.24 | 22-FEB-16:20 | 20.67 | 11.54 | 0.334540E+09 | 549.48 | 15-FEB-14:00 | 20.67 | 11.54 |
March | 0.213629E+10 | 4246.84 | 16-MAR-16:00 | 28.80 | 13.95 | 0.419512E+09 | 549.50 | 21-MAR-13:20 | 25.17 | 12.74 |
April | 0.442176E+10 | 9334.01 | 30-APR-15:42 | 33.00 | 11.94 | 0.398741E+09 | 549.50 | 12-APR-09:20 | 33.00 | 11.94 |
May | 0.617165E+10 | 11937.29 | 07-MAY-17:32 | 35.33 | 14.08 | 0.437132E+09 | 549.50 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.873191E+10 | 13826.97 | 25-JUN-18:11 | 37.33 | 14.77 | 0.437392E+09 | 549.51 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.800661E+10 | 13837.95 | 16-JUL-17:51 | 36.00 | 21.58 | 0.406804E+09 | 549.52 | 21-JUL-09:09 | 31.17 | 20.71 |
August | 0.748156E+10 | 13829.68 | 13-AUG-16:11 | 38.00 | 20.37 | 0.455770E+09 | 549.51 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.599541E+10 | 13384.96 | 17-SEP-13:43 | 34.50 | 17.78 | 0.404353E+09 | 549.50 | 22-SEP-09:20 | 24.20 | 17.34 |
October | 0.341091E+10 | 11617.89 | 02-OCT-04:02 | 26.00 | 17.05 | 0.403834E+09 | 549.51 | 03-OCT-13:30 | 33.00 | 20.21 |
November | 0.183313E+10 | 4193.77 | 01-NOV-15:30 | 28.50 | 15.96 | 0.385043E+09 | 549.50 | 16-NOV-14:20 | 18.00 | 11.91 |
December | 0.114091E+10 | 2184.89 | 22-DEC-16:40 | 24.33 | 9.71 | 0.339336E+09 | 549.48 | 01-DEC-14:20 | 24.33 | 9.71 |
Annual Sum or Average | 0.521696E+11 | 0.479763E+10 | ||||||||
Minimum of Months | 0.114091E+10 | 2184.89 | 20.67 | 9.71 | 0.334540E+09 | 549.48 | 18.00 | 9.71 | ||
Maximum of Months | 0.873191E+10 | 13837.95 | 38.00 | 21.58 | 0.455770E+09 | 549.52 | 33.33 | 20.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162709E+10 | 3133.03 | 27-JAN-10:30 | 21.00 | 7.83 | 0.255079E+09 | 347.88 | 23-JAN-14:20 | 21.00 | 7.83 |
February | 0.119001E+10 | 3402.12 | 23-FEB-10:30 | 15.00 | 11.05 | 0.229218E+09 | 347.87 | 14-FEB-10:20 | 15.00 | 11.05 |
March | 0.222633E+10 | 4647.96 | 23-MAR-10:20 | 22.33 | 10.61 | 0.279001E+09 | 347.89 | 14-MAR-13:50 | 22.33 | 10.61 |
April | 0.496949E+10 | 11461.85 | 02-APR-09:53 | 26.00 | 11.10 | 0.255292E+09 | 347.90 | 03-APR-09:20 | 25.00 | 9.18 |
May | 0.627556E+10 | 12701.62 | 28-MAY-10:32 | 30.33 | 12.86 | 0.277424E+09 | 348.21 | 11-MAY-09:00 | 30.33 | 12.86 |
June | 0.793782E+10 | 12907.76 | 18-JUN-09:02 | 32.33 | 17.55 | 0.277167E+09 | 348.17 | 08-JUN-09:00 | 32.33 | 17.55 |
July | 0.719792E+10 | 13189.36 | 02-JUL-09:32 | 30.33 | 11.95 | 0.257828E+09 | 348.14 | 28-JUL-09:00 | 31.00 | 20.55 |
August | 0.698582E+10 | 12863.71 | 13-AUG-09:32 | 32.67 | 21.08 | 0.288853E+09 | 348.16 | 01-AUG-09:00 | 32.67 | 21.08 |
September | 0.543126E+10 | 11963.30 | 10-SEP-10:22 | 32.45 | 19.22 | 0.256353E+09 | 348.43 | 08-SEP-09:00 | 32.45 | 19.22 |
October | 0.359836E+10 | 9533.49 | 01-OCT-11:23 | 34.50 | 19.32 | 0.262590E+09 | 347.89 | 17-OCT-09:20 | 24.67 | 9.84 |
November | 0.183623E+10 | 3967.10 | 01-NOV-10:05 | 23.33 | 16.05 | 0.255918E+09 | 347.89 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.103419E+10 | 1987.30 | 01-DEC-10:30 | 18.50 | 8.87 | 0.235962E+09 | 347.88 | 13-DEC-10:20 | 11.67 | 10.42 |
Annual Sum or Average | 0.503101E+11 | 0.313068E+10 | ||||||||
Minimum of Months | 0.103419E+10 | 1987.30 | 15.00 | 7.83 | 0.229218E+09 | 347.87 | 11.67 | 7.83 | ||
Maximum of Months | 0.793782E+10 | 13189.36 | 34.50 | 21.08 | 0.288853E+09 | 348.43 | 32.67 | 21.08 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.624321E+10 | 16453.54 | 29-JAN-14:12 | 24.00 | 9.34 | 0.405054E+09 | 549.67 | 24-JAN-14:00 | 24.00 | 9.34 |
February | 0.334846E+10 | 9635.36 | 28-FEB-14:05 | 18.17 | 7.92 | 0.359514E+09 | 549.62 | 23-FEB-14:39 | 18.17 | 7.92 |
March | 0.418437E+10 | 8834.52 | 16-MAR-13:40 | 27.53 | 13.09 | 0.433093E+09 | 549.52 | 14-MAR-13:50 | 27.53 | 13.09 |
April | 0.655909E+10 | 15361.43 | 30-APR-12:23 | 32.50 | 11.90 | 0.399872E+09 | 549.80 | 12-APR-13:00 | 32.50 | 11.90 |
May | 0.679488E+10 | 14940.12 | 07-MAY-13:32 | 34.67 | 14.00 | 0.436847E+09 | 549.50 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.843813E+10 | 14898.08 | 04-JUN-16:41 | 38.00 | 16.06 | 0.437190E+09 | 549.51 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.819403E+10 | 15146.33 | 30-JUL-15:02 | 38.00 | 18.95 | 0.406769E+09 | 549.71 | 31-JUL-13:00 | 37.00 | 19.00 |
August | 0.881050E+10 | 15461.59 | 13-AUG-16:11 | 38.00 | 20.37 | 0.455929E+09 | 550.31 | 28-AUG-13:09 | 37.83 | 20.53 |
September | 0.842308E+10 | 15691.29 | 10-SEP-13:42 | 34.90 | 19.64 | 0.404927E+09 | 565.17 | 28-SEP-13:50 | 36.83 | 16.07 |
October | 0.752216E+10 | 16777.11 | 15-OCT-12:52 | 30.00 | 12.08 | 0.413119E+09 | 567.30 | 02-OCT-13:09 | 30.00 | 12.08 |
November | 0.577088E+10 | 15906.86 | 19-NOV-14:02 | 26.17 | 11.19 | 0.405305E+09 | 549.66 | 15-NOV-14:00 | 26.17 | 11.19 |
December | 0.459068E+10 | 16511.46 | 25-DEC-13:52 | 26.00 | 12.00 | 0.382981E+09 | 549.67 | 29-DEC-14:00 | 20.00 | 9.12 |
Annual Sum or Average | 0.788795E+11 | 0.494060E+10 | ||||||||
Minimum of Months | 0.334846E+10 | 8834.52 | 18.17 | 7.92 | 0.359514E+09 | 549.50 | 18.17 | 7.92 | ||
Maximum of Months | 0.881050E+10 | 16777.11 | 38.00 | 20.37 | 0.455929E+09 | 567.30 | 37.83 | 20.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.195952E+10 | 10836.12 | 29-JAN-16:12 | 24.67 | 9.41 | 0.241626E+09 | 347.85 | 23-JAN-14:20 | 24.67 | 9.41 |
February | 0.127219E+10 | 6117.18 | 22-FEB-16:30 | 20.50 | 11.47 | 0.215254E+09 | 347.84 | 15-FEB-14:00 | 20.50 | 11.47 |
March | 0.222190E+10 | 10356.69 | 18-MAR-17:42 | 25.78 | 12.29 | 0.267440E+09 | 347.85 | 21-MAR-13:20 | 25.17 | 12.74 |
April | 0.484754E+10 | 14363.99 | 02-APR-16:32 | 31.00 | 12.54 | 0.252996E+09 | 347.86 | 03-APR-09:20 | 25.00 | 9.18 |
May | 0.597990E+10 | 14794.49 | 28-MAY-17:11 | 32.67 | 12.64 | 0.276830E+09 | 347.86 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.760259E+10 | 15136.90 | 25-JUN-17:31 | 38.00 | 15.08 | 0.277024E+09 | 347.86 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.642917E+10 | 15045.33 | 30-JUL-17:01 | 38.00 | 19.22 | 0.257666E+09 | 347.86 | 21-JUL-09:09 | 38.00 | 19.22 |
August | 0.632188E+10 | 15177.24 | 13-AUG-16:51 | 38.00 | 19.94 | 0.288709E+09 | 347.86 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.506027E+10 | 14279.60 | 04-SEP-15:52 | 31.60 | 21.45 | 0.256197E+09 | 347.86 | 22-SEP-09:20 | 24.20 | 17.34 |
October | 0.343862E+10 | 14799.57 | 15-OCT-15:32 | 31.00 | 12.59 | 0.256804E+09 | 347.86 | 03-OCT-13:30 | 31.00 | 12.59 |
November | 0.209747E+10 | 10431.55 | 19-NOV-15:22 | 27.00 | 11.59 | 0.246730E+09 | 347.85 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.124577E+10 | 8891.23 | 25-DEC-15:52 | 26.00 | 12.00 | 0.222926E+09 | 347.84 | 22-DEC-14:50 | 26.00 | 12.00 |
Annual Sum or Average | 0.484768E+11 | 0.306020E+10 | ||||||||
Minimum of Months | 0.124577E+10 | 6117.18 | 20.50 | 9.41 | 0.215254E+09 | 347.84 | 20.00 | 9.18 | ||
Maximum of Months | 0.760259E+10 | 15177.24 | 38.00 | 21.45 | 0.288709E+09 | 347.86 | 38.00 | 20.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.168155E+10 | 2314.49 | 27-JAN-16:30 | 26.50 | 9.48 | 0.387309E+09 | 549.49 | 23-JAN-14:20 | 26.50 | 9.48 |
February | 0.129606E+10 | 1411.59 | 22-FEB-16:20 | 20.67 | 11.54 | 0.339236E+09 | 549.47 | 22-FEB-14:20 | 20.67 | 11.54 |
March | 0.180700E+10 | 2930.28 | 20-MAR-14:30 | 27.70 | 14.31 | 0.421202E+09 | 549.50 | 17-MAR-09:00 | 27.70 | 14.31 |
April | 0.347943E+10 | 4880.50 | 25-APR-15:00 | 33.00 | 15.10 | 0.400238E+09 | 549.50 | 12-APR-09:20 | 33.00 | 15.10 |
May | 0.479630E+10 | 5500.21 | 08-MAY-15:20 | 34.00 | 13.77 | 0.436763E+09 | 549.50 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.715778E+10 | 11111.78 | 25-JUN-18:11 | 37.33 | 14.77 | 0.436997E+09 | 549.51 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.730288E+10 | 11098.37 | 30-JUL-17:31 | 38.00 | 19.05 | 0.406607E+09 | 549.51 | 28-JUL-13:50 | 38.00 | 19.05 |
August | 0.722536E+10 | 11320.29 | 27-AUG-17:41 | 39.17 | 18.06 | 0.455834E+09 | 549.52 | 29-AUG-13:39 | 28.67 | 21.18 |
September | 0.640922E+10 | 11126.25 | 10-SEP-14:02 | 35.18 | 19.78 | 0.404973E+09 | 549.50 | 19-SEP-09:20 | 29.23 | 14.41 |
October | 0.389307E+10 | 9850.74 | 01-OCT-13:43 | 37.00 | 19.01 | 0.416240E+09 | 549.50 | 05-OCT-09:20 | 27.00 | 16.87 |
November | 0.224468E+10 | 3977.72 | 02-NOV-14:00 | 27.00 | 15.44 | 0.404465E+09 | 549.51 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.155093E+10 | 1980.15 | 22-DEC-16:40 | 24.33 | 9.71 | 0.365506E+09 | 549.49 | 22-DEC-14:20 | 24.33 | 9.71 |
Annual Sum or Average | 0.488443E+11 | 0.487537E+10 | ||||||||
Minimum of Months | 0.129606E+10 | 1411.59 | 20.67 | 9.48 | 0.339236E+09 | 549.47 | 20.00 | 9.48 | ||
Maximum of Months | 0.730288E+10 | 11320.29 | 39.17 | 19.78 | 0.455834E+09 | 549.52 | 38.00 | 21.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.178469E+10 | 3026.28 | 27-JAN-10:30 | 21.00 | 7.83 | 0.260314E+09 | 347.88 | 23-JAN-14:20 | 21.00 | 7.83 |
February | 0.121800E+10 | 2775.57 | 23-FEB-10:30 | 15.00 | 11.05 | 0.233133E+09 | 347.87 | 14-FEB-10:20 | 15.00 | 11.05 |
March | 0.192165E+10 | 3706.12 | 23-MAR-10:30 | 22.70 | 10.73 | 0.282087E+09 | 347.88 | 17-MAR-09:00 | 22.70 | 10.73 |
April | 0.436763E+10 | 8732.60 | 23-APR-09:12 | 25.67 | 9.63 | 0.255728E+09 | 347.89 | 28-APR-09:00 | 25.00 | 10.77 |
May | 0.537001E+10 | 10806.94 | 28-MAY-10:32 | 30.33 | 12.86 | 0.277500E+09 | 348.02 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.694028E+10 | 11268.55 | 11-JUN-10:12 | 30.33 | 13.50 | 0.277125E+09 | 348.06 | 02-JUN-09:50 | 30.33 | 13.50 |
July | 0.678280E+10 | 11710.02 | 30-JUL-09:31 | 31.00 | 18.77 | 0.257851E+09 | 348.00 | 28-JUL-09:00 | 31.00 | 18.77 |
August | 0.694401E+10 | 11324.09 | 27-AUG-11:02 | 37.17 | 17.45 | 0.289013E+09 | 348.06 | 10-AUG-09:00 | 37.17 | 17.45 |
September | 0.582091E+10 | 11348.11 | 04-SEP-09:42 | 26.33 | 22.09 | 0.256744E+09 | 352.66 | 05-SEP-08:09 | 24.58 | 20.15 |
October | 0.419777E+10 | 8799.69 | 15-OCT-09:32 | 25.33 | 10.24 | 0.265705E+09 | 347.89 | 17-OCT-09:30 | 25.00 | 10.00 |
November | 0.237495E+10 | 4114.46 | 02-NOV-08:40 | 21.00 | 14.47 | 0.261310E+09 | 347.89 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.145455E+10 | 2681.55 | 26-DEC-10:30 | 19.00 | 8.41 | 0.249334E+09 | 347.88 | 13-DEC-10:20 | 19.00 | 8.41 |
Annual Sum or Average | 0.491772E+11 | 0.316584E+10 | ||||||||
Minimum of Months | 0.121800E+10 | 2681.55 | 15.00 | 7.83 | 0.233133E+09 | 347.87 | 15.00 | 7.83 | ||
Maximum of Months | 0.694401E+10 | 11710.02 | 37.17 | 22.09 | 0.289013E+09 | 352.66 | 37.17 | 20.15 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.560135E+10 | 13519.29 | 29-JAN-14:12 | 24.00 | 9.34 | 0.407540E+09 | 561.13 | 17-JAN-14:39 | 24.00 | 9.34 |
February | 0.206101E+10 | 8649.12 | 28-FEB-13:07 | 17.17 | 7.91 | 0.347182E+09 | 549.51 | 15-FEB-14:00 | 17.17 | 7.91 |
March | 0.295106E+10 | 10168.20 | 16-MAR-16:10 | 28.72 | 13.89 | 0.420988E+09 | 549.52 | 13-MAR-13:09 | 28.72 | 13.89 |
April | 0.625752E+10 | 11838.75 | 14-APR-16:50 | 35.00 | 14.56 | 0.399115E+09 | 623.58 | 14-APR-12:09 | 35.00 | 14.56 |
May | 0.702954E+10 | 12316.66 | 15-MAY-17:00 | 37.00 | 15.57 | 0.438058E+09 | 623.76 | 18-MAY-12:09 | 34.00 | 13.67 |
June | 0.954431E+10 | 14116.75 | 28-JUN-17:00 | 42.00 | 19.33 | 0.445912E+09 | 733.59 | 28-JUN-12:09 | 42.00 | 19.33 |
July | 0.966088E+10 | 13293.42 | 20-JUL-17:00 | 39.00 | 20.23 | 0.414041E+09 | 719.25 | 12-JUL-12:09 | 39.00 | 20.23 |
August | 0.108453E+11 | 13951.28 | 25-AUG-17:00 | 41.00 | 17.61 | 0.467076E+09 | 769.58 | 25-AUG-12:09 | 41.00 | 17.61 |
September | 0.102634E+11 | 13645.94 | 10-SEP-14:02 | 35.18 | 19.78 | 0.416733E+09 | 718.99 | 07-SEP-12:09 | 35.18 | 19.78 |
October | 0.827255E+10 | 13757.08 | 15-OCT-12:52 | 30.00 | 12.08 | 0.423543E+09 | 701.02 | 02-OCT-12:09 | 30.00 | 12.08 |
November | 0.576587E+10 | 13035.81 | 19-NOV-12:53 | 26.00 | 10.91 | 0.409137E+09 | 583.88 | 20-NOV-14:20 | 27.00 | 11.68 |
December | 0.416308E+10 | 13100.04 | 24-DEC-13:32 | 23.67 | 10.24 | 0.382614E+09 | 556.64 | 26-DEC-14:09 | 23.00 | 10.20 |
Annual Sum or Average | 0.824159E+11 | 0.497194E+10 | ||||||||
Minimum of Months | 0.206101E+10 | 8649.12 | 17.17 | 7.91 | 0.347182E+09 | 549.51 | 17.17 | 7.91 | ||
Maximum of Months | 0.108453E+11 | 14116.75 | 42.00 | 20.23 | 0.467076E+09 | 769.58 | 42.00 | 20.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.192522E+10 | 8085.10 | 29-JAN-16:53 | 24.00 | 9.34 | 0.254202E+09 | 347.85 | 23-JAN-14:20 | 24.00 | 9.34 |
February | 0.118519E+10 | 4535.67 | 22-FEB-16:30 | 20.50 | 11.47 | 0.222626E+09 | 347.85 | 14-FEB-14:20 | 20.50 | 11.47 |
March | 0.180705E+10 | 6686.44 | 18-MAR-17:42 | 25.78 | 12.29 | 0.273713E+09 | 347.85 | 17-MAR-09:20 | 25.78 | 12.29 |
April | 0.413827E+10 | 11623.41 | 23-APR-17:11 | 32.67 | 12.49 | 0.255091E+09 | 347.85 | 24-APR-09:20 | 26.33 | 10.70 |
May | 0.500721E+10 | 11931.19 | 29-MAY-17:51 | 31.00 | 13.66 | 0.277234E+09 | 347.86 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.659584E+10 | 12117.00 | 11-JUN-17:31 | 34.00 | 15.03 | 0.277024E+09 | 347.86 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.599000E+10 | 12198.77 | 30-JUL-17:31 | 38.00 | 19.05 | 0.257719E+09 | 347.86 | 28-JUL-13:50 | 38.00 | 19.05 |
August | 0.624148E+10 | 12804.43 | 27-AUG-17:41 | 39.17 | 18.06 | 0.288884E+09 | 347.87 | 29-AUG-13:39 | 28.67 | 21.18 |
September | 0.541990E+10 | 11711.76 | 04-SEP-17:01 | 31.60 | 21.23 | 0.256681E+09 | 347.86 | 15-SEP-09:20 | 25.90 | 16.61 |
October | 0.386835E+10 | 11826.28 | 15-OCT-15:32 | 31.00 | 12.59 | 0.264990E+09 | 347.86 | 10-OCT-09:20 | 31.00 | 12.59 |
November | 0.249265E+10 | 6653.50 | 20-NOV-16:30 | 26.50 | 12.08 | 0.259603E+09 | 347.86 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.153983E+10 | 7519.24 | 24-DEC-16:12 | 22.67 | 10.02 | 0.240550E+09 | 347.85 | 26-DEC-10:20 | 18.67 | 8.27 |
Annual Sum or Average | 0.462110E+11 | 0.312832E+10 | ||||||||
Minimum of Months | 0.118519E+10 | 4535.67 | 20.50 | 9.34 | 0.222626E+09 | 347.85 | 18.67 | 8.27 | ||
Maximum of Months | 0.659584E+10 | 12804.43 | 39.17 | 21.23 | 0.288884E+09 | 347.87 | 38.00 | 21.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184228E+10 | 2979.04 | 31-JAN-16:30 | 29.00 | 10.73 | 0.390423E+09 | 549.49 | 23-JAN-14:20 | 29.00 | 10.73 |
February | 0.142629E+10 | 2224.35 | 22-FEB-16:20 | 20.67 | 11.54 | 0.349366E+09 | 549.49 | 15-FEB-14:00 | 20.67 | 11.54 |
March | 0.228483E+10 | 4048.44 | 20-MAR-14:30 | 27.70 | 14.31 | 0.432923E+09 | 549.50 | 23-MAR-13:20 | 25.17 | 11.90 |
April | 0.428045E+10 | 5746.97 | 25-APR-15:00 | 33.00 | 15.10 | 0.401617E+09 | 549.50 | 10-APR-09:20 | 33.00 | 15.10 |
May | 0.584113E+10 | 9859.37 | 21-MAY-17:41 | 31.17 | 13.16 | 0.437585E+09 | 549.50 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.799472E+10 | 11666.01 | 25-JUN-18:11 | 37.33 | 14.77 | 0.437412E+09 | 550.37 | 19-JUN-13:20 | 37.33 | 14.77 |
July | 0.733755E+10 | 11705.37 | 04-JUL-19:01 | 35.50 | 14.61 | 0.406762E+09 | 549.51 | 21-JUL-09:20 | 31.33 | 20.88 |
August | 0.699192E+10 | 11608.98 | 27-AUG-18:31 | 37.67 | 18.06 | 0.455799E+09 | 549.51 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.573945E+10 | 11305.47 | 17-SEP-16:52 | 34.40 | 17.12 | 0.404719E+09 | 549.50 | 05-SEP-09:20 | 34.40 | 17.12 |
October | 0.352031E+10 | 9576.26 | 02-OCT-04:02 | 26.00 | 17.05 | 0.412245E+09 | 549.51 | 03-OCT-13:39 | 33.00 | 20.21 |
November | 0.209143E+10 | 3942.97 | 02-NOV-14:00 | 27.00 | 15.44 | 0.397996E+09 | 549.50 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.146882E+10 | 2230.54 | 22-DEC-16:50 | 24.17 | 9.62 | 0.357503E+09 | 549.48 | 22-DEC-14:20 | 24.17 | 9.62 |
Annual Sum or Average | 0.508192E+11 | 0.488435E+10 | ||||||||
Minimum of Months | 0.142629E+10 | 2224.35 | 20.67 | 9.62 | 0.349366E+09 | 549.48 | 20.00 | 9.62 | ||
Maximum of Months | 0.799472E+10 | 11705.37 | 37.67 | 18.06 | 0.455799E+09 | 550.37 | 37.33 | 20.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174422E+10 | 4385.30 | 27-JAN-11:05 | 22.33 | 7.96 | 0.191187E+09 | 356.46 | 26-JAN-13:09 | 22.33 | 7.96 |
February | 0.126919E+10 | 5716.46 | 24-FEB-13:01 | 14.17 | 9.26 | 0.172197E+09 | 356.46 | 10-FEB-15:09 | 14.17 | 9.26 |
March | 0.223263E+10 | 5956.25 | 23-MAR-10:05 | 21.97 | 10.49 | 0.208317E+09 | 356.46 | 16-MAR-10:09 | 21.97 | 10.49 |
April | 0.466511E+10 | 11508.67 | 09-APR-08:53 | 23.00 | 8.57 | 0.189844E+09 | 356.47 | 28-APR-10:09 | 25.17 | 10.76 |
May | 0.579446E+10 | 12607.60 | 21-MAY-09:02 | 27.33 | 11.56 | 0.206096E+09 | 356.47 | 22-MAY-10:09 | 25.33 | 9.96 |
June | 0.719587E+10 | 12677.00 | 11-JUN-08:52 | 28.00 | 12.26 | 0.205697E+09 | 356.47 | 19-JUN-10:09 | 34.17 | 14.95 |
July | 0.650059E+10 | 13087.00 | 30-JUL-09:31 | 31.00 | 18.77 | 0.191936E+09 | 356.46 | 03-JUL-14:09 | 31.00 | 18.77 |
August | 0.637334E+10 | 12984.38 | 27-AUG-09:11 | 33.67 | 16.18 | 0.214265E+09 | 356.46 | 14-AUG-10:09 | 33.67 | 16.18 |
September | 0.503941E+10 | 12506.75 | 10-SEP-10:12 | 32.17 | 19.22 | 0.190578E+09 | 356.46 | 22-SEP-10:09 | 25.37 | 17.42 |
October | 0.354006E+10 | 8536.37 | 01-OCT-11:13 | 34.33 | 19.35 | 0.196058E+09 | 356.46 | 18-OCT-10:09 | 26.33 | 11.01 |
November | 0.194071E+10 | 5289.67 | 01-NOV-10:05 | 23.33 | 16.05 | 0.191741E+09 | 356.47 | 22-NOV-11:09 | 19.33 | 11.05 |
December | 0.115421E+10 | 4780.55 | 13-DEC-13:02 | 15.17 | 9.27 | 0.180136E+09 | 356.46 | 15-DEC-15:09 | 13.83 | 5.31 |
Annual Sum or Average | 0.474498E+11 | 0.233805E+10 | ||||||||
Minimum of Months | 0.115421E+10 | 4385.30 | 14.17 | 7.96 | 0.172197E+09 | 356.46 | 13.83 | 5.31 | ||
Maximum of Months | 0.719587E+10 | 13087.00 | 34.33 | 19.35 | 0.214265E+09 | 356.47 | 34.17 | 18.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.666535E+10 | 14175.44 | 15-JAN-13:42 | 22.67 | 10.33 | 0.412566E+09 | 562.97 | 30-JAN-14:39 | 24.67 | 9.55 |
February | 0.366541E+10 | 9643.37 | 26-FEB-14:33 | 17.00 | 9.86 | 0.368579E+09 | 549.85 | 23-FEB-14:50 | 17.00 | 9.86 |
March | 0.438962E+10 | 8458.48 | 23-MAR-13:50 | 25.42 | 11.73 | 0.442447E+09 | 550.14 | 23-MAR-13:20 | 25.42 | 11.73 |
April | 0.630660E+10 | 13459.28 | 30-APR-13:23 | 34.00 | 12.40 | 0.402524E+09 | 550.66 | 25-APR-13:20 | 34.00 | 12.40 |
May | 0.640451E+10 | 11065.48 | 21-MAY-16:21 | 32.00 | 13.36 | 0.437605E+09 | 549.50 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.771154E+10 | 12703.69 | 04-JUN-16:41 | 38.00 | 16.06 | 0.437215E+09 | 549.98 | 19-JUN-13:20 | 38.33 | 18.31 |
July | 0.751113E+10 | 13370.08 | 30-JUL-12:12 | 36.00 | 18.60 | 0.406746E+09 | 550.39 | 31-JUL-13:20 | 37.00 | 19.00 |
August | 0.823713E+10 | 13266.76 | 27-AUG-15:11 | 40.00 | 18.27 | 0.456024E+09 | 550.85 | 28-AUG-13:20 | 37.67 | 20.48 |
September | 0.806835E+10 | 13902.38 | 24-SEP-12:22 | 31.90 | 18.33 | 0.405455E+09 | 580.73 | 28-SEP-13:50 | 36.83 | 16.07 |
October | 0.758621E+10 | 13758.92 | 09-OCT-13:12 | 31.33 | 17.32 | 0.418592E+09 | 583.75 | 02-OCT-13:20 | 31.33 | 17.32 |
November | 0.618797E+10 | 14054.75 | 19-NOV-13:22 | 26.00 | 11.02 | 0.411461E+09 | 567.41 | 01-NOV-13:00 | 26.00 | 11.02 |
December | 0.524237E+10 | 14631.30 | 25-DEC-13:52 | 26.00 | 12.00 | 0.392431E+09 | 551.90 | 22-DEC-14:09 | 26.00 | 12.00 |
Annual Sum or Average | 0.779762E+11 | 0.499165E+10 | ||||||||
Minimum of Months | 0.366541E+10 | 8458.48 | 17.00 | 9.86 | 0.368579E+09 | 549.50 | 17.00 | 9.55 | ||
Maximum of Months | 0.823713E+10 | 14631.30 | 40.00 | 18.60 | 0.456024E+09 | 583.75 | 38.33 | 20.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.211607E+10 | 6417.46 | 15-JAN-16:23 | 22.50 | 9.88 | 0.251032E+09 | 347.85 | 23-JAN-14:20 | 21.67 | 11.33 |
February | 0.140632E+10 | 5992.51 | 22-FEB-16:30 | 20.50 | 11.47 | 0.223974E+09 | 347.85 | 10-FEB-14:00 | 20.50 | 11.47 |
March | 0.230867E+10 | 9216.68 | 18-MAR-17:42 | 25.78 | 12.29 | 0.275643E+09 | 347.85 | 17-MAR-09:20 | 25.78 | 12.29 |
April | 0.465283E+10 | 12830.65 | 30-APR-16:42 | 32.17 | 11.84 | 0.254803E+09 | 347.86 | 10-APR-09:20 | 32.17 | 11.84 |
May | 0.565729E+10 | 13186.15 | 21-MAY-17:01 | 31.83 | 13.32 | 0.277273E+09 | 347.86 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.705504E+10 | 13368.37 | 25-JUN-17:31 | 38.00 | 15.08 | 0.277047E+09 | 347.86 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.593011E+10 | 13562.85 | 30-JUL-17:32 | 38.00 | 19.05 | 0.257665E+09 | 347.86 | 21-JUL-09:20 | 38.00 | 19.05 |
August | 0.592840E+10 | 13492.58 | 27-AUG-16:31 | 40.00 | 18.00 | 0.288745E+09 | 347.86 | 28-AUG-09:20 | 32.00 | 20.57 |
September | 0.484786E+10 | 12948.45 | 04-SEP-15:41 | 31.60 | 21.45 | 0.256407E+09 | 347.86 | 05-SEP-09:20 | 26.07 | 20.24 |
October | 0.347550E+10 | 12062.18 | 15-OCT-16:22 | 30.50 | 12.33 | 0.261831E+09 | 347.86 | 03-OCT-13:39 | 30.50 | 12.33 |
November | 0.228228E+10 | 10691.06 | 19-NOV-15:22 | 27.00 | 11.59 | 0.254280E+09 | 347.86 | 16-NOV-14:20 | 27.00 | 11.59 |
December | 0.148557E+10 | 9978.23 | 25-DEC-15:52 | 26.00 | 12.00 | 0.232977E+09 | 347.84 | 12-DEC-14:39 | 26.00 | 12.00 |
Annual Sum or Average | 0.471459E+11 | 0.311168E+10 | ||||||||
Minimum of Months | 0.140632E+10 | 5992.51 | 20.50 | 9.88 | 0.223974E+09 | 347.84 | 20.50 | 11.33 | ||
Maximum of Months | 0.705504E+10 | 13562.85 | 40.00 | 21.45 | 0.288745E+09 | 347.86 | 38.00 | 20.57 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.873676E+09 | 9655.34 | 02-JAN-07:02 | 6.00 |
February | 0.754877E+09 | 4686.77 | 13-FEB-07:02 | 8.33 |
March | 0.767907E+09 | 6585.93 | 27-MAR-06:01 | 1.97 |
April | 0.335284E+09 | 2991.98 | 21-APR-05:03 | 8.17 |
May | 0.182737E+09 | 4441.92 | 22-MAY-05:12 | 15.33 |
June | 50841456.48 | 3642.24 | 12-JUN-05:12 | 20.33 |
July | 32376074.84 | 4743.88 | 10-JUL-04:02 | 26.83 |
August | 32847917.09 | 4938.47 | 21-AUG-04:02 | 25.00 |
September | 58678403.38 | 4241.09 | 18-SEP-04:02 | 25.42 |
October | 0.470186E+09 | 3867.93 | 02-OCT-04:02 | 26.00 |
November | 0.659229E+09 | 5646.38 | 24-NOV-07:01 | 4.50 |
December | 0.120086E+10 | 9543.25 | 07-DEC-07:01 | 1.33 |
Annual Sum or Average | 0.541950E+10 | |||
Minimum of Months | 32376074.84 | 2991.98 | 1.33 | |
Maximum of Months | 0.120086E+10 | 9655.34 | 26.83 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.321733E+09 | 4097.56 | 15-JAN-16:23 | 22.50 |
February | 0.340563E+09 | 2976.27 | 26-FEB-14:33 | 17.00 |
March | 0.190697E+09 | 2169.89 | 26-MAR-15:50 | 18.12 |
April | 27000675.95 | 3221.45 | 02-APR-14:53 | 31.00 |
May | 23279716.35 | 2683.04 | 21-MAY-17:01 | 31.83 |
June | 19685782.02 | 2714.27 | 11-JUN-16:51 | 34.00 |
July | 25806340.08 | 2772.68 | 30-JUL-14:51 | 38.00 |
August | 19176484.65 | 2628.35 | 27-AUG-15:11 | 40.00 |
September | 18004233.54 | 2614.81 | 24-SEP-14:22 | 33.55 |
October | 50378602.74 | 3411.70 | 15-OCT-15:42 | 31.00 |
November | 0.165477E+09 | 5207.88 | 19-NOV-15:22 | 27.00 |
December | 0.647926E+09 | 5368.32 | 25-DEC-15:52 | 26.00 |
Annual Sum or Average | 0.184973E+10 | |||
Minimum of Months | 18004233.54 | 2169.89 | 17.00 | |
Maximum of Months | 0.647926E+09 | 5368.32 | 40.00 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138963E+09 | 3115.97 | 29-JAN-16:12 | 24.67 |
February | 90717543.56 | 2160.31 | 13-FEB-08:04 | 10.17 |
March | 35771741.69 | 1789.30 | 27-MAR-07:06 | 4.73 |
April | 20204701.41 | 2212.46 | 23-APR-15:51 | 33.30 |
May | 17498528.52 | 1652.43 | 07-MAY-16:01 | 36.00 |
June | 19492170.53 | 2842.80 | 29-JUN-04:02 | 28.00 |
July | 31570401.63 | 3510.07 | 12-JUL-04:02 | 27.83 |
August | 25907423.54 | 3491.17 | 16-AUG-04:02 | 28.17 |
September | 31568785.94 | 3844.10 | 07-SEP-04:02 | 26.10 |
October | 40871628.35 | 2945.71 | 15-OCT-14:52 | 31.00 |
November | 51968709.78 | 3324.56 | 26-NOV-16:13 | 18.67 |
December | 0.216052E+09 | 3553.93 | 10-DEC-14:02 | 21.00 |
Annual Sum or Average | 0.720587E+09 | |||
Minimum of Months | 17498528.52 | 1652.43 | 4.73 | |
Maximum of Months | 0.216052E+09 | 3844.10 | 36.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1333415.45 | 11111.80 | 02-JAN-07:02 | 6.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 1333415.45 | |||
Minimum of Months | 0.00 | 0.00 | 6.00 | |
Maximum of Months | 1333415.45 | 11111.80 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 47296178.72 | 25413.81 | 02-JAN-06:11 | 4.67 |
February | 5303772.57 | 22796.38 | 13-FEB-07:02 | 8.33 |
March | 1384239.45 | 20763.59 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 1209735.35 | 14113.58 | 24-NOV-07:01 | 4.50 |
December | 33339579.22 | 23491.73 | 18-DEC-07:01 | 3.33 |
Annual Sum or Average | 88533505.31 | |||
Minimum of Months | 0.00 | 0.00 | 1.97 | |
Maximum of Months | 47296178.72 | 25413.81 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109413E+09 | 11247.06 | 02-JAN-06:11 | 4.67 |
February | 82554551.98 | 10035.70 | 13-FEB-06:12 | 8.00 |
March | 63180902.91 | 10202.03 | 27-MAR-05:12 | 2.33 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 4919721.54 | 9123.95 | 26-OCT-06:02 | 8.17 |
November | 53624761.91 | 10225.85 | 24-NOV-06:12 | 3.33 |
December | 0.355600E+09 | 10836.97 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 0.669292E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 0.355600E+09 | 11247.06 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 45145025.54 | 7994.07 | 02-JAN-06:11 | 4.67 |
February | 31159546.56 | 6824.30 | 13-FEB-06:12 | 8.00 |
March | 26462183.86 | 6963.73 | 27-MAR-05:12 | 2.33 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 2614768.52 | 5490.26 | 26-OCT-06:02 | 8.17 |
November | 16263196.12 | 7056.50 | 24-NOV-06:12 | 3.33 |
December | 0.144511E+09 | 7641.36 | 07-DEC-06:01 | -0.7 |
Annual Sum or Average | 0.266156E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 0.144511E+09 | 7994.07 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 49536385.92 | 11924.76 | 02-JAN-06:11 | 4.67 |
February | 41774396.23 | 10839.66 | 13-FEB-06:12 | 8.00 |
March | 44461436.35 | 10911.91 | 27-MAR-05:12 | 2.33 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 1877237.35 | 6102.34 | 26-OCT-06:02 | 8.17 |
November | 18202572.90 | 10874.19 | 24-NOV-06:12 | 3.33 |
December | 0.175184E+09 | 11697.43 | 07-DEC-06:01 | -0.7 |
Annual Sum or Average | 0.331036E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 0.175184E+09 | 11924.76 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 60037184.81 | 7766.91 | 02-JAN-06:11 | 4.67 |
February | 48227561.85 | 6769.15 | 13-FEB-06:12 | 8.00 |
March | 33967705.97 | 6630.00 | 27-MAR-05:12 | 2.33 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 2402406.90 | 5045.40 | 26-OCT-06:02 | 8.17 |
November | 28725138.88 | 6721.10 | 24-NOV-06:12 | 3.33 |
December | 0.211956E+09 | 7450.23 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 0.385316E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 0.211956E+09 | 7766.91 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15422228.01 | 6928.96 | 02-JAN-06:11 | 4.67 |
February | 4045693.61 | 6512.36 | 13-FEB-07:02 | 8.33 |
March | 7043511.78 | 6528.19 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 8974288.34 | 6431.41 | 06-DEC-07:01 | -0.5 |
Annual Sum or Average | 35485721.76 | |||
Minimum of Months | 0.00 | 0.00 | -0.5 | |
Maximum of Months | 15422228.01 | 6928.96 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2896637.57 | 4337.58 | 02-JAN-06:11 | 4.67 |
February | 657753.61 | 4297.31 | 13-FEB-07:02 | 8.33 |
March | 467858.00 | 4340.37 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 1062657.61 | 4044.36 | 06-DEC-07:01 | -0.5 |
Annual Sum or Average | 5084906.79 | |||
Minimum of Months | 0.00 | 0.00 | -0.5 | |
Maximum of Months | 2896637.57 | 4340.37 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.480272E+09 | 7460.15 | 02-JAN-07:10 | 6.00 |
February | 0.514122E+09 | 7477.67 | 08-FEB-07:10 | 6.17 |
March | 0.593478E+09 | 8090.62 | 27-MAR-06:10 | 1.97 |
April | 93053251.06 | 6678.93 | 21-APR-06:10 | 9.33 |
May | 3404943.89 | 5582.21 | 01-MAY-06:06 | 13.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.196085E+09 | 7181.49 | 25-OCT-06:55 | 5.00 |
November | 0.263766E+09 | 7242.08 | 24-NOV-07:10 | 4.50 |
December | 0.579134E+09 | 7984.24 | 07-DEC-07:10 | 1.33 |
Annual Sum or Average | 0.272332E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.33 | |
Maximum of Months | 0.593478E+09 | 8090.62 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2896405.79 | 3928.39 | 02-JAN-07:02 | 6.00 |
February | 1197186.48 | 4286.39 | 13-FEB-07:02 | 8.33 |
March | 239751.91 | 3528.44 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 1560782.86 | 4263.14 | 18-DEC-07:01 | 3.33 |
Annual Sum or Average | 5894127.05 | |||
Minimum of Months | 0.00 | 0.00 | 1.97 | |
Maximum of Months | 2896405.79 | 4286.39 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20274476.22 | 8727.34 | 02-JAN-06:11 | 4.67 |
February | 4404755.55 | 7847.17 | 13-FEB-07:02 | 8.33 |
March | 4896338.45 | 8031.24 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 2079177.60 | 7903.61 | 24-NOV-07:01 | 4.50 |
December | 45273532.94 | 8325.50 | 07-DEC-06:01 | -0.7 |
Annual Sum or Average | 76928280.76 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 45273532.94 | 8727.34 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8749336.96 | 5340.79 | 02-JAN-06:11 | 4.67 |
February | 2082976.55 | 4992.39 | 13-FEB-07:02 | 8.33 |
March | 2286053.65 | 4694.08 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 505187.51 | 4846.55 | 24-NOV-07:01 | 4.50 |
December | 17887248.69 | 5184.16 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 31510803.36 | |||
Minimum of Months | 0.00 | 0.00 | 1.97 | |
Maximum of Months | 17887248.69 | 5340.79 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7502131.35 | 8209.95 | 02-JAN-06:11 | 4.67 |
February | 1916638.86 | 7624.49 | 13-FEB-07:02 | 8.33 |
March | 1894474.24 | 7708.10 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 263699.63 | 3076.50 | 24-NOV-07:01 | 4.50 |
December | 14817984.67 | 7860.31 | 07-DEC-07:01 | 1.33 |
Annual Sum or Average | 26394928.75 | |||
Minimum of Months | 0.00 | 0.00 | 1.33 | |
Maximum of Months | 14817984.67 | 8209.95 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10285828.74 | 5108.28 | 02-JAN-06:11 | 4.67 |
February | 2514910.76 | 4953.78 | 13-FEB-07:02 | 8.33 |
March | 1765959.62 | 4449.95 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 698727.89 | 5020.79 | 24-NOV-07:01 | 4.50 |
December | 27610891.47 | 5121.35 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 42876318.48 | |||
Minimum of Months | 0.00 | 0.00 | 1.97 | |
Maximum of Months | 27610891.47 | 5121.35 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.610952E+09 | 936.57 | 20-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.539142E+09 | 882.29 | 03-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.597988E+09 | 822.97 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.514258E+09 | 562.54 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.542364E+09 | 541.02 | 26-MAY-08:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.528490E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.501483E+09 | 554.53 | 13-JUL-15:00 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.575332E+09 | 830.38 | 04-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.525806E+09 | 732.67 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.580332E+09 | 904.34 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.595063E+09 | 1040.56 | 28-NOV-16:30 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.603287E+09 | 1040.56 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.671450E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.501483E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.610952E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.371321E+09 | 586.68 | 20-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.332325E+09 | 534.53 | 10-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.374427E+09 | 423.96 | 09-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.323480E+09 | 314.23 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.345048E+09 | 333.34 | 25-MAY-15:30 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.337076E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.320085E+09 | 355.84 | 13-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.363290E+09 | 510.72 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330923E+09 | 354.29 | 29-SEP-14:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.355755E+09 | 444.69 | 31-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.366511E+09 | 658.76 | 28-NOV-16:30 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.368456E+09 | 658.76 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.418870E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.320085E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.374427E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.573550E+09 | 913.98 | 20-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.517979E+09 | 859.84 | 10-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.588394E+09 | 790.64 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.516185E+09 | 567.18 | 04-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.548962E+09 | 541.02 | 26-MAY-08:30 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.536840E+09 | 534.49 | 27-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.509558E+09 | 558.75 | 27-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.578700E+09 | 834.63 | 04-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.523329E+09 | 572.72 | 19-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.552728E+09 | 762.77 | 27-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.567317E+09 | 1040.56 | 28-NOV-16:30 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.567633E+09 | 1040.56 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.658118E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.509558E+09 | 534.49 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.588394E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.378440E+09 | 599.94 | 20-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.336477E+09 | 559.16 | 03-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.376970E+09 | 562.81 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.326273E+09 | 453.51 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.346612E+09 | 354.31 | 26-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.338181E+09 | 340.64 | 27-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.321171E+09 | 413.50 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.365955E+09 | 534.18 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.333344E+09 | 505.27 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.361260E+09 | 579.73 | 27-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.368715E+09 | 658.71 | 28-NOV-16:30 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.372170E+09 | 658.71 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.422557E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.321171E+09 | 340.64 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.378440E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.607825E+09 | 932.11 | 20-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.537237E+09 | 876.58 | 03-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.596099E+09 | 814.01 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.513490E+09 | 559.51 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.542194E+09 | 536.25 | 26-MAY-08:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.528348E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.501035E+09 | 550.41 | 13-JUL-15:00 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.574214E+09 | 822.32 | 04-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.524896E+09 | 720.36 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.578027E+09 | 897.00 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.592506E+09 | 1040.56 | 28-NOV-16:30 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.600411E+09 | 1040.56 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.669628E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.501035E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.607825E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.370230E+09 | 584.46 | 20-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.331539E+09 | 530.44 | 10-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.373845E+09 | 417.46 | 09-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.323238E+09 | 314.23 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.344785E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.336646E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.319635E+09 | 353.69 | 13-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.362774E+09 | 505.88 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330506E+09 | 352.49 | 29-SEP-14:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.355169E+09 | 439.93 | 31-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.365513E+09 | 658.76 | 28-NOV-16:30 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.367164E+09 | 658.76 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.418104E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.319635E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.373845E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.573239E+09 | 909.02 | 20-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.517277E+09 | 852.78 | 10-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.587601E+09 | 780.38 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.515579E+09 | 564.44 | 04-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.548265E+09 | 536.25 | 26-MAY-08:30 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.535991E+09 | 531.51 | 27-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.508394E+09 | 556.53 | 27-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.577602E+09 | 826.78 | 04-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.522725E+09 | 569.52 | 19-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.552347E+09 | 751.35 | 27-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.566873E+09 | 1040.56 | 28-NOV-16:30 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.567214E+09 | 1040.56 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.657311E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.508394E+09 | 531.51 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.587601E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.376899E+09 | 597.87 | 20-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335704E+09 | 556.20 | 03-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.376203E+09 | 559.89 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.325742E+09 | 445.83 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.346151E+09 | 352.20 | 26-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.337782E+09 | 339.09 | 27-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.320629E+09 | 406.40 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.365251E+09 | 530.38 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.332714E+09 | 500.59 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.360387E+09 | 576.71 | 27-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.367973E+09 | 658.71 | 28-NOV-16:30 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.371215E+09 | 658.71 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.421665E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.320629E+09 | 339.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.376899E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.610951E+09 | 936.56 | 20-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.539141E+09 | 882.29 | 03-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.597987E+09 | 822.95 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.514257E+09 | 562.53 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.542364E+09 | 541.00 | 26-MAY-08:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.528490E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.501482E+09 | 554.52 | 13-JUL-15:00 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.575331E+09 | 830.36 | 04-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.525805E+09 | 732.65 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.580331E+09 | 904.35 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.595062E+09 | 1040.56 | 28-NOV-16:30 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.603288E+09 | 1040.56 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.671449E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.501482E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.610951E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.371351E+09 | 586.67 | 20-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.332324E+09 | 534.52 | 10-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.374426E+09 | 423.97 | 09-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.323480E+09 | 314.23 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.345048E+09 | 333.33 | 25-MAY-15:30 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.337076E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.320085E+09 | 355.83 | 13-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.363289E+09 | 510.70 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330923E+09 | 354.29 | 29-SEP-14:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.355754E+09 | 444.69 | 31-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.366511E+09 | 658.76 | 28-NOV-16:30 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.368456E+09 | 658.76 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.418872E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.320085E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.374426E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.573550E+09 | 913.97 | 20-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.517978E+09 | 859.82 | 10-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.588393E+09 | 790.63 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.516185E+09 | 567.17 | 04-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.548961E+09 | 541.01 | 26-MAY-08:30 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.536840E+09 | 534.48 | 27-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.509558E+09 | 558.75 | 27-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.578699E+09 | 834.61 | 04-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.523329E+09 | 572.71 | 19-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.552728E+09 | 762.76 | 27-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.567317E+09 | 1040.56 | 28-NOV-16:30 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.567633E+09 | 1040.56 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.658117E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.509558E+09 | 534.48 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.588393E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.378440E+09 | 599.93 | 20-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.336477E+09 | 559.17 | 03-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.376969E+09 | 562.80 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.326272E+09 | 453.52 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.346612E+09 | 354.30 | 26-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.338181E+09 | 340.63 | 27-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.321170E+09 | 413.50 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.365955E+09 | 534.17 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.333343E+09 | 505.26 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.361249E+09 | 579.73 | 27-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.368714E+09 | 658.71 | 28-NOV-16:30 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.372170E+09 | 658.71 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.422555E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.321170E+09 | 340.63 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.378440E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.610952E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2776625.48 | 0.349857E+09 |
