Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:31
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 08:32:02
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2147.58 | 431.05 | 431.05 |
Net Site Energy | 2147.58 | 431.05 | 431.05 |
Total Source Energy | 6575.21 | 1319.74 | 1319.74 |
Net Source Energy | 6575.21 | 1319.74 | 1319.74 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 871.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 231.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 168.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 108.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2039.00 | 108.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 871.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 231.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 50.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 168.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 108.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 871.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 231.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 50.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 168.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 108.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 208.68 | 21.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 409.26 | 21.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 208.68 | 21.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 409.26 | 21.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 2038.998 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 2038.998 | 100.00 |
Total On-Site and Utility Electric Sources | 2038.998 | 100.00 |
Total Electricity End Uses | 2038.998 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 2.33 |
Time Setpoint Not Met During Occupied Cooling | 570.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1363.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:31 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.6636 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.6636 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.6636 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 6.6636 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.6636 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:30 | 18-JAN-12:09 | - | - | - | - | - | - | - | - | - | - | 24-APR-11:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 126423.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 42072.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 831.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 23922.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 9530.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 212927.65 | 9530.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 126423.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 7527.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 831.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 23922.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 9530.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 1.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2758.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 733.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 160.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 37.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 532.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 117.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6457.51 | 117.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 553.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 106.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 23.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1296.12 | 23.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 553.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 106.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 23.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1296.12 | 23.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.83 | 0.264539 | 0.225000 | 0.637437 | 0.705438 | 0.500000 | 0.001440 |
CORE_MID VAV BOX COMPONENT | 2.14 | 0.350786 | 0.298000 | 0.636678 | 0.935428 | 0.500000 | 0.001086 |
CORE_TOP VAV BOX COMPONENT | 2.39 | 0.313026 | 0.266000 | 0.636864 | 0.834737 | 0.500000 | 0.001217 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.915033 | 0.172662 | 0.147000 | 0.134510 | 0.460432 | 0.500000 | 0.002207 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.720451 | 0.138832 | 0.118000 | 0.085013 | 0.370219 | 0.500000 | 0.002744 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.02 | 0.155564 | 0.132000 | 0.134060 | 0.414837 | 0.500000 | 0.002449 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.819200 | 0.122089 | 0.104000 | 0.085197 | 0.325570 | 0.500000 | 0.003121 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.781287 | 0.202220 | 0.172000 | 0.134381 | 0.539253 | 0.500000 | 0.001884 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.652114 | 0.153381 | 0.130000 | 0.084775 | 0.409015 | 0.500000 | 0.002484 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.874128 | 0.180742 | 0.154000 | 0.134616 | 0.481979 | 0.500000 | 0.002108 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.691582 | 0.144618 | 0.123000 | 0.085065 | 0.385648 | 0.500000 | 0.002635 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.786786 | 0.200806 | 0.171000 | 0.134540 | 0.535484 | 0.500000 | 0.001897 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.672352 | 0.396704 | 0.500000 | 0.002561 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.885612 | 0.178398 | 0.152000 | 0.134613 | 0.475729 | 0.500000 | 0.002136 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.727557 | 0.137467 | 0.117000 | 0.085124 | 0.366579 | 0.500000 | 0.002772 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 21279.64 |
CORE_MID VAV BOX REHEAT COIL | 21254.29 |
CORE_TOP VAV BOX REHEAT COIL | 21260.48 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 7258.45 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 4741.48 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 7223.60 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 4761.47 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 4486.06 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 2830.05 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 4493.89 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2839.72 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 5218.74 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 3443.08 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 5192.53 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 3457.48 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.92 | 1.08 | 5.83 | 1.08 | 5.47 | 5.47 | 0.300000 | 0.196916 | 5.47 |
PACU_VAV_MID | 2.60 | 1.08 | 5.21 | 1.08 | 4.80 | 4.80 | 0.300000 | 0.224290 | 4.80 |
PACU_VAV_TOP | 2.93 | 1.08 | 5.86 | 1.22 | 5.71 | 5.71 | 0.300000 | 0.213082 | 5.71 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.47 |
PACU_VAV_MID_OA_CONTROLLER | 4.80 |
PACU_VAV_TOP_OA_CONTROLLER | 5.71 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.47 | 125350.97 | 0.726367 | 1.82 | 41779.48 | 0.726367 |
PACU_VAV_MID COOLING COIL | 4.80 | 113454.85 | 0.716264 | 1.60 | 37814.50 | 0.716264 |
PACU_VAV_TOP COOLING COIL | 5.71 | 129741.27 | 0.729724 | 1.90 | 43242.77 | 0.729724 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 0.000000 |
PACU_VAV_MID HEATING COIL | 0.000000 |
PACU_VAV_TOP HEATING COIL | 0.000000 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.47 |
PACU_VAV_MID FAN | 4.80 |
PACU_VAV_TOP FAN | 5.71 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 31.498 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 6 | 0.167 | 1.328 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 6 | 0.167 | 1.313 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.592 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5188 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5277 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3941 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 6 | 0.22034119E-07 | 0.34186667E-09 | 0.51028043E-08 | -0.99966795E-13 |
43 | 5 | -0.15575685E-03 | 0.30726149E-05 | -0.80471308E-04 | 0.50596976E-08 |
44 | 4 | 0.25098773 | 0.15612093E-02 | 0.84928613E-01 | -0.27863917E-04 |
45 | 3 | -6.4488769 | 0.50236036E-01 | -2.0965073 | 0.25009644E-01 |
46 | 2 | 38.172500 | 0.18459162 | 14.265034 | -0.30329881 |
47 | 1 | -78.474946 | 0.85697261E-01 | -28.243456 | 1.0344939 |
48 | 0 | 46.824353 | 0.17727373E-02 | 16.313943 | |
49 | 6 | 0.22220471E-07 | 0.33897870E-09 | 0.51439591E-08 | -0.10094351E-12 |
50 | 5 | -0.15674173E-03 | 0.30417725E-05 | -0.80970714E-04 | 0.51000978E-08 |
51 | 4 | 0.25219758 | 0.15433791E-02 | 0.85360851E-01 | -0.28028645E-04 |
52 | 3 | -6.4729780 | 0.49601353E-01 | -2.1036496 | 0.25127351E-01 |
53 | 2 | 38.252148 | 0.18206636 | 14.294681 | -0.30418501 |
54 | 1 | -78.536155 | 0.84448529E-01 | -28.270134 | 1.0357980 |
55 | 0 | 46.824353 | 0.17453530E-02 | 16.313230 | |
56 | 6 | 0.18845480E-07 | 0.38509844E-09 | 0.43982754E-08 | -0.83379515E-13 |
57 | 5 | -0.13867918E-03 | 0.35672754E-05 | -0.71780061E-04 | 0.43666335E-08 |
58 | 4 | 0.22968634 | 0.18605187E-02 | 0.77334699E-01 | -0.24995801E-04 |
59 | 3 | -6.0237384 | 0.61253070E-01 | -1.9705638 | 0.22935651E-01 |
60 | 2 | 36.766583 | 0.22953206 | 13.740229 | -0.28766105 |
61 | 1 | -77.393480 | 0.10834582 | -27.770672 | 1.0114547 |
62 | 0 | 46.824361 | 0.22782066E-02 | 16.327018 | |
63 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
64 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
65 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
66 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
67 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
68 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
69 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
70 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
71 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
72 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
73 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
74 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
75 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
76 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
77 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
78 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
79 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
80 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
81 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
82 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
83 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
84 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
85 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
86 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
87 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
88 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
89 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
90 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
91 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
92 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
93 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
94 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
95 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
96 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
97 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
98 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
99 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
100 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
101 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
102 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
103 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.504_SHGC_EAST_0.219 | 35 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
2 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 36 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
3 | WINDOW_U_0.504_SHGC_WEST_0.219 | 37 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
4 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 38 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4296E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4635E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.6887E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7167E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4486E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4698E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5578E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5722E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6220E-002 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2028E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2708E-002 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3184E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.2613E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3760E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8099E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0520E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4309E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4714E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.6901E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7253E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4501E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4767E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5576E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5721E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1837E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3527E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9154E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1486E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9954E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9683E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3022E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5557E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8234E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8362E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6164E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6257E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4487E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4522E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9854E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.9904E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4722E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5037E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1032E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1285E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8332E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8508E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5576E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5721E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2493E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2592E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7599E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.7337E-003 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5795E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.7005E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8099E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0520E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4717E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5031E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1025E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1267E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8319E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8460E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5578E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5722E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4071E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0064E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9932E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7376E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2056E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6181E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3022E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5557E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3143E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3387E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0058E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0296E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9549E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9686E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9855E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9905E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.0102E-002 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.0646E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.6112E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.2210E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.7641E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.1035E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.2063E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.4956E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.0542E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2773E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.8020E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.0822E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9057E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9140E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.2406E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.5186E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.5930E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6764E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.0694E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3379E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8837E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.0026E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.2063E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4956E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.3003E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9469E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.9070E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.6904E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.1382E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5793E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2406E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5186E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.0098E-002 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.0641E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.6107E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.2205E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.7635E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.1031E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.2060E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.4955E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.0541E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2771E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.8018E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.0820E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9055E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9138E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.2403E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.5184E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.5931E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6763E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.0695E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3378E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8836E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.0025E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.2060E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4955E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.3003E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9468E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.9069E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.6903E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.1380E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5791E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2403E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5184E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 39301.45807 | 39301.45807 | 2.83306 | 2.83306 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 1079.17480 | 1079.17480 | 4.60736E-002 | 0.42469 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 29671.42959 | 29671.42959 | 2.13650 | 2.13650 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 6802.39227 | 6802.39227 | 0.28450 | 0.42469 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 32937.31543 | 32937.31543 | 2.39422 | 2.39422 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 42.50900 | 1.07813E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 11787.95611 | 11787.95611 | 0.49765 | 0.49765 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 12587.85437 | 12587.85437 | 0.91503 | 0.91503 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 5114.54129 | 5114.54129 | 0.21743 | 0.21743 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9911.04723 | 9911.04723 | 0.72045 | 0.72045 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 40.08400 | 1.07771E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 3340.32872 | 3340.32872 | 0.14203 | 0.14203 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13971.43881 | 13971.43881 | 1.01561 | 1.01561 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 5090.13508 | 5090.13508 | 0.21638 | 0.21638 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11269.53499 | 11269.53499 | 0.81920 | 0.81920 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 3354.33195 | 3354.33195 | 0.14263 | 0.14263 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 10748.08868 | 10748.08868 | 0.78129 | 0.78129 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 2590.21970 | 2590.21970 | 0.10943 | 0.10943 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8971.10317 | 8971.10317 | 0.65211 | 0.65211 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 40.08400 | 1.07771E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 1718.64815 | 1718.64815 | 7.26549E-002 | 7.26549E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 12025.30930 | 12025.30930 | 0.87413 | 0.87413 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 2579.49563 | 2579.49563 | 0.10897 | 0.10897 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9514.06917 | 9514.06917 | 0.69158 | 0.69158 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 41.83000 | 1.07801E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 1725.70374 | 1725.70374 | 7.29574E-002 | 7.29574E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 10823.62622 | 10823.62622 | 0.78679 | 0.78679 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 3686.77765 | 3686.77765 | 0.15633 | 0.15633 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9249.41045 | 9249.41045 | 0.67235 | 0.67235 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 39.59900 | 1.07763E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 2431.72887 | 2431.72887 | 0.10314 | 0.10314 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 12183.17064 | 12183.17064 | 0.88561 | 0.88561 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 3668.36956 | 3668.36956 | 0.15554 | 0.15554 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10008.85871 | 10008.85871 | 0.72756 | 0.72756 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 2441.85031 | 2441.85031 | 0.10357 | 0.10357 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 95750.61 | 5.46566 | 5.46566 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 95.87 | 0.79271 | 0.79271 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 86608.32 | 4.79590 | 4.79590 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 114.08 | 0.94327 | 0.94327 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 98836.97 | 5.70733 | 5.70733 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 115.58 | 1.21613 | 1.21613 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.83306 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26454 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22500 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63744 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70544 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44024E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21279.63761 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.13650 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35079 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29800 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63668 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93543 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08613E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21254.29377 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.39422 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31303 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26600 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63686 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83474 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21715E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21260.47944 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.91503 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17266 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14700 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13451 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46043 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.20662E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7258.45314 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72045 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13883 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11800 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50132E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37022 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.74432E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4741.47524 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.01561 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15556 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13200 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13406 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41484 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.44916E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7223.59922 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81920 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12209 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10400 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51968E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32557 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.12068E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4761.47096 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78129 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20222 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17200 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13438 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53925 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.88409E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4486.06384 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65211 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15338 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47749E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40902 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.48401E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 2830.04778 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.87413 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18074 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15400 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13462 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48198 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.10798E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4493.88791 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69158 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14462 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12300 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50646E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38565 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.63453E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 2839.72117 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78679 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20081 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17100 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13454 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53548 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.89735E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5218.73651 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67235 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39670 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.56110E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 3443.08003 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88561 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17840 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15200 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13461 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47573 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.13567E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5192.52790 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72756 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13747 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11700 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51241E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36658 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.77157E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 3457.48074 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.91608 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07627 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.83217 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07627 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.46566 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.46566 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.19692 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.60441 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07567 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.20881 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07567 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.79590 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.79590 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.22429 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.93226 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07564 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.86452 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 1.21613 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.70733 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.70733 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.21308 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.46566 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.79590 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.70733 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.46566 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.46566 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 125350.97322 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.72637 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.82170 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 41779.47937 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.72637 |
152 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.46566 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.79590 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.79590 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 113454.85177 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.71626 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.59847 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 37814.50209 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.71626 |
161 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.79590 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.70733 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.70733 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 129741.27197 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.72972 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.90225 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 43242.76595 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.72972 |
170 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.70733 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 124823.18 | 425914.36 | 11.49 | 2.94 | 3.29 | 3.47 | 3.61 | 10.04 | 11.24 | 11.85 | 12.32 | 6.3186 | 5.0202 | 3.3812 | 1.4190 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 113093.95 | 385892.58 | 11.55 | 2.95 | 3.31 | 3.49 | 3.62 | 10.08 | 11.30 | 11.92 | 12.36 | 5.5444 | 4.4064 | 2.9637 | 1.2559 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 129156.14 | 440699.04 | 11.47 | 2.94 | 3.29 | 3.47 | 3.61 | 10.03 | 11.22 | 11.82 | 12.31 | 6.5980 | 5.2526 | 3.5335 | 1.4764 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 7.8672442615E-002 | 0.1626707494 | Pass | Pass | 7.0518488916E-002 | 0.2546215966 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.3691127459E-002 | 4.8722298144E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.7113518509E-002 | 2.0813169438E-002 | Pass | Pass | 0.3017146138 | 1.9199726923 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.6206758198E-002 | 2.2105667124E-002 | Pass | Pass | 0.3455437717 | 1.5408357590 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.8146744069E-002 | 0.1124815629 | Pass | Pass | 1.5381033131E-002 | 0.1233759570 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 2.3551152898E-002 | 1.3311055895E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.3735741754E-002 | 2.7860980240E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.6740479529E-002 | 2.6274983336E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.2415773782E-002 | 5.6130194351E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.5160302318E-002 | 4.5462646029E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 7.9492030289E-002 | 0.1264162348 | Pass | Pass | 7.0092494550E-002 | 0.2544038447 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.2747401430E-002 | 0.1281444161 | Pass | Pass | 7.0127737140E-002 | 0.2545184685 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 9.8494323901E-002 | 0.1676892005 | Pass | Pass | 0.1049899891 | 0.3981934842 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.1732498589E-002 | 0.1396624217 | Pass | Pass | 6.9487757157E-002 | 0.2525151398 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.5292581812E-002 | 9.2895689150E-002 | Pass | Pass | 1.4913841196E-002 | 0.1213658435 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.9054126745E-002 | 9.2693160011E-002 | Pass | Pass | 1.4916992320E-002 | 0.1213776293 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 8.6760060441E-002 | 0.1223166286 | Pass | Pass | 1.4290049551E-002 | 0.1187100194 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 7.1186602434E-002 | 0.1027927985 | Pass | Pass | 1.4688220522E-002 | 0.1204090720 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2120.93 | -121.8 | 0.00 | -1057.7 | 3981.17 | 4922.64 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.219 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.219 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.219 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.504_SHGC_EAST_0.219 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.504_SHGC_EAST_0.219 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.504_SHGC_WEST_0.219 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.504_SHGC_WEST_0.219 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.219 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.219 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.219 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.865 | 0.220 | 0.242 | |||||||||||||||||
North Total or Average | 195.79 | 2.865 | 0.220 | 0.242 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.865 | 0.220 | 0.242 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.63 | 0.0000 | Y | 6.65 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.57 | 0.0000 | Y | 4.20 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.38 | 0.0000 | Y | 6.58 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.55 | 0.0000 | Y | 4.20 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.58 | 0.0000 | Y | 6.63 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.54 | 0.0000 | Y | 4.19 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.35 | 0.0000 | Y | 6.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.51 | 0.0000 | Y | 4.19 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.63 | 0.0000 | Y | 6.65 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.57 | 0.0000 | Y | 4.20 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.38 | 0.0000 | Y | 6.58 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.55 | 0.0000 | Y | 4.20 |
Interior Lighting Total | 6.6636 | 4982.19 | 33199.39 | 231.63 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 41.85 | 41.85 | 4.43 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.85 | 62.85 | 4.81 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.85 | 46.68 | 41.32 | |
Exterior Lighting Total | 5686.19 | 50.55 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 125350.97 | 91050.80 | 34300.17 | 0.73 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 113454.85 | 81263.65 | 32191.20 | 0.72 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 129741.27 | 94675.28 | 35065.99 | 0.73 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 124823.2 | 2.94 | 10.04 | N/A | N/A | 11.49 | |
PACU_VAV_MID COOLING COIL | 113094.0 | 2.95 | 10.08 | N/A | N/A | 11.55 | |
PACU_VAV_TOP COOLING COIL | 129156.1 | 2.94 | 10.03 | N/A | N/A | 11.47 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 21279.64 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 21254.29 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 21260.48 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7258.45 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4741.48 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7223.60 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4761.47 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4486.06 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 2830.05 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4493.89 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 2839.72 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5218.74 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3443.08 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5192.53 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3457.48 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 0.00 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 0.00 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 0.00 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.47 | 11887.20 | 2174.89 | 1.00 | 1.14 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.80 | 10498.29 | 2189.01 | 1.00 | 1.14 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.71 | 12412.81 | 2174.89 | 1.00 | 1.13 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 124823.18 | 2.94 | 10.04 | 11.49 | 6.3186 | 3.29 | 11.24 | 5.0202 | 3.47 | 11.85 | 3.3812 | 3.61 | 12.32 | 1.4190 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 113093.95 | 2.95 | 10.08 | 11.55 | 5.5444 | 3.31 | 11.30 | 4.4064 | 3.49 | 11.92 | 2.9637 | 3.62 | 12.36 | 1.2559 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 129156.14 | 2.94 | 10.03 | 11.47 | 6.5980 | 3.29 | 11.22 | 5.2526 | 3.47 | 11.82 | 3.5335 | 3.61 | 12.31 | 1.4764 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 39301.46 | 39301.46 | 39.96 | 2.833 | 2.833 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00881 | 35.62 | 0.01077 | 0.425 | 0.00 |
CORE_MID | 29671.43 | 29671.43 | 30.17 | 2.137 | 2.137 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 35.62 | 0.01077 | 0.425 | 0.00 |
CORE_TOP | 32937.32 | 32937.32 | 33.49 | 2.394 | 2.394 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 24.00 | 24.00 | 0.00886 | 42.51 | 0.01078 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 12587.85 | 12587.85 | 60.71 | 0.915 | 0.915 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00878 | 42.70 | 0.01078 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9911.05 | 9911.05 | 75.51 | 0.720 | 0.720 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 24.00 | 24.00 | 0.00873 | 40.08 | 0.01078 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13971.44 | 13971.44 | 67.38 | 1.016 | 1.016 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00875 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11269.53 | 11269.53 | 85.86 | 0.819 | 0.819 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00870 | 41.96 | 0.01078 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 10748.09 | 10748.09 | 51.84 | 0.781 | 0.781 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00878 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8971.10 | 8971.10 | 68.34 | 0.652 | 0.652 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 24.00 | 24.00 | 0.00872 | 40.08 | 0.01078 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12025.31 | 12025.31 | 58.00 | 0.874 | 0.874 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00875 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9514.07 | 9514.07 | 72.49 | 0.692 | 0.692 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00871 | 41.83 | 0.01078 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 10823.63 | 10823.63 | 52.20 | 0.787 | 0.787 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00881 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9249.41 | 9249.41 | 70.47 | 0.672 | 0.672 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 24.00 | 24.00 | 0.00873 | 39.60 | 0.01078 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12183.17 | 12183.17 | 58.76 | 0.886 | 0.886 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00877 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10008.86 | 10008.86 | 76.26 | 0.728 | 0.728 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00871 | 41.96 | 0.01078 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 1079.17 | 1079.17 | 1.10 | 0.046 | 0.425 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00810 | 12.70 | 0.00915 | 0.425 | 0.00 |
CORE_MID | 6802.39 | 6802.39 | 6.92 | 0.284 | 0.425 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 0.425 | 0.00 |
CORE_TOP | 11787.96 | 11787.96 | 11.99 | 0.498 | 0.498 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 5114.54 | 5114.54 | 24.67 | 0.217 | 0.217 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00823 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 3340.33 | 3340.33 | 25.45 | 0.142 | 0.142 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00823 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 5090.14 | 5090.14 | 24.55 | 0.216 | 0.216 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00823 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 3354.33 | 3354.33 | 25.56 | 0.143 | 0.143 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00823 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 2590.22 | 2590.22 | 12.49 | 0.109 | 0.109 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00829 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 1718.65 | 1718.65 | 13.09 | 0.073 | 0.073 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00829 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 2579.50 | 2579.50 | 12.44 | 0.109 | 0.109 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00829 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 1725.70 | 1725.70 | 13.15 | 0.073 | 0.073 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00829 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 3686.78 | 3686.78 | 17.78 | 0.156 | 0.156 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00829 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 2431.73 | 2431.73 | 18.53 | 0.103 | 0.103 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00829 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 3668.37 | 3668.37 | 17.69 | 0.156 | 0.156 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00829 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 2441.85 | 2441.85 | 18.60 | 0.104 | 0.104 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00829 | 12.70 | 0.00915 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.47 | 5.47 | 0.79 | 0.79 | 5.4657 | 1.0763 | 5.4657 | 0.1969 | 0.3000 |
PACU_VAV_MID | 4.80 | 4.80 | 0.94 | 0.94 | 4.7959 | 1.0757 | 4.7959 | 0.2243 | 0.3000 |
PACU_VAV_TOP | 5.71 | 5.71 | 1.22 | 1.22 | 5.7073 | 1.2161 | 5.7073 | 0.2131 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 21279.638 | 21279.638 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21279.64 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00810493 | 52.3621 | 1079.17 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 21254.294 | 21254.294 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21254.29 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 6802.39 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 21260.479 | 21260.479 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21260.48 | 16613.09 | 0.497650 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 11787.96 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 7258.453 | 7258.453 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7258.45 | 7258.45 | 0.217429 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00823014 | 53.1586 | 5114.54 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 4741.475 | 4741.475 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4741.48 | 4741.48 | 0.142032 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00823014 | 53.1585 | 3340.33 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 7223.599 | 7223.599 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7223.60 | 7223.60 | 0.216385 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00823158 | 53.1677 | 5090.14 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 4761.471 | 4761.471 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4761.47 | 4761.47 | 0.142631 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00822885 | 53.1503 | 3354.33 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 4486.064 | 4486.064 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4486.06 | 3652.95 | 0.109425 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00828857 | 53.5316 | 2590.22 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 2830.048 | 2830.048 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 2830.05 | 2425.45 | 0.072655 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00829105 | 53.5473 | 1718.65 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 4493.888 | 4493.888 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4493.89 | 3637.60 | 0.108965 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00828950 | 53.5375 | 2579.50 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 2839.721 | 2839.721 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 2839.72 | 2435.54 | 0.072957 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00829008 | 53.5412 | 1725.70 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 5218.737 | 5218.737 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5218.74 | 5218.74 | 0.156329 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00829090 | 53.5460 | 3686.78 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 3443.080 | 3443.080 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3443.08 | 3443.08 | 0.103138 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00829071 | 53.5447 | 2431.73 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 5192.528 | 5192.528 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5192.53 | 5192.53 | 0.155544 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00829240 | 53.5555 | 3668.37 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 3457.481 | 3457.481 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3457.48 | 3457.48 | 0.103570 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00828941 | 53.5364 | 2441.85 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 125350.973 | 91050.801 | 5.465659 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 115767.71 | 105054.84 | 5.465659 | 27.29 | 18.05 | 0.00914026 | 11.03 | 11.03 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 17.4929 | 24.00 | 0.00879212 | 47.2880 | 75172.21 | 0.00 | 129253.68 | 92507.15 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 0.00 | 0.00 | 1.639698 | 16.16 | 13.68 | 0.00874267 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 58.3095 | 21.00 | 0.00822919 | 53.1534 | 9527.61 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 113454.852 | 81263.652 | 4.795904 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 105440.88 | 94690.64 | 4.795904 | 27.75 | 18.28 | 0.00923362 | 11.02 | 11.02 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 19.9358 | 24.00 | 0.00884747 | 47.5817 | 65886.22 | 0.00 | 116987.18 | 82603.45 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 1.438771 | 15.40 | 13.45 | 0.00882017 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 66.4525 | 21.00 | 0.00818792 | 52.8901 | 19031.12 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 129741.272 | 94675.278 | 5.707330 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 119769.48 | 108722.90 | 5.707330 | 27.14 | 17.99 | 0.00913180 | 11.03 | 11.03 | 0.00850000 | 42.70 | 0.01078164 | 23.83 | 16.7521 | 24.00 | 0.00879932 | 47.3264 | 78420.86 | 0.00 | 133780.67 | 96206.46 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 1.712199 | 16.37 | 13.69 | 0.00866885 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 55.8405 | 21.00 | 0.00806064 | 52.0793 | 20607.66 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 21279.638 | 21279.638 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21279.64 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21279.64 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.93 | 0.00810493 | 21.00 | 0.00810493 | 52.3621 | 1079.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 21254.294 | 21254.294 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21254.29 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21254.29 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.58 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 6802.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 21260.479 | 21260.479 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21260.48 | 16613.09 | 1.0000 | 0.59896864 | 0.497650 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21260.48 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 11787.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 7258.453 | 7258.453 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7258.45 | 7258.45 | 1.0000 | 0.26169644 | 0.217429 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7258.45 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00823014 | 21.00 | 0.00823014 | 53.1586 | 5114.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4741.475 | 4741.475 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4741.48 | 4741.48 | 1.0000 | 0.17094926 | 0.142032 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4741.48 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00823014 | 21.00 | 0.00823014 | 53.1585 | 3340.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 7223.599 | 7223.599 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7223.60 | 7223.60 | 1.0000 | 0.26043982 | 0.216385 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7223.60 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00823158 | 21.00 | 0.00823158 | 53.1677 | 5090.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4761.471 | 4761.471 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4761.47 | 4761.47 | 1.0000 | 0.17167019 | 0.142631 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4761.47 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00822885 | 21.00 | 0.00822885 | 53.1503 | 3354.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 4486.064 | 4486.064 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4486.06 | 3652.95 | 1.0000 | 0.13170351 | 0.109425 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4486.06 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00828857 | 21.00 | 0.00828857 | 53.5316 | 2590.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 2830.048 | 2830.048 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 2830.05 | 2425.45 | 1.0000 | 0.08744713 | 0.072655 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2830.05 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00829105 | 21.00 | 0.00829105 | 53.5473 | 1718.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 4493.888 | 4493.888 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4493.89 | 3637.60 | 1.0000 | 0.13114997 | 0.108965 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4493.89 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00828950 | 21.00 | 0.00828950 | 53.5375 | 2579.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 2839.721 | 2839.721 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 2839.72 | 2435.54 | 1.0000 | 0.08781117 | 0.072957 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2839.72 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00829008 | 21.00 | 0.00829008 | 53.5412 | 1725.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5218.737 | 5218.737 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5218.74 | 5218.74 | 1.0000 | 0.18815645 | 0.156329 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5218.74 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00829090 | 21.00 | 0.00829090 | 53.5460 | 3686.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 3443.080 | 3443.080 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3443.08 | 3443.08 | 1.0000 | 0.12413689 | 0.103138 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3443.08 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00829071 | 21.00 | 0.00829071 | 53.5447 | 2431.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 5192.528 | 5192.528 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5192.53 | 5192.53 | 1.0000 | 0.18721152 | 0.155544 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5192.53 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00829240 | 21.00 | 0.00829240 | 53.5555 | 3668.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 3457.481 | 3457.481 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3457.48 | 3457.48 | 1.0000 | 0.12465609 | 0.103570 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3457.48 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00828941 | 21.00 | 0.00828941 | 53.5364 | 2441.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 125350.973 | 91050.801 | 5.465659 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.8313 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.465659 | 6.57844008 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 115767.71 | 105054.84 | 0.9235 | 6.57844008 | 5.465659 | 27.29 | 18.05 | 0.00914026 | 50743.4 | 11.03 | 11.03 | 0.00850000 | 32517.3 | -999.0 | -999.00 | -999.00 | -999.00 | 11887.199 | 103880.51 | 42.80 | 0.01078182 | 23.86 | 0.95610000 | 17.4929 | 24.00 | 0.00879212 | 24.00 | 0.00879212 | 47.2880 | 75172.21 | 0.00 | 129253.68 | 92507.15 | 6.31864143 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.33 | 12.31 | 0.00890450 | 34866.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.465659 | 6.57844008 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 0.00 | 0.00 | 1.0000 | 1.97353202 | 1.639698 | 16.16 | 13.68 | 0.00874267 | 38368.4 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 0.95610000 | 58.3095 | 21.01 | 0.00816814 | 21.00 | 0.00822919 | 53.1534 | 9527.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 113454.852 | 81263.652 | 4.795904 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.0048 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.795904 | 5.77232659 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | Sensible | 105440.88 | 94690.64 | 0.9294 | 5.77232659 | 4.795904 | 27.75 | 18.28 | 0.00923362 | 51455.4 | 11.02 | 11.02 | 0.00850000 | 32505.9 | -999.0 | -999.00 | -999.00 | -999.00 | 10498.288 | 94942.59 | 42.80 | 0.01078182 | 23.86 | 0.95610000 | 19.9358 | 24.00 | 0.00884747 | 24.00 | 0.00884747 | 47.5817 | 65886.22 | 0.00 | 116987.18 | 82603.45 | 5.54436332 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.08 | 12.05 | 0.00875317 | 34222.2 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.795904 | 5.77232659 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 1.73169798 | 1.438771 | 15.40 | 13.45 | 0.00882017 | 37780.9 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 0.95610000 | 66.4525 | 20.73 | 0.00815999 | 21.00 | 0.00818792 | 52.8901 | 19031.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 129741.272 | 94675.278 | 5.707330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.8156 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.707330 | 6.86931373 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | Sensible | 119769.48 | 108722.90 | 0.9231 | 6.86931373 | 5.707330 | 27.14 | 17.99 | 0.00913180 | 50565.8 | 11.03 | 11.03 | 0.00850000 | 32517.3 | -999.0 | -999.00 | -999.00 | -999.00 | 12412.805 | 107356.68 | 42.70 | 0.01078164 | 23.83 | 0.95610000 | 16.7521 | 24.00 | 0.00879932 | 24.00 | 0.00879932 | 47.3264 | 78420.86 | 0.00 | 133780.67 | 96206.46 | 6.59802777 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.39 | 12.38 | 0.00895187 | 35046.5 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.707330 | 6.86931373 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 2.06079412 | 1.712199 | 16.37 | 13.69 | 0.00866885 | 38388.5 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 0.95610000 | 55.8405 | 21.00 | 0.00805608 | 21.00 | 0.00806064 | 52.0793 | 20607.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 5505.33 | 0.00 | 0.00 |