February | 0.901968E+09 | 0.539142E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282173E+09 |
March | 0.107774E+10 | 0.597988E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3671700.86 | 0.374915E+09 |
April | 0.956342E+09 | 0.514258E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65444768.14 | 0.129277E+09 |
May | 0.103597E+10 | 0.542364E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124431E+09 | 82812602.82 |
June | 0.103308E+10 | 0.528490E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227443E+09 | 25510882.22 |
July | 0.959235E+09 | 0.501483E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222717E+09 | 21918357.51 |
August | 0.107774E+10 | 0.575332E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155956E+09 | 29620038.68 |
September | 0.956342E+09 | 0.525806E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115871E+09 | 56399053.26 |
October | 0.994195E+09 | 0.580332E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44141175.91 | 0.192393E+09 |
November | 0.984487E+09 | 0.595063E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5548534.96 | 0.320673E+09 |
December | 0.959235E+09 | 0.603287E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1372156.36 | 0.335558E+09 |
Annual Sum or Average | 0.119305E+11 | 0.671450E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969372E+09 | 0.220111E+10 |
Minimum of Months | 0.901968E+09 | 0.501483E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21918357.51 |
Maximum of Months | 0.107774E+10 | 0.610952E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227443E+09 | 0.374915E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.371321E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 847301.61 | 0.245797E+09 |
February | 0.571020E+09 | 0.332325E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196478E+09 |
March | 0.682301E+09 | 0.374427E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2273241.74 | 0.260615E+09 |
April | 0.605444E+09 | 0.323480E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41263732.48 | 92271380.18 |
May | 0.655854E+09 | 0.345048E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80615361.93 | 57772524.17 |
June | 0.654023E+09 | 0.337076E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150769E+09 | 17606955.50 |
July | 0.607275E+09 | 0.320085E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146977E+09 | 15378470.34 |
August | 0.682301E+09 | 0.363290E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101782E+09 | 21151205.63 |
September | 0.605444E+09 | 0.330923E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75485501.25 | 39137612.61 |
October | 0.629407E+09 | 0.355755E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26785017.66 | 0.135081E+09 |
November | 0.623262E+09 | 0.366511E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2314009.97 | 0.223663E+09 |
December | 0.607275E+09 | 0.368456E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 375047.97 | 0.232968E+09 |
Annual Sum or Average | 0.755301E+10 | 0.418870E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629488E+09 | 0.153792E+10 |
Minimum of Months | 0.571020E+09 | 0.320085E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15378470.34 |
Maximum of Months | 0.682301E+09 | 0.374427E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150769E+09 | 0.260615E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.573550E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1194014.55 | 0.402235E+09 |
February | 0.901968E+09 | 0.517979E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306369E+09 |
March | 0.107774E+10 | 0.588394E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3261630.84 | 0.397720E+09 |
April | 0.956342E+09 | 0.516185E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61347180.57 | 0.134303E+09 |
May | 0.103597E+10 | 0.548962E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123609E+09 | 82668947.57 |
June | 0.103308E+10 | 0.536840E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229247E+09 | 24879427.93 |
July | 0.959235E+09 | 0.509558E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223071E+09 | 21621202.04 |
August | 0.107774E+10 | 0.578700E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154175E+09 | 30587189.08 |
September | 0.956342E+09 | 0.523329E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112236E+09 | 59840495.01 |
October | 0.994195E+09 | 0.552728E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38732351.90 | 0.212144E+09 |
November | 0.984487E+09 | 0.567317E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2151636.96 | 0.358971E+09 |
December | 0.959235E+09 | 0.567633E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 106315.79 | 0.376779E+09 |
Annual Sum or Average | 0.119305E+11 | 0.658118E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.949131E+09 | 0.240812E+10 |
Minimum of Months | 0.901968E+09 | 0.509558E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21621202.04 |
Maximum of Months | 0.107774E+10 | 0.588394E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229247E+09 | 0.402235E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.378440E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1124414.26 | 0.247205E+09 |
February | 0.570983E+09 | 0.336477E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195335E+09 |
March | 0.682256E+09 | 0.376970E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2177363.11 | 0.260974E+09 |
April | 0.605404E+09 | 0.326273E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39965199.04 | 93016984.45 |
May | 0.655811E+09 | 0.346612E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79642628.46 | 58898097.81 |
June | 0.653980E+09 | 0.338181E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148511E+09 | 18333266.96 |
July | 0.607235E+09 | 0.321171E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144689E+09 | 15829754.67 |
August | 0.682256E+09 | 0.365955E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100767E+09 | 21196205.32 |
September | 0.605404E+09 | 0.333344E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74488362.57 | 39832145.31 |
October | 0.629366E+09 | 0.361260E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27111993.22 | 0.135948E+09 |
November | 0.623221E+09 | 0.368715E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2474365.38 | 0.225161E+09 |
December | 0.607235E+09 | 0.372170E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 262501.47 | 0.233045E+09 |
Annual Sum or Average | 0.755252E+10 | 0.422557E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621214E+09 | 0.154478E+10 |
Minimum of Months | 0.570983E+09 | 0.321171E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15829754.67 |
Maximum of Months | 0.682256E+09 | 0.378440E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148511E+09 | 0.260974E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.607825E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1434305.22 | 0.204107E+09 |
February | 0.901968E+09 | 0.537237E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159721E+09 |
March | 0.107774E+10 | 0.596099E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2100456.74 | 0.203753E+09 |
April | 0.956342E+09 | 0.513490E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39833416.43 | 68034938.84 |
May | 0.103597E+10 | 0.542194E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72497808.66 | 42361915.10 |
June | 0.103308E+10 | 0.528348E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125513E+09 | 12592370.77 |
July | 0.959235E+09 | 0.501035E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122634E+09 | 11413024.11 |
August | 0.107774E+10 | 0.574214E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85205847.12 | 17248910.94 |
September | 0.956342E+09 | 0.524896E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63126573.81 | 33154154.57 |
October | 0.994195E+09 | 0.578027E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23907751.60 | 0.115958E+09 |
November | 0.984487E+09 | 0.592506E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2632303.80 | 0.197298E+09 |
December | 0.959235E+09 | 0.600411E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 499896.04 | 0.204219E+09 |
Annual Sum or Average | 0.119305E+11 | 0.669628E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539385E+09 | 0.126986E+10 |
Minimum of Months | 0.901968E+09 | 0.501035E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11413024.11 |
Maximum of Months | 0.107774E+10 | 0.607825E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125513E+09 | 0.204219E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.370230E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 447723.39 | 0.146790E+09 |
February | 0.571020E+09 | 0.331539E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113338E+09 |
March | 0.682301E+09 | 0.373845E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1259946.95 | 0.145943E+09 |
April | 0.605444E+09 | 0.323238E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23153596.76 | 50941602.40 |
May | 0.655854E+09 | 0.344785E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44352775.94 | 31516507.35 |
June | 0.654023E+09 | 0.336646E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81571861.74 | 9461459.47 |
July | 0.607275E+09 | 0.319635E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79308628.47 | 8793172.83 |
August | 0.682301E+09 | 0.362774E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54399853.97 | 13255251.64 |
September | 0.605444E+09 | 0.330506E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40425584.56 | 24369840.40 |
October | 0.629407E+09 | 0.355169E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14397854.13 | 82636414.44 |
November | 0.623262E+09 | 0.365513E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1132371.33 | 0.138967E+09 |
December | 0.607275E+09 | 0.367164E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 138565.92 | 0.144089E+09 |
Annual Sum or Average | 0.755301E+10 | 0.418104E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340589E+09 | 0.910101E+09 |
Minimum of Months | 0.571020E+09 | 0.319635E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8793172.83 |
Maximum of Months | 0.682301E+09 | 0.373845E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81571861.74 | 0.146790E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.573239E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44669331.13 | 0.239855E+10 |
February | 0.901968E+09 | 0.517277E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290659E+10 |
March | 0.107774E+10 | 0.587601E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150046E+09 | 0.242389E+10 |
April | 0.956342E+09 | 0.515579E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116403E+10 | 0.736323E+09 |
May | 0.103597E+10 | 0.548265E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203784E+10 | 0.335403E+09 |
June | 0.103308E+10 | 0.535991E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325416E+10 | 69842774.44 |
July | 0.959235E+09 | 0.508394E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263558E+10 | 28423006.75 |
August | 0.107774E+10 | 0.577602E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280199E+10 | 94242482.00 |
September | 0.956342E+09 | 0.522725E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188494E+10 | 0.226617E+09 |
October | 0.994195E+09 | 0.552347E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818320E+09 | 0.139510E+10 |
November | 0.984487E+09 | 0.566873E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92682095.80 | 0.222527E+10 |
December | 0.959235E+09 | 0.567214E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4605989.44 | 0.334380E+10 |
Annual Sum or Average | 0.119305E+11 | 0.657311E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148889E+11 | 0.161841E+11 |
Minimum of Months | 0.901968E+09 | 0.508394E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28423006.75 |
Maximum of Months | 0.107774E+10 | 0.587601E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325416E+10 | 0.334380E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.376899E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 498404.71 | 0.148186E+09 |
February | 0.570983E+09 | 0.335704E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112416E+09 |
March | 0.682256E+09 | 0.376203E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1185219.17 | 0.145702E+09 |
April | 0.605404E+09 | 0.325742E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22000299.48 | 52079179.12 |
May | 0.655811E+09 | 0.346151E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43559395.83 | 32612218.87 |
June | 0.653980E+09 | 0.337782E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80187741.91 | 10068289.60 |
July | 0.607235E+09 | 0.320629E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78016740.18 | 9022084.33 |
August | 0.682256E+09 | 0.365251E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53867513.98 | 13153740.72 |
September | 0.605404E+09 | 0.332714E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39868608.24 | 24717875.78 |
October | 0.629366E+09 | 0.360387E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14393730.33 | 83482876.45 |
November | 0.623221E+09 | 0.367973E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1053912.79 | 0.140329E+09 |
December | 0.607235E+09 | 0.371215E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75507.43 | 0.143695E+09 |
Annual Sum or Average | 0.755252E+10 | 0.421665E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334707E+09 | 0.915464E+09 |
Minimum of Months | 0.570983E+09 | 0.320629E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9022084.33 |
Maximum of Months | 0.682256E+09 | 0.376899E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80187741.91 | 0.148186E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.610951E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1937809.05 | 0.320225E+09 |
February | 0.901968E+09 | 0.539141E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255448E+09 |
March | 0.107774E+10 | 0.597987E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3086208.37 | 0.333837E+09 |
April | 0.956342E+09 | 0.514257E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56926329.88 | 0.113101E+09 |
May | 0.103597E+10 | 0.542364E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106091E+09 | 72308977.08 |
June | 0.103308E+10 | 0.528490E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190918E+09 | 22021469.68 |
July | 0.959235E+09 | 0.501482E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188040E+09 | 18727199.56 |
August | 0.107774E+10 | 0.575331E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131559E+09 | 26063951.35 |
September | 0.956342E+09 | 0.525805E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97787321.33 | 49233480.88 |
October | 0.994195E+09 | 0.580331E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37202679.27 | 0.173080E+09 |
November | 0.984487E+09 | 0.595062E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4240900.32 | 0.293426E+09 |
December | 0.959235E+09 | 0.603288E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 861973.26 | 0.307450E+09 |
Annual Sum or Average | 0.119305E+11 | 0.671449E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818651E+09 | 0.198492E+10 |
Minimum of Months | 0.901968E+09 | 0.501482E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18727199.56 |
Maximum of Months | 0.107774E+10 | 0.610951E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190918E+09 | 0.333837E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.371351E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 627281.53 | 0.223466E+09 |
February | 0.421807E+09 | 0.332324E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176875E+09 |
March | 0.502994E+09 | 0.374426E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1778951.32 | 0.230975E+09 |
April | 0.447140E+09 | 0.323480E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34816063.29 | 80112815.64 |
May | 0.484071E+09 | 0.345048E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67670521.90 | 50278674.31 |
June | 0.482240E+09 | 0.337076E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125832E+09 | 15162779.02 |
July | 0.448971E+09 | 0.320085E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123329E+09 | 13137977.31 |
August | 0.502994E+09 | 0.363289E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85107658.87 | 18606307.78 |
September | 0.447140E+09 | 0.330923E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63010902.65 | 34167513.57 |
October | 0.465148E+09 | 0.355754E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22288493.27 | 0.120645E+09 |
November | 0.460569E+09 | 0.366511E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1752663.58 | 0.203428E+09 |
December | 0.448971E+09 | 0.368456E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 225389.72 | 0.212798E+09 |
Annual Sum or Average | 0.557719E+10 | 0.418872E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526439E+09 | 0.137965E+10 |
Minimum of Months | 0.421807E+09 | 0.320085E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13137977.31 |
Maximum of Months | 0.502994E+09 | 0.374426E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125832E+09 | 0.230975E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.573550E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 989379.51 | 0.360953E+09 |
February | 0.901968E+09 | 0.517978E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273891E+09 |
March | 0.107774E+10 | 0.588393E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2777687.51 | 0.351225E+09 |
April | 0.956342E+09 | 0.516185E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52407923.64 | 0.117195E+09 |
May | 0.103597E+10 | 0.548961E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104971E+09 | 72317914.69 |
June | 0.103308E+10 | 0.536840E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192788E+09 | 21466842.43 |
July | 0.959235E+09 | 0.509558E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188510E+09 | 18456866.50 |
August | 0.107774E+10 | 0.578699E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129791E+09 | 26872111.25 |
September | 0.956342E+09 | 0.523329E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94457607.76 | 52095878.87 |
October | 0.994195E+09 | 0.552728E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32504800.58 | 0.188358E+09 |
November | 0.984487E+09 | 0.567317E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1782948.33 | 0.322470E+09 |
December | 0.959235E+09 | 0.567633E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90522.11 | 0.339300E+09 |
Annual Sum or Average | 0.119305E+11 | 0.658117E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.801070E+09 | 0.214460E+10 |
Minimum of Months | 0.901968E+09 | 0.509558E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18456866.50 |
Maximum of Months | 0.107774E+10 | 0.588393E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192788E+09 | 0.360953E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.378440E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 809822.93 | 0.224504E+09 |
February | 0.570983E+09 | 0.336477E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175809E+09 |
March | 0.682256E+09 | 0.376969E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1833081.53 | 0.231327E+09 |
April | 0.605404E+09 | 0.326272E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33703019.67 | 81236612.27 |
May | 0.655811E+09 | 0.346612E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67002215.72 | 51425542.31 |
June | 0.653980E+09 | 0.338181E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124366E+09 | 15809358.15 |
July | 0.607235E+09 | 0.321170E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121547E+09 | 13507371.06 |
August | 0.682256E+09 | 0.365955E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84621175.93 | 18611931.52 |
September | 0.605404E+09 | 0.333343E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62604188.15 | 34688455.83 |
October | 0.629366E+09 | 0.361249E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22705978.17 | 0.121502E+09 |
November | 0.623221E+09 | 0.368714E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1844349.83 | 0.204313E+09 |
December | 0.607235E+09 | 0.372170E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 138683.65 | 0.212188E+09 |
Annual Sum or Average | 0.755252E+10 | 0.422555E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521175E+09 | 0.138492E+10 |
Minimum of Months | 0.570983E+09 | 0.321170E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13507371.06 |
Maximum of Months | 0.682256E+09 | 0.378440E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124366E+09 | 0.231327E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 832704.69 | 0.475652E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369641E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2865719.15 | 0.475995E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64823684.72 | 0.159190E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126904E+09 | 98279692.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235983E+09 | 27871114.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233767E+09 | 23658247.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160222E+09 | 35051424.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115781E+09 | 66053663.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39471323.45 | 0.252850E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2600794.67 | 0.433962E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233127.06 | 0.457430E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.983484E+09 | 0.287563E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23658247.62 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235983E+09 | 0.475995E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1395198.68 | 0.578932E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452654E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3956517.37 | 0.594787E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83849952.43 | 0.203066E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161981E+09 | 0.126851E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301861E+09 | 36741741.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299400E+09 | 30979272.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206543E+09 | 43709796.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151042E+09 | 82668933.25 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53245658.24 | 0.311118E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4954918.67 | 0.527396E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 658757.21 | 0.552782E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126889E+10 | 0.354169E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30979272.03 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301861E+09 | 0.594787E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 669648.76 | 0.546107E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444854E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2093084.75 | 0.582766E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68076777.33 | 0.191688E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147392E+09 | 0.109131E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312436E+09 | 30279305.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297457E+09 | 26243530.25 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212586E+09 | 37015956.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150640E+09 | 74295894.34 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49096469.51 | 0.294876E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1762852.47 | 0.496457E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65345.75 | 0.517018E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124227E+10 | 0.335073E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26243530.25 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312436E+09 | 0.582766E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 936.57 | 20-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.09 | 16-JAN-11:53 | 623.83 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 882.29 | 03-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 831.89 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 822.97 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.80 | 18-MAR-17:02 | 710.80 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 562.54 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 490.55 | 30-APR-15:45 | 369.91 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 541.02 | 26-MAY-08:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 20-MAY-17:02 | 309.72 | 23-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 734.17 | 17-JUN-17:10 | 158.17 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 554.53 | 13-JUL-15:00 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 924.50 | 22-JUL-17:43 | 250.85 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 830.38 | 04-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 830.21 | 13-AUG-16:00 | 384.64 | 05-AUG-17:50 |
September | 1306.65 | 01-SEP-09:09 | 732.67 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 582.41 | 17-SEP-11:53 | 261.51 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 904.34 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 369.99 | 01-OCT-14:45 | 738.03 | 22-OCT-14:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 28-NOV-16:30 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.53 | 19-NOV-13:10 | 692.47 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.24 | 25-DEC-14:00 | 591.49 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.17 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 924.50 | 831.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 586.68 | 20-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.81 | 31-JAN-14:00 | 425.28 | 01-JAN-01:00 |
February | 827.22 | 01-FEB-10:09 | 534.53 | 10-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 566.21 | 02-FEB-23:00 |
March | 827.22 | 01-MAR-10:09 | 423.96 | 09-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.85 | 18-MAR-17:02 | 476.09 | 28-MAR-04:00 |
April | 827.22 | 03-APR-09:09 | 314.23 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 330.29 | 30-APR-15:45 | 363.34 | 16-APR-08:40 |
May | 827.22 | 01-MAY-09:09 | 333.34 | 25-MAY-15:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.54 | 20-MAY-17:47 | 205.89 | 23-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 488.60 | 17-JUN-17:10 | 114.77 | 11-JUN-06:20 |
July | 827.22 | 03-JUL-09:09 | 355.84 | 13-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 617.24 | 22-JUL-17:43 | 167.64 | 26-JUL-24:00 |
August | 827.22 | 01-AUG-09:09 | 510.72 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 553.47 | 13-AUG-16:00 | 261.66 | 05-AUG-17:50 |
September | 827.22 | 01-SEP-09:09 | 354.29 | 29-SEP-14:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.31 | 17-SEP-11:53 | 174.14 | 03-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 444.69 | 31-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.82 | 01-OCT-14:45 | 540.36 | 22-OCT-14:00 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 28-NOV-16:30 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.33 | 19-NOV-15:00 | 465.32 | 29-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.16 | 25-DEC-16:00 | 395.50 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.77 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 617.24 | 566.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 913.98 | 20-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.21 | 31-JAN-14:10 | 707.26 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 859.84 | 10-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 898.91 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 790.64 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.18 | 15-MAR-13:00 | 728.00 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 567.18 | 04-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 486.21 | 30-APR-15:04 | 374.60 | 26-APR-21:10 |
May | 1306.65 | 01-MAY-09:09 | 541.02 | 26-MAY-08:30 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 433.81 | 20-MAY-17:47 | 309.75 | 23-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 534.49 | 27-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 734.11 | 17-JUN-17:10 | 157.31 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 558.75 | 27-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 925.66 | 22-JUL-17:43 | 249.53 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 834.63 | 04-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 830.20 | 13-AUG-16:00 | 395.92 | 05-AUG-17:50 |
September | 1306.65 | 01-SEP-09:09 | 572.72 | 19-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 569.03 | 17-SEP-11:53 | 265.35 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 762.77 | 27-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 368.57 | 01-OCT-14:45 | 876.33 | 22-OCT-14:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 28-NOV-16:30 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.15 | 01-NOV-16:00 | 725.14 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.48 | 21-DEC-15:00 | 614.26 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 534.49 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.31 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 925.66 | 898.91 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 599.94 | 20-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.58 | 16-JAN-11:53 | 439.45 | 01-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 559.16 | 03-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 580.56 | 02-FEB-23:00 |
March | 827.17 | 01-MAR-10:09 | 562.81 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.46 | 15-MAR-13:00 | 483.34 | 28-MAR-04:00 |
April | 827.17 | 03-APR-09:09 | 453.51 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 321.37 | 30-APR-15:04 | 261.71 | 26-APR-21:10 |
May | 827.17 | 01-MAY-09:09 | 354.31 | 26-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.64 | 20-MAY-18:30 | 210.70 | 23-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 340.64 | 27-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 488.74 | 17-JUN-17:10 | 109.87 | 13-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 413.50 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 612.00 | 22-JUL-18:00 | 178.78 | 26-JUL-24:00 |
August | 827.17 | 01-AUG-09:09 | 534.18 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 553.46 | 13-AUG-16:00 | 265.15 | 05-AUG-17:40 |
September | 827.17 | 01-SEP-09:09 | 505.27 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 383.96 | 17-SEP-11:53 | 173.94 | 03-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 579.73 | 27-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.99 | 01-OCT-14:45 | 506.79 | 22-OCT-14:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 28-NOV-16:30 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.44 | 19-NOV-12:30 | 465.40 | 29-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.74 | 25-DEC-13:42 | 397.80 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 340.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.87 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 612.00 | 580.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 932.11 | 20-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.96 | 16-JAN-12:00 | 392.60 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 876.58 | 03-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 476.11 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 814.01 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 51.39 | 18-MAR-17:02 | 402.74 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 559.51 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.50 | 30-APR-15:30 | 213.17 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 536.25 | 26-MAY-08:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.83 | 20-MAY-18:10 | 171.10 | 23-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 398.36 | 17-JUN-17:03 | 85.27 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 550.41 | 13-JUL-15:00 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 503.59 | 22-JUL-18:00 | 137.63 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 822.32 | 04-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 443.91 | 13-AUG-16:00 | 207.94 | 05-AUG-17:50 |
September | 1306.65 | 01-SEP-09:09 | 720.36 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.30 | 17-SEP-12:10 | 157.65 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 897.00 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.28 | 01-OCT-14:28 | 422.78 | 22-OCT-14:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 28-NOV-16:30 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.71 | 19-NOV-15:00 | 425.59 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.71 | 25-DEC-15:52 | 355.91 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.27 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 503.59 | 476.11 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 584.46 | 20-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.06 | 31-JAN-14:00 | 278.12 | 01-JAN-01:00 |
February | 827.22 | 01-FEB-10:09 | 530.44 | 10-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 334.96 | 02-FEB-23:00 |
March | 827.22 | 01-MAR-10:09 | 417.46 | 09-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.14 | 18-MAR-17:02 | 280.45 | 28-MAR-04:00 |
April | 827.22 | 03-APR-09:09 | 314.23 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.91 | 30-APR-15:45 | 183.46 | 16-APR-08:30 |
May | 827.22 | 01-MAY-09:09 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.41 | 20-MAY-17:02 | 118.03 | 23-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 255.89 | 17-JUN-18:50 | 62.00 | 25-JUN-06:00 |
July | 827.22 | 03-JUL-09:09 | 353.69 | 13-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 335.83 | 22-JUL-18:00 | 96.67 | 26-JUL-24:00 |
August | 827.22 | 01-AUG-09:09 | 505.88 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.63 | 13-AUG-16:00 | 143.74 | 05-AUG-17:50 |
September | 827.22 | 01-SEP-09:09 | 352.49 | 29-SEP-14:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.39 | 17-SEP-12:07 | 108.40 | 03-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 439.93 | 31-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.55 | 01-OCT-14:28 | 309.86 | 22-OCT-14:00 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 28-NOV-16:30 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.95 | 19-NOV-15:00 | 293.42 | 29-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.46 | 25-DEC-15:42 | 243.23 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.00 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 335.83 | 334.96 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 909.02 | 20-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4698.24 | 31-JAN-17:10 | 18445.79 | 12-JAN-07:02 |
February | 1306.65 | 01-FEB-10:09 | 852.78 | 10-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 18782.94 | 01-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 780.38 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5353.15 | 20-MAR-17:00 | 21302.52 | 27-MAR-06:01 |
April | 1306.65 | 03-APR-09:09 | 564.44 | 04-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11367.38 | 14-APR-16:02 | 13678.29 | 21-APR-06:03 |
May | 1306.65 | 01-MAY-09:09 | 536.25 | 26-MAY-08:30 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13441.22 | 31-MAY-16:02 | 10434.53 | 01-MAY-06:01 |
June | 1306.65 | 01-JUN-09:09 | 531.51 | 27-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18530.90 | 28-JUN-16:01 | 4575.64 | 21-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 556.53 | 27-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15593.08 | 05-JUL-16:01 | 2097.93 | 27-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 826.78 | 04-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17359.14 | 25-AUG-16:01 | 5029.36 | 24-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 569.52 | 19-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13792.10 | 08-SEP-16:01 | 7178.44 | 22-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 751.35 | 27-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10848.73 | 03-OCT-16:02 | 19044.13 | 25-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 28-NOV-16:30 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3379.69 | 01-NOV-16:05 | 19545.50 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 331.09 | 21-DEC-15:00 | 24618.81 | 05-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 531.51 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2097.93 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 18530.90 | 24618.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 597.87 | 20-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 | 16-JAN-12:00 | 286.01 | 01-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 556.20 | 03-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 340.35 | 02-FEB-23:00 |
March | 827.17 | 01-MAR-10:09 | 559.89 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.16 | 15-MAR-13:00 | 283.88 | 28-MAR-04:00 |
April | 827.17 | 03-APR-09:09 | 445.83 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.72 | 30-APR-15:43 | 147.87 | 21-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 352.20 | 26-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.15 | 20-MAY-17:07 | 121.76 | 23-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 339.09 | 27-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.38 | 17-JUN-17:03 | 63.25 | 13-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 406.40 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 326.89 | 22-JUL-18:00 | 102.04 | 26-JUL-24:00 |
August | 827.17 | 01-AUG-09:09 | 530.38 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.62 | 13-AUG-16:00 | 143.61 | 05-AUG-17:50 |
September | 827.17 | 01-SEP-09:09 | 500.59 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.07 | 17-SEP-12:07 | 107.29 | 03-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 576.71 | 27-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.66 | 01-OCT-14:25 | 293.62 | 22-OCT-14:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 28-NOV-16:30 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.09 | 19-NOV-12:32 | 293.87 | 29-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.87 | 25-DEC-13:42 | 243.13 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 339.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.25 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 326.89 | 340.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 936.56 | 20-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.95 | 16-JAN-12:00 | 595.89 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 882.29 | 03-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 753.12 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 822.95 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.51 | 18-MAR-17:02 | 641.23 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 562.53 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 405.95 | 30-APR-15:10 | 332.72 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 541.00 | 26-MAY-08:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 385.90 | 20-MAY-17:02 | 274.53 | 23-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 608.47 | 17-JUN-17:10 | 138.58 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 554.52 | 13-JUL-15:00 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 773.36 | 22-JUL-18:00 | 210.61 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 830.36 | 04-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 692.67 | 13-AUG-16:00 | 316.04 | 05-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 732.65 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 480.59 | 17-SEP-11:53 | 226.13 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 904.35 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 311.78 | 01-OCT-14:36 | 633.72 | 22-OCT-14:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 28-NOV-16:30 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.88 | 19-NOV-13:10 | 632.88 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.67 | 25-DEC-16:00 | 536.85 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.58 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 773.36 | 753.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 586.67 | 20-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.09 | 31-JAN-14:00 | 404.48 | 01-JAN-01:00 |
February | 805.43 | 01-FEB-08:09 | 534.52 | 10-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 509.89 | 02-FEB-23:00 |
March | 805.43 | 01-MAR-08:09 | 423.97 | 09-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.50 | 18-MAR-17:02 | 428.90 | 28-MAR-04:00 |
April | 805.43 | 03-APR-07:10 | 314.23 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.72 | 30-APR-15:26 | 319.56 | 16-APR-09:00 |
May | 805.43 | 01-MAY-07:10 | 333.33 | 25-MAY-15:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.62 | 20-MAY-17:02 | 182.61 | 23-MAY-05:00 |
June | 805.43 | 01-JUN-07:10 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 408.29 | 17-JUN-17:10 | 99.87 | 11-JUN-06:10 |
July | 805.43 | 03-JUL-07:10 | 355.83 | 13-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 519.79 | 22-JUL-18:00 | 141.24 | 26-JUL-24:00 |
August | 805.43 | 01-AUG-07:10 | 510.70 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 461.78 | 13-AUG-16:00 | 215.98 | 05-AUG-17:50 |
September | 805.43 | 01-SEP-07:10 | 354.29 | 29-SEP-14:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.95 | 17-SEP-12:15 | 150.98 | 03-SEP-05:00 |
October | 805.43 | 02-OCT-07:10 | 444.69 | 31-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.93 | 01-OCT-14:34 | 461.52 | 22-OCT-14:00 |
November | 805.43 | 01-NOV-07:10 | 658.76 | 28-NOV-16:30 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.99 | 19-NOV-15:00 | 424.19 | 29-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 658.76 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.57 | 25-DEC-16:00 | 359.34 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.87 | |||||
Maximum of Months | 805.43 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 519.79 | 509.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 913.97 | 20-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.12 | 31-JAN-14:05 | 663.01 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 859.82 | 10-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 803.02 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 790.63 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.63 | 15-MAR-13:00 | 654.66 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 567.17 | 04-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 407.08 | 30-APR-15:24 | 334.95 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 541.01 | 26-MAY-08:30 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.44 | 20-MAY-17:02 | 274.52 | 23-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 534.48 | 27-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 609.09 | 17-JUN-17:10 | 137.83 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 558.75 | 27-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 784.24 | 22-JUL-18:00 | 209.53 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 834.61 | 04-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 692.67 | 13-AUG-16:00 | 325.18 | 05-AUG-17:50 |
September | 1306.65 | 01-SEP-09:09 | 572.71 | 19-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 479.81 | 17-SEP-12:15 | 229.25 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 762.76 | 27-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.78 | 01-OCT-14:34 | 743.90 | 22-OCT-14:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 28-NOV-16:30 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.46 | 01-NOV-16:00 | 657.26 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 | 21-DEC-15:00 | 555.75 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 534.48 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.83 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 784.24 | 803.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 599.93 | 20-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.76 | 16-JAN-12:00 | 415.59 | 01-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 559.17 | 03-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 521.37 | 02-FEB-23:00 |
March | 827.17 | 01-MAR-10:09 | 562.80 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.76 | 15-MAR-13:00 | 434.90 | 28-MAR-04:00 |
April | 827.17 | 03-APR-09:09 | 453.52 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 266.21 | 30-APR-15:24 | 224.26 | 21-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 354.30 | 26-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.92 | 20-MAY-17:45 | 186.54 | 23-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 340.63 | 27-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 408.42 | 17-JUN-17:10 | 96.10 | 13-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 413.50 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 510.61 | 22-JUL-18:00 | 149.80 | 26-JUL-24:00 |
August | 827.17 | 01-AUG-09:09 | 534.17 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 461.77 | 13-AUG-16:00 | 217.55 | 05-AUG-17:50 |
September | 827.17 | 01-SEP-09:09 | 505.26 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.99 | 17-SEP-12:15 | 150.39 | 03-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 579.73 | 27-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.26 | 01-OCT-14:34 | 434.60 | 22-OCT-14:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 28-NOV-16:30 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.36 | 19-NOV-12:30 | 424.48 | 29-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.96 | 25-DEC-13:42 | 360.65 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 340.63 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.10 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 510.61 | 521.37 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.09 | 31-JAN-14:00 | 918.51 | 01-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1106.11 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.33 | 18-MAR-17:02 | 925.65 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.84 | 30-APR-14:51 | 472.98 | 21-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.13 | 20-MAY-17:02 | 381.68 | 23-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 806.33 | 17-JUN-17:03 | 185.75 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 994.06 | 22-JUL-18:00 | 278.88 | 26-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 861.72 | 13-AUG-16:00 | 426.94 | 05-AUG-17:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 626.93 | 17-SEP-11:53 | 314.66 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.76 | 01-OCT-14:40 | 861.66 | 22-OCT-14:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.73 | 19-NOV-14:53 | 929.47 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.70 | 25-DEC-14:00 | 784.58 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.75 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 994.06 | 1106.11 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.76 | 31-JAN-14:00 | 1075.45 | 01-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1377.17 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.34 | 18-MAR-17:02 | 1153.16 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 677.31 | 30-APR-15:10 | 598.62 | 21-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 646.77 | 20-MAY-17:02 | 488.16 | 23-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1038.76 | 17-JUN-17:03 | 239.33 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1275.31 | 22-JUL-18:00 | 356.24 | 26-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1097.10 | 13-AUG-16:00 | 542.53 | 05-AUG-17:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 819.89 | 17-SEP-11:53 | 395.39 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.32 | 01-OCT-14:23 | 1053.11 | 22-OCT-14:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.71 | 19-NOV-15:00 | 1142.17 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.69 | 25-DEC-13:52 | 968.01 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.33 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1275.31 | 1377.17 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.04 | 31-JAN-17:00 | 946.12 | 01-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1263.68 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.49 | 15-MAR-13:00 | 1056.93 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.25 | 30-APR-16:00 | 562.65 | 26-APR-21:03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 566.61 | 20-MAY-17:02 | 437.65 | 23-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1043.96 | 17-JUN-17:03 | 211.88 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1228.91 | 22-JUL-18:00 | 371.22 | 26-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1002.18 | 13-AUG-16:00 | 639.00 | 05-AUG-17:40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 758.26 | 17-SEP-12:00 | 392.95 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.21 | 01-OCT-14:20 | 1332.18 | 22-OCT-14:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.32 | 19-NOV-15:10 | 1029.53 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.12 | 25-DEC-13:42 | 878.41 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.88 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1228.91 | 1332.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 36710.82 | 17-JAN-07:01 | 8893.70 | 11517.52 | 61577.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 36643.20 | 01-FEB-07:01 | 8893.70 | 11517.52 | 61577.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 36932.02 | 17-MAR-06:02 | 6352.64 | 8226.80 | 43983.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40788.52 | 17-APR-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41665.03 | 30-MAY-05:12 | 3176.32 | 2742.16 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41323.80 | 20-JUN-05:12 | 3176.32 | 2742.16 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41147.92 | 26-JUL-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 41357.17 | 08-AUG-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41134.72 | 26-SEP-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40965.64 | 11-OCT-05:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 41298.21 | 13-NOV-06:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 35807.55 | 27-DEC-07:02 | 7623.17 | 9872.16 | 52780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 35807.55 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41665.03 | 8893.70 | 11517.52 | 61577.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5938.41 | 31-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.28 | 0.00 |
February | 4449.48 | 23-FEB-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.50 |
March | 7035.79 | 16-MAR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.73 | 0.00 |
April | 11030.42 | 14-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.07 | 0.00 |
May | 10927.96 | 15-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.53 | 0.00 |
June | 13236.50 | 28-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.33 | 0.00 |
July | 12454.49 | 20-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.54 | 0.00 |
August | 12454.44 | 25-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.68 | 0.00 |
September | 11561.80 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.91 | 0.00 |
October | 10571.24 | 02-OCT-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.10 | 0.00 |
November | 7036.81 | 01-NOV-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.79 | 0.00 |
December | 4663.59 | 22-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4449.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13236.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.33 | 69.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2119.65 | 27-JAN-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.13 | 0.00 |
February | 1132.87 | 01-FEB-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.13 |
March | 2503.48 | 17-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.03 | 0.00 |
April | 4717.09 | 24-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.93 | 0.00 |
May | 5209.64 | 08-MAY-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.67 | 0.00 |
June | 6824.41 | 19-JUN-12:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.13 | 0.00 |
July | 6257.26 | 17-JUL-12:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.37 | 0.00 |
August | 6403.73 | 28-AUG-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.66 | 0.00 |
September | 6526.74 | 11-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.73 |
October | 5563.90 | 02-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.67 | 0.00 |
November | 2942.80 | 01-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.93 | 0.00 |
December | 2626.77 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1132.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6824.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.13 | 84.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2861.17 | 27-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 | 0.00 |
February | 2413.41 | 01-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.75 |
March | 3052.89 | 20-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.47 | 0.00 |
April | 4893.94 | 24-APR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.83 | 0.00 |
May | 5735.95 | 08-MAY-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.89 | 0.00 |
June | 7958.27 | 19-JUN-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.38 | 0.00 |
July | 7823.52 | 10-JUL-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.89 | 0.00 |
August | 6856.77 | 08-AUG-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.75 | 0.00 |
September | 6682.87 | 05-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.87 |
October | 6263.56 | 02-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 |
November | 3622.86 | 02-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.61 | 0.00 |
December | 2549.94 | 26-DEC-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2413.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7958.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.38 | 157.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13381.13 | 27-JAN-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12270.42 | 01-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14065.86 | 20-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 30086.33 | 17-APR-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31164.24 | 30-MAY-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33522.46 | 19-JUN-05:14 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32596.07 | 05-JUL-05:14 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30410.72 | 10-AUG-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33895.12 | 05-SEP-05:14 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31019.09 | 10-OCT-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15550.23 | 03-NOV-06:02 | 7623.17 | 9872.16 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12443.53 | 27-DEC-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12270.42 | 2541.06 | 2193.73 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33895.12 | 7623.17 | 9872.16 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13374.68 | 27-JAN-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11812.25 | 22-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15231.44 | 17-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 28460.28 | 24-APR-06:02 | 6352.64 | 8226.80 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33938.38 | 30-MAY-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33752.42 | 12-JUN-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34057.18 | 24-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34407.48 | 21-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34115.67 | 08-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33886.81 | 02-OCT-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15683.42 | 01-NOV-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11985.17 | 22-DEC-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11812.25 | 0.00 | 1058.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34407.48 | 6352.64 | 8226.80 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3018.76 | 31-JAN-16:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 21.31 | 0.00 |
February | 2266.24 | 22-FEB-16:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.14 |
March | 4246.84 | 16-MAR-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 39.72 | 0.00 |
April | 9334.01 | 30-APR-15:42 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 464.26 | 0.00 |
May | 11937.29 | 07-MAY-17:32 | 0.00 | 165.44 | 2316.62 | 0.00 | 0.00 | 0.00 | 0.00 | 352.45 | 0.00 |
June | 13826.97 | 25-JUN-18:11 | 0.00 | 193.02 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 555.97 | 0.00 |
July | 13837.95 | 16-JUL-17:51 | 0.00 | 193.02 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 647.38 | 0.00 |
August | 13829.68 | 13-AUG-16:11 | 468.72 | 193.02 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 748.59 | 0.00 |
September | 13384.96 | 17-SEP-13:43 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 397.28 | 0.00 |
October | 11617.89 | 02-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 |
November | 4193.77 | 01-NOV-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 35.02 | 0.00 |
December | 2184.89 | 22-DEC-16:40 | 1272.23 | 703.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2184.89 | 0.00 | 110.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13837.95 | 1272.23 | 703.98 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 748.59 | 36.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3133.03 | 27-JAN-10:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.89 |
February | 3402.12 | 23-FEB-10:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.45 |
March | 4647.96 | 23-MAR-10:20 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.02 |
April | 11461.85 | 02-APR-09:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 |
May | 12701.62 | 28-MAY-10:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 49.50 | 0.00 |
June | 12907.76 | 18-JUN-09:02 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 106.07 | 0.00 |
July | 13189.36 | 02-JUL-09:32 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 20.73 | 0.00 |
August | 12863.71 | 13-AUG-09:32 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 46.60 | 0.00 |
September | 11963.30 | 10-SEP-10:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 97.70 | 0.00 |
October | 9533.49 | 01-OCT-11:23 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 40.91 | 0.00 |
November | 3967.10 | 01-NOV-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 |
December | 1987.30 | 01-DEC-10:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1987.30 | 169.56 | 69.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13189.36 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 106.07 | 30.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16453.54 | 29-JAN-14:12 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.01 |
February | 9635.36 | 28-FEB-14:05 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.07 |
March | 8834.52 | 16-MAR-13:40 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 24.29 | 0.00 |
April | 15361.43 | 30-APR-12:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 209.45 | 0.00 |
May | 14940.12 | 07-MAY-13:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 220.64 | 0.00 |
June | 14898.08 | 04-JUN-16:41 | 468.72 | 193.02 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 404.77 | 0.00 |
July | 15146.33 | 30-JUL-15:02 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 394.20 | 0.00 |
August | 15461.59 | 13-AUG-16:11 | 468.72 | 193.02 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 736.65 | 0.00 |
September | 15691.29 | 10-SEP-13:42 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 354.53 | 0.00 |
October | 16777.11 | 15-OCT-12:52 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 58.18 | 0.00 |
November | 15906.86 | 19-NOV-14:02 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.88 |
December | 16511.46 | 25-DEC-13:52 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8834.52 | 267.84 | 110.30 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16777.11 | 2613.31 | 992.69 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 736.65 | 86.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10836.12 | 29-JAN-16:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.58 |
February | 6117.18 | 22-FEB-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.29 |
March | 10356.69 | 18-MAR-17:42 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.32 |
April | 14363.99 | 02-APR-16:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 42.78 | 0.00 |
May | 14794.49 | 28-MAY-17:11 | 0.00 | 139.64 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 155.81 | 0.00 |
June | 15136.90 | 25-JUN-17:31 | 0.00 | 122.19 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 307.61 | 0.00 |
July | 15045.33 | 30-JUL-17:01 | 0.00 | 122.19 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 331.01 | 0.00 |
August | 15177.24 | 13-AUG-16:51 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 387.66 | 0.00 |
September | 14279.60 | 04-SEP-15:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 56.23 | 0.00 |
October | 14799.57 | 15-OCT-15:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 44.39 | 0.00 |
November | 10431.55 | 19-NOV-15:22 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 5.21 | 0.00 |
December | 8891.23 | 25-DEC-15:52 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6117.18 | 0.00 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15177.24 | 805.38 | 314.21 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 387.66 | 45.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2314.49 | 27-JAN-16:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.45 | 0.00 |
February | 1411.59 | 22-FEB-16:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.92 |
March | 2930.28 | 20-MAR-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.29 | 0.00 |
April | 4880.50 | 25-APR-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 59.82 | 0.00 |
May | 5500.21 | 08-MAY-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.36 | 0.00 |
June | 11111.78 | 25-JUN-18:11 | 0.00 | 193.02 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 313.07 | 0.00 |
July | 11098.37 | 30-JUL-17:31 | 0.00 | 275.74 | 3861.03 | 0.00 | 0.00 | 0.00 | 0.00 | 352.53 | 0.00 |
August | 11320.29 | 27-AUG-17:41 | 0.00 | 220.59 | 3088.82 | 0.00 | 0.00 | 0.00 | 0.00 | 242.44 | 0.00 |
September | 11126.25 | 10-SEP-14:02 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 188.43 | 0.00 |
October | 9850.74 | 01-OCT-13:43 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 178.23 | 0.00 |
November | 3977.72 | 02-NOV-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 20.32 | 0.00 |
December | 1980.15 | 22-DEC-16:40 | 1272.23 | 687.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1411.59 | 0.00 | 110.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11320.29 | 1306.65 | 687.30 | 3861.03 | 0.00 | 0.00 | 0.00 | 0.00 | 352.53 | 18.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3026.28 | 27-JAN-10:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.15 |
February | 2775.57 | 23-FEB-10:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.98 |
March | 3706.12 | 23-MAR-10:30 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.37 |
April | 8732.60 | 23-APR-09:12 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.53 |
May | 10806.94 | 28-MAY-10:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 30.85 | 0.00 |
June | 11268.55 | 11-JUN-10:12 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 17.23 | 0.00 |
July | 11710.02 | 30-JUL-09:31 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.18 | 0.00 |
August | 11324.09 | 27-AUG-11:02 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 102.19 | 0.00 |
September | 11348.11 | 04-SEP-09:42 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.76 |
October | 8799.69 | 15-OCT-09:32 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.75 |
November | 4114.46 | 02-NOV-08:40 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.91 |
December | 2681.55 | 26-DEC-10:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2681.55 | 169.56 | 69.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11710.02 | 827.22 | 314.23 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.19 | 16.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13519.29 | 29-JAN-14:12 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.81 |
February | 8649.12 | 28-FEB-13:07 | 3816.70 | 1489.03 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1155.69 |
March | 10168.20 | 16-MAR-16:10 | 401.76 | 275.75 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 5270.11 | 0.00 |
April | 11838.75 | 14-APR-16:50 | 401.76 | 275.75 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 9788.56 | 0.00 |
May | 12316.66 | 15-MAY-17:00 | 401.76 | 275.75 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 11337.87 | 0.00 |
June | 14116.75 | 28-JUN-17:00 | 401.76 | 275.75 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 14496.51 | 0.00 |
July | 13293.42 | 20-JUL-17:00 | 401.76 | 275.75 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 12513.18 | 0.00 |
August | 13951.28 | 25-AUG-17:00 | 401.76 | 275.75 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 13663.89 | 0.00 |
September | 13645.94 | 10-SEP-14:02 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 156.70 | 0.00 |
October | 13757.08 | 15-OCT-12:52 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 35.20 | 0.00 |
November | 13035.81 | 19-NOV-12:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.44 |
December | 13100.04 | 24-DEC-13:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8649.12 | 267.84 | 110.30 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14116.75 | 3816.70 | 1489.03 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 14496.51 | 1155.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8085.10 | 29-JAN-16:53 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.73 |
February | 4535.67 | 22-FEB-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 |
March | 6686.44 | 18-MAR-17:42 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 |
April | 11623.41 | 23-APR-17:11 | 0.00 | 139.64 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 102.88 | 0.00 |
May | 11931.19 | 29-MAY-17:51 | 0.00 | 157.10 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 73.83 | 0.00 |
June | 12117.00 | 11-JUN-17:31 | 0.00 | 174.55 | 2444.18 | 0.00 | 0.00 | 0.00 | 0.00 | 76.24 | 0.00 |
July | 12198.77 | 30-JUL-17:31 | 0.00 | 174.55 | 2444.18 | 0.00 | 0.00 | 0.00 | 0.00 | 206.56 | 0.00 |
August | 12804.43 | 27-AUG-17:41 | 0.00 | 139.64 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 136.83 | 0.00 |
September | 11711.76 | 04-SEP-17:01 | 0.00 | 139.64 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 44.53 | 0.00 |
October | 11826.28 | 15-OCT-15:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 26.80 | 0.00 |
November | 6653.50 | 20-NOV-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.74 | 0.00 |
December | 7519.24 | 24-DEC-16:12 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4535.67 | 0.00 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12804.43 | 805.38 | 314.21 | 2444.18 | 0.00 | 0.00 | 0.00 | 0.00 | 206.56 | 43.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2979.04 | 31-JAN-16:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 0.00 |
February | 2224.35 | 22-FEB-16:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.85 |
March | 4048.44 | 20-MAR-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 0.00 |
April | 5746.97 | 25-APR-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 93.39 | 0.00 |
May | 9859.37 | 21-MAY-17:41 | 0.00 | 248.17 | 3474.93 | 0.00 | 0.00 | 0.00 | 0.00 | 212.44 | 0.00 |
June | 11666.01 | 25-JUN-18:11 | 0.00 | 193.02 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 473.34 | 0.00 |
July | 11705.37 | 04-JUL-19:01 | 0.00 | 217.12 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 295.40 | 0.00 |
August | 11608.98 | 27-AUG-18:31 | 0.00 | 312.45 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 303.06 | 0.00 |
September | 11305.47 | 17-SEP-16:52 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 126.82 | 0.00 |
October | 9576.26 | 02-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 | 0.00 |
November | 3942.97 | 02-NOV-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.53 | 0.00 |
December | 2230.54 | 22-DEC-16:50 | 1272.23 | 774.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2224.35 | 0.00 | 137.87 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11705.37 | 1306.65 | 774.48 | 3474.93 | 0.00 | 0.00 | 0.00 | 0.00 | 473.34 | 29.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4385.30 | 27-JAN-11:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.61 |
February | 5716.46 | 24-FEB-13:01 | 5638.00 | 2199.59 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.46 |
March | 5956.25 | 23-MAR-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 |
April | 11508.67 | 09-APR-08:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.11 |
May | 12607.60 | 21-MAY-09:02 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 |
June | 12677.00 | 11-JUN-08:52 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 |
July | 13087.00 | 30-JUL-09:31 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.79 | 0.00 |
August | 12984.38 | 27-AUG-09:11 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.91 | 0.00 |
September | 12506.75 | 10-SEP-10:12 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 59.72 | 0.00 |
October | 8536.37 | 01-OCT-11:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 33.57 | 0.00 |
November | 5289.67 | 01-NOV-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.54 |
December | 4780.55 | 13-DEC-13:02 | 4832.57 | 1885.36 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4385.30 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13087.00 | 5638.00 | 2199.59 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 77.91 | 36.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14175.44 | 15-JAN-13:42 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.92 |
February | 9643.37 | 26-FEB-14:33 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.43 |
March | 8458.48 | 23-MAR-13:50 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 | 0.00 |
April | 13459.28 | 30-APR-13:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 263.43 | 0.00 |
May | 11065.48 | 21-MAY-16:21 | 602.64 | 248.17 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 291.15 | 0.00 |
June | 12703.69 | 04-JUN-16:41 | 468.72 | 193.02 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 344.75 | 0.00 |
July | 13370.08 | 30-JUL-12:12 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 335.10 | 0.00 |
August | 13266.76 | 27-AUG-15:11 | 602.64 | 248.17 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 409.46 | 0.00 |
September | 13902.38 | 24-SEP-12:22 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 116.17 | 0.00 |
October | 13758.92 | 09-OCT-13:12 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 54.82 | 0.00 |
November | 14054.75 | 19-NOV-13:22 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.83 |
December | 14631.30 | 25-DEC-13:52 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8458.48 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14631.30 | 1306.65 | 496.34 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 409.46 | 272.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6417.46 | 15-JAN-16:23 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.77 |
February | 5992.51 | 22-FEB-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 |
March | 9216.68 | 18-MAR-17:42 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.66 |
April | 12830.65 | 30-APR-16:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 173.89 | 0.00 |
May | 13186.15 | 21-MAY-17:01 | 0.00 | 157.10 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 146.06 | 0.00 |
June | 13368.37 | 25-JUN-17:31 | 0.00 | 122.19 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 262.94 | 0.00 |
July | 13562.85 | 30-JUL-17:32 | 0.00 | 174.55 | 2444.18 | 0.00 | 0.00 | 0.00 | 0.00 | 353.67 | 0.00 |
August | 13492.58 | 27-AUG-16:31 | 423.88 | 174.55 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 215.12 | 0.00 |
September | 12948.45 | 04-SEP-15:41 | 339.11 | 139.64 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 54.63 | 0.00 |
October | 12062.18 | 15-OCT-16:22 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 57.82 | 0.00 |
November | 10691.06 | 19-NOV-15:22 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 4.88 | 0.00 |
December | 9978.23 | 25-DEC-15:52 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5992.51 | 0.00 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13562.85 | 805.38 | 314.21 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 353.67 | 51.77 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.104509E+12 | 114105.12 | 02-JAN-07:10 | 0.112872E+11 | 29537.62 | 02-JAN-07:30 |
February | 0.853124E+11 | 87794.77 | 22-FEB-16:10 | 0.105202E+11 | 24377.92 | 28-FEB-07:19 |
March | 0.107725E+12 | 113778.14 | 16-MAR-15:30 | 0.116643E+11 | 36224.90 | 27-MAR-06:10 |
April | 0.129286E+12 | 146084.59 | 14-APR-15:20 | 0.968037E+10 | 11355.37 | 21-APR-06:30 |
May | 0.151517E+12 | 152623.69 | 31-MAY-15:39 | 0.975313E+10 | 9491.15 | 01-MAY-11:30 |
June | 0.181253E+12 | 179744.45 | 28-JUN-14:00 | 0.921215E+10 | 9370.67 | 01-JUN-11:20 |
July | 0.171562E+12 | 171191.22 | 31-JUL-15:00 | 0.904689E+10 | 9295.22 | 03-JUL-11:20 |
August | 0.178701E+12 | 173921.21 | 25-AUG-15:20 | 0.943571E+10 | 9329.57 | 31-AUG-11:09 |
September | 0.154359E+12 | 162757.70 | 08-SEP-15:00 | 0.911996E+10 | 9419.79 | 28-SEP-11:20 |
October | 0.126169E+12 | 147365.50 | 02-OCT-15:09 | 0.999896E+10 | 22036.36 | 25-OCT-06:19 |
November | 0.103577E+12 | 114600.88 | 01-NOV-15:00 | 0.103452E+11 | 24873.54 | 04-NOV-06:19 |
December | 0.980755E+11 | 99777.18 | 22-DEC-16:49 | 0.136311E+11 | 40141.95 | 06-DEC-07:30 |
Annual Sum or Average | 0.159205E+13 | 0.123695E+12 | ||||
Minimum of Months | 0.853124E+11 | 87794.77 | 0.904689E+10 | 9295.22 | ||
Maximum of Months | 0.181253E+12 | 179744.45 | 0.136311E+11 | 40141.95 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.197093E+11 | 0.534996E+10 | 0.593559E+11 | 0.982682E+09 | 0.607650E+10 | 12379742.02 | 0.130877E+10 | 0.117130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177945E+11 | 0.443448E+10 | 0.537310E+11 | 0.889297E+09 | 0.440584E+10 | 11196021.66 | 0.117633E+10 | 0.286975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208250E+11 | 0.438976E+10 | 0.617796E+11 | 0.102908E+10 | 0.628823E+10 | 12675672.10 | 0.113081E+10 | 0.122698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.184317E+11 | 0.375368E+10 | 0.572952E+11 | 0.946226E+09 | 0.124166E+11 | 11960507.72 | 0.127411E+09 | 0.363037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198115E+11 | 0.344793E+10 | 0.605677E+11 | 0.100559E+10 | 0.160703E+11 | 12527707.06 | 5981585.85 | 0.505950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.196211E+11 | 0.318457E+10 | 0.594895E+11 | 0.989896E+09 | 0.214739E+11 | 12231776.97 | 0.00 | 0.764817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.184105E+11 | 0.336971E+10 | 0.583622E+11 | 0.961710E+09 | 0.194977E+11 | 12256437.81 | 0.00 | 0.709477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.206620E+11 | 0.370764E+10 | 0.617796E+11 | 0.102899E+10 | 0.196621E+11 | 12675672.10 | 0.00 | 0.718485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.185309E+11 | 0.400092E+10 | 0.572729E+11 | 0.946047E+09 | 0.158500E+11 | 11960507.72 | 0.00 | 0.577464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194588E+11 | 0.467103E+10 | 0.593671E+11 | 0.982628E+09 | 0.105858E+11 | 12379742.02 | 0.298518E+09 | 0.307925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.194427E+11 | 0.505049E+10 | 0.580818E+11 | 0.964435E+09 | 0.688928E+10 | 12059151.09 | 0.603085E+09 | 0.125327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.191854E+11 | 0.551714E+10 | 0.583511E+11 | 0.962126E+09 | 0.510423E+10 | 12256437.81 | 0.257765E+10 | 0.636562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.231883E+12 | 0.508773E+11 | 0.705434E+12 | 0.116887E+11 | 0.144321E+12 | 0.146559E+09 | 0.722856E+10 | 0.440466E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.177945E+11 | 0.318457E+10 | 0.537310E+11 | 0.889297E+09 | 0.440584E+10 | 11196021.66 | 0.00 | 0.286975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.208250E+11 | 0.551714E+10 | 0.617796E+11 | 0.102908E+10 | 0.214739E+11 | 12675672.10 | 0.257765E+10 | 0.764817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.660898E+09 | 0.00 | 0.106263E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.936533E+09 | 0.00 | 0.958363E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.979127E+09 | 0.00 | 0.106852E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 8366854.83 | 0.00 | 0.967200E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.975313E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.921215E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.904689E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.943571E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.911996E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.218496E+09 | 0.00 | 0.978047E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.443460E+09 | 0.00 | 0.990169E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.327821E+10 | 0.00 | 0.103529E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.652509E+10 | 0.00 | 0.117170E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.904689E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.327821E+10 | 0.00 | 0.106852E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 23793.64 | 20-JAN-16:00 | 5686.19 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 838.27 | 20-JAN-08:39 | 11645.11 | 27-JAN-16:49 | 6.85 | 12-JAN-08:09 | 75538.57 | 02-JAN-07:10 |
February | 23271.81 | 10-FEB-08:09 | 5686.19 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 837.85 | 10-FEB-08:20 | 9275.47 | 22-FEB-16:30 | 6.85 | 01-FEB-08:09 | 45203.60 | 13-FEB-07:10 |
March | 22342.37 | 21-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 836.61 | 21-MAR-07:19 | 14164.43 | 16-MAR-15:30 | 6.85 | 14-MAR-07:10 | 41369.25 | 27-MAR-06:10 |
April | 20486.96 | 04-APR-07:10 | 5686.19 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 834.15 | 04-APR-07:19 | 23287.78 | 24-APR-15:50 | 6.85 | 02-APR-16:30 | 8501.41 | 07-APR-06:19 |
May | 20037.32 | 26-MAY-08:30 | 5686.19 | 01-MAY-05:10 | 45864.70 | 01-MAY-07:10 | 833.47 | 26-MAY-07:19 | 25972.34 | 08-MAY-15:00 | 6.85 | 07-MAY-15:30 | 3447.49 | 01-MAY-06:19 |
June | 19860.60 | 27-JUN-07:10 | 5686.19 | 01-JUN-05:10 | 45864.70 | 01-JUN-07:10 | 833.32 | 27-JUN-07:19 | 28646.28 | 19-JUN-14:00 | 6.85 | 01-JUN-17:10 | 0.00 | 01-JUN-00:10 |
July | 20208.24 | 13-JUL-15:00 | 5686.19 | 01-JUL-05:10 | 45864.70 | 03-JUL-07:10 | 833.70 | 27-JUL-07:19 | 27138.57 | 05-JUL-15:09 | 6.85 | 01-JUL-17:10 | 0.00 | 01-JUL-00:10 |
August | 22913.15 | 04-AUG-07:10 | 5686.19 | 01-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 837.37 | 04-AUG-07:19 | 27592.00 | 14-AUG-15:20 | 6.85 | 01-AUG-17:10 | 0.00 | 01-AUG-00:10 |
September | 21159.36 | 29-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 835.04 | 29-SEP-07:19 | 24900.07 | 05-SEP-15:00 | 6.85 | 04-SEP-15:50 | 0.00 | 01-SEP-00:10 |
October | 22403.42 | 27-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 836.69 | 27-OCT-07:19 | 21333.18 | 02-OCT-15:30 | 6.85 | 25-OCT-07:10 | 16739.02 | 26-OCT-06:10 |
November | 25003.79 | 28-NOV-16:30 | 5686.19 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 838.79 | 28-NOV-16:40 | 14001.50 | 02-NOV-15:50 | 6.85 | 20-NOV-07:10 | 31581.62 | 24-NOV-07:10 |
December | 25003.79 | 01-DEC-16:30 | 5686.19 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 838.79 | 01-DEC-16:40 | 10262.33 | 22-DEC-16:49 | 6.85 | 04-DEC-07:10 | 58416.38 | 18-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 19860.60 | 5686.19 | 45864.70 | 833.32 | 9275.47 | 6.85 | 0.00 | |||||||
Maximum of Months | 25003.79 | 5686.19 | 45864.70 | 838.79 | 28646.28 | 6.85 | 75538.57 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 35695.30 | 31-JAN-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16228.91 | 22-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 37032.50 | 16-MAR-15:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 61733.95 | 14-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 67284.98 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 92791.32 | 28-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 83588.17 | 19-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 86810.47 | 25-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 77088.67 | 08-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 68339.55 | 02-OCT-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 40775.62 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26972.04 | 22-DEC-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 16228.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 92791.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 114105.12 | 02-JAN-07:10 | 8334.71 | 21098.80 | 5686.19 | 243.70 | 3196.30 | 6.85 | 75538.57 | 0.00 | 0.00 |