CORE_MID | 4922.50 | 106.33 | 0.00 |
CORE_TOP | 4568.83 | 483.67 | 25.50 |
PERIMETER_TOP_ZN_3 | 4551.17 | 1249.17 | 474.33 |
PERIMETER_TOP_ZN_2 | 4846.67 | 1110.17 | 564.50 |
PERIMETER_TOP_ZN_1 | 4941.83 | 1078.67 | 572.67 |
PERIMETER_TOP_ZN_4 | 4749.00 | 1228.67 | 570.00 |
PERIMETER_BOT_ZN_3 | 4953.83 | 576.67 | 282.33 |
PERIMETER_BOT_ZN_2 | 5263.50 | 553.67 | 414.83 |
PERIMETER_BOT_ZN_1 | 5333.33 | 1271.17 | 1065.00 |
PERIMETER_BOT_ZN_4 | 5212.67 | 603.33 | 426.50 |
PERIMETER_MID_ZN_3 | 4764.83 | 919.50 | 417.33 |
PERIMETER_MID_ZN_2 | 4216.00 | 844.00 | 523.17 |
PERIMETER_MID_ZN_1 | 5153.50 | 791.00 | 516.17 |
PERIMETER_MID_ZN_4 | 4969.00 | 916.83 | 523.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5679.33 | 2179.17 | 1363.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.67 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.17 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 107.50 | 0.00 | 64.67 |
PERIMETER_TOP_ZN_2 | 0.00 | 138.83 | 0.00 | 90.50 |
PERIMETER_TOP_ZN_1 | 0.00 | 134.33 | 0.00 | 89.17 |
PERIMETER_TOP_ZN_4 | 0.00 | 146.00 | 0.00 | 78.33 |
PERIMETER_BOT_ZN_3 | 0.00 | 65.00 | 0.00 | 45.33 |
PERIMETER_BOT_ZN_2 | 0.00 | 116.67 | 0.00 | 80.83 |
PERIMETER_BOT_ZN_1 | 2.33 | 441.33 | 2.33 | 412.50 |
PERIMETER_BOT_ZN_4 | 0.00 | 126.17 | 0.00 | 67.67 |
PERIMETER_MID_ZN_3 | 0.00 | 74.67 | 0.00 | 53.67 |
PERIMETER_MID_ZN_2 | 0.00 | 112.00 | 0.00 | 85.00 |
PERIMETER_MID_ZN_1 | 0.00 | 105.83 | 0.00 | 82.50 |
PERIMETER_MID_ZN_4 | 0.00 | 114.83 | 0.00 | 69.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 2.33 | 694.83 | 2.33 | 570.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.84 | 52.94 | 2698.04 | 0.492 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.84 | 52.94 | 2698.04 | 0.432 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.84 | 52.94 | 2698.04 | 0.430 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.614 | 0.072 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.762 | 0.076 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.757 | 0.072 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.746 | 0.076 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.519 | 0.038 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.650 | 0.040 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.738 | 1.257 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.643 | 0.040 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.610 | 0.060 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.720 | 0.066 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.751 | 0.060 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.746 | 0.063 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.56 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.30 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 8521948.40 | 0.00 | 8521948.40 | 0.00 | 8521948.40 | 13393058.27 | 6699.97 | 639.66 | 1420.37 | 593.25 |
CORE_MID | 7453670.54 | 0.00 | 7453670.54 | 0.00 | 7453670.54 | 13393058.27 | 7587.70 | 721.23 | 451.07 | 509.56 |
CORE_TOP | 7496779.87 | 0.00 | 7496779.87 | 0.00 | 7496779.87 | 13393058.27 | 7593.47 | 892.67 | 273.86 | 568.47 |
PERIMETER_TOP_ZN_3 | 2208934.28 | 0.00 | 2208934.28 | 413457.77 | 2622392.06 | 2823374.22 | 4238.42 | 952.09 | 3569.49 | 568.47 |
PERIMETER_TOP_ZN_2 | 1707407.80 | 0.00 | 1707407.80 | 275636.86 | 1983044.65 | 1787429.43 | 3584.41 | 863.97 | 4311.62 | 568.47 |
PERIMETER_TOP_ZN_1 | 2681062.51 | 0.00 | 2681062.51 | 413457.77 | 3094520.28 | 2823374.22 | 3674.40 | 768.26 | 4317.34 | 568.47 |
PERIMETER_TOP_ZN_4 | 1689845.82 | 0.00 | 1689845.82 | 275636.86 | 1965482.68 | 1787312.18 | 3733.24 | 874.38 | 4152.38 | 568.47 |
PERIMETER_BOT_ZN_3 | 1890807.92 | 0.00 | 1890807.92 | 219835.62 | 2110643.54 | 2823374.22 | 5789.31 | 671.69 | 2299.00 | 593.25 |
PERIMETER_BOT_ZN_2 | 1476525.66 | 0.00 | 1476525.66 | 146556.20 | 1623081.85 | 1787429.43 | 4248.69 | 526.61 | 3984.70 | 593.25 |
PERIMETER_BOT_ZN_1 | 2613079.36 | 0.00 | 2613079.36 | 4198137.27 | 6811216.63 | 2823374.22 | 3917.44 | 667.56 | 4175.01 | 593.25 |
PERIMETER_BOT_ZN_4 | 1474133.81 | 0.00 | 1474133.81 | 146556.20 | 1620690.01 | 1787312.18 | 4392.10 | 614.04 | 3753.86 | 593.25 |
PERIMETER_MID_ZN_3 | 2164805.95 | 0.00 | 2164805.95 | 344173.66 | 2508979.61 | 2823374.22 | 4447.13 | 843.24 | 3469.63 | 509.56 |
PERIMETER_MID_ZN_2 | 1604066.73 | 0.00 | 1604066.73 | 229447.73 | 1833514.46 | 1601953.02 | 3794.90 | 643.26 | 4321.84 | 1418.56 |
PERIMETER_MID_ZN_1 | 2631560.76 | 0.00 | 2631560.76 | 344173.66 | 2975734.42 | 2823374.22 | 3586.18 | 733.60 | 4440.23 | 509.56 |
PERIMETER_MID_ZN_4 | 1667941.08 | 0.00 | 1667941.08 | 229447.73 | 1897388.81 | 1787312.18 | 3889.89 | 764.54 | 4105.58 | 509.56 |
Total Facility | 47282570.51 | 0.00 | 47282570.51 | 7236517.31 | 54519087.82 | 67658168.57 | 8565.36 | 2041.46 | 5285.78 | 1725.44 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3576 | 0.0000 | 0.3576 | 0.0000 | 0.3576 | 0.4247 | 4127.44 | 403.35 | 1412.21 |
CORE_MID | 0.3136 | 0.0000 | 0.3136 | 0.0000 | 0.3136 | 0.4247 | 4944.71 | 549.32 | 448.97 |
CORE_TOP | 0.3122 | 0.0000 | 0.3122 | 0.0000 | 0.3122 | 0.4247 | 4932.18 | 738.17 | 272.65 |
PERIMETER_TOP_ZN_3 | 0.0938 | 0.0000 | 0.0938 | 0.0110 | 0.1048 | 0.0895 | 1773.96 | 731.65 | 3437.39 |
PERIMETER_TOP_ZN_2 | 0.0736 | 0.0000 | 0.0736 | 0.0073 | 0.0809 | 0.0567 | 1084.77 | 702.99 | 4155.24 |
PERIMETER_TOP_ZN_1 | 0.1157 | 0.0000 | 0.1157 | 0.0110 | 0.1267 | 0.0895 | 1118.51 | 650.76 | 4173.73 |
PERIMETER_TOP_ZN_4 | 0.0720 | 0.0000 | 0.0720 | 0.0073 | 0.0793 | 0.0567 | 1342.75 | 645.03 | 3955.22 |
PERIMETER_BOT_ZN_3 | 0.0793 | 0.0000 | 0.0793 | 0.0058 | 0.0851 | 0.0895 | 3278.88 | 433.26 | 2230.86 |
PERIMETER_BOT_ZN_2 | 0.0628 | 0.0000 | 0.0628 | 0.0039 | 0.0667 | 0.0567 | 1695.09 | 394.88 | 3853.03 |
PERIMETER_BOT_ZN_1 | 0.1125 | 0.0000 | 0.1125 | 0.1918 | 0.3043 | 0.0895 | 1528.31 | 355.67 | 4059.01 |
PERIMETER_BOT_ZN_4 | 0.0621 | 0.0000 | 0.0621 | 0.0039 | 0.0660 | 0.0567 | 1986.53 | 387.75 | 3568.72 |
PERIMETER_MID_ZN_3 | 0.0931 | 0.0000 | 0.0931 | 0.0091 | 0.1022 | 0.0895 | 1969.64 | 588.62 | 3384.74 |
PERIMETER_MID_ZN_2 | 0.0696 | 0.0000 | 0.0696 | 0.0064 | 0.0760 | 0.0567 | 1189.66 | 543.49 | 3300.85 |
PERIMETER_MID_ZN_1 | 0.1148 | 0.0000 | 0.1148 | 0.0091 | 0.1239 | 0.0895 | 1141.23 | 455.42 | 4346.35 |
PERIMETER_MID_ZN_4 | 0.0720 | 0.0000 | 0.0720 | 0.0061 | 0.0781 | 0.0567 | 1462.53 | 532.91 | 3947.55 |
Total Facility | 2.0046 | 0.0000 | 2.0046 | 0.2728 | 2.2774 | 2.1513 | 5774.04 | 1516.62 | 4936.07 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 23144149.09 | 0.00 | 23144149.09 | 22614548.33 | 3110.20 | 1.75 | 5648.05 | 593.25 |
PACU_VAV_MID | 22485824.94 | 0.00 | 22485824.94 | 22429071.92 | 3213.86 | 2.08 | 5544.06 | 509.56 |
PACU_VAV_TOP | 22865340.48 | 0.00 | 22865340.48 | 22614548.33 | 3151.15 | 0.94 | 5607.91 | 568.47 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 0.9767 | 0.0000 | 0.9767 | 0.7171 | 870.35 | 0.91 | 5071.74 |
PACU_VAV_MID | 0.9606 | 0.0000 | 0.9606 | 0.7084 | 895.10 | 1.63 | 5046.26 |
PACU_VAV_TOP | 0.9667 | 0.0000 | 0.9667 | 0.7171 | 887.04 | 0.38 | 5055.59 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 400.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5299.78 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 221.58 | 0.00 | 0.00 | 0.00 | 0.00 | 5368.49 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 215.14 | 0.00 | 0.00 | 0.00 | 0.00 | 5441.90 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.1982 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1321 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.0924 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1253 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.0610 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1315 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 943 |
Defaulted Fields | 546 |
Fields with Defaults | 2233 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 2039.00 | 12319.30 | 29-MAY-17:20 | 212927.65 | 10-AUG-15:30 |
Electricity:Building | 937.06 | 12150.69 | 29-MAY-17:20 | 69866.03 | 15-MAR-07:10 |
Electricity:Zone:CORE_BOTTOM | 291.77 | 4006.86 | 01-JAN-00:10 | 23121.21 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 937.06 | 12150.69 | 29-MAY-17:20 | 69866.03 | 15-MAR-07:10 |
InteriorLights:Electricity | 231.63 | 909.35 | 29-MAY-17:20 | 24001.33 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 231.63 | 909.35 | 29-MAY-17:20 | 24001.33 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity | 231.63 | 909.35 | 29-MAY-17:20 | 24001.33 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 231.63 | 909.35 | 29-MAY-17:20 | 24001.33 | 15-MAR-07:10 |
Electricity:Zone:CORE_MID | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 30.98 | 413.68 | 02-APR-17:10 | 2376.87 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.65 | 27.57 | 01-JAN-09:50 | 941.63 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.65 | 27.57 | 01-JAN-09:50 | 941.63 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.60 | 262.93 | 29-MAY-17:10 | 1496.42 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.20 | 17.46 | 01-JAN-08:00 | 587.85 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.20 | 17.46 | 01-JAN-08:00 | 587.85 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 30.91 | 413.67 | 12-MAR-17:10 | 2374.87 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.58 | 27.57 | 01-JAN-08:00 | 939.63 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.58 | 27.57 | 01-JAN-08:00 | 939.63 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.60 | 261.87 | 12-MAR-17:10 | 1508.01 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.20 | 17.46 | 01-JAN-09:40 | 599.44 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.20 | 17.46 | 01-JAN-09:40 | 599.44 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 30.97 | 413.68 | 02-APR-17:10 | 2373.08 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.63 | 27.57 | 01-JAN-09:40 | 937.83 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.63 | 27.57 | 01-JAN-09:40 | 937.83 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.60 | 261.88 | 29-MAY-17:10 | 1494.08 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.19 | 17.46 | 01-JAN-08:00 | 585.51 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.19 | 17.46 | 01-JAN-08:00 | 585.51 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 30.91 | 413.67 | 12-MAR-17:10 | 2370.98 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.57 | 27.57 | 01-JAN-08:00 | 935.74 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.57 | 27.57 | 01-JAN-08:00 | 935.74 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.59 | 261.87 | 12-MAR-17:10 | 1506.19 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.19 | 17.46 | 01-JAN-09:40 | 597.62 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.19 | 17.46 | 01-JAN-09:40 | 597.62 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 30.98 | 413.68 | 02-APR-17:10 | 2376.86 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.65 | 27.57 | 01-JAN-09:50 | 941.62 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.65 | 27.57 | 01-JAN-09:50 | 941.62 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.60 | 262.93 | 29-MAY-17:10 | 1496.41 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.20 | 17.46 | 01-JAN-08:00 | 587.84 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.20 | 17.46 | 01-JAN-08:00 | 587.84 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 30.91 | 413.67 | 12-MAR-17:10 | 2374.86 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.58 | 27.57 | 01-JAN-08:00 | 939.62 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.58 | 27.57 | 01-JAN-08:00 | 939.62 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.60 | 261.87 | 12-MAR-17:10 | 1508.00 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.20 | 17.46 | 01-JAN-09:40 | 599.43 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.20 | 17.46 | 01-JAN-09:40 | 599.43 | 14-MAR-07:10 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 1051.23 | 168.34 | 01-JAN-00:10 | 151176.97 | 10-AUG-15:30 |
ExteriorEquipment:Electricity | 11.69 | 168.34 | 01-JAN-00:10 | 838.82 | 15-MAR-07:20 |
Transformer:ExteriorEquipment:Electricity | 11.69 | 168.34 | 01-JAN-00:10 | 838.82 | 15-MAR-07:20 |
ElectricityPurchased:Facility | 2039.00 | 12319.30 | 29-MAY-17:20 | 212927.65 | 10-AUG-15:30 |
ElectricityPurchased:Plant | 2039.00 | 12319.30 | 29-MAY-17:20 | 212927.65 | 10-AUG-15:30 |
Cogeneration:ElectricityPurchased | 2039.00 | 12319.30 | 29-MAY-17:20 | 212927.65 | 10-AUG-15:30 |
General:Cogeneration:ElectricityPurchased | 2039.00 | 12319.30 | 29-MAY-17:20 | 212927.65 | 10-AUG-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 2039.00 | 12319.30 | 29-MAY-17:20 | 212927.65 | 10-AUG-15:30 |
ElectricityNet:Plant | 2039.00 | 12319.30 | 29-MAY-17:20 | 212927.65 | 10-AUG-15:30 |
Cogeneration:ElectricityNet | 2039.00 | 12319.30 | 29-MAY-17:20 | 212927.65 | 10-AUG-15:30 |
General:Cogeneration:ElectricityNet | 2039.00 | 12319.30 | 29-MAY-17:20 | 212927.65 | 10-AUG-15:30 |
Heating:Electricity | 0.39 | 0.00 | 01-JAN-00:10 | 4493.89 | 02-JAN-07:50 |
General:Heating:Electricity | 0.39 | 0.00 | 01-JAN-00:10 | 4493.89 | 02-JAN-07:50 |
Fans:Electricity | 168.00 | 0.00 | 01-JAN-00:10 | 26704.02 | 05-SEP-15:40 |
General:Fans:Electricity | 168.00 | 0.00 | 01-JAN-00:10 | 26704.02 | 05-SEP-15:40 |
ExteriorLights:Electricity | 50.55 | 0.00 | 01-JAN-07:10 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 50.55 | 0.00 | 01-JAN-07:10 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 871.15 | 0.00 | 01-JAN-00:10 | 126423.00 | 10-AUG-15:30 |
General:Cooling:Electricity | 871.15 | 0.00 | 01-JAN-00:10 | 126423.00 | 10-AUG-15:30 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 27-MAR-12:10 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 27-MAR-12:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 27-MAR-12:10 |
WIRED_LTG_ELECTRICITY | 6.51 | 0.00 | 01-JAN-00:10 | 674.44 | 15-MAR-07:20 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 108.58 | 1886.44 | 04-MAY-12:10 | 9530.11 | 18-JAN-12:10 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 108.58 | 1886.44 | 04-MAY-12:10 | 9530.11 | 18-JAN-12:10 |
WaterSystems:NaturalGas | 108.58 | 1886.44 | 04-MAY-12:10 | 9530.11 | 18-JAN-12:10 |
Water Heater:WaterSystems:NaturalGas | 108.58 | 1886.44 | 04-MAY-12:10 | 9530.11 | 18-JAN-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 5024.73 | 0.00 | 01-JAN-00:10 | 551843.69 | 10-AUG-16:00 |
EnergyTransfer:Building | 1882.76 | 0.00 | 01-JAN-00:10 | 195659.25 | 05-SEP-14:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 324.64 | 0.00 | 01-JAN-00:10 | 29755.07 | 05-SEP-07:20 |
Heating:EnergyTransfer | 2.21 | 0.00 | 01-JAN-00:10 | 4773.08 | 02-JAN-07:40 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 2.21 | 0.00 | 01-JAN-00:10 | 4773.08 | 02-JAN-07:40 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1880.55 | 0.00 | 01-JAN-00:10 | 195659.25 | 05-SEP-14:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 324.64 | 0.00 | 01-JAN-00:10 | 29755.07 | 05-SEP-07:20 |
General:Cooling:EnergyTransfer | 1880.55 | 0.00 | 01-JAN-00:10 | 195659.25 | 05-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 324.64 | 0.00 | 01-JAN-00:10 | 29755.07 | 05-SEP-07:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 87.26 | 0.00 | 01-JAN-00:10 | 14312.23 | 16-AUG-13:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.35 | 0.00 | 01-JAN-00:10 | 2252.50 | 03-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.35 | 0.00 | 01-JAN-00:10 | 2252.50 | 03-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 85.90 | 0.00 | 01-JAN-00:10 | 14312.23 | 16-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 85.90 | 0.00 | 01-JAN-00:10 | 14312.23 | 16-AUG-13:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 52.69 | 0.00 | 01-JAN-00:10 | 7538.55 | 05-SEP-15:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.24 | 0.00 | 01-JAN-00:10 | 1461.31 | 01-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.24 | 0.00 | 01-JAN-00:10 | 1461.31 | 01-JAN-13:40 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 52.46 | 0.00 | 01-JAN-00:10 | 7538.55 | 05-SEP-15:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 52.46 | 0.00 | 01-JAN-00:10 | 7538.55 | 05-SEP-15:20 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 60.08 | 0.00 | 01-JAN-00:10 | 7946.66 | 05-SEP-07:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.36 | 0.00 | 01-JAN-00:10 | 1460.44 | 01-JAN-12:50 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.36 | 0.00 | 01-JAN-00:10 | 1460.44 | 01-JAN-12:50 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 59.71 | 0.00 | 01-JAN-00:10 | 7946.66 | 05-SEP-07:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 59.71 | 0.00 | 01-JAN-00:10 | 7946.66 | 05-SEP-07:10 |
EnergyTransfer:Zone:CORE_MID | 231.53 | 0.00 | 01-JAN-00:10 | 21490.89 | 05-SEP-07:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 231.53 | 0.00 | 01-JAN-00:10 | 21490.89 | 05-SEP-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 231.53 | 0.00 | 01-JAN-00:10 | 21490.89 | 05-SEP-07:20 |
EnergyTransfer:Zone:CORE_TOP | 239.31 | 0.00 | 01-JAN-00:10 | 22627.98 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 239.31 | 0.00 | 01-JAN-00:10 | 22627.98 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 239.31 | 0.00 | 01-JAN-00:10 | 22627.98 | 05-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 78.15 | 0.00 | 01-JAN-00:10 | 9350.96 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 78.15 | 0.00 | 01-JAN-00:10 | 9350.96 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 78.15 | 0.00 | 01-JAN-00:10 | 9350.96 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 61.14 | 0.00 | 01-JAN-00:10 | 7977.04 | 04-AUG-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 61.14 | 0.00 | 01-JAN-00:10 | 7977.04 | 04-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 61.14 | 0.00 | 01-JAN-00:10 | 7977.04 | 04-AUG-10:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 94.22 | 0.00 | 01-JAN-00:10 | 11258.95 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 94.22 | 0.00 | 01-JAN-00:10 | 11258.95 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 94.22 | 0.00 | 01-JAN-00:10 | 11258.95 | 05-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 60.39 | 0.00 | 01-JAN-00:10 | 8185.20 | 09-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 60.39 | 0.00 | 01-JAN-00:10 | 8185.20 | 09-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 60.39 | 0.00 | 01-JAN-00:10 | 8185.20 | 09-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 77.84 | 0.00 | 01-JAN-00:10 | 8999.67 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 77.84 | 0.00 | 01-JAN-00:10 | 8999.67 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 77.84 | 0.00 | 01-JAN-00:10 | 8999.67 | 05-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 61.77 | 0.00 | 01-JAN-00:10 | 7551.70 | 31-JUL-10:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 61.77 | 0.00 | 01-JAN-00:10 | 7551.70 | 31-JUL-10:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 61.77 | 0.00 | 01-JAN-00:10 | 7551.70 | 31-JUL-10:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 116.24 | 0.00 | 01-JAN-00:10 | 18402.45 | 16-AUG-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.25 | 0.00 | 01-JAN-00:10 | 3499.76 | 04-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.25 | 0.00 | 01-JAN-00:10 | 3499.76 | 04-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 115.99 | 0.00 | 01-JAN-00:10 | 18402.45 | 16-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 115.99 | 0.00 | 01-JAN-00:10 | 18402.45 | 16-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 60.86 | 0.00 | 01-JAN-00:10 | 7582.39 | 05-SEP-15:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 60.86 | 0.00 | 01-JAN-00:10 | 7582.39 | 05-SEP-15:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 60.86 | 0.00 | 01-JAN-00:10 | 7582.39 | 05-SEP-15:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 73.92 | 0.00 | 01-JAN-00:10 | 8409.46 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 73.92 | 0.00 | 01-JAN-00:10 | 8409.46 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 73.92 | 0.00 | 01-JAN-00:10 | 8409.46 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 55.82 | 0.00 | 01-JAN-00:10 | 7708.45 | 04-AUG-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 55.82 | 0.00 | 01-JAN-00:10 | 7708.45 | 04-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 55.82 | 0.00 | 01-JAN-00:10 | 7708.45 | 04-AUG-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 89.67 | 0.00 | 01-JAN-00:10 | 10479.06 | 05-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 89.67 | 0.00 | 01-JAN-00:10 | 10479.06 | 05-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 89.67 | 0.00 | 01-JAN-00:10 | 10479.06 | 05-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 57.23 | 0.00 | 01-JAN-00:10 | 7573.22 | 31-JUL-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 57.23 | 0.00 | 01-JAN-00:10 | 7573.22 | 31-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 57.23 | 0.00 | 01-JAN-00:10 | 7573.22 | 31-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 31.56 | 0.00 | 01-JAN-00:10 | 4392.61 | 13-JAN-12:40 |
PlantLoopHeatingDemand:Plant | 31.56 | 0.00 | 01-JAN-00:10 | 4392.61 | 13-JAN-12:40 |
WaterSystems:PlantLoopHeatingDemand | 31.56 | 0.00 | 01-JAN-00:10 | 4392.61 | 13-JAN-12:40 |
General:WaterSystems:PlantLoopHeatingDemand | 31.56 | 0.00 | 01-JAN-00:10 | 4392.61 | 13-JAN-12:40 |
EnergyTransfer:HVAC | 3110.41 | 0.00 | 01-JAN-00:10 | 368742.32 | 10-AUG-16:00 |
HeatingCoils:EnergyTransfer | 0.39 | 0.00 | 01-JAN-00:10 | 4493.89 | 02-JAN-07:50 |
CoolingCoils:EnergyTransfer | 3110.02 | 0.00 | 01-JAN-00:10 | 368742.32 | 10-AUG-16:00 |
EnergyTransfer:Plant | 31.56 | 0.00 | 01-JAN-00:10 | 4392.61 | 13-JAN-12:40 |
WaterSystems:EnergyTransfer | 31.56 | 0.00 | 01-JAN-00:10 | 4392.61 | 13-JAN-12:40 |
WaterUse:WaterSystems:EnergyTransfer | 31.56 | 0.00 | 01-JAN-00:10 | 4392.61 | 13-JAN-12:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -324.642 | 0.000 | 0.000 | 32.654 | 55.599 | 236.167 | 0.000 | 0.000 | 0.000 | 0.221 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_MID | 0.000 | 0.000 | 0.000 | -231.531 | 0.000 | 0.000 | 32.701 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 27.806 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -239.316 | 0.000 | 0.000 | 32.750 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 35.542 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.000 | -78.151 | 0.000 | 0.000 | 6.925 | 6.648 | 24.333 | 36.514 | 0.000 | 2.179 | 10.198 | 0.000 | -8.032 | 0.000 | -0.613 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.000 | -61.143 | 0.000 | 0.000 | 4.369 | 4.199 | 15.404 | 36.848 | 0.000 | 1.434 | 4.421 | 0.000 | -5.104 | 0.000 | -0.428 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.000 | -94.224 | 0.000 | 0.000 | 6.903 | 6.582 | 24.332 | 57.698 | 0.000 | 2.153 | 5.265 | 0.000 | -8.024 | 0.000 | -0.684 | -0.000 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.000 | -60.387 | 0.000 | 0.000 | 4.380 | 4.195 | 15.403 | 37.424 | 0.000 | 1.428 | 3.499 | 0.000 | -5.508 | 0.000 | -0.434 | -0.001 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -77.839 | 0.000 | 0.000 | 6.892 | 6.634 | 24.333 | 36.352 | 0.000 | 1.181 | 11.697 | 0.000 | -8.877 | 0.000 | -0.374 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -61.765 | 0.000 | 0.000 | 4.357 | 4.193 | 15.404 | 36.736 | 0.000 | 0.771 | 6.270 | 0.000 | -5.702 | 0.000 | -0.263 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.254 | -115.990 | 0.000 | 0.000 | 6.834 | 6.573 | 24.332 | 57.394 | 0.000 | 26.888 | 7.290 | 0.000 | -9.009 | 0.000 | -4.567 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -60.860 | 0.000 | 0.000 | 4.358 | 4.188 | 15.403 | 37.368 | 0.000 | 0.766 | 5.231 | 0.000 | -6.186 | 0.000 | -0.268 | -0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.000 | -73.917 | 0.000 | 0.000 | 6.902 | 6.648 | 24.333 | 36.667 | 0.000 | 1.830 | 6.626 | 0.000 | -8.534 | 0.000 | -0.556 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.000 | -55.822 | 0.000 | 0.000 | 3.208 | 4.199 | 15.404 | 36.821 | 0.000 | 1.195 | 0.780 | 0.000 | -5.396 | 0.000 | -0.388 | -0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -89.668 | 0.000 | 0.000 | 6.889 | 6.582 | 24.332 | 57.903 | 0.000 | 1.806 | 1.234 | 0.000 | -8.465 | 0.000 | -0.612 | -0.000 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -57.226 | 0.000 | 0.000 | 4.366 | 4.195 | 15.403 | 37.565 | 0.000 | 1.196 | 0.726 | 0.000 | -5.835 | 0.000 | -0.391 | -0.000 |
TOPFLOOR_PLENUM | 1.351 | -85.904 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.951 | 82.536 | 0.000 | 0.000 | 0.000 | -0.934 | 0.000 |
MIDFLOOR_PLENUM | 0.236 | -52.456 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.865 | 50.342 | 0.000 | 0.000 | 0.000 | -0.988 | 0.000 |
FIRSTFLOOR_PLENUM | 0.365 | -59.713 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.224 | 57.941 | 0.000 | 0.000 | 0.000 | -0.816 | 0.000 |
Total Facility | 1.952 | -198.073 | 0.254 | -1682.481 | 0.000 | 0.000 | 164.489 | 231.631 | 705.434 | 505.289 | 0.000 | 50.868 | 317.625 | 0.000 | -84.672 | 0.000 | -12.316 | -0.006 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 25-APR-04:53 | 0.00 | 0.00 | 0.00 | -43993.98 | 0.00 | 0.00 | 0.00 | 211.73 | 4405.64 | 0.00 | 0.00 | 0.00 | 39376.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 15-MAY-05:14 | 0.00 | 0.00 | 0.00 | -34044.84 | 0.00 | 0.00 | 316.03 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 30154.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 25-SEP-04:02 | 0.00 | 0.00 | 0.00 | -37132.86 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 34479.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 21-MAY-13:02 | 0.00 | 0.00 | 0.00 | -16047.63 | 0.00 | 0.00 | 22.52 | 27.57 | 478.42 | 3277.19 | 0.00 | 2200.45 | 10041.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 23-JUL-09:52 | 0.00 | 0.00 | 0.00 | -13378.19 | 0.00 | 0.00 | 13.99 | 17.46 | 302.86 | 5285.32 | 0.00 | 319.72 | 7438.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 29-OCT-13:42 | 0.00 | 0.00 | 0.00 | -18798.75 | 0.00 | 0.00 | 22.28 | 27.57 | 478.41 | 7640.88 | 0.00 | 272.81 | 10356.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 21-MAY-16:22 | 0.00 | 0.00 | 0.00 | -14183.40 | 0.00 | 0.00 | 12.81 | 17.46 | 302.86 | 4979.98 | 0.00 | 374.46 | 8495.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 04-SEP-14:41 | 0.00 | 0.00 | 0.00 | -14268.05 | 0.00 | 0.00 | 25.23 | 27.57 | 478.42 | 3757.13 | 0.00 | 310.14 | 9669.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-SEP-10:42 | 0.00 | 0.00 | 0.00 | -12053.72 | 0.00 | 0.00 | 14.56 | 17.46 | 302.86 | 4181.65 | 0.00 | 138.96 | 7398.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 16-AUG-12:00 | 0.00 | 0.00 | 0.00 | -18402.08 | 0.00 | 0.00 | 222.64 | 496.34 | 1275.77 | 5944.45 | 0.00 | 18599.15 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8136.27 |
PERIMETER_BOT_ZN_4 | 04-SEP-16:01 | 0.00 | 0.00 | 0.00 | -13357.08 | 0.00 | 0.00 | 13.43 | 17.46 | 302.86 | 5488.73 | 0.00 | 189.58 | 7345.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 06-AUG-11:32 | 0.00 | 0.00 | 0.00 | -13579.88 | 0.00 | 0.00 | 26.33 | 27.57 | 478.42 | 3878.75 | 0.00 | 244.01 | 8924.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 06-AUG-10:12 | 0.00 | 0.00 | 0.00 | -12147.35 | 0.00 | 0.00 | 14.84 | 17.46 | 302.86 | 4785.12 | 0.00 | 162.67 | 6864.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 09-OCT-11:42 | 0.00 | 0.00 | 0.00 | -16268.80 | 0.00 | 0.00 | 23.43 | 27.57 | 478.41 | 8198.36 | 0.00 | 101.98 | 7439.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 04-SEP-16:12 | 0.00 | 0.00 | 0.00 | -12710.31 | 0.00 | 0.00 | 13.02 | 17.46 | 302.86 | 5306.02 | 0.00 | 340.43 | 6730.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 03-SEP-14:51 | 0.00 | -16467.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 701.47 | 15766.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 05-SEP-12:04 | 0.00 | -8028.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.67 | 7853.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 31-JUL-12:09 | 0.00 | -9281.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.50 | 9114.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-MAY-04:02 | 0.00 | 7903.79 | 0.00 | -231012.17 | 0.00 | 0.00 | 0.00 | 1072.56 | 14333.92 | 528.15 | 0.00 | 470.10 | 206703.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-JAN-08:00 | 0.00 | 0.00 | 3500.20 | 0.00 | 0.00 | 0.00 | 184.58 | 165.45 | 637.88 | 8.05 | 0.00 | 0.00 | 4602.98 | 0.00 | -0.00 | 0.00 | -9099.15 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 25-SEP-04:02 | 5031.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -34.30 | -4997.37 |
MIDFLOOR_PLENUM | 25-AUG-04:02 | 3273.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.45 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3366.84 |
FIRSTFLOOR_PLENUM | 28-SEP-04:02 | 4411.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.07 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4469.23 |
Total Facility | 15-SEP-04:02 | -186627.62 | 196930.94 | 0.00 | -196930.94 | 0.00 | 0.00 | 0.00 | 1072.56 | 14333.92 | 70.63 | 0.00 | 689.94 | 170651.52 | 0.00 | -190.94 | 0.00 | 0.00 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.8322 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.4657 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.2088 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7959 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.8645 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.7073 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.9161 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0763 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.6044 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0757 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.9323 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0756 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8331 | 2.8331 | 0.6374 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1365 | 2.1365 | 0.6367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3942 | 2.3942 | 0.6369 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9150 | 0.9150 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7205 | 0.7205 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0156 | 1.0156 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8192 | 0.8192 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7813 | 0.7813 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6521 | 0.6521 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8741 | 0.8741 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6916 | 0.6916 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7868 | 0.7868 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6724 | 0.6724 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8856 | 0.8856 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7276 | 0.7276 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.8322 | 5.4657 | 5.8322 | 1.0763 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.2088 | 4.7959 | 5.2088 | 1.0757 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.8645 | 5.7073 | 5.8645 | 1.0756 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4165 | 1.4165 | 0.6374 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0683 | 1.0683 | 0.6367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1971 | 1.1971 | 0.6369 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4575 | 0.4575 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3602 | 0.3602 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5078 | 0.5078 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4096 | 0.4096 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3906 | 0.3906 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3261 | 0.3261 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4371 | 0.4371 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3458 | 0.3458 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3934 | 0.3934 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3362 | 0.3362 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4428 | 0.4428 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3638 | 0.3638 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.9161 | 1.0763 | 1.0763 | 1.0763 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.6044 | 1.0757 | 1.0757 | 1.0757 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.9323 | 1.0756 | 1.0756 | 1.0756 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 2.33 |
Number of hours cooling loads not met | 570.00 |
Number of hours not met | 572.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.39 | 4493.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 871.15 | 126423.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 231.63 | 24001.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 50.55 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.69 | 838.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 168.00 | 26704.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 108.58 | 9530.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 2039.00 |
Natural Gas | 0.00 | 108.58 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 2147.58 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.49 |
Space Heating | 0.08 |
Space Cooling | 174.85 |
Fans (All) | 33.72 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 409.26 |
Subtotal | 409.26 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 21.79 |
Miscellaneous (All) | 21.79 |
Subtotal | 21.79 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.79 |
Space Heating | 0.02 |
Space Cooling | 40.56 |
Fans (All) | 7.82 |
Service Water Heating | 5.06 |
Receptacle Equipment | 32.85 |
Miscellaneous | 2.91 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 995. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8448.33 | 311.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8736.00 | 24.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8723.33 | 36.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7773.17 | 986.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7602.67 | 1157.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7630.17 | 1129.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7548.83 | 1211.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8049.33 | 710.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7701.17 | 1058.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7628.67 | 1131.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7598.50 | 1161.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7803.00 | 957.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7581.17 | 1178.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7640.50 | 1119.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7510.67 | 1249.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7811.67 | 948.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8266.83 | 493.17 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8385.17 | 374.83 | 0.00 | 0.00 | 0.00 |
Min | 7510.67 | 24.00 | 0.00 | 0.00 | 0.00 |
Max | 8736.00 | 1249.33 | 0.00 | 0.00 | 0.00 |
Average | 7913.29 | 846.71 | 0.00 | 0.00 | 0.00 |
Sum | 142439.17 | 15240.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128243.33 | 60.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128299.33 | 4.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128285.67 | 18.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24479.67 | 429.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128299.33 | 429.33 | 0.00 | 0.00 | 0.00 |
Average | 34114.83 | 28.50 | 0.00 | 0.00 | 0.00 |
Sum | 614067.00 | 513.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 7047.83 | 1712.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7283.00 | 1477.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7366.33 | 1393.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6363.83 | 2396.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6254.67 | 2505.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 6237.17 | 2522.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6251.83 | 2508.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6371.17 | 2388.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6223.00 | 2537.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 5496.50 | 3263.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6206.83 | 2553.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6253.33 | 2506.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6146.00 | 2614.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6122.00 | 2638.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6135.67 | 2624.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 4424.17 | 4335.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 5269.67 | 3490.33 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 5859.17 | 2900.83 | 0.00 | 0.00 | 0.00 |
Min | 4424.17 | 1393.67 | 0.00 | 0.00 | 0.00 |
Max | 7366.33 | 4335.83 | 0.00 | 0.00 | 0.00 |
Average | 6184.01 | 2575.99 | 0.00 | 0.00 | 0.00 |
Sum | 111312.17 | 46367.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127379.17 | 924.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 127553.83 | 750.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 127504.33 | 799.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24788.67 | 120.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14012.50 | 3.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24789.33 | 119.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14012.67 | 3.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24808.00 | 101.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 21274.00 | 3635.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24784.83 | 124.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10133.33 | 0.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24784.83 | 124.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14015.33 | 0.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 127553.83 | 3635.00 | 0.00 | 0.00 | 0.00 |
Average | 33770.71 | 372.62 | 0.00 | 0.00 | 0.00 |
Sum | 607872.83 | 6707.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:02
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226651E+11 | 43494.02 | 02-JAN-06:12 | 13.00 | 10.85 | 0.199552E+10 | 2606.69 | 17-JAN-10:09 | 23.00 | 15.97 |
February | 0.209626E+11 | 42373.75 | 21-FEB-06:12 | 13.90 | 13.23 | 0.181061E+10 | 2606.76 | 15-FEB-14:09 | 13.90 | 13.23 |
March | 0.256211E+11 | 43432.35 | 28-MAR-04:03 | 26.08 | 14.62 | 0.216171E+10 | 2606.82 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.249302E+11 | 44005.68 | 25-APR-04:53 | 24.00 | 12.96 | 0.191940E+10 | 2606.88 | 28-APR-13:39 | 35.57 | 23.16 |
May | 0.294480E+11 | 43752.53 | 16-MAY-04:03 | 25.00 | 22.44 | 0.207873E+10 | 2606.77 | 04-MAY-13:00 | 25.00 | 22.44 |
June | 0.298075E+11 | 43272.86 | 07-JUN-04:03 | 24.83 | 21.13 | 0.207181E+10 | 2606.72 | 02-JUN-13:09 | 24.83 | 21.13 |
July | 0.305023E+11 | 37367.90 | 03-JUL-06:03 | 28.20 | 16.17 | 0.192451E+10 | 2606.86 | 03-JUL-09:30 | 35.10 | 24.31 |
August | 0.327859E+11 | 37545.69 | 15-AUG-04:02 | 29.75 | 23.27 | 0.215951E+10 | 2606.64 | 25-AUG-13:20 | 36.47 | 27.84 |
September | 0.294053E+11 | 40947.09 | 26-SEP-04:02 | 26.97 | 19.72 | 0.191904E+10 | 2606.66 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.290783E+11 | 42955.48 | 31-OCT-04:03 | 24.33 | 22.73 | 0.199629E+10 | 2606.64 | 20-OCT-09:20 | 24.33 | 22.73 |
November | 0.262515E+11 | 43225.32 | 27-NOV-06:12 | 17.80 | 15.99 | 0.197710E+10 | 2606.67 | 22-NOV-10:20 | 17.80 | 15.99 |
December | 0.231809E+11 | 42720.17 | 04-DEC-06:12 | 17.40 | 16.34 | 0.192578E+10 | 2606.69 | 08-DEC-10:39 | 24.10 | 19.19 |
Annual Sum or Average | 0.324639E+12 | 0.239400E+11 | ||||||||
Minimum of Months | 0.209626E+11 | 37367.90 | 13.00 | 10.85 | 0.181061E+10 | 2606.64 | 13.90 | 13.23 | ||
Maximum of Months | 0.327859E+11 | 44005.68 | 29.75 | 23.27 | 0.216171E+10 | 2606.88 | 36.47 | 27.84 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203105E+10 | 5248.44 | 31-JAN-14:05 | 23.00 | 16.33 | 0.00 | 0.00 | 01-JAN-00:10 | 23.00 | 16.33 |
February | 0.274697E+10 | 8114.35 | 06-FEB-15:00 | 32.50 | 17.28 | 0.00 | 0.00 | 01-FEB-00:10 | 32.50 | 17.28 |
March | 0.459314E+10 | 11040.79 | 27-MAR-13:30 | 35.50 | 19.59 | 0.00 | 0.00 | 01-MAR-00:10 | 35.50 | 19.59 |
April | 0.620535E+10 | 12144.79 | 28-APR-12:40 | 38.47 | 22.15 | 0.00 | 0.00 | 01-APR-00:10 | 38.47 | 22.15 |
May | 0.990635E+10 | 12541.11 | 10-MAY-14:40 | 40.00 | 20.07 | 0.00 | 0.00 | 01-MAY-00:10 | 40.00 | 20.07 |
June | 0.108416E+11 | 13300.34 | 12-JUN-13:05 | 40.25 | 27.32 | 0.00 | 0.00 | 01-JUN-00:10 | 40.25 | 27.32 |
July | 0.120187E+11 | 14279.54 | 21-JUL-12:02 | 45.38 | 23.17 | 0.00 | 0.00 | 01-JUL-00:10 | 45.38 | 23.17 |
August | 0.126452E+11 | 14312.23 | 16-AUG-13:30 | 44.10 | 25.63 | 0.00 | 0.00 | 01-AUG-00:10 | 44.10 | 25.63 |
September | 0.975233E+10 | 16470.66 | 03-SEP-14:51 | 38.00 | 27.45 | 0.00 | 0.00 | 01-SEP-00:10 | 38.00 | 27.45 |
October | 0.766437E+10 | 11262.72 | 02-OCT-14:05 | 35.82 | 20.34 | 0.00 | 0.00 | 01-OCT-00:10 | 35.82 | 20.34 |
November | 0.490374E+10 | 9324.19 | 06-NOV-14:05 | 32.83 | 20.61 | 0.00 | 0.00 | 01-NOV-00:10 | 32.83 | 20.61 |
December | 0.259536E+10 | 6831.45 | 04-DEC-13:50 | 27.17 | 20.95 | 0.00 | 0.00 | 01-DEC-00:10 | 27.17 | 20.95 |
Annual Sum or Average | 0.859041E+11 | 0.00 | ||||||||
Minimum of Months | 0.203105E+10 | 5248.44 | 23.00 | 16.33 | 0.00 | 0.00 | 23.00 | 16.33 | ||
Maximum of Months | 0.126452E+11 | 16470.66 | 45.38 | 27.45 | 0.00 | 0.00 | 45.38 | 27.45 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121641E+10 | 2251.84 | 31-JAN-15:30 | 22.80 | 16.62 | 0.00 | 0.00 | 01-JAN-00:10 | 22.80 | 16.62 |
February | 0.162228E+10 | 4167.53 | 06-FEB-15:20 | 32.13 | 17.39 | 0.00 | 0.00 | 01-FEB-00:10 | 32.13 | 17.39 |
March | 0.276021E+10 | 5588.56 | 27-MAR-12:05 | 37.08 | 19.46 | 0.00 | 0.00 | 01-MAR-00:10 | 37.08 | 19.46 |
April | 0.364769E+10 | 5682.48 | 24-APR-12:04 | 37.07 | 17.93 | 0.00 | 0.00 | 01-APR-00:10 | 37.07 | 17.93 |
May | 0.593047E+10 | 7792.98 | 30-MAY-06:15 | 27.17 | 24.99 | 0.00 | 0.00 | 01-MAY-00:10 | 27.17 | 24.99 |
June | 0.641502E+10 | 7865.35 | 12-JUN-06:15 | 30.03 | 23.76 | 0.00 | 0.00 | 01-JUN-00:10 | 30.03 | 23.76 |
July | 0.693592E+10 | 7868.51 | 05-JUL-06:15 | 30.13 | 28.32 | 0.00 | 0.00 | 01-JUL-00:10 | 30.13 | 28.32 |
August | 0.740918E+10 | 7790.36 | 07-AUG-12:03 | 36.98 | 28.67 | 0.00 | 0.00 | 01-AUG-00:10 | 36.98 | 28.67 |
September | 0.606606E+10 | 8028.92 | 05-SEP-12:04 | 40.98 | 24.12 | 0.00 | 0.00 | 01-SEP-00:10 | 40.98 | 24.12 |
October | 0.517393E+10 | 6942.60 | 02-OCT-06:15 | 27.03 | 24.77 | 0.00 | 0.00 | 01-OCT-00:10 | 27.03 | 24.77 |
November | 0.349816E+10 | 5406.71 | 13-NOV-15:20 | 32.07 | 19.51 | 0.00 | 0.00 | 01-NOV-00:10 | 32.07 | 19.51 |
December | 0.178079E+10 | 3507.28 | 04-DEC-15:20 | 26.73 | 21.25 | 0.00 | 0.00 | 01-DEC-00:10 | 26.73 | 21.25 |
Annual Sum or Average | 0.524561E+11 | 0.00 | ||||||||
Minimum of Months | 0.121641E+10 | 2251.84 | 22.80 | 16.62 | 0.00 | 0.00 | 22.80 | 16.62 | ||
Maximum of Months | 0.740918E+10 | 8028.92 | 40.98 | 28.67 | 0.00 | 0.00 | 40.98 | 28.67 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.223885E+10 | 3617.01 | 02-JAN-07:07 | 13.00 | 10.98 | 0.00 | 0.00 | 01-JAN-00:10 | 13.00 | 10.98 |
February | 0.245168E+10 | 4804.97 | 06-FEB-13:10 | 30.25 | 18.19 | 0.00 | 0.00 | 01-FEB-00:10 | 30.25 | 18.19 |
March | 0.354193E+10 | 7261.14 | 27-MAR-12:09 | 37.08 | 19.46 | 0.00 | 0.00 | 01-MAR-00:10 | 37.08 | 19.46 |
April | 0.417923E+10 | 7149.61 | 26-APR-12:07 | 38.83 | 18.61 | 0.00 | 0.00 | 01-APR-00:10 | 38.83 | 18.61 |
May | 0.625185E+10 | 9194.49 | 22-MAY-12:06 | 38.02 | 22.04 | 0.00 | 0.00 | 01-MAY-00:10 | 38.02 | 22.04 |
June | 0.668694E+10 | 8850.89 | 26-JUN-12:06 | 38.97 | 25.98 | 0.00 | 0.00 | 01-JUN-00:10 | 38.97 | 25.98 |
July | 0.700879E+10 | 9282.17 | 31-JUL-12:09 | 40.98 | 25.84 | 0.00 | 0.00 | 01-JUL-00:10 | 40.98 | 25.84 |
August | 0.757289E+10 | 9157.73 | 07-AUG-12:09 | 36.98 | 28.67 | 0.00 | 0.00 | 01-AUG-00:10 | 36.98 | 28.67 |
September | 0.648500E+10 | 8437.18 | 12-SEP-12:09 | 38.87 | 25.21 | 0.00 | 0.00 | 01-SEP-00:10 | 38.87 | 25.21 |
October | 0.589325E+10 | 6949.56 | 02-OCT-06:15 | 27.03 | 24.77 | 0.00 | 0.00 | 01-OCT-00:10 | 27.03 | 24.77 |
November | 0.455740E+10 | 5948.30 | 13-NOV-16:10 | 30.00 | 21.15 | 0.00 | 0.00 | 01-NOV-00:10 | 30.00 | 21.15 |
December | 0.284499E+10 | 4891.18 | 04-DEC-13:10 | 27.83 | 21.18 | 0.00 | 0.00 | 01-DEC-00:10 | 27.83 | 21.18 |
Annual Sum or Average | 0.597128E+11 | 0.00 | ||||||||
Minimum of Months | 0.223885E+10 | 3617.01 | 13.00 | 10.98 | 0.00 | 0.00 | 13.00 | 10.98 | ||
Maximum of Months | 0.757289E+10 | 9282.17 | 40.98 | 28.67 | 0.00 | 0.00 | 40.98 | 28.67 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135622E+11 | 21128.89 | 30-JAN-06:12 | 20.07 | 17.42 | 0.198460E+10 | 2606.69 | 17-JAN-10:09 | 20.07 | 17.42 |
February | 0.132060E+11 | 31692.60 | 06-FEB-06:12 | 21.77 | 18.83 | 0.180352E+10 | 2606.73 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.170234E+11 | 32007.78 | 27-MAR-05:12 | 21.93 | 13.41 | 0.215675E+10 | 2606.79 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.177553E+11 | 32785.75 | 03-APR-04:03 | 24.50 | 18.54 | 0.191615E+10 | 2606.83 | 28-APR-13:39 | 35.57 | 23.16 |
May | 0.223464E+11 | 34048.48 | 15-MAY-05:14 | 23.00 | 17.48 | 0.207686E+10 | 2606.77 | 08-MAY-13:30 | 23.00 | 17.48 |
June | 0.228263E+11 | 32475.89 | 06-JUN-04:03 | 25.92 | 21.78 | 0.207009E+10 | 2606.75 | 02-JUN-13:09 | 25.92 | 21.78 |
July | 0.240954E+11 | 29819.84 | 03-JUL-06:03 | 28.20 | 16.17 | 0.192296E+10 | 2606.83 | 03-JUL-09:09 | 34.37 | 23.66 |
August | 0.253558E+11 | 29186.56 | 15-AUG-06:03 | 29.85 | 21.21 | 0.215838E+10 | 2606.63 | 07-AUG-13:20 | 29.85 | 21.21 |
September | 0.219680E+11 | 32205.84 | 26-SEP-04:02 | 26.97 | 19.72 | 0.191782E+10 | 2606.66 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.210359E+11 | 32769.68 | 17-OCT-04:03 | 25.25 | 24.38 | 0.199428E+10 | 2606.64 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.178097E+11 | 33049.68 | 13-NOV-06:12 | 20.83 | 17.71 | 0.197323E+10 | 2606.69 | 28-NOV-10:09 | 25.67 | 19.42 |
December | 0.145446E+11 | 31762.10 | 11-DEC-06:12 | 21.80 | 19.16 | 0.191817E+10 | 2606.67 | 08-DEC-10:20 | 21.80 | 19.16 |
Annual Sum or Average | 0.231529E+12 | 0.238928E+11 | ||||||||
Minimum of Months | 0.132060E+11 | 21128.89 | 20.07 | 13.41 | 0.180352E+10 | 2606.63 | 20.07 | 17.42 | ||
Maximum of Months | 0.253558E+11 | 34048.48 | 29.85 | 24.38 | 0.215838E+10 | 2606.83 | 35.57 | 23.66 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121222E+11 | 14611.31 | 30-JAN-14:50 | 22.17 | 20.62 | 0.196395E+10 | 2606.67 | 17-JAN-14:20 | 22.17 | 20.62 |
February | 0.123699E+11 | 18935.10 | 06-FEB-06:12 | 21.77 | 18.83 | 0.179137E+10 | 2606.74 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.166760E+11 | 35929.84 | 27-MAR-05:12 | 21.93 | 13.41 | 0.215017E+10 | 2606.81 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.182536E+11 | 35896.27 | 24-APR-05:12 | 21.67 | 13.88 | 0.191478E+10 | 2606.84 | 28-APR-13:39 | 35.57 | 23.16 |
May | 0.241043E+11 | 36074.68 | 01-MAY-05:12 | 20.87 | 20.87 | 0.207797E+10 | 2606.80 | 08-MAY-13:39 | 35.50 | 23.99 |
June | 0.250281E+11 | 36661.74 | 06-JUN-04:03 | 25.92 | 21.78 | 0.207142E+10 | 2606.81 | 02-JUN-13:09 | 25.92 | 21.78 |
July | 0.268948E+11 | 33524.57 | 10-JUL-06:03 | 31.98 | 24.04 | 0.192512E+10 | 2606.87 | 03-JUL-09:39 | 31.98 | 24.04 |
August | 0.281042E+11 | 33678.19 | 07-AUG-06:03 | 31.98 | 22.90 | 0.215977E+10 | 2606.61 | 03-AUG-13:20 | 31.98 | 22.90 |
September | 0.236296E+11 | 37138.30 | 25-SEP-04:02 | 24.17 | 23.10 | 0.191894E+10 | 2606.66 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.215348E+11 | 36867.94 | 23-OCT-04:02 | 25.42 | 23.19 | 0.199462E+10 | 2606.69 | 30-OCT-09:20 | 28.83 | 20.32 |
November | 0.172433E+11 | 36684.27 | 20-NOV-05:02 | 26.00 | 18.81 | 0.197102E+10 | 2606.69 | 28-NOV-10:50 | 25.93 | 20.29 |
December | 0.133536E+11 | 16363.94 | 11-DEC-07:03 | 21.50 | 18.56 | 0.190488E+10 | 2606.67 | 01-DEC-10:20 | 21.50 | 18.56 |
Annual Sum or Average | 0.239314E+12 | 0.238440E+11 | ||||||||
Minimum of Months | 0.121222E+11 | 14611.31 | 20.87 | 13.41 | 0.179137E+10 | 2606.61 | 21.50 | 18.27 | ||
Maximum of Months | 0.281042E+11 | 37138.30 | 31.98 | 24.04 | 0.215977E+10 | 2606.87 | 35.57 | 24.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.246668E+10 | 4092.08 | 23-JAN-14:10 | 27.50 | 16.66 | 0.402919E+09 | 549.50 | 17-JAN-14:20 | 27.50 | 16.66 |
February | 0.284823E+10 | 5871.43 | 06-FEB-15:00 | 32.50 | 17.28 | 0.371595E+09 | 549.52 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.443099E+10 | 7246.99 | 27-MAR-13:10 | 35.83 | 19.71 | 0.450033E+09 | 549.53 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.563005E+10 | 11976.30 | 30-APR-12:13 | 37.03 | 20.80 | 0.403288E+09 | 549.54 | 28-APR-13:09 | 37.03 | 20.80 |
May | 0.874630E+10 | 16050.44 | 21-MAY-13:02 | 38.00 | 22.80 | 0.439016E+09 | 549.54 | 08-MAY-13:39 | 38.00 | 22.80 |
June | 0.966549E+10 | 15157.01 | 11-JUN-09:52 | 38.00 | 26.72 | 0.437727E+09 | 549.53 | 02-JUN-13:09 | 38.00 | 26.72 |
July | 0.106164E+11 | 15956.01 | 23-JUL-09:52 | 40.60 | 22.99 | 0.407396E+09 | 549.55 | 03-JUL-09:39 | 40.60 | 22.99 |
August | 0.109012E+11 | 15422.66 | 20-AUG-10:12 | 37.20 | 26.10 | 0.456626E+09 | 549.49 | 04-AUG-13:20 | 37.20 | 26.10 |
September | 0.844986E+10 | 15672.39 | 04-SEP-12:32 | 40.73 | 24.78 | 0.405568E+09 | 549.50 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.680334E+10 | 15168.94 | 29-OCT-13:42 | 34.18 | 18.90 | 0.421164E+09 | 549.51 | 30-OCT-09:20 | 28.83 | 20.32 |
November | 0.465377E+10 | 8459.62 | 12-NOV-14:42 | 29.17 | 18.00 | 0.414745E+09 | 549.50 | 17-NOV-10:20 | 27.40 | 19.69 |
December | 0.293898E+10 | 4606.31 | 11-DEC-14:10 | 26.77 | 18.23 | 0.395784E+09 | 549.50 | 01-DEC-14:20 | 26.77 | 18.23 |
Annual Sum or Average | 0.781513E+11 | 0.500586E+10 | ||||||||
Minimum of Months | 0.246668E+10 | 4092.08 | 26.77 | 16.66 | 0.371595E+09 | 549.49 | 25.67 | 16.66 | ||
Maximum of Months | 0.109012E+11 | 16050.44 | 40.73 | 26.72 | 0.456626E+09 | 549.55 | 40.60 | 26.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199491E+10 | 3054.79 | 24-JAN-11:00 | 24.00 | 17.69 | 0.260523E+09 | 347.88 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.230824E+10 | 6356.92 | 05-FEB-15:23 | 32.00 | 19.15 | 0.238248E+09 | 347.89 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.355298E+10 | 7302.14 | 26-MAR-11:33 | 33.67 | 17.01 | 0.286292E+09 | 347.90 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.463734E+10 | 11877.71 | 30-APR-12:13 | 37.03 | 20.80 | 0.255819E+09 | 347.91 | 25-APR-09:09 | 37.03 | 20.80 |
May | 0.690415E+10 | 12654.96 | 21-MAY-13:02 | 38.00 | 22.80 | 0.278093E+09 | 348.03 | 22-MAY-09:00 | 36.70 | 22.71 |
June | 0.732127E+10 | 12901.50 | 18-JUN-09:12 | 35.53 | 24.85 | 0.277194E+09 | 347.90 | 02-JUN-13:09 | 35.53 | 24.85 |
July | 0.794903E+10 | 13383.11 | 23-JUL-09:52 | 40.60 | 22.99 | 0.258027E+09 | 347.94 | 21-JUL-09:39 | 40.60 | 22.99 |
August | 0.834753E+10 | 13018.14 | 20-AUG-10:12 | 37.20 | 26.10 | 0.289178E+09 | 348.02 | 04-AUG-09:09 | 37.20 | 26.10 |
September | 0.663900E+10 | 13231.11 | 04-SEP-09:12 | 36.53 | 22.23 | 0.256903E+09 | 347.88 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.545580E+10 | 12069.27 | 08-OCT-10:02 | 32.17 | 26.39 | 0.266884E+09 | 347.89 | 30-OCT-09:20 | 28.83 | 20.32 |
November | 0.373258E+10 | 9829.09 | 05-NOV-11:22 | 33.15 | 17.98 | 0.263317E+09 | 347.89 | 28-NOV-10:39 | 25.87 | 20.07 |
December | 0.230032E+10 | 3522.10 | 04-DEC-11:00 | 26.00 | 20.51 | 0.253493E+09 | 347.88 | 01-DEC-10:20 | 26.00 | 20.51 |
Annual Sum or Average | 0.611432E+11 | 0.318397E+10 | ||||||||
Minimum of Months | 0.199491E+10 | 3054.79 | 24.00 | 17.01 | 0.238248E+09 | 347.88 | 24.00 | 17.69 | ||
Maximum of Months | 0.834753E+10 | 13383.11 | 40.60 | 26.39 | 0.289178E+09 | 348.03 | 40.60 | 26.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.451604E+10 | 10210.92 | 22-JAN-14:23 | 26.00 | 16.36 | 0.411707E+09 | 549.51 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.472822E+10 | 17468.27 | 05-FEB-15:23 | 32.00 | 19.15 | 0.375679E+09 | 549.54 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.606780E+10 | 12830.71 | 26-MAR-14:13 | 32.87 | 18.44 | 0.451419E+09 | 549.54 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.643595E+10 | 17268.02 | 30-APR-12:13 | 37.03 | 20.80 | 0.403533E+09 | 549.55 | 28-APR-13:09 | 37.03 | 20.80 |
May | 0.878434E+10 | 17768.10 | 21-MAY-13:02 | 38.00 | 22.80 | 0.438985E+09 | 549.54 | 08-MAY-13:39 | 38.00 | 22.80 |
June | 0.929068E+10 | 16530.68 | 11-JUN-09:52 | 38.00 | 26.72 | 0.437671E+09 | 549.53 | 02-JUN-13:09 | 38.00 | 26.72 |
July | 0.105019E+11 | 17580.75 | 30-JUL-13:22 | 44.25 | 24.07 | 0.407365E+09 | 549.55 | 03-JUL-09:39 | 44.25 | 24.07 |
August | 0.114961E+11 | 17123.56 | 20-AUG-10:12 | 37.20 | 26.10 | 0.456660E+09 | 549.49 | 04-AUG-13:20 | 37.20 | 26.10 |
September | 0.100933E+11 | 17899.22 | 04-SEP-12:32 | 40.73 | 24.78 | 0.405744E+09 | 549.68 | 26-SEP-13:50 | 39.37 | 23.60 |
October | 0.952840E+10 | 18809.40 | 29-OCT-13:42 | 34.18 | 18.90 | 0.421661E+09 | 549.80 | 10-OCT-13:00 | 34.18 | 18.90 |
November | 0.754460E+10 | 18474.42 | 05-NOV-12:02 | 33.90 | 17.83 | 0.416173E+09 | 549.74 | 13-NOV-14:09 | 33.00 | 16.45 |
December | 0.523724E+10 | 17724.00 | 03-DEC-13:53 | 27.00 | 20.88 | 0.401161E+09 | 549.51 | 01-DEC-10:20 | 27.00 | 20.88 |
Annual Sum or Average | 0.942245E+11 | 0.502776E+10 | ||||||||
Minimum of Months | 0.451604E+10 | 10210.92 | 26.00 | 16.36 | 0.375679E+09 | 549.49 | 24.00 | 16.45 | ||
Maximum of Months | 0.114961E+11 | 18809.40 | 44.25 | 26.72 | 0.456660E+09 | 549.80 | 44.25 | 26.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199598E+10 | 3729.49 | 31-JAN-16:20 | 22.73 | 16.79 | 0.255951E+09 | 347.85 | 17-JAN-14:20 | 22.73 | 16.79 |
February | 0.235722E+10 | 10110.18 | 05-FEB-15:23 | 32.00 | 19.15 | 0.235797E+09 | 347.87 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.365297E+10 | 8527.15 | 26-MAR-15:32 | 32.07 | 18.56 | 0.285355E+09 | 347.87 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.447569E+10 | 12051.35 | 23-APR-14:13 | 32.00 | 18.41 | 0.255529E+09 | 347.88 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.666541E+10 | 14189.21 | 21-MAY-16:22 | 37.25 | 23.23 | 0.278030E+09 | 347.88 | 08-MAY-13:39 | 37.25 | 23.23 |
June | 0.722316E+10 | 13496.92 | 18-JUN-14:32 | 36.00 | 26.94 | 0.277191E+09 | 347.88 | 02-JUN-13:09 | 36.00 | 26.94 |
July | 0.784099E+10 | 14167.88 | 02-JUL-16:12 | 37.93 | 23.27 | 0.257995E+09 | 347.88 | 03-JUL-09:39 | 35.47 | 24.64 |
August | 0.820751E+10 | 14122.84 | 06-AUG-15:02 | 40.85 | 24.99 | 0.289171E+09 | 347.85 | 15-AUG-09:20 | 36.77 | 22.00 |
September | 0.653888E+10 | 14178.11 | 03-SEP-14:53 | 38.00 | 27.45 | 0.256885E+09 | 347.86 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.534131E+10 | 14104.79 | 29-OCT-15:42 | 32.00 | 19.85 | 0.266798E+09 | 347.86 | 30-OCT-09:20 | 28.83 | 20.32 |
November | 0.372872E+10 | 12722.46 | 12-NOV-14:42 | 29.17 | 18.00 | 0.262851E+09 | 347.86 | 17-NOV-10:20 | 27.40 | 19.69 |
December | 0.236021E+10 | 4413.07 | 06-DEC-15:30 | 26.85 | 20.67 | 0.251223E+09 | 347.86 | 01-DEC-10:20 | 26.85 | 20.67 |
Annual Sum or Average | 0.603881E+11 | 0.317278E+10 | ||||||||
Minimum of Months | 0.199598E+10 | 3729.49 | 22.73 | 16.79 | 0.235797E+09 | 347.85 | 22.73 | 16.79 | ||
Maximum of Months | 0.820751E+10 | 14189.21 | 40.85 | 27.45 | 0.289171E+09 | 347.88 | 37.25 | 26.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.295103E+10 | 4123.56 | 23-JAN-14:10 | 27.50 | 16.66 | 0.415928E+09 | 549.51 | 17-JAN-10:20 | 27.50 | 16.66 |
February | 0.299764E+10 | 5251.34 | 06-FEB-15:00 | 32.50 | 17.28 | 0.378222E+09 | 549.51 | 15-FEB-14:39 | 24.67 | 17.94 |
March | 0.413594E+10 | 6128.98 | 27-MAR-13:10 | 35.83 | 19.71 | 0.453000E+09 | 549.53 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.495166E+10 | 7987.30 | 30-APR-13:43 | 34.52 | 22.68 | 0.403704E+09 | 549.54 | 28-APR-13:39 | 34.52 | 22.68 |
May | 0.772732E+10 | 10911.64 | 08-MAY-04:02 | 26.67 | 16.98 | 0.438774E+09 | 549.53 | 04-MAY-13:00 | 26.67 | 16.98 |
June | 0.871130E+10 | 12036.31 | 18-JUN-12:43 | 35.92 | 26.87 | 0.437556E+09 | 549.51 | 02-JUN-13:09 | 35.92 | 26.87 |
July | 0.981806E+10 | 13401.83 | 23-JUL-09:52 | 40.60 | 22.99 | 0.407218E+09 | 549.55 | 03-JUL-09:30 | 40.60 | 22.99 |
August | 0.107661E+11 | 13430.08 | 20-AUG-10:52 | 38.00 | 26.24 | 0.456521E+09 | 549.50 | 04-AUG-13:00 | 38.00 | 26.24 |
September | 0.876360E+10 | 14274.17 | 04-SEP-14:41 | 41.00 | 24.39 | 0.405537E+09 | 549.50 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.766442E+10 | 13341.17 | 09-OCT-11:42 | 37.67 | 19.71 | 0.421488E+09 | 549.50 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.566160E+10 | 10286.07 | 13-NOV-07:03 | 20.75 | 17.82 | 0.416452E+09 | 549.50 | 22-NOV-10:20 | 23.93 | 17.19 |
December | 0.369027E+10 | 6599.21 | 11-DEC-07:03 | 21.50 | 18.56 | 0.403798E+09 | 549.51 | 08-DEC-10:20 | 21.50 | 18.56 |
Annual Sum or Average | 0.778389E+11 | 0.503820E+10 | ||||||||
Minimum of Months | 0.295103E+10 | 4123.56 | 20.75 | 16.66 | 0.378222E+09 | 549.50 | 21.50 | 16.66 | ||
Maximum of Months | 0.107661E+11 | 14274.17 | 41.00 | 26.87 | 0.456521E+09 | 549.55 | 40.60 | 26.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.246904E+10 | 3335.76 | 17-JAN-11:10 | 24.17 | 16.24 | 0.264862E+09 | 347.88 | 17-JAN-10:20 | 24.17 | 16.24 |
February | 0.248794E+10 | 3854.29 | 06-FEB-14:10 | 32.08 | 17.23 | 0.240517E+09 | 347.89 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.339392E+10 | 5736.47 | 27-MAR-10:50 | 37.50 | 18.71 | 0.287481E+09 | 347.90 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.418213E+10 | 10176.78 | 30-APR-11:02 | 34.50 | 21.63 | 0.256090E+09 | 347.91 | 28-APR-13:09 | 34.50 | 21.63 |
May | 0.624706E+10 | 10069.81 | 29-MAY-10:42 | 37.35 | 22.00 | 0.278031E+09 | 347.98 | 22-MAY-09:00 | 37.35 | 22.00 |
June | 0.669986E+10 | 11299.72 | 25-JUN-10:53 | 36.00 | 25.60 | 0.277139E+09 | 347.88 | 27-JUN-13:09 | 38.33 | 27.70 |
July | 0.747092E+10 | 11792.54 | 23-JUL-09:52 | 40.60 | 22.99 | 0.257955E+09 | 347.95 | 03-JUL-09:39 | 40.60 | 22.99 |
August | 0.834590E+10 | 11817.12 | 20-AUG-10:52 | 38.00 | 26.24 | 0.289145E+09 | 347.88 | 04-AUG-13:00 | 38.00 | 26.24 |
September | 0.692475E+10 | 12060.16 | 04-SEP-10:42 | 38.00 | 23.07 | 0.256926E+09 | 347.88 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.612638E+10 | 11539.02 | 09-OCT-10:22 | 34.65 | 23.19 | 0.267102E+09 | 347.88 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.449462E+10 | 9590.84 | 05-NOV-11:22 | 33.15 | 17.98 | 0.264076E+09 | 347.88 | 22-NOV-10:20 | 23.93 | 17.19 |
December | 0.292291E+10 | 5150.07 | 04-DEC-07:02 | 17.83 | 16.73 | 0.256255E+09 | 347.88 | 08-DEC-10:20 | 23.20 | 18.74 |
Annual Sum or Average | 0.617654E+11 | 0.319558E+10 | ||||||||
Minimum of Months | 0.246904E+10 | 3335.76 | 17.83 | 16.24 | 0.240517E+09 | 347.88 | 23.20 | 16.24 | ||
Maximum of Months | 0.834590E+10 | 12060.16 | 40.60 | 26.24 | 0.289145E+09 | 347.98 | 40.60 | 27.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.455341E+10 | 10983.07 | 23-JAN-13:00 | 27.40 | 16.52 | 0.412761E+09 | 549.52 | 23-JAN-14:39 | 26.00 | 16.86 |
February | 0.477834E+10 | 14959.00 | 05-FEB-15:23 | 32.00 | 19.15 | 0.376458E+09 | 584.16 | 07-FEB-13:09 | 31.00 | 20.70 |
March | 0.633495E+10 | 15355.05 | 27-MAR-12:00 | 37.30 | 19.38 | 0.451259E+09 | 702.89 | 27-MAR-12:09 | 37.08 | 19.46 |
April | 0.714253E+10 | 16696.16 | 28-APR-12:00 | 42.00 | 19.18 | 0.404960E+09 | 778.52 | 28-APR-12:09 | 41.12 | 20.13 |
May | 0.107186E+11 | 16301.81 | 09-MAY-12:00 | 41.00 | 19.42 | 0.446088E+09 | 754.46 | 09-MAY-12:09 | 41.02 | 19.49 |
June | 0.118112E+11 | 17190.78 | 12-JUN-12:00 | 43.00 | 24.56 | 0.447115E+09 | 796.69 | 12-JUN-12:09 | 42.65 | 25.06 |
July | 0.132964E+11 | 18078.54 | 21-JUL-12:00 | 46.00 | 22.01 | 0.418113E+09 | 853.13 | 21-JUL-12:09 | 45.38 | 23.17 |
August | 0.155109E+11 | 18402.45 | 16-AUG-12:00 | 46.00 | 25.38 | 0.471757E+09 | 866.72 | 16-AUG-12:09 | 45.70 | 25.45 |
September | 0.133353E+11 | 17049.05 | 05-SEP-12:00 | 41.00 | 24.24 | 0.416897E+09 | 789.08 | 05-SEP-12:09 | 40.98 | 24.12 |
October | 0.126761E+11 | 16153.16 | 09-OCT-11:42 | 37.67 | 19.71 | 0.429733E+09 | 727.09 | 04-OCT-12:09 | 37.67 | 19.71 |
November | 0.980754E+10 | 15901.29 | 05-NOV-12:02 | 33.90 | 17.83 | 0.419194E+09 | 641.57 | 06-NOV-13:09 | 32.42 | 19.73 |
December | 0.602563E+10 | 15403.12 | 25-DEC-13:23 | 27.25 | 17.58 | 0.402126E+09 | 559.26 | 04-DEC-13:09 | 27.25 | 17.58 |
Annual Sum or Average | 0.115991E+12 | 0.509646E+10 | ||||||||
Minimum of Months | 0.455341E+10 | 10983.07 | 27.25 | 16.52 | 0.376458E+09 | 549.52 | 26.00 | 16.86 | ||
Maximum of Months | 0.155109E+11 | 18402.45 | 46.00 | 25.38 | 0.471757E+09 | 866.72 | 45.70 | 25.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239531E+10 | 3619.82 | 31-JAN-16:30 | 22.80 | 16.92 | 0.264232E+09 | 347.86 | 17-JAN-10:20 | 22.80 | 16.92 |
February | 0.248619E+10 | 7192.17 | 05-FEB-15:23 | 32.00 | 19.15 | 0.240145E+09 | 347.86 | 15-FEB-14:20 | 25.33 | 18.17 |
March | 0.347883E+10 | 6056.13 | 26-MAR-16:12 | 31.60 | 18.63 | 0.287411E+09 | 347.87 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.401889E+10 | 9897.82 | 02-APR-15:23 | 31.70 | 18.45 | 0.255991E+09 | 347.88 | 28-APR-13:39 | 35.57 | 23.16 |
May | 0.601411E+10 | 11530.35 | 21-MAY-18:03 | 35.35 | 23.79 | 0.277991E+09 | 347.88 | 04-MAY-13:00 | 35.35 | 23.79 |
June | 0.662040E+10 | 10951.70 | 18-JUN-16:02 | 35.98 | 27.42 | 0.277147E+09 | 347.86 | 02-JUN-13:09 | 35.98 | 27.42 |
July | 0.737485E+10 | 12038.65 | 30-JUL-14:42 | 41.50 | 26.59 | 0.257934E+09 | 347.88 | 03-JUL-09:30 | 41.50 | 26.59 |
August | 0.821881E+10 | 12137.25 | 06-AUG-16:22 | 40.05 | 25.93 | 0.289150E+09 | 347.86 | 04-AUG-13:00 | 40.05 | 25.93 |
September | 0.683982E+10 | 13363.98 | 04-SEP-16:01 | 40.58 | 23.84 | 0.256925E+09 | 347.86 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.601278E+10 | 12204.50 | 01-OCT-15:32 | 33.80 | 26.53 | 0.267074E+09 | 347.85 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.446177E+10 | 10369.40 | 12-NOV-15:32 | 29.07 | 17.65 | 0.263982E+09 | 347.86 | 22-NOV-10:20 | 23.93 | 17.19 |
December | 0.293850E+10 | 4788.90 | 11-DEC-07:03 | 21.50 | 18.56 | 0.256119E+09 | 347.86 | 08-DEC-10:20 | 21.50 | 18.56 |
Annual Sum or Average | 0.608603E+11 | 0.319410E+10 | ||||||||
Minimum of Months | 0.239531E+10 | 3619.82 | 21.50 | 16.92 | 0.240145E+09 | 347.85 | 21.50 | 16.92 | ||
Maximum of Months | 0.821881E+10 | 13363.98 | 41.50 | 27.42 | 0.289150E+09 | 347.88 | 41.50 | 27.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.266743E+10 | 3987.69 | 23-JAN-14:10 | 27.50 | 16.66 | 0.411544E+09 | 549.51 | 17-JAN-10:20 | 27.50 | 16.66 |
February | 0.295076E+10 | 5481.18 | 06-FEB-15:00 | 32.50 | 17.28 | 0.376488E+09 | 549.52 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.441167E+10 | 6672.26 | 27-MAR-13:10 | 35.83 | 19.71 | 0.452753E+09 | 549.53 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.539023E+10 | 10846.19 | 30-APR-15:13 | 31.17 | 26.10 | 0.403959E+09 | 549.55 | 28-APR-13:09 | 31.17 | 26.10 |
May | 0.809805E+10 | 13549.63 | 21-MAY-13:02 | 38.00 | 22.80 | 0.438971E+09 | 549.53 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.879060E+10 | 12560.10 | 18-JUN-12:43 | 35.92 | 26.87 | 0.437650E+09 | 550.48 | 12-JUN-13:20 | 35.92 | 26.87 |
July | 0.951528E+10 | 13365.67 | 30-JUL-13:22 | 44.25 | 24.07 | 0.407303E+09 | 550.49 | 31-JUL-13:20 | 40.60 | 26.80 |
August | 0.993063E+10 | 13585.33 | 06-AUG-11:32 | 40.67 | 25.32 | 0.456549E+09 | 550.46 | 04-AUG-13:20 | 40.67 | 25.32 |
September | 0.781763E+10 | 13332.60 | 04-SEP-15:32 | 40.80 | 24.09 | 0.405495E+09 | 549.50 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.654728E+10 | 13294.49 | 09-OCT-11:42 | 37.67 | 19.71 | 0.421201E+09 | 549.50 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.468244E+10 | 8113.07 | 20-NOV-05:02 | 26.00 | 18.81 | 0.415639E+09 | 549.51 | 28-NOV-10:20 | 25.73 | 19.64 |
December | 0.311539E+10 | 4513.85 | 11-DEC-14:10 | 26.77 | 18.23 | 0.400817E+09 | 549.50 | 01-DEC-14:20 | 26.77 | 18.23 |
Annual Sum or Average | 0.739174E+11 | 0.502837E+10 | ||||||||
Minimum of Months | 0.266743E+10 | 3987.69 | 26.00 | 16.66 | 0.376488E+09 | 549.50 | 25.67 | 16.66 | ||
Maximum of Months | 0.993063E+10 | 13585.33 | 44.25 | 26.87 | 0.456549E+09 | 550.49 | 40.67 | 26.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199630E+10 | 4389.04 | 24-JAN-11:05 | 24.00 | 18.08 | 0.194957E+09 | 356.46 | 24-JAN-11:09 | 24.00 | 18.08 |
February | 0.222767E+10 | 5495.34 | 07-FEB-13:03 | 31.00 | 20.70 | 0.177713E+09 | 356.46 | 16-FEB-15:09 | 24.78 | 18.41 |
March | 0.333710E+10 | 9686.35 | 27-MAR-12:01 | 37.08 | 19.46 | 0.212654E+09 | 356.48 | 28-MAR-10:09 | 27.17 | 20.40 |
April | 0.425846E+10 | 10529.53 | 23-APR-11:23 | 33.00 | 16.90 | 0.190224E+09 | 356.48 | 28-APR-14:09 | 35.00 | 23.22 |
May | 0.623313E+10 | 11622.09 | 21-MAY-08:23 | 33.00 | 18.35 | 0.206571E+09 | 356.49 | 11-MAY-12:09 | 33.00 | 18.35 |
June | 0.649141E+10 | 10736.48 | 18-JUN-12:43 | 35.92 | 26.87 | 0.205657E+09 | 356.47 | 02-JUN-12:09 | 35.92 | 26.87 |
July | 0.698686E+10 | 11846.18 | 30-JUL-10:42 | 44.57 | 22.23 | 0.192092E+09 | 356.45 | 03-JUL-10:09 | 44.57 | 22.23 |
August | 0.745050E+10 | 12154.73 | 06-AUG-10:12 | 38.47 | 24.31 | 0.214509E+09 | 356.45 | 04-AUG-14:09 | 38.47 | 24.31 |
September | 0.598472E+10 | 11985.56 | 03-SEP-11:02 | 39.17 | 24.31 | 0.190978E+09 | 356.46 | 26-SEP-10:09 | 37.25 | 21.73 |
October | 0.505243E+10 | 11824.78 | 09-OCT-10:22 | 34.65 | 23.19 | 0.198544E+09 | 356.46 | 20-OCT-10:09 | 30.83 | 18.35 |
November | 0.353924E+10 | 7523.58 | 01-NOV-12:02 | 32.48 | 26.16 | 0.195901E+09 | 356.46 | 22-NOV-11:09 | 26.17 | 17.78 |
December | 0.226429E+10 | 4821.45 | 04-DEC-11:05 | 26.25 | 20.62 | 0.189252E+09 | 356.46 | 20-DEC-13:09 | 24.30 | 21.04 |
Annual Sum or Average | 0.558221E+11 | 0.236905E+10 | ||||||||
Minimum of Months | 0.199630E+10 | 4389.04 | 24.00 | 16.90 | 0.177713E+09 | 356.45 | 24.00 | 17.78 | ||
Maximum of Months | 0.745050E+10 | 12154.73 | 44.57 | 26.87 | 0.214509E+09 | 356.49 | 44.57 | 26.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.478655E+10 | 9609.03 | 22-JAN-14:43 | 26.00 | 16.66 | 0.416596E+09 | 549.51 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.482330E+10 | 15575.58 | 05-FEB-13:43 | 31.52 | 19.39 | 0.378810E+09 | 549.54 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.600553E+10 | 13177.75 | 26-MAR-14:02 | 32.93 | 18.40 | 0.453625E+09 | 550.40 | 27-MAR-13:20 | 35.67 | 19.65 |
April | 0.614618E+10 | 13879.44 | 02-APR-14:53 | 33.00 | 18.35 | 0.404209E+09 | 549.55 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.813272E+10 | 15211.65 | 21-MAY-13:02 | 38.00 | 22.80 | 0.438935E+09 | 549.53 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.844516E+10 | 13958.84 | 18-JUN-12:43 | 35.92 | 26.87 | 0.437578E+09 | 549.52 | 02-JUN-13:09 | 35.92 | 26.87 |
July | 0.940855E+10 | 15100.95 | 30-JUL-13:22 | 44.25 | 24.07 | 0.407256E+09 | 549.54 | 03-JUL-09:09 | 44.25 | 24.07 |
August | 0.104884E+11 | 15411.46 | 06-AUG-11:32 | 40.67 | 25.32 | 0.456586E+09 | 550.55 | 29-AUG-13:20 | 37.40 | 29.98 |
September | 0.937857E+10 | 15633.49 | 24-SEP-12:42 | 34.67 | 25.92 | 0.405709E+09 | 550.50 | 15-SEP-13:20 | 34.67 | 25.92 |
October | 0.915921E+10 | 16266.16 | 09-OCT-11:42 | 37.67 | 19.71 | 0.421740E+09 | 550.44 | 23-OCT-13:20 | 32.73 | 22.39 |
November | 0.744855E+10 | 15580.72 | 19-NOV-13:43 | 31.00 | 17.59 | 0.416736E+09 | 550.38 | 13-NOV-14:20 | 31.00 | 17.59 |
December | 0.544542E+10 | 15571.07 | 25-DEC-13:13 | 27.33 | 17.20 | 0.403871E+09 | 549.51 | 01-DEC-14:20 | 27.33 | 17.20 |
Annual Sum or Average | 0.896681E+11 | 0.504165E+10 | ||||||||
Minimum of Months | 0.478655E+10 | 9609.03 | 26.00 | 16.66 | 0.378810E+09 | 549.51 | 24.00 | 17.20 | ||
Maximum of Months | 0.104884E+11 | 16266.16 | 44.25 | 26.87 | 0.456586E+09 | 550.55 | 44.25 | 29.98 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.212635E+10 | 3643.68 | 31-JAN-16:20 | 22.73 | 16.79 | 0.261195E+09 | 347.86 | 17-JAN-10:20 | 22.73 | 16.79 |
February | 0.241176E+10 | 6716.54 | 05-FEB-16:23 | 31.50 | 18.69 | 0.238777E+09 | 347.87 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.361525E+10 | 9265.46 | 26-MAR-17:23 | 31.10 | 18.85 | 0.286968E+09 | 347.87 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.427435E+10 | 12106.82 | 02-APR-15:32 | 31.27 | 18.46 | 0.255963E+09 | 347.88 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.620574E+10 | 12515.84 | 21-MAY-16:22 | 37.25 | 23.23 | 0.278012E+09 | 347.88 | 04-MAY-13:00 | 37.25 | 23.23 |
June | 0.660399E+10 | 12419.60 | 11-JUN-16:42 | 36.90 | 26.08 | 0.277148E+09 | 347.86 | 02-JUN-13:09 | 36.90 | 26.08 |
July | 0.707599E+10 | 12492.53 | 02-JUL-16:12 | 37.93 | 23.27 | 0.257941E+09 | 347.88 | 03-JUL-09:09 | 34.37 | 23.66 |
August | 0.752962E+10 | 12486.53 | 06-AUG-14:51 | 41.00 | 24.84 | 0.289125E+09 | 347.85 | 04-AUG-13:20 | 41.00 | 24.84 |
September | 0.607639E+10 | 12715.64 | 04-SEP-16:12 | 40.47 | 23.66 | 0.256854E+09 | 347.86 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.513392E+10 | 12586.49 | 09-OCT-15:41 | 36.83 | 19.09 | 0.266835E+09 | 347.85 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.370310E+10 | 11525.66 | 05-NOV-15:32 | 31.60 | 21.44 | 0.263404E+09 | 347.86 | 28-NOV-10:20 | 25.73 | 19.64 |
December | 0.247047E+10 | 4252.78 | 04-DEC-15:20 | 26.73 | 21.25 | 0.254232E+09 | 347.86 | 11-DEC-10:20 | 24.07 | 19.01 |
Annual Sum or Average | 0.572269E+11 | 0.318646E+10 | ||||||||
Minimum of Months | 0.212635E+10 | 3643.68 | 22.73 | 16.79 | 0.238777E+09 | 347.85 | 22.73 | 16.79 | ||
Maximum of Months | 0.752962E+10 | 12715.64 | 41.00 | 26.08 | 0.289125E+09 | 347.88 | 41.00 | 26.08 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.393461E+09 | 2694.13 | 03-JAN-06:03 | 12.93 |
February | 0.243934E+09 | 2544.00 | 13-FEB-06:03 | 13.03 |
March | 0.200444E+09 | 4601.48 | 28-MAR-05:03 | 25.67 |
April | 83874087.24 | 4472.72 | 25-APR-05:03 | 23.83 |
May | 22941176.25 | 4319.22 | 04-MAY-05:02 | 24.00 |
June | 14945659.10 | 3494.18 | 13-JUN-04:02 | 28.50 |
July | 5760189.49 | 2537.68 | 06-JUL-04:02 | 29.17 |
August | 3962937.07 | 3112.52 | 15-AUG-04:02 | 29.75 |
September | 15062650.47 | 5031.96 | 25-SEP-04:02 | 24.17 |
October | 28708601.02 | 4949.01 | 16-OCT-04:02 | 25.83 |
November | 77688344.07 | 3952.53 | 20-NOV-05:02 | 26.00 |
December | 0.260653E+09 | 2543.88 | 18-DEC-06:03 | 13.17 |
Annual Sum or Average | 0.135144E+10 | |||
Minimum of Months | 3962937.07 | 2537.68 | 12.93 | |
Maximum of Months | 0.393461E+09 | 5031.96 | 29.75 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 24799881.55 | 2216.69 | 29-JAN-10:40 | 25.43 |
February | 15002189.96 | 2457.12 | 05-FEB-11:43 | 30.67 |
March | 11456113.52 | 2367.18 | 26-MAR-14:42 | 32.67 |
April | 15455178.21 | 2407.49 | 02-APR-14:53 | 33.00 |
May | 17716590.79 | 2981.78 | 12-MAY-04:02 | 28.67 |
June | 17482960.30 | 2844.33 | 16-JUN-04:02 | 28.83 |
July | 27645416.91 | 3123.76 | 28-JUL-04:02 | 30.67 |
August | 24830147.17 | 3273.02 | 25-AUG-04:02 | 31.17 |
September | 19780288.15 | 3100.56 | 08-SEP-04:02 | 30.62 |
October | 21514228.09 | 2586.26 | 05-OCT-04:02 | 27.83 |
November | 20471428.47 | 2153.88 | 20-NOV-05:02 | 26.00 |
December | 20066218.60 | 2542.13 | 25-DEC-12:32 | 26.67 |
Annual Sum or Average | 0.236221E+09 | |||
Minimum of Months | 11456113.52 | 2153.88 | 25.43 | |
Maximum of Months | 27645416.91 | 3273.02 | 33.00 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35197992.55 | 3358.59 | 02-JAN-06:12 | 13.00 |
February | 21527089.99 | 2824.37 | 21-FEB-06:12 | 13.90 |
March | 17088821.45 | 2783.61 | 28-MAR-04:03 | 26.08 |
April | 16814350.87 | 2894.98 | 25-APR-04:53 | 24.00 |
May | 19427903.71 | 3566.65 | 12-MAY-04:02 | 28.67 |
June | 23420964.84 | 3597.05 | 16-JUN-04:02 | 28.83 |
July | 43261210.77 | 3911.33 | 27-JUL-04:02 | 30.33 |
August | 44589747.26 | 3878.67 | 31-AUG-04:02 | 28.83 |
September | 38972914.99 | 4411.38 | 28-SEP-04:02 | 27.75 |
October | 36713367.29 | 4410.56 | 05-OCT-04:02 | 27.83 |
November | 34622420.13 | 3841.00 | 20-NOV-05:02 | 26.00 |
December | 32917295.49 | 2347.07 | 18-DEC-06:13 | 13.33 |
Annual Sum or Average | 0.364554E+09 | |||
Minimum of Months | 16814350.87 | 2347.07 | 13.00 | |
Maximum of Months | 44589747.26 | 4411.38 | 30.33 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122795E+09 | 3499.76 | 04-JAN-08:00 | 14.00 |
February | 84397536.99 | 3476.66 | 13-FEB-07:40 | 13.73 |
March | 25131478.75 | 3461.30 | 16-MAR-06:07 | 15.00 |
April | 71307.51 | 594.23 | 05-APR-06:10 | 17.02 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 21531881.81 | 3487.36 | 18-DEC-07:20 | 14.00 |
Annual Sum or Average | 0.253927E+09 | |||
Minimum of Months | 0.00 | 0.00 | 13.73 | |
Maximum of Months | 0.122795E+09 | 3499.76 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.590529E+09 | 792.70 | 04-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.517549E+09 | 813.11 | 09-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.599709E+09 | 941.63 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.521785E+09 | 785.65 | 18-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.547560E+09 | 496.34 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.539355E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.513373E+09 | 583.25 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.575141E+09 | 551.29 | 29-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.525409E+09 | 564.90 | 06-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.560812E+09 | 714.53 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.576439E+09 | 879.27 | 29-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.579907E+09 | 901.00 | 15-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.664757E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.513373E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.599709E+09 | 941.63 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.369077E+09 | 525.69 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.325937E+09 | 525.43 | 09-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.378133E+09 | 587.85 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.330389E+09 | 455.14 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.349002E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.344322E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.326643E+09 | 356.57 | 20-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.365062E+09 | 314.23 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.332465E+09 | 314.23 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.352446E+09 | 345.00 | 27-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.363318E+09 | 571.14 | 29-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.362117E+09 | 577.45 | 14-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.419891E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.325937E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.378133E+09 | 587.85 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.569592E+09 | 705.49 | 23-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.507171E+09 | 772.61 | 09-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.595851E+09 | 939.63 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.522939E+09 | 790.72 | 18-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.553254E+09 | 536.28 | 23-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.545592E+09 | 545.65 | 08-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.517902E+09 | 701.96 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.577811E+09 | 547.73 | 29-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.524575E+09 | 562.30 | 06-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.553190E+09 | 558.02 | 27-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.558346E+09 | 769.90 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.555427E+09 | 846.20 | 15-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.658165E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.507171E+09 | 536.28 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.595851E+09 | 939.63 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.366426E+09 | 498.25 | 09-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.323851E+09 | 474.33 | 09-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.380529E+09 | 599.44 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.332320E+09 | 519.45 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.350165E+09 | 357.81 | 23-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.344765E+09 | 359.26 | 08-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.328188E+09 | 471.92 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.366651E+09 | 431.03 | 29-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.333678E+09 | 446.68 | 06-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.354807E+09 | 486.91 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.356977E+09 | 488.51 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.356900E+09 | 552.17 | 15-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.419526E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.323851E+09 | 357.81 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.380529E+09 | 599.44 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.588594E+09 | 782.53 | 04-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.516194E+09 | 804.35 | 09-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.598509E+09 | 937.83 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.521171E+09 | 775.70 | 18-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.547150E+09 | 496.34 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.538957E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.512835E+09 | 580.42 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.574662E+09 | 547.07 | 29-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.524785E+09 | 561.29 | 06-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.559508E+09 | 700.40 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.574699E+09 | 872.81 | 29-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.577423E+09 | 895.55 | 15-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.663449E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.512835E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.598509E+09 | 937.83 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.368337E+09 | 521.32 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.325324E+09 | 521.33 | 09-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.377556E+09 | 585.51 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.330027E+09 | 447.86 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.348621E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.344002E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.326217E+09 | 354.28 | 20-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.364677E+09 | 314.23 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.332138E+09 | 314.23 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.351888E+09 | 342.86 | 27-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.362596E+09 | 568.37 | 29-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.361274E+09 | 574.92 | 14-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.419266E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.325324E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.377556E+09 | 585.51 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.569021E+09 | 691.77 | 23-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.506486E+09 | 762.02 | 09-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.594720E+09 | 935.74 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.522230E+09 | 781.02 | 18-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.552508E+09 | 531.47 | 23-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.544985E+09 | 541.29 | 08-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.517189E+09 | 688.84 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.577109E+09 | 543.29 | 29-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.523958E+09 | 558.54 | 06-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.552648E+09 | 553.81 | 27-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.557885E+09 | 758.35 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.554675E+09 | 838.20 | 15-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.657341E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.506486E+09 | 531.47 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.594720E+09 | 935.74 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.365397E+09 | 493.27 | 09-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.323203E+09 | 468.67 | 09-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.379808E+09 | 597.62 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.331745E+09 | 515.20 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.349703E+09 | 356.00 | 23-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.344178E+09 | 357.47 | 08-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.327703E+09 | 466.22 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.366213E+09 | 424.22 | 29-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.333122E+09 | 440.35 | 06-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.354100E+09 | 480.84 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.356290E+09 | 482.37 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.356124E+09 | 548.88 | 15-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.418759E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.323203E+09 | 356.00 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.379808E+09 | 597.62 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.590527E+09 | 792.68 | 04-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.517548E+09 | 813.09 | 09-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.599708E+09 | 941.62 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.521784E+09 | 785.63 | 18-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.547560E+09 | 496.34 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.539354E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.513372E+09 | 583.24 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.575140E+09 | 551.28 | 29-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.525408E+09 | 564.89 | 06-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.560811E+09 | 714.51 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.576437E+09 | 879.26 | 29-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.579905E+09 | 900.98 | 15-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.664755E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.513372E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.599708E+09 | 941.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.369076E+09 | 525.68 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.325936E+09 | 525.42 | 09-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.378132E+09 | 587.84 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.330389E+09 | 455.13 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.349001E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.344322E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.326642E+09 | 356.57 | 20-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.365062E+09 | 314.23 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.332465E+09 | 314.23 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.352446E+09 | 344.99 | 27-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.363317E+09 | 571.13 | 29-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.362117E+09 | 577.44 | 14-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.419891E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.325936E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.378132E+09 | 587.84 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.569591E+09 | 705.47 | 23-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.507170E+09 | 772.59 | 09-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.595850E+09 | 939.62 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.522938E+09 | 790.70 | 18-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.553237E+09 | 536.27 | 23-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.545591E+09 | 545.64 | 08-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.517901E+09 | 701.93 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.577811E+09 | 547.72 | 29-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.524575E+09 | 562.29 | 06-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.553190E+09 | 558.01 | 27-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.558346E+09 | 769.88 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.555427E+09 | 846.18 | 15-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.658163E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.507170E+09 | 536.27 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.595850E+09 | 939.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.366425E+09 | 498.23 | 09-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.323849E+09 | 474.32 | 09-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.380528E+09 | 599.43 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.332309E+09 | 519.44 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.350165E+09 | 357.81 | 23-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.344764E+09 | 359.26 | 08-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.328187E+09 | 471.91 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.366650E+09 | 431.01 | 29-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.333678E+09 | 446.66 | 06-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.354807E+09 | 486.90 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.356977E+09 | 488.50 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.356899E+09 | 552.16 | 15-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.419524E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.323849E+09 | 357.81 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.380528E+09 | 599.43 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.590529E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2267503.69 | 0.156750E+09 |
February | 0.901968E+09 | 0.517549E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17075462.49 | 0.158587E+09 |
March | 0.107774E+10 | 0.599709E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42807484.27 | 87886021.05 |
April | 0.956342E+09 | 0.521785E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102273E+09 | 40309295.25 |
May | 0.103597E+10 | 0.547560E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253125E+09 | 4697501.23 |
June | 0.103308E+10 | 0.539355E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315859E+09 | 467648.67 |
July | 0.959235E+09 | 0.513373E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452416E+09 | 0.00 |
August | 0.107774E+10 | 0.575141E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433864E+09 | 0.00 |
September | 0.956342E+09 | 0.525409E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303161E+09 | 716364.17 |
October | 0.994195E+09 | 0.560812E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172970E+09 | 6637243.63 |
November | 0.984487E+09 | 0.576439E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71563842.85 | 41720877.73 |
December | 0.959235E+09 | 0.579907E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11388462.11 | 0.115057E+09 |
Annual Sum or Average | 0.119305E+11 | 0.664757E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217877E+10 | 0.612829E+09 |
Minimum of Months | 0.901968E+09 | 0.513373E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2267503.69 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.599709E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452416E+09 | 0.158587E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.369077E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 831469.97 | 0.110385E+09 |
February | 0.571020E+09 | 0.325937E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9987166.71 | 0.110102E+09 |
March | 0.682301E+09 | 0.378133E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27809622.32 | 61047735.47 |
April | 0.605444E+09 | 0.330389E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66199254.76 | 27757424.39 |
May | 0.655854E+09 | 0.349002E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167311E+09 | 3283323.77 |
June | 0.654023E+09 | 0.344322E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209630E+09 | 350909.59 |
July | 0.607275E+09 | 0.326643E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300105E+09 | 0.00 |
August | 0.682301E+09 | 0.365062E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287681E+09 | 0.00 |
September | 0.605444E+09 | 0.332465E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200129E+09 | 507601.23 |
October | 0.629407E+09 | 0.352446E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113171E+09 | 4836891.19 |
November | 0.623262E+09 | 0.363318E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44624414.47 | 29687485.13 |
December | 0.607275E+09 | 0.362117E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6573644.98 | 79812598.86 |
Annual Sum or Average | 0.755301E+10 | 0.419891E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143405E+10 | 0.427771E+09 |
Minimum of Months | 0.571020E+09 | 0.325937E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 831469.97 | 0.00 |
Maximum of Months | 0.682301E+09 | 0.378133E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300105E+09 | 0.110385E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.569592E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 918419.03 | 0.180788E+09 |
February | 0.901968E+09 | 0.507171E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14611309.45 | 0.174222E+09 |
March | 0.107774E+10 | 0.595851E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41279790.15 | 94970181.69 |
April | 0.956342E+09 | 0.522939E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100132E+09 | 41348841.45 |
May | 0.103597E+10 | 0.553254E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253385E+09 | 4718563.00 |
June | 0.103308E+10 | 0.545592E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316653E+09 | 456619.07 |
July | 0.959235E+09 | 0.517902E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452989E+09 | 0.00 |
August | 0.107774E+10 | 0.577811E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433336E+09 | 0.00 |
September | 0.956342E+09 | 0.524575E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300299E+09 | 768229.50 |
October | 0.994195E+09 | 0.553190E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167190E+09 | 7790019.64 |
November | 0.984487E+09 | 0.558346E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63339833.11 | 47237522.12 |
December | 0.959235E+09 | 0.555427E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8413613.77 | 0.132058E+09 |
Annual Sum or Average | 0.119305E+11 | 0.658165E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215255E+10 | 0.684358E+09 |
Minimum of Months | 0.901968E+09 | 0.507171E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 918419.03 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.595851E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452989E+09 | 0.180788E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.366426E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1142162.60 | 0.110978E+09 |
February | 0.570983E+09 | 0.323851E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10746538.55 | 0.111115E+09 |
March | 0.682256E+09 | 0.380529E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27716831.31 | 63120442.54 |
April | 0.605404E+09 | 0.332320E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65756279.62 | 28773234.19 |
May | 0.655811E+09 | 0.350165E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166565E+09 | 3389355.73 |
June | 0.653980E+09 | 0.344765E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208121E+09 | 360054.33 |
July | 0.607235E+09 | 0.328188E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299294E+09 | 0.00 |
August | 0.682256E+09 | 0.366651E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286797E+09 | 0.00 |
September | 0.605404E+09 | 0.333678E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198927E+09 | 518872.02 |
October | 0.629366E+09 | 0.354807E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112159E+09 | 4911389.03 |
November | 0.623221E+09 | 0.356977E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44560777.56 | 29460085.40 |
December | 0.607235E+09 | 0.356900E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6536033.48 | 81459346.07 |
Annual Sum or Average | 0.755252E+10 | 0.419526E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142832E+10 | 0.434085E+09 |
Minimum of Months | 0.570983E+09 | 0.323851E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1142162.60 | 0.00 |
Maximum of Months | 0.682256E+09 | 0.380529E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299294E+09 | 0.111115E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.588594E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1133504.41 | 98326924.04 |
February | 0.901968E+09 | 0.516194E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9621782.55 | 94531005.97 |
March | 0.107774E+10 | 0.598509E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23794279.11 | 49651905.23 |
April | 0.956342E+09 | 0.521171E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57881417.90 | 21671676.48 |
May | 0.103597E+10 | 0.547150E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138293E+09 | 2324667.22 |
June | 0.103308E+10 | 0.538957E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171379E+09 | 207829.37 |
July | 0.959235E+09 | 0.512835E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244165E+09 | 0.00 |
August | 0.107774E+10 | 0.574662E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233739E+09 | 0.00 |
September | 0.956342E+09 | 0.524785E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163749E+09 | 378808.81 |
October | 0.994195E+09 | 0.559508E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92613760.90 | 4333001.31 |
November | 0.984487E+09 | 0.574699E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38397478.83 | 27931107.94 |
December | 0.959235E+09 | 0.577423E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6024009.39 | 74221852.50 |
Annual Sum or Average | 0.119305E+11 | 0.663449E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118079E+10 | 0.373579E+09 |
Minimum of Months | 0.901968E+09 | 0.512835E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1133504.41 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.598509E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244165E+09 | 98326924.04 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.368337E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 424459.33 | 69181791.73 |
February | 0.571020E+09 | 0.325324E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5587778.43 | 66130830.02 |
March | 0.682301E+09 | 0.377556E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15198511.39 | 34878869.61 |
April | 0.605444E+09 | 0.330027E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36405913.07 | 15457036.13 |
May | 0.655854E+09 | 0.348621E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90499909.34 | 1777806.96 |
June | 0.654023E+09 | 0.344002E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112899E+09 | 177413.88 |
July | 0.607275E+09 | 0.326217E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161173E+09 | 0.00 |
August | 0.682301E+09 | 0.364677E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154282E+09 | 0.00 |
September | 0.605444E+09 | 0.332138E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107271E+09 | 298230.20 |
October | 0.629407E+09 | 0.351888E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60094981.00 | 3365496.35 |
November | 0.623262E+09 | 0.362596E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23787346.01 | 20235698.15 |
December | 0.607275E+09 | 0.361274E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3543326.05 | 51479141.61 |
Annual Sum or Average | 0.755301E+10 | 0.419266E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.771166E+09 | 0.262982E+09 |
Minimum of Months | 0.571020E+09 | 0.325324E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 424459.33 | 0.00 |
Maximum of Months | 0.682301E+09 | 0.377556E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161173E+09 | 69181791.73 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.569021E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21691254.92 | 0.151981E+10 |
February | 0.901968E+09 | 0.506486E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257173E+09 | 0.945131E+09 |
March | 0.107774E+10 | 0.594720E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.889652E+09 | 0.602368E+09 |
April | 0.956342E+09 | 0.522230E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165308E+10 | 0.220348E+09 |
May | 0.103597E+10 | 0.552508E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342182E+10 | 37918123.95 |
June | 0.103308E+10 | 0.544985E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402893E+10 | 1453227.75 |
July | 0.959235E+09 | 0.517189E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427692E+10 | 0.00 |
August | 0.107774E+10 | 0.577109E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491733E+10 | 0.00 |
September | 0.956342E+09 | 0.523958E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342192E+10 | 3100782.59 |
October | 0.994195E+09 | 0.552648E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247209E+10 | 27801877.55 |
November | 0.984487E+09 | 0.557885E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132378E+10 | 0.319288E+09 |
December | 0.959235E+09 | 0.554675E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203973E+09 | 0.890044E+09 |
Annual Sum or Average | 0.119305E+11 | 0.657341E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268884E+11 | 0.456727E+10 |
Minimum of Months | 0.901968E+09 | 0.506486E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21691254.92 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.594720E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491733E+10 | 0.151981E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.365397E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 533365.85 | 69655282.98 |
February | 0.570983E+09 | 0.323203E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5828008.66 | 66915332.98 |
March | 0.682256E+09 | 0.379808E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14990639.53 | 36436017.77 |
April | 0.605404E+09 | 0.331745E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35960437.99 | 16044099.38 |
May | 0.655811E+09 | 0.349703E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89864182.31 | 1867349.72 |
June | 0.653980E+09 | 0.344178E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111839E+09 | 189493.65 |
July | 0.607235E+09 | 0.327703E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160538E+09 | 0.00 |
August | 0.682256E+09 | 0.366213E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153659E+09 | 0.00 |
September | 0.605404E+09 | 0.333122E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106476E+09 | 312352.23 |
October | 0.629366E+09 | 0.354100E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59414777.95 | 3482067.32 |
November | 0.623221E+09 | 0.356290E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23565371.97 | 20347708.79 |
December | 0.607235E+09 | 0.356124E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3491070.64 | 52404902.25 |
Annual Sum or Average | 0.755252E+10 | 0.418759E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766159E+09 | 0.267655E+09 |
Minimum of Months | 0.570983E+09 | 0.323203E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 533365.85 | 0.00 |
Maximum of Months | 0.682256E+09 | 0.379808E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160538E+09 | 69655282.98 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.590527E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1852317.96 | 0.143935E+09 |
February | 0.901968E+09 | 0.517548E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14674857.63 | 0.142751E+09 |
March | 0.107774E+10 | 0.599708E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36079750.08 | 78627095.52 |
April | 0.956342E+09 | 0.521784E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87034495.99 | 35721808.07 |
May | 0.103597E+10 | 0.547560E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212986E+09 | 4061514.89 |
June | 0.103308E+10 | 0.539354E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265121E+09 | 376146.60 |
July | 0.959235E+09 | 0.513372E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378996E+09 | 0.00 |
August | 0.107774E+10 | 0.575140E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363132E+09 | 0.00 |
September | 0.956342E+09 | 0.525408E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254520E+09 | 597483.36 |
October | 0.994195E+09 | 0.560811E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145586E+09 | 5962344.91 |
November | 0.984487E+09 | 0.576437E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60850123.35 | 38682342.97 |
December | 0.959235E+09 | 0.579905E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9615508.05 | 0.105482E+09 |