February | 87794.77 | 22-FEB-16:10 | 19671.42 | 42072.41 | 0.00 | 831.72 | 9150.98 | 6.85 | 0.00 | 16061.40 | 0.00 |
March | 113778.14 | 16-MAR-15:30 | 19671.42 | 42072.41 | 0.00 | 831.72 | 14164.43 | 6.85 | 0.00 | 37031.31 | 0.00 |
April | 146084.59 | 14-APR-15:20 | 19671.42 | 42072.41 | 0.00 | 831.72 | 21768.24 | 6.85 | 0.00 | 61733.95 | 0.00 |
May | 152623.69 | 31-MAY-15:39 | 19671.42 | 42072.41 | 0.00 | 831.72 | 23670.86 | 6.85 | 0.00 | 66370.44 | 0.00 |
June | 179744.45 | 28-JUN-14:00 | 19671.42 | 40588.47 | 0.00 | 831.19 | 25855.21 | 6.85 | 0.00 | 92791.32 | 0.00 |
July | 171191.22 | 31-JUL-15:00 | 19671.42 | 42072.41 | 0.00 | 831.72 | 27054.85 | 6.85 | 0.00 | 81553.98 | 0.00 |
August | 173921.21 | 25-AUG-15:20 | 19671.42 | 42072.41 | 0.00 | 831.72 | 24528.34 | 6.85 | 0.00 | 86810.47 | 0.00 |
September | 162757.70 | 08-SEP-15:00 | 19671.42 | 42072.41 | 0.00 | 831.72 | 23086.63 | 6.85 | 0.00 | 77088.67 | 0.00 |
October | 147365.50 | 02-OCT-15:09 | 19671.42 | 42072.41 | 0.00 | 831.72 | 20431.24 | 6.85 | 0.00 | 64351.87 | 0.00 |
November | 114600.88 | 01-NOV-15:00 | 19806.07 | 42072.41 | 0.00 | 831.72 | 11807.70 | 6.85 | 0.00 | 40076.14 | 0.00 |
December | 99777.18 | 22-DEC-16:49 | 21005.88 | 42072.41 | 0.00 | 833.01 | 10262.33 | 6.85 | 0.00 | 25596.69 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 87794.77 | 8334.71 | 21098.80 | 0.00 | 243.70 | 3196.30 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 179744.45 | 21005.88 | 42072.41 | 5686.19 | 833.01 | 27054.85 | 6.85 | 75538.57 | 92791.32 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 20958.77 | 02-JAN-07:19 | 0.00 | 9781.69 | 23-JAN-12:50 | 0.00 |
February | 0.00 | 0.00 | 15642.97 | 28-FEB-07:10 | 0.00 | 9787.80 | 01-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 29249.16 | 27-MAR-06:19 | 0.00 | 9736.51 | 01-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 3909.04 | 21-APR-06:10 | 0.00 | 9609.62 | 03-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 9491.15 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9370.67 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9295.22 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9329.57 | 31-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 9419.79 | 28-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 13601.26 | 25-OCT-06:10 | 0.00 | 9550.49 | 31-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 18404.13 | 24-NOV-07:10 | 0.00 | 9673.16 | 29-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 31873.91 | 06-DEC-07:19 | 0.00 | 9757.12 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9295.22 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 31873.91 | 0.00 | 9787.80 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.28 | 0.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.36 | 1.33 | 27.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.45 | 4.00 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.69 | 7.50 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.65 | 9.50 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.65 | 4.83 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.51 | 4.83 | 27.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.48 | 1.33 | 27.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.28 | 0.17 | 19.28 | 53.67 | 27.55 | 33.33 | 27.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.28 | 0.17 | 19.28 | 15.67 | 27.69 | 9.50 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.39 | 0.17 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.69 | 11.00 | 27.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.88 | 12.33 | 27.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 28.08 | 11.50 | 28.18 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 27.97 | 14.83 | 28.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.95 | 10.33 | 28.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.82 | 8.83 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.54 | 5.00 | 27.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
Annual Sum or Average | 0.33 | 18.30 | 0.17 | 18.67 | 96.50 | 27.85 | 73.83 | 27.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.39 | 0.17 | 19.39 | 21.33 | 28.08 | 14.83 | 28.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.86 | 5.50 | 27.86 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.46 | 0.17 | 27.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.70 | 6.83 | 27.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.58 | 6.50 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.71 | 7.00 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.73 | 10.50 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.84 | 6.50 | 27.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.96 | 7.50 | 28.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.97 | 7.83 | 27.99 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.67 | 4.33 | 27.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.79 | 4.83 | 27.79 |
Annual Sum or Average | 0.00 | 0.00 | 88.83 | 27.78 | 67.50 | 27.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.97 | 10.50 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.49 | 1.00 | 27.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.50 | 0.33 | 27.53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.17 | 5.33 | 28.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 28.36 | 5.83 | 28.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 28.23 | 7.67 | 28.25 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 28.11 | 10.33 | 28.14 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 28.22 | 6.00 | 28.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.97 | 5.83 | 28.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.94 | 4.00 | 27.98 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.54 | 0.67 | 27.54 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.63 | 0.50 | 27.63 |
Annual Sum or Average | 0.00 | 0.00 | 89.83 | 28.14 | 47.50 | 28.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 28.36 | 10.33 | 28.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.39 | 1.17 | 27.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.36 | 3.17 | 27.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.24 | 2.33 | 27.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.34 | 2.00 | 27.35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.31 | 0.50 | 27.31 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 14.33 | 27.33 | 9.17 | 27.35 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.39 | 3.17 | 27.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.52 | 6.17 | 27.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.60 | 9.50 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.77 | 10.83 | 27.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.69 | 14.50 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.72 | 9.50 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.62 | 9.00 | 27.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.42 | 5.33 | 27.44 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 75.17 | 27.65 | 64.83 | 27.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.77 | 14.50 | 27.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.00 | 19.65 | 13.00 | 19.65 | 6.00 | 21.17 | 6.00 | 22.21 |
February | 16.67 | 19.16 | 16.67 | 19.16 | 0.17 | 19.20 | 0.17 | 19.24 |
March | 16.50 | 18.88 | 16.50 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
April | 1.00 | 20.17 | 1.00 | 20.17 | 19.50 | 24.98 | 19.50 | 25.21 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 27.83 | 25.29 | 27.83 | 25.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 49.83 | 26.35 | 49.67 | 26.34 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 47.50 | 26.27 | 46.00 | 26.25 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 59.33 | 26.16 | 57.00 | 26.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 75.50 | 25.73 | 73.50 | 25.71 |
October | 4.17 | 19.73 | 4.17 | 19.73 | 54.33 | 24.98 | 52.83 | 25.33 |
November | 4.50 | 20.01 | 4.50 | 20.01 | 11.00 | 23.41 | 11.00 | 24.40 |
December | 17.67 | 18.61 | 17.67 | 18.61 | 6.17 | 19.97 | 6.17 | 20.98 |
Annual Sum or Average | 73.50 | 19.15 | 73.50 | 19.15 | 357.17 | 24.01 | 349.67 | 24.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.88 | 0.00 | 18.88 |
Maximum of Months | 17.67 | 20.17 | 17.67 | 20.17 | 75.50 | 26.35 | 73.50 | 26.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.41 | 0.33 | 27.41 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.42 | 0.17 | 27.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.87 | 3.67 | 27.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.03 | 4.50 | 28.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 28.03 | 4.50 | 28.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.87 | 8.33 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.88 | 5.50 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.75 | 5.50 | 27.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.72 | 3.83 | 27.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.42 | 1.00 | 27.42 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.51 | 0.67 | 27.51 |
Annual Sum or Average | 0.00 | 0.00 | 69.33 | 27.87 | 38.00 | 27.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 28.03 | 8.33 | 28.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.31 | 0.33 | 27.31 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.51 | 5.17 | 27.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.47 | 6.67 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.43 | 3.17 | 27.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.37 | 3.33 | 27.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.36 | 0.67 | 27.36 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 29.83 | 27.46 | 19.33 | 27.46 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.51 | 6.67 | 27.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.38 | 0.17 | 27.38 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.71 | 8.83 | 27.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.77 | 12.83 | 27.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.95 | 11.17 | 28.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 27.84 | 14.67 | 27.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.85 | 9.33 | 27.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.67 | 9.00 | 27.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.58 | 4.00 | 27.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 82.00 | 27.80 | 70.00 | 27.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 27.95 | 14.67 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.89 | 6.33 | 27.89 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.40 | 1.00 | 27.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.58 | 5.83 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.40 | 5.17 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.50 | 5.83 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.55 | 9.17 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.69 | 5.50 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.53 | 8.17 | 27.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.51 | 9.17 | 27.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.72 | 5.33 | 27.72 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.82 | 6.00 | 27.82 |
Annual Sum or Average | 0.00 | 0.00 | 77.50 | 27.60 | 67.67 | 27.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.89 | 9.17 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.43 | 1.33 | 27.43 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.73 | 0.17 | 27.73 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.06 | 5.00 | 28.09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.30 | 5.17 | 28.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 28.13 | 6.00 | 28.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 28.02 | 8.83 | 28.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 28.10 | 5.17 | 28.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.88 | 5.17 | 27.94 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.87 | 3.83 | 27.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.53 | 0.83 | 27.53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.60 | 0.67 | 27.60 |
Annual Sum or Average | 0.00 | 0.00 | 74.33 | 28.05 | 42.17 | 28.07 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 28.30 | 8.83 | 28.35 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 174.83 | 23.93 | 44.67 | 24.26 | 0.00 | 24.26 |
February | 58.17 | 23.99 | 102.00 | 24.56 | 0.00 | 24.56 |
March | 109.50 | 24.04 | 84.17 | 24.61 | 0.00 | 24.61 |
April | 79.67 | 24.02 | 49.67 | 24.75 | 0.00 | 24.75 |
May | 39.17 | 24.01 | 56.00 | 25.27 | 0.00 | 25.27 |
June | 0.00 | 0.00 | 156.83 | 25.11 | 0.00 | 25.11 |
July | 7.00 | 24.00 | 413.33 | 24.52 | 0.00 | 24.52 |
August | 0.00 | 0.00 | 459.00 | 24.44 | 0.00 | 24.44 |
September | 0.00 | 0.00 | 413.50 | 24.57 | 0.00 | 24.57 |
October | 69.17 | 24.01 | 194.50 | 24.72 | 0.00 | 24.72 |
November | 135.33 | 24.01 | 146.00 | 24.46 | 2.33 | 24.45 |
December | 291.17 | 24.06 | 3.33 | 24.08 | 0.00 | 24.08 |
Annual Sum or Average | 964.00 | 24.01 | 2123.00 | 24.54 | 2.33 | 24.53 |
Minimum of Months | 0.00 | 0.00 | 3.33 | 24.08 | 0.00 | 24.08 |
Maximum of Months | 291.17 | 24.06 | 459.00 | 25.27 | 2.33 | 25.27 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 402.50 | 23.66 | 5.83 | 23.68 | 0.00 | 23.68 |
February | 337.17 | 23.55 | 6.83 | 23.57 | 0.00 | 23.57 |
March | 276.33 | 23.77 | 19.50 | 23.82 | 0.00 | 23.82 |
April | 162.00 | 24.00 | 24.00 | 24.21 | 0.00 | 24.21 |
May | 108.33 | 24.02 | 33.83 | 24.47 | 0.00 | 24.47 |
June | 7.33 | 24.00 | 121.83 | 25.00 | 0.00 | 25.00 |
July | 10.33 | 24.03 | 402.50 | 24.44 | 0.00 | 24.44 |
August | 6.33 | 24.00 | 453.00 | 24.34 | 1.17 | 24.34 |
September | 0.00 | 0.00 | 391.00 | 24.49 | 0.00 | 24.49 |
October | 167.67 | 23.96 | 134.83 | 24.26 | 0.00 | 24.26 |
November | 281.17 | 23.82 | 92.83 | 24.01 | 12.00 | 24.01 |
December | 478.50 | 23.57 | 0.00 | 23.57 | 0.00 | 23.57 |
Annual Sum or Average | 2237.67 | 23.73 | 1686.00 | 24.08 | 13.17 | 24.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.57 | 0.00 | 23.57 |
Maximum of Months | 478.50 | 24.03 | 453.00 | 25.00 | 12.00 | 25.00 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 468.67 | 23.22 | 13.00 | 23.13 | 13.00 | 23.04 |
February | 395.17 | 22.98 | 0.00 | 22.98 | 0.00 | 22.98 |
March | 357.50 | 23.40 | 11.50 | 23.39 | 4.67 | 23.36 |
April | 187.33 | 23.92 | 22.17 | 24.07 | 0.00 | 24.07 |
May | 123.17 | 24.04 | 39.50 | 24.46 | 0.00 | 24.46 |
June | 6.00 | 23.99 | 152.17 | 24.92 | 0.00 | 24.92 |
July | 11.83 | 24.00 | 408.50 | 24.49 | 1.17 | 24.49 |
August | 8.33 | 23.99 | 453.00 | 24.37 | 2.50 | 24.36 |
September | 1.00 | 23.93 | 391.83 | 24.49 | 0.00 | 24.49 |
October | 226.00 | 23.71 | 113.33 | 23.97 | 0.00 | 23.97 |
November | 341.83 | 23.29 | 67.83 | 23.44 | 15.83 | 23.45 |
December | 497.00 | 22.78 | 35.33 | 22.64 | 35.33 | 22.53 |
Annual Sum or Average | 2623.83 | 23.27 | 1708.17 | 23.72 | 72.50 | 23.68 |
Minimum of Months | 1.00 | 22.78 | 0.00 | 22.64 | 0.00 | 22.53 |
Maximum of Months | 497.00 | 24.04 | 453.00 | 24.92 | 35.33 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.83 | 22.36 | 78.50 | 22.05 | 78.50 | 21.81 |
February | 432.50 | 22.02 | 38.17 | 21.88 | 38.17 | 21.75 |
March | 410.50 | 22.62 | 43.83 | 22.49 | 33.17 | 22.34 |
April | 203.17 | 23.56 | 60.00 | 23.94 | 0.67 | 23.93 |
May | 102.17 | 23.89 | 93.00 | 24.64 | 0.33 | 24.65 |
June | 20.67 | 26.57 | 313.67 | 24.89 | 17.00 | 25.00 |
July | 45.00 | 26.17 | 450.50 | 24.80 | 42.00 | 24.92 |
August | 32.83 | 25.60 | 472.50 | 24.54 | 25.50 | 24.62 |
September | 56.33 | 25.50 | 414.50 | 24.67 | 39.33 | 24.79 |
October | 281.67 | 23.13 | 129.17 | 23.48 | 14.33 | 23.44 |
November | 417.67 | 22.51 | 104.17 | 22.45 | 81.17 | 22.34 |
December | 497.00 | 21.68 | 186.00 | 21.36 | 186.00 | 21.17 |
Annual Sum or Average | 2996.33 | 22.64 | 2384.00 | 23.21 | 556.17 | 23.09 |
Minimum of Months | 20.67 | 21.68 | 38.17 | 21.36 | 0.33 | 21.17 |
Maximum of Months | 497.00 | 26.57 | 472.50 | 24.89 | 186.00 | 25.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 405.33 | 22.81 | 58.00 | 22.54 | 50.67 | 22.31 |
February | 340.67 | 22.33 | 44.17 | 22.31 | 24.67 | 22.17 |
March | 290.50 | 22.85 | 72.33 | 22.99 | 19.00 | 22.85 |
April | 100.67 | 23.91 | 194.17 | 24.56 | 9.17 | 24.64 |
May | 60.50 | 25.03 | 247.33 | 24.90 | 19.67 | 25.05 |
June | 40.83 | 27.12 | 411.33 | 24.89 | 40.33 | 25.07 |
July | 65.33 | 26.75 | 469.67 | 24.96 | 64.67 | 25.16 |
August | 50.67 | 26.52 | 492.17 | 24.72 | 48.33 | 24.88 |
September | 57.67 | 26.24 | 442.00 | 24.78 | 49.50 | 24.95 |
October | 194.67 | 23.43 | 189.67 | 24.02 | 16.67 | 24.03 |
November | 343.50 | 22.90 | 94.67 | 22.92 | 55.50 | 22.84 |
December | 491.17 | 22.43 | 104.83 | 22.07 | 104.83 | 21.83 |
Annual Sum or Average | 2441.50 | 23.17 | 2820.33 | 23.78 | 503.00 | 23.77 |
Minimum of Months | 40.83 | 22.33 | 44.17 | 22.07 | 9.17 | 21.83 |
Maximum of Months | 491.17 | 27.12 | 492.17 | 24.96 | 104.83 | 25.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 256.83 | 22.71 | 175.50 | 23.20 | 41.33 | 23.07 |
February | 285.33 | 22.17 | 108.17 | 22.56 | 22.00 | 22.44 |
March | 276.83 | 22.67 | 106.67 | 22.93 | 24.17 | 22.78 |
April | 154.67 | 23.63 | 158.17 | 24.24 | 5.67 | 24.29 |
May | 115.33 | 23.93 | 136.17 | 24.56 | 3.17 | 24.59 |
June | 32.67 | 25.79 | 295.00 | 24.87 | 18.83 | 24.99 |
July | 53.83 | 26.05 | 444.17 | 24.81 | 46.83 | 24.94 |
August | 39.67 | 25.94 | 478.17 | 24.60 | 32.67 | 24.70 |
September | 58.33 | 26.00 | 433.67 | 24.77 | 45.50 | 24.93 |
October | 181.50 | 23.67 | 239.17 | 24.22 | 29.50 | 24.33 |
November | 246.67 | 22.89 | 190.33 | 23.37 | 54.50 | 23.27 |
December | 324.00 | 22.40 | 157.17 | 22.50 | 90.50 | 22.25 |
Annual Sum or Average | 2025.67 | 23.12 | 2922.33 | 23.87 | 414.67 | 23.85 |
Minimum of Months | 32.67 | 22.17 | 106.67 | 22.50 | 3.17 | 22.25 |
Maximum of Months | 324.00 | 26.05 | 478.17 | 24.87 | 90.50 | 24.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 380.50 | 22.31 | 95.50 | 22.19 | 65.00 | 21.94 |
February | 368.33 | 22.02 | 56.00 | 22.00 | 34.00 | 21.87 |
March | 331.33 | 22.57 | 90.83 | 22.69 | 31.00 | 22.53 |
April | 166.83 | 23.84 | 163.67 | 24.32 | 15.83 | 24.45 |
May | 117.00 | 24.44 | 203.67 | 24.73 | 20.67 | 24.88 |
June | 36.33 | 26.30 | 342.00 | 24.92 | 26.33 | 25.06 |
July | 64.00 | 26.25 | 454.00 | 24.89 | 59.33 | 25.04 |
August | 41.67 | 25.93 | 482.83 | 24.63 | 35.00 | 24.73 |
September | 63.33 | 25.74 | 426.83 | 24.74 | 49.33 | 24.89 |
October | 234.17 | 23.29 | 185.50 | 23.82 | 23.67 | 23.85 |
November | 337.17 | 22.58 | 137.17 | 22.72 | 73.50 | 22.60 |
December | 443.83 | 21.90 | 160.50 | 21.61 | 151.00 | 21.38 |
Annual Sum or Average | 2584.50 | 22.85 | 2798.50 | 23.53 | 584.67 | 23.47 |
Minimum of Months | 36.33 | 21.90 | 56.00 | 21.61 | 15.83 | 21.38 |
Maximum of Months | 443.83 | 26.30 | 482.83 | 24.92 | 151.00 | 25.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.00 | 22.78 | 26.50 | 22.66 | 26.50 | 22.54 |
February | 452.17 | 22.37 | 2.00 | 22.36 | 2.00 | 22.36 |
March | 476.33 | 22.83 | 14.33 | 22.76 | 14.17 | 22.71 |
April | 262.00 | 23.79 | 13.67 | 23.85 | 0.00 | 23.85 |
May | 152.50 | 23.98 | 25.00 | 24.23 | 0.00 | 24.23 |
June | 2.00 | 24.86 | 220.83 | 24.93 | 0.50 | 24.93 |
July | 10.83 | 25.41 | 450.00 | 24.64 | 9.50 | 24.66 |
August | 7.17 | 25.55 | 469.17 | 24.50 | 6.67 | 24.51 |
September | 22.00 | 26.34 | 435.00 | 24.66 | 22.00 | 24.73 |
October | 218.50 | 23.74 | 134.17 | 24.07 | 0.17 | 24.07 |
November | 367.83 | 23.35 | 72.17 | 23.51 | 29.50 | 23.56 |
December | 497.00 | 22.58 | 34.33 | 22.47 | 34.33 | 22.37 |
Annual Sum or Average | 2967.33 | 23.03 | 1897.17 | 23.58 | 145.33 | 23.56 |
Minimum of Months | 2.00 | 22.37 | 2.00 | 22.36 | 0.00 | 22.36 |
Maximum of Months | 499.00 | 26.34 | 469.17 | 24.93 | 34.33 | 24.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 379.33 | 23.33 | 22.00 | 23.35 | 5.67 | 23.31 |
February | 344.00 | 22.86 | 21.00 | 22.96 | 0.00 | 22.96 |
March | 305.33 | 23.20 | 40.50 | 23.37 | 4.67 | 23.34 |
April | 81.83 | 23.92 | 152.33 | 24.65 | 0.83 | 24.66 |
May | 36.50 | 24.38 | 178.83 | 24.99 | 3.33 | 25.04 |
June | 23.83 | 27.18 | 393.17 | 24.82 | 23.83 | 24.95 |
July | 45.83 | 26.79 | 470.83 | 24.91 | 45.83 | 25.06 |
August | 35.50 | 26.84 | 495.00 | 24.72 | 35.50 | 24.85 |
September | 43.17 | 26.77 | 463.50 | 24.81 | 43.17 | 24.97 |
October | 107.17 | 23.95 | 214.17 | 24.54 | 3.50 | 24.57 |
November | 251.67 | 23.71 | 111.00 | 23.95 | 31.67 | 23.98 |
December | 438.67 | 23.27 | 9.33 | 23.23 | 7.83 | 23.19 |
Annual Sum or Average | 2092.83 | 23.59 | 2571.67 | 24.20 | 205.83 | 24.27 |
Minimum of Months | 23.83 | 22.86 | 9.33 | 22.96 | 0.00 | 22.96 |
Maximum of Months | 438.67 | 27.18 | 495.00 | 24.99 | 45.83 | 25.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 196.83 | 23.07 | 153.00 | 23.82 | 10.00 | 23.80 |
February | 321.17 | 22.30 | 55.00 | 22.54 | 8.83 | 22.45 |
March | 333.67 | 22.61 | 65.00 | 22.73 | 18.83 | 22.57 |
April | 152.67 | 23.36 | 96.50 | 24.08 | 0.83 | 24.07 |
May | 150.33 | 23.70 | 63.17 | 24.34 | 0.00 | 24.34 |
June | 17.67 | 24.60 | 226.67 | 25.28 | 3.50 | 25.31 |
July | 44.67 | 25.21 | 449.83 | 24.86 | 40.67 | 24.89 |
August | 49.50 | 25.74 | 483.50 | 24.85 | 47.83 | 24.93 |
September | 69.83 | 26.16 | 460.67 | 25.04 | 67.50 | 25.18 |
October | 114.50 | 24.02 | 283.33 | 24.77 | 31.67 | 24.90 |
November | 162.83 | 23.37 | 222.83 | 24.13 | 34.67 | 24.15 |
December | 282.17 | 22.77 | 107.83 | 23.21 | 24.00 | 23.09 |
Annual Sum or Average | 1895.83 | 23.22 | 2667.33 | 24.17 | 288.33 | 24.20 |
Minimum of Months | 17.67 | 22.30 | 55.00 | 22.54 | 0.00 | 22.45 |
Maximum of Months | 333.67 | 26.16 | 483.50 | 25.28 | 67.50 | 25.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 376.50 | 23.16 | 33.17 | 23.20 | 11.50 | 23.12 |
February | 385.00 | 22.64 | 8.00 | 22.69 | 0.00 | 22.69 |
March | 356.17 | 23.04 | 40.00 | 23.16 | 6.00 | 23.13 |
April | 131.00 | 23.96 | 133.00 | 24.43 | 3.33 | 24.47 |
May | 83.50 | 24.32 | 162.83 | 24.77 | 6.67 | 24.84 |
June | 13.67 | 26.82 | 331.33 | 24.87 | 12.00 | 24.95 |
July | 35.33 | 26.50 | 466.17 | 24.83 | 33.83 | 24.95 |
August | 26.67 | 26.52 | 488.17 | 24.65 | 26.67 | 24.74 |
September | 39.33 | 26.66 | 458.67 | 24.80 | 39.33 | 24.93 |
October | 135.33 | 24.00 | 205.33 | 24.45 | 8.17 | 24.51 |
November | 250.17 | 23.63 | 130.83 | 23.95 | 25.67 | 23.99 |
December | 426.67 | 22.98 | 23.50 | 22.98 | 13.00 | 22.92 |
Annual Sum or Average | 2259.33 | 23.39 | 2481.00 | 24.05 | 186.17 | 24.11 |
Minimum of Months | 13.67 | 22.64 | 8.00 | 22.69 | 0.00 | 22.69 |
Maximum of Months | 426.67 | 26.82 | 488.17 | 24.87 | 39.33 | 24.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 492.00 | 22.86 | 24.33 | 22.73 | 24.33 | 22.61 |
February | 419.83 | 22.55 | 3.33 | 22.53 | 3.33 | 22.52 |
March | 381.33 | 23.00 | 23.17 | 22.98 | 11.00 | 22.92 |
April | 185.67 | 23.81 | 44.33 | 24.11 | 0.00 | 24.11 |
May | 86.67 | 24.02 | 68.33 | 24.82 | 0.00 | 24.82 |
June | 7.17 | 27.11 | 275.67 | 24.94 | 7.17 | 24.99 |
July | 28.67 | 26.12 | 450.33 | 24.74 | 28.33 | 24.82 |
August | 18.83 | 25.48 | 467.50 | 24.52 | 15.50 | 24.56 |
September | 30.33 | 26.18 | 414.83 | 24.68 | 28.67 | 24.77 |
October | 254.83 | 23.53 | 122.33 | 23.86 | 1.17 | 23.87 |
November | 393.00 | 23.02 | 67.83 | 23.15 | 36.50 | 23.18 |
December | 497.00 | 22.29 | 66.33 | 22.10 | 66.33 | 21.95 |
Annual Sum or Average | 2795.33 | 23.01 | 2028.33 | 23.61 | 222.33 | 23.59 |
Minimum of Months | 7.17 | 22.29 | 3.33 | 22.10 | 0.00 | 21.95 |
Maximum of Months | 497.00 | 27.11 | 467.50 | 24.94 | 66.33 | 24.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 316.83 | 23.03 | 26.50 | 23.08 | 8.00 | 23.00 |
February | 279.17 | 22.67 | 30.00 | 22.85 | 2.33 | 22.83 |
March | 246.00 | 23.13 | 61.50 | 23.41 | 7.50 | 23.35 |
April | 87.50 | 24.16 | 140.17 | 24.81 | 8.17 | 24.90 |
May | 43.50 | 25.15 | 181.33 | 25.20 | 14.83 | 25.33 |
June | 33.83 | 27.17 | 322.17 | 25.07 | 33.83 | 25.25 |
July | 58.00 | 26.69 | 395.33 | 25.08 | 58.00 | 25.26 |
August | 41.67 | 26.67 | 411.17 | 24.83 | 41.67 | 24.99 |
September | 45.67 | 26.66 | 370.50 | 24.93 | 45.17 | 25.10 |
October | 153.33 | 23.68 | 160.33 | 24.34 | 6.83 | 24.40 |
November | 273.67 | 23.26 | 76.17 | 23.48 | 30.33 | 23.50 |
December | 394.17 | 22.77 | 39.17 | 22.59 | 37.50 | 22.43 |
Annual Sum or Average | 1973.33 | 23.46 | 2214.33 | 24.13 | 294.17 | 24.21 |
Minimum of Months | 33.83 | 22.67 | 26.50 | 22.59 | 2.33 | 22.43 |
Maximum of Months | 394.17 | 27.17 | 411.17 | 25.20 | 58.00 | 25.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 233.33 | 23.28 | 167.50 | 23.83 | 17.17 | 23.85 |
February | 259.17 | 22.72 | 98.83 | 23.20 | 2.83 | 23.19 |
March | 249.17 | 23.09 | 96.83 | 23.44 | 7.00 | 23.39 |
April | 129.50 | 23.82 | 139.17 | 24.39 | 1.67 | 24.41 |
May | 92.33 | 23.98 | 101.67 | 24.72 | 0.00 | 24.72 |
June | 14.17 | 25.92 | 259.33 | 24.91 | 8.67 | 24.98 |
July | 43.33 | 26.03 | 443.67 | 24.77 | 39.50 | 24.88 |
August | 31.33 | 26.03 | 478.17 | 24.59 | 27.50 | 24.68 |
September | 44.17 | 26.68 | 438.50 | 24.80 | 44.17 | 24.96 |
October | 148.00 | 24.10 | 247.33 | 24.51 | 23.17 | 24.65 |
November | 206.83 | 23.44 | 194.83 | 23.99 | 31.33 | 24.03 |
December | 293.33 | 22.93 | 111.17 | 23.29 | 32.17 | 23.21 |
Annual Sum or Average | 1744.67 | 23.50 | 2777.00 | 24.20 | 235.17 | 24.26 |
Minimum of Months | 14.17 | 22.72 | 96.83 | 23.20 | 0.00 | 23.19 |
Maximum of Months | 293.33 | 26.68 | 478.17 | 24.91 | 44.17 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 366.00 | 22.89 | 50.83 | 22.97 | 14.33 | 22.86 |
February | 351.33 | 22.59 | 26.83 | 22.68 | 3.50 | 22.66 |
March | 305.00 | 23.02 | 71.33 | 23.23 | 9.83 | 23.17 |
April | 138.33 | 24.05 | 153.17 | 24.47 | 10.83 | 24.58 |
May | 89.83 | 24.60 | 190.83 | 24.86 | 16.33 | 24.99 |
June | 26.17 | 26.67 | 330.83 | 24.94 | 22.50 | 25.07 |
July | 55.67 | 26.28 | 457.83 | 24.86 | 52.67 | 25.01 |
August | 34.83 | 26.09 | 482.83 | 24.63 | 31.67 | 24.72 |
September | 41.67 | 26.50 | 433.17 | 24.77 | 41.67 | 24.91 |
October | 200.00 | 23.71 | 182.17 | 24.17 | 11.67 | 24.25 |
November | 303.50 | 23.12 | 115.83 | 23.45 | 34.17 | 23.47 |
December | 433.67 | 22.49 | 67.00 | 22.37 | 55.17 | 22.20 |
Annual Sum or Average | 2346.00 | 23.26 | 2562.67 | 23.93 | 304.33 | 23.97 |
Minimum of Months | 26.17 | 22.49 | 26.83 | 22.37 | 3.50 | 22.20 |
Maximum of Months | 433.67 | 26.67 | 482.83 | 24.94 | 55.17 | 25.07 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.27808 | 21.04897 | 0.28564 | 7.02637 |
February | 454.00000 | 24.28656 | 33.29979 | 0.35773 | 7.86241 |
March | 514.00000 | 24.33163 | 26.53884 | 0.33982 | 7.66090 |
April | 485.00000 | 24.37922 | 18.64198 | 0.33279 | 7.53250 |
May | 508.00000 | 24.40050 | 18.04832 | -0.5047 | 10.75028 |
June | 496.00000 | 24.38673 | 25.22986 | -0.4370 | 9.42811 |
July | 497.00000 | 24.46955 | 41.32627 | -0.3055 | 7.50348 |
August | 514.00000 | 24.40147 | 44.05359 | -0.3033 | 7.41138 |
September | 485.00000 | 24.49039 | 43.18958 | -0.2858 | 7.43874 |
October | 502.00000 | 24.47134 | 26.00619 | 0.40537 | 8.91747 |
November | 489.00000 | 24.41994 | 26.07607 | 0.37234 | 8.47004 |
December | 497.00000 | 24.28231 | 16.21439 | 0.24305 | 6.38031 |
Annual Sum or Average | 5943.00000 | 24.38351 | 28.27597 | 0.03849 | 8.03653 |
Minimum of Months | 454.00000 | 24.27808 | 16.21439 | -0.5047 | 6.38031 |
Maximum of Months | 514.00000 | 24.49039 | 44.05359 | 0.40537 | 10.75028 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.81111 | 23.20931 | 0.16314 | 6.06217 |
February | 454.00000 | 23.69361 | 35.44856 | 0.20522 | 6.16010 |
March | 514.00000 | 23.98053 | 27.47576 | 0.23773 | 6.47849 |
April | 485.00000 | 24.23528 | 19.54067 | 0.28673 | 6.89927 |
May | 508.00000 | 24.30116 | 18.90383 | -0.5552 | 11.77021 |
June | 496.00000 | 24.32193 | 26.15962 | -0.4712 | 10.02607 |
July | 497.00000 | 24.39355 | 43.18627 | -0.3369 | 7.85535 |
August | 514.00000 | 24.32043 | 46.03219 | -0.3412 | 7.81814 |
September | 485.00000 | 24.39804 | 44.82670 | -0.3326 | 7.92990 |
October | 502.00000 | 24.25697 | 27.14758 | 0.33592 | 7.79184 |
November | 489.00000 | 24.04112 | 27.59196 | 0.25998 | 7.00780 |
December | 497.00000 | 23.59984 | 17.38462 | 0.05991 | 5.50520 |
Annual Sum or Average | 5943.00000 | 24.11550 | 29.70698 | -0.0434 | 7.62430 |
Minimum of Months | 454.00000 | 23.59984 | 17.38462 | -0.5552 | 5.50520 |
Maximum of Months | 514.00000 | 24.39804 | 46.03219 | 0.33592 | 11.77021 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.28429 | 24.26109 | 0.02922 | 6.07738 |
February | 454.00000 | 23.11185 | 36.79274 | 0.06006 | 5.90986 |
March | 514.00000 | 23.62336 | 27.84965 | 0.14479 | 6.20228 |
April | 485.00000 | 24.16877 | 19.58501 | 0.27292 | 6.83982 |
May | 508.00000 | 24.29733 | 18.92986 | -0.5471 | 11.66901 |
June | 496.00000 | 24.35808 | 25.85560 | -0.4394 | 9.58863 |
July | 497.00000 | 24.44453 | 42.52732 | -0.3049 | 7.57257 |
August | 514.00000 | 24.34354 | 45.60412 | -0.3218 | 7.63086 |
September | 485.00000 | 24.40087 | 44.50867 | -0.3268 | 7.88002 |
October | 502.00000 | 24.04555 | 27.30167 | 0.27713 | 7.34349 |
November | 489.00000 | 23.54814 | 28.24688 | 0.13194 | 6.54703 |
December | 497.00000 | 22.77570 | 18.18735 | -0.1452 | 6.69653 |
Annual Sum or Average | 5943.00000 | 23.87208 | 29.92727 | -0.0995 | 7.51250 |
Minimum of Months | 454.00000 | 22.77570 | 18.18735 | -0.5471 | 5.90986 |
Maximum of Months | 514.00000 | 24.44453 | 45.60412 | 0.27713 | 11.66901 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.37399 | 25.88480 | -0.1906 | 8.18809 |
February | 454.00000 | 22.11553 | 40.39045 | -0.1717 | 7.28036 |
March | 514.00000 | 22.91414 | 29.92471 | -0.0193 | 7.13067 |
April | 485.00000 | 24.04813 | 19.97081 | 0.25459 | 7.31214 |
May | 508.00000 | 24.33974 | 18.71516 | -0.4973 | 11.30173 |
June | 496.00000 | 24.52559 | 25.36936 | -0.3039 | 8.18559 |
July | 497.00000 | 24.61738 | 42.80658 | -0.1756 | 7.01811 |
August | 514.00000 | 24.44228 | 45.85402 | -0.2340 | 7.17113 |
September | 485.00000 | 24.46214 | 45.57771 | -0.2616 | 7.77907 |
October | 502.00000 | 23.64943 | 28.72864 | 0.18877 | 7.84579 |
November | 489.00000 | 22.73825 | 30.81120 | -0.0594 | 7.65291 |
December | 497.00000 | 21.67992 | 20.10076 | -0.4121 | 10.74056 |
Annual Sum or Average | 5943.00000 | 23.50176 | 31.11503 | -0.1577 | 8.14308 |
Minimum of Months | 454.00000 | 21.67992 | 18.71516 | -0.4973 | 7.01811 |
Maximum of Months | 514.00000 | 24.61738 | 45.85402 | 0.25459 | 11.30173 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.06486 | 24.38149 | -0.0064 | 7.39891 |
February | 454.00000 | 22.77484 | 38.71320 | 0.00076 | 7.18822 |
March | 514.00000 | 23.44327 | 28.49805 | 0.13479 | 7.36159 |
April | 485.00000 | 24.34068 | 19.12302 | 0.39687 | 9.55437 |
May | 508.00000 | 24.48636 | 18.32625 | -0.3409 | 9.28555 |
June | 496.00000 | 24.57711 | 25.16292 | -0.1814 | 7.44203 |
July | 497.00000 | 24.68465 | 42.52611 | -0.0596 | 6.86408 |
August | 514.00000 | 24.51690 | 45.42913 | -0.1132 | 6.80750 |
September | 485.00000 | 24.53157 | 45.14699 | -0.1620 | 7.27527 |
October | 502.00000 | 24.02237 | 27.58087 | 0.32375 | 9.38057 |
November | 489.00000 | 23.26368 | 29.59011 | 0.08888 | 7.26391 |
December | 497.00000 | 22.44577 | 19.76798 | -0.2160 | 8.66096 |
Annual Sum or Average | 5943.00000 | 23.85348 | 30.29626 | -0.0121 | 7.87621 |
Minimum of Months | 454.00000 | 22.44577 | 18.32625 | -0.3409 | 6.80750 |
Maximum of Months | 514.00000 | 24.68465 | 45.42913 | 0.39687 | 9.55437 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.52204 | 22.01592 | 0.17184 | 9.22586 |
February | 454.00000 | 22.94604 | 36.75242 | 0.06932 | 7.95524 |
March | 514.00000 | 23.39402 | 27.97596 | 0.13409 | 7.85165 |
April | 485.00000 | 24.17593 | 19.40400 | 0.33068 | 8.69459 |
May | 508.00000 | 24.33363 | 18.65252 | -0.4814 | 11.38933 |
June | 496.00000 | 24.49405 | 25.44428 | -0.3239 | 8.52543 |
July | 497.00000 | 24.61014 | 42.81037 | -0.1725 | 7.20486 |
August | 514.00000 | 24.46507 | 45.64668 | -0.1896 | 7.06350 |
September | 485.00000 | 24.52887 | 45.04068 | -0.1667 | 7.43577 |
October | 502.00000 | 24.08854 | 26.87598 | 0.37529 | 10.53947 |
November | 489.00000 | 23.61482 | 27.65412 | 0.22683 | 8.96649 |
December | 497.00000 | 23.12065 | 16.75500 | -0.0008 | 9.56615 |
Annual Sum or Average | 5943.00000 | 23.94747 | 29.53891 | -0.0039 | 8.70902 |
Minimum of Months | 454.00000 | 22.94604 | 16.75500 | -0.4814 | 7.06350 |
Maximum of Months | 514.00000 | 24.61014 | 45.64668 | 0.37529 | 11.38933 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.80379 | 24.97902 | -0.0580 | 8.46654 |
February | 454.00000 | 22.41843 | 39.68311 | -0.0805 | 7.48896 |
March | 514.00000 | 23.15457 | 29.54914 | 0.06733 | 7.74351 |
April | 485.00000 | 24.17430 | 19.78960 | 0.34828 | 9.18974 |
May | 508.00000 | 24.39401 | 18.69687 | -0.3972 | 10.62856 |
June | 496.00000 | 24.56469 | 25.36334 | -0.2135 | 7.96560 |
July | 497.00000 | 24.65592 | 42.79639 | -0.1139 | 7.28826 |
August | 514.00000 | 24.48942 | 45.77124 | -0.1580 | 7.21476 |
September | 485.00000 | 24.51758 | 45.46084 | -0.1879 | 7.57337 |
October | 502.00000 | 23.84086 | 28.32177 | 0.27490 | 9.14943 |
November | 489.00000 | 23.10574 | 29.95901 | 0.05840 | 8.22904 |
December | 497.00000 | 22.16634 | 19.52953 | -0.2786 | 10.17354 |
Annual Sum or Average | 5943.00000 | 23.69910 | 30.76534 | -0.0624 | 8.43255 |
Minimum of Months | 454.00000 | 22.16634 | 18.69687 | -0.3972 | 7.21476 |
Maximum of Months | 514.00000 | 24.65592 | 45.77124 | 0.34828 | 10.62856 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.79330 | 25.86185 | -0.0869 | 6.36117 |
February | 454.00000 | 22.37846 | 40.37652 | -0.1059 | 5.98128 |
March | 514.00000 | 22.92380 | 31.45026 | -0.0211 | 6.21784 |
April | 485.00000 | 24.00970 | 20.19675 | 0.22130 | 6.43823 |
May | 508.00000 | 24.24606 | 18.77317 | -0.5749 | 12.32878 |
June | 496.00000 | 24.45553 | 25.28059 | -0.3771 | 8.70563 |
July | 497.00000 | 24.58378 | 41.84008 | -0.2167 | 6.87928 |
August | 514.00000 | 24.44340 | 44.57742 | -0.2510 | 6.99066 |
September | 485.00000 | 24.51678 | 44.14644 | -0.2405 | 7.20124 |
October | 502.00000 | 24.10234 | 27.88440 | 0.30522 | 7.82432 |
November | 489.00000 | 23.53718 | 29.60183 | 0.14094 | 6.56279 |
December | 497.00000 | 22.57855 | 20.27738 | -0.1738 | 6.68729 |
Annual Sum or Average | 5943.00000 | 23.72200 | 30.79587 | -0.1164 | 7.36560 |
Minimum of Months | 454.00000 | 22.37846 | 18.77317 | -0.5749 | 5.98128 |
Maximum of Months | 514.00000 | 24.58378 | 44.57742 | 0.30522 | 12.32878 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.55180 | 24.01398 | 0.11630 | 6.30013 |
February | 454.00000 | 23.16912 | 38.49138 | 0.09643 | 6.26015 |
March | 514.00000 | 23.62017 | 29.67780 | 0.17113 | 6.67896 |
April | 485.00000 | 24.39368 | 18.99342 | 0.38580 | 8.82356 |
May | 508.00000 | 24.49082 | 18.09831 | -0.3844 | 9.32404 |
June | 496.00000 | 24.56261 | 24.91078 | -0.2323 | 7.40525 |
July | 497.00000 | 24.69129 | 41.39418 | -0.0848 | 6.47429 |
August | 514.00000 | 24.54904 | 44.00316 | -0.1152 | 6.43181 |
September | 485.00000 | 24.60338 | 43.65719 | -0.1310 | 6.72047 |
October | 502.00000 | 24.38527 | 26.77450 | 0.42731 | 9.92402 |
November | 489.00000 | 23.97053 | 28.25330 | 0.27483 | 7.39603 |
December | 497.00000 | 23.39110 | 19.36242 | 0.03373 | 6.12279 |
Annual Sum or Average | 5943.00000 | 24.12059 | 29.74761 | 0.04502 | 7.32819 |
Minimum of Months | 454.00000 | 23.16912 | 18.09831 | -0.3844 | 6.12279 |
Maximum of Months | 514.00000 | 24.69129 | 44.00316 | 0.42731 | 9.92402 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.92067 | 21.23602 | 0.29110 | 8.70619 |
February | 454.00000 | 22.88689 | 36.61703 | 0.08435 | 6.97379 |
March | 514.00000 | 23.21503 | 28.24498 | 0.10037 | 7.20575 |
April | 485.00000 | 24.15602 | 18.42419 | 0.29941 | 7.89485 |
May | 508.00000 | 24.28756 | 17.29945 | -0.5538 | 12.52353 |
June | 496.00000 | 24.64980 | 23.94314 | -0.3491 | 8.80470 |
July | 497.00000 | 24.76235 | 41.49899 | -0.1646 | 6.82338 |
August | 514.00000 | 24.71177 | 43.87788 | -0.1375 | 6.66012 |
September | 485.00000 | 24.81650 | 43.03009 | -0.0768 | 6.87287 |
October | 502.00000 | 24.48264 | 25.57347 | 0.48712 | 11.95186 |
November | 489.00000 | 24.08438 | 26.72087 | 0.37733 | 9.49669 |
December | 497.00000 | 23.55156 | 16.09995 | 0.15761 | 8.44106 |
Annual Sum or Average | 5943.00000 | 24.13408 | 28.49673 | 0.04113 | 8.54539 |
Minimum of Months | 454.00000 | 22.88689 | 16.09995 | -0.5538 | 6.66012 |
Maximum of Months | 514.00000 | 24.81650 | 43.87788 | 0.48712 | 12.52353 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.45860 | 24.45251 | 0.09820 | 6.53066 |
February | 454.00000 | 22.86853 | 39.40029 | 0.02474 | 6.02588 |
March | 514.00000 | 23.40665 | 30.51715 | 0.11682 | 6.57258 |
April | 485.00000 | 24.30756 | 19.46041 | 0.35513 | 8.41128 |
May | 508.00000 | 24.42767 | 18.39136 | -0.4289 | 10.08706 |
June | 496.00000 | 24.55396 | 25.08537 | -0.2596 | 7.72552 |
July | 497.00000 | 24.67063 | 41.68473 | -0.1349 | 6.78533 |
August | 514.00000 | 24.52639 | 44.34846 | -0.1577 | 6.67870 |
September | 485.00000 | 24.60276 | 43.90423 | -0.1523 | 6.85967 |
October | 502.00000 | 24.33336 | 27.24843 | 0.40368 | 9.45746 |
November | 489.00000 | 23.95308 | 28.48336 | 0.27382 | 7.68448 |
December | 497.00000 | 23.17388 | 19.41717 | -0.0152 | 6.48158 |
Annual Sum or Average | 5943.00000 | 24.03042 | 30.14227 | 0.00895 | 7.45193 |
Minimum of Months | 454.00000 | 22.86853 | 18.39136 | -0.4289 | 6.02588 |
Maximum of Months | 514.00000 | 24.67063 | 44.34846 | 0.40368 | 10.08706 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.88690 | 25.48928 | -0.0579 | 6.52470 |
February | 454.00000 | 22.66001 | 39.24607 | -0.0341 | 6.00439 |
March | 514.00000 | 23.28749 | 29.57463 | 0.07608 | 6.37784 |
April | 485.00000 | 24.15330 | 19.82731 | 0.27515 | 7.04908 |
May | 508.00000 | 24.37175 | 18.61127 | -0.4990 | 10.90502 |
June | 496.00000 | 24.52043 | 25.49160 | -0.3287 | 8.31466 |
July | 497.00000 | 24.61053 | 43.19108 | -0.1977 | 6.96612 |
August | 514.00000 | 24.44055 | 46.05845 | -0.2494 | 7.11129 |
September | 485.00000 | 24.48607 | 45.51877 | -0.2636 | 7.58056 |
October | 502.00000 | 23.92191 | 28.47055 | 0.25712 | 7.58895 |
November | 489.00000 | 23.23505 | 30.19998 | 0.06804 | 6.67406 |
December | 497.00000 | 22.29362 | 19.67646 | -0.2475 | 7.70324 |
Annual Sum or Average | 5943.00000 | 23.74630 | 30.89098 | -0.1015 | 7.41342 |
Minimum of Months | 454.00000 | 22.29362 | 18.61127 | -0.4990 | 6.00439 |
Maximum of Months | 514.00000 | 24.61053 | 46.05845 | 0.27515 | 10.90502 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.35475 | 23.99055 | 0.07072 | 6.67744 |
February | 385.00000 | 23.10190 | 37.79480 | 0.08683 | 6.60949 |
March | 433.00000 | 23.65870 | 28.06210 | 0.18513 | 7.16397 |
April | 410.00000 | 24.47994 | 18.65885 | 0.40430 | 9.50114 |
May | 430.00000 | 24.60869 | 17.75543 | -0.3420 | 9.27181 |
June | 418.00000 | 24.68140 | 24.72967 | -0.1994 | 7.70874 |
July | 422.00000 | 24.80319 | 42.11939 | -0.0712 | 6.92567 |
August | 433.00000 | 24.61946 | 44.75268 | -0.1280 | 6.92151 |
September | 410.00000 | 24.65216 | 44.55904 | -0.1607 | 7.30712 |
October | 427.00000 | 24.23992 | 27.01384 | 0.36379 | 9.45359 |
November | 417.00000 | 23.61049 | 29.04100 | 0.17602 | 7.03811 |
December | 422.00000 | 22.87446 | 18.81887 | -0.0995 | 7.06883 |
Annual Sum or Average | 5034.00000 | 24.06235 | 29.71313 | 0.02275 | 7.64257 |
Minimum of Months | 385.00000 | 22.87446 | 17.75543 | -0.3420 | 6.60949 |
Maximum of Months | 433.00000 | 24.80319 | 44.75268 | 0.40430 | 9.50114 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.87521 | 21.74877 | 0.26895 | 8.81738 |
February | 454.00000 | 23.38330 | 35.70385 | 0.18302 | 7.47280 |
March | 514.00000 | 23.69455 | 27.62563 | 0.21317 | 7.43785 |
April | 485.00000 | 24.28801 | 19.23443 | 0.35051 | 8.42487 |
May | 508.00000 | 24.38420 | 18.51759 | -0.4788 | 10.80246 |
June | 496.00000 | 24.48893 | 25.56324 | -0.3484 | 8.61599 |
July | 497.00000 | 24.60501 | 43.17257 | -0.1943 | 7.09797 |
August | 514.00000 | 24.46921 | 45.81573 | -0.2049 | 6.93643 |
September | 485.00000 | 24.55436 | 44.92619 | -0.1708 | 7.16530 |
October | 502.00000 | 24.29679 | 26.66243 | 0.42801 | 10.57232 |
November | 489.00000 | 23.96532 | 27.23130 | 0.32245 | 8.97735 |
December | 497.00000 | 23.55990 | 16.29834 | 0.12518 | 8.38226 |
Annual Sum or Average | 5943.00000 | 24.13491 | 29.33505 | 0.03898 | 8.39991 |
Minimum of Months | 454.00000 | 23.38330 | 16.29834 | -0.4788 | 6.93643 |
Maximum of Months | 514.00000 | 24.60501 | 45.81573 | 0.42801 | 10.80246 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.28704 | 24.57894 | 0.06698 | 7.14911 |
February | 454.00000 | 22.93384 | 38.53275 | 0.05005 | 6.43518 |
March | 514.00000 | 23.51141 | 29.15175 | 0.15809 | 7.09895 |
April | 485.00000 | 24.29481 | 19.57631 | 0.36997 | 8.92876 |
May | 508.00000 | 24.44621 | 18.53696 | -0.3947 | 9.96771 |
June | 496.00000 | 24.56190 | 25.45379 | -0.2381 | 7.87900 |
July | 497.00000 | 24.65646 | 43.15903 | -0.1342 | 7.10584 |
August | 514.00000 | 24.49351 | 45.94918 | -0.1729 | 7.02437 |
September | 485.00000 | 24.54275 | 45.38546 | -0.1907 | 7.30693 |
October | 502.00000 | 24.09659 | 28.04379 | 0.33840 | 8.95814 |
November | 489.00000 | 23.55671 | 29.38642 | 0.17546 | 7.57064 |
December | 497.00000 | 22.73484 | 19.01909 | -0.1250 | 7.63136 |
Annual Sum or Average | 5943.00000 | 23.93293 | 30.51206 | -0.0094 | 7.76361 |
Minimum of Months | 454.00000 | 22.73484 | 18.53696 | -0.3947 | 6.43518 |
Maximum of Months | 514.00000 | 24.65646 | 45.94918 | 0.36997 | 9.96771 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.180499E+11 | 0.451646E+10 | 281.00 | 0.179203E+11 | 0.129574E+09 | 0.00 | 1.00 | 05-JAN-16:10 | 0.00 | 01-JAN-00:10 | 49445.81 | 31-JAN-16:40 | 49445.81 | 31-JAN-16:40 | 4420.85 | 08-JAN-15:45 | 12881.29 | 31-JAN-16:40 | 0.00 |
February | 0.408738E+10 | 0.110786E+10 | 158.41 | 0.363302E+10 | 0.454359E+09 | 0.00 | 0.74 | 09-FEB-15:00 | 0.00 | 01-FEB-00:10 | 24865.52 | 09-FEB-15:00 | 24865.52 | 09-FEB-15:00 | 3994.21 | 17-FEB-12:00 | 6115.48 | 09-FEB-15:00 | 0.00 |
March | 0.185824E+11 | 0.473289E+10 | 310.54 | 0.182022E+11 | 0.380253E+09 | 0.00 | 1.00 | 10-MAR-15:00 | 0.00 | 01-MAR-00:10 | 47622.77 | 20-MAR-15:10 | 47622.77 | 20-MAR-15:10 | 2591.10 | 14-MAR-19:30 | 12318.54 | 16-MAR-15:50 | 0.00 |
April | 0.469467E+11 | 0.125740E+11 | 412.48 | 0.468342E+11 | 0.112548E+09 | 0.00 | 1.00 | 03-APR-09:05 | 0.00 | 01-APR-00:10 | 65623.87 | 14-APR-16:00 | 65623.87 | 14-APR-16:00 | 2558.66 | 16-APR-10:00 | 20370.55 | 14-APR-16:00 | 0.00 |
May | 0.620899E+11 | 0.173953E+11 | 457.99 | 0.620270E+11 | 62914445.22 | 0.00 | 1.00 | 01-MAY-09:30 | 0.00 | 01-MAY-00:10 | 69903.61 | 31-MAY-16:00 | 69903.61 | 31-MAY-16:00 | 2413.18 | 26-MAY-05:10 | 23077.79 | 31-MAY-16:00 | 0.00 |
June | 0.824406E+11 | 0.258822E+11 | 483.50 | 0.820696E+11 | 0.371000E+09 | 0.00 | 1.00 | 01-JUN-05:12 | 0.00 | 01-JUN-00:10 | 89242.24 | 28-JUN-06:03 | 89242.24 | 28-JUN-06:03 | 6285.50 | 17-JUN-17:00 | 30511.14 | 28-JUN-16:00 | 0.00 |
July | 0.846588E+11 | 0.250042E+11 | 502.54 | 0.783981E+11 | 0.626074E+10 | 0.00 | 1.00 | 01-JUL-08:70 | 0.00 | 01-JUL-00:10 | 119972.40 | 15-JUL-06:03 | 91671.01 | 17-JUL-06:03 | 71972.48 | 14-JUL-04:03 | 28958.64 | 19-JUL-13:00 | 0.00 |
August | 0.882573E+11 | 0.259115E+11 | 497.11 | 0.814008E+11 | 0.685653E+10 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 118204.74 | 01-AUG-04:03 | 91183.08 | 14-AUG-06:03 | 55708.75 | 01-AUG-04:03 | 28834.88 | 25-AUG-16:00 | 0.00 |
September | 0.768984E+11 | 0.214421E+11 | 456.41 | 0.699455E+11 | 0.695286E+10 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 118008.83 | 05-SEP-07:20 | 88238.49 | 18-SEP-06:03 | 67116.99 | 05-SEP-06:03 | 27220.69 | 08-SEP-04:02 | 0.00 |
October | 0.440706E+11 | 0.116913E+11 | 386.99 | 0.427463E+11 | 0.132429E+10 | 0.00 | 1.00 | 01-OCT-11:02 | 0.00 | 01-OCT-00:10 | 112904.89 | 03-OCT-06:03 | 85726.24 | 02-OCT-04:02 | 52827.31 | 03-OCT-06:03 | 25911.35 | 03-OCT-06:03 | 0.00 |
November | 0.201884E+11 | 0.500449E+10 | 284.45 | 0.190147E+11 | 0.117375E+10 | 0.00 | 1.00 | 01-NOV-10:00 | 0.00 | 01-NOV-00:10 | 55930.97 | 01-NOV-16:00 | 55930.97 | 01-NOV-16:00 | 31886.03 | 13-NOV-06:12 | 14311.22 | 01-NOV-15:10 | 0.00 |
December | 0.120642E+11 | 0.310394E+10 | 248.89 | 0.120182E+11 | 45986264.20 | 0.00 | 1.00 | 01-DEC-15:00 | 0.00 | 01-DEC-00:10 | 43904.64 | 22-DEC-16:30 | 43904.64 | 22-DEC-16:30 | 1349.01 | 03-DEC-14:06 | 10191.32 | 22-DEC-16:30 | 0.00 |
Annual Sum or Average | 0.558335E+12 | 0.158366E+12 | 4480.29 | 0.534210E+12 | 0.241248E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.408738E+10 | 0.110786E+10 | 158.41 | 0.363302E+10 | 45986264.20 | 0.00 | 0.74 | 0.00 | 24865.52 | 24865.52 | 1349.01 | 6115.48 | 0.00 | ||||||
Maximum of Months | 0.882573E+11 | 0.259115E+11 | 502.54 | 0.820696E+11 | 0.695286E+10 | 0.00 | 1.00 | 0.00 | 119972.40 | 91671.01 | 71972.48 | 30511.14 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.143787E+11 | 0.364329E+10 | 277.39 | 0.142174E+11 | 0.161323E+09 | 0.00 | 1.00 | 17-JAN-14:50 | 0.00 | 01-JAN-00:10 | 41953.36 | 31-JAN-16:30 | 41953.36 | 31-JAN-16:30 | 4671.87 | 08-JAN-15:55 | 10930.82 | 31-JAN-16:30 | 0.00 |
February | 0.324329E+10 | 0.887295E+09 | 152.58 | 0.279410E+10 | 0.449191E+09 | 0.00 | 0.71 | 22-FEB-16:00 | 0.00 | 01-FEB-00:10 | 21301.23 | 22-FEB-16:00 | 21301.23 | 22-FEB-16:00 | 3523.28 | 18-FEB-11:05 | 5282.77 | 22-FEB-16:00 | 0.00 |
March | 0.143067E+11 | 0.368548E+10 | 300.01 | 0.138597E+11 | 0.446936E+09 | 0.00 | 1.00 | 10-MAR-15:00 | 0.00 | 01-MAR-00:10 | 44551.60 | 16-MAR-15:30 | 44551.60 | 16-MAR-15:30 | 2578.13 | 18-MAR-09:05 | 11542.52 | 16-MAR-15:30 | 0.00 |
April | 0.418499E+11 | 0.112469E+11 | 414.48 | 0.417554E+11 | 94510834.39 | 0.00 | 1.00 | 01-APR-14:05 | 0.00 | 01-APR-00:10 | 62194.92 | 24-APR-15:50 | 62194.92 | 24-APR-15:50 | 2203.36 | 16-APR-09:48 | 19230.24 | 14-APR-15:20 | 0.00 |
May | 0.559343E+11 | 0.156955E+11 | 465.13 | 0.558813E+11 | 52942143.75 | 0.00 | 1.00 | 01-MAY-09:40 | 0.00 | 01-MAY-00:10 | 63311.19 | 08-MAY-16:00 | 63311.19 | 08-MAY-16:00 | 2084.68 | 26-MAY-05:10 | 20430.67 | 31-MAY-16:00 | 0.00 |
June | 0.754288E+11 | 0.237203E+11 | 487.85 | 0.751948E+11 | 0.234016E+09 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 77417.09 | 29-JUN-06:03 | 77417.09 | 29-JUN-06:03 | 4770.40 | 17-JUN-17:00 | 29070.70 | 28-JUN-15:00 | 0.00 |
July | 0.734845E+11 | 0.216911E+11 | 495.31 | 0.687342E+11 | 0.475025E+10 | 0.00 | 1.00 | 01-JUL-08:00 | 0.00 | 01-JUL-00:10 | 109693.82 | 14-JUL-05:03 | 78724.19 | 10-JUL-04:02 | 65517.14 | 14-JUL-05:03 | 28408.26 | 19-JUL-12:01 | 0.00 |
August | 0.743233E+11 | 0.218455E+11 | 489.47 | 0.693409E+11 | 0.498245E+10 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 106476.07 | 01-AUG-04:03 | 81363.02 | 28-AUG-06:03 | 51578.45 | 01-AUG-04:03 | 27829.27 | 28-AUG-12:01 | 0.00 |
September | 0.623473E+11 | 0.174645E+11 | 438.85 | 0.572322E+11 | 0.511507E+10 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 106416.18 | 02-SEP-05:03 | 71529.36 | 18-SEP-04:02 | 60580.17 | 05-SEP-06:03 | 24832.34 | 02-SEP-05:03 | 0.00 |
October | 0.347751E+11 | 0.933727E+10 | 377.81 | 0.336689E+11 | 0.110621E+10 | 0.00 | 1.00 | 01-OCT-11:13 | 0.00 | 01-OCT-00:10 | 91999.67 | 03-OCT-06:03 | 75504.20 | 02-OCT-04:02 | 44153.57 | 03-OCT-06:03 | 21945.80 | 02-OCT-14:05 | 0.00 |
November | 0.150896E+11 | 0.380852E+10 | 279.86 | 0.141209E+11 | 0.968627E+09 | 0.00 | 1.00 | 01-NOV-10:30 | 0.00 | 01-NOV-00:10 | 48403.68 | 01-NOV-15:30 | 48403.68 | 01-NOV-15:30 | 19183.79 | 13-NOV-15:05 | 12472.30 | 01-NOV-15:00 | 0.00 |
December | 0.643046E+10 | 0.168223E+10 | 190.50 | 0.636815E+10 | 62303710.10 | 0.00 | 1.00 | 22-DEC-15:00 | 0.00 | 01-DEC-00:10 | 35382.40 | 22-DEC-16:30 | 35382.40 | 22-DEC-16:30 | 1864.81 | 12-DEC-13:00 | 8466.68 | 22-DEC-15:05 | 0.00 |
Annual Sum or Average | 0.471592E+12 | 0.134708E+12 | 4369.25 | 0.453168E+12 | 0.184238E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.324329E+10 | 0.887295E+09 | 152.58 | 0.279410E+10 | 52942143.75 | 0.00 | 0.71 | 0.00 | 21301.23 | 21301.23 | 1864.81 | 5282.77 | 0.00 | ||||||
Maximum of Months | 0.754288E+11 | 0.237203E+11 | 495.31 | 0.751948E+11 | 0.511507E+10 | 0.00 | 1.00 | 0.00 | 109693.82 | 81363.02 | 65517.14 | 29070.70 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.137737E+11 | 0.355328E+10 | 279.25 | 0.135300E+11 | 0.243667E+09 | 0.00 | 1.00 | 18-JAN-15:50 | 0.00 | 01-JAN-00:10 | 45795.43 | 31-JAN-16:20 | 45795.43 | 31-JAN-16:20 | 2226.23 | 07-JAN-17:10 | 11933.01 | 31-JAN-16:20 | 0.00 |
February | 0.316219E+10 | 0.874599E+09 | 160.42 | 0.261889E+10 | 0.543301E+09 | 0.00 | 0.63 | 22-FEB-16:00 | 0.00 | 01-FEB-00:10 | 21247.11 | 22-FEB-16:00 | 21247.11 | 22-FEB-16:00 | 4106.25 | 18-FEB-14:00 | 5381.76 | 22-FEB-16:00 | 0.00 |
March | 0.148003E+11 | 0.385143E+10 | 301.68 | 0.141406E+11 | 0.659609E+09 | 0.00 | 1.00 | 10-MAR-15:00 | 0.00 | 01-MAR-00:10 | 50907.95 | 16-MAR-15:30 | 50907.95 | 16-MAR-15:30 | 3481.89 | 18-MAR-10:00 | 13189.38 | 16-MAR-15:30 | 0.00 |
April | 0.460034E+11 | 0.124828E+11 | 417.77 | 0.458294E+11 | 0.173988E+09 | 0.00 | 1.00 | 01-APR-14:30 | 0.00 | 01-APR-00:10 | 72729.98 | 14-APR-15:30 | 72729.98 | 14-APR-15:30 | 3002.57 | 15-APR-20:20 | 22571.16 | 14-APR-15:30 | 0.00 |
May | 0.617499E+11 | 0.175042E+11 | 465.87 | 0.616480E+11 | 0.101946E+09 | 0.00 | 1.00 | 01-MAY-10:05 | 0.00 | 01-MAY-00:10 | 73870.94 | 15-MAY-15:20 | 73870.94 | 15-MAY-15:20 | 2726.49 | 29-MAY-22:25 | 23776.52 | 31-MAY-16:00 | 0.00 |
June | 0.847300E+11 | 0.268792E+11 | 496.85 | 0.843331E+11 | 0.396979E+09 | 0.00 | 1.00 | 01-JUN-07:40 | 0.00 | 01-JUN-00:10 | 88707.47 | 28-JUN-15:00 | 88707.47 | 28-JUN-15:00 | 6553.63 | 17-JUN-16:25 | 34246.60 | 28-JUN-15:00 | 0.00 |
July | 0.816061E+11 | 0.242523E+11 | 504.49 | 0.765358E+11 | 0.507028E+10 | 0.00 | 1.00 | 01-JUL-09:05 | 0.00 | 01-JUL-00:10 | 125530.81 | 14-JUL-05:03 | 88855.87 | 12-JUL-04:02 | 75459.72 | 14-JUL-05:03 | 30046.72 | 19-JUL-13:40 | 0.00 |
August | 0.813117E+11 | 0.240915E+11 | 492.76 | 0.761484E+11 | 0.516334E+10 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 121848.50 | 01-AUG-04:03 | 85455.85 | 14-AUG-15:20 | 61608.42 | 01-AUG-04:03 | 31481.09 | 25-AUG-15:20 | 0.00 |
September | 0.666647E+11 | 0.188399E+11 | 441.21 | 0.614403E+11 | 0.522446E+10 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:10 | 117950.64 | 05-SEP-06:03 | 81325.47 | 08-SEP-16:00 | 69321.43 | 05-SEP-06:03 | 27310.35 | 08-SEP-16:00 | 0.00 |
October | 0.358867E+11 | 0.976397E+10 | 380.77 | 0.346075E+11 | 0.127918E+10 | 0.00 | 1.00 | 01-OCT-11:23 | 0.00 | 01-OCT-00:10 | 87432.34 | 02-OCT-04:02 | 86495.57 | 02-OCT-04:02 | 32184.82 | 03-OCT-06:03 | 24179.30 | 02-OCT-13:50 | 0.00 |
November | 0.144766E+11 | 0.371968E+10 | 283.44 | 0.134730E+11 | 0.100354E+10 | 0.00 | 1.00 | 01-NOV-12:00 | 0.00 | 01-NOV-00:10 | 54388.91 | 01-NOV-15:30 | 54388.91 | 01-NOV-15:30 | 15639.58 | 13-NOV-15:40 | 14020.33 | 01-NOV-15:00 | 0.00 |
December | 0.592891E+10 | 0.157946E+10 | 190.93 | 0.582152E+10 | 0.107387E+09 | 0.00 | 1.00 | 22-DEC-15:30 | 0.00 | 01-DEC-00:10 | 37452.23 | 22-DEC-15:50 | 37452.23 | 22-DEC-15:50 | 2145.04 | 12-DEC-15:00 | 8855.14 | 25-DEC-15:52 | 0.00 |
Annual Sum or Average | 0.510094E+12 | 0.147392E+12 | 4415.46 | 0.490126E+12 | 0.199677E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.316219E+10 | 0.874599E+09 | 160.42 | 0.261889E+10 | 0.101946E+09 | 0.00 | 0.63 | 0.00 | 21247.11 | 21247.11 | 2145.04 | 5381.76 | 0.00 | ||||||
Maximum of Months | 0.847300E+11 | 0.268792E+11 | 504.49 | 0.843331E+11 | 0.522446E+10 | 0.00 | 1.00 | 0.00 | 125530.81 | 88855.87 | 75459.72 | 34246.60 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 282.60 | 0.00 | 282.60 | 242.20 | 1070.98 | 0.00 | 0.00 | 0.00 |
February | 322.02 | 0.00 | 322.02 | 173.38 | 1044.56 | 0.00 | 0.00 | 0.00 |
March | 427.96 | 0.00 | 427.96 | 417.30 | 945.28 | 0.00 | 0.00 | 0.00 |
April | 521.41 | 5.41 | 516.00 | 862.08 | 527.58 | 0.00 | 0.00 | 0.00 |
May | 610.37 | 48.87 | 561.49 | 1179.10 | 359.67 | 0.00 | 0.00 | 0.00 |
June | 709.29 | 128.87 | 580.42 | 1817.96 | 156.33 | 0.00 | 0.00 | 0.00 |
July | 604.89 | 63.02 | 541.87 | 1546.92 | 119.32 | 0.00 | 0.00 | 0.00 |
August | 488.25 | 12.13 | 476.12 | 1281.49 | 148.38 | 0.00 | 0.00 | 0.00 |
September | 460.66 | 0.12 | 460.54 | 1071.14 | 223.52 | 0.00 | 0.00 | 0.00 |
October | 356.40 | 0.00 | 356.40 | 528.54 | 685.59 | 0.00 | 0.00 | 0.00 |
November | 296.95 | 0.00 | 296.95 | 242.11 | 987.83 | 0.00 | 0.00 | 0.00 |
December | 263.98 | 0.00 | 263.98 | 156.79 | 1289.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 445.85 | 21.58 | 424.27 | 796.10 | 628.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 263.98 | 0.00 | 263.98 | 156.79 | 119.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 709.29 | 128.87 | 580.42 | 1817.96 | 1289.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 608.64 | 381.81 | 226.82 | 799.32 | 671.95 | 0.00 | 0.00 | 0.00 |
February | 599.93 | 343.19 | 256.74 | 697.15 | 665.03 | 0.00 | 0.00 | 0.00 |
March | 750.78 | 386.21 | 364.58 | 993.27 | 596.99 | 0.00 | 0.00 | 0.00 |
April | 1071.70 | 638.75 | 432.95 | 1768.29 | 338.38 | 0.00 | 0.00 | 0.00 |
May | 1110.67 | 658.40 | 452.28 | 1954.04 | 240.24 | 0.00 | 0.00 | 0.00 |
June | 1157.68 | 719.37 | 438.31 | 2331.67 | 101.35 | 0.00 | 0.00 | 0.00 |
July | 977.73 | 551.30 | 426.43 | 1987.38 | 77.44 | 0.00 | 0.00 | 0.00 |
August | 927.95 | 529.58 | 398.37 | 1875.62 | 96.22 | 0.00 | 0.00 | 0.00 |
September | 761.45 | 367.03 | 394.42 | 1481.66 | 141.60 | 0.00 | 0.00 | 0.00 |
October | 764.83 | 465.47 | 299.36 | 1204.40 | 431.23 | 0.00 | 0.00 | 0.00 |
November | 588.11 | 353.05 | 235.06 | 764.07 | 625.94 | 0.00 | 0.00 | 0.00 |
December | 536.21 | 323.78 | 212.43 | 629.85 | 805.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 822.32 | 477.12 | 345.20 | 1377.13 | 398.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 536.21 | 323.78 | 212.43 | 629.85 | 77.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1157.68 | 719.37 | 452.28 | 2331.67 | 805.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2326.98 | 1858.50 | 468.49 | 3560.19 | 1062.69 | 0.00 | 0.00 | 0.00 |
February | 1471.32 | 992.31 | 479.01 | 2029.86 | 1015.80 | 0.00 | 0.00 | 0.00 |
March | 1224.25 | 630.55 | 593.70 | 1812.80 | 946.95 | 0.00 | 0.00 | 0.00 |
April | 1042.15 | 421.13 | 621.02 | 1961.03 | 553.92 | 0.00 | 0.00 | 0.00 |
May | 698.35 | 115.38 | 582.98 | 1445.50 | 390.79 | 0.00 | 0.00 | 0.00 |
June | 597.99 | 46.10 | 551.89 | 1634.78 | 162.23 | 0.00 | 0.00 | 0.00 |
July | 611.04 | 63.22 | 547.83 | 1593.98 | 120.59 | 0.00 | 0.00 | 0.00 |
August | 743.00 | 205.33 | 537.67 | 1850.24 | 149.21 | 0.00 | 0.00 | 0.00 |
September | 1070.59 | 456.74 | 613.85 | 2243.21 | 225.71 | 0.00 | 0.00 | 0.00 |
October | 1705.87 | 1180.72 | 525.15 | 2859.24 | 676.96 | 0.00 | 0.00 | 0.00 |
November | 1987.99 | 1522.70 | 465.29 | 3003.34 | 973.28 | 0.00 | 0.00 | 0.00 |
December | 2163.40 | 1712.62 | 450.78 | 3168.01 | 1253.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1303.61 | 766.96 | 536.65 | 2266.02 | 626.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 597.99 | 46.10 | 450.78 | 1445.50 | 120.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2326.98 | 1858.50 | 621.02 | 3560.19 | 1253.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 636.44 | 395.56 | 240.88 | 931.13 | 735.83 | 0.00 | 0.00 | 0.00 |
February | 515.58 | 249.25 | 266.33 | 611.28 | 699.20 | 0.00 | 0.00 | 0.00 |
March | 682.90 | 325.55 | 357.35 | 930.57 | 632.94 | 0.00 | 0.00 | 0.00 |
April | 1048.61 | 598.16 | 450.45 | 1777.72 | 379.35 | 0.00 | 0.00 | 0.00 |
May | 1051.31 | 589.47 | 461.84 | 1897.08 | 275.70 | 0.00 | 0.00 | 0.00 |
June | 1117.64 | 657.35 | 460.29 | 2284.16 | 122.20 | 0.00 | 0.00 | 0.00 |
July | 813.45 | 379.71 | 433.73 | 1716.50 | 89.60 | 0.00 | 0.00 | 0.00 |
August | 775.69 | 389.57 | 386.12 | 1630.21 | 108.73 | 0.00 | 0.00 | 0.00 |
September | 676.14 | 284.09 | 392.06 | 1352.42 | 156.42 | 0.00 | 0.00 | 0.00 |
October | 691.84 | 395.59 | 296.25 | 1128.46 | 468.68 | 0.00 | 0.00 | 0.00 |
November | 637.20 | 384.72 | 252.48 | 906.23 | 674.96 | 0.00 | 0.00 | 0.00 |
December | 513.56 | 292.40 | 221.15 | 677.72 | 870.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 764.23 | 412.36 | 351.87 | 1323.27 | 433.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 513.56 | 249.25 | 221.15 | 611.28 | 89.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1117.64 | 657.35 | 461.84 | 2284.16 | 870.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.20 | 0.00 | 94.20 | 77.82 | 380.91 | 0.00 | 0.00 | 0.00 |
February | 107.34 | 0.00 | 107.34 | 58.86 | 365.88 | 0.00 | 0.00 | 0.00 |
March | 142.65 | 0.00 | 142.65 | 144.74 | 318.61 | 0.00 | 0.00 | 0.00 |
April | 173.80 | 1.80 | 171.99 | 295.33 | 174.52 | 0.00 | 0.00 | 0.00 |
May | 203.45 | 16.29 | 187.16 | 402.03 | 115.88 | 0.00 | 0.00 | 0.00 |
June | 236.42 | 42.95 | 193.46 | 614.16 | 48.90 | 0.00 | 0.00 | 0.00 |
July | 201.62 | 21.00 | 180.61 | 520.16 | 39.25 | 0.00 | 0.00 | 0.00 |
August | 162.74 | 4.04 | 158.70 | 428.02 | 51.67 | 0.00 | 0.00 | 0.00 |
September | 153.55 | 0.04 | 153.50 | 354.83 | 81.03 | 0.00 | 0.00 | 0.00 |
October | 118.79 | 0.00 | 118.79 | 170.94 | 253.87 | 0.00 | 0.00 | 0.00 |
November | 98.98 | 0.00 | 98.98 | 72.96 | 370.93 | 0.00 | 0.00 | 0.00 |
December | 87.99 | 0.00 | 87.99 | 43.48 | 478.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 148.61 | 7.19 | 141.42 | 266.22 | 222.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.99 | 0.00 | 87.99 | 43.48 | 39.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 236.42 | 42.95 | 193.46 | 614.16 | 478.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.20 | 0.00 | 94.20 | 77.83 | 380.93 | 0.00 | 0.00 | 0.00 |
February | 107.34 | 0.00 | 107.34 | 58.86 | 365.90 | 0.00 | 0.00 | 0.00 |
March | 142.65 | 0.00 | 142.65 | 144.74 | 318.63 | 0.00 | 0.00 | 0.00 |
April | 173.80 | 1.80 | 172.00 | 295.35 | 174.53 | 0.00 | 0.00 | 0.00 |
May | 203.46 | 16.29 | 187.16 | 402.05 | 115.89 | 0.00 | 0.00 | 0.00 |
June | 236.43 | 42.96 | 193.47 | 614.19 | 48.90 | 0.00 | 0.00 | 0.00 |
July | 201.63 | 21.01 | 180.62 | 520.19 | 39.26 | 0.00 | 0.00 | 0.00 |
August | 162.75 | 4.04 | 158.71 | 428.05 | 51.67 | 0.00 | 0.00 | 0.00 |
September | 153.55 | 0.04 | 153.51 | 354.85 | 81.03 | 0.00 | 0.00 | 0.00 |
October | 118.80 | 0.00 | 118.80 | 170.95 | 253.88 | 0.00 | 0.00 | 0.00 |
November | 98.98 | 0.00 | 98.98 | 72.97 | 370.95 | 0.00 | 0.00 | 0.00 |
December | 87.99 | 0.00 | 87.99 | 43.48 | 478.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 148.61 | 7.19 | 141.42 | 266.23 | 222.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.99 | 0.00 | 87.99 | 43.48 | 39.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 236.43 | 42.96 | 193.47 | 614.19 | 478.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.20 | 0.00 | 94.20 | 77.83 | 380.93 | 0.00 | 0.00 | 0.00 |
February | 107.34 | 0.00 | 107.34 | 58.86 | 365.90 | 0.00 | 0.00 | 0.00 |
March | 142.65 | 0.00 | 142.65 | 144.74 | 318.63 | 0.00 | 0.00 | 0.00 |
April | 173.80 | 1.80 | 172.00 | 295.35 | 174.53 | 0.00 | 0.00 | 0.00 |
May | 203.46 | 16.29 | 187.16 | 402.05 | 115.89 | 0.00 | 0.00 | 0.00 |
June | 236.43 | 42.96 | 193.47 | 614.19 | 48.90 | 0.00 | 0.00 | 0.00 |
July | 201.63 | 21.01 | 180.62 | 520.19 | 39.26 | 0.00 | 0.00 | 0.00 |
August | 162.75 | 4.04 | 158.71 | 428.05 | 51.67 | 0.00 | 0.00 | 0.00 |
September | 153.55 | 0.04 | 153.51 | 354.85 | 81.03 | 0.00 | 0.00 | 0.00 |
October | 118.80 | 0.00 | 118.80 | 170.95 | 253.88 | 0.00 | 0.00 | 0.00 |
November | 98.98 | 0.00 | 98.98 | 72.97 | 370.95 | 0.00 | 0.00 | 0.00 |
December | 87.99 | 0.00 | 87.99 | 43.48 | 478.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 148.61 | 7.19 | 141.42 | 266.23 | 222.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.99 | 0.00 | 87.99 | 43.48 | 39.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 236.43 | 42.96 | 193.47 | 614.19 | 478.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 585.48 | 367.29 | 218.19 | 760.13 | 702.85 | 0.00 | 0.00 | 0.00 |
February | 577.10 | 330.13 | 246.97 | 671.84 | 686.20 | 0.00 | 0.00 | 0.00 |
March | 722.22 | 371.51 | 350.70 | 964.66 | 595.46 | 0.00 | 0.00 | 0.00 |
April | 1030.93 | 614.44 | 416.48 | 1717.05 | 335.93 | 0.00 | 0.00 | 0.00 |
May | 1068.41 | 633.34 | 435.07 | 1897.64 | 235.31 | 0.00 | 0.00 | 0.00 |
June | 1113.63 | 691.99 | 421.64 | 2259.75 | 98.41 | 0.00 | 0.00 | 0.00 |
July | 940.53 | 530.33 | 410.21 | 1920.64 | 79.38 | 0.00 | 0.00 | 0.00 |
August | 892.65 | 509.43 | 383.22 | 1808.00 | 104.50 | 0.00 | 0.00 | 0.00 |
September | 732.48 | 353.07 | 379.41 | 1423.44 | 155.04 | 0.00 | 0.00 | 0.00 |
October | 735.73 | 447.76 | 287.97 | 1150.57 | 467.16 | 0.00 | 0.00 | 0.00 |
November | 565.73 | 339.62 | 226.12 | 717.73 | 682.87 | 0.00 | 0.00 | 0.00 |
December | 515.80 | 311.46 | 204.35 | 580.24 | 873.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 791.03 | 458.96 | 332.07 | 1325.72 | 416.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 515.80 | 311.46 | 204.35 | 580.24 | 79.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1113.63 | 691.99 | 435.07 | 2259.75 | 873.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.15 | 14.52 | 8.63 | 30.05 | 27.79 | 0.00 | 0.00 | 0.00 |
February | 22.82 | 13.05 | 9.77 | 26.56 | 27.13 | 0.00 | 0.00 | 0.00 |
March | 28.56 | 14.69 | 13.87 | 38.14 | 23.54 | 0.00 | 0.00 | 0.00 |
April | 40.76 | 24.29 | 16.47 | 67.89 | 13.28 | 0.00 | 0.00 | 0.00 |
May | 42.24 | 25.04 | 17.20 | 75.03 | 9.30 | 0.00 | 0.00 | 0.00 |
June | 44.03 | 27.36 | 16.67 | 89.35 | 3.89 | 0.00 | 0.00 | 0.00 |
July | 37.19 | 20.97 | 16.22 | 75.94 | 3.14 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 20.14 | 15.15 | 71.49 | 4.13 | 0.00 | 0.00 | 0.00 |
September | 28.96 | 13.96 | 15.00 | 56.28 | 6.13 | 0.00 | 0.00 | 0.00 |
October | 29.09 | 17.70 | 11.39 | 45.49 | 18.47 | 0.00 | 0.00 | 0.00 |
November | 22.37 | 13.43 | 8.94 | 28.38 | 27.00 | 0.00 | 0.00 | 0.00 |
December | 20.39 | 12.31 | 8.08 | 22.94 | 34.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.28 | 18.15 | 13.13 | 52.42 | 16.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.39 | 12.31 | 8.08 | 22.94 | 3.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 44.03 | 27.36 | 17.20 | 89.35 | 34.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 775.65 | 619.49 | 156.16 | 1186.81 | 396.05 | 0.00 | 0.00 | 0.00 |
February | 490.43 | 330.76 | 159.67 | 684.18 | 362.84 | 0.00 | 0.00 | 0.00 |
March | 408.08 | 210.18 | 197.90 | 614.51 | 325.40 | 0.00 | 0.00 | 0.00 |
April | 347.38 | 140.37 | 207.01 | 662.02 | 188.15 | 0.00 | 0.00 | 0.00 |
May | 232.78 | 38.46 | 194.32 | 489.48 | 128.00 | 0.00 | 0.00 | 0.00 |
June | 199.33 | 15.37 | 183.96 | 548.05 | 51.82 | 0.00 | 0.00 | 0.00 |
July | 203.68 | 21.07 | 182.61 | 531.87 | 41.06 | 0.00 | 0.00 | 0.00 |
August | 247.66 | 68.44 | 179.22 | 612.75 | 55.48 | 0.00 | 0.00 | 0.00 |
September | 356.86 | 152.24 | 204.61 | 742.19 | 87.25 | 0.00 | 0.00 | 0.00 |
October | 568.61 | 393.57 | 175.05 | 949.87 | 256.92 | 0.00 | 0.00 | 0.00 |
November | 662.65 | 507.55 | 155.10 | 997.77 | 370.85 | 0.00 | 0.00 | 0.00 |
December | 721.12 | 570.86 | 150.26 | 1051.89 | 473.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 434.53 | 255.65 | 178.88 | 756.74 | 227.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.33 | 15.37 | 150.26 | 489.48 | 41.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 775.65 | 619.49 | 207.01 | 1186.81 | 473.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 775.65 | 619.49 | 156.16 | 1186.81 | 396.05 | 0.00 | 0.00 | 0.00 |
February | 490.43 | 330.76 | 159.67 | 684.18 | 362.84 | 0.00 | 0.00 | 0.00 |
March | 408.08 | 210.18 | 197.90 | 614.51 | 325.40 | 0.00 | 0.00 | 0.00 |
April | 347.38 | 140.37 | 207.01 | 662.02 | 188.15 | 0.00 | 0.00 | 0.00 |
May | 232.78 | 38.46 | 194.32 | 489.48 | 128.00 | 0.00 | 0.00 | 0.00 |
June | 199.33 | 15.37 | 183.96 | 548.05 | 51.82 | 0.00 | 0.00 | 0.00 |
July | 203.68 | 21.07 | 182.61 | 531.87 | 41.06 | 0.00 | 0.00 | 0.00 |
August | 247.66 | 68.44 | 179.22 | 612.75 | 55.48 | 0.00 | 0.00 | 0.00 |
September | 356.86 | 152.24 | 204.61 | 742.19 | 87.25 | 0.00 | 0.00 | 0.00 |
October | 568.61 | 393.57 | 175.05 | 949.87 | 256.92 | 0.00 | 0.00 | 0.00 |
November | 662.65 | 507.55 | 155.10 | 997.77 | 370.85 | 0.00 | 0.00 | 0.00 |
December | 721.12 | 570.86 | 150.26 | 1051.89 | 473.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 434.53 | 255.65 | 178.88 | 756.74 | 227.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.33 | 15.37 | 150.26 | 489.48 | 41.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 775.65 | 619.49 | 207.01 | 1186.81 | 473.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 775.60 | 619.45 | 156.15 | 1186.74 | 396.03 | 0.00 | 0.00 | 0.00 |
February | 490.40 | 330.74 | 159.66 | 684.13 | 362.81 | 0.00 | 0.00 | 0.00 |
March | 408.05 | 210.17 | 197.88 | 614.47 | 325.38 | 0.00 | 0.00 | 0.00 |
April | 347.36 | 140.37 | 206.99 | 661.98 | 188.14 | 0.00 | 0.00 | 0.00 |
May | 232.77 | 38.46 | 194.31 | 489.45 | 127.99 | 0.00 | 0.00 | 0.00 |
June | 199.32 | 15.36 | 183.95 | 548.02 | 51.82 | 0.00 | 0.00 | 0.00 |
July | 203.67 | 21.07 | 182.60 | 531.84 | 41.06 | 0.00 | 0.00 | 0.00 |
August | 247.65 | 68.44 | 179.21 | 612.71 | 55.47 | 0.00 | 0.00 | 0.00 |
September | 356.84 | 152.23 | 204.60 | 742.14 | 87.25 | 0.00 | 0.00 | 0.00 |
October | 568.58 | 393.54 | 175.04 | 949.81 | 256.90 | 0.00 | 0.00 | 0.00 |
November | 662.61 | 507.52 | 155.09 | 997.71 | 370.82 | 0.00 | 0.00 | 0.00 |
December | 721.08 | 570.83 | 150.25 | 1051.83 | 473.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 434.50 | 255.63 | 178.87 | 756.69 | 227.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.32 | 15.36 | 150.25 | 489.45 | 41.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 775.60 | 619.45 | 206.99 | 1186.74 | 473.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 612.22 | 380.51 | 231.72 | 891.97 | 775.55 | 0.00 | 0.00 | 0.00 |
February | 495.96 | 239.77 | 256.20 | 592.45 | 721.30 | 0.00 | 0.00 | 0.00 |
March | 656.92 | 313.16 | 343.76 | 907.40 | 633.66 | 0.00 | 0.00 | 0.00 |
April | 1008.72 | 575.40 | 433.32 | 1726.99 | 380.25 | 0.00 | 0.00 | 0.00 |
May | 1011.31 | 567.04 | 444.27 | 1842.67 | 272.75 | 0.00 | 0.00 | 0.00 |
June | 1075.12 | 632.34 | 442.78 | 2213.09 | 120.04 | 0.00 | 0.00 | 0.00 |
July | 782.50 | 365.27 | 417.23 | 1659.08 | 90.91 | 0.00 | 0.00 | 0.00 |
August | 746.18 | 374.75 | 371.44 | 1570.19 | 115.58 | 0.00 | 0.00 | 0.00 |
September | 650.42 | 273.28 | 377.14 | 1298.90 | 169.65 | 0.00 | 0.00 | 0.00 |
October | 665.51 | 380.54 | 284.98 | 1079.55 | 509.65 | 0.00 | 0.00 | 0.00 |
November | 612.95 | 370.08 | 242.87 | 860.99 | 741.85 | 0.00 | 0.00 | 0.00 |
December | 494.02 | 281.28 | 212.74 | 637.28 | 945.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 735.15 | 396.67 | 338.48 | 1276.22 | 455.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 494.02 | 239.77 | 212.74 | 592.45 | 90.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1075.12 | 632.34 | 444.27 | 2213.09 | 945.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.21 | 15.04 | 9.16 | 35.27 | 30.66 | 0.00 | 0.00 | 0.00 |
February | 19.61 | 9.48 | 10.13 | 23.43 | 28.52 | 0.00 | 0.00 | 0.00 |
March | 25.97 | 12.38 | 13.59 | 35.88 | 25.05 | 0.00 | 0.00 | 0.00 |
April | 39.88 | 22.75 | 17.13 | 68.28 | 15.03 | 0.00 | 0.00 | 0.00 |
May | 39.99 | 22.42 | 17.57 | 72.86 | 10.78 | 0.00 | 0.00 | 0.00 |
June | 42.51 | 25.00 | 17.51 | 87.50 | 4.75 | 0.00 | 0.00 | 0.00 |
July | 30.94 | 14.44 | 16.50 | 65.60 | 3.59 | 0.00 | 0.00 | 0.00 |
August | 29.50 | 14.82 | 14.69 | 62.08 | 4.57 | 0.00 | 0.00 | 0.00 |
September | 25.72 | 10.81 | 14.91 | 51.36 | 6.71 | 0.00 | 0.00 | 0.00 |
October | 26.31 | 15.05 | 11.27 | 42.68 | 20.15 | 0.00 | 0.00 | 0.00 |
November | 24.24 | 14.63 | 9.60 | 34.04 | 29.33 | 0.00 | 0.00 | 0.00 |
December | 19.53 | 11.12 | 8.41 | 25.20 | 37.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.07 | 15.68 | 13.38 | 50.46 | 18.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.53 | 9.48 | 8.41 | 23.43 | 3.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.51 | 25.00 | 17.57 | 87.50 | 37.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 282.60 | 0.00 | 282.60 | 224.65 | 1154.43 | 0.00 | 0.00 | 0.00 |
February | 322.02 | 0.00 | 322.02 | 160.09 | 1133.91 | 0.00 | 0.00 | 0.00 |
March | 427.96 | 0.00 | 427.96 | 404.12 | 1004.05 | 0.00 | 0.00 | 0.00 |
April | 521.41 | 5.41 | 516.00 | 865.32 | 549.30 | 0.00 | 0.00 | 0.00 |
May | 610.37 | 48.87 | 561.49 | 1183.68 | 369.23 | 0.00 | 0.00 | 0.00 |
June | 709.29 | 128.87 | 580.42 | 1829.56 | 157.99 | 0.00 | 0.00 | 0.00 |
July | 604.89 | 63.02 | 541.87 | 1560.32 | 119.55 | 0.00 | 0.00 | 0.00 |
August | 488.25 | 12.13 | 476.12 | 1291.07 | 151.72 | 0.00 | 0.00 | 0.00 |
September | 460.66 | 0.12 | 460.54 | 1077.05 | 230.96 | 0.00 | 0.00 | 0.00 |
October | 356.40 | 0.00 | 356.40 | 521.89 | 731.93 | 0.00 | 0.00 | 0.00 |
November | 296.95 | 0.00 | 296.95 | 226.17 | 1069.78 | 0.00 | 0.00 | 0.00 |
December | 263.98 | 0.00 | 263.98 | 136.42 | 1397.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 445.85 | 21.58 | 424.27 | 792.91 | 670.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 263.98 | 0.00 | 263.98 | 136.42 | 119.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 709.29 | 128.87 | 580.42 | 1829.56 | 1397.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 608.64 | 381.81 | 226.82 | 781.42 | 717.44 | 0.00 | 0.00 | 0.00 |
February | 599.93 | 343.19 | 256.74 | 683.59 | 716.57 | 0.00 | 0.00 | 0.00 |
March | 750.78 | 386.21 | 364.58 | 980.20 | 628.89 | 0.00 | 0.00 | 0.00 |
April | 1071.70 | 638.75 | 432.95 | 1767.84 | 349.52 | 0.00 | 0.00 | 0.00 |
May | 1110.67 | 658.40 | 452.28 | 1955.90 | 246.90 | 0.00 | 0.00 | 0.00 |
June | 1157.68 | 719.37 | 438.31 | 2337.69 | 102.93 | 0.00 | 0.00 | 0.00 |
July | 977.73 | 551.30 | 426.43 | 1994.10 | 77.98 | 0.00 | 0.00 | 0.00 |
August | 927.95 | 529.58 | 398.37 | 1879.86 | 99.04 | 0.00 | 0.00 | 0.00 |
September | 761.45 | 367.03 | 394.42 | 1483.20 | 146.38 | 0.00 | 0.00 | 0.00 |
October | 764.83 | 465.47 | 299.36 | 1196.85 | 456.15 | 0.00 | 0.00 | 0.00 |
November | 588.11 | 353.05 | 235.06 | 747.59 | 671.65 | 0.00 | 0.00 | 0.00 |
December | 536.21 | 323.78 | 212.43 | 605.95 | 867.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 822.32 | 477.12 | 345.20 | 1371.10 | 422.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 536.21 | 323.78 | 212.43 | 605.95 | 77.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1157.68 | 719.37 | 452.28 | 2337.69 | 867.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2326.98 | 1858.50 | 468.49 | 3544.47 | 1128.28 | 0.00 | 0.00 | 0.00 |
February | 1471.32 | 992.31 | 479.01 | 2014.71 | 1090.97 | 0.00 | 0.00 | 0.00 |
March | 1224.25 | 630.55 | 593.70 | 1802.22 | 999.47 | 0.00 | 0.00 | 0.00 |
April | 1042.15 | 421.13 | 621.02 | 1966.70 | 576.10 | 0.00 | 0.00 | 0.00 |
May | 698.35 | 115.38 | 582.98 | 1452.18 | 404.11 | 0.00 | 0.00 | 0.00 |
June | 597.99 | 46.10 | 551.89 | 1646.76 | 165.47 | 0.00 | 0.00 | 0.00 |
July | 611.04 | 63.22 | 547.83 | 1607.93 | 121.74 | 0.00 | 0.00 | 0.00 |
August | 743.00 | 205.33 | 537.67 | 1861.19 | 153.62 | 0.00 | 0.00 | 0.00 |
September | 1070.59 | 456.74 | 613.85 | 2251.68 | 233.32 | 0.00 | 0.00 | 0.00 |
October | 1705.87 | 1180.72 | 525.15 | 2855.46 | 715.34 | 0.00 | 0.00 | 0.00 |
November | 1987.99 | 1522.70 | 465.29 | 2987.86 | 1037.77 | 0.00 | 0.00 | 0.00 |
December | 2163.40 | 1712.62 | 450.78 | 3144.51 | 1339.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1303.61 | 766.96 | 536.65 | 2263.86 | 662.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 597.99 | 46.10 | 450.78 | 1452.18 | 121.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2326.98 | 1858.50 | 621.02 | 3544.47 | 1339.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 636.44 | 395.56 | 240.88 | 921.82 | 789.22 | 0.00 | 0.00 | 0.00 |
February | 515.58 | 249.25 | 266.33 | 603.45 | 756.27 | 0.00 | 0.00 | 0.00 |
March | 682.90 | 325.55 | 357.35 | 923.75 | 670.96 | 0.00 | 0.00 | 0.00 |
April | 1048.61 | 598.16 | 450.45 | 1782.01 | 394.31 | 0.00 | 0.00 | 0.00 |
May | 1051.31 | 589.47 | 461.84 | 1903.26 | 284.58 | 0.00 | 0.00 | 0.00 |
June | 1117.64 | 657.35 | 460.29 | 2294.28 | 124.28 | 0.00 | 0.00 | 0.00 |
July | 813.45 | 379.71 | 433.73 | 1726.22 | 90.23 | 0.00 | 0.00 | 0.00 |
August | 775.69 | 389.57 | 386.12 | 1637.74 | 111.37 | 0.00 | 0.00 | 0.00 |
September | 676.14 | 284.09 | 392.06 | 1357.62 | 161.32 | 0.00 | 0.00 | 0.00 |
October | 691.84 | 395.59 | 296.25 | 1126.12 | 498.33 | 0.00 | 0.00 | 0.00 |
November | 637.20 | 384.72 | 252.48 | 897.73 | 726.58 | 0.00 | 0.00 | 0.00 |
December | 513.56 | 292.40 | 221.15 | 665.28 | 939.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 764.23 | 412.36 | 351.87 | 1322.95 | 461.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 513.56 | 249.25 | 221.15 | 603.45 | 90.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1117.64 | 657.35 | 461.84 | 2294.28 | 939.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.756926E+09 | 0.00 | 0.756926E+09 | 0.648710E+09 | 0.286853E+10 |
February | 0.779031E+09 | 0.00 | 0.779031E+09 | 0.419437E+09 | 0.252701E+10 |
March | 0.114626E+10 | 0.00 | 0.114626E+10 | 0.111769E+10 | 0.253184E+10 |
April | 0.135150E+10 | 14025087.93 | 0.133747E+10 | 0.223450E+10 | 0.136748E+10 |
May | 0.163481E+10 | 0.130900E+09 | 0.150391E+10 | 0.315810E+10 | 0.963349E+09 |
June | 0.183847E+10 | 0.334031E+09 | 0.150444E+10 | 0.471215E+10 | 0.405201E+09 |
July | 0.162013E+10 | 0.168785E+09 | 0.145134E+10 | 0.414328E+10 | 0.319590E+09 |
August | 0.130774E+10 | 32487191.21 | 0.127525E+10 | 0.343234E+10 | 0.397427E+09 |
September | 0.119403E+10 | 318747.42 | 0.119371E+10 | 0.277640E+10 | 0.579368E+09 |
October | 0.954585E+09 | 0.00 | 0.954585E+09 | 0.141564E+10 | 0.183628E+10 |
November | 0.769689E+09 | 0.00 | 0.769689E+09 | 0.627537E+09 | 0.256044E+10 |
December | 0.707039E+09 | 0.00 | 0.707039E+09 | 0.419946E+09 | 0.345252E+10 |
Annual Sum or Average | 0.140602E+11 | 0.680547E+09 | 0.133796E+11 | 0.251057E+11 | 0.198090E+11 |
Minimum of Months | 0.707039E+09 | 0.00 | 0.707039E+09 | 0.419437E+09 | 0.319590E+09 |
Maximum of Months | 0.183847E+10 | 0.334031E+09 | 0.150444E+10 | 0.471215E+10 | 0.345252E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163017E+10 | 0.102265E+10 | 0.607520E+09 | 0.214089E+10 | 0.179974E+10 |
February | 0.145135E+10 | 0.830239E+09 | 0.621112E+09 | 0.168653E+10 | 0.160885E+10 |
March | 0.201090E+10 | 0.103442E+10 | 0.976479E+09 | 0.266037E+10 | 0.159897E+10 |
April | 0.277786E+10 | 0.165564E+10 | 0.112222E+10 | 0.458340E+10 | 0.877069E+09 |
May | 0.297482E+10 | 0.176345E+10 | 0.121137E+10 | 0.523371E+10 | 0.643456E+09 |
June | 0.300071E+10 | 0.186460E+10 | 0.113611E+10 | 0.604369E+10 | 0.262687E+09 |
July | 0.261876E+10 | 0.147661E+10 | 0.114215E+10 | 0.532299E+10 | 0.207422E+09 |
August | 0.248543E+10 | 0.141844E+10 | 0.106700E+10 | 0.502366E+10 | 0.257720E+09 |
September | 0.197368E+10 | 0.951348E+09 | 0.102233E+10 | 0.384045E+10 | 0.367029E+09 |
October | 0.204853E+10 | 0.124672E+10 | 0.801807E+09 | 0.322586E+10 | 0.115500E+10 |
November | 0.152439E+10 | 0.915110E+09 | 0.609278E+09 | 0.198048E+10 | 0.162245E+10 |
December | 0.143617E+10 | 0.867202E+09 | 0.568969E+09 | 0.168699E+10 | 0.215645E+10 |
Annual Sum or Average | 0.259328E+11 | 0.150464E+11 | 0.108863E+11 | 0.434290E+11 | 0.125568E+11 |
Minimum of Months | 0.143617E+10 | 0.830239E+09 | 0.568969E+09 | 0.168653E+10 | 0.207422E+09 |
Maximum of Months | 0.300071E+10 | 0.186460E+10 | 0.121137E+10 | 0.604369E+10 | 0.215645E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.623260E+10 | 0.497780E+10 | 0.125480E+10 | 0.953562E+10 | 0.284632E+10 |
February | 0.355942E+10 | 0.240059E+10 | 0.115882E+10 | 0.491063E+10 | 0.245742E+10 |
March | 0.327902E+10 | 0.168887E+10 | 0.159015E+10 | 0.485540E+10 | 0.253632E+10 |
April | 0.270126E+10 | 0.109157E+10 | 0.160969E+10 | 0.508300E+10 | 0.143577E+10 |
May | 0.187047E+10 | 0.309023E+09 | 0.156144E+10 | 0.387163E+10 | 0.104669E+10 |
June | 0.154999E+10 | 0.119485E+09 | 0.143051E+10 | 0.423735E+10 | 0.420509E+09 |
July | 0.163662E+10 | 0.169322E+09 | 0.146730E+10 | 0.426932E+10 | 0.322986E+09 |
August | 0.199005E+10 | 0.549951E+09 | 0.144010E+10 | 0.495569E+10 | 0.399640E+09 |
September | 0.277497E+10 | 0.118387E+10 | 0.159110E+10 | 0.581440E+10 | 0.585044E+09 |
October | 0.456901E+10 | 0.316244E+10 | 0.140657E+10 | 0.765820E+10 | 0.181318E+10 |
November | 0.515286E+10 | 0.394683E+10 | 0.120603E+10 | 0.778465E+10 | 0.252274E+10 |
December | 0.579446E+10 | 0.458709E+10 | 0.120737E+10 | 0.848520E+10 | 0.335777E+10 |
Annual Sum or Average | 0.411107E+11 | 0.241868E+11 | 0.169239E+11 | 0.714611E+11 | 0.197444E+11 |
Minimum of Months | 0.154999E+10 | 0.119485E+09 | 0.115882E+10 | 0.387163E+10 | 0.322986E+09 |
Maximum of Months | 0.623260E+10 | 0.497780E+10 | 0.160969E+10 | 0.953562E+10 | 0.335777E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170464E+10 | 0.105946E+10 | 0.645179E+09 | 0.249393E+10 | 0.197084E+10 |
February | 0.124729E+10 | 0.602987E+09 | 0.644300E+09 | 0.147881E+10 | 0.169151E+10 |
March | 0.182908E+10 | 0.871951E+09 | 0.957127E+09 | 0.249243E+10 | 0.169527E+10 |
April | 0.271801E+10 | 0.155043E+10 | 0.116757E+10 | 0.460784E+10 | 0.983280E+09 |
May | 0.281582E+10 | 0.157883E+10 | 0.123698E+10 | 0.508114E+10 | 0.738440E+09 |
June | 0.289693E+10 | 0.170386E+10 | 0.119307E+10 | 0.592054E+10 | 0.316737E+09 |
July | 0.217873E+10 | 0.101702E+10 | 0.116171E+10 | 0.459747E+10 | 0.239973E+09 |
August | 0.207762E+10 | 0.104342E+10 | 0.103420E+10 | 0.436635E+10 | 0.291227E+09 |
September | 0.175257E+10 | 0.736358E+09 | 0.101621E+10 | 0.350548E+10 | 0.405443E+09 |
October | 0.185302E+10 | 0.105955E+10 | 0.793465E+09 | 0.302246E+10 | 0.125531E+10 |
November | 0.165162E+10 | 0.997200E+09 | 0.654420E+09 | 0.234896E+10 | 0.174950E+10 |
December | 0.137551E+10 | 0.783172E+09 | 0.592336E+09 | 0.181520E+10 | 0.233145E+10 |
Annual Sum or Average | 0.241008E+11 | 0.130043E+11 | 0.110966E+11 | 0.417306E+11 | 0.136690E+11 |
Minimum of Months | 0.124729E+10 | 0.602987E+09 | 0.592336E+09 | 0.147881E+10 | 0.239973E+09 |
Maximum of Months | 0.289693E+10 | 0.170386E+10 | 0.123698E+10 | 0.592054E+10 | 0.233145E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.252297E+09 | 0.00 | 0.252297E+09 | 0.208445E+09 | 0.102023E+10 |
February | 0.259665E+09 | 0.00 | 0.259665E+09 | 0.142391E+09 | 0.885129E+09 |
March | 0.382069E+09 | 0.00 | 0.382069E+09 | 0.387665E+09 | 0.853378E+09 |
April | 0.450478E+09 | 4674808.12 | 0.445804E+09 | 0.765504E+09 | 0.452351E+09 |
May | 0.544910E+09 | 43631393.23 | 0.501279E+09 | 0.107680E+10 | 0.310376E+09 |
June | 0.612794E+09 | 0.111338E+09 | 0.501455E+09 | 0.159190E+10 | 0.126745E+09 |
July | 0.540017E+09 | 56259066.12 | 0.483758E+09 | 0.139320E+10 | 0.105139E+09 |
August | 0.435891E+09 | 10828551.39 | 0.425063E+09 | 0.114642E+10 | 0.138396E+09 |
September | 0.397990E+09 | 106244.11 | 0.397884E+09 | 0.919715E+09 | 0.210027E+09 |
October | 0.318180E+09 | 0.00 | 0.318180E+09 | 0.457854E+09 | 0.679958E+09 |
November | 0.256551E+09 | 0.00 | 0.256551E+09 | 0.189121E+09 | 0.961450E+09 |
December | 0.235669E+09 | 0.00 | 0.235669E+09 | 0.116444E+09 | 0.128202E+10 |
Annual Sum or Average | 0.468651E+10 | 0.226838E+09 | 0.445967E+10 | 0.839546E+10 | 0.702520E+10 |
Minimum of Months | 0.235669E+09 | 0.00 | 0.235669E+09 | 0.116444E+09 | 0.105139E+09 |
Maximum of Months | 0.612794E+09 | 0.111338E+09 | 0.501455E+09 | 0.159190E+10 | 0.128202E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.252308E+09 | 0.00 | 0.252308E+09 | 0.208455E+09 | 0.102029E+10 |
February | 0.259676E+09 | 0.00 | 0.259676E+09 | 0.142395E+09 | 0.885183E+09 |
March | 0.382085E+09 | 0.00 | 0.382085E+09 | 0.387680E+09 | 0.853427E+09 |
April | 0.450499E+09 | 4674933.78 | 0.445824E+09 | 0.765546E+09 | 0.452374E+09 |
May | 0.544934E+09 | 43632566.05 | 0.501302E+09 | 0.107685E+10 | 0.310390E+09 |
June | 0.612820E+09 | 0.111341E+09 | 0.501478E+09 | 0.159199E+10 | 0.126750E+09 |
July | 0.540039E+09 | 56260578.38 | 0.483779E+09 | 0.139327E+10 | 0.105143E+09 |
August | 0.435910E+09 | 10828842.47 | 0.425081E+09 | 0.114649E+10 | 0.138402E+09 |
September | 0.398007E+09 | 106246.97 | 0.397901E+09 | 0.919763E+09 | 0.210037E+09 |
October | 0.318194E+09 | 0.00 | 0.318194E+09 | 0.457878E+09 | 0.679994E+09 |
November | 0.256562E+09 | 0.00 | 0.256562E+09 | 0.189129E+09 | 0.961505E+09 |
December | 0.235679E+09 | 0.00 | 0.235679E+09 | 0.116448E+09 | 0.128210E+10 |
Annual Sum or Average | 0.468671E+10 | 0.226845E+09 | 0.445987E+10 | 0.839589E+10 | 0.702559E+10 |
Minimum of Months | 0.235679E+09 | 0.00 | 0.235679E+09 | 0.116448E+09 | 0.105143E+09 |
Maximum of Months | 0.612820E+09 | 0.111341E+09 | 0.501478E+09 | 0.159199E+10 | 0.128210E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.252308E+09 | 0.00 | 0.252308E+09 | 0.208455E+09 | 0.102029E+10 |
February | 0.259676E+09 | 0.00 | 0.259676E+09 | 0.142395E+09 | 0.885183E+09 |
March | 0.382085E+09 | 0.00 | 0.382085E+09 | 0.387680E+09 | 0.853427E+09 |
April | 0.450499E+09 | 4674933.78 | 0.445824E+09 | 0.765546E+09 | 0.452374E+09 |
May | 0.544934E+09 | 43632566.05 | 0.501302E+09 | 0.107685E+10 | 0.310390E+09 |
June | 0.612820E+09 | 0.111341E+09 | 0.501478E+09 | 0.159199E+10 | 0.126750E+09 |
July | 0.540039E+09 | 56260578.38 | 0.483779E+09 | 0.139327E+10 | 0.105143E+09 |
August | 0.435910E+09 | 10828842.47 | 0.425081E+09 | 0.114649E+10 | 0.138402E+09 |
September | 0.398007E+09 | 106246.97 | 0.397901E+09 | 0.919763E+09 | 0.210037E+09 |
October | 0.318194E+09 | 0.00 | 0.318194E+09 | 0.457878E+09 | 0.679994E+09 |
November | 0.256562E+09 | 0.00 | 0.256562E+09 | 0.189129E+09 | 0.961505E+09 |
December | 0.235679E+09 | 0.00 | 0.235679E+09 | 0.116448E+09 | 0.128210E+10 |
Annual Sum or Average | 0.468671E+10 | 0.226845E+09 | 0.445987E+10 | 0.839589E+10 | 0.702559E+10 |
Minimum of Months | 0.235679E+09 | 0.00 | 0.235679E+09 | 0.116448E+09 | 0.105143E+09 |
Maximum of Months | 0.612820E+09 | 0.111341E+09 | 0.501478E+09 | 0.159199E+10 | 0.128210E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.156814E+10 | 0.983737E+09 | 0.584407E+09 | 0.203592E+10 | 0.188252E+10 |
February | 0.139613E+10 | 0.798645E+09 | 0.597481E+09 | 0.162531E+10 | 0.166006E+10 |
March | 0.193439E+10 | 0.995059E+09 | 0.939327E+09 | 0.258375E+10 | 0.159488E+10 |
April | 0.267216E+10 | 0.159264E+10 | 0.107952E+10 | 0.445060E+10 | 0.870736E+09 |
May | 0.286163E+10 | 0.169634E+10 | 0.116529E+10 | 0.508263E+10 | 0.630261E+09 |
June | 0.288653E+10 | 0.179364E+10 | 0.109289E+10 | 0.585726E+10 | 0.255086E+09 |
July | 0.251912E+10 | 0.142042E+10 | 0.109870E+10 | 0.514424E+10 | 0.212624E+09 |
August | 0.239086E+10 | 0.136446E+10 | 0.102640E+10 | 0.484254E+10 | 0.279899E+09 |
September | 0.189858E+10 | 0.915146E+09 | 0.983434E+09 | 0.368956E+10 | 0.401859E+09 |
October | 0.197058E+10 | 0.119928E+10 | 0.771302E+09 | 0.308169E+10 | 0.125124E+10 |
November | 0.146638E+10 | 0.880287E+09 | 0.586098E+09 | 0.186035E+10 | 0.176999E+10 |
December | 0.138152E+10 | 0.834202E+09 | 0.547323E+09 | 0.155411E+10 | 0.233893E+10 |
Annual Sum or Average | 0.249460E+11 | 0.144739E+11 | 0.104722E+11 | 0.418080E+11 | 0.131481E+11 |
Minimum of Months | 0.138152E+10 | 0.798645E+09 | 0.547323E+09 | 0.155411E+10 | 0.212624E+09 |
Maximum of Months | 0.288653E+10 | 0.179364E+10 | 0.116529E+10 | 0.585726E+10 | 0.233893E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62003001.54 | 38896065.90 | 23106935.64 | 80498593.58 | 74433003.95 |
February | 55201549.19 | 31577700.44 | 23623848.76 | 64263265.89 | 65637215.67 |