Annual Sum or Average | 0.119305E+11 | 0.664755E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183045E+10 | 0.556197E+09 |
Minimum of Months | 0.901968E+09 | 0.513372E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1852317.96 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.599708E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378996E+09 | 0.143935E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.369076E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 630778.82 | 0.101022E+09 |
February | 0.421807E+09 | 0.325936E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8277287.83 | 99058205.66 |
March | 0.502994E+09 | 0.378132E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22681380.01 | 54614772.58 |
April | 0.447140E+09 | 0.330389E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55037667.79 | 24588059.29 |
May | 0.484071E+09 | 0.349001E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139771E+09 | 2841854.26 |
June | 0.482240E+09 | 0.344322E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174817E+09 | 285747.93 |
July | 0.448971E+09 | 0.326642E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250313E+09 | 0.00 |
August | 0.502994E+09 | 0.365062E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239625E+09 | 0.00 |
September | 0.447140E+09 | 0.332465E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166922E+09 | 423753.65 |
October | 0.465148E+09 | 0.352446E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94304602.05 | 4337118.35 |
November | 0.460569E+09 | 0.363317E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37017663.26 | 27303343.90 |
December | 0.448971E+09 | 0.362117E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5270217.45 | 73039177.35 |
Annual Sum or Average | 0.557719E+10 | 0.419891E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119467E+10 | 0.387514E+09 |
Minimum of Months | 0.421807E+09 | 0.325936E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 630778.82 | 0.00 |
Maximum of Months | 0.502994E+09 | 0.378132E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250313E+09 | 0.101022E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.569591E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 769071.31 | 0.162456E+09 |
February | 0.901968E+09 | 0.507170E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12342019.41 | 0.155134E+09 |
March | 0.107774E+10 | 0.595850E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34538097.95 | 84448431.44 |
April | 0.956342E+09 | 0.522938E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84572490.82 | 36555352.81 |
May | 0.103597E+10 | 0.553237E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213331E+09 | 4075348.81 |
June | 0.103308E+10 | 0.545591E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266118E+09 | 364157.39 |
July | 0.959235E+09 | 0.517901E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379746E+09 | 0.00 |
August | 0.107774E+10 | 0.577811E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362701E+09 | 0.00 |
September | 0.956342E+09 | 0.524575E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251754E+09 | 641354.40 |
October | 0.994195E+09 | 0.553190E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140295E+09 | 6920611.48 |
November | 0.984487E+09 | 0.558346E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52954994.31 | 43179407.71 |
December | 0.959235E+09 | 0.555427E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7136979.93 | 0.118651E+09 |
Annual Sum or Average | 0.119305E+11 | 0.658163E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180626E+10 | 0.612425E+09 |
Minimum of Months | 0.901968E+09 | 0.507170E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 769071.31 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.595850E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379746E+09 | 0.162456E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.366425E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 914300.63 | 0.100967E+09 |
February | 0.570983E+09 | 0.323849E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9048161.05 | 99394048.67 |
March | 0.682256E+09 | 0.380528E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23216145.28 | 56228946.56 |
April | 0.605404E+09 | 0.332309E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55279002.17 | 25354809.68 |
May | 0.655811E+09 | 0.350165E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139816E+09 | 2927309.08 |
June | 0.653980E+09 | 0.344764E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174475E+09 | 288115.42 |
July | 0.607235E+09 | 0.328187E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250391E+09 | 0.00 |
August | 0.682256E+09 | 0.366650E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239803E+09 | 0.00 |
September | 0.605404E+09 | 0.333678E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166526E+09 | 434241.86 |
October | 0.629366E+09 | 0.354807E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94019977.91 | 4390399.08 |
November | 0.623221E+09 | 0.356977E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37324271.02 | 27126177.30 |
December | 0.607235E+09 | 0.356899E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5512717.97 | 73983903.19 |
Annual Sum or Average | 0.755252E+10 | 0.419524E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119633E+10 | 0.391095E+09 |
Minimum of Months | 0.570983E+09 | 0.323849E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 914300.63 | 0.00 |
Maximum of Months | 0.682256E+09 | 0.380528E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250391E+09 | 0.100967E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1172884.30 | 0.216679E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15917700.52 | 0.209321E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39658158.60 | 0.113361E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101928E+09 | 48438270.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261142E+09 | 4832689.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328000E+09 | 469846.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471097E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447791E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311614E+09 | 744102.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171820E+09 | 8358404.25 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64861965.43 | 55667055.98 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8527049.99 | 0.158597E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222353E+10 | 0.816469E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1172884.30 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471097E+09 | 0.216679E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2447620.86 | 0.256991E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21653492.46 | 0.255297E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51920060.98 | 0.139620E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131239E+09 | 61307707.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333768E+09 | 6374737.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420166E+09 | 611622.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604088E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576057E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401324E+09 | 997827.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223070E+09 | 10084827.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87049691.56 | 66973240.50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12510848.80 | 0.189371E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286529E+10 | 0.987630E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2447620.86 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604088E+09 | 0.256991E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 779830.42 | 0.252819E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17820201.82 | 0.248849E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50132531.64 | 0.137467E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116678E+09 | 51980395.13 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339557E+09 | 4490393.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441748E+09 | 474089.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631948E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.610726E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420089E+09 | 698075.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231766E+09 | 6111228.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81979232.57 | 51885343.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7844498.55 | 0.179177E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295107E+10 | 0.933952E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 779830.42 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631948E+09 | 0.252819E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 792.70 | 04-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 148.84 | 29-JAN-12:00 | 394.19 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 813.11 | 09-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 367.69 | 05-FEB-15:00 | 337.81 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 941.63 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 324.72 | 26-MAR-13:53 | 346.43 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 785.65 | 18-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 467.58 | 30-APR-12:55 | 230.40 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2559.94 | 21-MAY-12:51 | 84.85 | 01-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 638.54 | 11-JUN-13:00 | 61.21 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 583.25 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 995.84 | 30-JUL-14:45 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 551.29 | 29-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 930.43 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 1306.65 | 01-SEP-09:09 | 564.90 | 06-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 710.00 | 03-SEP-16:00 | 63.97 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 714.53 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 614.06 | 09-OCT-15:14 | 111.57 | 20-OCT-04:50 |
November | 1306.65 | 01-NOV-09:09 | 879.27 | 29-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.65 | 19-NOV-13:53 | 186.15 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 901.00 | 15-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 169.06 | 10-DEC-11:50 | 265.83 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 148.84 | 0.00 | |||||
Maximum of Months | 1306.65 | 941.63 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2559.94 | 394.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 525.69 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.05 | 29-JAN-12:00 | 263.27 | 18-JAN-04:00 |
February | 827.22 | 01-FEB-10:09 | 525.43 | 09-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 240.99 | 05-FEB-15:28 | 226.41 | 13-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 587.85 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 210.19 | 26-MAR-13:53 | 237.43 | 05-MAR-15:00 |
April | 827.22 | 03-APR-09:09 | 455.14 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 311.03 | 30-APR-12:55 | 153.99 | 05-APR-01:00 |
May | 827.22 | 01-MAY-09:09 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1692.50 | 21-MAY-12:51 | 57.00 | 01-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 427.03 | 11-JUN-13:14 | 41.25 | 07-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 356.57 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 663.78 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 827.22 | 01-AUG-09:09 | 314.23 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 620.28 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 827.22 | 01-SEP-09:09 | 314.23 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 473.33 | 03-SEP-16:00 | 43.16 | 25-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 345.00 | 27-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 410.09 | 09-OCT-15:14 | 74.59 | 20-OCT-04:50 |
November | 827.22 | 01-NOV-09:09 | 571.14 | 29-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.87 | 19-NOV-13:53 | 123.40 | 22-NOV-06:00 |
December | 827.22 | 01-DEC-10:09 | 577.45 | 14-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 96.86 | 10-DEC-13:00 | 175.57 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 48.05 | 0.00 | |||||
Maximum of Months | 827.22 | 587.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1692.50 | 263.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 705.49 | 23-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.94 | 23-JAN-13:00 | 410.69 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 772.61 | 09-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.56 | 05-FEB-15:25 | 355.49 | 10-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 939.63 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 315.21 | 26-MAR-13:53 | 395.60 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 790.72 | 18-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 465.56 | 30-APR-12:55 | 233.27 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 536.28 | 23-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2554.04 | 21-MAY-12:51 | 85.60 | 01-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 545.65 | 08-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 645.96 | 11-JUN-13:14 | 61.41 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 701.96 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 995.68 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 547.73 | 29-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 930.42 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 1306.65 | 01-SEP-09:09 | 562.30 | 06-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 710.00 | 03-SEP-16:00 | 65.15 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 558.02 | 27-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 598.84 | 09-OCT-15:00 | 115.15 | 20-OCT-04:50 |
November | 1306.65 | 01-NOV-09:09 | 769.90 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.26 | 19-NOV-13:53 | 189.44 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 846.20 | 15-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 139.05 | 10-DEC-12:47 | 266.64 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 536.28 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 46.94 | 0.00 | |||||
Maximum of Months | 1306.65 | 939.63 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2554.04 | 410.69 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 498.25 | 09-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 94.09 | 29-JAN-12:00 | 265.36 | 18-JAN-04:00 |
February | 827.17 | 01-FEB-10:09 | 474.33 | 09-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 241.28 | 05-FEB-15:25 | 231.91 | 10-FEB-23:00 |
March | 827.17 | 01-MAR-10:09 | 599.44 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 210.14 | 26-MAR-13:53 | 254.00 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 519.45 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.78 | 30-APR-12:55 | 157.37 | 05-APR-01:00 |
May | 827.17 | 01-MAY-09:09 | 357.81 | 23-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1697.99 | 21-MAY-12:51 | 57.77 | 01-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 359.26 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 433.09 | 11-JUN-13:14 | 42.37 | 07-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 471.92 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 663.78 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 827.17 | 01-AUG-09:09 | 431.03 | 29-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 620.27 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 827.17 | 01-SEP-09:09 | 446.68 | 06-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 473.33 | 03-SEP-16:00 | 43.60 | 25-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 486.91 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 405.56 | 09-OCT-15:14 | 75.95 | 20-OCT-04:40 |
November | 827.17 | 01-NOV-09:09 | 488.51 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.84 | 19-NOV-13:53 | 124.37 | 22-NOV-06:00 |
December | 827.17 | 01-DEC-10:09 | 552.17 | 15-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 110.50 | 10-DEC-11:50 | 175.69 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 357.81 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 94.09 | 0.00 | |||||
Maximum of Months | 827.17 | 599.44 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1697.99 | 265.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 782.53 | 04-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 72.01 | 29-JAN-12:00 | 257.48 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 804.35 | 09-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 221.63 | 05-FEB-15:00 | 207.54 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 937.83 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 192.09 | 26-MAR-13:55 | 181.86 | 06-MAR-06:00 |
April | 1306.65 | 03-APR-09:09 | 775.70 | 18-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.14 | 30-APR-13:08 | 130.52 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1420.16 | 21-MAY-12:51 | 43.56 | 01-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 346.91 | 11-JUN-14:45 | 27.63 | 07-JUN-04:45 |
July | 1306.65 | 03-JUL-09:09 | 580.42 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 533.01 | 30-JUL-14:43 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 547.07 | 29-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 496.71 | 13-AUG-14:14 | 0.00 | 01-AUG-00:05 |
September | 1306.65 | 01-SEP-09:09 | 561.29 | 06-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 390.14 | 03-SEP-15:54 | 37.34 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 700.40 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 327.04 | 09-OCT-15:04 | 76.09 | 20-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 872.81 | 29-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.47 | 19-NOV-13:53 | 121.69 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 895.55 | 15-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 90.91 | 10-DEC-12:00 | 169.27 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 72.01 | 0.00 | |||||
Maximum of Months | 1306.65 | 937.83 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1420.16 | 257.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 521.32 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.64 | 29-JAN-12:00 | 177.06 | 18-JAN-04:00 |
February | 827.22 | 01-FEB-10:09 | 521.33 | 09-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 131.29 | 05-FEB-15:00 | 141.54 | 13-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 585.51 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 117.70 | 26-MAR-13:53 | 121.46 | 05-MAR-15:00 |
April | 827.22 | 03-APR-09:09 | 447.86 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.05 | 30-APR-13:05 | 88.96 | 05-APR-01:00 |
May | 827.22 | 01-MAY-09:09 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 946.76 | 21-MAY-12:53 | 30.55 | 01-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.44 | 11-JUN-14:45 | 19.70 | 07-JUN-04:45 |
July | 827.22 | 03-JUL-09:09 | 354.28 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 358.54 | 30-JUL-14:43 | 0.00 | 01-JUL-00:10 |
August | 827.22 | 01-AUG-09:09 | 314.23 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.35 | 13-AUG-14:14 | 0.00 | 01-AUG-00:05 |
September | 827.22 | 01-SEP-09:09 | 314.23 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.83 | 03-SEP-15:54 | 26.46 | 25-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 342.86 | 27-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.68 | 09-OCT-15:04 | 53.14 | 20-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 568.37 | 29-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.72 | 19-NOV-14:06 | 81.66 | 22-NOV-06:00 |
December | 827.22 | 01-DEC-10:09 | 574.92 | 14-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.33 | 10-DEC-12:40 | 112.46 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 21.64 | 0.00 | |||||
Maximum of Months | 827.22 | 585.51 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 946.76 | 177.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 691.77 | 23-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4217.14 | 23-JAN-13:00 | 12500.87 | 09-JAN-07:02 |
February | 1306.65 | 01-FEB-10:09 | 762.02 | 09-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7415.85 | 07-FEB-13:00 | 10949.72 | 01-FEB-07:02 |
March | 1306.65 | 01-MAR-10:09 | 935.74 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15800.79 | 27-MAR-11:01 | 9090.94 | 07-MAR-07:02 |
April | 1306.65 | 03-APR-09:09 | 781.02 | 18-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18450.65 | 28-APR-11:01 | 6869.25 | 05-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 531.47 | 23-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18294.47 | 09-MAY-11:01 | 4420.27 | 01-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 541.29 | 08-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20290.15 | 12-JUN-11:01 | 541.51 | 22-JUN-08:00 |
July | 1306.65 | 03-JUL-09:09 | 688.84 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23320.61 | 21-JUL-11:01 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 543.29 | 29-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22643.66 | 16-AUG-11:01 | 0.00 | 01-AUG-00:05 |
September | 1306.65 | 01-SEP-09:09 | 558.54 | 06-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17788.11 | 12-SEP-11:01 | 1055.03 | 25-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 553.81 | 27-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14175.31 | 04-OCT-11:01 | 2698.75 | 30-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 758.35 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9247.15 | 01-NOV-11:02 | 7981.56 | 27-NOV-07:02 |
December | 1306.65 | 01-DEC-10:09 | 838.20 | 15-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4915.40 | 01-DEC-12:05 | 11734.11 | 26-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 531.47 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 4217.14 | 0.00 | |||||
Maximum of Months | 1306.65 | 935.74 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 23320.61 | 12500.87 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 493.27 | 09-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 | 29-JAN-12:00 | 177.45 | 18-JAN-04:00 |
February | 827.17 | 01-FEB-10:09 | 468.67 | 09-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 127.33 | 05-FEB-15:28 | 143.47 | 10-FEB-23:10 |
March | 827.17 | 01-MAR-10:09 | 597.62 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 114.48 | 26-MAR-13:53 | 130.88 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 515.20 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.78 | 30-APR-13:05 | 91.15 | 05-APR-01:00 |
May | 827.17 | 01-MAY-09:09 | 356.00 | 23-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 946.76 | 21-MAY-12:53 | 31.09 | 01-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 357.47 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.01 | 11-JUN-14:45 | 20.72 | 07-JUN-04:45 |
July | 827.17 | 03-JUL-09:09 | 466.22 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 354.16 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 827.17 | 01-AUG-09:09 | 424.22 | 29-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.08 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 827.17 | 01-SEP-09:09 | 440.35 | 06-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 255.48 | 03-SEP-15:54 | 26.86 | 25-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 480.84 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.62 | 09-OCT-15:06 | 54.22 | 20-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 482.37 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.35 | 19-NOV-14:04 | 82.64 | 22-NOV-06:00 |
December | 827.17 | 01-DEC-10:09 | 548.88 | 15-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.78 | 10-DEC-12:00 | 112.53 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 356.00 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 | 0.00 | |||||
Maximum of Months | 827.17 | 597.62 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 946.76 | 177.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 792.68 | 04-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 116.99 | 29-JAN-12:00 | 368.91 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 813.09 | 09-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 325.19 | 05-FEB-14:50 | 310.01 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 941.62 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 268.92 | 26-MAR-13:53 | 287.42 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 785.63 | 18-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 382.89 | 30-APR-12:53 | 203.69 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2155.34 | 21-MAY-12:51 | 71.92 | 01-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 541.22 | 11-JUN-14:45 | 52.07 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 583.24 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 830.28 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 551.28 | 29-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 776.02 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 1306.65 | 01-SEP-09:09 | 564.89 | 06-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 598.23 | 04-SEP-16:54 | 54.68 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 714.51 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 504.82 | 09-OCT-15:04 | 101.98 | 20-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 879.26 | 29-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 326.39 | 19-NOV-14:00 | 171.56 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 900.98 | 15-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 146.22 | 10-DEC-12:20 | 241.06 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 116.99 | 0.00 | |||||
Maximum of Months | 1306.65 | 941.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2155.34 | 368.91 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 525.68 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.15 | 29-JAN-12:00 | 246.43 | 18-JAN-04:00 |
February | 805.43 | 01-FEB-08:09 | 525.42 | 09-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 193.40 | 05-FEB-14:50 | 207.46 | 13-FEB-04:00 |
March | 805.43 | 01-MAR-08:09 | 587.84 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 179.32 | 26-MAR-14:06 | 196.88 | 05-MAR-15:00 |
April | 805.43 | 03-APR-07:10 | 455.13 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 255.26 | 30-APR-12:53 | 136.28 | 05-APR-01:00 |
May | 805.43 | 01-MAY-07:10 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1426.08 | 21-MAY-12:51 | 48.34 | 01-MAY-05:00 |
June | 805.43 | 01-JUN-07:10 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 360.55 | 11-JUN-14:45 | 35.20 | 07-JUN-05:00 |
July | 805.43 | 03-JUL-07:10 | 356.57 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 553.52 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 805.43 | 01-AUG-07:10 | 314.23 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 517.34 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 805.43 | 01-SEP-07:10 | 314.23 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 401.58 | 04-SEP-16:54 | 36.86 | 25-SEP-05:00 |
October | 805.43 | 02-OCT-07:10 | 344.99 | 27-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.84 | 09-OCT-15:03 | 68.19 | 20-OCT-05:00 |
November | 805.43 | 01-NOV-07:10 | 571.13 | 29-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.89 | 19-NOV-13:53 | 113.74 | 22-NOV-06:00 |
December | 805.43 | 01-DEC-08:09 | 577.44 | 14-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.69 | 10-DEC-13:00 | 159.48 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 33.15 | 0.00 | |||||
Maximum of Months | 805.43 | 587.84 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1426.08 | 246.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 705.47 | 23-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.38 | 23-JAN-13:00 | 381.72 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 772.59 | 09-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 282.45 | 05-FEB-15:07 | 320.71 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 939.62 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 267.11 | 26-MAR-14:04 | 325.72 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 790.70 | 18-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 382.89 | 30-APR-12:53 | 206.01 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 536.27 | 23-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2150.76 | 21-MAY-12:51 | 72.60 | 01-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 545.64 | 08-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 541.19 | 11-JUN-14:45 | 52.16 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 701.93 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 830.28 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 547.72 | 29-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 776.02 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 1306.65 | 01-SEP-09:09 | 562.29 | 06-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 598.85 | 04-SEP-16:54 | 55.75 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 558.01 | 27-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 502.40 | 09-OCT-15:04 | 104.99 | 20-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 769.88 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 277.41 | 19-NOV-14:00 | 174.07 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 846.18 | 15-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 115.53 | 10-DEC-12:37 | 241.55 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 536.27 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 39.38 | 0.00 | |||||
Maximum of Months | 1306.65 | 939.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2150.76 | 381.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 498.23 | 09-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 73.33 | 29-JAN-12:00 | 247.68 | 18-JAN-04:00 |
February | 827.17 | 01-FEB-10:09 | 474.32 | 09-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.40 | 05-FEB-15:07 | 209.22 | 10-FEB-23:10 |
March | 827.17 | 01-MAR-10:09 | 599.43 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.95 | 26-MAR-14:04 | 210.39 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 519.44 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 255.26 | 30-APR-12:53 | 138.86 | 05-APR-01:00 |
May | 827.17 | 01-MAY-09:09 | 357.81 | 23-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1429.98 | 21-MAY-12:51 | 49.07 | 01-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 359.26 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 356.55 | 11-JUN-13:25 | 36.00 | 07-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 471.91 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 553.52 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 827.17 | 01-AUG-09:09 | 431.01 | 29-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 517.34 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 827.17 | 01-SEP-09:09 | 446.66 | 06-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 394.96 | 03-SEP-15:58 | 37.25 | 25-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 486.90 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.04 | 09-OCT-15:06 | 69.01 | 20-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 488.50 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.28 | 19-NOV-13:48 | 114.42 | 22-NOV-06:00 |
December | 827.17 | 01-DEC-10:09 | 552.16 | 15-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 95.33 | 10-DEC-12:10 | 159.32 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 357.81 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 73.33 | 0.00 | |||||
Maximum of Months | 827.17 | 599.43 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1429.98 | 247.68 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.64 | 29-JAN-11:55 | 550.55 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.35 | 05-FEB-15:00 | 455.57 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.06 | 26-MAR-14:00 | 405.33 | 06-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.58 | 30-APR-12:53 | 285.13 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2707.12 | 21-MAY-13:00 | 92.47 | 01-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 666.89 | 11-JUN-13:10 | 66.83 | 07-JUN-04:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1026.51 | 30-JUL-14:30 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 970.08 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 717.92 | 03-SEP-16:00 | 70.80 | 25-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.93 | 09-OCT-14:52 | 139.88 | 20-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.74 | 19-NOV-13:53 | 250.07 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.80 | 10-DEC-12:03 | 350.97 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.64 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2707.12 | 550.55 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.20 | 29-JAN-11:55 | 657.34 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551.61 | 05-FEB-14:53 | 557.86 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.04 | 26-MAR-13:53 | 498.65 | 06-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 639.45 | 30-APR-13:00 | 360.48 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3469.78 | 21-MAY-12:51 | 121.73 | 01-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 851.11 | 11-JUN-13:10 | 84.06 | 07-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1313.73 | 30-JUL-14:30 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1240.36 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 919.03 | 03-SEP-16:00 | 93.63 | 25-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 765.59 | 09-OCT-14:52 | 168.34 | 20-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524.09 | 19-NOV-14:00 | 308.56 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.51 | 10-DEC-13:00 | 431.21 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.20 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3469.78 | 657.34 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.58 | 29-JAN-11:55 | 578.13 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.48 | 05-FEB-15:00 | 526.64 | 19-FEB-19:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.08 | 02-MAR-04:00 | 625.09 | 05-MAR-15:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554.40 | 30-APR-13:00 | 323.16 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3118.65 | 21-MAY-12:51 | 117.86 | 01-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 768.94 | 09-JUN-03:00 | 71.33 | 07-JUN-04:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1269.97 | 30-JUL-14:30 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1164.98 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 903.55 | 04-SEP-17:00 | 82.05 | 25-SEP-04:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 716.98 | 09-OCT-15:00 | 140.46 | 20-OCT-04:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.40 | 19-NOV-13:55 | 258.25 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.60 | 10-DEC-11:53 | 395.66 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.58 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3118.65 | 625.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 43494.02 | 02-JAN-06:12 | 3176.32 | 2742.16 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 42373.75 | 21-FEB-06:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 43432.35 | 28-MAR-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 44005.68 | 25-APR-04:53 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43752.53 | 16-MAY-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 43272.86 | 07-JUN-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 37367.90 | 03-JUL-06:03 | 3811.58 | 4936.08 | 26390.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 37545.69 | 15-AUG-04:02 | 0.00 | 1058.67 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 40947.09 | 26-SEP-04:02 | 0.00 | 1058.67 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 42955.48 | 31-OCT-04:03 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 43225.32 | 27-NOV-06:12 | 3176.32 | 2742.16 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 42720.17 | 04-DEC-06:12 | 2541.06 | 2193.73 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 37367.90 | 0.00 | 846.94 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44005.68 | 3811.58 | 4936.08 | 26390.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5248.44 | 31-JAN-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.23 |
February | 8114.35 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.79 | 0.00 |
March | 11040.79 | 27-MAR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.78 | 0.00 |
April | 12144.79 | 28-APR-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.89 | 0.00 |
May | 12541.11 | 10-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.74 | 0.00 |
June | 13300.34 | 12-JUN-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.24 | 0.00 |
July | 14279.54 | 21-JUL-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.07 | 0.00 |
August | 14312.23 | 16-AUG-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.86 | 0.00 |
September | 16470.66 | 03-SEP-14:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 701.47 | 0.00 |
October | 11262.72 | 02-OCT-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.41 | 0.00 |
November | 9324.19 | 06-NOV-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.69 | 0.00 |
December | 6831.45 | 04-DEC-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5248.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16470.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 701.47 | 31.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2251.84 | 31-JAN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.93 |
February | 4167.53 | 06-FEB-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.64 | 0.00 |
March | 5588.56 | 27-MAR-12:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.25 | 0.00 |
April | 5682.48 | 24-APR-12:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.87 | 0.00 |
May | 7792.98 | 30-MAY-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.05 | 0.00 |
June | 7865.35 | 12-JUN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.17 | 0.00 |
July | 7868.51 | 05-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.43 | 0.00 |
August | 7790.36 | 07-AUG-12:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.43 | 0.00 |
September | 8028.92 | 05-SEP-12:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.67 | 0.00 |
October | 6942.60 | 02-OCT-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.90 | 0.00 |
November | 5406.71 | 13-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.04 | 0.00 |
December | 3507.28 | 04-DEC-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2251.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8028.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.25 | 31.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3617.01 | 02-JAN-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.66 |
February | 4804.97 | 06-FEB-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.00 | 0.00 |
March | 7261.14 | 27-MAR-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.41 | 0.00 |
April | 7149.61 | 26-APR-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.59 | 0.00 |
May | 9194.49 | 22-MAY-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.22 | 0.00 |
June | 8850.89 | 26-JUN-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.22 | 0.00 |
July | 9282.17 | 31-JUL-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.50 | 0.00 |
August | 9157.73 | 07-AUG-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.34 | 0.00 |
September | 8437.18 | 12-SEP-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.28 | 0.00 |
October | 6949.56 | 02-OCT-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.87 | 0.00 |
November | 5948.30 | 13-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.39 | 0.00 |
December | 4891.18 | 04-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3617.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9282.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.41 | 31.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 21128.89 | 30-JAN-06:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 31692.60 | 06-FEB-06:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 32007.78 | 27-MAR-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32785.75 | 03-APR-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34048.48 | 15-MAY-05:14 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32475.89 | 06-JUN-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29819.84 | 03-JUL-06:03 | 3811.58 | 4936.08 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29186.56 | 15-AUG-06:03 | 3811.58 | 4936.08 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32205.84 | 26-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32769.68 | 17-OCT-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33049.68 | 13-NOV-06:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 31762.10 | 11-DEC-06:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 21128.89 | 0.00 | 846.94 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34048.48 | 3811.58 | 4936.08 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14611.31 | 30-JAN-14:50 | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18935.10 | 06-FEB-06:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 35929.84 | 27-MAR-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35896.27 | 24-APR-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36074.68 | 01-MAY-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 36661.74 | 06-JUN-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33524.57 | 10-JUL-06:03 | 3811.58 | 4936.08 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33678.19 | 07-AUG-06:03 | 3811.58 | 4936.08 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37138.30 | 25-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 36867.94 | 23-OCT-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 36684.27 | 20-NOV-05:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16363.94 | 11-DEC-07:03 | 3811.58 | 4936.08 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14611.31 | 0.00 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37138.30 | 6198.29 | 4936.08 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4092.08 | 23-JAN-14:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 36.50 | 0.00 |
February | 5871.43 | 06-FEB-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 116.29 | 0.00 |
March | 7246.99 | 27-MAR-13:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 213.76 | 0.00 |
April | 11976.30 | 30-APR-12:13 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 275.47 | 0.00 |
May | 16050.44 | 21-MAY-13:02 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 2200.45 | 0.00 |
June | 15157.01 | 11-JUN-09:52 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 465.65 | 0.00 |
July | 15956.01 | 23-JUL-09:52 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 516.12 | 0.00 |
August | 15422.66 | 20-AUG-10:12 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 438.64 | 0.00 |
September | 15672.39 | 04-SEP-12:32 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 498.52 | 0.00 |
October | 15168.94 | 29-OCT-13:42 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 349.25 | 0.00 |
November | 8459.62 | 12-NOV-14:42 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 102.86 | 0.00 |
December | 4606.31 | 11-DEC-14:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 32.42 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4092.08 | 267.84 | 110.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 32.42 | 0.00 | |
Maximum of Months | 16050.44 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 2200.45 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3054.79 | 24-JAN-11:00 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
February | 6356.92 | 05-FEB-15:23 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 214.64 | 0.00 |
March | 7302.14 | 26-MAR-11:33 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 46.69 | 0.00 |
April | 11877.71 | 30-APR-12:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 181.92 | 0.00 |
May | 12654.96 | 21-MAY-13:02 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1464.58 | 0.00 |
June | 12901.50 | 18-JUN-09:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 193.97 | 0.00 |
July | 13383.11 | 23-JUL-09:52 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 319.72 | 0.00 |
August | 13018.14 | 20-AUG-10:12 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 263.17 | 0.00 |
September | 13231.11 | 04-SEP-09:12 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 214.92 | 0.00 |
October | 12069.27 | 08-OCT-10:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 41.90 | 0.00 |
November | 9829.09 | 05-NOV-11:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 84.47 | 0.00 |
December | 3522.10 | 04-DEC-11:00 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3054.79 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13383.11 | 827.22 | 314.23 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1464.58 | 0.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10210.92 | 22-JAN-14:23 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.95 |
February | 17468.27 | 05-FEB-15:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 307.07 | 0.00 |
March | 12830.71 | 26-MAR-14:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 293.67 | 0.00 |
April | 17268.02 | 30-APR-12:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 271.21 | 0.00 |
May | 17768.10 | 21-MAY-13:02 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 2208.22 | 0.00 |
June | 16530.68 | 11-JUN-09:52 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 475.95 | 0.00 |
July | 17580.75 | 30-JUL-13:22 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 808.37 | 0.00 |
August | 17123.56 | 20-AUG-10:12 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 438.42 | 0.00 |
September | 17899.22 | 04-SEP-12:32 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 483.84 | 0.00 |
October | 18809.40 | 29-OCT-13:42 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 272.81 | 0.00 |
November | 18474.42 | 05-NOV-12:02 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 135.46 | 0.00 |
December | 17724.00 | 03-DEC-13:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10210.92 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18809.40 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 2208.22 | 15.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3729.49 | 31-JAN-16:20 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.14 |
February | 10110.18 | 05-FEB-15:23 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 211.94 | 0.00 |
March | 8527.15 | 26-MAR-15:32 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 153.19 | 0.00 |
April | 12051.35 | 23-APR-14:13 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 158.32 | 0.00 |
May | 14189.21 | 21-MAY-16:22 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 374.46 | 0.00 |
June | 13496.92 | 18-JUN-14:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 269.27 | 0.00 |
July | 14167.88 | 02-JUL-16:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 327.39 | 0.00 |
August | 14122.84 | 06-AUG-15:02 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 377.42 | 0.00 |
September | 14178.11 | 03-SEP-14:53 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 417.44 | 0.00 |
October | 14104.79 | 29-OCT-15:42 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 166.36 | 0.00 |
November | 12722.46 | 12-NOV-14:42 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 65.52 | 0.00 |
December | 4413.07 | 06-DEC-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 23.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3729.49 | 169.55 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14189.21 | 805.38 | 314.21 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 417.44 | 11.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4123.56 | 23-JAN-14:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 19.70 | 0.00 |
February | 5251.34 | 06-FEB-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 62.21 | 0.00 |
March | 6128.98 | 27-MAR-13:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 114.15 | 0.00 |
April | 7987.30 | 30-APR-13:43 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 203.41 | 0.00 |
May | 10911.64 | 08-MAY-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 4.52 | 0.00 |
June | 12036.31 | 18-JUN-12:43 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 219.45 | 0.00 |
July | 13401.83 | 23-JUL-09:52 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 281.87 | 0.00 |
August | 13430.08 | 20-AUG-10:52 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 255.93 | 0.00 |
September | 14274.17 | 04-SEP-14:41 | 468.72 | 193.02 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 310.14 | 0.00 |
October | 13341.17 | 09-OCT-11:42 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 73.83 | 0.00 |
November | 10286.07 | 13-NOV-07:03 | 1071.35 | 989.01 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 |
December | 6599.21 | 11-DEC-07:03 | 803.52 | 954.71 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4123.56 | 0.00 | 110.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14274.17 | 2613.31 | 992.69 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 310.14 | 9.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3335.76 | 17-JAN-11:10 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 | 0.00 |
February | 3854.29 | 06-FEB-14:10 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 39.53 | 0.00 |
March | 5736.47 | 27-MAR-10:50 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 77.63 | 0.00 |
April | 10176.78 | 30-APR-11:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 60.17 | 0.00 |
May | 10069.81 | 29-MAY-10:42 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 93.89 | 0.00 |
June | 11299.72 | 25-JUN-10:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 100.10 | 0.00 |
July | 11792.54 | 23-JUL-09:52 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 177.27 | 0.00 |
August | 11817.12 | 20-AUG-10:52 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 158.75 | 0.00 |
September | 12060.16 | 04-SEP-10:42 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 138.96 | 0.00 |
October | 11539.02 | 09-OCT-10:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 22.54 | 0.00 |
November | 9590.84 | 05-NOV-11:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 45.31 | 0.00 |
December | 5150.07 | 04-DEC-07:02 | 847.82 | 573.96 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3335.76 | 169.56 | 69.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12060.16 | 1654.44 | 628.45 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 177.27 | 0.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10983.07 | 23-JAN-13:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4217.14 | 0.00 |
February | 14959.00 | 05-FEB-15:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 170.85 | 0.00 |
March | 15355.05 | 27-MAR-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 12157.56 | 0.00 |
April | 16696.16 | 28-APR-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 15912.86 | 0.00 |
May | 16301.81 | 09-MAY-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 15242.35 | 0.00 |
June | 17190.78 | 12-JUN-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 16542.65 | 0.00 |
July | 18078.54 | 21-JUL-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 18684.67 | 0.00 |
August | 18402.45 | 16-AUG-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 18599.15 | 0.00 |
September | 17049.05 | 05-SEP-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 14533.28 | 0.00 |
October | 16153.16 | 09-OCT-11:42 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 65.79 | 0.00 |
November | 15901.29 | 05-NOV-12:02 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 72.72 | 0.00 |
December | 15403.12 | 25-DEC-13:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10983.07 | 267.84 | 110.30 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 | 0.00 | |
Maximum of Months | 18402.45 | 687.71 | 496.34 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 18684.67 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3619.82 | 31-JAN-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 |
February | 7192.17 | 05-FEB-15:23 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 115.06 | 0.00 |
March | 6056.13 | 26-MAR-16:12 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 72.37 | 0.00 |
April | 9897.82 | 02-APR-15:23 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 82.49 | 0.00 |
May | 11530.35 | 21-MAY-18:03 | 0.00 | 69.82 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 140.42 | 0.00 |
June | 10951.70 | 18-JUN-16:02 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 169.72 | 0.00 |
July | 12038.65 | 30-JUL-14:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 341.40 | 0.00 |
August | 12137.25 | 06-AUG-16:22 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 176.96 | 0.00 |
September | 13363.98 | 04-SEP-16:01 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 189.58 | 0.00 |
October | 12204.50 | 01-OCT-15:32 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 87.47 | 0.00 |
November | 10369.40 | 12-NOV-15:32 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 32.88 | 0.00 |