March | 76483898.75 | 39343747.54 | 37140151.21 | 0.102159E+09 | 63060147.40 |
April | 0.105655E+09 | 62971384.63 | 42683417.76 | 0.175973E+09 | 34428135.27 |
May | 0.113146E+09 | 67071865.79 | 46074454.33 | 0.200963E+09 | 24919933.77 |
June | 0.114131E+09 | 70918989.07 | 43211812.98 | 0.231591E+09 | 10085890.07 |
July | 99603705.08 | 56162247.99 | 43441457.09 | 0.203399E+09 | 8406960.40 |
August | 94532548.83 | 53949436.95 | 40583111.87 | 0.191469E+09 | 11066952.65 |
September | 75068144.51 | 36184034.32 | 38884110.19 | 0.145882E+09 | 15889150.61 |
October | 77914880.04 | 47418280.87 | 30496599.17 | 0.121847E+09 | 49472787.57 |
November | 57979513.73 | 34805744.57 | 23173769.16 | 73556760.32 | 69983825.44 |
December | 54624237.24 | 32983593.39 | 21640643.85 | 61447990.94 | 92479069.03 |
Annual Sum or Average | 0.986343E+09 | 0.572283E+09 | 0.414060E+09 | 0.165305E+10 | 0.519863E+09 |
Minimum of Months | 54624237.24 | 31577700.44 | 21640643.85 | 61447990.94 | 8406960.40 |
Maximum of Months | 0.114131E+09 | 70918989.07 | 46074454.33 | 0.231591E+09 | 92479069.03 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207749E+10 | 0.165923E+10 | 0.418261E+09 | 0.317876E+10 | 0.106078E+10 |
February | 0.118645E+10 | 0.800182E+09 | 0.386270E+09 | 0.165516E+10 | 0.877772E+09 |
March | 0.109299E+10 | 0.562945E+09 | 0.530046E+09 | 0.164591E+10 | 0.871563E+09 |
April | 0.900411E+09 | 0.363851E+09 | 0.536560E+09 | 0.171597E+10 | 0.487681E+09 |
May | 0.623485E+09 | 0.103005E+09 | 0.520480E+09 | 0.131102E+10 | 0.342825E+09 |
June | 0.516663E+09 | 39827365.51 | 0.476836E+09 | 0.142055E+10 | 0.134319E+09 |
July | 0.545536E+09 | 56439392.14 | 0.489097E+09 | 0.142456E+10 | 0.109983E+09 |
August | 0.663343E+09 | 0.183313E+09 | 0.480029E+09 | 0.164118E+10 | 0.148586E+09 |
September | 0.924977E+09 | 0.394616E+09 | 0.530361E+09 | 0.192376E+10 | 0.226154E+09 |
October | 0.152298E+10 | 0.105412E+10 | 0.468854E+09 | 0.254412E+10 | 0.688137E+09 |
November | 0.171759E+10 | 0.131558E+10 | 0.402008E+09 | 0.258622E+10 | 0.961236E+09 |
December | 0.193145E+10 | 0.152900E+10 | 0.402451E+09 | 0.281739E+10 | 0.126696E+10 |
Annual Sum or Average | 0.137034E+11 | 0.806212E+10 | 0.564125E+10 | 0.238646E+11 | 0.717600E+10 |
Minimum of Months | 0.516663E+09 | 39827365.51 | 0.386270E+09 | 0.131102E+10 | 0.109983E+09 |
Maximum of Months | 0.207749E+10 | 0.165923E+10 | 0.536560E+09 | 0.317876E+10 | 0.126696E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207749E+10 | 0.165923E+10 | 0.418261E+09 | 0.317876E+10 | 0.106078E+10 |
February | 0.118645E+10 | 0.800182E+09 | 0.386270E+09 | 0.165516E+10 | 0.877772E+09 |
March | 0.109299E+10 | 0.562945E+09 | 0.530046E+09 | 0.164591E+10 | 0.871563E+09 |
April | 0.900411E+09 | 0.363851E+09 | 0.536560E+09 | 0.171597E+10 | 0.487681E+09 |
May | 0.623485E+09 | 0.103005E+09 | 0.520480E+09 | 0.131102E+10 | 0.342825E+09 |
June | 0.516663E+09 | 39827365.51 | 0.476836E+09 | 0.142055E+10 | 0.134319E+09 |
July | 0.545536E+09 | 56439392.14 | 0.489097E+09 | 0.142456E+10 | 0.109983E+09 |
August | 0.663343E+09 | 0.183313E+09 | 0.480029E+09 | 0.164118E+10 | 0.148586E+09 |
September | 0.924977E+09 | 0.394616E+09 | 0.530361E+09 | 0.192376E+10 | 0.226154E+09 |
October | 0.152298E+10 | 0.105412E+10 | 0.468854E+09 | 0.254412E+10 | 0.688137E+09 |
November | 0.171759E+10 | 0.131558E+10 | 0.402008E+09 | 0.258622E+10 | 0.961236E+09 |
December | 0.193145E+10 | 0.152900E+10 | 0.402451E+09 | 0.281739E+10 | 0.126696E+10 |
Annual Sum or Average | 0.137034E+11 | 0.806212E+10 | 0.564125E+10 | 0.238646E+11 | 0.717600E+10 |
Minimum of Months | 0.516663E+09 | 39827365.51 | 0.386270E+09 | 0.131102E+10 | 0.109983E+09 |
Maximum of Months | 0.207749E+10 | 0.165923E+10 | 0.536560E+09 | 0.317876E+10 | 0.126696E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207736E+10 | 0.165913E+10 | 0.418235E+09 | 0.317856E+10 | 0.106072E+10 |
February | 0.118638E+10 | 0.800131E+09 | 0.386246E+09 | 0.165505E+10 | 0.877716E+09 |
March | 0.109292E+10 | 0.562909E+09 | 0.530013E+09 | 0.164580E+10 | 0.871508E+09 |
April | 0.900354E+09 | 0.363828E+09 | 0.536527E+09 | 0.171586E+10 | 0.487650E+09 |
May | 0.623446E+09 | 0.102999E+09 | 0.520447E+09 | 0.131094E+10 | 0.342803E+09 |
June | 0.516631E+09 | 39824848.64 | 0.476806E+09 | 0.142046E+10 | 0.134310E+09 |
July | 0.545501E+09 | 56435825.49 | 0.489066E+09 | 0.142447E+10 | 0.109976E+09 |
August | 0.663301E+09 | 0.183302E+09 | 0.479999E+09 | 0.164108E+10 | 0.148576E+09 |
September | 0.924919E+09 | 0.394591E+09 | 0.530328E+09 | 0.192364E+10 | 0.226140E+09 |
October | 0.152288E+10 | 0.105406E+10 | 0.468824E+09 | 0.254396E+10 | 0.688093E+09 |
November | 0.171748E+10 | 0.131550E+10 | 0.401982E+09 | 0.258606E+10 | 0.961175E+09 |
December | 0.193133E+10 | 0.152890E+10 | 0.402425E+09 | 0.281722E+10 | 0.126688E+10 |
Annual Sum or Average | 0.137025E+11 | 0.806161E+10 | 0.564090E+10 | 0.238631E+11 | 0.717554E+10 |
Minimum of Months | 0.516631E+09 | 39824848.64 | 0.386246E+09 | 0.131094E+10 | 0.109976E+09 |
Maximum of Months | 0.207736E+10 | 0.165913E+10 | 0.536527E+09 | 0.317856E+10 | 0.126688E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163978E+10 | 0.101915E+10 | 0.620634E+09 | 0.238906E+10 | 0.207723E+10 |
February | 0.119983E+10 | 0.580043E+09 | 0.619788E+09 | 0.143326E+10 | 0.174497E+10 |
March | 0.175949E+10 | 0.838772E+09 | 0.920714E+09 | 0.243038E+10 | 0.169720E+10 |
April | 0.261459E+10 | 0.149144E+10 | 0.112315E+10 | 0.447635E+10 | 0.985606E+09 |
May | 0.270868E+10 | 0.151876E+10 | 0.118993E+10 | 0.493541E+10 | 0.730527E+09 |
June | 0.278671E+10 | 0.163903E+10 | 0.114768E+10 | 0.573632E+10 | 0.311151E+09 |
July | 0.209584E+10 | 0.978326E+09 | 0.111751E+10 | 0.444368E+10 | 0.243499E+09 |
August | 0.199857E+10 | 0.100372E+10 | 0.994852E+09 | 0.420559E+10 | 0.309579E+09 |
September | 0.168589E+10 | 0.708339E+09 | 0.977548E+09 | 0.336675E+10 | 0.439740E+09 |
October | 0.178251E+10 | 0.101923E+10 | 0.763279E+09 | 0.289146E+10 | 0.136506E+10 |
November | 0.158878E+10 | 0.959256E+09 | 0.629523E+09 | 0.223169E+10 | 0.192288E+10 |
December | 0.132317E+10 | 0.753372E+09 | 0.569801E+09 | 0.170690E+10 | 0.253291E+10 |
Annual Sum or Average | 0.231838E+11 | 0.125094E+11 | 0.106744E+11 | 0.402468E+11 | 0.143603E+11 |
Minimum of Months | 0.119983E+10 | 0.580043E+09 | 0.569801E+09 | 0.143326E+10 | 0.243499E+09 |
Maximum of Months | 0.278671E+10 | 0.163903E+10 | 0.118993E+10 | 0.573632E+10 | 0.253291E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 64835315.84 | 40296040.96 | 24539274.88 | 94461003.30 | 82131676.55 |
February | 47440085.14 | 22934289.60 | 24505795.54 | 56669774.77 | 68994364.57 |
March | 69568302.24 | 33164184.88 | 36404117.36 | 96094719.75 | 67105575.81 |
April | 0.103378E+09 | 58969948.50 | 44408441.88 | 0.176990E+09 | 38969939.82 |
May | 0.107099E+09 | 60050029.77 | 47048541.08 | 0.195141E+09 | 28884324.61 |
June | 0.110184E+09 | 64805458.31 | 45378164.41 | 0.226808E+09 | 12302599.72 |
July | 82867389.00 | 38682005.84 | 44185383.16 | 0.175699E+09 | 9627702.81 |
August | 79021467.22 | 39686009.75 | 39335457.46 | 0.166285E+09 | 12240452.80 |
September | 66658256.67 | 28006975.97 | 38651280.69 | 0.133118E+09 | 17386912.41 |
October | 70478756.76 | 40299438.77 | 30179317.99 | 0.114325E+09 | 53973076.36 |
November | 62818720.93 | 37927983.01 | 24890737.93 | 88238548.98 | 76028965.18 |
December | 52316928.45 | 29787537.45 | 22529391.01 | 67489104.01 | 0.100149E+09 |
Annual Sum or Average | 0.916666E+09 | 0.494610E+09 | 0.422056E+09 | 0.159132E+10 | 0.567794E+09 |
Minimum of Months | 47440085.14 | 22934289.60 | 22529391.01 | 56669774.77 | 9627702.81 |
Maximum of Months | 0.110184E+09 | 64805458.31 | 47048541.08 | 0.226808E+09 | 0.100149E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.756926E+09 | 0.00 | 0.756926E+09 | 0.601695E+09 | 0.309202E+10 |
February | 0.779031E+09 | 0.00 | 0.779031E+09 | 0.387280E+09 | 0.274317E+10 |
March | 0.114626E+10 | 0.00 | 0.114626E+10 | 0.108239E+10 | 0.268926E+10 |
April | 0.135150E+10 | 14025087.93 | 0.133747E+10 | 0.224292E+10 | 0.142377E+10 |
May | 0.163481E+10 | 0.130900E+09 | 0.150391E+10 | 0.317037E+10 | 0.988936E+09 |
June | 0.183847E+10 | 0.334031E+09 | 0.150444E+10 | 0.474221E+10 | 0.409506E+09 |
July | 0.162013E+10 | 0.168785E+09 | 0.145134E+10 | 0.417916E+10 | 0.320211E+09 |
August | 0.130774E+10 | 32487191.21 | 0.127525E+10 | 0.345800E+10 | 0.406371E+09 |
September | 0.119403E+10 | 318747.42 | 0.119371E+10 | 0.279172E+10 | 0.598653E+09 |
October | 0.954585E+09 | 0.00 | 0.954585E+09 | 0.139784E+10 | 0.196039E+10 |
November | 0.769689E+09 | 0.00 | 0.769689E+09 | 0.586222E+09 | 0.277288E+10 |
December | 0.707039E+09 | 0.00 | 0.707039E+09 | 0.365392E+09 | 0.374172E+10 |
Annual Sum or Average | 0.140602E+11 | 0.680547E+09 | 0.133796E+11 | 0.250052E+11 | 0.211469E+11 |
Minimum of Months | 0.707039E+09 | 0.00 | 0.707039E+09 | 0.365392E+09 | 0.320211E+09 |
Maximum of Months | 0.183847E+10 | 0.334031E+09 | 0.150444E+10 | 0.474221E+10 | 0.374172E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163017E+10 | 0.102265E+10 | 0.607520E+09 | 0.209295E+10 | 0.192159E+10 |
February | 0.145135E+10 | 0.830239E+09 | 0.621112E+09 | 0.165375E+10 | 0.173353E+10 |
March | 0.201090E+10 | 0.103442E+10 | 0.976479E+09 | 0.262536E+10 | 0.168443E+10 |
April | 0.277786E+10 | 0.165564E+10 | 0.112222E+10 | 0.458224E+10 | 0.905949E+09 |
May | 0.297482E+10 | 0.176345E+10 | 0.121137E+10 | 0.523868E+10 | 0.661302E+09 |
June | 0.300071E+10 | 0.186460E+10 | 0.113611E+10 | 0.605930E+10 | 0.266794E+09 |
July | 0.261876E+10 | 0.147661E+10 | 0.114215E+10 | 0.534100E+10 | 0.208865E+09 |
August | 0.248543E+10 | 0.141844E+10 | 0.106700E+10 | 0.503502E+10 | 0.265279E+09 |
September | 0.197368E+10 | 0.951348E+09 | 0.102233E+10 | 0.384446E+10 | 0.379418E+09 |
October | 0.204853E+10 | 0.124672E+10 | 0.801807E+09 | 0.320563E+10 | 0.122176E+10 |
November | 0.152439E+10 | 0.915110E+09 | 0.609278E+09 | 0.193776E+10 | 0.174091E+10 |
December | 0.143617E+10 | 0.867202E+09 | 0.568969E+09 | 0.162297E+10 | 0.232323E+10 |
Annual Sum or Average | 0.259328E+11 | 0.150464E+11 | 0.108863E+11 | 0.432391E+11 | 0.133131E+11 |
Minimum of Months | 0.143617E+10 | 0.830239E+09 | 0.568969E+09 | 0.162297E+10 | 0.208865E+09 |
Maximum of Months | 0.300071E+10 | 0.186460E+10 | 0.121137E+10 | 0.605930E+10 | 0.232323E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.623260E+10 | 0.497780E+10 | 0.125480E+10 | 0.949352E+10 | 0.302199E+10 |
February | 0.355942E+10 | 0.240059E+10 | 0.115882E+10 | 0.487400E+10 | 0.263926E+10 |
March | 0.327902E+10 | 0.168887E+10 | 0.159015E+10 | 0.482705E+10 | 0.267698E+10 |
April | 0.270126E+10 | 0.109157E+10 | 0.160969E+10 | 0.509768E+10 | 0.149326E+10 |
May | 0.187047E+10 | 0.309023E+09 | 0.156144E+10 | 0.388951E+10 | 0.108237E+10 |
June | 0.154999E+10 | 0.119485E+09 | 0.143051E+10 | 0.426841E+10 | 0.428908E+09 |
July | 0.163662E+10 | 0.169322E+09 | 0.146730E+10 | 0.430669E+10 | 0.326081E+09 |
August | 0.199005E+10 | 0.549951E+09 | 0.144010E+10 | 0.498501E+10 | 0.411448E+09 |
September | 0.277497E+10 | 0.118387E+10 | 0.159110E+10 | 0.583635E+10 | 0.604755E+09 |
October | 0.456901E+10 | 0.316244E+10 | 0.140657E+10 | 0.764806E+10 | 0.191596E+10 |
November | 0.515286E+10 | 0.394683E+10 | 0.120603E+10 | 0.774454E+10 | 0.268990E+10 |
December | 0.579446E+10 | 0.458709E+10 | 0.120737E+10 | 0.842226E+10 | 0.358877E+10 |
Annual Sum or Average | 0.411107E+11 | 0.241868E+11 | 0.169239E+11 | 0.713931E+11 | 0.208797E+11 |
Minimum of Months | 0.154999E+10 | 0.119485E+09 | 0.115882E+10 | 0.388951E+10 | 0.326081E+09 |
Maximum of Months | 0.623260E+10 | 0.497780E+10 | 0.160969E+10 | 0.949352E+10 | 0.358877E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170464E+10 | 0.105946E+10 | 0.645179E+09 | 0.246900E+10 | 0.211385E+10 |
February | 0.124729E+10 | 0.602987E+09 | 0.644300E+09 | 0.145988E+10 | 0.182958E+10 |
March | 0.182908E+10 | 0.871951E+09 | 0.957127E+09 | 0.247418E+10 | 0.179711E+10 |
April | 0.271801E+10 | 0.155043E+10 | 0.116757E+10 | 0.461897E+10 | 0.102205E+10 |
May | 0.281582E+10 | 0.157883E+10 | 0.123698E+10 | 0.509770E+10 | 0.762212E+09 |
June | 0.289693E+10 | 0.170386E+10 | 0.119307E+10 | 0.594677E+10 | 0.322141E+09 |
July | 0.217873E+10 | 0.101702E+10 | 0.116171E+10 | 0.462351E+10 | 0.241661E+09 |
August | 0.207762E+10 | 0.104342E+10 | 0.103420E+10 | 0.438652E+10 | 0.298293E+09 |
September | 0.175257E+10 | 0.736358E+09 | 0.101621E+10 | 0.351896E+10 | 0.418132E+09 |
October | 0.185302E+10 | 0.105955E+10 | 0.793465E+09 | 0.301621E+10 | 0.133472E+10 |
November | 0.165162E+10 | 0.997200E+09 | 0.654420E+09 | 0.232692E+10 | 0.188330E+10 |
December | 0.137551E+10 | 0.783172E+09 | 0.592336E+09 | 0.178189E+10 | 0.251501E+10 |
Annual Sum or Average | 0.241008E+11 | 0.130043E+11 | 0.110966E+11 | 0.417205E+11 | 0.145381E+11 |
Minimum of Months | 0.124729E+10 | 0.602987E+09 | 0.592336E+09 | 0.145988E+10 | 0.241661E+09 |
Maximum of Months | 0.289693E+10 | 0.170386E+10 | 0.123698E+10 | 0.594677E+10 | 0.251501E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 242.20 | 1070.98 | 282.60 | 0.00 | 282.60 | 0.00 | 0.00 |
February | 173.38 | 1044.56 | 322.02 | 0.00 | 322.02 | 0.00 | 0.00 |
March | 417.30 | 945.28 | 427.96 | 0.00 | 427.96 | 0.00 | 0.00 |
April | 862.08 | 527.58 | 521.41 | 5.41 | 516.00 | 0.00 | 0.00 |
May | 1179.10 | 359.67 | 610.37 | 48.87 | 561.49 | 0.00 | 0.00 |
June | 1817.96 | 156.33 | 709.29 | 128.87 | 580.42 | 0.00 | 0.00 |
July | 1546.92 | 119.32 | 604.89 | 63.02 | 541.87 | 0.00 | 0.00 |
August | 1281.49 | 148.38 | 488.25 | 12.13 | 476.12 | 0.00 | 0.00 |
September | 1071.14 | 223.52 | 460.66 | 0.12 | 460.54 | 0.00 | 0.00 |
October | 528.54 | 685.59 | 356.40 | 0.00 | 356.40 | 0.00 | 0.00 |
November | 242.11 | 987.83 | 296.95 | 0.00 | 296.95 | 0.00 | 0.00 |
December | 156.79 | 1289.02 | 263.98 | 0.00 | 263.98 | 0.00 | 0.00 |
Annual Sum or Average | 796.10 | 628.14 | 445.85 | 21.58 | 424.27 | 0.00 | 0.00 |
Minimum of Months | 156.79 | 119.32 | 263.98 | 0.00 | 263.98 | 0.00 | 0.00 |
Maximum of Months | 1817.96 | 1289.02 | 709.29 | 128.87 | 580.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 799.32 | 671.95 | 608.64 | 381.81 | 226.82 | 0.00 | 0.00 |
February | 697.15 | 665.03 | 599.93 | 343.19 | 256.74 | 0.00 | 0.00 |
March | 993.27 | 596.99 | 750.78 | 386.21 | 364.58 | 0.00 | 0.00 |
April | 1768.29 | 338.38 | 1071.70 | 638.75 | 432.95 | 0.00 | 0.00 |
May | 1954.04 | 240.24 | 1110.67 | 658.40 | 452.28 | 0.00 | 0.00 |
June | 2331.67 | 101.35 | 1157.68 | 719.37 | 438.31 | 0.00 | 0.00 |
July | 1987.38 | 77.44 | 977.73 | 551.30 | 426.43 | 0.00 | 0.00 |
August | 1875.62 | 96.22 | 927.95 | 529.58 | 398.37 | 0.00 | 0.00 |
September | 1481.66 | 141.60 | 761.45 | 367.03 | 394.42 | 0.00 | 0.00 |
October | 1204.40 | 431.23 | 764.83 | 465.47 | 299.36 | 0.00 | 0.00 |
November | 764.07 | 625.94 | 588.11 | 353.05 | 235.06 | 0.00 | 0.00 |
December | 629.85 | 805.13 | 536.21 | 323.78 | 212.43 | 0.00 | 0.00 |
Annual Sum or Average | 1377.13 | 398.17 | 822.32 | 477.12 | 345.20 | 0.00 | 0.00 |
Minimum of Months | 629.85 | 77.44 | 536.21 | 323.78 | 212.43 | 0.00 | 0.00 |
Maximum of Months | 2331.67 | 805.13 | 1157.68 | 719.37 | 452.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3560.19 | 1062.69 | 2326.98 | 1858.50 | 468.49 | 0.00 | 0.00 |
February | 2029.86 | 1015.80 | 1471.32 | 992.31 | 479.01 | 0.00 | 0.00 |
March | 1812.80 | 946.95 | 1224.25 | 630.55 | 593.70 | 0.00 | 0.00 |
April | 1961.03 | 553.92 | 1042.15 | 421.13 | 621.02 | 0.00 | 0.00 |
May | 1445.50 | 390.79 | 698.35 | 115.38 | 582.98 | 0.00 | 0.00 |
June | 1634.78 | 162.23 | 597.99 | 46.10 | 551.89 | 0.00 | 0.00 |
July | 1593.98 | 120.59 | 611.04 | 63.22 | 547.83 | 0.00 | 0.00 |
August | 1850.24 | 149.21 | 743.00 | 205.33 | 537.67 | 0.00 | 0.00 |
September | 2243.21 | 225.71 | 1070.59 | 456.74 | 613.85 | 0.00 | 0.00 |
October | 2859.24 | 676.96 | 1705.87 | 1180.72 | 525.15 | 0.00 | 0.00 |
November | 3003.34 | 973.28 | 1987.99 | 1522.70 | 465.29 | 0.00 | 0.00 |
December | 3168.01 | 1253.65 | 2163.40 | 1712.62 | 450.78 | 0.00 | 0.00 |
Annual Sum or Average | 2266.02 | 626.09 | 1303.61 | 766.96 | 536.65 | 0.00 | 0.00 |
Minimum of Months | 1445.50 | 120.59 | 597.99 | 46.10 | 450.78 | 0.00 | 0.00 |
Maximum of Months | 3560.19 | 1253.65 | 2326.98 | 1858.50 | 621.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 931.13 | 735.83 | 636.44 | 395.56 | 240.88 | 0.00 | 0.00 |
February | 611.28 | 699.20 | 515.58 | 249.25 | 266.33 | 0.00 | 0.00 |
March | 930.57 | 632.94 | 682.90 | 325.55 | 357.35 | 0.00 | 0.00 |
April | 1777.72 | 379.35 | 1048.61 | 598.16 | 450.45 | 0.00 | 0.00 |
May | 1897.08 | 275.70 | 1051.31 | 589.47 | 461.84 | 0.00 | 0.00 |
June | 2284.16 | 122.20 | 1117.64 | 657.35 | 460.29 | 0.00 | 0.00 |
July | 1716.50 | 89.60 | 813.45 | 379.71 | 433.73 | 0.00 | 0.00 |
August | 1630.21 | 108.73 | 775.69 | 389.57 | 386.12 | 0.00 | 0.00 |
September | 1352.42 | 156.42 | 676.14 | 284.09 | 392.06 | 0.00 | 0.00 |
October | 1128.46 | 468.68 | 691.84 | 395.59 | 296.25 | 0.00 | 0.00 |
November | 906.23 | 674.96 | 637.20 | 384.72 | 252.48 | 0.00 | 0.00 |
December | 677.72 | 870.47 | 513.56 | 292.40 | 221.15 | 0.00 | 0.00 |
Annual Sum or Average | 1323.27 | 433.44 | 764.23 | 412.36 | 351.87 | 0.00 | 0.00 |
Minimum of Months | 611.28 | 89.60 | 513.56 | 249.25 | 221.15 | 0.00 | 0.00 |
Maximum of Months | 2284.16 | 870.47 | 1117.64 | 657.35 | 461.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 233.48 | 1142.78 | 282.60 | 0.00 | 282.60 | 0.00 | 0.00 |
February | 176.58 | 1097.67 | 322.01 | 0.00 | 322.01 | 0.00 | 0.00 |
March | 434.22 | 955.88 | 427.96 | 0.00 | 427.96 | 0.00 | 0.00 |
April | 886.03 | 523.57 | 521.40 | 5.41 | 515.99 | 0.00 | 0.00 |
May | 1206.13 | 347.65 | 610.36 | 48.87 | 561.49 | 0.00 | 0.00 |
June | 1842.54 | 146.70 | 709.27 | 128.87 | 580.41 | 0.00 | 0.00 |
July | 1560.54 | 117.77 | 604.87 | 63.02 | 541.86 | 0.00 | 0.00 |
August | 1284.12 | 155.02 | 488.24 | 12.13 | 476.11 | 0.00 | 0.00 |
September | 1064.52 | 243.09 | 460.65 | 0.12 | 460.53 | 0.00 | 0.00 |
October | 512.85 | 761.63 | 356.39 | 0.00 | 356.39 | 0.00 | 0.00 |
November | 218.90 | 1112.83 | 296.94 | 0.00 | 296.94 | 0.00 | 0.00 |
December | 130.43 | 1436.01 | 263.97 | 0.00 | 263.97 | 0.00 | 0.00 |
Annual Sum or Average | 798.68 | 668.33 | 445.84 | 21.58 | 424.26 | 0.00 | 0.00 |
Minimum of Months | 130.43 | 117.77 | 263.97 | 0.00 | 263.97 | 0.00 | 0.00 |
Maximum of Months | 1842.54 | 1436.01 | 709.27 | 128.87 | 580.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 790.18 | 730.64 | 608.63 | 381.81 | 226.82 | 0.00 | 0.00 |
February | 698.40 | 713.33 | 599.92 | 343.18 | 256.74 | 0.00 | 0.00 |
March | 1002.80 | 619.00 | 750.77 | 386.20 | 364.57 | 0.00 | 0.00 |
April | 1784.94 | 349.21 | 1071.69 | 638.74 | 432.95 | 0.00 | 0.00 |
May | 1972.67 | 244.62 | 1110.65 | 658.38 | 452.27 | 0.00 | 0.00 |
June | 2349.09 | 102.30 | 1157.66 | 719.35 | 438.31 | 0.00 | 0.00 |
July | 1996.58 | 82.52 | 977.72 | 551.29 | 426.43 | 0.00 | 0.00 |
August | 1879.48 | 108.63 | 927.94 | 529.57 | 398.37 | 0.00 | 0.00 |
September | 1479.72 | 161.17 | 761.44 | 367.03 | 394.41 | 0.00 | 0.00 |
October | 1196.06 | 485.63 | 764.82 | 465.46 | 299.36 | 0.00 | 0.00 |
November | 746.11 | 709.87 | 588.10 | 353.04 | 235.06 | 0.00 | 0.00 |
December | 603.18 | 907.78 | 536.20 | 323.77 | 212.43 | 0.00 | 0.00 |
Annual Sum or Average | 1378.14 | 433.41 | 822.31 | 477.11 | 345.20 | 0.00 | 0.00 |
Minimum of Months | 603.18 | 82.52 | 536.20 | 323.77 | 212.43 | 0.00 | 0.00 |
Maximum of Months | 2349.09 | 907.78 | 1157.66 | 719.35 | 452.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3560.37 | 1188.13 | 2326.89 | 1858.42 | 468.47 | 0.00 | 0.00 |
February | 2052.48 | 1088.48 | 1471.26 | 992.27 | 479.00 | 0.00 | 0.00 |
March | 1843.50 | 976.19 | 1224.20 | 630.52 | 593.68 | 0.00 | 0.00 |
April | 1986.03 | 564.43 | 1042.12 | 421.11 | 621.01 | 0.00 | 0.00 |
May | 1468.41 | 383.98 | 698.33 | 115.37 | 582.96 | 0.00 | 0.00 |
June | 1644.12 | 155.46 | 597.98 | 46.10 | 551.88 | 0.00 | 0.00 |
July | 1595.58 | 123.19 | 611.03 | 63.21 | 547.81 | 0.00 | 0.00 |
August | 1838.20 | 166.42 | 742.98 | 205.32 | 537.66 | 0.00 | 0.00 |
September | 2226.53 | 261.75 | 1070.55 | 456.72 | 613.83 | 0.00 | 0.00 |
October | 2849.54 | 770.75 | 1705.81 | 1180.67 | 525.14 | 0.00 | 0.00 |
November | 2993.25 | 1112.52 | 1987.91 | 1522.63 | 465.28 | 0.00 | 0.00 |
December | 3155.62 | 1419.05 | 2163.32 | 1712.55 | 450.76 | 0.00 | 0.00 |
Annual Sum or Average | 2270.18 | 682.63 | 1303.57 | 766.93 | 536.64 | 0.00 | 0.00 |
Minimum of Months | 1468.41 | 123.19 | 597.98 | 46.10 | 450.76 | 0.00 | 0.00 |
Maximum of Months | 3560.37 | 1419.05 | 2326.89 | 1858.42 | 621.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 927.24 | 806.21 | 636.43 | 395.55 | 240.88 | 0.00 | 0.00 |
February | 615.88 | 749.82 | 515.57 | 249.25 | 266.33 | 0.00 | 0.00 |
March | 943.28 | 658.71 | 682.89 | 325.54 | 357.35 | 0.00 | 0.00 |
April | 1795.27 | 395.28 | 1048.60 | 598.15 | 450.45 | 0.00 | 0.00 |
May | 1915.53 | 283.53 | 1051.29 | 589.46 | 461.83 | 0.00 | 0.00 |
June | 2300.59 | 124.79 | 1117.63 | 657.34 | 460.28 | 0.00 | 0.00 |
July | 1724.68 | 94.51 | 813.44 | 379.71 | 433.73 | 0.00 | 0.00 |
August | 1632.27 | 120.15 | 775.68 | 389.56 | 386.12 | 0.00 | 0.00 |
September | 1350.26 | 176.36 | 676.14 | 284.08 | 392.05 | 0.00 | 0.00 |
October | 1122.23 | 529.81 | 691.83 | 395.58 | 296.24 | 0.00 | 0.00 |
November | 895.03 | 771.18 | 637.19 | 384.72 | 252.47 | 0.00 | 0.00 |
December | 662.48 | 983.07 | 513.55 | 292.40 | 221.15 | 0.00 | 0.00 |
Annual Sum or Average | 1326.68 | 473.37 | 764.22 | 412.36 | 351.87 | 0.00 | 0.00 |
Minimum of Months | 615.88 | 94.51 | 513.55 | 249.25 | 221.15 | 0.00 | 0.00 |
Maximum of Months | 2300.59 | 983.07 | 1117.63 | 657.34 | 461.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 224.65 | 1154.43 | 282.60 | 0.00 | 282.60 | 0.00 | 0.00 |
February | 160.09 | 1133.91 | 322.02 | 0.00 | 322.02 | 0.00 | 0.00 |
March | 404.12 | 1004.05 | 427.96 | 0.00 | 427.96 | 0.00 | 0.00 |
April | 865.32 | 549.30 | 521.41 | 5.41 | 516.00 | 0.00 | 0.00 |
May | 1183.68 | 369.23 | 610.37 | 48.87 | 561.49 | 0.00 | 0.00 |
June | 1829.56 | 157.99 | 709.29 | 128.87 | 580.42 | 0.00 | 0.00 |
July | 1560.32 | 119.55 | 604.89 | 63.02 | 541.87 | 0.00 | 0.00 |
August | 1291.07 | 151.72 | 488.25 | 12.13 | 476.12 | 0.00 | 0.00 |
September | 1077.05 | 230.96 | 460.66 | 0.12 | 460.54 | 0.00 | 0.00 |
October | 521.89 | 731.93 | 356.40 | 0.00 | 356.40 | 0.00 | 0.00 |
November | 226.17 | 1069.78 | 296.95 | 0.00 | 296.95 | 0.00 | 0.00 |
December | 136.42 | 1397.00 | 263.98 | 0.00 | 263.98 | 0.00 | 0.00 |
Annual Sum or Average | 792.91 | 670.56 | 445.85 | 21.58 | 424.27 | 0.00 | 0.00 |
Minimum of Months | 136.42 | 119.55 | 263.98 | 0.00 | 263.98 | 0.00 | 0.00 |
Maximum of Months | 1829.56 | 1397.00 | 709.29 | 128.87 | 580.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 781.42 | 717.44 | 608.64 | 381.81 | 226.82 | 0.00 | 0.00 |
February | 683.59 | 716.57 | 599.93 | 343.19 | 256.74 | 0.00 | 0.00 |
March | 980.20 | 628.89 | 750.78 | 386.21 | 364.58 | 0.00 | 0.00 |
April | 1767.84 | 349.52 | 1071.70 | 638.75 | 432.95 | 0.00 | 0.00 |
May | 1955.90 | 246.90 | 1110.67 | 658.40 | 452.28 | 0.00 | 0.00 |
June | 2337.69 | 102.93 | 1157.68 | 719.37 | 438.31 | 0.00 | 0.00 |
July | 1994.10 | 77.98 | 977.73 | 551.30 | 426.43 | 0.00 | 0.00 |
August | 1879.86 | 99.04 | 927.95 | 529.58 | 398.37 | 0.00 | 0.00 |
September | 1483.20 | 146.38 | 761.45 | 367.03 | 394.42 | 0.00 | 0.00 |
October | 1196.85 | 456.15 | 764.83 | 465.47 | 299.36 | 0.00 | 0.00 |
November | 747.59 | 671.65 | 588.11 | 353.05 | 235.06 | 0.00 | 0.00 |
December | 605.95 | 867.40 | 536.21 | 323.78 | 212.43 | 0.00 | 0.00 |
Annual Sum or Average | 1371.10 | 422.15 | 822.32 | 477.12 | 345.20 | 0.00 | 0.00 |
Minimum of Months | 605.95 | 77.98 | 536.21 | 323.78 | 212.43 | 0.00 | 0.00 |
Maximum of Months | 2337.69 | 867.40 | 1157.68 | 719.37 | 452.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3544.47 | 1128.28 | 2326.98 | 1858.50 | 468.49 | 0.00 | 0.00 |
February | 2014.71 | 1090.97 | 1471.32 | 992.31 | 479.01 | 0.00 | 0.00 |
March | 1802.22 | 999.47 | 1224.25 | 630.55 | 593.70 | 0.00 | 0.00 |
April | 1966.70 | 576.10 | 1042.15 | 421.13 | 621.02 | 0.00 | 0.00 |
May | 1452.18 | 404.11 | 698.35 | 115.38 | 582.98 | 0.00 | 0.00 |
June | 1646.76 | 165.47 | 597.99 | 46.10 | 551.89 | 0.00 | 0.00 |
July | 1607.93 | 121.74 | 611.04 | 63.22 | 547.83 | 0.00 | 0.00 |
August | 1861.19 | 153.62 | 743.00 | 205.33 | 537.67 | 0.00 | 0.00 |
September | 2251.68 | 233.32 | 1070.59 | 456.74 | 613.85 | 0.00 | 0.00 |
October | 2855.46 | 715.34 | 1705.87 | 1180.72 | 525.15 | 0.00 | 0.00 |
November | 2987.86 | 1037.77 | 1987.99 | 1522.70 | 465.29 | 0.00 | 0.00 |
December | 3144.51 | 1339.89 | 2163.40 | 1712.62 | 450.78 | 0.00 | 0.00 |
Annual Sum or Average | 2263.86 | 662.09 | 1303.61 | 766.96 | 536.65 | 0.00 | 0.00 |
Minimum of Months | 1452.18 | 121.74 | 597.99 | 46.10 | 450.78 | 0.00 | 0.00 |
Maximum of Months | 3544.47 | 1339.89 | 2326.98 | 1858.50 | 621.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 921.82 | 789.22 | 636.44 | 395.56 | 240.88 | 0.00 | 0.00 |
February | 603.45 | 756.27 | 515.58 | 249.25 | 266.33 | 0.00 | 0.00 |
March | 923.75 | 670.96 | 682.90 | 325.55 | 357.35 | 0.00 | 0.00 |
April | 1782.01 | 394.31 | 1048.61 | 598.16 | 450.45 | 0.00 | 0.00 |
May | 1903.26 | 284.58 | 1051.31 | 589.47 | 461.84 | 0.00 | 0.00 |
June | 2294.28 | 124.28 | 1117.64 | 657.35 | 460.29 | 0.00 | 0.00 |
July | 1726.22 | 90.23 | 813.45 | 379.71 | 433.73 | 0.00 | 0.00 |
August | 1637.74 | 111.37 | 775.69 | 389.57 | 386.12 | 0.00 | 0.00 |
September | 1357.62 | 161.32 | 676.14 | 284.09 | 392.06 | 0.00 | 0.00 |
October | 1126.12 | 498.33 | 691.84 | 395.59 | 296.25 | 0.00 | 0.00 |
November | 897.73 | 726.58 | 637.20 | 384.72 | 252.48 | 0.00 | 0.00 |
December | 665.28 | 939.00 | 513.56 | 292.40 | 221.15 | 0.00 | 0.00 |
Annual Sum or Average | 1322.95 | 461.00 | 764.23 | 412.36 | 351.87 | 0.00 | 0.00 |
Minimum of Months | 603.45 | 90.23 | 513.56 | 249.25 | 221.15 | 0.00 | 0.00 |
Maximum of Months | 2294.28 | 939.00 | 1117.64 | 657.35 | 461.84 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.648710E+09 | 0.286853E+10 | 0.756926E+09 | 0.00 | 0.756926E+09 | 0.00 | 0.00 |
February | 0.419437E+09 | 0.252701E+10 | 0.779031E+09 | 0.00 | 0.779031E+09 | 0.00 | 0.00 |
March | 0.111769E+10 | 0.253184E+10 | 0.114626E+10 | 0.00 | 0.114626E+10 | 0.00 | 0.00 |
April | 0.223450E+10 | 0.136748E+10 | 0.135150E+10 | 14025087.93 | 0.133747E+10 | 0.00 | 0.00 |
May | 0.315810E+10 | 0.963349E+09 | 0.163481E+10 | 0.130900E+09 | 0.150391E+10 | 0.00 | 0.00 |
June | 0.471215E+10 | 0.405201E+09 | 0.183847E+10 | 0.334031E+09 | 0.150444E+10 | 0.00 | 0.00 |
July | 0.414328E+10 | 0.319590E+09 | 0.162013E+10 | 0.168785E+09 | 0.145134E+10 | 0.00 | 0.00 |
August | 0.343234E+10 | 0.397427E+09 | 0.130774E+10 | 32487191.21 | 0.127525E+10 | 0.00 | 0.00 |
September | 0.277640E+10 | 0.579368E+09 | 0.119403E+10 | 318747.42 | 0.119371E+10 | 0.00 | 0.00 |
October | 0.141564E+10 | 0.183628E+10 | 0.954585E+09 | 0.00 | 0.954585E+09 | 0.00 | 0.00 |
November | 0.627537E+09 | 0.256044E+10 | 0.769689E+09 | 0.00 | 0.769689E+09 | 0.00 | 0.00 |
December | 0.419946E+09 | 0.345252E+10 | 0.707039E+09 | 0.00 | 0.707039E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.251057E+11 | 0.198090E+11 | 0.140602E+11 | 0.680547E+09 | 0.133796E+11 | 0.00 | 0.00 |
Minimum of Months | 0.419437E+09 | 0.319590E+09 | 0.707039E+09 | 0.00 | 0.707039E+09 | 0.00 | 0.00 |
Maximum of Months | 0.471215E+10 | 0.345252E+10 | 0.183847E+10 | 0.334031E+09 | 0.150444E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.214089E+10 | 0.179974E+10 | 0.163017E+10 | 0.102265E+10 | 0.607520E+09 | 0.00 | 0.00 |
February | 0.168653E+10 | 0.160885E+10 | 0.145135E+10 | 0.830239E+09 | 0.621112E+09 | 0.00 | 0.00 |
March | 0.266037E+10 | 0.159897E+10 | 0.201090E+10 | 0.103442E+10 | 0.976479E+09 | 0.00 | 0.00 |
April | 0.458340E+10 | 0.877069E+09 | 0.277786E+10 | 0.165564E+10 | 0.112222E+10 | 0.00 | 0.00 |
May | 0.523371E+10 | 0.643456E+09 | 0.297482E+10 | 0.176345E+10 | 0.121137E+10 | 0.00 | 0.00 |
June | 0.604369E+10 | 0.262687E+09 | 0.300071E+10 | 0.186460E+10 | 0.113611E+10 | 0.00 | 0.00 |
July | 0.532299E+10 | 0.207422E+09 | 0.261876E+10 | 0.147661E+10 | 0.114215E+10 | 0.00 | 0.00 |
August | 0.502366E+10 | 0.257720E+09 | 0.248543E+10 | 0.141844E+10 | 0.106700E+10 | 0.00 | 0.00 |
September | 0.384045E+10 | 0.367029E+09 | 0.197368E+10 | 0.951348E+09 | 0.102233E+10 | 0.00 | 0.00 |
October | 0.322586E+10 | 0.115500E+10 | 0.204853E+10 | 0.124672E+10 | 0.801807E+09 | 0.00 | 0.00 |
November | 0.198048E+10 | 0.162245E+10 | 0.152439E+10 | 0.915110E+09 | 0.609278E+09 | 0.00 | 0.00 |
December | 0.168699E+10 | 0.215645E+10 | 0.143617E+10 | 0.867202E+09 | 0.568969E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.434290E+11 | 0.125568E+11 | 0.259328E+11 | 0.150464E+11 | 0.108863E+11 | 0.00 | 0.00 |
Minimum of Months | 0.168653E+10 | 0.207422E+09 | 0.143617E+10 | 0.830239E+09 | 0.568969E+09 | 0.00 | 0.00 |
Maximum of Months | 0.604369E+10 | 0.215645E+10 | 0.300071E+10 | 0.186460E+10 | 0.121137E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.953562E+10 | 0.284632E+10 | 0.623260E+10 | 0.497780E+10 | 0.125480E+10 | 0.00 | 0.00 |
February | 0.491063E+10 | 0.245742E+10 | 0.355942E+10 | 0.240059E+10 | 0.115882E+10 | 0.00 | 0.00 |
March | 0.485540E+10 | 0.253632E+10 | 0.327902E+10 | 0.168887E+10 | 0.159015E+10 | 0.00 | 0.00 |
April | 0.508300E+10 | 0.143577E+10 | 0.270126E+10 | 0.109157E+10 | 0.160969E+10 | 0.00 | 0.00 |
May | 0.387163E+10 | 0.104669E+10 | 0.187047E+10 | 0.309023E+09 | 0.156144E+10 | 0.00 | 0.00 |
June | 0.423735E+10 | 0.420509E+09 | 0.154999E+10 | 0.119485E+09 | 0.143051E+10 | 0.00 | 0.00 |
July | 0.426932E+10 | 0.322986E+09 | 0.163662E+10 | 0.169322E+09 | 0.146730E+10 | 0.00 | 0.00 |
August | 0.495569E+10 | 0.399640E+09 | 0.199005E+10 | 0.549951E+09 | 0.144010E+10 | 0.00 | 0.00 |
September | 0.581440E+10 | 0.585044E+09 | 0.277497E+10 | 0.118387E+10 | 0.159110E+10 | 0.00 | 0.00 |
October | 0.765820E+10 | 0.181318E+10 | 0.456901E+10 | 0.316244E+10 | 0.140657E+10 | 0.00 | 0.00 |
November | 0.778465E+10 | 0.252274E+10 | 0.515286E+10 | 0.394683E+10 | 0.120603E+10 | 0.00 | 0.00 |
December | 0.848520E+10 | 0.335777E+10 | 0.579446E+10 | 0.458709E+10 | 0.120737E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.714611E+11 | 0.197444E+11 | 0.411107E+11 | 0.241868E+11 | 0.169239E+11 | 0.00 | 0.00 |
Minimum of Months | 0.387163E+10 | 0.322986E+09 | 0.154999E+10 | 0.119485E+09 | 0.115882E+10 | 0.00 | 0.00 |
Maximum of Months | 0.953562E+10 | 0.335777E+10 | 0.623260E+10 | 0.497780E+10 | 0.160969E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.249393E+10 | 0.197084E+10 | 0.170464E+10 | 0.105946E+10 | 0.645179E+09 | 0.00 | 0.00 |
February | 0.147881E+10 | 0.169151E+10 | 0.124729E+10 | 0.602987E+09 | 0.644300E+09 | 0.00 | 0.00 |
March | 0.249243E+10 | 0.169527E+10 | 0.182908E+10 | 0.871951E+09 | 0.957127E+09 | 0.00 | 0.00 |
April | 0.460784E+10 | 0.983280E+09 | 0.271801E+10 | 0.155043E+10 | 0.116757E+10 | 0.00 | 0.00 |
May | 0.508114E+10 | 0.738440E+09 | 0.281582E+10 | 0.157883E+10 | 0.123698E+10 | 0.00 | 0.00 |
June | 0.592054E+10 | 0.316737E+09 | 0.289693E+10 | 0.170386E+10 | 0.119307E+10 | 0.00 | 0.00 |
July | 0.459747E+10 | 0.239973E+09 | 0.217873E+10 | 0.101702E+10 | 0.116171E+10 | 0.00 | 0.00 |
August | 0.436635E+10 | 0.291227E+09 | 0.207762E+10 | 0.104342E+10 | 0.103420E+10 | 0.00 | 0.00 |
September | 0.350548E+10 | 0.405443E+09 | 0.175257E+10 | 0.736358E+09 | 0.101621E+10 | 0.00 | 0.00 |
October | 0.302246E+10 | 0.125531E+10 | 0.185302E+10 | 0.105955E+10 | 0.793465E+09 | 0.00 | 0.00 |
November | 0.234896E+10 | 0.174950E+10 | 0.165162E+10 | 0.997200E+09 | 0.654420E+09 | 0.00 | 0.00 |
December | 0.181520E+10 | 0.233145E+10 | 0.137551E+10 | 0.783172E+09 | 0.592336E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.417306E+11 | 0.136690E+11 | 0.241008E+11 | 0.130043E+11 | 0.110966E+11 | 0.00 | 0.00 |
Minimum of Months | 0.147881E+10 | 0.239973E+09 | 0.124729E+10 | 0.602987E+09 | 0.592336E+09 | 0.00 | 0.00 |
Maximum of Months | 0.592054E+10 | 0.233145E+10 | 0.289693E+10 | 0.170386E+10 | 0.123698E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.625355E+09 | 0.306081E+10 | 0.756913E+09 | 0.00 | 0.756913E+09 | 0.00 | 0.00 |
February | 0.427181E+09 | 0.265549E+10 | 0.779016E+09 | 0.00 | 0.779016E+09 | 0.00 | 0.00 |
March | 0.116302E+10 | 0.256023E+10 | 0.114624E+10 | 0.00 | 0.114624E+10 | 0.00 | 0.00 |
April | 0.229660E+10 | 0.135710E+10 | 0.135148E+10 | 14024675.69 | 0.133745E+10 | 0.00 | 0.00 |
May | 0.323050E+10 | 0.931156E+09 | 0.163478E+10 | 0.130897E+09 | 0.150388E+10 | 0.00 | 0.00 |
June | 0.477588E+10 | 0.380245E+09 | 0.183843E+10 | 0.334021E+09 | 0.150441E+10 | 0.00 | 0.00 |
July | 0.417974E+10 | 0.315426E+09 | 0.162010E+10 | 0.168780E+09 | 0.145132E+10 | 0.00 | 0.00 |
August | 0.343939E+10 | 0.415199E+09 | 0.130771E+10 | 32486236.32 | 0.127523E+10 | 0.00 | 0.00 |
September | 0.275924E+10 | 0.630101E+09 | 0.119400E+10 | 318738.06 | 0.119369E+10 | 0.00 | 0.00 |
October | 0.137361E+10 | 0.203994E+10 | 0.954568E+09 | 0.00 | 0.954568E+09 | 0.00 | 0.00 |
November | 0.567380E+09 | 0.288446E+10 | 0.769674E+09 | 0.00 | 0.769674E+09 | 0.00 | 0.00 |
December | 0.349341E+09 | 0.384621E+10 | 0.707026E+09 | 0.00 | 0.707026E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.251872E+11 | 0.210764E+11 | 0.140599E+11 | 0.680527E+09 | 0.133794E+11 | 0.00 | 0.00 |
Minimum of Months | 0.349341E+09 | 0.315426E+09 | 0.707026E+09 | 0.00 | 0.707026E+09 | 0.00 | 0.00 |
Maximum of Months | 0.477588E+10 | 0.384621E+10 | 0.183843E+10 | 0.334021E+09 | 0.150441E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.211642E+10 | 0.195695E+10 | 0.163015E+10 | 0.102263E+10 | 0.607514E+09 | 0.00 | 0.00 |
February | 0.168957E+10 | 0.172570E+10 | 0.145133E+10 | 0.830223E+09 | 0.621105E+09 | 0.00 | 0.00 |
March | 0.268591E+10 | 0.165794E+10 | 0.201087E+10 | 0.103440E+10 | 0.976467E+09 | 0.00 | 0.00 |
April | 0.462657E+10 | 0.905165E+09 | 0.277781E+10 | 0.165561E+10 | 0.112221E+10 | 0.00 | 0.00 |
May | 0.528359E+10 | 0.655180E+09 | 0.297478E+10 | 0.176341E+10 | 0.121136E+10 | 0.00 | 0.00 |
June | 0.608885E+10 | 0.265172E+09 | 0.300066E+10 | 0.186456E+10 | 0.113610E+10 | 0.00 | 0.00 |
July | 0.534764E+10 | 0.221031E+09 | 0.261872E+10 | 0.147659E+10 | 0.114214E+10 | 0.00 | 0.00 |
August | 0.503400E+10 | 0.290966E+09 | 0.248540E+10 | 0.141841E+10 | 0.106699E+10 | 0.00 | 0.00 |
September | 0.383544E+10 | 0.417748E+09 | 0.197365E+10 | 0.951330E+09 | 0.102232E+10 | 0.00 | 0.00 |
October | 0.320354E+10 | 0.130071E+10 | 0.204849E+10 | 0.124669E+10 | 0.801799E+09 | 0.00 | 0.00 |
November | 0.193391E+10 | 0.183997E+10 | 0.152436E+10 | 0.915092E+09 | 0.609271E+09 | 0.00 | 0.00 |
December | 0.161555E+10 | 0.243141E+10 | 0.143615E+10 | 0.867186E+09 | 0.568963E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.434610E+11 | 0.136679E+11 | 0.259324E+11 | 0.150461E+11 | 0.108862E+11 | 0.00 | 0.00 |
Minimum of Months | 0.161555E+10 | 0.221031E+09 | 0.143615E+10 | 0.830223E+09 | 0.568963E+09 | 0.00 | 0.00 |
Maximum of Months | 0.608885E+10 | 0.243141E+10 | 0.300066E+10 | 0.186456E+10 | 0.121136E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.953608E+10 | 0.318229E+10 | 0.623235E+10 | 0.497759E+10 | 0.125476E+10 | 0.00 | 0.00 |
February | 0.496537E+10 | 0.263326E+10 | 0.355928E+10 | 0.240049E+10 | 0.115879E+10 | 0.00 | 0.00 |
March | 0.493762E+10 | 0.261463E+10 | 0.327890E+10 | 0.168880E+10 | 0.159010E+10 | 0.00 | 0.00 |
April | 0.514780E+10 | 0.146301E+10 | 0.270118E+10 | 0.109153E+10 | 0.160965E+10 | 0.00 | 0.00 |
May | 0.393299E+10 | 0.102845E+10 | 0.187042E+10 | 0.309010E+09 | 0.156141E+10 | 0.00 | 0.00 |
June | 0.426156E+10 | 0.402948E+09 | 0.154996E+10 | 0.119480E+09 | 0.143048E+10 | 0.00 | 0.00 |
July | 0.427359E+10 | 0.329942E+09 | 0.163657E+10 | 0.169315E+09 | 0.146726E+10 | 0.00 | 0.00 |
August | 0.492344E+10 | 0.445748E+09 | 0.198999E+10 | 0.549928E+09 | 0.144006E+10 | 0.00 | 0.00 |
September | 0.577115E+10 | 0.678448E+09 | 0.277487E+10 | 0.118382E+10 | 0.159105E+10 | 0.00 | 0.00 |
October | 0.763220E+10 | 0.206437E+10 | 0.456884E+10 | 0.316231E+10 | 0.140653E+10 | 0.00 | 0.00 |
November | 0.775850E+10 | 0.288365E+10 | 0.515266E+10 | 0.394666E+10 | 0.120600E+10 | 0.00 | 0.00 |
December | 0.845200E+10 | 0.380080E+10 | 0.579423E+10 | 0.458690E+10 | 0.120733E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.715923E+11 | 0.215275E+11 | 0.411092E+11 | 0.241858E+11 | 0.169234E+11 | 0.00 | 0.00 |
Minimum of Months | 0.393299E+10 | 0.329942E+09 | 0.154996E+10 | 0.119480E+09 | 0.115879E+10 | 0.00 | 0.00 |
Maximum of Months | 0.953608E+10 | 0.380080E+10 | 0.623235E+10 | 0.497759E+10 | 0.160965E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.248352E+10 | 0.215936E+10 | 0.170462E+10 | 0.105944E+10 | 0.645174E+09 | 0.00 | 0.00 |
February | 0.148993E+10 | 0.181396E+10 | 0.124727E+10 | 0.602977E+09 | 0.644294E+09 | 0.00 | 0.00 |
March | 0.252647E+10 | 0.176430E+10 | 0.182905E+10 | 0.871936E+09 | 0.957118E+09 | 0.00 | 0.00 |
April | 0.465334E+10 | 0.102458E+10 | 0.271797E+10 | 0.155041E+10 | 0.116756E+10 | 0.00 | 0.00 |
May | 0.513055E+10 | 0.759411E+09 | 0.281578E+10 | 0.157881E+10 | 0.123698E+10 | 0.00 | 0.00 |
June | 0.596313E+10 | 0.323454E+09 | 0.289689E+10 | 0.170383E+10 | 0.119306E+10 | 0.00 | 0.00 |
July | 0.461937E+10 | 0.253126E+09 | 0.217871E+10 | 0.101701E+10 | 0.116170E+10 | 0.00 | 0.00 |
August | 0.437188E+10 | 0.321819E+09 | 0.207759E+10 | 0.104340E+10 | 0.103419E+10 | 0.00 | 0.00 |
September | 0.349986E+10 | 0.457127E+09 | 0.175254E+10 | 0.736345E+09 | 0.101620E+10 | 0.00 | 0.00 |
October | 0.300578E+10 | 0.141903E+10 | 0.185299E+10 | 0.105953E+10 | 0.793459E+09 | 0.00 | 0.00 |
November | 0.231992E+10 | 0.199891E+10 | 0.165160E+10 | 0.997184E+09 | 0.654414E+09 | 0.00 | 0.00 |
December | 0.177439E+10 | 0.263306E+10 | 0.137549E+10 | 0.783159E+09 | 0.592331E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.418382E+11 | 0.149281E+11 | 0.241005E+11 | 0.130040E+11 | 0.110965E+11 | 0.00 | 0.00 |
Minimum of Months | 0.148993E+10 | 0.253126E+09 | 0.124727E+10 | 0.602977E+09 | 0.592331E+09 | 0.00 | 0.00 |
Maximum of Months | 0.596313E+10 | 0.263306E+10 | 0.289689E+10 | 0.170383E+10 | 0.123698E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.601695E+09 | 0.309202E+10 | 0.756926E+09 | 0.00 | 0.756926E+09 | 0.00 | 0.00 |
February | 0.387280E+09 | 0.274317E+10 | 0.779031E+09 | 0.00 | 0.779031E+09 | 0.00 | 0.00 |
March | 0.108239E+10 | 0.268926E+10 | 0.114626E+10 | 0.00 | 0.114626E+10 | 0.00 | 0.00 |
April | 0.224292E+10 | 0.142377E+10 | 0.135150E+10 | 14025087.93 | 0.133747E+10 | 0.00 | 0.00 |
May | 0.317037E+10 | 0.988936E+09 | 0.163481E+10 | 0.130900E+09 | 0.150391E+10 | 0.00 | 0.00 |
June | 0.474221E+10 | 0.409506E+09 | 0.183847E+10 | 0.334031E+09 | 0.150444E+10 | 0.00 | 0.00 |
July | 0.417916E+10 | 0.320211E+09 | 0.162013E+10 | 0.168785E+09 | 0.145134E+10 | 0.00 | 0.00 |
August | 0.345800E+10 | 0.406371E+09 | 0.130774E+10 | 32487191.21 | 0.127525E+10 | 0.00 | 0.00 |
September | 0.279172E+10 | 0.598653E+09 | 0.119403E+10 | 318747.42 | 0.119371E+10 | 0.00 | 0.00 |
October | 0.139784E+10 | 0.196039E+10 | 0.954585E+09 | 0.00 | 0.954585E+09 | 0.00 | 0.00 |
November | 0.586222E+09 | 0.277288E+10 | 0.769689E+09 | 0.00 | 0.769689E+09 | 0.00 | 0.00 |
December | 0.365392E+09 | 0.374172E+10 | 0.707039E+09 | 0.00 | 0.707039E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.250052E+11 | 0.211469E+11 | 0.140602E+11 | 0.680547E+09 | 0.133796E+11 | 0.00 | 0.00 |
Minimum of Months | 0.365392E+09 | 0.320211E+09 | 0.707039E+09 | 0.00 | 0.707039E+09 | 0.00 | 0.00 |
Maximum of Months | 0.474221E+10 | 0.374172E+10 | 0.183847E+10 | 0.334031E+09 | 0.150444E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.209295E+10 | 0.192159E+10 | 0.163017E+10 | 0.102265E+10 | 0.607520E+09 | 0.00 | 0.00 |
February | 0.165375E+10 | 0.173353E+10 | 0.145135E+10 | 0.830239E+09 | 0.621112E+09 | 0.00 | 0.00 |
March | 0.262536E+10 | 0.168443E+10 | 0.201090E+10 | 0.103442E+10 | 0.976479E+09 | 0.00 | 0.00 |
April | 0.458224E+10 | 0.905949E+09 | 0.277786E+10 | 0.165564E+10 | 0.112222E+10 | 0.00 | 0.00 |
May | 0.523868E+10 | 0.661302E+09 | 0.297482E+10 | 0.176345E+10 | 0.121137E+10 | 0.00 | 0.00 |
June | 0.605930E+10 | 0.266794E+09 | 0.300071E+10 | 0.186460E+10 | 0.113611E+10 | 0.00 | 0.00 |
July | 0.534100E+10 | 0.208865E+09 | 0.261876E+10 | 0.147661E+10 | 0.114215E+10 | 0.00 | 0.00 |
August | 0.503502E+10 | 0.265279E+09 | 0.248543E+10 | 0.141844E+10 | 0.106700E+10 | 0.00 | 0.00 |
September | 0.384446E+10 | 0.379418E+09 | 0.197368E+10 | 0.951348E+09 | 0.102233E+10 | 0.00 | 0.00 |
October | 0.320563E+10 | 0.122176E+10 | 0.204853E+10 | 0.124672E+10 | 0.801807E+09 | 0.00 | 0.00 |
November | 0.193776E+10 | 0.174091E+10 | 0.152439E+10 | 0.915110E+09 | 0.609278E+09 | 0.00 | 0.00 |
December | 0.162297E+10 | 0.232323E+10 | 0.143617E+10 | 0.867202E+09 | 0.568969E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.432391E+11 | 0.133131E+11 | 0.259328E+11 | 0.150464E+11 | 0.108863E+11 | 0.00 | 0.00 |
Minimum of Months | 0.162297E+10 | 0.208865E+09 | 0.143617E+10 | 0.830239E+09 | 0.568969E+09 | 0.00 | 0.00 |
Maximum of Months | 0.605930E+10 | 0.232323E+10 | 0.300071E+10 | 0.186460E+10 | 0.121137E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.949352E+10 | 0.302199E+10 | 0.623260E+10 | 0.497780E+10 | 0.125480E+10 | 0.00 | 0.00 |
February | 0.487400E+10 | 0.263926E+10 | 0.355942E+10 | 0.240059E+10 | 0.115882E+10 | 0.00 | 0.00 |
March | 0.482705E+10 | 0.267698E+10 | 0.327902E+10 | 0.168887E+10 | 0.159015E+10 | 0.00 | 0.00 |
April | 0.509768E+10 | 0.149326E+10 | 0.270126E+10 | 0.109157E+10 | 0.160969E+10 | 0.00 | 0.00 |
May | 0.388951E+10 | 0.108237E+10 | 0.187047E+10 | 0.309023E+09 | 0.156144E+10 | 0.00 | 0.00 |
June | 0.426841E+10 | 0.428908E+09 | 0.154999E+10 | 0.119485E+09 | 0.143051E+10 | 0.00 | 0.00 |