December | 4788.90 | 11-DEC-07:03 | 508.66 | 610.21 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3619.82 | 0.00 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13363.98 | 805.38 | 610.21 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 341.40 | 5.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3987.69 | 23-JAN-14:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 30.61 | 0.00 |
February | 5481.18 | 06-FEB-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 97.10 | 0.00 |
March | 6672.26 | 27-MAR-13:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 178.33 | 0.00 |
April | 10846.19 | 30-APR-15:13 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 260.16 | 0.00 |
May | 13549.63 | 21-MAY-13:02 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1867.67 | 0.00 |
June | 12560.10 | 18-JUN-12:43 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 333.88 | 0.00 |
July | 13365.67 | 30-JUL-13:22 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 682.27 | 0.00 |
August | 13585.33 | 06-AUG-11:32 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 244.01 | 0.00 |
September | 13332.60 | 04-SEP-15:32 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 503.30 | 0.00 |
October | 13294.49 | 09-OCT-11:42 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 115.22 | 0.00 |
November | 8113.07 | 20-NOV-05:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 0.00 |
December | 4513.85 | 11-DEC-14:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 27.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3987.69 | 0.00 | 110.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 0.00 | |
Maximum of Months | 13585.33 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 1867.67 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4389.04 | 24-JAN-11:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
February | 5495.34 | 07-FEB-13:03 | 2416.29 | 942.68 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 45.96 | 0.00 |
March | 9686.35 | 27-MAR-12:01 | 6443.43 | 2513.82 | 7268.59 | 0.00 | 0.00 | 0.00 | 0.00 | 116.55 | 0.00 |
April | 10529.53 | 23-APR-11:23 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 130.17 | 0.00 |
May | 11622.09 | 21-MAY-08:23 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 152.28 | 0.00 |
June | 10736.48 | 18-JUN-12:43 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 222.44 | 0.00 |
July | 11846.18 | 30-JUL-10:42 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 351.74 | 0.00 |
August | 12154.73 | 06-AUG-10:12 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 162.67 | 0.00 |
September | 11985.56 | 03-SEP-11:02 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 223.24 | 0.00 |
October | 11824.78 | 09-OCT-10:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 35.13 | 0.00 |
November | 7523.58 | 01-NOV-12:02 | 4027.14 | 1571.14 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 44.35 | 0.00 |
December | 4821.45 | 04-DEC-11:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4389.04 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12154.73 | 6443.43 | 2513.82 | 7268.59 | 0.00 | 0.00 | 0.00 | 0.00 | 351.74 | 0.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9609.03 | 22-JAN-14:43 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.76 |
February | 15575.58 | 05-FEB-13:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 221.34 | 0.00 |
March | 13177.75 | 26-MAR-14:02 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 252.91 | 0.00 |
April | 13879.44 | 02-APR-14:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 231.70 | 0.00 |
May | 15211.65 | 21-MAY-13:02 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.07 | 0.00 |
June | 13958.84 | 18-JUN-12:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 340.04 | 0.00 |
July | 15100.95 | 30-JUL-13:22 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 680.24 | 0.00 |
August | 15411.46 | 06-AUG-11:32 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 241.99 | 0.00 |
September | 15633.49 | 24-SEP-12:42 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 314.15 | 0.00 |
October | 16266.16 | 09-OCT-11:42 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 101.98 | 0.00 |
November | 15580.72 | 19-NOV-13:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 229.55 | 0.00 |
December | 15571.07 | 25-DEC-13:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9609.03 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16266.16 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.07 | 12.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3643.68 | 31-JAN-16:20 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 |
February | 6716.54 | 05-FEB-16:23 | 127.16 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 143.56 | 0.00 |
March | 9265.46 | 26-MAR-17:23 | 0.00 | 69.82 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 90.41 | 0.00 |
April | 12106.82 | 02-APR-15:32 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 117.30 | 0.00 |
May | 12515.84 | 21-MAY-16:22 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 315.70 | 0.00 |
June | 12419.60 | 11-JUN-16:42 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 298.94 | 0.00 |
July | 12492.53 | 02-JUL-16:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 275.78 | 0.00 |
August | 12486.53 | 06-AUG-14:51 | 339.11 | 139.64 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 321.20 | 0.00 |
September | 12715.64 | 04-SEP-16:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 340.43 | 0.00 |
October | 12586.49 | 09-OCT-15:41 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 306.09 | 0.00 |
November | 11525.66 | 05-NOV-15:32 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 157.20 | 0.00 |
December | 4252.78 | 04-DEC-15:20 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 22.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3643.68 | 0.00 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12715.64 | 805.38 | 314.21 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 340.43 | 9.09 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.115696E+12 | 107044.62 | 23-JAN-13:00 | 0.988580E+10 | 9530.11 | 18-JAN-12:09 |
February | 0.110727E+12 | 127420.30 | 06-FEB-15:09 | 0.884968E+10 | 9512.07 | 02-FEB-12:09 |
March | 0.137145E+12 | 151824.76 | 27-MAR-12:09 | 0.977719E+10 | 9446.85 | 01-MAR-12:20 |
April | 0.143438E+12 | 165596.50 | 28-APR-12:09 | 0.884107E+10 | 9329.70 | 03-APR-11:30 |
May | 0.188530E+12 | 186078.99 | 30-MAY-15:09 | 0.889747E+10 | 9218.85 | 01-MAY-11:00 |
June | 0.208085E+12 | 196984.74 | 12-JUN-12:00 | 0.841503E+10 | 9126.90 | 02-JUN-11:20 |
July | 0.232053E+12 | 199193.80 | 31-JUL-14:09 | 0.837444E+10 | 9080.13 | 31-JUL-11:20 |
August | 0.251397E+12 | 212927.65 | 10-AUG-15:30 | 0.876351E+10 | 9141.02 | 31-AUG-11:20 |
September | 0.204567E+12 | 192092.48 | 05-SEP-12:09 | 0.856015E+10 | 9241.81 | 29-SEP-11:09 |
October | 0.178673E+12 | 164522.67 | 06-OCT-15:20 | 0.920488E+10 | 9355.30 | 31-OCT-11:50 |
November | 0.146390E+12 | 152151.46 | 01-NOV-12:30 | 0.930758E+10 | 9464.26 | 29-NOV-12:09 |
December | 0.122295E+12 | 123033.42 | 04-DEC-13:09 | 0.970398E+10 | 9521.22 | 29-DEC-12:09 |
Annual Sum or Average | 0.203900E+13 | 0.108581E+12 | ||||
Minimum of Months | 0.110727E+12 | 107044.62 | 0.837444E+10 | 9080.13 | ||
Maximum of Months | 0.251397E+12 | 212927.65 | 0.988580E+10 | 9530.11 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.195952E+11 | 0.507020E+10 | 0.593559E+11 | 0.982562E+09 | 0.642862E+10 | 12379742.02 | 0.185426E+09 | 0.240656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176411E+11 | 0.427755E+10 | 0.537310E+11 | 0.889174E+09 | 0.681673E+10 | 11196021.66 | 0.120226E+09 | 0.272398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208747E+11 | 0.435515E+10 | 0.617796E+11 | 0.102913E+10 | 0.966047E+10 | 12675672.10 | 44584899.15 | 0.393889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.185132E+11 | 0.382924E+10 | 0.572952E+11 | 0.946273E+09 | 0.114043E+11 | 11960507.72 | 701756.46 | 0.514376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198621E+11 | 0.363967E+10 | 0.605677E+11 | 0.100561E+10 | 0.179984E+11 | 12527707.06 | 0.00 | 0.854443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.197214E+11 | 0.340476E+10 | 0.594895E+11 | 0.989941E+09 | 0.196314E+11 | 12231776.97 | 0.00 | 0.104836E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.185123E+11 | 0.358307E+10 | 0.583622E+11 | 0.961754E+09 | 0.205613E+11 | 12256437.81 | 0.00 | 0.130060E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.206676E+11 | 0.383930E+10 | 0.617796E+11 | 0.102898E+10 | 0.223919E+11 | 12675672.10 | 0.00 | 0.141677E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.185395E+11 | 0.401557E+10 | 0.572729E+11 | 0.946045E+09 | 0.180954E+11 | 11960507.72 | 0.00 | 0.105686E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.193733E+11 | 0.454821E+10 | 0.593671E+11 | 0.982534E+09 | 0.156296E+11 | 12379742.02 | 0.00 | 0.787597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193163E+11 | 0.480143E+10 | 0.580818E+11 | 0.964318E+09 | 0.117477E+11 | 12059151.09 | 0.00 | 0.514668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190145E+11 | 0.518961E+10 | 0.583511E+11 | 0.961960E+09 | 0.763685E+10 | 12256437.81 | 41152566.14 | 0.310879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.231631E+12 | 0.505538E+11 | 0.705434E+12 | 0.116883E+11 | 0.168003E+12 | 0.146559E+09 | 0.392091E+09 | 0.871150E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176411E+11 | 0.340476E+10 | 0.537310E+11 | 0.889174E+09 | 0.642862E+10 | 11196021.66 | 0.00 | 0.240656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.208747E+11 | 0.518961E+10 | 0.617796E+11 | 0.102913E+10 | 0.223919E+11 | 12675672.10 | 0.185426E+09 | 0.141677E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.988580E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.884968E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.977719E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.884107E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.889747E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.841503E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.837444E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.876351E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.856015E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.920488E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.930758E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.970398E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.108581E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.837444E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.988580E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 21884.97 | 23-JAN-16:00 | 5686.19 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 835.62 | 09-JAN-08:20 | 10594.56 | 23-JAN-13:30 | 6.85 | 01-JAN-06:10 | 4493.89 | 02-JAN-07:49 |
February | 22491.26 | 09-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 835.01 | 09-FEB-08:20 | 15854.80 | 06-FEB-15:30 | 6.85 | 01-FEB-06:10 | 4493.89 | 01-FEB-07:40 |
March | 24001.33 | 15-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 838.82 | 15-MAR-07:19 | 20389.92 | 27-MAR-15:30 | 6.85 | 27-MAR-12:09 | 4493.89 | 07-MAR-07:19 |
April | 22429.67 | 18-APR-07:10 | 5686.19 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 836.73 | 18-APR-07:19 | 22203.47 | 24-APR-15:09 | 6.85 | 28-APR-11:09 | 401.60 | 05-APR-06:49 |
May | 19915.40 | 23-MAY-07:10 | 5686.19 | 01-MAY-05:10 | 45864.70 | 01-MAY-07:10 | 833.39 | 23-MAY-07:19 | 25476.04 | 30-MAY-15:30 | 6.85 | 05-MAY-12:09 | 0.00 | 01-MAY-00:10 |
June | 19948.33 | 08-JUN-07:10 | 5686.19 | 01-JUN-05:10 | 45864.70 | 01-JUN-07:10 | 833.44 | 08-JUN-07:19 | 25300.74 | 12-JUN-15:09 | 6.85 | 01-JUN-11:09 | 0.00 | 01-JUN-00:10 |
July | 21125.16 | 20-JUL-07:10 | 5686.19 | 01-JUL-05:10 | 45864.70 | 03-JUL-07:10 | 835.00 | 20-JUL-07:19 | 26082.06 | 31-JUL-15:39 | 6.85 | 02-JUL-15:30 | 0.00 | 01-JUL-00:10 |
August | 20325.36 | 29-AUG-07:10 | 5686.19 | 01-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 833.94 | 29-AUG-07:19 | 24645.74 | 07-AUG-15:30 | 6.85 | 02-AUG-17:10 | 0.00 | 01-AUG-00:10 |
September | 20458.64 | 06-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 834.11 | 06-SEP-07:19 | 26704.02 | 05-SEP-15:39 | 6.85 | 03-SEP-15:30 | 0.00 | 01-SEP-00:10 |
October | 20823.85 | 31-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 834.60 | 31-OCT-07:19 | 21692.09 | 10-OCT-15:20 | 6.85 | 04-OCT-12:09 | 0.00 | 01-OCT-00:10 |
November | 22832.36 | 29-NOV-16:00 | 5686.19 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 834.86 | 29-NOV-16:00 | 17811.69 | 13-NOV-15:09 | 6.85 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 23331.01 | 15-DEC-16:00 | 5686.19 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 837.68 | 15-DEC-08:20 | 13708.90 | 04-DEC-15:09 | 6.85 | 01-DEC-06:10 | 4493.89 | 18-DEC-07:19 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 19915.40 | 5686.19 | 45864.70 | 833.39 | 10594.56 | 6.85 | 0.00 | |||||||
Maximum of Months | 24001.33 | 5686.19 | 45864.70 | 838.82 | 26704.02 | 6.85 | 4493.89 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 33703.70 | 30-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 50644.76 | 06-FEB-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 71111.99 | 27-MAR-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 85037.11 | 28-APR-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 98575.46 | 31-MAY-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 110436.18 | 12-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 115199.80 | 21-JUL-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 126423.00 | 10-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 106504.97 | 07-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 83732.34 | 05-OCT-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 75130.43 | 01-NOV-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 47118.18 | 04-DEC-13:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 33703.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 126423.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 107044.62 | 23-JAN-13:00 | 19671.42 | 42402.18 | 0.00 | 831.83 | 10537.69 | 6.85 | 0.00 | 33594.66 | 0.00 |
February | 127420.30 | 06-FEB-15:09 | 19671.42 | 40588.47 | 0.00 | 831.19 | 15677.61 | 6.85 | 0.00 | 50644.76 | 0.00 |
March | 151824.76 | 27-MAR-12:09 | 19671.42 | 42402.18 | 0.00 | 831.83 | 18043.73 | 6.85 | 0.00 | 70868.75 | 0.00 |
April | 165596.50 | 28-APR-12:09 | 19671.42 | 42402.18 | 0.00 | 831.83 | 17647.11 | 6.85 | 0.00 | 85037.11 | 0.00 |
May | 186078.99 | 30-MAY-15:09 | 19671.42 | 42072.41 | 0.00 | 831.72 | 25232.65 | 6.85 | 0.00 | 98263.95 | 0.00 |
June | 196984.74 | 12-JUN-12:00 | 19671.42 | 42402.18 | 0.00 | 831.83 | 23636.28 | 6.85 | 0.00 | 110436.18 | 0.00 |
July | 199193.80 | 31-JUL-14:09 | 19671.42 | 40588.47 | 0.00 | 831.19 | 25103.97 | 6.85 | 0.00 | 112991.90 | 0.00 |
August | 212927.65 | 10-AUG-15:30 | 19671.42 | 42072.41 | 0.00 | 831.72 | 23922.25 | 6.85 | 0.00 | 126423.00 | 0.00 |
September | 192092.48 | 05-SEP-12:09 | 19671.42 | 42402.18 | 0.00 | 831.83 | 23102.60 | 6.85 | 0.00 | 106077.60 | 0.00 |
October | 164522.67 | 06-OCT-15:20 | 19671.42 | 42072.41 | 0.00 | 831.72 | 18835.54 | 6.85 | 0.00 | 83104.73 | 0.00 |
November | 152151.46 | 01-NOV-12:30 | 19671.42 | 42402.18 | 0.00 | 831.83 | 14372.20 | 6.85 | 0.00 | 74866.99 | 0.00 |
December | 123033.42 | 04-DEC-13:09 | 19671.42 | 42402.18 | 0.00 | 831.83 | 13002.97 | 6.85 | 0.00 | 47118.18 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 107044.62 | 19671.42 | 40588.47 | 0.00 | 831.19 | 10537.69 | 6.85 | 0.00 | 33594.66 | 0.00 | |
Maximum of Months | 212927.65 | 19671.42 | 42402.18 | 0.00 | 831.83 | 25232.65 | 6.85 | 0.00 | 126423.00 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 9530.11 | 18-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 9512.07 | 02-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 9446.85 | 01-MAR-12:20 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 9329.70 | 03-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 9218.85 | 01-MAY-11:00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9126.90 | 02-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9080.13 | 31-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9141.02 | 31-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 9241.81 | 29-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 9355.30 | 31-OCT-11:50 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 9464.26 | 29-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 9521.22 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9080.13 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9530.11 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.17 | 0.00 | 26.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.18 | 0.00 | 26.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 26.17 | 0.00 | 26.17 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.18 | 0.00 | 26.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.30 | 0.67 | 27.30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.47 | 3.50 | 27.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.68 | 9.83 | 27.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.65 | 9.00 | 27.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 | 27.64 | 13.83 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 27.52 | 9.33 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.69 | 9.67 | 27.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.56 | 8.00 | 27.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.33 | 0.83 | 27.33 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 107.50 | 27.61 | 64.67 | 27.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 | 27.69 | 13.83 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.50 | 27.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.54 | 1.83 | 27.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.64 | 10.00 | 27.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.94 | 12.33 | 28.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.83 | 10.33 | 27.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 27.83 | 15.67 | 27.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 27.70 | 10.50 | 27.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 27.90 | 12.00 | 28.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.75 | 13.17 | 27.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.40 | 4.17 | 27.40 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 138.83 | 27.79 | 90.50 | 27.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 27.94 | 15.67 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.36 | 1.33 | 27.36 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.60 | 2.67 | 27.61 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.59 | 3.17 | 27.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.63 | 6.83 | 27.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.72 | 9.50 | 27.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.63 | 8.17 | 27.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 27.67 | 12.83 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 27.57 | 9.33 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.91 | 10.33 | 28.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 28.03 | 11.33 | 28.10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.82 | 9.50 | 27.83 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.56 | 4.17 | 27.56 |
Annual Sum or Average | 0.00 | 0.00 | 134.33 | 27.73 | 89.17 | 27.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.36 | 1.33 | 27.36 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 28.03 | 12.83 | 28.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.52 | 1.17 | 27.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.67 | 2.33 | 27.67 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.79 | 6.17 | 27.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 27.95 | 10.17 | 28.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 27.82 | 9.17 | 27.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 33.67 | 27.78 | 14.83 | 27.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 27.67 | 10.00 | 27.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 27.90 | 10.33 | 28.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 27.90 | 9.00 | 27.95 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.63 | 5.17 | 27.64 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 146.00 | 27.80 | 78.33 | 27.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 33.67 | 27.95 | 14.83 | 28.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.38 | 5.33 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.41 | 6.33 | 27.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.44 | 11.67 | 27.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.31 | 8.17 | 27.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.47 | 8.33 | 27.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.31 | 5.50 | 27.37 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 65.00 | 27.39 | 45.33 | 27.45 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.47 | 11.67 | 27.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.32 | 0.33 | 27.32 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.46 | 4.50 | 27.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.62 | 11.50 | 27.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.63 | 9.33 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 27.63 | 14.67 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.48 | 10.33 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 27.68 | 11.83 | 27.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.54 | 13.83 | 27.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.37 | 4.50 | 27.37 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 116.67 | 27.58 | 80.83 | 27.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 27.68 | 14.67 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 20.10 | 2.33 | 20.10 | 1.50 | 21.86 | 1.50 | 22.93 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 26.45 | 3.00 | 26.45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 25.83 | 7.83 | 25.83 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 25.79 | 14.83 | 25.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 49.83 | 26.01 | 49.17 | 26.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 55.50 | 26.25 | 54.67 | 26.24 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 67.50 | 26.60 | 62.00 | 26.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 80.33 | 26.57 | 72.33 | 26.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 65.83 | 26.48 | 58.83 | 26.43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 62.50 | 26.16 | 56.50 | 26.11 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 26.22 | 26.50 | 26.21 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.51 | 5.33 | 27.51 |
Annual Sum or Average | 2.33 | 20.10 | 2.33 | 20.10 | 441.33 | 26.29 | 412.50 | 26.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.86 | 1.50 | 22.93 |
Maximum of Months | 2.33 | 20.10 | 2.33 | 20.10 | 80.33 | 27.51 | 72.33 | 27.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.36 | 0.50 | 27.36 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.54 | 0.83 | 27.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.56 | 3.83 | 27.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.68 | 7.83 | 27.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.59 | 7.50 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 27.58 | 12.83 | 27.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 | 27.42 | 10.83 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 27.66 | 10.00 | 27.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.65 | 8.50 | 27.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.53 | 5.00 | 27.53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 126.17 | 27.57 | 67.67 | 27.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 | 27.68 | 12.83 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.35 | 1.33 | 27.35 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.52 | 8.67 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.53 | 7.83 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 27.53 | 13.00 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.48 | 8.33 | 27.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.56 | 8.83 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.44 | 5.67 | 27.44 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 74.67 | 27.51 | 53.67 | 27.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 27.56 | 13.00 | 27.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.42 | 2.00 | 27.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.54 | 8.50 | 27.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.78 | 12.17 | 27.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.76 | 9.67 | 27.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 27.75 | 15.33 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.64 | 10.17 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.76 | 12.00 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.63 | 13.17 | 27.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.36 | 2.00 | 27.36 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 112.00 | 27.70 | 85.00 | 27.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 27.78 | 15.33 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.34 | 1.00 | 27.34 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.58 | 2.17 | 27.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.52 | 2.50 | 27.53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.47 | 5.67 | 27.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.54 | 8.67 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.51 | 7.17 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 27.54 | 12.17 | 27.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.57 | 8.50 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.76 | 9.83 | 27.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.89 | 11.67 | 27.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.72 | 9.50 | 27.73 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.57 | 3.67 | 27.57 |
Annual Sum or Average | 0.00 | 0.00 | 105.83 | 27.63 | 82.50 | 27.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.34 | 1.00 | 27.34 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 27.89 | 12.17 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.49 | 0.67 | 27.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.55 | 1.67 | 27.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.66 | 5.17 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.82 | 9.17 | 27.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.73 | 8.17 | 27.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 27.72 | 12.83 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 27.64 | 9.17 | 27.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.79 | 10.00 | 27.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.79 | 8.00 | 27.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.54 | 4.33 | 27.54 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 114.83 | 27.72 | 69.17 | 27.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 27.82 | 12.83 | 27.88 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 350.83 | 24.63 | 0.00 | 24.63 |
February | 0.00 | 0.00 | 378.67 | 24.55 | 0.00 | 24.55 |
March | 0.00 | 0.00 | 411.83 | 24.51 | 0.00 | 24.51 |
April | 0.00 | 0.00 | 460.83 | 24.45 | 0.00 | 24.45 |
May | 0.00 | 0.00 | 498.67 | 24.44 | 0.00 | 24.44 |
June | 0.00 | 0.00 | 496.00 | 24.40 | 0.00 | 24.40 |
July | 0.00 | 0.00 | 497.00 | 24.40 | 0.00 | 24.40 |
August | 0.00 | 0.00 | 514.00 | 24.32 | 0.00 | 24.32 |
September | 0.00 | 0.00 | 485.00 | 24.43 | 0.00 | 24.43 |
October | 0.00 | 0.00 | 492.17 | 24.49 | 0.00 | 24.49 |
November | 0.00 | 0.00 | 482.17 | 24.50 | 0.00 | 24.50 |
December | 0.00 | 0.00 | 438.17 | 24.51 | 0.00 | 24.51 |
Annual Sum or Average | 0.00 | 5505.33 | 24.46 | 0.00 | 24.46 | |
Minimum of Months | 0.00 | 0.00 | 350.83 | 24.32 | 0.00 | 24.32 |
Maximum of Months | 0.00 | 0.00 | 514.00 | 24.63 | 0.00 | 24.63 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 63.50 | 23.67 | 188.50 | 24.21 | 0.00 | 24.21 |
February | 16.17 | 23.73 | 263.83 | 24.35 | 0.00 | 24.35 |
March | 4.33 | 23.78 | 331.67 | 24.37 | 0.00 | 24.37 |
April | 0.50 | 23.92 | 411.33 | 24.37 | 0.00 | 24.37 |
May | 0.00 | 0.00 | 489.33 | 24.38 | 0.00 | 24.38 |
June | 0.00 | 0.00 | 496.00 | 24.34 | 0.00 | 24.34 |
July | 0.00 | 0.00 | 497.00 | 24.35 | 0.00 | 24.35 |
August | 0.00 | 0.00 | 514.00 | 24.29 | 0.00 | 24.29 |
September | 0.00 | 0.00 | 485.00 | 24.38 | 0.00 | 24.38 |
October | 0.00 | 0.00 | 484.00 | 24.42 | 0.00 | 24.42 |
November | 0.00 | 0.00 | 460.50 | 24.37 | 0.00 | 24.37 |
December | 21.83 | 23.70 | 301.33 | 24.31 | 0.00 | 24.31 |
Annual Sum or Average | 106.33 | 23.69 | 4922.50 | 24.35 | 0.00 | 24.35 |
Minimum of Months | 0.00 | 0.00 | 188.50 | 24.21 | 0.00 | 24.21 |
Maximum of Months | 63.50 | 23.92 | 514.00 | 24.42 | 0.00 | 24.42 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 209.17 | 23.50 | 113.67 | 23.72 | 13.67 | 23.73 |
February | 100.33 | 23.49 | 192.67 | 24.00 | 0.00 | 24.00 |
March | 49.33 | 23.58 | 281.00 | 24.19 | 0.00 | 24.19 |
April | 2.67 | 23.57 | 392.33 | 24.37 | 0.00 | 24.37 |
May | 0.50 | 26.65 | 487.50 | 24.43 | 0.50 | 24.44 |
June | 1.50 | 26.69 | 496.00 | 24.40 | 1.50 | 24.41 |
July | 3.83 | 26.61 | 496.33 | 24.45 | 3.83 | 24.47 |
August | 1.67 | 26.69 | 514.00 | 24.35 | 1.67 | 24.36 |
September | 4.33 | 26.57 | 485.00 | 24.45 | 4.33 | 24.47 |
October | 0.00 | 0.00 | 480.50 | 24.44 | 0.00 | 24.44 |
November | 2.83 | 23.65 | 416.33 | 24.34 | 0.00 | 24.34 |
December | 107.50 | 23.47 | 213.50 | 23.98 | 0.00 | 23.98 |
Annual Sum or Average | 483.67 | 23.58 | 4568.83 | 24.30 | 25.50 | 24.30 |
Minimum of Months | 0.00 | 0.00 | 113.67 | 23.72 | 0.00 | 23.73 |
Maximum of Months | 209.17 | 26.69 | 514.00 | 24.45 | 13.67 | 24.47 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 282.33 | 22.93 | 95.50 | 23.23 | 0.00 | 23.23 |
February | 162.33 | 23.04 | 183.17 | 23.67 | 1.00 | 23.67 |
March | 102.17 | 23.26 | 286.50 | 24.02 | 1.00 | 24.02 |
April | 52.00 | 24.75 | 403.67 | 24.50 | 29.67 | 24.59 |
May | 49.83 | 26.71 | 502.83 | 24.78 | 49.83 | 24.94 |
June | 73.17 | 26.56 | 496.00 | 24.84 | 73.17 | 25.03 |
July | 94.33 | 26.72 | 497.00 | 25.03 | 94.33 | 25.26 |
August | 69.17 | 26.65 | 514.00 | 24.82 | 69.17 | 25.01 |
September | 78.67 | 26.47 | 485.00 | 24.88 | 78.67 | 25.07 |
October | 66.00 | 26.23 | 487.83 | 24.77 | 65.17 | 24.93 |
November | 30.83 | 23.80 | 396.67 | 24.35 | 6.50 | 24.37 |
December | 188.33 | 23.09 | 203.00 | 23.66 | 5.83 | 23.66 |
Annual Sum or Average | 1249.17 | 24.35 | 4551.17 | 24.48 | 474.33 | 24.63 |
Minimum of Months | 30.83 | 22.93 | 95.50 | 23.23 | 0.00 | 23.23 |
Maximum of Months | 282.33 | 26.72 | 514.00 | 25.03 | 94.33 | 25.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 204.67 | 23.01 | 156.00 | 23.58 | 0.17 | 23.59 |
February | 117.17 | 23.12 | 232.00 | 23.94 | 2.00 | 23.95 |
March | 76.83 | 23.40 | 334.50 | 24.17 | 3.83 | 24.20 |
April | 68.17 | 25.81 | 434.83 | 24.70 | 53.50 | 24.88 |
May | 63.00 | 26.83 | 507.33 | 24.87 | 63.00 | 25.06 |
June | 78.83 | 26.66 | 496.00 | 24.88 | 78.83 | 25.10 |
July | 99.67 | 26.83 | 497.00 | 25.08 | 99.67 | 25.33 |
August | 75.67 | 26.78 | 514.00 | 24.87 | 75.67 | 25.09 |
September | 85.83 | 26.66 | 485.00 | 24.96 | 85.83 | 25.18 |
October | 77.67 | 26.53 | 496.00 | 24.89 | 77.67 | 25.09 |
November | 28.50 | 25.07 | 431.33 | 24.53 | 16.33 | 24.59 |
December | 134.17 | 23.19 | 262.67 | 23.91 | 8.00 | 23.92 |
Annual Sum or Average | 1110.17 | 24.90 | 4846.67 | 24.62 | 564.50 | 24.79 |
Minimum of Months | 28.50 | 23.01 | 156.00 | 23.58 | 0.17 | 23.59 |
Maximum of Months | 204.67 | 26.83 | 514.00 | 25.08 | 99.67 | 25.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 186.33 | 23.16 | 224.67 | 23.91 | 5.50 | 23.95 |
February | 114.50 | 23.37 | 259.33 | 24.10 | 10.33 | 24.17 |
March | 88.00 | 23.57 | 327.33 | 24.20 | 8.17 | 24.26 |
April | 65.17 | 25.27 | 413.50 | 24.60 | 44.00 | 24.74 |
May | 48.17 | 26.71 | 500.67 | 24.78 | 48.17 | 24.93 |
June | 69.67 | 26.52 | 496.00 | 24.81 | 69.67 | 25.00 |
July | 92.33 | 26.70 | 497.00 | 25.02 | 92.33 | 25.24 |
August | 70.00 | 26.68 | 514.00 | 24.83 | 70.00 | 25.03 |
September | 83.83 | 26.60 | 485.00 | 24.93 | 83.83 | 25.15 |
October | 78.00 | 26.58 | 495.50 | 24.91 | 78.00 | 25.11 |
November | 55.17 | 26.01 | 436.17 | 24.71 | 42.83 | 24.87 |
December | 127.50 | 23.68 | 292.67 | 24.26 | 19.83 | 24.37 |
Annual Sum or Average | 1078.67 | 24.97 | 4941.83 | 24.64 | 572.67 | 24.81 |
Minimum of Months | 48.17 | 23.16 | 224.67 | 23.91 | 5.50 | 23.95 |
Maximum of Months | 186.33 | 26.71 | 514.00 | 25.02 | 92.33 | 25.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 245.17 | 22.93 | 152.67 | 23.49 | 0.33 | 23.49 |
February | 139.00 | 23.10 | 223.67 | 23.86 | 3.83 | 23.88 |
March | 94.83 | 23.53 | 315.67 | 24.17 | 8.17 | 24.22 |
April | 64.17 | 25.32 | 415.83 | 24.63 | 44.17 | 24.76 |
May | 56.83 | 26.80 | 502.33 | 24.85 | 56.83 | 25.03 |
June | 80.67 | 26.68 | 496.00 | 24.90 | 80.67 | 25.12 |
July | 99.67 | 26.81 | 497.00 | 25.08 | 99.67 | 25.33 |
August | 79.33 | 26.78 | 514.00 | 24.89 | 79.33 | 25.11 |
September | 90.00 | 26.62 | 485.00 | 24.96 | 90.00 | 25.19 |
October | 74.67 | 26.39 | 490.17 | 24.86 | 74.00 | 25.04 |
November | 44.67 | 25.07 | 415.67 | 24.52 | 24.17 | 24.62 |
December | 159.67 | 23.09 | 241.00 | 23.83 | 8.83 | 23.84 |
Annual Sum or Average | 1228.67 | 24.69 | 4749.00 | 24.58 | 570.00 | 24.76 |
Minimum of Months | 44.67 | 22.93 | 152.67 | 23.49 | 0.33 | 23.49 |
Maximum of Months | 245.17 | 26.81 | 514.00 | 25.08 | 99.67 | 25.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 130.67 | 23.55 | 170.00 | 23.92 | 0.00 | 23.92 |
February | 68.33 | 23.44 | 242.17 | 24.08 | 0.17 | 24.08 |
March | 56.50 | 23.53 | 313.00 | 24.16 | 0.00 | 24.16 |
April | 17.17 | 24.77 | 419.17 | 24.42 | 11.17 | 24.44 |
May | 23.00 | 26.71 | 506.33 | 24.64 | 23.00 | 24.73 |
June | 47.00 | 26.50 | 496.00 | 24.72 | 47.00 | 24.86 |
July | 64.00 | 26.75 | 497.00 | 24.92 | 64.00 | 25.10 |
August | 46.50 | 26.75 | 514.00 | 24.74 | 46.50 | 24.89 |
September | 54.00 | 26.64 | 485.00 | 24.82 | 54.00 | 24.98 |
October | 35.67 | 26.61 | 498.83 | 24.74 | 35.67 | 24.86 |
November | 0.83 | 25.09 | 476.50 | 24.47 | 0.83 | 24.47 |
December | 33.00 | 23.57 | 335.83 | 24.22 | 0.00 | 24.22 |
Annual Sum or Average | 576.67 | 25.03 | 4953.83 | 24.55 | 282.33 | 24.65 |
Minimum of Months | 0.83 | 23.44 | 170.00 | 23.92 | 0.00 | 23.92 |
Maximum of Months | 130.67 | 26.75 | 514.00 | 24.92 | 64.00 | 25.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 59.83 | 23.56 | 263.17 | 24.24 | 0.17 | 24.24 |
February | 33.67 | 23.46 | 301.00 | 24.30 | 0.17 | 24.30 |
March | 28.50 | 23.53 | 373.00 | 24.29 | 0.17 | 24.30 |
April | 27.33 | 26.25 | 459.33 | 24.60 | 25.17 | 24.69 |
May | 51.67 | 26.87 | 508.00 | 24.82 | 51.67 | 24.99 |
June | 57.17 | 26.73 | 496.00 | 24.81 | 57.17 | 24.99 |
July | 80.33 | 26.90 | 497.00 | 25.02 | 80.33 | 25.25 |
August | 62.17 | 26.90 | 514.00 | 24.84 | 62.17 | 25.04 |
September | 67.83 | 26.87 | 485.00 | 24.93 | 67.83 | 25.15 |
October | 58.33 | 26.85 | 502.00 | 24.90 | 58.33 | 25.09 |
November | 11.67 | 26.91 | 483.83 | 24.64 | 11.67 | 24.69 |
December | 15.17 | 23.59 | 381.17 | 24.36 | 0.00 | 24.36 |
Annual Sum or Average | 553.67 | 26.01 | 5263.50 | 24.69 | 414.83 | 24.84 |
Minimum of Months | 11.67 | 23.46 | 263.17 | 24.24 | 0.00 | 24.24 |
Maximum of Months | 80.33 | 26.91 | 514.00 | 25.02 | 80.33 | 25.25 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 74.67 | 22.77 | 311.00 | 24.23 | 5.00 | 24.25 |
February | 55.50 | 22.97 | 337.67 | 24.26 | 11.00 | 24.28 |
March | 61.50 | 23.02 | 369.33 | 24.21 | 15.00 | 24.21 |
April | 50.17 | 24.25 | 427.67 | 24.49 | 35.83 | 24.51 |
May | 63.50 | 25.51 | 504.33 | 24.80 | 63.50 | 24.87 |
June | 139.00 | 25.39 | 496.00 | 24.90 | 139.00 | 24.98 |
July | 196.33 | 25.56 | 497.00 | 25.11 | 196.33 | 25.21 |
August | 191.50 | 25.70 | 514.00 | 25.11 | 191.50 | 25.24 |
September | 171.17 | 25.83 | 485.00 | 25.14 | 171.17 | 25.28 |
October | 130.67 | 25.79 | 502.00 | 25.05 | 130.67 | 25.18 |
November | 77.33 | 25.63 | 484.33 | 24.81 | 75.50 | 24.91 |
December | 59.83 | 24.05 | 405.00 | 24.48 | 30.50 | 24.56 |
Annual Sum or Average | 1271.17 | 25.10 | 5333.33 | 24.78 | 1065.00 | 24.90 |
Minimum of Months | 50.17 | 22.77 | 311.00 | 24.21 | 5.00 | 24.21 |
Maximum of Months | 196.33 | 25.83 | 514.00 | 25.14 | 196.33 | 25.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 77.00 | 23.52 | 252.33 | 24.18 | 0.00 | 24.18 |
February | 45.33 | 23.50 | 300.17 | 24.26 | 0.67 | 24.27 |
March | 30.50 | 23.67 | 365.00 | 24.32 | 1.17 | 24.33 |
April | 26.33 | 26.06 | 440.83 | 24.59 | 24.67 | 24.67 |
May | 40.33 | 26.86 | 506.67 | 24.77 | 40.33 | 24.92 |
June | 64.17 | 26.75 | 496.00 | 24.84 | 64.17 | 25.04 |
July | 81.83 | 26.88 | 497.00 | 25.03 | 81.83 | 25.26 |
August | 68.17 | 26.91 | 514.00 | 24.87 | 68.17 | 25.08 |
September | 78.00 | 26.84 | 485.00 | 24.97 | 78.00 | 25.20 |
October | 52.83 | 26.81 | 502.00 | 24.88 | 52.83 | 25.05 |
November | 14.50 | 26.90 | 483.50 | 24.62 | 14.50 | 24.69 |
December | 24.33 | 23.64 | 370.17 | 24.36 | 0.17 | 24.36 |
Annual Sum or Average | 603.33 | 25.85 | 5212.67 | 24.69 | 426.50 | 24.84 |
Minimum of Months | 14.50 | 23.50 | 252.33 | 24.18 | 0.00 | 24.18 |
Maximum of Months | 81.83 | 26.91 | 514.00 | 25.03 | 81.83 | 25.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 210.17 | 23.30 | 123.17 | 23.61 | 0.00 | 23.61 |
February | 105.17 | 23.32 | 218.67 | 23.95 | 0.83 | 23.95 |
March | 61.67 | 23.47 | 316.33 | 24.16 | 0.17 | 24.16 |
April | 28.67 | 24.98 | 427.00 | 24.49 | 19.83 | 24.54 |
May | 43.00 | 26.71 | 506.33 | 24.75 | 43.00 | 24.89 |
June | 67.33 | 26.50 | 496.00 | 24.80 | 67.33 | 24.98 |
July | 89.33 | 26.65 | 497.00 | 24.99 | 89.33 | 25.21 |
August | 63.50 | 26.58 | 514.00 | 24.78 | 63.50 | 24.96 |
September | 73.00 | 26.46 | 485.00 | 24.85 | 73.00 | 25.03 |
October | 53.83 | 26.27 | 490.83 | 24.74 | 53.83 | 24.88 |
November | 6.83 | 24.21 | 440.67 | 24.39 | 3.33 | 24.39 |
December | 117.00 | 23.41 | 249.83 | 23.96 | 3.17 | 23.97 |
Annual Sum or Average | 919.50 | 24.76 | 4764.83 | 24.54 | 417.33 | 24.67 |
Minimum of Months | 6.83 | 23.30 | 123.17 | 23.61 | 0.00 | 23.61 |
Maximum of Months | 210.17 | 26.71 | 514.00 | 24.99 | 89.33 | 25.21 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 140.00 | 23.35 | 153.00 | 23.94 | 0.67 | 23.95 |
February | 65.83 | 23.35 | 212.50 | 24.21 | 1.33 | 24.21 |
March | 44.17 | 23.71 | 290.83 | 24.35 | 3.33 | 24.38 |
April | 48.67 | 26.29 | 382.83 | 24.81 | 44.17 | 24.98 |
May | 59.67 | 26.85 | 430.00 | 24.99 | 59.67 | 25.19 |
June | 74.00 | 26.63 | 418.00 | 24.99 | 74.00 | 25.20 |
July | 97.67 | 26.77 | 422.00 | 25.22 | 97.67 | 25.46 |
August | 73.00 | 26.72 | 433.00 | 24.99 | 73.00 | 25.21 |
September | 79.00 | 26.66 | 410.00 | 25.07 | 79.00 | 25.29 |
October | 72.00 | 26.61 | 424.67 | 25.02 | 72.00 | 25.22 |
November | 13.00 | 26.16 | 389.83 | 24.65 | 11.67 | 24.70 |
December | 77.00 | 23.51 | 249.33 | 24.20 | 6.67 | 24.22 |
Annual Sum or Average | 844.00 | 25.41 | 4216.00 | 24.78 | 523.17 | 24.96 |
Minimum of Months | 13.00 | 23.35 | 153.00 | 23.94 | 0.67 | 23.95 |
Maximum of Months | 140.00 | 26.85 | 433.00 | 25.22 | 97.67 | 25.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 114.83 | 23.48 | 260.17 | 24.21 | 5.17 | 24.25 |
February | 65.83 | 23.70 | 297.50 | 24.30 | 8.50 | 24.36 |
March | 51.33 | 23.89 | 360.33 | 24.32 | 6.33 | 24.36 |
April | 41.67 | 25.67 | 435.17 | 24.60 | 33.33 | 24.70 |
May | 42.00 | 26.72 | 506.00 | 24.74 | 42.00 | 24.88 |
June | 64.00 | 26.45 | 496.00 | 24.77 | 64.00 | 24.94 |
July | 86.50 | 26.63 | 497.00 | 24.98 | 86.50 | 25.19 |
August | 64.17 | 26.62 | 514.00 | 24.79 | 64.17 | 24.97 |
September | 75.83 | 26.59 | 485.00 | 24.90 | 75.83 | 25.10 |
October | 71.83 | 26.64 | 498.50 | 24.90 | 71.83 | 25.10 |
November | 41.17 | 26.70 | 465.67 | 24.73 | 39.50 | 24.88 |
December | 71.83 | 24.24 | 338.17 | 24.46 | 19.00 | 24.57 |
Annual Sum or Average | 791.00 | 25.47 | 5153.50 | 24.68 | 516.17 | 24.84 |
Minimum of Months | 41.17 | 23.48 | 260.17 | 24.21 | 5.17 | 24.25 |
Maximum of Months | 114.83 | 26.72 | 514.00 | 24.98 | 86.50 | 25.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 166.67 | 23.26 | 186.00 | 23.84 | 0.00 | 23.84 |
February | 82.00 | 23.36 | 263.67 | 24.11 | 2.67 | 24.12 |
March | 54.67 | 23.75 | 349.00 | 24.28 | 4.67 | 24.31 |
April | 46.17 | 25.82 | 437.17 | 24.64 | 38.33 | 24.76 |
May | 50.83 | 26.82 | 506.00 | 24.82 | 50.83 | 24.98 |
June | 76.67 | 26.62 | 496.00 | 24.87 | 76.67 | 25.07 |
July | 97.83 | 26.75 | 497.00 | 25.06 | 97.83 | 25.30 |
August | 77.00 | 26.73 | 514.00 | 24.87 | 77.00 | 25.08 |
September | 84.83 | 26.61 | 485.00 | 24.94 | 84.83 | 25.16 |
October | 66.50 | 26.47 | 493.33 | 24.84 | 66.50 | 25.02 |
November | 20.83 | 26.07 | 454.17 | 24.54 | 17.33 | 24.61 |
December | 92.83 | 23.39 | 287.67 | 24.12 | 7.00 | 24.12 |
Annual Sum or Average | 916.83 | 25.19 | 4969.00 | 24.65 | 523.67 | 24.81 |
Minimum of Months | 20.83 | 23.26 | 186.00 | 23.84 | 0.00 | 23.84 |
Maximum of Months | 166.67 | 26.82 | 514.00 | 25.06 | 97.83 | 25.30 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.45353 | 42.47943 | 0.50397 | 10.56972 |
February | 454.00000 | 24.45794 | 45.65561 | 0.53097 | 11.15295 |
March | 514.00000 | 24.40750 | 45.00167 | 0.52465 | 11.00107 |
April | 485.00000 | 24.43122 | 47.78844 | 0.55876 | 11.80742 |
May | 508.00000 | 24.43093 | 49.95944 | -0.2497 | 6.82903 |
June | 496.00000 | 24.40039 | 53.03393 | -0.2333 | 6.64928 |
July | 497.00000 | 24.39952 | 52.37734 | -0.2398 | 6.58035 |
August | 514.00000 | 24.32439 | 52.55607 | -0.2574 | 6.70745 |
September | 485.00000 | 24.42521 | 52.38887 | -0.2307 | 6.62948 |
October | 502.00000 | 24.48499 | 50.57293 | 0.60562 | 13.02808 |
November | 489.00000 | 24.48995 | 49.70831 | 0.59177 | 12.58458 |
December | 497.00000 | 24.45109 | 46.91944 | 0.54232 | 11.41262 |
Annual Sum or Average | 5943.00000 | 24.42915 | 49.05144 | 0.21735 | 9.56035 |
Minimum of Months | 454.00000 | 24.32439 | 42.47943 | -0.2574 | 6.58035 |
Maximum of Months | 514.00000 | 24.48995 | 53.03393 | 0.60562 | 13.02808 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.15565 | 43.09941 | 0.40564 | 8.60571 |
February | 454.00000 | 24.22797 | 46.17471 | 0.45267 | 9.44685 |
March | 514.00000 | 24.25109 | 45.48622 | 0.46736 | 9.72795 |
April | 485.00000 | 24.31292 | 48.95097 | 0.52045 | 10.86356 |
May | 508.00000 | 24.36361 | 51.73595 | -0.2801 | 7.09586 |
June | 496.00000 | 24.33712 | 54.87564 | -0.2604 | 6.84209 |
July | 497.00000 | 24.34549 | 54.89564 | -0.2535 | 6.68287 |
August | 514.00000 | 24.29133 | 55.71018 | -0.2625 | 6.73753 |
September | 485.00000 | 24.38084 | 55.23133 | -0.2453 | 6.75235 |
October | 502.00000 | 24.40438 | 52.84313 | 0.58577 | 12.48090 |
November | 489.00000 | 24.34967 | 50.93863 | 0.54355 | 11.34128 |
December | 497.00000 | 24.22145 | 47.08988 | 0.45959 | 9.60196 |
Annual Sum or Average | 5943.00000 | 24.30365 | 50.60841 | 0.17478 | 8.83714 |
Minimum of Months | 454.00000 | 24.15565 | 43.09941 | -0.2801 | 6.68287 |
Maximum of Months | 514.00000 | 24.40438 | 55.71018 | 0.58577 | 12.48090 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.85453 | 44.48851 | 0.33064 | 7.70009 |
February | 454.00000 | 24.02868 | 45.86828 | 0.39534 | 8.54498 |
March | 514.00000 | 24.15601 | 44.85287 | 0.43772 | 9.23001 |
April | 485.00000 | 24.30329 | 48.22212 | 0.51765 | 10.83558 |
May | 508.00000 | 24.41403 | 51.29917 | -0.2481 | 6.93384 |
June | 496.00000 | 24.39588 | 54.77953 | -0.2201 | 6.64902 |
July | 497.00000 | 24.43439 | 54.64603 | -0.1995 | 6.48892 |
August | 514.00000 | 24.34171 | 55.63634 | -0.2204 | 6.49874 |
September | 485.00000 | 24.42900 | 55.27162 | -0.2118 | 6.63018 |
October | 502.00000 | 24.42619 | 52.61726 | 0.59438 | 12.73924 |
November | 489.00000 | 24.29956 | 50.32622 | 0.52312 | 10.88391 |
December | 497.00000 | 23.99919 | 46.63483 | 0.39349 | 8.54300 |
Annual Sum or Average | 5943.00000 | 24.25805 | 50.41123 | 0.17179 | 8.46523 |
Minimum of Months | 454.00000 | 23.85453 | 44.48851 | -0.2481 | 6.48892 |
Maximum of Months | 514.00000 | 24.43439 | 55.63634 | 0.59438 | 12.73924 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.43031 | 46.30381 | 0.22900 | 7.12056 |
February | 454.00000 | 23.74684 | 49.22459 | 0.34654 | 8.36712 |
March | 514.00000 | 24.01815 | 46.80856 | 0.42582 | 9.42300 |
April | 485.00000 | 24.35490 | 50.04075 | 0.56862 | 12.45322 |
May | 508.00000 | 24.58748 | 51.84779 | -0.1045 | 6.77929 |
June | 496.00000 | 24.58062 | 55.76770 | -0.0496 | 6.63457 |
July | 497.00000 | 24.70946 | 55.20322 | 0.00838 | 6.93202 |
August | 514.00000 | 24.56928 | 56.28799 | -0.0313 | 6.52618 |
September | 485.00000 | 24.61812 | 56.84643 | -0.0585 | 6.83417 |
October | 502.00000 | 24.55949 | 54.47318 | 0.67271 | 15.29347 |
November | 489.00000 | 24.28788 | 52.46359 | 0.54378 | 11.64234 |
December | 497.00000 | 23.73583 | 49.97940 | 0.34451 | 8.30827 |
Annual Sum or Average | 5943.00000 | 24.26961 | 52.11170 | 0.23958 | 8.85158 |
Minimum of Months | 454.00000 | 23.43031 | 46.30381 | -0.1045 | 6.52618 |
Maximum of Months | 514.00000 | 24.70946 | 56.84643 | 0.67271 | 15.29347 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.70670 | 45.52584 | 0.30948 | 8.01826 |
February | 454.00000 | 23.94477 | 48.58407 | 0.41228 | 9.45971 |
March | 514.00000 | 24.12800 | 46.44313 | 0.47581 | 10.49017 |
April | 485.00000 | 24.44704 | 49.57054 | 0.62493 | 14.08575 |
May | 508.00000 | 24.62479 | 51.62537 | -0.0356 | 6.83110 |
June | 496.00000 | 24.59907 | 55.60624 | 0.00466 | 6.73625 |
July | 497.00000 | 24.73521 | 55.04457 | 0.06549 | 7.28615 |
August | 514.00000 | 24.59126 | 56.09860 | 0.03090 | 6.68464 |
September | 485.00000 | 24.65595 | 56.49821 | 0.00856 | 7.02391 |
October | 502.00000 | 24.62509 | 53.96602 | 0.72271 | 16.92904 |
November | 489.00000 | 24.42335 | 52.02878 | 0.60196 | 13.23510 |
December | 497.00000 | 23.92921 | 49.46094 | 0.40575 | 9.25563 |
Annual Sum or Average | 5943.00000 | 24.36983 | 51.71455 | 0.30049 | 9.65655 |
Minimum of Months | 454.00000 | 23.70670 | 45.52584 | -0.0356 | 6.68464 |
Maximum of Months | 514.00000 | 24.73521 | 56.49821 | 0.72271 | 16.92904 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.89787 | 43.94810 | 0.37829 | 9.57664 |
February | 454.00000 | 24.02325 | 47.59874 | 0.45275 | 10.55389 |
March | 514.00000 | 24.13019 | 46.03093 | 0.48459 | 10.80759 |
April | 485.00000 | 24.39087 | 49.77979 | 0.59427 | 13.21844 |
May | 508.00000 | 24.58190 | 51.87619 | -0.1055 | 6.79792 |
June | 496.00000 | 24.57018 | 55.87141 | -0.0636 | 6.63861 |
July | 497.00000 | 24.70321 | 55.24587 | 0.00334 | 6.92511 |
August | 514.00000 | 24.57421 | 56.18974 | -0.0142 | 6.57428 |
September | 485.00000 | 24.64718 | 56.47270 | -0.0027 | 7.01536 |
October | 502.00000 | 24.63945 | 53.71333 | 0.74453 | 17.68961 |
November | 489.00000 | 24.47032 | 51.21707 | 0.64672 | 14.69455 |
December | 497.00000 | 24.11117 | 47.87810 | 0.47817 | 11.16521 |
Annual Sum or Average | 5943.00000 | 24.39693 | 51.33314 | 0.29755 | 10.12105 |
Minimum of Months | 454.00000 | 23.89787 | 43.94810 | -0.1055 | 6.57428 |
Maximum of Months | 514.00000 | 24.70321 | 56.47270 | 0.74453 | 17.68961 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.59276 | 45.97606 | 0.28249 | 8.01922 |
February | 454.00000 | 23.86690 | 48.91726 | 0.39524 | 9.36340 |
March | 514.00000 | 24.09895 | 46.57115 | 0.47126 | 10.51370 |
April | 485.00000 | 24.41177 | 49.90581 | 0.61039 | 13.72417 |
May | 508.00000 | 24.61768 | 51.81143 | -0.0523 | 6.96030 |
June | 496.00000 | 24.60608 | 55.71044 | -0.0007 | 6.86320 |
July | 497.00000 | 24.73415 | 55.13676 | 0.05651 | 7.29446 |
August | 514.00000 | 24.59769 | 56.17998 | 0.02466 | 6.80105 |
September | 485.00000 | 24.65794 | 56.66673 | 0.00183 | 7.12249 |
October | 502.00000 | 24.60796 | 54.36962 | 0.71479 | 16.68935 |
November | 489.00000 | 24.36136 | 52.26252 | 0.58700 | 12.91817 |
December | 497.00000 | 23.86978 | 49.68598 | 0.39305 | 9.33188 |
Annual Sum or Average | 5943.00000 | 24.33796 | 51.94171 | 0.28866 | 9.62231 |
Minimum of Months | 454.00000 | 23.59276 | 45.97606 | -0.0523 | 6.80105 |
Maximum of Months | 514.00000 | 24.73415 | 56.66673 | 0.71479 | 16.68935 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.98649 | 45.94610 | 0.37924 | 8.29923 |
February | 454.00000 | 24.06595 | 49.28269 | 0.43124 | 9.18840 |
March | 514.00000 | 24.13219 | 47.54750 | 0.45209 | 9.54563 |
April | 485.00000 | 24.34154 | 49.95556 | 0.54753 | 11.60477 |
May | 508.00000 | 24.54823 | 50.78672 | -0.1549 | 6.55711 |
June | 496.00000 | 24.55170 | 53.92691 | -0.0967 | 6.37393 |
July | 497.00000 | 24.68031 | 52.63971 | -0.0399 | 6.49343 |
August | 514.00000 | 24.55360 | 52.78007 | -0.0648 | 6.30159 |
September | 485.00000 | 24.61204 | 53.18647 | -0.0784 | 6.52803 |
October | 502.00000 | 24.60541 | 51.60580 | 0.67980 | 15.36664 |
November | 489.00000 | 24.45485 | 51.11171 | 0.60085 | 12.83733 |
December | 497.00000 | 24.18010 | 49.67743 | 0.47443 | 9.96991 |
Annual Sum or Average | 5943.00000 | 24.39445 | 50.70340 | 0.25864 | 9.07688 |
Minimum of Months | 454.00000 | 23.98649 | 45.94610 | -0.1549 | 6.30159 |
Maximum of Months | 514.00000 | 24.68031 | 53.92691 | 0.67980 | 15.36664 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.17800 | 45.39379 | 0.44537 | 9.51869 |
February | 454.00000 | 24.23099 | 48.75755 | 0.49234 | 10.47417 |
March | 514.00000 | 24.24208 | 47.19546 | 0.50334 | 10.70308 |
April | 485.00000 | 24.46881 | 49.41016 | 0.61176 | 13.42584 |
May | 508.00000 | 24.61052 | 50.46540 | -0.0762 | 6.47884 |
June | 496.00000 | 24.58655 | 53.68814 | -0.0358 | 6.40475 |
July | 497.00000 | 24.71867 | 52.42814 | 0.02304 | 6.74195 |
August | 514.00000 | 24.58567 | 52.54513 | 0.00371 | 6.38508 |
September | 485.00000 | 24.66197 | 52.83258 | -0.0045 | 6.68500 |
October | 502.00000 | 24.67423 | 51.15666 | 0.73334 | 17.11795 |
November | 489.00000 | 24.57533 | 50.76101 | 0.65855 | 14.58509 |
December | 497.00000 | 24.30269 | 49.35135 | 0.52343 | 11.10241 |
Annual Sum or Average | 5943.00000 | 24.48740 | 50.33332 | 0.32098 | 9.94998 |
Minimum of Months | 454.00000 | 24.17800 | 45.39379 | -0.0762 | 6.38508 |
Maximum of Months | 514.00000 | 24.71867 | 53.68814 | 0.73334 | 17.11795 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.16703 | 44.68028 | 0.48317 | 10.98718 |
February | 454.00000 | 24.20179 | 48.69461 | 0.52039 | 11.54957 |
March | 514.00000 | 24.18166 | 47.25819 | 0.50493 | 11.04686 |
April | 485.00000 | 24.40783 | 50.42786 | 0.58548 | 12.77021 |
May | 508.00000 | 24.70248 | 52.12225 | -0.1011 | 6.45033 |
June | 496.00000 | 24.75594 | 57.01514 | -0.0298 | 6.38356 |
July | 497.00000 | 24.93003 | 57.28930 | 0.05972 | 6.80155 |
August | 514.00000 | 24.88526 | 58.20523 | 0.08557 | 6.96987 |
September | 485.00000 | 24.89101 | 57.01225 | 0.08232 | 6.99001 |
October | 502.00000 | 24.86212 | 53.63556 | 0.81210 | 19.73417 |
November | 489.00000 | 24.65803 | 52.35592 | 0.73010 | 16.88284 |
December | 497.00000 | 24.34070 | 49.28895 | 0.57938 | 12.99376 |
Annual Sum or Average | 5943.00000 | 24.58417 | 52.34858 | 0.35712 | 10.77687 |
Minimum of Months | 454.00000 | 24.16703 | 44.68028 | -0.1011 | 6.38356 |
Maximum of Months | 514.00000 | 24.93003 | 58.20523 | 0.81210 | 19.73417 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.14948 | 45.49009 | 0.43500 | 9.37532 |
February | 454.00000 | 24.20860 | 48.80973 | 0.48601 | 10.35880 |
March | 514.00000 | 24.24960 | 47.10773 | 0.50679 | 10.78391 |
April | 485.00000 | 24.44865 | 49.65639 | 0.60169 | 13.13312 |
May | 508.00000 | 24.60710 | 50.63098 | -0.0903 | 6.55223 |
June | 496.00000 | 24.59562 | 53.75786 | -0.0388 | 6.48268 |
July | 497.00000 | 24.72058 | 52.49938 | 0.01619 | 6.73277 |
August | 514.00000 | 24.59438 | 52.62515 | -0.0009 | 6.47020 |
September | 485.00000 | 24.66954 | 52.94564 | -0.0085 | 6.74092 |
October | 502.00000 | 24.67467 | 51.40314 | 0.72920 | 16.99127 |
November | 489.00000 | 24.55085 | 50.87467 | 0.65162 | 14.36637 |
December | 497.00000 | 24.29883 | 49.32327 | 0.52194 | 11.11814 |
Annual Sum or Average | 5943.00000 | 24.48198 | 50.42785 | 0.31528 | 9.90871 |
Minimum of Months | 454.00000 | 24.14948 | 45.49009 | -0.0903 | 6.47020 |
Maximum of Months | 514.00000 | 24.72058 | 53.75786 | 0.72920 | 16.99127 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.75771 | 45.98995 | 0.31496 | 7.57793 |
February | 454.00000 | 23.96373 | 49.09605 | 0.40339 | 8.84866 |
March | 514.00000 | 24.13002 | 47.06460 | 0.45544 | 9.68732 |
April | 485.00000 | 24.38986 | 50.36687 | 0.57320 | 12.37197 |
May | 508.00000 | 24.57842 | 51.96890 | -0.1276 | 6.68057 |
June | 496.00000 | 24.56736 | 55.53707 | -0.0799 | 6.54329 |
July | 497.00000 | 24.69711 | 55.04169 | -0.0272 | 6.71361 |
August | 514.00000 | 24.56029 | 56.05703 | -0.0639 | 6.44322 |
September | 485.00000 | 24.60674 | 56.43739 | -0.0849 | 6.72319 |
October | 502.00000 | 24.56146 | 54.28806 | 0.66476 | 14.98289 |
November | 489.00000 | 24.34784 | 52.54684 | 0.56108 | 11.87223 |
December | 497.00000 | 23.96818 | 49.94836 | 0.40795 | 8.92108 |
Annual Sum or Average | 5943.00000 | 24.34628 | 52.03698 | 0.24771 | 8.93660 |
Minimum of Months | 454.00000 | 23.75771 | 45.98995 | -0.1276 | 6.44322 |