July | 0.430669E+10 | 0.326081E+09 | 0.163662E+10 | 0.169322E+09 | 0.146730E+10 | 0.00 | 0.00 |
August | 0.498501E+10 | 0.411448E+09 | 0.199005E+10 | 0.549951E+09 | 0.144010E+10 | 0.00 | 0.00 |
September | 0.583635E+10 | 0.604755E+09 | 0.277497E+10 | 0.118387E+10 | 0.159110E+10 | 0.00 | 0.00 |
October | 0.764806E+10 | 0.191596E+10 | 0.456901E+10 | 0.316244E+10 | 0.140657E+10 | 0.00 | 0.00 |
November | 0.774454E+10 | 0.268990E+10 | 0.515286E+10 | 0.394683E+10 | 0.120603E+10 | 0.00 | 0.00 |
December | 0.842226E+10 | 0.358877E+10 | 0.579446E+10 | 0.458709E+10 | 0.120737E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.713931E+11 | 0.208797E+11 | 0.411107E+11 | 0.241868E+11 | 0.169239E+11 | 0.00 | 0.00 |
Minimum of Months | 0.388951E+10 | 0.326081E+09 | 0.154999E+10 | 0.119485E+09 | 0.115882E+10 | 0.00 | 0.00 |
Maximum of Months | 0.949352E+10 | 0.358877E+10 | 0.623260E+10 | 0.497780E+10 | 0.160969E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.246900E+10 | 0.211385E+10 | 0.170464E+10 | 0.105946E+10 | 0.645179E+09 | 0.00 | 0.00 |
February | 0.145988E+10 | 0.182958E+10 | 0.124729E+10 | 0.602987E+09 | 0.644300E+09 | 0.00 | 0.00 |
March | 0.247418E+10 | 0.179711E+10 | 0.182908E+10 | 0.871951E+09 | 0.957127E+09 | 0.00 | 0.00 |
April | 0.461897E+10 | 0.102205E+10 | 0.271801E+10 | 0.155043E+10 | 0.116757E+10 | 0.00 | 0.00 |
May | 0.509770E+10 | 0.762212E+09 | 0.281582E+10 | 0.157883E+10 | 0.123698E+10 | 0.00 | 0.00 |
June | 0.594677E+10 | 0.322141E+09 | 0.289693E+10 | 0.170386E+10 | 0.119307E+10 | 0.00 | 0.00 |
July | 0.462351E+10 | 0.241661E+09 | 0.217873E+10 | 0.101702E+10 | 0.116171E+10 | 0.00 | 0.00 |
August | 0.438652E+10 | 0.298293E+09 | 0.207762E+10 | 0.104342E+10 | 0.103420E+10 | 0.00 | 0.00 |
September | 0.351896E+10 | 0.418132E+09 | 0.175257E+10 | 0.736358E+09 | 0.101621E+10 | 0.00 | 0.00 |
October | 0.301621E+10 | 0.133472E+10 | 0.185302E+10 | 0.105955E+10 | 0.793465E+09 | 0.00 | 0.00 |
November | 0.232692E+10 | 0.188330E+10 | 0.165162E+10 | 0.997200E+09 | 0.654420E+09 | 0.00 | 0.00 |
December | 0.178189E+10 | 0.251501E+10 | 0.137551E+10 | 0.783172E+09 | 0.592336E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.417205E+11 | 0.145381E+11 | 0.241008E+11 | 0.130043E+11 | 0.110966E+11 | 0.00 | 0.00 |
Minimum of Months | 0.145988E+10 | 0.241661E+09 | 0.124729E+10 | 0.602987E+09 | 0.592336E+09 | 0.00 | 0.00 |
Maximum of Months | 0.594677E+10 | 0.251501E+10 | 0.289693E+10 | 0.170386E+10 | 0.123698E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.450367E+10 | -0.380903E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -694641334.8 | 58.98 | 0.00 | 0.00 |
February | 0.405607E+10 | -0.342749E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -628575530.0 | 58.98 | 0.00 | 0.00 |
March | 0.455155E+10 | -0.385828E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -693271000.7 | 58.98 | 0.00 | 0.00 |
April | 0.386282E+10 | -0.319583E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666988823.8 | 58.99 | 0.00 | 0.00 |
May | 0.379826E+10 | -0.311015E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688112829.2 | 58.98 | 0.00 | 0.00 |
June | 0.349094E+10 | -0.282455E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666392311.9 | 58.98 | 0.00 | 0.00 |
July | 0.322772E+10 | -0.254014E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687574698.5 | 58.98 | 0.00 | 0.00 |
August | 0.354020E+10 | -0.285161E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688581534.2 | 58.98 | 0.00 | 0.00 |
September | 0.341748E+10 | -0.275368E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -663803578.9 | 58.98 | 0.00 | 0.00 |
October | 0.381825E+10 | -0.313100E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687244395.0 | 58.98 | 0.00 | 0.00 |
November | 0.404936E+10 | -0.338153E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667827866.1 | 58.98 | 0.00 | 0.00 |
December | 0.428130E+10 | -0.358632E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -694981828.2 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.465976E+11 | -0.384696E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.812800E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.322772E+10 | -0.385828E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -694981828.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.455155E+10 | -0.254014E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -628575530.0 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.50 | 0.48 | 01-JAN-07:49 | 9182.04 | 38.84 | 306.33 | 291.50 | 2427.03 | 28.40 | 169.50 | 288.00 |
February | 241.00 | 0.50 | 0.48 | 01-FEB-07:49 | 8250.77 | 36.26 | 234.17 | 264.83 | 1334.24 | 22.66 | 120.33 | 222.67 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-07:30 | 1568.35 | 17.87 | 2.33 | 327.67 | 931.86 | 20.08 | 120.83 | 286.83 |
April | 380.33 | 0.52 | 0.48 | 01-APR-07:49 | 1202.35 | 17.59 | 0.00 | 331.50 | 765.58 | 19.76 | 61.67 | 301.67 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-07:19 | 945.51 | 17.35 | 0.00 | 356.50 | 600.34 | 19.59 | 13.50 | 315.00 |
June | 418.17 | 0.52 | 0.48 | 01-JUN-06:00 | 781.80 | 16.60 | 0.00 | 361.17 | 509.73 | 18.89 | 0.83 | 308.33 |
July | 399.50 | 0.52 | 0.48 | 01-JUL-07:19 | 910.72 | 17.01 | 0.00 | 360.67 | 554.79 | 19.25 | 18.17 | 291.67 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:30 | 1050.17 | 17.36 | 0.00 | 335.50 | 647.12 | 19.56 | 33.17 | 286.33 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:00 | 1515.99 | 18.31 | 11.00 | 318.17 | 862.89 | 20.06 | 102.83 | 285.67 |
October | 348.00 | 0.51 | 0.48 | 01-OCT-07:10 | 3166.43 | 23.97 | 140.17 | 318.00 | 1150.91 | 20.00 | 86.83 | 300.17 |
November | 288.50 | 0.49 | 0.48 | 01-NOV-07:40 | 8686.22 | 37.47 | 282.00 | 285.17 | 1664.03 | 25.01 | 132.33 | 267.33 |
December | 290.67 | 0.49 | 0.48 | 01-DEC-07:40 | 8483.73 | 38.32 | 284.17 | 279.67 | 2263.84 | 28.07 | 164.33 | 274.50 |
Annual Sum or Average | 4135.50 | 0.51 | 3358.07 | 23.54 | 1260.17 | 3830.33 | 1072.98 | 21.43 | 1024.33 | 3428.17 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 781.80 | 16.60 | 0.00 | 264.83 | 509.73 | 18.89 | 0.83 | 222.67 | |
Maximum of Months | 418.17 | 0.52 | 0.48 | 9182.04 | 38.84 | 306.33 | 361.17 | 2427.03 | 28.40 | 169.50 | 315.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.52 | 0.48 | 01-JAN-07:49 | 2068.02 | 20.46 | 87.17 | 266.33 | 1192.61 | 23.02 | 77.17 | 221.17 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2606.48 | 23.03 | 85.83 | 253.33 | 1457.01 | 23.45 | 63.00 | 183.50 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-07:19 | 2130.83 | 19.72 | 86.17 | 312.00 | 1154.39 | 21.89 | 69.67 | 276.83 |
April | 380.33 | 0.50 | 0.48 | 01-APR-06:40 | 3049.97 | 21.29 | 112.33 | 345.33 | 1717.43 | 22.20 | 82.33 | 320.83 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-05:00 | 3410.84 | 21.05 | 118.50 | 377.00 | 1387.99 | 21.67 | 72.33 | 350.83 |
June | 418.17 | 0.50 | 0.48 | 01-JUN-05:49 | 3479.78 | 21.75 | 134.33 | 385.67 | 1371.67 | 21.12 | 74.83 | 346.17 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:49 | 2994.99 | 20.64 | 115.33 | 379.00 | 1237.24 | 21.11 | 68.33 | 318.33 |
August | 361.83 | 0.50 | 0.48 | 01-AUG-06:10 | 2965.63 | 21.55 | 114.50 | 350.17 | 1648.48 | 22.36 | 83.50 | 304.83 |
September | 350.17 | 0.51 | 0.48 | 01-SEP-06:30 | 2333.22 | 21.08 | 102.00 | 316.00 | 1259.56 | 22.15 | 75.17 | 274.67 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-06:49 | 2206.61 | 19.42 | 87.83 | 288.33 | 1229.53 | 21.57 | 72.33 | 249.50 |
November | 288.50 | 0.51 | 0.48 | 01-NOV-07:30 | 1837.63 | 20.90 | 80.17 | 267.00 | 974.45 | 21.51 | 52.83 | 201.33 |
December | 290.67 | 0.51 | 0.48 | 01-DEC-07:30 | 2131.32 | 22.82 | 101.67 | 253.67 | 1191.24 | 23.52 | 77.17 | 199.83 |
Annual Sum or Average | 4135.50 | 0.51 | 2659.18 | 21.09 | 1225.83 | 3793.83 | 1327.91 | 22.04 | 868.67 | 3247.83 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 1837.63 | 19.42 | 80.17 | 253.33 | 974.45 | 21.11 | 52.83 | 183.50 | |
Maximum of Months | 418.17 | 0.52 | 0.48 | 3479.78 | 23.03 | 134.33 | 385.67 | 1717.43 | 23.52 | 83.50 | 350.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.56 | 0.48 | 01-JAN-09:39 | 449.38 | 13.83 | 0.00 | 219.67 | 312.15 | 16.57 | 0.00 | 118.00 |
February | 241.00 | 0.54 | 0.48 | 01-FEB-09:00 | 554.59 | 14.85 | 0.00 | 221.83 | 358.84 | 17.27 | 0.00 | 125.17 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:00 | 636.27 | 16.14 | 0.00 | 298.33 | 399.41 | 18.35 | 0.00 | 224.83 |
April | 380.33 | 0.51 | 0.48 | 01-APR-07:00 | 749.09 | 17.41 | 0.00 | 335.17 | 494.78 | 19.58 | 5.33 | 302.50 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-06:10 | 886.38 | 18.16 | 2.67 | 388.50 | 585.62 | 20.38 | 52.00 | 373.00 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:49 | 1032.49 | 21.16 | 81.50 | 399.17 | 635.03 | 23.29 | 124.17 | 395.00 |
July | 399.50 | 0.49 | 0.48 | 01-JUL-05:49 | 914.17 | 20.47 | 62.50 | 394.00 | 584.08 | 22.58 | 108.33 | 359.67 |
August | 361.83 | 0.50 | 0.48 | 01-AUG-07:10 | 759.84 | 17.45 | 0.00 | 347.17 | 484.90 | 19.63 | 7.33 | 293.33 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:00 | 723.88 | 16.74 | 0.00 | 313.33 | 445.61 | 18.88 | 1.00 | 253.17 |
October | 348.00 | 0.55 | 0.48 | 01-OCT-07:49 | 519.38 | 14.77 | 0.00 | 255.83 | 348.49 | 17.21 | 0.00 | 172.00 |
November | 288.50 | 0.54 | 0.48 | 01-NOV-08:20 | 488.72 | 14.54 | 0.00 | 230.00 | 326.82 | 17.18 | 0.00 | 120.00 |
December | 290.67 | 0.55 | 0.48 | 01-DEC-08:00 | 453.34 | 13.99 | 0.00 | 205.17 | 307.22 | 16.74 | 0.00 | 94.00 |
Annual Sum or Average | 4135.50 | 0.52 | 704.42 | 16.92 | 146.67 | 3608.17 | 454.66 | 19.24 | 298.17 | 2830.67 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 449.38 | 13.83 | 0.00 | 205.17 | 307.22 | 16.57 | 0.00 | 94.00 | |
Maximum of Months | 418.17 | 0.56 | 0.48 | 1032.49 | 21.16 | 81.50 | 399.17 | 635.03 | 23.29 | 124.17 | 395.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.53 | 0.48 | 01-JAN-09:39 | 2321.64 | 21.96 | 105.67 | 243.33 | 1302.70 | 22.36 | 76.33 | 204.83 |
February | 241.00 | 0.53 | 0.48 | 01-FEB-09:00 | 2348.93 | 21.19 | 81.17 | 234.50 | 919.77 | 20.09 | 36.50 | 173.17 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-08:20 | 1936.79 | 19.04 | 79.00 | 310.00 | 1083.28 | 21.52 | 65.33 | 272.33 |
April | 380.33 | 0.51 | 0.48 | 01-APR-08:09 | 2840.61 | 18.93 | 85.00 | 332.33 | 1585.90 | 20.25 | 55.00 | 304.00 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-07:30 | 3052.44 | 16.65 | 54.50 | 361.17 | 1688.78 | 17.19 | 0.00 | 330.17 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-07:10 | 3069.80 | 12.96 | 0.00 | 367.67 | 1255.20 | 16.77 | 0.00 | 338.17 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-07:30 | 2293.01 | 13.85 | 3.67 | 367.67 | 1041.38 | 17.21 | 0.00 | 318.67 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:40 | 2370.25 | 16.48 | 49.17 | 340.33 | 1304.97 | 17.33 | 5.00 | 292.67 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-07:19 | 1864.32 | 19.16 | 81.83 | 315.67 | 1023.49 | 20.37 | 53.83 | 278.50 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-07:00 | 2296.65 | 21.03 | 109.33 | 282.83 | 1264.01 | 21.98 | 81.17 | 247.50 |
November | 288.50 | 0.52 | 0.48 | 01-NOV-08:30 | 2094.57 | 20.23 | 80.83 | 248.33 | 1171.74 | 21.96 | 62.50 | 203.50 |
December | 290.67 | 0.53 | 0.48 | 01-DEC-08:00 | 1769.71 | 20.15 | 80.67 | 233.33 | 940.92 | 20.84 | 53.17 | 192.67 |
Annual Sum or Average | 4135.50 | 0.52 | 2391.84 | 18.14 | 810.83 | 3637.17 | 1234.49 | 19.62 | 488.83 | 3156.17 | ||
Minimum of Months | 241.00 | 0.51 | 0.48 | 1769.71 | 12.96 | 0.00 | 233.33 | 919.77 | 16.77 | 0.00 | 173.17 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 3069.80 | 21.96 | 109.33 | 367.67 | 1688.78 | 22.36 | 81.17 | 338.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.50 | 0.48 | 01-JAN-07:49 | 9023.50 | 38.63 | 306.33 | 291.00 | 2290.31 | 26.30 | 145.50 | 286.50 |
February | 241.00 | 0.50 | 0.48 | 01-FEB-07:49 | 8125.05 | 36.02 | 234.17 | 264.17 | 1234.44 | 20.01 | 40.67 | 219.33 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-07:30 | 1484.99 | 14.04 | 2.33 | 326.17 | 869.00 | 17.65 | 1.83 | 283.17 |
April | 380.33 | 0.52 | 0.48 | 01-APR-07:49 | 1144.95 | 14.15 | 0.00 | 328.67 | 724.90 | 17.75 | 0.00 | 298.83 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-07:19 | 909.85 | 13.97 | 0.00 | 354.00 | 578.89 | 17.57 | 0.00 | 311.83 |
June | 418.17 | 0.52 | 0.48 | 01-JUN-07:10 | 755.53 | 13.23 | 0.00 | 357.33 | 495.44 | 16.88 | 0.00 | 301.83 |
July | 399.50 | 0.52 | 0.48 | 01-JUL-07:30 | 877.20 | 13.51 | 0.00 | 357.67 | 535.05 | 17.09 | 0.00 | 286.50 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-07:40 | 1005.51 | 13.82 | 0.00 | 333.17 | 617.54 | 17.42 | 0.00 | 281.33 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:00 | 1443.60 | 14.67 | 10.83 | 316.17 | 810.64 | 17.67 | 0.00 | 282.33 |
October | 348.00 | 0.51 | 0.48 | 01-OCT-07:10 | 3058.18 | 21.29 | 139.83 | 316.33 | 1062.50 | 17.39 | 13.17 | 297.33 |
November | 288.50 | 0.49 | 0.48 | 01-NOV-07:40 | 8543.42 | 37.19 | 281.83 | 284.50 | 1544.46 | 22.51 | 89.17 | 266.17 |
December | 290.67 | 0.49 | 0.48 | 01-DEC-07:40 | 8312.85 | 37.81 | 282.17 | 279.17 | 2127.04 | 25.85 | 130.67 | 273.67 |
Annual Sum or Average | 4135.50 | 0.51 | 3276.15 | 20.96 | 1257.50 | 3808.33 | 1010.10 | 19.18 | 421.00 | 3388.83 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 755.53 | 13.23 | 0.00 | 264.17 | 495.44 | 16.88 | 0.00 | 219.33 | |
Maximum of Months | 418.17 | 0.52 | 0.48 | 9023.50 | 38.63 | 306.33 | 357.67 | 2290.31 | 26.30 | 145.50 | 311.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.52 | 0.48 | 01-JAN-07:00 | 2014.93 | 19.97 | 87.17 | 262.83 | 1147.70 | 22.81 | 75.17 | 217.17 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2544.50 | 22.58 | 85.83 | 251.50 | 1407.54 | 23.26 | 63.00 | 178.67 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:19 | 2069.98 | 19.23 | 86.17 | 308.83 | 1101.52 | 21.70 | 69.83 | 273.00 |
April | 380.33 | 0.51 | 0.48 | 01-APR-06:40 | 2971.51 | 20.84 | 112.33 | 344.33 | 1656.42 | 22.03 | 82.33 | 317.50 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-05:00 | 3326.02 | 20.52 | 117.83 | 376.17 | 1324.02 | 21.51 | 72.33 | 347.67 |
June | 418.17 | 0.50 | 0.48 | 01-JUN-05:49 | 3335.28 | 19.69 | 115.00 | 384.33 | 1310.56 | 20.96 | 74.83 | 340.83 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:49 | 2924.80 | 20.18 | 115.33 | 376.33 | 1179.42 | 20.96 | 68.33 | 313.67 |
August | 361.83 | 0.50 | 0.48 | 01-AUG-06:10 | 2887.64 | 21.09 | 114.50 | 347.83 | 1590.55 | 22.19 | 83.50 | 300.00 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:30 | 2273.16 | 20.62 | 102.00 | 314.00 | 1210.00 | 21.97 | 75.17 | 271.00 |
October | 348.00 | 0.53 | 0.48 | 01-OCT-06:00 | 2145.25 | 18.93 | 87.83 | 284.83 | 1178.68 | 21.38 | 72.17 | 247.83 |
November | 288.50 | 0.51 | 0.48 | 01-NOV-07:30 | 1756.86 | 19.91 | 76.33 | 261.83 | 932.90 | 21.29 | 52.83 | 197.17 |
December | 290.67 | 0.51 | 0.48 | 01-DEC-07:40 | 1987.52 | 20.37 | 85.33 | 247.67 | 1150.25 | 23.30 | 74.33 | 196.67 |
Annual Sum or Average | 4135.50 | 0.51 | 2576.83 | 20.28 | 1185.67 | 3760.50 | 1274.33 | 21.86 | 863.83 | 3201.17 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 1756.86 | 18.93 | 76.33 | 247.67 | 932.90 | 20.96 | 52.83 | 178.67 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 3335.28 | 22.58 | 117.83 | 384.33 | 1656.42 | 23.30 | 83.50 | 347.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.56 | 0.48 | 01-JAN-09:50 | 433.21 | 10.36 | 0.00 | 211.67 | 304.37 | 14.29 | 0.00 | 109.17 |
February | 241.00 | 0.55 | 0.48 | 01-FEB-10:09 | 535.62 | 11.41 | 0.00 | 218.67 | 349.19 | 15.10 | 0.00 | 119.67 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-08:09 | 614.82 | 12.77 | 0.00 | 295.50 | 388.19 | 16.35 | 0.00 | 217.50 |
April | 380.33 | 0.51 | 0.48 | 01-APR-07:00 | 724.20 | 14.28 | 0.00 | 333.67 | 482.43 | 17.91 | 0.00 | 298.83 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-06:10 | 856.46 | 14.77 | 2.67 | 386.17 | 569.48 | 18.47 | 4.00 | 370.83 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:49 | 1000.39 | 18.27 | 81.33 | 398.83 | 616.37 | 21.53 | 82.33 | 394.33 |
July | 399.50 | 0.49 | 0.48 | 01-JUL-05:00 | 881.75 | 17.45 | 62.50 | 393.00 | 565.56 | 20.73 | 62.83 | 355.83 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:19 | 734.42 | 14.05 | 0.00 | 344.17 | 471.74 | 17.72 | 0.00 | 286.17 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:00 | 698.83 | 13.39 | 0.00 | 310.17 | 432.23 | 16.89 | 0.00 | 246.83 |
October | 348.00 | 0.55 | 0.48 | 01-OCT-07:49 | 502.21 | 11.39 | 0.00 | 250.33 | 340.10 | 15.16 | 0.00 | 165.50 |
November | 288.50 | 0.54 | 0.48 | 01-NOV-08:30 | 471.59 | 10.96 | 0.00 | 222.00 | 318.33 | 14.89 | 0.00 | 110.33 |
December | 290.67 | 0.55 | 0.48 | 01-DEC-09:09 | 436.77 | 10.39 | 0.00 | 199.00 | 299.04 | 14.36 | 0.00 | 85.33 |
Annual Sum or Average | 4135.50 | 0.52 | 680.58 | 13.61 | 146.50 | 3563.17 | 442.04 | 17.24 | 149.17 | 2760.33 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 433.21 | 10.36 | 0.00 | 199.00 | 299.04 | 14.29 | 0.00 | 85.33 | |
Maximum of Months | 418.17 | 0.56 | 0.48 | 1000.39 | 18.27 | 81.33 | 398.83 | 616.37 | 21.53 | 82.33 | 394.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.54 | 0.48 | 01-JAN-09:39 | 2144.52 | 19.49 | 86.50 | 238.83 | 1255.14 | 22.25 | 76.00 | 201.33 |
February | 241.00 | 0.53 | 0.48 | 01-FEB-09:00 | 2291.87 | 20.80 | 81.17 | 232.50 | 877.40 | 19.96 | 36.67 | 171.33 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-08:30 | 1880.27 | 18.59 | 79.00 | 308.17 | 1036.31 | 21.39 | 65.33 | 269.17 |
April | 380.33 | 0.51 | 0.48 | 01-APR-08:20 | 2761.19 | 18.46 | 85.00 | 329.83 | 1523.46 | 20.08 | 55.00 | 301.83 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-07:30 | 2970.65 | 16.15 | 54.50 | 359.50 | 1628.73 | 17.01 | 0.00 | 327.67 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-07:19 | 2999.49 | 12.42 | 0.00 | 364.83 | 1195.28 | 16.59 | 0.00 | 335.67 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-07:30 | 2232.72 | 13.30 | 3.67 | 364.83 | 995.23 | 17.01 | 0.00 | 314.83 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:49 | 2302.79 | 15.96 | 49.17 | 337.33 | 1257.23 | 17.14 | 5.00 | 289.33 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-07:30 | 1810.84 | 18.72 | 81.83 | 312.83 | 979.88 | 20.23 | 53.83 | 274.83 |
October | 348.00 | 0.53 | 0.48 | 01-OCT-07:00 | 2240.66 | 20.62 | 109.33 | 280.67 | 1218.38 | 21.86 | 81.17 | 245.67 |
November | 288.50 | 0.53 | 0.48 | 01-NOV-08:30 | 2032.91 | 19.80 | 80.83 | 245.17 | 1122.10 | 21.85 | 62.17 | 201.00 |
December | 290.67 | 0.53 | 0.48 | 01-DEC-08:00 | 1718.29 | 19.75 | 80.67 | 230.83 | 889.14 | 20.50 | 50.50 | 189.50 |
Annual Sum or Average | 4135.50 | 0.52 | 2319.27 | 17.52 | 791.67 | 3605.33 | 1183.62 | 19.45 | 485.67 | 3122.17 | ||
Minimum of Months | 241.00 | 0.51 | 0.48 | 1718.29 | 12.42 | 0.00 | 230.83 | 877.40 | 16.59 | 0.00 | 171.33 | |
Maximum of Months | 418.17 | 0.54 | 0.48 | 2999.49 | 20.80 | 109.33 | 364.83 | 1628.73 | 22.25 | 81.17 | 335.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.50 | 0.48 | 01-JAN-07:49 | 9023.49 | 38.63 | 306.33 | 291.00 | 2290.25 | 26.30 | 145.50 | 286.50 |
February | 241.00 | 0.50 | 0.48 | 01-FEB-07:49 | 8124.99 | 36.02 | 234.17 | 264.17 | 1234.37 | 20.02 | 40.67 | 219.33 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-07:30 | 1484.91 | 14.04 | 2.33 | 326.17 | 868.94 | 17.65 | 1.83 | 283.17 |
April | 380.33 | 0.52 | 0.48 | 01-APR-07:49 | 1144.91 | 14.16 | 0.00 | 328.67 | 724.86 | 17.75 | 0.00 | 298.83 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-07:19 | 909.82 | 13.97 | 0.00 | 354.00 | 578.86 | 17.57 | 0.00 | 311.83 |
June | 418.17 | 0.52 | 0.48 | 01-JUN-07:10 | 755.51 | 13.23 | 0.00 | 357.33 | 495.42 | 16.88 | 0.00 | 301.83 |
July | 399.50 | 0.52 | 0.48 | 01-JUL-07:30 | 877.16 | 13.51 | 0.00 | 357.67 | 535.02 | 17.09 | 0.00 | 286.50 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-07:40 | 1005.47 | 13.82 | 0.00 | 333.17 | 617.51 | 17.42 | 0.00 | 281.33 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:00 | 1443.52 | 14.67 | 10.83 | 316.17 | 810.58 | 17.67 | 0.00 | 282.33 |
October | 348.00 | 0.51 | 0.48 | 01-OCT-07:10 | 3058.12 | 21.29 | 139.83 | 316.33 | 1062.45 | 17.39 | 13.17 | 297.33 |
November | 288.50 | 0.49 | 0.48 | 01-NOV-07:40 | 8543.39 | 37.19 | 281.83 | 284.50 | 1544.40 | 22.51 | 89.17 | 266.17 |
December | 290.67 | 0.49 | 0.48 | 01-DEC-07:40 | 8312.85 | 37.81 | 282.17 | 279.17 | 2126.97 | 25.85 | 130.67 | 273.67 |
Annual Sum or Average | 4135.50 | 0.51 | 3276.11 | 20.96 | 1257.50 | 3808.33 | 1010.05 | 19.18 | 421.00 | 3388.83 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 755.51 | 13.23 | 0.00 | 264.17 | 495.42 | 16.88 | 0.00 | 219.33 | |
Maximum of Months | 418.17 | 0.52 | 0.48 | 9023.49 | 38.63 | 306.33 | 357.67 | 2290.25 | 26.30 | 145.50 | 311.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.52 | 0.48 | 01-JAN-07:00 | 2014.93 | 19.98 | 87.17 | 262.83 | 1147.68 | 22.81 | 75.17 | 217.17 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2544.48 | 22.58 | 85.83 | 251.50 | 1407.50 | 23.26 | 63.00 | 178.67 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:19 | 2069.95 | 19.23 | 86.17 | 308.83 | 1101.48 | 21.70 | 69.83 | 272.83 |
April | 380.33 | 0.51 | 0.48 | 01-APR-06:40 | 2971.50 | 20.84 | 112.33 | 344.33 | 1656.37 | 22.03 | 82.33 | 317.50 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-05:00 | 3326.00 | 20.53 | 117.83 | 376.17 | 1323.98 | 21.51 | 72.33 | 347.67 |
June | 418.17 | 0.50 | 0.48 | 01-JUN-05:49 | 3335.27 | 19.70 | 115.00 | 384.33 | 1310.53 | 20.97 | 74.83 | 340.83 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:49 | 2924.77 | 20.18 | 115.33 | 376.33 | 1179.38 | 20.96 | 68.33 | 313.67 |
August | 361.83 | 0.50 | 0.48 | 01-AUG-06:10 | 2887.62 | 21.10 | 114.50 | 347.83 | 1590.50 | 22.20 | 83.50 | 300.00 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:30 | 2273.12 | 20.62 | 102.00 | 314.00 | 1209.95 | 21.97 | 75.17 | 271.00 |
October | 348.00 | 0.53 | 0.48 | 01-OCT-06:00 | 2145.23 | 18.93 | 87.83 | 284.83 | 1178.65 | 21.38 | 72.17 | 247.83 |
November | 288.50 | 0.51 | 0.48 | 01-NOV-07:30 | 1756.85 | 19.91 | 76.33 | 261.83 | 932.87 | 21.30 | 52.83 | 197.17 |
December | 290.67 | 0.51 | 0.48 | 01-DEC-07:40 | 1987.52 | 20.37 | 85.33 | 247.67 | 1150.22 | 23.30 | 74.33 | 196.67 |
Annual Sum or Average | 4135.50 | 0.51 | 2576.81 | 20.28 | 1185.67 | 3760.50 | 1274.29 | 21.86 | 863.83 | 3201.00 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 1756.85 | 18.93 | 76.33 | 247.67 | 932.87 | 20.96 | 52.83 | 178.67 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 3335.27 | 22.58 | 117.83 | 384.33 | 1656.37 | 23.30 | 83.50 | 347.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.56 | 0.48 | 01-JAN-09:50 | 433.21 | 10.37 | 0.00 | 211.67 | 304.36 | 14.30 | 0.00 | 109.17 |
February | 241.00 | 0.55 | 0.48 | 01-FEB-10:09 | 535.61 | 11.41 | 0.00 | 218.67 | 349.17 | 15.10 | 0.00 | 119.67 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-08:09 | 614.80 | 12.77 | 0.00 | 295.50 | 388.17 | 16.35 | 0.00 | 217.50 |
April | 380.33 | 0.51 | 0.48 | 01-APR-07:00 | 724.19 | 14.28 | 0.00 | 333.67 | 482.40 | 17.91 | 0.00 | 298.83 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-06:10 | 856.45 | 14.77 | 2.67 | 386.17 | 569.45 | 18.47 | 4.17 | 370.83 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:49 | 1000.38 | 18.27 | 81.33 | 398.83 | 616.34 | 21.53 | 82.33 | 394.33 |
July | 399.50 | 0.49 | 0.48 | 01-JUL-05:00 | 881.73 | 17.46 | 62.50 | 393.00 | 565.53 | 20.73 | 62.83 | 355.83 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:19 | 734.41 | 14.05 | 0.00 | 344.17 | 471.72 | 17.72 | 0.00 | 286.17 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:00 | 698.81 | 13.39 | 0.00 | 310.17 | 432.20 | 16.89 | 0.00 | 246.83 |
October | 348.00 | 0.55 | 0.48 | 01-OCT-07:49 | 502.21 | 11.39 | 0.00 | 250.33 | 340.09 | 15.16 | 0.00 | 165.50 |
November | 288.50 | 0.54 | 0.48 | 01-NOV-08:30 | 471.59 | 10.96 | 0.00 | 222.00 | 318.32 | 14.89 | 0.00 | 110.33 |
December | 290.67 | 0.55 | 0.48 | 01-DEC-09:09 | 436.77 | 10.39 | 0.00 | 199.00 | 299.02 | 14.36 | 0.00 | 85.33 |
Annual Sum or Average | 4135.50 | 0.52 | 680.57 | 13.61 | 146.50 | 3563.17 | 442.02 | 17.24 | 149.33 | 2760.33 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 433.21 | 10.37 | 0.00 | 199.00 | 299.02 | 14.30 | 0.00 | 85.33 | |
Maximum of Months | 418.17 | 0.56 | 0.48 | 1000.38 | 18.27 | 81.33 | 398.83 | 616.34 | 21.53 | 82.33 | 394.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.54 | 0.48 | 01-JAN-09:39 | 2144.52 | 19.49 | 86.50 | 238.83 | 1255.11 | 22.25 | 76.00 | 201.33 |
February | 241.00 | 0.53 | 0.48 | 01-FEB-09:00 | 2291.85 | 20.80 | 81.17 | 232.50 | 877.36 | 19.97 | 36.67 | 171.33 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-08:30 | 1880.24 | 18.59 | 79.00 | 308.17 | 1036.27 | 21.39 | 65.33 | 269.17 |
April | 380.33 | 0.51 | 0.48 | 01-APR-08:20 | 2761.17 | 18.46 | 85.00 | 329.83 | 1523.41 | 20.08 | 55.00 | 301.83 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-07:30 | 2970.63 | 16.15 | 54.50 | 359.50 | 1628.68 | 17.01 | 0.00 | 327.67 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-07:19 | 2999.48 | 12.43 | 0.00 | 364.83 | 1195.24 | 16.59 | 0.00 | 335.67 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-07:30 | 2232.69 | 13.30 | 3.67 | 364.83 | 995.19 | 17.01 | 0.00 | 314.83 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:49 | 2302.77 | 15.96 | 49.17 | 337.33 | 1257.19 | 17.15 | 5.00 | 289.33 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-07:30 | 1810.80 | 18.72 | 81.83 | 312.83 | 979.83 | 20.23 | 53.83 | 274.83 |
October | 348.00 | 0.53 | 0.48 | 01-OCT-07:00 | 2240.65 | 20.62 | 109.33 | 280.67 | 1218.35 | 21.86 | 81.17 | 245.67 |
November | 288.50 | 0.53 | 0.48 | 01-NOV-08:30 | 2032.90 | 19.80 | 80.83 | 245.17 | 1122.07 | 21.85 | 62.17 | 201.00 |
December | 290.67 | 0.53 | 0.48 | 01-DEC-08:00 | 1718.28 | 19.75 | 80.67 | 230.83 | 889.11 | 20.50 | 50.50 | 189.50 |
Annual Sum or Average | 4135.50 | 0.52 | 2319.25 | 17.52 | 791.67 | 3605.33 | 1183.58 | 19.46 | 485.67 | 3122.17 | ||
Minimum of Months | 241.00 | 0.51 | 0.48 | 1718.28 | 12.43 | 0.00 | 230.83 | 877.36 | 16.59 | 0.00 | 171.33 | |
Maximum of Months | 418.17 | 0.54 | 0.48 | 2999.48 | 20.80 | 109.33 | 364.83 | 1628.68 | 22.25 | 81.17 | 335.67 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.618392E+09 | 8501.41 | 02-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.656387E+09 | 8501.41 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.750327E+09 | 8501.41 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127411E+09 | 8501.41 | 07-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5981585.85 | 7218.41 | 01-MAY-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.255990E+09 | 8501.41 | 12-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.348205E+09 | 8501.41 | 06-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.717340E+09 | 8501.41 | 01-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.348003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.750327E+09 | 8501.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 5960207.10 | 5637.47 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1625561.89 | 5513.23 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1546795.33 | 5637.47 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2405270.43 | 5637.47 | 07-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 11537834.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5960207.10 | 5637.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 33450898.55 | 8441.81 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17438960.44 | 8356.64 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18475556.64 | 8441.81 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26732275.47 | 8441.81 | 06-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96097691.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33450898.55 | 8441.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 6625788.56 | 5598.03 | 02-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4674999.30 | 5598.03 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1432636.32 | 4529.27 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7596483.64 | 5598.03 | 07-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20329907.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7596483.64 | 5598.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 5144952.27 | 14828.11 | 02-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5144952.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5144952.27 | 14828.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 13429043.42 | 10098.33 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4805172.59 | 10098.33 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6382948.96 | 10098.33 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 339373.81 | 3959.36 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 37251756.15 | 10098.33 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62208294.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37251756.15 | 10098.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 13273841.10 | 6671.82 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4386540.45 | 6671.82 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4913877.30 | 6671.82 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 743555.67 | 6671.82 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 37014569.30 | 6671.82 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60332383.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37014569.30 | 6671.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 35672482.69 | 10052.15 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15145443.35 | 10052.15 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12727877.51 | 10052.15 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5277041.11 | 10052.15 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.103905E+09 | 10052.15 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103905E+09 | 10052.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 18058177.06 | 6633.10 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8313924.81 | 6633.10 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5087165.91 | 6633.10 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2366310.08 | 6633.10 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 61521059.83 | 6633.10 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95346637.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 61521059.83 | 6633.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 83127394.99 | 29773.72 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 19746043.72 | 29773.72 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6100479.05 | 26578.15 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3997556.39 | 18123.55 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118946E+09 | 29773.72 | 06-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.231918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.118946E+09 | 29773.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 84866469.17 | 13150.97 | 02-JAN-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 95894474.48 | 13150.97 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 85505903.24 | 13150.97 | 27-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7908813.89 | 7892.10 | 26-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 36218388.72 | 13150.97 | 24-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.276000E+09 | 13150.97 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.586394E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.276000E+09 | 13150.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 75684640.52 | 8602.46 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 68245474.14 | 8602.46 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 45892824.65 | 8602.46 | 13-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7107873.75 | 7093.11 | 26-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 30526558.94 | 8602.46 | 24-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231864E+09 | 8602.46 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.459322E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.231864E+09 | 8602.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.204970E+09 | 12102.04 | 10-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177193E+09 | 12084.15 | 08-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122847E+09 | 12089.84 | 13-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18227200.04 | 11786.46 | 26-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112976E+09 | 12023.89 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.609306E+09 | 12839.87 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.609306E+09 | 12839.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110116E+09 | 8565.17 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102472E+09 | 8565.17 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 69568527.38 | 8565.17 | 27-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9283290.29 | 6520.37 | 26-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 62435252.91 | 8565.17 | 24-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.347768E+09 | 8565.17 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.701644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.347768E+09 | 8565.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 55424087.74 | 4911.30 | 02-JAN-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 85733179.74 | 4133.71 | 01-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127020E+09 | 7295.56 | 27-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1246060.22 | 1644.42 | 12-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 30703657.43 | 4943.61 | 24-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.524308E+09 | 7295.56 | 05-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.824435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.524308E+09 | 7295.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.175957E+09 | 5330.43 | 02-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.256705E+09 | 4710.50 | 01-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.267925E+09 | 7825.73 | 27-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1482254.92 | 1030.37 | 21-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 57647874.65 | 4595.32 | 25-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116147E+09 | 5648.63 | 24-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.907604E+09 | 9396.57 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.907604E+09 | 9396.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.297337E+09 | 6798.68 | 02-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.406788E+09 | 6189.77 | 28-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388356E+09 | 8883.82 | 27-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5211228.94 | 2134.38 | 21-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115903E+09 | 5842.01 | 25-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.207917E+09 | 7261.10 | 24-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119066E+10 | 8883.82 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.261217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.119066E+10 | 8883.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.180499E+11 | 0.179203E+11 | 49445.81 | 31-JAN-16:40 | 49445.81 | 0.00 |
February | 0.00 | 0.00 | 0.408738E+10 | 0.363302E+10 | 24865.52 | 09-FEB-15:00 | 24865.52 | 0.00 |
March | 0.00 | 0.00 | 0.185824E+11 | 0.182022E+11 | 47622.77 | 20-MAR-15:10 | 47622.77 | 0.00 |
April | 0.00 | 0.00 | 0.469467E+11 | 0.468342E+11 | 65623.87 | 14-APR-16:00 | 65623.87 | 0.00 |
May | 0.00 | 0.00 | 0.620899E+11 | 0.620270E+11 | 69903.61 | 31-MAY-16:00 | 69903.61 | 0.00 |
June | 0.00 | 0.00 | 0.824406E+11 | 0.820696E+11 | 89242.24 | 28-JUN-06:03 | 89242.24 | 0.00 |
July | 0.00 | 0.00 | 0.846588E+11 | 0.783981E+11 | 119972.40 | 15-JUL-06:03 | 55268.82 | 0.00 |
August | 0.00 | 0.00 | 0.882573E+11 | 0.814008E+11 | 118204.74 | 01-AUG-04:03 | 62495.99 | 0.00 |
September | 0.00 | 0.00 | 0.768984E+11 | 0.699455E+11 | 118008.83 | 05-SEP-07:20 | 51634.98 | 0.00 |
October | 0.00 | 0.00 | 0.440706E+11 | 0.427463E+11 | 112904.89 | 03-OCT-06:03 | 60077.58 | 0.00 |
November | 0.00 | 0.00 | 0.201884E+11 | 0.190147E+11 | 55930.97 | 01-NOV-16:00 | 55930.97 | 0.00 |
December | 0.00 | 0.00 | 0.120642E+11 | 0.120182E+11 | 43904.64 | 22-DEC-16:30 | 43904.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.558335E+12 | 0.534210E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.408738E+10 | 0.363302E+10 | 24865.52 | 24865.52 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.882573E+11 | 0.820696E+11 | 119972.40 | 89242.24 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.143787E+11 | 0.142174E+11 | 41953.36 | 31-JAN-16:30 | 41953.36 | 0.00 |
February | 0.00 | 0.00 | 0.324329E+10 | 0.279410E+10 | 21301.23 | 22-FEB-16:00 | 21301.23 | 0.00 |
March | 0.00 | 0.00 | 0.143067E+11 | 0.138597E+11 | 44551.60 | 16-MAR-15:30 | 44551.60 | 0.00 |
April | 0.00 | 0.00 | 0.418499E+11 | 0.417554E+11 | 62194.92 | 24-APR-15:50 | 62194.92 | 0.00 |
May | 0.00 | 0.00 | 0.559343E+11 | 0.558813E+11 | 63311.19 | 08-MAY-16:00 | 63311.19 | 0.00 |
June | 0.00 | 0.00 | 0.754288E+11 | 0.751948E+11 | 77417.09 | 29-JUN-06:03 | 77417.09 | 0.00 |
July | 0.00 | 0.00 | 0.734845E+11 | 0.687342E+11 | 109693.82 | 14-JUL-05:03 | 44176.67 | 0.00 |
August | 0.00 | 0.00 | 0.743233E+11 | 0.693409E+11 | 106476.07 | 01-AUG-04:03 | 54897.62 | 0.00 |
September | 0.00 | 0.00 | 0.623473E+11 | 0.572322E+11 | 106416.18 | 02-SEP-05:03 | 58356.20 | 0.00 |
October | 0.00 | 0.00 | 0.347751E+11 | 0.336689E+11 | 91999.67 | 03-OCT-06:03 | 47846.10 | 0.00 |
November | 0.00 | 0.00 | 0.150896E+11 | 0.141209E+11 | 48403.68 | 01-NOV-15:30 | 48403.68 | 0.00 |
December | 0.00 | 0.00 | 0.643046E+10 | 0.636815E+10 | 35382.40 | 22-DEC-16:30 | 35382.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.471592E+12 | 0.453168E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.324329E+10 | 0.279410E+10 | 21301.23 | 21301.23 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.754288E+11 | 0.751948E+11 | 109693.82 | 77417.09 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.137737E+11 | 0.135300E+11 | 45795.43 | 31-JAN-16:20 | 45795.43 | 0.00 |
February | 0.00 | 0.00 | 0.316219E+10 | 0.261889E+10 | 21247.11 | 22-FEB-16:00 | 21247.11 | 0.00 |
March | 0.00 | 0.00 | 0.148003E+11 | 0.141406E+11 | 50907.95 | 16-MAR-15:30 | 50907.95 | 0.00 |
April | 0.00 | 0.00 | 0.460034E+11 | 0.458294E+11 | 72729.98 | 14-APR-15:30 | 72729.98 | 0.00 |
May | 0.00 | 0.00 | 0.617499E+11 | 0.616480E+11 | 73870.94 | 15-MAY-15:20 | 73870.94 | 0.00 |
June | 0.00 | 0.00 | 0.847300E+11 | 0.843331E+11 | 88707.47 | 28-JUN-15:00 | 88707.47 | 0.00 |
July | 0.00 | 0.00 | 0.816061E+11 | 0.765358E+11 | 125530.81 | 14-JUL-05:03 | 50071.09 | 0.00 |
August | 0.00 | 0.00 | 0.813117E+11 | 0.761484E+11 | 121848.50 | 01-AUG-04:03 | 60240.08 | 0.00 |
September | 0.00 | 0.00 | 0.666647E+11 | 0.614403E+11 | 117950.64 | 05-SEP-06:03 | 48629.21 | 0.00 |
October | 0.00 | 0.00 | 0.358867E+11 | 0.346075E+11 | 87432.34 | 02-OCT-04:02 | 86495.57 | 0.00 |
November | 0.00 | 0.00 | 0.144766E+11 | 0.134730E+11 | 54388.91 | 01-NOV-15:30 | 54388.91 | 0.00 |
December | 0.00 | 0.00 | 0.592891E+10 | 0.582152E+10 | 37452.23 | 22-DEC-15:50 | 37452.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.510094E+12 | 0.490126E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.316219E+10 | 0.261889E+10 | 21247.11 | 21247.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.847300E+11 | 0.843331E+11 | 125530.81 | 88707.47 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1575.64 | 5407.01 | 24-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1570.31 | 5434.16 | 02-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1597.79 | 5271.90 | 01-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1387.03 | 4878.43 | 04-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1317.31 | 4492.20 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1247.21 | 4109.03 | 01-JUN-11:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1101.12 | 3837.90 | 03-JUL-11:13 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1223.12 | 3956.01 | 30-AUG-11:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1216.49 | 4257.85 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1323.47 | 4682.80 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1459.38 | 5072.85 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1491.04 | 5330.07 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 1374.76 | ||||
Minimum of Months | 0.00 | 0.00 | 1101.12 | 3837.90 | ||
Maximum of Months | 0.00 | 0.00 | 1597.79 | 5434.16 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.251972E+10 | 0.38 | 4752.60 | 19-JAN-17:00 | 1.11 |
February | 0.174353E+10 | 0.34 | 4393.73 | 01-FEB-07:01 | 1.05 |
March | 0.246162E+10 | 0.37 | 4976.90 | 20-MAR-14:30 | 1.13 |
April | 0.443924E+10 | 0.51 | 7606.69 | 04-APR-15:50 | 1.47 |
May | 0.575934E+10 | 0.58 | 9255.61 | 08-MAY-16:00 | 1.67 |
June | 0.717977E+10 | 0.69 | 11994.60 | 05-JUN-05:12 | 1.96 |
July | 0.677106E+10 | 0.66 | 11994.60 | 05-JUL-05:12 | 1.96 |
August | 0.685884E+10 | 0.65 | 11994.60 | 01-AUG-06:03 | 1.94 |
September | 0.594818E+10 | 0.60 | 11994.60 | 02-SEP-06:03 | 1.94 |
October | 0.437074E+10 | 0.49 | 11994.60 | 02-OCT-04:02 | 1.94 |
November | 0.305368E+10 | 0.41 | 5881.58 | 14-NOV-16:30 | 1.24 |
December | 0.215025E+10 | 0.36 | 4544.03 | 27-DEC-16:40 | 1.08 |
Annual Sum or Average | 0.532560E+11 | 0.51 | |||
Minimum of Months | 0.174353E+10 | 0.34 | 4393.73 | 1.05 | |