Maximum of Months | 514.00000 | 24.69711 | 56.43739 | 0.66476 | 14.98289 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.96326 | 45.08795 | 0.37042 | 8.52402 |
February | 385.00000 | 24.14723 | 48.36640 | 0.45464 | 9.97345 |
March | 433.00000 | 24.26748 | 46.36031 | 0.49627 | 10.72709 |
April | 410.00000 | 24.57230 | 49.79068 | 0.63410 | 14.28981 |
May | 430.00000 | 24.73149 | 51.57575 | -0.0447 | 6.90074 |
June | 418.00000 | 24.70050 | 55.34537 | -0.0112 | 6.84088 |
July | 422.00000 | 24.85671 | 54.56675 | 0.05013 | 7.31044 |
August | 433.00000 | 24.69483 | 55.73884 | 0.01099 | 6.77403 |
September | 410.00000 | 24.76783 | 56.03906 | -0.0005 | 7.13814 |
October | 427.00000 | 24.74256 | 53.68983 | 0.72635 | 17.08675 |
November | 417.00000 | 24.55891 | 51.49776 | 0.61943 | 13.63872 |
December | 422.00000 | 24.14008 | 49.25662 | 0.45448 | 9.91132 |
Annual Sum or Average | 5034.00000 | 24.51356 | 51.44980 | 0.31190 | 9.91672 |
Minimum of Months | 385.00000 | 23.96326 | 45.08795 | -0.0447 | 6.77403 |
Maximum of Months | 433.00000 | 24.85671 | 56.03906 | 0.72635 | 17.08675 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.14455 | 43.92801 | 0.44748 | 10.20530 |
February | 454.00000 | 24.20136 | 47.62156 | 0.50082 | 11.07380 |
March | 514.00000 | 24.23522 | 46.31900 | 0.51165 | 11.05922 |
April | 485.00000 | 24.43180 | 50.08166 | 0.59915 | 13.14738 |
May | 508.00000 | 24.57173 | 51.99211 | -0.1290 | 6.68806 |
June | 496.00000 | 24.55409 | 55.64386 | -0.0945 | 6.55110 |
July | 497.00000 | 24.68850 | 55.08915 | -0.0329 | 6.70217 |
August | 514.00000 | 24.56515 | 55.94790 | -0.0475 | 6.45378 |
September | 485.00000 | 24.63839 | 56.03439 | -0.0300 | 6.80938 |
October | 502.00000 | 24.64497 | 53.51033 | 0.73580 | 17.31038 |
November | 489.00000 | 24.52957 | 51.38168 | 0.66202 | 14.93916 |
December | 497.00000 | 24.28385 | 48.08259 | 0.52873 | 11.83751 |
Annual Sum or Average | 5943.00000 | 24.45864 | 51.31736 | 0.30182 | 10.21158 |
Minimum of Months | 454.00000 | 24.14455 | 43.92801 | -0.1290 | 6.45378 |
Maximum of Months | 514.00000 | 24.68850 | 56.03439 | 0.73580 | 17.31038 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.90228 | 45.69242 | 0.36421 | 8.50988 |
February | 454.00000 | 24.07362 | 48.80213 | 0.44930 | 9.85105 |
March | 514.00000 | 24.20856 | 46.82026 | 0.49959 | 10.76710 |
April | 485.00000 | 24.45549 | 50.22305 | 0.61617 | 13.67089 |
May | 508.00000 | 24.61207 | 51.92781 | -0.0748 | 6.77351 |
June | 496.00000 | 24.59462 | 55.46865 | -0.0310 | 6.67921 |
July | 497.00000 | 24.72504 | 54.95796 | 0.02136 | 6.98262 |
August | 514.00000 | 24.59037 | 55.93327 | -0.0081 | 6.61816 |
September | 485.00000 | 24.65193 | 56.23959 | -0.0241 | 6.92313 |
October | 502.00000 | 24.61517 | 54.18055 | 0.70732 | 16.36964 |
November | 489.00000 | 24.42887 | 52.35853 | 0.60487 | 13.17785 |
December | 497.00000 | 24.08606 | 49.67874 | 0.45260 | 9.94199 |
Annual Sum or Average | 5943.00000 | 24.41387 | 51.86634 | 0.29608 | 9.67447 |
Minimum of Months | 454.00000 | 23.90228 | 45.69242 | -0.0748 | 6.61816 |
Maximum of Months | 514.00000 | 24.72504 | 56.23959 | 0.70732 | 16.36964 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.393192E+11 | 0.969071E+10 | 407.75 | 0.337498E+11 | 0.556936E+10 | 0.00 | 1.00 | 02-JAN-13:30 | 0.00 | 01-JAN-00:10 | 62212.15 | 30-JAN-07:03 | 51131.83 | 23-JAN-14:00 | 14534.73 | 30-JAN-14:00 | 14275.81 | 30-JAN-07:03 | 0.00 |
February | 0.421885E+11 | 0.104464E+11 | 369.22 | 0.355716E+11 | 0.661695E+10 | 0.00 | 1.00 | 01-FEB-13:30 | 0.00 | 01-FEB-00:10 | 75569.16 | 06-FEB-06:12 | 62508.35 | 06-FEB-15:00 | 25706.04 | 07-FEB-06:12 | 20066.37 | 07-FEB-13:03 | 0.00 |
March | 0.568526E+11 | 0.145208E+11 | 436.42 | 0.496804E+11 | 0.717222E+10 | 0.00 | 1.00 | 01-MAR-07:03 | 0.00 | 01-MAR-00:10 | 81542.55 | 28-MAR-11:40 | 80194.54 | 02-MAR-07:03 | 28850.40 | 29-MAR-05:12 | 24931.10 | 27-MAR-12:09 | 0.00 |
April | 0.683259E+11 | 0.183238E+11 | 428.86 | 0.581400E+11 | 0.101859E+11 | 0.00 | 1.00 | 02-APR-14:43 | 0.00 | 01-APR-00:10 | 90992.28 | 10-APR-12:00 | 77846.62 | 28-APR-12:02 | 34265.36 | 12-APR-05:12 | 29552.62 | 28-APR-12:00 | 0.00 |
May | 0.103560E+12 | 0.300688E+11 | 495.77 | 0.853408E+11 | 0.182189E+11 | 0.00 | 1.00 | 01-MAY-05:12 | 0.00 | 01-MAY-00:05 | 139406.13 | 31-MAY-04:02 | 98057.79 | 22-MAY-06:03 | 66209.23 | 24-MAY-04:03 | 37868.30 | 31-MAY-12:02 | 0.00 |
June | 0.126080E+12 | 0.368558E+11 | 505.29 | 0.922569E+11 | 0.338227E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:05 | 144013.73 | 14-JUN-04:03 | 96419.28 | 01-JUN-04:02 | 70106.02 | 08-JUN-04:03 | 39792.78 | 12-JUN-12:02 | 0.00 |
July | 0.153908E+12 | 0.457089E+11 | 578.61 | 0.102522E+12 | 0.513858E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:10 | 141844.45 | 06-JUL-04:02 | 97623.25 | 03-JUL-06:03 | 73057.00 | 20-JUL-06:07 | 41863.48 | 30-JUL-15:22 | 0.00 |
August | 0.171448E+12 | 0.510847E+11 | 606.01 | 0.112112E+12 | 0.593353E+11 | 0.00 | 1.00 | 01-AUG-00:05 | 0.00 | 01-AUG-00:25 | 141948.54 | 26-AUG-04:02 | 100946.81 | 07-AUG-05:02 | 67561.97 | 22-AUG-17:00 | 43963.11 | 10-AUG-15:30 | 0.00 |
September | 0.136687E+12 | 0.387945E+11 | 525.54 | 0.922907E+11 | 0.443965E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:15 | 142895.71 | 28-SEP-04:02 | 99793.27 | 13-SEP-04:02 | 69952.06 | 10-SEP-14:42 | 39268.79 | 07-SEP-12:02 | 0.00 |
October | 0.109762E+12 | 0.297749E+11 | 502.14 | 0.823286E+11 | 0.274335E+11 | 0.00 | 1.00 | 01-OCT-08:13 | 0.00 | 01-OCT-00:10 | 141144.59 | 18-OCT-04:03 | 94724.50 | 11-OCT-04:02 | 62578.03 | 18-OCT-04:03 | 35928.50 | 08-OCT-11:52 | 0.00 |
November | 0.784051E+11 | 0.200574E+11 | 433.81 | 0.630612E+11 | 0.153439E+11 | 0.00 | 1.00 | 01-NOV-04:42 | 0.00 | 01-NOV-00:10 | 137441.31 | 02-NOV-06:03 | 94019.08 | 20-NOV-05:02 | 52956.73 | 02-NOV-05:12 | 31470.17 | 02-NOV-06:03 | 0.00 |
December | 0.502914E+11 | 0.123007E+11 | 410.50 | 0.416582E+11 | 0.863326E+10 | 0.00 | 1.00 | 01-DEC-09:50 | 0.00 | 01-DEC-00:10 | 89407.71 | 11-DEC-07:03 | 69042.40 | 12-DEC-07:03 | 26698.74 | 11-DEC-06:12 | 20543.60 | 11-DEC-07:03 | 0.00 |
Annual Sum or Average | 0.113683E+13 | 0.317627E+12 | 5699.91 | 0.848712E+12 | 0.288114E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.393192E+11 | 0.969071E+10 | 369.22 | 0.337498E+11 | 0.556936E+10 | 0.00 | 1.00 | 0.00 | 62212.15 | 51131.83 | 14534.73 | 14275.81 | 0.00 | ||||||
Maximum of Months | 0.171448E+12 | 0.510847E+11 | 606.01 | 0.112112E+12 | 0.593353E+11 | 0.00 | 1.00 | 0.00 | 144013.73 | 100946.81 | 73057.00 | 43963.11 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.285413E+11 | 0.721775E+10 | 403.03 | 0.228256E+11 | 0.571571E+10 | 0.00 | 1.00 | 23-JAN-13:05 | 0.00 | 01-JAN-00:10 | 44306.12 | 30-JAN-14:00 | 39306.39 | 23-JAN-13:30 | 12995.23 | 30-JAN-15:05 | 10186.70 | 30-JAN-14:00 | 0.00 |
February | 0.328851E+11 | 0.829704E+10 | 369.94 | 0.264240E+11 | 0.646107E+10 | 0.00 | 1.00 | 05-FEB-13:43 | 0.00 | 01-FEB-00:10 | 64557.96 | 07-FEB-15:05 | 57292.40 | 06-FEB-15:05 | 21765.41 | 06-FEB-06:12 | 16205.87 | 06-FEB-15:05 | 0.00 |
March | 0.468932E+11 | 0.121114E+11 | 438.03 | 0.399342E+11 | 0.695896E+10 | 0.00 | 1.00 | 01-MAR-10:20 | 0.00 | 01-MAR-00:10 | 67806.82 | 27-MAR-14:05 | 67806.82 | 27-MAR-14:05 | 15385.10 | 31-MAR-18:10 | 22774.55 | 27-MAR-11:00 | 0.00 |
April | 0.593180E+11 | 0.159284E+11 | 434.00 | 0.498547E+11 | 0.946326E+10 | 0.00 | 1.00 | 01-APR-14:05 | 0.00 | 01-APR-00:10 | 111632.94 | 30-APR-15:13 | 71136.74 | 28-APR-12:02 | 46506.99 | 30-APR-15:13 | 28201.94 | 30-APR-15:13 | 0.00 |
May | 0.917880E+11 | 0.264563E+11 | 500.68 | 0.755952E+11 | 0.161928E+11 | 0.00 | 1.00 | 01-MAY-05:12 | 0.00 | 01-MAY-00:05 | 129600.60 | 24-MAY-05:03 | 88299.92 | 21-MAY-13:02 | 64086.36 | 24-MAY-05:03 | 34949.03 | 31-MAY-12:01 | 0.00 |
June | 0.112050E+12 | 0.324109E+11 | 506.90 | 0.811252E+11 | 0.309250E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:15 | 132084.44 | 14-JUN-04:03 | 85001.33 | 01-JUN-04:02 | 65976.58 | 14-JUN-04:03 | 38386.42 | 12-JUN-12:01 | 0.00 |
July | 0.136234E+12 | 0.400885E+11 | 568.86 | 0.908486E+11 | 0.453851E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:10 | 131225.28 | 06-JUL-04:02 | 96766.84 | 30-JUL-13:22 | 62265.49 | 06-JUL-04:02 | 41142.50 | 30-JUL-14:02 | 0.00 |
August | 0.146519E+12 | 0.433046E+11 | 578.89 | 0.967216E+11 | 0.497975E+11 | 0.00 | 1.00 | 01-AUG-00:25 | 0.00 | 01-AUG-00:05 | 130705.45 | 09-AUG-04:02 | 89791.08 | 06-AUG-14:51 | 65391.12 | 08-AUG-04:02 | 41828.98 | 16-AUG-12:01 | 0.00 |
September | 0.114385E+12 | 0.322089E+11 | 494.79 | 0.772507E+11 | 0.371341E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:05 | 131346.16 | 28-SEP-04:02 | 92239.72 | 04-SEP-14:52 | 67194.08 | 10-SEP-16:42 | 39183.48 | 04-SEP-14:52 | 0.00 |
October | 0.883668E+11 | 0.238797E+11 | 473.00 | 0.662339E+11 | 0.221329E+11 | 0.00 | 1.00 | 01-OCT-07:47 | 0.00 | 01-OCT-00:10 | 129979.31 | 07-OCT-05:03 | 86246.24 | 09-OCT-15:01 | 63856.00 | 07-OCT-05:03 | 33915.52 | 01-OCT-11:42 | 0.00 |
November | 0.603037E+11 | 0.154962E+11 | 417.17 | 0.473580E+11 | 0.129457E+11 | 0.00 | 1.00 | 01-NOV-04:42 | 0.00 | 01-NOV-00:10 | 96580.00 | 03-NOV-05:03 | 71351.91 | 20-NOV-07:03 | 44293.99 | 03-NOV-05:03 | 24514.28 | 01-NOV-12:02 | 0.00 |
December | 0.374783E+11 | 0.936663E+10 | 404.78 | 0.290607E+11 | 0.841759E+10 | 0.00 | 1.00 | 01-DEC-11:05 | 0.00 | 01-DEC-00:10 | 62703.45 | 05-DEC-15:05 | 48488.40 | 04-DEC-13:05 | 24015.58 | 11-DEC-06:12 | 14991.24 | 04-DEC-13:05 | 0.00 |
Annual Sum or Average | 0.954762E+12 | 0.266766E+12 | 5590.07 | 0.703232E+12 | 0.251530E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.285413E+11 | 0.721775E+10 | 369.94 | 0.228256E+11 | 0.571571E+10 | 0.00 | 1.00 | 0.00 | 44306.12 | 39306.39 | 12995.23 | 10186.70 | 0.00 | ||||||
Maximum of Months | 0.146519E+12 | 0.433046E+11 | 578.89 | 0.967216E+11 | 0.497975E+11 | 0.00 | 1.00 | 0.00 | 132084.44 | 96766.84 | 67194.08 | 41828.98 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.278785E+11 | 0.715714E+10 | 400.22 | 0.214807E+11 | 0.639788E+10 | 0.00 | 0.96 | 23-JAN-14:00 | 0.00 | 01-JAN-00:10 | 44073.48 | 30-JAN-14:10 | 41624.85 | 23-JAN-14:00 | 13380.06 | 30-JAN-15:10 | 10688.56 | 23-JAN-14:00 | 0.00 |
February | 0.332198E+11 | 0.849638E+10 | 369.08 | 0.262449E+11 | 0.697489E+10 | 0.00 | 1.00 | 05-FEB-15:23 | 0.00 | 01-FEB-00:10 | 68100.72 | 07-FEB-15:30 | 63250.90 | 05-FEB-15:23 | 17199.62 | 07-FEB-16:00 | 17678.86 | 05-FEB-15:23 | 0.00 |
March | 0.488189E+11 | 0.127567E+11 | 438.03 | 0.411828E+11 | 0.763610E+10 | 0.00 | 1.00 | 01-MAR-10:50 | 0.00 | 01-MAR-00:10 | 74883.87 | 27-MAR-13:10 | 74883.87 | 27-MAR-13:10 | 16514.84 | 31-MAR-18:00 | 24449.01 | 27-MAR-12:03 | 0.00 |
April | 0.633652E+11 | 0.171855E+11 | 436.03 | 0.532593E+11 | 0.101059E+11 | 0.00 | 1.00 | 01-APR-14:05 | 0.00 | 01-APR-00:10 | 95470.85 | 30-APR-12:13 | 85959.05 | 30-APR-12:13 | 33702.69 | 30-APR-16:53 | 29971.46 | 28-APR-12:02 | 0.00 |
May | 0.997792E+11 | 0.289192E+11 | 507.52 | 0.828474E+11 | 0.169318E+11 | 0.00 | 1.00 | 01-MAY-05:12 | 0.00 | 01-MAY-00:05 | 145751.11 | 31-MAY-04:02 | 105384.04 | 21-MAY-13:02 | 74054.40 | 24-MAY-05:03 | 38031.51 | 29-MAY-14:42 | 0.00 |
June | 0.122468E+12 | 0.355693E+11 | 516.96 | 0.901705E+11 | 0.322970E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:33 | 151045.14 | 14-JUN-04:03 | 98906.40 | 18-JUN-14:32 | 79922.57 | 20-JUN-04:03 | 42198.52 | 11-JUN-09:52 | 0.00 |
July | 0.149994E+12 | 0.442631E+11 | 589.99 | 0.102018E+12 | 0.479757E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:10 | 149245.98 | 06-JUL-04:02 | 115732.66 | 30-JUL-13:22 | 67787.83 | 06-JUL-04:02 | 47417.16 | 30-JUL-14:02 | 0.00 |
August | 0.159555E+12 | 0.472875E+11 | 598.95 | 0.107552E+12 | 0.520029E+11 | 0.00 | 1.00 | 01-AUG-00:45 | 0.00 | 01-AUG-00:25 | 149027.35 | 26-AUG-04:02 | 107337.66 | 06-AUG-15:02 | 68366.76 | 26-AUG-04:02 | 44658.10 | 06-AUG-15:02 | 0.00 |
September | 0.122735E+12 | 0.346823E+11 | 506.16 | 0.843490E+11 | 0.383858E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:35 | 150680.07 | 28-SEP-04:02 | 115113.39 | 04-SEP-14:31 | 74415.62 | 28-SEP-04:02 | 44806.26 | 04-SEP-13:52 | 0.00 |
October | 0.922635E+11 | 0.251050E+11 | 472.61 | 0.696511E+11 | 0.226124E+11 | 0.00 | 1.00 | 01-OCT-08:33 | 0.00 | 01-OCT-00:10 | 146147.93 | 02-OCT-04:02 | 97416.80 | 09-OCT-14:32 | 67211.24 | 07-OCT-05:03 | 37078.64 | 01-OCT-13:52 | 0.00 |
November | 0.612708E+11 | 0.159132E+11 | 416.31 | 0.478526E+11 | 0.134182E+11 | 0.00 | 1.00 | 01-NOV-05:03 | 0.00 | 01-NOV-00:10 | 104379.62 | 03-NOV-05:03 | 69018.99 | 20-NOV-06:03 | 49389.54 | 03-NOV-05:03 | 25072.53 | 01-NOV-14:00 | 0.00 |
December | 0.370805E+11 | 0.942060E+10 | 404.19 | 0.279522E+11 | 0.912828E+10 | 0.00 | 1.00 | 01-DEC-13:05 | 0.00 | 01-DEC-00:10 | 63420.10 | 05-DEC-15:00 | 49415.35 | 04-DEC-14:05 | 19251.79 | 05-DEC-15:00 | 15054.07 | 05-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.101843E+13 | 0.286756E+12 | 5656.04 | 0.754561E+12 | 0.263867E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.278785E+11 | 0.715714E+10 | 369.08 | 0.214807E+11 | 0.639788E+10 | 0.00 | 0.96 | 0.00 | 44073.48 | 41624.85 | 13380.06 | 10688.56 | 0.00 | ||||||
Maximum of Months | 0.159555E+12 | 0.472875E+11 | 598.95 | 0.107552E+12 | 0.520029E+11 | 0.00 | 1.00 | 0.00 | 151045.14 | 115732.66 | 79922.57 | 47417.16 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 315.55 | 0.00 | 315.55 | 365.77 | 680.92 | 0.00 | 0.00 | 0.00 |
February | 361.71 | 0.00 | 361.71 | 502.07 | 571.73 | 0.00 | 0.00 | 0.00 |
March | 415.47 | 0.00 | 415.47 | 720.87 | 437.04 | 0.00 | 0.00 | 0.00 |
April | 468.10 | 0.96 | 467.13 | 1044.09 | 276.85 | 0.00 | 0.00 | 0.00 |
May | 526.89 | 15.45 | 511.43 | 1587.27 | 71.47 | 0.00 | 0.00 | 0.00 |
June | 564.13 | 31.32 | 532.81 | 1836.86 | 18.64 | 0.00 | 0.00 | 0.00 |
July | 517.65 | 14.91 | 502.73 | 2053.78 | 0.46 | 0.00 | 0.00 | 0.00 |
August | 481.88 | 3.99 | 477.90 | 2026.92 | 0.09 | 0.00 | 0.00 | 0.00 |
September | 438.95 | 0.05 | 438.90 | 1520.74 | 26.74 | 0.00 | 0.00 | 0.00 |
October | 389.12 | 0.00 | 389.12 | 1087.66 | 116.70 | 0.00 | 0.00 | 0.00 |
November | 334.05 | 0.00 | 334.05 | 689.98 | 315.78 | 0.00 | 0.00 | 0.00 |
December | 294.52 | 0.00 | 294.52 | 409.52 | 558.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 425.91 | 5.58 | 420.34 | 1157.85 | 254.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 294.52 | 0.00 | 294.52 | 365.77 | 0.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 564.13 | 31.32 | 532.81 | 2053.78 | 680.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 380.55 | 115.13 | 265.41 | 526.85 | 429.70 | 0.00 | 0.00 | 0.00 |
February | 414.71 | 112.39 | 302.32 | 635.92 | 363.85 | 0.00 | 0.00 | 0.00 |
March | 458.09 | 112.90 | 345.19 | 809.43 | 279.95 | 0.00 | 0.00 | 0.00 |
April | 557.74 | 162.51 | 395.23 | 1156.32 | 179.06 | 0.00 | 0.00 | 0.00 |
May | 623.29 | 198.58 | 424.71 | 1565.56 | 45.61 | 0.00 | 0.00 | 0.00 |
June | 610.42 | 186.67 | 423.75 | 1655.04 | 11.15 | 0.00 | 0.00 | 0.00 |
July | 569.73 | 164.25 | 405.48 | 1790.13 | 0.25 | 0.00 | 0.00 | 0.00 |
August | 583.40 | 179.05 | 404.34 | 1850.87 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 548.46 | 169.52 | 378.94 | 1497.36 | 16.05 | 0.00 | 0.00 | 0.00 |
October | 497.67 | 162.59 | 335.08 | 1170.42 | 72.07 | 0.00 | 0.00 | 0.00 |
November | 417.05 | 132.10 | 284.95 | 811.66 | 200.59 | 0.00 | 0.00 | 0.00 |
December | 337.56 | 92.61 | 244.95 | 514.80 | 355.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 500.22 | 149.18 | 351.04 | 1168.46 | 161.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 337.56 | 92.61 | 244.95 | 514.80 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 623.29 | 198.58 | 424.71 | 1850.87 | 429.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1019.82 | 479.46 | 540.35 | 1621.17 | 666.39 | 0.00 | 0.00 | 0.00 |
February | 957.65 | 391.72 | 565.93 | 1618.32 | 571.24 | 0.00 | 0.00 | 0.00 |
March | 788.19 | 213.99 | 574.20 | 1490.83 | 446.49 | 0.00 | 0.00 | 0.00 |
April | 619.58 | 65.69 | 553.89 | 1391.49 | 283.37 | 0.00 | 0.00 | 0.00 |
May | 524.83 | 8.04 | 516.80 | 1582.49 | 72.05 | 0.00 | 0.00 | 0.00 |
June | 494.27 | 0.61 | 493.66 | 1684.06 | 15.07 | 0.00 | 0.00 | 0.00 |
July | 494.26 | 4.20 | 490.06 | 1990.96 | 0.24 | 0.00 | 0.00 | 0.00 |
August | 573.30 | 40.62 | 532.68 | 2233.86 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 755.91 | 173.24 | 582.67 | 2202.07 | 26.67 | 0.00 | 0.00 | 0.00 |
October | 989.63 | 393.43 | 596.20 | 2283.85 | 116.74 | 0.00 | 0.00 | 0.00 |
November | 1091.76 | 526.31 | 565.45 | 2120.29 | 317.00 | 0.00 | 0.00 | 0.00 |
December | 1013.48 | 500.63 | 512.85 | 1717.90 | 556.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 775.80 | 232.32 | 543.49 | 1829.60 | 254.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 494.26 | 0.61 | 490.06 | 1391.49 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1091.76 | 526.31 | 596.20 | 2283.85 | 666.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 373.20 | 107.19 | 266.01 | 540.23 | 458.63 | 0.00 | 0.00 | 0.00 |
February | 426.15 | 121.52 | 304.63 | 678.21 | 385.82 | 0.00 | 0.00 | 0.00 |
March | 504.79 | 149.44 | 355.35 | 907.91 | 299.48 | 0.00 | 0.00 | 0.00 |
April | 551.65 | 154.98 | 396.67 | 1149.20 | 195.29 | 0.00 | 0.00 | 0.00 |
May | 600.47 | 179.74 | 420.72 | 1528.64 | 53.51 | 0.00 | 0.00 | 0.00 |
June | 620.53 | 195.61 | 424.92 | 1679.79 | 12.96 | 0.00 | 0.00 | 0.00 |
July | 569.27 | 162.86 | 406.41 | 1784.76 | 0.29 | 0.00 | 0.00 | 0.00 |
August | 584.01 | 177.56 | 406.45 | 1840.36 | 0.09 | 0.00 | 0.00 | 0.00 |
September | 555.54 | 174.54 | 381.01 | 1508.81 | 20.00 | 0.00 | 0.00 | 0.00 |
October | 493.72 | 159.48 | 334.23 | 1169.47 | 84.13 | 0.00 | 0.00 | 0.00 |
November | 424.29 | 138.76 | 285.53 | 845.68 | 218.68 | 0.00 | 0.00 | 0.00 |
December | 355.19 | 107.37 | 247.83 | 572.15 | 379.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 505.19 | 152.53 | 352.66 | 1186.69 | 174.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 355.19 | 107.19 | 247.83 | 540.23 | 0.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 620.53 | 195.61 | 424.92 | 1840.36 | 458.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.18 | 0.00 | 105.18 | 115.73 | 257.74 | 0.00 | 0.00 | 0.00 |
February | 120.56 | 0.00 | 120.56 | 165.18 | 209.11 | 0.00 | 0.00 | 0.00 |
March | 138.48 | 0.00 | 138.48 | 242.51 | 152.79 | 0.00 | 0.00 | 0.00 |
April | 156.03 | 0.32 | 155.70 | 353.53 | 92.17 | 0.00 | 0.00 | 0.00 |
May | 175.62 | 5.15 | 170.47 | 534.27 | 22.61 | 0.00 | 0.00 | 0.00 |
June | 188.04 | 10.44 | 177.60 | 615.14 | 5.73 | 0.00 | 0.00 | 0.00 |
July | 172.54 | 4.97 | 167.57 | 685.74 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 160.62 | 1.33 | 159.29 | 671.42 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 146.31 | 0.02 | 146.29 | 501.57 | 10.36 | 0.00 | 0.00 | 0.00 |
October | 129.70 | 0.00 | 129.70 | 356.04 | 45.45 | 0.00 | 0.00 | 0.00 |
November | 111.35 | 0.00 | 111.35 | 223.45 | 122.15 | 0.00 | 0.00 | 0.00 |
December | 98.17 | 0.00 | 98.17 | 130.00 | 214.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.96 | 1.86 | 140.11 | 384.23 | 93.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.17 | 0.00 | 98.17 | 115.73 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.04 | 10.44 | 177.60 | 685.74 | 257.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.18 | 0.00 | 105.18 | 115.74 | 257.76 | 0.00 | 0.00 | 0.00 |
February | 120.57 | 0.00 | 120.57 | 165.18 | 209.13 | 0.00 | 0.00 | 0.00 |
March | 138.49 | 0.00 | 138.49 | 242.52 | 152.80 | 0.00 | 0.00 | 0.00 |
April | 156.03 | 0.32 | 155.71 | 353.55 | 92.18 | 0.00 | 0.00 | 0.00 |
May | 175.63 | 5.15 | 170.48 | 534.29 | 22.61 | 0.00 | 0.00 | 0.00 |
June | 188.04 | 10.44 | 177.60 | 615.17 | 5.73 | 0.00 | 0.00 | 0.00 |
July | 172.55 | 4.97 | 167.58 | 685.78 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 160.63 | 1.33 | 159.30 | 671.46 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 146.32 | 0.02 | 146.30 | 501.60 | 10.37 | 0.00 | 0.00 | 0.00 |
October | 129.71 | 0.00 | 129.71 | 356.06 | 45.45 | 0.00 | 0.00 | 0.00 |
November | 111.35 | 0.00 | 111.35 | 223.46 | 122.16 | 0.00 | 0.00 | 0.00 |
December | 98.17 | 0.00 | 98.17 | 130.00 | 214.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.97 | 1.86 | 140.11 | 384.25 | 93.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.17 | 0.00 | 98.17 | 115.74 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.04 | 10.44 | 177.60 | 685.78 | 257.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.18 | 0.00 | 105.18 | 115.74 | 257.76 | 0.00 | 0.00 | 0.00 |
February | 120.57 | 0.00 | 120.57 | 165.18 | 209.13 | 0.00 | 0.00 | 0.00 |
March | 138.49 | 0.00 | 138.49 | 242.52 | 152.80 | 0.00 | 0.00 | 0.00 |
April | 156.03 | 0.32 | 155.71 | 353.55 | 92.18 | 0.00 | 0.00 | 0.00 |
May | 175.63 | 5.15 | 170.48 | 534.29 | 22.61 | 0.00 | 0.00 | 0.00 |
June | 188.04 | 10.44 | 177.60 | 615.17 | 5.73 | 0.00 | 0.00 | 0.00 |
July | 172.55 | 4.97 | 167.58 | 685.78 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 160.63 | 1.33 | 159.30 | 671.46 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 146.32 | 0.02 | 146.30 | 501.60 | 10.37 | 0.00 | 0.00 | 0.00 |
October | 129.71 | 0.00 | 129.71 | 356.06 | 45.45 | 0.00 | 0.00 | 0.00 |
November | 111.35 | 0.00 | 111.35 | 223.46 | 122.16 | 0.00 | 0.00 | 0.00 |
December | 98.17 | 0.00 | 98.17 | 130.00 | 214.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.97 | 1.86 | 140.11 | 384.25 | 93.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.17 | 0.00 | 98.17 | 115.74 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.04 | 10.44 | 177.60 | 685.78 | 257.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 366.07 | 110.75 | 255.32 | 491.89 | 468.89 | 0.00 | 0.00 | 0.00 |
February | 398.93 | 108.11 | 290.82 | 606.90 | 385.92 | 0.00 | 0.00 | 0.00 |
March | 440.66 | 108.61 | 332.05 | 783.36 | 285.52 | 0.00 | 0.00 | 0.00 |
April | 536.52 | 156.32 | 380.20 | 1123.71 | 176.91 | 0.00 | 0.00 | 0.00 |
May | 599.58 | 191.03 | 408.55 | 1516.36 | 44.59 | 0.00 | 0.00 | 0.00 |
June | 587.19 | 179.57 | 407.62 | 1597.94 | 11.11 | 0.00 | 0.00 | 0.00 |
July | 548.05 | 158.00 | 390.05 | 1723.58 | 0.31 | 0.00 | 0.00 | 0.00 |
August | 561.20 | 172.24 | 388.96 | 1771.53 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 527.59 | 163.07 | 364.52 | 1430.35 | 19.58 | 0.00 | 0.00 | 0.00 |
October | 478.74 | 156.40 | 322.33 | 1115.76 | 85.82 | 0.00 | 0.00 | 0.00 |
November | 401.18 | 127.07 | 274.11 | 769.12 | 227.62 | 0.00 | 0.00 | 0.00 |
December | 324.72 | 89.09 | 235.63 | 480.82 | 393.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 481.19 | 143.50 | 337.69 | 1120.57 | 173.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 324.72 | 89.09 | 235.63 | 480.82 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 599.58 | 191.03 | 408.55 | 1771.53 | 468.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.47 | 4.38 | 10.09 | 19.45 | 18.54 | 0.00 | 0.00 | 0.00 |
February | 15.77 | 4.27 | 11.50 | 24.00 | 15.26 | 0.00 | 0.00 | 0.00 |
March | 17.42 | 4.29 | 13.13 | 30.97 | 11.29 | 0.00 | 0.00 | 0.00 |
April | 21.21 | 6.18 | 15.03 | 44.43 | 6.99 | 0.00 | 0.00 | 0.00 |
May | 23.71 | 7.55 | 16.15 | 59.96 | 1.76 | 0.00 | 0.00 | 0.00 |
June | 23.22 | 7.10 | 16.12 | 63.18 | 0.44 | 0.00 | 0.00 | 0.00 |
July | 21.67 | 6.25 | 15.42 | 68.15 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 22.19 | 6.81 | 15.38 | 70.04 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20.86 | 6.45 | 14.41 | 56.55 | 0.77 | 0.00 | 0.00 | 0.00 |
October | 18.93 | 6.18 | 12.74 | 44.12 | 3.39 | 0.00 | 0.00 | 0.00 |
November | 15.86 | 5.02 | 10.84 | 30.41 | 9.00 | 0.00 | 0.00 | 0.00 |
December | 12.84 | 3.52 | 9.32 | 19.01 | 15.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19.03 | 5.67 | 13.35 | 44.31 | 6.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.84 | 3.52 | 9.32 | 19.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.71 | 7.55 | 16.15 | 70.04 | 18.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 339.93 | 159.82 | 180.12 | 537.95 | 252.75 | 0.00 | 0.00 | 0.00 |
February | 319.21 | 130.57 | 188.64 | 541.07 | 211.46 | 0.00 | 0.00 | 0.00 |
March | 262.73 | 71.33 | 191.40 | 500.98 | 157.88 | 0.00 | 0.00 | 0.00 |
April | 206.52 | 21.90 | 184.63 | 469.08 | 95.72 | 0.00 | 0.00 | 0.00 |
May | 174.94 | 2.68 | 172.26 | 528.75 | 23.68 | 0.00 | 0.00 | 0.00 |
June | 164.76 | 0.20 | 164.55 | 558.03 | 5.10 | 0.00 | 0.00 | 0.00 |
July | 164.75 | 1.40 | 163.35 | 658.38 | 0.10 | 0.00 | 0.00 | 0.00 |
August | 191.10 | 13.54 | 177.56 | 731.31 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 251.97 | 57.74 | 194.22 | 722.86 | 11.61 | 0.00 | 0.00 | 0.00 |
October | 329.87 | 131.14 | 198.73 | 753.41 | 49.82 | 0.00 | 0.00 | 0.00 |
November | 363.91 | 175.43 | 188.48 | 702.71 | 127.30 | 0.00 | 0.00 | 0.00 |
December | 337.82 | 166.87 | 170.95 | 569.89 | 213.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 258.60 | 77.44 | 181.16 | 606.66 | 95.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 164.75 | 0.20 | 163.35 | 469.08 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 363.91 | 175.43 | 198.73 | 753.41 | 252.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 339.93 | 159.82 | 180.12 | 537.95 | 252.75 | 0.00 | 0.00 | 0.00 |
February | 319.21 | 130.57 | 188.64 | 541.07 | 211.46 | 0.00 | 0.00 | 0.00 |
March | 262.73 | 71.33 | 191.40 | 500.98 | 157.88 | 0.00 | 0.00 | 0.00 |
April | 206.52 | 21.90 | 184.63 | 469.08 | 95.72 | 0.00 | 0.00 | 0.00 |
May | 174.94 | 2.68 | 172.26 | 528.75 | 23.68 | 0.00 | 0.00 | 0.00 |
June | 164.76 | 0.20 | 164.55 | 558.03 | 5.10 | 0.00 | 0.00 | 0.00 |
July | 164.75 | 1.40 | 163.35 | 658.38 | 0.10 | 0.00 | 0.00 | 0.00 |
August | 191.10 | 13.54 | 177.56 | 731.31 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 251.97 | 57.74 | 194.22 | 722.86 | 11.61 | 0.00 | 0.00 | 0.00 |
October | 329.87 | 131.14 | 198.73 | 753.41 | 49.82 | 0.00 | 0.00 | 0.00 |
November | 363.91 | 175.43 | 188.48 | 702.71 | 127.30 | 0.00 | 0.00 | 0.00 |
December | 337.82 | 166.87 | 170.95 | 569.89 | 213.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 258.60 | 77.44 | 181.16 | 606.66 | 95.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 164.75 | 0.20 | 163.35 | 469.08 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 363.91 | 175.43 | 198.73 | 753.41 | 252.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 339.91 | 159.81 | 180.10 | 537.92 | 252.74 | 0.00 | 0.00 | 0.00 |
February | 319.19 | 130.56 | 188.63 | 541.04 | 211.44 | 0.00 | 0.00 | 0.00 |
March | 262.71 | 71.32 | 191.39 | 500.95 | 157.87 | 0.00 | 0.00 | 0.00 |
April | 206.51 | 21.89 | 184.62 | 469.05 | 95.71 | 0.00 | 0.00 | 0.00 |
May | 174.93 | 2.68 | 172.25 | 528.72 | 23.68 | 0.00 | 0.00 | 0.00 |
June | 164.75 | 0.20 | 164.54 | 558.00 | 5.10 | 0.00 | 0.00 | 0.00 |
July | 164.74 | 1.40 | 163.34 | 658.33 | 0.10 | 0.00 | 0.00 | 0.00 |
August | 191.09 | 13.54 | 177.55 | 731.26 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 251.95 | 57.74 | 194.21 | 722.81 | 11.61 | 0.00 | 0.00 | 0.00 |
October | 329.85 | 131.13 | 198.72 | 753.37 | 49.82 | 0.00 | 0.00 | 0.00 |
November | 363.89 | 175.42 | 188.47 | 702.66 | 127.29 | 0.00 | 0.00 | 0.00 |
December | 337.80 | 166.86 | 170.94 | 569.85 | 213.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 258.58 | 77.43 | 181.15 | 606.62 | 95.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 164.74 | 0.20 | 163.34 | 469.05 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 363.89 | 175.42 | 198.72 | 753.37 | 252.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 359.00 | 103.11 | 255.89 | 510.74 | 504.84 | 0.00 | 0.00 | 0.00 |
February | 409.94 | 116.90 | 293.04 | 651.47 | 412.05 | 0.00 | 0.00 | 0.00 |
March | 485.58 | 143.76 | 341.83 | 881.25 | 307.84 | 0.00 | 0.00 | 0.00 |
April | 530.66 | 149.09 | 381.57 | 1118.43 | 193.56 | 0.00 | 0.00 | 0.00 |
May | 577.62 | 172.90 | 404.72 | 1480.51 | 52.42 | 0.00 | 0.00 | 0.00 |
June | 596.92 | 188.17 | 408.76 | 1619.73 | 13.25 | 0.00 | 0.00 | 0.00 |
July | 547.61 | 156.66 | 390.95 | 1717.90 | 0.39 | 0.00 | 0.00 | 0.00 |
August | 561.79 | 170.81 | 390.98 | 1761.99 | 0.12 | 0.00 | 0.00 | 0.00 |
September | 534.41 | 167.89 | 366.51 | 1441.84 | 23.92 | 0.00 | 0.00 | 0.00 |
October | 474.93 | 153.42 | 321.52 | 1115.46 | 98.19 | 0.00 | 0.00 | 0.00 |
November | 408.14 | 133.48 | 274.67 | 804.35 | 248.73 | 0.00 | 0.00 | 0.00 |
December | 341.68 | 103.28 | 238.40 | 541.04 | 421.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 485.96 | 146.72 | 339.24 | 1139.86 | 188.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 341.68 | 103.11 | 238.40 | 510.74 | 0.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 596.92 | 188.17 | 408.76 | 1761.99 | 504.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.19 | 4.08 | 10.12 | 20.19 | 19.96 | 0.00 | 0.00 | 0.00 |
February | 16.21 | 4.62 | 11.59 | 25.76 | 16.29 | 0.00 | 0.00 | 0.00 |
March | 19.20 | 5.68 | 13.52 | 34.84 | 12.17 | 0.00 | 0.00 | 0.00 |
April | 20.98 | 5.89 | 15.09 | 44.22 | 7.65 | 0.00 | 0.00 | 0.00 |
May | 22.84 | 6.84 | 16.00 | 58.54 | 2.07 | 0.00 | 0.00 | 0.00 |
June | 23.60 | 7.44 | 16.16 | 64.04 | 0.52 | 0.00 | 0.00 | 0.00 |
July | 21.65 | 6.19 | 15.46 | 67.92 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 22.21 | 6.75 | 15.46 | 69.67 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21.13 | 6.64 | 14.49 | 57.01 | 0.95 | 0.00 | 0.00 | 0.00 |
October | 18.78 | 6.07 | 12.71 | 44.10 | 3.88 | 0.00 | 0.00 | 0.00 |
November | 16.14 | 5.28 | 10.86 | 31.80 | 9.83 | 0.00 | 0.00 | 0.00 |
December | 13.51 | 4.08 | 9.43 | 21.39 | 16.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19.21 | 5.80 | 13.41 | 45.07 | 7.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.51 | 4.08 | 9.43 | 20.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.60 | 7.44 | 16.16 | 69.67 | 19.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 315.55 | 0.00 | 315.55 | 354.00 | 734.99 | 0.00 | 0.00 | 0.00 |
February | 361.71 | 0.00 | 361.71 | 495.64 | 610.49 | 0.00 | 0.00 | 0.00 |
March | 415.47 | 0.00 | 415.47 | 720.75 | 461.12 | 0.00 | 0.00 | 0.00 |
April | 468.10 | 0.96 | 467.13 | 1050.66 | 286.78 | 0.00 | 0.00 | 0.00 |
May | 526.89 | 15.45 | 511.43 | 1599.98 | 71.90 | 0.00 | 0.00 | 0.00 |
June | 564.13 | 31.32 | 532.81 | 1850.99 | 17.97 | 0.00 | 0.00 | 0.00 |
July | 517.65 | 14.91 | 502.73 | 2072.56 | 0.42 | 0.00 | 0.00 | 0.00 |
August | 481.88 | 3.99 | 477.90 | 2042.87 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 438.95 | 0.05 | 438.90 | 1531.79 | 26.92 | 0.00 | 0.00 | 0.00 |
October | 389.12 | 0.00 | 389.12 | 1093.64 | 121.16 | 0.00 | 0.00 | 0.00 |
November | 334.05 | 0.00 | 334.05 | 689.21 | 335.29 | 0.00 | 0.00 | 0.00 |
December | 294.52 | 0.00 | 294.52 | 401.19 | 599.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 425.91 | 5.58 | 420.34 | 1162.72 | 270.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 294.52 | 0.00 | 294.52 | 354.00 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 564.13 | 31.32 | 532.81 | 2072.56 | 734.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 380.55 | 115.13 | 265.41 | 513.25 | 459.68 | 0.00 | 0.00 | 0.00 |
February | 414.71 | 112.39 | 302.32 | 626.83 | 386.08 | 0.00 | 0.00 | 0.00 |
March | 458.09 | 112.90 | 345.19 | 804.78 | 294.29 | 0.00 | 0.00 | 0.00 |
April | 557.74 | 162.51 | 395.23 | 1156.66 | 185.28 | 0.00 | 0.00 | 0.00 |
May | 623.29 | 198.58 | 424.71 | 1570.64 | 46.19 | 0.00 | 0.00 | 0.00 |
June | 610.42 | 186.67 | 423.75 | 1660.71 | 10.92 | 0.00 | 0.00 | 0.00 |
July | 569.73 | 164.25 | 405.48 | 1798.77 | 0.23 | 0.00 | 0.00 | 0.00 |
August | 583.40 | 179.05 | 404.34 | 1857.52 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 548.46 | 169.52 | 378.94 | 1501.24 | 16.33 | 0.00 | 0.00 | 0.00 |
October | 497.67 | 162.59 | 335.08 | 1171.24 | 75.21 | 0.00 | 0.00 | 0.00 |
November | 417.05 | 132.10 | 284.95 | 807.25 | 212.19 | 0.00 | 0.00 | 0.00 |
December | 337.56 | 92.61 | 244.95 | 504.34 | 379.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 500.22 | 149.18 | 351.04 | 1167.57 | 171.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 337.56 | 92.61 | 244.95 | 504.34 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 623.29 | 198.58 | 424.71 | 1857.52 | 459.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1019.82 | 479.46 | 540.35 | 1610.76 | 711.19 | 0.00 | 0.00 | 0.00 |
February | 957.65 | 391.72 | 565.93 | 1614.65 | 605.63 | 0.00 | 0.00 | 0.00 |
March | 788.19 | 213.99 | 574.20 | 1492.82 | 469.53 | 0.00 | 0.00 | 0.00 |
April | 619.58 | 65.69 | 553.89 | 1398.92 | 293.60 | 0.00 | 0.00 | 0.00 |
May | 524.83 | 8.04 | 516.80 | 1595.80 | 72.97 | 0.00 | 0.00 | 0.00 |
June | 494.27 | 0.61 | 493.66 | 1698.11 | 14.74 | 0.00 | 0.00 | 0.00 |
July | 494.26 | 4.20 | 490.06 | 2010.44 | 0.23 | 0.00 | 0.00 | 0.00 |
August | 573.30 | 40.62 | 532.68 | 2250.76 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 755.91 | 173.24 | 582.67 | 2215.28 | 26.95 | 0.00 | 0.00 | 0.00 |
October | 989.63 | 393.43 | 596.20 | 2293.09 | 121.02 | 0.00 | 0.00 | 0.00 |
November | 1091.76 | 526.31 | 565.45 | 2122.30 | 334.30 | 0.00 | 0.00 | 0.00 |
December | 1013.48 | 500.63 | 512.85 | 1711.48 | 590.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 775.80 | 232.32 | 543.49 | 1836.08 | 268.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 494.26 | 0.61 | 490.06 | 1398.92 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1091.76 | 526.31 | 596.20 | 2293.09 | 711.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 373.20 | 107.19 | 266.01 | 533.96 | 493.58 | 0.00 | 0.00 | 0.00 |
February | 426.15 | 121.52 | 304.63 | 675.52 | 410.89 | 0.00 | 0.00 | 0.00 |
March | 504.79 | 149.44 | 355.35 | 909.54 | 315.25 | 0.00 | 0.00 | 0.00 |
April | 551.65 | 154.98 | 396.67 | 1154.77 | 202.15 | 0.00 | 0.00 | 0.00 |
May | 600.47 | 179.74 | 420.72 | 1538.21 | 54.03 | 0.00 | 0.00 | 0.00 |
June | 620.53 | 195.61 | 424.92 | 1689.89 | 12.63 | 0.00 | 0.00 | 0.00 |
July | 569.27 | 162.86 | 406.41 | 1797.98 | 0.26 | 0.00 | 0.00 | 0.00 |
August | 584.01 | 177.56 | 406.45 | 1852.25 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 555.54 | 174.54 | 381.01 | 1517.19 | 20.06 | 0.00 | 0.00 | 0.00 |
October | 493.72 | 159.48 | 334.23 | 1174.67 | 87.06 | 0.00 | 0.00 | 0.00 |
November | 424.29 | 138.76 | 285.53 | 846.47 | 231.58 | 0.00 | 0.00 | 0.00 |
December | 355.19 | 107.37 | 247.83 | 568.13 | 405.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 505.19 | 152.53 | 352.66 | 1191.18 | 185.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 355.19 | 107.19 | 247.83 | 533.96 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 620.53 | 195.61 | 424.92 | 1852.25 | 493.58 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.845162E+09 | 0.00 | 0.845162E+09 | 0.979684E+09 | 0.182377E+10 |
February | 0.875042E+09 | 0.00 | 0.875042E+09 | 0.121461E+10 | 0.138312E+10 |
March | 0.111279E+10 | 0.00 | 0.111279E+10 | 0.193079E+10 | 0.117057E+10 |
April | 0.121331E+10 | 2499967.15 | 0.121081E+10 | 0.270629E+10 | 0.717585E+09 |
May | 0.141121E+10 | 41390031.38 | 0.136982E+10 | 0.425135E+10 | 0.191421E+09 |
June | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.476113E+10 | 48317070.86 |
July | 0.138646E+10 | 39947373.00 | 0.134652E+10 | 0.550084E+10 | 1225411.27 |
August | 0.129068E+10 | 10675196.26 | 0.128000E+10 | 0.542891E+10 | 240874.21 |
September | 0.113776E+10 | 130377.42 | 0.113763E+10 | 0.394177E+10 | 69307695.62 |
October | 0.104222E+10 | 0.00 | 0.104222E+10 | 0.291319E+10 | 0.312566E+09 |
November | 0.865865E+09 | 0.00 | 0.865865E+09 | 0.178843E+10 | 0.818503E+09 |
December | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.109687E+10 | 0.149521E+10 |
Annual Sum or Average | 0.134316E+11 | 0.175822E+09 | 0.132558E+11 | 0.365139E+11 | 0.803184E+10 |
Minimum of Months | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.979684E+09 | 240874.21 |
Maximum of Months | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.550084E+10 | 0.182377E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101926E+10 | 0.308376E+09 | 0.710884E+09 | 0.141111E+10 | 0.115091E+10 |
February | 0.100327E+10 | 0.271890E+09 | 0.731376E+09 | 0.153842E+10 | 0.880223E+09 |
March | 0.122695E+10 | 0.302398E+09 | 0.924550E+09 | 0.216798E+10 | 0.749827E+09 |
April | 0.144567E+10 | 0.421221E+09 | 0.102445E+10 | 0.299718E+10 | 0.464121E+09 |
May | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.419319E+10 | 0.122151E+09 |
June | 0.158221E+10 | 0.483857E+09 | 0.109835E+10 | 0.428987E+10 | 28891175.24 |
July | 0.152597E+10 | 0.439934E+09 | 0.108604E+10 | 0.479469E+10 | 674978.22 |
August | 0.156257E+10 | 0.479573E+09 | 0.108299E+10 | 0.495737E+10 | 99172.84 |
September | 0.142161E+10 | 0.439402E+09 | 0.982206E+09 | 0.388116E+10 | 41599938.37 |
October | 0.133297E+10 | 0.435481E+09 | 0.897486E+09 | 0.313485E+10 | 0.193027E+09 |
November | 0.108100E+10 | 0.342405E+09 | 0.738593E+09 | 0.210382E+10 | 0.519938E+09 |
December | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.137884E+10 | 0.952693E+09 |
Annual Sum or Average | 0.157750E+11 | 0.470448E+10 | 0.110705E+11 | 0.368485E+11 | 0.510416E+10 |
Minimum of Months | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.137884E+10 | 99172.84 |
Maximum of Months | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.495737E+10 | 0.115091E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273147E+10 | 0.128419E+10 | 0.144728E+10 | 0.434213E+10 | 0.178485E+10 |
February | 0.231675E+10 | 0.947651E+09 | 0.136910E+10 | 0.391505E+10 | 0.138193E+10 |
March | 0.211109E+10 | 0.573148E+09 | 0.153794E+10 | 0.399303E+10 | 0.119588E+10 |
April | 0.160594E+10 | 0.170260E+09 | 0.143568E+10 | 0.360674E+10 | 0.734502E+09 |
May | 0.140572E+10 | 21527140.62 | 0.138419E+10 | 0.423855E+10 | 0.192971E+09 |
June | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.436509E+10 | 39049487.05 |
July | 0.132383E+10 | 11248476.20 | 0.131258E+10 | 0.533258E+10 | 652313.63 |
August | 0.153553E+10 | 0.108799E+09 | 0.142673E+10 | 0.598317E+10 | 141556.22 |
September | 0.195931E+10 | 0.449032E+09 | 0.151027E+10 | 0.570776E+10 | 69129032.68 |
October | 0.265062E+10 | 0.105377E+10 | 0.159685E+10 | 0.611705E+10 | 0.312685E+09 |
November | 0.282984E+10 | 0.136420E+10 | 0.146565E+10 | 0.549579E+10 | 0.821654E+09 |
December | 0.271452E+10 | 0.134089E+10 | 0.137363E+10 | 0.460124E+10 | 0.149051E+10 |
Annual Sum or Average | 0.244658E+11 | 0.732630E+10 | 0.171395E+11 | 0.576982E+11 | 0.802396E+10 |
Minimum of Months | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.360674E+10 | 141556.22 |
Maximum of Months | 0.282984E+10 | 0.136420E+10 | 0.159685E+10 | 0.611705E+10 | 0.178485E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.999569E+09 | 0.287085E+09 | 0.712484E+09 | 0.144696E+10 | 0.122840E+10 |
February | 0.103095E+10 | 0.293985E+09 | 0.736963E+09 | 0.164073E+10 | 0.933365E+09 |
March | 0.135203E+10 | 0.400272E+09 | 0.951758E+09 | 0.243173E+10 | 0.802115E+09 |
April | 0.142987E+10 | 0.401718E+09 | 0.102816E+10 | 0.297872E+10 | 0.506179E+09 |
May | 0.160829E+10 | 0.481426E+09 | 0.112687E+10 | 0.409432E+10 | 0.143315E+09 |
June | 0.160842E+10 | 0.507017E+09 | 0.110140E+10 | 0.435402E+10 | 33587281.63 |
July | 0.152474E+10 | 0.436197E+09 | 0.108854E+10 | 0.478029E+10 | 784398.03 |
August | 0.156421E+10 | 0.475587E+09 | 0.108862E+10 | 0.492923E+10 | 238983.73 |
September | 0.143997E+10 | 0.452397E+09 | 0.987572E+09 | 0.391083E+10 | 51838292.69 |
October | 0.132237E+10 | 0.427161E+09 | 0.895206E+09 | 0.313231E+10 | 0.225346E+09 |
November | 0.109975E+10 | 0.359654E+09 | 0.740098E+09 | 0.219200E+10 | 0.566815E+09 |
December | 0.951354E+09 | 0.287577E+09 | 0.663776E+09 | 0.153244E+10 | 0.101579E+10 |
Annual Sum or Average | 0.159315E+11 | 0.481008E+10 | 0.111214E+11 | 0.374236E+11 | 0.550778E+10 |
Minimum of Months | 0.951354E+09 | 0.287085E+09 | 0.663776E+09 | 0.144696E+10 | 238983.73 |
Maximum of Months | 0.160842E+10 | 0.507017E+09 | 0.112687E+10 | 0.492923E+10 | 0.122840E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.281707E+09 | 0.00 | 0.281707E+09 | 0.309980E+09 | 0.690339E+09 |
February | 0.291667E+09 | 0.00 | 0.291667E+09 | 0.399592E+09 | 0.505889E+09 |
March | 0.370914E+09 | 0.00 | 0.370914E+09 | 0.649543E+09 | 0.409238E+09 |
April | 0.404418E+09 | 833282.96 | 0.403585E+09 | 0.916354E+09 | 0.238917E+09 |
May | 0.470382E+09 | 13796024.38 | 0.456586E+09 | 0.143098E+10 | 60562331.02 |
June | 0.487387E+09 | 27058259.84 | 0.460329E+09 | 0.159444E+10 | 14862470.64 |
July | 0.462133E+09 | 13315161.00 | 0.448818E+09 | 0.183669E+10 | 404194.87 |
August | 0.430206E+09 | 3558230.40 | 0.426648E+09 | 0.179834E+10 | 73421.09 |
September | 0.379237E+09 | 43457.08 | 0.379193E+09 | 0.130008E+10 | 26865865.55 |
October | 0.347392E+09 | 0.00 | 0.347392E+09 | 0.953625E+09 | 0.121727E+09 |
November | 0.288608E+09 | 0.00 | 0.288608E+09 | 0.579171E+09 | 0.316615E+09 |
December | 0.262937E+09 | 0.00 | 0.262937E+09 | 0.348181E+09 | 0.573485E+09 |
Annual Sum or Average | 0.447699E+10 | 58604415.66 | 0.441838E+10 | 0.121170E+11 | 0.295898E+10 |
Minimum of Months | 0.262937E+09 | 0.00 | 0.262937E+09 | 0.309980E+09 | 73421.09 |
Maximum of Months | 0.487387E+09 | 27058259.84 | 0.460329E+09 | 0.183669E+10 | 0.690339E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.281718E+09 | 0.00 | 0.281718E+09 | 0.309990E+09 | 0.690377E+09 |
February | 0.291678E+09 | 0.00 | 0.291678E+09 | 0.399608E+09 | 0.505916E+09 |
March | 0.370928E+09 | 0.00 | 0.370928E+09 | 0.649571E+09 | 0.409259E+09 |
April | 0.404434E+09 | 833305.35 | 0.403601E+09 | 0.916398E+09 | 0.238927E+09 |
May | 0.470401E+09 | 13796395.22 | 0.456604E+09 | 0.143105E+10 | 60563600.08 |
June | 0.487406E+09 | 27058987.17 | 0.460347E+09 | 0.159453E+10 | 14862105.35 |
July | 0.462151E+09 | 13315518.92 | 0.448835E+09 | 0.183680E+10 | 404155.14 |
August | 0.430223E+09 | 3558326.05 | 0.426665E+09 | 0.179845E+10 | 73397.32 |
September | 0.379252E+09 | 43458.25 | 0.379209E+09 | 0.130016E+10 | 26866092.20 |
October | 0.347405E+09 | 0.00 | 0.347405E+09 | 0.953677E+09 | 0.121730E+09 |
November | 0.288619E+09 | 0.00 | 0.288619E+09 | 0.579199E+09 | 0.316629E+09 |
December | 0.262947E+09 | 0.00 | 0.262947E+09 | 0.348194E+09 | 0.573515E+09 |
Annual Sum or Average | 0.447716E+10 | 58605990.96 | 0.441856E+10 | 0.121176E+11 | 0.295912E+10 |
Minimum of Months | 0.262947E+09 | 0.00 | 0.262947E+09 | 0.309990E+09 | 73397.32 |
Maximum of Months | 0.487406E+09 | 27058987.17 | 0.460347E+09 | 0.183680E+10 | 0.690377E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.281718E+09 | 0.00 | 0.281718E+09 | 0.309990E+09 | 0.690377E+09 |
February | 0.291678E+09 | 0.00 | 0.291678E+09 | 0.399608E+09 | 0.505916E+09 |
March | 0.370928E+09 | 0.00 | 0.370928E+09 | 0.649571E+09 | 0.409259E+09 |
April | 0.404434E+09 | 833305.35 | 0.403601E+09 | 0.916398E+09 | 0.238927E+09 |
May | 0.470401E+09 | 13796395.22 | 0.456604E+09 | 0.143105E+10 | 60563600.08 |
June | 0.487406E+09 | 27058987.17 | 0.460347E+09 | 0.159453E+10 | 14862105.35 |
July | 0.462151E+09 | 13315518.92 | 0.448835E+09 | 0.183680E+10 | 404155.14 |
August | 0.430223E+09 | 3558326.05 | 0.426665E+09 | 0.179845E+10 | 73397.32 |
September | 0.379252E+09 | 43458.25 | 0.379209E+09 | 0.130016E+10 | 26866092.20 |
October | 0.347405E+09 | 0.00 | 0.347405E+09 | 0.953677E+09 | 0.121730E+09 |
November | 0.288619E+09 | 0.00 | 0.288619E+09 | 0.579199E+09 | 0.316629E+09 |
December | 0.262947E+09 | 0.00 | 0.262947E+09 | 0.348194E+09 | 0.573515E+09 |
Annual Sum or Average | 0.447716E+10 | 58605990.96 | 0.441856E+10 | 0.121176E+11 | 0.295912E+10 |
Minimum of Months | 0.262947E+09 | 0.00 | 0.262947E+09 | 0.309990E+09 | 73397.32 |
Maximum of Months | 0.487406E+09 | 27058987.17 | 0.460347E+09 | 0.183680E+10 | 0.690377E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.980477E+09 | 0.296641E+09 | 0.683836E+09 | 0.131747E+10 | 0.125587E+10 |
February | 0.965092E+09 | 0.261544E+09 | 0.703548E+09 | 0.146822E+10 | 0.933627E+09 |
March | 0.118026E+10 | 0.290890E+09 | 0.889372E+09 | 0.209816E+10 | 0.764731E+09 |
April | 0.139066E+10 | 0.405192E+09 | 0.985471E+09 | 0.291265E+10 | 0.458555E+09 |
May | 0.160591E+10 | 0.511648E+09 | 0.109426E+10 | 0.406142E+10 | 0.119430E+09 |
June | 0.152201E+10 | 0.465444E+09 | 0.105656E+10 | 0.414187E+10 | 28801120.84 |
July | 0.146791E+10 | 0.423193E+09 | 0.104472E+10 | 0.461645E+10 | 834608.23 |
August | 0.150311E+10 | 0.461324E+09 | 0.104179E+10 | 0.474487E+10 | 154855.48 |
September | 0.136752E+10 | 0.422681E+09 | 0.944836E+09 | 0.370748E+10 | 50761771.32 |
October | 0.128225E+10 | 0.418909E+09 | 0.863339E+09 | 0.298846E+10 | 0.229865E+09 |
November | 0.103987E+10 | 0.329375E+09 | 0.710490E+09 | 0.199355E+10 | 0.589992E+09 |
December | 0.869726E+09 | 0.238617E+09 | 0.631110E+09 | 0.128783E+10 | 0.105286E+10 |
Annual Sum or Average | 0.151748E+11 | 0.452546E+10 | 0.106493E+11 | 0.353384E+11 | 0.548548E+10 |
Minimum of Months | 0.869726E+09 | 0.238617E+09 | 0.631110E+09 | 0.128783E+10 | 154855.48 |
Maximum of Months | 0.160591E+10 | 0.511648E+09 | 0.109426E+10 | 0.474487E+10 | 0.125587E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38767169.86 | 11728917.87 | 27038251.99 | 52091720.41 | 49655791.98 |
February | 38158864.13 | 10341197.48 | 27817666.66 | 58052272.58 | 36914775.28 |
March | 46666517.65 | 11501534.46 | 35164983.19 | 82959199.03 | 30236792.20 |
April | 54985543.05 | 16020907.39 | 38964635.67 | 0.115164E+09 | 18130858.85 |
May | 63496079.79 | 20230091.31 | 43265988.49 | 0.160585E+09 | 4722158.38 |
June | 60178723.78 | 18403232.06 | 41775491.72 | 0.163766E+09 | 1138770.39 |
July | 58039777.31 | 16732677.45 | 41307099.86 | 0.182530E+09 | 32999.66 |
August | 59431730.36 | 18240318.79 | 41191411.57 | 0.187608E+09 | 6122.85 |
September | 54070390.91 | 16712442.13 | 37357948.79 | 0.146590E+09 | 2007074.74 |
October | 50698923.30 | 16563295.94 | 34135627.36 | 0.118161E+09 | 9088648.30 |
November | 41115338.64 | 13023186.67 | 28092151.97 | 78823283.33 | 23327768.42 |
December | 34388199.46 | 9434693.58 | 24953505.89 | 50919648.92 | 41629293.14 |
Annual Sum or Average | 0.599997E+09 | 0.178932E+09 | 0.421065E+09 | 0.139725E+10 | 0.216891E+09 |
Minimum of Months | 34388199.46 | 9434693.58 | 24953505.89 | 50919648.92 | 6122.85 |
Maximum of Months | 63496079.79 | 20230091.31 | 43265988.49 | 0.187608E+09 | 49655791.98 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.910476E+09 | 0.428054E+09 | 0.482421E+09 | 0.144086E+10 | 0.676975E+09 |
February | 0.772236E+09 | 0.315877E+09 | 0.456359E+09 | 0.130897E+10 | 0.511559E+09 |
March | 0.703685E+09 | 0.191046E+09 | 0.512640E+09 | 0.134182E+10 | 0.422874E+09 |
April | 0.535307E+09 | 56752191.30 | 0.478555E+09 | 0.121586E+10 | 0.248097E+09 |
May | 0.468568E+09 | 7175566.92 | 0.461393E+09 | 0.141621E+10 | 63435383.82 |
June | 0.427049E+09 | 528482.05 | 0.426520E+09 | 0.144642E+10 | 13213277.50 |
July | 0.441272E+09 | 3749415.45 | 0.437522E+09 | 0.176339E+10 | 264574.02 |
August | 0.511839E+09 | 36265474.26 | 0.475574E+09 | 0.195874E+10 | 103052.67 |
September | 0.653094E+09 | 0.149674E+09 | 0.503419E+09 | 0.187365E+10 | 30097875.95 |
October | 0.883526E+09 | 0.351250E+09 | 0.532276E+09 | 0.201794E+10 | 0.133441E+09 |
November | 0.943266E+09 | 0.454723E+09 | 0.488543E+09 | 0.182141E+10 | 0.329958E+09 |
December | 0.904824E+09 | 0.446954E+09 | 0.457870E+09 | 0.152639E+10 | 0.573122E+09 |
Annual Sum or Average | 0.815514E+10 | 0.244205E+10 | 0.571309E+10 | 0.191317E+11 | 0.300314E+10 |
Minimum of Months | 0.427049E+09 | 528482.05 | 0.426520E+09 | 0.121586E+10 | 103052.67 |
Maximum of Months | 0.943266E+09 | 0.454723E+09 | 0.532276E+09 | 0.201794E+10 | 0.676975E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.910476E+09 | 0.428054E+09 | 0.482421E+09 | 0.144086E+10 | 0.676975E+09 |
February | 0.772236E+09 | 0.315877E+09 | 0.456359E+09 | 0.130897E+10 | 0.511559E+09 |
March | 0.703685E+09 | 0.191046E+09 | 0.512640E+09 | 0.134182E+10 | 0.422874E+09 |
April | 0.535307E+09 | 56752191.30 | 0.478555E+09 | 0.121586E+10 | 0.248097E+09 |
May | 0.468568E+09 | 7175566.92 | 0.461393E+09 | 0.141621E+10 | 63435383.82 |
June | 0.427049E+09 | 528482.05 | 0.426520E+09 | 0.144642E+10 | 13213277.50 |
July | 0.441272E+09 | 3749415.45 | 0.437522E+09 | 0.176339E+10 | 264574.02 |
August | 0.511839E+09 | 36265474.26 | 0.475574E+09 | 0.195874E+10 | 103052.67 |
September | 0.653094E+09 | 0.149674E+09 | 0.503419E+09 | 0.187365E+10 | 30097875.95 |
October | 0.883526E+09 | 0.351250E+09 | 0.532276E+09 | 0.201794E+10 | 0.133441E+09 |
November | 0.943266E+09 | 0.454723E+09 | 0.488543E+09 | 0.182141E+10 | 0.329958E+09 |
December | 0.904824E+09 | 0.446954E+09 | 0.457870E+09 | 0.152639E+10 | 0.573122E+09 |
Annual Sum or Average | 0.815514E+10 | 0.244205E+10 | 0.571309E+10 | 0.191317E+11 | 0.300314E+10 |
Minimum of Months | 0.427049E+09 | 528482.05 | 0.426520E+09 | 0.121586E+10 | 103052.67 |
Maximum of Months | 0.943266E+09 | 0.454723E+09 | 0.532276E+09 | 0.201794E+10 | 0.676975E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.910418E+09 | 0.428027E+09 | 0.482391E+09 | 0.144077E+10 | 0.676932E+09 |
February | 0.772188E+09 | 0.315857E+09 | 0.456330E+09 | 0.130889E+10 | 0.511526E+09 |
March | 0.703641E+09 | 0.191033E+09 | 0.512607E+09 | 0.134174E+10 | 0.422848E+09 |
April | 0.535274E+09 | 56748604.88 | 0.478525E+09 | 0.121578E+10 | 0.248081E+09 |
May | 0.468539E+09 | 7175113.46 | 0.461363E+09 | 0.141612E+10 | 63431375.06 |
June | 0.427022E+09 | 528448.65 | 0.426494E+09 | 0.144633E+10 | 13212442.50 |
July | 0.441244E+09 | 3749178.51 | 0.437495E+09 | 0.176328E+10 | 264557.30 |
August | 0.511807E+09 | 36263182.48 | 0.475544E+09 | 0.195861E+10 | 103046.16 |
September | 0.653053E+09 | 0.149665E+09 | 0.503388E+09 | 0.187353E+10 | 30095973.93 |
October | 0.883470E+09 | 0.351228E+09 | 0.532243E+09 | 0.201781E+10 | 0.133432E+09 |
November | 0.943206E+09 | 0.454694E+09 | 0.488512E+09 | 0.182130E+10 | 0.329937E+09 |
December | 0.904767E+09 | 0.446926E+09 | 0.457841E+09 | 0.152629E+10 | 0.573085E+09 |
Annual Sum or Average | 0.815463E+10 | 0.244189E+10 | 0.571273E+10 | 0.191304E+11 | 0.300295E+10 |
Minimum of Months | 0.427022E+09 | 528448.65 | 0.426494E+09 | 0.121578E+10 | 103046.16 |
Maximum of Months | 0.943206E+09 | 0.454694E+09 | 0.532243E+09 | 0.201781E+10 | 0.676932E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.961538E+09 | 0.276161E+09 | 0.685377E+09 | 0.136797E+10 | 0.135217E+10 |
February | 0.991722E+09 | 0.282798E+09 | 0.708924E+09 | 0.157603E+10 | 0.996837E+09 |
March | 0.130059E+10 | 0.385041E+09 | 0.915547E+09 | 0.236033E+10 | 0.824512E+09 |
April | 0.137547E+10 | 0.386432E+09 | 0.989039E+09 | 0.289898E+10 | 0.501706E+09 |
May | 0.154710E+10 | 0.463108E+09 | 0.108399E+10 | 0.396541E+10 | 0.140406E+09 |
June | 0.154723E+10 | 0.487725E+09 | 0.105950E+10 | 0.419834E+10 | 34342492.20 |
July | 0.146673E+10 | 0.419600E+09 | 0.104713E+10 | 0.460124E+10 | 1041883.83 |
August | 0.150470E+10 | 0.457491E+09 | 0.104721E+10 | 0.471932E+10 | 316657.99 |
September | 0.138518E+10 | 0.435183E+09 | 0.950000E+09 | 0.373725E+10 | 62009901.98 |
October | 0.127205E+10 | 0.410907E+09 | 0.861147E+09 | 0.298765E+10 | 0.262983E+09 |
November | 0.105791E+10 | 0.345969E+09 | 0.711940E+09 | 0.208489E+10 | 0.644718E+09 |
December | 0.915157E+09 | 0.276635E+09 | 0.638522E+09 | 0.144913E+10 | 0.112971E+10 |
Annual Sum or Average | 0.153254E+11 | 0.462705E+10 | 0.106983E+11 | 0.359465E+11 | 0.595075E+10 |
Minimum of Months | 0.915157E+09 | 0.276161E+09 | 0.638522E+09 | 0.136797E+10 | 316657.99 |
Maximum of Months | 0.154723E+10 | 0.487725E+09 | 0.108399E+10 | 0.471932E+10 | 0.135217E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38018247.76 | 10919117.73 | 27099130.02 | 54088024.14 | 53463352.74 |
February | 39211705.00 | 11181551.15 | 28030153.85 | 62314615.45 | 39414021.02 |
March | 51423957.87 | 15224122.20 | 36199835.67 | 93325069.14 | 32600441.84 |
April | 54384761.88 | 15279138.20 | 39105623.68 | 0.114623E+09 | 19836962.20 |
May | 61170809.08 | 18310794.40 | 42860014.69 | 0.156788E+09 | 5551500.30 |
June | 61175738.81 | 19284136.55 | 41891602.26 | 0.165998E+09 | 1357861.63 |
July | 57992905.15 | 16590541.44 | 41402363.71 | 0.181928E+09 | 41194.20 |
August | 59494269.60 | 18088714.83 | 41405554.77 | 0.186597E+09 | 12520.04 |
September | 54768728.67 | 17206686.11 | 37562042.56 | 0.147767E+09 | 2451803.88 |
October | 50295743.05 | 16246847.94 | 34048895.11 | 0.118129E+09 | 10398097.38 |
November | 41828685.86 | 13679270.35 | 28149415.51 | 82434350.78 | 25491509.14 |
December | 36184378.39 | 10937853.43 | 25246524.96 | 57297222.79 | 44667830.25 |
Annual Sum or Average | 0.605950E+09 | 0.182949E+09 | 0.423001E+09 | 0.142129E+10 | 0.235287E+09 |
Minimum of Months | 36184378.39 | 10919117.73 | 25246524.96 | 54088024.14 | 12520.04 |
Maximum of Months | 61175738.81 | 19284136.55 | 42860014.69 | 0.186597E+09 | 53463352.74 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.845162E+09 | 0.00 | 0.845162E+09 | 0.948156E+09 | 0.196859E+10 |
February | 0.875042E+09 | 0.00 | 0.875042E+09 | 0.119905E+10 | 0.147689E+10 |
March | 0.111279E+10 | 0.00 | 0.111279E+10 | 0.193046E+10 | 0.123507E+10 |
April | 0.121331E+10 | 2499967.15 | 0.121081E+10 | 0.272332E+10 | 0.743321E+09 |
May | 0.141121E+10 | 41390031.38 | 0.136982E+10 | 0.428540E+10 | 0.192576E+09 |
June | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.479776E+10 | 46583234.74 |
July | 0.138646E+10 | 39947373.00 | 0.134652E+10 | 0.555114E+10 | 1121931.77 |
August | 0.129068E+10 | 10675196.26 | 0.128000E+10 | 0.547164E+10 | 181970.79 |
September | 0.113776E+10 | 130377.42 | 0.113763E+10 | 0.397039E+10 | 69785164.39 |
October | 0.104222E+10 | 0.00 | 0.104222E+10 | 0.292921E+10 | 0.324520E+09 |
November | 0.865865E+09 | 0.00 | 0.865865E+09 | 0.178644E+10 | 0.869084E+09 |
December | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.107454E+10 | 0.160579E+10 |
Annual Sum or Average | 0.134316E+11 | 0.175822E+09 | 0.132558E+11 | 0.366675E+11 | 0.853351E+10 |
Minimum of Months | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.948156E+09 | 181970.79 |
Maximum of Months | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.555114E+10 | 0.196859E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101926E+10 | 0.308376E+09 | 0.710884E+09 | 0.137470E+10 | 0.123120E+10 |
February | 0.100327E+10 | 0.271890E+09 | 0.731376E+09 | 0.151642E+10 | 0.934003E+09 |
March | 0.122695E+10 | 0.302398E+09 | 0.924550E+09 | 0.215551E+10 | 0.788225E+09 |
April | 0.144567E+10 | 0.421221E+09 | 0.102445E+10 | 0.299807E+10 | 0.480234E+09 |
May | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.420679E+10 | 0.123703E+09 |
June | 0.158221E+10 | 0.483857E+09 | 0.109835E+10 | 0.430455E+10 | 28302847.07 |
July | 0.152597E+10 | 0.439934E+09 | 0.108604E+10 | 0.481783E+10 | 626212.12 |
August | 0.156257E+10 | 0.479573E+09 | 0.108299E+10 | 0.497517E+10 | 74599.98 |
September | 0.142161E+10 | 0.439402E+09 | 0.982206E+09 | 0.389122E+10 | 42317220.21 |
October | 0.133297E+10 | 0.435481E+09 | 0.897486E+09 | 0.313706E+10 | 0.201444E+09 |
November | 0.108100E+10 | 0.342405E+09 | 0.738593E+09 | 0.209240E+10 | 0.550002E+09 |
December | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.135083E+10 | 0.101602E+10 |
Annual Sum or Average | 0.157750E+11 | 0.470448E+10 | 0.110705E+11 | 0.368206E+11 | 0.539615E+10 |
Minimum of Months | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.135083E+10 | 74599.98 |
Maximum of Months | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.497517E+10 | 0.123120E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273147E+10 | 0.128419E+10 | 0.144728E+10 | 0.431425E+10 | 0.190485E+10 |
February | 0.231675E+10 | 0.947651E+09 | 0.136910E+10 | 0.390615E+10 | 0.146515E+10 |
March | 0.211109E+10 | 0.573148E+09 | 0.153794E+10 | 0.399838E+10 | 0.125759E+10 |
April | 0.160594E+10 | 0.170260E+09 | 0.143568E+10 | 0.362601E+10 | 0.761001E+09 |
May | 0.140572E+10 | 21527140.62 | 0.138419E+10 | 0.427420E+10 | 0.195447E+09 |
June | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.440150E+10 | 38215216.17 |
July | 0.132383E+10 | 11248476.20 | 0.131258E+10 | 0.538477E+10 | 615963.76 |
August | 0.153553E+10 | 0.108799E+09 | 0.142673E+10 | 0.602845E+10 | 98170.29 |
September | 0.195931E+10 | 0.449032E+09 | 0.151027E+10 | 0.574201E+10 | 69844429.22 |
October | 0.265062E+10 | 0.105377E+10 | 0.159685E+10 | 0.614182E+10 | 0.324131E+09 |
November | 0.282984E+10 | 0.136420E+10 | 0.146565E+10 | 0.550100E+10 | 0.866501E+09 |
December | 0.271452E+10 | 0.134089E+10 | 0.137363E+10 | 0.458403E+10 | 0.158191E+10 |
Annual Sum or Average | 0.244658E+11 | 0.732630E+10 | 0.171395E+11 | 0.579026E+11 | 0.846535E+10 |
Minimum of Months | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.362601E+10 | 98170.29 |
Maximum of Months | 0.282984E+10 | 0.136420E+10 | 0.159685E+10 | 0.614182E+10 | 0.190485E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.999569E+09 | 0.287085E+09 | 0.712484E+09 | 0.143017E+10 | 0.132199E+10 |
February | 0.103095E+10 | 0.293985E+09 | 0.736963E+09 | 0.163421E+10 | 0.994016E+09 |
March | 0.135203E+10 | 0.400272E+09 | 0.951758E+09 | 0.243612E+10 | 0.844369E+09 |
April | 0.142987E+10 | 0.401718E+09 | 0.102816E+10 | 0.299317E+10 | 0.523972E+09 |
May | 0.160829E+10 | 0.481426E+09 | 0.112687E+10 | 0.411994E+10 | 0.144712E+09 |
June | 0.160842E+10 | 0.507017E+09 | 0.110140E+10 | 0.438019E+10 | 32735068.71 |
July | 0.152474E+10 | 0.436197E+09 | 0.108854E+10 | 0.481571E+10 | 691822.31 |
August | 0.156421E+10 | 0.475587E+09 | 0.108862E+10 | 0.496106E+10 | 216261.01 |
September | 0.143997E+10 | 0.452397E+09 | 0.987572E+09 | 0.393257E+10 | 51991726.64 |
October | 0.132237E+10 | 0.427161E+09 | 0.895206E+09 | 0.314624E+10 | 0.233190E+09 |
November | 0.109975E+10 | 0.359654E+09 | 0.740098E+09 | 0.219405E+10 | 0.600256E+09 |
December | 0.951354E+09 | 0.287577E+09 | 0.663776E+09 | 0.152168E+10 | 0.108637E+10 |
Annual Sum or Average | 0.159315E+11 | 0.481008E+10 | 0.111214E+11 | 0.375651E+11 | 0.583451E+10 |
Minimum of Months | 0.951354E+09 | 0.287085E+09 | 0.663776E+09 | 0.143017E+10 | 216261.01 |
Maximum of Months | 0.160842E+10 | 0.507017E+09 | 0.112687E+10 | 0.496106E+10 | 0.132199E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 365.77 | 680.92 | 315.55 | 0.00 | 315.55 | 0.00 | 0.00 |
February | 502.07 | 571.73 | 361.71 | 0.00 | 361.71 | 0.00 | 0.00 |
March | 720.87 | 437.04 | 415.47 | 0.00 | 415.47 | 0.00 | 0.00 |
April | 1044.09 | 276.85 | 468.10 | 0.96 | 467.13 | 0.00 | 0.00 |
May | 1587.27 | 71.47 | 526.89 | 15.45 | 511.43 | 0.00 | 0.00 |
June | 1836.86 | 18.64 | 564.13 | 31.32 | 532.81 | 0.00 | 0.00 |
July | 2053.78 | 0.46 | 517.65 | 14.91 | 502.73 | 0.00 | 0.00 |
August | 2026.92 | 0.09 | 481.88 | 3.99 | 477.90 | 0.00 | 0.00 |
September | 1520.74 | 26.74 | 438.95 | 0.05 | 438.90 | 0.00 | 0.00 |
October | 1087.66 | 116.70 | 389.12 | 0.00 | 389.12 | 0.00 | 0.00 |
November | 689.98 | 315.78 | 334.05 | 0.00 | 334.05 | 0.00 | 0.00 |
December | 409.52 | 558.25 | 294.52 | 0.00 | 294.52 | 0.00 | 0.00 |
Annual Sum or Average | 1157.85 | 254.69 | 425.91 | 5.58 | 420.34 | 0.00 | 0.00 |
Minimum of Months | 365.77 | 0.09 | 294.52 | 0.00 | 294.52 | 0.00 | 0.00 |
Maximum of Months | 2053.78 | 680.92 | 564.13 | 31.32 | 532.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 526.85 | 429.70 | 380.55 | 115.13 | 265.41 | 0.00 | 0.00 |
February | 635.92 | 363.85 | 414.71 | 112.39 | 302.32 | 0.00 | 0.00 |
March | 809.43 | 279.95 | 458.09 | 112.90 | 345.19 | 0.00 | 0.00 |
April | 1156.32 | 179.06 | 557.74 | 162.51 | 395.23 | 0.00 | 0.00 |
May | 1565.56 | 45.61 | 623.29 | 198.58 | 424.71 | 0.00 | 0.00 |
June | 1655.04 | 11.15 | 610.42 | 186.67 | 423.75 | 0.00 | 0.00 |
July | 1790.13 | 0.25 | 569.73 | 164.25 | 405.48 | 0.00 | 0.00 |
August | 1850.87 | 0.04 | 583.40 | 179.05 | 404.34 | 0.00 | 0.00 |
September | 1497.36 | 16.05 | 548.46 | 169.52 | 378.94 | 0.00 | 0.00 |
October | 1170.42 | 72.07 | 497.67 | 162.59 | 335.08 | 0.00 | 0.00 |
November | 811.66 | 200.59 | 417.05 | 132.10 | 284.95 | 0.00 | 0.00 |
December | 514.80 | 355.69 | 337.56 | 92.61 | 244.95 | 0.00 | 0.00 |
Annual Sum or Average | 1168.46 | 161.85 | 500.22 | 149.18 | 351.04 | 0.00 | 0.00 |
Minimum of Months | 514.80 | 0.04 | 337.56 | 92.61 | 244.95 | 0.00 | 0.00 |
Maximum of Months | 1850.87 | 429.70 | 623.29 | 198.58 | 424.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1621.17 | 666.39 | 1019.82 | 479.46 | 540.35 | 0.00 | 0.00 |
February | 1618.32 | 571.24 | 957.65 | 391.72 | 565.93 | 0.00 | 0.00 |
March | 1490.83 | 446.49 | 788.19 | 213.99 | 574.20 | 0.00 | 0.00 |
April | 1391.49 | 283.37 | 619.58 | 65.69 | 553.89 | 0.00 | 0.00 |
May | 1582.49 | 72.05 | 524.83 | 8.04 | 516.80 | 0.00 | 0.00 |
June | 1684.06 | 15.07 | 494.27 | 0.61 | 493.66 | 0.00 | 0.00 |
July | 1990.96 | 0.24 | 494.26 | 4.20 | 490.06 | 0.00 | 0.00 |
August | 2233.86 | 0.05 | 573.30 | 40.62 | 532.68 | 0.00 | 0.00 |
September | 2202.07 | 26.67 | 755.91 | 173.24 | 582.67 | 0.00 | 0.00 |
October | 2283.85 | 116.74 | 989.63 | 393.43 | 596.20 | 0.00 | 0.00 |
November | 2120.29 | 317.00 | 1091.76 | 526.31 | 565.45 | 0.00 | 0.00 |
December | 1717.90 | 556.49 | 1013.48 | 500.63 | 512.85 | 0.00 | 0.00 |
Annual Sum or Average | 1829.60 | 254.44 | 775.80 | 232.32 | 543.49 | 0.00 | 0.00 |
Minimum of Months | 1391.49 | 0.05 | 494.26 | 0.61 | 490.06 | 0.00 | 0.00 |
Maximum of Months | 2283.85 | 666.39 | 1091.76 | 526.31 | 596.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 540.23 | 458.63 | 373.20 | 107.19 | 266.01 | 0.00 | 0.00 |
February | 678.21 | 385.82 | 426.15 | 121.52 | 304.63 | 0.00 | 0.00 |
March | 907.91 | 299.48 | 504.79 | 149.44 | 355.35 | 0.00 | 0.00 |
April | 1149.20 | 195.29 | 551.65 | 154.98 | 396.67 | 0.00 | 0.00 |
May | 1528.64 | 53.51 | 600.47 | 179.74 | 420.72 | 0.00 | 0.00 |
June | 1679.79 | 12.96 | 620.53 | 195.61 | 424.92 | 0.00 | 0.00 |
July | 1784.76 | 0.29 | 569.27 | 162.86 | 406.41 | 0.00 | 0.00 |
August | 1840.36 | 0.09 | 584.01 | 177.56 | 406.45 | 0.00 | 0.00 |
September | 1508.81 | 20.00 | 555.54 | 174.54 | 381.01 | 0.00 | 0.00 |
October | 1169.47 | 84.13 | 493.72 | 159.48 | 334.23 | 0.00 | 0.00 |
November | 845.68 | 218.68 | 424.29 | 138.76 | 285.53 | 0.00 | 0.00 |
December | 572.15 | 379.25 | 355.19 | 107.37 | 247.83 | 0.00 | 0.00 |
Annual Sum or Average | 1186.69 | 174.65 | 505.19 | 152.53 | 352.66 | 0.00 | 0.00 |
Minimum of Months | 540.23 | 0.09 | 355.19 | 107.19 | 247.83 | 0.00 | 0.00 |
Maximum of Months | 1840.36 | 458.63 | 620.53 | 195.61 | 424.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 347.21 | 773.26 | 315.54 | 0.00 | 315.54 | 0.00 | 0.00 |
February | 495.54 | 627.37 | 361.70 | 0.00 | 361.70 | 0.00 | 0.00 |
March | 727.56 | 458.39 | 415.46 | 0.00 | 415.46 | 0.00 | 0.00 |
April | 1060.63 | 276.53 | 468.09 | 0.96 | 467.12 | 0.00 | 0.00 |
May | 1602.85 | 67.84 | 526.88 | 15.45 | 511.42 | 0.00 | 0.00 |
June | 1845.49 | 17.20 | 564.12 | 31.32 | 532.80 | 0.00 | 0.00 |
July | 2057.31 | 0.45 | 517.64 | 14.91 | 502.72 | 0.00 | 0.00 |
August | 2014.35 | 0.08 | 481.87 | 3.99 | 477.89 | 0.00 | 0.00 |
September | 1504.78 | 31.09 | 438.94 | 0.05 | 438.89 | 0.00 | 0.00 |
October | 1068.17 | 136.35 | 389.11 | 0.00 | 389.11 | 0.00 | 0.00 |
November | 670.36 | 366.46 | 334.05 | 0.00 | 334.05 | 0.00 | 0.00 |
December | 390.00 | 642.37 | 294.52 | 0.00 | 294.52 | 0.00 | 0.00 |
Annual Sum or Average | 1152.72 | 281.49 | 425.90 | 5.58 | 420.33 | 0.00 | 0.00 |
Minimum of Months | 347.21 | 0.08 | 294.52 | 0.00 | 294.52 | 0.00 | 0.00 |
Maximum of Months | 2057.31 | 773.26 | 564.12 | 31.32 | 532.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 511.34 | 487.43 | 380.54 | 115.13 | 265.41 | 0.00 | 0.00 |
February | 630.90 | 401.18 | 414.70 | 112.39 | 302.32 | 0.00 | 0.00 |
March | 814.34 | 296.81 | 458.08 | 112.90 | 345.18 | 0.00 | 0.00 |
April | 1168.14 | 183.91 | 557.73 | 162.50 | 395.23 | 0.00 | 0.00 |
May | 1576.32 | 46.35 | 623.28 | 198.58 | 424.70 | 0.00 | 0.00 |
June | 1661.12 | 11.55 | 610.41 | 186.67 | 423.74 | 0.00 | 0.00 |
July | 1791.73 | 0.32 | 569.72 | 164.25 | 405.47 | 0.00 | 0.00 |
August | 1841.57 | 0.06 | 583.39 | 179.05 | 404.34 | 0.00 | 0.00 |
September | 1486.91 | 20.36 | 548.45 | 169.52 | 378.93 | 0.00 | 0.00 |
October | 1159.88 | 89.22 | 497.67 | 162.59 | 335.08 | 0.00 | 0.00 |
November | 799.53 | 236.62 | 417.05 | 132.10 | 284.95 | 0.00 | 0.00 |
December | 499.83 | 408.64 | 337.56 | 92.61 | 244.95 | 0.00 | 0.00 |
Annual Sum or Average | 1164.88 | 180.82 | 500.22 | 149.18 | 351.04 | 0.00 | 0.00 |
Minimum of Months | 499.83 | 0.06 | 337.56 | 92.61 | 244.95 | 0.00 | 0.00 |
Maximum of Months | 1841.57 | 487.43 | 623.28 | 198.58 | 424.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1613.83 | 758.24 | 1019.78 | 479.44 | 540.34 | 0.00 | 0.00 |
February | 1623.19 | 634.36 | 957.61 | 391.70 | 565.91 | 0.00 | 0.00 |
March | 1502.91 | 473.64 | 788.16 | 213.98 | 574.18 | 0.00 | 0.00 |
April | 1407.22 | 287.14 | 619.56 | 65.68 | 553.87 | 0.00 | 0.00 |
May | 1586.22 | 71.05 | 524.82 | 8.04 | 516.78 | 0.00 | 0.00 |
June | 1674.06 | 15.29 | 494.26 | 0.61 | 493.65 | 0.00 | 0.00 |
July | 1975.08 | 0.30 | 494.25 | 4.20 | 490.05 | 0.00 | 0.00 |
August | 2193.88 | 0.12 | 573.28 | 40.62 | 532.67 | 0.00 | 0.00 |
September | 2168.53 | 34.83 | 755.88 | 173.23 | 582.65 | 0.00 | 0.00 |
October | 2260.19 | 149.46 | 989.59 | 393.42 | 596.18 | 0.00 | 0.00 |
November | 2108.07 | 381.89 | 1091.72 | 526.29 | 565.43 | 0.00 | 0.00 |
December | 1709.63 | 641.92 | 1013.45 | 500.61 | 512.84 | 0.00 | 0.00 |
Annual Sum or Average | 1819.94 | 285.68 | 775.78 | 232.31 | 543.47 | 0.00 | 0.00 |
Minimum of Months | 1407.22 | 0.12 | 494.25 | 0.61 | 490.05 | 0.00 | 0.00 |
Maximum of Months | 2260.19 | 758.24 | 1091.72 | 526.29 | 596.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 530.93 | 524.80 | 373.19 | 107.18 | 266.01 | 0.00 | 0.00 |
February | 677.23 | 428.34 | 426.15 | 121.52 | 304.63 | 0.00 | 0.00 |
March | 916.09 | 320.01 | 504.78 | 149.44 | 355.34 | 0.00 | 0.00 |
April | 1162.66 | 201.21 | 551.64 | 154.98 | 396.66 | 0.00 | 0.00 |
May | 1539.05 | 54.49 | 600.46 | 179.74 | 420.72 | 0.00 | 0.00 |
June | 1683.77 | 13.77 | 620.53 | 195.61 | 424.92 | 0.00 | 0.00 |
July | 1785.83 | 0.40 | 569.27 | 162.85 | 406.41 | 0.00 | 0.00 |
August | 1831.66 | 0.12 | 584.00 | 177.56 | 406.44 | 0.00 | 0.00 |
September | 1498.85 | 24.87 | 555.54 | 174.53 | 381.00 | 0.00 | 0.00 |
October | 1159.57 | 102.07 | 493.71 | 159.48 | 334.23 | 0.00 | 0.00 |
November | 836.16 | 258.57 | 424.28 | 138.75 | 285.53 | 0.00 | 0.00 |
December | 562.44 | 438.46 | 355.19 | 107.37 | 247.82 | 0.00 | 0.00 |
Annual Sum or Average | 1184.93 | 196.16 | 505.18 | 152.52 | 352.65 | 0.00 | 0.00 |
Minimum of Months | 530.93 | 0.12 | 355.19 | 107.18 | 247.82 | 0.00 | 0.00 |
Maximum of Months | 1831.66 | 524.80 | 620.53 | 195.61 | 424.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 354.00 | 734.99 | 315.55 | 0.00 | 315.55 | 0.00 | 0.00 |
February | 495.64 | 610.49 | 361.71 | 0.00 | 361.71 | 0.00 | 0.00 |
March | 720.75 | 461.12 | 415.47 | 0.00 | 415.47 | 0.00 | 0.00 |
April | 1050.66 | 286.78 | 468.10 | 0.96 | 467.13 | 0.00 | 0.00 |
May | 1599.98 | 71.90 | 526.89 | 15.45 | 511.43 | 0.00 | 0.00 |
June | 1850.99 | 17.97 | 564.13 | 31.32 | 532.81 | 0.00 | 0.00 |
July | 2072.56 | 0.42 | 517.65 | 14.91 | 502.73 | 0.00 | 0.00 |
August | 2042.87 | 0.07 | 481.88 | 3.99 | 477.90 | 0.00 | 0.00 |
September | 1531.79 | 26.92 | 438.95 | 0.05 | 438.90 | 0.00 | 0.00 |
October | 1093.64 | 121.16 | 389.12 | 0.00 | 389.12 | 0.00 | 0.00 |
November | 689.21 | 335.29 | 334.05 | 0.00 | 334.05 | 0.00 | 0.00 |
December | 401.19 | 599.53 | 294.52 | 0.00 | 294.52 | 0.00 | 0.00 |
Annual Sum or Average | 1162.72 | 270.60 | 425.91 | 5.58 | 420.34 | 0.00 | 0.00 |
Minimum of Months | 354.00 | 0.07 | 294.52 | 0.00 | 294.52 | 0.00 | 0.00 |
Maximum of Months | 2072.56 | 734.99 | 564.13 | 31.32 | 532.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 513.25 | 459.68 | 380.55 | 115.13 | 265.41 | 0.00 | 0.00 |
February | 626.83 | 386.08 | 414.71 | 112.39 | 302.32 | 0.00 | 0.00 |
March | 804.78 | 294.29 | 458.09 | 112.90 | 345.19 | 0.00 | 0.00 |
April | 1156.66 | 185.28 | 557.74 | 162.51 | 395.23 | 0.00 | 0.00 |
May | 1570.64 | 46.19 | 623.29 | 198.58 | 424.71 | 0.00 | 0.00 |
June | 1660.71 | 10.92 | 610.42 | 186.67 | 423.75 | 0.00 | 0.00 |
July | 1798.77 | 0.23 | 569.73 | 164.25 | 405.48 | 0.00 | 0.00 |
August | 1857.52 | 0.03 | 583.40 | 179.05 | 404.34 | 0.00 | 0.00 |
September | 1501.24 | 16.33 | 548.46 | 169.52 | 378.94 | 0.00 | 0.00 |
October | 1171.24 | 75.21 | 497.67 | 162.59 | 335.08 | 0.00 | 0.00 |
November | 807.25 | 212.19 | 417.05 | 132.10 | 284.95 | 0.00 | 0.00 |
December | 504.34 | 379.34 | 337.56 | 92.61 | 244.95 | 0.00 | 0.00 |
Annual Sum or Average | 1167.57 | 171.11 | 500.22 | 149.18 | 351.04 | 0.00 | 0.00 |
Minimum of Months | 504.34 | 0.03 | 337.56 | 92.61 | 244.95 | 0.00 | 0.00 |
Maximum of Months | 1857.52 | 459.68 | 623.29 | 198.58 | 424.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1610.76 | 711.19 | 1019.82 | 479.46 | 540.35 | 0.00 | 0.00 |
February | 1614.65 | 605.63 | 957.65 | 391.72 | 565.93 | 0.00 | 0.00 |
March | 1492.82 | 469.53 | 788.19 | 213.99 | 574.20 | 0.00 | 0.00 |
April | 1398.92 | 293.60 | 619.58 | 65.69 | 553.89 | 0.00 | 0.00 |
May | 1595.80 | 72.97 | 524.83 | 8.04 | 516.80 | 0.00 | 0.00 |
June | 1698.11 | 14.74 | 494.27 | 0.61 | 493.66 | 0.00 | 0.00 |
July | 2010.44 | 0.23 | 494.26 | 4.20 | 490.06 | 0.00 | 0.00 |
August | 2250.76 | 0.04 | 573.30 | 40.62 | 532.68 | 0.00 | 0.00 |
September | 2215.28 | 26.95 | 755.91 | 173.24 | 582.67 | 0.00 | 0.00 |
October | 2293.09 | 121.02 | 989.63 | 393.43 | 596.20 | 0.00 | 0.00 |
November | 2122.30 | 334.30 | 1091.76 | 526.31 | 565.45 | 0.00 | 0.00 |
December | 1711.48 | 590.62 | 1013.48 | 500.63 | 512.85 | 0.00 | 0.00 |
Annual Sum or Average | 1836.08 | 268.43 | 775.80 | 232.32 | 543.49 | 0.00 | 0.00 |
Minimum of Months | 1398.92 | 0.04 | 494.26 | 0.61 | 490.06 | 0.00 | 0.00 |
Maximum of Months | 2293.09 | 711.19 | 1091.76 | 526.31 | 596.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 533.96 | 493.58 | 373.20 | 107.19 | 266.01 | 0.00 | 0.00 |
February | 675.52 | 410.89 | 426.15 | 121.52 | 304.63 | 0.00 | 0.00 |
March | 909.54 | 315.25 | 504.79 | 149.44 | 355.35 | 0.00 | 0.00 |
April | 1154.77 | 202.15 | 551.65 | 154.98 | 396.67 | 0.00 | 0.00 |
May | 1538.21 | 54.03 | 600.47 | 179.74 | 420.72 | 0.00 | 0.00 |
June | 1689.89 | 12.63 | 620.53 | 195.61 | 424.92 | 0.00 | 0.00 |
July | 1797.98 | 0.26 | 569.27 | 162.86 | 406.41 | 0.00 | 0.00 |
August | 1852.25 | 0.08 | 584.01 | 177.56 | 406.45 | 0.00 | 0.00 |
September | 1517.19 | 20.06 | 555.54 | 174.54 | 381.01 | 0.00 | 0.00 |
October | 1174.67 | 87.06 | 493.72 | 159.48 | 334.23 | 0.00 | 0.00 |
November | 846.47 | 231.58 | 424.29 | 138.76 | 285.53 | 0.00 | 0.00 |
December | 568.13 | 405.60 | 355.19 | 107.37 | 247.83 | 0.00 | 0.00 |
Annual Sum or Average | 1191.18 | 185.01 | 505.19 | 152.53 | 352.66 | 0.00 | 0.00 |
Minimum of Months | 533.96 | 0.08 | 355.19 | 107.19 | 247.83 | 0.00 | 0.00 |
Maximum of Months | 1852.25 | 493.58 | 620.53 | 195.61 | 424.92 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.979684E+09 | 0.182377E+10 | 0.845162E+09 | 0.00 | 0.845162E+09 | 0.00 | 0.00 |
February | 0.121461E+10 | 0.138312E+10 | 0.875042E+09 | 0.00 | 0.875042E+09 | 0.00 | 0.00 |
March | 0.193079E+10 | 0.117057E+10 | 0.111279E+10 | 0.00 | 0.111279E+10 | 0.00 | 0.00 |
April | 0.270629E+10 | 0.717585E+09 | 0.121331E+10 | 2499967.15 | 0.121081E+10 | 0.00 | 0.00 |
May | 0.425135E+10 | 0.191421E+09 | 0.141121E+10 | 41390031.38 | 0.136982E+10 | 0.00 | 0.00 |
June | 0.476113E+10 | 48317070.86 | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.00 | 0.00 |
July | 0.550084E+10 | 1225411.27 | 0.138646E+10 | 39947373.00 | 0.134652E+10 | 0.00 | 0.00 |
August | 0.542891E+10 | 240874.21 | 0.129068E+10 | 10675196.26 | 0.128000E+10 | 0.00 | 0.00 |
September | 0.394177E+10 | 69307695.62 | 0.113776E+10 | 130377.42 | 0.113763E+10 | 0.00 | 0.00 |
October | 0.291319E+10 | 0.312566E+09 | 0.104222E+10 | 0.00 | 0.104222E+10 | 0.00 | 0.00 |
November | 0.178843E+10 | 0.818503E+09 | 0.865865E+09 | 0.00 | 0.865865E+09 | 0.00 | 0.00 |
December | 0.109687E+10 | 0.149521E+10 | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.365139E+11 | 0.803184E+10 | 0.134316E+11 | 0.175822E+09 | 0.132558E+11 | 0.00 | 0.00 |
Minimum of Months | 0.979684E+09 | 240874.21 | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.00 | 0.00 |
Maximum of Months | 0.550084E+10 | 0.182377E+10 | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.141111E+10 | 0.115091E+10 | 0.101926E+10 | 0.308376E+09 | 0.710884E+09 | 0.00 | 0.00 |
February | 0.153842E+10 | 0.880223E+09 | 0.100327E+10 | 0.271890E+09 | 0.731376E+09 | 0.00 | 0.00 |
March | 0.216798E+10 | 0.749827E+09 | 0.122695E+10 | 0.302398E+09 | 0.924550E+09 | 0.00 | 0.00 |
April | 0.299718E+10 | 0.464121E+09 | 0.144567E+10 | 0.421221E+09 | 0.102445E+10 | 0.00 | 0.00 |
May | 0.419319E+10 | 0.122151E+09 | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.00 | 0.00 |
June | 0.428987E+10 | 28891175.24 | 0.158221E+10 | 0.483857E+09 | 0.109835E+10 | 0.00 | 0.00 |
July | 0.479469E+10 | 674978.22 | 0.152597E+10 | 0.439934E+09 | 0.108604E+10 | 0.00 | 0.00 |
August | 0.495737E+10 | 99172.84 | 0.156257E+10 | 0.479573E+09 | 0.108299E+10 | 0.00 | 0.00 |
September | 0.388116E+10 | 41599938.37 | 0.142161E+10 | 0.439402E+09 | 0.982206E+09 | 0.00 | 0.00 |
October | 0.313485E+10 | 0.193027E+09 | 0.133297E+10 | 0.435481E+09 | 0.897486E+09 | 0.00 | 0.00 |
November | 0.210382E+10 | 0.519938E+09 | 0.108100E+10 | 0.342405E+09 | 0.738593E+09 | 0.00 | 0.00 |
December | 0.137884E+10 | 0.952693E+09 | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.368485E+11 | 0.510416E+10 | 0.157750E+11 | 0.470448E+10 | 0.110705E+11 | 0.00 | 0.00 |
Minimum of Months | 0.137884E+10 | 99172.84 | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.495737E+10 | 0.115091E+10 | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.434213E+10 | 0.178485E+10 | 0.273147E+10 | 0.128419E+10 | 0.144728E+10 | 0.00 | 0.00 |
February | 0.391505E+10 | 0.138193E+10 | 0.231675E+10 | 0.947651E+09 | 0.136910E+10 | 0.00 | 0.00 |
March | 0.399303E+10 | 0.119588E+10 | 0.211109E+10 | 0.573148E+09 | 0.153794E+10 | 0.00 | 0.00 |
April | 0.360674E+10 | 0.734502E+09 | 0.160594E+10 | 0.170260E+09 | 0.143568E+10 | 0.00 | 0.00 |
May | 0.423855E+10 | 0.192971E+09 | 0.140572E+10 | 21527140.62 | 0.138419E+10 | 0.00 | 0.00 |
June | 0.436509E+10 | 39049487.05 | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.00 | 0.00 |
July | 0.533258E+10 | 652313.63 | 0.132383E+10 | 11248476.20 | 0.131258E+10 | 0.00 | 0.00 |
August | 0.598317E+10 | 141556.22 | 0.153553E+10 | 0.108799E+09 | 0.142673E+10 | 0.00 | 0.00 |
September | 0.570776E+10 | 69129032.68 | 0.195931E+10 | 0.449032E+09 | 0.151027E+10 | 0.00 | 0.00 |
October | 0.611705E+10 | 0.312685E+09 | 0.265062E+10 | 0.105377E+10 | 0.159685E+10 | 0.00 | 0.00 |
November | 0.549579E+10 | 0.821654E+09 | 0.282984E+10 | 0.136420E+10 | 0.146565E+10 | 0.00 | 0.00 |
December | 0.460124E+10 | 0.149051E+10 | 0.271452E+10 | 0.134089E+10 | 0.137363E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.576982E+11 | 0.802396E+10 | 0.244658E+11 | 0.732630E+10 | 0.171395E+11 | 0.00 | 0.00 |
Minimum of Months | 0.360674E+10 | 141556.22 | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.00 | 0.00 |
Maximum of Months | 0.611705E+10 | 0.178485E+10 | 0.282984E+10 | 0.136420E+10 | 0.159685E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.144696E+10 | 0.122840E+10 | 0.999569E+09 | 0.287085E+09 | 0.712484E+09 | 0.00 | 0.00 |
February | 0.164073E+10 | 0.933365E+09 | 0.103095E+10 | 0.293985E+09 | 0.736963E+09 | 0.00 | 0.00 |
March | 0.243173E+10 | 0.802115E+09 | 0.135203E+10 | 0.400272E+09 | 0.951758E+09 | 0.00 | 0.00 |
April | 0.297872E+10 | 0.506179E+09 | 0.142987E+10 | 0.401718E+09 | 0.102816E+10 | 0.00 | 0.00 |
May | 0.409432E+10 | 0.143315E+09 | 0.160829E+10 | 0.481426E+09 | 0.112687E+10 | 0.00 | 0.00 |
June | 0.435402E+10 | 33587281.63 | 0.160842E+10 | 0.507017E+09 | 0.110140E+10 | 0.00 | 0.00 |
July | 0.478029E+10 | 784398.03 | 0.152474E+10 | 0.436197E+09 | 0.108854E+10 | 0.00 | 0.00 |
August | 0.492923E+10 | 238983.73 | 0.156421E+10 | 0.475587E+09 | 0.108862E+10 | 0.00 | 0.00 |
September | 0.391083E+10 | 51838292.69 | 0.143997E+10 | 0.452397E+09 | 0.987572E+09 | 0.00 | 0.00 |
October | 0.313231E+10 | 0.225346E+09 | 0.132237E+10 | 0.427161E+09 | 0.895206E+09 | 0.00 | 0.00 |
November | 0.219200E+10 | 0.566815E+09 | 0.109975E+10 | 0.359654E+09 | 0.740098E+09 | 0.00 | 0.00 |
December | 0.153244E+10 | 0.101579E+10 | 0.951354E+09 | 0.287577E+09 | 0.663776E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.374236E+11 | 0.550778E+10 | 0.159315E+11 | 0.481008E+10 | 0.111214E+11 | 0.00 | 0.00 |
Minimum of Months | 0.144696E+10 | 238983.73 | 0.951354E+09 | 0.287085E+09 | 0.663776E+09 | 0.00 | 0.00 |
Maximum of Months | 0.492923E+10 | 0.122840E+10 | 0.160842E+10 | 0.507017E+09 | 0.112687E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.929960E+09 | 0.207109E+10 | 0.845143E+09 | 0.00 | 0.845143E+09 | 0.00 | 0.00 |
February | 0.119881E+10 | 0.151772E+10 | 0.875023E+09 | 0.00 | 0.875023E+09 | 0.00 | 0.00 |
March | 0.194869E+10 | 0.122776E+10 | 0.111277E+10 | 0.00 | 0.111277E+10 | 0.00 | 0.00 |
April | 0.274915E+10 | 0.716770E+09 | 0.121329E+10 | 2499893.67 | 0.121079E+10 | 0.00 | 0.00 |
May | 0.429308E+10 | 0.181690E+09 | 0.141118E+10 | 41388814.81 | 0.136979E+10 | 0.00 | 0.00 |
June | 0.478350E+10 | 44586681.35 | 0.146220E+10 | 81176234.19 | 0.138102E+10 | 0.00 | 0.00 |
July | 0.551029E+10 | 1212505.15 | 0.138643E+10 | 39946198.84 | 0.134649E+10 | 0.00 | 0.00 |
August | 0.539523E+10 | 220215.74 | 0.129065E+10 | 10674882.49 | 0.127998E+10 | 0.00 | 0.00 |
September | 0.390039E+10 | 80598049.96 | 0.113774E+10 | 130373.59 | 0.113761E+10 | 0.00 | 0.00 |
October | 0.286098E+10 | 0.365188E+09 | 0.104220E+10 | 0.00 | 0.104220E+10 | 0.00 | 0.00 |
November | 0.173757E+10 | 0.949873E+09 | 0.865846E+09 | 0.00 | 0.865846E+09 | 0.00 | 0.00 |
December | 0.104457E+10 | 0.172051E+10 | 0.788831E+09 | 0.00 | 0.788831E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.363522E+11 | 0.887722E+10 | 0.134313E+11 | 0.175816E+09 | 0.132555E+11 | 0.00 | 0.00 |
Minimum of Months | 0.929960E+09 | 220215.74 | 0.788831E+09 | 0.00 | 0.788831E+09 | 0.00 | 0.00 |
Maximum of Months | 0.551029E+10 | 0.207109E+10 | 0.146220E+10 | 81176234.19 | 0.138102E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.136957E+10 | 0.130552E+10 | 0.101924E+10 | 0.308370E+09 | 0.710874E+09 | 0.00 | 0.00 |
February | 0.152628E+10 | 0.970542E+09 | 0.100325E+10 | 0.271885E+09 | 0.731366E+09 | 0.00 | 0.00 |
March | 0.218112E+10 | 0.794968E+09 | 0.122693E+10 | 0.302392E+09 | 0.924537E+09 | 0.00 | 0.00 |
April | 0.302782E+10 | 0.476686E+09 | 0.144565E+10 | 0.421212E+09 | 0.102444E+10 | 0.00 | 0.00 |
May | 0.422200E+10 | 0.124152E+09 | 0.166940E+10 | 0.531878E+09 | 0.113752E+10 | 0.00 | 0.00 |
June | 0.430563E+10 | 29939891.23 | 0.158218E+10 | 0.483847E+09 | 0.109834E+10 | 0.00 | 0.00 |
July | 0.479898E+10 | 867607.89 | 0.152595E+10 | 0.439926E+09 | 0.108602E+10 | 0.00 | 0.00 |
August | 0.493247E+10 | 160978.33 | 0.156254E+10 | 0.479564E+09 | 0.108298E+10 | 0.00 | 0.00 |
September | 0.385407E+10 | 52768846.06 | 0.142159E+10 | 0.439394E+09 | 0.982194E+09 | 0.00 | 0.00 |
October | 0.310662E+10 | 0.238953E+09 | 0.133295E+10 | 0.435473E+09 | 0.897474E+09 | 0.00 | 0.00 |
November | 0.207238E+10 | 0.613320E+09 | 0.108098E+10 | 0.342398E+09 | 0.738583E+09 | 0.00 | 0.00 |
December | 0.133875E+10 | 0.109449E+10 | 0.904115E+09 | 0.248051E+09 | 0.656063E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.367357E+11 | 0.570237E+10 | 0.157748E+11 | 0.470439E+10 | 0.110704E+11 | 0.00 | 0.00 |
Minimum of Months | 0.133875E+10 | 160978.33 | 0.904115E+09 | 0.248051E+09 | 0.656063E+09 | 0.00 | 0.00 |
Maximum of Months | 0.493247E+10 | 0.130552E+10 | 0.166940E+10 | 0.531878E+09 | 0.113752E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.432248E+10 | 0.203088E+10 | 0.273137E+10 | 0.128414E+10 | 0.144723E+10 | 0.00 | 0.00 |
February | 0.392682E+10 | 0.153464E+10 | 0.231666E+10 | 0.947611E+09 | 0.136905E+10 | 0.00 | 0.00 |
March | 0.402538E+10 | 0.126860E+10 | 0.211101E+10 | 0.573124E+09 | 0.153789E+10 | 0.00 | 0.00 |
April | 0.364750E+10 | 0.744275E+09 | 0.160589E+10 | 0.170253E+09 | 0.143564E+10 | 0.00 | 0.00 |
May | 0.424853E+10 | 0.190302E+09 | 0.140567E+10 | 21526247.30 | 0.138415E+10 | 0.00 | 0.00 |
June | 0.433917E+10 | 39638997.51 | 0.128112E+10 | 1585412.74 | 0.127953E+10 | 0.00 | 0.00 |
July | 0.529007E+10 | 793705.33 | 0.132379E+10 | 11248009.42 | 0.131254E+10 | 0.00 | 0.00 |
August | 0.587609E+10 | 309151.50 | 0.153548E+10 | 0.108794E+09 | 0.142669E+10 | 0.00 | 0.00 |
September | 0.562084E+10 | 90291725.83 | 0.195924E+10 | 0.449014E+09 | 0.151023E+10 | 0.00 | 0.00 |
October | 0.605370E+10 | 0.400313E+09 | 0.265052E+10 | 0.105373E+10 | 0.159680E+10 | 0.00 | 0.00 |
November | 0.546412E+10 | 0.989854E+09 | 0.282974E+10 | 0.136414E+10 | 0.146560E+10 | 0.00 | 0.00 |
December | 0.457907E+10 | 0.171933E+10 | 0.271441E+10 | 0.134083E+10 | 0.137358E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.573938E+11 | 0.900923E+10 | 0.244649E+11 | 0.732599E+10 | 0.171389E+11 | 0.00 | 0.00 |
Minimum of Months | 0.364750E+10 | 309151.50 | 0.128112E+10 | 1585412.74 | 0.127953E+10 | 0.00 | 0.00 |
Maximum of Months | 0.605370E+10 | 0.203088E+10 | 0.282974E+10 | 0.136414E+10 | 0.159680E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.142206E+10 | 0.140563E+10 | 0.999556E+09 | 0.287080E+09 | 0.712476E+09 | 0.00 | 0.00 |
February | 0.163834E+10 | 0.103625E+10 | 0.103093E+10 | 0.293980E+09 | 0.736954E+09 | 0.00 | 0.00 |
March | 0.245365E+10 | 0.857113E+09 | 0.135201E+10 | 0.400265E+09 | 0.951747E+09 | 0.00 | 0.00 |
April | 0.301360E+10 | 0.521543E+09 | 0.142986E+10 | 0.401712E+09 | 0.102814E+10 | 0.00 | 0.00 |
May | 0.412220E+10 | 0.145957E+09 | 0.160827E+10 | 0.481418E+09 | 0.112685E+10 | 0.00 | 0.00 |
June | 0.436434E+10 | 35700353.83 | 0.160840E+10 | 0.507009E+09 | 0.110139E+10 | 0.00 | 0.00 |
July | 0.478316E+10 | 1083078.03 | 0.152472E+10 | 0.436190E+09 | 0.108853E+10 | 0.00 | 0.00 |
August | 0.490591E+10 | 329178.03 | 0.156419E+10 | 0.475579E+09 | 0.108861E+10 | 0.00 | 0.00 |
September | 0.388502E+10 | 64461705.86 | 0.143995E+10 | 0.452390E+09 | 0.987562E+09 | 0.00 | 0.00 |
October | 0.310578E+10 | 0.273382E+09 | 0.132235E+10 | 0.427154E+09 | 0.895196E+09 | 0.00 | 0.00 |
November | 0.216732E+10 | 0.670209E+09 | 0.109974E+10 | 0.359649E+09 | 0.740090E+09 | 0.00 | 0.00 |
December | 0.150643E+10 | 0.117438E+10 | 0.951341E+09 | 0.287573E+09 | 0.663769E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.373678E+11 | 0.618604E+10 | 0.159313E+11 | 0.481000E+10 | 0.111213E+11 | 0.00 | 0.00 |
Minimum of Months | 0.142206E+10 | 329178.03 | 0.951341E+09 | 0.287080E+09 | 0.663769E+09 | 0.00 | 0.00 |
Maximum of Months | 0.490591E+10 | 0.140563E+10 | 0.160840E+10 | 0.507009E+09 | 0.112685E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.948156E+09 | 0.196859E+10 | 0.845162E+09 | 0.00 | 0.845162E+09 | 0.00 | 0.00 |
February | 0.119905E+10 | 0.147689E+10 | 0.875042E+09 | 0.00 | 0.875042E+09 | 0.00 | 0.00 |
March | 0.193046E+10 | 0.123507E+10 | 0.111279E+10 | 0.00 | 0.111279E+10 | 0.00 | 0.00 |
April | 0.272332E+10 | 0.743321E+09 | 0.121331E+10 | 2499967.15 | 0.121081E+10 | 0.00 | 0.00 |
May | 0.428540E+10 | 0.192576E+09 | 0.141121E+10 | 41390031.38 | 0.136982E+10 | 0.00 | 0.00 |
June | 0.479776E+10 | 46583234.74 | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.00 | 0.00 |
July | 0.555114E+10 | 1121931.77 | 0.138646E+10 | 39947373.00 | 0.134652E+10 | 0.00 | 0.00 |
August | 0.547164E+10 | 181970.79 | 0.129068E+10 | 10675196.26 | 0.128000E+10 | 0.00 | 0.00 |
September | 0.397039E+10 | 69785164.39 | 0.113776E+10 | 130377.42 | 0.113763E+10 | 0.00 | 0.00 |
October | 0.292921E+10 | 0.324520E+09 | 0.104222E+10 | 0.00 | 0.104222E+10 | 0.00 | 0.00 |
November | 0.178644E+10 | 0.869084E+09 | 0.865865E+09 | 0.00 | 0.865865E+09 | 0.00 | 0.00 |
December | 0.107454E+10 | 0.160579E+10 | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.366675E+11 | 0.853351E+10 | 0.134316E+11 | 0.175822E+09 | 0.132558E+11 | 0.00 | 0.00 |
Minimum of Months | 0.948156E+09 | 181970.79 | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.00 | 0.00 |
Maximum of Months | 0.555114E+10 | 0.196859E+10 | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.137470E+10 | 0.123120E+10 | 0.101926E+10 | 0.308376E+09 | 0.710884E+09 | 0.00 | 0.00 |
February | 0.151642E+10 | 0.934003E+09 | 0.100327E+10 | 0.271890E+09 | 0.731376E+09 | 0.00 | 0.00 |
March | 0.215551E+10 | 0.788225E+09 | 0.122695E+10 | 0.302398E+09 | 0.924550E+09 | 0.00 | 0.00 |
April | 0.299807E+10 | 0.480234E+09 | 0.144567E+10 | 0.421221E+09 | 0.102445E+10 | 0.00 | 0.00 |
May | 0.420679E+10 | 0.123703E+09 | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.00 | 0.00 |
June | 0.430455E+10 | 28302847.07 | 0.158221E+10 | 0.483857E+09 | 0.109835E+10 | 0.00 | 0.00 |
July | 0.481783E+10 | 626212.12 | 0.152597E+10 | 0.439934E+09 | 0.108604E+10 | 0.00 | 0.00 |
August | 0.497517E+10 | 74599.98 | 0.156257E+10 | 0.479573E+09 | 0.108299E+10 | 0.00 | 0.00 |
September | 0.389122E+10 | 42317220.21 | 0.142161E+10 | 0.439402E+09 | 0.982206E+09 | 0.00 | 0.00 |
October | 0.313706E+10 | 0.201444E+09 | 0.133297E+10 | 0.435481E+09 | 0.897486E+09 | 0.00 | 0.00 |
November | 0.209240E+10 | 0.550002E+09 | 0.108100E+10 | 0.342405E+09 | 0.738593E+09 | 0.00 | 0.00 |
December | 0.135083E+10 | 0.101602E+10 | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.368206E+11 | 0.539615E+10 | 0.157750E+11 | 0.470448E+10 | 0.110705E+11 | 0.00 | 0.00 |
Minimum of Months | 0.135083E+10 | 74599.98 | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.497517E+10 | 0.123120E+10 | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.431425E+10 | 0.190485E+10 | 0.273147E+10 | 0.128419E+10 | 0.144728E+10 | 0.00 | 0.00 |
February | 0.390615E+10 | 0.146515E+10 | 0.231675E+10 | 0.947651E+09 | 0.136910E+10 | 0.00 | 0.00 |
March | 0.399838E+10 | 0.125759E+10 | 0.211109E+10 | 0.573148E+09 | 0.153794E+10 | 0.00 | 0.00 |
April | 0.362601E+10 | 0.761001E+09 | 0.160594E+10 | 0.170260E+09 | 0.143568E+10 | 0.00 | 0.00 |
May | 0.427420E+10 | 0.195447E+09 | 0.140572E+10 | 21527140.62 | 0.138419E+10 | 0.00 | 0.00 |
June | 0.440150E+10 | 38215216.17 | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.00 | 0.00 |
July | 0.538477E+10 | 615963.76 | 0.132383E+10 | 11248476.20 | 0.131258E+10 | 0.00 | 0.00 |
August | 0.602845E+10 | 98170.29 | 0.153553E+10 | 0.108799E+09 | 0.142673E+10 | 0.00 | 0.00 |
September | 0.574201E+10 | 69844429.22 | 0.195931E+10 | 0.449032E+09 | 0.151027E+10 | 0.00 | 0.00 |
October | 0.614182E+10 | 0.324131E+09 | 0.265062E+10 | 0.105377E+10 | 0.159685E+10 | 0.00 | 0.00 |
November | 0.550100E+10 | 0.866501E+09 | 0.282984E+10 | 0.136420E+10 | 0.146565E+10 | 0.00 | 0.00 |
December | 0.458403E+10 | 0.158191E+10 | 0.271452E+10 | 0.134089E+10 | 0.137363E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.579026E+11 | 0.846535E+10 | 0.244658E+11 | 0.732630E+10 | 0.171395E+11 | 0.00 | 0.00 |
Minimum of Months | 0.362601E+10 | 98170.29 | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.00 | 0.00 |
Maximum of Months | 0.614182E+10 | 0.190485E+10 | 0.282984E+10 | 0.136420E+10 | 0.159685E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.143017E+10 | 0.132199E+10 | 0.999569E+09 | 0.287085E+09 | 0.712484E+09 | 0.00 | 0.00 |
February | 0.163421E+10 | 0.994016E+09 | 0.103095E+10 | 0.293985E+09 | 0.736963E+09 | 0.00 | 0.00 |
March | 0.243612E+10 | 0.844369E+09 | 0.135203E+10 | 0.400272E+09 | 0.951758E+09 | 0.00 | 0.00 |
April | 0.299317E+10 | 0.523972E+09 | 0.142987E+10 | 0.401718E+09 | 0.102816E+10 | 0.00 | 0.00 |
May | 0.411994E+10 | 0.144712E+09 | 0.160829E+10 | 0.481426E+09 | 0.112687E+10 | 0.00 | 0.00 |
June | 0.438019E+10 | 32735068.71 | 0.160842E+10 | 0.507017E+09 | 0.110140E+10 | 0.00 | 0.00 |
July | 0.481571E+10 | 691822.31 | 0.152474E+10 | 0.436197E+09 | 0.108854E+10 | 0.00 | 0.00 |
August | 0.496106E+10 | 216261.01 | 0.156421E+10 | 0.475587E+09 | 0.108862E+10 | 0.00 | 0.00 |
September | 0.393257E+10 | 51991726.64 | 0.143997E+10 | 0.452397E+09 | 0.987572E+09 | 0.00 | 0.00 |
October | 0.314624E+10 | 0.233190E+09 | 0.132237E+10 | 0.427161E+09 | 0.895206E+09 | 0.00 | 0.00 |
November | 0.219405E+10 | 0.600256E+09 | 0.109975E+10 | 0.359654E+09 | 0.740098E+09 | 0.00 | 0.00 |
December | 0.152168E+10 | 0.108637E+10 | 0.951354E+09 | 0.287577E+09 | 0.663776E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.375651E+11 | 0.583451E+10 | 0.159315E+11 | 0.481008E+10 | 0.111214E+11 | 0.00 | 0.00 |
Minimum of Months | 0.143017E+10 | 216261.01 | 0.951354E+09 | 0.287085E+09 | 0.663776E+09 | 0.00 | 0.00 |
Maximum of Months | 0.496106E+10 | 0.132199E+10 | 0.160842E+10 | 0.507017E+09 | 0.112687E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.390603E+10 | -0.321808E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687949508.6 | 58.98 | 0.00 | 0.00 |
February | 0.346404E+10 | -0.284293E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -621111629.5 | 58.98 | 0.00 | 0.00 |
March | 0.381562E+10 | -0.312694E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688684943.3 | 58.98 | 0.00 | 0.00 |
April | 0.319321E+10 | -0.252825E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -664953548.2 | 58.98 | 0.00 | 0.00 |
May | 0.310332E+10 | -0.241536E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687961202.9 | 58.98 | 0.00 | 0.00 |
June | 0.284898E+10 | -0.218186E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667125531.7 | 58.98 | 0.00 | 0.00 |
July | 0.268371E+10 | -0.199169E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692023120.7 | 58.98 | 0.00 | 0.00 |
August | 0.299853E+10 | -0.230388E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -694641389.9 | 58.98 | 0.00 | 0.00 |
September | 0.296470E+10 | -0.229722E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667486853.7 | 58.98 | 0.00 | 0.00 |
October | 0.335501E+10 | -0.266769E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687314995.5 | 58.97 | 0.00 | 0.00 |
November | 0.356828E+10 | -0.290453E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -663753057.7 | 58.98 | 0.00 | 0.00 |
December | 0.375741E+10 | -0.307022E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687190279.6 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.396588E+11 | -0.315487E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.811020E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.268371E+10 | -0.321808E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -694641389.9 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.390603E+10 | -0.199169E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -621111629.5 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-07:00 | 4165.40 | 34.10 | 310.83 | 292.67 | 1091.39 | 24.99 | 288.50 | 280.50 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-08:09 | 2142.31 | 24.98 | 142.00 | 274.00 | 971.87 | 20.80 | 176.33 | 243.83 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1573.30 | 18.39 | 5.00 | 313.33 | 824.91 | 20.36 | 144.83 | 276.83 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:40 | 1224.30 | 17.39 | 0.00 | 321.50 | 653.43 | 19.46 | 84.17 | 283.50 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:10 | 1037.58 | 17.33 | 0.00 | 348.00 | 572.30 | 19.45 | 16.50 | 303.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-07:10 | 992.35 | 17.23 | 0.00 | 343.50 | 556.25 | 19.40 | 7.50 | 296.33 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-07:10 | 1043.82 | 17.15 | 0.00 | 343.50 | 578.05 | 19.30 | 41.00 | 302.50 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:10 | 1228.01 | 17.65 | 0.00 | 342.67 | 663.58 | 19.78 | 132.83 | 302.83 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:19 | 1542.23 | 18.38 | 0.00 | 318.17 | 820.60 | 20.53 | 187.67 | 284.00 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-07:19 | 2072.38 | 20.36 | 34.50 | 317.00 | 996.12 | 21.43 | 230.50 | 287.83 |
November | 318.83 | 0.49 | 0.48 | 01-NOV-07:10 | 3503.94 | 31.74 | 256.33 | 297.50 | 1130.97 | 24.83 | 300.33 | 282.00 |
December | 319.00 | 0.50 | 0.48 | 01-DEC-07:19 | 4154.16 | 34.47 | 307.00 | 288.50 | 1165.61 | 26.17 | 287.67 | 275.33 |
Annual Sum or Average | 4323.33 | 0.52 | 1963.57 | 21.89 | 1055.67 | 3800.33 | 815.15 | 21.19 | 1897.83 | 3418.50 | ||
Minimum of Months | 308.33 | 0.49 | 0.48 | 992.35 | 17.15 | 0.00 | 274.00 | 556.25 | 19.30 | 7.50 | 243.83 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 4165.40 | 34.47 | 310.83 | 348.00 | 1165.61 | 26.17 | 300.33 | 303.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.53 | 0.48 | 01-JAN-07:00 | 1512.95 | 21.78 | 111.83 | 272.33 | 798.35 | 22.49 | 80.67 | 233.83 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-07:40 | 1634.75 | 21.36 | 102.33 | 261.17 | 706.79 | 20.76 | 47.17 | 224.33 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-07:00 | 1522.54 | 19.17 | 83.83 | 306.33 | 787.26 | 21.37 | 66.00 | 268.00 |
April | 375.00 | 0.53 | 0.48 | 01-APR-06:00 | 1791.97 | 20.37 | 109.33 | 318.50 | 918.91 | 21.37 | 79.83 | 280.83 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:19 | 2023.85 | 20.25 | 118.83 | 355.33 | 865.64 | 20.92 | 67.83 | 318.83 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:10 | 1944.47 | 19.98 | 114.33 | 348.83 | 853.40 | 20.99 | 66.67 | 315.67 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:30 | 1835.56 | 19.90 | 114.17 | 347.17 | 814.98 | 20.64 | 61.83 | 309.67 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:30 | 1890.37 | 20.49 | 113.83 | 339.83 | 848.20 | 20.38 | 56.00 | 305.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-06:49 | 1884.22 | 21.34 | 107.00 | 310.00 | 975.28 | 22.34 | 77.33 | 283.00 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-06:49 | 1752.13 | 21.26 | 104.67 | 303.83 | 911.81 | 22.30 | 76.00 | 272.50 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1505.13 | 20.48 | 84.33 | 275.33 | 785.64 | 22.26 | 63.00 | 241.17 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-07:19 | 1246.09 | 20.33 | 85.50 | 267.17 | 628.02 | 20.91 | 50.67 | 222.67 |
Annual Sum or Average | 4323.33 | 0.52 | 1729.56 | 20.52 | 1250.00 | 3705.83 | 829.32 | 21.36 | 793.00 | 3276.00 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1246.09 | 19.17 | 83.83 | 261.17 | 628.02 | 20.38 | 47.17 | 222.67 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 2023.85 | 21.78 | 118.83 | 355.33 | 975.28 | 22.49 | 80.67 | 318.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-09:39 | 581.30 | 15.19 | 0.00 | 258.00 | 336.26 | 17.33 | 0.00 | 172.67 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-08:50 | 661.11 | 16.04 | 0.00 | 251.67 | 381.33 | 18.17 | 0.00 | 188.67 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:50 | 771.41 | 16.70 | 0.00 | 305.17 | 438.69 | 18.78 | 0.00 | 252.67 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 884.53 | 17.02 | 0.00 | 325.50 | 496.49 | 19.04 | 0.00 | 285.17 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:49 | 1043.93 | 18.04 | 2.83 | 367.83 | 578.21 | 20.12 | 54.83 | 333.33 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:19 | 1155.84 | 21.18 | 77.67 | 366.00 | 631.89 | 21.73 | 157.00 | 336.83 |
July | 405.00 | 0.51 | 0.48 | 01-JUL-06:49 | 1117.31 | 19.00 | 27.00 | 357.33 | 611.95 | 21.14 | 128.50 | 327.00 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:00 | 1010.71 | 17.69 | 0.00 | 348.83 | 566.63 | 19.81 | 53.33 | 315.00 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:19 | 880.62 | 17.38 | 0.00 | 316.67 | 505.49 | 19.49 | 0.00 | 273.17 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-07:40 | 727.75 | 16.49 | 0.00 | 298.33 | 427.45 | 18.63 | 0.00 | 245.33 |
November | 318.83 | 0.53 | 0.48 | 01-NOV-07:00 | 630.06 | 16.11 | 0.00 | 260.33 | 371.49 | 18.32 | 0.00 | 193.83 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:39 | 563.66 | 15.28 | 0.00 | 247.33 | 326.72 | 17.46 | 0.00 | 150.17 |
Annual Sum or Average | 4323.33 | 0.52 | 854.57 | 17.31 | 107.50 | 3703.00 | 482.38 | 19.28 | 393.67 | 3073.83 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 563.66 | 15.19 | 0.00 | 247.33 | 326.72 | 17.33 | 0.00 | 150.17 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1155.84 | 21.18 | 77.67 | 367.83 | 631.89 | 21.73 | 157.00 | 336.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.53 | 0.48 | 01-JAN-09:39 | 1465.81 | 21.39 | 108.17 | 273.17 | 766.99 | 22.11 | 77.17 | 233.00 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-09:09 | 1434.95 | 19.78 | 76.33 | 260.33 | 728.09 | 20.67 | 48.33 | 222.00 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:00 | 1636.32 | 19.43 | 85.83 | 307.67 | 840.51 | 21.39 | 65.67 | 270.00 |
April | 375.00 | 0.52 | 0.48 | 01-APR-08:20 | 1662.92 | 16.77 | 55.00 | 322.67 | 867.51 | 17.26 | 0.00 | 285.17 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:40 | 1747.35 | 14.42 | 0.00 | 348.83 | 904.71 | 17.57 | 0.00 | 311.67 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-07:30 | 1856.25 | 14.60 | 0.00 | 345.17 | 827.69 | 17.77 | 0.00 | 310.17 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:40 | 1777.71 | 14.63 | 3.67 | 346.83 | 809.63 | 17.55 | 0.00 | 307.83 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:40 | 1815.78 | 17.24 | 59.83 | 342.00 | 941.08 | 17.96 | 5.50 | 306.67 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:00 | 1746.04 | 19.75 | 86.83 | 316.33 | 908.86 | 20.82 | 57.33 | 283.67 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:00 | 1815.24 | 21.42 | 107.83 | 301.67 | 945.05 | 22.46 | 79.33 | 271.33 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-08:09 | 1562.64 | 20.44 | 85.00 | 275.50 | 820.26 | 22.58 | 69.00 | 242.50 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-08:39 | 1365.77 | 19.99 | 87.33 | 266.83 | 716.56 | 22.16 | 71.17 | 225.33 |
Annual Sum or Average | 4323.33 | 0.52 | 1670.30 | 18.11 | 755.83 | 3707.00 | 843.97 | 19.85 | 473.50 | 3269.33 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1365.77 | 14.42 | 0.00 | 260.33 | 716.56 | 17.26 | 0.00 | 222.00 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 1856.25 | 21.42 | 108.17 | 348.83 | 945.05 | 22.58 | 79.33 | 311.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-07:00 | 4068.03 | 33.81 | 310.17 | 292.00 | 1023.94 | 22.66 | 91.67 | 279.50 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-08:09 | 2054.96 | 22.69 | 141.00 | 272.50 | 911.34 | 17.89 | 0.00 | 241.67 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1505.18 | 14.49 | 5.00 | 311.33 | 779.07 | 17.71 | 0.00 | 273.33 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:40 | 1176.28 | 13.72 | 0.00 | 320.50 | 623.12 | 17.04 | 0.00 | 280.33 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:19 | 999.17 | 13.73 | 0.00 | 345.67 | 549.41 | 17.13 | 0.00 | 299.00 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-07:10 | 955.80 | 13.56 | 0.00 | 342.33 | 534.82 | 17.03 | 0.00 | 294.17 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-07:10 | 1005.19 | 13.42 | 0.00 | 342.67 | 555.15 | 16.83 | 0.00 | 297.67 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:19 | 1180.43 | 14.00 | 0.00 | 341.67 | 634.30 | 17.39 | 0.00 | 299.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:19 | 1477.18 | 14.67 | 0.00 | 317.17 | 777.94 | 18.09 | 0.00 | 281.50 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-07:19 | 1985.91 | 16.78 | 34.50 | 316.17 | 935.96 | 18.92 | 10.67 | 284.83 |
November | 318.83 | 0.50 | 0.48 | 01-NOV-07:10 | 3403.96 | 30.74 | 255.67 | 296.17 | 1059.69 | 22.44 | 76.67 | 280.50 |
December | 319.00 | 0.50 | 0.48 | 01-DEC-07:30 | 4055.16 | 34.23 | 306.00 | 287.50 | 1096.76 | 24.01 | 113.17 | 274.33 |
Annual Sum or Average | 4323.33 | 0.52 | 1898.14 | 19.01 | 1052.33 | 3785.67 | 771.61 | 18.75 | 292.17 | 3386.33 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 955.80 | 13.42 | 0.00 | 272.50 | 534.82 | 16.83 | 0.00 | 241.67 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 4068.03 | 34.23 | 310.17 | 345.67 | 1096.76 | 24.01 | 113.17 | 299.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.53 | 0.48 | 01-JAN-07:00 | 1470.74 | 21.32 | 111.83 | 271.00 | 767.44 | 22.27 | 80.83 | 229.33 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-07:40 | 1591.03 | 20.90 | 102.33 | 259.33 | 674.70 | 20.54 | 47.17 | 221.83 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-07:00 | 1479.80 | 18.68 | 83.83 | 303.50 | 753.22 | 21.17 | 66.00 | 264.00 |
April | 375.00 | 0.53 | 0.48 | 01-APR-06:00 | 1737.78 | 19.93 | 109.33 | 316.33 | 881.83 | 21.20 | 79.83 | 277.67 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-06:19 | 1969.22 | 19.81 | 118.83 | 354.33 | 818.82 | 19.93 | 57.33 | 312.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:10 | 1898.13 | 19.53 | 114.33 | 347.17 | 814.52 | 20.80 | 66.33 | 312.17 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:40 | 1786.50 | 19.47 | 114.17 | 345.33 | 775.26 | 19.67 | 52.50 | 306.17 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:30 | 1829.23 | 20.06 | 113.67 | 338.17 | 808.87 | 20.21 | 56.00 | 303.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-06:49 | 1830.64 | 20.73 | 105.17 | 308.67 | 935.55 | 22.16 | 77.33 | 280.17 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-06:49 | 1679.74 | 19.29 | 87.83 | 301.83 | 873.61 | 22.11 | 76.00 | 268.67 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1458.94 | 19.98 | 84.33 | 273.33 | 750.98 | 22.03 | 63.00 | 237.33 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-07:19 | 1207.63 | 19.83 | 85.17 | 264.83 | 599.92 | 20.66 | 50.67 | 218.00 |
Annual Sum or Average | 4323.33 | 0.52 | 1678.82 | 19.93 | 1230.83 | 3683.83 | 792.31 | 21.02 | 773.00 | 3230.83 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1207.63 | 18.68 | 83.83 | 259.33 | 599.92 | 19.67 | 47.17 | 218.00 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 1969.22 | 21.32 | 118.83 | 354.33 | 935.55 | 22.27 | 80.83 | 312.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.55 | 0.48 | 01-JAN-09:50 | 560.47 | 11.54 | 0.00 | 253.50 | 324.54 | 15.00 | 0.00 | 160.00 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-08:50 | 637.65 | 12.30 | 0.00 | 250.00 | 368.10 | 15.80 | 0.00 | 182.00 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:50 | 744.27 | 13.02 | 0.00 | 302.50 | 423.19 | 16.46 | 0.00 | 246.00 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:40 | 852.99 | 13.47 | 0.00 | 324.00 | 478.20 | 16.82 | 0.00 | 280.83 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:49 | 1005.79 | 14.40 | 2.83 | 366.33 | 555.59 | 17.84 | 1.17 | 328.17 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:30 | 1112.67 | 18.32 | 77.33 | 363.00 | 605.82 | 19.53 | 34.17 | 333.50 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:49 | 1075.97 | 15.54 | 26.83 | 356.33 | 587.19 | 18.86 | 27.33 | 324.17 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:00 | 973.41 | 14.11 | 0.00 | 347.50 | 544.82 | 17.55 | 0.00 | 310.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:19 | 848.55 | 13.94 | 0.00 | 315.00 | 487.17 | 17.35 | 0.00 | 270.33 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-07:40 | 701.31 | 13.04 | 0.00 | 295.83 | 412.65 | 16.51 | 0.00 | 239.67 |
November | 318.83 | 0.53 | 0.48 | 01-NOV-07:00 | 606.97 | 12.51 | 0.00 | 256.67 | 358.64 | 16.09 | 0.00 | 184.33 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:39 | 543.18 | 11.51 | 0.00 | 243.50 | 315.21 | 15.05 | 0.00 | 136.67 |
Annual Sum or Average | 4323.33 | 0.52 | 823.44 | 13.78 | 107.00 | 3674.17 | 464.30 | 17.02 | 62.67 | 2996.17 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 543.18 | 11.51 | 0.00 | 243.50 | 315.21 | 15.00 | 0.00 | 136.67 | |
Maximum of Months | 405.33 | 0.55 | 0.48 | 1112.67 | 18.32 | 77.33 | 366.33 | 605.82 | 19.53 | 34.17 | 333.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.53 | 0.48 | 01-JAN-09:39 | 1424.55 | 21.01 | 108.17 | 271.00 | 736.54 | 22.00 | 77.17 | 228.67 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-09:09 | 1389.30 | 19.36 | 76.33 | 258.83 | 694.80 | 20.55 | 48.33 | 218.17 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:00 | 1589.53 | 18.99 | 85.83 | 306.50 | 802.73 | 21.27 | 65.83 | 265.67 |
April | 375.00 | 0.53 | 0.48 | 01-APR-08:20 | 1592.86 | 16.29 | 55.00 | 320.17 | 830.02 | 17.08 | 0.00 | 282.50 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:49 | 1691.85 | 13.87 | 0.00 | 347.83 | 866.89 | 17.36 | 0.00 | 309.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-07:40 | 1808.08 | 14.05 | 0.00 | 343.50 | 788.43 | 17.56 | 0.00 | 306.17 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:40 | 1726.20 | 14.08 | 3.67 | 345.00 | 772.28 | 17.34 | 0.00 | 304.50 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:40 | 1754.23 | 16.76 | 59.83 | 339.83 | 901.70 | 17.77 | 5.50 | 304.33 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:00 | 1695.99 | 19.32 | 86.83 | 314.33 | 868.51 | 20.68 | 57.33 | 280.83 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-08:09 | 1764.55 | 21.02 | 107.83 | 300.00 | 907.15 | 22.34 | 79.33 | 268.33 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-08:20 | 1515.72 | 20.01 | 85.00 | 273.17 | 785.33 | 22.47 | 69.00 | 239.83 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-08:50 | 1324.36 | 19.56 | 87.33 | 264.83 | 686.01 | 22.05 | 71.33 | 222.00 |
Annual Sum or Average | 4323.33 | 0.52 | 1619.05 | 17.64 | 755.83 | 3685.00 | 807.36 | 19.69 | 473.83 | 3230.00 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1324.36 | 13.87 | 0.00 | 258.83 | 686.01 | 17.08 | 0.00 | 218.17 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 1808.08 | 21.02 | 108.17 | 347.83 | 907.15 | 22.47 | 79.33 | 309.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-07:00 | 4067.94 | 33.81 | 310.17 | 292.00 | 1023.85 | 22.66 | 91.67 | 279.50 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-08:09 | 2054.84 | 22.70 | 141.00 | 272.50 | 911.26 | 17.89 | 0.00 | 241.67 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1505.07 | 14.49 | 5.00 | 311.33 | 779.00 | 17.71 | 0.00 | 273.33 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:40 | 1176.20 | 13.72 | 0.00 | 320.50 | 623.06 | 17.04 | 0.00 | 280.33 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:19 | 999.11 | 13.73 | 0.00 | 345.67 | 549.37 | 17.13 | 0.00 | 299.00 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-07:10 | 955.75 | 13.56 | 0.00 | 342.33 | 534.78 | 17.03 | 0.00 | 294.17 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-07:10 | 1005.13 | 13.42 | 0.00 | 342.67 | 555.10 | 16.83 | 0.00 | 297.50 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:19 | 1180.36 | 14.00 | 0.00 | 341.67 | 634.24 | 17.39 | 0.00 | 299.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:19 | 1477.08 | 14.67 | 0.00 | 317.17 | 777.87 | 18.10 | 0.00 | 281.50 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-07:19 | 1985.79 | 16.78 | 34.50 | 316.17 | 935.88 | 18.92 | 10.67 | 284.83 |
November | 318.83 | 0.50 | 0.48 | 01-NOV-07:10 | 3403.85 | 30.74 | 255.67 | 296.17 | 1059.59 | 22.44 | 76.67 | 280.50 |
December | 319.00 | 0.50 | 0.48 | 01-DEC-07:30 | 4055.08 | 34.23 | 306.00 | 287.50 | 1096.67 | 24.01 | 113.17 | 274.33 |