Maximum of Months | 0.717977E+10 | 0.69 | 11994.60 | 1.96 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.180765E+10 | 0.36 | 4191.85 | 31-JAN-16:40 | 1.11 |
February | 0.132818E+10 | 0.34 | 3200.09 | 22-FEB-16:30 | 0.95 |
March | 0.194916E+10 | 0.37 | 4904.50 | 20-MAR-14:05 | 1.21 |
April | 0.408530E+10 | 0.52 | 8396.36 | 24-APR-15:50 | 1.70 |
May | 0.527463E+10 | 0.59 | 9571.49 | 30-MAY-06:03 | 1.85 |
June | 0.716802E+10 | 0.73 | 10604.72 | 05-JUN-05:12 | 1.97 |
July | 0.644636E+10 | 0.67 | 10604.72 | 10-JUL-04:02 | 1.96 |
August | 0.648313E+10 | 0.66 | 10604.72 | 14-AUG-04:02 | 1.96 |
September | 0.508272E+10 | 0.57 | 10604.72 | 05-SEP-05:12 | 1.96 |
October | 0.324280E+10 | 0.45 | 10604.72 | 02-OCT-04:02 | 1.96 |
November | 0.199875E+10 | 0.37 | 4868.53 | 02-NOV-15:40 | 1.20 |
December | 0.147696E+10 | 0.34 | 3579.35 | 22-DEC-16:50 | 1.01 |
Annual Sum or Average | 0.463437E+11 | 0.50 | |||
Minimum of Months | 0.132818E+10 | 0.34 | 3200.09 | 0.95 | |
Maximum of Months | 0.716802E+10 | 0.73 | 10604.72 | 1.97 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.174913E+10 | 0.37 | 3675.11 | 27-JAN-16:30 | 0.93 |
February | 0.133414E+10 | 0.37 | 2731.04 | 22-FEB-16:30 | 0.79 |
March | 0.187745E+10 | 0.39 | 4560.68 | 16-MAR-15:30 | 1.05 |
April | 0.389205E+10 | 0.49 | 8565.25 | 24-APR-15:30 | 1.54 |
May | 0.503633E+10 | 0.54 | 8341.83 | 15-MAY-15:20 | 1.52 |
June | 0.712612E+10 | 0.68 | 11255.46 | 19-JUN-05:12 | 1.84 |
July | 0.628031E+10 | 0.62 | 11835.86 | 31-JUL-04:02 | 1.88 |
August | 0.632016E+10 | 0.61 | 11127.92 | 14-AUG-15:20 | 1.80 |
September | 0.481909E+10 | 0.53 | 11937.37 | 25-SEP-05:12 | 1.89 |
October | 0.297227E+10 | 0.43 | 11537.86 | 02-OCT-04:02 | 1.85 |
November | 0.183685E+10 | 0.37 | 4616.49 | 02-NOV-15:30 | 1.05 |
December | 0.147702E+10 | 0.37 | 3052.87 | 22-DEC-16:40 | 0.84 |
Annual Sum or Average | 0.447209E+11 | 0.48 | |||
Minimum of Months | 0.133414E+10 | 0.37 | 2731.04 | 0.79 | |
Maximum of Months | 0.712612E+10 | 0.68 | 11937.37 | 1.89 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 56.87 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 56.59 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 56.91 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 56.82 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.31 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:05 | 2.06 | 2.06 | 57.11 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 57.84 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:05 | 2.06 | 2.06 | 57.25 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:05 | 2.06 | 2.06 | 57.57 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.06 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 56.47 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 56.98 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.47 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.06 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 57.94 | 57.94 | 1575.64 | 5407.01 | 24-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.57 | 57.57 | 1570.31 | 5434.16 | 02-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.28 | 57.28 | 1597.79 | 5271.90 | 01-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.22 | 57.22 | 1387.03 | 4878.43 | 04-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.49 | 57.49 | 1317.31 | 4492.20 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.33 | 57.33 | 1247.21 | 4109.03 | 01-JUN-11:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.01 | 58.01 | 1101.12 | 3837.90 | 03-JUL-11:13 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.40 | 57.40 | 1223.12 | 3956.01 | 30-AUG-11:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.79 | 57.79 | 1216.49 | 4257.85 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.44 | 56.44 | 1323.47 | 4682.80 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.23 | 57.23 | 1459.38 | 5072.85 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.33 | 57.33 | 1491.04 | 5330.07 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 1374.76 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.44 | 56.44 | 1101.12 | 3837.90 | ||
Maximum of Months | 0.00 | 0.00 | 58.01 | 58.01 | 1597.79 | 5434.16 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.770061E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.353151E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.796629E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.171407E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.231607E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.330620E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.317753E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.327703E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.273903E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.163180E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.840638E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.600826E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.215230E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.353151E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.330620E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.553652E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.224812E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.566376E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.153322E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.209701E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.308883E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.281375E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.283286E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.225472E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.125801E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.581600E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.339888E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.181447E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.224812E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.308883E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.586117E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.267229E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.605880E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.163749E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.225405E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.340053E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.305326E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.304116E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.236589E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.127788E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.580268E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.464036E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.195338E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.267229E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.340053E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.251972E+10 | 0.180499E+11 | 0.719853E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174353E+10 | 0.408738E+10 | 0.765860E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.246162E+10 | 0.185824E+11 | 0.898802E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.443924E+10 | 0.469467E+11 | 0.127411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.575934E+10 | 0.620899E+11 | 5981585.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.717977E+10 | 0.824406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.677106E+10 | 0.846588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.685884E+10 | 0.882573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.594818E+10 | 0.768984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.437074E+10 | 0.440706E+11 | 0.257236E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.305368E+10 | 0.201884E+11 | 0.378909E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.215025E+10 | 0.120642E+11 | 0.127838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.532560E+11 | 0.558335E+12 | 0.443243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.174353E+10 | 0.408738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.717977E+10 | 0.882573E+11 | 0.127838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.180765E+10 | 0.143787E+11 | 0.261536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132818E+10 | 0.324329E+10 | 0.289356E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.194916E+10 | 0.143067E+11 | 0.297037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.408530E+10 | 0.418499E+11 | 1482254.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.527463E+10 | 0.559343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.716802E+10 | 0.754288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.644636E+10 | 0.734845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.648313E+10 | 0.743233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.508272E+10 | 0.623473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.324280E+10 | 0.347751E+11 | 57647874.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.199875E+10 | 0.150896E+11 | 0.124873E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147696E+10 | 0.643046E+10 | 0.114730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.463437E+11 | 0.471592E+12 | 0.217923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132818E+10 | 0.324329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.716802E+10 | 0.754288E+11 | 0.114730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.174913E+10 | 0.137737E+11 | 0.856102E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133414E+10 | 0.316219E+10 | 0.870339E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187745E+10 | 0.148003E+11 | 0.718271E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.389205E+10 | 0.460034E+11 | 5211228.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.503633E+10 | 0.617499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.712612E+10 | 0.847300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.628031E+10 | 0.816061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.632016E+10 | 0.813117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.481909E+10 | 0.666647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.297227E+10 | 0.358867E+11 | 0.158430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183685E+10 | 0.144766E+11 | 0.454071E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147702E+10 | 0.592891E+10 | 0.277454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.447209E+11 | 0.510094E+12 | 0.583697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133414E+10 | 0.316219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.712612E+10 | 0.847300E+11 | 0.277454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.251972E+10 | 0.00 | 0.00 | 0.00 | 0.451646E+10 | 0.664429E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174353E+10 | 0.00 | 0.00 | 0.00 | 0.110786E+10 | 0.680127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.246162E+10 | 0.00 | 0.00 | 0.00 | 0.473289E+10 | 0.771782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.443924E+10 | 0.00 | 0.00 | 0.00 | 0.125740E+11 | 0.127411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.575934E+10 | 0.00 | 0.00 | 0.00 | 0.173953E+11 | 5981585.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.717977E+10 | 0.00 | 0.00 | 0.00 | 0.258822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.677106E+10 | 0.00 | 0.00 | 0.00 | 0.250042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.685884E+10 | 0.00 | 0.00 | 0.00 | 0.259115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.594818E+10 | 0.00 | 0.00 | 0.00 | 0.214421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.437074E+10 | 0.00 | 0.00 | 0.00 | 0.116913E+11 | 0.255990E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.305368E+10 | 0.00 | 0.00 | 0.00 | 0.500449E+10 | 0.348205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.215025E+10 | 0.00 | 0.00 | 0.00 | 0.310394E+10 | 0.754074E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.532560E+11 | 0.00 | 0.00 | 0.00 | 0.158366E+12 | 0.360800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.174353E+10 | 0.00 | 0.00 | 0.00 | 0.110786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.717977E+10 | 0.00 | 0.00 | 0.00 | 0.259115E+11 | 0.771782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.180765E+10 | 0.00 | 0.00 | 0.00 | 0.364329E+10 | 85578496.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132818E+10 | 0.00 | 0.00 | 0.00 | 0.887295E+09 | 32651081.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.194916E+10 | 0.00 | 0.00 | 0.00 | 0.368548E+10 | 29111869.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.408530E+10 | 0.00 | 0.00 | 0.00 | 0.112469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.527463E+10 | 0.00 | 0.00 | 0.00 | 0.156955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.716802E+10 | 0.00 | 0.00 | 0.00 | 0.237203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.644636E+10 | 0.00 | 0.00 | 0.00 | 0.216911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.648313E+10 | 0.00 | 0.00 | 0.00 | 0.218455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.508272E+10 | 0.00 | 0.00 | 0.00 | 0.174645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.324280E+10 | 0.00 | 0.00 | 0.00 | 0.933727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.199875E+10 | 0.00 | 0.00 | 0.00 | 0.380852E+10 | 8726280.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147696E+10 | 0.00 | 0.00 | 0.00 | 0.168223E+10 | 0.239692E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.463437E+11 | 0.00 | 0.00 | 0.00 | 0.134708E+12 | 0.395760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132818E+10 | 0.00 | 0.00 | 0.00 | 0.887295E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.716802E+10 | 0.00 | 0.00 | 0.00 | 0.237203E+11 | 0.239692E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.174913E+10 | 0.00 | 0.00 | 0.00 | 0.355328E+10 | 0.558765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133414E+10 | 0.00 | 0.00 | 0.00 | 0.874599E+09 | 0.463551E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187745E+10 | 0.00 | 0.00 | 0.00 | 0.385143E+10 | 0.329915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.389205E+10 | 0.00 | 0.00 | 0.00 | 0.124828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.503633E+10 | 0.00 | 0.00 | 0.00 | 0.175042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.712612E+10 | 0.00 | 0.00 | 0.00 | 0.268792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.628031E+10 | 0.00 | 0.00 | 0.00 | 0.242523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.632016E+10 | 0.00 | 0.00 | 0.00 | 0.240915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.481909E+10 | 0.00 | 0.00 | 0.00 | 0.188399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.297227E+10 | 0.00 | 0.00 | 0.00 | 0.976397E+10 | 42527177.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183685E+10 | 0.00 | 0.00 | 0.00 | 0.371968E+10 | 0.246154E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147702E+10 | 0.00 | 0.00 | 0.00 | 0.157946E+10 | 0.158388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.447209E+11 | 0.00 | 0.00 | 0.00 | 0.147392E+12 | 0.322480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133414E+10 | 0.00 | 0.00 | 0.00 | 0.874599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.712612E+10 | 0.00 | 0.00 | 0.00 | 0.268792E+11 | 0.158388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.931183E+09 | 1101351.31 | 0.00 | 38911054.20 | 5866526.19 | 0.00 | 0.123620E+11 | 0.00 | 0.83 |
February | 0.613270E+09 | 0.00 | 0.00 | 36660466.58 | 1711805.79 | 0.00 | 0.158087E+11 | 0.00 | 0.82 |
March | 0.519636E+09 | 14101685.23 | 0.00 | 42508205.09 | 552385.85 | 0.00 | 0.127505E+11 | 0.00 | 0.80 |
April | 0.306376E+09 | 0.648387E+09 | 0.00 | 26969457.34 | 59990046.09 | 0.00 | 0.505256E+10 | 0.00 | 0.65 |
May | 0.233118E+09 | 0.132344E+10 | 0.00 | 16893577.12 | 46416799.54 | 0.00 | 0.201069E+10 | 0.00 | 0.49 |
June | 0.103174E+09 | 0.347392E+10 | 0.00 | 4385830.39 | 91227358.43 | 0.00 | 0.447417E+09 | 0.00 | 0.34 |
July | 59496840.20 | 0.461013E+10 | 0.00 | 1404393.02 | 0.193342E+09 | 0.00 | 0.158750E+09 | 0.00 | 0.32 |
August | 45513320.24 | 0.465310E+10 | 0.00 | 2565140.01 | 0.121756E+09 | 0.00 | 0.210067E+09 | 0.00 | 0.39 |
September | 70022128.37 | 0.321384E+10 | 0.00 | 9272280.80 | 0.395289E+09 | 0.00 | 0.739203E+09 | 0.00 | 0.46 |
October | 0.357331E+09 | 0.729387E+09 | 0.00 | 33701774.50 | 45195099.14 | 0.00 | 0.896156E+10 | 0.00 | 0.79 |
November | 0.736241E+09 | 20215413.80 | 0.00 | 44771326.29 | 6314812.50 | 0.00 | 0.140121E+11 | 0.00 | 0.96 |
December | 0.834585E+09 | 564871.12 | 0.00 | 40869859.65 | 336370.99 | 0.00 | 0.132927E+11 | 0.00 | 0.65 |
Annual Sum or Average | 0.480995E+10 | 0.186882E+11 | 0.00 | 0.298913E+09 | 0.967999E+09 | 0.00 | 0.858063E+11 | 0.00 | 0.62 |
Minimum of Months | 45513320.24 | 0.00 | 0.00 | 1404393.02 | 336370.99 | 0.00 | 0.158750E+09 | 0.00 | 0.32 |
Maximum of Months | 0.931183E+09 | 0.465310E+10 | 0.00 | 44771326.29 | 0.395289E+09 | 0.00 | 0.158087E+11 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.233930E+10 | 0.00 | 0.00 | 15392839.11 | 9464675.58 | 735504.43 | 0.550436E+10 | 0.00 | 0.49 |
February | 0.320728E+10 | 0.00 | 0.00 | 11836648.92 | 1960370.02 | 0.00 | 0.646668E+10 | 0.00 | 0.49 |
March | 0.211595E+10 | 2602330.03 | 0.00 | 18800369.37 | 540395.55 | 0.00 | 0.675560E+10 | 0.00 | 0.55 |
April | 0.608386E+09 | 0.419482E+09 | 0.00 | 17901370.59 | 77704475.65 | 0.00 | 0.311774E+10 | 0.00 | 0.46 |
May | 0.353370E+09 | 0.946160E+09 | 0.00 | 12824660.72 | 51886945.63 | 0.00 | 0.137044E+10 | 0.00 | 0.38 |
June | 0.141643E+09 | 0.289104E+10 | 0.00 | 3600656.46 | 92988833.30 | 0.00 | 0.346327E+09 | 0.00 | 0.30 |
July | 57139692.47 | 0.368174E+10 | 0.00 | 1157216.75 | 0.160263E+09 | 0.00 | 0.126754E+09 | 0.00 | 0.27 |
August | 61259736.99 | 0.366407E+10 | 0.00 | 1615433.66 | 0.102652E+09 | 0.00 | 0.130536E+09 | 0.00 | 0.33 |
September | 94936321.83 | 0.251287E+10 | 0.00 | 7025333.15 | 0.228463E+09 | 0.00 | 0.452936E+09 | 0.00 | 0.37 |
October | 0.694183E+09 | 0.575327E+09 | 0.00 | 18565429.57 | 26569406.79 | 0.00 | 0.496914E+10 | 0.00 | 0.51 |
November | 0.181241E+10 | 11625644.70 | 0.00 | 19960380.17 | 14708247.14 | 0.00 | 0.666592E+10 | 0.00 | 0.55 |
December | 0.408388E+10 | 772826.69 | 0.00 | 10480879.29 | 320752.83 | 0.00 | 0.523675E+10 | 0.00 | 0.44 |
Annual Sum or Average | 0.155698E+11 | 0.147057E+11 | 0.00 | 0.139161E+09 | 0.767522E+09 | 735504.43 | 0.411432E+11 | 0.00 | 0.43 |
Minimum of Months | 57139692.47 | 0.00 | 0.00 | 1157216.75 | 320752.83 | 0.00 | 0.126754E+09 | 0.00 | 0.27 |
Maximum of Months | 0.408388E+10 | 0.368174E+10 | 0.00 | 19960380.17 | 0.228463E+09 | 735504.43 | 0.675560E+10 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.326840E+10 | 0.00 | 0.00 | 9427105.26 | 0.00 | 30906609.97 | 0.350107E+10 | 0.00 | 0.48 |
February | 0.403867E+10 | 0.00 | 0.00 | 7121291.92 | 2268741.31 | 7514661.33 | 0.457854E+10 | 0.00 | 0.45 |
March | 0.298415E+10 | 1097339.56 | 0.00 | 13789387.19 | 167094.01 | 333322.90 | 0.485628E+10 | 0.00 | 0.52 |
April | 0.768840E+09 | 0.293804E+09 | 0.00 | 17673417.44 | 57618771.86 | 0.00 | 0.224100E+10 | 0.00 | 0.43 |
May | 0.346934E+09 | 0.713557E+09 | 0.00 | 14155093.52 | 45409992.90 | 0.00 | 0.844145E+09 | 0.00 | 0.35 |
June | 0.131294E+09 | 0.265290E+10 | 0.00 | 2732309.57 | 84083829.58 | 0.00 | 0.197912E+09 | 0.00 | 0.28 |
July | 42535552.32 | 0.350692E+10 | 0.00 | 953750.41 | 0.207729E+09 | 0.00 | 79161875.96 | 0.00 | 0.27 |
August | 52099673.76 | 0.347817E+10 | 0.00 | 1012056.51 | 0.127632E+09 | 0.00 | 59424188.94 | 0.00 | 0.31 |
September | 90458915.36 | 0.232695E+10 | 0.00 | 6113614.95 | 0.287632E+09 | 0.00 | 0.230579E+09 | 0.00 | 0.34 |
October | 0.112812E+10 | 0.509229E+09 | 0.00 | 14446384.58 | 40915996.35 | 0.00 | 0.339077E+10 | 0.00 | 0.45 |
November | 0.287721E+10 | 11320567.71 | 0.00 | 13148981.44 | 27385973.59 | 367069.26 | 0.443637E+10 | 0.00 | 0.51 |
December | 0.549386E+10 | 0.00 | 0.00 | 4544289.88 | 2710316.70 | 47615803.88 | 0.258332E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.212226E+11 | 0.134939E+11 | 0.00 | 0.105118E+09 | 0.883554E+09 | 86737467.34 | 0.269986E+11 | 0.00 | 0.40 |
Minimum of Months | 42535552.32 | 0.00 | 0.00 | 953750.41 | 0.00 | 0.00 | 59424188.94 | 0.00 | 0.27 |
Maximum of Months | 0.549386E+10 | 0.350692E+10 | 0.00 | 17673417.44 | 0.287632E+09 | 47615803.88 | 0.485628E+10 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.961945E+09 | 0.00 | 0.00 | 994286.06 | 0.00 | 92443263.11 | 0.287509E+09 | 0.00 | 0.44 |
February | 0.125421E+10 | 0.00 | 0.00 | 444029.88 | 479399.30 | 85155820.29 | 0.326077E+09 | 0.00 | 0.41 |
March | 0.916772E+09 | 229320.67 | 0.00 | 2207438.46 | 88479.44 | 67446612.85 | 0.591270E+09 | 0.00 | 0.50 |
April | 0.236503E+09 | 98693374.26 | 0.00 | 3895641.87 | 11627834.06 | 0.00 | 0.370863E+09 | 0.00 | 0.48 |
May | 97444331.67 | 0.260949E+09 | 0.00 | 3538263.49 | 8556221.57 | 0.00 | 0.160442E+09 | 0.00 | 0.46 |
June | 28483215.46 | 0.106853E+10 | 0.00 | 657551.71 | 12490652.88 | 0.00 | 45702400.51 | 0.00 | 0.47 |
July | 11601504.12 | 0.126746E+10 | 0.00 | 208935.26 | 29715435.88 | 0.00 | 15776105.45 | 0.00 | 0.42 |
August | 13413936.64 | 0.112469E+10 | 0.00 | 191880.25 | 26221770.78 | 0.00 | 8381789.53 | 0.00 | 0.45 |
September | 28701897.64 | 0.722591E+09 | 0.00 | 1482058.54 | 58359365.07 | 0.00 | 45010938.92 | 0.00 | 0.44 |
October | 0.462276E+09 | 0.141651E+09 | 0.00 | 2435230.05 | 9396210.62 | 7464551.15 | 0.386233E+09 | 0.00 | 0.45 |
November | 0.862026E+09 | 1857829.87 | 0.00 | 1746382.77 | 6240620.52 | 57110868.16 | 0.472041E+09 | 0.00 | 0.46 |
December | 0.125654E+10 | 0.00 | 0.00 | 234896.41 | 572706.95 | 0.302643E+09 | 0.105207E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.612992E+10 | 0.468665E+10 | 0.00 | 18036594.75 | 0.163749E+09 | 0.612264E+09 | 0.281451E+10 | 0.00 | 0.45 |
Minimum of Months | 11601504.12 | 0.00 | 0.00 | 191880.25 | 0.00 | 0.00 | 8381789.53 | 0.00 | 0.39 |
Maximum of Months | 0.125654E+10 | 0.126746E+10 | 0.00 | 3895641.87 | 58359365.07 | 0.302643E+09 | 0.591270E+09 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.387695E+09 | 0.00 | 0.00 | 2291775.35 | 0.00 | 27332485.60 | 0.775031E+09 | 0.00 | 0.63 |
February | 0.460349E+09 | 0.00 | 0.00 | 1664447.67 | 301863.46 | 31246123.97 | 0.929645E+09 | 0.00 | 0.54 |
March | 0.339821E+09 | 432473.99 | 0.00 | 3664963.72 | 8094.89 | 22745796.47 | 0.120129E+10 | 0.00 | 0.80 |
April | 84929232.63 | 94579939.46 | 0.00 | 6177260.87 | 7054457.04 | 0.00 | 0.797314E+09 | 0.00 | 0.98 |
May | 46951843.03 | 0.208605E+09 | 0.00 | 5083562.18 | 4466909.19 | 0.00 | 0.323893E+09 | 0.00 | 0.83 |
June | 14071215.26 | 0.897805E+09 | 0.00 | 833827.38 | 5279893.51 | 0.00 | 54066752.55 | 0.00 | 0.68 |
July | 5041623.48 | 0.113735E+10 | 0.00 | 259636.53 | 15604054.85 | 0.00 | 21312123.81 | 0.00 | 0.60 |
August | 7484386.68 | 0.106491E+10 | 0.00 | 223456.40 | 14114886.80 | 0.00 | 11867157.12 | 0.00 | 0.66 |
September | 14620676.42 | 0.696485E+09 | 0.00 | 1425193.75 | 26360868.00 | 0.00 | 45333184.59 | 0.00 | 0.65 |
October | 0.171103E+09 | 0.134350E+09 | 0.00 | 3615133.40 | 4785327.66 | 3979217.91 | 0.796145E+09 | 0.00 | 0.78 |
November | 0.378535E+09 | 1390634.30 | 0.00 | 2780086.19 | 3770050.67 | 11634641.28 | 0.866775E+09 | 0.00 | 0.68 |
December | 0.665800E+09 | 0.00 | 0.00 | 856150.46 | 360616.51 | 97330003.38 | 0.388898E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.257640E+10 | 0.423591E+10 | 0.00 | 28875493.90 | 82107022.58 | 0.194268E+09 | 0.621157E+10 | 0.00 | 0.69 |
Minimum of Months | 5041623.48 | 0.00 | 0.00 | 223456.40 | 0.00 | 0.00 | 11867157.12 | 0.00 | 0.44 |
Maximum of Months | 0.665800E+09 | 0.113735E+10 | 0.00 | 6177260.87 | 26360868.00 | 97330003.38 | 0.120129E+10 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.430199E+09 | 0.00 | 0.00 | 12010234.51 | 0.00 | 35650696.00 | 0.340771E+10 | 0.00 | 1.45 |
February | 0.652227E+09 | 0.00 | 0.00 | 6303672.56 | 477270.41 | 45711859.13 | 0.338049E+10 | 0.00 | 0.95 |
March | 0.551069E+09 | 606845.47 | 0.00 | 7054349.61 | 1794.88 | 52648522.81 | 0.219657E+10 | 0.00 | 0.93 |
April | 0.220472E+09 | 0.153813E+09 | 0.00 | 6182442.27 | 10974393.58 | 0.00 | 0.595053E+09 | 0.00 | 0.67 |
May | 0.116074E+09 | 0.285704E+09 | 0.00 | 3643922.97 | 7953402.73 | 0.00 | 0.137724E+09 | 0.00 | 0.48 |
June | 33830325.46 | 0.103579E+10 | 0.00 | 512707.19 | 13161856.38 | 0.00 | 29872240.11 | 0.00 | 0.44 |
July | 11922220.07 | 0.126901E+10 | 0.00 | 184370.74 | 31625461.08 | 0.00 | 11430440.23 | 0.00 | 0.42 |
August | 12839965.94 | 0.129245E+10 | 0.00 | 193653.60 | 24457540.98 | 0.00 | 8632448.22 | 0.00 | 0.50 |
September | 27628993.39 | 0.994222E+09 | 0.00 | 2187194.17 | 46507234.70 | 0.00 | 61391239.24 | 0.00 | 0.57 |
October | 0.258833E+09 | 0.240094E+09 | 0.00 | 8553797.23 | 8146146.09 | 1986088.67 | 0.169657E+10 | 0.00 | 1.00 |
November | 0.432155E+09 | 2780491.97 | 0.00 | 10545082.15 | 5960753.29 | 15691557.78 | 0.325604E+10 | 0.00 | 1.29 |
December | 0.632810E+09 | 849389.88 | 0.00 | 8915332.23 | 305171.77 | 0.115501E+09 | 0.345639E+10 | 0.00 | 1.11 |
Annual Sum or Average | 0.338006E+10 | 0.527532E+10 | 0.00 | 66286759.23 | 0.149571E+09 | 0.267190E+09 | 0.182379E+11 | 0.00 | 0.82 |
Minimum of Months | 11922220.07 | 0.00 | 0.00 | 184370.74 | 0.00 | 0.00 | 8632448.22 | 0.00 | 0.42 |
Maximum of Months | 0.652227E+09 | 0.129245E+10 | 0.00 | 12010234.51 | 46507234.70 | 0.115501E+09 | 0.345639E+10 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.495038E+09 | 0.00 | 0.00 | 2696491.11 | 0.00 | 51724518.82 | 0.703348E+09 | 0.00 | 0.75 |
February | 0.633853E+09 | 0.00 | 0.00 | 1615893.61 | 302475.09 | 52286350.53 | 0.878750E+09 | 0.00 | 0.61 |
March | 0.470922E+09 | 233433.81 | 0.00 | 3237421.81 | 46673.05 | 40378193.11 | 0.894441E+09 | 0.00 | 0.79 |
April | 0.143075E+09 | 0.128729E+09 | 0.00 | 4456388.63 | 1899487.52 | 0.00 | 0.390730E+09 | 0.00 | 0.76 |
May | 66408734.63 | 0.293831E+09 | 0.00 | 2678205.46 | 2043919.29 | 0.00 | 98339748.76 | 0.00 | 0.62 |
June | 18506803.99 | 0.971866E+09 | 0.00 | 376812.94 | 5469712.93 | 0.00 | 24469599.70 | 0.00 | 0.61 |
July | 7092153.61 | 0.100016E+10 | 0.00 | 131904.79 | 14583685.30 | 0.00 | 8716736.25 | 0.00 | 0.51 |
August | 7446384.17 | 0.909437E+09 | 0.00 | 148399.55 | 12095194.02 | 0.00 | 6511742.08 | 0.00 | 0.57 |
September | 17501032.58 | 0.594189E+09 | 0.00 | 1295489.61 | 32083610.73 | 0.00 | 37484836.22 | 0.00 | 0.55 |
October | 0.241550E+09 | 0.118276E+09 | 0.00 | 3365608.80 | 4901470.87 | 4397362.67 | 0.557857E+09 | 0.00 | 0.68 |
November | 0.436879E+09 | 1787797.77 | 0.00 | 3112435.23 | 3764958.55 | 34065174.42 | 0.865466E+09 | 0.00 | 0.76 |
December | 0.628211E+09 | 87396.24 | 0.00 | 1401803.51 | 328502.64 | 0.165971E+09 | 0.606794E+09 | 0.00 | 0.55 |
Annual Sum or Average | 0.316648E+10 | 0.401859E+10 | 0.00 | 24516855.05 | 77519689.98 | 0.348823E+09 | 0.507291E+10 | 0.00 | 0.65 |
Minimum of Months | 7092153.61 | 0.00 | 0.00 | 131904.79 | 0.00 | 0.00 | 6511742.08 | 0.00 | 0.51 |
Maximum of Months | 0.633853E+09 | 0.100016E+10 | 0.00 | 4456388.63 | 32083610.73 | 0.165971E+09 | 0.894441E+09 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112724E+10 | 47212.46 | 0.00 | 795755.44 | 1338620.77 | 16583303.75 | 0.215915E+09 | 0.00 | 0.40 |
February | 0.152433E+10 | 0.00 | 0.00 | 144895.10 | 360457.27 | 5960667.95 | 0.134049E+09 | 0.00 | 0.39 |
March | 0.109564E+10 | 1649465.08 | 0.00 | 961081.44 | 124445.39 | 15367863.52 | 0.232560E+09 | 0.00 | 0.38 |
April | 0.280385E+09 | 0.114514E+09 | 0.00 | 2193917.60 | 15580241.86 | 0.00 | 0.287447E+09 | 0.00 | 0.38 |
May | 0.114786E+09 | 0.283456E+09 | 0.00 | 1708826.67 | 9811356.92 | 0.00 | 0.164182E+09 | 0.00 | 0.36 |
June | 33037003.11 | 0.962152E+09 | 0.00 | 546995.75 | 20751266.68 | 0.00 | 60802798.60 | 0.00 | 0.38 |
July | 15978605.36 | 0.123195E+10 | 0.00 | 213738.17 | 40555685.80 | 0.00 | 25613643.45 | 0.00 | 0.37 |
August | 14380478.85 | 0.116409E+10 | 0.00 | 301521.04 | 28259470.08 | 0.00 | 27260807.27 | 0.00 | 0.41 |
September | 21750911.10 | 0.801980E+09 | 0.00 | 1484408.76 | 85916267.49 | 0.00 | 0.107166E+09 | 0.00 | 0.46 |
October | 0.345253E+09 | 0.161664E+09 | 0.00 | 3005286.00 | 9559538.67 | 0.00 | 0.662638E+09 | 0.00 | 0.50 |
November | 0.835691E+09 | 1426270.28 | 0.00 | 2717812.87 | 2939761.53 | 0.00 | 0.740536E+09 | 0.00 | 0.49 |
December | 0.136439E+10 | 0.00 | 0.00 | 398724.46 | 121168.19 | 27074390.23 | 0.173500E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.677287E+10 | 0.472293E+10 | 0.00 | 14472963.29 | 0.215318E+09 | 64986225.45 | 0.283167E+10 | 0.00 | 0.40 |
Minimum of Months | 14380478.85 | 0.00 | 0.00 | 144895.10 | 121168.19 | 0.00 | 25613643.45 | 0.00 | 0.34 |
Maximum of Months | 0.152433E+10 | 0.123195E+10 | 0.00 | 3005286.00 | 85916267.49 | 27074390.23 | 0.740536E+09 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.428111E+09 | 122776.35 | 0.00 | 2655587.08 | 782470.67 | 4321877.91 | 0.855046E+09 | 0.00 | 0.61 |
February | 0.535845E+09 | 0.00 | 0.00 | 1654914.50 | 228318.73 | 1155907.68 | 0.857726E+09 | 0.00 | 0.51 |
March | 0.413837E+09 | 1548305.03 | 0.00 | 2886567.84 | 73676.60 | 1405205.46 | 0.791677E+09 | 0.00 | 0.57 |
April | 89201439.17 | 0.129704E+09 | 0.00 | 4583111.72 | 8009218.35 | 0.00 | 0.766579E+09 | 0.00 | 0.86 |
May | 54157126.19 | 0.264866E+09 | 0.00 | 3203798.59 | 5901160.23 | 0.00 | 0.351289E+09 | 0.00 | 0.72 |
June | 11439862.94 | 0.858903E+09 | 0.00 | 783894.86 | 7712087.93 | 0.00 | 82732894.55 | 0.00 | 0.59 |
July | 4866828.81 | 0.111910E+10 | 0.00 | 304164.23 | 19380827.28 | 0.00 | 36513566.17 | 0.00 | 0.55 |
August | 4269982.92 | 0.109345E+10 | 0.00 | 398872.22 | 12856543.02 | 0.00 | 34363755.26 | 0.00 | 0.62 |
September | 8925861.77 | 0.752465E+09 | 0.00 | 1492755.91 | 38526643.74 | 0.00 | 0.113238E+09 | 0.00 | 0.68 |
October | 0.111297E+09 | 0.149465E+09 | 0.00 | 4513979.13 | 4978574.08 | 0.00 | 0.115319E+10 | 0.00 | 0.91 |
November | 0.285608E+09 | 1297358.46 | 0.00 | 4390313.30 | 1760629.01 | 0.00 | 0.133030E+10 | 0.00 | 0.80 |
December | 0.581789E+09 | 33466.90 | 0.00 | 1962642.16 | 44864.79 | 1565417.40 | 0.666029E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.252935E+10 | 0.437095E+10 | 0.00 | 28830601.55 | 0.100255E+09 | 8448408.46 | 0.703869E+10 | 0.00 | 0.66 |
Minimum of Months | 4269982.92 | 0.00 | 0.00 | 304164.23 | 44864.79 | 0.00 | 34363755.26 | 0.00 | 0.45 |
Maximum of Months | 0.581789E+09 | 0.111910E+10 | 0.00 | 4583111.72 | 38526643.74 | 4321877.91 | 0.133030E+10 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.410512E+09 | 1301658.96 | 0.00 | 10602122.13 | 995095.02 | 0.289086E+09 | 0.245441E+10 | 0.00 | 1.15 |
February | 0.100778E+10 | 0.00 | 0.00 | 2416779.56 | 360250.32 | 0.323976E+09 | 0.131418E+10 | 0.00 | 0.63 |
March | 0.799270E+09 | 3800194.83 | 0.00 | 3561882.94 | 116249.86 | 0.350519E+09 | 0.691052E+09 | 0.00 | 0.56 |
April | 0.278092E+09 | 0.248892E+09 | 0.00 | 3595203.12 | 12728926.95 | 58299500.84 | 0.332414E+09 | 0.00 | 0.58 |
May | 0.174231E+09 | 0.429251E+09 | 0.00 | 1620460.39 | 9805724.13 | 3315985.80 | 82020248.93 | 0.00 | 0.45 |
June | 55252206.30 | 0.125737E+10 | 0.00 | 358213.59 | 21236997.70 | 0.00 | 22667644.21 | 0.00 | 0.46 |
July | 18618605.01 | 0.157479E+10 | 0.00 | 184683.78 | 39259006.24 | 0.00 | 17863835.88 | 0.00 | 0.46 |
August | 18510589.28 | 0.168790E+10 | 0.00 | 266374.43 | 28443160.62 | 0.00 | 18507885.86 | 0.00 | 0.55 |
September | 37274844.01 | 0.125452E+10 | 0.00 | 2085039.05 | 62827188.69 | 0.00 | 96752695.54 | 0.00 | 0.63 |
October | 0.257353E+09 | 0.301376E+09 | 0.00 | 7945246.68 | 5048405.89 | 0.116798E+09 | 0.144622E+10 | 0.00 | 0.98 |
November | 0.386039E+09 | 2620371.92 | 0.00 | 10809685.22 | 3009756.59 | 0.158581E+09 | 0.282902E+10 | 0.00 | 1.16 |
December | 0.724961E+09 | 257495.19 | 0.00 | 7529758.24 | 41592.70 | 0.375501E+09 | 0.201961E+10 | 0.00 | 0.83 |
Annual Sum or Average | 0.416789E+10 | 0.676208E+10 | 0.00 | 50975449.12 | 0.183872E+09 | 0.167608E+10 | 0.113247E+11 | 0.00 | 0.70 |
Minimum of Months | 18510589.28 | 0.00 | 0.00 | 184683.78 | 41592.70 | 0.00 | 17863835.88 | 0.00 | 0.45 |
Maximum of Months | 0.100778E+10 | 0.168790E+10 | 0.00 | 10809685.22 | 62827188.69 | 0.375501E+09 | 0.282902E+10 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.538781E+09 | 304395.65 | 0.00 | 2513629.11 | 782189.44 | 3680376.70 | 0.560039E+09 | 0.00 | 0.60 |
February | 0.763173E+09 | 0.00 | 0.00 | 1195830.97 | 228236.67 | 2284692.85 | 0.589668E+09 | 0.00 | 0.53 |
March | 0.538074E+09 | 2121931.43 | 0.00 | 2108783.12 | 0.00 | 210645.49 | 0.488885E+09 | 0.00 | 0.51 |
April | 0.132536E+09 | 0.168924E+09 | 0.00 | 2816450.92 | 2425102.17 | 0.00 | 0.374110E+09 | 0.00 | 0.66 |
May | 62588220.11 | 0.344321E+09 | 0.00 | 1454817.48 | 2114555.13 | 0.00 | 0.140071E+09 | 0.00 | 0.54 |
June | 11783742.48 | 0.945219E+09 | 0.00 | 458930.73 | 6535564.43 | 0.00 | 51817034.52 | 0.00 | 0.54 |
July | 7677072.43 | 0.101344E+10 | 0.00 | 181886.47 | 17365537.36 | 0.00 | 21529188.79 | 0.00 | 0.47 |
August | 5638389.67 | 0.100502E+10 | 0.00 | 270919.72 | 10662160.17 | 0.00 | 25347992.21 | 0.00 | 0.54 |
September | 8369406.29 | 0.695816E+09 | 0.00 | 1199935.98 | 43273216.17 | 0.00 | 85785093.33 | 0.00 | 0.59 |
October | 0.143659E+09 | 0.142771E+09 | 0.00 | 3694829.65 | 4642061.26 | 0.00 | 0.775508E+09 | 0.00 | 0.75 |
November | 0.332321E+09 | 2186697.29 | 0.00 | 4202821.96 | 1644999.59 | 0.00 | 0.113957E+10 | 0.00 | 0.79 |
December | 0.692055E+09 | 51032.27 | 0.00 | 1770119.70 | 35080.05 | 4420804.92 | 0.540729E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.323666E+10 | 0.432017E+10 | 0.00 | 21868955.82 | 89708702.44 | 10596519.96 | 0.479306E+10 | 0.00 | 0.58 |
Minimum of Months | 5638389.67 | 0.00 | 0.00 | 181886.47 | 0.00 | 0.00 | 21529188.79 | 0.00 | 0.46 |
Maximum of Months | 0.763173E+09 | 0.101344E+10 | 0.00 | 4202821.96 | 43273216.17 | 4420804.92 | 0.113957E+10 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105368E+10 | 0.00 | 0.00 | 1278547.56 | 1991214.89 | 18686116.79 | 0.337841E+09 | 0.00 | 0.42 |
February | 0.130743E+10 | 0.00 | 0.00 | 638645.49 | 412430.19 | 8676269.68 | 0.431745E+09 | 0.00 | 0.42 |
March | 0.951667E+09 | 730095.40 | 0.00 | 2525743.48 | 113690.50 | 8599826.36 | 0.678024E+09 | 0.00 | 0.49 |
April | 0.244277E+09 | 0.149460E+09 | 0.00 | 3325932.93 | 12566786.36 | 0.00 | 0.432013E+09 | 0.00 | 0.49 |
May | 0.104114E+09 | 0.354613E+09 | 0.00 | 2832448.83 | 11005774.93 | 0.00 | 0.246869E+09 | 0.00 | 0.49 |
June | 26764137.97 | 0.121308E+10 | 0.00 | 814696.16 | 14465200.71 | 0.00 | 86756120.10 | 0.00 | 0.50 |
July | 13289359.30 | 0.134867E+10 | 0.00 | 233889.48 | 32395620.72 | 0.00 | 28553653.34 | 0.00 | 0.44 |
August | 15932719.93 | 0.122558E+10 | 0.00 | 252766.07 | 22077965.29 | 0.00 | 21513831.17 | 0.00 | 0.47 |
September | 30302351.79 | 0.800235E+09 | 0.00 | 1524039.17 | 50122627.00 | 0.00 | 75820878.69 | 0.00 | 0.46 |
October | 0.448733E+09 | 0.161946E+09 | 0.00 | 2527576.21 | 6210768.11 | 0.00 | 0.496089E+09 | 0.00 | 0.47 |
November | 0.912833E+09 | 1255353.44 | 0.00 | 2223546.41 | 4117585.15 | 5651329.60 | 0.584777E+09 | 0.00 | 0.46 |
December | 0.153759E+10 | 0.00 | 0.00 | 340709.84 | 229358.04 | 89835737.32 | 0.143379E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.664662E+10 | 0.525557E+10 | 0.00 | 18518541.63 | 0.155709E+09 | 0.131449E+09 | 0.356338E+10 | 0.00 | 0.46 |
Minimum of Months | 13289359.30 | 0.00 | 0.00 | 233889.48 | 113690.50 | 0.00 | 21513831.17 | 0.00 | 0.39 |
Maximum of Months | 0.153759E+10 | 0.134867E+10 | 0.00 | 3325932.93 | 50122627.00 | 89835737.32 | 0.678024E+09 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.409965E+09 | 261858.21 | 0.00 | 2618213.53 | 1002084.73 | 7289158.52 | 0.860970E+09 | 0.00 | 0.59 |
February | 0.481269E+09 | 0.00 | 0.00 | 1910267.86 | 261378.93 | 2510211.73 | 0.957578E+09 | 0.00 | 0.53 |
March | 0.360230E+09 | 507213.78 | 0.00 | 3771925.19 | 72051.71 | 3542557.51 | 0.121742E+10 | 0.00 | 0.75 |
April | 90236659.23 | 0.131245E+09 | 0.00 | 5433968.35 | 7890317.86 | 0.00 | 0.896514E+09 | 0.00 | 0.97 |
May | 53308028.49 | 0.275521E+09 | 0.00 | 4243762.99 | 6500176.68 | 0.00 | 0.427888E+09 | 0.00 | 0.86 |
June | 13583323.93 | 0.962615E+09 | 0.00 | 954197.90 | 7411016.39 | 0.00 | 94028150.45 | 0.00 | 0.70 |
July | 5728642.13 | 0.115076E+10 | 0.00 | 310160.31 | 17051632.80 | 0.00 | 35437257.16 | 0.00 | 0.61 |
August | 8922377.15 | 0.107775E+10 | 0.00 | 309033.23 | 11864297.56 | 0.00 | 24820470.37 | 0.00 | 0.66 |
September | 18402467.62 | 0.708949E+09 | 0.00 | 1470293.22 | 22651204.45 | 0.00 | 78823907.32 | 0.00 | 0.66 |
October | 0.172152E+09 | 0.138641E+09 | 0.00 | 3661723.71 | 3420137.94 | 0.00 | 0.907510E+09 | 0.00 | 0.79 |
November | 0.378437E+09 | 936866.81 | 0.00 | 3268359.19 | 2602407.26 | 407947.17 | 0.975571E+09 | 0.00 | 0.66 |
December | 0.600787E+09 | 51370.75 | 0.00 | 1346306.00 | 33394.70 | 28874820.64 | 0.573477E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.259302E+10 | 0.444724E+10 | 0.00 | 29298211.47 | 80760101.02 | 42624695.57 | 0.705004E+10 | 0.00 | 0.68 |
Minimum of Months | 5728642.13 | 0.00 | 0.00 | 309033.23 | 33394.70 | 0.00 | 24820470.37 | 0.00 | 0.42 |
Maximum of Months | 0.600787E+09 | 0.115076E+10 | 0.00 | 5433968.35 | 22651204.45 | 28874820.64 | 0.121742E+10 | 0.00 | 0.97 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.445570E+09 | 2914945.74 | 0.00 | 12705868.64 | 1320543.41 | 9346582.31 | 0.329011E+10 | 0.00 | 1.34 |
February | 0.690687E+09 | 0.00 | 0.00 | 7043121.50 | 413213.70 | 2936412.92 | 0.344438E+10 | 0.00 | 0.99 |
March | 0.613930E+09 | 1184608.84 | 0.00 | 7486489.38 | 113906.48 | 6235546.47 | 0.217870E+10 | 0.00 | 0.92 |
April | 0.234352E+09 | 0.242960E+09 | 0.00 | 4963293.38 | 12473795.98 | 0.00 | 0.611133E+09 | 0.00 | 0.68 |
May | 0.113906E+09 | 0.397273E+09 | 0.00 | 2749079.96 | 11026683.05 | 0.00 | 0.209485E+09 | 0.00 | 0.51 |
June | 37513777.45 | 0.118263E+10 | 0.00 | 604161.43 | 16479868.46 | 0.00 | 59166613.66 | 0.00 | 0.47 |
July | 16019954.77 | 0.136504E+10 | 0.00 | 199418.34 | 33211085.95 | 0.00 | 20113718.83 | 0.00 | 0.44 |
August | 16032516.39 | 0.143486E+10 | 0.00 | 252077.61 | 19626715.47 | 0.00 | 20582715.99 | 0.00 | 0.53 |
September | 29081581.03 | 0.111410E+10 | 0.00 | 2119234.89 | 42890419.28 | 0.00 | 92481463.15 | 0.00 | 0.60 |
October | 0.261476E+09 | 0.284683E+09 | 0.00 | 7915204.56 | 3324329.49 | 0.00 | 0.174262E+10 | 0.00 | 1.01 |
November | 0.424280E+09 | 2396344.20 | 0.00 | 11790918.71 | 3829775.55 | 135517.56 | 0.329728E+10 | 0.00 | 1.24 |
December | 0.738896E+09 | 159887.98 | 0.00 | 10454806.31 | 156264.13 | 26407190.18 | 0.370584E+10 | 0.00 | 1.16 |
Annual Sum or Average | 0.362174E+10 | 0.602821E+10 | 0.00 | 68283674.71 | 0.144867E+09 | 45061249.44 | 0.186719E+11 | 0.00 | 0.82 |
Minimum of Months | 16019954.77 | 0.00 | 0.00 | 199418.34 | 113906.48 | 0.00 | 20113718.83 | 0.00 | 0.44 |
Maximum of Months | 0.738896E+09 | 0.143486E+10 | 0.00 | 12705868.64 | 42890419.28 | 26407190.18 | 0.370584E+10 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.533819E+09 | 1180921.25 | 0.00 | 2899178.43 | 834735.11 | 10708233.70 | 0.669094E+09 | 0.00 | 0.67 |
February | 0.686671E+09 | 0.00 | 0.00 | 1811187.24 | 261198.52 | 4218477.30 | 0.897503E+09 | 0.00 | 0.63 |
March | 0.499575E+09 | 914292.30 | 0.00 | 3384281.29 | 0.00 | 4087999.98 | 0.883574E+09 | 0.00 | 0.76 |
April | 0.146255E+09 | 0.197599E+09 | 0.00 | 3355048.39 | 1922379.07 | 0.00 | 0.410119E+09 | 0.00 | 0.76 |
May | 68199185.14 | 0.411404E+09 | 0.00 | 2004167.05 | 1987156.10 | 0.00 | 0.144899E+09 | 0.00 | 0.66 |
June | 17155048.72 | 0.115183E+10 | 0.00 | 461882.73 | 6213750.37 | 0.00 | 48677146.91 | 0.00 | 0.66 |
July | 8337808.86 | 0.109562E+10 | 0.00 | 147336.02 | 13594813.70 | 0.00 | 16338099.60 | 0.00 | 0.54 |
August | 9161511.35 | 0.102866E+10 | 0.00 | 175059.96 | 8885175.13 | 0.00 | 14850107.19 | 0.00 | 0.60 |
September | 18629063.29 | 0.676295E+09 | 0.00 | 1223376.72 | 26886490.70 | 0.00 | 55337054.85 | 0.00 | 0.58 |
October | 0.234850E+09 | 0.142253E+09 | 0.00 | 3196963.50 | 1992000.73 | 0.00 | 0.598289E+09 | 0.00 | 0.69 |
November | 0.454917E+09 | 1695758.47 | 0.00 | 3498260.06 | 2472484.91 | 2050736.07 | 0.906588E+09 | 0.00 | 0.72 |
December | 0.778135E+09 | 37689.80 | 0.00 | 1644465.23 | 118893.61 | 54552220.01 | 0.639194E+09 | 0.00 | 0.56 |
Annual Sum or Average | 0.345571E+10 | 0.470749E+10 | 0.00 | 23801206.62 | 65169077.96 | 75617667.06 | 0.528446E+10 | 0.00 | 0.65 |
Minimum of Months | 8337808.86 | 0.00 | 0.00 | 147336.02 | 0.00 | 0.00 | 14850107.19 | 0.00 | 0.54 |
Maximum of Months | 0.778135E+09 | 0.115183E+10 | 0.00 | 3498260.06 | 26886490.70 | 54552220.01 | 0.906588E+09 | 0.00 | 0.76 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:04
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.193996E+12 | 0.732646E+10 | 0.00 | 0.184786E+12 | 0.580475E+11 |
February | 0.201931E+12 | 0.693293E+10 | 0.00 | 0.190852E+12 | 0.135499E+11 |
March | 0.255463E+12 | 0.756034E+10 | 0.00 | 0.187128E+12 | 0.601550E+11 |
April | 0.301459E+12 | 0.132091E+10 | 0.00 | 0.104099E+12 | 0.171105E+12 |
May | 0.292819E+12 | -821191164.7 | 0.00 | 0.656319E+11 | 0.230369E+12 |
June | 0.298539E+12 | -0.419042E+10 | 0.00 | -0.332041E+10 | 0.319081E+12 |
July | 0.276891E+12 | -0.633064E+10 | 0.00 | -0.366717E+11 | 0.310697E+12 |
August | 0.249382E+12 | -0.518318E+10 | 0.00 | -0.296770E+11 | 0.315741E+12 |
September | 0.215915E+12 | -0.341565E+10 | 0.00 | -0.292119E+11 | 0.263657E+12 |
October | 0.213818E+12 | 0.283648E+10 | 0.00 | 0.135108E+12 | 0.145569E+12 |
November | 0.195711E+12 | 0.668635E+10 | 0.00 | 0.184069E+12 | 0.623759E+11 |
December | 0.161574E+12 | 0.832118E+10 | 0.00 | 0.195527E+12 | 0.314448E+11 |
Annual Sum or Average | 0.285750E+13 | 0.210436E+11 | 0.00 | 0.114832E+13 | 0.198179E+13 |
Minimum of Months | 0.161574E+12 | -0.633064E+10 | 0.00 | -0.366717E+11 | 0.135499E+11 |