Annual Sum or Average | 4323.33 | 0.52 | 1898.05 | 19.01 | 1052.33 | 3785.67 | 771.54 | 18.75 | 292.17 | 3386.17 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 955.75 | 13.42 | 0.00 | 272.50 | 534.78 | 16.83 | 0.00 | 241.67 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 4067.94 | 34.23 | 310.17 | 345.67 | 1096.67 | 24.01 | 113.17 | 299.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.53 | 0.48 | 01-JAN-07:00 | 1470.69 | 21.32 | 111.83 | 271.00 | 767.39 | 22.27 | 80.83 | 229.33 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-07:40 | 1590.97 | 20.90 | 102.33 | 259.33 | 674.64 | 20.54 | 47.17 | 221.83 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-07:00 | 1479.74 | 18.68 | 83.83 | 303.50 | 753.16 | 21.17 | 66.00 | 264.00 |
April | 375.00 | 0.53 | 0.48 | 01-APR-06:00 | 1737.71 | 19.93 | 109.33 | 316.33 | 881.78 | 21.20 | 79.83 | 277.67 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-06:19 | 1969.15 | 19.81 | 118.83 | 354.33 | 818.76 | 19.93 | 57.33 | 312.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:10 | 1898.06 | 19.53 | 114.33 | 347.17 | 814.47 | 20.80 | 66.33 | 312.17 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:40 | 1786.43 | 19.47 | 114.17 | 345.33 | 775.20 | 19.67 | 52.50 | 306.17 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:30 | 1829.16 | 20.06 | 113.67 | 338.17 | 808.81 | 20.22 | 56.00 | 303.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-06:49 | 1830.57 | 20.73 | 105.17 | 308.67 | 935.49 | 22.16 | 77.33 | 280.17 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-06:49 | 1679.69 | 19.30 | 87.83 | 301.83 | 873.56 | 22.11 | 76.00 | 268.67 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1458.89 | 19.98 | 84.33 | 273.33 | 750.93 | 22.03 | 63.00 | 237.33 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-07:19 | 1207.59 | 19.83 | 85.33 | 264.83 | 599.87 | 20.66 | 50.67 | 218.00 |
Annual Sum or Average | 4323.33 | 0.52 | 1678.76 | 19.93 | 1231.00 | 3683.83 | 792.26 | 21.02 | 773.00 | 3230.83 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1207.59 | 18.68 | 83.83 | 259.33 | 599.87 | 19.67 | 47.17 | 218.00 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 1969.15 | 21.32 | 118.83 | 354.33 | 935.49 | 22.27 | 80.83 | 312.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.55 | 0.48 | 01-JAN-09:50 | 560.45 | 11.54 | 0.00 | 253.50 | 324.52 | 15.00 | 0.00 | 160.00 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-08:50 | 637.62 | 12.30 | 0.00 | 250.00 | 368.07 | 15.80 | 0.00 | 182.00 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:50 | 744.23 | 13.02 | 0.00 | 302.50 | 423.15 | 16.46 | 0.00 | 246.00 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:40 | 852.95 | 13.47 | 0.00 | 324.00 | 478.16 | 16.82 | 0.00 | 280.83 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:49 | 1005.74 | 14.40 | 2.83 | 366.33 | 555.55 | 17.84 | 1.17 | 328.17 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:30 | 1112.61 | 18.32 | 77.33 | 363.00 | 605.77 | 19.53 | 34.17 | 333.50 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:49 | 1075.91 | 15.54 | 26.83 | 356.33 | 587.15 | 18.86 | 27.33 | 324.17 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:00 | 973.36 | 14.11 | 0.00 | 347.50 | 544.78 | 17.55 | 0.00 | 310.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:19 | 848.52 | 13.94 | 0.00 | 315.00 | 487.14 | 17.35 | 0.00 | 270.33 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-07:40 | 701.28 | 13.05 | 0.00 | 295.83 | 412.62 | 16.51 | 0.00 | 239.67 |
November | 318.83 | 0.53 | 0.48 | 01-NOV-07:00 | 606.95 | 12.51 | 0.00 | 256.67 | 358.61 | 16.09 | 0.00 | 184.33 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:39 | 543.16 | 11.51 | 0.00 | 243.50 | 315.19 | 15.05 | 0.00 | 136.50 |
Annual Sum or Average | 4323.33 | 0.52 | 823.40 | 13.79 | 107.00 | 3674.17 | 464.26 | 17.02 | 62.67 | 2996.00 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 543.16 | 11.51 | 0.00 | 243.50 | 315.19 | 15.00 | 0.00 | 136.50 | |
Maximum of Months | 405.33 | 0.55 | 0.48 | 1112.61 | 18.32 | 77.33 | 366.33 | 605.77 | 19.53 | 34.17 | 333.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.53 | 0.48 | 01-JAN-09:39 | 1424.51 | 21.01 | 108.17 | 271.00 | 736.49 | 22.00 | 77.17 | 228.67 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-09:09 | 1389.24 | 19.36 | 76.33 | 258.83 | 694.75 | 20.55 | 48.33 | 218.17 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:00 | 1589.47 | 18.99 | 85.83 | 306.50 | 802.67 | 21.27 | 65.83 | 265.67 |
April | 375.00 | 0.53 | 0.48 | 01-APR-08:20 | 1592.79 | 16.29 | 55.00 | 320.17 | 829.96 | 17.08 | 0.00 | 282.50 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:49 | 1691.78 | 13.87 | 0.00 | 347.83 | 866.84 | 17.36 | 0.00 | 309.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-07:40 | 1808.01 | 14.05 | 0.00 | 343.50 | 788.37 | 17.56 | 0.00 | 306.17 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:40 | 1726.12 | 14.09 | 3.67 | 345.00 | 772.22 | 17.34 | 0.00 | 304.50 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:40 | 1754.16 | 16.76 | 59.83 | 339.83 | 901.64 | 17.77 | 5.50 | 304.33 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:00 | 1695.93 | 19.32 | 86.83 | 314.33 | 868.45 | 20.68 | 57.33 | 280.83 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-08:09 | 1764.50 | 21.02 | 107.83 | 300.00 | 907.09 | 22.34 | 79.33 | 268.33 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-08:20 | 1515.67 | 20.01 | 85.00 | 273.17 | 785.28 | 22.47 | 69.00 | 239.83 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-08:50 | 1324.31 | 19.56 | 87.33 | 264.83 | 685.96 | 22.05 | 71.33 | 221.83 |
Annual Sum or Average | 4323.33 | 0.52 | 1618.99 | 17.64 | 755.83 | 3685.00 | 807.30 | 19.69 | 473.83 | 3229.83 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1324.31 | 13.87 | 0.00 | 258.83 | 685.96 | 17.08 | 0.00 | 218.17 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 1808.01 | 21.02 | 108.17 | 347.83 | 907.09 | 22.47 | 79.33 | 309.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.185426E+09 | 4493.89 | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120226E+09 | 4493.89 | 01-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 44584899.15 | 4493.89 | 07-MAR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 701756.46 | 1487.88 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 41152566.14 | 4493.89 | 18-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.392091E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.185426E+09 | 4493.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.393192E+11 | 0.337498E+11 | 62212.15 | 30-JAN-07:03 | 48839.88 | 0.00 |
February | 0.00 | 0.00 | 0.421885E+11 | 0.355716E+11 | 75569.16 | 06-FEB-06:12 | 51510.58 | 0.00 |
March | 0.00 | 0.00 | 0.568526E+11 | 0.496804E+11 | 81542.55 | 28-MAR-11:40 | 57289.43 | 0.00 |
April | 0.00 | 0.00 | 0.683259E+11 | 0.581400E+11 | 90992.28 | 10-APR-12:00 | 58259.55 | 0.00 |
May | 0.00 | 0.00 | 0.103560E+12 | 0.853408E+11 | 139406.13 | 31-MAY-04:02 | 86771.47 | 0.00 |
June | 0.00 | 0.00 | 0.126080E+12 | 0.922569E+11 | 144013.73 | 14-JUN-04:03 | 76269.03 | 0.00 |
July | 0.00 | 0.00 | 0.153908E+12 | 0.102522E+12 | 141844.45 | 06-JUL-04:02 | 81901.04 | 0.00 |
August | 0.00 | 0.00 | 0.171448E+12 | 0.112112E+12 | 141948.54 | 26-AUG-04:02 | 80780.42 | 0.00 |
September | 0.00 | 0.00 | 0.136687E+12 | 0.922907E+11 | 142895.71 | 28-SEP-04:02 | 78996.77 | 0.00 |
October | 0.00 | 0.00 | 0.109762E+12 | 0.823286E+11 | 141144.59 | 18-OCT-04:03 | 78566.56 | 0.00 |
November | 0.00 | 0.00 | 0.784051E+11 | 0.630612E+11 | 137441.31 | 02-NOV-06:03 | 86432.76 | 0.00 |
December | 0.00 | 0.00 | 0.502914E+11 | 0.416582E+11 | 89407.71 | 11-DEC-07:03 | 68697.09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.113683E+13 | 0.848712E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.393192E+11 | 0.337498E+11 | 62212.15 | 48839.88 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.171448E+12 | 0.112112E+12 | 144013.73 | 86771.47 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.285413E+11 | 0.228256E+11 | 44306.12 | 30-JAN-14:00 | 31849.06 | 0.00 |
February | 0.00 | 0.00 | 0.328851E+11 | 0.264240E+11 | 64557.96 | 07-FEB-15:05 | 48981.24 | 0.00 |
March | 0.00 | 0.00 | 0.468932E+11 | 0.399342E+11 | 67806.82 | 27-MAR-14:05 | 67806.82 | 0.00 |
April | 0.00 | 0.00 | 0.593180E+11 | 0.498547E+11 | 111632.94 | 30-APR-15:13 | 65125.95 | 0.00 |
May | 0.00 | 0.00 | 0.917880E+11 | 0.755952E+11 | 129600.60 | 24-MAY-05:03 | 65514.24 | 0.00 |
June | 0.00 | 0.00 | 0.112050E+12 | 0.811252E+11 | 132084.44 | 14-JUN-04:03 | 66107.86 | 0.00 |
July | 0.00 | 0.00 | 0.136234E+12 | 0.908486E+11 | 131225.28 | 06-JUL-04:02 | 68959.79 | 0.00 |
August | 0.00 | 0.00 | 0.146519E+12 | 0.967216E+11 | 130705.45 | 09-AUG-04:02 | 68592.74 | 0.00 |
September | 0.00 | 0.00 | 0.114385E+12 | 0.772507E+11 | 131346.16 | 28-SEP-04:02 | 67226.71 | 0.00 |
October | 0.00 | 0.00 | 0.883668E+11 | 0.662339E+11 | 129979.31 | 07-OCT-05:03 | 66123.31 | 0.00 |
November | 0.00 | 0.00 | 0.603037E+11 | 0.473580E+11 | 96580.00 | 03-NOV-05:03 | 52286.01 | 0.00 |
December | 0.00 | 0.00 | 0.374783E+11 | 0.290607E+11 | 62703.45 | 05-DEC-15:05 | 42929.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.954762E+12 | 0.703232E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.285413E+11 | 0.228256E+11 | 44306.12 | 31849.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.146519E+12 | 0.967216E+11 | 132084.44 | 68959.79 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.278785E+11 | 0.214807E+11 | 44073.48 | 30-JAN-14:10 | 32098.02 | 0.00 |
February | 0.00 | 0.00 | 0.332198E+11 | 0.262449E+11 | 68100.72 | 07-FEB-15:30 | 52117.87 | 0.00 |
March | 0.00 | 0.00 | 0.488189E+11 | 0.411828E+11 | 74883.87 | 27-MAR-13:10 | 74883.87 | 0.00 |
April | 0.00 | 0.00 | 0.633652E+11 | 0.532593E+11 | 95470.85 | 30-APR-12:13 | 85959.05 | 0.00 |
May | 0.00 | 0.00 | 0.997792E+11 | 0.828474E+11 | 145751.11 | 31-MAY-04:02 | 86939.90 | 0.00 |
June | 0.00 | 0.00 | 0.122468E+12 | 0.901705E+11 | 151045.14 | 14-JUN-04:03 | 71275.72 | 0.00 |
July | 0.00 | 0.00 | 0.149994E+12 | 0.102018E+12 | 149245.98 | 06-JUL-04:02 | 81458.15 | 0.00 |
August | 0.00 | 0.00 | 0.159555E+12 | 0.107552E+12 | 149027.35 | 26-AUG-04:02 | 80660.59 | 0.00 |
September | 0.00 | 0.00 | 0.122735E+12 | 0.843490E+11 | 150680.07 | 28-SEP-04:02 | 76264.45 | 0.00 |
October | 0.00 | 0.00 | 0.922635E+11 | 0.696511E+11 | 146147.93 | 02-OCT-04:02 | 85913.59 | 0.00 |
November | 0.00 | 0.00 | 0.612708E+11 | 0.478526E+11 | 104379.62 | 03-NOV-05:03 | 54990.08 | 0.00 |
December | 0.00 | 0.00 | 0.370805E+11 | 0.279522E+11 | 63420.10 | 05-DEC-15:00 | 44168.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.101843E+13 | 0.754561E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.278785E+11 | 0.214807E+11 | 44073.48 | 32098.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.159555E+12 | 0.107552E+12 | 151045.14 | 86939.90 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1355.48 | 4624.87 | 12-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1329.47 | 4577.82 | 01-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1325.34 | 4371.37 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1129.96 | 3955.30 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 1059.05 | 3584.74 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 1000.04 | 3263.17 | 01-JUN-11:09 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 897.65 | 3085.76 | 31-JUL-11:18 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 1019.47 | 3308.27 | 31-AUG-11:18 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 1041.20 | 3660.38 | 29-SEP-11:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1150.02 | 4066.09 | 31-OCT-11:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1275.76 | 4402.98 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1298.82 | 4584.11 | 28-DEC-12:40 |
Annual Sum or Average | 0.00 | 1155.93 | ||||
Minimum of Months | 0.00 | 0.00 | 897.65 | 3085.76 | ||
Maximum of Months | 0.00 | 0.00 | 1355.48 | 4624.87 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.287085E+10 | 0.36 | 4847.46 | 23-JAN-13:30 | 1.01 |
February | 0.288275E+10 | 0.37 | 6417.77 | 06-FEB-13:10 | 1.20 |
March | 0.384989E+10 | 0.42 | 8350.89 | 27-MAR-12:09 | 1.42 |
April | 0.435726E+10 | 0.46 | 9485.58 | 24-APR-12:20 | 1.54 |
May | 0.660887E+10 | 0.59 | 11882.44 | 08-MAY-04:02 | 1.77 |
June | 0.710508E+10 | 0.64 | 11882.44 | 01-JUN-04:02 | 1.77 |
July | 0.708732E+10 | 0.67 | 11882.44 | 01-JUL-04:02 | 1.76 |
August | 0.750334E+10 | 0.70 | 11882.44 | 01-AUG-06:03 | 1.77 |
September | 0.633462E+10 | 0.61 | 11882.44 | 01-SEP-04:02 | 1.77 |
October | 0.587616E+10 | 0.56 | 11882.44 | 02-OCT-06:03 | 1.77 |
November | 0.499000E+10 | 0.49 | 11882.44 | 20-NOV-05:02 | 1.77 |
December | 0.346476E+10 | 0.39 | 6613.05 | 11-DEC-07:03 | 1.22 |
Annual Sum or Average | 0.629309E+11 | 0.52 | |||
Minimum of Months | 0.287085E+10 | 0.36 | 4847.46 | 1.01 | |
Maximum of Months | 0.750334E+10 | 0.70 | 11882.44 | 1.77 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.185721E+10 | 0.32 | 3192.96 | 23-JAN-13:30 | 0.86 |
February | 0.204904E+10 | 0.35 | 5893.62 | 06-FEB-15:05 | 1.24 |
March | 0.301123E+10 | 0.40 | 9412.83 | 02-MAR-07:03 | 1.66 |
April | 0.361017E+10 | 0.44 | 8205.62 | 28-APR-12:02 | 1.53 |
May | 0.577606E+10 | 0.58 | 10494.09 | 11-MAY-04:02 | 1.78 |
June | 0.630813E+10 | 0.63 | 10494.09 | 05-JUN-06:03 | 1.78 |
July | 0.671556E+10 | 0.67 | 10494.09 | 01-JUL-04:02 | 1.77 |
August | 0.746990E+10 | 0.71 | 10494.09 | 01-AUG-06:03 | 1.78 |
September | 0.597031E+10 | 0.60 | 10494.09 | 01-SEP-04:02 | 1.78 |
October | 0.504790E+10 | 0.52 | 10494.09 | 02-OCT-04:02 | 1.78 |
November | 0.359633E+10 | 0.43 | 8369.62 | 13-NOV-07:03 | 1.54 |
December | 0.220179E+10 | 0.34 | 4753.42 | 04-DEC-13:05 | 1.08 |
Annual Sum or Average | 0.536136E+11 | 0.50 | |||
Minimum of Months | 0.185721E+10 | 0.32 | 3192.96 | 0.86 | |
Maximum of Months | 0.746990E+10 | 0.71 | 10494.09 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.170056E+10 | 0.33 | 2611.43 | 23-JAN-14:00 | 0.70 |
February | 0.188494E+10 | 0.35 | 4934.21 | 06-FEB-15:00 | 1.00 |
March | 0.279935E+10 | 0.38 | 7121.93 | 27-MAR-14:30 | 1.25 |
April | 0.343687E+10 | 0.42 | 7160.56 | 24-APR-14:00 | 1.25 |
May | 0.561352E+10 | 0.54 | 12407.84 | 31-MAY-04:02 | 1.76 |
June | 0.621820E+10 | 0.59 | 12407.84 | 19-JUN-04:02 | 1.76 |
July | 0.675844E+10 | 0.65 | 12407.84 | 01-JUL-04:02 | 1.76 |
August | 0.741864E+10 | 0.68 | 12407.84 | 09-AUG-04:02 | 1.76 |
September | 0.579052E+10 | 0.57 | 12407.84 | 01-SEP-04:02 | 1.77 |
October | 0.470549E+10 | 0.48 | 12407.84 | 02-OCT-04:02 | 1.76 |
November | 0.316135E+10 | 0.39 | 6285.90 | 06-NOV-14:10 | 1.15 |
December | 0.197030E+10 | 0.34 | 3804.03 | 04-DEC-14:10 | 0.85 |
Annual Sum or Average | 0.514582E+11 | 0.48 | |||
Minimum of Months | 0.170056E+10 | 0.33 | 2611.43 | 0.70 | |
Maximum of Months | 0.741864E+10 | 0.68 | 12407.84 | 1.77 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 57.36 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 57.20 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:05 | 2.06 | 2.06 | 56.32 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 57.73 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.07 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:10 | 2.06 | 2.06 | 57.14 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 57.30 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:05 | 2.06 | 2.06 | 58.25 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:05 | 2.06 | 2.06 | 57.66 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.25 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.17 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 56.92 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.32 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.25 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.06 | 58.06 | 1355.48 | 4624.87 | 12-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.48 | 57.48 | 1329.47 | 4577.82 | 01-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.60 | 56.60 | 1325.34 | 4371.37 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.96 | 57.96 | 1129.96 | 3955.30 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 57.07 | 57.07 | 1059.05 | 3584.74 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 57.23 | 57.23 | 1000.04 | 3263.17 | 01-JUN-11:09 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.59 | 58.59 | 897.65 | 3085.76 | 31-JUL-11:18 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 58.37 | 58.37 | 1019.47 | 3308.27 | 31-AUG-11:18 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 57.78 | 57.78 | 1041.20 | 3660.38 | 29-SEP-11:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.36 | 56.36 | 1150.02 | 4066.09 | 31-OCT-11:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.38 | 57.38 | 1275.76 | 4402.98 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.18 | 57.18 | 1298.82 | 4584.11 | 28-DEC-12:40 |
Annual Sum or Average | 0.00 | 1155.93 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.36 | 56.36 | 897.65 | 3085.76 | ||
Maximum of Months | 0.00 | 0.00 | 58.59 | 58.59 | 1355.48 | 4624.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.127470E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.134493E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.184153E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.226817E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.366776E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.439609E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.527962E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.585881E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.451291E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.356511E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.250474E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.158066E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.380950E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.127470E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.585881E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.907495E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.103461E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.151227E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.195385E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.322324E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.387190E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.468040E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.507745E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.381792E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.289276E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.190925E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.115684E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.320380E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.907495E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.507745E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.885771E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.103813E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.155560E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.206223E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.345327E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.417875E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.510215E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.547062E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.404728E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.298105E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.190746E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.113909E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.338214E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.885771E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.547062E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.287085E+10 | 0.393192E+11 | 0.185426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.288275E+10 | 0.421885E+11 | 0.120226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384989E+10 | 0.568526E+11 | 44584899.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.435726E+10 | 0.683259E+11 | 701756.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.660887E+10 | 0.103560E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.710508E+10 | 0.126080E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.708732E+10 | 0.153908E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.750334E+10 | 0.171448E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.633462E+10 | 0.136687E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587616E+10 | 0.109762E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.499000E+10 | 0.784051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.346476E+10 | 0.502914E+11 | 41152566.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.629309E+11 | 0.113683E+13 | 0.392091E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.287085E+10 | 0.393192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.750334E+10 | 0.171448E+12 | 0.185426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.185721E+10 | 0.285413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.204904E+10 | 0.328851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.301123E+10 | 0.468932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.361017E+10 | 0.593180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.577606E+10 | 0.917880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.630813E+10 | 0.112050E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.671556E+10 | 0.136234E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.746990E+10 | 0.146519E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.597031E+10 | 0.114385E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.504790E+10 | 0.883668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.359633E+10 | 0.603037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220179E+10 | 0.374783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.536136E+11 | 0.954762E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.185721E+10 | 0.285413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.746990E+10 | 0.146519E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.170056E+10 | 0.278785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.188494E+10 | 0.332198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.279935E+10 | 0.488189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.343687E+10 | 0.633652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.561352E+10 | 0.997792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.621820E+10 | 0.122468E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.675844E+10 | 0.149994E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.741864E+10 | 0.159555E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.579052E+10 | 0.122735E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.470549E+10 | 0.922635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316135E+10 | 0.612708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197030E+10 | 0.370805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.514582E+11 | 0.101843E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.170056E+10 | 0.278785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.741864E+10 | 0.159555E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.287085E+10 | 0.00 | 0.00 | 0.00 | 0.969071E+10 | 0.185426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.288275E+10 | 0.00 | 0.00 | 0.00 | 0.104464E+11 | 0.120226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384989E+10 | 0.00 | 0.00 | 0.00 | 0.145208E+11 | 44584899.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.435726E+10 | 0.00 | 0.00 | 0.00 | 0.183238E+11 | 701756.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.660887E+10 | 0.00 | 0.00 | 0.00 | 0.300688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.710508E+10 | 0.00 | 0.00 | 0.00 | 0.368558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.708732E+10 | 0.00 | 0.00 | 0.00 | 0.457089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.750334E+10 | 0.00 | 0.00 | 0.00 | 0.510847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.633462E+10 | 0.00 | 0.00 | 0.00 | 0.387945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587616E+10 | 0.00 | 0.00 | 0.00 | 0.297749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.499000E+10 | 0.00 | 0.00 | 0.00 | 0.200574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.346476E+10 | 0.00 | 0.00 | 0.00 | 0.123007E+11 | 41152566.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.629309E+11 | 0.00 | 0.00 | 0.00 | 0.317627E+12 | 0.392091E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.287085E+10 | 0.00 | 0.00 | 0.00 | 0.969071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.750334E+10 | 0.00 | 0.00 | 0.00 | 0.510847E+11 | 0.185426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.185721E+10 | 0.00 | 0.00 | 0.00 | 0.721775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.204904E+10 | 0.00 | 0.00 | 0.00 | 0.829704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.301123E+10 | 0.00 | 0.00 | 0.00 | 0.121114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.361017E+10 | 0.00 | 0.00 | 0.00 | 0.159284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.577606E+10 | 0.00 | 0.00 | 0.00 | 0.264563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.630813E+10 | 0.00 | 0.00 | 0.00 | 0.324109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.671556E+10 | 0.00 | 0.00 | 0.00 | 0.400885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.746990E+10 | 0.00 | 0.00 | 0.00 | 0.433046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.597031E+10 | 0.00 | 0.00 | 0.00 | 0.322089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.504790E+10 | 0.00 | 0.00 | 0.00 | 0.238797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.359633E+10 | 0.00 | 0.00 | 0.00 | 0.154962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220179E+10 | 0.00 | 0.00 | 0.00 | 0.936663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.536136E+11 | 0.00 | 0.00 | 0.00 | 0.266766E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.185721E+10 | 0.00 | 0.00 | 0.00 | 0.721775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.746990E+10 | 0.00 | 0.00 | 0.00 | 0.433046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.170056E+10 | 0.00 | 0.00 | 0.00 | 0.715714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.188494E+10 | 0.00 | 0.00 | 0.00 | 0.849638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.279935E+10 | 0.00 | 0.00 | 0.00 | 0.127567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.343687E+10 | 0.00 | 0.00 | 0.00 | 0.171855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.561352E+10 | 0.00 | 0.00 | 0.00 | 0.289192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.621820E+10 | 0.00 | 0.00 | 0.00 | 0.355693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.675844E+10 | 0.00 | 0.00 | 0.00 | 0.442631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.741864E+10 | 0.00 | 0.00 | 0.00 | 0.472875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.579052E+10 | 0.00 | 0.00 | 0.00 | 0.346823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.470549E+10 | 0.00 | 0.00 | 0.00 | 0.251050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316135E+10 | 0.00 | 0.00 | 0.00 | 0.159132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197030E+10 | 0.00 | 0.00 | 0.00 | 0.942060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.514582E+11 | 0.00 | 0.00 | 0.00 | 0.286756E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.170056E+10 | 0.00 | 0.00 | 0.00 | 0.715714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.741864E+10 | 0.00 | 0.00 | 0.00 | 0.472875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.241811E+09 | 0.312503E+09 | 0.00 | 37315228.81 | 0.134702E+09 | 0.00 | 0.366776E+10 | 0.00 | 0.41 |
February | 0.107669E+09 | 0.104635E+10 | 0.00 | 25782192.18 | 0.151904E+09 | 0.00 | 0.193414E+10 | 0.00 | 0.39 |
March | 0.103504E+09 | 0.209797E+10 | 0.00 | 23315481.37 | 0.202246E+09 | 0.00 | 0.152793E+10 | 0.00 | 0.40 |
April | 55606978.72 | 0.437355E+10 | 0.00 | 7610381.56 | 0.106584E+10 | 0.00 | 0.496343E+09 | 0.00 | 0.36 |
May | 19799535.54 | 0.883741E+10 | 0.00 | 1859592.23 | 0.278464E+10 | 0.00 | 71486606.11 | 0.00 | 0.35 |
June | 3623789.97 | 0.140221E+11 | 0.00 | 341993.13 | 0.460734E+10 | 0.00 | 12977823.82 | 0.00 | 0.36 |
July | 2912558.18 | 0.178492E+11 | 0.00 | 3293.84 | 0.993086E+10 | 0.00 | 230281.19 | 0.00 | 0.39 |
August | 0.00 | 0.204679E+11 | 0.00 | 0.00 | 0.993072E+10 | 0.00 | 0.00 | 0.00 | 0.40 |
September | 137685.65 | 0.155722E+11 | 0.00 | 94274.37 | 0.647467E+10 | 0.00 | 645702.69 | 0.00 | 0.36 |
October | 32598213.16 | 0.981173E+10 | 0.00 | 1261910.52 | 0.366221E+10 | 0.00 | 60144216.51 | 0.00 | 0.34 |
November | 17775397.57 | 0.520708E+10 | 0.00 | 4523114.13 | 0.838734E+09 | 0.00 | 0.125817E+09 | 0.00 | 0.33 |
December | 0.112476E+09 | 0.148530E+10 | 0.00 | 27159232.58 | 0.371548E+09 | 0.00 | 0.171648E+10 | 0.00 | 0.37 |
Annual Sum or Average | 0.697915E+09 | 0.101083E+12 | 0.00 | 0.129267E+09 | 0.401554E+11 | 0.00 | 0.961396E+10 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.312503E+09 | 0.00 | 0.00 | 0.134702E+09 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.241811E+09 | 0.204679E+11 | 0.00 | 37315228.81 | 0.993086E+10 | 0.00 | 0.366776E+10 | 0.00 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.610310E+09 | 0.326047E+09 | 0.00 | 16938890.20 | 0.140799E+09 | 0.00 | 0.215980E+10 | 0.00 | 0.31 |
February | 0.331868E+09 | 0.868029E+09 | 0.00 | 12914050.37 | 0.178650E+09 | 0.00 | 0.112063E+10 | 0.00 | 0.31 |
March | 0.278858E+09 | 0.176211E+10 | 0.00 | 13001376.65 | 0.218782E+09 | 0.00 | 0.934175E+09 | 0.00 | 0.32 |
April | 0.119084E+09 | 0.362646E+10 | 0.00 | 4847407.93 | 0.106698E+10 | 0.00 | 0.363491E+09 | 0.00 | 0.31 |
May | 29487934.99 | 0.770597E+10 | 0.00 | 1442409.28 | 0.273956E+10 | 0.00 | 70818144.04 | 0.00 | 0.33 |
June | 6400385.00 | 0.126855E+11 | 0.00 | 321046.68 | 0.449437E+10 | 0.00 | 15127500.03 | 0.00 | 0.34 |
July | 4276720.04 | 0.165590E+11 | 0.00 | 0.00 | 0.906953E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.191966E+11 | 0.00 | 0.00 | 0.804907E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
September | 460154.95 | 0.144048E+11 | 0.00 | 125300.78 | 0.492495E+10 | 0.00 | 3329815.57 | 0.00 | 0.33 |
October | 35634883.15 | 0.887849E+10 | 0.00 | 1099362.82 | 0.272648E+10 | 0.00 | 56811523.87 | 0.00 | 0.31 |
November | 31904396.52 | 0.471828E+10 | 0.00 | 2695657.64 | 0.631107E+09 | 0.00 | 87992143.18 | 0.00 | 0.30 |
December | 0.295983E+09 | 0.141917E+10 | 0.00 | 13419753.81 | 0.308717E+09 | 0.00 | 0.978616E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.174427E+10 | 0.921504E+11 | 0.00 | 66805256.16 | 0.345490E+11 | 0.00 | 0.579079E+10 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.326047E+09 | 0.00 | 0.00 | 0.140799E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.610310E+09 | 0.191966E+11 | 0.00 | 16938890.20 | 0.906953E+10 | 0.00 | 0.215980E+10 | 0.00 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.959625E+09 | 0.331654E+09 | 0.00 | 11243045.21 | 0.199249E+09 | 0.00 | 0.129824E+10 | 0.00 | 0.30 |
February | 0.476745E+09 | 0.908253E+09 | 0.00 | 9457123.49 | 0.196657E+09 | 0.00 | 0.698483E+09 | 0.00 | 0.30 |
March | 0.319398E+09 | 0.179495E+10 | 0.00 | 9140675.48 | 0.200172E+09 | 0.00 | 0.625811E+09 | 0.00 | 0.32 |
April | 0.123511E+09 | 0.360010E+10 | 0.00 | 3592850.10 | 0.102896E+10 | 0.00 | 0.215220E+09 | 0.00 | 0.31 |
May | 25295372.60 | 0.757732E+10 | 0.00 | 1150739.83 | 0.274312E+10 | 0.00 | 46239256.78 | 0.00 | 0.33 |
June | 6851760.92 | 0.126030E+11 | 0.00 | 382705.50 | 0.443234E+10 | 0.00 | 15069287.79 | 0.00 | 0.35 |
July | 1292679.53 | 0.165695E+11 | 0.00 | 0.00 | 0.946580E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.190705E+11 | 0.00 | 0.00 | 0.876108E+10 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 260131.88 | 0.142280E+11 | 0.00 | 105107.17 | 0.516107E+10 | 0.00 | 2576926.08 | 0.00 | 0.34 |
October | 42321672.31 | 0.866843E+10 | 0.00 | 1025309.72 | 0.273564E+10 | 0.00 | 32460375.61 | 0.00 | 0.31 |
November | 24290796.75 | 0.475534E+10 | 0.00 | 2123105.59 | 0.633645E+09 | 0.00 | 54761808.49 | 0.00 | 0.30 |
December | 0.414776E+09 | 0.142979E+10 | 0.00 | 8558088.01 | 0.408633E+09 | 0.00 | 0.508357E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.239437E+10 | 0.915369E+11 | 0.00 | 46778750.09 | 0.359664E+11 | 0.00 | 0.349722E+10 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.331654E+09 | 0.00 | 0.00 | 0.196657E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.959625E+09 | 0.190705E+11 | 0.00 | 11243045.21 | 0.946580E+10 | 0.00 | 0.129824E+10 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.282970E+09 | 66696504.98 | 0.00 | 1888301.60 | 48133396.24 | 0.00 | 0.177644E+09 | 0.00 | 0.30 |
February | 0.127681E+09 | 0.194263E+09 | 0.00 | 2036880.87 | 66100023.71 | 0.00 | 0.127033E+09 | 0.00 | 0.32 |
March | 92089787.49 | 0.507441E+09 | 0.00 | 2004809.84 | 42322461.63 | 0.00 | 0.118395E+09 | 0.00 | 0.37 |
April | 41748157.23 | 0.126357E+10 | 0.00 | 824608.56 | 0.148077E+09 | 0.00 | 31562091.43 | 0.00 | 0.42 |
May | 4770927.19 | 0.332821E+10 | 0.00 | 307079.75 | 0.269216E+09 | 0.00 | 11783318.59 | 0.00 | 0.54 |
June | 1080007.47 | 0.590366E+10 | 0.00 | 129634.68 | 0.415912E+09 | 0.00 | 4194720.26 | 0.00 | 0.59 |
July | 157691.06 | 0.850963E+10 | 0.00 | 3895.37 | 0.896662E+09 | 0.00 | 122637.07 | 0.00 | 0.66 |
August | 0.00 | 0.905312E+10 | 0.00 | 0.00 | 0.935234E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
September | 54941.62 | 0.601275E+10 | 0.00 | 22119.50 | 0.568175E+09 | 0.00 | 568945.74 | 0.00 | 0.54 |
October | 9261266.93 | 0.300374E+10 | 0.00 | 333025.33 | 0.390780E+09 | 0.00 | 7629163.73 | 0.00 | 0.44 |
November | 6381705.11 | 0.129475E+10 | 0.00 | 520214.46 | 0.135691E+09 | 0.00 | 12977065.61 | 0.00 | 0.36 |
December | 0.104991E+09 | 0.321046E+09 | 0.00 | 1690343.91 | 0.101811E+09 | 0.00 | 89426812.24 | 0.00 | 0.31 |
Annual Sum or Average | 0.671187E+09 | 0.394589E+11 | 0.00 | 9760913.87 | 0.401811E+10 | 0.00 | 0.581336E+09 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 66696504.98 | 0.00 | 0.00 | 42322461.63 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.282970E+09 | 0.905312E+10 | 0.00 | 2036880.87 | 0.935234E+09 | 0.00 | 0.177644E+09 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143321E+09 | 62317730.61 | 0.00 | 1974217.43 | 25194978.34 | 0.00 | 0.199785E+09 | 0.00 | 0.36 |
February | 68177139.56 | 0.163179E+09 | 0.00 | 1924278.71 | 27582310.97 | 0.00 | 0.125459E+09 | 0.00 | 0.40 |
March | 50878950.77 | 0.420417E+09 | 0.00 | 1769406.52 | 20475707.22 | 0.00 | 0.103467E+09 | 0.00 | 0.47 |
April | 23379083.67 | 0.105854E+10 | 0.00 | 843057.27 | 65442231.70 | 0.00 | 32817471.96 | 0.00 | 0.55 |
May | 2454276.00 | 0.257764E+10 | 0.00 | 260877.06 | 0.141467E+09 | 0.00 | 9194613.70 | 0.00 | 0.66 |
June | 682298.43 | 0.442129E+10 | 0.00 | 106336.55 | 0.245429E+09 | 0.00 | 3024963.07 | 0.00 | 0.70 |
July | 99664.20 | 0.631931E+10 | 0.00 | 3318.67 | 0.516694E+09 | 0.00 | 102848.58 | 0.00 | 0.77 |
August | 0.00 | 0.686894E+10 | 0.00 | 0.00 | 0.534211E+09 | 0.00 | 0.00 | 0.00 | 0.77 |
September | 34724.30 | 0.469695E+10 | 0.00 | 14842.80 | 0.296971E+09 | 0.00 | 367158.30 | 0.00 | 0.66 |
October | 3189424.28 | 0.249549E+10 | 0.00 | 521475.42 | 0.180173E+09 | 0.00 | 11906713.83 | 0.00 | 0.55 |
November | 3250396.04 | 0.106669E+10 | 0.00 | 432498.41 | 64509058.07 | 0.00 | 10394917.27 | 0.00 | 0.45 |
December | 54539061.31 | 0.270168E+09 | 0.00 | 1516286.97 | 50487732.06 | 0.00 | 86198120.42 | 0.00 | 0.37 |
Annual Sum or Average | 0.350006E+09 | 0.304209E+11 | 0.00 | 9366595.81 | 0.216864E+10 | 0.00 | 0.582718E+09 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 62317730.61 | 0.00 | 0.00 | 20475707.22 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.143321E+09 | 0.686894E+10 | 0.00 | 1974217.43 | 0.534211E+09 | 0.00 | 0.199785E+09 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.209822E+09 | 0.170911E+09 | 0.00 | 5013275.39 | 19127289.02 | 0.00 | 0.488070E+09 | 0.00 | 0.49 |
February | 0.106720E+09 | 0.347788E+09 | 0.00 | 4295191.57 | 24755617.13 | 0.00 | 0.264144E+09 | 0.00 | 0.49 |
March | 83825152.65 | 0.695159E+09 | 0.00 | 3132854.81 | 28625042.10 | 0.00 | 0.184332E+09 | 0.00 | 0.49 |
April | 40427784.01 | 0.148715E+10 | 0.00 | 963943.02 | 0.119526E+09 | 0.00 | 35170440.48 | 0.00 | 0.48 |
May | 4754976.55 | 0.331356E+10 | 0.00 | 306645.77 | 0.275295E+09 | 0.00 | 11684153.79 | 0.00 | 0.54 |
June | 1076396.68 | 0.561396E+10 | 0.00 | 125354.77 | 0.447322E+09 | 0.00 | 4136346.54 | 0.00 | 0.57 |
July | 157163.86 | 0.837210E+10 | 0.00 | 3612.09 | 0.923682E+09 | 0.00 | 116160.92 | 0.00 | 0.65 |
August | 0.00 | 0.952582E+10 | 0.00 | 0.00 | 0.912162E+09 | 0.00 | 0.00 | 0.00 | 0.68 |
September | 54757.93 | 0.719385E+10 | 0.00 | 23095.81 | 0.483398E+09 | 0.00 | 576769.37 | 0.00 | 0.63 |
October | 5827144.88 | 0.427650E+10 | 0.00 | 942260.34 | 0.246133E+09 | 0.00 | 17224399.72 | 0.00 | 0.60 |
November | 5325005.87 | 0.209533E+10 | 0.00 | 963687.63 | 64015686.88 | 0.00 | 22906363.72 | 0.00 | 0.56 |
December | 81231771.85 | 0.669281E+09 | 0.00 | 4015515.75 | 42739923.98 | 0.00 | 0.215458E+09 | 0.00 | 0.50 |
Annual Sum or Average | 0.539221E+09 | 0.437614E+11 | 0.00 | 19785436.96 | 0.358678E+10 | 0.00 | 0.124382E+10 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 0.170911E+09 | 0.00 | 0.00 | 19127289.02 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.209822E+09 | 0.952582E+10 | 0.00 | 5013275.39 | 0.923682E+09 | 0.00 | 0.488070E+09 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.165162E+09 | 64800022.39 | 0.00 | 1855859.57 | 23716698.57 | 0.00 | 0.176403E+09 | 0.00 | 0.36 |
February | 76304013.65 | 0.173586E+09 | 0.00 | 1946467.18 | 26573904.60 | 0.00 | 0.124575E+09 | 0.00 | 0.40 |
March | 55926179.51 | 0.435624E+09 | 0.00 | 1806186.34 | 16978963.53 | 0.00 | 0.113448E+09 | 0.00 | 0.48 |
April | 25784832.98 | 0.109704E+10 | 0.00 | 625765.95 | 64745820.94 | 0.00 | 22315232.78 | 0.00 | 0.53 |
May | 2883614.06 | 0.267290E+10 | 0.00 | 221158.11 | 0.131924E+09 | 0.00 | 8074490.38 | 0.00 | 0.65 |
June | 584923.00 | 0.455959E+10 | 0.00 | 86969.47 | 0.218894E+09 | 0.00 | 2893528.04 | 0.00 | 0.70 |
July | 99879.45 | 0.645975E+10 | 0.00 | 2849.50 | 0.483986E+09 | 0.00 | 88331.75 | 0.00 | 0.76 |
August | 0.00 | 0.705520E+10 | 0.00 | 0.00 | 0.501955E+09 | 0.00 | 0.00 | 0.00 | 0.77 |
September | 34799.30 | 0.490407E+10 | 0.00 | 15218.55 | 0.272303E+09 | 0.00 | 371457.99 | 0.00 | 0.65 |
October | 5686611.75 | 0.247340E+10 | 0.00 | 245073.11 | 0.177663E+09 | 0.00 | 5311786.21 | 0.00 | 0.54 |
November | 4042088.12 | 0.106020E+10 | 0.00 | 454442.89 | 61075927.03 | 0.00 | 12011171.90 | 0.00 | 0.45 |
December | 62156551.33 | 0.284031E+09 | 0.00 | 1546168.05 | 50591972.75 | 0.00 | 86549610.58 | 0.00 | 0.37 |
Annual Sum or Average | 0.398666E+09 | 0.312402E+11 | 0.00 | 8806158.73 | 0.203041E+10 | 0.00 | 0.552042E+09 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 64800022.39 | 0.00 | 0.00 | 16978963.53 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.165162E+09 | 0.705520E+10 | 0.00 | 1946467.18 | 0.501955E+09 | 0.00 | 0.176403E+09 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.199989E+09 | 48201980.37 | 0.00 | 3314799.46 | 28605131.12 | 0.00 | 0.290046E+09 | 0.00 | 0.26 |
February | 0.115417E+09 | 0.168583E+09 | 0.00 | 2546006.97 | 34764961.10 | 0.00 | 0.154682E+09 | 0.00 | 0.26 |
March | 96365551.73 | 0.384022E+09 | 0.00 | 2225947.57 | 45650067.68 | 0.00 | 0.123746E+09 | 0.00 | 0.29 |
April | 43822986.65 | 0.939693E+09 | 0.00 | 721080.11 | 0.227848E+09 | 0.00 | 36602273.54 | 0.00 | 0.33 |
May | 5908106.26 | 0.269855E+10 | 0.00 | 275028.81 | 0.374493E+09 | 0.00 | 11624796.55 | 0.00 | 0.42 |
June | 838805.01 | 0.482644E+10 | 0.00 | 62434.37 | 0.519376E+09 | 0.00 | 2504065.18 | 0.00 | 0.48 |
July | 567769.97 | 0.730069E+10 | 0.00 | 2419.38 | 0.110039E+10 | 0.00 | 93062.28 | 0.00 | 0.56 |
August | 0.00 | 0.822888E+10 | 0.00 | 0.00 | 0.121187E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 29026.18 | 0.557410E+10 | 0.00 | 22233.94 | 0.829906E+09 | 0.00 | 152908.83 | 0.00 | 0.49 |
October | 6627342.52 | 0.292014E+10 | 0.00 | 255471.18 | 0.568013E+09 | 0.00 | 12398873.35 | 0.00 | 0.42 |
November | 8754651.70 | 0.118606E+10 | 0.00 | 630826.47 | 0.168328E+09 | 0.00 | 15060092.30 | 0.00 | 0.33 |
December | 89883155.83 | 0.268187E+09 | 0.00 | 3200870.20 | 79006628.63 | 0.00 | 0.170956E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.568203E+09 | 0.345435E+11 | 0.00 | 13257118.46 | 0.518825E+10 | 0.00 | 0.817866E+09 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 48201980.37 | 0.00 | 0.00 | 28605131.12 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.199989E+09 | 0.822888E+10 | 0.00 | 3314799.46 | 0.121187E+10 | 0.00 | 0.290046E+09 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 90279065.61 | 40989387.31 | 0.00 | 3369755.17 | 17506483.85 | 0.00 | 0.292549E+09 | 0.00 | 0.33 |
February | 58892285.51 | 0.131954E+09 | 0.00 | 2543112.96 | 18105511.82 | 0.00 | 0.153045E+09 | 0.00 | 0.34 |
March | 49068999.59 | 0.321786E+09 | 0.00 | 2115178.24 | 23570073.25 | 0.00 | 0.115373E+09 | 0.00 | 0.37 |
April | 22347595.55 | 0.844006E+09 | 0.00 | 776236.04 | 90160419.56 | 0.00 | 38925795.86 | 0.00 | 0.43 |
May | 2646828.39 | 0.221540E+10 | 0.00 | 263149.41 | 0.159564E+09 | 0.00 | 10013008.69 | 0.00 | 0.53 |
June | 501864.90 | 0.375472E+10 | 0.00 | 47355.61 | 0.253407E+09 | 0.00 | 1881451.96 | 0.00 | 0.57 |
July | 358179.51 | 0.567597E+10 | 0.00 | 2465.13 | 0.563568E+09 | 0.00 | 60442.76 | 0.00 | 0.66 |
August | 0.00 | 0.647547E+10 | 0.00 | 0.00 | 0.639887E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
September | 13298.14 | 0.451798E+10 | 0.00 | 16594.44 | 0.389460E+09 | 0.00 | 117683.71 | 0.00 | 0.61 |
October | 2350769.32 | 0.248927E+10 | 0.00 | 324399.14 | 0.244480E+09 | 0.00 | 14090507.32 | 0.00 | 0.52 |
November | 4002154.34 | 0.960884E+09 | 0.00 | 558627.81 | 79012620.12 | 0.00 | 14663592.95 | 0.00 | 0.41 |
December | 42648520.83 | 0.210671E+09 | 0.00 | 2833867.42 | 48427995.45 | 0.00 | 0.158294E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.273110E+09 | 0.276391E+11 | 0.00 | 12850741.37 | 0.252715E+10 | 0.00 | 0.799014E+09 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 40989387.31 | 0.00 | 0.00 | 17506483.85 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 90279065.61 | 0.647547E+10 | 0.00 | 3369755.17 | 0.639887E+09 | 0.00 | 0.292549E+09 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.165653E+09 | 0.112767E+09 | 0.00 | 5661443.01 | 12527849.13 | 61877255.24 | 0.421548E+09 | 0.00 | 0.38 |
February | 94388007.60 | 0.305385E+09 | 0.00 | 4394120.94 | 17374080.45 | 29790462.89 | 0.236247E+09 | 0.00 | 0.40 |
March | 89752170.99 | 0.645233E+09 | 0.00 | 3182284.28 | 31497362.23 | 10890294.83 | 0.162813E+09 | 0.00 | 0.42 |
April | 49502330.66 | 0.139930E+10 | 0.00 | 870047.43 | 0.180641E+09 | 46435.64 | 34842551.69 | 0.00 | 0.43 |
May | 6154886.35 | 0.350941E+10 | 0.00 | 351113.60 | 0.383749E+09 | 0.00 | 13174835.34 | 0.00 | 0.54 |
June | 840267.96 | 0.591711E+10 | 0.00 | 68413.03 | 0.609067E+09 | 0.00 | 2720032.39 | 0.00 | 0.59 |
July | 568760.20 | 0.923788E+10 | 0.00 | 3271.65 | 0.112187E+10 | 0.00 | 92376.54 | 0.00 | 0.69 |
August | 0.00 | 0.113111E+11 | 0.00 | 0.00 | 0.110462E+10 | 0.00 | 0.00 | 0.00 | 0.77 |
September | 21116.38 | 0.834770E+10 | 0.00 | 30370.23 | 0.611671E+09 | 0.00 | 209037.98 | 0.00 | 0.69 |
October | 4255776.89 | 0.507576E+10 | 0.00 | 552425.59 | 0.289106E+09 | 0.00 | 20045501.51 | 0.00 | 0.65 |
November | 10100982.28 | 0.221870E+10 | 0.00 | 929806.72 | 64960341.61 | 0.00 | 19316156.49 | 0.00 | 0.54 |
December | 83102451.99 | 0.548306E+09 | 0.00 | 5209812.85 | 35481308.16 | 11460546.04 | 0.262933E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.504340E+09 | 0.486286E+11 | 0.00 | 21253109.35 | 0.446257E+10 | 0.114065E+09 | 0.117394E+10 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.112767E+09 | 0.00 | 0.00 | 12527849.13 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.165653E+09 | 0.113111E+11 | 0.00 | 5661443.01 | 0.112187E+10 | 61877255.24 | 0.421548E+09 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.113420E+09 | 43837130.77 | 0.00 | 3032244.46 | 16424736.38 | 0.00 | 0.255302E+09 | 0.00 | 0.32 |
February | 67989136.61 | 0.145965E+09 | 0.00 | 2355318.83 | 16378881.39 | 0.00 | 0.141533E+09 | 0.00 | 0.34 |
March | 52347542.86 | 0.352560E+09 | 0.00 | 2049082.89 | 15817782.58 | 0.00 | 0.118881E+09 | 0.00 | 0.38 |
April | 21287436.12 | 0.901137E+09 | 0.00 | 580741.20 | 75926373.74 | 0.00 | 32394627.14 | 0.00 | 0.41 |
May | 3067466.96 | 0.233563E+10 | 0.00 | 222283.49 | 0.130315E+09 | 0.00 | 8949518.46 | 0.00 | 0.52 |
June | 367174.82 | 0.394880E+10 | 0.00 | 50502.37 | 0.201833E+09 | 0.00 | 2104817.86 | 0.00 | 0.58 |
July | 359403.80 | 0.584772E+10 | 0.00 | 3166.11 | 0.521199E+09 | 0.00 | 75809.86 | 0.00 | 0.67 |
August | 0.00 | 0.670441E+10 | 0.00 | 0.00 | 0.582437E+09 | 0.00 | 0.00 | 0.00 | 0.71 |
September | 13343.60 | 0.476343E+10 | 0.00 | 17518.73 | 0.338164E+09 | 0.00 | 122317.92 | 0.00 | 0.61 |
October | 4093827.52 | 0.253845E+10 | 0.00 | 201918.84 | 0.220897E+09 | 0.00 | 8881513.42 | 0.00 | 0.52 |
November | 4568071.89 | 0.998647E+09 | 0.00 | 525751.59 | 66640552.37 | 0.00 | 12761955.80 | 0.00 | 0.41 |
December | 54006937.88 | 0.232754E+09 | 0.00 | 2673275.66 | 43126365.87 | 0.00 | 0.143772E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.321520E+09 | 0.288133E+11 | 0.00 | 11711804.16 | 0.222916E+10 | 0.00 | 0.724779E+09 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 43837130.77 | 0.00 | 0.00 | 15817782.58 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.113420E+09 | 0.670441E+10 | 0.00 | 3032244.46 | 0.582437E+09 | 0.00 | 0.255302E+09 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.297040E+09 | 67079664.54 | 0.00 | 2330043.27 | 34721922.21 | 0.00 | 0.230591E+09 | 0.00 | 0.29 |
February | 0.147223E+09 | 0.206735E+09 | 0.00 | 2225708.15 | 43593545.14 | 0.00 | 0.147326E+09 | 0.00 | 0.32 |
March | 0.109468E+09 | 0.516306E+09 | 0.00 | 2337498.70 | 42239066.88 | 0.00 | 0.140479E+09 | 0.00 | 0.37 |
April | 45019864.85 | 0.127105E+10 | 0.00 | 892986.52 | 0.186506E+09 | 0.00 | 52797256.63 | 0.00 | 0.42 |
May | 6878804.24 | 0.337292E+10 | 0.00 | 370818.65 | 0.298124E+09 | 0.00 | 16093002.28 | 0.00 | 0.53 |
June | 1135626.54 | 0.587557E+10 | 0.00 | 97468.36 | 0.415368E+09 | 0.00 | 3898261.48 | 0.00 | 0.58 |
July | 727900.10 | 0.839152E+10 | 0.00 | 11554.14 | 0.866143E+09 | 0.00 | 208563.96 | 0.00 | 0.63 |
August | 0.00 | 0.904656E+10 | 0.00 | 0.00 | 0.893783E+09 | 0.00 | 0.00 | 0.00 | 0.63 |
September | 97238.15 | 0.600186E+10 | 0.00 | 25815.73 | 0.581073E+09 | 0.00 | 721373.75 | 0.00 | 0.52 |
October | 8869179.81 | 0.300598E+10 | 0.00 | 286684.02 | 0.440114E+09 | 0.00 | 10710405.49 | 0.00 | 0.44 |
November | 11978700.62 | 0.128634E+10 | 0.00 | 472410.44 | 0.139548E+09 | 0.00 | 12847091.80 | 0.00 | 0.36 |
December | 0.129209E+09 | 0.325957E+09 | 0.00 | 2101084.52 | 74471365.26 | 0.00 | 0.124079E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.757647E+09 | 0.393679E+11 | 0.00 | 11152072.51 | 0.401569E+10 | 0.00 | 0.739750E+09 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 67079664.54 | 0.00 | 0.00 | 34721922.21 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.297040E+09 | 0.904656E+10 | 0.00 | 2337498.70 | 0.893783E+09 | 0.00 | 0.230591E+09 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.145504E+09 | 51136628.39 | 0.00 | 2181630.98 | 19633537.35 | 0.00 | 0.230232E+09 | 0.00 | 0.34 |
February | 77775459.63 | 0.155030E+09 | 0.00 | 2008814.73 | 16967051.92 | 0.00 | 0.138101E+09 | 0.00 | 0.37 |
March | 59279966.91 | 0.393161E+09 | 0.00 | 1979191.97 | 22564943.74 | 0.00 | 0.118080E+09 | 0.00 | 0.44 |
April | 26015022.80 | 0.103162E+10 | 0.00 | 851019.85 | 68678133.10 | 0.00 | 47945634.67 | 0.00 | 0.52 |
May | 3101578.06 | 0.254122E+10 | 0.00 | 326485.96 | 0.149659E+09 | 0.00 | 13614988.27 | 0.00 | 0.63 |
June | 701221.71 | 0.427387E+10 | 0.00 | 76775.16 | 0.235380E+09 | 0.00 | 2757422.51 | 0.00 | 0.66 |
July | 435100.04 | 0.609064E+10 | 0.00 | 11135.10 | 0.485830E+09 | 0.00 | 193199.72 | 0.00 | 0.72 |
August | 0.00 | 0.670796E+10 | 0.00 | 0.00 | 0.495233E+09 | 0.00 | 0.00 | 0.00 | 0.73 |
September | 52853.80 | 0.456994E+10 | 0.00 | 17367.58 | 0.284555E+09 | 0.00 | 473523.98 | 0.00 | 0.62 |
October | 2944453.94 | 0.240323E+10 | 0.00 | 392751.16 | 0.196493E+09 | 0.00 | 13885086.73 | 0.00 | 0.52 |
November | 5906320.33 | 0.979626E+09 | 0.00 | 414908.81 | 68530525.24 | 0.00 | 12251328.81 | 0.00 | 0.42 |
December | 66711179.00 | 0.237206E+09 | 0.00 | 1781865.14 | 42254940.94 | 0.00 | 0.111425E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.388427E+09 | 0.294347E+11 | 0.00 | 10041946.43 | 0.208578E+10 | 0.00 | 0.688959E+09 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 51136628.39 | 0.00 | 0.00 | 16967051.92 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.145504E+09 | 0.670796E+10 | 0.00 | 2181630.98 | 0.495233E+09 | 0.00 | 0.230232E+09 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.215592E+09 | 0.162108E+09 | 0.00 | 5678503.60 | 12960620.77 | 0.00 | 0.554181E+09 | 0.00 | 0.48 |
February | 0.125653E+09 | 0.358492E+09 | 0.00 | 4401264.93 | 12353961.39 | 0.00 | 0.284130E+09 | 0.00 | 0.48 |
March | 0.101182E+09 | 0.722506E+09 | 0.00 | 3481147.28 | 27395458.11 | 0.00 | 0.205069E+09 | 0.00 | 0.49 |
April | 44081761.86 | 0.153753E+10 | 0.00 | 988658.89 | 0.132257E+09 | 0.00 | 55878890.66 | 0.00 | 0.48 |
May | 7033091.85 | 0.335601E+10 | 0.00 | 363433.73 | 0.316196E+09 | 0.00 | 15687462.01 | 0.00 | 0.53 |
June | 1136239.81 | 0.557189E+10 | 0.00 | 93547.22 | 0.467710E+09 | 0.00 | 3849492.79 | 0.00 | 0.55 |
July | 728293.19 | 0.820850E+10 | 0.00 | 10479.51 | 0.944555E+09 | 0.00 | 203096.79 | 0.00 | 0.62 |
August | 0.00 | 0.955462E+10 | 0.00 | 0.00 | 0.870411E+09 | 0.00 | 0.00 | 0.00 | 0.66 |
September | 83983.88 | 0.729792E+10 | 0.00 | 26918.03 | 0.458621E+09 | 0.00 | 747521.86 | 0.00 | 0.61 |
October | 6400644.42 | 0.437539E+10 | 0.00 | 610629.85 | 0.261688E+09 | 0.00 | 17006449.23 | 0.00 | 0.60 |
November | 9920450.41 | 0.209670E+10 | 0.00 | 869961.44 | 54146981.45 | 0.00 | 22879013.39 | 0.00 | 0.55 |
December | 0.102849E+09 | 0.648241E+09 | 0.00 | 4716463.64 | 33542767.05 | 0.00 | 0.265059E+09 | 0.00 | 0.50 |
Annual Sum or Average | 0.614660E+09 | 0.438899E+11 | 0.00 | 21241008.11 | 0.359184E+10 | 0.00 | 0.142469E+10 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.162108E+09 | 0.00 | 0.00 | 12353961.39 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.215592E+09 | 0.955462E+10 | 0.00 | 5678503.60 | 0.944555E+09 | 0.00 | 0.554181E+09 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.168263E+09 | 62830567.90 | 0.00 | 2176677.81 | 17524151.06 | 0.00 | 0.217175E+09 | 0.00 | 0.35 |
February | 87100312.83 | 0.181385E+09 | 0.00 | 2029467.92 | 15696468.80 | 0.00 | 0.136979E+09 | 0.00 | 0.39 |
March | 66471774.46 | 0.455437E+09 | 0.00 | 2005611.08 | 15405152.26 | 0.00 | 0.126207E+09 | 0.00 | 0.47 |
April | 27946349.86 | 0.115314E+10 | 0.00 | 643864.63 | 63938220.81 | 0.00 | 35347399.41 | 0.00 | 0.53 |
May | 3769464.49 | 0.278312E+10 | 0.00 | 259133.57 | 0.132150E+09 | 0.00 | 11232617.06 | 0.00 | 0.64 |
June | 667406.41 | 0.463023E+10 | 0.00 | 65767.02 | 0.200645E+09 | 0.00 | 2665771.08 | 0.00 | 0.69 |
July | 416489.98 | 0.647976E+10 | 0.00 | 9764.81 | 0.450165E+09 | 0.00 | 204884.29 | 0.00 | 0.74 |
August | 0.00 | 0.716320E+10 | 0.00 | 0.00 | 0.461931E+09 | 0.00 | 0.00 | 0.00 | 0.76 |
September | 53108.20 | 0.498902E+10 | 0.00 | 17856.22 | 0.251440E+09 | 0.00 | 479844.61 | 0.00 | 0.64 |
October | 5401813.44 | 0.252935E+10 | 0.00 | 195184.69 | 0.184180E+09 | 0.00 | 7276488.14 | 0.00 | 0.54 |
November | 7331760.57 | 0.106635E+10 | 0.00 | 406391.74 | 54908385.78 | 0.00 | 11275930.36 | 0.00 | 0.44 |
December | 77136996.52 | 0.281522E+09 | 0.00 | 1827021.06 | 40283746.20 | 0.00 | 0.109826E+09 | 0.00 | 0.37 |
Annual Sum or Average | 0.444558E+09 | 0.317754E+11 | 0.00 | 9636740.54 | 0.188827E+10 | 0.00 | 0.658670E+09 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 62830567.90 | 0.00 | 0.00 | 15405152.26 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.168263E+09 | 0.716320E+10 | 0.00 | 2176677.81 | 0.461931E+09 | 0.00 | 0.217175E+09 | 0.00 | 0.76 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:02
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.148071E+12 | 0.284620E+10 | 0.00 | 0.241058E+11 | 0.119805E+12 |
February | 0.162418E+12 | 0.118818E+10 | 0.00 | 0.792424E+10 | 0.135533E+12 |
March | 0.198467E+12 | -747914535.5 | 0.00 | -0.446350E+10 | 0.191954E+12 |
April | 0.208109E+12 | -0.483843E+10 | 0.00 | -0.388805E+11 | 0.242447E+12 |
May | 0.215509E+12 | -0.114655E+11 | 0.00 | -0.956022E+11 | 0.380571E+12 |
June | 0.205073E+12 | -0.189119E+11 | 0.00 | -0.157460E+12 | 0.465433E+12 |
July | 0.201912E+12 | -0.256363E+11 | 0.00 | -0.218824E+12 | 0.570196E+12 |
August | 0.196424E+12 | -0.274627E+11 | 0.00 | -0.235200E+12 | 0.619198E+12 |
September | 0.176366E+12 | -0.201754E+11 | 0.00 | -0.181275E+12 | 0.479492E+12 |
October | 0.153986E+12 | -0.117796E+11 | 0.00 | -0.110874E+12 | 0.369152E+12 |
November | 0.127005E+12 | -0.518973E+10 | 0.00 | -0.458888E+11 | 0.251446E+12 |
December | 0.127595E+12 | 0.359671E+09 | 0.00 | -0.124398E+10 | 0.155938E+12 |
Annual Sum or Average | 0.212093E+13 | -0.121814E+12 | 0.00 | -0.105768E+13 | 0.398117E+13 |
Minimum of Months | 0.127005E+12 | -0.274627E+11 | 0.00 | -0.235200E+12 | 0.119805E+12 |
Maximum of Months | 0.215509E+12 | 0.284620E+10 | 0.00 | 0.241058E+11 | 0.619198E+12 |